LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
STANDARD FEATURES
TANDEM COMPRESSORS - Scroll with a suction gas cooled motor, vibration isolators, thermal overloads, manual reset high-pressure switch and pump
down low-pressure switch.
REFRIGERATION SYSTEM - Dual R-407C refrigeration circuits each including liquid line filter dryers, refrigerant sight glass with moisture indicator,
electronic control valve, adjustable externally equalized expansion valves and liquid line solenoid valves.
HEAT EXCHANGER - Brazed plate design with interwoven circuiting constructed of stainless steel plates, copper brazed.
PUMPS - Centrifugal type. Uses R-134a.
STANDARD CONTROL PROCESSOR - The standard control system is microprocessor-based with an external LCD numerical display to allow
observation of specified settable functions. Normal operating conditions are indicated on the LCD display panel, which is mounted to the unit. The control
system also monitors unit operation and activates an alarm when any of the specified factory preset conditions are exceeded.
CABINET AND FRAME - Custom powder painted steel panels. A hinged control access panel opens to a second front panel, which is a protected
enclosure for all high voltage components. Frame is constructed of 14 gauge heli-arc welded tubular steel and painted using an auto-deposition coating
system.
CANBUS ISOLATOR - Electrically isolates external CANBUS from internal CANBUS. Allows for greater total length of external CANBUS cables.
REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.
DPN001599
PAGE 1/6
REV 12/11
REV 4
Download from Www.Somanuals.com. All Manuals Search And Download.
LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
To First Cooling Module or
Bypass Flow Controller **
Install Replaceable Filter Drier Assembly
in Liquid Supply Line
22in
559mm
Orientation
Defined by
Installer.*
21in
533mm
3 1/4in
83mm
Return Line From
Cooling Units
(line is spin closed)
(elbow customer provided)
8in
203mm
A
*
Liquid Supply Line
To Cooling Units
B
DIMENSIONS ARE SUBJECT
TO CHANGE WITHOUT NOTICE.
47in
1194 mm
44in
~
1118 mm
6in
152 mm
23in
584 mm
* Allow 8in (204mm) Of Clearance For Filter Replacement.
Filter assembly may be positioned horizontally.
** To Ensure All Refrigerant Flow is Filtered, Install the Filter
Drier Assembly Between the Discharge Line of the Liebert
XDC and the first Bypass Flow Controller or the first
Liebert XD Cooling Module.
Hot Gas Refrigerant Lines
C
Liquid Refrigerant Lines
D
UNIT PIPING OUTLET CONNECTION SIZES, inches
MODEL
A
B
C
D
50/60 HZ
XDC160
OD CU OD CU OD CU OD CU
2-1/8 1-1/8 1-3/8 7/8
REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.
DPN001599
PAGE 3/6
REV 12/11
REV 4
Download from Www.Somanuals.com. All Manuals Search And Download.
LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
Bypass Flow Control Assembly
Return Main
Field Supplied and
Field Installed
LIEBERT
XD
Bypass Flow Controller
Factory Supplied and
Field Installed
Field Supplied and
Field Installed
COOLING
MODULE
Ball Valve
Supply Main
RETURN
Flow Direction
Must be toward
Return Main.
Install Bypass Flow Control Assembly
between the Liebert XDC and first
Liebert XD Cooling module. See System
Design Manual SL-16655 for quantity
required.
SUPPLY
Replaceable
Filter Drier
Assembly
Install Replaceable
Filter Drier Assembly
in liquid supply line
RETURN
SUPPLY
LIEBERT XDC
Factory Piping
Field Piping
REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.
DPN001599
PAGE 4/6
REV 12/11
REV 4
Download from Www.Somanuals.com. All Manuals Search And Download.
LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
Three phase electric
Factory installed unit
service not provided
disconnect switches
by Liebert.
iCOM display
Field supplied disconnect
switch may not be required,
check local codes.
Three phase electric service
not by Liebert.
HEAT REJECTION CONNECTION (R-407C Side)
Field supplied 24V. Class 1 wiring to
interlock heat rejection from pigtails:
70A & 71A - Compressor 1 circuit
70B & 71B - Compressor 2 circuit
70C & 71C - Dual Cool relay (optional)
ELECTRIC CONDUIT KNOCKOUTS
On top of electric box. Knockout size
2 in (51 mm)
EARTH GROUND CONNECTION
Connection terminal for field supplied
earth grounding wire.
Electrical handy box factory
installed with cover.
THREE PHASE CONNECTION
Electric service connection terminals
CANBUS ISOLATOR
ALARM AND WARNING OUTPUT RELAYS
Field supplied 24V Class 2 wire for
special alarms.
Factory wired to components
on electric panel
(Not to exceed 1.0A @ 24v each.)
REMOTE UNIT SHUTDOWN
Replace existing jumper between terminals
37 & 38 with normally closed switch having
a minimum 50VA rating. Use field supplied
24V Class 2 wire.
Factory installed disconnect switch
EARTH GROUND BAR (50Hz only)
Connection terminal with factory
ground from each high voltage
component
®
INTELLISLOTS
Two Liebert Intellislots for optional
OCWEB-LBDS or OC485-LBDS card.
®
60HZ COMPONENTS SHOWN
NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.
REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.
DPN001599
PAGE 5/6
REV 12/11
REV 4
Download from Www.Somanuals.com. All Manuals Search And Download.
LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
Liebert XDC Extra Low Voltage field connection points
TO P64 ON ICOM CONTROL BOARD
RED ETHER NET CABLE
TO P66 ON ICOM CONTROL BOARD
TERMINATION PLUG
TO LIEBERT XD COOLING
MODULE AND REMOTE
T/H SENSOR B
TO REMOTE T/H SENSOR A
COMMON WARNING OUTPUT
TO OPTIONAL
EXTERNAL
CONNECTIONS
FOR CONTACTS INDICATING AN
ALARM CONDITION.
(MAX) 1.0AMP @ 24V
P66 P67
P64
K11
K11
K11NO K11COM K11NC
TO REMOTE ALARM
CIRCUIT BY OTHERS
INPUT: REMOTE ALARM DEVICE
FOR INDICATION OF ALARM, WIRE
N.O. CONTACTS FROM REMOTE
ALARM DEVICE AS SHOWN.
UNIT DISPLAY (REAR VIEW)
24
50
FACTORY WIRED
TEMPERATURE SENSOR.
N.O. CONTACT BY OTHERS
P67
INPUT: CONDENSATION
DETECTION
ALARM WHEN CLOSED.
DO NOT
USE
24
51
N.O. CONTACTS REQUIRED
INPUT: FAN BREAKER STATUS
1
ALARM WHEN CLOSED.
24
54
N.O. CONTACTS REQUIRED
COMMON ALARM OUTPUT
FOR CONTACTS INDICATING AN
ALARM CONDITION.
(MAX) 1.0AMP @ 24V
K3
K3
K3NO K3COM K3NC
TO REMOTE ALARM
CIRCUIT BY OTHERS
1
INPUT: REMOTE SHUTDOWN
NOTES:
FOR SHUTDOWN OF CONTROL
CIRCUIT, REMOVE JUMPER
BETWEEN TERMINALS 37 & 38
1. CONTROL WIRING MUST BE CLASS 2 AND INSTALLED IN
AND REPLACE WITH N.C. CONTACT
ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC).
37
38
2. REQUIRES SHIELDED CABLE.
N.C. CONTACTS BY OTHERS
1
2
REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.
DPN001599
PAGE 6/6
REV 12/11
REV 4
Download from Www.Somanuals.com. All Manuals Search And Download.
|