IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE  
INSTRUCTIONS  
This manual contains important instructions that  
should be closely followed during installation and  
maintenance of this UPStation GXT 6kVA  
Maintenance Bypass.  
CAUTION  
!
To reduce the risks of fire, connect  
only to a circuit provided with  
maximum branch circuit  
overcurrent protection of 40A in  
accordance with applicable  
national and local electrical codes.  
Install the bypass equipment in a clean  
environment, free of conductive contaminants,  
moisture, flammable liquids, gases, and corrosive  
substances.  
This product is designed for commercial / industrial  
use only. This product is not intended for use with  
life support and other designated “critical” devices.  
Maximum load must not exceed that shown on the  
Maintenance Bypass Cabinet rating label.  
WARNING  
!
LETHAL VOLTAGES MAY BE  
PRESENT WITHIN THIS UNIT  
EVEN WHEN IT IS APPARENTLY  
NOT OPERATING. OBSERVE ALL  
CAUTIONS AND WARNINGS IN  
THIS MANUAL. FAILURE TO DO  
SO MAY RESULT IN SERIOUS  
INJURY OR DEATH. NEVER  
WORK ALONE.  
The UPStation GXT 6 kVA Maintenance Bypass is  
designed for use on properly grounded (earthed)  
208/240VAC 60Hz supply, for installation by  
qualified personnel. This UPS equipment is  
intended to be installed by a qualified / certified  
electrician who must review and approve customer  
supplied wiring, circuit breakers, intended loads  
and verify correct input, output and grounded  
(earth) connections to ensure compliance with  
technical standards and national and local  
electrical codes. Installation instructions and  
warning notices are in the Cable Installation  
section of this manual beginning on page 6.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
GLOSSARY OF SYMBOLS  
Risk of electrical shock  
Indicates Warning or Caution followed by important instructions  
Requests the user to consult the manual  
i
Equipment grounding conductor  
On  
Off  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
GENERAL DESCRIPTION  
Congratulations on your purchase of Liebert's  
Features  
UPStation GXT 6 kVA Maintenance Bypass. As  
with every Liebert product, we stand behind our  
quality. If you have any questions concerning this  
Maintenance Bypass, please feel free to contact  
your local sales representative, or call the  
appropriate Technical Support number listed on  
the back of this manual.  
• Supports up to 30A loads  
• Compact design  
• Highly configurable  
• Multiple power path indicators  
• High-speed, break-before-make transfer  
switch  
Standard Components  
To ensure proper installation and operation of this  
unit, please read this manual thoroughly.  
• Provisions for hardwire output  
• Power indicator lamps  
• Branch rated circuit breakers  
• Easily accessible terminal blocks  
While installation must be completed by a  
qualified / certified electrician, general operation  
may be performed without special training.  
Options  
SYSTEM DESCRIPTION  
• Field-installable output distribution kits  
The Liebert UPStation GXT 6 kVA Maintenance  
Bypass is intended for use with the UPStation GXT  
6 kVA UPS. Typical applications include  
supporting workstations, servers, network, telecom  
or other sensitive electronic equipment.  
The UPStation GXT 6 kVA Maintenance Bypass  
was designed to provide maximum system  
availability to business-critical equipment. The  
bypass allows for transfer of connected loads to an  
alternate power path, allowing full isolation of the  
UPS. After connected loads are switched to  
alternate power and the UPS is isolated, the UPS  
can be turned off and removed from service with  
no interruption of power to connected loads.  
The Configurable Output Distribution was  
designed to provide maximum flexibility to  
business-critical equipment.  
Various output receptacle options are available  
from 15 A to 30 A. Hardwire options are also  
available with a branch rated circuit breaker.  
NOTE  
The 120V loads need to be balanced on  
the UPS output. To do this, when  
connecting 120V equipment to the  
Maintenance Bypass (MB), start at one  
end of the MB and fill in toward the  
other end.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Maintenance Bypass component layout  
Bypass availability  
indicator (amber)  
UPS input power  
present (amber)  
UPS input  
switch  
(SW2)  
Bypass  
switch  
(SW1)  
Output  
breaker  
(CB1)  
UPS output  
availability  
indicator  
(green)  
Hardwire  
output  
terminal  
block  
1
2
3 4  
Configurable  
Output  
(TB4)  
Distribution  
GND3  
GND1  
1 2 3 1 2 3 1 2 3 4  
GND2  
TOP VIEW  
Utility UPS  
input input  
UPS  
output  
TB3  
TB1  
TB2  
INSIDE VIEW— RECEPTACLE  
PLATES AND END PLATE REMOVED  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
MAJOR COMPONENTS  
The following is a general description of each  
20 Amp Options  
component and its functions. Please review this  
section carefully, as it will give you a better  
understanding as to how the UPStation GXT 6 kVA  
Maintenance Bypass operates.  
5-20R2 (T-Slot)  
L5-20R  
L6-20R-208  
L6-20R-240  
BYPASS SWITCH  
L14-20R-240  
The Bypass Switch allows easy and rapid transfer  
of connected loads between the UPS and bypass  
source.  
20A, 120V, 1 Pole Breaker for 1/2" & 3/4" conduit  
20A, 208V, 2 Pole Breaker for 1/2" & 3/4" conduit  
20A, 240V, 2 Pole Breaker for 1/2" & 3/4" conduit  
CONFIGURABLE OUTPUT DISTRIBUTION  
30 Amp Options  
Several receptacle and hardwire options are  
available as user-selectable output distribution.  
These are factory-configured when ordered and  
also allow for field upgrades. Common receptacle  
and hardwire options include:  
L5-30R  
L6-30R-208  
L6-30R-240  
L14-30R-240  
15 Amp Options  
30A, 120V, 1 Pole Breaker for 1/2" & 3/4" conduit  
30A, 208V, 2 Pole Breaker for 1/2" & 3/4" conduit  
30A, 240V, 2 Pole Breaker for 1/2" & 3/4" conduit  
5-15R2  
L5-15R2  
6-15R2-208  
Other Options  
6-15R2-240  
Single Position Blanking Plate  
Hardwire Options  
L6-15R2-208  
L6-15R2-240  
Single Position Plate with 1/2", 3/4" and 1"  
conduit knockouts  
15A, 120V, 1 Pole Breaker for 1/2" & 3/4" conduit  
15A, 208V, 2 Pole Breaker for 1/2" & 3/4" conduit  
15A, 240V, 2 Pole Breaker for 1/2" & 3/4" conduit  
Double Position Plate with 1-3/4" and 2"  
conduit knockouts  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
CABLE INSTALLATION  
WIRING PREPARATION  
POWER CABLE INSTALLATION  
Refer to the chart below when selecting cables:  
!
CAUTION  
Power Cable and Protection Ratings  
Please read this section  
thoroughly before attempting to  
install wiring to this unit.  
Be sure that the unit is not  
connected to any AC mains power  
source or UPS before installing  
any wiring to this unit. This should  
be installed by a qualified/certified  
electrician.  
208V  
240V  
Max Input Current  
Input Protection  
Max Output Current  
30 A  
40 A  
30 A  
30 A  
40 A  
30 A  
2
Max: 16 mm (6 AWG)  
2
Terminal Block Details  
Min: 2.5 mm (14 AWG)  
Torque: 2 Nm (16 in/lb)  
For access to terminal blocks, see diagrams on  
page 4.  
NOTE  
Customer must supply power cables  
between Maintenance Bypass and UPS,  
utility and load. (GMB12 models are  
supplied with an attached input power  
cord complete with L14-30 plug.)  
NOTE  
The 120V loads need to be balanced on  
the UPS output. To do this, when  
connecting 120V equipment to the  
Maintenance Bypass, start at one end of  
the output modules and fill in toward the  
other end. Load balancing must be  
performed with the UPStation  
GXT6000T - 208X and 240X. It is not  
required on the GXT6000T-208 because  
the unit has no 120V output.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Connecting Maintenance Bypass to UPStation GXT6000T - 208  
208  
VAC  
Output  
TB4  
1
2
3
4
GND3  
MAINTENANCE BYPASS  
NOTE  
When using the Maintenance  
Bypass with an UPStation  
GXT6000T-208, a jumper  
(included with the accessory  
kit) must be connected to the  
TB3 (UPS output) terminal  
block on the Maintenance  
Bypass between TB3-1 and  
TB3-2, as shown.  
GND1  
Utility  
TB1  
UPS input  
TB2  
UPS output  
TB3  
GND2  
1
2
3
1
2
3
1
2
3
4
Utility  
input  
L1  
L2  
NOTE  
GMB12 models are supplied  
with an attached input power  
cord complete with L14-30  
plug.  
L1  
L2  
L1  
L2  
+
-
Input  
Output  
Ext. battery  
GXT6000T - 208  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connecting Maintenance Bypass to UPStation GXT6000T - 208X  
120V  
208V  
120V  
Output TB4  
1
2
3
4
GND3  
MAINTENANCE BYPASS  
GND1  
Utility  
TB1  
UPS input  
TB2  
UPSoutput  
TB3  
GND2  
1
2
3
1
2
3
1
2
3
4
Utility  
input  
L2  
L1  
N
GEC  
NOTE  
L1  
L2  
N
L1  
L2  
Output  
L2A  
GMB12 models are supplied  
with an attached input power  
cord complete with L14-30 plug.  
+
-
Input  
Ext. battery  
GXT6000T - 208X  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connecting Maintenance Bypass to UPStation GXT6000T - 240X  
120V  
240V  
120V  
Output TB4  
1
2
3
4
GND3  
MAINTENANCE BYPASS  
GND1  
Utility  
TB1  
UPS input  
TB2  
UPSoutput  
TB3  
GND2  
1
2
3
1
2
3
1
2
3
4
Utility  
input  
L2  
L1  
N
GEC  
NOTE  
L1  
L2  
N
L1  
Output  
GXT6000T - 240X  
L2  
+
-
GMB12 models are supplied  
with an attached input power  
cord complete with L14-30 plug.  
Input  
Ext. battery  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
WALL-MOUNT DIAGRAM  
DIAGRAM FOR ATTACHING UNIT TO WALL  
Use the following diagram, which shows the location and measurements of factory-cut mounting slots,  
when preparing to attach the GXT Maintenance Bypass to a wall. Liebert recommends using 1/4-20  
mounting screws. Rubber pads are supplied for placing the Maintenance Bypass on the floor.  
178mm  
7.00"  
514mm  
20.25"  
C
L
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
HARDWIRE OUTPUT OPTION  
This product is intended to be installed by a  
qualified electrician only.  
6. Connect the remaining wires in accordance  
with the wiring diagram (located inside the  
base enclosure).  
1. COMPLETELY REMOVE ALL POWER FROM  
THE FRAME. If the Maintenance Bypass is  
connected to the UPS, disconnect external  
battery supply.  
2. Remove the end cover plate to access the  
terminal block (see Accessing terminal  
block below).  
3. Without disconnecting from the terminal block,  
unscrew and pull out the hardwire plate(s).  
4. Route all wires from the hardwire plate(s) to  
the terminal block.  
NOTE  
When wiring 120 V loads, LINE must be  
alternated between TB4-1 and TB4-3 to  
balance the 120V load. Connect all  
neutral wires to TB4-4.  
7. Replace the receptacle plates and the end  
cover plate, using care to not damage the  
wires.  
5. Connect the GROUND wire to the grounding  
bar strip (GND1).  
Accessing terminal block  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
OPERATING PROCEDURES  
START-UP AND INITIALIZATION  
Follow these steps in order to start up the  
GXT 6kVA UPS while connected to the  
Maintenance Bypass.  
TRANSFERRING SYSTEM FROM  
UPS TO MAINTENANCE BYPASS  
OPERATION  
1. On UPS verify that Bypass LED is lit, if not,  
press UPS OFF/Bypass button for at least  
one second.  
ON MAINTENANCE BYPASS  
1. Set the Maintenance Bypass switch (SW1) to  
UPS position.  
2. On Maintenance Bypass verify that the  
Bypass lamp is illuminated.  
2. Close (position I) UPS Input switch (SW2).  
3. Close (position I) Output Circuit breaker  
(CB1).  
3. Rotate Bypass switch SW1 to the Bypass  
position.  
4. Set UPS Input switch SW2 to the Off position  
(position O). This will remove power from UPS  
input.  
ON UPS  
1. Close (position I) battery circuit breaker.  
2. Close (position I) input circuit breaker.  
3. Close (position I) output circuit breaker.  
4. After the start-up sequence the UPS will  
automatically default to its internal bypass.  
The bypass LED will be lit.  
5. Press UPS On/Alarm/Battery Test button for at  
least one second to turn the UPS on. The  
UPS ON LED will be lit.  
CAUTION  
!
The connected load is now  
powered by the bypass source and  
is not protected.  
TRANSFERRING SYSTEM FROM  
MAINTENANCE BYPASS TO UPS  
OPERATION  
1. On Maintenance Bypass close (position I)  
UPS Input switch (SW2).  
6. Connected equipment may now be switched  
on.  
2. On UPS close (position I) input, output and  
battery circuit breakers.  
SHUTTING DOWN THE UPS  
Use the following procedure to power down the  
system.  
3. After the start-up sequence the UPS will  
automatically default to its internal bypass.  
The bypass LED will be lit.  
4. Press UPS ON/Alarm/Battery Test button for  
at least one second to turn the UPS on. The  
UPS ON LED will be lit.  
5. On Maintenance Bypass verify that UPS  
Output LED is illuminated.  
ON UPS  
1. Press Output OFF/Bypass button for at least  
1 second, twice, within 4 seconds.  
2. Open (position O) UPS output, input and  
battery circuit breakers.  
6. Rotate Bypass switch SW1 to the UPS  
position.  
ON MAINTENANCE BYPASS  
1. Open (position O) output breaker (CB1).  
2. Open (position O) UPS input switch (SW2).  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
                 
SPECIFICATIONS  
Typical Transfer Time  
(to or from maintenance bypass)  
< 6 milliseconds  
Input Voltage  
Nominal 208VAC or 240VAC  
30A max.  
Total Current  
Operating Ambient Temperature  
Storage Ambient Temperature  
Dimensions, W x D x H, in (mm)  
Chassis Weight (no receptacles)  
0° to +40° C  
-20° to +60° C  
8.2 x 21.0 x 6.2 (209 x 534 x 158)  
10 lbs.  
Distribution Module Weights (each) 2 lbs.  
Connections to UPS  
Humidity  
Hardwire Terminal Blocks  
0 to 95%, non-condensing  
UL 1778, c-UL  
Agency/Standards  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
POWER PROTECTION  
UPStation GXT 6kVA Maintenance Bypass  
USER MANUAL  
Technical Support/Service  
The Company Behind the Products  
Web Site  
With over a million installations around the globe,  
Liebert is the world leader in computer protection  
systems. Since its founding in 1965, Liebert has  
developed a complete range of support and  
protection systems for sensitive electronics:  
Monitoring  
800-222-5877  
Outside the US: 614-841-6755  
Environmental systems—close-control air  
conditioning from 1 to 60 tons  
Single-Phase UPS  
800-222-5877  
Power conditioning and UPS with power  
ranges from 300 VA to more than 1000 kVA  
Integrated systems that provide both  
environmental and power protection in a  
single, flexible package  
Monitoring and control—from systems of any  
size or location, on-site or remote  
Service and support through more than 100  
service centers around the world and a 24/7  
Customer Response Center  
Outside the US: 614-841-6755  
Three-Phase UPS  
800-543-2378  
Environmental Systems  
800-543-2778  
Outside the United States  
614-888-0246  
While every precaution has been taken to ensure  
the accuracy and completeness of this literature,  
Liebert Corporation assumes no responsibility and  
disclaims all liability for damages resulting from  
use of this information or for any errors or  
omissions.  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Italy  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD)  
+39 049 9719 111  
© 2002 Liebert Corporation  
All rights reserved throughout the world.  
Specifications subject to change without notice.  
® Liebert and the Liebert logo are registered  
trademarks of Liebert Corporation. All names  
referred to are trademarks or registered  
trademarks of their respective owners.  
Fax: +39 049 5841 257  
Asia  
23F, Allied Kajima Bldg.  
138 Gloucester Road  
Wanchai  
Hong Kong  
+852 2 572 2201  
Fax: +852 2 831 0114  
SL-23447 (8/02) Rev. 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  

KWC Outdoor Shower Z534543000 User Manual
Lennox Hearth Indoor Fireplace TM 4500 User Manual
Lenoxx Electronics Furnace O23V User Manual
LG Electronics Flat Panel Television W ZB User Manual
Lochinvar Swimming Pool Heater ERN User Manual
Magnavox Flat Panel Television 26MF231D 37B User Manual
Maytag Range MES5875BAB User Manual
Mazda Automobile 2005 B2300 Truck User Manual
Meyer Sound Home Theater Screen UM 1 User Manual
MGE UPS Systems Power Supply EPS 6000 User Manual