Liebert Power Supply RAC2 8 User Manual

(19,5210(17$/ý&21752/  
$XWRð&KDQJHRYHUý&RQWUROOHU  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF FIGURES  
Figure i.  
Typical System Configuration..........................................................................................................iii  
Local Control Panel ..........................................................................................................................3  
RAC2-8 Dimensional Enclosure Diagram ......................................................................................39  
RAC2-8 Component Arrangement..................................................................................................40  
RAC2-8 Connection Diagram.........................................................................................................45  
RAC2-8 Switch and Jumper Settings ..............................................................................................42  
Figure 2–1.  
Figure 5–1.  
Figure 5–2.  
Figure 5–3.  
Figure 5–4.  
ii User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power Source  
120 VAC  
Aux Pwr Out  
24 VAC, 2A  
Terminal  
Port  
Modem  
Port  
SiteScan  
EIA-422  
Twisted Pair  
Liebert  
Temp/Humid  
Module  
EIA-232  
EIA-232  
RAC2-8  
(p/n THS28-xx)  
N.O.  
C
N.C.  
Common Alarm  
Output  
Emergency  
Power Oper.  
Input  
N.O.  
C
N.C.  
Humidity Lockout  
Relay  
N.O.  
C
N.C.  
Optional Lockout  
Relay  
Emergency  
Power Off  
Common  
Alarm  
Output  
Control  
Input  
Common  
Alarm  
Output  
Common  
Alarm  
Output  
Control  
Input  
Control  
Input  
UNIT 8  
UNIT 2  
UNIT 1  
Figure i. Typical System Configuration  
Liebert RAC2-8 iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1: Introduction  
The Liebert RAC2-8 remotely controls from two to eight environmental  
units. Each unit is assigned to a Zone (room) from 1 to 4. In Zone 1, the  
largest room, the temperature and humidity can be monitored. The  
common alarm output from each unit is monitored and annunciated by  
the RAC2-8. Up to 20 system alarms can be stored with time and date  
stamp. All alarms are latching and must be manually cleared.  
See SECTION 5 —  
INSTALLATION for special  
instructions when using the RAC2-8  
with Liebert mini-MATE, mini-MATE  
Plus, and DataMate environmental  
control systems.  
The most important control functions are Autochangeover,  
Autosequencing, and Standby Testing. Each unit can be assigned a  
Running or Standby status.  
Autochangeover turns on a Standby unit if a Running unit in the same  
zone has an alarm. The Running unit (with alarm) will be turned off if  
that control option is selected. Each unit will return to its previous  
status when the alarm is manually cleared.  
Autosequencing balances unit run-times by changing Standby units to  
Running (and Running units to Standby) at programmed time intervals.  
Standby Testing turns on Standby units at programmed intervals to test  
their operation. Note that Autosequencing and Standby Testing cannot  
both be selected at the same time.  
Other control functions include Manual Override, Emergency Power  
Operation, Power Failure Mode, Password, and Programmable Delays.  
Refer to SECTION 4 — GLOSSARY OF CONTROL FUNCTIONS  
for more details.  
System outputs include Humidity Lockout Relay, Optional Control  
Lockout Relay, and Common Alarm. Communication ports are  
EIA-232 for terminal or printer, a modem port, and a proprietary  
EIA-422 port for communication to a Liebert SiteScan monitoring  
system.  
The RAC2-8 can be operated locally from the built-in control panel or  
remotely from an optional terminal (EIA-232 communication). This  
manual shows examples of several typical display screens during both  
local and remote operation.  
Liebert RAC2-8 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2: Start Up  
To start up the RAC2-8:  
1. Mount unit to wall.  
2. Connect cables.  
3. Set switches and jumpers on circuit boards as required for your  
application. Refer to instructions and illustrations in SECTION 5  
— INSTALLATION.  
4. Make user programmable selections from the local control panel or  
from an optional remote terminal. Refer to SECTION 4 —  
GLOSSARY OF CONTROL FUNCTIONS and SECTION 3 —  
OPERATION.  
5. Apply power to the unit. Note that the ON/OFF switch is inside the  
enclosure.  
Figure 2–1. Local Control Panel  
Liebert RAC2-8 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
This chapter describes how to use the RAC2-8.  
Local  
The following screens are displayed at the LCD display built into the  
RAC2-8 unit control panel.  
Refer to SECTION 4 —  
GLOSSARY OF CONTROL FUNCTIONS for more details.  
Sequencing Status Screens  
With power ON, the following status screens are displayed in sequence.  
LIEBERT RAC2-8  
TEMP 71.8°F HUM 47%  
MO 07-15-96 13:26:55  
NO ALARMS PRESENT  
STATUS ZONE 1  
01-R 02-S  
A=ALM S=STBY R=RUN  
STATUS ZONE 2  
03-R 04-S  
A=ALM S=STBY R=RUN  
STATUS ZONE 3  
05-R 06-S  
A=ALM S=STBY R=RUN  
STATUS ZONE 4  
07-R 08-S  
A=ALM S=STBY R=RUN  
Liebert RAC2-8 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
Sequencing Status Screens (cont’d.)  
AUTO SEQUENCING ON  
DAY 06 OF 15 <00:00>  
TEMP STAGING OFF  
Each screen is automatically displayed for 3 seconds.  
To control the display of the status screens, you can press the  
Hold/Sequence button to hold a screen and to manually step through the  
screens. Press C to resume automatic sequencing. The system returns to  
the Sequencing Status Screens if no control keys have been pressed  
during a two minute period.  
xx is the number of alarms recorded  
since alarm history was last cleared.  
See Alarm submenu.  
If alarms are present, the last line of the first screen displayed above  
reads “ALARMS PRESENT - xx.” Alarm screens are displayed next in  
the status sequence. Up to 20 alarms can be displayed, 5 screens of 4  
alarms each. Alarms are stored in a First In First Out (FIFO) sequence.  
These functions cannot both be ON  
at the same time. Select the function  
required for your installation.  
Select either Auto Sequencing or Standby Testing from the Set Options  
Sub-menu.  
Password Screen  
If the Password function is enabled, you must enter the valid password  
to access the RAC2-8 Main Menu. At the Enter Password screen, type  
the established password:  
ENTER PASSWORD  
>
Units are shipped from the factory with the Password function disabled.  
To enable the Password function, press the MENU button to display the  
Main Menu, then press 2 SETUP. Follow the instructions on page 12 to  
Set Password.  
Main Menu  
Press the Menu button to display the Main Menu:  
MAIN MENU  
1. STATUS  
3. ALARMS  
5. OVERRIDE  
2.  
4.  
6.  
SETUP  
SET CLOCK  
EXIT  
Press 9 to display RAC2-8 revision code and date.  
Status Sub-menu  
From the Main Menu, press 1. STATUS to display the Status Sub-  
menu:  
6 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
STATUS MENU  
1. UNITS  
3. A-DELAY  
5. H-DELAY  
2.  
4.  
6.  
T/H  
R-DELAY  
RETURN  
1. UNITS  
From the Status Sub-menu, press 1. UNITS to display the Unit Status  
menu:  
UNIT STATUS  
01-R 02-S 03-R 04-S  
05-R 06-S 07-R 08-S  
A=ALM S=STBY R=RUN  
2. T/H  
From the Status Sub-menu, press 2. T/H to display the  
Temperature/Humidity screen:  
TEMP 71.8°F HUM 47%  
STAGING OFF  
PUSH CLEAR TO RETURN  
3. A-DELAY  
From the Status Sub-menu, press 3. A-DELAY to display the Alarm  
Delays screen:  
ALARM DELAYS  
0000 0000 0000 0000  
0000 0000 0000 0000  
PUSH CLEAR TO RETURN  
Liebert RAC2-8 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
Status Sub-menu (cont’d)  
The Alarm Delays screen indicates the time in seconds of an active  
delay on each unit. Active alarm delays count up while the condition is  
present and count down if the condition is cleared before the Alarm  
Delay time elapses.  
4. R-DELAY  
From the Status Sub-menu, press 4. R-DELAY to display the Restart  
Delays screen:  
RESTART DELAYS  
0000 0000 0000 0000  
0000 0000 0000 0000  
PUSH CLEAR TO RETURN  
The Restart Delays screen indicates the time in seconds of an active  
restart delay on each unit.  
5. H-DELAY  
From the Status Sub-menu, press 5. H-DELAY to display the Hold  
Delay screen:  
HOLD DELAY = 0000  
PUSH CLEAR TO RETURN  
Hold Delay applies to the system rather than to each unit. Therefore,  
only one number is displayed. This display indicates the time in seconds  
of an active Hold Delay.  
Set Options Sub-menu  
From the Main Menu, press 2. SETUP to display the Set Options  
Menu:  
SET OPTIONS MENU  
1. UNITS  
2.  
4.  
6.  
DELAYS  
STANDBY  
RETURN  
3. TEMP/HUM  
5. PASSWORD  
1. UNITS  
From the Set Options Sub-menu, press 1. UNITS to display the Set  
Units menu:  
Set Options Sub-menu (cont’d)  
SET UNITS MENU  
1. ZONES/UNITS  
2. EMER.OP  
4. SHUTDOWN  
3.  
5.  
LABELS  
RETURN  
8 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
From the Set Units menu, select 1. ZONES/UNITS to select the number  
of zones, number of units in each zone, and operating status of each  
unit. Complete all of these selections before exiting this setup  
function.  
Note that the Clear button will not  
allow you to exit these screens until  
all selections have been made.  
When you press 1. ZONES/UNITS, the RAC2-8 sequences through the  
screens you must complete.  
SET NUMBER OF ZONES  
RANGE 1-4 <4> >_  
PUSH ENTER FOR NEXT  
SET NUMBER OF UNITS  
ZONE 1 <2> >_  
PUSH ENTER FOR NEXT  
Set Number of Units screen will be iterated for each zone selected (up  
to 4).  
The RAC2-8 then displays the Set Status screen for Zone 1:  
SET STATUS ZONE 1  
01-R 02-S  
1=RUN O=STBY E=NEXT  
Set Status screen is iterated for each zone selected. Press 1, or 0 to set  
the status. After you have selected the operating status of units in your  
last zone, Press E to return to the Set Units Menu.  
From the Set Units menu, press 2. EMER OP. to display the Set  
Emergency Operating Units ON screen:  
SET EMRG.OP UNITS ON  
01-R 02-0 03-0 04-R  
05-0 06-R 07-0 08-0  
1=RUN O=OFF E=NEXT  
Set Options Sub-menu (cont’d)  
Beginning with unit 01, set each unit's emergency operating status.  
Press E to continue to the next unit. When you have configured the last  
unit, the RAC2-8 returns to the Set Units menu.  
From the Set Units menu, press 3. LABELS to display the Assign  
Labels to Unit screen:  
ASSIGN LABEL TO UNIT  
1-01 2-02 3-03 4-04  
5-05 6-06 7-07 8-08  
PUSH ENTER FOR NEXT  
Beginning with unit 01, assign a label to each unit. You can use two  
numbers, two letters, or a two-character number/letter label. Press E to  
continue to the next unit. When you have configured the last unit, the  
RAC2-8 returns to the Set Units menu.  
Liebert RAC2-8 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
From the Set Units menu, press 4. SHUTDOWN to display the  
Shutdown on Alarm screen:  
SHUTDOWN ON ALARM  
01-Y 02-Y 03-Y 04-Y  
05-Y 06-Y 07-Y 08-Y  
1=YES O=NO E=NEXT  
Beginning with unit 01, indicate 1 (Yes) or 0 (No) if the unit should  
shut down on alarm. When you have selected the shutdown status for  
the last unit, the RAC2-8 displays the Set Units menu.  
When you have configured the delays, from the Set Units menu, press 5  
to return to the Set Options Menu.  
2. DELAYS  
From the Set Options Sub-menu, press 2. DELAYS to display the Set  
Delays menu:  
SECTION 4 — GLOSSARY OF  
CONTROL FUNCTIONS  
includes a functional description  
of each delay.  
SET DELAYS MENU  
1. ALARM  
2.HOLD  
3. UNIT RESTART  
5. RETURN  
From the Set Delays menu, press 1. ALARM to configure the Alarm  
Delay:  
Set Options Sub-menu (cont’d)  
ENTER ALARM DELAY  
<10.0> XX.X MINUTES  
THEN PUSH ENTER  
PUSH CLEAR TO RETURN  
Enter the desired time for the alarm delay. The default is 10 minutes.  
Press E to accept the new delay, then press C to return to the Set Delays  
menu.  
From the Set Delays menu, press 2. HOLD to configure the Hold  
Delay:  
ENTER HOLD DELAY  
<10.0> XX.X MINUTES  
THEN PUSH ENTER  
PUSH CLEAR TO RETURN  
Enter the desired time for the hold delay. The default is 10 minutes.  
Press E to accept the new delay, then press C to return to the Set Delays  
menu.  
10 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
From the Set Delays menu, press 3. UNIT RESTART to configure the  
restart delay:  
ENTER RESTART DELAY  
<00.1> XX.X MINUTES  
THEN PUSH ENTER  
PUSH CLEAR TO RETURN  
Enter the desired time for the restart delay. The default is 0.1 minutes.  
Press Enter to accept the new delay, then press C to return to the Set  
Delays menu.  
When you have configured the delays, from the Set Delays menu, press  
5 to return to the Set Options Sub-menu.  
3. TEMP/HUM  
From the Set Options Sub-menu, press 3. TEMP/HUM to display the  
Set T/H menu:  
SET T/H MENU  
1.T/H ALARM POINTS  
2.TEMP. STAGING  
3.F/C  
4.LOCK  
5.EXIT  
Set Options Sub-menu (cont’d)  
The Set Temp/Hum and Temp Staging functions apply only to Zone 1.  
The temperature and humidity inputs are from a separate remote sensor,  
not from an operating unit.  
From the Set T/H menu, press 1. T/H ALARM POINTS:  
TEMP HI>75 LOW>65  
HUM HI>60 LOW>40  
<RANGE 50-90> 00=off  
E=NEXT C=RETURN  
Beginning with Temp Hi, enter the temperature and humidity alarm  
points. The third line displays the range for the alarm limit you are  
selecting. Press E to continue to the next point. When you have set all  
points, press C to return to the Set T/H menu.  
From the T/H menu, press 2. TEMP. STAGING:  
STAGING ON/OFF >OFF  
NORMAL TEMP  
SENSITIVITY  
1=ON O=OFF  
>72  
>02  
E=NEXT  
Beginning with Staging ON/OFF, configure each parameter. Press E at  
the last parameter to return to the T/H menu.  
From the T/H menu, press 3. F/C to configure degrees in Fahrenheit or  
Celsius:  
SELECT F/C <F>  
Liebert RAC2-8 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
1. F  
2. C  
5. RETURN  
From the T/H menu, press 4. LOCK to configure the optional Humidity  
Lockout feature:  
HUMIDITY LOCKOUT  
SET HI>00 LOW>00  
(RANGE 20-80) 00=OFF  
E=NEXT C=RETURN  
Refer to SECTION 4 — GLOSSARY OF CONTROL FUNCTIONS  
for details on the Humidity Lockout feature.  
Set Options Sub-menu (cont’d)  
4. STANDBY  
From the Set Options Sub-menu, press 4. STANDBY to display the  
Standby Options menu:  
STANDBY OPTIONS MENU  
1. AUTO SEQUENCE UNIT  
2. AUTO STANDBY TEST  
5. RETURN  
From the Standby Options menu, select Auto Sequencing, Standby  
Testing, or neither. These functions cannot both be active (ON) at the  
same time.  
Select the desired function. If you select 1. AUTO SEQUENCE UNIT,  
you must also configure a schedule for your installation:  
AUTO SEQUENCING ON  
EVERY <0-99> XX DAYS  
AT TIME 00:00  
00=OFF E=NEXT C=RTN  
5. PASSWORD  
From the Set Options Sub-menu, press 5. PASSWORD to display the  
Set Password menu:  
SET PASSWORD MENU  
1. NEW PASSWORD  
5. RETURN  
The Password function provides security to the RAC2-8 so that only  
authorized personnel can make Setup changes to the system.  
12 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
Press 1. NEW PASSWORD to set a new four-digit password for the  
system, then follow the instruction on the screens:  
ENTER NEW PASSWORD  
>
THEN PUSH ENTER  
PUSH CLEAR TO RETURN  
Enter “0000” to disable the Password function.  
Set Options Sub-menu (cont’d)  
CONFIRM NEW PASSWORD  
>
THEN PUSH ENTER  
When you have finished configuring the Password, Press E to return to  
the Main Menu.  
Alarm Sub-menu  
From the Main Menu, press 3. ALARMS to display the Alarm Sub-  
menu:  
ALARM MENU  
1. ALARM REVIEW  
2. CLEAR ALARMS  
3. RETURN  
Press 1 to review all alarms. The RAC2-8 can store up to 20 alarms in  
the alarm memory buffer in a First-In-First-Out (FIFO) sequence.  
For each alarm, the review screen displays the alarm number, total  
number of alarms, date and time stamp, and the alarm message:  
ALARM #01/05 ZONE #1  
@ 07-15-96 15:20:42  
UNIT XX COMMON ALARM  
PUSH ENTER FOR NEXT  
If there are no alarms, the screen reads "NO ALARMS PRESENT."  
NO ALARMS PRESENT  
PUSH CLEAR TO RETURN  
Press 2. to display the CLEAR ALARMS screen, then press 1 again to  
clear all alarms:  
CLEAR ALARMS  
1. CLEAR ALL ALARMS  
2. RETURN  
Liebert RAC2-8 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
Set Clock Sub-menu  
From the Main Menu, press 4. SET CLOCK to display the Set Clock  
Sub-menu:  
SET CLOCK MENU  
1. DATE  
2. TIME  
3. DAY OF WEEK  
4. RETURN  
1. DATE  
Press 1 to set the system date:  
MO 07-15-96 15:12:34  
SET DATE MM-DD-YY  
THEN PUSH ENTER  
PUSH CLEAR TO RETURN  
The first line displays the current system day, date, and time. Enter the  
new date, then press E to return to the Set Clock Sub-menu.  
2. TIME  
Press 2 to set the system time:  
MO 07-15-96 15:12:34  
SET TIME HH:MM:SS  
THEN PUSH ENTER  
PUSH CLEAR TO RETURN  
The first line displays the current system day, date, and time. Enter the  
new time, then press E to return to the Set Clock Sub-menu.  
3. DAY OF WEEK  
Press 3 to set the system day of the week:  
SET DAY >MON  
1-SUN 2-MON 3-TUE  
4-WED 5-THU 6-FRI  
7-SAT 8-RETURN  
Enter the appropriate number for the desired day. When finished, press  
8 to return to the Main Menu.  
Override Submenu  
From the Main Menu, press 5. OVERRIDE to display the Override a  
Unit screen:  
OVERRIDE A UNIT  
ENTER UNIT #  
THEN PUSH ENTER  
PUSH CLEAR TO RETURN  
14 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
The Override function lets you manually force a unit ON or OFF, or to  
restore a forced unit to the normal control of the RAC2-8 system. The  
Override function acts immediately, ignoring the Hold Delay. An  
override message with time stamp is entered in the Alarm memory  
buffer. The Alarm light remains on while any unit is in an Override  
mode.  
To override a unit, enter the two digit label assigned to the unit, then  
press Enter:  
UNIT 01 FORCED ON  
2. FORCE OFF  
3. RESTORE  
4. RETURN  
Select the desired override option.  
When finished, press 4 to return to the Main Menu.  
Liebert RAC2-8 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
Terminal  
A local terminal can be connected directly by an EIA-232  
communication cable to the RAC2-8, or a remote terminal can be  
connected through modems. All of the status information and control  
functions available at the RAC2-8 local display are available from the  
terminal. An additional function available at the terminal is Set Modem.  
The terminal also displays a status message with time and date stamp  
whenever a unit changes status (OFF or ON). These status messages  
will be printed if a printer (instead of a terminal) is connected to the  
EIA-232 port. Once each 24 hours (at midnight) the terminal checks its  
ability to communicate with the RAC2-8 and writes a Comm Check  
message.  
A terminal connected to an active RAC2-8 displays alarm and status  
messages when they occur. The prompt then asks the operator to press  
<space>, <S>, or <A>.  
07-15-96  
07-15-96  
12:14:12  
12:14:19  
On UNIT 03 FORCED ON  
On UNIT 63 RESTORED Menu  
Exited - Press <space> to Enter Menu, <S> for  
Status, <A> for Alarms  
<space> displays Main Menu after a password is entered.  
<S> displays present status.  
<A> displays a list of alarms (up to 20).  
LOG ON:  
is the prompt to enter a password. This prompt is also displayed when  
the system is accessed through a modem.  
Main Menu  
The Main Menu is displayed on a terminal as shown below:  
RAC2-8 MAIN MENU  
1. Status  
2. Setup Zones/Units Options Menu  
3. Alarms Review  
4. Alarms Clear  
5. Set Clock  
6. Override a Unit  
7. Set Modem Options  
8. Setup Temp/Humid Options Menu  
9. Setup Standby Unit Options  
A. Display SS Alarm Block  
P. Set New Password  
X. Exit  
Main Menu (cont’d)  
Each Main Menu item has a corresponding screen that lets you  
configure the system parameters. Each screen is shown in the following  
sections.  
When you make a program selection  
from the terminal, the screen is  
displayed again with the new  
value(s).  
16 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
Status Screen  
The Status screen is displayed by pressing the <S> key (no password  
required) or by pressing the <1> key from the Main Menu.  
RAC2-8 STATUS - 07-16-96 09:22:13  
Temperature = 70.6°F  
Humidity = --%  
Modem = OFF  
STATUS  
UNIT LABEL ZONE  
-----------------------------------------------------  
EMRG.PWRSHUTDOWN  
01  
02  
03  
04  
05  
06  
07  
08  
01  
02  
03  
04  
05  
06  
07  
08  
1
1
1
1
0
0
0
0
RY  
RN  
RN  
RN  
ON  
RN  
RN  
RN  
RUNNING  
RUNNING  
RUNNING  
STANDBY  
UNPROGRAMMED  
UNPROGRAMMED  
UNPROGRAMMED  
UNPROGRAMMED  
Alarm Delay  
= 10.0  
= 10.0  
= 00.1  
Hold Delay  
Auto Restart Delay  
High Temperature Alarm  
High Humidity Alarm  
High Humidity Lockout  
= 00  
= 00  
= 00  
Low Temperature Alarm  
Low Humidity Alarm = 00  
Low Humidity Lockout  
= 00  
= 00  
AUTO SEQUENCING  
= ON  
STANDBY TESTING  
= OFF  
DAY 01 of 59 @ 00:00  
Temperature Staging  
= OFF  
NO ALARMS PRESENT  
Press menu selection (1-X) key <ESC to display Main Menu>  
Configure the parameters as desired.  
Liebert RAC2-8 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
Setup Zones/Units Options  
Press 2 from the Main Menu to display the Set Options menu. The  
following screens show the terminal display that enables you to  
configure the Options menu items.  
NUMBER OF ZONES/NUMBER OF UNITS PER ZONE  
RAC2-8 MAIN MENU  
SET OPTIONS MENU  
1. Set Number of Zones  
2. Set Number of Units per Zone  
3. Set Unit Status  
4. Set Emergency Power Units  
5. Set Unit Shutdown on Alarm  
6. Set Unit Labels  
7. Set Alarm Delay  
8. Set Hold Delay  
9. Set Restart Delay  
<ESC> TO EXIT  
CURRENT NUMBER OF ZONES = 1  
ENTER NEW NUMBER (1-4) <ESC to quit> >2  
CURRENT NUMBER OF ZONES = 2  
ENTER NEW NUMBER (1-4) <ESC to quit> >  
SET OPTIONS MENU  
** SET NUMBER OF UNITS PER ZONE **  
ZONE 1 = 4 UNITS  
ZONE 2 = 0 UNITS  
ZONE 3 = UNPROGRAMMED  
ZONE 4 = UNPROGRAMMED  
ENTER ZONE (1 - 2) <ESC to quit> >2  
ZONE 2 has 0 UNITS  
ENTER NEW NUMBER (2-8) <ESC to quit> >2  
** SET NUMBER OF UNITS PER ZONE **  
ZONE 1 = 4 UNITS  
ZONE 2 = 2 UNITS  
ZONE 3 = UNPROGRAMMED  
ZONE 4 = UNPROGRAMMED  
ENTER ZONE (1 - 2) <ESC to quit> >  
SET OPTIONS MENU  
Setup Zones/Units Options (cont’d)  
Configure the number of zones and number of units as desired.  
UNIT STATUS  
SET OPTIONS MENU  
** SET UNIT STATUS **  
UNIT LABEL ZONE  
STATUS  
-----------------------------------------------  
1
01 RUNNING  
1
18 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
2
3
02  
03  
1
1
RUNNING  
RUNNING  
4
5
6
7
8
04  
05  
06  
07  
08  
1
2
2
0
0
STANDBY  
RUNNING  
STANDBY  
UNPROGRAMMED  
UNPROGRAMMED  
PRESS UNIT (1-8) KEY <ESC TO QUIT> 3  
PRESS A KEY (R=RUN or S=STANDBY) <ESC to quit> >07-17-96  
00:24:29 UNIT 03 SHUTDOWN  
** SET UNIT STATUS **  
UNIT  
LABEL ZONE  
STATUS  
-----------------------------------------------  
1
2
3
4
5
6
7
8
01  
02  
03  
04  
05  
06  
07  
08  
1
1
1
1
2
2
0
0
RUNNING  
RUNNING  
STANDBY  
STANDBY  
RUNNING  
STANDBY  
UNPROGRAMMED  
UNPROGRAMMED  
PRESS UNIT (1-8) KEY <ESC TO QUIT>  
Setup Zones/Units Options (cont’d)  
EMERGENCY POWER UNITS  
SET OPTIONS MENU  
The number of Running units can be  
reduced to limit the load on the  
backup power source (a UPS system  
or a standby generator).  
** SET EMERGENCY POWER UNITS **  
UNIT  
LABEL ZONE EMERGENCY POWER  
----------------------------------------  
1
2
3
4
5
6
7
8
01  
02  
03  
04  
05  
06  
07  
08  
1
1
1
1
2
2
0
0
RUN  
RUN  
RUN  
RUN  
OFF  
RUN  
RUN  
RUN  
PRESS UNIT (1-8) KEY <ESC TO QUIT> 1  
Unit Shutdown on Alarm  
When an alarm occurs in a Running unit, the Standby unit in the same  
zone will be turned ON. The unit in alarm will remain ON unless it is  
programmed to be turned OFF (Yes).  
SET OPTIONS MENU  
** SET UNIT SHUTDOWN ON ALARM **  
UNIT LABEL ZONE SHUTDOWN  
------------------------------------------  
1
2
3
4
5
01  
02  
03  
04  
05  
1
1
1
1
2
YES  
NO  
NO  
NO  
NO  
6
7
06  
07  
2
0
NO  
NO  
Liebert RAC2-8 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
8
08  
0
NO  
PRESS UNIT (1-8) KEY <ESC TO QUIT> 1  
20 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
Unit Labels  
The RAC2-8 will accept any 2 digit label if you prefer something other  
than 01 through 08.  
SET OPTIONS MENU  
** SET UNIT LABEL **  
UNIT LABEL  
-------------  
1
2
3
4
5
6
7
8
01  
02  
03  
04  
05  
06  
07  
08  
PRESS UNIT (1-8) KEY <ESC TO QUIT> 1  
Alarms Review and Alarms Clear  
Press 3 or 4 from the Main Menu to access the Alarms Review and  
Alarms Clear screens. The RAC2-8 can store and display up to 20  
Alarms with time and date stamp. All alarms are latching and must be  
cleared manually.  
RAC2-8 MAIN MENU  
NO ALARMS PRESENT  
07-18-96 00:25:47 ALARMS CLEARED  
Set Clock  
Press 5 from the Main Menu to display the Set Clock screen.  
RAC2-8 MAIN MENU  
Current Date/Time is THU 07-18-96 00:25:50  
Enter New Date/Time (DOW MM-DD-YY HH:MM) MON 07-22-96 09:15  
Current Date/Time is MON 07-22-96 09:15:00  
Set the new date and time as desired.  
Liebert RAC2-8 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
Override A Unit  
Press 6 from the Main Menu to display the Override a Unit screen. A  
unit can be Forced ON, Forced OFF, or Restored to automatic control.  
RAC2-8 MAIN MENU  
** OVERRIDE A UNIT **  
UNIT LABEL STATUS  
------------------------------------------  
1
2
3
4
5
6
7
8
01  
02  
03  
04  
05  
06  
07  
08  
RUNNING  
RUNNING  
STANDBY  
STANDBY  
RUNNING  
STANDBY  
UNPROGRAMMED  
UNPROGRAMMED  
PRESS UNIT (1-8) KEY <ESC TO QUIT> 3  
1.  
2.  
3.  
FORCE ON  
FORCE OFF  
RESTORE  
07-22-96 12:14:12 On UNIT 03 FORCED ON  
** OVERRIDE A UNIT **  
UNIT LABEL STATUS  
------------------------------------------  
1
2
3
4
5
6
7
8
01  
02  
03  
04  
05  
06  
07  
08  
RUNNING  
RUNNING  
FORCED ON  
STANDBY  
RUNNING  
STANDBY  
UNPROGRAMMED  
UNPROGRAMMED  
PRESS UNIT (1-8) KEY <ESC TO QUIT> 3  
1. FORCE ON  
2. FORCE OFF  
3. RESTORE  
07-22-96 12:14:19 On UNIT 03 RESTORED  
22 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
Set Modem Options  
Press 7 from the Main Menu to display the Set Modem Options screen.  
RAC2-8 MAIN MENU  
** SET MODEM OPTIONS **  
1. Phone Number =  
2. Site ID  
3. Dial Prefix  
=
= ATE1X4DT  
4. Redial Interval (minutes) = 01  
5. Redial Tries (--- = Forever)  
6. Modem Messages Y/N = No  
<ESC> TO EXIT  
= 03  
Phone Number = 7944  
** SET MODEM OPTIONS **  
1. Phone Number = 7944  
2. Site ID  
3. Dial Prefix  
=
= ATE1X4DT  
4. Redial Interval (minutes) = 01  
S. Redial Tries (--- = Forever)  
6. Modem Messages Y/N = No  
<ESC> TO EXIT  
= 03  
Site ID  
= AIR ROOM #1  
These parameters are unique to terminal operation.  
The Site ID (up to 20 characters) is user selected to identify a specific  
facility. The Dial Prefix activates the modem and therefore must be  
compatible with the modem. The Dial Prefix is factory set. Do not  
change the Dial Prefix without consulting the modem user’s  
manual. Modem messages describe modem activity such as No  
Answer, Line Busy, Redial in 3 Minutes, etc. Select Yes if you want  
these messages displayed at the terminal.  
Make modem baud rate selection by setting DIP Switch 2-1 inside the  
RAC2-8 enclosure. Refer to Figure 5–4 in SECTION 5 —  
INSTALLATION. Set Switch 2-2 to ON (down) if you are using a  
leased line.  
The Modem must be Hayes or Hayes compatible. Switches inside the  
modem should remain factory set except the following which are user  
selectable.  
Liebert RAC2-8 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
Set Modem Options (cont’d)  
Hang up on DTR on-off transition  
Model 1200:  
Model 2400:  
SW1 up and SW10 down  
&D3  
Track status of carrier detect  
Model 1200:  
Model 2400:  
SW6 up  
&C1  
Enable Auto-answer  
Model 1200:  
Model 2400:  
SW5 up  
S0=1  
Setup Temp/Humid Options  
Press 8 from the Main Menu to display the Setup Temp/Humid Options  
screen.  
RAC2-8 MAIN MENU  
** SET TEMP/HUMIDITY OPTIONS **  
1. High Temperature Alarm= 00  
2. Low Temperature Alarm = 00  
3. High Humidity Alarm  
4. Low Humidity Alarm  
5. Temperature Staging  
6. Normal Temperature  
= 00  
= 00  
= OFF  
= 70  
7. Sensitivity  
= 02  
8. Temp Display (F/C)  
= F  
9. High Humidity Lockout = 60  
A. Low Humidity Lockout = 00  
<ESC> TO EXIT  
High Temperature Alarm = (50-90) >80  
** SET TEMP/HUMIDITY OPTIONS **  
1. High Temperature Alarm= 80  
2. Low Temperature Alarm = 00  
3. High Humidity Alarm  
4. Low Humidity Alarm  
5. Temperature Staging  
6. Normal Temperature  
= 00  
= 00  
= OFF  
= 70  
7. Sensitivity  
= 02  
8. Temp Display (F/C)  
= F  
9. High Humidity Lockout = 60  
A. Low Humidity Lockout = 00  
<ESC> TO EXIT  
Temperature Staging = (ENTER 1 for ON, 0 for OFF) >ON  
Setup Temp/Humid Options (cont’d)  
Temperature and humidity options apply to Zone 1. The system inputs  
come from a remote temp/hum sensor. Each alarm can be disabled by  
entering 00 as the alarm trip-point. Temperature Staging turns on a  
Standby unit when the room temperature exceeds the Normal  
Temperature by the number of degrees entered in Sensitivity. Also note  
that temperature can be displayed in either degrees F or degrees C.  
24 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
Setup Standby Unit Options  
Press 9 from the Main Menu to display the Set Standby Unit Options  
screen:  
RAC2-8 MAIN MENU  
** SET STANDBY UNIT OPTIONS **  
1. Auto Sequencing = ON  
2. Standby Testing = OFF  
3. Day Interval  
4. At Time  
= 89  
= 07:00  
<ESC> TO EXIT  
Auto Sequencing = (ENTER 1 for ON, 0 for OFF) >OFF  
** SET STANDBY UNIT OPTIONS **  
1. Auto Sequencing = OFF  
2. Standby Testing = OFF  
3. Day Interval  
4. At Time  
<ESC> TO EXIT  
= 89  
= 07:00  
Two options are available for controlling Standby units (in addition to  
Autochangeover). The RAC2-8 will operate with both of these options  
turned OFF, or with one of them turned ON. Select the option (or  
neither) required for your installation. The interval (in days) and time of  
day are user selected.  
Auto Sequencing balances the run time of units by changing the status  
of a Standby unit to Running, and changing the Running unit to  
Standby.  
Standby Testing tests the operating condition of a Standby unit by  
turning it ON for a period of time equal to the Hold Delay plus the  
Alarm Delay. The Running unit is turned OFF during this period if it is  
programmed to shutdown on an alarm.  
Liebert RAC2-8 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3: Operation  
Display SS Alarm Block  
Set New Password  
This display is useful to a Liebert Customer Engineer for system  
diagnostics.  
Press P from the Main Menu to configure a password for terminal  
operation.  
Enter New Password (4 chars) <ESC to quit> >****  
Confirm New Password (4 chars) <ESC to quit> >****  
OK  
This Password can be different from the one used locally at the RAC2-  
8.  
Enter “TERM” to disable the Password function from the terminal. A  
Password is always be required when accessing the RAC2-8 system  
through a modem.  
26 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4: Glossary of Control Functions  
The following terms are used to describe the control and operation of  
the Liebert RAC2-8. For each term, both the operator actions and the  
system performance are defined. Refer to this section if necessary while  
setting up your system or to answer any questions about how the system  
operates.  
Alarms  
For each alarm condition or warning condition, the RAC2-8 locally  
annunciates the condition, locally displays the message, provides a time  
and date stamp, stores up to 20 messages in memory, and displays the  
message at a remote terminal. Alarms are produced for normal alarm  
conditions such as Common Alarm inputs and Temp/Hum alarms.  
Warnings are produced for conditions such as Manual Override.  
List of Alarms  
UNIT XX COMMON ALARM  
Alarm  
EMERGENCY POWER OFF  
EMERGENCY POWER OP.  
Alarm  
Alarm  
MANUAL OVERRIDE Alarm  
HIGH TEMP ALARM  
LOW TEMP ALARM  
HIGH HUM ALARM  
LOW HUM ALARM  
Alarm  
Alarm  
Alarm  
Alarm  
STBY NOT AVAILABLE  
STBY UNIT FAILED  
Alarm  
Alarm  
UNIT XX FORCED ON Warning  
UNIT XX FORCED OFF Warning  
UNIT XX RESTORED  
(no audible alarm)  
(no audible alarm)  
Warning  
(no audible alarm)  
Liebert RAC2-8 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4: Glossary of Control Functions  
Alarm Annunciation  
The RAC2-8 provides the following alarm annunciation mechanisms:  
Audible indication (horn).  
A lighted ‘Alarms Present’ front panel indicator.  
Activation of the Common Alarm relay output.  
Display of alarm messages on the front panel LCD.  
Warnings activate the ‘Alarms Present’ indicator and a message on the  
LCD, but no audible alarm or Common Alarm.  
When an alarm occurs the LCD immediately displays a message (unless  
an Override screen is being displayed). Pushing the Alarms  
Present/Silence pushbutton acknowledges the alarm and silences the  
alarm horn. The alarm message is displayed until the alarm is  
acknowledged (silenced). After the alarm is silenced, normal status  
display scanning resumes.  
Any alarms present are displayed during scanning of normal display  
pages. If more than 4 alarms are present additional pages of alarms are  
created as necessary. Up to 20 alarms are stored in a First-In-First-Out  
sequence.  
Alarm Communications  
EIA-232 Terminal Port—Transmits Alarm with time stamp.  
EIA-232 Modem Port—Dials out alarm.  
Both EIA-232 ports are compatible with SS-AMS (SiteScan Alarm  
Management System).  
EIA-422 (proprietary) to SiteScan monitoring system.  
Alarm Delay  
Delay before an alarm is annunciated (false alarm delay). This delay  
begins on the occurrence of an alarm condition in a unit. If the alarm  
condition has not corrected itself by the end of the delay period, the  
alarm is annunciated and an autochangeover to the standby unit Occurs.  
If a unit is programmed to shutdown on an alarm, the unit shuts down  
when the alarm is annunciated. The Alarm Delay timer counts both up  
and down and an active Alarm Delay timer can be monitored at the  
display. The Alarm Delay is user selectable from the display. Range -  
0.1 to 60 minutes, in increments of 0.1 minute (6 sec).  
Autochangeover  
If an alarm occurs in a Running unit, a Standby unit in the same zone is  
started. The Running unit in alarm is stopped if it is programmed to shut  
down, and the Standby unit is started. The Standby unit changes status  
to become the Running unit and remains running until the Alarm is  
manually cleared. Messages are written to the terminal to record the  
status changes. Status screens show new unit status at the local display.  
After a changeover, the newly started unit may briefly have a High  
Temp or other alarm. A user selectable Hold Delay begins when any  
28 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4: Glossary of Control Functions  
unit is turned ON. During the Hold Delay no alarms are annunciated  
from the started unit or any unit in the system.  
If the Standby unit has an alarm, the Running unit is restarted if DIP  
switch 1-8 is ON. Also, whenever the alarm is cleared in a Running  
unit, the unit is turned on and the Standby unit is turned off.  
Autosequencing  
An optional operating mode in which Standby units are periodically  
sequenced to RUN to balance operating time among all units. Select  
Autosequencing ON or OFF from the display. Note that  
Autosequencing and Standby Testing cannot both be ON at the same  
time.  
When Autosequencing is ON, periodically the Standby and Running  
units are changed to balance unit running time. This interval (in days)  
and time of day are user selected from the display. When this  
changeover Occurs, the Standby unit becomes a running unit, and the  
Running unit that has been running the longest becomes the Standby  
Unit. Messages are written to the terminal to record the status changes.  
Status screens show new unit status at the local display.  
After a changeover, the newly started unit may briefly have a High  
Temp or other alarm. A user selectable Hold Delay begins when any  
unit is turned ON. During the Hold Delay no alarms are annunciated  
from the started unit or any unit in the system. If the newly started unit  
has an alarm at the end of this delay (plus the Alarm Delay), this unit is  
shut down, and the previously running unit is restarted. An alarm is  
indicated on the LCD and the alarm is annunciated.  
Liebert RAC2-8 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4: Glossary of Control Functions  
If a zone includes more than 1 Standby unit, the same actions occur. At  
the end of each Interval, one unit is started and one is stopped. For  
example, if two Standby units are used, the First is started after the First  
Interval. The unit that had been running the longest becomes the  
Standby unit. After the second Interval, the second Standby unit is  
started, and the Running unit with the longest operating time becomes  
the Standby unit.  
C key  
The Clear key <C> at the local control panel serves two functions:  
Remove incorrectly entered data.  
Return to the previous display page.  
Clear Alarms  
All alarms are latching and must be manually cleared from the control  
panel or from a terminal. Be sure to review alarms before clearing them  
because recent alarm history is your best indication of system  
performance. When alarms are cleared, units that are running because  
of an Autochangeover will change back to their programmed status.  
Common Alarm—Inputs  
Each environmental control unit has a Common Alarm contact closure  
output. The RAC2-8 receives the Common Alarm from each unit as a  
control input. These alarms are annunciated only if the programmed  
Delays (Hold and/or Alarm) are exceeded. A Common Alarm from a  
Running unit causes a Standby unit to be turned ON, and turns OFF the  
Running unit if shutdown is selected. A Common Alarm from a Standby  
unit causes the unit to be unavailable.  
Common Alarm—Output  
A Form C contact labeled Common Alarm is available for customer  
use. This relay is energized during the following conditions:  
A Common Alarm input from one of the units  
A Temp/Hum Alarm  
Manual Override ALL ON internal switch  
Emergency Power Operation mode  
Emergency Power OFF  
The Common Alarm is de-energized by the Silence pushbutton if DIP  
switch 1-7 is ON.  
Control Lockout  
A Form C contact labeled (optional) Control Lockout is available for  
customer use. This relay is energized during the following conditions:  
Manual Override internal switch (all units on)  
Emergency Power Operation mode  
30 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4: Glossary of Control Functions  
Delay  
E key  
Refer to Alarm Delay, Hold Delay, and Restart Delay.  
The Enter key <E> at the local control panel serves two functions:  
Causes data entered in setup display pages to be stored in the  
RAC2-8 permanent memory.  
Causes selection of next unit on multi-unit displays.  
Emergency Power OFF (EPO)  
EPO can be initiated from a remote switch wired to the RAC2-8. This  
user input causes all units to be turned OFF immediately. RAC2-8  
control power is maintained. This Normally Closed contact must be  
Open for 0.5 seconds for the input signal to be detected.  
After the input signal is removed (closed), the alarm must be manually  
cleared. Then all units programmed to be Running are started  
sequentially, separated by the Restart Delay.  
Emergency Power Operation  
This user input activates a separate mode for operating on an  
emergency power source (a UPS system or standby generator) which  
may have limited capacity. Only units selected to be ON during this  
mode are running. Select ON units for this mode from the display.  
Autochangeover, Autosequencing, and Standby Testing are inactive  
during this mode to reduce power load. Units that are OFF during this  
mode will remain OFF until normal mode is resumed. This mode also  
energizes both lockout relays, Humidity and (Optional) Control.  
Force ON  
Force OFF  
Hold Delay  
To manually turn a unit ON from the display. Refer to Override.  
To manually turn a unit OFF from the display. Refer to Override.  
Delay after turn ON of a Standby unit to allow the newly started unit to  
gain control. During the Hold Delay alarms from this unit and all other  
units are ignored. This delay begins when any changeover Occurs,  
either in Autosequence or Standby Test mode. An active Hold Delay  
can be monitored at the display. At the end of the Hold Delay, the  
Alarm Delay time begins. The Hold Delay is user selectable from the  
display.  
Range—0.1 to 60 minutes, selectable in increments of 0.1 minute  
(6 seconds).  
Liebert RAC2-8 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4: Glossary of Control Functions  
Humidity Alarms  
Humidity alarms are caused when the humidity detected by the remote  
sensor in Zone 1 exceeds the programmed High or Low trip-point. Trip-  
points are selected in 1% RH increments from the display. Entering 00  
disables an alarm. A Humidity Alarm activates the Common Alarm  
output.  
High Range—up to 80% RH.  
Low Range—down to 20% RH.  
Humidity Lockout  
A Form C contact labeled Humidity Lockout is energized when a  
humidity reading exceeds a lockout trip-point. The relay is de-energized  
when humidity drops to 2% RH below the High Humidity Trip-point, or  
when humidity rises to 2% RH above the Low Humidity Trip-point. To  
use this contact for a single control function (increase or decrease  
humidity) disable one of the Humidity Alarms.  
Inactive Unit  
Interval  
An inactive unit is one that is not programmed to the RAC2-8 system.  
This appears in an error message if you try to Override a unit that the  
system does not recognize.  
The Interval is the time period (in days) used to program the  
Autosequencing and Standby Testing functions. The interval is user  
selected from the display. Range—0 to 99 days.  
Labels  
Each unit may be labeled with a 2 digit number from 01 to 99. If you  
prefer something other than 01 through 08, unit labels can be selected  
from the display.  
Manual Override  
A switch located inside the RAC2-8 enclosure turns all units ON. This  
action also annunciates an alarm, energizes the Common Alarm output  
relay, and energizes the Control Lockout relay. To return to normal  
operation, turn this switch off and clear the alarm. Refer to Override for  
manual operations from the display.  
Modem  
The RAC2-8 includes an EIA-232 modem port to provide remote  
display of alarms. This same port also allows system monitoring and  
programming from a remotely located terminal. Operation from a  
remote terminal requires a Password after the “LOG ON: ” prompt. If a  
remote terminal is active, alarms are displayed at the terminal instead  
of being dialed out. The modem selections such as phone number,  
redial interval, etc., are made from a local or remote terminal. Modem  
baud rate is selected using switches inside the RAC2-8 enclosure.  
32 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4: Glossary of Control Functions  
Normal Temperature  
Override  
Refer to Temperature Staging.  
The RAC2-8 allows manual control of units from the display and also  
from switches inside the enclosure. To manually turn all units ON refer  
to Manual Override. To manually select units to be ON during a control  
power failure refer to Power Failure Mode.  
Manual Override control from the display includes Force ON, Force  
OFF, and Restore to normal operation. If any unit is Forced ON or OFF  
a warning message is recorded and the Alarm Present light is  
illuminated, but the audible alarm (horn) is not sounded. Changes of  
status messages are displayed at a local terminal if one is connected.  
While an Override screen is displayed, alarm messages are stored but  
not displayed.  
Force ON of any unit  
Selected from the Override screen at the display. This action causes the  
selected unit to be turned ON and held ON until further action is taken.  
The unit remains ON until it is Forced OFF or Restored to normal.  
Force OFF of any unit  
Selected from the Override screen at the display. This action causes the  
selected unit to be turned OFF and held OFF until further action is  
taken. The unit remains OFF until it is Forced ON or Restored to  
normal.  
Restore to normal  
Selected from the Override screen at the display. This action returns the  
selected unit to the programmed control of the RAC2-8. The unit  
returns to its operating status (Running or Standby) as defined in  
Unit/Zone Setup.  
Password  
A four digit number used to limit access to setup information and  
clearing of alarms. A Password (if active) is required for entry to the  
Main Menu. Assign a new Password from the display. A Password of  
0000” disables the Password function at the local display: “TERM”  
disables the password at a local terminal. The Password is always  
required for a remote terminal (through a modem).  
Power Failure Mode  
During a failure of power to the RAC2-8, units can be programmed to  
be ON by manually setting jumpers inside the enclosure. This assumes  
that power will be available to the units. When power is restored to the  
RAC2-8, all units programmed to be Running during normal operation  
are sequentially started, separated by the Restart Delay.  
Compare this mode with Emergency Power operations which is  
selectable from the display and applies to power being available from a  
standby source.  
Liebert RAC2-8 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4: Glossary of Control Functions  
Restart Delay  
The length of time between a request to turn ON a unit and when the  
unit is actually turned ON. Also the length of time between the start of  
each successive unit after power is applied or restored. This delay  
prevents an excessive inrush current demand on the power source.  
Restart Delay is typically very short and is user selectable from the  
display. Range—0.1 to 60 minutes, in increments of 0.1 minute (6  
seconds).  
Restore  
To return a Forced ON or Forced OFF unit to normal control. Refer to  
Override.  
Running Units  
The units selected to be ON during an operating mode. Select Running  
units from the display. Units not selected for Running status are given  
Standby status. Running units can be turned OFF by Autochangeover,  
Autosequencing, or Standby Testing.  
Shutdown  
Site ID  
When a Running unit is in an alarm condition, it can be programmed to  
remain running or be shut down. Select Shutdown (Yes or No) from the  
display.  
The user assigned identification of this facility (up to 20 characters).  
The Site ID is included in alarm messages dialed out by the modem.  
Assign the Site ID from the terminal.  
SiteScan  
A Liebert site monitoring system. The RAC2-8 sends information to  
SiteScan if a system is connected to the EIA-422 port.  
Standby Testing  
When Standby Testing is ON the RAC2-8 periodically starts the  
Standby unit(s) to test operation. The time between these tests is the  
Interval. Standby Testing ON/OFF, Interval (in days), and time of day  
for testing are user selected from the display. Standby Testing and  
Autosequencing cannot both be ON at the same time.  
Each time a test is performed, the Standby unit(s) operate for a time  
equal to the Hold Delay plus the Alarm Delay. At the end of this period  
operation returns to the Running unit(s). If an alarm occurs and does not  
correct itself by the end of the test time, an alarm is displayed and  
annunciated.  
Standby Units  
The units selected to be OFF during an operating mode. Select Standby  
units from the display. Units not selected for Standby status are given  
34 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4: Glossary of Control Functions  
Running status. Standby units can be turned ON by Autochangeover,  
Autosequencing, or Standby Testing.  
Temperature Alarms  
Temperature alarms are caused when the temperature detected by the  
remote sensor in Zone 1 exceeds the programmed High or Low trip-  
point. Trip-points are selected in 1 degree increments from the display.  
Entering 00 disables an alarm. A Temperature Alarm activates the  
Common Alarm output.  
High Range—up to 90°F (32°C).  
Low Range—down to 50°F (10°C).  
Temperature Sensitivity  
Temperature Staging  
Refer to Temperature Staging.  
The RAC2-8 can be programmed to use Standby units, along with  
Running units, for increased capacity in Zone 1. If more than one  
Standby unit is available, these units can be staged to turn on as  
temperature increases. Temperature Staging is selected from the  
display. This mode is the best way to control room temperature after  
recovering from a power failure (a remote T/H sensor is required).  
Normal Temperature  
The temperature to be maintained when Temperature Staging is ON.  
Normal Temperature is selected from the display.  
Range—50 to 90°F (10 to 32°C), in 1 degree increments.  
Temperature Sensitivity  
The number of degrees from the Normal Temperature which causes the  
next Standby unit to be turned ON. As temperature approaches Normal,  
the Standby units are turned OFF in first-on/last-off order. Sensitivity is  
selected from the display in 1 degree increments, and is a small number.  
Terminal  
A local terminal can be connected directly to the RAC2-8 or a remote  
terminal can be connected through modems. Two EIA-232 ports are  
available at the enclosure. All of the status information and control  
functions available at the RAC2-8 local display are available from the  
terminal. An additional function available at the terminal is Set Modem.  
The terminal also displays a status message with time and date stamp  
whenever a unit changes status (OFF or ON). The terminal baud rate is  
selected by using switches inside the enclosure.  
Units  
Each environmental control system connected to the RAC2-8 is called a  
Unit. Each Unit is located in a Zone, is assigned a Label, and a status  
(Running or Standby). All of these selections are made from the display  
(for 2 to 8 units). The RAC2-8 monitors Unit Common Alarms and  
turns Units ON or OFF from the automatic control program or from  
manual inputs.  
Liebert RAC2-8 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4: Glossary of Control Functions  
Zones  
Each area (room) controlled by the RAC2-8 is called a Zone. Zones are  
numbered 1 through 4. Zone 1 should be the largest or most important  
room, it is the only Zone that can be monitored by a Temp/Hum sensor,  
and the only Zone that can be controlled by Temperature Staging. Each  
Zone contains at least one Unit.  
36 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5: Installation  
Select a location for the RAC2-8 that is convenient for both operation  
and cable routing. If the application at your installation is critical, the  
location should also provide limited access to the controller.  
The RAC2-8 enclosure is surface mounted using four 1/4 in. bolts. The  
power cord is factory wired. Note that the use of a 220 VAC 50/60 Hz  
power source must be selected when the unit is ordered. This is not a  
field selectable option. Two EIA-232 ports are available at the bottom  
of the enclosure. All other customer cables enter through knockouts at  
the bottom of the enclosure.  
Refer to Figure i on Page iv in the  
beginning of this manual for a  
typical system configuration. Refer to  
the following drawings (including  
notes) for details of wire  
terminations and switch settings for  
inputs and outputs used at your  
installation.  
The RAC2-8 includes a lithium backup battery for control memory. The  
battery is disconnected from the system for storage and shipment. Set  
DIP switch 2-8 to ON to connect the battery.  
Call Liebert Environmental Support  
at 1-800-543-2778 if you require any  
assistance for the installation or  
operation of your RAC2-8  
The RAC2-8 may show an alarm from a Liebert DataMate, mini-  
MATE, and/or mini-MATE Plus unit when an alarm condition does  
not, in fact, exist. If you are using or plan to use the RAC2-8 with the  
Liebert DataMate, mini-MATE, and/or mini-MATE Plus, remove the  
C5 capacitor at the K5 common alarm relay to avoid false alarms:  
Autochangeover controller.  
Installation (cont’d.)  
1. Put on an anti-static wrist strap.  
2. Turn the main disconnect switch OFF.  
Liebert RAC2-8 37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5: Installation  
3. Using wire cutters, carefully snip and remove the C5 capacitor at  
the K5 common alarm on the interface board. Refer to the diagram  
below for the location of the C5 capacitor.  
K8  
K7  
K6  
P2  
4
3
2
1
RV4  
R5  
Interface Board  
4C13521G  
TB2  
C5 (yellow)  
CR7  
K5  
K4  
RV5  
(Located in the  
DataMate,  
mini-MATE, or  
mini-MATE Plus)  
K3  
K2  
K1  
P1  
TB1  
38 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5: Installation  
Figure 5–1. RAC2-8 Dimensional Enclosure Diagram  
Liebert RAC2-8 39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5: Installation  
Figure 5–2. RAC2-8 Component Arrangement  
40 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5: Installation  
Figure 5–3. RAC2-8 Connection Diagram  
Liebert RAC2-8 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5: Installation  
Figure 5–4. RAC2-8 Switch and Jumper Settings  
42 User Manual (9/97)  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Kyocera Printer FS 1100 User Manual
Land Pride Automobile Electronics 322 119A User Manual
Linksys Network Router BEFSR41 v2 User Manual
Linksys Printer PPS1UW User Manual
Majestic Appliances Gas Heater UVS33RN User Manual
M Audio Computer Hardware 4215 MRP User Manual
McCulloch Lawn Mower 11597SD User Manual
McCulloch Lawn Mower 96141020200 User Manual
Meridian Audio Flat Panel Television DVP 1080 User Manual
Meridian Audio Speaker P200Z User Manual