User Manual–1000/1500/1920/3000VA, 60Hz, 120VAC
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
WHAT’S INCLUDED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Tower UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Rack-Mount UPS Conversion and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Orient Display for Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Connect Input Power and Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Connect Network Surge protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Connect Computer Interface Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
EPO Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
External Battery Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
CONTROLS AND INDICATORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Control Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.1.1 On/Alarm Silence/Manual Self-Diagnostic Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.1.2 Off Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.2.1 Status Change Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.2.2 Load Level Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.2.3 Battery Level Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.2.4 UPS Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
OPERATIONAL MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Buck/Boost Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Battery Recharge Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
DB-9 Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Remote Shutdown Via the DB-9 Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.2.1 Any Mode Shutdown Via Pins 5 & 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.2.2 Battery Mode Shutdown Via Pins 4 & 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.5
RJ-45 Data Line Protection Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
UPS Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
UPS Inverter/Transfer Voltage Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
i
Download from Www.Somanuals.com. All Manuals Search And Download.
BATTERY MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Battery Charging, Storage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Internal Battery Replacement Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
FIGURES
Figure 1
Front view of UPS, rack mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1000 and 1500VA—rear view. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1920VA—rear view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3000VA—rear view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Placing the Liebert PSI XR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Tower configuration—attach Tower Stand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Convert the Liebert PSI XR for rack installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Adjusting the UPS display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 10 Connect input power and load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 11 Connect network surge protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 12 Connect computer interface port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 13 EPO connection for normally open operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 14 Install the external battery cabinet in tower installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 15 Connect battery cabinets to UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 16 Display and status indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 17 DIP switch settings for 120V system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 18 Battery replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
TABLES
Table 1
Battery cabinet connector color key. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Display and status indicators function, legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Status indicators—color, illumination mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
DB-9 pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Voltage configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Liebert PSI XR specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Liebert PSI XR battery run times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Troubleshooting—problems, causes and solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
ii
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and mainte-
nance of the UPS.
• Intended for installation in a temperature-controlled, indoor area free of conductive contami-
nants.
• Maximum ambient temperature 104°F (40°C).
Read this manual thoroughly before attempting to install or operate this UPS.
The equipment can be installed and operated by individuals without previous training.
WARNING
supply.
!
Operate the UPS only from a properly grounded (earthed) 110-127VAC, 50Hz or 60Hz AC
Some components are live, even when AC power is disconnected. For service, contact a
properly trained and qualified technician. Do not remove the cover; the UPS has no
user-serviceable parts inside except the internal battery pack.
WARNING
use can result in electrical shock or fire. To ensure safety, observe the following rules:
!
Although the UPS has been designed and manufactured to ensure personal safety, improper
• Turn Off and unplug the UPS before cleaning it. Clean the UPS with a dry cloth. Do not use
liquid or aerosol cleaners.
• Do not install or operate the UPS in or near water.
• Never block or insert any objects into the ventilation holes or other openings of the UPS.
Keep all vents free of dust accumulation that could restrict air flow.
• Do not place UPS power cord anywhere it might be damaged.
Battery Handling Precautions
WARNING
of batteries and required precautions.
!
Batteries should be replaced only by properly trained and qualified personnel knowledgeable
A battery can present a risk of electrical shock and high short-circuit current. The following
precautions must be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Do not dispose battery or batteries in a fire. The battery may explode.
• Do not open or mutilate the battery or batteries. Released electrolyte is toxic. It may cause
injury to the skin and eyes.
• Handle, transport and recycle batteries in accordance with local regulations.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
ELECTROMAGNETIC COMPATIBILITY—The Liebert PSI XR complies with part 15 of the FCC
Rules. Operation is subject to the following two conditions:
• This device may not cause harmful interference, and
• This device must accept any interference received, including interference that may cause unde-
sired operation.
This equipment uses, generates and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference with radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception, the user is encouraged to
try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the UPS and the receiver.
• Connect the UPS to an outlet on a circuit different from the one the receiver is connected to.
The Liebert PSI XR is not intended for use with life support or other designated critical devices. Max-
imum load must not exceed that shown on the rating label.
NOTICE
The input receptacle must be within 10 feet (3 meters) of the UPS.
Your UPS provides conditioned power to connected equipment. Maximum load must not
exceed that shown on UPS rating label. If uncertain, consult your local dealer, Emerson
representative or Emerson Network Power Liebert Applications.
Placing magnetic storage media on top of the UPS may result in data corruption.
NOTICE
Do not connect equipment that could overload the UPS or demand half-wave rectification
from the UPS, such as electric drills, vacuum cleaners, laserjet printers and hair dryers.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
GLOSSARY OF SYMBOLS
Risk of electrical shock
Indicates caution followed by important instructions
!
Indicates the unit contains a valve-regulated, lead-acid battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
ON/Alarm Silence/Manual Self-Diagnostic Test
OFF
Status Change Button
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
1.0 INTRODUCTION
™
The Liebert PSI XR is a 2U, line-interactive UPS that may be installed in a rack or used as a tower
UPS.
Status indicators on the front of the Liebert PSI XR display load level, battery level, buck/boost, site-
wiring fault and battery status. Controls include a combination ON/ Alarm Silence/Manual Self-Diag-
nostic button, an Off button and a Display Status Change button.
The Liebert PSI XR has USB, DB-9 (RS232/contact closure) and SNMP interface ports. The DB-9 and
USB ports provide detailed operating information including voltages, currents, and alarm status to
the host system when used in conjunction with Liebert MultiLink™ shutdown software.
Figure 1
Front view of UPS, rack mount
Liebert PSI XR
rack-mount configuration
Display rotates for use as tower
Liebert PSI XR
tower configuration
Display rotates for use in rack
Figure 2
1000 and 1500VA—rear view
Input Circuit Breaker
(12A for 1000VA;
15A for 1500VA)
Output Circuit Breaker
(8A for 1000VA;
15A for 1500VA)
Liebert
IntelliSlot
Port
Receptacles
NEMA 5-15R
RS232 (DB-9) Port
USB
Port
PUT
OUTPT
EPO
EPO
FUNCTION
VOLTAGE=110V
VOLTAGE=120V
VOLTAGE=127V
2
1
DC 24V
RJ-45 Data Line
Connectors
Voltage Configuration
DIP Switch
Power Cord; 5-15P
(not shown for clarity)
External Battery
Cabinet Connector
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
Figure 3
1920VA—rear view
15A Output Circuit Breaker
for Receptacles #3 & #4
Receptacles #3 and #4
NEMA 5-15R
Power Cord; 5-20P
(not shown for clarity)
RS232 (DB-9)
Port
Receptacles #1 and #2;
NEMA 5-20R T-Slot
Receptacles
#5 and #6
NEMA 5-15R
Liebert
IntelliSlot
Port
30A Input
Circuit Breaker
INPUT
EPO
FUNCTION
VOLTAGE=110V
VOLTAGE=120V
VOLTAGE=127V
2
1
OUTPUT
DC 48V
EPO
External Battery
Cabinet Connector
USB Port
RJ-45 Data
Line Connectors
20A Input Circuit Breaker
Receptacles #1 and #2
15A Output Circuit Breaker
for Receptacles #5 & #6
Voltage Configuration
DIP Switch
Figure 4
3000VA—rear view
15A Output Circuit Breaker
for Receptacles #3 & #4
Power Cord; L5-30P
Receptacles #3 and #4
NEMA 5-15R
(not shown for clarity)
NEMA L5-30R
Receptacle
Receptacles #1 and #2;
NEMA 5-20R T-Slot
RS232
(DB-9)
Port
Liebert
IntelliSlot
Port
30A Input
Circuit Breaker
Receptacles
#5 and #6
NEMA 5-15R
INPUT
EPO
FUNCTION
VOLTAGE=110V
VOLTAGE=120V
VOLTAGE=127V
2
1
OUTPUT
DC 48V
EPO
USB Port
External Battery
Cabinet Connector
15A Output Circuit Breaker
for Receptacles #5 & #6
RJ-45 Data
Line Connectors
Voltage Configuration
DIP Switch
20A Output Circuit Breaker
Receptacles #1 and #2
5
Download from Www.Somanuals.com. All Manuals Search And Download.
What’s Included
2.0 WHAT’S INCLUDED
The Liebert PSI XR is shipped with the following items:
• Multi-Language User Manual on CD
• Liebert MultiLink Shutdown Software and User Manual on CD
• DB-9 Serial Cable
• USB Cable
• Tower Stand
• Rack-Mount Handles
• Battery-UPS Tab
• Mounting Hardware
• Fixed Mounting Rails
• EPO Connector
Figure 5
Accessories
Liebert Shutdown
Software Program
Liebert MultiLink
Shutdown Software &
User Manual on CD
Battery-UPS Tab
DB-9
Serial Cable
6 ft (1.8m)
USB cable
6 ft (1.8m)
Rack-Mount
Handles
Mounting Hardware
(Screws and Washers)
Fixed
Mounting Rails
Tower Stand
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
3.0 INSTALLATION
3.1 Preparation
CAUTION
when lifting or moving either the UPS or battery cabinets.
!
The Liebert PSI XR may be installed in either a tower or rack configuration. Determine the method
that suits the application and proceed.
Decide where to install the Liebert PSI XR. The UPS must be installed indoors in a controlled envi-
ronment. Place it in an area with unrestricted airflow around the unit, away from water, flammable
Maintain a minimum clearance of 12 inches (305mm) in the front and rear of the UPS. Maintain an
ambient temperature range of 32°F to 104°F (0°C to 40°C).
Figure 6
Placing the Liebert PSI XR
32 F (0 C)
104 F (40 C)
m
m
5
0
3
/
.
n
i
2
1
Relative humidity
(non-condensing)
0% ~ 90%
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
3.3
Rack-Mount UPS Conversion and Installation
See Figure 8 when installing the Liebert PSI XR in a rack. External battery cabinets are installed in
same manner.
Figure 8
Convert the Liebert PSI XR for rack installation
Step 1
Step 2
Loa
Loa
d
d
Le
Le
vel
Bat
tery
Lev
vel
Bat
tery
Lev
el
el
Step 4
Step 3
Loa
d
Le
vel
Bat
tery
Lev
el
Step 5
Loa
d
Le
vel
Bat
tery
Lev
el
WARNING
!
!
Placing heavy equipment near the top of a rack may increase the risk of tipping. Place the
UPS, and battery cabinet if one is being used, in the bottom of the rack.
CAUTION
Lifting equipment into rack may be a two-person job, depending on weight of equipment.
NOTICE
When rack-mounted, the UPS must be supported by a shelf, slide rails, brackets or fixed rails
on each side. The rack-mount handles WILL NOT support the weight of the UPS. They are
used to move the UPS into and out of the rack.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
3.4
Orient Display for Installation
The Liebert PSI XR features a rotating display that may be oriented for either tower or rack installa-
tions.
To set the display for your installation, pull out on the display and rotate it until it is oriented cor-
rectly, then press it into the UPS until it is seated.
Figure 9
Adjusting the UPS display
3.5
Connect Input Power and Load
Connect input power to the UPS, then plug the equipment into the outlets on the rear of the UPS.
These UPS outlets provide battery backup and surge protection to the equipment when utility power
Figure 10 Connect input power and load
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
3.6
Connect Network Surge protection
Connect a 10 base-T/100 network cable to the RJ-45 network surge protection IN jack on the rear of
Figure 11 Connect network surge protection
Network
Equipment
INPUT
OUTPUT
EPO
FUNCTION
2
1
VOLTAGE=110V
VOLTAGE=120V
VOLTAGE=127V
DC 24V
Network surge
protection IN jack
Network surge
protection OUT Jack
3.7
Connect Computer Interface Port
Determine what type of communication connection to use to manage the UPS. The Liebert PSI XR
can be monitored with any of these communication methods:
• serial
• contact closure
• USB
• SNMP
Connect the appropriate, factory-supplied cable to the interface port on the rear of the UPS and to the
computer interface port. See the Liebert MultiLink shutdown software user manual on the included
Figure 12 Connect computer interface port
USB connector is to left of DB-9 port
on the UPS; USB port on computer varies
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
3.8
EPO Switch
The Liebert PSI XR is equipped with an Emergency Power Off (EPO) switch. The user must supply a
means of interfacing with the EPO circuit to allow disconnecting the UPS input feeder breaker to
interrupt all sources of power to the UPS and connected equipment to comply with national and local
wiring codes and regulations.
Figure 13 EPO connection for normally open operation
1 = EPO+
2 = Ground
1
2
Short Pin 1 and Pin 2 to enable the EPO function
3.9
External Battery Cabinet Installation
Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery
run time. External battery cabinets are designed to be placed all on one side of the UPS or stacked
beneath the UPS. The batteries have a maximum run time of three hours at full load.
1. Install the external battery cabinet in tower- or rack-configuration (see Figure 14 or 3.3 - Rack-
2. Connect the external battery cabinet cable to the rear of the external battery cabinet, then to the
Figure 14 Install the external battery cabinet in tower installation
Connect the top of the UPS
to the top of the battery cabinet
with the Battery UPS Tab and
hardware
If two or more battery cabinets are
used in a tower setup, the tower stand
must be extended with the spacers
included with each battery cabinet.
Connect tower stand and set
the UPS and battery cabinet in
them; check to ensure stability
NOTICE
install external battery cabinets with connectors that are a different color from the battery
connector on the UPS.
Table 1
Battery cabinet connector color key
UPS Model
Nominal System Voltage (connector color) External Battery Cabine Model
PS1000RT3-120XR
PS1000RT3120XRW
24VDC (Red)
48VDC (Gray)
12
PSRT3-24VBXR
PSRT3-48VBXR
PS1500RT3-120XR
PS1500RT3120XRW
PS2200RT3-120XR
PS2200RT3120XRW
PS3000RT3-120XR
PS3000RT3120XRW
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls and Indicators
4.0 CONTROLS AND INDICATORS
Buttons on the front panel display control the Liebert PSI XR. Eight LEDs indicate the UPS’s status.
Figure 16 Display and status indicators
1
2
3
4
5
Load Level
Battery Level
6
7
8
9
10
11
Table 2
Item
Display and status indicators function, legend
Name Status Indicators Description
1
LED 1
LED 2
LED 3
LED 4
LED 5
AVR Boost
UPS Operation in AVR Boost Mode
UPS Operation in AVR Buck Mode
Battery Fault/Weak
2
AVR Buck
3
4
Battery Condition
Grounding/Site Wiring Fault UPS Grounding/Site Wiring Fault
5
Overload
UPS Overload
1 to 5
Load/Battery Level
Status Change Button
OFF Button
Indicate Load/Battery Level
Switches Display from Load Level Indicators
to Battery Level Indicators
6
7
8
UPS Off
Turn on UPS, Manual Self-Diagnostic (Normal Mode),
Silence Alarm (Battery Mode)
ON Button
9
LED 9
Normal Mode
UPS Operation in Normal Mode
UPS Operation in Battery Mode
UPS Fault
10
11
LED 10 Battery Mode
LED 11 UPS Fault
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls and Indicators
4.1
Control Buttons
4.1.1 On/Alarm Silence/Manual Self-Diagnostic Test
This button controls output power to connected load(s). It has three functions:
• On
• Alarm Silence
• Manual Self-Diagnostic Test
ON—Start the UPS by pressing this button for more than 3 seconds, then releasing the button (an
alarm will sound briefly). If the ON button is pressed and utility is outside input parameters, the UPS
will start on battery (dark start).
Alarm Silence—Silence a battery mode audible alarm by pressing this button for longer than one
second, then releasing it.
Manual Self-Diagnostic Test—To initiate a Manual Self-Diagnostic, press this button for at least
three (3) seconds while operating from utility power. UPS will switch to Battery Mode to detect bat-
tery voltage and whether the UPS is operating normally.
If LED indicates the battery is weak: Allow the UPS to recharge the batteries for 8 hours.
Retest the battery after recharge.
If LED still indicate battery weak after the battery has been retested, contact your local
dealer, Emerson representative or Liebert Applications.
If LED indicates a Battery Fault: Contact your local dealer, Emerson representative or Liebert
Applications.
If LED indicates UPS Fault: Remove the load, retest the self diagnostic test, if LED indicated
UPS Fault, Contact your local dealer, Emerson representative or Liebert Applications.
NOTE
4.1.2 Off Button
When the UPS is operating in either Normal Mode or Battery Mode, pressing the Off button for more
than three seconds will shut down the UPS.
4.2
Status Indicators
4.2.1 Status Change Button
The Status Change Button determines the information displayed by the five LEDs on the front panel.
The default information shown by the LEDs is the load level on the UPS. Pressing the Status Change
Button while the UPS is On prompts the LED display to show battery capacity for 5 seconds. This
function assists in assessing the meaning of status indicators as described in 4.2.4 - UPS Status
4.2.2 Load Level Indicator
The five LEDs at the top of the front panel illuminate with a steady glow to indicate the load level on
the output of the UPS. The LEDs show the load level as a range, ± 5%. The LEDs’ load level meanings
and colors are:
LED 1
LED 2
LED 3
LED 4
LED 5
10 - 24% — Green
25 - 49% — Green
50 - 74% — Yellow
75 - 99% — Yellow
100% or greater — Red
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls and Indicators
4.2.3 Battery Level Indicator
The five LEDs illuminate with a steady glow to indicate battery capacity. Battery capacity is shown
for five seconds after the Status Change Button is pressed. The LEDs show the battery capacity as a
range, ± 5% The LEDs’ battery level meanings and colors are:
LED 1
LED 2
LED 3
LED 4
LED 5
100 - 76% — Green
75 - 51% — Green
50 - 26% — Yellow
25 - 11% — Yellow
10% or less — Red
4.2.4 UPS Status Indicators
LEDs on the display panel illuminate with a steady glow or flash to indicate the UPS’s status:
Normal Mode—The Normal Mode indicator illuminates (LED 9) with a steady glow when utility
power is available and within the input specifications.
Battery Mode—The Battery Indicator illuminates (LED 10) with a steady glow when the UPS is
operating on battery
AVR Boost, AVR Buck—When the UPS is in AVR Boost/Buck Mode, the LED display will indicate
the relative load level on the output of the UPS and will flash LED 1 (boost) or LED 2 (buck) to indi-
cate the mode.
Weak Battery—When the UPS battery voltage is low, the LED display will indicate the relative load
level on the output of the UPS and LED 3 will flash as a warning.
Site-Wiring Fault—In case of a site-wiring fault, the LED display will indicate the relative load
level on the output of the UPS and LED 4 will flash as a warning.
Overload—When UPS operates in overload status, the LED display will indicate the relative load
level on the output of the UPS and LED 5 will flash as a warning.
Table 3
Status indicators—color, illumination mode
Status
LED 1
LED 2
LED 3
LED 4
LED 5
LED 9
LED 10
LED 11
Green
Steady
Normal Mode
AVR Boost
AVR Buck
Green
Flashes
Green
Steady
Green
Flashes
Green
Steady
Battery Mode
(dark start)
Yellow
Steady
Yellow
Flashes
Weak Battery
Site-Wiring Fault
Overload
Yellow
Flashes
Red
Flashes
Battery Fault
Shutdown
Yellow
Steady
Red
Steady
Overload
Shutdown
Red
Steady
Red
Steady
UPS Output
Abnormal
Shutdown
Yellow
Steady
Red
Steady
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Operational Modes
5.0 OPERATIONAL MODES
5.1
5.2
Normal Mode
When the UPS is in Normal Mode, the Normal Mode Indicator illuminates green.
Buck/Boost Mode
The Automatic Voltage Regulator (AVR) circuitry compensates for fluctuations in utility power, such
as voltage surges and sags. When the Liebert PSI XR detects an abnormality, it raises the undervolt-
age (boost) or lowers the overvoltage (buck) as needed. The AVR operates automatically and main-
tains the output voltage to the connected equipment, without utilizing the batteries.
LED 1 flashes green and LED 9 illuminates steady green when the UPS is in Boost Mode. LED 2
flashes green and LED 9 illuminates steady green when the UPS is in Buck Mode (see 9.0 - Trouble-
shooting for details).
5.3
5.4
Battery Mode
The UPS switches to Battery Mode in the event of an extreme input voltage/frequency condition or
utility failure.
When the UPS is in Battery Mode, the Battery Indicator illuminates amber and an alarm sounds at
two-second intervals. As capacity decreases, fewer indicators remain illuminated.
When a Low Battery condition occurs, the Battery Indicator flashes amber and an alarm sounds at
Battery Recharge Operation
Once utility power is restored, the UPS resumes normal operation and the Battery Charger begins
recharging the batteries.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Communication
6.0 COMMUNICATION
6.1 DB-9 Connector
The UPS has a DB-9 (9 pin female) connector on the rear to allow UPS status communications with a
computer running Liebert MultiLink shutdown software. The connection provides serial communica-
tion, On Battery and Low Battery signals. Liebert MultiLink software and a 6 ft. (1.8m) DB-9 serial
cable are shipped with the UPS.
When power is interrupted and battery power is low, Liebert MultiLink software can signal the host
computer to gracefully shut down the operating system.
Table 4
DB-9 pin assignment
DB-9 Pin
Assignment Description
1
2
3
4
5
6
7
8
9
Low Battery (open collector)
UPS TxD
UPS RxD
Remote Shutdown (5-12V); on-battery operation
Common
Output Off, (short to Pin 5, non-latching); any mode operation
Low Battery (open emitter)
Utility Fail (open emitter)
Utility Fail (open collector)
Pin Assignment
Collector to Emitter*
Open
Collector
6
7
8
9
(+)
(-)
330 Ohms
Open
Emitter
1
2
3
4
5
6.2
Remote Shutdown Via the DB-9 Connector
The Liebert PSI XR can be shut down remotely by shorting Pins 5 and 6 or via Pins 4 and 5 of the DB-
9 connector.
6.2.1 Any Mode Shutdown Via Pins 5 & 6
When Pin 6 is shorted to Pin 5, the UPS output is shut Off no matter what mode the UPS is operat-
ing. The UPS cannot be started as long as the pins are shorted. When the short is removed, the UPS
output can be enabled by pressing the ON/Alarm Silence/Manual Self-Diagnostic button.
6.2.2 Battery Mode Shutdown Via Pins 4 & 5
While the UPS is operating on battery, a 5-12VDC signal for 2 seconds or longer is required to signal
a shutdown. Signals for less than 2 seconds are ignored.
After Pin 4 receives the shutdown signal, a 2-minute shutdown timer begins a countdown. The shut-
down timer cannot be stopped: If utility power returns during the 2-minute countdown, the shutdown
timer continues until the end of 2 minutes and the UPS turns Off. The UPS will restart 10 seconds
after utility power returns.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Communication
6.3
6.4
RJ-45 Data Line Protection Connectors
Data line (in and out) connectors on the rear of the UPS provide transient voltage surge suppression
(TVSS) for network devices.
UPS Communications
®
The Liebert PSI XR is equipped with a Liebert IntelliSlot port to provide advanced communication
and monitoring options.
Liebert MultiLink software continually monitors the UPS and can shut down your computer or server
via USB and RS-232 in the event of an extended power failure.
The Liebert IS-WEBRT3 provides SNMP and Web-based monitoring and control of the UPS across
the network.
NOTE
The USB, SNMP and contact closure communications operate in parallel. Using the Liebert
IS-WEBRT3 disables the serial communications of the DB-9.
6.5
UPS Inverter/Transfer Voltage Configurations
A two-pin DIP switch on the rear of the PSI XR permits setting the UPS to operate at nominal volt-
ages of 110V, 120V or 127V. This feature will change the high and low points at which the UPS
switches to battery power. It also changes the UPS’ output voltage when the UPS is operating in bat-
tery mode. The factory default setting is 120 VAC.
Figure 17 DIP switch settings for 120V system
FUNCTION
1
2
Voltage = 110V
Voltage = 120V
Voltage = 120V
Voltage = 127V
1
2
ON
DIP
Table 5
Voltage configurations
Setting
110
Input Voltage Range
83~138
Output Voltage (Battery Mode)
110VAC
120VAC
127VAC
120
90~150
127
96~159
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Battery Maintenance
7.0 BATTERY MAINTENANCE
7.1
Battery Charging, Storage
The batteries are valve-regulated, nonspillable, lead acid and must be kept charged to retain their
design life. The Liebert PSI XR continuously charges the batteries when connected to the utility sup-
ply, even while the UPS is switched Off.
If the Liebert PSI XR will be stored for an extended period, Liebert recommends connecting the UPS
to input power for at least 8 hours every four to six months to keep the batteries charged.
7.2
Internal Battery Replacement Procedure
NOTICE
This UPS is equipped with internal batteries that the user can replace without shutting down
the UPS or connected loads (hot swappable). Caution must be exercised when replacing the
batteries because the load is unprotected from power fluctuations and power failures.
To replace the batteries:
1. Remove the two screws on the left side of the front bezel.
2. Pull the front bezel off the UPS.
3. Remove the screw on the battery connectors holder.
4. Remove the two screws on the battery bracket.
5. Disconnect the two slotted, red/gray and black battery connectors.
6. Grasp the battery pack assembly by the handle and pull it out of the front of the UPS.
7. Unpack the new battery assembly, taking care not to destroy the packing.
8. Compare the new and old battery assemblies to make sure they are the same. If so, proceed with
replacement. If they are different, STOP and contact your local dealer, Emerson representative or
Liebert Applications.
9. Slide the new battery pack into the UPS.
10. Reattach the battery bracket with the two screws.
11. Reconnect the slotted, red/gray and black battery connectors.
12. Reinsert the screw on the battery connectors holder.
13. Reattach the front bezel.
Figure 18 Battery replacement
Load Le
vel
Batter
y
Le
vel
Load Le
vel
Batter
y
Le
vel
l
ve
e
L
d
a
o
L
l
ve
e
L
ry
tte
a
B
Load Le
vel
Batter
y
Le
vel
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
8.0 SPECIFICATIONS
Table 6
Liebert PSI XR specifications
PS1000RT3-120XR PS1500RT3-120XR PS2200RT3-120XR
PS3000RT3-120XR
Model Number
PS1000RT3120XRW PS1500RT3120XRW PS2200RT3120XRW PS3000RT3120XRW
*
Power Rating, VA/W
1000VA/900W
1500VA/1350W
1920VA/1920W
3000VA/2700W
Dimensions, W x D x H, in (mm)
17.3 x 19.3 x 3.5
(440 x 490.5 x 88)
17.3 x 19.3 x 3.5
(440 x 490.5 x 88)
17.3 x 27.6 x 3.5
(440 x 700.5 x 88)
17.3 x 27.6 x 3.5
(440 x 700.5 x 88)
Unit
22 x 24.1 x 9
(560 x 612 x 228)
22 x 24.1 x 9
(560 x 612 x 228)
22 x 34.8 x 9.0
(560 x 884 x 228)
22.0 x 34.8 x 9
(560 x 884 x 228)
Shipping
Weight, lb (kg)
Unit
56 (25)
64 (29)
62 (28)
70 (32)
92 (42)
105 (48)
115 (52)
Shipping
101 (46)
Input AC Parameters
Surge Protection
570J
Voltage Range
Without Battery Operation
83 to 159 VAC (configurable)
45~65Hz, (±0.5Hz)
Frequency Range
Input Power Cord,
10ft (3m) attached
NEMA 5-15P plug
(6) NEMA 5-15R
NEMA 5-15P plug
NEMA 5-20P plug
NEMA L5-30P plug
(4) NEMA 5-15R
(2) NEMA 5-20R T-Slot,
accepts15A Plug
(4) NEMA 5-15R
(6) NEMA 5-15R (2) NEMA 5-20R T-Slot,
accepts15A Plug
Output Receptacles
(1) NEMA L5-30R
Voltage (Normal Mode)
Voltage (Battery Mode)
Transfer Time
110/120/127 VAC (configurable)
110/120/127 VAC; ±5% before low-battery warning
4-6 ms typical
Sinewave
Battery Waveform
Battery Parameters
Type
Valve-regulated, nonspillable, lead acid
Quantity x Voltage x Ah
Recharge Time
4 x 12 x 7.2
4 x 12 x 9
8 x 12 x 7.2
8 x 12 x 9
5 hours to 90% of rated capacity, after full discharge into resistive load
Battery Backup Time
Full Load
5 minutes
Half Load
10 minutes
Environmental
Operating Temperature, °F (°C)
Storage Temperature, °F (°C)
Relative Humidity
Operating Altitude
Audible Noise
32 to 104 (0 to 40)
5 to 104 (-15 to 40)
0% to 90%, non-condensing
Up to 3000m (10,000 ft)
<40 dBA, internal fan(s) Off; <45 dBA, internal fan(s) On
Agency
Safety
UL 1778, c-UL Listed
FCC Part 15, Class A
UL 497 B
Emissions
Network Surge
Transportation
ISTA Procedure 1A Certification
*
NEC limits the input current rating of the PS2200RT3-120XR and PS2200RT3120XRW models to 80% of the input plug's rating. Up to
2200VA/1980W is available by contacting a certified electrician to change the input plug to 30A plug. Emerson Network Power assumes no
liability for damage caused by miswiring or misapplication of the input plug.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
Table 7
Battery cabinet specifications
Model Number
PSRT3-24VBXR
PSRT3-48VBXR
PS1000RT3-120XR
PS1000RT3120XRW
PS1500RT3-120XR
PS1500RT3120XRW
PS2200RT3-120XR
PS2200RT3120XRW
PS3000RT3-120XR
PS3000RT3120XRW
Used w/UPS Model
Dimensions, W x D x H, in (mm)
Weight, lb (kg)
Unit
17.3 x 19.3 x 3.5 (440 x 490.5 x 88)
Shipping
22 x 26.6 x 9 (560 x 675 x 228)
Unit
64 (29)
73 (33)
Shipping
Batteries
Type
Valve-regulated, nonspillable, lead acid
Quantity x Voltage x Ah
Manufacturer
8 x 12 x 7.2
8 x 12 x 7.2
CSB, YUASA or Equivalent
Environmental
Operating Temperature, °F (°C)
Storage Temperature, °F (°C)
Relative Humidity
32 to 104 (0 to 40)
5 to 104 (-15 to 40)
0% to 90%, non-condensing
10,000 ft. (3000m)
Maximum Operating Altitude
Agency
Safety
Emissions
UL 1778, c-UL Listed
FCC Part 15, Class A
Transportation
ISTA Procedure 1A Certification
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
Table 8
Liebert PSI XR battery run times
Number of Batteries
Load %
10
1000VA
82
1500VA
81
1920VA
76
3000VA
75
25
43
32
32
32
Internal Battery
50
15
13
14
13
75
9
8
8
8
100
10
6
5
5
5
272
139
73
222
109
55
161
80
142
70
25
Internal Battery
+ 1 External
50
45
31
Battery Cabinets
75
51
31
25
17
100
10
31
18
15
12
438
231
129
84
357
175
95
241
128
67
205
106
56
25
Internal Battery
+ 2 External
Battery Cabinets
50
75
61
47
31
100
10
65
46
29
18
614
324
181
126
96
492
241
131
84
322
170
95
267
139
73
25
Internal Battery
+ 3 External
Battery Cabinets
50
75
62
50
100
10
64
48
31
789
385
233
162
124
964
509
285
197
151
1140
601
336
233
179
627
308
167
114
82
483
255
143
100
72
329
171
95
Internal Battery
+ 4 External
Battery
25
50
Cabinets
75
62
100
10
47
762
374
203
139
106
897
440
239
163
124
564
298
167
116
84
392
204
113
74
25
Internal Battery
+ 5 External
Battery Cabinets
50
75
100
10
56
644
341
191
133
102
454
236
131
85
25
Internal Battery
+ 6 External
Battery Cabinets
50
75
100
65
Run times are in minutes, assume fully charged batteries and are typical at 77°F (25°C) with resistive loads.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
9.0 TROUBLESHOOTING
The information below indicates various symptoms a user may encounter if the Liebert PSI XR expe-
1. An alarm sounds, alerting that the UPS requires attention. The alarm can be silenced except for
low battery, overload warning and fault.
2. One or more additional indicators will be illuminated to provide a diagnostic aid to the operator,
as described below:
If the UPS fails to operate properly, turn Off the unit and repeat the steps in 3.0 - Installation. If the
Table 9
Troubleshooting—problems, causes and solutions
Problem Cause
Solution
Check the circuit breaker on the
rear of the UPS.
If it is tripped, reset it and restart the
UPS. For help, contact your local
dealer, Emerson representative or
Liebert Applications.
Short circuit
UPS will not start
Battery is disconnected or
completely discharged
Check for proper connection of
battery or batteries.
UPS not plugged in
Plug in the power cord securely.
Reset the circuit breaker and restart
the UPS.
Circuit breaker tripped
UPS starts on battery, but will not
switch to AC (dark start)
Wait until voltage drops to an
appropriate level or have the utility
power checked by a properly
trained and qualified electrician.
AC overvoltage
Remove the load and turn on the
UPS again. For help, contact your
local dealer, Emerson
representative or Liebert
Applications.
Short circuit or UPS output is
abnormal; LED 10 and LED 11
illuminate and sound audible
alarm
Check load level display and
remove nonessential loads.
Recalculate the load and reduce
equipment connected to UPS - the
total wattage must not exceed the
capacity of the UPS.
Overload; LED 5 and LED 11
illuminate and sound audible
alarm
UPS shuts down
LED 3 and LED 11 illuminate and
sound audible alarm
Recharge the battery for 8 hours,
then turn ON the UPS.
Consult the Liebert MultiLink
software user manual or contact
your LAN administrator.
Liebert MultiLink shutdown
software
Site Wiring Fault, UPS detected a
Site Wiring Fault LED (LED 4) flashing line-to-neutral reversal or a loss of
Have the utility checked by a
properly trained and qualified
electrician.
proper grounding.
Batteries weak
Battery weak LED (LED 3) flashing
Recharge batteries.
Replace batteries.
Batteries need to be replaced
NOTE
The 1920VA UPS will sound an Overload alarm under certain Low Line conditions when it is
fully loaded and it exceeds the input current rating. Unless the load is reduced, the condition
will trip the branch circuit breaker.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Notes
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Ensuring The High Availability
Of Mission-Critical Data And Applications.
Technical Support / Service
Web Site
Emerson Network Power, the global leader in enabling business-critical
continuity, ensures network resiliency and adaptability through
a family of technologies—including Liebert power and cooling
technologies—that protect and support business-critical systems.
Liebert solutions employ an adaptive architecture that responds
to changes in criticality, density and capacity. Enterprises benefit
from greater IT system availability, operational flexibility and
reduced capital equipment and operating costs.
Monitoring
800-222-5877
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
© 2008 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change
without notice.
852 2572220
Fax: 852 28029250
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks
or registered trademarks of their respective owners.
SL-23315_REV02_08-08
Emerson Network Power.
EmersonNetworkPower.com
The global leader in enabling Business-Critical Continuity.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power