unqualified to replace the battery, do not open battery door. Refer to
qualified service personnel.
INTRODUCTION & SYSTEM DESCRIPTION
Congratulations on choosing the Liebert PowerSure™. It provides continuous,
conditioned power to microcomputers and other data processing equipment.
Upon generation, AC power is clean and stable. However, during transmission, it
may be subject to load variations or accidents which cause power problems like
low voltage, voltage spikes, or complete power failure. These problems may
interrupt computer operations, cause data loss, or even damage equipment.
The UPS provides protection from many of these disturbances. It smoothes out
voltage variations and, in the event of complete power failure, it supports
equipment long enough for an orderly shutdown. These compact UPS units are
available in three ratings: 250, 400, and 600 VA. This manual includes
specifications for each model.
Normally, the UPS filters and connects AC utility input power to its AC outputs;
but when the UPS senses a power failure, it lights the battery LED (400 & 600
VA only) and provides AC power to equipment through a maintenance free,
sealed, lead acid battery.
The UPS contains a counter which automatically initiates a 15-second battery
test every 7 days and upon start-up. The UPS resets the counter after back-up
operation, manual battery test, or if the UPS is switched OFF. The operator may
perform a manual battery test by pressing the BATTERY TEST button on the
back of 400 and 600 VA models.
A control circuit monitors power input and battery condition and upon sensing a
fault, sounds an alarm and flashes a visual indication of the UPS status. In
addition, the 400VA and 600VA UPS models have a communications port which
enables the UPS to inform a computer equipped with SiteNet® software of the
power failure. SiteNet® automatically saves data and performs an orderly
shutdown. Cables and software are available as optional computer/LAN
Interface Kits. Consult your dealer for the kit suitable for your application.
CONDITIONS OF USE: The utility receptacle must be within 6 feet of the UPS.
This model utilizes a 110V to 120V AC 60 Hz supply voltage. Models are
available for other supply voltages.
Your UPS is designed to protect only Communication and Data Processing
equipment. Maximum load must not exceed that shown on UPS rating label. If
uncertain, consult your dealer or representative.
Placing magnetic storage media on top of the UPS may result in data corruption.
CAUTION: This equipment complies with Part 15, Subpart B of FCC rules for
Class B computing devices. Equipment operation in residential areas may cause
interference to radio and TV reception. The operator must take necessary steps
to correct interference.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
250 VA / 115 V
400 VA / 115 V
1. ON/OFF Button
600 VA / 115 V
2. Battery Light (400/600 Only)
3. Check Light (400/600 Only)
4. AC Light
5. Battery Test Button / Alarm Silen
(400/600 Only)
6. Option Switches
7. Output Receptacles
8. Power Cord Input
9. Circuit Breaker
10. Communications Port (400/600 Only)
ATTENTION: Please refer to these drawings when reading this
manual. This manual references the various parts of your UPS by
number.
GENERAL INSTALLATION
1. Unpack the unit and check the contents. There should be one UPS with
power cord (8) and one User’s Manual.
2. Check the items for damage. If any appear faulty or damaged, contact your
dealer immediately. Store the packaging in a safe place for possible future
shipment of UPS.
3. Place the UPS on a sturdy, dry surface in a well ventilated area away from
direct heat sources. Leave at least 4 inch (100 cm) clearance all around the
UPS to provide adequate ventilation.
4. Plug in the UPS and turn the UPS control switch (1) to ON.
5. Plugging in the UPS charges the batteries. Charge the UPS batteries for 12
hours before connecting the load equipment.
6. After charging the UPS, shut down your computer and unplug it. Plug the
computer equipment into the UPS AC outputs (7).
7. When all equipment is plugged in, the UPS is ready for normal operation.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING INSTRUCTIONS
1. Check that all power connections to and from the unit are secure and fitted
with
the correct cables.
2. Press the UPS ON/OFF Button (1) to ON.
3. Switch your equipment ON at their respective power switch(es).
4. Check the condition of the UPS front panel LED's. The 250VA AC LED (4)
should be lit. For the 400/600 VA models, the AC LED (4) should be lit, and
the Check and Battery LED's (3 & 2) should be unlit.
5. Check the operation of your equipment. It should display normal operational
conditions.
6. If any function provides an abnormal condition, refer to the troubleshooting
guide later in this manual. If a problem persists, consult your dealer or call
Tech Support at 1-800-222-5877.
STARTING FROM BATTERY (400/600 VA only): Turn OFF UPS. Press and
hold BATTERY TEST button (5) for 4 seconds. Switch ON UPS and release
BATTERY TEST button (5). UPS will run in backup mode with the Battery LED
(2) lit. To stop, switch OFF at front panel.
Battery Back-up Time
Back-up Time (minutes)
600 VA Models
400 VA Models
250 VA Models
5
Download from Www.Somanuals.com. All Manuals Search And Download.
COMPUTER/LAN INTERFACE (400/600 VA ONLY)
Optional SiteNet® 1 kits provide connection to a wide range of popular computer
operating systems such as Novell, UNIX, UNISYS, SUN, WINDOWS and many
others. SiteNet® 1 software automatically performs an orderly shutdown of
computer operating systems in the event of a power outage and/or low battery
conditions.
The SiteNet ®1 kit supplies a cable to connect supported computer systems to
the UPS communications port (10). The table below shows connector details.
Note: Your dealer supplies computer communications kits separately, if you wish. They
come with installation instructions, cable connections, and appropriate computer software.
1
COLLECTOR TO EMITTER
INTERFACE FUNCTION
DB25
ADAPTER
Open Collector
(+)
UPS Shutdown/Active High*
On Battery/Return
On Battery/Normally Open
Low Battery/Normally Open
Low Battery/Return
19
17
16
11
9
330 Ohms
(-)
Return
UPS Shutdown/Return
*Remote Shutdown (5-12V DC, 5-10 mA. max.); battery
operation
7
1
Maximum voltage and current on pins
11 & 16 are +40V DC; 1.0mA
6
Download from Www.Somanuals.com. All Manuals Search And Download.
OPTION SWITCH SETTINGS
On the back of your UPS is a bank of option switches (6) with a removable
plastic cover. These switches determine transfer levels and operating frequency.
Slide the switches to the left to turn them OFF, to the right to turn ON. Turn OFF
equipment and UPS and unplug the UPS prior to changing switch settings, or the
UPS will ignore the new settings. Replace the plastic option switch cover.
Option Switch 1: 50/60 Hz Select – When OFF, this switch sets UPS for 60 Hz
utility. Output in backup mode will be 60 Hz. When ON, the switch sets UPS for
50 Hz utility and output in backup mode is 50 Hz. The switch must match the
utility frequency or the UPS will not start. The factory setting is 60 Hz.
Option Switch 2: High Line Transfer –
250VA model: When ON, this switch transfers the UPS to battery operation
when the utility voltage reaches 135 VAC. When OFF, the UPS will not
transfer to battery. Factory setting is ON.
400/600VA models: You may select at which voltage the UPS will transfer
to battery operation when it encounters a high utility voltage. The ON
position transfers the UPS to battery operation at 135VAC; the OFF position
transfers at 140VAC. Factory setting is 135 VAC.
Option Switch 3 & 4: Low Voltage Transfer Select – Low voltage transfer is
the voltage level at which battery operation starts. You may set the low voltage
transfer of the UPS to 90V, 95V, or 100V. The factory setting is 95V. This option
reduces excessive battery usage in brownout conditions. Make sure your
computer equipment can operate at 90 VAC before selecting the lowest limit
(most will). Refer to the tables below to change switch settings:
250 VA MODEL
400/600 VA MODELS
VOLTAGE
100V
95V
SWITCH #3
ON
SWITCH #4
VOLTAGE
SWITCH #3
OFF
SWITCH #4
N/A
OFF
ON
100V
95V
N/A
OFF
ON
OFF
OFF
ON
90V
90V
ON
Option Switch 5: Line Neutral Reverse Alarm – When ON, this switch enables
the L-N reverse alarm, which detects wiring faults. When OFF, the alarm is
disabled. The factory setting is ON.
BATTERY TEST BUTTON
The Battery Test Button (5) on the 400 and 600 VA models tests the condition of
the battery. If the charge is sufficient, the UPS lights the Battery Light (2), runs
on battery power for 15 seconds, then returns to utility power. If the battery fails
the test, the Check Light (3) illuminates and the UPS immediately returns to utility
power. The Check Light remains lit while on utility power. A battery in
unacceptable condition requires recharge or replacement of the battery.
Pressing the Battery Test Button (5) also silences alarms.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
BATTERY CARE AND USE
STORAGE: If the unit is not in continued use, plug in the UPS every 4 to 6
months for 12 hours to recharge the battery. Warranty is void if the battery
discharges below the minimum battery cutoff point. To prevent such discharge,
DO NOT leave UPS ON for more than two days without plugging it in.
BATTERY LIFE & REPLACEMENT: Excessive battery use, storage at high
ambient temperatures, and lengthy periods in a discharged state greatly reduce
battery life. Your UPS maximizes battery life by limiting the depth of battery
discharge. You may replace the UPS battery yourself, but if you feel unqualified,
refer battery replacement to qualified personnel. Contact your local dealer or call
Liebert for a replacement battery.
WARNING: To replace batteries, turn OFF UPS and unplug it from utility supply.
CAUTION: Observe proper precautions. When replacing batteries, use the
same number and type of batteries. Proper battery disposal required. Refer to
local codes for disposal requirements. DO NOT OPEN OR MUTILATE
BATTERY. RELEASED ELECTROLYTE IS HARMFUL TO SKIN AND EYES
AND IS TOXIC.
To Replace the Battery:
1. Close active programs and turn off
computers.
Turn OFF the UPS and
unplug it from utility supply.
2. Place UPS on its side and remove retaining
screws (A) to battery door (B).
3. Open battery door (B) and remove the
battery (C) by pulling on the battery tab (D).
4. Remove terminal wires (E) from old battery.
Connect terminal wires (E) to new battery
(C); the red connects to the positive
terminal, the black connects to the
negative. DO NOT reverse terminal
connections. Slide battery (C) into unit, and
close battery door (B). Dispose of used
battery properly (it contains lead and acid).
5. Plug in UPS, turn it on, and charge
batteries for 8 to 10 hours.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
RESETTING THE CIRCUIT BREAKER
If the UPS is overloaded, the circuit breaker (9) at the lower rear of the UPS
activates to protect the UPS. If the circuit breaker activates, its center bar will
extend. To reset the circuit breaker, simply push the bar back in. If the circuit
breaker activates often, ask your dealer to check the UPS sizing or call Tech
Support at 1-800-222-5877.
ALARM CONDITIONS
The 400 VA and 600 VA models sound alarms and flash visual indications at the
front panel LED's (2, 3, 4) whenever they sense a power failure, low battery
voltage (while on battery), an overload, or a utility overvoltage condition. The
250 VA model only sounds an alarm. Sometimes, a fault in your computer
equipment may cause an overload alarm. See following page for alarm
indications.
You may silence the On-Battery alarm on 400 VA and 600 VA models by
pressing the BATTERY TEST button (5), on the rear panel. You must turn off
your computer equipment and then turn off the UPS to silence an alarm on a 250
VA model.
Refer to the first table on the next page for recommended actions when alarms
occur. Check this table first before calling for assistance. It diagnoses and
solves common problems, and helps prevent potential problems.
PROBLEM
CAUSE
SOLUTION
UPS will not start
Input voltage below
threshold
Wait until utility voltage rises to appropriate level.
Overload/Short Circuit
Check circuit breaker at rear of UPS (9). If it is activated, reset it and restart
the UPS (See "Resetting Circuit Breaker'). If problem persists, disconnect
some of the equipment from UPS - the total wattage or all your equipment
may exceed the capacity of the UPS. If it still will not start, check your
computer equipment for short circuits. For further help, call your dealer.
Input frequency mis-
match with option switch
setting
Check Option Switch #1 on rear of UPS (6). Slide switch to left for OFF, to
right for ON. OFF = 60 Hz, ON = 50 Hz. The UPS frequency must match
the frequency of your input utility supply.
Utility overvoltage
Utility voltage must be less than 135 VAC.
UPS starts on
battery, but will not
switch to utility
power.
(400 & 600 VA
only)
UPS not plugged in
Plug in power cord securely.
Circuit breaker activated
Reset circuit breaker (see “Resetting Circuit Breaker”) and restart UPS.
Call a qualified electrician.
Power not available at
utility receptacle
UPS shuts down.
Overload/Short Circuit
Check circuit breaker at rear of UPS (9). If it is activated, reset it and restart
the UPS (See "Resetting Circuit Breaker"). If problem persists, disconnect
some of the equipment from UPS - the total wattage of all your equipment
may exceed the capacity of the UPS. If it still will not start, check your
computer equipment for short circuits. For further help, call your dealer.
Low Battery
Turn OFF equipment and recharge UPS battery for at least 8 hours. If
problem persists, replace battery.
Sitenet 1 Shutdown
(400 & 600 VA only)
Consult the SiteNet 1 User Manual or contact your LAN administrator.
Download from Www.Somanuals.com. All Manuals Search And Download.
250 VA LED & ALARM INDICATIONS
Condition
Green AC
Light (4)
Audible Alarm
Status
NORMAL/START UP
Start-Up Test Fail
On after Beep
On after Beep
Single Beep, then Off
Fast Beep for 15 Sec and then Off
Operate
Operate*
Input Frequency Mismatch with
Option Switch Setting
Off
Continuous
Will Not Start
Input Voltage Below Threshold
Overload/Short Circuit
NORMAL MODE
Battery Test Fail
Overload/Short Circuit
BACKUP MODE
Off
On
On
Off
Off
Off
Continuous for 15 Sec and then Off
Off
Fast Beep for 15 Sec and then Off
Continuous for 15 Sec and then Off
Slow Beep
Will Not Start
Operate
Operate
Shutdown
Operate
Low Battery Alarm
Fast Beep
Warn of Shutdown
Low Battery Shutdown
Overload/Short Circuit
Utility Overvoltage
(transfer enabled)
Off
Off
Continuous for 15 Sec and then Off
Slow Beep
Shutdown
Operate
*The UPS starts and repeats the battery test sequence every hour until the test is passed.
400/600 VA LED & ALARM INDICATIONS
Green AC
Light (4)
Amber
Battery
Light (2)
Flash Once &
then Off
Red
Warning
Light (3)
Condition
Audible Alarm
Status
Single Beep and then
Off
NORMAL/START UP
On
Off
Off
Operate
Start-Up Test Fail
Off
On
Continuous for 15
Sec and then Off
Will Not Start
Input Frequency Mismatch
with Option Switch Setting
Off
Off
On for 15
Sec and
then Off
Off
Flash
Flash
Continuous for 15
Sec and then Off
Will Not Start
Will Not Start
Overload/Short Circuit
Input Voltage Below
Threshold
NORMAL MODE
Battery Test Fail
Overpower
Continuous for 15
Sec and then Off
Off
N/A
Fast Beep
Continuous for 15
Sec & then Off
On
On
On
Off
Off
Off
Off
Off
On
Operate
Operate
Alarm Only
Shutdown
Flash
Flash for 15
Sec & then
Off
Overload/Short Circuit
On for 15
Sec & then
Off
Charger Fail
On
Off
Off
Off
Off
On
On
On*
On
Off
On
On*
Slow Beep
Slow Beep
Fast Beep
Continuous for 15
Sec & then Off
Slow Beep
Slow Beep
Continuous for 15
Sec & then Off
Alarm Only
Operate
Operate
BACKUP MODE
Low Battery Alarm
Low Battery Shutdown
Shutdown
Utility Undervoltage
Utility Overvoltage
Overload/Short Circuit
SiteNet 1 Shutdown
Off
Off
Off
On
On
On*
Off
Flash
Flash*
Operate
Operate
Shutdown
*If there is insufficient utility voltage, this indicator illuminates for 15 seconds then turns off to preserve the battery.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
SPECIFICATIONS
PS250-60/PS250-60S
250 VA / 150 W
FCC ID #
N/A
BHKAF400T-60
PS400-60 / PS400-60S
400 VA / 240 W
BKAF600T-60
PS600-60 / PS600-60S
600 VA / 360 W
Model # / Stock #
Model Rating
Dimensions
Unit (W x D x H)
3.51 x 10.18 x 6.79 in
(90 x 262 x 175 mm)
4.25 x 10.18 x 7.02 in
(109 x 262 x 186 mm)
4.84 x 10.18 x 8.15 in
(124 x 262 x 216 mm)
Shipping (W x D x H)
7.13 x 14.37 x 11.93 in
(181 x 365 x 303 mm)
8.35 x 18.98 x 11.5 in
(212 x 482 x 292 mm)
9.33 x 18.98 x 13.15 in
(237 x 482 x 334 mm)
Weight
Unit
Shipping
8.8 lb. (4 kg)
10.1 lb. (4.6 kg)
12.5 lb. (5.7 kg)
15.4 lb. (7 kg)
19.8 lb. (9 kg)
23.1 lb.(10.5 kg)
AC Parameters
Receptacles
(2) NEMA 5-15
(4) NEMA 5-15
(4) NEMA 5-15
Input Voltage Range
Low Voltage Transfer Point
High Voltage Transfer Point
Input Frequency Range
Output Voltage (on battery)
Output waveform (on battery)
Max. Output Current at 120 V
Output Frequency
Max. Overload Capacity
Battery
90-135 VAC, Single Phase, 2 Wire Plus Ground
95 VAC, User Selectable to 90 or 100 VAC
135 VAC, User Selectable to 140 VAC
47 – 53 Hz, 57 – 63 Hz
135 VAC
2.1 A
115 VAC, ± 5%
Stepped Sine Wave
3.3A
5 A
50 or 60 Hz, ±5%
115% of Power Rating
Type
Sealed, Valve-Regulated Lead Acid, Maintenance-Free
Qty x Voltage x Rating
Back-up Time
1 x 12 V x 4.5 AH
1 x 12 V x 7 AH
6 minutes at full load
2 x 12 V x 7 AH
Time from Low Battery Alarm
to Shutdown
Approximately 2 Minutes, depending on load
Recharge Time
Battery Life
8 – 10 Hours to 90% Capacity
3 – 5 Years Typical
Transfer Time to/from Inverter
Agency Approvals
Safety
2 – 6 msec. Typical
UL, C-UL Listed
EMI / RFI
Surge Protection
MTBF (Bellcore Method)
Environmental Standards
Operating Temperatures
Storage Temperatures
Meets FCC Part 15, Subpart B, Class B
Meets IEEE 587, Category A and B
100,000 Hours (Excluding Battery)
50° F to +104° F (10° C to +40° C)
0° F to +104° F (-20° C to +40° C)
(High Temperatures Reduce Battery Life)
Cooling
Convection
Audible Noise
Operating Elevation
Storage Elevation
Less than 40 dB @ 1 meter
Up to 9,900 ft. (3,000 m)
Up to 33,000 ft. (10,000 m)
11
Download from Www.Somanuals.com. All Manuals Search And Download.
LIMITED WARRANTY
Liebert Corporation extends the following LIMITED WARRANTY to the
purchaser and to its customer (collectively referred to as the "Purchaser"): the
enclosed Uninterruptible Power System (UPS) and components are free from
defects in materials and workmanship under normal use, service, and
maintenance FOR A PERIOD OF TWO YEARS FROM THE DATE OF
ORIGINAL PURCHASE from Liebert or the Liebert dealer or retailer. THE
FOREGOING WARRANTY IS THE ONLY WARRANTY GIVEN AND NO
OTHER WARANTY IS PROVIDED, EXPRESS OR IMPLIED, INCLUDING
WITHOUT LIMITATION, MERCHANTABILITY OR FITNESS FOR
A
PARTICULAR PURPOSE. Certain aspects of disclaimers are not applicable to
consumer products acquired by individuals and used for personal, family, or
household purposes (as distinguished from industrial or other purposes). Local
laws may not allow limitations on how long an implied warranty lasts, so the
above limitation may not apply to you. This warranty gives you specific legal
rights, and you may have other rights which vary according to local law.
Certain repairs or services are the responsibility of the Purchaser and the
Purchaser is expected to pay for them. This warranty does not extend either to
products with removed or altered serial numbers or to any losses or damages
due to act of God or source external to the product, misuse, accident, abuse,
neglect, negligence, unauthorized modification, alteration, or repair, use beyond
rated capacity, or improper installation, maintenance, application or use,
including, without limitation, use in a manner contrary to the accompanying
instructions or applicable codes. WARNING: Warranty is void if the battery is
allowed to discharge below the minimum battery cutoff point. To prevent such
discharge DO NOT leave the unit power switch "ON" for more than two (2) days
without AC power being supplied to the UPS. The battery must be recharged
every four (4) to six (6) months when not in use.
If the UPS fails to conform with the above warranty within the two year warranty
period, Liebert will repair or replace the UPS, at Liebert's option. Repairs or
replacements are warranted for the remainder of the original warranty period.
Purchaser, to make a warranty claim, should call 1-800-222-5877 to obtain a
Returned Goods Authorization number and shipping instructions. Return
transportation costs to Liebert are the responsibility of the Purchaser.
"LIFE SUPPORT" POLICY
This product is not recommended, and the Company will not knowingly sell this
product, for use with life support and other designated "critical" devices. ANY
SUCH USE BY A USER AUTOMATICALLY VOIDS AND DISCLAIMS ANY
AND ALL WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF
MERCHANTABILITY, IMPLIED WARRANTY OF FITNESS FOR
A
PARTICULAR PURPOSE, AND EXPRESS WARRANTIES THAT THIS
PRODUCT WILL CONFORM TO ANY AFFIRMATION OR PROMISE, FOR
THIS PRODUCT AND THE USER AGREES THAT IN NO EVENT SHALL THE
COMPANY BE LIABLE FOR CONSEQUENTIAL OR INDIRECT DAMAGES.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
1050 Dearborn Drive Columbus, OH 43229 614-888-0246
Technical Support
U.S.A................................................................ 1-800-222-5877
Outside the U.S.A ........................................... 614-841-6755
U.K................................................................ +44 (0) 1793 553355
France ...........................................................+33 1 4 87 51 52
Germany ...................................................... +49 89 99 19 220
Italy .............................................................. +39 2 98250 1
Netherlands.................................................. +00 31 475 503333
Internet.......................................................... [email protected]
Worldwide FAX tech support......................…614-841-5471
While every precaution has been taken to ensure
accuracy and completeness in this manual, Liebert
Corporation assumes no responsibility, and
disclaims all liability for damages resulting from
use of this information or for any errors or
omissions.
©1996 Liebert Corporation All rights reserved
throughout the world. Specifications subject to
change without notice.
® Liebert and the Liebert logo are registered
trademarks of Liebert Corporation. All names
referred to are trademarks or registered
trademarks of their respective owners.
Printed in U.S.A.
SL-23235 (11/97) Rev. 3.0
13
Download from Www.Somanuals.com. All Manuals Search And Download.
|