Liebert Power Supply PS250 50S PS400 50S PS600 50S User Manual |
PowerSure™
PS250-50S PS400-50S
PS600-50S
250 VA
400 VA
600 VA
POWER PROTECTION
Uninterruptible
Power System
250 VA – 600 VA
230 VAC
USER’S MANUAL
Download from Www.Somanuals.com. All Manuals Search And Download.
1. ON/OFF Button
2. Battery Light (400/600 Only)
3. Check Light (400/600 Only)
4. AC Light
5. Battery Test Button (400/600 Only)
6. Option Switches
7. Output Receptacles
8. Power Cord Input
9. Circuit Breaker
10. Communications Port
ATTENTION: Please refer to these drawings when reading this manual. This
manual references the various parts of your UPS by number.
INSTALLATION INSTRUCTIONS
1. Unpack unit and check contents. There should be one UPS, two CEE-22
output cables, and one User's Manual. Check items for damage. If any
appear faulty or damaged, contact your dealer immediately. Store packaging
in a safe place for possible future shipment of UPS.
2. Place UPS on a sturdy, dry surface in a well-ventilated area away from direct
heat sources. Leave at least 100 mm clearance all around UPS for adequate
ventilation.
3. Shut down load equipment, turn OFF
mains supply, and unplug load
equipment's power input cable (A)
from AC supply socket.
4. Unplug power input cable (A) from
load equipment input socket (D) and
plug it into UPS input socket (C). Re-
plug the power input cable (A) into AC
supply socket. Turn ON both the
mains supply and the UPS. Turning
ON the UPS charges the batteries.
Charge batteries for at least 8 hours
before connecting load equipment.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
5. After charging, shutdown both the UPS and load equipment and unplug
them from the AC supply socket. Connect the supplied CEE-22 output cable
(B) between the load equipment input socket (D) and one of the UPS AC
output sockets (E). Connect all load equipment to UPS in this way.
6. When all equipment is plugged in, plug UPS into the AC supply socket and
turn it ON. The UPS is ready for normal operation.
OPERATING INSTRUCTIONS
1. Check that all power connections to and from the unit are secure and fitted
with
the correct cables and switch the AC input supply ON.
2. Press the ON/OFF Button (1) to ON.
3. Switch your equipment ON at their respective power switch(es).
4. Check the condition of the UPS front panel LED's. The 250 VA AC LED (4)
should be lit. For the 400/600 VA models, the AC LED (4) should be lit, and
the Check and Battery LED's (3 & 2) should be unlit.
5. Check the operation of your equipment. It should display normal operational
conditions.
6. If any function provides an abnormal condition, refer to the troubleshooting
guide later in this manual. If a problem persists, consult your dealer or call
Tech Support at the number listed at the end of this manual.
STARTING FROM BATTERY (400/600 VA only): Turn OFF UPS. Press and
hold BATTERY TEST button (5) for 4 seconds. Switch ON UPS and release
BATTERY TEST button (5). UPS will run in backup mode with the Battery LED
(2) lit. To stop, switch OFF at front panel.
Battery Back-up Time
Back-up Time (minutes)
250 VA Models
Download from Www.Somanuals.com. All Manuals Search And Download.
COMPUTER/LAN INTERFACE (400/600 VA ONLY)
Optional SiteNet 1 kits provide connection to a wide range of popular computer
operating systems; such as Novell, UNIX, UNISYS, SUN, WINDOWS and many
others. SiteNet 1 software automatically performs an orderly shutdown of
computer operating systems, in the event of a power outage and/or low battery
conditions.
The SiteNet 1 kit supplies a cable to connect supported computer systems to the
UPS communications port (10). The table below shows connector details.
Note: Your dealer supplies
INTERFACE FUNCTION
UPS Shutdown/Active High*
On Battery/Return
On Battery/Normally Open
Low Battery/Normally Open
Low Battery/Return
DB25 ADAPTER
computer communications kits
separately, if you wish. They come
with installation instructions, cable
connections, and appropriate
computer software.
19
17
16
11
9
UPS Shutdown/Return
7
*Remote Shutdown (5-12V DC, 5-10 mA. max.); battery operation
1
COLLECTOR TO EMITTER
Open Collector
(+)
330 Ohms
(-)
Return
1
Maximum voltage and current on pins 11 & 16 are +40V DC; 1.0mA
OPTION SWITCH SETTINGS
On the back of your UPS is a bank of option switches (6) with a removable
plastic cover. These switches determine transfer levels and operating frequency.
Slide the switches to the left to turn them OFF, to the right to turn ON. Turn OFF
equipment and UPS and unplug the UPS prior to changing switch settings, or the
UPS will ignore the new settings. Replace the plastic option switch cover.
Option Switch 1: 50/60 Hz Select – When OFF, this switch sets UPS for 60 Hz
mains. Output in backup mode will be 60 Hz. When ON, the switch sets UPS for
50 Hz mains and output in backup mode is 50 Hz. The switch must match the
mains frequency or the UPS will not start. The factory setting is 50 Hz.
Option Switch 2: High Line Transfer –
250VA model: When ON, this switch transfers the UPS to battery operation
when the mains voltage reaches 270 VAC. When OFF, the UPS will not
transfer to battery. Factory setting is ON.
400/600VA models: You may select at which voltage the UPS will transfer to
battery operation when it encounters a high mains voltage. The ON position
transfers the UPS to battery operation at 270VAC; the OFF position transfers at
280VAC. Factory setting is 270 VAC.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Option Switch 3 & 4: Low Voltage Limit Select – Low voltage limit is the
voltage level at which battery operation starts. You may set the low voltage limit
of the UPS to 180V, 190V, or 200V. The factory setting is 190V. This option
reduces excessive battery usage in brownout conditions. Make sure your
computer equipment can operate at 180 VAC before selecting the lowest limit
(most will). Refer to the tables below to change switch settings:
250 VA MODEL
400/600 VA MODELS
VOLTAGE
SWITCH #3
OFF
SWITCH #4
N/A
VOLTAGE
SWITCH #3
ON
SWITCH #4
200V
190V
180V
200V
190V
180V
N/A
OFF
ON
ON
ON
OFF
ON
OFF
OFF
BATTERY TEST BUTTON
The Battery Test Button (5) on the 400 and 600 VA models tests the condition of
the battery. If the charge is sufficient, the UPS lights the Battery Light (2), runs
on battery power for 15 seconds, then returns to mains power. If the battery fails
the test, the Check Light (3) illuminates and the UPS immediately returns to
mains power. The Check Light remains lit while on mains power. A battery in
unacceptable condition requires recharge or replacement of the battery.
Pressing the Battery Test Button (5) also silences alarms.
BATTERY CARE AND USE
STORAGE: If the unit is not in continued use, plug in the UPS every 4 to 6
months for 12 hours to recharge the battery. Warranty is void if the battery
discharges below the minimum battery cutoff point. To prevent such discharge,
DO NOT leave UPS ON for more than two days without plugging it in.
BATTERY LIFE & REPLACEMENT: Excessive battery use, storage at high
ambient temperatures, and lengthy periods in a discharged state greatly reduce
battery life. Your UPS maximizes battery life by limiting the depth of battery
discharge. You may replace the UPS battery yourself, but if you feel unqualified,
refer battery replacement to qualified personnel. Contact your local dealer or call
Liebert for a replacement battery.
WARNING: To replace batteries, turn OFF UPS and unplug it from mains supply.
CAUTION: Observe proper precautions. When replacing batteries, use the same
number and type of batteries. Proper battery disposal required. Refer to local
codes for disposal requirements. Do not open or mutilate battery. Released
electrolyte is harmful to skin and eyes and is toxic.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
To Replace the Battery:
1. Close active programs and turn off
computers. Turn OFF the UPS and unplug it
from mains supply.
2. Place UPS on its side and remove retaining
screws (A) to battery door (B).
3. Open battery door (B) and remove the battery
(C) by pulling on the battery tab (D).
4. Remove terminal wires (E) from old battery.
Connect terminal wires (E) to new battery (C);
the red connects to the positive terminal, the
black connects to the negative. DO NOT
reverse terminal connections. Slide battery
(C) into unit, and close battery door (B).
Dispose of used battery properly (it contains
lead and acid).
5. Plug in UPS, turn it on, and charge batteries
for 8 to 10 hours.
RESETTING THE CIRCUIT BREAKER
If the UPS is overloaded, the circuit breaker (9) at the lower rear of the UPS
activates to protect the UPS. If the circuit breaker activates, its center bar will
extend. To reset the circuit breaker, simply push the bar back in. If the circuit
breaker activates often, ask your dealer to check the UPS sizing or call Tech
Support at the number listed at the end of this manual.
ALARM CONDITIONS
The 400 VA and 600 VA models sound alarms and flash visual indications at the
front panel LED's (2, 3, 4) whenever they sense a power failure, low battery
voltage (while on battery), an overload, or a mains overvoltage condition. The
250 VA model only sounds an alarm. Sometimes, a fault in your computer
equipment may cause an overload alarm. See following page for alarm
indications.
You may silence the On-Battery alarm on 400 VA and 600 VA models by
pressing the BATTERY TEST button (5), on the rear panel. You must turn off
your computer equipment and then turn off the UPS to silence an alarm on a 250
VA model.
Refer to the first table on the next page for recommended actions when alarms
occur. Check this table first before calling for assistance. It diagnoses and
solves common problems, and helps prevent potential problems.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
PROBLEM
CAUSE
SOLUTION
UPS will not start
Input voltage below
threshold
Wait until mains voltage rises to appropriate level.
Overload/Short Circuit
Check circuit breaker at rear of UPS (9). If it is activated, reset it and restart
the UPS (See "Resetting Circuit Breaker'). If problem persists, disconnect
some of the equipment from UPS - the total wattage or all your equipment
may exceed the capacity of the UPS. If it still will not start, check your
computer equipment for short circuits. For further help, call your dealer.
Input frequency mis-
match with option switch
setting
Check Option Switch #1 on rear of UPS (6). Slide switch to left for OFF, to
right for ON. OFF = 60 Hz, ON = 50 Hz. The UPS frequency must match
the frequency of your input mains supply.
Mains overvoltage
Mains voltage must be less than 270 VAC.
UPS starts on
battery, but will not
switch to mains
power.
(400 & 600 VA
only)
UPS not plugged in
Circuit breaker activated
Plug in power cord securely.
Reset circuit breaker (see “Resetting Circuit Breaker”) and restart UPS.
Call a qualified electrician.
Power not available at
utility receptacle
UPS shuts down.
Overload/Short Circuit
Check circuit breaker at rear of UPS (9). If it is activated, reset it and restart
the UPS (See "Resetting Circuit Breaker"). If problem persists, disconnect
some of the equipment from UPS - the total wattage of all your equipment
may exceed the capacity of the UPS. If it still will not start, check your
computer equipment for short circuits. For further help, call your dealer.
Low Battery
Turn OFF equipment and recharge UPS battery for at least 8 hours. If
problem persists, replace battery.
Sitenet 1 Shutdown
(400 & 600 VA only)
Consult the SiteNet 1 User Manual or contact your LAN administrator.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
250 VA LED & ALARM INDICATIONS
Condition
Green AC
Light (4)
Audible Alarm
Status
NORMAL/START UP
Start-Up Test Fail
On after Beep
On after Beep
Single Beep, then Off
Fast Beep for 15 Sec and then Off
Operate
Operate
Input Frequency Mismatch with
Option Switch Setting
Off
Continuous
Will Not Start
Input Voltage Below Threshold
Overload/Short Circuit
NORMAL MODE
Battery Test Fail
Overload/Short Circuit
BACKUP MODE
Low Battery Alarm
Low Battery Shutdown
Main Overvoltage
(transfer enabled)
Continuous for 15 Sec and then Off
Off
On
On
Off
Off
Off
Off
Off
Will Not Start
Operate
Operate
Shutdown
Operate
Warn of Shutdown
Shutdown
Operate
Off
Fast Beep for 15 Sec and then Off
Continuous for 15 Sec and then Off
Slow Beep
Fast Beep
Continuous for 15 Sec and then Off
Slow Beep
The UPS starts and repeats the battery test sequence every hour until the test is passed.
400/600 VA LED & ALARM INDICATIONS
Green AC
Light (4)
Amber
Battery
Red Warning
Light (3)
Condition
Audible Alarm
Status
Light (2)
Flash Once &
then Off
Single Beep and then
Off
Continuous for 15 Sec
and then Off
NORMAL/START UP
Start-Up Test Fail
On
Off
Off
On
Operate
Off
Will Not Start
Input Frequency Mismatch
with Option Switch Setting
On for 15 Sec
and then Off
Continuous for 15 Sec
and then Off
Off
Off
Flash
Flash
Will Not Start
Will Not Start
Overload/Short Circuit
Input Voltage Below
Threshold
Continuous for 15 Sec
and then Off
Off
NORMAL MODE
Battery Test Fail
Overpower
On
On
On
Off
Off
Off
Off
Off
On
Flash
Flash for 15
Sec & then Off
Off
N/A
Operate
Operate
Alarm Only
Shutdown
Fast Beep
Continuous for 15 Sec
& then Off
On for 15 Sec
& then Off
Overload/Short Circuit
Charger Fail
On
Off
Off
Off
Off
On
On
On
Off
On
Slow Beep
Slow Beep
Fast Beep
Continuous for 15 Sec
& then Off
Alarm Only
Operate
Operate
BACKUP MODE
Low Battery Alarm
Low Battery Shutdown
On*
On*
Shutdown
Slow Beep
Mains Undervoltage
Mains Overvoltage
Overload/Short Circuit
SiteNet 1 Shutdown
Off
Off
Off
On
On
On*
Off
Flash
Flash*
Operate
Operate
Shutdown
Slow Beep
Continuous for 15 Sec
& then Off
*If there is insufficient utility voltage, this indicator illuminates for 15 seconds then turns off to preserve the battery.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
SPECIFICATIONS
Model # / Stock #
Model Rating
PS250-50/PS250-50S
250 VA / 150 W
PS400-50 / PS400-50S
PS600-50 / PS600-50S
600 VA / 360 W
400 VA / 240 W
Dimensions: mm
Unit (W x D x H)
Shipping (W x D x H)
Weight: Kg
90 x 262 x 175
181 x 365 x 303
109 x 262 x 186
212 x 482 x 292
124 x 262 x 216
237 x 482 x 334
Unit
Shipping
4
4.6
5.7
7
9
10.5
AC Parameters
Receptacles
(2) CEE-22
(4) CEE-22
(4) CEE-22
Input Voltage Range
Low Voltage Transfer Point
High Voltage Transfer Point
Input Frequency Range
Spike Protection
Output Voltage (on battery)
Output waveform (on battery)
Max. Output Current at 230 V
Output Frequency
Max. Overload Capacity
Battery
180-300 VAC, Single Phase, 2 Wire Plus Earth
190 VAC, User Selectable to 180 or 200 VAC
270 VAC, User Selectable to 280 VAC
47 – 53 Hz, 57 – 63 Hz
270 VAC
1.1 A
80 Joules
230 VAC, ± 5%
Stepped Sine Wave
1.7A
2.6A
50 or 60 Hz, ± 5%
115% of Power Rating
Type
Valve-Regulated Lead Acid
1 x 12 V x 7 AH
6 minutes at full load
Qty x Voltage x Rating
Back-up Time
1 x 12 V x 4.5 AH
2 x 12 V x 7 AH
Time from Low Battery Alarm
to Shutdown
Approximately 2 Minutes, depending on load
Recharge Time
Battery Life
8 – 10 Hours to 90% Capacity
3 – 5 Years Typical
Transfer Time to/from Inverter
Agency Approvals
Safety
2 – 6 msec. Typical
EN 50091-1
RFI
Meets EN 55022 Class B, IEC 801-2, 3, 4
Meets IEC 801-5 (Draft)
100,000 Hours (Excluding Battery)
Surge Protection
MTBF (Bellcore Method)
Environmental Standards
Operating Temperatures
Storage Temperatures
Cooling
+10° C to +40° C
-20° C to +40° C (High Temperatures Reduce Battery Life)
Convection
Audible Noise
Operating Elevation
Storage Elevation
Less than 40 dB @ 1 meter
Up to 3,000 m
Up to 10,000 m
10
Download from Www.Somanuals.com. All Manuals Search And Download.
LIMITED WARRANTY
Liebert Corporation extends the following LIMITED WARRANTY to the
purchaser and to its customer (collectively referred to as the "Purchaser"):
the enclosed Uninterruptible Power System (UPS) and components are free
from defects in materials and workmanship under normal use, service, and
maintenance FOR A PERIOD OF TWO YEARS FROM THE DATE OF
ORIGINAL PURCHASE from Liebert or the Liebert dealer or retailer. THE
FOREGOING WARRANTY IS THE ONLY WARRANTY GIVEN AND NO
OTHER WARANTY IS PROVIDED, EXPRESS OR IMPLIED, INCLUDING
WITHOUT LIMITATION, MERCHANTABILITY OR FITNESS FOR
A
PARTICULAR PURPOSE. Certain aspects of disclaimers are not applicable
to consumer products acquired by individuals and used for personal, family,
or household purposes (as distinguished from industrial or other purposes).
Local laws may not allow limitations on how long an implied warranty lasts,
so the above limitation may not apply to you. This warranty gives you
specific legal rights, and you may have other rights which vary according to
local law.
Certain repairs or services are the responsibility of the Purchaser and the
Purchaser is expected to pay for them. This warranty does not extend either
to products with removed or altered serial numbers or to any losses or
damages due to act of God or source external to the product, misuse,
accident, abuse, neglect, negligence, unauthorized modification, alteration,
or repair, use beyond rated capacity, or improper installation, maintenance,
application or use, including, without limitation, use in a manner contrary to
the accompanying instructions or applicable codes. WARNING: Warranty is
void if the battery is allowed to discharge below the minimum battery cutoff
point. To prevent such discharge DO NOT leave the unit power switch "ON"
for more than two (2) days without AC power being supplied to the UPS. The
battery must be recharged every four (4) to six (6) months when not in use.
If the UPS fails to conform with the above warranty within the two year
warranty period, Liebert will repair or replace the UPS, at Liebert's option.
Repairs or replacements are warranted for the remainder of the original
warranty period. Purchaser, to make a warranty claim, should call +44
(0)1793 553355 to obtain a Returned Goods Authorization number and
shipping instructions. Return transportation costs to Liebert are the
responsibility of the Purchaser.
"LIFE SUPPORT" POLICY
This product is not recommended, and the Company will not knowingly sell
this product, for use with life support and other designated "critical" devices.
ANY SUCH USE BY A USER AUTOMATICALLY VOIDS AND DISCLAIMS
ANY AND ALL WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF
MERCHANTABILITY, IMPLIED WARRANTY OF FITNESS FOR
A
PARTICULAR PURPOSE, AND EXPRESS WARRANTIES THAT THIS
PRODUCT WILL CONFORM TO ANY AFFIRMATION OR PROMISE, FOR
THIS PRODUCT AND THE USER AGREES THAT IN NO EVENT SHALL
THE COMPANY BE LIABLE FOR CONSEQUENTIAL OR INDIRECT
DAMAGES.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
R
1050 Dearborn Drive Columbus, OH 43229 614-888-0246
Technical Support
U.S.A................................................................ 1-800-222-5877
Outside the U.S.A ........................................... 614-841-6755
U.K................................................................ +44 (0) 1793 553355
France ...........................................................+33 1 4 87 51 52
Germany ...................................................... +49 89 99 19 220
Italy .............................................................. +39 2 98250 1
Netherlands.................................................. +00 31 475 503333
Internet.......................................................... [email protected]
Worldwide FAX tech support......................…614-841-5471
While every precaution has been taken to ensure
accuracy and completeness in this manual, Liebert
Corporation assumes no responsibility, and
disclaims all liability for damages resulting from
use of this information or for any errors or
omissions.
©1997 Liebert Corporation All rights reserved
throughout the world. Specifications subject to
change without notice.
® Liebert and the Liebert logo are registered
trademarks of Liebert Corporation. All names
referred to are trademarks or registered
trademarks of their respective owners.
Printed in U.S.A.
SL-23237 (9/97) Rev. 2.0
12
Download from Www.Somanuals.com. All Manuals Search And Download.
|