POWER AVAILABILITY
USER MANUAL
Nfinity™ Power System
208/240V
60Hz
4 to 16kVA
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
GLOSSARY OF SYMBOLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1.1 System Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Modes of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Major Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3.1 Unit Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3.2 User Interface Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3.3 System Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3.4 Power Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3.5 Battery Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1.1 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1.2 Required Setup Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1.3 Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Unloading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2.1 Unloading the UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2.2 Stationary Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Cable Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3.1 Wiring Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3.2 Connecting to External Panel Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Input Cabling and Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Output Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.3.3 REPO Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.4.1 COM Ports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.4.2 Intellislot™ Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Controls and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.1.1 Display Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Status LED Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Navigating the Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Operating Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.4.1 Start-Up and Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.4.2 Shutting Down the UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.4.3 Manual Transfer to Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
i
Download from Www.Somanuals.com. All Manuals Search And Download.
Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.5.1 UPS Status Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.5.2 UPS Configuration Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.5.3 Display Date/Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.5.4 Event Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.5.5 Active Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.5.6 Transfer to Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.5.7 Module Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.5.8 Service Tools for Liebert Global Services Engineers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Active Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Module LED Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Module Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
4.3.1 Removing Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
4.3.2 Adding or Replacing Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.3.3 Replacing the User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.1.1 Proper Care. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.1.2 Scheduled Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.1.3 Replacing Fan Filters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Product Warranty Registration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
FIGURES
Figure 1
Front and back views (12 bay model shown). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
REPO switch connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
TABLES
Table 1
Nfinity weight and dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Guide to LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
ii
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be closely followed during installation and
maintenance of this UPS unit and during the installation and replacement of Power and Battery
Modules.
This product is designed for Commercial/Industrial use only. This product is not intended for use
with life support and other U.S. FDA-designated “critical” devices. Maximum load must not exceed
that shown on the UPS rating label.
WARNING
!
Lethal voltages may be present within this unit even when it is apparently not operating.
Observe all cautions and warnings in this manual. Failure to do so MAY result in serious
injury or death. Never work alone.
Observe the following precautions when working with batteries:
CAUTION
!
DO NOT dispose of Battery Modules in a fire because the modules may explode.
DO NOT open or mutilate batteries; released electrolyte is harmful to skin and eyes and may
be toxic.
A battery can present a risk of electrical shock and high short-circuit current. The following
precautions should be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
Lead-acid batteries contain hazardous toxic materials. Handle, transport and recycle in
accordance with local regulations.
This UPS is designed for use on a properly grounded (earthed), 208/240 VAC, 60 Hz supply and is to
be installed by qualified personnel.
Electromagnetic Compatibility—The Nfinity™ UPS complies with the limits for a Class A digital
device, pursuant to Part 15 of FCC rules. These limits provide reasonable protection against harmful
interference in a commercial environment. This device generates, uses and radiates radio frequency
energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operating this device in a residential area is likely to cause
harmful interference which users must correct at their own expense.
Operate the UPS in an indoor environment only in an ambient temperature range of 32°F to +104°F
(0°C to +40°C). Install it in a clean environment, free from conductive contaminates, moisture, flam-
mable liquids, gases and corrosive substances.
Turn the UPS off and isolate the UPS before cleaning. Use only a soft cloth, never liquid or aerosol
cleaners. Keep the front and rear vents free of dust accumulation that could restrict airflow.
Never block or insert any object into the ventilation holes or other openings.
This UPS contains user replaceable modules. No attempts should be made to access the interior of
1
Download from Www.Somanuals.com. All Manuals Search And Download.
GLOSSARY OF SYMBOLS
Risk of electrical shock
Indicates caution followed by important instructions
AC input
AC output
Requests the user to consult the manual
i
Indicates the unit contains a valve-regulated lead acid
battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
OFF
ON
Standby
No telecommunication connection
Locked position
Unlocked position
Contact closure signals
Serial communications
2
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
1.0 INTRODUCTION
1.1 General Description
Congratulations on your purchase of Liebert’s Nfinity™ Uninterruptible Power System. As with
every other Liebert product, we stand behind our quality. If you have any questions concerning this
UPS, please feel free to contact your local dealer or Liebert representative or call the appropriate
Technical Support number listed on the back of this manual.
To ensure proper installation and operation of this unit, please read this manual thoroughly.
1.1.1 System Description
The Liebert Nfinity Power System is a modular UPS available in 8 & 12 bay frames. It is intended for
use with workstations, servers, network, telecom and other sensitive electronic equipment. It pro-
vides continuous, high-quality AC power to your equipment, protecting it from any power disturbance
due to blackouts, brownouts, surges or noise interference.
The Nfinity modular UPS was designed to provide maximum system availability to business-critical
equipment. Nfinity is also an easily adaptable UPS system. By simply installing additional Power or
Battery Modules, you can expand your current system capacity or extend your backup runtime.
Nfinity has a comprehensive user interface that enables configuration according to the user’s prefer-
ence. It also informs the user of details on the status of the UPS and keeps a log of events.
Features
• Up to 16 kVA of modular backup power
• Continuous power conditioning
• A user-friendly interface for custom configuration
• Continuous system monitoring
• Warning alarms and event logs
• Internal automatic & manual bypass
Standard Components
• Power Modules - for power conditioning
• Battery Modules - for backup power
• System Control Modules - for system monitoring and communications
• LCD Display - for comprehensive user indications and programmable controls
• Output Transformer - for isolation
• REPO Switch Connection
Communications
• Dry contacts
• RS-232
• Optional communications via Intellislot™ communication ports
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
Figure 1 Front and back views (12 bay model shown)
Control
Switch (SW2) Connection
REPO
Intellislot™
Communications Ports
User Interface
!
ESC
DB-9
Communication
Ports
Power
Module
Bays
Battery
Module
Bays
Output Power
Terminal
208/240 Jumper
Input Power
Terminal
Input Earth
Terminal
Manual
Bypass
Switch
(SW1)
Input Circuit
Breaker (CB1)
Intake
Cooling Fans
External Battery
Connection
FRONT VIEW
with bezels
removed
BACK VIEW
with access
plates removed
Refer to the table below for size and fully populated weight considerations.
Table 1 Nfinity weight and dimensions
Max Weight - lb (kg)
Model
8 bay
W x D x H - in. (mm)
855 (388)
20 x 28 x 40 (508 x 711 x 1016)
20 x 28 x 53 (508 x 711 x 1346)
12 bay
1176 (534)
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
1.2
Modes of Operation
INPUT
OUTPUT
MANUAL
BYPASS
OUTPUT &
EMI
FILTER
POWER
MODULE(S)
OUTPUT
TRANSFORMER
BYPASS
CONTACTOR
BATTERY
MODULE(S)
SYSTEM
USER
INTERFACE
CONTROL
INTERFACE
CONTROL
MODULE(S)
POWER
CONTROL
COMMUNICATIONS
Normal Mode
The Power Module rectifiers derive power from a utility AC source and supply regulated DC power to
the inverter. The module’s inverter regenerates precise AC power to supply the connected equipment.
The battery charger is in the Power Module and maintains a float-charge on the batteries.
Backup Mode
When AC utility fails, the connected equipment is supplied power by the inverter, which obtains
energy from the Battery Modules. The output power equipment will not be interrupted during the
failure or restoration of the AC utility source.
Auto Restart Mode
After a power outage and complete battery discharge, and once AC utility is restored, the UPS will
automatically restart and resume supplying power to connected equipment. This feature is enabled at
the factory, but can be disabled by the user. The user can also program two auto restart delay settings:
1. Battery capacity level (%)
2. Countdown timer
Bypass Mode
The bypass provides an alternate path for power to the connected equipment and operates in the fol-
lowing manner:
• Automatic
In the event of an internal fault or should the inverter overload capacity be exceeded, the UPS
performs an automatic transfer of the connected equipment from the inverter to the bypass
source.
• Manual
Should the UPS need to be taken out of service for limited maintenance or repair, manual activa-
tion of the bypass will cause an immediate transfer of the equipment from the inverter to the
bypass source.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
1.3
Major Components
Nfinity’s frame
with bezels removed
The following is a general description of each compo-
nent and its functions. Please review this section
carefully, as it will give you a better understanding as
to how the Nfinity operates.
1.3.1 Unit Frame
The front of the Nfinity consists of a series of plastic
bezels. By grasping these bezels from the left and
right sides and pulling straight out, you can remove
the bezel to reveal the Battery / Power Module bays.
The bottom bezel covers the internal cooling fans and
the manual bypass switch.
The User Interface Module is located above the
Power / Battery Module bays for easy access. By mov-
ing the User Interface and setting it on top of the
frame, you will see the system control module bays.
NOTE
In the figure at right, the Power Module and
Battery Module are extended for illustration
purposes only. Extending more than one
module at a time could cause the unit to be
top-heavy and/or tip.
1.3.2 User Interface Module
User Interface Module
The User Interface Module is the primary source of
communication between the UPS and the user. From
the interface, the user can:
• View the status of the UPS
• Custom configure the system
• Review the event log to assist with
troubleshooting
• Enable/disable the output power
• Silence the audible alarm
• Manually transfer the unit to bypass
For a more detailed explanation on how to operate the
User Interface Module, see 3.1 - Controls and Indi-
1.3.3 System Control Module
System Control Module
The System Control Module is the communications
backbone of the UPS. It gathers input from all mod-
ules and processes the data to control the operation of
the system — including monitoring the condition of
each module. An optional redundant System Control
Module can be installed to provide full system func-
tionality (operation and communication).
Fasteners
Under normal operation, the Status LED (green) will
blink and the Fault LED (yellow) will be off. For any
condition other than this, check 4.0 - Troubleshoot-
ing.
Fault LED
Status LED
Lever
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
1.3.4 Power Module
Each power module is an independent 4 kVA, 2.8kW unit, consisting of a power factor corrected recti-
fier, battery charger and inverter, with associated monitoring and control circuitry. The modules are
paralleled to provide greater capacity and/or redundancy. Modules may be added or replaced on-line
with no interruption or danger to the connected equipment.
1.3.5 Battery Module
Each battery module contains 10 individual 12-volt, 9 amp hour, valve-regulated (VRLA) battery
blocks with associated monitoring and controls to isolate the Battery Module in the event of a battery
failure. The modules are paralleled to provide greater capacity, backup time and/or redundancy. Mod-
ules may be added or replaced on-line with no interruption or danger to the connected equipment,
provided that the UPS is not operating on battery.
Power Module
Battery Module
Shipping screws
Fastener
Green Status LED
Yellow Fault LED
Cooling Fan
Lever
FRONT
FRONT
Under normal operation, the Green Status LED will blink continuously and the Yellow Fault LED
NOTE
Nfinity is shipped with each battery module secured to the frame by two shipping screws. These
screws should be removed prior to start-up.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
2.0 INSTALLATION
2.1 Inspection
Upon receiving the UPS, examine the packaging for any signs of mishandling or damage. If any dam-
age is noted, call your local dealer or Liebert representative and/or notify your carrier.
2.1.1 Environment
NOTE
Operating in temperatures above 77°F (25°C) will reduce battery life. The UPS environment
must be free of conductive contaminants and excessive moisture (water and condensation),
flammable vapors, chemical fumes, corrosive gases and liquids.
2.1.2 Required Setup Equipment
The tools below are required to properly set up your UPS:
• Pallet jack
• 1/2" (13mm) ratchet or wrench
• Torque wrench (in-lb)
• Flathead screwdriver
• #2 Phillips screwdriver
2.1.3 Site Preparation
When deciding where to locate your UPS,
consider the weight and size of the unit. Make
sure that the structural integrity of the floor
can withstand the weight of a fully loaded unit.
12"
(305mm)
Check to make sure that your UPS will be
located in a well-ventilated area with at least
12 inches (305mm) behind it. The UPS is
air-cooled utilizing internal fans. Air is drawn
into the front of the UPS and is exhausted
through ventilation grilles in the back. It should
also have at least 36 inches (915mm) in front in
order to change modules when necessary.
36"
(915 mm)
The unit frame is bolted to the shipping pallet to ensure safety. It is recommended that a pallet jack
be used to transport the unit to its operating location (prior to unbolting the unit).
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
2.2
Unloading
2.2.1 Unloading the UPS
2. Remove the metal ramp from the bottom of
the UPS.
CAUTION
!
This UPS is very heavy (see weight in
Table 1). At least two people should
assist in unloading it from the pallet.
Pull ramp out from
under front of unit,
then turn ramp over
3. Fit the ramp flange in the slot in the rear
of the pallet (back of unit) as shown below.
1. Use a ratchet or wrench, 1/2" (13mm), to
remove the four mounting bolts from the
front and rear pallet brackets. Remove the
mounting brackets from the pallet and
UPS. Keep the brackets for future
Fit ramp in
rear of pallet
transportation of the UPS or for additional
stability of the UPS once in place.
4. Using two people, slowly move the UPS
down the ramp until the UPS is on a level
surface.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
5. Once the UPS is in the desired location, adjust the leveling feet to secure its position.
1/2" (13mm)
2.2.2 Stationary Mounting
Additional stability can be added by bolting the mounting brackets (used in shipping) to the floor, as
shown below left.
Shipping Brackets Used
for Stationary Mounting
Optional Stationary
Mounting Dimensions
4.75"
4.75"
(120mm) (120mm)
28"
(711mm)
5/16" (7.94mm)
diameter - in six
places
For greater stability, use a higher-grade bolt. Refer to the dimensions above right when drilling holes
for stationary mounting.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
2.3
Cable Installation
2.3.1 Wiring Preparation
Customer-Provided Overcurrent Protection
A branch rated overcurrent protection device (cir-
cuit breaker or fused disconnect switch) must be
installed for the AC input.
WARNING
!
Please read this section thoroughly
before attempting to install wiring to
this unit.
If the start-up is on bypass, the UPS has a six-
cycle inrush current that is up to 20 times the
rated output current. This must be taken into
account when selecting the overload protection
device at the AC input supply distribution point.
To avoid random tripping on start-up, it is recom-
mended that the AC input supply be protected
with a circuit breaker capable of withstanding
this initial inrush.
This UPS should be installed by a
qualified / certified electrician.
Removing the Cover Plates
On the back
of the UPS,
cover plates
are over the
input and
output
Remove Cover Plates
This UPS is fitted with EMI suppression filters.
Earth leakage current is less than 40mA. Tran-
sient and steady state earth leakage currents may
occur when starting the equipment. This should
be taken into account when selecting ground cur-
rent detection devices, as the earth leakage cur-
rents of both the UPS and load will be carried.
terminals, as
shown at
right. Keep
screws and
plates to one
side.
Input and output cables must be run in separate
conduits.
Configuring the Bypass Voltage (TB2)
The UPS voltage is factory-set to 208 V.
Should the user have a utility supply of 240 V,
the bypass voltage jumper will have to be
changed to ensure correct output voltage.
After selection, retorque jumper screws to
28 in-lb.
Bypass Voltage Jumper
OR
208 V
(default)
240 V
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Input Wiring (TB1)
To connect the input wiring, follow these steps:
1. Locate the input wiring access, remove the knockout and
pull the three input wires through it, allowing some slack
for installation.
2. Secure the conduit to the rear panel of the UPS.
3. Input Power cables connect to screw terminals on the
Input Terminal Block located to the right of the Bypass
Voltage Terminal. Connect the wires to the block
connections as shown below. Using a torque wrench, turn
the screws clockwise until tightened to the proper torque
value (28 in-lb). Insert the ground wire through the
grounding lug and tighten it to the proper torque value
(120 in-lb).
TB1
L1
Grounding Conductor Installation
1
2
An insulated grounding conductor must be identical or larger
in size, insulation material, and thickness as the grounded
and ungrounded branch circuit supply conductors. This cable
must be green with or without one or more yellow stripes and
is to be installed as part of the branch circuit that supplies
the unit or system.
L2
The grounding conductor is to be grounded to earth at the
service equipment or, if supplied by a separately derived sys-
tem, at the supply transformer or generator set.
Output Wiring (TB3)
Output wiring may be configured one of two different
ways (240/120 or 208/120). Refer to the chart below
and the diagram at right when configuring the out-
put wiring.
Voltage
120
208
240
Between terminals
1 & 4
3 & 4
2 & 3
1 & 3
Use only the connections listed above. Other connections will
produce nonstandard voltages.
NOTE
The Nfinity UPS contains an isolation
transformer that generates a neutral
conductor for the connected equipment.
The UPS is a separately derived source
and contains a neutral to ground bonding
jumper. A grounding electrode conductor
(GEC) must be installed in accordance
with national and local wiring codes and
regulations.
Note the Neutral / Earth
jumper on the terminal
above
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
2.3.2 Connecting to External Panel Boards
The following instructions are also shipped attached to the rear of the unit.
INPUT CABLING AND PROTECTION
Table Below Applies to 4-16kVA Scalable Systems:
Stand-alone UPS or
UPS equipped with a Maintenance Bypass Cabinet (Without Transformer)
Input Voltage – 208VAC
Input Voltage – 240VAC
Recommended
Input Protection
Circuit Breaker
Recommended
Input Protection
Circuit Breaker
Max. Current
in UPS mode
Max. Current
in UPS mode
Max. System
Load Rating
4kVA
8kVA
18 amps
36 amps
53 amps
70 amps
50 amps
50 amps
75 amps
100 amps
15 amps
31 amps
46 amps
50 amps
50 amps
75 amps
100 amps
12kVA
16kVA
62 amps
2
Terminal
Block
Maximum: 35mm (2AWG)
2
Minimum: 16mm (6AWG)
Details
Torque Rating: 2.5-3.0Nm (22-26in/lbs)
UPS With Maintenance Bypass Cabinet (With Transformer)
Single Input Feed: All UPS ratings must use 100A input circuit breaker protection.
Dual Input Feed: See table below.
UPS Feed
Bypass Feed
208V or 240V
Input Voltage – 208VAC
Recommended
Input Voltage – 240VAC
Recommended
Input Protection
Circuit Breaker
Max. Current
Max. Current
in UPS mode Protection Circuit Breaker
Recommended Input
Max. System
Load Rating
Input Protection
Circuit Breaker
in UPS mode
4kVA
8kVA
18 amps
36 amps
53 amps
70 amps
50 amps
50 amps
75 amps
100 amps
15 amps
31 amps
46 amps
62 amps
50 amps
50 amps
75 amps
100 amps
100 amps
100 amps
12kVA
16kVA
100 amps
100 amps
2
Terminal
Block
Maximum: 35mm (2AWG)
2
Minimum: 16mm (6AWG)
Details
Torque Rating: 2.5-3.0Nm (22-26in/lbs)
Bypass Voltage Jumper Position (TB2)
208 VAC
(Factory Default)
240 VAC
(Field Change)
Bypass Voltage Selection
Jumper/link
on upper two
screws
Jumper/link
on lower two
screws
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
OUTPUT CABLING
UPS Output Terminal Block (TB3)
Connection to External Panel Boards
208 VAC
If connected equipment operates at 208VAC only, use a single-phase panel board connected to the UPS as follows.
Setup 1 - 208 VAC
Max output current = 77A
Panel Board Input
UPS Output TB3
1
1
2
3
4
5
2
L
L
L
208
208
3
L
4
5
GEC
Grounding Electrode Conductor
(Field connection must be made)
GEC
Grounding Electrode Conductor
(Field connection must be made)
G
Connected Equipment
Ground
208 VAC and 120 VAC
If connected equipment is a combination of 208 VAC and 120 VAC, use a three-phase panel board connected to
the UPS as follows.
Panel Board Input
UPS Output TB3
Setup 2 - 120 VAC
Max output current = 67A
each 120 VAC circuit
1
L3
2
1
2
3
L2
L
L
120
208
3
L1
120
120
120
Note: L2 to N
is 88 VAC
4
N
5
4
5
GEC
N
Grounding Electrode Conductor
(Field connection must be made)
208 VAC also
available
as shown
connected
in Setup 1
GEC
Grounding Electrode Conductor
(Field connection must be made)
G
CAUTION: It is important for the installing
electrician to clearly identify the connections for
future reference. Refer to NEC 215-8 and 210-4(d).
Connected Equipment
Ground
240VAC and/or 120VAC
If connected equipment operates at 240VAC only or 120VAC only or is a combination of both, use a single-phase
panel board connected to the UPS as follows.
Setup 3 - 240 VAC
Max output current = 67A
Panel Board Input
UPS Output TB3
1
1
L
L
L
240
2
2
3
4
240
120
3
L
120 VAC also
available as shown
connected in Setup 2
120
4
N
5
5
GEC
GEC
Grounding Electrode Conductor
(Field connection must be made)
Grounding Electrode Conductor
(Field connection must be made)
Connected Equipment
Ground
G
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
2.3.3 REPO Connection
The Nfinity is equipped with a Remote Emergency Power Off (REPO) connection.
NOTE
A jumper is factory installed between pins 1 & 2 to disable the Control Switch (SW2).
This will prevent the unit from being started during installation. This jumper must
be removed in order to start the unit.
Figure 2 REPO switch connections
Hanger for cable-tie
to strain relief REPO
wiring
REPO switch
on rear of unit
REPO jumper
connected
as shipped
REPO connections
for normally open
switch system
REPO connections
for normally closed
switch system (fail-safe)
1
2
3
4
1
2
3
4
1
2
3
4
NOTE
Key to REPO switch connections
1. 24 V DC, 50mA
2. Sense
3. Sense
4. Ground
Remove jumper before wiring.
If the installation does not
require connection to a REPO
system, the jumper must be
removed.
CAUTION
!
To maintain safety, Signal Edge Low Voltage (SELV) barriers, and electromagnetic
compatibility, signal cables should be segregated and run separately from power cables.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
2.4
Communications
2.4.1 COM Ports
Pin Assignment
Nfinity is able to communicate through multiple communication
ports simultaneously. Use only Liebert-provided communication
cards. Connect only Signal Edge Low Voltage (SELV)/Class 2 cir-
cuits when connecting to any communication port.
5
4
3
2
1
There are two DB-9 COM ports available on the rear of the Nfinity.
9
8
7
6
COM1 - Relay Contacts
Relay contacts are available through a DB-9F communications connector. Contact closure provides
the following:
Pin
1
Assignment
Low Battery (normally open)
4
UPS shutdown in battery mode
(5-12 V DC for 1.5 sec)
5
7
8
9
Common
Low Battery (common)
On Battery (common)
On Battery (normally open)
These contacts are rated 48 VDC, 1 amp maximum and are compatible with Liebert MultiLink™
software.
COM2 - Serial
Nfinity is able to communicate via Liebert proprietary protocol. This communication port can be used
for serial communication with Liebert MultiLink software. For more detailed information, please see
the MultiLink software documentation on the CD shipped with the Nfinity. The pin-out configuration
of the DB-9 connector is:
Pin
2
Assignment
Transmit Data
3
Receive Data
Common
5
2.4.2 Intellislot™ Ports
The following communication cards may be used with Nfinity:
• Intellislot OpenComms Web Card—allows
the Nfinity to communicate intelligently with
your Ethernet network. The OpenComms Web
Card must be installed in port 1.
Port 1 Port 2
Port 3 Port 4
• Intellislot MultiPort4 cards—allows up to
four client computer systems to monitor the sta-
tus of Nfinity simultaneously.
• Intellislot Relay Contacts cards—provides
contact closures for remote monitoring of alarm
COM 1
COM 2
conditions; On Battery, On Bypass, Low Battery,
Summary Alarm, UPS Fault and On UPS
signals.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
3.0 OPERATING INSTRUCTIONS
3.1 Controls and Indicators
3.1.1 Display Controls
The User Interface Module informs you of the status of the UPS and lets you configure the UPS to
your own needs or preferences.
The module consists of a series of Status LEDs, an LCD display window (four lines of 20 characters
each), and buttons for navigation, as displayed below.
Status LEDs
Fault/Warning LED
Standby Button
ESC
LCD Display
Window
Alarm
Silence
Button
Navigation Buttons
Buttons
Fault/Warning and Status LEDs
Refer to the legend below to properly navigate the
Nfinity User Interface.
Refer to the legend below to indicate occurrence
when an LED is lit.
Fault/Warning
Up
Solid - A UPS fault condition has occurred.
Flashing - A Warning has occurred. Consult event log.
- Navigates cursor on display menus
Down
AC Input - AC utility is available.
Escape - Returns to previous display screen
ESC
On Bypass - The Bypass is supplying the power.
Inverter On - The inverter is supplying the power.
On Battery - Battery is supplying power to the inverter.
AC Output - Power is available to supply the load.
Enter
- Selects displayed information
Standby - Enables / disables output power
Alarm
Silence
- Mutes the audible alarm
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
3.2
Status LED Modes
3.3
Navigating the Menu
To review or change any settings on the UPS,
use the buttons on the User Interface shown
at left. Because some menus contain more
than four rows of information, you may see an
arrow on the display pointing up or down (as
shown below)—indicating to scroll using the
UPS is Off or Initializing
or
buttons.
If you are scrolling through any of the Main
Menus, items will scroll one line at a time
with the menu heading on the top line:
UPS is On, Utility is Good
and Output is Off
UPS Status
Present Load
Redundant Status
Battery Status
UPS is On, Utility is Good
and Output is On
(Normal Operation)
Pressing
reveals:
UPS Status
Redundant Status
Battery Status
Volts/Amps/kVA
UPS is On, Utility is Bad
and Output is On
(On Battery Operation)
Note the arrows on the screen indicate that
the user can scroll up or down to reveal more
information.
UPS is On, Utility is Bad
and Output is Off
UPS is in Bypass Operation
(Manual or Automatic)
UPS is in Manual Bypass
Operation with Utility Out of
Bypass Operation Range
Shutdown Due to
End of Discharge
LED Off
LED On
LED Flashing
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
3.4.3 Manual Transfer to Bypass
3.4
Operating Procedures
To manually transfer the UPS to bypass,
move the manual bypass switch to the bypass
position. The manual bypass switch is behind
the front bottom bezel. To transfer the UPS
from bypass to normal mode, follow the on-
screen instructions.
3.4.1 Start-Up and Initialization
Follow these steps to start up the UPS.
1. Ensure the manual bypass switch is in
UPS position. Close Input Circuit Breaker
(CB1) and close the Control Enable
Switch (SW2). You should see the
Main Menu
> Transfer to Bypass
following on the LCD display window:
UPS Initializing
Please wait...
Transfer to Bypass
Press for bypass
Press ESC to cancel
*Press to Enable
UPS Output.
2. Press
or
button.
ESC
Assert manual bypass
On Mains/Utility
Output % = xx
Battery Minutes yyy
Press for menu
Once
is pressed, the bypass alarm will
annunciate and cannot be canceled until the
manual bypass switch is operated.
3. Press
to access the Main Menu.
3.4.2 Shutting Down the UPS
Use the following procedure to power down
the UPS.
On Bypass
Manual
Bypass
Switch
1. Press
connected equipment.
2. Verify request to disable the output by
pressing
to disable power from the
On UPS
.
3. Turn off the Enable Switch (SW2). Open
the Input Circuit Breaker (CB1).
UPS on manual bypass
NOTE
The load is not protected from utility
interruptions when the UPS is in
bypass mode.
To transfer the UPS from bypass to normal
mode, simply operate the manual bypass
switch back to the UPS position.
On return from bypass, the following screen
will be displayed.
No active alarms
See Event Log
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
3.5
Main Menu
After initialization, the
button will take you to the Main Menu. From here you may check on the
status of the UPS, review the event log and active alarms, configure your UPS and even receive
instructions on replacing modules. The Main Menu is divided into eight sub-menus as shown below:
Main Menu
> UPS Status
UPS Configuration
Display Date/Time
Event Log
Active Alarms
Transfer to Bypass
Module Replacement
Service Tools
UPS Status
Event Log
Module Replacement
UPS Status
Event: xxx/xxx xx
event message
Module Replacement
Ctrl w/ Redundant
Ctrl w/o Redundant
Pwr w/ Redundant
Pwr w/o Redundant
Battery Module
Present Load
Redundant Status
Battery Status
Volts/Amps/kVA
UPS Frequency
event message
DD/MMM/YYYY HH:MM:SS
Bypass Information
UPS Information
Module Information
UPS Configuration
Active Alarms
Service Tools
UPS Configuration
Review Settings
Change Settings
Service Mode
Active Alarms Message
Service Tools
UPS Test
Clear Failures
BM Cell Replacement
Reset Battery Stats
Reset Bypass Stats
Transfer to Bypass
Press for bypass
Press ESC to cancel
Display Date/Time
Date/Time
xx/xx/xxxx xx:xx:xx
mm/dd/yyyy hh:mm:ss
Use the
and
buttons to select the desired menu item and press
to access the appropriate
submenu.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
3.5.1 UPS Status Screen
From the Main Menu the user may select UPS Status and press
. Once at the UPS Status Screen,
the user may access any information on the present condition of the UPS. Note the chart below when
reviewing the UPS.
Main Menu
> UPS Status
UPS Configuration
Display Date/Time
Event Log
Active Alarms
Transfer to Bypass
Module Replacement
Service Tools
UPS Status
UPS Status
Present Load
Redundant Status
Battery Status
Volts/Amps/kVA
UPS Frequency
Bypass Information
UPS Information
Module Information
UPS Status menu options
Present Load
Volts/Amps/kVA
Module Information
On Mains/Utility
Output: kVA xx.x
Output: kW xx.x
Output: pf xx.x
Input
Output
Main Control
S/N: xxxxxxxxxxxxxxx
FW ver: xxxx
xxx VAC
xxx A
xxx VAC
xxx A
xx.x kVA
xx.x kVA
Redundant Control
S/N: xxxxxxxxxxxxxxx
FW ver: xxxx
Redundant Status
Redundant Status
PMs Installed xx
PM:N+1 redundant/non-redundant
SC:Redundant/(non-redundant)
UPS Frequency
UPS Frequency
Input Hz: xx.x
Output Hz: xx.x
User Interface
S/N: xxxxxxxxxxxxxxx
FW ver: xxxx
Bypass Information
Bypass Reasons
Manual-User x
Overload
Other
Battery Status
Battery Status
Voltage (VDC) xxx
Capacity % xxx
Power Module
S/N: xxxxxxxxxxxxxxx
FW ver: xxxx
x
x
Status: charging
BMs Installed xx
Ext batt present: No
Discharge count: xxxx
Batt Usage Hr: xxxx.x
Battery Module
S/N: xxxxxxxxxxxxxxx
FW ver: xxxx
UPS Information
UPS Information
UPS ID: xxxxxxxxxxxx
xxxxxxxxxxxxxxxxxxx
Bays=x,XFMR=x
Defaults = xxxV/xxHz
Limit/Cnfg=xxxkVA/1x1
Model ID=x
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
3.5.2 UPS Configuration Screen
Review Settings
Follow this procedure to review your UPS configuration settings. Follow the menus below by pressing
and to review the settings.
Main Menu
UPS Status
> UPS Configuration
Display Date/Time
Event Log
Active Alarms
Transfer to Bypass
Module Replacement
Service Tools
UPS Configuration
UPS Configuration
> Review Settings
Change Settings
Service Mode
Review Settings
Voltage
Frequency
Battery
Alarm
Service Contact
Auto Restart
UPS Shutdown Delay
Remote Shutdown
External Battery
Bypass Alarm Mode
Intelli-Battery Ca.
Air Filter Reminder
Guarantee Shutdown
Review Settings menu options
Service Contact
Voltage
External Battery
Voltage Settings
Input 208/120
Output 208
Service Contact
Liebert Corp.
External batt config
Amp.Hr
0000
Charge (A) 00.0
Frequency
Bypass Alarm Mode
Auto Restart
Auto Restart
Frequency Settings
Frequency Hz: 60
Sync Range Hz: +/- 5.0
Slew Range Hz/S: 3.0
Bypass Alarm Mode
Mode:
Enable
Mode:
Batt %
Delay
Disable
0%
10
Intelli-Battery Ca.
Intelli-Batteries
0
Battery
UPS Shutdown Delay
UPS Shutdown Delay
120 seconds
Battery Settings
Test intrvl weeks: 2
on Wed 06:00
Air Filter Reminder
Air Filter Reminder
Low Batt Warn:2 min
Mode:
26 weeks
Remote Shutdown
Remote comm shutdown
Mode: Enable
Alarm
Guarantee Shutdown
Guarantee Shutdown
Mode: Enable/Disable
Alarm Settings
Redundant Alarm:
Enabled/Disabled
Max Load: Enabled/Disabled
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
Change Configuration Settings - Change Settings Menu
Starting from the Main Menu, locate and press UPS Configuration. From the UPS Configuration
screen, select the Change Settings option. You may configure Nfinity from a large variety of selec-
tions. Items indicated by an asterisk (*) are the selected settings.
Main Menu
UPS Status
> UPS Configuration
Display Date/Time
Event Log
Active Alarms
Transfer to Bypass
Module Replacement
Service Tools
UPS Configuration
UPS Configuration
Review Settings
> Change Settings
Service Mode
Change Settings
Input Voltage
Display Voltage
Frequency Sync Range
Frequency Slew Rate
Set Password
Auto Battery Test
Low Battery Warning
Auto Restart
User Settings
Set Date/Time
Max Load Alarm Set
UPS Shutdown Delay
Redund Alarm Set
Service Contact
Remote Shutdown
External Battery
Bypass Alarm Mode
Intelli-Batt Ca.
Air Filter Reminder
Guarantee Shutdown
Line Compensation
Factory Defaults
Input Voltage: Select the required input voltage set- Frequency Slew Rate: Sets the rate of change of
ting. This voltage must match the bypass voltage
jumper setting.
frequency through the sync range window.
Frequency Slew Rate
0.5 Hz
Input Voltage
* 208/120
240/120
1.0 Hz
2.0 Hz
3.0 Hz
4.0 Hz
Display Voltage: Displays the actual voltage the
unit is configured for.
* 5.0 Hz
Set Password: Set a Password to prevent unautho-
rized users from changing the configuration of the
Nfinity. It can be up to seven characters in length.
Once set, the password will be required to change the
configuration.
Display Voltage
208
* 240
Frequency Sync Range: Sets the window to which
the system synchronizes to the input supply.
Set Password
xxxxxxx
Frequency Sync Range
0.5 Hz
1.0 Hz
2.0 Hz
NOTE
3.0 Hz
If the password is lost, call Liebert Technical
Support.
4.0 Hz
* 5.0 Hz
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
Auto Battery Test: Configure when and how often
Auto Restart: Automatically restarts once both
the Nfinity’s automatic battery test will run. This test delay parameters (battery capacity percentage and
is designed to ensure battery system integrity and
provide early warning of problems.
countdown timer) are met.
Auto Restart
Mode
Auto Battery Test
Interval
Auto restart batt %
Auto restart delay
Start Day
Start Time
Auto Restart Mode
Interval
Batt Test Interval
1 week
Auto Restart Mode
* Enable
Disable
* 2 weeks
3 weeks
4 weeks
Auto Restart Batt %
Auto Restart Batt %
6 weeks
Disabled
* 0%
10%
25%
40%
60%
80%
Start Day
Batt Test Weekday
SUN
MON
TUE
WED
THU
FRI
SAT
Auto Restart Delay
Auto Restart Delay
in 10-second
increments,
x0 sec
Start Time
Battery Test Time
06:00
User Settings: You may adjust the contrast of the
user interface LCD or select the appropriate lan-
guage.
Low Battery Warning: Notifies user how much run
time is available. Can be set from 1 to 30 minutes.
User Settings
Screen Contrast
Display Language
Low Battery Warning
02 Minutes
Screen Contrast
Screen Contrast
Press to increase
Press to decrease
Display Language
Display Language
English
Francais
Italiano
Deutsch
Espanol
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
Set Date/Time: Allows user to enable/disable DST
(Daylight Saving Time), change the Day, Date and
Time setting on Nfinity. When enabled, the time will
automatically adjust to Daylight Saving Time.
Service Contact: Set a contact for the user to reach
if problems occur.
Service Contact
>Company Name
Company Phone
Set Time/Date
DST Mode
Set Time/Date
Company Name
Company/Name
DST Mode
LIEBERT CORP.
DST Mode
Enabled
* Disabled
Phone Number
Phone Number
Set Date/Time
Date/Time
WWW.LIEBERT.COM
MM/DD/YYYY HH:MM:SS
Remote Shutdown: Enables / Disables the Remote
Communications Shutdown.
Max Load Alarm Set: Allows an alarm to set when
Nfinity’s load reaches a specific level.
If you are using MultiLink™ software, this parameter
should be enabled in order for the UPS output to be
turned off once the operating system has been shut-
down.
Max Load Alarm Set
Mode
Threshold
Remote Shutdn
* Enable
Disable
Alarm Mode
Max Load Alarm Mode
* Enable
External Battery: Sets total amp-hour for external
batteries to provide a more accurate runtime remain-
ing value on the LCD display and through communi-
cations.
Disable
Threshold
Max Load Alarm Set
Threshold kVA = xx.x
External Battery
Amp-hour
> Charge Current
UPS Shutdown Delay: Delays UPS shutdown for
specified amount of time after receiving shutdown
command via relay contacts only.
External Batt Config
Enter total amp-hour
0000
UPS Shutdown Delay
xxx seconds
External Batt Config
Enter charge current
00.0
Redundant Alarm Set: Sets Alarm to notify user
when redundancy is no longer available.
Redundant PWR Alarm Set
Enable
* Disable
When using the Non-Modular External Battery
Cabinets with Chargers (P/N: PB10SLF105WC120),
enter the following:
# Cabinets
AH Value
0091
Charge Current
1
2
3
4
5
6
07.0
14.0
21.0
28.0
35.0
42.0
0182
0273
0364
0455
0546
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
Bypass Alarm Mode: Allows the user to enable/dis- Guarantee Shutdown: Allows the user to guarantee
able alarm, indicating that the bypass is not quali-
fied.
a shutdown after a low battery warning is announced,
even if the utility becomes qualified.
Bypass Alarm Mode
> Enable
Guarantee Shutdown
Enable
* Disable
Disable
Line Compensation: Allows the user to control the
amount of line drop compensation to be applied to the
nominal output voltage. Line drop compensation is
intended to compensate for any IR drop that may
occur when the UPS is a significant distance from the
protected load.
Intelli-Battery Ca.: Allows the user to enter the
quantity of intelligent battery cabinets installed.
Enter Intelli-
Battery cabinet
count
x
Output Volt: x
Increase Decrease
ESC to cancel
Air Filter Reminder: Allows the user to set a warn-
ing reminder to check the air filters.
to Accept & Exit
Air Filter Reminder
2 weeks
4 weeks
Factory Defaults: Allows the user to reset all set-
tings to the values in effect when the UPS was
shipped from the factory.
10 weeks
26 weeks
52 weeks
* Disable
Load Factory Default
Are you sure?
Press for yes
Press ESC for no
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
UPS Configuration Screen - Service Mode Menu
Service Mode contains site identification information about the UPS system. The data is entered by
Liebert Global Services (LGS). To view the data, go to the Main Menu, select UPS Configuration and
press
. Next, select Service Mode and press
.
Set Site ID: Press
menu. Scroll to Set Site ID and press
the screen shown below.
to return to the Service Mode
ESC
Main Menu
to display
UPS Status
> UPS Configuration
Display Date/Time
Event Log
Service Mode
Service Mode
> Set Site ID
Set Tag Number
Set UPS ID
Active Alarms
Transfer to Bypass
Module Replacement
Service Tools
Set Site ID
-
UPS Configuration
UPS Configuration
Review Settings
Change Settings
> Service Mode
Set Tag Number: Press
Mode menu. Scroll to Set Tag Number and press
to display the screen shown below.
to return to the Service
ESC
Service Mode
Service Mode
Service Mode
> Set Site ID
Set Tag Number
Set UPS ID
Service Mode
Set Site ID
> Set Tag Number
Set UPS ID
Set Tag Number
-
Set UPS ID: Press
menu. Scroll to Set UPS ID and press
the screen shown below.
to return to the Service Mode
ESC
to display
Service Mode
Service Mode
Set Site ID
Set Tag Number
> Set UPS ID
Set UPS ID
3.5.3 Display Date/Time
This feature shows the current date and time. At the Main Menu, select UPS Configuration and
press
. Next, select Display Date/Time and press
.
Main Menu
UPS Status
UPS Configuration
> Display Date/Time
Event Log
Active Alarms
Transfer to Bypass
Module Replacement
Service Tools
Display Date/Time
Date/Time
xx/xx/xxxx xx:xx:xx
mm/dd/yyyy hh:mm:ss
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
3.5.4 Event Log
3.5.5 Active Alarms
Accessing the Event Log enables the user to
Alarms affecting the Nfinity can be viewed at
the Active Alarms screen. To access the
screen, go to the Main Menu, select Active
scroll through the Nfinity’s past 255 occur-
rences. To open the Event Log, start at the
Main Menu, select Event Log and press
.
Alarms and press
.
Main Menu
Main Menu
UPS Status
UPS Status
UPS Configuration
Display Date/Time
> Event Log
UPS Configuration
Display Date/Time
Event Log
Active Alarms
> Active Alarms
Transfer to Bypass
Module Replacement
Service Tools
Transfer to Bypass
Module Replacement
Service Tools
Event Log
Active Alarms
Event: xxx/xxx xx
event message
Active Alarms Message
event message
DD/MMM/YYYY HH:MM:SS
When an alarm sounds, the User Interface
LCD will display a general explanation as to
what the alarm is indicating. To view these
messages in chronological order, press the
Press the
and
buttons to scroll through
the Nfinity’s Event Log in chronological order.
The Event Log contains the following infor-
mation.
and
buttons.
• The first line of a typical Active Alarms
screen will display the reason for the
alarm occurrence.
• The second line will give a more specific
detail of the occurrence (i.e., module serial
number).
Reference Code
Event Number
Description
Event 031/255
NC09
Power module warning
S/N:0012200001002G1
19 MAY 2000 16:54:27
Event Detail or
Serial Number
Press
to go back to the Main Menu.
ESC
Date of
Event
Time of
Event
3.5.6 Transfer to Bypass
The typical event log screen will display the
event number and reference code on the first
line. The purpose of this code is to assist fac-
tory trained service personnel in trouble-
shooting. Please make a note of the code
number when contacting technical support.
The second line contains the event descrip-
tion. The third line will have either more
detail about the event, a serial number indi-
cating as to which module the event occurred,
or be left blank. The last line will show the
date and time the event occurred.
In the event of a UPS overload or failure, the
UPS will transfer to bypass via its automatic
bypass switch.
Main Menu
UPS Status
UPS Configuration
Display Date/Time
Event Log
Active Alarms
> Transfer to Bypass
Module Replacement
Service Tools
Press
to go back to the Main Menu.
ESC
When an event or alarm occurs, the User
Interface LCD will display the last message
regardless of the default screen. See 4.1 -
Active Alarms for a list of events and alarms
and possible solutions. If you are unsure of
the corrective action to take, contact a Liebert
representative at the number listed on the
back of this manual.
Transfer to Bypass
Press for bypass
Press ESC to cancel
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
3.5.7 Module Replacement
The user interface also supplies instructions for removing and replacing modules. From the Main
Menu, access the module replacement screen and select the type of module. Refer to the screens
below:
Main Menu
UPS Status
UPS Configuration
Display Date/Time
Event Log
Active Alarms
Transfer to Bypass
> Module Replacement
Service Tools
Module Replacement
Module Replacement
> Ctrl w/ Redundant
Ctrl w/o Redundant
Pwr w/ Redundant
Pwr w/o Redundant
Battery Module
Module Replacement menu options
Control Module w/ Redundant
Power Module w/ Redundant
Battery Module
Cntl Mod Replacement
1. Lift off display
panel and place
Pwr Mod Replacement
1. Remove all
Battery Module
1. Remove all
front bezels
front bezels
on top of UPS
2. Locate amber LED
3. Open lever
2. Locate amber LED
3. Loosen fastener
4. Replace module
5. Tighten fastener
6. Replace all bezels
2. Locate amber LED
3. Open lever
4. Loosen fastener
5. Replace module
6. Tighten fastener
7. Close lever
4. Loosen fastener
5. Replace module
6. Tighten fastener
7. Close lever
8. Replace all bezels
8. Replace display
Control Module w/o Redundant
Power Module w/o Redundant
Cntl Mod Replacement
1. Remove bottom
bezel and place
UPS in bypass
2. Lift off display
panel and place
on top of UPS
3. Locate amber LED
4. Open lever
5. Loosen fastener
6. Replace module
7. Tighten fastener
8. Close lever
9. Wait for amber LED
to stop flashing.
10.Replace display
11.Switch bypass to
return to UPS
operation
12.Replace bezel
Pwr Mod Replacement
1. Remove bottom
bezel and place
UPS in bypass
2. Remove remaining
front bezels
3. Locate amber LED
4. Open lever
5. Loosen fastener
6. Replace module
7. Tighten fastener
8. Close lever
9. Wait for amber LED
to stop flashing.
10.Switch bypass to
return to UPS
operation
11.Replace all bezels
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
3.5.8 Service Tools for Liebert Global Services Engineers
The Service Tools option is intended for use by Liebert Global Services engineers or Liebert-trained
engineers to carry out certain tests and clear failures. These are advanced menus, entering changes
may adversely affect UPS operation. From the Main Menu, shown below left, select Service Tools and
press
.
BM Cell Replacement: Allows a Liebert-trained
engineer to reset the battery module (BM) energy val-
ues to defaults after replacing battery cells within the
module.
Main Menu
UPS Status
UPS Configuration
Display Date/Time
Event Log
Active Alarms
Service Tools
Transfer to Bypass
Module Replacement
> Service Tools
Service Tools
UPS Test
Clear Failures
> BM Cell Replacement
Reset Battery Stats
Reset Bypass Stats
Service Tools
Service Tools
> UPS Test
Clear Failures
Reset All BM Energy
Settings to Default
Press for Yes
BM Cell Replacement
Reset Battery Stats
Reset Bypass Stats
Press ESC for No
UPS Test: Allows a Liebert-trained engineer to test
the Batteries, LEDs or LCD.
Reset Battery Stats: Allows a Liebert-trained engi-
neer to reset all battery statistics. These statistics
include battery usage and discharge count.
Service Tools
Service Tools
Service Tools
> UPS Test
Service Tools
Clear Failures
UPS Test
BM Cell Replacement
Reset Battery Stats
Reset Bypass Stats
Clear Failures
BM Cell Replacement
> Reset Battery Stats
Reset Bypass Stats
UPS Test
LED
Reset Battery Stats
Are you sure?
LCD
Battery
Press for Yes
Press ESC for No
Clear Failures: Allows a Liebert-trained engineer to
reset the UPS after a Battery Module failure alarm.
Reset Bypass Stats: Allows a Liebert-trained engi-
neer to reset all bypass statistics. These statistics
include manual bypass count, bypass overload count
and other bypass count.
Service Tools
Service Tools
UPS Test
> Clear Failures
BM Cell Replacement
Reset Battery Stats
Reset Bypass Stats
Service Tools
Service Tools
UPS Test
Clear Failures
BM Cell Replacement
Reset Battery Stats
> Reset Bypass Stats
Clear Failures
Clear batt failures
Reset Bypass Stats
Are you sure?
Clear batt failures
Press for Yes
Press for Yes
Press ESC for No
Press ESC for No
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
4.0 TROUBLESHOOTING
4.1 Active Alarms
In the event of an alarm, the User Interface LCD will display the last message regardless of the
default screen. A list of possible alarm messages is displayed below. If you encounter one of these or
other alarm messages and are unsure of the corrective action to take, please contact a qualified Lie-
bert representative at the number listed on the back of this manual.
User Interface Text
Cause
Action
Main Control Failure The Nfinity system has detected a
System Control Module failure.
Identify and replace the failed System Control Module or
contact Liebert Global Services for support.
Power Module Fail The Nfinity system has detected a Power Identify and replace the failed Power Module or contact
Module failure. Liebert Global Services for support.
Battery Module Fail The Nfinity system has detected a Battery Identify and replace the failed Battery Module or contact
Module failure.
Liebert Global Services for support.
Redun. Control Fail The Nfinity system has detected a
System Control Module failure.
Identify and replace the failed System Control Module or
contact Liebert Global Services for support.
Battery Card Failure The Nfinity system has detected an
Intellislot Battery Card failure.
Identify and replace the failed Intellislot Battery Card or
contact Liebert Global Services for support.
UPS On Battery
The Nfinity is drawing power from the
batteries, not from utility.
Verify input breaker is closed. Verify input voltage is
present and correct voltage. Verify input frequency is
correct.
Reminder alarm -
Check air filter
The fan filter reminder time has elapsed. Check and clean the fan filter and acknowledge the alarm.
This alarm may be disabled or the interval between these
alarms can be configured via the User Interface.
Short Circuit
User tried to turn the output on following a Wait for at least 30 seconds and then turn the output on.
Recovery - Please short circuit on the output without waiting
Wait for the required 30 seconds to expire.
Power Module N+1 Number of power modules is not
Redundancy Alarm adequate to provide power redundancy.
Reduce the UPS’s load, add power modules to the frame
or disable the alarm feature via the User Interface.
Output Off - Output A short circuit was detected on the output. Correct short (or extreme overload condition) and turn on
Short Circuit
the UPS’s output.
UPS Output
Overload
The load on the Nfinity exceeded the
capacity of the active power modules.
Reduce the UPS’s load or add power modules.
Output exceeds
max load setting
This will occur if the max load alarm is
enabled, and the measured load at the
UPS’s output is greater than the value
set.
Reduce the UPS’s load, increase the Maximum Load
Alarm limit via configuration or disable the Maximum Load
Alarm limit via configuration.
Output Off-
Overload, bypass
unavailable
Normally a severe overload will cause the Reduce the UPS’s output load and verify that the UPS’s
unit to go to automatic bypass. This event bypass source is qualified (amplitude and frequency).
informs the user that bypass was not
qualified so the unit dropped the load to
protect itself.
Verify that the configuration voltage and frequency
settings are properly selected.
Switch To
Manual Bypass
The Nfinity is on automatic bypass.
Manual bypass switch should be
activated before servicing.
Transfer Nfinity to manual bypass and call Liebert service
for assistance.
Load Exceeds
Battery Module
Capacity
The measured load on the output will
cause the battery modules to exceed their non-modular battery cabinet(s) are added, verify that the
limits if the UPS transfers to battery
mode.
Reduce the UPS’s load or add battery capacity. If external
UPS’s configuration is set to match the external battery
amp-hour rating and charger rating.
Bypass source
not qualified
The input voltage is not within the
specified voltage or frequency range so
the UPS will not allow an automatic or
manual transfer to bypass.
Verify UPS’s configuration for voltage and frequency.
Check UPS’s input breaker; disable this alarm if desired
via configuration.
Load exceeds
frame limit
Load is greater then the rated frame limit. Reduce the UPS’s load.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
User Interface Text
Cause
Action
Assert manual
bypass
A user-initiated transfer to bypass will
assert this alarm, instructing the user to
enable the manual bypass switch. Once
Engage the manual bypass switch (located at the bottom
front on the left hand corner of the unit). Once engaged,
the switch may be de-asserted to return to normal
the manual bypass is asserted, the alarm operation.
will clear. This is a non-mutable alarm.
Remote shutdown The most likely cause is that the incorrect Check for a wiring problem to the Shutdown On Battery at
on COM port 1
active
cable has been connected to the COM
port between the UPS and the host.
the COM1 connector. If this problem is not addressed, the
unit will shut down shortly after switching to battery
operation.
Battery Test
Weak Battery
The battery was determined to be weak
as a result of the battery test.
Depending on the age of the batteries, it may be
appropriate to replace all batteries in the system.
Schedule a battery test so that the system operation is
double-checked once the batteries become fully charged.
Battery Test
Failure
One or more of the following was
detected during a battery test:
• UPS output regulation failure was
detected.
Replace the battery modules that have active failures/
warnings. Depending on the age of the batteries, it may be
appropriate to replace all batteries in the system.
Schedule a battery test so that the system operation is
double-checked once the batteries become fully charged.
• A battery module warning or failure
occurred.
• A system control failure occurred.
Battery Cabinet
Not Connected
This is intended to detect a situation
where a Modular battery cabinet has
been connected for communication, but
the power busses are not connected.
Check that the Modular Battery breaker is closed. Verify
proper connections between UPS and Modular Battery
Cabinet.
Don’t Remove SC
The only good System Control Module
lock lever was raised with the output on
and the unit is not on bypass.
• Lower the lock lever on the System Control Module.
• Provide qualified bypass power so that transfer to
bypass is possible.
• Add a redundant System Control Module so that the load
is not dropped.
Failure: Select
Manual Bypass
The System Controller detected a failure. Transfer UPS to manual bypass and contact Liebert
Select manual bypass so that the unit can Global Services.
be serviced.
Output Off -
This event informs the user that bypass
Verify that the UPS’s bypass source is qualified (amplitude
bypass unavailable was not qualified so the unit dropped the and frequency). Verify that the configuration voltage and
load to protect itself.
frequency settings are properly selected.
Last UPS Shutdown REPO switch was pressed.
If REPO wasn’t pressed, check for REPO wiring problems.
By Emergency
Power Off
External Battery
Module Warning
The energy delivered from the Non-
Modular battery did not meet
programmed battery capacity.
Verify proper connections between UPS and Non-Modular
Battery Cabinet. Reenter the amp-hour rating for the
external battery (set the amp-hour entry to zero and press
the return key, then reset it to the appropriate value for the
external battery). If the problem persists, the external
battery should be replaced.
Battery Module
Not Ready
A battery module is not ready. In most
cases, one or more battery modules
should indicate a warning/failure
condition.
Ensure that the battery module is fully seated and the 1/4
turn fastener is engaged. If the problem persists, replace
the battery module with warning/failure condition indicated
at the User Interface. If no User Interface warning/failure
of battery module, look for the battery module with LEDs
indicating a problem and replace that unit.
Power Module
Not Ready
A power module is not ready. In most
cases, one or more power modules
should indicate a warning or failure
condition.
Ensure that the power module is fully seated and the 1/4
turn fastener is engaged. If the problem persists, replace
the power module with warning/failure condition indicated
at the User Interface. If no User Interface warning/failure
of power module, look for the power module with LEDs
indicating a problem and replace that unit.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
4.2
Module LED Indication
Every Battery, Power and Control Module features two LEDs to help inform the user of the module
Table 2
Guide to LEDs
Green Status LED
Yellow Fault LED
Status
LED
Fault
LED
Control Module
(Green)
(Yellow)
Module Status
Module not inserted into
frame. System is OFF.
OFF
OFF
Module is initializing
(max 30 seconds*).
OFF
ON
Green Status LED
Yellow Fault LED
FLASHING
OFF
Normal Operation
Module is in start-up
qualification mode or module
warning. **
FLASHING FLASHING
FLASHING
OFF
ON
FLASHING
OFF
Module failed and is off-line.
Power Module
Abnormal operation,
re-insert module.
ON
If this persists, contact
Liebert Global Services at
1-800-543-2378.
ON
ON
Green Status LED
Yellow Fault LED
ON
FLASHING
*
If this persists for more than 30 seconds, check to verify the
lever is in the down position, otherwise the module is faulty.
** If both green and yellow LEDs are flashing for more than 30
seconds, then reinsert module.
Battery Module
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
4.3
Module Replacement
MODULE REMOVAL
Follow the instructions below when replacing or
adding a Control, Battery or Power Module to the
system.
To order additional modules, contact your Liebert
representative or call 1-800-LIEBERT.
4.3.1 Removing Modules
1. Remove bezel cover of appropriate module.
When replacing a Power or Battery Module,
verify the faulty module by confirming the
yellow LED is lit.
2. If removing a Control or Power Module with
no redundant modules, switch UPS to
manual bypass.
3. Pull out and lift the lever if replacing a
Control or Power Module, then turn fastener
counterclockwise until it is loosened.
Turn fastener
counterclockwise
Lift lever up (for
Control and Power Modules)
4. To remove the module:
a. Start to pull out module (shown above
right, top). About 2/3 out it will stop.
CAUTION
!
Battery Modules are heavy—66 lb (30 kg).
b. Slide module away from the center of the
UPS (shown above right, center).
c. Continue to pull until module is removed
(shown above right, bottom).
WARNING
POTENTIAL TIP HAZARD
Install all battery modules starting from
the bottom. For module removal, start
from the top. Do not remove more than
one module at a time. Failure to do so
may cause unit to tip over and cause
serious injury.
5. Dispose of module in an environmentally
responsible way that complies with local
codes/regulations or return to Liebert for
proper disposal.
NOTE
Battery Modules may contain shipping
screws. These screws may be removed and
discarded.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
4.3.2 Adding or Replacing Modules
NOTE
Power Modules must be installed in the top half of the Nfinity frame. Battery Modules can be
installed in any bay of the UPS frame.
1. Lift module to appropriate bay, resting end of module on bay
shelf. Use caution not to rest the module on the lower bezel
cover.
Turn fastener
clockwise
2. Push module into bay. Once halfway in, slide module sideways
toward the center of the UPS. Continue pushing module until
fully inserted.
3. Press and turn fastener clockwise until locked. If replacing a
Control or Power Module, press lever down.
4. Wait about 15 seconds as the module performs a start-up test
and synchronizes with the other modules. Both the yellow and
green LEDs should be flashing. A green flashing LED will
then confirm the module is properly installed.
5. If UPS was placed in bypass manually, transfer back to UPS
operation.
6. Replace bezels.
Press lever down (for
Control and Power Modules)
NOTE
When replacing the Control Module, record user configuration data before removing. Re-verify
the configuration settings after the new Control Module is installed.
4.3.3 Replacing the User Interface
1. Lift off user interface and set it on top
of the UPS frame.
2. The attached cable will be connected to
an Intellislot card, found in a port
between the control modules.
3. Remove the cable and the attached
Intellislot card from the UPS.
4. Plug the new Intellislot card into the
UPS.
5. Plug the new user interface cable into
the Intellislot card.
6. Set replacement User Interface into
proper position.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
5.0 MAINTENANCE
5.1 Maintenance
5.1.1 Proper Care
Keeping your Liebert Nfinity UPS operating properly is imperative to optimal performance and life of
the unit. It is recommended that a certified technician perform preventive and corrective mainte-
nance. Liebert Global Services (LGS) is dedicated to ensuring the highest level of performance and
unmatched support for your Nfinity UPS. Contact an LGS representative for service to guarantee
maximum reliability and system availability.
5.1.2 Scheduled Maintenance
It is recommended the following maintenance is performed at least monthly:
• Clean unit
• Clean / replace filters
• Verify proper airflow
It is recommended the following maintenance is performed annually:
• Verify all Power Modules are operating properly.
• Verify all Battery Modules are operating properly.
• Verify redundancy (if applicable).
5.1.3 Replacing Fan Filters
Nfinity’s intake fans contain filters that will need to
be replaced or cleaned periodically, depending on
the surrounding environment. Check by removing
the bottom bezel and noting the condition of the two
filters. If filters are dirty, replace them by removing
the plastic cover over the filter frame and inserting
a new filter in its place. Use caution when replacing
filters when fans are running.
The fan filters are washable and can be reused. To
wash filters, place them under running water (with
the dirt side down) to remove dirt and dust. Blot dry
with a towel and allow air-drying before reusing.
Fan Filters
36
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
6.0 SPECIFICATIONS
General & Environmental
Units
kVA
kW
Configuration
4
8
12
16
Unit Rating
2.8
5.6
8.4
11.2
Compliant Safety Standards
Conducted and Radiated EMC Levels
Compliant Immunity Standards
Mechanical
UL 1778; c-UL
FCC Part 15, Class A
IEEE C62.41, Category B
Units
8 Bay
12 Bay
20 (508)
28 (711)
Width
20 (508)
28 (711)
40 (1016)
Dimensions
Depth
Height
in (mm)
54 (1372)
Environmental
Units
F (C)
%
Operating Temperature (max)
Relative Humidity
32° - 104° (0° - 40°)
0-95% non-condensing
10,000 (3,000)
Maximum operating altitude
Nominal heat dissipation
Acoustic noise level
Input Data
ft. (m)
BTU/Hr
dBA
1,062
2,124
3,186
<62 @ 1 meter
4,248
Units
VAC
Nominal input voltage
208 or 240
Operating voltage range is variable based on output loading percentages
% UPS Load
80 – 100%
60 – 80%
30 – 60%
0 – 30%
Input Voltage
170 VAC
144 VAC
127 VAC
110 VAC
Minimum Voltage
Range (Typical)
Power factor
Cos Ø
Hz
>.98
60
Input frequency (nominal)
Input frequency range
Battery Module
Hz
40-70
Units
Number of lead acid batteries
Number of battery cells
Maximum charge current (full load)
Nominal Voltage
10
60
A
VDC
Hrs
3
120
Recharge Time
Typically 6 (to 90% capacity)
Output Data
Units
VAC
%
Output voltage
208/120 or 240/120
Voltage regulation
±3
Voltage stability (100% step load)
Recovery time
%
±7
96
msec
<3 THD, linear load
<7 THD, non-linear load
60
Voltage distortion
%
Output frequency
Hz
%
Efficiency at 100% load
89
110 - 125% for 10 min
126-150% for 10 sec
151 - 200% for 2 cycles
Output overload capability
%
6.1
Product Warranty Registration
To register for warranty protection:
• Visit the Quick Links section of our Web site at:
• Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:
US: 800-222-5877
Outside the US: 614-841-6755
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
38
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
POWER AVAILABILITY
Nfinity™ Power System
USER MANUAL
The Company Behind the Products
Technical Support/Service
Web Site
With over a million installations around the globe,
Liebert is the world leader in computer protection
systems. Since its founding in 1965, Liebert has
developed a complete range of support and
protection systems for sensitive electronics:
Monitoring
800-222-5877
Outside the US: 614-841-6755
•
•
•
Environmental systems—close-control air
conditioning from 1 to 60 tons
Single-Phase UPS
800-222-5877
Power conditioning and UPS with power
ranges from 300 VA to more than 1000 kVA
Integrated systems that provide both
environmental and power protection in a
single, flexible package
Monitoring and control—from systems of any
size or location, on-site or remote
Service and support through more than 100
service centers around the world and a 24/7
Customer Response Center
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
•
•
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
While every precaution has been taken to ensure
the accuracy and completeness of this literature,
Liebert Corporation assumes no responsibility and
disclaims all liability for damages resulting from
use of this information or for any errors or
omissions.
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Italy
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
+39 049 9719 111
© 2003 Liebert Corporation
All rights reserved throughout the world.
Specifications subject to change without notice.
® Liebert and the Liebert logo are registered
trademarks of Liebert Corporation. All names
referred to are trademarks or registered
trademarks of their respective owners.
Fax: +39 049 5841 257
Asia
23F, Allied Kajima Bldg.
138 Gloucester Road
Wanchai
Hong Kong
+852 2 572 2201
Fax: +852 2 831 0114
SL-23950 (6/03) Rev. 4
Download from Www.Somanuals.com. All Manuals Search And Download.
|