GENERAL INSTALLATION
LRT CABINET INSTALLATIONS
1. CAUTION: The LRT cabinet is heavy (see specifications). Take proper
precautions when lifting or moving it.
2. Remove the retaining straps and protective cardboard covering from the
shipping package.
3. Remove the 14mm (9/16”) hex bolts from the side of the shipping crate.
Retain one hex bolt and the side of the shipping crate.
4. Remove the four wood planks from each corner of the shipping crate.
Remove the top of the shipping crate from the LRT cabinet.
5. Place the side of the shipping crate at the bottom of the crate and insert one
hex bolt in the crate bottom. The LRT cabinet can now be rolled off of the
shipping crate.
6. Visually inspect the LRT cabinet for freight damage. Report damage to the
carrier and your dealer.
7. Locate the LRT cabinet indoors in a controlled environment, where it cannot
be accidentally disconnected. Locate it in an area with unrestricted air flow,
away from water, flammable liquids, gases, corrosives, or conductive
contaminants. Maintain a minimum of 4 inches (100 mm) clearance in front
and rear of the LRT cabinet. Battery cabinets are designed to be placed on
either side of, or beneath the UPS. Maintain an ambient temperature range of
32° to 104° F (0° to 40° C).
NOTE: LRT cabinet operation in temperatures above 77° F (25° C) reduces
battery life.
8. Plug the LRT cabinet into a dedicated wall receptacle properly protected by a
circuit breaker or fuse in accordance with the National and Local Codes. Use
a 15 amp rated device for 120VAC applications, or a 10 amp rated device for
230VAC applications. The wall receptacle must be grounded, and should be
wired so as to experience outages simultaneously with the connected
UPStation GXT™ UPS.
CAUTION: Do not use the UPS output receptacles as the LRT input power
source.
9. Connect the supplied cable to the battery cabinet then to the UPS. Turn on
the charger by pressing the On switch located on the rear panel. Turn on the
breaker on the rear of the battery cabinet. The LRT cabinet is ready for
normal operation. Up to three optional LRT cabinets may be connected to the
UPS to provide additional run time.
4
DISCONTINUED
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT
5
DISCONTINUED
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT
CONTROLS AND INDICATORS
On/Off Switch
This switch controls charger output. The switch is located on the rear of the unit
and must be in the "Up" position to enable the charger.
Circuit Breaker Switch
This breaker is located on the rear of the unit and must be closed to allow the LRT
Battery Cabinet to supply additional DC power to the UPS in the event of an
interruption in commercial power. The switch must be in the "On" position to close
the breaker.
Power Indicator (Green)
The Power indicator is located on the rear of the unit and is illuminated when the
LRT Battery Cabinet is receiving commercial power and the internal charger is
operating.
Summary Alarm (Red)
The Alarm indicator is located on the rear of the unit and is illuminated if the LRT
Battery Cabinet has detected a problem. In addition, one or more of the UPS
load/battery level indicators may be illuminated (refer to the UPS Troubleshooting
Guide).
MAINTENANCE
The LRT Battery Cabinet requires very little maintenance. The batteries are valve
regulated, nonspillable, lead acid, and should be kept charged to obtain their
designed life. Periodically, examine the vents on the front and rear of the cabinet,
and remove any obstructions from the surface of the vents.
When storing the LRT Battery Cabinet for any length of time, it is recommended to
recharge the LRT Battery Cabinet for at least 24 hours every four to six months to
increase battery life. In no case should the unit be stored in excess of nine months
without recharge.
6
DISCONTINUED
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT
LRTTM Battery Cabinet Specifications
Model Number
GXT96VLRT2UL
Compatible With
UPStation GXT:
1800RT-208, 2000RT-120, 2000RT-230, 2700RT-208,
3000RT-120 and 3000RT-230 VA UPS’
DIMENSIONS: in. (mm)
Unit W x D x H
WEIGHT: lbs (kg)
Unit
15 x 27 x 29 (381 x 686 x 737)
600 lbs (272kg)
INPUT AC PARAMETERS
Voltage Range
85 to 265VAC
Frequency
>40 to <70 Hz; auto sensing
>0.95
30% THD maximum
< 4A at 120VAC, < 2A at 230VAC
IEC320-C14 recessed plug, with input cords:
(1) 6’ cord with NEMA 5-15P
6.3 A
Input Power Factor
Current Reflected THD
Current Rating
Input Power Connection
Fuse Rating
OUTPUT DC PARAMETERS
Output Sockets
(2) per LRT cabinet
Interconnect Cable
Protection
(1) 9.8’ (3m) cable with appropriately keyed plugs
(1) resettable DC circuit breaker
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, lead acid
Quantity x Voltage x
Rating
8 x 12V x 65.0Ah
Approved Battery
Manufacturers:
Recharge Time
CSB, Panasonic, and Yuasa
<20 Hours to 95% capacity after full discharge into 100% load
ENVIRONMENTAL
Operating Temperature
+32° F to + 104° F (0° C to +40° C) for altitudes
0 to 5,000 ft (1,500m);
+32° F to + 95° F (0° C to +35° C) for altitudes
5,000 ft (1,500m) to 10,000 ft (3,000m)
+5° F to + 122° F (-15° C to +50° C)
0% to 95%, non-condensing
Storage Temperature
Relative Humidity
Audible Noise
AGENCY
< 45 dBA, at 1 meter
Safety
Surge
UL 1778; c-UL Listed; EN 50091-1; CE low voltage directive
IEEE 587 Category A; EN61000-4-5,
Level 3 (L-E), Level 2 (L-L)
ESD
EN6100-4-2, Level 3
Susceptibility
Electrical Fast
Transient/Burst
Immunity
EN6100-4-3, Level 2
EN6100-4-4, Level 3
EN50082-1
EMI/EMC
FCC Part15, Class A; EN50081-1; EN 55022, Class B;
CE EMC Directive
Additional information on this product can be located on our web site
7
DISCONTINUED
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT
LIMITED WARRANTY
Liebert Corporation extends the following LIMITED WARRANTY to the
purchaser and to its customer (collectively referred to as the "Purchaser"): the
enclosed Long Run Time Battery Cabinet (LRT) and components are free from
defects in materials and workmanship under normal use, service, and
maintenance FOR A PERIOD OF TWO YEARS FROM THE DATE OF
ORIGINAL PURCHASE from Liebert or the Liebert dealer or retailer. THE
FOREGOING WARRANTY IS THE ONLY WARRANTY GIVEN AND NO
OTHER WARANTY IS PROVIDED, EXPRESS OR IMPLIED, INCLUDING
WITHOUT LIMITATION, MERCHANTABILITY OR FITNESS FOR
A
PARTICULAR PURPOSE. Certain aspects of disclaimers are not applicable to
consumer products acquired by individuals and used for personal, family, or
household purposes (as distinguished from industrial or other purposes). Local
laws may not allow limitations on how long an implied warranty lasts, so the
above limitation may not apply to you. This warranty gives you specific legal
rights, and you may have other rights, which vary according to local law.
Certain repairs or services are the responsibility of the Purchaser and the
Purchaser is expected to pay for them. This warranty does not extend either to
products with removed or altered serial numbers or to any losses or damages
due to act of God or source external to the product, misuse, accident, abuse,
neglect, negligence, unauthorized modification, alteration, or repair, use beyond
rated capacity, or improper installation, maintenance, application or use,
including, without limitation, use in a manner contrary to the accompanying
instructions or applicable codes. WARNING: Warranty is void if the battery is
allowed to discharge below the minimum battery cutoff point. To prevent such
discharge DO NOT leave the unit power switch "ON" for more than two (2) days
without AC power being supplied to the LRT. The battery must be recharged
every four (4) to six (6) months when not in use.
If the LRT fails to conform with the above warranty within the two year warranty
period, Liebert will repair or replace the LRT, at Liebert's option. Repairs or
replacements are warranted for the remainder of the original warranty period.
Purchaser, to make a warranty claim, should call 1-800-222-5877 to obtain a
Returned Goods Authorization number and shipping instructions.
transportation costs to Liebert are the responsibility of the Purchaser.
"LIFE SUPPORT" POLICY
Return
This product is not recommended, and the Company will not knowingly sell this
product, for use with life support and other designated "critical" devices. ANY
SUCH USE BY A USER AUTOMATICALLY VOIDS AND DISCLAIMS ANY
AND ALL WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF
MERCHANTABILITY, IMPLIED WARRANTY OF FITNESS FOR
A
PARTICULAR PURPOSE, AND EXPRESS WARRANTIES THAT THIS
PRODUCT WILL CONFORM TO ANY AFFIRMATION OR PROMISE, FOR
THIS PRODUCT AND THE USER AGREES THAT IN NO EVENT SHALL THE
COMPANY BE LIABLE FOR CONSEQUENTIAL OR INDIRECT DAMAGES.
8
DISCONTINUED
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT
1050 Dearborn Drive Columbus, OH 43229 614-888-0246
UPStation GXT™
LRTTM Battery Cabinet
for use with the
1800-3000 VA
UPS Units
Technical Support
U.S.A.
1-800-222-5877
Outside the U.S.A.
614-841-6755
U.K.
France
Germany
Italy
Netherlands
+44 (0) 1793 553355
+33 (0) 1 4 87 51 52
+49 89 99 19 220
+39 2 98250 1
+31 (0) 475 503333
614-841-5471
E-mail
Web site
Worldwide FAX tech support
The Company Behind The Products
With more than 500,000 installations around the
globe, Liebert is the world leader in computer
protection systems. Since its founding in 1965,
While every precaution has been
taken to ensure accuracy and
completeness in this literature,
Liebert Corporation assumes no
responsibility, and disclaims all
liability for damages resulting from
use of this information or for any
errors or omissions.
Liebert has developed
a
complete range of
support and protection systems for sensitive
electronics:
•
•
•
Environmental systems: close-control air
conditioning from 1.5 to 60 tons.
Power conditioning and UPS with power
ranges from 250 VA to more than 1000 kVA.
Integrated systems that provide both
©1999 Liebert Corporation All
rights reserved throughout the
world. Specifications subject to
change without notice.
environmental and power protection in
a
single, flexible package.
•
•
Monitoring and control — on-site or remote
— from systems of any size or location.
Service and support, through more than 100
service centers around the world, and a 24-
hour Customer Response Center.
® Liebert and the Liebert logo are
registered trademarks of Liebert
Corporation. All names referred to
are trademarks or registered
trademarks of their respective
owners.
SL-23455 (5/99) Rev. 1