Liebert Power Supply GXT2 4500RT230 User Manual

POWER AVAILABILITY  
GXT2-6000RT230& GXT2-4500RT230™  
USER MANUAL  
230VAC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
8.5  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURES  
Figure 1  
TABLES  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS  
This Manual Contains Important Safety Instructions. Read all safety and operating instructions  
before operating the Uninterruptible Power Supply (UPS). Adhere to all warnings on the unit and in  
this manual. Follow all operating and user instructions. This equipment can be operated by individu-  
als without previous training.  
This product is designed for Commercial/Industrial use only. It is not intended for use with life sup-  
port and other designated “critical” devices. Maximum load must not exceed that shown on the UPS  
rating label. The UPS is designed for data processing equipment. If uncertain, consult your dealer.  
See Limited Warranty.  
This UPS is designed for use on a properly earthed (grounded), 220-240 VAC, 50Hz or 60Hz supply,  
for installation by qualified personnel. A qualified electrician must review and approve customer sup-  
plied wiring, circuit breakers, intended loads, and verify correct input, output and earth connections  
to ensure compliance with technical standards and local electrical codes of practice. Installation  
instructions and warning notices only for use by qualified personnel are located after the UPS opera-  
tor instructions in this manual.  
WARNING  
!
This UPS should not be supplied from electrical power systems of the “IT” (Impédance à  
Terre) type. (IEC 364-ELECTRICAL INSTALLATION OF BUILDINGS)  
ELECTROMAGNETIC COMPATIBILITY—This UPS complies with the requirements of the EMC  
Directive 89/336/EEC and the published technical standards. Continued compliance requires installa-  
tion in accordance with these instructions and the use of manufacturer approved accessories only.  
WARNING  
!
This is a product for restricted sales distribution to informed partners. Installation  
restrictions or additional measures may be needed to prevent radio interference.  
Operate the UPS in an indoor environment only in an ambient temperature range of 0-40°C  
(32-104°F). Install it in a clean environment, free from moisture, flammable liquids, gases and corro-  
sive substances.  
This UPS contains no user serviceable parts. The UPS ON/OFF push buttons do not electrically iso-  
late internal parts. Under no circumstances attempt to gain access internally, due to the risk of elec-  
tric shock or burn.  
Do not continue to use the UPS if the front panel indications are not in accordance with these operat-  
ing instructions, or the UPS performance alters in use. Refer all faults to your dealer.  
Only trained engineers authorized by Liebert should perform troubleshooting. To replace batteries,  
refer all servicing to qualified service personnel. Proper disposal of batteries is required. Refer to your  
local laws and regulations for disposal requirements.  
Never block or insert any object into the ventilation holes or other openings.  
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS,  
for example: electric drills, vacuum cleaners, laser printers, hairdryers or any appliance using half  
wave rectification.  
Storing magnetic media on top of the UPS may result in data loss or corruption.  
Turn the off UPS and isolate the UPS before cleaning. Use only a soft cloth, never liquid or aerosol  
cleaners.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
GLOSSARY OF SYMBOLS  
Risk of electrical shock  
Indicates caution followed by important instructions  
!
AC input  
AC output  
Requests the user to consult the manual  
Indicates the unit contains a valve-regulated lead acid battery  
Recycle  
i
+
-
PbH2SO4  
R
DC voltage  
Equipment grounding conductor  
Bonded to ground  
AC voltage  
ON/Alarm Silence/Battery Test  
OFF/Bypass  
Indicates the position of a fuse  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Introduction  
1.0 INTRODUCTION  
Congratulations on your choice of the Liebert UPStation GXT2-6000RT230 and GXT2-4500RT230  
Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other  
sensitive electronic equipment.  
Upon generation, AC power is clean and stable. However, during transmission and distribution it  
may be subject to voltage sags, spikes, or complete power failure that may interrupt computer opera-  
tions, cause data loss, or even damage equipment. The UPStation GXT2 protects equipment from  
these disturbances.  
The UPStation GXT2 comes in nominal power ratings of 4500 VA and 6000 VA. Complete model spec-  
ifications appear at the end of this manual.  
The UPStation GXT2 is a compact, on-line UPS. An on-line UPS continuously conditions and regu-  
lates its output voltage, whether mains power is present or not. It supplies connected equipment with  
clean sinewave power. Sensitive electronic equipment operates best from sinewave power.  
For ease of use, the UPStation GXT2 features a light-emitting diode (LED) display to indicate both  
load percentage and battery capacity. It also provides self-diagnostic tests, a combination ON/Alarm  
Silence/Manual Battery Test button, a Standby button, user configurable program, and two levels of  
alarms when the unit is operating on battery.  
The UPStation GXT2 has an interface port for communication between the UPS and a network server  
or other computer systems. This port provides detailed operating information including voltages, cur-  
rents, and alarm status to the host system when used in conjunction with Liebert MultiLink™ soft-  
ware. MultiLink software can also remotely control UPS operation.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System Description  
2.0 SYSTEM DESCRIPTION  
Input  
Output  
Dynamic  
Bypass  
L1  
L1  
N
Rectifier  
/PFC  
DC-to-DC  
TVSS &  
EMI/RFI  
Filters  
Inverter  
Converter  
N
Battery  
Charger  
Battery  
G
G
2.1  
2.2  
Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters  
These UPS components provide surge protection and filter both electromagnetic interference (EMI)  
and radio frequency interference (RFI). They minimize any surges or interference present in the  
mains line and keep the sensitive equipment protected.  
Rectifier/Power Factor Correction (PFC) Circuit  
In normal operation, the rectifier/power factor correction (PFC) circuit converts mains AC power to  
regulated DC power for use by the inverter while ensuring that the waveshape of the input current  
used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives:  
• The mains power is used as efficiently as possible by the UPS.  
• The amount of distortion reflected on the mains is reduced.  
This results in cleaner power being available to other devices in the building not being protected by  
the UPStation GXT2.  
2.3  
2.4  
Inverter  
In normal operation, the inverter utilizes the DC output of the power factor correction circuit and  
inverts it into precise, regulated sinewave AC power. Upon a mains power failure, the inverter  
receives its required energy from the battery through the DC to DC converter. In both modes of oper-  
ation, the UPS inverter is on-line and continuously generating clean, precise, Regulated Ac Output  
Power.  
Battery Charger  
The battery charger utilizes energy from the mains power and precisely regulates it to continuously  
float charge the batteries. The batteries are being charged whenever the UPStation GXT2 is con-  
nected to mains power.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
System Description  
2.5  
2.6  
DC-to-DC Converter  
The DC to DC converter utilizes energy from the battery system and raises the DC voltage to the opti-  
mum operating voltage for the inverter. This allows the inverter to operate continuously at its opti-  
mum efficiency and voltage, thus increasing reliability.  
Battery  
The UPStation GXT2 utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery  
design life, operate the UPS  
in an ambient temperature of 20°C to 25°C (68°F to 77°F). Optional external battery cabinets are  
available to extend battery run times.  
2.7  
Dynamic Bypass  
The UPStation GXT2 provides an alternate path for mains power to the connected load in the  
unlikely event of a UPS malfunction. Should the UPS have an overload, overtemperature, or UPS  
failure condition, the UPS automatically transfers the connected load to bypass. Bypass operation is  
indicated by an audible alarm and illuminated amber Bypass LED (other LEDs may be illuminated to  
indicate the diagnosed problem). To manually transfer the connected load from the inverter to bypass,  
press the Standby button once.  
NOTE  
The bypass power path does NOT protect the connected equipment from disturbances  
in the mains supply.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Major Components  
3.0 MAJOR COMPONENTS  
The GXT2 is composed of three major assemblies to provide easier handling, installation, and versa-  
tility.  
3.1  
Main Frame and Electronics  
This 5U cabinet is shipped with internal batteries installed and a basic, hardwire distribution box  
attached and ready to install.  
Figure 1 GXT2, front view  
Top Trim  
(2 pieces;  
tower use  
only)  
Lower Bezel &  
Battery Access  
Door  
Status  
Indicators  
& Controls  
Upper  
Bezel  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Major Components  
Figure 2 GXT2, rear view  
Battery  
Disconnect  
External Battery  
Connector  
Fans  
UPS Output  
Circuit Breaker  
DB-9  
Communication  
Port  
REPO Connector  
Relay Card Slot  
Removable Power  
Distribution Box  
Serial Card Slot  
(SNMP, OCWEB, USB)  
3.2  
Internal Battery Packs  
The UPS has two internal battery packs behind a battery access door on the front of the unit. Each  
pack is fitted with a connector to link to the UPS.  
Figure 3 Internal battery pack with connector  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Major Components  
3.3  
Removable Power Distribution Box  
The UPS arrives with a basic hardwire power distribution pack installed. This box always contains  
the UPS input circuit breaker.  
Optional versions may be available to replace the standard box for custom installations.  
Figure 4 Power distribution boxes, basic, optional  
Basic Hardwire Power Distribution Box  
PD-CEHDWR  
Optional Hardwire Power Distribution  
Box with Maintenance Bypass Switch  
PD-CEHDWRBYP  
NOTE  
Hardwire and hardwire/receptacle boxes that include a manual bypass switch allow  
AC power to continue to flow from the mains input to the load while the box is removed  
from the UPS. For details, refer to 11.2 - AC Power Connections.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
What’s Included  
4.0 WHATS INCLUDED  
The GXT2 are shipped with the following items:  
• GXT2-6000RT230 and GXT2-4500RT230 user manual  
• Vertical display overlay  
• Top bezels - 2  
• MultiLink software CD  
• MultiLink serial cable, 10 ft (3m)  
• Rack mount handles  
• Support base - 2  
• Mounting hardware  
• Configuration program disk  
• DB9 port cover  
Top bezels  
(tower use)  
MultiLink  
software CD  
MultiLink  
serial cable  
10 ft (3m)  
Vertical  
display  
overlay  
Rack mount  
handles  
GXT2™ Configuration  
Program  
For use with LiebertGXT2U model UPS  
systems  
Version 1.6  
For Windows 95/98/NT  
To Install:  
Choose the Start button on the Taskbar  
and select Run  
Mounting hardware  
Configuration  
disk  
Support base  
with spacers  
DB9 port cover  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation and Configuration  
5.0 INSTALLATION AND CONFIGURATION  
Do NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until  
Visually inspect the UPS for freight damage. Report any damage to the carrier and your local dealer  
or Liebert representative.  
CAUTION  
!
The UPS is heavy (see 13.0 - Specifications). Take proper precautions  
when lifting or moving it.  
Install the GXT2 indoors in a controlled environment, where it cannot be accidentally turned off.  
Place it where air flows unrestricted around the unit. The installation location must be free of water,  
flammable liquids, gases, corrosives and conductive contaminants. Maintain a minimum clearance of  
100mm (4 inches) in the front and rear of the UPS. Maintain an ambient temperature range of 0 to  
40°C (32 -104°F).  
NOTE  
UPS operation in sustained temperatures above 25°C (77°F) reduces battery life.  
This device is intended for use in an Installation Category II environment.  
5.1  
Install the Main Cabinet  
The GXT2 may be installed in either a tower configuration or in a rack, depending on available space  
and use considerations. Determine the type of installation and follow the appropriate instructions in  
5.1.1 Tower UPS Installation  
When using the GXT2 in a tower configuration, use the included support base (shown below, left) to  
stabilize the UPS. If any external battery cabinets are added, they will include spacers to accommo-  
date the additional cabinets (shown below, right).  
Figure 5 Tower-use support bases, spacers for external battery cabinets  
3U  
3U  
2U  
2U  
5U support base for GXT2  
End bases and 3U spacer  
Spacers added to support base  
to accommodate additional battery cabinets  
5.1.2 Rack-Mount UPS Installation  
When using the GXT2 in a rack-mount configuration, the UPS must be supported by a slide kit, fixed  
rails or a shelf.  
When using the optional Adjustable Rack Mount Kit, you will use the following instructions. The fig-  
the positioning of the rack-mounting brackets. Liebert recommends taking the internal batteries out  
of the UPS during rack installation. This will make the UPS cabinet lighter and easier to handle.  
CAUTION  
!
Only three (3) M4 screws are used on the side of the GXT2 where the Power Distribution Box  
is located. The fourth mounting hole is above the Power Distribution Box and is not used.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Installation and Configuration  
5.1.3 Installing the Adjustable Rack-Mount Kit—Sold Separately  
This kit contains parts needed to mount several different models of UPS and external battery cabi-  
nets into EIA310-D standard four-post racks that are 18-32" deep (457-813mm). The weight limit per  
pair of adjustable rack-mounting brackets is 91 kg (200lbs.).  
Parts included are:  
Item  
Quantity  
Rear bracket members  
Front bracket members  
Inner bracket members  
M4 x 8mm machine screws  
M4 locking hex nuts  
2
2
2
16  
8
M5 x 16 mm machine screws  
Grease packet.  
12  
1
Tools needed for installation are:  
• one Phillips screwdriver  
• one 7mm wrench  
The adjustable rack-mounting brackets (Part#: RMKIT18-32) feature retaining latches to prevent  
users from inadvertently sliding the UPS or battery cabinet out of the rack.  
To install the rack mount brackets:  
Return  
flanges  
1. Unpack two (2) rack-mounting bracket assemblies and  
mounting hardware from this kit. Bracket assemblies are  
interchangeable between left-hand or right-hand.  
Retaining  
Latches  
Remove inner member of each bracket assembly as shown  
at right by extending it to its outermost position, depress-  
ing the retaining latch and then pulling the inner member  
out of the bracket assembly.  
2. Determine the height position inside the rack enclosure  
where you want to mount the UPS or battery cabinet.  
Front  
members  
Inner  
members  
CAUTION  
!
Reduce the risk of tipping the rack enclosure by  
placing the UPS or battery cabinet in the lowest  
possible rack position.  
3. Install the rear member of each bracket assembly into the  
rack enclosure with two (2) M5 screws provided in this kit  
(see figure at right). The return flanges on the bracket  
assembly fit to the inside of rack mounting rails. Insert  
screws loosely (finger-tight) into the top and bottom holes of  
the return flange on the rear member. Extend the bracket  
assembly by sliding the front member forward until it  
touches the front rack mounting rail. Insert two (2) M5  
screws loosely (finger-tight) into the top and bottom holes of  
the return flange on each front member. Make sure that the  
bracket assemblies are at the same mounting height on all  
four (4) rack mounting rails.  
M5 screws  
Front rack  
mounting rails  
Rear rack  
mounting  
rails  
M5 screws  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation and Configuration  
4. Get eight (8) M4 screws and eight (8) M4 nuts from the  
hardware pack in this kit. Each nut has a locking, nylon  
insert that begins gripping the screw when it is halfway  
tight. Make sure to tighten the nut and screw completely to  
ensure locking action. Fasten the rear member and the front  
member together using (4) screws and (4) nuts per bracket  
assembly as shown in at right. For maximum support, insert  
fasteners for each bracket assembly as far apart as possible,  
depending on rack depth, while still joining both members  
(see figures at right). Check alignment of bracket assemblies  
and TIGHTEN ALL SCREWS FROM Steps 2 and 3.  
5. Prepare the UPS or battery cabinet (the “equipment”) for  
rack mounting by following instructions in the equipment’s  
user manual. The equipment may require additional parts to  
be added or parts to be removed for rack mounting. After it is  
prepared, lay the equipment in rack-mounting position.  
Fasten the inner members from Step 1 to the equipment on  
both sides as shown at right with eight (8) M4 screws  
provided in the kit. Make sure retaining latch is near the rear  
of the equipment as shown (see figure at right).  
M4 nuts  
M4  
screws  
457mm  
(18")  
rack  
M4 nuts  
M4  
depth  
M4 nuts  
screws  
813mm  
(32") rack  
depth  
M4 nuts  
Retaining latch  
6. Open the grease packet provided in the kit. Apply a bead of  
grease 25mm (1") long at four (4) places inside the bottom,  
curved tracks of the front members as shown below right. The  
grease will allow the equipment to slide into the bracket  
assemblies more easily.  
M4 screws  
UPS or battery  
cabinet  
CAUTION  
!
Lifting equipment into the rack may be a two-person  
6.  
job, depending on the weight of the equipment.  
Liebert recommends taking the internal batteries  
out of the UPS during rack installation. This will  
make the UPS cabinet lighter and easier to handle.  
The GXT2 weighs 67kg (151lb). For the battery  
cabinet’s weight, see the unit’s user manual.  
Front  
M4 screws  
Apply  
grease  
7. Insert the equipment, with inner members attached in  
Step 5, into the bracket assemblies by inserting the top and  
bottom edges of the inner members into the top and bottom  
curved tracks of the front members and sliding the  
UPS or  
battery  
cabinet  
equipment into the rack (see figure at right). Ends of inner  
members are tapered to allow the rear of the equipment to be  
angled upward before insertion, if space allows.  
Apply  
Then the rear, bottom edges of the inner members can be  
placed into the front edge of the bottom tracks and the front  
of the equipment can be tipped up so they are level to insert  
the top edges of the inner members before sliding the equip-  
ment into the rack (see figure below right). The equipment  
should move smoothly into the bracket assemblies. If it does  
not, recheck the alignment of the front and rear members  
from Steps 2 and 3.  
grease  
(inside)  
... and push it  
into the rack.  
8. Secure the front of the equipment to the rack mounting rails  
to prevent the equipment from sliding out of position. If  
securing holes are provided on the front of the equipment  
that align with the center holes on the return flange of the  
front members, you can use the four (4) extra M5 screws  
provided in the kit to secure the equipment. Otherwise, the  
equipment should be secured to the front of the rack with  
four (4) customer-supplied fasteners.  
Insert the UPS into the front  
members, lift the front ...  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and Configuration  
5.2  
External Battery Cabinet Installation  
Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery  
run time. External battery cabinets are designed to be placed on one side of the UPS or stacked  
beneath the UPS.  
CAUTION  
!
The external battery cabinet(s) are heavy (see 13.0 - Specifications). External battery  
cabinets can be used in rack-mount or tower configuration. Take proper precautions when  
lifting them.  
1. Visually inspect the external battery cabinet for freight damage. Report damage to the carrier  
and your local dealer or Liebert representative.  
2. For slide rail installations, first remove the top/side fin. Top/side fin slides forward and then lift  
up to remove. Optional rack-mount handles are shipped with the external battery cabinet and  
may be installed at this time if desired.  
3. Securing hardware and slide rails are sold separately. Please contact your local dealer or Liebert  
representative for these additional options and any assistance needed. Fasten the slides into  
position with the screws per the instructions included with the slide rails.  
4. Use the enclosed support bases for the tower option to prevent tip-over. One additional set of  
support base extensions ships with each external battery cabinet.  
5. Connect the supplied external battery cabinet cable to the rear of the external battery cabinet,  
then to the rear of the UPS.  
6. The UPS is now equipped with additional backup battery run time. For approximate battery run  
times, refer to Table 6.  
NOTE  
You must use the included configuration program to program the UPS for the number  
of external battery cabinets connected. Instructions for the configuration program are in  
3U  
2U  
2U  
Spacers added to support  
base to accommodate  
additional battery cabinets  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation and Configuration  
5.3  
Connect the Internal Batteries Using the External Connector  
The internal connectors of the internal battery packs will be connected when shipped. However, the  
internal batteries will be disconnected from the UPS using a rear panel connector. The connector  
attaches to the UPS in both the open and closed position using two screws. The picture on the left  
shows the connector in the open position, as shipped.  
When the UPS is installed, remove the two screws to release the connector. Plug the connector into  
the socket. The internal batteries are now connected to the UPS electronics. Install the two screws to  
secure the connector in the closed position.  
Remove these screws  
to release connector  
5.3.1 Storage  
If the UPS is to be shipped or stored for an extended time, the connector should be removed and  
attached in the open position, as shown above. This will minimize any standby current drain on the  
batteries.  
5.4  
Connect Input/Output Power  
The UPS should arrive with the basic hardwire  
box attached. If the box needs to be exchanged for  
an optional model, remove and install the desired  
box using the three captive screws marked in the  
illustration at right.  
Unscrew  
these  
captive  
screws  
To remove:  
Loosen the screws about 20 turns until the box  
can be pulled away from the UPS.  
To install:  
Align the connectors on the box and UPS. Push  
the box into place. While holding the box firmly  
against the UPS, tighten the three captive screws  
until the box is secure. Do not over tighten.  
5.4.1 Distribution Box Electrical Connections  
Electrical connections are made through a remov-  
able power distribution box that attaches to the rear of the UPS.  
The installer must provide a 32A branch circuit breaker. The Input circuit breaker on the distribution  
box and the Output circuit breaker on the rear fixed-panel of the UPS disconnect all power between  
the main cabinet and the distribution box.  
Models equipped with a manual bypass switch pass bypass power directly to the bypass switch from  
the input terminal block. The input circuit breaker on the distribution box does not disconnect power  
from the manual bypass switch.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Installation and Configuration  
Figure 6 Distribution box electrical connections diagram  
PD-CEHDWR  
PD-CEHDWRBYP  
Input  
Mains  
Mains  
32A  
Input  
Byp.  
Input  
CB  
Input  
CB  
Output  
32A  
Output  
External  
Branch  
CB  
External  
Branch  
CB  
Inv.  
30  
30  
UPS  
Output  
UPS  
Output  
CB  
CB  
30  
30  
UPS - PFC, Battery, Inverter  
UPS - PFC, Battery, Inverter  
PD-CEHDWR and PD-CEHDWRBYP Terminal Block Connections  
Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not  
share the same conduit.  
Table 1  
Electrical specifications  
Input  
Current  
Rating  
Recommended  
(Maximum) External  
Overcurrent Protection  
Recommended Wire  
(Including ground wire)  
(758C copper wire)  
Maximum Wire  
Accepted by  
Terminal Block  
Terminal  
Tightening  
Torque  
2
2
24A  
32A  
6-10mm (8-10AWG)  
10mm (8AWG)  
2.26 Nm (20 in-lb)  
N L N L  
32Amp Max Branch  
INPUT Overcurrent Protection  
OUTPUT  
6-10mm2 - Use Copper Wire Only  
N L N L  
OUTPUT TO LOAD  
INPUT TO UPS  
NOTE  
1. Note1 The installer must provide circuit breaker protection according to local codes. The  
mains disconnect should be within sight of the UPS or have appropriate an appropriate  
lock-out. Maintain service space around the UPS or use flexible conduit.  
2. Note 2 The installer must provide output distribution panels, circuit breaker protection, or  
emergency disconnects according to local codes. Output circuits must not share a common  
conduit with any other wiring.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Initial Start-Up and Electrical Checks  
6.0 INITIAL START-UP AND ELECTRICAL CHECKS  
1. Verify that the Input Output circuit breakers are off.  
2. During initial system checks, disconnect all loads (open load disconnects).  
3. Inspect all wiring, cables, and connection.  
4. If external battery cabinets are used, verify that the battery interconnect cables are fully inserted  
in the sockets.  
5. If you are using a distribution box that includes a Manual Bypass Switch, place the switch in  
BYPASS position.  
6. Turn on the branch circuit disconnect to apply voltage to the input terminal block.  
7. Using a voltmeter, verify the expected L1-N voltage.  
If no Manual Bypass Switch is used, there will be no output voltage at this time. If a Manual  
Bypass Switch is used, verify that the same voltages appear at the Output terminals. If a Manual  
Bypass Switch is used, the Bypass lamp will light by the switch. If no manual bypass switch is  
used, there will be no output voltage at this time.  
8. After verifying proper input voltage to the UPS terminal block, turn off the branch circuit power,  
close all access panels to the distribution box, and reapply input power.  
9. Close the Input circuit breaker located on the distribution box. The green AC INPUT lamp should  
illuminate on the front panel.  
10. Press the ON button for 1 second. The BYPASS lamp will light for several seconds before the UPS  
ON lamp turn on continuously. If the batteries are determined to charged above 80%, an  
automatic battery test will run for about 15 seconds.  
11. Close the Output circuit breaker on the rear of the UPS. If a Manual Bypass Switch is used, the  
Inverter lamp by the switch will light. If a Manual Bypass Switch is used, transfer the switch to  
the Inverter position. The output terminal block will be powered at this time.  
12. Perform a Manual Battery Test - Press the ON button for 1 second. The front BATTERY lamp will  
light for about 15 seconds and then return to only the UPS ON and AC INPUT lamps being on.  
13. Review all setting option provided by the configuration program. Some changes require that the  
UPS be OFF. If this is the case, these should be programmed before powering the loads. The  
configuration program is described in the next section.  
14. Connect all loads for normal operation.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Configuration Program  
7.0 CONFIGURATION PROGRAM  
The final step of installation may require custom configuration of your UPS using the enclosed config-  
uration program. Some configuration settings may be changed only while the UPS is off. These should  
be set before the UPS is put into full-time service powering the critical load.  
For most users operating with 230VAC and with no external batteries, the factory default settings  
will be adequate.  
7.1  
GXT2-6000RT230 and GXT2-4500RT230 Configuration Program Features  
• Select one of three L-N output voltages to match local voltages.  
• Enable/Disable Auto-Restart.  
• Select frequency converter operation with a fixed output frequency of 50 or 60 Hz.  
• Set the Low Battery Warning alarm time from 2 to 30 minutes.  
• Enable/Disable the Auto-Battery test.  
• Set the Auto-Battery test to 7, 14, 21, or 28 days.  
• Specify the number of external battery cabinets connected to the UPS to adjust the remaining run  
time calculations reported by Liebert software products.  
• Modify the shutdown setting of DB-9 pin 6 (for information on pin assignments, see Table 2).  
7.1.1 What You Will Need  
In addition to the GXT2 UPS, you will need the configuration program diskette and serial cable (beige  
or tan, 3-wire: GND, TX, RX; straight through 2-2, 3-3, 5-5) included in the UPS accessory box. A Win-  
dows 95® or later computer, desktop or laptop, is also required to set up and run the configuration  
program.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Controls and Indicators  
8.0 CONTROLS AND INDICATORS  
All indicators illuminated  
for illustration only.  
UPStation GXT  
AC INPUT  
BATTERY  
UPS ON  
BYPASS  
8.1  
ON/Alarm Silence/Manual Battery Test Button  
This button controls output power to connected load(s) and has three functions:  
• ON  
• Alarm Silence  
• Manual Battery Test  
ON - Pressing this button will start up the UPS in order to provide conditioned and  
protected power.  
Alarm Silence - To silence alarms, press this button for at least one Second. After the  
alarm is silenced, the UPStation GXT2 will reactivate the alarm system to alert of  
additional problems.  
NOTE  
The LOW BATTERY and BYPASS reminder alarms CANNOT be silenced.  
Manual Battery Test - To initiate a manual battery test, press the ON button for at least one second  
while operating from mains power with no alarm conditions present.  
• If only three of the five Battery LEDs illuminate, allow the UPS to recharge the batteries for 24  
hours.  
• After 24 hours, retest the batteries.  
• After the batteries have been retested, if only three of the five Battery LEDs illuminate, contact  
your local dealer, Liebert representative or Liebert Worldwide Support Group.  
8.2  
Standby/Manual Bypass Button  
This button controls output power to connected load(s) and has dual functions:  
Standby and Manual Bypass.  
CAUTION  
!
Pressing the Standby/Manual Bypass button once will transfer the  
load to bypass power. Pressing the Standby/Manual Bypass button a  
second time within 4 seconds will cut off power to the output sockets  
and connected loads. Perform all necessary shutdown procedures on  
connected loads before pressing this button twice.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Controls and Indicators  
8.3  
8.4  
Load Level Indicators (4 Green, 1 Amber)  
The load level indicators display the approximate electrical load placed upon the UPS at all times.  
Battery Level Indicators (5 Green)  
The battery level indicators display approximate battery capacity at all times.  
The UPStation GXT2 is equipped with automatic and remote battery test features. The automatic  
test occurs every 14 days (this option is user configurable) if mains has not been interrupted. Should  
the battery fail this test, the red Fault indicator LED along with the A and C diagnostic LEDs will  
illuminate and an alarm will sound (refer to 12.0 - Troubleshooting). The remote test feature func-  
tions with MultiLink 3.x software and can remotely initiate the battery test.  
8.5  
8.6  
8.7  
Fault Indicator LED (Red)  
The Fault indicator LED is illuminated if the UPS has detected a problem. Also, one or more of the  
battery level indicators may be illuminated (refer to 12.0 - Troubleshooting).  
Bypass Indicator LED (Amber)  
The Bypass indicator LED is illuminated when the UPS is operating from bypass power. An alarm  
will sound indicating the UPS detected a problem, or the manual bypass function has been activated.  
UPS ON Indicator LED (Green)  
The UPS ON indicator LED is illuminated when the UPS inverter is operating and supplying power  
to the connected loads.  
8.8  
8.9  
Battery Indicator LED (Amber)  
The Battery indicator LED is illuminated when the UPS is operating on battery.  
AC Input Indicator LED (Green)  
The AC Input indicator LED is illuminated when mains power is available and within the input spec-  
ifications.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
Operating Instructions  
9.0 OPERATING INSTRUCTIONS  
9.1  
Normal Mode Operation  
During normal operation, mains power provides energy to the  
UPS. The filters, power factor correction circuit and the inverter  
process this power to provide computer grade power to connected  
loads. The UPS maintains the batteries in a fully charged state.  
The four green load level LEDs indicate an approximate level of  
load in 25% increments. If the UPS becomes loaded beyond full  
rating, the fifth (amber) LED indicator will illuminate and the  
UPS will sound an audible alarm. The display template indicates  
the percentage of load (10% of load shown in example) on the UPS  
output.  
AC INPUT BATTERY UPS ON BYPAS S  
Normal Mode Operation  
Batteries at 100% Charge  
Load at 10%  
9.2  
Battery Mode Operation  
Battery mode occurs in event of an extreme input voltage condition  
or complete mains failure. The battery system supplies power  
through the DC to DC converter to the inverter to generate power  
for the connected load. During battery mode an alarm sounds  
every 10 seconds. This will change to two beeps every 5 seconds  
when the battery runs low (approximately 2 minutes remaining,  
but this is user configurable). The AC Input LED will extinguish,  
and the Battery LED will illuminate to warn that a mains problem  
has occurred. Each battery level indicator represents a 20% capac-  
ity level. As capacity decreases, fewer indicators remain illumi-  
nated. Refer to 12.0 - Troubleshooting. For approximate battery  
Battery Mode Operation  
Batteries at 30% Charge  
Load at 50%  
run times, refer to Table 6. These times are approximate, based on resistive load and an ambient  
temperature of 25°C (77°F). To increase this time, turn off non-essential pieces of equipment (such as  
idle computers and monitors) or add the optional external battery cabinet.  
CAUTION  
!
Turning OFF the UPS while in it is battery mode will cut off output power.  
9.3  
Bypass Mode Operation  
Bypass mode occurs when the OFF button is pressed once while  
the UPS is in Normal Mode. During bypass operation, mains  
power provides energy to the UPS. The mains power bypasses the  
inverter and provides power for the connected load.  
AC INPUT BAT  
UPS ON BYPAS S  
The four green load level LEDs indicate an approximate level of  
load in 25% increments. If the UPS becomes loaded beyond full  
rating, the fifth (amber) LED indicator will illuminate and the  
UPS will sound an audible alarm. The display template indicates  
the percentage of load (26-50% of load shown in the example above) on the UPS output.  
9.4  
Battery Recharge Mode  
Once mains power is restored, the UPS resumes normal operation. At this time, the Battery Charger  
begins recharging.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Communications  
10.0 COMMUNICATIONS  
10.1 Communications Interface Port  
The UPStation GXT2 UPS has a standard DB-9 serial port female connector located on the rear of the  
UPS unit. Several signals are provided on this port and are assigned as follows:  
Table 2  
DB-9 pin assignment  
DB-9 Assignment Description  
Pin  
1
2
3
4
5
6
7
8
9
Low Battery (open collector)  
UPS TxD (typically RS-232 levels)  
UPS RxD (typically RS-232 levels)  
Remote Shutdown (5-12VDC, 10-24mA max; battery operation)  
Common  
Remote Shutdown (short to pin 5); all modes of operation  
Low Battery (open emitter)  
Mains Fail (open emitter)  
Mains Fail (open collector)  
Pin Assignment  
Collector to Emitter*  
Open  
Collector  
6
7
8
9
(+)  
(-)  
330 Ohms  
Open  
Emitter  
1
2
3
4
5
* Maximum voltage and current on pins 1, 7, 7 and 9 are 60VDC and 10.0 mA  
10.2 Pin 4 - Remote Shutdown on Battery  
1. 1. This pin is functional only when the UPS is in battery mode. If the UPS is being powered by the  
mains, Pin 4 will ignore any signal on this pin.  
2. 2. Pin 4 requires a 5-12 VDC signal to shutdown. This normally comes form the serial port using  
Liebert's contact closure cable. It cannot be used with just a contact closure unless the relay is  
used to switch a voltage source. A 5-12 VDC signal for 1.5 seconds or greater is required to signal  
a shutdown. Signals for less than 1.5 seconds will be ignored. After Pin 4 receives a shutdown  
signal for 1.5 seconds, the command cannot be canceled.  
3. 3. A battery shutdown signal on Pin 4 will NOT cause an immediate Shutdown. A shutdown  
signal will start a 2-minute shutdown timer. The timer cannot be stopped. After 2 minutes, the  
UPS will shut down.  
4. 4. If the mains returns during the 2-minute timer countdown, the shutdown timer will continue  
until the end of 2 minutes and the UPS will turn OFF. The UPS must remain OFF for at least  
10 seconds even if AC input power Returns before the UPS turns OFF. This serves to reset and  
restart the server.  
Whether the UPS turns back ON when power is restored depends on the auto-restart setting: enabled  
or disabled.  
If the auto-restart is disabled, the UPS will not restart after performing the 2-minute shutdown  
delay.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Communications  
10.3 UPS Intelligent Communications  
The UPStation GXT2 is equipped with two Intellislot® ports to provide advanced communication and  
monitoring options.  
The Intellislot port closer to the corner of the UPS chassis is the serial card slot. This Intellislot port is  
used for the OCWEBCARD and the USBCARD. The other Intellislot port is used for  
RELAYCARD-INT or the MULTIPORT Card.  
Liebert’s OCWEBCARD  
DB9 (RS232) port  
covered  
NOTE  
The OCWEBCARD DB9 serial port cable should be used only for the initial card setup. Remove  
the cable after setup is complete.  
When the DB9 OCWEBCARD serial port cable is removed, the OCWEBCARD DB9 connector  
needs to be covered. The DB9 cover is included with the UPS.  
Liebert's MultiLink software continually monitors the UPS and can shut down your computer or  
server in the event of an extended power failure.  
MultiLink can also be configured for use without the serial cable when the Intellislot SNMP/Web card  
is installed in the UPS. Additionally, MultiLink can be configured to coordinate shutdown across the  
network with other computers running MultiLink when you purchase a MultiLink License Kit. For  
more information about the Intellislot SNMP/Web Card and MultiLink license Kits, visit our Web site  
Several option cards are available for use in the Intellislot port of the UPStation GXT2. The Intellislot  
SNMP/Web Card provides SNMP and Web-based monitoring and control of the UPS across the net-  
work.  
The Intellislot MultiPort 4 Card allows you to install MultiLink software on four computers and coor-  
dinate shutdown in the event of a power failure.  
The Intellislot Relay Card provides dry contact relay outputs for custom wired applications and deliv-  
ers support for built-in shutdown for AS/400 systems.  
CAUTION  
!
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables  
should be segregated and run separate from all other power cables, where applicable.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Communications  
10.4 Remote Emergency Power Off  
The UPS is equipped with a Remote Emergency Power Off (REPO) connector.  
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS  
input feeder breaker to remove all sources of power to the UPS and connected equipment to comply  
with national and local wiring codes and regulations.  
REPO switch connection diagram  
UPS ships with REPO jumper  
installed allowing the UPS  
to operate  
Opening the REPO connection will disable the UPS.  
Manual restart using the front panel is required after  
the REPO connection is closed again.  
1
2
1
2
Normally closed switch system  
(fail-safe)  
CAUTION  
!
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should  
be segregated and run separately from power cables.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Maintenance  
11.0 MAINTENANCE  
11.1 Internal Battery  
The UPStation GXT2 requires very little maintenance. The batteries are valve-regulated, non-spill-  
able, flame retardant, lead acid, and should be kept charged to obtain their designed life. The UPS  
continuously charges the batteries when connected to the mains supply.  
When storing the UPS for any length of time, it is essential to plug the UPS in for at least 24 hours  
every four to six months to ensure full recharge of the batteries. Failure to recharge the batteries peri-  
odically will result in permanent degradation of battery capacity.  
!
UPStation GXT  
-
+
AC INPUT BATTERY UPS ON  
BYPASS  
The UPStation GXT2 is designed to allow the user to safely replace the internal batteries. Read the  
safety cautions before proceeding. Contact your local dealer or Liebert representative to obtain the  
appropriate replacement battery kit part number and pricing.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Maintenance  
11.1.1 Internal Battery Replacement  
CAUTION  
!
A battery can present a risk of electrical shock and high short circuit current. Observe the  
following precautions before replacing the batteries:  
• Remove rings, watches and other metal objects.  
• Use a Phillips (cross-head) screwdriver with insulated grips.  
• Do not lay tools or other metal objects on top of the batteries.  
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact  
your local dealer or Liebert representative immediately.  
• Do not dispose of batteries in a fire. The batteries may explode.  
• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It is  
toxic.  
1. Remove the 3U battery access panel on the front of  
Battery Door Captive Screws  
the UPS by loosening the two captive screws  
located between the bezels (see illustration at  
right).  
!
UPStation GXT  
AC OUTPUT  
BATTERY  
UPS ON  
BYPASS  
2. Once the captive screws are loosened, tip the panel  
forward and lift to remove it from the main  
cabinet.  
3. Use a Phillips (cross-head) screwdriver to remove  
the screw in the battery retaining bracket on each  
battery pack (see illustration at right). Remove the  
retaining brackets.  
4. Disconnect the battery connectors in the front of  
each battery pack.  
5. Lift the internal connector out of the way and slide  
the battery out of the UPS. Support the weight of  
the battery to prevent it from falling.  
3U Battery Access Door and  
Battery Bezel  
Retaining bracket  
Retaining screw  
6. Unpack the new battery assembly, taking care not  
to destroy the packing. Compare new and old  
battery assemblies to make sure they are the  
same. If so, proceed with Step 7; otherwise STOP  
and contact your local dealer, Liebert  
representative or the Liebert Worldwide Support  
Group.  
7. Line up and slide in the new replacement battery  
pack while holding the internal connector out of  
the way.  
8. Reconnect the electrical connections for each  
battery pack.  
9. Install the battery retaining brackets using the  
Phillips removed earlier.  
UPStation GXT  
!
-
+
AC INPUT BATTERY UPS ON  
BYPASS  
10. Install the battery access panel and tighten the  
captive screws.  
NOTE  
These are hot-swappable replacement  
batteries. However, caution should be  
exercised because during this procedure the  
load is unprotected from disturbances and  
power outages.  
Battery Connectors  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Maintenance  
11.2 AC Power Connections  
Power connections may be disconnected from the UPS cabinet via a removable distribution box. This  
may be a convenient feature if the UPS must be moved a short distance or replaced. This box allows  
power connections to be conveniently disconnection from the main UPS cabinet. A label is attached to  
the UPS to describe these procedures.  
Hardwire and Hardwire/Receptacle boxes that include a Manual Bypass Switch allow AC power to  
continue to flow from the mains input to the load while the box is removed from the UPS.  
11.2.1 PD-CEHDWR—Manual Bypass Switch Available  
Disconnect  
1. DO NOT turn off the branch circuit breaker feeding power the box unless you intend to disconnect  
all power to the load.  
2. Ensure that the Maintenance Bypass Lamp is ON.  
3. Switch to the maintenance bypass position.  
The Load is now unprotected from line disturbances or interruptions.  
4. Turn off the UPS using the front panel controls.  
a. If needed, push the OFF button for one second once to transfer the load to bypass.  
b. Press the OFF button twice within four seconds to turn the UPS off.  
5. Turn off the UPS input circuit breaker on the box at the rear of the UPS.  
This input circuit breaker only cuts power to the connector between the box and UPS. The input  
circuit breaker does not cut power to the manual bypass switch.  
6. Turn off the output circuit breaker on the rear of the UPS.  
7. Remove the distribution box from the UPS  
a. Loosen all three captive screws until box releases.  
b. Pull box away from the UPS and set the box aside on a padded surface.  
CAUTION  
!
Power is still passing through the box from mains to the load.  
Reconnect  
1. Align connectors and press the box onto the rear of the UPS.  
2. 2. Hold the box firmly against the UPS and tighten the captive screws. Do not overtighten.  
3. If the Mains branch circuit breaker and load is off, turn the branch breaker on now.  
4. Turn on the output circuit breaker on the rear of the UPS.  
5. Turn on the input circuit breaker on the box.  
6. Start the UPS according to the startup instructions.  
Press the ON button for one second.  
7. Confirm that the UPS AVAILABLE lamp is lit beside the manual bypass switch.  
8. Turn the manual bypass switch to the UPS position.  
9. The UPS now protects the load.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Troubleshooting  
12.0 TROUBLESHOOTING  
The information below indicates various symptoms a user may encounter in the event the UPStation  
GXT2 develops a problem. Use this information to determine whether external factors caused the  
problem and how to remedy the situation.  
1. 1. The Fault indicator will illuminate, indicating the UPS detected a problem.  
2. 2. An alarm will sound, alerting that the UPS requires attention.  
Fault  
Example shows UPS  
on bypass because  
of output overload,  
signified by amber  
load indicator.  
AC INPUT BAT  
ON BYPAS S  
3. 3. One or more additional battery level LED indicators will be illuminated to provide a diagnostic  
aid to the operator, as described below:  
Table 3  
Indicator meanings  
LED status  
Diagnosis/Audible alarm  
All LEDs  
A LED  
On bypass due to output overload; beep every half-second  
On bypass due to overtemperature condition; beep every 4 sec.  
On bypass due to DC bus overvoltage; beep every 4 sec.  
DC-DC failure during battery mode; beep every 4 sec.  
On bypass due to PFC failure; beep every 4 sec.  
B LED  
C LED  
D LED  
E LED  
On bypass due to inverter failure; beep every 4 sec.  
A&C LEDs  
C&E LEDs  
UPS failed battery test; long beep every minute  
UPS shutdown due to command from communication port (SNMP); no beep  
Internal Battery source not available (continuous horn). Check Battery connection,  
completely power down and reboot UPS.  
Battery LED Flashing  
A&E LEDs  
B&C  
Fan locked  
REPO active. UPS cannot run with REPO loop open.  
UPS is OFF due to previous REPO shutdown. Autorestart disabled.  
Charger Malfunction  
B&D  
D&E  
Under fault conditions, the Fault indicators will be illuminated indefinitely while battery charger is  
operational, or for a maximum of 5 minutes while the battery charger is not operational.  
If a problem persists, consult your local dealer, Liebert representative or contact the Liebert World-  
wide Support Group. Please have the UPS model number and serial number available at the time of  
your inquiry.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Troubleshooting  
Table 4  
Troubleshooting guide  
Cause  
Solution  
Problem  
Ensure UPS is OFF. Disconnect all loads and ensure nothing is  
lodged in output receptacles.  
Ensure loads are not defective or shorted internally.  
UPS fails to start when the  
ON button is pressed.  
UPS is short-circuited or  
overloaded.  
UPS is operating from battery mode, make certain UPS is  
securely plugged into the wall receptacle.  
UPS not plugged in.  
UPS input protection fuse  
has blown/opened.  
UPS is operating from battery mode. Save data and close  
applications. Replace UPS input fuse, then restart UPS.  
Battery indicator LED is  
illuminated.  
UPS is operating from battery mode. Save data and close  
applications. Ensure mains supply voltage is within acceptable  
limits for UPS.  
Mains voltage out of UPS  
input range.  
Batteries are not fully  
charged.  
Keep UPS plugged in continuously at least 24 hours to  
recharge batteries.  
UPS has reduced battery  
time.  
UPS is overloaded.  
Check load level display and reduce the load on the UPS.  
Replace batteries. Contact your local dealer, Liebert  
representative or the Liebert Worldwide Support Group for  
replacement battery kit.  
Batteries may not be able to  
hold a full charge due to age.  
Fault and Bypass indicator  
LEDs and all load level LEDs  
are illuminated.  
Check load level display and remove non-essential loads.  
Recalculate the load and reduce number of loads connected to  
UPS. Check load equipment for faults.  
UPS overloaded or load  
equipment is faulty.  
Ensure UPS is not overloaded, ventilation openings not  
blocked, or room ambient temperature is not excessive. Wait  
30 minutes to allow UPS to cool, then restart UPS. If UPS does  
not restart, contact your local dealer, Liebert representative or  
the Liebert Worldwide Support Group.  
UPS internal fan has a  
Fault and Bypass indicator  
LEDs and diagnostic LED A  
are illuminated.  
problem or UPS shutdown  
due to temperature condition.  
Load is on bypass power.  
Fault and Bypass indicator  
LEDs and diagnostic LED B  
are illuminated.  
UPS internal DC bus  
overvoltage.  
UPS requires service. Contact your local dealer, Liebert  
representative or the Liebert Worldwide Support Group.  
Bus voltage under 315VDC(O/P 220VAC) / 330VDC(O/P  
DC-DC failure during battery 230VAC) / 345VDC(O/P 240VAC). UPS requires service.  
Fault indicator LED and  
diagnostic LED C are  
illuminated.  
mode.  
Contact your local dealer, Liebert representative or the Liebert  
Worldwide Support Group.  
Fault and Bypass indicator  
LEDs and diagnostic LED D  
are illuminated.  
UPS PFC (Power Factor  
Correction Circuit) fault.  
UPS requires service. Contact your local dealer, Liebert  
representative or the Liebert Worldwide Support Group.  
Fault and Bypass indicator  
LEDs and diagnostic LED E UPS inverter fault.  
are illuminated.  
UPS requires service. Contact your local dealer, Liebert  
Representative or the Liebert Worldwide Support Group.  
Fault indicator LED and  
diagnostic LEDs A and C are UPS failed the battery test.  
illuminated.  
Replace batteries. Contact your local dealer, Liebert  
representative or the Liebert Worldwide Support Group.  
Your UPS has received a signal or command from the attached  
computer. If this was inadvertent, ensure the communication  
cable used is correct for your system. For assistance, contact  
your local dealer, Liebert representative or the Liebert  
Worldwide Support Group.  
Fault and Bypass indicator  
LEDs and diagnostic LED C command from the  
and E are illuminated.  
UPS shutdown due to a  
communications port(s).  
Check for external obstruction entering fan guard. UPS  
requires service. Contact your local dealer, Liebert  
representative or Liebert Worldwide Support Group.  
Fault and LEDs A&E are  
Illuminated  
Fan locked  
Fault and LEDs B&C are  
Illuminated  
circuit is closed. If not used, a wire jumper must connect the  
REPO terminals.  
REPO active  
UPS is OFF due to previous  
REPO shutdown, but the  
REPO has been connected  
or reset. Autorestart  
disabled.  
Fault and LEDs B&D are  
Illuminated  
Start the UPS using the front panel.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Troubleshooting  
Table 4  
Troubleshooting guide (cont’d)  
Cause  
Solution  
Problem  
If the charger is overvoltage, the UPS will shutdown. If the  
charger is undervoltage and the batteries are nearly depleted,  
this alarm will give a temporary warning before the UPS shuts  
down. UPS requires service. Contact your local dealer, Liebert  
representative or Liebert Worldwide Support Group.  
Fault and LEDs D&E are  
Illuminated  
Charger malfunction  
Check battery connections, completely power down and restart  
UPS.  
NOTE: If the battery circuit  
Battery source is not  
Battery LED is flashing.  
available; continuous horn.  
opens while the UPS is running,  
it will be detected when the next  
battery test is performed.  
Table 5  
Alarm conditions  
Condition  
Alarm  
Battery Mode (mains failure)  
Low Battery  
One short beep every 10 seconds: more than 2 minutes of run time remaining  
Two short beeps every 5 seconds: less than 2 minutes of run time remaining  
One short beep every half second  
Output Overload (Bypass)  
Overtemperature (Bypass)  
DC Bus Overvoltage (Bypass)  
A one-second beep every 4 seconds  
A one-second beep every 4 seconds  
DC-DC failure during battery  
mode  
A one-second beep every 4 seconds  
PFC Failure (Bypass)  
Inverter Failure  
Battery Test Failure  
Fan Locked  
A one-second beep every 4 seconds  
A one-second beep every 4 seconds  
A two-second beep every 1 minute  
A one-second beep every 4 seconds  
A 0.25-second beep every 0.25 seconds  
REPO Active  
UPS OFF; Autorestart disabled  
from previous REPO shutdown  
A one-second beep every 4 seconds  
A one-second beep every 4 seconds  
Charger Malfunction  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Troubleshooting  
Table 6  
Battery run times  
Load%  
4500VA  
125  
66  
6000VA  
94  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
46  
29  
21  
17  
13  
11  
9
8
41  
30  
24  
19  
16  
14  
12  
10  
296  
166  
114  
86  
70  
56  
48  
41  
35  
31  
467  
262  
180  
142  
120  
98  
83  
72  
62  
54  
638  
358  
247  
193  
164  
138  
120  
104  
90  
Internal Battery  
(minutes)  
7
222  
124  
81  
60  
49  
39  
33  
28  
24  
Internal Battery  
+ 1 External Battery  
Cabinet (minutes)  
21  
350  
197  
135  
105  
85  
70  
58  
50  
43  
Internal Battery  
+ 2 External Battery  
Cabinets (minutes)  
38  
478  
269  
185  
145  
123  
101  
85  
73  
63  
55  
606  
341  
235  
184  
156  
131  
113  
97  
Internal Battery  
+ 3 External Battery  
Cabinets (minutes)  
80  
809  
454  
313  
245  
208  
175  
153  
135  
120  
106  
Internal Battery  
+ 4 External Battery  
Cabinets (minutes)  
85  
75  
Using the configuration program, the user may specify the number of GXT2-240VBATT external bat-  
tery cabinets attached to the UPS. The factory default is programmed for internal batteries only.  
Table 6 above shows the estimated run times at different loads.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Troubleshooting  
12.0.1 Auto-Learning Battery Run Times  
As batteries age, the estimated runtimes may become less accurate. The GXT2 is programmed to  
“learn” from a full battery discharge and modify the estimated runtime for the measured battery  
capacity. This can improve accuracy and compensate for aging batteries or batteries that operate at  
different ambient temperatures.  
The UPS will update the anticipated run time calculation only under certain conditions.  
• The UPS must have a steady load that is greater than 20%.  
• The UPS must be at 100% charge at the start of a battery discharge.  
• The battery discharge must continue uninterrupted until the batteries reach their end-of-dis-  
charge voltage.  
If all conditions are not met, the run time calculation will not be modified.  
If the configuration program is used to change the number of battery cabinets, then the values in the  
battery above table will be restored. This will override any value that is Auto-Learned.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Specifications  
13.0 SPECIFICATIONS  
Table 7  
UPS specifications  
Model Number  
GXT2-6000RT230  
GXT2-4500RT230  
4.5KVA / 3,150W  
Model Rating  
6KVA / 4,200W  
Dimensions mm (in.)  
Unit, W x D x H  
Shipping, W x D x H  
221 x 547 x 430 (8.7 x 21.5 x 16.9)  
560 x 690 x 500 (22.05 x 27.17 x 19.7)  
Weight kg (lbs)  
Unit  
Shipping  
67 (151)  
79.5 (175.3)  
67 (151)  
79.5 (175.3)  
Input AC Parameters  
Nominal Operating Frequency  
50 or 60Hz (Factory Default = 50)  
Factory Default VAC  
230VAC  
220/230/240VAC  
(May be modified using configuration program)  
User Configurable VAC  
Operating Voltage Range Without  
Battery Operation  
176 – 276VAC  
276VAC  
Maximum Allowable VAC  
Input Frequency Without Battery  
Operation  
40 - 70Hz  
Input Power Connection PD-CEHDWR Standard (See 3.3 - Removable Power Distribution Box)  
Output AC Parameters  
Factory Default VAC  
Output Connections PD-CEHDWR Standard (See 3.3 - Removable Power Distribution Box)  
230VAC  
Frequency  
Waveform  
50Hz or 60Hz, Nominal  
Sinewave  
Main Mode  
Overload  
>200% for 96 milliseconds; 131 - 199% for 2 seconds;  
112- 129% for 10 seconds with transfer to bypass  
Battery Parameters  
Type  
Quantity x V  
Valve-regulated, non-spillable, lead acid  
20 x 12V  
Battery Mfr. / Part #  
Back-up Time  
Yuasa / REW 28-12  
3 hrs. to 90% capacity after full discharge into 100% load  
Recharge Time (Internal Batteries)  
Bypass Protection Limits  
Disable Bypass operation  
Re-enable Bypass operation  
Disable Bypass operation  
Environmental  
If input voltage exceeds ±15% of the nominal voltage  
If input voltage returns to within ±10% of nominal output voltage  
When the input frequency prevents synchronous operation  
Operating Temperature  
Storage Temperature  
0°C to +40°C (+32°F to +104° F)  
-15°C to +50°C (+5°F to +122° F)  
0-95% non-condensing  
Relative Humidity  
Operating Elevation  
Storage Elevation  
Up to 2000m (6600 ft) at 40°C (104° F) without derating  
15,000m (50,000 ft.) maximum  
<55 dBA, at 1 meter from the rear  
<50 dBA, at 1 meter from the front or sides  
Audible Noise  
Agency  
Safety  
EMI/EMC/C-Tick EMC  
ESD  
EN62040-1-1; TUV/GS  
EN50091-2 and AS 62040-2: 2002, Class A; CE EMC Directive  
EN61000-4-2, Level 4, Criteria A  
Radiated Susceptibility  
Electrical Fast Transient  
Surge Immunity  
Transportation  
EN61000-4-3, Level 3, Criteria A  
EN61000-4-4, Level 4, Criteria A  
EN61000-4-5, Level 3, Criteria A  
ISTA Procedure 1B  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Specifications  
Table 8  
Model Number  
Amps Rating  
Power distribution specifications  
PD-CEHDWR  
PD-CEHDWRBYP  
32 Amps  
2
Input Power Connection  
Output Power Connection  
3-Wire Hardwired, 6-10mm (8-10AWG)  
2
3-Wire Hardwired, 6-10mm (8-10AWG)  
Two IEC320 C19 16A/250V sockets  
Manual Bypass Switch with Indicator Lamps  
Includes: Two IEC320 C19 16A/250V sockets  
Input Branch Circuit Breaker  
32A, Supplied by User  
Table 9  
External battery cabinet specifications  
Model Number  
GXT2-240VBATT  
Used w/ UPS model  
Dimensions, W x D x H, mm (in.)  
Unit (with bezel)  
Shipping  
GXT2-6000RT230, GXT2-4500RT230  
176 x 522 x 430 (6.9 x 20.55 x 16.9)  
560 x 690 x 455 (22 x 27.2 x 17.9)  
Weight, kg (lbs)  
Unit  
65 (145)  
Shipping  
78.5 (173.1)  
Battery Parameters  
Type  
Valve-regulated, non-spillable, flame retardant, lead acid  
20 x 12V  
Qty x V  
Battery Manufacturer, Part #  
Backup Time  
Yuasa / REW 45-12  
See Battery Run Times charts  
Environmental  
Operating Temp  
Storage Temp  
Relative Humidity  
Operating Elevation  
Storage Elevation  
Agency  
0°C to +40°C (+32°F to +104° F)  
-15°C to +50°C (+5°F to +122° F)  
0-95% non-condensing  
Up to 2000m (6600 ft.) at 40°C (104° F) without derating  
15,000m (50,000 ft.) maximum  
Safety  
EN62040-1-1; TUV/GS  
ISTA Procedure 1B  
Transportation  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Specifications  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
POWER AVAILABILITY  
GXT2-6000RT230& GXT2-4500RT230™  
USER MANUAL  
The Company Behind the Products  
Technical Support/Service  
Web Site  
With over a million installations around the globe,  
Liebert is the world leader in computer protection  
systems. Since its founding in 1965, Liebert has  
developed a complete range of support and  
protection systems for sensitive electronics:  
Monitoring  
800-222-5877  
Outside the US: 614-841-6755  
Environmental systems—close-control air  
conditioning from 1 to 60 tons  
Single-Phase UPS  
800-222-5877  
Power conditioning and UPS with power  
ranges from 300 VA to more than 1000 kVA  
Integrated systems that provide both  
environmental and power protection in a  
single, flexible package  
Monitoring and control—from systems of any  
size or location, on-site or remote  
Service and support through more than 100  
service centers around the world and a 24/7  
Customer Response Center  
Outside the US: 614-841-6755  
Three-Phase UPS  
800-543-2378  
Environmental Systems  
800-543-2778  
Outside the United States  
614-888-0246  
While every precaution has been taken to ensure  
the accuracy and completeness of this literature,  
Liebert Corporation assumes no responsibility and  
disclaims all liability for damages resulting from  
use of this information or for any errors or  
omissions.  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Italy  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD)  
+39 049 9719 111  
© 2004 Liebert Corporation  
All rights reserved throughout the world.  
Specifications subject to change without notice.  
® Liebert and the Liebert logo are registered  
trademarks of Liebert Corporation. All names  
referred to are trademarks or registered  
trademarks of their respective owners.  
Fax: +39 049 5841 257  
Asia  
23F, Allied Kajima Bldg.  
138 Gloucester Road  
Wanchai  
Hong Kong  
+852 2 572 2201  
Fax: +852 2 831 0114  
SLI-23170 (7/04) Rev. 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  

LG Electronics Flat Panel Television RU 23LZ50C User Manual
LG Electronics Indoor Fireplace MP 42OD User Manual
LG Electronics Microwave Oven LMV2015 User Manual
Macrom Stereo Amplifier 2100x User Manual
Manhattan Computer Products Computer Keyboard 176408 User Manual
Martin Audio Portable Speaker AQ15 User Manual
Maytag Oven CWE4800 User Manual
Maytag Range MGR6751BD User Manual
Melissa Juicer 144 002 User Manual
Metra Electronics Automobile Accessories 99 7503 User Manual