Liebert® GXT3™
Quick Start Guide – 5000-6000VA RT230 Models
The Liebert GXT3 is shipped with the following items:
•
•
Terminal Block Communication terminals
Compact disc with:
o
o
o
Liebert MultiLink®
Configuration program
User manual (electronic version)
•
•
•
•
•
USB cable, one; 2m (6-1/2 ft.) long
Rack handles with mounting hardware
Plastic tower support base, one set
Plastic Bezel
Warnings, safety instructions booklet and WEEE recycling sheet (ISO 14001 compliance)
If the UPS is intended to be installed in the Tower orientation, locate the support base and spacers then assemble the two
stand assemblies with an even number of spacers in each assembly. Insert the UPS between the support base
assemblies with adequate space between the assemblies as shown in the picture below. Note the display should be
located on the upper half of the unit in the Tower orientation. To rotate the display with the bezels removed, depress the
grooved tabs on the sides and rotate it 90 degrees clockwise. If the USP is to be installed in a rack enclosure, follow the
instructions provided with the rack mounting hardware for proper installation.
The UPS is hardwired input with a conduit entry knockouts provided. Input and output wiring should be installed in
separate conduits. All wiring should be done in accordance to all local and national electrical codes. Before wiring the
UPS ensure that the breaker in the external upstream panelboard is OFF.
Recommended
(Maximum) External Recommended Wire
Maximum Wire
Accepted by
Terminal Block
Over Current
Protection
(All wires)
75 degC Copper Wire
Terminal Block
Torque
UPS Model
GXT3-5000RT230
GXT3-6000RT230
32A
4mm2 (10 AWG)
6mm2 (8 AWG)
2.26 Nm (20 in-lb)
Terminal Block Connections
5000-6000 VA models
L
N
L
N
OUTPUT
INPUT
The UPS is equipped with a POD containing output receptacles; connect the equipment to be protected to the output
receptacles.
1
SLI-23185QS6_Rev0_09-2012
Download from Www.Somanuals.com. All Manuals Search And Download.
The Liebert® GXT3™ UPS is ready to be powered.
1. Locate the plastic bezel from the shipping box and attach the bezel to the UPS taking care to align the fastening
clips on both ends before inserting them into the holes.
2. If your application requires the use of external battery cabinets for longer back up time requirements, connect the
first battery cabinet to the UPS with the cable provided with the battery cabinet. Note: Either connector is
acceptable to connect the external battery cabinet. If more than one battery cabinet is used the additional
cabinets then connect to the previously connected battery cabinet.
3. Ensure the maintenance bypass breaker is in the open position and that the guard is secured in place.
4. Ensure that the REPO connector on the rear of the unit has a jumper between pins 1-2 of the REPO connector or
properly wired to an Emergency Power Off circuit (normally closed).
5. Install any optional Intellislot communication card into the Intellislot port on the rear of the unit.
6. Close the input breaker in the panelboard that provides input power to the UPS
7. Close the input breaker on the rear of the UPS unit. Note: The UPS will now have power and the AC Input
indicator on the display will illuminate. The UPS will begin to charge the internal batteries causing the battery
capacity LEDs to illuminate.
8. The Liebert GXT3 UPS has customizable settings that might be required depending on the application. Please
review the CD that ships with the UPS unit for the steps to use the configuration program and make any
necessary changes. Once that is complete, proceed to the next step.
9. Close all output breakers on the rear of the UPS
10. If external battery cabinets are used, close all breakers on the rear of each battery cabinet
11. Press and hold for about 4 seconds, the “ON” button on the UPS display. Note: this will apply power to the output
receptacles via the internal bypass. The bypass indicator will be illuminated along with an audible beep during this
time.
12. Over the next several seconds the UPS will perform the self checks and then automatically transfer the connected
equipment to conditioned power. Once that is complete, the bypass indicator will turn off and the inverter
indicator will illuminate.
The UPS is now running in normal operation mode providing protected, filtered power to the connected equipment.
6000VA
3
SLI-23185QS6_Rev0_09-2012
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
The following symptoms indicate the Liebert® GXT3™ is malfunctioning:
•
•
The relative indicators illuminate, indicating the UPS has detected a problem.
An alarm buzzer sounds, alerting the user that the UPS requires attention.
In addition to the fault indicator being illuminated, one or more of LED segments of battery level indicator will also be
illuminated to provide a diagnostic aid to the user, as shown below
The descriptions are listed in the following table
Indicator
A - E
Diagnosis/Audible alarm
On bypass from output overload (half-second beep every half-second)
On bypass due to over temperature condition (1-second beep every 4 seconds)
On bypass due to DC bus overvoltage (1-second beep every 4 seconds)
On bypass due to DC/DC power supply failure (1-second beep every 4 seconds)
PFC failure (1-second beep every 4 seconds)
On bypass due to inverter failure (1-second beep every 4 seconds)
UPS Failure (includes dual-fan failure, single-fan failure under certain conditions and
battery charger failure) and continuous alarm
A
B
C
D
E
A&B
A&C
A&D
A&E
B&C
B&E
UPS failed battery test (2-second beep every 60 seconds)
Maintenance bypass switch on (continuous)
Bypass feedback (1-second beep every 4 seconds)
REPO (one quarter-second beep at quarter-second intervals)
Short circuit on the output
UPS shutdown by command from communication (USB or Liebert IntelliSlot® port)
(no audible alarm)
C&E
AC Input Indicator
LED flashing
Battery Indicator
Flashing
L-N reverse
Internal battery source not available (continuous audible alarm); check battery
connection, power down and reboot UPS
Bypass Indicator
Flashing
Utility power voltage or frequency is out of tolerance; bypass is unavailable
Single-Phase UPS & Server Cabinets Technical Support
800-222-5877
Outside North America: +00800 1155 4499
Emerson Network Power Worldwide Locations
United States
Europe
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
800-222-5877
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572
4
SLI-23185QS6_Rev0_09-2012
Download from Www.Somanuals.com. All Manuals Search And Download.
|