Liebert Power Supply 115V User Manual

POWERSURE™ PROACTIVE  
350-700 VA  
115V & 230V  
USER MANUAL  
English / Deutsch / Français /  
Italiano / Español  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL INSTALLATION  
Check for damage  
Remove from box  
Or  
32 - 104 F  
0 - 40 C  
4 inches  
110 mm  
Plug in loads  
R
R
Plug UPS into AC / Mains  
Press On button  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
INTRODUCTION & SYSTEM DESCRIPTION  
Congratulations on your choice of the Liebert PowerSure ProActive  
Uninterruptible Power System (UPS).  
It provides conditioned power to  
microcomputers and other sensitive electronic equipment.  
The PowerSure ProActive is a compact, “Automatic Voltage Regulation” UPS. It  
offers “line-interactive” features by continuously conditioning and regulating  
output voltage, whether the utility power is present or not. It supplies connected  
equipment with stepped approximation to sinewave power to simulate the power  
generated by the utility.  
NOTE: This equipment has been tested and found to comply with the limits for a  
Class B digital device, pursuant to part 15 of the FCC Rules. These limits are  
designed to provide reasonable protection against harmful interference in a  
residential installation. This equipment uses, generates and can radiate radio  
frequency energy and, if not installed and used in accordance with the  
instructions, may cause harmful interference with radio communications.  
However, there is no guarantee that interference will not occur in a particular  
installation. If this equipment does cause harmful interference to radio or  
television reception, which can be determined by turning the equipment off and  
on, the user is encouraged to try to correct the interference by one or more of the  
following measures:  
-
-
-
Reorient or relocate the receiving antenna.  
Increase the separation between the equipment and the receiver.  
Connect the equipment into an outlet on a circuit different from that which  
the receiver is connected.  
-
Consult the dealer or an experienced radio/TV technician for help.  
BATTERY OPERATION  
Battery mode occurs in event of extreme input conditions or complete utility  
failure. During battery mode the Utility LED will flash every second and an alarm  
will sound every 3 seconds. This will change to a beep every second when  
battery runs low (approximately 2 minutes remaining).  
WARNING: Turning off the UPS while in battery mode will result in loss of output  
power.  
Press Battery Test button occasionally to ensure battery is fully charged.  
AUDIBLE ALARM CONDITIONS  
CONDITION  
Battery mode  
(utility failure)  
Low battery  
ALARM  
One short beep every three seconds; more  
than two minutes of run time remaining  
One beep every second; less than two  
minutes of run time remaining  
Two second beep every minute  
Continuous tone  
Battery replacement  
UPS output overload  
UPS fault  
Continuous tone  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAJOR COMPONENTS  
Continuous  
Flashing  
AC / Mains  
R
Battery Mode  
!
Fault  
Overload  
ON / Standby  
UPS Test  
Alarm Silence  
FRONT  
DB-9 Interface  
for SiteNet  
MultiLink cable  
Output  
Receptacles  
AC Input /  
Fuse Holder  
Phone / Fax /  
Modem / Network  
Interface  
BACK  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE  
The PowerSure ProActive UPS requires very little maintenance. The batteries  
are valve regulated, nonspillable, lead acid, and require that they be kept  
charged to obtain their designed life. When ON, the UPS continuously charges  
the batteries when connected to the utility supply.  
When storing the UPS for any length of time, it is recommended to plug in and  
turn on the UPS for at least 24 hours every four to six months to ensure full  
recharge of the batteries.  
The following will help ensure trouble-free operation for years to come:  
-
-
Vacuum dust from the ventilation intake occasionally.  
Wipe the cover periodically with a dry cloth.  
-
Occasionally press the UPS test button to test the condition of the batteries.  
FUSE REPLACEMENT PROCEDURES  
AC Inlet  
Insert flat blade screw  
driver into slot and pull  
fuse holder out to remove  
Fuse Holder  
Input Fuse  
Spare Fuse  
CAUTION: Before changing the supply fuse, turn off the UPS, and unplug the  
input cord from the AC input power supply and from the UPS.  
1. Remove the fuse holder by inserting a flat blade screwdriver into the slot and  
pulling out as indicated in the figure above.  
2. Remove the input fuse.  
3. Remove the spare fuse from its position by using the screwdriver to push it  
out.  
4. Place spare fuse in the input fuse position, and replace the fuse holder. The  
fuse holder will lock into position.  
5. Reconnect the input power lead to the UPS, and the input power lead to the  
input AC supply.  
6. Restart the UPS. The UPS is ready for normal operation.  
ProActive Model #  
PSA350-120  
PSA470-120  
PSA700-120  
PSA350-230  
PSA470-230  
PSA700-230  
Fuse Type  
5A / 125V  
6A / 125V  
8A / 125V  
3.15A / 250V  
4A / 250V  
6.3A / 250V  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATIONS  
You can use SiteNet® MultiLink™ to allow your UPS to communicate to  
your computer via your DB-9 communications port. Download MultiLink  
from our web site at www.liebert.com.  
Pin Configuration  
PIN ASSIGNMENT  
Pin #  
Function  
On Battery (N.O.)  
On Battery (Common)  
On Battery (N.C.)  
Low Battery  
9
8
6
1
7
Low Battery  
5
4
UPS Ground  
UPS Off  
TROUBLESHOOTING  
If the UPS fails to operate properly, turn off the unit and repeat the steps in the  
installation section of this manual. If the problem persists, refer to the chart  
below:  
PROBLEM  
CAUSE  
SOLUTION  
UPS will not start  
Overload/Short Circuit  
Check fuse at rear of UPS. If blown, replace it  
and restart the UPS. For further help, call your  
Liebert representative.  
UPS starts on  
battery, but will  
not switch to AC  
UPS not plugged in  
Fuse blown  
Plug in power  
cord securely.  
Replace fuse and restart UPS.  
Call a qualified electrician.  
Power not available at  
utility receptacle  
Input voltage below  
threshold  
Wait until voltage rises to appropriate level  
AC overvoltage  
AC voltage must be less than 144 VAC for  
115V, 270 VAC for 230V.  
UPS shuts down  
Overload/Short Circuit  
Check the fuse holder at rear of UPS. If fuse is  
blown, replace it and restart the UPS. If problem  
persists, disconnect some of the equipment from  
your UPS - the total wattage of your equipment  
may exceed the capacity of the UPS. For  
further help, call your Liebert representative.  
Low Battery  
Turn OFF equipment and recharge UPS battery  
for at least 8 hours. If problem persists, contact  
your Liebert representative.  
Sitenet 1 Shutdown  
Consult the Sitenet 1 User Manual or contact  
your LAN administrator.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
115V SPECIFICATIONS  
Model Number  
Model Rating VA/W  
PSA350-120  
350VA/210W  
PSA470-120  
470VA/282W  
PSA700-120  
700VA/420W  
DIMENSIONS: in (mm)  
Unit  
6.5 x 4.5 x 13.9  
(166 x 115.5 x 352.5)  
8.8 x 6.2 x 15.8  
6.5 x 4.5 x 13.9  
(166 x 115.5 x 352.5)  
8.8 x 6.2 x 15.8  
6.5 x 4.5 x 13.9  
(166 x 115.5 x 352.5)  
8.8 x 6.2 x 15.8  
H x W x D  
Shipping  
H x W x D  
(226 x 156 x 404)  
(226 x 156 x 404)  
(226 x 156 x 404)  
WEIGHT: lbs (kg)  
Unit  
Shipping  
13.2 (6)  
15 (6.8)  
15.4 (7)  
17.2 (7.8)  
22 (10)  
23.8 (10.8)  
INPUT AC PARAMETERS  
Voltage Range  
87 to 144VAC  
without Battery Operation  
Line to Boost Transfer  
Line to Buck Transfer  
Frequency  
104VAC  
124VAC  
47-53 Hz or 57-63 Hz; auto sensing  
6 ft. detachable, w/ NEMA 5-15 P  
Input Power Cord  
OUTPUT AC PARAMETERS  
Output Receptacles  
(4) 5-15R  
Voltage (Battery Mode)  
Waveform (Battery Mode)  
Voltage (Normal)  
115 VAC + 5%  
Stepped Sinewave  
VIN * (1.0)  
Voltage (Boost Mode)  
Voltage (Buck Mode)  
Frequency  
VIN * (1.16)  
VIN * (0.84)  
50 Hz or 60 Hz; auto sensing  
Overload Warning  
(Utility and Battery Modes)  
101 – 120%  
Overload Shutdown  
(Utility and Battery Modes)  
Overload  
+ (15 – 30W)  
Overload  
+ (20 – 40W)  
Overload  
+ (30 – 60W)  
BATTERY PARAMETERS  
Type  
Valve-regulated, nonspillable, lead acid  
Quantity x Voltage x Rating  
Approved Battery  
Manufacturers:  
Transfer Time  
(1) x 12V x 7.0 Ah  
CSB, Panasonic, and Yuasa  
(1) x 12V x 7.0 Ah  
(1) x 12V x 10 Ah  
4 – 6 ms typical  
Back-up Time:  
Full load  
At 77°F (25°C), resistive loading, with fully charged batteries:  
> 5 minutes typical  
Half load  
> 15 minutes typical  
> 12 minutes typical  
> 13 minutes typical  
Recharge Time  
ENVIRONMENTAL  
Operating Temperature  
Storage Temperature  
Relative Humidity  
Operating Elevation  
Audible Noise  
7-10 hours to 90% capacity, after full discharge into 100% resistive load  
+32° F to + 104° F (0° C to +40° C)  
+5° F to + 122° F (-15° C to +50° C)  
0% to 90%, non-condensing  
Up to 10,000 ft. (3000 m) at 95° F (35° C) without derating  
< 40 dBA, at 1 meter  
AGENCY  
Safety  
UL 1778, c-UL Listed  
Surge  
IEEE C62.41 Category A  
ESD  
Susceptibility  
Electrical Fast Transient/Burst  
Emissions  
IEC 801-2, Level 3, Criterion< 2  
IEC 801-3, Level 3, Criterion< 2  
IEC 801-4, Level 4, Criterion< 2  
FCC Part 15, Subpart B, Class B  
Transportation  
ISTA Project 1A  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
230V SPECIFICATIONS  
Model Number  
Model Rating VA/W  
PSA350-230  
350VA/210W  
PSA470-230  
470VA/282W  
PSA700-230  
700VA/420W  
DIMENSIONS: mm (in)  
Unit  
166 x 115.5 x 352.5  
(6.5 x 4.5 x 13.9)  
226 x 156 x 404  
(8.8 x 6.2 x 15.8)  
166 x 115.5 x 352.5  
(6.5 x 4.5 x 13.9)  
226 x 156 x 404  
(8.8 x 6.2 x 15.8)  
166 x 115.5 x 352.5  
(6.54 x 4.55 x 13.9)  
226 x 156 x 404  
H x W x D  
Shipping  
H x W x D  
(8.8 x 6.2 x 15.8)  
WEIGHT: kg (lbs)  
Unit  
Shipping  
6 (13.2)  
6.8 (15)  
7 (15.4)  
7.8 (17.2)  
10 (22)  
10.8 (23.8)  
INPUT AC PARAMETERS  
Voltage Range without  
Battery Operation  
166 to 275VAC  
Line to Boost Transfer  
Line to Buck Transfer  
Frequency  
198VAC  
250VAC  
47-53 Hz or 57-63 Hz; auto sensing  
EN60320/C14 recessed plug  
Input Power Receptacle  
OUTPUT AC PARAMETERS  
Output Receptacles  
(4) EN60320/C13 sockets, (2) detachable EN60320-2-2 1.8m (6’) power  
cords  
Voltage (Battery Mode)  
Waveform (Battery Mode)  
Voltage (Normal)  
230 VAC + 5%  
Stepped Sinewave  
VIN * (1.0)  
Voltage (Boost Mode)  
Voltage (Buck Mode)  
Frequency  
VIN * (1.13)  
VIN * (0.85)  
50 Hz or 60 Hz; auto sensing  
101 – 120%  
Overload Warning  
(Utility and Battery Modes)  
Overload Shutdown  
(Utility and Battery Modes)  
Overload  
+ (15 – 30W)  
Overload  
+ (20 – 40W)  
Overload  
+ (30 – 60W)  
BATTERY PARAMETERS  
Type  
Quantity x Voltage x Rating  
Valve-regulated, nonspillable, lead acid  
(1) x 12V x 7.0 Ah (1) x 12V x 7.0 Ah  
(1) x 12V x 10 Ah  
Approved Battery  
Manufacturers:  
Transfer Time  
Back-up Time:  
Full load  
Half load  
Recharge Time  
CSB, Panasonic, and Yuasa  
4 – 6 ms typical  
At 25°C (77°F), resistive loading, with fully charged batteries:  
> 5 minutes typical  
> 15 minutes typical  
> 12 minutes typical  
> 13 minutes typical  
7-10 hours to 90% capacity, after full discharge into 100% resistive load  
ENVIRONMENTAL  
Operating Temperature  
Storage Temperature  
Relative Humidity  
0° C to +40° C (+32° F to + 104° F)  
-15° C to +50° C (+5° F to + 122° F)  
0% to 90%, non-condensing  
Operating Elevation  
Audible Noise  
Up to 3000 m. (10,000 ft) at 35° C (95° F) without derating  
<40 dBA, at 1 meter  
AGENCY  
Safety  
Surge  
EN50091-1, TUV/GS listed, CE Compliance Mark  
IEC 801-5, Level 3  
ESD  
IEC 801-2, Level 3, Criterion< 2  
IEC 801-3, Level 3, Criterion< 2  
IEC 801-4, Level 4, Criterion< 2  
Susceptibility  
Electrical Fast  
Transient/Burst  
Emissions  
Transportation  
EN50091-2, EN55011 Class B  
ISTA Project 1A  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIMITED WARRANTY  
Liebert Corporation extends the following LIMITED WARRANTY to the purchaser  
and to its customer (collectively referred to as the "Purchaser"): the enclosed  
Uninterruptible Power System (UPS) and components are free from defects in  
materials and workmanship under normal use, service, and maintenance FOR A  
PERIOD OF TWO YEARS FROM THE DATE OF ORIGINAL PURCHASE from  
Liebert or the Liebert dealer or retailer. THE FOREGOING WARRANTY IS THE  
ONLY WARRANTY GIVEN AND NO OTHER WARANTY IS PROVIDED, EXPRESS  
OR IMPLIED, INCLUDING WITHOUT LIMITATION, MERCHANTABILITY OR  
FITNESS FOR A PARTICULAR PURPOSE. Certain aspects of disclaimers are not  
applicable to consumer products acquired by individuals and used for personal,  
family, or household purposes (as distinguished from industrial or other purposes).  
Local laws may not allow limitations on how long an implied warranty lasts, so the  
above limitation may not apply to you. This warranty gives you specific legal rights,  
and you may have other rights which vary according to local law.  
Certain repairs or services are the responsibility of the Purchaser and the Purchaser  
is expected to pay for them. This warranty does not extend either to products with  
removed or altered serial numbers or to any losses or damages due to act of God or  
source external to the product, misuse, accident, abuse, neglect, negligence,  
unauthorized modification, alteration, or repair, use beyond rated capacity, or  
improper installation, maintenance, application or use, including, without limitation,  
use in a manner contrary to the accompanying instructions or applicable codes.  
WARNING: Warranty is void if the battery is allowed to discharge below the minimum  
battery cutoff point. To prevent such discharge DO NOT leave the unit power switch  
"ON" for more than two (2) days without AC power being supplied to the UPS. The  
battery must be recharged every four (4) to six (6) months when not in use.  
If the UPS fails to conform with the above warranty within the two year warranty  
period, Liebert will repair or replace the UPS, at Liebert's option. Repairs or  
replacements are warranted for the remainder of the original warranty period. To  
make a warranty claim, purchaser should call a Liebert Representative to obtain a  
Returned Goods Authorization number and shipping instructions. Return  
transportation costs to Liebert are the responsibility of the Purchaser.  
"LIFE SUPPORT" POLICY  
This product is not recommended, and the Company will not knowingly sell this  
product, for use with life support and other designated "critical" devices. ANY SUCH  
USE BY A USER AUTOMATICALLY VOIDS AND DISCLAIMS ANY AND ALL  
WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY,  
IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, AND  
EXPRESS WARRANTIES THAT THIS PRODUCT WILL CONFORM TO ANY  
AFFIRMATION OR PROMISE, FOR THIS PRODUCT AND THE USER AGREES  
THAT IN NO EVENT SHALL THE COMPANY BE LIABLE FOR CONSEQUENTIAL  
OR INDIRECT DAMAGES.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
POWERSURE™ PROACTIVE  
350- 700 VA  
115V & 230V  
Technical Support  
U.S.A.  
1-800-222-5877  
Outside the U.S.A.  
614-841-6755  
U.K.  
France  
Germany  
Italy  
Netherlands  
+44 (0) 1793 553355  
+33 (0) 1 43 60 01 77  
+49 89 99 19 220  
+39 2 98250 1  
+00 31 475 503333  
+614-841-5471  
E-mail  
Web site  
Worldwide FAX tech support  
The Company Behind The Products  
With more than 500,000 installations around  
the globe, Liebert is the world leader in  
While every precaution has been taken  
to ensure accuracy and completeness of  
this literature, Liebert Corporation  
computer protection systems.  
Since its  
founding in 1965, Liebert has developed a  
complete range of support and protection  
systems for sensitive electronics:  
assumes  
no  
responsibility,  
and  
disclaims all liability for damages  
resulting from use of this information or  
for any errors or omissions.  
·
·
·
Environmental systems: close-control air  
conditioning from 1.5 to 60 tons.  
Power conditioning and UPS with power  
ranges from 250 VA to more than 1000 kVA.  
Integrated systems that provide both  
©1998 Liebert Corporation All rights  
reserved  
throughout  
the  
world.  
Specifications subject to change without  
notice.  
environmental and power protection in  
single, flexible package.  
a
®
Liebert and the Liebert logo are  
registered trademarks of Liebert  
·
·
Monitoring and control — on-site or remote —  
from systems of any size or location  
Service and support, through more than 100  
service centers around the world, and a 24-  
hour Customer Response Center.  
Corporation. All names referred to are  
trademarks or registered trademarks of  
their respective owners.  
SLI-23256 (1/99) Rev. 2  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  

KTM Motorcycle 250 SX F 250 XC F XCF W 250 EXC F EXC F User Manual
Land Pride Snow Blower Snow Plow User Manual
LG Electronics Air Conditioner EN 61000 2 User Manual
Liebert Stereo System TM 10098 User Manual
Lincoln Electric Welding System IM10031 A User Manual
Linksys Network Card WPC54GX4 User Manual
Marantz Home Theater System SR5006 User Manual
Master Bilt Refrigerator ATMC 122SS User Manual
McCulloch Chainsaw M3816 User Manual
Metra Electronics eBook Reader 99 2008 User Manual