POWERSURE™ PROACTIVE
350-700 VA
115V & 230V
USER MANUAL
English / Deutsch / Français /
Italiano / Español
Download from Www.Somanuals.com. All Manuals Search And Download.
GENERAL INSTALLATION
Check for damage
Remove from box
Or
32 - 104 F
0 - 40 C
4 inches
110 mm
Plug in loads
R
R
Plug UPS into AC / Mains
Press On button
3
Download from Www.Somanuals.com. All Manuals Search And Download.
INTRODUCTION & SYSTEM DESCRIPTION
Congratulations on your choice of the Liebert PowerSure ProActive
Uninterruptible Power System (UPS).
It provides conditioned power to
microcomputers and other sensitive electronic equipment.
The PowerSure ProActive is a compact, “Automatic Voltage Regulation” UPS. It
offers “line-interactive” features by continuously conditioning and regulating
output voltage, whether the utility power is present or not. It supplies connected
equipment with stepped approximation to sinewave power to simulate the power
generated by the utility.
NOTE: This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment uses, generates and can radiate radio
frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference with radio communications.
However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more of the
following measures:
-
-
-
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and the receiver.
Connect the equipment into an outlet on a circuit different from that which
the receiver is connected.
-
Consult the dealer or an experienced radio/TV technician for help.
BATTERY OPERATION
Battery mode occurs in event of extreme input conditions or complete utility
failure. During battery mode the Utility LED will flash every second and an alarm
will sound every 3 seconds. This will change to a beep every second when
battery runs low (approximately 2 minutes remaining).
WARNING: Turning off the UPS while in battery mode will result in loss of output
power.
Press Battery Test button occasionally to ensure battery is fully charged.
AUDIBLE ALARM CONDITIONS
CONDITION
Battery mode
(utility failure)
Low battery
ALARM
One short beep every three seconds; more
than two minutes of run time remaining
One beep every second; less than two
minutes of run time remaining
Two second beep every minute
Continuous tone
Battery replacement
UPS output overload
UPS fault
Continuous tone
4
Download from Www.Somanuals.com. All Manuals Search And Download.
MAJOR COMPONENTS
Continuous
Flashing
AC / Mains
R
Battery Mode
!
Fault
Overload
ON / Standby
UPS Test
Alarm Silence
FRONT
DB-9 Interface
for SiteNet
MultiLink cable
Output
Receptacles
AC Input /
Fuse Holder
Phone / Fax /
Modem / Network
Interface
BACK
5
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
The PowerSure ProActive UPS requires very little maintenance. The batteries
are valve regulated, nonspillable, lead acid, and require that they be kept
charged to obtain their designed life. When ON, the UPS continuously charges
the batteries when connected to the utility supply.
When storing the UPS for any length of time, it is recommended to plug in and
turn on the UPS for at least 24 hours every four to six months to ensure full
recharge of the batteries.
The following will help ensure trouble-free operation for years to come:
-
-
Vacuum dust from the ventilation intake occasionally.
Wipe the cover periodically with a dry cloth.
-
Occasionally press the UPS test button to test the condition of the batteries.
FUSE REPLACEMENT PROCEDURES
AC Inlet
Insert flat blade screw
driver into slot and pull
fuse holder out to remove
Fuse Holder
Input Fuse
Spare Fuse
CAUTION: Before changing the supply fuse, turn off the UPS, and unplug the
input cord from the AC input power supply and from the UPS.
1. Remove the fuse holder by inserting a flat blade screwdriver into the slot and
pulling out as indicated in the figure above.
2. Remove the input fuse.
3. Remove the spare fuse from its position by using the screwdriver to push it
out.
4. Place spare fuse in the input fuse position, and replace the fuse holder. The
fuse holder will lock into position.
5. Reconnect the input power lead to the UPS, and the input power lead to the
input AC supply.
6. Restart the UPS. The UPS is ready for normal operation.
ProActive Model #
PSA350-120
PSA470-120
PSA700-120
PSA350-230
PSA470-230
PSA700-230
Fuse Type
5A / 125V
6A / 125V
8A / 125V
3.15A / 250V
4A / 250V
6.3A / 250V
6
Download from Www.Somanuals.com. All Manuals Search And Download.
COMMUNICATIONS
You can use SiteNet® MultiLink™ to allow your UPS to communicate to
your computer via your DB-9 communications port. Download MultiLink
Pin Configuration
PIN ASSIGNMENT
Pin #
Function
On Battery (N.O.)
On Battery (Common)
On Battery (N.C.)
Low Battery
9
8
6
1
7
Low Battery
5
4
UPS Ground
UPS Off
TROUBLESHOOTING
If the UPS fails to operate properly, turn off the unit and repeat the steps in the
installation section of this manual. If the problem persists, refer to the chart
below:
PROBLEM
CAUSE
SOLUTION
UPS will not start
Overload/Short Circuit
Check fuse at rear of UPS. If blown, replace it
and restart the UPS. For further help, call your
Liebert representative.
UPS starts on
battery, but will
not switch to AC
UPS not plugged in
Fuse blown
Plug in power
cord securely.
Replace fuse and restart UPS.
Call a qualified electrician.
Power not available at
utility receptacle
Input voltage below
threshold
Wait until voltage rises to appropriate level
AC overvoltage
AC voltage must be less than 144 VAC for
115V, 270 VAC for 230V.
UPS shuts down
Overload/Short Circuit
Check the fuse holder at rear of UPS. If fuse is
blown, replace it and restart the UPS. If problem
persists, disconnect some of the equipment from
your UPS - the total wattage of your equipment
may exceed the capacity of the UPS. For
further help, call your Liebert representative.
Low Battery
Turn OFF equipment and recharge UPS battery
for at least 8 hours. If problem persists, contact
your Liebert representative.
Sitenet 1 Shutdown
Consult the Sitenet 1 User Manual or contact
your LAN administrator.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
115V SPECIFICATIONS
Model Number
Model Rating VA/W
PSA350-120
350VA/210W
PSA470-120
470VA/282W
PSA700-120
700VA/420W
DIMENSIONS: in (mm)
Unit
6.5 x 4.5 x 13.9
(166 x 115.5 x 352.5)
8.8 x 6.2 x 15.8
6.5 x 4.5 x 13.9
(166 x 115.5 x 352.5)
8.8 x 6.2 x 15.8
6.5 x 4.5 x 13.9
(166 x 115.5 x 352.5)
8.8 x 6.2 x 15.8
H x W x D
Shipping
H x W x D
(226 x 156 x 404)
(226 x 156 x 404)
(226 x 156 x 404)
WEIGHT: lbs (kg)
Unit
Shipping
13.2 (6)
15 (6.8)
15.4 (7)
17.2 (7.8)
22 (10)
23.8 (10.8)
INPUT AC PARAMETERS
Voltage Range
87 to 144VAC
without Battery Operation
Line to Boost Transfer
Line to Buck Transfer
Frequency
104VAC
124VAC
47-53 Hz or 57-63 Hz; auto sensing
6 ft. detachable, w/ NEMA 5-15 P
Input Power Cord
OUTPUT AC PARAMETERS
Output Receptacles
(4) 5-15R
Voltage (Battery Mode)
Waveform (Battery Mode)
Voltage (Normal)
115 VAC + 5%
Stepped Sinewave
VIN * (1.0)
Voltage (Boost Mode)
Voltage (Buck Mode)
Frequency
VIN * (1.16)
VIN * (0.84)
50 Hz or 60 Hz; auto sensing
Overload Warning
(Utility and Battery Modes)
101 – 120%
Overload Shutdown
(Utility and Battery Modes)
Overload
+ (15 – 30W)
Overload
+ (20 – 40W)
Overload
+ (30 – 60W)
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, lead acid
Quantity x Voltage x Rating
Approved Battery
Manufacturers:
Transfer Time
(1) x 12V x 7.0 Ah
CSB, Panasonic, and Yuasa
(1) x 12V x 7.0 Ah
(1) x 12V x 10 Ah
4 – 6 ms typical
Back-up Time:
Full load
At 77°F (25°C), resistive loading, with fully charged batteries:
> 5 minutes typical
Half load
> 15 minutes typical
> 12 minutes typical
> 13 minutes typical
Recharge Time
ENVIRONMENTAL
Operating Temperature
Storage Temperature
Relative Humidity
Operating Elevation
Audible Noise
7-10 hours to 90% capacity, after full discharge into 100% resistive load
+32° F to + 104° F (0° C to +40° C)
+5° F to + 122° F (-15° C to +50° C)
0% to 90%, non-condensing
Up to 10,000 ft. (3000 m) at 95° F (35° C) without derating
< 40 dBA, at 1 meter
AGENCY
Safety
UL 1778, c-UL Listed
Surge
IEEE C62.41 Category A
ESD
Susceptibility
Electrical Fast Transient/Burst
Emissions
IEC 801-2, Level 3, Criterion< 2
IEC 801-3, Level 3, Criterion< 2
IEC 801-4, Level 4, Criterion< 2
FCC Part 15, Subpart B, Class B
Transportation
ISTA Project 1A
8
Download from Www.Somanuals.com. All Manuals Search And Download.
230V SPECIFICATIONS
Model Number
Model Rating VA/W
PSA350-230
350VA/210W
PSA470-230
470VA/282W
PSA700-230
700VA/420W
DIMENSIONS: mm (in)
Unit
166 x 115.5 x 352.5
(6.5 x 4.5 x 13.9)
226 x 156 x 404
(8.8 x 6.2 x 15.8)
166 x 115.5 x 352.5
(6.5 x 4.5 x 13.9)
226 x 156 x 404
(8.8 x 6.2 x 15.8)
166 x 115.5 x 352.5
(6.54 x 4.55 x 13.9)
226 x 156 x 404
H x W x D
Shipping
H x W x D
(8.8 x 6.2 x 15.8)
WEIGHT: kg (lbs)
Unit
Shipping
6 (13.2)
6.8 (15)
7 (15.4)
7.8 (17.2)
10 (22)
10.8 (23.8)
INPUT AC PARAMETERS
Voltage Range without
Battery Operation
166 to 275VAC
Line to Boost Transfer
Line to Buck Transfer
Frequency
198VAC
250VAC
47-53 Hz or 57-63 Hz; auto sensing
EN60320/C14 recessed plug
Input Power Receptacle
OUTPUT AC PARAMETERS
Output Receptacles
(4) EN60320/C13 sockets, (2) detachable EN60320-2-2 1.8m (6’) power
cords
Voltage (Battery Mode)
Waveform (Battery Mode)
Voltage (Normal)
230 VAC + 5%
Stepped Sinewave
VIN * (1.0)
Voltage (Boost Mode)
Voltage (Buck Mode)
Frequency
VIN * (1.13)
VIN * (0.85)
50 Hz or 60 Hz; auto sensing
101 – 120%
Overload Warning
(Utility and Battery Modes)
Overload Shutdown
(Utility and Battery Modes)
Overload
+ (15 – 30W)
Overload
+ (20 – 40W)
Overload
+ (30 – 60W)
BATTERY PARAMETERS
Type
Quantity x Voltage x Rating
Valve-regulated, nonspillable, lead acid
(1) x 12V x 7.0 Ah (1) x 12V x 7.0 Ah
(1) x 12V x 10 Ah
Approved Battery
Manufacturers:
Transfer Time
Back-up Time:
Full load
Half load
Recharge Time
CSB, Panasonic, and Yuasa
4 – 6 ms typical
At 25°C (77°F), resistive loading, with fully charged batteries:
> 5 minutes typical
> 15 minutes typical
> 12 minutes typical
> 13 minutes typical
7-10 hours to 90% capacity, after full discharge into 100% resistive load
ENVIRONMENTAL
Operating Temperature
Storage Temperature
Relative Humidity
0° C to +40° C (+32° F to + 104° F)
-15° C to +50° C (+5° F to + 122° F)
0% to 90%, non-condensing
Operating Elevation
Audible Noise
Up to 3000 m. (10,000 ft) at 35° C (95° F) without derating
<40 dBA, at 1 meter
AGENCY
Safety
Surge
EN50091-1, TUV/GS listed, CE Compliance Mark
IEC 801-5, Level 3
ESD
IEC 801-2, Level 3, Criterion< 2
IEC 801-3, Level 3, Criterion< 2
IEC 801-4, Level 4, Criterion< 2
Susceptibility
Electrical Fast
Transient/Burst
Emissions
Transportation
EN50091-2, EN55011 Class B
ISTA Project 1A
9
Download from Www.Somanuals.com. All Manuals Search And Download.
LIMITED WARRANTY
Liebert Corporation extends the following LIMITED WARRANTY to the purchaser
and to its customer (collectively referred to as the "Purchaser"): the enclosed
Uninterruptible Power System (UPS) and components are free from defects in
materials and workmanship under normal use, service, and maintenance FOR A
PERIOD OF TWO YEARS FROM THE DATE OF ORIGINAL PURCHASE from
Liebert or the Liebert dealer or retailer. THE FOREGOING WARRANTY IS THE
ONLY WARRANTY GIVEN AND NO OTHER WARANTY IS PROVIDED, EXPRESS
OR IMPLIED, INCLUDING WITHOUT LIMITATION, MERCHANTABILITY OR
FITNESS FOR A PARTICULAR PURPOSE. Certain aspects of disclaimers are not
applicable to consumer products acquired by individuals and used for personal,
family, or household purposes (as distinguished from industrial or other purposes).
Local laws may not allow limitations on how long an implied warranty lasts, so the
above limitation may not apply to you. This warranty gives you specific legal rights,
and you may have other rights which vary according to local law.
Certain repairs or services are the responsibility of the Purchaser and the Purchaser
is expected to pay for them. This warranty does not extend either to products with
removed or altered serial numbers or to any losses or damages due to act of God or
source external to the product, misuse, accident, abuse, neglect, negligence,
unauthorized modification, alteration, or repair, use beyond rated capacity, or
improper installation, maintenance, application or use, including, without limitation,
use in a manner contrary to the accompanying instructions or applicable codes.
WARNING: Warranty is void if the battery is allowed to discharge below the minimum
battery cutoff point. To prevent such discharge DO NOT leave the unit power switch
"ON" for more than two (2) days without AC power being supplied to the UPS. The
battery must be recharged every four (4) to six (6) months when not in use.
If the UPS fails to conform with the above warranty within the two year warranty
period, Liebert will repair or replace the UPS, at Liebert's option. Repairs or
replacements are warranted for the remainder of the original warranty period. To
make a warranty claim, purchaser should call a Liebert Representative to obtain a
Returned Goods Authorization number and shipping instructions. Return
transportation costs to Liebert are the responsibility of the Purchaser.
"LIFE SUPPORT" POLICY
This product is not recommended, and the Company will not knowingly sell this
product, for use with life support and other designated "critical" devices. ANY SUCH
USE BY A USER AUTOMATICALLY VOIDS AND DISCLAIMS ANY AND ALL
WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY,
IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, AND
EXPRESS WARRANTIES THAT THIS PRODUCT WILL CONFORM TO ANY
AFFIRMATION OR PROMISE, FOR THIS PRODUCT AND THE USER AGREES
THAT IN NO EVENT SHALL THE COMPANY BE LIABLE FOR CONSEQUENTIAL
OR INDIRECT DAMAGES.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
POWERSURE™ PROACTIVE
350- 700 VA
115V & 230V
Technical Support
U.S.A.
1-800-222-5877
Outside the U.S.A.
614-841-6755
U.K.
France
Germany
Italy
Netherlands
+44 (0) 1793 553355
+33 (0) 1 43 60 01 77
+49 89 99 19 220
+39 2 98250 1
+00 31 475 503333
+614-841-5471
E-mail
Web site
Worldwide FAX tech support
The Company Behind The Products
With more than 500,000 installations around
the globe, Liebert is the world leader in
While every precaution has been taken
to ensure accuracy and completeness of
this literature, Liebert Corporation
computer protection systems.
Since its
founding in 1965, Liebert has developed a
complete range of support and protection
systems for sensitive electronics:
assumes
no
responsibility,
and
disclaims all liability for damages
resulting from use of this information or
for any errors or omissions.
·
·
·
Environmental systems: close-control air
conditioning from 1.5 to 60 tons.
Power conditioning and UPS with power
ranges from 250 VA to more than 1000 kVA.
Integrated systems that provide both
©1998 Liebert Corporation All rights
reserved
throughout
the
world.
Specifications subject to change without
notice.
environmental and power protection in
single, flexible package.
a
®
Liebert and the Liebert logo are
registered trademarks of Liebert
·
·
Monitoring and control — on-site or remote —
from systems of any size or location
Service and support, through more than 100
service centers around the world, and a 24-
hour Customer Response Center.
Corporation. All names referred to are
trademarks or registered trademarks of
their respective owners.
SLI-23256 (1/99) Rev. 2
11
Download from Www.Somanuals.com. All Manuals Search And Download.
|