Liebert Power Supply 1000kVA User Manual

AC POWER SYSTEMS  
SERIES 610™ UPS  
OPERATION & MAINTENANCE MANUAL  
100-1000kVA, 60Hz  
Three Phase  
Multi-Module  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.5  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURES  
Figure 1  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLES  
iv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS  
This manual contains important instructions that should be followed during installation and mainte-  
nance of your Series 610 UPS and batteries.  
WARNING  
!
Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to  
personnel. Refer to separate installation manual for equipment handling information and  
installation procedures.  
Follow all battery safety precautions in 4.0 - Maintenance when installing, charging or  
servicing batteries. In addition to the hazard of electric shock, gas produced by batteries can  
be explosive and sulfuric acid can cause severe burns.  
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or  
others approved for use in electrical fire fighting.  
Extreme caution is required when performing maintenance.  
Be constantly aware that the UPS system contains high DC as well as AC voltages. With  
input power off and the battery disconnected, high voltage at filter capacitors and power  
circuits should be discharged within 30 seconds. However, if a power circuit failure has  
occurred, you should assume that high voltage may still exist after shutdown. Check with a  
voltmeter before making contact.  
AC voltage will remain on the system bypass, the UPS output terminals and the static bypass  
switch, unless associated external circuit breakers are opened.  
Check for voltage with both AC and DC voltmeters prior to making contact.  
When the UPS system is under power, both the operator and any test equipment must be  
isolated from direct contact with earth ground and the UPS chassis frame by using rubber  
mats.  
Some components within the cabinets are not connected to chassis ground. Any contact  
between floating circuits and the chassis is a lethal shock hazard. Exercise caution that the  
test instrument exterior does not make contact either physically or electrically with earth  
ground.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Introduction  
1.0 INTRODUCTION  
1.1 System Description  
The role of the parallel-redundant multi-module UPS system is to supply uninterruptible, clean  
power to the critical load. The UPS maintains a full-voltage, low-distortion output, even if the utility  
source power sags, becomes distorted or fails.  
If there is an outage of the source power, the UPS maintains power to the load until an alternate  
source of power is activated or until the original power source is restored. If input AC power is not  
restored, the UPS maintains the load (with a storage battery plant) long enough that the critical  
equipment can be shut down in an orderly manner or an alternate power source (e.g., Genset) can be  
brought on line. The Series 610 UPS module displays the rate of battery discharge and calculates the  
amount of battery time remaining based on the actual connected load. The time that the battery will  
maintain the load depends on the capacity of the battery backup plant and the size of the load.  
The system control logic automatically manages critical bus operation. System logic is resident in dig-  
ital control logic for precise control and improved reliability.  
If the critical load current exceeds the rated load of the Series 610 UPS system, the control logic deter-  
mines the magnitude of the overload and reacts appropriately. Overloads are usually the result of  
inrush current requirements. The UPS system supports loads that are 150% of the rated load for up  
to 30 seconds and 125% of the rated load for up to 10 minutes. If the system is operating in the non-  
redundant mode (e.g., a UPS module is off line), the overload limits are automatically adjusted.  
Figure 1 Multi-Module UPS, 100-500kVA  
100-500kVA  
If the load surpasses the overload capacity of the UPS, the load is automatically transferred to bypass  
without interruption. When the load returns to within the UPS rating, it is either automatically or  
manually returned (retransferred) to the UPS. How and when the load is returned to the UPS  
depends on several factors: how long the overload lasted, how many overload conditions occurred  
before transfer, whether there is an imminent failure of any part of the UPS, etc. Refer to 3.5 - Auto-  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Introduction  
In the unlikely event of a fault within the UPS, the SCC control logic, which continuously monitors all  
critical circuits within the UPS system, transfers the load to bypass without interruption and simul-  
taneously activates local and remote alarms. If a fault is detected in an individual UPS module, that  
module is automatically disconnected from the critical bus and shut down. A Module Off Line status  
message will appear at the SCC display. The module can be manually returned to service when the  
fault has been corrected.  
If the multi-module UPS system is operating in the redundant mode (at least one extra module is  
available for the connected critical load), the load will remain on the UPS system if one individual  
module is disconnected from the critical bus (off line). If the UPS system is operating in the non-  
redundant mode, the load will be automatically transferred to bypass if a module goes off line.  
The Series 610 UPS display system provides precise monitoring of the UPS, fast alarm response and  
quick troubleshooting. For easy manual operations, menu-driven software provides access to several  
step-by-step help screens. All operator functions are performed using menu-prompted displays and a  
minimum number of operator controls. The System Control Cabinet includes external communication  
capability with both automatic transmit and receive features for early warning and diagnosis of  
abnormal conditions.  
System software allows the operator or Liebert Global Services to enter application specific informa-  
tion. Overload, overvoltage, battery discharge and shutdown limits can be set by the operator. In  
effect, UPS operations are tailored for each site.  
The UPS system protects critical equipment from source power disturbances and outages, load faults  
and UPS malfunctions. This triple protection virtually eliminates computer and computing equip-  
ment downtime as a result of utility source power problems.  
Figure 2 Multi-Module UPS, 500-750kVA  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Introduction  
Figure 3 System Control Cabinets  
Types of System Control Cabinets (SCCs)  
SCCT—A stand-alone cabinet containing system control logic for up to six UPS modules, a static  
bypass switch, manually operated disconnects for the static bypass switch and two motor-oper-  
ated system circuit breakers.  
SCCI—System control logic and static bypass switch are integrated into a switchboard cabinet  
manufactured by others, which also includes the system circuit breakers.  
SCCC—An integrated configuration like the SCCI, but with a static switch rated for continuous  
duty.  
1.2  
Reliability  
Reliability is the most important design goal for Uninterruptible Power Systems. Liebert Series 610  
UPS systems have demonstrated reliability by achieving a field-proven critical bus MTBF in excess of  
2 million hours. In addition, our Quality Assurance program is certified to the requirements of  
ISO 9001 standards.  
Liebert Large UPS systems are ETL listed to the requirements of UL 1778. All equipment and compo-  
nents are manufactured to applicable UL, NEC, NEMA, ANSI, IEEE and CSA standards and guide-  
lines.  
Designed for Success  
The keys to reliability in the design of the UPS system are using conservatively rated components,  
minimizing transfers to bypass, making operator controls understandable and providing easy access  
for maintenance and repair. Liebert UPS systems lead the industry in all these areas.  
For example, the Series 610 can handle substantial overloads through the solid state static bypass  
switch without transferring to the bypass source. By minimizing transfers to bypass, the Series 610  
minimizes operation of motor-operated circuit breakers and enhances system reliability.  
As another example, the system control logic has been packaged into digital control logic to eliminate  
the failure-prone discrete logic boards used in other brands of UPS products. Furthermore, the logic is  
isolated from heat-generating components to ensure optimal operating temperatures.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Introduction  
Other Factors to Consider  
Reliability depends on more than just UPS module design. Improper installation can cause any sys-  
tem to fail. To prevent this, customer engineers from Liebert Global Services thoroughly inspect the  
installation of all our systems to ensure they are installed properly and operating within performance  
specifications.  
Once a UPS is properly installed, you—the on-site equipment operator—are the most important fac-  
tor in preventing critical bus failures or unplanned transfers to bypass. To make your task easier, the  
Series 610 UPS provides easy-to-follow, prompted instructions on the industry’s largest operator dis-  
play screen.  
If you ever need help, call Liebert Global Services (24 hours a day at 1-800-LIEBERT). Your attention  
to proper installation, operation and periodic maintenance will ensure that your mission-critical oper-  
ations receive the best possible protection from electrical disturbances and outages.  
1.3  
Safety Precautions  
Read this manual thoroughly, paying special attention to the sections that apply to you, before work-  
ing with the UPS. Also refer to the battery manufacturer’s manual, available on the manufacturer’s  
Web site, before working on or near the battery.  
Under typical operation and with all UPS doors closed, only normal safety precautions are necessary.  
The area around the UPS system and battery should be kept free from puddles of water, excess mois-  
ture or debris.  
Special safety precautions are required for procedures involving handling, installation and mainte-  
nance of the UPS system or the battery. Observe precautions in the separate Installation Manual  
before handling or installing the UPS system. Observe precautions in 4.0 - Maintenance before as  
well as during performance of all maintenance procedures on the UPS system or battery. Observe all  
battery safety precautions in 4.0 - Maintenance before working on or near the battery.  
This equipment contains circuitry that is energized with high voltage. Only test equipment  
designated for troubleshooting should be used. This is particularly true for oscilloscopes. Always  
check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when  
the power is turned Off, dangerously high voltage may exist at the capacitor banks. Observe all bat-  
tery precautions when near the battery for any reason.  
ONLY qualified service personnel should perform maintenance on the UPS system. When  
performing maintenance with any part of the equipment under power, service personnel and test  
equipment should be standing on rubber mats. The service personnel should wear insulating shoes for  
isolation from direct contact with the floor (earth ground).  
Unless all power is removed from the equipment, one person should never work alone. A second per-  
son should be standing by to assist and summon help in case an accident should occur. This is partic-  
ularly true when work is performed on the battery.  
1.4  
Modes of Operation  
Refer to 2.0 - Theory of Operation and 3.0 - Operation for more details.  
1.4.1 Normal—Load on UPS  
The utility AC source provides power to the rectifier/charger in each UPS module. Each rectifier/  
charger converts the utility AC power to DC and supplies DC power to the UPS module inverter while  
simultaneously float charging the battery plant. Each UPS module inverter converts DC to AC and  
furnishes AC power to the critical bus. The System Control Cabinet (SCC) is the tie point for the par-  
alleled modules and monitors and controls the critical bus performance.  
1.4.2 Input Power Failure  
If the utility source power fails or is outside the acceptable range, the battery plant becomes the pri-  
mary supplier of DC power to the inverter.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Introduction  
1.4.3 Recharge  
After the utility source power is restored or an alternate power source becomes available, each recti-  
fier/charger slowly walks-in to once again power the inverters and recharge the battery plant.  
1.4.4 Overload  
Overloads in critical systems may be caused by inrush currents during connected equipment start-up  
or by faults in the critical load or distribution network. The Liebert Series 610 UPS system can main-  
tain full output voltage regulation while sustaining the following overloads:  
• Up to 150% for 30 seconds  
• Up to 125% for 10 minutes  
• Up to 104% for an indefinite period of time  
For momentary faults above 155% of rated SCC current, the static switch turns on for 40 milliseconds  
to supply power from the bypass source. Up to 1000% of the rated current can be supplied for less  
than one cycle, while up to 500% of rated load can be sustained for the full 40 milliseconds of pulsed-  
parallel operation.  
The critical load remains on the UPS modules for the above conditions. If the UPS system overload  
capacity is exceeded, an automatic transfer to bypass is initiated, which closes the system bypass cir-  
cuit breaker (SBB) and opens the UPS output circuit breaker.  
CAUTION  
!
Whenever an overload occurs, it is imperative to determine the cause of the overload.  
1.4.5 Redundant  
If the multi-module UPS system includes one more module than the number required to supply the  
critical load, the UPS system can operate in the redundant mode. This means that the load will  
remain on the UPS system if one of the modules is disconnected because of an overload, an internal  
fault or for maintenance. If the additional module is not included in the system design or if the addi-  
tional module is disconnected from the critical bus, the UPS system operates in the non-redundant  
mode.  
1.4.6 Bypass—Internal  
The SCC control logic initiates an automatic transfer to the bypass source if the overload-current-ver-  
sus-time curve is exceeded or if specified UPS system faults occur. You can also manually transfer the  
load to the bypass (without interruption) if you must take the UPS module out of service for mainte-  
nance.  
The SCC internal bypass will allow most key components and operating modes to be checked without  
disturbing the critical bus. However, certain key power-carrying components, such as the output and  
bypass circuit breakers, will require isolation through an external maintenance bypass cabinet or  
complete system shutdown to maintain 100% critical load operation.  
1.4.7 Maintenance Bypass  
The installation of a Maintenance Bypass Cabinet, Panelboard or Switchboard is recommended to  
allow you to totally isolate the UPS from all power sources. Use of the Maintenance Bypass is  
described in 3.0 - Operation.  
1.4.8 Off-Battery  
The battery plant can be disconnected from the rectifier/charger by using an external Module Battery  
Disconnect (MBD) circuit breaker. The UPS module continues to function normally, though it does  
not have power outage back-up capability until the battery plant is reconnected.  
1.5  
Operator Controls  
The Liebert Series 610 UPS System Control Cabinet (SCC) and each individual module are equipped  
with a microprocessor-based Operator Display Screen and Control Panel designed for convenient and  
reliable operation.  
The front panel location of the monitoring and control system enables the user to quickly identify the  
current status of the UPS and to perform most of the manual operations. The operator display screen  
(a backlit liquid crystal display or LCD) is driven by an easy-to-follow menu-prompted software pro-  
gram that controls and monitors the UPS system.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
Introduction  
Figure 4 SCC controls and display screen with example of the Monitor/Mimic screen  
© 1989-2003  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Introduction  
The operator controls and Monitor/Mimic screen for the System Control Cabinet (SCC) are shown in  
Figure 4. The controls and display screen for each UPS module are shown in Figure 5. Each cabinet  
(SCC or module) has the displays and controls required to monitor and perform its functions.  
Figure 4 shows a three-module system designed for redundant operation. A multi-module UPS sys-  
tem may include up to six (6) modules for each SCC.  
Detailed instructions on how to interpret the displays and use the controls are in 3.0 - Operation.  
Figure 5 Module controls and display screen with example of the Monitor/Mimic screen  
© 1989-2003  
1.6  
Options  
A number of options are available from Liebert for your UPS system. (Some options are not available  
for all ratings.) Described below are the most frequently provided options. Note that the battery items  
( 1- 3) are required to complete the UPS system. The remaining options provide improved system per-  
formance or convenience. Other options are available. Contact your Liebert sales representative for  
more information.  
1. Battery  
The batteries provide power in the event of a power outage. The Liebert UPS can use a variety of  
battery types, provided the battery plant is designed for the UPS DC voltage range and the load  
requirements of your application.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Introduction  
2. Battery Racks or Cabinets  
The battery racks are specifically designed for stationary service batteries. They are painted with  
electrolyte-resistant paint for corrosion resistance. Battery cabinets are available for 150 through  
600kVA modules.  
3. Module Battery Disconnect  
The UPS system utilizes a separate Module Battery Disconnect for remotely located batteries. A  
sensing circuit in the UPS module, set at the battery low voltage limit, trips the Module Battery  
Disconnect to safeguard the battery from excessive discharge. The Module Battery Disconnect has  
an undervoltage release mechanism designed to ensure that during any shutdown or failure mode  
all battery potential is removed from the UPS system.  
4. Input Current Distortion Filter  
This filter reduces rectifier input current reflected harmonic distortion to less than 7% reflected  
THD and less than 4% reflected THD for modules with the optional 12-pulse rectifier. The filter is  
factory installed within the UPS. This filter also improves the input power factor to better than  
0.92 lagging.  
5. 12-Pulse Rectifier  
All 500-750kVA models may be ordered with the optional 12-pulse rectifier section; this feature is  
standard in 1000kVA models. This provides input isolation and reduces input current reflected  
THD to less than 9% or less than 4% with optional input filter.  
6. Isolation Transformers  
An optional rectifier input isolation transformer is available in a matching transformer cabinet;  
this feature is standard in 1000kVA models. A bypass isolation transformer is also available.  
7. Three Breaker Maintenance Bypass  
This switchboard provides make-before-break maintenance bypass. It includes: UPS Bypass  
Input Breaker (BIB), Maintenance Bypass Breaker (MBB) and Maintenance Isolation Breaker  
(MIB).  
8. Two Breaker Maintenance Bypass  
This switchboard provides make-before-break maintenance bypass. It includes: Maintenance  
Bypass Breaker (MBB) and Maintenance Isolation Breaker (MIB).  
9. Load Bus Synchronization (LBS)  
The Load Bus Sync (LBS) option keeps two independent UPS systems (and therefore their critical  
load buses) in sync, even when the modules are operating on batteries or asynchronous AC  
sources. This means that critical loads connected to both load buses through a Static Bus Transfer  
Switch can be switched seamlessly between the two.  
10. SiteScan Central Monitoring System  
Liebert manufactures a central monitoring system that automatically displays key UPS measure-  
ments and alarms, as well as data from a variety of sensors. This monitoring system activates  
alarms so corrective action can be taken. Events and data can be printed in hard copy. Data can  
be logged for analysis.  
11. Remote Monitor Panel  
The UPS system may also be provided with an optional Remote Monitor Panel. This Panel pro-  
vides eight LED indicators and may be placed at a convenient location near the critical load. A  
functional description of the Remote Monitor Panel is provided in 3.0 - Operation of this manual.  
12. Customer Alarm Interface  
This optional interface board allows the input and display of 8 alarms from customer-supplied  
contacts, each with a customer-selected name of up to 16 characters. The following attributes can  
be user programmed for each alarm: latching, summary, freeze history, sound horn, auto-dial and  
time delay (0 to 999.9 seconds).  
13. Temperature-Compensated Charging  
When battery temperature climbs above a preset limit (typically 77 degrees F), this optional cir-  
cuit proportionally reduces float charging voltage to prevent overcharging the battery.  
14. Battery Load Testing  
When activated, this option forces the battery string to assume the load for a short period of time.  
The UPS then compares the test results to data collected during the UPS commissioning to see if  
the battery system appears to meet specifications.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Theory of Operation  
2.0 THEORY OF OPERATION  
2.1 General Component Descriptions  
The UPS system includes all of the equipment necessary to continuously provide computer-grade AC  
power to a critical load, even when there is an interruption of the utility power. It consists of a System  
Control Cabinet (SCC), UPS modules and a back-up battery plant. Refer to Figure 6 and Figure 7.  
Except where otherwise noted, the configuration is presumed to be parallel-redundant (with at least  
one more UPS module than required to support the rated load).  
2.1.1 System Control Cabinet  
The System Control Cabinet (SCC) includes system controls, static bypass switch, load transfer con-  
trol, protective devices and other accessories. The system controls simultaneously monitor two or  
more parallel UPS modules sharing a critical load for increased capacity and/or redundancy. The two  
(2) motor-operated system circuit breakers (system bypass breaker—SBB and UPS output breaker)  
may be contained within the SCC, depending on the configuration designed for your installation.  
System Controls: The system control logic automatically manages critical bus operation and moni-  
tors performance of the UPS modules. Microprocessor technology and dedicated firmware provide  
advanced logic control and a comprehensive display of information. The system control logic synchro-  
nizes the output of the UPS system to the bypass source. The SCC includes ports for communicating  
with external devices. Liebert Multi-Module Units do not require an SCC for load sharing. Automatic,  
parallel module load sharing is a function built into the modules themselves; however interconnection  
through the SCC enables the modules to share data for more precise control. Modules do not require  
master clocks or controls in order to load share or free-run at 60.0 Hz.  
Static Bypass Switch: The static (solid-state) bypass switch immediately transfers the load from  
the inverter to the bypass AC power source in the event of a severe overload on the system or a failure  
within the UPS. This transfer takes place without any interruption of the power supplied to the load.  
In all SCCT control cabinets 1600A or larger and in all SCCI and SCCC control cabinets, the system  
includes redundant circuits to detect and isolate shorted SCRs in the static switch.  
Fuses are installed in series with the static bypass circuit (with the exception of the continuous duty  
static switch installed in the SCCC control cabinet) to ensure reliable overload protection in the  
unlikely event of a catastrophic output condition (e.g., a dropped wrench) electrically close to the out-  
put of your UPS system. The static switch SCRs themselves are rated to easily handle the fuse-blow-  
ing current.  
Bypass Circuit: The bypass circuit consists of electrically operated circuit breakers and associated  
synchronizing and control circuitry to transfer the load to/from the bypass source.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Theory of Operation  
Figure 6 UPS module block diagram  
MULTI-MODULE UPS SYSTEM  
Control  
Wiring  
To SCC  
CONTROL POWER  
Controls  
Utility  
Input  
Output  
Power  
Rectifier/  
Charger  
Inverter  
Output  
CB  
Power  
Input  
CB  
To SCC  
Battery  
MBD  
CB - Circuit Breaker  
MBD - Module Battery Disconnect  
SCC - System Control Cabinet  
2.1.2 UPS Module  
The UPS module consists of module controls, a rectifier/charger, an inverter, protective devices and  
other accessories.  
Module Controls: The module control logic monitors performance of the UPS module. The UPS  
module status is displayed locally and is also sent to the System Control Cabinet.  
Rectifier/Charger: The rectifier/charger converts utility power from AC to DC to charge the battery  
and provide the DC input to the inverter. Its design limits reflected harmonic current distortion to  
source power and provides low-ripple DC power for charging batteries. Multiple rectifier/chargers can  
share a common battery plant, if that configuration is preferred for your application.  
Inverter: The inverter converts DC power into the precise AC power required to supply a sensitive  
critical load. The inverter converts DC power into a pulse-width-modulated (PWM)/six-step waveform  
that is easily filtered into a clean sine wave output. The PWM/stepwave also minimizes the harmonic  
voltage distortion caused by typical switching power supplies and other non-linear load components  
used in computers and related electronics.  
2.1.3 Battery Plant  
The battery is used as the alternate source of power to supply DC power to the inverter if the AC sup-  
ply voltage is outside the acceptable range. The battery supplies power to the inverter until the utility  
power is restored or until an alternate power source is available. If AC source power is not restored or  
an alternate power source is not available, the battery can be sized to provide power long enough for  
an orderly shutdown of the load.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Theory of Operation  
2.2  
Detailed Component Descriptions  
2.2.1 Controls  
Hardware  
The Series 610 UPS Operator Interface Display System is designed to provide all of the information  
that is required for the operation of each UPS cabinet (the System Control Cabinet and each module).  
The following is a list of the hardware features:  
1. The control logic performs automatic operations with minimal operator interface. The limited  
number of manual controls are easy-to-use.  
2. Each Series 610 UPS cabinet is equipped with an easy-to-read 640 x 200 pixel backlit liquid  
crystal display (LCD) screen. It presents information in a way that is easy to understand at an  
eye-level front panel location.  
3. The display is controlled by a dedicated microprocessor with a flash-updatable program, non-  
volatile static RAM and a battery-backed system clock.  
4. The Series 610 System Control Cabinet (SCC) has communication ports (terminal board  
connections) for:  
a. Transmission of present status information to remote terminals via a resident auto-dial  
communications program and an optional internal or external modem. This port also  
responds to inquiries of the UPS system status and history from the remote terminal.  
b. Reporting UPS system status and history information in response to inquiries from a local  
terminal (no modem required).  
c. Reporting to a local monitor the information requested from the local terminal.  
d. Reporting information to a Liebert SiteScan central monitoring system.  
e. Relaying selected alarm messages to a Liebert Remote Monitor Panel and to a separate  
terminal board for customer use.  
f. Relaying performance and status information to your network monitoring system via SNMP  
interface (optional).  
Software  
The operator interface display system software enables the operator to monitor the UPS system sta-  
tus, to control the power flow through the UPS, to monitor all of the meter readings, to execute the  
start-up, shutdown and load transfer procedures, to access the event history files and to make adjust-  
ments to the programmable parameters. The following is a list of the software features:  
1. The menu-driven software prompts the operator for input.  
2. Step-by-step instructions assist the operator during the start-up, shutdown and load transfer  
procedures. This helps to eliminate operator errors.  
3. Graphics-based mimic diagrams illustrate circuit breaker status and the power flow through the  
UPS system.  
4. The Present Status screen reports information about the system’s present status. The History  
Status screen chronicles the events leading up to and immediately after a fault. The Event  
History screen lists all of the alarm messages that have been logged over a period of time.  
5. The Battery Cycle Monitor records information on up to 132 battery discharge events.  
Information includes date, time, length of discharge, highest current demand, lowest battery  
voltage and cumulative battery amp hours discharged.  
Refer to 3.0 - Operation for a description of the controls and indicators located on the Operator Con-  
trol Panel.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Theory of Operation  
2.2.2 Rectifier/Charger  
The UPS module rectifier/charger consists of an input circuit breaker, AC current limiting circuit,  
battery equalize charge circuit, DC filter, battery charge current limiting circuit and bridge rectifiers.  
Optional items are an isolation transformer and a 12-pulse rectifier (these are standard on 1000kVA  
units).  
Operation  
The rectifier/charger converts the AC input power to DC power. This conversion is accomplished by  
3-phase bridge rectifiers using SCRs. All phases are individually fused. Input current reflected THD is  
less than 7% at full load with optional input filter or 30% without. For modules 500kVA and larger, the  
optional 12-pulse rectifier reduces reflected THD to less than 4% with optional filter or 9% without.  
The filtered output of the rectifier/charger provides regulated DC power to drive the inverter and  
charge the battery.  
Input Circuit Breaker  
The input circuit breaker (CB1) is sized to allow enough current to recharge the battery and supply a  
full rated load at the same time. The circuit breaker contains a thermal magnetic trip mechanism and  
an undervoltage release that interrupts power, preventing damage to the system, if there is an inter-  
nal AC overcurrent condition or a short circuit. The circuit breaker also opens during certain alarmed  
faults. This circuit breaker must be closed manually.  
Isolation Transformer  
The optional input isolation transformer—standard with 1000kVA models and with the 12-pulse rec-  
tifier option—has a dry type core and copper windings with Class H insulation. The transformer on  
modules with standard 6-pulse rectifier has wye primary and delta secondary windings. For models  
with the optional 12-pulse rectifier, the transformer has a delta primary, with delta and wye second-  
ary windings. The isolation transformer provides the initial step of critical bus isolation. This reduces  
the AC shock hazard at the battery and at other DC components and prevents a DC fault from dis-  
rupting upstream AC circuitry.  
The transformer has a nominal tap and one tap 6% below the rated nominal input voltage (normally  
used for 460 VAC input).  
Input Current Limit  
AC input current-sensing transformers (CTs) are used to measure current levels. Control circuitry  
connected to the CTs restricts the AC current to less than 125% of the full input current rating by  
reducing the battery charging voltage. This current limit is adjustable from 100 to 125% and is fac-  
tory-set at 115%.  
An optional second level of input current limit is initiated by an external contact closure (field sup-  
plied for use with back-up generator) and is adjustable from 85 to 100% (factory-set at 100%). This  
second level of input current limit may be used to set the maximum amount of input current permit-  
ted under all operating conditions of connected load and battery recharge.  
During a start-up procedure, the current slowly ramps up (walks-in) from 20% of the rated input cur-  
rent to 100% over 15 to 20 seconds. The maximum rate of change of the AC input current is 15% per  
second. The input current walk-in reduces the start-up surge effects on all other equipment connected  
to the same source and prolongs the service life of internal components.  
Input Current Inrush  
The maximum sub-cycle of inrush current due to the optional input isolation transformer is typically  
less than five times the rated input current for the first 1/2 cycle with the optional input filter. With-  
out this transformer, inrush current is typically less than three times nominal.  
Input Power Factor  
The rated input power factor is not less than 0.85 lagging at the nominal input voltage and the full  
rated UPS load. The optional input filter will improve the power factor to better than 0.92 lagging at  
full load. Refer to your submittal package or installation drawings in the installation manual for your  
specific model.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Theory of Operation  
2.2.3 Battery Charging Circuit  
The UPS module charging circuit is capable of recharging the battery plant to 95% of full capacity  
within 10 times the discharge time. Recharging the last 5% takes longer because of characteristics  
inherent in the battery. DC ripple voltage is limited to less than 0.5% RMS to preserve battery life  
during long-term float charging while the UPS system is operating on utility source power.  
Multiple UPS module rectifier/chargers can share a common battery plant, if that configuration is  
preferred for your application.  
Operation After Discharge  
When commercial power is interrupted, the battery continues to supply DC power to the inverter  
without interruption to the critical load. If the AC source power is restored before the battery has  
fully discharged, the rectifier automatically restarts and resumes carrying the inverter and battery  
recharge load requirements.  
Operation After End-of-Discharge  
The battery time screen displayed on the control panel enables you to estimate when battery shut-  
down will occur. If the battery plant discharges to the shutdown point during an outage, the UPS  
automatically disconnects the load, the AC input and the battery. After AC input power is restored,  
the rectifier can be manually restarted by the user.  
Battery Disconnect  
The external module battery disconnect (MBD) circuit breaker is used to isolate the UPS module from  
the battery during maintenance and to automatically disconnect the battery from the inverter at the  
end of battery discharge. The MBD circuit breaker can be opened or tripped automatically, from the  
control panel or manually. It must be closed manually.  
Battery Charge Current Limiting  
The battery recharge current, after a battery discharge, is limited to between 1 and 25% (adjustable)  
of the full load discharge current. An additional (optional) charge-limiting circuit can be activated by  
external dry contact closure (field supplied) for use when operating on a back-up generator. These two  
levels of control regulate the amount of current that flows from the power source to the battery while  
the battery is recharging.  
The battery charge current limit is factory-set at 10% for normal operation and at 1% for alternate  
power source recharge operation.  
Battery Equalize Charge Circuit  
The battery equalize charge feature can be manually initiated or it can be programmed to operate  
automatically. Either can be selected from the battery equalize screen displayed on the control panel.  
The battery equalizing charge circuit increases the rectifier/charger output voltage to charge the bat-  
tery any time there is a power outage of 30 seconds or longer. The equalizing voltage is slightly higher  
than the float voltage. Equalize charging is primarily used in flooded battery systems to boost individ-  
ual cells that are at a low state of charge, per the battery manufacturer's specification and recommen-  
dations.  
NOTE  
Do not use equalize charging with valve-regulated lead-acid batteries.  
Consult the battery manufacturer’s manual, available on the manufacturer’s Web site, for  
specific information about equalize charging.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Theory of Operation  
2.2.4 Inverter  
The inverter is a solid state device that converts the DC output of the rectifier/charger or the battery  
to AC power.  
Operation  
The inverter converts DC power—from either the battery or the rectifier/charger—into three pulse-  
width-modulated/six-step waveforms. These waveforms are filtered into low-distortion sine wave  
power. The inverter is controlled by digitally controlled logic. This logic controls the precise synchro-  
nization, amplitude and frequency of the output voltage.  
In addition to the inverter efficiently supplying a regulated AC output from a DC source, the output  
isolation transformer acts as a second stage of isolation between the critical load bus and the commer-  
cial source power. The inverter is configured to handle most critical load inrush surges. It maintains  
output voltage Total Harmonic Distortion (THD) within specifications even when handling non-linear  
computer loads. Refer to Non-Linear Load Characteristics.  
Output Regulation and Overload Performance  
The inverter is capable of sustaining full output voltage (±2% of the nominal voltage) for up to 150%  
overload at the output for as long as 30 seconds without reducing the output voltage. It can also han-  
dle at least 125% of the rated current for up to 10 minutes and 104% of the rated current continu-  
ously. The System Control Cabinet (SCC) will transfer the critical load to the bypass source if the  
overload exceeds the system capacity or the capacity of the modules on-line. The multi-module over-  
load capacity (in terms of percent of rated full load current of modules on-line) is 140% for 20 seconds,  
108% for 10 minutes and 104% continuously.  
Note that in normal operation the SCC will transfer the load to bypass before a UPS module exceeds  
its overload capacity. If an individual module overload condition is sustained (beyond inverter capac-  
ity) the UPS module is automatically taken off-line (disconnected from the critical bus) and is shut  
down. If the UPS system is operating in the redundant mode, the load may remain on the UPS sys-  
tem. Refer to 3.5 - Automatic Operations.  
Non-Linear Load Characteristics  
Computers and computer equipment with switching power supplies generate non-linear currents rich  
in fifth and seventh harmonics.  
The inverter pulse-width-modulated/six-step waveform, coupled with the output filter, provides a nat-  
ural path for reducing the fifth and seventh harmonic currents produced by the load. The inverter/fil-  
ter limits the output voltage THD to less than 5% with up to 100% typical electronic data processing  
(EDP) loads. EDP equipment characteristically includes both non-linear and linear load components.  
Unbalanced Load Characteristics  
Unbalanced loads are actively regulated. The phase-to-phase voltage balance is maintained to within  
2%, even with a 50% load imbalance.  
The three-phase, root mean square (RMS—approximately 70% of the peak) average voltage is also  
regulated through a separate control circuit (phase-to-phase sensing).  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Theory of Operation  
2.2.5 Static Bypass  
A static bypass is an integral part of the UPS System Control Cabinet (SCC). Refer to Figure 7. The  
static bypass consists of two reverse-paralleled SCRs (silicon-controlled rectifiers) per phase and  
solid-state switching devices working in conjunction with the motor-operated System Bypass Breaker  
(SBB). An automatic transfer control circuit senses the status of the operator controls, UPS logic sig-  
nals and alarm messages and critical bus operating conditions. If the UPS modules can no longer sup-  
ply the critical load, the static bypass switch (in conjunction with the SBB and UPS Output Breaker)  
automatically transfers the critical load to the bypass source without interruption.  
Figure 7 System Control Cabinet block diagram  
Gate  
Driver  
Static  
Bypass  
Switch  
Static Switch  
Disconnects  
Static Bypass Breaker  
Bypass Line  
Sync &  
Transfer  
Control  
Power  
Supply  
Transfer  
Control  
UPS  
System  
Modules  
System  
Monitor  
Voltage  
Adjust  
Alarms  
To Critical  
Load  
UPS Output  
Fuse Protection  
The static bypass switch path uses two back-to-back SCRs per phase. Each phase is individually pro-  
tected by a fuse sized to clear only in the event of a catastrophic fault (with the exception of the con-  
tinuous duty static switch used in the SCCC control cabinet). This is a more reliable method than  
depending on external protection devices. The fuses are in the circuit to protect the critical bus distri-  
bution equipment against catastrophic faults. The static switch SCRs are oversized to easily handle  
any current surges that may blow the fuses.  
Shorted SCR Monitoring  
In all SCCI and SCCC control cabinets, and all SCCT control cabinets 1600A and larger, the static  
bypass system has redundant shorted SCR sensing circuits and disconnects. This will prevent UPS  
output power backfeed to the distribution system even if two component failures exist simulta-  
neously. If a shorted SCR is detected, the static bypass switch is isolated and annunciated at the SCC  
control panel, and the critical load remains on UPS output power.  
In all SCCT control cabinets smaller than 1600A, the static bypass system is equipped with redun-  
dant disconnect circuits that prevent backfeed of lethal voltage to a de-energized bypass input in the  
event of a shorted static switch SCR. If the bypass input power is interrupted, the static switch dis-  
connect devices will open, preventing backfeed of inverter voltage to the bypass input terminals.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Theory of Operation  
Static Switch Isolation  
The motor-operated system bypass circuit breaker (SBB), wired in parallel with the static switch,  
automatically closes in approximately 200 milliseconds after the load is transferred to the bypass  
power source, removing the static switch from the power flow.  
Also, if required for maintenance, the static switch can be isolated from the bypass line by opening (to  
the OFF position) the Static Switch Disconnects. For maintenance, this should only be done with the  
UPS system critical load on bypass power.  
Pulsed Parallel Operation  
When an overload condition such as magnetic inrush current or a branch load circuit fault exceeds the  
overload capacity of the connected modules, the static bypass switch pulses on for 40 milliseconds.  
This allows up to 1000% of the rated full load current from the bypass line to clear the overload with-  
out closing the bypass circuit breaker. The bypass source is briefly in parallel with the UPS system,  
permitting the bypass source to carry the initial overload current. If the overload clears before 40 mil-  
liseconds, a load transfer to bypass is not made. If the overload condition continues, the automatic  
transfer is made (maintaining the load voltage within the specified limits).  
This pulsed static switch operation reduces nuisance operation of motor-operated circuit breakers for  
such short-term conditions and serves, under some circumstances, as a backup in the event that an  
external bypass feeder breaker trips open during this pulse-paralleling period.  
Load Transfers  
Transfers to (transfer) or from (retransfer) the bypass may be performed automatically or manually in  
a make-before-break sequence. This is accomplished through the overlapping operation of the UPS  
output and the system bypass power switching devices.  
Manual load transfers and retransfers are initiated by the operator from the System Control Cabinet  
(SCC).  
In a manual operation or an automatic retransfer, the two motorized circuit breakers—UPS output  
and system bypass—are both closed simultaneously for a short period of time (overlap).  
Automatic transfers are initiated by the SCC system control logic when an overload is beyond the  
specified capabilities of the UPS system or when a fault occurs within a non-redundant UPS module.  
An automatic retransfer is initiated if this function is enabled and if system conditions for a retrans-  
fer are present.  
In an automatic transfer, the circuit breakers do not overlap, but, during the short time gap, bypass  
power is supplied to the critical load through the solid state static switch. In an SCCC control cabinet  
with a continuous duty static switch, if for some reason the Static Bypass Breaker (SBB) fails to close,  
the static switch will carry the load continuously.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Theory of Operation  
Transfer and Retransfer Conditions  
1. Automatic Transfers to Bypass  
Critical bus conditions that will initiate an automatic transfer of the critical load from the UPS  
system to the bypass source are:  
a. System Overload: overcurrent condition in excess of the overload rating of the System Control  
Cabinet (SCC).  
b. Output Overload: overcurrent condition in excess of the current-versus-time overload capacity  
of UPS modules ON LINE.  
c. Overvoltage/Undervoltage (OV/UV): critical bus voltage is outside the allowable tolerance.  
d. Non-redundant UPS Module Inoperative: an essential UPS module is taken OFF LINE for  
one of the reasons below.  
1. Battery discharged to the shutdown voltage.  
2. Inverter overload capacity exceeded.  
3. Inverter or rectifier fault condition (power, logic or overtemperature) present or  
imminent.  
4. Failure of UPS module logic or logic power.  
e. SCC Logic:  
1. Emergency Module Off (EMO) circuit activated.  
2. Failure of UPS system logic or logic power.  
2. Manual Transfers  
Manual transfers may be initiated at any time provided no transfer inhibition conditions are  
present.  
3. Transfer Inhibited  
A manual transfer to the bypass source will be inhibited if any of the following conditions exist:  
a. UPS system to bypass voltage difference (V) exceeds a predetermined percentage (normally  
5%).  
b. Static switch disconnects open.  
c. OK to Transfer signal from the control logic is not present.  
NOTE  
A load transfer to the bypass line will be completed whenever an automatic transfer to bypass  
is initiated. If the Static Switch Unable alarm message is present for any reason (including a  
±20° phase lock synchronization error), the automatic transfer will be interrupted for  
40-120 milliseconds. Because of the reliability of the UPS components, an interrupted load  
transfer is a very unlikely occurrence.  
4. Automatic Retransfers to UPS  
Critical bus conditions that must be present to initiate an automatic retransfer (Auto-Rexfer) of  
the critical load from the bypass source to the UPS system are:  
a. The number of Auto-Rexfer Attempts selected must be greater than zero (0). If zero (0) is  
selected, no automatic retransfer will occur.  
b. Critical load was initially transferred to the bypass source due to a system overload only.  
c. Overload has since dropped below 100% of the rated SCC current.  
d. Enough UPS modules are ON LINE to supply the critical load.  
e. OK to Transfer signal received from the control logic for at least 10 seconds, within 5 minutes  
of the overload transfer. (A manually initiated retransfer from bypass is required for  
overloads lasting 5 minutes or more.)  
f. Cyclic-type system overloads, which occur up to five (select range is 0 to 5) times in  
60 minutes, are automatically returned to the UPS system for each event including the Nth  
overload. A manually initiated retransfer from bypass is required for the N+1 overload.  
5. Manual Retransfers  
Manual retransfers may be initiated at any time provided no retransfer inhibition conditions are  
present.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Theory of Operation  
6. Retransfer Inhibited  
A retransfer from the bypass source to the UPS system shall be inhibited if any of the following  
conditions exist:  
a. Manual (and Automatic) Retransfer Inhibitions:  
1. UPS system-to-bypass voltage difference (V) exceeds a predetermined percentage  
(normally 5%).  
2. System circuit breaker (UPS output or SBB) is inoperative.  
3. OK to Transfer signal from the control logic is not present.  
4. Not enough UPS modules are ON LINE to supply the connected critical load.  
b. Automatic Retransfer Inhibitions (in addition to those above):  
1. The load transfer to bypass was not caused by a system overload.  
2. Excessive cyclical overloads within a one-hour period.  
3. Retransfer conditions are not satisfied within 5 minutes of the initial transfer.  
2.2.6 Redundant Mode  
The typical multi-module UPS system is configured with a back-up (redundant) UPS module, con-  
nected in parallel to share the critical load with the other module(s). This parallel redundant system  
includes one more module than is required to supply the full critical load.  
A parallel redundant system will always be in the Redundant Mode if all modules are ON LINE. In  
addition, if the critical load is reduced so that not all ON LINE modules are required, the UPS system  
can also operate in the Redundant Mode with one or more modules OFF LINE. The critical load will  
remain on the UPS system—even if one or more of the modules is taken OFF LINE for maintenance  
or because of an internal fault—as long as the remaining ON LINE modules can carry the full con-  
nected system load.  
The system control logic monitors the connected critical load and the number of UPS modules ON  
LINE. If the UPS system is operating in the Redundant Mode, the REDUNDANT status message will  
be displayed at the System Control Cabinet (SCC). If the UPS system is operating in the Non-Redun-  
dant Mode (redundant module is OFF LINE or was not included in the system configuration), the  
NON-REDUNDANT status message is displayed at the SCC. In the Non-Redundant Mode, the criti-  
cal load will be transferred to bypass if any UPS module goes OFF LINE and the remaining ON LINE  
module(s) cannot carry the connected load without being overloaded.  
The system control logic, located in the SCC, automatically adjusts the allowable overload limits  
based on the connected load and the number of modules ON LINE.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
3.0 OPERATION  
3.1 Display Screen and Operator Controls  
Each Liebert Series 610 UPS cabinet is equipped with a microprocessor-based Operator Control Panel  
and Display Screen and System Control Panel designed for convenient and reliable operation. The  
System Control Cabinet (SCC) performs different functions than the UPS modules. Each cabinet has  
the controls and displays required to operate and monitor its functions. The locations of operator con-  
trols are shown in Figure 8 through Figure 11.  
The front location of the control panel enables the user to quickly identify the current status of the  
UPS system and to perform most of the manual operations. The operator display screen is driven by  
an easy-to-follow menu-prompted software program.  
Features  
The Series 610 interface display system enables the operator to easily perform the following:  
• Obtain a quick indication of operational status:  
• Is the critical bus OK?  
• Is the UPS system OK?  
• Which UPS modules are available?  
• Is the battery available?  
• Is the bypass line available?  
• Monitor the power flow through the UPS system and monitor all meter readings:  
• Is the critical load being supplied power from the UPS system or bypass?  
• Are input, battery and output voltage, frequency and current readings at nominal levels?  
• How much battery time is still available during an outage?  
• Is the battery recharging after discharge?  
• Execute operational procedures:  
• Perform critical bus transfer/retransfer between the UPS system and the bypass line.  
• Start up and shut down the UPS system and each module.  
• Shut down the system and all modules instantly in the event of an emergency.  
• Access status reports and history files:  
• Obtain a complete listing of the present status of the UPS system and all modules (input, out-  
put and battery voltage, frequency and current readings and any alarms that may be  
present).  
• Review a complete history report of all events leading up to and immediately after a fault con-  
dition.  
• Examine an archive listing of all alarm conditions that have occurred over a period of time.  
• Make adjustments to programmable parameters (access limited by Security Access function):  
• Set the date and the time functions.  
• Change the auto-dial phone number and the modem options.  
• Select the number of auto-retransfer attempts.  
• Make adjustment to the UPS output voltage before performing a manual load transfer.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Figure 8 Typical operator controls  
2
100kVA-  
500kVA  
5
4
1000kVA  
3
5
2
1
Table 1  
Item  
Typical operator controls  
Description  
Function  
This manually operated circuit breaker provides power to the UPS module rectifier. In  
625-750kVA modules and some 500kVA modules, this breaker is located in the  
transformer cabinet.  
1
Input Circuit Breaker (CB1)  
Module Output Circuit  
Breaker (CB2)  
This manually operated circuit breaker connects the UPS module inverter output to the  
UPS System Control Cabinet.  
2
3
4
Operator Control Panel  
Refer to Figure 10 for controls available on this panel.  
Control Disconnect  
(behind inner door)  
These two fuses provide power to the controls. They are normally closed (ON). Turn  
Control Power OFF (by opening the two fuse holders) only for maintenance procedures.  
Interlock Button  
(on rear of Control Panel)  
Press this button to make authorized changes to any parameter protected by the  
Security Access function. This includes time, date, auto-dial phone numbers, etc.  
5
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Figure 9 Operator controls, typical SCCT System Control Cabinet  
Table 2  
Item  
Typical SCCT System Control Cabinet operator controls  
Description  
Function  
UPS Output Circuit  
Breaker  
This motorized circuit breaker connects the critical load to the UPS system  
output.  
1
System Bypass Circuit  
Breaker  
2
3
4
This motorized circuit breaker connects the critical load to the bypass line.  
Refer to Figure 10 for controls available on this panel.  
Refer to Figure 11.  
Operator Control Panel  
Interlock Button  
(on rear of Control Panel)  
Close Bypass Switch  
(behind door)  
5
6
Refer to Figure 11.  
Bypass Reset Switch  
(behind door)  
Refer to Figure 11.  
These manually operated switches disconnect the static switch from the  
bypass line and from the critical load. They are normally ON (closed). Turn  
them OFF (open) only to isolate (disconnect) the static switch for  
maintenance procedures. For SCCT less than 1600A, the static switch  
disconnects are contactors that open automatically upon loss of bypass input  
power and close automatically when bypass power is restored. Control power  
fuse disconnects are used to manually open the contactors for maintenance.  
Static Switch Disconnects  
(behind door)  
7
Press these two switches before closing Static Switch Disconnects when  
recovering from a shutdown that includes loss of Control Power. Green LED  
on means Control Power is available. Red LED on means Reset Switch  
needs to be pushed. Only SCCI and SCCC control cabinets and SCCT  
1600A and larger.  
Reset Switches (SW1) for  
Static Switch Disconnects  
(behind door)  
8
9
Control Power Disconnect  
(behind door)  
Normally ON. Fuseblocks that are labeled F7 through F10. Turn OFF Control  
Power only when required for maintenance procedures.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Figure 10 Series 610 UPS and SCC operator control panels  
Numbers are used  
as keys to data in  
Table 3, below.  
Table 3  
Series 610 UPS and SCC operator control panels  
Item Description (Location)  
Function  
Display Screen  
1
This screen displays all vital UPS information in one convenient location. All of the  
UPS monitoring functions and conditions are indicated here.  
(SCC and modules)  
This touch-sensitive pad (button) is used to move the cursor up through various  
selections present on the display screen. Note that all pads on this control panel  
have touch-sensitive switches behind them.  
Up  
2
(SCC and modules)  
Down  
(SCC and modules)  
Similar to the Up pad, this pad is used to move the cursor down through the  
various selections present on the display screen.  
3
After choosing the desired item (with highlighted cursor) from the display screen  
with the Up and Down pads, pushing this pad tells the microprocessor to go to the  
highlighted selection.  
Select  
(SCC and modules)  
4
This pad is used to clear all of the alarm conditions that are no longer present.  
However, all active alarms remain in memory and on the applicable screens until  
they are corrected.  
Alarm Reset  
5
(SCC and modules)  
This push-to-turn knob permits adjustment of the UPS output voltage to meet load  
requirements or to match the bypass voltage before transferring the load to or from  
bypass.  
Voltage Adjust  
(SCC only)  
6
This pad activates the circuits that connect the UPS to the critical load (a  
retransfer). When this pad is pushed (along with Control Enable), the UPS output  
circuit breaker closes and the bypass circuit breaker opens.  
UPS  
7
(SCC only)  
This pad activates the circuits that connect the bypass line to the critical load (a  
transfer). When this button is pushed (along with Control Enable), the bypass  
circuit breaker closes and the UPS output circuit breaker opens.  
Bypass  
8
(SCC only)  
Control Enable  
9
This pad must be pressed simultaneously with the UPS, Bypass, Battery Trip or  
Output Trip pads to activate them.  
(SCC and modules)  
This pad is used to silence the alarm horn after it is activated. When this switch is  
pressed, the alarm horn is silenced but the active and latched alarm messages  
remain on the screen. The alarm messages still displayed stop flashing to indicate  
they have been acknowledged.  
Horn Off  
10  
(SCC only)  
Alarm Horn and  
11  
This electronic horn sounds to alert nearby personnel whenever a new alarm  
occurs. A red LED (light emitting diode) is located in the middle of the alarm horn.  
Red LED (SCC only)  
During an emergency, pressing this guarded switch will transfer the load to bypass  
and then shut down the UPS modules. The load will remain on bypass power.  
Emergency Module  
Off (SCC only)  
12  
This pad can be used (along with Control Enable) to trip the module battery  
disconnect (MBD) circuit breaker open (disconnecting the battery from the UPS  
module).  
Battery Trip  
13  
(modules only)  
Output Trip  
14  
This pad can be used (along with Control Enable) to trip the module output circuit  
breaker open (disconnecting the module from the UPS system).  
(modules only)  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Figure 11 Switches behind SCC control panel door  
Numbers are used  
as keys to data in  
Table 4, below.  
Table 4  
Item  
Series 610 UPS and SCC operator control panels  
Description (Location)  
Function  
Press this button to make authorized changes to any site parameter protected  
by the Security Access function. These include the time, date, auto-dial phone  
number and other site parameters.  
Interlock Button  
(on rear of Control Panel)  
1
2
Bypass Reset Switch  
(SW1, on Transfer  
Relay Board)  
Press this button to reset the transfer relays during start-up, after an  
Emergency Power Off shutdown. You must press this button before the Close  
Bypass Switch (Item 3).  
Press this button to close the Bypass circuit breaker during a start-up  
procedure, if it remains open after a shutdown procedure (refer to 3.4.1 - SCC  
Start-Up Procedure). Note that the Static Switch Disconnects must be OFF to  
reset the Bypass circuit breaker. See also Bypass Reset Switch (Item 2).  
Close Bypass Switch  
(SW1, on System  
Interface Board)  
3
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operation  
3.2  
Menu Tree Navigation  
The Operator Interface Display is a blue-background display with white text. The display is always  
on, but the backlight will remain lit for 15 minutes following any display activation. After 15 minutes,  
the backlight will go out and the display may appear very dim. To reactivate the backlight, push any  
key. The backlight will again be active for 15 minutes after the last interaction or alarm. If any screen  
other than the mimic screen has been activated, after 5 minutes with no further interaction, the  
screen will revert to the basic mimic screen.  
Figure 12 Menu tree  
Master Menu  
Monitor  
Mimic  
Display  
Status  
Reports  
Start-Up  
Procedures  
Battery  
Equalize  
Limit Settings  
Battery Time  
System  
Configura-  
tion  
Walk-In  
Display  
Load  
Transfer  
Shutdown  
Procedures  
Meter  
Calibration  
Present  
Status  
Date  
Time  
Event History  
History  
Status  
Auto Dial  
Max. Auto  
Rexfer  
Attempts  
System  
Status  
System  
Current  
Rating  
Battery Cycle  
Monitor  
Lang.  
Selection  
System  
Options  
Customer  
Alarm  
Definitions  
Batt. Temp.  
Charging  
Compensation  
Continuous  
Duty Static  
Switch  
Backlight  
Brightness  
Battery  
Exercise  
LCD Contrast  
Auto Restart  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Figure 12 illustrates the primary screens that you can access through the Operator Interface Display  
System. The liquid crystal display (LCD) screen provides a full 80 characters by 25 lines of informa-  
tion for easy readability. The following sections describe what these screens display and how and  
when to use them.  
Module status information is available on the display screen, provided Control Power is ON, even  
when the UPS module is not operating. System status information is available on the SCC display  
screen and at local and remote terminals when at least one module is on-line or when the bypass  
source is available.  
The screen will automatically display the Monitor/Mimic during normal operation. The System con-  
figuration screen will be displayed during start-up and whenever a system reset is required.  
If a module display screen is blank, either power is not available, the Rectifier Input (RIB) circuit  
breaker (external to the UPS module) is open or the Control Power switch is OFF. If power is avail-  
able and a display is blank, contact Liebert Global Services (1-800-LIEBERT). Note that status infor-  
mation may be available at local and remote terminals. Use control touch pads at the SCC to  
manually transfer the critical load to the bypass line if the SCC display goes blank while load is on  
UPS (a very unlikely event).  
3.2.1 Master Menu Screen  
The Master Menu contains the primary menu selections that monitor and control the operation of the  
UPS.  
Figure 13 SCC and module master menu screens  
UP : CURSOR UP  
DOWN : CURSOR DOWN  
© 1989-2003  
SELECT : CHOOSE  
MASTER MENU  
MONITOR/MIMIC DISPLAY  
START-UP PROCEDURES  
SHUTDOWN PROCEDURES  
METER CALIBRATION  
STATUS REPORTS  
SYSTEM CONFIGURATION  
LIMIT SETTINGS  
BATTERY EQUALIZE  
LOAD TRANSFER PROCEDURES  
CUSTOMER ALARM DEFINITIONS  
SCC Master Menu  
UP : CURSOR UP  
DOWN : CURSOR DOWN  
SELECT : CHOOSE  
© 1989-2003  
MASTER MENU  
MONITOR/MIMIC DISPLAY  
WALK-IN DISPLAY  
START-UP PROCEDURES  
SHUTDOWN PROCEDURES  
BATTERY TIME  
STATUS REPORTS  
SYSTEM CONFIGURATION  
LIMIT SETTINGS  
METER CALIBRATION  
BATTERY EQUALIZE  
Module Master Menu  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
From any primary screen (accessed directly from the Master Menu), pushing the Select pad once will  
return you to the Master Menu. From any secondary screen, pushing the Select pad twice will return  
you to the Master Menu.  
Please note that some screens have multiple pages. However, in each case, instructions appear for  
accessing other pages.  
Monitor/Mimic Display—This graphic mimics the power flow through the UPS system. Input  
voltage and current readings, battery status, UPS ratings, load readings, circuit breaker indica-  
tions, system status and alarm messages are all displayed on this screen.  
Walk-In Display (Modules Only)—This is a bar graph that shows DC bus voltage, input cur-  
rents and UPS module output voltage (all in percent of nominal). This screen typically is utilized  
during start-up procedures.  
Status Reports—This display consists of four submenu selections: present status, event history,  
history status and system status. These screens display data on the system’s present and past  
performance. They also display information about any faults that have occurred in the system and  
total operating hours for the controls.  
System Configuration—This screen displays the current configuration of the UPS system. It  
also enables the operator to reset the date, time and dial-out phone numbers. The SCC current  
rating can also be adjusted lower than design maximum. The operator can view, but cannot  
change, any of the settings unless the Interlock (Security Access) button is pressed.  
Limit Settings—This security access display shows the present UPS system alarm limit set-  
tings. The operator can view the settings, but they should not be changed without consulting Lie-  
bert Global Services.  
Load Transfer Procedures (SCC Only)—This screen specifies all of the steps required to man-  
ually transfer the critical load between the UPS system and the bypass source. Comparisons of  
the voltage, frequency and phase synchronization of the UPS system output and the bypass line  
are also illustrated to aid in the transfer or retransfer procedure.  
Start-Up Procedures—This two-page screen lists step-by-step procedures to start the UPS sys-  
tem and the modules.  
Shutdown Procedures—This two-page screen lists the proper sequence of steps to shutdown  
the UPS system and the modules for maintenance or repairs. The steps instruct the operator to  
transfer the critical load to bypass, open the battery circuit breakers and open the UPS module  
output and input circuit breakers to shut down and isolate the modules. The critical load will  
remain on bypass power unless circuit breakers outside the UPS system are also opened.  
Battery Time (Modules Only)—This graph displays the projected battery voltage drop caused  
by a battery discharge over time. During a period of battery discharge, the Series 610 calculates  
the battery time remaining based on battery rating, initial battery condition and actual connected  
load. The UPS continues to update and display both rated (theoretical) and calculated time every  
6 seconds. This enables the operator to immediately see the effects of load shedding on time  
remaining and to accurately assess his power resources.  
Meter Calibration—This security access screen enables an authorized Liebert field-service  
engineer to adjust and calibrate the UPS metered functions. The operator can view, but should  
not change, any of the settings.  
Battery Equalize—The battery equalize screen lets the operator change the battery equalize  
recharging mode from manual to automatic and to observe or change the equalize time. Battery  
equalize charge voltage is higher than battery float (constant) charge voltage. Automatic and  
manual equalizing can be controlled from the SCC, while only manual equalizing can be con-  
trolled from the module.  
NOTE  
Do not use battery equalize charging with sealed-cell batteries. Refer to the battery  
manufacturer’s manual, available on the manufacturer’s Web site, for specific information  
about equalize charging.  
Customer Alarm Definitions (SCC Only)—This optional screen allows the operator to define  
alarms for conditions external to the UPS, battery or switchgear.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Battery Test (MMU Only)—The optional battery test screen allows the operator to perform  
manual battery tests to determine the general condition of the battery system. The results of the  
last 10 tests are recorded in non-volatile storage and can be retrieved through the battery test  
results screen.  
Battery Temp Compensation Charging (MMU Only)—The optional battery temperature  
sensing unit, when installed, automatically reduces the float charge voltage in response to  
increases in battery temperature. The nominal float voltage is 540VDC (2.25 volts per cell) at  
25°C. This float voltage is automatically reduced 5VDC for each temperature rise of 5°C. The LCD  
indicates whether the temperature compensation circuit is active.  
3.2.2 SCC Monitor/Mimic Display Screen  
From SCC Master Menu move the highlighted cursor to MONITOR/MIMIC DISPLAY. Press the  
Select pad and the Monitor/Mimic screen is displayed.  
The Monitor/Mimic display screen is a simplified block diagram of the UPS system. This screen gives  
the operator an overall view of the power flow through the UPS system. The screen consists of three  
major sections: the input/UPS metering section, the load metering section and the status and alarm  
message areas. The metered parameter values on the Monitor/Mimic screen are updated at one-sec-  
ond intervals.  
Figure 14 SCC Monitor/Mimic display screen  
4
1
2
© 1989-2003  
BYPASS INPUT  
LOAD  
A-B  
B-C C-A  
627 KVA / 502 KW  
480V 480V 480V  
60.0 Hz  
A
B
C
3
UPS RATINGS  
SCCB1600  
755A 755A 755A  
UPS INPUT PWR  
3 OF 3 MODULES  
CONNECTED  
A-B  
B-C C-A  
OUTPUT VOLTAGE  
480V 480V 480V  
A-B  
B-C C-A  
REDUNDANT  
480V 480V 480V  
60.0 Hz  
5
7
6
MOD 1 ON LINE  
MOD 2 ON LINE  
MOD 3 ON LINE  
OK to Transfer  
Static Switch Connected  
Input Metering Displays  
NOTE  
All voltage readings are phase-to-phase measurements (A-B, B-C and C-A). All current  
readings are phase measurements (A, B and C).  
Item 1 - Bypass Input: This block displays the bypass input voltage and the bypass input frequency.  
The System Bypass Breaker is shown to the right of this block. The status of the circuit breaker is  
illustrated as open or closed.  
Item 2 - UPS Input Pwr: This block displays the input voltage to the UPS modules. This data is  
received serially from the modules.  
Output Metering Displays  
Item 3 - UPS Ratings: The SCC current rating is specified at the top of this block. The UPS system  
output voltage and frequency are also displayed in this block. The UPS Output Breaker is shown to  
the right of this block. The status of the circuit breaker is illustrated as open or closed.  
Item 4 - Load: This block displays the total output power to the critical load in kVA and kW. The  
critical load current per phase is also displayed in this block. Note that kW is not displayed when the  
load is on the bypass line.  
The load block also indicates the number of modules connected and whether the UPS system is oper-  
ating in the redundant or non-redundant mode.  
During an overload condition, the time remaining before shutdown or transfer is displayed at the bot-  
tom of the load box.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Status/Alarm Message Areas  
The status/alarm message areas display vital information about the operation of the UPS system.  
During normal operation no alarm messages should be present. Changes in the status of the system  
and possible alarm conditions can be monitored. Both the status and the alarm messages are dis-  
played in reverse video (highlighted—light on dark). The alarm messages continue flashing until the  
Horn Off pad is pressed. To clear a latching alarm, you must also press the Alarm Reset pad after  
the alarm condition is corrected.  
The following lists show the status and alarm messages that may be displayed in these areas. For  
more information and the corrective actions for these messages, refer to Table 9 in this section.  
Item 5 - Module Status Messages  
Module On Line  
Module Off Line  
Module Summary Alarm  
Module Communication Failure  
Item 6 - System Status Messages  
Static Switch Connected  
Static Switch Disconnected  
OK To Transfer  
Not OK To Transfer  
Item 7 - Alarm Messages  
Load On Bypass  
Auto Retransfer Primed  
Manual Reset/Retransfer  
Static Switch Unable  
Bypass Not Available  
Bypass Phase Sequence Wrong  
Control Power Fail  
Output Over/Underfrequency  
Output Undervoltage  
Output Overvoltage  
Overload  
Overload Transfer  
Emergency Off  
Module Summary Alarm  
Battery Cycle Buffer Warning  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
3.2.3 Module Monitor/Mimic Display Screen  
From module Master Menu move the highlighted cursor to MONITOR/MIMIC DISPLAY. Press the  
Select pad and the Monitor/Mimic screen is displayed.  
The Monitor/Mimic display screen is a simplified block diagram of the UPS module and power connec-  
tions. This screen gives the operator an overall view of the power flow through the UPS module. The  
screen consists of three major sections: the input/UPS metering section, the load metering section and  
the status and alarm message areas. The metered parameter values on the Monitor/Mimic screen are  
updated at one second intervals.  
Figure 15 Module Monitor/Mimic display screen  
4
© 1989-2003  
LOAD  
270 KVA / 217 KW  
A
B
C
3
UPS RATINGS  
325A  
1
2
325A 325A  
AP648-84  
RATED 400 KVA  
OUTPUT VOLTAGE  
UPS INPUT PWR  
A-B  
480V  
350A  
B-C C-A  
480V  
350A  
480V  
350A  
A-B  
B-C C-A  
480V 480V 480V  
60.0 Hz  
5
BATTERY  
VOLTS 540  
AMPS 15 CHARG  
NOTE  
All voltage readings are phase-to-phase measurements (A-B, B-C and C-A). All current  
readings are phase measurements (A, B and C).  
Input Metering Displays  
Item 1 - UPS Input Pwr: This block displays the UPS module input voltage and current. The Mod-  
ule Input breaker is shown to the right of this block. The status of the circuit breaker is illustrated as  
open or closed.  
Item 2 - Battery: The battery block displays the DC bus voltage and the charge or discharge current  
to or from the battery. This block reads MODULE DC BUS when the battery circuit breaker is open  
and BATTERY when the battery circuit breaker is closed during normal operation. This block reads  
BATTERY EQUALIZE when the battery equalize charge voltage is used to recharge the battery.  
This block also shows BATTERY TEMPERATURE when the battery temperature sensor option is  
installed. The Module Battery Disconnect (MBD) is shown to the right of this block. The status of the  
circuit breaker is illustrated as open or closed.  
Output Metering Displays  
Item 3 - UPS Ratings: The module part number and kVA rating are specified at the top of this block.  
The UPS output voltage and frequency are also displayed in this block. The Module Output breaker is  
shown to the right of this block. The status of the circuit breaker is illustrated as open or closed.  
Item 4 - Load: This block displays the module output power to the critical load in kVA and kW. The  
critical load current per phase is also displayed in this block.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Alarm Messages  
The alarm message area displays vital information about the operation of the UPS system. During  
normal operation no alarm messages should be present. Alarm conditions can be monitored. The  
alarm messages are displayed in reverse video (highlighted— light on dark). To clear a latching  
alarm, you must also press the Alarm Reset pad after the alarm condition is corrected.  
The following list shows the alarm messages that may be displayed in this area. For more information  
and the corrective actions for these messages, refer to Table 9 in this section.  
Item 5 - Alarm Messages  
Input Fail  
Reverse Power  
DC Ground Fault  
Rectifier Fuse Blown  
Inverter Fault  
DC Capacitor Fuse Blown  
Battery CB Open  
Hardware Shutdown  
Emergency Off  
Battery Discharging  
Low Battery Warning  
Low Battery Shutdown  
DC Overvoltage Shutdown  
Input Current Unbalanced  
Control Power Fail  
Inverter Non-Synchronized  
Overload  
Ambient Overtemperature  
Fan/Blower Failed  
Equipment Overtemperature  
Overtemperature Timeout  
Battery Cycle Buffer Warning  
Battery Overtemperature  
Battery Exercise  
Overload Shutdown  
Figures 16 through 20 illustrate how the Monitor/Mimic Display screens on the SCC and on a mod-  
ule depict the power flow through the UPS system.  
A three-module system designed for redundant operation is shown. A multi-module UPS system may  
include up to six (6) modules for each System Control Cabinet (SCC).  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Figure 16 Monitor/Mimic display example: Normal power flow  
© 1989-2003  
BYPASS INPUT  
LOAD  
A-B  
480V 480V  
B-C C-A  
627 KVA / 502 KW  
480V  
60.0 Hz  
A
B
C
UPS RATINGS  
SCCB 1600  
755A  
755A 755A  
UPS INPUT PWR  
3 OF 3 MODULES  
CONNECTED  
A-B  
B-C C-A  
OUTPUT VOLTAGE  
480V  
480V 480V  
A-B  
480V  
B-C C-A  
480V 480V  
60.0 Hz  
REDUNDANT  
MOD 1 ON LINE  
MOD 2 ON LINE  
MOD 3 ON LINE  
OK to Transfer  
Static Switch Connected  
SCC Display  
© 1989-2003  
LOAD  
270 KVA / 217 KW  
A
B
C
UPS RATINGS  
AP648-84  
RATED 400 KVA  
410A  
410A  
410A  
UPS INPUT PWR  
A-B  
480V 480V  
350A 350A 350A  
B-C C-A  
OUTPUT VOLTAGE  
480V  
A-B  
B-C C-A  
480V 480V  
60.0 Hz  
480V  
BATTERY  
VOLTS 540  
AMPS 15 CHARG  
Module Display  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
Figure 17 Monitor/Mimic display example: Utility fail  
© 1989-2003  
LOAD  
BYPASS INPUT  
A-B  
0V  
B-C C-A  
627 KVA / 502 KW  
0V  
0V  
0 Hz  
A
B
C
UPS RATINGS  
SCCB 1600  
755A 755A 755A  
UPS INPUT PWR  
3 OF 3 MODULES  
CONNECTED  
A-B  
0V  
B-C C-A  
0V 0V  
OUTPUT VOLTAGE  
A-B  
B-C C-A  
480V 480V  
60.0Hz  
REDUNDANT  
480V  
MOD 1 ON LINE SUM ALM  
MOD 2 ON LINE SUM ALM  
MOD 3 ON LINE SUM ALM  
Byp Not Avail  
Static Sw Unable  
Module Sum Alm  
Not OK to Transfer  
Static Switch Connected  
SCC Display  
© 1989-2003  
LOAD  
270 KVA / 217 KW  
A
B
C
UPS RATINGS  
AP648-84  
RATED 400 KVA  
325A 325A 325A  
UPS INPUT PWR  
A-B  
B-C C-A  
OUTPUT VOLTAGE  
0V  
0A  
0V  
0A  
0V  
0A  
A-B  
480V  
B-C C-A  
480V 480V  
60.0 Hz  
BATTERY  
VOLTS 480  
AMPS 645 DISCHARG  
Input Fail  
Batt Discharging  
Not OK to Transfer  
Static Switch Connected  
Module Display  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
Figure 18 Monitor/Mimic display example: Load on bypass, UPS modules on and charging battery  
© 1989-2003  
BYPASS INPUT  
LOAD  
A-B  
B-C C-A  
627 KVA / 502 KW  
480V 480V 480V  
60.0 Hz  
A
B
C
UPS RATINGS  
755A  
755A  
755A  
SCCB 1600  
UPS INPUT PWR  
3 OF 3 MODULES  
CONNECTED  
A-B  
B-C C-A  
OUTPUT VOLTAGE  
480V 480V  
480V  
A-B  
B-C C-A  
REDUNDANT  
480V  
480V 480V  
60.0 Hz  
MOD 1 ON LINE  
MOD 2 ON LINE  
MOD 3 ON LINE  
Load On Bypass  
OK to Transfer  
Static Switch Connected  
SCC Display  
© 1989-2003  
LOAD  
270 kVA / 217 kW  
A
B
C
UPS RATINGS  
325A 325A 325A  
AP648-84  
RATED 400 KVA  
OUTPUT VOLTAGE  
UPS INPUT PWR  
A-B  
B-C C-A  
480V  
480V 480V  
A-B  
B-C C-A  
390A 390A 390A  
480V  
480V 480V  
60.0 Hz  
BATTERY  
VOLTS 540  
AMPS 75 CHARG  
Module Display  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
Figure 19 Monitor/Mimic display example: Load on UPS, one UPS module off line  
© 1989-2003  
LOAD  
BYPASS INPUT  
A-B B-C C-A  
480V 480V 480V  
627KVA/502KW  
60.0 Hz  
A
B
C
UPS RATINGS  
755A 755A  
755A  
SCCB 1600  
UPS INPUT PWR  
2 OF 3 MODULES  
CONNECTED  
480V  
A-B  
B-C C-A  
OUTPUT VOLTAGE  
480V  
480V  
A-B  
B-C C-A  
NON-REDUNDANT  
480V 480V 340V  
60.0 Hz  
MOD 1 ON LINE  
MOD 2 OFF LINE SUM ALM  
Module Sum Alm  
MOD 3 ON LINE  
OK to Transfer  
Static Switch Connected  
SCC Display  
© 1989-2003  
LOAD  
314KVA/251KW  
A
B
C
UPS RATINGS  
378A 378A 378A  
AP648-84  
UPS INPUT PWR  
RATED 400 KVA  
A-B  
B-C C-A  
OUTPUT VOLTAGE  
480V480V  
480V  
A-B  
480V  
B-C C-A  
405A 405A 405A  
480V 480V  
60.0Hz  
BATTERY  
VOLTS540
AMPS 15 CHARG  
Module Display  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
Figure 20 Monitor/Mimic Display example: Load on bypass, all UPS modules off line  
© 1989-2003  
LOAD  
BYPASS INPUT  
A-B B-C C-A  
480V 480V 480V  
627KVA/502KW  
60.0 Hz  
A
B
C
UPS RATINGS  
755A 755A  
755A  
SCCB 1600  
UPS INPUT PWR  
0 OF 3 MODULES  
CONNECTED  
480V  
A-B  
B-C C-A  
OUTPUT VOLTAGE  
480V  
480V  
A-B  
0V  
B-C C-A  
NON-REDUNDANT  
0V  
0V  
0 Hz  
MOD 1 OFF LINE SUM ALM  
Load on Bypass  
Static Sw Unable  
Module Sum Alm  
MOD 2 OFF LINE SUM ALM  
MOD 3 OFF LINE SUM ALM  
Not OK to Transfer  
Static Switch Connected  
SCC Display  
© 1989-2003  
LOAD  
0KVA/0KW
A
B
C
UPSRATINGS
0A 0A 0A
AP646-84
RATED 375KVA  
OUTPUT VOLTAGE  
UPS INPUT PWR  
A-B  
B-C C-A  
480V 480V 480V
A-B  
B-C C-A  
0A 0A 0A  
0V  
0V  
0V  
0 Hz  
MODULE DC BUS  
VOLTS  
AMPS  
0
0
Input Fail  
Batt CB Open  
Module Display  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
3.2.4 Walk-In Display Screen  
From the module Master Menu, highlight WALK-IN DISPLAY and then press the Select pad. Note  
that this screen is displayed at the UPS modules but is not required at the System Control Cabinet  
(SCC).  
Figure 21 Walk-in display screen during start-up  
SELECT :  
DOWN :  
MASTER MENU  
SELECT :  
© 1989-2003  
D.C. VOLTS  
INPUT AMPS  
OUTPUT VOLTS  
0%  
25%  
50%  
75%  
100%  
The Walk-In Display screen enables the operator to monitor the UPS module DC bus voltage, the  
input currents and the output voltage. This is important during the start-up procedures.  
During start-up, the UPS module input circuit breaker is closed and power is applied to the UPS mod-  
ule. The Walk-In Display screen graphically shows the voltage increasing on the DC bus as the UPS  
module rectifier begins to walk-in.  
The DC Volts bar gradually moves to the right. After the DC Volts bar reaches the 90% level, the  
UPS module inverter starts-up and the Output Volts bar also moves to the right. Both the DC Volts  
and the Output Volts bars should settle near the 100% line as the UPS module becomes fully ener-  
gized.  
The three Input Amps bars (one for each phase of input current) move to the right during the initial  
transformer inrush. They should return to the left after the momentary inrush has subsided, then  
increase to about 10% as the DC Volts increase.  
Modules equipped with the optional input filter will indicate more than 10% with no connected load.  
NOTE  
After the critical load is transferred from the bypass line to the UPS modules, the Input Amps  
bars continue to indicate the percent of the design input current to the UPS module rectifier.  
If any Input Amps bar differs from the average bar length by more than 10%, call Liebert  
Global Services.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
3.2.5 Status Reports Screens  
Go to the Master Menu and move the highlighted cursor to STATUS REPORTS. Press the Select  
button and the Status Reports screen is displayed.  
The Status Report screen is divided into four submenu reports: PRESENT STATUS, EVENT HIS-  
TORY, HISTORY STATUS and SYSTEM STATUS.  
To look at any of the reports, do the following:  
1. From the Status Reports screen, press the Up or Down pad to move the highlighted cursor to the  
desired selection.  
2. Press the Select pad to view the desired report page.  
3. Use the Up and Down pads to move through a report that includes several screens (frames).  
4. Press the Select pad to exit the report.  
5. To return to the Master Menu, return to EXIT and press the Select pad.  
Each report screen includes the date, time and a frame number. The frame number indicates the rela-  
tionship sequence of a 4 millisecond time segment. The SCC and each module generate their own  
frame numbers independently. The clock in each module is synchronized to the SCC clock.  
NOTE  
Each of the four Status Reports can be displayed on a remote terminal.  
Figure 22 Status reports screen  
UP : CURSOR UP  
DOWN : CURSOR DOWN  
© 1989-2003  
SELECT : CHOOSE  
EXIT  
PRESENT STATUS  
EVENT HISTORY  
HISTORY STATUS  
SYSTEM STATUS  
Present Status  
The Present Status screen shows the current status of the UPS system (SCC) or module. This screen  
displays any alarm messages that are present and the values of the metered parameters for each cab-  
inet. Battery values are displayed only at the UPS modules.  
Each update sequence (every 4 milliseconds) is called a frame. The frame number is displayed in the  
upper right corner. The Present Status screen display is updated every two seconds.  
Battery Time Remaining (in minutes) is displayed on the module screens during a battery discharge.  
The value is on the Battery Volts line in the TIME column (far right side of the screen). For the first  
two minutes of discharge, the Rated Time Remaining is displayed. After that, the Calculated Time  
Remaining is displayed and updated every six seconds.  
All the information on this screen, including Battery Time Remaining, is available to a local terminal  
or modem through the communications ports provided in the Series 610 UPS. Refer to Table 11 in  
this manual for keyboard commands to use with the communication ports.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operation  
Figure 23 Present status report screens, SCC (above) and module  
PRESENT STATUS  
MODULE-0  
01/12/98  
14:06:26  
FRAME 35  
ORDER - 000000 SITE ID - 00000 SITE TAG - 0000000  
**** ACTIVE ALARMS **** Batt Discharging  
DC  
HERTZ  
A
480  
325  
B
480  
325  
C
480  
325  
LOAD  
TIME  
0:06  
OUTPUT VOLTS  
OUTPUT AMPS  
OUTPUT FREQUENCY  
LOAD KVA  
60.0  
270  
BYPASS VOLTS  
0
0
0
END OF REPORT  
SELECT : EXIT  
SCC Status Report  
PRESENT STATUS  
MODULE-0  
01/12/98  
14:06:26  
FRAME 35  
ORDER - 000000 SITE ID - 00000 SITE TAG - 0000000  
**** ACTIVE ALARMS **** Batt Discharging  
DC  
HERTZ  
A
480  
325  
B
480  
325  
C
480  
325  
LOAD  
TIME  
0:09  
OUTPUT VOLTS  
OUTPUT AMPS  
OUTPUT FREQUENCY  
BATTERYVOLTS  
BATTERYAMPS  
INPUT VOLTS  
60.0  
480  
-645  
0
0
0
0
0
0
INPUTAMPS
LOAD KVA  
270  
END OF REPORT  
SELECT : EXIT  
Module Status Report  
Event History  
The Event History screen lists the active alarms present in the UPS system (SCC) or modules. This  
screen also displays the prior 128 alarm frames, in a first in, first out (FIFO) sequence, that have  
taken place along with the date and the time that each alarm frame occurred. Use the Up and Down  
pads to look through the different alarm frames.  
Figure 24 Event history report screen  
EVENT HISTORY  
MODULE-0  
01/17/98  
15:06:41  
FRAME 175  
ORDER - 000000 SITE ID - 00000 SITE TAG - 0000000  
**** ACTIVE ALARMS **** Batt Discharging  
Low Batt Warning  
UP : NEXT FRAME  
DOWN : PREVIOUS FRAME  
SELECT : EXIT  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
History Status  
The History Status screen displays 64 frames, of 4 milliseconds each, from the Present Status screen.  
Note that the values for output volts and amps are updated once each millisecond. Alarms are listed  
in the sequence they occurred, within 1 millisecond resolution. The frames are stored in a buffer (a  
computer information storage technique). The buffer stores the frames in a first in, first out sequence.  
As a new frame enters the buffer the oldest one is released.  
When a designated fault occurs (see list below), the buffer stores information for the next 24 frames  
and then freezes (stops gathering information). At that time, the History Status screen contains  
40 frames before the fault, the frame when the fault occurred and 23 frames after the fault. This  
64-page report is a very useful diagnostic tool for the operator or Liebert Global Services. Use the Up  
and Down pads to view the screens.  
Figure 25 History status report screens  
HISTORY STATUS  
ORDER - 000000  
**** ACTIVE ALARMS **** Output Ov-volts  
MODULE-0  
04/10/97  
16:49:21  
FRAME 36  
SITE ID - 00000 SITE TAG - 0000000  
DC  
A
480  
420  
B
480  
420  
C
480  
420  
LOAD  
349  
TIME  
HERTZ  
60.0  
OUTPUT VOLTS  
OUTPUT AMPS  
OUTPUT FREQUENCY  
LOAD KVA  
BYPASS VOLTS  
480  
480  
480  
UP : NEXT FRAME  
DOWN : PREVIOUS FRAME  
SELECT : EXIT  
HISTORYSTATUS  
MODULE-0 01/17/98 11:21:59 FRAME100  
SITE ID - 00000 SITE TAG - 0000000  
**** ACTIVE ALARMS **** BattDischarging Low Batt Warning  
ORDER - 000000  
DC  
A
B
C
LOAD  
TIME  
HERTZ  
OUTPUT VOLTS  
OUTPUT AMPS  
OUTPUT FREQUENCY  
OUTPUTVOLTS  
OUTPUTAMPS
BATTERY VOLTS  
OUTPUT VOLTS  
OUPUT AMPS  
480  
325  
480  
325
480  
325
60.0  
480  
325  
480  
325
480  
325
390  
0:01  
480  
325  
480  
325  
480  
325  
-645  
BATTERY AMPS  
INPUT VOLTS  
INPUT AMPS  
0
0
0
0
0
0
UP : NEXT FRAME  
DOWN : PREVIOUS FRAME  
SELECT : EXIT  
OUPUT VOLTS  
OUTPUT AMPS  
LOAD KVA  
480  
325  
480  
325  
480  
325  
270  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
Table 5 shows the alarm conditions that stop the History Status buffer from gathering data.  
Table 5 Alarm conditions that freeze history data gathering  
Alarm in SCC Alarm in Module  
Auto Transfer to Bypass DC Cap Fuse Blown  
Output Overvoltage  
Output undervoltage  
Overload Transfer  
DC Overvoltage Shutdown  
Inverter Fault  
Low Battery Shutdown  
Overload Shutdown  
Overtemperature Timeout  
Rectifier Fuse Blown  
Reverse Power  
NOTE  
The Emergency Off alarm will also freeze the SCC History Status buffer with the Auto  
Transfer to Bypass alarm (if the load is on the UPS system when the alarm condition occurs).  
The History Status buffer does not resume collecting new frames until the fault is cleared and the  
Alarm Reset pad is pressed for more than 5 seconds (or until the screen clears).  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
System Status  
The System Status screen displays the module Total Operating Hours, Enable Backlight and the Bat-  
tery Cycle Monitor.  
Battery Cycle Monitor—Module Only  
Selecting the Battery Cycle Monitor gives you access to detailed information about the module’s most  
recent battery discharge events. Periodic review of this data can give a good indication of battery per-  
formance and expected life.  
Each battery discharge cycle is put into one of four categories, depending on the length of the event:  
• 0-30 Seconds Discharge  
• 31-90 Seconds Discharge  
• 91-240 Seconds Discharge  
• Over 240 Seconds Discharge  
Each discharge cycle is sorted by time duration and tagged with the following system parameters:  
• System time and date  
• Event Number  
• Duration of cycle (seconds)  
• Lowest DC Bus Voltage  
• Highest DC Bus Current  
• kW carried by the batteries at the start of cycle  
• Battery Environment Ambient Temperature (when equipped with optional temperature sensor)  
Up to 132 discharge cycle events can be stored at any given time. When the buffer approaches its  
capacity, a warning message is broadcast via terminal and modem communication channels and a  
complete listing of all records (in order of occurrence) is sent to the terminal port. If a serial printer is  
attached to the terminal port (see 3.2.15 - Communication Interfaces), the operator can print a  
hard copy of the report. If a printer is not available, a terminal emulation program can capture the  
report to disk for later review or printing. Once the buffer is filled, new data will replace the old on a  
first in, first out (FIFO) basis as new cycles occur.  
To view this data, select the BATTERY CYCLE MONITOR option on the System Status screen. At  
the next screen (see Figure 26), you can select either the Battery Cycle Monitoring Summary screen  
or a screen showing detailed information on any one of the four categories of discharge (0-30 seconds,  
31-90 seconds, 91-240 seconds and over 240 seconds).  
Figure 26 Battery cycle monitor screen  
UP : CURSOR UP  
DOWN : CURSOR DOWN  
SELECT : CHOOSE  
© 1989-2003  
EXIT  
EXIT  
...............................................  
...............................................  
Battery Cycle Monitor  
Battery Temperature  
Enable  
Enable  
Battery Cycle Monitoring Summary  
0-30 Seconds Discharge  
31-90 Seconds Discharge  
91-240 Seconds Discharge  
Over 240 Seconds Discharge  
Total Since 02/4/95  
................................  
................................  
................................  
................................  
11  
5
2
1
19  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
The Summary screen (Figure 27) shows Total Number of Discharge Cycles, Accumulated Battery  
Time, Accumulated Battery Amp Hours, Accumulated Battery Kilowatt Hours and Battery Tempera-  
ture. During a battery discharge event, the screen changes to show information about the present dis-  
charge cycle. The screen displays Active Cycle Time in place of Accumulated Battery Time and shows  
Active Battery AH and Active Battery kWH instead of accumulated values.  
Figure 27 Battery cycle monitoring summary screen  
© 1989-2003  
SELECT : EXIT  
Battery Cycle Monitoring Summary  
Total No. of Cycles . . . . . . . . . . . . .  
Accumulated Battery Time . . . . . . .  
Accumulated Battery AH . . . . . . . .  
Accumulated Battery KWH . . . . . . .  
Battery Temperature . . . . . . . . . . . .  
7
15 min. 32 sec.  
71  
34  
25°C / 77°F  
Figure 28 shows a typical detail screen for the 91-240 Seconds Discharge category. This information  
can be collected remotely, through the optional communications board and modem, by a remote termi-  
nal or a personal computer equipped with a modem and communications program. See 3.2.15 - Com-  
munication Interfaces for more information.  
NOTE  
This information is applicable to systems with separate batteries for each module. If the  
modules share a common battery, select one module to do the monitoring and disregard  
the other(s).  
Figure 28 Typical data on discharge cycles of 91 to 240 seconds duration during the recording period  
UP  
:
CURSOR UP  
DOWN : CURSOR DOWN  
SELECT : CHOOSE  
© 1989-2003  
Total 91-240 se c. Cycl  
EXIT  
5
Event  
Date  
Time Duration  
Min. Volt Max. Amp Start KW Start Temp  
15  
12  
9
5
2
4/12/95  
3/25/95  
3/13/95  
2/07/95  
11/24/94  
10:31  
20:21  
7:35  
17:22  
12:33  
235  
98  
139  
199  
95  
477  
479  
467  
478  
477  
110  
97  
173  
95  
70  
37  
69  
40  
39  
68  
65  
67  
70  
69  
83  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
3.2.6 System Configuration Screens  
Go to the Master Menu and move the highlighted cursor to SYSTEM CONFIGURATION. Press the  
Select pad and the System Configuration screen is displayed.  
The System Configuration screen lists parameters that can be changed to adjust your UPS modules  
and the SCC to your site requirements. Some of the information displayed is factory-set and should  
only be changed by Liebert Global Services. Parameters that should be adjusted by the user include  
date, time, auto dial number and modem baud rate.  
The System Configuration screen is one of the displays that has controlled access to limit who is able  
to change site parameters. This type of screen is called a Security Access screen. This controlled  
access feature allows anyone to review the present parameters, but limits access for making changes.  
When you see Security Access displayed on the screen (upper left corner), to make authorized changes  
you must open the control cabinet door (key required) and push the Interlock button on the back of  
the control panel (Figure 11). Close and lock the control cabinet door after making authorized  
changes.  
Figure 29 SCC system configuration screen  
SECURITY ACCESS  
UP: CURSOR UP  
DOWN: CURSOR DOWN  
SELECT: CHOOSE  
SYSTEM CONFIGURATION  
EXIT  
Part Number....................................................................... 02-791112-14  
Order Number .................................................................... 000000  
Site ID Number................................................................... 00000  
Site TAG Number ............................................................... 0000000  
System Number ................................................................. 1  
Number of Modules in System........................................... 2  
Date.................................................................................... 01/17/03  
Time ................................................................................... 14:51:59  
Auto Dial............................................................................. YES  
Max Auto-Rexfer Attempts ................................................. 5  
System Current Rating....................................................... 1600  
Language Selection ........................................................... English  
System Options  
Version 3.02.0  
Copyright© 1989-2003  
Liebert Corporation  
All Rights Reserved  
NOTE  
If you mistakenly set a site parameter digit to an incorrect value, you must return to the System  
Configuration screen and then go to the required screen to reset the value.  
Part Number: This is a factory-set part number of the UPS cabinet, which determines many internal  
operating parameters. It cannot be changed.  
Order Number: This is a factory-set number to identify your particular installation.  
System Number: This number is used to identify one or more UPS systems that may be present on  
one site.  
Number of Modules in System: This shows the total number of modules.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Date  
This is the system’s real-time date setting. The system control program sends to each module the date  
entered at the System Control Cabinet (SCC). You cannot change the system date from the control  
panel of a UPS module.  
Figure 30 Date screen  
© 1989-2003  
DATE  
01/17/96  
UP  
:
INCREASE VALUE  
DOWN : DECREASE VALUE  
SELECT : WALK-THRU/ EXIT  
To reset the date, do the following at the SCC.  
1. From the System Configuration screen, press the Up or Down pad to move the highlighted cursor  
to DATE.  
2. Press the Select pad. The Date screen will appear.  
3. Press the Select pad to move the arrow to the next digit to the right.  
4. When the arrow is on the digit to be changed, press the Up pad to increase the number or the  
Down pad to decrease it.  
5. Press Select to set the value and move to the next digit.  
6. After the correct month/day/year has been set, press the Select pad again to return to the System  
Configuration screen.  
NOTE  
Precise Date and Time functions are required for accurate archival and event history purposes.  
Both the Date and Time can be set from a remote terminal. Refer to 3.2.15 - Communication  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
Time  
This is the system’s real-time clock. The system control program sends to each module the time  
entered at the System Control Cabinet (SCC).  
You cannot change the system time from the control panel of a UPS module.  
Figure 31 Time screen  
© 1989-2003  
TIME  
09:15:00  
UP  
:
INCREASE VALUE  
DOWN : DECREASE VALUE  
SELECT : WALK-THRU/ EXIT  
To reset the time do the following at the SCC:  
1. From the System Configuration screen, press the Up or Down pad to move the highlighted cursor  
to Time.  
2. Press the Select pad. The Time screen will appear.  
3. Press the Select pad to move the arrow to the next digit to the right.  
4. When the arrow is on the digit to be changed, press the Up or Down pad to increase or decrease  
the hour/minute/second number.  
5. Press Select to set the value and move to the next digit.  
6. After the correct hour/minute/second has been set, press the Select pad again to return to the  
System Configuration screen.  
NOTE  
Precise Date and Time functions are required for accurate archival and event history purposes.  
Both the Date and Time can be set from a remote terminal. Refer to 3.2.15 - Communication  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
Auto Dial  
This is a feature that automatically dials (through a customer supplied PC-compatible modem) a pre-  
programmed telephone number (up to 12 digits) when specified alarm conditions occur within the  
UPS system. The connection for the modem is at the SCC. Automatic dial attempts to the first num-  
ber are made at periodic intervals for 30 minutes. If unanswered, the system rolls over to the second  
number and repeats the process until connection is made.  
Upon connection, the system transmits data, in RS-232C format, that includes the system identifica-  
tion code, the present alarm message(s) and the time that the alarm(s) occurred. Refer to 3.2.15 -  
Refer to the Special Functions column in Table 9 to see which alarm messages will initiate an auto-  
dial call.  
If the auto-dial numbers were specified at time of order or installation, the numbers are pre-pro-  
grammed into the system. However, if the numbers need to be changed, follow the steps listed below  
to reprogram the auto-dialer at the SCC.  
1. From the System Configuration screen, press the Up or Down pad to move the highlighted cursor  
to Auto Dial.  
2. Press the Select pad. The Auto Dial screen will appear.  
3. Move to and select the first Auto Dial Number.  
4. Press the Select pad to move the arrow to the next digit to the right.  
5. When the arrow is on the digit to be changed, press the Up pad to increase the number or press  
the Down pad to decrease it. Press Select to set the value and move to the next digit.  
6. After all of the changes have been made, press the Select pad again to return to the System  
Configuration screen.  
7. If required, go to the Second Number screen and enter the correct number.  
Figure 32 Auto dial setting screen  
UP: CURSOR UP  
DOWN: CURSOR  
SELECT: CHOOSE  
AUTO DIAL SETTING SCREEN  
EXIT  
Enable Auto Dial ............................................................. YES  
Enable Communication Check........................................ NO  
Modem Baud Rate .......................................................... 2400  
Auto Dial Number............................................................ 1 800 555-1234  
Second Number....................................................... 0 000 000-0000  
Modem Initialization String .............................................. xxxxxxxxxxxxx  
Set Communication Check Time..................................... 00:00  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
Modem Baud Rate  
This sets the transmission rate at which the system relays data to a terminal through the modem.  
Figure 33 Modem baud rate  
UP: CURSOR UP  
DOWN: CURSOR  
SELECT: CHOOSE  
AUTO DIAL SETTING SCREEN  
EXIT  
Enable Auto Dial ............................................................. YES  
Enable Communication Check........................................ NO  
Modem Baud Rate .......................................................... 2400  
Auto Dial Number............................................................ 1 800 555-1234  
Second Number....................................................... 0 000 000-0000  
Modem Initialization String .............................................. xxxxxxxxxxxxx  
Set Communication Check Time..................................... 00:00  
To change the modem baud rate, do the following at the SCC:  
1. From the System Configuration screen, press the Up or Down pad to move the highlighted cursor  
to Auto Dial.  
2. Move to and select the Modem Baud Rate.  
3. Press the Up or Down pad to display the desired baud rate.  
4. Press the Select pad to set the baud rate and to return to the System Configuration screen.  
Maximum Auto-Retransfer Attempts  
When a UPS output overload condition exceeds a pre-programmed current-versus-time window  
(based on the SCC current rating), the UPS automatically transfers the critical load to the bypass  
line. After the overload condition has been corrected, the UPS attempts to automatically retransfer  
the critical load to the UPS output (unless zero attempts is selected). The Maximum Auto-Retrans-  
fer Attempts limits the number of times (0 to 5) that the UPS attempts to retransfer the load back to  
the UPS within a one-hour time period.  
If more than the selected number of overloads occurs during one hour, the critical load remains on the  
bypass line and must be manually retransferred to the UPS system. Note that you should determine  
the cause of any overload condition.  
Note that automatic retransfers are initiated only if the critical load was transferred to the bypass  
line because of a system overload. If an automatic transfer to bypass occurred for any other reason, an  
automatic retransfer will not be initiated. Refer to 3.5.3 - Automatic Retransfers to UPS.  
Figure 34 Maximum auto-retransfer attempts screen  
© 1989-2003  
MAX AUTO-REXFER ATTEMPTS  
LOWER INPUT  
0
UPPER LIMIT  
5
VALUE  
3
UP  
:
INCREASE  
DOWN : DECREASE  
SELECT : EXIT  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
To change the Maximum Auto-Retransfer Attempts parameter, do the following at the SCC:  
1. From the System Configuration Screen, press the Up or Down pad to highlight Maximum Auto-  
Retransfer Attempts.  
2. Press the Select pad. The screen above will appear.  
3. Press the Up pad to increase the value or the Down pad to decrease it.  
4. Press the Select pad to set the value and to return to the System Configuration screen.  
System Current Rating  
System current rating is determined by the part number, which is entered at the factory and cannot  
be changed. Once it has been entered, the part number determines the value displayed for the System  
Current Rating on the SCC system configuration screen (see Figure 29).  
Language Selection  
English and Portuguese are supported.  
System Options  
Figure 35 SCC system options screen  
UP: CURSOR UP  
DOWN: CURSOR DOWN  
SELECT: CHOOSE  
SYSTEM OPTIONS  
EXIT  
LCD Contrast  
Backlight Brightness  
Customer Alarm Interface Board................................NO  
Continuous Duty Static Switch .................................YES  
Figure 36 MMU system options screen  
UP: CURSOR UP  
DOWN: CURSOR DOWN  
SELECT: CHOOSE  
SYSTEM OPTIONS  
EXIT  
LCD Contrast  
Backlight Brightness  
Battery Temp. Compensated Charging......................NO  
Battery Test.............................................................. YES  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Figure 37 Battery test screen—MMU only  
UP: CURSOR UP  
DOWN: CURSOR DOWN  
SELECT: CHOOSE  
BATTERY TEST  
EXIT  
Battery Test Results  
Start Battery Test  
Stop Battery Test  
Select Battery Type...............................................15 min  
Figure 38 Battery test results screen  
UP: CURSOR UP  
DOWN: CURSOR DOWN  
SELECT: CHOOSE  
End DC  
Voltage  
End DC  
Current  
Elapsed  
Time  
Load  
kW  
Starting  
Date  
Starting  
Time  
Start  
Temp.  
Test  
Result  
Continuous Duty Static Switch (Optional)  
This option applies to SCC only. This feature requires installation of a Customer Alarm Interface  
board. When the CDSS feature is enabled and the Customer Alarm Interface option is installed and  
enabled, the mimic display will be modified to include a box in parallel with the bypass circuit  
breaker. The box will be labeled CDSS.  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Figure 39 Monitor/Mimic display example: Continuous Duty Static Switch  
LOAD  
627 KVA / 502 KW  
BYPASS INPUT  
A-B B-C C-A  
480V 480V 480V  
A B C  
755V 755V 755V  
CDSS  
60.0Hz  
UPS RATINGS  
SCCB 1600  
3 OF 3 MODULES  
CONNECTED  
UPS INPUT PWR  
A-B B-C C-A  
480V 480V 480V  
OUTPUT VOLTAGE  
REDUNDANT  
A-B B-C C-A  
480V 480V 480V  
60.0Hz  
MOD 1 ON LINE  
MOD 2 ON LINE  
MOD 3 ON LINE  
OK to Transfer  
Static Switch Connected  
Remote Monitor  
The Remote Monitor Panel (optional) displays eight (8) alarms. These alarms are also available for  
customer use through a set of contacts on a separate terminal board.  
When the New Alarm, System Summary Alarm or Module Summary Alarm is activated, you can get  
more information at the Operator Display Panel or through a remote terminal. Refer to 3.2.15 - Com-  
Table 6  
SCC and module remote monitor indications  
SCC Remote Monitor Indications  
Load On UPS  
Channel Module Remote Monitor Indications  
CH1  
CH2  
CH3  
CH4  
CH5  
CH6  
CH7  
CH8  
Output CB Open  
Battery CB Open  
Battery Discharging  
Low Battery Warning  
Control Failure  
Load On Bypass  
Battery Discharging  
Low Battery Warning  
Overload  
Ambient Overtemp  
System Summary Alarm  
New Alarm  
Ambient Overtemp  
Module Summary Alarm  
New Alarm  
The following alarms, as well as those listed above, will activate the System Summary Alarm or the  
Module Summary Alarm.  
Table 7  
Other alarms that activate summary alarms  
System Summary Alarm  
Module Summary Alarm  
Activation  
Activation  
Control Power Fail  
Emergency Off  
Blower Failed  
Control Power Fail  
DC Capacitor Fuse Blown  
Module Summary Alarm  
Output Over/Under Frequency DC Ground Fault  
Output Overvoltage  
Output undervoltage  
Overload Transfer  
DC Overvoltage Shutdown  
Emergency Off  
Equipment Overtemperature  
Inverter Fault  
Low Battery Shutdown  
Overload  
Static Switch Unable  
Overload Shutdown  
Rectifier Fuse Blown  
Reverse Power  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operation  
3.2.7 Alarm Limit Settings Screen  
Go to the Master Menu and move the highlighted cursor to LIMIT SETTINGS. Press the Select pad  
and the Limit Settings screen is displayed.  
The Alarm Limit Settings screen has Security Access to enable an authorized Liebert field-service  
engineer to adjust the UPS system alarm limit settings.  
CAUTION  
!
All alarm limit settings are application matched and factory-set. They should not be  
changed casually. Contact Liebert Global Services for changing the alarm limit settings.  
Figure 40 Module alarm limit settings screen  
SECURITY ACCESS  
UP: CURSOR UP  
DOWN: CURSOR DOWN  
SELECT: CHOOSE  
ALARM SETTINGS  
EXIT  
Overload Alarm................................................................ 104  
%
DC Over Voltage.............................................................. 600 VDC  
Battery Discharging ......................................................... 480 VDC  
Low Battery...................................................................... 437 VDC  
Battery Shutdown (15 minutes) ....................................... 384 VDC  
Upper Point (60 minutes)................................................. 427 VDC  
Battery Rating (100%) ..................................................... 500 KW 15 min  
Battery Rating ................................................................. 250 KW 45 min  
Battery Float Voltage ....................................................... 540 VDC  
Temperature Limit Settings.............................................. 34°C  
Overload Alarm (SCC and Modules): This alarm setting initiates an alarm message on the display  
screen warning the operator that the UPS system output current has exceeded the specified limit.  
This condition only activates an alarm. The UPS does not shut down, but a separate control circuit  
will transfer the critical load to bypass if the current and time of the overload condition exceeds sys-  
tem capability.  
DC Overvoltage (Modules Only): This setting limits the maximum permitted level of the DC bus  
voltage. When this setting is exceeded, an alarm indication appears on the module display screen. The  
UPS module is taken off-line (the module output circuit breaker is tripped open) and the input and  
battery circuit breakers trip open.  
Battery Discharging (Modules Only): When the battery voltage on the DC bus falls below this  
limit for 5 seconds, a Battery Discharging alarm message is displayed on the module screen. This  
means that the battery is discharging due to an input voltage sag or interruption or a module output  
overload.  
Low Battery (Modules Only): While the battery is discharging, this alarm warns the operator that  
the Battery Shutdown level is approaching. This is generally set for a reserve time of approximately 5  
minutes (typically 10 volts above the 60-Minute Battery Shutdown voltage), based on full load opera-  
tion.  
Battery Shutdown (15 Minutes) (Modules Only): When the battery voltage decreases to this limit  
for five seconds during the first 15 minutes of the discharge, the battery circuit breaker opens to prevent  
overdischarge. Note that the rated battery reserve time at your site may be other than 15 minutes.  
Battery Shutdown (60 Minutes) (Modules Only): During extended outages or deep sags of more  
than 15 minutes, the shutdown voltage limit will ramp up gradually to this 60-minute limit to prevent  
lengthy discharge and possible battery damage. The battery circuit breaker opens when the battery  
voltage and the shutdown limit are equal for five seconds. See the Battery Time screen for more infor-  
mation. Also refer to the battery manufacturer’s manual, available on the manufacturer’s Web site.  
Battery Rating (100%) (Modules Only). This setting is the full load discharge rating of the battery  
in kilowatts for the rated backup period. A typical rating might be 500 kW for 15 minutes.  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Battery Rating (Modules Only): This setting is a battery discharge rating in kilowatts under par-  
tial load for an extended period, typically 60 minutes. The UPS uses the two battery shutdown voltage  
settings and the two battery discharge ratings in computing rated and calculated time remaining dur-  
ing a discharge event.  
Battery Float Voltage  
Both the information entered here and the actual float setting in the hardware are determined based  
on the battery’s requirements. This information is generally available before factory testing and is set  
up at the factory. If the information is not available, it is set to the default of 540VDC.  
Temperature Limit Setting (Optional)  
This setting is visible when the optional battery-temperature-compensated charging board is  
installed. This setting determines the battery temperature that triggers the Battery Overtemp alarm.  
The alarm becomes active when the temperature setting is exceeded for more than one minute.  
NOTE  
The Low Battery alarm setting is designed to be useful at full load battery discharge rates. It is  
typically set for 10 volts above the 60-minute Battery Shutdown voltage, to provide some  
measure of warning under all circumstances. If the discharge period extends past 15 minutes  
(i. e., the load on the UPS is less than full capacity), the Battery Shutdown voltage setting is  
gradually and automatically increased to protect the batteries from deep discharge. The Low  
Battery alarm setting is not automatically increased and should not be relied upon as an  
accurate indicator of battery time remaining. Instead, the operator should consult the Battery  
Time screen or Present Status screen to see the calculated time remaining based on actual  
usage during the discharge period.  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
3.2.8 Load Transfer Procedures Screen  
Go to the SCC Master Menu and move the highlighted cursor to LOAD TRANSFER PROCE-  
DURES. Note that this screen is displayed at the System Control Cabinet but is not required at the  
UPS modules. Press the Select pad and the Load Transfer Procedures screen is displayed.  
The Load Transfer Procedures screen contains instructions to transfer the critical load between the  
UPS system and the bypass line. Comparisons of the UPS and bypass voltage, frequency and phase  
synchronization are displayed along with transfer status messages and an indication of circuit  
breaker overlap time. The metered parameter values on the Load Transfer Procedures screen are  
updated at half-second intervals.  
Refer to 3.4.3 - Load Transfer Procedures for more details.  
Figure 41 Load transfer procedures screen  
1
H
SELECT : MASTER MENU  
VOLTAGE COMPARISON  
2
SYNCHRONIZATION  
A-B B-C C-A  
FREQUENCY  
-30  
0
+30  
60.0 Hz  
60.0 Hz  
UPS  
BYPASS  
-
-
480 480 480  
4
481 480 479  
3
MANUAL  
UPS LEAD  
=
2 Deg  
TRANSFER INSTRUCTIONS  
Adjust the UPS voltage until it equals the  
ON UPS  
1.  
OK TO TRANSFER  
TRANSFER PROHIBIT  
bypass voltage with the VOLTAGE ADJUST pot.  
If the OK TO TRANSFER message is highlighted,  
simultaneously press the BYPASS and CONTROL ENABLE  
2.  
buttons.  
Verify that the transfer was successful by checking the  
3.  
breaker status on the "MONITOR/MIMIC" screen.  
Press the ALARM RESET button to clear alarms which  
4.  
are no longer active  
Item 1 - Voltage Comparisons: This chart shows the UPS and bypass voltage and frequency com-  
parisons between each of the three phases. If the UPS and bypass voltages are not within specified  
tolerances, a manual transfer is not permitted and TRANSFER PROHIBIT is highlighted.  
The Voltage Adjust knob (push-to-turn), located on the SCC Operator Control Panel (Figure 10), is  
used to match the UPS output voltage to the bypass voltage. When the UPS and bypass voltages  
match within the specific tolerance, a manual transfer is possible and OK TO TRANSFER is high-  
lighted.  
CAUTION  
!
The UPS output voltage responds very slowly to inputs from the Voltage Adjust knob.  
Make small adjustments and wait several seconds each time for voltage to stabilize before  
continuing.  
Item 2 - Synchronization: This display shows the phase synchronization between the UPS output  
and bypass power. If the phase displacement is outside of the tolerance, a manual transfer is not per-  
mitted and TRANSFER PROHIBIT is highlighted.  
During normal operation, the synchronization display should read UPS LEAD from zero to 4 degrees.  
Item 3 - Status Messages: Three messages are constantly displayed here. Only the active message  
is highlighted. If TRANSFER PROHIBIT is highlighted, manual transfers/retransfers cannot be  
performed and automatic retransfers will not be initiated.  
Item 4 - Manual Transfer Instructions: These instructions assist the operator in transferring the  
critical load between the UPS system and the bypass line.  
If the load is on the bypass line, step 2 on the screen will instruct you to press the UPS and Control  
Enable buttons to retransfer the load from the bypass line to the UPS system.  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
3.2.9 Start-Up Procedures Screen  
From the SCC Master Menu, move the highlighted cursor to START-UP PROCEDURES. Press the  
Select pad and the SCC Start-Up Procedures screen is displayed (Figure 42).  
This screen contains the steps you must follow to start-up the UPS system. The instructions are listed  
so you can review them prior to performing the start-up.  
Figure 42 SCC start- up procedures screen  
SELECT : MASTER MENU  
© 1989-2003  
START-UP PROCEDURES  
1.  
2.  
Wait approximately two (2) minutes before attempting any other action .  
Select "SYSTEM CONFIGURATION" screen to verify that the correct model number is  
displayed.  
3.  
4.  
Go to the modules(s) and follow the module "STARTUP PROCEDURES".  
Select "MONITOR/MIMIC" screen, verify that the output voltages are at the  
proper nominal level and correct number of modules online is displayed.  
5.  
6.  
If the bypass or static switch breakers are open, refer to Start-up Procedures  
in the UPS manual for instructions on closing these breakers.  
System is now ready to assume load. Select "LOAD TRANSFER PROCEDURES"  
screen for this procedure.  
Prior to this procedure, supply power to the critical load through the bypass line. Start-up each UPS  
module according to the module start-up procedures. You can then transfer the load from bypass to  
the UPS system per instructions on the SCC Load Transfer Procedures Screen.  
Refer to 3.4.1 - SCC Start-Up Procedure for more details.  
NOTE  
If the system was shut down in response to an “Emergency Off” signal (typically because of a  
load fault), there may be alarm messages on the LCD screen that describe system conditions  
before (or at the time of) the shutdown. Some or all of the alarm conditions may have already  
been resolved. To clear these alarm messages, make sure the critical load is on bypass power  
and turn off the control power (see Figure 8 and Figure 9). Wait at least ten minutes for the  
control power circuitry to completely de-energize. After ten minutes, turn control power back on  
and follow the start-up procedures on the UPS and SCC screens.  
From the module Master Menu, move the highlighted cursor to START-UP PROCEDURES. Press  
the Select pad and the module Start-Up Procedures screen is displayed (Figure 43).  
This two-page screen contains the steps you must follow to start-up each UPS system. The instruc-  
tions are listed so you can review them prior to performing the start-up.  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Figure 43 Module start- up procedures screens  
DOWN : NEXT PAGE  
SELECT : MASTER MENU  
© 1989-2003  
START-UP PROCEDURES  
1.  
Verify that the control power is applied to the system control cabinet (check the display  
on the system control cabinet).  
2.  
3.  
Wait approximately two (2) minutes before attempting any other action .  
Select "SYSTEM CONFIGURATION" screen to verify that the correct model is  
displayed.  
4.  
Select "WALK-IN" screen and do the following:  
a)  
Close module input circuit breaker. Verify that the DC voltage bar on  
the display begins to gradually move to the right and the AC input  
current bars do not move to the right more than 10% (40% for modules  
with input filters) after the transformer inrush has subsided.  
UP : FIRST PAGE  
SELECT : MASTER MENU  
© 1989-2003  
START-UP PROCEDURES (Cont'd)  
b)  
c)  
Verify that the output voltage bar moves to the right after the DC  
bus bar has reached the 90% point. Both bars should settle near  
their respective 100% levels.  
If anything happens on the display not mentioned in (a) or (b),  
immediately open the module input circuit breaker and investigate.  
5.  
6.  
If step 4 is successful, select "MONITOR/MIMIC" screen and verify module  
DC bus and output voltages are at proper nominal level. If so, close  
module battery circuit breaker.  
If no alarms are present on the "MONITOR/MIMIC" screen, the module may be  
placed online by closing the module output breaker.  
Prior to this procedure, supply power to the critical load through the bypass line (at the SCC). When  
you close the UPS module input breaker, power is provided to the UPS rectifier. The module DC bus  
voltage ramps up to the nominal battery voltage and the UPS inverter turns on when the DC bus  
reaches the proper voltage. You can then close the battery circuit breaker (MBD) and the UPS module  
output circuit breaker to place the UPS module on-line.  
Refer to 3.4.1 - SCC Start-Up Procedure for more details.  
3.2.10 Shutdown Procedures Screen  
Go to the SCC Master Menu and move the cursor to SHUTDOWN PROCEDURES. Press the Select  
pad and the SCC Shutdown Procedures screen is displayed.  
This screen contains the steps you must follow to perform a controlled shutdown of the UPS system.  
The instructions are listed so you can review them before performing the controlled shutdown.  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Figure 44 SCC shutdown procedures screen  
© 1989-2003  
SHUTDOWN PROCEDURES  
1.  
If load is not already being supplied by the bypass line, select the  
"LOAD TRANSFER PROCEDURE" screen and follow the instructions to transfer  
the load to bypass.  
2.  
3.  
4.  
Go to the modules(s) and follow the module "SHUTDOWN PROCEDURES."  
Press the ALARM RESET button to clear alarms which are no longer active.  
If necessary for maintenance purposes, open the static switch disconnect  
circuit breakers.  
5.  
Wait approximately two (2) minutes before attempting any other action .  
To perform the shutdown procedure, transfer the critical load from the UPS system to the bypass line.  
Shut down each UPS module according to the module Shutdown Procedures.  
Refer to 3.4.5 - Shutdown Procedures for more details, including emergency shutdowns.  
Go to the module Master Menu and move the cursor to SHUTDOWN PROCEDURES. Press the  
Select pad and the module Shutdown Procedures screen is displayed.  
This two-page screen contains the steps you must follow to perform a controlled shutdown of each  
UPS module. The instructions are listed so you can review them before performing the controlled  
shutdown.  
Figure 45 Module shutdown procedures screen  
DOWN : NEXT PAGE  
SELECT : MASTER MENU  
© 1989-2003  
SHUTDOWN PROCEDURES  
1.  
If load can not be supported by the remaining modules when this module  
is taken off line, go to the system control cabinet and select the "LOAD  
TRANSFER PROCEDURES" screen. Follow the instructions to transfer  
to bypass.  
2.  
3.  
4.  
Open the module output breaker by simultaneously pressing the OUTPUT TRIP  
and CONTROL ENABLE pushbuttons.  
Open the module battery breaker by simultaneously pressing the BATTERY TRIP  
and CONTROL ENABLE pushbuttons.  
Manually open the input breaker by moving the handle to the OFF position.  
UP : FIRST PAGE  
SELECT : MASTER MENU  
© 1989-2003  
SHUTDOWN PROCEDURES (Cont'd)  
5.  
6.  
Verify breaker status on the "MONITOR / MIMIC" screen.  
If necessary for maintenance purposes, turn the control power switch (fuse  
disconnect on some models) to the OFF position.  
7.  
Wait a minimum of two (2) minutes before attempting any other action.  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
To perform the shutdown procedure, transfer the critical load from the UPS system to the bypass line  
(at the SCC). Then trip open the UPS module output and battery circuit breaker (MBD) and manually  
open the UPS module input circuit breaker. The Control Power switch may be turned Off if  
required for maintenance procedures.  
Refer to 3.4.5 - Shutdown Procedures for more details, including module shutdowns for service and  
emergency shutdowns.  
3.2.11 Battery Time Screen (Module Only)  
At the Master Menu, move the highlighted cursor to BATTERY TIME. Press the Select pad and the  
Battery Time screen is displayed.  
When AC power is not available to the UPS module, the UPS inverter uses DC power from the battery  
to supply the critical load. This screen helps the operator assess his power resources to determine if  
and when the critical load shutdown procedures need to be started.  
The Battery Time screen is a line graph that tracks the present battery voltage versus the elapsed  
time that the battery has been discharging (Figure 46). As the battery voltage decreases, the line  
representing it moves closer to intersecting the line that represents the battery shutdown voltage.  
When the battery starts to discharge, the screen displays a 15-minute graph. If the battery has been  
providing power for more than 15 minutes, the screen displays a 30-minute graph. If battery power is  
still available after 30 minutes, a 60-minute graph is displayed (Figure 47).  
Figure 46 Battery time screen (15 minute discharge)  
VDC  
500  
SELECT : MASTER MENU  
Low Battery Warning  
Calculated Time (Hrs:Min)  
Total 00:15 Remain 0:01  
480  
460  
440  
420  
400  
380  
360  
340  
Battery Shutdown = 384  
Battery Charge = 5%  
Rated Time (Hrs:Min)  
Total 00:10 Remain 0:00  
0
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15  
Time (Minutes)  
NOTE  
If the UPS modules connect to independent battery plants, consult all the individual module  
screens to get the complete picture. If the modules share a common battery, select one module  
to do the monitoring and disregard the others.  
The screen also displays alarm messages (Battery Discharging, Low Battery Warning and Battery  
Shutdown) and a set of five parameters that inform the operator of battery condition and time  
remaining. The five parameters describing battery resources are:  
Rated Total Time, in hours and minutes, is the amount of battery backup time that should be  
available under full rated load, based on system design.  
Rated Time Remaining is the Rated Total Time less the duration of the present discharge  
event.  
Calculated Total Time is an estimate of the total battery backup time available, based on the  
initial battery condition and actual performance while powering the connected load during the  
discharge event.  
Calculated Time Remaining is a real-time estimation of battery time remaining—with the  
actual connected load—before battery voltage drops to the Battery Shutdown setpoint.  
Battery Charge is the approximate percentage of total designed ampere hours of battery capac-  
ity presently available based on recharge/discharge activity.  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Values for Calculated Total Time and Calculated Time Remaining will appear on the screen approxi-  
mately two minutes after the beginning of the discharge event. Calculated Time Remaining also  
appears on the Present Status Report screen. Both Calculated Total Time and Calculated Time  
Remaining will be updated every six seconds, reflecting actual load changes and battery condition.  
When the Calculated Times become available, they will be displayed in place of the Battery Discharg-  
ing message on this screen.  
Figure 47 Battery time screen (45-minute discharge)  
VDC  
500  
SELECT : MASTER MENU  
Low Battery Warning  
Calculated Time (Hrs:Min)  
480  
460  
440  
420  
400  
380  
360  
340  
Total 00:45 Remain 0:01  
Battery Shutdown = 417  
Battery Charge = 3%  
Rated Time (Hrs:Min)  
Total 00:25 Remain 0:00  
0
10  
20  
30  
40  
50  
60  
Time (Minutes)  
The Battery Time Remaining graph and the Calculated times are extremely helpful to the operator who  
has the discretionary authority to order load-shedding activities. The Series 610 automatically samples  
battery voltage and load current and recomputes every six seconds. This gives the operator fast and  
accurate feedback on efforts to extend battery time remaining by shutting down non-critical loads.  
Figure 48 Accuracy range of values for calculated battery times  
25  
20  
15  
10  
5
0
0
2.5  
5
7.5  
10  
12.5  
15  
17.5  
20  
22.5  
25  
Elapsed Time (Minutes)  
Upper Limit  
Actual  
Lower Limit  
NOTE  
While every effort has been made to make the Rated and Calculated Time Remaining values as  
accurate as practical, these values must be regarded as approximations. At the beginning of the  
discharge cycle, the Calculated times could be off by as much as ±20% due to such variables as  
battery initial charge, age of battery and the subsequent load-shedding activities of the  
operator. Within a few minutes, however, these calculations should settle into their design  
accuracy of ±10%, with the end-of-discharge tolerance being +0, -10% of actual observed time.  
In addition, the operator can adjust the settings affecting Rated Total Time after gaining  
experience with the actual battery and connected load.  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
The Series 610 dynamically adjusts the Battery Shutdown voltage based on battery characteristics  
and the length of the current discharge event. If a discharge event extends past 15 minutes (i.e., the  
load is less than the full design rating), the Battery Shutdown voltage setting is gradually and auto-  
matically increased, to protect the batteries from deep discharge.  
When the battery voltage decreases to a preset limit (see 3.2.7 - Alarm Limit Settings Screen), the  
Low Battery Warning alarm message appears on the display screen. This warns the operator that the  
battery voltage is approaching the Battery Shutdown level—about five minutes of time remaining at  
full rated load.  
NOTE  
The Low Battery alarm setting is designed to be useful at full load battery discharge rates.  
Unlike the Battery Shutdown voltage, the Low Battery alarm setting is not automatically  
increased and should not be relied upon as an indicator of battery time remaining. Instead, the  
operator should consult the Battery Time screen or Present Status screen to see the Calculated  
Time Remaining based on actual usage during the discharge period.  
If the battery discharges to the Battery Shutdown level, represented by the lower line on the Battery  
Time screen, the battery and input circuit breakers trip open and the UPS module is shut down. This  
protects the battery from being damaged by an extended deep discharge.  
CAUTION  
!
When battery shutdown occurs, no power will be supplied to the critical load unless power is  
available through the bypass line from the utility source (or from an engine generator set). If  
you anticipate a battery shutdown (and an engine generator set is not available), either  
transfer the load to bypass (if available) or perform a controlled shutdown of the critical load.  
If the Battery Time screen is displayed while the battery is not discharging, it will display the present  
Battery Charge percentage and the results of the previous discharge event.  
NOTE  
1. During initial UPS start-up, the Battery Charge will display 100%, even though actual  
state of charge may be slightly less. It will normally take three to four days of operation to  
completely charge the battery. After the battery is fully charged the first time, Battery  
Charge will be an accurate indication of battery status.  
2. If Calculated Time Remaining is less than Rated Time Remaining, a battery problem may  
be indicated. Battery maintenance personnel should thoroughly examine the battery plant  
for factors that may reduce battery performance, such as:  
• Battery age  
• Excessive battery discharge/recharge cycles  
• Bad or weak cells  
• Low acid levels in flooded cells  
• Loose electrical connections  
• Ambient temperature extremes  
• Dirty battery jar covers  
3. If the battery plant has been thoroughly examined for proper maintenance and condition  
and the Calculated value is still less than 80% of Rated value, contact Liebert Global  
Services.  
The Series 610 records information about each discharge event. This data can be reviewed on the Bat-  
tery Cycle Monitor screen, as described in 3.2.5 - Status Reports Screens.  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
3.2.12 Meter Calibration Screen  
Go to the Master Menu and move the highlighted cursor to METER CALIBRATION. Press the  
Select pad and the Meter Calibration screen is displayed.  
The Meter Calibration screen enables a Liebert field-service engineer to adjust the calibration of the  
UPS metered functions at each cabinet. Access to these settings is limited by the Security Access con-  
trol.  
NOTE  
Bypass volts are calibrated only at the System Control Cabinet (SCC). Input amps, DC volts,  
DC amps and temperature are calibrated only at the UPS modules.  
CAUTION  
!
Meter calibrations are factory-set and should not require adjustment. Contact Liebert Global  
Services for meter calibration.  
WARNING  
!
Do not attempt to calibrate meters without adequate training. Meter calibration requires  
special test equipment, access to test points in sensitive circuitry and exposure to hazardous  
voltage.  
Figure 49 Meter calibration screen  
UP: CURSOR UP  
SECURITY ACCESS  
DOWN: CURSOR DOWN  
SELECT: CHOOSE  
METER CALIBRATION  
D.C. VOLTS  
D.C. AMPS  
INPUT VOLTS  
INPUT VOLTS  
INPUT VOLTS  
INPUT AMPS  
INPUT AMPS  
INPUT AMPS  
PHASE A-B  
OUTPUT VOLTS  
OUTPUT VOLTS  
OUTPUT VOLTS  
OUTPUT AMPS  
OUTPUT AMPS  
OUTPUT AMPS  
TEMPERATURE  
PHASE A-B  
PHASE B-C  
PHASE C-A  
PHASE A  
PHASE B  
PHASE C  
PHASE B-C  
PHASE C-A  
PHASE A  
PHASE B  
PHASE C  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
3.2.13 Battery Equalize Screen  
Go to the Master Menu and move the highlighted cursor to BATTERY EQUALIZE. Press the Select  
pad and the Battery Equalize screen is displayed.  
The Battery Equalize screen enables the operator to adjust the battery equalize time. It is also used to  
choose between auto and manual battery equalize recharging modes. Note that AUTO MODE can be  
selected only from the System Control Cabinet (SCC). Selections made at the SCC override previous  
selections made at the UPS modules.  
When the input utility power is interrupted, the battery supplies DC power to the UPS module invert-  
ers so there is no interruption of power to the critical load. When the AC input power is restored, the  
battery equalize recharging circuit can be activated automatically or manually to increase the module  
rectifier/charger output voltage to recharge the battery. The battery equalize circuit may also be man-  
ually activated at any time during normal float (constant) voltage operation. The equalizing time can  
be adjusted from 0 to 72 hours.  
Figure 50 Battery equalize screen  
UP  
:
CURSOR UP  
SECURITY ACCESS  
DOWN : CURSOR DOWN  
SELECT : CHOOSE  
© 1989-2003  
BATTERY EQUALIZE RECHARGING  
EXIT  
EQUALIZE TIME PERIOD (hrs.) ...........  
STOP EQUALIZE CHARGE ...................  
MANUAL MODE .....................................  
AUTO MODE ..........................................  
MANUAL / RESET TO AUTO MODE ......  
0
NO  
NO  
YES  
NO  
CAUTION  
!
Do not use the Battery Equalize mode if you have valve-regulated, sealed-cell  
(maintenance-free) batteries. Refer to your battery manufacturer’s manual,  
available on the manufacturer’s Web site.  
EQUALIZE TIME PERIOD. This selection permits the operator to adjust the battery equalize time  
in one hour increments from 0 to 72. The battery equalize time must be greater than zero for the bat-  
tery to begin recharging in both the AUTO and the MANUAL modes. This period is set by use of the  
Up/Down pads and Select pad.  
When the battery is at full voltage (not being recharged), this selection reads EQUALIZE TIME  
PERIOD (hrs). When the battery is recharging, this selection reads EQUALIZE TIME REMAIN-  
ING (hrs). After the equalize recharge time has expired, the indication returns to the preset equalize  
time.  
STOP EQUALIZE CHARGE. This selection lets the operator halt the equalizing charge to the bat-  
tery at any time, whether the circuit was activated automatically or manually.  
MANUAL MODE. This mode enables the operator to manually initiate a battery equalize charge to  
raise the DC bus voltage to correct a non-uniformity in the individual cell voltages or specific gravity  
readings.  
AUTO MODE (SCC only). When the battery recharge control logic is in the AUTO MODE, the UPS  
module battery chargers attempt the equalization process only if the EQUALIZE TIME PERIOD is  
greater than zero, the battery voltage has been at or below the Battery Discharging alarm limit for  
longer than 30 seconds and the battery breakers (MBD) are closed.  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
3.2.14 Alarm and Status Messages  
Module Status Messages  
The module status messages indicate how many UPS modules are included in the system and the  
present status of each module.  
The following status messages may appear in the module status area.  
1. MOD N: A module status message line is displayed for each UPS module in the system. Up to six  
(6) modules may be included in a multi-module system. The N in the message will indicate a  
specific UPS module number, 1 through 6.  
2. ON LINE: The UPS module output circuit breaker is closed and power from the module is available  
to the SCC. The module output is sharing the critical load if the UPS Output Breaker is closed.  
3. OFF-LINE: The UPS module output circuit breaker is open. More specific alarm messages are  
displayed at the UPS module.  
4. SUM ALM: The Module Summary Alarm has been activated by one of the alarm messages listed  
message is displayed at the UPS module.  
5. COM FAIL: The UPS module is not communicating with the SCC. This could mean loss of power  
to the UPS module controls, a disconnected cable or a control logic failure (detected by watchdog  
timer. Call Liebert Global Services if you require assistance. To resume communication after  
control power is restored, sequence display to Master Menu.  
Figure 51 SCC status and alarm message areas  
© 1989-2003  
LOAD  
BYPASS INPUT  
A-B  
0V  
B-C C-A  
627 KVA / 502 KW  
0V  
0V  
A
B
C
0 Hz  
755A 755A 755A  
UPS RATINGS  
SCCT 1600  
3 OF 3 MODULES  
CONNECTED  
REDUNDANT  
UPS INPUT PWR  
A-B  
0V  
B-C C-A  
0V 0V  
OUTPUT VOLTAGE  
Time To Overload  
Transfer: XXXX SEC  
A-B  
B-C C-A  
480V 480V 480V  
60.0 Hz  
MOD 1 ON LINE SUM ALM  
MOD 2 ON LINE SUM ALM  
MOD 3 ON LINE SUM ALM  
Byp Not Avail  
Static Sw Unable  
Module Sum Alm  
Not OK to Transfer  
Static Switch Connected  
MODULE STATUS  
MESSAGES  
SYSTEM STATUS  
MESSAGES  
LOAD BLOCK  
MESSAGES  
ALARM  
MESSAGES  
System Status Messages  
The system status messages indicate whether the static bypass switch is connected or disconnected,  
through the manually operated Static Switch Disconnects (see Figure 9). The status messages  
also advise the operator when a transfer or retransfer between the UPS system and bypass line is per-  
mitted, based on matching voltage, frequency and phase.  
The following status messages may appear in the system status area.  
1. Static Switch Connected: The static switch is connected (the disconnect switches are closed—  
ON) and is ready to provide a current path from the bypass input to the load.  
2. Static Switch Disconnected: The static switch is disconnected (the disconnect switches are  
open—OFF) for maintenance procedures.  
3. OK to Transfer: The UPS system voltage, frequency and phase match the bypass line. This  
means that a transfer between the bypass line and the UPS system is permitted.  
4. Not OK to Transfer: Either the UPS or bypass voltage, frequency or phase is not within the  
specified limits or the static bypass switch is not available. Therefore, manually initiated transfer  
between the bypass line and the UPS system is not permitted. Emergency or overload transfer to  
bypass may still be available provided the “Static Switch Unable” alarm is not indicating.  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Load Block Messages  
Status messages in the Load Block indicate how many modules are in the system, how many modules  
are ON LINE and whether the system is operating in the redundant mode.  
The following status messages may appear in the load block.  
1. N OF X MODULES CONNECTED: The number N is the number of UPS modules ON LINE.  
This means the module output circuit breaker is closed. X is the number of UPS modules in the  
system (connected to this SCC). This number is set from the System Configuration screen.  
2. REDUNDANT: The capacity of the UPS modules ON LINE is sufficient to supply the critical  
load even if one module is taken OFF LINE. The critical load will remain on the UPS system if  
one module goes OFF LINE.  
3. NON-REDUNDANT: The critical load will be transferred to bypass if one module goes OFF  
LINE and you must transfer the load to bypass in order to perform maintenance on any UPS  
module.  
4. TIME TO OVERLOAD TRANSFER: During an overload condition, the time remaining before  
transfer (in seconds) is displayed at the bottom of the load block. At each Module (MMU), the  
message is Time to Overload Shutdown.  
Alarm Messages  
The alarm message area displays the alarm conditions that are present within the UPS system.  
Alarm messages are displayed in flashing reverse video. During normal operation no alarm messages  
should be present. Up to four messages are displayed. To see if any additional alarm conditions are  
present in the UPS system, display the Present Status screen on the control panel.  
Table 9 is a complete list of all alarm messages and corrective actions, if any.  
The first column lists the alarm message, with related alarms grouped together.  
The third column indicates which special functions (if any) are initiated by the alarm.  
D - The alarm initiates an auto-dial call through a user-provided modem to a remote terminal.  
E - Message displayed only on Status Report screens including Event History.  
F - The alarm freezes the History Status Report memory buffer in the cabinet where the alarm is  
displayed. Pressing the Alarm Reset pad for more than 5 seconds will unfreeze the memory  
buffer as long as the alarm is no longer active.  
L - The alarm latches the displayed alarm message. Some alarm conditions are temporary (tran-  
sient) and may not last long enough to be noticed. Latching the display (keeping it on) lets you  
know that an alarm condition has occurred. A latching display alarm remains on the display  
screen until the alarm condition is removed and the Alarm Reset pad is pressed.  
R - The alarm is displayed on an (optional) Remote Monitor Panel. This information is also avail-  
able for customer use through a set of contacts on a separate terminal board.  
S - The alarm initiates a summary alarm at the Remote Monitor Panel and at the SCC.  
The fourth column provides an explanation of the alarm condition, the critical bus status and the  
corrective actions, if any, to remedy the alarm.  
Table 8  
Abbreviations used in alarm messages  
Abbreviation Definition  
Abbreviation Definition  
Auto  
Automatic  
Ov-temp  
O-volt  
Overtemperature  
Avail  
Available  
Overvoltage  
Overvoltage  
Phase Sequence  
Rectifier Fuse  
Retransfer  
Batt  
Battery  
O-volts  
Ph Seq  
Rect Fuse  
Rexfer  
Byp  
Bypass  
Cap Fuse  
Cont Power  
Equip  
Capacitor Fuse  
Control Power  
Equipment  
Shutdn  
Static Sw  
Un-volts  
Xfer  
Shutdown  
H/W  
Hardware  
Static Switch  
undervoltage  
Transfer  
Inv Fuse  
OF/UF  
Inverter Fuse  
Over/Under Frequency  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
Table 9  
Alarm  
Message  
AC INPUT  
Alarm messages - meaning and corrective action  
Cabinet  
Special  
Functions  
Location  
Meaning and Corrective Action  
The rectifier input line voltage is outside of specified limits or the input  
circuit breaker is opened while the battery circuit breaker remains closed.  
The battery supplies power to the critical load through the UPS inverter.  
Provide an alternate source of AC power or prepare to initiate critical load  
procedures when battery reserve time is low.  
Input Fail  
MMU  
DC BUS  
Either the positive (+) or negative (-) DC bus is grounded. No transfer or  
shutdown occurs.  
DC Ground Fault  
MMU  
MMU  
D, L, S  
D, F, S  
Contact Liebert Global Services at once. Do not attempt to locate or repair  
the fault.  
At least one DC capacitor fuse has opened. The UPS module is taken off-  
line and the input and battery circuit breakers trip open.  
Contact Liebert Global Services at once. Do not attempt to reset the  
circuit breakers.  
DC Capacitor  
Fuse Blown  
The module battery circuit breaker (MBD) is open. This circuit breaker can  
be opened either manually or automatically in a UPS shutdown  
procedure. If the UPS is operating with this breaker open, the critical  
load is not protected from loss of the utility source power.  
After AC power is restored and the DC bus is at 100% operating voltage,  
manually close the battery circuit breaker so the rectifier can charge the  
battery.  
Battery CB Open  
MMU  
MMU  
D, R, S  
The battery is discharging. This occurs whenever the battery supplies  
power to the load for more than 5 seconds because of input power failure,  
a rectifier problem or an overload condition. If the input power or a source  
of auxiliary power is restored to the UPS module, the UPS automatically  
returns to normal operation.  
Battery  
Discharging  
D, R, S  
Watch the battery voltage carefully. Reduce the load (begin controlled  
shutdown) to extend the battery back-up time. Reset the UPS alarms after  
the input power is restored. The message clears after 30 seconds.  
The battery voltage is approaching the minimum discharge voltage  
(approximately 5 minutes remaining).  
Complete the controlled shutdown of the critical load. Reset the alarms if  
the input power is restored before shutdown.  
Low Battery  
Warning  
MMU  
MMU  
D, R, S  
The battery voltage has decreased to the minimum discharge value. The  
UPS module is taken off-line (no power to the critical load) and the  
battery and input circuit breakers trip open.  
Perform a UPS system start-up procedure when AC power becomes  
available.  
Low Battery  
Shutdown  
D, F, L, S  
The maximum preset value of the DC Bus voltage has been exceeded.  
The UPS module is taken off-line and the input and battery circuit  
breakers trip open.  
Contact Liebert Global Services at once. A fault may have occurred within  
the UPS. Do not attempt to reset the circuit breaker.  
DC Overvoltage  
Shutdown  
MMU  
SCC  
D, F, L, S  
BYPASS  
The critical load is being supplied power from the bypass line and is  
therefore exposed to utility power disturbances.  
Clear all of the alarms before attempting to retransfer the load from the  
Load On Bypass  
D
bypass line to the UPS.  
Table 9 Abbreviations  
D = auto-dial;  
E = logs only;  
F = freezes;  
L = latches  
R = remote  
S = summary  
D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs  
D# = auto-dial initiated through Module N (1-6) off-line  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
Table 9  
Alarm  
Alarm messages - meaning and corrective action (continued)  
Cabinet  
Special  
Functions  
Message  
Location  
Meaning and Corrective Action  
BYPASS (Cont’d.)  
The critical load has been automatically transferred to the bypass line.  
Use the History Status screen to determine the cause for the transfer.  
Clear all of the alarms before attempting to retransfer the load from  
bypass to UPS.  
Auto Transfer to  
Bypass  
SCC  
SCC  
D, E, F  
An automatic retransfer will be initiated when the OK to Transfer condition  
has been present for 10 seconds, if the overload has dropped below  
100% of the rated SCC current and if enough UPS modules are on-line.  
Auto Retransfer  
Primed  
A manual retransfer is required. Either a system overload condition has  
lasted more than 5 minutes or no more auto-retransfer attempts are  
available. Note that this alarm is only used if auto-retransfer attempts are  
enabled.  
Manual Reset/  
Retransfer  
SCC  
SCC  
Perform a manual retransfer if all necessary conditions are present.  
The UPS output is not synchronized to the bypass power source. The  
static bypass switch is disconnected or it has failed internally.  
Emergency and overload transfer to the bypass source is not available.  
Manually set the Static Switch Disconnects to ON (closed) if the static  
switch is disconnected. If the alarm conditions are automatically  
corrected, reset the alarm to clear it. Contact Liebert Global Services if the  
alarm stays on.  
Static Switch  
Unable  
D, S  
Bypass Not  
Available  
The bypass power source voltage is not within specifications.  
Correct the bypass AC power source.  
SCC  
SCC  
The power conductors on the bypass line are not wired to the UPS in the  
required sequence. This alarm should appear only during initial start-up or  
after a repair to the source power system.  
Disconnect power from the bypass line and correct the wiring. A Liebert  
Global Services representative must be present during initial start-up of  
your UPS System.]  
Bypass Phase  
Sequence Wrong  
D, L, S  
UPS SYSTEM  
At least one input phase differs from the average current by 10% or more  
for four (4) hours. Contact Liebert Global Services. If the condition  
persists, transfer the load to the bypass line.  
Input Current  
Unbalance  
MMU  
SCC  
MMU  
D, E  
D, L, S  
D, L, S  
The logic control power supply from the UPS output is not operating  
properly. The UPS module continues operating but will shut down if the  
input power fails. The SCC continues operating but will shut down if the  
bypass power fails. Contact Liebert Global Services immediately.  
Control Power  
Fail  
Output frequency differs from the nominal (60 Hz) by more than 0.5 Hz.  
No transfer or shutdown occurs.  
Contact Liebert Global Services at once.  
Output Over/  
Under Frequency  
SCC  
SCC  
D, L, S  
The UPS system output voltage is under the minimum (-12%) deviation  
from nominal. The load automatically transfers to the bypass line.  
If the alarm condition is no longer present, reset the alarm and retransfer  
the load from bypass to UPS. Contact Liebert Global Services if alarm  
persists.  
Output  
Undervoltage  
D, F, L, S  
The UPS system output voltage is above the maximum (+10%) deviation  
from nominal. The load automatically transfers to the bypass line. All UPS  
modules are taken off-line and are shut down.  
Contact Liebert Global Services at once. Do not attempt to reset circuit  
breakers.  
Output  
Overvoltage  
SCC  
D, F, L, S  
SCC  
D, R, S  
D, S  
The UPS output current exceeds the rated system load current. This  
condition causes an alarm only, the UPS does not shut down.  
Determine cause of the overload. Reduce the load until the overload  
condition is corrected. Reset the UPS alarm.  
Overload  
MMU  
Table 9 Abbreviations  
D = auto-dial;  
E = logs only;  
F = freezes;  
L = latches  
R = remote  
S = summary  
D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs  
D# = auto-dial initiated through Module N (1-6) off-line  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Table 9  
Alarm  
Message  
Alarm messages - meaning and corrective action (continued)  
Cabinet  
Special  
Functions  
Location  
Meaning and Corrective Action  
UPS SYSTEM (Cont’d.)  
The load on the UPS has exceeded the current versus time window of  
system overload capacity. The UPS system transfers the load to bypass.  
Reduce the load. If the system does not initiate an automatic load  
retransfer, manually retransfer the critical load from the bypass line to the  
UPS. Reset the alarm.  
Overload  
Transfer  
SCC  
D, F, L, S  
SCC  
S
R
An alarm message (see lists in SCC and module remote monitor  
System Configuration Screens) or the watchdog timer has activated the  
Module Summary Alarm.  
Module Summary  
Alarm  
MMU  
Clear alarm conditions, if possible.  
SCC  
D
R
The output circuit breaker of Module N is open. The number N will identify  
the module (1 through 6).  
Review active alarms at Module N and clear alarm conditions, if possible.  
Module N Off  
Line  
MMU  
Inverter output is not synchronized with the UPS system critical bus. This  
also means the output circuit breaker is open and should not be closed  
until the output is in sync. This condition may correct itself. If not, shut  
down the UPS module and then perform a start-up procedure.  
Contact Liebert Global Services if condition persists.  
Inverter  
Nonsynchronized  
MMU  
MMU  
The UPS output current has exceeded 175% of the rated full load or the  
overload capacity has been exceeded. The UPS module is taken off-line  
and shut down.  
Contact Liebert Global Services at once. Do not attempt to reset circuit  
breakers.  
Overload  
Shutdown  
D, F, L, S  
Excessive reverse power flow from the critical bus into the UPS inverter  
has occurred, probably because of low inverter output voltage or a phase  
mismatch. The UPS module is taken off-line and is shut down.  
Contact Liebert Global Services immediately. Do not attempt to reset  
circuit breakers.  
Reverse Power  
MMU  
MMU  
D, F, L, S  
D, F, S  
At least one of the fuses has opened or a rectifier fault was detected. UPS  
module is taken off-line and is shut down.  
Contact Liebert Global Services immediately. Do not attempt to reset  
circuit breakers.  
Rectifier Fuse  
Blown  
At least one of the fuses has opened or an inverter fault was detected.  
The UPS module is taken off-line and is shut down.  
Contact Liebert Global Services immediately. Do not attempt to reset the  
circuit breakers.  
Inverter Fault  
MMU  
SCC  
D, F, S  
S
Communication  
Failure  
The COM FAIL status message is as important as an alarm message.  
The optional Battery Cycle Monitor can retain information about the last  
132 battery discharge events. When the storage buffer approaches its  
capacity, this warning message is broadcast via terminal and modem  
communication channels and a complete listing of all records is sent to  
the terminal port. The message clears after 30 seconds.  
Battery Cycle  
Buffer Warning  
MMU  
D, S  
Battery self-test can be enabled from System Options screen. For test to  
start, the following conditions must be valid:  
1. No Battery Overtemp Alarm must exist.  
2. Battery input and output circuit breakers must be closed.  
3. All three input volt phases must be within nominal range (+10%, -20%).  
4. DC volts must be greater than (DC Ref) -20V. For a 540 bus, the  
nominal float voltage for 240 cells (the DC voltage reference setting) the  
DC voltage on the battery must be greater than 520VDC.  
5. Battery charge must be greater than 90%.  
Battery Exercise  
MMU  
6. Load must be greater than 15%.  
Table 9 Abbreviations  
D = auto-dial;  
E = logs only;  
F = freezes;  
L = latches  
R = remote  
S = summary  
D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs  
D# = auto-dial initiated through Module N (1-6) off-line  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Table 9  
Alarm  
Alarm messages - meaning and corrective action (continued)  
Cabinet  
Special  
Functions  
Message  
Location  
Meaning and Corrective Action  
Battery Temp option must be installed and enabled. Battery Temp  
exceeds the programmed limit set in Alarm Settings screen for more than  
one minutes.  
Battery Overtemp  
MMU  
MMU  
D, S  
D#  
At least one of the following alarm conditions is present: Inverter Fault,  
Rectifier Fuse Blown, Reverse Power, Overload Shutdown, logic power  
supply failure or inverter output symmetry failure. The UPS module is  
taken off-line and is shut down.  
Hardware  
Shutdown  
Contact Liebert Global Services at once. Do not attempt to reset the  
circuit breakers.  
SCC  
The Emergency Module Off (or Emergency Power Off) switch has been  
pressed, which caused the UPS system to shut down and transfer the  
load to the bypass line (or all power to the critical load has been  
shutdown).  
Determine the cause of the emergency condition and correct it if possible.  
Contact Liebert Global Services if you require assistance.  
Emergency Off  
COOLING  
D*, L, S  
MMU  
The intake air to the UPS module exceeds the specified maximum  
temperature.  
This condition only causes an alarm, but should be corrected immediately  
Ambient  
Overtemperature  
MMU  
MMU  
D, R, S  
D, S  
to prevent damage to equipment due to overheating.  
A fault in one or more of the blower motors has occurred. This condition  
only causes an alarm, but if not promptly corrected it could cause an  
equipment overtemperature condition that would shut down the UPS  
module.  
Blower Failed  
Check the blowers for proper operation. Contact Liebert Global Services if  
you require assistance.  
Sensors on power semiconductor heatsinks detect temperatures above  
the steady state limits for these components. The control logic sets off the  
alarm but does not shut down the UPS module if the condition lasts less  
than 10 minutes.  
Check the air intake, air exhaust and filters. Reduce the load or transfer it  
to bypass. Contact Liebert Global Services if the alarm persists.  
Equipment  
Overtemperature  
MMU  
MMU  
D, S  
D, F  
An Equipment Overtemperature condition has persisted for more than 10  
minutes. The UPS module is taken off-line and is shut down.  
Check the air intake, air exhaust and filters before attempting to start-up  
the UPS.  
Overtemperature  
Timeout  
REMOTE MONITOR PANELS  
Load On UPS  
SCC  
SCC  
MMU  
R
R
R
The UPS is operating properly. No corrective action is necessary.  
Another new alarm message has been registered on the UPS system.  
Clear the new alarm condition, if possible.  
New Alarm  
One or more of the UPS system alarm messages has been activated or a  
control logic failure has been detected by a watchdog timer.  
Use the Present Status screen to determine which alarms are active.  
Clear the new alarm condition if possible to do so.  
System Summary  
Alarm  
SCC  
R
R
One or more of the UPS module alarm messages has been activated.  
Use the Present Status screen to determine which alarms are active.  
Clear the new alarm condition, if possible to do so.  
Module Summary  
Alarm  
MMU  
Table 9 Abbreviations  
D = auto-dial;  
E = logs only;  
F = freezes;  
L = latches  
R = remote  
S = summary  
D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs  
D# = auto-dial initiated through Module N (1-6) off-line  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Table 10 Alarm messages - summary  
Alarm Message  
MMU  
X
SCC  
R
Special Functions  
Input Fail  
D, L, S  
D, F, S  
D, S  
DC Ground Fault  
X
DC Capacitor Fuse Blown  
Battery CB Open  
X
X, R  
X, R  
X, R  
X
Battery Discharging  
Low Battery Warning  
Low Battery Shutdown  
DC Overvoltage Shutdown  
Load On Bypass  
D, S  
R
D, S  
X, R  
E
D, F, L, S  
D, F, L, S  
D
X
E
Auto Transfer to Bypass  
Auto Retransfer Primed  
Manual Reset/Retransfer  
Static Switch Unable  
Bypass Not Available  
Bypass Phase Sequence Wrong  
Input Current Unbalanced  
Control Power Fail  
D, F  
X
X
X
D, S  
X
D, L, S  
X
X
D
X, R  
X
D, L, S  
D, L, S  
D, F, L, S  
D, F, L, S  
D, S  
Output Over/Under Frequency  
Output Undervoltage  
Output Overvoltage  
Overload  
X
X
X
X, R  
X
Overload Transfer  
X
D, F, L, S  
Inverter Non-Synchronized  
Module N (1-6) Off Line  
Overload Shutdown  
Reverse Power  
X
R
D
X
X
D, F, L, S  
D, F, L, S  
D, F, S  
D, F, S  
D#  
X
Rectifier Fuse Blown  
Inverter Fault  
X
X
Hardware Shutdown  
Emergency Off  
X
X
D*, L, S  
D, S  
Ambient Overtemperature  
Blower Failed  
X, R  
X
R
R
D, S  
Equipment Overtemperature  
Overtemperature Timeout  
Load On UPS  
X
D, S  
X
D, F  
R
New Alarm  
R
Module Summary Alarm  
System Summary Alarm  
Battery Exercise  
R
X
S
X
R
Battery Overtemp  
X
D, S  
D = Auto-Dial initiated  
D* = Auto-Dial initiated through Auto Transfer to  
Bypass if load is on UPS  
D# = Auto-Dial initiated through Module N (1-6)  
off-line  
E = message displayed on Status Report screens  
F = freezes the History Status Report memory buffer  
L = latches the displayed alarm message  
R = Remote Alarm Contact (optional on MMU)  
S = Summary Alarm (System or Module) initiated  
X = message displayed on Monitor/Mimic screen  
and audible alarm  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
3.2.15 Communication Interfaces  
Your Liebert Series 610 UPS includes the following communication ports:  
• Worldwide reporting to a remote terminal through a modem  
• Reporting to a local terminal (no modem required)  
• Reporting to a local monitor only  
• Site reporting to Liebert SiteScan or other central monitoring system  
• Reporting through an SNMP interface to a building management or network management system  
• Selected alarm messages to a Liebert Remote Monitor Panel and to contact closures for customer  
use  
All external communication devices, including the modem, are optional equipment. Connections to  
communication ports are made by wiring cables to terminal boards at the SCC. Connection points are  
shown on the Control Wiring Interconnect Diagram in the installation manual. Contact Liebert Glo-  
bal Services for assistance when attaching an external device to your UPS system.  
Any terminal that accepts the standard 7-bit ASCII codes and conforms to the data link requirements  
can be used to interface with the Series 610 UPS. If a printer is used, the terminal must support it.  
The UPS does not send or receive any printer control commands.  
Data link requirements are:  
• Asynchronous RS-232 communication  
• Terminals may be configured as DTE or DCE  
• Baud Rate:  
Modem: 1200 or 2400  
Terminal: 2400 only  
• Data Bits: 8  
• Stop Bits: 1  
• Parity: None  
• Handshaking: Not required  
• Full Duplex  
Worldwide Reporting  
The Series 610 transmits UPS system status and history information to a remote terminal in RS-232  
format through a PC-compatible modem.  
Auto-Dial  
The Series 610 UPS communication program will automatically dial a pre-programmed (customer-  
selected) phone number when specified alarm conditions occur. The auto-dial phone number, an alter-  
nate number and the modem baud rate are programmed by using the SCC System Configuration  
screen. The alarm messages that initiate an auto-dial call are identified in Table 9.  
When the auto-dial function is initiated, automatic dial attempts to the first phone number are made  
at periodic intervals for 30 minutes. If unanswered, the system rolls over to the second number and  
repeats calling until connection is made or returns to first phone number after 30 minutes.  
Once a connection is made to a terminal, the system transmits the information on the Present Status  
Report screen, then hangs up. The Present Status Report includes the UPS system identification  
number, date, time, alarm messages and metered parameter indications.  
Requesting Information  
If your Series 610 is equipped with a modem and telephone line, you can call the UPS and receive sys-  
tem status and historical information on discharge events. You can place the call from either a remote  
terminal or a personal computer with a communications program.  
Follow the instructions for your terminal or your communications program to call the UPS. When you  
make connection, the UPS will send you the greeting: “Hello, you are connected to a Series 610.” At  
this point, the UPS will respond to your specific requests for information, according to Table 11.  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
For example, to see a copy of information on the Present Status Report screen from the SCC (see  
Present Status in this manual), press the “A” key (either uppercase or lowercase can be used for all  
except the date and time commands) and then the Enter key. The Series 610 will send the data, which  
will be displayed on your screen. To see the Present Status Report screen from, say, Module 1, type A1  
and press the Enter key. Please note that the data on the screen is like a snapshot—the status of the  
UPS at the moment you requested the information. The information sent remotely is not updated,  
although you can repeat the process at intervals to request the present information.  
Some screens, like the Battery Cycle Monitor information, contain data that you may wish to import  
into a spreadsheet for further calculations. To put this data into a usable format, use the screen-cap-  
ture feature of your communications software (or a separate screen-capture program) to save all or  
part of the data to disk.  
NOTE  
If you save the file with an extension of “.txt,” it can then be imported into a spreadsheet  
program and converted to worksheet format.  
To terminate your connection to the Series 610, press the “H” key and then the Enter key. The UPS  
will hang up its modem and await your next call.  
Local Reporting to a Terminal  
The Series 610 sends UPS system status and history information to a local terminal in RS-232 for-  
mat. No modem is required. The Present Status Report screen is sent to the local terminal whenever  
a new alarm occurs. Commands for requesting information and for changing the date and time are in  
Local Reporting to a Monitor  
A monitor connected to this port will display the same alarm information being sent to the local ter-  
minal. This monitor does not display information going out through the modem port.  
Site Reporting: SiteScan or SNMP  
The SiteScan port sends UPS system information to a Liebert SiteScan Central Monitoring System.  
UPS operation, environmental control systems and facility security can all be monitored from a single  
location. This information can also be sent via SNMP interface to a local network or building manage-  
ment system.  
If your site has SNMP communications, the optional Liebert SiteNet Integrator allows you to monitor  
the status of all the dry-contact outputs of the Series 610. The Integrator module monitors up to 10  
digital inputs and two temperature/humidity sensors and can control two external devices with con-  
tact closure outputs. It can be programmed to activate local audible and visual alarms in addition to  
network “traps.”  
Other communications options include the use of an Ethernet-based Liebert Network Management  
System. Contact your local Liebert representative for further details.  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Remote Monitor Panel  
The Liebert Remote Monitor Panel provides an LED indication of the following conditions:  
• Load On UPS  
• Load On Bypass  
• Battery Discharge  
• Low Battery Warning  
• Overload  
• Ambient Overtemp  
• System Summary Alarm  
• New Alarm  
This information is also available for customer use through a set of contacts on a separate terminal  
board.  
Alarm messages that activate the System Summary Alarm are listed in Table 6 and Table 7.  
The Remote Monitor Panel housing is a NEMA Type 1 enclosure, available for either surface-mount  
or flush-mount installations.  
Separate / Simultaneous Outputs  
The RS-232 interface can support a modem plus either a local terminal or a local monitor. The  
SiteScan port can support either SiteScan or SNMP communications. Whatever communication  
options are installed in the Series 610 UPS can all be used simultaneously.  
Table 11  
Series 610 terminal commands  
Key(s)  
Function  
Displays Present Status Report screen. NOTE: For all three report screens, a numeral 1  
through 6 in place of N will access an individual UPS module. If no numeral is entered,  
you will get a report from the SCC.  
A, return  
AN (N=1 to 6), return  
^B (control-B), return  
^BN (N=1 to 6) return  
Displays Event History Report screen, starting with the most recent frame and then  
scrolling back through earlier frames.  
C, return  
Displays History Status Report screen starting with the most recent frame and then  
^CN (N=1 to 6), return scrolling back through the earlier frames.  
Freezes data output. This stops the data scrolling on the monitor to allow closer study or  
a printout. This is a toggle switch command. Press the F key again to resume data  
scrolling.  
F (no return)  
G, return  
Resets (unfreezes and clears) the History Status Report memory buffer. This erases the  
alarm messages and meter indications that were stored immediately before and after a  
significant system fault. NOTE: Do not reset the History Status Report memory buffer  
until operation and maintenance personnel have reviewed it as a troubleshooting tool.  
The data output stops (quits). The UPS communication system remains on stand-by,  
ready to receive the next communication command. NOTE: To return to the beginning of  
the Event History or History Status Report, press Q, then request your desired report  
again.  
Q (no return)  
This entry sets the date (month/day/year) in the UPS system clock. You must include the  
slash (/) as you key in the date. Note that the d command must be lower case.  
d mm/dd/yy, return  
t hh:mm:ss, return  
H, return  
This entry sets the time (hour:minute:second) in the UPS system clock. You must include  
the colon (:) as you key in the time. Note that the t command must be lower case.  
Prompts the UPS system to hang up its modem (only applicable to the modem  
communications port).  
I, return  
J, return  
K, return  
L, return  
M, return  
Display Battery Cycle Monitor information for 0-30 second discharge events.  
Display Battery Cycle Monitor information for 31-90 second discharge events.  
Display Battery Cycle Monitor information for 91-240 second discharge events.  
Display Battery Cycle Monitor information for over 240 second discharge events.  
Display Status Summary screen of battery discharge events.  
Show detail information on all battery discharge events in order of occurrence  
(last in, first out).  
N, return  
backspace  
Moves cursor left to cancel previous entry or command.  
72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
3.3  
Modes of Operation  
This section illustrates the flow of power through circuit breakers, switches and UPS components  
during various modes of operation. An SCCT with three modules is shown. The same modes of opera-  
tion apply to all configurations of the Liebert Series 610 UPS multi-module system. Highlighted  
(thick) lines in the diagrams indicate power flow and power availability.  
These illustrations show a three-breaker maintenance bypass because it is commonly used. Your instal-  
lation may have a two-breaker, three-breaker or four-breaker maintenance bypass or none at all.  
These illustrations do not show an alternate power source (generator) and automatic transfer switch  
(external to the UPS) that might be present at your installation.  
Table 12 below lists abbreviations for circuit breakers used in this manual.  
Table 12 Circuit breaker abbreviations  
Abbreviation  
Circuit Breaker  
BFB  
BIB  
Bypass Feeder Breaker  
Bypass Input Breaker  
CB1  
CB2  
MBB  
MBD  
MIB  
RIB  
Module Input Breaker  
Module Output Breaker  
Maintenance Bypass Breaker  
Module Battery Disconnect  
Maintenance Isolation Breaker  
Rectifier Input Breaker  
SBB  
System Bypass Breaker  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
3.3.1 Load on Bypass  
Load on Bypass, with the UPS not available, is shown in Figure 52. The UPS system could be in this  
mode of operation during either initial start-up or UPS system shutdown and isolation for mainte-  
nance.  
NOTE  
When the critical load is being supplied power from the bypass line, it is exposed to utility  
power disturbances.  
Figure 52 Load on bypass, UPS not available  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
3.3.2 OK to Transfer  
The OK to Transfer status message will be displayed when the bypass line and UPS system output  
power are both available, their voltage, frequency and phase synchronization are matched within  
specifications and the Static Switch Disconnects are closed (ON). An alarm message may be displayed  
to indicate Load On Bypass. If no alarm is displayed, the operating status is Load On UPS.  
When the OK to Transfer message is displayed, you can perform a manual transfer of the load from  
the UPS system to bypass or a manual retransfer of the load from bypass to the UPS system.  
Use the Load Transfer Procedures screen at the SCC when performing a manual transfer. Refer to  
The UPS system control logic at the SCC will initiate an automatic transfer to bypass if an overload  
condition exceeds the system current versus time window or if a UPS module is taken off line while  
the system is operating in the non-redundant mode. An automatic retransfer to the UPS system may  
be initiated when recovering from system overloads lasting less than five minutes. Refer to 3.5 -  
NOTE  
When the critical load is being supplied power from the bypass line, it is exposed to utility  
power disturbances.  
74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operation  
Figure 53 Load on bypass, UPS available  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
Figure 54 Load on UPS, bypass available  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
Controls  
SKRU  
CB2  
CB2  
CB2  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
3.3.3 Momentary Overloads  
An overload in the critical load will continue to be supplied by the UPS system if the overload condi-  
tion does not exceed the current versus time curve of overload capacity for either the SCC rating or for  
the number of modules on-line.  
For momentary overloads exceeding 155% of rated system (SCC) current, the static switch turns on  
for 40 milliseconds to provide current from the bypass line in parallel with current from the UPS sys-  
tem output. Up to 1000% of rated current can be supplied for less than one cycle, while up to 500% of  
rated load can be sustained for the full 40 milliseconds of pulsed-parallel operation. By providing two  
power sources simultaneously, high current can be supplied to the critical load with full output volt-  
age regulation. The critical load can be supported through inrush currents and momentary faults  
without operating the motorized circuit breakers. Pulse paralleling also serves, under some circum-  
stances, as a backup in the event that an external bypass feeder breaker (e.g., BFB) trips open during  
this pulse-paralleling period, retaining the UPS inverter connection with the critical load.  
If an overload condition exceeds 40 milliseconds, the UPS system continues to supply power to the  
critical load if it remains within the current-versus-time curve of overload capacity. If the system  
overload capacity is exceeded, the UPS control logic at the SCC initiates an automatic transfer to the  
bypass line by operating the static bypass switch and the motorized system circuit breakers (SBB and  
UPS Output). Refer to 3.5 - Automatic Operations.  
Figure 55 Momentary overload, pulsed static bypass switch  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
76  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
3.3.4 Input Power Failure—Load on Battery  
If the utility AC power source fails or is outside the acceptable range, the battery plant becomes the  
power source for the UPS module inverters. The UPS system continues to supply power to the critical  
load and also to the controls of the UPS modules and the SCC.  
You can use the Battery Time screen at the UPS modules to monitor the present battery voltage com-  
pared to the shutdown value. The length of time the battery can sustain the load depends on the size  
of the load and the size and condition of the battery plant. The battery plant is usually large enough  
to supply a 100% rated load for 15 minutes.  
Alarm messages that indicate battery status are Battery Discharge, Low Battery and Battery Shut-  
down. The voltage limits for these alarms are displayed on the UPS module Alarm Limit Settings  
screen. These limits were selected for your installation by Liebert Global Services during initial start-  
up.  
The battery block in the UPS module Monitor/Mimic Display indicates Charge or Discharge and the  
current in Amperes. Maximum battery discharge current ranges from 326 amps (for 150kVA) to 1620  
amps (for 750kVA). Refer to the separate Installation Manual or drawings for specific data on your  
system.  
Figure 56 Input power fail—load on battery  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
3.3.5 One Module Off-Line  
A multi-module UPS system can be supplied with a back-up (redundant) UPS module, which is the  
typical configuration. A redundant system includes one more module than the number required to  
supply the critical load. A redundant system operates in the redundant mode if all modules are ON  
LINE. Note that the UPS system can also operate in the redundant mode with one module OFF  
LINE if the critical load is reduced so that not all ON LINE modules are required. The UPS modules  
share the load and the critical load will remain on the UPS system if any one of the modules is discon-  
nected (goes OFF LINE) for maintenance or because of an internal fault.  
The system control logic monitors the connected critical load and the number of UPS modules ON  
LINE. If the UPS system is operating in the redundant mode, the REDUNDANT status message  
will be displayed at the System Control Cabinet (SCC). If the UPS system is operating in the non-  
redundant mode (redundant module is OFF LINE or was not included in the system configuration),  
the NON-REDUNDANT status message is displayed at the SCC. In the Non-Redundant mode, the  
critical load will be transferred to bypass if any UPS module goes OFF LINE and you must transfer  
the load to bypass in order to perform maintenance on any UPS module.  
Figure 57 One module off-line, load on UPS  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
78  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
3.3.6 Off Battery  
The battery plant can be disconnected from the UPS modules, if required for battery maintenance, by  
opening the module battery disconnect (MBD) circuit breaker(s). In this situation the UPS system  
will continue to supply conditioned power to the critical load, but if input power fails the UPS system  
cannot supply power to the load.  
CAUTION  
!
When the UPS system is operating with the module battery disconnect (MBD) circuit  
breaker(s) open, the critical load is not protected from loss of the utility source power.  
For battery maintenance on multi-module systems, Liebert recommends taking the  
module requiring maintenance off-line before beginning the work. This precaution will  
minimize disturbances on the system bus if input power fails during the maintenance  
work.  
Figure 58 Load on UPS—battery not available  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
3.3.7 Emergency Modules Off  
The Local Emergency Modules Off (LEMO) mode is used to remove power from all UPS system com-  
ponents and the critical load will continue to be supplied through the bypass line.  
The Emergency Module Off control is a guarded pad on the SCC Control Panel (see Figure 10).  
Lift the cover and press the pad. The load will be transferred to bypass and the battery (MBD), input  
and output circuit breakers will be opened (tripped). This will remove power from all UPS system  
components except the controls, system bypass circuit breaker and the static switch.  
Figure 59 Emergency modules off  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
80  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
3.3.8 Remote Emergency Power Off  
The Remote Emergency Power Off (REPO) mode is used to remove all power from the critical load.  
The Remote Emergency Power Off control is a switch located remotely from the UPS system. It will  
normally be in the same room as the critical load equipment. This mode can also be initiated by an  
automatic contact closure in the same external circuit as the manually operated switch.  
When you operate the Remote Emergency Power Off switch, all UPS circuit breakers are opened,  
including the bypass circuit breaker. All power through the UPS is removed from the load. Typically,  
the REPO circuit also opens the circuit breakers that provide power to the bypass lines and the UPS  
controls.  
Figure 60 Emergency power off  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
3.3.9 System Shutdown  
Perform a System Shutdown procedure when you must disconnect the UPS system components from  
all power sources when required for maintenance procedures.  
Use the Shutdown Procedures screen when performing a manual System Shutdown.  
Before performing any maintenance on your Liebert Series 610 UPS System, observe ALL of the  
WARNINGS in 4.0 - Maintenance.  
WARNING  
!
Lethal voltages are present within this system even when it is not on or when power is not  
being supplied. Observe all cautions and warnings in this manual. Failure to do so could  
result in serious injury or death. Do not work on or operate this equipment unless you are  
fully qualified to do so! Never work alone.  
Figure 61 System shutdown  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
3.3.10 Maintenance Bypass  
Maintenance Bypass switchgear (cabinet, panelboard, switchboard or custom switchgear) allows you  
to totally isolate the UPS system from all power sources, while you maintain power to the critical  
load.  
Your installation may have a two-breaker, three-breaker or four-breaker maintenance bypass or none  
at all. The main differences are the locations of the Rectifier Input Breaker and the Bypass Input  
Breaker (BIB).  
Another option that may be present at your site is an alternate power source (generator) and an auto-  
matic transfer switch (ATS).  
Note that to totally isolate the UPS system from all power sources, the Main Input switchgear and  
battery circuit breakers must also be opened  
82  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operation  
.
CAUTION  
!
Instructions for operating the Maintenance Bypass circuit breakers are on the Maintenance  
Bypass cabinet. Make sure you understand the proper sequence before operating any circuit  
breaker. Operating a Maintenance Bypass circuit breaker out of sequence could cut off power  
to the critical load.  
Figure 62 Load on maintenance bypass, two breakers  
RIB  
RIB  
RIB  
BIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
STANDBY GENERATOR  
Figure 63 Load on maintenance bypass, three breakers  
AUTOMATIC  
TRANSFER SWITCH  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
SKRU  
System  
Controls  
CB2  
CB2  
CB2  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
(can accommodate up to 6 UPS modules)  
Battery  
Battery  
Battery  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
3.4  
Manual Procedures  
The Liebert Series 610 UPS system is designed to function while unattended by an operator. The sys-  
tem control logic at the System Control Cabinet (SCC) monitors the performance of the UPS system,  
the availability of power sources and the current required by the critical load.  
The system control logic at the SCC:  
1. Determines what overload conditions can be sustained without a transfer to bypass.  
2. Initiates an automatic transfer to bypass to sustain an overload.  
3. Can initiate an automatic retransfer to the UPS after a system overload has been cleared.  
4. Initiates an automatic transfer to bypass and emergency module shutdown when a specified UPS  
fault occurs.  
The control logic at each UPS module:  
1. Determines what overload conditions can be sustained by the module while it is on-line.  
2. Automatically takes the UPS module off line and initiates an emergency module shutdown when  
selected UPS faults occur.  
Refer to 3.5 - Automatic Operations for more details.  
Manual procedures available to the operator include Start-Up, Load Transfers and Shutdowns. These  
procedures are performed by using the operator control panel and some manually operated circuit  
breakers and switches.  
The LCD at each UPS cabinet includes a screen to help you with each manual procedure by listing  
each step you must perform.  
This section lists step-by-step controls to operate and conditions to observe in the following manual  
procedures:  
1. Start-Up: including initial start-up, recovering from input power failure, recovering from battery  
shutdown and recovering from shutdowns for emergencies or maintenance procedures.  
2. Load Transfers: including transfers from UPS system to bypass and retransfers from bypass to  
the UPS system.  
3. Shutdowns: including module shutdowns for maintenance procedures and emergency  
shutdowns.  
3.4.1 SCC Start-Up Procedure  
When the UPS system has been shut down for any reason, use this procedure to start-up the UPS sys-  
tem to provide filtered, reliable power to the critical load. This procedure gives step-by-step instruc-  
tions for controls to operate and conditions to observe. Your present situation could be initial start-up  
or recovering from input power failure, battery shutdown, maintenance shutdown or an emergency  
shutdown.  
NOTE  
The following procedure assumes that the UPS installation inspection and initial start-up  
have been performed by Liebert Global Services. A Liebert-authorized representative must  
perform the initial system start-up to ensure proper system operation.  
CAUTION  
!
The following procedure provides power to the critical load distribution system. Verify that  
the critical load distribution is ready to accept power. Make sure that personnel and  
equipment are ready for the critical load distribution system to be energized.  
If your installation includes a Maintenance Bypass, you may already be supplying power to the criti-  
cal load equipment through the Maintenance Bypass. If there is no power to the critical load, apply  
power through the UPS bypass line per the following procedure.  
During a start-up procedure, power is supplied to the critical load through the UPS (internal) bypass  
line while the UPS system is being energized. Depending on the reason for your UPS system shut-  
down, you may already have power through the bypass line. You can determine this by observing the  
Monitor/Mimic Display screen at the System Control Cabinet (SCC) after Control Power is available.  
84  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Step 1. Before you apply power to the UPS modules, determine the position of the following circuit  
breakers and switches:  
a. Bypass Input Breaker (BIB) - If this circuit breaker is closed, you may already have power  
to the critical load through the bypass line. If this breaker is closed, leave it closed. If it is  
open, leave it open until you are ready to energize the bypass line.  
b. System Bypass Circuit Breaker (SBB) - This motorized circuit breaker (Figure 9) should  
be closed unless you are recovering from a Remote Emergency Power Off. You may already be  
supplying power to the critical load through this breaker. If this breaker is open, you will be  
instructed to reset it later in this procedure.  
c. UPS Output Circuit Breaker - This motorized circuit breaker (see Figure 9) should be  
open.  
d. Static Switch Disconnect - This manually operated disconnect (see Figure 9) will be in the  
ON (closed) position unless you are recovering from a shutdown. If the disconnect is OFF  
(open), you will be instructed to reset it and turn it on later in this procedure.  
NOTE  
Depending on SCC model, the static switch disconnects can be one or two circuit breakers or  
two contactors. The location could be at the front, right or rear of the cabinet. Refer to the  
drawing of the SCC cabinet selected for your UPS system.  
NOTE  
If the system was shut down in response to an “Emergency Off, there may be alarm messages on  
the LCD screen that describe system conditions before (or at the time of) the shutdown. Some or  
all of the alarm conditions may have already been resolved. To clear these alarm messages,  
turn off the control power (see Figure 8 and Figure 9). Wait at least 10 minutes for the control  
power circuitry to completely de-energize. After 10 minutes, turn control power back on and  
wait two minutes before continuing.  
e. Control Power - The fuses for the SCC control power (labeled F7 through F10, located below  
the SCC control boards in Figure 9) should be ON (pushed in) unless you are recovering from  
a maintenance shutdown. If control power is OFF (fuseholders pulled open), leave it OFF  
until you are ready to apply power to the UPS controls.  
CAUTION  
!
If you are recovering from a UPS system shutdown for maintenance procedures, verify that all  
of the SCC doors are closed and latched. All test equipment must be removed from the system.  
All electrical connections must be secure.  
Power must be provided to the UPS controls so the operator can use the LCD and so the system logic  
can perform its control functions. Note that you can use the LCD to monitor UPS system status, even  
when the UPS modules are not operating.  
During a start-up procedure, power is supplied to the critical load through the UPS (internal) bypass  
line while the UPS modules are being energized. Depending on the reason for your UPS system shut-  
down, you may already have power through the bypass line. You can determine this by observing the  
Monitor/Mimic Display screen at the System Control Cabinet (SCC).  
85  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Step 2. If the bypass line is not supplied to the SCC, the LCD screen will be blank. Energize the  
bypass line by operating the following controls:  
a. Close the Bypass Input Breaker (BIB). This breaker may be in your Maintenance Bypass  
cabinet.  
NOTE  
Wait two minutes after applying bypass power before you operate any other UPS controls.  
CAUTION  
!
DO NOT assume that the UPS System Bypass Breaker (SBB) is closed.  
Instructions for operating the Maintenance Bypass circuit breakers are on the Maintenance  
Bypass cabinet.  
Make sure you understand the proper sequence before operating any circuit breaker.  
Operating a Maintenance Bypass circuit breaker out of sequence could cut off power to the  
critical load.  
Operations involving MIB and MBB MUST only be done when the UPS system is on internal  
bypass.  
b. Ensure the SCC Control Power Disconnect is ON. Open the door to the SCC control section  
and locate the fuseblock F7 through F10 (see Figure 9). If they are not connected already,  
push the fuseholders in to turn ON control power, then reclose the SCC control door.  
c. Observe the Monitor/Mimic Display screen to determine if your System Bypass circuit  
breaker (SBB) is closed and whether the UPS Bypass line is supplying power to the critical  
load.  
If your System Bypass circuit breaker is open (as in recovering from an Emergency Power Off  
or Low Battery Shutdown), close this circuit breaker as follows:  
1. Open the SCC control panel door and find the Transfer Relay Board (Figure 11). If the  
red LED (CR18) labeled TOT S/D (Total Shutdown) is on, press the Bypass Reset switch  
(SW1) on this board. The red LED should turn off.  
2. Set the Static Switch Disconnects (Figure 9) OFF (open), if not off already.  
NOTE  
Depending on SCC model, the static switch disconnects can be one or two circuit breakers or  
two contactors. The location could be at the front, right or rear of the cabinet. Refer to the  
drawing of the SCC cabinet selected for your UPS system.  
3. Find the Close Bypass switch (SW1) on the System Interface Board (Figure 11, Item 3).  
Press this switch to reset the System Bypass circuit breaker. Check the Monitor/Mimic  
screen to verify the breaker is closed.  
d. If currently OFF, close the Static Switch Disconnects.  
NOTE  
Depending on SCC model, the static switch disconnects can be one or two circuit breakers  
or two contactors. The location could be at the front, right or rear of the cabinet. Refer to the  
drawing of the SCC cabinet selected for your UPS system.  
4. Press two Reset Switches for Static Switch Disconnects behind door below SCC  
control panel (see Figure 9). Note that in an SCCT less than 1600A, there is no Reset  
Switch for the Static Switch Disconnect, so this step is not necessary.  
5. Set the Static Switch Disconnects to ON (closed).  
86  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
e. If the UPS Bypass line is available, but not yet supplying power to the load, close the circuit  
breakers (external to the UPS) required to provide power to the critical load equipment.  
Follow the three steps shown below.  
CAUTION  
!
Be sure to operate Maintenance Bypass circuit breakers in the proper sequence.  
1. Verify the Bypass Input Breaker (BIB) and System Bypass circuit breakers are closed.  
2. Close the Maintenance Isolation Breaker (MIB).  
3. Open the Maintenance Bypass Breaker (MBB).  
Observe the Monitor/Mimic Display screen to confirm that the UPS Bypass line is energized and sup-  
plying power to the critical load equipment.  
At the System Control Cabinet (SCC), press the Select pad to put the Master Menu on the LCD.  
Move the highlighted cursor to Start-Up Procedures (use the Up and Down pads). Press the Select  
pad to display the Start-Up Procedures screen. Return to this screen whenever you need to see the  
start-up instructions.  
Perform a module start-up procedure at each module in your UPS system until all required modules  
are on-line. Refer to 3.4.2 - UPS Module Start-Up for instructions. After the module start-up is com-  
plete, return to the SCC (see 3.4.3 - Load Transfer Procedures) to complete your UPS system  
start-up.  
Figure 64 SCC start-up procedures screen  
SELECT : MASTER MENU  
© 1989-2003  
START-UP PROCEDURES  
1.  
2.  
Wait approximately two (2) minutes before attempting any other action .  
Select "SYSTEM CONFIGURATION" screen to verify that the correct model number is  
displayed.  
3.  
4.  
Go to the modules(s) and follow the module "STARTUP PROCEDURES".  
Select "MONITOR/MIMIC" screen, verify that the output voltages are at the  
proper nominal level and correct number of modules online is displayed.  
5.  
6.  
If the bypass or static switch breakers are open, refer to Start-up Procedures  
in the UPS manual for instructions on closing these breakers.  
System is now ready to assume load. Select "LOAD TRANSFER PROCEDURES"  
screen for this procedure.  
87  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
3.4.2 UPS Module Start-Up  
When a UPS module has been shut down for any reason, use this procedure to start-up the UPS mod-  
ule to provide filtered, reliable power to the critical bus. This procedure gives step-by-step instruc-  
tions for controls to operate and conditions to observe. Your present situation could be initial start-up  
or recovering from input power failure, battery shutdown, maintenance shutdown or an emergency  
shutdown.  
Perform this module start-up procedure at each module in your UPS system until all required mod-  
ules are on-line.  
Step 1. Before you apply power to the UPS module, determine the position of the following circuit  
breakers and switches:  
a. Rectifier Input Breaker (RIB) - If this external circuit breaker is closed, you already have  
power to the UPS cabinet and possibly power to the controls. If this breaker is closed, leave it  
closed. If it is open, leave it open until you are ready to apply power to the UPS cabinet.  
b. Input Circuit Breaker (CB1) - Verify that this breaker on the front of the UPS module  
cabinet (Figure 8) is in the OFF position.  
c. Module Battery Disconnect (MBD) - Verify that this external breaker is open or tripped.  
d. Module Output Circuit Breaker (CB2) - Verify that this breaker on the front of the UPS  
module cabinet (Figure 8) is in the OFF position.  
e. Control Power - The fuses labeled Control Disconnect should be ON (pushed in) unless you  
are recovering from a maintenance shutdown. If control power is OFF (fuseholders pulled  
open), leave it OFF until you are ready to apply power to the UPS controls.  
Power must be provided to the UPS module controls so you can use the LCD and so the system logic  
can perform its control functions. Note that you can use the LCD to monitor UPS status, even when  
the UPS module is not on-line. If the LCD is operating, you already have Control Power. This will be  
the usual condition, unless you are recovering from a maintenance shutdown.  
Step 2. If the LCD is not operating, energize Control Power by operating the following two controls:  
a. Close the Rectifier Input Breaker (RIB), which is outside the UPS cabinet. This will provide  
power to the UPS cabinet but not to any UPS components.  
b. Open the UPS cabinet door and close the Control Disconnect fuseholders to turn the Control  
Power ON. See Figure 8. Close the UPS cabinet door.  
NOTE  
Wait 2 minutes after applying control power before operating any other UPS module controls.  
Press the Select pad on the UPS module to put the Master Menu on the LCD. Move the highlighted  
cursor to Start-Up Procedures (use the Up and Down pads). Press the Select pad to display the  
Start-Up Procedures screen. Return to this screen whenever you need to see the start-up instructions.  
Select the Monitor/Mimic Display on the LCD. In the ALARM MESSAGES block (see Figure 15), the  
only alarm present should be Battery CB Open. If any other alarm messages are present, do not pro-  
ceed with the module start-up. Contact Liebert Global Services (LGS) for assistance.  
88  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
Figure 65 Module start-up procedures screen  
DOWN : NEXT PAGE  
SELECT : MASTER MENU  
© 1989-2003  
START-UP PROCEDURES  
1.  
Verify that the control power is applied to the system control cabinet (check the display  
on the system control cabinet).  
2.  
3.  
Wait approximately two (2) minutes before attempting any other action .  
Select "SYSTEM CONFIGURATION" screen to verify that the correct model is  
displayed.  
4.  
Select "WALK-IN" screen and do the following:  
a)  
Close module input circuit breaker. Verify that the DC voltage bar on  
the display begins to gradually move to the right and the AC input  
current bars do not move to the right more than 10% (40% for modules  
with input filters) after the transformer inrush has subsided.  
UP : FIRST PAGE  
SELECT : MASTER MENU  
© 1989-2003  
START-UP PROCEDURES (Cont'd)  
b)  
c)  
Verify that the output voltage bar moves to the right after the DC  
bus bar has reached the 90% point. Both bars should settle near  
their respective 100% levels.  
If anything happens on the display not mentioned in (a) or (b),  
immediately open the module input circuit breaker and investigate.  
5.  
6.  
If step 4 is successful, select "MONITOR/MIMIC" screen and verify module  
DC bus and output voltages are at proper nominal level. If so, close  
module battery circuit breaker.  
If no alarms are present on the "MONITOR/MIMIC" screen, the module may be  
placed online by closing the module output breaker.  
Select the Walk-In screen on the LCD.  
Step 3. To energize the UPS module, manually close the input circuit breaker (CB1, Figure 8). This  
will provide power to the rectifier. Use the Walk-In screen to monitor the Module DC Bus voltage.  
WARNING  
!
If any abnormal situation occurs during this walk-in procedure, open the input circuit breaker  
and investigate the problem. Each input amps bar should be within 25% of the average bar  
length. Call Liebert Global Services if you need help.  
The Input Amps bars should settle at 25% or less after the momentary inrush current has subsided.  
Verify that the DC Voltage bar begins to gradually move to the right.  
Verify that the Output Voltage bar moves to the right after the DC Voltage bar has reached the 90%  
level. Both bars should settle near the 100% line.  
Select the Monitor/Mimic display from the Master Menu and confirm that the module DC bus and  
AC output are at their proper operating voltages.  
Step 4. When the Module DC Bus voltage is at 100%, you can manually close the module battery dis-  
connect (MBD) circuit breaker (external to the UPS).  
89  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
The Battery block in the Monitor/Mimic Display indicates the battery voltage and charge current.  
NOTE  
The battery charge current may increase quickly, but then should slowly decrease. If you are  
recovering from a battery shutdown or an input power failure, the UPS rectifier will be  
recharging the battery. Recharge current can be more than 100 Amps. The maximum allowable  
recharge current for your unit will depend on the kVA rating and your factory-set battery  
recharge current limit.  
CAUTION  
!
Do not use equalize charging with valve-regulated, sealed-cell batteries. Refer to the battery  
manufacturer’s manual, available on the manufacturer’s Web site, for specific information  
about equalize charging.  
Use the Monitor/Mimic Display screen to determine the condition of the UPS module. Press the  
Alarm Reset pad to clear the Alarm Messages. Refer to Table 9 for an explanation of any remaining  
alarm messages. Call Liebert Global Services if you cannot clear the remaining alarm messages.  
If no alarm messages are displayed, the UPS module is now ready to provide filtered, uninterruptible  
power to the critical bus. Manually close the module output circuit breaker (CB2, Figure 8) to place  
this UPS module on-line.  
When all required UPS modules are on-line, return to the SCC (see 3.4.3 - Load Transfer Proce-  
dures) to complete your UPS system start-up.  
90  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
3.4.3 Load Transfer Procedures  
Use the Monitor/Mimic Display at the SCC to determine the operating condition of the UPS system.  
Press the Alarm Reset pad to clear the Alarm Messages. If all UPS modules are on-line, the only  
message remaining should be Load On Bypass. Refer to Table 9 for an explanation of any other  
remaining alarm messages. Call Liebert Global Services if you cannot clear any remaining alarm  
messages.  
If the only alarm message displayed is Load On Bypass (or no alarms), you can perform a manual  
transfer of the load between the UPS system and the UPS bypass line. Changing the load from the  
UPS system to the UPS bypass is called a transfer. Changing the load from UPS bypass to the UPS  
system is called a retransfer. Note that the UPS system control logic can initiate automatic load  
transfers and retransfers. Refer to 3.5 - Automatic Operations.  
Press the Select pad to display the Master Menu on the LCD of the SCC. Move the highlighted cursor  
to Load Transfer Procedures (using the Up and Down pads). Press the Select pad to display the  
Load Transfer Procedures screen.  
Step 1. Verify that the OK TO TRANSFER message is highlighted. If not (if the TRANSFER PRO-  
HIBIT message is highlighted instead), slowly rotate the Voltage Adjust knob (Figure 10, item 6)  
to match the UPS system voltage to the bypass voltage.  
NOTE  
1. UPS output voltage changes VERY slowly in response to movements of the Voltage Adjust  
knob. To avoid overshooting, allow at least a minute for UPS output voltage to stabilize  
before proceeding to the next step.  
2. If the TRANSFER PROHIBIT message remains, refer to Table 9 for corrective action for  
any alarm messages. Call Liebert Global Services if you cannot solve the problem.  
Figure 66 Load transfer procedures screen  
SELECT : MASTER MENU  
SYNCHRONIZATION  
+30  
VOLTAGE COMPARISON  
A-B B-C C-A  
FREQUENCY  
-30  
0
UPS  
BYPASS  
-
-
380 380 380  
381 380 379  
50.0 Hz  
50.0 Hz  
MANUAL  
TRANSFER INSTRUCTIONS  
UPS LEAD  
=
2 Deg  
ON BYPASS  
ON UPS  
Adjust the UPS voltage until it equals the  
Adjust the UPS voltage until it equals the  
1.  
OK TO TRANSFER  
bypass voltage with the VOLTAGE ADJUST pot.  
TRANSFER PROHIBIT  
2. Ifthli
e
O
K
T
O
T
R
A
N
S
FE es ig ghte  
R
m
s
a
g
e
i
s
h
h
d,  
simultaneously press the UPS and CONTROL ENABLE  
buttons.  
ri  
th
breaker status on the "MONITOR/MIMIC" screen.  
3.  
4.  
V
e
f
y
a
t
th
e
tr  
a
n
s
f
e
r
w
assu  
c
c
e
s
s
fu  
l
b
y checking the
bu to
rethSE tole la ic  
are no longer active.  
P
s
s
e
A
L
A
R
M
R
E
T
t
n
c
a
r
a
r
m
s
w
h h  
Step 2. Perform Step 2 on the Load Transfer Procedures Screen.  
a. If the load is on internal bypass, simultaneously press the UPS and Control Enable  
pads (Figure 10). This will close the motorized UPS Output circuit breaker and open the  
motorized System Bypass circuit breaker (SBB) in a make-before-break sequence.  
b. If the load is on the UPS system, simultaneously press the Bypass and Control Enable  
pads (Figure 10). This will close the motorized System Bypass circuit breaker (SBB) and  
open the motorized UPS Output circuit breaker in a make-before-break sequence.  
Return to the Monitor/Mimic Display screen to monitor the operation of the UPS system. Press the  
Alarm Reset pad to clear any latched alarm messages removed by the new load status. Refer to  
Table 9 if an alarm message other than Load On Bypass is still displayed. Contact Liebert Global  
Services if you require assistance.  
91  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
3.4.4 Maintenance Bypass Load Transfers  
To manually transfer the load between Maintenance Bypass and the UPS system bypass line, care-  
fully follow these instructions. Do not transfer the load between Maintenance Bypass and the UPS  
system (module inverters) output. Use the SCC Monitor/Mimic Display screen to verify the UPS sys-  
tem bypass line is available.  
CAUTION  
!
Make sure you understand the proper sequence before operating any circuit breaker.  
Operating a Maintenance Bypass circuit breaker out of sequence could cut off power to the  
critical load.  
CAUTION  
!
The UPS system (SCC) must be on internal bypass before performing the following  
procedures and operating MIB or MBB or damage to the UPS may occur and the critical load  
may be lost.  
If the load is on the UPS System Bypass:  
a. If the maintenance bypass cabinet or switchboard has an optional 2-key interlock system,  
press the button on the maintenance bypass cabinet to remove the key from the solenoid.  
NOTE  
If the maintenance bypass cabinet or switchboard has any other type of custom interlock, follow  
the specific instructions for that interlock system to remove the key.  
b. If using a key interlock system, insert the key into the lock for the Maintenance Bypass  
Breaker (MBB) to enable it to be closed.  
c. Close the Maintenance Bypass Breaker (MBB).  
d. Verify closure of the MBB. Then open the Maintenance Isolation Breaker (MIB). The UPS  
system is now isolated from the critical load and the load is now on Maintenance  
Bypass.  
e. If using a key interlock system, remove the key from the lock for the Maintenance Isolation  
Breaker (MIB) to lock it open.  
f. If the maintenance bypass cabinet or switchboard has an optional 2-key interlock system,  
replace the key into the solenoid.  
g. If UPS bypass shutdown is required, open the Bypass Input Breaker (BIB).  
If the load is on Maintenance Bypass:  
a. Close the Bypass Input Breaker (BIB) or verify BIB is closed. Note that UPS System Bypass  
circuit breaker (motorized) must also be closed. Refer to 3.4.1 - SCC Start-Up Procedure.  
b. If the maintenance bypass cabinet or switchboard has an optional 2-key interlock system,  
press the button on the maintenance bypass cabinet to remove the key from the solenoid.  
NOTE  
If the maintenance bypass cabinet or switchboard has any other type of custom interlock,  
follow the specific instructions for that interlock system to remove the key.  
c. If using a key interlock system, insert the key into the lock for the Maintenance Isolation  
Breaker (MIB) to enable it to be closed.  
d. Close the Maintenance Isolation Breaker (MIB).  
e. Verify closure of the MIB. Then open the Maintenance Bypass Breaker (MBB). Load is now  
on UPS Internal Bypass.  
f. If using a key interlock system, remove the key from the lock for the Maintenance Bypass  
Breaker (MBB) to lock it open.  
g. If the maintenance bypass cabinet or switchboard has an optional 2-key interlock system,  
replace the key into the solenoid.  
92  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
3.4.5 Shutdown Procedures  
System Shutdown Procedure  
Perform a System Shutdown Procedure when you want to remove power from the UPS system and  
System Control Cabinet (SCC) when required for maintenance or if you need to perform maintenance  
on a UPS module in a non-redundant system.  
Before performing any maintenance on your Liebert Series 610 UPS, observe ALL of the WARN-  
INGS in 4.0 - Maintenance.  
Use the SCC Monitor/Mimic Display to determine the operating condition of the UPS system.  
From the SCC Master Menu, select the Shutdown Procedures screen.  
Figure 67 SCC shutdown procedures screen  
© 1989-2003  
SHUTDOWN PROCEDURES  
1.  
If load is not already being supplied by the bypass line, select the  
"LOAD TRANSFER PROCEDURE" screen and follow the instructions to transfer  
the load to bypass.  
2.  
3.  
4.  
Go to the modules(s) and follow the module "SHUTDOWN PROCEDURES."  
Press the ALARM RESET button to clear alarms which are no longer active.  
If necessary for maintenance purposes, open the static switch disconnect  
circuit breakers.  
5.  
Wait approximately two (2) minutes before attempting any other action .  
Step 1. If the UPS system is supplying power to the load (Load On UPS), select the Load Transfer  
Procedures screen at the SCC and perform a manual transfer to the bypass line (Load On Bypass),  
see 3.4.3 - Load Transfer Procedures. This will open the motorized UPS Output circuit breaker  
(see Figure 9) and close the motorized System Bypass circuit breaker (SBB, Figure 9).  
Step 2. If maintenance is required on the Static Bypass Switch, set the Static Switch Disconnects  
to OFF (open). Refer to Figure 9.  
NOTE  
Depending on SCC model, the static switch disconnects can be two circuit breakers, contactors  
or plug-in connections on a drawout carriage assembly. The location could be at the front, right  
or rear of the cabinet. Refer to the drawing of the SCC cabinet selected for your UPS system.  
CAUTION  
!
The UPS bypass line is still energized.  
Step 3. If maintenance is required in the area of the SCC controls or the motorized system circuit  
breakers (UPS Output and SBB), transfer the load to the Maintenance Bypass, if available (see 3.4.4 -  
CAUTION  
!
If your installation does not include a Maintenance Bypass, power must still be isolated from  
both sides of the UPS circuit breakers if maintenance is required. This will result in loss of  
power to the critical load. Perform an orderly load shutdown before isolating power.  
WARNING  
!
Lethal voltages are present within this unit even when it is not on or when utility is not being  
supplied. Observe all cautions and warnings in this manual. Failure to do so could result in  
serious injury or death. Do not work on or operate this equipment unless you are fully  
qualified to do so! Never work alone.  
Before performing any maintenance on your Liebert Series 610 UPS, observe ALL of the WARN-  
INGS in 4.0 - Maintenance.  
93  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Module Shutdown Procedure  
Perform a Module Shutdown Procedure when you want to remove power from a UPS module when  
required for maintenance.  
Before performing any maintenance on your Liebert Series 610 UPS, observe ALL of the WARN-  
INGS in 4.0 - Maintenance.  
Use the module Monitor/Mimic Display to determine the operating condition of the UPS module.  
From the module Master Menu, select the Shutdown Procedures screen. Note that this is a two-page screen.  
Figure 68 Module shutdown procedures screen  
DOWN : NEXT PAGE  
SELECT : MASTER MENU  
© 1989-2003  
SHUTDOWN PROCEDURES  
1.  
If load can not be supported by the remaining modules when this module  
is taken off line, go to the system control cabinet and select the "LOAD  
TRANSFER PROCEDURES" screen. Follow the instructions to transfer  
to bypass.  
2.  
3.  
4.  
Open the module output breaker by simultaneously pressing the OUTPUT TRIP  
and CONTROL ENABLE pushbuttons.  
Open the module battery breaker by simultaneously pressing the BATTERY TRIP  
and CONTROL ENABLE pushbuttons.  
Manually open the input breaker by moving the handle to the OFF position.  
UP : FIRST PAGE  
SELECT : MASTER MENU  
© 1989-2003  
SHUTDOWN PROCEDURES (Cont'd)  
5.  
6.  
Verify breaker status on the "MONITOR / MIMIC" screen.  
If necessary for maintenance purposes, turn the control power switch (fuse  
disconnect on some models) to the OFF position.  
7.  
Wait a minimum of two (2) minutes before attempting any other action.  
Step 1. If the UPS module is on-line, simultaneously press the Output Trip and Control Enable  
pads (Figure 10). This will open the UPS module output circuit breaker (CB2, Figure 8).  
Step 2. Open the module battery disconnect (MBD) circuit breaker by simultaneously pressing the  
Battery Trip and Control Enable pads (Figure 10).  
Step 3. Open the UPS input circuit breaker by moving the handle to the OFF position (Figure 8).  
Return to the Monitor/Mimic Display to verify status of the circuit breakers. Press the Alarm Reset  
pad to clear alarm messages.  
Step 4. If maintenance is required on the UPS controls, turn the Control Power switch to the OFF  
position (Figure 8). You may also want to open the Rectifier Input Breaker (RIB), external to the  
UPS cabinet.  
WARNING  
!
Lethal voltages are present within this unit even when it is not on or when utility is not being  
supplied. Observe all cautions and warnings in this manual. Failure to do so could result in  
serious injury or death. Do not work on or operate this equipment unless you are fully  
qualified to do so! Never work alone.  
Before performing any maintenance on your Liebert Series 610 UPS, observe ALL of the WARN-  
INGS in 4.0 - Maintenance.  
94  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
Local Emergency Modules Off (LEMO)  
The UPS controls at the SCC include an Emergency Module Off pad (Figure 10, item 12). When  
this guarded pad is pressed, the load is automatically transferred to the bypass line and the  
module output, battery and input circuit breakers trip open to isolate and shut down all the UPS  
modules. Control Power for indicators and alarms remains On.  
Remote Emergency Power Off (REPO)  
The Remote Emergency Power Off control (REPO) is a switch located remotely from the UPS system.  
It will normally be in the same room as the critical load equipment.  
The Remote Emergency Power Off switch removes all power to the critical load.  
When you trip the Remote Emergency Power Off switch, all UPS circuit breakers are opened, includ-  
ing the System Bypass circuit breaker (SBB). All power through the UPS is removed from the  
load. You will still have power to the UPS controls, and you may have power to the static switch.  
3.5  
Automatic Operations  
The Liebert Series 610 UPS system is designed to function while unattended by an operator. The sys-  
tem control logic monitors the performance of the UPS, the availability of power sources and the cur-  
rent required by the critical load.  
The system control logic at the SCC:  
• Determines what overload conditions can be sustained without a transfer to bypass.  
• Initiates an automatic transfer to bypass to sustain an overload.  
• Can initiate an automatic retransfer to the UPS after a system overload has been cleared.  
• Initiates an automatic transfer to bypass and emergency module shutdown when a specified UPS  
fault occurs.  
The control logic at each UPS module:  
• Determines what overload conditions can be sustained by the module while it is on-line.  
• Automatically takes the UPS module off line and initiates an emergency module shutdown when  
selected UPS faults occur.  
95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
3.5.1 Overloads (Without Transfer)  
The UPS system is capable of sustaining full output voltage (±2% of the nominal voltage) for overload  
conditions that remain within (under) the current versus time curve of system overload capacity and  
the capacity of modules on-line (Figure 69). Note that the time scale is not linear. Load On UPS is  
illustrated in Figure 54.  
For high current demands of short duration (momentary overloads) the critical load is supplied simul-  
taneously by both the UPS system and the bypass line. Whenever the critical load requires more than  
155% of the capacity of the modules on-line, the bypass line will supply up to 1000% rated system cur-  
rent through the solid state static switch for 40 milliseconds. Refer to 3.3.3 - Momentary Over-  
loads.  
Whenever an overload condition occurs, you should determine the cause of the overload.  
If an overload condition exceeds the UPS system overload capacity or the capacity of the modules on-  
line, the UPS system initiates an automatic load transfer to the bypass line.  
Figure 69 Current-versus-time curves of module overload capacity  
% Load  
% Load  
1000%  
INVERTER OVERLOAD  
PULSED-PARALLEL  
(FAULT-CLEARING)  
150%  
150%  
100%  
125%  
104%  
100%  
40ms  
30s  
10m  
40ms  
3.5.2 Automatic Transfers to Bypass  
The UPS system will initiate an automatic load transfer to the bypass line if an overload condition  
exceeds the current-versus-time curve of system overload capacity or capacity of the modules on-line  
or if specified UPS system faults occur. Note that when the UPS system is operating in the non-  
redundant mode, an automatic transfer to bypass will be initiated when any UPS module is taken off  
line, either automatically or manually. Load On Bypass is illustrated in Figure 53.  
The Overload Transfer and Output Undervoltage alarm messages will initiate an automatic transfer  
to bypass and the Load On Bypass message will be displayed. The status report screens will include  
the Automatic Transfer to Bypass message. Other UPS system faults will initiate an automatic trans-  
fer to bypass followed immediately by the shutdown and isolation of the UPS modules. Refer to 3.5.5 -  
In an automatic transfer to bypass the UPS Output and System Bypass circuit breakers do not over-  
lap as they do in a manual transfer. The static bypass switch is fired (closed), the UPS Output circuit  
breaker is opened and the System Bypass circuit breaker is closed.  
Bypass power is supplied to the critical load through the static bypass switch during the short time  
while both circuit breakers are open.  
NOTE  
A load transfer to the bypass line will be completed whenever an automatic transfer to bypass  
is initiated. If the OK to Transfer condition is present, the load transfer will be uninterrupted.  
If the Static Switch Unable alarm message is present for any reason, the automatic transfer  
will be interrupted for 40 to 120 milliseconds. Because of the reliability of the UPS components,  
an interrupted load transfer is a very unlikely occurrence.  
96  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operation  
3.5.3 Automatic Retransfers to UPS  
Automatic Retransfer to UPS is an option that you can select from the SCC System Configuration  
screen. If you do not want the UPS system to initiate any automatic retransfers, set Max Auto-Rexfer  
Attempts to zero (0).  
In an automatic retransfer, the two motorized circuit breakers (System Bypass and UPS Output) are  
both closed simultaneously for a short period of time (overlap).  
The following critical bus conditions must be present to initiate an automatic retransfer of the critical  
load from the bypass source to the UPS system:  
1. The number of Auto-Rexfer Attempts selected must be greater than zero (0). If zero (0) is selected,  
no automatic retransfers will occur.  
2. Critical load was initially transferred to the bypass source due to a system overload only. (A  
manually initiated retransfer from bypass is required if the critical load exceeded the capacity of  
the modules on-line or if a UPS fault occurred.).  
3. Overload has since dropped below 100% of the rated SCC current.  
4. Enough UPS modules are on-line to supply the critical load.  
5. OK to Transfer signal received from the control logic for at least 10 seconds, within 5 minutes of  
the system overload transfer. (A manually initiated retransfer from bypass is required for  
overloads lasting 5 minutes or more.)  
6. Cyclic-type overloads, which occur up to five (select range is 0 to 5) times in 60 minutes, are  
automatically returned to the UPS system for each event including the Nth overload. A manually  
initiated retransfer from bypass is required for the N + 1 overload.  
3.5.4 Automatic Module Off-Line  
For specified UPS module faults, the control logic will initiate an automatic isolation and shutdown of  
the UPS module. In the Module Off-Line mode the output, battery (MBD) and input circuit breakers  
are open. If the UPS system was operating in the redundant mode when the module was taken off-  
line, the critical load will remain on the UPS system. If the UPS system was operating in the non-  
redundant mode, an automatic transfer to bypass will be initiated. Note that the bypass line is usu-  
ally not available during Low Battery Shutdown. One Module Off-Line is illustrated in Figure 57.  
The following UPS module faults will initiate an automatic Module Off-Line:  
DC Overvoltage Shutdown  
Hardware Shutdown  
Inverter Fault  
Low-Battery Shutdown  
Overload Shutdown  
Overtemperature Timeout  
Rectifier Fuse Blown  
Reverse Power  
Refer to Table 9 for more information regarding these alarm messages.  
3.5.5 Automatic Emergency Modules Off  
For the specified UPS system fault, the control logic will initiate an automatic transfer to bypass fol-  
lowed immediately by a shutdown and isolation of the UPS system. In the Emergency Modules Off  
mode the output, battery (MBD) and input circuit breakers at each UPS module are open. The System  
Bypass Breaker (SBB) will be closed if the bypass line is available. Emergency Modules Off is  
illustrated in Figure 59.  
The following UPS system fault will initiate an automatic Emergency Modules Off: Output Over Voltage  
Refer to Table 9 for more information regarding alarm messages.  
NOTE  
A load transfer to the bypass line will be completed whenever an automatic transfer to bypass  
is initiated and the bypass line is available. If the OK to Transfer condition is present, the load  
transfer will be uninterrupted. If the Static Switch Unable alarm message is present for any  
reason, the automatic transfer will be interrupted for 40 to 120 milliseconds. Because of the  
reliability of the UPS components, an interrupted load transfer is a very unlikely occurrence.  
Your installation may include a Remote Emergency Power Off mode that can be initiated automatically  
by a contact closure in the critical load equipment. Refer to 3.3.8 - Remote Emergency Power Off.  
97  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Maintenance  
4.0 MAINTENANCE  
4.1 Safety Precautions  
Observe the safety precautions in Important Safety Instructions on page 1 and in 1.3 - Safety  
ONLY qualified service personnel should perform maintenance on the UPS system.  
Observe ALL of the WARNINGS below before performing ANY maintenance on the UPS System and  
associated equipment. Also observe the manufacturer’s safety precautions pertaining to the battery,  
along with the battery safety precautions in this section.  
CAUTION  
!
Always identify connecting wiring prior to disconnecting any wiring.  
Do not substitute parts except as authorized by Liebert Corporation.  
Maintain the UPS cabinets free of foreign materials such as solder, wire cuttings, etc.  
Contact Liebert Global Services if you are not sure of the procedures to follow or if you are not  
familiar with the circuitry.  
WARNING  
!
Extreme caution is required when performing maintenance.  
Be constantly aware that the UPS system contains high DC as well as AC voltages. With  
input power off and the battery disconnected, high voltage at filter capacitors and power  
circuits should be discharged within 30 seconds. However, if a power circuit failure has  
occurred, you should assume that high voltage may still exist after shutdown. Check with a  
voltmeter before making contact.  
AC voltage will remain on the bypass and output circuit breakers and the static bypass  
switch, unless associated external circuit breakers are opened.  
Check for voltage with both AC and DC voltmeters prior to making contact.  
Be sure to read the battery manufacturer’s manual before working on or near the battery.  
Battery terminals will constantly be energized, regardless of whether the UPS is operating or  
not.  
When the UPS system is under power, both the operator and any test equipment must be  
isolated from direct contact with earth ground and the UPS chassis frame by using rubber mats.  
Some components within the cabinets are not connected to chassis ground.  
Any contact between floating circuits and the chassis is a lethal shock hazard. Use differential  
oscilloscopes when measuring a floating circuit. The differential input should have at least  
800 vrms common mode input rating and a common mode rejection ratio of at least 80dB.  
Exercise caution that the test instrument exterior does not make contact, either physically or  
electrically, with earth ground.  
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or  
others approved for use in fighting electrical fires.  
98  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Maintenance  
4.2  
Liebert Global Services  
Start-up, UPS maintenance, battery maintenance and training programs are available for the  
Series 610 UPS through your Liebert sales representative.  
Professional Start-Up  
UPS Start-Up - Liebert’s Customer Engineers perform a thorough non-powered inspection of the  
units and will then conduct a complete electrical checkout which includes calibrating all components  
to published specifications. The battery installation is also inspected and placed on an initialization  
charge to ensure cell equalization. Customer Operation training will be conducted during battery  
charge time.  
Load Bank Testing and Full Site Acceptance Testing are additional services that can be performed  
during a UPS Start-Up. One Preventive Maintenance Service Call can be added to the initial UPS  
Start-Up Agreement.  
Battery Installation/Start-Up - When purchased with a UPS Start-Up, this Agreement provides  
consistent, professional service for your entire UPS system. This one-source approach avoids conflicts  
that may occur during a multisource installation. Note that Liebert requires a mandatory installation  
inspection for all batteries not installed by Liebert Customer Engineers.  
Battery IEEE Certification Inspection - The Battery Specialist will perform a detailed inspection  
of the entire battery system to ensure it meets current IEEE standards.  
Maintenance Agreements: The Signature Program  
UPS Service Agreements - Liebert Global Services (LGS) has a variety of available maintenance  
agreements, depending on specific site needs. Choose the level of support appropriate for each instal-  
lation. Mission-critical sites can have the standard parts-and-labor, around-the-clock coverage for  
their UPS, with or without scheduled preventive maintenance visits. Other sites can benefit from a  
variety of money-saving options.  
As a rule of thumb, Liebert recommends two preventive maintenance visits per year for the UPS. The  
first can be conducted with the UPS operational and includes an infrared scan of key UPS compo-  
nents. The annual visit will require taking the UPS off-line for a thorough nonpowered inspection.  
These visits are in addition to the general housekeeping tasks (changing air filters, etc.) that can be  
performed by customer personnel.  
Battery Service Agreements - The same flexible Signature Program can also be applied to con-  
tracts for battery maintenance. Again, the coverage needed will depend on the type of battery pur-  
chased and the degree of support required from Liebert Global Services.  
Training  
Customer training courses include the proper operation of the system, emergency procedures, preven-  
tive maintenance and some corrective maintenance.  
Warranties  
Contact Liebert Global Services if you have any questions regarding the warranty on your Series 610  
UPS or the batteries.  
99  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Maintenance  
4.3  
Routine Maintenance  
You are encouraged to become thoroughly familiar with the equipment, but at no time should you go  
beyond the specific procedures in this manual while performing maintenance or correcting a malfunc-  
tion. If you have any doubt as to what must be done, call Liebert Global Services at 1-800-LIEBERT  
for further instructions.  
The UPS is designed for unattended operation, but does require some common sense maintenance.  
• Keep good records.  
Troubleshooting is easier if you have historical background.  
• Keep it clean.  
Maintain the UPS free of dust and any moisture.  
• Keep it cool.  
Battery systems must be kept in the range of 72-77°F (22-26°C) in order to meet design specifica-  
tions for capacity and longevity.  
The UPS will reliably meet all performance specifications at temperatures up to 104°F (40°C) and  
can be slightly derated for operation at even higher temperatures or higher altitudes. However,  
performance and longevity will be optimized when the UPS is operated at the same temperature  
as the batteries. Contact your local Liebert sales representative or call 1-800-LIEBERT for fur-  
ther details.  
• Keep connections tight.  
Tighten all connections at installation and at least annually thereafter. (See torque requirements,  
• Periodically inspect external upstream and downstream circuit breakers to assure that the trip  
current settings are correct.  
• Periodically inspect surroundings and ancillary equipment.  
Become familiar with typical ambient conditions surrounding equipment so that abnormal condi-  
tions may be more quickly recognized. Know what typical meter readings are and where adjust-  
able settings should be.  
4.3.1 Record Log  
Set up a maintenance log to record scheduled checks and any abnormal conditions.  
The log should have space for all metered parameter indications including phase readings, alarm  
messages, UPS mode of operation, air filter replacement date and observation notes. A second log  
should be maintained for the battery module as directed by the battery manufacturer.  
A periodic walk-through inspection of the UPS and battery rooms is advised to check for visible and  
audible indications of problems. Log the inspection, metered parameter indications and any discrep-  
ancies.  
4.3.2 Air Filters  
The air filters must be inspected and serviced on a regular schedule. The period between inspections  
will depend upon environmental conditions. Under normal conditions, the air filters will require  
cleaning or replacement approximately every two months.  
All Series 610 models have replaceable filter elements built into the full-width grille across the front  
of the unit. This element can be changed from the front, with the UPS operating.  
Series 610 models rated 300kVA and higher also have recyclable filters built into the front of their  
base assemblies. These metal filter elements can be removed, washed in water, dried and returned to  
service.  
CAUTION  
!
Be certain recyclable filter elements are dry before reinstalling them in the UPS.  
Abnormal or dusty conditions will require more-frequent cleaning and replacement of air filters.  
Inspect installations in new buildings more often, then extend the inspection period as experience dic-  
tates.  
100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Maintenance  
4.3.3 Limited Life Components  
Your Liebert UPS has a design life well in excess of 10 years. Well-maintained units can continue to  
provide economic benefits for 20 years or more. Long-life components are used in your UPS wherever  
practical and cost-effective. However, due to current component material and manufacturing technol-  
ogy limitations, a few components in your Liebert UPS will wear out and require replacement in less  
than 10 years.  
The following limited-life components are utilized in your UPS system. To prevent a wear-out failure  
of one of these components affecting your critical load operations, Liebert recommends these compo-  
nents be periodically inspected and replaced before their expected wear-out life. Individual users may  
have site-specific requirements that differ from these typical life expectations.  
Component  
Expected Life  
Replace in:  
> 7 years  
(~62,000 hours)  
Power AC filter capacitors  
5 to 6 years  
> 7 years  
(~62,000 hours)  
Power DC filter capacitors  
Low-profile fans  
5 to 6 years  
5 to 6 years  
8 to 9 years  
> 7 years  
(~62,000 hours)  
10 years  
(~87,600 hours)  
Squirrel-cage blowers  
Air filters, disposable  
(see also 4.3.2 - Air Filters)  
Check four times  
per year  
1 to 3 years  
Battery, lithium  
10 years  
(~87,600 hours)  
8 to 9 years  
Logic memory backup  
Battery, storage  
Lead-acid wet-cell  
(user selection)  
10 to 20  
years  
1 to 2 years  
prior to end-of-life  
5 years  
3 to 4 years  
6 to 8 years  
Valve-regulated lead-acid  
(VRLA)  
10 years  
Power capacitors are considered “failed” when their measured capacitance is -5% below their name-  
plate rating. Typically, storage batteries are “worn out” when their full-load reserve time is -20%  
below rated. Site-specific battery plants may have different end-of-life requirements. Fans and blow-  
ers typically will stop rotating or rotate slower than expected.  
In most cases, replacement components must exactly match the original component specifications and  
are not readily available from third-party component distributors. For assistance with your specific  
component specifications, replacement component selection and sourcing, call 1-800-LIEBERT.  
For customers using Liebert Global Services (LGS) Preventive Maintenance Services, periodic inspec-  
tion of these components is part of this service, as well as recommending replacement intervals to cus-  
tomers to avoid unanticipated interruptions in critical load operations.  
101  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Maintenance  
4.4  
Battery Maintenance  
WARNING  
!
These maintenance procedures will expose hazardous live parts. Refer servicing to qualified  
personnel.  
DC fuses operate at the rated battery voltage at all times. A blown DC bus fuse indicates a  
serious problem. Serious injury or damage to the equipment can result if the fuse is replaced  
without knowing why it failed. Call Liebert Global Services for assistance.  
4.4.1 Battery Safety Precautions  
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and  
the required precautions. Keep unauthorized personnel away from batteries.  
When replacing batteries, use the same number and type of batteries.  
WARNING  
!
Lead-acid batteries contain hazardous materials. Batteries must be handled, transported and  
recycled or discarded in accordance with federal, state and local regulations. Because lead is a  
toxic substance, lead-acid batteries must be recycled rather than discarded.  
Do not dispose of battery or batteries in a fire. The battery may explode.  
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin  
and eyes. It is toxic.  
A battery can present a risk of electrical shock and high short circuit current. The following  
precautions should be observed when working on batteries:  
• Remove watches, rings and other metal objects.  
• Use tools with insulated handles.  
• Wear rubber gloves and boots.  
• Do not lay tools or metal parts on top of batteries.  
• Disconnect charging source prior to connecting or disconnecting battery terminals.  
• Determine if battery is inadvertently grounded. If inadvertently grounded, remove source  
of ground. Contact with any part of a grounded battery can result in electrical shock. The  
likelihood of such shock will be reduced if such grounds are removed during installation  
and maintenance.  
Lead-acid batteries can present a risk of fire because they generate hydrogen gas. In addition,  
the electrical connections must be protected against accidental short circuits which can cause  
sparks. The following procedures should be followed:  
• DO NOT SMOKE when near batteries.  
• DO NOT cause flame or spark in battery area.  
• Discharge static electricity from body before touching batteries by first touching a grounded  
metal surface.  
• After replacing battery jars in a battery cabinet, replace the retaining straps that hold the  
jars in place on the shelves. This will limit accidental movement of the jars and connectors  
should the cabinet ever need to be repositioned or relocated. Regular maintenance of the  
battery module is an absolute necessity. Periodic inspections of battery and terminal volt-  
ages, specific gravity and connection resistance should be made. Strictly follow the proce-  
dures outlined in the battery manufacturer’s manual, available on the manufacturer’s Web  
site.  
102  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Maintenance  
Battery Safety Precautions In French Per CSA Requirements  
Instructions Importantes Concernant La Sécurité  
Conserver Ces Instructions  
AVERTISSEMENT  
!
Respecter toutes les consignes de sécurité applicables à l'installation, le chargement ou  
l'entretien des batteries. En plus du danger de chocs électriques, le gaz produit par les  
batteries peut exploser dégageant de l'acide sulfurique qui peut entraîner de très graves  
brûlures.  
Toute opération d'entretien/réparation des batteries doit être exécutée ou supervisée par un  
personnel qualifié dans le domaine et en prenant toutes les précautions nécessaires. Tenir le  
personnel non autorisé à l’écart des batteries.  
ATTENTION  
!
Les batteries acide-plomb contiennent des substances toxiques dangereuses. Les batteries  
doivent être manipulées, transportées et recyclées ou jetées conformément à la  
réglementation en vigueur aux niveaux national et local. Le plomb étant toxique, les batteries  
acide-plomb doivent être recyclées et non jetées.  
Ne pas ouvrir ni endommager la ou les batteries. Les électrolytes diffusés sont dangereux  
pour la peau et les yeux. Ils sont toxiques. Ne pas jeter la ou les batteries dans le feu. Risque  
d'explosion.  
Ne jamais installer de batteries avec des cellules fissurées ou endommagées. Contacter  
Liebert Global Services ou le représentant agréé Liebert local.  
Une batterie peut poser un risque de choc électrique et de courant élevé provoqué par un  
court-circuit. Respecter les précautions suivantes lors de travaux sur les batteries:  
• Enlever montres, bagues ou autres objets métalliques.  
• Utiliser des outils dont les poignées sont isolées.  
• Porter des gants et des bottes en caoutchouc.  
• Ne pas poser d'outils ou d'objets métalliques sur les batteries.  
• Déconnecter la source de chargement avant de connecter ou de déconnecter les bornes de  
batterie.  
• Vérifier que la batterie n'a pas été mise à la masse par inadvertance. Si elle est mise à la  
masse, éliminer la source de masse. Tout contact avec des composants de batterie mise à la  
masse peut entraîner un choc électrique. Éliminer le risque de chocs électriques potentiels  
en retirant les sources de masse avant l'installation et la maintenance.  
Les batteries acide-plomb peuvent représenter un risque d'incendie puisqu'elles génèrent de  
l'hydrogène. Respecter les procédures suivantes:  
• NE PAS FUMER près des batteries.  
• NE PAS générer de flammes ou d'étincelles près des batteries.  
• Éliminer l'électricité statique du corps avant de manipuler les batteries en touchant d'abord  
une surface métallique mise à la terre.  
L’électrolyte est un acide sulfurique dilué qui est dangereux au contact de la peau et des yeux.  
Ce produit est corrosif et aussi conducteur electrique. Les procédures suivantes devront être  
observées:  
• Porter toujours des vêtements protecteurs ainsi que des lunettes de protection pour les yeux.  
• Si l’électrolyte entre en contact avec la peau, nettoyer immédiatement en rincant avec de l’eau.  
• Si l’électrolyte entre en contact avec les yeux, arroser immédiatement et généreusement  
avec de l’eau. Demander pour de l’aide médicale.  
• Lorsque l’électrolyte est renversée, la surface affectée devrait être nettoyée en utilisant un  
agent neutralisant adéquat. Une pratique courante est d’utiliser un mélange d’approxima-  
tivement une livre (500 grammes) de bicarbonate de soude dans approximativement un gal-  
lon (4 litres) d’eau. Le mélange de bicarbonate de soude devra être ajouté jusqu’à ce qu’il n’y  
ait plus apparence de réaction (mousse). Le liquide résiduel devra être nettoyé à l’eau et la  
surface concernée devra être asséchée.  
103  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Regular maintenance of the battery module is an absolute necessity. Periodic inspections of battery  
and terminal voltages, specific gravity and connection resistance should be made. Strictly follow the  
procedures outlined in the battery manufacturer’s manual, available on the manufacturer’s Web site.  
Valve-regulated lead-acid (sealed-cell) batteries do require periodic maintenance. Although mainte-  
nance of electrolyte levels is not required, visual inspections and checks of battery voltage and connec-  
tion resistance should be made.  
NOTE  
Do not use cleaners on the batteries. Solvents can make the battery cases brittle. Use only a dry  
cloth or a cloth moistened in water.  
Since individual battery characteristics are not identical and may change over time, the UPS module  
is equipped with circuitry to equalize battery cell voltages. This circuit increases charging voltage to  
maintain flooded type battery cells at full capacity.  
NOTE  
Do not use equalize charging with valve-regulated lead-acid batteries. Consult the battery  
manufacturer’s manual, available on the manufacturer’s Web site, for specific information  
about equalize charging.  
The equalizing charge time period is adjustable from zero to 72 hours and can be initiated automati-  
cally or manually. Refer to 3.0 - Operation.  
Matching Battery Cabinets (Optional)  
Although the individual battery cells are sealed (valve-regulated) and require only minimal mainte-  
nance, the Battery Cabinets should be given a periodic inspection and electrical check. Checks should  
be performed at least annually to ensure years of trouble-free service.  
Voltage Records: With the Battery Cabinet DC circuit breaker closed and the connected UPS oper-  
ating, measure and record battery float voltage. With the DC circuit breaker open, measure and  
record the nominal (open circuit) voltage. Both these measurements should be made across the final  
positive and negative terminal lugs. Compare these values with those shown below. The recorded  
nominal voltage should be no less than the value shown, while the recorded float voltage should be  
within the range shown. If a discrepancy is found, contact Liebert Global Services.  
Battery Voltage (VDC)  
Number of Cells  
Nominal  
Float  
240  
480  
527 - 576  
Power Connections: Check for corrosion and connection integrity. Visually inspect wiring for discol-  
ored or cracked insulation. Clean and/or retighten as required. Refer to torque specifications in  
Battery Cell Terminals: Check for discoloration, corrosion and connection integrity. Clean and  
tighten if necessary. Note that when installing a new battery, the initial torque value is 5 lb.-in. more  
than the retorque value. Table 13 shows battery retorque values.  
104  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Table 13 Battery retorque values  
Battery  
Manufacturer  
Battery  
Model No.  
Retorque  
Value  
UPS12-270(FR)  
UPS12-310(FR)  
UPS12-370(FR)  
UPS12-475(FR)  
LS12-100  
12G-17  
32 lb-in.  
52 lb-in.  
52 lb-in.  
100 lb-in.  
100 lb-in.  
100 lb-in.  
60 lb-in.  
60 lb-in.  
60 lb-in.  
60 lb-in.  
60 lb-in.  
Dynasty  
C&D Batteries  
HX205  
HX300  
Enersys  
HX370  
HX400  
HX500  
If you have a different model battery, contact Liebert Global Services for the required torque value.  
To access battery cell terminals, disconnect the inter-tier cable and two shelf retaining screws. Once  
disconnected, insulate (with protective boot or electrical tape) the cables to prevent accidental shorts.  
The battery shelf can now be pulled out. Tighten each terminal connection to the retorque value.  
When replacing a battery, the terminal connections must be cleaned and tightened. Disconnect and  
insulate the cables connected to the battery. Secure each battery shelf with retaining screws when  
maintenance is complete.  
Rack-Mounted Batteries  
If the UPS system uses a battery other than a factory-supplied Matching Battery Cabinet, perform  
maintenance on the battery as recommended in the battery manufacturer’s maintenance manual,  
available on the manufacturer’s Web site.  
Table 14 Battery voltage record  
Date  
Float Voltage (Volts DC)  
Nominal Voltage (Volts DC)  
Ambient Temp. (°F)  
(To be completed by Liebert Global Services customer engineer at time of start-up)  
105  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Maintenance  
4.4.2 Torque Requirements  
All electrical connections must be tight. Table 15 provides the torque values for the connections in  
the UPS. Use these values unless the equipment is labeled otherwise.  
NOTE  
Refer to the battery manufacturer’s manual, available on the manufacturer’s Web site, for  
the proper torque values required for the battery.  
Table 15 Torque specifications (unless otherwise labeled)  
Nut And Bolt Combinations  
Grade 2  
Standard  
Electrical Connections  
with Belleville Washers  
Bolt Shaft Size  
Lb-in  
53  
N-m  
6.0  
12  
Lb-in  
46  
N-m  
5.2  
6.8  
11  
1/4  
5/16  
3/8  
107  
192  
428  
60  
22  
95  
1/2  
48  
256  
29  
Circuit Breakers with Compression Lugs (For Power Wiring)  
Current Rating  
Lb-in  
N-m  
400 - 1200 Amps  
300  
34  
Circuit Breakers with Compression Lugs (For Control Wiring)  
AWG Wire Size or Range  
Lb-in  
N-m  
#22 - #14  
3.5 to 5.3  
0.4 to 0.6  
4.5  
Detection of Trouble  
It is important that the operator check the instrument readings if abnormal equipment performance  
is suspected. Any metered value that differs appreciably from normal could mean an impending mal-  
function and should be investigated.  
Items to check include:  
• Output voltage of all phases should be within 2% of normal voltage. Output currents on each  
phase should not normally differ by more than 20%. If a greater difference is noted, the load is  
unbalanced and corrective action should be taken to redistribute the load, if possible.  
• If the UPS has not operated on battery power during the last 10 hours, the batteries should  
require little charging current. Battery mimic should indicate normal DC voltage with the battery  
charge current no more than 31 Amperes.  
• Input current on each phase should be within 10% of the average input current.  
• Alarm messages indicate malfunction or impending malfunction. A daily check of the Operator  
Control Panel will help to provide an early detection of problems. Refer to Table 9 and Table 10  
to interpret alarm messages.  
• Tracing a problem to a particular section is facilitated by alarm messages and the metered  
parameter indications. These are stored in the Status Reports and can be displayed at the Opera-  
tor Control Panel or at an optional terminal. A Liebert Global Services engineer will be familiar  
with test points inside the unit.  
NOTE  
If the UPS system has a blown fuse, determine the cause should be determined before replacing  
the fuse. Contact Liebert Global Services for assistance.  
106  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Maintenance  
4.6  
Reporting a Problem  
If a problem occurs within the UPS, review all alarm messages along with other pertinent data. This  
information should be given by telephone to the Liebert service representative’s office nearest you.  
This information can be downloaded to Liebert Global Services by using the optional modem. Contact  
Liebert Global Services at 1-800-LIEBERT to report a problem or to request assistance.  
4.7  
4.8  
Corrective Actions  
For each alarm message on the Operator Control Panel and the Remote Monitor Panel, you can find  
the recommended corrective action in Table 9.  
Recommended Test Equipment  
A list of recommended test equipment and tools required to maintain, troubleshoot and repair the  
UPS module is given in Table 16. You may substitute instruments of equivalent range and accuracy.  
All instruments should be calibrated and be within the current calibration cycle. Calibration data for  
the instruments should be maintained in equipment-history files and the instruments labeled for  
audit and verification.  
Table 16 Recommended test equipment and tools  
Qty  
1
Test Equipment  
Oscilloscope  
Manufacturer  
Tektronix, H-P or Fluke  
Tektronix, H-P or Fluke  
Tektronix, H-P or Fluke  
Fluke  
Model or Type  
DC to 50 MHz  
2
Voltage Probes  
Voltage Probes  
Digital Multi-meter  
Tool Kit  
10X, with 10 ft. cable  
2
100X, with 10 ft. cable  
87, with test leads  
1
1
N/A  
Standard electrical contractor tools  
4.9  
Upstream Feeder Circuit Breaker Setting Inspections  
During normal UPS operations, short-term overload current demand from the bypass source may  
reach 10 times the UPS output current rating. This overload current demand may be caused by the  
magnetizing inrush current of one or more downstream transformers (i.e., PDUs—Power Distribution  
Units) or faults on downstream branch circuits. The instantaneous trip point(s) of the upstream  
bypass feeder breaker(s) must be set to support these temporary overloads. The magnitude of short-  
term overload bypass current demand is typically six to eight times the UPS current rating, but must  
be determined by analysis on a per-site basis. This analysis, generally known as an End-to-End Fault  
Coordination Study, must be done by a Registered Professional Engineer experienced in this activity  
and familiar with local codes and related requirements.  
Liebert strongly recommends periodic inspections of the bypass feeder breaker instantaneous trip set-  
tings, as well as the module input (rectifier) feeder breaker trip settings, to ensure that they are cor-  
rect. For a variety of reasons, although typically during circuit breaker maintenance procedures by  
others, trip settings have been known to be inadvertently left improperly set. Correct trip setting of  
these circuit breakers is most important to achieving high-availability from your Liebert UPS system.  
For further information regarding proper trip settings for your feeder breakers, call 1-800-LIEBERT.  
NOTE  
The instantaneous trip setting of the breaker feeding the UPS bypass input should be high  
enough to accommodate short-duration overloads. The bypass static switch power path inside  
the UPS can draw up to 10 times the system’s rated current for up to three cycles.  
NOTE  
While Liebert can provide typical guidelines, the responsibility for the proper breaker trip  
settings outside the Liebert-manufactured UPS equipment resides with the owner. Contact  
Liebert Global Services at 1-800-LIEBERT for further details.  
107  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Specifications  
5.0 SPECIFICATIONS  
5.1 Rating  
The kVA and kW ratings and the nominal voltages and currents for continuous operation are listed on  
the unit nameplates (inside Operator Control Panel door) and on the System One-Line Diagram. The  
rated output power envelope of the UPS is illustrated in Figure 70. The UPS is rated to deliver rated  
kVA and rated kW at 0.8 lagging power factor (pf), or 0.9 lagging pf for some models. However, the  
UPS will operate connected loads with power factors ranging from 0.7 lagging through 1.0 (unity).  
Connected load kW and kVA are both displayed on the LCD screen when the UPS is powering the  
load. The approximate connected load power factor may be easily calculated by kW ÷ kVA = pf.  
For load power factors between 0.7 lagging and the rated power factor (usually 0.8 or 0.9), the full  
kVA rating of the unit is available. However, above the rated pf the kW rating will become the limit-  
ing factor. Note that some models are specifically rated for a 0.9 lagging output power factor.  
For loads with power factors below 0.7 lagging or with leading power factors, the UPS output is kVA  
limited and the UPS System may not meet all of its output performance specifications. Contact Lie-  
bert Global Services at 1-800-LIEBERT to request assistance for these applications.  
Figure 70 Output power envelope for 0.8 and 0.9 pf rated units  
kW  
1.0  
0.9  
0.9 xkVA  
LEADING  
power factor (pf)  
LAGGING  
power factor (pf)  
0.8  
0.8 xkVA  
0.7  
0.7 xkVA  
Contact Liebert for  
load operation in this  
area  
Contact Liebert for  
load operation in this  
area  
Rated  
kVA  
108  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Specifications  
5.2  
Environmental Conditions  
Table 17 Specifications applicable to environment  
The UPS is housed in a NEMA-1 enclosure. The enclosure is designed for indoor use only  
and is not to be subjected to falling objects or precipitation.  
Enclosure  
Recommended Operating  
Temperature  
25°C ambient  
Maximum Operating  
Temperature  
40°C ambient (design temperature) without derating (see Notes 1- 3).  
Minimum Operating  
Temperature  
0°C  
Storage Temperature  
-20°C to 70°C  
Typical Battery  
Temperature Requirements  
Average annual temperature shall not exceed 27°C. Peak temperature shall not exceed  
43°C during any 24-hour period. See battery manufacturer’s recommendations.  
Relative Humidity  
Operating Elevation  
Storage Elevation  
0 to 95% without condensation  
Sea level to 1219 meters (4000 ft.) without derating  
Sea level to 15,000 meters (50,000 ft.)  
62-69 dBA typical for 100-450kVA units  
72 dBA typical for 500-750kVA units  
75 dBA typical for 1000kVA units  
Audible Noise, measured  
5 feet from unit  
98% at 45°C  
96% at 50°C  
93% at 55°C  
Derating for Higher  
Ambient Temperatures  
(see Note 3)  
Consult your Liebert sales representative regarding applications in high ambient  
temperatures or call 1-800-LIEBERT. Special temperature sensors must be installed at the  
factory.  
% Derating @ 104°F (40°C)  
Ambient (see Note 3)  
% Derating @ 95°F (35°C)  
Ambient (see Note 3)  
Elevation-ft. (m)  
5000 (1524)  
5249 (1600)  
5906 (1800)  
6562 (2000)  
7218 (2200)  
7874 (2400)  
8530 (2600)  
9186 (2800)  
9843 (3000)  
98%  
98%  
97%  
96%  
95%  
94%  
93%  
92%  
90%  
100%  
100%  
99%  
98%  
97%  
96%  
95%  
94%  
92%  
Derating for Higher  
Elevations  
(see Note 4)  
NOTES  
1. This category of electronic equipment is agency rated for use in an atmosphere free of conductive particles. Some industrial facilities  
may require a room air filtration system to keep the UPS free of excess moisture and contaminants.  
2. The UPS system is designed to operate continuously at 40°C. However, design equipment life expectancy will be extended with lower  
temperatures (25°C is recommended).  
3. Ambient temperature is the maximum ambient temperature during any 24-hour period. For operation at higher ambient temperatures,  
consult your Liebert sales representative or call Liebert Global Services at 1-800-LIEBERT.  
4. Exercise care during installation to ensure unimpeded airflow through the UPS system. For operation at higher elevations, consult your  
Liebert sales representative or call Liebert Global Services at 1-800-LIEBERT.  
109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Specifications  
5.3  
Adjustments  
All adjustments are set at the factory or during start-up and normally do not have to be field read-  
justed.  
• Input Current Limit: Normal, 115%; on generator (with optional circuit), 100%  
• Battery Charge Current Limit: Normal, 10%; on generator, 1%  
• Battery Equalize Charge: Set at start-up dependent on battery characteristics  
• DC Overvoltage: 600 volts  
• Overload Alarm: 104% normal load.  
• Output Frequency Tolerance: ±0.5 Hz  
• Output Voltage: Nominal - operator adjustable ±5%  
• Line Drop Compensation: 0 to +5% - set at start-up to match load characteristics; if significant  
additional loads are connected, call Liebert Global Services  
5.4  
Battery Operation  
The separate battery manufacturer’s manual, available on the manufacturer’s Web site, provides the  
necessary information for the installation, operation and maintenance of the battery. Use the battery  
manual in conjunction with this manual.  
The float charge voltage for a battery is equal to the number of cells in series making up the battery  
multiplied by the charge voltage for each cell.  
Since the charging voltage level is critical to proper battery operation, refer to your battery manual,  
available on the manufacturer’s Web site, for information regarding your system.  
For 150-750kVA models with nominal 240 cell battery, the DC bus nominal voltage range is 527 to  
576 VDC. For 100-125kVA models (with 240 cell battery only), the DC bus nominal voltage range is  
534-574 VDC. Maximum equalize voltage is 585 VDC. Battery voltage at end of discharge is 386 VDC  
at the UPS terminals (389 VDC at the battery). The number of battery cells required will range from  
236 to 244, depending on the UPS model and your application.  
110  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Specifications  
5.5  
Electrical Specifications  
RECTIFIER INPUT  
Standard voltages for 100 - 450kVA units: 208, 480 and 600VAC  
Standard voltages for 500 - 1000kVA units: 480 and 600VAC  
Other voltages available on request. 3-phase, 3-wire plus ground.  
Input Voltage  
Voltage Range  
+10%, -15% (no battery discharge at -20%)  
Frequency Range  
57 Hz to 63 Hz  
Less than 3 times normal full load input current for UPS models without optional  
input isolation transformer. Less than 8 times normal full load input current for  
models with optional input isolation transformer and optional input filter  
Subcycle Magnetization Inrush  
Input Current Walk-In  
Current Limit  
From 20% to 100% in 15-20 seconds  
Maximum of 125% normal full load input current  
Less than 30% reflected THD typical at normal full load input current. Less than 7%  
reflected THD typical at normal full load input current with optional input filter  
500kVA to 750kVA models with optional 12-pulse rectifier: Less than 9% reflected  
THD typical at normal full load input current. Less than 4% reflected THD typical at  
normal full load input current with optional input filter  
Current Distortion  
0.85 minimum lagging at full load  
0.92 minimum lagging at full load with optional input filter  
Power Factor  
BYPASS INPUT  
Standard voltages - 208/120 VAC, 480/277 VAC, 600/346 VAC. 3-phase, 4-wire  
plus ground or 3-phase, 3-wire plus ground. Other optional voltages available.  
Optional voltages - 208 VAC, 480 VAC, 600 VAC. 3-phase, 3-wire plus ground  
(ungrounded or corner grounded delta). Other optional voltages available.  
±5% for manually initiated bypass transfer  
±10% for automatically initiated uninterrupted transfer  
Input Voltage  
Voltage Range  
Frequency Range  
59.5 Hz to 60.5 Hz  
Voltage Transient  
±4% for manually initiated bypass transfer  
CRITICAL LOAD OUTPUT  
Standard voltages - 208/120 VAC, 480/277 VAC, 600/346 VAC. Other optional  
voltages available.  
SCC output: 3-phase, 3-wire plus ground or 3-phase, 4-wire plus ground  
Module output to SCC: 3-phase, 4-wire plus ground (neutral required)  
Output Voltage  
Optional voltages - 208 VAC, 480 VAC, 600 VAC. 3-phase, 3-wire plus ground  
(ungrounded or corner grounded delta). Other optional voltages available.  
±0.5% for balanced load  
±2% for unbalanced load  
Voltage Regulation  
Voltage Adjustment Range  
Line Drop Compensation Range  
Frequency  
±5% manually  
Up to +5% automatic load dependent  
595 Hz to 605 Hz  
Slew Rate  
0.01 to 1 Hz per second, adjustable  
120° ±1° for balanced loads  
120° ±3° for 50% unbalanced loads  
Phase Balancing  
Voltage Imbalance  
20% Unbalanced Load ±1% from the arithmetic average of the 3 phases  
50% Unbalanced Load ±2% from the arithmetic average of the 3 phases  
Voltage Transient  
20% Load Step ±4% RMS  
50% Load Step ±4% RMS for 100-750kVA units; ±5% RMS for 1000kVA units  
100% Load Step ±5% RMS for 100-750kVA units; ±8% RMS for 1000kVA units  
Loss or Return of AC Input Power ±1% RMS  
Manual Transfer of 100% Load ±4% RMS  
Voltage Transient Recovery Time  
To within 1% of steady state output voltage within 50 milliseconds  
Maximum 5% RMS total, for any combination of linear and nonlinear loads  
Maximum 3% RMS single, for linear loads  
Voltage Harmonic Content  
Module Overload Capacity  
at Full Output Voltage  
104% of full load rating continuously  
125% of full load rating for 10 minutes  
(System overload capacity depends on 150% of full load rating for 30 seconds  
the configuration of on-line modules.)  
(with ±2% voltage regulation)  
Up to 300% of normal full load current subcycle; up to 500% of normal full load  
current for up to 40 milliseconds with bypass available; up to 1000% of normal full  
load current for up to 16 milliseconds with bypass available  
Fault Clearing  
111  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Specifications  
112  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AC POWER SYSTEMS  
SERIES 610™ UPS  
OPERATION & MAINTENANCE MANUAL  
Technical Support/Service  
The Company Behind the Products  
Web Site  
With over a million installations around the globe,  
Liebert is the world leader in computer protection  
systems. Since its founding in 1965, Liebert has  
developed a complete range of support and  
protection systems for sensitive electronics:  
www.liebert.com  
Monitoring  
800-222-5877  
Outside the US: 614-841-6755  
Single-Phase UPS  
800-222-5877  
Environmental systems—close-control air  
conditioning from 1 to 60 tons  
Power conditioning and UPS with power  
ranges from 300 VA to more than 1000 kVA  
Outside the US: 614-841-6755  
Three-Phase UPS  
800-543-2378  
Integrated systems that provide both  
environmental and power protection in a  
single, flexible package  
Environmental Systems  
800-543-2778  
Monitoring and control—from systems of any  
size or location, on-site or remote  
Outside the United States  
614-888-0246  
Service and support through more than 100  
service centers around the world and a 24/7  
Customer Response Center  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
While every precaution has been taken to ensure the  
accuracy and completeness of this literature, Liebert  
Corporation assumes no responsibility and disclaims all  
liability for damages resulting from use of this information  
or for any errors or omissions.  
Columbus, OH 43229  
Italy  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD)  
+39 049 9719 111  
© 2005 Liebert Corporation  
All rights reserved throughout the world. Specifications  
subject to change without notice.  
Fax: +39 049 5841 257  
Asia  
7/F, Dah Sing Financial Centre  
108 Gloucester Road, Wanchai  
Hong Kong  
® Liebert and the Liebert logo are registered trademarks  
of Liebert Corporation. All names referred to are  
trademarks or registered trademarks of their respective  
owners.  
852 25722201  
SL-25115 (8/05) Rev. 2  
Fax: 852 28029250  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Kut Kwick Lawn Mower RM80 187D User Manual
Linksys Network Card WPC54A User Manual
Makita Grinder GA7011Cx User Manual
Marantz Garage Door Opener VC 8100 User Manual
Maxxsonics Car Amplifier P1 10002 User Manual
Maytag Washer 2206679 User Manual
Melissa Coffeemaker 245 060 User Manual
Melissa Hot Beverage Maker WK 222 User Manual
Mercedes Benz Automobile 2003 CL 500 User Manual
MGE UPS Systems Power Supply EX 5 EX 7 EX 11RT User Manual