Liebert Network Router micro smart switch User Manual

DISCONTINUED  
PRODUCT  
DUAL INPUT POWER DISTRIBUTION  
USER MANUAL  
MICRO SMARTSWITCH  
200 VAC to 240 VAC  
50/60 Hz  
24 Amps  
Download from Www.Somanuals.com. All Manuals Search And Download.  
About This Device  
This guide serves as an outline to assist Qualified personnel with the installation  
of the Liebert Micro SmartSwitch. The input voltage for this Micro SmartSwitch  
unit is 200VAC to 240VAC.  
This Micro SmartSwitch includes the following features:  
Mounts in 1U of rack space  
Provides 12 receptacles on 4 circuit breakers  
Protects against electrical line surges and spikes  
This Micro SmartSwitch is UL and c-UL listed as Information Technology  
Equipment.  
WARNING: There is a risk of personal injury from electrical shock  
and hazardous energy levels. The installation of options and routine  
!
maintenance and service of the product must be performed by individuals  
who are knowledgeable about the procedures, precautions, and hazards  
associated with AC power products (trained service technician).  
To reduce the risk of electrical shock and/or equipment damage when installing  
or servicing the Micro SmartSwitch:  
The Micro SmartSwitch must be disconnected from the product and  
unplugged from the AC electrical outlet before servicing or repairing prod-  
uct.  
Do not overload the output of the Micro SmartSwitch. The total connected  
load should not exceed rated input power.  
Do not exceed the leakage current limit for the Micro SmartSwitch in your  
system. See the “Earth Leakage Current” section later in this document for  
limits.  
Earth Leakage Current  
To reduce the risk of electrical shock due to high leakage current, a reliable  
grounded (earth) connection is essential before connecting Micro SmartSwitch to  
AC power. Observe the following limits when connecting the product to AC  
power distribution devices.  
For products that have attached AC power cords directly connected to the build-  
ing power, the total combined leakage current should not exceed 5 percent of the  
rated input current for the device.  
For products that have detachable AC power cords, the total combined leakage  
current should not exceed 3.5mA.  
Voltage Selection  
On connected equipment that have voltage select switches, make sure that the  
switch is set for the type of voltage you use (208/240 VAC).  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS.  
This manual contains important instructions that should be closely followed dur-  
ing installation and maintenance of this product.  
This product is designed for Commercial/Industrial use only. It is not intended  
for use with life support and other U. S. FDA designated “critical” devices. Max-  
imum load must not exceed that shown on the rating label. See Limited Warranty.  
WARNING:Lethal voltages may be present within this unit even when it is  
apparently not operating. Observe all cautions and warnings in this manual.  
Failure to do so MAY result in serious injury.  
This equipment or Micro SmartSwitch is designed for use on a properly  
grounded (earthed), 208/240 VAC, 50Hz or 60Hz supply.  
ELECTROMAGNETIC COMPATIBILITY- The Micro SmartSwitch complies  
with the limits for a CLASS B digital device, pursuant to part 15 of FCC rules.  
These limits provide reasonable protection against harmful interference. If this  
device is not installed and used in accordance with the instruction manual, it may  
cause harmful interference to radio communications. Not operating this device in  
accordance with these instructions may cause harmful interference, which the  
user must correct at their own expense.  
Operate the Micro SmartSwitch in an indoor environment only in an ambient  
temperature range of 0°C to 50°C (32°F to +122°F). Install it in a clean environ-  
ment, free from conductive contaminates, moisture, flammable liquids, gasses, or  
corrosive substances.  
Turn the Micro SmartSwitch off and isolate it from other equipment before  
cleaning. Use a soft cloth, never liquid or aerosol cleaners.  
Keep the vents free from dust accumulation that could restrict airflow.  
Never block or insert any object into the ventilation holes or other openings.  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
Installation  
Place rear rail [R] over the studs in the front rail [F]. Tighten nuts finger tight.  
The mounting tab [T] will be facing out, so the holes align with the rack sides.  
Adjust length of rail assembly to fit inside rack. Tighten either the wing nuts or  
hex nuts.  
Insert cage nut (one on each side) in rack. Set hooks at rear of rail over holes in  
rack. Use screw [2] (one on each side) to attach rails to rear of rack through cage  
nut. Use screw [2] (two on each side) to attach rails to front of rack.  
R
F
T
FRONT  
OUTSIDE  
2
Use screws [1] (two on each side) to attach brackets to side of unit. Slide unit  
into rails and secure by using screws [2] (one on each side) to attach the unit.  
1
2
1
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
Ground Bonding Screw  
A ground bond-  
ing screw is pro-  
vided on the rear  
of the unit. This  
feature is pro-  
vided as an  
attachment point  
for conductors  
the rack may  
contain for the  
purpose of func-  
tional grounding  
or bonding of  
ungrounded  
metal parts.  
Ground cables  
are not included.  
Note: The Ground Bonding wire must be a minimum of 10 AWG to maintain  
proper grounding.  
Connecting Devices  
Make sure that  
the devices con-  
nected do not  
exceed the unit  
capabilities.  
This Dual Input  
Micro Smart-  
Switch features  
3 output recepta-  
cles per circuit  
breaker, for a  
total of 12  
receptacles.  
This model is  
rated at 10A per  
breaker.  
Each block of 3  
receptacles has a maximum output rating of 10A. If the total connected load  
exceeds 10A, the circuit breaker will trip and interrupt power to all loads attached  
to that block of receptacles.  
The maximum output of this Micro SmartSwitch is 24A. If the total load con-  
nected to all load segments exceed 24A, the circuit breaker at the wall could trip  
and interrupt power to all loads.  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
About the Circuit Breakers  
Input power can be verified by the illumination of the two LEDs on the front of  
the unit, marked ~A and ~B.  
Output power can be verified by the illumination of the circuit breaker, when in  
the On position  
If connected device is not powered, verify the respective circuit breaker is On  
and illuminated.  
If power is still not restored, see “Contacts” section later in this document.  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
Configurations  
The Micro SmartSwitch can be configured to fit several power distribution  
requirements.  
Configuration 1  
This application shows use of the Micro SmartSwitch in conjunction with single-  
line cord devices .  
Note: Each segment can accommodate a maximum current draw of 10A, so the  
individual load connected to it must not exceed 10A or the circuit breaker will  
trip.  
~A: AC Input A  
L6-30P  
Load  
Load  
Load  
Load  
~B: AC Input B  
1
2
3
4
~ A  
Dual Input  
~ B  
P
D
U
1,2,3,4: Load segments on the  
Micro SmartSwitch  
L6-30P  
Load: Any server, storage, or  
other equipment connected to  
the Micro SmartSwitch  
200-240 VAC  
Configuration 2  
This configuration shows the use of the Micro SmartSwitch with 3-line cord  
devices. The figure below shows how three Micro SmartSwitchs can be used to  
connect with up to four 3-line cord devices.  
Note: Each segment can accommodate a maximum current draw of 10A, so the  
individual load connected to it must not exceed 10A or the circuit breaker will  
trip.  
~A: AC Input A  
L6-30P  
Load  
Load  
Load  
Load  
1
2
3
4
~B: AC Input B  
~ A  
Dual Input  
~ B  
P
D
U
Load: Any server, storage, or  
other equipment connected to  
the Micro SmartSwitch  
L6-30P  
200-240 VAC  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
Configuration 3  
This configuration shows the use of a Micro SmartSwitch with 2-line cord  
devices. In this configuration, a server is connected to each of the four segments  
of the Micro SmartSwitch.  
Note: Each segment can  
L6-30P  
accommodate a maximum cur-  
rent draw of 10A, so the individ-  
ual load connected to it must not  
exceed 10A or the circuit  
breaker will trip.  
Load  
Load  
Load  
Load  
1
2
3
4
~ A  
Dual Input  
~ B  
P
D
U
L6-30P  
L6-30P  
~A: AC Input A  
200-240 VAC  
~B: AC Input B  
1,2,3,4: Load segments on the  
Micro SmartSwitch  
1
P
~ A  
Dual Input  
~ B  
Load  
Load  
2
D
U
Load: Any server, storage, or  
other equipment connected to  
the Micro SmartSwitch  
3
4
L6-30P  
200-240 VAC  
Configuration 4  
If your facility does not have a centralized Uninterruptible Power System, then  
the following configuration will provide maximum redundancy in a rack environ-  
ment. The diagram below shows how to use three Micro SmartSwitchs, each con-  
nected to a UPS and a server.  
Note: Each segment can accommodate a maximum current draw of 10A, so the  
individual load connected to it must not exceed 10A or the circuit breaker will  
trip.  
DUAL INPUT  
~A: AC Input A  
P
D
U
~ A  
Load  
Load  
UPS  
UPS  
UPS  
~ B  
~B: AC Input B  
P
D
U
~ A  
~ B  
Load: Any server, storage, or  
other equipment connected to  
the Micro SmartSwitch  
P
D
U
~ A  
~ B  
Load  
L6-30P  
200-240 VAC  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
Liebert Micro SmartSwitch Specifications  
Liebert Model Name  
Part Number  
Micro SmartSwitch  
MSS30A-240  
Unit Dimensions (H x W x D) in  
(mm)  
1.72 x 17.00 x 15.25 in  
(43.7mm x 432mm x 387mm)  
20.0 lbs.(9.7kg)  
Unit Weight: lbs.(kg)  
Shipping Weight: lbs.(kg)  
LED Indictors  
32.0 lbs.(14.55kg)  
Input A (Primary) / Input B (Secondary)  
200 – 240VAC  
Nominal Input Voltage Range  
On-Line Voltage Range  
Input Plug  
180 – 262VAC  
(2) Attached x L6-30 Plugs  
50/60Hz  
Input Frequency  
Input Surge Rating  
500J  
Output Connectors  
(12) x IEC-320-C13  
(4) x 10A  
Output Circuit Breaker Protection Rating  
Output Power (VA) Rating  
Maximum Output Current  
Transfer Time  
4320  
24A  
<18ms  
Environmental  
0°C to 50°C (32°F to 122°F)  
-30°C to 60°C (-22°F to 140°F)  
10 % to 80 %, non-condensing  
0 to 10,000 feet above sea level  
Safety and Agency  
UL, c-UL  
Operating Temperature  
Storage Temperature  
Relative Humidity  
Operating Altitude  
Safety Markings  
Safety Certifications  
EMC Markings  
Emissions  
UL1950  
FCC  
FCC Class A,  
Immunity  
ANSI C62.41 Cat B (formerly IEEE 587)  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
DUAL INPUT POWER DISTRIBUTION  
Micro Smart Switch  
USER MANUAL  
Technical Support  
The Company Behind the Products  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
With over a million installations around the globe,  
Liebert is the world leader in computer protection  
systems. Since its founding in 1965, Liebert has  
Columbus, OH 43229  
1-800-222-5877  
developed  
a
complete range of support and  
protection systems for sensitive electronics:  
Outside the United States  
Environmental systems—close-control air  
conditioning from 1 to 60 tons  
Power conditioning and UPS with power  
ranges from 300 VA to more than 1000 kVA  
Integrated systems that provide both  
+614-888-0246  
24 hours a day, 7 days a week  
1-800-222-5877  
3-Phase UPS  
1-800-543-2778  
environmental and power protection in  
single, flexible package  
a
Environmental Control  
Monitoring and control—from systems of any  
size or location, on-site or remote  
Service and support through more than 100  
service centers around the world and a 24/7  
Customer Response Center  
1-800-543-2778  
Italy  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD)  
+39 049 9719 111  
While every precaution has been taken to ensure  
the accuracy and completeness of this literature,  
Liebert Corporation assumes no responsibility and  
disclaims all liability for damages resulting from  
use of this information or for any errors or  
omissions.  
FAX: +39 049 5841 257  
Asia  
23F, Allied Kajima Bldg.  
138 Gloucester Road  
Wanchai  
Hong Kong  
+852 2 572 2201  
FAX: +852 2 831 0114  
© 2001 Liebert Corporation  
All rights reserved throughout the world.  
Specifications subject to change without notice.  
®
Liebert and the Liebert logo are registered  
trademarks of Liebert Corporation. All names  
referred to are trademarks or registered  
trademarks of their respective owners.  
Web Site  
SL-20350 (10/01)  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Lenovo Tablet S2109A F User Manual
LG Electronics Microwave Oven MD 2653GT User Manual
Linak Telephone CB14 User Manual
Lucent Technologies IP Phone 555 235 100 User Manual
Lund Industries Mouse MW520 User Manual
M 2GR45MF 2GR65MR 2GR85MF 3GR45MF 3GR65MF 3GR85MF 4GR45MF ML 136407 ML 136408 ML 136409 ML 136410 ML 136417 ML 136418 ML 136419 ML 136420 ML 136421 ML 136422 ML 136423 User Manual
Makita Power Hammer BDF451RFE User Manual
Manitowoc Ice Ice Maker K00055 User Manual
Maxim Log Splitter LSM75BVG LSM55H LSM80H User Manual
Maytag Trash Compactor MTUC7000AWS User Manual