Liebert Humidifier 50 60Hz User Manual

Precision Cooling  
For Business-Critical Continuity™  
Liebert Mini-Mate2™  
User Manual - 8 Tons, 50 & 60Hz  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8.0  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURES  
Figure 1  
TABLES  
iv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL NUMBER NOMENCLATURE  
Evaporators and Chilled-Water Units  
MMD96E-AHEL0 (example)  
Indoor Condensing Units  
MCD96ALA00 (example)  
MM  
D
Mini-Mate2  
MC  
D
Mini-Mate2 Indoor Condensing Unit  
0 = No Disconnect  
0 = No Disconnect  
D = Disconnect  
D= Disconnect  
96E- = 8-ton Evaporator, 60 Hz  
95E- = 8-ton Evaporator, 50 Hz  
8TCD = 8-ton Chilled-Water w/ 2-way valve  
8TCT = 8-ton Chilled-Water w/ 3-way valve  
A = 460V-3ph-60 Hz  
96A = 8-ton Air-Cooled Centrifugal, 60 Hz  
95A = 8-ton Air-Cooled Centrifugal, 50 Hz  
98W = 8-ton Water/Glycol-Cooled, 60 Hz  
97W = 8-ton Water/Glycol, 50 Hz  
L = Lee-temp Head Pressure Control (Air-Cooled)  
2 = 2-way Water/Glycol reg valve, 150 psi  
3 = 3-way, Water/Glycol reg valve, 150 psi  
D = 2-way, Water/Glycol reg valve, 350 psi  
T = 3-way, Water/Glycol reg valve, 350 psi  
A = 460V-3ph-60 Hz  
96E-  
96A  
B = 575V-3ph-60 Hz  
A
L
C = 208V-3ph-60 Hz  
D =230V-3ph-60 Hz  
M = 380/415V-3ph-50 Hz  
0 = No Humidifier  
H
E
L
H = Humidifier  
B = 575V-3ph-60 Hz  
A
0 = No Reheat  
Y = 208/230V-3ph-60 Hz  
E= Electric Reheat  
M = 380/415-3ph-50 Hz  
S = SCR Reheat  
0 = No Hot Gas Bypass  
H
0
L = Low Fan Speed Drive, 2 hp  
H = High Fan Speed Drive, 3 hp  
0 = None  
H = Hot Gas Bypass  
0 = Revision Level  
A = Filter Clog  
Prop Fan Condensing Units  
PFC096A-AL0 (example)  
B = Smoke Detector  
C = Firestat  
PF  
H
Prop Fan Condensing Unit  
H = Hot Gas Bypass  
0
D = Filter Clog & Smoke Detector  
E = Filter Clog & Firestat  
F = Smoke Detector & Firestat  
G = Filter Clog, Smoke Detector, & Firestat  
096A = 8-ton Air-Cooled, 60 Hz  
095A = 8-ton Air-Cooled, 50 Hz  
- = Standard Coil  
096A  
-
C = Coated Coil  
A = 460V-3ph-60 Hz  
B = 575V-3ph-60 Hz  
A
Y = 208/230V-3ph-60 Hz  
M = 380/415V-3ph-50 Hz  
L = 95°F Ambient, Lee-temp  
0 = Revision Level  
L
0
Table iii  
Heat rejection matchup – 60 Hz  
Condensing Unit  
Nominal  
Capacity  
Cooling  
Unit  
Indoor Air-Cooled  
Centrifugal Fan  
Outdoor Air-Cooled  
Propeller Fan  
Indoor  
Water/Glycol  
8 Tons  
MMD96E  
MMD8TC  
MCD96A  
PFC096A  
MCD98W  
8 Tons  
Chilled Water Unit  
Table iv  
Heat rejection matchup – 50 Hz  
Condensing Unit  
Nominal  
Capacity  
Cooling  
Unit  
Indoor Air-Cooled  
Centrifugal Fan  
Outdoor Air-Cooled  
Propeller Fan  
Indoor Remote  
Water/Glycol Cooled  
MMD95E  
MMD8TC  
MCD95A  
PFC095A  
MCD97W  
8 Tons  
Chilled Water Unit  
v
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
vi  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Product Features  
1.0 PRODUCT FEATURES  
1.1 Standard Product Features  
The Mini-Mate2 is a temperature/humidity control system designed to be installed above a ceiling  
grid system. The unit is available as a split system evaporator to be matched with an Indoor Centrif-  
ugal Fan Condensing Unit, Outdoor Prop Fan Condensing Unit, or Indoor Water/Glycol Condensing  
Unit. A self-contained Chilled Water Fan Coil is also available.  
1.1.1 Controls  
The Mini-Mate2 system includes a wall-mounted display panel with a liquid crystal display (LCD)  
screen and a 7 membrane keypad. The control is menu-driven for ease of use. Figure 24, Section 3,  
depicts the complete menu tree for the control. All control setpoints and alarm setpoints are program-  
mable.  
1.1.2 Evaporator System Components  
DX Evaporator Section  
The evaporator section includes the evaporator coil, thermostatic expansion valves, filter dryers, and  
blower. The evaporator coil is constructed of copper tubes and aluminum fins and is designed for the  
high sensible heat ratio required for electronic equipment. Room air circulation is accomplished by a  
double inlet, belt driven centrifugal blower that has been dynamically balanced. The blower has self-  
aligning bearings. Both the blower and motor have permanently lubricated ball bearings.  
Chilled-Water Model  
The Chilled-Water model is self-contained and is designed for use with an existing chilled-water loop.  
It contains a chilled-water coil and a proportional modulating valve to control the flow of chilled  
water.  
1.1.3 Condensing Unit Components  
The condensing unit is connected to the evaporator unit by four refrigerant lines and low voltage con-  
trol wires. The condensing unit requires a power source and a power disconnect switch. A single point  
power kit is available for close coupled (attached) units.  
Air-Cooled Condensing Unit (Indoor Centrifugal)  
The Air-Cooled Condensing units (MC models) include: 3-ton and 5-ton scroll compressors with motor,  
belt-driven centrifugal blower, crankcase heaters, high pressure switches, condenser coils, and Lee-  
Temp head pressure control with receivers.  
Air-Cooled Condensing Unit (Outdoor Prop Fan)  
Outdoor Air-Cooled Condensing Units (PFC models) include: 3-ton and 5-ton scroll compressors with  
crankcase heaters, high-pressure switch, condenser coils, direct-driven propeller fan, and Lee-Temp  
head pressure control with receivers.  
Water/Glycol Condensing Unit (Indoor)  
The Water/Glycol-Cooled Condensing units include: 3-ton and 5-ton scroll compressors with crank-  
case heaters, high pressure switches, coaxial condensers, and regulating valves. Drycooler and pumps  
are selected separately for glycol systems.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Product Features  
1.2  
Optional Equipment  
1.2.1 Canister Humidifier  
The optional, factory-installed steam generating humidifier adds pure water vapor to the room air to  
control humidity. Room humidity setpoints are established by the user. The humidifier components  
include: a steam canister (replaceable), control board, inlet strainer, fill and drain valves.  
1.2.2 Electric Reheat  
The 304/304 stainless steel electric reheat is energized when required to heat room air or to control  
room temperature during dehumidification. A safety switch prevents the reheat from exceeding tem-  
perature limits.  
1.2.3 SCR Electric Reheat  
The 304/304 stainless steel reheat is pulsed rapidly to provide precise temperature control, while cool-  
ing is locked on. A safety switch prevents the reheat from exceeding temperature limits.  
1.2.4 Hot Gas Bypass (Condensing Units)  
This optional system bypasses compressor discharge around the condenser directly to suction to pro-  
vide capacity control and reduce compressor cycling. System includes liquid injection valve to main-  
tain proper suction superheat. Hot gas bypass is provided on both circuits.  
1.2.5 Free-Cooling Coil (GLYCOOL)  
When ambient temperatures are low enough, cold fluid is piped to a secondary coil or a separate  
source of chilled-water may be piped to this coil.  
1.2.6 Smoke Detector  
If smoke is detected in the return air, the unit display sounds an audible signal and the unit shuts  
down.  
1.2.7 Firestat  
When the return air temperature limit of approximately 125°F (51.7°C) is exceeded, the unit shuts  
down.  
1.2.8 Filter Clog  
If high pressure differential is detected across the return air filter, an adjustable pressure differential  
switch sounds an audible signal.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
                 
Product Features  
1.3  
Ancillary (Ship Loose Accessories)  
1.3.1 Single Point Power Kit  
A Single Point Power Kit allows the connection of a system (Evaporator and indoor condensing unit)  
to a single power source when the units are close coupled. The kit includes a junction box with power  
distribution, sub-fusing, and evaporator and condenser wiring.  
1.3.2 Refrigerant Line Sweat Adapter Kits  
This kit includes the compatible fittings required (four suction and four liquid line connections) when  
using field supplied interconnecting refrigerant piping.  
1.3.3 Return Air Filter Box with Duct Collar Kit  
A return air filter box with duct flange, 4" (102 mm) filter, and a supply air duct flange are provided  
for ducting the evaporator air.  
1.3.4 Condensate Pump Kit  
A condensate pump is required when the evaporator is installed below the level of the gravity-fed  
drain line. Components include: the pump; check valve; sump; level sensor; float switch; and controls.  
Refer to detailed instructions and drawings supplied with the pump.  
1.3.5 Remote Monitoring and Control  
Liebert can provide a variety of remote monitoring and control devices to enhance your Mini-Mate2  
system. These include water detection, remote monitoring of a single unit, and remote control/moni-  
toring of multiple units.  
1.3.6 Remote Sensors  
Remote temperature/humidity sensors can be mounted in the controlled space or in duct work and  
includes 30 feet of control cable.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
Site Preparation and Installation  
2.0 SITE PREPARATION AND INSTALLATION  
NOTE  
Before installing unit, determine whether any building alterations are required to run piping,  
wiring, and duct work. Carefully follow all unit dimensional drawings and refer to the  
submittal engineering dimensional drawings of individual units for proper clearances.  
2.1  
Installation Considerations  
The evaporator unit is usually mounted above the suspended ceiling using field supplied threaded  
rods. Refer to Figure 1 for possible configurations. The condensing unit may be:  
• Indoor Air-Cooled Centrifugal Fan Condensing Unit mounted remotely or close coupled to the  
evaporator in the ceiling space.  
• Outdoor Air-Cooled Propeller Fan Condensing Unit.  
• Indoor Water/Glycol-Cooled Condensing Unit, mounted remotely or close coupled to the evapora-  
tor.  
Table 1  
Application limits, evaporator and chilled-water units*  
Range of Return Air Conditions to Unit  
Input Voltage  
Min  
Max  
Dry Bulb Temp.  
Relative Humidity  
65°F to 85°F  
(18°C to 29°C)  
20% to 80%  
-5%  
+10%  
*Unit will operate at these conditions but will not control to these extremes.  
Table 2  
Input  
Application limits, indoor and outdoor air-cooled condensing units  
Condensing Units  
Entering Dry Bulb  
Air Temperature  
Voltage  
Min Max  
Min  
Max  
120°F (49°C)  
Outdoor Prop Fan Condensing Unit  
-30°F (-34°C)  
-5% +10%  
Indoor Air-Cooled Centrifugal Condensing Unit -20°F (-29°C) 115°F (46°C)  
Table 3  
Application limits, indoor water/glycol-cooled condensing units  
Entering Fluid Temperature  
Input Voltage  
Min  
Max  
Min  
Max  
-5%  
+10%  
65°F (18.3°C) *  
115°F (46°C)  
*Operation below 65°F (18°C) may result in reduced valve life and fluid noise.  
2.1.1 Room Preparation  
The room should be well-insulated and must have a sealed vapor barrier. The vapor barrier in the  
ceiling and walls can be a polyethylene film. Paint on concrete walls and floors should be vapor resis-  
tant.  
NOTE  
The single most important requirement for maintaining environmental control in the  
conditioned room is the vapor barrier.  
Outside or fresh air should be kept to a minimum when tight temperature and humidity control is  
required. Outside air adds to the cooling, heating, dehumidifying and humidifying loads of the site.  
Doors should be properly sealed to minimize leaks and should not contain ventilation grilles.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Site Preparation and Installation  
2.1.2 Location Considerations  
CAUTION  
!
Units contain water. Water leaks can cause damage to sensitive equipment below. DO NOT  
MOUNT UNITS OVER SENSITIVE EQUIPMENT. A field-supplied pan with drain must be  
installed beneath cooling units and water/glycol-cooled condensing unit.  
NOTE  
Do not mount units in areas where normal unit operating sound may disturb the working  
environment.  
Locate the evaporator unit over an unobstructed floor space if possible. This will allow easy access for  
routine maintenance or service. Do not attach additional devices to the exterior of the cabinet, as they  
could interfere with maintenance or service.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation and Installation  
Figure 1 System configurations—air cooled systems  
Evaporator  
Prop Fan  
Condensing Unit  
Evaporator  
Centrifugal Fan  
Condensing Unit  
Figure 2 System Configurations—water/glycol systems  
Cooling  
Tower  
WATER-COOLED SYSTEMS  
Evaporator  
Water/Glycol  
Condensing Unit  
GLYCOL-COOLED SYSTEMS  
Drycooler  
Evaporator  
Water/Glycol  
Condensing Unit  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Site Preparation and Installation  
Figure 3 System Configurations—chilled water systems  
COUPLED COMPONENTS  
(AIR-COOLED SYSTEM  
Evaporator  
CHILLED-WATER SYSTEMS  
Evaporator  
Condensing  
Unit  
Condensate Pump  
Condensate Pump  
2.2  
System Weights  
Table 4  
Unit weights  
Cooling Units*  
lbs  
665  
665  
lbs  
kg  
MMD96E  
MMD95E  
302  
302  
kg  
Condensing Units  
MCD96A  
530  
530  
470  
470  
241  
241  
213  
213  
MCD95A  
MCD98W  
MCD97W  
*Add 40 lbs. (20 kg.) to units with free cooling or hot water reheat coils.  
2.3  
Equipment Inspection upon receipt  
When the unit arrives, do not uncrate equipment until it is close to its final location. All required  
assemblies are banded and shipped in corrugated containers. If you discover any damage when you  
uncrate the unit, report it to the shipper immediately. If you later find any concealed damage, report  
it to the shipper and to your Liebert supplier.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Site Preparation and Installation  
2.4  
Installing the Evaporator or Chilled-Water Units  
WARNING  
!
Be sure the supporting roof structure is capable of supporting the weight of the unit(s) and the  
accessories during installation and service. (See 2.2 - System Weights.)  
Be sure to securely anchor the top ends of the suspension rods. Make sure all nuts are tight.  
The evaporator unit and indoor condensing unit are usually mounted above the ceiling and must be  
securely mounted to the roof structure. The ceiling and ceiling supports of existing buildings may  
require reinforcements. Be sure to follow all applicable codes. Use field-supplied 1/2"-13 tpi threaded  
suspension rods and 1/2"-13 tpi hardware kit.  
Recommended clearance between ceiling grids and building structural members is unit height plus 3  
inches.  
Install the four field-supplied rods by suspending them from suitable building structural members.  
Locate the rods so that they will align with the four mounting holes in the flanges that are part of the  
unit base.  
Using a suitable lifting device, raise the unit up and pass the threaded rods through the four mount-  
ing holes in the flanges that are part of the unit base.  
Attach the threaded rods to the unit flanges using the supplied, springs, and washers. (See Figure 4).  
The coil springs provide vibration isolation.  
1. Use the plain nuts to hold unit in place. Adjust these nuts so that the weight of the unit is  
supported by the four rods, does not rest on the ceiling grid, and is level. Ensure none of the  
springs are compressed to solid height. The coil side of the unit is heavier, so these springs will be  
compressed more than the other side.  
NOTE  
The units must be level in order to drain condensate properly.  
2. Use the Nylock nuts to “jam” the plain nuts.  
Figure 4 Threaded rod and hardware kit installation  
1/2" threaded rod  
(supplied by field)  
hanging bracket  
1" O.D. spring  
1/2" flat washer  
base pan (ref)  
1/2" hex nut  
1/2" Nylock  
locking nut  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Site Preparation and Installation  
2.4.1 Close Coupled Installations  
If the evaporator and condensing units are to be mounted side-to-side (close coupled), hang each unit  
before connecting them together (See Figure 5). If Single Point Power Kit is used, install the box into the  
evaporator prior to suspending the units. Route power wire flex conduit into condensing unit as units are  
suspended. Refer to instructions supplied with kit for details. Align bolt holes in the condensing unit and  
in the evaporator. Insert rubber spacers and secure four (4) sets of hardware provided. Align the refriger-  
ant connections and tighten them as described in 2.4.3 - Piping Connections and Coolant Require-  
ments. Remove “P” clamps from piping to aid fitting alignment.  
Figure 5 Close coupled installation  
Condensing  
Unit  
Evaporator  
Isolator rubber  
5/16" lock washer  
5/16" capscrew  
5/16" flat washer  
Cage  
nut  
NOTE: Disconnect P-clamps on lines in the evaporator  
for easy close coupling.  
P-clamps are for shipping purposes only.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Site Preparation and Installation  
2.4.2 Evaporator Air Distribution  
Filter Box  
The optional filter box mounts directly to the return air opening of the evaporator. The filter box is  
supplied with two (2) 20% (Liebert part no. A-0320) or 30% (Liebert part no. A-0400) 25" x 20" x 4" fil-  
ters.  
NOTE  
Do not operate the unit without filters installed in return air system.  
Connections for Ducted Systems  
Use flexible duct work or non-flammable cloth collars to attach duct work to the unit and to help con-  
trol the transmission of vibrations to building structures. Insulation of duct work is vital to prevent  
condensation during the cooling cycle. The use of a vapor barrier is required to prevent absorption of  
moisture from the surrounding air into the insulation.  
If the return air duct is short, or if noise is likely to be a problem, sound-absorbing insulation should  
be used on the duct. Duct work should be fabricated and installed in accordance with local and  
national codes.  
Table 5  
Evaporator external static pressure (60) at 3750 CFM (6371 CMH)  
2 hp Motor (std)  
3 hp Motor (opt)  
Turns  
Open  
External  
External  
RPM  
n/a  
Static, in.  
n/a  
RPM  
1146  
1125  
1104  
1083  
1063  
1042  
1021  
1000  
979  
Static, in.  
1.9  
0
0.5  
1
n/a  
n/a  
1.8  
n/a  
n/a  
1.7  
1.5  
2
946  
922  
972  
899  
851  
828  
804  
780  
757  
733  
0.9  
1.6  
0.8  
1.5  
2.5  
3
0.7  
1.4  
0.6  
1.3  
3.5  
4
0.5  
1.2  
0.4  
1.1  
4.5  
5
0.3  
958  
1.0  
0.2  
938  
0.9  
5.5  
6
0.1  
917  
0.8  
0
896  
0.7  
If free-cooling or hot water coil is ordered, reduce available external static  
pressure by 0.3" (8 mm). Contact Liebert Representative for other Air Volumes.  
Factory setting is 0.5" (13 mm) with 2 hp motor. Field adjust to suit application.  
NOTE  
Maximum return air static pressure should not exceed 0.3" (8 mm) to provide proper drainage  
of the unit.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Site Preparation and Installation  
2.4.3 Piping Connections and Coolant Requirements  
Drain Line  
CAUTION  
!
The drain line must not be trapped outside the unit, or water may back-up in drain pan.  
Drain is internally trapped.  
This line may contain boiling water. Use copper or other suitable material for the drain line.  
Sagging condensate drain lines may inadvertently create an external trap.  
A 3/4 in. (19.1 mm) female pipe thread (FPT) connection is provided for the evaporator coil condensate  
drain. This line also drains the humidifier, if applicable. The drain line must be located so it will not  
be exposed to freezing temperatures. The drain should be the full size of the drain connection.  
The evaporator drain pan includes a float switch to prevent unit operation if drain becomes blocked.  
Figure 6 Drain installation  
Unit  
Unit  
Continuous slope  
away from unit  
Do not externally  
trap the unit  
Correct  
Incorrect  
Unit  
These are external traps also, although  
unintentional. Lines must be rigid  
enough to not bow between supports.  
Humidifier drain water can approach  
100° Celsius.  
Incorrect  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Site Preparation and Installation  
Condensate Pump  
The optional condensate pump kit is required when the evaporator is installed below the level of the  
gravity-fed drain line. Refer to the installation instructions provided with the condensate pump kit.  
Figure 7 Condensate pump installation  
3/8" Compression Fitting  
Drain Connection  
Power Supply from  
Electric Service Power  
Drain Line  
Block in Fan/Coil Module.  
(field supplied)  
Evaporator or  
Chilled Water  
Unit  
Condensate Pump  
AIR INLET  
FRONT OF UNIT  
10 9/16 "  
(268.3mm)  
Condensate Drain  
21 1/2 "  
(546mm)  
3/4" (13mm) FPT  
Customer Connection  
6 5/8 "  
(168.3mm)  
Condensate  
Pump  
Support Bracket  
3/4" (13mm) Hose Barb  
Flexible Rubber Tubing  
Supplied on Pump Tank  
Notes:  
1. 3/4" (13mm) Flexible Rubber Tubing Assembly (Supplied  
with Pump Kit) must be installed on pump end.  
2. The High Water Safety Float included with pump must be  
interlocked with unit control. Wire to terminals 60 & 61 on  
Evaporator terminal strip to shut down unit.  
DPN000239_Rev0  
Humidifier Water Supply Line  
Units supplied with the optional humidifier package have a 1/4 in. (6.4 mm) FPT connection for water  
inlet. Supply pressure range is 10 psig to 150 psig. Required flow rate is 1 gpm. A shut-off valve  
should be installed in this line to isolate the humidifier for maintenance.  
NOTE  
DO NOT route humidifier supply line in front of filter box access panel.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation and Installation  
Chilled-Water Piping—Chilled-water Systems Only  
Refer to Figure 8 for recommended field installed hardware such as shut-off valves and hose bibs.  
Chilled-water supply and return lines must be insulated to prevent condensation.  
The minimum recommended water temperature is 42°F. Connection sizes are 1-1/4" FPT.  
Figure 8 General arrangement diagram - chilled-water systems  
Bleed Valve  
Chilled  
Water  
Chilled Water Coil  
Supply  
Chilled  
Water  
Return  
Chilled Water  
Control Valve  
** Shutoff Valves  
Female Adapters  
Supply  
Return  
** Hose Bibs  
3 - Way Chilled Water  
Control Valve  
(Optional)  
* Field piping refers to the use of hard  
piping using sweat adapter kit  
or precharged line set.  
FIELD PIPING  
FACTORY PIPING  
** Components are not supplied by  
Liebert but are recommended for  
proper circuit operation and  
maintenance.  
DPN000236_Rev0  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation and Installation  
Refrigerant (R-22) Piping  
All split systems require two sets of refrigerant lines (two insulated copper suction lines and two cop-  
per liquid lines) between the evaporator and the condensing unit.  
Two possible methods exist for installing the copper suction and liquid lines.  
• Close coupling the units together using the quick connects.  
• Using an optional Sweat Adapter Kit and hard piping between the two units.  
All refrigeration piping should be installed with high temperature brazed joints. Prevailing good refrig-  
eration practices should be employed for piping supports, leak testing, evacuation, dehydration, and  
charging of the refrigeration circuits. The refrigeration piping should be isolated from the building by  
the use of vibration isolating supports. To prevent tube damage when sealing openings in walls and to  
reduce vibration transmission, use a soft flexible material to pack around the tubes.  
When installing remote condensing units above the evaporator, the suction gas line should be trapped  
at the evaporator. This trap will retain refrigerant oil in the off cycle. When the unit starts, oil in the  
trap is carried up the vertical riser and returns to the compressor.  
Table 6  
Recommended refrigerant line sizes  
Equivalent  
Suction  
Line  
Feet  
Circuit  
3-ton  
3-ton  
3-ton  
5-ton  
5-ton  
5-ton  
Liquid Line  
3/8" O.D.  
1/2" O.D.  
5/8" O.D.  
1/2" O.D.  
5/8" O.D.  
5/8" O.D.  
50 feet  
100 feet  
150 feet  
50 feet  
100 feet  
150 feet  
7/8" O.D.  
7/8" O.D  
1-1/8" O.D  
1-1/8" O.D  
1-1/8" O.D  
1-3/8" O.D  
Consult your Liebert representative for longer line lengths.  
NOTE  
If field supplied refrigerant piping is installed, refrigerant (R-22) must be  
added to the system.  
Figure 9 Refrigerant piping diagram  
Pitch down 1/2" per 10 feet  
NOTE: When installing remote condensing  
Evaporator  
units below the evaporator, the suction gas  
line should be trapped with an inverted trap  
to the height of the evaporator. This  
prevents refrigerant migration to the  
compressors during off cycles. Maximum  
recommended vertical drop to condensing  
unit is 20 feet (6.1 m).  
Suction Line Piping  
Condensing Unit Below Evaporator  
Condensing Unit  
Condensing Unit  
Evaporator  
Suction Line Piping  
Condensing Unit Above Evaporator  
Traps recommended every 25 feet (7.6 m) of vertical rise.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Site Preparation and Installation  
Refrigerant Charge Requirements: Total refrigerant charge (R-22) will be required only if units  
are evacuated during installation or maintenance. For safe and effective operation, refer to 2.4.3 -  
Total refrigerant = Units and Lines  
Table 7  
8-ton unit refrigerant charge  
Evaporator  
Charge (ounces)  
Model No.  
MMD96E  
3-ton circuit  
5-ton circuit  
7
7
7
MMD95E  
7
Condensing Units  
Model No  
MCD96A  
MCD95A  
MCD98W  
MCD97W  
Charge (ounces)  
361  
361  
54  
581  
581  
94  
54  
94  
Table 8  
Line charges (field piping)*  
O.D.  
1/2"  
Liquid Line  
7.3 (1.1)  
Suction Line  
0.2 (0.1)  
5/8"  
11.7 (1.7)  
24.4 (3.6)  
41.6 (6.2)  
0.3 (0.1)  
7/8"  
0.7 (0.1)  
1-1/8"  
1.2 (0.2)  
*weight of R-22 in type “L” copper tube: lb per 100 ft (kg per 10 m)  
Quick Connect Fittings  
NOTE  
When hard piping is used, complete all piping and evacuate lines before  
connecting quick connects.  
Be especially careful when connecting the quick connect fittings. Read through the following steps  
before making the connections.  
1. Remove protector caps and plugs.  
2. Carefully wipe coupling seats and threaded surfaces with a clean cloth.  
3. Lubricate the male diaphragm and synthetic rubber seal with refrigerant oil.  
4. Thread the coupling halves together by hand to insure that the threads mate properly.  
5. Tighten the coupling body hex nut and union nut with the proper size wrench until the coupling  
bodies “bottom out” or until a definite resistance is felt.  
6. Using a marker or pen, make a line lengthwise from the coupling union nut to the bulkhead.  
7. Tighten the nuts an additional quarter-turn; the misalignment of the lines shows how much the  
coupling has been tightened. This final quarter-turn is necessary to insure that the joint will not  
leak. Refer to Table 9 for torque requirements.  
Table 9  
Refrigerant quick connect sizes and torque  
Size O.D. Cu  
Coupling Size  
Torque (lb-ft)  
10-12  
3/8"  
1/2"  
#6  
#10  
#11  
#12  
35-45  
7/8"  
35-45  
1-1/8"  
50-65  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Site Preparation and Installation  
Figure 10 Evaporator or chilled-water unit dimensional data  
Customer Supplied  
threaded rods for module  
support from ceiling (1/2" minimum  
diameter recommended) (typ. 4).  
54 1/8 "  
(1375mm)  
CABINET  
1 3/16 "  
(30.2mm)  
9/16" (14mm) dia. holes for  
DIMENSION  
12 1/8 "  
(308mm)  
threaded rods (typ. 2 each end)  
15 5/8 "  
(397mm)  
2"  
Air Outlet  
Air Inlet  
16 13/16 "  
(427mm)  
(50.8mm)  
26 1/2 "  
(673mm)  
19 1/2 "  
(495mm)  
FRONT  
OF  
UNIT  
1 "  
(25.4mm)  
50 "  
(1270mm)  
70 "  
(1778mm)  
Hanger Bracket  
72 "  
50 "  
(1270mm)  
(1828.8mm)  
Shaded area indicates a  
recommended clearance  
for access  
of 30" (762mm)  
and  
filter removal.  
1 "  
(25.4mm)  
49 "  
(1244.6mm)  
1 "  
(25.4mm)  
1 "  
(25.4mm)  
19 1/2 "  
(495.3mm)  
Shaded area indicates a  
recommended clearance  
for access  
17 1/2 "  
(444.5mm)  
of 30" (762mm)  
21 1/2 " and  
filter removal.  
Optional 1" (25.4mm)  
(546.1mm)  
Discharge Duct Connection  
ships with Filter Box  
47 "  
Duct Flange  
(1193.8mm)  
16 13/16 "  
(427mm)  
8 "  
1 "  
(25.4mm)  
(203mm)  
15 5/8 "  
(397mm)  
DPN000240_Rev0  
(OPTIONAL) FILTER BOX  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation and Installation  
2.4.4 Electrical Connections, Evaporator or Chilled-Water Unit  
WARNING  
!
Unit contains hazardous electrical voltage. Disconnect power supply before working  
within. Line side of factory disconnect remains energized when disconnect is off.  
WARNING  
!
UNIT CONTAINS HAZARDOUS ELECTRICAL VOLTAGE. More than one disconnect  
may be required to remove power. Evaporator and condensing units may have separate  
disconnects. Open all disconnects before working within.  
Each unit is shipped from the factory with internal wiring completed. Refer to electrical sche-  
matic, Figure 11, Figure 25, and Figure 26 when making connections. Electrical connections  
to be made at the installation site are:  
• Power supply to each ceiling unit and control wiring between the evaporator unit and the con-  
densing unit, if applicable.  
• Control wiring between the control panel (wallbox) and the evaporator or chilled-water unit  
control board.  
Power Connections  
All power and control wiring and ground connections must be in accordance with the National  
Electrical Code (NEC) and local codes. Refer to Unit serial tag data for electrical requirements.  
CAUTION  
!
Use copper wiring only. Make sure that all connections are tight.  
Voltage supplied must agree with the voltage specified on the unit serial tag. A field supplied dis-  
connect switch may be required. Consult local code.  
Route the electrical service conduit through the hole provided in the cabinet and terminate it at  
the electric box. Make connections at the factory terminal block or disconnect switch, L1, L2, L3.  
Connect earth ground to lug provided. See transformer label for primary tap connections.  
Installer will need to change transformer primary taps if applied unit voltage is other than pre-  
wired tap voltage.  
An optional single point power kit is available for units that are close coupled (refer to Figure 11  
and 2.4.3 - Piping Connections and Coolant Requirements). This kit should be mounted  
inside the evaporator unit before installing the unit in the ceiling. Specific installation instruc-  
tions are included with the single point power kit.  
Control Connections (10-wire on air-cooled, 8-wire on water/glycol cooled)  
A field-supplied control connection (24 VAC) is required between the evaporator and the condens-  
ing unit. Control wiring must be installed in accordance with the National Electrical Code (NEC)  
Class 2 circuit. Glycol-cooled units also require a two-wire control connection to the drycooler and  
pump.  
Control wiring between the evaporator and the condensing unit must not allow a voltage drop in  
the line of more than 1 volt (16 gauge minimum for 75 feet). Do not connect additional electri-  
cal devices to the control circuit. The internal control transformer is only sized for factory-  
supplied components.  
Additional control wiring will be required if your system includes other optional monitoring and  
control devices.  
Four (4) wire (thermostat type) must be connected between the evaporator control board and the  
wall box. See Figure 25 and Figure 26 and see Figure 11 for electrical connections.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation and Installation  
Figure 11 Evaporator unit electrical connections  
Customer Remote Alarm  
Connection TB50,51,56,24.  
Field supplied 24V Class 2  
wiring.  
Earth Ground Connection  
Connection terminal for field  
supplied earth grounding wire.  
Common Alarm Connection.  
Use field supplied 24V  
Class 2 wire. TB75-76.  
Optional factory installed  
disconnect switch.  
High Volt Power Connections  
Electric service connection terminals.  
Drycooler/Circulating Pump Control  
Circuit TB70-71. Optional  
W/Glycool/Econ-O-Cycle models.  
Use field supplied 24V class 2 wire.  
Optional Condensate Pump  
Auxiliary Float Switch Shut  
Down Connection  
TB60-61.  
1
2
3
4
5
6
7
8
9
60  
61  
70  
71  
75  
76  
77  
78  
84  
85  
38  
24  
50  
51  
56  
11  
12  
Microprocessor  
Board  
FRONT OF UNIT  
Remote Control Panel Connection to  
TB3-1,2,3,4 connected with field supplied  
Thermostat wire (22ga, shielded/jacketed:  
available from Liebert or others).  
10  
37  
Heat Rejection Connection. Field supplied  
24V NEC Class 2 wiring TB1-10. See note 2.  
Remote Unit Shutdown. Use field supplied  
24V Class 2 wire. Replace existing jumper  
between TB37 & TB38 with NC switch  
having a minimum 75 VA rating.  
Optional Remote Sensor  
Connection P16-1,2,3,4.  
Remote Humidifier Contact  
Field Supplied 24V class 2  
wiring to terminals 11 & 12,  
located in field wire  
Site Monitoring Connection.  
Terminals TB78 (+) TB77 (-) are for  
connection of a 2 wire, twisted pair,  
communication cable to optional  
compartment.  
Field supplied unit disconnect switch  
when factory unit disconnect switch  
is not supplied.  
Optional Main Fan Auxilary  
Side Switch TB84-85.  
Field supplied 24V Class 2  
wire.  
sitescan.  
Electric service  
not by Liebert  
Entrance for customer high  
volt connections.  
NOTES:  
Electrical entrance for  
optional condensate  
pump on left side of unit.  
1. Refer to specification sheet for  
full load amp. and wire size amp.  
ratings.  
2. Control voltage wiring must be a  
minimum of 16 GA (1.6mm) for up  
to 75’ (23m) or not to exceed 1 volt  
drop in control line.  
Optional Single  
Point Power Kit  
Field supplied, field wired thermostat wire to remote wall box.  
Entrance for customer low voltage connections  
Field supplied 24V (NEC Class2 wiring) to condensing unit. (if applicable)  
Entrance for customer low  
voltage connections.  
DPN000244_Rev0  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation and Installation  
2.5  
Indoor Air-Cooled Centrifugal Fan Condensing Unit Installation  
2.5.1 Location Considerations  
The centrifugal fan air-cooled condensing unit may be located above the dropped ceiling or any remote  
indoor area. If noise is of concern, the condensing unit should be located away from personnel. Normal  
operating sound may be objectionable if the condensing unit is placed near quiet work areas.  
To mount the unit in the ceiling, refer to 2.4 - Installing the Evaporator or Chilled-Water Units  
for hanging guidelines and to Figure 13 for dimensional data.  
2.5.2 Ducting  
Fan operation is designed for 5000 CFM (8495 CMH) at 0.5" external static pressure.  
General Considerations  
Use flexible duct work or nonflammable cloth collars to attach duct work to the unit and to control  
vibration transmission to the building. Attach the duct work to the unit using the flanges provided.  
Locate the unit and duct work so that the discharge air does not short circuit to the return air inlet.  
Duct work that runs through a conditioned space or is exposed to areas where condensation may  
occur must be insulated. Duct work should be suspended using flexible hangers. Duct work should not  
be fastened directly to the building structure.  
For multiple unit installations, space the units so that the hot condensing unit exhaust air is not  
directed toward the air inlet of an adjacent unit.  
Considerations for Specific Applications  
In applications where the ceiling plenum is used as the heat rejection domain, the discharge  
air must be directed away from the condensing unit air inlet and a screen must be added to the end of  
the discharge duct to protect service personnel. Locate the air discharge a minimum of 4 feet from an  
adjacent wall. Failure to do so may result in reduced air flow and poor system performance.  
If the condensing unit draws air from the outside of the building, rain hoods must be  
installed. Hood intake dimensions should be the same as the condensing unit duct dimensions. In  
addition, install a triple layer bird screen over rain hood openings to eliminate the possibility of  
insects, birds, water, or debris entering the unit. Avoid directing the hot exhaust air toward adjacent  
doors or windows.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Site Preparation and Installation  
2.5.3 Piping Connections  
Details for refrigerant (R-22) loop piping are in 2.4.3 - Piping Connections and Coolant Require-  
ments.  
Figure 12 Piping connections - indoor air-cooled centrifugal fan condensing unit  
Condenser Coil  
High Pressure  
Switch  
Scroll  
Compressor  
Liquid Injection  
Valve Bulb  
Hot Gas Bypass  
Solenoid Valve  
3/8" (9.5mm) FLR  
Suction Line Male Quick  
Connect Coupling  
Pressure Relief Valve  
3 - Way Head  
Suction Line Female Quick  
Pressure  
Check  
Valve  
*
Connect Coupling  
Sight Glass  
Control Valve  
Hot Gas Bypass  
Sensing Bulb  
External Equalizer  
Control Valve  
Liquid Injection  
Valve  
Lee - Temp  
Receiver  
Liquid Line  
Service Access  
Ports  
Solenoid Valve  
Receiver Heater  
Pressure Limiting  
Switch  
Pressure Balancing  
Valve  
*
Liquid Line Male Quick  
Connect Coupling  
Liquid Line Female Quick  
Connect Coupling  
Filter  
Drier  
Expansion Valve  
(Two circuits required, single circuit shown for clarity)  
Evaporator Coil  
DPN000236_Rev0  
2.5.4 Electrical Connections - Condensing Unit  
general wiring requirements and cautions. Refer to electrical schematic when making connections.  
Refer to unit serial tag for full load amp and wire size amp ratings.  
Power Connections  
The condensing unit requires its own power source and earth ground, with a disconnect switch to iso-  
late the unit for maintenance.  
NOTE  
Refer to serial tag for full load amp and wire size amp ratings  
Control Connections  
Field-supplied control wires must be connected between the evaporator and the condensing unit (See  
Figure 14 and the electrical schematic on the units for more details.) Seven (7) wires are required  
between the evaporator and condensing unit. Eighth and ninth wires are required on systems with  
hot gas bypass.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Site Preparation and Installation  
Figure 13 Indoor air-cooled centrifugal condensing unit dimensions and pipe connections  
40 5/32 "  
(1020mm)  
66 9/32 "  
(1683.5mm)  
CABINET  
CABINET  
DIMENSION  
DIMENSION  
1 13/16 "  
(40mm)  
Customer supplied  
threaded rods for module  
support from ceiling (1/2"  
minimum diameter  
19 1/32 "  
(483mm)  
59 13/16 "  
(1519mm)  
8 13/16 "  
(224mm)  
recommended) (typ. 4).  
1 3/32 "  
(26mm)  
13/16"  
(21mm)  
16 5/16 "  
(414mm)  
23 7/8 "  
(606mm)  
26 3/8 "  
(670mm)  
Shaded area indicates a  
recommended clearance of  
component  
30" (762mm)for  
64 1/4 "  
42 17/32 "  
Hanger  
Bracket  
access and removal.  
(1632mm)  
THREADED ROD  
CENTERS  
(1080.3mm)  
THREADED ROD  
CENTERS  
NOTE: Unit is spaced evenly in  
reference to threaded  
rod centers.  
9/16" (14mm) dia. holes for  
threaded rods (typ. 2 each end)  
Air Inlet  
7/8" (22mm) & 1 1/8" (29mm)  
dia. knockouts electrical entrance  
for high voltage connection  
Air Outlet  
Single Point Power Kit  
connection from Evaporator.  
System 1 (3Ton) Suction Line Connection,  
Aeroquip #11 Male.  
System 2 (5Ton) Suction Line Connection,  
Aeroquip #12 Male.  
System 1 (3Ton) Liquid Line Connection,  
Aeroquip #6 Male.  
System 2 (5Ton) Liquid Line Connection,  
7/8" (22.2mm) dia. electrical entrance  
for low voltage connection.  
Aeroquip #10 Male.  
7/8" (22.2mm) dia. knockout  
electrical entrance for alternate  
control panel low voltage routing.  
DPN000248_Rev1  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation and Installation  
Figure 14 Indoor air-cooled centrifugal condenser electrical connections  
Field Supplied Unit Disconnect  
Switch when Factory Unit  
Disconnect Switch is not  
Supplied.  
Electric Service not  
by Liebert.  
Line VoltageElectric Power Supply  
Conduit.  
Removable  
Access Panels  
Connection Terminal for  
Field Supplied Earth  
Grounding Wire.  
Optional Factory Installed  
Disconnect Switch.  
Heat rejection connectio.nField  
supplied 24V NEC class 2 wiring. See note 2.  
Wire connections from evaporator module:  
1. 24V GND System 1  
LowVoltageElectric Power  
2. 24V Supply System 1  
Supply Conduit Entrance.  
3. High Pressure Alarm System 1  
4. Hot Gas Bypass Connection System 1  
(only on units with hot gas bypass.  
If no hot gas bypass, connection is  
provided in the evaporator module.  
Connect wire 4 and wire 2 to the  
24V supply).  
Openings for Field Supplied  
24V NEC Class 2 Wiring  
Between Condensing Unit and  
Fan/Coil Unit.  
5. 24V GND System 2  
6. 24V Supply System 2  
7. High Pressure Alarm System 2  
8. Hot Gas Bypass Connection System 2  
(only on units with hot gas bypass.  
If no hot gas bypass, connection is  
provided in the evaporator module.  
Connect wire 8 and wire 6 to the  
24V supply).  
4"  
6 "  
(101.6mm)  
(152.4mm)  
8 1/2 "  
(215.9mm)  
9. 24V GND Condenser Fan  
10. 24V SUPPLY Condenser Fan  
12 1/2 "  
(317.5mm)  
16 1/2 "  
(419.1mm)  
NOTES:  
1. Refer to specification sheet for full load amp. and wire size amp. ratings.  
2. Control voltage wiring must be a minimum of 16 GA (1.6mm) for up to 75’ (23m) or not  
to exceed 1 volt drop in control line.  
DPN000249_Rev0  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation and Installation  
2.6  
Outdoor Air-Cooled Condensing Unit Installation  
2.6.1 Location Considerations  
To insure a satisfactory air supply, locate air-cooled propeller fan condensing units in an environment  
providing clean air, away from loose dirt and foreign matter that may clog the coil. Condensing units  
must not be located in the vicinity of steam, hot air, or fume exhausts, or closer than 18 inches from a  
wall, obstruction, or adjacent unit. Avoid areas where heavy snow will accumulate at air inlet and dis-  
charge locations.  
The condensing unit should be located for maximum security and maintenance accessibility. Avoid  
ground-level sites with public access.  
Install a solid base, capable of supporting the weight of the condensing unit. The base should be at  
least 2 inches higher than the surrounding grade and 2 inches larger than the dimensions of the con-  
densing unit base. For snowy areas, a base of sufficient height to clear snow accumulation must be  
installed.  
2.6.2 Piping Connections  
Details for refrigerant (R-22) loop piping are in Figure 12 - Piping connections - indoor air-  
2.6.3 Electrical Connections  
requirements and cautions. Refer to electrical schematic when making connections.  
Power Connections  
The outdoor condensing unit requires its own power source and earth ground, with a disconnect  
switch (field supplied) to isolate the unit for maintenance.  
Control Connections  
Field-supplied control wires must be connected between the evaporator and the condensing unit. (See  
Figure 6 and the electrical schematic on the units for more details.) Seven (7) wires are required  
between the evaporator and condensing unit. Eighth and ninth wires are required on systems with  
hot gas bypass.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Site Preparation and Installation  
Figure 15 Electrical field connections - outdoor condensing unit  
Field supplied unit  
disconnect switch.  
Single or three phase  
electric service not provided  
by Liebert.  
Field supplied 24V NEC class 2  
wiring to evaporator module.  
Electric service  
connection  
to contactor  
or terminal block.  
Factory wired  
to components on  
electric panel.  
Single or three phase  
electric service not  
provided by Liebert.  
High voltage  
electric power  
supply entrance.  
Heatrejection connection.Field  
supplied 24V NEC class 2 wiring.  
Wire connections from evaporator module:  
1 24V GND System 1  
Low voltage  
electric power supply  
entrance.  
2 24V Supply System 1  
3 High Pressure Alarm System 1  
4 Hot Gas Bypass Connection System 1  
(only on units with hot gas bypass.  
If no hot gas bypass, connection is  
provided in the evaporator module.  
Connect wire 4 and wire 2 to the  
24V supply).  
Earth ground connection  
terminal for field wiring.  
5 24V GND System 2  
6 24V Supply System 2  
7 High Pressure Alarm System 2  
8 Hot Gas Bypass Connection System 2  
(only on units with hot gas bypass.  
If no hot gas bypass, connection is  
provided in the evaporator module.  
Connect wire 8 and wire 6 to the  
24V supply).  
Refer to specification sheet  
for full load amp and wire size  
amp ratings.  
NOTE:  
9 24V GND Condenser Fan  
10 24V SUPPLY Condenser Fan  
DPN000135_Rev0  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation and Installation  
Figure 16 Footprint dimensions - outdoor condensing unit  
GUARD  
HEIGHT  
TOP  
AIR  
DISCHARGE  
D
RIGHT  
AIR  
INTAKE  
B
LEFT  
AIR  
SHADED AREA  
INDICATES A RECOMMENDED  
CLEARANCE OF 18" (457mm)  
FOR PROPER AIR FLOW  
INTAKE  
2 "  
(51mm)  
A
C
SHADED AREA  
SHADED AREA  
INDICATES A RECOMMENDED  
CLEARANCE OF 18" (457mm)  
INDICATES A RECOMMENDED  
CLEARANCE OF 24" (610mm)  
FOR COMPONENT  
REMOVABLE FRONT PANEL FOR  
ACCESS TO HIGH VOLTAGE &  
AIR FLOW  
FOR PROPER  
LOW VOLTAGE CONNECTIONS  
AND REFRIGERATION COMPONENTS  
ACCESS AND REMOVAL  
36 1/8 "  
(918mm)  
4 " TYP.  
(102mm)  
53 3/16 "  
(1351mm)  
2 " TYP.  
1/2" Bolt-Down Holes  
(6 places)  
(51mm)  
4 23/32 "  
(120mm)  
2 "  
(51mm)  
32 1/8 "  
(816mm)  
25 3/32 "  
(637mm)  
2 "  
(51mm)  
46 7/32 "  
(1174mm)  
DPN000131_Rev0  
FOOTPRINT DIMENSIONS  
Model  
Dimensional Data in. (mm)  
Net Weight  
60 Hz  
50 Hz  
Width (A)  
Height (B)  
Depth (C)  
lbs (kg)  
PFC096A-_L  
PFH096A-_H  
PFC095A-_L  
PFH095A-_L  
53 (1343)  
53 (1343)  
36-1/4 (918)  
36-1/4 (918)  
38-1/2 (978)  
38-1/2 (978)  
488 (222)  
488 (222)  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation and Installation  
Figure 17 Piping and electrical connections - outdoor condensing unit  
SL-11081Page7  
Model Numbers  
60 Hz 50 Hz  
PFC096A-L PFC095A-L  
Electrical Connections In. (mm)  
Piping Connections In. (mm)  
A
B
C
D
E
F
G
2
(51)  
6
8-1/2  
(216)  
4-3/4 7-3/4 8-1/2 11-1/2  
(121) (197) (216) (292)  
(152)  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation and Installation  
2.7  
Indoor Water- and Glycol-Cooled Condensing Unit Installation  
2.7.1 Location Considerations  
The condensing unit may be located above the dropped ceiling or any remote indoor area. If noise is of  
concern, the condensing unit should be located away from personnel. Normal operating sound may be  
objectionable if the condensing unit is placed near quiet work areas.  
To mount the unit in the ceiling, refer to 2.4 - Installing the Evaporator or Chilled-Water Units.  
2.7.2 Piping Connections  
Details for Refrigerant (R-22) Loop piping are in 2.4.3 - Piping Connections and Coolant  
Water/Glycol Piping Considerations  
Refer to Figure 20 for recommended field installed piping hardware such as shut-off valves and hose-  
bibs. Water filters should be installed if water quality is poor. Filters will extend the service life and  
efficiency of the condensers.  
Condensing Unit Fluid Requirements  
The maximum fluid pressure is 150 psi standard pressure or 350 psi for high pressure units (Refer to  
unit serial tag and model number description page at beginning of this manual).  
NOTE  
HVAC grade ethylene or propylene glycol should be used on glycol systems.  
Automotive antifreeze must not be used.  
Regulating Valve  
Water/Glycol-cooled units include a coolant flow regulating valve which is factory adjusted and should  
not need field adjustment.  
Standard water pressure and high water pressure valves are adjusted differently. Contact Liebert  
Service before making any adjustments.  
2.7.3 Electrical Connections  
requirements and cautions. Refer to electrical schematic when making connections. Refer to serial tag  
for full load amp and wire size amp ratings.  
Control Connections  
A six-wire control connection is required from the evaporator unit to the water/glycol condensing unit.  
Two (2) additional wires are required when hot gas bypass is ordered. Glycol-cooled units also  
require a two-wire control connection to the drycooler and pump package.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Site Preparation and Installation  
Figure 18 Indoor water/glycol condensing unit dimensional data  
1. 24V GND System 1  
2. 24V Supply System 1  
3. High-Pressure Alarm  
System 1  
4. Hot Gas Bypass  
Connection System 1  
(only on units with hot  
gas bypass. If no hot gas  
bypass, connection is  
provided in the  
evaporator module.  
Connect wire 4 and wire 2  
to the 24V supply).  
5. 24V GND System 2  
6. 24V Supply System 2  
7. High-Pressure Alarm  
System 2  
8. Hot Gas Bypass  
Connection System 2  
(only on units with hot  
gas bypass. If no hot gas  
bypass, connection is  
provided in the  
evaporator module.  
Connect wire 8 and wire 6  
to the 24V supply).  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation and Installation  
Figure 19 Indoor water/glycol condensing unit electrical field connections  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation and Installation  
Figure 20 System piping with indoor water/glycol-cooled condensing unit  
Two circuits provided. Single circuit shown.  
SL-11088Pg7  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation and Installation  
2.8  
Optional Equipment Piping  
2.8.1 Free-Cooling Coil (GLYCOOL)  
The free-cooling coil is a secondary coil located upstream of the DX coil. To take maximum advantage  
of available free-cooling, the secondary coil may operate at the same time as the DX coil. A tempera-  
ture sensor is factory-mounted to the free-cooling piping. When fluid temperature is sufficiently below  
the room temperature, cooling is provided by circulating the fluid through the secondary cooling coil  
(flow is controlled by a motorized valve). Compressors are staged on if needed to supplement the free-  
cooling. To keep deposits from building up in the free-cooling coil, the coil is flushed periodically.  
NOTE  
If the free-cooling coil is piped to an open water tower, a CU/NI (cupro-nickel) type coil must  
be ordered to prevent corrosion of the copper tubes; or a heat exchanger must separate the  
tower water from the free-cooling loop.  
On water-cooled systems, the free-cooling coil outlet can be field piped to the condensing unit inlet,  
provided a 3-way regulating valve has been installed within the water/glycol condensing unit (see  
Figure 21 Optional free cooling coil (3-way valve) on water/glycol units  
SL-11088Pg12  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Site Preparation and Installation  
Figure 22 Optional free cooling coil (3-way valve) on air-cooled units  
SL-11088Pg12  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation and Installation  
2.9  
Checklist for Completed Installation  
___ 1. Proper clearance for service access has been maintained around the equipment.  
___ 2. Equipment is level and lock-nuts are installed with the leveling nuts on the spring isolators.  
___ 3. Piping completed to refrigerant or coolant loop (if required). Refrigerant charge added (if  
required).  
___ 4. Condensate pump installed (if required).  
___ 5. Drain line Connected.  
___ 6. Water supply line connected to humidifier (if required). Route to allow air filter removal.  
___ 7. Field provided pan with drain installed under all cooling units and water/glycol condensing  
units.  
___ 8. Filter box installed.  
___ 9. Ducting completed.  
___ 10. Filter(s) installed in return air duct.  
___ 11. Line voltage to power wiring matches equipment serial tag.  
___ 12. Power wiring connections completed and phased correctly between disconnect switch,  
evaporator, and condensing unit, including earth ground.  
___ 13. Power line circuit breakers or fuses have proper ratings for equipment installed.  
___ 14. Control wiring connections completed to evaporator and condensing unit (if required,  
including wiring to wall-mounted control panel and optional controls).  
___ 15. Control panel DIP switches set based on customer requirements.  
___ 16. All wiring connections are tight.  
___ 17. Foreign materials have been removed from in and around all equipment installed (shipping  
materials, construction materials, tools, etc.)  
___ 18. Fans and blowers rotate freely without unusual noise.  
___ 19. Inspect all piping connections for leaks during initial operations. Correct as needed.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Microprocessor Control  
3.0 MICROPROCESSOR CONTROL  
The Microprocessor Control for the Liebert Mini-Mate2 unit features an easy to use menu-driven  
LCD display. The menus, control features, and circuit board details are described in this section.  
Detailed information concerning controls (4.0 - System Performance Microprocessor Controls)  
and alarms (5.0 - Alarms) are provided.  
3.1  
Feature Overview  
To turn the unit ON, press the ON/OFF (I/O) key after power is applied. To turn the unit OFF, press  
the ON/OFF (I/O) key before power is disconnected.  
The following control keys may be used to move through the menus, as prompted on the LCD display:  
• ON/OFF (I/O) – turns unit on or off (top far left).  
• Menu – Enables user to access the program menu to change control parameters, alarms, setback  
schedule, etc. (top near left).  
• Increase (UP) – Raises the value of displayed parameter while in a set mode (setpoints, time, etc.)  
(Arrow-top near right) and navigates the program menu.  
• Escape (ESC) – Allows user to move back to a previous menu (top far right).  
• Alarm Silence/Help – If an alarm is present, pressing this keypad will silence he alarm. If this key  
is pressed when no alarms are present, help text will appear (bottom near left).  
• Decrease (DOWN) Arrow – Lowers the value of displayed parameter while in a set mode (bottom  
near right) and navigates the program menu.  
• Enter – After setting a control point, press ENTER to store the information in the microprocessor  
(bottom far right) Also, press ENTER to select a menu item.  
Figure 23 Wall box  
Active alarms are displayed on the LCD screen and sound an audible beeper. To silence an alarm,  
press the Alarm Silence/Help key as prompted on the display.  
Setpoints, DIP switch settings, and other selections were made during factory testing of your unit and  
are based upon typical operating experience. (Other default selections were made according to options  
included with your unit). MAKE ADJUSTMENTS TO THE FACTORY DEFAULT SELECTIONS  
ONLY IF THEY DO NOT MEET YOUR SPECIFICATIONS.  
Allowable ranges are displayed by pressing the help key. A password will be required (if enabled) to  
change setpoints, time delays, etc.  
The display normally shown includes the present room temperature, humidity, active status func-  
tions (cooling, heating, dehumidifying, humidifying), and active alarms. More detailed status and  
alarm information is available from the menu.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Microprocessor Control  
3.2  
Main Menu <Menu>  
Press the MENU key to display the Main Menu. The Menu selections (in the following order) include:  
• SETPOINTS  
• STATUS  
• ACTIVE ALARMS  
• ALARM HISTORY  
• TIME  
• DATE  
• SETBACK  
• SETUP OPERATION  
• SETPT PASSWORD  
• SETUP PASSWORD  
• CALIBRATE SENSOR  
• ALARM ENABLE  
• ALARM TIME DELAY  
• COM ALARM ENABLE  
• CUSTOM ALARMS  
• CUSTOM TEXT  
• DIAGNOSTICS  
• end of MENU  
Use the UP/DOWN arrow to scroll through the selections, then, when ready to select a particular  
function, press ENTER.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Microprocessor Control  
3.3  
Setpoints  
Setpoints and system setup parameters are kept in nonvolatile memory. Selecting SETPOINTS from  
the Main Menu will display the following selections:  
• TEMPERATURE SETPOINT  
• TEMPERATURE SENSITIVITY  
• HUMIDITY SETPOINT  
• HUMIDITY SENSITIVITY  
• HIGH TEMPERATURE ALARM  
• LOW TEMPERATURE ALARM  
• HIGH HUMIDITY ALARM  
• LOW HUMIDITY ALARM  
Scroll through this sub-menu by using the UP/DOWN arrow, then press ENTER to select a particu-  
lar function. To change a value, press ENTER and use the UP/DOWN arrows. When the value has  
been changed, press ENTER to store the value. For example, to change the temperature setpoint  
from the main status display:  
1. Press MENU key to display main menu.  
2. Scroll to “SETPOINTS” using the UP/DOWN arrow key. Press ENTER.  
3. Scroll to “TEMP SETPT” using the UP/DOWN arrow key. Press ENTER.  
4. Use the UP/DOWN arrow to change the value. Press ENTER.  
Table 10 Default setpoints and allowable ranges  
Setpoint  
Default  
72°F  
2.0°F  
50%  
Range  
40-90°F (5-32°C)  
1-9.9°F (0.6-5.6°C)  
20-80% RH  
Temperature Setpoint  
Temperature Sensitivity  
Humidity Setpoint  
Humidity Sensitivity  
5%  
1-30% RH  
35-95°F  
High Temperature Alarm  
Low Temperature Alarm  
80°F  
(2-35°C)  
35-95°F  
(2-35°C)  
65°F  
High Humidity Alarm  
Low Humidity Alarm  
60%  
40%  
15-85% RH  
15-85% RH  
3.4  
3.5  
Status  
The operator can monitor the percentage heating, cooling, dehumidifying, and humidifying status of  
the unit by selecting “STATUS” from the main menu.  
Active Alarms  
The operator can monitor the alarms status by selecting “ACTIVE ALARMS” which will display a  
“Alarm XX of YY” alert and description. If more than one alarm is activated, use the Up/Down arrow  
to scroll through the alarms list. (“XX” reference is the number of the alarm shown, and the “YY” ref-  
erence is the total number of alarms activated).  
3.6  
Alarm History  
A history of the 10 most recent alarms is kept in non-volatile memory complete with the date and  
time of their occurrence. The first alarm in the history is the most recent, and the 10th is the oldest. If  
the ALARM HISTORY is full (10 alarms) and a new alarm occurs, the oldest is lost and the newest is  
saved in ALARM HISTORY location 1.The rest are moved down the list by 1. ALARM HISTORY on  
new units may show the results of factory testing.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Microprocessor Control  
3.7  
Time  
The controller time clock must be set to allow for the setback control. The clock uses the 24-hour sys-  
tem (i.e., 12 midnight is entered 24:00). To change the time press ENTER to select the function, then  
use the UP/DOWN arrow to change the first character, press ENTER to store, then press the UP/  
DOWN arrow key to change the character, press ENTER to store, etc. The real time clock is backed-  
up.  
3.8  
3.9  
Date  
The controller date must be set to allow for setback control. To change the date press ENTER, then  
use the UP/DOWN arrow to change the first character, press ENTER to store, press the UP/DOWN  
arrow key to change the second character, etc.  
Setback  
The microprocessor can be programmed for night and weekend setback. Two (2) events can be pro-  
grammed for a five-day workweek and two (2) events can be programmed for a two-day weekend. The  
following table can be used to devise a setback plan.  
Table 11  
Night and weekend setback plan  
Event Weekend Weekday  
Time 1  
Temperature1  
Sensitivity 1  
Humidity 1  
Humidity Sensitivity 1  
Time 2  
Temperature 2  
Sensitivity 2  
Humidity 2  
Humidity Sensitivity 2  
3.10 Setup Operation  
Selecting SETUP OPERATION from the Main Menu will display the following selections:  
• RESTART TIME DELAY  
• C/F DEGREES  
• HUMIDITY CONTROL METHOD  
• LEAD COMPRESSOR  
• SHOW DIP SWITCH  
• VALVE TIME (if valve present)  
• CW FLUSH (if valve present)  
Use the UP/DOWN ARROW to scroll through the submenu. Press ENTER to select a particular  
function.  
3.10.1 Restart Time Delay  
This function delays unit restart after main power is restored to the unit. If several systems are oper-  
ating, the time delays should be set to different values to cause a sequential start. Delay can be set  
from 0.1 minutes (6 seconds to 9.9 minutes. Setting the value to zero (0) will prevent unit restart  
when power is restored. In this case, the unit must be restarted manually by pressing the ON/OFF  
button on the keypad.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Microprocessor Control  
3.10.2 C/F Degrees  
The control may be selected to show readings and setpoints in either degrees Fahrenheit (°F) or in  
degrees Celsius (°C). To change the value use ENTER to select this function, then use the UP/DOWN  
arrow to change the value. Press ENTER to store the value.  
3.10.3 Humidity Control Method  
The operator may select either relative (direct) or absolute (predictive) humidity control. If “relative”  
is selected, the RH control is taken directly from the RH sensor. If “absolute” is selected, the RH con-  
trol is automatically adjusted whenever return air temperature deviates from the desired tempera-  
ture setpoint (i.e., predictive humidity control). The LCD display will indicate percentage relative  
humidity for both methods of control. If the “absolute” feature is selected, the adjusted humidity read-  
ing will also be shown. When utilizing the predictive humidity control feature, the humidity level is  
automatically adjusted ~2% RH for each degree difference between the return air temperature and  
the temperature setpoint.  
Unnecessary dehumidification can result when overcooling occurs during a dehumidification cycle.  
This is due to a higher than normal RH reading caused by overcooling the room (about 2% RH for  
each degree of overcooling). This drop in temperature extends the dehumidification cycle. Later, when  
the dehumidification ends and the temperature rises to the setpoint, the RH reading falls. The final  
RH reading will then be lower than actually desired. If the temperature drop was significant enough,  
the percentage RH could be low enough to activate the humidifier.  
If the absolute humidity control is selected, over-dehumidification may be avoided. When overcooling  
occurs (i.e., causing an increase in the RH reading) the humidity control program estimates what the  
RH will be when the dehumidification cycle ends and temperature returns to the setpoint. This allows  
the dehumidification cycle to end at the proper time. Predictive humidity control can greatly reduce  
energy consumption by minimizing both compressor/reheat operation. Use the UP/DOWN ARROW  
key to select the desired humidity control method.  
3.10.4 Lead Compressor  
This function allows the user to select which compressor is the lead: Compressor 1 (3 ton), Compres-  
sor 2 (5 ton), or Auto. The factory default is Auto. If Auto is selected, the control will determine which  
compressor is to be the lead compressor based on the average room load over the previous one hour of  
operation.  
3.10.5 Show DIP Switch  
This function shows the position of the DIP switches which are located on the control board in the  
unit. 1 = Switch is “ON” and 0 = Switch is “OFF”. For more information on the DIP switches and their  
functions, see Table 17 Equipment Switch Settings.  
3.10.6 Valve Time (For Systems With a Modulating Chilled-Water Valve)  
This function shows the full valve travel time of the modulating valve on a chilled-water system. This  
is the time it takes for the valve to travel from full closed to full open. It is programmable from 50 to  
250 seconds; factory default time is 165 seconds and should not be changed unless actual valve travel  
time is not correct. The full valve travel time is used by the control to determine the appropriate valve  
position. For example, if the valve travel time is 165 seconds and 50% cooling is being called for, the  
valve will open for 83 seconds to achieve 50% open.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Microprocessor Control  
3.10.7 CW Flush (For Systems With a Modulating Chilled-Water Valve)  
This function shows the interval time at which the system will perform a modulating chilled-water  
valve system flush cycle. The factory default is 24 (hours) and is programmable from 0 (hours) which  
signifies to never flush, to 99 (hours) which signifies to flush after every 99 hours of valve non-use. If  
the valve is called on by the control to open within the programmed interval time, the timer will be  
reset to 0. The flush cycle is active even when the fan is turned off, but power is applied to the unit.  
When the interval timer reaches the programmed time, the valve will be opened for 3 minutes to flush  
any contaminates which may have collected in the system.  
Table 12 Setup functions, default values and allowable ranges  
Function  
Default  
Range  
0 to 9.9 min  
(0 = manual restart)  
Restart Time Delay  
0.1  
C/F Degrees  
Humidity Control  
Valve Time  
°F  
Rel  
165  
24  
°C or °F  
Relative or Absolute  
50 to 250 sec(s)  
0 to 99 hours  
CW Flush  
3.11 Change Passwords  
The display will prompt the operator to enter a three digit password when attempting to make  
changes. The system includes two (2) passwords, one for setpoints and one for setup. The system  
allows the password to be changed by first entering the default password set at the factory (1-2-3) for  
setpoints and (3-2-1) for setup. The password function provides system security, so that only autho-  
rized personnel are allowed to make changes to the system. (If unauthorized changes are being made,  
the passwords may be compromised and new ones should be selected). The password function can be  
disabled by setting DIP switch 8 in the wallbox to OFF, then resetting power to the unit.  
3.12 Calibrate Sensors  
The temperature and humidity sensors can be calibrated by selecting the CALIBRATE SENSORS  
menu item. The temperature sensor can be calibrated ±5°F, while the humidity sensor can be cali-  
brated ±10% RH. When calibrating the humidity sensor, the value shown will always be % RH, even  
though absolute humidity control may be selected. If absolute humidity control is selected, the Nor-  
mal Status Display will display the adjusted reading. This reading may not agree with the relative  
humidity reading displayed while in calibration.  
If the sensors are subject to frequent wide temperature and humidity swings, it may be necessary to  
shorten the cycling by increasing the sensor response time delay. If the sensors are located too close to  
the air discharge, they will likely experience rapid swings in measurement. The factory default is 30  
seconds. Another method in reducing compressor cycling is to increase the temperature and/or humid-  
ity sensitivity.  
3.13 Alarm Enable  
Each alarm can be disabled or enabled. Use the UP/DOWN ARROW to select a particular alarm,  
press Enter to select either enable or disable. Then press Enter again to store the change. When the  
alarm is disabled it will NOT report to either the wallbox beeper or the common alarm relay. The high  
water in condensate pan and high head alarms cannot be disabled.  
NOTE  
The high-water alarm will automatically shut the unit off.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Microprocessor Control  
3.14 Alarm Time Delay  
Each individual alarm can be programmed with a time delay (Table 13), causing the unit to delay a  
specified amount of time (0-255 seconds) before recognizing the alarm. The alarm condition must be  
present for the full amount of the time delay before the alarm will sound. If the alarm condition is  
diverted prematurely, the alarm will not be recognized and the time delay will automatically reset.  
NOTE  
For software alarms such as “loss of power” and “short cycle,” the time  
delay should be left at the factory default of 0.  
Table 13 Alarm default time delays  
Default Time Delay  
Alarm  
(seconds)  
Hum Prob  
2
2
Chng Fltr  
Custom Alarm #1  
Custom Alarm #2  
Custom Alarm #3  
High Temperature  
Low Temperature  
High Humidity  
0
0
0
30  
30  
30  
30  
0
Low Humidity  
Short Cycle 1 & 2  
Loss of Power  
0
3.15 Common Alarm Enable  
Each individual alarm can be selected to activate/deactivate the common alarm relay. If the energize  
common alarm function is set to YES, the relay is energized immediately as the alarm is enunciated,  
and de-energized when the alarm condition has cleared. If the alarm is completely DISABLED, the  
alarm has no effect on the common alarm relay. Use the UP/DOWN arrows to scroll to a particular  
alarm, press the ENTER button to select it, then press the ENTER key again to select Yes or No.  
3.16 Custom Alarms  
The custom alarm messages can be selected from a list of standard alarm messages, or the operator  
can write his/her own message. A MAXIMUM OF THREE (3) ALARM MESSAGES CAN BE CUS-  
TOMIZED.  
The text for custom alarms can be changed at any time by selecting “CUSTOM ALARMS”. To change  
the text for a custom alarm, select the alarm you would like to change, 1, 2 or 3. Using the UP/DOWN  
arrows, step through the list of seven standard alarm messages (listed below) and two custom alarms.  
Select the alarm message desired and store it by pressing ENTER.  
• SMOKE DETECTED  
• CUSTOM 2  
• CUSTOM 3  
• STANDBY GC PUMP  
• WATER FLOW LOSS  
• STANDBY UNIT ON  
• CUSTOM 1  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Microprocessor Control  
3.17 Custom Text  
To modify the two custom alarm messages select “CUSTOM TEXT”. Then select “Custom Text #1,”  
“Custom Text #2” or “Custom Text #3.” Text can be up to 16 characters in length and can be either a  
blank space or any of the following alphanumeric characters and symbols:  
• A,B,C,D,E,F,G,H,I,J,K,L,M,N,O,P,Q,R,S,T,U,V,W,X,Y,Z  
• #,%,*,-  
• 0,1,2,3,4,5,6,7,8 or 9  
Use the UP/DOWN arrows to select a character, then press ENTER. The cursor will move to the  
next space where you may once use the UP/DOWN arrows to select another character, etc. The cus-  
tom text alarm will be displayed only if the alarm is selected in Custom Alarms.  
LCD Display Contrast  
The level of contrast due to the viewing angle of the LCD display can be adjusted using a potentiome-  
ter screw, inside the wall box next to the display.  
Nonvolatile Memory  
All critical information is stored in nonvolatile memory. Setpoints and setup parameters are kept  
inside the microcontroller in EEPROM.  
Equipment Options Switches  
Equipment options are selected and enabled using DIP switches 1 through 7. These are located on the  
control board near TB3. These switches are factory set and should not require any user changes. The  
setting and function of the switches can be individually read on the LCD display.  
NOTE  
In order to update the DIP switch settings, power must be cycled off, then on, from the unit  
disconnect switch.  
Table 14 Equipment switch settings (unit control board)  
Switch  
OFF Position  
Step Cool  
ON Position  
Ramp Cool  
1
2
3
4
5
6
7
Step Heat  
Ramp Heat  
Not Used  
Not Used  
No GLYCOOL  
Disable 1 stage CW  
Not used  
GLYCOOL  
Enable 1 stage CW  
Not used  
1-stage  
2-stage  
dehumidification  
dehumidification  
8
Disable SCR Reheat  
Enable SCR Reheat  
Table 15 Switch settings (wallbox board)  
Switch  
OFF Position  
Beeper Disable  
Not Used  
ON Position  
Beeper Enable  
Not Used  
1
2
3
4
5
6
7
8
Not Used  
Not Used  
Enable Reheat  
Enable Hum.  
Disable Reheat  
Disable Hum.  
Disable Dehum.  
Enable Setback  
Disable Password  
Enable Dehum.  
Disable Setback  
Enable Password  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Microprocessor Control  
3.18 Run Diagnostics  
By selecting Run Diagnostics, maintenance personnel can check system inputs, outputs, and conduct  
a test of the microcontroller circuit board from the wall box control. A review of the system inputs and  
the microcontroller test can be done without interrupting normal operation.  
Test Outputs  
• When this feature is selected, the controller is effectively turned off. When stepping from one load  
to the next, the previous load is automatically turned off. The loads can also be toggled on/off by  
selecting “ENTER”. Once turned on, the output will remain on for five minutes unless toggled off  
or the test outputs function is exited by selecting “MENU/ESC” (Compressor is limited to 15 sec-  
onds on to prevent damage.  
CAUTION  
!
Testing compressor output for more than a few seconds could damage the compressor. To  
eliminate damaging the compressor during testing, DO NOT test compressor output for more  
than a few seconds.  
CAUTION  
!
Extended unit operation in the test outputs mode for troubleshooting may cause damage to  
unit. DO NOT operate unit in the test outputs mode any longer than is necessary for  
troubleshooting.  
NOTE  
Fan turned on with all loads.  
The outputs are:  
• Main Fan  
• Compr1 (3-ton)  
• Compr1 & HGBP1  
• Compr2  
• Compr2 & HGBP2  
• Compr1 & Compr2  
• Chill Water/Gly (if present)  
• Reheat 1  
• Reheat 2  
• SCR Reheats (if present)  
• Humidifier  
• Common Alarm  
Test Inputs  
With the unit on and the fan running, the input states may be displayed for the following devices:  
• Input Power  
• High Water in Pan  
• High Head Comp1  
• High Head Comp2  
• Air Sail Switch (requires additional factory-installed components)  
• Filter Clog  
• Humidifier Prob.  
• Custom Alarm #1  
• Custom Alarm #2  
• Custom Alarm #3  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Microprocessor Control  
Test Micro  
By selecting this function, the microcontroller will perform a self test lasting approximately 10 sec-  
onds. When the test is complete, the display will show the ROM checksum, ROM part number, and  
firmware revision number.  
Figure 24 Control menu  
Setpoints  
Temp Setpt  
Temp Sens  
Hum Setpt  
Alarm Time Delay  
Hum Prob  
Chng Filt  
Hum Sens  
Loss Air  
Hi Temp Alm  
Lo Temp Alrm  
Hi Hum Alm  
Lo Hum Alm  
Setup Operation  
Restart TD  
C/F Degrees  
Humidity Control  
Lead Compr  
Dipswch 00000000  
Pos 12345678  
Valve Time  
Custom #1  
Custom #2  
Custom #3  
High Temp  
Low Temp  
High Hum  
Low Hum  
Short Cyc1  
Short Cyc2  
Fan Ovrld  
Loss Pwr  
Status  
Dx Cool %  
CW Valve%  
Econo Cool %0  
Heat %  
Dehumidify% 0  
Humidify%  
0
0
0
CW Flush  
0
Menu  
Setpoints  
Status  
Active Alarms  
Alarm History  
Time  
Date  
Setback  
Setup Operation  
Setpoint  
Setpoint Password  
Enter New PSW  
Setpt PSW = 000  
Active Alarms  
No Alarms  
or  
Alarm 01 of 01  
High Head  
Com Alarm Enable  
Hum Prob  
Hi Head 1  
Hi Head 2  
Chng Fltr  
Setup Password  
Enter New PSW  
Setup PSW = 000  
Loss Air  
Time  
Date  
Custom #1  
Custom #2  
Custom #3  
Hi Water  
Status Display  
72 F 50 %RH  
NO ALARMS  
Password  
Calibrate sensor  
Temp Cal  
Setup Password  
Calibrate Sensor  
Alarm Enable  
Alarm Time Delay  
Com Alarm  
Enable  
Custom Alarms  
Custom Text  
Diagnostics  
End of Menu  
Hum Cal  
Temp Delay  
Hum Delay  
High Temp  
Low Temp  
High Hum  
Low Hum  
Short Cyc1  
Short Cyc2  
Fan Ovrld  
Loss Pwr  
Setback  
Wknd Time 1  
On/Off:  
Wknd Temp 1  
Wknd Tsens 1  
Wknd Humd 1  
Wknd Hsens 1  
Wknd Time 2  
On/Off:  
Wknd Temp 2  
Wknd Tsens 2  
Wknd Humd 2  
Wknd Hsens 2  
Wkdy Time 1  
On/Off:  
Alarm Enable  
Hum Prob  
Chng Fltr  
Loss Air  
Custom #1  
Custom #2  
Custom #3  
High Temp  
Low Temp  
High Hum  
Low Hum  
Custom Alarms  
Custom Alarm #1  
Custom Alarm #2  
Custom Alarm #3  
Custom Text  
Custom Text #1  
Custom Text #2  
Custom Text #3  
Wkdy Temp 1  
Wkdy Humd 1  
Wkdy Hsens 1  
Wkdy Time 2  
On/Off:  
Wkdy Temp 2  
Wkdy Tsens 2  
Wkdy Humd 2  
Wkdy Hsens 2  
Short Cyc1  
Short Cyc2  
Fan Ovrld  
Loss Pwr  
Diagnostics  
Test Outputs  
Test Inputs  
Test Microcontroller  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Microprocessor Control  
Figure 25 Control board (inside evaporator)  
P25  
TB3-4 Connection to Terminal #4 Wallbox  
P18  
P7  
T+  
P40  
P32  
P8  
TB3-3 Connection to Terminal #3 Wallbox  
TB3-2 Connection to Terminal #2 Wallbox  
TB3-1 Connection to Terminal #1 Wallbox  
T-  
+5V  
GND  
P33  
P34  
P26  
P5  
P16  
P16 Remote Sensor Connection  
P10  
P35  
P22  
P43  
TB  
P38  
P39  
P4  
P3 P2  
P1  
P36  
G4  
G2 G3  
G5  
Figure 26 Wall box board  
TB3-1  
TB3-2  
TB3-3  
TB4-4  
Wall Box  
DIP Switches (1-8)  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System Performance Microprocessor Controls  
4.0 SYSTEM PERFORMANCE MICROPROCESSOR CONTROLS  
4.1  
Control Type Response Proportional Control  
The percent requirement is determined by the difference between the return air temperature and the  
temperature setpoint. As the return air temperature rises above the temperature setpoint, the per-  
cent cooling required increases proportionally (from 0 to 100%) over a temperature band equal to the  
temperature sensitivity plus 1 degree Fahrenheit. The heating requirement is determined in a simi-  
lar manner as the temperature decreases below the setpoint. With this control type the temperature  
at which the room is controlled increases as the room load increases. At full load the room would be  
controlled at a temperature equal to the setpoint plus the sensitivity.  
4.2  
Cooling  
4.2.1 Multi-Step Cooling, Compressorized Direct Expansion (DX) Systems  
The system will use the 3-ton (compressor #1) and 5-ton (compressor #2) compressors in an 8-ton sys-  
tem. The control will determine the average cooling requirement updated every hour and select the  
lead compressor or, the user can select the lead compressor through the “Setup Operation” menu. At  
startup, the 3-ton compressor will be the lead compressor. The compressors will be staged on with hot  
gas bypass energized at 50 and 100% cooling requirements. The compressors will turn off at 75% and  
25% requirements.  
4.2.2 Chilled-Water Cooling (8 Ton)  
The chilled-water control valve is adjusted proportionally as the temperature control varies the  
requirement for cooling from 0% to 100%. This is based on the full valve travel time programmed in  
the “Setup Operation” menu.  
4.2.3 GLYCOOL Cooling (8 Ton)  
When GLYCOOL is available, the temperature control will calculate a total cooling requirement of  
200%. Assuming that full GLYCOOL capacity is available, the GLYCOOL valve opens proportionally  
as the requirement for cooling rises from 0 to 100%. If the call for cooling continues to increase, the  
control will energize the compressors as needed to match the average cooling requirement. As long as  
GLYCOOL is available, the control will leave the valve 100% open. If GLYCOOL cooling is not avail-  
able, the temperature control will operate the compressors in the same manner as the Multi-Step  
without GLYCOOL.  
4.3  
Reheat  
4.3.1 Electric Reheat - Staged  
For 2-stage electric reheat, they are activated when the temperature control calculates a requirement  
of 50% and 100%. They are deactivated when the requirement decreases to 75% (reheat 2) and 25%  
(reheat 1).  
4.3.2 SCR Electric Reheat  
The SCR (Silicon Controlled Rectifier) controller shall proportionally control the stainless steel  
reheats to maintain the selected room temperature. The rapid cycling made possible by the SCR con-  
troller provides precise temperature control, and the more constant element temperature extends  
heater life. During operation of the SCR control, the compressor(s) operate(s) continuously. The heat-  
ers are modulated to provide temperature control. If overcooling occurs, the compressor(s) will be  
locked off when the temperature drops to the low temperature alarm. SCR reheats are 15 kW.  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
                 
System Performance Microprocessor Controls  
4.4  
Dehumidification / Humidification Percent Required  
The humidity control for the MM2 is based on a calculated percent requirement for dehumidification  
or humidification. The percent requirement is calculated from the difference between the sensor read-  
ing and the humidity setpoint, divided by the sensitivity. The control method is selectable between  
relative and absolute. Relative humidity control is the default.  
4.4.1 Staged Dehumidification, Compressorized Direct Expansion (DX) Systems  
For the 8-ton unit operation, 1 or 2 stage dehumidification is selected through DIP switch #7. For 2  
stages, the 5-ton compressor is the lead compressor when dehumidifying. Dehumidification will be  
staged on at 50 and 100% call. The electric reheats are turned on at 25% cooling (reheat 1) and 25%  
heating (reheat 2) for improved temperature control. The reheats are deactivated at 0% and 50% cool-  
ing requirement, respectively. If overcooling occurs, the first stage of dehumidification is disabled at  
125% call for heating. If 1 stage or 2 stage is selected, dehumidification is disabled at 200% call for  
heating. Dehumidification is re-enabled at 66% call for 2 stage and 33% call for 1 stage. For optional  
hot water heating, the valve is energized at its normal point, 100% heating requirement.  
4.4.2 Humidification Operation  
System Activation  
The humidifier is activated when the humidity control calculates a requirement for 100% humidifica-  
tion, and is deactivated when the requirement falls below 50%.  
4.4.3 Dehumidification Lockout  
Dehumidification is locked out if overcooling occurs. Dehumidification on the 8-ton unit is disabled at  
125% (first stage) and 200% (all stages) heating requirement. Dehumidification is re-enabled at 66%  
and 33% heating requirement.  
4.5  
4.6  
Load Control Features  
The control system monitors the compressor and prevents it from turning on within a 3-minute period  
of being off. If this on-off cycle occurs to often (e.g. 10 times within a one hour period) a Short Cycle  
Alarm will occur.  
Communications  
The control system uses a two-wire, RS-422 channel to communicate with Liebert Site Products via a  
proprietary protocol. A converter board (ECA2) is available to allow communications with a “dumb”  
terminal or a computer using RS-232 channel. More details are provided in the Site Products and  
ECA2 User Manual.  
The communications channel provides both monitoring and control options, including:  
• TEMPERATURE/HUMIDITY: Current temperature and humidity readings.  
• STATUS (%), Cooling/heating and humidify/dehumidify operating status.  
• PRESENT ALARMS: Alarms currently activated.  
• SETPOINTS:  
• Temperature Setpoint  
• Temperature Sensitivity  
• Humidity Setpoint  
• Humidity Sensitivity  
• High Temperature Alarm  
• Low Temperature Alarm  
• High Humidity Alarm  
• Low Humidity Alarm  
• ON/OFF STATUS and CONTROL  
• SILENCE ALARM  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Alarms  
5.0 ALARMS  
The microprocessor control system will audibly and visually signal all ENABLED Alarms (including  
two (2) custom alarms). These special alarms can be chosen from the optional alarm list and/or can  
have their own fully custom text. The custom alarm inputs are contact closures wired from terminal  
24 through a normally open contact to either 50 (alarm 1), 51 (alarm 2), or 56 (alarm 3). The alarms  
can be enabled/disabled (refer to 3.0 - Microprocessor Control) and a time delay of 0-255 seconds  
can be set. The alarms can also be programmed to either sound the alarm & activate the common  
alarm relay OR to sound the alarm only.  
When a new alarm occurs, it is displayed on the screen and the audible alarm is activated. (If commu-  
nicating with a Liebert Site Product, the alarm is also transmitted). The message “PRESS ALARM  
SILENCE” will prompt the operator to silence the alarm. After the alarm is silenced, the display will  
return to the Normal Status Display. Alarms can be reviewed by selecting the “ACTIVE ALARMS”  
feature. The alarms can also be silenced through communications with a Liebert Site Products Unit.  
Many alarms will reset automatically when the alarm condition is no longer present and only after it  
has been acknowledged by being “Silenced.” The exceptions are:  
1. Software alarms, i.e., Loss of Power and Short Cycle alarms will reset automatically 30 seconds  
and 90 minutes respectively, after being silenced or acknowledged; and  
2. Specific alarms monitoring overload or high pressure switches may require a manual reset  
depending upon the model.  
5.1  
Alarms: Definitions and Troubleshooting  
The following list provides a definition and troubleshooting suggestions for each type of alarm. Refer  
to 8.0 - Troubleshooting for additional details. If you need further assistance, contact your Liebert  
supplier. THE CUSTOMER MUST SPECIFY ALARM(S) AT THE TIME OF ORDER. OTHER  
DEVICES AND WIRING MAY BE REQUIRED AT THE FACTORY FOR SOME OF THE ALARMS.  
5.1.1 Custom Alarms  
Custom alarm(s) messages are programmed at the LCD display. The message displayed may be  
included in a list of provided alarms or it may be customized text (for up to three alarms). IF CUS-  
TOMIZED TEXT IS USED, MAINTENANCE PERSONNEL SHOULD BE INFORMED OF THE  
ALARM FUNCTION AND THE REQUIRED ACTION.  
5.1.2 High Head Pressure  
Compressor head pressure is monitored with a pressure switch. (One SPDT pressure switch is used).  
If head pressure exceeds 360 psig, the switch turns off the compressor contactor and sends an input  
signal to the control. The condition is acknowledged by pressing the alarm silence button on the wall  
box, which will clear if the head pressure is alleviated. If the head pressure alarm has activated three  
times, the alarm will lock until the unit is serviced. After the head-pressure problem is fixed, reset the  
control by disconnecting power to the evaporator unit.  
Air-Cooled Systems  
Check for power shut off to the condenser, condenser fans not working, defective head pressure con-  
trol valves, dirty condenser coils or crimped lines.  
Water/Glycol Systems  
Check water regulating valves. Verify water/glycol flow (i.e., pumps operating and service valves  
open). Is water tower or drycooler operating? Is the coolant temperature entering the condenser at or  
below design conditions? Is AUX relay (terminals 70 & 71) operating during cooling to turn on the  
drycooler?  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Alarms  
5.1.3 Humidity  
The humidity alarm may be activated under the following conditions:  
High: The room return air humidity exceeds the pre-set high humidity alarm setpoint. Is the unit  
set up for dehumidification? Check DIP switch.  
Low: The room return air humidity decreases to the low humidity alarm setpoint. Is the unit  
setup for humidification? Check DIP switch.  
High and Low Humidity (simultaneously): The simultaneous display of two alarms results in  
loss of the humidity input signal. DASHES WILL BE DISPLAYED IN THE HUMIDITY READ-  
ING DISPLAY. Under these conditions, the control system deactivates both humidification and  
dehumidification. Check for a disconnected cable or failed sensor.  
NOTE  
Check for proper setpoints. Does the room have a vapor barrier to seal it  
from outdoor humidity? Are doors or windows open to outside air?  
5.1.4 Temperature  
The temperature level alarm may be activated under the following conditions:  
High: The room return air temperature increases to the high temperature alarm setpoint. Check  
for proper setpoint value. Is the room load more than the unit can handle (i.e., capacity too small)?  
Make sure cooling components are operating (compressor or valves).  
Low: The room return air temperature decreases to the low temperature alarm setpoint. Check  
for proper setpoint value. Make sure all heating components are operating (e.g., contactors,  
reheats, etc.). Are reheats drawing the proper current (refer to amp rating on nameplate).  
High and Low (simultaneously): The simultaneous display of these two alarms results in loss  
of the temperature input signal (or the humidity is out of sensor range-15 to 85% RH). Dashes will  
be displayed for the temperature reading. The control system will initiate 100% cooling. Check for  
a disconnected cable or a failed sensor.  
5.1.5 Humidifier Problem Alarm  
The Humidifier Problem Alarm will sound and display a message if any of the following humidifier  
conditions occur: overcurrent detection; fill system fault or end of cylinder life.  
Check fault indicator LED on humidifier control board:  
• Constant LED on = Overcurrent  
• 1 second LED Flash = Fill System Fault  
• 1/2 second LED Flash = End of cylinder life, replace tank  
5.1.6 High-Water Alarm  
A float switch in the evaporator pan will shutdown the evaporator on a high water level. Clear the  
drain and reset power to the unit in order to clear the alarm.  
5.1.7 Loss of Power  
The Loss of Power Alarm will activate (after power is restored to the unit) if the unit has lost power or  
the disconnect switch was incorrectly turned off before the unit ON/OFF switch was pressed. A Lie-  
bert remote monitoring unit (optional) will immediately indicate loss of power.  
5.1.8 Short Cycle  
A Short Cycle Alarm will occur if a compressor system has exceeded 10 cooling start attempts in a  
one-hour period. This can be caused by room cooling load is small compared to capacity of the unit. If  
room load is low, increase temperature sensitivity to reduce cycle.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Alarms  
5.2  
Optional/Custom Alarms  
5.2.1 Change Filter  
Periodically, the return air filters in the evaporator must be changed. The Change Filter alarm noti-  
fies the user that filter replacement is necessary. A differential air pressure switch closes when the  
pressure drop across the filters becomes excessive. The switch is adjustable using the procedure on  
the switch label.  
5.2.2 Firestat  
The optional firestat feature is a bi-metal operated sensing device with a closed switch under normal  
conditions. Connected between pins 1-8 and 1-9, this device will shut down the entire unit.  
5.2.3 Smoke Detector  
The smoke detector is located in the unit, the optional smoke detector power supply is located in the  
electric panel. It constantly samples return air through a tube. No adjustments are required.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
System Operation, Testing, and Maintenance  
6.0 SYSTEM OPERATION, TESTING, AND MAINTENANCE  
This section describes system testing, maintenance and replacement procedures. Use copies of the  
Maintenance Inspection Checklist to record preventive maintenance inspections.  
WARNING  
!
Unit contains hazardous electrical voltage. Disconnect power supply before working within.  
Line side of factory disconnect remains energized when disconnect is off.  
6.1  
System Testing  
6.1.1 Environmental Control Functions  
The performance of all control circuits can be tested by changing the setpoints, which activates each  
of the main functions.  
6.1.2 Cooling  
To test the cooling function, set the setpoint to a temperature of 10°F (5°C) below room temperature.  
A call for cooling should register and prompt the equipment to begin cooling cycle. (Disregard any  
temperature alarms). Upon completion of testing, return setpoint to the desired temperature.  
6.1.3 Heating  
Reheat may be tested by setting the setpoint 10°F (5°C) above room temperature. A call for heating  
should register and prompt the equipment to begin heating cycle. (Disregard any temperature  
alarms). Upon completion of testing, return setpoint to the desired temperature.  
6.1.4 Humidification  
To check humidification, set the humidity setpoint at RH 10% above the room humidity reading. After  
a short delay, the canister will fill with water and steam will be produced. Upon completion of testing,  
return the humidity setpoint to the desired humidity.  
6.1.5 Dehumidification  
The dehumidification performance can be tested by setting the humidity setpoint at RH 10% below  
room relative humidity. The compressor should turn on. Upon completion of testing, return humidity  
setpoint to the desired humidity.  
6.1.6 Remote Shutdown  
A connection point is provided for remote shutdown devices supplied by the customer. This terminal  
strip is located in the electric panel. (Terminals 37 and 38 are fitted with a jumper when no remote  
shutdown device is installed).  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
               
System Operation, Testing, and Maintenance  
6.2  
Maintenance and Component Operation  
6.2.1 Electric Panel  
The electric panel should be inspected on a semi-annual basis for any loose electrical connections.  
6.2.2 Filters  
Filters are usually the most neglected item in an environmental control system. In order to maintain  
efficient operation, they should be checked monthly and changed as required. ALWAYS TURN  
POWER OFF BEFORE REPLACING FILTERS.  
Filters are replaced by opening the hinged door on the return air filter box.  
6.2.3 Blower System  
Monthly inspection of the blower package includes: motor mounts, belts, fan bearings, and impellers.  
Fan impellers should be thoroughly inspected and any debris removed. Check to see if they are tightly  
mounted on the fan shaft and do not rub against the fan housing during rotation. Motor and fan bear-  
ings are permanently sealed and self-lubricating and do NOT need lubricated.  
The drive belt should be checked monthly for signs of wear and proper tension. Pressing on belts mid-  
way between the sheave and pulley should produce from 1/2" to 1" (12 to 25 mm) of deflection. Belts  
that are too tight can cause excessive bearing wear.  
Belt tension can be adjusted by raising or lowering the fan motor base. Loosen nut above motor  
mounting plate to remove belt. Turn nut below motor mounting plate to adjust belt tension. If belt  
appears cracked or worn, it should be replaced with a matched belt (identically sized). With proper  
care, a belt should last several years.  
NOTE  
After adjusting or changing the belt, always be certain that motor base nuts are tightened. The  
bottom adjustment nut should be finger tight. The top locking nut should be tightened with a  
wrench.  
Air Distribution  
Since all unit models are designed for constant volume air delivery, any unusual restrictions within  
the air circuit must be avoided. High efficiency filters can reduce air performance and evaporator  
capacity.  
Blower Removal (Evaporator)  
If the blower or bearings must be removed or serviced, use the following procedure.  
1. Prepare the main center section of the three (3) piece electric panel by first marking and  
disconnecting all power and control wiring entering the panel.  
2. Remove the electric panel by removing screws from top and bottom sections  
3. Remove the bottom electric panel mounting flange from unit base.  
4. Remove the belt, motor, motor mounting plate, and tensioning bolt.  
5. Remove the four (4) screws holding the blower mounting rails to the sled.  
CAUTION  
!
Protect refrigerant and water piping from damage.  
6. Remove the (4) screws holding the blower mounting rails to the sled.  
7. Slide the blower/rail assembly forward and rotate approximately 45 degrees and remove from  
unit.  
8. Replace failed parts.  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
System Operation, Testing, and Maintenance  
6.2.4 Electric Reheat  
Reheat element sheets and fins are manufactured with stainless steel. Regular inspections are neces-  
sary to assure proper cleanliness of the reheating element. Should inspection reveal corrosion parti-  
cles on the reheating element or adjoining surfaces (including ducts and plenums), appropriate  
cleaning should be performed. Periodic replacement of the reheating element may be necessary to  
meet specific application requirements.  
6.2.5 Refrigeration System  
Each month the components of the refrigeration system should be inspected for proper function and  
signs of wear. Since in most cases evidence of malfunction is present prior to component failure, peri-  
odic inspections can be a major factor in the prevention of most system failures. Refrigerant lines  
must be properly supported and not allowed to vibrate against ceilings, floors, or the unit frame.  
Inspect all refrigerant lines every six months for signs of wear and proper support. Inspect the capil-  
lary and equalizer lines from the expansion valve.  
Suction Pressure  
Suction pressure will vary with load conditions. Suction pressure normally ranges from 58 psi to 75  
psi (405 kPa to 517 kPa). When the 3-ton circuit is operating alone, the upper range of suction pres-  
sure may approach 100 psig. This is a function of the unit design and is acceptable for scroll compres-  
sors.  
Discharge Pressure  
The discharge pressure will vary greatly with load and ambient conditions (Table 16). The high-pres-  
sure switch will shut the compressor down at its cut-out setting.  
Table 16 Typical discharge pressures  
System Design  
Air-Cooled  
psig  
(kPa)  
180-275  
(1242-1895)  
Water-Cooled  
65ºF to 85ºF water  
200-225  
(1380-1550)  
(18 to 29.4ºC)  
Glycol-Cooled  
Maximum  
210-275  
330  
(1445-1895)  
(2275)  
High Pressure Cut-Out  
360  
(2480)  
Thermostatic Expansion Valve  
The thermostatic expansion valve keeps the evaporator supplied with enough refrigerant to satisfy  
load conditions. Proper valve operation can be determined by measuring superheat level. If too little  
refrigerant is being fed to the evaporator, then the superheat will be high. Conversely, if too much  
refrigerant is being supplied, then the superheat will be low. The correct superheat setting is between  
10 and 15°F (5.6 and 8.3°C). Only the 5-ton valve is adjustable.  
Air-Cooled Condensing Units  
Restricted airflow through the condenser coil will reduce the operating efficiency of the unit. Addi-  
tionally, it can result in high compressor head pressure and loss of cooling. Using compressed air or  
commercial coil cleaner, clean the condenser coil of all debris that will inhibit airflow. In winter, do  
not permit snow to accumulate around the side or underneath the condenser. At the same time check  
for bent or damaged coil fins and repair as necessary. Check all refrigerant lines and capillaries for  
vibration and support as necessary. Carefully inspect all refrigerant lines for signs of oil leaks.  
Coaxial Condensers (Water/Glycol-Cooled Condensing Units)  
Each water or glycol-cooled condensing unit has a coaxial condenser consisting of an exterior steel  
tube and an interior copper tube. If the water supply is clean, coaxial condensers do not normally  
require maintenance or replacement. Should your system begin to operate at high head pressure with  
reduced capacity, and all other causes have been eliminated, the condenser may be obstructed or  
fouled and should be replaced.  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System Operation, Testing, and Maintenance  
Regulating Valves (Water/Glycol Condensing Units)  
The water regulating valve automatically regulate the amount of fluid necessary to remove the heat  
from the refrigeration system, permitting more fluid to flow when load conditions are high and less  
fluid to flow when load conditions are low.  
The water regulating valve is designed to begin opening at 180 psi (1240 kPa) and be fully opened at  
240 psi (1655 kPa). The valve is factory set and should not need adjustment.  
Glycol Solution Maintenance  
It is difficult to establish a specific schedule of inhibitor maintenance since the rate of inhibitor deple-  
tion depends upon local water conditions. Analysis of water samples at time of installation and every  
six (6) months should help to establish a pattern of depletion. A visual inspection of the solution and  
filter residue is often helpful in judging whether or not active corrosion is occurring. The complexity of  
problems caused by water requires expert advice from a water treatment specialist plus a regular  
maintenance program schedule. It is important to note that improper use of water treatment chemi-  
cals can cause severe problems.  
Proper inhibitor maintenance must be performed in order to prevent corrosion of the glycol system.  
Consult your glycol manufacturer for proper testing and maintenance procedures. Do not mix prod-  
ucts from different manufacturers.  
Hot Gas Bypass (Optional)  
Operation  
The hot gas bypass valve is installed between the compressor discharge piping and suction piping,  
bypassing the condenser and evaporator coils. The discharge gas mixes with the suction gas, raising  
the suction temperature and pressure and decreasing the mass flow through the evaporator. The  
higher suction temperatures could cause compressor overheating, therefore a separate liquid quench-  
ing valve is provided to mix refrigerant from the system liquid line with the discharge gas before mix-  
ing with the suction gas entering the compressor.  
During normal operation, when the evaporator is under full load the hot gas bypass equalizer pres-  
sure will remain high enough to keep the valve port closed. If the evaporator load decreases, the evap-  
orator temperature and pressure will drop. When the suction pressure reduces below the hot gas  
bypass valve setting the hot gas bypass valve opens diverting some of the refrigerant flow back to the  
compressor suction. The liquid quenching valve bulb senses this increased superheat and opens,  
allowing liquid refrigerant to mix with the discharge gas, desuperheating it.  
Proper mixing of the three refrigerant paths ensures stable operation and system performance. The  
liquid quenching valve bulb must be located downstream of all these connections to control superheat  
at the compressor inlet. Superheat settings for the liquid quenching valve are chosen to maintain con-  
sistency with the system expansion valve. During hot gas bypass operation higher superheats, 25-  
40°F (14-22°C), may be observed at the compressor. The liquid quenching valve is internally equal-  
ized and superheat is not adjustable.  
Adjustment  
1. Install the suction and discharge pressure gauge.  
2. Adjust temperature setpoint to call for cooling so that the refrigeration compressor will run  
continuously.  
3. Remove the TOP adjusting nut from the valve.  
4. Insert an Allen wrench in the brass hole at top of valve in adjusting port, and turn CLOCKWISE if a  
higher evaporator temperature is required. Adjust no more than 1/4 turn at a time. Let the system  
stabilize for 15 minutes before determining if additional adjustment is necessary.  
5. After obtaining the suction pressure required, reinstall cap tightly making sure there are no leaks.  
6. Let the evaporator operate for approximately 10 to 15 minutes to make sure the suction pressure  
is within the range desired.  
7. There may be a fluctuation of approximately 3 to 6 psig (21 to 41 kPa) on the evaporator due to  
the differential on the hot gas bypass.  
8. Return temperature setpoint to the desired setting.  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Operation, Testing, and Maintenance  
Replacement Procedures  
Compressor Replacement: Infrequently a fault in the motor insulation may result in a motor burn-  
out (if system is properly installed, motor burnout rarely occurs). Primarily this type of failure is due  
to mechanical or lubrication problems, where the burnout is a secondary consequence.  
Early detection can prevent a large percentage of the problems that can cause compressor failures.  
Periodic maintenance inspections by alert service personnel (i.e., identification of abnormal opera-  
tion) can be a major factor in reducing maintenance costs. It is easier and more cost-effective to imple-  
ment the necessary preventative steps that ensure proper system operation; rather than ignore a  
problem until it results in compressor failure and costly replacement. When troubleshooting a com-  
pressor problem, check all electrical components for proper operation:  
CAUTION  
!
Avoid touching or contacting the gas and oils with exposed skin. Severe burns will result. Use  
long rubber gloves in handling contaminated parts.  
• Check all fuses and circuit breakers.  
• Check pressure switch operation.  
• If a compressor failure has occurred, determine whether its cause is an electrical or mechanical  
problem.  
CAUTION  
!
System contains refrigerant. Recover refrigerant before maintenance  
Mechanical Failure: If you have determined that a mechanical failure has occurred, the compressor  
must be replaced.  
Electrical Failure: In the event of an electrical failure and subsequent burnout of the refrigeration com-  
pressor motor, proper procedures must be followed to thoroughly remove any acids that would cause a future  
failure. There are two kits that can be used with a complete compressor burnout: Sporlan System Cleaner  
and Alco Dri-Kleener. Follow the manufacturer's procedure. DAMAGE TO A REPLACEMENT COMPRES-  
SOR DUE TO IMPROPER SYSTEM CLEANING CONSTITUTES ABUSE UNDER THE TERMS OF THE  
WARRANTY, THEREBY VOIDING THE WARRANTY.  
Replacement compressors are available from your Liebert supplier and will be shipped to the job site  
in a reusable crate (as required by the service contractor). If the compressor is under warranty, it  
must be returned to Liebert in order to receive proper warranty credit. It should be returned in the  
same container the replacement was shipped in. The possible cause(s) or condition(s) of the damage  
should be legibly recorded on the provided return tag.  
Proper procedures to remove and replace the failed compressor are:  
1. Disconnect power  
2. Attach suction and discharge gauges to access fittings.  
3. Recover refrigerant using standard recovery procedures and equipment.  
NOTE  
Release of refrigerant to the atmosphere is harmful to the environment and unlawful.  
Refrigerant must be recycled or discarded in accordance with federal, state, and local  
regulations.  
4. Remove failed compressor.  
5. Install replacement compressor and make all connections. Pressurize and leak test the system at  
approximately 150 psig (1034kPa) pressure.  
6. Follow manufacturer's instructions for clean out kits.  
7. Evacuate the system twice to 1500 microns, and the third time to 500 microns. Break the vacuum  
each time with clean, dry refrigerant to 2 psig (13.8 kPa).  
8. Charge the system with refrigerant (R-22) based on requirements of the evaporator, condensing  
unit, and lines. Refer to the installation manual or the unit nameplate.  
9. Apply power and operate the system. Check for proper operation. Refer to Table 16 for discharge  
pressure.  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Operation, Testing, and Maintenance  
6.2.6 Steam Generating Humidifier - Operation Procedures  
Steam generating humidifiers operate efficiently over a wide range of water quality conditions and  
automatically adjust to changes in the conductivity of water. The system will automatically drain and  
refill to maintain a current setpoint and alert the operator when the humidifier canister needs to be  
replaced.  
The humidifier RUN/DRAIN switch is located in the humidifier assembly. This switch should be in  
the RUN position when the humidifier is in normal operation, and in the DRAIN position during ser-  
vice. The electronic control board for the humidifier is also located in the humidifier assembly. When  
the unit is energized, power is available to humidifier. Operation involves the following steps:  
1. During start-up, when the humidity control calls for humidification, the fill valve will open,  
allowing water to enter the canister. When the water level reaches the electrodes, current flows  
and the water will begin to warm. The canister fills until the amperage reaches the setpoint and  
the fill valve closes. As the water warms, its conductivity increases and the current flow, in turn,  
rises. If the amperage reaches 115% of the normal operating amperage, the drain valve opens and  
flushes some of the water out of the canister. This reduces electrode contact with the water and  
lowers the current flow to the amperage setpoint. Boiling soon commences and the canister  
operates normally.  
2. If the conductivity of the water is low, the canister fills and the water level reaches the canister  
full electrode before the amperage setpoint is reached. The humidifier stops filling to prevent  
overflow. Boiling should commence in time. As water is boiled off, the mineral concentration in  
the canister increases and current flow also increases. The canister eventually reaches full output  
and goes to normal operation. No drain is permitted until then.  
3. When full output is reached the circuit board starts a time cycle which is factory set at 60 seconds.  
During this repeating time cycle, the fill valve will open periodically to replenish the water being  
boiled off and maintain a “steady state” output at the setpoint. The amperage variance will  
depend on the conductivity of the water.  
4. After a period of time, the mineral concentration in the canister becomes too high. When this  
occurs, the water boils too quickly. As the water quickly boils off and less of the electrode is  
exposed, the current flow decreases. When the current crosses the low threshold point (factory set  
at 85%) before the end of the time cycle, the drain valve opens, draining the mineral laden water  
out and replacing it with fresh water. This lowers the mineral concentration and returns the  
canister to “steady state” operation and prolongs canister life. The frequency of drains depends on  
water conductivity.  
5. Over a period of time, the electrode surface will become coated with a layer of insulating material,  
which causes a drop in current flow. As this happens, the water level in the canister will slowly  
rise exposing new electrode surface to the water to maintain normal output. Eventually, the  
steady state water level will reach the canister full electrode and indicate so by activating the  
canister full alarm. At this point, all of electrode surface has been used up and the canister should  
be replaced.  
6. After the entire electrode surface has been coated, the output will slowly decrease. During these  
last hours of electrode life, the mineral concentration can increase and arcing can occur. If the  
electrodes start to arc, turn off the humidifier immediately and replace the canister with the  
identical part.  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System Operation, Testing, and Maintenance  
Replacing the Humidifier Canister  
The proper procedure to replace the humidifier canister is:  
1. Turn off the humidifier by lowering the humidity setpoint below the ambient humidity level.  
Record the original setpoint.  
2. Turn unit off at wallbox.  
3. Place the RUN/DRAIN switch in the DRAIN position to drain the water from the canister.  
4. Return the RUN/DRAIN switch to the RUN position after the canister has drained.  
5. Turn OFF the power at the main unit.  
6. Remove the cover from the humidifier cabinet.  
7. Locate the power wires to the steam canister. They are connected to the canister with 1/4" quick  
connects. Make note of the wiring configuration before removing any wires. Refer to schematic on  
unit. Slide the rubber boot back to expose the connections. Remove the three (3) power wires and  
the canister full wire. Do not loosen the screws that secure the electrodes.  
WARNING  
!
Canister and steam hose may be hot! Allow time for the humidifier to cool before replacing  
parts.  
8. Loosen the steam outlet hose clamps and slide the steam hose away from the canister fitting.  
9. Remove the canister.  
10. Reverse Previous steps to re-assemble humidifier, paying special attention to the following:  
WARNING  
!
Hazardous voltage! use extreme caution. Circuit board adjustment should be performed by  
qualified personnel only.  
Power should be disconnected prior to the procedure.  
6.2.7 Circuit Board Adjustments  
The humidifier control board governs humidifier operation. There are three potentiometers mounted  
on the board and can be used to adjust for extreme water conductivity conditions.  
POT2 controls the amperage at which the drain will energize and is clearly marked in percentages.  
This adjustment is factory set at 85%, which indicates that the unit will drain when the amperage  
falls off to 85% of the capacity setpoint. Raising the value increases the frequency of drain cycles.  
Lowering the value decreases the frequency of drain cycles.  
The frequency should be increased for highly conductive water and decreased for less conductive  
water. If adjustment is necessary, and a change of three to four percent in either direction does not  
permit normal operation of the unit, consult your Liebert supplier.  
The POT1 controls the duration of the drain cycle. This adjustment is factory set at 60 seconds  
(1 VDC) and should not be readjusted without consulting your Liebert supplier.  
The DIP switch settings are used to set the capacity of the humidifier. If the humidifier is replaced in  
the field the DIP switches should be set to the required settings described below.  
Table 17 Humidifier control board DIP switch settings  
Voltage  
208  
SW1  
On  
SW2  
On  
SW3  
On  
SW4  
Off  
Amps  
8.9  
240  
Off  
On  
On  
Off  
8.5  
380/415  
460  
Off  
Off  
Off  
Off  
5.2  
On  
On  
On  
Off  
4.5  
575  
On  
On  
Off  
Off  
3.4  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Maintenance Inspection Checklist  
7.0 MAINTENANCE INSPECTION CHECKLIST  
JOB NAME: ______________________________  
SERIAL: ______________________________  
UNIT MODEL: ______________________________  
ROOM TEMP/HUM: ______________________________  
DATE: ______________________________  
COND. MODEL: ______________________________  
FILTERS  
COMPRESSOR  
___ 1. Check/Replace Filters  
___ 2. Check Filter Switch  
___ 3. Wipe Section Clean  
___ 1. Amp Draw 1. ____ / ____ / ____  
___ 2. Amp Draw 2. ____ / ____ / ____  
___ 3. Check For Leaks/Oil Level  
___ 4. Vibration  
BLOWER SECTION  
___ 5. Noise  
___ 1. Impellers Free of Debris & Spins Freely  
___ 2. Check Belt Tension and Condition  
___ 3. Check/Lube Bearings  
___ 6. Cap Tubes (Not Rubbing)  
CONTROLS  
___ 4. Check Pulleys and Motor Mounts  
___ 5. Amp Draw ____ / ____ / ____  
___ 1. Check/Test Changeover Panel  
___ 2. Check/Test Water Detection  
___ 3. Check/Test Condensate Pump  
Operation  
REHEAT  
___ 1. Amp Draw ____ / ____ / ____  
___ 2. Inspect elements for cleanliness  
___ 4. Check/Verify Control Settings  
AIR-COOLED CONDENSER/  
DRYCOOLER  
HUMIDIFIER  
___ 1. Check for Clogs  
___ 1. Coil Clean  
___ 2. Check Humidifier Lamps/tank  
___ 3. Check for Mineral Deposits  
___ 4. Check Water Make-Up Valve for Leaks  
___ 5. Check Drain & Trap for Debris  
___ 6. Check Amp Draw ____ / ____ / ____  
___ 2. Motor Mounts Tight  
___ 3. Bearings in Good Condition  
___ 4. Piping in Good Condition  
___ 5. Ambient Settings ____ / ____ / ____  
___ 6. Motor Amp Draws ____ / ____ / ____  
___ 7. Check Electrical Connections  
___ 8. Refrigerant/Glycol Level ______  
___ 9. Cap. Tubes (Not Rubbing)  
REFRIGERATION CYCLE/SECTION  
___ 1. Check Refrigerant Lines (rubbing)  
___ 2. Suction Pressure 1.______ 2._______  
___ 3. Discharge Pressure 1.______ 2.______  
___ 4. Check Thermostatic Expansion Valve  
___ 5. Check Superheat 1.______ 2.______  
___ 6. Check Refrigerant Level (Site Glass)  
WATER/GLYCOL CONDENSER  
___ 1. Copper Tube Clean  
___ 2. Water Regulating Valve Functions  
___ 3. Glycol Solution  
___ 4. Check for Water/Glycol Leaks  
ELECTRICAL PANEL  
___ 1. Check Fuses  
GLYCOL PUMP  
___ 2. Check Electrical Connections  
___ 3. Check Operation Sequence  
___ 4. Check Contactors for Pitting  
___ 1. Pump Rotation  
___ 2. Glycol Leaks  
___ 3. Pump Operation  
___ 4. Amp Draw ____ / ____ / ____  
___ 5. Pump Changeover (If Dual)  
COMMENTS  
_________________________________________________________________________  
_________________________________________________________________________  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Troubleshooting  
8.0 TROUBLESHOOTING  
Table 18 Troubleshooting  
Symptom  
Possible Cause  
Check or Remedy  
Check voltage at input terminal block.  
No power to unit  
Control voltage fuses (at  
transformer) open  
Locate and repair short. Replace fuses.  
Float switch relay has closed  
due to high water in the  
condensate pan.  
Check drain and line. Access through left panel. Power must be  
cycled at the disconnect to reset. Check return air static pressure is  
less than 0.3" wg.  
Unit will not start  
Check terminal 37 and 38 for jumper or N/C contact. Check pins P39-  
1 and P39-2 for jumper, or N/C firestat contact. Check pins P40-12  
and 1HWAR-Com for jumper or N/C smoke detector contact.  
Jumper not in place  
“Cooling” is not displayed at  
the control panel.  
Adjust TEMP control setpoint and sensitivity to require cooling.  
Short cycle prevention  
control.  
Control software delays compressor 3 minutes cooling, from stop to  
start  
Check for 24 VAC ± 2 VAC at terminals TB2 to TB1 for Compressor 1;  
TB6 to TB5 for Compressor 2. If voltage, check contactor. If voltage,  
check freeze stat (FR1 and FR2).  
Compressor contactor not  
pulling in.  
No cooling  
Compressor high head  
pressure.  
See below for cause.  
Replace filter/dryer.  
Plugged filter/dryer.  
Check pressure gauges. At low ambient temperatures, proper  
refrigerant charge is very important on units with Lee-Temp receivers.  
Low refrigerant charge.  
Insufficient air flow across  
condenser coil  
Remove debris from coil and air inlets.  
Compressor high  
head pressure  
Water/Glycol-Cooled only:  
No fluid flowing through  
condenser.  
Check fluid supply to regulating valve. Adjust valve if necessary.  
Condenser fan not operating Check fan operation.  
DIP switch not set to enable  
humidifier option  
See DIP switch settings Table 17.  
“HUMIDIFY” not displayed  
at control panel  
Increase humidity control setpoint and sensitivity to require  
humidification.  
Check voltage at 35-1 and 35-5 on interface board for 24 VAC ±2  
VAC. If no voltage, check wiring and/or replace board. Check wiring  
from control panel to board.  
Defective board  
Humidifier does  
not operate  
Humidity display will indicate dashes. Check wiring from temperature/  
humidity board to the control board and from the wall box to the  
control board. Replace wallbox or temperature/humidity circuit board  
(if remote).  
Failed humidity sensor  
No water flow  
Make sure switch is in Run position. Check humidifier water supply  
(including filter screen) and check nylon overflow line if canister is full.  
Canister fill rate is not  
keeping up with the steam  
output  
Check fill valve screen opening and capillary tube for obstructions.  
Check water supply pressure (minimum 10 psig).  
DIP switch not set to enable  
reheat option  
See DIP switch settings Table 17.  
“HEAT” not displayed at the  
control panel  
Increase temperature setpoint to require heating.  
Reheat will not  
operate  
Reheat safety open,  
defective reheat contact or  
defective board  
Check voltage at P34-4 or P34-6 to P34-10 on interface board for 24  
VAC ± 2 VAC. If voltage, check reheat contactor and reheat safety. If  
no voltage, check wiring and/or replace board.  
Element is burned out  
Turn off power. Check element continuity with Ohm meter.  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Troubleshooting  
Table 18 Troubleshooting (continued)  
Symptom  
Possible Cause  
Check or Remedy  
Cooling cycle too  
short  
Sensor response delay too  
short  
Increase sensor response delay. See 3.12 - Calibrate Sensors.  
During period of low humidity, static electricity can cause the control  
program to freeze or display incorrect information. Although this is  
unlikely, the control can be reset by cycling power from the disconnect  
switch.  
Display freezes  
and control pads  
do not respond  
Static discharge  
Condensate  
pump does not  
operate  
Open or short circuit in  
wiring  
Find open or short circuit and repair power to pump.  
Temperature display will indicate dashes. Check wiring from  
temperature/humidity board (remote sensors) to the control board or  
from control board to wallbox. Replace temperature/humidity circuit  
board (remote sensors) or wallbox.  
Continuous  
Cooling  
Failed temperature sensor  
Continuous  
Heating  
Dehumidification  
Humidification  
Shorted wiring or failed  
control board  
Check wiring and/or replace control board.  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
NOTES  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ensuring The High Availability  
0f Mission-Critical Data And Applications.  
Technical Support / Service  
Web Site  
Emerson Network Power, the global leader in enabling business-critical  
continuity, ensures network resiliency and adaptability through  
a family of technologies—including Liebert power and cooling  
technologies—that protect and support business-critical systems.  
Liebert solutions employ an adaptive architecture that responds  
to changes in criticality, density and capacity. Enterprises benefit  
from greater IT system availability, operational flexibility and  
reduced capital equipment and operating costs.  
Monitoring  
800-222-5877  
Outside the US: 614-841-6755  
Single-Phase UPS  
800-222-5877  
Outside the US: 614-841-6755  
Three-Phase UPS  
800-543-2378  
Environmental Systems  
800-543-2778  
Outside the United States  
614-888-0246  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Europe  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD) Italy  
+39 049 9719 111  
Fax: +39 049 5841 257  
Asia  
7/F, Dah Sing Financial Centre  
108 Gloucester Road, Wanchai  
Hong Kong  
While every precaution has been taken to ensure the accuracy  
and completeness of this literature, Liebert Corporation assumes no  
responsibility and disclaims all liability for damages resulting from use of  
this information or for any errors or omissions.  
© 2007 Liebert Corporation  
All rights reserved throughout the world. Specifications subject to change  
without notice.  
852 2572220  
Fax: 852 28029250  
® Liebert and the Liebert logo are registered trademarks of Liebert  
Corporation. All names referred to are trademarks  
or registered trademarks of their respective owners.  
SL-10533_REV2_02-07  
Emerson Network Power.  
The global leader in enabling Business-Critical Continuity.  
EmersonNetworkPower.com  
AC Power  
Connectivity  
DC Power  
Embedded Computing  
Embedded Power  
Monitoring  
Outside Plant  
Racks & Integrated Cabinets  
Power Switching & Controls  
Services  
Precision Cooling  
Surge Protection  
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.  
©2007 Emerson Electric Co.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Leica DVD Player 762960 User Manual
Lennox Hearth Stove EPIC CK LP User Manual
Lenovo Personal Computer 10051 User Manual
Lifescan Blood Glucose Meter SPD2410BD User Manual
Mackie Musical Instrument U420 User Manual
Maytag Clothes Dryer MED5870TW0 User Manual
Maytag Cooktop W10274251A User Manual
MB QUART Car Speaker DWG 304 User Manual
McCulloch Trimmer MCT2024 User Manual
Micro Innovations Surge Protector NB460SP User Manual