INSTALLER’S SYSTEM SETUP
GUIDE
E 2009 Lennox Industries Inc.
Dallas, Texas, USA
icomfortt Thermostat
Touch Screen Programmable Communicating Thermostat
CONTROLS
506052−01
11/09
Litho U.S.A.
Shipping and Packing List1
1 − icomfortt Touch Screen Communicating, 7−day Programmable
Thermostat
6 − Mounting Screws
6 − Wall Anchors
1 each − Installation Quick-Start Guide, Installer’s System Setup Guide,
Homeowner’sManual, Warranty card, Warranty Audit tag
*2P1109*
*P506052-01*
Download from Www.Somanuals.com. All Manuals Search And Download.
icomfortt Thermostat Terms and Acronyms
Subnet Controller (SC): (part of the communicating thermostat) Local
device that controls the system.
tions, fan motor, and reversing valve and monitors all safety features in
the unit.
AC Control: Communicating air conditioning control. AC controls low
and high speed compressor operation, fan motor operation, and all safe-
ty monitors in the unit.
Subnet: A part of the communication network that contains devices to
control one functional HVAC system.
RSBus − Residential Serial Bus − the means for transmitting data within
the communicating system.
Discharge Air Sensor (DAS): Communicating discharge air sensor.
Provides discharge air temperature to Bus, UI, and IFC for proper opera-
tion of equipment.
Controller Area Network Protocol: Rules for networking, for transmis-
sion and receipt of information between communicating systems.
R: 24V power
Baud Rate: Maximum speed of BUS 40K baud.
C: 24V common
i+: + data information connection
i−: − data information connection
Byte: 8 bits of information transmitted on the RSBus.
IntegratedFurnace Control (IFC): Communicating control for furnace.
IFC controls ignition, CAI, blower, and monitors all safety features in the
unit.
Configuration:Function that accrues during setup of system to identify
other communicating devices. Configuration is also used in setup of a
variable capacity furnace to properly set furnace parameters.
Air Handler Control (AHC): Communicating control for air handler
units. AHC controls operation of blower, heat strips, and monitors all
safety features in the unit.
Memory Fault Recall: Method of checking for errors
Firmware:Software stored on a memory chip instead of being part of a
program
HP Control (Defrost Control) (UC): Communicating defrost control.
UC controls low and high speed compressor operation, defrost opera-
Software: Programming and applications for computer
Page 3
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
icomfortt Technical Description
The 24VAC icomfortt thermostat stores system parameters and set-
tings in a nonvolatile memory (i.e., it retains data when electrical power
S
S
includes on-board help screens,
Thermostat
connections
supports heat pumps or non−heat pump units, with up to 4 stage
heat / 2 stage compressor operation. (2 stages of heat pump heat-
ing and 2 stages of auxiliary backup heat are provided. Also, 2
stages of emergency heat are provided),
R
I+ I − C
S
S
supports Indoor Air Quality with time-based notification of consum-
ables including media filters, UVC bulbs, humidifier pads, and
PureAirt catalyst service / replacement,
supports variable capacity / multistage heat/cool, universal com-
patibility(gas/electric/heat pump/ac), and is dual fuel capable with
two balance points.
Maximum total length
of all connections on
the RSBus is limited
to 1500ft.
RSBUS
Minimum wire size is
18 gauge
Important
icomfortt Outdoor Units Control
icomfortt Furnace Control
icomfortt Air Handler Control
Always use correct software version as recommended for replacement
configuration (discovery).
External Sensors − outdoor temperature and humidity
Humidify control
Dehumidify control
Connectionsto non communication outdoor units and all accessories is
describedin the Quick−Start Installation guide. (Wiring diagrams are also
Figure 1. icomfort thermostat system
Page 4
Download from Www.Somanuals.com. All Manuals Search And Download.
506052−01 11/09
icomfortt Thermostat Features
Installing icomfortt thermostat
Refer to the Quick Start Guide for all the information about installing the
thermostatto a wall and for wiring diagrams for connecting the thermo-
stat to the system using one of a number of possible configurations.
Thermostat Type
Electronic communicating, color display touch screen, 7−day program-
mable.
Supports
After all the wiring is in place, apply power to the system. 24VAC will be-
gin to power up the thermostat.
S
S
S
S
S
S
S
Humidification Measurement and Control,
Dew Point Adjustment Control,
Dehumidification Measurement and Control,
Continue with the Installer setup that follows.
®
Humiditrol Enhanced Dehumidification Accessory (EDA),
Multi-stage HVAC Systems,
Equipment Maintenance Reminders.
On-board Help Screens.
The icomfortt thermostat’s autochangeover mode permits control of
heating, cooling, humidification, and dehumidification without user in-
volvement.
Outdoor Temperature Sensor
Communicatingoutdoor units contain a built in outdoor temperature sen-
sor.
Page 5
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
After power is applied to the thermostat for the first time, the processor
checks the system for installed communicating devices, the ꢀSystem
ue.
During the setup process, alerts may pop open to inform the installer
such alerts prior to continuing setup.
critical alert
SYSTEM DISCOVERY IN PROGRESS
Active
Critical Alert Code: 31
AIR HANDLER reports:
Lost Communication with
THERMOSTAT −
Figure 2. System discovery
setup
HELP
Latest occurrence: 8/23/09
1:57 PM
close
press for more
Thermostat 1
Figure 4. Alert window
Use this Thermostat?
press here
Figure 3. Use this thermostat screen
Page 6
Download from Www.Somanuals.com. All Manuals Search And Download.
506052−01 11/09
to scroll through the settings, the right hand side will show the current
value, for example, Current Value: (35% ) shows the current setting of
the Circulate Fan ON time.
been made, use save to store the changed data or cancel to exit the
screen and return to the list of settings.
setup
HELP
Daylight Saving Time
up/down arrows
scroll through a
numeric range for
some settings
To view/edit a setting,
highlight it, then press edit.
system settings
Enabled
Time and Date
Current Value:
(35%)
Daylight Saving
Time
Disabled
cancel
save
Circulate Fan ON
time
edit
Dealer Name
Dealer Address
typewriter tool to input
names, address, phone
numbers etc.
Dealer Phone
Number
next step
back
Dealer Email
Dealer Name
Figure 5. System settings
The following shows the range/condition and defaults for the settings.
Lennox Repairman
1
2
3
4
5
6
7
8
9
0
system setting
range/condition
default
use
q
w
e
r
t
y
u
i
o
p
Time and Date
!
@
#
$
%
^
&
(
)
Daylight Saving Time
Circulate Fan ON Time
Enabled/Disabled
15 to 45
Enabled
35%
a
s
d
f
g
h
j
k
l
−
_
=
+
cancel
save
.
*
/
Dealer Name
Lennox
z
x
c
v
b
n
m
Dealer Address
Dealer Phone Number
Dealer Email
Ċ
use type
writer to
change
back
space
CAPS
ON
(alpha−numeric
characters)
symbols
space
1−800−9−LENNOX
Ċ
Dealer Website
Figure 6. Settings change tools
Page 7
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
Setting time and date
S
Press other boxes and adjust with the arrows for all time and date
information. When the date and time is correct, press save to save
settings and return to previous settings screen.
tests
setup
HELP
setup
HELP
to adjust a setting, highlight
it, then press edit.
Time and Date
system settings
Time and Date
Current Value:
(September 15, 2009,
09:23 AM)
Daylight Saving
Time
10 :19
AM
Circulate Fan ON
time
adjust
Oct 15 2009
edit
Dealer Name
cancel
save
Dealer Address
Dealer Phone
Number
next step
back
Dealer Email
Figure 8. Set current time and date
Figure 7. View/edit time and date
NOTE − After setting the time and date, if you don’t need to add any non−
communicating devices, you may wish to accept the default system pa-
rameters and skip forward to ꢀtests". To do so, repeatedly press next
step on each screen until you get to the tests screen. From there, you
can check the systems operation. Thereafter, should you need to
change a communicating device parameter, access those settings by
pressing the equipment tab in the installer section.
When the ꢀTime and Date" screen appears, enter the correct date as fol-
lows:
S
S
Press one of the time and date boxes − the text will change to white
Press the up/down arrows to change the data.
Page 8
Download from Www.Somanuals.com. All Manuals Search And Download.
506052−01 11/09
Add/remove/modify non−communicating devices
setup
HELP
communicatingdevices for installing or removing. A list similar to that
non−communicating
device list
to adjust a setting, highlight it,
then press edit
HUMIDIFIER
Current Value:
(Not Installed)
setup
HELP
DEHUMIDIFIER
UV LIGHT
system devices
edit
HP
XP19−060−230−06
5809K00015
Add or Remove
Non−communicating
equipment?
yes
AIR HANDLER
CBX32MV−60
5809K00020
back
THERMOSTAT
49W95
A109K00139
Figure 10. Installing UV Light
A typical Installed status screen (Figure 11) shows if the device is not
installed or type of equipment installed. Use the arrows to change and
use save to save the change. (Cancel goes pack to previous screen.)
back
next step
SYSTEM
Installed Status
Figure 9. Add/remove/modify non−communicating devices
Not Installed
Humidification / Dehumidification Control Modes depend on a hu-
midifierand/or dehumidifier being added to the system. Therefore, you
must press yes on the button near "Add or Remove Non−communicating
equipment?" Also, in order for the user’s display to show these controls,
UV LIGHT
cancel
save
side of the screen indicates what is currently selected, for example, Cur-
rent Value: (Not Installed); press edit if you want to modify that setting.
Figure 11. Typical non−communicating device edit screen
Page 9
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
Modify communicating device settings
setup
HELP
Use back to return to the previous screen or next step to go on.
to adjust a setting, highlight it,
then press edit
HP
Equipment Name
setup
system devices
HELP
Compressor Short
Cycle Delay
Current Value:
(Off)
to adjust a device, highlight
it, then press edit
Defrost
Termination Temp
HP
XP19−060−230−06
5809K00015
reset
edit
Compressor Shift
Delay On/Off
about
AIR HANDLER
CBX32MV−60
5809K00020
edit
back
reset ALL
next step
THERMOSTAT
49W95
A109K00139
Figure 13. Modify communicating device settings
SYSTEM
back
Settingsavailable for the devices are dependant on the components you
have. Shown below is an example of changing the compressor shift
delay on. After using the arrows to select On, press save to save the
changes and return to the previous screen.
Figure 12. Accessing communicating device settings
With one of the devices highlighted, press about, then use arrow keys to
see a list of data about the selected device. If you select reset ALL, and
then confirm, ALL devices will be reset to their factory settings. (You
Compressor Shift Delay On/Off
On
Off
cancel
Use the up/down arrows to scroll through the device’s settings and ob-
ting, for example, Current Value: (Off). Press edit if you want to modify
that setting, or press back to return to the previous screen.
save
Page 10
Download from Www.Somanuals.com. All Manuals Search And Download.
506052−01 11/09
If you select reset and then confirm, the highlighted device will be reset
erencing only the selected device.
HP
XP19−060−230−06
5809K00015
After a reset, the device which had its settings reset to
default will display in the system devices screen in red
type. You will be required to highlight the red−type de-
least view the changed settings of the red−type de-
vices .
AIR HANDLER
CBX32MV−60
5809K00020
Resetting ALL devices to their factory default
settings will cause the system to restart the
setup process. If you want to continue, then
press ’confirm’ or press ’cancel’.
Equipment
Name
In the edit mode, the feature list will show the selected
device’s changed features in red type. Use the up/
down arrows to select each red−typed feature and
press edit. Make changes to the settings using the
Edit tools if desired, or at least, press save in each fea-
ture screen. Upon saving, the previous screen will
display and the type will again be black. Press back to
return the Modify communicating device settings
screen.
Electric Heating
Airflow
cancel
confirm
Low Cooling
Airflow
Low Cooling
Airflow
Figure 14. Reset device confirmation note
At this point press next step to advance to the test controls.
Page 11
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
Indoor air quality controls
setup
tests
equipment
HELP
(to adjust a device, highlight
it, then press edit)
system devices
XP19−060−230−06
5809K00015
To turn on humidification or dehumidification controls, in addition to
to highlight the SYSTEM selection. Press edit.
AIR HANDLER
CBX32MV−60
5809K00020
about
edit
A long list of features are listed on the right of the next screen (see figure
humidificationControl Mode. Press edit.
THERMOSTAT
49W95
A109K00139
reset ALL
next step
SYSTEM
49W95
A109K00139
back
Dependingon the type of equipment installed, the lists of options may be
controls to display, the selected option must be other than ꢀDisplay
Only".
Figure 15. Accessing the SYSTEM adjustment screen
Page 12
Download from Www.Somanuals.com. All Manuals Search And Download.
506052−01 11/09
HUMIDIFICATION modes
setup
tests
equipment
HELP
BASIC & PRECISIONĊthese modes allow user control of RH between
15 and 45%. These conditions must be met for either mode to operate:
(to adjust a setting, highlight
it, then press edit)
SYSTEM
S
S
S
S
humidification mode has been enabled, and
the unit is in HEAT mode, and
humidification demand exists (24V present at H), and
BASIC mode also requires heat demand exists (Y for HP heat, or W for
gas heat [W may be energized with G de−energized]).
Equipment Name
Current Value:
(Display Only)
Filter 1 Timer
Selection
.
.
(various)
DEW POINT CONTROLĊDew point adjustment mode will change the
humidificationsetpoint based on the outdoor temperature and a user−de-
fined dew point adjustment setting.
.
.
edit
reset
Dehumidification
Control Mode
DEHUMIDIFICATION modes
InBASIC mode, dehumidification occurs if these conditions are met and
signals are present at specific terminals:
Humidification
Control Mode
back
S
S
S
S
dehumidification has been enabled on installer settings, and
the unit is in COOL mode, and
dehumidification demand exists (RH above setpoint), and
cooling demand exists (Y1 energized).
Figure 16. SYSTEM adjustment screen
In PRECISION mode, dehumidification occurs if all BASIC conditions
are true, except cooling demand may or may not be present. Maximum
overcool from cooling set point is 2ºF.
Humidification Control Mode
Dehumidification Control Mode
Display Only
Basic
Display Only
Basic
HUMIDITROL or AUX. DEHUMIDIFIER mode requires:
S
S
S
outdoor sensor must be installed and setup
dehumidification has been enabled on installer settings, and
the unit is in COOL mode, (or if in AUTO, at least one thermostat cooling
call made prior to the dehumidification demand), and
Precision
Precision
Humiditrol
(or Auxiliary
Dehumidifier)
cancel
save
Dew Point Control
cancel
S
S
S
a dehumidification demand exists (RH above setpoint), and
outdoor temp. below 95°F; indoor temp. above 65°F, and
for HUMIDITROL, Humiditrol comfort adjust parameters as follows:
save
MAX adj. − Indoor temp > 2°F above heating setpoint
HEAT SETPOINT+COOL SETPOINT
MID adj. − Indoor temp >
2
Figure 17. Selecting Dehumidification/Humidification mode
MIN adj. − Indoor temp > 2°F below cooling setpoint
Page 13
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
The tests feature is not available until after setup has been completed
once. After you press next step in the final setup screen, the ꢀSelect
When the tests screen opens, TEST ALL will be highlighted (but not yet
selected).If you want to run TEST ALL, press select. Note your selection
on the right side says ꢀselected test TEST ALL". Also, note there are now
two buttons along the bottom labeled remove and start. Use remove to
deselect a selected test.
If you re−select the tests tab from any other screen, a message to ꢀpress
Start button below to begin system testing" appears; press start.
If you prefer, run tests one−at−a−time using the arrows to highlight a de-
sired test and then press select.
press start button below to begin system testing
Press start to begin testing.
start
setup
tests
equipment
HELP
setup
tests
equipment
HELP
select tests to run
select tests to run
selected tests
TEST ALL
TEST ALL
selected tests
TEST ALL
Blower
Blower
HP Heat − 1st
Stage
HP Heat − 1st
Stage
HP Heat − 2nd
Stage
select
HP Heat − 2nd
Stage
select
Defrost Now
Defrost Now
Cooling − 1st
Stage
Cooling − 1st
Stage
remove
start
Cooling − 2nd
Stage
skip tests
Cooling − 2nd
Stage
alerts
diagnostics
EXIT
alerts
diagnostics
EXIT
Figure 18. Select tests to run
Figure 19. Start running tests
Page 14
Download from Www.Somanuals.com. All Manuals Search And Download.
506052−01 11/09
After the tests have been started, the screen will describe which test is
running (see figure 20). After concluding that the results are the desired
results for any test, press next (if using TEST ALL) to proceed to the next
test or done (if running a single test).
After pressing done, the ꢀTesting finished" screen will appear (see figure
use diagnostics tab (to analyze the system), or use equipment tab (if
you wish to make any changes to device details).
setup
tests
equipment
HELP
TEST ALL example
CURRENT TEST: Blower
The Testing Process is Finished
Check Blower Operation
cancel
next
single test example
CURRENT TEST: Blower
Check Blower Operation
press the ’tests’ tab to run more tests.
press the ’EXIT’ tab to start normal operation.
cancel
done
alerts
diagnostics
EXIT
Figure 20. Typical tests results screens
Figure 21. Testing finished screen
Page 15
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
Equipment − Page 1 of 1
This feature allows the installer to edit details of devices in the system
without having to re−run the setup program. The following appears after
the equipment tab has been selected
setup
tests
equipment
HELP
(to adjust a setting, highlight
it, then press edit)
SYSTEM
press start button below to edit details of devices in
the system
Equipment
Name
Current Value:
(System)
Filter 1 Timer
Selection
start
Filter 2 Timer
Selection
You may view information about or modify communicating devices as
edit
reset
UV Bulb Timer
Selection
setup
tests
equipment
HELP
Humidifier Pad
Timer Selection
back
to adjust a device, highlight
it, then press edit
system devices
Figure 23. Equipment details edit
HP
XP19−060−230−
06
5809K00015
availabledevices designed to communicate in this system. Other de-
vices and additional parameters may be added at a later date. Check the
unit installation manuals (i.e. furnace, air handler, heat pump, ac unit) for
current information and default parameters.
about
AIR HANDLER
CBX32MV−60
5809K00020
edit
reset ALL
next step
THERMOSTAT
49W95
A109K00139
back
SYSTEM
Figure 22. Equipment details edit
Page 16
Download from Www.Somanuals.com. All Manuals Search And Download.
506052−01 11/09
Diagnostics − Page 1 of 1
If you need to run diagnostics to analyze the system, press thediagnos-
open.
select type of device to run
diagnostics on
run diagnostics on:
HP
HP
XP19−060−230−
06
5809K00015
select device to run
diagnostics on
run diagnostics on:
AIR HANDLER
CBX32MV−60
5809K00020
HP
XP19−060−230−
06
5809K00015
AIR HANDLER
CBX32MV−60
5809K00020
select
remove
start
diagnostics
HP
Diagnostics
diagnostics
Line Voltage
220 volts
Figure 24. Select device to run diagnostics
24VAC Voltage
24 volts
Use the arrow buttons to scroll through the list of items found on the left of
the screen. Then press select. The right side of the screen shows which
will show ꢀDIAGNOSTICS IN PROGRESS..." briefly, then change to
show the list of values and conditions discovered.
Y1 − Output
PSC Fan Relay
ECM Fan 1
ECM Fan 2
Y2 Solenoid
On
Closed
On
On
Use the arrow buttons to scroll through the information and take note of
any found to be out of operating range.
done
On
Pressdone when finished with the information and select another device
to diagnose or use EXIT if finished.
Figure 25. Running diagnostics
Page 17
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
Alerts − Page 1 of 4
setup. To view alerts otherwise, press the alerts tab. Up to 10 alerts are
stored for recall by the technician.
order of:
1. critical first (red icon),
The left side of the main alert screen shows a list of each communicating
device discovered in the system and includes model and serial number
information.The up/down arrows allow you to scroll through the list of
discovered devices. The selected device is shown in bold lettering.
2. service next (yellow icon).
If the information in the alert box exceeds the box size, press press for
more to see the remaining information.
On the right side of the alert screen, press view active alerts to list all
active alerts for either SYSTEM ALERTS (lists alerts from all communi-
cating devices) or a selected device. If there are no alerts, the display will
show ꢀThere are no new alerts that require service".
alert description
active alerts
Press view cleared alerts to list previously active alerts that were
cleared by the device or installer. Until at least one alert has been cleared
by the device or the installer, the display will show ꢀThere are no new
alerts that require service".
ALERT 1 of 5
remind later
(Service) Alert Code − (0)
(Thermostat) reports:
(Replace Filter 1)
Latest Occurrence
(04/03/09)
use the arrows to
System Devices
select a device
clear
next alert
EXIT
SYSTEM ALERTS
(08:45 PM)
(4) Occurrences
view active
alerts
HP
XP19−060−230−06
5809K00015
back
press for more
AIR HANDLER
CBX32MV−60
5809K00020
view cleared
alerts
alerts
diagnostics
THERMOSTAT
49W95
A109K00139
Figure 27. Device alert
alerts
diagnostics
EXIT
Figure 26. System Devices alerts
Page 18
506052−01 11/09
Download from Www.Somanuals.com. All Manuals Search And Download.
Alerts − Page 2 of 4
Clearing alerts
alert description
set time for next reminder
Acritical alert (red icon) identifies a system or device issue that can pre-
vent the system from working properly or at all, and if allowed to run,
could cause damage to the system. The issue raised by the alert must
be addressed before clearing the alert.
disabled
ALERT 1 of 5
3 months
(Service) Alert Code − (0)
(Thermostat) reports:
(Replace Filter 1)
Latest Occurrence
(04/03/09)
6 months
select
12 months
24 months
custom time
press ’confirm’ to clear the
alert, or press ’cancel
clearing of a critical alert; then confirm
the request (shown to the right). The de-
vice will respond to the request indicating
whether or not the alert can be cleared at
that time. If it cannot be cleared, revisit
the alert issue and make repairs accord-
ingly.
(08:45 PM)
(4) Occurrences
set
cancel
confirm
cancel
press for more
Figure 28. Set new alert date
After selecting a time period using either method and pressing set, the
The edit date option is not available for a critical alert.
A service alert (yellow icon) reminds users to service filters, humidifier
pad, UV light and PureAirt Air Purification system.
alert description
the alert was cleared and
moved to alert history.
please press ’done’ to
return to the list of
active alerts.
ALERT 1 of 5
(Service) Alert Code − (0)
(Thermostat) reports:
(Replace Filter 1)
Latest Occurrence
(04/03/09)
clearing of a service alert. If you answer
no to the ꢀwas action taken" screen
(shown to the right), the alert reappears
and is not cleared. Action must be taken,
either to perform the maintenance re-
quired, or instead of clearing, you may
edit the time to again be reminded (de-
scribed later).
was action taken?
yes
no
(08:45 PM)
(4) Occurrences
done
press for more
If you press yes to ’was action taken?’, the ꢀSet new alert date" screen
(figure 28) appears. You may chose from the list of options or set a cus-
Figure 29. Cleared alert confirmation
Page 19
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
Alerts − Page 3 of 4
Using ꢀcustom time"
set time for next reminder
alert description
ALERT 1 of 5
(Service) Alert Code − (0)
(Thermostat) reports:
(Replace Filter 1)
Latest Occurrence
(04/03/09)
Use ꢀSetting custom time" screen (figure 30) to set an exact date and
time for the reminder to appear. Press in one of the boxes to highlight it
and use the up/down arrows to change the value in that box. Repeat for
all boxes. When desired reminder is displayed, press set.
1 day
1 week
1 month
select
3 months
custom time
(08:45 PM)
(4) Occurrences
alert description
set time for next reminder
set
cancel
10
12
19
AM
press for more
ALERT 1 of 5
(Service) Alert Code − (0)
(Thermostat) reports:
(Replace Filter 1)
Latest Occurrence
(04/03/09)
19 2009
Figure 31. Remind later options
After selecting a reminder time using the listed options or a custom time,
press set; the ꢀRemind later confirmation" screen appears (see figure
32).
set
(08:45 PM)
(4) Occurrences
alert description
cancel
press for more
remind later
ALERT 1 of 5
(Service) Alert Code − (0)
(Thermostat) reports:
(Replace Filter 1)
Latest Occurrence
(04/03/09)
set for:
Figure 30. Setting custom time
Using ꢀremind later"
1/19/10 9:49AM
done
(08:45 PM)
(4) Occurrences
You may chose remind later and select from ꢀRemind later options" list
Figure 32. Remind later confirmation
Page 20
Download from Www.Somanuals.com. All Manuals Search And Download.
506052−01 11/09
Alerts − Page 4 of 4
View cleared alerts
A history of cleared alerts allows the installer to review the cleared alerts.
This information can help diagnose problems. Use the arrows to (figure
alerts screen.
If no alert or only one alert is present in the history of cleared alerts, only
the back button appears. If no alerts are present in the system or de-
vice’s history, a message will state that ꢀThere are no new alerts that re-
quire service".
alert description
history
use the arrows to
System Devices
select a device
SYSTEM ALERTS
ALERT 1 of 5
view active
(Service) Alert Code − (0)
(Thermostat) reports:
(Replace Filter 1)
Latest Occurrence
(04/03/09)
HP
XP19−060−230−06
5809K00015
alerts
AIR HANDLER
CBX32MV−60
5809K00020
(08:45 PM)
(4) Occurrences
view cleared
alerts
THERMOSTAT
49W95
A109K00139
next alert
EXIT
back
alerts
diagnostics
alerts
diagnostics
EXIT
Figure 33. System Devices alerts
Figure 34. History display
Page 21
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
Access installer program from Home screen − Page 1 of 1
To access the installer program after the unit has been placed in opera-
tion and the user home screen is displayed, press the ꢀLennox" logo and
screens.
pears; press yes to proceed (no returns the home screen).
WARNING
The following screens are intended for use by
qualified Lennox equipment installers only.
Do you want to proceed?
yes
no
Figure 36. Qualified Lennox equipment installer warning
When you press yes, the thermostat’s processor will search for commu-
nicating devices in the system. The next display will be a summary of all
alerts detected.
After initial installation, if an alert is present when you are making
changes to settings, no action on the alert is mandatory.
Figure 35. Enter installation setup mode from home screen
Page 22
Download from Www.Somanuals.com. All Manuals Search And Download.
506052−01 11/09
Reconfiguring a system − Page 1 of 2
To begin reconfiguring a system, press the setup tab.
Press confirm to continue system configuration; the screen will change
to the system discovery screen.
to proceed.
setup
tests
equipment
HELP
tests
equipment
setup
tests
HELP
configuring the system may affect some device settings.
confirm to continue, or press cancel
press start button below only if you wish to setup a
new system, or to re−setup an existing system
confirm
cancel
start
back
Figure 38. Re−configure confirmation
Figure 37. Start system configuration
If this is the first attempt to configure a system, the screen will change to
the system discovery screen.
SYSTEM DISCOVERY IN PROGRESS
The ꢀRe−configure confirmation" screen (figure 38) will only appear on
attempts to RE−CONFIGURE the system. It is a reminder that system
configuration may affect some existing device settings and prompts to
Figure 39. System discovery
Page 23
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
Reconfiguring a system − Page 2 of 2
Whilereconfiguring, the thermostat will have retained settings from the
previous configuration. If a device has been replaced and re−configura-
tion has detected its replacement device, it will know the original device
tunity to review the reconfigured devices. Use the arrow buttons to scroll
through the list of items found on the left of the screen. Press about to
highlightan option on the right side of the screen and view details about
that device. If necessary, change SYSTEM settings as described on
If this is the initial configuration, the ꢀCompatible device found" screen
does not appear.
setup
HELP
setup
system devices
HELP
view/ edit selected device’s
settings
Missing
(DEVICE ETN)
Found Compatible
(DEVICE ETN)
HP
XP19−060−230−
06
5809c00015
Model No.(control model no.)
Serial No. (control serial no.)
Model No.(control model no.)
Serial No. (control serial no.)
about
AIR HANDLER
CBX32MV−60
5809B00020
edit
reset all
Settings were not copied
THERMOSTAT
49W95
A109B00139
next
next step
back
SYSTEM
Figure 40. Compatible device found
Press next to accept the device and write the thermostat’s settings from
the previous configuration to the found compatible device. The display
changes to ꢀSettings were copied". Press next to advance to the next
screen.
Figure 41. System devices screen
Page 24
Download from Www.Somanuals.com. All Manuals Search And Download.
506052−01 11/09
Editable Parameters Table (User and Installer)
Parameter Name:
Default
Parameter Value Setting
Increment
Installer settings
Time and Date
Ċ
(Time/date elements screen)
Ċ
Ċ
1%
Ċ
Ċ
Ċ
Ċ
Ċ
Daylight Saving Time
Enabled
Enabled, Disabled
Circulate Fan − Percentage of Time ON
Dealer Contact Information – Name
Dealer Contact Information – Address
Dealer Contact Information – Phone
Dealer Contact Information – Email
Dealer Contact Information – Website
SYSTEM
35%
15 to 45%
Lennox
(Typewriter input screen)
(Typewriter input screen)
(Typewriter input screen)
(Typewriter input screen)
(Typewriter input screen)
Ċ
1−800−9−LENNOX
Ċ
Equipment Name
Ċ
(Typewriter input screen)
Calendar Time, Run Time
Calendar Time, Run Time
Calendar Time, Run Time
Calendar Time, Run Time
Calendar Time, Run Time
Enabled, Disabled
Standard, Even Heat
Staged, Modulating
3 to 9ºF
Ċ
Ċ
Filter 1 Timer Selection
Calendar Time
Calendar Time
Calendar Time
Calendar Time
Calendar Time
Disabled
Filter 2 Timer Selection
Ċ
Humidifier Pad Timer Selection
UV Bulb Timer Selection
PureAir Timer Selection
Ċ
Ċ
Ċ
Smooth Setback Recovery
Electric Heat Control Mode
Gas Heat Control Mode
Ċ
Standard
Ċ
Modulating
5ºF
Ċ
Autochangeover Temp Deadband
Max Heat Setpoint
1ºF
1ºF
1ºF
Ċ
90ºF
40 to 90ºF
Min Cool Setpoint
60ºF
60 to 99ºF
Heat/Cool Stages Locked In
Disabled
Enabled, Disabled
table continued on next page
Page 25
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
Parameter Name:
Default
Parameter Value Setting
Increment
1st Stage Differential
0.5ºF
1.5ºF
0.5 to 3ºF
.5ºF
.5ºF
.5ºF
.5ºF
.5ºF
.5ºF
Ċ
2nd Stage Differential
0.5 to 8ºF
0.5 to 8ºF
3rd Stage Differential
2.0ºF
4th Stage Differential
2.5ºF
0.5 to 8ºF
5th Stage Differential
3.0ºF
0.5 to 8ºF
6th Stage Differential
3.5ºF
0.5 to 8ºF
Stage Delay Timers
Enabled
20 Minutes
20 Minutes
20 Minutes
20 Minutes
20 Minutes
Off
Enabled, Disabled
5 to 120 Minutes
5 to 120 Minutes
5 to 120 Minutes
5 to 120 Minutes
5 to 120 Minutes
Off, 40F (4C), 45F (7C), 50F (10C), 55F (13C),
Enabled, Disabled
50 to 60ºF
2nd Stage Delay
5 Min
5 Min
5 Min
5 Min
5 Min
Ċ
3rd Stage Delay
4th Stage Delay
5thStage Delay
6th Stage Delay
Locked in 2nd Stage HP by Outdoor Temp
Balance Point Control
Defrost Target Discharge Temp
Dehumidification Control Mode
Humidification Control Mode
Autochangeover Humidification Deadband
Max Humidification Setpoint
Max Dehumidification Setpoint
OK/Humid Boundary
Disabled
55ºF
Ċ
1ºF
Display Only
Display Only
5%
Display Only, Basic, Precision
Display Only, Basic, Precision, Dew Point Control
5 to 10%
Ċ
Ċ
1ºF
45%
15 to 45%
1ºF
40%
40 to 60%
1ºF
50%
45 to 60%
1ºF
table continued on next page
Page 26
Download from Www.Somanuals.com. All Manuals Search And Download.
506052−01 11/09
Parameter Name:
Default
Parameter Value Setting
(Typewriter input screen)
Increment
AIR HANDLER
Equipment Name
Air Handler
Ċ
Electric Heating Airflow
Low Cooling Airflow
High Cooling Airflow
5CFM
5CFM
5CFM
nnnn CFM
SEE NOTE −.
NOTE: CFM Default and Values Settings are dependent on the tonnage of the unit
1: No Delays,
2: ON: No delays; OFF: 45 sec delay
3: ON: 82%/7.5min; OFF: No delays
4: ON: 50%/30s,82%/7.5min; OFF:50%/30s
Cooling Airflow Profile
1
Ċ
Low Heating Airflow
5CFM
5CFM
10CFM
10CFM
1%
High Heating Airflow
nnnn CFM
SEE NOTE −.
NOTE: CFM Default and Values Settings are dependent on the tonnage of the unit
Continuous Indoor Blower Airflow
Humidification Airflow
Dehumidification Airflow
Heating Indoor Blower OFF Delay
Heating Indoor Blower ON Delay
Cooling Indoor Blower OFF Delay
Cooling Indoor Blower ON Delay
HP Indoor Blower OFF Delay
HP Indoor Blower ON Delay
THERMOSTAT
70%
10 sec
0 sec
0 sec
2 sec
45 sec
0 sec
60 to 80% (percentage of reduction of High Cooling Airflow)
0 to 10 Seconds
0 to 5 Seconds
0 to 30 Seconds
0 to 10 Seconds
0 to 60 Seconds
0 to 30 Seconds
1 sec
1 sec
2 sec
1 sec
5 sec
5 sec
Equipment Name
Ċ
(Typewriter input screen)
−5ºF to 5ºF
Ċ
1ºF
Temp Reading Calibration
Humidity Reading Calibration
0ºF
0%
−10 to 10%
1%RH
OUTDOOR EQUIPMENT
Equipment Name (HP and AC)
Outdoor Unit
300 Seconds
On
(Typewriter input screen = up to 35 characters in string)
Ċ
60 Sec
Ċ
Compressor Short Cycle Delay (HP and AC)
Compressor Shift Delay On/Off (HP only)
Defrost Termination Temp (HP only)
60 to 300 Seconds
On, Off
50ºF
50 to 100ºF
10ºF
Page 27
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
Value
Min.
Default
Max.
Incr.
Parameter Name
FURNACE
Dependency
Note
Heating indoor blower OFF delay
Heating indoor blower ON delay
Cooling indoor blower OFF delay
Cooling indoor Blower ON Delay
Heat pump indoor blower OFF delay
Heat pump indoor blower ON delay
DIP SW
60
15
0
180
45
30
10
60
30
10
5
None
None
DIP switch setting in Non−comm.
45 sec fixed in Non−Comm. IFC
Not used on Non Com. IFC
2 sec fixed in Non−Comm. IFC
Not used on Non Com. IFC
Not used on Non Com. IFC
45
0
2
Outdoor Unit present
Outdoor Unit present
Heat Pump present
Heat Pump present
2
0
1
45
0
0
5
0
5
Gas Heat Airflow Setting
Heating Airflow Control Type
0 – Fixed CFM
DIP SW
0
1
1
DATS installed
0 – Text ID 0x000E (Fixed CFM)
1 – Text ID 0x000F (Fixed DAT)
Low Heating Airflow (CFM @ 40% heat)
325
500
425
625
750
800
925
1025
1350
1500
110
110
110
110
110
120
130
120
120
125
450
675
25
25
25
25
25
25
25
25
25
25
5
Heating Airflow Control Type = 0
70,000 BTU; 1/2 HP fan
90,000 BTU; 1/2 HP fan
90,000 BTU; 1HP fan
110,000 BTU; 1 HP fan
135,000 BTU; 1HP fan
70,000 BTU; 1/2 HP fan
90,000 BTU; 1/2 HP fan
90,000 BTU; 1HP fan
110,000 BTU; 1 HP fan
135,000 BTU; 1HP fan
70,000 BTU; 1/2 HP fan
90,000 BTU; 1/2 HP fan
90,000 BTU; 1HP fan
110,000 BTU; 1 HP fan
135,000 BTU; 1HP fan
70,000 BTU; 1/2 HP fan
90,000 BTU; 1/2 HP fan
90,000 BTU; 1HP fan
110,000 BTU; 1 HP fan
135,000 BTU; 1HP fan
625
875
1025
1100
1250
1425
1850
2050
140
High Heating Airflow (CFM @ 100%
heat)
DIP SW
DIP SW*
DIP SW*
Heating Airflow Control Type = 0
Heating Airflow Control Type = 1
Heating Airflow Control Type = 1
Low Heating Discharge Air Temperature
(DAT @ 40% heat)
140
5
140
5
140
5
140
5
High Heating Discharge Air Tempera-
ture (DAT @ 100% heat)
150
5
160
5
150
5
150
5
155
5
* − Default DAT value is rounded to the closest number on 5 deg F resolution and limited by Minimum and Maximum value.
table continued on next page
Page 28
Download from Www.Somanuals.com. All Manuals Search And Download.
506052−01 11/09
Value
Min.
Default
Max.
Incr.
Parameter Name
Dependency
Note
Cooling Airflow Setting
High Cooling Airflow
(CFM @ 100% cool)
OU tons (OUNC) *
400CFM
Min CFM
Min CFM
Min CFM
Min CFM
0
Max CFM
Max CFM
Max CFM
Max CFM
3
25
25
25
25
1
Outdoor Unit present
1/2 HP blower
1 HP blower
1/2 HP blower
1 HP blower
Low Cooling Airflow
(CFM @ lowest cool stage)
See Note1 below
2+ stage Outdoor Unit present
Outdoor Unit present
Airflow Profile − Cooling
DIP SW
0–Text ID 0x0105
(A:ON:50%/30s,82%/7.5min
OFF:50%/30s)
1–Text ID 0x0106 (B:ON:82%/7.5min;
OFF: No delays)
2–Text ID 0x0107 (C:ON: No delays;
OFF: 45sec delay)
3–Text ID 0x0108 (D:No delays)
Heat Pump Airflow Setting
High Heat Pump Airflow (CFM @
100%)
OU tons (OUNC) *
400CFM
Min CFM
Min CFM
Min CFM
Min CFM
Max CFM
Max CFM
Max CFM
Max CFM
25
25
25
25
Heat Pump present
1/2 HP blower
1 HP blower
1/2 HP blower
1 HP blower
Low Heat Pump Airflow (CFM @ lowest
stage)
See Note 2 below
2+ stage Heat Pump present
Other Parameters
Equipment Name
Furnace
N/A
N/A
N/A
25
None
None
Up to 35 characters
1/2 HP blower
Continuous Indoor Blower Airflow
DIP SW (See
Note 3)
Min CFM
Min CFM
Min CFM
Min CFM
Max CFM
Max CFM
Max CFM
Max CFM
25
1 HP blower
Humidification Airflow
Same as above
25
Humidifier present
1/2 HP blower
25
1 HP blower
Dehumidification Airflow Percentage
140
(=70%)
120
(=60%)
160
(=80%)
2
(=1%)
OU present AND SC algorithm support
Percent of High Cooling Airflow
Note 1: Minimum Outdoor Unit Cooling Stage as a percentage of High Cooling Airflow (value is rounded up to the closest number on 25 CFM resolution
Note 2: Minimum Outdoor Unit Heating Stage as a percentage of High Heat Pump Airflow (value is rounded up to the closest number on 25 CFM resolution).
Note 3: All communicating Installer Parameters default CFM values based on DIP switch setting (non−communicating value) are calculated using the CFM conversion tables and
rounded up to closest number on 25 CFM resolution.
Note 4: Parameter dependency − Certain parameters are dependent on others and may not be shown on the display.
Note 5: Default Values − Jumper/DIP switches impact the default value of some parameters.
Page 29
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
Parameter Name:
Default
Parameter Value Setting
Increment
User settings
Time and Date
Ċ
Enabled
35%
(Time/date elements screen)
Ċ
Ċ
Daylight Saving Time
Circulate Fan − Percentage of Time ON
Dealer Contact Information – Name
Dealer Contact Information – Address
Dealer Contact Information – Phone
Dealer Contact Information – Email
Dealer Contact Information – Website
Language Displayed
Enabled, Disabled
15 to 45%
1%
Ċ
Lennox
(Typewriter input screen)
Ċ
(Typewriter input screen)
Ċ
1−800−9−LENNOX
Ċ
(Typewriter input screen)
Ċ
(Typewriter input screen)
Ċ
English
(Typewriter input screen)
Ċ
English
Ċ
Temperature Display Scale
Clock Format
(F)
(F) Fahrenheit, (C) Celsius
Ċ
12H
12 Hour, 24 Hour
Ċ
Screen Lock−out
Unlocked
Always On
100%
Unlocked, Partially Locked, Fully Locked
Power Save, Always On
Ċ
Backlight Setting
Ċ
Backlight Intensity
20 to 100%
20%
Ċ
Outdoor Temp Display
Indoor Humidity Display
Filter 1 Timer
Disabled
Enabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled, Enabled
Disabled, Enabled
Ċ
Disabled, 3 Months, 6 Months, 12 Months, 24 Months, Custom Time
Disabled, 3 Months, 6 Months, 12 Months, 24 Months, Custom Time
Disabled, 3 Months, 6 Months, 12 Months, 24 Months, Custom Time
Disabled, 3 Months, 6 Months, 12 Months, 24 Months, Custom Time
Disabled, 3 Months, 6 Months, 12 Months, 24 Months, Custom Time
Disabled, 3 Months, 6 Months, 12 Months, 24 Months, Custom Time
Filter 1 Timer
Humidifier Pad Timer
UV Bulb Timer
Maintenance Timer
PureAir Timer
Page 30
Download from Www.Somanuals.com. All Manuals Search And Download.
506052−01 11/09
Alarm Codes and Troubleshooting
Alarm ID
Message Name
Action required to Clear/Recover
10
Unknown Device Detected − DEVICE2
Reconfigure the system. Press and hold Lennox Logo, press setup tab, press start, and press confirm. If still
persists, then check all DEVICE connections to make sure they are icomfort compatible.
11
Missing DEVICE2
Check all connections and cycle system power. If problem persists, then reconfigure the system (procedure
mentioned above).
12
14
Incomplete System
Thermostat did not find an Indoor Unit. Check connections and cycle power. Replace board if no response.
Too Many Devices of the Same Type
Thermostat found more than one outdoor unit, or more than 1 indoor unit, or more than 1 thermostat connected
to the system. Check wiring and remove duplicate equipment.
18
19
Low Ambient HP Heat Lockout
Notification only − Outdoor Temp is below the Low Balance Point. HP will not be used to service a Heating Call.
High Ambient Auxiliary Heat Lockout
Notification only − Outdoor Temp is above the High Balance Point. Indoor Unit (Furnace or Electric Heat) will not
be used to service a Heating Call.
29
Over Temperature Protection
Indoor Temp went above 99ºF during a heating or cooling call. Heating is not allowed. Check that Thermostat
Sensor is accurate. Check that Heating Equipment is not stuck ON (reversing value, etc.). Select system mode
to cooling to try and cool the indoor space.
30
31
32
Low Temperature Protection
Indoor Temp went below 40ºF. Cooling is not allowed. Check that cooling equipment is not stuck ON. Check
accuracy of the thermostat temperature. Try to heat the space to above 40ºF.
Lost Communication with DEVICE2
Asynchronous Reset DEVICE2
DEVICE2 is not communicating to the thermostat for more than 3 minutes. Check connections if fault persists,
then cycle power.
DEVICE2 is resetting by itself. Check power connections, and check 24VAC voltage at DEVICE. The alarm is
only cleared by pressing the clear button on the Installer Alerts Tab. If fault persists after checking connections,
replace board.
34
Must Program Unit Capacity for DEVICE2
DEVICE2 is missing the programmed unit capacity. Go to DEVICE2 and program unit capacity manually. See
unit IOM for instructions.
35
Incorrect Operation of DEVICE2
Communication Problem
DEVICE2 did not follow the command of the thermostat. Check connections and cycle power.
105
Equipment is unable to communicate. Check for miswired and/or loose connections and check for a high volt-
age source of noise close to the system (welder etc.).
110
113
114
115
116
120
124
Low AC Line Voltage
Line Voltage Low (Voltage lower than nameplate rating). Check voltage.
Line Voltage High (Voltage higher than nameplate rating). Check voltage.
No 60 Hertz Power (Check voltage and frequency).
High AC Line Voltage
AC Line Frequency/Distortion Problem
Low Secondary (24VAC) Voltage
High Secondary (24VAC) Voltage
Unresponsive DEVICE2
24 Voltage Low (Range is 18 and 30 volts ). Check voltage.
24 Voltage High (Range is 18 and 30 volts ). Check voltage.
Usually caused by delay in outdoor unit responding to indoor unit poling recycle power, check wiring.
Equipment lost communication with the thermostat. Check connections and cycle power on the thermostat.
Active Subnet Controller Missing
table continued on next page
Page 31
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
Alarm Codes and Troubleshooting
Alarm ID
Message Name
Action required to Clear/Recover
125
Control Hardware Problem
Hardware problem on the control board. Cycle power on control. Replace if problem prevents service and is
persistent.
126
Control Internal Communication Problem
Hardware problem on the control board. Cycle power on control. Replace if problem prevents service and is
persistent.
130
131
132
Configuration Jumper Missing
Corrupted Control Parameters
Configuration jumper(s) missing on control board (applicable in non−communication only).
Reconfigure the system. Replace board if service (heating cooling) is not viable.
Failed Flash CRC Check (Check Sum) Software
is corrupted.
Recycle power, if re−occurs replace control.
180
Outdoor Temperature Sensor Problem
Compare outdoor sensor resistance to temperature/resistance charts in installation instructions. Replace if
necessary.
200
201
202
Rollout Limit Switch Open
Correct unit cause of rollout trip or replace flame rollout switch and test furnace operation.
Indoor blower communication failure including power outage. Check wiring to motor.
Indoor Blower Motor Problem
ID Blower Motor & Unit Size Mismatch
Incorrect appliance capacity code selected. Check for proper configuring under: Unit Size Codes for Furnace/Air
Handler on configuration guide or in installation instructions.
203
Invalid Unit Code
No appliance capacity code selected. Check for proper configuring under: Unit Size Codes for Furnace/Air
Handler on configuration guide or in installation instructions.
204
205
207
Gas Valve Problem
Check operation and wiring of gas valve.
Gas Valve Relay Contact Closed
HSI Sensed Open
Check wiring to relay; if wiring is correct, replace relay.
Measure resistance of Hot Surface Ignition ignitor. Replace if open or not within specification range found in
IOM.
223
224
225
226
227
Low Pressure Switch Open
Check inches of water column closing pressure of low pressure switch on heat call, measure inches of water
column of operating pressure, inspect vent and combustion air inducer for correct operation and restriction.
Low Pressure Switch Stuck Closed
High Pressure Switch Failed to Close
High Pressure Switch Stuck Closed
Low Pressure Switch Open in Run Mode
Check operation of low pressure switch for stuck closed on heat call, measure inches of water column of oper-
ating pressure, inspect vent and combustion air inducer for correct operation and restriction.
Check inches of water column closing pressure of high pressure switch on heat call, measure inches of water
column of operating pressure, inspect vent and combustion air inducer for correct operation and restriction.
Check operation of high pressure switch for closing on heat call, measure inches of water column of operating
pressure, inspect vent and combustion air inducer for correct operation and restriction.
Check inches of water column closing pressure of low pressure switch on heat call, measure inches of water
column of operating pressure, inspect vent and combustion air inducer for correct operation and restriction.
228
240
Inducer/Pressure Switch Calibration Failure
Low Flame Current − Run Mode
Unable to perform pressure switch calibration. Check vent system and pressure switch wiring connections.
Check micro amperes of flame sensor in board diagnostics or field installed mode; clean or replace sensor.
Measure voltage of neutral to ground for good unit ground.
table continued on next page
Page 32
Download from Www.Somanuals.com. All Manuals Search And Download.
506052−01 11/09
Alarm Codes and Troubleshooting
Alarm ID
Message Name
Action required to Clear/Recover
241
250
252
270
271
Flame Out of Sequence − Still Present
Primary Limit Switch Open
Shut off gas, check for gas valve leak.
Check firing rate on furnace, blockage in heater, and air flow.
Check temperature rise, air flow and input rate.
Discharge Air Temperature High
Watch Guard − Flame Failure on Ignite
Watch Guard − Low Pressure Switch Open
Check for gas flow, ignitor lighting burner, flame sensor current.
Check inches of water column closing pressure of low pressure switch on heat call, measure inches of water
column of operating pressure, inspect vent and combustion air inducer for correct operation and restriction.
272
Watch Guard − Low Pressure Switch Open Run
Mode
Check operation of low pressure switch for stuck closed on heat call, measure inches of water column of oper-
ating pressure, inspect vent and combustion air inducer for correct operation and restriction. Check inches of
water column closing pressure of high pressure switch on heat call, measure inches of water column of operat-
ing pressure, inspect vent and combustion air inducer for correct operation and restriction.
273
Watch Guard − Flame Fail in Run Mode
Watch Guard − Primary Limit Switch Open
Check micro amperes of flame sensor in board diagnostics or field installed mode; clean or replace sensor.
Measure voltage of neutral to ground for good unit ground.
274
275
Check why limit is tripping, over fired, low air flow.
Shut off gas, check for gas valve leak.
Watch Guard − Flame Out of Sequence. No
Flame
276
290
Watch Guard − Calibration Failure
Ignition Circuit Problem
Unable to perform pressure switch calibration. Check vent system and pressure switch wiring connections.
Measure resistance of Hot Surface Ignition ignitor, replace if open or not within specification; otherwise replace
control.
291
292
Heat Airflow Restricted Below Min.
Indoor Blower Motor Start Problem
Check for dirty filter, unit air flow restriction, blower performance.
Indoor blower motor unable to start (seized bearing, stuck wheel, etc.). Replace motor or wheel if assembly
does not operate or meet performance.
294
295
Inducer Motor Over current
Check combustion blower bearings, wiring, amps. Replace if does not operate or meets performance.
Indoor Blower Over Temperature
Indoor blower motor over temperature (motor tripped on internal protector). Check motor bearings, amps; re-
place if necessary.
310
311
312
Discharge Air Sensor Problem
Compare outdoor sensor resistance to temperature/resistance charts in installation instructions. Replace sensor
if necessary.
Heat Rate Reduced to Match Airflow
Reduced Airflow − Indoor Blower Cutback
Furnace blower in cutback mode due to restricted airflow. Check filter and ductwork. To clear, replace filter if
needed or repair/add ductwork.
Restricted airflow − Indoor blower is running at a reduced CFM (Cutback Mode − The variable speed motor has
pre−set speed and torque limiters to protect the motor from damage caused by operating out of its designed
parameters (0 to 0.8" w.g. total external static pressure). Check filter and ductwork. To clear, replace filter if
needed or repair/add ductwork.
table continued on next page
Page 33
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
Alarm Codes and Troubleshooting
Alarm ID
Message Name
Action required to Clear/Recover
313
Indoor/Outdoor Unit Capacity Mismatch
Incorrect indoor/outdoor capacity code selected. Check for proper configuring in installation instructions. Alarm
is just a warning. The system will operate, but might not meet efficiency and capacity parameters and alarm
would clear when commissioning is exited.
345
346
Relay O Failure
O relay / Stage 1 failed (Pilot relay contacts did not close or the relay coil did not energize),
HP Jumper not Removed
Configuration jumper(s) not removed on control board cut O−R. Applicable with non communicating outdoor unit
with communicating indoor system.
347
348
349
350
Relay Y1 Failure
Y1 relay / Stage 1 failed (Pilot relay contacts did not close or the relay coil did not energize),
Y2 relay / Stage 2 failed (Pilot relay contacts did not close or the relay coil did not energize),
Configuration link R to O needs to restored Applicable in non communicating mode,
Relay Y2 Failure
IFC Error Check Jumper O to R
Electric Heat not Configured
Heat call with no configured or mis−configured electric heat. Check for proper configuring under Configuring
Electric Heat Stages in the air handler installation instructions.
351
Electric Heat Stage 1 Problem
Heat section / Stage 1 failed (Pilot relay contacts did not close or the relay coil in the electric heat section did
not energize).
352
353
354
355
400
Electric Heat Stage 2 Problem
Electric Heat Stage 3 Problem
Electric Heat Stage 4 Problem
Electric Heat Stage 5 Problem
LSOM Compressor Internal Overload Tripped
Heat section / Stage 2 failed (Same as Code 351).
Heat section / Stage 3 failed (Same as Code 351).
Heat section / Stage 4 failed (Same as Code 351).
Heat section / Stage 5 failed (Same as Code 351).
Compressor protector is open. Check for high head pressure, check compressor supply voltage.
Outdoor unit power disconnect is open.
Compressor circuit breaker or fuse(s) is open.
Broken wire or connector is not making contact.
Low or high pressure switch open if present in the system.
Compressor contactor has failed to close.
401
402
403
404
405
406
407
408
409
LSOM Compressor Long Run Cycle
LSOM Outdoor Unit System Pressure Trip
LSOM Compressor Short−Cycling
LSOM Compressor Rotor Locked
LSOM Compressor Open Circuit
Compressor ran over 18 hours on one room thermostat demand.
Outdoor unit pressure trip. Check dirty coil, fan motor, refrigerant charge.
Compressor short cycling (Running less than 4 minutes).
Check capacitor, wiring, hard−start kit, replace compressor.
Check compressor for hot (cool down), check pressures, fan motor etc. Replace compressor if unable to get
circuit to close and compressor to operate.
LSOM Compressor Open Start Circuit
LSOM Compressor Open Run Circuit
LSOM Compressor Contactor Welded
LSOM Compressor Voltage Low
Replace contactor.
Check power to unit.
table continued on next page
Page 34
Download from Www.Somanuals.com. All Manuals Search And Download.
506052−01 11/09
Alarm Codes and Troubleshooting
Alarm ID
Message Name
Action required to Clear/Recover
410
411
Open Low Pressure Switch
Remove any blockages or restrictions from indoor coils and/or fans. Check refrigerant charge and system operation.
Low Pressure Switch Strikes Lockout
Check system charge using approach and sub cooling temperatures. Reset by putting outdoor board in test
mode or resetting low voltage power.
412
413
Open High Pressure Switch
Check system operating pressures and compare to unit charging charts.
High Pressure Switch Strikes Lockout
Check system charge using approach and sub cooling temperatures. Reset by putting outdoor board in test
mode or resetting low voltage power.
414
415
High Discharge Line Temperature
Check system operating pressures and compare to unit charging charts.
High Discharge Line Temperature Strikes Lock-
out
Check system charge using approach and sub cooling temperatures. Reset by putting outdoor board in test
mode or resetting low voltage power.
416
417
Outdoor Coil Sensor Faulty
Sensor being detected open or shorted or out of temperature range. Board will not perform demand or time/tem-
perature defrost operation. (System will still heat or cool).
Discharge Sensor Faulty
The board detects open sensor or out of temperature sensor range. This fault is detected by allowing the unit to
run for 90 seconds before checking sensor resistance. If the sensor resistances not within range after 90 sec-
onds, the board will count one fault. After 5 faults, the board will lockout.
418
419
420
421
530
531
532
594
700
701
702
703
704
705
W Output Hardware Fault
Replace the control board.
W Output Hardware Fault Lockout
Defrost Out of Control
Defrost longer than 20 minutes. Check HP operation.
Check and correct the wiring.
W External Miswire Alarm
Damper End Switch Failed to Close
Damper End Switch Failed to Open
Damper Control Module Alarm
Repair/replace damper.
Repair/replace damper.
Check/replace if needed.
Discharge Air Temperature Sensor Problem
Comfort Sensor Temperature Sensor Problem
Comfort Sensor Temperature Too High
Comfort Sensor Temperature Too Low
Comfort Sensor Humidity Sensor Problem
Comfort Sensor Humidity Too High
Comfort Sensor Humidity Too Low
Check wiring. Ohm out sensor and check to temperature/resistance chart.
Recalibrate stat to clear, replace thermostat if needed.
Recalibrate stat to clear, cool down stat, adjust setpoint, replace thermostat if needed.
Recalibrate stat to clear, warm up stat, adjust setpoint, replace thermostat if needed.
Recalibrate stat to clear, adjust setpoint, replace thermostat if needed.
Recalibrate stat to clear, replace thermostat if needed.
Recalibrate stat to clear replace thermostat if needed.
Page 35
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring Diagrams − Communicating Systems
icomfort
FURNACE (IFC) OR AIR HANDLER (AHC)
OPTIONAL DIS-
CHARGE AIR SEN-
SOR (SEE DAS
NOTE)
t
DAS NOTE − The discharge air sensor
is intended to be mounted downstream
of the heat exchanger and air condi-
tioning coil. It must be placed in free
airflow, where other accessories (such
as humidifiers, UV lights, etc.) will not
interfere with its accuracy. Wiring dis-
tance between the IFC or AHC and the
discharge air sensor should not exceed
10ft when wired with 18−gauge thermo-
stat wire.
OPTIONAL OUT-
DOOR AIR SENSOR
(SEE OAS NOTE)
icomfortt
THERMOSTAT
OAS NOTE − Wiring distance between
the IFC or AHC and the outdoor tem-
perature sensor should not exceed
200ft when wired with 18−gauge ther-
mostat wire.
icomfort
t
OUTDOOR AIR
CONDITIONING OR
HEAT PUMP UNIT
RSBus
RSBus
icomfort
icomfort
icomfort
t
Thermostat
Maximum total length of all connections
on the RSBus is limited to 1500ft.
t
Indoor Furnace or Air Handler
Outdoor Condensing Unit or Heat Pump
t
Wire gauge of RSBus wire is 18.
Page 36
Download from Www.Somanuals.com. All Manuals Search And Download.
506052−01 11/09
Wiring Diagrams − Communicating Indoor/non−Communicating Outdoor Systems
icomfortt AIR HANDLER (AHC)
icomfortt FURNACE (IFC) OR AIR HANDLER (AHC)
OPTIONAL DIS-
OPTIONAL DIS-
CHARGE AIR SEN-
SOR (SEE DAS
OPTIONAL OUT-
DOOR AIR SENSOR
(SEE OAS NOTE
CHARGE AIR SEN-
SOR (SEE DAS
OPTIONAL OUT-
DOOR AIR SENSOR
(SEE OAS NOTE
icomfortt
THERMOSTAT
icomfortt
THERMOSTAT
RSBus
RSBus
Maximum total
length of all connec-
tions on the RSBus
is limited to 1500ft.
Maximum total
length of all connec-
tions on the RSBus
is limited to 1500ft.
STANDARD
OUTDOOR AIR
CONDITIONING
UNIT − 1 OR 2
STAGE
STANDARD
OUTDOOR HEAT
PUMP UNIT − 1
OR 2 STAGE
Wire gauge of
RSBus wire is 18.
Wire gauge of
RSBus wire is 18.
icomfortt Thermostat
icomfortt Thermostat
icomfortt Indoor Furnace or Air Handler
Standard Outdoor Condensing Unit
icomfortt Air Handler
Standard Outdoor Heat Pump
Page 37
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
Optional Accessories for use with any icomfortt system
NOTE: icomfortt T’STAT SENSES HUMIDITY & CON-
TROLS 24V ꢀH" OUTPUT (& 120V ꢀH" OUTPUT) TO
CYCLE HUMIDIFIER BASED ON DEMAND. NO OTH-
ER CONTROL OR HUMIDISTAT REQUIRED.
icomfort
FURNACE (IFC) OR
AIR HANDLER (AHC)
t
OPTIONAL OUTDOOR AIR SENSOR FOR USE WITH
HUMIDIFIER (IF NOT ALREADY IN THE SYSTEM FOR
OTHER FUNCTIONS. BUILT INTO ALL icomfortt OUT-
DISCHARGE AIR SENSOR
(REQUIRED FOR EVEN HEAT)
DOOR UNITS). (SEE OAS NOTE Page 36)
icomfortt
THERMOSTAT
RSBus
Maximum total
length of all con-
nections on the
RSBus is limited
to 1500ft.
Wire gauge of
RSBus wire is 18.
NOTE: 24V UV LIGHT
APPLICATIONS
Neither icomfort furnace nor
icomfort air handler transformer
will have adequate VA to power
24V UV light applications. An
additional transformer for UV
light applications is required.
Page 38
Download from Www.Somanuals.com. All Manuals Search And Download.
506052−01 11/09
Optional Accessories for use with any icomfortt system
icomfort
FURNACE OR
AIR HANDLER
t
icomfort
t
icomfort
t
FURNACE OR
AIR HANDLER
OUTDOOR AIR
CONDITIONING OR
HEAT PUMP UNIT
HEPA BYPASS FIL-
TER X2680 HEPA
INTERLOCK KIT
PASS INDOOR BLOWER
MOTOR COMMON WIRE
THROUGH CURRENT LOOP.
SEE HEPA INTERLOCK KIT
FOR INSTALLATION DE-
TAILS
icomfort
FURNACE OR
AIR HANDLER
t
STANDARD
1 OR 2 STAGE
AC OR HP UNIT
icomfort
FURNACE OR
AIR HANDLER
t
LVCS VENTILATION
CONTROL SYSTEM
SEE LVCS VENTILATION
INSTRUCTIONS FOR DAMPER
& SENSOR WIRING
Page 39
icomfortt Touch Screen 7−Day Programmable Thermostat
Download from Www.Somanuals.com. All Manuals Search And Download.
|