Lennox International Inc Oven GWB8 042IE 2 User Manual

INSTALLATION  
INSTRUCTIONS  
GWB8-042IE-2, GWB8-075IE-2  
GWB8-112IE-2, GWB8-150IE-2  
GWB8-187IE-2, GWB8-225IE-2  
GAS FIRED BOILER  
PRODUCT LITERATURE  
Lennox Industries Inc.  
Dallas, Texas  
RETAIN THESE INSTRUCTIONS FOR  
FUTURE REFERENCE  
These instructions must be afxed on  
or adjacent to the boiler.  
!
WARNING  
Improper installation, adjustment, alteration,  
service, or maintenance could result in death  
or serious injury. Refer to this manual for  
assistance. For additional information consult  
a qualied installer, service agency, or the gas  
supplier.  
This boiler cannot be used with all types of  
chimneys. Read these instructions carefully  
before installing.  
GAS-FIRED HOT WATER BOILERS  
These Gas-Fired Water boilers are low pressure,  
sectional cast iron boilers Design Certied by  
CSA (Canadian Standards Association) for  
use with Natural and Propane Gases. They  
are constructed and hydrostatically tested for  
maximum working pressure of 50 psi (pounds  
per square inch) in accordance with A.S.M.E.  
(American Society of Mechanical Engineers)  
Boiler and Pressure Vessel Code Section IV  
Standards for Cast Iron Heating Boilers.  
C.S.A. Certied  
For Natural Gas Or Propane  
Tested For 50 psi.  
ASME  
Working Pressure  
P/N# 240009135, Rev. C [06/2012]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BOILER RATINGS & CAPACITIES  
Table 1 RATINGS NATURAL AND PROPANE GASES  
**Net  
AHRI  
Rating  
Water  
*Mbh  
Vent Diameter (Inches)  
Heating  
Capacity  
*Mbh  
Input  
*Mbh  
Model  
AFUE  
To Chimney  
Horizontal Vent  
(Category III)  
(Category I)  
GWB8-042IE-2  
GWB8-075IE-2  
GWB8-112IE-2  
GWB8-150IE-2  
GWB8-187IE-2  
GWB8-225IE-2  
42.5  
75.0  
36  
63  
31  
55  
84.4  
83.4  
83.0  
82.7  
82.3  
82.0  
4
4
4
4
4
4
3
3
3
3
4
4
112.5  
150.0  
187.5  
225.0  
94  
82  
125  
155  
186  
109  
135  
162  
* MBH = 1,000 Btuh = British Thermal Unit Per Hour. Boilers are equipped for altitudes up to 2,000 feet only.  
• U.S.A. Only - For altitudes above 2,000 feet, ratings should be reduced at the rate of 4% for each  
1,000 feet above sea level.  
• Canada Only - Boilers may be used at high altitude (2,000-4500 feet/640-1350m) by using a certied  
eld conversion kit, resulting in a 10% de-rate. Contact Provincial authority having jurisdiction for  
installations above 4500 ft (1350m)above sea level.+ Heating Capacity based on D.O.E. (Department  
of Energy) test procedure.  
** Net AHRI Water Ratings indicate amount of remaining heat input that can be used to heat the radiation  
or terminal units. Net AHRI Ratings shown are based on an allowance of 1.15 Selection of  
boiler size should be based upon “Net AHRI Rating” being equal to or greater than calculated  
heat loss of building.  
Manufacturer should be consulted before selecting a boiler for installations having unusual piping  
and pickup requirements.  
New York City MEA Number 484-84-E Vol. IV  
.
This boiler cannot be used with all types of chimneys. Read these instructions carefully before installing.  
These Gas-Fired Hot Water Boilers are low pressure, sectional cast iron boilers Design Certied by C.S.A. (Canadian Standards  
Association) for use with Natural and Propane Gases. Constructed and hydrostatically tested for maximum working pressure of 50 psi in  
accordance with A.S.M.E. Boiler and Pressure Vessel Code Section IV Standards for cast iron heating boilers.  
Boilers must stand on noncombustible oor. If installed on combustible oor, please refer to Repair Parts manual for appropriate  
Combustible Floor Base part number.  
Boilers For Use At High Altitude  
Boiler is factory equipped for use at altitudes of 0-2,000 feet above sea level. For use at altitudes above 2,000 feet above sea level,  
input ratings are reduced by change in main burner orice size.  
U.S.A. Only - For altitudes above 2,000 feet above sea level, input ratings should be reduced at rate of 4% for each 1,000 feet above  
sea level. Consult National Fuel Gas Code, ANSI Z223.1/NFPA 54, and/or Natural Gas and Propane Installation Code, CAN/CSA B149.1,  
or manufacturer for correct orice sizing information.  
Canada Only - For altitudes in the range of 2,000-4,500 feet (610 - 1350m) above sea level, boilers may be eld equipped for use  
at high altitude by using a certied eld conversion kit. The change in main burner orice size results in the boiler’s input rating  
being reduced by 10%.The conversion shall be carried out by a manufacturer’s authorized representative, in accordance with the  
requirements of the manufacturer, provincial or territorial authorities having jurisdiction and in accordance with the requirements of  
CSA-B149 Natural Gas and Propane Installation Code. The certied eld conversion kit includes a conversion data plate, which must be  
attached to the boiler adjacent to the rating plate, indicating that the boiler has been converted for high altitude use. The conversion  
data plate must be lled in with the correct conversion information.  
For altitudes over 4500 feet (1350m), contact Provincial authority having jurisdiction.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
DIMENSIONS  
Model  
Width (A)  
GWB8-042IE-2  
GWB8-075IE-2  
GWB8-112IE-2  
GWB8-150IE-2  
GWB8-187IE-2  
GWB8-225IE-2  
11  
14-1/4  
17-1/2  
20-3/4  
24  
27-1/4  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION PROCEDURE  
!
NOTICE  
Follow local regulations with respect to installation  
of CO detectors.  
WARNING  
Improper installation, adjustment, alteration, service  
or maintenance could result in death or serious  
injury.  
10. FOR INSTALLATION ON NON-COMBUSTIBLE  
FLOORS ONLY - For installation on combustible  
ooring special base must be used. (See Replacement  
Parts Section.) Do Not Install Boiler on carpeting.  
1. The installation must conform to the requirements of  
the authority having jurisdiction or, in the absence  
of such requirements, to the National Fuel Gas Code,  
ANSI Z223.1/NFPA 54, and/or Natural Gas and Propane  
Installation Code, CAN/CSA B149.1  
11. Verify boiler is supplied with correct type of gas, fresh  
air for combustion, and suitable electrical supply.  
2. Where required by authority having jurisdiction,  
installation must conform to the Standard for Controls  
and Safety Devices for Automatically red Boilers,  
ANSI/ASME CSD-1.  
Figure 1 - Minimum Clearances To Combustible  
Construction  
3. This boiler series is classied as a Category I. Vent  
installation shall be in accordance with “Venting of  
Equipment ,” of the National Fuel Gas Code, ANSI  
Z223.1/NFPA 54, or “Venting Systems and Air Supply  
for Appliances,” of the Natural Gas and Propane  
Installation Code, CAN/CSA B149.1, or applicable  
provisions of the local building codes.  
6”  
Rear  
6”  
8”  
Boiler  
Front  
4. Boiler has met safe lighting and other performance  
criteria with gas manifold and control assembly on  
boiler per latest revision of ANSI Z21.13/CGA 4.9.  
5. Install such that gas ignition system components are  
protected from water (dripping, spraying, rain, etc.)  
during appliance operation and service, (circulator  
replacement, condensate trap, control replacement,  
etc.).  
18”  
6. Locate boiler on level, solid base as near chimney as  
possible and centrally located with respect to heat  
distribution system as practical.  
7. Verify you have the right size boiler before starting  
installation. See rating and capacity table.  
Table 2 - BOILER MINIMUM CLEARANCE TO  
COMBUSTIBLES  
8. When installed in utility room, door should be wide  
enough to allow largest boiler part to enter, or to  
permit replacement of another appliance such as water  
heater.  
Minimum  
Unit  
Clearances  
9. Boiler installed in building under construction, take  
care to insure clean combustion air supply during  
construction process. Airborne particulates such as  
from drywall dust and from berglass insulation can  
clog burner ports and cause incomplete combustion and  
sooting.  
Top  
6” (152mm)  
6” (152mm)  
Rear  
Control Side  
Opposite Side  
Front (Alcove)  
8” (203mm)  
6” (152mm)  
18” (457mm)  
!
WARNING  
Flue/Vent Connector  
Near Boiler Piping  
6” (152mm)  
1/2” (13mm)  
Fire hazard. Do not install boiler on combustible  
ooring or carpeting. Failure to follow these  
instructions could result in death or serious injury.  
Set unit on concrete or other noncombustible material base or  
oor. DO NOT INSTALL ON CARPETING.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENTILATION & COMBUSTION AIR  
• All Outdoor Air. Provide permanent opening(s)  
communicating directly or by ducts with outdoors.  
Provide combustion air and ventilation air in accordance  
with the section “Air for Combustion and Ventilation,” of the  
National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Sections  
8.2, 8.3 or 8.4 of Natural Gas and Propane Installation  
Code, CAN/CSA B149.1, or applicable provisions of local  
building codes.  
о Two Permanent Opening Method. Provide opening  
commencing within 12 inches of top and second  
opening commencing within 12 inches of bottom  
enclosure.  
Direct communication with outdoors or  
communicating through vertical ducts. Provide  
minimum free area of 1 in2 per 4 Mbh of total  
input rating of all appliances in enclosure.  
Provide make-up air where exhaust fans, clothes dryers,  
and kitchen ventilation equipment interfere with proper  
operation.  
Communicating through horizontal ducts.  
Provide minimum free area of 1 in2 per 2  
Mbh of total input rating of all appliances in  
enclosure.  
National Fuel Gas Code recognizes several methods  
of obtaining adequate ventilation and combustion air.  
Requirements of the authority having jurisdiction may  
override these methods.  
• Engineered Installations. Must be approved by  
authority having jurisdictions.  
о One Permanent Opening Method. Provide opening  
commencing within 12 inches of top of enclosure.  
Provide minimum clearance of 1 inch on sides  
and back and 6 inches on front of boiler (does not  
supersede clearance to combustible materials).  
• Mechanical Air Supply. Provide minimum of 0.35  
cfm per Mbh for all appliances located within space.  
Additional requirements where exhaust fans installed.  
Interlock each appliance to mechanical air supply  
system to prevent main burner operation when  
mechanical air supply system not operating.  
о Combination Indoor and Outdoor Air. Refer to  
National Fuel Gas Code for additional requirements  
for louvers, grilles, screens and air ducts.  
• All Indoor Air. Calculate minimum volume for all  
appliances in space. Use a different method if  
minimum volume not available.  
• Combination Indoor and Outdoor Air. Refer to  
National Fuel Gas Code for application information.  
National Gas and Propane Installation Code Requires  
providing air supply in accordance with:  
о Standard Method. Cannot be used if known air  
inltration rate is less than 0.40 air changes per  
hour. See Table 3 for space with boiler only. Use  
equation for multiple appliances.  
• Section 8.2 and 8.3 when combination of appliances  
has a total input of up to and including 400 Mbh (120  
kW).  
Volume 50 ft3 x Total Input [Mbh]  
о Does not have draft control device.  
о Known Air Inltration Rate. See Table 3 for  
space with boiler only. Use equation for multiple  
appliances. Do not use an air inltration rate  
(ACH) greater than 0.60.  
• Section 8.4 when combination of appliances has total  
input exceeding 400 Mbh (120 kW).  
• Refer to Natural Gas and Propane Installation Code  
for specic air supply requirements for enclosure  
or structure where boiler is installed, including air  
supply openings and ducts.  
Volume 15 ft3/ACH x Total Input [Mbh]  
о Refer to National Fuel Gas Code for opening  
requirements between connection indoor spaces.  
Table 3- Air Inltration Rate  
Known Air Inltration Rate Method (Air Changes Per Hour)  
Standard  
Method  
Input Mbh  
0.1  
0.2  
0.3  
2125  
3750  
5625  
7500  
9375  
11250  
0.4  
0.5  
0.6  
42.5  
75  
2125  
3750  
5625  
7500  
9375  
11250  
6375  
3188  
1594  
2813  
4219  
5625  
7031  
8438  
1275  
2250  
3375  
4500  
5625  
6750  
1063  
1875  
2813  
3750  
4688  
5625  
11250  
16875  
22500  
28125  
33750  
5625  
112.5  
150  
8438  
11250  
14063  
16875  
187.5  
225  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION SYSTEM PIPING  
!
WARNING  
Burn or Scald Hazard. Discharge line shall be installed to relief valve outlet connection to avoid burns,  
scalding, or water damage due to discharge of steam and/or hot water during operation.  
Discharge line shall:  
• connect to relief valve outlet and piped down to safe point of disposal. Check local codes for maximum  
distance from oor or allowable safe point of discharge.  
• be of pipe size equal to or greater than that of the relief valve outlet over the entire length of discharge  
line;  
• have no intervening shutoff valve between safety relief valve and discharge to atmosphere (do not plug or  
place any obstruction in discharge line.  
• terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing;  
• allow complete drainage of the valve and the discharge line;  
• be independently supported and securely anchored to avoid applied stress on the relief valve;  
• be as short and straight as possible;  
• terminate with plain end (not threaded);  
• be constructed of material suitable for exposure to temperatures of 375° F; or greater.  
Refer to local codes and appropriate ANSI/ASME Boiler and Pressure Vessel Code, Section IV, or Boiler,  
Pressure Vessel and Pressure Piping Code, CSA B51 for additional installation requirements.  
1. Refer to local codes and appropriate ASME Boiler  
and Pressure Vessel Code for additional installation  
requirements.  
Figure 2 - Safety Relief Valve Discharge Piping  
2. Install relief valve on 3/4” pipe nipple in tapped boiler  
opening.  
RELIEF VALVE  
A. Pipe discharge line following guidelines in preceding  
Warning. See Figure 2.  
DISCHARGE  
PIPING  
B. Discharge line pipe size shall be equal or greater  
than that of relief valve outlet over entire length  
of discharge line with no intervening shutoff valve  
between safety relief valve and discharge to  
atmosphere.  
C. Discharge line shall terminate with plain end to  
atmosphere where any discharge will be clearly  
visible and is at no risk of freezing.  
Check local codes  
for maximum  
distance from  
oor or other  
allowable safe  
point of discharge  
D. Discharge line shall be independently supported to  
avoid applied stress on relief valve.  
E. Installation shall allow complete drainage of relief  
valve and discharge line.  
3. Install Drain Valve on lower left side of boiler as  
marked.  
4. Install Temperature and Pressure Gauge into ¼”  
bushing threaded in tee furnished with supply piping.  
See Figures 3 and 4  
.
5. Connect Supply and Return Lines to boiler. Figure 3 &  
4. Connections may require certain additional ttings  
and parts.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION SYSTEM PIPING  
Figure 3 - Forced Hot Water Typical Piping  
Figure 4 - Forced Hot Water Typical Piping  
With Zone Control Valve  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION SYSTEM PIPING  
• Install radiation units (panels, radiators or cabinets) and  
supply and return mains rst then make connections at  
boiler.  
Low Design Water Temperature Systems (Below  
140°F) And Large Water Content Systems  
• Verify clean water supply is available when connecting  
cold water supply to water valve. Install sand strainer at  
pump when water supply is from well or pump.  
• Provide low water cutoff device when boiler is installed  
above radiation level or as required by the Authority  
having jurisdiction, either provide as part of boiler  
or at time of boiler installation. Periodic inspection  
is necessary, as is ushing of oat type devices, per  
manufacturers specic instructions.  
Condensation is corrosive and can eventually cause severe  
damage to boiler and venting system.  
• Minimum design return water temperature to prevent  
condensation in boiler and venting is 120°F. Minimum  
high limit setting is 140°F.  
• Boiler used in heating systems where design water  
temperatures below 140°F are desired (e.g. radiant oor  
heating), a 3-way or 4-way mixing valve or suitable  
alternative is required to prevent low temperature return  
water from entering boiler. When using mixing valve,  
follow manufacturer’s installation instructions.  
• Boiler used in connection with refrigeration systems shall  
be installed so chilled medium is piped in parallel with  
heating boiler with appropriate valves to prevent chilled  
• Boiler connected to system having large water content  
(such as former gravity system), suggest use of bypass  
medium from entering heating boiler. See Figure 5  
.
• Boiler connected to heating coils located in air handling  
units exposed to refrigerated air circulation, piping  
system shall be equipped with ow control valves or  
other automatic means to prevent gravity circulation of  
boiler water during cooling cycle.  
piping. See Figure 6  
.
Figure 5 - Piping Arrangements For Boiler When  
Used In Connection With Refrigeration  
System  
Figure 6 - Bypass Piping  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENT INSTALLATION  
11. Fasten sections of vent pipe with sheet metal screws to  
Check Your Chimney  
make piping rigid. Use stovepipe wires to support pipe  
from above.  
Chimney must be clean, right size, properly constructed  
and in GOOD CONDITION.  
12. Do not connect to replace ue.  
1. Installation must conform to requirements of the  
authority having jurisdiction or, in absence of such  
requirements, to the National Fuel Gas Code, ANSI  
Z223.1/NFPA 54 or of the Natural Gas and Propane  
Installation Code, CAN/CSA B149.1, or applicable  
provisions of the local building codes..  
13. Do not install damper on this boiler.  
Minimum Vent Pipe Clearance  
• Use Type B vent pipe through crawl space. Where vent  
pipe passes through combustible wall or partition, use  
ventilated metal thimble. Thimble should be 4 inches  
larger in diameter than vent pipe.  
• Boiler installed with single wall vent, must have 6”  
clearance between its surface and any combustible  
material. New Type B gas vent or exible liner must be  
installed in accordance with instructions furnished with  
vent. Maintain clearances as specied for vent pipe.  
• Verify vent pipe is re-stopped where it goes through  
oor or ceiling. It should have approved vent cap with  
clearances from roof. If clearances are less than shown  
in have vent checked by local authorities. See Figure 7,  
Page 11.  
• Vent connectors serving appliances vented by natural  
draft shall not be connected into any portion of  
mechanical draft systems operating under positive  
pressure.  
2. Boiler’s induced draft blower has 3” outlet. 3” X  
4” increaser tting is included in parts bag. Locate  
increaser tting on outlet of induced draft blower, and  
secure gas-tight with bead of furnished silicone sealant.  
Increaser tting is required on this boiler for Category I  
venting, and 4” is minimum permissible vent diameter.  
This does not imply vent connector is intended to be 4”  
diameter pipe. Vent connector shall be sized according  
to appropriate venting tables in the National Fuel  
Gas Code and may be required to be larger than 4”  
diameter.  
NOTICE  
Boiler installation for chimney venting is not complete  
unless increaser tting is located and secured.  
3. These are high efciency boilers with low stack or  
exhaust temperature.  
4. Venting into masonry chimney without liner, line  
chimney from top to bottom with either:  
A. Listed Type B vent pipe  
B. Listed exible vent liner  
C. Poured ceramic liner.  
5. Outside chimneys should not be used unless they are  
(choose one of the following):  
A. Enclosed in a chase  
B. Lined with Type B vent pipe  
C. Use listed exible vent liner  
D. Use certied chimney lining system  
6. Vent connector from boiler to chimney should run as  
directly as possible with as few elbows as possible.  
7. Where possible, it is recommended to common vent  
water heater and boiler. Consult appropriate Vent  
Sizing Tables in National Fuel Gas Code for specic  
requirements of multiple appliance venting.  
8. Boiler is only appliance connected to vent, Type B vent  
pipe is recommended for vent connector.  
9. Slope pipe up from boiler to chimney not less than 1/4”  
per foot (21mm/m).  
10. End of vent pipe must be ush with inside face of  
chimney ue. Use sealed-in thimble for chimney  
connection.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENT INSTALLATION  
Figure 7 - Type B Gas Vent  
CHECK YOUR CHIMNEY  
For boilers for connection to gas vents or  
chimneys, vent installations shall be in  
accordance with “Venting of Equipment, of the  
National Fuel Gas Code, ANSI Z223.1/NFPA 54,  
or of the Natural Gas and Propane Installation  
Code, CAN/CSA B149.1, or applicable provisions  
of the local building codes.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENT INSTALLATION  
Removing Existing Boiler From Common Venting  
System  
5. Test for spillage at the draft hood relief opening after 5  
minutes of main burner operation. Use ame of a match  
or candle, or smoke from a cigarette, cigar, or pipe.  
When an existing boiler is removed from a common  
venting system, the common venting system is likely to be  
too large for proper venting of the appliances remaining  
connected to it.  
6. After it has been determined that each appliance  
remaining connected to the common venting system  
properly vents when tested as outlined above, return  
doors, windows, exhaust fans, replace dampers and any  
other gas-burning appliance to their previous conditions  
of use.  
At the time of removal of an existing boiler, the following  
steps shall be followed with each appliance remaining  
connected to the common venting system placed in  
operation, while the other appliance remaining connected  
to the common venting system are not in operation.  
7. Any improper operation of the common venting system  
should be corrected so the installation conforms with  
the National Fuel gas Code, ANSI Z223.1/NFPA 54,  
and/or the Natural Gas and Propane Installation Code,  
CAN/CSA B149.1. When re-sizing any portion of the  
common venting system, the common venting system  
should be re-sized to approach the minimum size  
determined using the appropriate tables in Chapter 13  
of the National Fuel Gas Code, ANSI Z223.1/NFPA 54,  
and/or the Natural Gas and Propane Installation Code,  
CAN/CSA B149.1.  
1. Seal any unused openings in the common venting  
system.  
2. Visually inspect the venting system for proper size and  
horizontal pitch and determine there is no blockage or  
restriction, leakage, corrosion and other deciencies  
which could cause an unsafe condition.  
3. Insofar as is practical, close all building doors and  
windows and all doors between the space in which the  
appliances remaining connected to the common venting  
system are located and other spaces of the building.  
Turn on clothes dryers and any appliance not connected  
to the common venting system. Turn on any exhaust  
fans, such as range hoods and bathroom exhausts, so  
they will operate at maximum speed. Do not operate a  
summer exhaust fan. Close replace dampers.  
8. It is recommended that existing gas vents be checked  
to be sure they meet local codes.  
4. Place in operation the appliance being inspected. Follow  
the lighting instructions. Adjust thermostat so appliance  
will operate continuously.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL HORIZONTAL VENTING INSTRUCTION  
Horizontal venting with a power venter is an alternate  
Conrm that installing a power venter is an option allowed  
by local codes. Follow the specic power venter installation  
instructions issued with the power venter kits. Although  
the power venter is equipped with its own fan, the fan on  
the boiler remains in place and is unaltered when a power  
venter is used.  
method of sidewall venting. This boiler is CSA listed for  
sidewall venting with standard single wall galvanized or  
Type B vent pipe when using the following power venter  
kits, which were specically sized for these boilers:  
Table 4- Field Controls  
When sidewall venting, ue gases must be vented to a  
point in relation to the prevailing wind so that they may  
freely disperse without being blown back at the building  
causing discoloration, or into the building through doors or  
windows causing odors. Also, under certain conditions ue  
gases will condense, forming moisture. In such cases, steps  
should be taken to prevent building materials at the vent  
terminal from being damaged by the exhausted ue gas.  
Number Of  
Boiler Sections  
2, 3, 4, 5  
Field Controls  
Power Venter  
SWG-4D  
6, 7  
SWG-5D  
Some possible reasons for using a power venter for  
sidewall venting:  
When installing single wall galvanized vent pipe for power  
venting follow the specic power venter installation  
instructions for layout, location of the barometric draft  
control and termination connections.  
1. May be preferred by local codes.  
2. Need a vent piping run beyond 30’ (9.1m) (but not  
more than 50’ (15.2m)).  
3. The boiler installation site experiences gusting or high  
winds. A power venter can help prevent the boiler from  
short cycling due to gusting or high winds by providing  
vent exhaust pressures greater than the boiler’s  
induced draft blower alone.  
When joining and sealing the single wall galvanized or Type  
B vent piping, use RTV silicone sealant with a minimum  
temperature rating of 400°F. For 3” vent pipe runs, be-  
gin with the female end of the vent pipe over the boiler’s  
induced draft blower outlet. For 4” vent pipe runs begin  
with the galvanized 3” to 4” increaser tting (included in  
the boiler’s parts bag) over the induced draft blower outlet.  
Then follow by placing the female end of the 4” vent pipe  
over the increaser tting.  
4. When installers or homeowners prefer a negative  
pressure vent system instead of a positive pressure  
vent system.  
5. May be more cost effective than stainless steel  
venting, particularly at longer vent length.  
The Field Controls power vent kit includes either a  
SWG-II-4HD or SWG-II-5 power venter, a MG-1 4”  
When joining pieces of single wall galvanized vent pipe, a  
substantial bead of silicone should be used at the joint to  
insure a leak proof connection.  
barometric draft controller, and the CK-43D controls kit.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS SUPPLY PIPING  
Connecting Gas Piping  
!
CAUTION  
Gas line enters boiler from right side. Flexible gas  
connectors must never breach any boiler openings.  
WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance.  
• Use piping materials and joining methods acceptable  
to authority having jurisdiction. In absence of such  
requirements:  
• Do not touch any electrical switch; do not use  
any phone in your building.  
• USA - National Fuel gas Code, ANSI Z223.1/NFPA 54  
• Immediately call your gas supplier from a  
neighbor’s phone. Follow gas supplier’s  
instructions.  
• Canada - Natural Gas and Propane Installation Code,  
CAN/CSA B149.1  
• All pipe compound must be resistant to liqueed  
petroleum gas.  
• If you cannot reach your gas supplier, call the re  
department.  
• Install ground joint union in gas supply line between  
shut-off valve and boiler controls.  
• Install sediment trap upstream of gas controls.  
Figure 8 - Gas Piping At Boiler  
• Use two pipe wrenches when making connection to gas  
valve to keep it from turning.  
• Install manual shut-off valve in vertical pipe about 5 feet  
(1.5m) above oor. See Figure 8.  
• Tighten all joints securely.  
• Propane gas connections should only be made by  
licensed propane installer.  
• Two-stage regulation should be used by propane  
installer.  
• Propane gas piping should be check by propane installer.  
Check Gas Supply  
Gas pipe must be correct size for length of run and for  
total BTU per hour input of all gas utilization equipment  
connected to it. See Table 6 & 7, Page 15 for proper size.  
Be sure your gas line complies with local codes and gas  
company requirements.  
!
DANGER  
Fire Hazard. Do not use matches, candles, open  
ames, or other methods providing ignition source.  
Failure to comply will result in death or serious  
injury.  
Table 5 - Gas Pressures  
GAS  
PRESSURE  
NATURAL  
5" w.c.  
PROPANE  
11" w.c.  
MIN. SUPPLY  
MAX. SUPPLY  
MANIFOLD  
Check Gas Piping  
13.5" w.c.  
3.5" w.c.  
13.5" w.c.  
10" w.c.  
Pressure test boiler and gas connection before placing  
boiler in operation.  
• Pressure test over 1/2 psig (3.5 kPa). Disconnect  
boiler and its individual gas shutoff valve from gas  
supply system.  
Verify minimum pressure while boiler is operating.  
Verify maximum pressure when boiler is not operating  
• Pressure test at 1/2 psig (3.5 kPa) or less. Isolate  
boiler from gas supply system by closing manual gas  
shutoff valve. See Figure 8.  
• Locate leakage using gas detector, noncorrosive  
detection uid, or other leak detection method  
acceptable to authority having jurisdiction.  
• Correct leaks immediately and retest.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS SUPPLY PIPING  
Table 7- PROPANE GAS  
Table 6 - NATURAL GAS  
Pipe Capacity - BTU Per Hour Input  
Includes Fittings  
Pipe Capacity - BTU Per Hour Input  
Includes Fittings  
Length of  
Pipe - Ft.  
Length  
of  
Pipe - Ft.  
Copper Tubing*  
Iron Pipe  
½"  
¾"  
1"  
1¼"  
"  
¾"  
½"  
¾"  
20  
40  
92,000  
63,000  
190,000  
130,000  
350,000  
245,000  
625,000  
445,000  
20  
40  
60  
131,000  
90,000  
72,000  
216,000  
145,000  
121,000  
189,000  
129,000  
103,000  
393,000  
267,000  
217,000  
60  
50,000  
105,000  
195,000  
365,000  
*Outside diameter:  
Measure length of pipe or tubing from gas meter or propane  
second stage regulator.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL WIRING  
Electric Power Supply  
!
WARNING  
Run a separate 115 volt circuit from separate over current  
protective device 15 ampere circuit in electrical service  
entrance panel.  
Electrical shock hazard. Turn OFF electrical power  
supply at service panel before making electrical  
connections. Failure to do so could result in death  
or serious injury.  
Connect 115 volt power supply to terminals L1 (HOT) and  
L2 inside J box.  
Run 14 gauge or heavier copper wire from boiler to  
grounded connection in service panel or properly driven  
and electrically grounded ground rod.  
Electrical Wiring  
See wiring diagram Figure 10 page 18 for details.  
Refer to Ladder Diagram from document envelope  
received with boiler.  
Thermostat Installation  
Electrically bond boiler to ground in accordance with  
requirements of authority having jurisdiction. Refer to:  
1. Thermostat should be installed on an inside wall about  
four feet above the oor.  
• USA- National Electrical Code, ANSI/NFPA 70.  
• Canada - Canadian Electrical Code, Part I, CSA C22.1:  
Safety Standard for Electrical Installations.  
2. NEVER install a thermostat on an outside wall.  
3. Do not install a thermostat where it will be affected  
by drafts, hot or cold pipes, sunlight, lighting xtures,  
televisions, a replace, or a chimney.  
If any of the original wire as supplied with this appliance  
must be replaced, it must be replaced with type 105°C  
thermoplastic wire or its equivalent  
4. Check thermostat operation by raising and lowering  
thermostat setting as required to start and stop the  
burners.  
Circulator harness is factory wired to control module.  
Connect harness to circulator in eld. See Figure 9.  
5. Instructions for the nal adjustment of the thermostat  
are packaged with the thermostat (adjusting heating  
anticipator, calibration, etc.)  
6. Set heat anticipator at .2 amps. 24 volt thermostat  
connects to yellow low voltage wires labled T.  
Figure 9 - Control Module Panel  
J BOX  
L1 & L2  
BLOWER  
TRANSFORMER  
SECONDARY  
CI
RCULATOR  
HARNESS  
TRANSFORMER  
THERMOSTAT WIRES  
TRANSFORMER LINE VOLT  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SEQUENCE OF OPERATION  
Sequence of Operation - Figure 10, Page 18.  
1. Thermostat calls for heat, control relay contacts.  
2. Circulator pump is powered through terminals C1 and  
C2. Control holds off burner and attempts to satisfy  
thermostat with residual boiler heat.  
3. Induced draft blower and transformer primary are  
powered.  
4. When blower gets up to speed and blower suction  
pressure reaches pressure switch set point, pressure  
switch contacts close sending 24 volts to pilot control  
from transformer secondary.  
5. Pilot gas valve opens and spark initiates to light pilot  
burner.  
6. When pilot ame is proven, spark drops out.  
7. Main gas valve opens and pilot burner ignites main  
burners.  
8. If boiler water temperature reaches high limit set  
point, high limit contacts open, cutting power to  
blower and pilot control. Burners extinguish and blower  
stops. Circulator pump continues to run as long as  
the thermostat continues to call for heat. When boiler  
water temperature drops past the high limit set point  
and through the differential, high limit contacts close,  
repeating steps 3-7.  
9. If venting system becomes blocked, blower suction  
pressure will drop below pressure switch set point,  
opening pressure switch contacts and cutting power to  
pilot control. Burners will extinguish, but blower will  
remain powered as long as thermostat continues to call  
for heat. If venting system clears, steps 4-7 will repeat.  
10. Thermostat is satised, ending call for heat. Relay coil  
is de-energized, opening contacts. Burners extinguish.  
Blower and circulator pump stop.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING DIAGRAMS  
Figure 10 - Control Module  
Damper is not an option.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STARTING YOUR BOILER  
NOTICE  
Do not add water into hot empty boiler.  
Filling System With Water  
• Close air vents on all radiation units. Open valves to  
these units.  
• Verify boiler and expansion tank drain valves are closed.  
Air bleed screw on tank drain tting should be closed.  
• Open valve in line from boiler to expansion tank.  
• Open water inlet to your boiler and leave open.  
• Start with lowest radiation unit. Open air vent on this  
unit. When all air has escaped and water starts to ow  
from vent, close it.  
• Go to next radiation unit, and repeat this process.  
• Repeat until you have covered every radiation unit in  
system. End at highest unit in system.  
• If units have automatic vents, manual venting is  
unnecessary but it will speed up proper lling of system.  
• If system is closed expansion tank system, you may  
have automatic ll valve. Leave it open to rell system  
automatically as needed.  
• Check temperature-pressure gauge. Note position of  
hand indicating pressure. This should be between 10  
and 15 psi. Any lowering of this movable hand below  
10 psi indicates loss of water due to leakage. Automatic  
ll valve should compensate for this. Instructions are  
packaged with valve.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STARTING YOUR BOILER  
Operating Instructions.  
!
WARNING  
1. STOP! Read Safety Information on previous page.  
2. Set the thermostat to lowest setting.  
3. Turn off all electric power to the appliance.  
4. This appliance is equipped with an ignition device which  
automatically lights the burner. Do not attempt to light  
pilot by hand.  
If you do not follow these instructions  
exactly, a re or explosion may result  
causing property damage, personal injury  
or loss of life.  
• This appliance is equipped with an ignition device  
which automatically lights burner. Do NOT try to  
light this burner by hand.  
5. Remove burner access panel.  
Figure 11 - Gas Control Knob  
• Before operating smell all around appliance area  
for gas. Be sure to smell next to oor because  
some gas is heavier than air and will settle to the  
oor.  
Use only your hand to turn the gas shutoff  
valve. Never use tools. If valve will not turn by  
hand, do not try to repair it, call a qualied ser-  
vice technician. Force or attempted repair may  
result in re or explosion.  
ON  
INLET  
OFF  
GAS CONTROL KNOB  
Do not use this appliance if any part has  
been under water. Immediately call a qualied  
service technician to inspect appliance and to  
replace any part of control system and any gas  
control which has been under water.  
SHOWN IN "ON" POSITION  
6. Depress gas control knob slightly and turn clockwise  
to “OFF” position.  
7. Wait ve (5) minutes to clear out any gas. If you then  
smell gas STOP! Follow WHAT TO DO IF YOU SMELL  
GAS. If you don’t smell gas, go to next step.  
LIGHTING PROCEDURE FOR BOILER WITH  
INTERMITTENT PILOT SYSTEM  
8. Turn gas control knob counterclockwise  
9. Turn on all electric power to the appliance.  
10. Set thermostat to desired setting.  
to “ON.”  
For Your Safety, Read Before Operating!!  
A. This appliance is equipped with an ignition device  
which automatically lights the pilot. Do not try to light  
appliance by hand.  
11. After visually inspecting the ame, replace lower front  
panel.  
12. If appliance will not operate after several tries, turn gas  
control knob to “OFF” and call your service technician  
or gas supplier.  
!
CAUTION  
WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance.  
To Turn Off Gas To The Appliance  
• Do not touch any electrical switches; do not use  
any phone in your building.  
1. Set the thermostat to lowest setting.  
2. Turn off all electric power to the appliance if servicing is  
to be performed.  
• Immediately call your gas supplier from a  
neighbor’s phone. Follow the gas supplier’s  
instructions.  
3. Depress gas control knob slightly and turn clockwise  
to “OFF” position. Do not force.  
• If you cannot reach your gas supplier, call the re  
department.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHECKING AND ADJUSTING  
Figure 12 - Automatic Gas Valve  
Gas Valve Safety Shutdown Test  
!
WARNING  
Electrical shock hazard. Follow instructions to turn  
off electric power. Failure to do so could result in  
death or serious injury.  
Ignition system safety shutoff device must be tested after  
placing boiler in operation.  
With main burners ring, disconnect ignition cable from  
intermittent pilot control box. Gas valve should shut off  
main burners. TURN OFF ELECTRIC POWER to boiler before  
reconnecting ignition cable, to prevent electric shock.  
Adjust Pilot Burner  
1. Remove screw cover over pilot adjusting screw.  
2. Insert small screwdriver and adjust ame as needed  
See Figure 12 & 13. Turn screw counterclockwise  
to increase ame, clockwise to decrease.  
Figure 13 - Pilot Flame Adjustment  
Main Burner(S)  
Main burners do not require primary air adjustment and are  
not equipped with primary air shutters.  
Main burner ames form sharp blue inner cones in softer  
blue outer mantel, with no yellow. Puffs of air from blow-  
ing on ame or stamping on oor will cause ames to turn  
orange momentarily. This is not unusual. Remain still when  
observing main burner ames. See Figure 14, Page 22  
If ame appearance is not correct, check main burner  
orices, burner throat and ame ports for dust and lint  
.
obstruction. It may be necessary to remove rollout shield  
to observe main burner ames. Replace rollout shield after  
observation.  
Adjust Limit Controls  
Instructions for each control are included with the controls.  
Recommended Boiler Water Temperatures  
Settings can be changed after you have had some idea how  
the system works. Example: If your system does not give  
enough heat in very cold weather, you can raise limit setting  
to 190°F.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHECKING AND ADJUSTING  
Figure 14 - Main Burner Flame  
Adjust Thermostat Heat Anticipator  
Instruction for nal adjustment of thermostat are packaged  
with thermostat.  
1. Set Heat anticipator at .2.  
2. Check thermostat operation. When set above  
temperature indicated on thermometer, boiler burners  
should ignite. Verify thermostat turns off boiler when  
room temperature reaches selected setting and starts  
boiler operating when room temperature falls few  
degrees. After setting limit control to desired setting,  
check to see if it shuts off gas supply to burners.  
3. Turn your thermostat up to call for heat and let your  
boiler run until temperature of water reaches limit  
setting. Gas valve shuts off and circulator keeps  
running until thermostat is satised, or water cools  
enough to restart burners through limit control.  
Main burner ame should form sharp blue inner mantel  
with no yellow.  
4. To check operation of contacts in pressure switch,  
disconnect rubber tubing (located between blower and  
pressure switch) from pressure switch, while boiler  
is operating. Burners extinguish and blower keeps  
running. When tubing is reconnected to pressure  
switch, ignition sequence begins, resulting in ignition of  
main burners.  
5. Set thermostat for desired temperature.  
Safe lighting and other performance criteria were met with  
gas manifold and control assembly provided on boiler when  
boiler underwent tests specied in ANSI Z21.13.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTAINING YOUR BOILER  
Burners  
Cleaning Your Boiler And Burners  
Beginning of heating season visually check pilot and main Flue passages between sections should be examined yearly  
burner ames. See Figures 13, and 14  
.
and cleaned if necessary.  
To clean:  
Safety Relief Valve  
• Remove burners, pilot, and vent pipe.  
Test safety relief valve for proper operation. Refer to valve  
manufacturer’s instructions packaged with relief valve.  
• Remove top and front jacket panels.  
• Remove two screws attaching intermediate front panel  
to left and right side jacket panels.  
Expansion Tank (Non-diaphragm)  
• Remove control panel.  
Tank may become waterlogged, or may receive excess  
of air. Frequent automatic opening of safety relief  
valve indicates water logging. High boiler temperature  
accompanied by unusually low radiation unit temperature  
(and “knocking”) indicates excess air in tank.  
• Remove draft diverter and intermediate front panel.  
• Carefully remove cerafelt gasket strips.  
• Clean passageways between sections with exible  
handle wire brush. Remove dirt from bottom of boiler  
and from between sections by vacuuming.  
To correct:  
1. Close valve between boiler and tank. Drain tank until  
empty.  
• Verify all ame ports in burners are open and clear.  
Shake out or blow out all loose dirt in burners.  
2. Check all tank plugs and ttings. Tighten as necessary.  
• Reseal seams between adjacent sections as necessary  
with 400° F RTV silicone sealant.  
3. Open valve between boiler and tank. Water will rise to  
normal height in tank if you have automatic ll valve  
(otherwise, manually rell system).  
• Reassemble all parts.  
• Verify tightness of pilot connections and condition of  
burner ames after reassembly. See Figures 13 and 14.  
Boiler Flue Passages  
Recommend following checked annually by qualied service  
agent.  
• Verify vent pipe connections to chimney are secure and  
no obstructions are present.  
ue passages  
Blower  
• burner adjustment  
Blower motor features permanently lubricated ball bearing  
construction. Lubrication is not required.  
• operation of controls  
Before start of each season (or whenever system has been  
shut down for some time) recheck whole system for leaks  
and recheck boiler and vent pipe for leaks. Replace or patch  
any boiler seals that are faulty. Before start of each season  
(or whenever system has been shut down for some time)  
recheck the whole system for leaks . . . and recheck the  
boiler and vent pipe for leaks. Replace or patch any boiler  
seals that are faulty.  
Circulator Pump Isolation Valves  
Operate isolation valves in circulator pump anges  
manually once or twice per year to prevent valves from  
becoming stuck in open position  
Rotate valves from open position to closed position and  
back to open position.  
Low Water Cutoff(s)  
Vent Pipe  
Inspect eld sourced low water cutoffs annually or  
as recommended by low water cutoff manufacturer.  
Flush oat type low water cutoff(s) per manufacturer’s  
instructions.  
Venting and piping should be checked at least monthly. If  
vent piping shows any sign of leaking, replace immediately.  
Water System  
If system is to remain out of service during freezing  
weather, always drain it completely (water left in to freeze  
will crack pipes and/or boiler).  
Housekeeping  
• Keep boiler area clear and free from combustible  
materials, gasoline and other ammable vapors and  
liquids.  
• Keep boiler area clear of debris and other materials  
obstructing ow of combustion and ventilation air.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE HINTS  
You may avoid inconvenience and service calls by checking these points before you call for service:  
!
CAUTION  
WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance.  
• Do not touch any electrical switch; do not use  
any phone in your building.  
• Immediately call your gas supplier from a  
neighbor’s phone. Follow the gas supplier’s  
instructions.  
• If you cannot reach your gas supplier, call the re  
department.  
IF YOUR SYSTEM IS NOT HEATING OR NOT GIVING ENOUGH HEAT . . .  
POSSIBLE CAUSE  
WHAT TO DO  
Thermostat is not set correctly  
Reset thermostat  
Check ame. If it is yellow, the burner is not getting enough air. Or, if  
ame is blue and noisy and seems to lift off the burner, the burner is  
getting too much air. Contact your service agency.  
Burner is not operating properly  
Check over-current protection. Check to be sure electric power supply  
circuit is “ON.  
No electric power to boiler  
Controls out of adjustment  
Reset according to instructions.  
Open radiator vents to excess air. Check ow control valve (if used). It  
may be in closed position.  
Radiators not heating  
Circulating pump not running  
Poor electrical contact  
Check over-current protection. Check relay operation.  
Check all control terminals and wire joints.  
Pressure switch will not close and pilot spark will not operate to start  
pilot. Have your service technician check and correct, if necessary.  
Chimney ue is blocked  
Have your service technician check heat exchanger for blockage. Replace  
rollout switch with exact replacement.  
Rollout switch blown  
IF BURNER IS NOISY . . .  
WHAT TO DO  
POSSIBLE CAUSE  
Gas input amount is incorrect  
Contact your service technician.  
RELIEF VALVE LEAKING . . .  
POSSIBLE CAUSE  
WHAT TO DO  
Dirt on seat  
Open valve manually. Allow water to run and clear valve seat.  
Water logged expansion tank  
Drain tank, see manufacurer instructions.  
HAVE YOUR SERVICE AGENCY CHECK ANY PROBLEM YOU  
ARE UNABLE TO CORRECT.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EQUIPMENT & OPTIONAL ACCESSORIES  
AIR ELIMINATING FITTING (AIR PURGER)  
!
WARNING  
Air purger is used to remove excess air from system. It  
is installed in supply line. It will eliminate air from water  
before it reaches radiators and bleed off this air.  
Burn and scald hazard. Safety relief valve could  
discharge steam or hot water during operation.  
Install discharge piping per these instructions.  
MAIN AIR VENT FOR DOWN FLOW SYSTEMS OR  
DIAPHRAGM TYPE EXPANSION TANK  
SAFETY RELIEF VALVE  
Safety relief valve is required on your boiler. Water expands  
as it is heated. If there is no place for water to expand  
into, water pressure will build up inside boiler and system.  
Should this happen, safety relief valve will automatically  
open at predetermined pressure. This will relieve the strain  
on boiler and system. Run pipe from relief valve outlet  
(pipe must be same size as outlet and open end must not  
be threaded) to open drain, tub or sink, or other suitable  
drainage point not subject to freezing. Failure to do so may  
cause water damage or injury should safety relief valve  
release.  
Before system is lled with water, there is air in pipes and  
radiation units. Some of it will be trapped as system is  
lled . It is possible to eliminate most of this air through  
air vent on radiation units. Main air vent will speed and  
simplify this. Install on highest point in supply main when  
all radiation is below top of boiler.  
AUTOMATIC FILL VALVE  
For a safe, efcient operation, hot water system must be  
completely lled with water. Adding new water, when  
needed can be done manually (by use of hand valve in  
water supply line). Requires regular attention to system’s  
needs. Automatic ll valve accomplishes this without  
attention. Install in supply line on hot water boilers only.  
Valve operates through water pressure differentials. It does  
not require electrical connection.  
EXPANSION TANK  
Expanding water ows into expansion tank. Tank should  
be correct size. Tank is lled with air. As water expands it  
compresses air in the tank to form air pressure cushion.  
This “spring-like” cushion serves to maintain correct  
operating water pressure regardless of water temperature.  
This assures “full measure” of water, even in highest  
radiation unit of system. It also prevents blowing off of  
safety relief valve. Air in tank in beginning (with system  
lled with cold water) is sufcient for proper operation.  
Tank also serves as trap for excess air in system. Air  
would cause gurgling in pipes and in efcient circulation in  
radiators if left in system.  
DRAIN VALVE  
Manual valve provides means of draining all water from  
boiler and system. It is often installed in 3/4” tapping at  
bottom of end boiler section. Or it can be installed in tee  
where return line enters boiler.  
It is possible for tank to become “waterlogged” (lled  
with water). It can also become overlled with air. This  
can happen after lling system with new water. Fittings  
provided on tank and in line to tank are for bleeding off  
excess water or air.  
WATER TEMPERATURE CONTROL  
Water temperature limit control in relay is adjustable  
and may be set as necessary. It may be set as low as  
140°F, or as high as 220°F. This depends on type and  
amount of radiation involved and weather conditions.  
When installing this tank, it is important:  
1. Tank be higher than boiler top.  
CIRCULATING PUMP  
2. Pipe to tank continuously rises up to tank (so air  
Every forced hot-water system requires circulating pump.  
Separate pump or zone valve is required for each zone,  
if you have a two or more zone system. Pump must have  
capacity to provide circulation required by your system.  
Pump is connected into main just ahead of boiler. It is also  
wired to electrical system.  
can “bubble” up to it).  
DIAPHRAGM TYPE EXPANSION TANK  
Diaphragm type expansion tank takes place of conventional  
expansion tank. Carefully read instructions packed with  
your tank assembly.  
Tank comes with 10-12 pounds per square inch air charge.  
This is the same as pressure produced in system by  
automatic ll valve. When system is rst lled, tank will  
contain little or no water.  
As water is heated its pressure increases. It expands into  
tank, compressing air in tank. Compressed air cushion  
permits water in system to expand as temperature  
changes. Diaphragm type tank can be mounted on air  
purger tting or at any convenient place in supply or return  
line.  
BLOWER (Draft Inducer)  
Blower provides means for pulling air through boiler and  
exhausting ue gasses into vent system. Blower shuts  
off when burners are not ring. This keeps heat in house  
rather than having it go up chimney.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EQUIPMENT & OPTIONAL ACCESSORIES  
PRESSURE SWITCH  
Air pressure switch works on negative pressure. When  
blower comes on air pressure switch operates intermittent  
pilot and gas valve. Air pressure switch is factory set and  
will only work when blower operates properly. It will not  
allow boiler to come on if blower does not generate enough  
pressure or if venting system is blocked.  
Factory Pressure Switch Set point:  
-0.4” wc. for 2-5 section boilers.  
-0.5” w.c. for 6-7 section boilers.  
ROLLOUT SWITCH  
(FLAME ROLLOUT SAFETY SHUTOFF)  
Rollout switch is temperature-sensitive fuse link device.  
Located on boiler base just outside re box. In event of  
heat exchanger ueway blockage causing ame to roll  
out of re box, fuse does not change in appearance when  
blown.  
If rollout switch blows, it must be replaced with exact  
replacement. Check heat exchanger ueways for blockage  
when restoring system to operating condition. DO NOT  
operate system without rollout switch.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A - CONTROL MODULE  
A.1 Installation Environment Considerations A.3 Adjusting Settings  
To discourage unauthorized changing of settings, procedure  
to enter adjustment mode is required.  
!
WARNING  
If you do not follow these instructions  
exactly, a re or explosion may result  
causing property damage, personal injury  
or loss of life.  
To enter adjustment mode, press UP, DOWN, and I buttons  
(see Figure 1) simultaneously for three seconds. Press and  
release I button until parameter requiring adjustment is  
displayed:  
о “SP_” Setpoint (180 °F default setting; adjustable  
Do not use this appliance if any part has  
been under water. Immediately call a qualied  
service technician to inspect appliance and to  
replace any part of control system and any gas  
control which has been under water.  
between 130 and 220 °F)  
о “Df_” Setpoint Differential (15 °F default setting;  
adjustable between 10 and 30 °F)  
о “°F_” Degrees Fahrenheit  
• Do not allow water to drip on controls. Prevent  
condensation by allowing air circulation around  
module and gas control.  
Press UP or DOWN button until parameter has reached  
desired value. After 60 seconds without any button inputs,  
control automatically returns to READ mode.  
• Do not use corrosive chemicals around or on  
module or gas control.  
A.4 Display  
In RUN mode, status items and parameters are viewable.  
• Install plastic cover.  
Example, to display setpoint, control ashes “sp” (setpoint)  
followed by temperature (i.e., 135), followed by °F or °C.  
• Controls can be damaged by excessively high  
temperatures. Verify adequate air circulation around  
louvers is maintained when installing boiler.  
To read settings, press and release I key to nd parameter  
of interest.  
Example, press and release I until setpoint (sp) is  
displayed, followed by three-digit number, i.e., 190,  
followed by °F or °C. Press I button again will display (S1T)  
Sensor 1 Temperature followed by three-digit number and  
corresponding degree designator.  
A.2 Electrical Connections  
Connect Module Connectors Figure 10, Page 18  
• L1& L2 leads inside J box using wire nuts. Secure J  
box cover.  
See Display Readout.  
• Circulator harness to circulator. Harness comes  
plugged into module with Molex® plug.  
Figure 15 - Display Readout  
• Thermostat connection to yellow wires marked TT  
using wire nuts.  
• Ensure remaining Molex® plug connectors have not  
worked loose during transit.  
• Check sensing bulb is fully inserted in well and is not  
loose.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A - CONTROL MODULE  
2. Control determines burner operation is required,  
A.5 Operation  
Module continuously monitors boiler water temperature and  
res or shuts off burner based on this temperature data.  
module proceeds to start burner (see state codes list)  
and heats water in boiler until setpoint temperature is  
achieved or thermostat is satised. .  
1. When “Call for Heat” occurs, control enables circulator  
and monitors boiler water temperature to determine  
whether thermostat can be satised without ring  
burners.  
3. Burner is de-activated, ignition module completes heat-  
ing cycle, returns to idle and waits for temperature to  
drop again.  
4. Circulator is turned on throughout “Call for Heat.”  
Table 1 - Operation State Codes  
State  
Code  
Denition  
Explanation  
Number  
Idle  
Standby - no call for heat  
1
2
3
Heat request present. Boiler temperature sufciently high to run circulator pump  
only.  
Circulator  
Inducer is off. Control waits for pressure switch to open.  
Wait for pressure switch  
to open  
Checked at beginning of heat cycle before turning on inducer.  
If pressure switch does not open in 60 seconds, control goes to State 11.  
Inducer is turned on. Control waits for pressure switch to close.  
Checked at beginning of heat cycle after turning on inducer.  
If pressure switch does not close in 60 seconds, control goes to State 12  
System is purging before ignition trial; includes Pilot Valve circuit diagnostics.  
System sparking. Flame is not present  
Wait for pressure switch  
to close  
4
6
Pre-purge  
Spark  
Flame signal is being established. Variation in signal is allowed during this state,  
ame must be stable at end of period  
7
Flame stabilization  
8
9
Running  
System is running. Flame signal must be present.  
System is purging at end of call for heat  
Post-Purge  
Retry delay  
Recycle delay  
Successful ignition was not detected, and delay is called before retry.  
Flame signal was lost, and delay is called before retry  
10  
11  
12  
Wait for pressure switch  
to open - failed to close  
Inducer is still off. Pressure switch has not opened at beginning of heat cycle.  
Alarm is sent, but no lockout occurs  
Wait for pressure switch  
to close - failed to open  
Inducer is on. Pressure switch has not closed at beginning of heat cycle.  
Alarm message is sent but no lockout occurs.  
13  
14  
15  
Soft lock-out  
Soft lockout duration is one hour, may override with manual reset.  
Manual reset is required for hard lockout  
Hard lock-out  
Wait for limit to close  
Possible thermostat call for heat; limit switch is open.  
Flame signal sensed before trial for ignition. Appropriate alarm is sent.  
OR  
16  
17  
Flame out of sequence  
Flame signal sensed during post purge. Appropriate alarm is sent.  
OR  
Flame signal present when not expected. Appropriate alarm is sent.  
Pilot valve circuitry diagnostics during pre-purge.  
Pilot valve diagnostics  
Self check performed at start up, again at beginning of heat cycle, and during  
“Wait for Recovery “ State.  
Current leakage detection  
Self check performed at start up, again at beginning of heat cycle, and during  
“Wait for Recovery “ State  
Wait for recovery  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A - CONTROL MODULE  
A.6 Boiler High Limit Temperature Controller  
A.7 Troubleshooting  
• When water temperature reaches setpoint, controller  
ends heating cycle.  
• Following service procedures are provided as general  
guide.  
• When water temperature drops below setpoint minus  
differential, controller restarts heat cycle to re-heat  
boiler water.  
• On lockout and retry models, meter readings between  
gas control and ignition module must be taken within  
trial for ignition period. Once ignition module shuts  
off, lockout models must be reset through key buttons  
and display. On retry models, wait for retry or reset at  
thermostat.  
• If water temperature exceeds maximum allowed  
temperature (220°F or 104°C), controller enters manual  
reset lockout state.  
• Check for correct installation and wiring before replacing  
any component.  
• For models having reset capability, press any onboard  
button or cycle power to reset.  
• Control module cannot be repaired. If it malfunctions, it  
must be replaced.  
Figure 16 - Basic Control Algorithm Example  
• Use only qualied service agent to service ignition  
systems.  
1. Perform checkout as rst step in troubleshooting.  
2. Check troubleshooting guide to pinpoint cause of  
problem. See Table 2, page 30.  
3. If troubleshooting indicates ignition problem, see  
Ignition System Checks to isolate and correct the  
problem.  
4. Perform checkout procedure following troubleshooting  
guide again to verify system is operating normally.  
A.8 Troubleshooting Error Codes  
Integrated boiler control uses advanced diagnostic  
capability to assist in troubleshooting error conditions.  
Table 2 shows codes that could arise on integrated display  
during fault.  
Suggestions are provided in Table 8 for servicing these  
potential errors.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A - CONTROL MODULE  
Table 2 - Troubleshooting Error Codes  
Error  
Code  
Denition  
Consequence  
Number  
Pressure switch failed to open (stuck closed).  
2
4
Wait for recovery  
Non critical alarm  
Soft lockout  
Flame current too low. Check for ame.  
Flame sensed out of normal sequence (before opening or after closing gas valve).  
Gas valve relays welded. Five consecutive soft lockouts.  
Flame sensed during prepurge ( before gas valve signaled opened).  
Flame sensed during postpurge (after gas valve signaled closed).  
Pressure switch failed to close (Contacts stuck open)  
6
18  
23  
24  
29  
Hard lockout  
Soft lockout  
Soft lockout  
Wait for recovery  
Sensor 1 error. Temperature sensor in well is not reading correctly.  
Verify it is connected to board. Replace if necessary.  
32  
Wait for recovery  
Igniter ame rod shorted to burner ground  
57  
58  
59  
Wait for recovery  
Wait for recovery  
Wait for recovery  
Igniter ame rod shorted to burner ground. Repair or replace igniter.  
Line Voltage error - voltage out of specication high or low (15-37V (44-66Hz))  
Applies only to thermostats having on-board transformer.  
Polarity is wrong in this case.  
60  
Wait for recovery  
Thermostat input higher than threshold.  
Line voltage unstable - possibly too may heavy loads switching on and off causing  
erratic supply voltage.  
61  
62  
Wait for recovery  
Soft lockout  
Soft lockout: maximum number of retries exceeded.  
Soft lockout is reset after one hour if alarm reason disappears.  
Soft lockout: maximum number of recycles exceeded.  
63  
64  
Soft lockout  
Soft lockout  
Soft Lockout - electronics failure. On-board self diagnostics detected error.  
Over temperature error. Sensor measured temperature in excess of maximum  
allowable limit.  
65  
Soft lockout  
Note: Soft lockout time is 1 hour or manual reset. Hard lockout requires manual reset.  
STEP 2:  
A.9 Intermittent Pilot  
Verify ignition system grounding. Nuisance shutdowns are  
often caused poor or erratic grounding.  
Ignition System Checks  
Common ground is required for module and pilot burner/  
igniter sensor.  
STEP 1: Check ignition cable.  
• Verify ignition cable does not run in contact with metal  
surfaces.  
— Check for good metal-to-metal contact between  
pilot burner bracket and the main burner.  
• Verify only factory supplied Ignition cable (or approved  
replacement) is used.  
— Check ground lead from GND (BURNER) terminal  
on module to pilot burner. Verify connections are  
clean and tight. If wire is damaged or deteriorated,  
replace with No. 14-18 gauge, moisture-resistant,  
thermoplastic insulated wire with 105°C [221°F]  
minimum rating.  
• Verify connections to ignition module and igniter or  
igniter-sensor are clean and tight.  
• Verify ignition cable provides good electrical continuity.  
— Check ceramic ame rod insulator for cracks or  
evidence of exposure to extreme heat, which can  
permit leakage to ground. Replace pilot burner/igniter  
sensor and provide shield if necessary.  
— If ame rod or bracket is bent out of position, restore  
to correct position.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A - CONTROL MODULE  
STEP 3: Check spark ignition circuit.  
Disconnect ignition cable at SPARK terminal on module.  
• Recheck ignition sequence as follows.  
— Reconnect main valve wire.  
— Adjust thermostat above room temperature.  
— Verify ignition sequence at burner.  
!
WARNING  
Electrical shock hazard. Ignition circuit generates  
over 10,000 volts. Turn OFF electrical power  
supply at service panel before making electrical  
connections. Failure to do so could result in death  
or serious injury.  
— If spark does not stop after pilot lights, replace  
module.  
— If main burner does not light or if main burner lights  
and system locks out, check module, ground wire  
and gas control as described in troubleshooting Error  
Codes. See Table 2 page 30.  
Energize module and listen for audible sparking noise.  
When operating normally, there should be buzzing noise  
turns on and off twice per second for duration of 1–7  
seconds, depending on model.  
Figure 17 - Pilot Flame  
STEP 4: Verify pilot and main burner lightoff.  
• Initiate call for heat. Turn thermostat above room  
temperature. Ignition sequence may be delayed by  
thermal purge until boiler water temperature is below  
140°F (60°C)  
• Watch pilot burner during ignition sequence.  
— Verify ignition spark continues after pilot is lit.  
— Verify pilot lights and spark stops, verify main  
burner does not light.  
• If so, ensure adequate ame current as follows.  
Turn off boiler at circuit breaker or fuse box.  
— Clean ame rod with emery cloth.  
— Verify electrical connections are clean and tight.  
Replace damaged wire..  
— Check for cracked ceramic insulator, which can  
cause short to ground, and replace igniter-sensor if  
necessary.  
— At gas valve, disconnect main valve wire from MV  
terminal.  
Turn on power and set thermostat to call for heat. Pilot  
should light, main burner will remain off because main  
valve actuator is disconnected.  
— Check pilot ame. Verify it is blue, steady and  
envelops 3/8 to 1/2 in. [10 to 13 mm] of ame rod.  
Figure 17 for possible ame problems and causes.  
— If necessary, adjust pilot ame by turning pilot  
adjustment screw on gas control clockwise to decrease  
or counterclockwise to increase pilot ame. Following  
adjustment, always replace pilot adjustment cover  
screw and tighten rmly to assure proper gas control  
operation. Figure 12, Page 21.  
— Set temperature below room set-point to end call for  
heat.  
Correct Pilot Flame: 3/8 to 1/2 inch in ame.  
See Figure 13, Page 21.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT LITERATURE  
Lennox Industries Inc.  
Dallas, Texas  
Manufactured by:  
ECR International, Inc.  
2201 Dwyer Avenue, Utica NY 13501  
Download from Www.Somanuals.com. All Manuals Search And Download.  

LG Electronics Computer Monitor E1910S User Manual
Locke Lawn Mower MP 160 MP 148 MP 172 User Manual
Makita Cordless Sander 9227C User Manual
M Audio Computer Keyboard QS02 User Manual
Mazda Automobile 2007 B2300 Truck User Manual
McCulloch Lawn Mower 966485901 User Manual
Melissa Microwave Oven 753 097 User Manual
Melissa Vacuum Cleaner VC 340 User Manual
Metra Electronics Car Stereo System 95 7331 User Manual
Microsoft Computer Hardware 64 MHz 32 Bit Floating Point Central Processing Unity 1 Mbyte Memory State Logic User Manual