INSTALLATION
INSTRUCTIONS
E2011 Lennox Industries Inc.
Dallas, Texas, USA
Dave Lennox Signature®
Collection XP17 System
HEAT PUMPS
506586−01
06/11
Litho U.S.A.
Supersedes 05/11
TABLE OF CONTENTS
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Model Number Identification . . . . . . . . . . . . . . . . . . . .
Typical Unit Parts Arrangement . . . . . . . . . . . . . . . . .
Shipping and Packing List . . . . . . . . . . . . . . . . . . . . . .
Using Manifold Gauge Set . . . . . . . . . . . . . . . . . . . . . .
Operating Service Valves . . . . . . . . . . . . . . . . . . . . . . .
Recovering Refrigerant from Existing System . . . . .
Unit Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing and Installing Panels . . . . . . . . . . . . . . . . .
2
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
NOTICE TO INSTALLER
UNIT PLACEMENT
It is critical for proper unit operation to place outdoor unit on an
DEFROST OPERATION
It is critical for proper defrost operation to set the defrost termination
pins (E46) on the heat pump control prior to starting system. See
BRAZING LINE SET TO SERVICE VALVES
It is imperative to follow the brazing technique illustrated starting on
Heat Pump Control (A175) Jumpers and Terminals
Air Handler / Coil Matchups and Targeted Subcooling
NOTICE
A thermostat is not included and must be ordered
separately.
D The Lennox icomfort Touch® thermostat must be used
in communicating application
D In
non−icomfortt
applications,
the
Lennox
®
ComfortSense 7000 thermostat may be used, as well
as other non−communicating thermostats.
®
In all cases, setup is critical to ensure proper system
operation.
General
Field wiring examples for non−icomforttapplications
This outdoor unit is designed for use with HFC−410A
refrigerant only. This unit must be installed with an
approved indoor air handler or coil. See the Lennox XP17
Engineering Handbook for approved indoor component
matchups.
See the icomfort Touch® thermostat Quick Start Guide
for communicating and partial communicating field
wiring connections.
06/11
506586−01
Page 1
*2P0611*
*P506586-01*
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical Unit Parts Arrangement
SECOND GROUND LUG FOR SOURCESOURCEt
FAN MOTOR CONTROL (A177)
GROUND LUG
WIRE TIE
CONTACTOR−1POLE (K1−1)
HIGH VOLTAGE FIELD
CONNECTIONS
SLEEVE
OUTDOOR AMBIENT
TEMPERATURE
SENSOR (RT13)
CAPACITOR (C12)
HEAT PUMP
CONTROL (A175)
CONTROL BOX
COMPRESSOR
RT21 ꢀ MODELS
−024, − 030, −036
AND −042 (12
TUBES UP)
DISCHARGE
LINE
MUFFLER
REVERSING
VALVE
MODELS −048
AND −060
24 TUBES UP
TRUE
SUCTION
LINE
REVERSING
VALVE
SOLENOID (L1)
VAPOR VALVE
AND GAUGE
PORT
CHECK EXPANSION
VALVE
HR1 CRANKCASE
HEATER
TRUE SUCTION
LINE PORT
LIQUID VALVE AND
GAUGE PORT
CRANKCASE HEATER THERMOSTAT
(S40)
LIQUID LINE
BI−FLOW FILTER
DRIER
LOW PRESSURE
SWITCH (S87)
HIGH PRESSURE SWITCH
(S4)
Figure 1. Typical Parts Arrangement
Page 3
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
1 ꢀ Bushing (for low voltage wiring)
WARNING
2 ꢀ Isolation grommets for liquid and suction lines
Improper installation, adjustment, alteration, service or
maintenance can cause personal injury, loss of life, or
damage to property.
Using Manifold Gauge Set
When checking the system charge, only use a manifold
gauge set that features low−loss anti−blow back fittings.
Installation and service must be performed by a licensed
professional installer (or equivalent) or a service agency.
IMPORTANT
To prevent stripping of the various caps used, the
appropriately sized wrench should be used and fitted
snugly over the cap before tightening.
CAUTION
Physical contact with metal edges and corners while
applying excessive force or rapid motion can result in
personal injury. Be aware of, and use caution when
working near these areas during installation or while
servicing this equipment.
Manifold gauge set used with HFC−410A refrigerant
systems must be capable of handling higher system
operating pressures. The gauges should be rated for use
with pressures of 0 − 800 psig on the high side and a low
side of 30" vacuum to 250 psig with dampened speed to
500 psi. Gauge hoses must be rated for use at or up to 800
psig of pressure with a 4000 psig burst rating.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of
refrigerant (CFCs, HCFCs AND HFCs) as of July 1,
1992. Approved methods of recovery, recycling or
reclaiming must be followed. Fines and/or incarceration
may be levied for noncompliance.
Table 1. Torque Requirements
Parts
Recommended Torque
Service valve cap
Sheet metal screws
Machine screws #10
Compressor bolts
Gauge port seal cap
8 ft.− lb.
11 NM
16 in.− lb.
28 in.− lb.
90 in.− lb.
8 ft.− lb.
2 NM
3 NM
WARNING
Electric Shock Hazard. Can cause injury
or death. Unit must be grounded in
accordance with national and local
codes.
10 NM
11 NM
Operating Service Valves
The liquid and vapor line service valves are used for
removing refrigerant, flushing, leak testing, evacuating,
verifying charge and charging.
Line voltage is present at all components
when unit is not in operation on units with
single-pole contactors. Disconnect all
remote electric power supplies before
opening access panel. Unit may have
multiple power supplies.
Each valve is equipped with a service port which has a
on how to access and operating both angle and ball service
valves.
IMPORTANT
This model is designed for use in check expansion valve
systems only. An indoor expansion valve approved for
use with HFC−410A refrigerant must be ordered
separately, and installed prior to operating the system.
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc −
Rockwell Harness Scale minimum). Fully insert the
wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for
small valves, to 25 ft−lbs for large valves) to prevent
refrigerant loss during shipping and handling. Using an
Allen wrench rated at less than 50Rc risks rounding or
breaking off the wrench, or stripping the valve stem
recess.
Shipping and Packing List
Check unit for shipping damage. Consult last carrier
immediately if damage is found.
1 ꢀ Assembled outdoor unit.
See the Lennox Service and Application Notes #C−08−1
for further details and information.
1 ꢀ Bag assembly which includes the following:
Page 4
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
ANGLE AND BALL
SERVICE VALVES
Operating Angle Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back
the stem out counterclockwise as far as it will go.
SERVICE PORT CAP
SERVICE PORT CORE
(VALVE STEM SHOWN
CLOSED) INSERT HEX
WRENCH HERE
(VALVE STEM SHOWN OPEN)
INSERT HEX WRENCH HERE
TO INDOOR
UNIT
STEM CAP
TO OUTDOOR UNIT
ANGLE−TYPE SERVICE VALVE
(FRONT−SEATED CLOSED)
ANGLE−TYPE SERVICE VALVE
(BACK−SEATED OPENED)
When service valve is OPEN, the service port is
open to linE set, indoor and outdoor unit.
WHEN SERVICE VALVE IS CLOSED, THE SERVICE PORT IS OPEN
TO THE LINE SET AND INDOOR UNIT.
To Access Service Port:
Operating Ball Type Service Valve:
A service port cap protects the service port core from contamination and
serves as the primary leak seal.
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve,
rotate stem counterclockwise 90°. To close, rotate stem
clockwise 90°.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as
follows:
TO INDOOR UNIT
1/6 TURN
S
S
With torque wrench: Finger tighten and
12
6
1
5
11
10
Without torque wrench: Finger tighten and
use an appropriately sized wrench to turn
an additional 1/6 turn clockwise.
2
TO OPEN ROTATE STEM
COUNTERCLOCKWISE 90°.
9
3
BALL (SHOWN
CLOSED)
4
8
7
VALVE
TO CLOSE ROTATE STEM
STEM
Reinstall Stem Cap:
CLOCKWISE 90°.
Stem cap protects the valve stem from damage and serves as the
primary seal. Replace the stem cap and tighten as follows:
1/12 TURN
SERVICE PORT
S
S
With Torque Wrench: Finger tighten and then
SERVICE PORT
CORE
12
1
5
11
10
SERVICE PORT
CAP
Without Torque Wrench: Finger tighten and use
an appropriately sized wrench to turn an addi-
tional 1/12 turn clockwise.
2
9
3
4
STEM CAP
8
TO OUTDOOR
UNIT
7
6
NOTE ꢀ A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Figure 2. Angle and Ball Service Valves
Page 5
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
Recovering Refrigerant from Existing System
CONNECT MANIFOLD GAUGE SET
DISCONNECT POWER
Disconnect all power to the existing outdoor unit at the disconnect
Connect a gauge set, clean recovery cylinder and a recovery
machine to the service ports of the existing unit. Use the
instruction provided with the recovery machine to make the
connections.
2
1
switch or main fuse box/breaker panel.
SERVICE DISCONNECT
SWITCH
MANIFOLD GAUGES
RECOVERY MACHINE
LOW
HIGH
RECOVERING REFRIGERANT
Remove existing HCFC−22 refrigerant using one of the following methods
below:
OUTDOOR UNIT
CLEAN RECOVERY
CYLINDER
3
IMPORTANT ꢀ Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes, and/or
long line sets.
METHOD 1:
Us this method if the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational and you plan to use the existing
HCFC−22 to flush the system.
Remove all HCFC−22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of
refrigerant.
METHOD 2:
Use this method if the existing outdoor unit is equipped with manual shut−off valves, and you plan to use new HCFC−22 refrigerant to flush the
system.
The following devices could prevent full system charge recovery into the outdoor unit:
S
S
S
Outdoor unit’s high or low−pressure switches (if applicable) when tripped can cycle the compressor OFF.
Compressor can stop pumping due to tripped internal pressure relief valve.
Compressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets
a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum.
Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and
internal seals.)
Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the vapor valve. Turn OFF the
main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
Perform the following task:
A
B
Start the existing HCFC−22 system in the cooling mode and close the liquid line valve.
Use the compressor to pump as much of the existing HCFC−22 refrigerant into the outdoor unit until the outdoor system is full (high pressure
switch will trip and shut the compressor off). Turn the outdoor unit main power OFF and use a recovery machine to remove the remaining refriger-
ant from the system.
NOTE ꢀ It may be necessary to bypass the low pressure switch (if equipped) to ensure complete refrigerant evacuation.
C
D
When the low side system pressures reach 0 psig, close the vapor line valve.
Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
Figure 3. Refrigerant Recovery Procedure
Page 6
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
MINIMUM CLEARANCE
ABOVE UNIT
CLEARANCE ON ALL SIDES ꢀ INCHES (MILLIMETERS)
6 (152)
ACCESS PANEL
NOTES:
48 (1219)
S
S
CLEARANCE TO ONE OF THE
30 (762)
OTHER THREE SIDES MUST BE 36
INCHES (914MM).
12 (305)
CLEARANCE TO ONE OF THE
REMAINING TWO SIDES MAY BE 12
INCHES (305MM) AND THE FINAL
SIDE MAY BE 6 INCHES (152MM).
LINE SET
CONNECTIONS
36 (914)
MINIMUM CLEARANCE BETWEEN
TWO UNITS
ACCESS PANEL
24 (610)
LINE SET
CONNECTIONS
REAR VIEW OF UNIT
Figure 4. Installation Clearances
PLACING UNIT ON SLAB
Unit Placement
When installing unit at grade level, the top of the slab
should be high enough above grade so that water from
higher ground will not collect around the unit. The slab
should have a slope tolerance as described in figure 5,
detail B.
CAUTION
In order to avoid injury, take proper precaution when lift-
ing heavy objects.
NOTE ꢀ If necessary for stability, anchor unit to slab as
ELEVATING THE UNIT
See Unit Dimensions on page 3 for sizing mounting slab,
installation clearance requirements.
Units are outfitted with elongated support feet as illustrated
If additional elevation is necessary, raise the unit by
extending the height of the unit support feet. This may be
achieved by using a 2 inch (50.8mm) Schedule 40 female
threaded adapter.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
S
Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent
property, not from the installation property. Install the
unit as far as possible from the property line.
The specified coupling will fit snuggly into the recessed
portion of the feet. Use additional 2−inch (50.8mm)
Schedule 40 male threaded adaptors which can be
threaded into the female threaded adaptors to make
additional adjustments to the level of the unit.
S
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound
transmission. For proper placement of unit in relation
to a window see the provided illustration in figure 5,
detail A.
NOTE ꢀ Keep the height of extenders short enough to
ensure a sturdy installation. If it is necessary to extend
further, consider a different type of field−fabricated
framework that is sturdy enough for greater heights.
Page 7
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
ꢀ Outside Unit Placement
DETAIL A
Install unit away from windows.
ꢀ Slab Mounting at Ground Level
DETAIL B
Install unit level or, if on a slope, maintain slope tolerance of two (2)
degrees (or two inches per five feet [50 mm per 1.5 m]) away from
building structure.
BUILDING
STRUCTURE
MOUNTING
SLAB
GROUND LEVEL
TWO 90° ELBOWS INSTALLED IN LINE SET WILL
REDUCE LINE SET VIBRATION.
STABILIZING UNIT ON UNEVEN SURFACES
DETAIL Cꢀ Elevated Slab Mounting
using Feet Extenders
ꢀ Slab Side Mounting
DETAIL D
#10 1/2" LONG SELF−DRILLING
SHEET METAL SCREWS
COIL
STABILIZING BRACKET (18 GAUGE
METAL ꢀ 2" WIDTH; HEIGHT AS
REQUIRED)
BASE PAN
#10 1−1/4" LONG HEX HD SCREW
AND FLAT WASHER
CORNER POST
Concrete slab ꢀ use two plastic anchors (hole
drill 1/4")
BASE
Wood or plastic slab ꢀ no plastic anchor (hole
drill 1/8")
DETAIL E ꢀ Deck Top Mounting
Stabilizingbracket (18 gauge metal ꢀ 2" (50.8mm) width; height as required); bend to form
right angle as exampled below.
LEG DETAIL
MINIMUM ONE
PER SIDE
2" (50.8MM) SCH 40
FEMALE THREADED
ADAPTER
2" (50.8MM) SCH 40
MALE THREADED
ADAPTER
SAME FASTENERS AS
FOR EXTRA
SLAB SIDE MOUNTING.
STABILITY
Use additional 2" SCH 40 male threaded adapters
which can be threaded into the female threaded
adapters to make additional adjustments to the level of
the unit.
One bracket per side (minimum). For extra stability, two brackets per side, two inches
(51mm) from each corner.
IMPORTANT ꢀ To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors
commonly available in the marketplace.
Figure 5. Placement, Slab Mounting and Stabilizing Unit
Page 8
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
STABILIZING UNIT ON UNEVEN SURFACES
IMPORTANT
Unit Stabilizer Bracket Use (field−provided):
NOTICE
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roofing material may absorbed oil and cause the
rubber to swell when it comes into contact with oil. The
rubber will then bubble and could cause leaks. Protect
the roof surface to avoid exposure to refrigerant and oil
during service and installation. Failure to follow this
notice could result in damage to roof surface.
Always use stabilizers when unit is raised above the
factory height. (Elevated units could become unstable in
gusty wind conditions).
Stabilizers may be used on factory height units when
mounted on unstable an uneven surface.
1. Remove two side louvered panels to expose the unit
base.
Removing and Installing Panels
using conventional practices.
IMPORTANT
Do not allow panels to hang on unit by top tab. Tab is for
alignment and not designed to support weight of panel.
3. Replace the panels after installation is complete.
ROOF MOUNTING
Install the unit a minimum of six inches (152 mm) above the
roof surface to avoid ice build−up around the unit. Locate
the unit above a load bearing wall or area of the roof that
can adequately support the unit. Consult local codes for
rooftop applications.
IMPORTANT
To help stabilize an outdoor unit, some installations may
require strapping the unit to the pad using brackets and
anchors commonly available in the marketplace.
If unit coil cannot be mounted away from prevailing winter
winds, a wind barrier should be constructed. Size barrier at
least the same height and width as outdoor unit. Mount
barrier 24 inches (610 mm) from the sides of the unit in the
direction of prevailing winds.
WARNING
To prevent personal injury, or damage to panels, unit or
structure, be sure to observe the following:
PREVAILING WINTER
WINDS
While installing or servicing this unit, carefully stow all
removed panels out of the way, so that the panels will not
cause injury to personnel, nor cause damage to objects
or structures nearby, nor will the panels be subjected to
damage (e.g., being bent or scratched).
WIND BARRIER
INLET AIR
24"
(610)
While handling or stowing the panels, consider any
weather conditions, especially windy conditions, that
may cause panels to be blown around and battered.
INLET AIR
INLET AIR
Figure 6. Rooftop Application and Wind Barrier ꢀ
Inches (millimeters)
Page 9
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
REMOVING AND INSTALLING
PANELS
Panel shown slightly rotated to allow top tab to exit (or enter) top slot for removing (or
installing)panel.
WARNING
REMOVE 4 SCREWS TO
REMOVE PANEL FOR
ACCESSING COMPRESSOR
AND CONTROLS.
LOUVERED PANEL REMOVAL
Remove the louvered panels as follows:
1. Remove two screws, allowing the panel to swing open slightly.
2. Hold the panel firmly throughout this procedure Rotate bottom corner of panel away
from hinged corner post until lower three tabs clear the slots as illustrated in detail
B.
Position panel with holes aligned;
install screws and tighten.
3. Move panel down until lip of upper tab clears the top slot in corner post as illustrated
in detail A.
Detail A
LOUVERED PANEL INSTALLATION
Position the panel almost parallel with the unit as illustrated in detail Dwith the screw side
as close to the unit as possible. Then, in a continuous motion:
LIP
1. Slightly rotate and guide the lip of top tab inward as illustrated in detail A and C; then
upward into the top slot of the hinge corner post.
2. Rotate panel to vertical to fully engage all tabs.
3. Holdingthe panel’s hinged side firmly in place, close the right−hand side of the panel,
aligningthe screw holes.
4. When panel is correctly positioned and aligned, insert the screws and tighten.
SCREW
HOLES
Detail C
Maintain minimum panel angle (as close
to parallel with the unit as possible)
while installing panel.
Detail B
Detail D
HOLD DOOR FIRMLY ALONG
THE HINGED SIDE TO MAINTAIN
FULLY−ENGAGED TABS
ANGLE MAY BE TOO EXTREME
ROTATE IN THIS DIRECTION; THEN
DOWN TO REMOVE PANEL
PREFERRED ANGLE FOR INSTALLATION
Figure 7. Removing and Installing Panels
Page 10
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2. Refrigerant Line Set ꢀ Inches (mm)
New or Replacement Line Set
L15
Line Sets
Feet (Meters)
Liquid
Line
Vapor
Line
Model
REFRIGERANT LINE SET
−024 and
−030
L15 line set sizes are depen-
dent on unit match up. See
XP17 Engineering Handbook to
determine correct line set sizes.
3/8" (10) 3/4" (19)
3/8" (10) 7/8" (22)
This section provides information on installation or
replacement of existing line set. If new or replacement line
set is not being installed then proceed to Brazing
−036, −042
and −048
1−1/8"
3/8" (10)
−060
Field Fabricated
(29)
IMPORTANT
NOTE ꢀ Some applications may required a field provided 7/8" to
1−1/8" adapter
Lennox highly recommends changing line set when
converting the existing system from HCFC−22 to
HFC−410A. If that is not possible and the line set is the
proper size as reference in Table 2, use the procedure
outlined under Flushing the System on page 13.
NOTE ꢀ When installing refrigerant lines longer than 50
feet, see the Lennox Refrigerant Piping Design and
Fabrication Guidelines, or contact Lennox Technical
Support Product Applications for assistance. :
To obtain the correct information from Lennox, be sure to
communicate the following information:
If refrigerant lines are routed through a wall, then seal and
isolate the opening so vibration is not transmitted to the
building. Pay close attention to line set isolation during
installation of any HVAC system. When properly isolated
from building structures (walls, ceilings. floors), the
refrigerant lines will not create unnecessary vibration and
subsequent sounds. See figure 8 for recommended
installation practices. Also, consider the following when
placing and installing a high−efficiency outdoor unit.
S
S
Model (XP17) and size of unit (e.g. −036).
Line set diameters for the unit being installed as listed
S
Number of elbows vertical rise or drop in the piping.
The compressor is charged with sufficient Polyol ester oil
for line set lengths up to 50 feet. Recommend adding oil to
system based on the amount of refrigerant charge in the
system. No need to add oil in system with 20 pounds of
refrigerant or less. For systems over 20 pounds − add one
ounce of every five pounds of refrigerant.
Recommended topping−off POE oils are Mobil EAL
ARCTIC 22 CC or ICI EMKARATEt RL32CF.
IMPORTANT
Refrigerant lines must not contact structure.
WARNING
Polyol Ester (POE) oils used with HFC−410A
refrigerant absorb moisture very quickly. It is very
important that the refrigerant system be kept closed
as much as possible. DO NOT remove line set caps
or service valve stub caps until you are ready to make
connections.
Liquid lines that meter the refrigerant, such as RFC1 liquid
lines, must not be used in this application. Existing line set
was previously charged with HCFC−22 refrigerant, then
existing line set must be flushed (see Flushing the System
Field refrigerant piping consists of liquid and vapor lines
from the outdoor unit to the indoor unit coil (braze
connections). Use Lennox L15 (sweat, non−flare) series
line set, or field−fabricated refrigerant line sizes as listed in
table 2.
IMPORTANT
Mineral oils are not compatible with HFC−410A. If oil
must be added, it must be a Polyol ester oil.
Page 11
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
Line Set Isolation ꢀ The following illustrations are examples of proper refrigerant line set isolation:
REFRIGERANT LINE SET ꢀ INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
REFRIGERANT LINE SET ꢀ TRANSITION
FROM VERTICAL TO HORIZONTAL
NOTE ꢀ Insulate liquid line when it is routed through areas where the
surrounding ambient temperature could become higher than the
temperatureof the liquid line or when pressure drop is equal to or greater
than 20 psig.
ANCHORED HEAVY NYLON
WIRE TIE OR AUTOMOTIVE
AUTOMOTIVE
MUFFLER-TYPE HANGER
MUFFLER-TYPE HANGER
OUTSIDE WALL
LIQUID LINE
VAPOR LINE
WALL
STUD
WIRE TIE
INSIDE WALL
STRAP
WOOD BLOCK
BETWEEN STUDS
STRAP LIQUID LINE TO
VAPOR LINE
NON−CORROSIVE
METAL SLEEVE
WIRE TIE
LIQUID LINE
NON−CORROSIVE
METAL SLEEVE
WOOD BLOCK
WIRE TIE
VAPOR LINE − WRAPPED
IN ARMAFLEX
STRAP
REFRIGERANT LINE SET ꢀ INSTALLING
HORIZONTAL RUNS
SLEEVE
To hang line set from joist or rafter, use either metal strapping material
or anchored heavy nylon wire ties.
WIRE TIE (AROUND
VAPOR LINE ONLY)
VAPOR LINE WRAPPED
WITH ARMAFLEX
8 FEET (2.43 METERS)
OUTSIDE
WALL
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
FLOOR JOIST OR
LIQUID
LINE
ROOF RAFTER
TAPE OR
WIRE TIE
8 FEET (2.43 METERS)
PVC
PIPE
CAULK
NON−CORROSIVE
METAL SLEEVE
FIBERGLASS
INSULATION
STRAP THE VAPOR LINE TO THE JOIST
OR RAFTER AT 8 FEET (2.43 METERS)
INTERVALS THEN STRAP THE LIQUID
LINE TO THE VAPOR LINE.
TAPE OR
WIRE TIE
NOTE ꢀ Similar installation practices should be used if line set is
to be installed on exterior of outside wall.
FLOOR JOIST OR
ROOF RAFTER
Figure 8. Line Set Installation
Page 12
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
Brazing Connections
IMPORTANT
Connect gauge set low pressure side to vapor line
service valve and repeat procedure starting at
paragraph 4 for brazing the liquid line to service port
valve.
line set connections to service valves.
WARNING
Danger of fire. Bleeding the refrigerant
charge from only the high side may result
in pressurization of the low side shell and
suction tubing. Application of a brazing
torch to a pressurized system may result
in ignition of the refrigerant and oil
mixture − Check the high and low
pressures before applying heat.
IMPORTANT
Allow braze joint to cool before removing the wet rag
from the service valve. Temperatures above 250ºF can
damage valve seals.
IMPORTANT
Use silver alloy brazing rods with 5% minimum silver
alloy for copper−to−copper brazing. Use 45% minimum
alloy for copper−to−brass and copper−to−steel brazing.
WARNING
When using a high pressure gas such as
dry nitrogen to pressurize a refrigeration
or air conditioning system, use a
regulator that can control the pressure
down to 1 or 2 psig (6.9 to 13.8 kPa).
WARNING
Fire, Explosion and Personal Safety
Hazard.
CAUTION
Brazing alloys and flux contain materials which are
hazardous to your health.
Failure to follow this warning could
result in damage, personal injury or
death.
Avoid breathing vapors or fumes from brazing
operations. Perform operations only in well−ventilated
areas.
Never use oxygen to pressurize or
purge refrigeration lines. Oxygen,
when exposed to a spark or open
flame, can cause fire and/or an ex-
plosion, that could result in property
damage, personal injury or death.
Wear gloves and protective goggles or face shield to
protect against burns.
Wash hands with soap and water after handling brazing
alloys and flux.
Page 13
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
CAP AND CORE REMOVAL
PIPING PANEL REMOVAL AND PREPARING LINE
SET
Remove service cap and core from both the suction / vapor and
liquid line service ports.
2
1
Remove piping panel for easier access to service valves. Cut ends
of the refrigerant lines square (free from nicks or dents) and debur
the ends. The pipe must remain round. Do not crimp end of the line.
SERVICE PORT CAP
SERVICE PORT
CORE
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
SERVICE VALVE
CONNECTION
COPPER TUBE
STUB
REDUCER
LIQUID LINE SERVICE VALVE
LINE SET SIZE IS SMALLER
THAN CONNECTION
REFRIGERANT LINE
SERVICE PORT
CORE
SERVICE
PORT CAP
SUCTION / VAPOR LINE
SERVICE VALVE
DO NOT CRIMP SERVICE VALVE
CONNECTOR WHEN PIPE IS
SMALLER THAN CONNECTION
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING
LIQUID AND SUCTION / VAPOR LINE SERVICE VALVES
3
A
B
C
Connect gauge set low pressure side to liquid line
service valve (service port).
Connect gauge set center port to bottle of nitrogen with
regulator.
LOW
HIGH
With valve core removed from the suction / vapor line
service port, nitrogen flow will have an exit point.
ATTACH
GAUGES
SUCTION / VAPOR SERVICE PORT MUST BE
OPEN AND SERVICE PORT CORE REMOVED
TO ALLOW EXIT POINT FOR NITROGEN FLOW
B
SUCTION /
VAPOR LINE
SERVICE
VALVE
C
SUCTION / VAPOR
LINE
OUTDOOR
UNIT
INDOOR
UNIT
NITROGEN
LIQUID LINE SERVICE
VALVE
LIQUID LINE
A
Figure 9. Brazing Procedures
Page 14
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water saturated cloths around service valve bodies and copper tube stubs. Use
4additionalwater saturated cloths underneath the valve body to protect the base paint.
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration
FLOW NITROGEN
WARNING
5
1. FIRE, PERSONAL INJURY, OR PROPERTY
DAMAGE will result if you do not wrap a water
saturated cloth around both liquid and suction line
service valve bodies and copper tube stub while
brazing in the line set! The braze, when complete,
must be quenched with water to absorb any residual
heat.
gauge set into the valve stem port connection on the liquid service
valve and out of the suction / vapor valve stem port. See steps 3A, 3B
and 3C on previous page and below for manifold gauge setup.
BRAZE LINE SET
Water saturated cloths must remain water saturated throughout
the brazing and cool−down process.
6
2. Do not open service valves until refrigerant lines and
indoor coil have been leak−tested and evacuated.
Refer to procedures provided in this supplement.
A
B
Braze liquid line to liquid line service valve.
Braze suction / vapor line to suction / vapor service
valve.
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME AWAY
FROM SERVICE VALVE.
6B
SUCTION / VAPOR LINE
SUCTION / VAPOR SERVICE PORT
MUST BE OPEN AND SERVICE PORT
CORE REMOVED TO ALLOW EXIT
POINT FOR NITROGEN FLOW
WATER SATURATED CLOTHS
IMPORTANT ꢀ Allow braze joint to cool. Apply
additional water saturated cloths to help cool
brazed joints. Do not remove water saturated
cloths until piping has cooled. Temperatures
above 250ºF will damage valve seals.
6A
LIQUID LINE
WATER SATURATED
CLOTHS
PREPARATION FOR NEXT STEP
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water saturated cloths to both services
valves to cool piping. Once piping is cool, remove all water saturated cloths. Refer to the unit installation instructions for the next step in preparing
the unit.
7
Figure 10. Brazing Procedures (Continued)
Page 15
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
Flushing Line Set and Indoor Coil
TYPICAL EXISTING FIXED ORIFICE
REMOVAL PROCEDURE (UNCASED
COIL SHOWN)
TYPICAL EXISTING EXPANSION VALVE REMOVAL
PROCEDURE (UNCASED COIL SHOWN)
OR
1B
1A
STUB END
TWO PIECE PATCH PLATE
(UNCASED COIL ONLY)
LIQUID LINE
ORIFICE
HOUSING
CHECK
EXPANSION
VALVE
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
DISTRIBUTOR
TUBES
®
TEFLON
RING
®
TEFLON RING
FIXED ORIFICE
BRASS NUT
®
TEFLON
RING
SENSING
LINE
DISTRIBUTOR
ASSEMBLY
DISTRIBUTOR
ASSEMBLY
EQUALIZER
LINE
REMOVE AND DISCARD
®
WHITE TEFLON SEAL
(IF PRESENT)
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
A
B
On fully cased coils, remove the coil access and plumbing panels.
Remove any shipping clamps holding the liquid line and distributor as-
sembly.
MALE EQUALIZER
LINE FITTING
VAPOR
LINE
C
Using two wrenches, disconnect liquid line from liquid line orifice hous-
ing. Take care not to twist or damage distributor tubes during this pro-
cess.
LIQUID
LINE
SENSING BULB
A
B
On fully cased coils, remove the coil access and plumbing panels.
D
E
Remove and discard fixed orifice, valve stem assembly if present and
®
Teflon washer as illustrated above.
Remove any shipping clamps holding the liquid line and distributor
assembly.
Use a field−provided fitting to temporary reconnect the liquid line to the
indoor unit’s liquid line orifice housing.
C
Disconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line.
D
E
Remove the vapor line sensing bulb.
CONNECT GAUGES AND EQUIPMENT FOR
FLUSHING PROCEDURE
Disconnect the liquid line from the check expansion valve at the liquid
line assembly.
2
INVERTED HCFC−22
GAUGE
MANIFOLD
F
Disconnect the check expansion valve from the liquid line orifice
housing.Take care not to twist or damage distributor tubes during this
process.
CYLINDER CONTAINS
CLEAN HCFC−22 TO BE
USED FOR FLUSHING.
A
®
G
H
Remove and discard check expansion valve and the two Teflon rings.
LOW
HIGH
1
Use a field−provided fitting to temporary reconnect the liquid line to the
indoor unit’s liquid line orifice housing.
NEW
OUTDOOR
UNIT
VAPOR LINE
SERVICE VALVE
FLUSHING LINE SET
OPENED
CLOSED
The line set and indoor unit coil must be flushed with at least the
same amount of clean refrigerant that previously charged the
system. Check the charge in the flushing cylinder before
proceeding.
EXISTING
INDOOR
UNIT
3
B
LIQUID LINE SERVICE
VALVE
A
Set the recovery machine for liquid recovery and start the
recovery machine. Open the gauge set valves to allow the
TANK
RETURN
rBecovery machine to pull a vacuum on the existing system line
set and indoor unit coil.
C
B
Invert the cylinder of clean HCFC−22 and open its valve to allow
liquid refrigerant to flow into the system through the vapor line
valve. Allow the refrigerant to pass from the cylinder and through
the line set and the indoor unit coil before it enters the recovery
machine.
INLET
D
RECOVERY
CYLINDER
DISCHARGE
RECOVERY MACHINE
A
Inverted HCFC−22 cylinder with clean refrigerant to the vapor service
valve.
C
D
After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC−22
vapor is recovered. Allow the recovery machine to pull down to 0
the system.
B
C
HCFC−22 gauge set (low side) to the liquid line valve.
HCFC−22 gauge set center port to inlet on the recovery machine with an
empty recovery tank to the gauge set.
Close the valve on the inverted HCFC−22 drum and the gauge
set valves. Pump the remaining refrigerant out of the recovery
machine and turn the machine off.
D
Connect recovery tank to recovery machines per machine instructions.
Figure 11. Flushing Line Set and Indoor Coil
Page 16
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
Installing Indoor Expansion Valve
This outdoor unit is designed for use in systems that use check expansion valve metering device. See the Lennox XP17
Engineering Handbook for approved check expansion valve kit match−ups and application information. The check
expansion valve unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being
installed in a field−provided plenum, install the check expansion valve in a manner that will provide access for field servicing
of the check expansion valve. Refer to below illustration for reference during installation of check expansion valve unit.
1/2 Turn
A
Remove the field−provided fitting that temporary
reconnectedthe liquid line to the indoor unit’s distributor
assembly.
INDOOR EXPANSION VALVE INSTALLATION
TWO PIECE
12
PATCH PLATE
(Uncased Coil Shown)
1
11
10
®
(UNCASED
STUB
END
2
B
Install one of the provided Teflon rings around the
stubbed end of the check expansion valve and lightly
lubricate the connector threads and expose surface of
LIQUID LINE
ORIFICE
COIL ONLY)
9
3
CHECK
EXPANSION
VALVE
4
8
HOUSING
5
7
®
6
DISTRIBUTOR
TUBES
the Teflon ring with refrigerant oil.
®
TEFLON
RING
C
D
E
Attach the stubbed end of the check expansion valve to
the liquid line orifice housing. Finger tighten and use an
appropriatelysized wrench to turn an additional 1/2 turn
clockwise as illustrated in the figure above, or 20 ft−lb.
®
®
Place the remaining Teflon washer around the other
end of the check expansion valve. Lightly lubricate
TEFLON
RING
SENSING
LINE
®
connector threads and expose surface of the Teflon
ring with refrigerant oil.
DISTRIBUTOR
ASSEMBLY
EQUALIZER
LINE
Attach the liquid line assembly to the check expansion
valve. Finger tighten and use an appropriately sized
wrench to turn an additional 1/2 turn clockwise as
illustratedin the figure above or 20 ft−lb.
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
SENSING BULB INSTALLATION
A
Attach the vapor line sensing bulb in the proper
orientationas illustrated to the right using the clamp and
screws provided.
1/8 Turn
MALE EQUALIZER LINE
FITTING (SEE
VAPOR
LINE
EQUALIZER LINE
INSTALLATION FOR
FURTHER DETAILS)
NOTE ꢀ Confirm proper thermal contact between vapor line
and check expansion bulb before insulating the sensing bulb
once installed.
12
1
5
11
10
2
LIQUID LINE
9
3
4
8
B
Connect the equalizer line from the check expansion
valve to the equalizer vapor port on the vapor line. Finger
tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated
below.
7
Sensing bulb insulation is required if
mountedexternal to the coil casing. sensing
bulb installation for bulb positioning.
6
ON LINES SMALLER THAN
7/8", MOUNT SENSING
BULB AT EITHER THE 3 OR
9 O’CLOCK POSITION.
VAPOR LINE
EQUALIZER LINE INSTALLATION
A
Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port
on the vapor line as illustrated in the figure to the right.
12
BULB
BULB
B
Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port on
the vapor line as illustrated in the figure to the right.
FLARE SEAL CAP
FLARE NUT
VAPOR LINE
ON 7/8" AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O’CLOCK
POSITION. NEVER MOUNT ON
BOTTOM OF LINE.
COPPER FLARE
SEAL BONNET
OR
12
MALE BRASS EQUALIZER
LINE FITTING
BULB
BULB
NOTE ꢀ NEVER MOUNT ON BOTTOM OF LINE.
VAPOR LINE
Figure 12. Installing Indoor Expansion Valve
Page 17
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
Leak Test Line Set and Indoor Coil
IMPORTANT
The Environmental Protection Agency (EPA) prohibits
the intentional venting of HFC refrigerants during
maintenance, service, repair and disposal of appliance.
Approved methods of recovery, recycling or reclaiming
must be followed.
IMPORTANT
Leak detector must be capable of sensing HFC
refrigerant.
IMPORTANT
WARNING
When using a high pressure gas such as
dry nitrogen to pressurize a refrigeration
or air conditioning system, use a
regulator that can control the pressure
down to 1 or 2 psig (6.9 to 13.8 kPa).
If this unit is being matched with an approved line set
or indoor unit coil which was previously charged with
mineral oil, or if it is being matched with a coil which
was manufactured before January of 1999, the coil
and line set must be flushed prior to installation. Take
care to empty all existing traps. Polyol ester (POE) oils
are used in Lennox units charged with HFC−410A
refrigerant. Residual mineral oil can act as an
insulator, preventing proper heat transfer. It can also
clog the expansion device, and reduce the system
performance and capacity.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.
Failure to properly flush the system per the
instructions below will void the warranty.
Failure to follow this warning may result in personal injury
or death.
CONNECT GAUGE SET
A
Connect an HFC−410A manifold gauge set high pressure
hose to the vapor valve service port.
LOW
HIGH
MANIFOLD GAUGE SET
1
NOTE ꢀ Normally, the high pressure hose is connected to
the liquid line port. However, connecting it to the vapor port
better protects the manifold gauge set from high pressure
damage.
OUTDOOR UNIT
B
With both manifold valves closed, connect the cylinder of
HFC−410A refrigerant to the center port of the manifold gauge
set.
NOTE ꢀ Later in the procedure,
the HFC−410A container will be
replaced by the nitrogen
container.
A
B
TO VAPOR
SERVICE VALVE
NITROGEN
HFC−410A
TEST FOR LEAKS
After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the
following procedure to test for leaks:
2
A
With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Open the valve
on the HFC−410A cylinder (vapor only).
B
Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount of HFC−410A. [A
trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the HFC−410A cylinder
and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.
C
D
Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set
and the indoor unit.
E
F
After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak
detector.
After leak testing disconnect gauges from service ports.
Figure 13. Leak Test
Page 18
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
Evacuating Line Set and Indoor Coil
CONNECT GAUGE SET
NOTE ꢀ Remove cores from service valves (if not already done).
HIGH
LOW
1
A
Connect low side of manifold gauge set
with 1/4 SAE in−line tee to vapor line
service valve
B
C
D
Connect high side of manifold gauge
set to liquid line service valve
OUTDOOR
UNIT
MANIFOLD
GAUGE SET
A34000 1/4 SAE TEE WITH
SWIVEL COUPLER
Connect micron gauge available
connector on the 1/4 SAE in−line tee.
Connect the vacuum pump (with
vacuum gauge) to the center port of the
manifold gauge set. The center port
line will be used later for both the
HFC−410A and nitrogen containers.
A
500
MICRON
GAUGE
C
TO VAPOR
SERVICE VALVE
NITROGEN
HFC−410A
B
VACUUM PUMP
TO LIQUID LINE
SERVICE VALVE
D
EVACUATE THE SYSTEM
RECOMMEND
MINIMUM 3/8" HOSE
A
B
Open both manifold valves and start the vacuum pump.
Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
2
NOTE ꢀ During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure
indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE ꢀ The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of
pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
C
When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:
S
S
S
S
S
S
S
Close manifold gauge valves
Close valve on vacuum pump
Turn off vacuum pump
Disconnect manifold gauge center port hose from vacuum pump
Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose.
Open manifold gauge valves to break the vacuum in the line set and indoor unit.
Close manifold gauge valves.
D
E
Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the
dry nitrogen from the line set and indoor unit.
Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the
absolutepressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.
When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an
F
upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and
indoor unit.
Perform the following:
G
1/6 TURN
S
S
S
S
Close manifold gauge valves.
Shut off HFC−410A cylinder.
12
1
5
11
7
2
4
10
Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
tool while maintaining a positive system pressure.
9
3
8
Replace stem caps and secure finger tight, then tighten an additional one−sixth (1/6) of a turn as illustrated.
6
Figure 14. Evacuating System
Page 19
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
temperatures and pressures present during operation of
an air conditioning system. Non−condensables and water
suction combine with refrigerant to produce substances
that corrode copper piping and compressor parts.
IMPORTANT
Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
capable of accurately measuring down to 50 microns.
Electrical
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).
WARNING
Danger of Equipment Damage. Avoid deep vacuum
operation. Do not use compressors to evacuate a
system. Extremely low vacuums can cause internal
arcing and compressor failure. Damage caused by
deep vacuum operation will void warranty.
Refer to the furnace or air handler installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
24VAC TRANSFORMER
Evacuating the system of non−condensables is critical for
proper operation of the unit. Non−condensables are
defined as any gas that will not condense under
Use the transformer provided with the furnace or air
handler for low-voltage control power (24VAC − 40 VA
minimum)
INSTALL THERMOSTAT
SIZE CIRCUIT AND INSTALL DISCONNECT
SWITCH
Install room thermostat (ordered separately) on an inside wall
2
1
approximately in the center of the conditioned area and 5 feet
(1.5m) from the floor. It should not be installed on an outside wall
or where it can be affected by sunlight or drafts.
Refer to the unit nameplate for minimum circuit ampacity, and
maximum fuse or circuit breaker (HACR per NEC). Install power
wiring and properly sized disconnect switch.
SERVICE
DISCONNECT
SWITCH
THERMOSTAT
5 FEET
(1.5M)
NOTE ꢀ Units are approved for use only with copper conductors.
Ground unit at disconnect switch or to an earth ground.
NOTE ꢀ 24VAC, Class II circuit connections are made in the control
box.
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and
local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors.
Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power
supplies.
CAUTION
Electrostatic discharge can affect electronic components. Take precautions
during unit installation and service to protect the unit’s electronic controls.
Precautions will help to avoid control exposure to electrostatic discharge by
putting the unit, the control andthe technicianat thesame electrostaticpotential.
Neutralize electrostaticchargebytouchinghandandalltoolsonanunpaintedunit
surface before performing any service procedure
ELECTROSTATIC DISCHARGE
(ESD)
Precautions and Procedures
Page 20
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
A. ROUTE CONTROL WIRES ꢀ NON−COMMUNICATING
Install low voltage control wiring from outdoor to indoor unit and from
thermostat to indoor unit.
3
CONTROL BOX
A
B
Run 24VAC control wires through hole with grommet.
Make 24VAC control wire connections to heat pump control (A175) .
NOTE ꢀ Do not bundle any excess 24VAC control wires inside control box.
NOTE ꢀ Wire tie provides low voltage wire strain relief and to maintain
separation of field installed low and high voltage circuits.
B
NOTE ꢀ For proper voltages, select control wires gauge per table below.
WIRE RUN LENGTH
AWG# INSULATION TYPE
LESS THAN 100’ (30 METERS) 18
MORE THAN 100’ (30 METERS) 16
TEMPERATURE RATING
35ºC MINIMUM.
HEAT PUMP
CONTROL (A175)
HOLE
A
B. ROUTE CONTROL WIRES ꢀ COMMUNICATING
º
º
Maximumlength of wiring (18 gauge) for all connections on the RSBus is limited to 1500 feet (457 meters). Color−coded, temperature rating 95 F (35 C)
minimum,solid core. (Class II Rated Wiring)
ROUTE HIGH VOLTAGE AND GROUND WIRES
Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring. To facilitate a conduit, a
cutout is located in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting.
4
PIPING PANEL
CONTROL BOX
GROUND LUG
HIGH VOLTAGE
CONDUIT HOLE
ELECTRICAL INLET
(HIGH VOLTAGE)
CONTACTOR
WATERTIGHT
CONDUIT
FITTING
WIRING ENTRY POINTS
WATERTIGHT
FLEXIBLE
CONDUIT
TO SERVICE
DISCONNECT BOX
ELECTRICAL INLET (CONTROL WIRING ꢀ LOW VOLTAGE).
USE BUSHING PROVIDED IN BAG ASSEMBLY HERE.
ACCESS VIEW
Page 21
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 15. Typical XP17 Wiring
Page 22
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
Heat Pump Control (A175) Jumpers and Terminals
HEAT PUMP CONTROL ꢀ ONE STAGE
Table 3 on page 24 provides additional information concerning jumpers, links, and connections for the heat pump control.
DS11 and DS14
*30
LED ALERT CODES
E37
COMPRESSOR
SHIFT DELAY
SECOND DELAY
30
0
SECOND DELAY
0
E33
FIELD TEST
DS13 and DS15
LED ALERT CODES
E47
100
DEGREE
TARGET
90
DEGREE
TARGET
70
DEGREE
TARGET
*50
DEGREE
TARGET
DEFROST TERMINATION TEMPERATURE
DS12
RECEIVING DATA INDICATOR
(COMMUNICATION MODE ONLY)
W1
CUT FOR HUMIDITROL APPLICATION
(TWO−STAGE UNITS ONLY)
Figure 16. Heat Pump Control (A175) Jumpers, Connections and LED Locations
Page 23
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 3. Heat Pump Control (A175) Jumper and Terminal Descriptions
Board ID
E12
Label
Description
PSC Fan
PSC Fan
W
240 VAC output connection for outdoor fan.
E16
240 VAC input connection for outdoor fan.
24VAC output for defrost auxiliary heat output.
L
Thermostat service light connection.
Y2
24VAC thermostat input/output for second stage operation of the unit.
24VAC thermostat input for first stage operation of the unit.
24VAC thermostat input for reversing valve operation
Y1
O
E18
DS
Humiditrol Input
C
24VAC system common
i−
Input/Output − RSBus data low. Used in communicating mode only with compatible indoor thermostat.
Input/Output − RSBus data high. Used in communicating mode only with compatible indoor thermostat.
24VAC system power input
i+
R
E19 and E20
E21 and E22
E31 and E32
E24 and E25
E26
O OUT
LO−PS
Y1 OUT
HS−PS
FAN 1
FAN 2
FAN C
24 VAC output connection for reversing valve.
Connection for low−pressure switch (2.4 milliamps @ 18VAC)
24 VAC common output, switched for enabling compressor contactor.
S87 connection for high−pressure switch (E25) and 24VAC (E24) to A177 ꢁR" input.
First Stage and second stage basic and precision dehumidification ECM fan motor 24VDC output connection 1.
Second stage basic and precision dehumidification ECM fan motor 24VDC output connection 2.
ECM common connection for ECM fan.
E27
E28
Six position square pin header. P4 provides connections for the temperature sensors.
DIS
Not used.
(YELLOW)
AMB 1 ꢀ Outdoor ambient temperature sensor supply.
AMB (BLACK)
(RT13)
AMB 2 ꢀ Outdoor ambient temperature return.
E30
Range is −40ºF to +140ºF
COIL 1 ꢀ Outdoor coil temperature sensor supply.
COIL
(BROWN)
(RT21)
COIL 2 ꢀ Outdoor coil temperature sensor return
Range is −40ºF to 140ºF. Sensor is clipped on a 5/16" copper return bend.
This jumper allows service personnel to defeat the timed off control, initiate or terminate a defrost and field
programmingof unit nominal capacity feature.
E33
E37
Field Test
Two position square pin header. When jumper is installed, a 30−second compressor shift delay which de−energizes
the compressor contactor output, second−stage solenoid output (if on) and the ECM fan outputs. After the timer
expires, the compressor contactor and ECM fan outputs are energized. If no jumper is installed, it changes the
reversing valve with de−energizing the outputs immediately.
Comp Shift
Delay
50*
70
Seven position square pin header. E47 provides selection of the defrost terminate temperature based on the posi-
tion of the selection jumper. The defrost termination temperature is measured by the defrost coil sensor. The jumper
terminationpin is factory set at 50°F (10°C). If the temperature jumper is not installed, the default termination tem-
perature is 90°F (32°C). In addition, it provides selection points for enabling the field test mode.
E47
W1
90
100
Short DS To R Cut for Humiditrol (EDA) application. Use only in two−stage units.
* Factory default setting
Page 24
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
Field Control Wiring
Air Hander Control
DS
ComfortSense[ 7000 Thermostats
Catalog # Y0349 or Y2081
One−Stage
Heat Pump Control
R
W
L
O
On−board link
5
G
Low voltage thermostat
wiring
Flat metal jumper
W2
L
6
Y2
Y1
O
W1
O
H
DH
L
R
DS
H
2
C
C
D
B
Y1
Y2
Y2
Y1
i−
1
G
i+
W3
C
R
3
W2
W1
T
T
4
1. Thermostat T terminals are used for outdoor sensor input. Use for thermostat’s outdoor temperature display (optional).
®
2. R to L connection is required for this model when using the ComfortSense 7000 − catalog number Y0349 only. Resistor Kit (catalog number 47W97)
required and ordered separately.
3. Air handler control ships from factory with metal jumpers installed across W1, W2 and W3. For one−stage electric heat, do not remove factory
installed metal jumpers.
4. Air handler control ships from factory with metal jumpers installed across W1, W2 and W3. For two−stage electric heat, remove factory installed metal
jumper between W1 to W2. Then connect thermostat wire between the air handler control’s W2 and the thermostat’s W2 terminal.
5. Cut on−board link (clippable wire) from R−O HEAT PUMP for heat pump applications.
®
6. Cut on−board link (clippable wire) DS−R for Humiditrol or Harmony IIIt applications. This will slow the indoor blower motor to the lowest speed
setting. See air handler installation instruction or engineering handbook for lowest fan speed information.
Figure 17. ComfortSense® 7000 Series Thermostat ꢀ Air Hander/One−Stage Heat Pump
Page 25
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
Furnace Control
DS
ComfortSense[ 7000 Thermostats
Catalog # Y0349 or Y2081
One−Stage
Heat Pump Control
R
W
L
O
On−board link
3
G
Low voltage thermostat
wiring
W2
L
H
4
Y2
Y1
O
W1
O
DH
L
R
DS
H
2
C
C
D
B
Y1
Y2
G
Y2
Y1
i−
1
i+
C
R
W2
W1
T
T
1. Thermostat T terminals are used for outdoor sensor input. Use for thermostat’s outdoor temperature display (optional).
®
2. R to L connection is required for this model when using the ComfortSense 7000 − catalog number Y0349 only. Resistor Kit (catalog number
47W97) required and ordered separately.
3. Cut on−board link W951 (clippable wire) from R−O HEAT PUMP for heat pump applications.
®
4. Cut on−board link (clippable wire) DS−R for Humiditrol or Harmony IIIt applications. This will slow the indoor blower motor to the lowest speed
setting. See furnace installation instruction or engineering handbook for lowest fan speed information.
NOTE − For defrost temper with furnace, the optional 67M41 temper kit would be wired between W of from the heat pump control (A175) to the W1 of the
furnace control. The kit allows for the furnace to cycle on and off during a defrost. It protects the compressor from high refrigeration pressures during
defrost.
®
Figure 18. ComfortSense 7000 Series Thermostat ꢀ Furnace/One−Stage Heat Pump
Page 26
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
3. After evacuation is complete, open both the liquid and
vapor line service valves to release the refrigerant
charge contained in outdoor unit into the system.
Servicing Units Delivered Void of Charge
If the outdoor unit is void of refrigerant, clean the system
using the procedure described below.
4. Replace the stem caps and tighten to the value listed
in table 1.
1. Leak check system using procedure outlined on page
18.
5. Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit’s
nameplate. If not, do not start the equipment until you
have consulted with the power company and the
voltage condition has been corrected.
2. Evacuate the system using procedure outlined on
3. Use nitrogen to break the vacuum and install a new
filter drier in the system.
4. Evacuate the system again using procedure outlined
6. Set the thermostat for a cooling demand. Turn on
power to the indoor indoor unit and close the outdoor
unit disconnect switch to start the unit.
5. Weigh in refrigerant using procedure outlined in figure
21.
7. Recheck voltage while the unit is running. Power must
be within range shown on the nameplate.
6. Monitor the system to determine the amount of
moisture remaining in the oil. It may be necessary to
replace the filter drier several times to achieve the
required dryness level. If system dryness is not
verified, the compressor will fail in the future.
8. Check system for sufficient refrigerant by using the
procedures listed under System Refrigerant.
Unit Start−Up
System Refrigerant
This section outlines procedures for:
IMPORTANT
If unit is equipped with a crankcase heater, it should be
energized 24 hours before unit start−up to prevent
compressor damage as a result of slugging.
1. Connecting gauge set for testing and charging (see
2. Checking and adjusting indoor airflow as described in
1. Rotate fan to check for binding.
3. Add or remove refrigerant using the weigh in method
2. Inspect all factory− and field−installed wiring for loose
connections.
MANIFOLD GAUGE SET
HIGH
LOW
GAUGE SET
CONNECTIONS FOR TESTING AND CHARGING
TRUE SUCTION PORT
B
CONNECTION
OUTDOOR UNIT
REFRIGERANT TANK
CHARGE IN
LIQUID PHASE
A
DIGITAL SCALE
INSIDE OUTDOOR UNIT
C
TO LIQUID
LINE SERVICE
VALVE
TEMPERATURE SENSOR
(LIQUID LINE)
D
TEMPERATURE
SENSOR
AClose manifold gauge set valves and connect the center hose to a cylinder of HFC−410A. Set for liquid phase charging.
BConnect the manifold gauge set’s low pressure side to the true suction port.
CConnect the manifold gauge set’s high pressure side to the liquid line service port.
DPosition temperature sensor on liquid line near liquid line service port.
Figure 19. Gauge Set Connections
Page 27
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
ADDING OR REMOVING REFRIGERANT
S
Temperature rise between the return air and supply air
temperatures at the indoor coil blower unit,
This system uses HFC−410A refrigerant which operates at
much higher pressures than HCFC−22. The pre−installed
liquid line filter drier is approved for use with HFC−410A
only. Do not replace it with components designed for use
with HCFC−22.
S
Measuring voltage supplied to the unit,
S
Measuring amperage being drawn by the heat unit(s).
Then, apply the measurements taken in following formula
to determine CFM:
COOLING MODE INDOOR AIRFLOW CHECK
Check airflow using the Delta−T (DT) process using the
Amps x Volts x 3.41
CFM =
1.08 x Temperature rise (F)
HEATING MODE INDOOR AIRFLOW CHECK
Blower airflow (CFM) may be calculated by energizing
electric heat and measuring:
INDOOR COIL
AIRFLOW
DT
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15
TEMPERATURE OF AIR
ENTERING INDOOR COIL ºF
78 23 23 23 22 22 21 21 20 19 18 17 16 15 14
76 22 22 22 21 21 20 19 19 18 17 16 15 14 13
74 21 21 21 20 19 19 18 17 16 16 15 14 13 12
72 20 20 19 18 17 17 16 15 15 14 13 12 11 10
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
A
WET−BULB ºF
57 58 59 60 61 62 63 64 65 66 67 68 69 70
DRY
BULB
B
A
72º
T
DROP
C
53º
19º
AIR FLOW
AIR FLOW
B
64º
DRY BULB
INDOOR COIL
All temperatures are expressed in ºF
WET BULB
Use the following procedure to adjust for optimal air flow across the indoor coil:
1. DETERMINE THE DESIRED DT ꢀ MEASURE ENTERING AIR TEMPERATURE USING DRY BULB (A) AND WET BULB (B). DT IS THE INTERSECTING VALUE
OF A AND B IN THE TABLE (SEE TRIANGLE).
2. Find temperature drop across coil ꢀ Measure the coil’s dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula:
(T
) = A minus C.
Drop
3. Determine if fan needs adjustment ꢀ If the difference between the measured T
is needed. See example below:
and the desired DT (T –DT) is within +3º, no adjustment
Drop
Drop
ASSUME DT = 15 AND A TEMP. = 72º, THESE C TEMPERATURES WOULD NECESSITATE STATED ACTIONS:
Cº
T
–
DT
=
ºF ACTION
DROP
19
Changing air flow affects all temperatures; recheck temperatures to
confirm that the temperature drop and DT are within +3º.
53º
58º
62º
–
–
–
15
15
15
=
=
=
4
INCREASE THE AIRFLOW
14
−1 (WITHIN +3º RANGE) NO CHANGE
10
−5 DECREASE THE AIRFLOW
4. ADJUST THE FAN SPEED ꢀ See indoor unit instructions to increase/decrease fan speed.
Figure 20. Checking Indoor Airflow over Evaporator Coil using Delta−T Chart Formula
Page 28
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
Use WEIGH IN method for adding initial refrigerant charge, and then use SUBCOOLING method for for verifying
refrigerant charge.
CHARGING METHOD
WEIGH IN
CALCULATING SYSTEM CHARGE FOR OUTDOOR UNIT VOID OF CHARGE
If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit. To calculate the total refriger-
ant charge:
Additional charge specified per indoor
Adjust amount. for variation in line set
length listed on line set length table below.
Amount specified on
nameplate
Total Charge
+
=
+
Refrigerant Charge per Line Set Length
OUNCES PER 5 FEET (G PER 1.5 M) ADJUST FROM 15 FEET (4.6 M)
LINE SET*
LIQUID LINE SET DIAMETER
3/8" (9.5 MM)
3 OUNCE PER 5’ (85 G PER 1.5 M)
*If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this
amount.
NOTE ꢀ Insulate liquid line when it is routed through areas where the surrounding ambient temperature could
become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.
NOTE ꢀ The above nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge
information.
Figure 21. Using HFC−410A Weigh In Method
CHARGING METHOD
SUBCOOLING
1. Check the airflow as illustrated in figure 20 to be sure the indoor airflow is as required. (Make any air flow adjustments
before continuing with the following procedure.)
2. Measure outdoor ambient temperature; determine whether to use coolingmodeor heating mode to check charge.
3. Connect gauge set.
4. Check liquid and vapor line pressures. Compare pressures with either heat or cooling mode normal operating
USE
COOLING
MODE
NOTE ꢀ The reference table is a general guide. Expect minor pressure variations. Significant differences may
mean improper charge or other system problem.
60ºF
(15ºC)
5. Set thermostat for heat/cool demand, depending on mode being used:
USE
HEATING
MODE
USING COOLING MODE ꢀ When the outdoor ambient temperature is 60°F (15°C) and above. Target
subcooling values (second stage − high capacity) in table 10 are based on 70 to 80°F (21−27°C) indoor return air
temperature; if necessary, operate heating to reach that temperature range; then set thermostat to cooling mode
setpoint to 68ºF (20ºC) which should call for second−stage (high stage) cooling. When pressures have stabilized,
USING HEATING MODE ꢀ When the outdoor ambient temperature is below 60°F (15°C). Target subcooling
values (second−stage − high capacity) in table 10 are based on 65−75°F (18−24°C) indoor return air temperature;
if necessary, operate cooling to reach that temperature range; then set thermostat to heating mode setpoint to
77ºF (25ºC) which should call for second−stage (high stage) heating. When pressures have stabilized, continue
SATº
LIQº
SCº
–
6. Read the liquid line temperature; record in the LIQº space.
=
7. Read the liquid line pressure; then find its corresponding temperature in the temperature/ pressure chart listed
in table 11 and record it in the SATº space.
8. Subtract LIQº temperature from SATº temperature to determine subcooling; record it in SCº space.
9. CompareSCº results with tables 4 through 9, being sure to note any additional charge for line set and/or match−
up.
10. If subcooling value is greater than shown in tables 4 through 9 for the applicable unit, remove refrigerant; if less
than shown, add refrigerant.
12. Disconnect gauge set and re−install both the liquid and suction service valve caps.
Figure 22. Using HFC−410A Subcooling Method ꢀ High Stage (High Capacity)
Page 29
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
Air Handler / Coil Match ups and Targeted Subcooling Values
Listed below are the targeted subcooling and charging values for approved indoor unit air handler / coil match ups. This
information is also listed on the unit charging sticker located on the access panel.
* Indicates amount of charge required in additional to charge shown on unit nameplate. Remember to consider line set
length differences.
Table 4. XP17−024
Table 7. XP17−042
Target
Subcooling
Heat Cool
(+5ºF)ꢁꢁꢁ(+1ºF)
Target
Subcooling
Heat Cool
(+5ºF)ꢁꢁꢁ(+1ºF)
*Add
charge
*Add
charge
INDOOR MATCHUPS
INDOOR MATCHUPS
lb
oz
lb
oz
CBX27UH−024
CBX27UH−030
CBX32M−030
CBX32M−036
CBX32MV−024/030
CBX32MV−036
CBX40UHV−024, −030, −036
CH23−51
16
16
16
16
16
16
16
16
16
16
28
16
16
3
5
3
5
3
5
5
3
3
3
3
3
5
1
6
9
CBX27UH−042, −048
CBX32M−048
CBX32MV−048
CBX40UHV−042, −048
CH23−51
12
12
12
12
17
14
14
14
36
11
19
14
19
8
4
4
4
4
7
4
4
4
4
6
6
4
6
7
4
1
0
0
0
0
0
0
0
0
0
8
6
0
6
0
0
1
1
1
1
1
1
1
0
0
0
1
1
1
1
1
0
0
0
0
0
0
0
0
0
1
0
6
9
6
9
CH33−43
9
CH33−44/48B, −48C, −49C
CH33−50/60C
CR33−48
6
CH33−31
11
11
0
CH33−42
CR33−50/60
CR33−48
CX34−38
CX34−31
6
CX34−43
CX34−38
9
CX34−44/48B
CX34−49
CX34−50/60C
14
Table 5. XP17−030
Table 8. XP17−048
Target
Subcooling
Heat Cool
(+5ºF)ꢁꢁꢁ(+1ºF)
*Add
charge
Target
Subcooling
Heat Cool
(+5ºF)ꢁꢁꢁ(+1ºF)
*Add
charge
INDOOR MATCHUPS
INDOOR MATCHUPS
lb
oz
lb
oz
CBX27UH−030, −036
CBX32M−030
CBX32M−036
CBX32MV−024/030
CBX32MV−036
CBX40UHV−024, −030, −036
CH23−51
15
19
15
19
15
15
19
19
19
30
19
15
6
5
5
5
5
5
5
5
5
5
4
5
5
4
5
8
4
1
3
7
CBX27UH−048
CBX27UH−060
CBX32M−048
CBX32M−060
CBX32MV−048
CBX32MV−060
CBX32MV−068
CBX40UHV−048
CBX40UHV−060
CH23−68
23
15
23
20
23
20
15
23
20
15
20
20
25
15
21
15
25
11
3
8
3
5
3
5
5
3
5
8
5
5
4
5
4
6
4
4
0
2
8
2
0
2
0
7
2
0
8
0
0
0
7
0
0
0
5
1
1
1
1
1
1
1
1
0
1
1
0
1
1
0
2
0
1
0
1
1
0
1
2
1
1
0
1
0
1
0
1
3
7
3
3
7
CH33−31
7
CH33−42
7
CR33−48
0
CX34−31
7
CH33−49C
CX34−38
3
CH33−50/60C
CH33−60D
CX34−43
11
3
CX34−44/48B
CX34−49
15
8
CH33−62D
14
11
CR33−50/60, −60D
CX34−49
CX34−50/60C
6
CX34−60D
CX34−62C, −62D
Table 6. XP17−036
Target
Subcooling
Heat Cool
(+5ºF)ꢁꢁꢁ(+1ºF)
Table 9. XP17−060
*Add
charge
Target
Subcooling
Heat Cool
(+5ºF)ꢁꢁꢁ(+1ºF)
*Add
charge
INDOOR MATCHUPS
lb
oz
INDOOR MATCHUPS
lb
oz
CBX27UH−036
CBX27UH−042
CBX32M−036, −042
CBX32M−048
CBX32MV−036
CBX32MV−048
CBX40UHV−036
CBX40UHV−042, −048
CH23−51
19
12
19
12
19
12
19
12
19
18
18
18
32
19
18
19
9
7
5
7
5
7
5
7
5
7
6
6
6
4
7
6
7
9
6
1
1
4
1
4
1
4
1
4
10
4
4
4
0
1
4
1
8
4
2
1
2
1
2
1
2
0
1
1
1
0
1
1
1
2
1
CBX27UH−048
CBX27UH−060
CBX32M−048
CBX32M−060
CBX32MV−048
CBX32MV−060
CBX32MV−068
CBX40UHV−048
CBX40UHV−060
CH23−68
14
15
14
16
14
16
13
14
16
18
16
16
13
21
16
13
13
3
8
3
3
3
3
5
3
3
8
3
3
5
4
3
5
5
0
0
8
1
0
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
12
0
12
15
0
CH33−42, −43
CH33−44/48B
CH33−48C
12
8
CH33−49C
12
12
15
0
CR33−48
CH33−50/60C
CH33−62D
CX34−38
CX34−43
CR33−50/60, −60D
CX34−49
CX34−44/48B
CX34−49
12
15
15
CX34−60D
CX34−50/60C
18
CX34−62C, −62D
Page 30
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating and Temperature Pressures
Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean
that the system is not properly charged or that a problem exists with some component in the system. The normal operating
pressures listed here are also located on the unit charging sticker located on the unit access panel.
Table 10. Normal Operating Pressure − Liquid +10 and Vapor +5 PSIG*
Use this table to perform maintenance checks; it is not a procedure for charging the
system. Minor variations in these pressures may be due to differences in installations.
Significant deviations could mean that the system is not properly charged or that a
IMPORTANT
problem exists with some component in the system.
Model
XP17−024
XP17−030
XP17−036
XP17−042
XP17−048
XP17−060
Heating Operation
5F (5C)**
20 (−6.6)
30 (−1.1)
40 (4.4)
Liquid
Vapor
65
Liquid
Vapor
63
Liquid
Vapor
60
Liquid
Vapor
59
Liquid
Vapor
63
Liquid
Vapor
58
291
309
319
340
361
303
328
338
366
387
280
290
310
326
344
288
306
320
339
361
324
345
366
398
428
330
354
368
391
413
79
77
74
68
76
72
94
92
88
85
91
83
50 (10.0)
60 (15.5)
110
129
110
128
105
124
107
125
109
127
107
126
Cooling Operation
65 (18.3)
70 21.1)
233
250
269
289
310
332
356
379
405
431
456
143
144
145
147
148
149
150
151
152
153
155
234
251
270
291
312
335
358
383
408
433
462
137
139
141
142
143
145
146
147
148
149
150
227
137
139
140
141
142
143
144
144
147
148
150
234
250
269
292
315
337
362
386
415
442
472
138
139
141
143
144
146
147
148
147
148
150
240
256
275
297
319
342
366
392
418
446
475
136
138
139
140
141
142
144
144
146
148
150
238
256
278
299
322
344
369
395
422
450
481
133
135
136
137
138
139
140
141
142
143
145
243
262
284
306
329
354
377
406
434
463
75 (23.9)
80 (26.7)
85 (29.4)
90 (32.2)
95 (35.0)
100 (37.8)
105 (40.6)
110 (43.3)
115 (46.1)
*These are most−popular−match−up pressures. Indoor match up, indoor air quality, and indoor load cause pressures to vary.
**Temperature of the air entering the outdoor coil.
Table 11. HFC−410A Temperature (°F) − Pressure (Psig)
°F
Psig
°F
Psig
°F
Psig
°F
Psig
°F
Psig
°F
Psig
°F
Psig
°F
Psig
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
100.8
102.9
105.0
107.1
109.2
111.4
113.6
115.8
118.0
120.3
122.6
125.0
127.3
129.7
132.2
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
137.1
139.6
142.2
144.8
147.4
150.1
152.8
155.5
158.2
161.0
163.9
166.7
169.6
172.6
175.4
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
178.5
181.6
184.3
187.7
190.9
194.1
197.3
200.6
203.9
207.2
210.6
214.0
217.4
220.9
224.4
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
231.6
235.3
239.0
242.7
246.5
250.3
254.1
258.0
262.0
266.0
270.0
274.1
278.2
282.3
286.5
94
95
290.8
295.1
299.4
303.8
308.2
312.7
317.2
321.8
326.4
331.0
335.7
340.5
345.3
350.1
355.0
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
365.0
370.0
375.1
380.2
385.4
390.7
396.0
401.3
406.7
412.2
417.7
423.2
428.8
434.5
440.2
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
545.6
552.3
559.1
565.9
572.8
579.8
586.8
593.8
601.0
608.1
615.4
622.7
630.1
637.5
645.0
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
445.9
451.8
457.6
463.5
469.5
475.6
481.6
487.8
494.0
500.2
506.5
512.9
519.3
525.8
532.4
96
97
98
99
100
101
102
103
104
105
106
107
108
47
134.6
78
228.0
109
360.0
140
539.0
Page 31
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
COMPRESSOR PROTECTION ꢀ FIVE−STRIKE
LOCKOUT SAFETY FUNCTION
System Operations
The five−strike lockout safety function is designed to
protect the unit’s compressor from damage. The five−strike
feature is used for high pressure (S4) and low (S87)
pressure switch trips and W input fault or miswire.
IMPORTANT
Some scroll compressor have internal vacuum protector
that will unload scrolls when suction pressure goes
below 20 psig. A hissing sound will be heard when the
compressor is running unloaded. Protector will reset
when low pressure in system is raised above 40 psig. DO
NOT REPLACE COMPRESSOR.
Resetting Five−Strike Lockout
Once the condition has been rectified, power to the heat
pump control’s R terminal must be cycled OFF, or a jumper
placed on the FIELD TEST pins between 1− to 2−seconds
to reset the heat pump control.
The heat pump control (A175) provides the following
functions:
Defrost System
The heat pump control (A175) measures differential
temperatures to detect when the system is performing
poorly because of ice build−up on the outdoor coil. The
system starts and after each system defrost cycle. The
heat pump control monitors ambient temperature, outdoor
coil temperature, and total run−time to determine when a
defrost cycle is required. The coil temperature sensor is
designed with a spring clip to allow mounting to the outside
coil tubing. The location of the coil sensor is important for
sensor).
S
S
Demand defrost algorithm
Field−selectable defrost termination temperatures
S
S
S
S
Internal switching of outputs
Compressor anti−short−cycle delay.
Five strikes lockout safety function
High (S4) and low (S87) pressure switches
S
Ambient (RT13), and coil temperatures (RT21)
temperature monitoring and protection.
COMPRESSOR ANTI−SHORT CYCLE DELAY
The heat pump control protects the compressor from:
NOTE − The heat pump control accurately measures the
performance of the system as frost accumulates on the
outdoor coil. This typically will translate into longer running
time between defrost cycles as more frost accumulates on
the outdoor coil before the heat pump control initiates
defrost cycles.
S
Short cycling (five minutes) when there is initial power
up
S
S
S
Interruption in power to the unit
Pressure or sensor trips
Delay after Y1 demand is removed.
DEFROST OPERATING MODES
The heat pump control board has three operational modes
which are:
In non−communicating systems the delay is set for 300
seconds (five minutes) and can not be changed. To
override timer when active or inactive, place a jumper on
the field test pins between 1 and 2 seconds.
S
S
®
In communicating system, the icomfort Touch thermostat
has a separate built−in 5−minute non−adjustable short cycle
protection.
DEFROST TERMINATION TEMPERATURES (E47)
The heat pump control selections are: 50, 70, 90, and
100°F (10, 21, 32 and 38°C). The jumper termination pin is
factory set at 50°F (10°C).
Resetting Anti−Short Cycle Delay
The FIELD TEST pins (E33) on the heat pump control can
be jumpered between 1 to 2 seconds to bypass delay.
If the temperature jumper is not installed, the default
on how this settings affects defrost calibration and defrost
modes.
HIGH (S4) AND LOW (S87) PRESSURE SWITCHES
The unit’s pressure switches (LO PS − S87 and HI PS − S4)
are factory−wired into the heat pump control on the LO−PS
and HI−PS terminals, respectively.
NOTE − Colder climates could require a high discharge
termination temperature setting to maintain a clear coil.
pressure switch sequence of operation.
IF JUMPER IS
NOT INSTALLED
(90ºF)
100
90
DEGREE
TARGET
DEGREE
TARGET
pressure switch sequence of operation.
Pressure Switch Event Settings
70
DEGREE
TARGET
50
DEGREE
TARGET
FACTORY DEFAULT
(50ºF)
The following pressures are the auto reset event value
triggers for low and high pressure thresholds:
S
S
High Pressure (auto reset) − trip at 590 psig; reset at
418.
Figure 23. Defrost Termination Temperature
Settings
Low Pressure (auto reset) − trip at 25 psig; reset at 40.
Page 32
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
UNIT SENSORS
Sensors connect to the heat pump control through a
field-replaceable harness assembly that plugs into the
control. Through the sensors, the heat pump control
detects outdoor ambient and coil temperature fault
conditions. As the detected temperature changes, the
how the resistance varies as the temperature changes for
both type of sensors. Sensor resistance values can be
COIL TEMPERATURE
SENSOR
AMBIENT AIR
TEMPERATURE SENSOR
10K RESISTOR
Figure 24. 10k Resistor Location
Table 12. Sensor Temperature / Resistance Range
Temperature
Range °F (°C)
Resistance values Pins/Wire
range (ohms)
NOTE ꢀ When checking the ohms across a sensor, be
aware that a sensor showing a resistance value that is not
designed. However, if a shorted or open circuit is detected,
then the sensor may be faulty and the sensor harness will
need to be replaced.
Sensor
Color
Outdoor
(Ambient)
3 and 4
(Black)
−40 (−40) to 140
(60)
280,000 to 3750
5 and 6
(Brown)
Coil
Ambient Temperature Sensor (RT13)
NOTE ꢀ Sensor resistance decreases as sensed temperature
detected as being open, shorted or out of the temperature
range of the sensor, the heat pump control will not perform
demand defrost operation. The heat pump control will
revert to time/temperature defrost operation and will
display the appropriate alert code. Heating and cooling
operation will be allowed in this fault condition.
W Input Fault or Miswire
In case of a W input fault or possible miswire, the system
will function as listed in the sequence of operation in figure
30.
Shift Delay (E37)
The heat pump control has a field−selectable function to
reduce occasional sounds that may occur while the unit is
cycling in and out of the defrost mode. When a jumper is
installed on the DELAY pins (E37), the compressor will be
cycled off for 30 seconds going in and out of the defrost
mode. Units are shipped with jumper installed on DELAY
pins.
Coil Temperature Sensor (RT21)
open, shorted or out of the temperature range of the
sensor, the heat pump control will not perform demand or
time/temperature defrost operation and will display the
appropriate fault code. Heating and cooling operation will
be allowed in this fault condition.
*30
FACTORY DEFAULT OR WHEN
JUMPER IS MISSING
SECOND DELAY
High Discharge Line Temperature Sensor
30
This model does not use a high discharge line temperature
sensor. The cable assembly attached to the heat pump
control’s E30 connection has a 10K resister installed
alarms would be generated if resistor is damage.
0
SECOND DELAY
0
Figure 25. Shift Delay Settings
Page 33
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
Defrost Calibration
Heat pump control monitors mode of
operation through outdoor ambient
temperature (RT13), outdoor coil
temperature(RT21) and compressor
run−time to determine when a defrost
cycle is required.
Coil sensor (RT21) detects temperature below 35°F {2°C}
during either initial power−up, after loss of power or after
cooling mode, a sacrificial defrost will be used to ensure there
is a clear coil before attempting calibration.
NOTE ꢀ No system alert codes can
be active for defrost calibration to be
achieved.
Coil sensor
No attempt
NO
below 35°F {2°C}
to calibrate.
100
DEGREE
TARGET
E47
*Heat Pump Control (A175)
YES
Defrost Termination (E47)
Pins (Factory Default is 50ºF)
90
Accumulate compressor run−time while outdoor
coil temperature sensor input (RT21) is below
35°F (2°C)
DEGREE
TARGET
70
DEGREE
TARGET
Continue to
accumulate
run time.
30−35 minutes
compressor
NO
*50
DEGREE
TARGET
run−time
YES
Defrost Mode
Demand Mode
Initiate a defrost and monitor coil temperature
sensor input (RT21) and accumulate defrost time.
After the initial calibration, the heat pump control
disables the defrost mode for 30−34 minutes in
order to avoid unnecessary defrosts. Beyond
this timing period, both the ambient (RT13) and
coil (RT21) sensors are continuously moni-
tored. If the coil temperature is below 35°F (2°C)
and the calibration delta is reached or accumu-
lated compressor run−time is more than six (6)
hours, a defrost is to be initiated.
How did defrost
terminate?
Defrosted for 14 minutes with-
Coil temperature sensor input
out the coil temperature sensor
input (RT21) reaching defrost
terminationtemperature as set
on heat pump control E47
pins*.
(RT21) reached specified de-
frost termination temperature
as set on heat pump control
E47 pins*.
Calibration Attempted
(Unit Running in Heat Mode)
NO
Calibration
YES
Figure 26. Defrost Calibration Sequence of Operations
Page 34
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
MULTI−FUNCTION TEST PINS (E33)
PSlacing the jumper on the field test pins (E33) using a specific sequence allows the technician to:
Clear short cycle lockout
S
S
S
Clear five−strike fault lockout
Cycle the unit in and out of defrost mode
Manually place the unit in defrost mode to clear the coil
WhenY1 is energized and 24V power is being applied to the heat pump control (A175), a test cycle can be initiated by placing a jumper on the heat pump
control’s TEST pins for 2 to 5 seconds. If the jumper remains on the TEST pins (E33) for longer than five seconds, the heat pump control will ignore the
jumperedTEST pins and revert to normal operation.
The heat pump control will initiate one test event each time a jumper is placed on the TEST pins. For each TEST the jumper must be removed for
at least one second and then reapplied.
Y1 Active
Place a jumper on TEST pins for
longer than one second but less
than two seconds.
Place a jumper on TEST pins for
more than two seconds.
Clears any short cycle lockout and
five strike fault lockout function, if
applicable.
Clears any short cycle lockout and
five strike fault lockout function, if
applicable.No other functions will be
executed and unit will continue in the
mode it was operating.
ACTIVE
INACTIVE
O Line Status
If in HEATING Mode
If in COOLING Mode
If in DEFROST Mode
The unit will terminate defrost and
enter HEAT MODE uncalibrated
with defrost timer set for a maximum
34 minute test.
If no ambient or coil sensor fault ex-
ist, unit will go into DEFROST
MODE.
If ambient or coil faults exist (open or
shorted), unit will remain in HEAT
MODE.
No further test mode operation will be
executed until the jumper is removed
from the TEST pins and reapplied.
If jumper on TEST pins remains in
place for more than five seconds.
If jumper on TEST pins is removed
before a maximum of five seconds.
NOTE ꢀ Heat pump control cannot be force into
defrost mode when the ambient temperature input
from the RT13 sensor is above 65ºF (18ºC).
The unit will remain in DEFROST
MODE until termination on time or
temperature.
The unit will return to HEAT MODE
un−calibrated with defrost timer set
for 34 minutes.
NOTE ꢀ If ambient or coil fault is detected, the board
will not execute the TEST mode.
Figure 27. Test Pin (E33) Functions
Page 35
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
LOW
PRESSURE
SWITCH (S87)
INITIAL TRIP
SWITCH IS
IGNORED FOR
90 SECONDS
COMPRESSOR
CONTACTOR
ENERGIZED
CLOSED
Y1 DEMAND
LOW
PRESSURE
SWITCH (S87)
SWITCH IS CLOSED OR OUTDOOR
AMBIENT TEMPERATURE IS 15ºF
OR BELOW
CLOSED
OPEN
COMPRESSOR
CONTACTOR
DE−ENERGIZED
1
If 5−strike counter has four or less strikes when Y1 demand is
terminatedor satisfied, the strike counter will reset to zero. In a icomfort
Touch® thermostat enabled setup, the thermostat will terminate demand
when the compressor contactor is de−energized. If demand is satisfied
when alarm is not active, the 5−strike counter will reset.
OPEN
2
COMPRESSOR
ANTI−SHORT
CYCLE TIMER
BEGINS
Lockouts can be reset by either cycling power off to the heat pump con-
trol’s (A175) R terminal, or placing a jumper on the field test pins (E33)
between 1 to 2 seconds.
5−STRIKE
COUNTER
REACHES 5
INCREMENT
5−STRIKE
COUNTER
WITHIN A SINGLE
Y1 DEMAND
1
LED ALERT
CODE / OR
MODERATE
ALERT 410
DISPLAYED
LOW
PRESSURE
SWITCH (S87)
LOCKOUT
LED ALERT
ANTI−SHORT
CYCLE TIMER
ENDS
CODE / OR
SERVICE
REQUIRED
CRITICAL
2
ALERT 411
DISPLAYED
COMPRESSOR
CONTACTOR
ENERGIZED
LED ALERT
CODE / OR
MODERATE
ALERT 410
DISPLAYED
LOW
PRESSURE
SWITCH (S87)
NORMAL
OPERATION
CLOSED
SERVICE
REQUIRED
2
WAITING FOR
PRESSURE
SWITCH TO
CLOSE
OPEN
CLOSED
Figure 28. Low Pressure (S87) Switch Operation
Page 36
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
HIGH
PRESSURE
SWITCH (S4)
COMPRESSOR
CONTACTOR
ENERGIZED
CLOSED
Y1 DEMAND
HIGH
PRESSURE
SWITCH (S4)
CLOSED
OPEN
COMPRESSOR
CONTACTOR
DE−ENERGIZED
1
If 5−strike counter has four or less strikes when Y1 demand is terminated
®
or satisfied, the strike counter will reset to zero. In a icomfort Touch
thermostatenabled setup, the thermostat will terminate demand when the
compressor contactor is de−energized. If demand is satisfied when alarm
is not active, the 5−strike counter will reset.
OPEN
COMPRESSOR
ANTI−SHORT
CYCLE TIMER
BEGINS
2
Lockouts can be reset by either cycling power off to the heat pump con-
trol’s (A175) R terminal, or placing a jumper on the field test pins (E33) be-
tween 1 to 2 seconds.
5−STRIKE
COUNTER
REACHES 5
INCREMENT
5−STRIKE
COUNTER
WITHIN A SINGLE
Y1 DEMAND
1
LED ALERT
CODE / OR
MODERATE
ALERT 412
DISPLAYED
HIGH
PRESSURE
SWITCH (S4)
LOCKOUT
LED ALERT
ANTI−SHORT
CYCLE TIMER
ENDS
CODE / OR
SERVICE
REQUIRED
CRITICAL
2
ALERT 413
CLEARED
COMPRESSOR
CONTACTOR
ENERGIZED
LED ALERT
CODE / OR
MODERATE
ALERT 412
DISPLAYED
HIGH
PRESSURE
SWITCH (S4)
NORMAL
OPERATION
CLOSED
SERVICE
REQUIRED
2
WAITING FOR
PRESSURE
SWITCH TO
CLOSE
OPEN
CLOSED
Figure 29. High Pressure Switch (S4) Sequence of Operation
Page 37
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
INITIAL TRIP
SWITCH IS
Y1 DEMAND
IGNORED FOR
90 SECONDS
COMPRESSOR
CONTACTOR
ENERGIZED
NORMAL
OPERATION
W OUTPUT
ACTIVE)
NO
YES
COMPRESSOR
CONTACTOR
DE−ENERGIZED
LED ALERT
CODE / OR
MODERATE
ALERT 418
DISPLAYED
COMPRESSOR
ANTI−SHORT
CYCLE TIMER
BEGINS
W OUTPUT
ACTIVE)
YES
NO
ANTI−SHORT
CYCLE TIMER
ENDS
COMPRESSOR
ANTI−SHORT
CYCLE TIMER
BEGINS
LED ALERT
CODE / OR
MODERATE
ALERT 418
CLEARED
W OUTPUT
ACTIVE)
NO
5−STRIKE
COUNTER
REACHES 5
INCREMENT
5−STRIKE
YES
WITHIN A SINGLE
Y1 DEMAND
1
COUNTER
WAITING FOR
W OUTPUT TO
DEACTIVATE
LED ALERT
CODE / OR
MODERATE
ALERT 418
DISPLAYED
W OUTPUT
HARDWARE
FAULT
LOCKOUT
ANTI−SHORT
CYCLE TIMER
ENDS
LED ALERT
CODE / OR
CRITICAL
ALERT 419
DISPLAYED
SERVICE
REQUIRED
2
LED ALERT
CODE / OR
MODERATE
ALERT 418
CLEARED
1
If 5−strike counter has four or less strikes when Y1 demand is terminated or satisfied, the strike counter will
®
reset to zero. In a icomfort Touch thermostat enabled setup, the thermostat will terminate demand when the
compressor contactor is de−energized. If demand is satisfied when alarm is not active, the 5−strike counter will
reset.
2
Lockouts can be reset by either cycling power off to the heat pump control’s (A175) R terminal, or placing
a jumper on the field test pins (E33) between 1 to 2 seconds.
Figure 30. W Input Fault or Miswire
Page 38
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 13. Ambient (RT13) and Coil (RT21) Sensors Temperature / Resistance Range
Degrees
Fahrenheit
Degrees
Fahrenheit
Degrees
Fahrenheit
Degrees
Fahrenheit
Resistance
Resistance
Resistance
Resistance
136.3
133.1
130.1
127.3
124.7
122.1
119.7
117.5
115.3
113.2
111.2
109.3
107.4
105.6
103.9
102.3
100.6
99.1
97.6
96.1
94.7
93.3
92.0
90.6
89.4
88.1
86.9
85.7
84.5
83.4
82.3
81.2
80.1
79.0
78.0
77.0
76.0
75.0
74.1
73.1
72.2
71.3
70.4
69.5
68.6
67.7
66.9
66.0
65.2
64.4
63.6
62.8
62.0
61.2
60.5
59.7
59.0
58.2
57.5
2680
2859
56.8
56.0
55.3
54.6
53.9
53.2
52.5
51.9
51.2
50.5
49.9
49.2
48.5
47.9
47.3
46.6
46.0
45.4
44.7
44.1
43.5
42.9
42.3
41.7
41.1
40.5
39.9
39.3
38.7
38.1
37.5
37.0
36.4
35.8
35.2
34.7
34.1
33.5
33.0
32.4
31.9
31.3
30.7
30.2
29.6
29.1
28.6
28.0
27.5
26.9
26.4
25.8
25.3
24.8
24.2
23.7
23.2
22.6
22.1
16657
16973
17293
17616
17942
18273
18607
18945
19287
19633
19982
20336
20695
21057
21424
21795
22171
22551
22936
23326
23720
24120
24525
24934
25349
25769
26195
26626
27063
27505
27954
28408
28868
29335
29808
30288
30774
31267
31766
32273
32787
33309
33837
34374
34918
35471
36031
36600
37177
37764
38359
38963
39577
40200
40833
41476
42130
42794
43468
21.6
21.0
20.5
20.0
19.4
18.9
18.4
17.8
17.3
16.8
16.3
15.7
15.2
14.7
14.1
13.6
13.1
12.5
12.0
11.5
11.0
10.4
9.9
44154
44851
45560
46281
47014
47759
48517
49289
50074
50873
51686
52514
53356
54215
55089
55979
56887
57811
58754
59715
60694
61693
62712
63752
64812
65895
67000
68128
69281
70458
71661
72890
74147
75431
76745
78090
79465
80873
82314
83790
85302
86852
88440
90068
91738
93452
95211
97016
98870
100775
102733
104746
106817
108948
111141
113400
115727
118126
120600
−11.3
−11.9
−12.6
−13.2
−13.9
−14.5
−15.2
−15.9
−16.5
−17.2
−17.9
−18.6
−19.3
−20.1
−20.8
−21.5
−22.3
−23.0
−23.8
−24.6
−25.4
−26.2
−27.0
−27.8
−28.7
−29.5
−30.4
−31.3
−32.2
−33.2
−34.1
−35.1
−36.1
−37.1
−38.2
−39.2
123152
125787
128508
131320
134227
137234
140347
143571
146913
150378
153974
157708
161588
165624
169824
174200
178762
183522
188493
193691
199130
204829
210805
217080
223677
230621
237941
245667
253834
262482
271655
281400
291774
302840
314669
327343
3040
3223
3407
3592
3779
3968
4159
4351
4544
4740
4937
5136
5336
5539
5743
5949
6157
6367
6578
6792
7007
7225
9.3
7444
8.8
7666
8.3
7890
7.7
8115
7.2
8343
6.7
8573
6.1
8806
5.6
9040
5.0
9277
4.5
9516
3.9
9757
3.4
10001
10247
10496
10747
11000
11256
11515
11776
12040
12306
12575
12847
13122
13400
13681
13964
14251
14540
14833
15129
15428
15730
16036
16345
2.8
2.3
1.7
1.2
0.6
0.0
−0.5
−1.1
−1.7
−2.2
−2.8
−3.4
−4.0
−4.6
−5.2
−5.7
−6.3
−6.9
−7.5
−8.2
−8.8
−9.4
−10.0
−10.6
Page 39
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
System Status, Fault and Lockout LED
Codes
IMPORTANT
DS15 and DS13 compressor LED fault and lockout
codes do not provide safety protection. The is a
monitoring function only and cannot control or shut down
other devices.
LED codes are displayed using various LEDs located on
heat pump control LEDs.
DS11 AND DS14 ꢀ SYSTEM STATUS, FAULT AND
LOCKOUT LED CODES
RESETTING FAULT AND LOCKOUT LED CODES
DS11 (Green) and DS14 (Red) LEDs indicate
non−communicatingmodediagnosticsconditionsthatare
All LED fault and lockout codes can be reset manually or
automatically:
These LEDs display the most common fault conditions in
the system. When an abnormal condition is detected, this
function communicates the specific condition through
system LED alert codes The function is capable of
detecting both mechanical and electrical system
problems.
1. Manual Reset
Manual reset can be achieve by one of the following
methods:
S
DisconnectingR wire from the heat pump control’s
R terminal.
DS15 AND DS13 ꢀ COMPRESSOR FAULT AND
LOCKOUT LED CODES
S
Turning the indoor unit off an on again
DS15 (Yellow) and DS13 (Red) LEDs indicate
non−communicatingmodediagnosticsconditionsthatare
After power up, existing code will display for 60
seconds and then clear.
These LEDs display the most common fault conditions in
the system. When an abnormal condition is detected, this
function communicates the specific condition through
system LED alert codes The function is capable of
detecting both mechanical and electrical system
problems.
2. Automatic Reset
After a fault or lockout is detected, the heat pump
control continues to monitor the unit’s system and
compressor operations. When/if conditions return to
normal, the alert code is turned off automatically.
®
Table 14. System Status, Fault and Lockout LED Codes and Related icomfort Touch Thermostat Alert Codes
System fault and lockout LED (DS11 / DS14) alarm codes takes precedence over system status LED codes (cooling, heating stages or
defrost/dehumidification).Only the latest active LED fault or lockout alarm code if present will be displayed. If no fault or lockout codes are active, then
system status LEDs are routinely displayed. See notes 1 and 2 in table below for duration of fast / slow flashes and pause.
Heat Pump Control
LEDs
icomfort
®
Touch
Condition
Possible Cause(s)
Solution
Thermostat
Display
DS11
DS14 Red
Green
SYSTEM STATUS
1. No power (24V) to heat
pump control terminal’s
R and C or heat pump
control failure.
1
2
Check control transformer power (24V).
Not
applicable
Off
Off
Power problem
If power is available to control and LED(s) do not
light, replace the heat pump control.
2. Heat pump control
failure.
Not
applicable
Simultaneous slow flash
Alternating slow flash
Normal operation Unit operating normally or in standby mode.
5−minute
anti−short cycle
delay
Initial power up, safety trip,
end of room thermostat de-
mand.
Not
applicable
None required (Jumper FIELD TEST (E33) pins to
override)
Moderate /
Critical Alert
Code 180
Simultaneous fast
flashes
Ambient sensor
problem
If sensor detects an open, shorted or out−of−temperature range. heat pump control
will revert to time/temperature defrost operation. System will still heat or cool.
Moderate /
Critical Alert
Code 417
Coil sensor
problem
If the outdoor coil temperature sensor is detected as being open or shorted, the heat
pump control will not perform defrost operations.
Alternating fast flash
Not
applicable
Heat pump
control failure
Indicates that heat pump control has an internal component failure. Cycle 24 volt
power to heat pump control. If code does not clear, replace the heat pump control.
On
On
Page 40
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
System fault and lockout LED (DS11 / DS14) alarm codes takes precedence over system status LED codes (cooling, heating stages or
defrost/dehumidification).Only the latest active LED fault or lockout alarm code if present will be displayed. If no fault or lockout codes are active, then
system status LEDs are routinely displayed. See notes 1 and 2 in table below for duration of fast / slow flashes and pause.
icomfort
®
Heat Pump Control
LEDs
Touch
Condition
Possible Cause(s)
Solution
Thermostat
Display
DS11
DS14 Red
Green
Single stage
compressor
heating
1 fast flash
Off
Not
applicable
then pause
2 fast
flashes
then pause
Not
applicable
On
Defrost
These are codes that show status of operation whether the system is operating in either
in first or second stage heating or cooling operation, defrost or in the dehumidification
modes.
Single−stage
compressor
cooling
1 fast flash
then pause
Not
applicable
Off
On
2 fast
flashes
then pause
Not
applicable
Dehumidification
mode
ALERT STATUS
®
icomfort Touch thermostat is unable to communicate with any other device on the
Moderate
Alert Code
105
Device
communication
failure
RSBus. Alarm only occurs if a specific device did communicate initially after power
up and communication was later lost. Possible causes are lost connection, bus
short or open, or other device stop responding.
None
Message could be sent by any device on RSBus if expected response message is
not received from other device. If sent by indoor or heat pump control, device did
not get expected response (incorrect or no response at all) from active Subnet
controller. If sent by the icomfort Touch thermostat, and did not get the expected
response (incorrect or no response at all) from device. Normally this indicate device
malfunction.
Moderate
Alert Code
120
Unresponsive
device
None
None
®
®
Device lost connection to icomfort Touch thermostat. Thermostat is sending
heartbeat message in one minute intervals. Device sets this alarm if no Heartbeat is
received for three minutes. Normally this indicate lost connection to thermostat, or
thermostat is not working. Alert will clear after valid subnet controller message is
received.
Critical Alert
Code 124
Active subnet
controller missing
Critical Alert
Code 125
Entire or partial system failure. Alert will clear 300 seconds after fault has
recovered.
None
None
Hardware Failure
Moderate /
Critical Alert
Code 126
Internal control
communication
failure
Internal communication on heat pump control. Alert will clear 300 seconds after fault
has recovered.
Critical Alert Corrupted control
Code 131 parameters
None
None
System stored configuration data is corrupted. System will not run.
Critical Alert Failed flash CRC No operations, heat pump control enters boot loader mode. Alarm will clears after
Code 132
check.
reset. Refer to communicating thermostat for memory corrupt handling.
Moderate
Alert Code
410
1
Remove any blockages or restrictions from coils
1
Low pressure
fault
Off
Off
Slow flash
Restricted air flow over in-
and/or fans. Check indoor and outdoor fan motor
for proper current draws.
door or outdoor coil.
2
Improper refrigerant
charge in system.
2
3
4
Check system charge using approach and sub-
cooling temperatures.
Critical Alert
Code 411
Low pressure
switch lockout
On
Off
Off
3
4
Improper metering device
installed or incorrect op-
eration of metering device.
Check system operating pressures and compare
to unit charging charts.
Moderate
Alert Code
412
High pressure
fault
Slow flash
On
Make sure all pressure switches and sensors have
secure connections to system to prevent refriger-
ant leaks or errors in pressure and temperature
measurements.
Incorrect or improper sen-
sor location or connection
to system.
Critical Alert
Code 413
High pressure
switch lockout
Page 41
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
System fault and lockout LED (DS11 / DS14) alarm codes takes precedence over system status LED codes (cooling, heating stages or
defrost/dehumidification).Only the latest active LED fault or lockout alarm code if present will be displayed. If no fault or lockout codes are active, then
system status LEDs are routinely displayed. See notes 1 and 2 in table below for duration of fast / slow flashes and pause.
icomfort
®
Heat Pump Control
LEDs
Touch
Condition
Possible Cause(s)
Solution
Thermostat
Display
DS11
DS14 Red
Green
Moderate
Alert Code
414
Discharge line
temperature fault
Slow flash
Fast flash
On
On
This code indicates high discharge temperatures. If the discharge line temperature
exceeds a temperature of 279ºF (137ºC) during compressor operation, the control
will de−energize the compressor contactor output (and the defrost output if active).
The compressor will remain off until the discharge temperature has dropped below
225ºF (107ºC).
Discharge line
temperature
lockout
Critical Alert
Code 415
Moderate /
Critical Alert
Code 417
The heat pump control (A175) detects open or short sensor or out of temperature
sensor range. This fault is detected by allowing the unit to run for 90 seconds before
checking sensor resistance. If the sensor resistance is not within range after 90
seconds, the control will raise the alarm.
Discharge sensor
fault
Off
Fast flash
3 fast
flashes
then pause
Moderate /
Critical Alert
Code 418
W output
hardware fault
When auxiliary heat output is detected as active. Fault in the heat pump control.
Replace heat pump control. See figure 30 for further details.
Off
On
3 fast
flashes
then pause
Moderate /
Critical Alert
Code 419
W output
hardware fault
lockout
If heat pump control recognizes five output hardware fault events during a single
ther details.
3 fast
flashes
then pause
Critical Alert
Code 421
W external
miswire fault
When auxiliary heat output is detected as active after compressor has been de−en-
ergized. See figure 30 for further details.
Off
Second−stage
heat lock−in
If the unit is in non−communicating mode and it goes to second stage due to ambi-
ent temperature being below second stage lock−in setting (E48).
Simultaneous fast
flashes then pause
None
Fast simultaneous flashing of DS11,
DS13, DS14 and DS15
OEM mode
Factory test mode.
1. Pause duration is two (2) seconds.
2. Fast flash duration is 1/2 second. Slow flash duration is one (1) second.
Page 42
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
®
Table 15. Compressor Fault and Lockout LED Codes and Related icomfort Touch Thermostat Alert Codes
NOTE ꢀ See notes 1 and 2 in table below for duration of fast / slow flashes and pause.
Heat Pump Control
icomfort
LEDs
®
Possible
Cause(s)
Touch
Condition
Solution
Clearing Status
Thermostat
Display
DS15
Yellow
DS13
Red
1
Compressor protector is open.
S
S
Check for high head pressure
Clears the error
after current is
sensed in the
run and start
winding for two
seconds, ser-
vice removed or
power reset.
Check compressor supply voltage
Thermostat
2
3
4
5
Outdoor unit power disconnect is open.
Moderate/
3
Compressor
internal
overload trip
demand signal Y1
is present, but
compressor not
running
Critical Alert
Code 400
Off
On
Compressor circuit breaker or fuse(s) is open.
Broken wire or connector is not making contact.
Low or high pressure switch open if present in the
system.
6
Compressor contactor has failed to close.
1
2
Low refrigerant charge.
Evaporator blower is not running.
S
S
S
S
Check blower relay coil and contacts
Check blower motor capacitor
Check blower motor for failure or blockage
Check evaporator blower wiring and connec-
tors
S
S
Check indoor blower control
Check thermostat wiring for open circuit
3
Evaporator coil is frozen.
S
S
S
Check for low suction pressure
Check for excessively low thermostat setting
Clears the error
after 30 consec-
utive normal run
cycles, or after
power reset.
Compressor is
running extremely
long run cycles.
Check evaporator airflow (coil blockages or re-
turn air filter)
1 flash
then pause
Critical Alert
Code 401
Off
Long run time.
S
Check ductwork or registers for blockage.
4
Faulty metering device.
S
S
Check TXV bulb installation (size, location and
contact)
Check if TXV/fixed orifice is stuck closed or de-
fective
5
6
7
.
Condenser coil is dirty
.
Liquid line restriction (filter drier blocked if present)
.
Thermostat is malfunctioning
S
S
Check thermostat sub−base or wiring for short
circuit
Check thermostat installation (location and lev-
el)
1
High head pressure.
S
Check high pressure switch if present in sys-
tem
S
S
Check if system is overcharged with refrigerant
Check for non−condensable in system
Indicates the
compressor
protector is open
or missing supply
power to the
Clears after four
consecutive
normal com-
pressor run
cycles, or after
power reset.
2
3
Condenser coil poor air circulation (dirty, blocked,
damaged).
2 flashes
then pause
Critical Alert
Code 402
System
pressure trip
Off
Condenser fan is not running.
compressor.
S
S
S
Check fan capacitor
Check fan wiring and connectors
Check fan motor for failure or blockage
4
Return air duct has substantial leakage.
Clears after four
consecutive
normal com-
pressor run
cycles, or after
power reset.
1
2
3
Thermostat demand signal is intermittent.
Moderate
Alert Code
403
Compressor is
running less than
three minutes.
3 flashes
then pause
Time delay relay or heat pump control is defective.
Off
Short cycling
If high pressure switch is present, see flash code 2
information.
Page 43
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
Heat Pump Control
LEDs
icomfort
®
Possible
Cause(s)
Touch
Condition
Solution
Clearing Status
Thermostat
Display
DS15
Yellow
DS13
Red
1
Compressor has
a locked out due
to run capacitor
short, bearings
are seized,
Run capacitor has failed.
2
Clears after
power reset or
four normal
compressor
cycles.
Low line voltage (contact utility if voltage at discon-
nect is low).
4 flashes
then pause
Critical Alert
Code 404
Off
Locked rotor
S
Check wiring connections
3
4
Excessive liquid refrigerant in the compressor.
Compressor bearings are seized.
excessive liquid
refrigerant.
1
2
3
Outdoor unit power disconnect is open.
Unit circuit breaker or fuse(s) is open.
Unit contactor has failed to close.
S
S
S
S
Check compressor contactor wiring and
connectors
Check for compressor contactor failure
(burned, pitted or open)
Compressor has
an open circuit
due to power dis-
connection, fuse
is open or other
similar conditions.
Check wiring and connectors between supply
and compressor
Clears after one
normal com-
pressor run
cycle or power
reset.
5 flashes
then pause
Critical Alert
Code 405
Off
Open circuit
Check for low pilot voltage at compressor
contactor coil
4
5
6
7
High pressure switch is open and requires manual
reset.
Open circuit in compressor supply wiring or
connections.
Unusually long compressor protector reset time
due to extreme ambient temperature.
Compressor windings are damaged.
S Check compressor motor winding resistance
Run capacitor has failed.
1
2
Clears when
Open circuit in compressor start wiring or
connections.
amperage is de-
tected in RUN
and START
sensors, or after
power reset.
Current not
sensed by Start
transformer.
6 flashes
then pause
Critical Alert
Code 406
Open start
circuit
S
Check wiring and connectors between supply
and the compressor S terminal
Off
3
1
Compressor start winding is damaged.
S
Check compressor motor winding resistance
Open circuit in compressor start wiring or
connections.
Clears when
amperage is de-
tected in RUN
and START
sensors, or after
power reset.
Current not
sensed by run
transformer.
S
Check wiring and connectors between supply
and the compressor R terminal
7 flashes
then pause
Critical Alert
Code 407
Open run
circuit
Off
2
Compressor start winding is damaged.
S
Check compressor motor winding resistance
Clears after one
normal com-
pressor run
cycle or after
power reset.
1
2
Compressor contactor failed to open.
8 flashes
then pause
Critical Alert
Code 408
Welded
contactor
Compressor
always runs
Off
Off
Thermostat demand signal not connected to mod-
ule.
Clears after volt-
age is higher
than 20VAC for
two seconds, or
after power re-
set.
1
2
Control circuit transformer is overloaded.
Moderate/
Critical Alert
Code 409
9 flashes
then pause
Secondary low 24VAC is below
voltage
Low line voltage (contact utility if voltage at discon-
nect is low).
3
18VAC.
S
Check wiring connections
Fast simultaneous flashing of DS11,
DS13, DS14 and DS15
OEM Mode
Factory test mode.
1. Pause duration is two (2) seconds.
2. Fast flash duration is 1/2 second. Slow flash duration is one (1) second.
3. Initially a moderate status is displayed and is escalated to critical if alarm exists for more than 10 minutes.
Page 44
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
FAN MOTOR CONTROL (A177) OPERATION, AND
TROUBLESHOOTING
Field Configuration and Testing
This section provides procedures for configuring,
adjusting and testing various components of this unit.
This section provides information concerning operation
and testing of the fan control.
Fan Motor Control Sequence of Operation
During start up, the following sequence is followed:
S
S
S
Fan Motor (B4) Testi Procedure
Fan Motor Control (A177) Configuration and Testing
Top Grille and Fan Motor Mounting Adjustment (Fan
Clearance)
2. If no errors are detected, the LED code indicating
applicable code and then a long pause.
S
Heat Pump Control (A175) Unit Nominal Capacity
Code configuration
3. The fan motor speed / RPM (revolutions per minute)
FAN MOTOR (B4) TEST PROCEDURE
4. There is a short pause.
The following procedure can be used to test the fan
motor operation. A fully charged 9V battery will be
test procedure.
The above sequence will continue to repeat if a thermostat
This is a test that will verify that the motor does operate.
1. Verify main (240 volt) power if OFF to unit.
2. Remove both wires (brown and black) from the J2 terminal on the fan motor
control (A177).
3. Room thermostat should be in OFF position (unit in idle mode − no heating or
cooling demands)
4. Turn main power (240 volt) ON to unit.
5. Connect 9 Volt battery to fan motor plugs as noted in picture below.
6. Fan motor should run at a reduced fan speed.
7. If fan motor does not run, then replace fan motor assembly.
BLACK LEAD
FAN MOTOR CONTROL
BROWN LEAD
BLACK LEAD
BROWN LEAD
J2
CONNECT B4 FAN MOTOR
WIRE TO 9V BATTERY
POSITIVE TERMINAL
REMOVE BOTH LEADS
FROM J2 TERMINALS
V
CONNECT B4 FAN
MOTOR BLACK COMMON
WIRE TO 9V BATTERY
NEGATIVE TERMINAL
BLACK LEAD
BROWN LEAD
NEGATIVE TERMINAL
POSITIVE TERMINAL
FULLY CHARGED
9V BATTERY
Figure 31. Fan Motor (B4) Test
Page 45
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 16. Fan Motor Control RPM, LED Code and DC Voltage Output
CFM Profile Pin Select
LED Code*
ECM1/Y1
(J2) DC Volt
Model
4
3
2
1
RPM
400
450
600
675
XP17−024
XP17−030
5
6
8
9
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
ON
OFF
ON
ON
12.7
14.3
19.2
21.6
ON
XP17−036, −042
XP17−048, −060
OFF
OFF
* LED Code indicates fan motor control LED flash sequence. For example, LED Code 9 indicates 9 slow flashes and pause.
Table 17. Fan Motor Control Error/Fault LED Codes
Verifying Correct DC Output Voltage (J2)
The following three methods can be used to determine
whether the fan motor (B4) is operating at the correct
RPMs based on unit size.
Unit Status
Motor Control LED
Possible Cause
Internal feedback,
PWM does not
match target
Fast flash with no
pause
Mismatched RPM
all four jumper terminals are set correctly for the
specific size unit.
Microcontroller CRC
failure
CRC Failure
Constant ON.
2. Verify LED RPM indicator is displaying the correct
flash sequence for the applicable size unit (see table
18).
Table 18. 19. Fan Motor Control Stage LED Indicator
Codes
Fan Motor Control
LED
Unit Status
Unit Status
3. Test DC voltage output on the fan motor control’s J2
verify the voltage read to the voltage listed in table 16
for the applicable size unit.
One Stage
Operation
Low Stage ꢀ
ECM1/Y1 ONLY
One slow flash, then
short pause.
4. If no voltage is detected at the J2 terminals, verify
there is a Y1 demand at the thermostat and applicable
voltages detected all fan motor control (A177) voltage
Table 20. Fan Motor Control Flash and Pause
Durations
Flash or Pause State
Duration
Flash Flash
Three flashes per second
One flash per second
Two seconds of OFF time
Five seconds of OFF time
If there is a demand, proceed to the next section for further
testing.
Slow Flash
Short Pause
Verifying Correct Input Voltage (ECM/Y1, ECM/Y2,
ECM C and EXT ECM/R)
Long Pause
Using a voltmeter, check voltages on the following fan
example.
Testing
Use the following subsections to verify and test the fan
motor control (A177).
If correct voltages are detected at applicable inputs during
a demand, and no voltage is present at the J2 terminals,
then fan motor control should be replaced.
Verifying Jumper Settings (J2)
The unit is shipped from the factory with the default fan
motor speed setting (in RPMs) required for each specific
correctly for the specific unit.
Table 21. Fan Motor Control Voltage Inputs
Call for
Cooling
Voltage
Present
Input
Verifying LED Status Codes
Between 24VDC
and 32 VDC
During start up, the fan motor control (A177) LED
will display any error conditions. If error conditions
exist then no other codes will display. If no error
conditions are present, then the stage status and
and RPM indicator are displayed. Fan motor speeds
are not adjustable for a single stage outdoor unit (see
YES
ECM/Y1 and ECM C
NO
NONE
24VAC
NONE
YES
NO
EXT ECM/R and ECM C
Page 46
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
DEMAND
BEGINS
DEFAULT FAN
MOTOR SPEED
USED
MISMATCHED
RPM
REPLACE FAN MOTOR
CONTROL BOARD
LED CONTINUOUS FAST
FLASH
DEFAULT FAN
MOTOR SPEED
USED
LED CONSTANT ON
REPLACE FAN MOTOR
CONTROL BOARD
CRC FAILURE
SINGLE STAGE
OR EDA
ECM1/Y1
STAGE LED INDICATOR: ONE
SLOW FLASH AND ONE
SHORT PAUSE FOR SINGLE
STAGE OR EDA OPERATION
FAN MOTOR
RPM SET PER
JUMPER
YES
ONLY OR
ECM2/Y2
ONLY
OPERATION
SETTINGS
NO
LED RPM INDICATOR:
EXAMPLE: (2−TON
DEMAND
ENDED
UNIT) – 5 SLOW
FLASHES AND ONE
LONG PAUSE
Figure 32. Fan Motor Control One Stage LED Sequence of Operation
TOP GRILLE OR FAN MOTOR MOUNT ADJUSTMENT FOR FAN CLEARANCE
Sometimes during shipping, either the fan motor mounting or top grille may become out of alignment. This may cause the fan
motor blade to not clear the orifice ring. If this situation occurs, simply adjust either or both the fan motor mount or top grille
positions to allow proper clearance. The top grille four fastener insertion points to the plastic top and motor mount locations are
larger than the fasteners used to secure the grille and fan motor mounts. Use the procedures provided in figure 33 to adjust for fan
clearance.
GRILLE MOUNTING
PUSH
FORWARD
PUSH
FORWARD
POINTS
FASTENER
INSERTION POINT
FAN MOTOR MOUNTING POINTS
The four mounting point holes that secure the top grille to the
plastic top are larger than the fasteners used to secure the grille.
this is also true for the four fasteners securing the fan motor to
the top grille. To provide more clearance, preform either or both
of the following procedures.
TOP GRILLE ADJUSTMENT
loosen the four grille mounting fasteners and push the grille
forward. tighten mounting hardware. if there is still insufficient
clearance proceed to Fan Motor Position Adjustment.
FAN MOTOR POSITION ADJUSTMENT
Loosen the four fan motor grille mounting fasteners and push the
fan motor forward. tighten mounting hardware.
GRILLE MOUNTING POINTS
ORIFICE RING
Figure 33. Fan Blade Clearance Adjustment
Page 47
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
CFM Profile Pin Select
FAN MOTOR CONTROL (A177) ꢀ
PULSE−WIDTH MODULATION (PWM)
JUMPER
OFF
LED
JUMPER
ON
CONTROL BOX
HEAT PUMP
CONTROL (A175)
VERIFY DC VOLTAGE OUTPUT USING FAN PWM OUT AND
VOLTAGE BASED ON CFM PROFILE USED.
J2
J2
COM
FAN PWM OUT
GREEN
GREEN
RED
RED
RED
B4 FAN
MOTOR
BLACK
RED
BROWN
YELLOW
HIGH PRESSURE SWITCH (S4)
YELLOW
BLUE
BLACK
YELLOW
YELLOW
FAN MOTOR
CONTROL
YELLOW
YELLOW
SELECTION OPTIONS.
HEAT PUMP CONTROL (A175)
Figure 34. Fan Motor Control, Wiring, Jumper Settings, Testing and LED Location
Page 48
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
FAN MOTOR CONTROL (A177) ꢀ
PULSE−WIDTH MODULATION (PWM)
CONTROL BOX
INPUT VOLTAGES DURING DEMAND
ECM/Y1 ONLY − 24VDC
YELLOW WIRE
HEAT PUMP
CONTROL (A175)
BLUE WIRE
24
BLACK WIRE
VDC
VAC
ONE YELLOW WIRE FROM PS (E24) TERMINAL ON HEAT PUMP
CONTROL (A175) AND SECOND YELLOW WIRES ON PIGGYBACK
TERMINALS GOES TO S4 HIGH PRESSURE SWITCH.
GREEN
EXT PWR/R (24VAC INPUT
DURING DEMAND ONLY)
GREEN
RED
RED
RED
B4 FAN
MOTOR
BLACK
BROWN
RED
YELLOW
YELLOW
BLUE
BLACK
S4 HIGH PRESSURE SWITCH
YELLOW
YELLOW
FAN MOTOR
CONTROL
YELLOW
YELLOW
SELECTION OPTIONS.
HEAT PUMP CONTROL
Figure 35. Testing for External Power to Fan Motor Control
Page 49
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
HEAT PUMP CONTROL (A175) UNIT NOMINAL
CAPACITY CODE CONFIGURATION
In a communicating system, if the room thermostat is
indicating either a error code 313, indoor and outdoor unit
capacity mismatch error code, or error code 34, must
program unit capacity for outdoor unit. Use the procedure
FINISH
START
DS14 (Red)
DS11 (Green)
Set room thermostat
to OFF
Connect R wire to
control (24 volt AC
power)
Go to control terminal
strip
Remove R wire
from control (24 volt
AC power)
Field Test
(E33)
Reconnect any control
wiring previously
removed.
DS12
Communicating
Status Indicator
®
®
icomfort
Non − icomfort
enabled ꢀ
enabled ꢀ
Remove control
wires from i+ and
i− terminals
Remove R wire from
air conditioner control
Remove control
wire from Y1
terminal
(24 volt AC power)
Sensor harness
must be attached
to air conditioner
control.
Place jumper on
FIELD TEST
(E33 pins)
When the required Unit Capacity Code
is displaying on the LEDs, remove
FIELD TEST jumper from pins (E33).
LEDs will continue to display the
selected unit capacity code for two (2) minutes
before defaulting back to the idle mode
{simultaneous slow flash}, or until the 24 volt
power is cycled to the air conditioner control.
Place jumper on FIELD
TEST (E33 pins) within 2 to 4
seconds after removal
Connect R wire to control
(24 volt AC power)
The control´s DS11 and DS14 LEDs will
start blinking the Unit Nominal Code at
three (3) second intervals starting at 1−ton
throughto 6−ton. If a code is not selected,
the control will cycle one more time
through the codes before defaulting back
to the idle mode (simultaneous slow
flash).
DS11
Green
LED
DS14
Red LED
Size
Model
Status LED lights DS11
and DS14 will blink and
then on continuously.
Once both LEDs are on
continuouslythen remove
jumper immediately from
E33.
−012
1−ton
1 long flash
OFF
ON
−018
−024
−030
−036
−042
−048
−054
−060
−066
−072
1.5−ton
2−ton
1 long flash
2 long flashes
2 long flashes
3 long flashes
3 long flashes
4 long flashes
4 long flashes
5 long flashes
5 long flashes
6 long flashes
OFF
ON
2.5−ton
3−ton
If jumper is not removed
immediatelyfrom E33, then DS11
and DS14 LEDs will resume
blinking again.
OFF
ON
Long blink ON red LED (DS14) to indicate
tonnageand solid ON green LED (DS11)
to indicate ½ tonnage.
3.5−ton
4−ton
YES
OFF
ON
Jumper
removed
successfully
4.5−ton
5−ton
OFF
ON
Remove R wire
from control (24 volt
AC power)
5.5−ton
6.0−ton
NO
OFF
Figure 36. Heat Pump Control (A175) Unit Nominal Capacity Code Configuration
Page 50
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
S
S
Outdoor Coil ꢀ The outdoor coil may be flushed with
a water hose.
Maintenance
Outdoor Coil (sea coast) ꢀ Moist air in ocean
locations can carry salt, which is corrosive to most
metal. Units that are located near the ocean require
frequent inspections and maintenance. These
inspections will determine the necessary need to wash
the unit including the outdoor coil. Consult your
installing contractor for proper intervals/procedures
for your geographic area or service contract.
WARNING
This product and/or the indoor unit it is matched with may
contain fiberglass wool.
Disturbing
the
insulation
during
installation,
maintenance, or repair will expose you to fiberglass wool
dust. Breathing this may cause lung cancer. (Fiberglass
wool is known to the State of California to cause cancer.)
Indoor Unit
Fiberglass wool may also cause respiratory, skin, and
eye irritation.
1. Clean or change filters.
2. Lennox blower motors are prelubricated and
permanently sealed. No more lubrication is needed.
To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact your
supervisor.
3. Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure.
Lennox Industries Inc.
P.O. Box 799900
Dallas, TX 75379−9900
4. Belt Drive Blowers − Check belt for wear and proper
tension.
DEALER
5. Check all wiring for loose connections.
6. Check for correct voltage at unit. (blower operating)
7. Check amp draw on blower motor.
Outdoor Unit
Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each
cooling season, the system should be checked as follows:
Motor Nameplate:_________ Actual:__________.
Indoor Coil
1. Clean and inspect outdoor coil (may be flushed with a
water hose). Ensure power is off before cleaning.
1. Clean coil if necessary.
2. Check connecting lines, joints and coil for evidence of
oil leaks.
2. Outdoor unit fan motor is pre−lubricated and sealed.
No further lubrication is needed.
3. Check condensate line and clean if necessary.
3. Visually inspect all connecting lines, joints and coils for
evidence of oil leaks.
Locations with Possibility of Heavy Snow or
Freezing Rain Accumulation
4. Check all wiring for loose connections.
Heavy snow and/or freezing rain can interfere with the
performance of the outdoor fan assembly. Lennox
recommends use of the optional snow guard (X8782) in
these areas.
5. Check for correct voltage at unit (unit operating).
6. Check amp draw on outdoor fan motor.
Motor Nameplate:_________ Actual:__________.
7. Inspect drain holes in coil compartment base and
clean if necessary.
NOTE - If insufficient heating or cooling occurs, the unit
should be gauged and refrigerant charge should be
checked.
Outdoor Coil
It may be necessary to flush the outdoor coil more
frequently if it is exposed to substances which are
corrosive or which block airflow across the coil (e.g., pet
urine, cottonwood seeds, fertilizers, fluids that may contain
high levels of corrosive chemicals such as salts)
Figure 37. Snow Guard Top Cover ꢀ X8782
Page 51
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
formed as your system removes humidity from the
inside air. Have your dealer show you the location of
the drain line and how to check for obstructions. (This
would also apply to an auxiliary drain, if installed.)
HOMEOWNER
Cleaning of the outdoor unit’s coil should be performed by
a trained service technician. Contact your dealer and set
up a schedule (preferably twice a year, but at least once a
year) to inspect and service your outdoor unit. The
following maintenance may be performed by the
homeowner.
Thermostat Operation
®
See the ComfortSense 7000 thermostat homeowner
manual for instructions on how to operate your thermostat.
Heat Pump Operation
Your new Lennox heat pump has several characteristics
that you should be aware of:
IMPORTANT
Sprinklers and soaker hoses should not be installed
where they could cause prolonged exposure to the
outdoor unit by treated water. Prolonged exposure of the
unit to treated water (i.e., sprinkler systems, soakers,
waste water, etc.) will corrode the surface of steel and
aluminum parts and diminish performance and longevity
of the unit.
S
Heat pumps satisfy heating demand by delivering
large amounts of warm air into the living space. This
is quite different from gas- or oil-fired furnaces or an
electric furnace which deliver lower volumes of
considerably hotter air to heat the space.
S
Do not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor
coil during the heating cycle when temperatures are
below 45F (7C). The heat pump control activates a
defrost cycle lasting 5 to 15 minutes at preset intervals
to clear the outdoor coil of the frost.
Outdoor Coil
The outdoor unit must be properly maintained to ensure its
proper operation.
S
S
S
Please contact your dealer to schedule proper
inspection and maintenance for your equipment.
S
During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The
thermostat may engage auxiliary heat during the
defrost cycle to satisfy a heating demand; however,
the unit will return to normal operation at the
conclusion of the defrost cycle.
Make sure no obstructions restrict airflow to the
outdoor unit.
Grass clippings, leaves, or shrubs crowding the unit
can cause the unit to work harder and use more
energy.
Extended Power Outage
The heat pump is equipped with a compressor crankcase
heater which protects the compressor from refrigerant
slugging during cold weather operation.
S
Keep shrubbery trimmed away from the unit and
periodically check for debris which collects around the
unit.
If power to your unit has been interrupted for several hours
or more, set the room thermostat selector to the
EMERGENCY HEAT setting to obtain temporary heat
without the risk of serious damage to the heat pump.
Routine Maintenance
In order to ensure peak performance, your system must be
properly maintained. Clogged filters and blocked airflow
prevent your unit from operating at its most efficient level.
In EMERGENCY HEAT mode, all heating demand is
satisfied by auxiliary heat; heat pump operation is locked
out. After a six-hour compressor crankcase warm-up
period, the thermostat can be switched to the HEAT setting
and normal heat pump operation may resume.
1. Air Filter ꢀ Ask your Lennox dealer to show you
where your indoor unit’s filter is located. It will be either
at the indoor unit (installed internal or external to the
cabinet) or behind a return air grille in the wall or
ceiling. Check the filter monthly and clean or replace
it as needed.
Preservice Check
If your system fails to operate, check the following before
calling for service:
2. Disposable Filter ꢀ Disposable filters should be
replaced with a filter of the same type and size.
S
S
S
S
S
S
Verify room thermostat settings are correct.
Verify that all electrical disconnect switches are ON.
Check for any blown fuses or tripped circuit breakers.
Verify unit access panels are in place.
NOTE ꢀ If you are unsure about the filter required for your
system, call your Lennox dealer for assistance.
3. Reusable Filter ꢀ Many indoor units are equipped
with reusable foam filters. Clean foam filters with a
mild soap and water solution; rinse thoroughly; allow
filter to dry completely before returning it to the unit or
grille.
Verify air filter is clean.
If service is needed, locate and write down the unit
model number and have it handy before calling.
NOTE ꢀ The filter and all access panels must be in place
any time the unit is in operation.
Accessories
For update−to−date information, see any of the following
publications:
4. Lennox Branded Air Filters ꢀ are designed to
remove airborne particles from the air passing through
the filter.
S
S
S
Lennox XP17 Engineering Handbook
Lennox Product Catalog
5. Indoor Unit ꢀ The indoor unit’s evaporator coil is
equipped with a drain pan to collect condensate
Lennox Price Book
Page 52
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
The SolarSynct package consists of the following
SunSource® Home Energy System
components:
®
®
This Dave Lennox Signature Collection heat pump is
factory−equipped with components that make it
S Lennox Solar Subpanel installed in a Dave Lennox
unit.
®
Signature Collection air conditioner or heat pump
®
SunSource solar−ready. These units can be matched
with solar modules and other optional equipment so that
they can become part of a SunSource Home Energy
System.
S Solar modules (1 to 15 may be used to vary the
®
amount of electricity generated).
S Envoy Communications Gateway monitors solar
Units can be upgraded for use with solar equipment at the
time of installation or in the future.
power performance.
All components must be ordered separately. See the
®
Lennox XP17 Engineering Handbook for SunSource
Home Energy System component ordering.
Solar energy is first used to meet cooling/heating
demands. When the outdoor unit is not operating, the
system powers lighting, appliances and other electronic
devices in the home. Any surplus power is sent back to the
utility company for a possible credit (check with your local
utility company for availability).
Wiring runs from the roof−mounted solar modules to the
outdoor unit. From there, power travels to the home
electrical service panel using the existing outdoor unit
power wiring.
Page 53
XP17 SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
XP17 Start−Up and Performance Checklist
Customer
Address
Serial
Indoor Unit Model
Outdoor Unit Model
Solar Module Mfg and Model
Notes:
Serial
Serial
START−UP CHECKS
RefrigerantType:
Rated Load Amps
Actual Amps
Actual Amps:
Rated Volts
Actual Volts
Condenser Fan Full Load Amps
COOLING MODE
Vapor Pressure:
Liquid Pressure:
Supply Air Temperature:
Ambient Temperature:
Return Air Temperature:
Return Air Temperature:
HEATING MODE
Vapor Pressure:
Liquid Pressure:
Supply Air Temperature:
Ambient Temperature:
System Refrigerant Charge (Refer to manufacturer’s information on unit or installation instructions for required subcooling and approach
temperatures.)
Subcooling:
A
A
A
ꢀ
ꢀ
ꢀ
B
B
B
=
=
=
SUBCOOLING
APPROACH
Saturated Condensing Temperature (A)
minus Liquid Line Temperature (B)
Approach:
Liquid Line Temperature (A)
minus Outdoor Air Temperature (B)
Indoor Coil Temp. Drop (18 to 22°F)
COIL TEMP DROP
Return Air Temperature (A)
minus Supply Air Temperature (B)
Page 54
506586−01 10/10
Download from Www.Somanuals.com. All Manuals Search And Download.
|