Lennox International Inc Gas Heater G61MP Series Units User Manual

INSTALLATION  
INSTRUCTIONS  
E 2009 Lennox Industries Inc.  
Dallas, Texas, USA  
G61MP SERIES UNITS  
GAS UNITS  
506406−01  
08/2009  
Litho U.S.A.  
Supersedes 505,124M  
Table of Contents  
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
G61MP Parts Identification . . . . . . . . . . . . . . . . . . . . . . 3  
Shipping and Packing List . . . . . . . . . . . . . . . . . . . . . . 4  
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
Use of Furnace as Construction Heater . . . . . . . . . . . 5  
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Combustion, Dilution & Ventilation Air . . . . . . . . . . . . 6  
Installation − Setting Equipment . . . . . . . . . . . . . . . . . . 8  
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
Duct System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
Pipe & Fittings Specifications . . . . . . . . . . . . . . . . . . . . 16  
Vent Piping Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . 18  
Joint Cementing Procedure . . . . . . . . . . . . . . . . . . . . . 20  
Venting Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21  
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
Integrated Control Board . . . . . . . . . . . . . . . . . . . . . . . 42  
Unit Start−Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42  
Gas Pressure Adjustment . . . . . . . . . . . . . . . . . . . . . . 44  
High Altitude Information . . . . . . . . . . . . . . . . . . . . . . . 45  
Other Unit Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . 46  
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53  
Ignition Control Board Diagnostic Codes . . . . . . . . . . 56  
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57  
Repair Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62  
Vent Pipe Sizing Worksheet . . . . . . . . . . . . . . . . . . . . . 63  
Start−Up & Performance Check List . . . . . . . . . . . . . . 63  
THIS MANUAL MUST BE LEFT WITH THE  
HOMEOWNER FOR FUTURE REFERENCE  
WARNING  
FIRE OR EXPLOSION HAZARD.  
Failure to follow safety warnings exact-  
ly could result in serious injury, death,  
or property damage.  
WHAT TO DO IF YOU SMELL GAS:  
Do not store or use gasoline or other  
D Do not try to light any appliance.  
flammable vapors and liquids in the  
vicinity of this or any other ap-  
pliance.  
D Do not touch any electrical switch; do not  
use any phone in your building.  
D Leave the building immediately.  
D Immediately call your gas supplier from a  
neighbor’s phone. Follow the gas supplier’s  
instructions.  
Installation and service must be  
performed by a qualified installer,  
service agency or the gas supplier.  
D If you cannot reach your gas supplier, call  
the fire department.  
08/09  
506406−01  
Page 1  
*2P0809*  
*P506406-01*  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G61MP Parts Arrangement  
G61MP PARTS IDENTIFICATION  
TOP CAP  
DuralokPlusTM  
HEAT EXCHANGER  
ASSEMBLY  
CABINET  
BURNER BOX  
ASSEMBLY  
GAS VALVE  
AND MANIFOLD  
FLUE  
COLLAR  
COMBUSTION  
AIR PRESSURE  
PROVE SWITCHES*  
WARM HEADER  
(COLLECTOR)  
BOX  
COMBUSTION AIR  
INDUCER  
CONDENSER COIL  
BURNER  
ACCESS  
PANEL  
PRIMARY LIMIT  
COLD HEADER  
(COLLECTOR)  
BOX  
BLOWER  
ACCESS  
DOOR  
DOOR  
INTERLOCK  
SWITCH  
SECONDARY  
LIMITS (2)  
*G61MP−090 shown.  
G61MP−045 and −070  
are equipped with  
two switches.  
BLOWER  
ASSEMBLY  
SIGHT  
GLASS  
CONTROL BOX  
FIGURE 1  
Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE  
G61MP−48C−110, G61MP−60C−110 and  
G61MP Gas Furnace  
G61MP−60C−111 units also include a 2" diameter PVC  
street elbow, which is shipped on the blower deck in the  
heating compartment. G61MP−60D−135 units are shipped  
with a 3" to 2" PVC reducing elbow.  
The G61MP category IV gas furnace is shipped ready for  
installation in the upflow, downflow, horizontal left air dis-  
charge or horizontal right air discharge position. The fur-  
nace is shipped with the bottom panel in place. The bot-  
tom panel must be removed if the unit is to be installed in  
upflow applications with bottom return air. The bottom  
panel must also be removed and discarded in all downflow  
or horizontal applications.  
Canadian Installations Only − Replace the provided 2"  
street elbow shipped with the G61MP−48C−110,  
G61MP−60C−110 and G61MP−60C−111 units with 2" street  
elbow Y0162. Replace the provided 3" X 2" reducing elbow  
shipped with the G61MP−60D−135 units with 3" X 2" reduc-  
ing elbow 40W22. Y0162 and 40W22 meet B149 vent re-  
quirements.  
The furnace is equipped for installation in natural gas ap-  
plications. A conversion kit (ordered separately) is re-  
quired for use in propane/LP gas applications.  
Check equipment for shipping damage. If you find any  
damage, immediately contact the last carrier.  
The G61MP can be installed as either a Direct Vent or a  
Non−Direct Vent gas central furnace.  
The following items may also be ordered separately:  
1 − Thermostat  
NOTE − In Direct Vent installations, combustion air is taken  
from outdoors and flue gases are discharged outdoors. In  
Non−Direct Vent installations, combustion air is taken from  
indoors and flue gases are discharged outdoors. See figure  
2 for applications involving roof termination.  
1 − Propane/LP changeover kit  
DANGER  
Danger of explosion.  
DIRECT VENT INSTALLATION  
COMBUSTION  
NON−DIRECT VENT  
INSTALLATION  
There are circumstances in which odorant used with  
LP/propane gas can lose its scent. In case of a leak,  
LP/propane gas will settle close to the floor and may  
be difficult to smell. An LP/propane leak detector  
should be installed in all LP applications.  
EXHAUST  
AIR INTAKE  
OUTLET  
EXHAUST  
OUTLET  
OUTSIDE OF  
HOUSE  
COMBUSTION  
AIR INTAKE INSIDE  
OF HOUSE  
Safety Information  
WARNING  
Improper installation, adjustment, alteration, service  
or maintenance can cause property damage, person-  
al injury or loss of life. Installation and service must  
be performed by a licensed professional installer (or  
equivalent), service agency or the gas supplier.  
G61MP  
G61MP  
CONDENSATE  
DRAIN  
CONDENSATE  
DRAIN  
FIGURE 2  
CAUTION  
Shipping and Packing List  
As with any mechanical equipment, personal injury  
can result from contact with sharp sheet metal  
edges. Be careful when you handle this equipment.  
Package 1 of 1 contains  
1 − Assembled G61MP unit  
1 − Bag assembly containing the following:  
3 Screws  
Use only the type of gas approved for use with this furnace.  
Refer to unit nameplate.  
3 Wire nuts  
G61MP units are CSA International certified to ANSI  
Z21.47 and CSA 2.3 standards.  
1 Snap bushing  
1 Snap plug  
In the USA, installation of gas furnaces must conform with lo-  
cal building codes. In the absence of local codes, units must  
be installed according to the current National Fuel Gas Code  
(ANSI-Z223.1/NFPA 54). The National Fuel Gas Code is  
available from the following address:  
1 − Wire tie  
1 Condensate trap  
1 Condensate trap cap  
2 2" diameter vent / intake plugs  
1 3" diameter cabinet plug (intake)  
1 2" diameter debris screen  
1 Logo sticker (for use in downflow applications)  
American National Standards Institute, Inc.  
11 West 42nd Street  
New York, NY 10036  
Page 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
In Canada, installation must conform with current National  
Standard of Canada CSA-B149 Natural Gas and Propane  
Installation Codes, local plumbing or waste water codes  
and other applicable local codes.  
When installed, this furnace must be electrically grounded  
according to local codes. In addition, in the United States,  
installation must conform with the current National Electric  
Code, ANSI/NFPA No. 70. The National Electric Code  
(ANSI/NFPA No. 70) is available from the following ad-  
dress:  
In order to ensure proper unit operation in non−direct vent  
applications, combustion and ventilation air supply must be  
provided according to the current National Fuel Gas Code  
or CSA-B149 standard.  
National Fire Protection Association  
1 Battery March Park  
Quincy, MA 02269  
This furnace is CSA International certified for installation  
clearances to combustible material as listed on the unit  
nameplate and in the tables in figures 8, 13 and 17. Accessi-  
bility and service clearances must take precedence over fire  
protection clearances.  
In Canada, all electrical wiring and grounding for the unit  
must be installed according to the current regulations of the  
Canadian Electrical Code Part I (CSA Standard C22.1)  
and/or local codes.  
NOTE − This furnace is designed for a minimum continu-  
ous return air temperature of 60°F (16°C) or an intermit-  
tent operation down to 55°F (13°C) dry bulb for cases  
where a night setback thermostat is used. Return air tem-  
perature must not exceed 85°F (29°C) dry bulb.  
NOTE − For installation on combustible floors, the furnace  
shall not be installed directly on carpeting, tile, or other  
combustible material other than wood flooring.  
For installation in a residential garage, the furnace must  
be installed so that the burner(s) and the ignition source  
are located no less than 18 inches (457 mm) above the  
floor. The furnace must be located or protected to avoid  
physical damage by vehicles. When a furnace is installed  
in apublic garage, hangar, or other building that has a haz-  
ardous atmosphere, the furnace must be installed accord-  
ing to recommended good practice requirements and cur-  
rent National Fuel Gas Code or CSA B149 standard.  
The G61MP furnace may be installed in alcoves, closets,  
attics, basements, garages, and utility rooms.  
This furnace design has not been CSA certified for installa-  
tion in mobile homes, recreational vehicles, or outdoors.  
Never use an open flame to test for gas leaks. Check all  
connections using a commercially available soap solution  
made specifically for leak detection.  
Use of Furnace as Construction Heater  
NOTE − Furnace must be adjusted to obtain a temperature  
rise within the range specified on the unit nameplate. Failure  
to do so may cause erratic limit operation.  
Lennox does not recommend the use of G61MP units as a  
construction heater during any phase of construction. Very  
low return air temperatures, harmful vapors and operation  
of the unit with clogged or misplaced filters will damage the  
unit.  
This G61MP furnace may be used as a high−static unit  
heater. The G61MP may also be installed in an aircraft han-  
gar in accordance with the Standard for Aircraft Hangars  
(ANSI/NFPA No. 408−1990).  
G61MP units may be used for heating of buildings or struc-  
tures under construction, if the following conditions are  
met:  
Installation in parking structures must be in accordance  
with the Standard for Parking Structures (ANSI/NFPA No.  
88A−1991). Installation in repair garages must be in accor-  
dance with the Standard for Repair Garages (ANSI/NFPA  
No. 88B−1991).  
D The vent system must be permanently installed per  
these installation instructions.  
D A room thermostat must control the furnace. The use of  
fixed jumpers that will provide continuous heating is not  
allowed.  
This G61MP furnace must be installed so that its electrical  
components are protected from water.  
D The return air duct must be provided and sealed to the  
furnace.  
When this furnace is used with cooling units, it shall be  
installed in parallel with, or on the upstream side of, cooling  
units to avoid condensation in the heating compartment.  
With a parallel flow arrangement, a damper (or other means  
to control the flow of air) must adequately prevent chilled air  
from entering the furnace. If the damper is manually oper-  
ated, it must be equipped to prevent operation of either the  
heating or the cooling unit, unless it is in the full HEAT or  
COOL setting.  
D Return air temperature range between 60°F (16°C) and  
80°F (27°C) must be maintained.  
D Air filters must be installed in the system and must be  
maintained during construction.  
D Air filters must be replaced upon construction comple-  
tion.  
D The input rate and temperature rise must be set per the  
furnace rating plate.  
Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
D One hundred percent (100%) outdoor air must be pro-  
vided for combustion air requirements during construc-  
tion. Temporary ducting may supply outdoor air to the  
furnace. Do not connect duct directly to the furnace.  
Size the temporary duct following these instructions in  
section for Combustion, Dilution and Ventilation Air in a  
confined space with air from outside.  
CAUTION  
G61MP unit should not be installed in areas normally  
subject to freezing temperatures.  
Combustion, Dilution & Ventilation Air  
D The furnace heat exchanger, components, duct system,  
air filters and evaporator coils must be thoroughly  
cleaned following final construction clean−up.  
If the G61MP is installed as a Non−Direct Vent Fur-  
nace, follow the guidelines in this section.  
NOTE − In Non−Direct Vent installations, combustion air  
is taken from indoors and flue gases are discharged out−  
doors.  
D All furnace operating conditions (including ignition, in-  
put rate, temperature rise and venting) must be verified  
according to these installation instructions.  
General  
WARNING  
These instructions are intended as a general guide and do  
not supersede local codes in any way. Consult authorities  
having jurisdiction before installation.  
Insufficient combustion air can cause headaches,  
nausea, dizziness or asphyxiation. It will also cause  
excess water in the heat exchanger resulting in rust-  
ing and premature heat exchanger failure. Excessive  
exposure to contaminated combustion air will result  
in safety and performance related problems. Avoid  
exposure to the following substances in the com-  
bustion air supply:  
In addition to the requirements outlined previously, the fol-  
lowing general recommendations must be considered  
when installing a G61MP furnace:  
Place the furnace as close to the center of the air dis-  
tribution system as possible. The furnace should also be  
located close to the chimney or vent termination point.  
Permanent wave solutions  
Chlorinated waxes and cleaners  
Chlorine base swimming pool chemicals  
Water softening chemicals  
De−icing salts or chemicals  
When the furnace is installed in non−direct vent applica-  
tions, do not install the furnace where drafts might blow  
directly into it. This could cause improper combustion  
and unsafe operation.  
Carbon tetrachloride  
Halogen type refrigerants  
Cleaning solvents (such as perchloroethylene)  
Printing inks, paint removers, varnishes, etc.  
Hydrochloric acid  
Cements and glues  
Antistatic fabric softeners for clothes dryers  
Masonry acid washing materials  
When the furnace is installed in non−direct vent applica-  
tions, do not block the furnace combustion air opening  
with clothing, boxes, doors, etc. Air is needed for proper  
combustion and safe unit operation.  
When the furnace is installed in an attic or other insu-  
lated space, keep insulation away from the furnace.  
In the past, there was no problem in bringing in sufficient  
outdoor air for combustion. Infiltration provided all the air  
that was needed. In today’s homes, tight construction  
practices make it necessary to bring in air from outside  
for combustion. Take into account that exhaust fans, ap-  
pliance vents, chimneys, and fireplaces force additional  
air that could be used for combustion out of the house.  
Unless outside air is brought into the house for combus-  
tion, negative pressure (outside pressure is greater than  
inside pressure) will build to the point that a downdraft  
can occur in the furnace vent pipe or chimney. As a result,  
combustion gases enter the living space creating a po-  
tentially dangerous situation.  
When the furnace is installed in an unconditioned  
space, consider provisions required to prevent freezing  
of condensate drain system.  
WARNING  
Product contains fiberglass wool.  
Disturbing the insulation in this product during  
installation, maintenance, or repair will expose you  
to fiberglass wool. Breathing this may cause lung  
cancer. (Fiberglass wool is known to the State of Cal-  
ifornia to cause cancer.)  
Fiberglass wool may also cause respiratory, skin,  
and eye irritation.  
In the absence of local codes concerning air for combus−  
tion and ventilation, use the guidelines and procedures in  
this section to install G61MP furnaces to ensure efficient  
and safe operation. You must consider combustion air  
needs and requirements for exhaust vents and gas pip-  
ing. A portion of this information has been reprinted with  
permission from the National Fuel Gas Code (ANSI−  
To reduce exposure to this substance or for further  
information, consult material safety data sheets  
available from address shown below, or contact your  
supervisor.  
Lennox Industries Inc.  
P.O. Box 799900  
Dallas, TX 75379−9900  
Page 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Z223.1/NFPA 54). This reprinted material is not the com-  
plete and official position of the ANSI on the referenced  
subject, which is represented only by the standard in its  
entirety.  
which are sealed to the furnace casing and which terminate  
outside the space containing the furnace. This is especially  
important when the furnace is mounted on a platform in a  
confined space such as a closet or small equipment room.  
Even a small leak around the base of the unit at the platform  
or at the return air duct connection can cause a potentially  
dangerous negative pressure condition. Air for combustion  
and ventilation can be brought into the confined space ei-  
ther from inside the building or from outside.  
In Canada, refer to the standard CSA B149 installation  
codes.  
CAUTION  
Do not install the furnace in a corrosive or contami-  
nated atmosphere. Meet all combustion and ventila-  
tion air requirements, as well as all local codes.  
Air from Inside  
If the confined space that houses the furnace adjoins a  
space categorized as unconfined, air can be brought in by  
providing two permanent openings between the two  
spaces. Each opening must have a minimum free area of 1  
All gas-fired appliances require air for the combustion pro-  
cess. If sufficient combustion air is not available, the fur-  
nace or other appliance will operate inefficiently and un-  
safely. Enough air must be provided to meet the needs of all  
fuel−burning appliances and appliances such as exhaust  
fans which force air out of the house. When fireplaces, ex-  
haust fans, or clothes dryers are used at the same time as  
the furnace, much more air is required to ensure proper  
combustion and to prevent a downdraft. Insufficient air  
causes incomplete combustion which can result in carbon  
monoxide.  
2
square inch (645 mm ) per 1,000 Btu (.29 kW) per hour of  
total input rating of all gas−fired equipment in the confined  
space. Each opening must be at least 100 square inches  
2
(64516 mm ). One opening shall be within 12 inches (305  
mm) of the top of the enclosure and one opening within 12  
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM INSIDE  
ROOF TERMINATED  
EXHAUST PIPE  
In addition to providing combustion air, fresh outdoor air di-  
lutes contaminants in the indoor air. These contaminants  
may include bleaches, adhesives, detergents, solvents  
and other contaminants which can corrode furnace compo-  
nents.  
The requirements for providing air for combustion and ven-  
tilation depend largely on whether the furnace is installed in  
an unconfined or a confined space.  
OPENINGS  
(To Adjacent  
SIDE WALL  
Unconfined  
TERMINATED EX-  
Space)  
HAUST PIPE (ALTER-  
NATE LOCATION)  
G61MP  
Unconfined Space  
An unconfined space is an area such as a basement or  
large equipment room with a volume greater than 50 cubic  
NOTE − Each opening shall have a free area of at least one square  
2
3
feet (1.42 m ) per 1,000 Btu (.29 kW) per hour of the com-  
inch per 1,000 Btu (645mm per .29kW) per hour of the total input  
rating of all equipment in the enclosure, but not less than 100 square  
2).  
inches (64516mm.  
bined input rating of all appliances installed in that space.  
This space also includes adjacent rooms which are not  
separated by a door. Though an area may appear to be un-  
confined, it might be necessary to bring in outdoor air for  
combustion if the structure does not provide enough air by  
infiltration. If the furnace is located in a building of tight  
construction with weather stripping and caulking around  
the windows and doors, follow the procedures in the air  
from outside section.  
FIGURE 3  
Air from Outside  
If air from outside is brought in for combustion and ventila-  
tion, the confined space shall be provided with two perma-  
nent openings. One opening shall be within 12" (305mm)  
of the top of the enclosure and one within 12" (305mm) of  
the bottom. These openings must communicate directly  
or by ducts with the outdoors or spaces (crawl or attic) that  
freely communicate with the outdoors or indirectly  
through vertical ducts. Each opening shall have a mini-  
Confined Space  
A confined space is an area with a volume less than 50 cubic  
3
2
mum free area of 1 square inch per 4,000 Btu (645mm  
feet (1.42 m ) per 1,000 Btu (.29 kW) per hour of the com−  
per 1.17kW) per hour of total input rating of all equipment  
in the enclosure. When communicating with the outdoors  
through horizontal ducts, each opening shall have a mini-  
mum free area of 1 square inch per 2,000 Btu (645mm  
per .59kW) per total input rating of all equipment in the en-  
closure (See figure 4).  
bined input rating of all appliances installed in that space. This  
definition includes furnace closets or small equipment rooms.  
When the furnace is installed so that supply ducts carry air  
circulated by the furnace to areas outside the space con-  
taining the furnace, the return air must be handled by ducts  
2
Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
in the enclosure. See figures 4 and 5. When communicat-  
ing with the outdoors through horizontal ducts, each open-  
ing shall have a minimum free area of 1 square inch (645  
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE  
(Inlet Air from Crawl Space and Outlet Air to Ventilated Attic)  
VENTILATION LOUVERS  
(Each end of attic)  
2
mm ) per 2,000 Btu (.56 kW) per total input rating of all  
ROOF TERMINATED  
EXHAUST PIPE  
equipment in the enclosure. See figure 6.  
When ducts are used, they shall be of the same cross−sec-  
tional area as the free area of the openings to which they  
connect. The minimum dimension of rectangular air ducts  
shall be no less than 3 inches (75 mm). In calculating free  
area, the blocking effect of louvers, grilles, or screens  
must be considered. If the design and free area of protec-  
tive covering is not known for calculating the size opening  
required, it may be assumed that wood louvers will have  
20 to 25 percent free area and metal louvers and grilles  
will have 60 to 75 percent free area. Louvers and grilles  
must be fixed in the open position or interlocked with the  
equipment so that they are opened automatically during  
equipment operation.  
OUTLET  
AIR  
SIDE WALL  
TERMINATED  
EXHAUST PIPE  
(ALTERNATE  
LOCATION)  
VENTILATION  
LOUVERS  
(For unheated  
crawl space)  
G61MP  
INLET  
AIR  
NOTE−The inlet and outlet air openings shall each have a free area  
2
of at least one square inch per 4,000 Btu (645mm per 1.17kW) per  
hour of the total input rating of all equipment in the enclosure.  
EQUIPMENT IN CONFINED SPACE −  
ALL AIR FROM OUTSIDE  
FIGURE 4  
ROOF TERMINATED  
EXHAUST PIPE  
OUTLET AIR  
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE  
(All Air Through Ventilated Attic)  
SIDE WALL  
TERMINATED  
EXHAUST PIPE  
(ALTERNATE  
LOCATION)  
ROOF TERMINATED  
EXHAUST PIPE  
VENTILATION LOUVERS  
(Each end of attic)  
G61MP  
INLET AIR  
OUTLET  
AIR  
NOTE−Each air duct opening shall have a free area of at least one  
2
square inch per 2,000 Btu (645mm per .59kW) per hour of the total  
input rating of all equipment in the enclosure. If the equipment room  
is located against an outside wall and the air openings communi-  
cate directly with the outdoors, each opening shall have a free area  
of at least 1 square inch per 4,000 Btu (645mm per 1.17kW) per  
hour of the total input rating of all other equipment in the enclosure.  
INLET AIR  
(Ends 12" above  
bottom)  
SIDE WALL  
TERMINATED  
EXHAUST PIPE  
(ALTERNATE  
LOCATION)  
2
G61MP  
FIGURE 6  
NOTE−The inlet and outlet air openings shall each have a free area of  
2
at least one square inch per 4,000 Btu (645mm per 1.17kW) per hour  
of the total input rating of all equipment in the enclosure.  
Installation − Setting Equipment  
WARNING  
FIGURE 5  
Do not install the furnace on its front or its back. Do  
not connect the return air ducts to the back of the fur-  
nace. Doing so will adversely affect the operation of  
the safety control devices, which could result in per-  
sonal injury or death.  
If air from outside is brought in for combustion and ventila-  
tion, the confined space must have two permanent open-  
ings. One opening shall be within 12 inches (305 mm) of  
the top of the enclosure and one opening within 12 inches  
(305 mm) of the bottom. These openings must communi-  
cate directly or by ducts with the outdoors or spaces (crawl  
or attic) that freely communicate with the outdoors or indi-  
rectly through vertical ducts. Each opening shall have a  
Select a location that allows for the required clearances  
that are listed on the unit nameplate. Also consider gas  
supply connections, electrical supply, vent connection,  
condensate trap and drain connections, and installation  
and service clearances [24 inches (610 mm) at unit  
front].  
2
minimum free area of 1 square inch (645 mm ) per 4,000  
Btu (1.17 kW) per hour of total input rating of all equipment  
Page 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SETTING EQUIPMENT  
UPFLOW APPLICATION  
DOWNFLOW APPLICATION  
UNIT MUST BE LEVEL SIDE−TO−SIDE IN ALL APPLICATIONS.  
AIR FLOW  
HORIZONTAL APPLICATION  
AIR FLOW  
AIR FLOW  
FRONT VIEW  
FRONT VIEW  
FRONT VIEW  
AIR FLOW  
UNIT  
FRONT  
UNIT  
FRONT  
UNIT  
FRONT  
1/2"  
max.  
AIR FLOW  
END VIEW  
1/2"  
max.  
1/2"  
max.  
UNIT SHOULD BE LEVEL FROM LEFT TO RIGHT BUT MAY BE  
TILTED SLIGHTLY (MAX. 1/2") FROM BACK TO FRONT  
TO AID IN THE DRAINING OF THE HEAT EXCHANGER.  
SIDE VIEW  
SIDE VIEW  
FIGURE 7  
The unit must be level from side to side. The unit may be  
tilted slightly (maximum 1/2 in.) from back to front to aid  
in the draining of the heat exchanger. See figure 7.  
Allow for clearances to combustible materials as indicated  
on the unit nameplate. Minimum clearances for closet or al-  
cove installations are shown in figures 8, 13 and 17.  
NOTE − Units with 1/2 hp blower motors are equipped with  
three flexible legs and one rigid leg. The rigid leg is  
equipped with a shipping bolt and a flat white plastic wash-  
er (rather than the rubber mounting grommet used with a  
flexible mounting leg). The bolt and washer must be re-  
moved before the furnace is placed into operation. Af-  
ter the bolt and washer have been removed, the rigid leg  
will not touch the blower housing.  
WARNING  
Improper installation of the furnace can result in per-  
sonal injury or death. Combustion and flue products  
must never be allowed to enter the return air system  
or air in the living space. Use sheet metal screws and  
joint tape to seal return air system to furnace.  
In platform installations with furnace return, the fur-  
nace should be sealed airtight to the return air ple-  
num. A door must never be used as a portion of the  
return air duct system. The base must provide a  
stable support and an airtight seal to the furnace. Al-  
low absolutely no sagging, cracks, gaps, etc.  
For no reason should return and supply air duct sys-  
tems ever be connected to or from other heating de-  
vices such as a fireplace or stove, etc. Fire, explo-  
sion, carbon monoxide poisoning, personal injury  
and/or property damage could result.  
WARNING  
Blower access panel must be securely in place when  
blower and burners are operating. Gas fumes, which  
could contain carbon monoxide, can be drawn into  
living space resulting in personal injury or death.  
Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Return Air −− Upflow Units  
Upflow Applications  
Return air can be brought in through the bottom or either  
side of the furnace installed in an upflow application. If the  
furnace is installed on a platform with bottom return, make  
an airtight seal between the bottom of the furnace and the  
platform to ensure that the furnace operates properly and  
safely. The furnace is equipped with a removable bottom  
panel to facilitate installation.  
The G61MP gas furnace can be installed as shipped in  
the upflow position. Refer to figure 8 for clearances.  
Installation Clearances  
Top  
Markings are provided on both sides of the furnace cabinet  
for installations that require side return air. Cut the furnace  
cabinet at the maximum dimensions shown on page 2.  
Left Side  
Right Side  
NOTE − When air volumes over 1800 cfm (850 L/s) are  
required with 60C or 60D models in an upflow applica-  
tion, the following return air options are available:  
Bottom (Floor)  
1 − Return air from single side with transition which will  
accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter.  
(Required to maintain proper air velocity.) See figure 10.  
Top/Plenum  
*Front  
Back  
1 in. (25 mm)  
0
0
2 − Return air from single side with optional RAB Return  
3 − Return air from bottom.  
Sides  
0†  
0
4 − Return air from both sides.  
Vent  
5 − Return air from bottom and one side.  
Refer to Engineering Handbook for additional information.  
Floor  
0‡  
*Front clearance in alcove installation must be 24 in. (610 mm).  
Maintain a minimum of 24 in. (610 mm) for front service access.  
Allow proper clearances to accommodate condensate trap and  
vent pipe installation.  
For installations on a combustible floor, do not install the furnace  
directly on carpeting, tile or other combustible materials other  
than wood flooring.  
FIGURE 8  
Page 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Optional Return Air Base  
(Upflow Applications Only −− For use with B, C and D cabinets only)  
1
23 (584)  
Overall  
(Maximum)  
4
(102)  
1
Minimum  
11 (279)  
Maximum  
14 (356)  
14  
(356)  
1
2
22−7−16  
(570)  
Overall  
1
Unit side return air  
Opening  
AIR FLOW  
FURNACE  
FRONT  
(Maximum)  
SIDE RETURN  
AIR OPENINGS  
(Either Side)  
5−5/8  
(143)  
7−1/4 (184)  
3/4  
(19)  
23 (584)  
OPTIONAL RAB  
RETURN AIR BASE  
17−1/2 (446) RAB−B (98M60)  
21 (533) RAB−C (98M58)  
24−1/2 (622) RAB−D (98M59)  
FRONT VIEW  
7/8  
(22)  
27−5/8 (702)  
SIDE VIEW  
NOTE− Optional Side Return Air Filter Kits are not for use with RAB Return Air Base.  
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.  
Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in.  
(584 x 279 mm).  
The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.  
Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return  
air opening. The size of the opening must not extend beyond the markings on the furnace cabinet.  
To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.  
2
NOTE− Optional Side Return Air Filter Kits are not for use with RAB Return Air Base.  
FIGURE 9  
G61MP applications which include side return air and  
a condensate trap installed on the same side of the  
cabinet require either a return air base or field−fabri-  
cated transition to accommodate an optional IAQ ac-  
cessory taller than 14.2".  
Removing the Bottom Panel  
Remove the two screws that secure the bottom cap to the  
furnace. Pivot the bottom cap down to release the bottom  
panel. Once the bottom panel has been removed, reinstall  
Removing the Bottom Panel  
Side Return Air  
(with transition and filter)  
20" X 25" X 1"  
(508mm X635mm X 25mm)  
Air Filter  
Screw  
Return  
Air  
Plenum  
Bottom Cap  
Bottom Panel  
Transition  
FIGURE 10  
FIGURE 11  
Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Setting an Upflow Unit  
Refer to figure 13 for clearances in downflow applica-  
tions.  
When the side return air inlets are used in an upflow ap-  
plication, it may be necessary to install leveling bolts on the  
bottom of the furnace. Use field−supplied corrosion−resist-  
ant 5/16 inch machine bolts (4) and nuts (8). See figure 12.  
Downflow Application Installation Clearances  
Top  
NOTE − The maximum length of the bolt is 1−1/2 inches.  
1 − Lie the furnace on its back and drill a 5/16 inch diame-  
ter hole in each corner of the furnace’s bottom. See fig-  
ure 12 for the correct location of the holes. Drill through  
the bottom panel and the bottom flange of the cabinet.  
2 − Install one bolt and two nuts into each hole. Screw the  
first nut onto a bolt and then insert the bolt into a hole. A  
flat washer may be added between the nut and the bot-  
tom of the unit.  
Left Side  
Right Side  
Bottom  
3 − Screw another nut onto the bolt on the inside of the fur-  
nace base. A flat washer may be added between the  
nut and the bottom of the unit.  
Top  
*Front  
Back  
Sides  
Vent  
0
0
4 − Adjust the outside nut to the appropriate height and  
tighten the inside nut to secure the arrangement.  
0
0†  
0
NOTE − The unit may be tilted back−to−front a maximum of  
1". This will ensure proper draining of the heat exchanger.  
Floor  
NC‡  
Leveling Bolt Installation  
*Front clearance in alcove installation must be 24 in. (610 mm).  
Maintain a minimum of 24 in. (610 mm) for front service access.  
†Allow proper clearances to accommodate condensate trap and  
vent pipe installation.  
Inches (mm)  
3/8  
(10)  
Furnace Front  
The furnace may be installed on a combustible wood floor if an op-  
tional additive base is installed between the furnace and the com-  
bustible floor.  
1−3/4  
(44)  
3/8  
(10)  
FIGURE 13  
Installation on Non−Combustible Flooring  
1−3/4  
(44)  
1 − Cut floor opening keeping in mind clearances listed on  
unit rating plate. Also keep in mind gas supply connec-  
tions, electrical supply, flue and air intake connections  
and sufficient installation and servicing clearances.  
See table 1 for correct floor opening size.  
2 − Flange warm air plenum and lower the plenum into the  
opening.  
Leveling Bolt  
Locations  
Furnace  
Bottom  
3/8  
(10)  
Leveling Bolt  
Locations  
3 − Set the unit over the plenum and seal the plenum to  
the unit.  
3/8  
(10)  
1−3/4  
(44)  
4 − Ensure that the seal is adequate.  
1−3/4 (44)  
NON−COMBUSTIBLE FLOOR OPENING SIZE  
FIGURE 12  
Front to Rear  
Side to Side  
Downflow Applications  
Model No.  
in.  
mm  
502  
502  
502  
in.  
mm  
422  
511  
600  
The unit may be installed three ways in downflow applica-  
tions: on non−combustible flooring, on combustible flooring  
using an additive base, or on a reverse−flow cooling cabi-  
net. Do not drag the unit across the floor in the down-  
flow position. Flange damage will result.  
B Cabinet (17.5")  
C Cabinet (21")  
D Cabinet (24.5")  
19 − 3/4  
19 − 3/4  
19 − 3/4  
16 − 5/8  
20−1/8  
23 − 5/8  
After unit has been properly set in place, position provided  
logo over existing logo and affix sticker on front panel.  
NOTE − Floor opening dimensions listed are 1/4 inch (6 mm) larger than  
the unit opening. See dimension drawing on page 2.  
Page 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation on Combustible Flooring  
(Using an Additive Base)  
Installation on Cooling Coil Cabinet  
1 − Refer to reverse−flow coil installation instructions for  
correctly sized opening in floor and installation of cabi-  
net.  
1 − When unit is installed on a combustible floor, an addi-  
tive base must be installed between the furnace and  
the floor. The base must be ordered separately. See  
table 2 for opening size to cut in floor.  
2 − When cooling cabinet is in place, set and secure the  
furnace according to the instructions that are provided  
with the cooling coil. Secure the furnace to the cabinet.  
CAUTION  
The furnace and additive base shall not be installed  
directly on carpeting, tile, or other combustible ma-  
terial other than wood flooring.  
3 − Seal the cabinet and check for air leaks.  
Return Air Opening −− Downflow Units  
Return air may be brought in only through the top opening  
of a furnace installed in the downflow position.The follow-  
ing steps should be taken when installing plenum:  
ADDITIVE BASE FLOOR OPENING SIZE  
Front to Rear  
Side to Side  
Cabinet  
Width  
Catalog  
Number  
1 − Bottom edge of plenum should be flanged with a  
in.  
22  
mm  
559  
in.  
mm  
476  
B Cabinet  
(17.5")  
11M60  
11M61  
11M62  
18 − 3/4  
2 − Sealing strips should be used to ensure an airtight seal  
between the cabinet and the plenum.  
C Cabinet  
(21")  
22  
22  
559  
559  
22 − 3/4  
25 − 3/4  
578  
654  
3 − In all cases, plenum should be secured to top of fur-  
nace using sheet metal screws.  
D Cabinet  
(24.5")  
4 − Make certain that an adequate seal is made.  
2 − After opening is cut, set additive base into opening.  
3 − Check fiberglass strips on additive base to make sure  
they are properly glued and positioned.  
PLENUM  
4 − Lower supply air plenum into additive base until ple-  
num flanges seal against fiberglass strips.  
SECURE FROM  
(Field Provided)  
OUTSIDE CABINET  
CABINET  
NOTE − Be careful not to damage fiberglass strips.  
Check for a tight seal.  
5 − Set the furnace over the plenum.  
SEALING STRIP  
SIDE PANEL  
6 − Ensure that the seal between the furnace and plenum  
is adequate.  
(Field Provided)  
Side View  
FIGURE 15  
G61MP UNIT  
PLENUM  
SUPPLY AIR PLENUM  
(Field Provided)  
SEALING STRIP  
PROPERLY  
SIZED FLOOR  
OPENING  
(Field Provided)  
ADDITIVE BASE  
CABINET  
SIDE PANEL  
SECURE FROM  
INSIDE CABINET  
Side View  
FIGURE 16  
FIGURE 14  
Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3 − If unit is installed above finished space, fabricate a  
drain pan fitted with a 1/2 inch or 3/4 inch N.P.T. fitting.  
Horizontal Applications  
The G61MP furnace can be installed in horizontal applica-  
tions with either right− or left−hand air discharge.  
4 − Using 3/8 inch rods and support frame kit or field−fabri-  
cated supports, fabricate suspension hangers, keep-  
ing in mind front service access clearances.  
The G61MP may also be installed as a unit heater. Either  
suspend the furnace as shown in figure 18, or install the  
furnace on a field−fabricated raised platform. The unit  
must be supported at both ends and beneath the blower  
deck to prevent sagging.  
6 − Continue with exhaust, condensate and intake line  
piping instructions.  
Refer to figure 17 for clearances in horizontal applications.  
7 − If unit is suspended above finished space, hang the  
field−provided drain pan below the support frame as  
shown in figure 18. Leave 5−1/2 inches for service  
clearance below unit for condensate trap.  
Horizontal Application  
Installation Clearances  
Right−Hand Discharge  
Top  
8 − Route auxiliary drain line so that water draining from  
this outlet will be easily noticed by the homeowner. If  
necessary, run the condensate line into a condensate  
pump to meet drain line slope requirements. The  
pump must be rated for use with condensing furnaces.  
Protect the condensate discharge line from the pump  
to the outside to avoid freezing.  
Left End  
Right End  
Bottom (Floor)**  
Left−Hand Discharge  
Top  
TYPICAL HORIZONTAL CEILING APPLICATION  
BLOWER ACCESS PANEL  
3/8 in. RODS  
Left End  
Right End  
INTAKE/EXHAUST  
CONNECTION  
Bottom (Floor)**  
Top  
0
0
0
0
0
Front*  
Back  
Ends  
Vent  
Floor  
0‡  
DRAIN PAN  
(to protect finished space)  
*Front clearance in alcove installation must be 24 in. (610 mm).  
Maintain a minimum of 24 in. (610 mm) for front service access.  
**A 5−1/2ꢀ service clearance must be maintained below the unit to  
provide for servicing of the condensate trap.  
SUPPORT FRAME  
FIGURE 18  
For installations on a combustible floor, do not install the furnace  
directly on carpeting, tile or other combustible materials other  
than wood flooring.  
Platform Installation of Horizontal Unit  
1 − Select location for unit keeping in mind service and  
FIGURE 17  
Suspended Installation of Horizontal Unit  
2 − Construct a raised wooden frame and cover frame  
with a plywood sheet. Provide a service platform in  
front of unit. If unit is installed above finished space,  
fabricate a drain pan to be installed under unit.  
NOTE − If unit is suspended in attic or crawl space, horizon-  
tal support kit (Cat No. 56J18 ordered separately) must be  
used to ensure proper unit support and coil drainage.  
1 − Select location for unit keeping in mind service and  
When installing the unit in a crawl space, a proper sup-  
port platform may be created using cement blocks and  
the horizontal support frame kit (ordered separately,  
2 − Provide service platform in front of unit.  
Page 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Lennox part number 56J18). Position the support  
frame on top of the blocks and install the unit on the  
frame. Leave 5−1/2 inches for service clearance for  
condensate trap.  
Unit Heater Discharge Duct Guidelines  
A field−fabricated and installed discharge air duct and grille  
cabinet is suitable for use with the G61MP heater. Keep the  
following items in mind when constructing the cabinet.  
1 − Outer dimensions of cabinet should match those of the  
unit heater, so the duct/grille cabinet installs flush with  
3 − Route auxiliary drain line so that water draining from  
this outlet will be easily noticed by the homeowner. If  
necessary, run the condensate line into a condensate  
pump to meet drain line slope requirements. The  
pump must be rated for use with condensing furnaces.  
Protect the condensate discharge line from the pump  
to the outside to avoid freezing.  
2 − Flange both ends of duct/grille cabinet so that screws  
can be used to secure cabinet to discharge end of unit  
heater.  
3 − To ensure proper operation, the duct/grille cabinet  
must be at least 18 inches long.  
4 − Set unit in drain pan as shown in figure 19. Leave 5−1/2  
inches for service clearance below unit for condensate  
trap.  
4 − Use #10−16 x 1/2 inch sheet metal screws to secure  
duct/grille cabinet to unit, taking care not to damage in-  
ternal components of unit heater when drilling holes or  
installing screws. See figure 20.  
5 − Continue with exhaust, condensate and intake piping  
installation according to instructions.  
5 − Use adjustable, double−deflection grille(s) to distribute  
discharge air. Adjust static pressure to be in the 0.06  
inch to 0.10 inch w.c. range.  
EXHAUST PIPE  
INTAKE PIPE  
*GAS  
CONNECTOR  
*Gas connector may be  
used for Canadian  
installation if accept-  
able by local authority  
having jurisdiction.  
18 in.  
MIN.  
RAISED  
DRAIN PAN  
(to protect  
finished  
PLATFORM  
CONDENSATE LINE  
SERVICE PLATFORM  
space)  
FIGURE 19  
NOTE − When installing duct/grille cabinet, take care not to damage internal unit  
heater components when drilling holes or installing screws.  
G61MP Installed in Unit Heater Applications  
FIGURE 20  
The G61MP may also be installed as a unit heater. Either  
suspend the furnace from roof rafters or floor joists, as  
shown in figure 18, or install the furnace on a field−fabri-  
cated raised platform, as shown in figure 19. The unit must  
be supported at both ends and beneath the blower deck to  
prevent sagging. The condensate trap must be installed  
where it can be serviced at a later date.  
Return Air −− Horizontal Applications  
Return air may be brought in only through the end of a fur-  
nace installed in the horizontal position. The furnace is  
equipped with a removable bottom panel to facilitate  
installation. See figure 11.  
Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Filters  
Pipe & Fittings Specifications  
This unit is not equipped with a filter or rack. A field−pro-  
vided filter is required for the unit to operate properly. Table  
3 lists recommended filter sizes.  
All pipe, fittings, primer and solvent cement must conform  
with American National Standard Institute and the Ameri-  
can Society for Testing and Materials (ANSI/ASTM) stan-  
dards. The solvent shall be free flowing and contain no  
lumps, undissolved particles or any foreign matter that ad-  
versely affects the joint strength or chemical resistance of  
the cement. The cement shall show no gelation, stratifica-  
tion, or separation that cannot be removed by stirring. Re-  
A filter must be in place whenever the unit is operating.  
TABLE 3  
Filter Size  
Furnace  
Cabinet Width  
Side Return  
Bottom Return  
16 X 25 X 1 (1)  
20 X 25 X 1 (1)  
24 X 25 X 1 (1)  
17−1/2"  
21"  
16 X 25 X 1 (1)  
16 X 25 X 1 (1)  
16 X 25 X 1 (2)  
24−1/2"  
CAUTION  
Duct System  
Solvent cements for plastic pipe are flammable liq-  
uids and should be kept away from all sources of  
ignition. Do not use excessive amounts of solvent  
cement when making joints. Good ventilation should  
be maintained to reduce fire hazard and to minimize  
breathing of solvent vapors. Avoid contact of cement  
with skin and eyes.  
Use industry-approved standards to size and install the  
supply and return air duct system. This will result in a quiet  
and low-static system that has uniform air distribution.  
NOTE − Operation of this furnace in heating mode (indoor  
blower operating at selected heating speed) with an exter-  
nal static pressure which exceeds 0.5 inches w.c. may re-  
sult in erratic limit operation.  
TABLE 4  
PIPING AND FITTINGS SPECIFICATIONS  
Supply Air Plenum  
ASTM  
PIPE & FITTING MATERIAL  
If the furnace is installed without a cooling coil, a removable  
access panel should be installed in the supply air duct. The  
access panel should be large enough to permit inspection  
(by reflected light) of the heat exchanger for leaks after the  
furnace is installed. If present, this access panel must al-  
ways be in place when the furnace is operating and it must  
not allow leaks into the supply air duct system.  
SPECIFICATION  
Schedule 40 PVC (Pipe)  
D1785  
F891  
Schedule 40 PVC (Cellular Core Pipe)  
Schedule 40 PVC (Fittings)  
D2466  
F441  
Schedule 40 CPVC (Pipe)  
Schedule 40 CPVC (Fittings)  
SDR−21 PVC or SDR−26 PVC (Pipe)  
SDR−21 CPVC or SDR−26 CPVC (Pipe)  
Schedule 40 ABS Cellular Core DWV (Pipe)  
Schedule 40 ABS (Pipe)  
F438  
D2241  
F442  
Return Air Plenum  
F628  
NOTE − Return air must not be drawn from a room  
where this furnace, or any other gas−fueled ap-  
pliance (i.e., water heater), or carbon monoxide−  
producing device (i.e., wood fireplace) is installed.  
D1527  
D2468  
Schedule 40 ABS (Fittings)  
ABS−DWV (Drain Waste & Vent)  
(Pipe & Fittings)  
D2661  
D2665  
When return air is drawn from a room, a negative pres-  
sure is created in the room. If a gas appliance is operating  
in a room with negative pressure, the flue products can  
be pulled back down the vent pipe and into the room. This  
reverse flow of the flue gas may result in incomplete com-  
bustion and the formation of carbon monoxide gas. This  
toxic gas might then be distributed throughout the house  
by the furnace duct system.  
PVC−DWV (Drain Waste & Vent)  
Pipe & Fittings)  
ASTM  
SPECIFICATION  
PRIMER & SOLVENT CEMENT  
PVC & CPVC Primer  
PVC Solvent Cement  
CPVC Solvent Cement  
ABS Solvent Cement  
F656  
D2564  
F493  
D2235  
PVC/CPVC/ABS All Purpose Cement For Fit-  
tings & Pipe of the same material  
D2564, D2235,  
F493  
Return air can be brought in through the bottom or either  
side of the furnace. If a furnace with bottom return air is  
installed on a platform, make an airtight seal between the  
bottom of the furnace and the platform to ensure that the  
unit operates properly and safely. Use fiberglass sealing  
strips, caulking, or equivalent sealing method between the  
plenum and the furnace cabinet to ensure a tight seal. If a  
filter is installed, size the return air duct to fit the filter frame.  
ABS to PVC or CPVC Transition Solvent  
Cement  
D3138  
CANADA PIPE & FITTING & SOLVENT  
CEMENT  
MARKING  
PVC & CPVC Pipe and Fittings  
PVC & CPVC Solvent Cement  
ULCS636  
ABS to PVC or CPVC Transition Cement  
Page 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Use PVC primer and solvent cement or ABS solvent cement  
meeting ASTM specifications, refer to Table 4. As an alter-  
nate, use all purpose cement, to bond ABS, PVC, or CPVC  
pipe when using fittings and pipe made of the same materi-  
als. Use transition solvent cement when bonding ABS to ei-  
ther PVC or CPVC.  
Canadian Applications Only − Pipe, fittings, primer  
and solvent cement used to vent (exhaust) this ap-  
pliance must be certified to ULC S636 and supplied by a  
single manufacturer as part of an approved vent (ex-  
haust) system. When bonding the vent system to the fur-  
nace, use ULC S636 approved One−Step Transition Ce-  
ment to bond the pipe to the flue collar, or to bond the 90°  
elbow or reducing 90° elbow to the flue collar. In addi-  
tion, the first three feet of vent pipe from the furnace flue  
collar must be accessible for inspection.  
Low temperature solvent cement is recommended. Metal or  
plastic strapping may be used for vent pipe hangers. Uni-  
formly apply a liberal coat of PVC primer for PVC or use a  
clean dry cloth for ABS to clean inside socket surface of fit-  
ting and male end of pipe to depth of fitting socket.  
Table 5 lists the available exhaust termination kits, as well  
as vent pipe equivalencies which must be used when siz-  
ing vent pipe. All Lennox vent terminations are PVC.  
TABLE 5  
OUTDOOR TERMINATION KITS AND CORRESPONDING EQUIVALENCIES  
Vent Pipe Length Equivalency (feet)  
Outdoor Ex- Outdoor Ex-  
haust Accel- haust Accel-  
1−1/2"  
Concentric  
Kit  
VENT  
PIPE  
DIA.  
2" Con- 3" Con-  
centric Kit centric Kit  
2" Wall Plate 3" Wall Plate  
Kit  
2" Wall  
Ring Kit  
erator  
(Dia. X  
Length)  
erator  
(Dia. X  
Length)  
UNIT  
MODEL  
Kit  
(in.)  
71M80  
69M29  
60L46  
22G44  
or 44W92ꢀ or 44W92ꢀ or 44W93ꢀ or 30G28ꢀ  
44J40  
or 81J20ꢀ  
1−1/2" X 12"  
2" X 12"  
15F74  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
2
4
5
12  
15  
21  
42  
12  
15  
24  
42  
4
5
4*  
5*  
7*  
14*  
4*  
5*  
8*  
14*  
1
4
5
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
2−1/2  
36B−045  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
3
7
7
7
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
4
14  
4
14  
4
14  
4
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
2
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
2−1/2  
5
5
5
36B−070  
36B−071  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
3
8
8
8
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
4
14  
14  
14  
1**  
2**  
2**  
4**  
2
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
2
2−1/2  
3
1
2
2
4
2
2
4
3
6
3
6
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
2
48C−090  
60C−090  
60C−091  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
6
6
2
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
4
12  
6
12  
6
4
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
2−1/2  
3
2
48C−110  
60C−110  
60C−111  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
6
6
2
2
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
4
12  
12  
4
4
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
3
4
6
15  
25  
6
60D−135  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
10  
10  
*Requires field−provided and installed 1−1/2" exhaust accelerator.  
**Requires field−provided and installed 2" exhaust accelerator.  
Termination kits 44W92 (includes 1−1/2" reducer), 44W93,  
30G28 and 81J20 approved for use in Canadian installations.  
Page 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Vent Piping Guidelines  
The G61MP can be installed as either a Non−Direct Vent  
or a Direct Vent gas central furnace.  
leased from the exhaust termination. The minimum ex-  
haust vent length is 15 ft. Shorter exhaust vent lengths may  
result in the discharge of water droplets from the exhaust  
termination, in spite of the 12−inch vertical offset. See fig-  
ure 21.  
NOTE − In Non-Direct Vent installations, combustion air is  
taken from indoors and flue gases are discharged outdoors.  
In Direct Vent installations, combustion air is taken from out-  
doors and flue gases are discharged outdoors.  
Each 90° elbow (including those provided with the furnace)  
of any diameter is equivalent to 5 feet (1.52m) of vent pipe  
of the same diameter. Two 45° elbows are equivalent to  
one 90° elbow of the same diameter. One 45° elbow is  
equal to 2.5 feet (.76m) of vent pipe of the same diameter.  
Intake and exhaust pipe sizing in Direct Vent applications  
and exhaust pipe sizing in Non-Direct Vent applications −−  
Size pipe according to tables 6 and 7. Table 6 lists the mini-  
mum equivalent vent pipe lengths permitted. Table 7 lists  
the maximum equivalent pipe lengths permitted.  
In some applications which permit the use of several differ-  
ent sizes of vent pipe, a combination vent pipe may be  
used. Contact the Application Department for assistance in  
sizing vent pipe in these applications.  
Maximum vent length is defined as:  
Total length (linear feet) of pipe,  
Plus Equivalent length (feet) of fittings,  
Plus Equivalent length (feet) of termination.  
NOTE − Include ALL pipe and ALL fittings, both in  
doors and outdoors.  
NOTE − The flue collar on all models is sized to accommo-  
date 2" Schedule 40 flue pipe. When vent pipe which is  
larger than 2" must be used in an upflow application, a 2"  
elbow must be applied at the flue collar in order to proper-  
ly transition to the larger diameter flue pipe. This elbow  
must be added to the elbow count used to determine ac-  
ceptable vent lengths. Assign an equivalent feet value to  
this elbow according to the larger size pipe being used.  
Contact Lennox’ Application Department for more infor-  
mation concerning sizing of vent systems which include  
multiple pipe sizes.  
Regardless of the diameter of pipe used, the standard roof  
and wall terminations described in section Exhaust Piping  
Terminations should be used. Exhaust vent termination  
pipe is sized to optimize the velocity of the exhaust gas as  
it exits the termination. Refer to table 8.  
*NOTE − The exhaust pipe should be offset a minimum of  
12 inches to avoid the possibility of water droplets being re-  
Exhaust Pipe Offset  
12" Min.  
*12" Min.  
Upflow and Downflow Application  
Rooftop Termination  
Upflow and Downflow Application  
Side Wall Termination  
*12" Min.  
*12" Min.  
Horizontal Application  
Rooftop Termination  
Horizontal Application  
Side Wall Termination  
*A minimum of 1/4" (6mm) drop for each 12" (305mm) of horizontal run is mandatory for drainage  
FIGURE 21  
Page 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Use the following steps to correctly size vent pipe diameter.  
Refer to Vent Pipe Size Determination Worksheet on  
page 53.  
TABLE 7  
MAXIMUM VENT PIPE LENGTHS  
MAXIMUM EQUIVALENT VENT  
LENGTH FEET  
G61MP  
MODEL  
1 − Determine the vent termination and its corresponding  
equivalent feet value according to table 5.  
ALTITUDE  
2"  
PIPE  
2−1/2"  
PIPE  
3"  
PIPE  
4"  
PIPE  
2 − Determine the number of 90° elbows required for both  
indoor and outdoor (e.g. snow riser) use. Calculate the  
corresponding equivalent feet of vent pipe.  
045  
070  
59  
59  
59  
26  
26  
n/a  
n/a  
n/a  
59  
59  
59  
26  
26  
n/a  
n/a  
n/a  
59  
59  
59  
26  
26  
n/a  
n/a  
n/a  
65  
65  
65  
42  
42  
32  
32  
n/a  
65  
65  
65  
42  
42  
32  
32  
n/a  
65  
65  
65  
42  
42  
32  
32  
n/a  
77  
78  
78  
72  
72  
72  
72  
61  
77  
78  
78  
72  
72  
72  
72  
46  
77  
78  
78  
72  
72  
72  
72  
46  
234  
214  
214  
204  
204  
179  
179  
160  
234  
214  
214  
204  
204  
179  
179  
160  
234  
214  
214  
204  
204  
179  
179  
160  
071†  
090  
0 − 4500  
(0 − 1371 m)  
3 − Determine the number of 45° elbows required for both  
indoor and outdoor use. Calculate the corresponding  
equivalent feet of vent pipe.  
091†  
110*  
111*†  
135**‡  
045  
4 − Determine the length of straight pipe required.  
5 − Add the total equivalent feet calculated in steps 1  
through 4 and compare that length to the maximum  
ameter. If the total equivalent length required exceeds  
the maximum equivalent length listed in the appropri-  
ate table, evaluate the next larger size pipe.  
070  
071†  
090  
4501−7500  
(1372−2286 m)  
091†  
110*  
111*†  
135**‡  
045  
TABLE 6  
MINIMUM VENT PIPE LENGTHS  
070  
071†  
090  
G61MP  
MODEL  
MIN. EQUIV.  
VENT LENGTH  
EXAMPLE  
7501 − 10000  
(2287 − 3048 m)  
091†  
110*  
111*†  
135**‡  
045, 070,  
071, 090,  
091  
5 ft. plus 2 elbows of 2", 2−1/2", 3"  
or 4" diameter pipe  
5 ft. plus 2 elbows of 2−1/2" 3" or 4"  
diameter pipe  
15 ft.*  
n/a −− Not allowed.  
110, 111**  
135***  
*G61MP−48C−110, G61MP−60C−110 and G61MP−60C−111must have 90°  
street ell (supplied or field replacment Canadian ki) installed directly into unit  
flue collar.  
5 ft. plus 2 elbows of 3" or 4"  
diameter pipe  
**G61MP−60D−135 must have 3" to 2" reducing ell (supplied or field replacment  
Canadian ki) installed directly into unit flue collar.  
*Any approved termination may be added to the minimum equivalent length  
listed.  
***90° elbows used in configuration of G61MP−60D−135 vent, must be lim-  
ited to 3" sweep elbows.  
**G61MP−48C−110, G61MP−60C−110 and G61MP−60C−111 must have 90°  
street ell (supplied or field replacment Canadian kit) installed directly into unit  
flue collar.  
†On G61MP−071, −091 and −111 units, sweep elbows must be used for  
all 90° elbows in the venting system when 2", 2−1/2" or 3" vent pipe is  
used. Sweep elbows are recommended for use in vent systems of  
other G61MP units.  
***G61MP−60D−135 must have 3" to 2" reducing ell (supplied or field replac-  
ment Canadian ki) installed directly into unit flue collar.  
Page 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
NOTE − Furnace flue collar and air inlet fitting are both  
made of ABS material. Use transition solvent cement  
when bonding ABS to either PVC or CPVC, refer to the  
procedure specified in ASTM D3138..  
Joint Cementing Procedure  
All cementing of joints should be done according to the  
specifications outlined in ASTM D 2855.  
6 − Promptly apply solvent cement to end of pipe and in-  
side socket surface of fitting. Cement should be ap-  
plied lightly but uniformly to inside of socket. Take  
care to keep excess cement out of socket. Apply sec-  
ond coat to end of pipe.  
WARNING  
DANGER OF EXPLOSION!  
NOTE − Time is critical at this stage. Do not allow prim-  
Fumes from PVC glue may ignite during system  
check. Allow fumes to dissipate for at least 5 minutes  
before placing unit into operation.  
er to dry before applying cement.  
7 − Immediately after applying last coat of cement to pipe,  
and while both inside socket surface and end of pipe  
are wet with cement, forcefully insert end of pipe into  
socket until it bottoms out. Turn PVC pipe 1/4 turn dur-  
ing assembly (but not after pipe is fully inserted) to dis-  
tribute cement evenly. DO NOT turn ABS or cellular  
core pipe.  
1 − Measure and cut vent pipe to desired length.  
2 − Debur and chamfer end of pipe, removing any ridges  
or rough edges. If end is not chamfered, edge of pipe  
may remove cement from fitting socket and result in a  
leaking joint.  
NOTE − Assembly should be completed within 20 sec-  
onds after last application of cement. Hammer blows  
should not be used when inserting pipe.  
3 − Clean and dry surfaces to be joined.  
4 − Test fit joint and mark depth of fitting on outside of pipe.  
8 − After assembly, wipe excess cement from pipe at end  
of fitting socket. A properly made joint will show a  
bead around its entire perimeter. Any gaps may indi-  
cate a defective assembly due to insufficient solvent.  
5 − Uniformly apply a liberal coat of PVC primer for PVC or  
use a clean dry cloth for ABS to clean inside socket  
surface of fitting and male end of pipe to depth of fitting  
socket.  
9 − Handle joints carefully until completely set.  
Page 20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4 − Isolate piping at the point where it exits the outside wall  
or roof in order to prevent transmission of vibration to  
the structure.  
Venting Practices  
The thickness of construction through which vent pipes  
may be installed is 24" (610mm) maximum and 3" (76mm)  
minimum. If a G61MP furnace replaces a furnace which  
was commonly vented with another gas appliance, the size  
of the existing vent pipe for that gas appliance must be  
checked. Without the heat of the original furnace flue prod-  
ucts, the existing vent pipe is probably oversized for the  
single water heater or other appliance. The vent should be  
checked for proper draw with the remaining appliance.  
5 − When furnace is installed in a residence where unit is  
shut down for an extended period of time, such as a  
vacation home, make provisions for draining conden-  
sate collection trap and lines.  
Exhaust Piping  
NOTE − A 2" diameter PVC street ell is located on the  
blower deck of 48C−110, 60C−110 and 60C−111 units. In  
upflow or downflow applicationsthestreet ellmust be  
glued using transition solvent cement directly into the  
unit flue collar. See figure23. A 3" to 2" PVC reducing ell is  
located on the blower deck of the 60D−135 units. In up-  
flow or downflow applications, the reducing ell must  
be glued using transition solvent cement directly into the  
unit flue collar.  
1 − Use recommended piping materials for exhaust pip-  
ing.  
2 − Secure all joints so that they are gas-tight using ap-  
proved cement.  
Suspend piping using hangers at a minimum of every 5  
feet (1.52m) for schedule  
40 PVC and every 3 feet  
(.91m) for ABS−DWV, PVC−  
DWV, SPR−21 PVC, and  
SDR−26 PVC piping. A suit-  
able hanger can be fabri-  
cated by using metal or  
plastic strapping or a large  
wire tie.  
STRAPPING  
(metal, plastic  
or large wire  
ties)  
1 − Choose the appropriate side for venting in upflow or  
downflow positions. Exhaust piping exits from the top  
of the unit in horizontal air discharge applications.  
Glue the field−provided exhaust vent pipe (or provided  
street ell or reducing ell in upflow or downflow applica-  
tions) to the flue collar. All PVC cement joints should  
be made according to the specifications outlined in  
ASTM D 2855. Refer to pipe and fittings specifications  
and gluing procedures.  
FIGURE 22  
3 − In areas where piping penetrates joists or interior  
walls, hole must be large enough to allow clearance on  
all sides of pipe through center of hole using a hanger.  
TYPICAL EXHAUST PIPE CONNECTIONS AND CONDENSATE TRAP INSTALLATION  
IN UPFLOW OR DOWNFLOW DIRECT OR NONDIRECT VENT APPLICATIONS  
(RightHand Exit in Upflow Application Shown)  
45°  
MAX  
45°  
MAX  
2−1/2",  
3", OR  
4"  
2"  
PLUG  
PLUG  
TRANSITION  
or  
**2"  
2"  
G61MP−045,  
−070, −071 or  
−090, −091 with  
2−1/2", 3", or 4"  
vent pipe  
2"  
2"  
SIDE VIEW  
VENT PLUG  
(Must be  
glued in  
2"  
place)  
4"  
2−1/2",  
3", OR  
4"  
PLUG  
TRANSITION  
(use only if 4"  
pipe is  
CONDENSATE  
TRAP  
(Must be installed  
on same side as  
exhaust piping)  
TRANSITION  
required)  
2" max  
length  
2" max  
length  
*2"  
3" to 2" REDUCING ELBOW  
(provided)  
G61MP−110, −111 with  
2−1/2", 3", OR 4" vent  
pipe  
*2" diameter street elbow provided.  
G61MP−135, −110, −111  
with  
3" OR 4" vent pipe  
**Street elbow may be used on −045, −070, 071, −090 and −091.  
FIGURE 23  
Page 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TYPICAL EXHAUST PIPE CONNECTIONS  
HORIZONTAL DIRECT OR NONDIRECT VENT  
APPLICATIONS  
CAUTION  
Do not discharge exhaust into an existing stack or  
stack that also serves another gas appliance. If verti-  
cal discharge through an existing unused stack is re-  
quired, insert PVC pipe inside the stack until the end  
is even with the top or outlet end of the metal stack.  
(Horizontal RightHand Air  
Discharge Application Shown)  
* 2" maximum length  
for −110, −111 −135 only  
36B−045  
2−1/2",  
3", OR  
4"  
36B−070  
36B−071  
48C−090  
60C−090  
60C−091  
48C−110  
60C−110*  
60C−111*  
60D−135*  
TRANSITION  
*2"  
CAUTION  
The exhaust vent pipe operates under positive pres-  
sure and must be completely sealed to prevent leak-  
age of combustion products into the living space.  
2"  
2"  
36B−045  
36B−070  
36B−071  
36C−090  
60C−090  
60C−091  
DO NOT transition  
from smaller to larger  
pipe size in horizontal  
runs of exhaust pipe.  
Intake Piping  
2"  
The G61MP furnace may be installed in either direct vent  
or non−direct vent applications. In non−direct vent applica-  
tions, when intake air will be drawn into the furnace from the  
surrounding space, the indoor air quality must be consid-  
ered and guidelines listed in Combustion, Dilution and Ven-  
tilation Air section must be followed.  
The G61MP unit is designed for either left−side or right−side  
air intake connections in either upflow or downflow applica-  
tions. In horizontal applications, air intake must be brought  
in through the top. Intake air piping is independent of ex-  
haust piping.  
Follow the next four steps when installing the unit in direct  
vent applications, where combustion air is taken from out-  
doors and flue gases are discharged outdoors. The pro-  
vided air intake screen must not be used in direct vent ap-  
plications.  
FIGURE 24  
IMPORTANT  
Exhaust piping and condensate trap must be  
installed on the same side of the unit in upflow and  
dowflow applications or use alternate drain kit  
76M20.  
1 − Use transition solvent cement to connect PVC pipe to  
the ABS slip connector located on the side of the burn-  
er box.  
2 − All horizontal runs of exhaust pipe must slope back to-  
ward unit. A minimum of 1/4" (6mm) drop for each 12"  
(305mm) of horizontal run is mandatory for drainage.  
Horizontal runs of exhaust piping must be supported ev-  
ery 5 feet (1.52m) using hangers.  
2 − Use a #7 sheet metal screw to secure the intake pipe to  
the connector, if desired. A pilot indentation is provided in  
the slip connector to assist in locating and starting the fas-  
tener.  
NOTE − Exhaust piping should be checked carefully to  
3 − Glue the provided 2" ABS plug into the unused ABS air  
intake connector on the opposite side of the cabinet with  
ABS all pupose cement.  
make sure there are no sags or low spots.  
3 − On the opposite side of the cabinet, glue the provided  
2" ABS vent plug into the unused ABS flue collar with  
ABS or all purpose solvent cement.  
4 − Route piping to outside of structure. Continue with instal-  
lation following instructions given in general guide lines for  
piping terminations and in intake and exhaust piping ter-  
minations for direct vent sections. Refer to figure 25 for  
pipe sizes.  
4 − Route piping to outside of structure. Continue with  
installation following instructions given in piping ter-  
mination section.  
Page 22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL AIR INTAKE PIPE CONNECTIONS  
UPFLOW OR DOWNFLOW DIRECT VENT APPLICATIONS  
(RightHand Exit in Upflow Application Shown)  
2−1/2",  
3" OR  
4ꢁ  
2−1/2",  
3" OR  
4ꢁ  
TRANSITION  
2ꢁ  
2ꢁ  
TRANSITION  
*2"  
2ꢁ  
2ꢁ  
2ꢁ  
2ꢁ  
PLUG  
(Must be  
glued in  
place)  
−36B−045−  
−36B−070  
−36B−071  
−48C−090  
−60C−090  
−60C−091  
−36B−045  
−36B−070  
−36B−071  
−48C−090  
−60C−090  
−60C−091  
−48C−110  
−60C−110*  
−60C−111*  
−60D−135*  
−36B−045  
−36B−070  
−36B−071  
−48C−090  
−60C−090  
−60C−091  
−48C−110  
−60C−110  
−60C−111  
*Limit pipe length to 4" in G61MP−110,  
−111, −135 applications.  
FIGURE 25  
Follow the next three steps when installing the unit in Non-  
Direct Vent applications where combustion air is taken  
from indoors and flue gases are discharged outdoors.  
TYPICAL AIR INTAKE PIPE CONNECTIONS  
HORIZONTAL DIRECT VENT APPLICATIONS  
(Horizontal RightHand Air Discharge Application Shown)  
−36B−045  
*Limit pipe  
length to 4" in −110, −111,  
−135 applications.  
−36B−070  
−36B−071  
−48C−090  
−60C−090  
−60C−091  
−48C−110  
−60C−110*  
−60C−111  
−60D−135*  
21/2”,  
TYPICAL AIR INTAKE PIPE CONNECTIONS  
UPFLOW OR HORIZONTAL NONDIRECT  
VENT APPLICATIONS  
3” OR 4”  
(RightHand Exit in Upflow Application Shown)  
TRANSITION  
6 in. Max.  
*2”  
21/2”,  
3” OR 4”  
−36B−045  
2”  
−36B−070  
−36B−071  
−48C−090  
−60C−090  
−60C−091  
−48C−110  
−60C−110  
−60C−111  
2”  
PLUG  
(Must be  
TRANSITION  
glued in  
INTAKE  
place)  
2”  
DEBRIS  
SCREEN  
(Provided)  
2”  
2”  
−36B−045  
−36B−070  
−36B−071  
−48C−090  
−60C−090  
−60C−091  
2”  
NOTE − Debris screen and elbow may be rotated, so that  
screen may be positioned to face forward, backward or  
downward.  
FIGURE 27  
FIGURE 26  
Page 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TYPICAL AIR INTAKE PIPE CONNECTIONS  
DOWNFLOW NONDIRECT VENT APPLICATIONS  
(RightHand Exit in Downflow Applications Shown)  
2" SWEEP  
ELL  
INTAKE  
DEBRIS  
SCREEN  
(Provided)  
6 in. Max.  
PLUG  
PLUG  
(Must be  
glued in  
place)  
(Must be  
glued in  
place)  
2"  
18 in.  
2" SWEEP ELL  
INTAKE DEBRIS  
SCREEN  
(Provided)  
Downflow Additive Flloor Base  
Downflow  
Evaporator  
Coil  
NOTE − Debris screen and sweep ell may be rotated, so that  
screen may be positioned to face forward, backward or to the side.  
FIGURE 28  
1 Use field−provided materials and the factory−provided  
air intake screen to route the intake piping as shown in  
figures 27 and 28. Maintain a minimum clearance of 3"  
(76mm) around the air intake opening. The air intake  
opening (with the protective screen) should always be  
directed either downward or straight out. Use 2" pipe  
and fittings only and make sure that the air intake does  
not extend more than 6" beyond the G61MP cabinet.  
The air intake connector must not be located near  
the floor. To avoid this complication in downflow  
applications which do not include a downflow  
evaporator coil, the intake air routing should be modi-  
2 − Use a #7 sheet metal screw to secure the intake pipe to  
the connector, if desired. A pilot indentation is provided in  
the slip connector to assist in locating and starting the fas-  
tener.  
3 − Glue the provided 2" ABS plug into the unused ABS air  
intake connector on the opposite side of the cabinet with  
ABS or all purpose solvent cement.  
Page 24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
General Guidelines for Vent Terminations  
(13mm) Armaflex or equivalent. In extreme cold climate  
areas, 3/4" (19mm) Armaflex or equivalent may be neces-  
sary. Insulation on outside runs of exhaust pipe must be  
painted or wrapped to protect insulation from deterioration.  
Exhaust pipe insulation may not be necessary in some  
specific applications.  
In Non-Direct Vent applications, combustion air is taken  
from indoors and the flue gases are discharged to the out-  
doors. The G61MP is then classified as a non-direct vent,  
Category IV gas furnace.  
In Direct Vent applications, combustion air is taken from  
outdoors and the flue gases are discharged to the out-  
doors. The G61MP is then classified as a direct vent,  
Category IV gas furnace.  
NOTE − During extremely cold temperatures, below  
approximately 20°F (6.7°C), units with long runs of vent  
pipe through unconditioned space, even when insulated,  
may form ice in the exhaust termination that prevents the  
unit from operating properly. Longer run times of at least 5  
minutes will alleviate most icing problems. Also, a heating  
cable may be installed on exhaust piping and termination to  
prevent freeze−ups. Heating cable installation kit is avail-  
able from Lennox. See Condensate Piping section for part  
numbers.  
In both Non-Direct Vent and Direct Vent applications, the  
vent termination is limited by local building codes. In the  
absence of local codes, refer to the current National Fuel  
Gas Code ANSI Z223−1/NFPA 54 in U.S.A., and current  
CSA−B149 Natural Gas and Propane Installation Codes in  
Canada for details.  
or 30. In addition, position termination so it is free from any  
obstructions and 12" above the average snow accumula-  
tion.  
IMPORTANT  
Do not use screens or perforated metal in exhaust  
terminations. Doing so will cause freeze−ups and  
may block the terminations.  
At vent termination, care must be taken to maintain  
protective coatings over building materials (prolonged  
exposure to exhaust condensate can destroy protective  
coatings). It is recommended that the exhaust outlet not be  
located within 6 feet (1.8m) of a condensing unit because  
the condensate can damage the painted coating.  
IMPORTANT  
For Canadian Installations Only:  
NOTE − If winter design temperature is below 32°F (0°C),  
exhaust piping should be insulated with 1/2" (13mm), Ar-  
maflex or equivalent when run through unheated space.  
Do not leave any surface area of exhaust pipe open to out-  
side air; exterior exhaust pipe should be insulated with 1/2"  
In accordance to CSA International B149 installation  
codes, the minimum allowed distance between the  
combustion air intake inlet and the exhaust outlet of  
other appliances shall not be less than 12 inches  
(305mm).  
Page 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENT TERMINATION CLEARANCES  
FOR NON−DIRECT VENT INSTALLATIONS IN THE USA AND CANADA  
INSIDE CORNER  
DETAIL  
G
H
A
D
E
B
L
B
Fixed  
Closed  
B
B
I
C
Operable  
Fixed  
Closed  
M
F
Operable  
K
J
A
B
AREA WHERE TERMINAL  
IS NOT PERMITTED  
AIR SUPPLY INLET  
VENT TERMINAL  
1
2
US Installations  
Canadian Installations  
A =  
Clearance above grade, veranda,  
porch, deck or balcony  
12 inches (305mm) or 12 in. 305mm)  
above average snow accumulation.  
12 inches (305mm) or 12 in. 305mm)  
above average snow accumulation.  
B =  
Clearance to window or  
door that may be opened  
6 inches (152mm) for appliances <10,000  
Btuh (3kw), 12 inches (305mm) for  
appliances > 10,000 Btuh (3kw) and  
<100,000 Btuh (30kw), 36 inches (.9m)  
for appliances > 100,000 Btuh (30kw)  
4 feet (1.2 m) below or to side of opening;  
1 foot (30 cm) above opening  
C =  
D =  
Clearance to permanently  
closed window  
* 12"  
* 12"  
Vertical clearance to ventilated soffit  
located above the terminal within a  
horizontal distance of 2 feet (mm)  
from the center line of the terminal  
* Equal to or greater than soffit depth.  
* Equal to or greater than soffit depth.  
* Equal to or greater than soffit depth.  
* No minimum to outside corner  
* 3 feet (.9m)  
E =  
F =  
Clearance to unventilated soffit  
Clearance to outside corner  
* Equal to or greater than soffit depth.  
* No minimum to outside corner  
* 3 feet (.9m)  
G = Clearance to inside corner  
H = Clearance to each side of center line ex-  
tended above meter / regulator assembly  
3 feet (.9m) within a height 15 feet (4.5m) 3 feet (.9m) within a height 15 feet (4.5m)  
above the meter / regulator assembly  
*
above the meter / regulator assembly  
I =  
Clearance to service regulator  
vent outlet  
3 feet (.9m)  
* 3 feet (.9m)  
J =  
Clearance to non−mechanical air  
supply inlet to building or the com-  
bustion air inlet to any other ap-  
pliance  
6 inches (152mm) for appliances <10,000  
Btuh (3kw), 12 inches (305mm) for  
appliances > 10,000 Btuh (3kw) and  
<100,000 Btuh (30kw), 36 inches (.9m)  
for appliances > 100,000 Btuh (30kw)  
4 feet (1.2 m) below or to side of opening;  
1 foot (30 cm) above opening  
K =  
L =  
Clearance to mechanical air sup-  
ply inlet  
3 feet (.9m) above if within 10 feet  
(3m) horizontally  
6 feet (1.8m)  
Clearance above paved sidewalk or  
paved driveway located on public property  
7 feet (2.1m)ꢀ  
7 feet (2.1m)ꢀ  
M =  
Clearance under veranda, porch,  
deck or balcony  
12 inches (305mm)ꢂ  
*12 inches (305mm)ꢂ  
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code  
2
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code  
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clear-  
ance will be in accordance with local installation codes and the requirements  
of the gas supplier and these installation instructions."  
ꢀ A vent shall not terminate directly above a sidewalk or paved driveway that is located  
between two single family dwellings and serves both dwellings.  
ꢂ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two  
sides beneath the floor. Lennox recommends avoiding this location if possible.  
FIGURE 29  
Page 26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
VENT TERMINATION CLEARANCES  
FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA  
INSIDE CORNER  
DETAIL  
G
H
A
D
E
B
L
B
Fixed  
Closed  
B
B
I
C
Operable  
Fixed  
Closed  
M
F
Operable  
K
J
A
B
AREA WHERE TERMINAL  
IS NOT PERMITTED  
AIR SUPPLY INLET  
VENT TERMINAL  
1
2
US Installations  
Canadian Installations  
A =  
Clearance above grade, veranda,  
porch, deck or balcony  
12 inches (305mm) or 12 in. 305mm)  
above average snow accumulation.  
12 inches (305mm) or 12 in. 305mm)  
above average snow accumulation.  
B =  
Clearance to window or  
door that may be opened  
6 inches (152mm) for appliances <10,000 6 inches (152mm) for appliances <10,000  
Btuh (3kw), 9 inches (mm) for appliances  
> 10,000 Btuh (3kw) and <50,000 Btuh  
(15 kw), 12 inches (305mm) for ap-  
pliances > 50,000 Btuh (15kw)  
Btuh (3kw), 12 inches (305mm) for  
appliances > 10,000 Btuh (3kw) and  
<100,000 Btuh (30kw), 36 inches (.9m)  
for appliances > 100,000 Btuh (30kw)  
* 12"  
C =  
D =  
Clearance to permanently  
closed window  
* 12"  
Vertical clearance to ventilated soffit  
located above the terminal within a  
horizontal distance of 2 feet (mm)  
from the center line of the terminal  
* Equal to or greater than soffit depth  
* Equal to or greater than soffit depth  
* Equal to or greater than soffit depth  
* No minimum to outside corner  
* 3 feet (.9m)  
* Equal to or greater than soffit depth  
* No minimum to outside corner  
E =  
F =  
G =  
Clearance to unventilated soffit  
Clearance to outside corner  
Clearance to inside corner  
* 3 feet (.9m)  
H = Clearance to each side of center line ex-  
tended above meter / regulator assembly  
3 feet (.9m) within a height 15 feet (4.5m) 3 feet (.9m) within a height 15 feet (4.5m)  
above the meter / regulator assembly  
above the meter / regulator assembly  
I =  
Clearance to service regulator  
vent outlet  
3 feet (.9m)  
* 3 feet (.9m)  
J =  
Clearance to non−mechanical air  
supply inlet to building or the com-  
bustion air inlet to any other ap-  
pliance  
6 inches (152mm) for appliances <10,000 6 inches (152mm) for appliances <10,000  
Btuh (3kw), 9 inches (mm) for appliances  
> 10,000 Btuh (3kw) and <50,000 Btuh  
(15 kw), 12 inches (305mm) for ap-  
pliances > 50,000 Btuh (15kw)  
Btuh (3kw), 12 inches (305mm) for  
appliances > 10,000 Btuh (3kw) and  
<100,000 Btuh (30kw), 36 inches (.9m)  
for appliances > 100,000 Btuh (30kw)  
K =  
L =  
Clearance to mechanical air sup-  
ply inlet  
3 feet (.9m) above if within 10 feet  
(3m) horizontally  
6 feet (1.8m)  
Clearance above paved sidewalk or  
paved driveway located on public property  
7 feet (2.1m)ꢀ  
* 7 feet (2.1m)  
M =  
Clearance under veranda, porch,  
deck or balcony  
*12 inches (305mm)ꢂ  
12 inches (305mm)ꢂ  
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code  
2
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clear-  
ance will be in accordance with local installation codes and the requirements  
of the gas supplier and these installation instructions."  
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code  
ꢀ A vent shall not terminate directly above a sidewalk or paved driveway that is located  
between two single family dwellings and serves both dwellings.  
ꢂ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two  
sides beneath the floor. Lennox recommends avoiding this location if possible.  
FIGURE 30  
Page 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Details of Intake and Exhaust Piping Terminations for  
Direct Vent Installations  
TABLE 8  
EXHAUST PIPE TERMINATION SIZE REDUCTION  
G61MP  
Exhaust Pipe Size  
Termination Pipe Size  
NOTE − In Direct Vent installations, combustion air is taken  
from outdoors and flue gases are discharged to outdoors.  
MODEL  
045, 070, −071  
090, −091  
110, −111  
135  
2", 2−1/2", 3" or 4"  
2", 2−1/2", 3" or 4"  
2−1/2", 3" or 4"  
3" or 4"  
1−1/2"  
2"  
Intake and exhaust pipes may be routed either horizontally  
through an outside wall or vertically through the roof. In at-  
tic or closet installations, vertical termination through the  
roof is preferred. Figures 31 through 39 show typical ter-  
minations.  
*2"  
*2"  
*Approved 3" concentric termination kit terminates with 2−5/8" ID pipe.  
3(76) MAX.  
SIZE TERMINATION  
PIPE PER TABLE 8.  
Inches(mm)  
1 − Exhaust and intake exits must be in same pressure  
zone. Do not exit one through the roof and one on the  
side. Also, do not exit the intake on one side and the  
exhaust on another side of the house or structure.  
UNCONDITIONED  
ATTIC SPACE  
8" (203) MIN  
1/2" (13) FOAM  
INSULATION IN  
UNCONDITIONED  
SPACE  
2 − Intake and exhaust pipes should be placed as close  
together as possible at termination end (refer to il-  
lustrations). Maximum separation is 3" (76mm) on roof  
terminations and 6" (152mm) on side wall termina-  
tions.  
12" (305) ABOVE  
AVERAGE SNOW  
ACCUMULATION  
3" (76) OR  
2" (51) PVC  
3 − If necessary, install a field−provided reducer to adapt  
larger vent pipe size to termination pipe size.  
PROVIDE SUPPORT  
FOR INTAKE AND  
EXHAUST LINES  
4 − On roof terminations, the intake piping should termi-  
nate straight down using two 90° elbows (See figure  
31).  
DIRECT VENT ROOF TERMINATION KIT  
(15F75 or 44J41)  
5 − Exhaust piping must terminate straight out or up as  
shown. In rooftop applications, a reducer may be re-  
quired on the exhaust piping at the point where it exits  
the structure to improve the velocity of exhaust away  
from the intake piping. See table 8.  
FIGURE 31  
12" (305) MAX.  
(unless supported)  
1/2" (13) ARMAFLEX  
INSULATION IN  
UNCONDITIONED SPACE  
1/2" (13)  
ARMAFLEX  
INSULATION  
NOTE − Care must be taken to avoid recirculation of  
exhaust back into intake pipe.  
FIELD−  
PROVIDED  
REDUCER MAY  
BE REQUIRED  
TO ADAPT  
LARGER VENT  
PIPE SIZE TO  
TERMINATION  
OUTSIDE  
SIZE  
TERMINA-  
TION PIPE  
PER TABLE  
6 − On field supplied terminations for side wall exits, ex-  
haust piping should extend a minimum of 12 inches  
(305mm) beyond the outside wall. Intake piping  
6" (152)  
MAXI-  
MUM  
Inches (mm)  
8" (203)  
MINIMUM  
WALL  
2" (51)  
PVC  
7 − On field supplied terminations, a minimum separation  
distance between the end of the exhaust pipe and the  
end of the intake pipe is 8 inches (203mm).  
COUPLING  
TOP VIEW WALL RING KIT WITH STRAIGHT INTAKE  
(15F74)  
8 − If intake and exhaust piping must be run up a side wall  
to position above snow accumulation or other obstruc-  
tions, piping must be supported every 3 ft. (.9m) as  
shown in figure 22. Refer to figure 35 for proper piping  
method. In addition, WTK wall termination kit must be  
extended for use in this application. See figure 38.  
When exhaust and intake piping must be run up an  
outside wall, the exhaust piping is reduced to 1−1/2"  
(38mm) after the final elbow. The intake piping may be  
equipped with a 90° elbow turndown. Using turndown  
will add 5 feet (1.5m) to the equivalent length of the  
pipe.  
1/2 (13) ARMAFLEX  
12 (305) MAX.  
INSULATION IN  
UNCONDITIONED  
SPACE  
1/2" (13)  
ARMAFLEX  
INSULATION  
FIELD−  
PROVIDED  
REDUCER MAY  
BE REQUIRED  
TO ADAPT  
SIZE  
TERMINATION PIPE  
LARGER VENT  
PIPE SIZE TO  
TERMINATION  
6 (152)  
MAXIMUM  
4 (102)  
MINIMUM  
Inches (mm)  
OUTSIDE  
WALL  
9 − Based on the recommendation of the manufacturer, a  
multiple furnace installation may use a group of up to  
four termination kits WTK assembled together hori-  
TOP VIEW WALL RING KIT WITH 90° ELBOW ON INTAKE  
(15F74)  
FIGURE 32  
Page 28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
EXHAUST VENT  
EXHAUST  
TERMINATION  
12" (305) ABOVE  
AVERAGE SNOW  
ACCUMULATION  
Inches (mm)  
Front View  
INTAKE  
VENT  
INTAKE  
TERMINATION  
1/2" (13) Foam Insulation  
in Unconditioned Space  
Side View  
FIELD−PROVIDED  
REDUCER MAY BE REQUIRED  
TO ADAPT LARGER VENT  
PIPE SIZE TO TERMINATION  
FIELD−  
PROVIDED  
REDUCER MAY  
BE REQUIRED  
TO ADAPT  
EXHAUST VENT  
EXHAUST  
INTAKE  
LARGER VENT  
PIPE SIZE TO  
TERMINATION  
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION  
(71M80, 69M29 or 60L46)  
INTAKE VENT  
OUTSIDE WALL  
Inches (mm)  
FIGURE 33  
DIRECT VENT WALL TERMINATION KIT  
(22G44, 44J40, 30G28 or 81J20)  
INTAKE  
Inches (mm)  
TERMINATION  
EXHAUST  
TERMINATION  
FIGURE 36  
EXHAUST  
12"  
(305)  
INTAKE  
EXHAUST  
VENT  
12" (305) Min.  
above grade or average  
snow accumulation.  
5"  
(127)  
5−1/2"  
(140)  
FIELD−PROVIDED  
REDUCER MAY  
INTAKE  
VENT  
BE REQUIRED TO  
ADAPT LARGER  
VENT PIPE SIZE  
TO TERMINATION  
18" MAX.  
(457)  
Front View  
EXHAUST VENT  
DIRECT VENT CONCENTRIC WALL TERMINATION  
(71M80, 69M29 or 60L46)  
Inches (mm)  
FIGURE 34  
INTAKE  
VENT  
Side View  
12" (305) MAX. for 2" (51)  
(unless supported)  
Inches(mm)  
UNCONDITIONED  
SPACE  
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT  
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT WTK  
8 (203)  
MIN.  
OUTSIDE WALL  
FIGURE 37  
SIZE  
TERMINATION  
PROVIDE SUPPORT  
FOR INTAKE AND  
PIPE PER  
EXHAUST LINES EVERY  
36" (914)  
12" (305) ABOVE  
FIELD−PROVIDED  
AVERAGE SNOW  
REDUCER MAY  
ACCUMULATION  
BE REQUIRED TO  
ADAPT LARGER  
VENT PIPE SIZE  
TO TERMINATION  
1/2" (13) FOAM  
INSULATION IN  
UNCONDITIONED  
SPACE  
1/2" (13) FOAM  
INSULATION  
SIDE VIEW  
DIRECT VENT WALL RING TERMINATION  
(15F74)  
FIGURE 35  
Page 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
12" (305) MAX. for 2" (51)  
20" (508) MAX. for 3" (76)  
(unless supported)  
Inches (mm)  
EXHAUST  
AIR  
COVER EXHAUST  
VENT WITH  
1/2" (13)  
12"  
(305)  
FOAM  
INSULATION  
8" (203)  
INTAKE  
AIR  
INTAKE  
AIR  
Minimum  
Minimum 12"  
(305)  
above grade or  
average snow  
accumulation.  
EXHAUST  
AIR  
Minimum 12"  
(305)  
5"  
(127)  
above grade or  
average snow  
accumulation.  
5-1/2"  
(140)  
GRADE  
Side View  
GRADE  
Front View  
DIRECT VENT TERMINATION  
WALL TERMINATION KIT (22G44, 44J40, 30G28 or 81J20) EXTENDED VENT FOR GRADE CLEARANCE  
FIGURE 38  
G61MP DIRECT VENT APPLICATION  
USING EX
STRAIGHT−CUT OR  
ANGLE−CUT IN DIRECTION  
OF ROOF SLOPE *  
Inches(mm)  
SIZE TERMINATION  
PIPE PER TABLE 8.  
12" (305mm)  
ABOVE AVE.  
SNOW  
ACCUMULATION  
3" − 8"  
(76mm−  
8" − 12"  
EXHAUST VENT  
1/2" (13mm)  
WEATHERPROOF  
INSULATION  
203mm)  
(203mm − 305mm)  
SHOULDER OF FITTINGS  
PROVIDE SUPPORT  
OF PIPE ON TOP PLATE  
INTAKE PIPE  
INSULATION (optional)  
3" (76) OR  
2" (51) PVC  
SHEET  
METAL TOP  
PLATE  
UNCONDITIONED  
ATTIC SPACE  
ALTERNATE  
INTAKE PIPE  
PROVIDE SUPPORT  
FOR EXHAUST LINES  
Minimum 12" (305)  
above roof or average  
snow accumulation.  
3" − 8"  
(76mm−  
203mm)  
INSULATE  
TO FORM  
SEAL  
EXTERIOR  
PORTION OF  
CHIMNEY  
*SIZE TERMINATION  
PIPE PER TABLE 8.  
NON−DIRECT VENT ROOF TERMINATION KIT  
(15F75 or 44J41)  
FIGURE 40  
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver-  
tical discharge through an existing unused chimney or stack is required, insert piping  
inside chimney until the pipe open end is above top of chimney and terminate as illus-  
trated. In any exterior portion of chimney, the exhaust vent must be insulated.  
FIGURE 39  
Details of Exhaust Piping Terminations for Non-Direct  
Vent Applications  
12" (305) Max. for 2" (51)  
Unless Supported  
1/2" (13) ARMAFLEX  
INSULATION IN  
UNCONDITIONED SPACE  
Exhaust pipes may be routed either horizontally through an  
outside wall or vertically through the roof. In attic or closet  
installations, vertical termination through the roof is pre-  
ferred. Figures 40 through 43 show typical terminations.  
1/2" (13)  
ARMAFLEX  
INSULATION  
FIELD−PROVIDED  
REDUCER MAY  
BE REQUIRED TO  
ADAPT LARGER  
VENT PIPE SIZE  
TO TERMINATION  
1 − Exhaust piping must terminate straight out or up as  
shown. The termination pipe must be sized as listed in  
table 8.The specified pipe size ensures proper veloc-  
ity required to move the exhaust gases away from the  
building.  
PVC REDUCER  
SIZE TERMINATION  
PIPE PER TABLE 8.  
Inches (mm)  
TOP VIEW  
NON−DIRECT VENT WALL RING KIT  
(15F74)  
2 − On field supplied terminations for side wall exits, ex-  
haust piping should extend a maximum of 12 inches  
(305mm) beyond the outside wall, unless support is  
provided in the horizontal section. See figure 41.  
FIGURE 41  
Page 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3 − If exhaust piping must be run up a side wall to position  
above snow accumulation or other obstructions, pip-  
ing must be supported every 3 feet (.9m) as shown in  
figure 22. Refer to figure 42 for proper piping method.  
When exhaust piping must be run up an outside wall,  
any reduction in exhaust pipe size must be done after  
the final elbow.  
sate trap should extend below the unit. A 5−1/2" service  
clearance is required for the condensate trap. Refer to fig-  
ure 44 for condensate trap locations.  
CONDENSATE TRAP LOCATIONS  
(Unit shown in upflow position)  
Horizontal  
left and  
Horizontal  
right and  
optional  
12" (305) Max. for 2" (51)  
Unless Supported  
Inches(mm)  
optional  
downflow  
downflow  
UNCONDITIONED  
SPACE  
OUTSIDE WALL  
SIZE TER-  
MINATION  
PIPE PER  
PROVIDE SUPPORT  
FOR EXHAUST LINES  
EVERY 36" (914)  
12" (305) ABOVE  
AVERAGE SNOW  
ACCUMULATION  
Optional  
upflow  
Optional  
upflow  
FIELD−PROVIDED  
REDUCER MAY BE  
REQUIRED TO  
ADAPT LARGER  
VENT PIPE SIZE TO  
TERMINATION  
1/2" (13) FOAM  
INSULATION IN  
UNCONDITIONED  
SPACE  
1/2" (13) FOAM  
INSULATION  
SIDE VIEW  
NON−DIRECT VENT WALL RING TERMINATION  
(15F74)  
FIGURE 44  
1 − Determine which side condensate piping will exit the  
unit. Remove plugs from the condensate collar at the  
appropriate location on the side of the unit.  
FIGURE 42  
G61MP NON−DIRECT VENT APPLICATION  
USING EXISTING CHIMNEY  
NOTE − The condensate trap is factory−shipped with  
two rubber O−rings and two rubber clean−out caps  
installed. Check to make sure that these items are in  
place before installing the trap assembly.  
STRAIGHT−CUT OR  
ANGLE−CUT IN DIRECTION  
OF ROOF SLOPE  
SIZE TERMINATION  
PIPE PER TABLE 8.  
3" − 8"  
(76mm−  
203mm)  
2 − Install condensate trap onto the condensate collar.  
Use provided HI/LO screws to secure two upper  
flanges of the trap to the collar. Use provided sheet  
metal screw to secure bottom trap flange to side of  
unit. DO NOT apply glue to secure condensate trap  
to cabinet. All other joints must be glued. See figure  
45.  
EXHAUST VENT  
1/2" (13mm)  
WEATHERPROOF  
INSULATION  
MINIMUM12"  
(305mm) ABOVE  
AVERAGE SNOW  
ACCUMULATION  
SHOULDER OF FITTINGS  
PROVIDE SUPPORT  
OF PIPE ON TOP PLATE  
SHEET  
METAL TOP  
PLATE  
3" − 8"  
(76mm−  
203mm)  
NOTE − In upflow and downflow applications, con-  
densate trap must be installed on the same side as  
exhaust piping.  
INSULATE  
TO FORM  
SEAL  
EXTERIOR  
PORTION OF  
CHIMNEY  
CAUTION  
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver-  
tical discharge through an existing unused chimney or stack is required, insert piping  
inside chimney until the pipe open end is above top of chimney and terminate as illus-  
trated. In any exterior portion of chimney, the exhaust vent must be insulated.  
DO NOT use a power driver to tighten screws which  
secure condensate trap to cabinet. Screws should  
be hand−tightened using a screw driver to avoid the  
possibility of damage to the trap assembly.  
FIGURE 43  
Condensate Piping  
3 − The condensate trap provided with the unit is  
manufactured using ABS material. Use ABS to PVC  
transition solvent cement to glue a field−provided PVC  
coupling or PVC pipe to the trap. Install a tee and vent  
pipe near the trap.  
This unit is designed for either right- or left-side exit of con-  
densate piping in either upflow or downflow applications;  
however, it must be installed on the same side of the unit as  
the exhaust piping. In horizontal applications, the conden-  
Page 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
NOTE − The condensate trap drain stubs (both sides)  
have an outer diameter which will accept a standard  
3/4" PVC coupling. The inner diameter of each stub  
will accept standard 1/2" diameter PVC pipe.  
5 − If unit will be started immediately upon completion of  
installation, prime trap per procedure outlined in Unit  
Start−Up section.  
6 − Glue the provided cap onto the unused condensate  
drain line stub.  
NOTE − Vinyl tubing may be used for condensate  
drain. Tubing must be 1−1/4" OD X 1" ID and should be  
attached to the drain stubs on the trap using a hose  
clamp.  
CONDENSATE ASSEMBLY  
4 − Glue the field−provided drain line to the tee. Route the  
drain line to an open drain. As an alternate, clear vinyl  
tubing may be used to drain condensate away from  
the trap. Secure the vinyl tubing to the drain stubs on  
the trap using a hose clamp. Do not overtighten the  
hose clamp.  
HI/LO SCREWS  
(DO NOT use power  
driver. Hand−tighten  
using screw driver.)  
VENT  
NIPPLE  
O−RINGS  
Condensate line must be sloped downward away from  
condensate trap to drain. If drain level is above con-  
densate trap, condensate pump must be used. Con-  
densate drain line should be routed within the condi-  
tioned space to avoid freezing of condensate and  
blockage of drain line. If this is not possible, a heat  
cable kit may be used on the condensate trap and line.  
Heating cable kit is available from Lennox in various  
lengths; 6 ft. (1.8m) − kit no. 26K68; 24 ft. (7.3m) − kit  
no. 26K69; and 50 ft. (15.2m) − kit no. 26K70.  
TEE  
CAP  
NIPPLE  
COUPLING  
CLEAN−OUT ACCESS  
(both sides)  
CONDENSATE TRAP  
SCREW  
NOTE − Use screws to secure condensate trap to cabinet. DO  
NOT apply glue to this joint. All other joints must be glued.  
CAUTION  
Do not use copper tubing or existing copper  
condensate lines for drain line.  
FIGURE 45  
Page 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Gas Piping  
IMPORTANT  
Compounds used on threaded joints of gas piping  
must be resistant to the actions of liquified petro-  
leum gases.  
CAUTION  
If a flexible gas connector is required or allowed by  
the authority that has jurisdiction, black iron pipe  
shall be installed at the gas valve and extend outside  
the furnace cabinet.  
MANUAL MAIN SHUT−OFF  
VALVE WILL NOT HOLD  
NORMAL TEST PRESSURE  
FURNACE  
ISOLATE  
GAS VALVE  
WARNING  
Do not exceed 600 in−lbs (50 ft−lbs) torque when at-  
taching the gas piping to the gas valve.  
CAP  
1 − Gas piping may be routed into the unit through either  
the left- or right-hand side. Supply piping enters into  
the gas valve from the side of the valve as shown in  
figure 48.  
FIGURE 46  
Leak Check  
After gas piping is completed, carefully check all piping  
connections (factory− and field−installed) for gas leaks. Use  
a leak detecting solution or other preferred means.  
2 − When connecting gas supply, factors such as length of  
run, number of fittings and furnace rating must be con-  
sidered to avoid excessive pressure drop. Table 9 lists  
recommended pipe sizes for typical applications.  
The furnace must be isolated from the gas supply system  
by closing its individual manual shut-off valve during any  
pressure testing of the gas supply system at pressures less  
than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).  
NOTE − Use two wrenches when connecting gas pip-  
ing to avoid transferring torque to the manifold.  
3 − Gas piping must not run in or through air ducts, clothes  
chutes, chimneys or gas vents, dumb waiters or eleva-  
tor shafts. Center gas line through piping hole. Gas  
IMPORTANT  
When testing pressure of gas lines, gas valve must  
valves can be damaged if subjected to pressures  
greater than 1/2 psig (3.48 kPa).  
4 − Piping should be sloped 1/4 inch per 15 feet (6mm per  
5.6m) upward toward the gas meter from the furnace.  
The piping must be supported at proper intervals, ev-  
ery 8 to 10 feet (2.44 to 3.05m), using suitable hangers  
or straps. Install a drip leg in vertical pipe runs to serve as  
a trap for sediment or condensate.  
WARNING  
FIRE OR EXPLOSION HAZARD  
5 − A 1/8" N.P.T. plugged tap or pressure post is located  
on the gas valve to facilitate test gauge connection.  
Failure to follow the safety warnings exactly could  
result in serious injury, death, or property damage.  
Never use an open flame to test for gas leaks. Check  
all connections using a commercially available soap  
solution made specifically for leak detection.Some  
soaps used for leak detection are corrosive to certain  
metals. Carefully rinse piping thoroughly after leak  
test has been completed.  
6 − In some localities, codes may require installation of a  
manual main shut-off valve and union (furnished by in-  
staller) external to the unit. Union must be of the  
ground joint type.  
Upflow Application  
Left Side Piping  
(Standard)  
Upflow Application  
Right Side Piping  
(Alternate)  
AUTOMATIC  
GAS VALVE  
(with manual  
shut−off valve)  
MANUAL  
MAIN SHUT−OFF  
VALVE  
MANUAL  
MAIN SHUT−OFF  
VALVE  
GROUND  
JOINT  
UNION  
GROUND  
JOINT  
UNION  
DRIP LEG  
FIELD  
PROVIDED  
AND INSTALLED  
DRIP LEG  
FIGURE 47  
Page 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Horizontal Applications  
Possible Gas Piping Configerations  
MANUAL  
MAIN SHUT−OFF  
VALVE  
Horizontal Application  
Left−Side Air Discharge  
MANUAL  
MAIN SHUT−OFF  
VALVE  
GROUND  
JOINT  
UNION  
GROUND  
JOINT  
UNION  
DRIP LEG  
DRIP LEG  
MANUAL  
MAIN SHUT−OFF  
VALVE  
(With 1/8 in. NPT  
Plugged Tap  
Shown)  
Horizontal Application  
Right−Side Air Discharge  
GROUND  
JOINT  
UNION  
DRIP LEG  
FIGURE 48  
TABLE 9  
GAS PIPE CAPACITY − FT3/HR (kL/HR)  
Length of Pipe−Feet(m)  
Nominal  
Iron Pipe Size  
−Inches(mm)  
Internal  
Diameter  
−Inches(mm)  
10  
(3.048)  
20  
(6.096)  
30  
(9.144)  
40  
50  
60  
70  
80  
90  
(12.192) (15.240) (18.288) (21.336) (24.384) (27.432) (30.480)  
100  
1/4  
(6.35)  
.364  
(9.246)  
43  
(1.13)  
29  
(.82)  
24  
(.68)  
20  
(.57)  
18  
(.51)  
16  
(.45)  
15  
(.42)  
14  
(.40)  
13  
(.37)  
12  
(.34)  
3/8  
(9.53)  
.493  
(12.522)  
95  
(2.69)  
65  
(1.84)  
52  
(1.47)  
45  
(1.27)  
40  
(1.13)  
36  
(1.02)  
33  
(.73)  
31  
(.88)  
29  
(.82)  
27  
(.76)  
1/2  
(12.7)  
.622  
(17.799)  
175  
(4.96)  
120  
(3.40)  
97  
(2.75)  
82  
(2.32)  
73  
(2.07)  
66  
(1.87)  
61  
(1.73)  
57  
(1.61)  
53  
(1.50)  
50  
(1.42)  
3/4  
(19.05)  
.824  
(20.930)  
360  
(10.19)  
250  
(7.08)  
200  
(5.66)  
170  
(4.81)  
151  
(4.28)  
138  
(3.91)  
125  
(3.54)  
118  
(3.34)  
110  
(3.11)  
103  
(2.92)  
1
(25.4)  
1.049  
(26.645)  
680  
(19.25)  
465  
(13.17)  
375  
(10.62)  
320  
(9.06)  
285  
(8.07)  
260  
(7.36)  
240  
(6.80)  
220  
(6.23)  
205  
(5.80)  
195  
(5.52)  
1−1/4  
(31.75)  
1.380  
(35.052)  
1400  
(39.64)  
950  
(26.90)  
770  
(21.80)  
660  
(18.69)  
580  
(16.42)  
530  
(15.01)  
490  
(13.87)  
460  
(13.03)  
430  
(12.18)  
400  
(11.33)  
1−1/2  
(38.1)  
1.610  
(40.894)  
2100  
(59.46)  
460  
(41.34)  
1180  
(33.41)  
990  
(28.03)  
900  
(25.48)  
810  
(22.94)  
750  
(21.24)  
690  
(19.54)  
650  
(18.41)  
620  
(17.56)  
2
(50.8)  
2.067  
(52.502)  
3950  
(111.85)  
2750  
(77.87)  
2200  
(62.30)  
1900  
(53.80)  
1680  
(47.57)  
1520  
(43.04)  
1400  
(39.64)  
1300  
(36.81)  
1220  
(34.55)  
1150  
(32.56)  
2−1/2  
(63.5)  
2.469  
(67.713)  
6300  
(178.39)  
4350  
(123.17)  
3520  
(99.67)  
3000  
(84.95)  
2650  
(75.04)  
2400  
(67.96)  
2250  
(63.71)  
2050  
(58.05)  
1950  
(55.22)  
1850  
(52.38)  
3
(76.2)  
3.068  
(77.927)  
11000  
(311.48)  
7700  
(218.03)  
6250  
(176.98)  
5300  
(150.07)  
4750  
(134.50)  
4300  
(121.76)  
3900  
(110.43)  
3700  
(104.77)  
3450  
(97.69)  
3250  
(92.03)  
4
(101.6)  
4.026  
(102.260)  
23000  
(651.27)  
15800  
(447.39)  
12800  
(362.44)  
10900  
(308.64)  
9700  
(274.67)  
8800  
(249.18)  
8100  
(229.36)  
7500  
(212.37)  
7200  
(203.88)  
6700  
(189.72)  
NOTE − Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.  
Page 34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
The unit is equipped with a field make−up box. The make−  
up box may be moved to the right side of the furnace to fa-  
cilitate installation. If the make−up box is moved to the right  
side, the excess wire must be pulled into the blower  
compartment. Secure the excess wire to the existing har-  
ness to protect it from damage.  
Electrical  
ELECTROSTATIC DISCHARGE (ESD)  
Precautions and Procedures  
CAUTION  
for schematic wiring diagram and troubleshooting.  
Electrostatic discharge can affect electronic com-  
ponents. Take precautions during furnace installa-  
tion and service to protect the furnace’s electronic  
controls. Precautions will help to avoid control ex-  
posure to electrostatic discharge by putting the fur-  
nace, the control and the technician at the same  
electrostatic potential. Neutralize electrostatic  
charge by touching hand and all tools on an un-  
painted unit surface, such as the gas valve or blower  
deck, before performing any service procedure.  
1 − Select circuit protection and wire size according to the  
unit nameplate. The power supply wiring must meet  
Class I restrictions.  
2 − Holes are on both sides of the furnace cabinet to facili-  
tate wiring.  
3 − Install a separate disconnect switch (protected by ei-  
ther fuse or circuit breaker) near the furnace so that  
power can be turned off for servicing.  
4 − Before connecting the thermostat or the power wiring,  
check to make sure the wires will be long enough for  
servicing at a later date. Remove the blower access  
panel to check the length of the wire.  
INTERIOR MAKE−UP BOX INSTALLATION  
MAKE−UP  
BOX  
5 − Complete the wiring connections to the equipment.  
Use the provided unit wiring diagram and the field wir-  
ing diagram shown in figure 51 and table 10. Use  
18−gauge wire or larger that is suitable for Class II rat-  
ing for thermostat connections.  
Right Side  
NOTE − Do NOT make a wire connection between  
the room thermostat L terminal and the L terminal  
of the G61MP integrated control.  
6 − Electrically ground the unit according to local codes or,  
in the absence of local codes, according to the current  
National Electric Code (ANSI/NFPA No. 70) for the  
USA and current Canadian Electric Code part 1 (CSA  
standard C22.1) for Canada. A green ground wire is  
provided in the field make−up box.  
FIGURE 49  
INTERIOR MAKE−UP BOX INSTALLATION  
NOTE − The G61MP furnace contains electronic com-  
ponents that are polarity sensitive. Make sure that the  
furnace is wired correctly and is properly grounded.  
Left side  
MAKE−UP  
BOX  
7 − One line voltage ꢁHUM" 1/4" spade terminal is provided  
on the furnace control board. Any humidifier rated up  
to one amp can be connected to this terminal with the  
neutral leg of the circuit being connected to one of the  
provided neutral terminals. See figure 52 for control  
board configuration. This terminal is energized in the  
heating mode when the combustion air inducer is oper-  
ating.  
8 − One line voltage ꢁEAC" 1/4" spade terminal is provided  
on the furnace control board. Any electronic air cleaner  
rated up to one amp can be connected to this terminal  
with the neutral leg of the circuit being connected to  
control board configuration. This terminal is energized  
when the indoor blower is operating.  
FIGURE 50  
Page 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9 − One 24V ꢁH" terminal is provided on the furnace control  
board terminal block. Any humidifier rated up to 0.5  
amp can be connected to this terminal with the ground  
leg of the circuit being connected to either ground or  
the ꢁC" terminal. See figure 52 for control board config-  
uration.  
Indoor Blower Speeds  
1 − When the thermostat is set to ꢁFAN ON," the indoor  
blower will run continuously on the low heat speed  
when there is no cooling or heating demand.  
2 − When the G61MP is operating in the high−fire or low−  
fire heating mode, the indoor blower will run on the cor-  
responding heating speed.  
10 −Install the room thermostat according to the instruc-  
tions provided with the thermostat. See table 10 for  
field wiring connections in varying applications. If the  
furnace is being matched with a heat pump, refer to the  
instruction packaged with the dual fuel thermostat.  
3 − When there is a cooling demand, the indoor blower will  
run on the corresponding cooling speed.  
TYPICAL G61MP FIELD WIRING DIAGRAM  
FIGURE 51  
Page 36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE 10  
Field Wiring Applications  
DIP Switch Settings and On−Board Links  
W915  
W951  
Thermostat  
Wiring Connections  
(Y1 to Y2)  
Two−Stage  
Cooling  
DIP Switch 1  
(O to R)  
Heat Pumps  
1 Heat / 1 Cool  
ON  
Intact  
Intact  
S1  
T’STAT  
CONTROL  
TERM. STRIP  
OUTDOOR  
UNIT  
NOTE − Use DIP  
switch 2 to set sec-  
ond−stage heat ON  
delay.  
OFF10 minutes.  
ON−15 minutes.  
EXISTING  
W915 JUMPER  
1 Heat / 2 Cool  
ON  
Cut  
Intact  
S1  
T’STAT  
CONTROL  
TERM. STRIP  
OUTDOOR  
UNIT  
NOTE − Use DIP  
switch 2 to set sec-  
ond−stage heat ON  
delay.  
OFF−10 minutes.  
ON−15 minutes.  
Page 37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE 10  
Field Wiring Applications (Continued)  
DIP Switch Settings and On−Board Links  
W915  
W951  
Thermostat  
Wiring Connections  
(Y1 to Y2)  
Two−Stage  
Cooling  
DIP Switch 1  
(O to R)  
Heat Pumps  
2 Heat / 2 Cool  
OFF  
Cut  
Intact  
S1  
T’STAT  
CONTROL  
TERM. STRIP  
OUTDOOR  
UNIT  
2 Heat / 1 Cool  
OFF  
Intact  
Intact  
S1  
T’STAT  
CONTROL  
TERM. STRIP  
OUTDOOR  
UNIT  
EXISTING  
W915 JUMPER  
NOTE Do NOT make a wire connection between the room thermostat L terminal and the L terminal of the G61MP  
integrated control.  
Page 38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TWO−STAGE INTEGRATED CONTROL BOARD  
1/4" QUICK CONNECT TERMINALS  
SENSE = 120 VAC OUTPUT TO FLAME SENSER  
NEUTRALS= 120 VAC NEUTRAL  
PARK = DEAD TERMINAL FOR UNUSED BLOWER LEAD  
HEAT LOW = 120 VAC OUTPUT TO CIRC BLWR −− LOW HT SPEED  
AND CONTINUOUS FAN  
HEAT HIGH/ COOL LOW = 120 VAC OUTPUT TO CIRC BLWR −−  
HIGH HEAT AND LOW COOL SPEED  
COOL HIGH = 120 VAC OUTPUT TO CIRC BLWR −− HIGH COOL SPEED  
DIAGNOSTIC  
LEDs  
THERMOSTAT CONNECTIONS (TB1)  
DIP  
SWITCHES  
ON−BOARD  
JUMPERS  
1= ERROR CODE RECALL  
H= 24V HUMIDIFIER OUTPUT  
L= DO NOT USE  
DIP SWITCH FUNCTIONS  
W915  
W951  
DIP SWITCH(ES)  
FUNCTION  
1 −− 2 Stage T’stat  
2 −− 2nd Stage Delay  
3 & 4 −− Heat Off Delay  
5 −− Cool Off Delay  
Selects t/stat type (single or two−stage)  
Second stage ON delay (single−stage t’stat)  
Heating fan OFF delay  
Cooling fan OFF delay  
FIGURE 52  
Page 39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INTEGRATED CONTROL BOARD DIP SWITCH SETTINGS AND JUMPERS  
FIGURE 53  
Page 40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TYPICAL G61MP WIRING DIAGRAM  
FIGURE 54  
Page 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE 11  
Heating Blower−Off Delay Switch Settings  
Integrated Control Board  
G61MP units are equipped with a two−stage integrated  
control. This control manages ignition timing and fan off  
delays based on selections made using the control DIP  
switches and jumpers. The control includes an internal  
watchguard feature which automatically resets the ignition  
control when it has been locked out. After one hour of con-  
tinuous thermostat demand for heat, the watchguard will  
break and remake thermostat demand to the furnace and  
automatically reset the control to relight the furnace.  
Blower Off Delay  
(Seconds)  
60  
Switch 3  
Switch 4  
Off  
Off  
On  
On  
On  
Off  
Off  
On  
90  
120  
180  
Switch 5 −− Cooling Blower−Off Delay −− The cooling  
blower−off delay (time that the blower operates after the  
cooling demand has been satisfied) can be adjusted by  
moving switch 5 on the integrated control board. The  
switch is factory−set in the OFF position, which provides a  
cooling blower−off delay of 45 seconds. If the switch is  
toggled to the ON position, it will provide a 2−second cool-  
ing blower−off delay  
Switch 1 −− Thermostat Selection −This unit may be used  
with either a single−stage or two−stage thermostat. The  
thermostat selection is made using a DIP switch which  
must be properly positioned for the particular application.  
The DIP switch is factory−positioned for use with a two−  
stage thermostat. If a single−stage thermostat is to be used,  
the DIP switch must be repositioned.  
On−board jumper W951, which connects terminals R and O  
on the integrated control board, must be cut when the fur-  
nace is installed in applications which include a heat pump  
unit and a thermostat which features dual fuel use. If the  
jumper is left intact, terminal ꢁO" will remain energized elim-  
inating the HEAT MODE in the heat pump.  
a − Select ꢁOFF" for two−stage heating operation con-  
trolled by a two−stage heating thermostat (factory set-  
ting);  
b − Select ꢁON" for two−stage heating operation con-  
trolled by a single−stage heating thermostat. This set-  
ting provides a timed delay before second−stage heat  
is initiated.  
On−board jumper W915, which connects terminals Y1 and  
Y2 on the integrated control board, must be cut if two−stage  
cooling will be used. If the jumper is not cut the outdoor unit  
will operate in first−stage cooling only.  
Switch 2 −− Second Stage Delay (Used with Single−  
Stage Thermostat Only) −− This switch is used to deter-  
mine the second stage on delay when a single−stage ther-  
mostat is being used. The switch is factory−set in the OFF  
position, which provides a 10−minute delay before second−  
stage heat is initiated. If the switch is toggled to the ON  
position, it will provide a 15−minute delay before second−  
stage heat is initiated. This switch is only activated when  
the thermostat selector jumper is positioned for SINGLE−  
stage thermostat use.  
Unit Start−Up  
FOR YOUR SAFETY READ BEFORE OPERATING  
WARNING  
Do not use this furnace if any part has been under-  
water. A flood−damaged furnace is extremely dan-  
gerous. Attempts to use the furnace can result in  
fire or explosion. Immediately call a qualified ser-  
vice technician to inspect the furnace and to replace  
all gas controls, control system parts, and electrical  
parts that have been wet or to replace the furnace,  
if deemed necessary.  
Switches 3 and 4 −− Heating Blower−Off Delay −− The  
heating blower−on delay of 45 seconds is not adjustable.  
The heating blower−off delay (time that the blower operates  
after the heating demand has been satisfied) can be ad-  
justed by moving switches 3 and 4 on the integrated control  
board. The unit is shipped from the factory with a heating  
blower−off delay of 90 seconds. The heating blower off  
delay affects comfort and is adjustable to satisfy individual  
applications. Adjust the blower off delay to achieve a sup-  
ply air temperature between 90° and 110°F at the exact  
moment that the blower is de−energized. Longer off delay  
settings provide lower supply air temperatures; shorter set-  
tings provide higher supply air temperatures.Table 11 pro-  
vides the blower off timings that will result from different  
switch settings.  
WARNING  
Danger of explosion. Can cause injury  
or product or property damage. Should  
the gas supply fail to shut off or if  
overheating occurs, shut off the gas  
valve to the furnace before shutting off  
the electrical supply.  
Page 42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4 − This furnace is equipped with an ignition device which  
automatically lights the burners. Do not try to light the  
burners by hand.  
CAUTION  
Before attempting to perform any service or mainte-  
nance, turn the electrical power to unit OFF at dis-  
connect switch.  
5 − Remove the upper access panel.  
6 − White Rodgers 36E Gas Valve − Move gas valve  
switch to OFF. See figure 55 for the White Rodgers  
36E valve.  
Priming Condensate Trap  
Honeywell VR8205 Gas Valve − Move switch on gas  
The condensate trap should be primed with water prior to  
start−up to ensure proper condensate drainage. Either  
pour 10 fl. oz. (300 ml) of water into the trap, or follow  
these steps to prime the trap:  
valve clockwise  
56.  
to OFF. Do not force. See figure  
7 − Wait five minutes to clear out any gas. If you then smell  
gas, STOP! Immediately call your gas supplier from a  
neighbor’s phone. Follow the gas supplier’s instruc-  
tions. If you do not smell gas go to next step.  
1 − Follow the lighting instructions to place the unit into op-  
eration.  
2 − Set the thermostat to initiate a heating demand.  
WHITE RODGERS 36E SERIES GAS VALVE  
3 − Allow the burners to fire for approximately 3 minutes.  
4 − Adjust the thermostat to deactivate the heating de-  
mand.  
HIGH FIRE  
MANIFOLD  
PRESSURE  
ADJUSTMENT  
ON SIDE  
5 − Wait for the combustion air inducer to stop. Set the  
thermostat to initiate a heating demand and again al-  
low the burners to fire for approximately 3 minutes.  
(under cap)  
6 − Adjust the thermostat to deactivate the heating de-  
mand and again wait for the combustion air inducer to  
stop. At this point, the trap should be primed with suffi-  
cient water to ensure proper condensate drain opera-  
tion.  
MANIFOLD  
PRESSURE  
TAP ON SIDE  
LOW FIRE MANIFOLD  
PRESSURE ADJUSTMENT  
ON SIDE (under cap)  
INLET PRESSURE  
TAP ON SIDE  
BEFORE LIGHTING the unit, smell all around the fur-  
nace area for gas. Be sure to smell next to the floor be-  
cause some gas is heavier than air and will settle on the  
floor.  
GAS VALVE SHOWN IN OFF POSITION  
FIGURE 55  
HONEYWELL VR8205 SERIES GAS VALVE  
HIGH FIRE  
ADJUSTING SCREW  
(under cap)  
The gas valve on the G61MP will be be equipped with a  
gas control switch (lever). Use only your hand to move  
the switch. Never use tools. If the the switch will not move  
by hand, do not try to repair it. Force or attempted repair  
may result in a fire or explosion.  
MANIFOLD  
PRESSURE  
TAP  
Placing the furnace into operation:  
G61MP units are equipped with an automatic ignition  
system. Do not attempt to manually light burners on this  
furnace. Each time the thermostat calls for heat, the  
burners will automatically light. The ignitor does not get  
hot when there is no call for heat on units with this ignition  
system.  
LOW FIRE  
ADJUSTING SCREW  
(under cap)  
INLET PRESSURE TAP  
GAS VALVE SHOWN IN OFF POSITION  
FIGURE 56  
8 − White Rodgers 36E Gas Valve − Move gas valve switch  
to ON. See figure 55 for the White Rodgers 36E  
valve.  
WARNING  
If you do not follow these instructions exactly, a fire  
or explosion may result causing property damage,  
personal injury or death.  
Honeywell VR8205 Gas Valve − Move switch on gas  
valve counterclockwise  
to ON. Do not force.  
9 − Replace the upper access panel.  
1 − STOP! Read the safety information at the beginning of  
10− Turn on all electrical power to to the unit.  
11− Set the thermostat to desired setting.  
this section.  
2 − Set the thermostat to the lowest setting.  
3 − Turn off all electrical power to the unit.  
NOTE − When unit is initially started, steps 1 through 11  
may need to be repeated to purge air from gas line.  
Page 43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
12− If the appliance will not operate, follow the instructions  
ꢁTurning Off Gas to Unit" and call your service techni-  
cian or gas supplier.  
2 − Tee into the gas valve regulator vent hose and connect  
test gauge ꢁ−" connection.  
TABLE 12  
Turning Off Gas to Unit  
3
Gas Flow Rate (Ft. /Hr.)  
1 − Set the thermostat to the lowest setting.  
Gas Meter Size  
1/2 cu ft Dial  
Seconds for 1  
Revolution  
1 cu ft Dial  
360  
300  
257  
225  
200  
180  
164  
150  
138  
129  
120  
113  
106  
100  
95  
2 − Turn off all electrical power to the unit if service is to be  
performed.  
10  
12  
14  
16  
18  
20  
22  
24  
26  
28  
30  
32  
34  
36  
38  
40  
42  
44  
46  
48  
50  
52  
54  
56  
58  
60  
180  
150  
129  
113  
100  
90  
82  
75  
69  
64  
60  
56  
53  
50  
47  
45  
43  
41  
39  
38  
36  
35  
33  
32  
31  
30  
3 − Remove the upper access panel.  
4 − White Rodgers 36E Gas Valve − Move gas valve  
switch to OFF.  
Honeywell VR8205 Gas Valve − Move switch on gas  
valve clockwise  
to OFF. Do not force.  
5 − Replace the upper access panel.  
Gas Pressure Adjustment  
Gas Flow (Approximate)  
1 − Operate unit at least 15 minutes before checking gas  
flow. Determine the time in seconds for one revolu-  
tions of gas through the meter. A portable LP gas me-  
ter (17Y44) is available for LP applications.  
90  
86  
2 − Compare the number of seconds and the gas meter  
size in table 12 to determine the gas flow rate. Multiply  
the gas flow rate by the heating value to determine the  
unit input rate. If manifold pressure is correct and the  
unit input rate is incorrect, check gas orifices for proper  
size and restriction.  
82  
78  
75  
72  
69  
67  
3 − Remove temporary gas meter if installed.  
64  
NOTE To obtain accurate reading, shut off all other gas  
62  
60  
appliances connected to meter.  
Supply Pressure Measurement  
3 − Start unit on low heat (68% rate) and allow 5 minutes  
for unit to reach steady state.  
A threaded plug on the inlet side of the gas valve provides  
access to the supply pressure tap. Remove the threaded  
plug, install a field−provided barbed fitting and connect a  
manometer to measure supply pressure. Replace the  
threaded plug after measurements have been taken.  
4 − While waiting for the unit to stabilize, notice the flame.  
Flame should be stable and should not lift from burner.  
Natural gas should burn blue.  
5 − After allowing unit to stabilize for 5 minutes, record  
manifold pressure and compare to value given in table  
13.  
Manifold Pressure Measurement  
To correctly measure manifold pressure, the differential  
pressure between the positive gas manifold and the nega-  
tive burner box must be considered. Use pressure test  
adapter kit (available as Lennox part 10L34) to assist in  
measurement.  
6 − Repeat steps 3, 4 and 5 on high heat.  
NOTE − Shut unit off and remove manometer as soon as an  
accurate reading has been obtained. Take care to remove  
barbed fitting and replace threaded plug.  
1 − Remove the threaded plug from the outlet side of the  
gas valve and install a field−provided barbed fitting.  
Connect test gauge ꢁ+" connection to barbed fitting to  
measure manifold pressure.  
CAUTION  
Do not attempt to make adjustments to the gas valve.  
Page 44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE 13  
Manifold Pressure (Outlet) inches w.c.  
Altitude (feet)  
0−2000  
2001−4500  
4501−5500  
5501−6500  
6501−7500  
7501−10000  
Model Number  
Fuel  
Low High  
Fire Fire  
Low High  
Fire Fiire  
Low High  
Fire Fiire  
Low High  
Fire Fiire  
Low High  
Fire Fiire  
Low High  
Fire Fiire  
Natural  
1.7  
3.5  
1.7  
4.9  
1.7  
4.9  
3.5  
1.7  
4.9  
1.7  
4.9  
3.5  
1.7  
4.9  
1.7  
4.9  
3.5  
1.7  
4.9  
1.7  
4.9  
3.5  
1.7  
4.9  
1.7  
4.9  
3.5  
045, 070, 090, 110,  
135  
Propane 4.9  
Natural 1.7  
Propane 4.9  
10.0  
3.5  
10.0  
3.4  
10.0  
3.3  
10.0  
3.2  
10.0  
3.1  
10.0  
3.5  
071, 091, 111  
10.0  
10.0  
10.0  
10.0  
10.0  
10.0  
High Altitude Information  
NOTE − In Canada, certification for installations at eleva-  
tions over 4500 feet (1372 m) is the jurisdiction of local au-  
thorities.  
The combustion air pressure switches are factory−set and  
require no adjustment.  
NOTE − A natural to L.P. propane gas changeover kit is nec-  
essary to convert this unit. Refer to the changeover kit  
installation instruction for the conversion procedure.  
The manifold pressure may require adjustment to ensure  
proper operation at higher altitudes. Refer to table 13 for  
proper manifold pressure settings at varying altitudes.  
Refer to table 14 for required pressure switch changes and  
conversion kits at varying altitudes.  
TABLE 14  
Conversion Kit Requirements  
High Altitude  
Orifice Kit  
Natural Gas  
Only  
High Altitude Pressure Switch Kit  
ORDER TWO EACH  
LPG/Propane Kit  
LPG/Propane to  
Natural Gas Kit  
Input  
1
7501−10,000 ft. 2000−4500 ft. 4501−7500 ft. 7501−10,000 ft. 0−7500 ft. 7501−10,000 ft. 0−7500 ft.  
7501−10,000 ft.  
44W49 + 44W51  
44W49 + 44W51  
44W49 + 47M82  
44W49 + 44W51  
44W49 + 47M82  
44W49 + 44W51  
44W49 + 47M82  
44W49 + 44W51  
−045  
−070  
−071  
−090  
−091  
−110  
−111  
−135  
44W51  
44W51  
47M82  
44W51  
47M82  
44W51  
47M82  
44W51  
− − −  
− − −  
− − −  
− − −  
44W48  
44W48  
44W48  
44W48  
44W48  
44W48  
44W48  
44W48  
44W50  
44W50  
44W50  
44W50  
44W50  
44W50  
44W50  
44W50  
44W49  
44W49  
44W49  
44W49  
44W49  
44W49  
44W49  
44W49  
− − −  
56M06  
26W83  
56M21  
26W86  
75M22  
56M23  
56M93  
24W49  
− − −  
24W49  
75M22  
26W85  
− − −  
26W85  
− − −  
56M22  
− − −  
56M22  
56M93  
1
High Altitude Orifice Kit is required and must be ordered separately for applications from 7501 to 10,000 ft.  
Page 45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Testing for Proper Venting and Sufficient Combustion Air for Non−Direct Vent Applications  
sufficient combustion/make-up air must be provided.  
The venting system should be re-sized to approach  
the minimum size as determined by using the ap-  
propriate tables in appendix G in the current standards  
WARNING  
CARBON MONOXIDE POISONING HAZARD!  
of the National Fuel Gas Code ANSI−Z223.1/NPFA 54  
in the U.S.A., and the appropriate Natural Gas and  
Propane appliances venting sizing tables in the cur-  
rent standard of the CSA−B149 Natural Gas and Pro-  
pane Installation Codes in Canada.  
Failure to follow the steps outlined below for each  
appliance connected to the venting system being  
placed into operation could result in carbon monox-  
ide poisoning or death.  
The following steps shall be followed for each ap-  
pliance connected to the venting system being  
placed into operation, while all other appliances con-  
nected to the venting system are not in operation.  
9 − After determining that each appliance remaining  
connected to the common venting system properly  
vents when tested as indicated in step 3, return  
doors, windows, exhaust fans, fireplace dampers  
and any other gas-burning appliance to their previous  
condition of use.  
After the G61MP gas furnace has been started, the follow-  
ing test should be conducted to ensure proper venting and  
sufficient combustion air has been provided to the G61MP,  
as well as to other gas-fired appliances which are separate-  
ly vented.  
Other Unit Adjustments  
Primary and Secondary Limits  
If a G61MP furnace replaces a Category I furnace which  
was commonly vented with another gas appliance, the size  
of the existing vent pipe for that gas appliance must be  
checked. Without the heat of the original furnace flue prod-  
ucts, the existing vent pipe is probably oversized for the  
single water heater or other appliance. The vent should be  
checked for proper draw with the remaining appliance.  
The primary limit is located on the heating compartment  
vestibule panel. The secondary limits are located in the  
blower compartment, attached to the back side of the blow-  
er. These limits are factory set and require no adjustment.  
Flame Rollout Switches (Two)  
These manually reset switches are located on the burner  
box. If tripped, check for adequate combustion air before  
resetting.  
The test should be conducted while all appliances (both in  
operation and those not in operation) are connected to the  
venting system being tested. If the venting system has  
been installed improperly, or if provisions have not been  
made for sufficient amounts of combustion air, corrections  
must be made as outlined in the previous section.  
Pressure Switches (Two or Four)  
The pressure switches are located in the heating compart-  
ment on the combustion air inducer. These switches check  
for proper combustion air inducer operation before allow-  
ing ignition trial. The switches are factory−set and require  
no adjustment.  
1 − Seal any unused openings in the venting system.  
2 − Visually inspect the venting system for proper size and  
horizontal pitch. Determine there is no blockage or re-  
striction, leakage, corrosion, or other deficiencies  
which could cause an unsafe condition.  
Back−Up Secondary Limit (090, 110 & 135 Models)  
The back−up secondary limit is located on the combustion  
air inducer. This switch protects the plastic components  
from overheating due to indoor blower motor failure. If  
tripped, check for proper blower operation before resetting.  
3 − To the extent that it is practical, close all building doors  
and windows and all doors between the space in which  
the appliances connected to the venting system are lo-  
cated and other spaces of the building.  
Temperature Rise  
After the furnace has been started and supply and return air  
temperatures have been allowed to stabilize, check the  
temperature rise. If necessary, adjust the blower speed to  
maintain the temperature rise within the range shown on  
the unit nameplate. Increase the blower speed to decrease  
the temperature. Decrease the blower speed to increase  
the temperature rise. Failure to do adjust the temperature  
rise may cause erratic limit operation.  
4 − Close fireplace dampers.  
5 − Turn on clothes dryers and any appliances not con-  
nected to the venting system. Turn on any exhaust  
fans, such as range hoods and bathroom exhausts, so  
they will operate at maximum speed. Do not operate a  
summer exhaust fan.  
6 − Follow the lighting instruction to place the appliance  
being inspected into operation. Adjust thermostat so  
appliance will operate continuously.  
Thermostat Heat Anticipation  
Set the heat anticipator setting (if adjustable) according to  
the amp draw listed on the wiring diagram that is attached  
to the unit.  
7 − Use the flame of match or candle to test for spillage of  
flue gases at the draft hood relief opening after 5 min-  
utes of main burner operation.  
Electrical  
8 − If improper venting is observed during any of the  
above tests, the venting system must be corrected or  
1 − Check all wiring for loose connections.  
Page 46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2 − Check for the correct voltage at the furnace (furnace  
operating).  
sure. After one hour of continuous thermostat demand for  
heat, the Watchguard will break and remake thermostat de-  
mand to the furnace and automatically reset the control to  
begin the ignition sequence.  
3 − Check amp-draw on the blower motor.  
Motor Nameplate__________Actual__________  
NOTE − Do not secure the electrical conduit directly to the  
air ducts or structure.  
Exhaust and Air Intake Pipe  
1 − Check exhaust and air intake connections for tightness  
and to make sure there is no blockage.  
Blower Speeds  
NOTE − CFM readings are taken external to unit with a dry  
evaporator coil and without accessories.  
1 − Turn off electrical power to furnace.  
2 − Remove blower access panel.  
2 − Are pressure switches closed? Obstructed exhaust  
pipe will cause unit to shut off at pressure switches.  
Check termination for blockages.  
3 − Reset manual flame rollout switches on burner box  
cover.  
3 − Disconnect existing speed tap at control board speed  
terminal.  
Failure To Operate  
NOTE − Termination of any unused motor leads must be  
insulated.  
If the unit fails to operate, check the following:  
1 − Is the thermostat calling for heat?  
2 − Are access panels securely in place?  
3 − Is the main disconnect switch closed?  
4 − Is there a blown fuse?  
4 − Refer to blower speed selection chart on unit wiring dia-  
gram for desired heating or cooling speed. See blower  
performance data beginning on Page 48.  
5 − Connect selected speed tap at control board speed  
terminal.  
5 − Is the filter dirty or plugged? Dirty or plugged filters will  
cause the limit control to shut the unit off.  
6 − Resecure blower access panel.  
7 − Turn on electrical power to furnace.  
Electronic Ignition  
6 − Is gas turned on at the meter?  
7 − Is the manual main shut-off valve open?  
8 − Is the internal manual shut-off valve open?  
The integrated control has an added feature of an internal  
Watchguard control. The feature serves as an automatic re-  
set device for ignition control lockout caused by ignition fail-  
ure. This type of lockout is usually due to low gas line pres-  
9 − Is the unit ignition system in lock out? If the unit locks out  
again, inspect the unit for blockages.  
Page 47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Blower Performance Data  
G61MP−36B−045 PERFORMANCE (Less Filter)  
G61MP−48C−090 PERFORMANCE (Less Filter)  
Air Volume / Watts at Different Blower Speeds  
External  
Air Volume / Watts at Different Blower Speeds  
External  
Medium−  
High  
Medium−  
Low  
Medium−  
High  
Medium−  
Low  
Static  
Pressure  
in. w.g.  
Static  
Pressure  
in. w.g.  
High  
Low  
High  
Low  
cfm Watts cfm Watts cfm Watts cfm Watts  
1555 630 1410 585 1190 520 1030 435  
1515 605 1385 555 1190 485 1020 415  
1470 580 1345 520 1170 455 1010 400  
1410 555 1310 495 1155 440 1000 385  
1350 535 1250 465 1120 410 980 360  
1290 505 1205 450 1080 390 950 345  
1220 485 1145 420 1020 365 905 320  
1145 460 1080 400 975 345 860 300  
1050 425 985 365 870 320 785 285  
945 410 900 345 825 305 730 270  
cfm Watts cfm Watts cfm Watts cfm Watts  
2180 930 1835 790 1520 630 1280 510  
2135 885 1825 750 1510 610 1275 495  
2085 840 1810 720 1505 580 1270 475  
2030 800 1775 685 1500 565 1265 460  
1940 760 1735 650 1480 535 1250 440  
1865 725 1660 600 1430 505 1215 425  
1740 670 1590 575 1380 475 1175 410  
1645 640 1475 520 1290 450 1105 375  
1540 600 1340 465 1175 405 1020 355  
1335 540 1170 440 1070 375 950 330  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.  
G61MP−48C−110 PERFORMANCE (Less Filter)  
G61MP−36B−070 PERFORMANCE (Less Filter)  
Air Volume / Watts at Different Blower Speeds  
External  
Air Volume / Watts at Different Blower Speeds  
External  
Medium−  
High  
Medium−  
Low  
Static  
Pressure  
in. w.g.  
Medium−  
High  
Medium−  
Low  
Static  
Pressure  
in. w.g.  
High  
Low  
High  
Low  
cfm Watts cfm Watts cfm Watts cfm Watts  
2160 880 1880 755 1490 602 1235 485  
2100 850 1855 730 1480 585 1230 475  
2035 805 1815 690 1475 560 1225 460  
1965 750 1755 650 1475 545 1220 445  
1885 725 1715 625 1465 510 1215 430  
1780 680 1630 580 1420 490 1150 400  
1690 660 1550 550 1360 460 1110 380  
1575 620 1410 505 1210 405 1035 350  
1375 550 1230 450 1125 380 970 325  
1225 520 1120 415 1050 365 885 310  
cfm Watts cfm Watts cfm Watts cfm Watts  
1640 660 1415 575 1160 485 1005 410  
1600 635 1395 550 1160 460 1000 385  
1540 605 1370 525 1160 445 995 375  
1495 580 1345 505 1145 425 990 365  
1420 545 1275 480 1125 395 965 345  
1360 525 1245 450 1080 375 945 325  
1275 490 1165 410 1025 350 900 305  
1170 465 1085 385 965 335 860 295  
1080 440 1010 360 865 310 775 270  
945 400 840 320 765 275 710 245  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.  
G61MP−36B−071 PERFORMANCE (Less Filter)  
Air Volume / Watts at Different Blower Speeds  
External  
Medium−  
High  
Medium−  
Low  
Static  
Pressure  
in. w.g.  
High  
Low  
cfm Watts cfm Watts cfm Watts cfm Watts  
1460 620 1215 570 965 445 785 375  
1420 590 1215 545 990 425 815 365  
1365 550 1195 505 980 410 810 350  
1325 525 1170 490 980 390 820 335  
1255 495 1155 455 945 365 795 320  
1190 465 1080 425 915 345 785 305  
1120 440 1050 395 865 320 755 285  
1035 410 975 365 790 295 695 255  
900 375 865 330 715 275 615 235  
795 350 745 300 600 245 510 215  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.  
Page 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
G61MP−60C−090 PERFORMANCE (Less Filter)  
Air Volume / Watts at Different Blower Speeds  
Bottom Return Air, Side Return Air with Optional RAB Single Side Return Air − Air volumes in bold require field  
Return Air Base, Return Air from Both Sides or Return fabricated transition to accommodate 20 x 25 x 1 in. air  
External  
Static  
Air from Bottom and One Side.  
filter in order to maintain proper air velocity.  
Pressure  
in. w.g.  
Medium−  
High  
Medium−  
Low  
Medium−  
High  
Medium−  
Low  
High  
Low  
High  
Low  
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts  
2840 1450 2345 1105 1895 900 1515 700 2835 1495 2340 1155 1800 895 1440 695  
2765 1415 2365 1080 1950 885 1580 700 2785 1475 2345 1135 1805 865 1515 690  
2695 1385 2345 1050 1985 870 1620 695 2715 1435 2275 1080 1825 845 1560 685  
2605 1335 2315 1030 1990 850 1645 690 2620 1380 2260 1035 1840 825 1600 680  
2530 1300 2265 990 1990 825 1665 675 2550 1350 2230 1015 1845 815 1620 670  
2420 1260 2210 955 1970 800 1675 665 2450 1305 2175 990 1850 790 1615 655  
2330 1220 2145 925 1930 775 1665 650 2365 1270 2130 940 1830 775 1615 640  
2250 1190 2050 885 1875 745 1645 630 2240 1205 2070 915 1815 760 1595 620  
2135 1140 2000 865 1810 715 1620 615 2185 1190 1965 865 1775 745 1555 605  
2030 1090 1885 830 1720 685 1560 590 2015 1150 1820 820 1690 715 1440 580  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
G61MP−60C−091 PERFORMANCE (Less Filter)  
Air Volume / Watts at Different Blower Speeds  
Bottom Return Air, Side Return Air with Optional RAB Single Side Return Air − Air volumes in bold require field  
Return Air Base, Return Air from Both Sides or Return fabricated transition to accommodate 20 x 25 x 1 in. air  
External  
Static  
Air from Bottom and One Side.  
filter in order to maintain proper air velocity.  
Pressure  
in. w.g.  
Medium−  
High  
Medium−  
Low  
Medium−  
High  
Medium−  
Low  
High  
Low  
High  
Low  
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts  
2320 1230 2240 960 1970 810 1505 690 2350 1275 2195 960 1920 830 1535 680  
2250 1195 2155 910 1950 805 1610 665 2270 1240 2125 930 1910 800 1580 665  
2185 1165 2080 890 1915 775 1630 660 2200 1190 2060 905 1875 775 1570 655  
2060 1120 1965 835 1795 710 1590 620 2070 1135 1945 830 1830 725 1545 625  
1995 1095 1890 805 1720 690 1535 600 1935 1095 1875 815 1750 705 1495 605  
1920 1060 1860 790 1705 665 1540 580 1910 1070 1820 780 1715 670 1510 585  
1800 1025 1750 755 1605 640 1485 560 1825 1050 1720 760 1635 645 1450 555  
1710 1000 1625 735 1500 605 1380 535 1705 1025 1605 725 1485 615 1360 535  
1600 975 1545 700 1455 585 1335 515 1605 995 1515 700 1440 585 1320 510  
1475 940 1405 670 1305 555 1105 450 1460 950 1370 665 1285 555 1175 480  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
Page 49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Blower Performance Data  
G61MP−60C−110 PERFORMANCE (Less Filter)  
Air Volume / Watts at Different Blower Speeds  
Air Volume / Watts at Different Blower Speeds  
Bottom Return Air, Side Return Air with Optional RAB Single Side Return Air − Air volumes in bold require field  
Return Air Base, Return Air from Both Sides or Return fabricated transition to accommodate 20 x 25 x 1 in. air  
External  
Static  
Air from Bottom and One Side.  
filter in order to maintain proper air velocity.  
Pressure  
in. w.g.  
Medium−  
High  
Medium−  
Low  
Medium−  
High  
Medium−  
Low  
High  
Low  
High  
Low  
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts  
2720 1385 2410 1090 2055 935 1620 710 2625 1350 2310 1080 1885 885 1515 700  
2665 1355 2385 1075 2025 885 1730 735 2570 1330 2325 1060 1910 865 1575 700  
2585 1315 2350 1015 2030 865 1680 690 2410 1305 2285 1035 1930 845 1620 690  
2505 1275 2290 990 2025 840 1695 675 2425 1265 2230 990 1925 825 1635 675  
2435 1250 2235 940 2030 830 1695 660 2335 1220 2175 950 1910 810 1640 660  
2350 1205 2170 930 1975 790 1735 665 2270 1195 2120 935 1895 785 1640 640  
2255 1185 2100 895 1915 765 1720 650 2170 1155 2045 885 1860 765 1630 630  
2160 1150 2005 840 1865 730 1680 635 2110 1130 1950 855 1795 730 1590 610  
2020 1090 1905 825 1810 710 1625 610 2035 1090 1885 820 1745 705 1540 580  
1910 1050 1820 795 1705 675 1540 590 1900 1055 1760 780 1665 680 1470 565  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
G61MP−60C−111 PERFORMANCE (Less Filter)  
Air Volume / Watts at Different Blower Speeds  
Air Volume / Watts at Different Blower Speeds  
Bottom Return Air, Side Return Air with Optional RAB Single Side Return Air − Air volumes in bold require field  
Return Air Base, Return Air from Both Sides or Return fabricated transition to accommodate 20 x 25 x 1 in. air  
External  
Static  
Air from Bottom and One Side.  
filter in order to maintain proper air velocity.  
Pressure  
in. w.g.  
Medium−  
High  
Medium−  
Low  
Medium−  
High  
Medium−  
Low  
High  
Low  
High  
Low  
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts  
2475 1305 2275 1010 1800 870 1425 680 2460 1355 2210 1045 1850 860 1435 670  
2395 1260 2215 980 1850 850 1495 675 2395 1320 2170 1010 1850 830 1490 660  
2340 1220 2165 945 1860 830 1535 665 2280 1270 2115 965 1875 810 1525 650  
2255 1205 2085 915 1855 805 1545 655 2225 1250 2075 940 1835 785 1530 640  
2165 1160 2000 880 1820 780 1540 645 2150 1210 2005 905 1800 760 1535 626  
2055 1140 1920 845 1780 755 1535 625 2050 1155 1935 885 1760 740 1555 620  
1995 1120 1845 825 1720 725 1485 605 1975 1140 1835 845 1660 705 1480 595  
1880 1075 1760 800 1680 710 1470 595 1870 1110 1745 810 1620 685 1440 575  
1795 1060 1640 755 1595 680 1415 570 1760 1065 1645 770 1510 655 1370 550  
1680 1020 1530 725 1505 645 1345 550 1635 1025 1545 740 1415 620 1295 530  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
Page 50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G61MP−60D−135 PERFORMANCE (Less Filter)  
Air Volume / Watts at Different Blower Speeds  
Air Volume / Watts at Different Blower Speeds  
Bottom Return Air, Side Return Air with Optional RAB Single Side Return Air − Air volumes in bold require field  
Return Air Base, Return Air from Both Sides or Return fabricated transition to accommodate 20 x 25 x 1 in. air  
External  
Static  
Air from Bottom and One Side.  
filter in order to maintain proper air velocity.  
Pressure  
in. w.g.  
Medium−  
High  
Medium−  
Low  
Medium−  
High  
Medium−  
Low  
High  
Low  
High  
Low  
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts  
2730 1465 2425 1125 2055 915 1560 680 2665 1440 2325 1100 1865 890 1410 690  
2670 1440 2400 1100 2065 890 1590 675 2615 1405 2310 1065 1915 865 1465 685  
2600 1400 2365 1070 2045 865 1620 665 2530 1370 2280 1055 1925 850 1570 675  
2525 1360 2315 1045 2035 845 1615 655 2470 1330 2235 1015 1920 825 1590 670  
2445 1325 2260 1015 2020 820 1615 645 2380 1290 2175 985 1910 805 1590 655  
2360 1280 2195 985 1960 790 1610 635 2310 1265 2120 965 1890 790 1595 645  
2290 1255 2130 965 1900 755 1600 615 2200 1230 2055 935 1835 765 1580 630  
2205 1220 2035 910 1825 730 1570 600 2120 1190 1970 900 1790 740 1545 605  
2110 1195 1945 880 1765 710 1540 580 2025 1160 1890 875 1720 710 1515 590  
1970 1120 1835 830 1680 690 1540 545 1930 1110 1800 835 1655 685 1440 570  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
Page 51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Applications Using A Single−Stage Thermostat  
Heating Sequence of Operation  
B − Heating Sequence −− Control Board Thermostat  
Selection DIP switch in ꢀSingle−Stage" Position  
NOTE − The thermostat selection DIP switch on the control  
board is factory−set in the ꢁTWO−STAGE" position.  
Applications Using a Two−Stage Thermostat  
A − Heating Sequence −− Control Board Thermostat  
Selection DIP switch in ꢀTwo−Stage" Position (Factory  
Setting)  
NOTE − In these applications, two−stage heat will be initi-  
ated by the integrated control if heating demand has not  
been satisfied after the field adjustable period (10 or 15  
minutes).  
1 − On a call for heat, thermostat first−stage contacts close  
sending a signal to the integrated control. The inte-  
grated control runs a self-diagnostic program and  
checks high temperature limit switches for normally  
closed contacts and pressure switches for normally  
open contacts.The combustion air inducer is ener-  
gized at low speed and the humidifier terminal is ener-  
gized.  
1 − On a call for heat, thermostat first−stage contacts close  
sending a signal to the integrated control. The inte-  
grated control runs a self-diagnostic program and  
checks high temperature limit switches for normally  
closed contacts and pressure switches for normally  
open contacts.The combustion air inducer is ener-  
gized at low speed and the humidifier terminal is ener-  
gized.  
2 − Once the control receives a signal that the low−fire  
pressure switch has closed, the combustion air induc-  
er begins a 15−second pre−purge in low speed.  
3 − After the pre−purge is complete, a 20−second initial ig-  
nitor warm−up period begins. The combustion air in-  
ducer continues to operate at low speed.  
2 − Once the control receives a signal that the low−fire  
pressure switch has closed, the combustion air induc-  
er begins a 15−second pre−purge in low speed.  
3 − After the pre−purge is complete, a 20−second initial ig-  
nitor warm−up period begins. The combustion air in-  
ducer continues to operate at low speed.  
4 − After the 20−second warm−up period has ended, the gas  
valve is energized on low fire (first stage) and ignition oc-  
curs. At the same time, the control module sends a sig-  
nal to begin an indoor blower 45−second ON−delay.  
When the delay ends, the indoor blower motor is ener-  
gized on the low fire heating speed. The furnace will  
continue this operation as long as the thermostat has  
a first−stage heating demand.  
4 − After the 20−second warm−up period has ended, the gas  
valve is energized on low fire (first stage) and ignition oc-  
curs. At the same time, the control module sends a sig-  
nal to begin an indoor blower 45−second ON−delay.  
When the delay ends, the indoor blower motor is ener-  
gized on the low−fire heating speed. The integrated  
control also initiates a second−stage on delay (factory−  
set at 10 minutes; adjustable to 15 minutes).  
5 − If second−stage heat is required, the thermostat sec-  
ond−stage heat contacts close and send a signal to the  
integrated control. The integrated control initiates a  
30−second second−stage recognition delay.  
5 − If the heating demand continues beyond the second−  
stage on delay, the integrated control energizes the  
combustion air inducer at high speed. The control also  
checks the high−fire (second stage) pressure switch to  
make sure it is closed. Once the control receives a sig-  
nal the high−fire pressure switch is closed, the high−fire  
(second stage) gas valve is energized and the indoor  
blower motor is energized for operation at the high−fire  
heating speed.  
6 − At the end of the recognition delay, the integrated con-  
trol energizes the combustion air inducer at high  
speed. The control also checks the high−fire (second  
stage) pressure switch to make sure it is closed. Once  
the the control receives a signal that the high−fire pres-  
sure switch is close, the high−fire (second stage) gas  
valve is energized and the indoor blower motor is en-  
ergized for operation at the high−fire heating speed.  
7 − When the demand for high−fire (second stage) heat is  
satisfied, the combustion air inducer is switched to the  
low−fire heating speed and the high−fire (second  
stage) gas valve is de−energized. The low−fire (first  
stage) gas valve continues operation. The indoor  
blower motor is switched to the low−fire heating speed.  
8 − When the thermostat demand for low−fire (first stage)  
heat is satisfied, the gas valve is de−energized and the  
field−selected indoor blower off delay begins. The  
combustion air inducer begins a 5−second post−purge  
period.  
6 − When the thermostat heating demand is satisfied, the-  
combustion air inducer begins a 5−second post−purge.  
The field−selected indoor blower off delay begins.  
7 − When the combustion air post−purge period is com-  
plete, the inducer and humidifier terminal are de−ener-  
gized. The indoor blower is de−energized at the end of  
the off delay.  
9 − When the combustion air post−purge period is com-  
plete, the inducer and humidifier terminal are de−ener-  
gized. The indoor blower is de−energized at the end of  
the off delay.  
Page 52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3 − Remove the drain plug from the condensate trap and  
empty water. Inspect the trap then reinstall the drain  
plug.  
Service  
Cleaning Heat Exchanger  
WARNING  
ELECTRICAL SHOCK, FIRE,  
OR EXPLOSION HAZARD.  
If cleaning the heat exchanger becomes necessary, follow  
the below procedures and refer to figure 1 when disassem-  
bling unit. Use papers or protective covering in front of fur-  
nace while removing heat exchanger assembly.  
Failure to follow safety warnings exactly could result  
in dangerous operation, serious injury, death or  
property damage.  
1 − Turn off electrical and gas supplies to the furnace.  
2 − Remove the upper and lower furnace access panels.  
Improper servicing could result in dangerous opera-  
tion, serious injury, death, or property damage.  
Before servicing, disconnect all electrical power to  
furnace.  
When servicing controls, label all wires prior to dis-  
connecting. Take care to reconnect wires correctly.  
Verify proper operation after servicing.  
3 − Mark all gas valve wires and disconnect them from  
valve.  
4 − Remove gas supply line connected to gas valve. Re-  
move gas valve/manifold assembly.  
5 − Remove sensor wire from sensor. Disconnect 2-pin  
plug from the ignitor.  
6 − Disconnect wires from flame roll−out switches.  
At the beginning of each heating season, system should be  
checked as follows by a qualified service technician:  
7 − Remove burner box cover and remove four burner box  
screws at the vestibule panel and remove burner box.  
Set burner box assembly aside.  
Blower  
NOTE − G61MP−135 units are secured to the vestibule  
panel by two additional screws. These screws must be  
removed for servicing; however it is not necessary to  
replace the screws.  
Check the blower wheel for debris and clean if necessary.  
The blower motors are prelubricated for extended bearing  
life. No further lubrication is needed.  
NOTE − If necessary, clean burners at this time. Follow  
procedures outlined in Burner Cleaning section.  
8 − Loosen three clamps and remove flexible exhaust tee.  
WARNING  
9 − Remove 3/8 inch rubber cap from condensate drain  
plug and drain. Replace cap after draining.  
The blower access panel must be securely in place  
when the blower and burners are operating. Gas  
fumes, which could contain carbon monoxide, can  
be drawn into living space resulting in personal inju-  
ry or death.  
10 − Disconnect condensate drain line from the conden-  
sate trap. Remove condensate trap (it may be neces-  
sary to cut drain pipe). Remove screws that secure  
condensate collars to either side of the furnace and re-  
move collars. Remove drain tubes from cold end  
header collector box.  
Filters  
All G61MP filters are installed external to the unit. Filters  
should be inspected monthly. Clean or replace the filters  
when necessary to ensure proper furnace operation.  
Table 3 lists recommended filter sizes.  
11 − Disconnect condensate drain tubing from flue collar.  
Remove screws that secure both flue collars into  
place. Remove flue collars. It may be necessary to cut  
the exiting exhaust pipe for removal of the fittings.  
Exhaust and air intake pipes  
12 − Mark and disconnect all combustion air pressure tub-  
ing from cold end header collector box.  
Check the exhaust and air intake pipes and all connections  
for tightness and to make sure there is no blockage.  
13 − Mark and remove wires from pressure switches. Re-  
move pressure switches. Keep tubing attached to  
pressure switches.  
NOTE − After any heavy snow, ice or frozen fog event the  
furnace vent pipes may become restricted. Always check  
the vent system and remove any snow or ice that may be  
obstructing the plastic intake or exhaust pipes.  
14 − Disconnect the 3-pin plug from the combustion air in-  
ducer. Disconnect the two wires to the backup secon-  
dary limit, if applicable. Remove four screws which se-  
cure combustion air inducer to collector box. Remove  
combustion air inducer assembly. Remove ground  
wire from vest panel.  
Electrical  
1 − Check all wiring for loose connections.  
2 − Check for the correct voltage at the furnace (furnace  
operating).  
15 − Remove electrical junction box from the side of the fur-  
nace.  
3 − Check amp−draw on the blower motor.  
Motor Nameplate__________Actual__________  
16 − Mark and disconnect any remaining wiring to heating  
compartment components. Disengage strain relief  
bushing and pull wiring and bushing through the hole in  
the blower deck.  
Winterizing and Condensate Trap Care  
1 − Turn off power to the unit.  
2 − Have a shallow pan ready to empty condensate water.  
Page 53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
17 − Remove the primary limit from the vestibule panel.  
38 − Secure burner box assembly to vestibule panel using  
four existing screws. Make sure burners line up in  
center of burner ports.  
18 − Remove two screws from the front cabinet flange at  
the blower deck. Spread cabinet sides slightly to allow  
clearance for removal of heat exchanger.  
39 − Reinstall gas valve manifold assembly. Reconnect  
gas supply line to gas valve.  
19 − Remove screws along vestibule sides and bottom  
which secure vestibule panel and heat exchanger as-  
sembly to cabinet. Remove two screws from blower  
rail which secure bottom heat exchanger flange. Re-  
move heat exchanger from furnace cabinet.  
40 − Reinstall burner box cover.  
41 − Reconnect wires to gas valve.  
42 − Replace the blower compartment access panel.  
43 − Refer to instruction on verifying gas and electrical con-  
nections when re−establishing supplies.  
20 − Back wash heat exchanger with soapy water solution  
or steam. If steam is used it must be below 275°F  
(135°C) .  
44 − Follow lighting instructions to light and operate fur-  
nace for 5 minutes to ensure that heat exchanger is  
clean and dry and that furnace is operating properly.  
21 − Thoroughly rinse and drain the heat exchanger. Soap  
solutions can be corrosive. Take care to rinse entire  
assembly.  
45 − Replace heating compartment access panel.  
Cleaning the Burner Assembly  
22 − Reinstall heat exchanger into cabinet making sure that  
the clamshells of the heat exchanger assembly are  
resting on the support located at the rear of the cabi-  
net. Remove the indoor blower to view this area  
through the blower opening.  
1 − Turn off electrical and gas power supplies to furnace.  
Remove upper and lower furnace access panels.  
2 − Mark all gas valve wires and disconnect them from the  
valve.  
23 − Re-secure the supporting screws along the vestibule  
sides and bottom to the cabinet.  
3 − Disconnect the gas supply line from the gas valve. Re-  
move gas valve/manifold assembly.  
24 − Reinstall cabinet screws on front flange at blower  
deck.  
4 − Mark and disconnect sensor wire from the sensor. Dis-  
connect 2-pin plug from the ignitor at the burner box.  
25 − Reinstall the primary limit on the vestibule panel.  
5 − Remove burner box cover and remove four screws  
which secure burner box assembly to vest panel. Re-  
move burner box from the unit.  
26 − Route heating component wiring through hole in blow-  
er deck and reinsert strain relief bushing.  
NOTE − G61MP−135 units are secured to the vestibule  
panel by two additional screws. These screws must be  
removed for servicing; however it is not necessary to  
replace the screws.  
27 − Reinstall electrical junction box.  
28 − Reinstall the combustion air inducer. Reconnect the  
3−pin plug to the wire harness. Reconnect the two  
wires to the backup secondary limit, if applicable.  
6 − Use the soft brush attachment on a vacuum cleaner to  
gently clean the face of the burners. Visually inspect  
the inside of the burners and crossovers for any block-  
age caused by foreign matter. Remove any blockage.  
29 − Reinstall pressure switches and reconnect pressure  
switch wiring.  
30 − Carefully connect combustion air pressure switch  
hosing from pressure switches to proper stubs on  
cold end header collector box.  
7 − Reconnect the sensor wire and reconnect the 2−pin  
plug to the ignitor wiring harness.  
31 − Reinstall condensate collars on each side of the fur-  
nace. Reconnect drain tubing to collector box.  
8 − Reinstall the burner box assembly using the existing  
four screws. Make sure that the burners line up in the  
center of the burner ports.  
32 − Reinstall condensate trap on same side as exhaust  
pipe. Reconnect condensate drain line to the conden-  
sate trap.  
9 − Reinstall the gas valve manifold assembly. Reconnect  
the gas supply line to the gas valve. Reinstall the burn-  
er box cover.  
33 − Use securing screws to reinstall flue collars to either  
side of the furnace. Reconnect exhaust piping and ex-  
haust drain tubing.  
10 − Reconnect the gas valve wires to the gas valve.  
11 − Replace the blower compartment access panel.  
34 − Replace flexible exhaust tee on combustion air induc-  
er and flue collars. Secure using three existing hose  
clamps.  
12 − Refer to instruction on verifying gas and electrical con-  
nections when re−establishing supplies.  
35 − Reinstall burner box assembly in vestibule area.  
36 − Reconnect flame roll−out switch wires.  
13 − Follow lighting instructions to light and operate fur-  
nace for 5 minutes to ensure that heat exchanger is  
clean and dry and that furnace is operating properly.  
37 − Reconnect sensor wire and reconnect 2−pin plug from  
ignitor.  
14 − Replace heating compartment access panel.  
Page 54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Return air duct − Must be properly attached and provide  
Planned Service  
an air seal to the unit.  
A service technician should check the following items dur-  
ing an annual inspection. Power to the unit must be shut off  
for safety.  
Operating performance − Unit must be observed during  
operation to monitor proper performance of the unit and the  
vent system.  
Fresh air grilles and louvers (on the unit and in the room  
where the furnace is installed) − Must be open and unob-  
structed to provide combustion air.  
Combustion gases − Flue products must be analyzed and  
compared to the unit specifications.  
Problems detected during the inspection may make it nec-  
essary to temporarily shut down the furnace until the items  
can be repaired or replaced.  
Burners − Must be inspected for rust, dirt, or signs of water.  
Vent pipe − Must be inspected for signs of water, damaged,  
cracked or sagging pipe, or disconnected joints.  
Instruct the homeowners to pay attention to their  
furnace. Situations can arise between annual furnace in-  
spections that may result in unsafe operation. For instance,  
items innocently stored next to the furnace may obstruct  
the combustion air supply. This could cause incomplete  
combustion and the production of carbon monoxide gas.  
Unit appearance − Must be inspected for rust, dirt, signs  
of water, burnt or damaged wires, or components.  
Blower access door − Must be properly in place and pro-  
vide a seal between the return air and the room where the  
furnace is installed.  
Page 55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ignition Control Board Diagnostic Codes  
FLASH CODE  
(X + Y)  
STATUS / ERROR DESCRIPTION  
FLASH CODE DESCRIPTIONS  
Pulse  
A 1/4 second flash followed by four seconds of off time.  
Heartbeat  
Constant 1/2 second bright and 1/2 second dim cycles.  
LED flashes X times at 2Hz, remains off for two seconds, flashes Y times at 2Hz, remains off for four  
seconds, then repeats.  
X + Y  
Pulse  
Power on − Standby.  
Heartbeat  
Normal operation − signaled when heating demand initiated at thermostat.  
FLAME CODES  
1 + 2  
1 + 3  
Low flame current −− run mode.  
Flame sensed out of sequence −− flame still present.  
PRESSURE SWITCH CODES  
2 + 3  
2 + 4  
2 + 5  
2 + 6  
2 + 7  
Low pressure switch failed open.  
Low pressure switch failed closed.  
High pressure switch failed open.  
High pressure switch failed closed.  
Low pressure switch opened during ignition trial or heating demand.  
LIMIT CODE  
3 + 1  
Limit switch open.  
WATCHGUARD CODES  
4 + 1  
4 + 2  
4 + 3  
4 + 5  
4 + 6  
4 + 7  
4 + 8  
Watchguard −− Exceeded maximum number of retries.  
Watchguard −− Exceeded maximum number of retries or last retry was due to pressure switch opening.  
Watchguard −− Exceeded maximum number of retries or last retry was due to flame failure.  
Watchguard −− Limit remained open longer than three minutes.  
Watchguard −− Flame sensed out of sequence; flame signal gone.  
Ignitor circuit fault −− Failed ignitor or triggering circuitry.  
Low line voltage.  
HARD LOCKOUT CODES  
5 + 1  
5 + 2  
5 + 3  
5 + 4  
5 + 6  
Hard lockout −− Rollout circuit open or previously opened.  
Control failed self check, internal error (control will restart if error recovers).  
No Earth ground (control will restart if error recovers).  
Reversed line voltage polarity (control will restart if the error recovers).  
Low secondary (24VAC) voltage.  
Error Code Storage  
5 − After final error code is indicated, STATUS LED will  
flash to indicate normal operation.  
The ignition control stores the last ten error codes in  
memory. The codes are retained in case of power loss.  
Clearing Error Codes  
Error Code Review  
1 − Short R (2) to (1). Within 1/2 second, the STATUS LED  
will stay lit continuously to indicate that the short was  
sensed.  
1 − Short R (2) to (1). Within 1/2 second, the STATUS LED  
will stay lit continuously to indicate that the short was  
sensed.  
2 − Continue to hold the short between R (2) to (1). After 5  
seconds, STATUS LED will go from being continuously  
lit to off.  
2 − Continue to hold the short between R (2) to (1). After 5  
seconds, STATUS LED will go from being continuously  
lit to off. This indicates that error code review is pend-  
ing.  
3 − Continue to hold the short between R (2) to (1) beyond  
ten seconds after STATUS LED has turned off. STA-  
TUS LED will turn on, indicating that error codes have  
been cleared.  
3 − Remove R (2) to (1) short within ten seconds of STA-  
TUS LED turning off. This activates error code review.  
4 − Last ten error codes will be flashed on the STATUS  
LED.  
4 − Remove R (2) to (1) short. STATUS LED will flash to in-  
dicate normal operation.  
Page 56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting: Heating Sequence of Operation  
HEATING SEQUENCE OF OPERATION  
NORMAL AND ABNORMAL HEATING MODE  
POWER ON  
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.  
INDOOR BLOWER OFF. (RESET CONTROL BY  
TURNING MAIN POWER OFF.)  
NO  
NO  
CONTROL SELF−CHECK OKAY?  
POLARITY REVERSED.  
STATUS ERROR CODE 5 + 4.  
POLARITY OKAY?  
YES  
NO  
IS THERE A  
PROPER GROUND?  
SIGNAL HOLDS UNTIL UNIT IS PROPERLY GROUNDED.  
STATUS ERROR CODE 5 + 3.  
YES  
A
NORMAL OPERATION:  
STATUS LED −− PULSE  
COMBUSTION AIR INDUCER OFF.  
INDOOR BLOWER ON. HAS PRIMARY OR  
SECONDARY LIMIT RESET WITHIN 3 MINUTES?  
STATUS ERROR CODE 3 + 1.  
YES  
B
THERMOSTAT CALLS FOR HEAT:  
STATUS LED −− HEARTBEAT  
NO  
NO  
NO  
60−MINUTE LIMIT WATCHGUARD MODE.  
GAS VALVE OFF, COMBUSTION AIR INDUCER  
OFF, INDOOR BLOWER OFF WITH DELAY.  
STATUS ERROR CODE 4 + 5.  
YES  
PRIMARY AND SECONDARY LIMIT  
SWITCHES CLOSED?  
YES  
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.  
INDOOR BLOWER ON.  
STATUS ERROR CODE 5 + 1.  
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS  
RESET AND MAIN POWER IS INTERRUPTED OR  
T’STAT IS CYCLED OFF/ON FOR 3 SEC. MINIMUM.  
NO  
ROLLOUT SWITCH CLOSED?  
NO  
YES  
YES  
FIRST (LOW) STAGE PRESSURE SWITCH  
CONTACTS OPEN?  
NO  
YES  
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.  
INDOOR BLOWER OFF. CONTROL REMAINS UNTIL  
PRESSURE SWITCH IS DETECTED OPEN.  
STATUS ERROR CODE 2 + 4  
SECOND (HIGH) STAGE PRESSURE SWITCH  
CONTACTS OPEN?  
NO  
YES  
GAS VALVE OFF.  
COMBUSTION AIR INDUCER OFF.  
INDOOR BLOWER OFF.  
TWO−STAGE OR SINGLE−STAGE THERMOSTAT  
CALL FOR HEAT  
CONTROL WILL NOT ATTEMPT SECOND−STAGE  
OPERATION DURING THIS HEAT DEMAND.  
FIRST−STAGE OPERATION WILL BE ATTEMPTED.  
STATUS ERROR CODE 2 + 6.  
COMBUSTION AIR INDUCER ON LOW SPEED.  
STATUS LED −− HEARTBEAT  
CONTINUED ON NEXT PAGE  
Page 57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting: Heating Sequence of Operation (Continued)  
HEATING SEQUENCE OF OPERATION  
CONTINUED  
THERMOSTAT CALLS FOR HEAT  
STATUS LED − HEARTBEAT.  
(Refer to box A on previous page)  
NO  
FIRST−STAGE (LOW FIRE) PRESSURE  
SWITCH CLOSED WITHIN 2.5 MINUTES?  
GAS VALVE OFF. COMBUSTION AIR INDUCER  
OFF. INDOOR BLOWER OFF. UNIT WILL RETRY  
AFTER 5−MINUTE WAIT PERIOD.  
YES  
STATUS ERROR CODE 2 + 3.  
15−SECOND COMBUSTION AIR INDUCER  
PRE−PURGE INITIATED BY CLOSED FIRST−STAGE  
PRESSURE SWITCH (or 15 SECOND  
INTER−PURGE PERIOD.)  
STATUS LED −− HEARTBEAT.  
IGNITOR WARM−UP (20 SECONDS)  
STATUS LED −− HEARTBEAT.  
YES  
COMBUSTION AIR INDUCER OFF, IGNITOR OFF.  
SIGNAL HOLDS UNTIL IGNITOR IS REPLACED OR  
RECONNECTED.  
NO  
IS IGNITOR INTACT AND CONNECTED?  
STATUS ERROR CODE 4 + 7.  
YES  
AT END OF IGNITOR 20 SECOND WARM UP  
PERIOD, 4−SECOND TRIAL FOR IGNITION.  
GAS VALVE OPENS, IGNITOR ENERGIZED DURING  
4−SECOND TRIAL UNTIL FLAME SENSED.  
YES  
IS VOLTAGE ABOVE 90 VOLTS?  
NO  
YES  
COMBUSTION AIR INDUCER OFF, IGNITER OFF.  
SIGNAL HOLDS UNTIL VOLTAGE RISES ABOVE 95  
VOLTS. STATUS ERROR CODE 4 + 8.  
4−SECOND FLAME STABILIZATION PERIOD.  
NO  
FLAME RECTIFICATION CURRENT CHECK  
CAN FLAME BE PROVEN WITHIN 4  
SECONDS AFTER GAS VALVE OPENS?  
(u0.20 microamps)  
GAS VALVE OFF. COMBUSTION AIR  
INDUCER ON. INDOOR BLOWER OFF.  
STATUS LED −− HEARTBEAT.  
HAS CONTROL FAILED TO SENSE  
FLAME FOR FIVE CONSECUTIVE TRIES  
DURING A SINGLE HEAT DEMAND?  
NO  
YES  
WATCHGUARD MODE. GAS VALVE OFF,  
COMBUSTION AIR INDUCER OFF.  
INDOOR BLOWER OFF.  
YES  
STATUS ERROR CODE 4 + 1.  
IS 60−MINUTE RESET PERIOD COMPLETE?  
YES  
NO  
FLAME PRESENT?  
HAS CONTROL RESET IGNITION SEQUENCE  
FOUR (4) TIMES?  
WATCHGUARD MODE.  
NO  
YES  
STATUS ERROR CODE 4 + 3.  
CONTINUED ON NEXT PAGE  
Page 58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting: Heating Sequence of Operation (Continued)  
HEATING SEQUENCE OF OPERATION  
CONTINUED  
THERMOSTAT CALLS FOR HEAT.  
STATUS LED −− HEARTBEAT.  
SEE BOX A.  
FLAME SIGNAL ABOVE  
(u1.40 microamps)  
NO  
LOW FLAME SIGNAL  
(Does not affect control operation)  
STATUS ERROR CODE 1 + 2.  
YES  
YES  
SINGLE−STAGE THERMOSTAT MODE  
(DIP SWITCH SET AT ꢁSINGLE")  
TWO STAGE THERMOSTAT MODE  
(DIP SWITCH SET AT ꢁTWO")  
YES  
YES  
START SECOND−STAGE RECOGNITION  
ON DELAY (10 OR 15 MINUTES).  
STATUS LED −− HEARTBEAT  
45−SECOND INDOOR BLOWER ON DELAY BEGINS.  
STATUS LED −− HEARTBEAT.  
YES  
NO  
YES  
NO  
PRIMARY & SECONDARY LIMIT SWITCHES  
CLOSED?  
ROLLOUT SWITCHES CLOSED?  
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.  
INDOOR BLOWER ON.  
YES  
STATUS ERROR CODE 5 + 1. SEQUENCE HOLDS  
UNTIL ROLLOUT SWITCH IS RESET AND MAIN  
POWER IS INTERRUPTED OR THERMOSTAT  
IS CYCLED OFF/ON FOR 3 SECOND MINIMUM.  
YES  
FIRST−STAGE (LOW FIRE)  
PRESSURE SWITCH CLOSED?  
NO  
YES  
NO  
GAS VALVE OFF, COMBUSTION AIR INDUCER OFF,  
INDOOR BLOWER ON.  
STATUS ERROR CODE 3 + 1.  
FIRST−STAGE HEAT DEMAND SATISFIED?  
YES  
YES  
YES  
HAS PRIMARY OR SECONDARY LIMIT  
SWITCH CLOSED WITHIN 3 MINUTES?  
(Indoor blower on low speed during 3−minute period)  
GAS VALVE OFF, COMBUSTION AIR INDUCER  
OFF FOLLOWING POST PURGE.  
INDOOR BLOWER OFF WITH DELAY  
STATUS LED −− PULSE  
NO  
LIMIT SWITCH WATCHGUARD MODE.  
GAS VALVE OFF, COMBUSTION AIR INDUCER OFF,  
INDOOR BLOWER OFF WITH DELAY.  
SECOND−STAGE HEAT DEMAND.  
SECOND−STAGE HEAT DEMAND REQUIRED?  
STATUS ERROR CODE 4 + 5  
IS 60−MINUTE RESET PERIOD COMPLETE?  
YES  
SECOND STAGE PRESSURE SWITCH CLOSED?  
ABNORMAL FLASH CODE.  
NOTE − IF SECOND−STAGE PRESSURE SWITCH  
WAS ORIGINALLY FOUND CLOSED,  
ABNORMAL CODE WILL FLASH.  
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.  
INDOOR BLOWER OFF AFTER DELAY.  
STATUS ERROR CODE 2 + 3. CONTROL RESTARTS YES  
IGNITION SEQUENCE IF PRESSURE SWITCH  
CLOSES WITHIN 2−1/2 MINUTES.  
YES  
NO  
SECOND−STAGE PRESSURE SWITCH CLOSED  
AT BEGINNING OF HEAT DEMAND?  
STATUS ERROR CODE 2 + 6.  
NO  
SECOND−STAGE 30−SECOND DELAY ON BEGINS.  
STATUS LED −− HEARTBEAT.  
YES  
SECOND STAGE HEAT DEMAND  
STATUS LED −− HEARTBEAT.  
SECOND−STAGE COMBUSTION AIR INDUCER  
ON. SECOND−STAGE GAS VALVE ON. HIGH  
HEAT INDOOR BLOWER SPEED ON.  
STATUS LED −− HEARTBEAT.  
NO  
RETURNS TO FIRST−STAGE HEAT MODE WHICH  
CONTINUES UNTIL SECOND−STAGE PRESSURE  
SWITCH CAN BE PROVEN or HEAT DEMAND IS  
SATISFIED. FIVE (5) MINUTE WAIT PERIOD  
INITIATED BEFORE RETRY. WERE 5 ATTEMPTS  
MADE FOR SECOND−STAGE HEAT?  
YES  
SECOND−STAGE PRESSURE SWITCH CLOSED  
IN LESS THAN TEN (10) SECONDS?  
STATUS LED −− HEARTBEAT  
NO  
YES  
CONTINUES FIRST−STAGE HEATING DEMAND.  
WILL NOT REATTEMPT SECOND−STAGE  
HEATING DEMAND.  
YES  
CONTINUED ON NEXT PAGE  
STATUS ERROR CODE 2 + 5.  
Page 59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting: Heating Sequence of Operation (Continued)  
HEATING SEQUENCE OF OPERATION  
CONTINUED  
SEE BOX A  
NORMAL OPERATION.  
SEE BOX B  
THERMOSTAT CALLS FOR HEAT.  
RETURN TO FIRST−STAGE HEAT MODE.  
FIRST−STAGE CONTINUES UNTIL SECOND−  
STAGE PRESSURE SWITCH CAN BE PROVEN  
or HEAT DEMAND IS SATISFIED. A FIVE (5)  
MINUTE WAIT PERIOD IS INITIATED BEFORE  
RETRY. WERE 5 ATTEMPTS MADE FOR  
SECOND−STAGE HEAT?  
SECOND−STAGE (HIGH FIRE) HEAT  
PRESSURE SWITCH CLOSED?  
YES  
NO  
YES  
NO  
HEAT DEMAND SATISFIED?  
STATUS LED −− HEARTBEAT.  
SEE BOX C  
FIRST−STAGE HEAT DEMAND SATISFIED?  
YES  
YES  
SINGLE−STAGE THERMOSTAT MODE  
(DIP SWITCH SET AT ꢁSINGLE")  
TWO STAGE THERMOSTAT MODE?  
(DIP SWITCH SET AT ꢁTWO")  
YES  
YES  
SECOND STAGE HEAT  
DEMAND SASTISFIED?  
STATUS LED −− HEARTBEAT.  
FIRST AND SECOND STAGE HEAT  
DEMAND SATISFIED SIMULTANEOUSLY.  
STATUS LED −− HEARTBEAT.  
GAS VALVE OFF, COMBUSTION AIR  
INDUCER OFF AFTER 5−SECOND  
LOW SPEED POST PURGE PERIOD,  
INDOOR BLOWER OFF DELAY  
INITIATED ON LOW HEAT SPEED.  
STATUS LED −− HEARTBEAT.  
YES  
NO  
YES  
GAS VALVE, COMBUSTION AIR INDUCER  
AND INDOOR BLOWER RETURN TO FIRST−  
STAGE OPERATION.  
STATUS LED −− HEARTBEAT.  
FIRST STAGE HEAT DEMAND SATISFIED?  
YES  
GAS VALVE OFF. COMBUSTION AIR INDUCER  
OFF AFTER 5−SECOND LOW SPEED POST−  
PURGE PERIOD. INDOOR BLOWER OFF.  
DELAY INITIATED ON LOW HEAT SPEED.  
STATUS LED −− PULSE.  
DEMAND FOR HEAT SATISFIED.  
POWER ON STAND BY.  
STATUS LED −− PULSE.  
Page 60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting: Cooling Sequence of Operation  
COOLING SEQUENCE OF OPERATION  
POWER ON  
SIGNAL POLARITY REVERSED.  
CONTROL WILL CONTINUE TO CALL FOR COOLING  
IN THIS CONDITION.  
YES  
IS POLARITY REVERSED?  
STATUS ERROR CODE 5 + 4.  
NO  
SIGNAL IMPROPER GROUND AT LED.  
CONTROL WILL CONTINUE TO CALL FOR COOLING  
IN THIS CONDITION.  
NO  
IS THERE  
PROPER GROUND?  
STATUS ERROR CODE 5 + 3.  
YES  
THERMOSTAT CALLS FOR FIRST−STAGE COOL.  
COMPRESSOR AND CONDENSER FAN  
ENERGIZED.  
INDOOR BLOWER ENERGIZED ON FIRST STAGE  
COOL SPEED AFTER 2 SECOND DELAY.  
YES  
COMPRESSOR AND CONDENSER FAN DE−ENERGIZED.  
INDOOR BLOWER DE−ENEGIZED.  
FIRST−STAGE DEMAND FOR COOL SATISFIED?  
NO  
THERMOSTAT CALLS FOR SECOND−STAGE COOL.  
INDOOR BLOWER RAMPS UP TO SECOND−STAGE COOL SPEED.  
SECOND−STAGE DEMAND FOR COOL SATISFIED?  
YES  
UNIT RETURNS TO FIRST STAGE COOL  
Page 61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting: Continuous Fan Sequence of Operation  
CONTINUOUS LOW SPEED FAN SEQUENCE OF OPERATION  
MANUAL FAN SELECTION MADE AT THERMOSTAT.  
AFTER 2 SECOND DELAY, INDOOR BLOWER IS  
ENERGIZED ON CONTINUOUS FAN SPEED.  
YES  
YES  
THERMOSTAT CALLS FOR FIRST STAGE COOL.  
YES  
THERMOSTAT CALLS FOR FIRST−STAGE HEAT.  
YES  
INDOOR BLOWER RAMPS TO FIRST STAGE  
COOLING SPEED AFTER A 2−SECOND DELAY.  
AFTER 45−SECOND DELAY, INDOOR BLOWER  
SWITCHES TO LOW HEAT SPEED.  
FIRST−STAGE COOL DEMAND SATISFIED?  
FIRST−STAGE HEAT DEMAND SATISFIED.  
NO  
YES  
YES  
NO  
SECOND STAGE COOL DEMAND  
THERMOSTAT CALLS FOR SECOND−STAGE HEAT.  
YES  
INDOOR BLOWER RAMPS TO SECOND  
STAGE COOL SPEED  
INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED  
AFTER 30−SECOND RECOGNITION PERIOD.  
YES  
SECOND STAGE COOL DEMAND SATISFIED?  
YES  
SECOND−STAGE HEAT DEMAND SATISFIED.  
YES  
INDOOR BLOWER RAMPS DOWN TO FIRST STAGE  
COOL SPEED.  
INDOOR BLOWER RAMPS DOWN TO LOW  
HEAT SPEED.  
Repair Parts List  
The following repair parts are available through Lennox dealers. When ordering parts, include the complete furnace model  
number listed on the CSA nameplate −− Example: G61MP−36B−045−1. All service must be performed by a licensed pro-  
fessional installer (or equivalent), service agency, or gas supplier.  
Cabinet Parts  
Upper access panel  
Heating Parts  
Flame Sensor  
Blower access panel  
Top Cap  
Heat exchanger assembly  
Gas manifold  
Control Panel Parts  
Transformer  
Combustion air inducer  
Gas valve  
Two−stage integrated control board  
Door interlock switch  
Circuit Breaker  
Main burner cluster  
Main burner orifices  
Pressure switches  
Ignitor  
Blower Parts  
Blower wheel  
Motor  
Primary limit control  
Secondary limit control  
Flame rollout switches  
Combustion air inducer auxiliary limit  
Motor mounting frame  
Motor capacitor  
Blower housing cutoff plate  
Page 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Vent Pipe Sizing Worksheet  
Step 1  
Step 2  
Proposed vent pipe size : ______  
Equivalent Feet  
Termination kit catalog number : _____________  
Vent pipe equivalency value from table 5 : ______  
Step 3  
Step 4  
Total number of 90° elbows required (indoors and outdoors)  
______ X 5 = ______ equivalent feet of pipe  
Total number of 45° elbows required (indoors and outdoors)  
______ X 2.5 = ______ equivalent feet of pipe  
Step 5  
Step 6  
Linear feet of straight pipe required : ______  
TOTAL  
Add equivalent feet of vent pipe listed in  
steps 2 through 5.  
If the total is equal to, or less than, the allowable maximum given in table 6, the proposed pipe size is acceptable. If the  
total exceeds the maximum allowed vent pipe length, repeat the process above using the next larger diameter pipe until  
an acceptable total is achieved.  
NOTE − In Direct Vent systems, total the equivalent length of either the exhaust OR intake piping run, depending upon which  
will be LONGER. Intake and exhaust pipe diameter must be the same size and must be terminated in the same pressure  
zone. Intake and exhaust pipe should be roughly the same length.  
G61MP Start−Up & Performance Check List  
Job Name  
Job No.  
City  
Date  
State  
State  
Job Location  
Installer  
City  
Technician  
Unit Model No.  
Serial No.  
Heating Section  
Electrical Connections Tight?  
Line Voltage  
Blower Motor H.P.  
Gas Piping Connections  
Tight & Leak−Tested?  
Blower Motor Amps  
Fuel Type: Natural Gas?  
LP/Propane Gas?  
Furnace Btu Input (High fire)  
Low Fire Manifold Pressure  
High Fire Manifold Pressure  
Flue Connections Tight?  
Line Pressure  
w.c. − LP/Propane  
w.c. − LP/Propane  
Proper Draft?  
w.c. − Nat.:  
w.c. − Nat.:  
Combustion Gas Tested (high fire and low fire)?  
CO  
CO  
2
Blower ON delay confirmed?  
(45 Seconds Fixed On)  
External Static Pressure?  
(0.5 maximum)  
Temperature Rise  
Blower OFF Delay Setting (60, 90, 120 or 180)?  
Filter Clean & Secure?  
Thermostat  
Heat Anticipator Setting?  
Thermostat Level?  
Page 63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Requirements for Commonwealth of Massachusetts  
Modifications to NFPA−54, Chapter 10  
4 − INSPECTION. The state or local gas inspector of the  
side wall, horizontally vented, gas−fueled equipment  
shall not approve the installation unless, upon inspec-  
tion, the inspector observes carbon monoxide detec-  
tors and signage installed in accordance with the pro-  
visions of 248 CMR 5.08(2)(a) 1 through 4.  
Revise NFPA−54 section 10.8.3 to add the following re-  
quirements:  
For all side wall, horizontally vented, gas−fueled equipment  
installed in every dwelling, building or structure used in  
whole or in part for residential purposes, including those  
owned or operated by the Commonwealth and where the  
side wall exhaust vent termination is less than seven (7)  
feet above the finished grade in the area of the venting, in-  
cluding but not limited to decks and porches, the following  
requirements shall be satisfied:  
EXEMPTIONS: The following equipment is exempt  
from 24 CMR 5.08(2)(a) 1 through 4:  
1 − The equipment listed in Chapter 10 entitled ꢁEquip-  
ment Not Required to Be Vented" in the most current  
edition of NFPA 54 as adopted by the Board; and  
2 − Product Approved side wall, horizontally vented, gas−  
fueled equipment installed in a room or structure sepa-  
rate from the dwelling, building or structure used in  
whole or in part for residential purposes.  
1 − INSTALLATION OF CARBON MONOXIDE DETEC-  
TORS. At the time of installation of the side wall, hori-  
zontally vented, gas−fueled equipment, the installing  
plumber or gasfitter shall observe that a hard−wired  
carbon monoxide detector with an alarm and battery  
backup is installed on the floor level where the gas  
equipment is to be installed. In addition, the installing  
plumber or gasfitter shall observe that a battery−oper-  
ated or hard−wired carbon monoxide detector with an  
alarm is installed on each additional level of the dwell-  
ing, building or structure served by the side wall, hori-  
zontally vented, gas−fueled equipment. It shall be the  
responsibility of the property owner to secure the ser-  
vices of qualified licensed professionals for the instal-  
lation of hard−wired carbon monoxide detectors.  
MANUFACTURER REQUIREMENTS −  
GAS EQUIPMENT VENTING SYSTEM PROVIDED.  
When the manufacturer of Product Approved side wall,  
horizontally vented, gas−fueled equipment provides a vent-  
ing system design or venting system components with the  
equipment, the instructions provided by the manufacturer  
for installation of the equipment and the venting system  
shall include:  
1 − Detailed instructions for the installation of the venting  
system design or the venting system components:  
and  
a − In the event that the side wall, horizontally vented,  
gas−fueled equipment is installed in a crawl space  
or an attic, the hard−wired carbon monoxide detec-  
tor with alarm and battery back−up may be installed  
on the next adjacent floor level.  
2 − A complete parts list for the venting system design or  
venting system.  
MANUFACTURER REQUIREMENTS −  
GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.  
b − In the event that the requirements of this subdivi-  
sion cannot be met at the time of completion of  
installation, the owner shall have a period of thirty  
(30) days to comply with the above requirements;  
provided, however, that during said thirty (30) day  
period, a battery−operated carbon monoxide detec-  
tor with an alarm shall be installed.  
When the manufacturer of Product Approved side wall,  
horizontally vented, gas−fueled equipment does not pro-  
vide the parts for venting the flue gases, but identifies ꢁspe-  
cial venting systems," the following requirements shall be  
satisfied by the manufacturer:  
2 − APPROVED CARBON MONOXIDE DETECTORS.  
Each carbon monoxide detector as required in accor-  
dance with the above provisions shall comply with  
NFPA 720 and be ANSI/UL 2034 listed and IAS certi-  
fied.  
1 − The referenced ꢁspecial venting system" instructions  
shall be included with the appliance or equipment  
installation instructions; and  
2
The ꢁspecial venting systems" shall be Product Ap-  
proved by the Board, and the instructions for that sys-  
tem shall include a parts list and detailed installation  
instructions.  
3 − SIGNAGE. A metal or plastic identification plate shall  
be permanently mounted to the exterior of the building  
at a minimum height of eight (8) feet above grade di-  
rectly in line with the exhaust vent terminal for the hori-  
zontally vented, gas−fueled heating appliance or  
equipment. The sign shall read, in print size no less  
than one−half (1/2) inch in size, ꢁGAS VENT DIRECT-  
LY BELOW. KEEP CLEAR OF ALL OBSTRUC-  
TIONS."  
A copy of all installation instructions for all Product  
Approved side wall, horizontally vented, gas−fueled  
equipment, all venting instructions, all parts lists for  
venting instructions, and/or all venting design instruc-  
tions shall remain with the appliance or equipment at  
the completion of the installation.  
Page 64  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Lenoxx Electronics Air Conditioner HSXA19 User Manual
LG Electronics Indoor Fireplace MPE 27 User Manual
Life Fitness Exercise Bike exercise bikes User Manual
Lincoln Convection Oven II Advantage Series User Manual
Little Wonder Trimmer Double Edge User Manual
Lochinvar Heating System SCH I O User Manual
Louisville Tin and Stove Furnace W251F User Manual
Makita Grinder 9564CVL User Manual
Maytag Cooktop MGC5430 User Manual
Maytag Range MGR7665WB0 User Manual