INSTALLATION
INSTRUCTIONS
EL296UHE
E 2013 Lennox Industries Inc.
Dallas, Texas, USA
®
ELITE SERIES GAS FURNACE
UPFLOW / HORIZONTAL AIR DISCHARGE
507067-01
02/2013
Supersedes 01/2012
Litho U.S.A.
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
This is a safety alert symbol and should never be ignored.
When you see this symbol on labels or in manuals, be alert
to the potential for personal injury or death.
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person-
al injury or loss of life. Installation and service must
be performed by a licensed professional installer (or
equivalent), service agency or the gas supplier.
AIR FLOW
UPFLOW
CAUTION
As with any mechanical equipment, personal injury
can result from contact with sharp sheet metal
edges. Be careful when you handle this equipment.
HORIZONTAL RIGHT
HORIZONTAL LEFT
Table of Contents
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
EL296UHE Gas Furnace . . . . . . . . . . . . . . . . . . . . . . . . . 3
Shipping and Packing List . . . . . . . . . . . . . . . . . . . . . . . . 3
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Use of Furnace as a Construction Heater . . . . . . . . . . . 4
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Combustion, Dilution, Ventilation Air . . . . . . . . . . . . . . . 5
Setting Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Duct System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Pipe and Fittings Specifications . . . . . . . . . . . . . . . . . . . 13
Joint Cementing Procedure . . . . . . . . . . . . . . . . . . . . . . . 15
Venting Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Integrated Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Unit Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Gas Pressure Measurement . . . . . . . . . . . . . . . . . . . . . . 50
Proper Combustion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
High Altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Other Unit Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Repair Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Start-Up and Performance Checklist . . . . . . . . . . . . . . . 56
02/13
507067-01
*2P0213*
Page 1
*P507067-01*
Download from Www.Somanuals.com. All Manuals Search And Download.
EL296UHE Gas Furnace
Shipping and Packing List
Package 1 of 1 contains
The EL296UHE Category IV gas furnace is shipped ready
for installation in the upflow or horizontal position. The fur-
nace is shipped with the bottom panel in place. The bot-
tom panel must be removed if the unit is to be installed in
horizontal or upflow applications with bottom return air.
1 - Assembled EL296UHE unit
1 - Bag assembly containing the following:
1 -Snap bushing
1 -Snap plug
The EL296UHE can be installed as either a Direct Vent
or a Non-Direct Vent gas central furnace.
1 - Wire tie
1 -Condensate trap
The furnace is equipped for installation in natural gas ap-
plications. A conversion kit (ordered separately) is re-
quired for use in propane/LP gas applications.
1 -Condensate trap cap
1 -Condensate trap clamp
1 -2” diameter debris screen
1 -3/4” Threaded street elbow
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
NOTE - In Direct Vent installations, combustion air is taken
from outdoors and flue gases are discharged outdoors. In
Non-Direct Vent installations, combustion air is taken from
indoors or ventilated attic or crawlspace and flue gases are
volving roof termination.
The following items may also be ordered separately:
1 - Thermostat
1 - LP/Propane changeover kit
1 - Return air base kit
DIRECT VENT INSTALLATION
NON-DIRECT VENT
INSTALLATION
EXHAUST OUTLET
COMBUSTION
EXHAUST
OUTLET
1 - Horizontal suspension kit
1 - High altitude pressure switch
AIR INTAKE OUTSIDE
OF HOUSE
Safety Information
CAUTION
As with any mechanical equipment, personal injury
can result from contact with sharp sheet metal
edges. Be careful when you handle this equipment.
COMBUSTION
AIR INTAKE
INSIDE
OF HOUSE
DANGER
Danger of explosion.
There are circumstances in which odorant used with
LP/propane gas can lose its scent. In case of a leak,
LP/propane gas will settle close to the floor and may
be difficult to smell. An LP/propane leak detector
should be installed in all LP applications.
FIGURE 1
NON-DIRECT VENT
INSTALLATION
NON-DIRECT VENT
INSTALLATION
EXHAUST
OUTLET
EXHAUST
OUTLET
Use only the type of gas approved for use with this furnace.
Refer to unit nameplate.
EL296UHE units are CSA International certified to ANSI
Z21.47 and CSA 2.3 standards.
Building Codes
In the USA, installation of gas furnaces must conform with lo-
cal building codes. In the absence of local codes, units must
be installed according to the current National Fuel Gas Code
(ANSI‐Z223.1/NFPA 54). The National Fuel Gas Code is
available from the following address:
COMBUSTION
AIR INTAKE INSIDE
VENTILATED
COMBUSTION
AIR INTAKE INSIDE
VENTILATED
CRAWL SPACE
ATTIC SPACE
American National Standards Institute, Inc.
11 West 42nd Street
New York, NY 10036
In Canada, installation must conform with current National
Standard of Canada CSA‐B149 Natural Gas and Propane
Installation Codes, local plumbing or waste water codes
and other applicable local codes.
FIGURE 2
Page 3
Download from Www.Somanuals.com. All Manuals Search And Download.
In order to ensure proper unit operation in non-direct vent
applications, combustion and ventilation air supply must be
provided according to the current National Fuel Gas Code
or CSA‐B149 standard.
Heating Unit Installed Parallel to Air Handler Unit
Dampers
(open during heating operation only)
Installation Locations
Gas Unit
This furnace is CSA International certified for installation
clearances to combustible material as listed on the unit
vice clearances must take precedence over fire protection
clearances.
AIR FLOW
AIR FLOW
Air Handler Unit
Dampers
(open during cooling operation only)
NOTE - For installation on combustible floors, the furnace
shall not be installed directly on carpeting, tile, or other
combustible material other than wood flooring.
Heating Unit Installed Upstream of Cooling Coil
For installation in a residential garage, the furnace must
be installed so that the burner(s) and the ignition source
are located no less than 18 inches (457 mm) above the
floor. The furnace must be located or protected to avoid
physical damage by vehicles. When a furnace is installed
in apublic garage, hangar, or other building that has a haz-
ardous atmosphere, the furnace must be installed accord-
ing to recommended good practice requirements and cur-
rent National Fuel Gas Code or CSA B149 standards.
AIR FLOW
AIR FLOW
Gas Unit
Cooling Coil
FIGURE 3
NOTE - This furnace is designed for a minimum continu-
ous return air temperature of 60°F (16°C) or an intermit-
tent operation down to 55°F (13°C) dry bulb for cases
where a night setback thermostat is used. Return air tem-
perature must not exceed 85°F (29°C) dry bulb.
NOTE - Furnace must be adjusted to obtain a temperature
rise within the range specified on the unit nameplate. Failure
to do so may cause erratic limit operation and premature heat
exchanger failure.
The EL296UHE furnace may be installed in alcoves, clos-
ets, attics, basements, garages, crawl spaces and utility
rooms in the upflow or horizontal position.
This EL296UHE furnace must be installed so that its
electrical components are protected from water.
This furnace design has not been CSA certified for installa-
tion in mobile homes, recreational vehicles, or outdoors.
Installed in Combination with a Cooling Coil
Use of Furnace as Construction Heater
be installed in parallel with, or on the upstream side of, cool-
ing coils to avoid condensation in the heating compartment.
With a parallel flow arrangement, a damper (or other means
to control the flow of air) must adequately prevent chilled air
from entering the furnace. If the damper is manually oper-
ated, it must be equipped to prevent operation of either the
heating or the cooling unit, unless it is in the full HEAT or
COOL setting.
Lennox does not recommend the use of EL296UHE units
as a construction heater during any phase of construction.
Very low return air temperatures, harmful vapors and op-
eration of the unit with clogged or misplaced filters will dam-
age the unit.
EL296UHE units may be used for heating of buildings or
structures under construction, if the following conditions
are met:
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Electric
Code, ANSI/NFPA No. 70. The National Electric Code
(ANSI/NFPA No. 70) is available from the following ad-
dress:
D The vent system must be permanently installed per
these installation instructions.
D A room thermostat must control the furnace. The use of
fixed jumpers that will provide continuous heating is not
allowed.
D The return air duct must be provided and sealed to the
furnace.
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
D Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
D Air filters must be installed in the system and must be
maintained during construction.
In Canada, all electrical wiring and grounding for the unit
must be installed according to the current regulations of the
Canadian Electrical Code Part I (CSA Standard C22.1)
and/or local codes.
D Air filters must be replaced upon construction comple-
tion.
Page 4
Download from Www.Somanuals.com. All Manuals Search And Download.
D The input rate and temperature rise must be set per the
furnace rating plate.
WARNING
D One hundred percent (100%) outdoor air must be pro-
vided for combustion air requirements during construc-
tion. Temporary ducting may supply outdoor air to the
furnace. Do not connect duct directly to the furnace.
Size the temporary duct following these instructions in
section for Combustion, Dilution and Ventilation Air in a
confined space with air from outside.
The State of California has determined that this prod-
uct may contain or produce a chemical or chemicals,
in very low doses, which may cause serious illness
or death. It may also cause cancer, birth defects or
reproductive harm.
WARNING
D The furnace heat exchanger, components, duct system,
air filters and evaporator coils must be thoroughly
cleaned following final construction clean-up.
Insufficient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rust-
ing and premature heat exchanger failure. Excessive
exposure to contaminated combustion air will result
in safety and performance related problems. Avoid
exposure to the following substances in the com-
bustion air supply:
D All furnace operating conditions (including ignition, in-
put rate, temperature rise and venting) must be verified
according to these installation instructions.
General
Permanent wave solutions
Chlorinated waxes and cleaners
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
Chlorine base swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
In addition to the requirements outlined previously, the fol-
lowing general recommendations must be considered
when installing an EL296UHE furnace:
• Place the furnace as close to the center of the air dis-
tribution system as possible. The furnace should also be
located close to the vent termination point.
• When the furnace is installed in non-direct vent applica-
tions, do not install the furnace where drafts might blow
directly into it. This could cause improper combustion
and unsafe operation.
Combustion, Dilution & Ventilation Air
If the EL296UHE is installed as a Non-Direct Vent Fur-
nace, follow the guidelines in this section.
• When the furnace is installed in non-direct vent applica-
tions, do not block the furnace combustion air opening
with clothing, boxes, doors, etc. Air is needed for proper
combustion and safe unit operation.
NOTE - In Non-Direct Vent installations, combustion air
is taken from indoors or ventilated attic or crawlspace
and flue gases are discharged out-doors.
• When the furnace is installed in an attic or other insu-
lated space, keep insulation away from the furnace.
In the past, there was no problem in bringing in sufficient
outdoor air for combustion. Infiltration provided all the air
that was needed. In today's homes, tight construction
practices make it necessary to bring in air from outside
for combustion. Take into account that exhaust fans, ap-
pliance vents, chimneys, and fireplaces force additional
air that could be used for combustion out of the house.
Unless outside air is brought into the house for combus-
tion, negative pressure (outside pressure is greater than
inside pressure) will build to the point that a downdraft
can occur in the furnace vent pipe or chimney. As a result,
combustion gases enter the living space creating a po-
tentially dangerous situation.
• When the furnace is installed in an unconditioned
space, consider provisions required to prevent freezing
of condensate drain system.
• The “A” coil drain pan is high quality engineering poly-
mer with a maximum service temperature of 500° F.
However, adequate space must be provided between
the drain pan and the furnace heat exchanger. At least
2” space is required for sectionalized heat exchanger
and and 4” for drum-type or oil-fired furnace exchanger.
Closer spacing may damage the drain pan and cause
leaking.
In the absence of local codes concerning air for combus-
tion and ventilation, use the guidelines and procedures in
this section to install EL296UHE furnaces to ensure effi-
cient and safe operation. You must consider combustion
air needs and requirements for exhaust vents and gas
CAUTION
EL296UHE unit should not be installed in areas nor-
mally subject to freezing temperatures.
Page 5
Download from Www.Somanuals.com. All Manuals Search And Download.
piping. A portion of this information has been reprinted
with permission from the National Fuel Gas Code (ANSI-
Z223.1/NFPA 54). This reprinted material is not the com-
plete and official position of the ANSI on the referenced
subject, which is represented only by the standard in its
entirety.
Confined Space
A confined space is an area with a volume less than 50 cubic
3
feet (1.42 m ) per 1,000 Btu (.29 kW) per hour of the com-
bined input rating of all appliances installed in that space. This
definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space con-
taining the furnace, the return airmust be handled by ducts
which are sealed to the furnace casing and which terminate
outside the space containing the furnace. This is especially
important when the furnace is mounted on a platform in a
confined space such as a closet or small equipment room.
Even a small leak around the base of the unit at the platform
or at the return air duct connection can cause a potentially
dangerous negative pressure condition. Air for combustion
and ventilation can be brought into the confined space ei-
ther from inside the building or from outside.
In Canada, refer to the CSA B149 installation codes.
CAUTION
Do not install the furnace in a corrosive or contami-
nated atmosphere. Meet all combustion and ventila-
tion air requirements, as well as all local codes.
All gas‐fired appliances require air for the combustion pro-
cess. If sufficient combustion air is not available, the fur-
nace or other appliance will operate inefficiently and un-
safely. Enough air must be provided to meet the needs of all
fuel-burning appliances and appliances such as exhaust
fans which force air out of the house. When fireplaces, ex-
haust fans, or clothes dryers are used at the same time as
the furnace, much more air is required to ensure proper
combustion and to prevent a downdraft. Insufficient air
causes incomplete combustion which can result in carbon
monoxide.
Air from Inside
If the confined space that houses the furnace adjoins a
space categorized as unconfined, air can be brought in by
providing two permanent openings between the two
spaces. Each opening must have a minimum free area of 1
2
square inch (645 mm ) per 1,000 Btu (.29 kW) per hour of
total input rating of all gas-fired equipment in the confined
space. Each opening must be at least 100 square inches
In addition to providing combustion air, fresh outdoor air di-
lutes contaminants in the indoor air. These contaminants
may include bleaches, adhesives, detergents, solvents
and other contaminants which can corrode furnace compo-
nents.
2
(64516 mm ). One opening shall be within 12 inches (305
mm) of the top of the enclosure and one opening within 12
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM INSIDE
The requirements for providing air for combustion and ven-
tilation depend largely on whether the furnace is installed in
an unconfined or a confined space.
ROOF TERMINATED
EXHAUST PIPE
Unconfined Space
An unconfined space is an area such as a basement or
large equipment room with a volume greater than 50 cubic
3
feet (1.42 m ) per 1,000 Btu (.29 kW) per hour of the com-
OPENINGS
(To Adjacent
bined input rating of all appliances installed in that space.
This space also includes adjacent rooms which are not
separated by a door. Though an area may appear to be un-
confined, it might be necessary to bring in outdoor air for
combustion if the structure does not provide enough air by
infiltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around
the windows and doors, follow the procedures in the Air
from Outside section.
SIDE WALL
EL296UH
Unconfined
Space)
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
E
NOTE - Each opening shall have a free area of at least one square inch
2
per 1,000 Btu (645mm per .29kW) per hour of the total input rating of
all equipment in the enclosure, but not less than 100 square inches
2).
(64516mm.
FIGURE 4
Page 6
Download from Www.Somanuals.com. All Manuals Search And Download.
Air from Outside
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)
If air from outside is brought in for combustion and ventila-
tion, the confined space shall be provided with two perma-
nent openings. One opening shall be within 12” (305mm)
of the top of the enclosure and one within 12” (305mm) of
the bottom. These openings must communicate directly
or by ducts with the outdoors or spaces (crawl or attic) that
freely communicate with the outdoors or indirectly
through vertical ducts. Each opening shall have a mini-
Roof Terminated
Exhaust Pipe
2
mum free area of 1 square inch per 4,000 Btu (645mm
per 1.17kW) per hour of total input rating of all equipment
with the outdoors through horizontal ducts, each opening
shall have a minimum free area of 1 square inch per 2,000
Inlet Air
(Minimum
12 in.(305mm)
Above crawl
space floor)
Ventilation
Louvers
(Crawl space)
Furnace
2
Btu (645mm per .59kW) per total input rating of all equip-
to bring in air for combustion from a ventilated attic (figure
Coupling or
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE
(Inlet Air from Crawl Space and Outlet Air to Outside)
*Intake Debris Screen Provided)
3 in. to 2 in.
Transition
(Field Provided)
VENTILATION LOUVERS
(Each end of attic)
ROOF TERMINATED
EXHAUST PIPE
NOTE-The inlet and outlet air openings shall each have a free area
2
of at least one square inch per 4,000 Btu (645mm per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
FIGURE 7
OUTLET
AIR
When ducts are used, they shall be of the same cross-sec-
tional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3 inches (75 mm). In calculating free
area, the blocking effect of louvers, grilles, or screens
must be considered. If the design and free area of protec-
tive covering is not known for calculating the size opening
required, it may be assumed that wood louvers will have
20 to 25 percent free area and metal louvers and grilles
will have 60 to 75 percent free area. Louvers and grilles
must be fixed in the open position or interlocked with the
equipment so that they are opened automatically during
equipment operation.
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
FURNACE
VENTILATION
LOUVERS
(For unheated
crawl space)
INLET
AIR
NOTE-The inlet and outlet air openings shall each have a free area
2
of at least one square inch per 4,000 Btu (645mm per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
FIGURE 5
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Attic and Outlet Air to Outside)
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
Ventilation Louvers
Inlet Air
Roof Terminated
Exhaust Pipe
ROOF TERMINATED
EXHAUST PIPE
(Minimum
VENTILATION LOUVERS
(Each end of attic)
12 in.(305mm) Above
attic floor)
OUTLET
AIR
*Intake Debris
Screen
(Provided)
INLET AIR
(Ends 12” above
bottom)
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
FURNACE
Furnace
NOTE-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
NOTE-The inlet and outlet air openings shall each have a free area of
2
at least one square inch per 4,000 Btu (645mm per 1.17kW) per hour
of the total input rating of all equipment in the enclosure.
2
FIGURE 8
FIGURE 6
Page 7
Download from Www.Somanuals.com. All Manuals Search And Download.
EQUIPMENT IN CONFINED SPACE -
ALL AIR FROM OUTSIDE
Installation - Setting Equipment
WARNING
ROOF TERMINATED
EXHAUST PIPE
Do not connect the return air duct to the back of the
furnace. Doing so will adversely affect the operation
of the safety control devices, which could result in
personal injury or death.
OUTLET AIR
FURNACE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
WARNING
INLET AIR
Blower access panel must be securely in place when
blower and burners are operating. Gas fumes, which
could contain carbon monoxide, can be drawn into
living space resulting in personal injury or death.
NOTE-Each air duct opening shall have a free area of at least one
2
square inch per 2,000 Btu (645mm per .59kW) per hour of the total
input rating of all equipment in the enclosure. If the equipment room
is located against an outside wall and the air openings communi-
cate directly with the outdoors, each opening shall have a free area
of at least 1 square inch per 4,000 Btu (645mm per 1.17kW) per
hour of the total input rating of all other equipment in the enclosure.
Upflow Applications
The EL296UHE gas furnace can be installed as shipped
Select a location that allows for the required clearances
that are listed on the unit nameplate. Also consider gas
supply connections, electrical supply, vent connection,
condensate trap and drain connections, and installation
and service clearances [24 inches (610 mm) at unit
front]. The unit must be level from side to side. The unit
may be positioned from level to ½” toward the front. See
2
FIGURE 9
Shipping Bolt Removal
Units with 1/2 hp blower motor are equipped with three flex-
ible legs and one rigid leg. The rigid leg is equipped with a
shipping bolt and a flat white plastic washer (rather than the
rubber mounting grommet used with a flexible mounting
leg). See figure 10. The bolt and washer must be re-
moved before the furnace is placed into operation. Af-
ter the bolt and washer have been removed, the rigid leg
will not touch the blower housing.
Allow for clearances to combustible materials as indicated
on the unit nameplate.
EL296 Furnaces with
1/2 HP Blower Motor
RIGID LEG
(Remove shipping bolt
and washer)
FIGURE 10
Page 8
Download from Www.Somanuals.com. All Manuals Search And Download.
SETTING EQUIPMENT
UPFLOW APPLICATION
UNIT
FRONT
UNIT
FRONT
AIR FLOW
AIR FLOW
1/2”
max.
FRONT VIEW
SIDE VIEW
SIDE VIEW
HORIZONTAL APPLICATION
UNIT
FRONT
AIR FLOW
1/2”
max.
END VIEW
FRONT VIEW
Unit must be level side-to-side. Unit may be positioned from level to 1/2” toward the front to aid in draining.
FIGURE 11
Page 9
Download from Www.Somanuals.com. All Manuals Search And Download.
Return Air Guidelines
WARNING
Return air can be brought in through the bottom or either
side of the furnace installed in an upflow application. If the
furnace is installed on a platform with bottom return, make
an airtight seal between the bottom of the furnace and the
platform to ensure that the furnace operates properly and
safely. The furnace is equipped with a removable bottom
panel to facilitate installation.
Improper installation of the furnace can result in per-
sonal injury or death. Combustion and flue products
must never be allowed to enter the return air system
or air in the living space. Use sheet metal screws and
joint tape to seal return air system to furnace.
In platform installations with furnace return, the fur-
nace should be sealed airtight to the return air ple-
num. A door must never be used as a portion of the
return air duct system. The base must provide a
stable support and an airtight seal to the furnace. Al-
low absolutely no sagging, cracks, gaps, etc.
Markings are provided on both sides of the furnace cabinet
for installations that require side return air. Cut the furnace
cabinet at the maximum dimensions shown on page 2.
For no reason should return and supply air duct sys-
tems ever be connected to or from other heating de-
vices such as a fireplace or stove, etc. Fire, explo-
sion, carbon monoxide poisoning, personal injury
and/or property damage could result.
Refer to Product Specifications for additional information.
EL296UHE applications which include side return air
and a condensate trap installed on the same side of the
cabinet (trap can be installed remotely within 5 ft.) re-
quire either a return air base or field-fabricated transi-
tion to accommodate an optional IAQ accessory taller
Installation Clearances
Top
Side Return Air
(with transition and filter)
Left Side
Right Side
20” X 25” X 1”
(508mmX635mmX25mm)
Bottom (Floor)
1−1/2”
Air Filter
Top/Plenum
*Front
Back
1 in. (25 mm)
0
0
Sides
0†
0
Return
Air
Vent
Plenum
Floor
0‡
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
†Allow proper clearances to accommodate condensate trap.
‡For installations on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other
than wood flooring.
Transition
FIGURE 13
FIGURE 12
Page 10
Download from Www.Somanuals.com. All Manuals Search And Download.
Optional Return Air Base
(Upflow Applications Only)
FURNACE
FRONT
1 23 (584)
Overall
IF BASE
IS USED
3−1/4
(83)
1 Minimum
11 (279)
Maximum
WITHOUT
IAQ CABINET,
A SINGLE
RETURN AIR
PLENUM
(Maximum)
INDOOR AIR
QUALITY
CABINET
(PCO, Filter
Cabinet, etc.)
2
1 22−7/16
(570)
Overall
1 Unit side return air
Opening
14 (356)
MUST
AIR FLOW
(Maximum)
COVER BOTH
UNIT AND
RETURN
AIR BASE
OPENINGS
SIDE RETURN
AIR OPENINGS
(Either Side)
5−5/8
(143)
7−1/4
(184)
23
(584)
OPTIONAL
RETURN
AIR BASE
3/4
(19)
17−1/2 (446) B Width (50W98)
21 (533) C Width (50W99)
26−7/8
(683)
24−1/2 (622) D Width (51W00)
SIDE VIEW
FRONT VIEW
NOTE- Optional side return air filter kits are not for use with return air base.
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.
Minimum unit side return air opening dimensions for units requiring 1800 cfm of air and over (W x H): 23 x 11 in. (584 x 279 mm).
The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.
Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air
opening. The size of the opening must not extend beyond the markings on the furnace cabinet.
2
To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
FIGURE 14
Removing the Bottom Panel
Removing the Bottom Panel
Remove the two screws that secure the bottom cap to the
furnace. Pivot the bottom cap down to release the bottom
panel. Once the bottom panel has been removed, reinstall
Horizontal Applications
WARNING
Do not install the furnace on its front or back.
Screw
Bottom Cap
Bottom Panel
FIGURE 15
FIGURE 16
Page 11
Download from Www.Somanuals.com. All Manuals Search And Download.
The EL296UHE furnace can be installed in horizontal ap-
plications with either right- or left-hand air discharge.
HORIZONTAL SUSPENSION KIT
Internal Brace
(provided with kit)
Metal Strap
(typical)
Horizontal Application
Installation Clearances
Right-Hand Discharge
Bracket
(typical)
Left End
Right End
Air
Flow
Air
Flow
Air
Flow
Bottom (Floor)**
Left-Hand Discharge
Top
FIGURE 18
Left End
Right End
NOTE - When the furnace is installed on a platform or with
the horizontal suspension kit in a crawlspace, it must be
elevated enough to avoid water damage, accommodate
drain trap and to allow the evaporator coil to drain.
Air
Flow
Air
Flow
Bottom (Floor)**
Platform Installation of Horizontal Unit
Top
0
0
0
0
0
1 - Select location for unit keeping in mind service and
Front*
Back
Ends
Vent
2 - Construct a raised wooden frame and cover frame
with a plywood sheet. If unit is installed above finished
space, install an an auxiliary drain pan under unit. Set
for service clearance below unit for condensate trap.
Floor
0‡
3 - Provide a service platform in front of unit. When instal-
ling the unit in a crawl space, a proper support platform
may be created using concrete blocks.
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
**An 8” service clearance must be maintained below the unit to
provide for servicing of the condensate trap.
‡For installations on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other
than wood flooring.
4 - Route auxiliary drain line so that water draining from
this outlet will be easily noticed by the homeowner.
5 - If necessary, run the condensate line into a conden-
sate pump to meet drain line slope requirements. The
pump must be rated for use with condensing furnaces.
Protect the condensate discharge line from the pump
to the outside to avoid freezing.
FIGURE 17
Suspended Installation of Horizontal Unit
This furnace may be installed in either an attic or a crawl-
space. Either suspend the furnace from roof rafters or
kit (51W10) may be ordered from Lennox or use equiva-
lent.
6 - Continue with exhaust, condensate and intake piping
installation according to instructions.
NOTE - Heavy-gauge sheet metal straps may be used to
suspend the unit from roof rafters or ceiling joists. When
straps are used to suspend the unit in this way, support
must be provided for both the ends. The straps must not
interfere with the plenum or exhaust piping installation.
Cooling coils and supply and return air plenums must
be supported separately.
Page 12
Download from Www.Somanuals.com. All Manuals Search And Download.
Duct System
*GAS CONNECTION
INTAKE PIPE
Use industry‐approved standards to size and install the
supply and return air duct system. Refer to ACCA Manual
D. This will result in a quiet and low‐static system that has
uniform air distribution.
EXHAUST PIPE
*Gas connector may be
used for Canadian
installation if accept-
able by local authority
having jurisdiction.
NOTE - This furnace is not certified for operation in heating
mode (indoor blower operating at selected heating speed)
with an external static pressure which exceeds 0.8 inches
w.c. Operation at these conditions may result in improper
limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable
access panel should be installed in the supply air duct. The
access panel should be large enough to permit inspection
of the heat exchanger. The furnace access panel must al-
ways be in place when the furnace is operating and it must
not allow leaks.
RAISED
PLATFORM
SERVICE PLATFORM
FIGURE 19
Return Air -- Horizontal Applications
Return air may be brought in only through the end of a fur-
nace installed in the horizontal position. The furnace is
equipped with a removable bottom panel to facilitate
installation. See figure 15.
Return Air Plenum
NOTE - Return air must not be drawn from a room
where this furnace, or any other gas-fueled appliance
(i.e., water heater), or carbon monoxide-producing de-
vice (i.e., wood fireplace) is installed.
Filters
When return air is drawn from a room, a negative pres-
sure is created in the room. If agas appliance is operating
in a room with negative pressure, the flue products can
be pulled back down the vent pipe and into the room. This
reverse flow of the flue gas may result in incomplete com-
bustion and the formation of carbon monoxide gas. This
raw gas or toxic fumes might then be distributed through-
out the house by the furnace duct system.
This unit is not equipped with a filter or rack. A field-pro-
vided high velocity rated filter is required for the unit to oper-
A filter must be in place whenever the unit is operating.
IMPORTANT
If a high-efficiency filter is being installed as part of
this system to ensure better indoor air quality, the fil-
ter must be properly sized. High-efficiency filters
have a higher static pressure drop than standard-ef-
ficiency glass/foam filters. If the pressure drop is too
great, system capacity and performance may be re-
duced. The pressure drop may also cause the limit to
trip more frequently during the winter and the indoor
coil to freeze in the summer, resulting in an increase
in the number of service calls.
Return air can be brought in through the bottom or either
side of the furnace (return air brought into either side of fur-
nace allowed only in upflow applications). If a furnace with
bottom return air is installed on a platform, make an airtight
seal between the bottom of the furnace and the platform to
ensure that the unit operates properly and safely. Use fiber-
glass sealing strips, caulking, or equivalent sealing method
between the plenum and the furnace cabinet to ensure a
tight seal. If a filter is installed, size the return air duct to fit
the filter frame.
Before using any filter with this system, check the
specifications provided by the filter manufacturer
against the data given in the appropriate Lennox
Product Specifications bulletin. Additional informa-
tion is provided in Service and Application Note
ACC-00-2 (August 2000).
Pipe & Fittings Specifications
All pipe, fittings, primer and solvent cement must conform
with American National Standard Institute and the Ameri-
can Society for Testing and Materials (ANSI/ASTM) stan-
dards. The solvent shall be free flowing and contain no
lumps, undissolved particles or any foreign matter that ad-
versely affects the joint strength or chemical resistance of
the cement. The cement shall show no gelation, stratifica-
tion, or separation that cannot be removed by stirring. Re-
terials.
TABLE 1
Filter Size
Furnace
Cabinet Width
Side Return
Bottom Return
16 X 25 X 1 (1)
20 X 25 X 1 (1)
24 X 25 X 1 (1)
17-1/2”
21”
16 X 25 X 1 (1)
16 X 25 X 1 (1)
16 X 25 X 1 (2)
24-1/2”
Page 13
Download from Www.Somanuals.com. All Manuals Search And Download.
Low temperature solvent cement is recommended during
installation in cooler weather. Metal or plastic strapping may
be used for vent pipe hangers. Uniformly apply a liberal coat
of PVC primer for PVC or use a clean dry cloth for ABS to
clean inside socket surface of fitting and male end of pipe to
depth of fitting socket.
CAUTION
Solvent cements for plastic pipe are flammable liq-
uids and should be kept away from all sources of
ignition. Do not use excessive amounts of solvent
cement when making joints. Good ventilation should
be maintained to reduce fire hazard and to minimize
breathing of solvent vapors. Avoid contact of ce-
ment with skin and eyes.
Canadian Applications Only - Pipe, fittings, primer
and solvent cement used to vent (exhaust) this ap-
pliance must be certified to ULC S636 and supplied by a
single manufacturer as part of an approved vent (ex-
haust) system. In addition, the first three feet of vent
pipe from the furnace flue collar must be accessible for
inspection.
TABLE 2
PIPING AND FITTINGS SPECIFICATIONS
Schedule 40 PVC (Pipe)
D1785
F891
Schedule 40 PVC (Cellular Core Pipe)
Schedule 40 PVC (Fittings)
D2466
F441
Joint Cementing Procedure
Schedule 40 CPVC (Pipe)
All cementing of joints should be done according to the
specifications outlined in ASTM D 2855.
Schedule 40 CPVC (Fittings)
SDR-21 PVC or SDR-26 PVC (Pipe)
SDR-21 CPVC or SDR-26 CPVC (Pipe)
Schedule 40 ABS Cellular Core DWV (Pipe)
Schedule 40 ABS (Pipe)
F438
D2241
F442
F628
DANGER
DANGER OF EXPLOSION!
D1527
D2468
Schedule 40 ABS (Fittings)
Fumes from PVC glue may ignite during system
check. Allow fumes to dissipate for at least 5 minutes
before placing unit into operation.
ABS-DWV (Drain Waste & Vent)
(Pipe & Fittings)
D2661
D2665
PVC-DWV (Drain Waste & Vent)
Pipe & Fittings)
1 - Measure and cut vent pipe to desired length.
ASTM
SPECIFICATION
PRIMER & SOLVENT CEMENT
2 - Debur and chamfer end of pipe, removing any ridges
or rough edges. If end is not chamfered, edge of pipe
may remove cement from fitting socket and result in a
leaking joint.
PVC & CPVC Primer
PVC Solvent Cement
CPVC Solvent Cement
ABS Solvent Cement
F656
D2564
F493
NOTE - Check the inside of vent pipe thoroughly for
D2235
any obstruction that may alter furnace operation.
PVC/CPVC/ABS All Purpose Cement For
Fittings & Pipe of the same material
D2564, D2235, F493
D3138
3 - Clean and dry surfaces to be joined.
ABS to PVC or CPVC Transition Solvent
Cement
4 - Test fit joint and mark depth of fitting on outside of pipe.
5 - Uniformly apply a liberal coat of PVC primer for PVC or
use a clean dry cloth for ABS to clean inside socket
surface of fitting and male end of pipe to depth of fitting
socket.
CANADA PIPE & FITTING & SOLVENT
CEMENT
MARKING
PVC & CPVC Pipe and Fittings
PVC & CPVC Solvent Cement
ULCS636
NOTE- Time is critical at this stage. Do not allow prim-
er to dry before applying cement.
ABS to PVC or CPVC Transition Cement
6 - Promptly apply solvent cement to end of pipe and in-
side socket surface of fitting. Cement should be ap-
plied lightly but uniformly to inside of socket. Take
care to keep excess cement out of socket. Apply sec-
ond coat to end of pipe.
IMPORTANT
EL296UHE exhaust and intake connections are
made of PVC. Use PVC primer and solvent cement
when using PVC vent pipe. When using ABS vent
pipe, use transitional solvent cement to make con-
nections to the PVC fittings in the unit.
7 - Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe
are wet with cement, forcefully insert end of pipe into
socket until it bottoms out. Turn PVC pipe 1/4 turn dur-
ing assembly (but not after pipe is fully inserted) to dis-
tribute cement evenly. DO NOT turn ABS or cellular
core pipe.
Use PVC primer and solvent cement or ABS solvent cement
nate, use all purpose cement, to bond ABS, PVC, or CPVC
pipe when using fittings and pipe made of the same materi-
als. Use transition solvent cement when bonding ABS to ei-
ther PVC or CPVC.
NOTE - Assembly should be completed within 20 sec-
onds after last application of cement. Hammer blows
should not be used when inserting pipe.
Page 14
Download from Www.Somanuals.com. All Manuals Search And Download.
8 - After assembly, wipe excess cement from pipe at end
of fitting socket. A properly made joint will show a
bead around its entire perimeter. Any gaps may indi-
cate an improper assembly due to insufficient sol-
vent.
Conduct the following test while each appliance is operat-
ing and the other appliances (which are not operating) re-
main connected to the common venting system. If the
venting system has been installed improperly, you must
correct the system as indicated in the general venting re-
quirements section.
9 - Handle joints carefully until completely set.
Venting Practices
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon mon-
oxide poisoning or death.
The following steps shall be followed for each ap-
pliance connected to the venting system being
placed into operation, while all other appliances
connected to the venting system are not in
operation:
Piping Suspension Guidelines
SCHEDULE 40
PVC - 5'
all other pipe* - 3'
NOTE - Isolate piping at the point where it exits the outside wall or
roof in order to prevent transmission of vibration to the structure.
1 - Seal any unused openings in the common venting sys-
tem.
NOTE - All horizontal runs of exhaust pipe must slope back to-
ward unit a minimum of 1/4” (6mm) drop for each 12” (305mm).
2 - Inspect the venting system for proper size and horizontal
pitch. Determine that there is no blockage, restriction,
leakage, corrosion, or other deficiencies which could
cause an unsafe condition.
Wall Thickness Guidelines
24” maximum
3/4” minimum
3 - Close all building doors and windows and all doors be-
tween the space in which the appliances remaining
connected to the common venting system are located
and other spaces of the building. Turn on clothes dry-
ers and any appliances not connected to the common
venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they will oper-
ate at maximum speed. Do not operate a summer ex-
haust fan. Close fireplace dampers.
Wall
inside
outside
insulation
(if required)
4 - Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that
the appliance operates continuously.
FIGURE 20
1 - In areas where piping penetrates joists or interior
walls, hole must be large enough to allow clearance on
all sides of pipe through center of hole using a hanger.
5 - After the main burner has operated for 5 minutes, test
for leaks of flue gases at the draft hood relief opening.
Use the flame of a match or candle.
2 - When furnace is installed in a residence where unit is
shut down for an extended period of time, such as a
vacation home, make provisions for draining conden-
sate collection trap and lines.
6 - After determining that each appliance connected to the
common venting system is venting properly, (step 3)
return all doors, widows, exhaust fans, fireplace damp-
ers, and any other gas-burning appliances to their pre-
vious mode of operation.
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a
venting system commonly run with separate gas ap-
pliances, the venting system is likely to be too large to
properly vent the remaining attached appliances.
7 - If a venting problem is found during any of the preced-
ing tests, the common venting system must be modi-
fied to correct the problem.
Page 15
Download from Www.Somanuals.com. All Manuals Search And Download.
Resize the common venting system to the minimum
vent pipe size determined by using the appropriate
tables in Appendix G. (These are in the current stan-
dards of the National Fuel Gas Code ANSI Z223.1.
NOTE - In Non‐Direct Vent installations, combustion air is
taken from indoors or ventilated attic or crawlspace and flue
gases are discharged outdoors. In Direct Vent installations,
combustion air is taken from outdoors and flue gases are
discharged outdoors.
Intake and exhaust pipe sizing -- Size pipe according to
REPLACING FURNACE THAT
WAS PART OF A COMMON
VENT SYSTEM
CHIMNEY
OR GAS
VENT
(Check sizing
for water
heater only)
Regardless of the diameter of pipe used, the standard roof
and wall terminations described in section Exhaust Piping
Terminations should be used. Exhaust vent termination
pipe is sized to optimize the velocity of the exhaust gas as
FURNACE
(Replaced
by EL296)
WATER
HEATER
In some applications which permit the use of several differ-
ent sizes of vent pipe, a combination vent pipe may be
used. Contact Lennox' Application Department for assis-
tance in sizing vent pipe in these applications.
OPENINGS
(To Adjacent
Room)
NOTE - The exhaust collar on all models is sized to ac-
commodate 2” Schedule 40 vent pipe. In horizontal ap-
plications, any transition to exhaust pipe larger than 2”
must be made in vertical runs of the pipe. Therefore a 2”
elbow must be added before the pipe is transitioned to
any size larger than 2”. This elbow must be added to the
elbow count used to determine acceptable vent lengths.
Contact the Application Department for more information
concerning sizing of vent systems which include multiple
pipe sizes.
If an EL296UHE furnace replaces a furnace which
was commonly vented with another gas appliance,
the size of the existing vent pipe for that gas ap-
pliance must be checked. Without the heat of the
original furnace flue products, the existing vent pipe
is probably oversized for the single water heater or
other appliance. The vent should be checked for
proper draw with the remaining appliance.
FIGURE 21
Horizontal Installation Offset Requirements
Exhaust Pipe
Route piping to outside of structure. Continue with installa-
tion following instructions given in piping termination sec-
tion.
12” Min.
12” Max.
Horizontal
Gas Furnace
CAUTION
Do not discharge exhaust into an existing stack or
stack that also serves another gas appliance. If verti-
cal discharge through an existing unused stack is re-
quired, insert PVC pipe inside the stack until the end
is even with the top or outlet end of the metal stack.
NOTE - All horizontal runs of exhaust pipe must slope back to-
ward unit. A minimum of 1/4” (6mm) drop for each 12” (305mm)
of horizontal run is mandatory for drainage.
NOTE - Exhaust pipe MUST be glued to furnace exhaust fittings.
NOTE - Exhaust piping should be checked carefully to make
sure there are no sags or low spots.
CAUTION
FIGURE 22
The exhaust vent pipe operates under positive pres-
sure and must be completely sealed to prevent leak-
age of combustion products into the living space.
TABLE 3
MINIMUM VENT PIPE LENGTHS
EL296UHE
MODEL
MIN. VENT LENGTH*
Vent Piping Guidelines
15 ft. or
5 ft. plus 2 elbows or
10 ft. plus 1 elbow
045, 070, 090, 110, 135
The EL296UHE can be installed as either a Non-Direct
Vent or a Direct Vent gas central furnace.
*Any approved termination may be added to the minimum length listed.
Page 16
Download from Www.Somanuals.com. All Manuals Search And Download.
Use the following steps to correctly size vent pipe diameter.
IMPORTANT
Do not use screens or perforated metal in exhaust or
intake terminations. Doing so will cause freeze-ups
and may block the terminations.
Piping Size Process
What is the
furnace capacity?
1
2
045, 070, 090,
110 or 135?
Which style termination
being used?
Standard or concentric?
Which needs
most elbows?
Intake or
3
exhaust?
How many elbows?
Count all elbows inside
and outside house.
4
5
Desired pipe size?
2”, 2-1/2”, 3”
What is the altitude of
the furnace installation?
6
max intake or exhaust pipe
length. Includes all vent
pipe and elbows inside
and outside the house.
7
FIGURE 23
Page 17
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 4
OUTDOOR TERMINATION USAGE
STANDARD
CONCENTRIC
Wall Kit
Wall Ring Kit
2 inch
FlushMount
Kit
1-1/2 inch
2 inch
3 inch
Vent
Pipe
Dia. in.
2 inch
3 inch
Input Size
Field
Fabricated
71M80
(US)
44W92
(CA)
69M29
(US)
44W92
(CA)
51W11 (US)
51W12 (CA)
22G44 (US)
30G28 (CA)
44J40 (US)
4
60L46 (US)
44W93 (CA)
15F74
4
4
4
4
81J20 (CA)
3
1
1
5
2
2
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
3
1
1
5
2
2-1/2
YES
YES
YES
YES
YES
045
070
090
3
1
1
5
2
3
YES
YES
YES
YES
YES
3
1
1
5
2
2
YES
YES
YES
YES
YES
3
1
1
5
2
2-1/2
YES
YES
YES
YES
YES
3
1
1
5
2
3
YES
YES
YES
YES
YES
3
5
2
2-1/2
3
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
3
5
YES
YES
3
5
YES
YES
5
2
YES
YES
YES
YES
YES
5
2-1/2
3
YES
110
135
5
YES
YES
YES
5
3
YES
NOTE - Standard Terminations do not include any vent pipe or elbows external to the structure. Any vent pipe or elbows external to the structure must be included in total vent length
calculations. See vent length tables.
1
Requires field-provided outdoor 1-1/2” exhaust accelerator.
Concentric kits 71M80 and 44W92 include 1-1/2” outdoor accelerator, when used with 045 and 070 input models.
Flush mount kit 51W11 and 51W12 includes 1-1/2 in. outdoor exhaust accelerator, required when used with 045, 070 and 090 input models.
Termination kits 30G28, 44W92, 44W93 and 81J20 are certified to ULC S636 for use in Canada only.
See table 8 for vent accelerator requirements.
2
3
4
5
Page 18
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 5
Maximum Allowable Intake or Exhaust Vent Length in Feet
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe
size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.
Standard Termination at Elevation 0 - 4500 ft
2” Pipe
Model
090
44
2-1/2” Pipe
3” Pipe
Model
090
118
113
108
103
98
Number Of
90° Elbows
Used
Model
090
93
045
81
76
71
66
61
56
51
46
41
36
070
66
61
56
51
46
41
36
31
26
21
110
24
135
045
115
110
105
100
95
070
115
110
105
100
95
110
58
53
48
43
38
33
28
23
18
13
135
045
138
133
128
123
118
113
108
103
98
070
137
132
127
122
117
112
107
102
97
110
118
113
108
103
98
135
114
109
104
99
1
2
39
19
88
3
34
14
83
4
29
78
5
24
73
94
n/a
n/a
6
19
90
90
68
93
93
89
7
14
85
85
63
88
88
84
n/a
8
80
80
58
83
83
79
9
75
75
53
78
78
74
n/a
10
70
70
48
93
92
73
73
69
Standard Termination Elevation 4500 - 10,000 ft
2” Pipe
Model
090
44
2-1/2” Pipe
3” Pipe
Model
090
118
113
108
103
98
Number Of
90° Elbows
Used
Model
045
81
76
71
66
61
56
51
46
41
36
070
66
61
56
51
46
41
36
31
26
21
110
135
045
115
110
105
100
95
070
115
110
105
100
95
090
93
88
83
78
73
68
63
58
53
48
110
58
53
48
43
38
33
28
23
18
13
135
045
138
133
128
123
118
113
108
103
98
070
137
132
127
122
117
112
107
102
97
110
118
113
108
103
98
135
114
109
104
99
1
2
39
3
34
4
29
5
24
94
n/a
n/a
n/a
6
19
90
90
93
93
89
7
14
85
85
88
88
84
8
80
80
83
83
79
9
75
75
78
78
74
n/a
10
70
70
93
92
73
73
69
See concentric terminations next page.
Page 19
Download from Www.Somanuals.com. All Manuals Search And Download.
Maximum Allowable Intake or Exhaust Vent Length in Feet
Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.
Concentric Termination at Elevation 0 - 4500 ft
2” Pipe
Model
090
42
2-1/2” Pipe
3” Pipe
Model
090
114
109
104
99
Number Of
90° Elbows
Used
Model
090
89
045
73
68
63
58
53
48
43
38
33
28
070
58
53
48
43
38
33
28
23
18
13
110
22
135
045
105
100
95
070
105
100
95
110
54
49
44
39
34
29
24
19
14
n/a
135
045
121
116
111
106
101
96
070
121
116
111
106
101
96
110
114
109
104
99
135
105
100
95
1
2
37
17
84
3
32
12
79
4
27
90
90
74
90
5
22
85
85
69
94
94
85
n/a
n/a
6
17
80
80
64
89
89
80
7
12
75
75
59
91
91
84
84
75
n/a
8
70
70
54
86
86
79
79
70
9
65
65
49
81
81
74
74
65
n/a
10
60
60
44
76
76
69
69
60
Concentric Termination Elevation 4501 - 10,000 ft
2” Pipe
2-1/2” Pipe
3” Pipe
Model
090
114
109
104
99
Number Of
90° Elbows
Used
Model
090
42
Model
090
89
045
73
68
63
58
53
48
43
38
33
28
070
58
53
48
43
38
33
28
23
18
13
110
135
045
105
100
95
070
105
100
95
110
54
49
44
39
34
29
24
19
14
n/a
135
045
121
116
111
106
101
96
070
121
116
111
106
101
96
110
114
109
104
99
135
105
100
95
1
2
37
84
3
32
79
4
27
90
90
74
90
5
22
85
85
69
94
94
85
n/a
n/a
n/a
6
17
80
80
64
89
89
80
7
12
75
75
59
91
91
84
84
75
8
70
70
54
86
86
79
79
70
9
65
65
49
81
81
74
74
65
n/a
10
60
60
44
76
76
69
69
60
Page 20
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 6
Maximum Allowable Exhaust Vent Lengths With Furnace Installed in a Closet or Basement Using Ventilated
Attic or Crawl Space For Intake Air in Feet
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe
size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.
Standard Termination at Elevation 0 - 4500 ft
2” Pipe
Model
090
34
2-1/2” Pipe
3” Pipe
Model
090
98
Number Of
90° Elbows
Used
Model
090
78
045
71
66
61
56
51
46
41
36
31
26
070
56
51
46
41
36
31
26
21
16
11
110
14
9
135
045
100
95
90
85
80
85
70
65
60
55
070
100
95
90
85
80
75
70
65
60
55
110
43
38
33
28
23
18
13
8
135
045
118
113
108
103
98
070
117
112
107
102
97
110
98
93
88
83
78
73
68
63
58
53
135
94
89
84
79
74
69
64
59
54
49
1
2
29
73
93
3
24
4
68
88
4
19
63
83
5
14
58
78
n/a
n/a
6
9
63
93
92
73
7
4
48
88
87
68
n/a
8
43
83
82
63
9
38
3
78
77
58
n/a
10
33
n/a
73
72
53
Standard Termination Elevation 4500 - 10,000 ft
2” Pipe
Model
090
34
2-1/2” Pipe
3” Pipe
Model
090
98
Number Of
90° Elbows
Used
Model
045
71
66
61
56
51
46
41
36
31
26
070
56
51
46
41
36
31
26
21
16
11
110
135
045
100
95
90
85
80
85
70
65
60
55
070
100
95
90
85
80
85
70
65
60
55
090
78
73
68
63
58
53
48
43
38
33
110
43
38
33
28
23
18
13
8
135
045
118
113
108
103
98
070
117
112
107
102
97
110
98
93
88
83
78
73
68
63
58
53
135
94
89
84
79
74
69
64
59
54
49
1
2
29
93
3
24
88
4
19
83
5
14
78
n/a
n/a
n/a
6
9
93
92
73
7
4
88
87
68
8
83
82
63
9
3
78
77
58
n/a
10
n/a
73
72
53
Page 21
Download from Www.Somanuals.com. All Manuals Search And Download.
TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN UPFLOW DIRECT OR
NON-DIRECT VENT APPLICATIONS
EXHAUST INTAKE
EXHAUST
INTAKE
2”
2”
2”
2”
or
3”
3”
TRANSITION
TRANSITION
2”
2”
*2”
*2”
DO NOT transition
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
FIGURE 24
TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN HORIZONTAL DIRECT OR NON-DIRECT VENT
APPLICATIONS (RIGHT HAND DISCHARGE SHOWN)
45°
MAX
45°
MAX
12” max.
2”
or
EXHAUST
2”
2”
2”
2”
or
2”
2”
*2”
2”
SIDE VIEW
2”
2”
INTAKE
3”
DO NOT transition
from smaller to larger
pipe in horizontal runs
TRANSITION
3”
*2”
of exhaust pipe.
EXHAUST
*2”
*2”
*2”
INTAKE
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
FIGURE 25
Page 22
Download from Www.Somanuals.com. All Manuals Search And Download.
Intake Piping
TYPICAL AIR INTAKE PIPE CONNECTIONS
HORIZONTAL NON−DIRECT VENT APPLICATIONS
(Horizontal Right−Hand Air Discharge Application Shown)
The EL296UHE furnace may be installed in either direct
vent or non-direct vent applications. In non-direct vent
applications, when intake air will be drawn into the furnace
from the surrounding space, the indoor air quality must be
considered and guidelines listed in Combustion, Dilution
and Ventilation Air section must be followed.
PVC pipe
coupling
Follow the next two steps when installing the unit in Direct
Vent applications, where combustion air is taken from
outdoors and flue gases are discharged outdoors. The
provided air intake screen must not be used in direct
vent applications (outdoors).
OR
1 - Use transition solvent cement or a sheet metal screw
to secure the intake pipe to the inlet air connector.
INTAKE
DEBRIS
SCREEN
(Provided)
2 - Route piping to outside of structure. Continue with
installation following instructions given in general
guidelines for piping terminations and intake and ex-
haust piping terminations for direct vent sections. Re-
NOTE - Debris screen may be positioned straight out
(preferred) or with an elbow rotated to face down.
TYPICAL AIR INTAKE PIPE CONNECTIONS
UPFLOW NON−DIRECT
FIGURE 27
VENT APPLICATIONS
Follow the next two steps when installing the unit in Non‐
Direct Vent applications where combustion air is taken
from indoors or ventilated attic or crawlspace and flue
gases are discharged outdoors.
INTAKE
DEBRIS
SCREEN
(Provided)
1 - Use field-provided materials and the factory-provided
air intake screen to route the intake piping as shown in
(76mm) around the air intake opening. The air intake
opening (with the protective screen) should always be
directed forward or to either side in the upflow position,
and either straight out or downward in the horizontal
position.
The air intake piping must not terminate too close
to the flooring or a platform. Ensure that the intake
air inlet will not be obstructed by loose insulation
or other items that may clog the debris screen.
ameter pipe is used, reduce to 2” diameter pipe at the
termination point to accommodate the debris screen.
NOTE - Debris screen and elbow may be rotated, so that
screen may be positioned to face forward or to either side.
3 - Use a sheet metal screw to secure the intake pipe to
the connector, if desired.
FIGURE 26
Page 23
Download from Www.Somanuals.com. All Manuals Search And Download.
General Guidelines for Vent Terminations
CAUTION
In Non‐Direct Vent applications, combustion air is taken
from indoors or ventilated attic or crawlspace and the flue
gases are discharged to the outdoors. The EL296UHE is
then classified as a non‐direct vent, Category IV gas fur-
nace.
If this unit is being installed in an application with
combustion air coming in from a space serviced by
an exhaust fan, power exhaust fan, or other device
which may create a negative pressure in the space,
take care when sizing the inlet air opening. The in-
let air opening must be sized to accommodate the
maximum volume of exhausted air as well as the
maximum volume of combustion air required for
all gas appliances serviced by this space.
In Direct Vent applications, combustion air is taken from
outdoors and the flue gases are discharged to the out-
doors. The EL296UHE is then classified as a direct vent,
Category IV gas furnace.
In both Non‐Direct Vent and Direct Vent applications, the
vent termination is limited by local building codes. In the
absence of local codes, refer to the current National Fuel
Gas Code ANSI Z223-1/NFPA 54 in U.S.A., and current
CSA-B149 Natural Gas and Propane Installation Codes in
Canada for details.
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Attic and Outlet Air to Outside)
Ventilation Louvers
Inlet Air
Roof Terminated
Exhaust Pipe
(Minimum
12 in.(305mm) Above
attic floor)
obstructions and 12” above the average snow accumula-
tion.
*Intake Debris
Screen
(Provided)
At vent termination, care must be taken to maintain
protective coatings over building materials (prolonged
exposure to exhaust condensate can destroy protective
coatings). It is recommended that the exhaust outlet not be
located within 6 feet (1.8m) of a condensing unit because
the condensate can damage the painted coating.
Furnace
NOTE-The inlet and outlet air openings shall each have a free area
2
of at least one square inch per 4,000 Btu (645mm per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
length without insulation in unconditioned space during
winter design temperatures below 32°F (0°C). If required
exhaust pipe should be insulated with 1/2” (13mm) Arma-
flex or equivalent. In extreme cold climate areas, 3/4”
(19mm) Armaflex or equivalent may be necessary. Insula-
tion on outside runs of exhaust pipe must be painted or
wrapped to protect insulation from deterioration. Exhaust
pipe insulation may not be necessary in some specific ap-
plications.
FIGURE 28
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
Inlet Air
(Minimum
IMPORTANT
Do not use screens or perforated metal in exhaust
terminations. Doing so will cause freeze-ups and
may block the terminations.
12 in.(305mm)
Above crawl
space floor)
Ventilation
Louvers
(Crawl space)
Furnace
Coupling or
*Intake Debris Screen Provided)
3 in. to 2 in.
Transition
IMPORTANT
For Canadian Installations Only:
(Field Provided)
In accordance to CSA International B149 installation
codes, the minimum allowed distance between the
combustion air intake inlet and the exhaust outlet of
other appliances shall not be less than 12 inches
(305mm).
NOTE-The inlet and outlet air openings shall each have a free area
2
of at least one square inch per 4,000 Btu (645mm per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
FIGURE 29
Page 24
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 7
Maximum Allowable Exhaust Vent Pipe Length Without Insulation
In Unconditioned Space For Winter Design Temperatures
Unit Input Size
Vent Pipe
Diameter
Winter Design
1
Temperatures °F (°C)
045
20
15
12
12
10
6
070
30
22
18
20
14
10
12
8
090
40
30
25
25
20
15
18
12
10
110
24
40
32
24
24
20
22
16
12
135
N/A
N/A
32
2 in.
2-1/2 in.
3 in.
32 to 21
(0 to -6)
2 in
N/A
N/A
20
20 to 1
(-7 to -17)
2-1/2 in.
3 in.
2 in.
8
N/A
N/A
12
0 to -20
(-18 to -29)
2-1/2 in.
3 in.
6
2
6
1
Refer to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook.
NOTE - Maximum uninsulated vent lengths listed may include the termination(vent pipe exterior to the structure) and cannot exceed 5 linear feet or the
Page 25
Download from Www.Somanuals.com. All Manuals Search And Download.
VENT TERMINATION CLEARANCES
FOR NON-DIRECT VENT INSTALLATIONS IN THE US AND CANADA
INSIDE CORNER
DETAIL
G
H
A
D
E
B
L
B
Fixed
Closed
B
B
I
C
Operable
Fixed
Closed
M
F
Operable
K
J
A
B
AREA WHERE TERMINAL
IS NOT PERMITTED
AIR SUPPLY INLET
VENT TERMINAL
1
2
US Installations
Canadian Installations
A =
Clearance above grade, veranda,
porch, deck or balcony
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
B =
Clearance to window or
door that may be opened
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
4 feet (1.2 m) below or to side of opening;
1 foot (30cm) above opening
C =
D =
Clearance to permanently
closed window
* 12”
* 12”
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (610 mm)
from the center line of the terminal
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
E =
F =
Clearance to unventilated soffit
Clearance to outside corner
* Equal to or greater than soffit depth.
* No minimum to outside corner
*
* No minimum to outside corner
*
G = Clearance to inside corner
H = Clearance to each side of center line ex-
tended above meter / regulator assembly
3 feet (.9m) within a height 15 feet (4.5m) 3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
*
above the meter / regulator assembly
I =
Clearance to service regulator
vent outlet
3 feet (.9m)
* 3 feet (.9m)
J =
Clearance to non-mechanical air
supply inlet to building or the com-
bustion air inlet to any other ap-
pliance
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
K =
L =
Clearance to mechanical air sup-
ply inlet
3 feet (.9m) above if within 10 feet
(3m) horizontally
6 feet (1.8m)
Clearance above paved sidewalk or
paved driveway located on public property
7 feet (2.1m)†
7 feet (2.1m)†
M = Clearance under veranda, porch, deck or balcony
12 inches (305mm)‡
*12 inches (305mm)‡
1
2
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA
B149.1, clearance will be in accordance with local installation
codes and the requirements of the gas supplier and these instal-
lation instructions.”
† A vent shall not terminate directly above a sidewalk or paved driveway that is
located between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck or balcony is fully open
on a minimum of two sides beneath the floor. Lennox recommends
avoiding this location if possible.
FIGURE 30
Page 26
Download from Www.Somanuals.com. All Manuals Search And Download.
VENT TERMINATION CLEARANCES
FOR DIRECT VENT INSTALLATIONS IN THE US AND CANADA
INSIDE CORNER
DETAIL
G
H
A
D
E
B
L
B
Fixed
Closed
B
B
I
C
Operable
Fixed
Closed
M
F
Operable
K
J
A
B
AREA WHERE TERMINAL
IS NOT PERMITTED
AIR SUPPLY INLET
VENT TERMINAL
1
2
US Installations
Canadian Installations
A =
Clearance above grade, veranda,
porch, deck or balcony
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
B =
Clearance to window or
door that may be opened
6 inches (152mm) for appliances <10,000 6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (228mm) for ap-
pliances > 10,000 Btuh (3kw) and <50,000
Btuh (15 kw), 12 inches (305mm) for ap-
pliances > 50,000 Btuh (15kw)
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
* 12”
C =
D =
Clearance to permanently
closed window
* 12”
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (610mm)
from the center line of the terminal
* Equal to or greater than soffit depth
* Equal to or greater than soffit depth
* Equal to or greater than soffit depth
* Equal to or greater than soffit depth
* No minimum to outside corner
E =
F =
G =
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
* No minimum to outside corner
*
*
H = Clearance to each side of center line ex-
tended above meter / regulator assembly
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
I =
Clearance to service regulator
vent outlet
3 feet (.9m)
* 3 feet (.9m)
J =
Clearance to non-mechanical air
supply inlet to building or the com-
bustion air inlet to any other ap-
pliance
6 inches (152mm) for appliances <10,000 6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (228mm) for ap-
pliances > 10,000 Btuh (3kw) and <50,000
Btuh (15 kw), 12 inches (305mm) for ap-
pliances > 50,000 Btuh (15kw)
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
K =
L =
Clearance to mechanical air sup-
ply inlet
3 feet (.9m) above if within 10 feet
(3m) horizontally
6 feet (1.8m)
Clearance above paved sidewalk or
paved driveway located on public property
7 feet (2.1m)†
* 7 feet (2.1m)
M = Clearance under veranda, porch, deck or balcony
*12 inches (305mm)‡
12 inches (305mm)‡
1
2
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA
B149.1, clearance will be in accordance with local installation
codes and the requirements of the gas supplier and these
installation instructions.”
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
† A vent shall not terminate directly above a sidewalk or paved driveway that is located
between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of
two sides beneath the floor. Lennox recommends avoiding this location if possible.
FIGURE 31
Page 27
Download from Www.Somanuals.com. All Manuals Search And Download.
Details of Intake and Exhaust Piping Terminations for
Direct Vent Installations
3”(76MM) MAX.
SIZE TERMINATION
PIPE PER TABLE 8.
Inches(MM)
NOTE - In Direct Vent installations, combustion air is tak-
en from outdoors and flue gases are discharged to out-
doors.
UNCONDITIONED
ATTIC SPACE
8” (203MM) MIN
1/2” (13MM) FOAM
INSULATION IN
UNCONDITIONED
SPACE
NOTE - Flue gas may be slightly acidic and may adversely
affect some building materials. If any vent termination is
used and the flue gasses may impinge on the building ma-
terial, a corrosion-resistant shield (minimum 24 inches
square) should be used to protect the wall surface. If the
optional tee is used, the protective shield is recommended.
The shield should be constructed using wood, plastic,
sheet metal or other suitable material. All seams, joints,
cracks, etc. in the affected area should be sealed using an
12” (305MM) ABOVE
AVERAGE SNOW
ACCUMULATION
3” (76MM) OR
2” (51MM) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
Intake and exhaust pipes may be routed either horizontally
through an outside wall or vertically through the roof. In at-
tic or closet installations, vertical termination through the
terminations.
DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
FIGURE 32
Exiting Exhaust and Intake Vent
(different pressure zones)
1 - Intake and exhaust terminations are not required to be
in the same pressure zone. You may exit the intake on
one side of the structure and the exhaust on another
2 - Intake and exhaust pipes should be placed as close
together as possible at termination end (refer to il-
lustrations). Maximum separation is 3” (76MM) on roof
terminations and 6” (152MM) on side wall termina-
tions.
Inlet Air
Exhaust
Pipe
Furnace
(Minimum 12 in.
305 MM) above
grade or snow
accumulation
NOTE - When venting in different pressure zones, the
maximum separation requirement of intake and ex-
haust pipe DOES NOT apply.
FIGURE 33
3 - On roof terminations, the intake piping should termi-
nate straight down using two 90° elbows (See figure
32).
Exiting Exhaust and Intake Vent
(different pressure zones)
4 - Exhaust piping must terminate straight out or up as
shown. A reducer may be required on the exhaust pip-
ing at the point where it exits the structure to improve
the velocity of exhaust away from the intake piping.
Roof T
erminated
Exhaust Pipe
NOTE - Care must be taken to avoid recirculation of ex-
haust back into intake pipe.
Inlet Air
5 - On field-supplied terminations for side wall exit, ex-
haust piping may extend a maximum of 12 inches
(305MM) for 2” PVC and 20 inches (508MM) for 3”
(76MM) PVC beyond the outside wall. Intake piping
6 - On field-supplied terminations, a minimum distance
between the end of the exhaust pipe and the end of
the intake pipe without a termination elbow is 8” and a
minimum distance of 6” with a termination elbow. See
(Minimum 12 in.
305 MM) above
grade or snow
accumulation
Furnace
FIGURE 34
TABLE 8
EXHAUST PIPE TERMINATION SIZE REDUCTION
EL296UHE
MODEL
Termination
Pipe Size
1-1/2” (38MM)
*045 and 070
*090
110
2” (51MM)
2” (51MM)
2” (51MM)
135
*EL296UHE-045, -070 and -090 units with the flush mount termination must
use the 1-1/2”accelerator supplied with the kit.
Page 28
Download from Www.Somanuals.com. All Manuals Search And Download.
7 - If intake and exhaust piping must be run up a side wall
to position above snow accumulation or other ob-
structions, piping must be supported every 24”
close coupled wall termination kits must be extended
When exhaust and intake piping must be run up an
outside wall, the exhaust piping must be terminated
equipped with a 90° elbow turndown. Using turndown
will add 5 feet (1.5m) to the equivalent length of the
pipe.
8 - A multiple furnace installation may use a group of up to
four terminations assembled together horizontally, as
Alternate Terminations
(Tee & Forty-Five Degree Elbows Only)
B
B
D
D
C
3
Intake
C
1
Front View of
Intake and Exhaust
A
Exhaust
A
2
Intake
Exhaust
TABLE 9
2” (51MM)
Vent Pipe
D
3” (76MM)
Vent Pipe
1
A- Clearance above
grade or average snow
accumulation
E
12” (305MM) Min.
12” (305MM) Min.
B
B-Horizontal
separation between
intake and exhaust
6” (152MM) Min. 6” (152MM) Min.
24” (610MM) Max 24” (610MM) Max
12”
C-Minimum from
end of exhaust to
inlet of intake
9” (227MM) Min. 9” (227MM) Min.
C
2
12” (305MM) Min.
16” (405MM) Max.
12” (305MM) Min.
20” (508MM) Max.
D-Exhaust pipe length
A
E-Wall support distance
from top of each pipe
(intake/exhaust)
6” (152MM) Max. 6” (152MM) Max.
1
The exhaust termination tee should be connected to the 2” or 3” PVC flue pipe as shown in the illustration. Do
not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.
As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent
2
termination is used and flue gases will impinge on the building materials, a corrosion-resistant shield (24 inches
square) should be used to protect the wall surface. If optional tee is used, the protective shield is recommende-
d. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints,
cracks, etc. in affected area, should be sealed using an appropriate sealant.
3
Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away
from adjacent property. The exhaust must never be directed toward the combustion air inlet.
FIGURE 35
Page 29
Download from Www.Somanuals.com. All Manuals Search And Download.
FIELD FABRICATED WALL TERMINATION OR
(15F74) WALL RING TERMINATION KIT
With INTAKE ELBOW
FIELD FABRICATED WALL TERMINATION OR
(15F74) WALL RING TERMINATION KIT
NOTE - FIELD-PROVIDED
REDUCER MAY BE
NOTE - FIELD-PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION
1/2” (13MM) ARMAFLEX
INSULATION IN UN-
CONDITIONED SPACE
1/2” (13MM) ARMAFLEX
REQUIRED TO ADAPT
INSULATION IN UN-
LARGER VENT PIPE SIZE
CONDITIONED SPACE
TO TERMINATION
SIZE TERMINATION
PER TABLE 8
SIZE TERMINATION
PER TABLE 8
D
B
D
B
STRAIGHT
APPPLICATION
A
STRAIGHT
APPPLICATION
C
C
A
1/2” (13MM) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE
1/2” (13MM) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE
D
D
E
* WALL
SUPPORT
E
* WALL
SUPPORT
B
B
A
A
EXTENDED
APPLICATION
C
C
EXTENDED
APPLICATION
arrangement.
arrangement.
* Use wall support every 24” (610MM). Use two wall supports if
extension is greater than 24” (610MM) but less than 48” (1219 MM).
NOTE - One wall support must be 6” (152MM) from top of each pipe
(intake and exhaust)
* Use wall support every 24” (610MM). Use two wall supports if
extension is greater than 24” (610MM) but less than 48” (1219 MM).
NOTE - One wall support must be 6” (152MM) from top of each pipe
(intake and exhaust)
2” (51MM)
Vent Pipe
3” (76MM)
Vent Pipe
2” (51MM)
Vent Pipe
3” (7MM)
Vent Pipe
A-Minimum clearance
above grade or average
snow accumulation
A-Minimum clearance
above grade or average
snow accumulation
12” (305MM)
12” (305MM)
12” (305MM)
6” (152MM)
8” (203MM)
12” (305MM)
6” (152MM)
8” (203MM)
B-Maximum horizontal
separation between
intake and exhaust
B-Maximum horizontal
separation between
intake and exhaust
6” (152MM)
6” (152MM)
C-Minimum from
end of exhaust to
inlet of intake
C-Minimum from
end of exhaust to
inlet of intake
6” (152MM)
20” (508MM)
6” (152MM)
6” (152MM)
12” (305MM)
6” (152MM)
D-Maximum exhaust
pipe length
D-Maximum exhaust
pipe length
12” (305MM)
6” (152MM)
20” (508MM)
6” (152MM)
E-Maximum wall support
distance from top of each
pipe (intake/exhaust)
E-Maximum wall support
distance from top of each
pipe (intake/exhaust)
FIGURE 37
FIGURE 36
Page 30
Download from Www.Somanuals.com. All Manuals Search And Download.
2” EXTENSION FOR 2” PVC
PIPE1” EXTENSION FOR 3”
PVC PIPE
12”
(305MM)
5-1/2”
(140mm)
EXHAUST
VENT
FURNACE
EXHAUST
PIPE
5”
(127MM)
4''
INTAKE
AIR
18” MAX.
(457MM)
FURNACE
INTAKE
PIPE
Front View
NT
12” (305MM) Min.
above grade or
average snow
accumulation.
GLUE EXHAUST
END FLUSH INTO
TERMINATION
Inches (MM)
AKE
IR
FLAT
SIDE
1-1/2” ACCELERATOR
(all -45, -070 and -090 units)
optional intake elbow
FLUSH-MOUNT SIDE WALL TERMINATION
51W11 (US) or 51W12 (Canada)
Side View
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT
(22G44, 44J40, 30G28 or 81J20)
FIGURE 38
FIGURE 41
1 1/2” (38mm) accelerator
EXHAUST VENT
provided on 71M80 & 44W92
kits for EL296UH045E36B, &
070E36B
Front View
EXHAUST
VENT
SIZE
TERMINATION
PIPE PER
FLASHING
(Not Furnished)
INTAKE
AIR
12” (305mm)
INTAKE
AIR
Minimum
Above Average
Snow
Top View
1/2” (13MM) Foam Insulation
in Unconditioned Space
Accumulation
FIELD-
PROVIDED
SHEET METAL STRAP
EXHAUST VENT
REDUCER MAY
(Clamp and sheet metal strap
must be field installed to support
the weight of the termination kit.)
BE REQUIRED
TO ADAPT
LARGER VENT
INTAKE AIR
CLAMP
PIPE SIZE TO
TERMINATION
FIELD-PROVIDED
6 (152MM) MIN.
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
OUTSIDE WALL
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
DIRECT VENT WALL TERMINATION KIT
(30G28 or 81J20)
FIGURE 42
FIGURE 39
EXHAUST VENT
Front View
SIZE
TERMINATION
PIPE PER
FIELD-PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
1-1/2” (38mm) accelerator
provided on 71M80 & 44W92
kits for EL296UH045E36B, &
070E36B
INTAKE
AIR
OUTSIDE
INTAKE
WALL
AIR
1/2” (13MM) Foam Insulation
in Unconditioned Space
Top View
EXHAUST
VENT
EXHAUST
VENT
FIELD-
PROVIDED
REDUCER MAY
BE REQUIRED
EXHAUST VENT
TO ADAPT
INTAKE AIR
LARGER VENT
12” (305mm) Min.
above grade or
average snow
accumulation.
INTAKE
AIR
INTAKE
AIR
CLAMP
(Not Furnished)
PIPE SIZE TO
TERMINATION
8” (206MM) MIN.
GRADE
DIRECT VENT CONCENTRIC WALL TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
OUTSIDE WALL
DIRECT VENT WALL TERMINATION KIT
(22G44 or 44J40)
FIGURE 40
FIGURE 43
Page 31
Download from Www.Somanuals.com. All Manuals Search And Download.
WALL TERMINATION KITS (CLOSE−COUPLE)
EXTENDED VENT FOR GRADE CLEARANCE
2 inch (51 mm) 22G44 (US)
3 inch (76 mm) 44J40 (US)
If intake and exhaust pipe is less than 12 in. (305 MM)
above snow accumulation or other obstructions, field−
fabricated piping must be installed.
FIELD-PROVIDED
REDUCER MAY BE REQUIRED TO ADAPT
LARGER VENT PIPE SIZE TO TERMINATION
8” (203mm) Min. for 2” (51MM) & 3” (76MM) DIA. pipe
between the end of the exhaust pipe and intake pipe
12” (305MM) Max. for 2” (51MM) Dia. Exhaust
20” (508MM) Max. for 3” (76MM) Dia. Exhaust
WALL SUPPORT*
12”
(305 mm)
EXHAUST
AIR
1/2” (13 mm)
FOAM INSULATION
(Field−Furnished)
6” (152 MM)
Maximum
INTAKE
AIR
EXHAUST
AIR
INTAKE
AIR
5” (127 mm)
12” (305 MM) Minimum
8” (203 mm) Min.
12” (305MM) Minimum
Above Grade or Average
Snow Accumulation
Above Grade or Average
5−1/2”
(140 mm)
Snow Accumulation
GRADE
GRADE
*Use wall support every 24” (610). Use two supports if
extension is greater than 24” but less than 48”.
12” (305 MM) Max. for 2” (51MM) Dia. Exhaust
20” (508MM) Max. for 3” (76MM) Dia. Exhaust
FIGURE 44
WALL TERMINATION KITS (CLOSE−COUPLE)
EXTENDED VENT FOR GRADE CLEARANCE
2 inch (51 mm) 30G28 (WTK Canada)
3 inch (76 mm) 81J20 (WTK Canada)
See Installation Instructions for additional information.
If intake and exhaust pipe is less than 12 in. (305 MM)
above snow accumulation or other obstructions, field−
fabricated piping must be installed.
FIELD-PROVIDED
REDUCER MAY BE REQUIRED TO ADAPT
LARGER VENT PIPE SIZE TO TERMINATION
WALL SUPPORT*
12” (305 MM) Max. for 2” (51 MM) Dia. Exhaust
20” (508 MM) Max. for 3” (76 MM) Dia. Exhaust
12”
(305 mm)
EXHAUST
AIR
1/2” (13 mm)
FOAM INSULATION
(Field−Furnished)
6” (152 MM)
Maximum
INTAKE
AIR
6” (152 MM)
Minimum
EXHAUST
AIR
INTAKE
AIR
5” (127 mm)
12” (305 MM) Minimum
Above Grade or Average
Snow Accumulation
6” (152 MM)
Minimum
12” (305 MM) Minimum
Above Grade or Average
Snow Accumulation
GRADE
5−1/2”
(140 mm)
GRADE
*Use wall support every 24” (610). Use two supports if
extension is greater than 24” but less than 48”.
12” (305 MM) Max. for 2” (51 MM) Dia. Exhaust
20” (508 MM) Max. for 3” (76 MM) Dia. Exhaust
FIGURE 45
Page 32
Download from Www.Somanuals.com. All Manuals Search And Download.
EL296UHE DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
12” (305MM) MAX. for 2” (51MM)
20” (508MM) MAX. for 3” (76MM)
1/2” (13MM) ARMAFLEX
INSULATION IN
UNCONDITIONED SPACE
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE *
3”-8”
(76MM-203MM)
1/2” (13MM)
ARMAFLEX
INSULATION
FIELD-PROVIDED
REDUCER MAY
BE REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE
TO TERMINATION
EXHAUST VENT
1/2” (13MM)
WEATHERPROOF
INSULATION
8” - 12”
(203MM - 305MM)
PVC REDUCER
12” MIN.
(305MM)
Above Grade or
average snow
accumulation
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
Minimum 12” (305MM)
INTAKE PIPE
INSULATION (optional)
SIZE TERMINATION
PIPE PER TABLE 8.
above chimney top
plate or average snow
accumulation
SHEET
METAL TOP
PLATE
ALTERNATE
INTAKE PIPE
3” - 8”
(76MM-
203MM)
NON-DIRECT VENT FIELD SUPPLIED WALL TERMINATION OR
(15F74) WALL TERMINATION KIT
INSULATE
TO FORM
SEAL
EXTERIOR
PORTION OF
CHIMNEY
FIGURE 48
3 - If exhaust piping must be run up a side wall to position
above snow accumulation or other obstructions, pip-
ing must be supported every 24 inches (610MM) as
shown in figure 49. When exhaust piping must be run
up an outside wall, any reduction in exhaust pipe size
must be done after the final elbow.
*SIZE TERMINATION
PIPE PER TABLE 8.
NOTE - Do not discharge exhaust gases directly into any chimney or vent stack. If ver-
tical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illus-
trated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 46
12” (305MM) MAX. for 2” (51MM)
20” (508MM) MAX. for 3” (76MM)
UNCONDITIONED
SPACE
Details of Exhaust Piping Terminations for Non‐Direct
Vent Applications
Exhaust pipes may be routed either horizontally through an
outside wall or vertically through the roof. In attic or closet
installations, vertical termination through the roof is pre-
1 - Exhaust piping must terminate straight out or up as
shown. The termination pipe must be sized as listed in
ity required to move the exhaust gases away from the
building.
6” (152MM)
Max
SIZE TER-
MINATION
PIPE PER
*WALL SUPPORT
OUTSIDE WALL
FIELD-PROVIDED
12” (305MM)
REDUCER MAY BE
REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE TO
TERMINATION
ABOVE GRADE OR
AVERAGE SNOW
ACCUMULATION
1/2” (13MM) FOAM
INSULATION IN
UNCONDITIONED
SPACE
2 - On field supplied terminations for side wall exit, ex-
haust piping may extend a maximum of 12 inches
(305MM) for 2” PVC and 20 inches (508MM) for 3”
1/2” (13MM) FOAM
INSULATION
NON-DIRECT VENT FIELD SUPPLIED WALL TERMINATION
EXTENDED OR (15F74) WALL TERMINATION VENT PIPE
EXTENDED
*Use wall support every 24” (610). Use two supports if extension is
greater than 24” but less than 48”.
SIZE TERMINATION
PIPE PER TABLE 8.
12” (305MM)
ABOVE AVE.
SNOW
ACCUMULATION
FIGURE 49
1/2” (13MM) FOAM
INSULATION
3” (76MM) OR
2” (51MM) PVC
UNCONDITIONED
ATTIC SPACE
PROVIDE SUPPORT
FOR EXHAUST LINES
NON-DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
FIGURE 47
Page 33
Download from Www.Somanuals.com. All Manuals Search And Download.
CONDENSATE TRAP AND PLUG LOCATIONS
(Unit shown in upflow position)
Trap
EL296UHE NON-DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE
SIZE TERMINATION
PIPE PER TABLE 8.
(same on
right side)
1-1/2 in.
EXHAUST VENT
1/2” (13MM)
WEATHERPROOF
Minimum 12” (305MM)
above chimney top
INSULATION
plate or average snow
accumulation
Plug
(same on left side)
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
SHEET
METAL TOP
PLATE
INSULATE
TO FORM
SEAL
EXTERIOR
PORTION OF
CHIMNEY
NOTE - In upflow applications where side return
air filter is installed on same side as the conden-
sate trap, filter rack must be installed beyond
condensate trap or trap must be re-located to
avoid interference.
NOTE - Do not discharge exhaust gases directly into any chimney or vent stack. If ver-
tical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illus-
trated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 50
Condensate Piping
This unit is designed for either right‐ or left‐side exit of con-
densate piping in upflow applications. In horizontal applica-
tions, the condensate trap must extend below the unit. An
8” service clearance is required for the condensate trap.
Refer to figures 51 and 53 for condensate trap locations.
PVC.
FIGURE 51
coil using a separate drain. If necessary the conden-
sate line from the furnace and evaporator coil can
drain together. See figures 55, 57 and 58.
NOTE - If necessary the condensate trap may be installed
up to 5’ away from the furnace. Use PVC pipe to connect
trap to furnace condensate outlet. Piping from furnace
must slope down a minimum of 1/4” per ft. toward trap.
tions the field provided vent must be a minimum 1” to a
maximum 2” length above the condensate drain outlet
connection. Any length above 2” may result in a
flooded heat exchanger if the combined primary drain
line were to become restricted.
1 - Determine which side condensate piping will exit the
unit, location of trap, field-provided fittings and length of
PVC pipe required to reach available drain.
Horizontal furnace (figure 58) - In horizontal furnace
applications the field provided vent must be a mini-
mum 4” to a maximum 5” length above the condensate
drain outlet connection. Any length above 5” may re-
sult in a flooded heat exchanger if the combined pri-
mary drain line were to become restricted.
2 - Use a large flat head screw driver or a 1/2” drive socket
end header box at the appropriate location on the side
of the unit. Install provided 3/4 NPT street elbow fitting
into cold end header box. Use Teflon tape or appropri-
ate pipe dope.
3 - Install the cap over the clean out opening at the base
NOTE - In horizontal applications it is recommended to
install a secondary drain pan underneath the unit and
trap assembly.
4 - Install drain trap using appropriate PVC fittings, glue
all joints. Glue the provided drain trap as shown in fig-
Condensate line must maintain a 1/4” downward slope
from the furnace to the drain.
NOTE - Appropriately sized tubing and barbed fitting
may be used for condensate drain. Attach to the drain
Page 34
Download from Www.Somanuals.com. All Manuals Search And Download.
Field Provided Drain Components
EL296UHE With Evaporator
Coil Using A Separate Drain
Evaporator drain
line required
Elbow
Field Provided Vent
(1” min. 2” max. above
condensate connection)
Barbed Fitting
Hose Clamp
FIGURE 52
Tubing
Condensate
DrainConnection
CAUTION
Donot use copper tubing or existing copper conden-
sate lines for drain line.
6 - If unit will be started immediately upon completion of
installation, prime trap per procedure outlined in Unit
Start-Up section.
FIGURE 54
Condensate line must slope downward away from the
trap to drain. If drain level is above condensate trap,
condensate pump must be used. Condensate drain
line should be routed within the conditioned space to
avoid freezing of condensate and blockage of drain
line. If this is not possible, a heat cable kit may be used
on the condensate trap and line. Heating cable kit is
available from Lennox in various lengths; 6 ft. (1.8m) -
kit no. 26K68; 24 ft. (7.3m) - kit no. 26K69; and 50 ft.
(15.2m) - kit no. 26K70.
CONDENSATE TRAP LOCATIONS
(Unit shown in upflow position with remote trap)
Condensate Trap With Optional Overflow Switch
From Evaporator Coil
Horizontal Furnace Min.to 5” Max.above
4”
FieldProvidedVent
Min.1” AboveCondensate
DrainConnection
condensate drain connection)
1” Min.
2” Max.
FurnaceCondensate
DrainConnection
*5’ max.
PVCPipeOnly
Optional
Trap can be installed a
maximum 5' from furnace
To Drain
*Piping from furnace must slope down a minimum of
1/4” per ft. toward trap.
FIGURE 55
FIGURE 53
Page 35
Download from Www.Somanuals.com. All Manuals Search And Download.
EL296UHE with Evaporator Coil Using a Separate Drain
(Unit shown in horizontal left-hand discharge position)
Field Provided Vent
(4” min. to 5” max. above
condensate connection)
Evaporator
Coil
4”min
5”max
5’ max.
PVC Pipe Only
Condensate
DrainConnection
Drain Pan
Piping from furnace and evaporator coil must slope down a minimum 1/4” per ft. toward trap
.
FIGURE 56
EL296UHE with Evaporator
Coil Using a Common Drain
IMPORTANT
Evaporator drain
line required
When combining the furnace and evaporator
coil drains together, the A/C condensate drain
outlet must be vented to relieve pressure in or-
der for the furnace pressure switch to operate
properly.
(1”min. to 2” Max.above
condensate drain connection)
Condensate
DrainConnection
FIGURE 57
EL296UHE with Evaporator Coil Using a Common Drain
(Unit shown in horizontal left−hand discharge position)
(4”min. to 5” Max.above
condensate drain connection)
Evaporator
Coil
4”min
5”max
5’ max.
PVC Pipe Only
Condensaet Drain
Connection
Drain Pan
Piping from furnace and evaporator coil must slope down a minimum 1/4” per ft. toward trap
FIGURE 58
Page 36
Download from Www.Somanuals.com. All Manuals Search And Download.
TRAP / DRAIN ASSEMBLY USING 1/2” PVC OR 3/4” PVC
Optional Condensate Drain Connection
Adapter 3/4 inch slip X
3/4 inch mpt (not furnished)
90° Street Elbow
3/4 inch PVC
(not furnished)
Adapter 3/4 inch slip X
3/4 inch mpt (not furnished)
Condensate Drain
Connection In Unit
1 (25 mm) Min.
2 (50 mm) Max.
Above Top Of
Condensate Drain
Connection In Unit
Vent
5 Feet
Maximum
Condensate Drain
Connection In Unit
90° Street Elbow
3/4 inch PVC
( furnished)
90° Elbow 3/4 inch PVC
(Not Furnished)
To
Trap
3/4 inch PVC Pipe
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
OptionalDrainPipingFromTrap
Coupling 3/4 inch slip X slip
(Not Furnished)
Drain Assembly for 1/2 inch Drain Pipe
1/2 inch PVC Pipe
(Not Furnished)
Drain Trap
Assembly
(Furnished)
90° Elbow
1/2 inch PVC
(Not Furnished)
To
Drain
Drain Assembly for 3/4 inch Drain Pipe
Drain Trap
Clean Out
90° Elbow
90° Elbow
3/4 inch PVC
(Not Furnished)
3/4 inch PVC
(Not Furnished)
To
Drain
To
Drain
Coupling 3/4 inch slip X slip
(Not Furnished)
DrainTrap Assembly with 3/4 inch Piping
DrainTrap Assembly with 1/2 inch Piping
1 (25 mm) Min. 2 (50 mm) Max. Above Top
Of Condensate Drain Connection In Unit
1 (25 mm) Min. 2 (50 mm) Max. Above Top
Of Condensate Drain Connection In Unit
Vent
DrainTrapAssembly
(Furnished)
Vent
3/4 inch
1/2 inch
7
Condensate Drain
Connection In Unit
Condensate Drain
Connection In Unit
(178)
To
Drain
To
Drain
FIGURE 59
Page 37
Download from Www.Somanuals.com. All Manuals Search And Download.
6 - In some localities, codes may require installation of a
manual main shut‐off valve and union (furnished by in-
staller) external to the unit. Union must be of the
ground joint type.
Gas Piping
Gas supply piping should not allow more than 0.5”W.C. drop
in pressure between gas meter and unit. Supply gas pipe
must not be smaller than unit gas connection.
IMPORTANT
Compounds used on threaded joints of gas piping
must be resistant to the actions of liquified petro-
leum gases.
CAUTION
If a flexible gas connector is required or allowed by
the authority that has jurisdiction, black iron pipe
shall be installed at the gas valve and extend outside
the furnace cabinet. The flexible connector can then
be added between the black iron pipe and the gas
supply line.
Leak Check
After gas piping is completed, carefully check all piping
connections (factory- and field-installed) for gas leaks. Use
a leak detecting solution or other preferred means.
Never use an open flame to test for gas leaks. Check all
connections using a commercially available soap solution
made specifically for leak detection.
The furnace must be isolated from the gas supply system
by closing its individual manual shut‐off valve during any
pressure testing of the gas supply system at pressures
greater than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
WARNING
Do not exceed 600 in-lbs (50 ft-lbs) torque when at-
taching the gas piping to the gas valve.
MANUAL MAIN SHUT-OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
CAP
FURNACE
1 - Gas piping may be routed into the unit through either
the left‐ or right‐hand side. Supply piping enters into
the gas valve from the side of the valve as shown in
ISOLATE
GAS VALVE
1/8” N.P.T.
PLUGGED TAP
2 - When connecting gas supply, factors such as length of
run, number of fittings and furnace rating must be con-
lists recommended pipe sizes for typical applications.
FIGURE 60
NOTE - Use two wrenches when connecting gas pip-
ing to avoid transferring torque to the manifold.
IMPORTANT
When testing pressure of gas lines, gas valve must
valves can be damaged if subjected to pressures
greater than 1/2 psig (3.48 kPa).
3 - Gas piping must not run in or through air ducts, clothes
chutes, chimneys or gas vents, dumb waiters or eleva-
tor shafts. Center gas line through piping hole. Gas
4 - Piping should be sloped 1/4 inch per 15 feet (6mm per
5.6m) upward toward the gas meter from the furnace.
The piping must be supported at proper intervals, ev-
ery 8 to 10 feet (2.44 to 3.05m), using suitable hangers
or straps. Install a drip leg in vertical pipe runs to serve as
a trap for sediment or condensate.
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could
result in serious injury, death, or property damage.
Never use an open flame to test for gas leaks. Check
all connections using a commercially available soap
solution made specifically for leak detection. Some
soaps used for leak detection are corrosive to cer-
tain metals. Carefully rinse piping thoroughly after
leak test has been completed.
5 - A 1/8” N.P.T. plugged tap or pressure post is located
on the gas valve to facilitate test gauge connection.
Page 38
Download from Www.Somanuals.com. All Manuals Search And Download.
Left Side Piping
(Standard)
Right Side Piping
(Alternate)
MANUAL
MAIN SHUT-OFF
VALVE
MANUAL
MAIN SHUT-OFF
VALVE
GROUND
JOINT
UNION
GROUND
JOINT
UNION
DRIP LEG
Gas Valve
Gas Valve
DRIP LEG
FIELD
PROVIDED
AND INSTALLED
NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
FIGURE 61
Horizontal Applications
Possible Gas Piping Configurations
MANUAL
MAIN SHUT-OFF
VALVE
Horizontal Application
Left-Side Air Discharge
MANUAL
MAIN SHUT-OFF
VALVE
GROUND
JOINT
UNION
GROUND
JOINT
UNION
DRIP LEG
DRIP LEG
Gas Valve
Horizontal Application
Right-Side Air Discharge
MANUAL
MAIN SHUT-OFF
VALVE
Gas Valve
GROUND
JOINT
UNION
FIELD
PROVIDED
AND INSTALLED
DRIP LEG
NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
FIGURE 62
Page 39
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 10
GAS PIPE CAPACITY - FT3/HR (kL/HR)
Nominal
Iron Pipe
Size
inches
(mm)
Length of Pipe - feet (m)
Internal
Diameter
inches
(mm)
10
(3.048)
20
(6.096)
30
(9.144)
40
50
60
70
80
90
100
(12.192) (15.240) (18.288) (21.336) (24.384) (27.432) (30.480)
1/2
(12.7)
.622
(17.799)
172
(4.87)
118
(3.34)
95
(2.69)
81
(2.29)
72
(2.03)
65
(1.84)
60
(1.69)
56
(1.58)
52
(1.47)
50
(1.42)
3/4
(19.05)
.824
(20.930)
360
(10.19)
247
(7.00)
199
(5.63)
170
(4.81)
151
(4.28)
137
(3.87)
126
(3.56)
117
(3.31)
110
(3.11)
104
(2.94)
1
(25.4)
1.049
(26.645)
678
(19.19)
466
(13.19)
374
(10.59)
320
(9.06)
284
(8.04)
257
(7.27)
237
(6.71)
220
(6.23)
207
(5.86)
195
(5.52)
1-1/4
(31.75)
1.380
(35.052)
1350
(38.22)
957
(27.09)
768
(22.25)
657
(18.60)
583
(16.50)
528
(14.95)
486
(13.76)
452
(12.79)
424
(12.00)
400
(11.33)
1-1/2
(38.1)
1.610
(40.894)
2090
(59.18)
1430
(40.49)
1150
(32.56)
985
(27.89)
873
(24.72)
791
(22.39)
728
(20.61)
677
(19.17)
635
(17.98)
600
(17.00)
2
(50.8)
2.067
(52.502)
4020
(113.83)
2760
(78.15)
2220
(62.86)
1900
(53.80)
1680
(47.57)
1520
(43.04)
1400
(39.64)
1300
(36.81)
1220
(34.55)
1160
(32.844)
2-1/2
(63.5)
2.469
(67.713)
6400 4400
(181.22) (124.59)
3530
(99.95)
3020
(85.51)
2680
(75.88)
2480
(70.22)
2230
(63.14)
2080
(58.89)
1950
(55.22)
1840
(52.10)
3
(76.2)
3.068
(77.927)
11300 7780
(319.98) (220.30) (176.98) (151.49) (134.22) (121.47) (111.85) (103.92)
6250
5350
4740
4290
3950
3670
3450
(97.69)
3260
(92.31)
NOTE - Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.
The unit is equipped with a field make-up box. The make-
up box may be moved to the right side of the furnace to fa-
cilitate installation. Secure the excess wire to the existing
harness to protect it from damage.
Electrical
ELECTROSTATIC DISCHARGE (ESD)
and troubleshooting.
Precautions and Procedures
The power supply wiring must meet Class I restrictions.
Protected by either a fuse or circuit breaker, select circuit
protection and wire size according to unit nameplate.
CAUTION
Electrostatic discharge can affect elec-
tronic components. Take precautions
to neutralize electrostatic charge by
touching your hand and tools to metal
prior to handling the control.
NOTE - Unit nameplate states maximum current draw.
Maximum Over-Current Protection allowed is 15 AMP.
Holes are on both sides of the furnace cabinet to facilitate
wiring.
Install a separate (properly sized) disconnect switch near
the furnace so that power can be turned off for servicing.
INTERIOR MAKE-UP BOX INSTALLATION
Before connecting the thermostat check to make sure the
wires will be long enough for servicing at a later date. Make
sure that thermostat wire is long enough to facilitate future
removal of blower for service.
remove and relocate
plug to unused
opening on left side
MAKE-UP
BOX
Complete the wiring connections to the equipment. Use the
provided unit wiring diagram and the field wiring diagram
able for Class II rating for thermostat connections.
Electrically ground the unit according to local codes or, in
the absence of local codes, according to the current Na-
tional Electric Code (ANSI/NFPA No. 70) for the USA and
current Canadian Electric Code part 1 (CSA standard
C22.1) for Canada. A green ground wire is provided in the
field make-up box.
Right Side
NOTE - The EL296UHE furnace contains electronic
components that are polarity sensitive. Make sure that the
furnace is wired correctly and is properly grounded.
FIGURE 63
Page 40
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessory Terminals
D The furnace integrated control requires both polarity
and proper ground. Both polarity and proper grounding
should be checked before attempting to operate the
furnace on either permanent or temporary power.
D Generator should have a wave form distortion of less
than 5% THD (total harmonic distortion).
One line voltage “ACC” 1/4” spade terminal is provided on
control configuration. This terminal is energized when the
indoor blower is operating. Any accessory rated up to one
amp can be connected to this terminal with the neutral leg
of the circuit being connected to one of the provided neutral
terminals. If an accessory rated at greater than one amp is
connected to this terminal, it is necessary to use an exter-
nal relay.
On-Board Links and Diagnostic Push
WARNING
Carefully review all configuration information pro-
vided. Failure to properly set DIP switches, jumpers
and on-board links can result in improper operation!
An unpowered, normally open (dry) set of contacts with a
1/4” spade terminal “HUM” are provided for humidifier con-
nections and may be connected to 24V or 120V. Any hu-
midifier rated up to one amp can be connected to these ter-
minals. In 120V humidifier applications the neutral leg of
the circuit can be connected to one of the provided neutral
terminals. This terminal is energized in the heating mode.
On-Board Link W914 Dehum
On-board link W914, is a clippable connection between ter-
minals R and DS on the integrated control. W914 must be
cut when the furnace is installed with a thermostat which
features humidity control. If the link is not cut, terminal “DS”
will remain energized not allowing the blower to reduce to
low cool speed upon a call for dehumidification.
Install the room thermostat according to the instructions
designations. If the furnace is being matched with a heat
pump, refer to the FM21 installation instruction or appropri-
ate dual fuel thermostat instructions.
On-Board Link W951 Heat Pump (R to O)
On-board link W951 is a clippable connection between ter-
minals R and O on the integrated control. W951 must be cut
when the furnace is installed in applications which include a
heat pump unit and a thermostat which features dual fuel
use. If the link is left intact, terminal “O” will remain ener-
gized eliminating the HEAT MODE in the heat pump.
Indoor Blower Speeds
1 - When the thermostat is set to “FAN ON,” the indoor
blower will run continuously on the field selectable fan
speed (“LOW HEAT” is default) when there is no cool-
ing or heating demand.
On-Board Link W915 2 Stage Compr (Y1 to Y2)
On-board link W915 is a clippable connection between ter-
minals Y1 and Y2 on the integrated control. W915 must be
cut if two-stage cooling will be used. If the Y1 to Y2 link is
not cut the outdoor unit will operate in second-stage cool-
ing only.
2 - When the EL296UHE is running in the heating mode,
the indoor blower will run on the 'LOW HEAT” or “HIGH
HEAT” speed per demand.
3 - When there is a cooling demand, the indoor blower will
run on the “LOW COOL” or “HIGH COOL” speed per
demand.
Diagnostic Push Button
The diagnostic push button is located adjacent to the
seven-segment diagnostic LED. This button is used to en-
able the Error Code Recall “E” mode and the Flame Signal
“F” mode. Press the button and hold it to cycle through a
menu of options. Every five seconds a new menu item will
be displayed. When the button is released, the displayed
item will be selected. Once all items in the menu have been
displayed, the menu resumes from the beginning until the
button is released.
Generator Use - Voltage Requirements
The following requirements must be kept in mind when
specifying a generator for use with this equipment:
D The furnace requires 120 volts + 10% (Range: 108
volts to 132 volts).
D The furnace operates at 60 Hz + 5% (Range: 57 Hz to
63 Hz).
Page 41
Download from Www.Somanuals.com. All Manuals Search And Download.
Integrated Control
HUM
ACC
24VAC Indoor
Blower Terminals
Ignitor and Combustion
Air Inducer
Neutrals
Flame Sense
LED
S4 DIP Switches
Diagnostic Push
Button
On Board Links
THERMOSTAT CONNECTIONS (TB1)
DS = DEHUMIDIFICATION SIGNAL
3/16” QUICK CONNECT TERMINALS
FLAME SENSE SIGNAL
HI COOL 24VAC
W2 = HEAT DEMAND FROM 2ND STAGE T/STAT
W1 = HEAT DEMAND FROM 1ST STAGE T/STAT
R = CLASS 2 VOLTAGE TO THERMOSTAT
G = MANUAL FAN FROM T'STAT
HI HEAT 24VAC
LO COOL 24VAC
LO HEAT 24VAC
C = THERMOSTAT SIGNAL GROUND CONNECTED TO
TRANSFORMER GRD (TR) & CHASIS GROUND (GRD)
PARK
PARK
COMMON 24VAC
Y1 = THERMOSTAT 1ST STAGE COOL SIGNAL
Y2 = THERMOSTAT 2ND STAGE COOL SIGNAL
1/4” QUICK CONNECT TERMINALS
O = THERMOSTAT SIGNAL TO HEAT PUMP
REVERSING VALVE
NEUTRALS = 120 VAC NEUTRAL
HUM = UNPOWERED NORMALLY OPEN (DRY) CONTACTS
LI = 120 VAC INPUT TO CONTROL
ACC = 120 VAC OUTPUT TO OPTIONAL ACCESSORY
DH = NOT USED
L = NOT USED
FIGURE 65
. . . . . . . . . . . . .
Page 43
Download from Www.Somanuals.com. All Manuals Search And Download.
is shipped from the factory with a blower-off delay of 90 se-
conds. The blower off delay affects comfort and is adjust-
able to satisfy individual applications. Adjust the blower off
delay to achieve a supply air temperature between 90° and
110°F at the exact moment that the blower is de-energized.
Longer off delay settings provide lower supply air tempera-
tures; shorter settings provide higher supply air temperatu-
from different switch settings.
Integrated Control DIP Switch Settings
EL296UHE units are equipped with a two-stage integrated
control. This control manages ignition timing, heating
mode fan off delays and indoor blower speeds based on
selections made using the control dip switches and jump-
ers. The control includes an internal watchguard feature
which automatically resets the ignition control when it has
been locked out. After one hour of continuous thermostat
demand for heat, the watchguard will break and remake
thermostat demand to the furnace and automatically reset
the control to relight the furnace.
TABLE 11
Blower Off Heating Mode Delay Switch Settings
Blower Off Delay
(Seconds)
Heating Operation DIP Switch Settings
Switch 3
Switch 4
Switch 1 -- Thermostat Selection -- This unit may be
used with either a single-stage or two-stage thermostat.
The thermostat selection is made using a DIP switch which
must be properly positioned for the particular application.
The DIP switch is factory-positioned for use with a two-
stage thermostat. If a single-stage thermostat is to be used,
the DIP switch must be repositioned.
60
90 (Factory)
120
On
Off
Off
On
Off
Off
On
On
180
Switch 5 -- Cooling Mode Blower-Off Delay-- The unit is
shipped from the factory with the dip switch positionedOFF
off delay settings.
a- Select “OFF” for two-stage heating operation con-
trolled by a two-stage heating thermostat (factory set-
ting);
TABLE 12
Blower Off Cooling Mode Delay Switch Settings
b - Select “ON” for two-stage heating operation con-
trolled by a single-stage heating thermostat. This set-
ting provides a timed delay before second-stage heat
is initiated.
Blower Off Delay
(Seconds)
Switch 5
45 (Factory)
2
Off
On
Switch 2 -- Second Stage Delay (Used with Single-
Stage Thermostat Only) -- This switch is used to deter-
mine the second stage on delay when a single-stage ther-
mostat is being used. The switch is factory-set in the OFF
position, which provides a 7-minute delay before second-
stage heat is initiated. If the switch is toggled to the ON
position, it will provide a 12-minute delay before second-
stage heat is initiated. This switch is only activated when
the thermostat selector jumper is positioned for SINGLE-
stage thermostat use.
Switches 6 and 7 -- Continuous Fan Mode -- Continuous
fan speed can be controlled by changing DIP switch posi-
tinuous fan mode.
TABLE 13
Continuous Fan Mode Settings
Continuous Fan
Mode
Switch 6
Switch 7
Indoor Blower Operation DIP Switch Settings
Low Heat Speed
(factory)
Off
Off
Switches 3 and 4 -- Heating Mode Blower-Off Delay --
The blower-on delay of 30 seconds is not adjustable. The
blower-off delay (time that the blower operates after the
heating demand has been satisfied) can be adjusted by
moving switches 3 and 4 on the integrated control. The unit
Low Cool Speed
High High Speed
High Cool Speed
Off
On
On
On
Off
On
Page 44
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 14
EL296 Field Wiring Applications With Conventional Thermostat
DIP Switch 1
On Board Links Must Be Cut To Select
System Options
Thermostat
Heating
Stages
Thermostat
Wiring Connections
1 Heat / 1 Cool
ON
ON
ON
S1
T'STAT
FURNACE
TERM. STRIP
OUTDOOR
UNIT
NOTE - Use DIP
switch 2 to set
second-stage
heat ON delay.
OFF-7 minutes.
ON-12 minutes.
DO NOT CUT ANY
ON-BOARD LINKS
*
*Not required on all units
1 Heat / 2 Cool
S1
T'STAT
FURNACE
TERM. STRIP
OUTDOOR
UNIT
NOTE - Use DIP
switch 2 to set
second-stage
heat ON delay.
OFF-7 minutes.
ON-12 minutes.
CUT ON-BOARD LINK
W915
2 STAGE
*
DEHUM
COMPR
*Not required on all units
1 Heat / 2 Cool
with t'stat with
humidity control
S1
T'STAT
FURNACE
TERM. STRIP
OUTDOOR
UNIT
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
NOTE - Use DIP
switch 2 to set
second-stage
*
heat ON delay.
OFF-7 minutes.
ON-12 minutes.
CUT ON-BOARD LINK
W914
DEHUM
DEHUM
o
*Not required on all units
Page 45
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 14
EL296 Field Wiring Applications With Conventional Thermostat (Continued)
DIP Switch 1
On Board Links Must Be Cut To Select
System Options
Thermostat
Heating
Stages
Thermostat
Wiring Connections
2 Heat / 2 Cool
OFF
OFF
OFF
OFF
S1
T'STAT
FURNACE
TERM. STRIP
OUTDOOR
UNIT
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
*
DEHUM
*Not required on all units
2 Heat / 2 Cool
with t'stat with
humidity control
S1
T'STAT
FURNACE
TERM. STRIP UNIT
OUTDOOR
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
*
CUT ON-BOARD LINK
W914
DEHUM
*Not required on all units
o
2 Heat / 1 Cool
with t'stat with
humidity control
S1
T'STAT
FURNACE
TERM. STRIP
OUTDOOR
UNIT
CUT ON-BOARD LINK
W914
DEHUM
*
o
*Not required on all units
2 Heat / 1 Cool
S1
T'STAT
FURNACE
TERM. STRIP
OUTDOOR
UNIT
DO NOT CUT ANY
ON-BOARD LINKS
*
DEHUM
*Not required on all units
Page 46
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 14
EL296 Field Wiring Applications With Conventional Thermostat (Continued)
DIP Switch 1
Wiring Connections
Thermostat
Heating
Stages
On Board Links Must Be Cut To Select
System Options
Thermostat
FURNACE
TERM. STRIP
HEAT PUMP
Dual Fuel
Single Stage
Heat Pump
L7724U
T'STAT
OFF
H
CUT ON-BOARD LINK
W951
HEAT
PUMP
ComfortSense
7000 L7724U
thermostat w/
dual fuel capa-
bilities
67M41*
DEHUM
L
Y
L
Capable of 2
stage gas heat
control
Y2
D
B
Y2
L7724U
T'STAT
FURNACE
TERM. STRIP
Dual Fuel
Two Stage
Heat Pump
HEAT PUMP
OFF
CUT ON-BOARD LINK
W915
2 STAGE
H
COMPR
67M41*
ComfortSense
7000 L7724U
thermostat w/
dual fuel capa-
bilities
Capable of 2
stage gas heat
control
CUT ON-BOARD LINK
W951
L
DEHUM
L
HEAT
PUMP
Y2
Y2
D
B
out blue
* Connect W1 to W1 ONLY if using defrost tempering kit 67M41
NOTE - Do NOT make a wire connection between the room thermostat L terminal and the L terminal of the EL296
integrated control.
Page 47
Download from Www.Somanuals.com. All Manuals Search And Download.
EL296 Field Wiring Applications With Conventional Thermostat (Continued)
DIP Switch 1
Wiring Connections
Thermostat
Heating
Stages
On Board Links Must Be Cut To Select
System Options
Thermostat
FURNACE
TERM. STRIP
HEAT PUMP
Dual Fuel
Single Stage
Heat Pump
L7742U
T'STAT
OFF
H
CUT ON-BOARD LINK
W951
HEAT
PUMP
ComfortSense
7000 L7742U
thermostat w/
dual fuel capa-
bilities
Capable of 2
stage gas heat
control w/dehu-
midification
control
67M41*
L
Y
L
CUT ON-BOARD LINK
W914
DEHUM
Y2
D
B
Y2
FURNACE
TERM. STRIP
HEAT PUMP
Dual Fuel
Two Stage
Heat Pump
L7742U
T'STAT
CUT ON-BOARD LINK
W915
2 STAGE
OFF
COMPR
H
ComfortSense
7000 L7742U
thermostat w/
dual fuel capa-
bilities
Capable of 2
stage gas heat
control w/dehu-
midification
67M41*
CUT ON-BOARD LINK
W951
HEAT
PUMP
L
L
CUT ON-BOARD LINK
W914
DEHUM
Y2
Y2
D
B
Y2
out blue
* Connect W1 to W1 ONLY if using defrost tempering kit 67M41
NOTE - Do NOT make a wire connection between the room thermostat L terminal and the L terminal of the EL296
integrated control.
Page 48
Download from Www.Somanuals.com. All Manuals Search And Download.
5 - Wait for the combustion air inducer to stop. Set the
thermostat to initiate a heating demand and again al-
low the burners to fire for approximately 3 minutes.
Unit Start-Up
FOR YOUR SAFETY READ BEFORE OPERATING
6 - Adjust the thermostat to deactivate the heating de-
mand and wait for the combustion air inducer to stop.
At this point, the trap should be primed with sufficient
water to ensure proper condensate drain operation.
WARNING
Do not use this furnace if any part has been under-
water. A flood-damaged furnace is extremely dan-
gerous. Attempts to use the furnace can result in
fire or explosion. Immediately call a qualified ser-
vice technician to inspect the furnace and to replace
all gas controls, control system parts, and electrical
parts that have been wet or to replace the furnace,
if deemed necessary.
WARNING
If you do not follow these instructions exactly, a fire
or explosion may result causing property damage,
personal injury or death.
1 - STOP! Read the safety information at the beginning of
this section.
WARNING
2 - Set the thermostat to the lowest setting.
3 - Turn off all electrical power to the unit.
Danger of explosion. Can cause injury
or product or property damage. Should
the gas supply fail to shut off or if
overheating occurs, shut off the gas
valve to the furnace before shutting off
the electrical supply.
4 - This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the
burners by hand.
5 - Remove the access panel.
7 - Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's instruc-
tions. If you do not smell gas go to next step.
CAUTION
Before attempting to perform any service or mainte-
nance, turn the electrical power to unit OFF at dis-
connect switch.
HIGH FIRE ADJUSTMENT
SCREW
(under cap)
BEFORE LIGHTING the unit, smell all around the fur-
nace area for gas. Be sure to smell next to the floor be-
cause some gas is heavier than air and will settle on the
floor.
MANIFOLD
PRESSURE POST
INLET PRESSURE POST
The gas valve on the EL296UHE is equipped with a gas
control switch (lever). Use only your hand to move
switch. Never use tools. If the the switch will not move by
hand, do not try to repair it. Force or attempted repair may
result in a fire or explosion.
Placing the furnace into operation:
EL296UHE units are equipped with an automatic hot sur-
face ignition system. Do not attempt to manually light
burners on this furnace. Each time the thermostat calls
for heat, the burners will automatically light. The ignitor
does not get hot when there is no call for heat on these
units.
GAS VALVE SHOWN IN ON POSITION
FIGURE 66
9 - Replace the access panel.
10- Turn on all electrical power to to the unit.
11- Set the thermostat to desired setting.
Priming Condensate Trap
NOTE - When unit is initially started, steps 1 through 11
The condensate trap should be primed with water prior to
start-up to ensure proper condensate drainage. Either
pour 10 fl. oz. (300 ml) of water into the trap, or follow
these steps to prime the trap:
may need to be repeated to purge air from gas line.
12- If the appliance will not operate, follow the instructions
“Turning Off Gas to Unit” and call your service techni-
cian or gas supplier.
1 - Follow the lighting instructions to place the unit into op-
eration.
Turning Off Gas to Unit
2 - Set the thermostat to initiate a heating demand.
1 - Set the thermostat to the lowest setting.
3 - Allow the burners to fire for approximately 3 minutes.
2 - Turn off all electrical power to the unit if service is to be
performed.
4 - Adjust the thermostat to deactivate the heating de-
mand.
3 - Remove the access panel.
Page 49
Download from Www.Somanuals.com. All Manuals Search And Download.
4 - Move gas valve switch to OFF.
Furnace should operate at least 5 minutes before check-
ing gas flow. Determine time in seconds for two revolu-
tions of gas through the meter. (Two revolutions assures a
more accurate time.) Divide by two and compare to time
is incorrect, check gas orifices for proper size and re-
striction. Remove temporary gas meter if installed.
5 - Replace the access panel.
Failure To Operate
If the unit fails to operate, check the following:
1 - Is the thermostat calling for heat?
2 - Are access panels securely in place?
3 - Is the main disconnect switch closed?
4 - Is there a blown fuse or tripped breaker?
5 - Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off.
6 - Is gas turned on at the meter?
NOTE - To obtain accurate reading, shut off all other gas
appliances connected to meter.
Supply Pressure Measurement
7 - Is the manual main shut‐off valve open?
8 - Is the internal manual shut‐off valve open?
9 - Is the unit ignition system in lockout? If the unit locks out
again, inspect the unit for blockages.
An inlet post located on the gas valve provides access to
screw one turn, connect a piece of 5/16 tubing and connect
for supply line pressure.
Heating Sequence Of Operation
1 - When thermostat calls for heat, combustion air inducer
starts.
On multiple unit installations, each unit should be checked
separately, with and without units operating. Supply pres-
2 - Combustion air pressure switch proves blower opera-
tion. Switch is factory set and requires no adjustment.
3 - After a 15-second prepurge, the hot surface ignitor en-
ergizes.
Manifold Pressure Measurement
NOTE - Pressure test adapter kit (10L34) is available from
Lennox to facilitate manifold pressure measurement.
4 - After a 20-second ignitor warm-up period, the gas
valve solenoid opens. A 4-second trial for ignition peri-
od begins.”
A manifold pressure post located on the gas valve provides
the 3/32 hex screw one turn, connect a piece of 5/16 tubing
and connect to a manometer to measure manifold pres-
sure.
5 - Gas is ignited, flame sensor proves the flame, and the
combustion process continues.
6 - If flame is not detected after first ignition trial, the igni-
tion control will repeat steps 3 and 4 four more times
before locking out the gas valve (“WATCHGUARD”
flame failure mode). The ignition control will then auto-
matically repeat steps 1 through 6 after 60 minutes.
To interrupt the 60-minute “WATCHGUARD” period,
move thermostat from “Heat” to “OFF” then back to
“Heat”. Heating sequence then restarts at step 1.
To correctly measure manifold pressure, the differential
pressure between the positive gas manifold and the nega-
tive burner box must be considered.
1 - Connect the test gauge positive side “+“ to manifold
pressure tap on gas valve as noted above.
2 - Tee into the gas valve regulator vent hose and connect
to test gauge negative “-”.
Gas Pressure Adjustment
Gas Flow (Approximate)
3 - Ignite unit on low fire and let run for 5 minutes to allow
for steady state conditions.
TABLE 15
GAS METER CLOCKING CHART
Seconds for One Revolution
4 - After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in table
Natural
LP
EL296
Unit
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
DIAL
location of high fire and low fire adjustment screws.
-045
-070
-090
-110
-135
80
160
110
82
200
136
102
82
400
272
204
164
136
6 - Repeat steps 3, 4 and 5 on high fire. See values in
55
41
33
66
NOTE - Shut unit off and remove manometer as soon as an
accurate reading has been obtained. Re-start unit and
check gas valve for gas leaks.
27
54
68
Natural-1000 btu/cu ft
LP-2500 btu/cu ft
Page 50
Download from Www.Somanuals.com. All Manuals Search And Download.
Proper Combustion
High Altitude Information
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas flow rate before checking com-
bustion. Take combustion sample beyond the flue outlet
and compare to the tables below.
NOTE - In Canada, certification for installations at eleva-
tions over 4500 feet (1372 m) is the jurisdiction of local au-
thorities.
Units may be installed at altitudes up to 10,000 ft. above
sea level without manifold adjustment. Units installed at al-
titude of 4501 - 10,000 feet (1373 to 3048m) may require a
pressure switch change which can be ordered separately.
ments at varying altitudes.
TABLE 16
CO %
2
CO %
For L.P
For Nat
2
EL296
Model
Low Fire High Fire Low Fire High Fire
5.4 - 6.4 7.5 - 8.5 6.4 - 7.4 8.8 - 9.8
5.3 - 6.3 7.4 - 8.4 6.3 - 7.3 8.7 - 9.7
5.8 - 6.8 7.6 - 8.6 6.8 - 7.8 8.9 - 9.9
6.1 - 7.1 8.0 - 9.0 7.1 - 8.1 9.3 - 10.3
6.1 - 7.1 7.8 - 8.8 7.1 - 8.2 9.1 - 10.1
045
070
090
110
135
The combustion air pressure switch is factory-set and re-
quires no adjustment.
The maximum carbon monoxide reading should not exceed 50 ppm.
TABLE 17
Manifold and Supply Line Pressure 0-10,000ft.
Manifold Pressure in.wg.
Supply Line Pressure in. w.g.
EL296
Unit
Gas
Low Fire
1.7
High Fire
3.5
Min
4.5
Max
10.5
13.0
Natural
All Sizes
LP/propane
4.9
10.0
11.0
NOTE -
A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion
procedure.
TABLE 18
LP/Propane Conversion Kit and Pressure Switch Requirements at Varying Altitudes
High Altitude
Natural Burner
Orifice Kit
High Altitude
LP/Propane Burner
Orifice Kit
Natural to
LP/Propane
High Altitude Pressure Switch
EL296
Unit
0 - 7500 ft
(0 - 2286m)
7501 - 10,000 ft
(2286 - 3038m)
7501 - 10,000 ft
(2286 - 3038m)
4501 - 7500 ft
(1373 - 2286m)
7501 -10,000 ft
(2286 - 3048m)
-045
-070
-090
-110
-135
93W81
93W80
93W82
93W80
93W83
93W84
93W85
93W80
93W85
93W85
*78W93
73W37
*78W96
* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit.
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-1370 m).
Page 51
Download from Www.Somanuals.com. All Manuals Search And Download.
Testing for Proper Venting and Sufficient Combustion Air for Non-Direct Vent Applications
horizontal pitch. Determine there is no blockage or re-
striction, leakage, corrosion, or other deficiencies
which could cause an unsafe condition.
WARNING
CARBON MONOXIDE POISONING HAZARD!
3 - To the extent that it is practical, close all building doors
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monox-
ide poisoning or death.
and windows and all doors between the space in which
the appliances connected to the venting system are lo-
cated and other spaces of the building.
4 - Close fireplace dampers.
The following steps shall be followed for each ap-
pliance connected to the venting system being
placed into operation, while all other appliances con-
nected to the venting system are not in operation.
5 - Turn on clothes dryers and any appliances not con-
nected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they will operate at maximum speed. Do not operate a
summer exhaust fan.
After the EL296UHE gas furnace has been started, the fol-
lowing test should be conducted to ensure proper venting
and sufficient combustion air has been provided to the
EL296UHE as well as to other gas‐fired appliances which
are separately vented.
6 - Follow the lighting instruction to place the appliance
being inspected into operation. Adjust thermostat so
appliance will operate continuously.
7 - Use the flame of match or candle to test for spillage of
flue gases at the draft hood relief opening after 5 min-
utes of main burner operation.
If a EL296UHE furnace replaces a Category I furnace
which was commonly vented with another gas appliance,
the size of the existing vent pipe for that gas appliance must
be checked. Without the heat of the original furnace flue
products, the existing vent pipe is probably oversized for
the single water heater or other appliance. The vent should
be checked for proper draw with the remaining appliance.
8 - If improper venting is observed during any of the
above tests, the venting system must be corrected or
sufficient combustion/make‐up air must be provided.
The venting system should be re‐sized to approach
the minimum size as determined by using the ap-
propriate tables in appendix G in the current standards
of the National Fuel Gas Code ANSI-Z223.1/NPFA 54
in the U.S.A., and the appropriate Natural Gas and
Propane appliances venting sizing tables in the cur-
rent standard of the CSA-B149 Natural Gas and Pro-
pane Installation Codes in Canada.
The test should be conducted while all appliances (both in
operation and those not in operation) are connected to the
venting system being tested. If the venting system has
been installed improperly, or if provisions have not been
made for sufficient amounts of combustion air, corrections
must be made as outlined in the previous section.
9 - After determining that each appliance remaining
connected to the common venting system properly
vents when tested as indicated in step 3, return
doors, windows, exhaust fans, fireplace dampers
and any other gas‐burning appliance to their previous
condition of use.
1 - Seal any unused openings in the venting system.
2 - Visually inspect the venting system for proper size and
Page 52
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTE - The ignition control thermostat selection DIP switch is
factory-set in the “TWO-STAGE” position.
Other Unit Adjustments
Applications Using a Two-Stage Thermostat
A - Heating Sequence -- Integrated Control Thermostat
Selection DIP Switch 1 OFF in “Two-Stage” Position
(Factory Setting)
Primary Limit.
The primary limit is located on the heating compartment
vestibule panel. This limit is factory set and requires no ad-
justment.
1 - On a call for heat, thermostat first-stage contacts close
sending a signal to the integrated control. The inte-
grated control runs a self‐diagnostic program and
checks high temperature limit switches for normally
closed contacts and pressure switches for normally
open contacts. The combustion air inducer is ener-
gized at low speed.
Flame Rollout Switches (Two)
These manually reset switches are located on the front of
the burner box.
Pressure Switch
2 - Once the control receives a signal that the low pres-
sure switch has closed, the combustion air inducer be-
gins a 15-second pre-purge in low speed.
The pressure switch is located in the heating compartment
on the cold end header box. This switch checks for proper
combustion air inducer operation before allowing ignition
trial. The switch is factory-set and must not be adjusted.
NOTE - If the low fire pressure switch does not close
the combustion air inducer will switch to high fire. After
a 15 second pre-purge the high fire pressure switch
will close and the unit will begin operation on high fire.
After 10 to 20 seconds of high fire operation the unit
will switch to low fire..
Temperature Rise
Place the unit into operation with a second-stage heating
demand. After supply and return air temperatures have
stabilized, check the temperature rise. If necessary, adjust
the heating blower speed to maintain the temperature rise
within the range shown on the unit nameplate. Increase the
blower speed to decrease the temperature rise. Decrease
the blower speed to increase the temperature rise. Failure
to properly adjust the temperature rise may cause erratic
limit operation.
3 - After the pre-purge is complete, a 20-second initial ig-
nitor warm-up period begins. The combustion air in-
ducer continues to operate at low speed.
4 - After the 20-second warm-up period has ended, the gas
valve is energized on low fire (first stage) and ignition oc-
curs. At the same time, the control module sends a sig-
nal to begin an indoor blower 30-second ON-delay.
When the delay ends, the indoor blower motor is ener-
gized on the low fire heating speed, the HUM contacts
close energizing the humidifier and 120V ACC termi-
nal is energized. The furnace will continue this opera-
tion as long as the thermostat has a first-stage heating
demand.
Electrical
1 - Check all wiring for loose connections.
2 - Check for the correct voltage at the furnace (furnace
operating). Correct voltage is 120VAC + 10%
3 - Check amp-draw on the blower motor with blower ac-
cess panel in place.
Unit Nameplate__________Actual__________
5 - If second-stage heat is required, the thermostat sec-
ond-stage heat contacts close and send a signal to the
integrated control. The integrated control initiates a
30-second second-stage recognition delay.
Exhaust and Air Intake Pipe
1 - Check exhaust and air intake connections for tightness
and to make sure there is no blockage.
6 - At the end of the recognition delay, the integrated con-
trol energizes the combustion air inducer at high
speed. The control also checks the high fire (second
stage) pressure switch to make sure it is closed. The
high fire (second stage) gas valve is energized and the
indoor blower motor is energized for operation at the
high fire heating speed.
2 - Is pressure switch closed? Obstructed exhaust pipe
will cause unit to shut off at pressure switch. Check ter-
mination for blockages.
3 - Obstructed pipe or termination may cause rollout
switches to open. Reset manual flame rollout switches
on burner box assembly if necessary.
7 - When the demand for high fire (second stage) heat is
satisfied, the combustion air inducer is switched to the
low-fire heating speed and the high-fire (second
stage) gas valve is de-energized. The low-fire (first
stage) gas valve continues operation. The indoor
blower motor is switched to the low-fire heating speed.
8 - When the thermostat demand for low-fire (first stage)
heat is satisfied, the gas valve is de-energized and the
field-selected indoor blower off delay begins. The
combustion air inducer begins a 5-second post-purge
period.
Heating Sequence of Operation
Electronic Ignition
The two-stage, variable speed integrated control used in
EL296UHE units has an added feature of an internal Watch-
guard control. The feature serves as an automatic reset de-
vice for ignition control lockout caused by ignition failure. Af-
ter one hour of continuous thermostat demand for heat, the
Watchguard will break and remake thermostat demand to
the furnace and automatically reset the control to begin the
ignition sequence.
9 - When the combustion air post-purge period is com-
plete, the inducer, the HUM contacts as well as the
120V ACC terminals are de-energized. The indoor
blower is de-energized at the end of the off delay.
Page 53
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Using A Single-Stage Thermostat
B - Heating Sequence -- Integrated Control Thermostat
Selection DIP Switch 1 ON in “Single-Stage” Position
Repair Parts List
The following repair parts are available through Lennox
dealers. When ordering parts, include the complete fur-
nace model number listed on the CSA nameplate -- Exam-
ple: EL296UH045XE24B-01. All service must be per-
formed by a licensed professional installer (or
equivalent), service agency, or gas supplier.
NOTE - In these applications, two-stage heat will be initi-
ated by the integrated control if heating demand has not
been satisfied after the field adjustable period (7 or 12 min-
utes).
1 - On a call for heat, thermostat first-stage contacts close
sending a signal to the integrated control. The inte-
grated control runs a self‐diagnostic program and
checks high temperature limit switches for normally
closed contacts and pressure switches for normally
open contacts. The combustion air inducer is ener-
gized at low speed.
Cabinet Parts
Outer access panel
Blower access panel
Top Cap
2 - Once the control receives a signal that the low pres-
sure switch has closed, the combustion air inducer be-
gins a 15-second pre-purge in low speed.
Control Panel Parts
Transformer
Integrated control board
Door interlock switch
NOTE - If the low fire pressure switch does not close
the combustion air inducer will switch to high fire. After
a 15 second pre-purge the high fire pressure switch
will close and the unit will begin operation on high fire.
After 10 to 20 seconds of high fire operation the unit
will switch to low fire.
Blower Parts
Blower wheel
Motor
Motor mounting frame
Motor capacitor
Blower housing cutoff plate
3 - After the pre-purge is complete, a 20-second initial ig-
nitor warm-up period begins. The combustion air in-
ducer continues to operate at low speed.
Heating Parts
4 - After the 20-second warm-up period has ended, the gas
valve is energized on low fire (first stage) and ignition oc-
curs. At the same time, the control module sends a sig-
nal to begin an indoor blower 30-second ON-delay.
When the delay ends, the indoor blower motor is ener-
gized on the low fire heating speed and the HUM con-
tacts are energized. The integrated control also initi-
ates a second-stage on delay (factory-set at 7
minutes; adjustable to 12 minutes).
5 - If the heating demand continues beyond the second-
stage on delay, the integrated control energizes the
combustion air inducer at high speed. The control also
checks the high fire (second stage) pressure switch to
make sure it is closed. The high fire (second stage)
gas valve is energized and the indoor blower motor is
energized for operation at the high fire heating speed.
6 - When the thermostat heating demand is satisfied, the
combustion air inducer begins a 5-second low speed
post-purge. The field-selected indoor blower off delay
begins. The indoor blower operates at the low-fire
heating speed.
Flame Sensor
Heat exchanger assembly
Gas manifold
Combustion air inducer
Gas valve
Main burner cluster
Main burner orifices
Pressure switch
Ignitor
Primary limit control
Flame rollout switches
7 - When the combustion air post-purge period is com-
plete, the inducer, the HUM contacts as well as the
120V ACC terminals are de-energized. The indoor
blower is de-energized at the end of the off delay.
Page 54
Download from Www.Somanuals.com. All Manuals Search And Download.
2 - Check for the correct voltage at the furnace (furnace
operating).
Service
3 - Check amp-draw on the blower motor.
Motor Nameplate__________Actual__________
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Winterizing and Condensate Trap Care
1 - Turn off power to the furnace.
2 - Have a shallow pan ready to empty condensate water.
Failure to follow safety warnings exactly could result
in dangerous operation, serious injury, death or
property damage.
Improper servicing could result in dangerous opera-
tion, serious injury, death, or property damage.
Before servicing, disconnect all electrical power to
furnace.
3 - Remove the clean out cap from the condensate trap
and empty water. Inspect the trap then reinstall the
clean out cap.
Cleaning The Burner Assembly
If cleaning the burner assembly becomes necessary, fol-
low the steps below:
When servicing controls, label all wires prior to dis-
connecting. Take care to reconnect wires correctly.
Verify proper operation after servicing.
1 - Turn off electrical and gas power supplies to furnace.
Remove upper and lower furnace access panels.
2 - Disconnect the wires from the gas valve.
3 - Remove the burner box cover (if equipped).
4 - Disconnect the gas supply line from the gas valve. Re-
move gas valve/manifold assembly.
At the beginning of each heating season, system should be
checked as follows by a qualified service technician:
Blower
5 - Mark and disconnect sensor wire from the sensor. Dis-
connect wires from flame rollout switches.
Check the blower wheel for debris and clean if necessary.
The blower motors are prelubricated for extended bearing
life. No further lubrication is needed.
6 - Disconnect combustion air intake pipe. It may be nec-
essary to cut the existing pipe to remove burner box
assembly.
7 - Remove four screws which secure burner box assem-
bly to vest panel. Remove burner box from the unit.
WARNING
8 - Use the soft brush attachment on a vacuum cleaner to
gently clean the face of the burners. Visually inspect
the inside of the burners and crossovers for any block-
age caused by foreign matter. Remove any blockage.
9 - Reinstall the burner box assembly using the existing
four screws. Make sure that the burners line up in the
center of the burner ports.
The blower access panel must be securely in place
when the blower and burners are operating. Gas
fumes, which could contain carbon monoxide, can
be drawn into living space resulting in personal inju-
ry or death.
Filters
10 - Reconnect the sensor wire and reconnect the 2-pin
plug to the ignitor wiring harness. Reconnect wires to
flame rollout switches.
All air filters are installed external to the unit. Filters should
be inspected monthly. Clean or replace the filters when
lists recommended filter sizes.
11 - Reinstall the gas valve manifold assembly. Reconnect
the gas supply line to the gas valve. Reinstall the burn-
er box cover.
Exhaust and air intake pipes
Check the exhaust and air intake pipes and all connections
for tightness and to make sure there is no blockage.
12 - Reconnect wires to gas valve.
13 - Replace the blower compartment access panel.
14 - Refer to instruction on verifying gas and electrical con-
nections when re-establishing supplies.
NOTE - After any heavy snow, ice or frozen fog event the
furnace vent pipes may become restricted. Always check
the vent system and remove any snow or ice that may be
obstructing the plastic intake or exhaust pipes.
15 - Follow lighting instructions to light and operate fur-
nace for 5 minutes to ensure that heat exchanger is
clean and dry and that furnace is operating properly.
Electrical
1 - Check all wiring for loose connections.
16 - Replace heating compartment access panel.
Page 55
Download from Www.Somanuals.com. All Manuals Search And Download.
Start-Up & Performance Check List
UNIT SET UP
(typical)
Furnace:
Model Number_______________
Serial Number_________________
SUPPLY
AIR
Line Voltage
2
4
1
GAS SUPPLY
Natural Gas
LP Propane Gas
3
Piping Connections Tight
Leak Tested
Flter
RETURN AIR
2
Supply Line Pressure “W.C.________
1
Gas Supply Pressure
1
DUCT SYSTEM
3
SUPPLY AIR DUCT
Sealed
2
INTAKE / EXHAUST PIPE
Insulated (if necessary)
All Joints Primed and Glued
RETURN DUCT
Sealed
Terminations Installed Properly
Horizontal Pipes Sloped (if applicable)
Condensate Trap Primed / Line Sloped
Filter Installed and Clean
Grilles Unobstructed
Pipes Supported
VOLTAGE CHECK
4
Supply Voltage _____
Heat Cable Installed and Operable (if applicable)
Electrical Connections Tight
Page 56
Download from Www.Somanuals.com. All Manuals Search And Download.
UNIT OPERATION
HEATING MODE
COOLING MODE
GAS MANIFOLD PRESSURE “W.C._____
1
2
INDOOR BLOWER AMPS______
3
4
COMBUSTION SAMPLE CO % CO PPM_______
2 ______
TEMPERATURE DROP
Return Duct Temperature _________
_
INDOOR BLOWER AMPS______
TEMPERATURE RISE
3
4
Supply Duct Temperature _______
Temperature Drop = _________
5
TOTAL EXTERNAL STATIC (dry coil)
Supply External Static _______
Supply Duct Temperature ________
_
Return Duct Temperature
_____
Return External Static + ______
Total External Static = _______
Temperature Rise = ________
TOTAL EXTERNAL STATIC
5
8
DRAIN LINE
Leak Free
Supply External Static _______
Return External Static + ______
Total External Static = _______
THERMOSTAT
6
7
9
CONDENSATE LINE
Leak Free
Adjusted and Programmed
Explained Operation to Owner
VENT PIPE
Leak Free
Combustion CO
2
2
7
SUPPLY
AIR
Thermostat
Temperatures
8
Gas Manifold Pressure
9
4
1
Blower Motor Amps
6
3
Duct Static
5
High +
RETURN AIR
Low -
Contractor's: Name_________________________Telephone_____________Checklist Completed____________________
Job Address_____-________________________________Technician's Name___________________________________
Page 57
Download from Www.Somanuals.com. All Manuals Search And Download.
Requirements for Commonwealth of Massachusetts
Modifications to NFPA-54, Chapter 10
4 - INSPECTION. The state or local gas inspector of the
side wall, horizontally vented, gas-fueled equipment
shall not approve the installation unless, upon inspec-
tion, the inspector observes carbon monoxide detec-
tors and signage installed in accordance with the pro-
visions of 248 CMR 5.08(2)(a) 1 through 4.
Revise NFPA-54 section 10.8.3 to add the following re-
quirements:
For all side wall, horizontally vented, gas-fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7)
feet above the finished grade in the area of the venting, in-
cluding but not limited to decks and porches, the following
requirements shall be satisfied:
EXEMPTIONS: The following equipment is exempt
from 24 CMR 5.08(2)(a) 1 through 4:
1 - The equipment listed in Chapter 10 entitled “Equip-
ment Not Required to Be Vented” in the most current
edition of NFPA 54 as adopted by the Board; and
2 - Product Approved side wall, horizontally vented, gas-
fueled equipment installed in a room or structure sepa-
rate from the dwelling, building or structure used in
whole or in part for residential purposes.
1 - INSTALLATION OF CARBON MONOXIDE DETEC-
TORS. At the time of installation of the side wall, hori-
zontally vented, gas-fueled equipment, the installing
plumber or gasfitter shall observe that a hard-wired
carbon monoxide detector with an alarm and battery
backup is installed on the floor level where the gas
equipment is to be installed. In addition, the installing
plumber or gasfitter shall observe that a battery-oper-
ated or hard-wired carbon monoxide detector with an
alarm is installed on each additional level of the dwell-
ing, building or structure served by the side wall, hori-
zontally vented, gas-fueled equipment. It shall be the
responsibility of the property owner to secure the ser-
vices of qualified licensed professionals for the instal-
lation of hard-wired carbon monoxide detectors.
MANUFACTURER REQUIREMENTS -
GAS EQUIPMENT VENTING SYSTEM PROVIDED.
When the manufacturer of Product Approved side wall,
horizontally vented, gas-fueled equipment provides a vent-
ing system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system
shall include:
1 - Detailed instructions for the installation of the venting
system design or the venting system components:
and
a - In the event that the side wall, horizontally vented,
gas-fueled equipment is installed in a crawl space
or an attic, the hard-wired carbon monoxide detec-
tor with alarm and battery back-up may be installed
on the next adjacent floor level.
2 - A complete parts list for the venting system design or
venting system.
MANUFACTURER REQUIREMENTS -
GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
b - In the event that the requirements of this subdivi-
sion cannot be met at the time of completion of
installation, the owner shall have a period of thirty
(30) days to comply with the above requirements;
provided, however, that during said thirty (30) day
period, a battery-operated carbon monoxide detec-
tor with an alarm shall be installed.
When the manufacturer of Product Approved side wall,
horizontally vented, gas-fueled equipment does not pro-
vide the parts for venting the flue gases, but identifies “spe-
cial venting systems,” the following requirements shall be
satisfied by the manufacturer:
2 - APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in accor-
dance with the above provisions shall comply with
NFPA 720 and be ANSI/UL 2034 listed and IAS certi-
fied.
1 - The referenced “special venting system” instructions
shall be included with the appliance or equipment
installation instructions; and
2
The “special venting systems” shall be Product Ap-
proved by the Board, and the instructions for that sys-
tem shall include a parts list and detailed installation
instructions.
3 - SIGNAGE. A metal or plastic identification plate shall
be permanently mounted to the exterior of the building
at a minimum height of eight (8) feet above grade di-
rectly in line with the exhaust vent terminal for the hori-
zontally vented, gas-fueled heating appliance or
equipment. The sign shall read, in print size no less
than one-half (1/2) inch in size, “GAS VENT DIRECT-
LY BELOW. KEEP CLEAR OF ALL OBSTRUC-
TIONS.”
A copy of all installation instructions for all Product
Approved side wall, horizontally vented, gas-fueled
equipment, all venting instructions, all parts lists for
venting instructions, and/or all venting design instruc-
tions shall remain with the appliance or equipment at
the completion of the installation.
Page 58
Download from Www.Somanuals.com. All Manuals Search And Download.
|