Lennox International Inc Furnace EL296UHE User Manual

INSTALLATION  
INSTRUCTIONS  
EL296UHE  
E 2013 Lennox Industries Inc.  
Dallas, Texas, USA  
®
ELITE SERIES GAS FURNACE  
UPFLOW / HORIZONTAL AIR DISCHARGE  
507067-01  
02/2013  
Supersedes 01/2012  
Litho U.S.A.  
THIS MANUAL MUST BE LEFT WITH THE  
HOMEOWNER FOR FUTURE REFERENCE  
This is a safety alert symbol and should never be ignored.  
When you see this symbol on labels or in manuals, be alert  
to the potential for personal injury or death.  
WARNING  
Improper installation, adjustment, alteration, service  
or maintenance can cause property damage, person-  
al injury or loss of life. Installation and service must  
be performed by a licensed professional installer (or  
equivalent), service agency or the gas supplier.  
AIR FLOW  
UPFLOW  
CAUTION  
As with any mechanical equipment, personal injury  
can result from contact with sharp sheet metal  
edges. Be careful when you handle this equipment.  
HORIZONTAL RIGHT  
HORIZONTAL LEFT  
Table of Contents  
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
EL296UHE Gas Furnace . . . . . . . . . . . . . . . . . . . . . . . . . 3  
Shipping and Packing List . . . . . . . . . . . . . . . . . . . . . . . . 3  
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
Use of Furnace as a Construction Heater . . . . . . . . . . . 4  
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Combustion, Dilution, Ventilation Air . . . . . . . . . . . . . . . 5  
Setting Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
Duct System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
Pipe and Fittings Specifications . . . . . . . . . . . . . . . . . . . 13  
Joint Cementing Procedure . . . . . . . . . . . . . . . . . . . . . . . 15  
Venting Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38  
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40  
Integrated Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43  
Unit Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49  
Gas Pressure Measurement . . . . . . . . . . . . . . . . . . . . . . 50  
Proper Combustion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51  
High Altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51  
Other Unit Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . 53  
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 53  
Repair Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54  
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55  
Start-Up and Performance Checklist . . . . . . . . . . . . . . . 56  
02/13  
507067-01  
*2P0213*  
Page 1  
*P507067-01*  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EL296UHE Gas Furnace  
Shipping and Packing List  
Package 1 of 1 contains  
The EL296UHE Category IV gas furnace is shipped ready  
for installation in the upflow or horizontal position. The fur-  
nace is shipped with the bottom panel in place. The bot-  
tom panel must be removed if the unit is to be installed in  
horizontal or upflow applications with bottom return air.  
1 - Assembled EL296UHE unit  
1 - Bag assembly containing the following:  
1 -Snap bushing  
1 -Snap plug  
The EL296UHE can be installed as either a Direct Vent  
or a Non-Direct Vent gas central furnace.  
1 - Wire tie  
1 -Condensate trap  
The furnace is equipped for installation in natural gas ap-  
plications. A conversion kit (ordered separately) is re-  
quired for use in propane/LP gas applications.  
1 -Condensate trap cap  
1 -Condensate trap clamp  
1 -2” diameter debris screen  
1 -3/4” Threaded street elbow  
Check equipment for shipping damage. If you find any  
damage, immediately contact the last carrier.  
NOTE - In Direct Vent installations, combustion air is taken  
from outdoors and flue gases are discharged outdoors. In  
Non-Direct Vent installations, combustion air is taken from  
indoors or ventilated attic or crawlspace and flue gases are  
discharged outdoors. See figures 1 and 2 for applications in-  
volving roof termination.  
The following items may also be ordered separately:  
1 - Thermostat  
1 - LP/Propane changeover kit  
1 - Return air base kit  
DIRECT VENT INSTALLATION  
NON-DIRECT VENT  
INSTALLATION  
EXHAUST OUTLET  
COMBUSTION  
EXHAUST  
OUTLET  
1 - Horizontal suspension kit  
1 - High altitude pressure switch  
AIR INTAKE OUTSIDE  
OF HOUSE  
Safety Information  
CAUTION  
As with any mechanical equipment, personal injury  
can result from contact with sharp sheet metal  
edges. Be careful when you handle this equipment.  
COMBUSTION  
AIR INTAKE  
INSIDE  
OF HOUSE  
DANGER  
Danger of explosion.  
There are circumstances in which odorant used with  
LP/propane gas can lose its scent. In case of a leak,  
LP/propane gas will settle close to the floor and may  
be difficult to smell. An LP/propane leak detector  
should be installed in all LP applications.  
FIGURE 1  
NON-DIRECT VENT  
INSTALLATION  
NON-DIRECT VENT  
INSTALLATION  
EXHAUST  
OUTLET  
EXHAUST  
OUTLET  
Use only the type of gas approved for use with this furnace.  
Refer to unit nameplate.  
EL296UHE units are CSA International certified to ANSI  
Z21.47 and CSA 2.3 standards.  
Building Codes  
In the USA, installation of gas furnaces must conform with lo-  
cal building codes. In the absence of local codes, units must  
be installed according to the current National Fuel Gas Code  
(ANSI‐Z223.1/NFPA 54). The National Fuel Gas Code is  
available from the following address:  
COMBUSTION  
AIR INTAKE INSIDE  
VENTILATED  
COMBUSTION  
AIR INTAKE INSIDE  
VENTILATED  
CRAWL SPACE  
ATTIC SPACE  
American National Standards Institute, Inc.  
11 West 42nd Street  
New York, NY 10036  
In Canada, installation must conform with current National  
Standard of Canada CSA‐B149 Natural Gas and Propane  
Installation Codes, local plumbing or waste water codes  
and other applicable local codes.  
FIGURE 2  
Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
In order to ensure proper unit operation in non-direct vent  
applications, combustion and ventilation air supply must be  
provided according to the current National Fuel Gas Code  
or CSA‐B149 standard.  
Heating Unit Installed Parallel to Air Handler Unit  
Dampers  
(open during heating operation only)  
Installation Locations  
Gas Unit  
This furnace is CSA International certified for installation  
clearances to combustible material as listed on the unit  
nameplate and in the table in figure 12. Accessibility and ser-  
vice clearances must take precedence over fire protection  
clearances.  
AIR FLOW  
AIR FLOW  
Air Handler Unit  
Dampers  
(open during cooling operation only)  
NOTE - For installation on combustible floors, the furnace  
shall not be installed directly on carpeting, tile, or other  
combustible material other than wood flooring.  
Heating Unit Installed Upstream of Cooling Coil  
For installation in a residential garage, the furnace must  
be installed so that the burner(s) and the ignition source  
are located no less than 18 inches (457 mm) above the  
floor. The furnace must be located or protected to avoid  
physical damage by vehicles. When a furnace is installed  
in apublic garage, hangar, or other building that has a haz-  
ardous atmosphere, the furnace must be installed accord-  
ing to recommended good practice requirements and cur-  
rent National Fuel Gas Code or CSA B149 standards.  
AIR FLOW  
AIR FLOW  
Gas Unit  
Cooling Coil  
FIGURE 3  
NOTE - This furnace is designed for a minimum continu-  
ous return air temperature of 60°F (16°C) or an intermit-  
tent operation down to 55°F (13°C) dry bulb for cases  
where a night setback thermostat is used. Return air tem-  
perature must not exceed 85°F (29°C) dry bulb.  
NOTE - Furnace must be adjusted to obtain a temperature  
rise within the range specified on the unit nameplate. Failure  
to do so may cause erratic limit operation and premature heat  
exchanger failure.  
The EL296UHE furnace may be installed in alcoves, clos-  
ets, attics, basements, garages, crawl spaces and utility  
rooms in the upflow or horizontal position.  
This EL296UHE furnace must be installed so that its  
electrical components are protected from water.  
This furnace design has not been CSA certified for installa-  
tion in mobile homes, recreational vehicles, or outdoors.  
Installed in Combination with a Cooling Coil  
Use of Furnace as Construction Heater  
When this furnace is used with cooling coils (figure 3), it shall  
be installed in parallel with, or on the upstream side of, cool-  
ing coils to avoid condensation in the heating compartment.  
With a parallel flow arrangement, a damper (or other means  
to control the flow of air) must adequately prevent chilled air  
from entering the furnace. If the damper is manually oper-  
ated, it must be equipped to prevent operation of either the  
heating or the cooling unit, unless it is in the full HEAT or  
COOL setting.  
Lennox does not recommend the use of EL296UHE units  
as a construction heater during any phase of construction.  
Very low return air temperatures, harmful vapors and op-  
eration of the unit with clogged or misplaced filters will dam-  
age the unit.  
EL296UHE units may be used for heating of buildings or  
structures under construction, if the following conditions  
are met:  
When installed, this furnace must be electrically grounded  
according to local codes. In addition, in the United States,  
installation must conform with the current National Electric  
Code, ANSI/NFPA No. 70. The National Electric Code  
(ANSI/NFPA No. 70) is available from the following ad-  
dress:  
D The vent system must be permanently installed per  
these installation instructions.  
D A room thermostat must control the furnace. The use of  
fixed jumpers that will provide continuous heating is not  
allowed.  
D The return air duct must be provided and sealed to the  
furnace.  
National Fire Protection Association  
1 Battery March Park  
Quincy, MA 02269  
D Return air temperature range between 60°F (16°C) and  
80°F (27°C) must be maintained.  
D Air filters must be installed in the system and must be  
maintained during construction.  
In Canada, all electrical wiring and grounding for the unit  
must be installed according to the current regulations of the  
Canadian Electrical Code Part I (CSA Standard C22.1)  
and/or local codes.  
D Air filters must be replaced upon construction comple-  
tion.  
Page 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
D The input rate and temperature rise must be set per the  
furnace rating plate.  
WARNING  
D One hundred percent (100%) outdoor air must be pro-  
vided for combustion air requirements during construc-  
tion. Temporary ducting may supply outdoor air to the  
furnace. Do not connect duct directly to the furnace.  
Size the temporary duct following these instructions in  
section for Combustion, Dilution and Ventilation Air in a  
confined space with air from outside.  
The State of California has determined that this prod-  
uct may contain or produce a chemical or chemicals,  
in very low doses, which may cause serious illness  
or death. It may also cause cancer, birth defects or  
reproductive harm.  
WARNING  
D The furnace heat exchanger, components, duct system,  
air filters and evaporator coils must be thoroughly  
cleaned following final construction clean-up.  
Insufficient combustion air can cause headaches,  
nausea, dizziness or asphyxiation. It will also cause  
excess water in the heat exchanger resulting in rust-  
ing and premature heat exchanger failure. Excessive  
exposure to contaminated combustion air will result  
in safety and performance related problems. Avoid  
exposure to the following substances in the com-  
bustion air supply:  
D All furnace operating conditions (including ignition, in-  
put rate, temperature rise and venting) must be verified  
according to these installation instructions.  
General  
Permanent wave solutions  
Chlorinated waxes and cleaners  
These instructions are intended as a general guide and do  
not supersede local codes in any way. Consult authorities  
having jurisdiction before installation.  
Chlorine base swimming pool chemicals  
Water softening chemicals  
De-icing salts or chemicals  
Carbon tetrachloride  
Halogen type refrigerants  
Cleaning solvents (such as perchloroethylene)  
Printing inks, paint removers, varnishes, etc.  
Hydrochloric acid  
Cements and glues  
Antistatic fabric softeners for clothes dryers  
Masonry acid washing materials  
In addition to the requirements outlined previously, the fol-  
lowing general recommendations must be considered  
when installing an EL296UHE furnace:  
Place the furnace as close to the center of the air dis-  
tribution system as possible. The furnace should also be  
located close to the vent termination point.  
When the furnace is installed in non-direct vent applica-  
tions, do not install the furnace where drafts might blow  
directly into it. This could cause improper combustion  
and unsafe operation.  
Combustion, Dilution & Ventilation Air  
If the EL296UHE is installed as a Non-Direct Vent Fur-  
nace, follow the guidelines in this section.  
When the furnace is installed in non-direct vent applica-  
tions, do not block the furnace combustion air opening  
with clothing, boxes, doors, etc. Air is needed for proper  
combustion and safe unit operation.  
NOTE - In Non-Direct Vent installations, combustion air  
is taken from indoors or ventilated attic or crawlspace  
and flue gases are discharged out-doors.  
When the furnace is installed in an attic or other insu-  
lated space, keep insulation away from the furnace.  
In the past, there was no problem in bringing in sufficient  
outdoor air for combustion. Infiltration provided all the air  
that was needed. In today's homes, tight construction  
practices make it necessary to bring in air from outside  
for combustion. Take into account that exhaust fans, ap-  
pliance vents, chimneys, and fireplaces force additional  
air that could be used for combustion out of the house.  
Unless outside air is brought into the house for combus-  
tion, negative pressure (outside pressure is greater than  
inside pressure) will build to the point that a downdraft  
can occur in the furnace vent pipe or chimney. As a result,  
combustion gases enter the living space creating a po-  
tentially dangerous situation.  
When the furnace is installed in an unconditioned  
space, consider provisions required to prevent freezing  
of condensate drain system.  
The “A” coil drain pan is high quality engineering poly-  
mer with a maximum service temperature of 500° F.  
However, adequate space must be provided between  
the drain pan and the furnace heat exchanger. At least  
2” space is required for sectionalized heat exchanger  
and and 4” for drum-type or oil-fired furnace exchanger.  
Closer spacing may damage the drain pan and cause  
leaking.  
In the absence of local codes concerning air for combus-  
tion and ventilation, use the guidelines and procedures in  
this section to install EL296UHE furnaces to ensure effi-  
cient and safe operation. You must consider combustion  
air needs and requirements for exhaust vents and gas  
CAUTION  
EL296UHE unit should not be installed in areas nor-  
mally subject to freezing temperatures.  
Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
piping. A portion of this information has been reprinted  
with permission from the National Fuel Gas Code (ANSI-  
Z223.1/NFPA 54). This reprinted material is not the com-  
plete and official position of the ANSI on the referenced  
subject, which is represented only by the standard in its  
entirety.  
Confined Space  
A confined space is an area with a volume less than 50 cubic  
3
feet (1.42 m ) per 1,000 Btu (.29 kW) per hour of the com-  
bined input rating of all appliances installed in that space. This  
definition includes furnace closets or small equipment rooms.  
When the furnace is installed so that supply ducts carry air  
circulated by the furnace to areas outside the space con-  
taining the furnace, the return airmust be handled by ducts  
which are sealed to the furnace casing and which terminate  
outside the space containing the furnace. This is especially  
important when the furnace is mounted on a platform in a  
confined space such as a closet or small equipment room.  
Even a small leak around the base of the unit at the platform  
or at the return air duct connection can cause a potentially  
dangerous negative pressure condition. Air for combustion  
and ventilation can be brought into the confined space ei-  
ther from inside the building or from outside.  
In Canada, refer to the CSA B149 installation codes.  
CAUTION  
Do not install the furnace in a corrosive or contami-  
nated atmosphere. Meet all combustion and ventila-  
tion air requirements, as well as all local codes.  
All gas‐fired appliances require air for the combustion pro-  
cess. If sufficient combustion air is not available, the fur-  
nace or other appliance will operate inefficiently and un-  
safely. Enough air must be provided to meet the needs of all  
fuel-burning appliances and appliances such as exhaust  
fans which force air out of the house. When fireplaces, ex-  
haust fans, or clothes dryers are used at the same time as  
the furnace, much more air is required to ensure proper  
combustion and to prevent a downdraft. Insufficient air  
causes incomplete combustion which can result in carbon  
monoxide.  
Air from Inside  
If the confined space that houses the furnace adjoins a  
space categorized as unconfined, air can be brought in by  
providing two permanent openings between the two  
spaces. Each opening must have a minimum free area of 1  
2
square inch (645 mm ) per 1,000 Btu (.29 kW) per hour of  
total input rating of all gas-fired equipment in the confined  
space. Each opening must be at least 100 square inches  
In addition to providing combustion air, fresh outdoor air di-  
lutes contaminants in the indoor air. These contaminants  
may include bleaches, adhesives, detergents, solvents  
and other contaminants which can corrode furnace compo-  
nents.  
2
(64516 mm ). One opening shall be within 12 inches (305  
mm) of the top of the enclosure and one opening within 12  
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM INSIDE  
The requirements for providing air for combustion and ven-  
tilation depend largely on whether the furnace is installed in  
an unconfined or a confined space.  
ROOF TERMINATED  
EXHAUST PIPE  
Unconfined Space  
An unconfined space is an area such as a basement or  
large equipment room with a volume greater than 50 cubic  
3
feet (1.42 m ) per 1,000 Btu (.29 kW) per hour of the com-  
OPENINGS  
(To Adjacent  
bined input rating of all appliances installed in that space.  
This space also includes adjacent rooms which are not  
separated by a door. Though an area may appear to be un-  
confined, it might be necessary to bring in outdoor air for  
combustion if the structure does not provide enough air by  
infiltration. If the furnace is located in a building of tight  
construction with weather stripping and caulking around  
the windows and doors, follow the procedures in the Air  
from Outside section.  
SIDE WALL  
EL296UH  
Unconfined  
Space)  
TERMINATED  
EXHAUST PIPE  
(ALTERNATE  
LOCATION)  
E
NOTE - Each opening shall have a free area of at least one square inch  
2
per 1,000 Btu (645mm per .29kW) per hour of the total input rating of  
all equipment in the enclosure, but not less than 100 square inches  
2).  
(64516mm.  
FIGURE 4  
Page 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Air from Outside  
EQUIPMENT IN CONFINED SPACE  
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)  
If air from outside is brought in for combustion and ventila-  
tion, the confined space shall be provided with two perma-  
nent openings. One opening shall be within 12” (305mm)  
of the top of the enclosure and one within 12” (305mm) of  
the bottom. These openings must communicate directly  
or by ducts with the outdoors or spaces (crawl or attic) that  
freely communicate with the outdoors or indirectly  
through vertical ducts. Each opening shall have a mini-  
Roof Terminated  
Exhaust Pipe  
2
mum free area of 1 square inch per 4,000 Btu (645mm  
per 1.17kW) per hour of total input rating of all equipment  
in the enclosure (figures 5 and 8). When communicating  
with the outdoors through horizontal ducts, each opening  
shall have a minimum free area of 1 square inch per 2,000  
Inlet Air  
(Minimum  
12 in.(305mm)  
Above crawl  
space floor)  
Ventilation  
Louvers  
(Crawl space)  
Furnace  
2
Btu (645mm per .59kW) per total input rating of all equip-  
ment in the enclosure (See figure 9). It is also permissible  
to bring in air for combustion from a ventilated attic (figure  
6) or ventilated crawl space (figure 7).  
Coupling or  
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE  
(Inlet Air from Crawl Space and Outlet Air to Outside)  
*Intake Debris Screen Provided)  
3 in. to 2 in.  
Transition  
(Field Provided)  
VENTILATION LOUVERS  
(Each end of attic)  
ROOF TERMINATED  
EXHAUST PIPE  
NOTE-The inlet and outlet air openings shall each have a free area  
2
of at least one square inch per 4,000 Btu (645mm per 1.17kW) per  
hour of the total input rating of all equipment in the enclosure.  
FIGURE 7  
OUTLET  
AIR  
When ducts are used, they shall be of the same cross-sec-  
tional area as the free area of the openings to which they  
connect. The minimum dimension of rectangular air ducts  
shall be no less than 3 inches (75 mm). In calculating free  
area, the blocking effect of louvers, grilles, or screens  
must be considered. If the design and free area of protec-  
tive covering is not known for calculating the size opening  
required, it may be assumed that wood louvers will have  
20 to 25 percent free area and metal louvers and grilles  
will have 60 to 75 percent free area. Louvers and grilles  
must be fixed in the open position or interlocked with the  
equipment so that they are opened automatically during  
equipment operation.  
SIDE WALL  
TERMINATED  
EXHAUST PIPE  
(ALTERNATE  
LOCATION)  
FURNACE  
VENTILATION  
LOUVERS  
(For unheated  
crawl space)  
INLET  
AIR  
NOTE-The inlet and outlet air openings shall each have a free area  
2
of at least one square inch per 4,000 Btu (645mm per 1.17kW) per  
hour of the total input rating of all equipment in the enclosure.  
FIGURE 5  
EQUIPMENT IN CONFINED SPACE  
(Inlet Air from Ventilated Attic and Outlet Air to Outside)  
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE  
(All Air Through Ventilated Attic)  
Ventilation Louvers  
Inlet Air  
Roof Terminated  
Exhaust Pipe  
ROOF TERMINATED  
EXHAUST PIPE  
(Minimum  
VENTILATION LOUVERS  
(Each end of attic)  
12 in.(305mm) Above  
attic floor)  
OUTLET  
AIR  
*Intake Debris  
Screen  
(Provided)  
INLET AIR  
(Ends 12” above  
bottom)  
SIDE WALL  
TERMINATED  
EXHAUST PIPE  
(ALTERNATE  
LOCATION)  
FURNACE  
Furnace  
NOTE-The inlet and outlet air openings shall each have a free area  
of at least one square inch per 4,000 Btu (645mm per 1.17kW) per  
hour of the total input rating of all equipment in the enclosure.  
NOTE-The inlet and outlet air openings shall each have a free area of  
2
at least one square inch per 4,000 Btu (645mm per 1.17kW) per hour  
of the total input rating of all equipment in the enclosure.  
2
FIGURE 8  
FIGURE 6  
Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
EQUIPMENT IN CONFINED SPACE -  
ALL AIR FROM OUTSIDE  
Installation - Setting Equipment  
WARNING  
ROOF TERMINATED  
EXHAUST PIPE  
Do not connect the return air duct to the back of the  
furnace. Doing so will adversely affect the operation  
of the safety control devices, which could result in  
personal injury or death.  
OUTLET AIR  
FURNACE  
SIDE WALL  
TERMINATED  
EXHAUST PIPE  
(ALTERNATE  
LOCATION)  
WARNING  
INLET AIR  
Blower access panel must be securely in place when  
blower and burners are operating. Gas fumes, which  
could contain carbon monoxide, can be drawn into  
living space resulting in personal injury or death.  
NOTE-Each air duct opening shall have a free area of at least one  
2
square inch per 2,000 Btu (645mm per .59kW) per hour of the total  
input rating of all equipment in the enclosure. If the equipment room  
is located against an outside wall and the air openings communi-  
cate directly with the outdoors, each opening shall have a free area  
of at least 1 square inch per 4,000 Btu (645mm per 1.17kW) per  
hour of the total input rating of all other equipment in the enclosure.  
Upflow Applications  
The EL296UHE gas furnace can be installed as shipped  
in the upflow position. Refer to figure 12 for clearances.  
Select a location that allows for the required clearances  
that are listed on the unit nameplate. Also consider gas  
supply connections, electrical supply, vent connection,  
condensate trap and drain connections, and installation  
and service clearances [24 inches (610 mm) at unit  
front]. The unit must be level from side to side. The unit  
may be positioned from level to ½” toward the front. See  
figure 11.  
2
FIGURE 9  
Shipping Bolt Removal  
Units with 1/2 hp blower motor are equipped with three flex-  
ible legs and one rigid leg. The rigid leg is equipped with a  
shipping bolt and a flat white plastic washer (rather than the  
rubber mounting grommet used with a flexible mounting  
leg). See figure 10. The bolt and washer must be re-  
moved before the furnace is placed into operation. Af-  
ter the bolt and washer have been removed, the rigid leg  
will not touch the blower housing.  
Allow for clearances to combustible materials as indicated  
on the unit nameplate.  
EL296 Furnaces with  
1/2 HP Blower Motor  
RIGID LEG  
(Remove shipping bolt  
and washer)  
FIGURE 10  
Page 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SETTING EQUIPMENT  
UPFLOW APPLICATION  
UNIT  
FRONT  
UNIT  
FRONT  
AIR FLOW  
AIR FLOW  
1/2”  
max.  
FRONT VIEW  
SIDE VIEW  
SIDE VIEW  
HORIZONTAL APPLICATION  
UNIT  
FRONT  
AIR FLOW  
1/2”  
max.  
END VIEW  
FRONT VIEW  
Unit must be level side-to-side. Unit may be positioned from level to 1/2” toward the front to aid in draining.  
FIGURE 11  
Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Return Air Guidelines  
WARNING  
Return air can be brought in through the bottom or either  
side of the furnace installed in an upflow application. If the  
furnace is installed on a platform with bottom return, make  
an airtight seal between the bottom of the furnace and the  
platform to ensure that the furnace operates properly and  
safely. The furnace is equipped with a removable bottom  
panel to facilitate installation.  
Improper installation of the furnace can result in per-  
sonal injury or death. Combustion and flue products  
must never be allowed to enter the return air system  
or air in the living space. Use sheet metal screws and  
joint tape to seal return air system to furnace.  
In platform installations with furnace return, the fur-  
nace should be sealed airtight to the return air ple-  
num. A door must never be used as a portion of the  
return air duct system. The base must provide a  
stable support and an airtight seal to the furnace. Al-  
low absolutely no sagging, cracks, gaps, etc.  
Markings are provided on both sides of the furnace cabinet  
for installations that require side return air. Cut the furnace  
cabinet at the maximum dimensions shown on page 2.  
For no reason should return and supply air duct sys-  
tems ever be connected to or from other heating de-  
vices such as a fireplace or stove, etc. Fire, explo-  
sion, carbon monoxide poisoning, personal injury  
and/or property damage could result.  
Refer to Product Specifications for additional information.  
EL296UHE applications which include side return air  
and a condensate trap installed on the same side of the  
cabinet (trap can be installed remotely within 5 ft.) re-  
quire either a return air base or field-fabricated transi-  
tion to accommodate an optional IAQ accessory taller  
Installation Clearances  
Top  
Side Return Air  
(with transition and filter)  
Left Side  
Right Side  
20” X 25” X 1”  
(508mmX635mmX25mm)  
Bottom (Floor)  
1−1/2”  
Air Filter  
Top/Plenum  
*Front  
Back  
1 in. (25 mm)  
0
0
Sides  
0†  
0
Return  
Air  
Vent  
Plenum  
Floor  
0‡  
*Front clearance in alcove installation must be 24 in. (610 mm).  
Maintain a minimum of 24 in. (610 mm) for front service access.  
Allow proper clearances to accommodate condensate trap.  
For installations on a combustible floor, do not install the furnace  
directly on carpeting, tile or other combustible materials other  
than wood flooring.  
Transition  
FIGURE 13  
FIGURE 12  
Page 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Optional Return Air Base  
(Upflow Applications Only)  
FURNACE  
FRONT  
1 23 (584)  
Overall  
IF BASE  
IS USED  
3−1/4  
(83)  
1 Minimum  
11 (279)  
Maximum  
WITHOUT  
IAQ CABINET,  
A SINGLE  
RETURN AIR  
PLENUM  
(Maximum)  
INDOOR AIR  
QUALITY  
CABINET  
(PCO, Filter  
Cabinet, etc.)  
2
1 22−7/16  
(570)  
Overall  
1 Unit side return air  
Opening  
14 (356)  
MUST  
AIR FLOW  
(Maximum)  
COVER BOTH  
UNIT AND  
RETURN  
AIR BASE  
OPENINGS  
SIDE RETURN  
AIR OPENINGS  
(Either Side)  
5−5/8  
(143)  
7−1/4  
(184)  
23  
(584)  
OPTIONAL  
RETURN  
AIR BASE  
3/4  
(19)  
17−1/2 (446) B Width (50W98)  
21 (533) C Width (50W99)  
26−7/8  
(683)  
24−1/2 (622) D Width (51W00)  
SIDE VIEW  
FRONT VIEW  
NOTE- Optional side return air filter kits are not for use with return air base.  
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.  
Minimum unit side return air opening dimensions for units requiring 1800 cfm of air and over (W x H): 23 x 11 in. (584 x 279 mm).  
The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.  
Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air  
opening. The size of the opening must not extend beyond the markings on the furnace cabinet.  
2
To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.  
FIGURE 14  
Removing the Bottom Panel  
Removing the Bottom Panel  
Remove the two screws that secure the bottom cap to the  
furnace. Pivot the bottom cap down to release the bottom  
panel. Once the bottom panel has been removed, reinstall  
Horizontal Applications  
WARNING  
Do not install the furnace on its front or back.  
Screw  
Bottom Cap  
Bottom Panel  
FIGURE 15  
FIGURE 16  
Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
The EL296UHE furnace can be installed in horizontal ap-  
plications with either right- or left-hand air discharge.  
Refer to figure 17 for clearances in horizontal applications.  
HORIZONTAL SUSPENSION KIT  
Internal Brace  
(provided with kit)  
Metal Strap  
(typical)  
Horizontal Application  
Installation Clearances  
Right-Hand Discharge  
Bracket  
(typical)  
Left End  
Right End  
Air  
Flow  
Air  
Flow  
Air  
Flow  
Bottom (Floor)**  
Left-Hand Discharge  
Top  
FIGURE 18  
Left End  
Right End  
NOTE - When the furnace is installed on a platform or with  
the horizontal suspension kit in a crawlspace, it must be  
elevated enough to avoid water damage, accommodate  
drain trap and to allow the evaporator coil to drain.  
Air  
Flow  
Air  
Flow  
Bottom (Floor)**  
Platform Installation of Horizontal Unit  
Top  
0
0
0
0
0
1 - Select location for unit keeping in mind service and  
Front*  
Back  
Ends  
Vent  
2 - Construct a raised wooden frame and cover frame  
with a plywood sheet. If unit is installed above finished  
space, install an an auxiliary drain pan under unit. Set  
unit in drain pan as shown in figure 19. Leave 8 inches  
for service clearance below unit for condensate trap.  
Floor  
0‡  
3 - Provide a service platform in front of unit. When instal-  
ling the unit in a crawl space, a proper support platform  
may be created using concrete blocks.  
*Front clearance in alcove installation must be 24 in. (610 mm).  
Maintain a minimum of 24 in. (610 mm) for front service access.  
**An 8” service clearance must be maintained below the unit to  
provide for servicing of the condensate trap.  
For installations on a combustible floor, do not install the furnace  
directly on carpeting, tile or other combustible materials other  
than wood flooring.  
4 - Route auxiliary drain line so that water draining from  
this outlet will be easily noticed by the homeowner.  
5 - If necessary, run the condensate line into a conden-  
sate pump to meet drain line slope requirements. The  
pump must be rated for use with condensing furnaces.  
Protect the condensate discharge line from the pump  
to the outside to avoid freezing.  
FIGURE 17  
Suspended Installation of Horizontal Unit  
This furnace may be installed in either an attic or a crawl-  
space. Either suspend the furnace from roof rafters or  
floor joists, as shown in figure 18, or install the furnace on  
a platform, as shown in figure 19. A horizontal suspension  
kit (51W10) may be ordered from Lennox or use equiva-  
lent.  
6 - Continue with exhaust, condensate and intake piping  
installation according to instructions.  
NOTE - Heavy-gauge sheet metal straps may be used to  
suspend the unit from roof rafters or ceiling joists. When  
straps are used to suspend the unit in this way, support  
must be provided for both the ends. The straps must not  
interfere with the plenum or exhaust piping installation.  
Cooling coils and supply and return air plenums must  
be supported separately.  
Page 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Duct System  
*GAS CONNECTION  
INTAKE PIPE  
Use industry‐approved standards to size and install the  
supply and return air duct system. Refer to ACCA Manual  
D. This will result in a quiet and low‐static system that has  
uniform air distribution.  
EXHAUST PIPE  
*Gas connector may be  
used for Canadian  
installation if accept-  
able by local authority  
having jurisdiction.  
NOTE - This furnace is not certified for operation in heating  
mode (indoor blower operating at selected heating speed)  
with an external static pressure which exceeds 0.8 inches  
w.c. Operation at these conditions may result in improper  
limit operation.  
Supply Air Plenum  
If the furnace is installed without a cooling coil, a removable  
access panel should be installed in the supply air duct. The  
access panel should be large enough to permit inspection  
of the heat exchanger. The furnace access panel must al-  
ways be in place when the furnace is operating and it must  
not allow leaks.  
RAISED  
PLATFORM  
SERVICE PLATFORM  
FIGURE 19  
Return Air -- Horizontal Applications  
Return air may be brought in only through the end of a fur-  
nace installed in the horizontal position. The furnace is  
equipped with a removable bottom panel to facilitate  
installation. See figure 15.  
Return Air Plenum  
NOTE - Return air must not be drawn from a room  
where this furnace, or any other gas-fueled appliance  
(i.e., water heater), or carbon monoxide-producing de-  
vice (i.e., wood fireplace) is installed.  
Filters  
When return air is drawn from a room, a negative pres-  
sure is created in the room. If agas appliance is operating  
in a room with negative pressure, the flue products can  
be pulled back down the vent pipe and into the room. This  
reverse flow of the flue gas may result in incomplete com-  
bustion and the formation of carbon monoxide gas. This  
raw gas or toxic fumes might then be distributed through-  
out the house by the furnace duct system.  
This unit is not equipped with a filter or rack. A field-pro-  
vided high velocity rated filter is required for the unit to oper-  
A filter must be in place whenever the unit is operating.  
IMPORTANT  
If a high-efficiency filter is being installed as part of  
this system to ensure better indoor air quality, the fil-  
ter must be properly sized. High-efficiency filters  
have a higher static pressure drop than standard-ef-  
ficiency glass/foam filters. If the pressure drop is too  
great, system capacity and performance may be re-  
duced. The pressure drop may also cause the limit to  
trip more frequently during the winter and the indoor  
coil to freeze in the summer, resulting in an increase  
in the number of service calls.  
Return air can be brought in through the bottom or either  
side of the furnace (return air brought into either side of fur-  
nace allowed only in upflow applications). If a furnace with  
bottom return air is installed on a platform, make an airtight  
seal between the bottom of the furnace and the platform to  
ensure that the unit operates properly and safely. Use fiber-  
glass sealing strips, caulking, or equivalent sealing method  
between the plenum and the furnace cabinet to ensure a  
tight seal. If a filter is installed, size the return air duct to fit  
the filter frame.  
Before using any filter with this system, check the  
specifications provided by the filter manufacturer  
against the data given in the appropriate Lennox  
Product Specifications bulletin. Additional informa-  
tion is provided in Service and Application Note  
ACC-00-2 (August 2000).  
Pipe & Fittings Specifications  
All pipe, fittings, primer and solvent cement must conform  
with American National Standard Institute and the Ameri-  
can Society for Testing and Materials (ANSI/ASTM) stan-  
dards. The solvent shall be free flowing and contain no  
lumps, undissolved particles or any foreign matter that ad-  
versely affects the joint strength or chemical resistance of  
the cement. The cement shall show no gelation, stratifica-  
tion, or separation that cannot be removed by stirring. Re-  
fer to the table 2 below for approved piping and fitting ma-  
terials.  
TABLE 1  
Filter Size  
Furnace  
Cabinet Width  
Side Return  
Bottom Return  
16 X 25 X 1 (1)  
20 X 25 X 1 (1)  
24 X 25 X 1 (1)  
17-1/2”  
21”  
16 X 25 X 1 (1)  
16 X 25 X 1 (1)  
16 X 25 X 1 (2)  
24-1/2”  
Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Low temperature solvent cement is recommended during  
installation in cooler weather. Metal or plastic strapping may  
be used for vent pipe hangers. Uniformly apply a liberal coat  
of PVC primer for PVC or use a clean dry cloth for ABS to  
clean inside socket surface of fitting and male end of pipe to  
depth of fitting socket.  
CAUTION  
Solvent cements for plastic pipe are flammable liq-  
uids and should be kept away from all sources of  
ignition. Do not use excessive amounts of solvent  
cement when making joints. Good ventilation should  
be maintained to reduce fire hazard and to minimize  
breathing of solvent vapors. Avoid contact of ce-  
ment with skin and eyes.  
Canadian Applications Only - Pipe, fittings, primer  
and solvent cement used to vent (exhaust) this ap-  
pliance must be certified to ULC S636 and supplied by a  
single manufacturer as part of an approved vent (ex-  
haust) system. In addition, the first three feet of vent  
pipe from the furnace flue collar must be accessible for  
inspection.  
TABLE 2  
PIPING AND FITTINGS SPECIFICATIONS  
Schedule 40 PVC (Pipe)  
D1785  
F891  
Schedule 40 PVC (Cellular Core Pipe)  
Schedule 40 PVC (Fittings)  
D2466  
F441  
Joint Cementing Procedure  
Schedule 40 CPVC (Pipe)  
All cementing of joints should be done according to the  
specifications outlined in ASTM D 2855.  
Schedule 40 CPVC (Fittings)  
SDR-21 PVC or SDR-26 PVC (Pipe)  
SDR-21 CPVC or SDR-26 CPVC (Pipe)  
Schedule 40 ABS Cellular Core DWV (Pipe)  
Schedule 40 ABS (Pipe)  
F438  
D2241  
F442  
F628  
DANGER  
DANGER OF EXPLOSION!  
D1527  
D2468  
Schedule 40 ABS (Fittings)  
Fumes from PVC glue may ignite during system  
check. Allow fumes to dissipate for at least 5 minutes  
before placing unit into operation.  
ABS-DWV (Drain Waste & Vent)  
(Pipe & Fittings)  
D2661  
D2665  
PVC-DWV (Drain Waste & Vent)  
Pipe & Fittings)  
1 - Measure and cut vent pipe to desired length.  
ASTM  
SPECIFICATION  
PRIMER & SOLVENT CEMENT  
2 - Debur and chamfer end of pipe, removing any ridges  
or rough edges. If end is not chamfered, edge of pipe  
may remove cement from fitting socket and result in a  
leaking joint.  
PVC & CPVC Primer  
PVC Solvent Cement  
CPVC Solvent Cement  
ABS Solvent Cement  
F656  
D2564  
F493  
NOTE - Check the inside of vent pipe thoroughly for  
D2235  
any obstruction that may alter furnace operation.  
PVC/CPVC/ABS All Purpose Cement For  
Fittings & Pipe of the same material  
D2564, D2235, F493  
D3138  
3 - Clean and dry surfaces to be joined.  
ABS to PVC or CPVC Transition Solvent  
Cement  
4 - Test fit joint and mark depth of fitting on outside of pipe.  
5 - Uniformly apply a liberal coat of PVC primer for PVC or  
use a clean dry cloth for ABS to clean inside socket  
surface of fitting and male end of pipe to depth of fitting  
socket.  
CANADA PIPE & FITTING & SOLVENT  
CEMENT  
MARKING  
PVC & CPVC Pipe and Fittings  
PVC & CPVC Solvent Cement  
ULCS636  
NOTE- Time is critical at this stage. Do not allow prim-  
er to dry before applying cement.  
ABS to PVC or CPVC Transition Cement  
6 - Promptly apply solvent cement to end of pipe and in-  
side socket surface of fitting. Cement should be ap-  
plied lightly but uniformly to inside of socket. Take  
care to keep excess cement out of socket. Apply sec-  
ond coat to end of pipe.  
IMPORTANT  
EL296UHE exhaust and intake connections are  
made of PVC. Use PVC primer and solvent cement  
when using PVC vent pipe. When using ABS vent  
pipe, use transitional solvent cement to make con-  
nections to the PVC fittings in the unit.  
7 - Immediately after applying last coat of cement to pipe,  
and while both inside socket surface and end of pipe  
are wet with cement, forcefully insert end of pipe into  
socket until it bottoms out. Turn PVC pipe 1/4 turn dur-  
ing assembly (but not after pipe is fully inserted) to dis-  
tribute cement evenly. DO NOT turn ABS or cellular  
core pipe.  
Use PVC primer and solvent cement or ABS solvent cement  
meeting ASTM specifications, refer to Table 2. As an alter-  
nate, use all purpose cement, to bond ABS, PVC, or CPVC  
pipe when using fittings and pipe made of the same materi-  
als. Use transition solvent cement when bonding ABS to ei-  
ther PVC or CPVC.  
NOTE - Assembly should be completed within 20 sec-  
onds after last application of cement. Hammer blows  
should not be used when inserting pipe.  
Page 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
8 - After assembly, wipe excess cement from pipe at end  
of fitting socket. A properly made joint will show a  
bead around its entire perimeter. Any gaps may indi-  
cate an improper assembly due to insufficient sol-  
vent.  
Conduct the following test while each appliance is operat-  
ing and the other appliances (which are not operating) re-  
main connected to the common venting system. If the  
venting system has been installed improperly, you must  
correct the system as indicated in the general venting re-  
quirements section.  
9 - Handle joints carefully until completely set.  
Venting Practices  
WARNING  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow the steps outlined below for each  
appliance connected to the venting system being  
placed into operation could result in carbon mon-  
oxide poisoning or death.  
The following steps shall be followed for each ap-  
pliance connected to the venting system being  
placed into operation, while all other appliances  
connected to the venting system are not in  
operation:  
Piping Suspension Guidelines  
SCHEDULE 40  
PVC - 5'  
all other pipe* - 3'  
NOTE - Isolate piping at the point where it exits the outside wall or  
roof in order to prevent transmission of vibration to the structure.  
1 - Seal any unused openings in the common venting sys-  
tem.  
NOTE - All horizontal runs of exhaust pipe must slope back to-  
ward unit a minimum of 1/4” (6mm) drop for each 12” (305mm).  
2 - Inspect the venting system for proper size and horizontal  
pitch. Determine that there is no blockage, restriction,  
leakage, corrosion, or other deficiencies which could  
cause an unsafe condition.  
Wall Thickness Guidelines  
24” maximum  
3/4” minimum  
3 - Close all building doors and windows and all doors be-  
tween the space in which the appliances remaining  
connected to the common venting system are located  
and other spaces of the building. Turn on clothes dry-  
ers and any appliances not connected to the common  
venting system. Turn on any exhaust fans, such as  
range hoods and bathroom exhausts, so they will oper-  
ate at maximum speed. Do not operate a summer ex-  
haust fan. Close fireplace dampers.  
Wall  
inside  
outside  
insulation  
(if required)  
4 - Follow the lighting instructions. Turn on the appliance  
that is being inspected. Adjust the thermostat so that  
the appliance operates continuously.  
FIGURE 20  
1 - In areas where piping penetrates joists or interior  
walls, hole must be large enough to allow clearance on  
all sides of pipe through center of hole using a hanger.  
5 - After the main burner has operated for 5 minutes, test  
for leaks of flue gases at the draft hood relief opening.  
Use the flame of a match or candle.  
2 - When furnace is installed in a residence where unit is  
shut down for an extended period of time, such as a  
vacation home, make provisions for draining conden-  
sate collection trap and lines.  
6 - After determining that each appliance connected to the  
common venting system is venting properly, (step 3)  
return all doors, widows, exhaust fans, fireplace damp-  
ers, and any other gas-burning appliances to their pre-  
vious mode of operation.  
Removal of the Furnace from Common Vent  
In the event that an existing furnace is removed from a  
venting system commonly run with separate gas ap-  
pliances, the venting system is likely to be too large to  
properly vent the remaining attached appliances.  
7 - If a venting problem is found during any of the preced-  
ing tests, the common venting system must be modi-  
fied to correct the problem.  
Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Resize the common venting system to the minimum  
vent pipe size determined by using the appropriate  
tables in Appendix G. (These are in the current stan-  
dards of the National Fuel Gas Code ANSI Z223.1.  
NOTE - In Non‐Direct Vent installations, combustion air is  
taken from indoors or ventilated attic or crawlspace and flue  
gases are discharged outdoors. In Direct Vent installations,  
combustion air is taken from outdoors and flue gases are  
discharged outdoors.  
Intake and exhaust pipe sizing -- Size pipe according to  
tables 3 and 5. Count all elbows inside and outside the  
home. Table 3 lists the minimum vent pipe lengths per-  
mitted. Table 5 lists the maximum pipe lengths permitted.  
REPLACING FURNACE THAT  
WAS PART OF A COMMON  
VENT SYSTEM  
CHIMNEY  
OR GAS  
VENT  
(Check sizing  
for water  
heater only)  
Regardless of the diameter of pipe used, the standard roof  
and wall terminations described in section Exhaust Piping  
Terminations should be used. Exhaust vent termination  
pipe is sized to optimize the velocity of the exhaust gas as  
it exits the termination. Refer to table 8.  
FURNACE  
(Replaced  
by EL296)  
WATER  
HEATER  
In some applications which permit the use of several differ-  
ent sizes of vent pipe, a combination vent pipe may be  
used. Contact Lennox' Application Department for assis-  
tance in sizing vent pipe in these applications.  
OPENINGS  
(To Adjacent  
Room)  
NOTE - The exhaust collar on all models is sized to ac-  
commodate 2” Schedule 40 vent pipe. In horizontal ap-  
plications, any transition to exhaust pipe larger than 2”  
must be made in vertical runs of the pipe. Therefore a 2”  
elbow must be added before the pipe is transitioned to  
any size larger than 2”. This elbow must be added to the  
elbow count used to determine acceptable vent lengths.  
Contact the Application Department for more information  
concerning sizing of vent systems which include multiple  
pipe sizes.  
If an EL296UHE furnace replaces a furnace which  
was commonly vented with another gas appliance,  
the size of the existing vent pipe for that gas ap-  
pliance must be checked. Without the heat of the  
original furnace flue products, the existing vent pipe  
is probably oversized for the single water heater or  
other appliance. The vent should be checked for  
proper draw with the remaining appliance.  
FIGURE 21  
Horizontal Installation Offset Requirements  
Exhaust Pipe  
Route piping to outside of structure. Continue with installa-  
tion following instructions given in piping termination sec-  
tion.  
12” Min.  
12” Max.  
Horizontal  
Gas Furnace  
CAUTION  
Do not discharge exhaust into an existing stack or  
stack that also serves another gas appliance. If verti-  
cal discharge through an existing unused stack is re-  
quired, insert PVC pipe inside the stack until the end  
is even with the top or outlet end of the metal stack.  
NOTE - All horizontal runs of exhaust pipe must slope back to-  
ward unit. A minimum of 1/4” (6mm) drop for each 12” (305mm)  
of horizontal run is mandatory for drainage.  
NOTE - Exhaust pipe MUST be glued to furnace exhaust fittings.  
NOTE - Exhaust piping should be checked carefully to make  
sure there are no sags or low spots.  
CAUTION  
FIGURE 22  
The exhaust vent pipe operates under positive pres-  
sure and must be completely sealed to prevent leak-  
age of combustion products into the living space.  
TABLE 3  
MINIMUM VENT PIPE LENGTHS  
EL296UHE  
MODEL  
MIN. VENT LENGTH*  
Vent Piping Guidelines  
15 ft. or  
5 ft. plus 2 elbows or  
10 ft. plus 1 elbow  
045, 070, 090, 110, 135  
The EL296UHE can be installed as either a Non-Direct  
Vent or a Direct Vent gas central furnace.  
*Any approved termination may be added to the minimum length listed.  
Page 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Use the following steps to correctly size vent pipe diameter.  
IMPORTANT  
Do not use screens or perforated metal in exhaust or  
intake terminations. Doing so will cause freeze-ups  
and may block the terminations.  
Piping Size Process  
What is the  
furnace capacity?  
1
2
045, 070, 090,  
110 or 135?  
Which style termination  
being used?  
Standard or concentric?  
Which needs  
most elbows?  
Intake or  
3
exhaust?  
How many elbows?  
Count all elbows inside  
and outside house.  
4
5
Desired pipe size?  
2”, 2-1/2”, 3”  
What is the altitude of  
the furnace installation?  
6
max intake or exhaust pipe  
length. Includes all vent  
pipe and elbows inside  
and outside the house.  
7
FIGURE 23  
Page 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 4  
OUTDOOR TERMINATION USAGE  
STANDARD  
CONCENTRIC  
Wall Kit  
Wall Ring Kit  
2 inch  
FlushMount  
Kit  
1-1/2 inch  
2 inch  
3 inch  
Vent  
Pipe  
Dia. in.  
2 inch  
3 inch  
Input Size  
Field  
Fabricated  
71M80  
(US)  
44W92  
(CA)  
69M29  
(US)  
44W92  
(CA)  
51W11 (US)  
51W12 (CA)  
22G44 (US)  
30G28 (CA)  
44J40 (US)  
4
60L46 (US)  
44W93 (CA)  
15F74  
4
4
4
4
81J20 (CA)  
3
1
1
5
2
2
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
3
1
1
5
2
2-1/2  
YES  
YES  
YES  
YES  
YES  
045  
070  
090  
3
1
1
5
2
3
YES  
YES  
YES  
YES  
YES  
3
1
1
5
2
2
YES  
YES  
YES  
YES  
YES  
3
1
1
5
2
2-1/2  
YES  
YES  
YES  
YES  
YES  
3
1
1
5
2
3
YES  
YES  
YES  
YES  
YES  
3
5
2
2-1/2  
3
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
3
5
YES  
YES  
3
5
YES  
YES  
5
2
YES  
YES  
YES  
YES  
YES  
5
2-1/2  
3
YES  
110  
135  
5
YES  
YES  
YES  
5
3
YES  
NOTE - Standard Terminations do not include any vent pipe or elbows external to the structure. Any vent pipe or elbows external to the structure must be included in total vent length  
calculations. See vent length tables.  
1
Requires field-provided outdoor 1-1/2” exhaust accelerator.  
Concentric kits 71M80 and 44W92 include 1-1/2” outdoor accelerator, when used with 045 and 070 input models.  
Flush mount kit 51W11 and 51W12 includes 1-1/2 in. outdoor exhaust accelerator, required when used with 045, 070 and 090 input models.  
Termination kits 30G28, 44W92, 44W93 and 81J20 are certified to ULC S636 for use in Canada only.  
2
3
4
5
Page 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE 5  
Maximum Allowable Intake or Exhaust Vent Length in Feet  
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe  
size.  
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.  
Standard Termination at Elevation 0 - 4500 ft  
2” Pipe  
Model  
090  
44  
2-1/2” Pipe  
3” Pipe  
Model  
090  
118  
113  
108  
103  
98  
Number Of  
90° Elbows  
Used  
Model  
090  
93  
045  
81  
76  
71  
66  
61  
56  
51  
46  
41  
36  
070  
66  
61  
56  
51  
46  
41  
36  
31  
26  
21  
110  
24  
135  
045  
115  
110  
105  
100  
95  
070  
115  
110  
105  
100  
95  
110  
58  
53  
48  
43  
38  
33  
28  
23  
18  
13  
135  
045  
138  
133  
128  
123  
118  
113  
108  
103  
98  
070  
137  
132  
127  
122  
117  
112  
107  
102  
97  
110  
118  
113  
108  
103  
98  
135  
114  
109  
104  
99  
1
2
39  
19  
88  
3
34  
14  
83  
4
29  
78  
5
24  
73  
94  
n/a  
n/a  
6
19  
90  
90  
68  
93  
93  
89  
7
14  
85  
85  
63  
88  
88  
84  
n/a  
8
80  
80  
58  
83  
83  
79  
9
75  
75  
53  
78  
78  
74  
n/a  
10  
70  
70  
48  
93  
92  
73  
73  
69  
Standard Termination Elevation 4500 - 10,000 ft  
2” Pipe  
Model  
090  
44  
2-1/2” Pipe  
3” Pipe  
Model  
090  
118  
113  
108  
103  
98  
Number Of  
90° Elbows  
Used  
Model  
045  
81  
76  
71  
66  
61  
56  
51  
46  
41  
36  
070  
66  
61  
56  
51  
46  
41  
36  
31  
26  
21  
110  
135  
045  
115  
110  
105  
100  
95  
070  
115  
110  
105  
100  
95  
090  
93  
88  
83  
78  
73  
68  
63  
58  
53  
48  
110  
58  
53  
48  
43  
38  
33  
28  
23  
18  
13  
135  
045  
138  
133  
128  
123  
118  
113  
108  
103  
98  
070  
137  
132  
127  
122  
117  
112  
107  
102  
97  
110  
118  
113  
108  
103  
98  
135  
114  
109  
104  
99  
1
2
39  
3
34  
4
29  
5
24  
94  
n/a  
n/a  
n/a  
6
19  
90  
90  
93  
93  
89  
7
14  
85  
85  
88  
88  
84  
8
80  
80  
83  
83  
79  
9
75  
75  
78  
78  
74  
n/a  
10  
70  
70  
93  
92  
73  
73  
69  
See concentric terminations next page.  
Page 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE 5 Continued  
Maximum Allowable Intake or Exhaust Vent Length in Feet  
Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.  
Concentric Termination at Elevation 0 - 4500 ft  
2” Pipe  
Model  
090  
42  
2-1/2” Pipe  
3” Pipe  
Model  
090  
114  
109  
104  
99  
Number Of  
90° Elbows  
Used  
Model  
090  
89  
045  
73  
68  
63  
58  
53  
48  
43  
38  
33  
28  
070  
58  
53  
48  
43  
38  
33  
28  
23  
18  
13  
110  
22  
135  
045  
105  
100  
95  
070  
105  
100  
95  
110  
54  
49  
44  
39  
34  
29  
24  
19  
14  
n/a  
135  
045  
121  
116  
111  
106  
101  
96  
070  
121  
116  
111  
106  
101  
96  
110  
114  
109  
104  
99  
135  
105  
100  
95  
1
2
37  
17  
84  
3
32  
12  
79  
4
27  
90  
90  
74  
90  
5
22  
85  
85  
69  
94  
94  
85  
n/a  
n/a  
6
17  
80  
80  
64  
89  
89  
80  
7
12  
75  
75  
59  
91  
91  
84  
84  
75  
n/a  
8
70  
70  
54  
86  
86  
79  
79  
70  
9
65  
65  
49  
81  
81  
74  
74  
65  
n/a  
10  
60  
60  
44  
76  
76  
69  
69  
60  
Concentric Termination Elevation 4501 - 10,000 ft  
2” Pipe  
2-1/2” Pipe  
3” Pipe  
Model  
090  
114  
109  
104  
99  
Number Of  
90° Elbows  
Used  
Model  
090  
42  
Model  
090  
89  
045  
73  
68  
63  
58  
53  
48  
43  
38  
33  
28  
070  
58  
53  
48  
43  
38  
33  
28  
23  
18  
13  
110  
135  
045  
105  
100  
95  
070  
105  
100  
95  
110  
54  
49  
44  
39  
34  
29  
24  
19  
14  
n/a  
135  
045  
121  
116  
111  
106  
101  
96  
070  
121  
116  
111  
106  
101  
96  
110  
114  
109  
104  
99  
135  
105  
100  
95  
1
2
37  
84  
3
32  
79  
4
27  
90  
90  
74  
90  
5
22  
85  
85  
69  
94  
94  
85  
n/a  
n/a  
n/a  
6
17  
80  
80  
64  
89  
89  
80  
7
12  
75  
75  
59  
91  
91  
84  
84  
75  
8
70  
70  
54  
86  
86  
79  
79  
70  
9
65  
65  
49  
81  
81  
74  
74  
65  
n/a  
10  
60  
60  
44  
76  
76  
69  
69  
60  
Page 20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 6  
Maximum Allowable Exhaust Vent Lengths With Furnace Installed in a Closet or Basement Using Ventilated  
Attic or Crawl Space For Intake Air in Feet  
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe  
size.  
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.  
Standard Termination at Elevation 0 - 4500 ft  
2” Pipe  
Model  
090  
34  
2-1/2” Pipe  
3” Pipe  
Model  
090  
98  
Number Of  
90° Elbows  
Used  
Model  
090  
78  
045  
71  
66  
61  
56  
51  
46  
41  
36  
31  
26  
070  
56  
51  
46  
41  
36  
31  
26  
21  
16  
11  
110  
14  
9
135  
045  
100  
95  
90  
85  
80  
85  
70  
65  
60  
55  
070  
100  
95  
90  
85  
80  
75  
70  
65  
60  
55  
110  
43  
38  
33  
28  
23  
18  
13  
8
135  
045  
118  
113  
108  
103  
98  
070  
117  
112  
107  
102  
97  
110  
98  
93  
88  
83  
78  
73  
68  
63  
58  
53  
135  
94  
89  
84  
79  
74  
69  
64  
59  
54  
49  
1
2
29  
73  
93  
3
24  
4
68  
88  
4
19  
63  
83  
5
14  
58  
78  
n/a  
n/a  
6
9
63  
93  
92  
73  
7
4
48  
88  
87  
68  
n/a  
8
43  
83  
82  
63  
9
38  
3
78  
77  
58  
n/a  
10  
33  
n/a  
73  
72  
53  
Standard Termination Elevation 4500 - 10,000 ft  
2” Pipe  
Model  
090  
34  
2-1/2” Pipe  
3” Pipe  
Model  
090  
98  
Number Of  
90° Elbows  
Used  
Model  
045  
71  
66  
61  
56  
51  
46  
41  
36  
31  
26  
070  
56  
51  
46  
41  
36  
31  
26  
21  
16  
11  
110  
135  
045  
100  
95  
90  
85  
80  
85  
70  
65  
60  
55  
070  
100  
95  
90  
85  
80  
85  
70  
65  
60  
55  
090  
78  
73  
68  
63  
58  
53  
48  
43  
38  
33  
110  
43  
38  
33  
28  
23  
18  
13  
8
135  
045  
118  
113  
108  
103  
98  
070  
117  
112  
107  
102  
97  
110  
98  
93  
88  
83  
78  
73  
68  
63  
58  
53  
135  
94  
89  
84  
79  
74  
69  
64  
59  
54  
49  
1
2
29  
93  
3
24  
88  
4
19  
83  
5
14  
78  
n/a  
n/a  
n/a  
6
9
93  
92  
73  
7
4
88  
87  
68  
8
83  
82  
63  
9
3
78  
77  
58  
n/a  
10  
n/a  
73  
72  
53  
Page 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN UPFLOW DIRECT OR  
NON-DIRECT VENT APPLICATIONS  
EXHAUST INTAKE  
EXHAUST  
INTAKE  
2”  
2”  
2”  
2”  
or  
3”  
3”  
TRANSITION  
TRANSITION  
2”  
2”  
*2”  
*2”  
DO NOT transition  
from smaller to larger  
pipe in horizontal runs  
of exhaust pipe.  
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.  
FIGURE 24  
TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN HORIZONTAL DIRECT OR NON-DIRECT VENT  
APPLICATIONS (RIGHT HAND DISCHARGE SHOWN)  
45°  
MAX  
45°  
MAX  
12” max.  
2”  
or  
EXHAUST  
2”  
2”  
2”  
2”  
or  
2”  
2”  
*2”  
2”  
SIDE VIEW  
2”  
2”  
INTAKE  
3”  
DO NOT transition  
from smaller to larger  
pipe in horizontal runs  
TRANSITION  
3”  
*2”  
of exhaust pipe.  
EXHAUST  
*2”  
*2”  
*2”  
INTAKE  
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.  
FIGURE 25  
Page 22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Intake Piping  
TYPICAL AIR INTAKE PIPE CONNECTIONS  
HORIZONTAL NON−DIRECT VENT APPLICATIONS  
(Horizontal Right−Hand Air Discharge Application Shown)  
The EL296UHE furnace may be installed in either direct  
vent or non-direct vent applications. In non-direct vent  
applications, when intake air will be drawn into the furnace  
from the surrounding space, the indoor air quality must be  
considered and guidelines listed in Combustion, Dilution  
and Ventilation Air section must be followed.  
PVC pipe  
coupling  
Follow the next two steps when installing the unit in Direct  
Vent applications, where combustion air is taken from  
outdoors and flue gases are discharged outdoors. The  
provided air intake screen must not be used in direct  
vent applications (outdoors).  
OR  
1 - Use transition solvent cement or a sheet metal screw  
to secure the intake pipe to the inlet air connector.  
INTAKE  
DEBRIS  
SCREEN  
(Provided)  
2 - Route piping to outside of structure. Continue with  
installation following instructions given in general  
guidelines for piping terminations and intake and ex-  
haust piping terminations for direct vent sections. Re-  
fer to table 5 for pipe sizes.  
NOTE - Debris screen may be positioned straight out  
(preferred) or with an elbow rotated to face down.  
TYPICAL AIR INTAKE PIPE CONNECTIONS  
UPFLOW NON−DIRECT  
FIGURE 27  
VENT APPLICATIONS  
Follow the next two steps when installing the unit in Non‐  
Direct Vent applications where combustion air is taken  
from indoors or ventilated attic or crawlspace and flue  
gases are discharged outdoors.  
INTAKE  
DEBRIS  
SCREEN  
(Provided)  
1 - Use field-provided materials and the factory-provided  
air intake screen to route the intake piping as shown in  
(76mm) around the air intake opening. The air intake  
opening (with the protective screen) should always be  
directed forward or to either side in the upflow position,  
and either straight out or downward in the horizontal  
position.  
The air intake piping must not terminate too close  
to the flooring or a platform. Ensure that the intake  
air inlet will not be obstructed by loose insulation  
or other items that may clog the debris screen.  
ameter pipe is used, reduce to 2” diameter pipe at the  
termination point to accommodate the debris screen.  
NOTE - Debris screen and elbow may be rotated, so that  
screen may be positioned to face forward or to either side.  
3 - Use a sheet metal screw to secure the intake pipe to  
the connector, if desired.  
FIGURE 26  
Page 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
General Guidelines for Vent Terminations  
CAUTION  
In Non‐Direct Vent applications, combustion air is taken  
from indoors or ventilated attic or crawlspace and the flue  
gases are discharged to the outdoors. The EL296UHE is  
then classified as a non‐direct vent, Category IV gas fur-  
nace.  
If this unit is being installed in an application with  
combustion air coming in from a space serviced by  
an exhaust fan, power exhaust fan, or other device  
which may create a negative pressure in the space,  
take care when sizing the inlet air opening. The in-  
let air opening must be sized to accommodate the  
maximum volume of exhausted air as well as the  
maximum volume of combustion air required for  
all gas appliances serviced by this space.  
In Direct Vent applications, combustion air is taken from  
outdoors and the flue gases are discharged to the out-  
doors. The EL296UHE is then classified as a direct vent,  
Category IV gas furnace.  
In both Non‐Direct Vent and Direct Vent applications, the  
vent termination is limited by local building codes. In the  
absence of local codes, refer to the current National Fuel  
Gas Code ANSI Z223-1/NFPA 54 in U.S.A., and current  
CSA-B149 Natural Gas and Propane Installation Codes in  
Canada for details.  
EQUIPMENT IN CONFINED SPACE  
(Inlet Air from Ventilated Attic and Outlet Air to Outside)  
Ventilation Louvers  
Inlet Air  
Roof Terminated  
Exhaust Pipe  
(Minimum  
12 in.(305mm) Above  
attic floor)  
or 31. In addition, position termination so it is free from any  
obstructions and 12” above the average snow accumula-  
tion.  
*Intake Debris  
Screen  
(Provided)  
At vent termination, care must be taken to maintain  
protective coatings over building materials (prolonged  
exposure to exhaust condensate can destroy protective  
coatings). It is recommended that the exhaust outlet not be  
located within 6 feet (1.8m) of a condensing unit because  
the condensate can damage the painted coating.  
Furnace  
NOTE-The inlet and outlet air openings shall each have a free area  
2
of at least one square inch per 4,000 Btu (645mm per 1.17kW) per  
hour of the total input rating of all equipment in the enclosure.  
NOTE - See table 7 for maximum allowed exhaust pipe  
length without insulation in unconditioned space during  
winter design temperatures below 32°F (0°C). If required  
exhaust pipe should be insulated with 1/2” (13mm) Arma-  
flex or equivalent. In extreme cold climate areas, 3/4”  
(19mm) Armaflex or equivalent may be necessary. Insula-  
tion on outside runs of exhaust pipe must be painted or  
wrapped to protect insulation from deterioration. Exhaust  
pipe insulation may not be necessary in some specific ap-  
plications.  
FIGURE 28  
EQUIPMENT IN CONFINED SPACE  
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)  
Roof Terminated  
Exhaust Pipe  
Inlet Air  
(Minimum  
IMPORTANT  
Do not use screens or perforated metal in exhaust  
terminations. Doing so will cause freeze-ups and  
may block the terminations.  
12 in.(305mm)  
Above crawl  
space floor)  
Ventilation  
Louvers  
(Crawl space)  
Furnace  
Coupling or  
*Intake Debris Screen Provided)  
3 in. to 2 in.  
Transition  
IMPORTANT  
For Canadian Installations Only:  
(Field Provided)  
In accordance to CSA International B149 installation  
codes, the minimum allowed distance between the  
combustion air intake inlet and the exhaust outlet of  
other appliances shall not be less than 12 inches  
(305mm).  
NOTE-The inlet and outlet air openings shall each have a free area  
2
of at least one square inch per 4,000 Btu (645mm per 1.17kW) per  
hour of the total input rating of all equipment in the enclosure.  
FIGURE 29  
Page 24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE 7  
Maximum Allowable Exhaust Vent Pipe Length Without Insulation  
In Unconditioned Space For Winter Design Temperatures  
Unit Input Size  
Vent Pipe  
Diameter  
Winter Design  
1
Temperatures °F (°C)  
045  
20  
15  
12  
12  
10  
6
070  
30  
22  
18  
20  
14  
10  
12  
8
090  
40  
30  
25  
25  
20  
15  
18  
12  
10  
110  
24  
40  
32  
24  
24  
20  
22  
16  
12  
135  
N/A  
N/A  
32  
2 in.  
2-1/2 in.  
3 in.  
32 to 21  
(0 to -6)  
2 in  
N/A  
N/A  
20  
20 to 1  
(-7 to -17)  
2-1/2 in.  
3 in.  
2 in.  
8
N/A  
N/A  
12  
0 to -20  
(-18 to -29)  
2-1/2 in.  
3 in.  
6
2
6
1
Refer to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook.  
NOTE - Maximum uninsulated vent lengths listed may include the termination(vent pipe exterior to the structure) and cannot exceed 5 linear feet or the  
Page 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
VENT TERMINATION CLEARANCES  
FOR NON-DIRECT VENT INSTALLATIONS IN THE US AND CANADA  
INSIDE CORNER  
DETAIL  
G
H
A
D
E
B
L
B
Fixed  
Closed  
B
B
I
C
Operable  
Fixed  
Closed  
M
F
Operable  
K
J
A
B
AREA WHERE TERMINAL  
IS NOT PERMITTED  
AIR SUPPLY INLET  
VENT TERMINAL  
1
2
US Installations  
Canadian Installations  
A =  
Clearance above grade, veranda,  
porch, deck or balcony  
12 inches (305mm) or 12 in. (305mm)  
above average snow accumulation.  
12 inches (305mm) or 12 in. (305mm)  
above average snow accumulation.  
B =  
Clearance to window or  
door that may be opened  
6 inches (152mm) for appliances <10,000  
Btuh (3kw), 12 inches (305mm) for  
appliances > 10,000 Btuh (3kw) and  
<100,000 Btuh (30kw), 36 inches (.9m)  
for appliances > 100,000 Btuh (30kw)  
4 feet (1.2 m) below or to side of opening;  
1 foot (30cm) above opening  
C =  
D =  
Clearance to permanently  
closed window  
* 12”  
* 12”  
Vertical clearance to ventilated soffit  
located above the terminal within a  
horizontal distance of 2 feet (610 mm)  
from the center line of the terminal  
* Equal to or greater than soffit depth.  
* Equal to or greater than soffit depth.  
* Equal to or greater than soffit depth.  
E =  
F =  
Clearance to unventilated soffit  
Clearance to outside corner  
* Equal to or greater than soffit depth.  
* No minimum to outside corner  
*
* No minimum to outside corner  
*
G = Clearance to inside corner  
H = Clearance to each side of center line ex-  
tended above meter / regulator assembly  
3 feet (.9m) within a height 15 feet (4.5m) 3 feet (.9m) within a height 15 feet (4.5m)  
above the meter / regulator assembly  
*
above the meter / regulator assembly  
I =  
Clearance to service regulator  
vent outlet  
3 feet (.9m)  
* 3 feet (.9m)  
J =  
Clearance to non-mechanical air  
supply inlet to building or the com-  
bustion air inlet to any other ap-  
pliance  
6 inches (152mm) for appliances <10,000  
Btuh (3kw), 12 inches (305mm) for  
appliances > 10,000 Btuh (3kw) and  
<100,000 Btuh (30kw), 36 inches (.9m)  
for appliances > 100,000 Btuh (30kw)  
4 feet (1.2 m) below or to side of opening;  
1 foot (30 cm) above opening  
K =  
L =  
Clearance to mechanical air sup-  
ply inlet  
3 feet (.9m) above if within 10 feet  
(3m) horizontally  
6 feet (1.8m)  
Clearance above paved sidewalk or  
paved driveway located on public property  
7 feet (2.1m)†  
7 feet (2.1m)†  
M = Clearance under veranda, porch, deck or balcony  
12 inches (305mm)‡  
*12 inches (305mm)‡  
1
2
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code  
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code  
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA  
B149.1, clearance will be in accordance with local installation  
codes and the requirements of the gas supplier and these instal-  
lation instructions.”  
† A vent shall not terminate directly above a sidewalk or paved driveway that is  
located between two single family dwellings and serves both dwellings.  
‡ Permitted only if veranda, porch, deck or balcony is fully open  
on a minimum of two sides beneath the floor. Lennox recommends  
avoiding this location if possible.  
FIGURE 30  
Page 26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
VENT TERMINATION CLEARANCES  
FOR DIRECT VENT INSTALLATIONS IN THE US AND CANADA  
INSIDE CORNER  
DETAIL  
G
H
A
D
E
B
L
B
Fixed  
Closed  
B
B
I
C
Operable  
Fixed  
Closed  
M
F
Operable  
K
J
A
B
AREA WHERE TERMINAL  
IS NOT PERMITTED  
AIR SUPPLY INLET  
VENT TERMINAL  
1
2
US Installations  
Canadian Installations  
A =  
Clearance above grade, veranda,  
porch, deck or balcony  
12 inches (305mm) or 12 in. (305mm)  
above average snow accumulation.  
12 inches (305mm) or 12 in. (305mm)  
above average snow accumulation.  
B =  
Clearance to window or  
door that may be opened  
6 inches (152mm) for appliances <10,000 6 inches (152mm) for appliances <10,000  
Btuh (3kw), 9 inches (228mm) for ap-  
pliances > 10,000 Btuh (3kw) and <50,000  
Btuh (15 kw), 12 inches (305mm) for ap-  
pliances > 50,000 Btuh (15kw)  
Btuh (3kw), 12 inches (305mm) for  
appliances > 10,000 Btuh (3kw) and  
<100,000 Btuh (30kw), 36 inches (.9m)  
for appliances > 100,000 Btuh (30kw)  
* 12”  
C =  
D =  
Clearance to permanently  
closed window  
* 12”  
Vertical clearance to ventilated soffit  
located above the terminal within a  
horizontal distance of 2 feet (610mm)  
from the center line of the terminal  
* Equal to or greater than soffit depth  
* Equal to or greater than soffit depth  
* Equal to or greater than soffit depth  
* Equal to or greater than soffit depth  
* No minimum to outside corner  
E =  
F =  
G =  
Clearance to unventilated soffit  
Clearance to outside corner  
Clearance to inside corner  
* No minimum to outside corner  
*
*
H = Clearance to each side of center line ex-  
tended above meter / regulator assembly  
3 feet (.9m) within a height 15 feet (4.5m)  
above the meter / regulator assembly  
3 feet (.9m) within a height 15 feet (4.5m)  
above the meter / regulator assembly  
I =  
Clearance to service regulator  
vent outlet  
3 feet (.9m)  
* 3 feet (.9m)  
J =  
Clearance to non-mechanical air  
supply inlet to building or the com-  
bustion air inlet to any other ap-  
pliance  
6 inches (152mm) for appliances <10,000 6 inches (152mm) for appliances <10,000  
Btuh (3kw), 9 inches (228mm) for ap-  
pliances > 10,000 Btuh (3kw) and <50,000  
Btuh (15 kw), 12 inches (305mm) for ap-  
pliances > 50,000 Btuh (15kw)  
Btuh (3kw), 12 inches (305mm) for  
appliances > 10,000 Btuh (3kw) and  
<100,000 Btuh (30kw), 36 inches (.9m)  
for appliances > 100,000 Btuh (30kw)  
K =  
L =  
Clearance to mechanical air sup-  
ply inlet  
3 feet (.9m) above if within 10 feet  
(3m) horizontally  
6 feet (1.8m)  
Clearance above paved sidewalk or  
paved driveway located on public property  
7 feet (2.1m)†  
* 7 feet (2.1m)  
M = Clearance under veranda, porch, deck or balcony  
*12 inches (305mm)‡  
12 inches (305mm)‡  
1
2
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code  
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA  
B149.1, clearance will be in accordance with local installation  
codes and the requirements of the gas supplier and these  
installation instructions.”  
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code  
† A vent shall not terminate directly above a sidewalk or paved driveway that is located  
between two single family dwellings and serves both dwellings.  
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of  
two sides beneath the floor. Lennox recommends avoiding this location if possible.  
FIGURE 31  
Page 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Details of Intake and Exhaust Piping Terminations for  
Direct Vent Installations  
3”(76MM) MAX.  
SIZE TERMINATION  
PIPE PER TABLE 8.  
Inches(MM)  
NOTE - In Direct Vent installations, combustion air is tak-  
en from outdoors and flue gases are discharged to out-  
doors.  
UNCONDITIONED  
ATTIC SPACE  
8” (203MM) MIN  
1/2” (13MM) FOAM  
INSULATION IN  
UNCONDITIONED  
SPACE  
NOTE - Flue gas may be slightly acidic and may adversely  
affect some building materials. If any vent termination is  
used and the flue gasses may impinge on the building ma-  
terial, a corrosion-resistant shield (minimum 24 inches  
square) should be used to protect the wall surface. If the  
optional tee is used, the protective shield is recommended.  
The shield should be constructed using wood, plastic,  
sheet metal or other suitable material. All seams, joints,  
cracks, etc. in the affected area should be sealed using an  
12” (305MM) ABOVE  
AVERAGE SNOW  
ACCUMULATION  
3” (76MM) OR  
2” (51MM) PVC  
PROVIDE SUPPORT  
FOR INTAKE AND  
EXHAUST LINES  
Intake and exhaust pipes may be routed either horizontally  
through an outside wall or vertically through the roof. In at-  
tic or closet installations, vertical termination through the  
terminations.  
DIRECT VENT ROOF TERMINATION KIT  
(15F75 or 44J41)  
FIGURE 32  
Exiting Exhaust and Intake Vent  
(different pressure zones)  
1 - Intake and exhaust terminations are not required to be  
in the same pressure zone. You may exit the intake on  
one side of the structure and the exhaust on another  
side (figure 33). You may exit the exhaust out the roof  
2 - Intake and exhaust pipes should be placed as close  
together as possible at termination end (refer to il-  
lustrations). Maximum separation is 3” (76MM) on roof  
terminations and 6” (152MM) on side wall termina-  
tions.  
Inlet Air  
Exhaust  
Pipe  
Furnace  
(Minimum 12 in.  
305 MM) above  
grade or snow  
accumulation  
NOTE - When venting in different pressure zones, the  
maximum separation requirement of intake and ex-  
haust pipe DOES NOT apply.  
FIGURE 33  
3 - On roof terminations, the intake piping should termi-  
nate straight down using two 90° elbows (See figure  
32).  
Exiting Exhaust and Intake Vent  
(different pressure zones)  
4 - Exhaust piping must terminate straight out or up as  
shown. A reducer may be required on the exhaust pip-  
ing at the point where it exits the structure to improve  
the velocity of exhaust away from the intake piping.  
Roof T  
erminated  
Exhaust Pipe  
NOTE - Care must be taken to avoid recirculation of ex-  
haust back into intake pipe.  
Inlet Air  
5 - On field-supplied terminations for side wall exit, ex-  
haust piping may extend a maximum of 12 inches  
(305MM) for 2” PVC and 20 inches (508MM) for 3”  
(76MM) PVC beyond the outside wall. Intake piping  
6 - On field-supplied terminations, a minimum distance  
between the end of the exhaust pipe and the end of  
the intake pipe without a termination elbow is 8” and a  
minimum distance of 6” with a termination elbow. See  
figures 36 and 37.  
(Minimum 12 in.  
305 MM) above  
grade or snow  
accumulation  
Furnace  
FIGURE 34  
TABLE 8  
EXHAUST PIPE TERMINATION SIZE REDUCTION  
EL296UHE  
MODEL  
Termination  
Pipe Size  
1-1/2” (38MM)  
*045 and 070  
*090  
110  
2” (51MM)  
2” (51MM)  
2” (51MM)  
135  
*EL296UHE-045, -070 and -090 units with the flush mount termination must  
use the 1-1/2”accelerator supplied with the kit.  
Page 28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7 - If intake and exhaust piping must be run up a side wall  
to position above snow accumulation or other ob-  
structions, piping must be supported every 24”  
(610MM) as shown in figures 36 and 37. In addition,  
close coupled wall termination kits must be extended  
for use in this application. See figures 44 and 45.  
When exhaust and intake piping must be run up an  
outside wall, the exhaust piping must be terminated  
with pipe sized per table 8.The intake piping may be  
equipped with a 90° elbow turndown. Using turndown  
will add 5 feet (1.5m) to the equivalent length of the  
pipe.  
8 - A multiple furnace installation may use a group of up to  
four terminations assembled together horizontally, as  
Alternate Terminations  
(Tee & Forty-Five Degree Elbows Only)  
B
B
D
D
C
3
Intake  
C
1
Front View of  
Intake and Exhaust  
A
Exhaust  
A
2
Intake  
Exhaust  
TABLE 9  
2” (51MM)  
Vent Pipe  
D
3” (76MM)  
Vent Pipe  
1
A- Clearance above  
grade or average snow  
accumulation  
E
12” (305MM) Min.  
12” (305MM) Min.  
B
B-Horizontal  
separation between  
intake and exhaust  
6” (152MM) Min. 6” (152MM) Min.  
24” (610MM) Max 24” (610MM) Max  
12”  
C-Minimum from  
end of exhaust to  
inlet of intake  
9” (227MM) Min. 9” (227MM) Min.  
C
2
12” (305MM) Min.  
16” (405MM) Max.  
12” (305MM) Min.  
20” (508MM) Max.  
D-Exhaust pipe length  
A
E-Wall support distance  
from top of each pipe  
(intake/exhaust)  
6” (152MM) Max. 6” (152MM) Max.  
1
The exhaust termination tee should be connected to the 2” or 3” PVC flue pipe as shown in the illustration. Do  
not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.  
As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent  
2
termination is used and flue gases will impinge on the building materials, a corrosion-resistant shield (24 inches  
square) should be used to protect the wall surface. If optional tee is used, the protective shield is recommende-  
d. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints,  
cracks, etc. in affected area, should be sealed using an appropriate sealant.  
3
Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away  
from adjacent property. The exhaust must never be directed toward the combustion air inlet.  
FIGURE 35  
Page 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
FIELD FABRICATED WALL TERMINATION OR  
(15F74) WALL RING TERMINATION KIT  
With INTAKE ELBOW  
FIELD FABRICATED WALL TERMINATION OR  
(15F74) WALL RING TERMINATION KIT  
NOTE - FIELD-PROVIDED  
REDUCER MAY BE  
NOTE - FIELD-PROVIDED  
REDUCER MAY BE  
REQUIRED TO ADAPT  
LARGER VENT PIPE SIZE  
TO TERMINATION  
1/2” (13MM) ARMAFLEX  
INSULATION IN UN-  
CONDITIONED SPACE  
1/2” (13MM) ARMAFLEX  
REQUIRED TO ADAPT  
INSULATION IN UN-  
LARGER VENT PIPE SIZE  
CONDITIONED SPACE  
TO TERMINATION  
SIZE TERMINATION  
SIZE TERMINATION  
D
B
D
B
STRAIGHT  
APPPLICATION  
A
STRAIGHT  
APPPLICATION  
C
C
A
1/2” (13MM) ARMAFLEX INSULATION  
IN UNCONDITIONED SPACE  
1/2” (13MM) ARMAFLEX INSULATION  
IN UNCONDITIONED SPACE  
D
D
E
* WALL  
SUPPORT  
E
* WALL  
SUPPORT  
B
B
A
A
EXTENDED  
APPLICATION  
C
C
EXTENDED  
APPLICATION  
See venting table 5 for maximum venting lengths with this  
arrangement.  
See venting table 5 for maximum venting lengths with this  
arrangement.  
* Use wall support every 24” (610MM). Use two wall supports if  
extension is greater than 24” (610MM) but less than 48” (1219 MM).  
NOTE - One wall support must be 6” (152MM) from top of each pipe  
(intake and exhaust)  
* Use wall support every 24” (610MM). Use two wall supports if  
extension is greater than 24” (610MM) but less than 48” (1219 MM).  
NOTE - One wall support must be 6” (152MM) from top of each pipe  
(intake and exhaust)  
2” (51MM)  
Vent Pipe  
3” (76MM)  
Vent Pipe  
2” (51MM)  
Vent Pipe  
3” (7MM)  
Vent Pipe  
A-Minimum clearance  
above grade or average  
snow accumulation  
A-Minimum clearance  
above grade or average  
snow accumulation  
12” (305MM)  
12” (305MM)  
12” (305MM)  
6” (152MM)  
8” (203MM)  
12” (305MM)  
6” (152MM)  
8” (203MM)  
B-Maximum horizontal  
separation between  
intake and exhaust  
B-Maximum horizontal  
separation between  
intake and exhaust  
6” (152MM)  
6” (152MM)  
C-Minimum from  
end of exhaust to  
inlet of intake  
C-Minimum from  
end of exhaust to  
inlet of intake  
6” (152MM)  
20” (508MM)  
6” (152MM)  
6” (152MM)  
12” (305MM)  
6” (152MM)  
D-Maximum exhaust  
pipe length  
D-Maximum exhaust  
pipe length  
12” (305MM)  
6” (152MM)  
20” (508MM)  
6” (152MM)  
E-Maximum wall support  
distance from top of each  
pipe (intake/exhaust)  
E-Maximum wall support  
distance from top of each  
pipe (intake/exhaust)  
FIGURE 37  
FIGURE 36  
Page 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2” EXTENSION FOR 2” PVC  
PIPE1” EXTENSION FOR 3”  
PVC PIPE  
12”  
(305MM)  
5-1/2”  
(140mm)  
EXHAUST  
VENT  
FURNACE  
EXHAUST  
PIPE  
5”  
(127MM)  
4''  
INTAKE  
AIR  
18” MAX.  
(457MM)  
FURNACE  
INTAKE  
PIPE  
Front View  
NT  
12” (305MM) Min.  
above grade or  
average snow  
accumulation.  
GLUE EXHAUST  
END FLUSH INTO  
TERMINATION  
Inches (MM)  
AKE  
IR  
FLAT  
SIDE  
1-1/2” ACCELERATOR  
(all -45, -070 and -090 units)  
optional intake elbow  
FLUSH-MOUNT SIDE WALL TERMINATION  
51W11 (US) or 51W12 (Canada)  
Side View  
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT  
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT  
(22G44, 44J40, 30G28 or 81J20)  
FIGURE 38  
FIGURE 41  
1 1/2” (38mm) accelerator  
EXHAUST VENT  
provided on 71M80 & 44W92  
kits for EL296UH045E36B, &  
070E36B  
Front View  
EXHAUST  
VENT  
SIZE  
TERMINATION  
PIPE PER  
FLASHING  
(Not Furnished)  
INTAKE  
AIR  
12” (305mm)  
INTAKE  
AIR  
Minimum  
Above Average  
Snow  
Top View  
1/2” (13MM) Foam Insulation  
in Unconditioned Space  
Accumulation  
FIELD-  
PROVIDED  
SHEET METAL STRAP  
EXHAUST VENT  
REDUCER MAY  
(Clamp and sheet metal strap  
must be field installed to support  
the weight of the termination kit.)  
BE REQUIRED  
TO ADAPT  
LARGER VENT  
INTAKE AIR  
CLAMP  
PIPE SIZE TO  
TERMINATION  
FIELD-PROVIDED  
6 (152MM) MIN.  
REDUCER MAY BE REQUIRED  
TO ADAPT LARGER VENT  
PIPE SIZE TO TERMINATION  
OUTSIDE WALL  
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION  
71M80, 69M29 or 60L46 (US)  
44W92 or 44W93 (Canada)  
DIRECT VENT WALL TERMINATION KIT  
(30G28 or 81J20)  
FIGURE 42  
FIGURE 39  
EXHAUST VENT  
Front View  
SIZE  
TERMINATION  
PIPE PER  
FIELD-PROVIDED  
REDUCER MAY BE REQUIRED  
TO ADAPT LARGER VENT  
PIPE SIZE TO TERMINATION  
1-1/2” (38mm) accelerator  
provided on 71M80 & 44W92  
kits for EL296UH045E36B, &  
070E36B  
INTAKE  
AIR  
OUTSIDE  
INTAKE  
WALL  
AIR  
1/2” (13MM) Foam Insulation  
in Unconditioned Space  
Top View  
EXHAUST  
VENT  
EXHAUST  
VENT  
FIELD-  
PROVIDED  
REDUCER MAY  
BE REQUIRED  
EXHAUST VENT  
TO ADAPT  
INTAKE AIR  
LARGER VENT  
12” (305mm) Min.  
above grade or  
average snow  
accumulation.  
INTAKE  
AIR  
INTAKE  
AIR  
CLAMP  
(Not Furnished)  
PIPE SIZE TO  
TERMINATION  
8” (206MM) MIN.  
GRADE  
DIRECT VENT CONCENTRIC WALL TERMINATION  
71M80, 69M29 or 60L46 (US)  
44W92 or 44W93 (Canada)  
OUTSIDE WALL  
DIRECT VENT WALL TERMINATION KIT  
(22G44 or 44J40)  
FIGURE 40  
FIGURE 43  
Page 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
WALL TERMINATION KITS (CLOSE−COUPLE)  
EXTENDED VENT FOR GRADE CLEARANCE  
2 inch (51 mm) 22G44 (US)  
3 inch (76 mm) 44J40 (US)  
If intake and exhaust pipe is less than 12 in. (305 MM)  
above snow accumulation or other obstructions, field−  
fabricated piping must be installed.  
FIELD-PROVIDED  
REDUCER MAY BE REQUIRED TO ADAPT  
LARGER VENT PIPE SIZE TO TERMINATION  
8” (203mm) Min. for 2” (51MM) & 3” (76MM) DIA. pipe  
between the end of the exhaust pipe and intake pipe  
12” (305MM) Max. for 2” (51MM) Dia. Exhaust  
20” (508MM) Max. for 3” (76MM) Dia. Exhaust  
WALL SUPPORT*  
12”  
(305 mm)  
EXHAUST  
AIR  
1/2” (13 mm)  
FOAM INSULATION  
(Field−Furnished)  
6” (152 MM)  
Maximum  
INTAKE  
AIR  
EXHAUST  
AIR  
INTAKE  
AIR  
5” (127 mm)  
12” (305 MM) Minimum  
8” (203 mm) Min.  
12” (305MM) Minimum  
Above Grade or Average  
Snow Accumulation  
Above Grade or Average  
5−1/2”  
(140 mm)  
Snow Accumulation  
GRADE  
GRADE  
*Use wall support every 24” (610). Use two supports if  
extension is greater than 24” but less than 48”.  
12” (305 MM) Max. for 2” (51MM) Dia. Exhaust  
20” (508MM) Max. for 3” (76MM) Dia. Exhaust  
FIGURE 44  
WALL TERMINATION KITS (CLOSE−COUPLE)  
EXTENDED VENT FOR GRADE CLEARANCE  
2 inch (51 mm) 30G28 (WTK Canada)  
3 inch (76 mm) 81J20 (WTK Canada)  
See Installation Instructions for additional information.  
If intake and exhaust pipe is less than 12 in. (305 MM)  
above snow accumulation or other obstructions, field−  
fabricated piping must be installed.  
FIELD-PROVIDED  
REDUCER MAY BE REQUIRED TO ADAPT  
LARGER VENT PIPE SIZE TO TERMINATION  
WALL SUPPORT*  
12” (305 MM) Max. for 2” (51 MM) Dia. Exhaust  
20” (508 MM) Max. for 3” (76 MM) Dia. Exhaust  
12”  
(305 mm)  
EXHAUST  
AIR  
1/2” (13 mm)  
FOAM INSULATION  
(Field−Furnished)  
6” (152 MM)  
Maximum  
INTAKE  
AIR  
6” (152 MM)  
Minimum  
EXHAUST  
AIR  
INTAKE  
AIR  
5” (127 mm)  
12” (305 MM) Minimum  
Above Grade or Average  
Snow Accumulation  
6” (152 MM)  
Minimum  
12” (305 MM) Minimum  
Above Grade or Average  
Snow Accumulation  
GRADE  
5−1/2”  
(140 mm)  
GRADE  
*Use wall support every 24” (610). Use two supports if  
extension is greater than 24” but less than 48”.  
12” (305 MM) Max. for 2” (51 MM) Dia. Exhaust  
20” (508 MM) Max. for 3” (76 MM) Dia. Exhaust  
FIGURE 45  
Page 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
EL296UHE DIRECT VENT APPLICATION  
USING EXISTING CHIMNEY  
12” (305MM) MAX. for 2” (51MM)  
20” (508MM) MAX. for 3” (76MM)  
1/2” (13MM) ARMAFLEX  
INSULATION IN  
UNCONDITIONED SPACE  
STRAIGHT-CUT OR  
ANGLE-CUT IN DIRECTION  
OF ROOF SLOPE *  
3”-8”  
(76MM-203MM)  
1/2” (13MM)  
ARMAFLEX  
INSULATION  
FIELD-PROVIDED  
REDUCER MAY  
BE REQUIRED TO  
ADAPT LARGER  
VENT PIPE SIZE  
TO TERMINATION  
EXHAUST VENT  
1/2” (13MM)  
WEATHERPROOF  
INSULATION  
8” - 12”  
(203MM - 305MM)  
PVC REDUCER  
12” MIN.  
(305MM)  
Above Grade or  
average snow  
accumulation  
SHOULDER OF FITTINGS  
PROVIDE SUPPORT  
OF PIPE ON TOP PLATE  
Minimum 12” (305MM)  
INTAKE PIPE  
INSULATION (optional)  
SIZE TERMINATION  
PIPE PER TABLE 8.  
above chimney top  
plate or average snow  
accumulation  
SHEET  
METAL TOP  
PLATE  
ALTERNATE  
INTAKE PIPE  
3” - 8”  
(76MM-  
203MM)  
NON-DIRECT VENT FIELD SUPPLIED WALL TERMINATION OR  
(15F74) WALL TERMINATION KIT  
INSULATE  
TO FORM  
SEAL  
EXTERIOR  
PORTION OF  
CHIMNEY  
FIGURE 48  
3 - If exhaust piping must be run up a side wall to position  
above snow accumulation or other obstructions, pip-  
ing must be supported every 24 inches (610MM) as  
up an outside wall, any reduction in exhaust pipe size  
must be done after the final elbow.  
*SIZE TERMINATION  
PIPE PER TABLE 8.  
NOTE - Do not discharge exhaust gases directly into any chimney or vent stack. If ver-  
tical discharge through an existing unused chimney or stack is required, insert piping  
inside chimney until the pipe open end is above top of chimney and terminate as illus-  
trated. In any exterior portion of chimney, the exhaust vent must be insulated.  
FIGURE 46  
12” (305MM) MAX. for 2” (51MM)  
20” (508MM) MAX. for 3” (76MM)  
UNCONDITIONED  
SPACE  
Details of Exhaust Piping Terminations for Non‐Direct  
Vent Applications  
Exhaust pipes may be routed either horizontally through an  
outside wall or vertically through the roof. In attic or closet  
installations, vertical termination through the roof is pre-  
1 - Exhaust piping must terminate straight out or up as  
shown. The termination pipe must be sized as listed in  
table 8.The specified pipe size ensures proper veloc-  
ity required to move the exhaust gases away from the  
building.  
6” (152MM)  
Max  
SIZE TER-  
MINATION  
PIPE PER  
*WALL SUPPORT  
OUTSIDE WALL  
FIELD-PROVIDED  
12” (305MM)  
REDUCER MAY BE  
REQUIRED TO  
ADAPT LARGER  
VENT PIPE SIZE TO  
TERMINATION  
ABOVE GRADE OR  
AVERAGE SNOW  
ACCUMULATION  
1/2” (13MM) FOAM  
INSULATION IN  
UNCONDITIONED  
SPACE  
2 - On field supplied terminations for side wall exit, ex-  
haust piping may extend a maximum of 12 inches  
(305MM) for 2” PVC and 20 inches (508MM) for 3”  
1/2” (13MM) FOAM  
INSULATION  
NON-DIRECT VENT FIELD SUPPLIED WALL TERMINATION  
EXTENDED OR (15F74) WALL TERMINATION VENT PIPE  
EXTENDED  
*Use wall support every 24” (610). Use two supports if extension is  
greater than 24” but less than 48”.  
SIZE TERMINATION  
PIPE PER TABLE 8.  
12” (305MM)  
ABOVE AVE.  
SNOW  
ACCUMULATION  
FIGURE 49  
1/2” (13MM) FOAM  
INSULATION  
3” (76MM) OR  
2” (51MM) PVC  
UNCONDITIONED  
ATTIC SPACE  
PROVIDE SUPPORT  
FOR EXHAUST LINES  
NON-DIRECT VENT ROOF TERMINATION KIT  
(15F75 or 44J41)  
FIGURE 47  
Page 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
CONDENSATE TRAP AND PLUG LOCATIONS  
(Unit shown in upflow position)  
Trap  
EL296UHE NON-DIRECT VENT APPLICATION  
USING EXISTING CHIMNEY  
STRAIGHT-CUT OR  
ANGLE-CUT IN DIRECTION  
OF ROOF SLOPE  
SIZE TERMINATION  
PIPE PER TABLE 8.  
(same on  
right side)  
1-1/2 in.  
EXHAUST VENT  
1/2” (13MM)  
WEATHERPROOF  
Minimum 12” (305MM)  
above chimney top  
INSULATION  
plate or average snow  
accumulation  
Plug  
(same on left side)  
SHOULDER OF FITTINGS  
PROVIDE SUPPORT  
OF PIPE ON TOP PLATE  
SHEET  
METAL TOP  
PLATE  
INSULATE  
TO FORM  
SEAL  
EXTERIOR  
PORTION OF  
CHIMNEY  
NOTE - In upflow applications where side return  
air filter is installed on same side as the conden-  
sate trap, filter rack must be installed beyond  
condensate trap or trap must be re-located to  
avoid interference.  
NOTE - Do not discharge exhaust gases directly into any chimney or vent stack. If ver-  
tical discharge through an existing unused chimney or stack is required, insert piping  
inside chimney until the pipe open end is above top of chimney and terminate as illus-  
trated. In any exterior portion of chimney, the exhaust vent must be insulated.  
FIGURE 50  
Condensate Piping  
This unit is designed for either right‐ or left‐side exit of con-  
densate piping in upflow applications. In horizontal applica-  
tions, the condensate trap must extend below the unit. An  
8” service clearance is required for the condensate trap.  
Refer to figures 51 and 53 for condensate trap locations.  
PVC.  
FIGURE 51  
coil using a separate drain. If necessary the conden-  
sate line from the furnace and evaporator coil can  
NOTE - If necessary the condensate trap may be installed  
up to 5’ away from the furnace. Use PVC pipe to connect  
trap to furnace condensate outlet. Piping from furnace  
must slope down a minimum of 1/4” per ft. toward trap.  
Upflow furnace (figure 57) - In upflow furnace applica-  
tions the field provided vent must be a minimum 1” to a  
maximum 2” length above the condensate drain outlet  
connection. Any length above 2” may result in a  
flooded heat exchanger if the combined primary drain  
line were to become restricted.  
1 - Determine which side condensate piping will exit the  
unit, location of trap, field-provided fittings and length of  
PVC pipe required to reach available drain.  
Horizontal furnace (figure 58) - In horizontal furnace  
applications the field provided vent must be a mini-  
mum 4” to a maximum 5” length above the condensate  
drain outlet connection. Any length above 5” may re-  
sult in a flooded heat exchanger if the combined pri-  
mary drain line were to become restricted.  
2 - Use a large flat head screw driver or a 1/2” drive socket  
extension and remove plug (figure 51) from the cold  
end header box at the appropriate location on the side  
of the unit. Install provided 3/4 NPT street elbow fitting  
into cold end header box. Use Teflon tape or appropri-  
ate pipe dope.  
3 - Install the cap over the clean out opening at the base  
NOTE - In horizontal applications it is recommended to  
install a secondary drain pan underneath the unit and  
trap assembly.  
4 - Install drain trap using appropriate PVC fittings, glue  
all joints. Glue the provided drain trap as shown in fig-  
Condensate line must maintain a 1/4” downward slope  
from the furnace to the drain.  
NOTE - Appropriately sized tubing and barbed fitting  
may be used for condensate drain. Attach to the drain  
Page 34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Field Provided Drain Components  
EL296UHE With Evaporator  
Coil Using A Separate Drain  
Evaporator drain  
line required  
Elbow  
Field Provided Vent  
(1” min. 2” max. above  
condensate connection)  
Barbed Fitting  
Hose Clamp  
FIGURE 52  
Tubing  
Condensate  
DrainConnection  
CAUTION  
Donot use copper tubing or existing copper conden-  
sate lines for drain line.  
6 - If unit will be started immediately upon completion of  
installation, prime trap per procedure outlined in Unit  
Start-Up section.  
FIGURE 54  
Condensate line must slope downward away from the  
trap to drain. If drain level is above condensate trap,  
condensate pump must be used. Condensate drain  
line should be routed within the conditioned space to  
avoid freezing of condensate and blockage of drain  
line. If this is not possible, a heat cable kit may be used  
on the condensate trap and line. Heating cable kit is  
available from Lennox in various lengths; 6 ft. (1.8m) -  
kit no. 26K68; 24 ft. (7.3m) - kit no. 26K69; and 50 ft.  
(15.2m) - kit no. 26K70.  
CONDENSATE TRAP LOCATIONS  
(Unit shown in upflow position with remote trap)  
Condensate Trap With Optional Overflow Switch  
From Evaporator Coil  
Horizontal Furnace Min.to 5” Max.above  
4”  
FieldProvidedVent  
Min.1” AboveCondensate  
DrainConnection  
condensate drain connection)  
1” Min.  
2” Max.  
FurnaceCondensate  
DrainConnection  
*5’ max.  
PVCPipeOnly  
Optional  
Trap can be installed a  
maximum 5' from furnace  
To Drain  
*Piping from furnace must slope down a minimum of  
1/4” per ft. toward trap.  
FIGURE 55  
FIGURE 53  
Page 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
EL296UHE with Evaporator Coil Using a Separate Drain  
(Unit shown in horizontal left-hand discharge position)  
Field Provided Vent  
(4” min. to 5” max. above  
condensate connection)  
Evaporator  
Coil  
4”min  
5”max  
5’ max.  
PVC Pipe Only  
Condensate  
DrainConnection  
Drain Pan  
Piping from furnace and evaporator coil must slope down a minimum 1/4” per ft. toward trap  
.
FIGURE 56  
EL296UHE with Evaporator  
Coil Using a Common Drain  
IMPORTANT  
Evaporator drain  
line required  
When combining the furnace and evaporator  
coil drains together, the A/C condensate drain  
outlet must be vented to relieve pressure in or-  
der for the furnace pressure switch to operate  
properly.  
(1min. to 2” Max.above  
condensate drain connection)  
Condensate  
DrainConnection  
FIGURE 57  
EL296UHE with Evaporator Coil Using a Common Drain  
(Unit shown in horizontal left−hand discharge position)  
(4min. to 5” Max.above  
condensate drain connection)  
Evaporator  
Coil  
4”min  
5”max  
5’ max.  
PVC Pipe Only  
Condensaet Drain  
Connection  
Drain Pan  
Piping from furnace and evaporator coil must slope down a minimum 1/4” per ft. toward trap  
FIGURE 58  
Page 36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TRAP / DRAIN ASSEMBLY USING 1/2” PVC OR 3/4” PVC  
Optional Condensate Drain Connection  
Adapter 3/4 inch slip X  
3/4 inch mpt (not furnished)  
90° Street Elbow  
3/4 inch PVC  
(not furnished)  
Adapter 3/4 inch slip X  
3/4 inch mpt (not furnished)  
Condensate Drain  
Connection In Unit  
1 (25 mm) Min.  
2 (50 mm) Max.  
Above Top Of  
Condensate Drain  
Connection In Unit  
Vent  
5 Feet  
Maximum  
Condensate Drain  
Connection In Unit  
90° Street Elbow  
3/4 inch PVC  
( furnished)  
90° Elbow 3/4 inch PVC  
(Not Furnished)  
To  
Trap  
3/4 inch PVC Pipe  
(Not Furnished)  
1/2 inch PVC Pipe  
(Not Furnished)  
OptionalDrainPipingFromTrap  
Coupling 3/4 inch slip X slip  
(Not Furnished)  
Drain Assembly for 1/2 inch Drain Pipe  
1/2 inch PVC Pipe  
(Not Furnished)  
Drain Trap  
Assembly  
(Furnished)  
90° Elbow  
1/2 inch PVC  
(Not Furnished)  
To  
Drain  
Drain Assembly for 3/4 inch Drain Pipe  
Drain Trap  
Clean Out  
90° Elbow  
90° Elbow  
3/4 inch PVC  
(Not Furnished)  
3/4 inch PVC  
(Not Furnished)  
To  
Drain  
To  
Drain  
Coupling 3/4 inch slip X slip  
(Not Furnished)  
DrainTrap Assembly with 3/4 inch Piping  
DrainTrap Assembly with 1/2 inch Piping  
1 (25 mm) Min. 2 (50 mm) Max. Above Top  
Of Condensate Drain Connection In Unit  
1 (25 mm) Min. 2 (50 mm) Max. Above Top  
Of Condensate Drain Connection In Unit  
Vent  
DrainTrapAssembly  
(Furnished)  
Vent  
3/4 inch  
1/2 inch  
7
Condensate Drain  
Connection In Unit  
Condensate Drain  
Connection In Unit  
(178)  
To  
Drain  
To  
Drain  
FIGURE 59  
Page 37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
6 - In some localities, codes may require installation of a  
manual main shut‐off valve and union (furnished by in-  
staller) external to the unit. Union must be of the  
ground joint type.  
Gas Piping  
Gas supply piping should not allow more than 0.5”W.C. drop  
in pressure between gas meter and unit. Supply gas pipe  
must not be smaller than unit gas connection.  
IMPORTANT  
Compounds used on threaded joints of gas piping  
must be resistant to the actions of liquified petro-  
leum gases.  
CAUTION  
If a flexible gas connector is required or allowed by  
the authority that has jurisdiction, black iron pipe  
shall be installed at the gas valve and extend outside  
the furnace cabinet. The flexible connector can then  
be added between the black iron pipe and the gas  
supply line.  
Leak Check  
After gas piping is completed, carefully check all piping  
connections (factory- and field-installed) for gas leaks. Use  
a leak detecting solution or other preferred means.  
Never use an open flame to test for gas leaks. Check all  
connections using a commercially available soap solution  
made specifically for leak detection.  
The furnace must be isolated from the gas supply system  
by closing its individual manual shut‐off valve during any  
pressure testing of the gas supply system at pressures  
greater than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).  
WARNING  
Do not exceed 600 in-lbs (50 ft-lbs) torque when at-  
taching the gas piping to the gas valve.  
MANUAL MAIN SHUT-OFF  
VALVE WILL NOT HOLD  
NORMAL TEST PRESSURE  
CAP  
FURNACE  
1 - Gas piping may be routed into the unit through either  
the left‐ or right‐hand side. Supply piping enters into  
the gas valve from the side of the valve as shown in  
ISOLATE  
GAS VALVE  
1/8” N.P.T.  
PLUGGED TAP  
2 - When connecting gas supply, factors such as length of  
run, number of fittings and furnace rating must be con-  
sidered to avoid excessive pressure drop. Table 10  
lists recommended pipe sizes for typical applications.  
FIGURE 60  
NOTE - Use two wrenches when connecting gas pip-  
ing to avoid transferring torque to the manifold.  
IMPORTANT  
When testing pressure of gas lines, gas valve must  
valves can be damaged if subjected to pressures  
greater than 1/2 psig (3.48 kPa).  
3 - Gas piping must not run in or through air ducts, clothes  
chutes, chimneys or gas vents, dumb waiters or eleva-  
tor shafts. Center gas line through piping hole. Gas  
4 - Piping should be sloped 1/4 inch per 15 feet (6mm per  
5.6m) upward toward the gas meter from the furnace.  
The piping must be supported at proper intervals, ev-  
ery 8 to 10 feet (2.44 to 3.05m), using suitable hangers  
or straps. Install a drip leg in vertical pipe runs to serve as  
a trap for sediment or condensate.  
WARNING  
FIRE OR EXPLOSION HAZARD  
Failure to follow the safety warnings exactly could  
result in serious injury, death, or property damage.  
Never use an open flame to test for gas leaks. Check  
all connections using a commercially available soap  
solution made specifically for leak detection. Some  
soaps used for leak detection are corrosive to cer-  
tain metals. Carefully rinse piping thoroughly after  
leak test has been completed.  
5 - A 1/8” N.P.T. plugged tap or pressure post is located  
on the gas valve to facilitate test gauge connection.  
Page 38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Left Side Piping  
(Standard)  
Right Side Piping  
(Alternate)  
MANUAL  
MAIN SHUT-OFF  
VALVE  
MANUAL  
MAIN SHUT-OFF  
VALVE  
GROUND  
JOINT  
UNION  
GROUND  
JOINT  
UNION  
DRIP LEG  
Gas Valve  
Gas Valve  
DRIP LEG  
FIELD  
PROVIDED  
AND INSTALLED  
NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET  
FIGURE 61  
Horizontal Applications  
Possible Gas Piping Configurations  
MANUAL  
MAIN SHUT-OFF  
VALVE  
Horizontal Application  
Left-Side Air Discharge  
MANUAL  
MAIN SHUT-OFF  
VALVE  
GROUND  
JOINT  
UNION  
GROUND  
JOINT  
UNION  
DRIP LEG  
DRIP LEG  
Gas Valve  
Horizontal Application  
Right-Side Air Discharge  
MANUAL  
MAIN SHUT-OFF  
VALVE  
Gas Valve  
GROUND  
JOINT  
UNION  
FIELD  
PROVIDED  
AND INSTALLED  
DRIP LEG  
NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET  
FIGURE 62  
Page 39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE 10  
GAS PIPE CAPACITY - FT3/HR (kL/HR)  
Nominal  
Iron Pipe  
Size  
inches  
(mm)  
Length of Pipe - feet (m)  
Internal  
Diameter  
inches  
(mm)  
10  
(3.048)  
20  
(6.096)  
30  
(9.144)  
40  
50  
60  
70  
80  
90  
100  
(12.192) (15.240) (18.288) (21.336) (24.384) (27.432) (30.480)  
1/2  
(12.7)  
.622  
(17.799)  
172  
(4.87)  
118  
(3.34)  
95  
(2.69)  
81  
(2.29)  
72  
(2.03)  
65  
(1.84)  
60  
(1.69)  
56  
(1.58)  
52  
(1.47)  
50  
(1.42)  
3/4  
(19.05)  
.824  
(20.930)  
360  
(10.19)  
247  
(7.00)  
199  
(5.63)  
170  
(4.81)  
151  
(4.28)  
137  
(3.87)  
126  
(3.56)  
117  
(3.31)  
110  
(3.11)  
104  
(2.94)  
1
(25.4)  
1.049  
(26.645)  
678  
(19.19)  
466  
(13.19)  
374  
(10.59)  
320  
(9.06)  
284  
(8.04)  
257  
(7.27)  
237  
(6.71)  
220  
(6.23)  
207  
(5.86)  
195  
(5.52)  
1-1/4  
(31.75)  
1.380  
(35.052)  
1350  
(38.22)  
957  
(27.09)  
768  
(22.25)  
657  
(18.60)  
583  
(16.50)  
528  
(14.95)  
486  
(13.76)  
452  
(12.79)  
424  
(12.00)  
400  
(11.33)  
1-1/2  
(38.1)  
1.610  
(40.894)  
2090  
(59.18)  
1430  
(40.49)  
1150  
(32.56)  
985  
(27.89)  
873  
(24.72)  
791  
(22.39)  
728  
(20.61)  
677  
(19.17)  
635  
(17.98)  
600  
(17.00)  
2
(50.8)  
2.067  
(52.502)  
4020  
(113.83)  
2760  
(78.15)  
2220  
(62.86)  
1900  
(53.80)  
1680  
(47.57)  
1520  
(43.04)  
1400  
(39.64)  
1300  
(36.81)  
1220  
(34.55)  
1160  
(32.844)  
2-1/2  
(63.5)  
2.469  
(67.713)  
6400 4400  
(181.22) (124.59)  
3530  
(99.95)  
3020  
(85.51)  
2680  
(75.88)  
2480  
(70.22)  
2230  
(63.14)  
2080  
(58.89)  
1950  
(55.22)  
1840  
(52.10)  
3
(76.2)  
3.068  
(77.927)  
11300 7780  
(319.98) (220.30) (176.98) (151.49) (134.22) (121.47) (111.85) (103.92)  
6250  
5350  
4740  
4290  
3950  
3670  
3450  
(97.69)  
3260  
(92.31)  
NOTE - Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.  
The unit is equipped with a field make-up box. The make-  
up box may be moved to the right side of the furnace to fa-  
cilitate installation. Secure the excess wire to the existing  
harness to protect it from damage.  
Electrical  
ELECTROSTATIC DISCHARGE (ESD)  
Refer to figure 64 for field wiring, schematic wiring diagram  
and troubleshooting.  
Precautions and Procedures  
The power supply wiring must meet Class I restrictions.  
Protected by either a fuse or circuit breaker, select circuit  
protection and wire size according to unit nameplate.  
CAUTION  
Electrostatic discharge can affect elec-  
tronic components. Take precautions  
to neutralize electrostatic charge by  
touching your hand and tools to metal  
prior to handling the control.  
NOTE - Unit nameplate states maximum current draw.  
Maximum Over-Current Protection allowed is 15 AMP.  
Holes are on both sides of the furnace cabinet to facilitate  
wiring.  
Install a separate (properly sized) disconnect switch near  
the furnace so that power can be turned off for servicing.  
INTERIOR MAKE-UP BOX INSTALLATION  
Before connecting the thermostat check to make sure the  
wires will be long enough for servicing at a later date. Make  
sure that thermostat wire is long enough to facilitate future  
removal of blower for service.  
remove and relocate  
plug to unused  
opening on left side  
MAKE-UP  
BOX  
Complete the wiring connections to the equipment. Use the  
provided unit wiring diagram and the field wiring diagram  
shown in figure 64. Use 18-gauge wire or larger that is suit-  
able for Class II rating for thermostat connections.  
Electrically ground the unit according to local codes or, in  
the absence of local codes, according to the current Na-  
tional Electric Code (ANSI/NFPA No. 70) for the USA and  
current Canadian Electric Code part 1 (CSA standard  
C22.1) for Canada. A green ground wire is provided in the  
field make-up box.  
Right Side  
NOTE - The EL296UHE furnace contains electronic  
components that are polarity sensitive. Make sure that the  
furnace is wired correctly and is properly grounded.  
FIGURE 63  
Page 40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Accessory Terminals  
D The furnace integrated control requires both polarity  
and proper ground. Both polarity and proper grounding  
should be checked before attempting to operate the  
furnace on either permanent or temporary power.  
D Generator should have a wave form distortion of less  
than 5% THD (total harmonic distortion).  
One line voltage “ACC” 1/4” spade terminal is provided on  
control configuration. This terminal is energized when the  
indoor blower is operating. Any accessory rated up to one  
amp can be connected to this terminal with the neutral leg  
of the circuit being connected to one of the provided neutral  
terminals. If an accessory rated at greater than one amp is  
connected to this terminal, it is necessary to use an exter-  
nal relay.  
On-Board Links and Diagnostic Push  
WARNING  
Carefully review all configuration information pro-  
vided. Failure to properly set DIP switches, jumpers  
and on-board links can result in improper operation!  
An unpowered, normally open (dry) set of contacts with a  
1/4” spade terminal “HUM” are provided for humidifier con-  
nections and may be connected to 24V or 120V. Any hu-  
midifier rated up to one amp can be connected to these ter-  
minals. In 120V humidifier applications the neutral leg of  
the circuit can be connected to one of the provided neutral  
terminals. This terminal is energized in the heating mode.  
On-Board Link W914 Dehum  
On-board link W914, is a clippable connection between ter-  
minals R and DS on the integrated control. W914 must be  
cut when the furnace is installed with a thermostat which  
features humidity control. If the link is not cut, terminal “DS”  
will remain energized not allowing the blower to reduce to  
low cool speed upon a call for dehumidification.  
Install the room thermostat according to the instructions  
designations. If the furnace is being matched with a heat  
pump, refer to the FM21 installation instruction or appropri-  
ate dual fuel thermostat instructions.  
On-Board Link W951 Heat Pump (R to O)  
On-board link W951 is a clippable connection between ter-  
minals R and O on the integrated control. W951 must be cut  
when the furnace is installed in applications which include a  
heat pump unit and a thermostat which features dual fuel  
use. If the link is left intact, terminal “O” will remain ener-  
gized eliminating the HEAT MODE in the heat pump.  
Indoor Blower Speeds  
1 - When the thermostat is set to “FAN ON,” the indoor  
blower will run continuously on the field selectable fan  
speed (“LOW HEAT” is default) when there is no cool-  
ing or heating demand.  
On-Board Link W915 2 Stage Compr (Y1 to Y2)  
On-board link W915 is a clippable connection between ter-  
minals Y1 and Y2 on the integrated control. W915 must be  
cut if two-stage cooling will be used. If the Y1 to Y2 link is  
not cut the outdoor unit will operate in second-stage cool-  
ing only.  
2 - When the EL296UHE is running in the heating mode,  
the indoor blower will run on the 'LOW HEAT” or “HIGH  
HEAT” speed per demand.  
3 - When there is a cooling demand, the indoor blower will  
run on the “LOW COOL” or “HIGH COOL” speed per  
demand.  
Diagnostic Push Button  
The diagnostic push button is located adjacent to the  
seven-segment diagnostic LED. This button is used to en-  
able the Error Code Recall “E” mode and the Flame Signal  
“F” mode. Press the button and hold it to cycle through a  
menu of options. Every five seconds a new menu item will  
be displayed. When the button is released, the displayed  
item will be selected. Once all items in the menu have been  
displayed, the menu resumes from the beginning until the  
button is released.  
Generator Use - Voltage Requirements  
The following requirements must be kept in mind when  
specifying a generator for use with this equipment:  
D The furnace requires 120 volts + 10% (Range: 108  
volts to 132 volts).  
D The furnace operates at 60 Hz + 5% (Range: 57 Hz to  
63 Hz).  
Page 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL EL296UHE WIRING DIAGRAM  
FIGURE 64  
Page 42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Integrated Control  
HUM  
ACC  
24VAC Indoor  
Blower Terminals  
Ignitor and Combustion  
Air Inducer  
Neutrals  
Flame Sense  
LED  
S4 DIP Switches  
Diagnostic Push  
Button  
On Board Links  
THERMOSTAT CONNECTIONS (TB1)  
DS = DEHUMIDIFICATION SIGNAL  
3/16” QUICK CONNECT TERMINALS  
FLAME SENSE SIGNAL  
HI COOL 24VAC  
W2 = HEAT DEMAND FROM 2ND STAGE T/STAT  
W1 = HEAT DEMAND FROM 1ST STAGE T/STAT  
R = CLASS 2 VOLTAGE TO THERMOSTAT  
G = MANUAL FAN FROM T'STAT  
HI HEAT 24VAC  
LO COOL 24VAC  
LO HEAT 24VAC  
C = THERMOSTAT SIGNAL GROUND CONNECTED TO  
TRANSFORMER GRD (TR) & CHASIS GROUND (GRD)  
PARK  
PARK  
COMMON 24VAC  
Y1 = THERMOSTAT 1ST STAGE COOL SIGNAL  
Y2 = THERMOSTAT 2ND STAGE COOL SIGNAL  
1/4” QUICK CONNECT TERMINALS  
O = THERMOSTAT SIGNAL TO HEAT PUMP  
REVERSING VALVE  
NEUTRALS = 120 VAC NEUTRAL  
HUM = UNPOWERED NORMALLY OPEN (DRY) CONTACTS  
LI = 120 VAC INPUT TO CONTROL  
ACC = 120 VAC OUTPUT TO OPTIONAL ACCESSORY  
DH = NOT USED  
L = NOT USED  
FIGURE 65  
. . . . . . . . . . . . .  
Page 43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
is shipped from the factory with a blower-off delay of 90 se-  
conds. The blower off delay affects comfort and is adjust-  
able to satisfy individual applications. Adjust the blower off  
delay to achieve a supply air temperature between 90° and  
110°F at the exact moment that the blower is de-energized.  
Longer off delay settings provide lower supply air tempera-  
tures; shorter settings provide higher supply air temperatu-  
res.Table 11 provides the blower off timings that will result  
from different switch settings.  
Integrated Control DIP Switch Settings  
EL296UHE units are equipped with a two-stage integrated  
control. This control manages ignition timing, heating  
mode fan off delays and indoor blower speeds based on  
selections made using the control dip switches and jump-  
ers. The control includes an internal watchguard feature  
which automatically resets the ignition control when it has  
been locked out. After one hour of continuous thermostat  
demand for heat, the watchguard will break and remake  
thermostat demand to the furnace and automatically reset  
the control to relight the furnace.  
TABLE 11  
Blower Off Heating Mode Delay Switch Settings  
Blower Off Delay  
(Seconds)  
Heating Operation DIP Switch Settings  
Switch 3  
Switch 4  
Switch 1 -- Thermostat Selection -- This unit may be  
used with either a single-stage or two-stage thermostat.  
The thermostat selection is made using a DIP switch which  
must be properly positioned for the particular application.  
The DIP switch is factory-positioned for use with a two-  
stage thermostat. If a single-stage thermostat is to be used,  
the DIP switch must be repositioned.  
60  
90 (Factory)  
120  
On  
Off  
Off  
On  
Off  
Off  
On  
On  
180  
Switch 5 -- Cooling Mode Blower-Off Delay-- The unit is  
shipped from the factory with the dip switch positionedOFF  
for a 45 second delay. Table 12 provides the cooling mode  
off delay settings.  
a- Select “OFF” for two-stage heating operation con-  
trolled by a two-stage heating thermostat (factory set-  
ting);  
TABLE 12  
Blower Off Cooling Mode Delay Switch Settings  
b - Select “ON” for two-stage heating operation con-  
trolled by a single-stage heating thermostat. This set-  
ting provides a timed delay before second-stage heat  
is initiated.  
Blower Off Delay  
(Seconds)  
Switch 5  
45 (Factory)  
2
Off  
On  
Switch 2 -- Second Stage Delay (Used with Single-  
Stage Thermostat Only) -- This switch is used to deter-  
mine the second stage on delay when a single-stage ther-  
mostat is being used. The switch is factory-set in the OFF  
position, which provides a 7-minute delay before second-  
stage heat is initiated. If the switch is toggled to the ON  
position, it will provide a 12-minute delay before second-  
stage heat is initiated. This switch is only activated when  
the thermostat selector jumper is positioned for SINGLE-  
stage thermostat use.  
Switches 6 and 7 -- Continuous Fan Mode -- Continuous  
fan speed can be controlled by changing DIP switch posi-  
tions. Table 13 below provides DIP switch settings for con-  
tinuous fan mode.  
TABLE 13  
Continuous Fan Mode Settings  
Continuous Fan  
Mode  
Switch 6  
Switch 7  
Indoor Blower Operation DIP Switch Settings  
Low Heat Speed  
(factory)  
Off  
Off  
Switches 3 and 4 -- Heating Mode Blower-Off Delay --  
The blower-on delay of 30 seconds is not adjustable. The  
blower-off delay (time that the blower operates after the  
heating demand has been satisfied) can be adjusted by  
moving switches 3 and 4 on the integrated control. The unit  
Low Cool Speed  
High High Speed  
High Cool Speed  
Off  
On  
On  
On  
Off  
On  
Page 44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE 14  
EL296 Field Wiring Applications With Conventional Thermostat  
DIP Switch Settings and On-Board Links (See figure 65)  
DIP Switch 1  
On Board Links Must Be Cut To Select  
System Options  
Thermostat  
Heating  
Stages  
Thermostat  
Wiring Connections  
1 Heat / 1 Cool  
ON  
ON  
ON  
S1  
T'STAT  
FURNACE  
TERM. STRIP  
OUTDOOR  
UNIT  
NOTE - Use DIP  
switch 2 to set  
second-stage  
heat ON delay.  
OFF-7 minutes.  
ON-12 minutes.  
DO NOT CUT ANY  
ON-BOARD LINKS  
*
*Not required on all units  
1 Heat / 2 Cool  
S1  
T'STAT  
FURNACE  
TERM. STRIP  
OUTDOOR  
UNIT  
NOTE - Use DIP  
switch 2 to set  
second-stage  
heat ON delay.  
OFF-7 minutes.  
ON-12 minutes.  
CUT ON-BOARD LINK  
W915  
2 STAGE  
*
DEHUM  
COMPR  
*Not required on all units  
1 Heat / 2 Cool  
with t'stat with  
humidity control  
S1  
T'STAT  
FURNACE  
TERM. STRIP  
OUTDOOR  
UNIT  
CUT ON-BOARD LINK  
W915  
2 STAGE  
COMPR  
NOTE - Use DIP  
switch 2 to set  
second-stage  
*
heat ON delay.  
OFF-7 minutes.  
ON-12 minutes.  
CUT ON-BOARD LINK  
W914  
DEHUM  
DEHUM  
o
*Not required on all units  
Page 45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE 14  
EL296 Field Wiring Applications With Conventional Thermostat (Continued)  
DIP Switch Settings and On-Board Links (See figure 65)  
DIP Switch 1  
On Board Links Must Be Cut To Select  
System Options  
Thermostat  
Heating  
Stages  
Thermostat  
Wiring Connections  
2 Heat / 2 Cool  
OFF  
OFF  
OFF  
OFF  
S1  
T'STAT  
FURNACE  
TERM. STRIP  
OUTDOOR  
UNIT  
CUT ON-BOARD LINK  
W915  
2 STAGE  
COMPR  
*
DEHUM  
*Not required on all units  
2 Heat / 2 Cool  
with t'stat with  
humidity control  
S1  
T'STAT  
FURNACE  
TERM. STRIP UNIT  
OUTDOOR  
CUT ON-BOARD LINK  
W915  
2 STAGE  
COMPR  
*
CUT ON-BOARD LINK  
W914  
DEHUM  
*Not required on all units  
o
2 Heat / 1 Cool  
with t'stat with  
humidity control  
S1  
T'STAT  
FURNACE  
TERM. STRIP  
OUTDOOR  
UNIT  
CUT ON-BOARD LINK  
W914  
DEHUM  
*
o
*Not required on all units  
2 Heat / 1 Cool  
S1  
T'STAT  
FURNACE  
TERM. STRIP  
OUTDOOR  
UNIT  
DO NOT CUT ANY  
ON-BOARD LINKS  
*
DEHUM  
*Not required on all units  
Page 46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 14  
EL296 Field Wiring Applications With Conventional Thermostat (Continued)  
DIP Switch Settings and On-Board Links (figure 65)  
DIP Switch 1  
Wiring Connections  
Thermostat  
Heating  
Stages  
On Board Links Must Be Cut To Select  
System Options  
Thermostat  
FURNACE  
TERM. STRIP  
HEAT PUMP  
Dual Fuel  
Single Stage  
Heat Pump  
L7724U  
T'STAT  
OFF  
H
CUT ON-BOARD LINK  
W951  
HEAT  
PUMP  
ComfortSense  
7000 L7724U  
thermostat w/  
dual fuel capa-  
bilities  
67M41*  
DEHUM  
L
Y
L
Capable of 2  
stage gas heat  
control  
Y2  
D
B
Y2  
L7724U  
T'STAT  
FURNACE  
TERM. STRIP  
Dual Fuel  
Two Stage  
Heat Pump  
HEAT PUMP  
OFF  
CUT ON-BOARD LINK  
W915  
2 STAGE  
H
COMPR  
67M41*  
ComfortSense  
7000 L7724U  
thermostat w/  
dual fuel capa-  
bilities  
Capable of 2  
stage gas heat  
control  
CUT ON-BOARD LINK  
W951  
L
DEHUM  
L
HEAT  
PUMP  
Y2  
Y2  
D
B
out blue  
* Connect W1 to W1 ONLY if using defrost tempering kit 67M41  
NOTE - Do NOT make a wire connection between the room thermostat L terminal and the L terminal of the EL296  
integrated control.  
Page 47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EL296 Field Wiring Applications With Conventional Thermostat (Continued)  
DIP Switch Settings and On-Board Links (figure 65)  
DIP Switch 1  
Wiring Connections  
Thermostat  
Heating  
Stages  
On Board Links Must Be Cut To Select  
System Options  
Thermostat  
FURNACE  
TERM. STRIP  
HEAT PUMP  
Dual Fuel  
Single Stage  
Heat Pump  
L7742U  
T'STAT  
OFF  
H
CUT ON-BOARD LINK  
W951  
HEAT  
PUMP  
ComfortSense  
7000 L7742U  
thermostat w/  
dual fuel capa-  
bilities  
Capable of 2  
stage gas heat  
control w/dehu-  
midification  
control  
67M41*  
L
Y
L
CUT ON-BOARD LINK  
W914  
DEHUM  
Y2  
D
B
Y2  
FURNACE  
TERM. STRIP  
HEAT PUMP  
Dual Fuel  
Two Stage  
Heat Pump  
L7742U  
T'STAT  
CUT ON-BOARD LINK  
W915  
2 STAGE  
OFF  
COMPR  
H
ComfortSense  
7000 L7742U  
thermostat w/  
dual fuel capa-  
bilities  
Capable of 2  
stage gas heat  
control w/dehu-  
midification  
67M41*  
CUT ON-BOARD LINK  
W951  
HEAT  
PUMP  
L
L
CUT ON-BOARD LINK  
W914  
DEHUM  
Y2  
Y2  
D
B
Y2  
out blue  
* Connect W1 to W1 ONLY if using defrost tempering kit 67M41  
NOTE - Do NOT make a wire connection between the room thermostat L terminal and the L terminal of the EL296  
integrated control.  
Page 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5 - Wait for the combustion air inducer to stop. Set the  
thermostat to initiate a heating demand and again al-  
low the burners to fire for approximately 3 minutes.  
Unit Start-Up  
FOR YOUR SAFETY READ BEFORE OPERATING  
6 - Adjust the thermostat to deactivate the heating de-  
mand and wait for the combustion air inducer to stop.  
At this point, the trap should be primed with sufficient  
water to ensure proper condensate drain operation.  
WARNING  
Do not use this furnace if any part has been under-  
water. A flood-damaged furnace is extremely dan-  
gerous. Attempts to use the furnace can result in  
fire or explosion. Immediately call a qualified ser-  
vice technician to inspect the furnace and to replace  
all gas controls, control system parts, and electrical  
parts that have been wet or to replace the furnace,  
if deemed necessary.  
WARNING  
If you do not follow these instructions exactly, a fire  
or explosion may result causing property damage,  
personal injury or death.  
1 - STOP! Read the safety information at the beginning of  
this section.  
WARNING  
2 - Set the thermostat to the lowest setting.  
3 - Turn off all electrical power to the unit.  
Danger of explosion. Can cause injury  
or product or property damage. Should  
the gas supply fail to shut off or if  
overheating occurs, shut off the gas  
valve to the furnace before shutting off  
the electrical supply.  
4 - This furnace is equipped with an ignition device which  
automatically lights the burners. Do not try to light the  
burners by hand.  
5 - Remove the access panel.  
6 - Move gas valve switch to OFF. See figure 66.  
7 - Wait five minutes to clear out any gas. If you then smell  
gas, STOP! Immediately call your gas supplier from a  
neighbor's phone. Follow the gas supplier's instruc-  
tions. If you do not smell gas go to next step.  
CAUTION  
Before attempting to perform any service or mainte-  
nance, turn the electrical power to unit OFF at dis-  
connect switch.  
8 - Move gas valve switch to ON. See figure 66.  
HIGH FIRE ADJUSTMENT  
SCREW  
(under cap)  
BEFORE LIGHTING the unit, smell all around the fur-  
nace area for gas. Be sure to smell next to the floor be-  
cause some gas is heavier than air and will settle on the  
floor.  
MANIFOLD  
PRESSURE POST  
INLET PRESSURE POST  
The gas valve on the EL296UHE is equipped with a gas  
control switch (lever). Use only your hand to move  
switch. Never use tools. If the the switch will not move by  
hand, do not try to repair it. Force or attempted repair may  
result in a fire or explosion.  
Placing the furnace into operation:  
EL296UHE units are equipped with an automatic hot sur-  
face ignition system. Do not attempt to manually light  
burners on this furnace. Each time the thermostat calls  
for heat, the burners will automatically light. The ignitor  
does not get hot when there is no call for heat on these  
units.  
GAS VALVE SHOWN IN ON POSITION  
FIGURE 66  
9 - Replace the access panel.  
10- Turn on all electrical power to to the unit.  
11- Set the thermostat to desired setting.  
Priming Condensate Trap  
NOTE - When unit is initially started, steps 1 through 11  
The condensate trap should be primed with water prior to  
start-up to ensure proper condensate drainage. Either  
pour 10 fl. oz. (300 ml) of water into the trap, or follow  
these steps to prime the trap:  
may need to be repeated to purge air from gas line.  
12- If the appliance will not operate, follow the instructions  
“Turning Off Gas to Unit” and call your service techni-  
cian or gas supplier.  
1 - Follow the lighting instructions to place the unit into op-  
eration.  
Turning Off Gas to Unit  
2 - Set the thermostat to initiate a heating demand.  
1 - Set the thermostat to the lowest setting.  
3 - Allow the burners to fire for approximately 3 minutes.  
2 - Turn off all electrical power to the unit if service is to be  
performed.  
4 - Adjust the thermostat to deactivate the heating de-  
mand.  
3 - Remove the access panel.  
Page 49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4 - Move gas valve switch to OFF.  
Furnace should operate at least 5 minutes before check-  
ing gas flow. Determine time in seconds for two revolu-  
tions of gas through the meter. (Two revolutions assures a  
more accurate time.) Divide by two and compare to time  
in table 15. If manifold pressure matches table 17 and rate  
is incorrect, check gas orifices for proper size and re-  
striction. Remove temporary gas meter if installed.  
5 - Replace the access panel.  
Failure To Operate  
If the unit fails to operate, check the following:  
1 - Is the thermostat calling for heat?  
2 - Are access panels securely in place?  
3 - Is the main disconnect switch closed?  
4 - Is there a blown fuse or tripped breaker?  
5 - Is the filter dirty or plugged? Dirty or plugged filters will  
cause the limit control to shut the unit off.  
6 - Is gas turned on at the meter?  
NOTE - To obtain accurate reading, shut off all other gas  
appliances connected to meter.  
Supply Pressure Measurement  
7 - Is the manual main shut‐off valve open?  
8 - Is the internal manual shut‐off valve open?  
9 - Is the unit ignition system in lockout? If the unit locks out  
again, inspect the unit for blockages.  
An inlet post located on the gas valve provides access to  
screw one turn, connect a piece of 5/16 tubing and connect  
for supply line pressure.  
Heating Sequence Of Operation  
1 - When thermostat calls for heat, combustion air inducer  
starts.  
On multiple unit installations, each unit should be checked  
separately, with and without units operating. Supply pres-  
2 - Combustion air pressure switch proves blower opera-  
tion. Switch is factory set and requires no adjustment.  
3 - After a 15-second prepurge, the hot surface ignitor en-  
ergizes.  
Manifold Pressure Measurement  
NOTE - Pressure test adapter kit (10L34) is available from  
Lennox to facilitate manifold pressure measurement.  
4 - After a 20-second ignitor warm-up period, the gas  
valve solenoid opens. A 4-second trial for ignition peri-  
od begins.”  
A manifold pressure post located on the gas valve provides  
the 3/32 hex screw one turn, connect a piece of 5/16 tubing  
and connect to a manometer to measure manifold pres-  
sure.  
5 - Gas is ignited, flame sensor proves the flame, and the  
combustion process continues.  
6 - If flame is not detected after first ignition trial, the igni-  
tion control will repeat steps 3 and 4 four more times  
before locking out the gas valve (“WATCHGUARD”  
flame failure mode). The ignition control will then auto-  
matically repeat steps 1 through 6 after 60 minutes.  
To interrupt the 60-minute “WATCHGUARD” period,  
move thermostat from “Heat” to “OFF” then back to  
“Heat”. Heating sequence then restarts at step 1.  
To correctly measure manifold pressure, the differential  
pressure between the positive gas manifold and the nega-  
tive burner box must be considered.  
1 - Connect the test gauge positive side “+“ to manifold  
pressure tap on gas valve as noted above.  
2 - Tee into the gas valve regulator vent hose and connect  
to test gauge negative “-”.  
Gas Pressure Adjustment  
Gas Flow (Approximate)  
3 - Ignite unit on low fire and let run for 5 minutes to allow  
for steady state conditions.  
TABLE 15  
GAS METER CLOCKING CHART  
Seconds for One Revolution  
4 - After allowing unit to stabilize for 5 minutes, record  
manifold pressure and compare to value given in table  
Natural  
LP  
EL296  
Unit  
1 cu ft  
Dial  
2 cu ft  
Dial  
1 cu ft  
Dial  
2 cu ft  
DIAL  
5 - If necessary, make adjustments. Figure 66 shows  
location of high fire and low fire adjustment screws.  
-045  
-070  
-090  
-110  
-135  
80  
160  
110  
82  
200  
136  
102  
82  
400  
272  
204  
164  
136  
6 - Repeat steps 3, 4 and 5 on high fire. See values in  
55  
41  
33  
66  
NOTE - Shut unit off and remove manometer as soon as an  
accurate reading has been obtained. Re-start unit and  
check gas valve for gas leaks.  
27  
54  
68  
Natural-1000 btu/cu ft  
LP-2500 btu/cu ft  
Page 50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Proper Combustion  
High Altitude Information  
Furnace should operate minimum 15 minutes with correct  
manifold pressure and gas flow rate before checking com-  
bustion. Take combustion sample beyond the flue outlet  
and compare to the tables below.  
NOTE - In Canada, certification for installations at eleva-  
tions over 4500 feet (1372 m) is the jurisdiction of local au-  
thorities.  
Units may be installed at altitudes up to 10,000 ft. above  
sea level without manifold adjustment. Units installed at al-  
titude of 4501 - 10,000 feet (1373 to 3048m) may require a  
pressure switch change which can be ordered separately.  
ments at varying altitudes.  
TABLE 16  
CO %  
2
CO %  
For L.P  
For Nat  
2
EL296  
Model  
Low Fire High Fire Low Fire High Fire  
5.4 - 6.4 7.5 - 8.5 6.4 - 7.4 8.8 - 9.8  
5.3 - 6.3 7.4 - 8.4 6.3 - 7.3 8.7 - 9.7  
5.8 - 6.8 7.6 - 8.6 6.8 - 7.8 8.9 - 9.9  
6.1 - 7.1 8.0 - 9.0 7.1 - 8.1 9.3 - 10.3  
6.1 - 7.1 7.8 - 8.8 7.1 - 8.2 9.1 - 10.1  
045  
070  
090  
110  
135  
The combustion air pressure switch is factory-set and re-  
quires no adjustment.  
The maximum carbon monoxide reading should not exceed 50 ppm.  
TABLE 17  
Manifold and Supply Line Pressure 0-10,000ft.  
Manifold Pressure in.wg.  
Supply Line Pressure in. w.g.  
EL296  
Unit  
Gas  
Low Fire  
1.7  
High Fire  
3.5  
Min  
4.5  
Max  
10.5  
13.0  
Natural  
All Sizes  
LP/propane  
4.9  
10.0  
11.0  
NOTE -  
A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion  
procedure.  
TABLE 18  
LP/Propane Conversion Kit and Pressure Switch Requirements at Varying Altitudes  
High Altitude  
Natural Burner  
Orifice Kit  
High Altitude  
LP/Propane Burner  
Orifice Kit  
Natural to  
LP/Propane  
High Altitude Pressure Switch  
EL296  
Unit  
0 - 7500 ft  
(0 - 2286m)  
7501 - 10,000 ft  
(2286 - 3038m)  
7501 - 10,000 ft  
(2286 - 3038m)  
4501 - 7500 ft  
(1373 - 2286m)  
7501 -10,000 ft  
(2286 - 3048m)  
-045  
-070  
-090  
-110  
-135  
93W81  
93W80  
93W82  
93W80  
93W83  
93W84  
93W85  
93W80  
93W85  
93W85  
*78W93  
73W37  
*78W96  
* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit.  
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-1370 m).  
Page 51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Testing for Proper Venting and Sufficient Combustion Air for Non-Direct Vent Applications  
horizontal pitch. Determine there is no blockage or re-  
striction, leakage, corrosion, or other deficiencies  
which could cause an unsafe condition.  
WARNING  
CARBON MONOXIDE POISONING HAZARD!  
3 - To the extent that it is practical, close all building doors  
Failure to follow the steps outlined below for each  
appliance connected to the venting system being  
placed into operation could result in carbon monox-  
ide poisoning or death.  
and windows and all doors between the space in which  
the appliances connected to the venting system are lo-  
cated and other spaces of the building.  
4 - Close fireplace dampers.  
The following steps shall be followed for each ap-  
pliance connected to the venting system being  
placed into operation, while all other appliances con-  
nected to the venting system are not in operation.  
5 - Turn on clothes dryers and any appliances not con-  
nected to the venting system. Turn on any exhaust  
fans, such as range hoods and bathroom exhausts, so  
they will operate at maximum speed. Do not operate a  
summer exhaust fan.  
After the EL296UHE gas furnace has been started, the fol-  
lowing test should be conducted to ensure proper venting  
and sufficient combustion air has been provided to the  
EL296UHE as well as to other gas‐fired appliances which  
are separately vented.  
6 - Follow the lighting instruction to place the appliance  
being inspected into operation. Adjust thermostat so  
appliance will operate continuously.  
7 - Use the flame of match or candle to test for spillage of  
flue gases at the draft hood relief opening after 5 min-  
utes of main burner operation.  
If a EL296UHE furnace replaces a Category I furnace  
which was commonly vented with another gas appliance,  
the size of the existing vent pipe for that gas appliance must  
be checked. Without the heat of the original furnace flue  
products, the existing vent pipe is probably oversized for  
the single water heater or other appliance. The vent should  
be checked for proper draw with the remaining appliance.  
8 - If improper venting is observed during any of the  
above tests, the venting system must be corrected or  
sufficient combustion/make‐up air must be provided.  
The venting system should be re‐sized to approach  
the minimum size as determined by using the ap-  
propriate tables in appendix G in the current standards  
of the National Fuel Gas Code ANSI-Z223.1/NPFA 54  
in the U.S.A., and the appropriate Natural Gas and  
Propane appliances venting sizing tables in the cur-  
rent standard of the CSA-B149 Natural Gas and Pro-  
pane Installation Codes in Canada.  
The test should be conducted while all appliances (both in  
operation and those not in operation) are connected to the  
venting system being tested. If the venting system has  
been installed improperly, or if provisions have not been  
made for sufficient amounts of combustion air, corrections  
must be made as outlined in the previous section.  
9 - After determining that each appliance remaining  
connected to the common venting system properly  
vents when tested as indicated in step 3, return  
doors, windows, exhaust fans, fireplace dampers  
and any other gas‐burning appliance to their previous  
condition of use.  
1 - Seal any unused openings in the venting system.  
2 - Visually inspect the venting system for proper size and  
Page 52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE - The ignition control thermostat selection DIP switch is  
factory-set in the “TWO-STAGE” position.  
Other Unit Adjustments  
Applications Using a Two-Stage Thermostat  
A - Heating Sequence -- Integrated Control Thermostat  
Selection DIP Switch 1 OFF in “Two-Stage” Position  
(Factory Setting)  
Primary Limit.  
The primary limit is located on the heating compartment  
vestibule panel. This limit is factory set and requires no ad-  
justment.  
1 - On a call for heat, thermostat first-stage contacts close  
sending a signal to the integrated control. The inte-  
grated control runs a self‐diagnostic program and  
checks high temperature limit switches for normally  
closed contacts and pressure switches for normally  
open contacts. The combustion air inducer is ener-  
gized at low speed.  
Flame Rollout Switches (Two)  
These manually reset switches are located on the front of  
the burner box.  
Pressure Switch  
2 - Once the control receives a signal that the low pres-  
sure switch has closed, the combustion air inducer be-  
gins a 15-second pre-purge in low speed.  
The pressure switch is located in the heating compartment  
on the cold end header box. This switch checks for proper  
combustion air inducer operation before allowing ignition  
trial. The switch is factory-set and must not be adjusted.  
NOTE - If the low fire pressure switch does not close  
the combustion air inducer will switch to high fire. After  
a 15 second pre-purge the high fire pressure switch  
will close and the unit will begin operation on high fire.  
After 10 to 20 seconds of high fire operation the unit  
will switch to low fire..  
Temperature Rise  
Place the unit into operation with a second-stage heating  
demand. After supply and return air temperatures have  
stabilized, check the temperature rise. If necessary, adjust  
the heating blower speed to maintain the temperature rise  
within the range shown on the unit nameplate. Increase the  
blower speed to decrease the temperature rise. Decrease  
the blower speed to increase the temperature rise. Failure  
to properly adjust the temperature rise may cause erratic  
limit operation.  
3 - After the pre-purge is complete, a 20-second initial ig-  
nitor warm-up period begins. The combustion air in-  
ducer continues to operate at low speed.  
4 - After the 20-second warm-up period has ended, the gas  
valve is energized on low fire (first stage) and ignition oc-  
curs. At the same time, the control module sends a sig-  
nal to begin an indoor blower 30-second ON-delay.  
When the delay ends, the indoor blower motor is ener-  
gized on the low fire heating speed, the HUM contacts  
close energizing the humidifier and 120V ACC termi-  
nal is energized. The furnace will continue this opera-  
tion as long as the thermostat has a first-stage heating  
demand.  
Electrical  
1 - Check all wiring for loose connections.  
2 - Check for the correct voltage at the furnace (furnace  
operating). Correct voltage is 120VAC + 10%  
3 - Check amp-draw on the blower motor with blower ac-  
cess panel in place.  
Unit Nameplate__________Actual__________  
5 - If second-stage heat is required, the thermostat sec-  
ond-stage heat contacts close and send a signal to the  
integrated control. The integrated control initiates a  
30-second second-stage recognition delay.  
Exhaust and Air Intake Pipe  
1 - Check exhaust and air intake connections for tightness  
and to make sure there is no blockage.  
6 - At the end of the recognition delay, the integrated con-  
trol energizes the combustion air inducer at high  
speed. The control also checks the high fire (second  
stage) pressure switch to make sure it is closed. The  
high fire (second stage) gas valve is energized and the  
indoor blower motor is energized for operation at the  
high fire heating speed.  
2 - Is pressure switch closed? Obstructed exhaust pipe  
will cause unit to shut off at pressure switch. Check ter-  
mination for blockages.  
3 - Obstructed pipe or termination may cause rollout  
switches to open. Reset manual flame rollout switches  
on burner box assembly if necessary.  
7 - When the demand for high fire (second stage) heat is  
satisfied, the combustion air inducer is switched to the  
low-fire heating speed and the high-fire (second  
stage) gas valve is de-energized. The low-fire (first  
stage) gas valve continues operation. The indoor  
blower motor is switched to the low-fire heating speed.  
8 - When the thermostat demand for low-fire (first stage)  
heat is satisfied, the gas valve is de-energized and the  
field-selected indoor blower off delay begins. The  
combustion air inducer begins a 5-second post-purge  
period.  
Heating Sequence of Operation  
Electronic Ignition  
The two-stage, variable speed integrated control used in  
EL296UHE units has an added feature of an internal Watch-  
guard control. The feature serves as an automatic reset de-  
vice for ignition control lockout caused by ignition failure. Af-  
ter one hour of continuous thermostat demand for heat, the  
Watchguard will break and remake thermostat demand to  
the furnace and automatically reset the control to begin the  
ignition sequence.  
9 - When the combustion air post-purge period is com-  
plete, the inducer, the HUM contacts as well as the  
120V ACC terminals are de-energized. The indoor  
blower is de-energized at the end of the off delay.  
Page 53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Applications Using A Single-Stage Thermostat  
B - Heating Sequence -- Integrated Control Thermostat  
Selection DIP Switch 1 ON in “Single-Stage” Position  
Repair Parts List  
The following repair parts are available through Lennox  
dealers. When ordering parts, include the complete fur-  
nace model number listed on the CSA nameplate -- Exam-  
ple: EL296UH045XE24B-01. All service must be per-  
formed by a licensed professional installer (or  
equivalent), service agency, or gas supplier.  
NOTE - In these applications, two-stage heat will be initi-  
ated by the integrated control if heating demand has not  
been satisfied after the field adjustable period (7 or 12 min-  
utes).  
1 - On a call for heat, thermostat first-stage contacts close  
sending a signal to the integrated control. The inte-  
grated control runs a self‐diagnostic program and  
checks high temperature limit switches for normally  
closed contacts and pressure switches for normally  
open contacts. The combustion air inducer is ener-  
gized at low speed.  
Cabinet Parts  
Outer access panel  
Blower access panel  
Top Cap  
2 - Once the control receives a signal that the low pres-  
sure switch has closed, the combustion air inducer be-  
gins a 15-second pre-purge in low speed.  
Control Panel Parts  
Transformer  
Integrated control board  
Door interlock switch  
NOTE - If the low fire pressure switch does not close  
the combustion air inducer will switch to high fire. After  
a 15 second pre-purge the high fire pressure switch  
will close and the unit will begin operation on high fire.  
After 10 to 20 seconds of high fire operation the unit  
will switch to low fire.  
Blower Parts  
Blower wheel  
Motor  
Motor mounting frame  
Motor capacitor  
Blower housing cutoff plate  
3 - After the pre-purge is complete, a 20-second initial ig-  
nitor warm-up period begins. The combustion air in-  
ducer continues to operate at low speed.  
Heating Parts  
4 - After the 20-second warm-up period has ended, the gas  
valve is energized on low fire (first stage) and ignition oc-  
curs. At the same time, the control module sends a sig-  
nal to begin an indoor blower 30-second ON-delay.  
When the delay ends, the indoor blower motor is ener-  
gized on the low fire heating speed and the HUM con-  
tacts are energized. The integrated control also initi-  
ates a second-stage on delay (factory-set at 7  
minutes; adjustable to 12 minutes).  
5 - If the heating demand continues beyond the second-  
stage on delay, the integrated control energizes the  
combustion air inducer at high speed. The control also  
checks the high fire (second stage) pressure switch to  
make sure it is closed. The high fire (second stage)  
gas valve is energized and the indoor blower motor is  
energized for operation at the high fire heating speed.  
6 - When the thermostat heating demand is satisfied, the  
combustion air inducer begins a 5-second low speed  
post-purge. The field-selected indoor blower off delay  
begins. The indoor blower operates at the low-fire  
heating speed.  
Flame Sensor  
Heat exchanger assembly  
Gas manifold  
Combustion air inducer  
Gas valve  
Main burner cluster  
Main burner orifices  
Pressure switch  
Ignitor  
Primary limit control  
Flame rollout switches  
7 - When the combustion air post-purge period is com-  
plete, the inducer, the HUM contacts as well as the  
120V ACC terminals are de-energized. The indoor  
blower is de-energized at the end of the off delay.  
Page 54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2 - Check for the correct voltage at the furnace (furnace  
operating).  
Service  
3 - Check amp-draw on the blower motor.  
Motor Nameplate__________Actual__________  
WARNING  
ELECTRICAL SHOCK, FIRE,  
OR EXPLOSION HAZARD.  
Winterizing and Condensate Trap Care  
1 - Turn off power to the furnace.  
2 - Have a shallow pan ready to empty condensate water.  
Failure to follow safety warnings exactly could result  
in dangerous operation, serious injury, death or  
property damage.  
Improper servicing could result in dangerous opera-  
tion, serious injury, death, or property damage.  
Before servicing, disconnect all electrical power to  
furnace.  
3 - Remove the clean out cap from the condensate trap  
and empty water. Inspect the trap then reinstall the  
clean out cap.  
Cleaning The Burner Assembly  
If cleaning the burner assembly becomes necessary, fol-  
low the steps below:  
When servicing controls, label all wires prior to dis-  
connecting. Take care to reconnect wires correctly.  
Verify proper operation after servicing.  
1 - Turn off electrical and gas power supplies to furnace.  
Remove upper and lower furnace access panels.  
2 - Disconnect the wires from the gas valve.  
3 - Remove the burner box cover (if equipped).  
4 - Disconnect the gas supply line from the gas valve. Re-  
move gas valve/manifold assembly.  
At the beginning of each heating season, system should be  
checked as follows by a qualified service technician:  
Blower  
5 - Mark and disconnect sensor wire from the sensor. Dis-  
connect wires from flame rollout switches.  
Check the blower wheel for debris and clean if necessary.  
The blower motors are prelubricated for extended bearing  
life. No further lubrication is needed.  
6 - Disconnect combustion air intake pipe. It may be nec-  
essary to cut the existing pipe to remove burner box  
assembly.  
7 - Remove four screws which secure burner box assem-  
bly to vest panel. Remove burner box from the unit.  
WARNING  
8 - Use the soft brush attachment on a vacuum cleaner to  
gently clean the face of the burners. Visually inspect  
the inside of the burners and crossovers for any block-  
age caused by foreign matter. Remove any blockage.  
9 - Reinstall the burner box assembly using the existing  
four screws. Make sure that the burners line up in the  
center of the burner ports.  
The blower access panel must be securely in place  
when the blower and burners are operating. Gas  
fumes, which could contain carbon monoxide, can  
be drawn into living space resulting in personal inju-  
ry or death.  
Filters  
10 - Reconnect the sensor wire and reconnect the 2-pin  
plug to the ignitor wiring harness. Reconnect wires to  
flame rollout switches.  
All air filters are installed external to the unit. Filters should  
be inspected monthly. Clean or replace the filters when  
necessary to ensure proper furnace operation. Table 1  
lists recommended filter sizes.  
11 - Reinstall the gas valve manifold assembly. Reconnect  
the gas supply line to the gas valve. Reinstall the burn-  
er box cover.  
Exhaust and air intake pipes  
Check the exhaust and air intake pipes and all connections  
for tightness and to make sure there is no blockage.  
12 - Reconnect wires to gas valve.  
13 - Replace the blower compartment access panel.  
14 - Refer to instruction on verifying gas and electrical con-  
nections when re-establishing supplies.  
NOTE - After any heavy snow, ice or frozen fog event the  
furnace vent pipes may become restricted. Always check  
the vent system and remove any snow or ice that may be  
obstructing the plastic intake or exhaust pipes.  
15 - Follow lighting instructions to light and operate fur-  
nace for 5 minutes to ensure that heat exchanger is  
clean and dry and that furnace is operating properly.  
Electrical  
1 - Check all wiring for loose connections.  
16 - Replace heating compartment access panel.  
Page 55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start-Up & Performance Check List  
UNIT SET UP  
(typical)  
Furnace:  
Model Number_______________  
Serial Number_________________  
SUPPLY  
AIR  
Line Voltage  
2
4
1
GAS SUPPLY  
Natural Gas  
LP Propane Gas  
3
Piping Connections Tight  
Leak Tested  
Flter  
RETURN AIR  
2
Supply Line Pressure “W.C.________  
1
Gas Supply Pressure  
1
DUCT SYSTEM  
3
SUPPLY AIR DUCT  
Sealed  
2
INTAKE / EXHAUST PIPE  
Insulated (if necessary)  
All Joints Primed and Glued  
RETURN DUCT  
Sealed  
Terminations Installed Properly  
Horizontal Pipes Sloped (if applicable)  
Condensate Trap Primed / Line Sloped  
Filter Installed and Clean  
Grilles Unobstructed  
Pipes Supported  
VOLTAGE CHECK  
4
Supply Voltage _____  
Heat Cable Installed and Operable (if applicable)  
Electrical Connections Tight  
Page 56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT OPERATION  
HEATING MODE  
COOLING MODE  
GAS MANIFOLD PRESSURE “W.C._____  
1
2
INDOOR BLOWER AMPS______  
3
4
COMBUSTION SAMPLE CO % CO PPM_______  
2 ______  
TEMPERATURE DROP  
Return Duct Temperature _________  
_
INDOOR BLOWER AMPS______  
TEMPERATURE RISE  
3
4
Supply Duct Temperature _______  
Temperature Drop = _________  
5
TOTAL EXTERNAL STATIC (dry coil)  
Supply External Static _______  
Supply Duct Temperature ________  
_
Return Duct Temperature  
_____  
Return External Static + ______  
Total External Static = _______  
Temperature Rise = ________  
TOTAL EXTERNAL STATIC  
5
8
DRAIN LINE  
Leak Free  
Supply External Static _______  
Return External Static + ______  
Total External Static = _______  
THERMOSTAT  
6
7
9
CONDENSATE LINE  
Leak Free  
Adjusted and Programmed  
Explained Operation to Owner  
VENT PIPE  
Leak Free  
Combustion CO  
2
2
7
SUPPLY  
AIR  
Thermostat  
Temperatures  
8
Gas Manifold Pressure  
9
4
1
Blower Motor Amps  
6
3
Duct Static  
5
High +  
RETURN AIR  
Low -  
Contractor's: Name_________________________Telephone_____________Checklist Completed____________________  
Job Address_____-________________________________Technician's Name___________________________________  
Page 57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Requirements for Commonwealth of Massachusetts  
Modifications to NFPA-54, Chapter 10  
4 - INSPECTION. The state or local gas inspector of the  
side wall, horizontally vented, gas-fueled equipment  
shall not approve the installation unless, upon inspec-  
tion, the inspector observes carbon monoxide detec-  
tors and signage installed in accordance with the pro-  
visions of 248 CMR 5.08(2)(a) 1 through 4.  
Revise NFPA-54 section 10.8.3 to add the following re-  
quirements:  
For all side wall, horizontally vented, gas-fueled equipment  
installed in every dwelling, building or structure used in  
whole or in part for residential purposes, including those  
owned or operated by the Commonwealth and where the  
side wall exhaust vent termination is less than seven (7)  
feet above the finished grade in the area of the venting, in-  
cluding but not limited to decks and porches, the following  
requirements shall be satisfied:  
EXEMPTIONS: The following equipment is exempt  
from 24 CMR 5.08(2)(a) 1 through 4:  
1 - The equipment listed in Chapter 10 entitled “Equip-  
ment Not Required to Be Vented” in the most current  
edition of NFPA 54 as adopted by the Board; and  
2 - Product Approved side wall, horizontally vented, gas-  
fueled equipment installed in a room or structure sepa-  
rate from the dwelling, building or structure used in  
whole or in part for residential purposes.  
1 - INSTALLATION OF CARBON MONOXIDE DETEC-  
TORS. At the time of installation of the side wall, hori-  
zontally vented, gas-fueled equipment, the installing  
plumber or gasfitter shall observe that a hard-wired  
carbon monoxide detector with an alarm and battery  
backup is installed on the floor level where the gas  
equipment is to be installed. In addition, the installing  
plumber or gasfitter shall observe that a battery-oper-  
ated or hard-wired carbon monoxide detector with an  
alarm is installed on each additional level of the dwell-  
ing, building or structure served by the side wall, hori-  
zontally vented, gas-fueled equipment. It shall be the  
responsibility of the property owner to secure the ser-  
vices of qualified licensed professionals for the instal-  
lation of hard-wired carbon monoxide detectors.  
MANUFACTURER REQUIREMENTS -  
GAS EQUIPMENT VENTING SYSTEM PROVIDED.  
When the manufacturer of Product Approved side wall,  
horizontally vented, gas-fueled equipment provides a vent-  
ing system design or venting system components with the  
equipment, the instructions provided by the manufacturer  
for installation of the equipment and the venting system  
shall include:  
1 - Detailed instructions for the installation of the venting  
system design or the venting system components:  
and  
a - In the event that the side wall, horizontally vented,  
gas-fueled equipment is installed in a crawl space  
or an attic, the hard-wired carbon monoxide detec-  
tor with alarm and battery back-up may be installed  
on the next adjacent floor level.  
2 - A complete parts list for the venting system design or  
venting system.  
MANUFACTURER REQUIREMENTS -  
GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.  
b - In the event that the requirements of this subdivi-  
sion cannot be met at the time of completion of  
installation, the owner shall have a period of thirty  
(30) days to comply with the above requirements;  
provided, however, that during said thirty (30) day  
period, a battery-operated carbon monoxide detec-  
tor with an alarm shall be installed.  
When the manufacturer of Product Approved side wall,  
horizontally vented, gas-fueled equipment does not pro-  
vide the parts for venting the flue gases, but identifies “spe-  
cial venting systems,” the following requirements shall be  
satisfied by the manufacturer:  
2 - APPROVED CARBON MONOXIDE DETECTORS.  
Each carbon monoxide detector as required in accor-  
dance with the above provisions shall comply with  
NFPA 720 and be ANSI/UL 2034 listed and IAS certi-  
fied.  
1 - The referenced “special venting system” instructions  
shall be included with the appliance or equipment  
installation instructions; and  
2
The “special venting systems” shall be Product Ap-  
proved by the Board, and the instructions for that sys-  
tem shall include a parts list and detailed installation  
instructions.  
3 - SIGNAGE. A metal or plastic identification plate shall  
be permanently mounted to the exterior of the building  
at a minimum height of eight (8) feet above grade di-  
rectly in line with the exhaust vent terminal for the hori-  
zontally vented, gas-fueled heating appliance or  
equipment. The sign shall read, in print size no less  
than one-half (1/2) inch in size, “GAS VENT DIRECT-  
LY BELOW. KEEP CLEAR OF ALL OBSTRUC-  
TIONS.”  
A copy of all installation instructions for all Product  
Approved side wall, horizontally vented, gas-fueled  
equipment, all venting instructions, all parts lists for  
venting instructions, and/or all venting design instruc-  
tions shall remain with the appliance or equipment at  
the completion of the installation.  
Page 58  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Leica Laser Level 764555 User Manual
Lexmark Printer 240n User Manual
Lincoln Electric Welding System V205 T AC DC User Manual
Link electronic TV Converter Box 1163 User Manual
Magnavox Flat Panel Television 20MF500T User Manual
Manitowoc Ice Ice Maker K00095 User Manual
MB QUART Car Speaker PKC 110 User Manual
McDATA Network Card OPENconnectors Command Line Interace User Manual
Mellerware Hair Dryer 2 0 1 0 0 User Manual
Micronics Computer Hardware 60 66MHz User Manual