Lennox International Inc Air Conditioner 06 11 50672801 User Manual

INSTALLATION  
INSTRUCTIONS  
E 2011 Lennox Industries Inc.  
Dallas, Texas, USA  
Elite® Series XP13 Units  
HEAT PUMPS  
506728−01  
06/11  
These instructions are intended as a  
Litho U.S.A.  
general guide and do not supersede  
local codes in any way. Consult  
authorities having jurisdiction before  
installation.  
Supersedes 04/11  
TABLE OF CONTENTS  
Model Number Identification . . . . . . . . . . . . . . . . . . . .  
RETAIN THESE INSTRUCTIONS  
FOR FUTURE REFERENCE  
Caps and Fasteners Torque Requirements . . . . . . . .  
Operating Gauge Set and Service Valves . . . . . . . . .  
Recovering Refrigerant from Existing System . . . . .  
New Outdoor Unit Placement . . . . . . . . . . . . . . . . . . .  
Removing and Installing Panels . . . . . . . . . . . . . . . . .  
NOTICE TO INSTALLER  
BRAZING LINE SET TO SERVICE VALVES  
It is imperative to follow the brazing technique illustrated starting on  
page 12 to avoid damaging the service valve’s internal seals.  
Indoor Refrigerant Metering Device Removal and  
Flushing Line Set and Indoor Coil . . . . . . . . . . . . . . . . 15  
WARNING  
Installing New Indoor Metering Device . . . . . . . . . . . . 16  
Leak Test Line Set and Indoor Coil . . . . . . . . . . . . . . . 17  
Evacuating Line Set and Indoor Coil . . . . . . . . . . . . . 18  
Improper installation, adjustment, alteration, service or  
maintenance can cause personal injury, loss of life, or  
damage to property.  
Installation and service must be performed by a licensed  
professional installer (or equivalent) or a service agency.  
Servicing and Weighing In Refrigerant for Units  
IMPORTANT  
Optimizing System Refrigerant Charge . . . . . . . . . . . 24  
Maintenance (Dealer and Homeowner) . . . . . . . . . . . 30  
Start−up and Performance Checklist . . . . . . . . . . . . . . 32  
The Clean Air Act of 1990 bans the intentional venting of  
refrigerant (CFCs, HFCs, and HCFCs) as of July 1,  
1992. Approved methods of recovery, recycling or  
reclaiming must be followed. Fines and/or incarceration  
may be levied for noncompliance.  
Shipping and Packing List  
Check the unit for shipping damage and listed times below  
are intact. If damaged, or if parts are missing, immediately  
contact the last shipping carrier.  
IMPORTANT  
This unit must be matched with an indoor coil as  
specified in Lennox’ Engineering Handbook. Coils  
previously charged with HCFC−22 must be flushed.  
1 ꢀ Assembled XP13 outdoor unit  
General  
The XP13 outdoor unit uses HFC−410A refrigerant. This  
unit must be installed with a matching indoor blower coil  
and line set as outlined in the XP13 Engineering  
Handbook. These outdoor units are designed for use in  
check / expansion valve (CTXV) systems only and are not  
to be used with other refrigerant flow control devices. An  
indoor coil check / expansion valve approved for use with  
HFC−410A must be ordered separately and installed prior  
to operating the unit.  
CAUTION  
Physical contact with metal edges and corners while  
applying excessive force or rapid motion can result in  
personal injury. Be aware of, and use caution when  
working near these areas during installation or while  
servicing this equipment.  
06/11  
506728−01  
Page 1  
*2P0611*  
*P506728-01*  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Typical Unit Parts Arrangement  
CONTROL PANEL  
CAPACITOR (C12)  
CONTACTOR−  
1POLE (K1−1)  
DEFROST CONTROL  
(CMC1)  
THERMAL  
PROTECTION  
SWITCH (S173)  
GROUND  
LUG  
SWITCH  
COVER  
ONLY ON UNITS  
USING EXTERNAL  
SWITCH  
COMPRESSOR  
MUFFLER  
5−TON UNIT  
EXAMPLED HERE  
DEFROST  
THERMOSTAT (S6)  
TRUE SUCTION  
PORT  
CHECK EXPANSION  
VALVE  
REVERSING  
VALVE  
REVERSING VALVE  
SOLENOID  
CRANKCASE HEATER  
(−042, −048 AND 060  
UNITS ONLY)  
LIQUID LINE FILTER  
DRIER (BI−FLOW)  
CRANKCASE HEATER THERMOSTAT (S40)  
(−042, −048 AND 060 UNITS ONLY)  
LOW PRESSURE  
SWITCH (S87)  
HIGH PRESSURE SWITCH  
(AUTO−RESET) (S4)  
VAPOR LINE SERVICE  
VALVE  
LIQUID LINE  
SERVICE VALVE  
FIELD CONNECTION  
FOR VAPOR LINE  
(BALL−TYPE −060 ONLY)  
FIELD CONNECTION  
FOR LIQUID LINE SET  
PLUMBING, SWITCHES AND  
SENSOR COMPONENTS  
FIELD CONNECTION FOR VAPOR  
LINE (ANGLE−TYPE − ALL OTHER  
SIZES)  
Figure 1. Typical Parts Arrangements  
Page 3  
XP13 SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Caps and Fasteners Torque Requirements  
Operating Gauge Set and Service Valves  
IMPORTANT  
To prevent stripping of the various caps used, the  
appropriately sized wrench should be used and fitted  
snugly over the cap before tightening.  
IMPORTANT  
Only use Allen wrenches of sufficient hardness (50Rc −  
Rockwell Harness Scale minimum). Fully insert the  
wrench into the valve stem recess.  
OPERATING SERVICE VALVES  
Service valve stems are factory−torqued (from 9 ft−lbs for  
small valves, to 25 ft−lbs for large valves) to prevent  
refrigerant loss during shipping and handling. Using an  
Allen wrench rated at less than 50Rc risks rounding or  
breaking off the wrench, or stripping the valve stem  
recess.  
The liquid and vapor line service valves are used for  
refrigerant recovery, flushing, leak testing, evacuating,  
weighing in refrigerant and optimizing system charge.  
Each valve is equipped with a service port which has a  
factory−installed valve core. Figure 2 provides information  
on how to access and operate both angle− and ball−type  
service valves.  
See the Lennox Service and Application Notes  
Corp.0807−L5 (C−08−1) for further details and  
information.  
USING MANIFOLD GAUGE SET  
When checking the system charge, only use a manifold  
gauge set that features low−loss anti−blow back fittings.  
When servicing or repairing HVAC equipment and  
components, ensure the fasteners are appropriately  
fasteners.  
Manifold gauge set used for HFC−410A refrigerant  
systems must be capable of handling the higher system  
operating pressures. The manifold gauges should be rated  
for:  
Table 1. Torque Requirements  
Parts  
Recommended Torque  
S
S
S
High side ꢀ Pressure range of 0 − 800 pound−force per  
square inch gauge (psig)  
Service valve cap  
Sheet metal screws  
Machine screws #10  
Compressor bolts  
Gauge port seal cap  
8 ft.− lb.  
11 NM  
2 NM  
16 in.− lb.  
28 in.− lb.  
90 in.− lb.  
8 ft.− lb.  
Low side ꢀ Use with 30" vacuum to 250 psig with  
dampened speed to 500 psig  
3 NM  
10 NM  
11 NM  
Manifold gauge set hoses must be rated for use to 800  
psig of pressure with a 4000 psig burst rating.  
506728−01  
Page 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operating Angle−Type Service Valve:  
1. Remove stem cap with an appropriately sized wrench.  
INSERT HEX−HEAD  
EXTENSION HERE  
2
2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16"  
for vapor line valve sizes) to back the stem out counterclockwise as far as it will go to open  
the service valve.  
SERVICE PORT CAP  
TO INDOOR  
UNIT  
SERVICE PORT CORE  
TO OUTDOOR  
UNIT  
SERVICE PORT  
CORE  
(VALVE STEM SHOWN OPEN)  
INSERT HEX WRENCH HERE  
VALVE STEM  
SHOWN  
CLOSED  
TO INDOOR  
UNIT  
REMOVE  
STEM CAP  
1
When service valve stem is in the CLOSED position,  
the service port is open to the line set and indoor unit.  
STEM CAP  
TO OUTDOOR UNIT  
To Access Service Port:  
When service valve is OPEN, the service port is open to line set,  
indoor and outdoor unit.  
1/6 TURN  
A service port cap protects the service port core from  
contaminationand serves as the primary leak seal.  
Operating Ball−Type Service Valve:  
12  
6
1
5
11  
10  
1. Remove service port cap with an appropriately sized  
wrench.  
2
1. Remove stem cap with an appropriately sized wrench.  
2. Use an appropriately sized wrenched to open.  
9
3
2. Connect gauge set to service port.  
4
8
7
A
To open rotate stem  
counterclockwise  
90°.  
3. When testing is completed, replace service port cap and  
tighten as follows:  
TO INDOOR UNIT  
S
S
With torque wrench: Finger tighten and torque cap per table 1.  
B
To close rotate stem  
clockwise 90°.  
Without torque wrench: Finger tighten and use an appropriately sized  
wrench to turn an additional 1/6 turn clockwise.  
1/12 TURN  
BALL (SHOWN CLOSED)  
Reinstall Stem Cap:  
VALVE STEM  
2
Stem cap protects the valve stem from damage and  
serves as the primary seal. Replace the stem cap and  
tighten as follows:  
12  
1
5
11  
10  
SERVICE PORT  
2
SERVICE PORT CORE  
SERVICE PORT CAP  
9
3
S
S
With Torque Wrench: Finger tighten and then  
torque cap per table 1.  
4
8
7
6
Without Torque Wrench: Finger tighten and use an  
REMOVE  
STEM CAP  
TO OUTDOOR UNIT  
appropriatelysized wrench to turn an additional 1/12 turn clockwise.  
1
NOTE ꢀ A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.  
Figure 2. Angle and Ball−Type Service Valves  
Page 5  
XP13 SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Recovering Refrigerant from Existing System  
CONNECT MANIFOLD GAUGE SET  
DISCONNECT POWER  
Connect a manifold gauge set, clean recovery cylinder and a  
recovery machine to the service ports of the existing unit..  
Disconnect all power to the existing outdoor unit at the disconnect  
switch and/or main fuse box/breaker panel.  
2
1
NOTE ꢀ Use the recovery machine instructions to make  
the correct manifold gauge set connections for recovery  
refrigerant.The illustration below is a typical connection.  
MAIN FUSE  
BOX/BREAKER  
PANEL  
MANIFOLD GAUGES  
DISCONNECT  
SWITCH  
RECOVERY MACHINE  
LOW  
HIGH  
OUTDOOR UNIT  
CLEAN RECOVERY  
CYLINDER  
RECOVERING REFRIGERANT  
3
Remove existing HCFC−22 refrigerant using one of the following procedures:  
METHOD 2 LIMITATIONS  
METHOD 1:  
Use Method 1 if the existing outdoor unit is not equipped with shut−off valves, or  
if the unit is not operational and you plan to use the existing HCFC−22 to flush  
the system.  
NOTE ꢀ When using Method 2, the listed devices  
below could prevent full system charge recovery into  
the outdoor unit:  
Recover all HCFC−22 refrigerant from the existing system using a recovery  
machine and clean recovery cylinder. Check gauges after shutdown to confirm  
that the entire system is completely void of refrigerant.  
S
Outdoor unit’s high or low−pressure switches (if  
applicable) when tripped can cycle the  
compressor OFF.  
S
S
Compressor can stop pumping due to tripped  
internal pressure relief valve.  
METHOD 2:  
Use Method 2 if the existing outdoor unit is equipped with manual shut−off valves,  
and you plan to use new HCFC−22 refrigerant to flush the system.  
Compressor has internal vacuum protection that  
is designed to unload the scrolls (compressor  
stops pumping) when the pressure ratio meets a  
certain value or when the suction pressure is as  
high as 20 psig. (Compressor suction  
pressuresshould never be allowed to go into  
a vacuum. Prolonged operation at low suction  
pressures will result in overheating of the  
scrolls and permanent damage to the scroll  
tips, drive bearings and internal seals.)  
Perform the following task:  
A
Start the existing HCFC−22 system in the cooling mode and close the liquid line  
valve.  
B
Use the compressor to pump as much of the existing HCFC−22 refrigerant into  
the outdoor unit until the outdoor system is full. Turn the outdoor unit main power  
OFF and use a recovery machine to remove the remaining refrigerant from the  
system.  
NOTE ꢀ It may be necessary to bypass the low pressure switches (if equipped) to  
ensure complete refrigerant evacuation.  
Once the compressor can not pump down to a lower  
pressure due to any of the above mentioned system  
conditions, shut off the vapor valve. Turn OFF the main  
power to unit and use a recovery machine to recover  
any refrigerant left in the indoor coil and line set.  
C
D
When the low side system pressures reach 0 psig, close the vapor line valve.  
Check gauges after shutdown to confirm that the valves are not allowing  
refrigerantto flow back into the low side of the system.  
Figure 3. Refrigerant Recovery  
IMPORTANT  
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance,  
service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.  
WARNING  
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.  
Failure to follow this warning may result in personal injury or death.  
506728−01  
Page 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
New Outdoor Unit Placement  
higher ground will not collect around the unit. The slab  
should have a slope tolerance as described in figure 5,  
detail B.  
CAUTION  
In order to avoid injury, take proper precaution when lift-  
ing heavy objects.  
NOTE ꢀ If necessary for stability, anchor unit to slab as  
described in figure 5, detail D.  
Remove existing outdoor unit prior to placement of new  
outdoor unit. See Unit Dimensions on page 2 for sizing  
mounting slab, platforms or supports. Refer to figure 4 for  
mandatory installation clearance requirements.  
ELEVATING THE UNIT  
Units are outfitted with elongated support feet as illustrated  
If additional elevation is necessary, raise the unit by  
extending the height of the unit support feet. This may be  
achieved by using a 2 inch (50.8mm) schedule 40 female  
threaded adapter.  
POSITIONING CONSIDERATIONS  
Consider the following when positioning the unit:  
S
Some localities are adopting sound ordinances based  
on the unit’s sound level registered from the adjacent  
property, not from the installation property. Install the  
unit as far as possible from the property line.  
NOTE ꢀ Keep the height of extenders short enough to  
ensure a sturdy installation. If it is necessary to extend  
further, consider a different type of field−fabricated  
framework that is sturdy enough for greater heights.  
S
When possible, do not install the unit directly outside  
a window. Glass has a very high level of sound  
transmission. For proper placement of unit in relation  
to a window see the provided illustration in figure 5,  
detail A.  
ROOF MOUNTING  
Install the unit a minimum of 6 inches (152 mm) above the  
roof surface to avoid ice build−up around the unit. Locate  
the unit above a load bearing wall or area of the roof that  
can adequately support the unit. Consult local codes for  
rooftop applications. See figure 5, detail F for other roof top  
mounting considerations.  
PLACING UNIT ON SLAB  
When installing unit at grade level, the top of the slab  
should be high enough above grade so that water from  
MINIMUM CLEARANCE  
ABOVE UNIT  
CLEARANCE ON ALL SIDES ꢀ INCHES (MILLIMETERS)  
NOTES:  
S
Service clearance of 30 inches (762 mm) must be  
maintained on one of the sides adjacent to the  
control panel  
S
S
Clearanceto one of the other three sides must be 36  
inches (914mm).  
48 (1219)  
Clearanceto one of the remaining two sides may be  
12 inches (305mm) and the final side may be 6  
inches (152mm).  
CONTROL PANEL ACCESS  
LOCATION  
MINIMUM CLEARANCE BETWEEN TWO UNITS  
24  
(610)  
Figure 4. Installation Clearances  
NOTICE  
Roof Damage!  
This system contains both refrigerant and oil. Some rubber roofing material may absorb oil and cause therubber toswell  
when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid  
exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof  
surface.  
Page 7  
XP13 SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ꢀ Outside Unit Placement  
DETAIL A  
Install unit away from windows.  
ꢀ Slab Mounting at Ground Level  
DETAIL B  
Install unit level or, if on a slope, maintain slope tolerance of two (2)  
degrees (or two inches per five feet [50 mm per 1.5 m]) away from  
building structure.  
BUILDING  
STRUCTURE  
MOUNTING  
SLAB  
GROUND LEVEL  
TWO 90° ELBOWS INSTALLED IN LINE SET WILL  
REDUCE LINE SET VIBRATION.  
Elevated Slab Mounting  
DETAIL C ꢀ  
ꢀ Slab Side Mounting  
DETAIL D  
using Feet Extenders  
#10 1/2" LONG SELF−DRILLING  
SHEET METAL SCREWS  
COIL  
STABILIZING BRACKET (18 GAUGE  
METAL ꢀ 2" WIDTH; HEIGHT AS  
REQUIRED)  
BASE PAN  
#10 1−1/4" LONG HEX HD SCREW  
AND FLAT WASHER  
CORNER POST  
Concrete slab ꢀ use two plastic anchors (hole  
drill 1/4")  
BASE  
Wood or plastic slab ꢀ no plastic anchor (hole  
drill 1/8")  
Stabilizing bracket (18 gauge metal ꢀ 2" (50.8mm) width; height as required); bend to form  
right angle as exampled below.  
LEG DETAIL  
2" (50.8MM) SCH 40  
FEMALE THREADED  
ADAPTER  
ꢀ Roof Top Mounting  
DETAIL F  
If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be  
constructed. Size barrier at least the same height and width as outdoor unit. Mount barrier 24  
inches (610 mm) from the sides of the unit in the direction of prevailing winds as illustrated.  
2" (50.8MM) SCH 40  
MALE THREADED  
ADAPTER  
PREVAILING WINTER WINDS  
Use additional 2" SCH 40 male threaded adapters which  
can be threaded into the female threaded adapters to  
make additional adjustments to the level of the unit.  
WIND BARRIER  
INLET AIR  
ꢀ Deck Top Mounting  
DETAIL E  
MINIMUM ONE  
PER SIDE  
One bracket per side  
(minimum). For extra  
INLET AIR  
INLET AIR  
stability, two brackets per  
side, two inches (51mm)  
from each corner.  
SAME FASTENERS AS  
SLAB SIDE MOUNTING.  
FOR EXTRA  
STABILITY  
INLET AIR  
Figure 5. Placement, Slab Mounting and Stabilizing Unit  
506728−01  
Page 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Removing and Installing Panels  
LOUVERED PANEL REMOVAL  
Remove the louvered panels as follows:  
IMPORTANT! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR  
ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL.  
1. Remove two screws, allowing the panel to swing open  
slightly.  
PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR  
ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.  
2. Hold the panel firmly throughout this procedure. Rotate  
bottom corner of panel away from hinged corner post until  
lower three tabs clear the slots as illustrated in detail B.  
SCREW  
HOLES  
3. Move panel down until lip of upper tab clears the top slot in  
corner post as illustrated in detail A.  
LIP  
LOUVERED PANEL INSTALLATION  
Position the panel almost parallel with the unit as illustrated in  
detail D with the screw side as close to the unit as possible.  
Then, in a continuous motion:  
Detail A  
Detail B  
1. Slightly rotate and guide the lip of top tab inward as  
illustrated in detail A and C; then upward into the top  
slot of the hinge corner post.  
2. Rotate panel to vertical to fully engage all tabs.  
3. Holding the panel’s hinged side firmly in place, close  
the right−hand side of the panel, aligning the screw  
holes.  
4. When panel is correctly positioned and aligned, insert  
the screws and tighten.  
ROTATE IN THIS DIRECTION;  
THEN DOWN TO REMOVE  
PANEL  
HOLD DOOR FIRMLY TO THE HINGED  
SIDE TO MAINTAIN  
FULLY−ENGAGED TABS  
ANGLE MAY BE TOO  
EXTREME  
Detail C  
PREFERRED ANGLE  
FOR INSTALLATION  
Detail D  
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO  
PARALLEL WITH THE UNIT AS POSSIBLE) WHILE  
INSTALLING PANEL.  
Figure 6. Removing and Installing Panels  
WARNING  
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:  
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause  
injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g.,  
being bent or scratched).  
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause  
panels to be blown around and battered.  
Page 9  
XP13 SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Line Set Requirements  
This section provides information on: installation of new or  
replacement line set.  
S
S
Model (XP13) and size of unit (e.g. −036).  
Line set diameters for the unit being installed as listed  
in table 2 and total length of installation.  
S
S
S
Adding Polyol ester oil requirements  
New or replacement line set installation  
Using existing line set.  
S
Number of elbows vertical rise or drop in the piping.  
USING EXISTING LINE SET  
ADDING POLYOL ESTER OIL REQUIREMENTS  
Things to consider:  
S
S
S
Liquid line that meter the refrigerant, such as RFC1  
liquid line, must not be used in this application.  
IMPORTANT  
Mineral oils are not compatible with HFC−410A. If oil  
must be added, it must be a Polyol Ester oil.  
Existing line set of proper size as listed in table 2 may  
be reused.  
If system was previously charged with HCFC−22  
refrigerant, then existing line set must be flushed (see  
Flushing Line Set and Indoor Coil on page 15).  
The compressor is charged with sufficient Polyol Ester oil  
(POE) for line set lengths up to 50 feet. Recommend  
adding oil to system based on the amount of refrigerant  
charge in the system. Systems with 20 pounds or less of  
refrigerant required no oil to be added.  
If existing line set is being used, then proceed to Brazing  
Connections on page 11.  
For systems over 20 pounds − add one ounce for every five  
(5) pounds of HFC−410A refrigerant.  
IMPORTANT  
Recommended topping−off POE oils are Mobil EAL  
ARCTIC 22 CC or ICI EMKARATEt RL32CF.  
Lennox highly recommends changing line set when  
converting the existing system from HCFC−22 to  
HFC−410A. If that is not possible and the line set is the  
proper size as reference in table 2, use the procedure  
outlined under Flushing Line Set and Indoor Coil on page  
13.  
NEW OR REPLACEMENT LINE SET INSTALLATION  
Field refrigerant piping consists of both liquid and vapor  
lines from the outdoor unit to the indoor coil. Use Lennox  
L15 (sweat, non−flare) series line set, or field−fabricated  
refrigerant line sizes as specified in table 2.  
IMPORTANT  
If refrigerant lines are routed through a wall, then seal and  
isolate the opening so vibration is not transmitted to the  
building. Pay close attention to line set isolation during  
installation of any HVAC system. When properly isolated  
from building structures (walls, ceilings. floors), the  
refrigerant lines will not create unnecessary vibration and  
subsequent sounds. See figure 7 for recommended  
installation practices.  
If this unit is being matched with an approved line set  
or indoor unit coil which was previously charged with  
mineral oil, or if it is being matched with a coil which  
was manufactured before January of 1999, the coil  
and line set must be flushed prior to installation. Take  
care to empty all existing traps. Polyol ester (POE) oils  
are used in Lennox units charged with HFC−410A  
refrigerant. Residual mineral oil can act as an  
insulator, preventing proper heat transfer. It can also  
clog the expansion device, and reduce the system  
performance and capacity.  
NOTE ꢀ When installing refrigerant lines longer than 50  
feet, see the Lennox Refrigerant Piping Design and  
Fabrication Guidelines, CORP. 9351−L9, or contact  
Lennox Technical Support Product Applications for  
assistance. To obtain the correct information from Lennox,  
be sure to communicate the following information:  
Failure to properly flush the system per the  
instructions below will void the warranty.  
Table 2. Refrigerant Line Set ꢀ Inches (mm)  
Field Connections  
Recommended Line Set  
Model  
Liquid Line  
Suction Line  
Liquid Line  
Suction Line  
L15 Line Set  
XP13−018−230  
XP13−024−230  
XP13−030−230  
XP13−036−230  
XP13−042−230  
XP13−048−230  
XP13−060−230  
3/8" (10 mm)  
3/4" (19 mm)  
3/8" (10 mm)  
3/4" (19 mm)  
L15−41 ꢀ 15 ft. − 50 ft. (4.6 m − 15 m)  
3/8" (10 mm)  
3/8" (10 mm)  
7/8" (22 mm)  
3/8" (10 mm)  
3/8" (10 mm)  
7/8" (22 mm)  
L15−65 ꢀ 15 ft. − 50 ft. (4.6 m − 15 m)  
Field Fabricated  
1−1/8" (29 mm)  
1−1/8" (29 mm)  
NOTE ꢀ Some applications may required a field provided 7/8" to 1−1/8" adapter  
506728−01  
Page 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Line Set Isolation ꢀ The following illustrations are examples of proper refrigerant line set isolation:  
REFRIGERANT LINE SET ꢀ INSTALLING  
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)  
REFRIGERANT LINE SET ꢀ TRANSITION  
FROM VERTICAL TO HORIZONTAL  
NOTE ꢀ Insulate liquid line when it is routed through areas where the  
surrounding ambient temperature could become higher than the  
temperatureof the liquid line or when pressure drop is equal to or greater  
than 20 psig.  
ANCHORED HEAVY NYLON  
WIRE TIE OR AUTOMOTIVE  
AUTOMOTIVE  
MUFFLER-TYPE HANGER  
MUFFLER-TYPE HANGER  
OUTSIDE WALL  
LIQUID LINE  
VAPOR LINE  
WALL  
STUD  
WIRE TIE  
INSIDE WALL  
STRAP  
WOOD BLOCK  
BETWEEN STUDS  
STRAP LIQUID LINE TO  
VAPOR LINE  
NON−CORROSIVE  
METAL SLEEVE  
WIRE TIE  
LIQUID LINE  
NON−CORROSIVE  
METAL SLEEVE  
WOOD BLOCK  
WIRE TIE  
VAPOR LINE − WRAPPED  
IN ARMAFLEX  
STRAP  
REFRIGERANT LINE SET ꢀ INSTALLING  
HORIZONTAL RUNS  
SLEEVE  
To hang line set from joist or rafter, use either metal strapping material  
or anchored heavy nylon wire ties.  
WIRE TIE (AROUND  
VAPOR LINE ONLY)  
VAPOR LINE WRAPPED  
WITH ARMAFLEX  
8 FEET (2.43 METERS)  
OUTSIDE  
WALL  
STRAPPING  
MATERIAL (AROUND  
VAPOR LINE ONLY)  
FLOOR JOIST OR  
LIQUID  
LINE  
ROOF RAFTER  
TAPE OR  
WIRE TIE  
8 FEET (2.43 METERS)  
PVC  
PIPE  
CAULK  
NON−CORROSIVE  
METAL SLEEVE  
FIBERGLASS  
INSULATION  
STRAP THE VAPOR LINE TO THE JOIST  
OR RAFTER AT 8 FEET (2.43 METERS)  
INTERVALS THEN STRAP THE LIQUID  
LINE TO THE VAPOR LINE.  
TAPE OR  
WIRE TIE  
NOTE ꢀ Similar installation practices should be used if line set is  
to be installed on exterior of outside wall.  
FLOOR JOIST OR  
ROOF RAFTER  
Figure 7. Line Set Installation  
Page 11  
XP13 SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Brazing Connections  
WARNING  
IMPORTANT  
Polyol Ester (POE) oils used with HFC−410A  
refrigerant absorb moisture very quickly. It is very  
important that the refrigerant system be kept closed  
as much as possible. DO NOT remove line set caps  
or service valve stub caps until you are ready to make  
connections.  
Allow braze joint to cool before removing the wet rag  
from the service valve. Temperatures above 250ºF can  
damage valve seals.  
IMPORTANT  
Use silver alloy brazing rods with 5% minimum silver  
alloy for copper−to−copper brazing. Use 45% minimum  
alloy for copper−to−brass and copper−to−steel brazing.  
WARNING  
Danger of fire. Bleeding the refrigerant  
charge from only the high side may result  
in pressurization of the low side shell and  
suction tubing. Application of a brazing  
torch to a pressurized system may result  
in ignition of the refrigerant and oil  
mixture − Check the high and low  
pressures before applying heat.  
WARNING  
Fire, Explosion and Personal Safety  
Hazard.  
Failure to follow this warning could  
result in damage, personal injury or  
death.  
Never use oxygen to pressurize or  
purge refrigeration lines. Oxygen,  
when exposed to a spark or open  
flame, can cause fire and/or an ex-  
plosion, that could result in property  
damage, personal injury or death.  
CAUTION  
Brazing alloys and flux contain materials which are  
hazardous to your health.  
Avoid breathing vapors or fumes from brazing  
operations. Perform operations only in well−ventilated  
areas.  
WARNING  
When using a high pressure gas such as  
dry nitrogen to pressurize a refrigeration  
or air conditioning system, use a  
regulator that can control the pressure  
down to 1 or 2 psig (6.9 to 13.8 kPa).  
Wear gloves and protective goggles or face shield to  
protect against burns.  
Wash hands with soap and water after handling brazing  
alloys and flux.  
506728−01  
Page 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
CAP AND CORE REMOVAL  
CUT AND DEBUR  
Cut ends of the refrigerant lines square (free from nicks or dents)  
and debur the ends. The pipe must remain round. Do not crimp end  
of the line.  
Remove service cap and core from both the suction / vapor and  
liquid line service ports.  
2
1
CUT AND DEBUR  
SERVICE PORT  
CAP  
SERVICE  
PORT  
CORE  
LINE SET SIZE MATCHES  
SERVICE VALVE CONNECTION  
SERVICE VALVE  
CONNECTION  
SERVICE  
PORT  
CORE  
COPPER TUBE  
STUB  
REDUCER  
SUCTION / VAPOR LINE  
SERVICE VALVE (BALL−TYPE  
FOR −060 AND ANGLE−TYPE  
FOR ALL OTHER SIZES)  
LINE SET SIZE IS SMALLER  
THAN CONNECTION  
DO NOT CRIMP SERVICE VALVE  
CONNECTOR WHEN PIPE IS  
SMALLER THAN CONNECTION  
REFRIGERANT LINE  
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE  
VALVES  
3
Flow regulated nitrogen (at 1 to 2 psig) through the low−side refrigeration gauge set into the liquid line service port valve, and out of the suction /  
vapor line service port valve.  
A
B
C
Connect gauge set low pressure side to liquid line service valve (service port).  
Connect gauge set center port to bottle of nitrogen with regulator.  
Remove core from valve in suction / vapor line service port to allow nitrogen to escape.  
USE REGULATOR TO FLOW  
NITROGEN AT 1 TO 2 PSIG.  
HIGH  
LOW  
ATTACH  
GAUGES  
SUCTION / VAPOR SERVICE PORT MUST BE  
OPEN TO ALLOW EXIT POINT FOR NITROGEN  
B
SUCTION /  
VAPOR LINE  
SERVICE  
VALVE  
C
VAPOR LINE  
OUTDOOR  
UNIT  
INDOOR  
UNIT  
NITROGEN  
LIQUID LINE SERVICE  
VALVE  
WHEN BRAZING LINE SET TO  
SERVICE VALVES, POINT FLAME  
AWAY FROM SERVICE VALVE.  
LIQUID LINE  
A
Figure 8. Brazing Procedures  
Page 13  
XP13 SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
WRAP SERVICE VALVES  
To help protect service valve seals during brazing, wrap water saturated cloths around service valve bodies and copper tube stubs. Use  
additionalwater saturated cloths underneath the valve body to protect the base paint.  
4
FLOW NITROGEN  
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and  
out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections  
5
6
BRAZE LINE SET  
Wrap both service valves with water saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set. Water  
saturated cloths must remain water saturated throughout the brazing and cool−down process.  
SUCTION / VAPOR LINE  
SERVICE VALVE  
LIQUID LINE SERVICE VALVE  
VAPOR LINE SERVICE VALVE  
COULD BE EITHER A ANGLE−TYPE  
OR BALL−TYPE VALVE.  
ANGLE−TYPE SERVICE  
VALVE  
WHEN BRAZING  
LINE SET TO  
SERVICE VALVES,  
POINT FLAME  
AWAY FROM  
SERVICE VALVE.  
WATER SATURATED  
CLOTH  
LIQUID LINE  
SUCTION / VAPOR LINE  
WATER SATURATED  
CLOTH  
WHEN BRAZING LINE SET TO SERVICE VALVES, POINT FLAME AWAY  
FROM SERVICE VALVE.  
PREPARATION FOR NEXT STEP  
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water saturated cloths to both  
service valves to cool piping. Once piping is cool, remove all water saturated cloths.  
7
Figure 9. Brazing Procedures (continued)  
IMPORTANT  
Allow braze joint to cool. Apply additional water saturated cloths to help cool brazed joint. Do not remove water saturated  
cloths until piping has cooled. Temperatures above 250ºF will damage valve seals.  
WARNING  
FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE may result if you do not wrap a water satu-  
rated cloth around both liquid and suction line service valve bodies and copper tube stub while brazing  
in the line set! The braze, when complete, must be quenched with water to absorb any residual heat.  
Do not open service valves until refrigerant lines and indoor coil have been leak−tested and evacuated.  
Refer to procedures provided in this supplement.  
506728−01  
Page 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Indoor Refrigerant Metering Device Removal and Flushing Line Set and Indoor Coil  
Flushing is only required when the existing system used HCFC−22 refrigerant. If the existing system used HFC−410a, then  
remove the original indoor coil metering device and proceed to Installing New Indoor Metering Device on page 16.  
TYPICAL EXISTING FIXED ORIFICE  
REMOVAL PROCEDURE (UNCASED  
COIL SHOWN)  
TYPICAL EXISTING EXPANSION VALVE REMOVAL  
PROCEDURE (UNCASED COIL SHOWN)  
OR  
1B  
1A  
STUB END  
TWO PIECE PATCH PLATE  
(UNCASED COIL ONLY)  
LIQUID LINE  
ORIFICE  
HOUSING  
CHECK  
EXPANSION  
VALVE  
DISTRIBUTOR TUBES  
LIQUID LINE ORIFICE HOUSING  
DISTRIBUTOR  
TUBES  
®
TEFLON  
RING  
®
TEFLON RING  
FIXED ORIFICE  
BRASS NUT  
®
TEFLON  
RING  
SENSING  
LINE  
DISTRIBUTOR  
ASSEMBLY  
DISTRIBUTOR  
ASSEMBLY  
EQUALIZER  
LINE  
REMOVE AND DISCARD  
®
WHITE TEFLON SEAL  
(IF PRESENT)  
LIQUID LINE ASSEMBLY  
(INCLUDES STRAINER)  
LIQUID LINE  
ASSEMBLY WITH  
BRASS NUT  
A
B
On fully cased coils, remove the coil access and plumbing panels.  
Remove any shipping clamps holding the liquid line and distributor as-  
sembly.  
MALE EQUALIZER  
LINE FITTING  
VAPOR  
LINE  
C
Using two wrenches, disconnect liquid line from liquid line orifice hous-  
ing. Take care not to twist or damage distributor tubes during this pro-  
cess.  
LIQUID  
LINE  
SENSING BULB  
A
B
On fully cased coils, remove the coil access and plumbing panels.  
D
E
Remove and discard fixed orifice, valve stem assembly if present and  
®
Teflon washer as illustrated above.  
Remove any shipping clamps holding the liquid line and distributor  
assembly.  
Use a field−provided fitting to temporary reconnect the liquid line to the  
indoor unit’s liquid line orifice housing.  
C
Disconnect the equalizer line from the check expansion valve  
equalizer line fitting on the vapor line.  
D
E
Remove the vapor line sensing bulb.  
CONNECT GAUGES AND EQUIPMENT FOR  
FLUSHING PROCEDURE  
Disconnect the liquid line from the check expansion valve at the liquid  
line assembly.  
2
INVERTED HCFC−22  
GAUGE  
MANIFOLD  
F
Disconnect the check expansion valve from the liquid line orifice  
housing.Take care not to twist or damage distributor tubes during this  
process.  
CYLINDER CONTAINS  
CLEAN HCFC−22 TO BE  
USED FOR FLUSHING.  
A
®
G
H
Remove and discard check expansion valve and the two Teflon rings.  
LOW  
HIGH  
1
Use a field−provided fitting to temporary reconnect the liquid line to the  
indoor unit’s liquid line orifice housing.  
NEW  
OUTDOOR  
UNIT  
VAPOR LINE  
SERVICE VALVE  
FLUSHING LINE SET  
OPENED  
CLOSED  
The line set and indoor unit coil must be flushed with at least the  
same amount of clean refrigerant that previously charged the  
system. Check the charge in the flushing cylinder before  
proceeding.  
EXISTING  
INDOOR  
UNIT  
3
B
LIQUID LINE SERVICE  
VALVE  
A
Set the recovery machine for liquid recovery and start the  
recovery machine. Open the gauge set valves to allow the  
RECOVERY  
CYLINDER  
TANK  
RETURN  
rBecovery machine to pull a vacuum on the existing system line  
set and indoor unit coil.  
C
B
Invert the cylinder of clean HCFC−22 and open its valve to allow  
liquid refrigerant to flow into the system through the vapor line  
valve. Allow the refrigerant to pass from the cylinder and through  
the line set and the indoor unit coil before it enters the recovery  
machine.  
INLET  
D
DISCHARGE  
RECOVERY MACHINE  
A
Inverted HCFC−22 cylinder with clean refrigerant to the vapor service  
valve.  
C
D
After all of the liquid refrigerant has been recovered, switch the  
recovery machine to vapor recovery so that all of the HCFC−22  
vapor is recovered. Allow the recovery machine to pull down to 0  
the system.  
B
C
HCFC−22 gauge set (low side) to the liquid line valve.  
HCFC−22 gauge set center port to inlet on the recovery machine with an  
empty recovery tank to the gauge set.  
Close the valve on the inverted HCFC−22 drum and the gauge  
set valves. Pump the remaining refrigerant out of the recovery  
machine and turn the machine off.  
D
Connect recovery tank to recovery machines per machine instructions.  
Figure 10. Removing Indoor Refrigerate Metering Device and Flushing Procedures  
Page 15  
XP13 SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing New Indoor Metering Device  
This outdoor unit is designed for use in HFC−410A systems that use a check / expansion valve metering device (purchased  
separately) at the indoor coil.  
See the Lennox XP13 Engineering Handbook for approved check / expansion valve kit match−ups. The check / expansion  
valve device can be installed either internal or external to the indoor coil. In applications where an uncased coil is being  
installed in a field−provided plenum, install the check / expansion valve in a manner that will provide access for field servicing  
1/2 Turn  
A
B
Remove the field−provided fitting that temporarily  
reconnectedthe liquid line to the indoor unit’s distributor  
assembly.  
INDOOR EXPANSION VALVE INSTALLATION  
TWO PIECE  
12  
PATCH PLATE  
(Uncased Coil Shown)  
1
11  
10  
®
(UNCASED  
STUB  
END  
2
Install one of the provided Teflon rings around the  
stubbed end of the check / expansion valve and lightly  
lubricate the connector threads and expose surface of  
LIQUID LINE  
ORIFICE  
COIL ONLY)  
9
3
CHECK /  
EXPANSION  
VALVE  
4
8
HOUSING  
5
7
®
6
DISTRIBUTOR  
TUBES  
the Teflon ring with refrigerant oil.  
®
TEFLON  
RING  
C
D
E
Attach the stubbed end of the expansion valve to the  
liquid line orifice housing. Finger tighten and use an  
appropriatelysized wrench to turn an additional 1/2 turn  
clockwise as illustrated in the figure above, or 20 ft−lb.  
®
®
Place the remaining Teflon washer around the other  
end of the check / expansion valve. Lightly lubricate  
TEFLON  
RING  
SENSING  
LINE  
®
connector threads and expose surface of the Teflon  
ring with refrigerant oil.  
DISTRIBUTOR  
ASSEMBLY  
EQUALIZER  
LINE  
Attach the liquid line assembly to the check / expansion  
valve. Finger tighten and use an appropriately sized  
wrench to turn an additional 1/2 turn clockwise as  
illustratedin the figure above or 20 ft−lb.  
LIQUID LINE  
ASSEMBLY WITH  
BRASS NUT  
SENSING BULB INSTALLATION  
A
Attach the vapor line sensing bulb in the proper  
orientationas illustrated to the right using the clamp and  
screws provided.  
1/8 Turn  
MALE EQUALIZER LINE  
FITTING (SEE  
VAPOR  
LINE  
EQUALIZER LINE  
INSTALLATION FOR  
FURTHER DETAILS)  
NOTE ꢀ Confirm proper thermal contact between vapor line  
and expansion bulb before insulating the sensing bulb once  
installed.  
12  
1
5
11  
10  
2
LIQUID LINE  
9
3
4
8
B
Connect the equalizer line from the check / expansion  
valve to the equalizer vapor port on the vapor line. Finger  
tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated  
below.  
7
Sensing bulb insulation is  
required if mounted external to  
the coil casing.  
6
ON LINES SMALLER THAN  
7/8", MOUNT SENSING  
BULB AT EITHER THE 3 OR  
9 O’CLOCK POSITION.  
VAPOR LINE  
EQUALIZER LINE INSTALLATION  
Remove and discard either the flare seal cap or flare nut with  
copper flare seal bonnet from the equalizer line port on the vapor  
line as illustrated in the figure to the right.  
12  
BULB  
BULB  
FLARE SEAL CAP  
FLARE NUT  
VAPOR LINE  
ON 7/8" AND LARGER LINES,  
MOUNT SENSING BULB AT  
EITHER THE 4 OR 8 O’CLOCK  
POSITION. NEVER MOUNT ON  
BOTTOM OF LINE.  
COPPER FLARE  
SEAL BONNET  
OR  
12  
MALE BRASS EQUALIZER  
LINE FITTING  
BULB  
BULB  
NOTE ꢀ NEVER MOUNT ON BOTTOM OF LINE.  
VAPOR LINE  
Figure 11. Installing Indoor Check / Expansion Valve  
506728−01  
Page 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Leak Test Line Set and Indoor Coil  
IMPORTANT  
Leak detector must be capable of sensing HFC refrigerant.  
CONNECT GAUGE SET  
A
Connect an HFC−410A manifold gauge set high pressure hose to the  
vapor valve service port.  
LOW  
HIGH  
MANIFOLD GAUGE SET  
NOTE ꢀ Normally, the high pressure hose is connected to the liquid  
line port. However, connecting it to the vapor port better protects the  
manifoldgauge set from high pressure damage.  
B
With both manifold valves closed, connect the cylinder of HFC−410A  
refrigerantto the center port of the manifold gauge set.  
NOTE ꢀ Later in the procedure, the  
HFC−410A container will be replaced by  
the nitrogen container.  
A
B
TO VAPOR  
SERVICE VALVE  
(ANGLE OR BALL  
TYPE)  
NITROGEN  
OUTDOOR UNIT  
HFC−410A  
Figure 12. Manifold Gauge Set Connections for Leak Testing  
TEST FOR LEAKS  
side of the manifold gauge set. Disconnect the  
HFC−410A cylinder.  
After the line set has been connected to the indoor and  
outdoor units, check the line set connections and indoor  
unit for leaks. Use the following procedure to test for leaks:  
3. Connect a cylinder of dry nitrogen with a pressure  
regulating valve to the center port of the manifold  
gauge set.  
1. With both manifold valves closed, connect the cylinder  
of HFC−410A refrigerant to the center port of the  
manifold gauge set. Open the valve on the HFC−410A  
cylinder (vapor only).  
4. Adjust dry nitrogen pressure to 150 psig (1034 kPa).  
Open the valve on the high side of the manifold gauge  
set in order to pressurize the line set and the indoor unit.  
2. Open the high pressure side of the manifold to allow  
HFC−410A into the line set and indoor unit. Weigh in  
a trace amount of HFC−410A. [A trace amount is a  
maximum of two ounces (57 g) refrigerant or three  
pounds (31 kPa) pressure]. Close the valve on the  
HFC−410A cylinder and the valve on the high pressure  
5. After a few minutes, open one of the service valve  
ports and verify that the refrigerant added to the  
system earlier is measurable with a leak detector.  
6. After leak testing disconnect gauges from service  
ports.  
Page 17  
XP13 SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Evacuating Line Set and Indoor Coil  
Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any  
gas that will not condense under temperatures and pressures present during operation of an air conditioning system.  
Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and  
compressor parts.  
CONNECT GAUGE SET  
NOTE ꢀ Remove cores from service valves (if not already done).  
LOW  
HIGH  
1
A
Connect low side of manifold gauge set  
with 1/4 SAE in−line tee to vapor line  
service valve  
B
C
D
Connect high side of manifold gauge  
set to liquid line service valve  
MANIFOLD  
GAUGE SET  
A34000 1/4 SAE TEE WITH  
SWIVEL COUPLER  
Connect micron gauge available  
connector on the 1/4 SAE in−line tee.  
Connect the vacuum pump (with  
vacuum gauge) to the center port of the  
manifold gauge set. The center port  
line will be used later for both the  
HFC−410A and nitrogen containers.  
A
500  
TO VAPOR  
SERVICE VALVE  
MICRON  
GAUGE  
C
NITROGEN  
OUTDOOR  
UNIT  
TO LIQUID LINE  
SERVICE VALVE  
HFC−410A  
B
VACUUM PUMP  
RECOMMEND  
MINIMUM 3/8" HOSE  
D
EVACUATE THE SYSTEM  
A
B
Open both manifold valves and start the vacuum pump.  
Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).  
2
NOTE ꢀ During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure  
indicates a relatively large leak. If this occurs, repeat the leak testing procedure.  
NOTE ꢀ The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of  
pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.  
C
When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:  
S
S
S
S
S
S
Close manifold gauge valves  
Close valve on vacuum pump and turn off vacuum pump  
Disconnect manifold gauge center port hose from vacuum pump  
Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose.  
Open manifold gauge valves to break the vacuum in the line set and indoor unit.  
Close manifold gauge valves.  
D
E
Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the  
dry nitrogen from the line set and indoor unit.  
Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the  
absolutepressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump  
and closing the manifold gauge valves.  
F
When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an  
upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and  
indoor unit.  
1/6 TURN  
G
Perform the following:  
S
S
S
Close manifold gauge valves.  
Shut off HFC−410A cylinder.  
12  
1
5
11  
7
2
4
10  
Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core  
tool while maintaining a positive system pressure.  
9
3
8
S
Replace stem caps and secure finger tight, then tighten an additional one−sixth (1/6) of a turn as illustrated.  
6
Figure 13. Evacuating Line Set and Indoor Coil  
506728−01  
Page 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Electrical  
IMPORTANT  
In the U.S.A., wiring must conform with current local codes  
and the current National Electric Code (NEC). In Canada,  
wiring must conform with current local codes and the current  
Canadian Electrical Code (CEC).  
Use a thermocouple or thermistor electronic vacuum  
gauge that is calibrated in microns. Use an instrument  
capable of accurately measuring down to 50 microns.  
Refer to the furnace or air handler installation instructions  
for additional wiring application diagrams and refer to unit  
nameplate for minimum circuit ampacity and maximum  
overcurrent protection size.  
WARNING  
Danger of Equipment Damage. Avoid deep vacuum  
operation. Do not use compressors to evacuate a  
system. Extremely low vacuums can cause internal  
arcing and compressor failure. Damage caused by  
deep vacuum operation will void warranty.  
24VAC TRANSFORMER  
Use the transformer provided with the furnace or air  
handler for low-voltage control power (24VAC − 40 VA  
minimum)  
INSTALL THERMOSTAT  
SIZE CIRCUIT AND INSTALL DISCONNECT  
SWITCH  
Install room thermostat (ordered separately) on an inside wall  
2approximately in the center of the conditioned area and 5 feet  
(1.5m) from the floor. It should not be installed on an outside wall  
or where it can be affected by sunlight or drafts.  
1
Refer to the unit nameplate for minimum circuit ampacity, and  
maximum fuse or circuit breaker (HACR per NEC). Install power  
wiring and properly sized disconnect switch.  
MAIN FUSE  
BOX/BREAKER  
PANEL  
THERMOSTAT  
DISCONNECT  
SWITCH  
5 FEET  
(1.5M)  
NOTE ꢀ 24VAC, Class II circuit connections are made in the control  
panel.  
NOTE ꢀ Units are approved for use only with copper conductors.  
Ground unit at disconnect switch or to an earth ground.  
HIGH VOLTAGE FIELD WIRING  
FACTORY WIRING  
UNIT LOW VOLTAGE CONNECTIONS  
3
LOW VOLTAGE (24V) FIELD WIRING  
WIRE RUN LENGTH  
AWG# INSULATION TYPE  
LESS THAN 100’ (30 METERS)  
MORE THAN 100’ (30 METERS)  
18  
16  
TEMPERATURE RATING  
35ºC MINIMUM.  
ARun 24VAC control wires through cutout with grommet.  
BRun 24VAC control wires through wire tie.  
CMake 24VAC control wire connections defrost control terminal strip.  
DTighten wire tie to security 24V control wiring.  
C
TERMINAL STRIP  
NOTE − FOR PROPER VOLTAGES, SELECT THERMOSTAT WIRE (CONTROL WIRES)  
GAUGE PER TABLE ABOVE.  
NOTE − WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND TO MAINTAIN  
SEPARATION OF FIELD INSTALLED LOW AND HIGH VOLTAGE CIRCUITS.  
NOTE − DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE CONTROL  
BOX.  
A
D
B
Page 19  
XP13 SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Figure 14. Typical Unit Wiring Diagram  
506728−01  
Page 20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Figure 15. Typical Factory Wiring  
have consulted with the power company and the  
voltage condition has been corrected.  
Unit Start−Up  
6. Open both the liquid and vapor line service valves to  
release the refrigerant charge contained in outdoor  
unit into the system.  
IMPORTANT  
If unit is equipped with a crankcase heater, it should be  
energized 24 hours before unit start−up to prevent  
compressor damage as a result of slugging.  
7. Use figure 16 to determine next step in system  
preparation.  
OPEN BOTH VAPOR AND LIQUID SERVICE  
VALVE STEMS TO RELEASE  
REFRIGERANT FROM OUTDOOR UNIT TO  
SYSTEM.  
UNIT START−UP  
1. Rotate fan to check for binding.  
2. Inspect all factory− and field−installed wiring for loose  
connections.  
3. Verify that the manifold gauge set is connected as  
illustrated in figure 17. Use a temperature sensor  
positioned near the liquid line service port as illustrated  
in figure 17 which will be required later when using the  
subcooling method for optimizing the system  
refrigerant charge.  
NO  
YES  
GO TO SERVICE AND WEIGH  
IN REFRIGERANT CHARGE  
FOR OUTDOOR UNITS  
DELIVERED VOID OF CHARGE  
ON PAGE 22.  
GO TO OPTIMIZING SYSTEM  
REFRIGERANT CHARGE ON  
PAGE 24.  
4. Replace the stem caps and tighten to the value listed  
in table 1.  
5. Check voltage supply at the disconnect switch. The  
voltage must be within the range listed on the unit’s  
nameplate. If not, do not start the equipment until you  
Figure 16. Outdoor Unit Factory Charge  
Page 21  
XP13 SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Service and Weigh In Refrigerant for Outdoor Units Delivered Void of Charge  
The following procedures are only required if it has been determine that the new outdoor unit is void of charge. Skip to the  
next section if refrigerant charge is present.  
LEAK CHECK, REPAIR AND EVACUATE  
If the outdoor unit is void of refrigerant, clean the system  
using the procedure described below.  
1. Close manifold gauge set valves and connect the  
2. Check that fan rotates freely.  
1. Leak check system using procedures provided on  
page 17. Repair any leaks discovered during leak test.  
3. Inspect all factory− and field−installed wiring for loose  
connections.  
2. Evacuate the system using procedure provided in  
4. Open the high side manifold gauge valve and weigh in  
liquid refrigerant. Use figure 18 to calculate the correct  
weigh−in charge.  
3. Use nitrogen to break the vacuum and install a new  
filter drier in the system.  
5. Close manifold gauge valves.  
4. Evacuate the system again using procedure in figure  
13.  
6. Monitor the system to determine the amount of  
moisture remaining in the oil. It may be necessary to  
replace the bi−flow filter drier several times to achieve  
the required dryness level. If system dryness is not  
verified, the compressor will fail in the future.  
CONNECT MANIFOLD GAUGE SET AND WEIGH−IN  
CHARGE  
After the evacuation procedure, reconnect the manifold  
7. Continue to Optimizing System Refrigerant Charge  
on page 24 to optimize the system charge using  
subcooling method.  
required for initial system weigh in charging.  
MANIFOLD GAUGE SET  
GAUGE SET  
LOW  
HIGH  
CONNECTIONS FOR OPTIMIZING SYSTEM CHARGE  
NOTE ꢀ Refrigerant  
tank should be turned  
right−side−up to deliver  
vapor during charge  
optimizingprocedure.  
B
TRUE SUCTION PORT  
CONNECTION  
HFC−410A  
REFRIGERANT  
TANK  
A
CHARGE IN  
LIQUID PHASE  
TEMPERATURE  
SENSOR  
(LIQUID LINE)  
DIGITAL SCALE  
TO LIQUID  
LINE SERVICE  
VALVE  
C
D
A
Close manifold gauge set valves and connect the center hose to a cylinder of HFC−410A. Set  
for liquid phase charging.  
NOTE ꢀ For simplify the illustration,  
the line set is not shown connected to  
service valves.  
B
C
D
Connect the manifold gauge set’s low pressure side to the true suction port.  
Connect the manifold gauge set’s high pressure side to the liquid line service port.  
Position temperature sensor on liquid line near liquid line service port (use only for subcooling  
method).  
Figure 17. Typical Gauge Set Connections for Initial Weight−in Charge or Optimizing System Charge  
506728−01  
Page 22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
WEIGH−IN CHARGING  
CALCULATING SYSTEM CHARGE FOR OUTDOOR UNIT VOID OF CHARGE  
If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit. To calculate the total refriger-  
ant charge:  
Additional charge specified per  
match indoor air handler or coil  
Adjust amount. for variation in line set  
length listed on line set length table below.  
Amount specified on  
nameplate  
Total Charge  
+
=
+
Refrigerant Charge per Line Set Length  
OUNCES PER  
ADJUST FROM 15 FEET (4.6 METERS) LINE SET*  
5
FEET (GRAMS PER 1.5 METERS)  
LIQUID LINE SET DIAMETER  
3/8" (9.5 MM)  
3 OUNCE PER 5’ (85 GRAMS PER 1.5 M)  
*If line length is greater than 15 feet (4.6 meters), add this amount. If line length  
is less than 15 feet (4.6 meters), subtract this amount.  
NOTE ꢀ Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature  
of the liquid line or when pressure drop is equal to or greater than 20 psig.  
NOTE ꢀ The above nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.  
Figure 18. Using HFC−410A Weigh In Method  
DISTRIBUTOR  
OUTDOOR UNIT  
NOTE − ARROWS INDICATE DIRECTION  
OF REFRIGERANT FLOW  
REVERSING VALVE  
CHECK / EXPANSION  
VALVE  
OUTDOOR  
COIL  
INDOOR UNIT  
BI−FLOW FILTER / DRIER  
MUFFLER  
TRUE SUCTION  
VAPOR  
SERVICE  
PORT  
PORT  
LIQUID LINE  
SERVICE PORT  
COMPRESSOR  
CHECK / EXPANSION VALVE  
INDOOR  
NOTE − Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant lines and  
indoor coil. Use true suction port to measure vapor pressure during charging.  
COIL  
Figure 19. Heat Pump Cooling Cycle  
Page 23  
XP13 SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Optimizing System Refrigerant Charge  
This section provides instructions on optimizing the  
system charge. This section includes:  
efficiency. Make any air flow adjustments before  
continuing with the optimizing procedure.  
S
S
S
S
Optimizing procedure  
Adjusting indoor airflow  
Using subcooling method  
5. Use subcooling method to optimize the system  
charge (see figure 21). Adjust charge as necessary.  
ADJUSTING INDOOR AIRFLOW  
Approved matched components, targeted subcooling  
(SC) values and add charge values  
Heating Mode Indoor Airflow Check  
(Only use when indoor unit has electric heat)  
S
S
Normal operating pressures  
Temperature pressures  
Indoor blower airflow (CFM) may be calculated by  
energizing electric heat and measuring:  
OPTIMIZING PROCEDURE  
S
Temperature rise between the return air and supply air  
temperatures at the indoor coil blower unit,  
1. Move the low−side manifold gauge hose from the  
vapor line service valve to the true suction port (see  
S
S
Measuring voltage supplied to the unit,  
Measuring amperage being drawn by the heat unit(s).  
2. Set the thermostat for either cooling or heating  
demand. Turn on power to the indoor unit and close  
the outdoor unit disconnect switch to start the unit.  
Then, apply the measurements taken in the following  
formula to determine CFM:  
Amps x Volts x 3.41  
CFM =  
1.08 x Temperature rise (F)  
3. Allow unit to run for five minutes to allow pressures to  
stabilize.  
Cooling Mode Indoor Airflow Check  
Check airflow using the Delta−T (DT) process using figure  
20.  
4. Check the airflow as instructed under Adjusting Indoor  
Airflow to verify or adjust indoor airflow for maximum  
ADJUSTING INDOOR AIRFLOW  
DT  
Temp.  
of air  
entering  
indoor  
coil ºF  
1. Determine the desired DTꢀMeasure entering air temper-  
ature using dry bulb (A) and wet bulb (B). DT is the intersect-  
ing value of A and B in the table (see triangle).  
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15  
78 23 23 23 22 22 21 21 20 19 18 17 16 15 14  
76 22 22 22 21 21 20 19 19 18 17 16 15 14 13  
74 21 21 21 20 19 19 18 17 16 16 15 14 13 12  
72 20 20 19 18 17 17 16 15 15 14 13 12 11 10  
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10  
2. Find temperature drop across coilꢀMeasure the coil’s dry  
bulb entering and leaving air temperatures (A and C). Tem-  
A
perature Drop Formula: (T  
) = A minus C.  
Drop  
Wet−bulb ºF  
57 58 59 60 61 62 63 64 65 66 67 68 69 70  
B
3. Determine if fan needs adjustmentꢀIf the difference between  
the measured T and the desired DT (T DT) is within  
Drop  
Drop  
+3º, no adjustment is needed. See examples: Assume DT =  
15 and A temp. = 72º, these C temperatures would necessi-  
tate stated actions:  
A
T
Drop  
C
72º  
19º  
53º  
Cº  
T
DT  
=
ºF ACTION  
Drop  
19  
B
air flow  
air flow  
53º  
58º  
62º  
15  
15  
15  
=
=
=
4
Increase the airflow  
DRY  
BULB  
DRY  
BULB  
64º  
14  
−1 (within +3º range) no change  
10  
−5 Decrease the airflow  
WET  
BULB  
INDOOR  
COIL  
All temperatures are  
expressed in ºF  
4. Adjust the fan speedꢀSee indoor unit instructions to in-  
crease/decrease fan speed.  
Changing air flow affects all temperatures; recheck tempera-  
tures to confirm that the temperature drop and DT are within  
+3º.  
Figure 20. Checking Airflow over Indoor Coil Using Delta−T Formula  
506728−01  
Page 24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPTIMIZE CHARGE USING SUBCOOLING  
1. Check liquid and vapor line pressures. Compare pressures with either second−stage heat  
or cooling mode normal operating pressures listed in table 4. Table 4 is a general guide  
and expect minor pressures variations. Significant pressure differences may indicate  
improper charge or other system problem.  
2. Decide whether to use cooling or heating mode based on current outdoor ambient  
temperature:  
USE  
COOLING  
MODE  
A
Use COOLING MODE when:  
60ºF  
(15ºC)  
S
S
Outdoor ambient temperature is 60°F (15.5°C) and above.  
Indoor return air temperature range is between 70 to 80°F (21−27°C). This  
temperature range is what the target subcooling values are base upon in table  
USE  
HEATING  
MODE  
If indoor return air temperature is not within reference range, set thermostat to  
cooling mode and a setpoint of 68ºF (20ºC). This should place the outdoor unit into  
second−stage (high−capacity) cooling mode. When operating and temperature  
B
Use HEATING MODE when:  
S
S
Outdoor ambient temperature is 59°F (15.0°C) and below.  
Indoor return air temperature range is between 65−75°F (18−24°C). This  
temperature range is what the target subcooling values are base upon in table  
If indoor return air temperature is not within reference range, set thermostat to  
heating mode and a setpoint of 77ºF (25ºC). This should place the outdoor unit into  
second−stage (high−capacity) heating mode. When operating and temperature  
3. Read the liquid line pressure; then find its corresponding temperature pressure listed in  
table 5 and record it in the SATº space to the left.  
4. Read the liquid line temperature; record in the LIQº space to the left.  
SATº  
LIQº  
SCº  
5. Subtract LIQº temperature from SATº temperature to determine subcooling; record it in  
SCº space to the left..  
6. Compare SCº results with table 3 (either Heating or Cooling mode column), also  
consider any additional charge required for line set lengths longer than 15 feet and/or unit  
matched component combinations (Add Charge column).  
=
7. If subcooling value is:  
A
B
GREATER than shown for the applicable unit match component, REMOVE  
refrigerant;  
LESS than shown for the applicable unit match component, ADD refrigerant.  
8. If refrigerant is added or removed, repeat steps 3 through 6 to verify charge.  
9. Close all manifold gauge set valves and disconnect gauge set from outdoor unit.  
10. Replace the stem and service port caps and tighten as specified in Operating Service  
Valves on page .  
11. Recheck voltage while the unit is running. Power must be within range shown on the  
nameplate.  
Figure 21. Using HFC−410A Subcooling Method ꢀ Second Stage (High Capacity)  
Page 25  
XP13 SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
APPROVED MATCHED SYSTEM COMPONENTS, TARGETED SUBCOOLING (SC) VALUES AND  
ADD CHARGE VALUES  
Listed below are the approved matched system  
components (air handlers and indoor coils), targeted  
subcooling and add charge values for the XP13. This  
information is also listed on the unit charging sticker  
located on the outdoor unit access panel.  
Subcooling values listed in the following tables are based  
on outdoor ambient air temperature of:  
S
S
60°F (15.5°C) and above for cooling mode  
59°F (15.0°C) and below for heating mode.  
Table 3. Unit Indoor Matches, Targeted Subcooling, and Add Charge Values  
*Additional  
Charge  
*Additional  
Charge  
*Additional  
Charge  
Subcooling  
Subcooling  
Subcooling  
Indoor Coil or Air  
Handler  
Indoor Coil or Air  
Handler  
Indoor Coil or Air  
Handler  
Size  
Size  
Size  
Heat  
Cool  
8
Lbs  
0
1
0
1
0
1
0
0
0
0
1
1
1
1
2
1
1
1
0
0
0
1
0
1
1
3
1
1
1
Oz.  
Heat  
Cool  
Lbs  
Oz.  
Heat  
Cool  
Lbs  
Oz.  
CBX26UH−018  
CBX27UH−024  
CBX32M−018/024  
CBX32MV−024/030  
CBX32MV−018/024  
CBX40UHV−024  
CH33−25A  
11  
11  
10  
11  
10  
10  
13  
13  
11  
11  
12  
12  
11  
12  
8
0
1
−030 (continued)  
CBX40UHV−036  
−042 (continued)  
CH33−48C  
14  
12  
14  
12  
18  
7
9
10  
10  
9
22  
7
1
0
0
0
0
0
1
1
1
1
1
0
0
0
0
1
1
1
2
2
2
0
2
2
2
0
1
0
0
7
8
14  
21  
14  
14  
7
1
2
1
1
1
1
1
1
0
1
0
1
1
1
1
0
0
0
0
0
1
2
0
2
0
2
1
1
0
2
4
5
CH33−42B  
CR33−50/60C  
CX34−43B  
1
CH33−31B  
7
0
8
13  
13  
2
5
CR33−30/36AB/C  
CX34−31A/B  
7
9
CX34−50/60C  
CBX26UH−048  
CBX27UH−048  
CBX27UH−060  
CBX32M−048  
CBX32M−060  
CBX32MV−048  
CBX32MV−060  
CBX40UHV−042  
8
−018  
8
9
19  
15  
13  
13  
13  
13  
13  
12  
7
14  
0
7
4
CBX26UH−036  
CBX27UH−036  
CBX32M−036  
CBX32MV−036  
CBX40UHV−030  
CBX40UHV−036  
CH33−36C  
19  
8
10  
8
8
5
CH33−36A  
7
4
2
10  
8
9
CR33−30/36A/B/C  
CX34−25A/B  
4
4
8
2
10  
9
5
12  
12  
18  
22  
18  
15  
18  
22  
22  
13  
13  
6
3
8
2
6
9
CBX26UH−024  
CBX27UH−024  
CBX27UH−030  
CBX32M−030  
9
8
2
10  
9
8
5
15  
6
8
2
6
9
−036  
8
5
10  
10  
9
8
5
−048  
15  
2
CH33−42B  
8
0
CBX40UHV−048  
8
5
CBX32MV−018/024  
CBX32MV−024/030  
CBX32MV−036  
CBX40UHV−024  
CH33−25B  
CH33−31B  
8
7
0
CBX40UHV−060  
CH33−50/60C  
CH33−60D  
8
3
12  
11  
11  
11  
11  
11  
12  
9
15  
6
CR33−48B/C  
CX34−38A/B  
9
6
8
9
7
6
−024  
8
16  
19  
7
2
7
6
11  
12  
12  
0
6
CX34−44/48B/C  
CBX26UH−042  
CBX27UH−042  
CBX27UH−048  
CBX32M−048  
CBX32MV−036  
CBX32MV−048  
CBX40UHV−042  
CBX40UHV−048  
CBX40UHV−036  
CH33−43C  
8
6
CR33−50/60C  
CR33−60D  
7
6
15  
15  
0
11  
8
1
7
6
CH33−36B  
23  
23  
23  
8
11  
11  
11  
0
CX34−49C  
6
7
CR33−30/36A/B/C  
CX34−25A/B  
8
CX34−60D  
9
5
0
16  
16  
22  
22  
18  
22  
22  
22  
9
8
CBX26UH−060  
CBX27UH−060  
CBX32MV−060  
CBX32MV−068  
6
8
11  
1
CBX26UH−030  
CBX27UH−030  
CBX32M−036  
14  
0
7
6
8
−042  
9
8
23  
23  
23  
8
11  
11  
11  
0
6
7
15  
2
9
0
8
8
11  
7
CBX32MV−024/030  
CBX32MV−036  
CBX40UHV−024  
CBX40UHV−030  
9
3
8
CBX40UHV−060  
CH33−62D  
6
15  
1
−030  
−060  
9
0
7
7
11  
6
9
0
7
14  
2
CR33−60D  
10  
7
6
9
0
CX34−62C  
8
6
*Amount of charge required in additional to charge shown on unit nameplate.  
CX34−62D  
7
7
0
Table 4. Normal Operating Pressures − Liquid +10 and Vapor +5 PSIG  
IMPORTANT  
Use table 4 as a general guide when performing maintenance checks. This is not a procedure for charging the unit (Refer  
to Charging / Checking Charge section). Minor variations in these pressures may be expected due to differences in instal-  
lations. Significant differences could mean that the system is not properly charged or that a problem exists with some  
component in the system.  
Vapor Pressure  
Model  
Number  
Heating Mode  
Cooling Mode  
20  
(−7)  
30  
40  
(4.5)  
50  
60  
(16)  
65  
(18)  
70  
(21)  
75  
(24)  
80  
(27)  
85  
90  
(32)  
95  
100  
(38)  
105  
(41)  
110  
(43)  
115  
(45)  
ºF (ºC)*  
(−1)  
80  
79  
73  
87  
75  
71  
76  
(10)  
116  
112  
103  
110  
108  
92  
(29)  
139  
141  
142  
136  
139  
139  
135  
(35)  
141  
144  
144  
138  
141  
142  
137  
XP13−018  
XP13−024  
XP13−030  
XP13−036  
XP13−042  
XP13−048  
XP13−060  
66  
65  
58  
78  
60  
59  
63  
96  
93  
88  
98  
89  
84  
88  
136  
134  
119  
128  
125  
95  
136  
138  
139  
133  
135  
135  
131  
138  
139  
140  
134  
136  
136  
132  
138  
139  
141  
134  
137  
137  
133  
138  
140  
141  
136  
138  
138  
134  
140  
143  
143  
137  
140  
140  
136  
142  
145  
145  
138  
142  
142  
138  
144  
144  
146  
139  
143  
143  
139  
145  
145  
147  
139  
145  
144  
140  
147  
146  
147  
140  
146  
147  
142  
101  
113  
*Temperature of the air entering the outside coil.  
506728−01  
Page 26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Liquid Pressure  
Model  
Number  
Heating  
Cooling  
20  
(−7)  
30  
(−1)  
40  
(4.5)  
50  
(10)  
60  
(16)  
65  
(18)  
70  
(21)  
75  
(24)  
80  
(27)  
85  
(29)  
90  
(32)  
95  
(35)  
100  
(38)  
105  
(41)  
110  
(43)  
115  
(45)  
ºF (ºC)*  
13HPX−018  
13HPX−024  
13HPX−030  
13HPX−036  
13HPX−042  
13HPX−048  
13HPX−060  
275  
267  
267  
289  
275  
274  
275  
289  
283  
279  
309  
288  
286  
287  
305  
299  
292  
301  
299  
299  
293  
323  
316  
305  
335  
313  
309  
326  
340  
334  
317  
353  
324  
316  
339  
236  
251  
259  
264  
238  
245  
259  
252  
271  
283  
284  
258  
265  
272  
272  
293  
307  
305  
280  
285  
294  
294  
315  
331  
327  
303  
307  
315  
316  
337  
355  
350  
325  
330  
343  
339  
361  
379  
372  
350  
354  
366  
363  
386  
403  
399  
375  
381  
388  
389  
413  
427  
425  
402  
409  
416  
415  
441  
451  
452  
430  
438  
443  
443  
471  
475  
480  
459  
469  
474  
472  
502  
499  
510  
490  
505  
494  
*Temperature of the air entering the outside coil.  
Table 5. HFC−410A Temperature (°F) − Pressure (Psig)  
°F  
°C  
Psig  
°F  
°C  
Psig  
−40  
−35  
−30  
−25  
−20  
−15  
−10  
−5  
−40.0  
−37.2  
−34.4  
−31.7  
−28.9  
−26.1  
−23.3  
−20.6  
−17.8  
−15.0  
−12.2  
−9.4  
11.6  
14.9  
18.5  
22.5  
26.9  
31.7  
36.8  
42.5  
48.6  
55.2  
62.3  
70.0  
78.3  
87.3  
96.8  
107  
60  
65  
15.6  
18.3  
21.1  
23.9  
26.7  
29.4  
32.2  
35.0  
37.8  
40.6  
43.3  
46.1  
48.9  
51.7  
54.4  
57.2  
60.0  
62.8  
65.6  
170  
185  
201  
217  
235  
254  
274  
295  
317  
340  
365  
391  
418  
446  
476  
507  
539  
573  
608  
70  
75  
80  
85  
90  
95  
0
100  
105  
110  
115  
120  
125  
130  
135  
140  
145  
150  
5
10  
15  
20  
25  
30  
35  
40  
45  
50  
55  
−6.7  
−3.9  
−1.1  
1.7  
4.4  
118  
7.2  
130  
10.0  
12.8  
142  
155  
Page 27  
XP13 SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Bi−Flow Liquid Line Filter Drier  
The unit is equipped with a large−capacity biflow filter drier  
which keeps the system clean and dry. If replacement is  
necessary, order another of the same design and capacity.  
The replacement filter drier must be suitable for use with  
HFC−410A refrigerant.  
System Operation  
IMPORTANT  
Some scroll compressor have internal vacuum protector  
that will unload scrolls when suction pressure goes  
below 20 psig. A hissing sound will be heard when the  
compressor is running unloaded. Protector will reset  
when low pressure in system is raised above 40 psig. DO  
NOT REPLACE COMPRESSOR.  
Defrost System  
The XP13 defrost system includes two components: a  
defrost thermostat (S6) and a defrost control (CMC1)  
High Pressure Switch (S4)  
This unit is equipped with a auto-reset high pressure  
switch (single−pole, single−throw) which is located on the  
liquid line. The switch shuts off the compressor when  
discharge pressure rises above the factory setting. High  
Pressure (auto reset) − trip at 590 psig, reset at 418 psig.  
FIELD SELECT  
TIMING PINS  
TEST  
PINS  
DIAGNOSTIC  
LEDS  
Low Pressure Switch (S87)  
COMPRESSOR  
DELAY PINS  
This unit is equipped an auto−reset low pressure switch  
which is located on the vapor line. The switch shuts off the  
compressor when the vapor pressure falls below the  
factory setting. Low Pressure (auto reset) − trip at 25 psig,  
reset at 40 psig.  
REVERSING  
VALVE  
24V TERMINAL  
STRIP  
CONNECTIONS  
S87  
LOW PRESSURE  
SWITCH  
Low Pressure Switch Bypass (S41) (Optional)  
For use in applications where the heat pump is operated in  
outdoor ambient temperatures below 15°F.  
DEFROST  
THERMOSTAT  
S
S
Prevents nuisance trips form the low pressure switch  
Wired in parallel with the low pressure switch  
S4  
HIGH PRESSURE  
SWITCH  
Thermal Protection Switch (S173) ꢀ Compressor  
Mounted  
Figure 22. Defrost Control (CMC1)  
Some units are equipped with a compressor mounted  
normally closed temperature switch that prevents  
compressor damage due to overheating caused by  
internal friction. The switch is located on top of the  
compressor casing (see figure 1). This switch senses the  
compressor casing temperature and opens at 239−257°F  
(115°C−125°C) to shut off compressor operation. The  
auto−reset switch closes when the compressor casing  
temperature falls to 151−187°F (66°C−86°C), and the  
compressor is re−energized. This single−pole, single−throw  
(SPST) bi−metallic switch is wired in series with the 24V Y  
input signal to control compressor operation.  
DEFROST CONTROL (CMC1)  
The defrost control includes the combined functions of a  
time/temperature defrost control, defrost relay, diagnostic  
LEDs and terminal strip for field wiring connections.  
The defrost control provides automatic switching from  
normal heating operation to defrost mode and back. When  
the defrost thermostat is closed, the control accumulates  
compressor run time at 30, 60 or 90 minute field adjustable  
intervals. When the selected compressor run time interval  
is reached, the defrost relay is energized and defrost  
begins.  
Defrost Control Timing Pins (P1)  
Each timing pin selection provides  
Crankcase Thermostat (S40) (−042, −048 and −060  
Units Only)  
a
different  
accumulated compressor run time period for one defrost  
cycle. This time period must occur before a defrost cycle  
is initiated. The defrost interval can be adjusted to 30  
(T1), 60 (T2), or 90 (T3) minutes (see figure 22). The  
maximum defrost period is 14 minutes and cannot be  
adjusted.  
The reference models are equipped with a 70 watt, belly  
band type crankcase heater. HR1 prevents liquid from  
accumulating in the compressor. HR1 is controlled by a  
thermostat located on the liquid line. When liquid line  
temperature drops below 50° F the thermostat closes  
energizing HR1. The thermostat will open, de−energizing  
HR1 once liquid line temperature reaches 70° F .  
NOTE ꢀ Defrost control part number is listed near the P1  
timing pins.  
Defrost Thermostat (S6)  
S
Units with defrost control 100269−02: Factory default  
is 60 minutes  
The defrost thermostat is located on the liquid line between  
the check/expansion valve and the distributor. When  
defrost thermostat senses 42°F (5.5°C) or cooler, the  
thermostat contacts close and send a signal to the defrost  
control to start the defrost timing. It also terminates defrost  
when the liquid line warms up to 70°F (21°C).  
S
Units with defrost control 100269−04: Factory default  
is 90 minutes  
If the timing selector jumper is missing, the defrost  
control defaults to a 90−minute defrost interval.  
506728−01  
Page 28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Compressor Delay (P5)  
power-up, the defrost control will ignore the test pins.  
When the jumper is placed across the TEST pins for two  
seconds, the defrost control will enter the defrost mode. If  
the jumper is removed before an additional 5−second  
period has elapsed (7 seconds total), the unit will remain in  
defrost mode until the defrost thermostat opens or 14  
minutes have passed. If the jumper is not removed until  
after the additional 5−second period has elapsed, the  
defrost will terminate and the test option will not function  
again until the jumper is removed and re−applied.  
The defrost control has a field−selectable function to  
reduce occasional sounds that may occur while the unit is  
cycling in and out of the defrost mode.  
S
Units with defrost control 100269−02: The compressor  
will be cycled off for 30 seconds going in and out of the  
defrost mode when the compressor delay jumper is  
removed.  
S
Units with defrost control 100269−04: The compressor  
will be cycled off for 30 seconds going in and out of the  
defrost mode when the compressor delay jumper is  
installed.  
Defrost Control Diagnostic LEDs  
The defrost board uses two LEDs for diagnostics. The  
LEDs flash a specific sequence according to the condition.  
NOTE ꢀ The 30-second compressor feature is ignored  
when jumpering the TEST pins.  
Table 6. Defrost Control (CMC1) Diagnostic LEDs  
Mode  
Green LED (DS2) Red LED (DS1)  
Time Delay  
No power to con-  
trol  
The timed-off delay is five minutes long. The delay helps to  
protect the compressor from short-cycling in case the  
power to the unit is interrupted or a pressure switch opens.  
The delay is bypassed by placing the timer select jumper  
across the TEST pins for 0.5 seconds.  
OFF OFF  
Normal operation /  
power to control  
Simultaneous Slow FLASH  
Alternating Slow FLASH  
Anti-short cycle  
lockout  
Test Mode (P1)  
High pressure  
switch fault  
Slow FLASH  
ON  
OFF  
OFF  
A TEST option is provided for troubleshooting. The TEST  
mode may be started any time the unit is in the heating  
mode and the defrost thermostat is closed or  
jumpered. If the jumper is in the TEST position at  
High pressure  
switch lockout  
Page 29  
XP13 SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE The filter and all access panels must be in place  
any time the unit is in operation.  
Maintenance  
DEALER  
HOMEOWNER  
Maintenance and service must be performed by a qualified  
installer or service agency. At the beginning of each  
cooling season, the system should be checked as follows:  
Cleaning of the outdoor unit’s coil should be performed by  
a trained service technician. Contact your dealer and set  
up a schedule (preferably twice a year, but at least once a  
year) to inspect and service your outdoor unit. The  
following maintenance may be performed by the  
homeowner.  
Outdoor Unit  
1. Clean and inspect the outdoor coil. The coil may be  
flushed with a water hose. Ensure the power is turned  
off before you clean the coil.  
IMPORTANT  
2. Outdoor fan motor is prelubricated and sealed. No  
further lubrication is needed.  
Sprinklers and soaker hoses should not be installed  
where they could cause prolonged exposure to the  
outdoor unit by treated water. Prolonged exposure of the  
unit to treated water (i.e., sprinkler systems, soakers,  
waste water, etc.) will corrode the surface of steel and  
aluminum parts and diminish performance and longevity  
of the unit.  
3. Visually inspect connecting lines and coils for  
evidence of oil leaks.  
4. Check wiring for loose connections.  
5. Check for correct voltage at the unit (with the unit  
operating).  
6. Check amp−draw outdoor fan motor.  
Outdoor Coil  
The outdoor unit must be properly maintained to ensure its  
proper operation.  
UNIT NAMEPLATE: _________ ACTUAL: __________  
NOTE − If owner reports insufficient cooling, the unit should  
be gauged and refrigerant charge checked.  
S
S
S
Please contact your dealer to schedule proper  
inspection and maintenance for your equipment.  
Outdoor Coil  
Make sure no obstructions restrict airflow to the  
outdoor unit.  
It may be necessary to flush the outdoor coil more  
frequently if it is exposed to substances which are  
corrosive or which block airflow across the coil (e.g., pet  
urine, cottonwood seeds, fertilizers, fluids that may contain  
high levels of corrosive chemicals such as salts)  
Grass clippings, leaves, or shrubs crowding the unit  
can cause the unit to work harder and use more  
energy.  
S
Keep shrubbery trimmed away from the unit and  
periodically check for debris which collects around the  
unit.  
S
S
Outdoor Coil ꢀ The outdoor coil may be flushed with  
a water hose.  
Outdoor Coil (Sea Coast) ꢀ Moist air in ocean  
locations can carry salt, which is corrosive to most  
metal. Units that are located near the ocean require  
frequent inspections and maintenance. These  
inspections will determine the necessary need to wash  
the unit including the outdoor coil. Consult your  
installing contractor for proper intervals/procedures  
for your geographic area or service contract.  
Routine Maintenance  
In order to ensure peak performance, your system must be  
properly maintained. Clogged filters and blocked airflow  
prevent your unit from operating at its most efficient level.  
1. Air Filter ꢀ Ask your Lennox dealer to show you  
where your indoor unit’s filter is located. It will be either  
at the indoor unit (installed internal or external to the  
cabinet) or behind a return air grille in the wall or  
ceiling. Check the filter monthly and clean or replace  
it as needed.  
INDOOR UNIT  
1. Clean or change filters.  
2. Disposable Filter ꢀ Disposable filters should be  
replaced with a filter of the same type and size.  
2. Adjust blower speed for cooling. Measure the pressure  
drop over the coil to determine the correct blower CFM.  
Refer to the unit information service manual for pressure  
drop tables and procedure.  
NOTE If you are unsure about the filter required for your  
system, call your Lennox dealer for assistance.  
3. Reusable Filter ꢀ Many indoor units are equipped  
with reusable foam filters. Clean foam filters with a  
mild soap and water solution; rinse thoroughly; allow  
filter to dry completely before returning it to the unit or  
grille.  
3. Check blower drive belt for wear and proper tension.  
4. Check all wiring for loose connections  
5. Check for correct voltage at unit (blower operating).  
6. Check amp−draw on blower motor.  
NOTE The filter and all access panels must be in place  
any time the unit is in operation.  
UNIT NAMEPLATE: _________ ACTUAL: __________  
4. Indoor Unit ꢀ The indoor unit’s evaporator coil is  
equipped with a drain pan to collect condensate  
formed as your system removes humidity from the  
inside air. Have your dealer show you the location of  
the drain line and how to check for obstructions. (This  
would also apply to an auxiliary drain, if installed.)  
INDOOR COIL  
1. Clean coil, if necessary.  
2. Check connecting lines and coils for signs of oil leaks.  
3. Check condensate line and clean, if necessary.  
506728−01  
Page 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Thermostat Operation  
See the thermostat homeowner manual for instructions on  
how to operate your thermostat.  
In EMERGENCY HEAT mode, all heating demand is  
satisfied by auxiliary heat; heat pump operation is locked  
out. After a six-hour compressor crankcase warm-up  
period, the thermostat can be switched to the HEAT setting  
and normal heat pump operation may resume.  
Heat Pump Operation  
Your new Lennox heat pump has several characteristics  
that you should be aware of:  
Preservice Check  
If your system fails to operate, check the following before  
calling for service:  
S
Heat pumps satisfy heating demand by delivering  
large amounts of warm air into the living space. This  
is quite different from gas- or oil-fired furnaces or an  
electric furnace which deliver lower volumes of  
considerably hotter air to heat the space.  
S
S
S
S
S
S
Verify room thermostat settings are correct.  
Verify that all electrical disconnect switches are ON.  
Check for any blown fuses or tripped circuit breakers.  
Verify unit access panels are in place.  
S
Do not be alarmed if you notice frost on the outdoor coil  
in the winter months. Frost develops on the outdoor  
coil during the heating cycle when temperatures are  
below 45F (7C). The heat pump control activates a  
defrost cycle lasting 5 to 15 minutes at preset intervals  
to clear the outdoor coil of the frost.  
Verify air filter is clean.  
If service is needed, locate and write down the unit  
model number and have it handy before calling.  
Accessories  
S
During the defrost cycle, you may notice steam rising  
from the outdoor unit. This is a normal occurrence. The  
thermostat may engage auxiliary heat during the  
defrost cycle to satisfy a heating demand; however,  
the unit will return to normal operation at the  
conclusion of the defrost cycle.  
For update−to−date information, see any of the following  
publications:  
S
S
S
Lennox XP13 Engineering Handbook  
Lennox Product Catalog  
Lennox Price Book  
Extended Power Outage  
The heat pump is equipped with a compressor crankcase  
heater which protects the compressor from refrigerant  
slugging during cold weather operation.  
If power to your unit has been interrupted for several hours  
or more, set the room thermostat selector to the  
EMERGENCY HEAT setting to obtain temporary heat  
without the risk of serious damage to the heat pump.  
Page 31  
XP13 SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start−Up and Performance Checklist  
Job Name  
Job Location  
Installer  
Job no.  
City  
Date  
State  
City  
State  
Unit Model No.  
Serial No.  
Service Technician  
Nameplate Voltage  
Rated Load Ampacity  
Compressor Amperage:  
Maximum Fuse or Circuit Breaker  
Electrical Connections Tight?  
Indoor Blower RPM  
-
Indoor Filter clean?  
-
Supply Voltage (Unit Off)  
S.P. Drop Over Indoor (Dry)  
Outdoor Coil Entering Air Temp.  
Vapor Pressure;  
Refrigerant Lines: Leak Checked? - Properly Insulated?  
-
-
Outdoor Fan Checked?  
Voltage With Compressor Operating  
THERMOSTAT  
-
Service Valves:  
Fully Opened? - Caps Tight?  
SEQUENCE OF OPERATION  
Calibrated?  
-
Properly Set? - Level?  
-
Heating Correct?  
-
Cooling Correct?  
-
506728−01  
Page 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 

Lanier Copier LD060 User Manual
Link electronic Switch VSW 822 User Manual
Linksys Network Card SPA 1001 User Manual
LST Smoke Alarm BC016 2 User Manual
LST Smoke Alarm EDS500 1 User Manual
Marantz Blu ray Player UD8004 User Manual
Maytag Microwave Oven Electric Microwave User Manual
Maytag Oven W10354190C User Manual
McIntosh Speaker XR27 User Manual
Melissa Fan 671 107 User Manual