INSTALLATION AND OPERATION MANUAL
TM
Catalytic Vent-Free
Wall-Mounted Gas Fireplace
Models: Scandium-NG and Scandium-LP
P/N 850,055M REV. E, 11/2008
Installer: Leave This Manual With The Appliance.
Consumer: Retain This Manual For Future Reference.
A Spanish manual is available upon request. Order P/N 850,055LS.
Este manual está disponible en espanol por solicitud. Pida P/N
850,055LS para la versión en espanol.
I
n the Commonwealth of Massachusetts:
Portland
• Installation must be performed by a licensed plumber or gas fitter
• See Table of Contents for location of additional Commonwealth of
Massachusetts requirements
US
Scandium™
Report No. 317-S-05-5
WARNINGS
• Hot! Do not touch! This appliance will be hot during operation and will retain heat for a while after
shutting off the appliance. Severe burns may result.
• Carefully supervise children in the same room as appliance.
• Due to high temperatures, the appliance should be located out of traffic and away from furniture or
draperies.
• Do not place clothing or other materials on or near this appliance.
• Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to
this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
• Do not build a wood fire. Do not burn wood or other material in these appliances.
• Thisisanunventedgaslogappliance. Itusesair(oxygen)fromtheroominwhichitisinstalled. Provisionsforadequate
combustion and ventilation air must be provided. Refer to Combustion and Ventilation Air Section in this manual.
• This appliance may be installed in an aftermarket, permanently located, manufactured (mobile) home, where
not prohibited by local codes.
• The appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible
for use with other gases.
• Lennox™ vent-free appliances are designed for use as a supplemental heater. They are not intended for continuous
use as a primary heat source.
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property
damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not light any appliance.
• Do not touch any electrical switches; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow your gas supplier's instructions.
• If your gas supplier cannot be reached, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Download from Www.Somanuals.com. All Manuals Search And Download.
These heaters are fitted with a specially designed pilot utilizing an
oxygen depletion sensor (ODS) which responds to the amount of
oxygen available in the room and shuts the heater off before the
oxygen level drops below 18%. It must not be adjusted or put out
of operation. If replaced then manufacturers original parts must be
used. The pilot can be relit only when fresh air is available. Refer to
the Combustion and Ventilation Air section.
CONGRATULATIONS ON THE PURCHASE OF YOUR NEW
GAS APPLIANCE MANUFACTURED BY LENNOX HEARTH
PRODUCTS.
When you purchased your new gas fireplace, you joined the ranks of
thousands of individuals whose answer to their home heating needs
reflects their concern for efficiency and our environment. We extend
our continued support to help you achieve the maximum benefit and
enjoyment available from your new gas fireplace. It is our goal at Lennox
Hearth Products to provide you, our valued customer, with an appliance
that will ensure years of trouble-free warmth and pleasure.
The appliance is designed to fit various types of situations as listed
in the installation requirements.
This appliance is factory set for operation on the gas type, and at the
pressure stated on the appliance rating plate.
Thank you for selecting a Lennox Hearth Products gas fireplace as the
answer to your supplemental home heating needs.
Sincerely, All of us at Lennox Hearth Products
Readalltheseinstructionsbeforecommencinginstallation.Allinstruc-
tions must be left in the possession of the user for safekeeping.
TABLE OF CONTENTS
Section Contents
Page No.
2
3.0 PACKAGING LIST
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
Safety And Warning Information . . . . . . . . . . . . .
General Information. . . . . . . . . . . . . . . . . . . . . . .
3
3
3
4
4
4
5
6
6
7
8
8
9
9
Quantity
Description
Packaging List. . . . . . . . . . . . . . . . . . . . . . . . . . .
Appliance Specifications . . . . . . . . . . . . . . . . . . .
Unpacking the Appliance . . . . . . . . . . . . . . . . . . .
Burn-in Period. . . . . . . . . . . . . . . . . . . . . . . . . . .
Codes, Massachusetts & New York. . . . . . . . . . .
Combustion And Ventilation Air. . . . . . . . . . . . . .
Site Requirements. . . . . . . . . . . . . . . . . . . . . . . .
1
1
1
1
1
1
Firebox And Burner Assembly
Installation And Operation Instructions
Glass Facia Panel Assembly
Fitting Template
Screw And Wall Plug Pack
Rubber Grommet
10.0 Preparing The Appliance . . . . . . . . . . . . . . . . . . .
11.0 Mounting The Appliance . . . . . . . . . . . . . . . . . . .
12.0 Checking The Burner . . . . . . . . . . . . . . . . . . . . . .
13.0 Connecting A Gas Line . . . . . . . . . . . . . . . . . . . .
14.0 Checking The Gas Connections . . . . . . . . . . . . . .
15.0 Gas Pressure Check. . . . . . . . . . . . . . . . . . . . . . .
4.0 APPLIANCE SPECIFICATIONS
Gas Type
Natural Gas
PropaneGas
16.0 Spark Gap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
17.0 Assembly of the Glass Facia . . . . . . . . . . . . . . . . 10
18.0 Fitting the Glass Facia . . . . . . . . . . . . . . . . . . . . . 11
19.0 Fitting the side panels . . . . . . . . . . . . . . . . . . . . . 11
20.0 Briefing The Customer. . . . . . . . . . . . . . . . . . . . . 12
21.0 Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
22.0 Servicing The Burner. . . . . . . . . . . . . . . . . . . . . . 12
23.0 Pilot Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . 12
24.0 Catalysts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
25.0 Testing For Firebox Leakage . . . . . . . . . . . . . . . . 13
26.0 Cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
27.0 Lighting Instructions & Turning Off Appliance. . . 14
28.0 Troubleshooting Guide. . . . . . . . . . . . . . . . . . . . . 15
29.0 Replacement Parts List . . . . . . . . . . . . . . . . . . . . 16
30.0 Positioning Of Field Assembled Parts . . . . . . . . . 17
31.0 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
32.0 Product Reference Information . . . . . . . . . . . . . . 20
10.5” w.c.
6” w.c.
13”w.c.
11”w.c.
Gas inlet pressure
Max.
Min.
Regulator Pressure Setting
Max Energy Input
5” w.c.
10”w.c.
11,950 BTU/hour
6,8ꢀ0 BTU/hour
560 BTU/hour
10,ꢀ35BTU/hour
6,8ꢀ0BTU/hour
560BTU/hour
Min Energy Input
Pilot Energy Input
ꢀ.4” w.c.
0.8” w.c.
5.5”w.c.
ꢀ.4”w.c.
Burner Pressure
(Manifold)
High
Low
Main burner flow restrictor
(burner orifice)
ꢀ.0 mm (0.079”)
1.45mm(0.057”)
Oxypilot
SIT/Bray 908ꢀ
3/8” NPT at regulator
Piezo spark
SIT/Bray9ꢀ84
3/8” NPTatregulator
Piezospark
Gas Inlet Connection
Ignition
Spark Gap
1/8” - 3/16”
1/8”-3/16”
Please see Data Plate affixed to appliance for current data. This applianceisforuse
only with the gas type, and at the pressure stated on the appliance DataPlate.
ꢀ.0 GENERAL INFORMATION
Table1
This appliance is a high efficiency, unvented, flame effect gas heater.
It provides radiant and convected warmth both efficiently and safely
utilizing the latest type catalytic convertor burner technology. The
appliance does not require a flue system of any type as the catalytic
converter cleans the flue products to provide a complete combustion
system, which is intrinsically safe.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Massachusetts Requirements
5.0 UNPACKING THE APPLIANCE
These fireplaces are approved for installation in the US state of Massa-
chusetts if the following additional requirements are met:
Remove the straps and the top lid of the outer packaging, remove any
instructions or fixing kits. Read ALL these instructions before continuing
to unpack or install this appliance.
• Unvented Room Heaters shall be installed in accordance with 527
CMR 30.00 and 248 CMR 3.00 through 7.00:
Lift off the remaining packaging components.
• Installation and repair must be done by a plumber or gas fitter licensed
in the Commonwealth of Massachusetts
Check that the components supplied with the packaging list on Page
3. Please dispose of all the packaging materials at your local recycling
center.
• The flexible gas line connector used shall not exceed 36 inches (92
centimeters) in length.
• The individual manual shut-off must be a T-handle type valve.
• Vent-Free appliances may NOT be installed in bedrooms or bath-
rooms.
6.0 BURN-IN PERIOD
• A working smoke detector must be installed in the area where vent-
free appliances are installed.
On initial light up of a new appliance, the ‘newness’ will burn off within
the first few hours of operation. During this period some smoke may be
emitted from outlet grill, this should be no cause for concern. Accord-
ingly, the room should be well ventilated with all windows and doors
open during this period.
Seller of unvented propane or natural gas-fired supplemental room
heaters shall provide to each purchaser a copy of 527 CMR 30 upon
sale of the unit.
Depending on your use, the burn-in period may take a few hours or a few
days. Also if you have a sensitive sense of smell you may notice slight
odors during operating after the burn-in period is over.
New York:
KEEPYOURHOUSEWELLVENTILATEDDURINGTHEBURN-INPERIOD.
THE ODOR AND HAZE EMITTED DURING THE BURN-IN PERIOD CAN BE
QUITE NOTICEABLE AND MAY SET OFF A SMOKE DETECTOR. MAKE
SURE SMOKE DETECTORS ARE NOT TOO CLOSE TO THE FIREBOX
(CHECK WITH YOUR LOCAL CODE FOR ALLOWABLE DISTANCES).
These fireplaces are approved for installation in the US state of New York,
but not in New York City.
7.0 CODES
Adhere to all local codes or in their absence the latest edition of The
National Fuel Gas Code ANSI Z223.1 / NFPA 54 - latest edition which can
be obtained from The American National Standards Institute, Inc. (1430
Broadway, New York, NY, 10018) or National Fire Protection Association,
Inc. (Batterymarch Park, Quincy, MA, 02269).
Seller of unvented propane or natural gas fired supplemental room
heaters in the Commonwealth of Massachusetts shall provide to each
purchaser a copy of 527 CMR 30 upon sale of the unit.
This Lennox Hearth Products Unvented Gas Room Heater is certified by
OMNI-Test Laboratories, Inc to ANSI Z21.11.2 standard.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Example:
Vent-free heater #1
8.0 COMBUSTION AND VENTILATION AIR
9,000 BTU/Hr
23,000 BTU/Hr
35,000 BTU/Hr
Vent-free heater #2
Gas appliance #1
(water heater)
This heater shall not be installed in a confined space or unusually tight
constructionunlessprovisionsareprovidedforadequatecombustionand
ventilation air. The heater may be located in unusually tight construction
provided the space is unconfined, or if confined, is provided with two
permanent openings communicating directly with an additional room(s)
of sufficient volume so that the combined volume of all connected spaces
meets the criteria for an unconfined space, (National Fuel Gas Code
NFPA 54 / ANSI Z223.1 - latest edition, Section on Air for Combustion
and Ventilation. Generally 50 ft3 per 1,000 BTU input of all operating
appliances in the space.
Total =
67,000 BTU/Hr
* Do not include direct-vent gas appliances. Direct-vent is sealed com-
bustion and draws combustion air from the outdoors.
4. Compare the maximum BTU/Hr the space can support with the actual
amount of BTU/Hr used.
_______ BTU/Hr (max. the space can support)
_______ BTU/Hr (actual amount of BTU/Hr used)
The National Fuel Gas Code, ANSI Z223.1/NFPA 54, defines a confined
space as a space whose volume is less than 50 ft3 per 1,000 BTU/Hr
(4.8 m3 per kW) of the aggregate input rating of all appliances installed
in that space and an unconfined space as a space whose volume is not
less than 50 ft3 per 1,000 BTU/Hr (4.8 m3 per kW) of the aggregate input
rating of all appliances installed in that space.
Example:
61,440
67,000
BTU/Hr (max. the space can support)
BTU/Hr (actual amount of BTU/Hr used)
The space in the previous example is a confined space because the
actual BTU/Hr used is more than the maximum BTU/Hr the space can
support. You must provide additional fresh air.
Rooms communicating directly with the space in which the appliances
are installed, through openings not furnished with doors, are considered
a part of the unconfined space.
Your options are:
a. Rework equations adding the space of adjoining room(s). If the extra
volume provides an unconfined space, then remove door or add
ventilation grills between rooms. Refer to National Fuel Gas Code,
ANSI Z223.1/NFPA 54-latest edition, Section "Air for Combustion and
Ventilation".
Unusually tight construction is defined as construction where:
a. Wall and ceilings exposed to the outside atmosphere have a continu-
ous water vapor retarder with a rating of one perm (6 X 10-11 kg per
pa-sec-m2) or less with openings gasketed or sealed;
b. Weather stripping has been added on operable windows and doors;
and
b. Vent room directly to the outdoors. Refer to National Fuel Gas Code,
ANSI Z223.1/NFPA 54-latest edition, Section "Air for Combustion and
Ventilation".
c. Install a lower BTU/Hr heater to make the area an unconfined space.
c. Caulkingorsealantsareappliedtoareassuchasjointsaroundwindow
and door frames, between sole plates and floors, between wall ceiling
joints, between wall panels, at penetrations for plumbing, electrical,
and gas lines, and at other openings.
If the actual BTU/Hr used is less than the maximum BTU/Hr the space
can support, then the space is an unconfined space. You will need no
additional fresh air ventilation for an unconfined space.
Use the following equations to determine if you have a confined or
unconfined space.
1. Determine the volume of space — ft3.
WARNING
Length x Width x Height = _____ ft3
If the area in which the heater may be operated is
smallerthanthatdefinedasanunconfinedspaceor
if the building is of unusually tight construction,
provideadequatecombustionandventilationairby
one of the methods described in the national fuel
gascode,ANSIZꢀꢀ3.1/NFPA54,AirforCombustion
and Ventilation Or applicable local codes.
(Include adjoining rooms with doorless passageways or ventilation
grills between rooms).
Example: 24' (L) x 16' (W) x 8' (H) = 3072 ft3
ꢀ. Dividethevolumeofspaceby50ft3 todeterminethemaximumBTU/Hr
the space can support.
______ (volume of space – ft3)/ 50 ft3 =
(Maximum BTU/Hr the space can support)
Example: 3072 ft3 / 50 ft3 = 61.44
or 61,440 BTU/Hr the space can support.
3. Add the BTU/Hr of all the fuel burning appliances in the space.
Vent-Free heater
Gas appliance #1*
Gas appliance #2 +
Gas appliance #3 +
Total =
_______ BTU/Hr
_______ BTU/Hr
_______ BTU/Hr
_______ BTU/Hr
_______ BTU/Hr
5
Download from Www.Somanuals.com. All Manuals Search And Download.
The minimum clearance to the ceiling above the appliance is 32” mea-
sured from the top of the appliance glass panel.
9.0 SITE REQUIREMENTS
Combustible materials should not be positioned directly in front of the
appliance within a distance of 40”.
This appliance is designed to be wall-hung. Do not recess any part of
the appliance into the wall.
Under no circumstances should any electrical equipment e.g. plasma
screen TV sets etc. be positioned on the wall above the appliance. The
appliance is designed to be wall mounted alone and not in conjunction
with any type of combustible fire surround.
This appliance may be installed in any room in a home except bedrooms
or bathrooms - or areas where large amounts of steam are likely to be
generated.
It should be noted that heaters create warm air currents. These currents
move heat to wall surfaces next to the heater. Installing the heater next
to vinyl or cloth wall coverings or operating the heater where impuri-
ties in the air (such as tobacco smoke or candle smoke) exist, may
discolor walls.
No combustible shelves should be positioned on the wall above the
appliance.
It should be established that any mirrors or picture frames etc. to
be positioned on the wall above the appliance are able to withstand
prolonged exposure to moderate heat and moisture before proceeding
with their installation.
Installation in living rooms is common, however other rooms such as
kitchens, dining rooms and hallways are permitted, providing a suitable
gas supply is available, and rooms sizing and ventilation requirements
are strictly adhered to (see Section 8.0).
The wall must be structurally sound and constructed from a material
capable of withstanding moderate heat. Finished plaster, conventional
wall paper and dry-lined plasterboard are examples of suitable materi-
als. Materials such as flock, blown vinyl and embossed paper which are
sensitive to even small amounts of heat should be avoided as scorching
and or discoloration may occur over time.
Theapplianceisdesignedtobeversatile,andassuchwilloperatecorrectly
when exposed to normal gentle drafts experienced within the home. It
is not recommended, however that the appliance be installed in areas
where it is likely to be exposed to persistent strong drafts, that may be
generated by outside doors or windows, air vents etc. It is recommended
that the appliance should not be installed within 20” of any air vent.
If the appliance is to be mounted on a dry-lined wall or a timber framed
construction wall then the integrity and ability of the wall to carry the
weight of the appliance must be confirmed. It is important in these
circumstances that any vapor control barrier is not damaged, and that
any structural members of the house frame are not damaged.
CAUTION
The back of the appliance may be installed directly
onto a combustible wall or non-combustible wall,
providing the area behind the appliance is flat and
does not interfere with the various vent holes in the
back panel of the appliance.
The appliance may be positioned as close to a solid floor (i.e. stone,
wooden laminate etc.) as the particular design of fire frame permits,
however it is not permitted to install the appliance within 4” of carpet,
rugs or fabric materials of any kind. This dimension is measured verti-
cally to the bottom of the appliance frame.
10.0 PREPARING THE APPLIANCE
Follow the steps below:
CLEARANCES TO NON-COMBUSTIBLES
Non-combustible surfaces are defined as brick, metal, marble, concrete
etc. and also a number of man-made materials impervious to flame. If in
doubt refer to the material manufacturer for further information before
proceeding with installation.
Gas connection: The heater gas inlet connection is 3/8” NPT at the
regulator, located below the burner, in the center of the heater.
Clearances to the sides of the appliance are 4”. Clearance to the front
of the appliance is 20”.
There are four possible entry points for the gas supply pipe-work to
enter the appliance firebox. These entry points are ‘knock out’ type holes
(shown in Figure 1).
Theappliancemaybeinstalledwithorwithoutanon-combustiblehearth.
If a hearth is fitted, the size and design may be as desired.
A non-combustible shelf of any depth may be positioned above the
appliance provided it is no closer than 16” from the top of the appli-
ance glass panel and the wall above the appliance is non-combustible.
CLEARANCES TO COMBUSTIBLE MATERIALS
Combustible materials are defined as wood, fabrics, or other materials
likely to combust if exposed to flame. Generally, any material, which is
likely to discolor, melt or misshape when exposed to moderate heat,
should be considered as a combustible material or surface.
Clearance to the sides of the appliance are 4” but curtains, drapes and
other fabrics are not permitted within a distance of 20” of the appliance
sides. No such materials are permitted directly above the appliance
regardless of distance.
Figure 1 - Gas Supply Entry Points
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Non-concealed gas connections may be made using the entry points
on the base of the firebox. A concealed gas connection may be made
using the knockout hole in the center back of the firebox. Select the most
appropriate entry point and knock out the relevant hole.
WARNING
The wall where the appliance is to be installed must
be capable of long-term support of the total load of
the appliance. Measures should also be taken to
ensure sufficient strength to withstand the force of
earthquakes, vibration and other external forces.
Ifaconcealedgasconnectionistobemade,thesupplypipeshouldalways
be sleeved through walls and floors using the shortest possible route.
For concealed supply pipe routing, pipes must (where possible) be ver-
ticalandprovidingthereissufficientwallthicknessavailable, theyshould
be placed in pipe chases. Horizontal pipe runs should be avoided where
possible. Prior to chasing a solid wall, an inspection should be made
to note the proximity of any cables/sockets outlets which may already
be buried. Pipes must be secured using suitable clips and protected
againstcorrosion.Ideallyfactoryfinishedprotectedpipe-workandfittings
should be used. Joints should be kept to a minimum and compression
fittings must not be used. The pipe-work installation must be tested for
soundness before any protection is applied and/or the pipe-work and
fittings are buried.
Incorrect installation can cause the appliance to fall from the wall and
cause injury. Do not block the ventilation holes of the appliance. The
wall onto which the appliance is installed must be flat. Install only on a
vertical surface. Avoid sloped surfaces. Installation onto anything other
than a vertical wall may result in fire, damage or injury.
A full size fitting template is supplied to assist with wall mounting.
Mark the positions shown as “Fixing Points” on the wall. If the appli-
ance is to be mounted on the inner leaf of a conventional cavity wall,
or a solid wall, drill four holes using a 5/16" masonry bit, to a depth of
1-11/16". Insert the wall plugs provided.
11.0 MOUNTING THE APPLIANCE
After having selected the final mounting position of the appliance, taking
intoaccountthesiterequirementsasspecifiedinSection8oftheseinstruc-
tions, the integrity of the wall, and the feasibility of the proposed supply
pipe routing, the firebox of appliance may be secured to the wall.
If the appliance is to be mounted on a dry lined wall or a timber framed
construction wall then special cavity screw fixings will be required which
are not supplied with this product. These should be constructed from
metal and not plastic.
To ensure customer safety, be sure to design the installation so that the
strength of both the wall and any wall fixings used are sufficient. Lennox
HearthProductsassumesnoresponsibilityforinjuriesanddamagesthat
may occur due to improper installation or handling.
If a concealed gas connection is to be made ensure the gas supply pipe
is in it’s final position and can enter the appliance in the correct position
when the appliance is hung on the wall.
The appliance should not be installed until all dry wall sanding and wall
painting has been completed.
POSITION SPIRIT LEVEL ALONG THIS EDGE TO LEVEL TEMPLATE BEFORE MARKING OUT WALL
COLOQUE EL NIVEL SOBRE ESTE BORDE PARA NIVELAR LA PLANTILLA ANTES DE MARCAR LA PARED
16”(406mm)
FIXING POINTS
PIERCE TEMPLATE TO MARK HOLE POSITION ON WALL X 4
PUNTOS DE SUJECION
PERFORE LA PLANTILLA PARA MARCAR LA POSICION DE LOS 4 TALADROS EN LA PARED
™
Scandium
WALL MOUNTED VENT FREE FITTING TEMPLATE
PLANTILLA PARA LA INSTALACION DE CHIMENEAS DE PARED SIN SALIDA DE HUMOS
WARNING
CLEARANCES FROM COMBUSTIBLE MATERIALS
The following clearances must be maintained at all times.
IMPORTANT
THIS APPLIANCE IS TO BE WALL HUNG ONLY.
DO NOT RECESS OR INSET ANY PART OF THE APPLIANCE.
THIS TEMPLATE IS FOR THE MARKING OF FIXING POINTS ONLY.
DO NOT INSTALL THE APPLIANCE WITH THIS TEMPLATE IN PLACE.
IMPORTANTE
Failure to do so may result in the risk of fire.
a
For full information refer to the instruction manual
provided with the heater.
ESTE APARATO UNICAMENTE DEBE SER COLGADO EN UNA PARED.
NO EMPOTRE NINGUN ELEMENTO DE ESTE APARATO.
ESTA PLANTILLA SIRVE UNICAMENTE PARA MARCAR LOS PUNTOS DE FIJACION.
RETIRE LA PLANTILLA ANTES DE COLOCAR LE APARATO.
Clearance to combustible ceiling
32”measured from top of appliance
glass panel
Clearance in
Clearance to
front of
heater 20”
combustible
sidewalls 4”
(both sides)
Note Zero clearance from bottom of heater frame
:
required for hard combustible floors. Minimum 4”
clearance required to rugs or any fabric floor
coverings. REFER TO INSTRUCTION MANUAL
IMPORTANT
:
Fabrics, curtains and drapes are not
permited above the heater at any distance and within
20”of the heater sides. No combustible shelves of any
size are permitted above the heater.
F860041/A
ADVERTENCIA
ESPACIO LIBRE HASTA MATERIALES COMBUSTIBLES
Deben mantenerse en todo momento los siguientes espacios
libres. El no hacerlo puede causar un riesgo de incendio.
Consulte el manual de instrucciones suministrado con este
aparato para obtener información completa.
FIXING POINTS
PUNTOS DE SUJECION
El espacio de 32”hasta un techo
combustible se mide desde el borde
superior del panel de vidrio del aparato
Espacio libre
Espacio hasta
delante del
CONCEALED
paredeslaterales
calentador 20”
combustibles
4”(ambos lados)
GAS INLET
Nota: No se requiere espacio libre desde el borde inferior del
marco del calentador en caso de pisos combustibles duros.
Se requiere un espacio mínimo de 4”entre el calentador
cualquier alfombra, moqueta revestimiento de suelo de
tela. CONSULTE EL MANUAL DE INSTRUCCIONES.
y
o
ENTRADA DE
GAS OCULTA
IMPORTANTE: No se permite la colocación de telas, cortinas
similares por encima del calentador cualquier distancia, ni
y
a
a
una distancia de 20”de los laterales del calentador. No se
permiten estantes combustibles de cualquier tamaño por
encima del calentador.
F860041/A
DO 005855/0
-
ISSUE
A
Figure 2 - Wall Fixing Template
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
7
Download from Www.Somanuals.com. All Manuals Search And Download.
11.0 MOUNTING THE APPLIANCE - continued
IMPORTANT
Hold heater regulator with a wrench to prevent
movement when connecting to inlet piping.
Insert the wall mounting screws into the top wall plugs, taking
care to leave the screws protruding approximately 3/8” from the
wall. Now hang the appliance onto these screws through the two
keyhole shaped holes in the back panel of the appliance.
A qualified gas appliance installer must connect the gas room
heater to the gas supply. Consult all local codes.
Insert the lower mounting screws into the lower wall plugs
through the corresponding depressed holes in the lower part of
the back panel. Do not tighten fully.
The installer must provide an ANSI approved manual shut off
valve, flex connector and 3/8" NPT fitting.
Before tightening the wall mounting screws fully, at this stage
it is recommended to check the horizontal alignment of the
appliance with a bubble level, as small adjustments can still be
made if necessary. When this has been checked, tighten all four
fixing screws fully.
Route gas line using techniques and materials prescribed by
local and/or national codes. Only use pipe of 1/2" or greater size
to allow full gas volume to the gas fireplace. Undue pressure
loss will occur if the pipe is too small.
An external regulator must be used on all propane (L.P.G.)
heaters, in addition to the regulator fitted to the heater, to reduce
the supply tank pressure to 13" w.c. (maximum).
To access the upper fixing screws insert a screwdriver through
the holes in the deflector plates above the catalyst as shown in
Figure 3.
Manual
Shut-Off
Valve
Regulator
Union
Fireplace or
Firebox Wall
Wall
Shut-Off
Key
Fireplace or
Firebox Wall
Figure 3
Sediment
Trap
3"
Down
1ꢀ.0 CHECKING THE BURNER
Figure 4
There are no imitation fuel bed components, such as logs or
rocks, to install. The appliance features a ribbon burner which is
designed to produce a continuous band of flame over its length.
The burner should be visually inspected to ensure it is free from
any foreign matter. If it is necessary to clean or dust off the
burner then the glass door should be removed by removal of
the four retaining screws. Re-fit the glass door after cleaning or
inspection, ensuring a good seal.
An ANSI approved manual shut-off valve and union must be
installed upstream of the heater within the fireplace cavity
when rigid pipe is used. Ensure that a sediment trap is installed
upstream of the heater (Figure 4) within the structure’s piping
system to prevent moisture and contaminants from passing
through the pipe to the heater controls and burner. Failure to do
so could prevent the heater from operating reliably.
The heater gas inlet connection is 3/8” NPT at the regulator,
located below the burner, in the right hand side of the heater.
When tightening up the joint to the regulator hold the regulator
securely with a wrench to prevent the regulator from moving.
13.0 CONNECTING A GAS LINE
WARNING
Connecting directly to a unregulated propane tank
may cause an explosion.
8
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
Download from Www.Somanuals.com. All Manuals Search And Download.
14.0 CHECKING THE GAS CONNECTIONS
WARNING
Never use an open flame to check for leaks.
Gas Valve Cover
Turn on gas supply and test for gas leaks using a gas leak test solution
(also referred to as bubble leak solution).
NOTE: using a soapy water solution (50% dish soap, 50% water) is
an effective leak test solution, but it is not recommended, because the
soap residue that is left on the pipes/fittings can result in corrosion
over time.
Figure 6 - Remove Gas Valve Cover
A. Light the appliance (refer to the lighting instructions label in the con-
trol compartment or on Page 14).
The pressure test points are located as shown in Figure 7. An alternative
burner (manifold test point is located below the left hand side of the
burner as shown in Figure 8).
B. Brush all joints and connections with the gas leak test solution to
check for leaks. If bubbles are formed, or gas odor is detected, turn
the gas control knob (off/pilot/on) to the “OFF” position. Either tighten
or refasten the leaking connection, then retest as described above.
C. When the gas lines are tested and leak free, be sure to rinse off the
leak testing solution.
The pressure regulator on manual models is preset and locked to avoid
tampering. If the pressure is not as specified in Table 1 on Page 3,
replace the burner assembly (see Page 16 for ordering information).
D. Observe the individual tongues of flame on the burner. Make sure all
ports are open and producing flame evenly across the burner. If any
ports are blocked, or partially blocked, clean out the ports.
Replace the test point screws after pressure measurement ensuring no
gas leaks. All instructions must be left in the possession of the user for
safekeeping.
15.0 GAS PRESSURE CHECK
The heater regulator controls the burner pressure which should
be checked at the pressure test points located on the control
valve itself (shown in Figure 7) for burner (manifold) and
regulator (inlet) setting pressures.
The pressure should be checked with the gas heater burning and the
control set to high flame.
The pressure test points are located on the gas valve. To access the
valve and the test points, firstly remove the control knob spindle from
the valve spindle by removing the retaining clip shown in Figure 5.
Retaining clip
Regulator (Inlet)
Pressure Setting
Burner (Manifold) Pressure
Figure 7 - Manifold and Inlet Pressure Taps
Alternate manifold test point
Figure 5 - Remove Retaining Clip
Withdraw the control knob and spindle from the heater, remove the
gas valve cover plate by removing the four retaining screws indicated
in Figure 6.
Figure 8 - Alternate Test Point
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
9
Download from Www.Somanuals.com. All Manuals Search And Download.
16.0 SPARK GAP
Grill fixing holes
Side Piece
The gap between the spark electrode and the pilot should be 1/8” to
3/16” to produce a good spark. There should be no need to adjust this
(DO NOT ATTEMPT TO ADJUST THE GAP). If under any circumstances
the piezo electric spark fails, the pilot cannot be lit manually.
Adjustment to the
1/8" to 3/16" Spark Gap
pilot is Not allowed
Figure 11 - Slide on Side Pieces
3. Ensure the sides are neatly aligned with the glass and secure the sides
using two M6 screws for each side as shown in Figure 12. Do not
overtighten the screws.
Figure 9 - Proper Spark Gap
Finger-tighten all screws until side
and top frame pieces are in place
and aligned. At that point, tighten in
1/4 turn increments until frame
pieces are secure. DO NOT
OVER-TIGHTEN.
17.0 ASSEMBLY OF THE GLASS FACIA
1. Remove the glass panel from all packaging and lay face down on a soft
surface. Identify the top and bottom of the glass facia by observing
the orientation of the keyhole shaped slots in the facia fixing brackets
as shown in Figure 10.
TOP
Figure 12 - Secure Side Pieces
IMPORTANT NOTES:
• The screws that are used to attach the brackets to the facia as seen
in Figures 12 and 14 below MUST NOT be over-tightened. Over-
tightening of the mounting screws may cause the glass facia to
slip from its brackets. The screws should be finger-tightened until
all side and top frame pieces are assembled and aligned. At that
point, tighten the screws in 1/4 turn increments until frame pieces
are firmly positioned and do not move.
Figure 10 - Key Hole Slots on Glass Facia
• If you find that your glass facia is experiencing slippage because of
this over-tightening of the screws, you can use normal RTV sealant
to secure the glass facia to its bracket. Remove the facia from the
fireplace, apply the sealant to the area where the slippage is oc-
curring, and allow the facia to dry face down until the sealant has
dried according to the directions on the sealant packaging.
2. Slide on the side pieces ensuring that the grill fixing holes (shown) are
aligned towards the top of the glass facia (as shown in Figure 11).
4. Position the grill within the two side pieces ensuring a proper fit.
10
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
Download from Www.Somanuals.com. All Manuals Search And Download.
19.0 FITTING THE SIDE PANELS
Remove the two side panel assemblies from the protective packaging
and fit onto the sides of the firebox as shown. Insert the M6 retain-
ing screws in the sides of the firebox and ensure they are unscrewed
approximately 1/8” so the keyhole shaped holes may engage, and the
sides can be hooked on.
TOP
Figure 13
5. Secure the grill in position using two M6 screws and two no. 8 self
tapping screws as shown in Figure 14.
Note:Frontframe/facia
not shown for clarity.
Figure 14 - Secure Grill In Position
Figure 16
18.0 FITTING THE GLASS FACIA
The glass facia panel is supported by four M6 screws which protrude
from the front of the outer casing. Insert the M6 retaining screws and
ensure they are unscrewed approximately 1/8” so the keyhole shaped
holes may engage, and the facia can be hooked on. Ensuring that the
corresponding keyhole shaped holes engage the screwheads fully. Refer
to Figure 15.
Insert
a
screwdriver
through the holes in the
right hand side panel to
access the two M6 fixing
screws (designated ‘a’ in
Figure 17) and tighten
fully. Next insert two no.8
self-tapping screws (des-
ignated ‘b’ in Figure 17)
through the side panel
support bracket, and the
corresponding holes in the
side of the firebox. Tighten
fully. Repeat for the left
hand side panel, which is
secured by tightening the
M6 ‘a’ screws only. The
right-handsidepanelhasa
hinged flap to allow access
to the control knob.
‘a’
‘a’
‘b’
‘b’
Figure 17
Figure 15
11
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
Download from Www.Somanuals.com. All Manuals Search And Download.
ꢀ0.0 BRIEFING THE CUSTOMER
ꢀꢀ.0 SERVICING THE BURNER
WARNING
WARNING
Do not add logs or ornaments such as pine cones,
vermiculite or rock wool. Using these added items
can cause sooting.
Any change to this heater or its controls can be
dangerous.
All instructions must be left in the possession of the user for safekeep-
ing. If at all possible, show the customer how to light and control the
appliance and how to remove and replace the glass facia.
WARNING
Youmustkeepcontrolareas,burnersandcirculatingair
passageways of appliance clean. Failure to keep the
primary air opening(s) of the burner clear may result
in sooting and property damage. Inspect these areas of
appliance before each use. Have appliance inspected
yearly by a qualified service person. Appliance may
need more frequent cleaning due to excessive lint form
carpeting, bedding material, etc.
After commissioning the appliance, the customer should be instructed
on the safe use of the appliance and the need for regular servicing. Fre-
quency of service depends on usage, but MUST be carried out at least
once annually. Advise that cleaning of the appliance may be achieved
when the appliance is cold using a damp cloth and mild detergent on
most surfaces.
Advise that the appliance will emit a "newness" smell for a time after
initial commissioning and that extra ventilation may be needed during
this time.
Advise the user to never place any objects on top of the appliance or
obstruction this area in any way.
First, remove the front Glass facia as described in Section 18.0 only in
reverse, remove the valve cover (4 screws) and disconnect the gas con-
nection inside appliance. The gas connections to the gas valve can now
be released. Undo the four screws retaining the burner brackets to the
base and rear of the firebox. The burner may now be removed.
A periodic visual check of the pilot flame and the burner flame should
be carried out.
ꢀ1.0 SERVICING
Remove the pilot and main burner pipes and blow through to dislodge
any debris. Now remove the in line restrictor and blow through to make
sure it is entirely clear.
WARNING
Unclip the pilot lint gauze and clean with a soft brush. Clean the exterior
of the pilot assembly with a soft brush and blow through the flame ports
on the pilot head. Check the aeration holes are free from lint or dirt. The
pilotassemblycanberemovedifrequiredbydisconnectingtheelectrode
HT lead, gas pipe, thermocouple lead and unscrewing the mounting
screws and lifting away. The pilot assembly is a non-serviceable item
and should not be taken apart. Aeration holes must be clear internally
for proper operation. NEVER MODIFY OR BEND THE THERMOCOUPLE
TO MAKE THE PILOT STAY LIT. Modifications are dangerous and can
have serious unseen effects on safety. If the pilot will not stay lit there
is a problem with dirt, the gas supply to it, or the thermocouple needs
replacement.
Turn off the appliance and allow to cool before cleaning.
Verify proper operation after servicing.
Turn off the fireplace at the gas supply. Ensure that the fireplace is fully
cold before attempting service. A suggested procedure for servicing
is detailed as follows;
1. Lay out the dustsheet and tools.
2. Remove the front glass facia as described in section 17.0, only in
reverse.
3. Remove the glass door assembly (5 screws) and clean carefully.
Remove the valve cover plate (4 screws).
4. Inspect the burner and the catalysts and clean if necessary with a
soft brush.
The gas valve is a non-serviceable item. If this needs replacement,
remove the cover plate then the securing screw holding the valve bracket
in place, remove all pipe unions, and the complete valve. Replacement
must be original manufacturers parts.
5. Disconnect the gas supply. IMPORTANT NOTE: This must be
done by a licensed plumber or gas fitter and must conform to
the requirements of the National Fuel Gas Code NFPA 54 / ANSI
Z223.1 - latest edition.
Re-assemble in the reverse of removal. Ensure setting pressures are as
stated in Table 1 on Page 3.
6. Undo the four screws retaining the burner support brackets to the
base and rear of the firebox.
7. Remove the burner unit, strip off the burner pipes and clean
thoroughly.
8. Clean the in-line restrictor, pilot assembly and the burner tube. Do
not attempt to remove the pilot injector as this can cause damage.
9. Re-assemble components.
10.Re-connect the gas supply. Turn on the gas supply and perform a
gas leak test using gas leak test solution. Check pilot and burner
for good ignition.
11. Refit the valve cover and retaining screws.
12. Refit the glass door assembly.
13. Refit the facia as described in section 16.0.
14. Check the purpose provided ventilation is unobstructed.
15. Light the appliance and test setting pressures.
16. Check safe operation of the appliance.
ꢀ3.0 PILOT ASSEMBLY
WARNING
No adjustments are to be made to the ODS pilot
system.Tamperingwiththissystemcanbeextremely
hazardous.
Remove the glass facia, glass panel and burner unit (as per servicing
section), lint arrestor and pilot assembly by using a screwdriver to
remove the retaining screws.
For specific servicing instructions, see relevant sections.
1ꢀ
Download from Www.Somanuals.com. All Manuals Search And Download.
Clean the pilot assembly with a soft brush and blow through. Check the
aeration holes are free of any dirt or lint. Clean thoroughly internally,
the connection can be removed from the base of the pilot assembly
using two wrenches to make cleaning easier. Do not damage or try to
dismantle the pilot injector. The unit is factory set and the only check
necessary is to ensure the spark gap is correct. See specifications for
gas setting.
Turn on the fireplace as per the operating instructions, and run at
maximum setting for 15 minutes. Position gas sample probe directly
over a catalyst via the outlet grill, on top of the appliance. Record the
carbon dioxide (COꢀ) concentration and then the carbon monoxide (CO)
concentration as displayed by the analyzer - also noting the units in
which the values are expressed. Most analyzers display carbon dioxide
(COꢀ) concentrations in percentage (%) terms and carbon monoxide
concentration in parts per million (ppm) terms.
NEVER MODIFY OR BEND THE THERMOCOUPLE TO MAKE THE PILOT
STAY LIT. If the pilot will not stay lit there is a problem with dirt, the
gas supply, or the thermocouple needs replacement. Modifications are
dangerous and can have a serious unseen effect on safety and therefore
MUST not be done. Replacements must be original manufacturers parts.
Re-assemble in the reverse of removal. Ensure setting pressures are as
stated in Table 1 on Page 3.
In order to calculate the combustion ratio for the appliance (CO/COꢀ)
it is first necessary to express both gas concentrations in terms of per-
centage. To convert from parts per million (ppm) to a percentage (%)
divide the ppm figure by 10,000. Examples : 35ppm = 0.0035%, 15ppm
= 0.0015%, 5ppm = 0.0005%.
Now divide the concentration of carbon monoxide (CO) expressed in
percent by the concentration of carbon dioxide (COꢀ) to obtain the
appliance combustion ratio.
ꢀ4.0 CATALYSTS
CO (%)
COꢀ (%) = ratio
WARNING
The combustion ratio of the gasses emitted by the catalytic convertor
should not exceed 0.0015. If replacing, firstly, remove the glass facia
as described in section 16.0. The catalysts are located on the top of the
internal firebox and can be removed be unscrewing the retaining nuts
securingtheclampingplate. Removethecatalystsandsealsanddiscard.
Refit a new catalysts and seals in reverse order, ensure the catalysts
and door have good seals.
Donotblockthecatalystsortheapplianceoutletgrill.
Blockage may cause high carbon monoxide levels
and/or breakage of the glass facia panel.
WARNING
Do not operate the appliance with the catalyst units
removed.
ꢀ5.0 TESTING FOR FIREBOX LEAKAGE
Appliancesthatareseveralyearsoldorhavebeenextensivelydismantled
should be checked for soundness. It is important that all the products
of combustion pass through the catalytic converters at the top of the
firebox before leaving the appliance.
DO NOT BLOCK
THESE AREAS
The firebox is heated by lighting for a few minutes to provide a flow
through the firebox. The burner is then shut off and a smoke pellet or
match introduced at the base of the fire underneath the burner tray. Large
quantities of smoke will emerge from the top of the appliance, but none
should emerge from the joints or gasket faces, especially around the
door. It is important to note that the appliance can never be expected
to be 100% smoke tight and small quantities of smoke may be seen in
corners of joints and gasket faces etc without affecting safety when the
appliance is in operation.
ꢀ6.0 CLEANING
Figure 18 - Catalysts and Outlet Grill
WARNING
Turn off the unvented gas room heater and allow to
cool before cleaning.
It is recommended that the catalysts are inspected for signs of damage
and dirt during routine servicing procedures. The expected life of the
catalysts is in excess of 11,000 hours (10 years of normal use). After
this time the catalyst should be replaced.
If there are any deposits of dirt or soot on the catalysts they should be
cleaned with a soft brush and a vacuum cleaner. If removed for cleaning
ensure the seals are in good condition before replacing the catalyst. New
seals will usually be required.
GLASS PANEL -This can be cleaned with a suitable glass cleaner. The
following solutions are approved for use to clean glass.
• Non-ammonia based household cleaner
• 50% -50% mix of white vinegar and water
• Gas fireplace/stove glass cleaner
The performance of the catalyst may be checked using a combustion
gas analyzer as follows.
PAINTED AREAS - These can be cleaned using a dry cloth.
FINISHEDMETALAREAS-Thesecaneitherbecleanedusingaproprietary
metal cleaner or baby oil. Test on a small hidden part before cleaning.
Always clean in the direction of the grain.
Important: The temperature of the gases emitted by the catalytic
converters reach very high temperatures (up to 700° F). Measuring
gas of this temperature may damage some types of gas analyzers. If
in doubt consult the equipment manufacturer.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
13
Download from Www.Somanuals.com. All Manuals Search And Download.
ꢀ7.0 LIGHTING INSTRUCTIONS & TURNING OFF APPLIANCE
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY
RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
• Immediately call your gas supplier from a neighbor’s phone.
This appliance has a pilot which must be lit with a piezo spark
igniter. When lighting the pilot, follow these instructions exactly.
A.
B.
Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
BEFORE OPERATING smell all around the heater area for gas. Be
sure to smell next to the floor because some gas is heavier than
air and will settle on the floor.
C.
D.
Use only your hand to push in or turn the gas control knob.
Never use tools. If the knob will not push in or turn by hand, do
not try to repair it, call a qualified service technician. Forced or
attempted repair may result in a fire or explosion.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
Do not use this heater if any part has been under water.
Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and any
gas control which has been under water.
• Do not touch any electric switch; do not use any phone in your
building.
LIGHTING INSTRUCTIONS
1. Stop! Read the safety information above.
ꢀ. Make sure manual shut-off valve is fully open.
3. Open the glass facia.
8. Continue turning counter-clockwise
to the PILOT light position, ensuring the pilot has lit. If not, turn the knob
fully clockwise, and repeat.
through the spark click
9. Hold the control knob in for a further 10 seconds to prevent the flame
failure detector from shutting off the gas while the probe is warming up.
4. Depress control knob in and turn clockwise
to the
“OFF” position (Figure 19).
10. Release the control knob while turning counter-clockwise
to the preferred setting. Close the control access panel.
5. Wait 5 minutes to clear out any gas. Then smell for gas, including near
the floor. If you smell gas, STOP! Follow the safety instructions in “What to
do if you smell gas” under section ‘B’ above. If you do not smell gas, go to
next step.
• If the knob does not pop out when released, stop and immediately call your
service technician or gas supplier.
• If the pilot will not stay lit after several tries, depress and turn the gas
6. The pilot is located on the left side behind the burner (Figure 20).
control knob clockwise
and turn knob counter-clockwise
to “OFF” and wait 30 seconds. Depress
to “SPARK” and ignite the
7. Depress control knob in and turn counter-clockwise
to the
heater again. If your pilot does not relight depress and turn control knob
“SPARK” position (Figure 19) and hold there for a few seconds.
clockwise
supplier.
to “OFF” and call your service technician or gas
Note: If you are running the heater for the first time or after an extended
period of non use it will be necessary to press the control knob all the way
in for 30 seconds to allow air to bleed out of the gas piping.
11. Wait 30 seconds before readjusting the heater when the control knob has
been turned down to a lower setting.
TO TURN OFF GAS TO APPLIANCE
ꢀ. Depress and turn control knob clockwise
position (Figure 19). Close the control access panel.
to the “OFF”
1. Open the control access panel.
Figure 19
The control knob is located on the lower
Figure 20
right hand side of the outer case. It is of a
spherical design and is marked as shown
in Figure 19.
‘OFF’ position
‘SPARK’ position
‘LOW’ position
Figure 20: Pilot assembly. This is located
behind the burner, on the left-hand side of
the appliance.
‘HIGH’ position
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
14
Download from Www.Somanuals.com. All Manuals Search And Download.
ꢀ8.0 TROUBLESHOOTING GUIDE
PROBLEM
CORRECTIVE ACTION
Igniter sparks but pilot does not light
• No gas to Pilot, check the gas line connections.
• Air not fully purged. Purge supply or wait longer.
• Spark grounding to metal work, reset gap correctly.
• Blocked pilot, clean out internally.
Pilot lights but then goes out
• Severe restriction in gas supply: clear obstruction.
• Faulty thermocouple, replace pilot assembly.
• Blocked pilot, clean out.
• Blocked lint gauze, clean.
• Hold control knob in for longer.
• If the pilot will not stay lit there is a problem with dirt, the gas supply, or
the thermocouple needs replacement. Modifications are dangerous and
can have a serious unseen effect on safety. NEVER MODIFY OR BEND THE
THERMOCOUPLE TO MAKE THE PILOT STAY LIT.
• There is a draft (i.e. from window or door, etc.) disturbing the pilot. Remove
draft. u
• The ODS safety system may sense lack of oxygen. Turn off appliance. Call a
qualified service technician. Open windows and doors to provide ventilation to
the area. v
Igniter electrode at pilot does not spark
• HT lead detached,refit.
• Check the spark gap (see Section 16.0).
• Faulty piezo unit, replace.
• Debris shorting out electrode, clean.
• Spark shorting to metalwork under tray, realign HT lead.
The burner stays on for a period of time,
then cuts off
• Loose or faulty thermocouple, rectify.
• Blocked pilot, clean out.
• Dirt or lint in pilot aeration hole or on the lint gauze, clean thoroughly.
• If the pilot will not stay lit there is a problem with dirt, the gas supply, or
the thermocouple needs replacement. Modifications are dangerous and
can have a serious unseen effect on safety. NEVER MODIFY OR BEND THE
THERMOCOUPLE TO MAKE THE PILOT STAY LIT.
Pilot flame shrinks when fire is on high
Fireplace smells when first lit or in use
• Poor gas flow to fire, check pressure with fire on high.
• If pressure is low, remove any restriction in pipe-work or valve.
• Check all pipe-work are adequately sized.
• Check meter pressure is adequate.
• If the pilot will not stay lit there is a problem with dirt, the gas supply, or
the thermocouple needs replacement. Modifications are dangerous and
can have a serious unseen effect on safety. NEVER MODIFY OR BEND THE
THERMOCOUPLE TO MAKE THE PILOT STAY LIT.
• Newness smell from brand new appliance.
• Leakage occurring. Carry out leakage test and rectify any problems.
• Combustible materials used in incorrect positions.
• Unit may require a service to remove dust from catalysts.
u
This appliance is equipped with a oxygen depletion monitoring safety device (ODS). If the appliance shuts down during use for no
apparent reason then several reasons may be suspected. If a door or window has been opened creating a draft, then pilot disturbance could
be the problem and removal of the draft should resolve this.
v
If pilot disturbance is not the cause, then the ODS safety system sensing that there is a lack of oxygen. TURN THE APPLIANCE OFF,
call in your installer to check the appliance and ventilation. DO NOT allow the appliance to be used until the qualified service technician has
determined that the appliance is operating properly and adequate ventilation is being provided.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
ꢀ9.0 REPLACEMENT PARTS - SCANDIUM™
POSITION SPIRIT LEVEL ALONG THIS EDGE TO LEVEL TEMPLATE BEFORE MARKING OUT WALL
Item #
Cat.No.
H6057
H6060
H6061
H6999
H6058
H7012
H6062
H7037
H7002
H7041
H7006
Description
COLOQUE EL NIVEL SOBRE ESTE BORDE PARA NIVELAR LA PLANTILLA ANTES DE MARCAR LA PARED
16”(406mm)
FIXING POINTS
PIERCE TEMPLATE TO MARK HOLE POSITION ON WALL
X
4
PUNTOS DE SUJECION
1
2
Glass door assembly
Catalyst
PERFORE LA PLANTILLA PARA MARCAR LA POSICION DE LOS
4
TALADROS EN LA PARED
12
™
Scandium
WALL MOUNTED VENT FREE FITTING TEMPLATE
PLANTILLA PARA LA INSTALACION DE CHIMENEAS DE PARED SIN SALIDA DE HUMOS
3
Pilot assembly, Natural Gas
Pilot assembly, Propane Gas
Burner Assembly, Natural Gas
Burner Assembly, Propane Gas
Catalyst Gasket
WARNING
CLEARANCES FROM COMBUSTIBLE MATERIALS
The following clearances must be maintained at all times.
IMPORTANT
IMPORTANTE
Failure to do so may result in the risk of
For full information refer to the instruction manual
provided with the heater
a
fire.
THIS APPLIANCE IS TO BE WALL HUNG ONLY.
ESTE APARATO UNICAMENTE DEBE SER COLGADO EN UNA PARED.
NO EMPOTRE NINGUN ELEMENTO DE ESTE APARATO.
ESTA PLANTILLA SIRVE UNICAMENTE PARA MARCAR LOS PUNTOS DE FIJACION.
RETIRE LA PLANTILLA ANTES DE COLOCAR LE APARATO.
.
DO NOT RECESS OR INSET ANY PART OF THE APPLIANCE.
THIS TEMPLATE IS FOR THE MARKING OF FIXING POINTS ONLY.
DO NOT INSTALL THE APPLIANCE WITH THIS TEMPLATE IN PLACE.
Clearance to combustible ceiling
32”measured from top of appliance
glass panel
4
Clearance in
front of
heater 20”
Clearance to
combustible
sidewalls 4”
(both sides)
Note Zero clearance from bottom of heater frame
:
required for hard combustible floors. Minimum 4”
clearance required to rugs or any fabric floor
coverings. REFER TO INSTRUCTION MANUAL
IMPORTANT
:
Fabrics, curtains and drapes are not
permited above the heater at any distance and within
20”of the heater sides. No combustible shelves of any
size are permitted above the heater.
F860041/A
5
ADVERTENCIA
ESPACIO LIBRE HAST MATERIALES COMBUSTIBLES
A
Deben mantenerse en todo momento los siguientes espacios
libres. El no hacerlo puede causar un riesgo de incendio.
Consulte el manual de instrucciones suministrado con este
aparato para obtener información completa.
FIXING POINTS
PUNTOS DE SUJECION
El espacio de 32”hasta un techo
combustible se mide desde el borde
superior del panel de vidrio del aparato
Espacio libre
Espacio hasta
delante del
CONCEALED
GAS INLET
ENTRADA DE
GAS OCULTA
paredeslaterales
calentador 20”
combustibles
4”(ambos lados)
6
Nota: No se requiere espacio libre desde el borde inferior del
marco del calentador en caso de pisos combustibles duros.
Se requiere un espacio mínimo de 4”entre el calentador
cualquier alfombra, moqueta revestimiento de suelo de
tela. CONSULTE EL MANUAL DE INSTRUCCIONES.
y
o
IMPORTANTE: No se permite la colocación de telas, cortinas
similares por encima del calentador cualquier distancia, ni
una distancia de 20”de los laterales del calentador No se
permiten estantes combustibles de cualquier tamaño por
encima del calentador
F860041/A
y
a
a
.
.
DO 005855/0
-
ISSUE
A
7
8
3 Pc. Frame Assembly
Ball Knob
9a
9b
10
Knob Spindle
3
4
Hardware Kit
u
11
12
H6068
H7321
Decorative Glass Facia
Fitting Template
10
uHardware kits consists of the following:
6 ea. No.8 x 5/16 Screw Pozi Pan Head
6 ea. M6 x 12 Screw Pozi Pan Head BZP
6 ea. M4 x 12 Screw Pozi Pan Head Black
1 ea. Rubber Grommet
4 ea. Wall Plug
4 ea. Wall Fixing Screws
2 ea. Ceramic bracket
7
2
2 ea. Clevis Pin
8
1
11
9b
5
6
9a
See ordering instructions on Page 20
16
Download from Www.Somanuals.com. All Manuals Search And Download.
30.0 POSITIONING OF FIELD REMOVABLE PARTS
WARNING
Failure to position the parts in
accordance with these diagrams
orfailuretouseonlypartsspecifi-
cally approved with this heater
may result in property damage
or personal injury.
Glass Door Removal: Remove
the four (4) screws indicated,
then lift door off.
Visual check for cor-
rect pilot flame.
4 off burner
installation
positions
Figure 22
Figure 21
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
17
Download from Www.Somanuals.com. All Manuals Search And Download.
31.0 SPECIFICATIONS
Product Reference Information
Cat. No.
H6065
Model
Ship. Wt. Ship. Volume
Scandium-NG
Scandium-LP
80.7 lb.
80.7 lb.
1ꢀ.9 cu. ft.
1ꢀ.9 cu. ft.
H6071
41-1/2”
27-11/16”
20-13/16”
18-5/8”
10-1/4”
Side View
Front View
Bottom View
7-1/8”
5-9/16”
16”
30-1/16”
Back View
18
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
19
Download from Www.Somanuals.com. All Manuals Search And Download.
3ꢀ.0 PRODUCT REFERENCE INFORMATION
WARRANTY
Normally, all parts should be ordered through your Lennox distributor or
dealer. Parts will be shipped at prevailing prices at time of order.
Your gas appliance is covered by a limited warranty. Please read the
warranty to be familiar with its coverage.
When ordering repair parts, always give the following information:
Retain this manual. File it with your other documents for future refer-
ence.
1. The model number of the appliance.
ꢀ. The serial number of the appliance.
3. The part number.
PRODUCT REFERENCE INFORMATION
4. The description of the part.
5. The quantity required.
Werecommendthatyourecordthefollowingimportantinformationabout
your appliance. Please contact your Lennox Hearth Products dealer for
anyquestionsorconcerns. ForthenumberofyournearestLennoxHearth
Products dealer, please call 1-800-9-LENNOX.
6. The installation date of the appliance.
If you encounter any problems or have any questions concerning the
installation or application of this system, please contact your dealer.
REPLACEMENT PARTS
LENNOX HEARTH PRODUCTS
1110 West Taft Avenue
Orange, CA 9ꢀ865
See Page 15 for a complete replacement parts list. Use only parts sup-
plied from the manufacturer.
Your Appliance's Model Number _______________________________________
Your Fireplace’s Serial Number ________________________________________
The Date On Which Your Fireplace Was Installed___________________________
The Type of Gas Your Fireplace Uses ____________________________________
Your Dealer's Name _________________________________________________
Fuel Type c Natural Gas c Propane Gas
Lennox Hearth Products reserves the right to make changes at any time, without notice, in
design, materials, specifications, prices and also to discontinue colors, styles and products.
Consult your local distributor for fireplace code information.
Printed in U.S.A. © ꢀ007 Lennox Hearth Products
1110 West Taft Avenue • Orange, CA 9ꢀ865
P/N 850,055M REV. E, 11/2008
ꢀ0
Download from Www.Somanuals.com. All Manuals Search And Download.
|