MUser Guide
Part Number 900-588
Revision B March 2013
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
Micro125 User Guide
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Micro125 User Guide
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Micro125 User Guide
5
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Using This Guide
Purpose and Audience
This guide covers the DeviceLinx Micro125 embedded device server. It provides the
information needed to configure, use, and update the Micro125 firmware and is intended for
OEMs and system integrators who are embedding Micro125 in their end product designs.
Chapter Summary
The remaining chapters in this guide include:
Chapter
Description
Describes the main features of the Micro125 and the protocols it
supports.
Provides information for physically connecting your unit.
Provides information for getting your unit up and running, using
DeviceInstaller to assign an IP address.
Details using the Web-Manager to set parameters such as port
and server properties.
Provides instructions for accessing Setup Mode (command line
interface) using a Telnet connection through the network or a
terminal or terminal emulation program through the serial port.
Details the network (server) settings
Details the serial port settings.
Details expert, and security settings and explains how to reset
the unit to factory default values.
Provides instructions for obtaining the latest firmware and
updating the Micro125.
Provides instructions for accessing and using the command line
interface for monitoring the network and diagnosing problems.
Describes common problems and error messages and how to
contact Lantronix Technical Support.
Provides instructions for converting binary numbers to
hexadecimals.
Micro125 User Guide
7
Download from Www.Somanuals.com. All Manuals Search And Download.
1: Using This Guide
Additional Documentation
documentation and the following additional documentation.
Document
Description
Micro125 Integration Guide
Provides information about the Micro125 hardware, testing
the Micro125 using the evaluation board, and integrating the
Micro125 into your product.
Com Port Redirector User Guide
DeviceInstaller Online Help
Provides information on using the Windows-based utility to
create a virtual com port.
Provides information on using DeviceInstaller to configure IP
addresses and locate Lantronix devices on the network.
Micro125 User Guide
8
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Introduction
This chapter summarizes the Micro125 device server’s features and the basic information
needed to get started.
Capabilities
The Micro125 device server has the following capabilities:
Connects devices through a TCP data channel or through a Telnet connection to
computers or to another device server. The Micro125 also supports UDP datagrams.
Contains a web [HTTP] server allowing presentation of custom content and easy
configuration through a browser.
Applications
The Micro125 device server connects serial devices such as those listed below to Ethernet
networks using the IP protocol family.
ATM machines
CNC controllers
Data collection devices
Environmental sensors
Universal Power Supply (UPS) management units
Telecommunications equipment
Data display devices
Security alarms and access control devices
Handheld instruments
Modems
Time/attendance clocks and terminals
Micro125 User Guide
9
Download from Www.Somanuals.com. All Manuals Search And Download.
2: Introduction
Protocol Support
The Micro125 device server uses the Internet Protocol (IP) for network communications. It
uses the Transmission Control Protocol (TCP) to assure that no data is lost or duplicated,
and that everything sent to the connection arrives correctly at the target.
Supported protocols include:
ARP, UDP, TCP, ICMP, Telnet, TFTP, AutoIP, DHCP, HTTP, and SNMP for network
communications and management.
TCP, UDP, and Telnet for connections to the serial port.
TFTP for firmware and web page updates.
IP for addressing, routing, and data block handling over the network.
User Datagram Protocol (UDP) for typical datagram applications in which devices interact
with other devices without maintaining a point-to-point connection.
Configuration Methods
For the unit to operate correctly on a network, it must have a unique IP address on the
network. There are three basic methods for logging into the device server to assign an IP
address and configure the unit:
DeviceInstaller: Assign an IP address and view the current Micro125 configuration using a
Web-Manager: Through a web interface, configure the Micro125 and its settings using the
Serial & Telnet Ports: There are two approaches to accessing Serial Mode. Make a Telnet
connection to the network port (9999) or connect a terminal (or a PC running a terminal
emulation program) to the unit’s serial port. (See Configuration via Telnet or Serial Port
Addresses and Port Numbers
Hardware Address
The hardware address is also referred to as the Ethernet address or the MAC address. The
first three bytes of the Ethernet address are fixed and read 00-20-4A, identifying the unit as a
Lantronix product. The fourth, fifth, and sixth bytes are unique numbers assigned to each
unit.
Example: 00-20-4A-14-01-18
Note: Make note of the MAC address. It is needed to locate the Micro125 using
DeviceInstaller.
Micro125 User Guide
10
Download from Www.Somanuals.com. All Manuals Search And Download.
2: Introduction
IP Address
Every device connected to an IP network must have a unique IP address. This address is
used to reference the specific unit. The Micro125 is automatically assigned an IP address on
DHCP-enabled networks, as it is DHCP-enabled by default.
Port Numbers
Every TCP connection and every UDP datagram is defined by a destination IP address and a
port number. For example, a Telnet application commonly uses port number 23. A port
number is similar to an extension on a phone system.
The unit's serial channel (port) can be associated with a specific TCP/UDP port number. Port
number 9999 is reserved for access to the unit's Setup (configuration) Mode window. Ports 0-
1024 are reserved as well. For more information on reserved port numbers, see Table 8-5.
Micro125 User Guide
11
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Getting Started
This chapter covers the steps required to get an embedded device physically connected.
Physically Connecting the Unit
The following diagram shows a properly installed Micro125. Other devices connect in a
similar manner.
Figure 3-1. Evaluation Board Connected to Serial Device and Network
10/100 Ethernet
+5
RS232
1. Connect a computer or serial device to your unit.
2. Connect an Ethernet cable to the RJ-45 Ethernet port.
3. Supply power to your unit using the power supply that was included in the packaging.
Note: The required input voltage for the Micro125 is 5VDC (+/-5% at ~200 mA). Other
devices may require a different voltage.
4. Supply power to the serial device.
Required Information
Hardware Address
You need to know the unit’s hardware address (also known as the MAC address), which is on
the product label. It is in the format: 00-20-4a-XX-XX-XX, where the XXs are unique numbers
assigned to the product.
Hardware Address: 00-20-4a-_____-_____-_____
Micro125 User Guide
12
Download from Www.Somanuals.com. All Manuals Search And Download.
3: Getting Started
IP Address
Your device server must have a unique IP address on your network. The systems
administrator generally provides the IP address and corresponding subnet mask and
gateway. The IP address must be within a valid range, unique to your network, and in the
same subnet as your PC.
IP Address:
Subnet Mask: _______ _______ _______ _______
Gateway: _______ _______ _______ _______
_______ _______ _______ _______
You have several options for assigning an IP address to your unit. We recommend that you
manually assign the IP address over the network using DeviceInstaller software, which is
Micro125 User Guide
13
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Using DeviceInstaller
This chapter covers the steps for getting the Micro125 device server online and viewing its
current configuration.
Note: DeviceInstaller is a free utility program provided by Lantronix that
discovers, configures, upgrades, and manages Lantronix Device Servers. It
can be downloaded from the Lantronix website at
For instructions on using DeviceInstaller to configure the IP address and
related settings or for more advanced features, see the DeviceInstaller
Installing DeviceInstaller
To install DeviceInstaller:
2. Run the executable to start the installation process.
3. Respond to the installation wizard prompts. (If prompted to select an installation type,
select Typical).
Assigning an IP Address
The unit’s IP address must be configured before it can work correctly on a network. You have
several options for assigning an IP to your unit. We recommend that you manually assign the
IP address over the network using DeviceInstaller.
Note: To use a serial connection instead of an Ethernet connection to configure the device,
The unit’s IP address is normally set to 0.0.0.0 at the factory. The hardware address is on the
product label. The unit is DHCP enabled as the default.
To assign an IP address manually:
1. Click StartAll Programs LantronixDeviceInstaller 4.3DeviceInstaller. If your
PC has more than one network adapter, a message displays. Select an adapter and click
OK.
Note: If the unit already has an IP address (e.g., DHCP has assigned an IP address), click
the Search icon and select the unit from the list of Lantronix device servers on the local
network.
2. Click the Assign IP icon
.
3. If prompted, enter the hardware address (on the product label) and click Next.
Micro125 User Guide
14
Download from Www.Somanuals.com. All Manuals Search And Download.
4: Using DeviceInstaller
4. Select Assign a specific IP address and click Next.
5. Enter the IP address. The Subnet mask displays automatically based on the IP address;
if desired, you may change it. On a local network, you can leave the Default gateway
blank (all zeros). Click Next.
6. Click the Assign button and wait several seconds until a confirmation message displays.
Click Finish.
7. Select the device from the main window list and select Ping from the Tools menu. The
Ping Device dialog box shows the IP address of the selected unit.
8. From the Tools menu, click the Ping button. The results display in the Status window.
Click the Clear Status button to clear the window so you can ping the device again.
Note: If you do not receive “Reply” messages, make sure the unit is properly attached to the
network and that the IP address assigned is valid for the particular network segment you are
working with. If you are not sure, check with your systems administrator.
9. Click the Close button to close the dialog box and return to the main window.
Accessing the Micro125 Using DeviceInstaller
1. Click StartPrograms LantronixDeviceInstallerDeviceInstaller.
2. Click the Micro folder. The list of available Lantronix Micro-type devices displays.
3. Expand the list of Micro125 devices by clicking the + symbol next to the Micro125 icon.
Select the Micro125 unit by clicking on its IP address to view its configuration.
Viewing the Current Configuration
DeviceInstaller provides a view of the unit's configuration.
To view the unit's current settings:
1. Follow the instructions above to locate the Micro125.
2. In the right pane, click the Device Details tab. The current Micro125 configuration
displays:
Device Details
Settings
Description
Name
Configurable field. A name that identifies the Micro125.
Double-click the field, type in the value, and press Enter to complete. This
name is not visible on other PCs or laptops using DeviceInstaller.
DHCP Device Name
Non-configurable field. Displays the name associated with Micro125’s
current IP address, if the IP address was obtained dynamically.
To change the DHCP device name, see sections, Configuration Using
Group
Configurable field. A group name to categorize the Micro125.
Double-click the field, type in the value, and press Enter to complete. This
group name is not visible on other PCs or laptops using DeviceInstaller.
Micro125 User Guide
15
Download from Www.Somanuals.com. All Manuals Search And Download.
4: Using DeviceInstaller
Device Details
Settings
Description
Comments
Configurable field. Information about the Micro125.
Double-click the field, type in the value, and press Enter to complete. This
description or comment is not visible on other PCs or laptops using
DeviceInstaller.
Device Family
Non-configurable field. Displays the Micro125’s device family as Micro125.
Non-configurable field. Displays the device type as Micro125.
Type
ID
Non-configurable field. Displays the Micro125’s ID embedded within the
box.
Hardware Address
Firmware Version
Non-configurable field. Displays the Micro125’s hardware (or MAC)
address.
Non-configurable field. Displays the firmware currently installed on the
Micro.
Extended Firmware
Version
Non-configurable field. Displays the full version nomenclature of the
firmware.
Online Status
Non-configurable field. Displays the Micro125’s status as online, offline,
unreachable (the Micro125 is on a different subnet), or busy (the Micro125
is currently performing a task).
IP Address
Non-configurable field. Displays the Micro125’s current IP address. To
change the IP address, click Assign IP on the DeviceInstaller menu bar.
Displays “Dynamically” if the device automatically received an IP address
(e.g., from DHCP). Displays “Statically” if the IP address was configured
manually. If the IP address was assigned dynamically, the following fields
appear:
IP Address was
Obtained
Obtain via DHCP with value of True or False.
Obtain via BOOTP with value of True or False.
Obtain via RARP with value of True or False
Obtain via Auto IP with value of True or False
Subnet Mask
Gateway
Non-configurable field. Displays the Micro125’s current subnet mask.
Non-configurable field. Displays the Micro125’s current gateway.
Non-configurable field. Displays the number of COB partitions supported.
Number of COB
partitions supported
Number of Serial
Ports
Non-configurable field. Displays the number of ports on the Micro125.
TCP Keepalive
Non-configurable field. Displays 1-65s, the Micro125’s TCP keepalive
value. The default setting is 45.
Telnet Supported
Non-configurable field. Indicates whether Telnet is enabled on this
Micro125.
Telnet Port
Web Port
Non-configurable field. Displays the Micro125’s port for Telnet sessions.
Non-configurable field. Displays the Micro125’s port for Web-Manager
configuration.
Maximum Baud Rate
Supported
Non-configurable field. Displays the Micro125’s maximum baud rate.
Note: the Micro125 may not currently be running at this rate.
Micro125 User Guide
16
Download from Www.Somanuals.com. All Manuals Search And Download.
4: Using DeviceInstaller
Device Details
Settings
Description
Firmware
Upgradeable
Non-configurable field. Displays True, indicating the Micro125’s firmware is
upgradeable as newer versions become available.
Supports
Configurable Pins
Non-configurable field. Displays False, indicating configurable pins are not
available on the Micro125.
Supports Email
Triggers
Non-configurable field. Displays False, indicating email triggers are not
available on the Micro125.
Supports AES Data
Stream
Non-configurable field. Displays True if the Micro125 unit supports AES
encryption.
Supports 485
Non-configurable field. Displays True, indicating the Micro125 supports the
RS-485 protocol.
Supports 921K Baud
Rate
Non-configurable field. Displays False. Micro125 does not support baud
rates up to 921 Kbps.
Supports HTTP
Server
Non-configurable field. Displays True.
Non-configurable field. Displays True.
Non-configurable field. Displays True.
Supports HTTP
Setup
Supports 230K Baud
Rate
Supports GPIO
Non-configurable field. Displays False, indicating the Micro125 does not
support communication via General Purpose Input Output (GPIO).
Micro125 User Guide
17
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Configuration Using Web Manager
You must configure the unit so that it can communicate on a network with your serial device.
For example, you must set the way the unit will respond to serial and network traffic, how it
will handle serial packets, and when to start or close a connection.
The unit’s configuration is stored in nonvolatile memory and is retained without power. You
can change the configuration at any time. The unit performs a reset after you change and
store the configuration.
In this chapter, we describe how to configure the Micro125 using Web-Manager, Lantronix’s
browser-based configuration tool. (For information on using Setup Mode, our command line
Note: The examples in this section show a typical device. Your device may have different
configuration options.
Accessing Web-Manager Using DeviceInstaller
1. Run DeviceInstaller and search for the list of available Lantronix device servers.
2. Click on the Micro folder. The list of available Micro type devices displays.
3. Expand the list of Micro125 devices by clicking the + symbol next to the Micro125 icon.
4. Select the Micro125 unit by clicking its hardware address.
5. In the right pane, click the Web Configuration tab.
6. To view the Micro125’s Web-Manager in the current DeviceInstaller window, click the Go
button. To open the Web-Manager in a web browser, click the External Browser button.
Note: Alternatively, to open Web-Manager, open your web browser and enter the IP address
of the Micro125.
A dialog box appears to prompt for a User name and Password.
Micro125 User Guide
18
Download from Www.Somanuals.com. All Manuals Search And Download.
5: Configuration Using Web Manager
Figure 5-1. Web-Manager Login Window
7. Perform one of the following:
.
.
If no Telnet/Web Manager password has been defined (default), leave both fields
blank and click OK.
If a Telnet/Web Manager password has been defined, leave the username blank,
type in the password, and then click OK.
The Web-Manager displays.
Figure 5-2. Lantronix Web-Manager
The main menu is in the left pane of the Web-Manager window.
Micro125 User Guide
19
Download from Www.Somanuals.com. All Manuals Search And Download.
5: Configuration Using Web Manager
Network Configuration
The unit’s network values display when you select Network from the main menu. The
following sections describe the configurable parameters on the Network Settings page.
Figure 5-3. Network Settings
Network Mode
1. Click Network from the main menu.
2. Select Wired Only. It is the only choice for Network Mode as it enables the Ethernet
network connectivity.
Automatic IP Address Configuration
An IP address can be assigned automatically. You then enter related network settings.
To assign an IP address automatically:
1. On the main menu, click Network.
2. Select Obtain IP address automatically.
Micro125 User Guide
20
Download from Www.Somanuals.com. All Manuals Search And Download.
5: Configuration Using Web Manager
3. Enter the following (as necessary):
Dynamic IP Setting Description
BOOTP
DHCP
Select Enable to permit the Bootstrap Protocol (BOOTP). server to assign
the IP address from a pool of addresses automatically. Enable is the
default.
Select Enable to permit the Dynamic Host Configuration Protocol (DHCP) to
assign a leased IP address to the Micro125 unit automatically. Enable is the
default.
AutoIP
Select Enable to permit the Micro125 to generate an IP in the 169.254.x.x
address range with a Class B subnet. Enable is the default.
DHCP Host Name
Enter the desired host name for the Micro125.
Note: Disabling BOOTP, DHCP, and AutoIP (all three checkboxes) is not advised as the only
available IP assignment method will then be ARP or serial port.
4. When you are finished, click the OK button.
5. On the main menu, click Apply Settings.
Static IP Address Configuration
You manually assign an IP address to the unit and enter related network settings.
To assign an IP address manually:
1. On the main menu, click Network.
2. Select Use the following IP configuration.
3. Enter the following (as necessary):
Static IP Settings
IP Address
Description
If DHCP is not used to assign IP addresses, enter it manually in decimal-
dot notation. The IP address must be set to a unique value in the network.
Subnet Mask
A subnet mask defines the number of bits taken from the IP address that
are assigned for the host part.
Default Gateway
The gateway address, or router, allows communication to other LAN
segments. The gateway address should be the IP address of the router
connected to the same LAN segment as the unit. The gateway address
must be within the local network.
DNS Server
The DNS server allows the name of a remote machine to be resolved
automatically. Enter the IP address of the DNS server. If the device is
DHCP enabled, the DHCP server provides the DNS server IP address,
which will override this configured value.
Note: This setting is applicable only in Manual Connection mode.
4. When you are finished, click the OK button.
5. On the main menu, click Apply Settings.
Micro125 User Guide
21
Download from Www.Somanuals.com. All Manuals Search And Download.
5: Configuration Using Web Manager
Ethernet Configuration
You must specify the speed and direction of data transmission.
To specify how data will be transmitted:
1. On the main menu, click Network.
2. Enter the following (as necessary):
Ethernet Settings
Auto Negotiate
Description
With this option, the Ethernet port auto-negotiates the speed and duplex
with the hardware endpoint to which it is connected. This is the default.
If this option is not selected, the complete the fields that become
available:
Speed: The speed of data transmission. The default is 100
Mbps.
Duplex: The direction of data transmission. The default is Full.
3. When you are finished, click the OK button.
4. On the main menu, click Apply Settings.
Micro125 User Guide
22
Download from Www.Somanuals.com. All Manuals Search And Download.
5: Configuration Using Web Manager
Server Configuration
The unit’s server values display when you select Server from the main menu. The following
sections describe the configurable parameters on the Server Settings page.
Figure 5-4. Server Settings
To configure the Micro125’s device server settings:
1. On the main menu, click Server.
2. Configure or modify the following fields:
Server Configuration
Server Configuration
Settings
Description
Enhanced Password
Select whether to enable enhanced password:
Enable: selecting this option enables advanced password
creation, allowing you to create passwords up to 16 bytes in length.
Disable: selecting this option disables advanced password
creation, allowing you to create basic passwords up to 4 bytes in
length.
Telnet/Web Manager
Password
Enter the password required for Telnet configuration and Web
Manager access.
Retype Password
Re-enter the password required for Telnet configuration and Web
Manager access.
Micro125 User Guide
23
Download from Www.Somanuals.com. All Manuals Search And Download.
5: Configuration Using Web Manager
Advanced
Advanced Settings
Description
ARP Cache Timeout
(secs)
When the unit communicates with another device on the network, it
adds an entry into its ARP table. ARP Cache timeout defines the
number of seconds (1-600) before it refreshes this table.
TCP Keepalive (secs)
Monitor Mode @ Bootup
HTTP Server Port
TCP Keepalive time defines how many seconds the unit waits during
an inactive connection before checking its status. If the unit does not
receive a response, it drops that connection. Enter a value between
0 and 60 seconds. 0 disables keepalive. The default setting is 45.
Select Disable to disable entry into the monitor mode using the 'yyy'
or 'xx1' key sequence at startup. This field prevents the unit from
entering monitor mode by interpreting the stream of characters that
are received during the device server's initialization at startup.
This option allows the configuration of the web server port number.
The valid range is 1-65535. The default port is 80.
Config Server Port
MTU Size
Not applicable for this product.
The Maximum Transmission Unit (MTU) is the largest physical
packet size a network can transmit for TCP and UDP. Enter between
512 and 1400 bytes. The default is 1400 bytes.
TCP Re-transmission
timeout (ms)
The desired TCP re-transmission timeout value. If the ACK is not
received for a packet sent from the Micro125 device, then the unit
will retransmit the data. The valid range is 500-4000 msec.
3. When you are finished, click the OK button.
4. On the main menu, click Apply Settings.
Host List Configuration
The Micro125 scrolls through the host list until it connects to a device listed in the host list
table. After a successful connection, the unit stops trying to connect to any others. If this
connection fails, the unit continues to scroll through the table until the next successful
connection.
The host list supports a minimum of 1 and a maximum of 12 entries. Each entry contains an
IP address and a port number.
Note: The host list is disabled for Manual and Modem Mode. The unit does not accept a data
connection from a remote device when the hostlist option is enabled.
To configure the Micro125’s host list:
1. On the main menu, click Hostlist.
Micro125 User Guide
24
Download from Www.Somanuals.com. All Manuals Search And Download.
5: Configuration Using Web Manager
Figure 5-5. Hostlist Settings
2. Enter or modify the following fields:
Retry Settings
Retry Settings
Description
Retry Counter
Enter the value for the number of times the Micro125 should attempt to
retry connecting to the host list.
Retry Timeout
Enter the duration (in milliseconds) the Micro125 should abandon
attempting a connection to the host list.
Host Information
Host Information
Settings
Description
Host Address
Port
Enter or modify the host’s IP address.
Enter the target port number.
3. When you are finished, click the OK button.
4. On the main menu, click Apply Settings.
Channel 1 and Channel 2 Configuration
The Channel 1 and Channel 2 configuration defines how the serial port responds to network
and serial communication.
Micro125 User Guide
25
Download from Www.Somanuals.com. All Manuals Search And Download.
5: Configuration Using Web Manager
Serial Settings
To configure the channel’s serial settings:
1. On the main menu, click Serial Settings (under Channel 1 or Channel 2) to display the
Serial Settings window.
Figure 5-6. Channel Serial Settings
2. In the available fields, enter the following information:
Channel 1 or Channel 2
Channel Setting
Description
Disable Serial Port
Available on Channel 1 settings only. When selected, disables
communication through the serial port.
Note: Using a telnet session (see Baudrate) you may enter a
baud rate of 00 in channel settings to disable the serial port.
Port Settings
Port Settings
Protocol
Description
From the drop-down menu, select the protocol type for the
selected channel.
Micro125 User Guide
26
Download from Www.Somanuals.com. All Manuals Search And Download.
5: Configuration Using Web Manager
Port Settings
Flow Control
Description
Flow control manages data flow between devices in a network to
ensure it is processed efficiently. Too much data arriving before a
device is prepared to manage it causes lost or retransmitted data.
None is the default.
Baud Rate
Data Bits
The unit and attached serial device, such as a modem, must agree
on a speed or baud rate to use for the serial connection. Valid
baud rates are 300, 600, 1200, 2400, 4800, 9600 (default), 19200,
38400, 57600, 115200 or 230400.
Indicates the number of bits in a transmitted data package. The
default is 8.
Parity
Checks for the parity bit. The default is None.
Stop Bits
The stop bit follows the data & parity bits in serial communication.
It indicates the end of transmission. The default is 1.
Pack Control
Pack Control Settings
Description
Enable Packing
Select to enable packing on the Micro125.
Two firmware-selectable packing algorithms define how and when
packets are sent to the network.
The standard algorithm is optimized for applications in which the
unit is used in a local environment, allowing for very small delays
for single characters, while keeping the packet count low.
The alternate packing algorithm minimizes the packet count on the
network and is especially useful in applications in a routed Wide
Area Network (WAN). Adjusting parameters in this mode can
economiz the network data stream.
Disabled by default.
Idle Gap Time
Select the maximum time for inactivity. The default time is
12 milliseconds.
Match 2 Byte Sequence
Use to indicate the end of a series of data to be sent as one group.
The sequence must occur sequentially to indicate end of the data
collection to the Micro125. The default is No.
Match Bytes
Use to indicate the end of a series of data to be sent as one group.
Set this value to 00 if specific functions are not needed.
Send Frame Immediate
After the detection of the byte sequence, indicates whether to send
the data frame or the entire buffer. Select Yes to send only the
data frame. The default setting is No.
Send Trailing Bytes
Select the number of bytes to send after the end-of-sequence
characters. The default is None.
Micro125 User Guide
27
Download from Www.Somanuals.com. All Manuals Search And Download.
5: Configuration Using Web Manager
Flush Input Buffer (Serial to Network)
Flush Input Buffer Settings
With Active Connect
Description
Select Yes to clear the input buffer with a connection that is
initiated from the device to the network. The default is No.
With Passive Connect
At Time of Disconnect
Select Yes to clear the input buffer with a connection initiated from
the network to the device. The default is No.
Select Yes to clear the input buffer when the network connection
to or from the device is disconnected. The default is No.
Flush Output Buffer (Network to Serial)
Flush Output Buffer
Settings
Description
With Active Connect
With Passive Connect
At Time of Disconnect
Select Yes to clear the output buffer with a connection that is
initiated from the device to the network. The default is No.
Select Yes to clear the output buffer with a connection initiated
from the network to the device. The default is No.
Select Yes to clear the output buffer when the network connection
to or from the device is disconnected. The default is No.
3. When you are finished, click the OK button.
4. On the main menu, click Apply Settings.
Micro125 User Guide
28
Download from Www.Somanuals.com. All Manuals Search And Download.
5: Configuration Using Web Manager
Connection Settings - TCP
To configure a channel’s TCP settings:
1. On the main menu, click Connection. The Connection Settings window for the channel
displays.
Figure 5-7. TCP Connection Settings
Micro125 User Guide
29
Download from Www.Somanuals.com. All Manuals Search And Download.
5: Configuration Using Web Manager
2. In the available fields, enter or modify the following information:
Connect Protocol
Connect Protocol Setting
Protocol
Description
From the drop-down menu, select TCP.
Connect Mode: Passive Connection
Passive Connection Mode
Settings
Description
Accept Incoming
Select Yes to accept incoming connections. The default is Yes.
Password Required
Determines whether a password is required for an incoming
passive connection. This field is not available when a password is
set for Telnet mode.
Password
If Password Required was set to Yes, enter the password for
passive connections.
Connect Mode: Active Connection
Active Connection Mode
Settings
Description
Active Connect
Select None to disable Active Connect. Otherwise, indicate the
connection type from the drop-down list:
With Any Character: Attempts to connect when any
character is received from the serial port.
With Active Mdm Ctrl In: Accepts external connection
requests only when the Modem Control In input is
asserted.
With Start Character: Attempts to connect when it
receives a specific start character from the serial port. The
default start character is carriage return.
Manual Connection: Attempts to connect when directed
by a command string received from the serial port.
Auto Start: Automatically connects to the remote IP
address and port after booting up.
Start Character
If Active Connect is set to With Start Character, enter the start
character in this field.
Modem Mode
Indicates the on-screen response type when in Modem Mode (if
Modem Mode is enabled).
Show IP Address After Ring
Indicates whether to display the remote IP address upon
connection. The default setting is Yes.
Micro125 User Guide
30
Download from Www.Somanuals.com. All Manuals Search And Download.
5: Configuration Using Web Manager
Endpoint Configuration
Endpoint Configuration
Settings
Description
Local Port
Enter the local port number.
Auto increment for active
connect
Select to auto-increment the local port number for new outgoing
connections. The range of auto-incremented port numbers is
50,000 to 59,999 and loops back to the beginning when the
maximum range is reached.
Remote Port
Remote Host
Enter the remote port number.
Enter the IP address of the remote device.
Common Options
Common Option Settings
Telnet Com Port Cntrl
Description
This field is available for configuration only when Active Connect
is set to None. Select Enable to permit Telnet communication to
the unit. The Telnet Com Port Cntrl feature is used in
conjunction with the Com Port Redirector (CPR) utility. (See the
CPR Online Help for details.)
Terminal Name
This field is available for configuration only when Telnet Mode is
set to Enable.
Use the terminal name for the Telnet terminal type. Enter only
one name. When this option is enabled, the unit also reacts to the
end of record (EOR) and binary options, which can be used for
applications such as terminal emulation to IBM hosts.
Connect Response
Use Hostlist
A single character is transmitted to the serial port when there is a
change in connection state. Default setting is None.
If this option is set to True, the device server scrolls through the
host list until it connects to a device listed in the host list table.
Once it connects, the unit stops trying to connect to any others. If
this connection fails, the unit continues to scroll through the table
until it connects to another IP in the host list.
The host list is disabled for Manual Mode and for Modem Mode.
The unit will not accept a data connection from a remote device
when the host list option is enabled.
LED
Select Blink for the status LEDs to blink upon connection or
None for no LED output.
Disconnect Mode
Disconnect Mode Settings
On Mdm_Ctrl_In Drop
Description
Set to Yes for the network connection to or from the serial port to
disconnect (drop) when Modem Control In transitions from an
asserted state to not asserted state. The default setting is No.
Hard Disconnect
When set to Yes, the TCP connection closes even if the remote
site does not acknowledge the disconnect request.
Micro125 User Guide
31
Download from Www.Somanuals.com. All Manuals Search And Download.
5: Configuration Using Web Manager
Disconnect Mode Settings
Check EOT (Ctrl-D)
Description
Select Yes to drop the connection when Ctrl-D or Hex 04 is
detected. Both Telnet Com Port Cntrl and Check EOT
(Ctrl+ D) must be enabled for Disconnect with EOT to function
properly. Ctrl+D is only detected going from the serial port to the
network. The default setting is No.
Use this parameter to set an inactivity timeout. The unit drops the
TCP connection to port 10001/10002* if there is no activity on the
serial line before the set time expires. Enter time in the format
mm:ss, where m is the number of minutes and s is the number of
seconds. To disable the inactivity timeout, enter 00:00.
Inactivity Timeout
Note*: The default port number for Port 1 is 10001 and 10002 for
Port 2. However, port numbers may be set to a different value.
3. When you are finished, click the OK button.
4. On the main menu, click Apply Settings.
Connection Settings - UDP
To configure a channel’s UDP settings:
1. On the main menu, click Connection. The Connection Settings window for the selected
channel displays.
2. In the available fields, enter or modify the following information:
Figure 5-8. UDP Connection Settings
Micro125 User Guide
32
Download from Www.Somanuals.com. All Manuals Search And Download.
5: Configuration Using Web Manager
Connect Protocol
Connection Protocol
Protocol
Description
Select UDP from the drop-down menu.
Datagram Mode
Datagram Mode
Settings
Description
Datagram Type
Configures the remote IP or network broadcast address and the
remote port. Enter 01 for directed or broadcast UDP. The default
setting is 00.
Accept Incoming
Select Yes to accept incoming UDP datagrams.
Endpoint Configuration
Endpoint Configuration Description
Settings
Local Port
Enter the local port number.
Remote Port
Remote Host
Use Broadcast
Enter the port number of the remote device.
Enter the IP address of the remote device.
Select to broadcast the UDP datagram. The default is not to
broadcast.
Note: Datagrams are sent as subnet-directed broadcasts.
Device Address Table
The table is enabled when Datagram Type is set to FD. Enter values
between 1 and 255 to identify units on the local network of device
servers.
Note: Lantronix Tech Support supports Datagram type 01. Datagram
Type FD is for OEM use.
3. When you are finished, click the OK button.
4. On the main menu, click Apply Settings.
Apply Settings
1. To save and apply the configuration changes to the device server, click the Apply
Settings button.
Note: Clicking OK on each page does not change the configuration on the device.
Clicking the OK button tells the MatchPort what changes to use; the Apply Settings
makes the changes permanent and reboots the Micro125.
Micro125 User Guide
33
Download from Www.Somanuals.com. All Manuals Search And Download.
5: Configuration Using Web Manager
Figure 5-9. Applying Settings
Apply Defaults
1. Click the Apply Factory Defaults button to set the device server back to the default
2. Click Yes to set factory settings, or click No to cancel.
Figure 5-10. Applying Default Settings
Micro125 User Guide
34
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Configuration via Telnet or Serial Port
(Setup Mode)
You must configure the unit so that it can communicate on a network with your serial device.
As an alternative to using a web browser, as described in the previous chapter, you can use
the following procedures remotely or locally:
Use a Telnet connection to configure the unit over the network.
Use a terminal or terminal emulation program to access the serial port locally.
The series of prompts at which you enter configuration settings is called Setup Mode.
Note: Detailed information about other setup methods is available from your Lantronix Sales
Associate.
The unit’s configuration is stored in nonvolatile memory and is retained without power. You
can change the configuration at any time. The unit performs a reset after the configuration
has been changed and stored.
This chapter tells you how to access Setup Mode and the general procedure for using it. To
Note: The menus in the configuration chapters show a typical device. Your device may have
different configuration options.
Accessing Setup Mode
Telnet Connection
To configure the unit over the network, establish a Telnet connection to port 9999.
Note: You can also use DeviceInstaller to access Telnet. Select the device from the main
window list, and click the Telnet Configuration tab. Skip steps 1 and 2.
Micro125 User Guide
35
Download from Www.Somanuals.com. All Manuals Search And Download.
6: Configuration via Telnet or Serial Port (Setup Mode)
To establish a Telnet connection:
1. From the Windows Start menu, click Run and type the following command, where x.x.x.x
is the IP address, and 9999 is the unit’s fixed network configuration port number:
Windows: telnet x.x.x.x 9999
UNIX: telnet x.x.x.x:9999
2. Click OK. The following information displays.
Figure 6-1. MAC Address
MAC address 00204AAE0412
Software version V6.8.0.4 (121207) M125
AES library version 1.8.2.1
Press Enter for Setup Mode
3. To enter Setup Mode, press Enter within 5 seconds. The configuration settings display,
followed by the Change Setup menu.
Figure 6-2. Setup Menu Options
Change Setup:
0 Server
1 Channel 1
2 Channel 2
5 Expert
6 Security
7 Defaults
8 Exit without save
9 Save and exit
Your choice?
4. Select an option on the menu by entering the number of the option in the Your choice ?
field and pressing Enter.
5. To enter a value for a parameter, type the value and press Enter, or to confirm a current
value, just press Enter.
6. When you are finished, save the new configuration (option 9). The unit reboots.
Serial Port Connection
To configure the unit through a serial connection:
1. Connect a console terminal or PC running a terminal emulation program to your unit's
serial port.
2. Set the terminal emulator serial port settings to 9600 baud, 8 bits, no parity, 1 stop bit, no
flow control.
Note: The Micro125 always uses these serial port settings on boot-up.
3. Reset the Micro125 unit by cycling the unit's power (turning the power off and back on).
Immediately upon resetting the device, enter three lowercase x characters (xxx).
Micro125 User Guide
36
Download from Www.Somanuals.com. All Manuals Search And Download.
6: Configuration via Telnet or Serial Port (Setup Mode)
Note: The easiest way to enter Setup Mode is to hold down the x key at the terminal (or
emulation) while resetting the unit. You must do this within three seconds of resetting the
Micro125.
At this point, the screen display is the same as when you use a Telnet connection. To
continue, go to step 4, above under the section, Telnet Connection
.
Exiting Setup Mode
To exit setup mode, utilize one of the following two options:
To save all changes and reboot the device, select option 9 Save and exit from the
Change Setup menu. All values are stored in nonvolatile memory.
To exit the configuration mode without saving any changes or rebooting, select option 8
Exit without save from the Change Setup menu.
Micro125 User Guide
37
Download from Www.Somanuals.com. All Manuals Search And Download.
7. Setup Mode: Server Configuration
This chapter explains how to configure the network settings.
Note: Current values appear in parentheses.
Server Configuration (Option 0)
The unit’s basic network parameters display when you select Server configuration (option
0). The IP Address, Set Gateway IP Address, and Netmask fields display the current
values.
IP Address : (000) .(000) .(000) .(000)
Set Gateway IP Address (N) ?
Netmask: Number of Bits for Host Part (0=default) (0)
Set DNS Server IP addr (N) ?
Change Telnet/Web Manager password (N) ?
Change DHCP device name (not set) ? (N) ?
Enable DHCP FQDN option : (N) ?
IP Address
If DHCP is not used to assign IP addresses, enter the IP address manually. The IP address
must be set to a unique value in the network. Enter each octet and press Enter between
each section. The current value displays in parentheses.
IP Address : (000) (000) (000) (000) _
If DHCP is used, the third octet of the IP address sets the BootP/DHCP/AutoIP options. The
following table shows the bits you can manually configure to force the Micro125 to disable
AutoIP, DHCP, or BootP. To disable an option, set the appropriate bit.
Table 7-1. BootP/DHCP/AutoIP options
Options
AutoIP
DHCP
Bit
0
1
BootP
2
For example, if the third octet is 0.0.5.0, the AutoIP and BootP options are disabled; only
DHCP is enabled. (The value 5 results from adding the binary equivalents of 0 and 2.) This is
the most common setting when using DHCP.
Micro125 User Guide
38
Download from Www.Somanuals.com. All Manuals Search And Download.
7: Setup Mode: Server Configuration
Set Gateway IP Address
The gateway address, or router, allows communication to other LAN segments. The gateway
address should be the IP address of the router connected to the same LAN segment as the
unit. The gateway address must be within the local network. The default is N (No), meaning
the gateway address has not been set. To set the gateway address, type Y and enter the
address.
Set Gateway IP Address (N) ? Y
Gateway IP addr ( 0) ( 0) ( 0) ( 0)_
Netmask: Number of Bits for Host Part
A netmask defines the number of bits taken from the IP address that are assigned for the
host part.
Netmask: Number of Bits for Host Part (0=default) (0) _
Note: Class A: 24 bits; Class B: 16 bits; Class C: 8 bits
The unit prompts for the number of host bits to be entered, then calculates the netmask,
which appears in standard decimal-dot notation (for example, 255.255.255.0) when the saved
parameters display.
Table 7-2. Standard IP Network Netmasks
Network Class
Host Bits
Netmask
A
B
C
24
16
8
255.0.0.0
255.255.0.0
255.255.255.0
Set DNS Server IP Address
The DNS server allows the name of a remote machine to be resolved automatically. The
default is N (No), indicating the DNS server address has not been set. To set the DNS server
address, type Y. At the prompt, enter the DNS server address. If the device is DHCP
enabled, the DHCP server provides the DNS server IP address, which will override this
configured value.
Note: This setting is applicable only in Manual Connection mode.
Set DNS Server IP addr (N) ?
Micro125 User Guide
39
Download from Www.Somanuals.com. All Manuals Search And Download.
7: Setup Mode: Server Configuration
Change Telnet/Web-Manager Password
Setting the Telnet/Web-Manager password prevents unauthorized access to the setup menu
through a Telnet connection to port 9999 or through web pages. The password must have 4
characters.
Change Telnet/Web-Manager password (N) ? _
An enhanced password setting (for Telnet access only) of 16 characters is available under
Note: You do not need a password to access the Setup Mode window by a serial connection.
DHCP Name
If a DHCP server has automatically assigned the IP address and network settings, you can
discover the unit by using the DeviceInstaller network search feature.
There are three methods for assigning DHCP names to the unit.
Default DHCP Name: If you do not change the DHCP name, and you are using an IP of
0.0.0.0, then the DHCP name defaults to CXXXXXX (XXXXXX is the last 6 digits of the MAC
address shown on the label on the bottom/side of the unit). For example, if the MAC address
is 00-20-4A-12-34-56, then the default DHCP name is C123456.
Custom DHCP Name: You can create your own DHCP name. If you are using an IP
address of 0.0.0.0, then the last option in Server configuration is Change DHCP device
name. This option allows you to change the DHCP name to an alphanumeric name (LTX in
our example).
Change DHCP device name (not set) ? (N) Y
Enter new DHCP device name : LTX
Numeric DHCP Name: You can change the DHCP name by specifying the last octet of the
IP address. When you use this method, the DHCP name is LTXYY where YY is what you
chose for the last octet of the IP address. If the IP address you specify is 0.0.0.12, then the
DHCP name is LTX12. This method only works with 2 digit numbers (01-99).
Micro125 User Guide
40
Download from Www.Somanuals.com. All Manuals Search And Download.
8. Setup Mode: Channel Configuration
This chapter explains how to configure the serial port. Two channels may be configured in
Micro125: Channel 1 and Channel 2.
Note: The directions for configuring Channel 1 provided below may also be used for
Channel 2.
Channels
Select Channel 1 (option 1) from the Change Setup menu to define how the serial port
responds to network and serial communications. The following sections describe the
configurable parameters within the Channel configuration menu.
Figure 8-1. Serial Port Parameters
Baudrate (9600) ?
I/F Mode (4C) ?
Flow (00) ?
Port No (10001) ?
ConnectMode (C0) ?
Send '+++' in Modem Mode (Y) ?
Show IP addr after 'RING' (Y) ?
Auto increment source port (N) ?
Remote IP Address : (000) .(000) .(000) .(000)
Remote Port (0) ?
DisConnMode (00) ?
FlushMode (00) ?
DisConnTime (00:00) ?:
SendChar 1 (00) ?
SendChar 2 (00) ?
Baudrate
The unit and attached serial device, such as a modem, must agree on a speed or baud rate
to use for the serial connection. Valid baud rates are 300, 600, 1200, 2400, 4800, 9600
(default), 19200, 38400, 57600, 115200, and 230400 bits per second. The current value is
displayed in parentheses. Entering a baud rate of 00 in channel settings in a telnet sessions
disables the serial port.
Baudrate (9600) ? _
Micro125 User Guide
41
Download from Www.Somanuals.com. All Manuals Search And Download.
8: Setup Mode: Channel Configuration
I/F (Interface) Mode
The Interface (I/F) Mode is a bit-coded byte entered in hexadecimal notation.
I/F Mode (4C) ? _
The following table displays available I/F Mode options:
Note: All bit positions in the table that are blank represent “don’t care” bits for that particular
option, which can be set to either a 0 or 1 value.
Table 8-1. Interface Mode Options
I/F Mode Option
RS-232C (1)
7 Bit
7
6
5
4
3
2
1
0
0
0
1
1
0
1
8 Bit
No Parity
Even Parity
Odd Parity
1 stop bit
2 stop bits (1)
0
1
0
0
1
1
0
1
1
1
(1) 2 stop bits are implemented by the software. This might influence performance.
The following table demonstrates how to build some common Interface Mode settings:
Table 8-2. Common Interface Mode Settings
Common I/F Mode Setting
Binary
Hex
RS-232C, 8-bit, No Parity, 1 stop bit
RS-232C, 7-bit, Even Parity, 1 stop bit
0100 1100 4C
0111 1000 78
I/F Mode
Additional settings for RS-422 4-wire and RS-485 2-wire are available on the
Micro125. However, this feature is only supported on channel 1.
Note: All bit positions in the table that are blank represent “don’t care” bits, for that particular
option, which can be set to either a 0 or 1 value.
Micro125 User Guide
42
Download from Www.Somanuals.com. All Manuals Search And Download.
8: Setup Mode: Channel Configuration
Table 8-3. Interface Mode Options
I/F Mode Option
RS-422 4-wire
RS-485 2-wire
7
6
5
4
3
2
1
0
1
0
1
1
Flow
Flow control sets the local handshaking method for stopping serial input/output.
Flow (00) ? _
Use the following table to select flow control options:
Table 8-4. Flow Control Options
Flow Control Option
Hex
No flow control
00
01
02
05
XON/XOFF flow control
Hardware handshake with RTS/CTS lines
XON/XOFF pass characters to host
Port Number
The setting represents the source port number in TCP connections. It is the number that
identifies the channel for remote initiating connections.
Port No (10001) ? _
The default setting for Port 1 is 10001. The range is 1-65535, except for the following
reserved port numbers:
Table 8-5. Reserved Port Numbers
Port Numbers Reserved for
1 – 1024
9999
Reserved (well known ports)
Telnet setup
14000-14009
30704
Reserved for Redirector
Reserved (77F0h)
30718
Reserved (77FEh)
WARNING: We recommend that you not use the reserved port numbers
for this setting as incorrect operation may result.
Use Port 0 for the outgoing local port to change with each connection. The port range is
50,000 to 59,999. Each subsequent connection increments the number by 1 (it wraps back
around to 50,000).
Only use this automatic port increment feature to initiate a connection using TCP. Set the port
to a non-zero value when the unit is in a passive mode or when using UDP instead of TCP.
Micro125 User Guide
43
Download from Www.Somanuals.com. All Manuals Search And Download.
8: Setup Mode: Channel Configuration
Connect Mode
Connect Mode defines how the unit makes a connection, and how it reacts to incoming
connections over the network.
ConnectMode (C0) ? _
Enter Connect Mode options in hexadecimal notation.
Note: All bit positions in the table that are blank represent “don’t care” bits, for that particular
option, which can be set to either a 0 or 1 value.
Table 8-6. Connect Mode Options
Connect Mode Option
a) Incoming Connection
Never accept incoming
7
6
5
4
3
2
1
0
0
0
1
0
1
1
0
0
0
Accept with active Modem Control In
Always Accept
b) Response
Nothing (quiet)
0
1
Character response (C=connect,
D=disconnect, N=unreachable)
c) Active Startup
No active startup
0
0
0
0
0
0
0
0
0
0
1
1
0
0
1
1
0
0
0
1
0
1
0
1
With any character
With active Modem Control In
With a specific start character
Manual connection
Autostart
Hostlist
0
0
1
0
d) Datagram Type
Directed UDP
e) Modem Mode
No Echo
1
1
0
0
0
0
0
1
1
1
1
1
Data Echo & Modem Response
(Numeric)
1
Data Echo & Modem Response
(Verbose)
0
0
1
0
1
1
1
1
0
1
Modem Response Only (Numeric)
1
Micro125 User Guide
44
Download from Www.Somanuals.com. All Manuals Search And Download.
8: Setup Mode: Channel Configuration
Connect Mode Option
7
6
5
4
3
2
1
0
Modem Response Only (Verbose)
0
0
1
1
1
0
a) Incoming Connection
Incoming Connection Mode
Description
Never Accept Incoming
Rejects all external connection attempts.
Accepts external connection requests only when the Modem
Accept with active Modem
Control In
Control In input is asserted. Cannot be used with Modem Mode.
Always Accept
Accepts any incoming connection when a connection is not
already established. Default setting.
b) Response
Response Mode
Description
Character Response
A single character is transmitted to the serial port when there is a
change in connection state:
C = connected, D = disconnected, N = host unreachable.
The IP address of the host connecting to the CoBos device will
be provided when you use verbose mode.
This option is overridden when the Active Start Modem Mode
or Active Start Host List is in effect. Default setting is Nothing
(quiet).
c) Active Startup
Active Startup Mode
No Active Startup
Description
Does not attempt to initiate a connection under any
circumstance. Default setting.
With Any Character
Attempts to connect when any character is received from the
serial port.
With active Modem Control
In
Attempts to connect when the Modem Control In input changes
from not asserted to asserted.
With a Specific Start
Character
Attempts to connect when it receives a specific start character
from the serial port. The default start character is carriage return.
Manual Connection
Attempts to connect when directed by a command string
received from the serial port. The first character of the command
string must be a C (ASCII 0x43), and the last character must be
either a carriage return (ASCII 0x0D) or a line feed (0x0A). No
blanks or space characters may be in the command string.
Between the first and last command string characters must be a
full or partial destination IP address and may be a destination
port number.
The IP address must be in standard decimal-dot notation and
may be a partial address, representing the least significant 1, 2,
or 3 bytes of the remote IP address. The period is required
between each pair of IP address numbers.
Micro125 User Guide
45
Download from Www.Somanuals.com. All Manuals Search And Download.
8: Setup Mode: Channel Configuration
Active Startup Mode
Description
If present, the port number must follow the IP address, must be
presented as a decimal number in the range 1-65535, and must
be preceded by a forward slash (ASCII 0x2F). The slash
separates the IP address and the port number. If you omit the
port number from a command string, the internally stored remote
port number starts a connection.
If a partial IP address is presented in a command string, it is
interpreted to be the least significant bytes of the IP address and
uses the internally stored remote IP address to provide the most
significant bytes of the IP address. If the IP address entered is
0.0.0.0/0, the device server enters Monitor Mode.
For example, if the remote IP address already configured in the
unit is 129.1.2.3, then an example command string would be
C3/7. (This would connect to 129.1.2.3 and port 7.) You may
also use a different ending for the connection string. For
example, C50.1/23 would connect you to 129.1.50.1 and port 23.
If an IP address does not follow the first command string
character (which is "C"), the subsequent character string is
interpreted as the host name and domain to be used in DNS
lookup. This character string can include a destination port
number as well. The port number can be preceded by either a
forward slash (/) or a colon ( : ).
Table 8-7. Manual Connection Address Example
Command String
C121.2.4.5/1
Result if remote IP is 129.1.2.3 and remote port is 1234
Complete override; connection is started with host 121.2.4.5,
port 1
C5
Connects to 129.1.2.5, port 1234
Connects to 129.1.28.10, port 12
Enters Monitor Mode
C28.10/12
C0.0.0.0/0
Tries to connect to the Lantronix web server if the
DNS server database.
Autostart (Automatic
Connection)
If you enable Autostart, the unit automatically connects to the
remote IP address & remote port specified when the firmware
starts.
Hostlist
If you enable this option, the device server scrolls through the
hostlist until it connects to a device listed in the hostlist table.
Once it connects, the unit stops trying to connect to any others.
If this connection fails, the unit continues to scroll through the
table until it is able to connect to another IP in the hostlist.
Hostlist supports a minimum of 1 and a maximum of 12 entries.
Each entry contains the IP address and the port number.
The hostlist is disabled for Manual and Modem Modes. The unit
does not accept a data connection from a remote device when
the hostlist option is enabled.
Micro125 User Guide
46
Download from Www.Somanuals.com. All Manuals Search And Download.
8: Setup Mode: Channel Configuration
Figure 8-2. Hostlist Option
Baudrate (9600) ?
I/F Mode (4C) ?
Flow (00) ?
Port No (10001) ?
ConnectMode (25) ?
Send '+++' in Modem Mode (Y) ?
Auto increment source port (N) ?
Hostlist :
01.IP : 172.019.000.001 Port : 00023
02.IP : 172.019.000.002 Port : 03001
03.IP : 172.019.000.003 Port : 10001
Change Hostlist ? (N) ? Y
01.IP address : (172) .(019) .(000) .(001)
02.IP address : (172) .(019) .(000) .(002)
03.IP address : (172) .(019) .(000) .(003)
04.IP address : (000) .(000) .(000) .(000)
Hostlist :
Port : (23) ?
Port : (3001) ?
Port : (10001) ?
01.IP : 172.019.000.001 Port : 00023
02.IP : 172.019.000.002 Port : 03001
03.IP : 172.019.000.003 Port : 10001
DisConnMode (00) ?
FlushMode (00) ?
DisConnTime (00:00) ?:
SendChar 1 (00) ?
SendChar 2 (00) ?
To enable the hostlist:
1. Enter a Connect Mode of 0x20 (2X), where X is any digit. The menu shows you a list of
current entries already defined in the product.
2. To delete, modify, or add an entry, select Yes. If you enter an IP address of 0.0.0.0, that
entry and all others after it are deleted.
3. After completing the hostlist, repeat the previous step if necessary to edit the hostlist
again.
4. For Retrycounter, enter the number of times the Lantronix unit should try to make a
good network connection to a hostlist entry that it has successfully ARPed. The range is
1-15, with the default set to 3.
5. For Retrytimeout, enter the number of seconds the unit should wait before failing an
attempted connection. The time is stored as units of milliseconds in the range of 10-
65535. The default is 250.
Micro125 User Guide
47
Download from Www.Somanuals.com. All Manuals Search And Download.
8: Setup Mode: Channel Configuration
d) Datagram Type
Datagram Type
Description
Directed UDP
When selecting this option, you are prompted for the Datagram type.
Enter 01 for directed or broadcast UDP. Datagrams of type 01 can be
sent as a broadcast by enabling the Send as Broadcast option. The
default is not to broadcast.
When the UDP option is in effect, the unit never attempts to initiate a
TCP connection because it uses UDP datagrams to send and receive
data.
e) Modem Mode
In Modem (Emulation) Mode, the unit presents a modem interface to the attached serial
device. It accepts AT-style modem commands and handles the modem signals correctly.
Normally, there is a modem connected to a local PC and a modem connected to a remote
machine. A user must dial from the local PC to the remote machine, accumulating phone
charges for each connection. Modem Mode allows you to replace modems with Micro125
units, and to use an Ethernet connection instead of a phone call. By not having to change
communications applications, you avoid potentially expensive phone calls.
To select Modem Mode, set the Connect Mode to C6 (no echo), D6 (echo with full verbose),
D7 (echo with numeric response), CF (modem responses only, numeric response), or CE
(modem responses only, full verbose).
Note: If the unit is in Modem Mode, and the serial port is idle, the unit can still accept network
TCP connections to the serial port if Connect Mode is set to C6 (no echo), D6 (echo with full
verbose), D7 (echo with numeric response, CF (modem responses only, numeric response),
or CE (modem responses only, full verbose).
Table 8-8. Modem Modes
Modem Mode
Without Echo
Description
In Modem Mode, echo refers to the echo of all of the characters
entered in command mode; it does not mean to echo data that is
transferred. Quiet Mode (without echo) refers to the modem not
sending an answer to the commands received (or displaying what was
typed).
Data Echo & Modem
Response
Full Verbose: The unit echoes modem commands and responds to a
command with a message string shown in the table below.
Numeric Response: The unit echoes modem commands and
responds to a command with a numeric response.
Modem Responses
Only
Full Verbose: The unit does not echo modem commands and
responds to a command with a message string shown in the table
below.
Numeric Response: The unit does not echo modem commands and
responds to a command with a numeric response.
Micro125 User Guide
48
Download from Www.Somanuals.com. All Manuals Search And Download.
8: Setup Mode: Channel Configuration
Table 8-9. Modem Mode Messages
Meaning
Message
Full Verbose
OK
Command was executed without error.
A network connection has been established.
A network connection has been closed.
CONNECT
NO CARRIER
A remote device, having IP address n.n.n.n, is connecting to this
device.
RING n.n.n.n.
Numeric Response
0
1
2
3
4
OK
Connected
Ring
No Carrier
Error
Received commands must begin with the two-character sequence AT and be terminated with
a carriage return character.
The unit ignores any character sequence received not starting with AT, and only recognizes
and processes single AT-style commands. The unit treats compound AT commands as
unrecognized commands.
If the Full Verbose option is in effect, the unit responds to an unrecognized command string
that is otherwise formatted correctly (begins with AT and ends with carriage return) with the
"OK" message and takes no further action.
If the Numeric Response option is in effect, the unit responds to an unrecognized command
string that is otherwise formatted correctly with the "OK" message and takes no further action.
When an active connection is in effect, the unit transfers data and does not process
commands received from the serial interface.
When a connection is terminated or lost, the unit reverts to command mode.
When an active connection is in effect, the unit terminates the connection if it receives the
following sequence from the attached serial device:
No serial data is received for one second.
The character sequence +++ is received, with no more than one second between each
two characters.
No serial data is received for one second after the last + character. At this time, the unit
responds affirmatively per the selected echo/response mode.
The character string ATH is received, terminated with a carriage return. The unit
responds affirmatively according to the selected echo/response mode and drops the
network connection. The serial interface reverts to accepting command strings.
Micro125 User Guide
49
Download from Www.Somanuals.com. All Manuals Search And Download.
8: Setup Mode: Channel Configuration
If this sequence is not followed, the unit remains in data transfer mode.
Table 8-10. Modem Mode Commands
Function
Modem Mode
Command
ATDTx.x.x.x,pppp,
ATDTx.x.x.x/pppp, or
ATDTx.x.x.x:pppp
Makes a connection to an IP address (x.x.x.x) and a remote port
number (pppp).
Makes a connection to an IP address (x.x.x.x) and the remote port
number defined within the unit.
ATDTx.x.x.x
ATD0.0.0.0
Forces the unit into Monitor Mode if a remote IP address and port
number are defined within the unit.
Forces the unit into Monitor Mode if a remote IP address and port
number are not defined within the unit.
ATD or ATDT
Makes a connection to an IP address (x.x.x.x) and the remote port
number defined within the unit.
ATDx.x.x.x
ATH
Hangs up the connection (Entered as +++ATH ).
Enables or disables connections from the network going to the serial
port.
n=0 disables the ability to make a connection from the network to the
serial port.
ATS0=n
n=1-9 enables the ability to make a connection from the network to
the serial port.
n>1-9 is invalid.
Enables or disables character echo and responses.
n=0 disables character echo and responses.
ATEn
ATVn
n=1 enables character echo and responses.
Enables numeric response or full verbose.
n=0 enables numeric response.
n=1 enables full verbose.
Note: The unit recognizes these AT commands as single commands such as ATE0 or ATV1;
it does not recognize compound commands such as ATE0V.
Send the Escape Sequence (+++) in Modem Mode
Send ‘+++’ in Modem Mode (Y) ? _
Disable or enable the Micro125’s ability to send the escape sequence. The default is Y (Yes)
(send the escape sequence).
Micro125 User Guide
50
Download from Www.Somanuals.com. All Manuals Search And Download.
8: Setup Mode: Channel Configuration
Show IP addr after 'RING'
Show IP addr after ‘RING’ (Y) ?
Disable or enable the Micro125's ability to show the IP address after RING in Modem Mode.
The default is Y (Yes), to show the IP address.
Auto Increment Source Port
Auto increment source port (N) ? _
Y (Yes) auto increment the source port. The Micro125 increments the port number used with
each new connection.
Remote IP Address
This is the destination IP address used with an outgoing connection.
Remote IP Address : (000) (000) (000) (000)_
Note: This option does not display when Hostlist is enabled from the ConnectMode prompt
Remote Port
You must set the remote TCP port number for the unit to make outgoing connections. This
parameter defines the port number on the target host to which a connection is attempted.
Remote Port (00) ? _
To connect an ASCII terminal to a host using the unit for login purposes, use the remote port
number 23 (Internet standard port number for Telnet services).
Note: This option does not display when Hostlist is enabled from the ConnectMode prompt
DisConnMode
This setting determines the conditions under which the unit will cause a network connection
to terminate.
DisConnMode (00) ? _
Notes:
In DisConnMode (Disconnect Mode), Modem Control In drop either drops the connection
or is ignored.
All bit positions in the table that are blank represent “don’t care” bits, for that particular
option, which can be set to either a 0 or 1 value.
Micro125 User Guide
51
Download from Www.Somanuals.com. All Manuals Search And Download.
8: Setup Mode: Channel Configuration
Table 8-11. Disconnect Mode Options
Disconnect Mode Option
7
6
5
4
3
2
1
0
Disconnect when Modem Control In is not asserted (6)
1
0
Ignore Modem Control In
Telnet Com Port Cntrl and terminal type setup (1)
Channel (port) password (2)
1
1
Hard disconnect (3)
0
1
Disable hard disconnect
State LED off with connection (4)
Disconnect with EOT (^D) (5)
1
1
(1) The Telnet Com Port Control feature is used in conjunction with Com Port Redirector. The unit
sends the Terminal Type upon an outgoing connection.
(2) A password is required for a connection to the serial port from the network.
(3) The TCP connection closes even if the remote site does not acknowledge the disconnection.
(4) When there is a network connection to or from the serial port, the state LED turns off instead of
blinking.
(5) When Ctrl+D or Hex 04 is detected, the connection is dropped. Both Telnet Com Port Cntrl and
Disconnect with EOT must be enabled for Disconnect with EOT to function properly. Ctrl+D is only
detected going from the serial port to the network.
(6) When Modem Control In transitions from a high state to a low state, the network connection to or
from the serial port drops.
Micro125 User Guide
52
Download from Www.Somanuals.com. All Manuals Search And Download.
8: Setup Mode: Channel Configuration
Flush Mode (Buffer Flushing)
Using this parameter, you can control line handling and network buffers with connection
startup and disconnect.
FlushMode (00) ? _
You can also select between two different packing algorithms.
Note: All bit positions in the table that are blank represent “don’t care” bits, for that particular
option, which can be set to either a 0 or 1 value.
Table 8-12. Flush Mode Options
Function
7
6
5
4
3
2
1
0
Input Buffer (Serial to Network)
Clear with a connection initiated from the device to the network
Clear with a connection initiated from the network to the device
1
1
Clear when the network connection to or from the device
is disconnected
1
Output Buffer (Network to Serial)
Clear with a connection initiated from the device to the network
Clear with a connection initiated from the network to the device
1
1
Clear when the network connection to or from the device
is disconnected
1
Alternate Packing Algorithm (Pack Control)
Enable
1
Pack Control
The packing algorithms define how and when packets are sent to the network. The standard
algorithm is optimized for applications in which the unit is used in a local environment,
allowing for very small delays for single characters, while keeping the packet count low. The
alternate packing algorithm minimizes the packet count on the network and is especially
useful in applications in a routed Wide Area Network (WAN). Adjusting parameters in this
mode can economize the network data stream.
Pack control settings are enabled in Flush Mode. Set this value to 00 if you do not need
specific functions.
Note: All bit positions in the table that are blank represent “don’t care” bits, for that particular
option, which can be set to either a 0 or 1 value.
Table 8-13. Pack Control Options
Option
7
6
5
4
3
2
1
0
Packing Interval
Micro125 User Guide
53
Download from Www.Somanuals.com. All Manuals Search And Download.
8: Setup Mode: Channel Configuration
Option
Interval: 12ms
7
6
5
4
3
2
1
0
0
1
1
0
0
1
0
1
Interval: 52ms
Interval: 250ms
Interval: 5sec
Trailing Characters
None
0
0
1
0
1
0
One
Two
Send Characters
2-Byte Send Character Sequence
Send Immediately After Send chars
1
1
Packing Interval
Packing Interval defines how long the unit should wait before sending accumulated
characters. This wait period is between successive network segments containing data. For
alternate packing, the default interval is 12 ms.
Trailing Characters
In some applications, CRC, Checksum, or other trailing characters follow the end-of-
sequence character; this option helps to adapt frame transmission to the frame boundary.
Send Characters
If 2-Byte Send Character Sequence is enabled, the unit interprets the sendchars as a 2-
byte sequence; if this option is not enabled, the unit interprets them independently.
If Send Immediately After Characters is not set, any characters already in the serial
buffer are included in the transmission after a "transmit" condition is found. If this option is
set, the unit sends immediately after recognizing the transmit condition (sendchar or
timeout).
Note: A transmission might occur if status information needs to be exchanged or an
acknowledgment needs to be sent.
DisConnTime (Inactivity Timeout)
Use this parameter to set an inactivity timeout. The unit drops the the TCP connection to port
10001/10002* if there is no activity on the serial line before the set time expires. Enter time in
the format mm:ss, where m is the number of minutes and s is the number of seconds.
Note*: The default port number for Port 1 is 10001 and 10002 for Port 2. However,
port numbers may be set to a different value.
Micro125 User Guide
54
Download from Www.Somanuals.com. All Manuals Search And Download.
8: Setup Mode: Channel Configuration
DisConnTime (00:00) ?:
To disable the inactivity timeout, enter 00:00. Range is 0 (disabled) to 5999 seconds (99
minutes, 59 seconds). Default is 0.
Send Characters
Enter up to two characters in hexadecimal representation in sendchar.
SendChar 1 (00) ? _
SendChar 2 (00) ? _
If the unit receives a character on the serial line that matches one of these characters, it
sends the character immediately, along with any awaiting characters, to the TCP connection.
This action minimizes the response time for specific protocol characters on the serial line (for
example, ETX, EOT). Setting the first sendchar to 00 disables the recognition of the
characters. Alternatively, the unit can interpret two characters as a sequence (see Pack
Telnet Terminal Type
This parameter displays only if you enabled the terminal type option in Disconnect Mode.
With this option enabled, you can use the terminal name for the Telnet terminal type. Enter
only one name.
With terminal type option enabled, the unit also reacts to the EOR (end of record) and binary
options, useful for applications like terminal emulation to IBM hosts.
Channel (Port) Password
This parameter appears only if the channel (port) password option is enabled in Disconnect
Mode. With this option enabled, you can set a password on the serial port.
Micro125 User Guide
55
Download from Www.Somanuals.com. All Manuals Search And Download.
9. Setup Mode: Advanced Settings
Expert Settings (Option 5)
Note: You can change the Enable alternate MAC setting using telnet or serial connections
only. It is not available through the Web-Manager.
CAUTION: Only an expert should change these parameters. You must definitely know
the consequences the changes might have.
Figure 9-1. Expert Settings
TCP Keepalive time in s (1s – 65 s; 0s-disable): (45) ?
ARP Cache timeout in s (1s – 600s) : (600) ?
Disable Monitor Mode @ bootup (N) ?
HTTP Port Number : (80) ?
MTU Size (512 – 1400): (1400) ?
TCP Re-transmission Timeout (500 - 4000) (ms): (500) ?
Enable alternate MAC (N) ?
Ethernet connection type: (0) ?
The default settings are listed below:
Table 9-1. Expert Settings: Details Settings
Device Details Settings
Description
TCP Keepalive time in s
(1s – 65s; 0s=disable)
45
ARP Cache timeout in s (1s – 600s)
Disable Monitor Mode @ bootup
HTTP Port Number (1-65535)
600
No
80
MTU Size (512 – 1400)
0 (resulting in an operational value of 1400)
500 (msec)
TCP Re-Transmission Timeout
(500-4000)
Enable alternate MAC
No (OEM use only)
Ethernet connection type
0 (resulting in auto-negotiation)
TCP Keepalive Time in Seconds
This option allows you to change how many seconds the unit waits during a silent connection
before attempting to see if the currently connected network device is still on the network. If
the unit gets no response, it drops that connection.
TCP Keepalive time in s (1s – 65s; 0s=disable): (45)? _
Micro125 User Guide
56
Download from Www.Somanuals.com. All Manuals Search And Download.
9: Setup Mode: Advanced Settings
ARP Cache Timeout in Seconds
Whenever the unit communicates with another device on the network, it adds an entry into its
ARP table. The ARP Cache timeout option allows you to define how many seconds (1-600)
the unit will wait before timing out this table.
ARP Cache timeout in s (1s - 600s) : (600) ?
Disable Monitor Mode at Bootup
This option allows you to disable all entries into Monitor Mode during startup, except for the
‘xxx’ sequence. This prevents entry using yyy, zzz, xx1, and yy1 key sequences (only during
Disable Monitor Mode @ bootup (N) ? _
HTTP Port Number
This option allows the configuration of the web server port number. The valid range is
1-65535. The default HTTP port number is 80.
HTTP Port Number : (80) ? _
MTU Size
The Maximum Transmission Unit (MTU) is the largest physical packet size a network can
transmit for TCP and UDP. Enter between 512 and 1400 bytes. The default is 1400 bytes.
MTU Size: (1400) ? _
TCP Re-transmission Timeout
This feature allows the configuration of the desired TCP re-transmission timeout value. If the
ACK is not received for a packet sent from the Micro125 device, then the unit will retransmit
the data. The valid range is 500-4000 msec.
TCP Re-transmission Timeout (500 - 4000) (ms): (500) ?
Enable Alternate MAC
If necessary, enable the alternate MAC address (if specified in the OEM setup record).
Enable alternate MAC (N) ? _
Ethernet Connection Type
The Micro125 allows for the Ethernet speed and duplex to be manually configured. Enter 0
for auto-negotiation (default). To select the speed and duplex, enter one of the following: 2
(10Mbit/half duplex), 3 (10Mbit/full duplex), 4 (100Mbit/half duplex), or 5 (100Mbit/full duplex).
Ethernet connection type: (0) ? _
Micro125 User Guide
57
Download from Www.Somanuals.com. All Manuals Search And Download.
9: Setup Mode: Advanced Settings
Security Settings (Option 6)
Note: You can change security settings by means of Telnet or serial connections only, not on
the Web-Manager. We recommend that you set security over the dedicated network or over
the serial setup to prevent eavesdropping.
CAUTION: Disabling both Telnet Setup and Port 77FE will prevent users
from accessing the setup menu from the network. Disabling Port 77FE
also disables the Web from configuring the device.
Select 6 to configure security settings.
Figure 9-2. Security Settings
Disable SNMP (N) ?
SNMP Community Name (public):
Disable Telnet Setup (N)?
Disable TFTP Firmware Update (N)?
Disable Port 77FEh (N)?
Disable Web Server (N)?
Disable Web Setup (N)?
Disable ECHO ports (Y)?
Enable Encryption (N)?
Enable Enhanced Password (N)?
Disable SNMP
This setting allows you to disable the SNMP protocol on the unit for security reasons.
Disable SNMP (N) ? _
SNMP Community Name
The SNMP Community Name is a required field for NMS to read or write to a device. Enter a
string of 1 to 13 characters.
SNMP Community Name (public): _
The default entry is public. The current value is displayed in parentheses.
Disable Telnet Setup
Note: If you choose to disable this option, keep in mind that disabling both Telnet Setup and
Port 77FE will prevent users from accessing the setup menu from the network.
This setting defaults to the N (No) option. The Y (Yes) option disables access to Setup Mode
by Telnet (port 9999). It only allows access locally using the web pages and the serial port of
the unit.
Disable Telnet Setup (N) ? _
Micro125 User Guide
58
Download from Www.Somanuals.com. All Manuals Search And Download.
9: Setup Mode: Advanced Settings
Disable TFTP Firmware Upgrade
This setting defaults to the N (No) option. The Y (Yes) option disables the use of TFTP to
perform network firmware upgrades. With this option, you can download firmware upgrades
over the serial port using DeviceInstaller’s Recover Firmware procedure. (See 10: Firmware
Disable TFTP Firmware Update (N) : _
Disable Port 77FE (Hex)
If you choose to disable this option, keep in mind that disabling both the Telnet Setup and
Port 77FE will prevent users from accessing the setup menu from the network. Port 77FE is
a setting that allows DeviceInstaller, WebManager, and custom programs to configure the
unit remotely. You may wish to disable this capability for security purposes.
Disable Port 77FEh(N) ?
Note: The default setting is the N (No) option, which enables remote configuration. You can
configure the unit by using DeviceInstaller, web pages, Telnet, or serial configuration. The Y
(Yes) option disables remote configuration and web sites. The Y (Yes) option also disables
many of the GUI tools for configuring the unit, including the embedded WebManager tool.
Disable Web Server
This setting defaults to the N (option). The Y (Yes) option disables the web server.
Disable Web Server (N) ? _
Disable Web Setup
The Y (Yes) option disables configuration using the Web-Manager. This setting defaults to
the N (option).
Disable Web Setup (N) ? _
Disable ECHO Ports
This setting controls whether port 7 echoes characters it receives.
Disable ECHO ports (Y) ? _
Enable Encryption
Rijndael is the block cipher algorithm chosen by the National Institute of Science and
Technology (NIST) as the Advanced Encryption Standard (AES) to be used by the US
government. The Micro125 supports 128-, 192-, and 256-bit encryption key lengths.
Note: Configuring encryption should be done through a local connection to the serial port of
the Micro125, or via a secured network connection. Initial configuration information, including
the encryption key, is sent in clear text over the network.
Micro125 User Guide
59
Download from Www.Somanuals.com. All Manuals Search And Download.
9: Setup Mode: Advanced Settings
To configure AES encryption on the Micro125:
Enable Encryption (N) Y
Key length in bits (0): 128
Change Keys (N) Y
Enter Keys: **-**-**-**-**-**-**-**-**-**-**-**-**-**-**-**-
1. When prompted to enable encryption, select Y.
2. When prompted, enter the encryption key length. The Micro125 supports 128-, 192-, and
256-bit encryption key lengths.
3. When prompted to change keys, select Y.
4. At the Enter Keys prompt, enter your encryption key. The encryption keys are entered in
hexadecimal. The hexadecimal values are echoed as asterisks to prevent onlookers from
seeing the key. Hexadecimal values are 0-9 and A-F.
.
.
.
For a 128-bit key length, enter 32 hexadecimal characters.
For a 192-bit key length, enter 48 hexadecimal characters.
For a 256-bit key length, enter 64 hexadecimal characters
5. Continue pressing Enter until you return to the Change Setup menu.
6. From the Change Setup menu, select option 9 to save and exit.
Encryption only applies to the port selected for data tunneling (default 10001), regardless of
whether you are using TCP or UDP.
Generally, one of these situations applies:
Encrypted Micro125-to-Micro125 communication. Be sure to configure both Micro125
devices with the same encryption key.
Third-party application to Micro125-encrypted communication: Micro125 uses standard
AES encryption protocols. To communicate successfully, products and applications on
the peer side must use the same protocols and the same encryption key as the Micro125.
Lantronix Secure Com Port Redirector provides an encrypted connection from Windows-
based applications to the Micro125. Information about SCPR is available on our web site,
is available.
Note: Developers can license the Lantronix Encryption Library Suite. See
Enable Enhanced Password
This setting defaults to the N (No) option, which allows you to set a 4-character password that
protects Setup Mode by means of Telnet and web pages. The Y (Yes) option allows you to
set an extended security password of 16-characters for protecting Telnet and Web Page
access.
Enable Enhanced Password (Y) ? _
Micro125 User Guide
60
Download from Www.Somanuals.com. All Manuals Search And Download.
9: Setup Mode: Advanced Settings
Default Settings (Option 7)
Select 7 to reset the unit’s channel configuration and expert settings to the default settings.
The server configuration settings for IP address, gateway IP address, and netmask remain
unchanged. The specific settings that this option changes are listed below:
Channel 1 and Channel 2 Configuration Defaults
Channel Setting
Default Configuration
Baudrate
I/F Mode
Flow
9600
4C (1 stop bit, no parity, 8 bit, RS-232C)
00 (no flow control)
Port number
10001 (channel 1)
10002 (channel 2)
Connect Mode
C0 (always accept incoming connection; no active
connection startup)
Send '+++' in Modem Mode
Show IP addr after 'RING'
Auto increment source port
Hostlist retry counter
Enabled
Enabled
Disable
3
Hostlist retry timeout
250 (msec)
0x0D (CR)
0
Start character for serial channel 1
All other parameters
Expert Settings Defaults
Expert Setting
Default Configuration
TCP Keepalive time in s
ARP Cache timeout in s
Disable Monitor Mode @ bootup
HTTP Port Number
45
600
No
80
MTU Size
0 (resulting in an operational value of 1400)
500 (ms)
TCP Re-Transmission Timeout
(500-4000)
Alternate MAC
Disabled ( for OEM use only)
0 (auto-negotiate)
Ethernet Connection Type
Micro125 User Guide
61
Download from Www.Somanuals.com. All Manuals Search And Download.
9: Setup Mode: Advanced Settings
Security Settings Defaults
Security Setting
Default Configuration
Disable SNMP
No
SNMP community name
Disable Telnet setup
Disable TFTP Firmware Update
Disable Port 77FEh
public
No
No
No
Disable Web Server
Disable Web Setup
No
No
Disable ECHO ports
Enable Encryption
Yes
No
Enable Enhanced Password
No
Micro125 User Guide
62
Download from Www.Somanuals.com. All Manuals Search And Download.
10. Firmware Upgrades
Obtaining Firmware
You can obtain the most up-to-date firmware and release notes for the unit from the Lantronix
Reloading Firmware
There are several ways to update the unit's internal operational code (*.ROM): using
DeviceInstaller (the preferred way), using TFTP, or using the serial port. You can also update
the unit's internal Web interface (*.COB) using TFTP or DeviceInstaller.
Here are typical names for those files. Check the Lantronix web site for the latest versions
and release notes.
Table 10-1. Firmware Files
ROM File
COB
m125e_6804.rom
m125_webm_1903.cob
Please refer to the DeviceInstaller online Help for information about reloading firmware using
DeviceInstaller. The other methods are discussed below.
Using TFTP: Graphical User Interface
To download new firmware from a computer:
1. Use a TFTP client to put a binary file to the unit (*.ROM to upgrade the unit's internal
operational code and *.COB to upgrade its internal web interface).
Note: TFTP requires the .rom (binary) version of the unit's internal operational code.
2. In the TFTP server field, enter the IP address of the unit being upgraded.
3. Select Upload operation and Binary format.
4. Enter the full path of the firmware file in the Local file name field.
5. In the Remote file name field, enter the current internal operational code or WEB1 to
WEB6 for the internal web interface.
Micro125 User Guide
63
Download from Www.Somanuals.com. All Manuals Search And Download.
10: Firmware Upgrades
Figure 10-1. TFTP Window
6. Click the Upload Now button to transfer the file to the unit. The unit performs a power
reset after the firmware has been loaded and stored.
Using TFTP: Command Line Interface
To download new firmware from a computer:
1. Enter the following from a TFTP command line interface:
tftp –i <ip address> put <local filename> <destination file name>
The following examples demonstrate the TFTP command sequence to download the .rom file
and the .cob file:
tftp –i 192.168.1.111 put m125e_6804.rom 5M
tftp –i 192.168.1.111 put m125_webm_1903.cob WEB1
Micro125 User Guide
64
Download from Www.Somanuals.com. All Manuals Search And Download.
10: Firmware Upgrades
Recovering the Firmware Using the Serial Port and DeviceInstaller
If for some reason the firmware is damaged, you can recover the firmware file by using
DeviceInstaller to download the *.ROM file over the serial port.
To recover firmware:
1. Start DeviceInstaller. If your PC has more than one network adapter, a message
displays. Select an adapter and click OK.
2. From the Tools menu, select Advanced/Recover Firmware. The Serial Port Firmware
Upgrade window displays.
3. For Port on PC, enter the COM port on the PC that is connected to the serial port of the
Lantronix unit.
Note: Make sure the Micro125 on which you are recovering firmware is connected to this
selected port on your PC.
4. For Device Model, be sure the appropriate Micro125 device is selected.
5. For Firmware File, click the Browse button and go to the location where the firmware file
resides.
6. Click OK to download the file.
7. When prompted, reset the device. Status messages and a progress bar at the bottom of
the screen show the progress of the file transfer. When the file transfer completes, the
message “Successful, Click OK to Close” appears.
8. Click the OK button to complete this procedure.
Note: For more information, see Recovering Firmware in the DeviceInstaller online Help.
Micro125 User Guide
65
Download from Www.Somanuals.com. All Manuals Search And Download.
11. Monitor Mode
Monitor Mode is a command-line interface used for diagnostic purposes.
There are two ways to enter Monitor Mode: locally using the serial port or remotely using the
network.
Entering Monitor Mode Using the Serial Port
To enter Monitor Mode locally:
1. Follow the same steps used for setting the serial configuration parameters
2. Instead of typing three x keys, however:
3. Type zzz (or xx1) to enter Monitor Mode with network connections.
4. Type yyy (or yy1) to enter Monitor Mode without network connections.
A 0> prompt indicates that you have successfully entered Monitor Mode.
Entering Monitor Mode Using the Network Port
To enter Monitor Mode using a Telnet connection:
1. Establish a Telnet session to the configuration port (9999). The following message
appears:
MAC address 00204AAE0412
Software version V6.8.0.4 (121207) M125
AES library version 1.8.2.1
Press Enter for Setup Mode
2. Type M (upper case).
A 0> prompt indicates that you have successfully entered Monitor Mode.
Monitor Mode Commands
The following commands are available in Monitor Mode. Many commands have an IP
address as an optional parameter (xxx.xxx.xxx.xxx). If you enter the IP address, the
command is applied to another unit with that IP address. If you do not enter the IP address,
the command is executed locally.
Note: All commands must be in capital letters. Responses to some of the commands are in
Intel Hex format.
Micro125 User Guide
66
Download from Www.Somanuals.com. All Manuals Search And Download.
11: Monitor Mode
Table 11-1. Monitor Mode Commands
Command Name Function
Command
VS x.x.x.x
Version
Queries software header record (16 bytes) of unit with
IP address x.x.x.x.
GC x.x.x.x
SC x.x.x.x
PI x.x.x.x
Get Configuration
Send Configuration
Ping
Gets configuration of unit with IP address x.x.x.x as
hex records (120 bytes).
Sets configuration of unit with IP address x.x.x.x from
hex records.
Pings unit with IP address x.x.x.x to check device
status.
AT
TT
NC
ARP Table
Shows the unit’s ARP table entries.
TCP Connection Table Shows all incoming and outgoing TCP connections.
Network Connection
Shows the unit’s IP address, gateway, subnet mask,
and DNS server.
RS
Reset
Quit
Resets the unit’s power.
Exits diagnostics mode.
QU
G0, G1, ....,Ge, Gf
Get configuration from
memory page
Gets a memory page of configuration information
from the device.
S0, S1,...,Se, Sf
Set configuration to
memory page
Sets a memory page of configuration information on
the device.
GM
SS
Get MAC address
Set Security record
Shows the unit's 6-byte MAC address.
Sets the Security record without the encryption key
and length parameters. The entire record must still be
written, but the encryption-specific bytes do not need
to be provided (they can be null since they are not
overwritten).
SA
Scan
Initiates a wireless scan if the wireless interface is
enabled. Reports any stations found, including
BSSID, SSID, and RSSI. If SA is followed by a string,
the string is used to filter SSIDs before reporting. If
the BSS does not broadcast its SSID, only the BSSID
and RSSI are returned.
NS
co
Network Status
Reports the network interfaces’ statuses. Includes
potentially negotiated parameters like speed/duplex
for Ethernet or BSSID, encryption, authentication for
wireless interfaces.
Example:
Set IP address,
hostbits, gateway ,
and DNS server IP
co 192.168.0.10 8 192.168.0.1 10001 192.168.1.10
with
192.168.0.10 = IP address of the Micro125
8 = number of hostbits
192.168.0.1 = gateway IP address
10001 = port number of the Micro125
192.168.1.10 = IP address of the DNS Server
The Micro125 stores the setup and performs a reset.
It sends an X before the reset if the command was
OK.
Micro125 User Guide
67
Download from Www.Somanuals.com. All Manuals Search And Download.
11: Monitor Mode
Note: Entering any of the commands listed above generates one of the following command
response codes:
Table 11-2. Command Response Codes
Response
Meaning
0>
1>
2>
8>
9>
OK; no error
No answer from remote device
Cannot reach remote device or no answer
Wrong parameter(s)
Invalid command
Micro125 User Guide
68
Download from Www.Somanuals.com. All Manuals Search And Download.
12. Troubleshooting
This chapter discusses how you can diagnose and fix errors quickly without having to contact
a dealer or Lantronix. It helps to connect a terminal to the serial port while diagnosing an
error to view summary messages that may display. When troubleshooting, always ensure
that the physical connections (power cable, network cable, and serial cable) are secure.
Note: Some unexplained errors might be caused by duplicate IP addresses on the network.
Make sure that your unit's IP address is unique.
When troubleshooting the following problems, make sure that the Micro125 is powered up.
Confirm that you are using a good network connection.
Problems and Error Messages
Problem/Message
Reason
Solution
When you issue the ARP –S
command in Windows, the
"ARP entry addition failed: 5"
message displays.
Your currently logged-in user
does not have the correct rights
to use this command on this
PC.
Have someone from your IT
department log you in with
sufficient rights.
When you attempt to assign an
IP address to the unit by the
ARP method, the "Press Enter
to go into Setup Mode" error
"(described below) message
displays. Now when you Telnet
to the device server, the
When you Telnet to port 1 on
the device server, you are only
assigning a temporary IP
address. When you Telnet into
port 9999 and do not press
Enter quickly, the device server
reboots, causing it to lose the IP
address.
Telnet back to Port 1. Wait for it
to fail, then Telnet to port 9999
again. Make sure you press
Enter quickly.
connection fails.
You did not press Enter quickly
enough. You only have 5
seconds to press Enter before
When you Telnet to port 9999,
the "Press Enter to go into
Setup Mode" message displays.
However, nothing happens
when you press Enter, or your
connection is closed.
Telnet to port 9999 again, but
press Enter as soon as you see
the "Press Enter to go into
Setup Mode" message.
the connection is closed.
When you Telnet to port 1 to
assign an IP address to the
device server, the Telnet
window does not respond for a
long time.
You may have entered the
Ethernet address incorrectly
with the ARP command.
Confirm that the Ethernet
address that you entered with
the ARP command is correct.
The Ethernet address may only
include numbers 0-9 and letters
A-F. In Windows and usually in
Unix, the segments of the
Ethernet address are separated
by dashes. In some forms of
Unix, the Ethernet address is
segmented with colons.
The IP address you are trying to Confirm that your PC has an IP
assign is not on your logical
subnet.
address and that it is in the
same logical subnet that you
are trying to assign to the
device server.
Micro125 User Guide
69
Download from Www.Somanuals.com. All Manuals Search And Download.
12: Troubleshooting
Problem/Message
Reason
Solution
The device server may not be
plugged into the network
properly.
Make sure that the Link LED is
lit. If the Link LED is not lit, then
the device server is not properly
plugged into the network.
When you try to assign an IP
with DeviceInstaller, you get the the following:
following :
The cause is most likely one of
Double-check the parameters
that you specified.
Note: You cannot assign an IP
address to a device server
through a router.
The hardware address you
specified is incorrect.
"No response from device!
Verify the IP, Hardware
Address and Network Class.
Please try again."
The IP address you are trying to
assign is not a valid IP for your
logical subnet.
You did not choose the correct
subnet mask.
The device server is not
communicating with the serial
device to which it is attached.
The most likely reason is the
wrong serial settings were
chosen.
The serial settings for the serial
device and the device server
must match. The default serial
settings for the device server
are RS-232, 9600 baud, 8
character bits, no parity, 1 stop
bit, no flow control.
When you try to enter the setup
mode on the device server
using the serial port, you get no
response.
The issue is most likely
Double-check everything in the
problem above. Confirm that
Caps Lock is not on.
something covered in the
previous problem, or possibly,
you have Caps Lock on.
You can ping the device server,
but not Telnet to the device
server on port 9999.
There may be an IP address
conflict on your network
Turn the device server off and
then issue the following
commands at the DOS prompt
of your computer:
You are not Telneting to port
9999.
ARP -D X.X.X.X (X.X.X.X is the
IP of the device server).
The Telnet configuration port
(9999) is disabled within the
device server security settings.
PING X.X.X.X (X.X.X.X is the IP
of the device server).
If you get a response, then
there is a duplicate IP address
on the network. If you do not
get a response, use the serial
port to verify that Telnet is not
disabled.
Micro125 User Guide
70
Download from Www.Somanuals.com. All Manuals Search And Download.
12: Troubleshooting
Problem/Message
Reason
Solution
The device server appears to
be set up correctly, but you are
not communicating with your
device attached to the device
server across the network.
If you are sure that the serial
port setting is correct, then you
may not be connecting to the
correct socket of the device
server.
You can check to see whether
there is a socket connection to
or from the device server by
looking at the Status LED.
If the Status LED is blinking
consistently, then there is a
good socket connection.
Another possibility is that the
device server is not set up
correctly to make a good socket
connection to the network.
If the Status LED is solid green,
then the socket connection
does not exist. Use the
Connect Mode option C0 for
making a connection to the
device server from the network.
Use Connect Mode option C1
or C5 for a connection to the
network from the device server.
See the full list of Connect
Mode options in Connect Mode
on page 44.
When connecting to the Web-
Manager within the device
server, the "No Connection With on the device server.
The Device Server" message
displays.
Your computer is not able to
connect to port 30718 (77FEh)
Make sure that port 30718
(77FEh) is not blocked with any
router that you are using on the
network. Also, make sure that
port 77FEh is not disabled
within the Security settings of
the device server.
Micro125 User Guide
71
Download from Www.Somanuals.com. All Manuals Search And Download.
12: Troubleshooting
Technical Support
If you are experiencing an error that is not described in this chapter, or if you are unable to fix
the error, you have the following options:
Technical Support US
Check our online knowledge base or send a question to Technical Support at
Phone: (800) 422-7044 (US Only)
(949) 453-7198
Technical Support Europe, Middle East, and Africa
Phone: +33 (0)1 39 30 41 72
+49 (0) 180 500 13 53 (Germany Only)
Firmware downloads, FAQs, and the most up-to-date documentation are available at
When you report a problem, please provide the following information:
Your name, and your company name, address, and phone number
Lantronix model number
Lantronix MAC number
Software version (on the first screen shown when you Telnet to port 9999)
Description of the problem
Status of the unit when the problem occurred (please try to include information on user
and network activity at the time of the problem).
Micro125 User Guide
72
Download from Www.Somanuals.com. All Manuals Search And Download.
A: Binary to Hexadecimal Conversions
Many of the unit’s configuration procedures require assembling a series of options
(represented as bits) into a complete command (represented as a byte). Convert the resulting
binary value to a hexadecimal representation.
Converting Binary to Hexadecimal
Following are two simple ways to convert binary numbers to hexadecimals.
Conversion Table
Hexadecimal digits have values ranging from 0 to F, which are represented as 0-9, A (for 10),
B (for 11), etc. To convert a binary value (for example, 0100 1100) to a hexadecimal
representation, the upper and lower four bits are treated separately, resulting in a two-digit
hexadecimal number (in this case, 4C). Use the following table to convert values from binary
to hexadecimal.
Decimal
Binary
Hex
0
1
0000
0001
0010
0011
0100
0101
0110
0111
1000
1001
1010
1011
1100
1101
1110
1111
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Micro125 User Guide
73
Download from Www.Somanuals.com. All Manuals Search And Download.
A: Binary to Hexadecimal Conversions
Scientific Calculator
Another simple way to convert binary to hexadecimals is to use a scientific calculator, such
as the one available on Windows’ operating systems. For example:
1. On the Windows’ Start menu, click ProgramsAccessoriesCalculator.
2. On the View menu, select Scientific. The scientific calculator displays.
3. Select Bin (Binary), and type the number to convert.
4. Click Hex. The hexadecimal value displays.
Micro125 User Guide
74
Download from Www.Somanuals.com. All Manuals Search And Download.
|