• Allows to address conventional
detectors Series FC600, 100, 300
and ECO1000
• Indication of detector number and
assigned element text on suitable fire
detection control panels
• Output for optional remote indicator
• Extremely small design
• Installation in the detector base
Description
The Address Module NG58-1 is an addressable elec-
tronic component, which allows to individually identify
automatic fire detectors Series FC600, 100, 300 and
ECO1000 as well as manual call points or contact de-
tectors in conventional technology.
to the fire detection control panel.
Apart from the detector address, on Fire Detection
Control Panels BC216 a possibly parameterised ele-
ment text (for example with the name of the room or
floor) can also be displayed.
The address module is installed in the detector base
and is preset with the detector address (within the num-
ber range 0 – 63) by cutting wire jumpers. In case of
alarm, the unique identification of the activated conven-
tional detector is achieved by transmitting the address
In addition to individual addressing, the address mo-
dule can as well be used for addressing a group of
several detectors. Thus, in case of alarm activation,
the address module achieves a summary indication of
this detector group.
Specifications
Current consumption at 24 V
Ambient temperature
Dimensions L × W × H
Weight
18mA (active)
-5°C to +50°C
32 × 19 × 5 (mm)
10g
Order number
249020
Order name
Address Module/Conv. NG58-1
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
NG58-1_DBL_LST_EN_0804.PDF • PAGE 1
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED