• Conventional technology
• Up to 20 detectors can be connected
to one safety barrier
• Extremely flat design
• Function testable with magnet
• ATEX certified
Description
The Intrinsically Safe Ionisation Smoke Detector the Safety Barrier ES58-2, the detector reaches the
1151EIS was developed for the safe detection of a given Ex classification. The two LEDs with 360° visibility
wide range of smoke aerosols. The modern design of indicate the activated condition of the detector.
the ionisation chamber allows to reliably evaluate the
characteristics of fire.
A detector function test can be conveniently conducted
using a magnet or test gas. The detector can be at-
Conventional technology is used for alarm transmission tached to various bases and it can be protected against
to the fire detection control panel. In conjunction with theft.
Specifications
Ignition protection
Ex classification
Current consumption at 24V
Ambient temperature
Relative humidity
Radioactive compound
Dimensions ø × H
Colour
intrinsically safe
EEx ia IIB T5
typ. 40µA (quiescent)
0°C to +50°C
10 – 93% (no condensation)
Am241, 0.5µCi (18.5kBq)
103 × 42 (mm)
cream
Weight
104g
Approval
BASEEFA03ATEX0156X
VdS G296051
Order number
Order name
240015
IS Ionisation Smoke Detector/Conv./100/SS 1151EIS
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
1151EIS_DBL_LST_EN_0804.PDF • PAGE 1
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
Download from Www.Somanuals.com. All Manuals Search And Download.
|