LG Electronics Air Conditioner 230 208V User Manual

LG  
LG Room  
Air Conditioner  
SERVICE MANUAL  
CAUTION  
• BEFORE SERVICING THE UNIT, READ THE SAFETY  
PRECAUTIONS IN THIS MANUAL.  
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.1 SPECIFICATIONS  
Cooling / Electric Heater  
Electric Heat  
(Btu/h)  
Electric Heat  
Amps(A)  
Min Circuit  
Model Name  
Cooling(Btu/h)  
Cooling Watts(W)  
1055/1025  
EER  
Protection (Amps)  
LP120CEM  
11800/11500  
11.2/11.2  
-
-
20  
Cooling / Heat Pump / Electric  
Cooling  
Model Name Cooling(Btu/h)  
Watts(W)  
Electric Cycle  
Heat (Btu/h)  
Electric Heat Electric Heat  
Min Circuit  
EER  
COP  
(Btu/h)  
Amps(A)  
3.2/3.5  
4.4/4.8  
Protection (Amps)  
LP090HEM  
9300/9000  
800/775  
11.6/11.6  
11.1/11.1  
8200/8000  
3.4/3.4  
3.3/3.3  
11900/9900  
11900/9900  
20  
20  
LP120HEM 12100/11800  
1090/1065  
10900/10700  
LP 12 0 C M 2  
12 34 5 6 7 8  
Digits 1,2 - LG Packaged Terminal Air Conditioner  
Digits 3,4 - Unit Cooling Capacity  
07 = 7,000 Btu/h  
Digit 6 - Product Type  
C = Air Conditoner  
H = Heat Pump  
09 = 9,000 Btu/h  
Digit 7- Control Type  
12 = 12,000 Btu/h  
M = Mechanical Control  
15 = 15,000 Btu/h  
Digit 5 - Serial No.  
Digit 8 - Electric Heating Capacity  
2 = 2.0 kW  
3 = 3.5 kW  
5 = 5.0 kW  
—3—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.2 features  
Unit Features  
The PTAC has many features, some of which are different than those found on conventional PTAC units. The servicer must be  
familiar with these features in order to  
properly service the unit.  
• Highly featured Micom controls using IIR (infinite impulse response)  
IIR function can make Micom controls maximize and keep the comfort conditions to sense the small changes in temperature  
per second.  
• Compressor Restart delay  
This feature extends the overall life of compressor by preventing the short-cycling of the air-conditioner. When the  
compressor restarts, LG PTAC is designed to give a minimum of three minutes to have a time of equalizing the refrigerant  
pressures for optimizing cycling.  
• Fan-Only Setting - High/Low  
The unit provides the function of selecting the either High or Low speed for Fan-Only operation.  
• Indoor Fan Speed Selections - High/Low  
The unit is operated in High-Heat or Low-Heat or High Cool or Low Cool.  
• Two Fan motors  
The unit has two fan motors to provide the occupants with the quiet environment to enjoy the peaceful life and maximum  
operating efficiency.  
• LED Diagnostics  
All units have this feature indicating the problem when the unit is not operating properly with easy -to-read diagnostics. For  
example, 1 blink every 2 seconds indicates the compressor failure.  
• Indoor Filters  
The unit uses the two indoor filters easily slide in and out. The filters may be cleaned by washing and brushing without  
removing the front grille.  
• Rotary Compressor  
The unit uses the rotary compressor for the quiet, reliable operation and prolong life.  
• 2 Position Discharge Grille  
The discharge grille can provide air flows upward at an angle of 40 off vertical or 80 15 degree off vertical. An angle is  
changed by removing the front grille and 4screws that fasten the discharge grille to the front grille to rotate an alternate  
position of the louvers.  
• Indoor Room Freeze Protection  
When the unit senses the room temperature falls to 40˚F below, the unit activates the fan motor and either the electric  
resistance heater or the hydronic heater to prevent pipes or fixtures from freezing. This also overrides front desk control of the  
unit mounted or wall mounted controls.  
• Door Switch/Occupancy Sensor  
The unit is capable of accommodating a field installed door switch and occupancy sensor to operate the energy management  
feature. For additional information, refer to the Unit Operation section.  
• Compressor Overload Protection  
This feature prevents the damage of the compressor by sensing the indoor tube temperature in heating. If the indoor  
temperature is over 130˚F, the outdoor fan will be switched off and on below 120˚F.  
—4—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
• Outdoor Air Temperature Switchover  
The unit is designed to control the electric heater interfacing with the outdoor temperature. When the outdoor temperature falls  
to 20˚F below, it makes the compressor be off and the electric heater be turned on until the outdoor temperature is above  
25˚F. This will effectively change the Unit from heat pump mode to total electric resistance heat.  
• Temperature limits  
The unit is programmed to provide both heating and cooling temperature limits by dip switches on control panel from 50˚F to  
90˚F. Temperature limits help to prevent overheating and overcooling for reducing the energy costs.  
• Condensate Drain Valve  
The unit has the condensate drain valve that prevents water from freezing in basepan.  
• Quick Heater Recovery  
The unit is designed to operate the electric heater to warm the room to the temperature set point as soon as heat pump cycle  
is on in heating. This feature has an advantage of reducing the time to reach the set point and improving the temperature  
increase for better comfort.  
• Reverse Cycle Defrosting - (PTHDs only)  
The unit will activate the reverse cycle defrost When the outdoor coil temperature has remained at a cold temperature to form  
the ice on the coil.This ice will reduce airflow though the coil and will also reduce the efficiency of unit. The LG PTHP will  
employ an active reverse cycle defrost function to melt the ice off the outdoor coil for insuring room comfort conditions and  
savings from extended operation.  
• High Temperature Heat Pump Operation Protection  
The compressor will be switched off to prevent damage when the heat pump is operated in high outdoor temperatures.  
• Remote Thermostat Control  
Each unit is built to be operated from any standard 4 or 5 wire remote-mounted thermostat, if desired. The unit has a built-in  
low voltage power source which can accommodate a large variety of thermostat choices-manual, auto changeover or  
programmable. A remote thermostat can also be added to any installed unit.  
• Zone Sensor  
Occupants enjoy ultimate comfort with consistent climate control. Attach an optional, inexpensive remote Zone Sensor, to  
exactly match the functions of the PTAC without disabling any features.  
—5—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.3 CONTROL LOCATIONS  
• OPERATION  
ELECTRIC HEATING MODEL  
COOLING ONLY MODEL  
TEMPERATURE CONTROL  
OPERATION MODE SELECTOR  
OFF: Turns air conditioner off.  
Set the Thermostat control to the desired temperature  
mark 5 (the mid-point is a good starting position). If the  
room temperature is not satisfactory after a reasonable  
time, adjust the control to a cooler or warmer setting, as  
appropriate.  
LOW FAN: Low speed fan operation without cooling.  
HIGH FAN: High speed fan operation without cooling.  
LOW COOL: Cooling with the low speed fan operation.  
HIGH COOL: Cooling with the high speed fan operation.  
LOW HEAT: Heating with the low speed fan operation.  
HIGH HEAT: Heating with the high speed fan operation.  
VENTILATION  
The ventilation lever is located to the lower left side of the unit.  
The ventilation lever must be in the CLOSE position in order  
to maintain the best cooling conditions.  
When fresh air is necessary in the room, set the ventilation  
lever to the OPEN position.  
VENT  
CLOSE  
The damper is opened and outdoor air is drawn into the room.  
This will reduce the cooling or heating efficiency.  
VENT  
OPEN  
CAUTION  
When the air conditioner has performed a cooling or  
heating operation and is turned off or set to the fan  
position, wait at least 3 minutes before resetting to the  
cooling operation.  
NOTE  
A slight heat odor may come from the unit when first  
switching to HEAT after the cooling season is over.  
This odor, caused by fine dust particles on the heater, will  
disappear quickly.  
This is harmless.  
—6—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.4 ADDITIONAL CONTROLS  
REMOVING THE FRONT GRILLE  
Additional controls are available after removing the front  
grille and option cover of control box.  
To remove the front grille, pull out the bottom of front  
grille and then lift up.  
To replace the front grille, place the tabs over the top of  
the unit and push the bottom of front grille until the clips  
snap into place.  
ADDITIONAL CONTROLS  
The additional controls are located behind the option cover of control box. The standard settings will be in the OFF position.  
The authorized service man has to check switches and ensure the switches are in the desired position.  
REMOTE ON ON ON ON  
ON  
OFF  
LOCAL  
1
OFF OFF OFF OFF  
2 3 4 5  
Remote/Local  
Energy Saver  
Temperature Limit 1  
Temperature Limit 2  
Temperature Limit 3  
TEMPERATURE LIMITING  
Temperature Limiting can save money by limiting the lowest temperature for cooling and the highest temperature for heating.  
The temperature limiting is controlled by dip switch #1 - #3.  
This temperature limiting is not available with the Remote Wall Thermostat.  
Cooling Operation  
Heating Operation  
Temperature Temperature Temperature  
Limit #1  
OFF  
ON  
Limit #2  
OFF  
OFF  
ON  
Limit #3  
OFF  
OFF  
OFF  
OFF  
ON  
Lowest Temp.  
Highest Temp.  
86°F (30.0°C)  
Lowest Temp.  
Highest Temp.  
86°F (30.0°C)  
54°F (12.2°C)  
56°F (13.3°C)  
58°F (14.4°C)  
60°F (15.5°C)  
62°F (16.6°C)  
64°F (17.7°C)  
66°F (18.9°C)  
68°F (20.0°C)  
54°F (12.2°C)  
54°F (12.2°C)  
54°F (12.2°C)  
54°F (12.2°C)  
54°F (12.2°C)  
54°F (12.2°C)  
54°F (12.2°C)  
54°F (12.2°C)  
86°F (30.0°C)  
86°F (30.0°C)  
86°F (30.0°C)  
86°F (30.0°C)  
86°F (30.0°C)  
86°F (30.0°C)  
86°F (30.0°C)  
84°F (28.9°C)  
82°F (27.8°C)  
80°F (26.7°C)  
78°F (25.5°C)  
76°F (24.4°C)  
74°F (23.3°C)  
72°F (22.2°C)  
OFF  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
—7—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMOTE/LOCAL CONTROL  
When remote/local switch #1 is on, it allow the unit to operate by the control of Remote Wall Thermostat.  
The unit control by knobs are not available.  
ENERGY SAVER  
The energy saver switch #2 is on. This switch is set at continuous fan to provide continuous fan operation in cool or heat  
modes. When the switch is off the continuous fan allows continuous circulation of room air and make the more balanced  
temperature of the room. When the switch is on the fan is on or off with the compressor or with the heater.  
FRONT DESK CONTROL  
When the pair wire is connected to the connector LOand LI, the unit can be turned ON or OFF with a switch located at the  
Front Desk Control panel. When the front desk switch is ON, the fan operate according to the condition of setting without  
working compressor and heater. When the front desk switch is OFF, the unit can operate according to the setting of controls.  
Wire # AWG  
#22  
Maximum Length  
600ft(180m)  
900ft(270m)  
1500ft(450m)  
2000ft(610m)  
Note: The following figures show wiring  
schematics for heat pump and straight cool  
units with electric heat, respectively.  
#20  
#18  
#16  
Wiring Schematic for  
Remote Heat Pump  
LO LI GL GH  
O
W
Y
R
C
Front Desk Switch  
REMOTE WALL THERMOSTAT  
When the wires are connected, the unit will be controlled by a remote wall  
thermostat.  
The thermostat connections supply the 24 Volt AC. When you install the  
digital / electronic thermostat, you must set it to the 24 Volt AC. See the  
installation Instruction in this manual for the Remote Wall Thermostat.  
Wiring Schematic for  
Straight Cool Unit.  
24 Volt-N  
24 Volt-L  
Compressor  
Heater  
Reversing Valve  
High Fan  
Low Fan  
LO LI GL GH  
O
W
Y
R
C
—8—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. DISASSEMBLY INSTRUCTIONS  
— Before the following disassembly, POWER SWITCH is set to OFF and disconnected the power cord.  
2.1 MECHANICAL PARTS  
2.1.1 FRONT GRILLE  
1. Remove the front grille. (See Fig. 1)  
2. To remove the front grille, pull out the bottom of  
the front grille and then lift up.  
Re-install the component by referring to the  
removal procedure.  
3. To replace the front grille, place the tabs over the  
top of the unit and push the bottom of front grille  
until the clips snap into place.  
Figure 1  
• This Room Air Conditioner (PTAC) discharges air  
from the top of the unit through reversible, 2-position  
discharge grille louvers. The unit is shipped from the  
factory with the discharge grille louvers at an angle  
of 40˚ off vertical. In an alternate position the louvers  
will be at an angle of 15˚ off vertical.  
40˚  
15˚  
To adjust air direction, remove the front grille.  
Remove the 4 screws that fasten the discharge grille  
to the front grille.  
Screws  
Flip the discharge grille 180°, then reattach the  
discharge grille to the front grille with 4 screws.  
—9—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.1.2 CONTROL BOX (Half-Disassembly)  
1. Remove the front grille. (Refer to section 2.1.1)  
2. Remove the three screw which fasten the control  
box. (See Fig. 2)  
3. Pull the control box from the barrier. (See Fig.2)  
4. Discharge the capacitor by placing a 20,000 ohm  
resistor across the capacitor terminals.  
5. Disconnect three wire housings in the control box.  
6. Pull the control box forward completely.  
7. Re-install the components by referring to the  
removal procedure. (See Fig. 2)  
(Refer to the circuit diagram found on page 25 in  
this manual and on the control box.)  
Figure 2  
2.1.3 CONTROL BOX (Full-Disassembly)  
1. Remove the front grille. (Refer to section 2.1.1)  
2. Remove the 4 screws which fasten the control box  
cover. (See Fig.3)  
3. Disconnect three wire housings in the control box.  
4. Remove three screws which fasten the control box  
assembly.  
5. Pull the control box assembly out from the unit.  
Figure 3  
—10—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.2 AIR HANDLING PARTS  
2.2.1 HEATER ASSEMBLY AND CROSS  
FLOW FAN  
1. Remove the front grille. (Refer to section 2.1.1)  
2. Remove the control box assembly.  
(Refer to section 2.1.3)  
3. Remove the 3 screws which fasten the net steel.  
(See Fig. 4)  
4. Remove the 3 screws which fasten the electric  
heater assembly. (Electric heater model only)  
(See Fig.4).  
Figure 4  
5. Loosen the hexagon screw with the Hex-wrench  
(See Fig.5)  
Figure 5  
6. Remove the 4 screws which fasten the indoor  
motor and the earth wire. (See Fig. 5. 6)  
7. Re-install the components by referring to the  
removal procedure, above.  
2.2.2 FAN  
1. Remove the brace.  
Figure 6  
2. Remove the 4 screws which fasten the condenser  
with the shroud and the basepan.  
3. Move the condenser sideways carefully.  
4. Remove the clamp which secures the fan with  
pliers.  
5. Remove the fan. (See Fig. 7)  
6. Re-install the components by referring to the  
removal procedure, above.  
Figure 7  
—11—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.2.3 SHROUD  
1. Remove the fan. (Refer to section 2.2.2)  
2. Remove the screw which fastens the shroud.  
3. Remove the shroud. (See Fig. 8)  
4. Re-install the component by referring to the  
removal procedure, above.  
2.3 ELECTRICAL PARTS  
2.3.1 OUTDOOR MOTOR  
1. Remove the clamp cord and disconnect a wire  
housing in control box. (Refer to section 2.1.2)  
2. Remove the fan. (Refer to section 2.2.2)  
3. Remove the 2 screws which fasten the motor.  
(See Fig. 9)  
Figure 8  
4. Remove the motor.  
5. Re-install the components by referring to the  
removal procedure, above.  
2.3.2 INDOOR MOTOR (Refer to section 2.2.1)  
2.3.3 COMPRESSOR  
1. Discharge the refrigerant system using FreonTM  
Recovery System.  
Figure 9  
If there is no valve to attach the recovery system,  
install one (such as a WATCO A-1) before venting  
the FreonTM . Leave the valve in place after  
servicing the system.  
2. Disconnect the 3 leads from the compressor.  
3. After purging the unit completely, unbraze the  
suction and discharge tubes at the compressor  
connections.  
4. Remove the 3 nuts and the 3 washers which  
fasten the compressor. (See Fig. 10)  
5. Remove the compressor.  
6. Re-instill the components by referring to the  
removal procedure, above.  
Figure 10  
2.3.4 CAPACITOR  
1. Remove the control box. (Refer to section 2.1.2)  
2. Remove 1 screw and disconnect the leads which  
connected to the box type capacitor.  
(See Fig. 11)  
3. Remove 1 screw and the clamp which fastens the  
can-type capacitor. (See Fig. 11)  
4. Disconnect all the leads of capacitor terminals.  
5. Re-install the components by referring to the  
removal procedure, above.  
Figure 11  
—12—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.3.5 POWER CORD  
1. Remove the control box. (Refer to section 2.1.2)  
2. Disconnect the grounding screw from the control  
box.  
3. Disconnect 2 receptacles.  
4. Remove a screw which fastens the clip cord.  
5. Separate the power cord from the control box.  
(See Fig. 12)  
6. Re-install the component by referring to the  
removal procedure, above.  
(Use only one ground-marked hole  
connection.)  
for ground  
7. If the supply cord of this appliance is damaged, it  
must be replaced by the special cord.  
(The special cord means the cord which has the  
same specification marked on the supply cord  
fitted to the unit.)  
Figure 12  
2.3.6 P.C.B.  
1. Remove the escutcheon.  
2. Remove the two knobs.  
3. Remove the 2 screws which fasten P.C.B. cover.  
4. Disconnect all the leads which connected to the  
P.C.B.  
5. Remove the two screws which fasten the P.C.B.  
board.  
6. Re-install the components by referring to the  
removal procedure, above.  
Figure 13  
—13—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.4 REFRIGERATION CYCLE  
CAUTION  
TM  
Discharge the refrigerant system using Freon  
Recovery System.  
If there is no valve to attach the recovery system,  
install one (such as a WATCO A-1) before  
TM  
venting the Freon . Leave the valve in place  
after servicing the system.  
2.4.1 CONDENSER  
1. Remove the brace and the shroud.  
(Refer to section 2.2.2)  
2. Remove the 4 screws which fasten the shroud.  
(Refer to section 2.2.2)  
Figure 14  
3. Push forward the shroud and remove the 2 screws  
which fasten the condenser with the basepan.  
4. After discharging the refrigerant completely,  
unbraze the interconnecting tube at the condenser  
connections.  
5. Remove the condenser.  
6. Re-install the components by referring to notes.  
(See Fig. 14)  
2.4.2 EVAPORATOR  
1. Remove the front grille. (Refer to section 2.1.1)  
2. Discharge the refrigerant completely.  
3. Remove the control box assembly.  
(Refer to section 2.1.2)  
Figure 15  
4. Remove the 4 screws which fasten the evaporator  
at the left side and the right side.  
5. Move the evaporator sideward carefully and then  
unbraze the interconnecting tube at the evaporator  
connectors.  
6. Remove the evaporator.  
7. Re-install the components by referring to notes.  
(See Fig. 15)  
2.4.3 CAPILLARY TUBE  
1. After discharging the refrigerant completely,  
unbraze the interconnecting tube at the capillary  
tube.  
2. Remove the capillary tube.  
3. Re-install the components by referring to notes.  
—14—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
— Replacement of the refrigeration cycle.  
1. When replacing the refrigeration cycle, be sure to  
discharge the refrigerant system using a FreonTM  
recovery System.  
6. Recharge as follows :  
1) Refrigeration cycle systems are charged from the  
High-side. If the total charge cannot be put  
in the High-side, the balance will be put in the  
suction line through the access valve which you  
installed as the system was opened.  
2) Connect the charging cylinder as shown in Fig. 16B.  
With valve C open, discharge the hose at the  
manifold connection.  
3) Open valve A and allow the proper charge to  
enter the system. Valve B is still closed.  
4) If more charge is required, the high-side will not  
take it. Close valve A.  
5) With the unit running, open valve B and add the  
balance of the charge.  
a. Do not add the liquid refrigerant to the Low-  
side.  
b. Watch the Low-side gauge; allow pressure to  
rise to 30 lbs.  
c. Turn off valve B and allow pressure to drop.  
d. Repeat steps B and C until the balance of the  
charge is in the system.  
If there is no valve to attach the recovery system,  
install one (such as a WATCO A-1) before venting  
the FreonTM. Leave the valve in place after  
servicing the system.  
2. After discharging the unit completely, remove the  
desired component, and unbraze the pinch-off  
tubes.  
3. Solder service valves into the pinch-off tube ports,  
leaving the valves open.  
4. Solder the pinch-off tubes with Service valves.  
5. Evacuate as follows.  
1) Connect the vacuum pump, as illustrated Fig.  
16A.  
2) Start the vacuum pump, slowly open manifold  
valves A and B with two full turns  
counterclockwise and leave the valves closed.  
The vacuum pump is now pulling through valves  
A and B up to valve C by means of the manifold  
and entire system.  
6) When satisfied the unit is operating correctly,  
use the pinch-off tool with the unit still running  
and clamp on to the pinch-off tube. Using a tube  
cutter, cut the pinch-off tube about 2 inches from  
the pinch-off tool. Use sil-fos solder and solder  
pinch-off tube closed. Turn off the unit, allow it to  
set for a while, and then test the leakage of the  
pinch-off connection.  
CAUTION  
If high vacuum equipment is used, just crack  
valves A and B for a few minutes, then open  
slowly with the two full turns counterclockwise.  
This will keep oil from foaming and being  
drawn into the vacuum pump.  
3) Operate the vacuum pump for 20 to 30 minutes,  
until 600 microns of vacuum is obtained. Close  
valves A and B, and observe vacuum gauge for  
a few minutes. A rise in pressure would  
indicate a possible leak or moisture remaining in  
the system. With valves A and B closed, stop  
the vacuum pump.  
4) Remove the hose from the vacuum pump and  
place it on the charging cylinder. See Fig. 16B.  
Open valve C.  
Discharge the line at the manifold connection.  
5) The system is now ready for final charging.  
—15—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pinch-off tool  
capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service  
valve.  
COMPOUND GAUGE  
CONDENSER  
(HIGH PRESSURE SIDE)  
MANIFOLD  
GAUGE  
A
B
CAPILLARY TUBE  
SEE INSETS  
BELOW  
EVAPORATOR  
(LOW PRESSURE SIDE)  
COMPRESSOR  
HI  
LOW  
A
B
A
B
EXTERNAL  
VACUUM PUMP  
CHARGING  
CYLINDER  
C
Figure 16A-Pulling Vacuum  
Figure 16B-Charging  
—16—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimension of air conditioner  
3. INSTALLATION  
3.1 HOW TO INSTALL THE UNIT  
1,066mm(42")  
CAUTION  
• There are sharp edges that can cause serious cuts.  
• When lifting the air conditioner, it is HEAVY.  
Use 2 peoples to lift.  
406mm  
(16")  
For existing sleeve, you should measure the wall sleeve  
dimensions.  
You can install the new air conditioner according to these  
installation instructions to achieve the best performence. All  
wall sleeves used to mount the new air conditioner must be in  
good structural condition and have the rear grille that securely  
attaches to the sleeve or the flange of the sleeve to secure the  
new air conditioner.  
318mm  
(12 1/2")  
505mm  
(20")  
Dimension of sleeve assembly (optional)  
• To avoid vibration and noise, make sure the unit is installed  
securely and firmly.  
1066mm  
(42")  
406mm  
(16")  
318mm  
(12 1/2")  
A. BEFORE ATTACHING THE FRONT  
GRILLE TO THE SLEEVE, IF YOU WANT  
TO PULL OUT THE FILTER UPWARD;  
1. There should be no obstacle, like a fence, within 20" which  
might restrict heat radiation from the condenser.  
INSULATION  
SLEEVE  
WALL  
WALL  
COOLED  
HEAT  
RADIATION  
AIR  
INTAKE  
AIR  
1/4" Bubble  
of the level  
B. IF YOU WANT TO PULL OUT THE FILTER  
DOWNWARD;  
Over 20"  
The grille is already designed for that way.  
1. Install the unit a little obliquely outward not to leak the  
condensed water into the room (about 1/2" or 1/4" bubble  
with level).  
1/4" Bubble  
2. Install the unit with its bottom portion 30~60" above the floor  
level.  
3. The power cord must be connected to an independent  
circuit. The green wire must be grounded.  
Level  
—17—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2 SUGGESTED TOOL REQUIREMENTS  
SCREWDRIVER(+, -), RULER, KNIFE, HAMMER, PENCIL, LEVEL  
3.2.1 PREPARATION OF SLEEVE  
12  
14  
SLEEVE HARDWARE  
R
NUMBER  
NAME OF PARTS  
SLEEVE LOWER  
SLEEVE UPPER  
SCREW  
Q’TY  
1
1
1
4
1
1
OUTDOOR GRILLE  
DRAIN KIT  
ASSEMBLE THE WALL SLEEVE  
• Raise the sleeve side panels to upright position as shown on  
the right.  
R
O
O
D
N
I
• Place sleeve upper on top of side panels.  
• Fasten the four screws as shown on the right.  
INDOOR  
R
O
O
D
I N  
• Assemble drain kit.  
• Fasten this assembly to the each side of the wall sleeve as  
shown on the right.  
I
N
D
O
O
R
• Assemble the outdoor grille and fasten the 4 screws as  
shown on the right.  
R
O
O
D
N
I
3.2.2 PREPARATION OF THE FRONT GRILLE  
Carefully remove shipping tape, if there is any, from the front  
grille.  
Shipping tape  
—18—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.3 UNIT INSTALLATION  
1. Remove the shipping screw from the ventilation door.  
(See Fig. 17)  
Figure 17  
2. Remove the front gille by pulling it out at the bottom to  
release it, then lift it up along the unit top front.  
(See Fig. 18)  
Figure 18  
3. Slide the unit into the wall sleeve and secure with 6 screws  
through the unit flange holes. (See Fig. 19)  
Figure 19  
4. Reinstall the front grille by hooking the top over the unit top,  
then pushing it in at the bottom. (See Fig. 20)  
Figure 20  
—19—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.3 ELECTRICAL REQUIREMENTS  
3.3.1 ELECTRICAL DATA (FOR 230/208V MODEL)  
CAUTION  
1. Do not use an extension cord with this unit.  
2. When the unit is in the OFF position, the power supply to the  
electrical controls.  
Tandem  
15 A  
3. Disconnect the power to the unit before servicing  
the unit.  
4. Remove the power cord from the wall receptacle.  
5. Remove or turn off the protective device (fuses or circuit breaker).  
Perpendicular  
20 A  
Wirings including installation of the receptacle must comply with the  
NEC and local codes, local regulations.  
Large Tandem  
30 A  
FUSE- Use a time-delay fuse or circuit breaker. Refer to the nameplate  
for proper power supply requirements.  
230/208 volt receptacle configuration  
3.3.2 ELECTRICAL SAFETY  
IMPORTANT GROUNDING INSTRUCTIONS  
Air conditioner has a three-prong grounding plug on its power supply cord, which must be plugged into properly grounded  
three-prong wall receptacle for your protection against possible shock hazard.  
FUSE Use a time-delay fuse or circuit breaker. Refer to the nameplate for proper power supply requirements.  
208, 230, and 208/230 VOLT UNITS  
These units are equipped with a three-prong grounding plug on the power supply cord, which must be plugged into a matching  
properly grounded three-prong wall receptacle for your protection against possible shock hazard. If such an outlet is not  
present, one must be installed by a qualified electrician in accordance with the National Electrical Code and local codes and  
ordinances.  
NOTE: DO NOT USE AN EXTENSION CORD on 208, 230, and 208/230 Volt units.  
—20—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. PERFORMANCE DATA  
Air Conditioner Performance Data  
LP120CEM  
Voltage (V)  
208 230  
208  
230  
Cooling Data  
Cooling Capacity  
(Btu/h)  
11,500  
4.8  
11,800  
Cooling Amps (A)  
Cooling Power (W)  
EER (Btuh/Watt)  
5.2  
1055  
11.0  
1025  
11.0  
Moisture Removal  
(Pts/h)  
3.3  
3.3  
Airflow  
Indoor CFM (Wet)  
@0.3ESP (Hi)  
300  
290  
320  
280  
330  
290  
350  
310  
Indoor CFM (Wet)  
@0.3ESP (Lo)  
Indoor CFM (Dry)  
@0.3ESP (Hi)  
Indoor CFM (Dry)  
@0.3ESP (Lo)  
Heat Pump Performance Data  
LP120HEM  
208 230  
LP090HEM  
208  
Voltage (V)  
208 230  
230  
Cooling Data  
Cooling Capacity (Btu/h)  
Cooling Amps (A)  
Cooling Power (W)  
EER (Btuh/Watt)  
Moisture Removal (Pts/h)  
Heat Pump Heating Data  
Heating Capacity (Btu/h)  
Heating Amps (A)  
Heating Power (W)  
COP (W/W)  
11,800  
5.4  
12,100  
5.0  
9,000  
3.9  
9,300  
3.7  
1,065  
11.1  
3.3  
1,090  
11.1  
3.3  
775  
11.6  
3.4  
800  
11.6  
3.4  
10,700  
4.8  
10,900  
4.4  
8,000  
3.5  
8,200  
3.2  
950  
970  
690  
3.4  
705  
3.4  
3.3  
3.3  
Airflow  
Indoor CFM (Wet)  
@0.3ESP (Hi)  
240  
190  
260  
270  
230  
290  
310  
270  
330  
340  
300  
360  
Indoor CFM (Wet)  
@0.3ESP (Lo)  
Indoor CFM (Dry)  
@0.3ESP (Hi)  
Indoor CFM (Dry)  
@0.3ESP (Lo)  
220  
250  
290  
330  
—21—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Cooling Wattage - Air Conditioners  
Model  
LP120CEM  
Temperature  
Outdoor  
Air  
Dry Bulb  
Return Air  
Wet Bulb  
Total Wattage  
Input  
Min  
Max  
Rating Wattage  
1045  
1090  
85  
80  
75  
70  
65  
60  
55  
85  
80  
75  
70  
65  
60  
55  
85  
80  
75  
70  
65  
60  
55  
85  
80  
75  
70  
65  
60  
55  
85  
80  
75  
70  
65  
60  
55  
1050  
1055  
1060  
1055  
1050  
1045  
1030  
1000  
1005  
1005  
1005  
1000  
990  
980  
950  
950  
955  
950  
950  
940  
930  
895  
900  
905  
900  
895  
890  
880  
850  
850  
850  
850  
850  
940  
830  
1180  
1180  
1180  
1180  
1180  
1175  
1160  
1125  
1130  
1135  
1130  
1125  
1120  
1105  
1070  
1075  
1080  
1075  
1070  
1060  
1055  
1020  
1020  
1030  
1020  
1020  
1010  
1000  
970  
100  
95  
90  
85  
80  
970  
975  
970  
970  
960  
950  
—22—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Cooling Wattage - Heat Pumps  
Model  
LP090HM*  
LP120HEM  
Temperature  
Outdoor  
Air  
Return Air  
Total Wattage  
Input  
Total Wattage  
Input  
Dry Bulb Wet Bulb  
Min  
Max  
Min  
Max  
Rating Wattage  
810  
850  
1120  
1145  
85  
80  
75  
830  
835  
835  
835  
830  
820  
810  
785  
790  
795  
790  
785  
780  
770  
745  
750  
750  
750  
745  
735  
720  
700  
705  
705  
705  
700  
690  
680  
655  
660  
660  
660  
655  
650  
635  
935  
940  
940  
940  
935  
925  
915  
890  
890  
890  
890  
890  
880  
865  
845  
850  
850  
850  
845  
835  
825  
800  
800  
810  
800  
800  
790  
775  
755  
760  
760  
760  
755  
745  
735  
1120  
1125  
1130  
1125  
1120  
1115  
1100  
1070  
1075  
1075  
1075  
1070  
1060  
1050  
1020  
1025  
1025  
1025  
1020  
1010  
1000  
970  
975  
975  
975  
970  
960  
950  
920  
925  
925  
920  
920  
910  
1230  
1235  
1240  
1240  
1230  
1230  
1210  
1180  
1190  
1190  
1190  
1180  
1170  
1160  
1130  
1135  
1135  
1125  
1130  
1120  
1110  
1080  
1085  
1085  
1085  
1080  
1070  
1060  
1030  
1030  
1035  
1030  
1030  
1020  
1010  
100  
70  
65  
60  
55  
85  
80  
75  
70  
65  
60  
55  
85  
80  
75  
70  
65  
60  
55  
85  
80  
75  
70  
65  
60  
55  
85  
80  
75  
70  
65  
60  
55  
95  
90  
85  
80  
900  
—23—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Cooling change of temperature - Air Conditioners  
Room Air Room Air  
LP120CEM  
Dry  
Bulb  
Wet  
Bulb  
Temperature Across  
Indoor Coil (T)  
Min  
Max  
Rating Btu/h  
Rating CFM  
11700  
300  
12000  
330  
85  
80  
75  
70  
80  
75  
70  
65  
75  
70  
65  
60  
70  
65  
60  
55  
65  
60  
55  
1
9
5
13  
22  
30  
10  
18  
25  
33  
13  
20  
26  
33  
15  
20  
25  
30  
13  
17  
21  
90  
85  
80  
18  
26  
5
13  
21  
29  
9
15  
23  
29  
10  
15  
21  
26  
9
75  
70  
13  
18  
Cooling Change of Temperature - Heat Pumps  
Model  
Room Air Room Air  
LP090HEM  
LP120HEM  
Dry  
Bulb  
Wet  
Bulb  
Temperature Across  
Indoor Coil (T)  
Temperature Across  
Indoor Coil (T)  
Min  
Max  
Min  
Max  
Rating Btu/h  
Rating CFM  
9300  
240  
9600  
270  
12300  
310  
12600  
340  
85  
80  
75  
70  
80  
75  
70  
65  
75  
70  
65  
60  
70  
65  
60  
55  
65  
60  
55  
2
6
1
5
11  
19  
29  
7
15  
22  
30  
11  
18  
25  
33  
15  
20  
27  
33  
16  
21  
26  
31  
15  
18  
22  
10  
18  
26  
5
13  
22  
30  
10  
18  
25  
33  
13  
20  
26  
33  
15  
20  
25  
30  
13  
17  
21  
90  
85  
80  
15  
23  
31  
11  
18  
24  
32  
13  
18  
23  
29  
12  
16  
20  
14  
21  
30  
10  
16  
23  
30  
11  
16  
21  
26  
10  
14  
18  
75  
70  
—24—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Heating Change of Temperature - Heat Pumps  
Model  
Room Air Room Air  
LP090HEM  
LP120HEM  
Dry  
Bulb  
Wet  
Bulb  
Temperature Across  
Indoor Coil (T)  
Temperature Across  
Indoor Coil (T)  
Min  
Max  
Min  
Max  
Rating Btu/h  
Rating CFM  
8200  
260  
8400  
290  
10900  
330  
11200  
360  
85  
80  
75  
70  
65  
85  
80  
75  
70  
65  
85  
80  
75  
70  
65  
85  
80  
75  
70  
65  
24  
25  
26  
28  
28  
22  
23  
24  
24  
25  
20  
21  
22  
23  
24  
17  
18  
19  
20  
21  
27  
28  
29  
30  
30  
24  
25  
26  
27  
28  
22  
23  
24  
24  
25  
20  
21  
22  
23  
24  
27  
28  
29  
31  
31  
24  
25  
26  
27  
28  
23  
23  
24  
25  
26  
21  
22  
23  
23  
24  
30  
31  
32  
34  
34  
29  
29  
30  
31  
32  
27  
28  
29  
29  
30  
24  
25  
26  
27  
28  
50  
45  
40  
35  
Cooling Ampere Chart - Air Conditioners  
Cond Inlet Air  
Temperature  
Model  
LP120CEM  
Amperage  
Min Max  
4.8 5.2  
Rating Ampere  
100  
95  
90  
85  
80  
5.6 5.6  
5.4 5.3  
5.2 5.1  
4.9 4.8  
4.7 4.6  
Cooling Ampere Chart - Heat Pumps  
Cond Inlet Air  
Temperature  
Model  
LP090HM*  
Amperage  
Min Max  
3.6 3.9  
3.4 4.0  
3.2 3.8  
3.1 3.6  
3.1 3.4  
2.9 3.3  
Model  
LP120HEM  
Amperage  
Min Max  
4.8 5.2  
5.6 5.5  
5.3 5.2  
5.0 5.0  
4.8 4.7  
4.6 4.5  
Rating Ampere  
100  
95  
90  
85  
80  
—25—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. TROUBLESHOOTING GUIDE  
5.1 OUTSIDE DIMENSIONS  
1,066mm(42")  
505mm(20")  
5.2 PIPING SYSTEM  
Following is a brief description of the important components and their functions in the refrigeration system.  
Refer to Fig. 21 to follow the refrigeration cycle and the flow of the refrigerant in the cooling cycle.  
ROOM AIR CONDITIONER  
CYCLE OF REFRIGERATION  
EVAPORATOR COILS  
CONDENSER COILS  
VAPOR INLET  
SUCTION LIME  
COOL LOW PRESSURE VAPOR  
HOT  
DISCHARGED  
AIR  
COMPLETE LIQUID  
BOIL OFF POINT  
COOLED  
AIR  
ROOM AIR HEAT LOAD  
OUTSIDE COOLING  
AIR FOR REFRIGERANT  
PASS THROUGH  
MOTOR  
COMPRESSOR  
OIL  
LIQUID  
PRESSURE  
DROP  
LIQUID OUTLET  
HIGH PRESSURE VAPOR  
(LIQUID REFRIGERANT)  
LIQUID PEFRIGERANT  
CAPILLARY TUBE  
LOW PRESSURE VAPOR  
Figure 21  
—26—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.3 TROUBLESHOOTING GUIDE  
In general, possible trouble is classified in two causes.  
The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air  
Conditioning caused by a defect in the refrigeration circuit and improper application.  
Unit is running but cooling is ineffective  
Ineffective Cooling  
Check of cold air circulation  
for smooth flow.  
Check of outdoor coil  
(heat exchanger) & the fan  
operation.  
Check heat load increase.  
Unexpected residue  
Overloaded Circuit  
Dirty indoor coil  
(Heat exchanger)  
Check gas leakage.  
Repair gas leak.  
Malfunction of fan  
Check of inside gas  
pressure.  
Clogged of air filter  
Obstruction at air outlet  
Replacement of unit if the  
unit is beyond repair.  
Adjusting of refrigerant  
charge  
Correct above trouble  
Malfunction of compressor  
Replacement of  
compressor  
Check clogging in  
refrigeration circuit.  
Satisfactory operation with  
temperature difference of  
inlet & outlet air ; 44.6~50˚F  
Repair clogging in  
refrigeration circuit.  
—27—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fails to Start  
Check of power source.  
Check of circuit breaker  
and fuse.  
Check of control switch  
setting.  
Gas leakage of feeler bulb  
of thermostat  
Check of control switch.  
Only compressor fails to  
start.  
Only fan fails to start.  
Improper wiring.  
Drop of power voltage.  
Improper thermostat setting  
Defect of fan motor  
capacitor.  
Defect of compressor  
capacitor.  
Loose terminal connection.  
Improper wiring  
Irregular motor resistance  
(
).  
Irregular motor insulation  
).  
Check capacitor.  
Replacement.  
(
Replacement of fan motor  
Regular but fails to start  
Irregular motor resistance ( )  
Irregular motor insulation ( )  
Replacement of compressor  
(locking of rotor, metal)  
Replacement of compressor  
(Motor damaged)  
—28—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMPLAINT  
CAUSE  
REMEDY  
Fan motor will not run.  
No power  
Check voltage at outlet. Correct if none.  
Power supply cord  
Rotary switch  
Check voltage to rotary switch. If none, check  
power supply cord. Replace cord if circuit is open.  
Check switch continuity. Refer to wiring diagram  
for terminal identification. Replace switch if  
defective.  
Wire disconnected or  
connection loose  
Connect wire. Refer to wiring diagram for terminal  
identification. Repair or replace loose terminal.  
Capacitor (Discharge  
Test capacitor.  
capacitor before testing.)  
Replace if not within ±10% of manufacturer's  
rating. Replace if shorted, open, or damaged.  
Will not rotate  
Fan blade hitting shroud or cross flow fan hitting  
scroll. Realign assembly.  
Units using slinger ring condenser fans must  
have 1/4 to 5/16 inch clearance to the base. If it is  
hitting the base, shim up the bottom of the fan  
motor with mounting screw(s).  
Check fan motor bearings; if motor shaft will not  
rotate, replace the motor.  
Fan motor runs  
intermittently  
Revolves on overload.  
Check voltage. See limits on this page. If not within  
limits, call an electrician.  
Test capacitor.  
Check bearings. Does the fan blade rotate freely?  
If not, replace fan motor.  
Pay attention to any change from high speed to  
low speed. If the speed does not change, replace  
the motor.  
Fan motor noise.  
Grommets  
Fan  
Check grommets; if worn or missing, replace them.  
If cracked, out of balance, or partially missing,  
replace it.  
Turbo fan  
If cracked, out of balance, or partially missing,  
replace it.  
Loose set screw  
Worn bearings  
Tighten it.  
If knocking sounds continue when running or  
loose, replace the motor. If the motor hums or  
noise appears to be internal while running,  
replace motor.  
—29—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMPLAINT  
CAUSE  
REMEDY  
Compressor will not run,  
but fan motor runs.  
Voltage  
Wiring  
Check voltage. See the limits on the preceding.  
page. If not within limits, call an electrician.  
Check the wire connections, if loose, repair or  
replace the terminal. If wires are off, refer to wiring  
diagram for identification, and replace. Check wire  
locations. If not per wiring diagram, correct.  
Rotary  
Check for continuity, refer to the wiring diagram  
for terminal identification. Replace the switch if  
circuit is open.  
Thermostat  
Check the position of knob If not at the coldest  
setting, advance the knob to this setting and  
restart unit.  
Check continuity of the thermostat. Replace  
thermostat if circuit is open.  
Capacitor (Discharge  
capacitor before  
servicing.)  
Check the capacitor.  
Replace if not within ±10% of manufacturers  
rating. Replace if shorted, open, or damaged.  
Check the compressor for open circuit or  
ground. If open or grounded, replace the  
compressor.  
Compressor  
Overload  
Check the compressor overload, if externally  
mounted. Replace if open. (If the compressor  
temperature is high, remove the overload, cool it,  
and retest.)  
ROOM AIR CONDITIONER VOLTAGE LIMITS  
NAME PLATE RATING  
MINIMUM  
MAXIMUM  
208/230V  
187V  
253V  
—30—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMEDY  
COMPLAINT  
CAUSE  
Compressor cycles  
on overload.  
Voltage  
Check the voltage. See the limits on the preced-  
ing page. If not within limits, call an electrician.  
Overload  
Check overload, if externally mounted.  
Replace if open. (If the compressor temperature  
is high, remove the overload, cool, and retest.)  
Fan motor  
If not running, determine the cause. Replace if  
required.  
Condenser air flow  
restriction  
Remove the cabinet. inspect the interior surface  
of the condenser; if restricted, clean carefully  
with a vacuum cleaner (do not damage fins) or  
brush. Clean the interior base before  
reassembling.  
Condenser fins  
(damaged)  
If condenser fins are closed over a large area  
on the coil surface, head pressures will increase,  
causing the compressor to cycle. Straighten the  
fins or replace the coil.  
Capacitor  
Test capacitor.  
Wiring  
Refrigerating system  
Air filter  
Check the terminals. If loose, repair or replace.  
Check the system for a restriction.  
If restricted, clean of replace.  
Insufficient cooling or  
heating  
Exhaust damper door  
Unit undersized  
Close if open.  
Determine if the unit is properly sized for the area to  
be cooled.  
Excessive noise.  
Cross flow fan  
Copper tubing  
Check the set screw or clamp. If loose or missing,  
correct. If the blower or fan is hitting air guide,  
rearrange the air handling parts.  
Carefully rearrange tubing not to contact,  
compressor, shroud, and barrier.  
—31—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. SCHEMATIC DIAGRAM  
POWER INPUT  
WH(BL)  
BK(BR)  
(Ribbed)  
(Plain)  
HEATER ASSY  
GN(GN/YL)  
BI-METAL  
THERMOSTAT  
FUSE  
LINK  
HEATER  
BK  
BK  
BK  
BK  
RD  
BL  
RD  
BL  
TB-1  
TB-2  
WH  
WH  
5KW  
WH  
TB-3  
TB-4  
RD  
RD  
BK  
BK  
FOR E/HEATER MODEL  
BK  
RD RD  
OR(BR) OR(BR)  
YL YL  
OUTDOOR  
FAN  
MOTOR  
3
3
CN-ODF  
CN-ICR  
4
4
RY-HEAT2  
RY-HEAT1  
F
LOW  
FAN  
VR1  
CAPACITOR  
HIGH  
FAN  
C
CN-4WAY  
OFF  
LOW  
HEAT  
LOW  
COOL  
H
BK BK  
WARM  
COOL  
R
HIGH  
HEAT  
HIGH  
COOL  
SW1  
RD RD  
S
COMP  
CN-IDF  
BL BL  
BR  
C
IN  
IN  
COIL AIR  
O.L.P  
CN-EXT(L)  
CN-EXT(N)  
CN-L  
CN-N  
BK  
INDOOR PIPE  
THERMISTOR  
BL BL  
RD RD  
OR OR  
BR BR  
YL YL  
INDOOR AIR  
THERMISTOR  
INDOOR  
FAN  
RY-COMP  
MOTOR  
CN-COMP  
CN-EXT2  
CN-TRANS  
CAPACITOR  
GN(GN/YL)  
C
F
REMOTE  
THERMOSTAT  
EXTERNAL  
TRANS  
FDC  
P/NO:3854A20196A  
LOCATION  
NO.  
Q'TY  
PER SET  
DESCRIPTION  
REMARKS  
1
2
1
1
1
1
1
1
1
1
POWER CORD  
MOTOR  
INDOOR  
OUTDOOR  
BOX TYPE  
3
CAPACITOR  
CAN TYPE  
4
5
6
THERMOSTAT  
COMPRESSOR  
OVERLOAD PROTECTOR  
—32—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. EXPLODED VIEW  
C
552111  
552102  
552114  
552113  
35211A  
152302  
349600  
346810  
D
148000  
554030  
359011  
546811  
135515  
349600-1  
F
W48602  
559011  
354210  
149980  
130411  
135500  
753000  
135312  
E
152302  
A
B
238310  
268714 237200  
149410  
249951  
135510  
237204  
567502  
554160  
W0CZZ-1  
237200  
263230-2  
264110  
263230-1  
W6640  
W0CZZ-2  
550140  
147900  
—33—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. REPLACEMENT PARTS LIST  
PART NO.  
LP120CEM  
LOCATION  
DESCRIPTION  
REMARK  
NO  
.
LP090HEM  
LP120HEM  
A
249951 CONTROL BOX,ASM(INDOOR)  
264110 POWER CORD ASM  
268714 PCB ASM(MAIN)  
4995A20466U  
4995A20463W  
6411A20048M  
4995A20463U  
6871A10082J  
6871A10082C  
149410 KNOB ASM  
237200 PANEL ASM,CONTROL  
237204 PANEL,SIDE  
4941A30015B  
3720A20169A  
3720A20186A  
3831A30008A  
6323A20003K  
6323A20006A  
3H00660C  
238310 ESCUTCHEON  
263230 THERMISTOR ASM  
263230 THERMISTOR ASM  
WOCZZ CAPACITOR,DRAWING(INDOOR)  
WOCZZ CAPACITOR,DRAWING(OUTDOOR)  
W6640 TERMINAL BLOCK  
261704 TRANSFORMER,POWER  
249940 CONTROL BOS ASM,SINGLE  
147900 BARRIER,SINGLE  
135510 COVER ASM(CONTROL)  
554160 COMPRESSOR SET  
550140 ISOLATOR,COMP  
567502 O.L.P  
35211A TUBE ASM,SUCTION  
552114 TUBE ASM,DISCHARGE  
552111 TUBE ASM,CAPILLARY  
552113 TUBE ASM, CONDENSER OUT  
552102 TUBE CAPILLARY,BEND  
147911 BARRIER ASM,INDOOR  
346810 MOTOR ASM(INDOOR)  
349600 MOUNT,MOTOR  
6120AR2194A  
2520UKYK2BA  
6120AR2194D  
3H00390A  
6120AR2194B  
2520UKHK2AA  
6170A20012A  
4994A20052A  
4790A20033A  
3551A20062G  
2520UKLK2BA  
4H00982E  
6750U-L061A  
5211A21365A  
5211A20531A  
5211A20623D  
5211A30434A  
5210A22614D  
B
C
6750U-L014A  
6750U-L039A  
-
-
-
-
-
-
-
-
-
-
D
4791A10005D  
4681A20064E  
4960A20026A  
4791A10005A  
4681A20064A  
4960A20032A  
359011 FAN ASM,CROSS FLOW  
349011 DAMPER ASM  
5901A10027A  
4901A30002A  
5230A20016A  
3531A10149D  
5230A20021A  
3551A20197P  
5300A20006A  
5040A30032A  
152302 FILTER(MECH),A/C  
135312 GRILLE ASM,FRONT  
152302 FILTER(MECH),A/C  
135515 COVER ASM,TOP  
753000 HEATER,ELECTRIC  
W50400 RUBBER  
E
F
546811 MOTOR ASM(OUTDOOR)  
130411 BASE ASM,WELD  
135500 DRAIN COVER  
552206 DRAIN,VALVE  
349600 MOUNT,MOTOR  
149980 SHROUD  
559010 FAN ASM,AXIAL  
W48602 CLAMP,SPRING  
4681A20063E  
4681A20063A  
3041A20028B  
3550A20102A  
5220A30006A  
4960A20005A  
4998A20001B  
5900AR1173A  
3H02932B  
148000 BRACE  
354210 EVAPORATOR ASM  
554030 CONDENSER ASM  
4800A20002A  
5421A20118C  
5403A20076B  
5421A20118A  
5403A20091D  
5421A20118A  
5403A20091D  
—34—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
May, 2006  
P/No.: 3828A20308H  
Printed in Korea  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Learning Resources Baby Toy LER 2247 User Manual
Lexmark Printer X782e XL User Manual
LG Electronics Refrigerator LFC20760 User Manual
Lindy Computer Hardware 70531 User Manual
Linksys Switch SD2005 SD2008 User Manual
Logitech Tablet Accessory T650 User Manual
Logitech Universal Remote UR5U 9000L User Manual
Makita Planer 1805N User Manual
Mazda Grill Accessory 9999 95 CX9BSM 08 User Manual
MicroFridge Double Oven FGB24L2EC User Manual