For model: i12060A
i12060A
Smoke Alarm User’s Guide
A.C. Wire-in Single and/or Multiple Station (up to 24 Devices) Ionization
TM
Smoke Alarm with 9 Volt Battery Back Up and HUSH Control to temporar-
ily silence nuisance alarms.
Thank you for purchasing this smoke alarm. It is an important part of your family’s
home safety plan. You can trust this product to provide the highest quality safety
protection. We know you expect nothing less when the lives of your family are at
stake. Kidde alarms and accessories CAN ONLY BE interconnected with other Kidde
alarms and accessories as well as specified brands and models of interconnect com-
patible alarms. Connection of Kidde products to a non-specified manufacturer’s
interconnect system, or connection with non-specified equipment from another
manufacturer into an existing Kidde system could result in nuisance alarming, fail-
ure to alarm, or damage to one or all of the devices in the interconnect system.
Refer to the User’s Guide supplied with each Kidde product for interconnect com-
patible models, brands, and devices. Refer to the wiring instructions in section 3 for
NFPA initiating device limits.
For your convenience, write down the following information. If you call
our Consumer Hotline, these are the first questions you will be asked.
Smoke Alarm Model Number
(located on back of alarm):
Date Code (located on back of alarm): The
National Fire Protection Association (NFPA)
and the manufacturer recommend replacing
this alarm ten years from the date code.
Date of Purchase:
Where Purchased:
Manual P/N 820-0394-EN Rev. G
Download from Www.Somanuals.com. All Manuals Search And Download.
1260-7205-01
• Locate an alarm in every room where someone sleeps with the door closed.
The closed door may prevent an alarm not located in that room from waking
the sleeper.
• Smoke, heat, and combustion products rise to the ceiling and spread horizon-
tally. Mounting the smoke alarm on the ceiling in the center of the room
places it closest to all points in the room. Ceiling mounting is preferred in
ordinary residential construction.
• For mobile home installation, select locations carefully to avoid thermal
barriers that may form at the ceiling. For more details, see MOBILE HOME
INSTALLATION.
• When mounting an alarm on the ceiling, locate it at a minimum of 4” (10 cm)
from the side wall (see FIGURE 1).
• When mounting the alarm on the wall, use an inside wall with the top edge
of the alarm at a minimum of 4” (10 cm) and a maximum of 12” (30.5 cm)
below the ceiling (see FIGURE 1).
• Put smoke alarms at both ends of a bedroom hallway or large room if the
hallway or room is more than 30 feet (9.1 m) long.
• Install Smoke Alarms on sloped, peaked or cathedral ceilings at or within 3ft
(0.9m) of the highest point (measured horizontally). NFPA 72 states: “Smoke
alarms in rooms with ceiling slopes greater than 1 foot in 8 feet (.3m in 2.4
m) horizontally shall be located on the high side of the room.” NFPA 72
states: “A row of detectors shall be spaced and located within 3 ft (0.9m) of
the peak of the ceiling measured horizontally” (see FIGURE 3).
FIGURE 1
FIGURE 2
FIGURE 3
Download from Www.Somanuals.com. All Manuals Search And Download.
MOBILE HOME INSTALLATION
Modern mobile homes have been designed and built to be energy efficient.
Install smoke alarms as recommended above (refer to RECOMMENDED LOCA-
TIONS and FIGURES 1 and 2).
In older mobile homes that are not well insulated compared to present stan-
dards, extreme heat or cold can be transferred from the outside to the inside
through poorly insulated walls and roof. This may create a thermal barrier
which can prevent the smoke from reaching an alarm mounted on the ceiling.
In such units, install the smoke alarm on an inside wall with the top edge of the
alarm at a minimum of 4” (10 cm) and a maximum of 12” (30.5 cm) below the
ceiling (see FIGURE 1).
If you are not sure about the insulation in your mobile home, or if you notice
that the outer walls and ceiling are either hot or cold, install the alarm on an
inside wall. For minimum protection, install at least one alarm close to the bed-
rooms. For additional protection, see SINGLE FLOOR PLAN in FIGURE 2.
WARNING: TEST YOUR SMOKE ALARM OPERATION AFTER R.V. OR
MOBILE HOME VEHICLE HAS BEEN IN STORAGE, BEFORE EACH TRIP AND
AT LEAST ONCE A WEEK DURING USE.
2. LOCATIONS TO AVOID
• In the garage. Products of combustion are present when you start your auto-
mobile.
• Less than 4” (10cm) from the peak of an “A” frame type ceiling.
• In an area where the temperature may fall below 40ºF (4.4˚C) or rise above
100ºF (37.8˚C), such as garages and unfinished attics.
• In dusty areas. Dust particles may cause nuisance alarm or failure to alarm.
• In very humid areas (greater than 85% R.H.). Moisture or steam can cause
nuisance alarms.
• In insect-infested areas.
• Smoke alarms should not be installed within 3 ft (.9m) of the following: the
door to a kitchen, the door to a bathroom containing a tub or shower, forced
air supply ducts used for heating or cooling, ceiling or whole house ventilating
fans, or other high air flow areas.
• Kitchens. Normal cooking may cause nuisance alarms. If a kitchen alarm is
desired, it should have an alarm silence feature or be a photoelectric type.
• Near fluorescent lights. Electronic “noise” may cause nuisance alarms.
• Smoke alarms are not to be used with detector guards unless the combination
Download from Www.Somanuals.com. All Manuals Search And Download.
(alarm and guard) has been evaluated and found suitable for that purpose.
3. INSTALLATION INSTRUCTIONS
WIRING REQUIREMENTS
• This smoke alarm should be installed on a U.L. listed or recognized junction
box. All connections should be made by a qualified electrician and all wiring
used shall be in accordance with articles 210 and 300.3(B) of the U.S. National
Electrical Code ANSI/NFPA 70, NFPA 72 and/or any other codes having jurisdic-
tion in your area. The multiple station interconnect wiring to the alarms must
be run in the same raceway or cable as the AC power wiring. In addition, the
resistance of the interconnect wiring shall be a maximum of 10 ohms.
• The appropriate power source is 120 Volt A.C. Single Phase supplied from a
non-switchable circuit which is not protected by a ground fault interrupter.
• WARNING: This alarm cannot be operated from power derived from a square
wave, modified square wave or modified sine wave inverters. These types of
inverters are sometimes used to supply power to the structure in off grid
installations, such as solar or wind derived power sources. These power
sources produce high peak voltages that will damage the alarm.
WIRING INSTRUCTIONS FOR A.C. QUICK CONNECT HARNESS
CAUTION! TURN OFF THE MAIN POWER TO THE CIRCUIT BEFORE WIRING
THE ALARM.
• For alarms that are used as single station, DO NOT CONNECT THE RED WIRE
TO ANYTHING. Leave the red wire insulating cap in place to make certain that
the red wire cannot contact any metal parts or the electrical box.
• When alarms are interconnected, all interconnected units must be powered
from a single circuit.
• A maximum of 24 Kidde devices may be interconnected in a multiple station
arrangement. The interconnect system should not exceed the NFPA intercon-
nect limit of 12 smoke alarms and/or 18 alarms total (smoke, heat, carbon
monoxide, etc.). With 18 alarms interconnected, it is still possible to intercon-
nect up to a total of 6 remote signaling devices and/or relay modules.
• When mixing models which have battery backup (i12040, i12040A, i12060,
i12060A, i12080, i12080A, i12090A, i4618, i4618A, 1275, 1276, 1285,
1296, PE120, PI2000, PI2010, KN-COSM-IB, RF-SM-ACDC, KN-COPE-I,
KN-SMFM-I, HD135, KN-COB-IC, KN-COP-IC) with models without battery
backup, (1235, i12020, i12020A, KN-COSM-I SM120X, CO120X SL177I) be
advised that the models without battery backup will not respond during an
AC power failure.
Download from Www.Somanuals.com. All Manuals Search And Download.
• For more information about compatible interconnect units and their function-
• The maximum wire run distance between the first and last unit in an intercon-
nected system is 1000 feet.
• Figure 4 illustrates interconnection wiring. Improper connection will result in
damage to the alarm, failure to operate, or a shock hazard.
• Make certain alarms are wired to a continuous (non-switched) power line.
NOTE: Use standard UL listed household wire (as required by local codes) avail-
able at all electrical supply stores and most hardware stores.
FUSE OR CIRCUIT BREAKER
WHITE
BLACK
WHITE
BLACK
RED
RED
Kidde
Relay Module
SM120X
CONNECTOR
CONNECTOR
First
Alarm
Additional
Alarm
Additional
Alarm
Optional
Accessory
FIGURE 4 INTERCONNECT WIRING DIAGRAM
WIRES ON ALARM HARNESS
CONNECTED TO
Black
White
Red
Hot Side of A.C. Line
Neutral Side of A.C. Line
Interconnect Lines (Red Wires) of Other
Units in the Multiple Station Set up
BATTERY INSTALLATION
See MAINTENANCE (Section 6) for battery installation.
CAUTION! THIS UNIT WILL NOT FUNCTION WITHOUT A PROPERLY
INSTALLED BATTERY, AND IS EQUIPPED WITH A BATTERY LOCKOUT FEA-
TURE WHICH PREVENTS THE BATTERY CARRIER FROM CLOSING IF A BAT-
TERY IS NOT INSTALLED CORRECTLY.
MOUNTING INSTRUCTIONS
CAUTION: THIS UNIT IS SEALED. THE COVER IS NOT
REMOVABLE!
CAUTION: WHEN WALL MOUNTING: UNIT MUST BE
MOUNTED SO THAT THE BATTERY BOX FACES
DOWN! (SEE FIGURE 5). INCORRECT ORIENTATION
FIGURE 5
Download from Www.Somanuals.com. All Manuals Search And Download.
OF WALL MOUNTED SMOKE ALARMS WILL DECREASE OPERATIONAL
EFFECTIVENESS.
1. Remove the trim ring from the back of the alarm by holding the trim ring and
twisting the alarm counter-clockwise.
2. After selecting the proper smoke alarm location as described in Section 1 and
wiring the AC Quick Connector as described in the WIRING INSTRUCTIONS,
attach the trim ring to the electrical box (see Figure 6). To ensure aesthetic align-
ment of the alarm with the hallway or wall, the “A” line on the mounting
bracket must be parallel with the hallway when ceiling mounted, or horizontal
when wall mounted.
When wall mounting,
the “A” line should be
When
mounting in
a hallway,
the “A” line
should be
horizontal.
parallel with
the hallway.
A
A
Install
Remove
FIGURE 6
Alignment Marks
3. Pull the AC QUICK CONNECTOR through the center hole in the mounting
bracket and secure the bracket, making sure that the mounting screws are posi-
tioned in the small ends of the keyholes before tightening the screws.
4. Plug the AC QUICK CONNECTOR into the back of the alarm (see Figure 7), making
sure that the locks on the connector snap into place. Then
push the excess wire back into the electrical box through
the hole in the center of the mounting bracket.
5. Install the alarm on the mounting bracket and rotate the
alarm clockwise until the alarm ratchets into place (this
ratcheting function allows for aesthetic alignment). NOTE:
The alarm will mount to the bracket in 4 positions (every 90
degrees). When wall mounting, make sure the battery box
is at the bottom of the unit. (see Figure 5).
FIGURE 7
6. Pull the Battery Pull Tab (yellow tab protruding from the unit) completely out
of the unit. This will automatically connect the battery.
7. Test the unit to ensure proper operation by pressing the Test/Hush Button for
a minimum of 5 seconds. (All interconnected, battery backed up, alarms should
respond).
Download from Www.Somanuals.com. All Manuals Search And Download.
CAUTION: Due to the loudness (85 decibels) of the alarm, always stand
an arms length away from the unit when testing.
8. Turn on the AC power. The green Power On Indicator should be lit when the
alarm is operating from AC power. Confirm unit operation by pressing the
Test/Hush button.
TAMPER RESIST FEATURES
Smoke Alarm Tamper Resist Feature
This alarm has a tamper resist feature, which helps prevent someone from
removing the unit from the mounting bracket. When used in conjunction with
the Battery Carrier Tamper Resist Feature, it can be very effective in preventing
smoke alarm tampering and battery removal.
Activate the smoke alarm tamper resist feature by breaking off the four posts in
the square holes in the mounting bracket (see Figure 8A). When the posts are
broken off, the tamper resist tab on the base is allowed to engage the mounting
bracket. Rotate the alarm onto the mounting bracket until you hear the tamper
resist tab snap into place, locking the alarm on the mounting bracket. Using the
tamper resist feature will help deter children and others from removing the
alarm from the bracket. NOTE: To remove the alarm when the tamper resist tab
is engaged, press down on the tamper resist tab, and rotate the alarm off the
bracket (see Figure 8B).
Battery Carrier Tamper Resist Feature
Locations
of Posts
FIGURE 8A
FIGURE 8B
This alarm has a battery carrier tamper resist feature, which helps prevent the
battery carrier from being opened. This feature is effective in preventing the
removal of the battery from this device (which will render the unit inoperable
during the loss of AC power).
To activate the battery carrier tamper resist feature, remove the unit from the
trim plate, disconnect the AC quick connector and locate the small cut-out in
the middle of the product label on the back of the unit. With a small screwdriv-
er, or similar tool, move the slider towards the lock position as indicated by the
Download from Www.Somanuals.com. All Manuals Search And Download.
arrow. (see Figure 9) The tamper resist feature is now active and the battery
carrier can not be opened until the tamper resist feature is deactivated.
NOTE: Before activating the battery carrier tamper resist
feature, make sure a fresh battery is installed in the
unit and that the battery carrier is properly closed. If
the battery carrier tamper resist feature is activated
while the battery carrier is open, the battery carrier will
not close and the unit will be inoperable during the
loss of AC power.
FIGURE 9
To deactivate the battery carrier tamper resist, in order to
change the smoke alarm battery, remove the unit from the trim plate (see Smoke
Alarm Tamper Resist Feature if activated), disconnect the AC quick connector and
locate the small cut-out in the middle of the product label. Using a screwdriver, or
similar tool, move the slider away from the lock position (opposite the direction
indicated by the arrow). The battery carrier can now be opened and the battery
changed.
4. OPERATION AND TESTING
OPERATION: The smoke alarm is operating once A.C. power is applied, fresh
batteries are installed and testing is complete. When the smoke alarm ionization
chamber senses products of combustion, the horn will sound a loud (85db)
temporal alarm until the sensing chamber is cleared of smoke particles.
HUSHTM CONTROL: The “HUSH” feature has the capability of temporarily
desensitizing the alarm circuit for up to 8 minutes. This feature is to be used
only when a known alarm condition, such as smoke from cooking, activates the
alarm.The smoke alarm is desensitized by pushing the “TEST/HUSH” button on
the smoke alarm cover. If the smoke is not too dense, the alarm will silence
immediately. The red LED will illuminate for 1.5 seconds every 8-10 seconds
while in hush. This indicates that the alarm is in a temporarily desensitized condi-
tion. The smoke alarm will automatically reset after approximately 8 minutes and
sound the alarm if particles of combustion are still present. The “HUSH” feature
can be used repeatedly until the air has been cleared of the condition causing the
alarm. Pushing the Test/Hush button on the alarm will end the hush period.
This alarm has a low battery HUSH feature. If the alarm is sounding a low
battery warning chirp, you can silence this chirp for approximately 13 hours by
pressing the Test/Hush button.
NOTE: DENSE SMOKE WILL OVERRIDE THE HUSH CONTROL FEATURE AND
SOUND A CONTINUOUS ALARM.
CAUTION: BEFORE USING THE ALARM HUSH FEATURE, IDENTIFY THE
SOURCE OF THE SMOKE AND BE CERTAIN A SAFE CONDITION EXISTS.
Download from Www.Somanuals.com. All Manuals Search And Download.
LED INDICATORS: This smoke alarm is equipped with red and green LED indica-
tors. The green LED (when illuminated) indicates the presence of AC power.
The red LED has four modes of operation:
Standby Condition: The red LED will flash every 40 seconds to indicate
that the smoke alarm is operating properly.
Alarm Condition:
When the alarm senses products of combustion and
goes into alarm, the red LED will flash one flash per
second. The flashing LED and pulsating alarm will
continue until the air is cleared.
WHEN UNITS ARE INTERCONNECTED, only the red LED
of the alarm which senses the smoke or is being tested
(the originating unit) will flash. All other units in the
interconnect system will sound an alarm but their red
LED’s will NOT be flashing.
Alarm Memory:
This smoke alarm is equipped with an alarm memory,
which provides a visual indication when an alarm has
been activated. The red LED will illuminate for about 1.5
seconds every 20 seconds to indicate the memory
condition. The memory will remain activated until
pushing the Test/Hush Button resets it or will time-out
between 11 to 13 hours. In an interconnected installation
only the memory of the originating alarm will be activated.
®
Hush mode:
The red LED will illuminate for 1.5 seconds every 10
seconds, indicating the smoke alarm is in the Hush®
mode.
TESTING: Test by pushing the Test/Hush button on the cover and hold it down
for a minimum of 5 seconds. This will sound the alarm if all the electronic cir-
cuitry, horn and battery are working. In an interconnected installation all inter-
connected alarms should sound when the test feature on any one of the inter-
connected alarms is activated. If no alarm sounds, check the fuse or circuit
breaker supplying power to the alarm circuit. If the alarm still does not sound,
the unit has defective batteries or other failure. DO NOT use an open flame to
test your alarm, you could damage the alarm or ignite combustible materials
and start a structure fire.
TEST THE ALARM WEEKLY TO ENSURE PROPER OPERATION. Erratic or low sound
coming from your alarm may indicate a defective alarm, and it should be
returned for service (see Section 12).
Download from Www.Somanuals.com. All Manuals Search And Download.
5. NUISANCE ALARMS
Smoke alarms are designed to minimize nuisance alarms. Cigarette smoke will
not normally set off the alarm, unless the smoke is blown directly into the alarm.
Combustion particles from cooking may set off the alarm if the alarm is located
close to the cooking area. Large quantities of combustible particles are generat-
ed from spills or when broiling. Using the fan on a range hood which vents to
the outside (non-recirculating type) will also help remove these combustible
products from the kitchen.
Model i12060A has a “HUSH” feature that is extremely useful in a kitchen area
or other areas prone to nuisance alarms. For more information, refer to Section
4 OPERATION AND TESTING.
If the alarm does sound, check for fires first. If a fire is discovered, get out and
call the fire department. If no fire is present, check to see if one of the reasons
listed in Section 2 may have caused the alarm.
6. MAINTENANCE/TROUBLESHOOTING
ALARM REMOVAL
IF SMOKE ALARM TAMPER RESIST FEATURE HAS BEEN ACTIVATED, REFER
TO SMOKE ALARM TAMPER RESIST FEATURE IN SECTION 3 FOR REMOVAL
INSTRUCTIONS.
To remove the alarm from the trim ring, rotate the alarm counter clockwise in the
direction of the "OFF" arrow on the cover. To disconnect the A.C. power harness,
squeeze the locking arms on the sides of the Quick Connector while pulling the
connector away from the bottom of the alarm (see Section 3, Figure 7).
BATTERY INSTALLATION AND REMOVAL
Note: If battery carrier tamper resist feature has been activated it will need to
be deactivated in order to change the battery. Refer to section 3 “Battery
Carrier Tamper Resist Feature” for instructions.
To replace or install the batteries press down on the battery carrier and then
release to allow the carrier to pop open. The battery can then be pulled out of
the carrier. When installing a new battery into the carrier, make sure the battery
terminals are exposed and that the polarity matches the markings printed on the
battery carrier. Completely press the battery carrier down into the alarm and
release, the battery carrier will lock into the closed position.
A missing or improperly installed battery will prevent the battery carrier from
closing and result in improper alarm operation.
Download from Www.Somanuals.com. All Manuals Search And Download.
This smoke alarm uses a 9V carbon zinc battery (alkaline and lithium batteries
may also be used). A fresh battery should last for one year under normal operat-
ing conditions.
PRESS
OPEN
INSERT
This alarm has a low/missing battery monitor circuit which will cause the alarm
to “chirp” approximately every 30-40 seconds for a minimum of seven (7) days
when the battery gets low.Replace the battery when this condition occurs.
NOTE: Low/missing battery monitor circuit WILL cause the unit to chirp while
replacing the battery. This function will cease once the new battery has been
installed. To avoid this “chirp” the unit can be removed from the base and dis-
connected from the AC power when replacing the battery, but it is not necessary.
USE ONLY THE FOLLOWING 9 VOLT BATTERIES FOR SMOKE ALARM
BATTERY REPLACEMENT.
Carbon-zinc type EVEREADY 1222; GOLD PEAK 1604P OR 1604S
Alkaline type
ENERGIZER 522; DURACELL MN1604 OR MX1604; GOLD
PEAK 1604A PANASONIC 6AM6, 6AM-6, 6AM-6PI,
6AM6X, AND 6LR61 (GA)
Lithium type
ULTRALIFE U9VL-J
These smoke alarms can be purchased at your local retailer.
NOTE: WEEKLY TESTING IS REQUIRED!
WARNING! BE SURE TO FOLLOW BATTERY INSTALLATION INSTRUCTIONS
PRINTED ON THE BACK OF THE ALARM AND USE ONLY THE BATTERIES
SPECIFIED. USE OF DIFFERENT BATTERIES MAY HAVE A DETRIMENTAL
EFFECT ON THE SMOKE ALARM.
WARNING: THIS ALARM WILL “CHIRP” IF ABNORMAL OPERATION OF THE
SMOKE-SENSING CHAMBER IS DETECTED. THIS CHIRP WILL OCCUR
APPROXIMATELY 20 SECONDS AFTER THE RED LED FLASH. REPLACE THE
ALARM IF THIS CONDITION OCCURS.
Download from Www.Somanuals.com. All Manuals Search And Download.
CLEANING YOUR ALARM
YOUR ALARM SHOULD BE CLEANED AT LEAST ONCE A YEAR
To clean your alarm, remove it from the mounting bracket as outlined in the
beginning of this section. You can clean the interior of your alarm (sensing
chamber) by using compressed air or a vacuum cleaner hose and blowing or
vacuuming through the openings around the perimeter of the alarm. The out-
side of the alarm can be wiped with a damp cloth. After cleaning, reinstall your
alarm, verify the green LED is on and test your alarm by using the Test/Hush
Button. If cleaning does not restore the alarm to normal operation the alarm
should be replaced.
7. LIMITATIONS OF SMOKE ALARMS
WARNING: PLEASE READ CAREFULLY AND THOROUGHLY
• NFPA 72 states: Life safety from fire in residential occupancies is based primari-
ly on early notification to occupants of the need to escape, followed by the
appropriate egress actions by those occupants. Fire warning systems for
dwelling units are capable of protecting about half of the occupants in poten-
tially fatal fires. Victims are often intimate with the fire, too old or young, or
physically or mentally impaired such that they cannot escape even when
warned early enough that escape should be possible. For these people, other
strategies such as protection-in-place or assisted escape or rescue are neces-
sary.
• Smoke alarms are devices that can provide early warning of possible fires at a
reasonable cost; however, alarms have sensing limitations. Ionization sensing
alarms may detect invisible fire particles (associated with fast flaming fires)
sooner than photoelectric alarms. Photoelectric sensing alarms may detect visi-
ble fire particles (associated with slow smoldering fires) sooner than ionization
alarms. Home fires develop in different ways and are often unpredictable. For
maximum protection, Kidde recommends that both Ionization and
Photoelectric alarms be installed.
• A battery powered alarm must have a battery of the specified type, in good con-
dition and installed properly.
• A.C. powered alarms (without battery backup) will not operate if the A.C.
power has been cut off, such as by an electrical fire or an open fuse.
• Smoke alarms must be tested regularly to make sure the batteries and the
alarm circuits are in good operating condition.
Download from Www.Somanuals.com. All Manuals Search And Download.
• Smoke alarms cannot provide an alarm if smoke does not reach the alarm.
Therefore, smoke alarms may not sense fires starting in chimneys, walls, on
roofs, on the other side of a closed door or on a different floor.
• If the alarm is located outside the bedroom or on a different floor, it may not
wake up a sound sleeper.
• The use of alcohol or drugs may also impair one’s ability to hear the smoke
alarm. For maximum protection, a smoke alarm should be installed in each
sleeping area on every level of a home.
• Although smoke alarms can help save lives by providing an early warning of a
fire, they are not a substitute for an insurance policy. Home owners and
renters should have adequate insurance to protect their lives and property.
8. GOOD SAFETY HABITS
DEVELOP AND PRACTICE A PLAN OF ESCAPE
• Install and maintain Fire extinguishers on every level of the home and in the
kitchen, basement and garage. Know how to use a fire extinguisher prior to
an emergency.
• Make a floor plan indicating all doors and windows and at least two (2)
escape routes from each room. Second story windows may need a rope or
chain ladder.
• Have a family meeting and discuss your escape plan, showing everyone what
to do in case of fire.
• Determine a place outside your home where you all can meet if a fire occurs.
• Familiarize everyone with the sound of the smoke alarm and train them to
leave your home when they hear it.
• Practice a fire drill at least every six months, including fire drills at night.
Ensure that small children hear the alarm and wake when it sounds. They
must wake up in order to execute the escape plan. Practice allows all occu-
pants to test your plan before an emergency. You may not be able to reach
your children. It is important they know what to do.
• Current studies have shown smoke alarms may not awaken all sleeping indi-
viduals, and that it is the responsibility of individuals in the household that are
capable of assisting others to provide assistance to those who may not be
awakened by the alarm sound, or to those who may be incapable of safely
evacuating the area unassisted.
Download from Www.Somanuals.com. All Manuals Search And Download.
WHAT TO DO WHEN THE ALARM SOUNDS
• Alert small children in the home.
• Leave immediately by your escape plan. Every second counts, so don’t waste
time getting dressed or picking up valuables.
• In leaving, don’t open any inside door without first feeling its surface. If hot,
or if you see smoke seeping through cracks, don’t open that door! Instead,
use your alternate exit. If the inside of the door is cool, place your shoulder
against it, open it slightly and be ready to slam it shut if heat and smoke rush
in.
• Stay close to the floor if the air is smoky. Breathe shallowly through a cloth,
wet if possible.
• Once outside, go to your selected meeting place and make sure everyone is
there.
• Call the fire department from your neighbor’s home - not from yours!
• Don’t return to your home until the fire officials say that it is all right to do so.
There are situations where a smoke alarm may not be effective to protect
against fire. For instance:
- Smoking in bed.
- Leaving children unsupervised.
- Cleaning with flammable liquids, such as gasoline.
- Fires where the victim is intimate with a flaming initiated fire;
for example, when a person's clothes catch fire while cooking.
- Fires where the smoke is prevented from reaching the detector
due to a closed door or other obstruction.
- Incendiary fires where the fire grows so rapidly that an occupant's
egress is blocked even with properly located detectors
9. NRC INFORMATION
Ionization type smoke alarms use a very small amount of a radioactive element
in the sensing chamber to enable detection of visible and invisible combustion
products. The radioactive element is safely contained in the chamber and
requires no adjustments or maintenance. This smoke alarm meets or exceeds all
government standards. It is manufactured and distributed under license from
the U.S. Nuclear Regulatory Commission.
Download from Www.Somanuals.com. All Manuals Search And Download.
10. NFPA REQUIRED PROTECTION
The National Fire Protection Association’s Standard 72 provides the following
information:
Smoke Detection – Where required by applicable laws, codes, or standards for
the specified occupancy, approved single- and multiple-station smoke alarms
shall be installed as follows: (1) In all sleeping rooms Exception: Smoke alarms
shall not be required in sleeping rooms in existing one- and two-family dwelling
units. (2) Outside of each separate sleeping area, in immediate vicinity of the
sleeping rooms. (3) On each level of the dwelling unit, including basements
Exception: In existing one- and two-family dwelling units, approved smoke
alarms powered by batteries are permitted.
Smoke Detection – Are More Smoke Alarms Desirable? The required number of
smoke alarms might not provide reliable early warning protection for those areas
separated by a door from the areas protected by the required smoke alarms. For
this reason, it is recommended that the householder consider the use of addi-
tional smoke alarms for those areas for increased protection. The additional
areas include the basement, bedrooms, dining room, furnace room, utility room,
and hallways not protected by the required smoke alarms. The installation of
the smoke alarms in the kitchen, attic (finished or unfinished), or garage is nor-
mally not recommended, as these locations occasionally experience conditions
that can result in improper operation.
This equipment should be installed in accordance with the National Fire
Protection Association’s Standard 72 (NFPA, Batterymarch Park, Quincy, MA
02269).
NOTIFY YOUR LOCAL FIRE DEPARTMENT AND INSURANCE COMPANY OF YOUR
SMOKE ALARM INSTALLATION.
11. CAUTION (AS REQUIRED BY THE CALIFORNIA STATE FIRE
MARSHAL)
“Early warning fire detection is best achieved by the installation of fire detection
equipment in all rooms and areas of the household as follows. A smoke alarm
installed in each separate sleeping area (in the vicinity of, but outside of the bed-
rooms), and heat or smoke detectors in the living rooms, dining rooms, bed-
rooms, kitchens, hallways, attics, furnace rooms, closets, utility and storage
rooms, basements and attached garages.”
Download from Www.Somanuals.com. All Manuals Search And Download.
12. SERVICE AND WARRANTY
If after reviewing this manual you feel that your smoke alarm is defective in any
way, do not tamper with the unit.
Return it for servicing to: KIDDE, 1016 Corporate Park Dr., Mebane, NC 27302.
1-800-880-6788 (See Warranty for in-warranty returns).
Download from Www.Somanuals.com. All Manuals Search And Download.
TEN YEAR LIMITED WARRANTY
Kidde warrants to the original purchaser that the enclosed smoke alarm (but not the
battery) will be free from defects in material and workmanship or design under normal
use and service for a period of ten years from the date of purchase. The obligation of
Kidde under this warranty is limited to repairing or replacing the smoke alarm or any
part which we find to be defective in material, workmanship or design, free of charge
to the customer, upon sending the smoke alarm with proof of date of purchase,
postage and return postage prepaid, to Warranty Service Department, Kidde, 1016
Corporate Park Dr., Mebane, NC 27302.
This warranty shall not apply to the smoke alarm if it has been damaged, modified,
abused or altered after the date of purchase or if it fails to operate due to improper
maintenance or inadequate A.C. or D.C. electrical power.
THE LIABILITY OF KIDDE OR ANY OF ITS PARENT OR SUBSIDIARY CORPORATIONS ARIS-
ING FROM THE SALE OF THIS SMOKE ALARM OR UNDER THE TERMS OF THIS LIMITED
WARRANTY SHALL NOT IN ANY CASE EXCEED THE COST OF REPLACEMENT OF
SMOKE ALARM AND, IN NO CASE, SHALL KIDDE OR ANY OF ITS PARENT OR SUB-
SIDIARY CORPORATIONS BE LIABLE FOR CONSEQUENTIAL LOSS OR DAMAGES RESULT-
ING FROM THE FAILURE OF THE SMOKE ALARM OR FOR BREACH OF THIS OR ANY
OTHER WARRANTY, EXPRESS OR IMPLIED, EVEN IF THE LOSS OR DAMAGE IS CAUSED
BY THE COMPANY’S NEGLIGENCE OR FAULT.
Since some states do not allow limitations on the duration of an implied warranty or do
not allow the exclusion or limitation of incidental or consequential damages, the above
limitations or exclusions may not apply to you. While this warranty gives you specific
legal rights, you may also have other rights which vary from state to state.
Also, Kidde makes no warranty, express or implied, written or oral, including that of
merchantability or fitness for any particular purpose, with respect to the battery.
The above warranty may not be altered except in writing signed by both parties hereto.
QUESTIONS OR FOR MORE INFORMATION
Call our Consumer Hotline at 1-800-880-6788 or contact
us at our website at www.kidde.com
Kidde 1016 Corporate Park Drive, Mebane, NC 27302
Download from Www.Somanuals.com. All Manuals Search And Download.
|