WARNING:
IF THE INFORMATION IN THESE INSTRUC-
TIONS ARE NOT FOLLOWED EXACTLY, A FIRE
OR EXPLOSION MAY RESULT CAUSING PROP-
ERTY DAMAGE, PERSONAL INJURY OR LOSS
OF LIFE.
FOR YOUR SAFETY:
DO NOT STORE OR USE GASOLINE OR OTHER
FLAMMABLE VAPORS AND LIQUIDS IN THE
VICINITY OF THIS OR ANY OTHER APPLIANCE.
Jøtul GZ 550 DV II
Acadia
INSTALLATION:
INSTALLATION AND SERVICE MUST BE PER-
FORMED BY A QUALIFIED INSTALLER, SER-
VICE AGENCY OR LICENSED GAS SUPPLIER.
Direct Vent Gas
Fireplace
WHAT TO DO IF YOU SMELL GAS:
• DO NOT TRY TO LIGHT ANY APPLIANCE.
• DO NOT TOUCH ANY ELECTRICAL
SWITCHES.
• DO NOT USE THE PHONE IN YOUR
BUILDING. IMMEDIATELY CALL YOUR GAS
SUPPLIER FROM A NEIGHBOR’S PHONE.
• FOLLOW YOUR GAS SUPPLIER’S
INSTRUCTIONS.
• IF YOU CANNOT REACH YOUR GAS
SUPPLIER, CALL THE FIRE DEPARTMENT.
AVERTISSEMENT:
ASSUREZ-VOUS DE BIEN SUIVRE LES IN-
STRUCTIONS DANS CETTE NOTICE POUR
REDUIRE AU MINIMUM LE RISQUE D’INCENDIE
OU POUR EVITER TOUT DOMMAGE MATERIEL,
TOUTE BLESSURE OU MORTALIT’E.
NE PAS ENTREPOSER NI UTILISER D’ESSENCE
NI OU LIQUIDES INFLAMMABLES DANS LE
VOISINAGE DE CET APPAREIL OU DE TOUT
AUTRE APPAREIL.
Installation
and
L’INSTALLATION LE SERVICE DOIVENT
ETRE EXECUTES PAR UN INSTALLATEUR
QUALIFIE, AGENCE DE SERVICE OU LE
FOURNISSEUR DE GAZ.
Operation
Instructions
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE
GAZ.
• NE PAS TENTER D’ALLUMER L’APPAREIL
• NE TOUCHEZ A AUCUM NTERRUPTEUR.
• NE PAS VOUS SERVIR DES TELEPHONES
SET TROUVANT DANS LE BATIMENT OU
VOUS VOUS TROUVEZ.
• APPELEZ IMMEDIATEMENT VOTRE
FOURNISSEUR DE GAZ CHEZ UN VOISIN.
SUIVEZ LES INSTRUCTIONS DU FOURNISSEUR.
• SI VOUS NE POUVEZ REJOINDRE LE
FOURNISSEUR DE GAZ, APPELEZ LE SER-
VICE DES INCENDIES.
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
Unpacking the Fireplace
1. Before you remove the carton, remove the cast
iron parts that are packed around the fireplace
cabinet.
Specifications ................................... 4
Installation / Service Tools ............ 5
General Information ....................... 5
Safety Information .......................... 6
Installation Requirements
Framing ............................................ 6
Mantel Clearances ........................ 8
Hearth Protection ......................... 8
Vent Requirements ....................... 9
Vertical Termination ................... 10
Horizontal Termination.............. 11
Terminal Clearances.................... 11
Vent Restrictor ............................. 12
Fireplace Assembly
2. Lift the shipping carton off of the fireplace
cabinet.
3. Unpack the Firebox. The Logset is packaged inside
the firebox. Remove the Glass Panel Frame to
unpack the firebox:
Blower Installation...................... 12
Gas Connection ............................ 14
Gas Pressure.................................. 14
High Altitude Adjustment ........ 15
Fuel Conversion............................ 16
Wall Thermostat .......................... 19
Remote Control ............................ 19
Antique Brick Kit .......................... 20
Log Set Installation ..................... 21
Surround Assembly..................... 22
Double Door Installation ........... 22
System Check................................ 23
Operation......................................... 25
Maintenance................................... 26
Glass Replacement ........................ 26
Service Log ....................................... 27
Illustrated Parts Breakdown ....... 28
Replacement Parts List................. 29
Accessories ...................................... 30
Lighting Instructions .... Back Cover
• Locate the right and left spring latches on the
underside of the firebox floor. Release each latch
by pulling them forward to disengage the frame
body.
• Pull the Glass Frame away from the firebox and
lift to disengage it from the three steel tabs
located at the top of the firebox. Set the glass out
of the way.
Do not unpack the logs until you are ready to
install them.
Spring Latches
BLOWER
BURNER
IGNITOR
ON
HI
MANUAL
OFF
MANUAL
OFF
AUTO
AUTO
OFF
LO
HI
LO
Pull each Spring Latch to disengage them from the
Glass Frame.
PLEASE READ THESE INSTRUCTIONS IN
THEIR ENTIRETY AND MAKE THEM
AVAILABLE TO ANYONE USING OR
SERVICING THIS APPLIANCE.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Jøtul GZ 550 DV II Acadia
Direct Vent Gas Fireplace
Manufactured and Distributed by:
Jøtul A.S.A.
Fredrikstad, Norway
Jøtul North America
Portland, Maine
Test Standards
THIS HEATER MUST BE INSTALLED AND
MAINTAINED BY A QUALIFIED SERVICE
AGENCY.
This appliance complies with
National Safety standards
and is tested and listed by
Intertek Testing Services of
Middleton, Wisconsin to ANSI
Z21.88-2002•CSA 2.33-M02
and CAN/CGA 2.17--M91,
CSA P.4.-01.2 for Canada.
IN THE COMMENWEALTH OF
MASSACHUSETTS, THIS PRODUCT
MUST BE INSTALLED BY A LICENSED
PLUMBER OR GAS-FITTER.
DO NOT ATTEMPT TO ALTER OR
MODIFY THE CONSTRUCTION OF THIS
APPLIANCE OR ITS COMPONENTS. ANY
MODIFICATION OR ALTERATION WILL
VOID THE WARRANTY, CERTIFICATION
AND LISTING OF THIS APPLIANCE.
DO NOT ATTEMPT TO ALTER OR MODIFY THE CON-
STRUCTION OF THE APPLIANCE OR ITS COMPONENTS.
ANY MODIFICATION OR ALTERATION WILL VOID THE
WARRANTY, CERTIFICATION AND LISTING OF THIS
APPLIANCE.
Specifications
Input Rates
Natural Gas
28,000 BTU/hr. maximum input
16,000 BTU/hr. minimum input
Propane
28,000 BTU/hr. maximum input
15,500 BTU/hr. minimum input
Inlet Pressure:
MIN
Natural Gas: 5.0 WC (1.24 kPa)
Propane: 12.0 WC (2.98 kPa)
MAX
We at Jøtul North America are dedicated to
manufacturing the finest quality hearth
products you can be assured will give you
many years of safe, dependable service.
11.0 WC (2.74 kPa)
14.9.0 WC (3.71 kPa)
Manifold Pressure: MIN
Natural Gas: 1.2 WC (.29 kPa)
MAX
3.8 WC (.94 kPa)
11.0 WC (2.74 kPa)
Propane:
2.9 WC (.72 kPa)
To ensure your confidence, we recommend
that whenever possible, our products be
installed and serviced by professionals who
are certified by the National Fireplace
Institute (NFI) or, in Canada, by Wood Energy
Technical Training (WETT).
THIS FIREPLACE IS SHIPPED AS A
NATURAL GAS FIREPLACE ONLY. IF
USE WITH PROPANE IS DESIRED,
THE FIREPLACE MUST BE CON-
VERTED TO USE WITH PROPANE.
FOR YOUR CONVENIENCE THIS
FIREPLACE IS SHIPPED WITH A
PROPANE CONVERSION KIT.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
4. DO NOT OPERATE THIS FIREPLACE IF ANY PART HAS
BEEN UNDER WATER.
General Information
Immediately call a qualified service technician to
inspect the heater and to replace any part of the
control system and any gas control which has
been under water.
IMPORTANT:
SAVE THESE INSTRUCTIONS.
Ne pas se servir de cet appareil s’il a ete’ plonge
dans l’eau, completement ou en partie. Appeler
un technicien qualifie pour inspecter l’appareil et
remplacer toute partie du syste’me de controle et
toute commande qui ont ete plonges dans l’eau.
THIS HEATER MUST BE INSTALLED AND
MAINTAINED BY A QUALIFIED SERVICE
AGENCY.
DO NOT ATTEMPT TO ALTER OR
MODIFY THE CONSTRUCTION OF THIS
APPLIANCE OR ITS COMPONENTS. ANY
MODIFICATION OR ALTERATION WILL
VOID THE WARRANTY, CERTIFICATION
AND LISTING OF THIS APPLIANCE.
5. Do not operate the fireplace with the glass front
removed, cracked or broken. Replacement of the
glass should be done by a licensed or qualified
service person. Only remove glass for routine
service. Always handle glass carefully.
Pour utilisation avec les portes en verre cerifiers
aved l’appareil seulemend ou. Ne pas utiliser avec
des portes on verre.
1. The installation and repair of this appliance must
be done by a qualified service person. Failure to
properly install and maintain this heater could
result in an unsafe or hazardous installation,
which may result in a fire, explosion, property
damage, personal injury or loss of life.
6. Notify your insurance company before proceding
with installation of this fireplace.
7. This appliance may be installed in an aftermarket
permanently located, manufactured (mobile)
home, where not prohibited by local codes. This
appliance is only for use with the type(s) of gas
indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a
certified kit is used.
2. This appliance should be inspected before use
and at least annually. More frequent cleaning
may be required due to excessive lint from
carpeting, bedding material, etc. It is imperative
that control compartments, burners and circulat-
ing air passageways of the appliance be kept
clean.
Cet appareil peut être installé dans un maison
préfabriquée (mobile) déjà installée à demeure si
les règlements locaux le permettent. Cet appareil
doit être utilisé uniquement avec les types de gas
indiqués sur la plaque signalétique. Ne pas
l’utiliser avec d’autres gas sauf si un kitde conver-
sion certifié est installé.
`S’assurer que le bruleur et le compartiment des
commandes sont propres. Voir les instructions
d’installation et d’utilisation qui accompagnent
l’appareil.
3. The installation must conform to local codes. Your
local Jøtul authorized dealer can assist you in
determining what is required in your area for a
safe and legal installation. Some areas require a
permit to install a gas burning appliance. Always
consult your local building inspector or authority
having jurisdiction to determine what regulations
apply in your area.
Suggested Tools for
Installation and Service
• External regulator (for Propane only)
• Piping which complies with local code
• Manual shutoff valve - T-Handle in MA
• Sediment trap - if required by code
• 10mm open end wrench
In the absence of local codes, the installation
requirements must comply with the current
National codes. In the U.S., these requirements
are established in the National Fuel Code, ANSI
Z223.1.(NFPA 54). In Canada, the codes have been
established in CAN/CGA B149 Fuel Installation
Code.
• 1/2”, 7/16” open end wrench
• Phillips head screwdriver
• Flat head screwdriver •Tee joint
• Pipe wrench
•Pipe sealant
• 1/4” nut driver
• Gloves
•Torx T20 screwdriver
•Safety glasses
•Power Drill
Installer l’appareil selon les codes ou reglements
locaux, ou, en l’absence de tels reglements, selon
les Codes d’installation CAN/CGA-B149.
• Leak test solution
• Reciprocating Saw
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Safety Information
Due to the high operating temperatures this
appliance should be located out of traffic and
away from furniture, draperies, etc. Maintain
proper clearance to combustible mantels and
fireplace trim.
Requirements
The GZ 550 DV Acadia Gas Fireplace and its vent
system must be installed within a totally enclosed
structure. The fireplace must be connected to the
specified vent and termination cap outside the
building. Do not vent into another room or inside
any part of a building. Under no circumstances may
the flow of combustion or ventilation air be ob-
structed.
Children and adults should be alerted to the
hazards of high surface temperatures and should
stay away to avoid burns or clothing ignition.
Young children should be supervised while they
The approved vent configurations described
herein are derived from extensive testing under
controlled laboratory conditions. Gas appliance
performance can be negatively affected by variables
present in the installation environment, i.e: strong
prevailing winds, steep roofs, nearby trees, snow
accumulation, etc. These conditions should be taken
into consideration by the installer and home owner.
In such instances, system performance can often be
improved by an increase in the vent height or
installation of a high wind termination cap.
are in the same room as the Acadia gas fireplace.
Surveiller les enfants. Garder les vetements, les
meubles, l’essence ou autres liquides a vapeur
inflammables loin de l’appareil.
Clothing or other flammable materials should not
be placed ON or NEAR the Acadia gas fireplace.
Never allow any to use the fireplace if they are
unfamiliar with its operation.
NEVER store or use gasoline or any other flam-
mable vapors or liquids in the vicinity of the
Acadia gas fireplace.
Placement and Framing
The combustible framing members of the fireplace
enclosure may be placed in direct contact with the
fireplace cabinet as specified in the illustrations on
the following pages. Use the standoffs integrated
into the sides and top of the front opening to locate
a combustible header and side framing members as
shown in the illustrations. See fig. 1.
Never burn any solid materials (wood, cardboard,
paper, coal, etc.) in this gas fireplace. Use with
natural gas or propane fuel ONLY.
Any safety screen, glass or guard removed for
servicing the appliance must be replaced prior to
operating the appliance.
Do not slam or strike the glass panel.
Electrical Power: If the optional Blower (#155630)
will be used, be sure to include provision for a
properly grounded, 120 volt house current outlet at
the fireplace structure.
Wear gloves and safety glases while performing
maintenance procedures.
Electrical Hazard
Parallel Installation
Be aware of electrical wiring locations when
Although it is possible to place combustible framing
members in direct contact with the rear surface of
the cabinet, the fireplace must be located forward
of the back wall with adequate clearance to accom-
modate the vent adaptor and subsequent lengths
of vent pipe. Consideration must also be given to
maintaining a minimum 1 inch (25 mm) clearance
between a vertical vent pipe and any combustible
materials to the rear of the unit. See Figs. 2, 3, and 4.
cutting holes in walls and ceilings for termination.
The optional Acadia Blower (155630) must be
electrically grounded in accordance with local
codes or, in the absence of local codes, with the
current ANSI/NFPA 70, National Electrical Code or
CSA C22.1-Canadian Electrical Code.
The Acadia Blower is supplied with a three-prong
(grounding) plug for protection against shock
hazard and should be plugged directly into a
properly grounded three-prong receptacle. DO
NOT CUT OR REMOVE THE GROUNDING PRONG
FROM THE PLUG.
Corner Installation
A corner installation will require that the Vent
Adaptor be installed in a top exit position. Horizontal
terminations will then require use of a 90° elbow.
Figs. 5 and 5a show rear termination with 5/8
Simpson Dura-Vent Wall Thimble #1247.
Always disconect the power supply when per-
forming routine service on the fireplace.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
25
635 mm
Figure 1. Cabinet Dimensions.
Figure 2. Minimum horizontal vent
allowance through wall.
16 1/4
410 mm
A
5/8 Vent Adaptor
Header Standoff Height: 36 1/2”
35 3/4
900 mm
6 Vent
Section
Wall Cutout :
4/6 Pipe - 10”x10”
5/8 Pipe - 11”x11”
Observe all vent
and termination
clearance
36 1/2
921 mm
35
890 mm
35 3/4*
910 mm
requirements.
Security Vent:
38
8
200 mm
4
100 mm
970 mm
A = 25 1/4 (645 mm)
Security Termination has no slip adjustibility.
NOTE: DO NOT INSTALL CABINET ON FLOOR SURFACE
LOWER THAN THE FRONTAL HEARTH SURFACE.
* Wallboard Standoff Height
Simpson DuraVent and Amerivent:
A = 25 3/4 (660 mm)
Rear Exit
Top Exit
16 1/4
(415 mm)
16 1/4
(415 mm)
A
38 3/4
(990 mm)
38
(970 mm)
32 3/4
(830 mm)
Horizontal Vent: Minimum depth accomodates the length of
Vent Adaptor and one 6 vent section through wall construction.
16 1/4
21 1/2
Vent Adaptor:
5/8
5/8 Vent
4/6 Vent
(413 mm)
(546 mm)
A =
21 3/4
20
(510mm)
Vertical Vent: Minimum depth includes 1 inch clearance
between Vent Adaptor and combustible wall construction.
Figure 4. Vent Adaptor orientation.
Vent Adaptor:
5/8
21 1/2
4/6
20
Min. Vent
Clearance
A =
WALL OPENING
5/8 VENT
Figure 3. Depth requirement to rear wall.
CUSTOM
MANTEL
CABINET
11 x 11
280 mm x 280 mm
See text for
details.
2
50 mm
9
230 mm
48 1/2
1232 mm
41
1041 mm
49 1/4
1232 mm
Minimum
mantel
shelf
28 1/2
730 mm
43
1092 mm
height to
cover vent
wall
16
410 mm
thimble
56 1/2
1435 mm
Figure 5. Corner framing dimensions.
Figure 5a. Corner Installation - 5/8 vent, rear termination.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Hearth Protection
The GZ550 Acadia is approved for installation
without hearth protection. Combustible materials
may be used on the floor directly under and in front
of the fireplace. NOTE: The floor surface under the
unit must be level with, or higher than, the surface
in front of the unit to allow the fireplace Controls
Door to fully open.
Mantel and Trim Clearance
12 8
4
13 1/2
10 1/2
MANTEL
AREA
DRYWALL
12
9
UPPER TRIM
2 1/2 Max. Depth
7 1/2
4 1/2
Facing and Clearance Requirements
HEADER
The following clearance and hearth specifications
are the minimum requirements for the GZ550
Acadia gas fireplace. Measure clearances from the
steel fireplace cabinet - not the cast iron surround
panels. See Figures 6 - 8.
STANDOFF
TOP OF CABINET
A combustible surface is anything that can burn
(i.e. sheet rock, wallpaper, wood, fabrics etc.). These
surfaces are not limited to those that are visible and
also include materials that are behind non-combus-
tibles.
35
If you are not sure of the combustible nature of
a material, consult your local fire officials. “Fire
Resistant” materials are considered combustible -
they are difficult to ignite, but will burn. “Fire-
rated” sheet rock is also considered combustible.
Maintain the proper clearances to the appliance
to allow adequate flow of ventilation air around
the fireplace.
Figure 7. Minimum Mantel Clearances. Measure
clearances from the top of the fireplace cabinet
before installation of the cast iron surround panels.
Wallboard
Header
TOP TRIM
Standoff
4 1/2
1.2 cm
GZ550 DV
Cabinet
4 1/2
1.2 cm
Standoffs
10
2.55 cm
Figure 8. Minimum Side Wall and Trim Clearance.
Measured from the cabinet, not standoffs or cast iron
panels.
10”
(250 mm)
Figure 6. Header and Side Standoffs
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Vent Requirements
The GZ550 DV Acadia Gas Fireplace is approved for
use with direct vent components produced by the
following manufacturers:
• Simpson Dura-Vent Corporation, 5/8 and 4/6 pipe
• Security Vent Ltd. International, 5/8 and 4/6 pipe
• Amerivent Corporation, 4/6 pipe
Horizontal Overhang
18.
min.
18.
min.
Lowest Discharge
Opening
• Selkirk Metalbestos Corp. MDV Direct Vent Systems
Termination
Cap
Use vent components from a single vent manu-
facturer. Do not combine parts from different
manufacturers in a single installation.
18 min.
The vent termination must fall within the shaded area
designated in the diagrams in Figures 12 - 14.
Venting Guidelines
The minimum height for a vertical termination
cap must be no less than 7' from the top of the
unit. The maximum height must not exceed 35'.
Figure 10. Gas Vent Height Rule: Vertical vent
termination height above roof.
The minimum vent height above the roof or
adjacent walls is specified by major building
codes. Use the Gas Vent Rule as a general guide.
See fig.10. requirements of the approval listing
and the manufacturer’s instructions.
Do not recess the vent terminal into a wall or siding.
Inspect the vent system annually for blockage and
deterioration. If the vent-air intake system is
disassembled for any reason, reinstall according to
the instructions provided for initial installation.
Clearance (airspace) between Vent and Combustibles:
Top - 2” (51 mm)
Sides/Bottom - 1” (25 mm)
Installation of any components not manufactured
or approved by Jøtul or failure to meet all clear-
ance requirements will void all warranties and
may result in property damage, bodily injury, or
loss of life.
Wall Cutout Dimensions:
4/6 Pipe - 10” x 10”
5/8 Pipe - 11” x 11”
Any horizontal run must rise 1/4” per foot.
Install venting in accordance with the vent
manufacturers’ instructions. Never modify any
venting component, or use any damaged venting
product.
IN DESIGNING THE VENT SYSTEM, DO NOT
COUNT THE 45° ELBOW CONNECTED TO THE
VENT COLLAR AS AN ELBOW.
THE GAS APPLIANCE AND VENT SYSTEM MUST BE
VENTED DIRECTLY TO THE OUTSIDE OF THE BUILDING.
DO NOT CONNECT VENT TO A
45° Elbow
6” Vent Section
CHIMNEY SERVING A SOLID FUEL
OR ANOTHER GAS APPLIANCE.
Wall Support
Joint Sealing Requirement:
Apply a 1/8” bead of high-
temperature (750°F) sealant
S
to the male section of the
inner vent pipe. See fig. 9.
The cement should seal
the inner pipe from the
outer pipe.
E
A
L
A
N
T
Wall Termination
Figure 11. Typical minimum horizontal vent
configuration - 5/8 Simpson DuraVent. Do not use
4/6 pipe in this configuration.
Figure 9. Seal each inner joint before joining pipe.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
35
35
Restrictor
Fully Closed
Restrictor
Fully Closed
30
30
Restrictor
2/3 Closed
Restrictor
2/3 Closed
18
18
Restrictor
1/3 Closed
Restrictor
1/3 Closed
10
10
9
9
7
Restrictor
Open
Minimum 7
Height
Both
5/8 Vent
4/6 Vent
Restrictor
Open
Max.Two
Elbows -
90° or 45°
Max.Two 45°
Elbows
10
12
10
5
12
7
Horizontal Run in Feet
Horizontal Run in Feet
Figure 12. Vent Window for vertical termination
using 5/8 or 4/6 pipe.
Figure 13. Vent Window for offset vertical
termination using 5/8 or 4/6 pipe.
Vertical Termination
Figure 14. Minimim
centerline for
horizontal
termination of 4/6
pipe
The vent must terminate within the shaded area
designated on the graphs in Figs. 12 and 13.
• Maximum Elbows - Two 90° or Two 45° (Do not
count the first elbow off the vent collar.)
• Use the restrictor settings indicated in the graph
as general guide. The specific characteristics of
your installation may require different settings.
52
(990 mm)
Horizontal Termination
The vent must terminate within the shaded area
designated in Figs. 15 and 16. (Do not count the first
elbow off the vent collar.)
• Max. Elbows - One 90° or one 45°.
• Use of 4/6 pipe requires a minimum 1 foot rise. Fig. 16.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
12
9
12
9
5
5
1
Max. One 90°
Elbow
Max. One 90°
Elbow
10
5
10
5
12
3
12
3
Horizontal Run in Feet
Horizontal Run in Feet
Figure 15. Horizontal termination -5/8 pipe.
Figure 16. Horizontal Termination - 4/6 Pipe.
Minimum 1 ft. rise required.
Horizontal Termination Clearance
Figure 17. Vent Terminal Clearances - National Fuel Gas Code.
A = Clearance above grade, veranda, porch , deck, or
balcony : *12 inches (30 cm) minimum.
G = Clearance to inside corner: Min. 6 inches, U.S. / *12
inches (30 cm) CAN. We strongly recommend 12 inches,
particularly where windy conditions pevail.
B = Clearance to window or door that may be opened:
Min. 9 inches, U.S. / *12 inches (30 cm) CAN.
We recommend 12in. minimum to prevent condensa-
tion on the window.
H = *Not to be installed above a meter/regulator assembly
within 3 feet (90 cm) horizontally from the center-line
of the regulator.
C = Clearance to permanently closed window:
Min. 9 inches, U.S. / *12 inches (30 cm) CAN
We recommend 12in. minimum to prevent condensa-
tion on the window.
I = Clearance to service regulator vent outlet:
3 feet, U.S. / 6 feet (1.8 m), CAN.
J = Clearance to nonmechanical air supply inlet to building
or the combustion air inlet to any other appliance:
*12 inches (30 cm) minimum.
D = Vertical clearance to ventilated soffit located above
the terminal within a horizontal distance of 2 feet (60 cm)
from the centerline of the terminal: 18 inches
(46 cm) minimum.
K = Clearance to a mechanical air supply inlet: *6 feet
(1.8 m) minimum.
L = ** Clearance above paved sidewalk or a paved driveway
located on public property: *7 feet (2.1 m) min.
E = Clearance to unventilated soffit: *12 inches (46 cm)
minimum.
M = Clearance under veranda, porch, deck, or balcony:
F = Clearance to outside corner: Min. 9 inches, U.S. / *12
inches (30 cm) CAN. We strongly recommend 12 inches,
particularly where windy conditions pevail.
*12 inches (30 cm) minimum. 1
** A vent shall not terminate directly above a sidewalk or driveway
which is located between two single family dwellings and serves
both dwellings.*
*
As specified in CGA B149 Installation Codes. Note: Local Codes
and Regulations may require different clearances.
1
Only permitted if veranda, porch, deck, or balcony, is fully open
on a minimum of two sides beneath the floor.*
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Fireplace Installation
Optional Blower
Install the optional Blower (155630) before
installing the gas supply line.
Figure 18.
Wall Vent Terminal /
Overhang Clearances
2 1/2
12
305
mm
64 mm
3
76 mm
Power Requirement
The blower must be electrically grounded in accor-
dance with local codes or, in the absence of local
codes, with the current NFPA 70- National Electrical
Code or CSA C22.1-Canadian Code.
Variable Vent Restriction
Vent restriction is accomplished by sliding a restric-
tor panel over the combustion air intake ports
located at the back of the firebox. See Fig 19. The
panel is set in a fully open position at the factory.
Use the Vent Window diagrams in Figs. 12-13 as a
starting point to determine the best restriction
setting. Follow these steps to adjust the restriction
as necessary:
A three-prong (grounding) power supply plug is
included for protection against shock hazard and
should be plugged directly into a properly grounded
three-prong receptacle. DO NOT CUT OR REMOVE
THE GROUNDING PRONG FROM THE PLUG.
Blower Function
In the Auto mode, the blower is controlled by a heat
activated switch (snapstat) that will turn the fan on
and off as the firebox heats and cools. Use the
Manual mode to over-ride the snapstat. If the blower
is not needed, place the blower control switch in the
OFF position and the snapstat will not function.
1. Remove the Controls Panel to access the adjust-
ment lever at the rear of the valve compatment.
Simply loosen the two wingnuts that secure the
panel to the cabinet floor and pull the panel
forward. You do not need to disconnect any wires.
CAUTION: Always unplug the Blower when
performing any routine service to the Acadia gas
fireplace.
2. Locate the vent restriction wingnut protruding
from the firebox floor at the rear of the valve
compartment. Loosen the wingnut and push the
lever to the left to increase restriction in one inch
increments, e.g: 1 inch travel = 1/3 closed position.
Installation
1. Loosen the two wingnuts that secure the Control
Panel to the fireplace floor. Pull the panel forward
and swing it to the right to access the rear of the
cabinet. Do not disconnect any wires.
The ideal restrictor setting for a particular vent
system will vary depending on the specific installa-
tion characteristics. Once the fireplace is operating,
further restrictor adjustment may be necessary to
obtain the best performance. See the Operation
chapter of this manual for more information.
2. Insert a rubber grommet at each corner of the
Base Plate as shown in fig. 20.
3. Engage the Blower unit base with the four studs
at the rear of the fireplace cabinet floor. See fig. 21.
Fully Closed
2/3 Closed
4. Insert the Snapstat into the slot in the Snapstat
Bracket and, using the M6 nuts and 10 mm socket,
attach the Control Switch / Snapstat Bracket to
the two studs protruding from the firebox floor.
See fig. 22.
1/3 Closed
Full Open
5. Connect the Blower Wire harness to the switch
connector at the back of the Control Panel and
two other leads to either terminal on the
snapstat.
BLOWER
BURNER
IGNITOR
ON
HI
MANUAL
OFF
M
6. Run the power cord to the duplex receptacle in
the side of the cabinet. Gather slack cord into the
side cavity, away from the plumbing and other
wiring. Reposition and secure the Control Panel.
AUTO
OFF
LO
HI
LO
Figure 19. Vent restrictor adjustment.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
6
Final Cabinet Positioning
1
1. If appropriate, attach the 4/6 Vent Adaptor
Collar:
2
• Remove the 5/8 Collar supplied with the unit.
• Align the 4/6 Collar as shown in fig. 23 and
secure to the unit using the original screws. Be
sure the single round fastener hole is oriented to
the 12 o-clock position for proper vent align-
ment.
4
5
3
6
1. #129374 Fan/Motor Unit- 125 cfm., variable speed
2. #220012 Base Plate
3. #220637 Snapstat (140°F - 120°F)
4. #220989 Snapstat Bracket
1. Side Standoffs: Remove the retainer screws. Using
vise grips or pliers, fold each standoff at the
perforations. Secure each standoff using the
screws previously removed. See fig. 24.
5. #220055 Rubber Grommets, 4
6. #9930 M6 Hex Flange nuts, 2
Figure 20. Blower Kit 155630 contents.
2. Wall Stud Brace: Loosen, bend, and position each
cabinet Retainer Strap for attachment to the
fireplace enclosure. See fig. 24.
3. Locate the fireplace cabinet in its final position
within the enclosure. Confirm that the first 45°
Elbow is correctly aligned for final vent assembly
and secure it to the Vent Collar using 3, #10 sheet
metal screws.
4. Confirm that the cabinet is positioned to align its
forward edge with the finished surface of the
wall facing. The stud braces allow approximately
2 inches of forward adjustment to accommodate
most any facing thickness. Secure the braces to
the enclosure frame.
Figure 21. Blower location.
5. Complete the gas line and electrical power
routing as appropriate for blower and thermo-
stat functions.
Snapstat Bracket
BLOWER
BURNER
IGNITOR
ON
HI
MANUAL
OFF
MANU
OFF
Standoff in shipping position.
AUTO
AUTO
OFF
LO
HI
LO
Figure 22. Install snapstat bracket and switch box.
Remove, bend and
reattach each Standoff.
For correct vent pipe
alignment, be sure the
round hole is oriented to
the 12- o’clock position
Remove, bend and
reattach each Wall
Stud Brace.
Figure 23. 4/6 Vent Collar orientation.
Figure 24. Standoff and Stud Brace orientation.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Connect the Gas Supply
Leak test:
• Mix a 50-50 solution of water and dish soap.
Gas Supply Requirements
• Light appliance- see lighting instructions on page
23 of this manual or on the fireplace’s rating
plate.
ALL INSTALLATIONS MUST COMPLY WITH LOCAL
CODE OR IN THE ABSENCE OF LOCAL CODE, MUST
COMPLY WITH THE MOST RECENT EDITION OF THE
NATIONAL FUEL GAS CODE ANSI Z223.1/NFPA 54 OR
CAN-B149.
• Brush or spray all joints and connections with the
soapy water solution.
• If bubbles appear at any connection or seam or a
gas odor is detected, immediately turn gas
control knob to the OFF position.
Shutoff Valve
All codes require a gas shutoff valve (gas cock)
and union to be installed in the supply line and in
the same room as the appliance. This allows for the
disconnection of the fireplace for servicing and
maintenance. See fig. 25.
Tighten or reconnect the leaking joint and retest
for any gas leaks.
A T-handle gas shutoff valve is required in
Massachusetts in compliance with Code 248CMR.
The fireplace and gas control valve must be
disconnected from the gas supply piping during any
pressure testing of the system at test pressures in
excess of 1/2 psig. For pressures lower than 1/2 psig,
isolate the gas supply by closing the manual shutoff
valve.
Control Valve Connection
The gas supply line connection is made to the
left side of the valve. The gas supply line should be a
minimum 3/8" diameter, or the appropriate size to
provide sufficient gas pressure to the valve regard-
less of the input setting.
Figure 25. Gas supply line fittings.
Gas Pressure
The use of flexible gas appliance connectors is
acceptable in many areas in the U.S. In Canada,
methods vary depending on local code. If local codes
permit, use flexible gas line for ease of installation
and service. For those locales where flexible gas
lines are not permitted, use the 3/8” iron fitting to
make the connection at the left side of the Control
Valve. See Figures 25 and 26.
Proper gas pressure provides a consistent flow
of gas to the appliance and is instrumental in
checking for gas leaks. The gas control valve on the
fireplace is equipped with pressure test points for
gauge connections. The gauge connections are
located on the front of the valve under the On/Off/
Pilot knob. Gauge connections are identified by:
• IN/E for inlet or supply pressure (the amount of
Secure all joints tightly using appropriate tools
and sealing compounds (for propane units, be sure
to use compounds that are propane resistant). Turn
on gas supply and test for gas leaks using a soapy
water solution. Never use an open flame to check
for leaks.
gas coming to the valve.)
• OUT/A for manifold pressure (the amount of gas
that is coming out of the valve to the burner.)
E
A
Figure 26. Pressure test point as located on the
front of the valve.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
DANCE WITH THE MANUFACTURER’S INSTRUCTIONS
AND ALL CODES AND REQUIREMENTS OF THE
AUTHORITY HAVING JURISDICTION. THE INFORMA-
TION STICKER MUST BE COMPLETED BY THE IN-
STALLER AND APPLIED TO THE APPLIANCE AT THE
TIME OF THE CONVERSION. THE QUALIFIED SERVICE
AGENCY PERFORMING THIS WORK ASSUMES RE-
SPONSIBILITY FOR THIS DERATING.
The appliance must be isolated from the gas
supply line by closing its individual manual gas
shutoff valve (gas cock) during any pressure testing
of the gas supply piping system that is equal to or
less than pressures of 1/2 psig (3.5 kPa).
Inlet Pressure
MIN
MAX
Natural Gas: 5.0 WC (1.24 kPa) 11.0 WC (2.74 kPa)
In Canada: This unit has been tested for installation
at high altitudes in accordance with Canadian test
standard CAN/CGA-2.17. THE DERATING SHALL BE
CARRIED OUT IN ACCORDANCE WITH THE REQUIRE-
MENTS OF THE PROVINCIAL AUTHORITIES HAVING
JURISDICTION AND IN ACCORDANCE WITH THE
REQUIREMENTS OF THE CAN1-B-149.1 AND .2
INSTALLATION CODE.
Propane:
12.0 WC (2.98 kPa) 14.9 WC (3.71kPa)
Manifold Pressure
MIN
Natural Gas: 1.2 WC (.29 kPa)
Propane: 2.9 WC (.72 kPa)
MAX
3.8 WC (.94 kPa)
11.0 WC (2.74 kPa)
ALWAYS TEST PRESSURE WITH VALVE CONTROL KNOB
SET ON HIGH. Symptoms of incorrect gas pressure
include:
Derating Procedure
1. Follow Steps 1-4 of the Fuel Conversion procedure
outlined on page 14.
2. Remove the original orifice. Consult Table 1 to
determine the correct orifice size for your eleva-
tion and fuel type. Install the appropriate orifice
included in the high altitude kit.
3. Fill out the high altitude conversion label and
attach to the rating plate or fireplace cabinet floor
See Figure 27.
4. Reassemble the firebox components.
5. It may be necessary to adjust the air shutter on
the burner tube. See the AIR SHUTTER/FLAME
APPEARANCE section of this manual for more
details.
Insufficient gas pressure:
• Small pilot flame which can result in insufficient
millivolts.
• Little variation in flame picture between HI and
LO settings.
• Insufficient gas to support more than one appli-
ance causing nuisance outages or gas surges.
Excessive gas pressure:
• Permanent damage to valve causing complete
appliance shut down.
• Too large a pilot flame resulting in overheating of
the power generator and consequent shut down.
• Sooting due to impingement and/or incorrect fuel
to air mix.
High Altitude Orifice Chart
High Altitude Adjustment
Orifice
Size
Elevation
Fuel
Part No.
Installations located at altitudes from 2000 - 4500 ft.
(610 M - 1370 M), require compensation for the
thinner air (less volume of air per cubic foot). Higher
altitudes affect the atmospheric pressure and heat
value of gaseous fuels. The lower oxygen content in
the air and the lower gas viscosity require the use of
a different orifice to achieve efficient, clean combus-
tion at the burner tube.
0 - 2000 ft.
(0 - 610 m)
Natural Gas
Propane
#38
1.55 mm
129130
220048
2001 - 4500 ft.
(611 - 1370 m)
Natural Gas
Propane
#39
1.50 mm
129367
129146
Table 1. High Altitude Orifice Chart.
THIS STOVE HAS BEEN CONVERTED FOR USE AT AN
ALTITUDE OF: ________________
For high altitude installations consult the local
gas distributor or the authority having jurisdiction
for proper rating methods. If the installer must
convert the unit to adjust for varying altitudes, use
Jøtul High Altitude Kit (#155610-NG / #155611-LP).
Orifice Size: ____________ Manifold Press. _____
Input Btu/Hr. ___________ Fuel Type __________
Date of Conversion ___________
In the U.S: THE DERATING KIT MUST BE INSTALLED
BY AN AUTHORIZED SERVICE TECHNICIAN IN ACCOR-
Figure 27. High Altitude Conversion Label.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Fuel Conversion
The GZ550 DV Acadia Fireplace is designed to for use
with either Natural gas or Propane. It is shipped
from the factory configured to use Natural gas. A
conversion kit is included for conversion to Propane
use if desired. Check the identification label on the
Control Valve to confirm that the correct fuel is used.
Tools required:
1/4” Nut driver, 7/16” and 1/2” open end wrench or
deep well socket, 4 mm allen wrench, Torx t20 or
slotted screwdriver.
Conversion Kit Contents:
WARNING:
• 1 Regulator Tower labeled for Propane
• 3 Regulator Tower Screws
THE CONVERSION KIT IS TO BE IN-
STALLED BY AN AUTHORIZED JØTUL
SERVICE TECHNICIAN IN ACCORDANCE
WITH THE MANUFACTURER’S INSTRUC-
TION AND ALL CODES AND REQUIRE-
MENTS OF THE AUTHORITY HAVING JU-
RISDICTION. FAILURE TO FOLLOW THESE
INSTRUCTIONS COULD RESULT IN SERI-
OUS INJURY OR PROPERTY DAMAGE. THE
QUALIFIED AGENCY PERFORMING THIS
WORK ASSUMES RESPONSIBILITY FOR
THIS CONVERSION.
• 1 Burner Orifice (#38 NG, 1.55 mm LP)
• 1 Pilot Orifice ( #30 for LP, #51 for NG)
• Label A - to be completed and applied to the back
of the fireplace.
• Label B - apply to the fireplace Rating Plate as
designated on the plate.
WARNING: If appropriate, be sure to unplug the
blower before proceeding with this conversion.
IN CANADA:
THE CONVERSION SHALL BE CARRIED
OUT IN ACCORDANCE WITH THE REQUIRE-
MENTS OF THE PROVINCIAL AUTHORITIES
HAVING JURISDICTION AND IN ACCOR-
DANCE WITH THE REQUIREMENTS OF THE
CAN1-B149.1 AND .2 INSTALLATION CODE.
Fuel Conversion Procedure
1. Remove the Glass Frame:
• Follow the removal procedure detailed on page 1.
2. Empty the firebox:
• Lift and remove the Fettle and Logset package.
CAUTION: THE LOGS ARE FRAGILE. Handle them
with care and set aside out of the way.
Cet equipement de conversion sera installe par une
agence qualifiee de service conformement aux
instructions du fabricant et toutes exigences et
codes applicables de l’autorises avoir la juridiction.
Si l’information dans cette Instruction n’est pas
suivie exactement, un fey, explosion ou production
de protoxyde de carbone peut resulter blessure
personnelle de vie. L’agence qualifiee de service est
esponsable de l’installation n’est pas propre et
complete jusqu’a l’operation de l’appareil converti
est cheque suivant les criteres etablis dans les
instructions de proprietaire provisionnees avec
l’equipement.
• Remove the Burner Skirt. Lift and tilt it to clear
the firebox opening. See fig. 28.
3. Change the Burner Orifice:
• Loosen the locknut on the Air Shutter Stem,
located under the firebox floor to the right of the
Control Valve. Pull the stem forward as far as it
will go. This will allow you to disengage the
Burner Assembly. See fig. 29.
• Lift the rear of the Burner Tube and rotate
slightly forward. Slide the tube back enough to
disengage it from the Air Shutter and Burner
Orifice, then lift out. See fig. 30.
• Slide the Air Shutter back out of the way to
expose the orifice. See fig. 31. Using a ½” open
end wrench or deep well socket remove the
burner orifice and replace with the appropriate
orifice, supplied in the kit.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Change the Pilot Orifice:
• FROM WITHIN THE FIREBOX, disengage the
Pilot Hood by releasing the retainer clip as
shown in fig. 32. Using the 4 mm hex key
supplied, unscrew the pilot orifice (counter-
clockwise). Replace with the appropriate
orifice:
#51 for Natural gas
#30 for Propane
Figure 28. Lift the Burner Skirt up and out of the firebox.
Tighten new orifice into the base of the pilot
assembly.
• Replace Pilot Hood by pushing it into the
base.
Air Shutter
Wingnut
Pull Frame Spring
Latch to release.
Pilot Hood
Pilot Orifice
Retainer Clip
Figure 29. Frame latch and air shutter stem location.
PILOT ASSEMBLY
Burner Tube
Air
Figure 32. Pilot Orifice replacement.
Shutter
Figure 30. Move shutter forward to disengage the
burner tube assembly. .
Burner Orifice
Figure 31. Move air shutter back to access the
burner orifice.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Replace the Burner Tube:. Slip the end of the tube
into the Air Shutter and SLIDE TUBE FORWARD TO
COMPLETELY COVER THE BURNER ORIFICE.
6. Adjust the Air Shutter: See fig. 33.
• Slide the shutter BACK to open the inlet, slide
FORWARD to close. The standard settings are:
Natural gas - 1/4” open
Propane - 1/2” open
• Tighten the wing nut on the Air Shutter Stem.
• Replace the Burner Skirt.
7. Change the Regulator: See fig. 34.
Figure 33. Adjust Air Shutter as appropriate. Fully
open position is shown here. Slide shutter forward to
close.
• Using a Torx T-20 screwdriver or small flat head
screwdriver, remove the three specialty screws
from the front of the valve regulator.
• Remove the regulator tower and gasket.
BE SURE TO REMOVE THE BLACK RUBBER GASKET
FROM THE VALVE.
• Install the new variable regulator tower with
the new rubber gasket. Thoroughly tighten new
regulator to valve body.
Be sure to
remove the black
rubber gasket
from the valve.
8. Apply the Conversion Labels:
• Apply LABEL A to the cabinet floor so that it
may be seen by anyone servicing the fireplace.
• Apply LABEL B to the Rating Plate in the space
provided.
Apply small
conversion notice
label here.
9. Reassemble the fireplace, apply gas to the system
and check for gas leaks including all gas lines
before and after the valve. NEVER USE AN OPEN
FLAME TO CHECK FOR GAS LEAKS.
IMPORTANT: Correct gas pressure is essential for
efficient and safe operation. It is important that
the correct gas pressure be established at the
time of the installation. For more details, see the
Gas Pressure section of this manual on page 12.
Figure 34.
Valve Regulator replacement.
WHEN LIGHTING THIS APPLIANCE, ALWAYS REFER TO
THE LIGHTING INSTRUCTIONS ON THE BACK COVER
OF THIS MANUAL.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Wall Thermostat Installation
Remote Control
Use Jøtul Thermostat #129706 or a 750 millivolt DC
two-wire circuit thermostat to automatically control
your fireplace operation. The thermostat should be
placed in the same room as the heater, typically 5’
off the floor. Avoid drafty areas or any area that
may affect the accuracy of the thermostat.
The optional Jøtul Remote Control can be installed
on the Acadia gas fireplace. Using the wire sup-
plied with the remote, connect the remote directly
to the gas control valve. See fig. 36
Connect one receiver lead to the terminal
labelled TH. Connect the other receiver lead to the
terminal labeled TH/TP. DO NOT DISCONNECT ANY
OTHER WIRES FROM THE VALVE, AND DO NOT OVER
TIGHTEN THE TERMINAL SCREWS.
The thermostat should be connected to the
Acadia using a minimum of 16 gauge wire with a
maximum length of 35 feet of wire.
Connect the two thermostat wire leads to the
two lower terminals on the terminal block located
to the right of the ON/OFF/T’STAT switch. Do not
overtighten the connections. IT IS NOT NECESSARY
TO DISCONNECT ANY OTHER WIRES. See Figure 34.
Place the receiver unit under the control valve
on the floor of the fireplace cabinet.
At the thermostat, the two wires should be
connected to the two connections screw on the
thermostat base plate per the manufacturer’s
instructions.
CAUTION:
LABEL ALL WIRES PRIOR TO DIS-
CONNECTION WHEN SERVICING
THE CONTROLS. WIRING ERRORS
CAN CAUSE IMPROPER AND DAN-
GEROUS OPERATION. ALWAYS
VERIFY PROPER OPERATION AFTER
SERVICING THE APPLIANCE.
For thermostatic function, place the ON/OFF/T-
STAT switch in the T-STAT position and the pilot
flame must be lit.
ATTENTION:
AU MOMENT DE L’ENTRETIENDES
COMMANDES, ETIQUETEZ TOUS LES
FILS AVANT LE DEBRANCHEMENT.
DES ERREURS DE CABLAGE
PEUVENT ENTRAIUN
ROCKER
THERMOPILE
SWITCH
ON
FONCTIONNEMENT INADEQUAT ET
DAGEREUX.
TH
TP
OFF
STAT
TH
TP
OPTIONAL
THERMOSTAT
or
REMOTE
CONTROL
VALVE
TERMINAL
BLOCK
Figure 36. ZG550 Acadia Wiring Diagram
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Brick Panel Assembly
Install the optional Brick Panels before placing the
Logset. Place the panels in position in the order as
numbered in fig. 37. No fasteners or tools are
required.
Pull Frame Latches to
Release Frame
Upper Rear Panel,
220031
4
Left Side
Panel,
220997
Right Side
Panel,
220996
Figure 38. Glass Frame latch locations.
1
2
3
Lower Rear Panel,
220030
Figure 37. Panel installation order.
Side
Panel
1. Remove the Glass Frame, if you have not already
done so. Open the lower control panel and locate
the two frame latches under the firebox floor. See
fig. 38
. Pull the latch handle forward to
disengage it from the bottom of the glass frame.
You can then pull the frame out and up off of the
three retainer tabs at the top of the firebox
opening. Set the Glass Frame out of the way.
Burner Skirt
2. Remove the Fettle and Logset. These parts are not
fastened. Simply lift them out of the firebox.
3. Install the Side Panels. Set the bottom edge of
each side panel on the Burner Skirt and against
the firebox wall. Push the panel forward against
the front lip of the firebox opening. See fig. 39.
Figure 39. Install the Side Panels.
4. Install the Lower Rear Panel. Orient the panel so
that the beveled edge is on top and the mortar
joints align with those on the side panels. Set the
bottom edge on the shelf above the restrictor
adjustment slots at the back of the firebox. The
panel should fit snugly between the two side
panels. See fig. 40.
Bevelled Edge
5. Install the Upper Rear Panel. This will also be a
snug fit. Set the panel up high and then carefully
lower it to seat its lower edge against the top of
the other rear panel. The side panels will hold it in
place.
Figure 40. Install Lower Rear Panel.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Logset Assembly
Unpack and arrange the five logs as outlined below.
CAUTION: The logs are fragile. Handle with care.
1
1. Seat Right Log (1) on the pin on the right side of
3
the Burner Skirt. fig. 41.
2
2. Set Rear Log (2) on the pins at the rear of the
Burner Skirt. This log should overlap the back of
the Right Log.
3. Set the Left Log (3) on the pins at the left side of
the Burner Skirt.
4. Set the end of Front Log (4) into the pocket at
the rear of Left Log (3). Engage the other end
with the pin in the middle of the Burner Plate.
Fig. 42.
Figure 41. Install Right Log, Rear Log and Left Log in
that order.
5. Engage the upper end of the Cross-over Log (5)
with the pin in the Rear Log. Fig. 42. Set the
Cross-over Log across the top of the lower end of
the Front Log (4) as illustrated.
6. Spread a layer of ember stones evenly over the
surface of the Burner Plate. Allow for 1/4”
clearance between the stones and the inner
edge of the Burner Skirt. Avoid blocking the pilot
flame area with ember stones. See Fig. 43.
5
7. Replace the Glass Panel Frame: Engage the top
of the frame with the three tabs at the top of
the firebox. Push the bottom of the frame
against the firebox face and pull the Frame
Latches out to engage them with the slots in the
bottom of the frame.
4
Figure 42. Install Front and Cross-over logs as shown.
Pilot
Area
Figure 43. Install ember stones, keeping clearance
around the pilot crossover area.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Surround Assembly
1. Install the Lower Grill / Control Door.
• Secure the hinges to the cabinet frame using
the hex head screws provided in the hardware
bag. fig. 44.
2. Install each of the Side castings onto the
cabinet by engaging the hanger tabs with the
holes in the cabinet frame. See fig. 52 for
orientation.
3. Install the Right and Left Upper Grill plates.
Figure 44. Install the Lower Grill / Control Door.
4. Attach the Inner Panel to the Center Plate. The Inner
Panel may be reversed to show the winter scene.
(Note: Blue Black Panel is enamelled on one side only).
5. Hang the Center Plate in position.
Optional Double Door
The Double Door set is fully assembled and requires
no tools for installation. Use the 4 mm hex key
supplied with the doors to adjust the door alignment
at the eight socket head hinge screws.
Door Installation
Unpack the door set and inspect the parts for
damage. Notify your dealer if any damage is found.
Figure 45. Hang the frame on the cabinet.
You may wish to remove the doors from the
frame to lighten the assembly and ease installation.
They simply lift off of the hinges.
B
The door assembly attaches to the fireplace by
engaging the three slots in the upper frame with the
corresponding steel tabs at the top of the firebox.
See fig. 45.
B
A dimple located on the inside of the frame at
each lower corner engages with corresponding holes
in the glass frame to hold the bottom of the door
assembly securely to the firebox. See A, fig. 46.
A
A
Figure 46. Rear view of door frame.
1. Open the Control Access Door. Hang the door
frame onto the firebox by engaging the tabs with
the holes in the frames. See fig. 45.
2. Push the frame over to one side and engage the
dimple on that lower corner with the hole in the
side of the glass frame. You will feel it lock into
place.
Loosen
screws to
adjust
3. Push the frame assembly over to the opposite side
and push that lower corner down to engage with
the firebox.
door
alignment
Door Alignment Adjustment
You can adjust the door alignment if necessary by
loosening the hinge screws (See B, fig. 46 and fig.
Figure 47. Door adjustment points.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
System Check
1. PURGING THE GAS LINE: When lighting the
appliance for the first time it will take a few
moments to clear the gas line of air. Once this
purge is complete, the appliance will operate as
described in the lighting instructions located on
the fireplace’s rating plate and back cover of this
manual.
Flame Appearance / Air Shutter
Adjustment
THE ACADIA GAS FIREPLACE IS SHIPPED FROM THE
FACTORY EQUIPPED TO USE NATURAL GAS. IF THE
BURNER HAS BEEN CONVERTED FOR USE WITH
PROPANE, IT WILL BE NECESSARY TO ADJUST THE AIR
SHUTTER ON THE BURNER TUBE TO ACHIEVE THE
PROPER GAS TO AIR MIX. See Figure 26.
2. PILOT FLAME: The pilot flame should be steady,
not lifting or floating. The flame should be blue
in color around the pilot hood, with traces of
yellow toward the outer edges. It is imperative
that the pilot flame engulf the top 3/8” of the
thermopile (power generator) and the top 1/8” of
the quick drop out thermocouple. The pilot flame
should project out of the pilot hood 1” at all three
ports. See Figure 48.
WARNING:
AIR SHUTTER ADJUSTMENTS SHOULD ONLY
BE PERFORMED BY A QUALIFIED PROFES-
SIONAL SERVICE TECHNICIAN.
The air shutter adjustment can also help achieve the
desired flame appearance. Generally, flame appear-
ance is a matter of individual preference, however a
warm yellowish flame is most common. See fig. 49.
3. BURNER ADJUSTMENT: Your Jøtul GZ550 Acadia
gas fireplace is equipped with a variable gas
control valve. This valve provides easy adjust-
ment of the flame height appearance and heat
output. To adjust the flame between the HI and
LO setting, rotate the HI/LO knob, located in the
center of the valve face. Flame height will adjust
approximately 1.0” to 1.5” between the HI and LO
settings.
Closing the air shutter - will generate very long
yellow flames resulting in soot. Sooting produces
black deposits on the logs, on the inside walls of
the appliance, and potentially on the exterior
termination cap.
Sooting is caused by incomplete combustion in
the flames and lack of combustion air entering
the air shutter opening.
NO SMOKE OR SOOT SHOULD BE PRESENT. CHECK
LOG PLACEMENT IF ANY SOOT OR SMOKE IS DE-
TECTED. IF SOOT OR SMOKE PERSISTS, THE AIR
SHUTTER MAY NEED TO BE ADJUSTED.
Opening the air shutter - will generate a flame that is
blue and transparent, or an “anemic” flame. This
flame is generally more efficient but not as pretty.
CAUTION:
Pilot Hood
Ignitor
DO NOT ATTEMPT TO ALTER THE FLAME
APPEARANCE BY POSITIONING THE GAS
VALVE IN ANY OTHER POSITION OTHER
THAN THE FULL “ON” POSITION.
1
(25mm)
3/8
(8mm)
Min.
1/8
(3mm)
Min.
Thermopile
Thermocouple
Figure 48 Correct Pilot Flame Pattern
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Air Shutter Adjustment Stem
Air Shutter Adjustment
1. Open the Lower Grill panel and locate the Air
Shutter adjustment stem extending down from
the right side of the firebox floor. See figs. 49.
2. Loosen the locknut and push the stem BACK (to
the rear of the firebox) to open the air inlet
increasing airflow into the burner. Push the stem
FORWARD to decrease the air inlet. Make adjust-
ments in 1/8” (3 mm) increments and allow time
for flame pattern to respond to the new setting.
Retighten the locknut when the desired flame
pattern is established.
3. Reassemble the fireplace including glass assem-
bly. Allow the fireplace to burn 15 -20 minutes on
the HIGH setting, observing the flame continu-
ously.
Figure 49. Air Shutter adjustment location.
4. If the flame appears weak, slow, or sooty, repeat
the process described above until the flame is as
desired.
Air Inlet Settings
Natural Gas - 1/4” open
Propane - 1/2” open
IMPORTANT: Run the fireplace for a minimum
of 15 to 20 minutes to produce an accurate
representation of the flame appearance. This
warm-up should be done before and between
any air shutter adjustment.
Figure 50. Proper flame pattern.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
1. Your Acadia gas fireplace can be operated manu-
ally using the On/Off/T-stat rocker switch or it can
be automatically controlled using an optional
wall-mounted thermostat and/or remote control
device. A separate switch is provided for the
optional forced air blower kit.
Pilot Assembly
Familiarize yourself with the location and func-
tion of the controls. See Figs. 51 and 52.
Gas Control - Used to control the Pilot light and
gas flow from the supply line.
Regulator - Allows you to adjust heat output and
flame intensity.
Piezo Ignitor - Push button pilot light ignition.
Figure 51. The pilot assembly is located at the right
rear corner of the burner plate under the right log.
ON/OFF/ T’STAT Switch - Allows for manual or
thermostatic control of the burner.
Always follow the Lighting Instructions located
on the inside Back Cover of this manual.
2. For the first several hours of operation, it is
common that you will detect some odor as the
metal and manufacturing materials cure under
heat. This condition is temporary and can be
alleviated by allowing plenty of fresh air to
circulate through the area.
Gas Control
Knob
Regulator
3. Condensation may develop on the glass upon
each lighting of the appliance. This “fog” will
disappear as the glass heats.
BURNER
IGNITOR
ON
OFF
TSTAT
4. Keep the controls and the area under the appli-
ance free of debris; vacuum this area frequently.
Always keep the appliance area clear and free
from combustible materials, gasoline and other
flammable liquids.
HI
LO
On/Off/T’stat Switch
Piezo Ignitor
When a vacuum is used on any service for the
fireplace, ALWAYS be sure the fireplace is com-
pletely cold.
Figure 52. Burner Controls.
5. Remember, your fireplace utilizes a continuously
burning pilot flame. Exercise caution when using
household products containing combustible
vapors.
6. CAUTION: DO NOT OPERATE THIS APPLIANCE
WITH THE GLASS REMOVED, CRACKED OR BRO-
KEN. REPLACEMENT OF THE GLASS SHOULD BE
DONE BY A LICENSED OR QUALIFIED SERVICE
PERSON. USE ONLY REPLACEMENT GLASS PRO-
VIDED BY YOUR AUTHORIZED JØTUL DEALER.
NEVER USE ANY SUBSTITUTE MATERIALS.
WARNING:
OBSERVE CAUTION NEAR THE GLASS
PANEL. THE GLASS MAY SHATTER
WHEN STRUCK BY AN OBJECT. ALWAYS
HANDLE THE GLASS PANEL WITH CARE.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
The Acadia gas fireplace and its venting system
should be inspected before use and at least annually
by a qualified service technician.
Glass Panel or Gasket Removal
1. Open the Lower Grill Panel.
2. Release the glass clips at either side of the bottom
of the firebox.
IMPORTANT:
3. Swing the bottom of the glass frame out and lift
to disengage it from the three retainer tabs at the
top of the firebox.
ALWAYS TURN OFF THE GAS SUPPLY TO
THE FIREPLACE AND UNPLUG THE
FORCED AIR BLOWER BEFORE ANY SER-
VICE WORK IS PERFORMED ON THE FIRE-
PLACE.
4. Lay the assembly on a flat surface and carefully lift
the metal tabs that secure the glass panel to the
frame. Remove the old gasket material.
5. Install the new glass panel and gasket in the glass
frame and secure with metal tabs. Do not over
tighten tabs as that may damage the glass.
General Cleaning
The firebox should be vacuumed annually to remove
any surface build up. Use a soft brush attachment
and handle the logs carefully as they are fragile. Be
sure to vacuum or wipe off the pilot assembly and
burner orifice and burner tube.
ONLY USE JØTUL AUTHORIZED PARTS. NEVER SUBSTI-
TUTE NON-JØTUL PARTS ON THIS FIREPLACE.
Glass Care
Clean the glass only when necessary. Wipe the
surface with a clean, dampened, soft cloth. Follow
with a dry, soft towel. Take care not to scratch the
glass surface.
WARNING:
DO NOT USE ABRASIVE CLEANERS ON
THE GLASS. NEVER CLEAN THE GLASS
WHEN IT IS HOT.
Gasket Inspection
It is important that the glass gasket be inspected at
least annually. Examine the ribbon gasket for signs
of deterioration and make sure the gasket has a
positive seal. Replace the gasket if necessary. Refer
to the replacement parts list on page 28.
Figure 53. Replacing the glass gasket.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
RETAIN THIS MANUAL FOR REFERENCE AND
MAKE IT AVAILABLE TO ANYONE USING OR SERVIC-
ING THE FIREPLACE.
SERVICE LOG:
First Year
Name of Technician________________________
Company Name____________________________
Date of service_____________________________
MODEL NAME: GZ 550 DV Acadia Gas Fire-
place
SERIAL NUMBER:__________________________
DATE OF PURCHASE:_______________________
AUTHORIZED DEALER:_____________________
NAME OF INSTALLER:______________________
TYPE OF FUEL:_____________________________
Work Per-
formed____________________________
____________________________________________
____________________________________________
WAS FIREPLACE CON-
VERTED?__________________
SERVICE LOG:
Second Year
NOTES:
Name of Technician________________________
Company Name____________________________
Date of service_____________________________
Work Per-
formed____________________________
____________________________________________
____________________________________________
BLOWER
SERVICE LOG:
Third Year
G
BLU
BK
YEL
W
G
Name of Technician________________________
Company Name____________________________
Date of service_____________________________
BLU
TERM
BK
SNAP STAT
BK
RHEOSTAT
POWER
SUPPLY
BRN
BLU
GRY
BLU
Work Per-
formed____________________________
SWITCH
____________________________________________
____________________________________________
MANUAL OFF AUTO
Figure 54. ZG550 DV Acadia Blower Wiring Diagram
27
Download from Www.Somanuals.com. All Manuals Search And Download.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
GZ 550 DV Acadia Parts
71.
72.
Surround Leg, Right / Matte Black
Surround Leg, Right / Blue Black
Surround Leg, Right / Jøtul Iron
Surround Leg, Left / Matte Black
Surround Leg, Left / Blue Black
Surround Leg,Left / Jøtul Iron
Hang Tab
10395792
10395727
10395785
10395992
10395927
10395985
129680
11730
No.
1.
2
Description
Screw, #8 x 1/2 Sheet metal
Adaptor, 8”
Part Number
117917
129784
129775
9930
3.
4.
Gasket, 8” Adaptor
M6 Hex Nut
73.
74.
75.
5.
Adaptor, 5”
129782
129774
220952
129774
220955
117917
220964
117917
220961
220969
220011
117917
117917
220959
117946
129159
220913
220957
129773
220963
220049
9930
M6 x 12 Hex Bolt
6.
7.
8.
9.
Gasket, 5” Adaptor
Air Intake Manifold
Gasket, 5” Adaptor
Top Shroud, Level 1
Screw, #8 X 1/2” Sheet metal
Support Bracket
Surround Breastplate, Right / Matte Black
Surround Breastplate, Right / Blue Black
Surround Breastplate, Right / Jøtul Iron
Surround Keystone / Matte Black
Surround Keystone / Blue Black
Surround Keystone / Jøtul Iron
Tablet / Matte Black
10395692
10395627
10395685
10395592
10395527
10395585
10396692
10396627
10396685
10395492
10395427
10395485
129471
220546
129670
220790
129668
220520
220044
155831
155830
117117
155612
155612
117975
155612
220987
155612
220783
155612
220954
155612
9930
129390
117917
117975
220388
129464
129463
220395
129152
129130
220048
129673
220950
129760
117917
220004
117917
129772
129759
220956
117917
220009
117917
220962
220947
117917
220789
117917
117986
221102
220702
129766
129765
3094527
76.
77.
78.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
40.
41.
42.
43.
44.
45.
46.
47.
48.
49.
50.
51.
52.
53.
54.
Screw, #8 x 1/2 Sheet metal
Cabinet Wall, Rear
Stand-ott, 1” Framing
Wallstud Brace
Screw, #8 x 1/2 Sheet metal
Screw, #8 x 1/2 Sheet metal
Cabinet Wall, Left
Rivet, .125 x .250
Lanyard, 062 Wire (Rating Plate)
Rating Plate
Cool Air Channel
Air Intake Gasket
Air Intake Restrictor Plate
Latch Assembly
Tablet / Blue Black
Tablet / Jøtul Iron
Surround Breastplate, Left / Matte Black
Surround Breastplate, Left / Blue Black
Surround Breastplate, Left/ Jøtul Iron
Pilot Assembly - NG
Spacer, Pilot Assembly
Gasket, Pilot Assembly
Primary Air Shutter Assembly
Orifice Holder
Gas Valve - NG (50% TD)
Compression Nipple, 3/8 NTP - 5/16
Rheostat Assembly
Wire Harness Assembly
M6 x 20 Hex Bolt
Tube Holder, Cast Iron
Venturi Tube
M6 Wingnut
M6 AS Series Fastener
Gasket, Air Intake Restrictor
Burner Base, Cast Iron
Subfloor - Burner Skirt
Gasket, Burner
Exhaust Baffle
Burner Plate Assembly
M6 Hex Nut
Flex Tube, 5/16” x 14”
#8 x 1/2” Sheet metal Screw
M6 Wingnut
Cover Plate, Primary Air Restrictor
Compression Nut - 5/16
Compression Sleeve - 5/16
Gasket, Cover Plate
Jam Nut
Orifice, #38 - NG
Orifice, 1.55 - LP
Gasket, Heat Exchanger
Heat Exchanger
79.
80.
81.
82.
83.
84.
85.
86.
87.
88.
89.
90.
91.
92.
93.
94.
M6 Hex Nut
M6 Hex Nut
M6 Wingnut
9930
117975
117967
117130
220958
117911
220945
220930
117922
129154
129679
117920
3902573
117921
129729
129730
220717
220709
220703
220944
117922
12979392
117921
901043
117970
220574
117917
10395892
10395827
10395885
117970
154987
129124
220042
129757
220957
220960
11039627
10396727
129680
11730
M6 x 12 Flat Head Phillips Screw
M6 x 12 Hex Bolt
Cabinet Base
10-32 x 3/8 Phillips Screw
Valve Bracket
Terminal Block Bracket
M4 Hex Nut
Terminal Block, 2 Pole
Igniter Bracket
M4 x 8 Phillips Screw
Ignitor
M4 x 12 Phillips Screw
Knob Extension, On/Off
Knob Extension, Hi/Lo
Rheostat Nut
Knob, Rheostat Control
On / Off Switch
Controls Board
M4 Hex Nut
Hinge Adaptor
M4 x 10 Hex Bolt
Control Door Hinge
M5 x 10 Screw
Lanyard, .062 Wire - Control Door
Screw, #8 x 1/2 Sheet metal
Control Door - Matte Black
Control Door - Blue Black
Control Door - Jøtul Iron Gray
M5 x 10 Screw
Ceramic Glass, Replacement (inc. gasket)
Gasket, Glass Tadpole
Glass Clip, Tinnerman
Glass Frame
95.
96.
97.
98.
99.
100.
101.
102.
103.
104.
105.
106.
107.
108.
109.
110.
111.
112.
113.
114.
115.
116.
117.
118.
119.
120.
121.
122.
123.
124.
125.
126.
127.
128.
129.
130.
131.
Glass Frame Hanger
#8 x 1/2” Sheet metal Screw
Relief Door Guide
#8 x 1/2” Sheet Metal Screw
Gasket, Relief Door
Relief Door
55.
56.
57.
58.
59.
60.
61.
62.
63.
64.
65.
66.
67.
68.
69.
70.
Top Shroud, Level 2
#8 x 1/2” Sheet Metal Screw
Keystone Heat Shield
#8 x 1/2” Sheet Metal Screw
Cabinet Top
Firebox
#8 x 1/2” Sheet Metal Screw
Sheetrock Standoff
#8 x 1/2” Sheet Metal Screw
#8 x 3/4” Sheet Metal Screw
Air Deflector, Burner Skirt
Ember Stones, 4 oz. *
Thermocouple *
Cool Air Channel
Cabinet Wall, Right
Fettle, Blue Black Enamel
Andiron, Blue Black Enamel
Hang Tab
M6 x 12 Hex Bolt
Log, Left
Log, Front
Log, Cross-over
Log, Right
Log, Rear
220993
220995
220701
220994
220992
Electrode *
Thermopile *
* not illustrated
29
Download from Www.Somanuals.com. All Manuals Search And Download.
GZ 550 DV Optional Accessories
• Antique Brick Kit ............................................ 155805
• Two Speed Blower, 125 / 60 c.f.m. ............ 155630
• 4” x 6-5/8” Adaptor Kit ................................ 154974
• High Altitude Conversion Kit - NG ........... 155610
• High Altitude Conversion Kit - LP ............. 155611
• Fuel Conversion Kit - LP................................ 155594
• Fuel Conversion Kit - NG.............................. 155595
• Wall Thermostat ............................................ 750003
• Remote Control .............................................. 129706
• QuickFace Fronts w/ Screen
Steel Rectangular, Matte Black.................. 154964
Steel Arch, Matte Black ................................ 154965
Brushed Stainless Steel, Rectangular ...... 154968
Brushed Stainless Steel Arch...................... 154969
• Arched Double Doors, Matte Black .......... 350560
• Arched Double Doors, Blue Black.............. 350561
• Double Door Basket Screen ........................ 154973
30
Download from Www.Somanuals.com. All Manuals Search And Download.
LIGHTING INSTRUCTIONS
FOR YOUR SAFETY, READ BEFORE LIGHTING.
WARNING:
IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY
RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE.
• If your gas supplier cannot be reached, call the
fire department.
A. This appliance has a pilot which must be lit
by hand. When lighting the pilot, follow
these instructions exactly.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will
not push in or turn by hand, do not try to repair
it. Call a qualified technician. Force or attempted
repair may result in a fire or explosion.
B. BEFORE LIGHTING, smell all around the
appliance area for gas. Be sure to smell next
to the floor because some gas is heavier than
air and will settle to the floor.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance and to
replace any part of the control system and any
gas control which has been under water.
WHAT TO DO IF YOU SMELL GAS:
• Extinguish any open flame.
• Open windows.
• Do not light any appliance.
• Do not touch any electrical switches.
• Do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
7. Push in gas control knob slightly and turn counter-
clockwise to“PILOT”.
2. Access the lower controls.
8. Push in control knob all the way and hold in.
Immediately light the pilot by triggering the spark
ignitor (push the red button repeatedly) until pilot
lights. Continue to hold the control knob in for
about one minute after
3. Turn the stove ON/OFF switch to“OFF”, or set the
thermostat to lowest setting (if used).
4. Confirm that the gas supply line shut-off valve is open.
the pilot lights. Release
knob and it should
spring back. The pilot
Control
Knob
should remain lit. If it
goes out, repeat Steps 5
through 8.
• If knob does not
return when released,
Pilot Assembly
Control Valve
stop and immediately call your service technician
or gas supplier.
5. Push in gas control knob slightly and turn clockwise
to“OFF”.
• If pilot will not stay lit after several tries, turn
the control knob to OFF and call your service
technician or gas supplier.
NOTE: Knob cannot be turned from“PILOT”to“OFF”
unless the knob is pushed in slightly. Do not force.
6. Wait five (5) minutes to clear out any gas. If you then
smell gas, STOP! Follow“B”in the safety information
above on this page. If you do not smell gas, go to the
next step.
9. Turn gas control knob counterclockwise
to“ON”.
10.Turn the stove ON/OFF switch to“ON”, or set
thermostat (if used) to desired temperature.
TO TURN OFF GAS TO THE APPLIANCE:
1. Turn ON/OFF switch to”OFF”. The pilot will remain lit for
3. Access the lower controls.
4. Depress gas control knob slightly and turn clock-
wise to“OFF”. Do not force.
normal service.
2. For complete shutdown, turn ON/OFF switch to“OFF”.
Download from Www.Somanuals.com. All Manuals Search And Download.
This appliance must be installed in conformance with local and national building regulations. Before
beginning the installation, it is important that the these instructions be carefully read and understood.
Jøtul maintains a policy of continual product development. Consequently, products may differ in
specification, color or type of accessories from those illustrated or described in various publications.
Jøtul vise sans cesse a ameliorer ses produits. C’est pourquoi, il se reserve le droit de modifier les
specifications, couleurs etequipement sans avis prelable.