Johnson Controls Furnace TM9V060B12MP11 User Manual

QUICK REFERENCE GUIDE  
96%TWO STAGE MULTI-POSITION RESIDENTAL  
GAS FURNACES (33” TALL)  
NOTES:  
This document does not replace the installation instructions, which must be referred to for  
detailed information.  
1. If the furnace is equipped with NOx screens and is to be  
used with LP (propane) gas, the screens must be removed  
prior to start-up.  
7. To measure total static pressure, add supply duct pressure  
to the return duct pressure, add pressure drop across the ‘A’  
coil, and add pressure drop across the filter. Ignore negative  
signs on the readings.  
SUPPLY END  
23.8”  
RETURN END  
2” Diameter  
Vent Connection  
Outlet  
.56”  
2. Drip leg in the gas line must be installed.  
3”  
8. Inlet gas pressure should be 7” w.c. for natural gas and 11”  
w.c. for propane. Nominal manifold gas pressure is 3.5” w.c.  
for natural gas and 10” w.c. for propane at max. input.  
3. The furnace controls require correct polarity on the power  
supply and a proper ground.  
DURING INSTALLATION,  
DOORS MUST REMAIN ON  
FURNACE WHEN MOVING  
OR LIFTING.  
4. Y & G must be connected to the control board for cooling  
operation.  
B
Combustion  
Air Inlet  
9. For downflow application the vent blower must be rotated 90  
left or right as shown.  
B
5. External filters are required on all configurations.  
Clips can be flipped  
into the up position  
for coil cabinet or  
plenum attachment  
6. Electrical or gas entry is available on both casing sides.  
.56”  
.56”  
24.25”  
Airflow CFM (Bottom Return without Filters)  
20”  
Minimum Wire  
Size awg @ 75'  
One-Way  
Maximum  
Over Current  
Protection  
Models  
0.5" ESP (Nominal)  
Combustion Air Inlet  
Combustion Air Inlet  
*D-A**  
600  
*C-A**  
690  
*B-A**  
1000  
1000  
1175  
1160  
1605  
1595  
*A-B**  
1305  
1290  
1670  
1655  
2215  
2180  
TM9V060B12MP11  
TM9V080B12MP11  
TM9V080C16MP11  
TM9V100C16MP11  
TM9V100C20MP11  
TM9V120D20MP11  
14  
14  
14  
14  
12  
12  
15  
15  
15  
15  
20  
20  
Condensate Drain  
(Downflow)  
Gas Pipe  
Entry  
Condensate Drain  
(Downflow)  
600  
680  
A-COIL  
Vent Connection  
Outlet  
850  
905  
Electrical  
Entry  
Vent Connection  
Outlet  
870  
910  
Condensate  
Drain  
960  
1155  
1160  
23”  
960  
Thermostat  
Wiring  
3
Input  
Rate  
Time For 1 ft Natural Gas  
Total Unit Air Temp. Rise Air Temp. Rise  
Amps  
Optional Return Air  
Cutout (Either side)  
14”  
3
Models  
(1030 Btu/Ft ) Seconds  
Max Input °F  
Min Input °F  
Max  
Min  
(On Max. Rate)  
1”  
TM9V060B12MP11  
TM9V080B12MP11  
TM9V080C16MP11  
TM9V100C16MP11  
TM9V100C20MP11  
TM9V120D20MP11  
60,000  
80,000  
80,000  
21,000  
28,000  
28,000  
9
35 - 65  
35 - 65  
35 - 65  
35 - 65  
35 - 65  
35 - 65  
35 - 65  
30 - 60  
35 - 65  
30 - 60  
35 - 65  
35 - 65  
62  
46  
46  
37  
37  
31  
33”  
9
28.5”  
29.5”  
1.5”  
12  
12  
14  
14  
100,000 35,000  
100,000 35,000  
120,000 42,000  
RIGHT SIDE  
LEFT SIDE  
Follow all national and local codes and standards in addition to this document.  
The installation must comply with regulations of the serving gas supplier, local building,  
heating, plumbing, and other codes. In absence of local codes, the installation must comply  
with national codes and all authorities having jurisdiction.  
Other airflows are available. see Tech Guide for all CFM options.  
* Cool Tap.  
A
FRONT  
** Adjustment Tap.  
LED INDICATOR  
CLEARANCES  
DIMENSIONS  
Slow Green Flash - Normal operation in standby mode.  
Slow Amber Flash - Normal operation with call for cooling.  
Two Amber Flashes - Normal operation with call for heat.  
Application  
Top  
Upflow  
Downflow  
Horizontal  
Cabinet Size  
A (in)  
17-1/2"  
21"  
B (in)  
1"  
0"  
0"  
0"  
0"  
0"  
0"  
0"  
0"  
0"  
0"  
All 'B' Cabinet Furnaces  
All 'C' Cabinet Furnaces  
All 'D' Cabinet Furnaces  
16-3/8"  
19-7/8"  
23-3/8"  
Vent  
0"  
Three Amber Flashes - Normal operation, burner is on at end of  
thermostat cycle.  
Rear  
0"  
24-1/2"  
Side  
1"  
0"  
Six Amber Flashes - Normal operation with call for heat pump  
heating.  
Front*  
1
Any Red Flash - Fault condition. NOTE: 4 or 5 flashes may indi-  
cate a blown fuse on the circuit board.  
Floor  
Closet  
Combustible  
Combustible  
Yes  
Combustible  
Yes  
No  
Yes  
No  
Line Contact  
Yes  
Subject to change without notice. Printed in U.S.A.  
Copyright © 2009 by Johnson Controls, Inc. All rights reserved.  
438336-URG-A-0209  
Supersedes: Nothing  
1. For combustible floors only when used with special  
sub-base.  
*438336*  
* 24" clearance in front and 18" on side recommended for  
service access.  
Johnson Controls Unitary Products  
5005 York Drive  
All furnaces approved for alcove and attic installation.  
Norman, OK 73069  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Infinity Speaker PS210W User Manual
Ingersoll Rand Water Pump 650311 X 650312 X User Manual
Invacare Patio Furniture 1171786 User Manual
JA Audio Satellite TV System 9902S User Manual
Jabra Projector Accessories SP CEIL 012 User Manual
JVC Security Camera VN H217U User Manual
Keating Of Chicago Fryer 7 05 User Manual
Kenmore Freezer 5966523403 User Manual
KitchenAid Cooktop xgcd807x User Manual
KitchenAid Garbage Disposal KBDS100T0 User Manual