Johnson Controls Air Conditioner PC090 THRU 240 User Manual

R-410A  
MODELS: PC090 Thru 240  
PD180 Thru 240  
7.5 - 20 Ton  
60 Hertz  
TABLE OF CONTENTS  
Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Crankcase Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Heating Sequence of Operation . . . . . . . . . . . . . . . . . . . . 20  
LIST OF TABLES  
1
5
PC090 - 240 and PD180 - 240 Physical Data. . . . . . . . . . 4  
Electrical Data - Outdoor Unit - HP Without Powered  
11 PD180 thru 240 Unit Control Board Flash Codes. . . . . . 22  
6
Electrical Data - Outdoor Unit - HP With Powered  
LIST OF FIGURES  
3
9
Fan Orientation, Control Box End . . . . . . . . . . . . . . . . . 21  
Typical Field Wiring Diagram - NC090 Air Handling Unit  
Typical Field Wiring Diagram - NC120 thru 240 Evaporator  
4
6
Typical Field Wiring Diagram - ND180 thru 240  
PC/PD180 & PC/PD240 Unit Dimensions and Piping  
8
430645-YIM-D-0610  
Download from Www.Somanuals.com. All Manuals Search And Download.  
430645-YIM-D-0610  
Safety Considerations  
Reference  
Installer should pay particular attention to the words: NOTE,  
CAUTION, and WARNING. Notes are intended to clarify or  
make the installation easier. Cautions are given to prevent  
equipment damage. Warnings are given to alert installer that  
personal injury and/or equipment damage may result if  
installation procedure is not handled properly.  
This instruction covers the installation and operation of the  
basic condensing unit. For refrigerant piping installation  
instructions refer to document 247077 “Application Data -  
General Piping Recommendations for Split System Air  
Conditioning and Heat Pumps”. For information on the  
installation and operation of the evaporator blower units, refer  
to Instruction Manual No. 508526.  
All accessories come with a separate Installation Manual.  
Renewal Parts  
Improper installation may create a condition where the  
operation of the product could cause personal injury or  
property damage. Improper installation, adjustment,  
alteration, service or maintenance can cause injury or  
property damage. Refer to this manual for assistance or  
for additional information, consult a qualified contractor,  
installer or service agency.  
Contact your local Source 1 Center for authorized replacement  
parts.  
Agency Approvals  
Design certified by CSA as follows:  
1. For use as a cooling/heating unit.  
2. For outdoor installation only.  
Before performing service or maintenance operations on  
unit, turn off main power switch to unit. Electrical shock  
could cause personal injury. Improper installation,  
adjustment, alteration, service or maintenance can  
cause injury or property damage. Refer to this manual.  
For assistance or additional information consult a  
qualified installer, service agency or the gas supplier.  
Inspection  
As soon as a unit is received, it should be inspected for possible  
damage during transit. If damage is evident, the extent of the  
damage should be noted on the carrier’s freight bill. A separate  
request for inspection by the carrier’s agent should be made in  
writing.  
This product must be installed in strict compliance with  
the enclosed installation instructions and any applicable  
local, state and national codes including, but not limited  
to, building, electrical, and mechanical codes.  
This system uses R-410A Refrigerant which operates at  
higher pressures than R-22. No other refrigerant may be  
used in this system. Gage sets, hoses, refrigerant  
containers and recovery systems must be designed to  
handle R-410A. If you are unsure, consult the  
equipment manufacturer. Failure to use R-410A  
compatible servicing equipment may result in property  
damage or injury.  
Johnson Controls Unitary Products  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
430645-YIM-D-0610  
Physical Data  
Table 1: PC090 - 240 and PD180 - 240 Physical Data  
Models  
Component  
PC090  
PC120  
10  
PC180  
15  
PD180  
15  
PC240  
20  
PD240  
20  
Nominal Tonnage  
REFRIGERANT  
Refrigerant type  
Holding charge (lb)  
7.5  
R-410A  
1.0  
R-410A  
1.0  
R-410A  
1.0  
R-410A  
1.0  
R-410A  
1.0  
R-410A  
1.0  
1
System #1  
System #2  
23.9  
---  
27.5  
---  
54.0  
---  
27.0  
60.0  
---  
34.0  
2
Operating Charge (lb)  
27.0  
34.0  
DIMENSIONS (inches)  
WEIGHTS (lb)  
Length  
Width  
59.1  
31.9  
44.5  
59.1  
31.9  
50.0  
59.1  
64.1  
44.5  
59.1  
64.1  
44.5  
59.1  
64.1  
50.0  
59.1  
64.1  
50.0  
Height  
Shipping  
421  
430  
543  
574  
947  
968  
921  
942  
1116  
1152  
1090  
1126  
Operating  
3
COMPRESSORS  
Type  
Single Scroll  
1
Tandem Scroll Tandem Scroll  
Single Scroll  
2
Tandem Scroll  
1
Single Scroll  
2
Quantity  
Cooling  
1
1
System #1  
System #2  
System #1  
System #2  
7.5  
---  
1
10  
---  
2
15  
---  
2
7.5  
7.5  
1
20  
---  
2
10  
10  
1
Nominal Capacity (Tons)  
Capacity Stages  
---  
---  
---  
1
---  
1
Heating  
Nominal Capacity (Tons)  
Capacity Stages  
System #1 & #2  
System #1 & #2  
7.5  
1
10  
1
15  
1
15  
1
20  
1
20  
1
SYSTEM DATA  
No. Refrigeration Circuits  
Suction Line OD (in.)  
Liquid Line OD (in.)  
1
1
1
2
1
2
1 1/8  
5/8  
1 3/8  
7/8  
1 5/8  
7/8  
1 3/8  
5/8  
1 5/8  
7/8  
1 3/8  
7/8  
OUTDOOR COIL DATA  
Face area (Sq. Ft.)  
23.8  
2
29.0  
2
47.5  
2
47.5  
2
58.1  
2
58.1  
2
Rows  
Fins per inch  
20  
20  
20  
20  
20  
20  
Tube diameter (in./MM)  
Circuitry Type  
Refrigerant Control  
0.38 / 10  
Interlaced  
TXV  
0.38 / 10  
Interlaced  
TXV  
0.38 / 10  
Interlaced  
TXV  
0.38 / 10  
Interlaced  
TXV  
0.38 / 10  
Interlaced  
TXV  
0.38 / 10  
Interlaced  
TXV  
CONDENSER FAN DATA  
No. Fans / Diameter (in.)  
Type  
2/24  
Axial  
Direct  
1
2/24  
Axial  
Direct  
1
4/24  
Axial  
Direct  
1
4/24  
Axial  
Direct  
1
4/24  
Axial  
Direct  
1
4/24  
Axial  
Direct  
1
Drive type  
No. speeds  
System #1  
System #2  
2
2
4
2
4
2
Number of motors  
Motor HP (ea.)  
---  
---  
---  
2
---  
2
1/3  
3/4  
1/3  
1/3  
3/4  
3/4  
4
Rotation  
CW  
850  
7500  
---  
CW  
1100  
9800  
---  
CW  
850  
15000  
---  
CW  
850  
7500  
7500  
CW  
1100  
19600  
---  
CW  
1100  
9800  
9800  
RPM  
System #1  
System #2  
Nominal CFM  
1. Holding Charge is the amount in the unit as shipped from the factory.  
2. Includes matched evaporator unit with 25 ft of piping.  
3. All Compressors include crankcase heater.  
4. When viewing the shaft end of the motor.  
4
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
430645-YIM-D-0610  
3. The heat pump and the evaporator should be positioned to  
minimize the number of bends in the refrigerant piping.  
Table 2: Unit Application Data  
208/230-3-60  
187/252  
432/504  
540/630  
4. The heat pump should be as close to the evaporator as  
practical.  
1
Voltage Variation  
Min. / Max.  
460-3-60  
575-3-60  
5. The heat pump should not be installed where normal  
operating sounds may be objectionable.  
Ambient Air on Condenser Coil  
40°F/125°F  
2
6. The evaporator should be located within the building, either  
outside or inside the conditioned space.  
Min. /Max.  
Suction Pressure at Compressor and  
Corresponding Temp. at Saturation  
Min. / Max.  
101.6 psig / 156.6 psig  
32.0 ºF / 55.0 ºF  
Rooftop Locations  
Be careful not to damage the roof. Consult the building  
contractor or architect if the roof is bonded. Choose a location  
with adequate structural strength to support the unit.  
1.Utilization range “A” in accordance with ARI Standard 110.  
2.These units can operate in an ambient temperature of  
125°F providing the wet bulb temperature of the air enter-  
ing the evaporator coil does not exceed 67°F. Unit can  
operate to 0°F if equipped with a low ambient kit.  
The heat pump must be mounted on level supports. The  
supports can be channel iron beams or wooden beams treated  
to reduce deterioration.  
Installation  
Minimums of two (2) beams are required to support each unit.  
The beams should: (1) be positioned perpendicular to the roof  
joists. (2) Extend beyond the dimensions of the section to  
distribute the load on the roof. (3) Be capable of adequately  
supporting the concentrated loads at the corners. These beams  
can usually be set directly on the roof. Flashing is not required.  
Limitations  
These units must be installed in accordance with all national  
and local safety codes. If no local codes apply, installation must  
conform to the appropriate national codes. Units are designed  
to meet National Safety Code Standards. If components are to  
be added to a unit to meet local codes, they are to be installed  
at the dealer's and/or the customer's expense.  
NOTE: On bonded roofs, check for special installation  
requirements.  
Ground Level Locations  
Location  
It is important that the units be installed on a substantial base  
that will not settle, causing strain on the refrigerant lines and  
possible leaks. A one-piece concrete slab with footers that  
extend below the frost line is recommended. The slab should  
not be tied to the building foundation, as noise will telegraph  
through the slab.  
Use the following guidelines to select a suitable location for  
both the condensing unit and the evaporator.  
1. The heat pump is designed for outdoor installation only.  
2. The condenser fans are the propeller type and are not  
suitable for use with ductwork in the condenser air stream.  
Johnson Controls Unitary Products  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
430645-YIM-D-0610  
Table 3: Corner Weights & Center of Gravity  
Weight (lbs.)  
Model  
Center of Gravity (in.)  
4 Point Load Location (lbs.)  
Shipping  
421  
Operating  
430  
X
Y
A
B
C
D
87  
PC090  
PC120  
PC180  
PD180  
PC240  
PD240  
17.3  
16.4  
32.5  
34  
32.1  
31.2  
33  
32.3  
33  
32.5  
30.8  
31.8  
110  
153  
266  
243  
300  
311  
130  
161  
274  
275  
301  
295  
103  
134  
217  
225  
276  
253  
543  
947  
921  
1116  
1090  
574  
968  
942  
1152  
1126  
127  
211  
199  
275  
267  
LEFT  
A
D
LEFT  
DIM X  
A
B
D
C
CG  
DIM X  
CG  
FRONT  
FRONT  
REAR  
REAR  
WIDTH  
WIDTH  
DIM Y  
LENGTH  
RIGHT  
PC090, PC120  
B
C
DIM Y  
LENGTH  
RIGHT  
PC180, PD180,  
PC240, PD240  
Figure 1: Corner Weights & Center Of Gravity  
NOTE: Front of unit is considered the side having the control  
Holes are provided in the base rails for bolting the unit to its  
foundation.  
box.  
Concrete piers can also support ground level units. These piers  
should (1) extend below the frost line, (2) be located under each  
of the section's four corners, and (3) be sized to carry the load  
of the corner it supports.  
For ground level installations, precautions should be taken to  
protect the unit from tampering and unauthorized persons from  
injury. Screws on access panels will prevent casual tampering.  
Further safety precautions such as a fenced enclosure or  
locking devices on the panels may be advisable. Check local  
authorities for safety regulations.  
On either rooftop or ground level installations, rubber padding  
can be applied under the unit to lessen any transmission of  
vibration.  
6
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
430645-YIM-D-0610  
LENGTH OF FORKS MUST BE A MINIMUM OF 60 INCHES.  
Clearances  
The unit must be installed with sufficient clearance for air to  
enter the condenser coils, for air discharge and for servicing  
access. See Table Table 4 for clearances.  
Spreaders, longer than the largest dimension across the  
unit must be used across the top of the unit.  
NOTE: Additional clearance is required to remove the  
compressors out the back of the unit.  
Table 4: Minimum Clearances  
Clearance Description  
Distance in Inches  
Overhead (Top)  
Front  
120  
36  
36  
30  
30  
0
Before lifting a unit, make sure that its weight is  
distributed equally on the cables so that it will lift evenly.  
Rear  
Left Side  
Right Side  
1
Bottom  
1.In all installations where snow accumulates and winter oper-  
ation is expected, additional height must be provided to  
insure normal condenser airflow.  
Do not permit overhanging structures or shrubs to  
obstruct condenser air discharge.  
Rigging  
Exercise care when moving the unit. Do not remove any  
packaging until the unit is near the place of installation. Rig the  
unit by attaching chain or cable slings to the lifting holes  
provided in the base rails. Spreader bars, whose length  
exceeds the largest dimension across the unit, MUST be used  
across the top of the unit.  
Figure 2: Typical Rigging  
The unit may be moved or lifted with a forklift. Slotted openings  
in the base rails are provided for this purpose.  
Johnson Controls Unitary Products  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
430645-YIM-D-0610  
Power Wiring  
Check the available power and the unit nameplate for correct  
voltage. Run the necessary number of properly sized wires to  
the unit. Provide a disconnect switch (if not included with the  
unit) and fusing as required (Factory disconnect is a fused  
disconnect /breaker). Route the conduit through the large  
knockout located near the electrical box. See Table 5 for  
Electrical Data.  
Do not leave the system open to the atmosphere. Unit  
damage could occur due to moisture being absorbed by  
the POE oil in the system. This type of oil is highly  
susceptible to moisture absorption  
POE (polyolester) compressor lubricants are known to cause  
long term damage to some synthetic roofing materials.  
The disconnect switch may be bolted to the side of the unit but  
not to any of the removable panels; which would interfere with  
access to the unit. Make sure that no refrigerant lines will be  
punctured when mounting the disconnect switch, and note that  
it must be suitable for outdoor installation.  
Exposure, even if immediately cleaned up, may cause  
embrittlement (leading to cracking) to occur in one year  
or more. When performing any service that may risk  
exposure of compressor oil to the roof, take precautions  
to protect roofing.  
All power and control wiring must be in accordance  
with National and Local electrical codes.  
Procedures which risk oil leakage include, but are not limited to,  
compressor replacement, repairing refrigerant leaks, replacing  
refrigerant components such as filter drier, pressure switch,  
metering device or coil.  
Control Wiring  
Route the necessary low voltage control wires from the  
Simplicity™ control board to the thermostat and also between  
the terminal blocks inside the heat pump and evaporator control  
boxes. Refer to Figures 3 thru 6 for field wiring diagrams.  
The unit is shipped with compressor mounting bolts which are  
factory adjusted and ready for operation.  
Compressors  
The scroll compressors used in this product are specifically  
designed to operate with R-410A Refrigerant and cannot be  
interchanged.  
Do not loosen compressor mounting bolts.  
Phasing  
Three-phase, scroll compressors operate in only one direction.  
If the scroll is drawing low amperage, has similar suction and  
discharge pressures, or is producing a high noise level, the  
scroll is misphased. Change the incoming line connection  
phasing to obtain the proper rotation.  
This system uses R-410A Refrigerant which operates at  
higher pressures than R-22. No other refrigerant may be  
used in this system.  
The compressor also uses a polyolester (POE oil), Mobil 3MA  
POE. This oil is extremely hydroscopic, meaning it absorbs  
water readily. POE oil can absorb 15 times as much water as  
other oils designed for HCFC and CFC refrigerants. Take all  
necessary precautions to avoid exposure of the oil to the  
atmosphere.  
Scroll compressors require proper rotation to operate  
properly. Failure to check and correct rotation may result  
in property damage.  
8
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
430645-YIM-D-0610  
Electrical Data  
Table 5: Electrical Data - Outdoor Unit - HP Without Powered Convenience Outlet  
Compressors  
Outdoor Fan Motor  
Pwr Conv Outlet  
Minimum  
Maximum  
Fuse Size  
(A)  
Model  
Circuit  
Ampacity  
Power  
RLA  
Qty  
MCC  
LRA  
Power  
FLA  
(each)  
1
2
HP Qty  
FLA  
Supply  
(each) (each) (each)  
Supply  
208/230-1-60  
460-1-60  
208/230-3-60  
460-3-60  
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
25.0  
12.2  
9.0  
39  
19  
164  
100  
78  
1/3  
1/3  
1/3  
3/4  
3/4  
3/4  
1/3  
1/3  
1/3  
1/3  
1/3  
1/3  
3/4  
3/4  
3/4  
3/4  
3/4  
3/4  
2
2
2
2
2
2
4
4
4
4
4
4
4
4
4
4
4
4
2.1  
1.2  
0.9  
3.0  
1.6  
1.4  
2.1  
1.2  
0.9  
2.1  
1.2  
0.9  
3.0  
1.6  
1.4  
3.0  
1.6  
1.4  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
35.5  
17.6  
13.1  
46.8  
23.5  
18.0  
64.7  
32.2  
24.0  
64.7  
32.2  
24.0  
79.8  
44.0  
32.9  
79.8  
44.0  
32.9  
45  
25  
20  
60  
30  
20  
80  
40  
30  
80  
40  
30  
100  
60  
45  
100  
60  
45  
PC090  
575-3-60  
14  
575-1-60  
208/230-3-60  
460-3-60  
18.1  
9.0  
28.3  
14.0  
10.6  
39  
137  
62  
208/230-1-60  
460-1-60  
PC120  
PC180  
PD180  
PC240  
PD240  
575-3-60  
6.8  
50  
575-1-60  
208/230-3-60  
460-3-60  
25.0  
12.2  
9.0  
164  
100  
78  
208/230-1-60  
460-1-60  
19  
575-3-60  
14  
575-1-60  
208/230-3-60  
460-3-60  
25.0  
12.2  
9.0  
39  
164  
100  
78  
208/230-1-60  
460-1-60  
19  
575-3-60  
14  
575-1-60  
208/230-3-60  
460-3-60  
30.1  
16.7  
12.2  
30.1  
16.7  
12.2  
47  
225  
114  
80  
208/230-1-60  
460-1-60  
26  
575-3-60  
19  
575-1-60  
208/230-3-60  
460-3-60  
47  
225  
114  
80  
208/230-1-60  
460-1-60  
26  
575-3-60  
19  
575-1-60  
1. Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.  
2. Maximum fuse or maximum circuit breaker (HACR type per NEC).  
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.  
Table 6: Electrical Data - Outdoor Unit - HP With Powered Convenience Outlet  
Compressors  
Outdoor Fan Motor  
Pwr Conv Outlet  
FLA  
Minimum  
Circuit  
Ampacity  
Maximum  
Fuse Size  
(A)  
Model  
Power  
RLA  
Qty  
MCC  
LRA  
Power  
FLA  
(each)  
1
2
HP Qty  
Supply  
(each) (each) (each)  
Supply  
208/230-1-60  
460-1-60  
208/230-3-60  
460-3-60  
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
25.0  
12.2  
9.0  
39  
19  
164  
100  
78  
1/3  
1/3  
1/3  
3/4  
3/4  
3/4  
1/3  
1/3  
1/3  
1/3  
1/3  
1/3  
3/4  
3/4  
3/4  
3/4  
3/4  
3/4  
2
2
2
2
2
2
4
4
4
4
4
4
4
4
4
4
4
4
2.1  
1.2  
0.9  
3.0  
1.6  
1.4  
2.1  
1.2  
0.9  
2.1  
1.2  
0.9  
3.0  
1.6  
1.4  
3.0  
1.6  
1.4  
10.0  
5.0  
45.5  
22.6  
17.1  
56.8  
28.5  
22.0  
74.7  
37.2  
28.0  
74.7  
37.2  
28.0  
89.8  
49.0  
36.9  
89.8  
49.0  
36.9  
60  
30  
25  
70  
35  
25  
90  
45  
35  
90  
45  
35  
110  
60  
45  
110  
60  
45  
PC090  
575-3-60  
14  
575-1-60  
4.0  
208/230-3-60  
460-3-60  
18.1  
9.0  
28.3  
14.0  
10.6  
39  
137  
62  
208/230-1-60  
460-1-60  
10.0  
5.0  
PC120  
PC180  
PD180  
PC240  
PD240  
575-3-60  
6.8  
50  
575-1-60  
4.0  
208/230-3-60  
460-3-60  
25.0  
12.2  
9.0  
164  
100  
78  
208/230-1-60  
460-1-60  
10.0  
5.0  
19  
575-3-60  
14  
575-1-60  
4.0  
208/230-3-60  
460-3-60  
25.0  
12.2  
9.0  
39  
164  
100  
78  
208/230-1-60  
460-1-60  
10.0  
5.0  
19  
575-3-60  
14  
575-1-60  
4.0  
208/230-3-60  
460-3-60  
30.1  
16.7  
12.2  
30.1  
16.7  
12.2  
47  
225  
114  
80  
208/230-1-60  
460-1-60  
10.0  
5.0  
26  
575-3-60  
19  
575-1-60  
4.0  
208/230-3-60  
460-3-60  
47  
225  
114  
80  
208/230-1-60  
460-1-60  
10.0  
5.0  
26  
575-3-60  
19  
575-1-60  
4.0  
1. Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.  
2. Maximum fuse or maximum circuit breaker (HACR type per NEC).  
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.  
Johnson Controls Unitary Products  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
430645-YIM-D-0610  
Take Adequate Precautions  
Refrigerant Mains  
Many service problems can be avoided by taking adequate  
precautions to provide an internally clean and dry system and  
by using procedures and materials that conform to established  
standards.  
This Split-System (Air Condensing / Heat Pump / Air  
Handling) unit is one component of an entire system. As  
such it requires specific application considerations with  
regard to the rest of the system (air handling unit, duct  
design, condensing unit, refrigerant piping and control  
scheme).  
Use hard drawn copper tubing where no appreciable amount of  
bending around pipes or other obstructions is necessary. If soft  
copper is used, care should be taken to avoid sharp bends that  
may cause a restriction. Pack fiberglass insulation and a  
sealing material such as permagum around refrigerant lines  
where they penetrate a wall to reduce vibrations and to retain  
some flexibility.  
Failure to properly apply this equipment with the rest of  
the system may result in premature failure and/or  
reduced performance / increased costs. Warranty  
coverage specifically excludes failures due to improper  
application and Unitary Products specifically disclaims  
any liability resulting from improper application.  
Support all tubing at minimum intervals with suitable hangers,  
brackets or clamps.  
Braze all copper-to-copper joints with Silfos-5 or equivalent  
brazing material. Do not use soft solder. Insulate all suction  
lines with a minimum of 1/2" ARMAFLEX or equivalent that  
meets local codes. Liquid lines exposed to direct sunlight and/  
or high temperatures must also be insulated. Never solder  
suction and liquid lines together. They can be taped together for  
convenience and support purposes, but they must be  
completely insulated from each other.  
Please refer to the equipment Technical Guide,  
Installation Manual and the piping applications bulletin  
247077 or call the applications department for Unitary  
Products @ 1-877-UPG-SERV for guidance.  
Line Sizing  
When sizing refrigerant pipe for a split-system air conditioner,  
check the following:  
The liquid and suction service ports on the condenser section  
permit leak testing, evacuation, and partial charging of the field  
piping and the evaporator without disturbing refrigerant stored  
in the condenser during initial installation.  
1. Suction line pressure drop due to friction.  
2. Liquid line pressure drop due to friction.  
3. Suction line velocity for oil return.  
Before beginning installation of the main lines, be sure that the  
evaporator section has not developed a leak in transit. Check  
pressure at the Schrader valve located on the header of each  
coil. If pressure still exists in the system, it can be assumed to  
be leak free. If pressure DOES NOT exist the section will need  
to be repaired before evacuation and charging is performed.  
4. Liquid line pressure drop due to vertical rise. For certain  
piping arrangements, different sizes of suction line pipe  
may have to be used. The velocity of the refrigerant vapor  
must always be great enough to carry the oil back to the  
compressor.  
A bi-flow solid core filter-drier MUST be field-installed in the  
liquid line of every system to prevent dirt and moisture from  
damaging the system. Properly sized filter-driers are shipped  
with each condensing section.  
5. Evaporator Located Below Condenser - On a split  
system where the evaporator blower is located below the  
condenser, the suction line must be sized for both pressure  
drop and for oil return.  
NOTE: Installing a filter-drier does not eliminate the need for  
6. Condenser Located Below Evaporator - When the  
condenser is located below the evaporator blower, the  
liquid line must be designed for the pressure drop due to  
both friction loss and vertical rise. If the pressure drop due  
to vertical rise and friction exceeds 60 psi, some refrigerant  
will flash before it reaches the thermal expansion valve.  
the proper evacuation of a system before it is charged.  
A field-installed moisture indicating sight-glass should be  
installed in the liquid line(s) between the filter-drier and the  
evaporator coil. The moisture indicating sight-glass can be used  
to check for excess moisture in the system.  
Flash gas:  
Both condenser and evaporator sections have copper sealing  
disks brazed over the end of liquid and suction connections.  
The temperature required to make or break a brazed joint is  
high enough to cause oxidation of the copper unless an inert  
atmosphere is provided.  
1. Increases the liquid line pressure loss due to friction that in  
turn causes further flashing.  
2. Reduces the capacity of the refrigerant control device  
which starves the evaporator.  
NOTE: Dry nitrogen should flow through the system at all times  
when heat is being applied and until the joint has  
cooled. The flow of nitrogen will prevent oxidation of the  
copper lines during installation.  
3. Erodes the seat of the refrigerant control device.  
4. Causes erratic control of the refrigerant entering the  
evaporator.  
10  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
430645-YIM-D-0610  
Always punch a small hole in sealing disks before unbrazing to  
prevent the pressure in the line from blowing them off. Do not  
use a drill as copper shavings can enter system.  
suction sealing disks and prepare the joints for connections of  
the main lines.  
Connect the main liquid line to the liquid line connection on the  
evaporator section, while maintaining a flow of nitrogen.  
NOTE: Solenoid and hot gas bypass valves (if used) should be  
opened manually or electrically during brazing or  
evacuating.  
Make the suction line connection at the evaporator and run the  
line to the heat pump. Connect the main suction line to the  
suction line service valve connection, while maintaining a flow  
of nitrogen. Cool the valve body and replace the Schrader valve  
stem in the service port.  
NOTE: Schrader valves located on unit service valves should  
have their stems removed during brazing to prevent  
damage to the valve and reduce system evacuation  
time.  
Once the brazing process is complete, leak testing should be  
done on all interconnecting piping and the evaporator before  
proper evacuation to below 500 microns is performed.  
Start Installation  
Start the installation of main lines at the heat pump. Verify  
holding charge in unit by cracking open valve. If pressure is  
present, close valve and proceed with installation. If no  
pressure is present, check system for leaks.  
Verify evacuation with micron guage or thermocouple. Once the  
line set and evaporator section is properly evacuated, the  
service valves can be opened and the heat pump is now ready  
to charge with the appropriate weight of refrigerant. Calculate  
the correct system charge for the outdoor unit, the indoor unit  
and the field line set.  
Verify all service valves are fully seated by screwing the stems  
of both valves down into the valve bodies until they stop.  
Remove the Schrader valve stem and connect a low-pressure  
nitrogen source to the service port on the suction line valve  
body. Punch a small hole in the sealing disk; the flow of  
nitrogen will prevent any debris from entering the system. Wrap  
the valve body with a wet rag to prevent overheating during the  
brazing process. Overheating the valve will damage the valve  
seals. Unbraze the sealing disk, cool the valve body and  
prepare the joint for connections of the main lines. Repeat for  
the liquid line valve body.  
Charge the system by introducing liquid refrigerant into the  
liquid line through the liquid port connection. Complete adding  
the refrigerant in vapor form into the suction port when the  
compressor is started.  
The correct refrigerant pressures are indicated as shown in  
Figures 11 thru 16.  
This system uses R-410A Refrigerant which operates at  
higher pressures than R-22. No other refrigerant may be  
used in this system. Gage sets, hoses, refrigerant  
containers and recovery systems must be designed to  
handle R-410A. If you are unsure, consult the  
equipment manufacturer. Failure to use R-410A  
compatible servicing equipment may result in property  
damage or injury.  
Never remove a cap from an access port unless the  
valve is fully back-seated with its valve stem in the  
maximum counter-clockwise position because the  
refrigerant charge will be lost. Always use a refrigeration  
valve wrench to open and close these service valves.  
Connect the main liquid line to the liquid line service valve  
connection, while maintaining a flow of nitrogen. Cool the valve  
body and replace the Schrader valve stem in the service port.  
Install the liquid line from the heat pump to the evaporator liquid  
connection, maintaining a flow of nitrogen during all brazing  
operations.  
Wear safety glasses and gloves when handling  
refrigerants. Failure to follow this warning can cause  
serious personal injury.  
The filter-drier and sight glass must be located in the liquid line,  
leaving the O.D. unit.  
NOTE: This instruction covers the installation and operation of  
the basic heat pump. For refrigerant piping installation  
instructions refer to document 247077 "Application  
Data - General Piping Recommendations for Split  
System Air Conditioning and Heat Pumps".  
Connect a low-pressure nitrogen source to the Schrader valve  
located on the evaporator section coil headers. Punch a small  
hole in the sealing disks, the flow of nitrogen will prevent any  
debris from entering the system. Unbraze both liquid and  
Johnson Controls Unitary Products  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
430645-YIM-D-0610  
NOTE: Do not use a heat pump thermostat.  
Y1  
G W1 W2  
R
C
THERMOSTAT  
SINGLE STAGE COOLING  
TWO STAGE HEATING  
NOTE: Liquid line solenoid is not included or required  
on 7.5 Ton Single Stage Units.  
Figure 3: Typical Field Wiring Diagram - NC090 Air Handling Unit With PC090 Heat Pump  
12  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
430645-YIM-D-0610  
NOTE: Do not use a heat pump thermostat.  
Y1  
Y2  
W1 W2  
R
C
G
THERMOSTAT  
TWO STAGE COOLING  
TWO STAGE HEATING  
NOTE: Liquid line solenoid is only activated during  
second stage cooling operation.  
Figure 4: Typical Field Wiring Diagram - NC120 thru 240 Evaporator Unit with PC120 thru 240 Heat Pump  
VALVE SYS 2  
218 / BR  
219 / Y  
BLK  
1LLS  
BLK  
Figure 5: NC120 - 240 Liquid Line Solenoid Wiring  
Johnson Controls Unitary Products  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
430645-YIM-D-0610  
NOTE: Do not use a heat pump thermostat.  
Y1  
Y2  
W1 W2  
R
C
G
THERMOSTAT  
TWO STAGE COOLING  
TWO STAGE HEATING  
NOTE: Liquid line solenoid is not included or required  
on any 4 pipe units.  
Figure 6: Typical Field Wiring Diagram - ND180 thru 240 Evaporator Unit with PD180 thru 240 Heat Pump  
14  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
430645-YIM-D-0610  
RIGHT  
REAR  
FRONT  
LEFT  
CONVENIENCE  
OUTLET  
A
2X (Ø 1.375)  
KNOCKOUT  
30.994  
2X (Ø 0.875)  
KNOCKOUT  
12.126  
9.876  
4.751  
3.883  
23.000  
37.000  
7.000  
7.000  
10.000  
7.000  
7.000  
3.664  
2.933  
1.664  
24.000  
31.758  
58.500  
RIGHT  
FRONT  
SYSTEM 2  
2X (Ø 0.875)  
KNOCKOUT  
2X (Ø 1.375)  
KNOCKOUT  
15.53  
12.70  
12.000  
10.000  
SYSTEM 1  
4.875  
6.26  
7.52  
8.98  
10.60  
4.132  
2.382  
1.882  
REAR  
LEFT  
Figure 7: PC090, PC120 Unit Dimensions  
NOTE: Use System 1 piping dimensions when applying a PC090/120 model system.  
Table 7: PC090, PC120 Unit Height Dimensions  
MODEL  
PC090  
PC120  
A
44.5  
50.0  
Johnson Controls Unitary Products  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
430645-YIM-D-0610  
REAR  
RIGHT  
LEFT  
FRONT  
A
SYSTEM 2  
SYSTEM 1  
2X (Ø 1.375)  
KNOCKOUT  
30.994  
2X (Ø 0.875)  
KNOCKOUT  
11.375  
9.125  
4.750  
4.132  
23.000  
37.000  
7.000  
7.000  
23.000  
37.000  
7.000  
7.000  
3.913  
3.181  
1.913  
64.000  
59.000  
FRONT  
RIGHT  
SYSTEM 2  
SYSTEM 1  
16.133  
13.133  
17.367  
18.867  
20.617  
22.617  
FRONT  
(PIPING DETAIL)  
Figure 8: PC/PD180 & PC/PD240 Unit Dimensions and Piping & Electrical Dimensions  
NOTE: Use System 1 piping dimensions when applying a PC180/240 model system.  
Table 8: PC/PD180 & PC/PD240 Unit Height Dimensions  
MODEL  
PC180  
PD180  
PC240  
PD240  
A
44.5  
44.5  
50.0  
50.0  
16  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
430645-YIM-D-0610  
Table 9: Piping and Electrical Connection Sizes  
MODEL  
No. Refrigeration Circuits  
Suction Line OD (in.)  
Liquid Line OD (in.)  
PC090  
PC120  
1
PC180  
1
PD180  
2
PC240  
1
PD240  
2
1
1 1/8  
5/8  
1 3/8  
7/8  
1 5/8  
7/8  
1 3/8  
5/8  
1 5/8  
7/8  
1 3/8  
7/8  
Power Wiring Knockout  
Control Wiring Knockout  
1 3/8  
7/8  
1 3/8  
7/8  
1 3/8  
7/8  
1 3/8  
7/8  
1 3/8  
7/8  
1 3/8  
7/8  
5. Does the available power supply agree with the nameplate  
data on the unit?  
Piping And Electrical Connections  
Piping connections are made from the rear of 7.5 thru 12.5 Ton  
units and from the front of 15 thru 20 Ton units. Stubouts are  
provided on the suction and liquid line service valves. Piping  
can be routed to the unit from the left or right side.  
6. Is the control circuit transformer set for the proper voltage?  
7. Have the fuses, disconnect switch and power wire been  
sized properly?  
8. Are all compressor mounting bolts properly secured?  
Electrical connections for power and control wiring are made  
from the right or left side of the electrical control box. See Table  
9 and Figures 7 and 8 for piping sizes and electrical knockout  
details.  
9. Are any refrigerant lines touching each other or any sheet  
metal surface? Rubbing due to vibration could cause a  
refrigerant leak.  
10. Are there any visible signs of a refrigerant leak, such as oil  
residue?  
Start-Up  
11. Has the refrigeration system been leak checked,  
evacuated and had the correctly calculated charge  
weighted in?  
Crankcase Heaters  
12. Is any electrical wire laying against a hot refrigerant line?  
The crankcase heaters must be energized at least 8 hours  
before starting the compressors. To energize the crankcase  
heaters, the main disconnect switch must be closed. During this  
8 hour period, the system switch on the room thermostat must  
be “OFF” to prevent the compressor from starting. Make sure  
that the bottom of the compressor is warm to the touch to prove  
crankcase heater operation.  
Initial Start-Up  
1. Supply power to the unit through the disconnect switch at  
least 8 hours prior to starting the compressor.  
2. Move the system switch on the thermostat to the AUTO or  
COOL position.  
3. Reduce the setting of the room thermostat to energize the  
compressor.  
4. Check the operation of the evaporator unit per the  
manufacturer’s recommendations.  
Do not attempt to start the compressor without at least 8  
hours of crankcase heat or compressor damage can  
occur.  
5. With an ammeter, check the compressor amps against the  
unit data plate.  
Pre-Start Check  
6. Check for refrigerant leaks.  
7. Check for any abnormal noises and/or vibrations, and  
make the necessary adjustments to correct fan blade(s)  
touching shroud, refrigerant lines hitting on sheet metal,  
etc.  
Before starting the unit, complete the following check list:  
1. Have sufficient clearances been provided?  
2. Has all foreign matter been removed from the interior of the  
unit (tools, construction or shipping materials, etc.)?  
8. After the unit has been operating for several minutes, shut  
off the main power supply at the disconnect switch and  
inspect all factory wiring connections and bolted surfaces  
for tightness.  
3. Have the condenser fans been rotated manually to check  
for free rotation?  
4. Are all wiring connections tight?  
Johnson Controls Unitary Products  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
430645-YIM-D-0610  
Compressor Protection  
Operation  
In addition to the external pressure switches, the compressors  
also have inherent (internal) protection. If there is an abnormal  
temperature rise in a compressor, the protector will open to shut  
down the compressor. The UCB incorporates features to  
minimize compressor wear and damage. An Anti-Short Cycle  
Delay (ASCD) is utilized to prevent operation of a compressor  
too soon after its previous run. Additionally, a minimum run time  
is imposed any time a compressor is energized.  
Unit Control Overview  
This series of heat pumps come factory equipped with  
Simplicity™ controls to monitor all unit functionality and safety  
controls.  
Safety Controls  
The Simplicity™ control board incorporates features to monitor  
safety circuits as well as minimize compressor wear and  
damage. An anti-short cycle delay (ASCD) is utilized to prevent  
operation of a compressor too soon after its previous run. The  
ASCD is initiated on unit start-up and on any compressor reset  
or lockout.  
The ASCD is initiated on unit start-up and on any compressor  
reset or lock-out.  
Flash Codes  
The UCB will initiate a flash code associated with errors within  
the system. Refer to UNIT CONTROL BOARD FLASH CODES  
Table 11.  
The Simplicity™ control board monitors the following inputs for  
each cooling system:  
• A high-pressure switch is factory installed to protect  
against excessive discharge pressure due to a blocked  
condenser coil or a condenser fan motor failure. During  
cooling operation, if a high-pressure limit switch opens,  
the Simplicity™ control board will de-energize the  
associated compressors and initiate the 5-minute ASCD.  
If the call for cool is still present at the end of the ASCD,  
the control board will re-energize the halted compressor. If  
a high-pressure switch opens three times within two hours  
of operation, the Simplicity™ control board will lockout the  
associated system compressors and will flash an error  
Reset  
Remove the call for cooling, by raising thermostat setting higher  
than the conditioned space temperature. This resets any  
pressure or freezestat flash codes. Simplicity™ only has  
minimum run time in cool. Heat pump mode shuts off  
immediately.  
Sequence of Operation  
Continuous Blower  
By setting the room thermostat to “ON,” the low voltage control  
circuit from the “R” to “G” is completed and the supply air blower  
will operate continuously.  
• A low-pressure switch to protect the unit against  
excessively low suction pressure is standard on all  
condensing units. If the low-pressure switch opens during  
normal operation, the Simplicity™ control board will de-  
energize the compressor, initiate the ASCD, and shut  
down the condenser fans. On startup, if the low-pressure  
switch opens, the Simplicity™ control board will monitor  
the low-pressure switch to make sure it closes within one  
minute. If it fails to close, the unit will shut down the  
associated compressor and begin an ASCD. If the call for  
cool is still present at the end of the anti-short cycle time  
delay, the control board will re-energize the halted  
compressor. If a low-pressure switch opens three times  
within one hour of operation, the Simplicity™ control  
board will lock-out the associated compressor and flash  
an error code (see Table 11).  
Intermittent Blower  
With the room thermostat fan switch set to “AUTO” and the  
system switch set to either the “AUTO” or “HEAT” settings, the  
blower is energized whenever a cooling or heating operation is  
requested. The blower is energized after any specified delay  
associated with the operation.  
When energized, the indoor blower has a minimum run time of  
30 seconds. Additionally, the indoor blower has a delay of 10  
seconds between operations.  
Cooling Sequence Of Operation  
Single-Stage Heat Pump (PC090)  
• An ambient air switch will lock out mechanical cooling at  
40F. If the product was equipped from the factory with  
the low ambient option the unit will operate down to 0F. If  
the unit was not ordered with the factory low ambient  
option a field installed low ambient kit is available.  
A single stage thermostat is required to operate the heat pump  
in cooling mode.  
The reversing valve is energized during cooling mode. A  
continuous 24V signal is passed through the normally closed  
contacts of relay RY2 to the "O" terminal of the Defrost Control  
Board (DC). The normally closed relay DR-2 within DC  
energizes the solenoid (SOL) of the reversing valve.  
The refrigerant systems are independently monitored and  
controlled. On any fault, only the associated system will be  
affected by any safety/preventive action. The other refrigerant  
system will continue to operate unless it is affected by the fault  
as well.  
When the thermostat calls for cooling (Y1), the Simplicity  
control board (UCB) closes the coils of relay RY1 and contactor  
18  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
430645-YIM-D-0610  
M1 while sending a signal to one of the "CFAN" terminals on  
DC.  
• Relay RY2 has two functions. 1) control the crankcase  
heater CCH2, 2) control the 24V output signal to S2 on  
terminal block TB2.  
• Relay RY1 controls the crankcase heater (CCH1). The  
normally closed contacts allow CCH1 to operate during  
unit shutdown.  
• Contactor M2 controls compressor COMPR2.  
If the initial call for cooling requires both stages (Y1 and Y2), the  
UCB will delay the second stage by 30 seconds to avoid an  
excessive power inrush.  
• Contactor M1 controls compressor COMPR1.  
The output signal from the remaining "CFAN" terminal on DC  
closes the coil of contactor M3.  
When the call for cooling (Y2) is satisfied, the UCB disables the  
signal to RY2 and M2 as long as the specified minimum run  
time (ASCD) has elapsed.  
• Contactor M3 controls outdoor fans ODFAN1 & 2.  
After completing the specified time for fan on-delay, UCB closes  
the coil of relay BR1.  
When the call for cooling (Y1) is satisfied, the UCB disables the  
signal to RY1 and M1 as long as the specified minimum run  
time (ASCD) has elapsed.  
• Relay BR1 sends a 24V signal to G1 of terminal block  
TB2. It may be used to control operation of an indoor  
blower.  
Dual Stage Heat Pump - 4 pipe (PD180-240)  
A two stage thermostat is required to operate the heat pump in  
cooling mode.  
When the call for cooling (Y1) is satisfied, the UCB disables the  
signal to RY1, M1 and DC as long as the specified minimum run  
time (ASCD) has elapsed.  
Both reversing valves are energized during cooling mode.  
Continuous 24V signals are passed through the normally  
closed contacts of relays RY2 and RY3 to the "O" terminals of  
their respective Defrost Control Boards (DC1 and DC2). The  
normally closed relays DR-2 within DC1 and DC2 energize the  
solenoids (SOL1 and SOL2) of the reversing valves.  
The UCB disables the signal to BR1 after completing the fan  
off-delay period.  
Dual Stage Heat Pump (PC120-240)  
A two stage thermostat is required to operate the heat pump in  
cooling mode.  
When the thermostat calls for first-stage cooling (Y1), the  
Simplicity control board (UCB) closes the coils of relay RY1 and  
contactor M1 while sending a signal to one of the "CFAN"  
terminals on DC1.  
The reversing valve is energized during cooling mode. A  
continuous 24V signal is passed through the normally closed  
contacts of relay RY2 to the "O" terminal of the Defrost Control  
Board (DC). The normally closed relay DR-2 within DC  
energizes the solenoid (SOL) of the reversing valve.  
• Relay RY1 has two functions. 1) control the crankcase  
heater CCH1, 2) control the 24V output signal to S1 on  
terminal block TB2.  
When the thermostat calls for first-stage cooling (Y1), the  
Simplicity control board (UCB) closes the coils of relay RY1 and  
contactor M1 while sending a signal to one of the "CFAN"  
terminals on DC.  
• Contactor M1 controls compressor COMPR1.  
The output signal from the remaining "CFAN" terminal on DC1  
closes the coil of contactor M3.  
• Contactor M3 controls outdoor fans ODFAN1 & 2.  
• Relay RY1 has two functions. 1) control the crankcase  
heater CCH1, 2) control the 24V output signal to S1 on  
terminal block TB2.  
After completing the specified time for fan on-delay, UCB closes  
the coil of relay BR1.  
• Contactor M1 controls compressor COMPR1.  
• Relay BR1 sends a 24V signal to G1 of terminal block  
TB2. It may be used to control operation of an indoor  
blower.  
The output signal from the remaining "CFAN" terminal on DC  
closes the coil of contactor M3.  
• Contactor M3 controls all outdoor fans.  
When the thermostat calls for second-stage cooling (Y2), the  
Simplicity control board (UCB) closes the coils of relay RY2 and  
contactor M2 while sending a signal to one of the "CFAN"  
terminals on DC2.  
After completing the specified time for fan on-delay, UCB closes  
the coil of relay BR1.  
• Relay BR1 sends a 24V signal to G1 of terminal block  
TB2. It may be used to control operation of an indoor  
blower.  
• Relay RY2 has two functions. 1) control the crankcase  
heater CCH2, 2) control the 24V output signal to S2 on  
terminal block TB2.  
When the thermostat calls for second-stage cooling (Y2), the  
Simplicity control board (UCB) closes the coil of relay RY2 and  
contactor M2.  
• Contactor M2 controls compressor COMPR2.  
The output signal from the remaining "CFAN" terminal on DC2  
closes the coil of contactor M4.  
Johnson Controls Unitary Products  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
430645-YIM-D-0610  
• Contactor M4 controls outdoor fans ODFAN3 & 4.  
• Relay RY1 has two functions: 1) control the operation of  
crankcase heater CCH1, and 2) control the 24V output  
signal to S1 on terminal block TB2.  
If the initial call for cooling requires both stages (Y1 and Y2), the  
UCB will delay the second stage by 30 seconds to avoid an  
excessive power inrush.  
• Contactor M1 controls compressor COMPR1.  
• Relay RY3 (RY2 for PC090 model) toggles the 24V signal  
from the "O" terminal of DC to the "Y" terminal assuring  
the reversing valve cannot be energized except during  
defrost.  
When the call for cooling (Y2) is satisfied, the UCB disables the  
signal to RY2 and M2 as long as the specified minimum run  
time (ASCD) has elapsed.  
When the call for cooling (Y1) is satisfied, the UCB disables the  
signal to RY1 and M1 as long as the specified minimum run  
time (ASCD) has elapsed.  
• Concurrently, a 24V signal is sent to one of the "CFAN"  
terminals of DC. The output signal from the remaining  
"CFAN" terminal closes the coil of contactor M3.  
• Contactor M3 controls outdoor fans ODFAN1 & 2 (all  
models) and ODFAN3 & 4 (PC180-240).  
Low Ambient Cooling  
These units are factory equipped with low ambient switches  
that work through the Simplicity control board to operate the  
compressors and condenser fans normally to 40ºF ambient  
temperature. The Electronic Low Ambient Controller  
2LA04703000 Accessory is designed to assure safe operation  
through condenser head pressure regulation down to 0ºF  
ambient temperature.  
(PC120-240; PD180-240 models)  
• After a two second delay, the UCB energizes the contacts  
of relay RY2 and contactor M2.  
• Relay RY2 has two functions: 1) control the operation of  
crankcase heater CCH2, and 2) control the 24V output  
signal to S2 on terminal block TB2.  
Low Ambient Control Operation  
• Contactor M2 controls compressor COMPR2.  
• A call for cooling closes contactor M3 which energizes all  
condenser fans. The Low Ambient Control starts all fans  
at full speed then adjusts according to the liquid line  
temperature.  
(PD180-240 models only)  
• Concurrently, a 24V signal is sent to one of the "CFAN"  
terminals of defrost control board DC2. The output signal  
from the remaining "CFAN" terminal closes the coil of  
contactor M4.  
Refer to the appropriate 2LA low ambient kit instructions for  
additional detail on the factory or field installed low ambient kit  
and its operation.  
• Contactor M4 controls outdoor fans ODFAN3 & 4.  
Heating Sequence of Operation  
General  
Second Stage Heating Operation  
When the thermostat calls for second stage heating (W2):  
Heat pump models are to be matched with air handlers of  
equivalent tonnage ratings. Twinning of heat pumps and air  
handlers is not recommended.  
• A 24V signal passes through UCB sending an input signal  
to the "W" terminal of DC. This signal passes through DC  
as an output signal to the "66" terminal of TB2 to be used  
as a control signal for first stage electric heat.  
A two stage thermostat is required to operate the heat pump in  
heating mode.  
Emergency Heating Operation  
All reversing valves are de-energized during normal heating  
mode. They are energized only during cooling and defrost  
modes.  
When the thermostat calls for emergency heating (EMER):  
• The UCB de-energizes all compressor relays and  
contactors.  
The heat pump operates all compressors during a first stage  
call for heating unless locked out by the Unit Control Board  
(UCB).  
• A 24V signal passes through UCB sending an input signal  
to the "W" terminal of DC. This signal passes through DC  
as an output signal to the "66" terminal of TB2 to be used  
as a control signal for first stage electric heat.  
First Stage Heating Operation  
• The normally closed contacts of M1-AUX and M2-AUX  
(PC120-240; PD180-240 models only) send a 24V output  
signal to the "60" terminal of TB2 to be used as a control  
signal for second stage electric heat.  
When the thermostat calls for first stage heating (W1):  
• The Simplicity control board (UCB) goes into a five minute  
ASCD timer delay.  
• When the ASCD time delay is satisfied, the UCB closes its  
internal compressor relay contact, thus energizing the  
contacts of relay RY1 and contactor M1.  
20  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
430645-YIM-D-0610  
Defrost Operation  
NOTE: The DC has two flash codes that only initiate if the  
jumper between the two pressure switch terminals is  
removed or broken.  
The defrost control board (DC) utilizes a time/temperature  
defrost scheme. The DC repeats normal heating run cycles,  
which must be completed, until one of the following conditions  
is met and the DC enters defrost mode:  
Blower Operation  
After completing the specified time for fan on-delay, UCB closes  
the coil of relay BR1.  
1. The DC satisfies its accumulated minimum run time. This  
is factory set at 60 minutes, but is field adjustable to 30, 60  
or 90 minutes.  
• Relay BR1 sends a 24V signal to G1 of terminal block  
TB2. It may be used to control operation of an indoor  
blower.  
2. The defrost switch(es) is closed. This normally open  
switch is set to close at 28° F (+/-3°).  
The UCB disables the signal to BR1 after completing the fan  
off-delay period.  
When the DC enters defrost mode, its on-board defrost relays  
are powered. This energizes the reversing valve solenoid, de-  
energizes the condenser fan motors and energizes the unit's  
optional electric heater. The DC remains in defrost mode until  
either of the following two conditions are met:  
Rear  
Rear  
1. Both of the liquid line thermostats are open. Each is set to  
open at 55 degrees (+/- 3).  
2
2
4
3
2. The maximum defrost run time of 10 minutes is met.  
The DC also contains a set of test pins. Placing a jumper  
across these pins will result in the following actions:  
• If the ASCD timer is active, it is now bypassed, allowing  
the compressor to run.  
1
1
• If the DC is in a lockout condition, the lockout is reset.  
• If the compressor is running, the DC is forced into defrost  
mode. The control will remain in defrost mode as long as  
the jumper is in place. When the jumper is removed, the  
control will terminate defrost mode.  
Front  
Front  
Figure 9: Fan Orientation, Control Box End  
Table 10: PC090 thru 240 Unit Control Board Flash Codes  
GREEN  
LED  
16  
RED  
LED  
8
RED  
LED  
4
RED  
LED  
2
RED  
LED  
1
FLASH CODE  
DESCRIPTION  
On Steady  
1 Flash  
This is a Control Failure  
Not Applicable  
-
-
-
-
-
-
-
-
-
-
Control waiting ASCD1  
2 Flashes  
3 Flashes  
4 Flashes  
5 Flashes  
6 Flashes  
7 Flashes  
8 Flashes  
10 Flashes  
12 Flashes  
13 Flashes  
14 Flashes  
OFF  
Flashing  
Off  
Off  
-
Off  
Off  
-
On  
On  
-
Off  
On  
-
HPS1 Compressor Lockout  
Not Applicable  
Off  
-
LPS1 Compressor Lockout  
Not Applicable  
Off  
Off  
-
On  
-
Off  
-
On  
-
-
Off  
FS1 Compressor Lockout2  
Not Applicable  
Off  
-
On  
-
On  
-
On  
-
-
Compressors Locked Out on Low Outdoor Air Temperature1  
Unit Locked Out due to Fan Overload Switch Failure  
Flashing  
Off  
On  
On  
On  
On  
Off  
Off  
On  
On  
On  
Off  
On  
Off  
Off  
On  
Off  
Off  
Off  
On  
Off  
Off  
Compressor Held Off due to Low Voltage1  
EEPROM Storage Failure  
Flashing  
Off  
No Power or Control Failure  
Off  
1. Non-alarm condition.  
2. Freeze - stat not applicable.  
Johnson Controls Unitary Products  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
430645-YIM-D-0610  
Table 11: PD180 thru 240 Unit Control Board Flash Codes  
GREEN  
LED  
16  
RED  
LED  
8
RED  
LED  
4
RED  
LED  
2
RED  
LED  
1
FLASH CODE  
DESCRIPTION  
On Steady  
1 Flash  
This is a Control Failure  
Not Applicable  
-
-
-
-
-
-
-
-
-
-
Control waiting ASCD1  
2 Flashes  
3 Flashes  
4 Flashes  
5 Flashes  
6 Flashes  
7 Flashes  
Flashing  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
On  
On  
On  
On  
On  
On  
Off  
Off  
On  
On  
Off  
On  
Off  
On  
Off  
On  
HPS1 Compressor Lockout  
HPS2 Compressor Lockout  
LPS1 Compressor Lockout  
LPS2 Compressor Lockout  
Off  
Off  
Off  
FS1 Compressor Lockout2  
FS2 Compressor Lockout2  
Off  
8 Flashes  
Off  
On  
Off  
Off  
Off  
Compressors Locked Out on Low Outdoor Air Temperature1  
Unit Locked Out due to Fan Overload Switch Failure  
10 Flashes  
12 Flashes  
13 Flashes  
14 Flashes  
OFF  
Flashing  
Off  
On  
On  
On  
On  
Off  
Off  
On  
On  
On  
Off  
On  
Off  
Off  
On  
Off  
Off  
Off  
On  
Off  
Off  
Compressor Held Off due to Low Voltage1  
EEPROM Storage Failure  
Flashing  
Off  
No Power or Control Failure  
Off  
1. Non-alarm condition.  
2. Freeze - stat not applicable.  
Check  
Alarm  
History  
Reset All  
ASCDs for  
One Cycle  
Non Alarm  
Condition Green  
LED Flashing  
Current Alarm  
Flashed  
Red LED  
Figure 10: Unit Control Board  
22  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
430645-YIM-D-0610  
Flash Codes  
Normal Maintenance  
Various flash codes are utilized by the unit control board (UCB)  
to aid in troubleshooting. Flash codes are distinguished by the  
short on and off cycle used (approximately 200ms on and  
200ms off). To show normal operation, the control board  
flashes a 1 second on, 1 second off "heartbeat" during normal  
operation. This is to verify that the UCB is functioning correctly.  
Do not confuse this with an error flash code. To prevent  
confusion, a 1-flash, flash code is not used.  
Prior to any of the following maintenance procedures,  
shut off all power to the unit, to avoid personal injury.  
Periodic maintenance consists of changing or cleaning filters  
and general cleaning of the outdoor coil.  
Alarm condition codes are flashed on the UCB lower left Red  
LED, See Figure Table 11. While the alarm code is being  
flashed, it will also be shown by the other LEDs: lit continuously  
while the alarm is being flashed. The total of the continuously lit  
LEDs equates to the number of flashes, and is shown in the  
table. Pressing and releasing the LAST ERROR button on the  
UCB can check the alarm history. The UCB will cycle through  
the last five (5) alarms, most recent to oldest, separating each  
alarm flash code by approximately 2 seconds. In all cases, a  
flashing Green LED will be used to indicate non-alarm  
condition.  
FILTERS - Inspect once a month. Replace Disposable or clean  
Permanent Type as necessary. DO NOT replace Permanent  
Type with Disposable.  
MOTORS - Outdoor fan motors are permanently lubricated and  
require no maintenance.  
OUTDOOR COIL - Dirt should not be allowed to accumulate on  
the outdoor coil surface or other parts in the air circuit. Cleaning  
should be as often as necessary to keep the coil clean. Use a  
brush, vacuum cleaner attachment, or other suitable means. Be  
sure that the power to the unit is shut off prior to cleaning.  
In some cases, it may be necessary to "zero" the ASCD for the  
compressors in order to perform troubleshooting. To reset all  
ASCDs for one cycle, press and release the UCB TEST/  
RESET button once.  
Flash codes that do and do not represent alarms are listed in  
Exercise care when cleaning the coil so that the coil fins  
are not damaged.  
Do not permit the hot condenser air discharge to be  
obstructed by overhanging structures or shrubs.  
Unit Control Board Option Setup  
Option Byte Setup  
Troubleshooting  
• Enter The Option Setup Mode By Pushing The Option  
Setup / Store Button, And Holding It For At Least 2  
Seconds.  
• The Green Status Led (Option Byte) Will Be Turned On  
And The Red Status Led (Heat Delay) Is Turned Off.  
Troubleshooting of components necessarily requires  
opening the electrical control box with the power  
connected to the unit. Use extreme care when working  
with live circuit! Check the unit nameplate for the correct  
range before making any connections with line  
terminals.  
• The 4 Led Will Then Show The Status Of The Labeled  
Option Low Ambient Lockout.  
• Press The Up Or Down Button To Change The Led Status  
To Correspond To The Desired Option Setup.  
• To Save The Current Displayed Value, Push The Option  
Setup / Store Button And Hold It For At Least 2 Seconds.  
When The Value Is Saved, The Green Led Will Flash A  
Few Times And Then Normal Display Will Resume.  
NOTE: While in either Setup mode, if no buttons are pushed for  
60 seconds, the display will revert to its normal display,  
exiting the Option Setup mode. When saving, the  
control board only saves the parameters for the  
currently displayed mode (Option Byte or Heat  
Delay). (Heat Delay not applicable on these units.)  
The wire number or color and terminal designations  
referred to may vary. Check the wiring label inside the  
control box access panel for the correct wiring.  
Johnson Controls Unitary Products  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
430645-YIM-D-0610  
Cooling Troubleshooting Guide  
2. If M1 is pulled in and voltage is supplied at M1, lightly touch  
the compressor housing. If it is hot, the compressor may be  
off on inherent protection. Cancel any calls for cooling and  
wait for the internal overload to reset. Test again when  
cool.  
On calls for cooling, if the compressors are operating but the  
supply air blower motor does not energize after a short delay  
(the room thermostat fan switch is in the “AUTO” position):  
1. Turn the thermostat fan switch to the ON position. If the  
supply air blower motor does not energize, go to Step 3.  
3. If M1 is not pulled in, check for 24 volts at the M1 coil. If 24  
volts are present and M1 is not pulled in, replace the  
contactor.  
2. If the blower motor runs with the fan switch in the ON  
position but will not run after the first compressor has  
energized when the fan switch is in the AUTO position,  
check the room thermostat for contact between R and G in  
the AUTO position during calls for cooling.  
4. Failing the above, if voltage is supplied at M1, M1 is pulled  
in, and the compressor still does not operate, replace the  
compressor.  
5. If 24 volts is not present at M1, check for 24 volts at the  
UCB terminal, C1. If 24 volts is present, check for loose  
wiring between C1 and the compressor contactor.  
3. If the supply air blower motor does not energize when the  
fan switch is set to ON, check that line voltage is being  
supplied to the contacts of the M3, contactor, and that the  
contactor is pulled in. Check for loose wiring between the  
contactor and the supply air blower motor.  
6. If 24 volts is not present at the C1 terminal, check for 24  
volts from the room thermostat at the UCB Y1 terminal. If  
24 volts is not present from the room thermostat, check for  
the following:  
4. If M3 is pulled in and voltage is supplied to M3, lightly touch  
the supply air blower motor housing. If it is hot, the motor  
may be off on internal protection. Cancel any thermostat  
calls and set the fan switch to AUTO. Wait for the internal  
overload to reset. Test again when cool.  
a. 24 volts at the thermostat Y1 terminal  
b. Proper wiring between the room thermostat and the  
UCB, i.e. Y1 to Y1, Y2 to Y2, and  
c. Loose wiring from the room thermostat to the UCB  
5. If M3 is not pulled in, check for 24 volts at the M3 coil. If 24  
volts are present at M3 but M3 is not pulled in, replace the  
contactor.  
7. If 24 volts is present at the UCB Y1 terminal, the  
compressor may be out due to an open high-pressure  
switch or low-pressure switch. Check for 24 volts at the  
HPS1 and LPS1 terminals of the UCB. If a switch has  
opened, there should be a voltage potential between the  
UCB terminals, e.g. if LPS1 has opened, there will be a 24-  
volt potential between the LPS1 terminals.  
6. Failing the above, if there is line voltage supplied at M3, M3  
is pulled in, and the supply air blower motor still does not  
operate, replace the motor.  
7. If 24 volts is not present at M3, check that 24 volts is  
present at the UCB supply air blower motor terminal,  
“FAN”. If 24 volts is present at the FAN, check for loose  
wiring between the UCB and M3.  
8. If 24 volts is present at the UCB Y1 terminal and none of  
the protection switches have opened, the UCB may have  
locked out the compressor for repeat trips. The UCB  
should be flashing an alarm code. If not, press and release  
the ALARMS button on the UCB. The UCB will flash the  
last five alarms on the LED. If the compressor is locked  
out, cancel any call for cooling. This will reset any  
compressor lock outs.  
8. If 24 volts is not present at the “FAN” terminal, check for 24  
volts from the room thermostat. If 24 volts are not present  
from the room thermostat, check for the following:  
a. Proper operation of the room thermostat (contact  
between R and G with the fan switch in the ON position  
and in the AUTO position during operation calls).  
NOTE: While the above step will reset any lockouts,  
compressor #1 may be held off for the ASCD. See the  
next step.  
b. Proper wiring between the room thermostat and the  
UCB, and  
c. Loose wiring from the room thermostat to the UCB  
9. If 24 volts is present at the UCB Y1 terminal and none of  
the switches are open and the compressor is not locked  
out, the UCB may have the compressor in an ASCD.  
Check the LED for an indication of an ASCD cycle. The  
ASCD should time out within 5 minutes. Press and release  
the TEST button to reset all ASCDs.  
9. If 24 volts is present at the room thermostat but not at the  
UCB, check for proper wiring between the thermostat and  
the UCB, i.e. that the thermostat G terminal is connected to  
the G terminal of the UCB, and for loose wiring.  
10. If the thermostat and UCB are properly wired, replace the  
UCB.  
10. If 24 volts is present at the UCB Y1 terminal and the  
compressor is not out due to a protective switch trip, repeat  
trip lock out, or ASCD, the economizer terminals of the  
UCB may be improperly wired. Check for 24 volts at the Y1  
“OUT” terminal of the UCB.  
On calls for cooling, the supply air blower motor is operating but  
compressor #1 is not (the room thermostat fan switch is in the  
“AUTO” position):  
1. If compressor #1 does not energize on a call for cooling,  
check for line voltage at the compressor contactor, M1, and  
that the contactor is pulled in. Check for loose wiring  
between the contactor and the compressor.  
11. If 24 volts is not present at the Y1 “OUT” terminal, the UCB  
must be replaced. (If 24 volts is present at the Y1 OUT  
terminal, check for 24 volts at the Y1 “ECON” terminal. If  
24 volts is not present, check for loose wiring from the Y1  
24  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
430645-YIM-D-0610  
“OUT” terminal to the Mate-N-Lock plug, the jumper in the  
Mate-N-Lock plug, and in the wiring from the Mate-N-Lock  
plug to the Y1 “ECON” terminal.)  
remove any call for cooling at the thermostat or by  
disconnecting the thermostat wiring at the Y2 UCB  
terminal. This will reset any compressor lock outs.  
12. If none of the above corrected the error, test the integrity of  
the UCB. Disconnect the C1 terminal wire and jumper it to  
the Y1 terminal. DO NOT jump the Y1 to C1 terminals. If  
the compressor engages, the UCB has faulted.  
NOTE: While the above step will reset any lock outs,  
compressor #1 will be held off for the ASCD, and  
compressor #2 may be held off for a portion of the  
ASCD. See the next step.  
13. If none of the above correct the error, replace the UCB.  
9. If 24 volts is present at the UCB Y2 terminal and none of  
the switches are open and the compressor is not locked  
out, the UCB may have the compressor in an ASCD.  
Check the LED for an indication of an ASCD cycle. The  
ASCD should time out within 5 minutes. Press and release  
the TEST button to reset all ASCDs.  
For units with two stages of cooling: On calls for the second  
stage of cooling, the supply air blower motor and compressor  
#1 are operating but compressor #2 is not (the room thermostat  
fan switch is in the “AUTO” position):  
1. Compressor #2 will not energize simultaneously with  
compressor #1 if a call for both stages of cooling is  
received. The UCB delays compressor #2 by 30 seconds  
to prevent a power surge. If after the delay compressor #2  
does not energize on a second stage call for cooling, check  
for line voltage at the compressor contactor, M2, and that  
the contactor is pulled in. Check for loose wiring between  
the contactor and the compressor.  
10. If none of the above corrected the error, test the integrity of  
the UCB. Disconnect the C2 terminal wire and jumper it to  
the Y2 terminal. DO NOT jump the Y2 to C2 terminals. If  
the compressor engages, the UCB has faulted.  
11. If none of the above correct the error, replace the UCB.  
On a call for cooling, the supply air blower motor and  
compressor #2 are operating but compressor #1 is not (the  
room thermostat fan switch is in the “AUTO” position):  
2. If M2 is pulled in and voltage is supplied at M2, lightly touch  
the compressor housing. If it is hot, the compressor may be  
off on inherent protection. Cancel any calls for cooling and  
wait for the internal overload to reset. Test again when cool.  
1. Compressor #2 is energized in place of compressor #1  
when compressor #1 is unavailable for cooling calls. Check  
the UCB for alarms indicating that compressor #1 is locked  
out. Press and release the ALARMS button if the LED is  
not flashing an alarm.  
3. If M2 is not pulled in, check for 24 volts at the M2 coil. If 24  
volts is present and M2 is not pulled in, replace the  
contactor.  
2. Check for line voltage at the compressor contactor, M1,  
and that the contactor is pulled in. Check for loose wiring  
between the contactor and the compressor.  
4. Failing the above, if voltage is supplied at M2, M2 is pulled  
in, and the compressor still does not operate, replace the  
compressor.  
3. If M1 is pulled in and voltage is supplied at M1, lightly touch  
the compressor housing. If it is hot, the compressor may be  
off on inherent protection. Cancel any calls for cooling and  
wait for the internal overload to reset. Test again when cool.  
5. If 24 volts is not present at M2, check for 24 volts at the  
UCB terminal, C2. If 24 volts are present, check for loose  
wiring between C2 and the compressor contactor.  
6. If 24 volts is not present at the C2 terminal, check for 24  
volts from the room thermostat at the UCB Y2 terminal. If  
24 volts is not present from the room thermostat, check for  
the following:  
4. If M1 is not pulled in, check for 24 volts at the M1 coil. If 24  
volts is present and M1 is not pulled in, replace the  
contactor.  
5. Failing the above, if voltage is supplied at M1, M1 is pulled  
in, and the compressor still does not operate, replace the  
compressor.  
a. 24 volts at the thermostat Y2 terminal  
b. Proper wiring between the room thermostat and the  
UCB, i.e. Y1 to Y1, Y2 to Y2, and  
6. If 24 volts is not present at M1, check for 24 volts at the  
UCB terminal, C1. If 24 volts is present, check for loose  
wiring between C1 and the compressor contactor.  
c. Loose wiring from the room thermostat to the UCB  
7. If 24 volts is present at the UCB Y2 terminal, the  
compressor may be out due to an open high-pressure  
switch, low-pressure switch, or freezestat. Check for 24  
volts at the HPS2, LPS2, and FS2 terminals of the UCB. If  
a switch has opened, there should be a voltage potential  
between the UCB terminals, e.g. if LPS2 has opened, there  
will be 24 volts of potential between the LPS2 terminals.  
7. If 24 volts is not present at the C1 terminal, check for 24  
volts from the room thermostat at the UCB Y1 terminal. If  
24 volts are not present at the UCB Y1 terminal, the UCB  
may have faulted. Check for 24 volts at the Y1 ECON  
terminal. If 24 volts is not present at Y1 “ECON”, the UCB  
has faulted. The UCB should de-energize all compressors  
on a loss of call for the first stage of cooling, i.e. a loss if 24  
volts at the Y1 terminal.  
8. If 24 volts is present at the UCB Y2 terminal and none of  
the protection switches have opened, the UCB may have  
locked out the compressor for repeat trips. The UCB  
should be flashing a code. If not, press and release the  
ALARMS button on the UCB. The UCB will flash the last  
five alarms on the LED. If the compressor is locked out,  
8. If 24 volts are present at the UCB Y1 terminal, the  
compressor may be out due to an open high-pressure  
switch or low-pressure switch. Check for 24 volts at the  
Johnson Controls Unitary Products  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
430645-YIM-D-0610  
HPS1 and LPS1 terminals of the UCB. If a switch has  
opened, there should be a voltage potential between the  
UCB terminals, e.g. if LPS1 has opened, there will be a 24-  
volt potential between the LPS1 terminals.  
ASCD should time out within 5 minutes. Press and release  
the TEST button to reset all ASCDs.  
11. If 24 volts is present at the UCB Y1 terminal and the  
compressor is not out due to a protective switch trip, repeat  
trip lock out, or ASCD, the economizer terminals of the UCB  
may be improperly wired. Check for 24 volts at the Y1 “OUT”  
terminal of the UCB. If 24 volts is not present at the Y1  
“OUT” terminal, the UCB must be replaced.  
9. If 24 volts is present at the UCB Y1 terminal and none of  
the protection switches have opened, the UCB may have  
locked out the compressor for repeat trips. The UCB  
should be flashing a code. If not, press and release the  
ALARMS button on the UCB. The UCB will flash the last  
five alarms on the LED. If the compressor is locked out,  
remove any call for cooling. This will reset any compressor  
lock outs.  
12. If 24 volts is present at the Y1 “OUT” terminal, check for 24  
volts at the Y1 “ECON” terminal. If 24 volts is not present,  
check for loose wiring from the Y1 “OUT” terminal to the  
Mate-N-Lock plug, the jumper in the Mate-N-Lock plug,  
and in the wiring from the Mate-N-Lock plug to the Y1  
“ECON” terminal.  
NOTE: While the above step will reset any lock outs,  
compressor #2 will be held off for the ASCD, and  
compressor #1 may be held off for a portion of the  
ASCD. See the next step.  
13. If none of the above corrected the error, test the integrity of  
the UCB. Disconnect the C1 terminal wire and jumper it to  
the Y1 terminal. DO NOT jump the Y1 to C1 terminals. If  
the compressor engages, the UCB has faulted.  
10. If 24 volts is present at the UCB Y1 terminal and none of  
the switches are open and the compressor is not locked  
out, the UCB may have the compressor in an ASCD.  
Check the LED for an indication of an ASCD cycle. The  
14. If none of the above correct the error, replace the UCB.  
26  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
430645-YIM-D-0610  
Cooling Charging Curves  
PC090  
600  
500  
400  
300  
200  
115°  
105°  
95°  
85°  
75°  
65°  
120  
130  
140  
150  
160  
170  
180  
Suction Pressure (psi)  
1. Make sure that both condenser fans are running when charging.  
2. This chart is applicable to unit with the TXV’s left to the factory setting. If the TXV’s have been  
adjusted in the field, the charging chart may no longer apply.  
Figure 11: PC090 Charging Chart  
Cooling Charging Curves  
PC120  
600  
500  
400  
300  
115°  
105°  
95°  
85°  
75°  
65°  
200  
120  
130  
140  
150  
160  
170  
180  
Suction Pressure (psi)  
1. Make sure that both condenser fans are running when charging.  
2. This chart is applicable to unit with the TXV’s left to the factory setting. If the TXV’s have been  
adjusted in the field, the charging chart may no longer apply.  
Figure 12: PC120 Charging Chart  
Johnson Controls Unitary Products  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
430645-YIM-D-0610  
Cooling Charging Curves  
PC180  
600  
500  
400  
300  
200  
115°  
105°  
95°  
85°  
75°  
65°  
120  
130  
140  
150  
160  
170  
180  
Suction Pressure (psi)  
1. Make sure that all condenser fans are running when charging.  
2. This chart is applicable to unit with the TXV’s left to the factory setting. If the TXV’s have been  
adjusted in the field, the charging chart may no longer apply.  
Figure 13: PC180 Charging Chart  
Cooling Charging Curves  
PD180  
600  
500  
400  
300  
115°  
105°  
95°  
85°  
75°  
65°  
200  
120  
130  
140  
150  
160  
170  
180  
Suction Pressure (psi)  
1. Make sure that all condenser fans are running when charging.  
2. This chart is applicable to unit with the TXV’s left to the factory setting. If the TXV’s have been  
adjusted in the field, the charging chart may no longer apply.  
Figure 14: PD180 Charging Chart  
28  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
430645-YIM-D-0610  
Cooling Charging Curves  
PC240  
600  
500  
400  
300  
200  
115°  
105°  
95°  
85°  
75°  
65°  
120  
130  
140  
150  
160  
170  
180  
Suction Pressure (psi)  
1. Make sure that all condenser fans are running when charging.  
2. This chart is applicable to unit with the TXV’s left to the factory setting. If the TXV’s have been  
adjusted in the field, the charging chart may no longer apply.  
Figure 15: PC240 Charging Chart  
Cooling Charging Curves  
PD240  
600  
500  
400  
300  
115°  
105°  
95°  
85°  
75°  
65°  
200  
120  
130  
140  
150  
160  
170  
180  
Suction Pressure (psi)  
1. Make sure that all condenser fans are running when charging.  
2. This chart is applicable to unit with the TXV’s left to the factory setting. If the TXV’s have been  
adjusted in the field, the charging chart may no longer apply.  
Figure 16: PD240 Charging Chart  
Johnson Controls Unitary Products  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
430645-YIM-D-0610  
Typical Wiring Diagrams  
Figure 17: Typical PC090 Heat Pump Wiring Diagram  
30  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
430645-YIM-D-0610  
Figure 18: Typical PC120 Heat Pump Wiring Diagram  
Johnson Controls Unitary Products  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
430645-YIM-D-0610  
Figure 19: Typical PC180 - 240 Heat Pump Wiring Diagram  
32  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Figure 20: Typical PD180 - 240 Heat Pump Wiring Diagram  
Subject to change without notice. Printed in U.S.A.  
430645-YIM-D-0610  
Copyright © 2010 by Johnson Controls, Inc. All rights reserved.  
Supersedes: 430645-YIM-C-0310  
Johnson Controls Unitary Products  
5005 York Drive  
Norman, OK 73069  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 

Ingersoll Rand Heat Pump 650684 XXX User Manual
Init TV Video Accessories NT C1142 User Manual
Jasco Mouse 98548 User Manual
JVC Car Stereo System KWR710 User Manual
Kenwood Car Stereo System CA C1AX User Manual
Kenwood Headphones KCA BT100 User Manual
KitchenAid Refrigerator 2004022 User Manual
Klipsch Speaker B 10 User Manual
Klipsch Speaker SW 308 User Manual
Kramer Electronics Car Amplifier VP 200D User Manual