Honeywell Automobile Parts 2000 User Manual

HercuLine® 2000 Series Actuator  
Installation, Operation and  
Maintenance Manual  
Doc. No.:  
Revision:  
Date:  
62-86-25-10  
6
7/07  
Honeywell Field Solutions  
About This Document  
Abstract  
This manual describes the installation, set up, operation, maintenance, and troubleshooting of the  
HercuLine 2000 series actuators.  
References  
The following list identifies all documents that may be sources of reference for material discussed in this  
publication.  
Document Title  
Doc ID  
HercuLine 2000 Series Actuator Specification  
HercuLine 2000 Series Actuator Model Selection Guide  
Modbus® RTU Serial Communications User Manual  
61-86-03-14  
62-86-16-21  
51-52-25-66  
51-52-25-103  
Modbus® RTU Serial Communications User Manual  
Configuration/Remote Calibration Interfaces for HercuLine Actuators  
HercuLink™ User Manual  
62-86-25-11  
62-86-25-12  
HART Communications Installation and Operations Manual  
Contacts  
World Wide Web  
The following lists Honeywell’s World Wide Web sites that will be of interest to our customers.  
Honeywell Organization  
WWW Address (URL)  
http://www.honeywell.com  
http://www.honeywell.com/ps  
Corporate  
Honeywell Process Solutions  
Telephone  
Contact us by telephone at the numbers listed below.  
Organization  
Phone Number  
United States and Canada  
Honeywell  
1-800-423-9883 Tech. Support  
1-800-525-7439 Service  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
iii  
Symbol Definitions  
The following table lists those symbols that may be used in this document to denote certain conditions.  
Symbol  
Definition  
This DANGER symbol indicates an imminently hazardous situation, which,  
if not avoided, will result in death or serious injury.  
This WARNING symbol indicates a potentially hazardous situation, which, if  
not avoided, could result in death or serious injury.  
This CAUTION symbol may be present on Control Product instrumentation  
and literature. If present on a product, the user must consult the  
appropriate part of the accompanying product literature for more  
information.  
This CAUTION symbol indicates a potentially hazardous situation, which, if  
not avoided, may result in property damage.  
WARNING  
PERSONAL INJURY: Risk of electrical shock. This symbol warns the user of a  
potential shock hazard where HAZARDOUS LIVE voltages greater than 30 Vrms,  
42.4 Vpeak, or 60 Vdc may be accessible. Failure to comply with these  
instructions could result in death or serious injury.  
ATTENTION, Electrostatic Discharge (ESD) hazards. Observe precautions for  
handling electrostatic sensitive devices  
Protective Earth (PE) terminal. Provided for connection of the protective earth  
(green or green/yellow) supply system conductor.  
Functional earth terminal. Used for non-safety purposes such as noise immunity  
improvement. NOTE: This connection shall be bonded to protective earth at the  
source of supply in accordance with national local electrical code requirements.  
Earth Ground. Functional earth connection. NOTE: This connection shall be bonded  
to Protective earth at the source of supply in accordance with national and local  
electrical code requirements.  
Chassis Ground. Identifies a connection to the chassis or frame of the equipment  
shall be bonded to Protective Earth at the source of supply in accordance with  
national and local electrical code requirements.  
iv  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Contents  
Contents  
Contents................................................................................................................v  
Introduction ...........................................................................................................1  
Product Description ...................................................................................................................... 1  
Model distinctions.....................................................................................................................................1  
HercuLink® Palm® software......................................................................................................................1  
Specifications........................................................................................................5  
Technical and Operating Specifications.......................................................................................5  
Model Selection Guide ............................................................................................................... 10  
Installation...........................................................................................................12  
Installation Overview .................................................................................................................. 12  
Before Starting............................................................................................................................ 13  
Installation Considerations .....................................................................................................................13  
Actuator Mounting ...................................................................................................................... 13  
Mechanical Installation............................................................................................................... 15  
Linkage Set-up.......................................................................................................................................15  
Electrical Installation................................................................................................................... 17  
General Wiring Recommendations ........................................................................................................17  
Actuator Connections.............................................................................................................................17  
HercuLine® 2000 Terminal Connections ................................................................................................18  
HercuLine® 2001/2002 with Auto/Manual Terminal Connections...........................................................19  
HercuLine® 2003 Wiring Connections and Operation (Actionator 640D Replacement) .........................20  
Burner Control/Flame Safety...............................................................................23  
Introduction ............................................................................................................................................23  
Configuration..........................................................................................................................................23  
Wiring.....................................................................................................................................................23  
Series 90 Control – HercuLine® 2001 model only......................................................................24  
Connections ...........................................................................................................................................24  
Considerations .......................................................................................................................................24  
Split Range................................................................................................................................. 26  
Master/Slave Arrangement......................................................................................................... 26  
Set Up and Calibration Procedures.....................................................................31  
Overview..................................................................................................................................... 31  
Local Display and Keypad.......................................................................................................... 31  
Set Up Tips................................................................................................................................. 33  
Set Up Groups............................................................................................................................ 34  
Set Up Procedure....................................................................................................................... 36  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
v
Contents  
Configuration Prompt Hierarchy.................................................................................................38  
Input Set Up Group..................................................................................................................... 39  
Equal Percentage Valve Characteristic..................................................................................................42  
Quick Opening Valve Characteristic.......................................................................................................43  
Relays Set Up Group.................................................................................................................. 44  
Relay Examples .....................................................................................................................................46  
Current Out Set Up Group.......................................................................................................... 49  
Communications Set Up Group..................................................................................................50  
Digital Input Set Up Group ......................................................................................................... 51  
Display Set Up Group................................................................................................................. 52  
Lock Set Up Group..................................................................................................................... 53  
Set/Change Password ...........................................................................................................................54  
Read Status Set Up Group......................................................................................................... 55  
Drive Set Up Group .................................................................................................................... 56  
Set Tag Name........................................................................................................................................58  
Maintenance Set Up Group........................................................................................................ 59  
Regions of Motor Travel............................................................................................................. 62  
CAL POSOUT Group ................................................................................................................. 63  
Auto - Manual Drive Switch........................................................................................................ 64  
Calibration .................................................................................................................................. 65  
Setting End-of-Travel Limit Switches .........................................................................................78  
Setting Auxiliary Switches .......................................................................................................... 81  
Start-Up/Operation ..............................................................................................83  
Introduction................................................................................................................................. 83  
Power Up Diagnostics ................................................................................................................ 83  
Operations Checklist .................................................................................................................. 83  
Operating Displays ..................................................................................................................... 84  
Motor Stall ..................................................................................................................................84  
Position Sensor Operation ......................................................................................................... 85  
Remote Setpoint Operation........................................................................................................ 85  
Maintenance........................................................................................................87  
Introduction................................................................................................................................. 87  
Basic Maintenance ..................................................................................................................... 87  
Spur Gear Lubrication............................................................................................................................87  
Replacement Procedures........................................................................................................... 89  
Replacement/Upgrade/Accessory Kits................................................................91  
Replacement Kits ....................................................................................................................... 91  
vi  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Contents  
Upgrade Kits.............................................................................................................................102  
Accessory Kits..........................................................................................................................104  
Troubleshooting ................................................................................................105  
Introduction...............................................................................................................................105  
Troubleshooting Procedures ....................................................................................................106  
Appendix A - HercuLine® 2001/2002 Configuration Record Sheet....................112  
Index .................................................................................................................116  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
vii  
Contents  
Tables  
Table 1 Specifications - General..................................................................................................................................5  
Table 2 Recommended Minimum Wire Size.............................................................................................................17  
Table 3 Terminal Connections: HercuLine® 2000....................................................................................................18  
Table 4 Terminal Connections: HercuLine® 2001/2002 with auto/manual..............................................................19  
Table 5 Split Range Set Up Procedure ......................................................................................................................26  
Table 6 Keypad Description......................................................................................................................................32  
Table 7 Set Up Tips...................................................................................................................................................33  
Table 8 Set Up Groups ..............................................................................................................................................34  
Table 9 Set Up Procedure Using Display and Keypad..............................................................................................36  
Table 10 Input Set Up Group Parameters..................................................................................................................39  
Table 11 Equal Percentage Valve Characteristics .....................................................................................................42  
Table 12 Quick Opening Valve Characteristic ..........................................................................................................43  
Table 13 Relay Set Up Group Parameters.................................................................................................................44  
Table 14 Relay Type Descriptions.............................................................................................................................45  
Table 15 Current Out Set Up Group Parameters .......................................................................................................49  
Table 16 Communications Set Up Group Parameters ...............................................................................................50  
Table 17 Digital Input Set Up Group Parameters......................................................................................................51  
Table 18 Display Set Up Group Parameters..............................................................................................................52  
Table 19 Lock Set Up Group Parameters ..................................................................................................................53  
Table 20 Read Status Set Up Group Parameters .......................................................................................................55  
Table 21 Drive Set Up Group Parameters .................................................................................................................56  
Table 22 Maintenance Set Up Group Parameters......................................................................................................59  
Table 23 CAL POSOUT Group Parameters..............................................................................................................63  
Table 24 Auto - Manual Switch Functions................................................................................................................64  
Table 25 Input Calibration Procedure........................................................................................................................69  
Table 26 Motor Calibration Procedure......................................................................................................................70  
Table 27 Output Calibration Procedure.....................................................................................................................71  
Table 28 Slidewire Emulation Calibration Procedure ...............................................................................................73  
Table 29 NCS Position Sensor Calibration Procedure..............................................................................................74  
Table 30 Potentiometer Position Sensor Calibration Procedure...............................................................................76  
Table 31 Load Position Sensor Factory Calibration..................................................................................................77  
Table 32 End-of-Travel Limit Switch Setting Procedure..........................................................................................79  
Table 33 Auxiliary Switch Setting Procedure ...........................................................................................................82  
Table 34 Typical Operating Displays........................................................................................................................84  
Table 35 Spur Gear Lubrication Procedure ...............................................................................................................87  
Table 36 Motor Drive Fuse Replacment Procedure ..................................................................................................89  
Table 37 Relay PWA Replacement Procedure..........................................................................................................90  
Table 38 Replacement kits.........................................................................................................................................96  
Table 39 Observable Symptoms of Failure .............................................................................................................105  
viii  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Contents  
Figures  
Figure 1 HercuLine® 2000 Series Actuator .................................................................................................................2  
Figure 2 HercuLine® 2002 Actuator Internal View.....................................................................................................3  
Figure 3 Outline and Dimensions of HercuLine® 2000 Series Actuators.................................................................14  
Figure 4 Constant Torque Linkage...........................................................................................................................15  
Figure 5 Variable Torque Linkage ............................................................................................................................16  
Figure 6 Standard crank arm......................................................................................................................................16  
Figure 7 Crank arm with optional ball joint and push rod.........................................................................................16  
Figure 8 HercuLine® 2000 connections.....................................................................................................................18  
Figure 9 HercuLine® 2001/2002 connections............................................................................................................19  
Figure 10 HercuLine® 2003 connections..............................................................................................................20  
Figure 11 CE wiring part 1.......................................................................................................................................21  
Figure 12 CE Wiring part 2 .......................................................................................................................................22  
Figure 13 Burner Control/Flame Safety Wiring.......................................................................................................23  
Figure 14 Series 90 connections................................................................................................................................24  
Figure 15 T775 Controller connections....................................................................................................................25  
Figure 16 Flow Diagram............................................................................................................................................27  
Figure 17 Interconnection Diagram...........................................................................................................................27  
Figure 18 Proportional Flow Using Multiple Actuators............................................................................................28  
Figure 19 Multiple Actuator Interconnection Diagrams............................................................................................29  
Figure 20 Interconnection Diagrams .........................................................................................................................30  
Figure 21 HercuLine® 2000 Display and Keypad .....................................................................................................31  
Figure 22 Relay connectors .......................................................................................................................................46  
Figure 23 Regions of Motor Travel...........................................................................................................................62  
Figure 24 Auto - Manual Switch ...............................................................................................................................64  
Figure 25 Calibration Wiring Connections (non-slidewire emulation) .....................................................................66  
Figure 26 Calibration Wiring Connections (slidewire emulation).............................................................................67  
Figure 27 Jumper Location on CPU PWA ...............................................................................................................68  
Figure 28 Location of NCS Assembly.......................................................................................................................75  
Figure 29 Location of potentiometer position sensor ................................................................................................77  
Figure 30 End of Travel Limit Switch Settings.........................................................................................................78  
Figure 31 Location of End-of-Travel Limit and Auxiliary Switches ........................................................................80  
Figure 32 Auxiliary Switch Settings..........................................................................................................................81  
Figure 33 Terminal Block Connections for Modbus Communications.....................................................................86  
Figure 34 Spur Gear Location ...................................................................................................................................88  
Figure 35 Power Distribution PWA and Relay PWA Locations...............................................................................89  
Figure 36 Motor Drive Circuit Fuses.........................................................................................................................90  
Figure 37 Replacement Kits 6, 7, 8, 11, 12, 14..........................................................................................................91  
Figure 38 Replacement Kit 10..................................................................................................................................92  
Figure 39 Replacement Kits 1, 2, 3, 4, 5, 9, 15, 16, 19..............................................................................................93  
Figure 40 Replacement Kit 13...................................................................................................................................94  
Figure 41 Replacement Kits 17, 18 ...........................................................................................................................95  
Figure 42 Test for Actuator Operation ....................................................................................................................107  
Figure 43 Power Up Diagnostics.............................................................................................................................108  
Figure 44 Test Power Distribution PWA.................................................................................................................109  
Figure 45 Test AUTO - MANUAL Switch.............................................................................................................110  
Figure 46 Test Relay Function ................................................................................................................................111  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
ix  
Introduction  
Product Description  
Introduction  
Product Description  
Honeywell’s HercuLine® 2000 series actuators are available in four versions: HercuLine® 2000,  
HercuLine® 2001, HercuLine® 2002, and HercuLine® 2003. All are low torque, precision electric rotary  
actuators incorporating all of the high quality and reliable features of the traditional HercuLine series  
actuators. These precision control and high reliability actuators ensure processes operate at maximum  
efficiency, with minimal downtime, and lowest lifetime cost.  
Honeywell's HercuLine® 2000 series actuators are precision engineered for exceptional reliability,  
accurate positioning, and low maintenance (Figure 1). Designed for very precise positioning of dampers  
and quarter turn valves the HercuLine® 2000 series actuators perform especially well in extremely  
demanding environments requiring continuous-duty, high reliability, and low maintenance.  
Model distinctions  
HercuLine® 2000 series actuators are used in applications requiring on/off or power to open/close position  
proportional with 135 or 1000 ohm feedback.  
HercuLine® 2001 and 2002 are smart actuators used in applications requiring current proportional control  
or digital control. They offer digital electronics providing for precision positioning control, easy set-up and  
configuration, on board health monitoring, and network communications. Programming access is provided  
through our HercuLink® Palm PDA software connected to the actuator via a 232/485 converter, via HART  
communications or through the optional local keypad and display.  
HercuLine® 2002 smart actuators offer features and functions similar to the HercuLine® 2001 and are  
used for more severe service applications requiring features such as non-contact position sensing.  
HercuLine® 2003 actuators are unidirectional/ 360 degree rotation, special purpose actuators.  
The keypad and display are available on the HercuLine® 2001 and HercuLine® 2002 products at  
additional charge.  
HercuLink® Software  
HercuLink® Computer software enables access to programming and communication functions available as  
standard with the HercuLine® 2001 and 2002 actuators without the added expense of the keypad &  
display HMI. Using a PalmPDA, laptop PC or desktop computer, HercuLink® software, and a  
RS232/485 converter users may configure, calibrate, and access maintenance information locally or  
remotely to the actuator.  
Using HercuLink® software, the computer may be used as a master device over a Modbus network to  
access information to/from the actuators and to control the device. Set-up configurations may also be  
stored on the computer for download to other HercuLine® devices. Information may be stored on the users  
PC in CSV format for use in preventative maintenance programs.  
Certified on Palmm125, m130, and m505.  
Compatible with Palm OS3.5 or higher.  
Compatible with Windows 2000 or XP operating systems  
Minimum system requirements:  
Windows 2000 (w/service pack 2), Windows NT (w/service pack 5), Windows ME, Windows XP  
200 MHz Pentium with 64 Megs Ram  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
1
Introduction  
Product Description  
Display and  
keypad  
Handwheel  
Conduit  
entry  
Shaft and  
position indicator  
Auto/manual  
switch  
Figure 1 HercuLine® 2000 Series Actuator  
2
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Introduction  
Product Description  
Display  
Keypad  
PWA  
Wiring  
Label  
Mechanical Stops  
TB3  
Connector  
for customer  
input and  
output  
Cams and  
limit  
switches  
connection  
on CPU  
PWA  
TB1  
customer  
power  
connection  
External  
auto-manual  
switch  
Non-contact  
sensor  
Relay PWAs  
Figure 2 HercuLine® 2002 Actuator Internal View  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
3
Introduction  
Product Description  
4
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Specifications  
Technical and Operating Specifications  
Specifications  
This section provides you with the technical specifications and the model selection guide for the  
HercuLine® 2000 Series Actuators.  
Technical and Operating Specifications  
Table 1 Specifications - General  
Physical  
Weight  
2000: 25 lb. (11.36 kg)  
2001,2002: 27 lbs. (12.27 kg)  
Enclosure  
Precision-machined die cast aluminum housing, finished in light gray powder coat  
epoxy.  
Gear Train  
Mechanical Stops  
Alloy steel, high efficiency steel spur gear primary train. Precision ground, self-  
locking/self releasing worm gear final mesh.  
Factory set at 90° or 150° (+/-5°).  
Attention: Do not adjust the mechanical Stops. Adjusting the stops will void  
the warranty  
Storage Temperature  
Relative Humidity  
Scale  
–40 °C to +93 °C (–40 °C to +200 °F)  
0 % to 99 % R.H. non-condensing over the full operating temperature range.  
0 % to 100 % corresponding to full crank arm travel.  
Crank Arm  
Adjustable radii 1.0 in (25.4mm) to a maximum of 2.8 in (71.1mm). Position  
adjustable through 360° rotation.  
Output Shaft  
Rotation  
0.625+/-.005 in (15.88 +/-.13mm) diameter  
90° or 150° degrees between 0 % and 100 % on scale, limited by mechanical stops.  
Manual Handwheel  
Provides a means of positioning the actuator in the event of a power failure or set-  
up.  
Lubrication  
Texaco Starplex 2 EP Grease  
Torque lb-in (N  
M)  
50 Hz (90°/150°)  
60 Hz (90°/150°)  
Output Torque/Full  
Travel Stroking Time  
4.5 / 7.5  
9 / 15  
18 / 30  
36 / 60  
54 / 90  
4 / 6  
50 / (6.0)  
7 / 12  
15 / 25  
30 / 50  
45 / 75  
100 / (11.5)  
200 / (22.5)  
400 / (45.0)  
400 / (45.0)  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
5
Specifications  
Technical and Operating Specifications  
Electrical  
Mains Supply  
Motor  
100-130 Vac single phase, 50 Hz or 60 Hz  
200-240 Vac single phase, 50 Hz or 60 Hz  
Instant start/stop, non-coasting, non-burnout, continuous duty, permanent  
magnet, synchronous induction motor. Can be stalled up to 100 hours without  
damage.  
Motor Current  
= No load = full load = locked rotor = 0.4 amp for 120Vac, 0.2 amp for 240 Vac  
Stays in place on loss of power  
Loss of Power  
Local Auto/Manual Switch  
Optional – Allows local and automatic operation of the actuator.  
End of travel Limit  
Switches  
Standard – adjustable to limit actuator travel to less than 90 or 150 degrees  
respectively  
Auxiliary Switches/Relays  
Optional – Up to 4 additional SPDT switches rated at (10 A at 125 Vac, 5 A at 250  
Vac).  
Certifications  
Approvals  
CSA/UL (Standard)  
CE Compliant (optional)  
Enclosure Rating  
Type 4 (NEMA 4), IP66 (standard)  
Torque Settings of Crank Arm Bolts  
88 lb-in (10 N-m)  
Clamp Bolt  
Electrical and Performance Specifications  
HercuLine® 2002  
Analog:  
HercuLine® 2001  
Analog:  
HercuLine® 2000/2003  
Input Signals  
0/4 to 20 mA (With CPU  
PWA jumper in current  
position)  
0/4 to 20 mA (With CPU  
PWA jumper in current  
position)  
120 vac drive open/120 vac  
drive close  
240 vac drive open/240 vac  
drive close  
0/1 to 5 Vdc  
0 to 10 Vdc  
Digital:  
0/1 to 5 Vdc  
0 to 10 Vdc  
Series 90 control  
Digital:  
Modbus RTU (RS485)  
Modbus RTU (RS485)  
Isolation  
Input signal, output signal and power are isolated from each other.  
Current Out — 0 to 1000 ohms  
NA  
NA  
NA  
Load Requirement (4-20)  
Input Impedance  
0/4 to 20 mA  
250 ohms  
10 K ohms  
0/1 to 5 Vdc  
0-10 vdc  
Feedback  
0 to 20 mA, 4 to 20 mA  
Dual output 1000 ohms  
over 90 degrees (135 ohms  
with 158 resistor)  
0 to 5 Vdc & 1 to 5 Vdc with 250 ohm resistor, (0 to 16 Vdc with 800  
ohm resistor)  
Dual output 1000 ohms  
over 150 degrees (135  
ohms with with 158 resistor)  
6
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Specifications  
Technical and Operating Specifications  
HercuLine® 2002  
HercuLine® 2001  
HercuLine® 2000/2003  
Feedback  
Slidewire emulation - Provides  
output voltage ratiometric to  
shaft position and  
potentiometric to supply voltage  
(1 Vdc to 18 Vdc) without a  
slidewire. Emulates a 100 ohm  
to 1000 ohm slidewire. 10 mA  
output maximum.  
Communications  
NA  
Modbus RTU or optional HART  
Operating Temperature  
–40°C to +75 °C (–40°F to +170 °F)  
-40°C to +85 °C (-40°F to  
+185 °F)  
Position sensing  
Non-contact position sensor  
1000 ohm film potentiometer  
Dual 1000 ohm film  
potentiometers  
(not on 2003)  
Sensitivity  
Hysteresis  
Deadband  
Repeatability  
0.2 % to 5 % of 90° span, proportional to deadband  
Less than 0.4 % of full scale  
NA  
NA  
NA  
NA  
0.2 % to 5 % of 90° span, programmable. Shipped at 0.5 %  
0.2 % of 90° span  
Repositions  
(minimum @ 90 or 150  
degree stroke)  
Table 1 option –050-  
Table 1 option –100-  
Table 1 option –200-  
Table 1 option –400-  
Table 1 option –600-  
160  
290  
450  
700  
900  
120  
250  
400  
400  
400  
500  
Voltage/ Supply  
Stability  
0.25 % of span with +10/–15 % voltage change  
NA  
NA  
Temperature  
Coefficient  
Less than ± 0.030 % of span per degree C for 0 °C to 50 °C  
Less than ± 0.05 % of span per degree C for –40 °C to 75 °C  
90 % of span.  
Zero Suppression  
Input Filters  
NA  
NA  
NA  
Selectable spike and low pass filters.  
Solid State Motor  
Control  
Two triac switches for clockwise or anti-clockwise motor operation.  
Transient voltage protection provided.  
Failsafe operation  
If input signal exceeds configured input range. Selectable and  
adjustable.  
NA  
Direction of Rotation  
Duty Cycle  
Field programmable  
Continuous  
Wire swap  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
7
Specifications  
Technical and Operating Specifications  
HercuLine® 2002  
HercuLine® 2001  
HercuLine® 2000/2003  
Programmable  
Functions  
Selectable and configurable operating parameters:  
NA  
Input range  
Input filtering  
Input characterization  
Security  
Digital Input action  
Deadband  
Failsafe on loss of input signal  
Failsafe on loss of position sensor  
Direction of rotation  
Relay closure action  
Communication parameters  
Split range operation  
Output range  
Alarms  
Specifications – Local Display and Keypad  
Display  
Display Design  
LED indicators  
Multi-segment LED displays that provides up to ten alphanumeric characters. Display  
arrangement consists of two rows:  
1st row (Upper display) – four characters  
2
nd row (Lower display) – six characters.  
Six single LEDs provide actuator status and alarm indications.  
Display Operating  
Temperature  
-30 °C to +50 °C (-20 °F to +122 °F)  
Automatically shuts off when operating temperature exceeds +50 °C  
Storage Temperature  
-40 °C to +93 °C (-40 °F to +200 °F)  
Keypad  
Keys  
Six single pushbutton keys allow access to all status displays and set up group  
parameters.  
See Set Up and Calibration Procedures (page 31) for detailed information on display and keypad functions.  
8
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Specifications  
Technical and Operating Specifications  
Specifications – Communications  
Communications  
Communications  
Option  
RS 485 Serial Communication, Modbus RTU Protocol  
Connection  
Twisted pair cable with shield  
600 meters (2000 feet)  
Maximum loop length  
Communication Mode  
Baud Rate  
Half duplex  
300, 600, 1200, 2400, 4800, 9600, 19.2K  
Required Specifications – PDA (customer provided)  
PDA  
Operating System  
RAM  
Palm OS version 3.5 or greater  
At least 8 MB  
Communications  
Serial port with RS232 compatible levels to drive external converter  
Note: As of this writing only Palm devices have this feature. Honeywell has qualified  
the M105, M125, M130, and M505 devices with the HercuLink application.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
9
Specifications  
Model Selection Guide  
Model Selection Guide  
Instructions  
Select the desired key number. The arrow to the right marks the selection available.  
Make the desired selections from Tables I thru VIII using the column below the arrow.  
A dot ( ) denotes unrestricted availability.  
Key Number  
I
II  
III  
IV  
V
VI  
VII  
VIII  
IX  
_ _ _ _  
-
_ _ _  
-
_ _ _  
-
_ _ _  
-
_ _ _ - _ _  
-
_ _ _ _ _ _  
-
_
-
_
-
_ _  
KEY NUMBER - Motor Selection  
Basic Motor Unit (no electronics)  
Selection  
2000  
Availability  
Basic Motor Unit plus Digital Electronics  
2001  
Enhanced Performance Motor Unit with Non-contact Position Sensing  
Unidirectional Motor (M640D Replacement)  
2002  
2003  
TABLE I - TORQUE & SPEED SELECTION (speed per 150 degree rotation)  
Torque, lb-in/(N-M)  
50 / (6.0)  
100 / (11.5)  
200 / 22.5)  
400 / (45.0)  
400 / (45.0)  
50Hz  
7.5 sec  
15 sec  
30 sec  
60 sec  
90 sec  
60Hz  
6 sec  
12 sec  
25 sec  
50 sec  
75 sec  
050  
100  
200  
400  
600  
TABLE II - ROTATION  
Travel  
90 degrees  
150 degrees  
360 degrees  
090  
150  
360  
TABLE III - POWER SUPPLY  
Single Phase 100 - 130 Vac, 60 Hz  
126  
125  
246  
245  
100 - 130 Vac, 50 Hz  
200 - 240 Vac, 60 Hz  
200 - 240 Vac, 50 Hz  
TABLE IV - ANALOG INPUT/OUTPUT SIGNALS  
Input  
3 Wire Drive up/down  
0 _ _  
2 _ _  
3 _ _  
4 _ _  
6 _ _  
_ 00  
_ 15  
_ 19  
_ 60  
_ 65  
_ 80  
_ 85  
0/4-20 mA, 0/1-5 Vdc, 0-10 Vdc  
0/4-20 mA, 0/1-5 Vdc, 0-10 Vdc  
0 to 135 ohm input (Series 90 control)  
Contact Input for 2003  
a
Output  
None  
(Note 1)  
(Note 1)  
b
c
Dual 1000 Ohm (1000 ohms over 150 degrees)  
Dual 1000 Ohm (1000 ohms over 90 degrees)  
Slidewire Emulation  
Slidewire Emulation  
0/4-20mAdc (0/1-5 Vdc, 0-16 Vdc)  
0/4-20mAdc (0/1-5 Vdc, 0-16 Vdc)  
TABLE V - SWITCH AND RELAY OUTPUTS (2 end-of-travel switches are standard)  
Auxiliary Outputs  
No Auxiliary Switches  
2 Auxilliary Switches  
4 Auxilliary Switches  
No Relays  
0 _  
2 _  
4 _  
_ 0  
_ 2  
_ 3  
_ 4  
Relay Outputs  
2 Programmable Relay Outputs  
2 Programmable Relay Outputs  
4 Programmable Relay Outputs  
continued  
10  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Specifications  
Model Selection Guide  
2000 2001 2002 2003  
TABLE VI - OPTIONS  
Local keypad/  
display  
Selection  
0_ _ _ _ _  
1_ _ _ _ _  
_ 0_ _ _ _  
_ 1_ _ _ _  
_ 2_ _ _ _  
_ _ 0_ _ _  
_ _ 1_ _ _  
_ _ _ 0 _ _  
_ _ _ 1_ _  
_ _ _ _ 0_  
_ _ _ _ 1_  
_ _ _ _ _0  
_ _ _ _ _1  
No local display interface supplied  
(Note 2)  
Integrally mounted local display/keypad interface  
No auto/manual switch  
Local Auto/  
manual switch  
Auto/manual switch with "Out of Auto Contact"  
Auto/manual switch with "Out of Auto Contact"  
No Handwheel  
Handwheel  
Handwheel  
Certificates  
Approvals  
None  
Certificate of Conformance  
UL Type 4/IP66, CSA  
CE  
(Note 4)  
Shipped Rotation  
Counter clockwise shaft rotation on increasing signal  
Clockwise shaft rotation on increasing signal  
TABLE VII - COMMUNICATIONS/PROTOCOL  
None  
No communications option board or protocol  
0
1
2
Modbus RTU RS485 RS-485 Modbus compliant - standard with EEU  
HART 5  
HART Communications Protocol  
TABLE VIII - MANUALS  
Standard  
English  
0
TABLE IX - FACTORY OPTIONS  
Factory Options  
None  
00  
Restrictions  
Restriction  
Letter  
Available Only With  
Not Available With  
Table  
Selection  
_ 00  
Table  
Selection  
IV  
II  
IV  
II  
_ 60, _ 80  
090  
a
b
c
150  
090  
150  
II  
II  
ACCESSORIES  
Mounting Hardware  
Mounting plate adapter for Barber Colman Series MP495  
Mounting plate adapter for Landis & Staefa SQM53/56  
Direct Couple Valve Hardware  
51452354-501  
51452354-502  
51452354-503  
51452354-511  
51452354-504  
51452354-505  
51452354-506  
51452354-507  
51452354-508  
51452352-501  
51452354-509  
51452354-510  
R7195A1031  
R7195A1056  
R7195A1064  
R7195B1021  
North American Valve Retrofit Kit  
Linkage Assembly  
Ball joint for 5/16" dia. Pushrod  
Pushrod 12 in. (304,5 mm) long, 5/16 " dia.  
Pushrod 18 in. (457,2 mm) long, 5/16 " dia.  
Pushrod 24 in. 609,6 mm) long, 5/16 " dia.  
Pushrod 48 in. (1219,2 mm) long, 5/16 " dia.  
Turk Cable for Handheld Connection  
HART  
HercuLinkTM Palm Software  
Handheld Config.  
(Note 3)  
Battery powered 232/485 converter with cable  
Remote 4-20 mA requires 135 ohm fdbk, 120V 50/60Hz  
Remote 4-20 mA requires 1000 ohm fdbk, 120V 50/60Hz  
Remote 4-20 mA requires 135 ohm fdbk, 220V 50/60Hz  
Remote 135 ohm input requires 135 ohm fdbk, 120V 50/60Hz  
Remote Mount  
Control  
Notes:  
1. 135 ohm available by parallelling 1K potentiometer with 158 Ohm resistor (supplied).  
2. HercuLinkTM software (pn 51452354-509), RS232/485 converter (pn 51452354-510),  
customer supplied PalmTM PDA running OS3.5 or higher and Palm serial cable are required  
for the 2001 and 2002 actuators if no display is selected.  
3. Requires PDA manufacturer's serial interface cable.  
4. CSA approval is good for 75°C and a maximum relay load of 3.5 amps or 70°C with a  
relay load of 5 amps.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
11  
Installation  
Installation Overview  
Installation  
Installation Overview  
The procedures to install the HercuLine® 2000 Series actuator and place it in service require that you:  
Select a suitable location for installation. (See Installation Considerations below.)  
Mount the actuator securely.  
Install mechanical connections or linkage between control arm and final control element. Use HAL software  
application to aid in mechanical installation.  
Make all electrical connections for actuator according to local and national electrical codes.  
Power up actuator.  
Enter, verify and adjust set up parameters for proper operation.  
Adjust control arm linkage for accurate operation of final control element.  
This section provides you with mechanical and electrical installation information required to mount and connect  
the HercuLine® 2000 Series Actuator to your specific application. Unpacking instructions, installation  
consisderations, electrical and safety precautions also included in this section should be observed.  
Mechanical Stops  
Factory set at 90° or 150° (+/-5°).  
See Figure 2 for location.  
Attention: Do not adjust the mechanical Stops. Adjusting the stops will void the warranty  
12  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Installation  
Before Starting  
Before Starting  
Unpacking  
If there are visible signs of damage to the shipping container, notify the carrier and Honeywell immediately.  
If there is no visible damage, compare the contents with the packing list. Notify the carrier and Honeywell  
immediately if there is equipment damage or shortage.  
Please do not return goods without contacting Honeywell Applications Center in advance. The contact number  
is 1-800-423-9883.  
Installation Considerations  
Mount the actuator in a location where it will be easily accessible for maintenance and for manual operation by  
means of the handwheel. The exact location must be determined in accordance with the linkage used.  
It is important that the actuator be mounted securely to a solid foundation commensurate with the maximum  
torque developed. Use studs or bolts that are as large as the foot mounting holes.  
Allocate sufficient clearance around the actuator for the removal of all covers to permit inspection of internal  
parts and to provide access to the handwheel.  
Actuator Mounting  
Firmly bolt the actuator to a mounting surface that will not distort when subjected to the torque stresses  
generated by the actuator. The output shaft of the actuator should be parallel to the output shaft of the driven  
device. The output shaft crank arm is fully adjustable through 360°.  
Mounting holes (bottom and side) and location of shaft/crank arm duplicate mounting for Honeywell  
Actionators M640A, 740A, 940A for drop-in replacement. Optional adaptor plates available for replacing  
Landis and Staefa SQM53/56 and Barber Coleman series MP495 models.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
13  
Installation  
Actuator Mounting  
CLEARANCE FOR TOP REMOVAL:  
101,6  
4.0  
289  
11.379  
25.4  
1.00  
mm  
inches  
Figure 3 Outline and Dimensions of HercuLine® 2000 Series Actuators  
14  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Installation  
Mechanical Installation  
Mechanical Installation  
Linkage Set-up  
Many applications require the use of a linkage assembly and often the final control element does not have a  
linear torque curve. The actuator linkage can be set up to achieve an optimal delivered torque distribution for  
specific applications. To assist with linkage design, Honeywell offers a linkage analysis software application  
(HAL). The software can be ordered as P/N 51197910-001.  
Constant Torque Linkage (typical)  
A constant torque linkage is employed when it is desired to provide a linear torque profile throughout the full  
range of final control element travel. In this situation, the actuator and driven crank arms will be set-up  
proportionally with respect to each other. Figure 4 shows a general linkage setup to achieve a linear torque  
profile.  
Vertical  
Centerline  
Vertical  
Centerline  
45°  
45°  
45°  
45°  
Linkage  
Start  
Stop  
Close  
Open  
Drive Unit  
Crank Arm  
Damper  
Crank Arm  
Horizontal Offset  
a/n 23199  
Figure 4 Constant Torque Linkage  
Variable Torque Linkage  
A variable torque linkage is employed when it is desired to provide a non-linear torque profile throughout the  
full range of final control element travel. In this general situation, the actuator and driven crank arms will be set  
up to provide a higher torque for seating or unseating the final control element. Figure 5 shows a general  
linkage setup to achieve a non-linear torque profile. Note that this linkage can be characterized in many  
different ways by varying start angles and rotation requirements of both the Actuator Crank Arm and the Driven  
Arm.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
15  
Installation  
Mechanical Installation  
Vertical  
Vertical  
Centerline  
Centerline  
45°  
45°  
Actuator  
Crank Arm  
Linkage  
Close  
Open  
5°  
Damper  
Horizontal Offset  
Crank Arm  
a/n 23200  
Figure 5 Variable Torque Linkage  
Actuator Crank Arms  
The HercuLine® 2000 Series Actuator comes standard with a crank arm with adjustable radius of 1.0 in  
(25.4mm) to 2.80 in (71.12mm). See Figure 6.  
Figure 6 Standard crank arm  
Figure 7 Crank arm with optional ball joint and push rod  
16  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Installation  
Electrical Installation  
Electrical Installation  
General Wiring Recommendations  
Only qualified personnel should perform wiring.  
Wiring must conform to national and local electrical codes.  
In general, copper wire used. Unless locally applicable codes dictate otherwise, the recommended minimum  
wire sizes in Table 2 should be observed.  
Table 2 Recommended Minimum Wire Size  
AWG  
14  
Description  
Earth ground wire to common power supply.  
18  
Earth ground wire to single actuator. 120/240 V ac line leads. +24 V and common  
signal leads. Common signal leads, relays, and aux switches.  
Safety Precautions  
An external disconnect switch must be installed to break all current carrying  
conductors connected to the actuator. Turn off power before working on  
conductors. Failure to observe this precaution may result in serious personal injury.  
Actuator Connections  
ATTENTION  
The ground terminal must be connected to a reliable earth ground.  
While the unit is powered, a potentially lethal shock hazard exists inside the case.  
Do not open the case while the unit is powered. Do not access the terminals while  
the unit is powered.  
The actuator terminal connections for the field wiring are located behind the cover on the actuator case as  
shown in Figure 2. Power and field wiring is brought into the actuator through two access holes located on the  
side of the actuator case.  
Use both openings: one for low level wiring (control signal) and the other for high  
level wiring (120Vac).  
Do not run both the High Level and Low Level wiring through the same  
opening.  
The screw terminals, locations, and descriptions for all customer connections are identified in the tables and  
figures that follow.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
17  
Installation  
Electrical Installation  
HercuLine® 2000 Terminal Connections  
Table 3 Terminal Connections: HercuLine® 2000  
Connection  
Terminal Numbers  
and LABEL  
Descriptions  
See Figure 8  
Hot  
1
Hot wire for 120/240VAC mains supply. Use only if Auto/Manual  
switch is present.  
Neutral  
2
Neutral wire for 120/240VAC mains supply  
Auto/Manual Switch  
Contact  
3
4
Switch contact to indicate setting of actuator AUTO/MANUAL  
switch.  
Switch is closed when actuator is “NOT-IN-AUTO”  
CW motor drive  
CW from Controller  
CCW from Controller  
Potentiometer #1  
5
6
CCW motor drive  
7
8
9
Clockwise-End  
Slider  
Counterclockwise-End  
Potentiometer #2  
Protective Ground  
10  
11  
12  
Clockwise-End  
Slider  
Counterclockwise-End  
Ground wire connection for mains supply  
158 ohm  
158 ohm  
Install resistors to convert 1000 ohm  
potentiometer to 135 ohms  
1
REQUIRED ONLY IF AUTO/MANUAL  
SWITCH IS PRESENT  
1
Figure 8 HercuLine® 2000 connections  
18  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Installation  
Electrical Installation  
HercuLine® 2001/2002 with Auto/Manual Terminal Connections  
Table 4 Terminal Connections: HercuLine® 2001/2002 with auto/manual  
Connection  
Terminal Numbers  
and LABEL  
Descriptions  
See Figure 9  
TB1  
Hot  
1
2
3
Hot wire for 120/240VAC mains supply  
Neutral wire for 120/240VAC mains supply  
Ground wire connection for mains supply  
Neutral  
Protective Ground  
Auto/Manual Switch  
Contact  
4
5
Switch contact to indicate setting of actuator AUTO/MANUAL  
switch.  
Switch is closed when actuator is “NOT-IN-AUTO”  
6
TB3  
4 to 20mA Output*  
Feedback  
1 (+)  
2 (-)  
Analog signal output  
3
Feedback signal used in conjunction with 4 to 20mA OUTPUT  
voltage when using Slidewire Emulation  
4 to 20mA Input  
4 (+)  
5 (-)  
Analog signal input  
Modbus  
6 (+)  
Connection for RS485 Modbus loop wires  
Communication  
7 (-)  
8 Shield  
HART Communications  
Digital Input  
4 (+)  
5 (-)  
HART Communication is 4-20 mA only.  
Customer’s contact closure  
9 Com  
10 Input  
HART  
Communications  
Connection  
_
+
HART connection using  
external Turck connector  
Auxiliary  
Connector  
_
+
Brown  
Blue  
Black  
Black Wire Not Used  
Figure 9 HercuLine® 2001/2002 connections  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
19  
Installation  
Electrical Installation  
HercuLine® 2003 Wiring Connections and Operation (Actionator 640D Replacement)  
Wiring  
Figure 10 HercuLine® 2003 connections  
Operation  
The 2003 actuator is uni-directional (it does not reverse rotation with a reversal in control action).  
Figure 10 illustrates the internal wiring and the external connections.  
The smaller insert of the figure describes the limit switch action for one complete cycle. When the two-position  
controller detects a sufficient fall in temperature in a heating application, the switch portion between the “4” and  
“5” terminals will close.  
The motor then rotates for 180º or until the opening switch breaks (stops are adjustable, factory set at 180º), and  
stops in full open position.  
A subsequent rise in temperature causes the controller to close the switch between the “4” and “6” terminals  
when the motor will start to rotate (in the same direction) for 180º or until the closing switch breaks.  
The motor stops in the closed position and completes one cycle.  
20  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Installation  
Electrical Installation  
Power Connections  
Depending on which power supply selection is ordered for your actuator, wire the power input (MAINS  
POWER) as described in the previous tables and figures. Wiring must conform to national and local electrical  
codes.  
CE Wiring  
When wiring the actuator power input for CE approved units, you must also install a MOV and ferrite beads  
supplied with the CE unit.  
You need the following tools:  
5mm hex key  
small flat blade screwdriver  
small needle nose pliers  
While the unit is powered, a potentially lethal shock hazard exists inside the case.  
Do not open the case while the unit is powered. Do not access the terminals while  
the unit is powered.  
Step  
1
Action  
Remove AC power to actuator.  
2
Loosen the 6 captive screws (use 5mm hex key) and remove the cover.  
Locate the terminals TB1-1, TB1-2 and ground screw.  
3
4
Loosen the screws at terminals TB1-1 and TB1-2. Remove screw used for ground.  
Install the appropriate MOV assembly as shown in Figure 11.  
All ferrites require 1 loop of wire per ferrite. Connect as shown in following steps.  
Current input and output (slidewire emulation) connection  
Communications and digital input connection  
5
6
7
Ground  
screw  
Current input  
and output  
(slidewire  
TB1-2  
TB1-1  
emulation)  
Communications  
and digital input  
Figure 11 CE wiring part 1  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
21  
Installation  
Electrical Installation  
Step  
8
Action  
AC power connection  
Auxiliary switches connection  
Relay contact connection  
Aux switches  
1 and 2  
(SW3 and SW4)  
Aux switches 3  
and 4  
(SW5 and SW6)  
Relays 1 and 2  
Relays 3 and 4  
AC power  
connection  
Figure 12 CE Wiring part 2  
9
Install new gasket and top cover. Secure top cover with 6 captive screws.  
Reapply AC power to the actuator.  
10  
11  
Actuator is ready for use.  
Input Signal Connections  
ATTENTION  
Shielded and grounded cables are recommended.  
0/4-20 mA Input Signals  
For current signal input, ensure jumper W2 on the CPU PWA is in the “Current” position. See Figure 27 on  
page 68. Observing polarity, connect the signal input wires TB3–4(+) and TB3–5(-) on CPU terminal board.  
0/1-5 Vdc and 0 to 10 Vdc Input Signals  
For voltage signal input, ensure jumper W2 on the CPU PWA is in the “Voltage” position. See Figure 27 on  
page 68. Observing polarity, connect the signal input wires to terminals TB3–4(+) and TB3–5(-) of the terminal  
block.  
22  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Burner Control/Flame Safety  
Electrical Installation  
Output Signal Connections  
0/4-20 mA, 0/1-5 Vdc Feedback Signal Connections  
ATTENTION  
Shielded and grounded cables are recommended.  
Actuator output is a 4 to 20 mA analog signal. If a voltage input is required for customer devices, a range  
resistor is needed at the device input. Refer to (page 19) for more information.  
Slidewire Emulator Connections  
ATTENTION  
Shielded and grounded cables are recommended.  
If you ordered the Slidewire output option for your actuator, it is set at the factory to provide an output that  
emulates 100 to 1000 ohm slidewires. Refer to (page 19) for more information.  
Burner Control/Flame Safety  
Introduction  
Often, Gas Fired control applications use a Flame Safety System that drives the gas valve to full closed and full  
open during the start-up sequencefor the burner. HercuLine® 2000 Series actuators have been designed to be  
compatible with the Flame Safety Systems and to perform the required operations.  
Configuration  
In the Input Set Up Group (Page 39), configure the parameter FSTYPL to Down .  
In the Digital Input Set Up group (Page 51), configure the parameter DIG INP to Up.  
Wiring  
Figure 13 Burner Control/Flame Safety Wiring shows a Typical Flame Safety Module wiring diagram.  
HercuLine TB3  
4
1
2
3
5
6
7
8
9
10  
High Fire  
Common  
To TB3 #10  
To TB3 #5  
+
Add Jumper  
Low Filter  
+ 4 to 20 Output from Controller  
– 4 to 20 Output from Controller  
Modulate  
Typical Flame  
Safety Module  
Figure 13 Burner Control/Flame Safety Wiring  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
23  
Burner Control/Flame Safety  
Series 90 Control – HercuLine® 2001 model only  
Series 90 Control – HercuLine® 2001 model only  
Series 90 Controls are commonly used in building environmental systems and flame safeguard systems to  
provide modulating control. The control is affected by balancing a 135 ohm potentiometer. The HercuLine  
2001 provides an emulation of this system as follows. The current output is used to excite the potentiometer in  
the controller. To do this it is set permanently at 11 ma. This produces a 1.5 volt span. The wiper is then  
connected to the HercuLine 2001 input, which is operating in voltage mode. The returns from both the input  
and the output are tied together.  
Series 90 terminals are typically color coded white, red and blue. Conventionally, red is the wiper and white  
and blue are the two ends of the potentiometer. On a drop in temperature, the wiper moves toward the blue  
terminal.  
Connections  
TB3  
White  
1+  
2-  
4-20mA output  
4-20mA input  
4+  
5-  
Red  
Blue  
Figure 14 Series 90 connections  
Considerations  
1. This connection performs an emulation of a series 90 motor. If the controller being used is also an  
emulation of a Series 90, the connections required may be different. Shown in Figure 15 are the  
connections found necessary to connect a T775 controller through an S443A S90 Auto/Manual Control. If  
the controller has the capability to provide a 4/20 or voltage output, it is easier to use that mode. It will  
require only two wires and it will allow the independent use of the 4/20 output. If help is required, contact  
Honeywell.  
2. Due to variations in the definition of rotation directions, it may be necessary to reverse the action of the  
actuator from CCW to CW or vice versa.  
24  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Burner Control/Flame Safety  
Series 90 Control – HercuLine® 2001 model only  
Auto  
W
T775 B 3  
T775 W 1  
I out from  
HercuLine2001  
W
R
R
+ Signal to  
HercuLine2001  
Man  
GND to  
HercuLine2001 (2)  
B
B
T775 R 2  
Figure 15 T775 Controller connections  
3. In the T775 controller manual there are several examples of using resistances or potentiometers as high and  
low limit controls. Because of the mode of emulation of Series 90, it is likely that these connections will  
not work as intended. Instead, use the output or input limits which are programmable in the  
HercuLine® 2001.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
25  
Burner Control/Flame Safety  
Split Range  
Split Range  
The HercuLine® 2001/2002 actuators can be set up to operate within a narrow input range (for example,  
4 to 12mA input) in certain applications. The procedure in Table 5 describes how to set up an actuator  
to operate as part of a split valve configuration.  
Table 5 Split Range Set Up Procedure  
Step  
Action  
To Set Actuator span to operate from 4 to 12 mA input.  
1
2
3
4
5
6
Enter Set Up mode by pressing SET UP key  
Select SET INPUT group  
Press FUNCTION key until INP HI (on lower display) is selected.  
Set INP HI value to 50.0  
Press FUNCTION key to select INP LO and set value to 0.0  
Press DISPLAY key to exit Set Up mode.  
To Set Actuator span to operate from 12 to 20 mA input.  
1
2
3
4
5
6
Enter Set Up mode by pressing SET UP key  
Select SET INPUT group  
Press FUNCTION key until INP HI (on lower display) is selected.  
Set INP HI value to 100.0  
Press FUNCTION key to select INP LO and set value to 50.0  
Press DISPLAY key to exit Set Up mode.  
ATTENTION  
Be sure to review failsafe strategy for your process application.  
Master/Slave Arrangement  
Introduction  
With the motor positioner, the controlling signal for the actuator is a 4 to 20mA from a current output  
controller as shown in the flow diagram in Figure 16.  
Unlike the position output controller, the current output controller must produce a continuous analog  
signal or the actuator will revert to one of its failsafe states. Signal failure is not a problem since the  
available failsafe settings allow you to set the actuator position on signal loss.  
26  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Burner Control/Flame Safety  
Master/Slave Arrangement  
Basic Flow Control  
When the process variable signal is below set point, the controller increases current (4 to 20mA) to the  
actuator input and opens the valve. Controller set point governs valve position to obtain desired flow  
rate.  
Orifice Plate  
PV  
FT  
Positioner & Actuator  
Controller  
4 to 20 mA  
Valve  
SP  
Linkage  
MP  
FIC  
Position  
mA  
Figure 16 Flow Diagram  
Current Output Controller  
Actuator  
See Figure  
27 for jumper  
location  
Jumper W2  
Hot  
Neutral  
Ground  
+
= Current  
120/240  
VAC  
4 to 20 mA  
-
Figure 17 Interconnection Diagram  
Proportional Flow using Multiple Actuators  
Refer to flow diagram in Figure 18 and interconnection diagrams in Figure 19. The controller governs  
flow rate in one burner. Only that flow is measured. Since #2 and #3 motor positions receive the same  
signal as #1 motor positioned, valves #2 and #3 will deliver the same amount of fuel. This is true when  
the span and zero adjustment are all set the same as in curve 2 of the graph. Other relationships between  
units exist if the span adjustment (3) for ratio or if the zero adjustment is changed (1) for bias.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
27  
Burner Control/Flame Safety  
Master/Slave Arrangement  
Orifice Plate  
FT  
PV  
Positioner & Actuator  
Controller  
Valve  
SP  
4 to 20 mA  
Linkage  
MP  
#1  
FIC  
Linkage  
Valve  
MP  
#2  
Proportional  
with Bias  
Linkage  
Valve  
MP  
#3  
Ratio  
Position  
mA  
Figure 18 Proportional Flow Using Multiple Actuators  
Actuator #1  
10260S Series Actuator #1  
Current Output Controller  
Jumper W2  
= Current  
Hot  
+
-
120/240  
VAC  
Neutral  
Ground  
1 to 5 VDC  
4 to 20 mA  
Actuator #2  
Note: Controller must  
be capable of sourcing  
the impedance.  
10260S SeeAuato#2  
Jumper W2  
= Current  
Hot  
Neutral  
Ground  
See Figure  
27 for jumper  
location  
120/240  
VAC  
Actuator #3  
10
Jumper W2  
Hot  
= Current  
Neutral  
Ground  
120/240  
VAC  
Preferred  
Wiring  
NOTE: If using HART® communications, for this application HART®must be configured for Multi-drop operation.  
28  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Burner Control/Flame Safety  
Master/Slave Arrangement  
Current Output Controller  
10Actuator#1
Hot  
Neutral  
Ground  
Jumper W2  
+
120/240  
VAC  
= Current  
4 to 20 mA  
-
10
Actuator #2  
ot  
120/240  
VAC  
Jumper W2 eutral  
round  
= Voltage  
See Figure  
27 for jumper  
location  
10260S Series Actuator #3  
Actuator #3  
Hot  
eutral  
round  
120/240  
VAC  
Alternate  
Wiring  
Jumper W2  
= Voltage  
Figure 19 Multiple Actuator Interconnection Diagrams  
NOTE: If using HART® communications, for this application HART® must be configured for Multi-drop operation.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
29  
Burner Control/Flame Safety  
Master/Slave Arrangement  
Split Valve Configuration  
A common heat or cool type process requires two valves. In this case the controller has only one output.  
The two motor positioners are calibrated differently, one responds to 4 to 12mA and the other responds  
to 12 to 20mA. At 12mA, both valves are closed; one opening below 12mA and the other above 12mA.  
Refer to Figure 20 for an interconnection diagram for split valve operation using two actuators.  
Current Output Controller  
1
Actuator #1  
Hot  
Neutral  
Ground  
Jumper W2  
+
120/240  
VAC  
= Current  
4 to 20 mA  
-
Actuator #2  
Note: Controller must  
be capable of sourcing  
the impedance.  
1
See Figure  
27 for jumper  
location  
Jumper W2  
Hot  
= Current  
120/240  
VAC  
Neutral  
Ground  
Preferred  
Wiring  
NOTE: If using HART® communications, for this application HART® must be configured for Multi-drop operation.  
Actuator #1  
1
Current Output Controller  
Jumper W2  
Hot  
Neutral  
Ground  
+
= Current  
120/240  
VAC  
4 to 20 mA  
-
Actuator #2  
1
See Figure  
27 for jumper  
location  
Jumper W2  
Hot  
Neutral  
Ground  
= Voltage  
120/240  
VAC  
Alternate  
Wiring  
Figure 20 Interconnection Diagrams  
NOTE: If using HART® communications, for this application HART® must be configured for Multi-drop operation.  
30  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Overview  
Set Up and Calibration Procedures  
Overview  
Once you have installed the actuator, you can verify, set or change certain operating parameters. Set up is  
accomplished through use of the local display and keypad interface through your PDA with HercuLink®  
software (see HercuLink® manual 62-86-25-11) or via the HART® communication option. Please keep in  
mind that the unit is calibrated at the factory for your application and can be placed into service right out of  
the box. Changing operating parameters may require recalibration of the actuator. This section details the  
various operating parameters and functions of the actuator available using the local display and keypad  
interface, and calibration procedures.  
Local Display and Keypad  
The alphanumeric display and keys on the keypad are the local operator interface for control, monitoring,  
and configuration of the actuator. The display consists of a four character upper display and a six character  
lower display. Six LEDs of various colors indicate actuator-operating status. Directly below the display  
are six keys that allow you to setup, monitor, and control the actuator locally, as well as call up various  
operating parameters and configuration values on the display. Figure 21 shows the physical features of the  
display and keypad. Table 6 summarizes the various functions you can perform using the keys as well as  
descriptions of the status indicators.  
STALLED  
ALARM  
Upper Display  
(Four Characters)  
MANUAL  
AUTO  
Lower Display  
(Six Characters)  
SET UP  
FUNCTION  
DISPLAY  
MAN/AUTO  
Figure 21 HercuLine® 2000 Display and Keypad  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
31  
Set Up and Calibration Procedures  
Local Display and Keypad  
Table 6 Keypad Description  
Function  
Key or  
LED Indicator  
SET UP  
Places the actuator in the set up group select mode. Sequentially displays the set  
up groups and allows the FUNCTION key to display function parameters within the  
set up group.  
See Set Up and Calibration Procedures (page 31)Error! Reference source not  
found. for descriptions of the various options available in the set up groups.  
FUNCTION  
MAN/AUTO  
Used in conjunction with the SET UP key to select the individual functions of a  
selected configuration set up group.  
Used during field calibration procedure.  
Alternately selects:  
MAN - Actuator is in Manual mode.  
AUTO - Actuator is in Automatic mode.  
NOTE: When in Manual mode the POS display is automatically selected so you  
can use the up and down arrow keys to drive actuator motor manually.  
NOTE: This button is disabled if MAENAB is set to DIS. See Table 19 (page 53).  
DISPLAY  
Pressing this key repeatedly cycles through the operating parameters that can be  
shown on the lower display.  
INP – Input. Shows the value of the actuator input.  
OP – Output. Shows the value of the actuator output  
DE – Deviation. Shows deviation between input value and actuator position.  
POS – Position. Shows current actuator position.  
INCREMENT  
DECREMENT  
Increases the configuration values shown on the display. Also shown as  
.
In manual mode and POSition display selected, pressing this key will drive actuator  
motor in direction of increasing signal input.  
Decreases the configuration values shown on the display. Also shown as  
.
In manual mode and POSition display selected, pressing this key will drive actuator  
motor in direction of decreasing signal input.  
Indicates the movement of the actuator arm in the counterclockwise direction.  
NOTE: Actuator rotation is the direction of the output shaft when facing the end of  
the shaft and refers to the direction of rotation on increasing signal.  
Indicates the movement of the actuator arm in the clockwise direction.  
NOTE: Actuator rotation is the direction of the output shaft when facing the end of  
the shaft and refers to the direction of rotation on increasing signal.  
Indicates that the actuator has detected a motor stall condition.  
Indicates a programmed alarm condition exists.  
Indicates actuator is in manual mode  
STALLED  
ALARM  
MANUAL  
AUTO  
Indicates actuator is in automatic mode.  
32  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Set Up Tips  
Set Up Tips  
Table 7 contains tips that will help you view, verify and enter the operating parameters more quickly. If  
you cannot change the parameters, check the status of the “SET LOCK” parameter. Also some parameters  
require that you enter a security password before you access or change the parameter value.  
Table 7 Set Up Tips  
Function  
Tip  
Displaying Groups  
Use the SET UP key to display and scroll through the set up groups. The  
group titles are listed in the order that they appear on the actuator  
display.  
Displaying Functions  
Scrolling  
Use the FUNCTION key to display the individual function parameters  
under each set up group. The prompts are listed in the order of their  
appearance in each group. See Tables 8 through 19.  
Pressing and holding the SET UP key will scroll through the set up  
groups. However, when any set up group is displayed, you can scroll  
through the set up groups twice as fast using the or  
key. When in  
any set up group, hold the FUNCTION key in to scroll through the  
prompts within that group.  
Changing values quickly  
When changing the value of a parameter, you can adjust a more  
significant digit in the upper display by holding in one key  
pressing the other or at the same time.  
or  
and  
The adjustment will move one digit to the left.  
Press the key again and you will move one more digit to the left.  
Exiting Set Up mode  
To exit Set Up mode, press the DISPLAY key.  
This returns the display to the same state it was in immediately preceding  
entry into the Set Up mode.  
Timing out from  
Set Up mode  
If you are in Set Up (configuration) mode and do not press any keys for  
thirty seconds, the actuator display will time out and revert to the mode  
and display that was being used prior to entry into Set Up mode.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
33  
Set Up and Calibration Procedures  
Set Up Groups  
Set Up Groups  
Pressing the SET UP key on the keypad provides access to the various set up groups and allows you to set  
up operating parameters, (such as input types and alarms), calibrate the actuator’s inputs and outputs, set  
communications, and check actuator status. Table 8 on the next page lists the set up groups that are  
available by using the SET UP and FUNCTION keys on the keypad.  
Table 8 Set Up Groups  
Set Up Group Title  
Pressing the FUNCTION Key Allows You to…  
For Details, See  
Table 10  
SET  
INPUT  
Select and set various parameters associated with the  
input signal to the actuator.  
SET  
RELAYn  
n = 1, 2, 3, or 4  
Select relay functions. NOTE: Set Relay groups will  
show on display only if relays are installed in the  
actuator.  
Table 13  
Table 15  
Table 16  
Table 17  
Table 18  
SET  
CUROUT  
Select the output signal type of the actuator.  
SET  
COMM  
Select communication parameters for remote control of  
actuator when connected to a SCADA system.  
SET  
DIGINP  
Select the parameters for external digital input states.  
Select and set parameters for the local display.  
Calibrate input zero and span values.  
SET  
DISPLA  
CAL  
INPUT  
Calibration  
Procedure,  
Table 25  
CAL  
MOTOR  
Calibrate zero and span values for motor operation.  
Calibration  
Procedure,  
Table 26  
ATTENTION  
When calibrating the motor to a short stroke range,  
you must reset the end-of-travel limit switches. See  
Setting End-of-Travel Limit Switches.  
CAL  
CURENT  
Calibrate actuator output.  
Calibration  
Procedure,  
Table 27  
SET  
LOCK  
Set or change security password. Enable or disable  
security access to set up parameters and calibration  
set up.  
Table 19  
Table 20  
Table 21  
READ  
STATUS  
Display operating and alarm status. Display self-test  
diagnostic results.  
SET  
DRVINF  
Display and/or set various parameters specific to the  
actuator.  
34  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Set Up Groups  
SET  
MAINT  
Display various operating statistics. Reset  
accumulated operating statistics  
Table 22  
Table 23  
CAL  
Use the display as an indicator, (in this case a  
POSOUT  
voltmeter) so you can verify that the position sensor is  
operating properly.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
35  
Set Up and Calibration Procedures  
Set Up Procedure  
Set Up Procedure  
Each of the set up groups and their functions are either pre-configured at the factory or set to their default  
values. Tables 8 through 19 list and describe the options available in each set up group. The following  
procedure shows you the key press sequence to access any set up group or any associated Function  
parameter. Make sure lock set up group “LOCK” function is set to “NONE” or “CAL.” Also some  
parameters require that you enter a security password before you access or change the parameter.  
You can use this procedure to access the set up groups and select all parameters.  
Table 9 Set Up Procedure Using Display and Keypad  
Step  
1
Operation  
Press  
Result  
SET  
Enter Set Up Mode  
SET UP  
Upper Display =  
Lets you know you are in the set up mode and a set up group  
title is being displayed in the lower display.  
Lower Display =  
INPUT  
This is the first set up group you see when you press SET UP.  
2
Select any Set Up  
Group  
SET UP  
Successive presses of the SET UP key will display the other set  
up group titles as listed in Table 8Error! Reference source not  
found..  
You can also use the or  
groups in both directions.  
keys to scroll through the set up  
Stop at the set up group title that describes the group of  
parameters you want to configure. Then proceed to the next  
step.  
Upper Display  
3
Select a Function  
Parameter  
FUNCTION  
4-20  
Shows the current value or selection for the  
function prompt in the selected set up group.  
Lower Display  
IN TYP  
Shows the first function prompt within the selected  
set up group.  
Example display shows Input group function prompt “IN TYP”  
and the selection.  
4
Select other  
function parameters  
FUNCTION  
Successive presses of the FUNCTION key will sequentially  
display the other function prompts of the selected set up group.  
Stop at the function prompt that you want to change, and then  
proceed to the next step.  
36  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Set Up Procedure  
Step  
5
Operation  
Press  
Result  
Change the Value  
or Selection  
These keys increase or decrease the value, or display the next  
available selection for the selected function prompt.  
or  
See Table 7, Set Up Tips for instructions to increase or decrease  
a value quickly.  
Change the value or selection to meet your needs.  
NOTE: If the display flashes, you are trying to make an  
unacceptable entry, or the value on the display is at its range  
limit. The display may also show “KEYERR” (Key error).  
6
7
Enter Value or  
Selection  
FUNCTION  
or  
This key selects another function prompt.  
SET UP  
This key selects another set up group.  
NOTE: Pressing either key will cause the previously selected  
value or selection to be entered into memory.  
Exit Set Up mode  
DISPLAY  
Exits set up mode and returns actuator to the same state it was  
in immediately preceding entry into the set up mode. Any  
changes you have made are stored in memory.  
If you do not press any keys for 30 seconds, the display times  
out and reverts to the mode and display shown prior to entering  
the set up mode.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
37  
Set Up and Calibration Procedures  
Configuration Prompt Hierarchy  
Configuration Prompt Hierarchy  
Setup Groups  
Function Prompts  
IN TYP INP HI INP LO FILTYP Direct Dband FSTYPH  
FsVALH  
X20 VAL  
INPUT  
FSTYPL  
Y0 VAL  
FsVALL  
CHAR CUSTOM X0 VAL  
Y20 VAL  
RTYPny Rny VAL Rny E*  
Rny HL RLYnHY  
Rny HL RTYPny Rny VAL Rny E*  
RELAYn  
n = 1,2,3 or 4 y = 1 or 2  
CUROUT  
CUROUT  
COMM  
DIGINP  
DISPLA  
LOCK  
COMM  
DIGINP  
DECMAL  
LOCKID  
FAILSF  
ADDRES  
EndPos  
BAUD  
XmtDLY DBLBYT  
EUNITS  
LOCK  
UNITS  
MAENAB  
SEETST  
RAMTST  
CFGTST  
ROTATE  
CALTST  
STATUS  
VERSON  
LREP  
SPEED  
LCAL  
POWER  
REPTYP  
TAG  
MFGDAT  
DRVINF  
MAINT  
TEMP  
TEMPHI TEMPLO  
ACSTAL  
REGN0  
STARTS  
RL1CNT  
REGN9 TOTDEG  
RL2CNT  
DATSAV  
RL3CNT  
PASSWD  
RL4CNT  
MANRST  
LD CAL  
LD CFG  
RESTRT  
38  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Input Set Up Group  
Input Set Up Group  
Table 10 lists the parameters and selections available when the SET INPUT group is selected.  
On the keypad and local display:  
Press the SET UP key to enter the Input Set Up group.  
Press the FUNCTION key to scroll through the prompts listed in the set up group.  
Press the or  
keys to view selections or change range settings.  
Table 10 Input Set Up Group Parameters  
Actuator Lower  
Display  
Selections or  
Range of Setting  
Parameter Definition/PDA HercuLink Prompt  
Prompt  
INPUT ACTUATION TYPE— This selection specifies the  
signal type and range you are going to use for the actuator  
input. Be sure that the values configured for the high and low  
range, alarm setpoint, etc. are within the measuring range  
for the selected signal range.  
IN TYP  
Note: If input  
type from model  
selection guide  
is:  
0/4-20mA, 0/1-  
5Vdc, 0-10Vdc  
4 to 20 mA  
0 to 20 mA  
1 to 5 Volts dc  
0 to 5 Volts dc  
0 to 10 Volts dc  
Remote Setpoint (via communications)  
4-20  
0-20  
1-5V  
0-5V  
0-10  
R_SP  
NOTE: Changing the Input Actuation Type will restore the  
actuator calibration to its factory values.  
IN TYP  
INP HI  
INP LO  
S_90  
Series 90 – 0 to 135 ohms.  
Note: If input type from model selection guide is: Series 90  
control  
10.0 to 100  
INPUT HIGH RANGE VALUE in % is displayed.  
default = 100  
NOTE: When Input Type (R_SP or S_90) is selected, Input  
Hi is not configurable.  
0.0 to 90.0  
INPUT LOW RANGE VALUE in % is displayed.  
default = 0.0  
NOTE: When Input Type (R_SP or S_90) is selected, Input  
Hi is not configurable.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
39  
Set Up and Calibration Procedures  
Input Set Up Group  
Actuator Lower  
Display  
Selections or  
Range of Setting  
Parameter Definition/PDA HercuLink Prompt  
Prompt  
NONE  
INPUT FILTER TYPE— Allows the selection of a software  
FILTYP  
digital input filter to smooth the input signal.  
SPIK  
Spike— Selects spike filter to remove transients in the input  
signal when actuator is installed in noisy environments.  
S+LP  
Spike plus Low Pass— Selects spike and low pass filtering.  
* Allows setting of lag time constant for low pass filter.  
LPAS  
Low Pass— Selects low pass filter.  
* Allows setting of lag time constant.  
default = LPAS  
NOTE: When Input Type (R_SP or S_90) is selected, Input  
Filter Type = NONE.  
LPFILT *  
Direct  
0 to 50.00  
(in seconds)  
LAG TIME CONSTANT— (Filter Type S+LP or LPAS only)  
Allows you to set the first order lag time constant of the low  
pass filter when selected. Range is from 0 to 50 seconds.  
NOTE: When Input Type (R_SP or S_90) is selected, Low  
Pass Filter Value is not configurable.  
default = 0.5  
CCW  
CW  
ACTUATOR ROTATION—This selection determines the  
direction of rotation of the actuator shaft.  
Counterclockwise rotation  
Clockwise rotation  
NOTE: Actuator rotation is the direction of the output shaft  
when facing the end of the shaft and refers to the direction of  
rotation on increasing signal.  
default = CCW  
Dband  
0.2 to 5.0  
(in percent of  
span)  
INPUT DEADBAND— Specifies an adjustable gap that is the  
difference between the setpoint value and the value at which  
the motor energizes. Deadband is set in percent of full span.  
default = 0.5  
FAILSAFEHI TYPE—Selects the motor position you want  
the actuator to go to when input signal is above the high end  
range value.  
FSFTYPH  
NOTE: Failsafe condition occurs when the input exceeds its  
high end range value by 3%,  
LAST  
UP  
Last Position—Actuator motor remains at last position.  
Up—Actuator motor moves to full scale value.  
Down—Actuator motor moves to zero value.  
DOWN  
USER  
User selected value—Actuator motor moves to a customer-  
defined value.  
default = UP  
* Allows setting of failsafehi input value.  
0 to 100%  
FAILSAFEHI INPUT VALUE—(FailsafeHI Type USER only)  
Selects the motor position you want the actuator to go to  
when input signal is above the high end range value.  
FsFVALH *  
default = 100  
Range is from 0 to 100%.  
40  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Input Set Up Group  
Actuator Lower  
Display  
Selections or  
Range of Setting  
Parameter Definition/PDA HercuLink Prompt  
Prompt  
FAILSAFELO TYPE—Selects the motor position you want  
the actuator to go to when input signal is below the low end  
range value or on loss of input signal.  
FSFTYPL  
NOTE: Failsafe condition occurs when the input exceeds its  
low end range value by 3%, or when the input signal goes to  
zero. For input types 0 to 20mA, 0 to 5 V, and 0 to 10 V  
there is no failsafe condition at the zero value.  
LAST  
UP  
Last Position—Actuator motor remains at last position.  
Up—Actuator motor moves to full scale value.  
Down—Actuator motor moves to zero value.  
DOWN  
USER  
User selected value—Actuator motor moves to a customer-  
defined value.  
default = DOWN  
* Allows setting of failsafelo input value.  
0 to 100%  
FAILSAFELO INPUT VALUE—(FailsafeLO Type USER  
only) Selects the motor position you want the actuator to go  
to when input signal is below the low end range value or on  
loss of input.  
FsFVALL *  
CHAR  
default = 0  
Range is from 0 to 100%.  
LINR  
SQRT  
CUST  
INPUT CHARACTERIZATION— Selects a characterization  
type that causes the actuator to characterize a linear input  
signal to represent a non-linear input.  
Linear— Provides linear characterization of the input signal.  
Square Root— Provides square root characterizations of  
the input signal.  
Custom— Custom characterization. Selecting custom  
allows you to create a twentieth order characterization of  
input value (x) and associated shaft position (y).  
default = LINR  
NOTE: Selecting CUST input characterization causes the  
following prompt CUSTOM to be displayed.  
EQUL  
QUIK  
USER  
Equal percentage – Sets the characterization as explained  
in Equal Percentage Valve Characteristic on page 42.  
Values are read-only.  
CUSTOM  
Quick opening - Sets the characterization as explained in  
Quick Opening Valve Characteristic on page 43. Values are  
read-only.  
default = EQUL  
User-configurable – Lets you create your own  
characterization using the following Xn VAL and Yn VAL  
prompts.  
Xn VAL  
n = 1 - 20  
Yn VAL  
0 to 100 %  
0 to 100 %  
Input Value— as a percentage of input range. Defaults are  
in increments of 5%.  
Shaft Position Value— as a percentage of position range.  
Defaults are in increments of 5%.  
n = 1 - 20  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
41  
Set Up and Calibration Procedures  
Input Set Up Group  
Equal Percentage Valve Characteristic  
Table 11 contains values that approximate an equal percentage valve characteristic in the actuator. When  
the EQUL custom characterization type is selected, the values in Table 11 are automatically loaded into the  
actuator configuration to produce the characteristic as presented in the graph. The Xn VAL is the input  
value as a percentage of range and Yn VAL is the characterized output (actuator shaft position) as a  
percentage of range.  
Table 11 Equal Percentage Valve Characteristics  
Xn VAL Yn Val  
Order  
Equal Percentage Valve Characterization  
% of  
% of  
Range  
Range  
0
1
0
5
0
0.8  
100  
95  
90  
85  
80  
75  
70  
65  
60  
55  
50  
45  
40  
35  
30  
25  
20  
15  
10  
5
2
10  
15  
20  
25  
30  
35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
95  
100  
2.1  
3
3.2  
4
4.9  
5
6.5  
6
8.4  
7
10.7  
13.2  
15.7  
18.7  
22.6  
27.2  
33.4  
40  
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
46  
0
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
53.8  
63.2  
73.7  
86.2  
100  
Xn VAL - Actual Input  
42  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Input Set Up Group  
Quick Opening Valve Characteristic  
Table 12 contains values that approximate the characteristic of a quick opening control valve. When the  
QUIK custom characterization type is selected, the values in Table 12 are automatically loaded into the  
actuator configuration to produce the characteristic as presented in the graph. The Xn VAL is the input  
value as a percentage of range and Yn VAL is the characterized output (actuator shaft position) as a  
percentage of range.  
Table 12 Quick Opening Valve Characteristic  
Xn VAL  
Yn Val  
Order  
Quick Opening Valve Characteristic  
% of  
% of  
Range  
Range  
0
1
0
5
0
10  
2
10  
15  
20  
25  
30  
35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
95  
100  
20  
100  
95  
90  
85  
80  
75  
70  
65  
60  
55  
50  
45  
40  
35  
30  
25  
20  
15  
10  
5
3
30  
4
40  
5
50  
6
60  
7
70  
8
77  
9
82  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
86  
88  
90  
92  
94  
95  
96  
0
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
97.5  
98.5  
99.5  
100  
Xn VAL - Actual Input  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
43  
Set Up and Calibration Procedures  
Relays Set Up Group  
Relays Set Up Group  
ATTENTION  
The Relay set up group parameters are accessible only if relay PWAs are installed in the  
actuator. HercuLine® 2001 actuators can be equipped with one PWA –for a total of two SPDT  
relays. Using the Relay set up groups you can program the installed relays to operate in  
response to various operating conditions.  
Table 13 lists the parameters and selections available when the SET RELAYn group is selected.  
Table 13 Relay Set Up Group Parameters  
Actuator Lower  
Display  
Selections or  
Range of Setting  
Parameter Definition/PDA HercuLink® Prompt  
Prompt  
RTYPny  
NONE  
RELAY TYPE— Selects the relay number and the relay  
activation type. See Table 14 Relay Type Descriptions.  
n = 1, 2, 3, or 4  
y = 1 or 2  
InPR  
PosR  
Input Range— Upper / lower limits of input signal exceeded  
Position Range— Upper / lower limits of motor position  
exceeded  
DEV  
ULim  
LLim  
T Hi  
T Lo  
STRT  
Deviation— Deviation from input exceeded  
Upper Limit Travel— Same as PosR for upper limit  
Lower Limit Travel— Same as PosR for lower limit  
Temperature High— High temperature limit exceeded  
Temperature Low— Low temperature limit exceeded  
Starts— Motor starts limit exceeded. Allows setting of  
multiplier value.  
STAL  
MAN  
PWRF  
FsFA  
PosF  
Stalled— Motor position does not follow input  
Manual— Actuator is set to manual mode  
Power Up Test Failure— Failure of any power up diagnostic  
Failsafe Alarm— Failsafe condition detected  
Position Sensor Signal Failure— position output out of valid  
range  
DiGI  
Digital Input— Digital input closure  
TDEG  
Total Degrees— total degrees traveled. Allows setting of  
multiplier value.  
default = InPR and  
NONE  
RnyE*  
X1  
X10k  
MULTIPLIER— (Relay Types STRT and TDEG only)  
Selects the multiplier for the number limit of motor starts and  
total degrees traveled before the relay is activated. Multiplier  
specifies the value on display as times one (X1) or times ten  
thousand (X10k).  
default = X1  
RnyVAL  
n = 1, 2, 3, or 4  
y = 1 or 2  
0.0 to 100.0  
RELAY VALUE— Sets numerical value of limit where relay  
trips (energizes). Units are determined by the relay type  
selection. See Table 14 Relay Type Descriptions for units.  
Rny HL  
n = 1, 2, 3, or 4  
y = 1 or 2  
HI  
LO  
RELAY HIGH/LOW— Sets relay trip point to high or low  
limit.  
RLYnHY  
0.0 to 100.0  
RELAY HYSTERESIS— 0.0 to 100.0% of span or full output.  
n = 1, 2, 3, or 4  
(in percent)  
NOTE: Relay Hysteresis parameter is accessible only if  
appropriate relay type is selected.  
n is the relay number, y is the relay contact.  
44  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Relays Set Up Group  
Table 14 Relay Type Descriptions  
When this Relay Type is  
selected…  
The Relay can be set up to indicate …  
(RTYP)  
The upper / lower limits of the input signal have been exceeded.  
Relay value parameter defines range limits and units are in percent of full span.  
Input Range  
Upper / lower limits of motor position have been exceeded.  
Relay value parameter defines range limits and units are in either percent of  
span or degrees of rotation. See “Relay Examples “for setting range limits.  
Position Range  
Deviation  
Motor position has exceeded deviation limit from input. (Deviation is defined as:  
setpoint – motor position = Deviation)  
Relay value parameter defines limits and units are in percent of span.  
See “Relay Examples” for setting deviation limit.  
The motor position has exceeded the upper limit of travel.  
(Same as Position Range.)  
Relay value parameter defines limits and units are in degrees of rotation or  
percent of span. See “Relay Examples” for setting upper limit with hysteresis.  
Upper Limit Travel  
Lower Limit Travel  
Temperature High  
The motor position has exceeded the lower limit of travel.  
(Same as Position Range.)  
Relay value parameter defines limits and units are in degrees of rotation or  
percent of span.  
The high temperature limit of the actuator has been exceeded. Relay value  
parameter defines temperature limits and units are in either degrees C or  
degrees F.  
(Temperature units are defined in the UNITS setting of the DISPLA set up  
group.)  
The low temperature limit of the actuator has been exceeded. Relay value  
parameter defines temperature limits and units are in either degrees C or  
degrees F.  
Temperature Low  
(Temperature units are defined in the UNITS setting of the DISPLA set up  
group.)  
The accumulated motor starts have exceeded the limit. Relay value parameter  
defines the limit. See “Relay Examples” for setting motor starts limit. Range is  
from 10 to 99,990,000.  
Starts  
The motor is in a stall condition.  
The actuator is in manual mode.  
Stall  
Manual Mode  
Power Up Test Failure  
A failure of any one of the power up test diagnostics. See READ STATUS set up  
group.  
The actuator is in failsafe. (input signal loss or input signal out of valid range)  
The potentiometer or non-contact sensor output is out of range or has failed.  
The digital input closure.  
Failsafe  
Position Sensor Failure  
Digital Input  
The total degrees traveled.  
Total Degrees  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
45  
Set Up and Calibration Procedures  
Relays Set Up Group  
Relay connector #1  
Relay connector #2  
Relay connector #3  
Relay connector #4  
Figure 22 Relay connectors  
Relay Examples  
Relay Type - Position Range  
Selecting PosR relay type, you can cause the relay to energize when the actuator motor travels below 20%  
of range and above 80% of range. Note in the example below that Relay 1 is set up to provide two trip  
points. The first trip point (R11VAL) causes the relay to energize when the motor travels above 80%, the  
second trip point (R12VAL) is set so the relay energizes when the motor travels below 20%.  
Set Up Group  
Parameter  
RTYP11  
R11VAL  
R11HL  
Value  
PosR  
80.0  
HI  
SET RELAY1  
RTYP12  
R12VAL  
R12HL  
PosR  
20.0  
LO  
RLY1HY  
0.0  
The figure below shows the resulting action.  
Motor  
0%  
Position  
20%  
17  
100%  
80%  
17  
Open  
18  
18  
Closed  
Closed  
RELAY 1  
Normally Open  
46  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Relays Set Up Group  
Relay Type - Deviation  
Setting up a relay to alarm (energize) when the motor position deviates 10% (+ or -) from the actuator  
setpoint can be set up as follows.  
Set Up Group  
Parameter  
RTYP11  
R11VAL  
R11HL  
Value  
DEV  
10.00  
HI  
SET RELAY1  
RTYP12  
R12VAL  
R12HL  
DEV  
-10.00  
LO  
RLY1HY  
0.0  
The resulting action is shown below.  
Input  
50%  
Motor  
0%  
Position  
100%  
-10%  
+10%  
Closed  
Closed  
Open  
RELAY n  
Normally Open  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
47  
Set Up and Calibration Procedures  
Relays Set Up Group  
Relay Type – Upper Limit Travel with Hysteresis  
Selecting relay type ULim will cause the relay to energize when the motor position exceeds the upper limit  
trip point, and can be set up as follows. Note that relay hysteresis parameter (RLY1HY) value is set to 10,  
which is 10% of range. This means that when the relay is energized, due to the motor position exceeding  
the upper limit value, the relay will not de-energize until the motor moves to 10% below the trip point.  
Set Up Group  
Parameter  
RTYP21  
R21VAL  
R21HL  
Value  
ULim  
70.0  
HI  
SET RELAY2  
RTYP22  
RLY2HY  
NONE  
10.0  
Motor  
Position  
60%  
70%  
100%  
0%  
H
y
s
t
e
r
Closed  
Open  
e
s
I
RELAY n  
Normally Open  
s
Motor  
Position  
60%  
70%  
100%  
0%  
H
y
s
t
e
r
Open  
Closed  
e
s
I
RELAY n  
Normally Open  
s
Relay Type – Motor Starts  
Selecting relay type STRT will cause the relay to trip when the number of motor starts exceeds the selected  
limit. The motor starts value is stored as one of the maintenance group statistics. This example sets the  
motor starts limit at 200,000 for Relay 1.  
Set Up Group  
Parameter  
RTYP11  
R11 E*  
Value  
STRT  
X10K  
20  
SET RELAY1  
R11VAL  
R11HL  
HI  
RTYP12  
NONE  
The resulting action is that Relay 1 will trip when the number of accumulated motor starts in the  
maintenance group exceeds 200,000.  
48  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Current Out Set Up Group  
Current Out Set Up Group  
Table 15 lists the parameters and selections available for the SET CUROUT group.  
Table 15 Current Out Set Up Group Parameters  
Actuator Lower  
Display  
Selections or  
Range of Setting  
Parameter Definition/PDA HercuLink Prompt  
Prompt  
CUROUT  
OUTPUT SIGNAL RANGE— Selects the signal output  
range.  
Note: If output  
type from model  
selection guide  
is:  
0/4-20mA, 0/1-  
5Vdc  
4 – 20  
0 – 20  
1 – 5V  
0 – 5V  
4 to 20 mA  
0 to 20 mA  
1 to 5 Volts (250 ohm resistor required)  
0 to 5 Volts (250 ohm resistor required)  
CUROUT  
SW E  
Slidewire Emulation  
Note: If output  
type from model  
selection guide  
is:  
Slidewire  
Emulation  
CUROUT  
NONE  
No current output configured.  
Note: If output  
type from model  
selection guide  
is:  
None  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
49  
Set Up and Calibration Procedures  
Communications Set Up Group  
Communications Set Up Group  
Table 16 lists the parameters and selections available for the SET COMM group.  
Table 16 Communications Set Up Group Parameters  
Actuator Lower  
Display  
Selections or  
Range of Setting  
Parameter Definition/PDA HercuLink Prompt  
Prompt  
COMM  
COMMUNICATONS PARAMETERS— Disables or enables  
parameter displays for Modbus communciations set up.  
DIS  
Disabled— Locks out access to communications displays  
and parameters.  
MODB  
Modbus— Allows access to the communication displays  
and settings for the parameters listed below.  
HART  
1 to 99  
HART – selects HART as the communications protocol  
ADDRES  
BAUD  
DEVICE ADDRESS— Selects device address when used in  
a Modbus communications loop. Select an address that is  
unique to other devices on the communications link.  
default = 1  
2400  
4800  
9600  
19.2k  
BAUD RATE— Selects the speed of data transfer. All  
equipment on the link must be set to match the host setting.  
default = 19.2k  
XmtDLY  
NONE  
10ms  
20ms  
30ms  
40ms  
50ms  
RESPONSE DELAY— Selects the time delay (in  
milliseconds) before a response to a query is transmitted.  
default = 20ms  
DBLBYT  
FLOATING POINT DATA FORMAT— Selects the format for  
transferring floating point data.  
Byte Order  
FP B  
FPBB  
Floating Point Big Endian format—  
Floating Point Big Endian format  
with byte-swapped—  
Floating Point Little Endian format—  
Floating Point Little Endian format  
with byte-swapped—  
0 1 2 3  
1 0 3 2  
3 2 1 0  
FP L  
FPLB  
2 3 0 1  
default = FP B  
50  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Digital Input Set Up Group  
Digital Input Set Up Group  
Table 17 lists the parameters and selections availible for the SET DIGINP group.  
Table 17 Digital Input Set Up Group Parameters  
Actuator Lower  
Display  
Selections or  
Range of Setting  
Parameter Definition/PDA HercuLink® Prompt  
Prompt  
DIGINP  
Digital Input State— Selects the position of the actuator in  
response to a digital input signal (contact closure).  
NONE  
UP  
None— No action by the actuator.  
Up— Actuator motor moves to full scale value.  
Down— Actuator motor moves to zero value.  
DOWN  
USER  
User selected value— Actuator motor moves to a  
customer-selected value.  
* Allows setting of End Position Value.  
default = UP  
EndPos  
0 – 100  
(in percent)  
END POSITION VALUE— (DIGINP USER only) Selects the  
motor position you want the actuator to go to when digital  
input signal present (contact closure).  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
51  
Set Up and Calibration Procedures  
Display Set Up Group  
Display Set Up Group  
Table 18 lists the parameters and selections availible for the SET DISPLAY group.  
Table 18 Display Set Up Group Parameters  
Actuator Lower  
Display  
Selections or  
Range of Setting  
Parameter Definition/PDA HercuLink® Prompt  
Prompt  
DECMAL  
DECIMAL POINT LOCATION— This selection determines  
where the decimal point appears in the display.  
8888  
None  
888.8  
One Place  
Note: Be sure the selection agrees with the value to be  
displayed. If display value requires 4 whole digits, the  
decimal will not show.  
default = 8888  
EUNITS  
UNITS DISPLAY— Selects the units of the position display.  
PCNT  
Percent— Shows actuator position as a percentage of span.  
(0 to 100%)  
DEG  
Degrees— Shows the actuator position in degrees of  
rotation. (0 to 150°) (90°)  
default = PCNT  
UNITS  
DISPLAY UNITS— Selects standard for unit values for the  
local display.  
SI  
SI— Display will show unit values in international (metric)  
units. (Temperature in degrees C, Date format: ddmmyy)  
ENGL  
English— Display will show unit values in U.S. units.  
(Temperature in degrees F, Date format: mmddyy)  
default = ENGL  
52  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Lock Set Up Group  
Lock Set Up Group  
Table 19 lists the parameters and selections available for the SET LOCK group.  
Table 19 Lock Set Up Group Parameters  
Actuator Lower  
Display  
Selections or  
Range of Setting  
Parameter Definition/PDA HercuLink® Prompt  
Prompt  
LOCKID  
0 to 4095  
PASSWORD LOCK— 4-digit password can be selected to  
provide security access to calibration information, set up  
parameters and supervisory functions. Password can be a  
number from 0 to 4095.  
default = 0  
LOCK OUT FEATURE— Selects lockout security for  
LOCK  
calibration and supervisory functions, and set up groups.  
NONE  
CAL  
None— No lockout of any calibration or set up groups. You  
select and change set up group values, and perform field  
calibration.  
Calibration— Lockout for calibration groups SET CALINP,  
SET CALMTR, SET CALOUT and CAL POSOUT only. You  
can select and change set up group values.  
CONF  
Configuration— Lockout for calibration groups and set up  
group configuration. You can only scroll through and view  
set up group values.  
FULL  
Full— Lockout for calibration and all set up group values.  
Only SET LOCK and READ STATUS groups are accessible.  
default = NONE  
MAENAB  
Manual / Auto— Allows the ability to lockout mode changes  
from the front panel.  
DIS  
ENAB  
Disabled— Disables the front panel auto / manual switch  
functionality.  
Enabled— Enables the front panel auto / manual switch  
functionality.  
default = ENAB  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
53  
Set Up and Calibration Procedures  
Lock Set Up Group  
Set/Change Password  
A password is required to disable the ability to readily change features of the actuator. Lock out of  
calibration capability and other supervisory functions can be controlled by using a password. The  
password can be any number from 0 to 4095. The password is set and/or changed by using the keys on the  
kepad and the local display. Follow the steps below to change the password.  
NOTE: The LOCK parameter must be set to NONE in order to change the password.  
Step  
1
Action  
Press SET UP key until the display reads SET LOCK.  
Press the FUNCTION key until the lower display reads LOCK.  
2
If the prompt in the upper display is flashing, a password is required to change the LOCK type,  
proceed to step 3.  
If the upper display is not flashing and you want to change the LOCK type, proceed to step 5.  
If the upper display is not flashing and you want to change the password proceed to step 3.  
Press the FUNCTION key until the lower display reads LOCKID.  
3
4
The upper display will show 0 (zero). Use the  
or  
keys to increment the number to the  
correct password. See NOTE below on use of keys.  
Note: If the password can not be recovered to allow user access, a universal password can be  
obtained by calling the Honeywell Tactical Assistance center.  
5
6
Press the FUNCTION key, the lower display should read LOCK. The upper display should not  
be flashing. If it is repeat steps 3 & 4.  
Use the  
or  
keys to change the LOCK type to the desired selection.  
If your not changing the password proceed to step 9.  
If your changing the password set the LOCK type to NONE and proceed to step 7.  
Press the FUNCTION key until the lower display reads LOCKID.  
7
8
The upper display will show 0 (zero). Use the or  
new password. See NOTE below on use of keys.  
keys to increment the number to the  
9
Press FUNCTION key to view next parameter. Press DISPLAY to exit set up mode.  
(LOCK type has now been changed or Password is now set to new value).  
NOTE: When changing the value of the number, you can adjust a more significant digit in the upper  
display by holding in one key or and pressing the other or at the same time.  
The adjustment will move one digit to the left.  
Press the key again and you will move one more digit to the left.  
54  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Read Status Set Up Group  
Read Status Set Up Group  
Table 20 lists the parameters and selections available for the READ STATUS group.  
Table 20 Read Status Set Up Group Parameters  
Actuator Lower  
Display  
Selections or  
Range of Setting  
Parameter Definition/PDA HercuLink® Prompt  
Prompt  
FAILSF  
RAMTST  
SEETST  
FAILSAFERead Only. Shows whether actuator in  
failsafe.  
NO  
No— Actuator not in failsafe.  
Yes— Actuator in failsafe, see  
Troubleshooting (page 105)  
YES  
RAM TEST DIAGNOSTICRead Only. Shows status of  
RAM test diagnostic.  
PASS  
FAIL  
Pass— Test passed, no errors  
Fail— Test failed, see see  
Troubleshooting (page 105)  
SERIAL EEPROM TEST DIAGNOSTICRead Only.  
Shows status of serial electrically eraseable PROM test  
diagnostic.  
PASS  
FAIL  
Pass— Test passed, no errors  
Fail— Test failed, see  
Troubleshooting (page 105)  
CFGTST  
CALTST  
CONFIGURATION TEST DIAGNOSTICRead Only.  
Shows status of Configuration test diagnostic.  
PASS  
FAIL  
Pass— Test passed, no errors  
Fail— Test failed, see  
Troubleshooting (page 105)  
CALIBRATION TEST DIAGNOSTICRead Only. Shows  
status of Calibration test diagnostic.  
PASS  
FAIL  
Pass— Test passed, no errors  
Fail— Test failed, see  
Troubleshooting (page 105)  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
55  
Set Up and Calibration Procedures  
Drive Set Up Group  
Drive Set Up Group  
Table 21 lists the parameters and selections available for the SET DRVINF group.  
Table 21 Drive Set Up Group Parameters  
Actuator Lower  
Display  
Selections or  
Range of Setting  
Parameter Definition/PDA HercuLink® Prompt  
Prompt  
VERSON  
nnnn  
FIRMWARE VERSIONRead Only. Displays the firmware  
version currently in use by the actuator’s CPU.  
SPEED  
6 S  
12 S  
25 S  
50 S  
75 S  
STROKE SPEEDRead Only. The speed is the number of  
seconds it takes for the actuator shaft to move its full range  
of travel.  
(150° @ 60hz)  
SPEED  
3.2 S  
7.2 S  
15 S  
30 S  
45 S  
STROKE SPEEDRead Only. The speed is the number of  
seconds it takes for the actuator shaft to move its full range  
of travel.  
(90° @ 60hz)  
SPEED  
7.5 S  
15 S  
30 S  
60 S  
90 S  
STROKE SPEEDRead Only. The speed is the number of  
seconds it takes for the actuator shaft to move its full range  
of travel.  
(150° @ 50hz)  
SPEED  
4.5 S  
9 S  
18 S  
36 S  
54 S  
STROKE SPEEDRead Only. The speed is the number of  
seconds it takes for the actuator shaft to move its full range  
of travel.  
(90° @ 50hz)  
POWER  
POWER INPUT VOLTAGE AND FREQUENCYRead  
Only. Selects the power input voltage and line frequency of  
the actuator.  
1206  
1205  
2206  
2205  
1206— 120Volts, 60Hz  
1205— 120Volts, 50Hz  
2206— 220Volts, 60Hz  
2205— 220Volts, 50Hz  
ROTATE  
ROTATION— Indicates the factory calibrated degrees of  
rotation.  
90  
150  
90— Factory calibrated for 90 degrees of rotation.  
150— Factory calibrated for 150 degrees of rotation.  
TAG  
nnnnnn  
TAG NAME— Selects the tag name or identifier of the  
actuator. Up to 6 alphanumeric characters. See “Set Tag  
Name” on next page.  
DMFG  
mmddyy *  
or  
MANUFACTURING DATERead Only. Displays date  
code of manufacture for actuator.  
ddmmyy  
56  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Drive Set Up Group  
Actuator Lower  
Display  
Selections or  
Range of Setting  
Parameter Definition/PDA HercuLink® Prompt  
Prompt  
LREP  
mmddyy *  
or  
DATE OF LAST REPAIRFactory set only. Displays date  
of last repair.  
ddmmyy  
LCAL  
mmddyy *  
or  
DATE OF LAST FACTORY CALIBRATIONFactory set  
only. Displays date of last factory calibration  
ddmmyy  
REPTYP  
REPAIR TYPEFactory set only. Displays a repair code to  
identify the type of repair service previously performed.  
NONE  
01  
None  
Future  
02  
03  
04  
Non-contact Sensor  
Main CPU PWA repair  
Motor service  
05  
06  
Power Distribution PWA service  
Switch repair  
07  
Relay service  
08  
Gear service  
09  
10  
11  
12  
Service to repair water damage  
Service to repair damage caused by heat  
Service to repair due to over-voltage damage  
Actuator reconfigured  
Warranty Repair  
13  
* NOTE: Date format is set by the UNITS parameter. See SET DISPLA set up group.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
57  
Set Up and Calibration Procedures  
Drive Set Up Group  
Set Tag Name  
The actuator tag name can be an alphanumeric name up to six characters. The tag name is set by using the  
keys on the keypad and the local display. Follow the steps below to set the tag name.  
Step  
Action  
1
2
3
Press SET UP key until the display reads SET DRVINF.  
Press the FUNCTION key until the upper display reads TAG.  
The lower display contains six digits. A decimal point will be flashing at the leftmost digit for  
approximately three seconds. Then the decimal point shifts to the right and flashes for three  
seconds before shifting again to the right. This pattern repeats continuously.  
4
5
Set the digit to the left of the flashing decimal point. Use the  
the character set of 0 through 9, the letters ‘a’ through ‘z’ and the letters ‘A’ through ‘Z’ . Scroll  
through until the desired character is displayed.  
or  
keys to scroll through  
Wait for the decimal point to shift to the right and then scroll through using the  
until the next character is displayed.  
or  
keys  
6
7
Repeat for each character of the tag until the complete tag name is displayed.  
Press the FUNCTION key to go to the next parameter, or press DISPLAY to exit set up mode.  
58  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Maintenance Set Up Group  
Maintenance Set Up Group  
The Maintenance set up group consists of information about actuator operation accumulated through time.  
This information (or maintenance statistics) can be used to evaluate actuator operation and determine  
predicted or scheduled maintenance periods. Table 22 lists the parameters and selections available for the  
SET MAINTENANCE group.  
Please note that maintenance statistics are written to the EEPROM every 8 hours. Therefore the statistics  
are saved in the event of a power interruption.  
Table 22 Maintenance Set Up Group Parameters  
Actuator Lower  
Display  
Selections or  
Range of Setting  
Parameter Definition/PDA HercuLink® Prompt  
PDA users: The prompts are organized differently on your PDA’s HercuLink®  
software. Grayed prompts are under Configuration, Maintenance. Non-grayed  
prompts are under Maintenance.  
Prompt  
TEMP  
nnnn F *  
nnnn F *  
ACTUATOR TEMPERATURERead Only. Displays the  
current internal temperature of the actuator.  
TEMPHI  
HIGH TEMPERATURE LIMIT— Displays the high  
temperature limit of the internal actuator temperature since it  
was last reset.  
TEMPLO  
nnnn F *  
LOW TEMPERATURE LIMIT— Displays the low  
temperature limit of the internal actuator temperature since it  
was last reset.  
ACCUMULATED STALL TIME— Displays the accumulated  
stall time of the actuator motor since it was last reset.  
hh:mm:ss †  
ACST †  
STARTS  
nnnn  
ACCUMULATED MOTOR STARTS— Displays the  
accumulated motor starts since it was last reset. Multiply  
displayed value times 105 to get actual value. Range is 0 to  
999,900,000.  
RLnCNT  
nnnn  
nnnn  
RELAY CYCLE COUNTS— Displays the accumulated cycle  
counts of a relay since it was last reset. One relay cycle is  
when a relay is energized and deenergized. Multiply  
displayed value times 105 to get actual value. Range is 0 to  
999,900,000.  
n = 1, 2, 3 or 4  
REGNn  
ACCUMULATED MOTOR STARTS— Displays the  
accumulated motor starts in the 1st 10% of motor span since  
it was last reset. See  
n = 0 to 9  
Regions of Motor Travel (page 62). Multiply displayed value  
times 105 to get actual value. Range is 0 to 999,900,000.  
TOTDEG  
nnnn  
TOTAL DEGREES OF MOTOR TRAVEL— Displays the  
total number of degrees of motor travel since it was last  
reset. Multiply displayed value times 105 to get actual value.  
Range is 0 to 999,900,000.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
59  
Set Up and Calibration Procedures  
Maintenance Set Up Group  
Actuator Lower  
Display  
Selections or  
Range of Setting  
Parameter Definition/PDA HercuLink® Prompt  
PDA users: The prompts are organized differently on your PDA’s HercuLink®  
software. Grayed prompts are under Configuration, Maintenance. Non-grayed  
prompts are under Maintenance.  
Prompt  
DATSAV  
MAINTENANCE DATA FORCED SAVE— Allows you to  
manually force a save of the current maintenance data  
values.  
DIS  
ENAB  
DISABLE— Forced data save is disabled.  
ENABLE— Forced data save is enabled.  
PASSWRD  
MANRST  
nnnn  
PASSWORD— If a password has been activated, then a 4-  
digit password is required to enable any of the functions  
below.  
NOTE: Password is set (or changed) from the Lock set up  
group.  
MAINTENANCE STATISTIC RESET— Allows reset of the  
following maintenance statistics:  
NONE  
STAL  
STRT  
None— No reset of maintenance statisitics  
Stall— Resets accumulated stall time to zero.  
Motor Starts— Resets the accumulated motor start counter  
to zero.  
REGNn  
Motor Starts in the Region— Resets the selected motor  
n = 0 to 9  
span region counter to zero.  
TEMP  
TDEG  
Temperature Statistics— Resets the high / low  
temperature limit statistics.  
Total Degrees— Resets the total degrees of motor travel to  
zero.  
RELn  
Relay Counts— Resets the selected accumulated relay  
n = 1, 2, 3 or 4  
cycle counter to zero.  
ALL  
SYST  
All— Resets all maintenance statistics to zero.  
SYST— Enables the system restart function.  
default = NONE  
60  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Actuator Lower  
Display  
Selections or  
Range of Setting  
Parameter Definition/PDA HercuLink® Prompt  
PDA users: The prompts are organized differently on your PDA’s HercuLink®  
software. Grayed prompts are under Configuration, Maintenance. Non-grayed  
prompts are under Maintenance.  
Prompt  
LD CAL  
NONE  
INP  
RESTORE CALIBRATION TYPE— Allows you to restore a  
calbration value to its factory calibration.  
Input — Restores input calibration to the factory calibration  
for the current configured input type.  
MTR  
COUT  
ALL  
Motor— Restores motor calibration to the factory calibration.  
Output — Restores actuator output calibration to the factory  
calibration for the current configured output type.  
POS  
All — Restores input (for the type configured), motor and  
output (for the type configured) calibration to the factory  
calibration.  
POS — Allows a position sensor field calibration to be stored  
as a factory calibration. This is to be used when a sensor is  
replaced in the field. See “Calibrate POS Output”.  
default = NONE  
DIS  
LD CFG  
RESTRT  
RESTORE DEFAULT FACTORY CONFIGURATION—  
Allows you to restore the factory default configuration.  
ENAB  
DIS — Restore disabled.  
ENAB— Restore enabled.  
default = DIS  
DIS  
SYSTEM RESTART— Allows you to force the system to  
restart.  
ENAB  
DIS — Restart disabled.  
ENAB— Restart enabled.  
default = DIS  
Note: The MANRST function must be set to SYST.  
* Temperature units are displayed in degrees C or F, and are set by the UNITS parameter. See SET  
DISPLA set up group.  
Note that the upper display contains the parameter name and the lower display contains the value.  
This is to allow for the display of hours: minutes: seconds.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
61  
Set Up and Calibration Procedures  
Regions of Motor Travel  
Regions of Motor Travel  
The full span of motor travel can be 90° or 150° rotation. The span is divided into 10 regions of motor  
travel as shown in Figure 23 (regions are numbered 0 through 9). Maintenance statistics are accumulated  
on the total number of motor starts, as well as the total number of motor starts that occur in each region of  
travel. The statistics can be accessed in the maintenance set up group. The counts can also be reset to zero  
if desired. See the Maintenance Set Up Group for more information. The regions of travel are determined  
by the full span motor travel (90° or 150° rotation). If the actuator is set up to operate in a smaller range,  
for example between 40% and 80% of full span, the maintenance statistics will show motor starts only in  
regions 4 through 7.  
Percent of Span  
0%  
20%  
40%  
60%  
80%  
100%  
Region of Travel  
0
1
2
3
4
5
6
7
8
9
o
o
30  
o
o
0
60  
90  
Degrees of Rotation  
Pe rc en t of S pa n  
0%  
20%  
4 0%  
60%  
8 0%  
100%  
Regio n of Trave l  
0
1
2
3
4
5
6
7
8
9
o
o
o
o
0
30  
60  
150  
De gr ee s of R ot at io n  
Figure 23 Regions of Motor Travel  
62  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
CAL POSOUT Group  
CAL POSOUT Group  
The CAL POSOUT group is used to verify that the position sensor is operating and adjusted properly. This  
group allows the local display to indicate the output voltage of the position sensor. This display is used  
when verifying the POS sensor is operating and that it is properly calibrated. Table 23 shows the selections  
available for the CAL POSOUT group.  
Table 23 CAL POSOUT Group Parameters  
Actuator Lower  
Display  
Selections or  
Range of Setting  
Parameter Definition/PDA HercuLink Prompt  
Prompt  
CALPOS  
n.nnn  
POSITION SENSOR OUTPUTRead Only. Displays the  
output voltage of the position sensor  
To access the display…  
Press  
Result  
SETUP  
until you see  
Upper Display =  
Lower Display =  
CAL  
POSOUT  
FUNCTION  
Upper Display =  
Lower Display =  
DIS  
CALPOS  
Upper Display =  
Lower Display =  
BEGN  
CALPOS  
or  
key  
FUNCTION  
Upper Display =  
Lower Display =  
n.nnn (sensor output in volts)  
POSOUT  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
63  
Set Up and Calibration Procedures  
Auto - Manual Drive Switch  
Auto - Manual Drive Switch  
The Auto - Manual switch is located on the side of the actuator case below the handwheel. The switch  
allows manual mode control of the actuator motor for set up, calibration and troubleshooting.  
Figure 24 shows an illustration of the Auto - Manual switch and Table 24 describes the switch settings.  
The Auto - Manual Drive switch setting overrides all input signals (analog signal and remote setpoint) and  
local display mode settings. When not in auto the manual LED will flash every second.  
MANUAL  
OFF  
CCW  
CW  
OFF  
A
U
T
O
AUTO - MANUAL DRIVE  
Figure 24 Auto - Manual Switch  
Table 24 Auto - Manual Switch Functions  
Switch Setting  
AUTO  
Motor Drive Control  
Actuator moves according to signal input and set up configuration.  
Actuator moves to the fully counterclockwise position.  
Actuator moves to the fully clockwise position.  
Actuator is idle.  
CCW  
CW  
OFF  
64  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Calibration  
Calibration  
Calibration of the HercuLine® 2000 Series Actuator may consist of calibrating the motor circuit that  
positions the actuator with 0/4-20mA input signal, calibrating the potentiometer or non-contact sensor, and  
calibrating the slidewire emulation output or the 0/4-20mA output signal. Typically, only a motor  
calibration is required for installation.  
Calibration is performed by connecting test equipment to the input terminals or output terminals and then  
using the keypad and display to step through the calibration group functions.  
ATTENTION  
Input calibration and output calibrations are performed at the factory and may not be  
necessary. Normally, you may only need to perform Calibrate Motor.  
Only qualified personnel should perform calibration.  
High voltages exist inside the actuator case. Do not touch the powered wires inside.  
Death or serious injury can occur.  
Equipment Needed  
The table below lists the equipment you will need to calibrate the HercuLine® 2000 input and output  
circuits.  
Procedure  
Input Calibration  
Equipment Needed  
A calibrated signal source which can provide current (4 to 20  
mA) or voltage (0 to 10 V) with an accuracy of 0.02% or better.  
Two insulated copper leads for connecting the current source  
to the actuator.  
Output Calibration  
A digital voltmeter with an accuracy of 0.01% or better.  
A 250 ohm resistor 0.01% tolerance.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
65  
Set Up and Calibration Procedures  
Calibration  
Calibration Set up  
Follow the steps below to set up the test equipment and actuator to verify calibration or perform calibration  
procedures.  
Step  
1
Action  
Determine input type (current or voltage).  
2
Set jumper W2 on main CPU board according to type of signal source. See Figure 27 on page  
68 for jumper location.  
3
Connect the copper leads from the signal source to the input terminals of the actuator as  
shown in Figure 25.  
4
5
Place signal source output at zero and switch power on.  
Connect a 250 ohm resistor across the Output terminals of the actuator and connect the DVM  
leads to the terminals.  
Actuator  
Calibrated  
Signal  
Terminal Block  
Source  
+
-
Input  
Output  
5
4
2 1  
Digital  
Voltmeter  
-
+
-
+
+
-
250 ohm  
resistor  
(supplied)  
Internal 250 ohm resistor  
settable through  
Jumper W2  
Current  
Voltage  
Figure 25 Calibration Wiring Connections (non-slidewire emulation)  
66  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Calibration  
Actuator  
Digital  
Voltmeter  
+
-
Calibrated  
Signal  
Terminal Block  
Source  
+
-
Input  
Output  
5
4
2 1  
3
-
+
-
+
FB  
Power  
Supply  
1-18 VDC  
+
-
Internal 250 ohm resistor  
settable through  
Jumper W2  
Current  
Voltage  
Figure 26 Calibration Wiring Connections (slidewire emulation)  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
67  
Set Up and Calibration Procedures  
Calibration  
Jumper W2  
Figure 27 Jumper Location on CPU PWA  
Calibrate Input  
The HercuLine® 2001/2002 actuator accepts a variety of signal inputs.  
1. 0 to 20 mA, or 4 to 20 mA  
2. 0 to 5 Volts,1 to 5 Volts, or 0 to 10 Volts  
The input type is selected through the Input set up group using the local keypad.  
Refer to Figure 25 for the wiring connections and follow the procedure in Table 25 to calibrate the input  
circuit of the HercuLine® 2001/2002 actuator.  
ATTENTION  
For an input calibration to be saved, you must complete the procedure. The calibration will not  
be saved if you exit without completing the steps of the procedure.  
To exit calibation mode, press DISPLAY or SETUP keys.  
68  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Calibration  
Table 25 Input Calibration Procedure  
Step  
1
Operation  
Press  
Result  
CAL  
Enter Calibration  
Mode  
SETUP  
until you see  
Upper Display =  
Lower Display =  
INPUT  
FUNCTION  
Upper Display =  
Lower Display =  
DIS  
CAL IN  
Upper Display =  
Lower Display =  
BEGN  
CAL IN  
or  
key  
2
3
4
Calibrate Zero (0%)  
FUNCTION  
FUNCTION  
FUNCTION  
Upper Display =  
Lower Display =  
APLY  
INZERO  
Adjust the signal source to an output value equal to 0% range  
value.  
Wait 5 seconds, then go to step 3.  
Calibrate Span  
(100%)  
Upper Display =  
Lower Display =  
APLY  
INSPAN  
Adjust the signal source to an output value equal to 100%  
range value.  
Wait 5 seconds, then go to step 4.  
Calibration for zero and span input values are now saved. Input  
calibration is complete.  
NOTE: The display will automatically go to the CAL MOTOR set  
up display. See Table 26. You may also exit calibation mode by  
pressing the DISPLAY or SETUP keys.  
ATTENTION:  
When calibrating the motor to a short stroke range, you must  
reset the end-of-travel limit switches. See Setting End-of-Travel  
Limit Switches.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
69  
Set Up and Calibration Procedures  
Calibration  
Calibrate Motor  
Use the procedure in Table 26 to calibrate the actuator motor for 0% and 100% input signal  
ATTENTION  
For a motor calibration to be saved, you must complete the procedure. The calibration will not  
be saved if you exit without completing the steps of the procedure.  
ATTENTION  
When calibrating the motor to a short stroke range, you must reset the end-of-travel limit  
switches. See Setting End-of-Travel Limit Switches.  
Table 26 Motor Calibration Procedure  
Step  
1
Operation  
Press  
Result  
CAL  
Enter Calibration  
Mode  
SETUP  
until you see  
Upper Display =  
Lower Display =  
MOTOR  
FUNCTION  
Upper Display =  
Lower Display =  
DIS  
CALMTR  
Upper Display =  
Lower Display =  
BEGN  
CALMTR  
or  
key  
2
3
4
Calibrate Zero (0%)  
FUNCTION  
FUNCTION  
FUNCTION  
Upper Display =  
Lower Display =  
APLY  
MTR LO  
Use the Handwheeel or AUTO/MANUAL switch to manually  
drive the actuator motor to its low position.  
Wait 5 seconds, then go to step 3.  
Calibrate Span  
(100%)  
Upper Display =  
Lower Display =  
APLY  
MTR HI  
Use the Handwheeel or AUTO/MANUAL switch to manually  
drive the actuator motor to its high position.  
Wait 5 seconds, then go to step 4.  
Calibration for zero and span motor positions are now saved.  
Motor calibration is complete.  
NOTE: The display will automatically go to the CAL CURENT  
set up display. See Table 27. You may also exit calibation  
mode by pressing the DISPLAY or SETUP keys.  
70  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Calibration  
Calibrate Output  
HercuLine® 2001/2002 actuator can be one of three output types:  
1. 0 to 20 mA, or 4 to 20 mA output  
2. 0 to 5 Volts, or 1 to 5 Volts with 250 ohm range resistor  
3. Slidewire emulation.  
The output signal range is selected through the Current Out set up group using the keypad and local  
display.  
0/4-20 mA Output  
The HercuLine® 2001/2002 Actuator comes already calibrated from the factory. If it becomes necessary to  
do a calibration in the field, adjust the output using the procedure in Table 27. Refer to Figure 25 for a  
diagram to connect a signal source to the actuator input and a DVM to measure actuator output signal.  
This procedure provides the steps to calibrate the actuator for a 4 to 20mA output. If you are using another  
output type, change the procedure accordingly.  
ATTENTION  
For an output calibration to be saved, you must complete the procedure. The calibration will  
not be saved if you exit without completing the steps of the procedure.  
To exit calibation mode, press DISPLAY or SETUP keys.  
Table 27 Output Calibration Procedure  
Step  
1
Operation  
Press  
Result  
CAL  
Enter Calibration  
Mode  
SETUP  
until you see  
Upper Display =  
Lower Display =  
CUR OUT  
FUNCTION  
Upper Display =  
Lower Display =  
DIS  
CALOUT  
Upper Display =  
Lower Display =  
BEGN  
CALOUT  
or  
key  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
71  
Set Up and Calibration Procedures  
Calibration  
Step  
2
Operation  
Press  
Result  
xxx  
Calibrate Zero (0%)  
FUNCTION  
Upper Display =  
Lower Display =  
ZERO  
Read meter connected to actuator output.  
Adjust actuator output to a value equal to 0% output as read  
or  
key  
from the DVM.  
NOTE: Typically for a 4 mA output, the display will show a value  
of approximately 382. A lower limit value is imposed on the zero  
output. If the value is 357 or lower, the actuator will not allow you  
to calibrate the zero output. The value must be larger than 357  
for a valid calibration.  
3
Calibrate Span  
(100%)  
FUNCTION  
Upper Display =  
Lower Display =  
xxxx  
SPAN  
Read meter connected to actuator output.  
Adjust actuator output to a value equal to 100% output as read  
or  
key  
from the DVM.  
NOTE: Typically for a 20 mA output, the display will show a  
value of approximately 1887.  
4
FUNCTION  
Calibration for zero and span output values are now stored.  
Output calibration is complete.  
Slidewire Emulation  
The HercuLine® 2001/2002 Actuator comes already calibrated from the factory. If it becomes necessary to  
do a calibrationin the field, adjust the output using the procedure in Table 28. Refer to Figure 26 for a  
diagram to connect a signal source to the actuator input and a DVM to measure actuator output signal.  
ATTENTION  
For a slidewire emulation output calibration to be saved, you must complete the procedure.  
The calibration will not be saved if you exit without completing the steps of the procedure.  
To exit calibration mode, press DISPLAY or SETUP keys.  
72  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Calibration  
Table 28 Slidewire Emulation Calibration Procedure  
Step  
1
Operation  
Press  
Result  
CAL  
Enter Calibration  
Mode  
SETUP  
until you see  
Upper Display =  
Lower Display =  
OUTPUT  
FUNCTION  
Upper Display =  
Lower Display =  
DIS  
CALOUT  
Upper Display =  
Lower Display =  
BEGN  
CALOUT  
or  
key  
2
3
Calibrate Zero (0%)  
FUNCTION  
Upper Display =  
Lower Display =  
xxx  
ZERO  
xxx = arbitrary number assigned by software  
Adjust actuator output voltage using down key until value on  
DVM ceases to change, then press up key until value on DVM  
moves up one digit  
or  
key  
Calibrate Span  
(100%)  
FUNCTION  
Upper Display =  
Lower Display =  
xxxx  
SPAN  
xxx = arbitrary number assigned by software  
or  
key  
Adjust actuator output voltage using  
key until value on DVM  
ceases to change, then press  
moves down one digit  
down key until value on DVM  
FUNCTION  
Calibration for zero and span output values are now stored.  
Slidewire Emulation Output Calibration is complete. Read meter  
connected to actuator output.  
Calibrate Position Sensor  
ATTENTION  
The Position Sensor is factory calibrated. Under normal operation it does not require  
calibration.  
Sensor calibration may be necessary due to any of the following conditions:  
The sensor output is incorrect,  
The position sensor in the actuator has been replaced,  
The position sensor adjustment has been disturbed.  
When the position sensor has been replaced (or serviced), you should perform a calibration of the position  
sensor circuit and then store it as the motor factory calibration. Please note that performing this procedure  
will destroy any previously stored motor factory calibration values. Table 29 outlines the steps to perform a  
calibration to the position sensor circuit.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
73  
Set Up and Calibration Procedures  
Calibration  
While the unit is powered, a potentially lethal shock hazard exists inside the case.  
Table 29 NCS Position Sensor Calibration Procedure  
Action  
Step  
1
Remove AC power to the actuator.  
2
Remove the six screws and the top cover from the actuator case. See Figure 2.  
Lay extended cover assembly on a flat surface. Remove relay cards if present.  
3
4
Reapply AC power to the actuator.  
Press SET UP key to access the INPUT set up group.  
Press FUNCTION key until the lower display reads Direct.  
Press the  
or  
keys to set Actuator Rotation direction to CCW.  
NOTE: Actuator direction must be set to CCW for this procedure. Direction can be changed  
after calibration is complete.  
5
6
Drive the actuator to the 50% position (this refers to the position on the actuator scale for CCW  
rotation). This should be done manually with the handwheel or with the AUTO - MANUAL  
switch.  
Press SET UP key until the display reads CAL POSOUT.  
Press the FUNCTION key until the dispaly reads DIS CALPOS.  
Press the  
or  
keys until the lower display reads BEGN CALPOS.  
Press FUNCTION key.  
The upper display now shows the output of the position sensor in Volts.  
7
8
Loosen the allen screw in the hub of the NCS spoiler just enough to be able to rotate the  
spoiler. See Figure 28.  
Adjust the NCS spoiler so that the voltage in the local display is 2.500 ± 0.010 volts dc. The  
allen screw should be almost in a vertical position. The bottom edge of the spoiler should  
almost be horizontal in relation to the NCS PWA. See Figure 28.  
9
Tighten NCS spoiler set screw with an allen wrench, holding spoilers located on each side of  
the NCS PWA in position.  
IMPORTANT: Spoilers need to be held in position both rotationally and longitudinally along  
the drive shaft extension. An air gap must be maintained between the surface of the PWA and  
each spoiler. (Any plastic or paper insulating material may be used to create this gap while  
positioning the spoilers). Make sure that neither spoiler is touching the sensor PWA when the  
adjustment is complete.  
10  
11  
12  
13  
Press DISPLAY key to exit calibration mode.  
Remove AC power to the actuator. Reinstall relay cards If present.  
Install a new gasket and replace extended cover. Secure to actuator with screws.  
Continue with calibration procedure in Table 31.  
74  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Calibration  
NCS set  
screw  
NCS PWA  
Relay PWA card  
guides (relay  
PWAs removed)  
NCS Spoiler (shown at full  
150 degree travel CCW)  
Figure 28 Location of NCS Assembly  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
75  
Set Up and Calibration Procedures  
Calibration  
Table 30 Potentiometer Position Sensor Calibration Procedure  
Step  
1
Action  
Remove AC power to the actuator.  
2
Remove the six screws and the top cover from the actuator case. See Figure 2.  
Lay extended cover assembly on a flat surface. Remove relay cards if present.  
3
4
Reapply AC power to the actuator.  
Press SET UP key to access the INPUT set up group.  
Press FUNCTION key until the lower display reads Direct.  
Press the  
or  
keys to set Actuator Rotation direction to CCW.  
NOTE: Actuator direction must be set to CCW for this procedure. Direction can be changed  
after calibration is complete.  
5
6
Drive the actuator to the 50% position (this refers to the position on the actuator scale for CCW  
rotation). This should be done manually with the handwheel or with the AUTO - MANUAL  
switch.  
Press SET UP key until the display reads CAL POSOUT.  
Press the FUNCTION key until the dispaly reads DIS CALPOS.  
Press the  
or  
keys until the lower display reads BEGN CALPOS.  
Press FUNCTION key.  
The upper display now shows the output of the position sensor in Volts.  
7
8
Loosen the set screw at the end of the switch camshaft where the potentiometer connects to  
the shaft.  
Using pliers, adjust the white plastic knob on the back side of the potentiometer so the voltage  
in the local display is 2.500 ± 0.010 volts dc.  
9
Tighten set screw with an allen wrench.  
10  
11  
12  
13  
Press DISPLAY key to exit calibration mode.  
Remove AC power to the actuator. Reinstall relay cards If present.  
Install a new gasket and replace extended cover. Secure to actuator with screws.  
Continue with calibration procedure in Table 31.  
76  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Calibration  
Potentiometer position sensor  
Mounting bracket  
Figure 29 Location of potentiometer position sensor  
Table 31 Load Position Sensor Factory Calibration  
Action  
Step  
1
Reapply AC power to the actuator.  
2
Press SET UP key to access the MAINT set up group. Press the FUNCTION key until the  
display reads LD CAL.  
Press the  
or  
keys until the display reads POS.  
3
4
Perform the Calibrate Motor procedure exactly as in Table 26 Motor calibration must be  
performed for the factory configured full span range (0-100%).  
ATTENTION  
When calibrating the motor to a short stroke range, you must reset the end-of-travel limit  
switches. See Setting End-of-Travel Limit Switches.  
When motor calibration is complete, the calibration is now stored as the factory calibration of  
the actuator motor.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
77  
Set Up and Calibration Procedures  
Setting End-of-Travel Limit Switches  
Setting End-of-Travel Limit Switches  
ATTENTION  
Referring to Figure 31. The first two cams (starting from the front) are for the 0% and  
100% limit switches (Switch #1 and Switch #2) and should not need any adjustments as  
they are factory set to stop the drive at 0% and 100%. See Figure 30 for limit switch  
settings.  
END OF TRAVEL LIMIT SWITCH SETTINGS  
(FACTORY SET AT 0% AND 100%)  
100%  
0%  
SW2 COM)  
SW1 COM)  
NC  
SW#1  
Clockwise Rotation  
NC  
SW#2  
Counterclockwise Rotation  
Clockwise and counterclockwise rotation is the direction of the output shaft when  
facing the end of the shaft. As shown, full clockwise rotation of the output shaft  
activates SW1 and CCW rotation activates SW2.  
Figure 30 End of Travel Limit Switch Settings  
REFERENCE  
An unactuated switch will have its normally closed (NC) contacts closed and its normally open  
(NO) contacts open.  
An actuated switch will have its NC contacts become open and its NO contacts become  
closed. Both NC and NO contacts are available at the terminal block. See Figure 8 (page 18)  
and Figure 9 (page 19).  
An unactuated switch has its roller arm in the up position when adjacent to the reduced  
diameter portion of the cam.  
If it becomes necessary to do adjust the limit switch cams in the field, use the procedure given in Table 32.  
While the unit is powered, a potentially lethal shock hazard exists inside the case.  
78  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Setting End-of-Travel Limit Switches  
Table 32 End-of-Travel Limit Switch Setting Procedure  
Step  
1
Action  
Remove AC power to the actuator.  
2
Remove the six screws and the cover from the actuator case. See Figure 2. Lay cover  
assembly on a flat surface.  
3
Using a flat blade screwdriver in the slots at the edge of the cams, or your finger, rotate the  
cams until the switches are set. (See Figure 31).  
Rotate the actuator shaft, using the manual handwheel or the auto-manual switch, to the 0%  
position (this is the 0% for CCW operation using the bottom scale or 100% for CW operation  
using the top scale). If the actuator is installed on a damper or valve, also make sure that  
this position is synchronized with the travel of the final control element.  
Rotate the #1 limit switch operating cam to activate at this position. The switch roller arm  
should go from being in an up, not depressed state, to a depressed state as the cam is  
rotated in the direction of the shaft rotation going toward the limit position. This will cause  
the switch to go from NC to NO and turn off the power to the motor when the switch  
activates. Switch activation may be detected by the clicking sound or with a continuity tester  
connected to the terminals.  
Rotate the actuator shaft, using the manual handwheel or the auto-manual switch, to the  
100% position (this is 100% for CCW operation using the bottom scale or 0% for CW  
operation using the top scale). If the actuator is installed on a damper or valve, also make  
sure that this position is synchronized with the travel of the final control element.  
Rotate the #2 limit switch operating cam to activate at this position. The switch roller arm  
should go from being in an up, not depressed state, to a depressed state as the cam is  
rotated in the direction of the shaft rotation going toward the limit position. This will cause  
the switch to go from NC to NO and turn off the power to the motor when the switch  
activates.  
If optional auxiliary switches were ordered, these switches may also be set at this time. (See  
Setting Auxiliary Switches (page 81).  
4
Double check limit switch actuation by first manually driving the actuator to each end of travel  
and hearing the switch click or by detecting it with a continuity tester. Secondly, drive the  
actuator to both ends of travel (using the auto/manual switch or by providing minimum and full  
input signal) and make sure the switches activate and turn off the motor.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
79  
Set Up and Calibration Procedures  
Setting End-of-Travel Limit Switches  
ATTENTION  
Make sure you do not to set the switches too close to the hard stop.  
Relay PWAs  
Relay #1  
End of travel switch #1  
(stops CW rotation)  
End of travel switch #2  
(stops CCW rotation)  
Relay #2  
Relay #3  
Relay #4  
Aux switch #1  
Aux switch #2  
Aux switch #3  
Aux switch #4  
Figure 31 Location of End-of-Travel Limit and Auxiliary Switches  
80  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Set Up and Calibration Procedures  
Setting Auxiliary Switches  
Setting Auxiliary Switches  
ATTENTION  
Referring to Figure 31. The first two cams (starting from the front) are for the 0% and  
100% end of travel limit switches (Switches #1 and #2) and should not need any  
adjustments as they are factory set to stop the actuator precisely at 0% and 100%. See  
Setting End-of-Travel Limit Switches (page 78).  
Additional switch settings should be set so that switch #3 operates in synchronism with switch  
#1 (i.e., both activating when the actuator is going in the same direction) and switch #4 to  
operates in synchronism with switch #2, etc. See Figure 32 for auxiliary switch settings.  
0%  
100%  
(SW 6 COM)
(SW5 COM)  
(SW3 COM)  
(SW4 COM)  
NC  
NO  
SW #3  
NC  
NC  
NO  
SW #4  
SW #5  
NO  
NC  
NO  
SW #6  
Figure 32 Auxiliary Switch Settings  
If it becomes necessary to do adjust the auxillary switch cams in the field, use the procedure given in Table  
33.  
While the unit is powered, a potentially lethal shock hazard exists inside the case.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
81  
Set Up and Calibration Procedures  
Setting Auxiliary Switches  
Table 33 Auxiliary Switch Setting Procedure  
Action  
Step  
1
2
Remove AC power to the actuator.  
Remove the six screws and the cover from the actuator case. See Figure 2. Lay cover  
assembly on a flat surface.  
3
4
Using a flat blade screwdriver on the slots on edge of cams, or your fingers, rotate the cams  
until the switches are set. (See Figure 31)  
The auxiliary switches should be set so switches #3 and #5 operate in synchronism with  
switch #1 (i.e., both activating when the drive is going in the same direction) and set  
switches #4 and #6 to operate in synchronism with switch #2. See Figure 32 for auxiliary  
switch settings.  
For Switches #3 and #5:  
Rotate the actuator shaft, using the manual handwheel or the auto-manual switch, to the  
desired low scale position.  
Rotate the #3 switch operating cam to activate at this position. The switch roller arm should  
go from being in an up, not depressed state, to a depressed state as the cam is rotated in  
the direction of the shaft rotation going toward the limit position. This will cause the switch to  
go from NC to NO and turn off the power to the motor when the switch activates. Switch  
activation may be detected by the clicking sound or with a continuity tester connected to the  
terminals.  
Repeat for Switch #5 if applicable.  
5
For Switches #4 and #6:  
Rotate the actuator shaft, using the manual handwheel or the auto-manual switch, to the  
desired up scale position.  
Rotate the #4 switch operating cam to activate at this position. The switch roller arm should  
go from being in an up, not depressed state, to a depressed state as the cam is rotated in  
the direction of the shaft rotation going toward the limit position. This will cause the switch  
to go from NC to NO and turn off the power to the motor when the switch activates.  
Repeat for Switch #6 if applicable.  
6
Double check limit switch actuation by first manually driving the actuator to each end of travel  
and hearing the switch click or by detecting it with a continuity tester. Secondly, drive the  
actuator to both ends of travel (using the auto/manual switch or by providing minimum and full  
input signal) and make sure the switches activate and turn off the motor.  
82  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Start-Up/Operation  
Introduction  
Start-Up/Operation  
Introduction  
After the actuator is completely installed, wired, and the preliminary adjustments made, it is advisable to check  
the operation of the actuator and controlled device before placing it in service. In other words, operate the  
controlled device and check its direction of travel in response to an increase of the input signal and make sure it  
is correct for the process. Actuators having the optional auto-manual switch must have the knob set in the  
AUTO position.  
This section provides a checklist that can be used to do a walk-through with the actuator before it is actually  
used for control. Other features which may be helpful in understanding actuator operation are also provided.  
Power-up Diagnostics  
When power is applied to the actuator, the actuator electronics performs a diagnostic routine on various device  
components. These tests include a:  
RAM diagnostic (RAMTST),  
Check of the electrically eraseable PROM (SEETST),  
Verification that valid parameter values are in the actuator configuration (CFGTST),  
Verification of valid calibration values (CALTST)  
Test of the local display and LED indicators (all display segments and LED indicators light simultaneously).  
The local display shows the status of the diagnostics as they are completed during power up. TEST DONE is  
shown on the display when diagnostics are complete and actuator should be in AUTO mode. See Table 20 for  
more information on the power up diagnostics.  
Operations Checklist  
To make sure that the actuator is properly installed and set up for your particular application, you should check  
and verify the following:  
Verify that the configuration is correct for your application by stepping through all set up groups and  
checking the setting of all set up parameters.  
Verify operation of end-of-travel limit switches.  
Verify operation of auxiliary switches or relay function (if installed).  
Check operation of AUTO - MANUAL DRIVE switch (if present), by setting the knob to the CW and CCW  
- MANUAL positions. The output shaft should rotate in the direction indicated by the knob. The LED  
indicator on the local display should also indicate the actuator is in manual mode.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
83  
Start-Up/Operation  
Operating Displays  
Operating Displays  
Pressing the DISPLAY key cycles the display through a number of operating parameters. Table 34 shows a  
number of sample displays that can be shown during operation.  
Table 34 Typical Operating Displays  
Display  
Description  
Input—  
Upper Display = Shows input value  
Lower Display = prompt  
0.0  
INP  
Output—  
Deviation—  
Upper Display = Shows input value  
Lower Display = Shows output value  
00  
OP 0.5  
Upper Display = Shows input value  
Lower Display = Shows value of deviation of  
sensor from input.  
100.0  
DE 99.9  
Position—  
Upper Display = Shows value of position sensor.  
Lower Display = prompt  
0.6  
POS  
NOTE: Position display will show negative values, if appropriate.  
NOTE: When the AUTO/MANUAL key is pressed, placing the actuator in manual mode, the local display  
mode is forced to the Position display (POS). The Manual L.E.D. indicator should be lit. When the  
AUTO/MANUAL key is pressed again, placing the actuator in auto mode, the local display mode is forced to  
the Output display (OP). The Auto L.E.D. indicator should be lit. Set up parameters can still be accessed.  
Motor Stall  
The actuator is equipped with a low current motor that prevents against burnout if the motor becomes stalled. A  
stall condition occurs when the motor position does not follow the input, or if the motor does not reach setpoint  
within a given period of time.  
When the stall condition occurs, a stall alarm is indicated. The actuator sets the STALLED LED indicator ON  
and also any other alarms or relay contacts that are programmed to close whenever a stall condition is detected.  
The motor drive for the indicated direction is shut off approximately 3 minutes after the stall alarm is indicated.  
Also, the appropriate CW/CCW LED direction indicator is turned OFF.  
The maintenance statistic for accumulated stall time gets updated during the stalled condition.  
To reactivate the drive in the stalled direction, change the position of the drive to the opposite direction and set  
at a point below where the stall originally occurred, then start the drive in the stalled direction.  
Note: A stall condition is not detected if a limit end of travel limit switch is activated while the motor is moving  
toward the setpoint, or if the motor position is within 0.5% of calibrated motor 0% and 100% end points.”  
84  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Start-Up/Operation  
Position Sensor Operation  
Position Sensor Operation  
On HercuLine® 2000 and HercuLine® 2001 the potentiometer position sensor is a sealed film pot that is directly  
coupled to the output shaft. On HercuLine® 2002 the non-contact sensor (NCS) is inductively coupled to the  
output shaft of the actuator so that the sensor detects shaft position. The sensor is adjusted at the factory and  
under normal conditions and requires no adjustment. A simple check can verify that the sensor working  
properly and that it is in adjustment. Verification of the output is performed by setting the drive motor to its  
zero, midpoint and 100% positions and observing the output voltage of the sensor. The actuator has a feature  
that the sensor output voltage can be read from the local display.  
Step  
1
Action  
Drive the motor to 50% position.  
Press SET UP key on the keyboard until the display reads CAL POSOUT.  
Press FUNCTION key until the display reads DIS CALPOS.  
2
Press the  
Press the FUNCTION key.  
Upper Display = n.nnn (Output voltage of the sensor)  
or  
keys until the display reads BEGN CALPOS.  
Lower Display = POSOUT  
The display should read 2.500 +/– 0.012 Volts for both 90° and 150° operation.  
3
4
Press DISPLAY key and then drive the motor to zero position. Repeat Step 2.  
The display should read 1.600 +/– 0.060 Volts for 90° operation; 1.000 +/- 0.060 volts for 150°  
operation.  
Press DISPLAY key and then drive the motor to 100% position. Repeat Step 2.  
5
6
The display should read 3.400 +/– 0.060 Volts for 90° operation; 4.000 +/- 0.060 volts for 150°  
operation.  
If the sensor needs adjustment, refer to the “Calibrate Non-Contact Sensor” procedure in Table  
29 (page 74).  
Remote Setpoint Operation  
The HercuLine® 2001/2002 actuator can be set up to receive a digital input from a remote source. The actuator  
uses RS485 communications that supports digital Modbus RTU protocol. Press the SET UP key to select the  
Input set up group. Change the Input Type to Remote Setpoint (R_SP). Make the necessary connections to  
terminals 6, 7, 8 on the actuator terminal block. See Figure 33. Communicaton parameters should be set to the  
same values as the host device. The actuator communication parameters are accessed in the Communications  
Set Up group.  
There are some restrictions to actuator operation when remote setpoint input is active. In order to provide a  
bumpless transfer when switching from one input signal type to remote setpoint, the actuator will use the last  
known analog input value as its setpoint when switching to remote setpoint input operation. No input filtering  
is active on the input signal to the actuator.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
85  
Start-Up/Operation  
Remote Setpoint Operation  
Actuator  
Terminal  
Block  
9
10  
6
7
8
-
COM  
+
SHIELD  
INP  
DIGITAL INPUT  
COMMUNICATION  
Figure 33 Terminal Block Connections for Modbus Communications  
86  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Maintenance  
Introduction  
Maintenance  
Introduction  
There is some basic maintenance that is recommended for the HercuLine® 2000 Series Actuators. The  
electronic PWAs within the actuator require no maintenance or servicing under normal conditions.  
If there is a problem, refer to information in this section or to Troubleshooting (page 105) .  
Basic Maintenance  
Position Sensor  
Under normal conditions the position sensor does not require maintenance.  
Main Gear Lubrication  
Under normal operating conditions, the main worm gear should not require maintenance.  
Spur Gear Lubrication  
Honeywell recommends that during major shutdown periods the spur gears should be inspected and  
lubricated. Follow the steps in Table 35 to access the spur gear compartment and lubricate the gears if  
necessary.  
Disconnect power before opening the actuator case to inspect the actuator gears. A  
potentially dangerous pinch hazard exists inside the case if the unit is open while  
powered.  
Table 35 Spur Gear Lubrication Procedure  
Step  
Action  
1
2
3
Remove AC power from actuator.  
Remove the six screws and the bottom cover of the actuator case. See Figure 34.  
Inspect the final spur gear, the idler gear and motor pinion for excessive wear and adequate  
lubrication. See Figure 34.  
4
If needed, use Texaco Starplex 2 EP grease, or equivalent and apply lubricant to assure that  
the gears are adequately protected.  
5
6
Install a new gasket and replace side cover. Secure to actuator with screws.  
Restore actuator to service.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
87  
Maintenance  
Basic Maintenance  
Bottom cover  
Gears  
Idler spur  
gear  
Final output  
spur gear  
Motor pinion  
gear  
Figure 34 Spur Gear Location  
88  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Maintenance  
Replacement Procedures  
Replacement Procedures  
Fuse Replacement  
The motor drive circuit contains two fuses. They are located on the power distribution PWA. If it becomes  
necessary to replace these fuses, follow the procedure in Table 36 and refer to Figure 36 for fuse location.  
Disconnect power before opening the actuator case to replace the fuse(s). A  
potentially lethal shock hazard exists inside the case if the unit is opened while  
powered.  
Table 36 Motor Drive Fuse Replacment Procedure  
Step  
1
Action  
Remove AC power from actuator.  
2
Remove the 6 screws and the extended cover of the actuator case. See Figure 35.  
Lay assembly down on a flat surface.  
3
4
Remove connectors from CPU and power distribution PWA.  
Remove power distribution PWA.  
5
6
Locate the two fuses on the power distribution PWA. See Figure 36. Carefully remove and  
replace fuse(s) with Wickmann T1 type 6A 250V, or equivalent (not available from Honeywell).  
7
8
9
Reinstall power distribution PWA.  
Reconnect connectors to CPU and power distribution PWA.  
Install a new gasket and replace extended cover. Secure to actuator with screws.  
Relay connector #1  
Relay connector #2  
Relay connector #3  
Relay connector #4  
CPU  
connections  
Power  
distribution  
PWA  
}Relay PWA#1  
}Relay PWA#2  
Figure 35 Power Distribution PWA and Relay PWA Locations  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
89  
Maintenance  
Replacement Procedures  
Fuses for  
Motor Drive  
Circuit  
Power Distribution PWA  
Figure 36 Motor Drive Circuit Fuses  
Relay PWA Replacement  
If a relay PWA needs to be replaced, follow the procedure in Table 37 to access and replace the PWA.  
Disconnect power before opening the actuator case. A potentially lethal shock  
hazard exists inside the case if the unit is opened while powered.  
Table 37 Relay PWA Replacement Procedure  
Step  
Action  
1
2
3
4
5
Remove AC power from actuator.  
Remove the six screws and the cover of the actuator case. See Figure 35.  
Lay assembly down on a flat surface.  
Disconnect the wire connector from the relay PWA.  
Carefully remove the relay PWA. Pry the locking tabs of the card guides away to unlock the  
PWA and slide it out from the card guides.  
6
Install the replacement relay PWA by sliding it into the card guides until it mates with the  
backplane board. Locking tabs on the card guides will engage to secure the PWA in place.  
7
8
Plug in wire connector to relay PWA.  
Install a new gasket if needed and replace cover. Secure to actuator with screws.  
90  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Replacement/Upgrade/Accessory Kits  
Replacement Kits  
Replacement/Upgrade/Accessory Kits  
Replacement Kits  
This section provides you with a complete list of all the spare parts that may be needed for the HercuLine®  
2000 Series Actuators and optional equipment.  
To determine which kit you need, cross-reference Figure 37 through Figure 41 with Table 38 on page 96.  
Each kit contains replacement parts accessories and instructions for component replacement.  
11  
12  
6,7  
,8  
14  
11  
14  
Figure 37 Replacement Kits 6, 7, 8, 11, 12, 14  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
91  
Replacement/Upgrade/Accessory Kits  
Replacement Kits  
10  
Figure 38 Replacement Kit 10  
92  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Replacement/Upgrade/Accessory Kits  
Replacement Kits  
1
15  
19  
4,5,9  
2
16  
3
Figure 39 Replacement Kits 1, 2, 3, 4, 5, 9, 15, 16, 19  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
93  
Replacement/Upgrade/Accessory Kits  
Replacement Kits  
13  
Figure 40 Replacement Kit 13  
94  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Replacement/Upgrade/Accessory Kits  
Replacement Kits  
17, 18  
Figure 41 Replacement Kits 17, 18  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
95  
Replacement/Upgrade/Accessory Kits  
Replacement Kits  
See Figure 37 through Figure 41 for drawings of replacement kit contents.  
Table 38 Replacement kits  
Qty/Unit  
Part Number  
51450802-503  
Description  
Relay Kit  
Figure ID #  
1
2
Relay Pwa  
4
1
Plug 03 Position  
Top Cover Gasket  
Qty/Unit  
Part Number  
51451397-501  
Description  
CPU Kit  
Figure ID #  
2
HercuLine® CPU Bd Assembly  
1
1
1
1
4
1
Plug, 10 Pos  
Label Phonix Connector 1 To 10  
Insulator  
Pin, Snap Lock, .125 X .187 Lg  
Top Cover Gasket  
Qty/Unit  
Part Number  
Description  
Figure ID #  
1
51452302-501  
Part Number  
PROM Kit  
2
Figure ID #  
3
Qty/Unit  
Description  
51451424-501  
Backplane Kit  
HercuLine® Backplane Assy  
Card Guide Assy  
1
1
1
4
4
4
1
Card Guide  
Split Washer  
Machine Screw-Pan Head-Slotted  
Screw,Trilob Philph #4-20x.38  
Top Cover Gasket  
Qty/Unit  
Part Number  
51451656-505  
Description  
Figure ID #  
1000 Ohm Potentiometer Kit 90 Degrees  
(HercuLine® 2000)  
4
1
2
2
2
2
1
Pot 1 K Double 90 Degree  
#6-32 Hex Nut N  
#6 Washer  
#6 Lock Washer  
Machine Screw-Pan Hd-Cross Rec  
Top Cover Gasket  
Kit Instruction# 62-86-33-38  
96  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Replacement/Upgrade/Accessory Kits  
Replacement Kits  
Qty/Unit  
Part Number  
51451656-506  
Description  
Figure ID #  
1000 Ohm Potentiometer Kit 150 Degrees  
(HercuLine® 2000)  
5
1
Pot 1 K Double 150 Degree  
#6-32 Hex Nut N  
2
2
2
2
1
#6 Washer  
#6 Lock Washer  
Machine Screw-Pan Hd-Cross Rec  
Top Cover Gasket  
Kit Instruction# 62-86-33-38  
Description  
Qty/Unit  
Part Number  
50018180-501  
Figure ID #  
Upgrade to Non Contact Position Sensor  
(HercuLine® 2001)  
6
1
4
1
1
1
1
1
1
PCB Assembly  
Screws SEMS #4-40 x .310 lg  
Gasket  
Cable Assembly  
RVI T-Z Setup Gage  
Bracket Molding  
Stainless Steel Pin  
Set Screw 3/32 x 4-40  
Kit Instruction# 62-86-33-46  
Description  
Qty/Unit  
Part Number  
51452342-501  
Figure ID #  
10K Ohm Potentiometer Kit (HercuLine® 2001)  
9
1
2
2
2
2
1
Position Sensor  
#6-32 Hex Nut N  
#6 Washer  
SA2001  
#6 Lock Washer  
Machine Screw-Pan Hd-Cross Rec  
Top Cover Gasket  
Kit Instruction# 62-86-33-40  
Qty/Unit  
Part Number  
Description  
Figure ID #  
515000657-502  
Rvit-Z Ncs Replacement Kit  
Ncs, Rvit-Z Pwa 0-150  
Machnl 4-40 X .31 Pnslstl  
Top Cover Gasket  
19  
1
4
1
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
97  
Replacement/Upgrade/Accessory Kits  
Replacement Kits  
Qty/Unit  
Part Number  
51452174-501  
Description  
Figure ID #  
Crank Arm Kit  
6
1
Crank Arm  
1
1
1
Screw,Hex Hd,1 3/4 X 1/4-20  
Kllwss1/4sp  
Nut Nmsndc 1/4-20  
Qty/Unit  
Part Number  
50011455-501  
Description  
120vac/60HZ Motor Kit  
Motor 120v,50/60 Hz,  
Figure ID #  
7
1
1
1
1
4
4
4
1
Capacitor, 3 µfd 400Vac  
Cable plus Resistor assembly, 600 Ohm  
Resistor Bracket  
Split Washer M5  
M3 X 5mm lg screw w/ext tooth lock washer  
Socket head cap screw-M5 x 12  
Top Cover Gasket  
Kit Instruction# 62-86-33-36  
Description  
Qty/Unit  
Part Number  
50011455-502  
Figure ID #  
120vac/50HZ Motor Kit  
Motor 120v,50/60 Hz,  
7
1
1
1
1
4
4
4
1
Capacitor, 4.0 µfd 400Vac  
Cable plus Resistor assembly, 400 Ohm  
Resistor Bracket  
Split Washer M5  
M3 X 5mm lg screw w/ext tooth lock washer  
Socket head cap screw-M5 x 12  
Top Cover Gasket  
Kit Instruction# 62-86-33-36  
Description  
Qty/Unit  
Part Number  
50011455-503  
Figure ID #  
240VAC/50/60HZ Motor Kit  
Motor 240v,50/60 Hz,  
7
1
1
1
1
4
4
2
4
1
Capacitor, .75 Mfd 400Vac  
Cable plus Resistor assembly, 1100 Ohm  
Resistor Bracket  
Split Washer M5  
M3 X 5mm lg screw w/ext tooth lock washer  
Butt Splice (SA2000)  
Socket head cap screw-M5 x 12  
Top Cover Gasket  
Kit Instruction# 62-86-33-36  
98  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Replacement/Upgrade/Accessory Kits  
Replacement Kits  
Qty/Unit  
Part Number  
Description  
Figure ID #  
Spur Gear Kit  
10  
51452443-501  
51452443-507  
51452443-508  
51452443-509  
51452443-510  
51452443-511  
1
Spur Gear 24p, 18t  
Spur Gear 24p, 18t  
Spur Gear 24p, 36t  
Spur Gear 24p, 72t  
Gear Assembly  
1
1
1
1
1
1
1
1
1
Gear Assembly  
Spur Gear 24p, 36t  
Bottom Cover Gasket  
Intermediate Shaft all except 7.5 seconds  
Intermediate Shaft – 7.5 seconds  
Kit Instructions# 62-86-33-35  
Description  
Qty/Unit  
Part Number  
51452443-502  
Figure ID #  
Auxiliary Switch Kit Replacement and Upgrade  
Cam Assembly (4 Aux switches, 2 end of travel switches)  
Switch and Mounting Plate assembly (6  
Kit Instruction# 62-86-33-45  
11  
1
1
Qty/Unit  
Part Number  
51452443-503  
Description  
Figure ID #  
Gasket Set Kit  
Bottom Cover Gasket  
Shaft Seal  
12  
1
1
1
1
1
1
O-Ring 2.144 Id X 0.070 Buna N  
Top Cover Gasket  
O-Ring Buna N  
Display Gasket  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
99  
Replacement/Upgrade/Accessory Kits  
Replacement Kits  
Qty/Unit  
Part Number  
51452443-504  
Description  
Figure ID #  
Display and Keypad Kit  
13  
1
Display Gasket  
Overlay, Display  
Lens, Display  
1
1
1
1
1
1
1
9
4
4
6
1
1
Gasket,Adhesive Die Cut  
Display Mtg Collar Machining  
Keypad, 6 Position  
Support Plate-Keypad  
Display Pwa  
Sems #4-40 X .310lg Pnphstl  
Screw,Metric Panhd,Cross Rec  
Split Washer  
Sleeve, Keypad  
Display/Keybd Cable  
Top Cover Gasket  
Qty/Unit  
Part Number  
51452443-505  
Description  
R/C Kit (Motor date codes prior to 8/5/2005)  
Capacitor, 2.25 Mfd  
Figure ID #  
14  
1
1
1
1
1
1
Resistor, 200 Ohm,25w  
Capacitor, .75 Mfd, 400vac  
Resistor, 500 Ohm,25w  
Top Cover Gasket  
Bottom Cover Gasket  
Kit Instruction 62-86-33-44  
100  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Replacement/Upgrade/Accessory Kits  
Replacement Kits  
Qty/Unit  
Part Number  
51452443-506  
Description  
R/C Kit (Motor date codes after to 8/5/2005)  
Capacitor, 4.0 Mfd  
Figure ID #  
1
1
1
1
1
1
1
1
1
1
1
1
Cable plus Resistor, 400Ohm  
Capacitor, 3 Mfd, 400vac  
Cable plus Resistor, 600 Ohm  
Capacitor, 0.75 Mfd, 400vac  
Cable plus Resistor, 1100 Ohm  
Top Cover Gasket  
1
1
Bottom Cover Gasket  
Kit Instruction 62-86-33-44  
Qty/Unit  
Part Number  
51500166-503  
Description  
Power Distribution Pwa Kit  
Power Dist Pwa  
Figure ID #  
15  
1
1
2
1
Insulator  
Pin, Snap Lock, .125 X .187 Lg  
Top Cover Gasket  
Qty/Unit  
Part Number  
51500457-502  
Description  
Transformer Kit  
Figure ID #  
16  
1
2
2
1
Transformer  
Split Washer  
Machine Screw-Pan Hd-Cross Rec  
Top Cover Gasket  
Qty/Unit  
Part Number  
Description  
Figure ID #  
515000581-503  
Auto/Manual Switch (replacement)  
Auto/Manual Label  
17  
1
1
1
1
1
1
Nut, Sealing 3/8-32 Thrd  
Knob  
A/M Switch/Wire Assy  
Label, Customer Wiring,  
Top Cover Gasket  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
101  
Replacement/Upgrade/Accessory Kits  
Upgrade Kits  
Qty/Unit  
Part Number  
Description  
Figure ID #  
18  
515000581-504  
Auto/Manual Switch (upgrade)  
Auto/Manual Label  
1
1
1
1
1
1
Nut, Sealing 3/8-32 Thrd  
Knob  
A/M Switch/Wire Assy  
Label, Customer Wiring,  
Top Cover Gasket  
Upgrade Kits  
Qty/Unit  
Part Number  
51452444-502  
Description  
Cover (with Display no Handwheel)  
1
Display gasket  
1
1
1
1
1
1
1
1
9
4
4
6
1
1
Overlay, display  
Lens, display  
Gasket,adhesive die cut  
Display mtg collar machining  
Keypad, 6 position  
Support plate-keypad  
Display PWA  
Top cover w/display no hndwhl  
Sems #4-40 x .310lg pnphstl  
Screw,metric panhd,cross rec  
Split washer  
Sleeve, keypad  
Display/keybd cable HercuLine 2001/2002  
Top cover gasket  
102  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Replacement/Upgrade/Accessory Kits  
Upgrade Kits  
Qty/Unit  
Part Number  
51452444-503  
Description  
Cover with Display and Handwheel  
Display gasket  
1
1
1
1
1
1
1
1
1
9
4
1
1
4
6
1
1
1
1
Overlay, display  
Lens, display  
Gasket,adhesive die cut  
Display mtg collar machining  
Keypad, 6 position  
Support plate-keypad  
Display PWA  
Top cover w/display & hndwheel  
Sems #4-40 x .310lg pnphstl  
Screw,metric panhd,cross rec  
Hand wheel  
O-ring buna n  
Split washer  
Sleeve, keypad  
Display/keybd cable HercuLine® 2001/2002  
Retaining ring  
Shim  
Top cover gasket  
Qty/Unit  
Part Number  
Description  
51452444-504  
Part Number  
51451656-510  
Blank Cover with Handwheel  
Description  
Qty/Unit  
1000 ohms 90 degrees upgrade kit  
Machine screw-pan hd-cross rec  
Knob  
2
1
1
1
2
2
2
1
1
2
2
2
Bracket molding  
Pot 1K double 90 degree  
#6 lock washer  
Machine screw-pan hd-cross rec  
#6-32 hex nut N  
Stainless steel pin  
3/32x4-40 setscrew sshxsocupsb  
Washer #6  
Flat washer M4 (zinc)  
Resistor 158 ohms 1% 1/2W  
Kit Instruction# 62-86-33-39  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
103  
Replacement/Upgrade/Accessory Kits  
Accessory Kits  
Qty/Unit  
Part Number  
51451656-511  
Description  
1000 ohms 150 degrees upgrade kit  
2
Machine screw-pan hd-cross rec  
1
1
1
2
2
2
1
1
2
2
2
Knob  
Bracket molding  
Pot 1K double 150 degree  
#6 lock washer  
Machine screw-pan hd-cross rec  
#6-32 hex nut N  
Stainless steel pin  
3/32x4-40 setscrew sshxsocupsb  
Washer #6  
Flat washer M4 (zinc)  
Resistor 158 ohms 1% 1/2W  
Kit Instruction# 62-86-33-39  
Accessory Kits  
Part Number  
51197910-001  
51452354-509  
51452354-510  
51452174-501  
51452791-001  
51452352-501  
Description  
HAL Linkage Analysis software  
HercuLink® software (PC/Palm)  
Battery powered Palm/485 converter w/cables  
Crank Arm - Standard  
Crank Arm – 2003 Unit  
Turk Cable for Communication Connection  
104  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Troubleshooting  
Introduction  
Troubleshooting  
Introduction  
Troubleshooting procedures can be followed when inaccurate or faulty actuator operation is detected. In  
this section, troubleshooting procedures consist of a few simple flow charts to test for proper function of  
various actuator components. Component replacement is at the PWA or assembly level.  
Table 39 indicates some of the observable symptoms of failure that can be identified by noting the faulty  
actuator operation.  
Table 39 Observable Symptoms of Failure  
Symptom  
No Actuator current output.  
Procedure  
Replace CPU Assembly  
No Actuator slidewire output.  
Replace CPU Assembly  
See Figure 42  
Local display does not light.  
Actuator fails one or more power up diagnostics.  
Actuator motor does not drive in response to input signal.  
See Figure 43  
Perform input calibration.  
See Figure 42  
Actuator motor does not drive to proper position.  
Perform motor calibration.  
Actuator Motor is “Hunting”  
(Motor does not drive to a position and stop.)  
Process control loop is not tuned correctly.  
Refer to the Instruction Manual for your  
controller on how to tune a loop.  
Increase the Deadband in the Actuator  
and/or in the control loop.  
Position sensor position is not correct.  
Auto/Manual Switch does not operate correctly.  
Relay(s) does not operate.  
See page 85.  
See Figure 45  
See Figure 46  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
105  
Troubleshooting  
Troubleshooting Procedures  
Troubleshooting Procedures  
Overview  
Follow the procedure or flow chart to test for and determine actuator component operation. When using  
the flow charts for troubleshooting, you may be instructed to go to another flow chart in order to identify  
the faulty component. Instruction for replacing actuator components can be found either in Maintenance  
(page 87) or in the kit with the replacement components.  
Equipment needed  
You will need the following equipment in order to troubleshoot the symptoms listed in the tables that  
follow:  
DC Milliammeter – mA DC  
Calibration source – Volt, mA, etc.  
Digital Voltmeter  
Safety precautions  
Exercise appropriate safety precautions when troubleshooting the actuator operation.  
While the unit is powered, a potentially lethal shock hazard exists inside the case.  
Do not open the case while the unit is powered. Do not access the terminals while  
the unit is powered.  
106  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Troubleshooting  
Troubleshooting Procedures  
Test for Actuator Operation  
A
Cycle power  
to actuator.  
No  
Yes  
Does display  
light up?  
Move handwheel  
on actuator 2 or  
3 turns.  
Observe self test.  
No  
Does motor  
reposition  
itself?  
Do all diagnostics pass?  
RAMTST PASS  
SEETST PASS  
No  
Yes  
Yes  
E
CALTST PASS  
CFGTST PASS  
B
Replace display  
assembly  
All LEDs and  
display segments  
light?  
No  
Yes  
E
Replace display  
assembly  
Figure 42 Test for Actuator Operation  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
107  
Troubleshooting  
Troubleshooting Procedures  
Power Up Self Test Diagnostics  
B
Cycle power  
to actuator.  
No  
Yes  
Does display  
light up?  
A
Observe self test.  
No  
Yes  
RAMTST PASS?  
No  
Yes  
Replace CPU  
Assembly.  
SEETST PASS?  
Check actuator  
configuration  
(setup), reconfigure  
if necessary.  
Cycle power to  
No  
Yes  
actuator. If CFGTST  
fails again, replace  
CPU assembly.  
CFGTST PASS?  
Check actuator  
calibration,  
recalibrate  
Cycle power to  
No  
actuator. If CALTST  
fails again, replace  
CPU assembly.  
CALTST PASS?  
Yes  
if necessary.  
Do all LEDs  
and display  
segments light  
up?  
No  
Yes  
Replace display  
assembly.  
E
Figure 43 Power Up Diagnostics  
Test Non-Contact Sensor PWA  
See page 85.  
108  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Troubleshooting  
Troubleshooting Procedures  
Test Power Distribution PWA  
D
Remove top  
cover of actuator.  
Check Fuses F1  
and F2 on the  
power distribution  
PWA.  
No  
Yes  
Are fuses good?  
Replace fuses with  
same type and  
rating  
Is correct  
No  
Yes  
voltage present  
at test points?  
See below.  
Replace Power  
Distribution PWA.  
Replace CPU  
assembly.  
Figure 44 Test Power Distribution PWA  
Power Distribution PWA Test Points  
Connector  
Test Points - Pins  
Voltage  
J2  
J3  
Pin 1 to pin 7  
5 V  
5 V  
9 V  
Pins 1,2 to pins 3, 4, 8  
Pins 3, 4 to pin 7  
J1  
Pins 5, 6 to pins 7, 8  
Pins 1, 2 to pins 7, 8  
24 V  
28 V + or – 3V  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
109  
Troubleshooting  
Troubleshooting Procedures  
Test AUTO - MANUAL DRIVE Switch  
E
Turn switch to  
Manual CCW  
setting.  
Does motor  
drive in the CCW  
direction?  
No  
Yes  
Turn switch to  
Manual CW setting.  
Does motor  
drive in the CW  
direction?  
No  
Yes  
OK  
Possible trouble spots  
a. Auto/Manual switch  
b. Power Supply PWA. (See D)  
c. Limit switches  
d. Motor  
e. R/C networks  
MANUAL  
OFF  
CCW  
CW  
f. etc.,Others?  
OFF  
A
U
T
O
AUTO - MANUAL DRIVE  
Figure 45 Test AUTO - MANUAL Switch  
110  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Troubleshooting  
Troubleshooting Procedures  
Test Relay Function  
Press SET UP  
button on keypad  
to enter Set up  
mode.  
Set suspect Relay  
type to MAN.  
Set AUTO -  
MANUAL switch  
to MAN.  
Place ohmmeter  
across associated  
relay contacts at  
Actuator terminal  
block. See below.  
No  
Yes  
Does Relay  
operate?  
Replace Relay PWA or  
Wire harness from Relay  
PWA to terminal block.  
See Relay replacement  
in Maintenance, Section 7.  
OK  
Figure 46 Test Relay Function  
Associated Contacts  
Relay  
NC  
RELAY1  
COM  
NO  
NC  
RELAY2  
RELAY3  
RELAY4  
COM  
NO  
NC  
COM  
NO  
NC  
COM  
NO  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
111  
Appendix A - HercuLine® 2001/2002 Configuration Record Sheet  
Appendix A - HercuLine® 2001/2002 Configuration Record  
Sheet  
Enter the value or selection for each set up parameter on this sheet so you will have a record of how your  
actuator is configured.  
Set Up Group  
Parameter  
Setting  
Default  
Prompt  
SET INPUT  
IN TYP - Input Actuation Type  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
See Note 1  
100  
INP HI – Input High Range Value  
INP LO – Input Low Range Value  
0.0  
FILTYP – Input Filter Type  
LPAS  
0
LPFILT – Low Pass Filter Time Constant *  
Direct – Actuator Rotation  
CCW  
0.5  
Dband – Input Deadband  
FSTYPH – Failsafehi Type  
UP  
FSVALH – Failsafehi Input Value  
100  
FSTYPL – Failsafelo Type  
DOWN  
0
FSVALL – Failsafelo Input Value  
CHAR – Input Characterization type  
LINR  
EQUL  
0.0  
CUSTOM -- Custom characterization type  
X0 VAL -- User configurable characterizer value  
X1 VAL -- User configurable characterizer value  
X2 VAL -- User configurable characterizer value  
X3 VAL -- User configurable characterizer value  
X4 VAL -- User configurable characterizer value  
X5 VAL -- User configurable characterizer value  
X6 VAL -- User configurable characterizer value  
X7 VAL -- User configurable characterizer value  
X8 VAL -- User configurable characterizer value  
X9 VAL -- User configurable characterizer value  
X10 VAL - User configurable characterizer value  
X11 VAL - User configurable characterizer value  
X12 VAL - User configurable characterizer value  
X13 VAL - User configurable characterizer value  
X14 VAL - User configurable characterizer value  
X15 VAL - User configurable characterizer value  
X16 VAL - User configurable characterizer value  
X17 VAL - User configurable characterizer value  
X18 VAL - User configurable characterizer value  
5.0  
10.0  
15.0  
20.0  
25.0  
30.0  
35.0  
40.0  
45.0  
50.0  
55.0  
60.0  
65.0  
70.0  
75.0  
80.0  
85.0  
90.0  
112  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Appendix A - HercuLine® 2001/2002 Configuration Record Sheet  
Set Up Group  
Prompt  
Parameter  
Setting  
Default  
X19 VAL - User configurable characterizer value  
X20 VAL - User configurable characterizer value  
Y0 VAL -- User configurable characterizer value  
Y1 VAL -- User configurable characterizer value  
Y2 VAL -- User configurable characterizer value  
Y3 VAL -- User configurable characterizer value  
Y4 VAL -- User configurable characterizer value  
Y5 VAL -- User configurable characterizer value  
Y6 VAL -- User configurable characterizer value  
Y7 VAL -- User configurable characterizer value  
Y8 VAL -- User configurable characterizer value  
Y9 VAL -- User configurable characterizer value  
Y10 VAL - User configurable characterizer value  
Y11 VAL - User configurable characterizer value  
Y12 VAL - User configurable characterizer value  
Y13 VAL - User configurable characterizer value  
Y14 VAL - User configurable characterizer value  
Y15 VAL - User configurable characterizer value  
Y16 VAL - User configurable characterizer value  
Y17 VAL - User configurable characterizer value  
Y18 VAL - User configurable characterizer value  
Y19 VAL - User configurable characterizer value  
Y20 VAL - User configurable characterizer value  
RTYP11 – Relay Type  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
95.0  
100.0  
0
0.8  
2.1  
3.2  
4.9  
6.5  
8.4  
10.7  
13.2  
15.7  
18.7  
22.6  
27.2  
33.4  
40  
46  
53.8  
63.2  
73.7  
86.2  
100  
NONE  
0
SET RELAY  
R11VAL – Relay Value  
R11 HL – Relay High/Low  
LO  
R11SCALE– Relay Scale  
X1  
RTYP12 – Relay Type  
NONE  
0
R12VAL – Relay Value  
R12 HL – Relay High/Low  
LO  
R12SCALE– Relay Scale  
X1  
RLY1HY – Relay Hysteresis  
0
RTYP21 – Relay Type  
NONE  
0
R21VAL – Relay Value  
R21 HL – Relay High/Low  
LO  
R21SCALE– Relay Scale  
X1  
RTYP22 – Relay Type  
NONE  
0
R22VAL – Relay Value  
R22HL– Relay High/Low  
LO  
R22SCALE– Relay Scale  
X1  
RLY2HY – Relay Hysteresis  
0
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
113  
Appendix A - HercuLine® 2001/2002 Configuration Record Sheet  
Set Up Group  
Prompt  
Parameter  
Setting  
Default  
RTYP31 – Relay Type  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
NONE  
R31VAL – Relay Value  
R31 HL – Relay High/Low  
R31SCALE– Relay Scale  
RTYP32 – Relay Type  
0
LO  
X1  
NONE  
R32VAL – Relay Value  
R32HL– Relay High/Low  
R32SCALE– Relay Scale  
RLY3HY – Relay Hysteresis  
RTYP41 – Relay Type  
0
LO  
X1  
0
NONE  
R41VAL – Relay Value  
R41 HL – Relay High/Low  
R41SCALE– Relay Scale  
RTYP42 – Relay Type  
0
LO  
X1  
NONE  
R42VAL – Relay Value  
R42HL– Relay High/Low  
R42SCALE– Relay Scale  
RLY4HY – Relay Hysteresis  
CUROUT - Output Signal Range  
0
LO  
X1  
0
See Note 1  
SET CUROUT  
SET COMM  
COMM – Communications Parameters  
ADDRES – Device Address  
BAUD – Baud Rate  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
MODBUS  
1
19.2K  
20MS  
FP B  
XmtDLY – Response Delay  
DBLBYT – Floating Point Data Format  
DIGINP – Digital Input State  
Endpos – End Position Value  
DECMAL – Decimal Point Location  
EUNITS – Units Display  
UP  
SET DIGINP  
SET DISPLA  
0
8888  
Pcnt  
UNITS – Display Units  
ENG  
LOCKID – Password Lock  
0
SET LOCK  
MAENAB – Enabled  
ENAB  
NONE  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
LOCK – Lock Out  
FAILSF – Failsafe  
READ STATUS  
RAMTST – RAM Test Diagnostic  
SEETST – Serial EEPROM Test Diagnostic  
CFGTST – Configuration Test Diagnostic  
CALTST – Calibration Test Diagnostic  
114  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Appendix A - HercuLine® 2001/2002 Configuration Record Sheet  
Set Up Group  
Prompt  
Parameter  
Setting  
Default  
VERSON – Firmware Version  
SPEED – Stroke Speed  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
__________________  
Read Only  
Factory Set  
Factory Set  
SET DRVINF  
POWER – Power Input Voltage Line Frequency  
TAG – Tag Name  
MFGDAT – Manufacturing Date  
LREP – Date of Last Repair  
LCAL – Date of Last Field Calibration  
REPTYP – Repair Type  
Factory Set  
Factory Set  
Factory Set  
Factory Set  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
TEMP – Actuator Temperature  
TEMPHI – High Temperature Limit  
TEMPLO – Low Temperature Limit  
ACST – Accumulated Stall Time  
STARTS – Accumulated Motor Starts  
RLnCNTS – Relay Cycle Counts  
n = 1, 2, 3, or 4  
SET MAIN  
REGNy – Accumulated Motor Starts for regions  
of motor travel.  
__________________  
y = 0 through 9  
DATSAV – Forced maintenance data save  
MANRST – Maintenance Statistic Reset  
LDCAL – Restore Factory Calibration Type  
LDCFG – Restore Factory Default Configuration  
RESTRT – System Restart  
__________________  
__________________  
__________________  
__________________  
__________________  
_________________  
DIS  
NONE  
NONE  
DIS  
DIS  
NCSOUT – Non-contact sensor circuit output  
Read Only  
CAL NCSOUT  
Note 1: Type is set from model number.  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
115  
Index  
Index  
A
D
Actuator Rotation, 40, 64  
Actuator Set Up, 33  
Set up groups, 33  
Deadband, 7, 40  
Decimal Point Location, 52  
Deviation, 45  
Set up procedure, 36  
Actuator Statistics  
Relay type, 47  
Device Address, 50  
Direction of Rotation, 7  
Duty Cycle, 7  
Accumulated motor starts, 59  
Motor starts, 59  
Relay cycle counts, 59  
Reset, 60  
Temperature limits, 59  
Total degrees of motor travel, 59  
Applications  
E
Electrical and Performance Specifications, 6  
Electrical Installation, 17  
Enclosure, 5  
Enclosure Rating, 6  
End of travel Limit Switches, 6  
Exiting Set Up mode, 33  
Basic flow control, 27  
Proportional flow with multiple actuators, 27  
Split range, 26, 30  
Approvals, 6  
Auto/Manual Switch  
Testing, 110  
F
Auto-Manual Switch, 64  
Auxiliary Switches, 81  
Setting, 81  
Failsafe, 40, 41  
Failsafe Input Value, 40, 41  
Failsafe operation, 7  
Feedback, 6  
Auxiliary Switches/Relays, 6  
Flame Safety Module wiring diagram, 23  
Fuses  
B
Baud Rate, 9, 50  
Burner Control/Flame Safety, 23  
Replacement, 89  
G
C
Gear Train, 5  
Calibration, 65  
Set up, 66  
Calibration Values  
Restore, 61  
CE Wiring, 21  
H
Handwheel, 5  
HercuLine 2000 Terminal Connections, 18  
HercuLine 2001/2002 with Auto/Manual Terminal  
Connections, 19  
HerculLine 2003 Wiring Connections and Operation, 20  
Hysteresis, 7, 44  
Change Password  
LOCKID parameter, 54  
Clamp Bolt, 6  
Communications, 7, 9  
Floating point data transfer, 50  
Configuration Prompt Hierarchy, 38  
Configuration Record Sheet, 112  
Configuration Tips, 33  
Connections  
I
Input Calibration, 68  
Input Characterization, 41  
Input Filters, 7, 40  
Input High Range, 39  
Input Impedance, 6  
Output, 23  
Slidewire emulation, 23  
Crank Arm, 5  
Crank Arms, 16  
Input Low Range, 39  
Input Set Up Group, 39  
Input Signal Connections, 22  
Input Signals, 6  
Customer Connections, 17  
CW and CCW Direction. See Actuator Rotation  
116  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Index  
Inputs, 39  
Installation, 12  
Installation Considerations, 13  
Isolation, 6  
Output Calibration, 71  
Output Shaft, 5  
Output Torque, 5  
Output Type, 49  
Outputs, 49  
K
P
Keypad, 8, 31  
Description, 32  
Password, 60  
(LOCKID), 53  
Change, 54  
PDA, 9  
Position Range  
L
LEDs on Local Display, 32  
Limit Switches, 78  
Setting, 78  
Relay type, 46  
Position sensing, 7  
POSITION SENSOR OUTPUT, 63  
Power Supply PWA  
Checking, 109  
Product Description, 1  
Programmable Functions, 8  
Pushbuttons  
Linkage Kits, 96  
Linkage Set-up, 15  
Constant torque, 15  
Crank arms, 16  
Variable torque, 15  
Load Requirement, 6  
Local Auto/Manual Switch, 6  
Local Display, 8, 31  
Description, 31  
Description, 32  
R
LEDs description, 32  
Operating displays, 84  
Set up, 52  
Regions of Motor Travel, 62  
REGN parameter, 59  
Relative Humidity, 5  
Relay Function  
LOCK parameter, 33, 36  
Lubrication, 5  
Main (Worm) gear, 87  
Spur gear, 87  
Testing, 111  
Relay PWA Replacement, 90  
Relay Type, 44, 45  
Remote Setpoint Operation, 85  
Repeatability, 7  
Restore Factory Calibration Values, 61  
Rotation, 5  
M
Main Gear Lubrication, 87  
Mains Supply, 6  
Mechanical Installation, 15  
Mechanical Stops, 5  
Modbus communications, 50, 85  
Model distinctions, 1  
Motor, 6  
S
Scale, 5  
Scrolling through Set Up Groups, 33  
Self-test Diagnostics, 55, 83, 108  
Sensitivity, 7  
Motor Calibration, 70  
Motor Current, 6  
Motor Speed, 56  
Motor Stall, 84  
Set Up and Calibration Procedures, 31  
Set Up Groups  
Motor Starts, 45  
Communications, 50  
Current out, 49  
Relay type, 48  
Mounting, 13  
Digital input, 51  
Display, 52  
Drive, 56  
Input, 39  
Lock, 53  
Maintenance, 59  
Read status, 55  
Relays, 44  
N
Non-Contact Sensor, 87  
Checking, 108  
Operation, 85  
Non-Contact Sensor Output Calibration, 72, 73  
Slidewire Emulation, 23  
Solid State Motor Control, 7  
specifications, 5  
Split Range, 26  
Spur Gear Lubrication, 87  
O
Operating Temperature, 7  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
117  
Index  
Stall, 84  
Equipment, 106  
Start Up Checklist, 83  
Storage Temperature, 5  
Stroke Speed, 56  
V
Voltage/ Supply Stability, 7  
T
W
Weight, 5  
Tag Name, 58  
TAG parameter, 56  
Technical and Operating Specifications, 5  
Temperature Coefficient, 7  
Terminal Connections, 18, 19  
Total Degrees of Motor Travel  
TOTDEG parameter, 59  
Troubleshooting, 105  
Z
Zero Suppression, 7  
118  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
Revision 6  
7/07  
Revision 6  
7/07  
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual  
119  
Honeywell Process Solutions  
Industrial Measurement and Control  
512 Virginia Drive  
Fort Washington, PA 19034  
62-86-25-10 0707 Printed in USA  
http://hpsweb.honeywell.com  

AGE07AJ User Manual
Bracketron Multi Vehicle Mount MVM 35 05 User Manual
Cornelius A0081 User Manual
Epson Stylus Printer CX6400 User Manual
GE ASQ05 User Manual
GE General Electric Air Conditioner AG_07 User Manual
Havis Shields Telescoping Computer Base C TCB 17 User Manual
HoMedics BKP 300 2 User Manual
HP Hewlett Packard D411 User Manual
HP Hewlett Packard LASERJET 9050MFP User Manual