Heat Controller Inc Air Conditioner RAD 243A User Manual

+($7ꢀ&21752//(5ꢁꢀ,1&ꢂ  
5RRPꢀ$LUꢀ&RQGLWLRQHU  
AD-183A  
AD-243A  
SERVICE MANUAL  
CAUTION  
• BEFORE SERVICING THE UNIT, READ THE SAFETY  
PRECAUTIONS IN THIS MANUAL.  
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.  
Safety Precautions  
Safety Precautions  
To prevent injury to the user or other people and property damage, the following instructions must  
be followed.  
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is  
classified by the following indications.  
This symbol indicates the possibility of death or serious injury.  
WARNING  
CAUTION This symbol indicates the possibility of injury or damage to property only.  
Meanings of symbols used in this manual are as shown below.  
Be sure not to do.  
Be sure to follow the instruction.  
WARNING  
Installation  
Do not use damaged power cord plugs, or a  
loose socket.  
Always use the power plug and socket with  
the ground terminal.  
• There is risk of fire or electric shock.  
• There is risk of electric shock.  
Service Manual 3  
Safety Precautions  
Do not modify or extend the power cord.  
Do not install, remove, or re-install the unit by  
yourself.  
• There is risk or fire or electric shock.  
• There is risk of fire, electric shock, explosion, or injury.  
Be cautious when unpacking and installing  
the product.  
Do not store or use flammable gas or com-  
bustibles near the air conditioner.  
• Sharp edges could cause injury. Be especially careful  
of the case edges and the fins on the condenser and  
evaporator.  
• There is risk of fire or failure of product.  
Sharp edges  
Gasolin  
Be sure the installation area does not deterio-  
rate with age.  
• If the base collapses, the air conditioner could fall with  
it, causing property damage, product failure, and per-  
sonal injury.  
4 Room Air Conditioner  
Dimensions  
Dimensions  
Symbols Used in this Manual  
This symbol alerts you to the risk of electric shock.  
This symbol alerts you to hazards that could cause harm to the  
air conditioner.  
NOTICE  
This symbol indicates special notes.  
Outside Dimensions  
660  
770  
Model  
18K Btu  
24K Btu  
Dimension  
W
H
mm(inch)  
mm(inch)  
mm(inch)  
660(26")  
428(16 27/32")  
770(305/16")  
660(26")  
428(16 27/32")  
770(305/16")  
D
Service Manual 5  
Specfications  
Product Specifications  
Table -1  
MODELS  
RAD-183A  
ITEMS  
POWER SUPPLY  
COOLING CAPACITY  
INPUT  
1Ø, 208/230V, 60Hz  
17,500/18,000  
1,800/1,850  
E.E.R  
9.0/8.3  
REFRIGERANT (R-22) CHARGE(g)  
720g(25.4oz)  
27(DB),19(WB)  
35(DB),24(WB)  
2 ROW 15 STACKS  
LOUVERED-FIN TYP  
OPERATING  
INDOOR(°C)  
TEMPERATURE  
EVAPORATOR  
OUTDOOR(°C)  
CONDENSER  
2 ROW 19 STACKS,LOUVERED-FIN TYPE  
L-BENDING TYPE  
FAN, INDOOR  
TURBO  
PROPELLER TYPE FAN WITH SLINGER-RING  
3/3  
FAN, OUTDOOR  
FAN SPEEDS, FAN/COOLING  
FAN MOTOR  
6 POLES  
OPERATION CONTROL  
ROOM TEMP. CONTROL  
AIR DIRECTION CONTROL  
WIRELESS REMOCN  
THERMISTOR  
VERTICAL LOUVER(RIGHT & LEFT)  
HORIZONTAL LOUVER(UP & DOWN)  
SLIDE IN-OUT CHASSIS  
CONSTRUCTION  
PROTECTOR  
COMPRESSOR  
INTERNAL OVERLOAD PROTECTOR  
INTERNAL THERMAL PROTECTOR  
3 WIRE WITH GROUNDING  
CORD-CONNECTED TYPE(ATTATCHMENT PLUG:OPTION)  
DRAIN PIPE OR SPLASHED BY FAN SLINGER  
137/62  
FAN MOTOR  
POWER CORD  
DRAIN SYSTEM  
NET WEIGHT  
(lbs/kg)  
OUTSIDE DIMENSION  
(W x H x D)  
(inch)  
(mm)  
26 x 16 27/32 x 30 5/16  
660 x 428 x770  
6 Room Air Conditioner  
Specfications  
Product Specifications  
Table -1  
MODELS  
RAD-243A  
ITEMS  
POWER SUPPLY  
COOLING CAPACITY  
INPUT  
1Ø, 208/230V, 60Hz  
23,500/23,000  
2,760/1,850  
E.E.R  
8.5/8.5  
REFRIGERANT (R-22) CHARGE(g)  
830g(29.3oz)  
27(DB),19(WB)  
35(DB),24(WB)  
3 ROW 15 STACKS  
LOUVERED-FIN TYP  
OPERATING  
INDOOR(°C)  
TEMPERATURE  
EVAPORATOR  
OUTDOOR(°C)  
CONDENSER  
2 ROW 19 STACKS,LOUVERED-FIN TYPE  
L-BENDING TYPE  
FAN, INDOOR  
TURBO  
PROPELLER TYPE FAN WITH SLINGER-RING  
3/3  
FAN, OUTDOOR  
FAN SPEEDS, FAN/COOLING  
FAN MOTOR  
6 POLES  
OPERATION CONTROL  
ROOM TEMP. CONTROL  
AIR DIRECTION CONTROL  
WIRELESS REMOCN  
THERMISTOR  
VERTICAL LOUVER(RIGHT & LEFT)  
HORIZONTAL LOUVER(UP & DOWN)  
SLIDE IN-OUT CHASSIS  
CONSTRUCTION  
PROTECTOR  
COMPRESSOR  
INTERNAL OVERLOAD PROTECTOR  
INTERNAL THERMAL PROTECTOR  
3 WIRE WITH GROUNDING  
CORD-CONNECTED TYPE(ATTATCHMENT PLUG:OPTION)  
DRAIN PIPE OR SPLASHED BY FAN SLINGER  
146/66  
FAN MOTOR  
POWER CORD  
DRAIN SYSTEM  
NET WEIGHT  
(lbs/kg)  
OUTSIDE DIMENSION  
(W x H x D)  
(inch)  
(mm)  
26 x 16 27/32 x 30 5/16  
660 x 428 x770  
7 Room Air Conditioner  
Installation  
Installation  
Select the Best Location  
1.To prevent vibration and noise, make sure the unit is  
installed securely and firmly.  
2.Install the unit where the sunlight does not shine directly  
on the unit.  
FENCE  
AWNING  
3.The outside of the cabinet must extend outward for at  
least 30cm and there should be no obstacles, such as a  
fence or wall, within 50cm from the back of the cabinet  
because it will prevent heat radiation of the condenser.  
Restriction of outside air will greatly reduce the cooling  
efficiency of the air conditioner.  
COOLED AIR  
HEAT  
RADIATION  
ABOUT 10~15mm  
Over 50cm  
CAUTION: All side louvers of the cabinet  
must remain exposed to the outside of  
the structure.  
Figure 1  
4.Install the unit a little slanted so the back is slightly lower  
than the front (about 10~15mm). This will help force con-  
densed water to the outside.  
5.Install the unit from the bottom about 75~150cm above  
the floor level.  
Installation Check  
The setting conditions must be checked prior to initial starting.  
The following items are especially important checking points when the installation is finished.  
1. Grounding wire (Green or Green and Yellow) is provided in the power cord. The green wire must be grounded.  
2. Connect to a single-outlet 15A circuit.  
(or 20A circuit for Electric Heater Model)  
3. To avoid vibration or noise, make sure the air conditioner is installed securely.  
4 Avoid placing furniture or draperies in front of the air inlet and outlet.  
How to Secure the Drain Pipe  
In humid weather, excess water may cause the BASE PAN to overflow. To drain  
the water, remove the DRAIN CAP and secure the DRAIN PIPE to the rear hole of  
the BASE PAN. Press the drain pipe into the hole by pushing down and away from  
Drain pipe  
the fins to avoid injury.  
Drain cap  
Optional  
CABINET  
SCREW  
1. Install the drain pan over the corner of the cabinet where you removed the  
plug with 4 (or 2) screws.  
2. Connect the drain hose to the outlet located at the bottom of the drain pan.  
You can purchase the drain hose or tubing locally to satisfy your particular  
needs. (Drain hose is not supplied).  
3. Select the most appropriate connection from among the following figures (by  
considering the hole of the unit) to fit drain pan to your own unit.  
Fig. 2  
Fig. 4  
Fig. 1  
DRAIN HOSE  
DRAIN  
PAN  
Fig. 3  
Service Manual 8  
Installation  
Window Requirements  
NOTICE  
All supporting parts should be secured to firm  
wood, masonry, or metal.  
26" to 41"  
1. This unit is designed for installation in standard dou-  
ble hung windows with actual opening widths from  
26" to 41".  
18" min  
Stool  
Offset  
The top and bottom window sashes must open suffi-  
ciently to allow a clear vertical opening of 18" from  
the bottom of the upper sash to the window stool.  
Less  
than 1 1/4"  
Sill  
2. The stool offset (height between the stool and sill)  
must be less than 1 1/4".  
Exterior  
Interior wall  
26" min.  
(Without frame curtain)  
Installation Kits Contents  
Foam strip  
(Plain-Back)  
Foam-PE  
(Adhesive-Backed)  
Foam-PE  
(Adhesive-Backed)  
Left frame  
curtain  
Drain joint pipe  
Frame guide(2)  
Window locking  
bracket  
Right frame  
curtain  
Sill bracket(2)  
Type A (14)  
Support bracket(2)  
Type B (7)  
Type C (5)  
Type D (2)  
Carriage Bolt (2)  
Lock Nut (4)  
9 Room Air Conditioner  
Installation  
Suggested Tool Requirements  
PREPARATION OF CHASSIS  
Shipping screws  
1. Remove the screws which fasten the cabinet at both  
sides and at the back.  
Figure 2  
2. Slide the unit out from the cabinet by gripping the  
base pan handle and pulling forward while bracing  
the cabinet.  
3. Cut the window sash seal to the proper length. Peel  
off the backing and attach the Foam-PE to the  
underside of the window sash.  
Figure 3  
4. Remove the backing from Foam-PE with 3 holes  
and attach it to the bottom of the Top retainer bar.  
Top retainer bar  
5. Attach the Top retainer bar on the top of the cabinet  
with 3 screws (Type A).  
Foam-PE  
Foam-PE  
Figure 4  
6. Insert the Frame guides into the bottom of the cabi-  
net.  
Top retainer bar  
7. Insert the Frame Curtain into the Top retainer bar  
and Frame guides.  
8. Fasten the curtains to the unit with 10 screws  
(Type A) at both sides.  
Screw  
(Type A)  
Screw(Type A)  
Figure 5  
Frame guide  
Service Manual 10  
Installation  
Cabinet Installation  
1. Open the window. Mark a line on the center of the  
window stool between the side window stop mold-  
ings.  
Sill  
Bracket  
Support  
Bracket  
Loosely attach the sill bracket to the support bracket  
using the carriage bolt and the lock nut.  
Carriage  
Bolt  
(M-Screw)  
Lock nut  
Figure 6  
2. Attach the sill bracket to the window sill using the  
screws (Type B).  
Machine screw(Type D)  
and lock nut  
Carefully place the cabinet on the window stool and  
align the center mark on the bottom front with the  
center line marked window stool.  
Cabinet  
Track hole  
Outer edge  
of window  
sill  
Support  
Bracket  
Screw(Type B)  
Carriage bolt  
and lock nut  
Sill bracket  
Figure 7  
3. Using the M-screw and the lock nut, attach the sup-  
port bracket to the cabinet track hole. Use the first  
track hole after the sill bracket on the outer edge of  
the window sill. Tighten the carriage bolt and the lock  
nut. Be sure the cabinet slants outward.  
Top  
retainer  
bar  
CAUTION: Do not drill a hole in the  
bottom pan. The unit is designed to  
operate with approximately 1/2" of  
water in bottom pan.  
Window stool  
Figure 8  
Front angle  
Window sash  
Foam-PE  
Top retainer bar  
4. Pull the bottom window sash down behind the Top  
retainer bar until they meet.  
NOTICE  
Cabinet  
Frame curtain  
1. Do not pull the window sash down so tightly that the  
movement of Frame curtain is restricted. Attach the  
cabinet to the window stool by driving the screws  
(Type B) through the cabinet into window stool.  
Foam-PE  
Figure 9  
2. The cabinet should be installed with a very slight tilt  
downward toward the outside.  
Sash track  
Front Angle  
Screw(Type B)  
Figure 10  
11 Room Air Conditioner  
Installation  
5. Pull each Frame curtain fully to each window sash  
track, and pull the bottom window sash down behind  
the Top retainer bar until it meets.  
w(Type C)  
Scre  
6. Attach each Frame curtain the window sash by using  
screws (Type C.) (See Fig. 11)  
Figure 11  
7. Slide the unit into the cabinet.(See Fig. 12)  
CAUTION: For security purpose, rein-  
stall screws(Type A) at cabinet's  
sides.  
Power Cord  
Screw (Type A)  
Figure 12  
Screw  
8. Cut the Foam-strip to the proper length and insert  
between the upper window sash and the lower win-  
dow sash.(See Fig. 13)  
Foam-Strip  
Figure 13  
9. Attach the Window locking bracket with a screw  
(Type C.) (See Fig. 14)  
Window locking  
bracket  
Figure 14  
10. Attach the front grille to the cabinet by inserting the  
tabs on the grille into the tabs on the front of the  
cabinet. Push the grille in until it snaps into  
place.(See Fig.15)  
11. Lift the inlet grille and secure it with a screw (Type  
A) through the front grille.(See Fig. 15)  
Figure 15  
12. Window installation of room air conditioner is now  
completed. See ELECTRICAL DATA for attaching  
power cord to electrical outlet.  
Figure 16  
Service Manual 12  
Operation  
Operation  
Features  
Designed for COOLING ONLY.  
Powerful and whispering cooling.  
Slide-in and slide-out chassis for the simple instal-  
lation and service.  
Built-in adjustable THERMOSTAT  
Washable one-touch filter  
Compact size  
Side air-intake, side cooled-air discharge.  
Reliable and efficient rotary compressor  
Control Locations Function of Controls  
1. Cooling Only Model  
• VENTILATION  
The ventilation lever must be in the CLOSE position  
in order to maintain the best cooling conditions.  
When a fresh air is necessary in the room, set the  
ventilation lever OPEN position.  
The damper is opened and room air is exhausted.  
CLOSE  
VENT  
OPEN  
NOTICE Before using the ventilation feature,  
make the lever, as shown. First, pull down  
part  
to horizontal line with part  
.
• THERMOSTAT  
Thermostat will automatically control the temperature  
of the room. Select a higher number for a cooler tem-  
perature in the room. The temperature is selected by  
positioning the knob to the desired position.  
The 5 or 6 position is a normal setting for average  
conditions.  
• OPERATION  
OFF  
: Turns the air conditioner off.  
MED FAN  
: Permits the medium fan speed operation  
without cooling.  
Thermostat  
Operation  
Auto Swing  
Off  
5
4
6
Med  
Fan  
High  
Cool  
LOW FAN : Permits the low fan speed operation  
without cooling.  
Off  
On  
3
7
8
HIGH COOL: Permits cooling with the high fan speed  
operation.  
2
Low  
Fan  
Med  
Cool  
1
9
MED COOL : Permits cooling with the medium fan  
speed operation.  
Low Cool  
LOW COOL : Permits cooling with the low fan speed  
operation.  
• AUTO SWING  
ON : Air swing is operated while OPERATION knob is  
set to the COOL position.  
OFF : Stops the operation of air swing.  
13 Room Air Conditioner  
Operation  
2. Cooling Only Model with Remote Control and Touch Type  
DISPLAY  
REMOTE CONTROL  
RAD-183A  
RAD-243A  
RAD-183A, RAD-243A  
2
7
3
Power  
1
Temp  
8
5
Fan Speed  
4
2
Timer  
Mode  
1
3
6
Energy  
Saver  
Auto  
Swing  
7
5
6
4
PRECAUTION: The Remote Control unit will not  
function properly if bright light strikes the sensor window of the air conditioner or if  
there are obstacles between the Remote Control unit and the air conditioner.  
POWER BUTTON  
Operation starts, when this button is pressed and stops when you press the button again.  
OPERATION MODE SELECTION BUTTON  
Select Cooling, or Fan or Dehumid mode with button. (Dehumid mode is not to all models.)  
ON/OFF TIMER BUTTON  
Set the time of starting and stopping operation. The timer is set by 1 hour.  
FAN SPEED SELECTOR  
Select the fan speed in three steps.  
- High [F3] Low[F1] Med[F2] High[F3]... .  
ROOM TEMPERATURE SETTING BUTTON  
Control the room temperature within a range of 60°F to 86°F by 1°F.  
ENERGY SAVER(Available In some models)  
The fan stops when the compressor stops cooling.  
Approximately every 3 minutes the fan will turn on and check the room air to determine if cooling is needed.  
6
7
AUTO SWING BUTTON  
Control the horizontal air direcion by air swing system.  
AUTO RESTART  
In case the power comes on again after a power failure, the unit runs as previous setting operation.  
Service Manual 14  
Disassembly  
Disassembly  
Before the following disassembly, CONTROL BOX set to OFF and disconnect the power cord.  
Mechanical Parts  
1. Front Grille  
1. Open the lnlet grille upward .  
2. Remove the screw that fastens the front grille.  
3. Pull the front grille from the right side.  
4. Remove the front grille.  
5. Re-install the component by referring to the removal  
procedure, above.(See Figure 17)  
NOTICE Mark " "of inlet grille means opening  
direction.  
2. Cabinet  
1. After disassembling the FRONT GRILLE, remove the  
2 screws that fasten the cabinet at both sides.  
2. Remove the 2 screws that fasten the cabinet at back.  
3. Pull the base pan forward. (See Figure 18)  
4. Remove the cabinet.  
Figure 17  
5. Re-install the component by referring to the removal  
procedure, above.  
3. Control Box  
1. Remove the front grille. (Refer to section 17)  
2. Remove the cabinet. (Refer to section 18)  
3. Remove the 2 screws that fasten the control box  
cover.  
Figure 18  
4. Remove two housings that connect compressor wire  
and motor wire in the control box.  
5. Discharge the capacitor by placing a 20,000 ohm  
resistor across the capacitor terminals.  
6. Remove the 2 screws that fasten the control box.  
7. Pull the control box forward completely.  
8. Re-install the components by referring to the removal  
procedure, above. (See Figure 19)  
(Refer to the circuit diagram found on page 23 in this  
manual and on the control box.)  
Figure 19  
15 Room Air Conditioner  
Disassembly  
Air Handling Parts  
4. Cover (at the top)  
1. Remove the front grille. (Refer to section 17)  
2. Remove the cabinet. (Refer to section 18)  
3. Remove 11 screws which fasten the brace and  
covers.  
4. Remove the covers and the brace. (See Fig. 20)  
5. Re-install the components by referring to the  
removal procedure, above.  
Figure 20  
5. Blower  
1. Remove the cover. (Refer to section 20)  
2. Remove the 3 screws which fasten the evaporator  
at the left side and the top side.  
3. Move the evaporator sideward carefully.  
4. Remove the orifice from the air guide carefully.  
5. Remove the clamp which secures the blower with  
plier. (See Fig. 21)  
6. Remove the blower with plier or your hand without  
touching blades. (See Fig. 22)  
7. Re-install the components by referring to the  
removal procedure, above.  
Figure 21  
Figure 22  
6. Fan  
1. Remove the cabinet. (Refer to section 18)  
2. Remove the brace and shroud cover.  
(Refer to section 20)  
3. Remove the 5 screws which fasten the condenser.  
4. Move the condenser sideways carefully.  
5. Remove the clamp which secures the fan.  
6. Remove the fan. (See Figure 23)  
7. Re-install the components by referring to the  
removal procedure, above.  
Figure 23  
Service Manual 16  
Disassembly  
6. Shroud  
1. Remove the fan. (Refer to section 21)  
2. Remove the screw that fastens the shroud.  
3. Remove the shroud. (See Figure 24)  
4. Re-install the component by referring to the  
removal procedure, above.  
Figure 24  
Electrical Parts  
7. Motor  
1. Remove the cabinet. (Refer to section 18)  
2. Remove the cover control and disconnect a wire  
housing in control box. (Refer to section 19)  
3. Remove the blower. (Refer to section 21)  
4. Remove the fan. (Refer to section 22)  
5. Remove the 4 screws which fasten the motor.  
(See Figure. 25)  
6. Remove the motor.  
7. Re-install the components by referring to the  
removal procedure, above.  
Figure 25  
8. Compressor  
1. Remove the cabinet. (Refer to section 18)  
2. Discharge the refrigerant system using FreonTM  
Recovery System.  
If there is no valve to attach the recovery system,  
install one (such as a WATCO A-1) before venting  
the FreonTM . Leave the valve in place after  
servicing the system.  
3. Disconnect the 3 leads from the compressor.  
4. After purging the unit completely, unbrace the suc-  
tion and discharge tubes at the compressor con-  
nections.  
5. Remove the 3 nuts and the 3 washers which fas-  
ten the compressor.  
6. Remove the compressor. (See Figure 26)  
7. Re-instill the components by referring to the  
removal procedure, above.  
Figure 26  
17 Room Air Conditioner  
Disassembly  
9. Capacitor  
1. Remove the control box. (Refer to section 19)  
2. Remove the knobs and the screw that fasten  
control panel from control box.  
3. Remove the screw that located in the front.  
4. Open the bottom side of control box.  
5. Remove the screw and the clamp that fastens  
the capacitor.  
6. Disconnect all the leads of capacitor terminals.  
7. Re-install the components by referring to the  
removal procedure, above. (See Figure 27)  
Figure 27  
10. Power Cord  
1. Remove the control box. (Refer to section 19)  
2. Open the control box. (Refer to section 25)  
3. Disconnect the grounding screw from the control  
box.  
4. Disconnect the 2 receptacles.  
5. Remove a screw which fastens the clip cord.  
(See Figure 28)  
6. Remove the power cord.  
7. Re-install the component by referring to the  
above removal procedure, above.  
Figure 28  
(Use only one ground-marked hole  
connection.)  
for ground  
8. If the supply cord of this appliance is damaged, it  
must be replaced by the special cord. (The  
special cord means the cord that has the same  
specification marked on the supply cord attached  
at the unit.)  
11. Thermistor  
1. Remove the control box. (Refer to section 19)  
2. Unfold the control box. (Refer to section 25)  
3. Disconnect the themistor terminals from main  
P.W.B Assembly.  
Figure 29  
4. Remove the thermistor.  
6. Re-install the components by refereing to the  
above removal procedure above. (See Figure 29)  
12. Synchronous Motor  
1. Remove the control box. (Refer to section 19)  
2. Unfold the control box. (Refer to section 25)  
3. Remove the crankshaft.  
4. Disconnect all the leads of the synchronous  
motor.  
5. Remove the 2 screws which fasten the syn-  
chronous motor. (See Figure. 30)  
6. Re-install the components by referring to the  
above removal procedure above.  
Figure 30  
Service Manual 18  
Disassembly  
Refrigerating Cycle  
CAUTION: Discharge the refrigerant  
system using a FreonTM Recovery  
System. If there is no valve to attach the  
recovery system, install one (such as a  
WATCO A-1) before venting the FreonTM.  
Leave the valve in place after servicing  
the system.  
13. Condenser  
1. Remove the cabinet. (Refer to section 18)  
2. Remove the 4 screws that fasten the brace.(Refer  
to section 20)  
3. Remove the 5 screws that fasten the condenser  
and shroud.  
4. After discharging the refrigerant completely,  
unbraze the interconnecting tube at the condenser  
connections.  
5. Remove the condenser.  
6. Re-install the component by referring to notes.  
(See Figure 31)  
Figure 31  
14. Evaporator  
1. Remove the cabinet. (Refer to section 18)  
2. Remove the 2 screws that fasten the evaporator.  
3. Move the evaporator sideways carefully.  
(Refer to section 20)  
4. After discharging the refrigerant completely,  
unbraze the interconnecting tube at the evaporator  
connections.  
5. Remove the evaporator.  
6. Re-install the component by referring to notes.  
(See Figure 32)  
15. Capillary Tube  
1. Remove the cabinet. (Refer to section 18)  
2. After discharging the refrigerant completely,  
unbraze the interconnecting tube at the capillary  
tube.(See caution above)  
3. Remove the capillary tube.  
4. Re-install the component by referring to notes.  
Figure 32  
19 Room Air Conditioner  
Disassembly  
NOTICE  
Replacement of the refrigeration cycle.  
6. Recharge as follows :  
1. When replacing the refrigeration cycle, be sure to  
TM  
Discharge the refrigerant system using a Freon  
recovery System.  
1) Refrigeration cycle systems are charged from the  
High-side. If the total charge cannot be put  
in the High-side, the balance will be put in the  
suction line through the access valve which you  
installed as the system was opened.  
2) Connect the charging cylinder as shown in figure  
33B.  
If there is no valve to attach the recovery system,  
install one (such as a WATCO A-1) before venting  
TM  
the Freon . Leave the valve in place after  
servicing the system.  
2. After discharging the unit completely, remove the  
desired component, and unbraze the pinch-off  
tubes.  
With valve C open, discharge the hose at the mani-  
fold connection.  
3. Braze service valves into the pinch-off tube ports,  
leaving the valves open.  
4. Braze the pinch-off tubes with Service valves.  
3) Open valve A and allow the proper charge to  
enter the system. Valve B is still closed.  
4) If more charge is required, the high-side will not  
take it. Close valve A.  
5. Evacuate as follows.  
1) Connect the vacuum pump, as illustrated figure  
33A.  
5) With the unit running, open valve B and add the  
balance of the charge.  
2) Start the vacuum pump, slowly open manifold  
valves A and B with two full turns counterclockwise  
and leave the valves open.  
a. Do not add the liquid refrigerant to the Low-  
side.  
b. Watch the Low-side gauge; allow pressure to  
rise to 30 lbs (0.2Mp).  
c. Turn off valve B and allow pressure to drop.  
d. Repeat steps b. and c. until the balance of the  
charge is in the system.  
The vacuum pump is now pulling through valves  
A and B up to valve C by means of the manifold  
and entire system.  
CAUTION: If high vacuum equip-  
ment is used, just crack valves A  
and B for a few minutes, then open slowly  
with the two full turns counterclockwise.  
This will keep oil from foaming and being  
drawn into the vacuum pump.  
6) When satisfied the unit is operating correctly,  
use the pinch-off tool with the unit still running  
and clamp on to the pinch-off tube. Using a tube  
cutter, cut the pinch-off tube about 2 inches from  
the pinch-off tool. Use sil-fos brazing rod and braze  
pinch-off tube closed. Turn off the unit, allow it to  
set for a while, and then test the leakage of the  
pinch-off connection.  
3) Operate the vacuum pump vaccum for 20 to 30  
minutes, until 600 microns of vaccum is obtained.  
Close valves A and B, and observe vacuum gauge  
for a few minutes. A rise in pressure would indi-  
cate a possible leak or moisture remaining in the  
system. With valves A and B closed, stop the vac-  
uum pump.  
4) Remove the hose from the vacuum pump and  
place it on the charging cylinder. See figure 33B.  
Open valve C.  
Discharge the line at the manifold connection.  
5) The system is now ready for final charging.  
Service Manual 20  
Disassembly  
Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pin-off tool capable  
of making a leak-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.  
COMPOUND GAUGE  
CONDENSER  
(HIGH PRESSURE SIDE)  
MANIFOLD  
GAUGE  
A
B
CAPILLARY TUBE  
SEE INSETS  
BELOW  
EVAPORATOR  
(LOW PRESSURE SIDE)  
COMPRESSOR  
HI  
LOW  
A
A
B
B
EXTERNAL  
VACUUM PUMP  
CHARGING  
CYLINDER  
C
Figure 33B-Charging  
Figure 33A-Pulling Vacuum  
21 Room Air Conditioner  
Schematic Diagram  
Schematic Diagram  
Electronic Control Device  
S E G - d  
S E G - e  
S E G - f  
S E G - g  
T E S T  
/ R e s e t  
O s c i n  
V D D  
O s c o u t  
V S S  
S L I D E S W  
V A r e f  
K E Y 0  
K E Y 1  
R o o m T H  
P i p e T H  
O p t i o n 1  
O p t i o n 2  
L E D o u t 0  
L E D o u t 1  
L E D o u t 2  
Service Manual 22  
Schematic Diagram  
Wiring Diagram  
• MODEL : RAD-183A and RAD-243A  
POWER INPUT  
WH(BL)  
(Ribbed)  
BK(BR)  
(Plain)  
GN/YL(GN)  
THERMISTOR  
CN-TH1  
BK  
BK  
BL  
BL  
RD  
OR(BR)  
YL  
RD  
OR(BR)  
YL  
MOTOR  
GN/YL  
(GN)  
CAPACITOR  
F
C
OR(BR)  
BK  
RD  
SYNC  
MOTOR  
BK  
RD  
BR  
BR  
H
PTC  
RY-SYNC  
ZNR  
BK  
RD  
BL  
R
S
C
RY-COMP  
COMP.  
4
3
TRANS  
FORMER  
BL  
FUSE 250V/T2A  
OLP  
(115V/T2A)  
3854AR2330P  
WIRING DIAGRAM  
23 Room Air Conditioner  
Schematic Diagram  
Components Location  
Main P.W.B Assembly  
Display P.W.B Assembly  
Service Manual 24  
Troubleshooting Guide  
Troubleshooting Guide  
Piping System  
CONDENSER COIL  
FAN  
CAPILLARY TUBE  
COMPRESSOR  
MOTOR  
BLOWER  
EVAPORATOR COIL  
Figure 34 is a brief description of the important components and their function in what is called the refrigeration  
system. This will help you to understand the refrigeration cycle and the flow of the refrigerant in the cooling cycle.  
ROOM AIR CONITIONER  
CYCLE OF REFRIGERATION  
EVAPORATOR COILS  
CONDENSER COILS  
VAPOR INLET  
SUCTION LINE  
COOL LOW PRESSURE VAPOR  
HOT  
DISCHARGED  
AIR  
COMPLETE LIQUID  
BOIL OFF POINT  
COOLED  
AIR  
ROOM AIR HEAT LOAD  
OUTSIDE COOLING  
AIR FOR REFRIGERANT  
PASS THROUGH  
MOTOR  
COMPRESSOR  
OIL  
LIQUID  
PRESSURE  
DROP  
LIQUID OUTLET  
HIGH PRESSURE VAPOR  
(LIQUID REFRIGERANT)  
LIQUID REFRIGERANT  
LOW PRESSURE VAPOR  
CAPILLARY TUBE  
Figure 34  
25 Room Air Conditioner  
Troubleshooting Guide  
Troubleshooting Guide  
In general, possible trouble is classified in two kinds.  
The one is called Starting Failure which is caused from an electrical defect, and the other is ineffective Air  
Conditioning caused by a defect in the refrigeration circuit and improper application.  
Unit runs but poor cooling.  
Ineffective Cooling  
Check cold air circulation  
for smooth flow.  
Check outdoor coil  
(heat exchanger) & the fan  
operation.  
Check heat load  
increase.  
Dirty indoor coil  
(Heat exchanger)  
Unexpected residue  
Overloaded circuit  
Check gas leakage.  
Repair gas leak.  
Malfunction of fan  
Clogged of air filter.  
Check inside gas  
pressure.  
Replacement of unit if the  
unit is beyond repair.  
Obstruction at air outlet  
Stop of auto air-swing  
Correct above trouble  
Adjusting of refrigerant  
charged.  
Malfunction of compressor.  
Check clogging in refrigera-  
tion circuit.  
Replacement of  
compressor.  
Satisfactory operation with  
temperature difference of  
inlet & outlet air ;  
Repair clogging in refrigera-  
tion circuit.  
44~50°F(7~10°C)  
Service Manual 26  
Troubleshooting Guide  
Fails to Start  
Check of power source.  
Check circuit breaker  
and fuse.  
Check of control switch  
setting.  
Gas leakage of feeler bulb  
of thermostat  
Check of control switch.  
Compressor only fails to  
start.  
Fan only fails to start.  
Improper wiring.  
Drop of power voltage.  
Improper thermostat setting.  
Defect of fan motor  
capacitor.  
Defect of compressor  
capacitor.  
Loose terminal connection.  
Improper wiring.  
Irregular motor resistance  
(
).  
Irregular motor insulation  
).  
Capacitor check.  
Replacement  
(
Replacement of fan motor.  
Regular but fails to start.  
Irregular motor resistance (  
Irregular motor insulation (  
)
)
Replacement of compressor  
(locking of rotor, metal).  
Replacement of compressor  
(Motor damaged)  
27 Room Air Conditioner  
Troubleshooting Guide  
Electrical Parts Troubleshooting Guide  
Possible Trouble 1 The unit does not operate.  
NO  
Check the Fuse.  
Check the wiring diagram.  
Is the Trans output power  
AC 220V?  
YES  
NO  
NO  
Check the Main  
PCB pattern.  
Is the Trans output power  
Is shorted the Trans. output?  
YES  
about AC 14V?  
YES  
Exchange the Trans.  
Exchange D02D~D05D.  
Exchange IC01D.  
NO  
NO  
Is output Voltage of IC01D  
DC 12V?  
YES  
Exchange IC02D.  
Is output Voltage of IC02D  
DC 5V?  
YES  
NO  
NO  
Is the reset circuit all right?  
(The No.16 of  
Exchange IC01A, C02A.  
Micom is 5V.)  
YES  
Is the  
Connect connector  
exactly.  
connection between  
Main and Display  
all right?  
YES  
NO  
Check the PCB  
pattern.  
Is the voltage No.20 of Micom  
DC 5V?  
YES  
Exchange Main PCB Ass'y.  
Service Manual 28  
Troubleshooting Guide  
Possible Trouble 2 The compressor does not operate.  
Is setting  
NO  
Select the setting Temp. to lower Number.  
Temp. set lower than Room  
Temp.-0.5°C?  
YES  
NO  
NO  
NO  
Is the voltage No.10  
of IC01M 0V?  
Is the voltage N0.7 of  
Is the Unit for 3 minutes  
delay?  
IC01M DC 5V?  
YES  
YES  
YES  
Check the RY-COMP.  
Check the wiring  
Diagram.  
Exchange IC01M.  
Wait 3 Minutes.  
Exchange MAIN  
PCB Ass'y.  
Possible Trouble 3 The compressor always operate.  
Connect LEAD Wire to  
RY-COMP again.  
NO  
Is the wire connection of  
RY-COMP all right?  
YES  
Check the RY-COMP.  
29 Room Air Conditioner  
Troubleshooting Guide  
Exchange IC01M.  
Possible Trouble 4 FAN does not operate.  
NO  
Is the voltage NO.1 or 4  
of IC01M DC 5V?  
YES  
NO  
Is the voltage NO.13 or 16  
Exchange IC01M.  
of IC01M 0V?  
YES  
Check the RY-Hi or  
RY-Lo.  
Check the wiring diagram.  
Possible Trouble 5 Auto Swing does not operate.  
NO  
NO  
Is the voltage NO.6  
of IC01M DC 5V?  
Exchange Micom.  
Exchange IC01M.  
YES  
Is the voltage NO.11  
of IC01M 0V?  
YES  
Check the RY-SYNC.  
Check the connectionn  
of CN-SYNC.  
Check the PCB pattern.  
Service Manual 30  
Troubleshooting Guide  
Possible Trouble 6 Remote controller does not operate.  
NO  
Is the voltage of Battery  
about over 2.3V?  
Exchange the battery.  
Check the PCB pattern.  
YES  
Is the voltage No.16  
of CN-DISP on Main PCB  
Ass'y DC 5V?  
NO  
YES  
Connect connector to  
CN-DISP exactly.  
NO  
Is the connection of  
CN-DISP all right?  
YES  
Exchange Receiver Ass'y.  
Possible Trouble 7 It displays abnormally on display PCB Ass'y.  
NO  
Exchange IC01G.  
Is the IC01G all right?  
YES  
NO  
Connect connector  
to CN-DISP exactly.  
NO  
NO  
Is the connection of  
CN-DISP all right?  
YES  
Does the  
Q01G~Q04G operate normally  
on main PCB Ass'y?  
Exchange  
Q01G-Q04G.  
YES  
Exchange the display  
PCB Ass'y.  
31 Room Air Conditioner  
Troubleshooting Guide  
Room Air Conditioner Voltage Limits  
NAME PLATE RATING  
208~230±10%  
115±10%  
MINIMUM  
187V  
MAXIMUM  
253V  
104V  
126V  
COMPLAINT  
CAUSE  
REMEDY  
Fan motor will not run.  
No power  
Check voltage at outlet. Correct if necessary.  
Power supply cord  
Check voltage to rotary switch. If none, check power  
supply cord. Replace cord if circuit is open.  
Rotary switch  
Check switch continuity. Refer to wiring diagram for  
terminal identification. Replace switch if defective.  
Wire disconnected or con-  
nection loose  
Connect wire. Refer to wiring diagram for terminal  
identification. Repair or replace loose terminal.  
Capacitor (Discharge  
capacitor before testing.)  
Test capacitor.  
Replace if not within ±10% of manufacturer's rating.  
Replace if shorted, open, or damaged.  
Will not rotate  
Fan blade hitting shroud or blower wheel hitting  
scroll. Realign assembly.  
Units using slinger ring for condenser fan must have  
1/4 to 5/16 inch clearance to the base. If it hits the  
base, shim up the bottom of the fan motor with  
mounting screw(s).  
Check fan motor bearings; if motor shaft will not  
rotate, replace the motor.  
Revolves on overload.  
Check voltage. If not within limits, call an electrician.  
Fan motor runs  
intermittently  
Test capacitor.  
Check bearings. Does the fan blade rotate freely?  
If not, replace fan motor.  
Pay attention to any change from high speed to  
low speed. If the speed does not change, replace the  
motor.  
Fan  
If cracked, out of balance, or partially missing,  
replace it.  
Fan motor noise.  
Turbo  
If cracked, out of balance, or partially missing,  
replace it.  
Loose clamper  
Worn bearings  
Tighten it.  
If knocking sounds continue when running or loose,  
replace the motor. If the motor hums or noise  
appears to be internal while running, replace motor.  
Check voltage.  
If not within limits, call an electrician.  
Compressor will not run,  
but fan motor runs.  
Voltage  
Wiring  
Check the wire connections, if loose, repair or  
replace the terminal. If wires are off, refer to wiring  
diagram for identification, and replace. Check wire  
locations. If not per wiring diagram, correct.  
Check for continuity, refer to the wiring diagram for  
terminal identification. Replace the switch if circuit is  
open.  
Rotary  
Service Manual 32  
Troubleshooting Guide  
COMPLAINT  
CAUSE  
Thermostat  
REMEDY  
Compressor will not run,  
but fan motor runs.  
Check the position of knob If not at the coldest set-  
ting, advance the knob to this setting and restart  
unit.  
Check continuity of the thermostat. Replace ther-  
mostat if circuit is open.  
Thermistor  
Check the TEMP control. If not at the lowest num-  
ber, set TEMP control to this setting and restart  
the unit. Check the continuity of the thermistor.  
Replace the thermistor if the circuit is open.  
Check the capacitor.  
Capacitor (Discharge  
Replace if not within ±10% of manufacturers rat-  
ing. Replace if shorted, open, or damaged.  
capacitor before servicing.)  
Check the compressor for open circuit or ground. If  
open or grounded, replace the compressor.  
Compressor  
Overload  
Check the compressor overload, if externally  
mounted. Replace if open. (If the compressor tem-  
perature is high, remove the overload, cool it, and  
retest.)  
Compressor cycles on  
overload.  
Check the voltage.  
If not within limits, call an electrician.  
Voltage  
Check overload, if externally mounted.  
Overload  
Replace if open. (If the compressor temperature is  
high, remove the overload, cool, and retest.)  
If not running, determine the cause. Replace if  
required.  
Compressor cycles on  
overload.  
Fan motor  
Remove the cabinet. inspect the interior surface of  
the condenser; if restricted, clean carefully with a  
vacuum cleaner (do not damage fins) or brush.  
Clean the interior base before reassembling.  
Condenser air flow restric-  
tion  
If condenser fins are closed over a large area on  
the coil surface, head pressures will increase,  
causing the compressor to overload. Straighten  
the fins or replace the coil.  
Condenser fins (damaged)  
Test capacitor.  
Capacitor  
Compressor cycles on  
overload.  
Check the terminals. If loose, repair or replace.  
Check the system for a restriction.  
If restricted, clean of replace.  
Close if open.  
Wiring  
Refrigerating system  
Air filter  
Insufficient cooling or heat-  
ing  
Exhaust damper door  
Unit undersized  
Determine if the unit is properly sized for the area  
to be cooled.  
Excessive noise  
Check the set screw or clamp. If loose or missing,  
correct. If the turbo or fan is hitting air guide,  
rearrange the air handling parts.  
Turbo or fan  
Remove the cabinet carefully and rearrange tubing  
not to contact cabinet, compressor, shroud, and  
barrier.  
Copper tubing  
33 Room Air Conditioner  
Troubleshooting Guide  
REMEDY  
COMPLAINT  
CAUSE  
Capacitor  
Wiring  
Compressor cycles  
on overload.  
Test capacitor.  
Check the terminals. If loose, repair or replace.  
Check the system for a restriction.  
If restricted, clean of replace.  
Refrigerating system  
Air filter  
Insufficient cooling or heat-  
ing  
Exhaust damper door  
Unit undersized  
Close if open.  
Determine if the unit is properly sized for the area to  
be cooled.  
Turbo or fan  
Check the set screw or clamp. If loose or missing,  
correct. If the blower or fan is hitting air guide,  
rearrange the air handling parts.  
Excessive noise.  
Copper tubing  
Rotary switch.  
Remove the cabinet and carefully rearrange tubing  
not to contact cabinet, compressor, shroud, and bar-  
rier.  
Set the knob to HIGH COOL or LOW COOL while  
rocker switch is ON.  
Auto air-swing fails.  
Wiring  
Check terminals. If loose, repair or replace.  
Check the synchronous motor for open circuit.  
Synchronous motor.  
Service Manual 34  
Exploded View  
Exploded View  
Cooling Model  
554031  
148000  
130910  
W48602  
559011  
149980  
749750  
349600  
130410  
346811  
554160  
550140  
359012  
349480  
354210  
325115-1  
325115-2  
147582  
349001  
W48602  
552111  
267110  
352113  
552113  
249950  
W0CZZ  
135312  
567480  
35211A  
159830  
249950  
135314  
268711-1  
269310  
146812  
137215  
238310  
135510  
W0CZZ  
137215  
146812  
135500  
266002  
147581-2  
266003  
149410  
268711-2  
147581-1  
264100  
264110  
35 Room Air Conditioner  
Replacement Parts List  
RAD-183A  
LocNo  
P/NO  
REMARK  
DESCRIPTION  
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
130410  
130910  
135312  
135314  
135510  
146812  
147581-1  
147581-2  
147582  
148000  
149980  
159830  
137215  
238310  
249950  
567480  
264100  
267110  
268711-1  
268711-2  
346811  
349001  
349480  
349600  
552113  
352113  
35211A  
749750  
354210  
359012  
552111  
554031  
554160  
559011  
W0CZZ  
W48602  
325115-1  
325115-2  
550140  
3041A30001H  
3091AR6056P  
AEB30969401  
3530AR1604A  
3551A30001A  
2H01102J  
BASEASSEMBLY,SINGLE  
CABINETASSY,SINGLE  
Grille,ASSY,Front(SINGLE)  
Grille,ASSY,INLET  
COVER,CONTROL(INDOOR)  
MotorAssembly,SYNC  
LOUVER,HORIZONTAL  
LOUVER,HORIZONTAL  
LOUVER,VERTICAL  
4758AR7264A  
4758AR7278A  
4758AR6157A  
4800AR7271A  
4998AR1597B  
5231AR6159A  
3720AR6163A  
3831A20032L  
4995A20613Y  
6323A20003S  
6411A20056P  
6711A20035A  
6871A20611A  
6871A10193N  
4681A20081T  
4900AR7265A  
4948A20016A  
4960AR1596A  
5211AR7059A  
BRACE  
SHROUD  
FILTERASSY,A/C  
PANEL,CONTROL  
ESCUTCHEON  
CONTROLBOXASSEMBLY,SINGLE  
Thermistor ASSEMBLY  
POWER CORD ASSEMBLY  
REMOTECONTROLLER  
PWB(PCB) ASSEMBLY,DISPLAY  
PWB(PCB) ASSEMBLY,MAIN  
MOTOR ASSEMBLY,SINGLE  
DAMPER,VENTILAYION  
ORIFICE  
MOUNT,MOTOR  
TUBE ASSEMBLY,CONDENSER OUT  
5211A25040B TUBE ASSEMBLY,DISCHARGER SINGLE  
5211A10247P  
5239A20001W  
5421A20248G  
5900A20027A  
5210A24956H  
5403A20062F  
2520UCBJ002  
5900AR1508B  
0CF1042856A  
3H02932C  
TUBE ASSEMBLY,SUCTIONSINGLE  
AIR GUIDE ASSEMBLY  
EVAPORATOR ASSEMBLY,FIRST  
FAN,TURBO  
Tube,BENDING  
CONDENSER ASSEMBLY,BEND  
COMPRESSOR  
FANASSEMBLY,AXIAL  
CAPACITOR  
CLAMP,SPRING  
5210A21083B  
5210A21083C  
4H00982C  
TUBE,EVAPORATOR  
TUBE,EVAPORATOR  
ISOLATOR, COMP  
Replacement Parts List  
RAD-243A  
LocNo  
P/NO  
REMARK  
DESCRIPTION  
130410  
130910  
135312  
135314  
135510  
146812  
147581-1  
147581-2  
147582  
148000  
149980  
159830  
137215  
238310  
249950  
567480  
264100  
267110  
268711-1  
268711-2  
346811  
349001  
349480  
349600  
552113  
352113  
35211A  
749750  
354210  
359012  
552111  
554031  
554160  
559011  
W0CZZ  
W48602  
325115-1  
325115-2  
550140  
3041A30001F  
3091AR6056P  
AEB30969401  
3530AR1604A  
3550AR7046D  
2H01102J  
BASE ASSEMBLY,SINGLE  
CABINET ASSY,SINGLE  
Grille ASSY,Front(SINGLE)  
Grille ASSY,INLET  
COVER,CONTROL(INDOOR)  
Motor Assembly,SYNC  
LOUVER,HORIZONTAL  
LOUVER,HORIZONTAL  
LOUVER,VERTICAL  
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
4758AR7264A  
4758AR7278A  
4758AR6157A  
4800AR7271A  
4998AR1597B  
5231AR6159A  
3720AR6163A  
3831A20032L  
ABQ32895801  
6323A20003S  
6411A20056Q  
6711A20035A  
6871A20611A  
6871A10193N  
4681A20081W  
4900AR7265A  
4948A20016A  
4960AR1596A  
5211AR7059E  
BRACE  
SHROUD  
FILTER ASSY,A/C  
PANEL,CONTROL  
ESCUTCHEON  
CONTROL BOX ASSEMBLY,SINGLE  
Thermistor ASSEMBLY  
POWER CORD ASSEMBLY  
REMOTE CONTROLLER  
PWB(PCB) ASSEMBLY,DISPLAY  
PWB(PCB) ASSEMBLY,MAIN  
MOTOR ASSEMBLY,SINGLE  
DAMPER,VENTILAYION  
ORIFICE  
MOUNT,MOTOR  
TUBE ASSEMBLY,CONDENSER OUT  
5211A21526J TUBE ASSEMBLY,DISCHARGER SINGLE  
5211A10094P  
5239A20001W  
5421A20248F  
5900A20027A  
5210A24956J  
5403A20062F  
5416A20045B  
5900AR1508B  
0CF1042856A  
3H02932C  
TUBE ASSEMBLY,SUCTION SINGLE  
AIR GUIDE ASSEMBLY  
EVAPORATOR ASSEMBLY,FIRST  
FAN,TURBO  
Tube,BENDING  
CONDENSER ASSEMBLY,BEND  
COMPRESSOR  
FAN ASSEMBLY,AXIAL  
CAPACITOR  
CLAMP,SPRING  
5210A30144U  
5210A30144V  
4022A30008A  
TUBE,EVAPORATOR  
TUBE,EVAPORATOR  
ISOLATOR, COMP  
6SHFLILFDWLRQVꢀDQGꢀSHUIRUPDQFHꢀGDWDꢀVXEMHFWꢀWRꢀFKDQJHꢀZLWKRXWꢀQRWLFHꢁ  
+($7ꢀ&21752//(5ꢁꢀ,1&ꢂ  
ꢀꢁꢂꢂꢃ:(//:257+ꢃ$9(18(ꢃ‡ꢃ-$&.621ꢄꢃ0,&+,*$1ꢃꢅꢁꢆꢂꢇ  
7+(ꢃ48$/,7<ꢃ/($'(5ꢃ,1ꢃ&21',7,21,1*ꢃ$,5  
04/18/07  

Agilent Technologies 6834B User Manual
Briggs Stratton 25100 User Manual
Briggs Stratton SNOW 150000 User Manual
Carrier CPLPCONV006A00 User Manual
Friedrich WALLMASTER SUBBASE WY User Manual
Fujitsu Air Conditioner AOU9RL2 User Manual
Hand Held Products HANDHELD 3800G User Manual
Harbor Freight Tools 2 Ton Compact Floor Jack 68783 User Manual
HP Hewlett Packard M475 User Manual
HP Hewlett Packard Officejet J4580 User Manual