Heat Controller Inc Air Conditioner DMH18DB 1 User Manual

HEAT CONTROLLER, INC.  
Wall Mounted  
Multi-Split System  
Air Conditioning/Heat Pump  
DMH18DB-1  
Before servicing the unit, read the  
“safety precautions” in this manual.  
Only for authorized service personnel.  
Combination table  
Combination table  
Cooling  
Heating  
Combination of Indoor Unit(kBtu/h)  
Operation  
Each Capacity  
Total Capacity  
Each Capacity  
Total Capacity  
Unit-A  
9
Unit-B  
Total  
9
UNIT-A(Btu/h) UNIT-B(Btu/h)  
Btu/h  
9000  
kW  
UNIT-A(Btu/h) UNIT-B(Btu/h)  
Btu/h  
9000  
kW  
9000  
9000  
-
2.63  
5.27  
9000  
9000  
-
2.63  
1 Unit  
2 Unit  
9
9
18  
9000  
18000  
9000  
18000  
5.27  
Notes :  
1.Cooling Capacity is based on : indoor temp. 26.7°C(80.1°F)DB, 19.4°C(66.9°F)WB; outdoor temp. 35°C(95°F)DB, 23.9°C(75°F)WB  
2.Heating Capacity is based on : indoor temp. 21.1°C(70°F)DB, 15.6°C(60.1°F)WB; outdoor temp. 8.3°C(46.9°F)DB, 6.1°C(43°F)WB  
3.The total ability of connected a indoor unit is up to 18k Btu/h  
Symbols Used in this Manual  
This symbol alerts you to the risk of electric shock.  
This symbol alerts you to hazards that could cause harm to the  
air conditioner.  
NOTICE  
This symbol indicates special notes.  
Service Manual 3  
Safety Precautions  
Safety Precautions  
To prevent injury to the user or other people and property damage, the following instructions must  
be followed.  
I Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is  
classified by the following indications.  
This symbol indicates the possibility of death or serious injury.  
WARNING  
CAUTION This symbol indicates the possibility of injury or damage to properties only.  
I Meanings of symbols used in this manual are as shown below.  
Be sure not to do.  
Be sure to follow the instruction.  
WARNING  
I Installation  
Do not use a defective or under-  
rated circuit breaker. Use this  
appliance on a dedicated circuit.  
For electrical work, contact the  
dealer, seller, a qualified electrician,  
or an Authorized Service Center  
Always ground the product.  
.
• There is risk of fire or electric  
shock.  
• Do not disassemble or repair the  
product. There is risk of fire or  
electric shock.  
• There is risk of fire or electric  
shock.  
Install the panel and the cover  
of control box securely.  
Always install a dedicated cir-  
cuit and breaker.  
Use the correctly rated break-  
er or fuse.  
• There is risk of fire or electric  
shock.  
• Improper wiring or installation may • There is risk of fire or electric  
cause fire or electric shock shock.  
4 Multi type Air Conditioner  
Safety Precautions  
Do not install, remove, or re-  
install the unit by yourself  
(customer).  
Be cautious when unpacking  
and installing the product.  
For installation, always con-  
tact the dealer or an  
Authorized Service Center.  
• There is risk of fire, electric shock, • Sharp edges could cause injury.  
• There is risk of fire, electric shock,  
explosion, or injury.  
explosion, or injury.  
Be especially careful of the case  
edges and the fins on the con-  
denser and evaporator.  
Do not install the product on a Be sure the installation area  
Do not let the air conditioner  
run for a long time when the  
humidity is very high and a  
door or a window is left open.  
defective installation stand.  
does not deteriorate with age.  
• It may cause injury, accident, or  
damage to the product.  
• If the base collapses, the air condi- • Moisture may condense and wet or  
tioner could fall with it, causing  
property damage, product failure,  
and personal injury.  
damage furniture.  
Do not allow water to run into  
electric parts.  
Do not store or use flammable Do not use the product in a  
gas or combustibles near the  
product.  
tightly closed space for a long  
time.  
• It may cause There is risk of fire,  
failure of the product, or electric  
shock.  
• There is risk of fire or failure of  
product.  
• Oxygen deficiency could occur.  
Gasolin  
Service Manual 5  
Safety Precautions  
When flammable gas leaks,  
turn off the gas and open a  
window for ventilation before  
turn the product on.  
If strange sounds, or smoke  
comes from product. Turn the  
breaker off.  
Stop operation and close the  
window in storm or hurricane.  
If possible, remove the prod-  
uct from the window before  
the hurricane arrives.  
• Do not use the telephone or turn  
switches on or off. There is risk of  
explosion or fire  
• There is risk of electric shock or  
fire.  
• There is risk of property damage,  
failure of product, or electric shock.  
Do not open the inlet grill of the product  
during operation. (Do not touch the elec-  
trostatic filter, if the unit is so equipped.)  
When the product is soaked  
(flooded or submerged), contact not enter the product.  
an Authorized Service Center.  
Be cautious that water could  
• There is risk of physical injury,  
electric shock, or product failure.  
• There is risk of fire or electric  
shock.  
• There is risk of fire, electric shock,  
or product damage.  
Ventilate the product from time to time when  
operating it together with a stove, etc.  
Turn the main power off when cleaning or  
maintaining the product.  
• There is risk of fire or electric shock.  
• There is risk of electric shock.  
6 Multi type Air Conditioner  
Safety Precautions  
When the product is not to be used for a long time,  
disconnect the power by turning off the breaker.  
Take care to ensure that nobody could step on  
or fall onto the outdoor unit.  
• There is risk of product damage or failure, or unintend- • This could result in personal injury and product dam-  
ed operation.  
age.  
CAUTION  
I Installation  
Always check for gas (refrigerant) leak-  
age after installation or repair of product.  
Install the drain hose to ensure that  
water is drained away properly.  
Keep level even when  
installing the product.  
• Low refrigerant levels may cause  
failure of product.  
• A bad connection may cause water • To avoid vibration or water leak-  
leakage.  
age.  
90°  
Do not install the product  
where the noise or hot air  
from the outdoor unit could  
oftend neighbors.  
Use two or more people to lift  
and transport the product.  
Do not install the product  
where it will be exposed to  
sea wind (salt spray) directly.  
• It may cause a problem for your  
neighbors.  
• Avoid personal injury.  
• It may cause corrosion on the  
product. Corrosion, particularly on  
the condenser and evaporator fins,  
could cause product malfunction or  
inefficient operation.  
Service Manual 7  
Safety Precautions  
I Operational  
Do not expose the skin direct-  
ly to cool air for long periods  
of time.  
Do not use the product for  
special purposes, such as  
preserving foods, works of  
art, etc. It is a consumer air  
conditioner, not a precision  
refrigeration system.  
Do not block the inlet or outlet  
of air flow.  
(Don't sit in the draft.)  
This could harm to your health.  
There is risk of damage or loss of  
It may cause product failure.  
property.  
Use a soft cloth to clean. Do  
not use harsh detergents, sol-  
vents, etc.  
Do not touch the metal parts of Do not step on or put anyting  
the product when removing the on the product. (outdoor  
air filter. They are very sharp!  
units)  
There is risk of fire, electric shock, There is risk of personal injury.  
or damage to the plastic parts of  
There is risk of personal injury and  
failure of product.  
the product.  
Always insert the filter secure- Do not insert hands or other  
Do not drink the water drained  
ly. Clean the filter every two  
weeks or more often if neces-  
sary.  
objects through the air inlet or from the product.  
outlet while the product is  
operated.  
A dirty filter reduces the efficiency of There are sharp and moving parts It is not sanitary and could cause  
the air conditioner and could cause  
product malfunction or damage.  
that could cause personal injury.  
serious health issues.  
8 Multi type Air Conditioner  
Safety Precautions  
Use a firm stool or ladder when cleaning or  
maintaining the product.  
Replace the all batteries in the remote control  
with new ones of the same type. Do not mix  
old and new batteries or different types of bat-  
teries.  
Be careful and avoid personal injury.  
There is risk of fire or explosion  
Do not recharge or disassemble the batteries.  
Do not dispose of batteries in a fire.  
If the liquid from the batteries gets onto your  
skin or clothes, wash it well with clean water.  
Do not use the remote if the batteries have  
leaked.  
They may burn or explode.  
The chemicals in batteries could cause burns or other  
health hazards.  
Service Manual 9  
Dimensions  
Dimensions  
Indoor Unit  
Split Type Indoor  
H
D
W
Installation plate  
Model  
Split Type(S4)  
9 kBtu/h  
Dimension  
W
H
mm(in)  
mm(in)  
mm(in)  
870(34.2)  
270(10.6)  
153(6)  
D
10 Multi type Air Conditioner  
Dimensions  
Outdoor Unit  
W
L6  
L5  
L7  
MODEL  
UE  
18kBtu/h  
DIM  
W
mm(in)  
870(34.3)  
655(25.8)  
320(12.6)  
370(14.6)  
25(1.0)  
H
mm(in)  
mm(in)  
mm(in)  
mm(in)  
mm(in)  
mm(in)  
mm(in)  
mm(in)  
mm(in)  
D
L1  
L2  
L3  
L4  
L5  
L6  
L7  
775(30.5)  
25(1.0)  
546(21.5)  
160(6.3)  
160(6.3)  
Service Manual 11  
Product Specifications  
Product Specifications  
Outdoor Unit  
A-DMH18DB-1  
Nominal Capacity  
(Min~Rating~Max)  
Cooling  
kW  
Btu/h  
kW  
5.27  
18000  
5.27  
Heating  
Btu/h  
kW  
kW  
18000  
1.98  
1.96  
A2NH093GCA0  
Nominal Input  
(Min~Rating~Max)  
Testing Combination  
Cooling  
Heating  
Running Current(Rating) Cooling  
Heating  
A
A
8.8  
8.6  
Starting Current  
Cooling/Heating  
A
13  
Power Supply  
Ø / V / Hz  
1/208~230/60  
3*2.5  
Power Supply Cable(Outdoor)  
Power and Transmission Cable  
(Outdoor to Indoor or Outdoor to BD)  
Power and Transmission Cable(BD to Indoor)  
Dimensions  
Net Weight  
No. x mm2  
No. x mm2  
4*0.75  
No. x mm2  
mm(inch)  
kg(lbs)  
-
W x H x D  
870*655*320(34.3*25.8*12.6)  
60(132.2)  
Max. Number of Connectable Indoor Units  
2
Compressor (#1)  
Compressor (#2)  
Compressor (#3)  
Refrigerant  
Type  
Qty x Model  
Motor type  
Oil charge volume  
Oil Type  
Type  
Qty x Model  
Motor type  
Oil charge volume  
Oil type  
Type  
Qty x Model  
Motor type  
Rotary(Non Tropical)  
1*GK113KAA  
Induction Motor  
330  
FVC68D  
Rotary(Non Tropical)  
cc  
cc  
cc  
1*GK094KAA  
Induction Motor  
330  
FVC68D  
-
-
-
-
Oil charge volume  
Oil type  
Cycle A Charge (at 7.5m)  
Cycle B Charge (at 7.5m)  
Type  
-
g(oz)  
g(oz)  
1400(49)  
-
R410A  
Control  
EEV  
Additional Refrigerant Charge  
g/m(oz/ft)  
µF/Vac  
20(0.22)  
(2R X 28C X 18) X 1  
Reversing Cycle  
6/370  
Heat Exchanger  
(Rows x Column x FPI) x No.  
Defrosting Method  
Capacitor  
Fan  
Drive  
Direct Drive  
Side  
50(1765.7)  
51  
6.35(1/4)  
9.52(3/8)  
-
Discharge Direction(Side/Top)  
Air Flow Rate x No. of Fan  
Sound Pressure  
Liquid(Cycle A)  
Gas(Cycle A)  
Liquid(Cycle B)  
Gas(Cycle B)  
High Pressure Gas  
Total Piping  
CMM(cfm)  
dB(A)+3  
mm(inch)  
mm(inch)  
mm(inch)  
mm(inch)  
mm(inch)  
m(ft)  
m(ft)  
m(ft)  
m(ft)  
m(ft)  
Sound Level(H/L)  
Piping Connections  
-
-
Max. Interunit  
Piping Length  
30(98.4)  
15(49.2)  
-
Main Piping  
Total Branch Piping  
Each Branch Piping  
Outdoor Unit~Indoor Unit  
Indoor Unit~Indoor Unit  
Cooling  
7.5(24.6)  
7.5(24.6)  
7.5(24.6)  
21~43(69.8~109.4)  
-5~24(23~75.2)  
Max. Elevation  
Difference  
Operation Range  
(Outdoor)  
m(ft)  
˚C(˚F)  
˚C(˚F)  
Heating  
Note:  
1. Capacities are based on the following conditions:  
2. Wiring cable size must comply with the applicable local and national code.  
3. The specification may be subject to change without prior notice for purpose  
of improvement.  
Cooling:  
- Indoor Temperature 26.7˚C(80˚F) DB/19.4˚C(67˚F) WB  
- Outdoor Temperature 35˚C(95˚F) DB/23.9˚C(75˚F) WB  
- Indoor Temperature 21.1˚C(70˚F) DB/15.6˚C(60˚F) WB  
- Outdoor Temperature 8.3˚C(47˚F) DB/6.1˚C(43˚F) WB  
Heating:  
Piping Length - Interconnecting Piping Length 7.5m  
- Level Difference of Zero  
12 Multi type Air Conditioner  
Product Specifications  
Indoor Unit  
B-DMH18DB-1  
Power Supply  
Cooling Capacity  
Ø / V / Hz  
kW  
1/208~230/60  
2.63  
Btu/h  
kW  
9000  
2.63  
Heating Capacity  
Btu/h  
A
9000  
0.5  
BLDC  
Current  
Fan  
Nominal Running Current  
Motor Type  
Fan Type  
Cross Flow fan  
Motor Output(W) x No. of Unit  
Air Flow Rate  
(H / M / L)  
15*1  
7
247.1  
CMM  
cfm  
External Static Pressure  
Capacitor  
mmAq  
µF / Vac  
-
-
Drive  
Row x Column x FPI  
Direct drive  
2*15*20  
Coil  
Dimensions (W x H x D) Body  
Decorative Panel  
Body  
mm(inch)  
mm(inch)  
kg (lbs)  
870*270*153(34.2*10.6*6)  
-
7(15.4)  
Net Weight  
Decorative Panel  
kg (lbs)  
-
Air Filter  
Sound Level (H / M / L)  
Piping Connections  
Long life filter  
31/27/21  
6.35(1/4)  
9.52(3/8)  
20/13  
dB(A)+3  
mm (inch)  
mm (inch)  
mm  
Liquid  
Gas  
Drain(OD/ID)  
Dehumidification Rate  
Safety Devices  
l/h  
1.2  
Fuse  
Temperature Sensor  
Referigerant  
Referigerant Control  
Connectable Outdoor Unit  
Thermistor  
R-410A  
EEV(Outdoor Unit)  
Multi  
Power and Transmission Interunit Cable  
No. x mm2  
4*0.75  
Note:  
1. Capacities are based on the following conditions:  
Cooling:  
- Indoor Temperature 26.7˚C(80˚F) DB/19.4˚C(67˚F) WB  
- Outdoor Temperature 35˚C(95˚F) DB/23.9˚C(75˚F) WB  
- Indoor Temperature 21.1˚C(70˚F) DB/15.6˚C(60˚F) WB  
- Outdoor Temperature 8.3˚C(47˚F) DB/6.1˚C(43˚F) WB  
Heating:  
Piping Length - Interconnecting Piping Length 7.5m  
- Level Difference of Zero  
2. Wiring cable size must comply with the applicable local and national code.  
3. The specification may be subject to change without prior notice for purpose of improvement.  
Service Manual 13  
Installation  
Installation  
Read carefully, and then follow step by step.  
Installation Parts  
Installation plate  
Type "A" screw and plastic anchor  
Remote Control Holder  
Type "B" screw  
Installation Tools  
Figure  
Name  
Figure  
Name  
Screw driver  
Electric Drill  
Ohmmeter  
Hexagonal wrench  
Measuring Tape, Knife  
Hole Core Drill  
Ammeter  
Gas Leak Detector  
Thermometer,  
Level  
Spanner  
Torque wrench  
Flaring Tool Set  
14 Multi type Air Conditioner  
Installation  
Select the best location  
Indoor unit  
1. Do not have any heat or steam near the unit.  
More than 30cm  
(11.8 inch)  
2. Select a place where there are no obstacles in front  
of the unit.  
More than 20cm  
(7.9 inch)  
3. Make sure that condensation drainage can be conve-  
niently routed away.  
4. Do not install near a doorway.  
5. Ensure the spaces indicated by arrows from the wall,  
ceiling, fence or other obstacles.  
More than 30cm  
(11.8 inch)  
6. Use a stud finder to locate studs to prevent unneces-  
sary damage to the wall.  
Outdoor unit  
1. If an awning is built over the unit to prevent direct  
sunlight or rain exposure, make sure that heat radia-  
tion from the condenser is not restricted.  
more than 20cm  
(7.9 inch)  
2. Ensure that the spaces indicated by arrows around  
front, back and side of the unit.  
more than 20cm  
(7.9 inch)  
3. Do not place animals and plants in the path of the  
warm air.  
4. Take the air conditioner weight into account and  
select a place where noise and vibration are mini-  
mum.  
more than 70cm  
(27.6 inch)  
more than 60cm  
(23.6 inch)  
5. Select a place so that the warm air and sound from  
the air conditioner do not disturb neighbors.  
Rooftop Installations:  
If the outdoor unit is installed on a roof structure, be  
sure to level the unit. Ensure the roof structure and  
anchoring method are adequate for the unit location.  
Consult local codes regarding rooftop mounting.  
Service Manual 15  
Installation  
Piping length and elevation  
Multi Piping Type  
Max Elevation  
between each  
indoor unit and out-  
door unit (h1)  
Max elevation  
between indoor  
units (h2)  
Max total length of Max length of each Min length of each  
Capacity(Btu/h)  
18k  
all pipes (A+B)  
pipe (A/B)  
pipe (A/B)  
5m(16ft)  
Pipe Size  
30m(100ft)  
15m(50ft)  
7.5m(25ft)  
7.5m(25ft)  
Indoor Capacity  
(Btu/h)  
Gas  
Liquid  
Standard Length  
Additional Refrigerant  
20g/m(0.22oz/ft)  
9k  
9.52mm(3/8")  
6.35mm(1/4")  
7.5m(25ft)  
A
h2  
B
h1  
h1  
B
CAUTION: Capacity is based on standard length and maximum allowance length is on the  
basis of reliability.  
16 Multi type Air Conditioner  
Installation  
Fixing Installation Plate  
The wall you select should be strong and solid  
enough to prevent vibration  
Installation Plate  
1. Mount the installation plate on the wall with  
type "A" screws. If mounting the unit on a concrete  
wall, use anchor bolts.  
Mount the installation plate horizontally by aligning  
the centerline using a level.  
Chassis  
Hook  
Type "A" screw  
2. Measure the wall and mark the centerline. It is also  
important to use caution concerning the location of  
the installation plate. Routing of the wiring to power  
outlets is through the walls typically. Drilling the  
hole through the wall for piping connections must  
be done safely.  
Distance (mm/inch)  
CHASSIS  
(Grade)  
A
B
C
D
S4  
50(1.97) 105(4.13) 59(2.32) 105(4.13)  
Installation plate  
B
D
A
C
Ø70mm  
Ø70mm  
(Ø2.75inch)  
(Ø2.75inch)  
Left rear piping  
Right rear piping  
Service Manual 17  
Flaring Work and Connection of Piping  
Flaring Work and Connection of Piping  
Flaring work  
Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure.  
Cut the pipes and the cable.  
1. Use the piping kit accessory or the pipes purchased  
locally.  
Copper  
pipe  
Slanted Uneven Rough  
2. Measure the distance between the indoor and the out-  
door unit.  
90°  
3. Cut the pipes a little longer than measured distance.  
4. Cut the cable 1.5m (5.0ft) longer than the pipe length.  
Burrs removal  
Pipe  
1. Completely remove all burrs from the cut cross section  
of pipe/tube.  
Reamer  
2. Put the end of the copper tube/pipe in a downward  
direction as you remove burrs in order to avoid dropping  
burrs into the tubing.  
Point down  
Putting nut on  
Flare nut  
Remove flare nuts attached to indoor and outdoor unit,  
then put them on pipe/tube having completed burr  
removal.  
Copper tube  
(not possible to put them on after flaring work)  
Flaring work  
Carry out flaring work using flaring tool as shown below.  
Firmly hold copper pipe in a Bar in the dimension shown  
in the table below.  
Handle  
Yoke  
Bar  
Bar  
Outside diameter  
A
Cone  
mm  
Ø6.35  
Ø9.52  
inch  
1/4  
3/8  
mm  
1.1~1.3  
1.5~1.7  
Copper pipe  
Clamp handle  
Red arrow mark  
18 Multi type Air Conditioner  
Flaring Work and Connection of Piping  
Check  
1. Compare the flared work with the figure.  
Smooth all round  
Inside is shiny without scratches  
2. If a flared section is defective, cut it off and do flaring  
work again.  
= Improper flaring =  
Inclined Surface Cracked Uneven  
damaged  
thickness  
Even length  
all round  
Connecting the Piping  
Indoor  
1. Prepare the indoor unit's piping and drain hose for installation through the wall.  
2. Remove the plastic tubing retainer(see the illustra-  
tion) and pull the tubing and drain hose away from  
chassis.  
3. Replace the plastic holder in original position.  
For right rear piping  
1. Route the indoor tubing and the drain hose in the  
direction of rear right.  
2. Insert the connecting cable into the indoor unit from the  
outdoor unit through the piping hole.  
Do not connect the cable to the indoor unit.  
Make a small loop with the cable for easy connec-  
tion later.  
Drain hose  
3. Tape the tubing, drain hose, and the connecting  
cable. Be sure that the drain hose is located at the  
lowest side of the bundle. Locating at the uper side  
can cause drain pan to overflow inside the unit.  
If the drain hose is routed inside the room, insulate the  
hose with an insulation material* so that dripping from  
"sweating"(condensation) will not damage furniture or  
floors.  
Tape  
Connecting  
pipe  
*Foamed polyethylene or equivalent is recommended.  
Drain hose  
Connecting cable  
Service Manual 19  
Flaring Work and Connection of Piping  
4. Indoor unit installation  
Hook the indoor unit onto the upper portion of the  
installation plate.(Engage the two hooks of the rear  
top of the indoor unit with the upper edge of the  
installation plate.) Ensure that the hooks are properly  
seated on the installation plate by moving it left and  
right.  
Connecting  
cable  
Drain hose  
Press the lower left and right sides of the unit against  
the installation plate until the hooks engage into their  
slots(clicking sound).  
Connecting the piping to the indoor unit and drain  
hose to drain pipe.  
Indoor unit tubing  
Flare nut Pipes  
1. Align the center of the pipes and sufficiently tighten  
the flare nut by hand.  
2. Tighten the flare nut with a wrench.  
Open-end wrench (fixed)  
Outside diameter  
Torque  
Flare nut  
.
mm  
Ø6.35  
Ø9.52  
inch  
1/4  
3/8  
kgf m(lbf-ft)  
1.8~2.5(13)  
3.4~4.2(30)  
Wrench  
Connection pipe  
Indoor unit tubing  
3. When extending the drain hose at the indoor unit,  
install the drain pipe.  
Drain pipe  
Indoor unit drain hose  
Vinyl tape(narrow)  
Adhesive  
Wrap the insulation material around the connecting  
portion.  
Plastic bands  
Insulation material  
1. Overlap the connection pipe insulation material and  
the indoor unit pipe insulation material. Bind them  
together with vinyl tape so that there may be no gap.  
2. Wrap the area which accommodates the rear piping  
housing section with vinyl tape.  
Indoor unit pipe  
Wrap with vinyl tape  
Connection pipe  
Vinyl tape (wide)  
Connecting cable  
Pipe  
3. Bundle the piping and drain hose together by wrap-  
ping them with vinyl tape for enough to cover where  
they fit into the rear piping housing section.  
Vinyl tape(narrow)  
Wrap with vinyl tape  
Pipe  
Vinyl tape(wide)  
Drain hose  
20 Multi type Air Conditioner  
Flaring Work and Connection of Piping  
For left rear piping  
1. Route the indoor tubing and the drain hose to the  
required piping hole position.  
1
2
Connecting  
cable  
2. Insert the piping, drain hose, and the connecting  
cable into the piping hole.  
3. Insert the connecting cable into the indoor unit.  
Don't connect the cable to the indoor unit.  
Make a small loop with the cable for easy connec-  
tion later.  
Drain pipe  
4. Tape the drain hose and the connecting cables.  
5. Indoor unit installation  
Hang the indoor unit from the hooks at the top of the  
installation plate.  
Insert the spacer etc. between the indoor unit and  
the installation plate and separate the bottom of the  
indoor unit from the wall.  
Indoor unit  
Spacer  
Installation plate  
8cm  
Connecting the piping to the indoor unit and the  
drain hose to drain pipe.  
1. Align the center of the pipes and sufficiently tighten  
the flare nut by hand.  
Indoor unit tubing  
Flare nut Pipes  
2. Tighten the flare nut with a wrench.  
Outside diameter  
Torque  
Open-end wrench (fixed)  
.
mm  
Ø6.35  
Ø9.52  
inch  
1/4  
3/8  
kgf m(lbf-ft)  
1.8~2.5(13)  
3.4~4.2(30)  
Flare nut  
Wrench  
Connection pipe  
Indoor unit tubing  
3. When extending the drain hose at the indoor unit,  
install the drain pipe.  
Drain hose  
Indoor unit drain hose  
Vinyl tape (narrow)  
Adhesive  
Service Manual 21  
Flaring Work and Connection of Piping  
Wrap the insulation material around the connecting  
portion.  
Plastic bands  
Insulation material  
1. Overlap the connection pipe heat insulation and the  
indoor unit pipe heat insulation material. Bind them  
together with vinyl tape so that there may be no gap.  
2. Wrap the area which accommodates the rear piping  
housing section with vinyl tape.  
Indoor  
unit piping  
Connection  
pipe  
Vinyl tape  
(wide)  
Wrap with vinyl tape  
Pipe  
Vinyl tape(narrow)  
Connecting cable  
3. Bundle the piping and drain hose together by wrap-  
ping them with cloth tape over the range within which  
they fit into the rear piping housing section.  
Pipe  
Drain hose  
Vinyl tape(narrow)  
Wrap with  
vinyl tape(wide)  
Reroute the pipings and the drain hose across the  
back of the chassis.  
Piping for  
passage through  
piping hole  
Indoor unit installation  
1. Remove the spacer.  
2. Ensure that the hooks are properly seated on the  
installation plate by moving it left and right.  
Connecting  
cable  
3. Press the lower left and right sides of the unit against  
the installation plate until the hooks engage into their  
slots(clicking sound).  
Drain hose  
22 Multi type Air Conditioner  
Flaring Work and Connection of Piping  
REMOTE CONTROL PREPARATION(OPTIONAL)  
HOW TO MOUNT ONTO A WALL  
HOW TO INSERT BATTERIES  
Remove the battery cover from the remote con-  
troller.  
Slide the cover according to the arrow direction.  
Do not use rechargeable batteries,  
such batteries differ from standard dry  
cells in shape, dimensions, and per-  
formance.  
Romove the batteries from the remote  
controller if the air conditioner is not  
going to be used for some long time.  
Insert the two batteries.  
Be sure that the (+) and (-) directions are correct.  
Be sure that both batteries are new.  
Re-attach the cover.  
Slide it back into position.  
Service Manual 23  
Flaring Work and Connection of Piping  
Outdoor  
Align the center of the pipings and sufficiently tighten  
the flare nut by hand.  
Finally, tighten the flare nut with torque wrench until the  
wrench clicks.  
Outdoor unit  
When tightening the flare nut with torque wrench,  
ensure the direction for tightening follows the arrow on  
the wrench.  
A-UNIT  
Gas side piping  
Outside diameter  
Torque  
.
mm  
Ø6.35  
Ø9.52  
inch  
1/4  
3/8  
kgf m(lbf-ft)  
1.8~2.5(13)  
3.4~4.2(30)  
B-UNIT  
Liquid side piping  
Torque wrench  
24 Multi type Air Conditioner  
Flaring Work and Connection of Piping  
Connecting the Cable between Indoor Unit and Outdoor Unit  
Connect the cable to the Indoor unit.  
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individu-  
ally according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the ter-  
minal No. are the same as those of the indoor unit.)  
The earth wire should be longer than the common wires.  
The circuit diagram is not subject to change without notice.  
When installing, refer to the electrical diagram behind the front panel of Indoor Unit.  
The wiring for the outdoor unit can be found on the inside of the Outdoor Unit control cover.  
WARNING:  
• The circuit diagram is not subject to change without notice.  
• Be sure to connect wires according to the wiring diagram.  
• Connect the wires firmly, so that not to be pulled out easily.  
• Connect the wires according to color codes by referring to the wiring diagram.  
WARNING: Provide a circuit breaker  
Main power source  
between power source and the out-  
door unit as shown below.  
Air  
Circuit Breaker  
Conditioner  
Use a circuit breaker  
or time delay fuse.  
WARNING! : The power wire to the outdoor unit must be of sufficient gauge to meet the  
Minimum Circuit Ampacity (MCA) as indicated on the outdoor unit rating plate and be of  
type required by NEC and local codes.  
AWG14  
Line voltage (208~230V)  
The connecting cable between the indoor and outdoor unit should be SJOW type, mini-  
mum 18 gauge, and meet requirements of NEC and local codes.  
AWG18  
Low voltage (below 40V)  
WARNING! Secure the interconnecting on both ends by using the clamps provided.  
Service Manual 25  
Connecting the Cable between Indoor Unit and Outdoor Unit  
Connect the cable to the Outdoor unit.  
1. Remove the cover control from the unit by loosening  
the screw.  
Outdoor unit  
Connect the wires to the terminals on the control  
board individually as the following.  
Terminal block  
Over 5mm  
2. Secure the cable into the control board with the strain  
relief clamp.  
Holder for  
power supply  
cord  
3. Refix the cover control to the original position with the  
screw.  
Power supply  
cable  
Outdoor side  
A-UNIT  
B-UNIT  
1
2
3
4
1
2
3
4
Cover control  
Connecting  
cable  
L
N
1
2
3
4
1
2
3
4
Terminal BLOCK  
Indoor A-UNIT  
Indoor B-UNIT  
Power Source  
208/230V AC  
(High voltage)  
NOTICE  
:
1. Separately wire the high and low voltage line.  
2. Use heat-proof electrical wiring capable of withstanding temperature up to 75°C(167°F).  
3. Use outdoor and waterproof connection cable rated more than 300V for the connection between indoor and out-  
door unit. (For example, Type SJOW)  
WARNING:  
Be sure to comply with local codes while running the wire from the indoor unit to the outdoor  
unit(size of wire and wiring method, etc).  
Every wire must be connected firmly.  
No wire should be allowed to touch refrigerant tubing, the compressor or any moving parts.  
26 Multi type Air Conditioner  
Connecting the Cable between Indoor Unit and Outdoor Unit  
Connection method of the connecting cable(Example)  
(1) Remove two-caps on the conduit panel.  
(for low voltage line)  
(2) Pull out connection cable through conduit.  
(3) After conduit to the panel, fix nut to the opposite side of  
panel  
Terminal  
block  
(4) Pass the conneciton cable through the hole  
(5) Properly connect the cable on the terminal block  
(6) Fix the connection cable with cord clamp provided on the  
unit not to have strain at the terminal when the connec-  
tion cable is pulled outside up to a 35 pound weight.  
Connecting cable  
Cord clamp  
Power supply  
cable  
Lock nut  
Cap(Remove)  
Hole  
(for low voltage line)  
Taping  
(for sealing)  
WARNING: Loose wiring may cause the  
terminal to overheat or result in unit mal-  
function. A fire hazard may also exist.  
Therefore, be sure all wiring is tightly con-  
nected.  
Power supply line  
(1ø, 230/208V)  
Low voltage line  
(connecting cable)  
Conduit panel  
When connecting each power wire to the corresponding  
terminal, follow instructions "How to connect wiring to the  
terminals" and fasten the wire tightly with the fixing  
screw of the terminal plate.  
High voltage  
Strand wire  
How to connect wiring to the terminals  
For strand wiring  
(1) Cut the wire end with a wire cutter or wire-cutting pli-  
ers, then strip the insulation to expose the strand  
wiring about 10mm(3/8").  
Round  
terminal  
(2) Using a screwdriver, remove the terminal screw(s) on  
the terminal plate.  
(3) Using a round terminal fastener or pliers, securely  
clamp each stripped wire end with a round terminal.  
(4) Position the round terminal wire, and replace and  
tighten the terminal screw using a screwdriver.  
Low voltage  
Loosening the  
Fastening the  
wire tightly  
terminal block screw  
Connecting cable  
Connecting cable  
Service Manual 27  
Connecting the Cable between Indoor Unit and Outdoor Unit  
CAUTION! Provide a circuit breaker between the power source and the outdoor  
unit as shown below. Size breaker per the Maximum Fuse or Circuit Breaker (MOC)  
rating on the unit rating plate.  
Main power source  
Air  
Fuse or breaker  
Circuit Breaker  
Use a circuit  
breaker or time  
delay fuse.  
Model  
18k  
Power source  
Conditioner  
Capacity  
1ø,230/208V  
20A  
Connect the cable to the indoor unit  
1. Connect the wires to the terminals on the control  
board individually according to the outdoor unit con-  
nection.  
Ensure that the color of the wires of outdoor unit  
and the terminal No. are the same as those of  
indoor unit respectively.  
Connecting cable  
2. Attach the Grille onto the cabinet.  
Grasp the lower left and right side of the Grille and  
engage four tabs on the top inside edge of the chas-  
sis.  
Press the Grille toward the chassis until it will be  
back into place.  
28 Multi type Air Conditioner  
Checking the Drainage, Forming the Pipings and Long Pipe Setting  
Checking the Drainage, Forming the Pipings and Long Pipe Setting  
Checking the drainage  
To check the drainage.  
1. Pour a glass of water on the evaporator.  
2. Ensure the water flows through the drain hose of the  
indoor unit without any leakage and goes out the  
drain exit.  
Drain piping  
1. The drain hose should point downward for easy drain  
Downward slope  
flow.  
2. Examples of incorrect drain piping.  
Accumulated  
drain water  
Air  
Do not raise  
Less than  
50mm gap  
Tip of drain hose  
dipped in water  
Water  
leakage  
Water  
leakage  
Water  
leakage  
Waving  
Ditch  
Service Manual 29  
Checking the Drainage, Forming the Pipings and Long Pipe Setting  
Forming the piping  
Form the piping by wrapping the con-  
necting portion of the indoor unit with  
insulation material and secure it with  
two kinds of vinyl tape.  
Seal a small  
opening around  
the pipings with  
gum type sealer.  
Taping  
Drain hose  
If you want to connect an additional drain hose, the  
end of the drain outlet should be routed above the  
ground. Secure the drain hose appropriately.  
Plastic  
band  
Pipings  
In cases where the outdoor unit is  
installed below the indoor unit perform  
the following.  
Connecting  
cable  
1. Tape the piping, drain hose and connecting cable  
Power supply  
cord  
from down to up.  
2. Secure the tapped piping along the exterior wall  
Trap is required to prevent water from entering  
into electrical parts.  
using saddle or equivalent.  
In cases where the Outdoor unit is  
installed above the Indoor unit perform  
the following.  
1. Tape the piping and connecting cable from down  
Seal a small opening  
around the pipings  
to up.  
with gum type sealant.  
2. Secure the taped piping along the exterior wall.  
Form a trap to prevent water entering the room.  
3. Fix the piping onto the wall by saddle or equiva-  
lent.  
Trap  
Trap  
30 Multi type Air Conditioner  
Air Purging and Evacuation  
Air Purging and Evacuation  
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.  
1. Pressure in the system rises.  
2. Operating current rises.  
3. Cooling(or heating) efficiency drops.  
4. Moisture in the refrigerant circuit may freeze and block capillary tubing.  
5. Water may lead to corrosion of parts in the refrigeration system.  
Therefore, the indoor/outdoor unit and connecting tube must be checked for leak tight, and vacuumed to remove  
incondensible gas and moisture in the system.  
Checking method  
1. Do a leakage test of all joints of the tubing(both  
indoor and outdoor) and both gas and liquid side ser-  
vice valves.  
Preparation  
Check that each tube(both liquid and gas side tubes)  
between the indoor and outdoor units have been properly  
connected and all wiring for the test run has been complet-  
ed. Remove the service valve caps from both the gas and  
the liquid side on the outdoor unit. Check that both the liq-  
uid and the gas side service valves on the outdoor unit are  
kept closed at this stage.  
Bubbles indicate a leak. Be sure to wipe off the soap  
with a clean cloth.  
2. After the system is found to be free of leaks, relieve  
the nitrogen pressure by loosening the charge hose  
connector at the nitrogen cylinder. When the system  
pressure is reduced to normal, disconnect the hose  
from the cylinder.  
Leakage test  
Connect the manifold valve(with pressure gauges) and dry  
nitrogen gas cylinder to this service port with charge  
hoses.  
CAUTION: Be sure to use a manifold  
valve for leak testing.  
Indoor unit  
The high side manifold valve must always  
be kept closed.  
Outdoor unit  
Pressurize the system to no more than 150 P.S.I.G.  
with dry nitrogen gas and close the cylinder valve  
when the gauge reading reached 150 P.S.I.G. Next,  
test for leaks with liquid soap.  
CAUTION: To avoid nitrogen entering the  
refrigerant system in a liquid state, the top  
of the cylinder must be higher than its bottom  
when you pressurize the system. Usually, the  
cylinder is used in a vertical standing position.  
Manifold valve  
Pressure  
Lo  
Hi  
gauge  
Charge hose  
NOTICE  
:
Leakage test shoud be done for each  
indoor unit connection set, separately.  
Nitrogen gas  
cylinder(in vertical  
standing position)  
Service Manual 31  
Checking the Drainage, Forming the Pipings and Long Pipe Setting  
Evacuation  
1. Connect the charge hose end described in the pre-  
ceding steps to the vacuum pump to evacuate the  
tubing and indoor unit.  
Indoor unit  
Confirm the "Lo" knob of the manifold valve is open.  
Then, run the vacuum pump.  
The operation time for evacuation varies with tubing  
length and capacity of the pump.  
[Each Room] The vacuum pump must be operated  
less than 0.8torr of the gage pressure.  
Outdoor unit  
2. When the desired vacuum is reached, close the "Lo"  
knob of the manifold valve and stop the vacuum  
pump.  
Finishing the job  
1. With a service valve wrench, turn the valve stem of  
liquid side valve counter-clockwise to fully open the  
valve.  
2. Turn the valve stem of gas side valve counter-clock-  
wise to fully open the valve.  
Manifold valve  
3. Loosen the charge hose connected to the gas side  
Pressure  
gauge  
Lo  
Hi  
service port slightly to release the pressure, then  
remove the hose.  
4. Replace the flare nut and its bonnet on the gas side  
service port and fasten the flare nut securely with an  
adjustable wrench. This process is very important to  
prevent leakage from the system.  
Open  
Close  
5. Replace the valve caps at both gas and liquid side  
service valves and fasten them tight.  
This completes air purging with a vacuum pump.  
The air conditioner is now ready for test running.  
Vacuum pump  
NOTICE  
: Repeat evacuation procedure for each indoor  
unit.  
32 Multi type Air Conditioner  
Charging  
Charging  
I Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line set for  
each indoor line.  
Any time total line set is used either shorter or longer then the nominal 15m(50ft) line set length the refrigerant  
charge has to be adjusted.  
I Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are  
either added or removed based on 20g/m(0.22oz/ft) of R-410A per meter(foot).  
Max Elevation  
between each indoor  
each pipe (A/B) each pipe (A/B) unit and outdoor unit  
(h1)  
Max total length  
of all pipes  
(A+B)  
Max elevation  
between indoor  
units (h2)  
Additional  
Refrigerant  
Max length of  
Min length of  
Capacity (Btu/h)  
18k  
30m(100ft)  
15m(50ft)  
5m(16ft)  
7.5m(25ft)  
7.5m(25ft)  
20g/m(0.22oz/ft)  
Example: A 75ft line set is used for dual - zone 25 additional ft X 0.22 ounces per foot= add 5.5 ounces of R-  
410A  
Important:(Unit is critically charge)  
If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit name-  
plate charge adjusting for line sets longer or shorter than 7.5m(25ft) for each indoor unit.  
Service Manual 33  
Test Running  
Test Running  
1. Check that all tubing and wiring have been properly connected.  
2. Check that the gas and liquid side service valves are fully open.  
Prepare remote control  
Remove the battery cover by pulling it according to the  
arrow direction.  
Insert new batteries making sure that the (+) and () of  
battery are installed correctly.  
Reattach the cover by pushing it back into position.  
NOTICE  
:
Bolt  
Use 2 AAA(1.5volt) batteries. Do not use rechargeable  
batteries.  
Remove the batteries from the remote control if the sys-  
tem is not going to be used for a long time.  
Evaluation of the performance  
Tubing connection  
Operate all indoor units for 15~20 minutes, then check  
the system refrigerant charge:  
1.Measure the pressure of one of the gas side service  
valves.  
Intake temperature  
2. Measure the temperature of the intake and discharge  
of air.  
Discharge air  
3. Ensure the difference between the intake temperature  
and the discharge is more than 8°C(14.4°F).  
4. For reference, the gas side pressure of optimum condi-  
tion is as below.(Cooling)  
Outside ambient  
TEMP.  
The pressure of the gas side  
service valve.  
Discharge  
temperature  
Refrigerant  
R-410A  
35°C (95°F) 8.5~9.5kg/cm2G(120~135 P.S.I.G.)  
NOTICE  
:
If the actual pressure are higher than shown, the  
system is most likely over-charged, and charge should be  
removed. If the actual pressure are lower than shown, the sys-  
tem is most likely undercharged, and charge should be added.  
Important:  
Individual zones should be all in the same  
operation mode (Heating or Cooling mode)  
34 Multi type Air Conditioner  
Operation  
Operation  
Function of control  
1. MAIN UNIT FUNCTION  
DISPLAY  
Operation Indicator  
On while in appliance operation, off while in appliance pause  
Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on)  
Sleep Timer Indicator  
On while in sleep timer mode, off when sleep timer cancel or appliance operation pause  
Timer Indicator  
On while in timer mode (on/off), off when timer mode is completed or canceled  
Defrost Indicator  
Off except when hot start during heating mode operation or while in defrost control  
I Cooling Mode Operation  
When the intake air temperature reaches 0.5°C(0.9°F) below the setting temp, the compressor and the outdoor  
fan stop.  
When it reaches 0.5°C(0.9°F) above the setting temp, they start to operate again.  
Compressor ON Temp  
Compressor OFF Temp  
Setting Temp+0.5°C(0.9°F)  
Setting Temp-0.5°C(0.9°F)  
While in compressor running, operating with the airflow speed set by the remote control. While compressor is  
off fan operates at low speed regardless of the setting.  
I Soft Dry Operation Mode  
When the dehumidification operation input by the remote control is received, the intake air temperature is  
detected and the setting temp is automatically set according to the intake air temperature.  
26°C(78.8°F) Intake Air Temp  
25°C(77°F)  
24°C(75.2°F) Intake Intake Air Temp<26°C(78.8°F)  
18°C(64.4°F) Intake Intake Air Temp<24°C(75.2°F)  
Intake Air Temp<18°C(64.4°F)  
Intake Air Temp-1°C(30.2°F)  
Intake Air Temp-0.5°C(31.1°F)  
18°C(64.4°F)  
While compressor off, the indoor fan repeats low airflow speed and stop.  
While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification  
operation and 4-min compressor off repeat.  
Compressor ON Temp.  
Setting Temp+0.5°C(0.9°F)  
Compressor OFF Temp. Setting Temp-0.5°C(0.9°F)  
In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.  
I Heating Mode Operation  
When the intake air temp reaches +3°(37.4°F)above the setting temp, the compressor is turned off. When  
below the setting temp, the compressor is turned on.  
Compressor ON Temp.  
Setting Temp.  
Compressor OFF Temp. Setting Temp.+3°C(37.4°F)  
While compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C(68°F), when above  
27°C(80.6°F) , it operates with the low or setting speed. When the indoor pipe temp is between 20°C(68°F) and  
Service Manual 35  
Operation  
27°C(80.6°F), it operates with Super-Low(while in sleep mode, with the medium airflow speed).  
While compressor off, the indoor fan is off when the indoor pipe temp is below 33°C(91.4°F), when above  
35°C(95°F) , it operates with the low airflow speed.  
While in defrost control, the indoor is outdoor fans are turned off.  
I Defrost Control(Heating)  
Defrost operation is controlled by timer and sensing temperature of outdoor pipe.  
The first defrost starts only when the outdoor pipe temperature falls below -6°C(21.2°F) after 35 minutes  
passed from starting of heating operation and more than 4 minutes operation of compressor.  
Defrost ends after 12 minutes passed from starting of defrost operation when the outdoor pipe temperature  
rises over 15°C(59°F) even before 12 minutes.  
The second defrost starts only when the outdoor pipe temperature falls below -6°C(21.2°F) after 35 minutes  
passed from ending of the first defrost and more than 4 minutes operation of compressor.  
I Fuzzy Operation  
When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since  
the operation off, the operation mode is selected.  
When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only  
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air  
temp at that moment as follows.  
24°C(75.2°F) Intake Air Temp  
21°C(69.8°F) Intake Air Temp<24°C(75.2°F)  
Intake Air Temp<21°C(69.8°F)  
Fuzzy Operation for Cooling  
Fuzzy Operation for Dehumidification  
Fuzzy Operation for Heating  
If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10  
sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.  
1) Fuzzy Operation for Cooling  
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(0.9°F) or more  
below the setting temp, the compressor is turned off. When 0.5°C(0.9°F) or more above the setting temp, the  
compressor is turned on.  
Compressor ON Temp  
Compressor OFF Temp  
Setting Temp +0.5°C(0.9°F)  
Setting Temp + 0.5°C(0.9°F)  
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the  
intake air temp at that time.  
26°C(78.8°F)Intake Air Temp  
25°C(77°F)  
24°C(75.2°F)Intake Air Temp<26°C(78.8°F)  
22°C(71.6°F)Intake Air Temp<24°C(75.2°F)  
18°C(64.4°F)Intake Air Temp<22°C(71.6°F)  
Intake Air Temp<18°C(64.4°F)  
Intake Air Temp + 1°C(1.8°F)  
Intake Air Temp + 0.5°C(0.9°F)  
Intake Air Temp  
18°C(64.4°F)  
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the  
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature  
automatically according to the Fuzzy rule.  
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temper-  
ature.  
36 Multi type Air Conditioner  
Operation  
2) Fuzzy Operation for Dehumidification  
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(0.9°F) or more  
below the setting temp, the compressor is turned off. When 0.5°C(0.9°F) or more above the setting temp, the  
compressor is turned on.  
Compressor ON Temp  
Compressor OFF Temp  
Setting Temp + 0.5°C(0.9°F)  
Setting Temp+0.5°C(0.9°F)  
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the  
intake air temp at that time.  
26°C(78.8°F) Intake Air Temp  
25°C(77°F)  
24°C(75.2°F) Intake Air Temp<26°C(78.8°F)  
22°C(71.6°F) Intake Air Temp<24°C(75.2°F)  
18°C(64.4°F) Intake Air Temp<22°C(71.6°F)  
Intake Air Temp<18°C(64.4°F)  
Intake Air Temp+1°C(1.8°F)  
Intake Air Temp+0.5°C(0.9°F)  
Intake Air Temp  
18°C(64.4°F)  
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the  
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature  
automatically according to the Fuzzy rule.  
While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in  
dehumidification operation.  
3) Fuzzy Operation for Heating  
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C(37.4°F) or more  
above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned  
on.  
Compressor ON Temp  
Compressor OFF Temp  
Setting Temp  
Setting Temp + 3°C(5.4°F)  
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the  
intake air temp at that time.  
20°C(68°F)Intake Air Temp  
Intake Air Temp<20°C(68°F)  
Intake Air Temp + 0.5°C(0.9°F)  
20°C(68°F)  
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the  
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature  
automatically according to the Fuzzy rule.  
While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the  
intake air temperature and the setting temperature.  
I Airflow Speed Selection  
The airflow speed of the indoor fan is set to high, medium, low, or power (auto) by the input of the airflow  
speed selection key on the remote control.  
I On-Timer Operation  
When the set time is reached after the time is input by the remote control, the appliance starts to operate.  
The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.  
If the appliance is operating at the time set by the timer, the operation continues.  
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.  
I Off-Timer Operation  
When the set time is reached after the time is input by the remote control, the appliance stops operating.  
The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.  
Service Manual 37  
Operation  
If the appliance is on pause at the time set by the timer, the pause continues.  
I Off-Timer <=> On-Timer Operation  
When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is  
carried out according to the set time.  
I Sleep Timer Operation  
When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appli-  
ance operation, the operation of the appliance stops.  
While the appliance is on pause, the sleep timer mode cannot be input.  
While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature  
increases by 1°C(33.8°F). After another 30 min elapse, it increases by 1°C(1.8°F) again.  
When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to  
the low.  
When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to  
the medium.  
I Chaos Swing Mode  
By the Chaos Swing key input, the upper/lower vane automatically operates with the Chaos Swing or they are  
fixed to the desired direction.  
While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.  
I Chaos Natural Wind Mode  
When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air-  
flow mode is operated for 2~15 sec. randomly by the Chaos Simulation.  
I Jet Cool Mode Operation  
While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the  
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.  
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.  
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C(64.4°F)  
.
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.  
When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then  
operated in order that the air outflow could reach further.  
I Auto Restarting Operation  
When the power is restored after a sudden power failure while in appliance operation, the mode before the  
power failure is kept on the memory and the appliance automatically operates in the mode on the memory.  
38 Multi type Air Conditioner  
Operation  
I Forced Operation  
To operate the appliance by force in case that the remote control is lost, the forced operation selection switch  
is on the main unit of the appliance to operate the appliance in the standard conditions.  
When the power is supplied while the slide switch is on the forced operation position, or when the slide switch  
position is switched to the Auto Restarting (or test operation) position or switched from the remote control  
position to the forced operation position while the power is on, the forced operation is carried out.  
When the slide switch position is switched from the forced operation position to the Auto Restarting position or  
the remote control position, the forced operation is canceled and the appliance stops operating.  
In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the opera-  
tion condition is set according to the intake air temperature as follows.  
24°C(43.2°F)Intake Air Temp  
21°C(37.8°F)Intake Air Temp<24°C(43.2°F)  
Intake Air Temp<21°C(37.8°F)  
Cooling Mode Operation, 22°C(39.6°F), High Speed  
Dehumidification Operation, 23°C(41.4°F), High Speed  
Heating Mode Operation, 24°C(43.2°F), High Speed  
I Buzzer Sounding Operation  
When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.  
When the appliance-pause key is input by the remote control, the long "beep" sounds.  
Service Manual 39  
Operation  
Function of Indoor Unit  
Split Type Indoor Unit  
Operation ON/OFF by Remote controller  
Sensing the Room Temperature  
Room temperature sensor. (THERMISTOR)  
Room temperature control  
Maintains the room temperature in accordance with the Setting Temp.  
Starting Current Control  
Indoor fan is delayed for 5 seconds at the starting.  
Time Delay Safety Control  
Restarting is delayed for approx. 3 minutes.  
Indoor Fan Speed Control  
High, Med, Low, Chaos, Jet Cool  
Operation indication Lamps (LED)  
On/Off  
Sleep Mode : Lights up during Sleep Mode Auto operation.  
Timer : Lights up during Timer operation.  
Defrost Mode: Lights up during Defrost Mode or Hot Start operation (Heat pump model only)  
: Lights up during the system operation.  
Outdoor unit  
operation  
: Lights up during outdoor unit operation.(Cooling model only)  
Desire temperature For cooling,dehumidification,heating modes it display Destired temperature  
indicator  
Cooling  
Dehumidification : 18°C~30°C(64°F~86°F)  
Heating : 16~30°C(60°F~86°F)  
: 18°C~30°C(64°F~86°F)  
AI : Auto Operation  
Po : Jet Cool  
Lo : Test Mode  
: The function illustrates its dynamic mode by using a multiple lighting system. (Optional)  
Plasma  
Soft Dry Operation Mode  
Intermittent operation of fan at low speed.  
Sleep Mode Auto Control  
Deice (defrost) control (Heating)  
Both the indoor and outdoor fan  
stops during deicing.  
Hot start after deice ends.  
The fan is switched to low(Cooling), med(Heating) speed.  
The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.  
Natural Air Control by CHAOS Logic  
Hot-start Control (Heating)  
The fan is switched to intermittent or irregular operation  
The indoor fan stops until the  
evaporator piping temperature will  
be reached at 27°C(80.6°F).  
The fan speed is automatically switched from high to low speed.  
* Airflow Direction Control  
The louver can be set at the desired position or swing  
up and down automatically.(Model base)  
"Wall Mounted Type is standard"  
* Functions is dependent on model type.  
40 Multi type Air Conditioner  
Operation  
Function of Outdoor Unit  
Outdoor Unit  
Operating Step  
Compressor step varies considering condition such as room temp,outdoor temp, operating room  
number,Temp gap between room temp and set temp and so on.  
LEV Control  
LEV pulse is modulated to keep constant superheat or subcooling.  
Out door Fan Control  
Outdoor fan operates at High or Off to respond to the load condition.  
R/Valve Control(Heating Model Only)  
Convert R/Valve to change cooling to heating, heating to cooling.  
Defrost Function  
After 45 min heating operation, check the defrost condition and if outdoor pipe temp is below -  
5°C(23°F) and released from deice operation in case outdoor pipe temp is over 12°C(53.6°F) or 9 min  
cooing mode.  
To deice outdoor heat exchanger in low temp condtion, convert operating mode from heating to cooling mode.  
Oil Return System  
In single(one) comp operation duration, another comp will operate for 30 seconds every 1 hours.  
Comp Overload Protection  
To protect comp from being overload, protector will turn off the comp.  
High Pressure Protction  
If cycle pressure is too high(around 36.7 kgf/cm2), it will turn off comp A  
Service Manual 41  
Operation  
Remote Control Operation  
The Remote Controller transmits the signals to the system.  
START/STOP BUTTON  
Operation starts when this button is pressed and stops when  
the button is pressed again.  
1
Signal transmitter  
OPERATION MODE SELECTION BUTTON  
Used to select the operation mode.  
2
3
(Cooling Only)  
(Heat Pump)  
ROOM TEMPERATURE  
SETTING BUTTONS  
Used to select the room temperature.  
INDOOR FAN SPEED SELECTOR  
Used to select fan speed in four steps  
low, medium, high and CHAOS.  
4
5
6
5
6
1
3
JET COOL  
Used to start or stop the speed cooling/heating.  
(Speed cooling/heating operates super high fan speed.)  
4
CHAOS SWING BUTTON  
Used to stop or start louver movement and set the desired  
up/down airflow direction.  
10  
2
7
CANCEL  
9
SET  
ON  
OFF  
AUTO CLEAN  
16  
11  
8
13  
ON/OFF TIMER BUTTONS  
Used to set the time of starting and stopping operation.  
7
8
9
12  
17  
18  
15  
°C/°F  
TIME SETTING BUTTONS  
Used to adjust the time.  
14  
TIMER SET/CANCEL BUTTON  
Used to set the timer when the desired time is obtained and to cancel  
the Timer operation.  
SLEEP MODE AUTO BUTTON  
Used to set Sleep Mode Auto operation.  
10  
11  
12  
13  
14  
15  
Flip-up door  
(opened)  
AIR CIRCULATION BUTTON  
Used to circulate the room air without cooling or heating.  
Operation Mode  
ROOM TEMPERATURE CHECKING BUTTON  
Used to check the room temperature.  
Cooling Operation  
PLASMA(OPTIONAL)  
Used to start or stop the plasma-purification function.  
Auto Operation  
RESET BUTTON  
Initialize remote controller.  
Healthy Dehumidification Operation  
2nd F Button  
Heating Operation  
Used prior to using modes printed in blue at the bottom of buttons.  
AUTO CLEAN  
Used to set Auto Clean mode.  
Cooling Model( ), Heat Pump Model(  
)
16  
17  
˚C TO ˚F SWITCHING BUTTON  
Used to switch temperature reading from Centigrade to Fahrenheit.  
HORIZONTAL AIRFLOW DIRECTION CONTROL BUTTON (NOT ON  
ALL MODELS)  
18  
Used to set the desired horizontal airflow direction.  
42 Multi type Air Conditioner  
Disassembly  
Disassembly  
Indoor Unit  
Split Type Indoor Unit  
Disconnect the unit from power supply before mak-  
ing any checks.  
Be sure the power switch is set to “OFF”.  
To remove the Grille from the Chassis.  
• Set the up-and-down air discharge louver to open  
position (horizontally) by finger pressure.  
• Remove the securing screws.  
• To remove the Grille, pull the lower left and right  
side of the grille toward you (slightly tilted) and lift it  
straight upward.  
1. Before removing the control box, be sure to  
take out the wire screwed at the other end.  
Earth  
Conductor  
Service Manual 43  
Disassembly  
2. To remove the Control Box.  
Remove securing screws.  
Pull the control box out from the chassis  
carefully.  
Screw  
3. To remove the Discharge Grille.  
Unhook the discharge grille and pull the  
discharge grille out from the chassis carefully.  
4. To remove the Evaporator.  
Remove 3 screws securing the evaporator(at the  
left 2EA in the Eva Holder, at the right 1EA).  
When repair, do not damage the Caution label.  
44 Multi type Air Conditioner  
Disassembly  
Unhook the tab on the right inside of the chassis  
at the same time, slightly pull the evaporator  
toward you until the tab is clear of the slot.  
5. To remove the Motor Cover  
Remove 2 securing screw.  
Pull the motor cover out from the chassis  
carefully.  
Motor cover  
6. To remove the Cross-Flow Fan  
Loosen the screw securing the cross-flow fan to  
the fan motor (do not remove).  
Bearing  
Lift up the right side of the cross-flow fan and the  
fan motor, separate the fan motor from the  
cross-flow fan.  
Cross-flow fan  
Remove the left end of the cross-flow fan from  
the self-aligning bearing.  
Service Manual 45  
Schematic Diagram  
Schematic Diagram  
Electronic Control Device  
1. Indoor Unit  
1) Split Type  
46 Multi type Air Conditioner  
Schematic Diagram  
2. Outdoor Unit  
Service Manual 47  
Schematic Diagram  
5 6 1 * 2  
1 u F  
1 u F  
1 M  
4
7 2 * 3  
1 u F  
2 2 2 * 2  
48 Multi type Air Conditioner  
Schematic Diagram  
Wiring Diagram  
1. Room Type Indoor Unit  
2. Outdoor Unit  
Service Manual 49  
Schematic Diagram  
Components Locations  
1. Indoor Unit  
MAIN P.C.B ASM  
1) Split Type  
• TOP VIEW  
PCB :6870A90409B  
ASSY:6871A20771  
6871A20782  
• BOTTOM VIEW  
50 Multi type Air Conditioner  
Schematic Diagram  
2. Display ASSEMBLY  
1) Split Type (6871A20682A)  
Service Manual 51  
Schematic Diagram  
3. Outdoor Unit  
1) Component side  
52 Multi type Air Conditioner  
Schematic Diagram  
2) Solder side  
Service Manual 53  
Troubleshooting Guide  
Troubleshooting Guide  
Refrigeration Cycle Diagram  
Indoor  
Outdoor  
Ø 9.52  
Th1  
Th2  
Th9  
High  
Pressure  
S/W  
Th3  
Ø 9.52  
Th4  
C/V2  
Th7  
C/V1  
Th5  
Th8  
EEV  
EEV  
Th6  
Ø 6.35  
Ø 6.35  
A
c
c
B
Comp  
A
Comp  
Refrigerent Flow  
Cooling  
Th10  
Strainer  
Heating  
LOC.  
Description  
PCB Connector  
CN-TH2(Indoor)  
CN-TH1(Indoor)  
CN-TH1(Indoor)  
CN-TH2(Indoor)  
CN-TH1(Indoor)  
CN-TH1(Indoor)  
CN-TH1(Outdoor)  
CN-TH1(Outdoor)  
CN-TH2(Outdoor)  
CN-TH2(Outdoor)  
Th1 Thermistor for evaporating temperature  
Th2 Thermistor for indoor air temperature  
Th3 Thermistor for evaporating temperature  
Th4 Thermistor for evaporating temperature  
Th5 Thermistor for indoor air temperature  
Th6 Thermistor for evaporating temperature  
Th7 Thermistor for Discharge temperature  
Th8 Thermistor for Discharge temperature  
Th9 Thermistor for outdoor air temperature  
Th10 Thermistor for Condensing temperature  
54 Multi type Air Conditioner  
Troubleshooting Guide  
Self-diagnosis Function  
I Error Indicator  
The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.  
Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.  
If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.  
After error occurrence, if error is released, error LED is also released simultaneously.  
To operate again on the occurrence of error code, be sure to turn off the power and then turn on.  
Having or not of error code is different from Model.  
LED1 LED2  
Indoor Error  
Error code  
Description  
MPS Variable  
LED1  
LED2  
Indoor Status  
00  
01  
02  
05  
06  
07  
10  
No Error  
ON  
Indoor Room Thermistor Error  
Indoor In-Piping Error  
1 time  
2 times  
5 times  
6 times  
7 times  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
Communication Error between In and Out  
Indoor Out-Piping Error  
Differnt mode operation  
Indoor fan motor locked error  
1 times  
Outdoor Error  
Error code  
Description  
MPS Variable  
LED1(Red)  
LED2(Green) Indoor Status  
33  
44  
45  
47  
51  
D-Pipe High(Normal)  
3 times  
4 times  
4 times  
4 times  
5 times  
3 times  
4 times  
5 times  
7 times  
1 times  
OFF  
OFF  
OFF  
OFF  
OFF  
Outdoor Air Thermistor Error(Open/Short)  
Cond Pipe Thermistor Error(Open/Short)  
Const. D-Pipe Thermistor Error(Open/Short)  
Capcity Error(High/Low)  
Service Manual 55  
Troubleshooting Guide  
Cycle Troubleshooting Guide  
Trouble analysis  
1. Check temperature difference between intake and discharge air, and operating current.  
Temp. difference  
Current  
: approx. 0°C(0°F)  
: less than 80% of  
rated current  
All amount of refrigerant leaked out.  
Check refrigeration cycle.  
Temp. Difference  
Operating Current  
Temp. difference  
Current  
: approx. 8°C(14.4°F)  
: less than 80% of  
rated current  
Refrigerant leakage  
Clog of refrigeration cycle  
Defective compressor  
Temp. difference  
Current  
: less than 8°C(14.4°F)  
: near the rated cur-  
rent  
Excessive amount of refrigerant  
Temp. difference : over 8°C(14.4°F)  
Normal  
Notice:  
Temperature difference between intake and discharge air depends on room air humidity. When the room air  
humidity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower  
temperature difference is larger.  
2. Check temperature and pressure of refrigeration cycle.  
Suction pressure  
(Compared with  
the normal value)  
Temperature  
(Compared with  
the normal value)  
Cause of Trouble  
Description  
High  
Defective compressor  
Current is low.  
Higher  
Lower  
Normal  
Excessive amount of  
refrigerant  
High pressure does not quickly  
rise at the beginning of operation.  
Insufficient amount of  
refrigerant(Leakage)  
Clogging  
Current is low.  
Higher  
Notice:  
2
1. The suction pressure is usually 4.5~6.0 kg/cm G at normal condition.  
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with  
putty.  
56 Multi type Air Conditioner  
Troubleshooting Guide  
Electronic Parts Troubleshooting Guide  
Refer to electronic contorol device drawing & schematic diagram.  
The Product doesnt operate at all.  
Trouble 1  
Turn off the main power and wait until LED on outdoor PCB is off.  
Turn on the main power again.  
Does "Beeping" sound is made from the indoor unit?  
NO  
YES  
Primarily, the operating condi-  
tion of Micom is O.K.  
Check the voltage of power(AC208V/AC230V, 60Hz).  
The voltage of main power.  
The voltage applied to the unit.  
The connecting method of Indoor/Outdoor connecting cable (each color)  
The P.W.B. Ass'y  
(Fuse, Noise Filter, Power Transformer, IC01D, IC02D, etc.)  
Check CN-DISP1  
The operation check of the P.C.B. Ass'y  
Specification  
1) AC230V ± 30V  
Remedy  
Procedure  
1) Replace  
1) The input voltage of power trans-  
former.  
: Check the rated voltage  
power transfomer.  
2) 15V ± 1.5V  
2) Replace  
2) The output voltage of power  
transformer.  
power transfomer.  
3) DC12V  
4) DC5V  
3) Replace IC01D.  
4) Replace IC02D.  
5) Replace IC01A.  
3) IC01D(7812)  
4) IC02D(7805)  
5) IC01A(KIA7036)  
5) The voltage of micom pin 29  
: DC4.5V  
Service Manual 57  
Troubleshooting Guide  
Product doesn't operate with the remote controller.  
Trouble 2  
Turn on main power.  
While the compressor has been stopped, the compressor does not operate  
owing to the delaying function for 3 minutes after stopped.  
When the compressor stopped Indoor Fan is driven by a low speed.  
At this point the wind speed is not controlled by the remote controller.  
(When operated in the Sleeping Mode, the wind speed is set to the low speed as force.)  
Caused by other parts except  
Caused by the remote controller.  
the remote controller  
When the mark (  
) is displayed in LCD  
Check the contact of CN-DISP 1 connector  
screen, replace battery.  
When the detect switch (double key) inside the  
remote controller door is fault, it is impossible to  
operate temperature regulating(L / M) and wind  
speed selecting.  
Check DISP PWB Ass'y  
-Voltage between CN1 - : DC +5V  
Check the Display PWB Ass'y  
Check receiver ass'y  
58 Multi type Air Conditioner  
Troubleshooting Guide  
The Compressor/Outdoor Fan are don't operate  
Trouble 3  
Turn on the main power.  
Operate Cooling Mode by setting the disired temperature of the remote controller is less  
than one of the Indoor temperature by 1°C at least.  
When in air circulation mode, compressor/outdoor fan is stopped.  
Check the sensor for Indoor temperature is attatched as close as to be effected by the  
themperature of Heat Exchange (EVA.)  
When the sensor circuit for Indoor temperature and connector are in bad connection or are  
not engaged, Compressor/Outdoor fan is stopped.  
Check the related circuit of R01H(1K), R02H(1K), R03H(1K), R04H(1K), Micom(pin No. 74 ,  
75 , 76 , 77 ).  
Check the Indoor temperature sensor is disconnected or not (about 10K at 25°C).  
Check the Relay(RY-PWR, RY-START) for driving Compressor.  
Check the voltage between brown and blue cable of terminal to connect the Outdoor  
(About AC208V / 230V).  
Check the related circuit of relay in Outdoor PCB Ass'y.  
Check Point  
Comp. ON  
DC 5V  
Comp. OFF  
DC 0V  
Between Micom(No. 50,51) and  
GND  
Between IC01M(No. 10) and  
GND  
DC 1V↓  
DC 12V  
Turn off main power.  
Check the electrical wiring diagram of Outdoor side.  
Check the open or short of connecting wires between Indoor and Outdoor.  
Service Manual 59  
Troubleshooting Guide  
When indoor Fan does not operate.  
Trouble 4  
When indoor Fan does not operate.  
Does the voltage of each terminals of CN-MOTOR CONNECTOR in  
Indoor unit corresponds to values in the Table of page 69  
Does the voltage of terminal of CN-DC/DC CONNECTOR in  
Check connecting condition of the CN-MOTOR CON-  
Indoor unit corresponds to the values in the table of page 56  
NECTOR  
Do the voltage of terminal of  
Check the pattern and the  
CN-DC/DC CONNECTOR in  
condition of Indoor unit PWB  
Outdoor unit corresponds to the  
Ass'y.  
Check the interference of Indoor Fan.  
values in the table of page 56  
NO  
Check the connecting condi-  
Check the patterns and the  
tion and disconnection of  
Check the motor of Indoor Fan  
conditions of outdoor unit  
connecting wires between  
PWB Assy's.  
Indoor and Outdoor unit.  
Indoor Fan may be stopped in the Soft Dry Mode(change to the Cooling Operation Mode).  
Indoor Fan is to be stopped when Indoor pipe(coil) termperature is lower than 79°F.  
(At that times, Defrost indicator is turned on)  
60 Multi type Air Conditioner  
Troubleshooting Guide  
When the louver does not operate.  
When Vertical Louver does not operate.  
Trouble 5  
Confirm that the Vertical Louver is normally geared with the shaft of  
Stepping Motor.  
If the regular torque is detected when rotating the Vertical Louver with  
hands  
Normal  
Check the connecting condition of CN-UP/DOWN Connector  
Check the soldering condition(on PWB) of CN-UP/DOWN Connector  
Check the operating circuit of the Vertical Louver  
+
Confirm that there is DC 12V between pin (RED) of CN-UP/DOWN and  
GND.  
Confirm that there is a soldering short at following terminals.  
- Between 60 , 61 , 62 and 63 of MICOM  
- Between 2 , 3 , 4 and 5 of IC01M  
- Between 12 , 13 , 14 , 15 of IC01M  
- Between 1 , 2 , 3 , 4 and 5 of CN-UP/DOWN  
If there are no problems after above checks  
Confirm the assembly conditions that are catching and interfering parts in  
the rotation radial of the Vertical Louver  
Service Manual 61  
Troubleshooting Guide  
Error Code  
I Trouble Shooting  
Error  
code  
Title  
Cause of error  
Open / Short  
Soldered poorly  
Internal circuit error  
Check point & Normal condition  
Normal resistor : 10K/ at 25°C(77°F) (Unplugged)  
Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)  
01  
02  
06  
Indoor air sensor  
Open / Short  
Soldered poorly  
Internal circuit error  
Normal resistor : 5K/ at 25°C(77°F) (Unplugged)  
Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)  
Indoor inlet pipe sensor  
Indoor outlet pipe sensor  
Open / Short  
Soldered poorly  
Internal circuit error  
Normal resistor : 5K/ at 25°C(77°F) (Unplugged)  
Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)  
10KΩ  
2.5Vdc  
V
Check the resistance / voltage  
Check Point  
1. Unplug the sensor on Indoor unit PCB.  
2. Estimate the resistance of each sensor  
3. If the resistance of the sensor is 10K/5Kat 25°C(77°F), then sensor is normal  
4. If the resistance of the sensor is 0 Kor , then sensor is abnormal. Change the sensor.  
5. Plug the sensor on Indoor unit PCB and Power ON.  
6. Estimate the voltage of each sensor.  
7. If the voltage of the sensor is 2.5Vdc / at 25°C(77°F), then sensor is normal.  
8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. Repair or Change the PCB  
62 Multi type Air Conditioner  
Troubleshooting Guide  
Error  
code  
Title  
Cause of error  
Check point & Normal condition  
Power input AC 230V.(Outdoor, Indoor)  
The connector for transmission is disconnected.  
The connecting wires are misconnected.  
The GND 1,2 is not connected at main GND.  
The communication line is shorted at GND.  
Transmission circuit of outdoor PCB is abnormal.  
Transmission circuit of indoor PCB is abnormal.  
Communication  
(Indoor Outdoor)  
05 / 53  
Communication poorly  
Check Point  
1. Check the input power AC 230V.(Outdoor, Indoor)  
2. Check the communication wires are correctly connected.  
Adjust the connection of wire  
Confirm the wire of "Live", "Neutral".  
3. Check the resistance between communication line and GND.(Normal : Over 2M)  
4. Check the connector for communication is correctly connected.  
5. Check the connection of GND1, GND2, and main GND.  
6. If one indoor unit is operated normally, outdoor PCB is no problem.  
Check the another indoor unit.  
* CH05 is displayed at indoor unit, CH53 is displayed at outdoor unit.  
Service Manual 63  
Troubleshooting Guide  
Error  
code  
Title  
Cause of error  
Check point & Normal condition  
Check the discharge pipe sensor.  
Check the install condition for over load.  
Check the leakage of refrigerent.  
Check the SVC V/V open.  
Discharge sensor  
temp. high  
33  
D-Pipe Temp. High  
COMP OFF  
115°C(239°F)  
LEV OPEN(16PULSE/MIN)  
100°C(212°F)  
95°C(203°F)  
LEV OPEN(10PULSE/MIN)  
NORMAL  
Check Point  
1. Check the install condition for over load.  
2. Check the SVC V/V open.  
3. Check the leakage of refrigerent.  
4. Check the constant compressor.  
Error  
code  
Title  
Cause of error  
Check point & Normal condition  
Over Capacitor com-  
bination  
Check the indoor unit capacity.  
Check the combination table  
51  
Capacitor error  
Check Point  
1. Check the indoor unit capacity.  
2. Check the combination table.  
# In the tropical model case  
single cycle has no error for over capacity.  
64 Multi type Air Conditioner  
Troubleshooting Guide  
Error  
code  
Title  
Cause of error  
Open / Short  
Soldered poorly  
Internal circuit error  
Check point & Normal condition  
Normal resistor : 10K/ at 25°C(77°F) (Unplugged)  
Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)  
44  
45  
47  
Outdoor air sensor  
Open / Short  
Soldered poorly  
Internal circuit error  
Normal resistor : 5K/ at 25°C(77°F) (Unplugged)  
Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)  
Condensor pipe sensor  
D-Pipe sensor  
Open / Short  
Soldered poorly  
Internal circuit error  
Normal resistor : 200K/ at 25°C(77°F) (Unplugged)  
Normal voltage : 4.5Vdc / at 25°C(77°F) (plugged)  
Check the resistance  
Check Point  
1. Estimate the resistance of each sensor.(Unplugged)  
2. Estimate the voltage of each sensor.(Plugged)  
3. If the resistance is 0V or 5Vdc, then sensor is abnormal  
Service Manual 65  
2-way, 3-way Valve  
2-way, 3-way Valve  
2-way Valve (Liguid Side)  
3-way Valve (Gas Side)  
Valve cap  
Hexagonal wrench  
(4mm)  
Open position  
Closed position  
Flare nut  
Flare nut  
Open position  
Pin  
Closed position  
To  
To  
piping  
piping  
Service  
port cap  
Service  
port  
connection  
connection  
To outdoor unit  
To outdoor unit  
Works  
Shaft position  
Shaft position  
Service port  
Shipping  
Closed  
Closed  
Closed  
(with valve cap)  
(with valve cap)  
(with cap)  
Air purging  
Open  
Closed  
Open  
(Installation)  
(counter-clockwise)  
(clockwise)  
(push-pin or with  
vacuum pump)  
1.  
2.  
Operation  
Open  
Open  
Closed  
(with valve cap)  
(with valve cap)  
(with cap)  
Pumping down  
(Transfering)  
Closed  
Open  
Open  
(clockwise)  
(counter-clockwise)  
(connected  
manifold gauge)  
Evacuation  
(Servicing)  
Open  
Open  
Open  
Open  
Open  
Open  
Open  
Open  
Open  
3.  
4.  
(with charging  
cylinder)  
Gas charging  
(Servicing)  
Open  
(with charging  
cylinder)  
Pressure check  
(Servicing)  
Open  
5.  
6.  
(with charging  
cylinder)  
Gas releasing  
(Servicing)  
Open  
(with charging  
cylinder)  
66 Multi type Air Conditioner  
2-way, 3-way Valve  
(1) Pumping down  
Liquid side  
Indoor unit  
Outdoor unit  
Close  
2-Way  
valve  
Gas side  
Open  
3-Way  
valve  
Liquid side  
Indoor unit  
Close  
2-Way  
valve  
Gas side  
Open  
3-Way  
valve  
manifold gauge  
Low-  
handle  
(CLOSE)  
Hi- handle  
(CLOSE)  
Procedure  
6. Operate the air conditioner at the cooling cycle  
1. Confirm that both the gas side and liquid side  
valves are set to the open position.  
2
and stop it when the gauge indicates 1kg/cmg.  
- Remove the valve stem caps and confirm that the  
valve stems are in the raised position.  
7. Immediately set the gas side valve to the closed  
position.  
- Do this quickly so that the gauge ends up indicat-  
- Be sure to use a hexagonal wrench to operate  
the valve stems.  
ing 1kg/  
g.  
8. Disconnect the charge set, and mount the liquid  
side and gas side valve caps and the service port  
nut.  
2. Operate the unit for 10 to 15 minutes.  
3. Stop operation and wait for 3 minutes, then con-  
nect the manifold gauge to the service port of the  
gas side valve.  
- Use torque wrench to tighten the service port nut to  
a torque of 1.8kg.m.(156.2 lbf·in) [4.2kg.m (364.5  
lbf·in)/5.5kg.m (477.4 lbf·in)]  
- Connect the hose of the gauge with the push pin  
to the service port.  
- Be sure to check for gas leakage.  
4. Air purging of the charge hose.  
- Open the Low-handle valve on the gauge  
slightly to air purge from the hose.  
5. Set the liquid side valve to the closed position.  
Be sure to short pressure S/W. otherwise Low pressure S/W detect low pressure skete and stops the compressor.  
Service Manual 67  
2-way, 3-way Valve  
(2) Evacuation  
(All amount of refrigerant leaked)  
Liquid side  
Indoor unit  
Outdoor unit  
Open  
2-Way  
valve  
Gas side  
Open  
3-Way  
valve  
Liquid side  
Indoor unit  
Open  
2-Way  
valve  
Gas side  
Open  
3-Way  
valve  
manifold gauge  
Vacuum pump  
Low-  
handle  
(OPEN)  
Hi- handle  
(OPEN)  
Procedure  
6. Disconnect the charge hose from the vacuum  
pump.  
1. Confirm that both the liguid side valve and gas  
side valve are set to the opened position.  
- Vacuum pump oil.  
If the vacuum pump oil becomes dirty or deplet-  
ed,replenish as needed.  
2. Connect the vaccum pump to the center hose of  
the manifold gauge.  
3. Connect the service port of the gas side valve to  
the low side of the gauge.  
7. Mount the valve caps and the service port caps.  
4. Evacuation for approximately one hour.  
- Confirm that the gauge needle has moved  
toward-76 cmHg (vacuum of 4 mmHg or less).  
5. Close the Low handle of the gauge turn off the  
vacuum pump, and confirm that the gauge needle  
does not move(approximately 5 minutes after  
turning off the vacuum pump).  
68 Multi type Air Conditioner  
2-way, 3-way Valve  
(3) Gas Charging  
(After Evacuation)  
Liquid side  
Indoor unit  
Outdoor unit  
Open  
2-Way  
valve  
Gas side  
Open  
3-Way  
valve  
Liquid side  
Indoor unit  
Open  
2-Way  
valve  
Gas side  
Open  
3-Way  
valve  
manifold gauge  
Charging  
cylinder  
Low-handle  
(OPEN)  
Hi- handle  
(OPEN)  
Check valve  
Procedure  
1. Connect the gauge to the charging cylinder.  
- Connect the charge hose which you disconnect-  
ed from the vacuum pump to the valve at the  
bottom of the cylinder.  
4. Immediately disconnect the charge hose from  
the gas side valve's service port.  
This is different from previous procedures.  
Because you are charging with liquid refrigerant  
from the gas side, absolutely do not attempt to  
charge with larger amounts of liquid refrigerant  
while operating the air conditioner.  
- If you are using a gas cylinder, also use a scale  
and reverse the cylinder so that the system can  
be charged with liquid.  
2. Purge the air from the charge hose.  
-
Open the valve at the bottom of the cylinder and  
press the check valve on the charge set to purge  
the air. (Be careful of the liquid refrigerant). The  
procedure is the same if using a gas cylinder.  
- Stopping partway will allow the gas to be dis-  
charged.  
- If the system has been charged with liquid  
refrigerant while operating the air conditioner  
turn off the air conditioner before disconnecting  
the hose.  
3. Open the low handle on the gauge and charge  
the system with liquid refrigerant.  
- If the system can not be charged with the speci-  
fied amount of refrigerant, it can be charged  
with a little at a time (approximately 150g each  
time) while operating the air conditioner in the  
cooling cycle; however, one time is not suffi-  
cient, wait approximately 1 minute and then  
repeat the procedure(pumping down-pin).  
5. Mount the valve stem nuts and the service port  
nut.  
- Use torque wrench to tighten the service port  
nut to a torque of 1.8 kg.m.(4.2kg.m/5.5kg.m.)  
- Be sure to check for gas leakage.  
Service Manual 69  
Specifications and performance data subject to change without notice.  
HEAT CONTROLLER, INC.  
1900 WELLWORTH AVENUE JACKSON, MICHIGAN 49203  
THE QUALITY LEADER IN CONDITIONING AIR  
05/15/07  

Actron SCAN TOOL CP9110 User Manual
Carrier 40KMQ 301 User Manual
Carrier 48JZ N 024 060 User Manual
Epson Printer FX 890 User Manual
Epson Stylus CX8300 User Manual
Friedrich Air Conditioner WE10 User Manual
Friedrich CP15F10A User Manual
Haier AB244FCAHA User Manual
Havis Shields Slide Out Trunk Tray 2006 2008 Chevrolet Impala C 3311 2 User Manual
HP Hewlett Packard HP PHOTOSMART 2700 User Manual