Haier AB424FCAHA User Manual

CASSETTE TYPE AIR CONDITIONER  
Indoor Unit Operation & Installation  
Manual  
AB094FAAHA  
AB124FAAHA  
AB184FCAHA  
AB244FCAHA  
AB424FCAHA  
AB484FCAHA  
No.0010576722A  
Please read this operation manual before using the air conditioner.  
Please keep this manual carefully and safely.  
Cautions  
Disposal of the old air conditioner  
Consult your local authorities for the name and  
address of the waste materials collecting  
centers and waste paper disposal services  
nearest to your house.  
Before disposing an old air conditioner  
that goes out of use, please make sure it's  
inoperative and safe. Unplug the air  
conditioner in order to avoid the risk of  
child entrapment.  
Safety Instructions and Warnings  
Before starting the air conditioner, read the  
information given in the User's Guide  
carefully. The User's Guide contains very  
important observations relating to the  
assembly, operation and maintenance of the  
air conditioner.  
It must be noticed that air conditioner  
system contains refrigerants, which require  
specialized waste disposal. The valuable  
materials contained in a air conditioner can  
be recycled. Contact your local waste  
disposal center for proper disposal of an  
old air conditioner and contact your local  
authority or your dealer if you have any  
question. Please ensure that the pipework  
of your air conditioner does not get  
damaged prior to being picked up by the  
relevant waste disposal center, and  
contribute to environmental awareness by  
insisting on an appropriate, anti-pollution  
method of disposal.  
The manufacturer does not accept  
responsibility for any damages that may  
arise due to non-observation of the following  
instruction.  
Damaged air conditioners are not to be  
put into operation. In case of doubt, consult  
your supplier.  
Use of the air conditioner is to be carried  
out in strict compliance with the relative  
instructions set forth in the User's Guide.  
Disposal of the packaging of your new  
air conditioner  
Installation shall be done by professional  
people, don't install unit by yourself.  
All the packaging materials employed in  
the package of your new air conditioner  
may be disposed without any danger to the  
environment.  
For the purpose of safety, the air  
conditioner must be properly grounded in  
accordance with specifications.  
The cardboard box may be broken or cut  
into smaller pieces and given to a waste  
paper disposal service. The wrapping bag  
made of polyethylene and the polyethylene  
foam pads contain no fluorochloric  
hydrocarbon.  
Always remember to unplug the air  
conditioner before opening inlet grill. Never  
unplug your air conditioner by pulling on the  
power cord. Always grip plug firmly and  
pull straight out from the outlet.  
All these valuable materials may be taken to a  
waste collecting center and used again after  
adequate recycling.  
1
Cautions  
All electrical repairs must be carried out  
by qualified electricians. Inadequate repairs  
may result in a major source of danger for  
the user of the air conditoiner.  
4. The wiring method should be in line with the  
local wiring standard.  
5. The power cable and connecting cable are  
self-provided. The requirement of the power  
cable:H05RN-F 3G 1.5mm2  
Do not damage any parts of the air  
conditioner that carry refrigerant by  
piercing or perforating the air conditioner's  
tubes with sharp or pointed items, crushing  
or twisting any tubes, or scraping the  
coatings off the surfaces. If the refrigerant  
spurts out and gets into eyes, it may result  
in serious eye injuries.  
The requirement of the connecting cable:  
H05RN-F 2¡`(1.0~1.5)mm2  
All the cables shall have got the European  
authentication certificate.  
6. The breaker of the air conditioner should be  
all-pole switch; and the distance between its two  
contacts should be no less 3mm. Such means for  
disconnection must be incorporation in the fixed  
wiring.  
7. The waste battery shall be disposed properly.  
8. The indoor unit installation height is at least  
2.5m.  
Do not obstruct or cover the ventilation  
grille of the air conditioner. Do not put  
fingers or any other things into the  
inlet/outlet and swing louver.  
Do not allow children to play with the air  
conditioner. In no case should children be  
allowed to sit on the outdoor unit.  
Specifications  
The refrigerating circuit is leak-proof.  
The machine is adaptive in following  
situation  
1. Applicable ambient temperature range:  
Rated Maximum Minimum  
DB C 27  
WB C 19.5  
DB C 35  
WB C 24  
32  
23  
43  
26  
27  
15  
21  
15  
21  
15  
21  
15  
20  
15  
-10  
--  
Indoor  
Cooling  
Heating  
outdoor  
20  
15  
7
DB C  
WB C  
DB C  
WB C  
Indoor  
outdoor  
6
2. If the supply cord is damaged, it must be  
replaced by the manufacturer or its service  
agentor a similar qualified person.  
3. If the fuse on PC board is broken please  
change it with the type of T 3.15A /250VAC.  
2
Cautions  
Safety cautions  
Carefully read the following information in order to operate the airconditioner correctly.  
Below are listed three kinds of Safety Cautions and Suggestions.  
WARNING!  
CAUTION!  
Incorrect operations may result in severe consequences of death or serious injuries.  
Incorrect operations may result in injuries or machine damages; in some cases may  
cause serious consequences.  
INSTRUCTIONS: These information can ensure the correct operation of the machine.  
Be sure to conform with the following important Safety Cautions.  
The Safety Cautions should be at hand so that they can be checked at any time when needed.  
If the conditioner is transferred to the new user, this manual should be as well transferred to the new user.  
WARNING!  
Don't blow the human body with the cooling  
air too long, and don't let the room tempera-  
ture decrease too low  
Please let the dealer be responsible for installing  
the conditioner.  
Incorrect installation may cause water leak, elec-  
trical shock and fire hazard.  
either.  
Otherwise the one  
will feel unpleasant  
or harm ones' health.  
Don't put fingers or any other things into the  
inlet/outlet and swing louver while the condi-  
tioner is in operation.  
Because the highspeed  
fan is very dangerous  
If any abnormal phenomena is found (e. g.  
smell of firing), please cut off the power  
supply immediately, and contact the dealer  
to find out the handling method.  
In such case, to continue  
and may cause injuries.  
using the conditioner will  
damage the conditioner,  
Call the dealer to take measures to prevent the  
refrigerant from leaking.  
switch  
off  
and may cause electrical  
shock or fire hazard.  
If conditioner is installed in a small room be sure  
to take every measure in order to prevent suffoca-  
tion accident even in case of refrigerant leakage.  
When need maintenance and repairment,  
call dealer to handle it.  
Incorrect mainten-  
ance and repairment  
may cause water  
When conditioner is deinstalled or reinstalled  
dealer should be responsible for them.  
Incorrect installation may cause water leaking,  
electrical shock and fire hazard.  
leak, electrical shock  
and fire hazard.  
3
Cautions  
CAUTIONS!  
Don't operate the air-con-  
ditioner with damp hands.  
Conditioner should not be used for any other  
purpose other than airconditioning.  
Don't use air-conditioner for any other special  
purposes, e.g. the preservation and protection  
of food, animals, plants,  
pecision apparatus as well  
as work of art, otherwise  
the qualities of these  
stuffs may be damaged.  
Otherwise will be shocked.  
Only use correctly-typed fuse.  
May not use wire or any other  
materials replacing fuse, other-  
wise may cause faults or fire  
accidents.  
Don't place any burning unit  
in the air flow of air-conditioner,  
which may cause incomplete  
combustion.  
Don't dismantle the outlet of the outdoor unit.  
The exposure of fan is  
very dangerous which  
may harm human be-  
ings.  
No inflammable spray fluid  
should be permitted to be  
placed or used near to air-  
conditioner otherwise may  
cause fire accidents.  
When air-conditioner is co-used with other  
heat-radiator the frequent replacement of  
room atmosphere should be required.  
Inefficient venti-  
lation may cause  
suffocation.  
Air-conditioner should be  
cleaned only after power  
supply is cut off to keep  
from shock or hurt.  
After a long time use of air-conditioner the  
base should be checked for any damages.  
If the damaged base is  
not repaired, the unit  
may fall down and  
Don't clean air-conditioner  
with water.  
Otherwise may cause  
shock.  
cause accidents.  
No goods or nobody is permitted to placed on  
or stand on outdoor unit.  
When use the fumigating insecticide don't  
open air-conditioner.  
The falling of goods and  
people may cause acci-  
dents.  
Otherwise the poisonous chemicals may settle  
in air-conditioner which harm the health of  
chemical-allergic people.  
Pets and plants should not be blowed directly  
in the air flow.  
Otherwise will suffer  
damage.  
4
Cautions  
Installation  
Please ask the dealer or specialist to install, never try by the users themselves. After the installation please  
be sure of the following conditions.  
WARNING !  
Please call dealer to install the air-conditioner.  
Incorrect installation may cause water leaking, shock and fire hazard.  
CAUTION !  
Air-conditioner can't be installed in the envi-  
ronment with inflammable gases because the  
inflammable gases near to air-conditioner may  
cause fire hazard.  
Connect earthing wire.  
Earthing wire should not be con-  
nected to the gas pipe, water pipe,  
lightning rod or phone line, in-  
correct earthing may cause shock.  
Earthing  
Installed electrical-leaking circuit breaker.  
It easily cause electrical shock without circuit  
breaker.  
Use discharge pipe correctly to ensure efficient  
discharge.  
Incorrect pipe use may cause water leaking.  
[Location]  
Air-conditioner should be located in well-vented  
and easily-accessible place.  
As required, take measures against heavy snow.  
Air-conditioner should not be located in the  
following places:  
(a) Places with machine oils or other oil vapours.  
(b) Seaside with high salt content in the air.  
(c) Near to hot spring with high content of sulfide  
gases.  
(d) Area with frequent fluctuation of voltage e.g.  
factory, etc.  
(e) In vehicles or ships.  
[Wiring]  
Air-conditioner should be equipped with special  
power supply wire.  
[Operating noise]  
Choose the following locations:  
(a) Capable of supporting air-conditioner weight,  
don't increase operating noise and vibration.  
(b) Hot vapour from outdoor unit outlet and ope-  
rating noise don't disturb neighbour.  
(f) Kitchen with heavy oil vapour or humidity.  
(g) Near to the machine emitting electric-magnetic  
waves.  
No obstacles around the outdoor unit outlet.  
(h) Places with acid, alkali vapuor.  
TV, radio, acoustic appliances etc are at least 1 m  
far away to the indoor unit, outdoor unit, power  
supply wire, connecting wire, pipes, otherwise  
images may be disturbed or noises be created.  
5
Introduction to Spare Parts  
Discharge unit (built in)  
In cooling operation,  
to discharge the  
water from inside the  
room.  
Drain Hose  
Swing fender  
(located in the outlet)  
Refrigerant pipe  
Cable line  
Earthing line  
Outlet  
Air filter  
(located in the suction grill)  
Suction grill  
Anti-bacteria filter  
Air intake  
Air Outlet  
6
Maintenance  
(B) Wash with water.  
[Clean air filter]  
With too much dust, use soft brush and neutral  
detergent.  
Swing off the water, and then place in cool place.  
When having to clean, don't dismantle  
NOTE  
air-filter,otherwise may cause faults.  
In the environment where there is too  
much dust, air filter should be cleaned  
for more times.  
(about half a year one time)  
1. Open inlet grill  
5. Install air filter  
Press the elliptical "PUSH" knob, the inlet  
grill will automatically drop. (the inlet grill  
is catched with two pothooks)  
(1) Put filter into protruding parts at the top of  
the inlet grill.  
(2) Connect the two pothooks with inlet grill  
See 2  
Press the elliptical knob  
PUSH  
the inlet grill will  
automatically drop  
Pothook  
Open two  
pothooks  
2. Open two othooks  
3. Dismantle air filter  
Connect the two pothooks with inlet grill  
See 1.  
6. Close inlet grill  
[Clean inlet grill]  
Drag the knob of  
the grill back lift  
the filter and take  
down.  
1. Open inlet grill  
Air filter  
Press the elliptical "PUSH" knob, the inlet  
grill will automatically drop. (the inlet grill  
is catched with two pothooks)  
4. Clean  
CAUTION!  
Press the elliptical knob  
PUSH  
the inlet grill will  
automatically drop  
(A) Remove dust with vacuum filter.  
Pothook  
Open two  
pothooks  
7
Maintenance  
2. Take off airfilter  
3. Take of inlet grill  
[Dismantle and install swing  
plate ]  
1. Fix the swing plate at the bottom.  
2. Dismantle the swing plate.  
CAUTION!  
4. Clean  
Use water to clean the plate and don't heavily  
scrub, otherwise the fine hair may fall off.  
Unscrew the screw at both ends of the swing  
plate.  
CAUTION!  
NOTE  
[Dismantle and install swing  
plate ]  
When the filter too much dust  
To spray the special detergent for vent fan or  
utensils.  
3. Install swing plate  
Lightly rotate swing plate to insert the ridge  
at both ends of the outlet into the groove  
and then screw up.  
5. Install inlet grill  
6. Install air filter  
7. Close inlet grill  
see 3  
see "Clean air filter"  
see 1  
[Clean outlet and shell]  
CAUTION!  
Don't use gasoline, benzene, dilutant,  
polishing powder, or liquid inseticide.  
8
Maintenance  
Seasonal Reserve  
Post-season Care  
Operate the unit with FAN mode on a fair day for about half  
a day to dry the inside of the unit well.  
Stop operation and turn off the power supply switch .Electric  
power is consumed even the air conditioner is in stop.  
Clean the air filter, indoor unit and outdoor unit,and cover  
the unit with dustcoat.  
Pre-season Care  
See that there is no obstacles blocking the air  
inlet and air outlet of both indoor and outdoor  
unit to avoid reduce the working efficiency.  
Be sure to install the air filter, ensure that the air filter is not dirty. Otherwise may result in  
machine damages or cause malfunciton due to dust inside the unit  
To prevent compressor when start in HEAT mode,  
please cut in the power supply switch 12 hours  
before starting run,furthermore, always keep the  
power supply switch on during the using senson.  
NOTE  
1. The inner part of indoor unit must be cleaned. Consult dealer, because clean must be done by  
technician.  
In cooling operation, discharging system discharge water in room.  
2.  
9
Trouble Shooting  
The followings are not malfuncition  
When the air conditoner is started, when the  
compressor starts or stops during operation  
or when the air conditioner is stopped,it som-  
etimes sounds “ Bi- Bi-” or “Godo-Godo”. It is  
the flowing sound of the refrigerant , not a  
malfunction.  
Water flowing sound is heard  
Hua  
Hua  
This is caused by heat expansion or contra-  
ction of plastics  
Cracking sound is heard  
It smells.  
Air blown out from the indoor unit sometimes  
smells. The smell results from smells of  
furniture, paint , tobacco absorbed by indoor  
unit.  
During operation, white fog comes out of  
indoor unit.  
When in COOL or DRY mode, a thin water  
fog can be seen blown out of unit ,this is the  
condensed fog because the suddenly cooled  
indoor air is blown out.  
To prevent frost from being accumulated on the  
indoor unit heat exchanger, it sometimes auto-  
matically switched into the FAN mode,but it will  
soon back to the cooling mode.  
Automatically switch into FAN mode during  
cooling.  
The air conditioner cannot be restarted soon  
after it stops.  
Air conditioner does not start?  
This is because of the self-protection function  
of the system, therefore,it cannot be restarted  
for about three minutes after it stops.  
Please wait for  
three minutes  
10  
Trouble Shooting  
Air does not blow or the fan speed cannot be  
changed during drying.  
In DRY mode, when room temperature  
becomes 2 C higher than temperature setting,  
unit rill run intermittently at LO speed regardless  
of FAN setting  
This happens when the frost accumulated on  
the outdoor unit is removed (during defrosting  
operation).  
Water or vapor generated from the outdoor  
unit during heating.  
Defrosting operation  
To get ride of the excess heat, indoor fan will  
continue running for a while after unit autom-  
atically stops.  
During heating,indoor fan is still running even  
unit is stopped.  
Please check the following things about your air conditioner before making a  
service call.  
Unit fails to start.  
Is the earth leakage breaker  
in action ?  
Is city supply power normal ?  
Is the power supply switch on ?  
ON  
OFF  
Power supply switch is not in  
ON position.  
Be sure to turn off the power  
supply switch immediately and  
contact the sales dealer.  
11  
When Trouble Happens  
Insufficient cooling or heating  
The operation controller  
adjusted as required  
Air filter too dirty ?  
Horizontal swing louver  
upward ? (in HEAT mode)  
Any obstacle exists at the air  
inlet or outlet?  
Door or window left opened ?  
Insufficient cooling  
Too crowed in the room ?  
Sunlight direct into the  
room ?  
Any other heat sources in the  
room?  
Cooled air blown out ( when heating)  
When the air conditioner does not operate properly after  
you have checked the above-mentioned items or when  
following phenomenon is observed,stop the operation of  
the air conditioner and contact your sales dealer.  
1)The fuse or breaker often shuts down.  
2)Water drops off during cooling or drying operation.  
3)There is an irregularity in operation or abnormal sound that  
is audible.  
12  
When Trouble Happens  
1. Error display  
Indoor unit malfunction display code  
Indoor unit malfunction  
Float switch or water motor abnormal  
Outdoor unit abnormal  
Display code  
Indoor unit malfunction  
Display code  
E7  
E0  
E1  
The communication with electronic  
expansion box is abnormal  
The communication between the  
wire remote controller and indoor  
unit control board is abnormal  
E8  
E3  
Liquid temperature sensor is abnormal  
Gas temperature sensor is abnormal  
Indoor unit adress abnormal  
(Firstly you saw E5 in controller LCD,  
and then the failure code is changed  
from E5 to E9)  
E4  
E5  
The communication between indoor  
and outdoor unit is abnormal  
E9  
E0  
Water temp. sensor is abnormal (Only  
used for the twin energy source function)  
Indoor unit EEPROM data is abnormal  
E6  
Remote controller Timer and Operation indicator malfunction code  
When the unit running, Timer indicator flash stand for indoor unit malfunction  
Timer indicator  
Indoor unit malfunction  
Flashing times  
The liquid tube temperature sensor is abnormal  
The gas tube temperature sensor is abnormal  
Flashing once  
Flashing twice  
Flashing 3 times The environment temperature sensor is abnormal  
Flashing 4 times The communication with outdoor unit is abnormal  
The ommunication with the electronic expansion valve control board is abnormal  
Flashing 5 times  
Flashing 10 times  
Flashing 11 times  
Indoor unit PG fan motor is abnormal  
Indoor unit water overflow or float switch is abnormal  
Flashing 12 times  
Flashing 15 times  
Indoor unit EEPROM data is abnormal  
Water temp. sensor is abnormal£¤Only used for the twin energy source function£'  
Outdoor unit malfunction display code  
When the wire remote controller display E1,Can check the outdoor unit control board LED1 or outdoor  
unit malfunction display code to sure outdoor unit malfunction.  
When the operation indicator flashing stand for outdoor unit malfunction,Operation indicator flashing  
times can't determinant outdoor unit malfunction ,You must check the outdoor unit control board LED1  
flashing times or outdoor unit malfunction display code to sure outdoor unit malfunction.  
Others malfunction manual plese read the outdoor unit manual.  
Please keep this manual carefully and safely.  
13  
Customer Need-to-know  
Customer Need-to-know  
Please install the air conditioner according to the requirements specified in this manual to ensure  
the air conditioner work well.  
Be careful not to scratch the surface of the case during moving the air conditioner.  
Please keep the installation manual for future reference when maintenance and changing installation place.  
After installation ,please use the air conditioner according to the specification in the operation  
manual.  
Using Directions  
Avoid direct sunlight and airflow  
Adjust suitable airflow direction  
Keep the proper indoor temperature.  
Too cool or hot is not good for your health.  
Furthermore,it will result in excessive  
consumption of electric power.  
Effectively use timer.  
Using TIMER mode, you can make the room  
temperature reach a suitable temperature when  
you wake up or go back home.  
Optimal  
temper-  
ature  
ATTENTION: after finishing installation,confirm no refrigerant leakage.  
14  
Installation Procedure  
Installation tools  
Following in the list are the accessories  
supplied with the unit,which can be used  
as required  
The installation tools listed in the  
following sheet can be used as required.  
1. Screw driver  
2. Hacksaw  
Accessory parts  
No.  
1
Qty.  
3. Drill with a diameter of 60mm  
4. Inner hexagon spanner,shifting  
spanner  
5. Spanner (14, 17, 19,24,27mm)  
6. Pipe cutter  
7. Pipe expander  
8. Knife  
9. Pincers  
1
2
Remote controller  
Battery  
2
3
Wire clamp  
4
Heat  
insulation  
sheathing  
1+1  
4
10. Leakage detector or soapy water  
11. Band tape  
12. Scraper  
1
Accesories  
5
6
7
1+1  
1
Screw cap  
13. Refrigerant oil  
R e m o t e  
controller  
bracket  
Standard accessories  
The following parts mentioned in this  
manual are the installation accessories  
we prepared.  
Symbol  
Parts Name  
A
B
C
D
E
F
Adhesive tape  
Pipe clamp  
Connecting hose  
Drainage hose  
Non-hydroscopic  
heat insulating material  
Gypsum powder  
15  
Installation Procedure  
To ensure proper installation, read "Cautions" carefully before working. After  
installation, start the unit correctly and show customers how to operate and  
maintain the unit.  
CAUTIONS:  
Meanings of Warning and Cautions:  
Warning! Serious injury or even death might happen, if it is not observed.  
Caution! Injury to people of damages to machine might happen, if it is not observed.  
WARNING!  
Installation shall be done by professional people, don't install unit by yourself. Incorrect installation will  
cause water leakage, electric shock or fire.  
Install unit as per the Manual. Incorrect installation will cause water leakage, electric shock or fire  
accident.  
Be sure to use specified accessaries and parts. Otherwise, water leakage, electric shock, fire accident or  
unit falling down may happen.  
Unit should be placed on a place strong enough to hold the unit. Or, unit will fall down causing injuries.  
When install the unit, take in consideration of storms, typhoom, earthquake. Incorrect installation may  
cause unit to fall down.  
All electric work shall be done by experienced people as per eocal code, regulations and this Manual.  
Use exclusive wire for the unit. Incorrect installation or undersized electric wire may cause electric  
shock or fire accident.  
All the wires and circuit shall be safe. Use exclusive wire firmly fixed. Be sure that external force  
will not affect terminal bolck and electric wire. Poor contact and installation may cause fire accident.  
Arrange wire correctly when connectin indoor and outdoor power supply. Fix terminal cover firmly to  
avoid overheat, electric shock or even fire accident.  
In case retrigerant leakage occurred during unit installation, keep a good ventilation in the room.  
Poisonous gas will occur when meet with fire.  
Check the unit upon installation. Be sure there is no leakage. Refrigerant will induce poisonous gas  
when meet heat source as heater, oven, etc.  
Cut power supply before touching terminal bolck.  
CAUTION!  
Unit shall be grounded. But grounding shall not be connected to gas pipe  
water pipe, telephone line. Poor grounding will cause electric shock.  
Be sure to install a leakage breaker to avoid electric shock.  
Earthing  
Arrange water drainage according to this Manual. Cover pipe with insulation materials in case  
dew may occur. Unproper installation of water drainage will cause water leakage and wet your furniture.  
To maintain good picture or reduce noise, keep at least 1 m from T.V. radio, when install indoor and ou-  
tdoor unit, connecting wire and power cable. (If the radio wave is relatively strong, 1 m is not enough  
to reduce noise).  
Don't install unit in following places:  
(a) Oil mist or oil gas exists, such as kitchen, or, plastic parts may get aged, or water leakage.  
(b) Where there is corrosive gas. Copper tube and welded part may be damaged due to corrosion,  
causing leakage.  
(c) Where there is strong radiation. This will affect unit's control system, causing malfunction of the unit  
(d) Where flamable gas, dirt, and volatile matter (thinner, gasoline) exist, These matter  
might cause fire accident.  
Refer to paper pattern when installing unit.  
Cautions for the installation personnel  
Don't fail to show customers how to operate unit.  
16  
Installation Procedure  
1
. BEFORE INSTALLATION  
<Don't discard any accessories until completed>  
Determine the way to carry unit to installation place.  
Don't remove packing until unit reaches installation place.  
If unpacking is unavoidable, protect unit properly.  
2
. SELECTION OF INSTALLATION PLACE  
(1) Installation place shall meet the following and agreed by customers:  
Place where proper air flow can be ensured.  
No block to air flow.  
Water drainage is smooth.  
Place strong enough to support unit .  
Place where inclination is not evident on ceiling.  
Enough space for maintenance.  
Indoor and outdoor unit piping length is within limit. (Refer to Installation Manual for outdoor unit.)  
Indoor and outdoor unit, power cable, inter unit cable are at least 1 m away fromT.V. radio. This is helpful  
to avoid picture disturbance and noise. (Even if 1 m is kept, noise can still appear if radio wave is strong)  
(2) Ceiling height  
Indoor unit can be installed on ceiling of 2.5-3m in height. (Refer to Field setting and Installation Manual of  
ornament panel.)  
(3) Install suspending bolt. Check if the installation place is strong enough to hold weight. Take necessary  
measures in case it is not safe. (Distance between holes are marked on paper pattern. Refer to paper pattern  
for place which need be reinforced)  
Installation space  
Air outlet  
Air outlet  
Air outlet  
1500 Over  
Air outlet  
1500 Over  
Air inlet  
Air inlet  
1500 Over  
1500 Over  
AB484FCAHA  
AB244FCAHA  
AB424FCAHA  
AB184FCAHA  
AB094FAAHAAB124FAAHA  
17  
Installation Procedure  
3
3. PREPARATION FOR THE INSTALLATION  
(1) Position of ceiling opening between unit and suspending bolt.  
AB184FCAHAAB244FCAHA  
AB424FCAHAAB484FCAHA  
(Ceiling opening)  
860-890  
(Distance between suspending bolts)  
780  
Refrigerant pipe  
Suspending bolts  
*
680  
(Distance between suspending bolts)  
840(Indoor unit)  
890(Ceiling opening)  
*
950(Ornament panel)  
AB094FAAHAAB124FAAHA  
A
807.6  
761  
Suspending bracket  
700  
Ceiling  
A
Note:  
Dimension of ceiling opening marked with can be as  
*
large as 910mm, but the matching part of ceiling with  
ornament panel shall be over 20mm.  
712.6  
831  
860(GRILLE)  
20 Over  
(2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.)  
Refer to paper pattern for dimension of ceiling hole.  
Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before installation.  
Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent vibration.  
Contact your real estate dealer  
(3) Install a suspending bolt.  
(Use a M10 bolt)  
To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For new  
ceiling, use built-in type bolt or parts prepared in the field.  
Before going on installing adjust space between ceiling.  
<Installation example>  
Roof  
Anchor bolt  
Long nut  
Suspending bolt  
Note: All the above mentioned parts shall be prepared in field.  
Ceiling  
18  
Installation Procedure  
4
. INSTALLATION OF INDOOR UNIT  
In the case of new ceiling  
(1) Install unit temporarily  
Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket.  
(2) As for the dimensions of ceiling hole, see paper pattern. Ask your real estate dealer for details.  
Center of the hole is marked on the paper pattern.  
Center of the unit is marked on the card in the unit and on the paper pattern.  
5
6
Mount paper pattern onto unit using 3 screws . Fix the corner of the drain pan at piping outlet.  
< After installation on the ceiling >  
(3) Adjust unit to its right position. (Refer to preparation for the installation-(1))  
(4) Check unit's horizontal level.  
Water pump and flating switch is installed inside indoor unit, check four corners of the unit for its level  
using horizontal compartor or PVC tube with water. (If unit is tilting against the direction of water drainage,  
problem may occur on floating switch, causing water leakage.)  
(5) Remove the washer mounting  
(6) Remove the paper pattern.  
2
, and tighten the nut above.  
Nut (Prepare in feild)  
Washer (Prepared in feild)  
In the case of ceiling already exists  
(1) Install unit temporarily  
Put suspending bracket on the suspending bolt.  
Be sure to use nut and washer at both ends  
of the bracket. Fix the bracket firmly.  
Suspending bolts  
(2) Adjust the height and position of the unit.  
(Refer to preparation for the installation (1) ).  
Fasten (double nuts)  
(3) Proceed with  
and  
of "In the case of new ceiling".  
4
3
Insert  
Washer fixing pad  
(prepared in feild)  
[ secure the washer firmly]  
Level  
Polythene pipe  
Screws at the piping outlet is fixed at the corner  
of drain pan.  
Center of ceiling hole Paper pattern  
Paper pattern  
5
Screw (accessory)  
Screw (accessory)  
[Fix the paper pattern]  
19  
Installation Procedure  
(As for outdoor piping, please refer to installation Manual of outdoor unit.)  
Outdoor is precharged with refrigerant.  
5. REFRIGERANT PIPING  
5
Be sure to see the Fig.1, when connecting and removing piping from unit.  
For the size of the flare nut, please refer to Table 1.  
Apply refrigerant oil at both inside and outside of lflare nut. Tighten it band tight 3-4 turns then tighten it.  
Use torque specified in Table 1. (Too much force may damage flare nut, causing gas leakage).  
Check piping joints for gas leakage. Insulate piping as shown in Fig. below.  
Cover joint of gas piping and insulator  
with seal.  
Table 1  
7
Tighten  
torque  
Pipe  
size  
Medium size seal pad 11 (accessory)  
Flare shape  
A(mm)  
8.3~8.7  
Apply refrigerant oil  
(Cover the piping joint  
with seal pad.)  
.
.
1420~1720N cm  
(144~176kgf cm)  
6.35  
Torque spanner  
Clamp 3  
.
3270~3990N cm  
9.52  
12.0~12.4  
18.6~19.0  
R0.4 ~ 0.8  
2
.
(333~407kgf cm)  
45  
8
7
Insulator (accessory)  
(For liquid pipe)  
.
spanner  
6180~7540N cm  
15.88  
19.05  
.
(630~770kgf cm)  
Insulator (accessory)  
(For gas pipe)  
Piping joing  
Flare nut  
.
9720~11860N cm  
Gas pipe  
Liquid pipe  
22.9~23.3  
.
(990~1210kgf cm)  
6
. INSTALLATION OF WATER DRAINAGE PIPE  
(1) Install water drainage pipe  
Pipe dia, shall be equal or larger than that of unit piping.(pipe of polyethene; size: 25mm; O.D:32mm)  
Drain pipe should be short, with a downward slope at least 1/100 to prevent air bag from happening.  
If downward slope can't be made, take other measures to lift it up.  
Keep a distance of 1-1.5m between suspending brackets, to make water hose straight.  
1-1.5m  
Slope over 1/100  
Use the self-provided stiff pipe and clamp with unit. Insert water pipe into water plug until it reaches the  
1
white tape. Tighten the clip until head of the screw is less than 4mm from hose.  
Wind the drain hose to the clip using seal pad 9 .  
Large size seal pad  
(accessory)  
10  
Insulate drain hose in the room.  
Clamp  
Clamp  
(accessory)  
Tape (White)  
Self-provided stiff pipe  
<Cautions for the drain water lifting pipe>  
4mm below  
Installation height shall be less than 280mm.  
There should be a right angle with unit, 300mm from unit.  
Suspending bracket  
1~1.5m  
300mm below  
Self-provided stiff pipe  
(accessory)  
Drain hose  
(accessory)  
drain water lifting pipe  
Clamp  
(accessory)  
(Note)  
The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it.  
If several water hoses join together, do as per following proceedures.  
Connect water hoses with a T joint.  
Specifications of the water hoses shall meet the requirements for the unit running.  
20  
Installation Procedures  
7. INSTALLING THE DECORATED BOARD ON THE BODY OF INDOOR UNIT  
7
As shown in Fig. 1, make the wind deflector motor of the decorated board face to the orifice of the indoor  
6
unit, and then mount the decorated board onto the body of the indoor unit.  
1
swing ring  
orifice location  
2
2
deflector motor  
3
4
Fig.1  
Mounting the decorated board:  
a. Hang temporarily the swing rings(2 pcs) opposite to the deflector motor of the decorated board on the ring  
stators of the swing rings of the indoor unit;  
b. Hang temporarily the other swing rings on the ring stators of the swing rings of the indoor unit (take care  
not to get the lead wire of the deflector motor into the sealing);  
c. Screw all 4 hex head screws under the rings about 15mm to lift the board;  
d. Turn and adjust the decorated board in the direction of arrow as shown in Fig. 4 until it covers the hole of  
the ceiling.  
e. Fasten the screw to keep the thickness of the sealing between the decorated board and the unit body within  
5-8mm, as shown in Fig. 2.  
sealing  
indoor unit  
ceiling material  
5-8mm  
decorated board  
Fig.2  
f. Mount the wiring of the decorated board according to the mounting drawing attached tothe inside of the  
machine;  
g. Check with the control if the mounting is correct and make sure if the machine work snormally;  
h. Mount the air inlet grid and angle covers.  
21  
Installation Procedures  
Attention  
Inappropriate tightening of screws might cause the faults as  
shown in Fig. 3.  
Fig.3  
Tighten the screws properly.  
air leakage  
If there is still a gap between the decorated board and the ceiling  
after tightening the screws, please readjust the height of the body  
of the indoor unit. (Fig. 4)  
leakage  
from roof  
If the indoor unit keeps the horizontal level and the drainpipe  
can’t be influenced, adjust the height of the body of the indoor  
unit from the holes on the angles of the decorated board.  
pollution  
vapour condensate drops  
Fig.4  
any gap is not allowed  
Wiring of Decorated Board  
a. Connect it to the connector of the wind deflector motor lead on the decorated board (Fig. 5);  
b. Connect it to the receiving terminal of remote control on the decorated board.  
side of decorated board  
electrical cabinet  
AB184~484FCAHA  
<circuit diagram>  
(different from the actual condition)  
side of indoor unit  
Fig.5  
22  
Installation Procedures  
Mounting Air Inlet Grid and Angle Covers  
(1) Mounting the air inlet grid:  
Take care not to wind the lead of the wind deflector motor during mounting the air inlet grid.  
(2)For Model AB184-484FCAHA units, the angle covers should be mounted on the angles.  
¢
¢
Tie the thread of the angle cover onto the cleat on the decorated board as shown in Fig. 6.  
Mount the angle cover onto the decorated board (as shown in Fig. 7).  
cleat  
Slide the 5 locks to mount angle covers  
to fit the holes on decorated board  
Fig.6  
Fig.7  
£¡Attention  
For proper drainage, the drainpipes should be connected according to the installation manual. Heat  
preservation should be performed as to prevent condensing. Improper connections may cause the water  
leakage.  
Requirements:  
The drainpipe of the indoor unit should be heat-insulated.  
Heat insulation should be treated for the connection with the indoor unit. Improper heat insulation may cause  
condensing.  
The drainpipe with the down gradient of over 1/100 can’t be in the S shape, or abnormal sound can be caused.  
The lateral length of the drainpipe should be kept with 20m. Under the condition of long pipes, supports can  
be provided every 1.52m as to avoid unevenness.  
The central piping should be connected according the following drawing.  
Take care not to apply external force on the connection of the drainpipes.  
1.5m~2m  
support bracket  
as big as possible (about 10 CM)  
s-shape elbow  
heat  
down gradient  
VP30  
down gradient  
over 1/100  
insulating over 1/100  
material  
23  
Installation Procedures  
Piping Materials & Heat Insulating Materials  
Piping  
Hard PVC tube VP31.5mm  
(inner bore)  
Vesicant polythene  
thickness: over 7mm  
As to prevent condensation, heat insulating  
treatment should be performed. The heat  
insulating treatment for piping should be done  
respectively.  
Material  
Heat Insulating  
Material  
Hose  
The attached hoses can be used to adjust the eccentricity and angle of the hard PVC tube.  
Stretch the hose directly to make connections as to avoid distortion. The soft end of the hose should be  
positioned with a clamp.  
The hose should be used in the lateral direction.  
eccentricity adjustment (max.20mm)  
hose clamp  
hose  
45obending (max.)  
hose  
indoor unit  
Heat Insulating Treatment:  
Wrap the connection between the clamp and the root segment of the indoor unit without any gap with heat  
insulating materials as shown in the drawing  
hose  
hose clamp  
Lifting Drainpipe  
The drainpipe can be lifted 360mm.  
When the down gradient of the drainpipe can’t be ensured, after upright  
lifting, the drainpipe is in the down slope.  
heat insulating  
material  
horniness pvc pipe  
attached heat  
insulating material  
Confirming Drainage  
The drainage should be confirmed during the test run to make sure that there is  
leakage at the connection.  
The confirmation of drainage should be also performed during the installation in  
the winter season.  
Fill water from the outlet or the specified position and confirm the drainage.  
Fill 600cc water with a hose from the outlet or the specified location on the machine.  
Add the water slowly. Don’t add water to the motor of the drainage pump.  
100mm  
below  
indoor unit  
under the ceiling  
After mounting the electrical system, do refrigerating operation and meanwhile  
add water and check.  
If the electrical installation hasn’t been completed, pull out the terminal(2P)  
of the floater switch on the electrical cabinet. After confirming the drainage,  
connect the terminal of the floater switch and run the drainage pump for 5  
minutes until it stops automatically.  
joint of drainpipe  
Confirm the sound of the motor:  
Confirm the sound of the motor of the drainage pump and meanwhile check  
the drainage.  
24  
Installation Procedure  
Tubing Permissible Length & Height Difference  
Please refer to the attached manual of outdoor units.  
Tubing Materials & Specifications  
AB094~  
124FAAHA  
AB184~  
244FCAHA  
AB424~  
484FCAHA  
Model  
Gas pipe  
Liquid pipe  
12.70  
6.35  
15.88  
9.52  
19.05  
9.52  
Tubing Size  
(mm)  
Phosphor deoxybronze seamless pipe (TP2) for  
air conditioner  
Tubing  
Material  
Refrigerant Filling Amount  
Add the refrigerant according to the installation instruction of outdoor unit. The addition of R22  
refrigerant must be performed with a measure gage to ensure the specified amount while compressor  
failure can be caused by filling too much or little refrigerant.  
Connecting Procedures of Refrigerant Tubing  
Proceed the flare tube connecting operation to connect all the refrigerant tubes.  
Dual wrenches must be used in the connection  
of indoor unit tubing.  
Mounting torque refers to the right table  
Outer  
Mounting  
Torque (N-m)  
Increase mounting  
Torque (N-m)  
Diameter of  
Tubing (mm)  
11.8(1.2kgf-m)13.7(1.4kgf-m)  
6.35  
9.52 24.5(2.5kgf-m)29.4(3.0kgf-m)  
12.70 49.0(5.0kgf-m)53.9(5.5kgf-m)  
15.88 78.4(8.0kgf-m)98.0(10.0kgf-m)  
19.05 98.0(10.0kgf-m1)17.7(12.0kgf-m)  
wrench  
Connecting  
circular terminals:  
Cutting and Enlarging  
Connecting  
Cutting or enlarging pipes should be proceeded  
by installation personnel according to the  
operating criterion if the tube is too long or flare  
opening is broken.  
1. Connecting circular terminals:  
The connecting method of circular terminal is  
shown in the Fig. Take off the screw, connect it  
to the terminal tier after heading it through the  
ring at the end of the lead and then tighten it.  
2.Connecting straight terminals:  
Vacuumizing  
Vacuumize from the stop valve of outdoor units  
with vacuum pump. Refrigerant sealed in indoor  
machine is not allowed to use for vacuumization.  
The connection methods for the circular terminals  
are shown as follows: loosen the screw before  
putting the line terminal into the terminal tier,  
tighten the screw and confirm it has been clamped  
by pulling the line gently.  
Open All Valves  
Open all the valves of outdoor units. [NB: oil  
balancing stop valve must be shut up completely  
when connected one main unit.]  
3.Pressing connecting line  
After connecting line is completed, press the  
connecting line with clips which should press on  
the protective sleeve of the connecting line.  
Checkup for Air Leakage  
terminal tier  
wrong  
pressing  
correct  
pressing  
Check if there is any leakage at the connecting part  
and bonnet with hydrophone or soapsuds.  
pressing clip  
25  
Electrical Wiring  
Warning  
Electrical construction should be made with specific mains circuit by the qualified personnel according  
to the installation instruction. Electric shock and fire may be caused if the capacity of power supply  
is not sufficient.  
During arranging the wiring layout, specified cables should be used as the mains line, which accords  
with the local regulations on wiring. Connecting and fastening should be performed reliably to avoid  
the external force of cables from transmitting to the terminals. Improper connection or fastness may  
lead to burning or fire accidents.  
There must be the ground connection according to the criterion. Unreliable grounding may cause  
electrical shocks. Do not connect the grounding line to the gas pipe, water pipe, lightening rod and  
telephone line.  
Attention  
Only copper wire can be used. Breaker for electric leakage should be provided, or electric shock may  
occur.  
The wiring of the mains line is of Y type. The power plug L should be connected to the live wire and  
plug N connected to null wire while should be connected to the ground wire. For the type with auxiliary  
electrically heating function, the live wire and the null wire should not be misconnected, or the surface  
of electrical heating body will be electrified. If the power line is damaged, replace it by the professional  
personnel of the manufacturer or service center.  
The power line of indoor units should be arranged according to the installation instruction of indoor units.  
The electrical wiring should be out of contact with the high-temperature sections of tubing as to avoid  
melting the insulating layer of cables, which may cause accidents.  
After connected to the terminal tier, the tubing should be curved into be a U-type elbow and fastened  
with the pressing clip.  
Controller wiring and refrigerant tubing can be arranged and fixed together.  
The machine can’t be powered on before electrical operation. Maintenance should be done while the  
power is shut down.  
Seal the thread hole with heat insulating materials to avoid condensation.  
Signal line and power line are separately independent, which can’t share one line. [Note: the power line,  
connecting line, signal line are provided by users. Parameters are shown as below: 3×(1.0-1.5) mm2;  
parameters for signal line: 2×(0.75-1.25)mm2( shielded line)]  
Supply Wiring Drawing  
AU52LFIAHA  
OUTDOOR UNIT TERMINAL BLOCK  
communication  
N
S
T
L m 1  
L m 2  
R
C2  
C1  
U
W
V
3N~,380-400V,50 /60Hz  
POWER SUPPLY:  
CM  
Compressor  
AB094FAAHA  
AB124FAAHA  
AB184FAAHA  
AB244FAAHA  
AB424FAAHA  
AB484FAAHA  
INDOOR UNIT TERMINAL BLOCK  
1
2
3
C2  
R
C1  
W
B
R
Y/G  
R
POWER SUPPLY:1PH,220-230V,50/60Hz  
communication  
N o t e :  
1 : L ( b l a c k )  
2 : N ( w h i t e )  
3 : C ( r e d ) - - - - I t ' s n o u s e f o r B u i l t i n E E V Ty p e o n t h e i n d o o r u n i t  
.
26  
Electrical Wiring  
Field setting  
Field setting the unit number  
Indoor unit number setting  
Indoor unit number setting switch and confirmation of the settings.  
There is a 4-position dial switch for setting the indoor unit number and fan speed level on the computer board of the indoor unit.  
Setting way is as follows:  
Before connecting the power supply, please set the indoor unit number manually according to the following table  
Matrix of the dial switch and indoor unit number  
Position 1 Position 2 Position 3 Representing unit number  
SW01  
Example:  
ON  
0
0
0
1
: 0  
1
0
0
1
0
0
2
3
: 1  
1
0
1
0
1
1
0
0
1
1
0
1
1
1
1
4
5
6
OFF  
0
1
0
1
7
8
1
The first bit of SW02 and SW03 is used to choose  
wired control or remote control type .  
“ON”means that the unit with wired controller .And  
“OFF”is remote controller.  
SW02  
Example:  
ON ON  
Pos.2 Pos.3 Pos.4  
Pos.1  
2
3
The second bit of SW02 is used to choose built-in or  
outside electronic expansion valve setting.  
“ON” means built-in type.And "OFF"means outside type.  
Setting for No. 3 indoor unit  
Pos.2  
ON  
Pos.1  
SW03  
ON  
"ON" means that in heating mode the  
indoor unit fan speed can be choosed to  
middle and low level. "OFF" means that  
the indoor unit fan speed can be choosed  
to high, middle and low level.After  
producing in plant , the position is "OFF".  
The second bit of SW03 is used to select the twin energy  
source function.  
"ON":The unit without TES function.  
"OFF":The unit can be used as TES function.  
When it is used for TES function ,the water tempeture  
sensor is available .  
Example:  
Pos.2  
Pos.1  
Auto restart (to be applied for a necessary situation)  
:
After the Auto restart is set, if power failure suddenly occurs while the air conditioner is working, it will resume the  
previous working state when the power is supplied again.  
*The setting method of auto restart function of wired remote control model or wired control+ remote control model:press  
the [sleep] button of the wired control or remote control 10 times within 5 seconds and after the buzzer rings 4 times,the  
air conditioner will enter the state of auto restart function.  
The cancel method :press the [sleep] button of the wired control or remote control 10 times within 5 seconds and after the  
buzzer rings 2 times, the Auto restart function will be cancelled.The setting method of wireless remote control:press the  
[swing] button of the remote control 10 times within 5 seconds and after the buzzer rings 4 times,the air conditioner  
will enter the state of auto restart function;  
The cancel method :press the [swing] button of wireless remote controller 10 times within 5 seconds and after the buzzer  
rings 2 times, the Auto restart function will be cancelled;  
*The setting method of wireless remote control:press the [swing] button of the remote control 10 times within 5 seconds  
and after the buzzer rings 4 times,the air conditioner will enter the state of auto restart function;  
The cancel method :press the [swing] button of wireless remote controller 10 times within 5 seconds and after the buzzer  
rings 2 times, the Auto restart function will be cancelled;  
Notes: When a power failure suddenly occurs during the air conditioner is working after the Auto restart is set, if the air  
conditioner will not be used for a long time, please cut off the power supply to prevent its operation from being resumed  
after the power is supplied again, or press the "Switch On/Off" button after the power comes again.  
27  
Electrical Wiring  
The unit has temperature compensation function.  
(Only used for remote controller)  
You can use [swing] button of the remote controller to set or cancel temperature compensation function.  
(1) About temperature compensation function setting  
* The setting method for heating mode:  
press [ON/OFF] button of the remote controller to start the indoor unit, setting temperature: 24¡ , press [swing] button 7  
times in 5 seconds, the buzzer will ring twice, and enter heating temp. compensation mode.  
set compensation temp. , if the set temp.is 25¡ , the compensation temp. is +1¡ , you can set it in range of 0¡ to +6¡  
*The setting method for cooling mode:  
press [ON/OFF] button of the remote controller to start the indoor unit, setting temperature:24¡ : press [swing] button  
7 times in 5 seconds, the buzzer will ring twice, and enter cooling temp. compensation mode.  
(2) Temperature compensation function checking  
*In cooling mode, setting temp.: 30 degree, High fan speed, press [swing] button 7 times in 5 seconds, The Running lamp  
will flash, the times of flash is same with cooling compensation setting number  
*In heating mode, setting temp. :16 degree, high fan speed, press [swing] 7 times in 5 seconds, the running lamp will flash,  
the flashing times is same with heating compensation setting number  
Concerning MRV Auto Restart function for H-MRV models  
Haier Auto Restart function when the unit power drops down suddenly, the unit microprocessor will store the previous  
working condition and when the power is on again, the unit will run as this memory.  
Auto Restart function is designed basically on the MRV whole system, but it is suitable for each indoor unit individually.  
If some of indoor units power cut down, but the outdoor unit and the other indoor units still work, maybe problems will  
happen such as freezing at cooling mode and overload protection at heating mode on those indoor units without power.  
Reason  
When one or some indoor units power drops down and the other indoor units are still work, the indoor units without  
the power, will keep the previous working condition before the power is off.  
And expansion valve keeps open at a kind of opening rate condition as the previous requirement,so there is refrigerant  
flowing in the exchanger, but the indoor fan stops working. If the units work at cooling mode, the indoor units without the  
power will maybe make freezing. If the unit works at heating mode, maybe the outdoor unit compressor will stop because  
of the pressure or temperature protection. This is our design basically on Auto Restart function currently.  
Haier, Herewith, solemnly informs our customers, installers, distributors, etc. when making installation,  
please make sure when the power is shut down whether artificially or accidentally, the whole system  
including outdoor unit and all the indoor units must be off. If you do not make the installation as  
our indication, Haier will not be responsible for any problem resulting from this.  
Pay special care to the following and check after installation  
Unproper installation may cause  
Item to the checked  
Check  
Unit might fall down, make vibration or noise.  
This may lead to gas shortage.  
Is gas leakage check performed?  
Is unit properly insulated?  
Dew or water drop may occur.  
Dew or water drop may occur.  
Is water drainage smooth?  
Is power voltage meet that stipulated on the nameplate?  
Is wiring and piping correctly arranged?  
Is unit safely grounded?  
Problem may occur or parts got burned.  
Problem may occur or parts got burned.  
There might be a danger of electric shock.  
Problem may occur or parts got burned.  
Is wire size correct?  
Are there any obstacles on air inlet and outlet grill of  
indoor and outdoor unit?  
This may cause poor cooling.  
It is hard to control refrigerant charging  
amount.  
Is record made for piping length and refrigerant  
charging amount?  
28  
Technical Specifications  
Model  
AB094FAAHA  
AB124FAAHA  
A184FCAHA  
AB244FCAHA  
Power Supply  
Cooling Capacity  
heating Capacity  
1PH.220V~,60Hz  
1PH.220V~,60Hz  
1PH.220V~,60Hz 1PH.220V~,60Hz  
3600W  
3900W  
6000W  
6300W  
7200W  
8000W  
2800W  
3200W  
Noise  
(Indoor Units)  
35 dB(A)  
--  
--  
34dB(A)  
Net Weight  
(Indoor Units)  
20kg  
20kg  
28kg  
28kg  
Air Volume  
(Indoor Units)  
1020m3/h  
450m3/h  
900m3/h  
400m3/h  
710*440*270  
Net Dimensions(mm)  
840*840*240  
710*440*270  
840*840*240  
Panel Dimensions(mm  
8
)
60*500*60  
860*500*60  
6.35/12.7  
950*950*80  
9.52/15.88  
950*950*80  
9.52/15.88  
Refrigerant liquid pipe/  
Refregerant gas pipe  
6.35/12.7  
Model  
AB424FCAHA  
1PH.220V~,60Hz  
AB484FCAHA  
1PH.220V~,60Hz  
Power Supply  
Cooling Capacity  
heating Capacity  
3600W  
3900W  
2800W  
3200W  
Noise  
37dB(A)  
35kg  
42dB(A)  
35kg  
(Indoor Units)  
Net Weight  
(Indoor Units)  
Air Volume  
(Indoor Units)  
1920m3/h  
1580m3/h  
Net Dimensions(mm)  
Panel Dimensions(mm)  
Refrigerant liquid pipe/  
950*950*80  
950*950*80  
9.52/19.05  
9.52/19.05  
Refregerant gas pipe  
29  

Brother MFC 9840CDW User Manual
Brother MFC J430W User Manual
Carrier CVL290 User Manual
Danby DPAC7099 User Manual
Epson All in One Printer M00037903VI User Manual
GE General Electric Air Conditioner ASM22 User Manual
Goodman Mfg CKLB24 1F User Manual
Heat Controller REG 253H User Manual
Honda Automobiles Trailer Hitch 08L91 STX 2000 81 User Manual
HP Hewlett Packard HP LASERJET 700 CLR MFP M775Z Printer CC524A#BGJ User Manual