Friedrich PTAC R410A User Manual

2 0 11  
PTAC - R410A Models  
Packaged Terminal Air Conditioners  
Packaged Terminal Heat Pumps  
PD-ServMan-E (2-11)  
Table of Contents  
Important Safety Information ...........................................2-4  
Capillary Tube Systems/Check Valve ..........................33  
Reversing Valve — Description/Operation ...................34  
Testing Coil ...................................................................34  
Checking Reversing Valves .....................................34-35  
Introduction .........................................................................4  
General Product Features ..................................................5  
HVAC Engineering Specifications ......................................6  
Component identification ....................................................7  
Accessories .....................................................................8-9  
Unit Identification ..............................................................10  
Chassis Specifications ......................................................11  
Cooling and Heating Performance ..............................12-13  
Electric Heat Data ............................................................14  
Electrical Rating Tables ....................................................15  
Power Cord Information ..............................................15-17  
Reversing Valve  
Touch Testing Heating/Cooling Cycle ..........................35  
Procedure For Changing Reversing Valve ..............35-36  
Compressor Checks .....................................................36  
Locked Rotor Voltage Test ............................................36  
Single Phase Connections ............................................36  
Determine Locked Rotor Voltage ..................................36  
Locked Rotor Amperage Test ........................................36  
Single Phase Running & Locked Rotor Amperage ........36  
Checking the Overload ..................................................36  
External Overload ..........................................................37  
Compressor Single Phase Resistance Test ...................37  
Compressor Replacement ........................................38-39  
Routine Maintenance .....................................................39  
Troubleshooting Charts .............................................40-41  
Wiring Diagrams for Wall Mounted Thermostats .......42-43  
Wiring Diagram .........................................................42-44  
RT6 Installation, Operation and Application Guide ...45-46  
Thermistors Resistance Values ................................47-48  
Warranty ...............................................................................49  
2011 PTAC Exploded View ...............................................50  
2011 PTAC Parts List - PDE Models ................................51  
2011 PTAC Parts List - PDH Models ................................52  
Remote Wall Thermostat / Low Voltage  
Wire Connections ........................................................18-19  
Digital Control Features ....................................................20  
Digital Control Operation ..................................................21  
Digital Control User Input Configuration ...........................22  
Digital Control Diagnostics ................................................23  
Malfunction Analysis ....................................................24-26  
Components Testing ....................................................27-28  
Refrigeration System Sequence of Operation ...................29  
Sealed Refrigeration System Repairs ...............................30  
Refrigerant Charging .........................................................31  
Method Of Charging ..........................................................31  
Undercharged Refrigerant Systems .............................31-32  
Overcharged Refrigerant Systems ....................................32  
Restricted Refrigerant Systems .........................................32  
1
IMPORTANT SAFETY INFORMATION  
The information contained in this manual is intended for use by a qualified service technician who is familiar  
with the safety procedures required for installation and repair, and who is equipped with the proper tools and  
test instruments required to service this product.  
Installation or repairs made by unqualified persons can result in subjecting the unqualified person making  
such repairs as well as the persons being served by the equipment to hazards resulting in injury or electrical  
shock which can be serious or even fatal.  
Safety warnings have been placed throughout this manual to alert you to potential hazards that may be  
encountered. If you install or perform service on equipment, it is your responsibility to read and obey these  
warnings to guard against any bodily injury or property damage which may result to you or others.  
Your safety and the safety of others are very important.  
We have provided many important safety messages in this manual and on your appliance. Always read  
and obey all safety messages.  
This is a safety Alert symbol.  
This symbol alerts you to potential hazards that can kill or hurt you and others.  
All safety messages will follow the safety alert symbol with the word “WARNING”  
or “CAUTION”. These words mean:  
You can be killed or seriously injured if you do not follow instructions.  
WARNING  
You can receive minor or moderate injury if you do not follow instructions.  
CAUTION  
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury,  
and tell you what will happen if the instructions are not followed.  
A message to alert you of potential property damage will have the  
word “NOTICE”. Potential property damage can occur if instructions  
are not followed.  
NOTICE  
2
PERSONAL INJURY OR DEATH HAZARDS  
ELECTRICAL HAZARDS:  
Unplug and/or disconnect all electrical power to the unit before performing inspections, maintenance,  
or service.  
Make sure to follow proper lockout/tag out procedures.  
Always work in the company of a qualified assistant if possible.  
Capacitors, even when disconnected from the electrical power source, retain an electrical charge  
potential capable of causing electric shock or electrocution.  
Handle, discharge, and test capacitors according to safe, established, standards, and approved  
procedures.  
Extreme care, proper judgment, and safety procedures must be exercised if it becomes necessary to  
test or troubleshoot equipment with the power on to the unit.  
Do not spray or pour water on the return air grille, discharge air grille, evaporator coil, control panel,  
and sleeve on the room side of the air conditioning unit while cleaning.  
Electrical component malfunction caused by water could result in electric shock or other electrically  
unsafe conditions when the power is restored and the unit is turned on, even after the exterior is dry.  
Never operate the A/C unit with wet hands.  
Use air conditioner on a single dedicated circuit within the specified amperage rating.  
Use on a properly grounded outlet only.  
Do not remove ground prong of plug.  
Do not cut or modify the power supply cord.  
Do not use extension cords with the unit.  
Follow all safety precautions and use proper and adequate protective safety aids such as: gloves,  
goggles, clothing, adequately insulated tools, and testing equipment etc.  
Failure to follow proper safety procedures and/or these warnings can result in serious injury or death.  
REFRIGERATION SYSTEM HAZARDS:  
Use approved standard refrigerant recovering procedures and equipment to relieve pressure before  
opening system for repair.  
Do not allow liquid refrigerant to contact skin. Direct contact with liquid refrigerant can result in minor  
to moderate injury.  
Be extremely careful when using an oxy-acetylene torch. Direct contact with the torch’s flame or hot  
surfaces can cause serious burns.  
Make sure to protect personal and surrounding property with fire proof materials.  
Have a fire extinguisher at hand while using a torch.  
Provide adequate ventilation to vent off toxic fumes, and work with a qualified assistant whenever  
possible.  
Always use a pressure regulator when using dry nitrogen to test the sealed refrigeration system for  
leaks, flushing etc.  
3
Make sure to follow all safety precautions and to use proper protective safety aids such as: gloves,  
safety glasses, clothing etc.  
Failure to follow proper safety procedures and/or these warnings can result in serious injury or death.  
MECHANICAL HAZARDS:  
Extreme care, proper judgment and all safety procedures must be followed when testing,  
troubleshooting, handling, or working around unit with moving and/or rotating parts.  
Be careful when, handling and working around exposed edges and corners of sleeve, chassis, and  
other unit components especially the sharp fins of the indoor and outdoor coils.  
Use proper and adequate protective aids such as: gloves, clothing, safety glasses etc.  
Failure to follow proper safety procedures and/or these warnings can result in serious injury or death.  
PROPERTY DAMAGE HAZARDS  
FIRE DAMAGE HAZARDS:  
Read the Installation/Operation Manual for this air conditioning unit prior to operating.  
Use air conditioner on a single dedicated circuit within the specified amperage rating.  
Connect to a properly grounded outlet only.  
Do not remove ground prong of plug.  
Do not cut or modify the power supply cord.  
Do not use extension cords with the unit.  
Failure to follow these instructions can result in fire and minor to serious property damage.  
WATER DAMAGE HAZARDS:  
Improper installation maintenance, or servicing of the air conditioner unit, or not following the above  
Safety Warnings can result in water damage to personal items or property.  
Insure that the unit has a sufficient pitch to the outside to allow water to drain from the unit.  
Do not drill holes in the bottom of the drain pan or the underside of the unit.  
Failure to follow these instructions can result in result in damage to the unit and/or minor to serious  
property damage.  
INTRODUCTION  
This service manual is designed to be used in conjunction with the installation manuals provided with each unit.  
This service manual was written to assist the professional HVAC service technician to quickly and accurately  
diagnose and repair any malfunctions of this product.  
This manual, therefore, will deal with all subjects in a general nature. (i.e. All text will pertain to all models).  
IMPORTANT:  
It will be necessary for you to accurately identify the unit you are  
servicing, so you can be certain of a proper diagnosis and repair.  
(See Unit Identification.)  
4
General Product Features  
Diamonblue seacoast protection protects the outdoor coil from harsh environments. Comes standard  
on all models.  
DIAMONBLUE  
TECHNOLOGY  
The new Friedrich PTAC uses a digital thermostat to accurately monitor the outdoor coil conditions to al-  
low the heat pump to run whenever conditions are correct. Running the PTAC in heat pump mode saves  
energy and reduces operating costs. The digital thermostat allows maximization of heat pump run time.  
DIGITALDEFROST  
THERMOSTAT  
Heat pump models will automatically run the electric heater to quickly bring the room up to temperature  
when initially energized, then return to heat pump mode. This ensures that the room is brought up to  
temperature quickly without the usual delay associated with heat pump units.  
INSTANT HEAT  
HEAT PUMP MODE  
of the setpoint. If necessary, the unit will cycle the electric heat to maintain the temperature. This feature  
-
EVEN HEAT MONITORING  
The owner may choose between fan cycling or fan continuous mode based on property preference. (Note:  
Even heat monitoring and quiet start/stop fan delay only operate in fan cycle mode) Fan continuous mode is  
SEPARATE HEAT/COOL  
FAN CYCLE  
CONTROL  
energy by only operating the fan while the compressor or electric heater is operating. The ability to set the  
fan cycling condition independently between heating and cooling mode will increase user comfort by  
allowing the choice of only constantly circulating air in the summer or winter time. Unlike other PTAC  
brands that only allow one selection.  
In the event of a compressor failure in heat pump mode, the compressor may be locked out to provide  
heat through the resistance heater. This feature ensures that even in the unlikely event of a compressor  
failure, the room temperature can be maintained until the compressor can be serviced.  
EMERGENCY  
HEAT OVERRIDE  
All Friedrich digital PTACs have low voltage terminals ready to connect a desk control energy manage-  
ment system. Controlling the unit from a remote location like the front desk can reduce energy usage and  
requires no additional accessories on the PTAC unit.  
DESK CONTROL  
READY  
temperatures cause the indoor coil to freeze. When the indoor coil reaches 30°F, the compressor is  
disabled and the fan continues to operate based on demand. Once the coil temperature returns to 45°F,  
the compressor returns to operation.  
INDOOR COIL  
FROST SENSOR  
The new Friedrich PD series units feature an indoor fan system design that reduces sound levels without  
ULTRA QUIET  
AIR SYSTEM  
The Friedrich PTAC has been engineered so that all functional systems are optimized so that they work  
together to deliver the highest possible performance.  
HIGH EFFICIENCY  
DUAL MOTOR  
With Friedrich’s new dual-motor design the indoor motor can run at slower speeds which reduces sound  
levels indoors.  
-
ROTARYCOMPRESSOR  
ciency.  
Outdoor coil endplates made from stainless steel reduce corrosion on the outdoor coil common with other  
coil designs.  
STAINLESS STEEL  
ENDPLATES  
TOP -MOUNTED  
ANTIMICROBIAL  
AIR FILTERS  
front cover.  
Friedrich PTAC units are capable of introducing up to 75 CFM of outside air into the conditioned space.  
The outdoor air passes through a washable mesh screen to prevent debris from entering the airstream.  
FILTERED FRESH  
AIR INTAKE  
Friedrich PTAC units use environmentally-friendly refrigerant.  
R-410A REFRIGERANT  
5
Digital Packaged Terminal Air Conditioners & Heat Pumps  
Cooling: 7600 – 15,000 Btuh  
Heating: 7600 – 14500 Btuh (Heat Pump)  
6824 – 17060 Btuh (Electric Heat)  
Friedrich Models: PDE – Cooling with or without electric heat  
PDH – Heat Pump with electric heat  
All units shall be factory assembled, piped, wiredand fully charged with The unit must have the following energy saving and convenience  
features built-in:  
310 for air conditioners and ARI standard 380 for heat pumps. Units  
shall be UL listed and carry a UL label. All units shall be factory run-  
tested to check operation and be Friedrich or equivalent.  
Quiet start/stop fan delay  
Fan cycle control for cooling and heating independently  
Room freeze protection  
The basic unit shall not exceed 16” high x 42” wide. Overall depth Random compressor restart  
of the unit from the rear of the Friedrich wall sleeve to the front of Electronic temperature limiting  
the decorative front cover shall not exceed 21 ¼”. The unit shall be  
The PTAC must also offer the ability to be controlled by a remote wall-  
designed so that room intrusion may be as little as 7 ½”. Installations  
in walls deeper than 13 ¼” may be accomplished with the use of a  
deep wall sleeve (PDXWSEXT). Unit shall draw in ambient air through  
both sides of an outdoor architectural louver or grille measuring 42”  
wide x 16” high and shall exhaust air out middle portion of the louver.  
The architectural louver and wall sleeve shall be designed so that the  
louver may be installed from the inside of the building.  
mountedthermostat without additionalaccessories. Lowvoltageinputs  
will include: C (common), R (24V power), Y (cooling), GL (fan low), GH  
(fan high), W (heat) and O (reversing valve on PDH heat pumps only).  
PTAC models shall use a single stage cool / single stage heat ther-  
mostat. PTHP models shall use a single stage cool / two-stage heat  
thermostat. An accessory thermostat must be available from the  
manufacturer, RT6 or equivalent. The RT6 thermostat will provide  
temperature setpoint, mode selection from cool, heat and fan modes.  
The thermostat must also allow the selection of fan speed between  
high and low speed.  
REFRIGERATION SYSTEM – The refrigeration system shall be her-  
metically sealed and consist of a rotary compressor that is externally  
mounted on vibration isolators no smaller than 1 3/8” dia. x 1 ½” high;  
condenser and evaporator coils constructed of copper tubes and  
Other controls accessible without removal of the chassis shall include  
fan cycle switch, fresh air vent control and emergency heat override  
switch (heat pump only).  
and have a drain pan capable of retaining 1 ½ gallons of condensate.  
A tertiary condensate removal system shall also be incorporated for  
ELECTRICAL CONNECTION– All PTAC/PTHP units shall come from  
the factory with a power cord installed. All 230/208V power cords shall  
feature a leakage current detection device on the plug head. All units  
shall feature a 6-pin connector for removal of the power cord. The  
power cord shall be interchangeable to allow changes to the heater  
output based on the property/electrical requirements.  
of the building as a safeguard against damage to the interior room.  
INDOOR AIR HANDLING SECTION – The indoor air handling sec-  
tion shall consist of a tangential blower wheel direct driven by a totally  
enclosed motor. The air handling system shall be designed to minimize  
fan must have three fan speeds that may be selected by the user.  
GENERAL CONSTRUCTION – The wall sleeve shall be constructed  
of 18-gauge Galvanized zinc-coated steel. It shall be prepared by  
a process where it is zinc phosphate pretreated and sealed with a  
throughout the room. The grille shall be reversible to allow a change  
personal injury or damage to the unit.  
cured for durability. The sleeve shall be shipped with a protective  
weatherboard and a structural center support, and be insulated for  
shipped separately and made from stamped or extruded anodized  
aluminum. All louvers shall be in the horizontal plane.  
and reusable by cleaning with water or by vacuuming.  
clips. As an option the cover may be attached by two screws to pre-  
vent tampering. The front panel will feature a contoured discharge  
with no sharp corners.  
The chassis shall have a built-in damper capable of providing at least  
CORROSION PROTECTION – The unit shall have corrosion-resistant  
fans, fan shroud and drain pan for corrosion protection and to prevent  
rust on the side of the building below the outdoor louver. The unit shall  
-
damper closed to ensure a proper seal.  
OUTDOOR AIR HANDLING SECTION – The outdoor air section  
shall consist of a single injection molded fan shroud that incorporates  
the outdoor motor mount into a single piece for ease of service and  
assembly. The outdoor motor shall be totally enclosed, ball-bearing,  
permanently lubricated and directly drive the outdoor fan/slinger ring.  
rioration. The outdoor coil shall have Diamonblue corrosion protection  
applications including seacoast environments. All outdoor coils shall  
also have stainless steel endplates to eliminate rusting of the endplates.  
CONTROLS – Covered controls shall be accessible in a compartment  
at least 7½” wide with the controls no deeper than 1 ¼” in the opening  
to facilitate easy operation of the unit.  
WARRANTY – The warranty is one year on all parts and 5 years on  
the sealed system including compressor, indoor and outdoor coils and  
refrigerant tubing.  
The unit controls shall feature a soft blue LED readout that can display  
either room temperature or setpoint temperature. The unit shall re-  
ceive input from the digital control panel through push buttons labeled:  
‘Cool’, ‘Heat’, ‘High Fan’, ‘Med Fan’, ‘Low Fan’,  
When ‘Off’, the unit may be put directly into cooling or heating mode  
by pressing the ‘Cool’ or ‘Heat’ button.  
’, ‘ˆ’ and ‘Power’.  
6
Component Identification  
Typical Unit Components and Dimensions  
WALL SLEEVE  
OUTDOOR GRILLE  
DISCHARGE  
GRILLE  
FILTERS  
CHASSIS  
FRONT COVER  
RETURN AIR GRILLE  
PDXWS Wall Sleeve Dimensions:  
16" H x 42" W x 13-¾" D  
Front Cover Dimensions:  
16" H x 42" W x 7-¾" D  
Cut-Out Dimensions:  
16-¼" x 42-¼"  
7
Accessories  
New Construction Accessories  
WALL SLEEVE Galvanized zinc coated steel is prepared in an 11-step  
PDXWS  
oven for exceptional durability. The wall sleeve is insulated for sound  
PDXWS  
DEEP WALL SLEEVE EXTENSION For use when the wall is thicker  
PDXWSEXT  
than 13 1/4”deep. The wall sleeve may be special ordered through your  
-
ments..  
PDXWSEXT  
GRILLE Standard, stamped aluminium, anodized to resist chalking and  
oxidation.  
PXGA  
ARCHITECTURAL GRILLES Consist of heavy-gauge 6063-T5 alumi-  
num alloy:  
PXAA – Clear, extruded aluminum  
PXBG – Beige acrylic enamel  
PXSC – Also available in custom colors.  
PXAA  
PXBG  
PXSC  
PXGA  
PXAA  
CONDENSATE DRAIN KIT Attaches to the bottom of the wall sleeve for  
PXDR10  
-
nal draining. Recommended on all units to remove excess condensate.  
Packaged in quantities of ten.  
DECORATIVE SUBBASE Provides unit support for walls less than  
PXSB  
RT6  
-
ing brackets for electrical accessories. Accepts circuit breaker, power  
disconnect switch, or conduit kit.  
DIGITAL REMOTE WALL THERMOSTAT Single stage cool, single  
stage heat for PDE models or single stage cool, dual stage heat for  
PDH model thermostat features high/low fan speed switch. Thermostat  
is hard wired and can be battery powered or unit powered. Features  
Friedrich PTACs and Vert-I-Paks.  
REMOTE THERMOSTAT ESCUTCHEON KIT This kit contains ten  
escutcheons that can be placed over the factory control buttons when  
a remote wall mounted thermostat is used. The escutcheon directs the  
guest to the wall thermostat for operation and retains the LED window to  
display error codes and diagnostic information.  
PDXRTA  
PXSE  
SLEEVE EXTENSION RETROFIT KIT Galvanized zinc coated steel,  
2.4" sleeve extension attached to the room side of the sleeve to allow for  
the installation of a PD-Series Friedrich PTAC in a T-Series sleeve.  
LATERAL DUCT ADAPTER Attaches to the PTAC/PTHP unit and  
provides a transition to direct up to 35% of the total CFM to a second-  
ary room, either left or right of the unit. Kit includes duct plenum with  
PDXDAA  
PDXDEA  
LATERAL DUCT EXTENSION A three-foot insulated plenum that at-  
taches to the left or right side of the duct adapter. The extension can be  
cut to length by the installer. Maximum allowable straight extension is 15  
feet.  
8
Accessories  
New Construction Accessories  
CONDUIT KIT WITH JUNCTION BOX Hard wire conduit kit with  
PXCJA  
junction box for 208/230V and 265V units (subbase not required). Kit  
includes a means of quick disconnect for easy removal of the chassis.  
*Required for 265V installations.  
REPLACEMENT FILTER PACK These are original equipment return air  
PXFTA  
chassis).  
9
UNIT IDENTIFICATION  
PD HM0o7del NKumb3er CoSde F A  
Series  
Engineering Digit  
Design Series  
PD = P Series Digital PTAC  
System  
E = Cooling with or  
without electric heat  
H = Heat Pump with  
Auxiliary Heat  
Options  
S = Standard  
Nominal Cooling Capacity  
07 = 7000 BTUh  
Nominal Heater Size  
(@ 230V or 265V)  
0 = No Heater  
2 = 2KW  
09 = 9000 BTUh  
12 = 12000 BTUh  
15 = 15000 BTUh  
3 = 3KW  
5 = 5.0KW  
Voltage  
K = 208/230V - 1Ph. - 60Hz.  
R = 265V - 1Ph. - 60Hz.  
PTAC Serial Number Identification Guide  
SERIAL NUMBER  
A
A
A
M
00001  
YEAR MANUFACTURED  
LJ = 2009 AE = 2015  
AK = 2010 AF = 2016  
AA = 2011 AG = 2017  
AB = 2012 AH = 2018  
AC = 2013 AJ = 2019  
AD = 2014  
PRODUCTION RUN NUMBER  
PRODUCT LINE  
M = PTAC  
MONTH MANUFACTURED  
A = Jan  
B = Feb  
C = Mar  
D = Apr  
E = May  
F = Jun  
G = Jul  
H = Aug  
J = Sep  
K = Oct  
L = Nov  
M = Dec  
10  
Chassis Specifications  
PDE Series  
PDE07K  
PDE07R  
PDE09K  
PDE09R  
PDE12K  
PDE12R  
PDE15K  
PDE15R  
PERFORMANCE DATA:  
COOLING BTUh  
7700/7600  
640/620  
12.0/12.2  
1.7  
7700  
640  
12.0  
1.7  
9000/8800  
800/770  
11.3/11.4  
2.2  
9000  
800  
11.3  
2.2  
12000/11800  
1120/1120  
10.7/10.5  
2.7  
12000  
1120  
10.7  
2.7  
15000/14600  
1530/1510  
9.8/9.7  
15000  
1530  
9.8  
POWER (WATTS)  
EER  
DEHUMIDIFICATION (pints/hr)  
SENSIBLE HEAT RATIO  
ELECTRICAL DATA:  
VOLTAGE (1 PHASE, 60 Hz)  
VOLT RANGE  
3.2  
3.2  
0.84  
0.84  
0.81  
0.81  
0.67  
0.67  
0.65  
0.65  
230/208  
253-187  
2.8/3.0  
0.97  
265  
292-239  
2.4  
230/208  
253-187  
3.7/3.9  
0.99  
265  
292-239  
3.7  
230/208  
253-187  
5.1/5.3  
0.99  
265  
292-239  
4.8  
230/208  
253-187  
6.7/7.5  
0.99  
265  
292-239  
5.9  
CURRENT (AMPS)  
POWER FACTOR  
Compressor LRA  
Compressor RLA  
Fan motor horsepower  
AIRFLOW DATA:  
0.99  
0.99  
0.99  
0.99  
19.0  
12.0  
17.0  
18.0  
27.00  
5.0  
23.0  
32.6  
27.8  
2.8  
2.4  
3.7  
2.9  
4.3  
6.6  
5.6  
0.024  
0.024  
0.029  
0.029  
0.031  
0.031  
0.031  
0.031  
INDOOR CFM, HIGH  
INDOOR CFM, MED  
INDOOR CFM, LOW  
VENT CFM  
345/315  
320/290  
295/265  
75  
345  
320  
295  
75  
360/345  
330/305  
300/270  
75  
360  
330  
300  
75  
360/350  
330/310  
310/280  
75  
360  
330  
310  
75  
385/375  
360/330  
320/290  
75  
385  
360  
320  
75  
PHYSICAL DATA:  
DIMENSIONS  
16x42x13 3/4 16x42x13 3/4 16x42x13 3/4 16x42x13 3/4 16x42x13 3/4  
16x42x13 3/4  
116  
16x42x13 3/4  
16x42x13 3/4  
119  
NET WEIGHT  
106  
126  
106  
126  
111  
131  
111  
131  
116  
136  
119  
139  
38.1  
SHIPPING WEIGHT  
R-410A CHARGE (oz)  
Dim.s w/ Pkg.  
136  
139  
23.63  
24.69  
33.51  
33.51  
35.27  
35.98  
40.21  
19.75x23x 43.5 (all models)  
PDH Series  
PDH07K  
PDH07R  
PDH09K  
PDH09R  
PDH12K  
PDH12R  
PDH15K  
PDH15R  
PERFORMANCE DATA:  
COOLING BTUh  
7700/7600  
640/620  
12.0/12.2  
6300/6100  
540/530  
3.4/3.4  
7700  
640  
12  
9000/8800  
800/770  
11.3/11.4  
8100/7900  
720/770  
3.3/3.3  
9000  
800  
11.3  
8100  
720  
3.3  
12000/11800  
1120/1120  
10.7/10.5  
10700/10500  
1010/990  
3.1/3.1  
12000  
1120  
10.7  
10700  
1010  
3.1  
14500/14200  
1480/1460  
9.8/9.7  
14500  
1480  
9.8  
POWER (WATTS) cool  
EER  
REVERSE HEATING BTUh  
POWER (WATTS) HEAT  
COP  
6300  
540  
3.4  
13300/13000  
1300/1270  
3.0/3.0  
13300  
1300  
3
DEHUMIDIFICATION (pints/hr)  
SENSIBLE HEAT RATIO  
ELECTRICAL DATA:  
VOLTAGE (1 PHASE, 60 Hz)  
VOLT RANGE  
1.7  
1.7  
2.2  
2.2  
2.7  
2.7  
3.2  
3.2  
0.84  
0.84  
0.81  
0.81  
0.67  
0.67  
0.65  
0.65  
230/208  
253-187  
2.8/3.0  
2.4/2.5  
0.97  
265  
292-239  
2.4  
230/208  
253-187  
3.7/3.9  
3.4/3.8  
0.99  
265  
292-239  
3.7  
230/208  
253-187  
5.1/5.3  
4.5/4.7  
0.99  
265  
292-239  
4.8  
230/208  
253-187  
6.7/7.5  
5.8/6.2  
0.98  
265  
292-239  
5.7  
CURRENT (AMPS)  
REVERSE HEAT. Amps  
POWER FACTOR  
Compressor LRA  
2.1  
3.4  
4.5  
5.0  
0.99  
12.0  
2.4  
0.99  
19.0  
3.2  
0.99  
23.0  
4.3  
0.98  
26.0  
5.3  
19.0  
18.5  
27.00  
5.0  
36.0  
Compressor RLA  
2.8  
3.6  
6.5  
Fan motor horsepower  
AIRFLOW DATA:  
0.024  
0.024  
0.029  
0.029  
0.031  
0.031  
0.031  
0.031  
INDOOR CFM, HIGH  
INDOOR CFM, MED  
INDOOR CFM, LOW  
VENT CFM  
345/315  
320/290  
295/265  
75  
345  
320  
295  
75  
360/345  
330/305  
300/270  
75  
360  
330  
300  
75  
360/350  
330/310  
310/280  
75  
360  
330  
310  
75  
420/390  
410/380  
380/350  
75  
385  
360  
320  
75  
PHYSICAL DATA:  
DIMENSIONS  
16x42x13.5  
108  
16x42x13.5 16x42x13.5  
16x42x13.5  
113  
16x42x13.5  
118  
16x42x13.5  
118  
16x42x13.5  
121  
16x42x13.5  
123  
NET WEIGHT  
108  
128  
113  
133  
SHIPPING WEIGHT  
R-410A CHARGE (oz)  
128  
133  
138  
138  
141  
143  
23.63  
24.69  
33.51  
35.27  
35.27  
35.98  
39.86  
36.33  
250 V Receptacles and Fuse Types  
AMPS  
15  
20  
30  
HEATER SIZE  
0, 2.0 kW 3.0 kW  
5.0 kW  
RECEPTACLE  
11  
Cooling & Heating Performance  
PDE 230V - Extended Cooling Performance  
OUTDOOR DRY BULB TEMP. (DEGREES F AT 40% R.H.)  
75  
85  
95  
105  
110  
INDOOR WET BULB TEMP. (DEGREES F AT 80 F D.B.)  
72  
9055  
522  
67  
8709  
531  
62  
8062  
536  
72  
8624  
569  
2.5  
0.54  
10080  
711  
3.3  
0.5  
13440  
996  
4.5  
67  
8131  
575  
62  
7500  
582  
72  
8285  
640  
67  
7700  
640  
2.80  
0.77  
9000  
800  
3.70  
0.71  
12000  
1120  
5.10  
0.71  
15000  
1530  
6.70  
62  
6815  
640  
72  
7762  
692  
67  
6892  
691  
62  
6075  
693  
3
0.99  
7101  
866  
4
0.92  
9468  
1213  
5.5  
0.92  
11835  
1657  
7.2  
72  
6907  
755  
67  
5944  
755  
3.3  
0.87  
6948  
943  
4.3  
62  
5251  
758  
BTUh  
WATTS  
AMPS  
SHR  
BTUh  
WATTS  
AMPS  
SHR  
BTUh  
WATTS  
AMPS  
SHR  
BTUh  
WATTS  
AMPS  
SHR  
PDE07  
PDE09  
PDE12  
PDE15  
2.3  
2.3  
2.4  
2.5  
2.5  
2.8  
2.8  
3
3
3.3  
3.3  
0.53  
10584  
653  
0.72  
10179  
663  
0.96  
9423  
670  
0.74  
9504  
718  
0.98  
8766  
727  
0.54  
9684  
800  
3.7  
0.5  
12912  
1120  
5.1  
0.99  
7965  
800  
0.55  
9072  
865  
0.81  
8055  
864  
0.58  
8073  
943  
0.99  
6138  
947  
3.1  
3.1  
3.1  
3.3  
3.3  
3.7  
4
4
4.3  
4.4  
0.49  
14112  
914  
0.66  
13572  
928  
0.89  
12564  
939  
0.69  
12672  
1006  
4.6  
0.69  
15840  
1374  
6
0.91  
11688  
1018  
4.6  
0.91  
14610  
1391  
6
0.91  
10620  
1120  
5.1  
0.91  
13275  
1530  
6.7  
0.51  
12096  
1211  
5.5  
0.51  
15120  
1654  
7.2  
0.75  
10740  
1210  
5.5  
0.75  
13425  
1652  
7.2  
0.54  
10764  
1320  
6
0.54  
13455  
1804  
7.9  
0.8  
0.91  
8184  
1326  
6
0.91  
10230  
1812  
7.9  
9264  
1320  
6
4.2  
4.2  
4.3  
0.49  
17640  
1248  
5.5  
0.66  
16965  
1268  
5.6  
0.89  
15705  
1282  
5.6  
0.5  
0.5  
0.8  
16800  
1360  
6
16140  
1530  
6.7  
11580  
1804  
7.9  
0.47  
0.63  
0.85  
0.48  
0.66  
0.87  
0.48  
0.87  
0.49  
0.72  
0.88  
0.51  
0.77  
0.87  
0.68  
RATING POINT  
ARI 310/380  
PDH 230V - Extended Cooling Performance  
OUTDOOR DRY BULB TEMP. (DEGREES F AT 40% R.H.)  
75  
85  
95  
105  
110  
INDOOR WET BULB TEMP. (DEGREES F AT 80 F D.B.)  
72  
9055  
522  
67  
8709  
531  
62  
8062  
536  
72  
8624  
569  
67  
8131  
575  
62  
7500  
582  
72  
8285  
640  
67  
7700  
640  
2.80  
0.77  
9000  
800  
3.70  
0.71  
12000  
1120  
5.10  
0.71  
14500  
1480  
6.6  
62  
6815  
640  
72  
7762  
692  
3
0.55  
9072  
865  
4
0.51  
12096  
1211  
5.5  
0.51  
14616  
1600  
7.1  
67  
6892  
691  
62  
6075  
693  
3
0.99  
7101  
866  
4
0.92  
9468  
1213  
5.5  
0.92  
11441  
1603  
7.1  
72  
6907  
755  
67  
5944  
755  
3.3  
0.87  
6948  
943  
4.3  
62  
5251  
758  
3.3  
0.99  
6138  
947  
4.4  
0.91  
8184  
1326  
6
0.91  
9889  
1752  
7.7  
BTUh  
WATTS  
AMPS  
SHR  
BTUh  
WATTS  
AMPS  
SHR  
BTUh  
WATTS  
AMPS  
SHR  
BTUh  
WATTS  
AMPS  
SHR  
PDH07  
PDH09  
PDH12  
PDH15  
2.3  
2.3  
2.4  
2.5  
2.5  
2.5  
2.8  
2.8  
3
3.3  
0.53  
10584  
653  
0.72  
10179  
663  
0.96  
9423  
670  
0.54  
10080  
711  
3.3  
0.5  
13440  
996  
4.5  
0.74  
9504  
718  
0.98  
8766  
727  
0.54  
9684  
800  
3.7  
0.5  
12912  
1120  
5.1  
0.99  
7965  
800  
0.81  
8055  
864  
0.58  
8073  
943  
3.1  
3.1  
3.1  
3.3  
3.3  
3.7  
4
4.3  
0.49  
14112  
914  
0.66  
13572  
928  
0.89  
12564  
939  
0.69  
12672  
1006  
4.6  
0.69  
15312  
1329  
5.9  
0.91  
11688  
1018  
4.6  
0.91  
14123  
1345  
5.9  
0.91  
10620  
1120  
5.1  
0.91  
12833  
1480  
6.6  
0.75  
10740  
1210  
5.5  
0.75  
12978  
1598  
7.1  
0.54  
10764  
1320  
6
0.54  
13007  
1745  
7.7  
0.8  
9264  
1320  
6
4.2  
4.2  
4.3  
0.49  
17052  
1208  
5.4  
0.66  
16400  
1227  
5.5  
0.89  
15182  
1240  
5.5  
0.5  
0.5  
0.8  
16240  
1316  
5.9  
15602  
1480  
6.5  
11194  
1745  
7.7  
0.48  
0.65  
0.88  
0.49  
0.68  
0.89  
0.49  
0.9  
0.5  
0.74  
0.9  
0.53  
0.79  
0.9  
0.70  
RATING POINT  
ARI 310/380  
Extended Heating Performance  
OUTDOOR DRY BULB TEMP. (DEGREES F)  
37  
42  
5540  
518  
47  
52  
6900  
549  
57  
7620  
580  
BTUh  
5250  
509  
2.3  
6300  
540  
WATTS  
AMPS  
BTUh  
PDH07  
PDH09  
PDH12  
PDH15  
2.4  
2.5  
2.6  
2.4  
6005  
647  
3.3  
6399  
656  
8647  
725  
9245  
735  
8100  
720  
WATTS  
AMPS  
BTUh  
3.3  
3.4  
3.5  
3.4  
7726  
883  
4
8531  
917  
11278  
1039  
4.7  
12234  
1073  
4.9  
10700  
1010  
4.5  
WATTS  
AMPS  
BTUh  
4.1  
10530  
1197  
5.3  
10850  
1212  
5.4  
14550  
1377  
6.1  
15940  
1439  
6.3  
13300  
1300  
WATTS  
AMPS  
5.8  
RATING POINT  
ARI 310/380  
12  
Cooling & Heating Performance  
PDE 265V - Extended Cooling Performance  
OUTDOOR DRY BULB TEMP. (DEGREES F AT 40% R.H.)  
75  
85  
95  
105  
110  
INDOOR WET BULB TEMP. (DEGREES F AT 80 F D.B.)  
72  
7762  
692  
67  
6892  
691  
62  
6075  
693  
72  
6907  
755  
67  
5944  
755  
62  
5251  
758  
72  
9055  
522  
67  
8709  
531  
62  
8062  
536  
2
72  
8624  
569  
67  
8131  
575  
62  
7500  
582  
72  
8285  
640  
67  
7700  
640  
62  
6815  
640  
BTUh  
WATTS  
AMPS  
SHR  
PDE07  
PDE09  
PDE12  
PDE15  
2.6  
2.6  
2.6  
2.8  
2.8  
2.8  
2
2
2.1  
2.1  
2.2  
2.4  
2.4  
2.40  
0.77  
9000  
800  
0.55  
9072  
865  
0.81  
8055  
864  
0.99  
7101  
866  
0.58  
8073  
943  
0.87  
6948  
943  
0.99  
6138  
947  
0.53  
10584  
653  
0.72  
10179  
663  
0.96  
9423  
670  
3.1  
0.54  
10080  
711  
0.74  
9504  
718  
0.98  
8766  
727  
0.54  
9684  
800  
0.99  
7965  
800  
BTUh  
WATTS  
AMPS  
SHR  
4
4
4
4.3  
4.3  
4.4  
3.1  
3.1  
3.3  
3.3  
3.3  
3.7  
3.7  
3.70  
0.71  
12000  
1120  
4.80  
0.71  
15000  
1530  
5.90  
0.51  
12096  
1211  
5.2  
0.75  
10740  
1210  
5.2  
0.92  
9468  
1213  
5.2  
0.54  
10764  
1320  
5.6  
0.8  
0.91  
8184  
1326  
5.7  
0.49  
14112  
914  
0.66  
13572  
928  
0.89  
12564  
939  
4
0.5  
0.69  
12672  
1006  
4.3  
0.91  
11688  
1018  
4.3  
0.5  
0.91  
10620  
1120  
4.8  
9264  
1320  
5.6  
BTUh  
WATTS  
AMPS  
SHR  
13440  
996  
12912  
1120  
4.8  
4
4
4.3  
0.51  
15120  
1654  
6.3  
0.75  
13425  
1652  
6.3  
0.92  
11835  
1657  
6.4  
0.54  
13455  
1804  
6.9  
0.8  
0.91  
10230  
1812  
7
0.49  
17640  
1248  
4.9  
0.66  
16965  
1268  
4.9  
0.89  
15705  
1282  
5
0.5  
0.69  
15840  
1374  
5.3  
0.91  
14610  
1391  
5.3  
0.5  
0.91  
13275  
1530  
5.9  
11580  
1804  
6.9  
BTUh  
WATTS  
AMPS  
SHR  
16800  
1360  
5.3  
16140  
1530  
5.9  
0.49  
0.72  
0.88  
0.51  
0.77  
0.87  
0.47  
0.63  
0.85  
0.48  
0.66  
0.87  
0.48  
0.87  
0.68  
RATING POINT  
ARI 310/380  
PDH 265V - Extended Cooling Performance  
OUTDOOR DRY BULB TEMP. (DEGREES F AT 40% R.H.)  
105  
110  
75  
85  
95  
INDOOR WET BULB TEMP. (DEGREES F AT 80 F D.B.)  
72  
9055  
522  
67  
8709  
531  
62  
8062  
536  
2
72  
8624  
569  
67  
8131  
575  
62  
7500  
582  
72  
8285  
640  
67  
7700  
640  
62  
6815  
640  
72  
7762  
692  
67  
6892  
691  
62  
6075  
693  
2.6  
72  
6907  
755  
67  
5944  
755  
2.8  
62  
5251  
758  
2.8  
BTUh  
WATTS  
AMPS  
SHR  
PDH07  
PDH09  
PDH12  
PDH15  
2
2
2.1  
2.1  
2.2  
2.4  
2.4  
2.6  
2.6  
2.8  
2.40  
0.77  
9000  
800  
0.53  
10584  
653  
0.72  
10179  
663  
0.96  
9423  
670  
3.1  
0.54  
10080  
711  
0.74  
9504  
718  
0.98  
8766  
727  
0.54  
9684  
800  
0.99  
7965  
800  
0.55  
9072  
865  
0.81  
8055  
864  
0.99  
7101  
866  
4
0.58  
8073  
943  
0.87  
6948  
943  
4.3  
0.99  
6138  
947  
4.4  
BTUh  
WATTS  
AMPS  
SHR  
3.1  
3.1  
3.3  
3.3  
3.3  
3.7  
3.7  
4
4
4.3  
3.70  
0.71  
12000  
1120  
4.80  
0.71  
14500  
1480  
5.7  
0.49  
14112  
914  
0.66  
13572  
928  
0.89  
12564  
939  
4
0.5  
0.69  
12672  
1006  
4.3  
0.91  
11688  
1018  
4.3  
0.5  
0.91  
10620  
1120  
4.8  
0.51  
12096  
1211  
5.2  
0.75  
10740  
1210  
5.2  
0.92  
9468  
1213  
5.2  
0.54  
10764  
1320  
5.6  
0.8  
0.91  
8184  
1326  
5.7  
BTUh  
WATTS  
AMPS  
SHR  
13440  
996  
12912  
1120  
4.8  
9264  
1320  
5.6  
4
4
4.3  
0.49  
17052  
1208  
4.7  
0.66  
16400  
1227  
4.7  
0.89  
15182  
1240  
4.8  
0.5  
0.69  
15312  
1329  
5.1  
0.91  
14123  
1345  
5.1  
0.5  
0.91  
12833  
1480  
5.7  
0.51  
14616  
1600  
6.1  
0.75  
12978  
1598  
6.1  
0.92  
11441  
1603  
6.2  
0.54  
13007  
1745  
6.7  
0.8  
0.91  
9889  
1752  
6.7  
BTUh  
WATTS  
AMPS  
SHR  
16240  
1316  
5.1  
15602  
1480  
5.7  
11194  
1745  
6.7  
0.48  
0.65  
0.88  
0.49  
0.68  
0.89  
0.49  
0.9  
0.5  
0.74  
0.9  
0.53  
0.79  
0.9  
0.70  
RATING POINT  
ARI 310/380  
Extended Heating Performance  
OUTDOOR DRY BULB TEMP. (DEGREES F)  
37  
42  
5540  
518  
47  
6300  
540  
52  
6900  
549  
57  
7620  
580  
BTUh  
5250  
509  
2.3  
WATTS  
AMPS  
BTUh  
PDH07  
PDH09  
PDH12  
PDH15  
2.4  
2.5  
2.6  
2.4  
6005  
647  
3.3  
6399  
656  
8647  
725  
9245  
735  
8100  
720  
WATTS  
AMPS  
BTUh  
3.3  
3.4  
3.5  
3.4  
7726  
883  
4
8531  
917  
11278  
1039  
4.7  
12234  
1073  
4.9  
10700  
1010  
4.5  
WATTS  
AMPS  
BTUh  
4.1  
10530  
1197  
4.5  
10850  
1212  
4.6  
14550  
1377  
5.3  
15940  
1439  
5.5  
13300  
1300  
WATTS  
AMPS  
5
RATING POINT  
ARI 310/380  
13  
Electric Heat Data  
Electric Heat Data  
PDE07K0  
PDE/PDH07K  
PDE/PDH07R  
HEATER WATTS  
0 Kw  
2000  
230  
6824  
8.9  
1635  
208  
5580  
7.9  
3000  
230  
2450  
208  
2000  
3000  
VOLTAGE  
230/208  
265  
HEATING BTUh  
0
0
10236  
13.2  
16.8  
20  
8360  
12.2  
15.6  
20  
6824  
7.6  
9.6  
15  
10236  
11.4  
14.6  
20  
HEATING CURRENT (AMPS)  
MINIMUM CIRCUIT AMPACITY  
BRANCH CIRCUIT FUSE (AMPS)  
4.0  
15  
11.4  
15  
10.0  
15  
Electric Heat Data  
PDE09K0  
PDE/PDH09K  
PDE/PDH09R  
3000  
HEATER WATTS  
0 Kw  
2000  
230  
6824  
8.9  
1635  
208  
5580  
7.9  
3000  
230  
2450  
208  
5000  
230  
4090  
208  
2000  
5000  
VOLTAGE  
230/208  
265  
HEATING BTUh  
0
0
10236  
13.2  
16.8  
20  
8360  
12.2  
15.6  
20  
17060  
21.5  
27.2  
30  
13960  
20.5  
26.0  
30  
6824  
7.6  
9.8  
15  
10236  
11.4  
17060  
19.0  
24.1  
30  
HEATING CURRENT (AMPS)  
MINIMUM CIRCUIT AMPACITY  
BRANCH CIRCUIT FUSE (AMPS)  
5.2  
15  
11.4  
15  
10.0  
15  
14.6  
20  
Electric Heat Data  
PDE12K0  
PDE/PDH12K  
PDE/PDH12R  
3000  
HEATER WATTS  
0 Kw  
2000  
230  
6824  
8.9  
1635  
208  
5580  
7.9  
3000  
230  
2450  
208  
5000  
230  
4090  
208  
2000  
5000  
VOLTAGE  
230/208  
265  
HEATING BTUh  
0
0
10236  
13.2  
16.8  
20  
8360  
12.2  
15.6  
20  
17060  
21.5  
27.2  
30  
13960  
20.5  
26.0  
30  
6824  
7.6  
9.8  
15  
10236  
11.4  
17060  
19.0  
24.1  
30  
HEATING CURRENT (AMPS)  
MINIMUM CIRCUIT AMPACITY  
BRANCH CIRCUIT FUSE (AMPS)  
7.1  
15  
11.4  
15  
10.0  
15  
14.6  
20  
Electric Heat Data  
PDE15K0  
PDE/PDH15K  
PDE/PDH15R  
3000  
HEATER WATTS  
0 Kw  
2000  
230  
6824  
8.9  
1635  
208  
5580  
7.9  
3000  
230  
2450  
208  
5000  
230  
4090  
208  
2000  
5000  
VOLTAGE  
230/208  
265  
HEATING BTUh  
0
0
10236  
13.2  
16.8  
20  
8360  
12.2  
15.6  
20  
17060  
21.5  
27.2  
30  
13960  
20.5  
26.0  
30  
6824  
7.6  
9.8  
15  
10236  
11.4  
17060  
19.0  
24.1  
30  
HEATING CURRENT (AMPS)  
MINIMUM CIRCUIT AMPACITY  
BRANCH CIRCUIT FUSE (AMPS)  
9.1  
15  
11.4  
15  
10.0  
15  
14.6  
20  
14  
ELECTRICAL RATING TABLES  
Use ONLY wiring size recommended for  
single outlet branch circuit.  
WARNING  
WIRE SIZE  
Use ONLY type and size fuse or HACR  
circuit breaker indicated on unit’s rating  
plate. Proper current protection to the unit  
is the responsibility of the owner. NOTE:  
A time delay fuse is provided with 265V  
units.  
ELECTRIC SHOCK HAZARD  
FUSE/CIRCUIT  
BREAKER  
Turn off electric power before service or  
installation. All electrical connections and  
wiring MUST be installed by a qualified  
electrician and conform to the National  
Electrical Code and all local codes which  
have jurisdiction. Failure to do so could result  
in serious personal injury or death.  
Unit MUST be grounded from branch  
circuit through service cord to unit, or  
through separate ground wire provided  
on permanently connected units. Be sure  
that branch circuit or general purpose  
outlet is grounded. The field supplied  
outlet must match plug on service cord  
and be within reach of service cord. Refer  
to Table 1 for proper receptacle and fuse  
type. Do NOT alter the service cord or  
plug. Do NOT use an extension cord.  
NOTE: Use Copper Conductors ONLY. Wire sizes  
are per NEC, check local codes for overseas applica-  
tions.  
GROUNDING  
Table 1  
250 V Receptacles and Fuse Types  
AMPS  
15  
20*  
30  
30  
The field supplied outlet must match plug  
on service cord and be within reach of  
service cord. Refer to Table 1 for proper  
receptacle and fuse type. Do NOT alter  
the service cord or plug. Do NOT use an  
extension cord.  
RECEPTACLE  
RECEPTACLE  
WIRE SIZING  
TIME-DELAY TYPE FUSE  
(or HACR circuit breaker)  
15  
20  
HACR – Heating, Air Conditioning, Refrigeration  
May be used for 15 Amp applications if fused for 15 Amp  
NOTE: 265 volt units are hard wired.  
Use recommended wire size given  
in Table 2 and install a single branch  
circuit. All wiring must comply with local  
and national codes. NOTE: Use copper  
conductors only.  
*
Table 2  
Recommended branch circuit wire sizes*  
NAMEPLATE / MAXIMUM  
CIRCUIT BREAKER SIZE  
AWG WIRE SIZE**  
15  
20  
30  
14  
12  
10  
AWG – American Wire Gauge  
Single circuit from main box  
*
** Based on copper wire, single insulated conductor at 60°C  
POWER CORD INFORMATION (230/208V MODELS ONLY)  
All Friedrich 230/208V PTAC units are shipped from the  
factory with a Leakage Current Detection Interrupter (LCDI)  
equipped power cord. The LCDI device meets the UL and  
NEC requirements for cord connected air conditioners  
Typical LCDI Devices  
TEST  
effective August 2004.  
RESET  
TEST  
RESET  
To test your power supply cord:  
WARNING  
TEST BEFORE EACH USE  
1. PRESS RESET BUTTON  
2. PLUG LCDI INTO POWER  
RECEPTACLE  
1. Plug power supply cord into a grounded 3 prong outlet.  
WARNING  
TEST BEFORE EACH USE  
3. PRESS TEST BUTTON,  
1. PRESS RESET BUTTON  
RESET BUTTON SHOULD  
2. PLUG LCDI INTO POWER  
POP UP  
RECEPTACLE  
2. Press RESET.  
4. PRESS TEST BUTTON,  
FOR USE  
DO NOT USE IF ABOVE TEST  
FAILS  
3. PRESS TEST BUTTON,  
RESET BUTTON SHOULD  
POP UP  
3. Press TEST (listen for click; Reset button trips and pops  
out).  
4. PRESS TEST BUTTON,  
FOR USE  
DO NOT USE IF ABOVE TEST  
FAILS  
WHEN GREEN LIGHT IS ON  
IT IS WORKING PROPERLY  
WHEN GREEN LIGHT IS ON  
IT IS WORKING PROPERLY  
4. Press and release RESET (listen for click; Reset button  
latches and remains in). The power supply cord is ready for  
operation.  
NOTE: The LCDI device is not intended to be used as a  
switch.  
15/20A LCDI Device  
30A LCDI Device  
Once plugged in the unit will operate normally without the  
need to reset the LCDI device. If the LCDI device trips and  
FRP014  
15  
Model  
PDE07K  
Heater kW  
0.0  
Power Cord Kit  
PXPC23000  
PXPC23015  
STD  
Voltage  
230/208  
230/208  
230/208  
230/208  
230/208  
230/208  
230/208  
230/208  
230/208  
230/208  
230/208  
230/208  
230/208  
230/208  
230/208  
265  
Amperage  
Receptacle  
NEMA.6-15r  
NEMA.6-15r  
NEMA.6-20r  
NEMA.6-15r  
NEMA.6-15r  
NEMA.6-20r  
NEMA.6-30r  
NEMA.6-15r  
NEMA.6-15r  
NEMA.6-20r  
NEMA.6-30r  
NEMA.6-15r  
NEMA.6-15r  
NEMA.6-20r  
NEMA.6-30r  
NEMA.6-15r  
NEMA.6-20r  
NEMA.6-15r  
NEMA.6-20r  
NEMA.6-30r  
NEMA.6-15r  
NEMA.6-20r  
NEMA.6-30r  
NEMA.6-15r  
NEMA.6-20r  
NEMA.6-30r  
15  
15  
20  
15  
15  
20  
30  
15  
15  
20  
30  
15  
15  
20  
30  
15  
20  
15  
20  
30  
15  
20  
30  
15  
20  
30  
PDE/PDH07K  
2.0  
3.0  
PDE09K  
0.0  
PXPC23000  
PXPC23015  
STD  
PDE/PDH09K  
2.0  
3.0  
5.0  
PXPC23030  
PXPC23000  
PXPC23015  
STD  
PDE12K  
0.0  
PDE/PDH12K  
2.0  
3.0  
5.0  
PXPC23030  
PXPC23000  
PXPC23015  
PXPC23020  
STD  
PDE15K  
0.0  
PDE/PDH15K  
2.0  
3.0  
5.0  
PDE/PDH07R  
PDE/PDH09R  
2.0  
PXPC26515  
STD  
3.0  
265  
2.0  
PXPC26515  
STD  
265  
3.0  
265  
5.0  
PXPC26530  
PXPC26515  
STD  
265  
PDE/PDH12R  
PDE/PDH15R  
2.0  
265  
3.0  
265  
5.0  
PXPC26530  
PXPC26515  
PXPC26520  
STD  
265  
2.0  
265  
3.0  
265  
5.0  
265  
To install the line voltage power leads and conduit  
to chassis, follow the instructions below.  
PXCJA Conduit Kit is required with this setup.  
Electrical Wiring for 265 Volt  
Models  
Power Cord Installation  
All 265V PTAC/PTHP units come with a factory installed non-LCDI  
power cord for use in a subbase. If the unit is to be hard-wired refer to  
the instructions below.  
1. Follow the removal process of the chassis’s junction box.  
listed in the installation manual (Figure 25, step 2, page 19).  
2. .Prepare the 265V (or 230V) power cord for connection to the chas-  
sis’ power cord connector by cutting the cord to the appropriate  
length (Figure15). Power cord harness selection shown on Table  
above.  
NOTE:  
It is recommended that the PXSB subbase assembly, the  
PXCJA conduit kit (or equivalent) be installed on all hardwire  
units. If installing a  
mounted unit, make sure the  
chassis can be removed from the sleeve for service and  
maintenance.  
WARNING  
Electrical Shock Hazard  
Turn off electrical power before service  
or installation.  
ALL electrical connections and wiring  
MUST be installed by a qualified  
electrician and conform to the National  
Code and all local codes which have  
jurisdiction.  
Failure to do so can result in property  
damage, personal injury and/or death.  
16  
TO CHASSIS JUNCTION  
STRAIGHT  
CONNECTOR  
WALL CONNECTION  
JUNCTION  
BOX  
4.0 IN.  
GROUND  
SCREW  
GROUND  
WIRE  
HARNESS  
COVER  
SCREWS  
18.0 IN.  
JUNCTION  
BOX COVER  
EXPOSE  
WIRES  
(1.0 IN.)  
FRP033  
TRIM HARNESS  
TO LENGTH  
LEADING SIDE FOR  
WIRE HARNESS INSERTION  
LOCKNUT  
SPACER  
SPACER  
STRIP WIRE ENDS (0.5 IN.)  
TO WALL JUNCTION  
CHASSIS  
JUNCTION  
BOX  
FRP032  
3. Route the cut ends of harness through the conduit connector  
assembly and conduit sleeve. Be sure to use the supplied  
conduit bushing to prevent damage to the cord by the conduit.  
CONDUIT  
CONNECTOR  
The cord should pass through the Locknut, Spacer, Chassis  
Junction Box, Conduit Connector, Bushing, then the Conduit  
Sleeve. Refer to wire harness insertion diagram.  
4. Route the cut ends of the power cord through the elbow connector  
at the other end of the conduit. Tighten screws on elbow connector  
to secure conduit sleeve.  
BUSHING  
CONDUIT  
SLEEVE  
5. Fasten and secure the elbow connector to the wall junction box  
cover with locknut. Place and mount the wall junction box with  
the four wall mounting screws making sure to pass the wall lines  
through the junction box. Connect and join all wall lines with the  
stripped ends using wire nuts. Tighten both screws of the wall  
junction box cover to junction box.  
EXITING SIDE FOR  
WIRE HARNESS  
FRP034  
17  
To control the unit with a wall mounted thermostat  
follow the steps below:  
Remote Control Thermostat  
Installation  
1. Unplug the unit before doing any work.  
2. With the front.cover removed locate the dip switches located below  
the Smart Center control panel. Switch Dip switch 2 to the up on  
'ON' position.  
Install Thermostat  
1. Approximately 5 ft. from the  
2. Close to or in a frequently used room, preferably on an inside wall.  
3. On a section of wall without pipes or ductwork.  
3. Remove the low voltage terminal block from the unit.  
4. Connect the corresponding terminals from the wall thermostat to  
the terminal block.  
The Thermostat should NOT be mounted:  
5. Replace the terminal block on the unit.  
6. Restore power to the unit.  
1. Close to a window, on an outside wall, or next to a door leading  
outside.  
2. Where it can be exposed to direct sunlight or heat, such as the sun,  
7. The unit is now controlled by the wall thermostat only.  
a lamp,  
or any temperature radiating object which  
may cause a false reading.  
8. If the accessory escutcheon kit (PDXRTA) is to be used, install it  
over the existing control panel.  
3. Close to or in the direct  
of supply registers and/or return  
air grilles.  
NOTE:.  
The unit mounted controls no longer control the unit. To restore  
the unit mounted controls move dip switch 2 to the down or  
'OFF' position.  
4. Any areas with poor air circulation, such as a corner, behind a  
door, or an alcove.  
Remote Thermostat and Low  
Voltage Control Connections  
Remote Thermostat  
Thermostat Connections  
R
= 24V Power from Unit  
Y
= Call for Cooling  
W = Call for Heating  
= Reversing Valve Energized in cooling mode (PDH Models Only)  
All Friedrich PD model PTAC units are factory  
to be controlled  
O
by either the chassis mounted Smart Center or a 24V remote wall mounted  
thermostat. The thermostat may be auto or manual changeover as long as  
GL = Call for Low Fan  
GH = Call for High Fan  
the control  
matches that of the PTAC unit.  
C
= Common Ground  
NOTE:  
All PDE models require a single stage cool, single stage heat.  
thermostat. All PDH models require a single stage cool, dual.  
stage heat thermostat with an O reversing valve control. The  
*If only one G terminal is present on thermostat connect to GL for low  
speed fan or to GH for high speed fan operation.  
Friedrich RT6 thermostat can be  
for either model.  
Control board with optional PDXRT escutcheon kit installed  
FRP029  
18  
Desk Control Terminals  
The Friedrich PD model PTAC has built-in provisions for connection to an  
external switch to control power to the unit. The switch can be a central  
desk control system or even a normally open door switch.  
WARNING  
Electrical Shock Hazard  
Turn off electrical power before service  
or installation.  
For desk control operation connect one side of the switch to the D1 terminal  
and the other to the D2 terminal. Whenever the switch closes the unit  
operation will stop.  
ALL electrical connections and wiring  
MUST be installed by a qualified  
electrician and conform to the National  
Code and all local codes which have  
jurisdiction.  
Improper connection of the thermostat  
control wiring and/or tampering with the  
units internal wiring may result in property  
damage, personal injury or death.  
NOTE:  
The desk control system and switches must be  
supplied.  
Energy Management  
Sometimes known as Front Desk Control, an input is provided so that the  
unit can be manually disabled from a remote location. If the unit detects  
24Vac on this input, it will automatically turn itself off. If no voltage is  
detected on the input, the unit will run normally.  
NOTE:  
It is the installer's responsibility to ensure that all control.wiring  
connections are made in accordance with the installation  
instructions. Improper connection of the thermostat control  
wiring and/or tampering with the unit's internal wiring can  
void the equipment warranty. Other manufacturer's PTACs  
and even older Friedrich models may have different control  
wire connections. Questions concerning proper connections  
to the unit should be directed to Friedrich.  
19  
FRIEDRICH DIGITAL CONTROL FEATURES  
The new Friedrich digital PTAC has state of the art features to improve guest comfort, indoor air quality and conserve  
energy. Through the use of specifically designed control software for the PTAC industry Friedrich has accomplished  
what other Manufacturer’s have only attempted – a quiet, dependable, affordable and easy to use PTAC.  
Below is a list of standard features on every Friedrich PTAC and their benefit to the owner.  
By digitally monitoring desired room temperature the room is controlled more precisely than conventional  
systems. The large, easy to read LED display can show either set-point or actual room temperature as  
selected by owner.  
Digital Temperature  
Readout  
When the unit is powered off the unit can be returned directly to heating or cooling mode by pressing the  
‘Heat’ or ‘Cool’ buttons without the confusing power up sequence of some controls. One-touch control  
takes guess-work out of unit control delivering a more enjoyable experience and eliminating front-desk  
calls.  
One-Touch  
Operation  
By having separate control buttons and indicators for both fan and mode settings the Friedrich digital con-  
trol eliminates the confusion of previous digital PTACs. The accurate temperature setting provides greater  
guest comfort than other systems.  
Individual Mode and  
Fan Control Buttons  
The fan start and stop delays prevent abrupt changes in room acoustics due to the compressor energizing  
or stopping immediately. Upon call for cooling or heating the unit fan will run for five seconds prior to en-  
ergizing the compressor. Also, the fan off delay allows for “free cooling” by utilizing the already cool indoor  
coil to its maximum capacity by running for 30 seconds after the compressor.  
Quiet Start/Stop  
Fan Delay  
Some applications require the use of a wall mounted thermostat. All new Friedrich PTACs may be switched  
from unit control to remote thermostat control easily without the need to order a special model or acces-  
sory kit.  
Remote Thermostat  
Operation  
Wireless Remote  
Control Ready  
Guests can adjust the temperature and mode of the unit through the use of an optional hand held wireless  
remote, improving guest comfort and relaxation.  
The new Friedrich digital PTAC features a self diagnostic program that can alert maintenance to compo-  
nent failures or operating problems. The internal diagnostic program saves properties valuable time when  
diagnosing running problems.  
Internal Diagnostic  
Program  
The self diagnosis program will also store error codes in memory if certain conditions occur and correct  
themselves such as extreme high or low operating conditions or activation of the room freeze protection  
feature. Storing error codes can help properties determine if the unit faced obscure conditions or if an error  
occurred and corrected itself.  
Service Error Code  
Storage  
The on-board processor monitors time between demand cycles (heat or cool) and will cycle the fan every  
9 minutes to sample the room condition and determine if the desired conditions are met. This allows the  
room to have similar benefi ts to a remote mounted stat without the complication or cost of a wall mounted  
thermostat.  
Constant Comfort  
Room Monitoring  
Electronic  
Temperature  
Limiting  
By limiting the operating range the property can save energy by eliminating “max cool” or “max heat” situ-  
ations common with older uncontrolled systems. The new electronic control allows owners to set operating  
ranges for both heating and cooling independently of one another.  
When the PTAC senses that the indoor room temperature has fallen to 40°F the unit will cycle on high fan  
and the electric strip heat to raise the room temperature to 46°F then cycle off again. This feature works  
regardless of the mode selected and can be turned off. The control will also store the Room Freeze cycle  
in the service code memory for retrieval at a later date. This feature ensures that unoccupied rooms do not  
reach freezing levels where damage can occur to plumbing and fixtures.  
Room Freeze  
Protection  
Multiple compressors starting at once can often cause electrical overloads and premature unit failure.  
The random restart delay eliminates multiple units from starting at once following a power outage or initial  
power up. The compressor delay will range from 180 to 240 seconds.  
Random  
Compressor Restart  
20  
'(/(4+*"&-.4<-*">)2<+4(-.  
'(/(4+*"&-.4<-*"5+.2*  
FRP030  
ꢀ!"#$%"ꢀ&"'($)*+,  
32+4:&--*"0-12*$"85';9  
 !"#$%&'#&(#)*+',-.#+,%[0$-"1#',#1&(23*.#*33#'"42"-*'$-"(#&%#1"0-""(#  
5*!-"%!"&'#6ꢀ#589# ,#(:&'+!#',#1"0-""(#;"3(&$(#2-"((#'!"#Q5*%#=%3.R#*%1#  
Q?,:#5*%R#@$'',%(#(&4$3'*%",$(3.#),-#'!-""#("+,%1(9# !"#1&(23*.#:&33#(!,:#  
*#Q;R#*(#*+A%,:3"10"4"%'#,)#'!"#+!*%0"9## ,#-"B"-'#@*+A#',#ꢀ#5#2-"((#'!"#  
Q5*%#=%3.R#*%1#Q?,:#5*%R#@$'',%(#(&4$3'*%",$(3.#),-#'!-""#("+,%1(9# !"#  
1&(23*.#:&33#(!,:#*%#Q5R#*(#*+A%,:3"10"4"%'#,)#'!"#+!*%0"9  
E)'"-#2-"((&%0#'!"#QK"*'R#@$'',%D#*1F$('#'!"#'"42"-*'$-"#-"*1,$'#',#'!"#  
1"(&-"1#-,,4#'"42"-*'$-"#*%1#'!"#$%&'#:&33#+.+3"#'!"#-"(&('*%+"#!"*'#,%#  
*%1#,))#',#4*&%'*&%#*#+,4),-'*@3"#-,,49# !"#!"*'"-#:&33#+,4"#,%#*%.'&4"#  
'!*'#'!"#-,,4#'"42"-*'$-"#&(#G9Hꢀ#5#@"3,:#'!"#1"(&-"1#'"42"-*'$-"9# !"#  
)*%#,2"-*'&,%#&(#1"2"%1"%'#,%#'!"#)*%#4,1"#("3"+'"1D#"&'!"-#+,%'&%$,$(#  
,-#+.+3&%09#Q&2#(:&'+!#R#+,%'-,3(#'!"#)*%#4,1"D#(""#2*0"#SR#),-#("''&%09  
&--*(./"0-12  
;72</2.=,"32+4">)2<+4(-.  
C-"((&%0#'!"#Q;,,3R#@$'',%#:!&3"#'!"#$%&'#&(#&%#*%.#4,1"D#&%+3$1&%0#,))D#  
:&33#2$'#'!"#$%&'#&%',#+,,3&%0#4,1"9#E1F$('#'!"#'"42"-*'$-"#-"*1,$'#',#'!"#  
1"(&-"1#-,,4#'"42"-*'$-"#*%1#'!"#$%&'#:&33#+.+3"#'!"#+,42-"((,-#,%#*%1#  
,))#',#4*&%'*&%#*#+,4),-'*@3"#-,,49# !"#+,42-"((,-#:&33#+,4"#,%#*%.'&4"#  
'!*'#'!"#-,,4#'"42"-*'$-"#&(#G9Hꢀ#5#*@,B"#'!"#1"(&-"1#'"42"-*'$-"9# !"#  
)*%#,2"-*'&,%#&(#1"2"%1"%'#,%#'!"#)*%#4,1"#("3"+'"1D#"&'!"-#+,%'&%$,$(#  
,-#+.+3&%09##I""#5*%#J,1"#),-#)*%#+.+3"#+,%'-,39  
O%#'!"#"B"%'#,)#*#+,42-"((,-#)*&3$-"#&%#!"*'#2$42#4,1"#'!"#+,42-"((,-#4*.#  
@"#3,+A"1#,$'#',#2-,B&1"#!"*'#'!-,$0!#'!"#-"(&('*%+"#!"*'"-9# !&(#)"*'$-"#  
"%($-"(#'!*'#"B"%#&%#'!"#$%3&A"3.#"B"%'#,)#*#+,42-"((,-#)*&3$-"#'!"#-,,4#  
'"42"-*'$-"#+*%#@"#4*&%'*&%"1#$%'&3#'!"#+,42-"((,-#+*%#@"#("-B&+"19#Q&2#  
(:&'+!#G#+,%'-,3(#'!"#"4"-0"%+.#!"*'#("''&%0D#(""#2*0"#SR9  
!+."0-12  
E33#$%&'(#*-"#(!&22"1#:&'!#)*%#4,1"#("'#',#+,%'&%$,$(#),-#+,,3&%0#*%1#+.+3"#  
),-#!"*'&%09  
32+4(./"0-12  
C-"((&%0#'!"#QK"*'R#@$'',%#:!&3"#'!"#$%&'#&(#&%#*%.#4,1"D#&%+3$1&%0#,))D#:&33#  
2$'#'!"#$%&'#&%',#!"*'&%0#4,1"9  
!+.">.*,"0-12  
C-"((&%0#'!"#Q5*%R#@$'',%#:&33#-$%#'!"#)*%#',#*33,:#),-#*&-#+&-+$3*'&,%#&%#'!"#  
-,,4#:&'!,$'#,2"-*'&%0#'!"#+,42-"((,-#,-#!"*'"-#-"0*-13"((#,)#'!"#-,,4#  
,-#("'#'"42"-*'$-"9# !"#)*%#(2""1#("3"+'&,%#&(#4*1"#@.#2-"((&%0#"&'!"-#  
'!"#QK&0!#5*%RD#QJ"1#5*%R#,-#Q?,:#5*%R#@$'',%9  
32+4"567)"0-12*$"85'39  
L!"%#'!"#QK"*'R#@$'',%#&(#2-"(("1#&%&'&*33.#'!"#$%&'#:&33#"%"-0&M"#'!"#"3"+'-&+#  
-"(&('*%+"#!"*'#',#N$&+A3.#@-&%0#'!"#-,,4#',#'!"#("'#'"42"-*'$-"9##L!"%#'!"#  
1"(&-"1#-,,4#'"42"-*'$-"#)*33(#G9Hꢀ#5#@"3,:#'!"#1"(&-"1#("'#'"42"-*'$-"#'!"#  
$%&'#:&33#+.+3"#'!"#+,42-"((,-#,%#*%1#,2"-*'"#*(#*#!"*'#2$42#',#4*&%'*&%#  
'!"#-,,4#'"42"-*'$-"#:!&3"#-$%%&%0#4,-"#")[+&"%'3.#'!*%#-"(&('*%+"#!"*'#  
,%3.#4,1"3(9##O)#'!"#-,,4#'"42"-*'$-"#(!,$31#)*33#4,-"#'!*%#Pꢀ#5#)-,4#'!"#  
("'#'"42"-*'$-"#'!"#$%&'#:&33#-$%#'!"#-"(&('*%+"#!"*'"-9## !"#)*%#,2"-*'&,%#  
&(#1"2"%1"%'#,%#'!"#)*%#4,1"#("3"+'"1D#"&'!"-#+,%'&%$,$(#,-#+.+3&%09#Q&2#  
(:&'+!#R#+,%'-,3(#'!"#)*%#4,1"D#(""#2*0"#SR#),-#("''&%09##  
&,=*2:&-.4(.6-6$  
 !"#,:%"-#4*.#+!,,("#@"':""%#)*%#+.+3&%0#,-#)*%#+,%'&%$,$(#4,1"#@*("1#  
,%#2-,2"-'.#2-")"-"%+"#6W,'"X#YB"%#!"*'#4,%&',-&%0#*%1#N$&"'#('*-'Z(',2#  
)*%#1"3*.#,%3.#,2"-*'"#&%#)*%#+.+3"#4,1"89#5*%#+,%'&%$,$(#4,1"#&(#$("1#  
',#A""2#+,%('*%'#*&-\,:#+&-+$3*'&,%#&%#'!"#-,,4#1$-&%0#*33#'&4"(#'!"#$%&'#&(#  
Q=WR9#5*%#+.+3"#:&33#+,%("-B"#"%"-0.#@.#,%3.#,2"-*'&%0#'!"#)*%#:!&3"#'!"#  
+,42-"((,-#,-#"3"+'-&+#!"*'"-#&(#,2"-*'&%09#Q&2#(:&'+!#RUV#+,%'-,3(#'!"#)*%#  
4,1"D#(""#2*0"#SR#),-#("''&%09  
L!"%#'!"#,$'1,,-#+,&3#'"42"-*'$-"#)*33(#@"3,:#RTꢀ#5#),-#4,-"#'!*%#S#4&%U  
$'"(#'!"#$%&'#:&33#,2"-*'"#'!"#-"(&('*%+"#!"*'"-(#*%1#%,'#'!"#+,42-"((,-9#  
L!"%#'!"#,$'1,,-#+,&3#'"42"-*'$-"#-"*+!"(#VPꢀ#5#'!"#+,42-"((,-#:&33#@"#  
*33,:"1#',#,2"-*'"#*0*&%9  
21  
 !"!#$%&'()#*(%&+,-*&.)/0#&'()1!"0*$#!()  
 !"#$%&'()$*+"#,-.)/-+#%01#(20),!"(#$/"#+-,$)"%#$)#)!"#+-2"/#+"3)#!$.%#1-/)0-.#-3#)!"#%040)$+#56$/)#7".)"/8# !"#0.1')(#$/"#-.+9#:0(0*+"#$.%#$,,"((0*+"#20)!#)!"#  
3/-.)#,-:"/#/"6-:"%#3/-6#)!"#; <78  
 !/&23!#45&2-##!)"  
451 67')2',$018'/#139'))":'1N1 !"#$%14  
C51 6>'$#)+,"$1?'7*')/#.)'1D"7"#",21N1 !"#$%'(1EBF  
 !"#%040)$+#,-.)/-+#0(#(")#3/-6#)!"#3$,)-/9#)-#$++-2#$#)"61"/$)'/"#  
/$.4"#*")2"".#N=ꢀ#K#$.%#ONꢀ#K#0.#*-)!#!"$)0.4#$.%#,--+0.4#  
6-%"8#A01#520),!"(#MCN#,$.#*"#'("%#)-#(")#!04!#$.%#+-2#+060)(#3-/#  
"0)!"/#!"$)0.4#*-)![#,--+0.4#*-)!#-/#*-)!8  
U.#)!"#'.+0V"+9#":".)#-3#$#,-61/"((-/#3$0+'/"#$#!"$)#1'61#'.0)#6$9#  
*"#(20),!"%#)-#-1"/$)"#0.#-.+9#)!"#"+",)/0,#!"$)#6-%"#'.)0+#/"1$0/(#  
,$.#*"#6$%"8#B-:0.4#A01#520),!#=#)-#Q@DR8  
<51 =/>>1?%')7+(#/#1 !"#$%1<  
K/-6#)!"#3$,)-/9#(20),!"(#$/"#0.#)!"#%-2.#Y@KKY#1-(0)0-.8# !"#  
,!$/)#*"+-2#(!-2(#)!"#$:$0+$*+"#"+",)/-.0,#+060)0.4#/$.4"(8  
U.#-/%"/#)-#".$*+"#)!"#2$++#)!"/6-()$)#6-:"#A01#520),!#)-#Y@DY8  
@51 -/,1A0$>'1A+,#)+>1N1 !"#$%1@BC  
E51 G++71-)''H'1I)+#'$#"+,1N1 !"#$%1J  
<++#; <7(#$/"#(!011"%#3/-6#)!"#3$,)-/9#20)!#A01#520),!#JCL#0.#  
)!"#Q@KKR#1-(0)0-.8##U.#)!0(#1-(0)0-.#)!"#,--+0.4#3$.#,9,+"#20++#/'.#  
,-.)0.'-'(+9#1/-:0%0.4#$0/#,0/,'+$)0-.#%'/0.4#)!"#2$/6#6-.)!(8##  
 !"#!"$)0.4#3$.#,9,+"#0(#(")#)-#Y,9,+"Y#-.#$.%#-338## !"#3$.#6$9#  
*"#(")#)-#Y,-.)0.'-'(Y#6-%"#*9#(20),!0.4#A01#520),!#J#)-#Y@DY#  
1-(0)0-.8  
E.0)(#$/"#(!011"%#3/-6#)!"#3$,)-/9#20)!#)!"#/--6#3/""T"#1/-)",)0-.#  
".$*+"%8##S--6#K/""T"#;/-)",)0-.#,$.#*"#(20),!"%#-33#$)#)!"#  
-2."/R(#1/"3"/".,"#*9#6-:0.4#A01#520),!#Q#)-#Q@KKR8# !0(#3"$)'/"#  
20++#6-.0)-/#)!"#0.%--/#/--6#,-.%0)0-.(#$.%#0.#)!"#":".)#)!$)#)!"#  
/--6#3$++(#*"+-2#LPꢀK#)!"#'.0)#20++#,9,+"#-.#!04!#3$.#20)!#)!"#  
"+",)/0,#!"$)"/8# !0(#-,,'/(#/"4$/%+"((#-3#6-%"8  
 !/&23!#45-,  
He  
Po  
M
d  
we  
r
o  
Lo  
w
Fan  
Fn  
Spee  
d
Mode  
T
e
mp  
era  
ture  
DIP SWITCH  
UP  
1
2
3
4
5
6
7
DOWN  
LOCATION OF  
DIP SWITCHES  
ON UNIT  
Freeze guard  
Setpoint Limit 2  
Setpoint Limit 1  
Fan CON/CYC for cooling  
Fan CON/CYC for heating  
Wall Thermostat enable  
Electric heat only (for Heat Pumps)  
FRP028  
 !"#$%  
&'($)"*#"+,  
-.,$#"+,  
-/$#+)01 '##",2  
3*#"+,  
=
>6"/4".,9#?"$)#@:"//0%"# >.$*+"(#"+",)/0,#!"$)#-.+9#-1"/$)0-.#0.#)!"#":".)#-3#$#,-6C  
A-2.#C#D-/6$+#@1"/$)0-.  
E1#C#@:"//0%"(#,-61/"((-/#-1"/$)0-.8#  
F;A?#6-%"+(#-.+9G  
3-/#;A?#?"$)#;'61#  
B-%"+(  
1/"((-/#3$0+'/"#-.#?;#6-%"+(8  
H
J
L
I$++# !"/6-()$)#520),!  
K$.#79,+"#3-/#?"$)0.4  
K$.#79,+"#3-/#7--+0.4  
>.$*+"(#)!"#'("#-3#$#2$++#)!"/6-()$)#-/#'.0)#,-.)/-+(  
A-2.#C#E.0)#7-.)/-+(  
E1#C#>.$*+"(#I$++# !"/6-()$)#E($4"  
E1#C#7-.)0.'-'(  
<++-2(#("+",)0-.#-3#,-.)0.'-'(#3$.#-/#,9,+0.4#0.#!"$)0.4#6-%"8 A-2.#C#79,+"  
<++-2(#("+",)0-.#-3#,-.)0.'-'(#3$.#-/#,9,+0.4#0.#,--+0.4#6-%"8  
<++-2(#)!"#)"61"/$)'/"#(")1-0.)#/$.4"#)-#*"#$%&'()"%8  
A-2.#C#7-.)0.'-'(  
E1#C#79,+"  
M
N
Q
5")1-0.)#520),!#=  
A-2.  
A-2.  
N=KCONK  
E1  
NJKCOPK  
A-2. NMKCQOK  
F=R7CHN7G  
E1 NOKCQMK  
5")1-0.)#520),!#H  
F=N7CJP7G A-2. F=O7CHO7G E1  
E1 FHP7CHL7G  
S--6#K/""T"#;/-)",)0-.  
<++-2(#)!"#'.0)#)-#".('/"#)!"#0.%--/#/--6#)"61"/$)'/"#%-"(#  
.-)#3$++#*"+-2#LPK#":".#2!".#)'/."%#-338  
A-2.#C#K/""T"#;/-)",)0-.#>.$*+"%  
E1#C#K/""T"#;/-)",)0-.#A0($*+"%  
22  
DIGITAL CONTROL DIAGNOSTICS  
The chart below lists malfunctions and their description.  
1
2
3
4
5
6
7
8
9
Indoor air temp sensor open/short  
Indoor coil sensor open or short  
Outdoor coil sensor open/short  
Freeze Guard protection  
Display ‘F1’, with STATUS light flash  
Display ‘F2’, with STATUS light flash  
Display ‘F4’, with STATUS light flash  
Display ‘FP’, with STATUS light flash  
Indoor coil high temp protection  
Outdoor coil high temp protection  
Indoor coil freeze protection  
Defrost (heat pump type)  
STATUS light flash 8 times and off 3 sec, repeat  
STATUS light flash 6 times and off 3 sec, repeat  
STATUS light flash 5 times and off 3 sec, repeat  
STATUS light flash 7 times and off 3 sec, repeat  
STATUS light flash 9 times and off 3 sec, repeat  
Thermostat wiring error  
23  
MALFUNCTION ANALYSIS  
Switch is at the OFF position; or socket and plug is  
loosened; or power wire has malfunction; or power failure  
No power supply  
Fuse is burned out  
Replace the fuse  
Inspect the supply voltage. If it is lower 10% of the rated  
voltage, pleaselook for the reason, improve the  
Supply voltage is too low  
Check if optional switch (ON,OFF) is disconnected with the  
wire or it’s with mechanical failure; use the universal meter to  
check if contacts of the switch are conducting; if not, replace  
it with a new one with the same model and specification  
Switch is broken down  
Failure of crystal oscillator or reset circuit  
Replace those parts which have malfunction  
A/C can’t run  
Check the circuit and connect the wire according to the  
electric diagram attached to the unit  
The wire is loosened  
Replace the transformer  
Replace the controller  
Transformer is broken  
Controller is broken  
Receiver head is loosened  
First press the “AUTO” button of the manual switch. If the  
button is normal, recheck if the installation and connection of  
head and lines are correct. If correct, replace receiving head  
or remote controller.  
Receiver head is broken or it isn’t plugged well  
Remote controller has malfunction  
Lower the temperature of the thermostat  
(or increase the temperature when heating)  
The thermostat hasn’t been adjusted well  
Too much dust accumulated on the filter  
Heat exchanger is blocked  
Clean the filter  
Clean the dust accumulated on the surface of the heat  
exchanger  
Set the fan speed at high or medium fan speed  
Fan speed is set too slow  
A/C can run but  
it can’t cooling  
(or heating)  
1. Wrong wire connection; 2. whether the capacitor  
damaged or not; 3. the motor has malfunction; Connect the  
wire correctly or replace those parts which has malfunction.  
The fan can’t run or the fan speed is too slow  
24  
Check leakage, carry out vacuum-pumping after repairing  
leakage and charge refrigerant according to requirements  
Refrigerant is insufficient or leaking  
Refrigeration system is blocked  
Too much refrigerant  
Check whether the system is blocked by observing the  
condensation of the evaporator and the pressure value of  
the high pressure manometer, and then take measures to  
deal with the system.  
Release the redundant refrigerant in system  
Replace the compressor  
The efficiency of the compressor is low  
Condenser can’t discharge smoothly  
Get rid of the obstacle  
1. the wire is loosened; 2. thermal fuse is broken;  
3. temperature limiter is damaged; 4. electric heater is  
damaged; 5. controller is broken. correct the wore correctly  
or replace those parts which has malfunction.  
A/C on. No  
cooling (or  
heating)  
At the time of heating, the electric heater  
can’t run  
You can install the rain-proof and sun-proof board. If the  
cooling air is still insufficient, you are suggested  
to replace the A/C  
Outdoor temperature is too high  
Whether the cooling (heating) load is suitable  
Check the preset cooling (heating) load  
The air tightness in room is not good. People  
come in and go out frequently. There are  
Keep the air tightness well. Try not to use the electic  
appliances with a large quantity of heat  
heating devices in the room when A/C is cooling  
Check the reason and correct it.  
Supply voltage is unstable  
Check the circuit and connect the wire correctly  
according to the electic circuit diagram  
Wrong wire connection  
Replace fan’s capacitor with the same  
mode and specification  
The fan’s capacitor is broken  
Call for fan  
motor but fan  
motor will not  
come on  
The motor winding is of broken circuit or short  
circuit or the built in temperature limiter device  
in open circuit due to overheat.  
Replace those parts which has malfunction  
Replace the controller  
The controller has malfunction  
Replace capacitor; connect the wire correctly  
according to the electric circuit diagram  
The compressor capacitor is broken; wrong wire  
connection  
Compressor  
isn’t running  
(controller is  
with output)  
Check with a multimeter if the enclosed motor windings of  
compressor is with short or broken circuit or earthing. If so, it  
is needed to replace it with the same type and specifications.  
The compressor’s motor is burned out  
The compressor is jammed or blocked  
Knock the compressor housing with a rubber bar or with  
a hammer padding with a wood, the compressor might be  
shocked and run. If not, change the compressor.  
25  
Adjust the quantity of the refrigerant  
Replace capillary  
Refrigerant is insufficient or super abundance  
Capillary is blocked and the suction  
temperature is rising  
Protector is  
activated due to  
overheating of  
the compressor  
The compressor can run smoothly or is stuck.  
The air discharge valve is damaged.  
Replace the compressor  
Use the multimeter to check whether the contact point of the  
compressor is conducted at the timer of non-subheating. If it  
can’t be conducted, please replace the protector.  
Protector has malfunction  
Check the reason, improve the power supply condition and  
add the regulated power supply  
Supply voltage is abnormal  
The radiating for evaporator and condensor is  
not good; Poor air ventilation  
Get rid of the dust on the evaporator and condensor, remove  
the obstacles at the air outlet  
Compressor  
is ON-OFF  
frequently  
The air conditioner capability does not match  
the area of the room, i.e. so called “Big system,  
small room”.  
Slect the A/C which is applicable to the room areas  
Replace the battery  
Reveiving distance of remote control  
is too short  
Replace the battery  
LCD display flashes or when pressing  
the transmit button the entire screen  
is displayed.  
Battery’s capacity is insufficient  
The LCD frame hasn’t fixed well  
Replace the battery  
LED display is found short of stroke  
Fix the LCD frame properly  
The compressor hasn’t installed well and the  
Check whether the base is firm  
base is unstable  
The unit hasn’t placed flatly and stable  
Adjust the unit’s position  
Vibration and  
noise are  
abnormal  
The unit’s support is unstable  
Strengthen the support or refit it  
There are foreign objects on the unit  
Screws are loosened  
Get rid of the foreign objects  
Tighten the screws  
As for the above malfunction analysis, there aren’t malfunction related to heating for the cooling only unit.  
26  
COMPONENTS TESTING  
BLOWER / FAN MOTOR  
Capacitor Check with Capacitor Analyzer  
Asinglephasepermanentsplitcapacitormotorisusedtodrive  
the evaporator blower and condenser fan. A self-resetting  
overload is located inside the motor to protect against high  
temperature and high amperage conditions.  
The capacitor analyzer will show whether the capacitor  
is “open” or “shorted.” It will tell whether the capacitor  
is within its micro farads rating and it will show whether  
the capacitor is operating at the proper power-factor  
percentage. The instrument will automatically discharge  
the capacitor when the test switch is released.  
WARNING  
Capacitor Connections  
ELECTRIC SHOCK HAZARD  
Disconnect power to the unit before  
servicing. Failure to follow this warning  
could result in serious injury or death.  
The starting winding of a motor can be damaged by a  
shorted and grounded running capacitor. This damage  
usually can be avoided by proper connection of the running  
capacitor terminals.  
BLOWER / FAN MOTOR TEST  
From the supply line on a typical 230 volt circuit, a 115 volt  
potential exists from the “R” terminal to ground through a  
possibleshortinthecapacitor. However, fromtheSorstart  
terminal, a much higher potential, possibly as high as 400  
volts, exists because of the counter EMF generated in the  
start winding. Therefore, the possibility of capacitor failure  
is much greater when the identified terminal is connected  
to the “S” or start terminal. The identified terminal should  
always be connected to the supply line, or “R” terminal,  
never to the “S” terminal.  
1. Make sure the motor has cooled down.  
2. Disconnect the fan motor wires from the control board.  
3. Test for continuity between the windings also, test to  
ground.  
4. If any winding is open or grounded replace the motor.  
When connected properly, a shorted or grounded running  
capacitor will result in a direct short to ground from the “R”  
terminal and will blow the line fuse. The motor protector  
will protect the main winding from excessive temperature.  
CAPACITORS  
WARNING  
ELECTRIC SHOCK HAZARD  
Turn off electric power before servicing.  
Discharge capacitor with a 20,000 Ohm 2 Watt  
resistor before handling.  
Failure to do so may result in personal injury,  
or death.  
Many motor capacitors are internally fused. Shorting the  
terminals will blow the fuse, ruining the capacitor. A 20,000  
ohm 2 watt resistor can be used to discharge capacitors  
safely. Remove wires from capacitor and place resistor  
across terminals. When checking a dual capacitor with  
a capacitor analyzer or ohmmeter, both sides must be  
tested.  
27  
COMPONENTS TESTING (Continued)  
HEATER ELEMENTS AND LIMIT SWITCHES’  
SPECIFICATIONS  
All heat pumps and electric heat models are equipped  
with a heating element and a limit switch (bimetal ther-  
mostat). The limit is in series with the element and will  
interrupt the power at a designed temperature.  
DRAIN PAN VALVE  
During the cooling mode of operation, condensate which  
collects in the drain pan is picked up by the condenser fan  
blade and sprayed onto the condenser coil. This assists  
in cooling the refrigerant plus evaporating the water.  
During the heating mode of operation, it is necessary that  
water be removed to prevent it from freezing during cold  
outside temperatures. This could cause the condenser  
fan blade to freeze in the accumulated water and prevent  
it from turning.  
Should the blower motor fail, filter become clogged or air-  
flow be restricted etc., the high limit switch will open and  
interrupt the power to the heater before reaching an un-  
safe temperature condition.  
To provide a means of draining this water, a bellows type  
drain valve is installed over a drain opening in the base  
pan.  
TESTING THE HEATING ELEMENTS AND  
LIMIT SWITCHES  
WARNING  
This valve is temperature sensitive and will open when  
the outside temperature reaches 40°F. The valve will  
close gradually as the temperature rises above 40°F to  
fully close at 60°F.  
ELECTRIC SHOCK HAZARD  
Disconnect power to the unit before  
servicing. Failure to follow this warning  
could result in serious injury or death.  
Testing of the heating elements can be made with an  
ohmmeter or continuity tester across the terminals after  
the power wires have been removed. Test the limit switch  
for continuity across its input and output terminals.Test  
below the limit switch’s reset temperature.  
Bellows Assembly  
Drain Pan Valve  
28  
REFRIGERATION SEQUENCE OF OPERATION  
A good understanding of the basic operation of the  
refrigeration system is essential for the service technician.  
Without this understanding, accurate troubleshooting of  
refrigeration system problems will be more difficult and time  
consuming, if not (in some cases) entirely impossible. The  
refrigeration system uses four basic principles (laws) in its  
operation they are as follows:  
The refrigerant leaves the condenser Coil through the liquid  
line as a warm high pressure liquid. It next will pass through  
the refrigerant drier (if so equipped). It is the function of the  
driertotrapanymoisturepresentinthesystem,contaminants,  
and large particulate matter.  
The liquid refrigerant next enters the metering device. The  
metering device is a capillary tube. The purpose of the  
metering device is to “meter” (i.e. control or measure) the  
quantity of refrigerant entering the evaporator coil.  
1. “Heat always flows from a warmer body to a cooler  
body.”  
2. “Heat must be added to or removed from a substance  
before a change in state can occur”  
In the case of the capillary tube this is accomplished (by  
design) through size (and length) of device, and the pressure  
difference present across the device.  
3. “Flow is always from a higher pressure area to a lower  
pressure area.”  
Since the evaporator coil is under a lower pressure (due to  
the suction created by the compressor) than the liquid line,  
the liquid refrigerant leaves the metering device entering the  
evaporator coil. As it enters the evaporator coil, the larger  
area and lower pressure allows the refrigerant to expand  
and lower its temperature (heat intensity). This expansion is  
often referred to as “boiling”. Since the unit’s blower is moving  
indoor air across the finned surface of the evaporator coil,  
the expanding refrigerant absorbs some of that heat. This  
results in a lowering of the indoor air temperature, hence the  
“cooling” effect.  
4. “The temperature at which a liquid or gas changes state  
is dependent upon the pressure.”  
The refrigeration cycle begins at the compressor. Starting  
the compressor creates a low pressure in the suction line  
which draws refrigerant gas (vapor) into the compressor.  
The compressor then “compresses” this refrigerant, raising  
its pressure and its (heat intensity) temperature.  
The refrigerant leaves the compressor through the discharge  
Line as a hot High pressure gas (vapor). The refrigerant  
enters the condenser coil where it gives up some of its  
heat. The condenser fan moving air across the coil’s finned  
surface facilitates the transfer of heat from the refrigerant to  
the relatively cooler outdoor air.  
The expansion and absorbing of heat cause the liquid  
refrigerant to evaporate (i.e. change to a gas). Once the  
refrigerant has been evaporated (changed to a gas), it is  
heated even further by the air that continues to flow across  
the evaporator coil.  
When a sufficient quantity of heat has been removed from  
the refrigerant gas (vapor), the refrigerant will “condense”  
(i.e. change to a liquid). Once the refrigerant has been  
condensed (changed) to a liquid it is cooled even further by  
the air that continues to flow across the condenser coil.  
The particular system design determines at exactly what  
point (in the evaporator) the change of state (i.e. liquid to a  
gas) takes place. In all cases, however, the refrigerant must  
be totally evaporated (changed) to a gas before leaving the  
evaporator coil.  
The PTAC design determines at exactly what point (in  
the condenser) the change of state (i.e. gas to a liquid)  
takes place. In all cases, however, the refrigerant must be  
totally condensed (changed) to a Liquid before leaving the  
condenser coil.  
The low pressure (suction) created by the compressor  
causes the refrigerant to leave the evaporator through the  
suction line as a cool low pressure vapor. The refrigerant then  
returns to the compressor, where the cycle is repeated.  
Suction  
Line  
Discharge  
Line  
Condenser  
Coil  
Evaporator  
Coil  
Compressor  
Metering  
Device  
Refrigerant Drier  
Liquid  
Line  
Refrigerant  
Strainer  
29  
R-410A SEALED REFRIGERATION SYSTEM REPAIRS  
IMPORTANT  
SEALED SYSTEM REPAIRS TO COOL-ONLY MODELS REQUIRE THE INSTALLATION OF A LIQUID LINE DRIER.  
SEALED SYSTEM REPAIRS TO HEAT PUMP MODELS REQUIRE THE INSTALLATION OF A SUCTION LINE DRIER.  
EQUIPMENT REQUIRED:  
9. High Pressure Gauge - (0 - 750 lbs.)  
1. Voltmeter  
10. Low Pressure Gauge - (30 - 200 lbs.)  
2. Ammeter  
11. Vacuum Gauge - (0 - 1000 microns)  
3. Ohmmeter  
12. Facilities for flowing nitrogen through refrigeration tubing  
during all brazing processes.  
4. E.P.A. Approved Refrigerant Recovery System  
5. Vacuum Pump (capable of 200 microns or less  
vacuum.)  
EQUIPMENT MUST BE CAPABLE OF:  
6. Acetylene Welder  
1. Recovering refrigerant to EPA required levels.  
7. Electronic Halogen Leak Detector capable of detect-  
ing HFC (Hydrofluorocarbon) refrigerants.  
2. Evacuation from both the high side and low side of the  
system simultaneously.  
8. Accurate refrigerant charge measuring device such  
as:  
3. Introducing refrigerant charge into high side of the  
system.  
a. Balance Scales - 1/2 oz. accuracy  
b. Charging Board - 1/2 oz. accuracy  
4. Accurately weighing the refrigerant charge introduced  
into the system.  
Too much refrigerant (overcharge) in the system is just as bad  
(if not worse) than not enough refrigerant (undercharge). They  
both can be the source of certain compressor failures if they  
remain uncorrected for any period of time. Quite often, other  
problems (such as low air flow across evaporator, etc.) are  
misdiagnosed as refrigerant charge problems. The refrigerant  
circuit diagnosis chart will assist you in properly diagnosing  
these systems.  
WARNING  
RISK OF ELECTRIC SHOCK  
Unplug and/or disconnect all electrical power  
to the unit before performing inspections,  
maintenances or service.  
Failure to do so could result in electric shock,  
serious injury or death.  
An overcharged unit will at times return liquid refrigerant  
(slugging) back to the suction side of the compressor eventually  
causing a mechanical failure within the compressor. This  
mechanical failure can manifest itself as valve failure, bearing  
failure, and/or other mechanical failure. The specific type of  
failure will be influenced by the amount of liquid being returned,  
and the length of time the slugging continues.  
WARNING  
HIGH PRESSURE HAZARD  
SealedRefrigerationSystemcontainsrefrigerant  
and oil under high pressure.  
Proper safety procedures must be followed,  
and proper protective clothing must be worn  
when working with refrigerants.  
Not enough refrigerant (undercharge) on the other hand, will  
cause the temperature of the suction gas to increase to the point  
where it does not provide sufficient cooling for the compressor  
motor. When this occurs, the motor winding temperature will  
increase causing the motor to overheat and possibly cycle open  
the compressor overload protector. Continued overheating of  
the motor windings and/or cycling of the overload will eventually  
lead to compressor motor or overload failure.  
Failure to follow these procedures could  
result in serious injury or death.  
Refrigerant Charging  
Proper refrigerant charge is essential to proper unit opera-  
tion. Operating a unit with an improper refrigerant charge will  
result in reduced performance (capacity) and/or efficiency.  
Accordingly, the use of proper charging methods during ser-  
vicing will insure that the unit is functioning as designed and  
that its compressor will not be damaged.  
30  
Method Of Charging / Repairs  
CAUTION  
The acceptable method for charging the RAC system is the  
Weighed in Charge Method. The weighed in charge method is  
applicable to all units. It is the preferred method to use, as it is  
the most accurate.  
FREEZE HAZARD  
Proper safety procedures must be followed,  
and proper protective clothing must be worn  
when working with liquid refrigerant.  
The weighed in method should always be used whenever  
a charge is removed from a unit such as for a leak repair,  
compressor replacement, or when there is no refrigerant  
charge left in the unit. To charge by this method, requires the  
following steps:  
Failure to follow these procedures could  
result in minor to moderate injury.  
4. Make necessary repairs to system.  
1. Install a piercing valve to remove refrigerant from the  
sealedsystem. (Piercing valve must be removed from the  
system before recharging.)  
5. Evacuate system to 200 microns or less.  
6. Weigh in refrigerant with the property quantity of R-410A  
refrigerant.  
2. Recover Refrigerant in accordance with EPA regulations.  
7. Start unit, and verify performance.  
WARNING  
BURN HAZARD  
WARNING  
Proper safety procedures must be followed,  
and proper protective clothing must be worn  
when working with a torch.  
BURN HAZARD  
Proper safety procedures must be followed,  
and proper protective clothing must be worn  
when working with a torch.  
Failure to follow these procedures could  
result in moderate or serious injury.  
Failure to follow these procedures could  
result in moderate or serious injury.  
3. Install a process tube to sealed system.  
8. Crimp the process tube and solder the end shut.  
Undercharged Refrigerant Systems  
An undercharged system will result in poor performance  
(low pressures, etc.) in both the heating and cooling  
cycle.  
WARNING  
ELECTRIC SHOCK HAZARD  
Turn off electric power before service or  
installation.  
Whenever you service a unit with an undercharge of  
refrigerant, always suspect a leak. The leak must be  
repaired before charging the unit.  
Extreme care must be used, if it becomes  
necessary to work on equipment with power  
applied.  
To check for an undercharged system, turn the unit on,  
allow the compressor to run long enough to establish  
working pressures in the system (15 to 20 minutes).  
Failure to do so could result in serious injury or  
death.  
During the cooling cycle you can listen carefully at the exit  
of the metering device into the evaporator; an intermittent  
hissing and gurgling sound indicates a low refrigerant  
charge. Intermittent frosting and thawing of the evaporator  
is another indication of a low charge, however, frosting  
and thawing can also be caused by insufficient air over  
the evaporator.  
WARNING  
HIGH PRESSURE HAZARD  
SealedRefrigerationSystemcontainsrefrigerant  
and oil under high pressure.  
Proper safety procedures must be followed,  
and proper protective clothing must be worn  
when working with refrigerants.  
Checks for an undercharged system can be made at  
the compressor. If the compressor seems quieter than  
normal, it is an indication of a low refrigerant charge.  
Failure to follow these procedures could  
result in serious injury or death.  
A check of the amperage drawn by the compressor  
motor should show a lower reading. (Check the Unit  
Specification.)  
31  
After the unit has run 10 to 15 minutes, check the gauge Improper air flow over the evaporator coil may indicate  
pressures.Gaugesconnectedtosystemwithanundercharge some of the same symptoms as an over charged system.  
will have low head pressures and substantially low suction An overcharge can cause the compressor to fail, since it  
pressures.  
would be “slugged” with liquid refrigerant.  
The charge for any system is critical. When the compressor  
is noisy, suspect an overcharge, when you are sure that the  
air quantity over the evaporator coil is correct. Icing of the  
evaporator will not be encountered because the refrigerant  
will boil later if at all. Gauges connected to system will usually  
have higher head pressure (depending upon amount of over  
charge). Suction pressure should be slightly higher.  
Overcharged Refrigerant Systems  
Compressor amps will be near normal or higher.  
Noncondensables can also cause these symptoms. To  
confirm, remove some of the charge, if conditions improve,  
system may be overcharged. If conditions don’t improve,  
Noncondensables are indicated.  
Wheneveranoverchargedsystemisindicated,alwaysmake  
sure that the problem is not caused by air flow problems.  
Restricted Refrigerant System  
Troubleshooting a restricted refrigerant system can be  
difficult. The following procedures are the more common  
problems and solutions to these problems. There are two  
types of refrigerant restrictions: Partial restrictions and  
complete restrictions.  
With a complete restriction the current drawn may be  
considerably less than normal, as the compressor is  
running in a deep vacuum (no load.) Much of the area of  
the condenser will be relatively cool since most or all of the  
liquid refrigerant will be stored there.  
A partial restriction allows some of the refrigerant to  
circulate through the system.  
The following conditions are based primarily on a system  
in the cooling mode.  
With a complete restriction there is no circulation of  
refrigerant in the system.  
Restricted refrigerant systems display the same symptoms  
as a “low-charge condition.”  
When the unit is shut off, the gauges may equalize very  
slowly.  
Gauges connected to a completely restricted system will  
run in a deep vacuum. When the unit is shut off, the gauges  
will not equalize at all.  
A quick check for either condition begins at the evaporator.  
With a partial restriction, there may be gurgling sounds  
at the metering device entrance to the evaporator. The  
evaporator in a partial restriction could be partially frosted  
or have an ice ball close to the entrance of the metering  
device. Frost may continue on the suction line back to the  
compressor.  
Often a partial restriction of any type can be found by feel,  
as there is a temperature difference from one side of the  
restriction to the other.  
With a complete restriction, there will be no sound at the  
metering device entrance. An amperage check of the  
compressor with a partial restriction may show normal  
current when compared to the unit specification.  
32  
HERMETIC COMPONENTS CHECK  
WARNING  
BURN HAZARD  
WARNING  
Proper safety procedures must be followed,  
and proper protective clothing must be worn  
when working with a torch.  
CUT/SEVER HAZARD  
Be careful with the sharp edges and corners.  
Wear protective clothing and gloves, etc.  
Failure to follow these procedures could  
result in moderate or serious injury.  
Failure to do so could result in serious injury.  
METERING DEVICE  
Capillary Tube Systems  
All units are equipped with capillary tube metering  
devices.  
3. Switch the unit to the heating mode and observe the  
gauge readings after a few minutes running time. If  
the system pressure is lower than normal, the heating  
capillary is restricted.  
Checking for restricted capillary tubes.  
1. Connect pressure gauges to unit.  
4. If the operating pressures are lower than normal in both  
the heating and cooling mode, the cooling capillary is  
restricted.  
2. Start the unit in the cooling mode. If after a few minutes  
of operation the pressures are normal, the check valve  
and the cooling capillary are not restricted.  
CHECK VALVE  
the port (liquid line) to the outdoor coil. The flow path of  
the refrigerant is then through the filter drier and heating  
capillary to the outdoor coil.  
A unique two-way check valve is used on the reverse cycle  
heat pumps. It is pressure operated and used to direct the  
flow of refrigerant through a single filter drier and to the  
proper capillary tube during either the heating or cooling  
cycle.  
Failure of the slide in the check valve to seat properly in  
either mode of operation will cause flooding of the cooling  
coil. This is due to the refrigerant bypassing the heating or  
cooling capillary tube and entering the liquid line.  
One-way Check Valve  
(Heat Pump Models)  
COOLING MODE  
In the cooling mode of operation, liquid refrigerant from  
condenser (liquid line) enters the cooling check valve  
forcing the heating check valve shut. The liquid refrigerant  
is directed into the liquid dryer after which the refrigerant  
is metered through cooling capillary tubes to evaporator.  
(Note: liquid refrigerant will also be directed through the  
heating capillary tubes in a continuous loop during the  
cooling mode).  
NOTE: The slide (check) inside the valve is made of teflon.  
Should it become necessary to replace the check valve,  
place a wet cloth around the valve to prevent overheating  
during the brazing operation.  
HEATING MODE  
In the heating mode of operation, liquid refrigerant from  
the indoor coil enters the heating check valve forcing the  
cooling check valve shut. The liquid refrigerant is directed  
into the liquid dryer after which the refrigerant is metered  
through the heating capillary tubes to outdoor coils. (Note:  
liquid refrigerant will also be directed through the cooling  
capillary tubes in a continuous loop during the heating  
mode).  
CHECK VALVE OPERATION  
In the cooling mode of operation, high pressure liquid enters  
the check valve forcing the slide to close the opposite port  
(liquid line) to the indoor coil. Refer to refrigerant flow chart.  
This directs the refrigerant through the filter drier and cooling  
capillary tube to the indoor coil.  
In the heating mode of operation, high pressure refrigerant  
enters the check valve from the opposite direction, closing  
33  
REVERSING VALVE DESCRIPTION/OPERATION  
of the system. The pilot section of the valve opens and  
WARNING  
ELECTRIC SHOCK HAZARD  
closes ports for the small capillary tubes to the main valve  
to cause it to shift.  
Disconnect power to the unit before servicing.  
Failure to follow this warning could result in  
serious injury or death.  
NOTE: System operating pressures must be near  
normal before valve can shift.  
The Reversing Valve controls the direction of refrigerant flow  
to the indoor and outdoor coils. It consists of a pressure-  
operated, main valve and a pilot valve actuated by a solenoid  
plunger. The solenoid is energized during the heating cycle  
only. The reversing valves used in the PTAC system is a  
2-position, 4-way valve.  
The single tube on one side of the main valve body is the  
high-pressure inlet to the valve from the compressor. The  
center tube on the opposite side is connected to the low  
pressure (suction) side of the system. The other two are  
connected to the indoor and outdoor coils. Small capillary  
tubes connect each end of the main valve cylinder to the “A”  
and “B” ports of the pilot valve. A third capillary is a common  
return line from these ports to the suction tube on the main  
valve body. Four-way reversing valves also have a capillary  
tube from the compressor discharge tube to the pilot valve.  
The piston assembly in the main valve can only be shifted  
by the pressure differential between the high and low sides  
TESTING THE COIL  
NOTE: Do not start unit with solenoid coil removed from  
valve, or do not remove coil after unit is in operation. This  
will cause the coil to burn out.  
WARNING  
ELECTRIC SHOCK HAZARD  
Unplug and/or disconnect all electrical power  
to the unit before performing inspections,  
maintenances or service.  
CHECKING THE REVERSING VALVE  
NOTE: You must have normal operating pressures before  
Failure to do so could result in electric shock,  
serious injury or death.  
the reversing valve can shift.  
WARNING  
The solenoid coil is an electromagnetic type coil mounted  
on the reversing valve and is energized during the  
operation of the compressor in the heating cycle.  
HIGH PRESSURE HAZARD  
SealedRefrigerationSystemcontainsrefrigerant  
and oil under high pressure.  
1. Turn off high voltage electrical power to unit.  
Proper safety procedures must be followed,  
and proper protective clothing must be worn  
when working with refrigerants.  
2. Unplug line voltage lead from reversing valve coil.  
3. Check for electrical continuity through the coil. If you  
do not have continuity replace the coil.  
Failure to follow these procedures could  
result in serious injury or death.  
4. Check from each lead of coil to the copper liquid line  
as it leaves the unit or the ground lug. There should  
be no continuity between either of the coil leads  
and ground; if there is, coil is grounded and must be  
replaced.  
Check the operation of the valve by starting the system  
and switching the operation from “Cooling” to “Heating”  
and then back to “Cooling”. Do not hammer on valve.  
Occasionally, the reversing valve may stick in the heating  
or cooling position or in the mid-position.  
5. If coil tests okay, reconnect the electrical leads.  
6. Make sure coil has been assembled correctly.  
34  
When sluggish or stuck in the mid-position, part of the  
discharge gas from the compressor is directed back to the  
suction side, resulting in excessively high suction pressure.  
Touch Test in Heating/Cooling Cycle  
WARNING  
BURN HAZARD  
Certain unit components operate at  
temperatures hot enough to cause burns.  
Should the valve fail to shift from coooling to heating,  
block the air flow through the outdoor coil and allow the  
discharge pressure to build in the system. Then switch the  
system from heating to cooling.  
Proper safety procedures must be followed,  
and proper protective clothing must be  
worn.  
If the valve is stuck in the heating position, block the air  
flow through the indoor coil and allow discharge pressure  
to build in the system. Then switch the system from heating  
to cooling.  
Failure to follow these procedures could  
result in minor to moderate injury.  
Shouldthevalvefailtoshiftineitherpositionafterincreasing  
the discharge pressure, replace the valve.  
The only definite indications that the slide is in the mid-  
position is if all three tubes on the suction side of the valve  
are hot after a few minutes of running time.  
Dented or damaged valve body or capillary tubes can  
prevent the main slide in the valve body from shifting.  
NOTE: A condition other than those illustrated above, and  
on Page 31, indicate that the reversing valve is not shifting  
properly. Both tubes shown as hot or cool must be the same  
corresponding temperature.  
If you determing this is the problem, replace the reversing  
valve.  
Procedure For Changing Reversing Valve  
After all of the previous inspections and checks have been  
made and determined correct, then perform the “Touch  
Test” on the reversing valve.  
WARNING  
HIGH PRESSURE HAZARD  
SealedRefrigerationSystemcontainsrefrigerant  
and oil under high pressure.  
Proper safety procedures must be followed,  
and proper protective clothing must be worn  
when working with refrigerants.  
Failure to follow these procedures could  
result in serious injury or death.  
NOTICE  
FIRE HAZARD  
The use of a torch requires extreme care and proper  
judgment. Follow all safety recommended precautions  
and protect surrounding areas with fire proof materials.  
Have a fire extinguisher readily available. Failure to follow  
this notice could result in moderate to serious property  
damage.  
Reversing Valve in Heating Mode  
1. Install Process Tubes. Recover refrigerant from sealed  
system. PROPER HANDLING OF RECOVERED  
REFRIGERANT ACCORDING TO EPA REGULATIONS  
IS REQUIRED.  
2. Remove solenoid coil from reversing valve. If coil is to  
be reused, protect from heat while changing valve.  
3. Unbraze all lines from reversing valve.  
4. Clean all excess braze from all tubing so that they will  
slip into fittings on new valve.  
5. Remove solenoid coil from new valve.  
Reversing Valve in Cooling Mode  
35  
6. Protectnewvalvebodyfromheatwhilebrazingwith plastic  
heat sink (Thermo Trap) or wrap valve body with wet  
rag.  
Determine L.R.V.  
Start the compressor with the volt meter attached; then stop  
the unit. Attempt to restart the compressor within a couple  
of seconds and immediately read the voltage on the meter.  
The compressor under these conditions will not start and will  
usually kick out on overload within a few seconds since the  
pressures in the system will not have had time to equalize.  
Voltage should be at or above minimum voltage of 197 VAC,  
as specified on the rating plate. If less than minimum, check  
for cause of inadequate power supply; i.e., incorrect wire  
size, loose electrical connections, etc.  
7. Fit all lines into new valve and braze lines into new  
valve.  
WARNING  
EXPLOSION HAZARD  
The use of nitrogen requires a pressure  
regulator. Follow all safety procedures and  
wear protective safety clothing etc.  
Amperage (L.R.A.) Test  
Failure to follow proper safety procedures  
could result in serious injury or death.  
The running amperage of the compressor is the most impor-  
tant of these readings. A running amperage higher than that  
indicated in the performance data indicates that a problem  
exists mechanically or electrically.  
8. Pressurize sealed system with a combination of R-22  
and nitrogen and check for leaks, using a suitable leak  
detector. Recover refrigerant per EPA guidelines.  
Single Phase Running and L.R.A. Test  
NOTE: Consult the specification and performance section  
for running amperage. The L.R.A. can also be found on the  
rating plate.  
9. Once the sealed system is leak free, install solenoid coil  
on new valve and charge the sealed system by weighing  
in the proper amount and type of refrigerant as shown  
on rating plate. Crimp the process tubes and solder the  
ends shut. Do not leave Schrader or piercing valves in  
the sealed system.  
Select the proper amperage scale and clamp the meter  
probe around the wire to the “C” terminal of the compressor.  
Turn on the unit and read the running amperage on the me-  
ter. If the compressor does not start, the reading will indicate  
the locked rotor amperage (L.R.A.).  
NOTE: When brazing a reversing valve into the system, it is  
of extreme importance that the temperature of the valve does  
not exceed 250°F at any time.  
Overloads  
The compressor is equipped with an external overload which  
senses both motor amperage and winding temperature. High  
motor temperature or amperage heats the overload causing it  
to open, breaking the common circuit within the compressor.  
Wrap the reversing valve with a large rag saturated with  
water. “Re-wet” the rag and thoroughly cool the valve after  
each brazing operation of the four joints involved.  
The wet rag around the reversing valve will eliminate  
conduction of heat to the valve body when brazing the line  
connection.  
Heat generated within the compressor shell, usually due to  
recycling of the motor, is slow to dissipate. It may take any-  
where from a few minutes to several hours for the overload  
to reset.  
COMPRESSOR CHECKS  
Checking the Overload  
WARNING  
ELECTRIC SHOCK HAZARD  
WARNING  
Turn off electric power before service or  
installation. Extreme care must be used, if it  
becomes necessary to work on equipment with  
power applied.  
ELECTRIC SHOCK HAZARD  
Turn off electric power before service or  
installation. Extreme care must be used, if it  
becomes necessary to work on equipment  
with power applied.  
Failure to do so could result in serious injury or  
death.  
Failure to do so could result in serious injury or  
death.  
Locked Rotor Voltage (L.R.V.) Test  
Locked rotor voltage (L.R.V.) is the actual voltage available  
at the compressor under a stalled condition.  
Single Phase Connections  
Disconnect power from unit. Using a voltmeter, attach one  
lead of the meter to the run “R” terminal on the compressor  
and the other lead to the common “C” terminal of the com-  
pressor. Restore power to unit.  
36  
In a single phase PSC compressor motor, the highest  
value will be from the start to the run connections (“S” to  
“R”). The next highest resistance is from the start to the  
common connections (“S” to “C”). The lowest resistance  
is from the run to common. (“C” to “R”) Before replacing a  
compressor, check to be sure it is defective.  
WARNING  
BURN HAZARD  
Certain unit components operate at  
temperatures hot enough to cause burns.  
Proper safety procedures must be followed,  
and proper protective clothing must be  
worn.  
Failure to follow this warning could result  
in moderate to serious injury.  
External Overload  
With power off, remove the leads from compressor termi-  
nals. If the compressor is hot, allow the overload to cool  
before starting check. Using an ohmmeter, test continu-  
ity across the terminals of the external overload. If you  
do not have continuity; this indicates that the overload is  
open and must be replaced.  
GROUND TEST  
Use an ohmmeter set on its highest scale. Touch one  
lead to the compressor body (clean point of contact as a  
good connection is a must) and the other probe in turn  
to each compressor terminal. If a reading is obtained the  
compressor is grounded and must be replaced.  
Check the complete electrical system to the compressor  
and compressor internal electrical system, check to be  
certain that compressor is not out on internal overload.  
Completeevaluationofthesystemmustbemadewhenever  
you suspect the compressor is defective. If the compressor  
has been operating for sometime, a careful examination  
must be made to determine why the compressor failed.  
Single Phase Resistance Test  
Many compressor failures are caused by the following  
conditions:  
WARNING  
ELECTRIC SHOCK HAZARD  
1. Improper air flow over the evaporator.  
Turn off electric power before service or  
installation. Extreme care must be used, if it  
becomes necessary to work on equipment  
with power applied.  
2. Overcharged refrigerant system causing liquid to be  
returned to the compressor.  
3. Restricted refrigerant system.  
4. Lack of lubrication.  
Failure to do so could result in serious injury or  
death.  
Remove the leads from the compressor terminals and set  
the ohmmeter on the lowest scale (R x 1).  
5. Liquid refrigerant returning to compressor causing oil  
to be washed out of bearings.  
Touch the leads of the ohmmeter from terminals common  
to start (“C” to “S”). Next, touch the leads of the ohmmeter  
from terminals common to run (“C” to “R”).  
6.  
Noncondensables such as air and moisture in  
the system. Moisture is extremely destructive to a  
refrigerant system.  
Add values “C” to “S” and “C” to “R” together and  
check resistance from start to run terminals (“S” to “R”).  
Resistance “S” to “R” should equal the total of “C” to “S”  
and “C” to “R.”  
37  
COMPRESSOR REPLACEMENT  
Recommendedprocedureforcompressor  
replacement  
3. After all refrigerant has been recovered, disconnect  
suction and discharge lines from the compressor and  
remove compressor. Be certain to have both suction  
and discharge process tubes open to atmosphere.  
WARNING  
4. Carefully pour a small amount of oil from the suction  
RISK OF ELECTRIC SHOCK  
Unplug and/or disconnect all electrical power  
to the unit before performing inspections,  
maintenances or service.  
stub of the defective compressor into a clean  
container.  
5. Using an acid test kit (one shot or conventional kit), test  
the oil for acid content according to the instructions  
with the kit.  
Failure to do so could result in electric shock,  
serious injury or death.  
6. If any evidence of a burnout is found, no matter how  
slight, the system will need to be cleaned up following  
proper procedures.  
1. Be certain to perform all necessary electrical and  
refrigeration tests to be sure the compressor is  
actually defective before replacing.  
7. Install the replacement compressor.  
WARNING  
WARNING  
HIGH PRESSURE HAZARD  
SealedRefrigerationSystemcontainsrefrigerant  
and oil under high pressure.  
EXPLOSION HAZARD  
The use of nitrogen requires a pressure  
regulator. Follow all safety procedures and  
wear protective safety clothing etc.  
Proper safety procedures must be followed,  
and proper protective clothing must be worn  
when working with refrigerants.  
Failure to follow proper safety procedures  
result in serious injury or death.  
Failure to follow these procedures could  
result in serious injury or death.  
8. Pressurize with a combination of R-410A and nitrogen  
and leak test all connections with leak detector capable of  
detecting HFC (Hydrofluorocarbon) refrigerant. Recover  
refrigerant/nitrogen mixture and repair any leaks found.  
2. Recover all refrigerant from the system though  
the process tubes. PROPER HANDLING OF  
RECOVERED REFRIGERANT ACCORDING TO  
EPA REGULATIONS IS REQUIRED. Do not use  
gauge manifold for this purpose if there has been  
a burnout. You will contaminate your manifold and  
hoses. Use a Schrader valve adapter and copper  
tubing for burnout failures.  
Repeat Step 8 to insure no more leaks are present.  
9. Evacuate the system with a good vacuum pump capable  
of a final vacuum of 200 microns or less. The system  
should be evacuated through both liquid line and suction  
line gauge ports. While the unit is being evacuated, seal  
all openings on the defective compressor.  
WARNING  
HIGH TEMPERATURES  
CAUTION  
FREEZE HAZARD  
Extreme care, proper judgment and all safety  
procedures must be followed when testing,  
troubleshooting, handling or working around  
unit while in operation with high temperature  
components. Wear protective safety aids  
such as: gloves, clothing etc.  
Proper safety procedures must be followed,  
and proper protective clothing must be worn  
when working with liquid refrigerant.  
Failure to follow these procedures could  
result in minor to moderate injury.  
Failure to do so could result in serious burn  
injury.  
10. Recharge the system with the correct amount of  
refrigerant. The proper refrigerant charge will be  
found on the unit rating plate. The use of an accurate  
measuring device, such as a charging cylinder,  
NOTICE  
FIRE HAZARD  
electronic scales or similar device is necessary.  
The use of a torch requires extreme care and proper  
judgment. Follow all safety recommended precautions  
and protect surrounding areas with fire proof materials.  
Have a fire extinguisher readily available. Failure to follow  
this notice could result in moderate to serious property  
damage.  
NOTICE  
NEVER, under any circumstances, charge a rotary  
compressor through the LOW side. Doing so would  
cause permanent damage to the new compressor.  
38  
SPECIAL PROCEDURE IN THE CASE OF MOTOR  
COMPRESSOR BURNOUT  
To ensure proper unit operation and life expectancy, the  
following maintenance procedures should be performed  
on a regular basis  
WARNING  
ELECTRIC SHOCK HAZARD  
Turn off electric power before service or  
installation.  
1. Air Filter  
To ensure proper unit operation, the air filters should  
be cleaned at least monthly, and more frequently if  
conditions warrant. The unit must be turned off before  
the filters are cleaned.  
Failure to do so may result in personal injury,  
or death.  
To remove the air filters, grasp the top of the filter and lift  
out of the front cabinet. Reverse the procedure to reinstall  
the filters.  
WARNING  
HIGH PRESSURE HAZARD  
SealedRefrigerationSystemcontainsrefrigerant  
and oil under high pressure.  
Clean the filters with a mild detergent in warm water, and  
allow them to dry thoroughly before reinstalling.  
2. Coils & Chassis  
Proper safety procedures must be followed,  
and proper protective clothing must be worn  
when working with refrigerants.  
NOTE: Do not use a caustic coil cleaning agent on coils  
or base pan. Use a biodegradable cleaning agent and  
degreaser. The use of harsh cleaning materials may  
lead to deterioration of the aluminum fins or the coil end  
plates.  
Failure to follow these procedures could  
result in serious injury or death.  
The indoor coil and outdoor coils and base pan should  
be inspected periodically (annually or semi-annually)  
and cleaned of all debris (lint, dirt, leaves, paper, etc.)  
as necessary. Under extreme conditions, more frequent  
cleaning may be required. Clean the coils and base  
pan with a soft brush and compressed air or vacuum.  
A pressure washer may also be used, however, you  
must be careful not to bend the aluminum fin pack. Use  
a sweeping up and down motion in the direction of the  
vertical aluminum fin pack when pressure cleaning coils.  
WARNING  
EXPLOSION HAZARD  
The use of nitrogen requires a pressure  
regulator. Follow all safety procedures and  
wear protective safety clothing etc.  
Failure to follow proper safety procedures  
result in serious injury or death.  
1.  
2.  
Recover all refrigerant and oil from the system.  
Note: It is extremely important to insure that none of the  
electrical and/or electronic parts of the unit get wet. Be  
sure to cover all electrical components to protect them  
from water or spray.  
Remove compressor, capillary tube and filter drier  
from the system.  
3.  
Flush evaporator condenser and all connecting  
tubing with dry nitrogen or equivalent. Use approved  
flushing agent to remove all contamination from  
system. Inspect suction and discharge line for  
carbon deposits. Remove and clean if necessary.  
Ensure all acid is neutralized.  
3. Decorative Front  
The decorative front and discharge air grille may be  
cleaned with a mild soap or detergent. Do NOT use  
solvents or hydrocarbon based cleaners such as  
acetone, naphtha, gasoline, benzene, etc., to clean the  
decorative front or air discharge grilles.  
4. Reassemble the system, including new drier strainer  
and capillary tube.  
Use a damp (not wet) cloth when cleaning the control  
area to prevent water from entering the unit, and possibly  
damaging the electronic control  
5. Proceed with step 8-10 on previous page.  
4. Fan Motor & Compressor  
The fan motor & compressor and are permanently  
lubricated, and require no additional lubrication.  
ROUTINE MAINTENANCE  
WARNING  
5. Wall Sleeve  
Inspect the inside of the wall sleeve and drain system  
periodically (annually or semi-annually) and clean as  
required. Under extreme conditions, more frequent  
cleaning may be necessary. Clean both of these areas  
with an antibacterial and antifungal cleaner. Rinse both  
items thoroughly with water and ensure that the drain  
outlets are operating properly.  
ELECTRICAL SHOCK HAZARD!  
Turn off electrical power before service or  
installation. All eletrical connections and wiring  
MUST be installed by a qualified electrician  
and conform to the National Code and all local  
codes which have jurisdiction. Failure to do so  
can result in property damage, personal injury  
and/or death.  
39  
TROUBLESHOOTING CHART - COOLING  
REFRIGERANT SYSTEM DIAGNOSIS COOLING  
PROBLEM  
PROBLEM  
PROBLEM  
PROBLEM  
LOW SUCTION PRESSURE  
HIGH SUCTION PRESSURE  
LOW HEAD PRESSURE  
HIGH HEAD PRESSURE  
Low Load Conditions  
High Load Conditions  
Low Load Conditions  
High Load Conditions  
Low Air Flow Across  
Indoor Coil  
High Air Flow Across  
Indoor Coil  
Refrigerant System  
Restriction  
Low Air Flow Across  
Outdoor Coil  
Refrigerant System  
Restriction  
Reversing Valve not  
Fully Seated  
Reversing Valve not  
Fully Seated  
Overcharged  
Undercharged  
Overcharged  
Non-Condensables (air)  
Undercharged System  
Defective Compressor  
Moisture in System  
Defective Compressor  
TROUBLESHOOTING CHART - HEATING  
REFRIGERANT SYSTEM DIAGNOSIS HEATING  
PROBLEM  
PROBLEM  
PROBLEM  
PROBLEM  
LOW SUCTION PRESSURE  
HIGH SUCTION PRESSURE  
LOW HEAD PRESSURE  
HIGH HEAD PRESSURE  
Low Air Flow Across  
Outdoor Coil  
Outdoor Ambient Too High  
for Operation in Heating  
Refrigerant System  
Restriction  
Outdoor Ambient Too High  
For Operation In Heating  
Refrigerant System  
Restriction  
Reversing Valve not  
Fully Seated  
Reversing Valve not  
Fully Seated  
Low Air Flow Across  
Indoor Coil  
Undercharged  
Overcharged  
Undercharged  
Overcharged  
Non-Condensables (air)  
in System  
Moisture in System  
Defective Compressor  
Defective Compressor  
40  
ELECTRICAL TROUBLESHOOTING CHART - HEAT PUMP  
CAUTION  
WARNING  
ELECTRIC SHOCK HAZARD  
Turn off electric power before service or  
installation.  
BURN HAZARD  
Certain unit components operate at  
temperatures hot enough to cause burns.  
Extreme care must be used, if it becomes  
necessary to work on equipment with power  
applied.  
Proper safety procedures must be followed,  
and proper protective clothing must be  
worn.  
Failure to do so could result in serious injury  
or death.  
Failure to do so could result in minor to  
moderate injury.  
HEAT PUMP  
SYSTEM COOLS WHEN  
HEATING IS DESIRED.  
Is Line Voltage  
Present at the  
Solenoid Valve?  
Is the Selector Switch  
Set for Heat?  
NO  
NO  
YES  
Is the Solenoid Coil Good?  
Replace the Solenoid Coil  
YES  
Reversing Valve Stuck  
Replace the Reversing Valve  
41  
REMOTE WALL THERMOSTAT WIRING DIAGRAM  
COOL WITH ELECTRIC HEAT  
LEGEND FOR T-STAT WIRING HARNESS  
R
24 VAC Power From Unit  
Coil for Cooling  
Y
W
O
Call for Heat  
Reversing Valve Energized in cooling mode  
Call for Low Fan  
GL  
GH  
Call for High Fan  
RT6 - Two Speeds Fan T-Stat - Field Provided  
-- -- -- Field Wiring  
Electronic  
Control  
Board  
THERMOSTAT CONNECTIONS  
GH  
GL  
R
Y
O
B
W
O
Y
GL  
GH  
C
W
RC  
RH  
C
EXT.  
SW  
Disk control  
or  
Auxillary fan  
RT6  
EXT.  
SW  
42  
REMOTE WALL THERMOSTAT WIRING DIAGRAM  
HEAT PUMP WITH ELECTRIC HEAT  
LEGEND FOR T-STAT WIRING HARNESS  
R
24 VAC Power From Unit  
Coil for Cooling  
Y
W
O
Call for Heat  
Reversing Valve Energized in cooling mode  
Call for Low Fan  
GL  
GH  
Call for High Fan  
RT6 - Two Speeds Fan T-Stat - Field Provided  
-- -- -- Field Wiring  
Electronic  
Control  
Board  
THERMOSTAT CONNECTIONS  
GH  
GL  
R
Y
O
B
W
O
Y
GL  
GH  
C
W
RC  
RH  
C
EXT.  
SW  
Disk control  
or  
Auxillary fan  
RT6  
EXT.  
SW  
43  
WIRING DIAGRAM  
RD  
5VDC 5VDC 5VDC  
Thermistors  
WH  
BL  
WH  
BL  
WH  
WH  
HR  
HR  
K103  
K104  
Indoor Air Outdoor  
Logic Board  
CAP  
RD  
BK  
24VAC  
BK  
BK  
BN  
BN  
BK  
BN  
12VAC  
12VDC  
TRAN  
RD  
BL  
RD  
BL  
BK  
BN  
Display  
Control  
Board  
HTR  
208/230  
265 VAC  
BK  
YL  
BL  
HTR  
OM  
IM  
Auto Reset  
Limit  
WH  
BN  
BN  
V 4  
3 N  
YV  
Fuse Link  
CAP  
CAP  
Rev Solenoid  
COMPONENT ID  
WIRE COLOR ID  
COMP = Compressor  
CAP = Capacitor  
BL = Blue  
BN = Brown  
BK = Black  
RD = Red  
HTR = Heater  
TB = Terminal Block  
OM = Outdoor Fan Motor  
IM = Indoor Fan Motor  
TRAN = Transformer  
RELAY COMM = L.V. Relay Cable  
CR = Compressor Relay  
HR = Heater Relay  
WH = White  
PR = Purple  
YL = Yellow  
GR = Green  
YV = Reversing Valve Solenoid  
44  
To Install Thermostat  
 ? ;,GO;1?(39P;Q(91R1G@(M(,/%)(0JJ(.0K"%('$($>"(-'&)(4"%M&#"(.')"!(<2(%"-0M&)*($>"(J/4"(  
0%(4K&$#>&)*($>"('..%0.%&'$"(#&%#/&$(<%"'C"%($0($>"(PDD(.04&$&0)(<"J0%"(%"-0M&)*($>"("T&4$&)*(  
$>"%-04$'$N  
RT6  
Electronic Thermostat  
OUEPG,1V,+  !"#$%&'(')*+&'(,,('*%+)$-&').%+/%#$)'%),%.(,)(+0)+('*%+(,)1-*,0*+2)(+0)",".'#*.(,).%0"&)(+0)  
%#0*+(+."&3)  
V0$"+ 4%-+')'!")'!"#$%&'(')(1%-')[6")/""')(1%6")'!")\%%#3)8%)+%')$%-+')'!")'!"#$%&'(')%+)(+)%-'&*0")9(,,:)*+)  
0*#".')&-+,*2!':)1"!*+0)()0%%#:)%#)*+)(+)(#"()(//".'"0)1;)()6"+')%#)0-.'3  
#(783$'*"(9"'$:783$'*"(;00!(324$"-4  
(A [357 9KK 09V45 69 6D4 D4.627C .7: F99827C BGB64/ IG 54/9^27C 6D4 K3B4 95 BV26FD27C 6D4 .0059052.64 F25F326  
I54.M45 9KKA  
#(;0)[*/%'<!"($0+(=84$'*"(>"'$(./-.  
#(?'%*"(@&4.!'2(A&$>(B'#C!&*>$  
"A [9 54/9^4 F9^45E 0388 C4768G .6 6D4 B4./ .6 6D4 690A  
+A c36 6D45/9B6.6 I.B4 .C.27B6 6D4 V.88 VD454 G93 08.7 69 /9376 26 'L4 B354 V254B V288 K44: 6D593CD 6D4 V254  
904727C 27 6D4 I.B4 9K 6D4 6D45/9B6.6-A  
#(3"!"#$'<!"(D'>%")>"&$(0%(;"!4&/4  
#A d.5M 6D4 08.F4/476 9K 6D4 /937627C D984BA  
;A Z46 6D45/9B6.6 I.B4 .7: F9^45 .V.G K59/ V95M27C .54.A  
_A XB27C . +R(_P :5288 I26E :5288 D984B 27 6D4 08.F4B G93 D.^4 /.5M4: K95 /937627CA  
?A XB4 . D.//45 69 6.0 B300824: .7FD95B 27 /937627C D984BA  
)A %82C7 6D45/9B6.6 I.B4 V26D /937627C D984B .7: K44: 6D4 F976598 V254B 6D593CD B826 27 6D45/.8 27653B297 I.55245 .7:  
2769 V254 904727CA  
>A XB4 B300824: BF54VB 69 /9376 6D45/9B6.6 I.B4 69 V.88A  
(,A ]7B456 B652004:E 8.I484: V254B 27 /.6FD27C V254 645/27.8BA  
;1W,OPVX+ <")&-#")"=>%&"0)>%#'*%+)%/)9*#"&)0%"&)+%')'%-.!)%'!"#)9*#"&3  
Installation, Operation & Application Guide  
((A O4768G 63C V254 69 I4 B354 9K 059045 F9774F6297A W93I84 FD4FM 6D.6 4.FD V254 2B F9774F64: 69 6D4 059045  
645/27.8A  
("A [357 97 09V45 69 6D4 BGB64/ .6 6D4 /.27 B45^2F4 0.748A  
(+A &97[C354 6D45/9B6.6 69 /.6FD 6D4 6G04 9K BGB64/ G93 D.^4A  
(#A N408.F4 F9^45 97 6D45/9B6.6 IG B7.0027C 26 27 08.F4A  
(;A [4B6 6D45/9B6.6 9045.6297 .B :4BF52I4: 27 O[4B627C 6D4 [D45/9B6.6PA  
Parts Diagram  
Wiring Diagrams  
9"'$:;00!(324$"-4  
9"'$(./-.(K&$>("!"#$%&#(<'#C/.  
X0 I36697  
[5.7BK95/45  
[5.7BK95/45  
W9V7 I36697  
N
N
(",  
$%&  
(",  
"# $%&  
"# $%&  
$%&  
&
&
P9V =.7  
Q2CD =.7  
OP  
OQ  
JRL  
S
P9V =.7  
OP  
OQ  
JRL  
S
Q2CD =.7  
N4^45B27C $.8^4  
&9/054BB95  
N
&
OP OQ JRL  
S
T
N2CD6 'K.7-  
I36697  
&998  
Q4.6  
NYZY[ &J\=]O  
%31282.5G Q4.6  
T
T
P4K6 'BGB64/-  
I36697  
N4B46  
BV26FD  
&97[C35.6297  
BV26FD  
P9RQ2 K.7  
BV26FD  
Terminal Designator Descriptions  
N
&
JRL  
M
M
M
"# $%& D96  
"# $%& F9//97  
&97[C35.I84  
Icon Descriptions  
J M &998 .F62^4 54^45B27C ^.8^4 '=542:52FD c[Qc-  
L M Q4.6 .F62^4 54^45B27C ^.8^4 '=542:52FD $456*]*c.ME g3D8hQc-  
S
T
OP  
OQ  
M
M
M
M
(B6 B6.C4 F998E (B6 B6.C4 D4.6 K95 D4.6 03/0B  
(B6 B6.C4 D4.6 K95 797*D4.6 03/0 BGB64/BE .31282.5G D4.6 K95 Qc BGB64/B  
P9V K.7  
Q2CD K.7  
N99/ 64/045.6354  
9KKB46 .F62^.64:  
=.7 9045.6297 2F97  
&99827C 9045.6297 2F97  
Q4.627C 9045.6297 2F97  
&JJP  
QY%[  
Q4.6 B46 09276 VD47 I827M27C  
&998 B46 09276 VD47 I827M27C  
RT6 Output Chart  
1ST Cool  
1ST Heat  
TE OE L  
SE O  
2ND Heat  
\R%  
Configuration  
Q4.6R&998 .7: B27C84 B6.C4 Qc /9:48B  
YP&  
SE O  
cWQ 'c[Qc- /9:48B 978G  
Qc QJR &97[C  
SE OE J  
SE TE O  
Specifications  
 !"#$%&#'!(%'$&)*+ # "# $%& '()*+, $%&-  
# ( ./0 /.12/3/ 045 645/27.8  
[D4 G,H 6D45/9B6.6 2B F97[C35.I84 K95 :2KK45476 BGB64/BA [D4 F97[C35.6297 :254F68G .KK4F6B 6D4 936036BA  
XB4 6D4 936036 FD.56 69 F9554F68G F97[C354 .7: V254 6D4 6D45/9B6.6 69 G935 BGB64/A  
# + ./0 /.12/3/ 696.8 89.:  
,"-."%'$/%"(#0)$%0!(%')*"+(#;ꢀ= 69 >,ꢀ= '?ꢀ& 69 +"ꢀ&- 1##/%'#2+ / (ꢀ= '/ ,A;ꢀ&-  
324$"-(#0)[*/%'$&0)4+ "*B6.C4 D4.6E (*B6.C4 F998E D4.6 03/0E 484F652F  
Configuration Mode  
,&-&)*+ %762*BD956 &GF84H # /27364B 'IG0.BB .762*BD956 FGF84 :48.G IG 54635727C 69 J== /9:4 K95 ; B4F97:B-  
L.FM82CD6 J045.6297H (, B4F97:B  
[D4 F97[C35.6297 /9:4 2B 3B4: 69 B46 6D4 G,H 69 /.6FD G935 D4.627CRF99827C BGB64/A [D4 G,H K37F6297B V26D D4.6  
03/0E .25 F97:2629727CE 95 484F652F D4.6 BGB64/BA  
,"%-&)'$&0)4+ NE &E OPE OQE JRLE SE T  
V0$"+  !"#$%&'(').%$"&).%+[2-#"0)/%#)@A&'(2")!"(')B)@A&'(2").%%,*+2)/%#)-&")9*'!)(,,)!"('B.%%,)(+0)&*+2,"A&'(2")!"(')  
>-$>)$%0",&3C%#)C#*"0#*.!)? D?)$%0",&)/%,,%9)'!")*+&'#-.'*%+&)1",%9)'%).%+[2-#")'!")'!"#$%&'(')/%#)'9%A&'(2")  
!"(')>-$>)%>"#('*%+)-&*+2)'!")QFR)'"#$*+(,3  
[9 F97[C354 6D4 G,HE 045K95/ 6D4 K9889V27C B640BH  
Important Safety Information  
1!K'24($/%)(0JJ(.0K"%('$($>"(-'&)(.0K"%(4/..!2(<"J0%"(&)4$'!!&)*L(#!"')&)*L(0%(%"-0M&)*(  
$>"%-04$'$N  
(A $452KG 6D4 G,H 2B 27 6D4 PDD /9:4A  
 !"#$#%&  
H
c54BB 6D4 3Y3 '84K6- I36697 37628 9KK /9:4 :2B08.GBA  
#
#
#
[D2B 6D45/9B6.6 2B K95 "# $%& .0082F.6297B 978Ga :9 796 3B4 97 ^986.C4B 9^45 +, $%&  
%88 V2527C /3B6 F97K95/ 69 89F.8 .7: 7.6297.8 484F652F.8 .7: I328:27C F9:4B  
W9 796 3B4 .25 F97:2629727C VD47 6D4 936:995 64/045.6354 2B I489V ;, :4C544Ba 6D2B F.7 :./.C4 G935 %R& BGB64/  
.7: F.3B4 045B97.8 27b3524B  
"A N4/9^4 6D4 F9^45 9K 6D4 6D45/9B6.6 IG C4768G 038827C 74.5 974 9K 6D4 F95745B .6  
6D4 690 9K 6D4 6D45/9B6.6A  
 !!  
#
XB4 6D2B 6D45/9B6.6 978G .B :4BF52I4: 27 6D2B /.73.8  
+A c54BB 6D4 ;PVDOZ I36697 K95 ( B4F97: VD284 6D4 G,H 2B 27 PDD(/9:4A  
&J\=]O  
Package Contents/Tools Required  
E'#C'*"(&)#!/F"4+ G,H 6D45/9B6.6 97 I.B4E 6D45/9B6.6 F9^45E V2527C 8.I48BE BF54VB .7: V.88 .7FD95BE ]7B6.88.6297E  
J045.6297 .7: %0082F.6297 O32:4  
c54BB 6D4 /. 95 F0K) I36697 69 FD.7C4 B46627CB V26D27 4.FD BF5447A  
X0  
I36697  
,00!4(%"I/&%"F(J0%(&)4$'!!'$&0)+ W5288 V26D +R(_P I26E D.//45E BF54V:52^45  
W9V7  
I36697  
c54BB 6D4 %&*>$ I36697 69 .:^.7F4 69 6D4 7416 BF5447A  
To Remove Existing Thermostat  
 ? ;,GO;1?(39P;Q(91R1G@(M(,/%)(0JJ(.0K"%('$($>"(-'&)(4"%M&#"(.')"!(<2(%"-0M&)*($>"(J/4"(  
0%(4K&$#>&)*($>"('..%0.%&'$"(#&%#/&$(<%"'C"%($0($>"(PDD(.04&$&0)(<"J0%"(%"-0M&)*($>"("T&4$&)*(  
$>"%-04$'$N  
V0$"+ ?#"&&*+2)'!")"#$%)1-''%+)9*,,)#"'-#+);%-)'%)'!")>#"6*%-&)&.#""+3  
P4K6  
I36697  
N2CD6  
I36697  
[9 4126 F97[C35.6297 /9:4E 054BB 6D4 ;PVDOZ BV26FD K95 ( B4F97:A  
(A [357 9KK 09V45 69 6D4 D4.627C .7: F99827C BGB64/ IG 54/9^27C 6D4 K3B4 95 BV26FD27C 6D4 .0059052.64 F25F326  
I54.M45 9KKA  
"A N4/9^4 F9^45 9K 98: 6D45/9B6.6A [D2B BD938: 4109B4 6D4 V254BA  
+A P.I48 6D4 412B627C V254B V26D 6D4 47F89B4: V254 8.I48B I4K954 54/9^27C V254BA  
#A %K645 8.I4827C V254BE 54/9^4 V254B K59/ V254 645/27.8BA  
;A N4/9^4 412B627C 6D45/9B6.6 I.B4 K59/ V.88A  
_A N4K45 69 6D4 K9889V27C B4F6297 K95 27B653F6297B 97 D9V 69 27B6.88 6D2B 6D45/9B6.6A  
45  
Configuration Mode Settings  
Operating Modes  
 !"#$"%&'#$()""*$#+,)#-,*[/&)0%1,*#2,3"#0)"#0$#+,44,5$6  
<8# T’†‡r€#M#9"%#+,)#!"0%#'&;'M#*,*N!"0%#'&;'M#)"A")$1*/#A04A"#,'")0%1,*  
 !")"#0)"#+,&)#',$$1@4"#,'")0%1*/#;,3"$#+,)#%!"#SU%8#O++M#P"0%M#0*3#-,,4#;,3"$#0)"#0(("$$"3#@:#')"$$1*/#%!"#T`T#  
D4"+%G#@&%%,*8  
OFF Mode  
T’†‡r€  
Tr‡‡vt Sr‰rꢀ†vt&Why‰r&Tr‡‡vt  
Aꢀvrqꢀvpu&H‚qry†  
## R*#%!1$#;,3"M#%!"#%!");,$%0%#5144#*,%#%&)*#,*#%!"#!"0%1*/#,)#(,,41*/#3"A1("$  
#I‚‡r)# !"#$%&''(#)*%#+*%#,"#-.(%"&#'%#/*%.*001#$%#"2"(1#'3"(*-$%4#/'&"#,1#  
3("55$%4#-!"#!,-#6($4!-7#,.--'%8# !"#9'(&#!,-$5!'95#'%#-!"#&$530*1#*%&#  
-!"#)*%#$+'%# #*33"*(5#9!"%#-!"#)*%#'3"(*-"58  
.!!  
Crh‡&Qˆ€ƒ  
P?  
O#N#^*")/1k"3#1*#-,,41*/  
?jP#D? P?G O*4:  
Crh‡ꢅ8‚‚y&hq&TvtyrꢆT‡htr&  
Crh‡&Qˆ€ƒ&Py’  
^V-  
]lW  
d^WM#?j^#D? W-GM#m&!4a  
Heat Mode  
## R*#%!1$#;,3"M#%!"#%!");,$%0%#(,*%),4$#%!"#!"0%1*/#$:$%";8#S!"*#%!"#!"0%#,&%'&%$M#  
%!"#\0;"#1(,*# #0'')"0)$#,*#%!"#31$'40:8  
#
#
?)"$$#%!"#ˆƒ#,)#q‚#@&%%,*#%,#$"4"(%8  
?)"$$#%!"#ꢀvtu‡#@&%%,*#%,#03A0*("#%,#%!"#*"B%#$()""*8  
#I‚‡r)#:'(#!"*-#3./35;#-!"("#$5#*#)'.(#/$%.-"#&"0*1#)'(#1'.(#+'/3("55'(#-'#  
("5-*(-#*)-"(#$-#!*5#-.(%"&#'))8# '#,13*55#-!"#+'/3("55'(#-$/"#&"0*1;#4'#-'#  
<::#/'&"#)'(#=#5"+'%&58  
H8# Ur€ƒrꢀh‡ˆꢀr&Tphyr&DF#,)#-G  
&
#
#
-!,,$"#F0!)"*!"1%#,)#-"4$1&$8  
Cool Mode  
?)"$$#%!"#ˆƒ#,)#q‚#@&%%,*#%,#$"4"(%8  
?)"$$#%!"#ꢀvtu‡#@&%%,*#%,#03A0*("#%,#%!"#*"B%#$()""*8  
## R*#%!1$#;,3"M#%!"#%!");,$%0%#(,*%),4$#%!"#(,,41*/#$:$%";8#S!"*#%!"#(,,41*/#  
,&%'&%$M#%!"#$*,5\0U"#1(,*# #0'')"0)$#,*#%!"#31$'40:8  
#I‚‡r)# !"("#$5#*#)'.(#/$%.-"#&"0*1#)'(#1'.(#+'/3("55'(#-'#("5-*(-#*)-"(#$-#!*5#  
-.(%"&#'))8# '#,13*55#-!"#+'/3("55'(#-$/"#&"0*1;#4'#-'#<::#/'&"#)'(#=#  
5"+'%&58  
†‡  
I8#   &T‡htr&Ur€ƒrꢀh‡ˆꢀr&9vssrꢀr‡vhy#D<ꢀF#%,#7ꢀFG#D>87ꢀ-#%,#H87ꢀ-G  
9"%#%!"#*&;@")#,+#3"/)""$#@"%5""*#:,&)#O$"%',1*%P#%";'")0%&)"#0*3#:,&)#O%&)*#,*P#  
%";'")0%&)"8  
#
#
?)"$$#%!"#ˆƒ#,)#q‚#@&%%,*#%,#$"%#31++")"*%104#A04&"8  
?)"$$#%!"#ꢀvtu‡&@&%%,*#%,#03A0*("#%,#%!"#*"B%#$()""*8  
Set Point Adjustment  
Heat Set Point  
C8# !q&T‡htr&Ur€ƒrꢀh‡ˆꢀr&9vssrꢀr‡vhy#D<ꢀF#%,#7ꢀFG#D>87ꢀ-#%,#H87ꢀ-G# !"#$%&$'$"()*+  
## b$"#%!"#9c9#@&%%,*#%,#$"4"(%#P"0%#2,3"8#?)"$$#%!"#&'#,)#3,5*#@&%%,*#%,#A1"5#%!"#  
(&))"*%#!"0%#$"%#',1*%#40)/")#,*#%!"#31$'40:8#S!"*#%!"#40)/"#$"%#',1*%#1$#31$'40:"3M#  
%!"#P^W #1(,*#5144#@41*U8# !"#&'#,)#3,5*#@&%%,*$#(0*#@"#&$"3#%,#03`&$%#%!"#$"%#  
',1*%8#W+%")#7#$"(,*3$#,+#1*0(%1A1%:#%!"#$()""*#5144#31$'40:#%!"#),,;#%";'")0%&)"#0*3#  
#
#
#
9"%#%!"#*&;@")#,+#3"/)""$#@"%5""*#5!"*#$%0/"#<#%&)*$#,*#0*3#5!"*#$%0/"#H#%&)*$#,*8  
?)"$$#%!"#ˆƒ#,)#q‚#@&%%,*#%,#$"%#31++")"*%104#A04&"8  
?)"$$#%!"#ꢀvtu‡&@&%%,*#%,#03A0*("#%,#%!"#*"B%#$()""*8  
%!"#P^W #1(,*#5144#*,%#@41*U8  
%/,0$12"($31))$4)1(56  
Cool Set Point  
78# T‡htrq&Pss&Pˆ‡ƒˆ‡†# !"#$%&$'$"()*+##  
## b$"#%!"#9c9#@&%%,*#%,#$"4"(%#-,,4#2,3"8#?)"$$#%!"#&'#,)#3,5*#@&%%,*#%,#A1"5#%!"#  
(&))"*%#(,,4#$"%#',1*%#40)/")#,*#%!"#31$'40:8#S!"*#%!"#40)/"#$"%#',1*%#1$#31$'40:"3M#  
%!"#-OOV#1(,*#5144#@41*U8# !"#&'#,)#3,5*#@&%%,*$#(0*#@"#&$"3#%,#03`&$%#%!"#$"%#  
',1*%8#W+%")#7#$"(,*3$#,+#1*0(%1A1%:#%!"#$()""*#5144#31$'40:#%!"#),,;#%";'")0%&)"#0*3#  
#
9"4"(%#5!"%!")#%!"#,&%'&%$#+,)#!"0%1*/#0*3#(,,41*/#0)"#$%0/"3#,++#1*3"'"*3"*%4:#,)#0)"#  
$0%1$["3#$1;&4%0*",&$4:8  
#
#
#
#
<#=#,&%'&%$#$%0/"3#,++#1*3"'"*3"*%4:#####  
>#=#,&%'&%$#,++#$1;&4%0*",&$4:  
%!"#-OOV#1(,*#5144#*,%#@41*U8  
7..8$12"($31))$4)1(56  
?)"$$#%!"#ˆƒ#,)#q‚#@&%%,*#%,#$"%8  
?)"$$#%!"#ꢀvtu‡&@&%%,*#%,#03A0*("#%,#%!"#*"B%#$()""*8  
%ꢁ& 6ˆ‘vyvhꢀ’&9ryh’&PI#M#D>NI>#;1*&%"$G# !"#$%&$'$"()*+  
Testing the Thermostat  
#
9"%#%!"#3"40:#%1;"#1*#;1*&%"$#+,)#0&B1410):#!"0%#%,#@"#4,(U"3#,&%#0+%")#0#(044#+,)#$"(,*3#  
$%0/"8# !1$#"B%)0#$0A1*/$#+"0%&)"#1$#&$"3#%,#%";',)0)14:#4,(U#,&%#0&B1410):#!"0%#3"A1("$M#  
044,51*/#`&$%#!"0%#'&;'#%,#%):#%,#$0%1$+:#!"0%#(0448  
O*("#%!"#%!");,$%0%#1$#(,*[/&)"3M#1%#$!,&43#@"#%!,),&/!4:#%"$%"38  
!"#$%&'(6# j,#*,%#"*")/1k"#%!"#01)#(,*31%1,*1*/#$:$%";#5!"*#%!"#,&%3,,)#%";'")0%&)"#1$#@"4,5#7>#  
3"/)""$8#R%#(0*#)"$&4%#1*#"f&1';"*%#30;0/"#,)#'")$,*04#1*`&):8  
#
?)"$$#%!"#ˆƒ#,)#q‚#@&%%,*#%,#$"4"(%8  
&
?)"$$&%!"#ꢀvtu‡&@&%%,*#%,#03A0*("#%,#%!"#*"B%#$()""*8  
Heat Test  
<8#?)"$$#T`T#D4"+%G#@&%%,*#&*%14#!"0%#;,3"#1$#31$'40:"38  
H8#W3`&$%#%!"#$"%#%";'")0%&)"#$,#1%#1$#7#3"/)""$#0@,A"#%!"#),,;#%";'")0%&)"8  
I8#P"0%#$!,&43#(,;"#,*#51%!1*#0#+"5#$"(,*3$8#  
Z8# Hh‘v€ˆ€&Crh‡&Tr‡ƒ‚v‡#DC7ꢀF#%,#\>ꢀFG#DZꢀ-#%,#IHꢀ-G#  
#
#
#
W3`&$%#%,#(,*%),4#%!"#;0B1;&;#!"0%#$"%#%";'")0%&)"#044,5"38  
?)"$$#%!"#ˆƒ#,)#q‚#@&%%,*#%,#$"4"(%8  
C8#W3`&$%#%!"#$"%#%";'")0%&)"#H#3"/)""$#@"4,5#%!"#),,;#%";'")0%&)"#0*3#%!"#!"0%#  
$!,&43#%&)*#,++8# !")"#;0:#@"#0#+0*#3"40:#,*#:,&)#$:$%";8  
?)"$$#%!"#ꢀvtu‡#@&%%,*#%,#03A0*("#%,#%!"#*"B%#$()""*8  
#I‚‡r)#F,)#!"0%#'&;'$M#%!")"#1$#0#+,&)N;1*&%"#3"40:#%,#'),%"(%#:,&)#(,;')"$$,)#0+%")#1%#%&)*$#,++8# ,#@:'0$$#%!"#  
(,;')"$$,)#%1;"#3"40:M#/,#%,#OFF#;,3"#+,)#7#$"(,*3$8  
[8# Hvv€ˆ€&8‚‚y&Tr‡ƒ‚v‡#DC7ꢀF#%,#\>ꢀFG#DZꢀ-#%,#IHꢀ-G#  
Cool Test  
#
#
#
W3`&$%#%,#(,*%),4#%!"#;1*1;&;#(,,4#$"%#%";'")0%&)"#044,5"38  
?)"$$#%!"#ˆƒ#,)#q‚#@&%%,*#%,#$"4"(%8  
<8# ?)"$$#T`T#D4"+%G#@&%%,*#&*%14#(,,4#;,3"#1$#31$'40:"38#  
H8# W3`&$%#$"%#%";'")0%&)"#$,#1%#1$#7#3"/)""$#@"4,5#),,;#%";'")0%&)"8  
I8# Wl-#$!,&43#(,;"#,*#51%!1*#0#+"5#$"(,*3$8#  
?)"$$#%!"#ꢀvtu‡#@&%%,*#%,#03A0*("#%,#%!"#*"B%#$()""*8  
C8# W3`&$%#%!"#$"%#%";'")0%&)"#H#3"/)""$#0@,A"#%!"#),,;#%";'")0%&)"#0*3#%!"#Wl-##  
$!,&43#%&)*#,++8# !")"#;0:#@"#0#+0*#3"40:#,*#:,&)#$:$%";8  
\8# S‚‚€&Ur€ƒrꢀh‡ˆꢀr&Pss†r‡#Da\ꢀF#%,#N\ꢀFG#DaC87ꢀ-#%,#NC87ꢀ-G#  
#
#I‚‡r)# !")"#1$#0#+,&)N;1*&%"#%1;"#3"40:#%,#'),%"(%#%!"#(,;')"$$,)#0+%")#1%#8# ,#@:'0$$#%!"#(,;')"$$,)#%1;"#  
3"40:M#/,#%,#OFF#;,3"#+,)#7#$"(,*3$8  
#
#
#
#
W3`&$%#%,#(041@)0%"#31$'40:"3#),,;#%";'")0%&)"#%,#;0%(!#0(%&04#),,;#%";'")0%&)"8#  
#I‚‡r)#>!"%#%'-#5"-#-'#?;# $9$00#&$530*18  
?)"$$#%!"#ˆƒ#,)#q‚#@&%%,*#%,#$"4"(%8  
Fan Test  
?)"$$#%!"#ꢀvtu‡#@&%%,*#%,#03A0*("#%,#%!"#*"B%#$()""*8  
<8# ?)"$$#A6I#D)1/!%G#@&%%,*8#F0*#31$'40:$8#R*3,,)#+0*#%&)*$#O]8  
H8# ?)"$$#A6I#D)1/!%G#@&%%,*8#R*3,,)#+0*#%&)*$#OFF8  
.!!  
Mode of Operation  
 !"#SU%#1$#0#<N$%0/"#,)#HN$%0/"#!"0%#%!");,$%0%8#R%#+&*(%1,*$#51%!#01)#(,*31%1,*1*/M#!"0%#'&;'$M#,)#"4"(%)1(#!"0%#  
$:$%";$8#  
 !"#%!");,$%0%#0(%1A0%"$#%!"#!"0%1*/#0''410*("#5!"*#%!"#),,;#%";'")0%&)"#1$#@"4,5#%!"#$"%#!"0%#%";'")0%&)"#  
D@:#%!"#31++")"*%104#%";'")0%&)"G8# !"#SU%#5144#$%,'#,&%'&%%1*/#5!"*#%!"#(044#+,)#!"0%#!0$#@""*#$0%1$["38#S1%!#  
!"0%#'&;'$M#%!"#%!");,$%0%#5144#*,%#4"%#%!"#(,;')"$$,)#(,;"#,*#+,)#C#;1*&%"$#0+%")#1%#%&)*$#,++8# !1$#'),%"(%$#:,&)#  
(,;')"$$,)8  
Troubleshooting  
Symptom  
Remedy  
-!"(U#+,)#HC#dW-#0%#%!");,$%0%e#31$'40:#1$#@40*U#5!"*#HC#dW-#1$#*,%#  
')"$"*%  
],#31$'40:  
S!"*#%!"#),,;#%";'")0%&)"#1$#/)"0%")#%!0*#%!"#$"%#(,,4#%";'")0%&)"#D@:#%!"#31++")"*%104#%";'")0%&)"GM#%!"#(,,41*/#  
3"A1("#1$#0(%1A0%"38# !"#SU%#5144#$%,'#,&%'&%%1*/#5!"*#%!"#(044#+,)#(,,41*/#1$#$0%1$["38# !"#%!");,$%0%#5144#*,%#4"%#%!"#  
(,;')"$$,)#(,;"#,*#+,)#C#;1*&%"$#0+%")#1%#%&)*$#,++8# !1$#'),%"(%$#:,&)#(,;')"$$,)8  
W44#%!");,$%0%#@&%%,*$#0)"#1*,'")0%1A"  
],#)"$',*$"#51%!#[)$%#@&%%,*#')"$$  
d")1+:#HC#dW-#1$#')"$"*%e#&*1%#4,(U$#,&%#5!"*#HC#dW-#1$#*,%#')"$"*%  
F1)$%#@&%%,*#')"$$#0(%1A0%"$#@0(U41/!%#,*4:  
 !"#SU%#!0$#%!)""#',$$1@4"#,'")0%1*/#;,3"$6#PAAM#Crh‡M#0*3#8‚‚y&;,3"8#R*#,++#;,3"M#%!"#%!");,$%0%#5144#*,%#%&)*#  
,*#!"0%1*/#,)#(,,41*/#3"A1("$8# !"#;0*&04#+0*#(0*#@"#%&)*"3#,*#1*#044#,'")0%1*/#;,3"$#&$1*/#%!"#+0*#@&%%,*8#R*#!"0%#  
;,3"M#%!"#%!");,$%0%#(,*%),4$#%!"#!"0%1*/#$:$%";8#R*#%!"#(,,4#;,3"M#%!"#%!");,$%0%#(,*%),4$#%!"#(,,41*/#$:$%";8#  
 !");,$%0%#%&)*$#,*#0*3#,++#%,,#  
+)"f&"*%4:  
W3`&$%#%";'")0%&)"#31++")"*%104##  
D$""#-,*[/&)0%1,*#2,3"#9"%%1*/$#I#g#CG  
F0*#)&*$#(,*%1*&,&$4:  
?)"$$#FW]#D)1/!%G#@&%%,*#%,#%&)*#+0*#,++  
h,,;#%";'")0%&)"#1$#*,%#(,))"(%  
P"0%#,)#-,,4#*,%#(,;1*/#,*  
-041@)0%"#%!");,$%0%#D$""#-,*[/&)0%1,*#2,3"#9"%%1*/#<>G  
Button Functions  
d")1+:#51)1*/#1$#(,))"(%M#/"*%4:#'&44#,*#"0(!#51)"#%,#A")1+:#%!")"#1$#0#/,,3#  
(,**"(%1,*#0%#%");1*04#@4,(U  
#@&%%,*  
P^W #@41*U1*/  
R*#!"0%#$"%#',1*%#$()""*  
R*#(,,4#$"%#',1*%#$()""*  
?)"$$#h"$"%#@&%%,*#,*("i  
-OOV#@41*U1*/  
9‚#@&%%,*  
?),@4";#*,%#41$%"3#0@,A"  
T`T%";#D4"+%G  
A6I#D)1/!%G  
ꢄ&Sr†r‡&7ˆ‡‡‚&Aˆp‡v‚6#@$530*1#$5#(")("5!"&;#+'%[4.(*-$'%#5"--$%45#*("#.%+!*%4"&8  
VQ#M#b$"3#%,#1*()"0$"#%!"#$"%#%";'")0%&)"$#0*3#%,#03`&$%#(,*[/&)0%1,*#$"%%1*/$8#  
9PXI#M#b$"3#%,#3"()"0$"#%!"#$"%#%";'")0%&)"$#0*3#%,#03`&$%#(,*[/&)0%1,*#$"%%1*/$8  
T`T&ꢂyrs‡ꢃ#M#b$"3#%,#(!0*/"#+),;#OFFM#P^W M#0*3#-OOV#;,3"$  
A6I&ꢂꢀvtu‡ꢃ#M#b$"3#%,#%&)*#,*#0*3#,++#%!"#1*3,,)#+0*8  
F)1"3)1(!#W1)#-,*31%1,*1*/#-,8  
?,$%#O+[("#Y,B#<7C>###90*#W*%,*1,M# "B0$#Z[H\7N<7C>  
CH>>#]8#?0*#W;#^B')"$$50:###90*#W*%,*1,M# "B0$#Z[H<[N7H<H  
DH<>G#I7ZNCC>>###FW_#DH<>G#I7ZNCC[>  
5558+)1"3)1(!8(,;  
VRWF<HX  
46  
Resistance Table for Air Indoor Temperature Sensor  
Temp.  
F  
Resistance  
k  
138.100  
Temp.  
F  
Resistance  
kꢀ  
18.750  
Temp.  
F  
Resistance  
kꢀ  
3.848  
Temp.  
F  
Resistance  
kꢀ  
1.071  
"
"
"
-19  
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
20  
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
59  
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
98  
99  
-18  
-17  
-16  
-15  
-14  
-13  
-12  
-11  
-10  
-9  
128.600  
121.600  
115.000  
108.700  
102.900  
97.400  
92.220  
87.350  
82.750  
78.430  
74.350  
70.500  
66.880  
63.460  
60.230  
57.180  
54.310  
51.590  
49.020  
46.600  
44.310  
42.140  
40.090  
38.150  
36.320  
34.580  
32.940  
31.380  
29.900  
28.510  
27.180  
25.920  
24.730  
23.600  
22.530  
21.510  
20.540  
19.630  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
17.930  
17.140  
16.390  
15.680  
15.000  
14.360  
13.740  
13.160  
12.600  
12.070  
11.570  
11.090  
10.630  
10.200  
9.779  
9.382  
9.003  
8.642  
8.297  
7.967  
7.653  
7.352  
7.065  
6.791  
6.529  
6.278  
6.038  
5.809  
5.589  
5.379  
5.197  
4.986  
4.802  
4.625  
4.456  
4.294  
4.139  
3.990  
60  
61  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
83  
84  
85  
86  
87  
88  
89  
90  
91  
92  
93  
94  
95  
96  
97  
3.711  
3.579  
3.454  
3.333  
3.217  
3.105  
2.998  
2.896  
2.797  
2.702  
2.611  
2.523  
2.439  
2.358  
2.280  
2.206  
2.133  
2.064  
1.997  
1.933  
1.871  
1.811  
1.754  
1.699  
1.645  
1.594  
1.544  
1.497  
1.451  
1.408  
1.363  
1.322  
1.282  
1.244  
1.207  
1.171  
1.136  
1.103  
1.039  
1.009  
0.980  
0.952  
0.925  
0.898  
0.873  
0.848  
0.825  
0.802  
0.779  
0.758  
0.737  
0.717  
0.697  
0.678  
0.660  
0.642  
0.625  
0.608  
0.592  
0.577  
0.561  
0.547  
0.532  
0.519  
0.505  
0.492  
0.480  
0.467  
0.456  
0.444  
0.433  
0.422  
0.412  
0.401  
0.391  
0.382  
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
112  
113  
114  
115  
116  
117  
118  
119  
120  
121  
122  
123  
124  
125  
126  
127  
128  
129  
130  
131  
132  
133  
134  
135  
136  
-8  
-7  
-6  
-5  
-4  
-3  
-2  
-1  
0
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
47  
Resistance Table for Frost Protection Indoor and Outdoor Temperature Sensors  
Temp.  
F  
-19  
-18  
-17  
-16  
-15  
-14  
-13  
-12  
-11  
-10  
-9  
Resistance  
k  
Temp.  
F  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
Resistance  
kꢀ  
Temp.  
F  
59  
60  
61  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
83  
84  
85  
86  
87  
88  
89  
90  
91  
92  
93  
94  
95  
96  
97  
Resistance  
kꢀ  
Temp.  
F  
Resistance  
kꢀ  
"
"
"
181.400  
171.400  
162.100  
153.300  
145.000  
137.200  
129.900  
123.000  
116.500  
110.300  
104.600  
99.130  
94.000  
89.170  
84.610  
80.310  
76.240  
72.410  
68.790  
65.370  
62.130  
59.080  
56.190  
53.460  
50.870  
48.420  
46.110  
43.920  
41.840  
39.870  
38.010  
36.240  
34.570  
32.980  
31.470  
30.040  
28.680  
27.390  
26.170  
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
25.010  
23.900  
22.850  
21.850  
20.900  
20.000  
19.140  
18.130  
17.550  
16.800  
16.100  
15.430  
14.790  
14.180  
13.590  
13.040  
12.510  
12.000  
11.520  
11.060  
10.620  
10.200  
9.803  
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
5.130  
4.948  
4.773  
4.605  
4.443  
4.289  
4.140  
3.998  
3.861  
3.729  
3.603  
3.481  
3.364  
3.252  
3.144  
3.040  
2.940  
2.844  
2.752  
2.663  
2.577  
2.495  
2.415  
2.339  
2.265  
2.194  
2.125  
2.059  
1.996  
1.934  
1.875  
1.818  
1.736  
1.710  
1.658  
1.609  
1.561  
1.515  
1.470  
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
98  
1.427  
1.386  
1.346  
1.307  
1.269  
1.233  
1.198  
1.164  
1.131  
1.099  
1.069  
1.039  
1.010  
0.983  
0.956  
0.930  
0.904  
0.880  
0.856  
0.833  
0.811  
0.770  
0.769  
0.746  
0.729  
0.710  
0.692  
0.674  
0.658  
0.640  
0.623  
0.607  
0.592  
0.577  
0.563  
0.549  
0.535  
0.521  
0.509  
99  
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
112  
113  
114  
115  
116  
117  
118  
119  
120  
121  
122  
123  
124  
125  
126  
127  
128  
129  
130  
131  
132  
133  
134  
135  
136  
-8  
-7  
-6  
-5  
-4  
-3  
-2  
-1  
0
1
2
3
4
9.420  
5
9.054  
6
8.705  
7
8.370  
8
8.051  
9
7.745  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
7.453  
7.173  
6.905  
6.648  
6.403  
6.167  
5.942  
5.726  
5.519  
5.320  
48  
Friedrich Air Conditioning Company  
10001 Reunion Place, Suite 500  
San Antonio, TX 78216  
800.541.6645  
PD-SERIES  
PACKAGED TERMINAL AIR CONDITIONERS  
LIMITED WARRANTY  
SAVE THIS CERTIFICATE. It gives you specific rights. You may also have other rights which may vary from state to state and province to  
province.  
In the event that your unit needs servicing, contact your nearest authorized service center. If you do not know the nearest service center,  
ask the company that installed your unit or contact us - see address and telephone number above. To obtain service and/or warranty parts  
replacement, you must notify an authorized FRIEDRICH Air Conditioning Co. service center, distributor, dealer, or contractor of any defect  
within the applicable warranty period.  
When requesting service: please have the model and serial number from your unit readily available.  
Unless specified otherwise herein, the following applies:  
FRIEDRICH PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS  
LIMITED WARRANTY - FIRST YEAR (Twelve (12) months from the date of installation). Any part found to be defective in the material  
or workmanship will be repaired or replaced free of charge by our authorized service center during the normal working hours; and  
LIMITED WARRANTY - SECOND THROUGH FIFTH YEAR (Sixty (60) months from the date of installation). ON THE SEALED  
REFRIGERATION SYSTEM. Any part of the sealed refrigeration system that is defective in material or workmanship will be repaired or  
replaced free of charge (excluding freight charges) by our authorized service center during normal working hours. The sealed refrigeration  
system consists of the compressor, metering device, evaporator, condenser, reversing valve, check valve, and the interconnecting tubing.  
These warranties apply only while the unit remains at the original site and only to units installed inside the continental United  
States, Alaska, Hawaii, Puerto Rico, Mexico and Canada. The warranty applies only if the unit is installed and operated in  
accordance with the printed instructions and in compliance with applicable local installation and building codes and good trade  
practices. For international warranty information, contact the Friedrich Air Conditioning Company - International Division.  
Any defective part to be replaced must be made available to FRIEDRICH in exchange for the replacement part. Reasonable proof must be  
presented to establish the date of install, otherwise the beginning date of this certificate will be considered to be our shipment date plus sixty  
days. Replacement parts can be new or remanufactured. Replacement parts and labor are only warranted for any unused portion of the  
unit’s warranty.  
We will not be responsible for and the user will pay for:  
1. Service calls to:  
A) Instruct on unit operation. B) Replace house fuses or correct house wiring. C) Clean or replace air filters. D) Remove the unit  
from its installed location when not accessible for service required. E) Correct improper installations.  
2. Parts or labor provided by anyone other than an authorized service center.  
3. Damage caused by:  
A) Accident, abuse, negligence, misuse, riot, fire, flood, or acts of God. B) Operating the unit where there is a corrosive atmosphere  
containing chlorine, fluorine, or any damaging chemicals (other than in a normal residential environment). C) Unauthorized  
alteration or repair of the unit, which in turn affects its stability or performance. D) Failing to provide proper maintenance and  
service. E) Using an incorrect power source. F) Faulty installation or application of the unit.  
We shall not be liable for any incidental, consequential, or special damages or expenses in connection with any use or failure of  
this unit. We have not made and do not make any representation or warranty of fitness for a particular use or purpose and there  
is no implied condition of fitness for a particular use or purpose. We make no expressed warranties except as stated in this  
certificate. No one is authorized to change this certificate or to create for us any other obligation or liability in connection with  
this unit. Any implied warranties shall last for one year after the original purchase date. Some states and provinces do not allow  
limitations on how long an implied warranty or condition lasts, so the above limitations or exclusions may not apply to you. The provisions of  
this warranty are in addition to and not a modification of or subtraction from the statutory warranties and other rights and remedies provided  
by law.  
Performance of Friedrich’s Warranty obligation is limited to one of the following methods:  
1. Repair of the unit  
2. A refund to the customer for the prorated value of the unit based upon the remaining warranty period of the unit.  
3. Providing a replacement unit of equal value  
The method of fulfillment of the warranty obligation is at the sole discretion of Friedrich Air Conditioning.  
In case of any questions regarding the provisions of this warranty, the English version will govern.  
(11-10)  
49  
2011 PTAC EXPLODED VIEW  
50  
2011 PTAC PARTS LIST - PDE MODELS  
Ref. # Description  
Qty  
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
2
1
2
1
1
1
1
1
1
1
3
Part #  
Part #  
Part #  
Part #  
Part #  
Part #  
Part #  
Part #  
1
Air Filter (Pair)  
68700138 68700138 68700138 68700138 68700138 68700138 68700138 68700138  
68700055 68700056 68700057 68700058 68700082 68700083 68700082 68700083  
68700152 68700152 68700152 68700152 68700152 68700152 68700152 68700152  
68700096 68700096 68700015 68700096 68700097 68700097 68700077 68700077  
68700127 68700127 68700127 68700127 68700127 68700127 68700127 68700127  
68700147 68700147 68700147 68700147 68700147 68700147 68700147 68700147  
68700134 68700134 68700134 68700134 68700134 68700134 68700134 68700134  
68700118 68700118 68700118 68700118 68700118 68700118 68700118 68700118  
68700100 68700100 68700107 68700100 68700107 68700107 68700044 68700107  
68700113 68700113 68700113 68700113 68700109 68700108 68700109 68700109  
68700091 68700108 68700091 68700108 68700113 68700109 68700113 68700108  
68700085 68700085 68700017 68700016 68700084 68700084 68700059 68700059  
68700124 68700124 68700124 68700124 68700124 68700124 68700124 68700124  
68700125 68700125 68700125 68700125 68700125 68700125 68700125 68700125  
68700050 68700049 68700001 68700004 68700047 68700048 68700005 68700006  
68700081 68700081 68700102 68700102 68700102 68700102 68700080 68700080  
68700135 68700135 68700135 68700135 68700135 68700135 68700135 68700135  
68700145 68700145 68700145 68700145 68700145 68700145 68700145 68700145  
68700158 68700158 68700158 68700158 68700158 68700158 68700158 68700158  
68700129 68700129 68700129 68700129 68700129 68700129 68700129 68700129  
68700130 68700130 68700130 68700130 68700130 68700130 68700130 68700130  
68700136 68700136 68700136 68700136 68700136 68700136 68700136 68700136  
68700131 68700131 68700131 68700131 68700131 68700131 68700131 68700131  
68700143 68700143 68700143 68700143 68700143 68700143 68700143 68700143  
68700122 68700122 68700122 68700122 68700122 68700122 68700122 68700122  
68700151 68700151 68700151 68700151 68700151 68700151 68700151 68700151  
68700028 68700030 68700032 68700034 68700036 68700038 68700040 68700042  
68700079 68700079 68700014 68700013 68700101 68700101 68700101 68700101  
68700141 68700141 68700141 68700141 68700141 68700141 68700141 68700141  
68700087 68700088 68700087 68700088 68700078 68700086 68700078 68700086  
68700072 68700073 68700070 68700071 68700089 68700090 68700089 68700090  
68700137 68700137 68700137 68700137 68700137 68700137 68700137 68700137  
68700121 68700121 68700121 68700121 68700121 68700121 68700121 68700121  
68700133 68700133 68700133 68700133 68700133 68700133 68700133 68700133  
68700139 68700139 68700139 68700139 68700139 68700139 68700139 68700139  
68700148 68700148 68700148 68700148 68700148 68700148 68700148 68700148  
68700144 68700144 68700144 68700144 68700144 68700144 68700144 68700144  
68700128 68700128 68700128 68700128 68700128 68700128 68700128 68700128  
68700074 68700075 68700098 68700099 68700098 68700099 68700098 68700099  
68700126 68700126 68700126 68700126 68700126 68700126 68700126 68700126  
68700115 68700115 68700115 68700115 68700115 68700115 68700115 68700115  
68700120 68700120 68700120 68700120 68700120 68700120 68700120 68700120  
68700117 68700117 68700117 68700117 68700117 68700117 68700117 68700117  
68700150 68700150 68700150 68700150 68700150 68700150 68700150 68700150  
68700105 68700105 68700105 68700105 68700105 68700105 68700105 68700105  
68700103 68700104 68700103 68700104 68700103 68700104 68700103 68700104  
68700123 68700123 68700123 68700123 68700123 68700123 68700123 68700123  
Air Guide  
*
Ambient Temperature Sensor  
Basepan  
3
4
5
6
7
8
9
9
Bearing Cap  
Bearing Support, Rubber sub-assy  
Bellows Drain Valve  
Bottom Inner Wall Brace  
Capacitor  
Capacitor, Fan  
Capacitor, Fan  
10 Capillary Tube Assy  
11 Chassis Flange, Right  
12 Chassis Flange, Left  
13 Compressor Assy  
14 Condenser Coil  
15 Condenser Fan Blade  
16 Control Door  
17 Control Panel Overlay Escutcheon  
18 Cross flow fan support, left  
19 Cross flow fan support, right  
20 Cross Flow Fan, Evaporator  
21 Deck  
22 Discharge Grille  
23 Discharge Screen  
24 Display Board  
25 Electric Box Assy  
26 Evaporator Coil  
27 Evaporator Foam Drain Tray  
28 Fan Motor, Condenser  
29 Fan Motor, Evaporator  
30 Fan Shroud + Motor Mount  
31 Fresh Air Door  
32 Fresh Air Door Cable  
33 Fresh Air Door Filter  
34 Fresh Air Door Lever  
35 Front Panel Assy (Complete)  
36 Front Panel clip  
37 Heater  
38 Heater Wiring Block Board  
39 Inner Wall assy  
40 Junction box  
41 Junction lid  
42 Lower cover of Fresh Air Door Lever  
44 Relay board  
45 Logic board  
46 Motor Bracket, Indoor  
*
Overload Protector  
68700052 68700051  
n/a  
68700162 68700053 68700161 68700010 68700009  
47 Shroud Brace  
68700119 68700119 68700119 68700119 68700119 68700119 68700119 68700119  
68700110 68700110 68700110 68700110 68700110 68700110 68700110 68700110  
68700156 68700156 68700156 68700156 68700156 68700156 68700156 68700156  
68700132 68700132 68700132 68700132 68700132 68700132 68700132 68700132  
68700116 68700116 68700116 68700116 68700116 68700116 68700116 68700116  
68700112 68700111 68700112 68700111 68700112 68700111 68700112 68700111  
68700153 68700153 68700153 68700153 68700153 68700153 68700153 68700153  
68700149 68700149 68700149 68700149 68700149 68700149 68700149 68700149  
68700154 68700154 68700154 68700154 68700154 68700154 68700154 68700154  
68700155 68700155 68700155 68700155 68700155 68700155 68700155 68700155  
*
Temperature Sensor  
48 Terminal Board, Input power  
49 Thermal baffle  
50 Top Cover Plate Sub-Assy  
51 Transformer  
*
Tube Thermistor  
52 Upper cover of Fresh Air Door Lever  
53 Wiring Terminal, 2 position 24VAC  
54 Wiring Terminal, 7 position 24VAC  
55 Compressor Grommets  
68700046 68700046 68700046 68700046 68700046 68700046  
68700046 68700076  
51  
2011 PTAC PARTS LIST - PDH MODELS  
Ref. # Description  
Qty Friedrich # Friedrich # Friedrich # Friedrich # Friedrich # Friedrich # Friedrich # Friedrich #  
1
2
*
Air Filter (Pair)  
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
2
1
1
1
3
1
1
68700138 68700138 68700138 68700138 68700138 68700138 68700138 68700138  
68700055 68700056 68700057 68700058 68700082 68700083 68700082 68700083  
68700152 68700152 68700152 68700152 68700152 68700152 68700152 68700152  
68700096 68700096 68700097 68700097 68700097 68700097 68700160 68700077  
68700127 68700127 68700127 68700127 68700127 68700127 68700127 68700127  
68700147 68700147 68700147 68700147 68700147 68700147 68700147 68700147  
68700134 68700134 68700134 68700134 68700134 68700134 68700134 68700134  
68700118 68700118 68700118 68700118 68700118 68700118 68700118 68700118  
68700100 68700100 68700107 68700100 68700107 68700107 68700043 68700107  
68700113 68700113 68700113 68700113 68700109 68700108 68700109 68700109  
68700091 68700108 68700091 68700108 68700113 68700109 68700113 68700108  
68700085 68700085 68700060 68700060 68700084 68700084 68700018 68700019  
68700124 68700124 68700124 68700124 68700124 68700124 68700124 68700124  
68700125 68700125 68700125 68700125 68700125 68700125 68700125 68700125  
68700050 68700049 68700002 68700003 68700047 68700048 68700007 68700008  
68700081 68700081 68700102 68700102 68700102 68700102 68700080 68700080  
68700135 68700135 68700135 68700135 68700135 68700135 68700135 68700135  
68700145 68700145 68700145 68700145 68700145 68700145 68700145 68700145  
68700158 68700158 68700158 68700158 68700158 68700158 68700158 68700158  
68700129 68700129 68700129 68700129 68700129 68700129 68700129 68700129  
68700130 68700130 68700130 68700130 68700130 68700130 68700130 68700130  
68700136 68700136 68700136 68700136 68700136 68700136 68700136 68700136  
68700131 68700131 68700131 68700131 68700131 68700131 68700131 68700131  
68700143 68700143 68700143 68700143 68700143 68700143 68700143 68700143  
68700122 68700122 68700122 68700122 68700122 68700122 68700122 68700122  
68700151 68700151 68700151 68700151 68700151 68700151 68700151 68700151  
68700029 68700031 68700033 68700035 68700037 68700039 68700041 68700027  
68700079 68700079 68700054 68700054 68700101 68700101 68700101 68700101  
68700141 68700141 68700141 68700141 68700141 68700141 68700141 68700141  
68700087 68700088 68700087 68700088 68700078 68700086 68700089 68700086  
68700072 68700073 68700070 68700071 68700089 68700090 68700026 68700090  
68700137 68700137 68700137 68700137 68700137 68700137 68700137 68700137  
68700121 68700121 68700121 68700121 68700121 68700121 68700121 68700121  
68700133 68700133 68700133 68700133 68700133 68700133 68700133 68700133  
68700139 68700139 68700139 68700139 68700139 68700139 68700139 68700139  
68700148 68700148 68700148 68700148 68700148 68700148 68700148 68700148  
68700144 68700144 68700144 68700144 68700144 68700144 68700144 68700144  
68700128 68700128 68700128 68700128 68700128 68700128 68700128 68700128  
68700074 68700075 68700098 68700099 68700098 68700099 68700098 68700099  
68700126 68700126 68700126 68700126 68700126 68700126 68700126 68700126  
68700115 68700115 68700115 68700115 68700115 68700115 68700115 68700115  
68700120 68700120 68700120 68700120 68700120 68700120 68700120 68700120  
68700117 68700117 68700117 68700117 68700117 68700117 68700117 68700117  
68700150 68700150 68700150 68700150 68700150 68700150 68700150 68700150  
68700093 68700092 68700093 68700092 68700093 68700092 68700093 68700092  
68700106 68700106 68700106 68700106 68700106 68700106 68700106 68700106  
68700103 68700104 68700103 68700104 68700103 68700104 68700103 68700104  
68700123 68700123 68700123 68700123 68700123 68700123 68700123 68700123  
Air Guide  
Ambient Temperature Sensor  
3
4
5
6
7
8
9
9
Basepan  
Bearing Cap  
Bearing Support, Rubber sub-assy  
Bellows Drain Valve  
Bottom Inner Wall Brace  
Capacitor  
Capacitor, Fan  
Capacitor, Fan  
10 Capillary Tube Assy  
11 Chassis Flange, Left  
12 Chassis Flange, Right  
13 Compressor Assy  
14 Condenser Coil  
15 Condenser Fan Blade  
16 Control Door  
17 Control Panel Overlay Escutcheon  
18 Cross flow fan support, left  
19 Cross flow fan support, right  
20 Cross Flow Fan, Evaporator  
21 Deck  
22 Discharge Grille  
23 Discharge Screen  
24 Display Board  
25 Electric Box Assy  
26 Evaporator Coil  
27 Evaporator Foam Drain Tray  
28 Fan Motor, Condenser  
29 Fan Motor, Evaporator  
30 Fan Shroud + Motor Mount  
31 Fresh Air Door  
32 Fresh Air Door Cable  
33 Fresh Air Door Filter  
34 Fresh Air Door Lever  
35 Front Panel Assy (Complete)  
36 Front Panel clip  
37 Heater  
38 Heater Wiring Block Board  
39 Inner Wall assy  
40 Junction box  
41 Junction lid  
42 Lower cover of Fresh Air Door Lever  
43 Solenoid Coil  
44 Relay board  
45 Logic board  
46 Motor Bracket, Indoor  
*
Overload Protector  
68700052 68700051 68700012  
n/a  
68700053  
n/a  
n/a  
68700011  
47 Shroud Brace  
68700119 68700119 68700119 68700119 68700119 68700119 68700119 68700119  
68700156 68700156 68700156 68700156 68700156 68700156 68700156 68700156  
68700132 68700132 68700132 68700132 68700132 68700132 68700132 68700132  
68700116 68700116 68700116 68700116 68700116 68700116 68700116 68700116  
68700112 68700111 68700112 68700111 68700112 68700111 68700112 68700111  
68700153 68700153 68700153 68700153 68700153 68700153 68700153 68700153  
68700149 68700149 68700149 68700149 68700149 68700149 68700149 68700149  
68700154 68700154 68700154 68700154 68700154 68700154 68700154 68700154  
68700155 68700155 68700155 68700155 68700155 68700155 68700155 68700155  
48 Terminal Board, Input power  
49 Thermal baffle  
50 Top Cover Plate Sub-Assy  
51 Transformer  
*
Tube Thermistor  
52 Upper cover of Fresh Air Door Lever  
53 Wiring Terminal, 2 position 24VAC  
54 Wiring Terminal, 7 position 24VAC  
55 Compressor Gasket  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
68700045 68700076  
56 4-way Reversing Valve Assy  
56 4-way Reversing Valve Assy  
68700094 68700094 68700094 68700094 68700095 68700095 68700095 68700095  
68700062 68700062 68700063 68700063 68700061 68700061 68700020 68700021  
52  
FRIEDRICH AIR CONDITIONING CO.  
10001 Reunion Place, Ste. 500, San Antonio, TX 78216  
P 210-546-0500 | F 210-546-0731  
Printed in the U.S.A.  
PD-ServMan-E (2-11)  

Canon PIXMA MX420 User Manual
Canon Printer H12 4603 User Manual
Epson C243 User Manual
Friedrich HEAT COOLING MODEL INVERTER REVERSE CYCLE ROOM AIR CONDITIONER WALL MOUNTED TYPE User Manual
Friedrich MR36C3G User Manual
Friedrich SQ06N10 User Manual
GE Zoneline AZ28E12D User Manual
Goodman Mfg ADPF User Manual
Haier Commercial Cool CPN11XCJ User Manual
Hitachi RAS 35YH6 User Manual