Carrier 48TJE008 014 User Manual

48TJD008-014  
48TJE008-014  
48TJF008-012  
Single-Package Rooftop Heating/Cooling Units  
Installation, Start-Up and  
Service Instructions  
CONTENTS  
Page  
Disconnect gas piping from unit when leak  
testing at pressure greater than12 psig. Pres-  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1  
1
sures greater than 2 psig will cause gas  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-22  
Step 1 — Provide Unit Support . . . . . . . . . . . . . . . 1  
• ROOF CURB  
• SLAB MOUNT  
Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . 2  
Step 3 — Install External Trap for  
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Step 4 — Rig and Place Unit . . . . . . . . . . . . . . . . . . 2  
• POSITIONING  
valve damage resulting in hazardous con-  
dition. If gas valve is subjected to pres-  
sure greater than 12 psig, it must be replaced  
before use. When pressure testing field-  
supplied gas piping at pressures of 12 psig  
or less, a unit connected to such piping must  
be isolated by manually closing the gas  
valve(s).  
Step 5 — Install Flue Hood . . . . . . . . . . . . . . . . . . . 8  
Step 6 — Install Gas Piping . . . . . . . . . . . . . . . . . . . 8  
Step 7 — Make Electrical Connections . . . . . . . . 8  
• FIELD POWER SUPPLY  
Before performing service or maintenance operations on  
unit, turn off main power switch to unit. Electrical shock  
could cause personal injury.  
• FIELD CONTROL WIRING  
• HEAT ANTICIPATOR SETTINGS  
Step 8 — Adjust Factory-Installed Options . . . 11  
• APOLLO CONTROL  
• MANUAL OUTDOOR-AIR DAMPER  
• OPTIONAL DURABLADE ECONOMIZER  
• OPTIONAL PARABLADE ECONOMIZER  
Step 9 — Adjust Evaporator-Fan Speed . . . . . . 16  
INSTALLATION  
Unit is shipped in the vertical discharge configuration. To  
convert to horizontal configuration, remove screws from side  
duct opening covers and remove covers. Using the same screws,  
install covers on vertical duct openings with the insulation-  
side down. Seals around duct openings must be tight. See  
Fig. 1.  
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23,24  
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-30  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . 31-36  
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . CL-1  
Step 1 — Provide Unit Support  
ROOF CURB — Assemble and install accessory roof curb  
in accordance with instructions shipped with curb. See  
Fig. 2. Install insulation, cant strips, roofing felt, and counter  
flashing as shown. Ductwork must be attached to curb. If  
gas is to be routed through the curb, attach the accessory  
thru-the-curb service connection plate to the roof curb in ac-  
cordance with the accessory installation instructions. Con-  
nection plate must be installed before unit is set in roof curb.  
SAFETY CONSIDERATIONS  
Installation and servicing of air-conditioning equipment  
can be hazardous due to system pressure and electrical com-  
ponents. Only trained and qualified service personnel should  
install, repair, or service air-conditioning equipment.  
Untrained personnel can perform basic maintenance func-  
tions of cleaning coils and filters and replacing filters. All  
other operations should be performed by trained service per-  
sonnel. When working on air-conditioning equipment, ob-  
serve precautions in the literature, tags and labels attached  
to the unit, and other safety precautions that may apply.  
IMPORTANT: The gasketing of the unit to the roof  
curb is critical for a watertight seal. Install gasket sup-  
plied with the roof curb as shown in Fig. 2. Improp-  
erly applied gasket can also result in air leaks and poor  
unit performance.  
Curb should be level. Unit leveling tolerances are shown  
in Fig. 3. This is necessary for unit drain to function prop-  
erly. Refer to Accessory Roof Curb Installation Instructions  
for additional information as required.  
Follow all safety codes. Wear safety glasses and work gloves.  
Use quenching cloth for unbrazing operations. Have fire ex-  
tinguishers available for all brazing operations.  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 1 PC 111 Catalog No. 564-934 Printed in U.S.A. Form 48TJ-13SI Pg 1 9-96 Replaces: 48TJ-10SI  
Tab 1a 6a  
4
CONNECTOR  
ACCESSORY  
PACKAGE  
UNIT SIZE  
48TJ  
‘‘E’’  
POWER  
CONTROL  
‘‘B’’  
‘‘C’’  
‘‘D’’ ALT DRAIN HOLE  
GAS CONNECTION CONNECTION  
CRBTMPWR00A100  
3
3
3
1
4Љ NPT  
4Љ NPT  
4Љ NPT  
2
Љ NPT  
(THRU-THE-BOTTOM)  
008-014 2Ј-8716Љ [827] 1Ј-101516Љ [583]  
134Љ [45]  
CRBTMPWR00A200  
(THRU-THE-BOTTOM)  
1
114Љ NPT  
2Љ NPT  
UNIT SIZE  
48TJ  
ROOF CURB  
‘‘A’’  
ACCESSORY  
1Ј-2Љ [356] CRRFCURB003A00  
008-014  
Fig. 2 — Roof Curb Details  
3
MAXIMUM ALLOWABLE  
DIFFERENCE (in.)  
A-B  
0.5  
B-C  
A-C  
1.0  
1.0  
Fig. 3 — Unit Leveling Tolerances  
NOTE: Trap should be deep enough to offset maximum unit static  
difference. A 4-in. trap is recommended.  
Fig. 5 — External Trap Condensate Drain  
Locate mechanical draft system flue assembly at least  
48 in. from any opening through which combustion prod-  
ucts could enter the building, and at least 48 in. from an ad-  
jacent building or combustible material. When unit is located  
adjacent to public walkways, flue assembly must be at least  
7 ft above grade.  
Flue vent discharge must have a minimum horizontal clear-  
ance of 48 in. from electric and gas meters, gas regulators,  
and gas relief equipment.  
Flue gas can deteriorate building materials. Orient unit so  
that flue gas will not affect building materials.  
Adequate combustion-air space must be provided for proper  
operation of this equipment. Be sure that installation com-  
plies with all local codes and Section 5.3, Air for Combus-  
tion and Ventilation, NFGC (National Fuel Gas Code), ANSI  
(American National Standards Institute) Z223.1-latest year  
and addendum Z223.1A-latest year. In Canada, installation  
must be in accordance with the CAN1. B149.1 and  
CAN1.B149.2 installation codes for gas burning appliances.  
NOTE: Drain plug is shown in factory-installed position.  
Fig. 4 — Condensate Drain Pan  
NOTES:  
DIMENSIONS  
‘‘B’’  
MAX  
1. Dimension in ( ) is in millimeters.  
WEIGHT  
UNIT  
‘‘A’’  
‘‘C’’  
2. Hook rigging shackles through holes in base rail as shown in detail ‘‘A.’’  
Holes in base rails are centered around the unit center of gravity. Use wooden  
top skid when rigging to prevent rigging straps from damaging unit.  
3. Weights include base unit without economizer. See Table 1 for economizer  
weights.  
lb  
kg  
in.  
mm  
in.  
mm  
in.  
mm  
48TJD/TJE/TJF008  
48TJD/TJE/TJF009  
870 395 87.38 2219 40.25 1022 41.31 1050  
880 399 87.38 2219 40.25 1022 41.31 1050  
48TJD/TJE/TJF012 1035 469 87.38 2219 40.25 1022 49.31 1253  
48TJD/TJE014 1050 476 87.38 2219 40.25 1022 49.31 1253  
All panels must be in place when rigging.  
Fig. 6 — Rigging Details  
4
Table 1 — Physical Data  
UNIT SIZE 48TJ  
008D/E/F  
009D/E/F  
012D/E/F  
014D/E  
1212  
NOMINAL CAPACITY (tons)  
712  
812  
10  
OPERATING WEIGHT (lb)  
Unit  
Al/Al*  
870  
881  
893  
44  
880  
896  
907  
44  
1035  
1057  
1080  
44  
1050  
1077  
1100  
44  
Al/Cu*  
Cu/Cu*  
Durablade Economizer  
PARBLADE Economizer  
Roof Curb  
62  
62  
62  
62  
143  
143  
143  
143  
COMPRESSOR  
Quantity  
Oil (oz)  
Reciprocating  
Scroll  
2
54 ea  
2
2
2
50 ea  
50 ea  
50 ea  
REFRIGERANT TYPE  
Operating Charge (lb-oz)  
Circuit 1  
R-22  
4-13  
4-14  
6-14  
6-3  
5-13  
5-14  
8-10  
8- 6  
Circuit 2  
CONDENSER COIL  
Rows...Fins/in.  
Total Face Area (sq ft)  
Enhanced Copper Tubes, Aluminum Lanced Fins  
1...17  
20.50  
2...17  
18.00  
2...17  
17.42  
2...17  
25.00  
CONDENSER FAN  
Nominal Cfm  
Propeller Type  
6500  
6500  
7000  
2...22  
4...1100  
600  
7000  
Quantity...Diameter (in.)  
Motor Hp...Rpm  
2...22  
2...22  
2...22  
1
1
1
1
4...1100  
600  
4...1100  
600  
4...1100  
600  
Watts Input (Total)  
EVAPORATOR COIL  
Rows...Fins/in.  
Total Face Area (sq ft)  
Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol™ Feed Device  
3...15  
8.0  
3...15  
8.0  
3...15  
10.0  
4...15  
11.1  
EVAPORATOR FAN  
Quantity...Size (in.)  
Centrifugal Type  
Std  
Alt  
1...15 x 15  
1...15 x 15  
Belt  
1...15 x 15  
1...15 x 15  
1...15 x 15  
Belt  
1...15 x 15  
1...15 x 15  
Belt  
Type Drive  
Std  
Alt  
Belt  
Belt  
Belt  
Belt  
Nominal Cfm  
Motor Hp  
3000  
3400  
4000  
5000  
Std  
Alt  
Maximum Continuous Bhp  
Motor Frame Size  
Std  
Alt  
2.40  
2.40  
2.40  
4.20  
2.90  
5.25  
Std  
Alt  
56  
56  
56  
56  
56  
56  
Nominal Rpm High/Low  
Fan Rpm Range  
Std  
Alt  
590-840  
685-935  
Ball  
685-935  
Ball  
2100  
2.8/3.8  
685-935  
835-1085  
Ball  
860-1080  
900-1260  
Ball  
Motor Bearing Type  
Maximum Allowable Rpm  
2100  
2.4/3.4  
2100  
2.8/3.8  
2100  
4.0/5.0  
Motor Pulley Pitch Diameter Min/Max (in.) Std  
Alt  
2.8/3.8  
3.4/4.4  
3.1/4.1  
5
5
5
7
Nominal Motor Shaft Diameter (in.)  
Std  
Alt  
Std  
Alt  
8
8
8
8
7
7
8
8
Fan Pulley Pitch Diameter (in.)  
7.0  
7.0  
7.0  
8.0  
7.0  
7.0  
5.9  
Nominal Fan Shaft Diameter (in.)  
Belt, Quantity...Type...Length (in.)  
Std  
Alt  
1...A...48  
1...A...48  
1...A...51  
1...A...51  
1...A...51  
1...A...57  
1...BX...46  
Pulley Center Line Distance (in.)  
Std  
Alt  
16.75-19.25  
16.75-19.25  
15.85-17.50  
15.85-17.50  
15.85-17.50  
16.75-19.25  
50  
5
5
685  
1
15.85-17.50  
Speed Change per Full Turn of  
Movable Pulley Flange (rpm)  
Movable Pulley Maximum Full Turns  
From Closed Position  
Std  
Alt  
50  
50  
5
50  
50  
5
44  
50  
5
Std  
Alt  
5
5
6
Factory Setting  
Std  
Alt  
5
5
5
5
5
6
Factory Speed Setting (rpm)  
Std  
Alt  
590  
685  
1
685  
835  
1
860  
960  
1
Fan Shaft Diameter at Pulley (in.)  
(See legend and notes on page 6.)  
5
Table 1 — Physical Data (cont)  
UNIT SIZE 48TJ  
008D/E/F  
009D/E/F  
012D/E/F  
014D/E  
FURNACE SECTION  
Rollout Switch Cutout  
Temp (F)  
195  
195  
195  
195  
Burner Orifice Diameter  
(in. ...drill size)  
Natural Gas  
Std  
Alt  
.120...31  
.096...41  
.120...31  
.096...41  
.120...31/.120...31/.129...30 .120...31/.129...30  
.096...41/.096...41/.102...38 .096...41/.102...38  
Liquid Propane  
Pilot Orifice Diameter  
(Quantity) in. ...drill size  
Natural Gas  
Std  
Alt  
Liquid Propane  
Thermostat Heat Anticipator  
Setting (amps)  
208/230 v Stage 1  
Stage 2  
.14  
.20  
.14  
.20  
.14  
.20  
.14  
.20  
.14  
.20  
.14  
.20  
.14  
.20  
.14  
.20  
460 v Stage 1  
Stage 2  
Gas Input (Btuh) Stage 1  
Stage 2  
125,000/120,000/180,000 125,000/120,000/180,000 120,000/180,000/200,000 180,000/200,000  
—/180,000/224,000  
—/180,000/224,000  
180,000/224,000/250,000 224,000/250,000  
Efficiency (Steady  
State) (%)  
80  
80  
80  
80  
Temperature Rise Range  
Manifold Pressure (in. wg)  
Natural Gas  
20-50/35-65/45-75  
20-50/35-65/45-75  
35-65/35-65/40-70  
35-65/40-70  
Std  
Alt  
3.5  
3.5  
1
3.5  
3.5  
1
3.5  
3.5  
1
3.5  
3.5  
1
Liquid Propane  
Gas Valve Quantity  
Field Gas Connection  
Size (in.)  
1
1
3
3
4/34  
2/34/34  
2/34/34  
4/34/34  
HIGH-PRESSURE SWITCH (psig)†  
Standard Compressor  
Internal Relief (Differential)  
Cutout  
450 ± 50  
500 ± 50  
428  
320  
428  
320  
Reset (Auto.)  
LOW-PRESSURE SWITCH (psig)†  
Cutout  
Reset (Auto.)  
7 ± 3  
22 ± 7  
FREEZE PROTECTION  
THERMOSTAT (F)†  
Opens  
30 ± 5  
45 ± 5  
Closes  
OUTDOOR-AIR INLET SCREENS  
Quantity...Size (in.)  
Cleanable  
1...20 x 25 x 1  
1...16 x 25 x 1  
RETURN-AIR FILTERS  
Quantity...Size (in.)  
Throwaway  
4...16 x 20 x 2  
4...16 x 20 x 2  
4...20 x 20 x 2  
4...20 x 20 x 2  
LEGEND  
*Evaporator coil fin material/condenser coil fin material.  
†Requires an optional or accessory controls kit.  
Al  
Bhp  
Cu  
Aluminum  
Brake Horsepower  
Copper  
NOTE: The 48TJ008-014 units have a loss-of-charge/low-pressure  
switch (accessory) located in the liquid line.  
6
CONNECTION SIZES  
STANDARD CORNER CORNER CORNER CORNER  
UNIT  
WEIGHT WEIGHT WEIGHT WEIGHT  
(A) (B) (C) (D)  
‘‘H’’  
‘‘J’’  
‘‘K’’  
‘‘L’’  
UNIT  
48TJ  
A
B
C
D
E
138Љ Dia [35] Field Power Supply Hole  
2-12Љ Dia [64] Power Supply Knock-Out  
134Љ Dia [44] Charging Port Hole  
WEIGHT  
Lb  
Kg  
Lb Kg Lb Kg Lb Kg Lb Kg ft-in. mm ft-in. mm  
ft-in. mm ft-in. mm  
86 161 73 239 109 280 127 1-278 378 3-5516 1050 2-91116 856 2- 2716 672  
87 163 74 242 110 284 129 3-378 1013 3-5516 1050 2-91116 856 2- 2716 672  
D/E/F008  
D/E/F009  
870 395 189  
880 399 191  
7
8Љ Dia [22] Field Control Wiring Hole  
4Љ—14 NPT Condensate Drain  
3
D/E/F012 1035 469 225 102 192 87 285 129 333 151 2-578 759 4-1516 1253 3-038  
D/E014  
1050 476 228 103 195 88 289 131 338 153 1-278 378 4-1516 1253 3-038  
924 2-10716 875  
924 2-10716 875  
1
3
2Љ—14 NPT Gas Connection 48TJD008 & 009  
4Љ—14 NPT Gas Connection 48TJE/F008 & 009;  
F
48TJD/E012,014, 48TJF012  
G
2Љ Dia [51] Power Supply Knock-Out  
NOTES:  
1. Dimensions in [ ] are in millimeters.  
BOTTOM POWER CHART, THESE HOLES  
REQUIRED FOR USE WITH ACCESSORY  
PACKAGES — CRBTMPWR001A00,  
OR CRBTMPWR002A00  
THREADED  
CONDUIT SIZE  
REQUIRED HOLE  
SIZES (MAX)  
WIRE SIZE  
1
7
2
؆
24 V  
Power*  
Power*  
8Љ [22.2]  
3
4؆  
118Љ [28.4]  
134Љ [44.4]  
114  
؆
3
*Select either ⁄  
4Љ or 114Љ for power, depending on wire size.  
Fig. 7 — Base Unit Dimensions  
7
Step 5 — Install Flue Hood — Flue hood is shipped  
screwed to the burner compartment access panel. Remove  
from shipping location and, using screws provided, install  
flue hood and screen in location shown in Fig. 8.  
Step 6 — Install Gas Piping — Unit is equipped for  
use with type of gas shown on nameplate. Refer to local build-  
ing codes, or in the absence of local codes, to ANSI Z223.1-  
latest year and addendum Z223.1A-latest year entitled  
National Fuel Gas Code. In Canada, installation must be in  
accordance with the CAN1.B149.1 and CAN1.B149.2 in-  
stallation codes for gas burning appliances.  
For natural gas applications, gas pressure at unit gas con-  
nection must not be less than 4.0 in. wg (5.0 in. wg in high  
heat units) or greater than 13.0 in. wg while unit is operat-  
ing. For liquid propane applications, the gas pressure must  
not be less than 5.0 in. wg or greater than 13.0 in. wg at the  
unit connection.  
LEGEND  
SPACING OF SUPPORTS  
NFGC  
National Fuel Gas Code  
STEEL PIPE  
X
*Field supplied.  
NOMINAL  
DIMENSION  
DIAMETER  
(feet)  
NOTE: Follow all local codes.  
(in.)  
1
Size gas supply piping for 0.5 in. wg maximum pres-  
sure drop. Do not use supply pipe smaller than unit gas  
connection.  
2  
6
8
10  
3
4
or 1  
114 or larger  
Support gas piping as shown in the table in Fig. 9. For  
example, a 34-in. gas pipe must have one field-fabricated sup-  
port beam every 8 ft. Therefore, an 18-ft long gas pipe would  
have a minimum of 2 support beams, and a 48-ft long pipe  
would have a minimum of 6 support beams.  
See Fig. 9 for typical pipe guide and locations of external  
manual gas shutoff valve.  
Fig. 9 — Gas Piping Guide (With Accessory  
Thru-the-Curb Service Connections)  
FIELD POWER SUPPLY — All units except 208/230-v units  
are factory wired for the voltage shown on the nameplate. If  
the 208/230-v unit is to be connected to a 208-v power sup-  
ply, the transformer must be rewired by moving the black  
wire from the 230-v red wire on the transformer and con-  
necting it to the 200-v blue wire from the transformer. The  
red wire then must be insulated.  
Step 7 — Make Electrical Connections  
Refer to unit label diagram for additional information. Pig-  
tails are provided for field service.  
Unit cabinet must have an uninterrupted, unbroken elec-  
trical ground to minimize the possibility of personal in-  
jury if an electrical fault should occur. This ground may  
consist of electrical wire connected to unit ground lug  
in control compartment, or conduit approved for elec-  
trical ground when installed in accordance with NEC  
(National Electrical Code), ANSI/NFPA (National Fire  
Protection Association), latest edition, and local elec-  
trical codes. Do not use gas piping as an electrical ground.  
Failure to follow this warning could result in the in-  
staller being liable for personal injury of others.  
When installing units, provide a disconnect per NEC. Use  
copper conductors only when splice connectors are used.  
All field wiring must comply with NEC and local require-  
ments. In Canada, electrical connections must be in accor-  
dance with CSA (Canadian Standards Association) C22.1  
Canadian Electrical Code Part One.  
Install conduit through side panel openings indicated in  
Fig. 7. Route power lines through connector to terminal con-  
nections as shown in Fig. 10.  
On 3-phase units, voltages between phases must be bal-  
anced within 2% and the current within 10%. Use the for-  
mula shown in Table 2, Note 2 to determine the percentage  
of voltage imbalance. Operation on improper line voltage or  
excessive phase imbalance constitutes abuse and may cause  
damage to electrical components. Such operation would in-  
validate any applicable Carrier warranty.  
NOTE: If field-installed thru-the-bottom connections are used,  
refer to the accessory installation instructions for power wir-  
ing. Refer to Fig. 7 for drilling holes in basepan.  
FIELD CONTROL WIRING — Install a Carrier-approved  
accessory thermostat assembly according to installation in-  
structions included with the accessory. Locate thermostat as-  
sembly on a solid wall in the conditioned space to sense av-  
erage temperature in accordance with thermostat installation  
instructions.  
NOTE: For wire runs up to 50 ft, use no. 18 AWG (Ameri-  
can Wire Gage) insulated wire (35 C minimum). For 50 to  
75 ft, use no. 16 AWG insulated wire (35 C minimum). For  
over 75 ft, use no. 14 AWG insulated wire (35 C minimum).  
All wire larger than no. 18 AWG cannot be directly con-  
nected to the thermostat and will require a junction box and  
splice at the thermostat.  
Fig. 8 — Flue Hood Details  
8
Route thermostat cable or equivalent single leads of col-  
ored wire from subbase terminals to low-voltage connec-  
tions on unit (shown in Fig. 11) as described in Steps 1 - 4  
below.  
1. If unit is mounted on roof curb and accessory thru-the-  
curb service plate connection is used, route wire through  
connection plate.  
box. See Fig. 12. The raceway provides the UL-required  
(UnderwritersLaboratories) clearance between high- and  
low-voltage wiring.  
4. Connect thermostat wires to screw terminals on low-  
voltage connection board.  
HEAT ANTICIPATOR SETTINGS — Set heat anticipator  
settings at .14 amp for the first stage and .20 amp for second-  
stage heating.  
2. Pass control wires through the hole provided on unit  
(see connection D in Connection Sizes table in Fig. 7).  
3. Feed wires through the raceway built into the corner post  
to the 24-v barrier located on the left side of the control  
Table 2 — Electrical Data  
VOLTAGE  
RANGE  
COMPR  
(ea)  
OFM  
(ea)  
COMBUSTION  
FAN MOTOR  
DISCONNECT  
SIZE*  
NOMINAL  
VOLTAGE  
(60 Hz)  
IFM  
POWER SUPPLY  
MCA  
UNIT  
48TJ  
IFM  
TYPE  
Min Max RLA LRA Hp FLA FLA  
FLA  
MOCP† FLA  
LRA  
208/230  
1
Std  
Std  
Std  
Std  
Std  
Std  
187 254 13.6  
73.4  
37.7  
31.0  
92.0  
46.0  
44.0  
4
4
4
4
4
4
1.4  
0.8  
0.8  
1.4  
0.8  
0.8  
5.8  
2.6  
2.6  
5.8  
2.6  
2.6  
.57  
39.2/39.2  
18.0  
45/45  
25  
41/41 194/194  
(3 phase)  
008  
460  
(3 phase)  
1
1
1
1
1
414 508  
518 632  
6.2  
4.9  
.30  
.30  
.57  
.30  
.30  
19  
15  
99  
81  
(712 Tons)  
575  
(3 phase)  
14.2  
20  
208/230  
(3 phase)  
187 254 15.8  
44.2/44.2  
20.7  
50/50  
25  
46/46 231/231  
009  
460  
(3 phase)  
414 508  
518 632  
7.4  
5.9  
22  
17  
116  
107  
(812 Tons)  
575  
(3 phase)  
16.5  
20  
Std  
Alt  
5.8  
7.5  
2.6  
3.4  
2.6  
3.4  
10.6  
15.0  
4.8  
7.4  
4.8  
7.4  
48.9/48.9  
50.6/50.6  
23.4  
60/60  
60/60  
30  
51/51 267/267  
53/53 286/286  
208/230  
1
1
1
1
1
1
187 254 17.9 110.0  
4
4
4
4
4
4
1.4  
0.8  
0.8  
1.4  
0.8  
0.8  
.57  
.30  
.30  
.57  
.30  
.30  
(3 phase)  
Std  
Alt  
24  
25  
18  
19  
134  
173  
107  
139  
012  
460  
(3 phase)  
414 508  
518 632  
8.6  
6.4  
55.0  
44.0  
(10 Tons)  
24.2  
30  
Std  
Alt  
17.6  
20  
575  
(3 phase)  
18.2  
20  
Std  
Alt  
65.2/65.2  
69.6/69.6  
29.6  
80/80  
80/80  
35  
68/68 383/383  
73/73 406/406  
208/230  
(3 phase)  
187 254 23.0 146.0  
Std  
Alt  
31  
34  
25  
27  
192  
203  
154  
163  
014  
460  
414 508 10.4  
518 632 8.3  
73.0  
58.4  
(1212 Tons) (3 phase)  
32.2  
35  
Std  
Alt  
23.6  
30  
575  
(3 phase)  
25.7  
35  
LEGEND  
EXAMPLE: Supply voltage is 460-3-60.  
FLA  
Full Load Amps  
AB = 452 v  
BC = 464 v  
AC = 455 v  
HACR  
IFM  
Heating, Air Conditioning and Refrigeration  
Indoor (Evaporator) Fan Motor  
Locked Rotor Amps  
LRA  
MCA  
MOCP  
NEC  
OFM  
RLA  
UL  
452 + 464 + 455  
Minimum Circuit Amps  
Average Voltage =  
Maximum Overcurrent Protection  
National Electrical Code  
3
1371  
3
Outdoor (Condenser) Fan Motor  
Rated Load Amps  
=
=
Underwriters’ Laboratories  
457  
*Used to determine minimum disconnect size per NEC.  
†Fuse or HACR circuit breaker.  
NOTE: The 575-v 48TJ008-014 units are UL, Canada, only.  
Determine maximum deviation from average voltage.  
(AB) 457 - 452 = 5 v  
(BC) 464 - 457 = 7 v  
(AC) 457 - 455 = 2 v  
Maximum deviation is 7 v.  
Determine percent voltage imbalance.  
NOTES:  
7
% Voltage Imbalance = 100 x  
457  
1. In compliance with NEC requirements for multimotor and combi-  
nation load equipment (refer to NEC Articles 430 and 440), the  
overcurrent protective device for the unit shall be fuse or HACR  
breaker. Canadian units may be fuse or circuit breaker.  
2. Unbalanced 3-Phase Supply Voltage  
= 1.53%  
This amount of phase imbalance is satisfactory as it is below the  
maximum allowable 2%.  
Never operate a motor where a phase imbalance in supply volt-  
age is greater than 2%. Use the following formula to determine  
the percent voltage imbalance.  
IMPORTANT: If the supply voltage phase imbalance is  
more than 2%, contact your local electric utility company  
immediately.  
% Voltage Imbalance  
max voltage deviation from average voltage  
= 100 x  
average voltage  
9
LEGEND  
C
Contactor  
COMPS  
IFC  
Compressors  
Indoor (Evaporator) Fan  
Contactor  
National Electrical Code  
Terminal Block  
NEC  
TB  
Terminal Block Connection  
Splice Connection  
(Factory Supplied)  
Field Wiring  
Factory Wiring  
Fig. 10 — Power Wiring Connections  
INTEGRATED  
GAS UNIT  
CONTROLLER  
(IGC)  
UNIT  
CONNECTION  
BOARD  
LEGEND  
AHA  
CC  
TC  
Adjustable Heat Anticipator  
Cooling Compensator  
Thermostat-Cooling  
Thermostat-Heating  
Field Wiring  
TH  
Factory Wiring  
Fig. 11 — Low-Voltage Connections  
RACEWAY  
Fig. 12 — Field Control Wiring Raceway  
10  
Step 8 — Adjust Factory-Installed Options  
APOLLO CONTROL — The optional Apollo control is used  
to actively monitor all modes of operation as well as indoor  
(evaporator) fan status, filter status, and indoor-air quality.  
The Apollo control is designed to work with Carrier TEMP  
and VVTsystems.  
OUTDOOR  
AIR OPENING  
PANEL  
The thermostat must be wired to the Apollo control before  
starting the unit. Refer to the Apollo control installation in-  
structions for information on installing the thermostat. See  
Fig. 13 for Apollo location.  
MANUAL OUTDOOR-AIR DAMPER — The outdoor-air  
hood and screen are attached to the basepan at the bottom of  
the unit for shipping.  
Assembly:  
1. Determine quantity of ventilation required for building.  
Record amount for use in Step 8.  
2. Remove filter access panel by raising panel and swing-  
ing panel outward. Panel is now disengaged from track  
and can be removed. No tools are required to remove  
the filter access panel. Remove outdoor-air opening panel.  
Save panels and screws. See Fig. 14.  
Fig. 14 — Damper Panel with Manual  
Outdoor-Air Damper Installed  
3. Separate hood and screen from basepan by removing the  
screws and brackets securing them. Save all screws and  
discard brackets.  
4. Replace outdoor air opening panel with screws saved  
from Step 2.  
5. Place hood on front of outdoor-air opening panel. See  
Fig. 15 for hood details. Secure top of hood with the  
6 screws removed in Step 3. See Fig. 16.  
6. Remove and save 8 screws (4 on each side) from sides  
of the manual outdoor-air damper.  
7. Align screw holes on hood with screw holes on side of  
manual outdoor-air damper. See Fig. 15 and 16. Secure  
hood with 8 screws from Step 6.  
8. Adjust minimum position setting of the damper blade  
by adjusting the manual outdoor-air adjustment screws  
on the front of the damper blade. See Fig. 14. Slide blade  
vertically until it is in the appropriate position deter-  
mined by Fig. 17. Tighten screws.  
WIRING TO  
APOLLO  
CONTROL  
WIRING  
THERMOSTAT CONTROL  
Fig. 15 — Outdoor-Air Hood Details  
HOOD  
NOT  
SHOWN)  
Fig. 13 — Apollo Control Factory-Installed  
in Typical Unit  
Fig. 16 — Damper with Hood Attached  
11  
b. Rotate the barometric relief damper hinge  
90 degrees. Barometric relief damper should open ver-  
tically to operate properly.  
c. Install horizontal discharge block-off plate over the  
opening on the access panel. (Block-off plate MUST  
be installed before installing hood assembly.) See  
Fig. 23.  
7. Insert economizer plug into economizer harness. Re-  
move tape from barometric relief damper. See Fig. 21.  
8. If ventilation air is not required, proceed to Step 9. If  
ventilation air is required, determine the minimum po-  
sition setting for required airflow. See Fig. 24. Adjust  
minimum position setting by adjusting the screws on the  
position setting bracket. See Fig. 25. Slide bracket until  
the top screw is in the position determined by  
Fig. 24. Tighten screws.  
9. Remove tape from outdoor-air thermostat (OAT). Fas-  
ten OAT to inside of hood using screws and speed clips  
provided. See Fig. 26. Make sure OAT terminals are po-  
sitioned up.  
Fig. 17 — Position Setting  
10. Replace outdoor-air opening panel using screws from  
Step 2. Replace filter access panel. Ensure the filter ac-  
cess panel slides along the tracks and is securely  
engaged.  
11. Fasten hood top and side plate assembly to outdoor-air  
opening panel with screws provided.  
9. Remove and save screws currently on sides of hood.  
Insert screens. Secure screens to hood using the screws.  
See Fig. 16.  
10. Replace filter access panel. Ensure filter access panel  
slides along the tracks and is securely engaged.  
12. Place knob supplied with economizer on OAT. See  
Fig. 26. Set for 3° F below indoor room thermostat set-  
ting. If accessory enthalpy control (EC) is used in place  
of OAT, see instructions shipped with EC for installa-  
tion and adjustment. See Fig. 26.  
OPTIONAL DURABLADE ECONOMIZER — The op-  
tional economizer hood assembly is packaged and shipped  
in the filter section. Damper blades and control boards are  
installed at the factory and the economizer is shipped in the  
vertical discharge position.  
NOTE: Horizontal discharge block-off plate is shipped with  
the air hood package. If unit is to be used for vertical dis-  
charge application, discard this plate.  
13. Connect OAT per Fig. 27.  
14. Slide outdoor-air inlet screens into screen track on hood  
side plate. While holding screens in place, fasten screen  
retainer to hood using screws provided.  
Assembly  
NOTE: Refer to Fig. 28 for Durablade economizer baromet-  
ric relief damper characteristics.  
1. Determine if ventilation air is required in building. If  
so, determine the minimum amount to be supplied by  
each unit and record quantity of ventilation air needed  
for use in Step 8.  
2. Remove filter access panel by raising panel and swing-  
ing panel outward. Panel is now disengaged from track  
and can be removed. No tools are required to remove  
filter access panel. Remove outdoor-air opening panel.  
Save panels and screws. See Fig. 18. Remove optional  
economizer and outdoor-air damper hood package from  
filter section.  
3. Assemble outdoor-air hood top and side plates as shown  
in Fig. 19. Install seal strips on hood top and sides. Put  
aside screen retainer and retainer screw for later assem-  
bly. Do not attach hood to unit at this time.  
4. On 012 and 014 units, install vertical discharge block-  
off plate over duct openings. See Fig. 20.  
5. Slide economizer into unit and secure with screws. See  
Fig. 21.  
NOTE: Be sure to engage rear economizer flange under  
tabs in vertical return-air opening.  
6. To convert to horizontal discharge application:  
a. Rotate the economizer 90 degrees until the econo-  
mizer motor faces the condenser section (see  
Fig. 22).  
OUTDOOR-AIR  
OPENING PANEL  
FILTER ACCESS  
PANEL  
Fig. 18 — Access Panel Locations  
12  
ECONOMIZER  
CONTROL BOARD  
ECONOMIZER  
PLUG  
ECONOMIZER  
MOTOR  
TOP  
SCREW  
Fig. 21 — Durablade Economizer Installed in Unit  
ECONOMIZER CONTROL BOARD  
ECONOMIZER MOTOR  
Fig. 19 — Outdoor-Air Hood Details  
POSITION SETTING BRACKET  
Fig. 22 — Horizontal Durablade Economizer  
Installation (90 Degree Rotation)  
Fig. 20 — Vertical Discharge Block-Off Plate  
(Sizes 120,150 only)  
BLOCK-OFF PLATE  
Fig. 23 — Horizontal Discharge Block-Off Plate  
13  
Example:  
Given —  
Negative Pressure . . . . . . . . . . . . . . . . . . . . . . . 0.1 in. wg  
Outdoor Airflow . . . . . . . . . . . . . . . . . . . . . . . . 1100 cfm  
Determine —  
Setting = 6Љ  
Fig. 24 — Durablade Economizer Damper  
Minimum Position Setting  
9
8
7
6
5
4
3
2
1
0
R
E
V
B
.
B
C
D
Fig. 25 — Durablade Economizer Minimum  
Position Damper Setting  
97-3672  
.
REV  
Fig. 26 — Outdoor-Air Thermostat/  
Enthalpy Control Installation  
Fig. 27 — Wiring Connections for  
Outdoor-Air Thermostat  
14  
dampers should be fully closed. Turn the potentiom-  
eter gradually counterclockwise until the desired po-  
sition is reached.  
c. Connect T and T1 to the 24 v power supply.  
d. After installation is complete, calculate the mini-  
mum airflow across the economizer. To calculate the  
minimum airflow, the following data is needed: total  
cfm (cfm3), temperature of the total cfm (T3), tem-  
perature of the return air (T1), and temperature of the  
entering outside air (T2). Cfm1 is the return air cfm,  
which will be the minimum airflow.  
Insert the data into the following equations:  
T1 (cfm1) + T2 (cfm2)  
= T3  
cfm3  
cfm2 = (cfm3 – cfm1)  
Therefore:  
T1 (cfm1) + T2 (cfm3 – cfm1)  
= T3  
cfm3  
Use this equation to determine cfm1, which is the mini-  
mum airflow across the economizer.  
(T3 – T2) cfm3  
cfm1 =  
Fig. 28 — Durablade Economizer Barometric Relief  
Damper Characteristics  
(T1 – T2)  
If cfm1 does not match the desired minimum airflow  
from Step 1, re-adjust the minimum position setting  
screw.  
OPTIONAL PARABLADE ECONOMIZER — The op-  
tional PARABLADE economizer hood assembly is pack-  
aged and shipped in the filter section. Damper blades and  
control boards are installed at the factory and the econo-  
mizer is shipped in the vertical discharge position.  
NOTE: Horizontal discharge block-off plate is shipped with  
the air hood package. The PARABLADE economizer can  
only be used for vertical discharge applications. Discard this  
plate.  
8. Determine the enthalpy changeover set point from  
Fig. 30. The enthalpy changeover set point should be  
set to return the outdoor air damper to the minimum po-  
sition when enthalpy rises above the set point. The set-  
tings are A, B, C, and D. Set the enthalpy changeover  
per the setting in Fig. 30.  
9. Replace outdoor-air opening panel using screws from  
Step 2. Replace filter access panel. Ensure the filter ac-  
cess panel slides along the tracks and is securely en-  
gaged. See Fig. 31.  
Assembly  
1. Determine if ventilation air is required in building. If  
so, determine the minimum amount to be supplied by  
each unit and record quantity of ventilation air needed  
for use in Step 7.  
10. Fasten hood top and side plate assembly (Fig. 32) to  
outdoor-air opening panel with screws provided.  
2. Remove filter access panel by raising panel and swing-  
ing panel outward. Panel is now disengaged from track  
and can be removed. No tools are required to remove  
filter access panel. Remove outdoor-air opening panel.  
See Fig. 18. Save panels and screws. Remove optional  
economizer so the outdoor-air damper hood package can  
be removed from the filter section.  
11. Slide outdoor-air inlet screens into screen track on hood  
side plate. While holding screens in place, fasten screen-  
retainer to hood using screws provided. See Fig. 33.  
ECONOMIZER CONTROL  
MODULE/DAMPER ACTUATOR  
3. Assemble outdoor-air hood top and side plates as shown  
in Fig. 19. Install seal strips on hood top and sides. Put  
aside screen retainer and retainer screw for later assem-  
bly. Do not attach hood to unit at this time.  
4. On 012 and 014 units, install vertical discharge block-  
off plate over duct openings. See Fig. 20.  
5. Slide economizer into unit and secure with screws. See  
Fig. 29.  
NOTE: Be sure to engage rear economizer flange under  
tabs in vertical return-air opening.  
6. Insert economizer plug into economizer harness. Re-  
move tape from barometric relief damper. See Fig. 29.  
7. If ventilation air is not required, proceed to Step 8. If  
ventilation air is required, perform the following:  
a. Make sure the factory-installed jumper is in place across  
terminals P and P1 on the economizer logic module.  
T and T1 should be disconnected during adjustment.  
b. The 2 potentiometers with slots for adjustment are  
located on the face of the economizer logic module.  
Turn the lower potentiometer fully clockwise. The  
WIRING  
ENTHALPY  
SENSOR  
BAROMETRIC  
HARNESS  
RELIEF DAMPER  
Fig. 29 — PARABLADE Economizer Installed in Unit  
15  
CONTROL POINT  
F (C) (APPROX)  
AT 50% RH  
CONTROL  
CURVE  
A
B
C
D
73 [23]  
70 [21]  
67 [19]  
63 [17]  
Fig. 33 — Filter Installed on Outdoor-Air Hood  
Step 9 — Adjust Evaporator-Fan Speed — Ad-  
just evaporator-fan speed to meet jobsite conditions.  
Table 3 shows fan rpm at motor pulley settings, Table 4  
shows motor efficiencies and Table 5 gives accessory static  
pressure drops. Table 6 shows motor performance. Refer to  
Tables 7-14 to determine fan speed settings. Fan motor pul-  
leys are factory set for speed shown in Table 1.  
To change fan speed:  
1. Shut off unit power supply.  
2. Loosen belt by loosening fan motor mounting plate nuts  
(see Fig. 34 and 35).  
RH  
Relative Humidity  
Fig. 30 — Enthalpy Settings for  
PARABLADE Economizer  
3. Loosen movable pulley flange setscrew (see Fig. 36).  
4. Screw movable flange toward fixed flange to increase speed  
and away from fixed flange to decrease speed. Increasing  
fan speed increases load on motor. Do not exceed maxi-  
mum speed specified in Table 1.  
5. Set movable flange at nearest keyway of pulley hub and  
tighten setscrew (see Table 1 for speed change for each  
full turn of pulley flange).  
To align fan and motor pulleys:  
1. Loosen fan pulley setscrews.  
2. Slide fan pulley along fan shaft.  
3. Make angular alignment by loosening motor from mount-  
ing plate.  
To adjust belt tension (see Fig. 34 and 35):  
1. Loosen fan motor mounting plate nuts.  
Fig. 31 — Panels Reinstalled on Unit  
2. Units 008,009 — Slide motor mounting plate away from  
fan scroll for proper belt tension (12-in. deflection with  
one finger) and tighten mounting nuts (see Fig. 34).  
Units 012,014 — Slide motor mounting plate downward  
to tighten belt tension. Secure motor mounting plate nuts.  
See Fig. 35.  
3. Adjust bolt and nut on mounting plate to secure motor in  
fixed position.  
Fig. 32 — Outdoor-Air Hood Installed on Unit  
16  
MOTOR MOUNTING  
PLATE NUTS  
Fig. 34 — Typical Belt-Drive Motor Mounting  
for Sizes 008,009  
Fig. 36 — Evaporator-Fan Pulley Adjustment  
Fig. 35 — Typical Belt-Drive Motor Mounting  
for Sizes 012,014  
Table 3 — Fan Rpm at Motor Pulley Settings*  
MOTOR PULLEY TURNS OPEN  
UNIT  
48TJ  
1
0
2
1
112  
765  
2
212  
715  
810  
810  
810  
960  
970  
1100  
3
312  
665  
760  
760  
760  
910  
925  
1045  
4
412  
615  
710  
710  
710  
860  
880  
990  
5
512  
6
900  
008†  
008**  
009†  
012†  
012††  
014†  
014††  
840  
815  
910  
790  
885  
885  
885  
1035  
1035  
1185  
740  
835  
835  
835  
985  
990  
1130  
690  
785  
785  
785  
935  
950  
1075  
640  
735  
735  
735  
885  
905  
1015  
590  
685  
685  
685  
835  
860  
960  
935  
860  
935  
910  
860  
935  
910  
860  
1085  
1080  
1260  
1060  
1060  
1220  
1010  
1015  
1155  
930  
*Approximate rpm shown.  
†Indicates standard motor and drive.  
**Indicates alternate drive.  
††Indicates alternate motor and drive.  
17  
Table 4 — Evaporator-Fan Motor Efficiency  
MOTOR  
EFFICIENCY (%)  
48TJD/TJE/TJF008,009  
48TJD/TJE/TJF012 (Std)  
48TJD/TJE/TJF012 (Alt)  
48TJD/TJE014 (Std)  
80  
80  
83  
85  
87  
48TJD/TJE014 (Alt)  
NOTE: Convert watts to bhp using the following formula:  
watts input x motor efficiency  
bhp =  
746  
Table 5 — Economizer Static Pressure Drop (in. wg)  
CFM  
UNIT  
48TJ  
2200  
.02  
2500  
.02  
3000  
.03  
3500  
.04  
4000  
.05  
4500  
.06  
5000  
.07  
5500  
.08  
6000  
.09  
Durablade Economizer  
PARABLADE Economizer  
.21  
.25  
.35  
.49  
.61  
Table 6 — Motor Data  
MAXIMUM  
CONTINUOUS  
BHP*  
MAXIMUM  
OPERATING  
WATTS*  
UNIT  
48TJ  
EVAPORATOR-  
FAN MOTOR  
UNIT  
VOLTAGE  
MAXIMUM  
AMP DRAW  
208/230  
460  
6.1  
2.7  
2.7  
6.1  
2.7  
2.7  
6.1  
2.7  
2.7  
7.9  
3.6  
3.6  
11.1  
5.0  
5.0  
15.0  
7.4  
7.4  
008  
009  
Std  
Std  
Std  
Alt  
2.40  
2.40  
2.40  
2.90  
4.20  
5.25  
2120  
2120  
2120  
2615  
3775  
4400  
575  
208/230  
460  
575  
208/230  
460  
575  
012  
014  
208/230  
460  
575  
208/230  
460  
Std  
Alt  
575  
208/230  
460  
575  
LEGEND  
Brake Horsepower  
Bhp  
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the  
motors can be utilized with confidence. Using your fan motors up to the ratings shown in this table will not result  
in nuisance tripping or premature motor failure. Unit warranty will not be affected.  
18  
Table 7 — Fan Performance, 48TJ008 — Vertical Discharge Units  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
(Cfm)  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
2200  
2250  
2300  
2400  
2500  
2550  
2600  
2700  
2800  
2900  
3000  
3100  
3200  
3300  
3400  
3500  
3600  
3700  
3750  
506  
514  
521  
536  
551  
559  
567  
582  
598  
614  
630  
646  
662  
679  
695  
712  
729  
745  
754  
0.52  
0.55  
0.57  
0.63  
0.69  
0.72  
0.75  
0.83  
0.90  
0.98  
1.07  
1.16  
1.26  
1.36  
1.47  
1.59  
1.71  
1.84  
1.91  
586  
593  
600  
613  
626  
634  
641  
655  
670  
684  
699  
714  
729  
744  
759  
774  
790  
805  
813  
0.72  
0.76  
0.79  
0.85  
0.93  
0.97  
1.00  
1.08  
1.17  
1.25  
1.35  
1.45  
1.55  
1.66  
1.78  
1.90  
2.03  
2.17  
2.24  
656  
662  
668  
680  
693  
700  
706  
719  
732  
745  
759  
773  
787  
801  
816  
830  
845  
860  
868  
0.95  
0.99  
1.02  
1.09  
1.17  
1.21  
1.25  
1.34  
1.43  
1.53  
1.63  
1.74  
1.86  
1.98  
2.10  
2.23  
2.37  
2.52  
2.59  
718  
724  
730  
741  
753  
759  
764  
776  
789  
802  
815  
828  
841  
854  
867  
881  
895  
909  
917  
1.18  
1.22  
1.26  
1.34  
1.43  
1.48  
1.52  
1.61  
1.71  
1.81  
1.92  
2.04  
2.16  
2.29  
2.42  
2.56  
2.71  
2.87  
2.95  
776  
781  
786  
796  
808  
814  
819  
831  
842  
854  
866  
878  
891  
904  
917  
930  
943  
956  
963  
1.43  
1.78  
1.50  
1.59  
1.69  
1.74  
1.79  
1.89  
2.00  
2.11  
2.23  
2.35  
2.48  
2.61  
2.75  
2.90  
3.05  
3.22  
3.30  
838  
841  
843  
849  
859  
864  
869  
880  
892  
903  
915  
926  
938  
950  
963  
976  
988  
1.78  
1.81  
1.83  
1.88  
1.96  
2.01  
2.06  
2.17  
2.29  
2.42  
2.54  
2.67  
2.81  
2.95  
3.10  
3.25  
3.41  
898  
902  
905  
910  
912  
915  
918  
927  
938  
949  
961  
972  
983  
995  
1007  
2.21  
2.25  
2.28  
2.31  
2.31  
2.34  
2.37  
2.47  
2.58  
2.71  
2.85  
3.00  
3.14  
3.30  
3.45  
935  
939  
943  
952  
963  
968  
973  
976  
983  
993  
1003  
1015  
1026  
2.58  
2.60  
2.62  
2.74  
2.81  
2.81  
2.81  
2.84  
2.92  
3.03  
3.17  
3.32  
3.47  
LEGEND  
Brake Horsepower Input to Fan  
5. Values include losses for filters, unit casing, and wet coils.  
6. Maximum continuous bhp is 2.4. Extensive motor and electrical  
testing on these units ensures that the full range of the motor can  
be utilized with confidence. Using your fan motors up to the rat-  
ings shown will not result in nuisance tripping or premature motor  
failure. Unit warranty will not be affected.  
Bhp  
NOTES:  
1. Boldface indicates field-supplied drive required. (See Note 4.)  
2.  
3.  
indicates alternate drive required.  
7. Use of a field-supplied motor may affect wire sizing. Contact your  
Carrier representative to verify.  
indicates field-supplied motor and drive required.  
8. Interpolation is permissible. Do not extrapolate.  
4. Standard drive range is 590 to 840 rpm. Alternate drive range is  
685 to 935 rpm. All other rpms require a field-supplied drive.  
Table 8 — Fan Performance, 48TJ009 — Vertical Discharge Units  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
(Cfm)  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
2550  
2600  
2700  
2800  
2900  
3000  
3100  
3200  
3300  
3400  
3500  
3600  
3700  
3750  
3800  
3900  
4000  
4100  
4200  
4250  
4300  
559  
567  
582  
598  
614  
630  
646  
662  
679  
695  
712  
729  
745  
754  
762  
779  
796  
813  
830  
839  
847  
0.72  
0.75  
0.83  
0.90  
0.98  
1.07  
1.16  
1.26  
1.36  
1.47  
1.59  
1.71  
1.84  
1.91  
1.98  
2.12  
2.27  
2.42  
2.59  
2.68  
2.76  
634  
641  
655  
670  
684  
690  
714  
729  
744  
759  
774  
790  
805  
813  
821  
836  
852  
868  
884  
890  
900  
0.97  
1.00  
1.08  
1.17  
1.25  
1.35  
1.45  
1.55  
1.66  
1.78  
1.90  
2.03  
2.17  
2.24  
2.31  
2.46  
2.61  
2.78  
2.95  
3.04  
3.13  
700  
706  
719  
732  
745  
759  
773  
787  
801  
816  
830  
845  
860  
868  
875  
890  
905  
920  
935  
1.21  
1.25  
1.34  
1.43  
1.53  
1.63  
1.74  
1.86  
1.98  
2.10  
2.23  
2.37  
2.52  
2.59  
2.66  
2.82  
2.98  
3.15  
3.33  
759  
764  
776  
789  
802  
815  
828  
841  
854  
867  
881  
895  
909  
917  
924  
938  
953  
1.48  
1.52  
1.61  
1.71  
1.81  
1.92  
2.04  
2.16  
2.29  
2.42  
2.56  
2.71  
2.87  
2.95  
3.03  
3.19  
3.37  
814  
819  
831  
842  
854  
866  
878  
891  
904  
917  
930  
943  
956  
963  
970  
1.74  
1.79  
1.89  
2.00  
2.11  
2.23  
2.35  
2.48  
2.61  
2.75  
2.90  
3.05  
3.22  
3.30  
3.38  
864  
869  
880  
892  
903  
915  
926  
938  
950  
963  
976  
988  
2.01  
2.06  
2.17  
2.29  
2.42  
2.54  
2.67  
2.81  
2.95  
3.10  
3.25  
3.41  
915  
918  
927  
938  
949  
961  
972  
983  
995  
1007  
2.34  
2.37  
2.47  
2.58  
2.71  
2.85  
3.00  
3.14  
3.30  
3.45  
968  
973  
976  
983  
993  
1003  
1016  
1026  
2.81  
2.81  
2.84  
2.92  
3.03  
3.17  
3.32  
3.47  
LEGEND  
Brake Horsepower Input to Fan  
5. Maximum continuous bhp is 2.4. Extensive motor and electrical  
testing on these units ensures that the full range of the motor can  
be utilized with confidence. Using your fan motors up to the rat-  
ings shown will not result in nuisance tripping or premature motor  
failure. Unit warranty will not be affected.  
Bhp  
NOTES:  
1. Boldface indicates field-supplied drive required. (See Note 3.)  
6. Use of a field-supplied motor may affect wire sizing. Contact your  
Carrier representative to verify.  
2. indicates field-supplied motor and drive required.  
3. Standard drive range is 685 to 935 rpm. All other rpms require a  
7. Interpolation is permissible. Do not extrapolate.  
field-supplied drive.  
4. Values include losses for filters, unit casing, and wet coils.  
19  
Table 9 — Fan Performance, 48TJ012 — Vertical Discharge Units  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
(Cfm)  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
1.8  
2.0  
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp  
3000  
3100  
3200  
3300  
3400  
3500  
3600  
3700  
3800  
3900  
4000  
4100  
4200  
4300  
4400  
4500  
4600  
4700  
4800  
4900  
5000  
592 0.76 661 0.93 722 1.09 779 1.26 829 1.42 880 1.58 924 1.73 970 1.89 1019 2.00 1066 2.30  
607 0.83 676 1.01 734 1.17 791 1.34 840 1.51 890 1.68 935 1.84 977 2.00 1026 2.17 1070 2.44  
622 0.90 690 1.09 746 1.25 803 1.43 852 1.60 900 1.77 946 1.95 987 2.11 1029 2.28 1075 2.51  
638 0.98 705 1.17 759 1.33 815 1.52 864 1.70 910 1.88 957 2.06 998 2.23 1037 2.40 1082 2.58  
653 1.06 719 1.26 772 1.43 826 1.62 876 1.81 921 1.98 967 2.17 1009 2.35 1047 2.53 1087 2.70  
669 1.15 733 1.35 786 1.53 838 1.72 888 1.91 933 2.10 976 2.29 1020 2.48 1058 2.66 1095 2.84  
684 1.24 747 1.44 800 1.64 850 1.82 900 2.03 945 2.22 986 2.41 1030 2.61 1069 2.80 1106 2.98  
700 1.33 760 1.54 814 1.75 863 1.92 912 2.14 957 2.34 998 2.54 1039 2.74 1081 2.94 1117 3.13  
715 1.43 774 1.64 828 1.86 875 2.04 924 2.26 969 2.47 1010 2.67 1049 2.87 1091 3.08 1128 3.29  
731 1.54 787 1.74 843 1.98 888 2.16 936 2.38 981 2.60 1022 2.81 1060 3.02 1100 3.23  
747 1.64 801 1.85 857 2.10 902 2.30 948 2.51 993 2.74 1034 2.96 1072 3.17 1110 3.38  
763 1.76 816 1.97 872 2.23 916 2.44 960 2.64 1005 2.88 1046 3.11 1084 3.32  
778 1.88 831 2.10 886 2.36 929 2.58 972 2.78 1016 3.03 1058 3.26  
794 2.00 846 2.23 900 2.50 943 2.73 985 2.93 1028 3.17  
810 2.13 861 2.37 913 2.64 958 2.89 999 3.09 1040 3.32  
826 2.27 876 2.52 927 2.78 973 3.04 1012 3.26  
842 2.41 892 2.67 940 2.92 987 3.21  
858 2.55 907 2.83 954 3.08 1002 3.38  
874 2.70 922 2.99 968 3.24  
890 2.86 938 3.16  
906 3.03 953 3.33  
LEGEND  
5. Values include losses for filters, unit casing, and wet coils.  
6. Maximum continuous bhp is 2.4 for the standard motor and 2.9 for  
the alternate motor. Extensive motor and electrical testing on these  
units ensures that the full range of the motor can be utilized with  
confidence. Using your fan motors up to the ratings shown will not  
result in nuisance tripping or premature motor failure. Unit war-  
ranty will not be affected.  
Bhp  
NOTES:  
1. Boldface indicates field-supplied drive required. (See Note 4.)  
Brake Horsepower Input to Fan  
2.  
3.  
indicates alternate motor and/or drive required.  
indicates field-supplied motor and drive required.  
7. Use of a field-supplied motor may affect wire sizing. Contact your  
Carrier representative to verify.  
4. Standard drive range is 685 to 935 rpm. Alternate drive range is  
835 to 1085 rpm. All other rpms require a field-supplied drive.  
8. Interpolation is permissible. Do not extrapolate.  
Table 10 — Fan Performance, 48TJ014 — Vertical Discharge Units  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
(Cfm)  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
1.8  
2.0  
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp  
3700  
3800  
3900  
4000  
4100  
4200  
4300  
4400  
4500  
4600  
4700  
4800  
4900  
5000  
5100  
5200  
5300  
5400  
5500  
5600  
5700  
5800  
5900  
6000  
6100  
6200  
729 1.36 790 1.58 847 1.79 902 2.06 955 2.29 1008 2.55 1060 2.80 1108 3.05 1152 3.27 1190 3.46  
745 1.46 805 1.69 861 1.89 915 2.17 967 2.41 1019 2.67 1070 2.94 1118 3.19 1163 3.44 1203 3.65  
761 1.56 820 1.80 875 2.01 928 2.29 979 2.55 1029 2.80 1079 3.07 1128 3.34 1173 3.60 1214 3.83  
777 1.67 836 1.92 889 2.14 941 2.40 991 2.68 1040 2.94 1089 3.22 1137 3.49 1183 3.76 1225 4.00  
793 1.79 851 2.05 904 2.27 955 2.52 1004 2.82 1052 3.08 1100 3.36 1147 3.65 1193 3,93 1236 4.19  
810 1.91 867 2.18 918 2.41 968 2.65 1017 2.96 1064 3.23 1110 3.51 1157 3.81 1202 4.09 1245 4.38  
826 2.04 883 2.32 933 2.55 982 2.79 1030 3.11 1076 3.40 1121 3.67 1167 3.97 1212 4.27 1255 4.56  
842 2.17 898 2.46 948 2.70 996 2.93 1043 3.25 1088 3.56 1133 3.84 1178 4.14 1222 4.44 1265 4.74  
859 2.31 914 2.60 962 2.85 1010 3.09 1056 3.40 1101 3.73 1144 4.00 1188 4.31 1232 4.62 1274 4.93  
876 2.45 930 2.76 977 3.01 1024 3.26 1070 3.55 1114 3.90 1157 4.19 1199 4.49 1242 4.81 1284 5.13  
892 2.60 945 2.91 992 3.18 1039 3.43 1083 3.71 1126 4.07 1169 4.38 1210 4.68 1252 5.00 1294 5.33  
909 2.77 961 3.07 1008 3.36 1053 3.61 1097 3.88 1140 4.25 1181 4.58 1222 4.87 1263 5.20  
926 2.93 977 3.24 1024 3.54 1068 3.80 1111 4.06 1153 4.41 1194 4.77 1234 5.09 1274 5.40  
942 3.11 993 3.41 1039 3.73 1080 3.99 1125 4.25 1166 4.59 1207 4.97 1247 5.30 1286 5.62  
959 3.29 1009 3.60 1055 3.92 1097 4.19 1139 4.46 1180 4.78 1220 5.18 1259 5.52  
976 3.47 1025 3.78 1071 4.12 1112 4.40 1153 4.67 1194 4.98 1233 5.38 1272 5.74  
993 3.67 1041 3.98 1086 4.33 1127 4.61 1168 4.90 1208 5.19 1246 5.58  
1010 3.87 1057 4.18 1102 4.54 1142 4.84 1182 5.13 1221 5.41  
1027 4.07 1073 4.39 1118 4.76 1157 5.07 1197 5.36 1235 5.64  
1043 4.29 1090 4.61 1133 4.99 1173 5.31 1211 5.61  
1060 4.51 1106 4.83 1149 5.22 1189 5.55  
1077 4.74 1122 5.07 1165 5.45  
1094 4.98 1139 5.31 1181 5.70  
1111 5.22 1155 5.55  
1128 5.48  
1145 5.74  
LEGEND  
5. Values include losses for filters, unit casing, and wet coils.  
6. Maximum continuous bhp is 4.2 for the standard motor and 5.25  
for the alternate motor. Extensive motor and electrical testing on  
these units ensures that the full range of the motor can be utilized  
with confidence. Using your fan motors up to the ratings shown  
will not result in nuisance tripping or premature motor failure. Unit  
warranty will not be affected.  
Bhp  
NOTES:  
1. Boldface indicates field-supplied drive required. (See Note 4.)  
Brake Horsepower Input to Fan  
2.  
3.  
indicates alternate motor and/or drive required.  
7. Use of a field-supplied motor may affect wire sizing. Contact your  
Carrier representative to verify.  
indicates field-supplied motor and drive required.  
4. Standard drive range is 860 to 1080 rpm. Alternate drive range is  
900 to 1260 rpm. All other rpms require a field-supplied drive.  
8. Interpolation is permissible. Do not extrapolate.  
20  
Table 11 — Fan Performance, 48TJ008 — Horizontal Discharge Units  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
(Cfm)  
0.2  
0.4  
0.6  
0.8  
0.9  
1.0  
1.2  
1.4  
1.6  
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp  
2200  
2250  
2300  
2400  
2500  
2550  
2600  
2700  
2800  
2900  
3000  
3100  
3200  
3300  
3400  
3500  
3600  
3700  
3750  
499 0.50 580 0.70 652 0.94 717 1.17  
507 0.53 586 0.73 658 0.97 722 1.22  
513 0.55 592 0.76 663 1.00 727 1.26  
528 0.60 606 0.83 674 1.06 738 1.34  
542 0.66 619 0.90 686 1.13 748 1.41  
550 0.69 627 0.94 692 1.17 754 1.45  
557 0.72 634 0.97 698 1.21 759 1.49  
573 0.79 648 1.05 711 1.29 770 1.58  
588 0.86 662 1.13 723 1.38 782 1.66  
604 0.94 676 1.21 737 1.48 794 1.76  
620 1.02 690 1.30 750 1.58 806 1.86  
636 1.11 704 1.39 764 1.69 818 1.97  
652 1.21 718 1.49 778 1.80 831 2.09  
668 1.31 732 1.59 793 1.92 844 2.21  
684 1.41 747 1.70 807 2.04 857 2.35  
701 1.53 762 1.82 821 2.16 871 2.48  
717 1.65 777 1.94 835 2.29 885 2.63  
733 1.77 792 2.07 849 2.42 899 2.78  
742 1.84 800 2.14 856 2.49 907 2.86  
748 1.30  
752 1.34  
756 1.38  
766 1.46  
777 1.55  
783 1.60  
787 1.64  
798 1.73  
809 1.82  
821 1.92  
832 2.02  
844 2.13  
856 2.25  
869 2.37  
882 2.51  
895 2.64  
908 2.79  
922 2.95  
929 3.03  
779 1.43  
783 1.46  
786 1.49  
795 1.58  
806 1.68  
812 1.74  
816 1.79  
827 1.88  
837 1.98  
848 2.08  
849 2.18  
870 2.29  
882 2.40  
894 2.53  
907 2.66  
919 2.80  
932 2.95  
945 3.11  
952 3.20  
839 1.78  
843 1.81  
846 1.84  
853 1.88  
859 1.94  
864 1.99  
868 2.04  
878 2.16  
889 2.29  
900 2.41  
910 2.52  
920 2.64  
931 2.76  
942 2.89  
905 2.21  
908 2.25  
910 2.25  
912 2.31  
919 2.37  
920 2.39  
921 2.41  
928 2.45  
937 2.57  
947 2.70  
958 2.85 1002 3.15  
968 2.99 1012 3.30  
979 3.13 1023 3.47  
989 3.26 1034 3.63  
951 2.57  
955 2.59  
959 2.61  
967 2.68  
971 2.73  
974 2.76  
976 2.78  
983 2.88  
986 2.91  
993 3.01  
954 3.02 1000 3.40 1044 3.79  
966 3.15 1011 3.55 1054 3.94  
978 3.30 1022 3.69 1065 4.10  
990 3.45 1034 3.84 1076 4.26  
997 3.54 1040 3.93 1082 5.27  
LEGEND  
5. Values include losses for filters, unit casing, and wet coils.  
6. Maximum continuous bhp is 2.4. Extensive motor and electrical  
testing on these units ensures that the full range of the motor can  
be utilized with confidence. Using your fan motors up to the rat-  
ings shown will not result in nuisance tripping or premature motor  
failure. Unit warranty will not be affected.  
Bhp  
NOTES:  
1. Boldface indicates field-supplied drive required. (See Note 4.)  
Brake Horsepower Input to Fan  
2.  
3.  
indicates alternate drive required.  
7. Use of a field-supplied motor may affect wire sizing. Contact your  
Carrier representative to verify.  
indicates field-supplied motor and drive required.  
4. Standard drive range is 590 to 840 rpm. Alternate drive range is  
685 to 935 rpm. All other rpms require a field-supplied drive.  
8. Interpolation is permissible. Do not extrapolate.  
Table 12 — Fan Performance, 48TJ009 — Horizontal Discharge Units  
EXTERNAL STATIC PRESSURE (in. wg)  
0.8 0.9 1.0  
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp  
AIRFLOW  
(Cfm)  
0.2  
0.4  
0.6  
1.2  
1.4  
1.6  
2550  
2600  
2700  
2800  
2900  
3000  
3100  
3200  
3300  
3400  
3500  
3600  
3700  
3750  
3800  
3900  
4000  
4100  
4200  
4250  
4300  
550 0.69 627 0.94 692 1.17 754 1.45  
557 0.72 634 0.97 698 1.21 759 1.49  
573 0.79 648 1.05 711 1.29 770 1.58  
588 0.86 662 1.13 723 1.38 782 1.66  
604 0.94 676 1.21 737 1.48 794 1.76  
620 1.02 690 1.30 750 1.58 806 1.86  
636 1.11 704 1.39 764 1.69 818 1.97  
652 1.21 718 1.49 778 1.80 831 2.09  
668 1.31 732 1.59 793 1.92 844 2.21  
684 1.41 747 1.70 807 2.04 857 2.35  
701 1.53 762 1.82 821 2.16 871 2.48  
717 1.65 777 1.94 835 2.29 885 2.63  
733 1.77 792 2.07 849 2.42 899 2.78  
742 1.84 800 2.14 856 2.49 907 2.86  
750 1.90 807 2.21 863 2.56 914 2.93  
767 2.04 822 2.35 877 2.71 928 3.09  
783 2.18 838 2.50 891 2.86 942 3.26  
800 2.34 854 2.66 905 3.02 956 2.43  
817 2.49 869 2.82 920 3.19 970 3.60  
826 2.58 877 2.91 928 3.28 977 3.69  
783 1.60  
787 1.64  
798 1.73  
809 1.82  
821 1.92  
832 2.02  
844 2.13  
856 2.25  
869 2.37  
882 2.51  
895 2.64  
908 2.79  
922 2.95  
929 3.03  
936 3.11  
950 3.27  
964 3.45  
812 1.74  
816 1.79  
827 1.88  
837 1.98  
848 2.08  
849 2.18  
870 2.29  
882 2.40  
894 2.53  
907 2.66  
919 2.80  
932 2.95  
945 3.11  
952 3.20  
864 1.99  
868 2.04  
878 2.16  
889 2.29  
900 2.41  
910 2.52  
920 2.64  
931 2.76  
942 2.89  
954 3.02 1000 3.40 1044 3.79  
966 3.15 1011 3.55 1054 3.94  
978 3.30 1022 3.69 1065 4.10  
990 3.45 1034 3.84 1076 4.26  
997 3.54 1040 3.93 1082 5.27  
920 2.39  
921 2.41  
928 2.45  
937 2.57  
947 2.70  
958 2.85 1002 3.15  
968 2.99 1012 3.30  
979 3.13 1023 3.47  
989 3.26 1034 3.63  
974 2.76  
976 2.78  
983 2.88  
986 2.91  
993 3.01  
958 3.28 1003 3.62 1045 4.01 1087 4.43  
972 3.45 1015 3.80 1057 4.18 1098 4.60  
986 3.63 1028 3.99 1070 4.36 1110 4.78  
978 3.62 1000 3.81 1042 4.18 1082 4.56 1122 4.97  
992 3.80 1015 4.00 1055 4.38 1095 4.76 1134 5.16  
999 3.90 1022 4.10 1062 4.49 1102 4.87 1140 5.27  
834 2.66 885 3.00 935 3.37 984 3.78 1006 3.99 1029 4.20 1069 4.59 1108 4.98 1147 5.38  
LEGEND  
Brake Horsepower Input to Fan  
5. Maximum continuous bhp is 2.4. Extensive motor and electrical  
testing on these units ensures that the full range of the motor can  
be utilized with confidence. Using your fan motors up to the rat-  
ings shown will not result in nuisance tripping or premature motor  
failure. Unit warranty will not be affected.  
Bhp  
NOTES:  
1. Boldface indicates field-supplied drive required. (See Note 3.)  
2. indicates field-supplied motor and drive required.  
6. Use of a field-supplied motor may affect wire sizing. Contact your  
Carrier representative to verify.  
3. Standard drive range is 685 to 935 rpm. All other rpms require a  
field-supplied drive.  
4. Values include losses for filters, unit casing, and wet coils.  
7. Interpolation is permissible. Do not extrapolate.  
21  
Table 13 — Fan Performance, 48TJ012 — Horizontal Discharge Units  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
(Cfm)  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
1.8  
2.0  
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp  
3000  
3100  
3200  
3300  
3400  
3500  
3600  
3700  
3800  
3900  
4000  
4100  
4200  
4300  
4400  
4500  
4600  
4700  
4800  
4900  
5000  
552 0.68 632 0.87 701 1.05 761 1.22 816 1.36 871 1.54 918 1.67 967 1.89 1010 2.09 1063 2.46  
565 0.74 644 0.93 711 1.12 772 1.31 825 1.45 879 1.63 928 1.78 973 1.94 1018 2.17 1070 2.51  
578 0.81 656 1.00 723 1.20 782 1.39 835 1.55 887 1.71 937 1.90 981 2.04 1026 2.26 1075 2.57  
591 0.88 668 1.08 734 1.28 793 1.47 845 1.65 895 1.80 946 2.00 991 2.16 1032 2.32 1080 2.64  
605 0.96 680 1.16 745 1.36 803 1.56 856 1.75 904 1.91 953 2.10 1000 2.29 1041 2.44 1083 2.65  
619 1.04 691 1.23 755 1.44 813 1.65 867 1.86 914 2.03 961 2.20 1009 2.41 1051 2.57 1090 2.74  
633 1.13 703 1.31 766 1.52 824 1.74 877 1.97 924 2.15 970 2.32 1017 2.53 1061 2.72 1099 2.88  
648 1.23 714 1.39 777 1.61 835 1.85 887 2.07 935 2.28 980 2.45 1024 2.64 1069 2.87 1109 3.03  
662 1.33 726 1.51 789 1.72 846 1.95 897 2.18 946 2.40 989 2.58 1033 2.76 1077 2.99 1118 3.20  
677 1.44 738 1.61 801 1.82 857 2.06 908 2.29 956 2.53 1000 2.73 1042 2.91 1085 3.12 1127 3.36  
692 1.55 750 1.73 813 1.94 868 2.17 918 2.40 967 2.66 1010 2.87 1052 3.06 1093 3.24  
707 1.67 762 1.84 825 2.05 878 2.28 929 2.53 977 2.78 1021 3.02 1062 3.22 1102 3.41  
722 1.80 775 1.97 837 2.16 889 2.40 941 2.66 987 2.91 1032 3.17 1072 3.38  
737 1.94 787 2.09 848 2.27 900 2.52 952 2.80 999 3.04 1042 3.32  
752 2.08 800 2.21 860 2.39 912 2.66 962 2.93 1008 3.19  
768 2.24 814 2.35 871 2.51 924 2.80 973 3.07 1019 3.34  
783 2.40 827 2.50 883 2.64 937 2.95 983 3.21  
799 2.56 841 2.64 894 2.77 949 3.10 994 3.36  
814 2.74 855 2.80 906 2.91 961 3.26  
868 2.90 918 3.05 972 3.40  
883 3.10 931 3.21  
LEGEND  
Brake Horsepower Input to Fan  
5. Values include losses for filters, unit casing, and wet coils.  
6. Maximum continuous bhp is 2.4 for the standard motor and 2.9 for  
the alternate motor. Extensive motor and electrical testing on these  
units ensures that the full range of the motor can be utilized with  
confidence. Using your fan motors up to the ratings shown will not  
result in nuisance tripping or premature motor failure. Unit war-  
ranty will not be affected.  
Bhp  
NOTES:  
1. Boldface indicates field-supplied drive required. (See Note 4.)  
2.  
3.  
indicates alternate motor and/or drive required.  
7. Use of a field-supplied motor may affect wire sizing. Contact your  
Carrier representative to verify.  
8. Interpolation is permissible. Do not extrapolate.  
indicates field-supplied motor and drive required.  
4. Standard drive range is 685 to 935 rpm. Alternate drive range is  
835 to 1085 rpm. All other rpms require a field-supplied drive.  
Table 14 — Fan Performance, 48TJ014 — Horizontal Discharge Units  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
(Cfm)  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
1.8  
2.0  
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp  
3700  
3800  
3900  
4000  
4100  
4200  
4300  
4400  
4500  
4600  
4700  
4800  
4900  
5000  
5100  
5200  
5300  
5400  
5500  
5600  
5700  
5800  
5900  
6000  
6100  
6200  
677 1.20 748 1.43 810 1.65 869 1.89 928 2.17 984 2.43 1036 2.68 1080 2.90 1114 3.07 1135 3.17  
691 1.28 761 1.52 822 1.75 880 1.98 937 2.28 993 2.55 1046 2.81 1092 3.05 1129 3.25 1156 3.39  
705 1.37 773 1.62 834 1.86 891 2.08 947 2.39 1002 2.66 1055 2.94 1102 3.20 1143 3.42 1174 3.59  
720 1.47 786 1.71 847 1.97 902 2.19 957 2.50 1011 2.79 1064 3.07 1112 3.34 1155 3.59 1190 3.80  
734 1.56 800 1.82 860 2.09 914 2.31 967 2.60 1021 2.91 1072 3.20 1121 3.49 1165 3.76 1203 3.99  
749 1.66 813 1.92 873 2.21 926 2.44 978 2.71 1030 3.04 1081 3.34 1130 3.64 1175 3.92 1215 4.18  
764 1.77 826 2.04 886 2.33 938 2.57 989 2.83 1040 3.18 1090 3.48 1139 3.79 1185 4.08 1226 4.36  
779 1.88 840 2.16 899 2.46 951 2.71 1000 2.96 1050 3.31 1100 3.63 1148 3.94 1194 4.25 1236 4.54  
793 1.99 854 2.28 912 2.59 963 2.86 1012 3.09 1061 3.43 1109 3.78 1157 4.09 1203 4.42 1246 4.72  
808 2.11 868 2.42 925 2.73 975 3.00 1024 3.25 1071 3.56 1119 3.93 1166 4.26 1212 4.58 1255 4.91  
822 2.24 882 2.56 937 2.86 988 3.16 1036 3.42 1082 3.70 1129 4.09 1175 4.43 1221 4.76 1264 5.09  
837 2.37 896 2.71 950 3.00 1001 3.32 1048 3.59 1093 3.86 1139 4.24 1185 4.60 1230 4.93 1273 5.28  
852 2.51 910 2.86 963 3.15 1014 3.48 1060 3.76 1105 4.02 1150 4.38 1194 4.77 1239 5.12 1282 5.47  
867 2.65 924 3.01 977 3.30 1027 3.65 1073 3.94 1117 4.20 1161 4.54 1204 4.95 1248 5.31 1291 5.66  
882 2.79 938 3.17 990 3.46 1040 3.82 1085 4.12 1129 4.40 1172 4.71 1214 5.13 1257 5.51  
896 2.95 952 3.33 1003 3.63 1053 4.00 1098 4.30 1141 4.60 1183 4.91 1225 5.29 1267 5.70  
911 3.11 967 3.50 1017 3.80 1066 4.18 1111 4.50 1153 4.80 1194 5.08 1236 5.47  
926 3.27 981 3.68 1030 3.98 1079 4.35 1124 4.70 1166 5.01 1206 5.29 1247 5.65  
940 3.44 995 3.86 1044 4.17 1092 4.54 1137 4.91 1178 5.22 1218 5.52  
955 3.62 1010 4.04 1058 4.38 1105 4.73 1150 5.12 1190 5.44 1230 5.75  
970 3.80 1024 4.23 1072 4.59 1118 4.93 1163 5.34 1203 5.67  
985 3.99 1039 4.42 1086 4.80 1131 5.14 1176 5.56  
1000 4.18 1053 4.62 1100 5.02 1144 5.36  
1015 4.39 1068 4.83 1114 5.25 1158 5.58  
1030 4.59 1083 5.04 1128 5.48  
1046 4.81 1097 5.26 1142 5.71  
LEGEND  
5. Values include losses for filters, unit casing, and wet coils.  
6. Maximum continuous bhp is 4.2 for the standard motor and 5.25  
for the alternate motor. Extensive motor and electrical testing on  
these units ensures that the full range of the motor can be utilized  
with confidence. Using your fan motors up to the ratings shown  
will not result in nuisance tripping or premature motor failure. Unit  
warranty will not be affected.  
Bhp  
NOTES:  
1. Boldface indicates field-supplied drive required. (See Note 4.)  
Brake Horsepower Input to Fan  
2.  
3.  
indicates alternate motor and/or drive required.  
7. Use of a field-supplied motor may affect wire sizing. Contact your  
Carrier representative to verify.  
indicates field-supplied motor and drive required.  
4. Standard drive range is 860 to 1080 rpm. Alternate drive range is  
900 to 1260 rpm. All other rpms require a field-supplied drive.  
8. Interpolation is permissible. Do not extrapolate.  
22  
START-UP  
Main Burners — Main burners are factory set and should  
require no adjustment.  
Unit Preparation — Make sure that unit has been in-  
stalled in accordance with these installation instructions and  
applicable codes. Make sure that Start-Up Checklist has been  
completed and filled out.  
TO CHECK ignition of main burners and heating controls,  
move thermostat set point above room temperature and verify  
that the burners light and evaporator fan is energized. After  
ensuring that the unit continues to heat the building, lower  
the thermostat setting below the room temperature and verify  
that the burners and evaporator fan turn off (fan will turn off  
only if fan selector switch is in the AUTO. position). Refer  
to Table 15 for the correct orifice to use at high altitudes.  
Return-Air Filters — Make sure correct filters are in-  
stalled in filter tracks (see Table 1). Do not operate unit with-  
out return-air filters.  
Outdoor-Air Inlet Screens — Outdoor-air inlet screens  
must be in place before operating unit.  
NOTE: Upon a call for heat, the main burners will remain  
on for a minimum of 60 seconds.  
Compressor Mounting — Compressors are inter-  
nally spring mounted. Do not loosen or remove compressor  
holddown bolts. On 48TJ014 units, remove the tiedown bands  
that hold the compressors together.  
Heating  
1. Purge gas supply line of air by opening union ahead of  
gas valve. When gas odor is detected, tighten union and  
wait 5 minutes before proceeding.  
2. Turn on electrical supply and open manual gas valve.  
3. Set system switch selector at HEAT position and fan switch  
at AUTO. or ON position. Set heating temperature lever  
above room temperature.  
Internal Wiring — Check all electrical connections in  
unit control boxes. Tighten as required.  
Refrigerant Service Ports — Each refrigerant sys-  
tem has 4 Schrader-type service gage ports: one on the suc-  
tion line, one on the liquid line, and two on the compressor  
discharge line. Be sure that caps on the ports are tight. One  
Schrader-type valve is located under both the high-pressure  
switch and the low-pressure switch when ordered as an option.  
4. The induced-draft motor will start.  
5. After a call for heating, the main burners should light within  
5 seconds. If the burners do not light, then there is a  
22-second delay before another 5-second try. If the burn-  
ers still do not light, the time delay is repeated. If the  
burners do not light within 15 minutes, there is a lockout.  
To reset the control, break the 24 v power to W1.  
6. The evaporator-fan motor will turn on 45 seconds after  
the burners are ignited.  
7. The evaporator-fan motor will turn off 45 seconds after  
the thermostat temperature is satisfied.  
8. Adjust airflow to obtain a temperature rise within the range  
specified on the unit nameplate and in Table 1.  
Compressor Rotation — On 3-phase units with scroll  
compressors, it is important to be certain compressor is  
rotating in the proper direction. To determine whether or not  
compressor is rotating in the proper direction:  
1. Connect service gages to suction and discharge pressure  
fittings.  
2. Energize the compressor.  
3. The suction pressure should drop and the discharge pres-  
sure should rise, as is normal on any start-up.  
If the suction pressure does not drop and the discharge  
pressure does not rise to normal levels:  
1. Note that the evaporator fan is probably also rotating in  
the wrong direction.  
2. Turn off power to the unit.  
3. Reverse any two of the unit power leads.  
4. Reapply power to the compressor.  
NOTE: The default value for the evaporator-fan motor  
ON and OFF delay is 45 seconds. The Integrated Gas Unit  
Controller (IGC) modifies this value when abnormal limit  
switch cycles occur. Based upon unit operating condi-  
tions, the ON delay can be reduced to 0 seconds and the  
OFF delay can be extended to 180 seconds.  
When one flash of the LED (light-emitting diode) is ob-  
served, the evaporator-fan ON/OFF delay has been modi-  
fied. If the limit switch trips at the start of the heating  
cycle during the evaporator ON delay, the time period of  
the ON delay for the next cycle will be 5 seconds less  
than the time at which the switch tripped. (Example: If  
the limit switch trips at 30 seconds, the evaporator-fan  
ON delay for the next cycle will occur at 25 seconds.) To  
prevent short-cycling, a 5-second reduction will only oc-  
cur if a minimum of 10 minutes has elapsed since the last  
call for heating.  
The suction and discharge pressure levels should now move  
to their normal start-up levels.  
NOTE: When the compressor is rotating in the wrong  
direction, the unit will make an elevated level of noise and  
will not provide cooling.  
The evaporator-fan OFF delay can also be modified. Once  
the call for heating has ended, there is a 10-minute period  
during which the modification can occur. If the limit switch  
trips during this period, the evaporator-fan OFF delay will  
increase by 15 seconds. A maximum of 9 trips can occur,  
extending the evaporator-fan OFF delay to 180 seconds.  
Cooling — To start unit, turn on main power supply. Set  
system selector switch at COOL position and fan switch at  
AUTO. position. Adjust thermostat to a setting below room  
temperature. Compressor starts on closure of contactor.  
Check unit charge. Refer to Service, Refrigerant Charge  
section, page 26.  
Reset thermostat at a position above room temperature.  
Compressor will shut off. Evaporator fan will shut off after  
30-second delay.  
TO SHUT OFF UNIT — Set system selector switch at OFF  
position. Resetting thermostat at a position above room tem-  
perature shuts unit off temporarily until space temperature  
exceeds thermostat setting.  
To restore the original default value, reset the power to  
the unit.  
TO SHUT OFF UNIT — Set system selector switch at OFF  
position. Resetting heating selector lever below room tem-  
perature will shut unit off temporarily until space tempera-  
ture falls below thermostat setting.  
23  
Table 15 — Altitude Compensation*  
compressor no. 1 and the outdoor (condenser) fan motor (OFM).  
The indoor (evaporator) fan motor (IFM) is energized and  
the economizer damper moves to the minimum position. Upon  
a further call for cooling, compressor contactor no. 2 will be  
energized, starting compressor no. 2. After the thermostat is  
satisfied, the damper moves to the fully closed position when  
using an auto fan or to the minimum position when using a  
continuous fan.  
When the outdoor-air temperature is below the OAT set-  
ting and the thermostat calls for cooling, the economizer damp-  
ers move to the minimum position. If the supply-air temperature  
is above 57 F, the damper continues to open until it reaches  
the fully open position or until the supply-air temperature  
drops below 52 F.  
When the supply-air temperature falls to between 57 F  
and 52 F, the damper will remain at an intermediate open  
position. If the supply-air temperature falls below 52 F, the  
damper will modulate closed until it reaches the minimum  
position or until the supply-air temperature is above 52 F.  
When the thermostat is satisfied, the damper will move to  
the fully closed position when using an auto fan or to the  
minimum position when using a continuous fan.  
125,000, 180,000, AND  
250,000 BTUH  
NOMINAL INPUT  
224,000 BTUH  
NOMINAL INPUT  
ELEVATION  
(Ft)  
Natural  
Liquid  
Propane  
Orifice  
Size†  
Natural  
Gas  
Orifice  
Size†  
Liquid  
Propane  
Orifice  
Size†  
Gas  
Orifice  
Size†  
0-2,000  
2,000  
31  
32  
32  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
41  
42  
42  
42  
43  
43  
44  
44  
45  
46  
47  
47  
48  
48  
30  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
38  
39  
40  
41  
42  
43  
43  
44  
44  
45  
45  
46  
47  
47  
3,000  
4,000  
5,000  
6,000  
7,000  
8,000  
9,000  
10,000  
11,000  
12,000  
13,000  
14,000  
If the outdoor air alone cannot satisfy the cooling require-  
ments of the conditioned space, economizer cooling is in-  
tegrated with mechanical cooling, providing second-stage  
cooling. Compressor no. 1 and the condenser fan will be en-  
ergized and the position of the economizer damper will be  
determined by the supply-air temperature. Compressor no. 2  
is locked out.  
When the second stage of cooling is satisfied, the com-  
pressor and OFM will be deenergized. The damper position  
will be determined by the supply-air temperature.  
*As the height above sea level increases, there is less oxygen per  
cubic foot of air. Therefore, heat input rate should be reduced at  
higher altitudes.  
†Orifice available through your local distributor.  
Safety Relief — A soft-solder joint at the suction line  
Schrader port provides pressure relief under abnormal tem-  
perature and pressure conditions.  
Ventilation (Continuous Fan) — Set fan and sys-  
tem selector switches at ON and OFF positions, respec-  
tively. Evaporator fan operates continuously to provide con-  
stant air circulation. When the evaporator-fan selector switch  
is turned to the OFF position, there is a 30-second delay be-  
fore the fan turns off.  
After a 30-second delay, the IFM shuts off. If the ther-  
mostat fan selector switch is in the ON position, the IFM  
will run continuously.  
COOLING UNITS WITH PARABLADE ECONOMIZER  
— When the outdoor air is above the enthalpy control set-  
ting, and the room thermostat calls for cooling, the compres-  
sor contactor no. 1 is energized to start compressor no. 1 and  
the outdoor (condenser) fan motor. The indoor (evaporator)  
fan motor is energized and the economizer damper moves to  
the minimum position. Upon further call for cooling, com-  
pressor contactor no. 2 is energized, starting compressor  
no. 2. After the room thermostat is satisfied the damper will  
spring return to the fully closed position.  
When the outdoor air is below the enthalpy control setting  
and the thermostat calls for cooling, the economizer outdoor  
air damper is opened proportionally to maintain between 50  
and 56 F at the mixed air sensor. If outside air alone cannot  
satisfy the cooling requirements, economizer cooling is in-  
tegrated with mechanical cooling and the second compres-  
sor is locked out. When the room thermostat is satisfied, the  
damper will spring return to the fully closed position.  
Operating Sequence  
COOLING, UNITS WITHOUT ECONOMIZER — When  
thermostat calls for cooling, terminals G and Y1 are ener-  
gized. The indoor (evaporator) fan contactor (IFC) and com-  
pressor contactor no. 1 (C1) are energized, and evaporator-  
fan motor, compressor no. 1, and condenser fan start. The  
condenser-fan motor runs continuously while unit is  
cooling. If the thermostat calls for a second stage of cooling  
by energizing Y2, compressor contactor no. 2 (C2) is ener-  
gized and compressor no. 2 starts.  
When the thermostat is satisfied, C1 and C2 are deener-  
gized and the compressors and outdoor (condenser) fan mo-  
tor (OFM) shut off. After a 30-second delay, the indoor  
(evaporator) fan motor (IFM) shuts off. If the thermostat fan  
selector switch is in the ON position, the evaporator motor  
will run continuously.  
HEATING, UNITS WITH ECONOMIZER — When the ther-  
mostat calls for heating, terminal W1 is energized. In order  
to prevent thermostat short-cycling, the unit is locked into  
the Heating mode for at least 1 minute when W1 is ener-  
gized. The induced-draft motor is then energized and the burner  
ignition sequence begins. The indoor (evaporator) fan motor  
(IFM) is energized 45 seconds after a flame is ignited and  
the damper moves to the minimum position. On units equipped  
for two stages of heat, when additional heat is needed, W2  
is energized and the high-fire solenoid on the main gas valve  
(MGV) is energized. When the thermostat is satisfied and  
W1 and W2 are deenergized, the IFM stops after a 45 sec-  
ond time-off delay. The economizer damper then moves to  
the fully closed position. When using continuous fan, the  
damper will remain in the minimum position.  
HEATING, UNITS WITHOUT ECONOMIZER — When  
the thermostat calls for heating, terminal W1 is energized. In  
order to prevent thermostat short-cycling, the unit is locked  
into the Heating mode for at least 1 minute when W1 is en-  
ergized. The induced-draft motor (IDM) is then energized  
and the burner ignition sequence begins. The indoor (evapo-  
rator) fan motor (IFM) is energized 45 seconds after a flame  
is ignited. On units equipped for two stages of heat, when  
additional heat is needed, W2 is energized and the high-fire  
solenoid on the main gas valve (MGV) is energized. When  
the thermostat is satisfied and W1 and W2 are  
deenergized, the IFM stops after a 45-second time-off delay.  
COOLING, UNITS WITH DURABLADE ECONOMIZER  
— When the outdoor-air temperature is above the OAT  
(outdoor-air thermostat) setting and the room thermostat calls  
for cooling, compressor contactor no. 1 is energized to start  
24  
SERVICE  
When servicing unit, shut off all electrical power to unit  
to avoid shock hazard or injury from rotating parts.  
Cleaning — Inspect unit interior at the beginning of each  
heating and cooling season and as operating conditions  
require.  
EVAPORATOR COIL — Clean coil as required. Inspect coil  
at beginning of heating and cooling seasons.  
1. Turn unit power off. Remove evaporator coil access panel.  
2. If economizer is installed, remove economizer by  
disconnecting Molex plug and removing economizer mount-  
ing screws. Refer to Accessory Economizer Installation  
Instructions or Optional Economizer sections on  
pages 12 and 15 for more details.  
Fig. 37 — Cleaning Condenser Coil  
3. Slide filters out of unit.  
4. Clean coil using a commercial coil cleaner or dishwasher  
detergent in a pressurized spray canister. Wash both sides  
of coil and flush with clean water. For best results, back-  
flush toward return-air section to remove foreign  
material.  
5. Flush condensate pan after completion.  
6. Reinstall economizer and filters.  
7. Reconnect wiring.  
8. Replace access panels.  
CONDENSER COIL — Inspect coil monthly. Clean con-  
denser coil annually, and as required by location and outdoor-  
air conditions.  
One-Row Coils — Wash coil with commercial cleaner. Clean  
outer surfaces with a stiff brush in the normal manner. It is  
not necessary to remove top panel.  
2-Row Coils — Clean coil as follows:  
1. Turn off unit power.  
Fig. 38 — Propping Up Top Panel  
2. Remove top panel screws on condenser end of unit.  
3. Remove condenser coil corner post. See Fig. 37. To hold  
top panel open, place coil corner post between top panel  
and center post. See Fig. 38.  
4. Remove screws securing coil to center post.  
5. Remove fastener holding coil sections together at return  
end of condenser coil. Carefully separate the outer coil  
section 3 to 4 in. from the inner coil section. See  
Fig. 39.  
6. Use a water hose or other suitable equipment to flush down  
between the 2 coil sections to remove dirt and debris. Clean  
the outer surfaces with a stiff brush in the normal manner.  
7. Secure inner and outer coil rows together with a field-  
supplied fastener.  
8. Reposition the outer coil section and remove the coil cor-  
ner post from between the top panel and center post.  
9. Reinstall the coil corner post and replace all screws.  
CONDENSATE DRAIN — Check and clean each year at  
start of cooling season. In winter, keep drain dry or protect  
against freeze-up.  
FILTERS — Clean or replace at start of each heating and  
cooling season, or more often if operating conditions require  
it. Replacement filters must be same dimensions as original  
filters.  
Fig. 39 — Separating Coil Sections  
Lubrication  
COMPRESSORS — Each compressor is charged with the  
correct amount of oil at the factory.  
FAN-MOTOR BEARINGS — Fan-motor bearings are of  
the permanently lubricated type. No further lubrication is  
required. No lubrication of condenser- or evaporator-fan  
motors is required.  
25  
to the service port on the suction line. Mount the tempera-  
ture sensing device on the suction line and insulate it so that  
outdoor ambient temperature does not affect the reading. Indoor-  
air cfm must be within the normal operating range of the  
unit.  
Condenser-Fan Adjustment (Fig. 40)  
1. Shut off unit power supply.  
2. Remove condenser-fan assembly (grille, motor, motor cover,  
and fan) and loosen fan hub setscrews.  
3. Adjust fan height as shown in Fig. 40.  
TO USE COOLING CHARGING CHART — Take the out-  
door ambient temperature and read the suction pressure gage.  
Refer to appropriate chart to determine what suction tem-  
perature should be. If suction temperature is high, add re-  
frigerant. If suction temperature is low, carefully recover some  
of the charge. Recheck the suction pressure as charge is ad-  
justed. Example (Fig. 44, Circuit 2):  
4. Tighten setscrews and replace condenser-fan assembly.  
Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . 85 F  
Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 psig  
Suction Temperature should be . . . . . . . . . . . . . . . . . . 56 F  
(Suction temperature may vary ± 5 F.)  
If Chargemastercharging device is used, temperature and  
pressure readings must be accomplished using the charging  
charts.  
48TJ UNIT VOLTAGE  
208/230 V  
FAN HEIGHT ‘‘A’’ (in.)  
2.75  
3.50  
460 V and 575 V  
Fig. 40 — Condenser-Fan Adjustment  
Manual Outdoor-Air Damper — If outdoor-air damper  
blade is required, see Manual Outdoor-Air Damper section  
on page 11.  
Economizer Adjustment — Refer to Optional Econo-  
mizer sections on pages 12 and 15.  
Condenser Coil Grille — Condenser coil grille is shipped  
factory-installed. No adjustments are required.  
Refrigerant Charge — Amount of refrigerant charge  
is listed on unit nameplate (also refer to Table 1). Refer to  
Carrier GTAC 2-5 Charging, Recovery, Recycling, and Rec-  
lamation training manual and the following procedures.  
Unit panels must be in place when unit is operating dur-  
ing charging procedure.  
NO CHARGE — Use standard evacuating techniques. After  
evacuating system, weigh in the specified amount of refrig-  
erant (refer to Table 1).  
LOW CHARGE COOLING — Using Cooling Charging  
Charts, Fig. 41-44, vary refrigerant until the conditions of  
the appropriate chart are met. Note the charging charts are  
different from the type normally used. The charts are based  
on charging the units to the correct superheat for the various  
operating conditions. Accurate pressure gage and tempera-  
ture sensing device are required. Connect the pressure gage  
Fig. 41 — Cooling Charging Chart; 48TJ008  
26  
Fig. 42 — Cooling Charging Chart; 48TJ009  
Fig. 43 — Cooling Charging Chart; 48TJ012  
27  
Fig. 44 — Cooling Charging Chart; 48TJ014  
history) and the indoor (evaporator) fan ON/OFF times will  
Flue Gas Passageways — To inspect the flue col-  
be reset. For additional information, refer to the Start-Up,  
Heating section on page 23. The LED error code can be ob-  
served through the viewport. See Fig. 12. During servicing  
refer to the label on the control box cover or Table 16 for an  
explanation of LED error code descriptions.  
lector box and upper areas of the heat exchanger:  
1. Remove the combustion blower wheel and motor assem-  
bly according to directions in Combustion-Air Blower sec-  
tion below.  
2. Remove the flue cover to inspect the heat exchanger.  
3. Clean all surfaces as required using a wire brush.  
If lockout occurs, unit may be adjusted by interrupting power  
supply to unit for at least 5 seconds.  
Combustion-Air Blower — Clean periodically to as-  
sure proper airflow and heating efficiency. Inspect blower  
wheel every fall and periodically during heating season. For  
the first heating season, inspect blower wheel bimonthly to  
determine proper cleaning frequency.  
To inspect blower wheel, shine a flashlight into drafthood  
opening. If cleaning is required, remove motor and wheel as  
follows:  
1. Slide burner access panel out.  
2. Remove the 6 screws that attach induced-draft motor hous-  
ing to vestibule plate (Fig. 45).  
3. The blower wheel can be cleaned at this point. If  
additional cleaning is required, continue with Steps 4  
and 5.  
4. To remove blower from the motor shaft, remove 2  
setscrews.  
5. To remove motor, remove the 4 screws that hold blower  
housing to mounting plate. Remove the motor cooling fan  
by removing one setscrew. Then remove nuts that hold  
motor to mounting plate.  
Table 16 — LED Error Code Description*  
LED INDICATION  
ON  
ERROR CODE DESCRIPTION  
Normal Operation  
OFF  
Hardware Failure  
1 Flash†  
2 Flashes  
3 Flashes  
4 Flashes  
5 Flashes  
6 Flashes  
7 Flashes  
8 Flashes  
Evaporator Fan On/Off Delay Modified  
Limit Switch Fault  
Flame Sense Fault  
4 Consecutive Limit Switch Faults  
Ignition Lockout Fault  
Induced-Draft Motor Fault  
Rollout Switch Fault  
Internal Control Fault  
LED  
Light-Emitting Diode  
*A 3-second pause exists between LED error code flashes. If more  
than one error code exists, all applicable codes will be displayed in  
numerical sequence.  
†Indicates a code that is not an error. The unit will continue to op-  
erate when this code is displayed.  
IMPORTANT: Refer to Troubleshooting Tables 17-21 for additional  
information.  
6. To reinstall, reverse the procedure outlined above.  
Limit Switch — Remove blower access panel (Fig. 7).  
Main Burners — At the beginning of each heating sea-  
son, inspect for deterioration or blockage due to corrosion or  
other causes. Observe the main burner flames and adjust if  
necessary.  
Limit switch is located on the fan deck.  
Burner Ignition — Unit is equipped with a direct spark  
ignition 100% lockout system. Integrated Gas Unit Control-  
ler (IGC) is located in the control box (Fig. 12). Module con-  
tains a self-diagnostic LED. A single LED on the IGC pro-  
vides a visual display of operational or sequential problems  
when the power supply is interrupted. When a break in power  
occurs, the module will be reset (resulting in a loss of fault  
When working on gas train, do not hit or plug orifice  
spuds.  
28  
REMOVAL AND REPLACEMENT OF GAS TRAIN  
(Fig. 45 and 46)  
ROLLOUT  
SWITCH  
1. Shut off manual gas valve.  
2. Shut off power to unit.  
3. Slide out burner section side panel (not shown).  
4. Disconnect gas piping at unit gas valve.  
5. Remove wires connected to gas valve. Mark each wire.  
BURNER  
SECTION  
FLUE  
6. Remove wires from ignitor and sensor wires at the Inte-  
grated Gas Unit Controller (IGC).  
7. Remove the 2 screws that attach the burner rack to the  
vestibule plate.  
8. Slide the burner tray out of the unit (Fig. 46).  
9. To reinstall, reverse the procedure outlined above.  
EXHAUST  
VESTIBULE  
PLATE  
INDUCED-DRAFT  
MOTOR  
MANIFOLD  
PRESSURE TAP  
CLEANING AND ADJUSTMENT  
GAS VALVE  
1. Remove burner rack from unit as described in Removal  
and Replacement of Gas Train section, above.  
2. Inspect burners; if dirty, remove burners from rack.  
3. Using a soft brush, clean burners and cross-over port as  
required.  
Fig. 45 — Burner Section Details  
4. Adjust spark gap. See Fig. 47.  
5. Reinstall burners on rack.  
6. Reinstall burner rack as described in Removal and Re-  
placement of Gas Train section, this page.  
Replacement Parts — A complete list of replace-  
ment parts may be obtained from any Carrier distributor upon  
request.  
Fig. 46 — Burner Tray Details  
29  
125,000 BTUH INPUT  
48TJD008,009  
120,000-180,000 BTUH INPUT  
48TJD012, 48TJE008,009  
180,000-224,000 BTUH INPUT  
200,000-250,000 BTUH INPUT  
48TJD014; 48TJE012  
48TJF008,009  
48TJE014; 48TJF012  
NOTE: Dimensions in ( ) are millimeters.  
Fig. 47 — Spark Gap Adjustment  
30  
TROUBLESHOOTING  
Table 17 — LED Error Code Service Analysis  
PROBLEM  
CAUSE  
REMEDY  
Hardware failure.  
(LED OFF)  
Loss of power to control module (IGC).  
Check 5-amp fuse on IGC, power to unit, 24-v circuit  
breaker, and transformer. Units without a 24-v circuit  
breaker have an internal overload in the 24-v trans-  
former. If the overload trips, allow 10 minutes for auto-  
matic reset.  
Limit switch fault.  
(LED 2 flashes)  
High temperature limit switch is open.  
Check the operation of the indoor (evaporator) fan mo-  
tor. Ensure that the supply-air temperature rise is in ac-  
cordance with the range on the unit nameplate.  
Flame sense fault.  
(LED 3 flashes)  
The IGC sensed flame that should not be present.  
Inadequate airflow to unit.  
Reset unit. If problem persists, replace control board.  
4 consecutive limit  
switch trips.  
(LED 4 flashes)  
Check operation of indoor (evaporator) fan motor and  
that supply-air temperature rise agrees with range on  
unit nameplate information.  
Ignition lockout.  
(LED 5 flashes)  
Unit unsuccessfully attempted ignition for 15 minutes.  
Check ignitor and flame sensor electrode spacing, gaps,  
etc. Ensure that flame sense and ignition wires are prop-  
erly terminated. Verify that unit is obtaining proper  
amount of gas.  
Induced-draft motor  
fault.  
(LED 6 flashes)  
IGC does not sense that induced-draft motor is  
operating.  
Check for proper voltage. If motor is operating, check  
the speed sensor plug/IGC Terminal J2 connection.  
Proper connection: PIN 1 — White, PIN 2 — Red, PIN 3  
— Black.  
Rollout switch fault.  
(LED 7 flashes)  
Rollout switch has opened.  
Rollout switch will automatically reset, but IGC will con-  
tinue to lock out unit. Check gas valve operation. Ensure  
that induced-draft blower wheel is properly secured to  
motor shaft. Reset unit at unit disconnect.  
Internal control fault. Microprocessor has sensed an error in the software or  
If error code is not cleared by resetting unit power, re-  
place the IGC.  
(LED 8 flashes)  
hardware.  
LEGEND  
IGC  
LED  
Integrated Gas Unit Controller  
Light-Emitting Diode  
IMPORTANT: Refer to Table 21 — Heating Service Troubleshoot-  
ing for additional troubleshooting information.  
If the IGC must be replaced, be sure to ground yourself to dis-  
sipate any electrical charge that may be present before han-  
dling new control board. The IGC is sensitive to static electricity  
and may be damaged if the necessary precautions are not taken.  
31  
Table 18 — Durablade Economizer Troubleshooting  
PROBLEM  
CAUSE  
REMEDY  
Damper does not  
open.  
Indoor (evaporator) fan is off.  
1. Check to ensure that 24 vac is present at terminal C1 on the IFC or  
that 24 vac is present at the IFO terminal. Check whether 24 vac is  
present at PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is  
not present, check wiring (see unit label diagram).  
2. Check proper thermostat connection to G on the connection board.  
No power to economizer motor.  
1. Check that SW3 is properly making contact with the damper  
blade. Check that SW1 is in the NC (normally closed) position.  
2. Check diode D1. If diode is not functioning properly, replace D1.  
3. Confirm that the economizer control board is grounded properly at  
PL6-4 (brown wire) and at brown terminal of the economizer control  
board (brown wire). The economizer motor must also be grounded  
properly at the negative motor terminal (brown wire).  
4. Verify SW1 and SW3 are working and wired properly (see unit label  
diagram).  
5. Check for 24 vac input at both PL6-1 (red wire) and PL6-3 (black  
wire). If 24 vac not present, check unit wiring (see unit label dia-  
gram). If 24 vac is found in both places, check for 24 vac at the yel-  
low terminal of the economizer control board (yellow wire). If  
24 vac power is not present, replace the economizer control board.  
Economizer motor failure.  
OAT or EC set too high.  
If the indoor (evaporator) fan and economizer motor are energized,  
verify that there is a minimum of 18 vdc at the positive motor terminal.  
If the motor is not operating, replace the motor.  
1. Set at correct temperature (3 F below indoor space temperature).  
2. Check OAT or EC by setting above outdoor temperature or humidity  
level. If the OAT or EC switches do not close, replace OAT or EC.  
Economizer operation  
limited to minimum  
position.  
Verify economizer control board is correctly wired 1. Perform the following tests when OAT or EC is closed, Y1 is called  
and works properly.  
for and damper is at minimum position. Confirm 24 vac on gray ter-  
minal of the economizer control board (gray wire). If 24 vac is not  
present, check wiring (see unit label diagram).  
2. Verify that SW1 and SW3 are wired correctly and working properly  
(see unit label diagram).  
3. Check to ensure that 24 vac exists at PL6-2 (blue wire). If  
24 vac is not present, check wiring (see unit wiring label diagram).  
4. Check 24 vac output at PL6-10 (white wire). If 24 vac is not  
present, replace economizer control board.  
Check SAT.  
1. After verifying that the OAT and EC settings and the economizer  
control board wiring are correct, check to ensure that the 24 vac  
terminal of the SAT has 24 vac (white wire). If OAT, EC, and control  
board are functioning and wired properly and no 24 vac exists,  
check wiring (see unit label diagram).  
2. If supply-air temperature is greater than 57 F, 24 vac should be  
found at terminal T2 on the SAT (pink wire). If 24 vac is not present,  
replace SAT.  
Damper does not  
close.  
Incorrect wiring of economizer.  
1. Verify that SW2 and SW4 are wired and working properly (see unit  
label diagram).  
2. Check diode D2. If diode is not functioning properly, replace D2.  
Verify economizer control board is functioning  
properly.  
1. After verifying that the wiring is correct, modulate the damper to the  
minimum position. Remove the call for G (evaporator fan).  
2. If the damper does not move, check for 24 vac at PL6-1 (red wire).  
If 24 vac is not present, check wiring (see unit label diagram).  
3. If damper still does not move, check for 24 vac at blue terminal of  
economizer control board (blue wire). If 24 vac is not present, re-  
place the economizer circuit board.  
Check SAT.  
1. After verifying that the wiring is correct and the economizer control  
board is functioning properly, place the OAT or EC switch in the  
closed position. Place a call for Y1 and open the damper to the fully  
open position. Confirm that the 24 vac terminal of the SAT has  
24 vac (white wire). If 24 vac is not present, check wiring (see unit  
label diagram).  
2. If supply-air temperature is less than 52 F, 24 vac should be found  
at terminal T1 on the SAT (violet wire). If 24 vac not found, replace  
SAT.  
Economizer motor failure.  
If economizer control board and SAT are functioning properly, verify  
that there is a minimum of 18 vdc at the positive motor terminal. If a  
minimum if 18 vdc is present and the motor is still not operating, re-  
place the motor.  
Economizer damper  
does not close on  
power loss.  
Verify that close-on-power-loss and economizer  
control board are functioning properly.  
1. Check voltage potential across batteries. If lower than 14 vdc, re-  
place close-on-power-loss power supply (9-v alkaline batteries). It is  
recommended that you check this emergency power supply on a  
regular basis or whenever the filters are changed.  
2. If the close-on-power-loss and economizer control board are func-  
tioning properly, check for 14 vdc or higher at the blue terminal of  
the economizer control board (blue wire) when power is discon-  
nected from unit. If 14 vdc is not present, replace the control board.  
LEGEND  
C1  
Common Power  
Enthalpy Control  
EC  
IFC  
IFO  
OAT  
PL  
SAT  
SW  
Indoor (Evaporator) Fan Contactor  
Indoor (Evaporator) Fan On  
Outdoor-Air Thermostat  
Plug  
Supply-Air Thermostat  
Economizer Position Switch  
32  
Table 19 — PARABLADE Economizer Service Troubleshooting  
PROBLEM  
CAUSE  
Evaporator fan not on.  
REMEDY  
Damper does not  
open.  
Check wiring between G on connection board and indoor (evaporator)  
fan contactor.  
No power to economizer motor.  
1. Disconnect power at TR and TR1. Disconnect jumper across P  
and P1.  
2. Connect jumper across TR and 1.  
3. Connect jumper across T1 and T.  
4. If connected, remove enthalpy sensor from terminals So and +.  
Factory-installed 620 ohm resistor should be connected to termi-  
nals SR and +.  
5. Apply power (24 vac) to terminals TR and TR1. The LED should  
be off and the damper should be in the closed position.  
6. Disconnect the factory-installed 620 ohm resistor from terminals  
SR and +. The LED should light up and the motor should drive to-  
wards open. If this does not happen, replace the economizer con-  
trol module.  
Economizer motor failure.  
If the indoor (evaporator) fan and economizer motor are energized,  
verify that there is a minimum of 24 vac at terminals TR and TR1. If  
the motor is not operating, replace the motor.  
Economizer opera-  
tion limited to mini-  
mum position.  
Economizer control module  
failure.  
1. To simulate high or low enthalpy, reconnect the factory-installed  
620 ohm resistor across terminals SR and +.  
2. Connect 1.2 Kohm checkout resistor across terminals So and +.  
Turn the enthalpy set point to ‘‘A.’’ The LED should turn on, indi-  
cating low enthalpy. The motor should drive towards open. If LED  
does not light, replace module. If motor does not drive open, check  
motor operation.  
3. Turn the enthalpy set point to ‘‘D.’’ The LED should turn off, indi-  
cating high enthalpy. The motor should drive towards closed. If  
these actions do not occur, replace module.  
4. Disconnect 1.2 Kohm checkout resistor before resuming operation.  
Damper does not  
close.  
No power to economizer.  
1. Disconnect power at TR and TR1. Disconnect jumper across P  
and P1.  
2. Connect jumper across TR and 1.  
3. Connect jumper across T1 and T.  
4. If connected, remove enthalpy sensor from terminals So and +.  
Factory-installed 620 ohm resistor should be connected to termi-  
nals SR and +.  
5. Apply power (24 vac) to terminals TR and TR1. The LED should  
be off and the damper should be in the closed position.  
6. Disconnect the factory-installed 620 ohm resistor from terminals  
SR and +. The LED should light up and the motor should drive to-  
wards open. If this does not happen, replace the economizer con-  
trol module.  
Spring return failure.  
If power to unit is off and damper does not close, check for a bound  
linkage. If linkage is not bound, then internal spring may be broken.  
Replace actuator.  
Economizer motor failure.  
Sensor incorrectly wired or bad.  
If the economizer control module is functioning properly, verify that  
there is a minimum of 24 vac at terminals TR and TR1. If the motor is  
not operating, replace the motor.  
Damper does not  
open or  
To verify sensor operation, reconnect the + lead of the outdoor en-  
thalpy sensor to the + terminal of the economizer control module.  
Connect a DC milliammeter between terminals So of the economizer  
control module and terminal S of the enthalpy sensor. The milliamme-  
ter should indicate between 3 and 25 mA if the sensor is operating  
properly. If the milliammeter indicates 0, the sensor may be wired  
backwards. If any other readings are shown, replace the sensor.  
close according to  
enthalpy  
readings.  
LEGEND  
LED  
Light-Emitting Diode  
33  
Table 20 — Cooling Service Troubleshooting  
PROBLEM  
CAUSE  
REMEDY  
Compressor and  
condenser fan  
will not start.  
Power failure.  
Call power company.  
Fuse blown or circuit breaker tripped.  
Replace fuse or reset circuit breaker.  
Replace component.  
Defective thermostat, contactor, transformer, or control  
relay.  
Insufficient line voltage.  
Incorrect or faulty wiring.  
Thermostat setting too high.  
Determine cause and correct.  
Check wiring diagram and rewire correctly.  
Lower thermostat setting below room temperature.  
Compressor will not start Faulty wiring or loose connections in compressor circuit. Check wiring and repair or replace.  
but condenser fan runs.  
Compressor motor burned out, seized, or internal  
overload open.  
Determine cause. Replace compressor.  
Defective run/start capacitor, overload, or start relay.  
One leg of 3-phase power dead.  
Determine cause and replace.  
Replace fuse or reset circuit breaker.  
Determine cause.  
Compressor cycles  
(other than normally  
satisfying thermostat).  
Refrigerant overcharge or undercharge.  
Recover refrigerant, evacuate system, and recharge  
to nameplate.  
Defective compressor.  
Replace and determine cause.  
Determine cause and correct.  
Determine cause and correct.  
Determine cause and replace.  
Replace thermostat.  
Insufficient line voltage.  
Blocked condenser.  
Defective run/start capacitor, overload, or start relay.  
Defective thermostat.  
Faulty condenser-fan motor or capacitor.  
Restriction in refrigerant system.  
Compressor rotating in wrong direction.  
Replace.  
Locate restriction and remove.  
Compressor makes  
excessive noise  
(48TJ014 scroll only)  
Reverse the 3-phase power leads as described  
on page 23.  
Compressor operates  
continuously.  
Dirty air filter.  
Replace filter.  
Unit undersized for load.  
Thermostat set too low.  
Low refrigerant charge.  
Leaking valves in compressor.  
Air in system.  
Decrease load or increase unit size.  
Reset thermostat.  
Locate leak, repair, and recharge.  
Replace compressor.  
Recover refrigerant, evacuate system, and recharge.  
Clean coil or remove restriction.  
Replace filter.  
Condenser coil dirty or restricted.  
Excessive head pressure. Dirty air filter.  
Dirty condenser coil.  
Clean coil.  
Refrigerant overcharged.  
Air in system.  
Remove excess refrigerant.  
Recover refrigerant, evacuate system, and recharge.  
Determine cause and correct.  
Check for leaks, repair, and recharge.  
Replace compressor.  
Condenser air restricted or air short-cycling.  
Low refrigerant charge.  
Compressor valves leaking.  
Restriction in liquid tube.  
High heat load.  
Head pressure too low.  
Remove restriction.  
Excessive suction  
pressure.  
Check for source and eliminate.  
Replace compressor.  
Compressor valves leaking.  
Refrigerant overcharged.  
Recover excess refrigerant.  
Replace filter.  
Suction pressure too low. Dirty air filter.  
Low refrigerant charge.  
Check for leaks, repair, and recharge.  
Remove source of restriction.  
Metering device or low side restricted.  
Insufficient evaporator airflow.  
Increase air quantity. Check filter and replace if  
necessary.  
Temperature too low in conditioned area.  
Field-installed filter drier restricted.  
Unit in economizer mode.  
Reset thermostat.  
Replace.  
Compressor no. 2  
will not run.  
Proper operation; no remedy necessary.  
34  
Table 21 — Heating Service Troubleshooting  
PROBLEM  
CAUSE  
REMEDY  
Burners will not  
ignite.  
Misaligned spark electrodes.  
Check flame ignition and sensor electrode positioning.  
Adjust as needed.  
No gas at main burners.  
Check gas line for air purge as necessary. After purging  
gas line of air, allow gas to dissipate for at least 5 min-  
utes before attempting to relight unit.  
Check gas valve.  
Water in gas line.  
Drain water and install drip leg to trap water.  
Check power supply, fuses, wiring, and circuit breaker.  
Check transformer. Transformers with internal overcur-  
No power to furnace.  
No 24 v power supply to control circuit.  
rent protection require  
resetting.  
a
cool down period before  
Miswired or loose connections  
Burned-out heat anticipator in thermostat.  
Broken thermostat wires.  
Dirty air filter.  
Check all wiring and wirenut connections.  
Replace thermostat.  
Run continuity check. Replace wires, if necessary.  
Clean or replace filter as necessary.  
Inadequate heating.  
Gas input to unit too low.  
Check gas pressure at manifold. Clock gas meter for  
input. If too low, increase manifold pressure, or replace  
with correct orifices.  
Unit undersized for application.  
Restricted airflow.  
Replace with proper unit or add additional unit.  
Clean filter, replace filter, or remove any restrictions.  
Blower speed too low.  
Use high speed tap, increase fan speed, or install op-  
tional blower, as suitable for individual units.  
Limit switch cycles main burners.  
Too much outdoor air.  
Check rotation of blower, thermostat heat anticipator set-  
tings, and temperature rise of unit. Adjust as needed.  
Adjust minimum position.  
Check economizer operation.  
Poor flame  
characteristics.  
Incomplete combustion (lack of combustion air)  
results in:  
Check all screws around flue outlets and burner com-  
partment. Tighten as necessary.  
Aldehyde odors, CO, sooting flame, or floating flame.  
Cracked heat exchanger.  
Overfired unit — reduce input, change orifices, or adjust  
gas line or manifold pressure.  
Check vent for restriction. Clean as necessary.  
Check orifice to burner alignment.  
Burners will not  
turn off.  
Unit is locked into Heating mode for a one minute  
minimum.  
Wait until mandatory one minute time period has  
elapsed or power to unit.  
LEGEND AND NOTES FOR FIG. 48  
IMPORTANT: Refer to unit wiring label for actual unit  
wiring information.  
AHA  
BR  
Adjustable Heat Anticipator  
Burner Relay  
IFM  
IGC  
Indoor (Evaporator) Fan Motor  
Integrated Gas Unit  
Controller  
Light Emitting Diode  
Low-Pressure/Loss-of-Charge  
Switch  
Limit Switch  
Main Gas Valve  
Motor  
Outdoor Air Thermostat  
Outdoor-Fan Motor  
Plug Assembly  
Quadruple Terminal  
Relay  
Rollout Switch  
Supply Air Thermostat  
Sensor  
Thermostat-Cooling  
Thermostat-Heating  
Transformer  
Field Splice  
Marked Wire  
C
Contactor, Compressor  
Capacitor  
CAP  
CB  
CC  
COMP  
CR  
D
EC  
EPS  
EQUIP  
FPT  
LED  
LPS  
Terminal (Marked)  
Circuit Breaker  
Cooling Compensator  
Compressor Motor  
Control Relay  
Terminal (Unmarked)  
LS  
MGV  
MTR  
OAT  
OFM  
PL  
Terminal Block  
Splice  
Diode  
Enthalpy Control  
Economizer Pressure Switch  
Equipment  
Splice (Marked)  
Factory Wiring  
Field Control Wiring  
Field Power Wiring  
Accessory or Optional Wiring  
To indicate common potential  
only, not to represent wiring  
Freeze-Protection  
Thermostat  
Ground  
Gas Valve Relay  
High-Pressure Switch  
Hall Effect Sensor  
Ignitor  
Induced-Draft Motor  
Indoor (Evaporator) Fan  
Contactor  
QT  
R
GND  
GVR  
HPS  
HS  
RS  
SAT  
SEN  
TC  
I
TH  
TRAN  
IDM  
IFC  
NOTES:  
1. If any of the original wire furnished must be replaced, it must be  
replaced with type 90 C wire or its equivalent.  
2. Three-phase motors are protected under primary single phasing  
conditions.  
5. Use copper conductors only.  
6. TRAN is wired for 230 v unit. If unit is to be run with 208 v power  
supply, disconnect BLK wire from 230 v tap (RED) and connect to  
200 v tap (BLU). Insulate end of 230 v tap.  
3. Thermostat: HH07AT170, 172, 174 and P272-2783  
Subbase: HH93AZ176, 178 and P272-1882, 1883  
4. Set heat anticipator for first stage at 0.14 amp, second stage at  
0.2 amp.  
7. When economizer assembly is installed move GRA wire from con-  
nection board (Y1) to GRA wire from PL6,5; move ORN wire from  
connection board (Y2) to ORN wire from PL6,9, on economizer  
assembly.  
35  
Fig. 48 — Typical Wiring Schematic and Component Arrangement  
36  
Copyright 1996 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 1  
4
PC 111  
Catalog No. 564-934  
Printed in U.S.A.  
Form 48TJ-13SI  
Pg 38  
9-96  
Replaces: 48TJ-10SI  
Tab 1a 6a  
START-UP CHECKLIST  
(Remove and Store in Job File)  
I. PRELIMINARY INFORMATION  
MODEL NO.:  
DATE:  
SERIAL NO.:  
TECHNICIAN:  
II. PRE-START-UP (insert checkmark in box as each item is completed)  
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT  
REMOVE SHIPPING TIE DOWN BANDS ON COMPRESSOR (SIZE 014 ONLY) PER INSTALLATION  
INSTRUCTIONS  
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS  
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS  
CHECK GAS PIPING FOR LEAKS  
CHECK THAT INDOOR-AIR FILTERS ARE CLEAN AND IN PLACE  
VERIFY THAT UNIT INSTALLATION IS LEVEL  
CHECK FAN WHEELS AND PROPELLERS FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW  
TIGHTNESS  
III. START-UP  
ELECTRICAL  
SUPPLY VOLTAGE  
L1-L2  
L2-L3  
L2  
L3-L1  
L3  
COMPRESSOR AMPS L1  
COMPRESSOR AMPS L1  
L2  
L3  
INDOOR-FAN AMPS  
L1  
L2  
L3  
TEMPERATURES  
OUTDOOR-AIR TEMPERATURE  
RETURN-AIR TEMPERATURE  
COOLING SUPPLY AIR  
DB  
DB  
DB  
DB  
WB  
GAS HEAT SUPPLY AIR  
PRESSURES  
GAS INLET PRESSURE  
GAS MANIFOLD PRESSURE  
REFRIGERANT SUCTION  
REFRIGERANT DISCHARGE  
IN. WG  
IN. WG (HI FIRE)  
PSIG — CIRCUIT NO. 1  
PSIG — CIRCUIT NO. 1  
PSIG — CIRCUIT NO. 2  
PSIG — CIRCUIT NO. 2  
VERIFY REFRIGERANT CHARGE USING CHARGING TABLES  
VERIFY THAT 3-PHASE SCROLL COMPRESSOR ROTATING IN CORRECT DIRECTION (48TJ014 ONLY)  
Copyright 1996 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 1  
4
PC 111  
Catalog No. 564-934  
Printed in U.S.A.  
Form 48TJ-13SI  
Pg CL-1  
9-96  
Replaces: 48TJ-10SI  
Tab 1a 6a  

Alen C360 User Manual
Amana Quiet Zone 5M11TA User Manual
Canon Pixma Inkjet Multifunction Printer Mg3220 User Manual
Carrier 30HH User Manual
Carrier 48SS024 User Manual
Carrier DPE012 User Manual
Fujitsu Air Conditioner ASU30CLX1 User Manual
Fusion EMPEROR L702B User Manual
GE General Electric Air Conditioner 3828A User Manual
HP Hewlett Packard Officejet J4660 User Manual