Carrier 39LD User Manual

39LA,LB,LC,LD,LF,LG,LH03-25  
Indoor Air-Handling Units  
Installation, Start-Up and  
Service Instructions  
CONTENTS  
Page  
CHECK the assembly and component weights to be sure  
that the rigging equipment can handle them safely. Note  
also, the centers of gravity and any specific rigging  
instructions.  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2,3  
Unit Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
PREINSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7  
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
Suspended Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
Service Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
External Vibration Isolators. . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-29  
Mixing Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8  
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8  
Inlet Guide Vane Actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
Install Fan Motor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11  
Install Sheaves on Motor and Fan Shafts . . . . . . . . . . . . . .11  
Install V-Belts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
Water and Steam Piping Recommendations . . . . . . . . . . 14  
Coil Freeze-Up Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
Refrigerant Piping, Direct Expansion  
(DX) Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Electric Heaters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
Discharge Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28  
START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29,30  
Check List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30-38  
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
Fan Motor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
Winter Shutdown (Chilled Water Coil Only) . . . . . . . . . . . 30  
Field-Installed Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Coil Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Changing Coil Hand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
Filters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
Fan Shaft Bearing Removal. . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
Fan and Shaft Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38  
Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38  
METRIC CONVERSION CHART . . . . . . . . . . . . . . . . . . . . . . . 39  
CHECK for adequate ventilation so that fumes will not  
migrate through ductwork to occupied spaces when weld-  
ing or cutting inside air-handling unit cabinet or plenum.  
WHEN STEAM CLEANING COILS be sure that the area  
is clear of personnel.  
DO NOT attempt to handle access covers and removable  
panels on outdoor units when winds are strong or gusting  
until you have sufficient help to control them. Make sure  
panels are properly secured while repairs are being made to  
a unit.  
DO NOT remove access panel fasteners until fan is com-  
pletely stopped. Pressure developed by a moving fan can  
cause excessive force against the panel which can injure  
personnel.  
DO NOT work on dampers until their operators are  
disconnected.  
BE SURE that fans are properly grounded before working  
on them.  
SECURE drive sheaves with a rope or strap before work-  
ing on a fan to ensure that rotor cannot free-wheel.  
DO NOT restore power to unit until all temporary walk-  
ways inside components have been removed.  
NEVER pressurize equipment in excess of specified test  
pressures.  
PROTECT adjacent flammable material when welding or  
flame cutting. Use sheet metal or asbestos cloth to contain  
sparks. Have a fire extinguisher at hand and ready for  
immediate use.  
SAFETY CONSIDERATIONS  
Air-handling equipment is designed to provide safe and  
reliable service when operated within design specifications. To  
avoid injury to personnel and damage to equipment or property  
when operating this equipment, use good judgment and follow  
safe practices as outlined below.  
IMPORTANT: The installation of air-handling units and all  
associated components, parts, and accessories which make  
up the installation and subsequent maintenance shall be in  
accordance with the regulations of ALL authorities having  
jurisdiction and MUST conform to all applicable codes. It  
is the responsibility of the installing contractor to determine  
and comply with ALL applicable codes and regulations.  
Field-supplied motors should be Underwriters Laboratories  
(UL) or Canadian Standards Association (CSA) approved.  
Field wiring must comply with National Electrical Code  
(NEC) and all local requirements.  
NEVER enter an enclosed fan cabinet or reach into a unit  
while the fan is running.  
LOCK OPEN AND TAG the fan motor power disconnect  
switch before working on a fan. Take fuses with you and  
note removal on tag. Electric shock can cause personal  
injury or death.  
LOCK OPEN AND TAG the electric heat coil power dis-  
connect switch before working on or near heaters.  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 533-932 Printed in U.S.A. Form 39L-6SI Pg 1 1110 2-04 Replaces: 39L-5SI  
3
PREINSTALLATION  
Suspended Units — Figure 6 shows overhead suspen-  
sion of unit using optional factory-supplied suspension  
channels.  
Each support channel consists of 2 pieces, the smaller of  
which fits inside the larger one. This allows the channel to be  
adjusted to the required length for installation.  
Channels are shipped on top of the unit. The 2 sections of  
each channel are shipped one inside the other, and are held in  
place during shipping by the panel screws in the top panel.  
1. Check items received against packing list. Notify Carrier  
of any discrepancy.  
2. Refer to Fig. 4 for service area requirements.  
3. To transfer unit from truck to storage site, refer to rigging  
details in Fig. 5 and section on unit rigging for proper  
handling. See Table 1 for component weights.  
Hardware required for installation of suspension channels is  
shipped in a package inside the fan section.  
If a fork lift truck is used, lift only from heavy end of skid.  
Minimum recommended fork length is 48 inches.  
At least 2 suspension channels are shipped with each fan  
and coil unit. One or more extra channels will be supplied  
depending on the number of accessories ordered. Be sure to  
install all the suspension channels shipped with a unit. Refer to  
39L Isolator Mounting (Suspended Unit) certified drawing for  
details.  
To install suspension channels:  
1. Remove panel screws to free suspension channels for in-  
stallation. Replace screws in top panel.  
2. Adjust channel to required length by sliding one channel  
section inside the other. The channel must extend at least  
9 in. but not more than 12 in. beyond the edge of the unit.  
Set length of channel by installing factory-supplied bolts  
through the overlapping channel sections.  
3. Mount unit to suspension channel using factory-supplied  
nuts and bolts through 7/16-in. diameter holes in unit lift-  
ing bracket.  
4. Do not stack unit components or accessories during stor-  
age. Stacking can cause damage or deformation.  
5. If unit is to be stored for more than 2 weeks prior to in-  
stallation, observe the following precautions:  
a. Choose a dry storage site that is reasonably level  
and sturdy to prevent undue stress or permanent  
damage to the unit structure or components. Do not  
store unit on vibrating surface. Damage to station-  
ary bearings can occur. Set unit off ground if in  
heavy rain area.  
b. Remove all fasteners and other small parts from  
jobsite to minimize theft. Tag and store parts in a  
safe place until needed.  
c. Cover entire unit with a tarp or plastic coverall.  
Extend cover under unit if stored on ground.  
Secure cover with adequate tiedowns or store  
indoors. Be sure all coil connections have protec-  
tive shipping caps.  
4. Install field-supplied suspension rods through 9/16-in. di-  
ameter holes provided at outer edges of channel. Be sure  
hanger rods are securely fastened in place.  
d. Monthly — Remove tarp from unit, enter fan  
section through access door or through fan inlet,  
and rotate fan and motor slowly by hand to redis-  
tribute the bearing grease and to prevent bearing  
corrosion.  
Service Clearance — Provide adequate space for unit  
service access (fan shaft and coil removal, filter removal, mo-  
tor access, damper linkage access, etc.) as shown in Fig. 4.  
Condensate Drain — To prevent excessive build-up of  
condensate in drain pan, adequate trap clearance must be pro-  
vided beneath the unit as indicated in Fig. 7. See Installation,  
Condensate Drain section (page 8) for additional details.  
Rigging (Fig. 5) — All 39L units can be rigged by means  
of the lifting brackets on bottom of unit.  
Units are shipped fully assembled. Do not remove shipping  
skids or protective covering until unit is ready for final place-  
ment. Use slings and spreader bars as applicable to lift unit. Do  
not lift unit by coil connections or headers.  
Do not remove protective caps from coil piping connections  
until ready to connect piping.  
External Vibration Isolators — Install vibration iso-  
lators per certified drawings, and in accordance with the job  
specifications and the instructions of the vibration isolator  
manufacturer. The coil piping must be isolated or have a flexi-  
ble connection to avoid coil header damage because of unit  
motion. A flexible connection should be installed at the fan dis-  
charge.  
Do not remove protective cover or grease from fan shaft un-  
til ready to install sheave.  
Lay rigid temporary protection such as plywood walkways  
in unit to prevent damage to insulation or bottom panel during  
installation.  
Figure 6 shows isolation location for floor mounting or  
overhead suspension of unit.  
4
NOTE: Dimensions in ( ) are in mm.  
DIMENSIONS (mm)  
DIMENSIONS (ft-in.)  
D
D
SIZE  
A
B
C
E
SIZE  
A
B
C
E
39LA  
500  
600  
700  
700  
700  
900  
1000  
1000  
700  
39LB 39LC  
39LA  
39LB 39LC  
1- 711/16 0-77/8 1-33/4 2- 39/16  
03 3-17/8  
06 3-93/4  
08 4-111/16 4-19/16 2-51/8  
10 4-99/16 4-97/16 2-51/8  
12 5-51/16 5-55/16 2-51/8  
15 5-51/16 5-55/16 3-1  
18 5-51/16 5-55/16 3-415/16 3- 33/8  
21 6-51/4  
25 6-51/4  
3-13/4 1-91/4  
3-95/8 2-13/16 1-115/8  
03  
06  
08  
10  
12  
15  
18  
21  
25  
952  
1162  
1262  
1462  
1653  
1653  
1653  
1962  
1962  
959  
1159  
1259  
1459  
1659  
1659  
1659  
1959  
1959  
540  
640  
740  
740  
740  
200  
200  
200  
200  
200  
200  
200  
200  
200  
400  
400  
400  
400  
400  
400  
400  
400  
400  
700  
700  
700  
700  
700  
700  
900  
900  
900  
0-77/8 1-33/4 2- 39/16  
2- 39/16 0-77/8 1-33/4 2- 39/16  
2- 39/16 0-77/8 1-33/4 2- 39/16  
2- 39/16 0-77/8 1-33/4 2- 39/16  
2-119/16 0-77/8 1-33/4 2- 39/16  
940  
0-77/8 1-33/4 2-117/16  
0-77/8 1-33/4 2-117/16  
6-51/8 4-015/16 2- 39/16 0-77/8 1-33/4 2-117/16  
1040  
1040  
1240  
6-51/8 3-415/16 3- 33/8  
Fig. 4 — Service Area Requirements  
5
Table 1 — Physical Data  
UNIT SIZE  
03  
06  
08  
10  
12  
15  
18  
21  
25  
UNIT WEIGHTS (lb)*  
39LA  
39LB  
39LC  
39LD  
39LF  
39LG  
39LH  
200  
150  
170  
230  
230  
120  
220  
280  
210  
238  
322  
322  
168  
308  
411  
308  
349  
472  
472  
246  
452  
470  
352  
400  
540  
540  
282  
517  
540  
405  
459  
621  
621  
324  
594  
620  
465  
527  
713  
713  
372  
682  
695  
521  
590  
799  
799  
417  
764  
740  
555  
629  
851  
851  
444  
814  
820  
615  
697  
943  
943  
492  
902  
COMPONENT WEIGHTS (lb)  
Mixing Box Section  
Filter Mixing Box  
Angle Filter Section  
Flat Filter Section  
139  
150  
75  
164  
173  
82  
193  
208  
97  
219  
227  
107  
50  
226  
245  
114  
55  
244  
279  
134  
74  
283  
327  
140  
75  
272  
340  
159  
86  
311  
395  
185  
90  
37  
43  
48  
Access Section  
48  
55  
60  
64  
68  
74  
77  
87  
92  
Preheat (Water) Section  
Preheat (Electric) Section  
36  
42  
43  
46  
49  
52  
54  
53  
57  
49  
56  
61  
66  
72  
74  
76  
87  
89  
TYPICAL DRY COIL WEIGHTS (lb)  
Large Face Area Cooling Coils,  
1/2-in. OD (Chilled Water & DX)†  
4-Row  
56  
63  
84  
95  
98  
123  
109  
138  
137  
174  
178  
234  
198  
270  
251  
327  
280  
363  
6-Row  
Small Face Area Cooling Coils,  
1/2-in. OD (Chilled Water & DX)†  
4-Row  
6-Row  
8-Row  
45  
53  
61  
72  
85  
92  
91  
113  
129  
105  
129  
143  
133  
162  
189  
161  
197  
228  
182  
225  
263  
211  
270  
324  
238  
307  
377  
1
Hot Water Coils, /2-in. OD†  
1-Row  
2-Row  
19  
28  
34  
43  
38  
51  
48  
61  
58  
76  
62  
89  
77  
104  
86  
117  
95  
130  
Steam Coils, 1-row, 1-in. OD  
6-FPI  
9-FPI  
12-FPI  
50  
55  
60  
70  
80  
85  
85  
100  
115  
95  
115  
130  
110  
125  
145  
135  
155  
180  
150  
175  
205  
180  
214  
248  
215  
256  
297  
FAN  
1
5
5
1
Wheel Diameter (in.)  
Wheel Width (in.)  
Shaft Diameter (in.)  
Maximum Fan Rpm  
9 /2  
12 /8  
12 /8  
15  
15  
15  
18 /8  
20  
20  
18  
25  
1
1
1
1
1
7 /8  
9 /2  
11 /8  
11 /8  
15  
13 /2  
15  
3
3
3
3
7
7
7
11  
3/4  
1 /16  
1 /16  
1 /16  
1 /16  
1 /16  
1 /16  
1 /16  
1
/
16  
2500  
2000  
2000  
1600  
1600  
1400  
1300  
1100  
1000  
OPERATING CHARGE, R-22 (lb)  
4-Row Coil  
1-2  
1-2  
2-3  
2-3  
2-4  
3-5  
3-4  
5-6  
5-6  
4-5  
5-6  
5-7  
4-5  
6-8  
7-9  
5- 6  
8-10  
10-12  
6- 7  
9-11  
12-14  
6- 8  
11-13  
13-19  
6- 9  
11-16  
16-24  
6-Row Coil  
8-Row Coil  
COIL VOLUME (gal. water)  
1
Chilled Water, /2-in. OD Tube,  
Large Face Area  
4-Row  
6-Row  
2.5  
3.2  
3.5  
4.7  
4.5  
6.0  
5.2  
6.8  
5.6  
7.7  
7.3  
10.1  
8.5  
11.7  
10.4  
14.2  
12.0  
16.3  
1
Chilled Water, /2-in. OD Tube,  
Small Face Area  
4-Row  
2.1  
2.4  
2.7  
3.3  
3.7  
4.1  
3.9  
5.1  
6.4  
4.1  
5.9  
7.4  
5.1  
6.6  
8.4  
6.3  
8.3  
10.7  
7.3  
9.5  
12.1  
8.7  
11.8  
14.7  
9.8  
13.5  
17.2  
6-Row  
8-Row  
1
Hot Water, /2-in. OD Tube  
1-Row  
2-Row  
0.5  
0.7  
0.8  
1.3  
1.0  
1.6  
1.3  
2.0  
1.5  
2.4  
1.8  
2.9  
2.1  
3.4  
2.5  
4.0  
2.9  
4.8  
COOLING COILS  
1
Chilled Water /2-in. OD Tube,  
(4, 6 Row) Large Face Area  
Face Area (sq ft)  
3.63  
16  
26.1  
5.90  
20  
34.0  
7.90  
24  
37.9  
9.54  
24  
45.8  
11.18  
24  
53.7  
14.91  
32  
53.7  
17.71  
38  
53.7  
21.6  
38  
65.5  
25.0  
44  
65.5  
Number of Tubes/Face  
Finned Tube Length (in.)  
1
Chilled Water /2-in. OD Tube  
(4, 6, 8 Row) Small Face Area  
Face Area (sq ft)  
2.72  
12  
26.1  
4.72  
16  
34.0  
6.58  
20  
37.9  
7.95  
20  
45.8  
9.32  
20  
53.7  
12.12  
26  
53.7  
13.98  
30  
53.7  
17.1  
30  
65.5  
20.5  
36  
65.5  
Number of Tubes/Face  
Finned Tube Length (in.)  
1
DX /2-in. OD Tube  
(4, 6 Row) Large Face Area  
Face Area (sq ft)  
Finned Tube Length (in.)  
3.63  
26.1  
5.90  
34.0  
7.90  
37.9  
9.54  
45.8  
11.18  
53.7  
14.91  
53.7  
17.71  
53.7  
21.6  
65.5  
25.0  
65.5  
1
DX /2-in. OD Tube  
(4, 6, 8 Row) Small Face Area  
Face Area (sq ft)  
Finned Tube Length (in.)  
2.72  
26.1  
4.72  
34.0  
6.58  
37.9  
7.95  
45.8  
9.32  
53.7  
12.12  
53.7  
13.98  
53.7  
17.1  
65.5  
20.5  
65.5  
HEATING COILS  
1
Hot Water /2-in. OD Tube,  
U-Bend (1, 2 Row)  
Face Area (sq ft)  
Number Tubes/Face  
Finned Tube Length (in.)  
2.72  
12  
26.1  
4.72  
16  
34.0  
6.58  
20  
37.9  
7.95  
20  
45.8  
9.32  
20  
53.7  
12.12  
26  
53.7  
13.98  
30  
53.7  
17.1  
30  
65.5  
20.5  
36  
65.5  
Steam 1-in. OD (1 Row)  
Face Area (sq ft)  
Number Tubes/Face  
Finned Tube Length (in.)  
2.13  
4
25.5  
4.18  
6
33.4  
6.22  
8
37.3  
7.53  
8
45.2  
8.85  
8
53.1  
11.06  
10  
53.1  
13.28  
12  
53.1  
16.2  
12  
53.1  
18.9  
14  
64.9  
LEGEND  
*Less coil.  
†Coils have 14 aluminum fins per inch on copper tubes.  
DX  
Direct Expansion  
FPI — Fins Per Inch  
6
DIFFERENTIAL  
1
H
DRAIN NIPPLE  
FAN OFF  
DIFFERENTIAL  
2
TRAP CONDITION WHEN FAN STARTS  
NOTE: Lift in one piece. Use slings and spreader bars at each lifting  
bracket.  
Fig. 5 — Unit Rigging Details  
COOLING COIL  
DRAIN PAN  
FAN RUNNING AND CONDENSATE DRAINING  
Fig. 7 — Condensate Drain  
Fig. 6 — Unit Support Details  
7
INSTALLATION  
Mixing Box  
DAMPER ACTUATORS — The 39L mixing boxes are sup-  
plied with low leak dampers and blade and edge seals. Damper  
operating torques are shown in Table 2.  
The actuator and mounting brackets are field supplied and  
may be mounted inside or outside the unit. A typical inside  
mounting bracket is shown in Fig. 8. For external mounting of  
actuators, drill or punch a hole in the exterior panel.  
NOTE: If the unit is shipped with AirManager™ controls,  
actuator(s) are factory-supplied. Refer to Table. 3.  
To ensure torque is transmitted equally to both damper sec-  
tions, actuator must be connected to the 1-in. hollow jackshaft  
that drives the interconnecting linkage bar. Connection to any  
other shaft is not recommended.  
DUCTWORK ATTACHMENT — Ductwork should be  
flanged out and attached to the mixing box panels as shown in  
Fig. 9. See Fig. 10 for duct connection sizes.  
Table 2 — Mixing Box Damper Operating Torque  
(in.-lb)  
39L UNIT SIZE  
TORQUE  
03  
06  
08  
10  
12  
15  
18  
21  
25  
20  
20  
26  
29  
33  
41  
52  
56  
76  
MXB — Mixing Box  
NOTES:  
1. Torque values are based on interconnected dampers driven by  
one operator. For units with separate operators for each  
damper, calculate torque as follows: Table values x .80 = torque  
per damper section.  
Fig. 9 — Mixing Box Ductwork Attachment  
2. Damper shaft moves 90 degrees from open to closed position.  
Condensate Drain — Install a trapped condensate drain  
line at unit drain connection. Use 1-in. standard pipe.  
Measure maximum design negative static pressure up-  
stream from the fan. Referring to Fig. 7, height “H” must be  
equal to or larger than negative static pressure at design operat-  
ing conditions. Prime enough water in trap to prevent losing  
seal (Differential 1). When the fan starts, Differential 2 is equal  
to the maximum negative static pressure.  
Provide freeze-up protection as required.  
Fig. 8 — Typical Mixing Box Actuator Mounting  
8
Table 3 — Recommended Actuators  
ROUND  
SHAFT  
SIZE  
MIN-MAX  
(in.)  
DAMPER AREA  
MAXIMUM  
WIRE  
LENGTH  
(ft)  
ACCESSORY  
PACKAGE  
NO.  
(sq ft)  
MAXIMUM  
STROKE  
(degrees)  
ACTUATOR  
PART NO.  
VOLTAGE  
(50/60 Hz)  
TIMING  
(sec)  
TORQUE  
(in.-lb)  
VA  
Parallel Opposed  
33AMACTDMP133  
33AMACTGV-133  
33AMACTGV-266  
HF27BJ035*  
HF27BJ033  
HF27BJ034  
24  
24  
24  
10 .750-1.050  
150  
< 150  
135  
44  
N/A  
N/A  
53  
N/A  
N/A  
133  
133  
266  
90  
90  
90  
300  
725  
450  
4
6
.375- .625  
.475- .750  
3. Damper areas are nominal and based on low leakage type  
dampers.  
4. For larger damper assemblies, multiple activators may be used.  
5. Part No. HF27BB033 and 034 are designed for inlet guide vane  
and face and bypass applications, but may be used for external  
relief dampers if spring return is not required.  
*Actuator is spring-return type.  
NOTES:  
1. All actuators are direct coupled type, designed to be directly  
mounted into jackshaft assembly.  
2. All actuators are equipped with a plenum rated cable, factory-  
terminated to the actuator. Part No. HF27BB035 and 034 are  
16 ft, HF27BB033 is 9.5 ft.  
NOTES:  
1. Hand is determined by the location of the fan drive and/or coil connection when viewed while facing the direction toward which air is flowing.  
2. Dimensions in ( ) are in millimeters.  
DIMENSIONS (ft-in.)  
UNIT  
A
B
C
D
E
F
G
H
J
K
L
39L-  
03  
06  
08  
10  
12  
15  
18  
21  
25  
2- 39/16  
2- 39/16  
2- 39/16  
2- 39/16  
2- 39/16  
2- 39/16  
2-117/16  
2-117/16  
2-117/16  
3-17/8  
3-93/4  
4-111  
4-99/16  
5-57/16  
5-57/16  
5-57/16  
6-51/4  
2-01/4  
2-43/16  
2-81/8  
2-81/8  
2-81/8  
3-4  
3-715  
3-715  
4-313  
1- 5  
1-5  
1-5  
1-5  
1-5  
1-5  
1-9  
2-3  
2-5  
2-5  
0- 15/8  
0- 41/8  
0- 61/16  
0- 61/16  
0- 61/16  
0- 8  
0- 7  
0- 6  
0- 97/8  
0-61/16  
0-61/16  
0-61/16  
0-61/16  
0-61/16  
0-41/16  
0-5  
0-101/2  
0-113/8  
0- 63/8  
0- 85/16  
0- 91/4  
0- 91/4  
0- 91/4  
1- 31/8  
0- 65/8  
1-43/4  
1-811  
1-51/4  
2-11/4  
3-31/4  
3-71/4  
4-11/4  
4-11/4  
4-11/4  
4-11/4  
5-61/4  
1- 51/4  
1- 71/4  
1- 71/4  
1- 71/4  
1- 71/4  
1-111/4  
2- 51/4  
2- 71/4  
2- 71/4  
1-11  
3- 1  
3- 5  
3-11  
3-11  
3-11  
3-11  
5- 4  
/
16  
/
2-05/8  
2-05/8  
2-05/8  
2-81/2  
3-07/16  
3-07/16  
3-85/16  
16  
/
/
/
16  
16  
16  
0-4  
0-4  
6-51/4  
Fig. 10 — Mixing Box Duct Connections  
9
11. If a second actuator is required, repeat the process for a  
second actuator. The second actuator mounts on the op-  
posite side of the fan on the opposite end of the jackshaft.  
ACTUATOR WIRING — To wire the actuator, perform the  
following:  
1. Each actuator is supplied with a length of plenum rated  
cable. Route the cable from the actuator to the exterior of  
the unit. Allow a sufficient service loop to provide free  
movement of the fan sled.  
Inlet Guide Vane (IGV) Actuators — The control  
board positions the unit IGVs in order to maintain the duct stat-  
ic pressure, as measured by the static pressure transducer, at the  
required set point. The IGV actuator is electrically connected to  
the control board and receives a signal whenever the guide  
vane position needs to be adjusted. The guide vane actuator is  
mounted to the IGV jackshaft, and secured to the jackshaft  
mounting member in order to prevent rotation.  
For factory-installed controls which are ordered with the  
unit, the IGV actuator is properly sized and factory mounted to  
the IGV jackshaft. The actuator wiring is routed across the fan  
section to a junction box which is mounted to the exterior of  
the unit. Two compatible actuators are available for field  
installation. Both actuators are supplied with a length of  
plenum rated cable to facilitate installation inside the unit. See  
Table 3 for actuator specifications and typical applications.  
Jackshaft and IGV linkage setup adjustments are extremely  
important for proper IGV performance and static pressure con-  
trol. Closely follow all instructions.  
To install the IGV actuators, perform the following:  
1. Disconnect power to the fan motor prior to performing  
the installation.  
2. At the desired location for field connection, drill a 3/8-in.  
7
hole (two holes within a /8-in. diameter are required if  
two actuators are used) through the unit and route the ca-  
ble through the hole.  
3. Install a field-supplied bushing to protect the cable and  
seal the hole, using a suitable silicone sealer such as  
Form-A-Gasket® by Permatex to secure the cable and  
prevent air leakage.  
4. Remove the center back plug from a field supplied 2 x  
4-in. electrical junction box. Route the cable(s) through  
the hole and secure the box to the unit using 2 field-  
supplied no. 10 drill/tap screws.  
5. Use a 3 or 4-conductor, 18 AWG cable or individual  
18 AWG wiring using RED, WHITE, and BLACK color  
coding to connect the actuator to the control box.  
6. Inside the control box, connect all RED wire(s)  
together. Secure with wire nuts or closed end crimp type  
connectors.  
2. Open the fan access door and locate the IGV jackshaft.  
Measure the IGV jackshaft diameter. Verify that the size  
is within the range of the actuator chosen. See Table 3.  
3. Loosen the U-bolt locking nuts on the actuator.  
4. Slip the actuator over the IGV jackshaft. Align the actua-  
tor parallel with the frame member which supports the  
jackshaft.  
7. Inside the control box, connect all BLACK wire(s) to-  
gether. Secure with wire nuts or closed end crimp type  
connectors.  
5. Take the anti-rotation bracket supplied with the actuator  
and, with the center locking pin pointed outward, slip the  
pin into the slot at the far end of the actuator. Seat the pin  
into the center of the groove provided. If the anti-rotation  
bracket is not seated against the frame member, measure  
the distance from the member and remove the anti-  
rotation bracket from the actuator. Bend the bracket to the  
required offset. See Fig. 11.  
6. With the anti-rotation bracket installed in the actuator  
groove, locate the hole in the bracket, closest to the pin,  
which is fully in contact against the frame. Mark this hole  
location on the frame. Trace the outline of the bracket on  
the frame so that it can be re-aligned again when  
removed.  
8. Inside the control box, connect all WHITE wire(s) to-  
gether. Secure with wire nuts or closed end crimp type  
connectors.  
1
9. At the control box, strip /4-in. of insulation from each  
1
conductor. Equip each conductor with a /4-in. female  
spade type crimp connector.  
10. Connect the RED wire to terminal T37 on the control  
board.  
11. Connect the WHITE wire to terminal T39 on the control  
board.  
12. Connect the BLACK wire to terminal no. 3 on the TB2  
terminal block in the control box.  
7. Remove the bracket and actuator. Drill a pilot hole at the  
location marked from Step 6. Install one screw through  
the hole. Re-align the bracket with the outline made pre-  
viously and tighten the screw.  
13. Check the rotation of the actuator. The switch is factory  
set in the A position which provides clockwise rotation to  
open the IGVs. If counterclockwise rotation is required to  
open the IGVs, reset the actuator switch to the B position.  
8. Locate and mark the hole on the opposite end of the  
bracket, closest to the pin, which contacts the frame. Drill  
a pilot hole in this location and install the remaining  
screw. Remove the first screw.  
9. Install the actuator on the jackshaft and while moving  
into position, adjust the free end of the anti-rotation  
bracket so that the pin fully locks into the slot provided in  
the actuator. Once the actuator is adjusted into position,  
install the remaining screw into the anti-rotation bracket.  
See Fig. 12.  
To adjust the jackshaft linkage, perform the following:  
1. Refer to Fig. 12. Close the IGVs fully.  
2. Loosen the crankarm and rods. Press the release button  
on the actuator and rotate it to the .9 mark for right hand  
units or the .1 mark for left hand units. Rotate the crank-  
arm on the jackshaft to a position which is about 30 de-  
grees from parallel alignment with the rod connecting the  
IGV.  
3. Tighten the crankarm into this position.  
4. Close the IGVs fully by hand. Tighten the rod into  
position.  
10. Rotate the jackshaft to fully close the IGVs. Press the  
release button (BLACK) on the face of the actuator, and  
rotate the clamp in the same direction that closed the  
IGVs, until the actuator stop is reached. With the release  
still pressed, rotate the actuator clamp from the full closed  
position to the .1 mark and release the actuator release  
button. Lock the U-bolt clamp into position to secure the  
actuator to the IGV jackshaft.  
5. Test the actuator and IGV operation. Be sure the IGVs  
fully close and open. Re-adjust the position of the swivel  
joint outward if full IGV travel is not reached with the  
actuator 90 degree rotation. If the IGVs reach the end of  
full travel in less than 90 degrees of actuator rotation,  
adjust the swivel joint inward toward the jackshaft. After  
making any adjustment, repeat Steps 2-5.  
10  
ANTIROTATION STRAP  
INSTALLED (ACTUATOR  
NOT SHOWN FOR  
CLARITY)  
JACKSHAFT  
CRANKARM  
Fig. 11 — IGV Actuator Bracket Installation  
CONNECTING ROD  
IGV ACTUATOR  
ANTIROTATION  
STRAP  
IGV  
JACKSHAFT  
INLET GUIDE  
VANES (IGV)  
Fig. 12 — IGV Actuator Mounting  
supply air; thus, condensate can form inside the junction box  
and, possibly, on the live terminal lugs.  
To prevent the moist air from migrating through the conduit  
to the motor, seal the power wires inside the flexible conduit at  
the motor starter or fused disconnect.  
Use a nonconductive, nonhardening sealant. Permagum  
(manufactured by Schnee Morehead) or sealing compound,  
thumb grade (manufactured by Calgon), are acceptable  
materials.  
POWER KNOCKOUTS — Panels are not provided with  
knockouts for the fan motor power wiring. Openings must be  
drilled or punched in the exterior panels of the unit. It is recom-  
mended that power wiring be routed through the discharge  
panel whenever possible, as this panel is rarely removed for  
service access.  
Install Fan Motor — For field installation of motors, be  
sure electrical junction box is toward the center of the unit.  
This is necessary for drive and belts to be properly tightened.  
Use smallest slots in motor mounting base that will accommo-  
date motor and allow minimum overhang (Fig. 13). Be sure  
that motor holddown bolts are tight on field-installed motor.  
JUNCTION BOX CONDENSATE PREVENTION — When  
air handlers are installed outdoors in a high humidity environ-  
ment or indoors where the apparatus room is used as a fresh air  
plenum, precautions must be taken to prevent condensation  
from forming inside the junction box of the internally mounted  
motor.  
Standard installation practice is to mount the motor starter  
or fused disconnect box adjacent to the air handler and enclose  
the power wiring to the motor in flexible conduit.  
The sheet metal housing of the disconnect switch or motor  
starter is not airtight (even when a box meeting NEMA  
[National Electrical Manufacturers Association] IV standards  
is used). Thus, warm moist air can migrate through the flexible  
conduit to the junction box on the motor. With the motor  
located inside the unit, the motor temperature is that of the cool  
Install Sheaves on Motor and Fan Shafts —  
Factory-supplied drives are prealigned and tensioned, however,  
Carrier recommends that you check the belt tension and align-  
ment before starting the unit. Always check the drive align-  
ment after adjusting belt tension.  
11  
When field installing or replacing sheaves, install sheaves  
on fan shaft and motor shaft for minimum overhang. (See  
Fig. 13.) Use care when mounting sheave on fan shaft; too  
much force may damage bearing. Remove rust-preventative  
coating or oil from shaft. Make sure shaft is clean and free of  
burrs. Add grease or lubricant to bore of sheave before  
installing.  
The 39L fan, shaft, and drive pulley are balanced as a com-  
plete assembly to a high degree of accuracy. If excessive unit  
vibration is present after fan pulley replacement, the unit must  
be rebalanced. For drive ratio changes, always reselect the mo-  
tor pulley — do not change the fan pulley.  
3. Rotating each sheave a half revolution will determine  
whether the sheave is wobbly or the drive shaft is bent.  
Correct any misalignment.  
4. With sheaves aligned, tighten cap screws evenly and  
progressively.  
1
1
NOTE: There should be a /8-in. to /4-in. gap between  
the mating part hub and the bushing flange. If gap is  
closed, the bushing is probably the wrong size.  
5. With taper-lock bushed hubs, be sure the bushing bolts  
are tightened evenly to prevent side-to-side pulley wob-  
ble. Check by rotating sheaves and rechecking sheave  
alignment. When substituting field-supplied sheaves for  
factory-supplied sheaves, consider that the fan shaft  
sheave has been factory balanced with fan and shaft as an  
assembly. For this reason, substitution of motor sheave is  
prefer-able for final speed adjustment.  
ALIGNMENT — Make sure that fan shafts and motor shafts  
are parallel and level. The most common causes of mis-  
alignment are nonparallel shafts and improperly located  
sheaves. Where shafts are not parallel, belts on one side are  
drawn tighter and pull more than their share of the load. As a  
result, these belts wear out faster, requiring the entire set to be  
replaced before it has given maximum service. If misalignment  
is in the sheave, belts will enter and leave the grooves at an  
angle, causing excessive belt cover and sheave wear.  
Install V-Belts — When installing or replacing belts, al-  
ways use a complete set of new belts. Mixing old and new belts  
will result in the premature wear or breakage of the newer  
belts.  
1. Always adjust the motor position so that V-belts can be  
installed without stretching over grooves. Forcing belts  
can result in uneven stretching and a mismatched set of  
belts.  
2. Do not allow belt to bottom out in sheave.  
3. Tighten belts by turning motor-adjusting jackscrews.  
Turn each jackscrew an equal number of turns.  
4. Equalize belt slack so that it is on the same side of belt for  
all belts. Failure to do so may result in uneven belt  
stretching.  
5. Tension new drives at the maximum deflection force  
recommended (Fig. 15).  
1. Shaft alignment can be checked by measuring the  
distance between the shafts at 3 or more locations. If the  
distances are equal, then the shafts will be parallel.  
2. Sheave alignment:  
Fixed sheaves — To check the location of the fixed  
sheaves on the shafts, a straightedge or a piece of string  
can be used. If the sheaves are properly lined up the string  
will touch them at the points indicated by the arrows in  
Fig. 14.  
Adjustable sheave — To check the location of adjustable  
sheave on shaft, make sure that the centerlines of both  
sheaves are in line and parallel with the bearing support  
channel. See Fig. 14. Adjustable pitch drives are installed  
on the motor shaft.  
With adjustable sheave, do not exceed maximum fan rpm.  
Fig. 13 — Determining Sheave-Shaft Overhang  
12  
DEFLECTION FORCE — LB  
SMALL  
SHEAVE  
PD RANGE  
(in.)  
BELT  
CROSS  
SECTION  
Super  
Belts  
Notch  
Belts  
SteelCable  
Belts  
Min Max Min Max Min Max  
3.0- 3.6  
3.8- 4.8  
5.0- 7.0  
3.4- 4.2  
4.4- 5.6  
5.8- 8.6  
7.0- 9.4  
9.6-16.0  
2.65-3.65  
4.12-6.90  
4.40-6.70  
7.1-10.9  
11.8-16.0  
12.5-17.0  
18.0-22.4  
3
31/2  
4
41/4 37/8 51/2  
3
4
A
B
5
51/2  
51/2 53/4  
41/2 61/4 33/4  
67/8 41/4  
41/2  
43/4  
51/4  
51/2  
71/4  
83/4  
5
4
8
51/8 71/8 61/2 91/8 53/4  
63/8 83/4 73/8 101/8  
7
111/4 143/8 133/4 177/8 111/4 14  
141/8 181/2 151/4 201/4 141/4 173/4  
C
31/2  
43/4 67/8 51/4 77/8  
10 15  
101/2 153/4 127/8 183/4  
5
37/8 51/2  
3V  
Fig. 14 — Sheave Alignment  
5V  
8V  
13  
27  
30  
191/2 15  
22  
6. To determine correct belt tension, use the deflection  
formula given below and the tension data from Fig. 15 as  
follows:  
401/2  
45  
PD — Pitch Diameter, inches  
EXAMPLE:  
Given  
Fig. 15 — Fan Belt Tension Data  
Belt Span  
Belt Cross-Section A, Super Belt  
Small Sheave PD 5 in.  
(Belt Span)  
16 in.  
NOTICE  
TENSION BELTS TO SPECIFICATION  
SHOWN ON DRIVE LABEL. OVER  
TENSIONING BELTS WILL SEVERELY  
REDUCE BELT AND BEARING LIFE.  
Deflection =  
64  
Solution  
1. From Fig. 15 find that deflection force for type A, super  
belt with 5-in. small sheave PD is 4 to 51/2 lb.  
REPLACEMENT PARTS  
2.  
16  
Deflection =  
64  
BEARINGS  
DRIVE _______________________  
3. Increase or decrease belt tension until force required for  
1/4-in. deflection is 51/2 lb.  
FREE ________________________  
SHAFT ________________________  
WHEEL ________________________  
INLET CONE ____________________  
Check belt tension at least twice during first operating  
day. Readjust as required to maintain belt tension within  
the recommended range.  
With correct belt tension, belts may slip and squeal  
momentarily on start up. This slippage is normal and disap-  
pears after unit reaches operating speed. Excessive belt tension  
shortens belt life and may cause bearing and shaft damage.  
TO ORDER REPLACEMENT PARTS,  
CONTACT: RCD  
(REPLACEMENT COMPONENTS DIVISION)  
1-800-443-4410  
After run-in, set belt tension at lowest tension at which belts  
will not slip during operation.  
Record information on the label (Fig. 16) found on the door  
of the fan section.  
Fig. 16 — Fan Section Label  
13  
Note the horizontal location of the 15-degree check valve,  
and the orientation of the gate/pivot. This valve is intended to  
relieve any vacuum forming in the condensate outlet of a  
condensing steam coil, and to seal this port when steam  
pressure is again supplied to the coil. It must not be installed in  
any other position, and should not be used in the supply line.  
Water and Steam Coil Piping Recommendations  
GENERAL — Use straps around the coil casing or the lifting  
holes (see Fig. 17) to lift and place the coil.  
For coils used in tempering service, or to preheat outside air,  
install an immersion thermostat in the condensate line ahead of  
the trap. This will shut down the supply fan and close the out-  
door damper whenever the condensate falls to a predetermined  
point, perhaps 120 F.  
To prevent damage to the coil or coil headers: Do not use  
the headers to lift the coil. Support the piping and coil con-  
nections independently. Do not use the coil connections to  
support piping. When tightening coil connections, use a  
backup wrench on the nozzles.  
NOTE: Do NOT use an immersion thermostat to override a  
duct thermostat and open the steam supply valve.  
For vacuum return systems, the vacuum breaking check  
valve would be piped into the condensate line between the trap  
and the gate valve instead of open to the atmosphere.  
Figure 19 illustrates the typical piping at the end of every  
steam supply main. Omitting this causes many field problems  
and failed coils.  
Figure 20 shows the typical field piping of multiple coils.  
Use this only if the coils are the same size and have the same  
pressure drop. If this is not the case, an individual trap must be  
provided for each coil.  
Piping practices are outlined in the Carrier System Design  
Manual, Part 3, Piping Design. See Tables 4-6 for circuiting data.  
WATER COILS — Typically, coils are piped by connecting  
the supply at the bottom and the return at the top. See Fig. 17.  
This is not always the case, especially if the coil hand has been  
changed in the field. Coils must be piped for counterflow; oth-  
erwise, a capacity reduction of 5% for each coil row will result.  
To ensure counterflow, chilled water coils are piped so that the  
coldest water meets the coldest air. Hot water coils are piped so  
that the warmest water meets the warmest air.  
STEAM COILS — Position the steam supply connection at  
the top of the coil, and the return (condensate) connection at the  
bottom. The coil tubes must incline downwards toward  
the return header connection for condensate drainage. See  
Fig. 18-22.  
Figure 21 shows a multiple coil arrangement applied to a  
gravity return, including the open air relief to the atmosphere,  
which DOES NOT replace the vacuum breakers.  
Figure 22 illustrates the basic condensate lift piping.  
Following the piping diagrams in Fig. 18-22, make all con-  
nections while observing the following precautions:  
Figure 18 illustrates the normal piping components and the  
suggested locations for high, medium, or low-pressure steam  
coils. The low-pressure application (zero to 15 psig) can  
dispense with the ¼-in. petcock for continuous venting located  
above the vacuum breaker (check valve).  
Install a drip line and trap on the pressure side of the  
inlet control valve. Connect the drip line to the return  
line downstream of the return line trap.  
To prevent scale or foreign matter from entering the con-  
3
trol valve and coil, install a /32-in. mesh strainer in the  
steam supply line upstream from the control valve.  
Provide air vents for the coils to eliminate noncondens-  
able gases.  
Select a control valve according to the steam load, not  
the coils supply connection size. Do not use an oversized  
control valve.  
Do not use bushings that reduce the size of the header  
return connection. The return connection should be the  
same size as the return line and reduced only at the  
downstream trap.  
To lift condensate above the coil return line into over-  
head steam mains, or pressurized mains, install a pump  
and receiver between the condensate trap and the  
pressurized main. Do not try to lift condensate with  
modulating or on-and-off steam control valves. Use only  
15-degree check valves, as they open with a lower water  
head. Do not use 45-degree or vertical-lift check valves.  
Use float and thermostatic traps. Select the trap size  
according to the pressure difference between the steam  
supply main and the return main.  
Load variations can be caused by uneven inlet air distri-  
bution or temperature stratification.  
Drain condensate out of coils completely at the end of  
the heating season to prevent the formation of acid.  
Coil Freeze-Up Protection  
WATER COILS — If a chilled water coil is applied with out-  
side air, provisions must be made to prevent coil freeze-up.  
Install a coil freeze-up thermostat to shut down the system if  
any air temperature below 36 F is encountered entering the  
water coil. Follow thermostat manufacturer’s instructions.  
Fig. 17 — Coil Connections and Lifting Points  
14  
When a water coil is applied downstream of a direct-  
expansion (DX) coil, a freeze-up thermostat must be installed  
between the DX and water coil and electrically interlocked to  
turn off the cooling to prevent freeze-up of the water coil.  
Variation in load on different coils in the same bank may  
be caused by several factors. Two of the most common  
are uneven airflow distribution across the coil and stratifi-  
cation of inlet air across the coil.  
For outdoor-air application where intermittent chilled water  
coil operation is possible, one of the following steps should be  
taken:  
8. Do not try to lift condensate above the coil return into an  
overhead main, or drain into a main under pressure with a  
modulating or on/off steam control valves. A pump  
and receiver should be installed between the coil conden-  
sate traps and overhead mains and return mains under  
pressure.  
9. Use a strainer (3/32-in. mesh) on the steam supply side,  
as shown in the piping diagrams, to avoid collection of  
scale or other foreign matter in the inner tube distributing  
orifices.  
Install an auxiliary blower heater in cabinet to maintain  
above-freezing temperature around coil while unit is  
shut down.  
Drain coils and fill with an ethylene glycol solution suit-  
able for the expected cold weather operation. Shut down  
the system and drain coils. See Service section, Winter  
Shutdown, page 30.  
NOTE: IDT coils must be installed with the tubes draining  
toward the header end of the coil. Carrier's IDT steam coils  
are pitched toward the header end as installed in the unit.  
10. Ensure the AHU (air-handling unit) is installed level to  
maintain the inherent slope. Also ensure the unit is in-  
stalled high enough to allow the piping to be installed cor-  
rectly, especially the traps which require long drip legs.  
11. Do not fail to provide all coils with the proper air vents to  
eliminate noncondensable gasses.  
12. Do not support steam piping from the coil units. Both  
mains and coil sections should be supported separately.  
IDT Steam Coil Installation — Refer to drawings to position  
the coils properly with regard to the location of the supply and  
return connections. Ensure that the IDT coil is pitched with the  
tubes draining toward the header. Carrier’s AHUs provide  
proper coil pitch when the AHU is installed level.  
Refer to schematic piping diagrams and piping connection  
notes for the recommended piping methods.  
STEAM COILS — When used for preheating outdoor air in  
pressure or vacuum systems, an immersion thermostat to con-  
trol outdoor-air damper and fan motor is recommended. This  
control is actuated when steam supply fails or condensate tem-  
perature drops below an established level, such as 120 to 150 F.  
A vacuum breaker should also be used to equalize coil pressure  
with the atmosphere when steam supply throttles close. Steam  
should not be modulated when outdoor air is below 40 F.  
On low-pressure and vacuum steam-heating systems, the  
thermostat may be replaced by a condensate drain with a ther-  
mal element. This element opens and drains the coil when con-  
densate temperature drops below 165 F. Note that condensate  
drains are limited to 5 psig pressure.  
INNER DISTRIBUTING TUBE STEAM COILS — The  
inner distributing tube (IDT) steam coil used in the Carrier  
39M air-handling units has an inner tube pierced to facilitate  
the distribution of the steam along the tube's length. The outer  
tubes are expanded into plate fins. The completed assembly  
includes the supply and condensate header and side casings  
which are built to slant the fin/tube bundle back toward the  
condensate header. The slanting of the assembly ensures that  
condensate will flow toward the drains. This condensate must  
be removed through the return piping to prevent premature  
failure of the coil. The fin/tube bundle is slanted vertically for  
horizontal airflow coils, and horizontally for vertical air-  
flow coils.  
IDT Steam Coil Piping — The following piping guidelines  
will contribute to efficient coil operation and long coil life:  
1. Use full size coil outlets and return piping to the steam  
trap. Do not bush return outlet to the coil. Run full size to  
the trap, reduce at the trap.  
2. Use float and thermostatic (F & T) traps only for conden-  
sate removal. Trap size selection should be based on the  
difference in pressure between the steam supply main and  
the condensate return main. It is good practice to select a  
trap with 3 times the condensate rating of the coil to  
which it is connected.  
3. Use thermostatic traps for venting only.  
1
4. Use only /2-in., 15-degree swing check valves installed  
horizontally, piped open to atmosphere, and located at  
least 12 in. above the condensate outlet. Do not use  
45-degree, vertical lift and ring check valves.  
NOTES:  
5. The supply valve must be sized for the maximum antici-  
pated steam load.  
6. Do not drip steam mains into coil sections. Drip them on  
the pressure side of the control valve and trap them into  
the return main beyond the trap for the coil.  
1. Flange or union is located to facilitate coil removal.  
2. Flash trap may be used if pressure differential between steam  
and condensate return exceeds 5 psi.  
3. When a bypass with control is required.  
4. Dirt leg may be replaced with a strainer. If so, tee on drop can  
be replaced by a reducing ell.  
5. The petcock is not necessary with a bucket trap or any trap  
which has provision for passing air. The great majority of high  
or medium pressure returns end in hot wells or deaerators  
which vent the air.  
7. Do not use a single trap for two or more coils installed in  
series. Where two or more coils are installed in a single  
bank, in parallel, the use of a single trap is permissible,  
but only if the load on each coil is equal. Where loads in  
the same coil bank vary, best practice is to use a separate  
trap for each coil.  
Fig. 18 — Low, Medium or  
High Pressure Coil Piping  
15  
NOTES:  
1. A bypass is necessary around trap and valves when continu-  
ous operation is necessary.  
2. Bypass to be the same size as trap orifice but never less than  
1/2 inch.  
Fig. 19 — Dripping Steam Supply to  
Condensate Return  
NOTES:  
1. Flange or union is located to facilitate coil removal.  
2. When control valve is omitted on multiple coils in parallel air  
flow.  
3. When a bypass with control is required.  
4. Coils with different pressure drops require individual traps. This  
is often caused by varying air velocities across the coil bank.  
Fig. 21 — Multiple Coil Low Pressure  
Piping Gravity Return  
NOTES:  
1. Flange or union is located to facilitate coil removal.  
2. When a bypass with control is required.  
3. Flash trap can be used if pressure differential between supply  
and condensate return exceeds 5 psi.  
4. Coils with different pressure drops require individual traps. This  
is often caused by varying air velocities across the coil bank.  
5. Dirt leg may be replaced with a strainer. If so, tee on drop can  
be replaced by a reducing ell.  
6. The petcock is not necessary with a bucket trap or any trap  
which has provision for passing air. The great majority of high  
pressure return mains terminate in hot wells or deaerators  
which vent the air.  
NOTES:  
1. Flange or union is located to facilitate coil removal.  
2. To prevent water hammer, drain coil before admitting steam.  
3. Do not exceed one foot of lift between trap discharge and  
return main for each pound of pressure differential.  
4. Do not use this arrangement for units handling outside air.  
Fig. 20 — Multiple Coil High Pressure Piping  
Fig. 22 — Condensate Lift to Overhead Return  
16  
Refrigerant Piping, Direct-Expansion (DX)  
Coils (Fig. 23) — Direct-expansion coils are divided into  
2 or 4 splits depending upon the unit size and coil circuiting.  
See Table 7 for coil circuiting data. Each split requires its own  
distributor nozzle, expansion valve, and suction piping. Suction  
connections are on the air entering side when the coil is proper-  
ly installed. Matching distributor connections for each coil split  
are on the air leaving side. See unit label or certified drawing to  
assure connection to matching suction and liquid connections.  
See Table 8 for distributor part numbers.  
Direct-expansion coils are shipped pressurized with dry  
air. Release pressure from each coil split through valves in  
protective caps before removing caps.  
Do not leave piping open to the atmosphere unnecessar-  
ily. Water and water vapor are detrimental to the refrigerant  
system. Until the piping is complete, recap the system and  
charge with nitrogen at the end of each workday. Clean all  
piping connections before soldering joints.  
The lower split of face split coils should be first on, last  
off.  
Fig. 23 — Typical Direct-Expansion  
Row Split Coil  
Row split coils utilize special intertwined circuits (as  
shown in Fig. 23); either split of these row split coils can be  
first on, last off.  
Table 4 — Hot Water Coil Circuiting Data  
39L UNIT SIZE  
03  
06  
08  
10  
12  
15  
18  
21  
25  
No. of Circuits  
1-ROW  
2-ROW  
H
6
6
12  
8
8
16  
10  
10  
20  
10  
10  
20  
10  
10  
20  
13  
13  
26  
15  
15  
30  
15  
15  
30  
13  
13  
36  
H
F
LEGEND  
NOTE: All hot water coils have 11/2-in. MPT.  
F
H
Full Circuit  
Half Circuit  
Table 5 — Chilled Water Coil Circuiting Data  
LARGE FACE AREA (39LA, 39LD)  
UNIT SIZE  
03  
06  
08  
Face Area (sq ft)  
7.90  
10  
12  
COIL  
TYPE  
CIRCUIT  
3.63  
5.90  
9.54  
11.18  
No.  
Circuits  
Connection  
No.  
Circuits  
Connection  
No.  
Circuits  
Connection  
Size  
No.  
Circuits  
Connection  
No.  
Circuits  
Connection  
Size  
Size  
Size  
Size  
Q
H
F
4
8
11/2  
11/2  
11/2  
11/2  
11/2  
5
10  
20  
10  
20  
11/2  
11/2  
11/2  
11/2  
11/2  
12  
24  
12  
24  
36  
11/2  
21/2  
11/2  
21/2  
21/2  
12  
24  
12  
24  
36  
11/2  
21/2  
11/2  
21/2  
21/2  
12  
24  
12  
24  
36  
11/2  
21/2  
11/2  
21/2  
21/2  
4-ROW  
6-ROW  
16  
D
H
F
D
8
16  
LARGE FACE AREA (39LA, 39LD)  
UNIT SIZE  
15  
18  
21  
21.60  
25  
COIL  
TYPE  
Face Area (sq ft)  
17.71  
CIRCUIT  
14.91  
25.00  
No.  
Circuits  
Connection  
Size  
No.  
Circuits  
Connection  
Size  
No.  
Circuits  
Connection  
No.  
Circuits  
Connection  
Size  
Size  
Q
H
F
16  
32  
16  
32  
48  
11/2  
21/2  
11/2  
21/2  
21/2  
19  
38  
19  
38  
57  
11/2  
21/2  
11/2  
21/2  
21/2  
19  
38  
76  
19  
38  
57  
22  
44  
88  
44  
66  
11/2  
21/2  
21/2  
11/2  
21/2  
21/2  
4-ROW  
6-ROW  
D
H
F
D
11/2  
21/2  
21/2  
21/2  
21/2  
LEGEND  
NOTES:  
1. Connection sizes are MPT — inches.  
2. Sizes 21-25 have 2 coils.  
D
F
H
Q
Double Circuit  
Full Circuit  
Half Circuit  
Quarter Circuit  
17  
Table 5 — Chilled Water Coil Circuiting Data (cont)  
SMALL FACE AREA (39LB, 39LC, 39LF)  
UNIT SIZE  
03  
06  
08  
Face Area (sq ft)  
6.58  
10  
12  
COIL  
TYPE  
CIRCUITING  
2.72  
4.72  
7.95  
9.23  
No.  
Circuits  
Connection  
No.  
Circuits  
Connection  
No.  
Circuits  
Connection  
Size  
No.  
Circuits  
Connection  
No.  
Circuits  
Connection  
Size  
Size  
Size  
Size  
Q
H
F
3
6
12  
11/2  
11/2  
11/2  
4
8
16  
11/2  
11/2  
11/2  
10  
20  
11/2  
21/2  
10  
20  
11/2  
21/2  
10  
20  
11/2  
21/2  
4-ROW  
D
H
F
D
6
12  
11/2  
11/2  
8
16  
11/2  
11/2  
10  
20  
30  
11/2  
21/2  
21/2  
10  
20  
30  
11/2  
21/2  
21/2  
10  
20  
30  
11/2  
21/2  
21/2  
6-ROW  
H
F
D
6
12  
11/2  
11/2  
8
16  
11/2  
11/2  
10  
20  
40  
11/2  
21/2  
21/2  
10  
20  
40  
11/2  
21/2  
21/2  
10  
20  
40  
11/2  
21/2  
21/2  
8-ROW*  
SMALL FACE AREA (39LB, 39LC, 39LF)  
UNIT SIZE  
18  
15  
21  
25  
COIL  
TYPE  
Face Area (sq ft)  
CIRCUITING  
12.12  
13.98  
17.10  
20.50  
No.  
Circuits  
Connection  
No.  
Circuits  
Connection  
No.  
Circuits  
Connection  
Size  
No.  
Circuits  
Connection  
Size  
Size  
Size  
Q
H
F
13  
26  
11/2  
21/2  
15  
30  
11/2  
21/2  
15  
30  
60  
18  
36  
72  
11/2  
21/2  
21/2  
11/2  
21/2  
21/2  
4-ROW  
D
H
F
D
13  
26  
39  
11/2  
21/2  
21/2  
15  
30  
45  
11/2  
21/2  
21/2  
15  
30  
45  
11/2  
21/2  
21/2  
36  
54  
11/2  
21/2  
21/2  
6-ROW  
H
F
D
13  
26  
52  
11/2  
21/2  
21/2  
13  
30  
60  
11/2  
21/2  
21/2  
30  
60  
11/2  
21/2  
21/2  
36  
72  
11/2  
21/2  
21/2  
8-ROW*  
LEGEND  
D
F
Double Circuit  
Full Circuit  
Half Circuit  
H
Q — Quarter Circuit  
*Not available on 39LB units.  
NOTE: Connection sizes are MPT - inches.  
Table 6 — Steam Coil Connection Sizes  
39L UNIT SIZE  
03-25  
FACE AREA  
COIL TYPE  
CIRCUITING  
CONNECTION  
CONNECTION SIZE  
Inlet  
21/2  
Small  
1-Row  
F
Outlet  
11/2  
LEGEND  
F
Full Circuit  
NOTE: Connection sizes are MPT - inches.  
18  
SUCTION PIPING — Connect suction piping as shown in  
Fig. 24 for face split coil or Fig. 25 for row split coil.  
Suction line from coil connection to end of the 15-diameter-  
long riser should be same tube size as coil connection to ensure  
proper refrigerant velocity.  
Refer to Carrier System Design Manual, Part 3, and size re-  
maining suction line to compressor for a pressure drop equiva-  
lent to 2.0 F. This will provide a total suction line header pres-  
sure drop equivalent to approximately 2.5 F. Refer to Fig. 26  
for piping risers to the compressor.  
To minimize the possibility of flooded starts and compres-  
sor damage during prolonged light load operation, install an ac-  
cumulator in the suction line or a solenoid in the liquid line of  
last-on, first off split in row-split applications.  
EXPANSION VALVE PIPING — Distributor nozzles sized  
for acceptable performance for a range of conditions are facto-  
ry supplied. Use the AHU (Air-Handling Unit) selection pro-  
gram in the Carrier electronic catalog to select optimal nozzle  
sizes. Replace factory nozzle as necessary for best perfor-  
mance. See Fig. 27.  
Thermostatic expansion valves are field supplied. See  
Fig. 27.  
NOTE: Be sure that correct nozzle is installed in each distribu-  
tor before installing expansion valve. Before installing field-  
supplied nozzles, remove nozzle retainer rings and factory-  
installed minimum-sized nozzles from distributors.  
TXV — Thermostatic Expansion Valve  
Fig. 24 — Face Split Coil Suction Line Piping  
Install expansion valve (Fig. 27) as follows:  
1. Wrap wet cloths around valve body to prevent excessive  
heat from reaching diaphragm and internal parts. Do not  
allow water to enter system. Disassemble expansion  
valve before soldering, if accessible, for easy reassembly.  
Use 95-5 tin-antimony soft solder.  
2. Solder expansion valve outlet directly to distributor un-  
less:  
a. An adapter bushing or coupling is supplied by the  
factory (solder adapter to distributor first, then to  
expansion valve).  
b. Hot gas bypass is required. (See Hot Gas Bypass  
section, below.)  
3. Solder expansion valve equalizer line to suction line and  
locate control bulb on suction line as in Fig. 24 or 25.  
4. Insulate expansion valve body, diaphragm assembly and  
control bulb area to prevent charge migration and exces-  
sive condensation.  
5. Install filter drier ahead of expansion valve to ensure sat-  
isfactory valve operation.  
TXV — Thermostatic Expansion Valve  
Fig. 25 — Row Split Coil Suction Line Piping  
HOT GAS BYPASS — When low-load operation requires  
use of hot gas bypass, hot gas must be introduced between ex-  
pansion valve and distributor. See Table 9.  
Install hot gas bypass connector (Fig. 28) in coil split that is  
first on, last off as follows:  
1. Remove distributor nozzle and retainer ring (area A) from  
distributor and reinstall in inlet (area B) of side connector.  
2. Solder side connector outlet to distributor inlet, using  
silver solder or equivalent with 1300 to 1500 F melt  
temperature.  
3. Silver-solder expansion valve outlet to side connector  
inlet.  
4. If required, install factory-supplied adapter bushing or  
coupling to connector inlet before soldering to expansion  
valve outlet.  
Fig. 26 — Suction Line Riser Piping  
19  
Table 7 — Direct Expansion Coil Circuiting Data  
LARGE FACE AREA (39LA, 39LD)  
UNIT SIZE  
CIRCUITING TYPE  
03  
Half  
06  
Half  
08  
Half  
10  
Half  
12  
Qtr  
Full  
Qtr  
Full  
Qtr  
Full  
Qtr  
Full  
Half  
Full  
CFM AT 550 FPM  
FACE AREA (sq ft)  
TUBE FACE  
1996  
3.63  
16  
3245  
5.90  
20  
4345  
7.90  
24  
5247  
9.54  
24  
6149  
11.18  
24  
TUBE LENGTH (in.)  
26.1  
34.0  
37.9  
45.8  
53.7  
NUMBER OF CIRCUITS  
4
8
16  
10  
20  
12  
24  
12  
24  
12  
24  
NUMBER OF TXVs  
NUMBER OF CIRCUITS/TXV†  
SUCTION CONNECTIONS  
(in. OD)  
DISTRIBUTOR CONNECTIONS  
(in. OD)  
2
2
2
4
11/8  
2
8
13/8  
2
5
11/8  
2
2
6
11/8  
2
2
6
11/8  
2
2
6
11/8  
2
10  
12  
12  
12  
7
/
13/8  
15/8  
15/8  
15/8  
8
7
7
7
7
7
7
/
/
11/8  
/
11/8  
/
15/8  
/
15/8  
/
11/8  
8
8
8
8
8
8
4-ROW COIL  
Circuit Equivalent Length (ft)  
Distributor Tube Length (in.)  
Face Split  
52  
26  
32  
34  
18  
40  
20  
45  
23  
11  
13  
2
11  
15  
2
11  
16  
3
13  
18  
4
15  
18  
4
13  
18  
5
15  
18  
5
13  
18  
6
15  
18  
6
Row Split  
Distributor Nozzle Size**  
6-ROW COIL  
Circuit Equivalent Length (ft)  
Distributor Tube Length (in.)  
Face Split  
39  
20  
47  
24  
51  
26  
59  
30  
67  
34  
11  
15  
2
11  
16  
3
11  
16  
3
13  
18  
3
13  
18  
4
15  
21  
4
13  
18  
5
15  
21  
5
13  
18  
6
15  
21  
6
Row Split  
Distributor Nozzle Size**  
LARGE FACE AREA (39LA, 39LD)  
18 21  
Full  
UNIT SIZE  
CIRCUITING TYPE  
15  
25  
Full  
Half  
Full  
Half  
Full  
Half  
Double  
Half  
Double  
CFM AT 550 FPM  
FACE AREA (sq ft)  
TUBE FACE  
8200  
9740  
17.71  
38  
11,880  
21.6  
38  
13,750  
25.0  
22U-22L  
65.5  
14.91  
32  
TUBE LENGTH (in.)  
53.7  
53.7  
65.5  
NUMBER OF CIRCUITS  
16  
32  
19  
2
38  
19  
38  
22  
44  
88  
NUMBER OF TXVs  
NUMBER OF CIRCUITS/TXV†  
SUCTION CONNECTIONS  
(in. OD)  
DISTRIBUTOR CONNECTIONS  
(in. OD)  
2
8
13/8  
4*  
8
13/8  
4*  
9-10  
13/8  
2
9-10  
13/8  
4*  
9-10  
11/8  
2
2
2
2
4
4
11  
15/8  
9-10  
13/8  
5-6  
5-6  
11  
11  
11  
11/8  
11/8  
13/8  
13/8  
15/8  
7
7
11/8  
11/8  
11/8  
11/8  
11/8  
11/8  
/
/
13/8  
13/8  
13/8  
13/8  
8
8
4-ROW COIL  
Circuit Equivalent Length (ft)  
Distributor Tube Length (in.)  
Face Split  
45  
23  
45  
23  
54  
26  
54  
54  
26  
26  
15  
26  
8
16  
16  
4
16  
28  
10  
16  
16  
5
16  
28  
10  
163/4  
163/4  
5
12  
21  
8
12  
21  
8
15  
23  
5
15  
23  
5
Row Split  
Distributor Nozzle Size**  
6-ROW COIL  
Circuit Equivalent Length (ft)  
Distributor Tube Length (in.)  
Face Split  
67  
34  
67  
34  
81  
40  
40  
40  
15  
23  
8
16  
16  
4
16  
28  
10  
18  
18  
5
16  
28  
10  
181/2  
181/2  
5
15  
22  
5
15  
22  
5
Row Split  
Distributor Nozzle Size**  
LEGEND  
**Factory-supplied distributors have factory-selected nozzle sizes  
shown. If necessary, replace factory-supplied nozzles with field-  
supplied and installed nozzles. Consult Electronic Catalog AHU  
selection program for correct nozzle selection.  
AHU — Air-Handling Unit Selection Program  
TXV — Thermostatic Expansion Valve (Field-supplied)  
††Not available on 39LB units.  
*May be field manifolded for either face split or row split.  
†Where each TXV has the same number of circuits, that number is  
shown once. When coil has an uneven number of circuits per TXV,  
both values are shown.  
20  
Table 7 — Direct Expansion Coil Circuiting Data (cont)  
SMALL FACE AREA (39LB, 39LC, 39LF)  
UNIT SIZE  
CIRCUITING TYPE  
03  
Half  
06  
Half  
08  
Half  
10  
Half  
12  
Qtr  
Full  
Qtr  
Full  
Qtr  
Full  
Qtr  
Full  
Half  
Full  
CFM AT 550 FPM  
FACE AREA (sq ft)  
TUBE FACE  
1496  
2.72  
12  
2596  
4.72  
16  
3619  
6.58  
20  
4372  
7.95  
20  
5126  
9.32  
20  
TUBE LENGTH (in.)  
26.1  
34.0  
37.9  
45.8  
53.7  
NUMBER OF CIRCUITS  
NUMBER OF TXVs  
NUMBER OF CIRCUITS/TXV†  
SUCTION CONNECTIONS  
(in. OD)  
DISTRIBUTOR CONNECTIONS  
(in. OD)  
4
2
2
6
2
3
11/8  
4
2
2
8
2
4
11/8  
16  
2
10  
2
20  
2
10  
2
20  
2
10  
2
20  
2
8
5
10  
5
10  
5
10  
7
7
/
/
13/8  
11/8  
13/8  
11/8  
13/8  
11/8  
13/8  
8
8
7
7
7
7
7
7
7
7
7
7
/
/
/
/
11/8  
/
/
/
/
/
/
8
8
8
8
8
8
8
8
8
8
4-ROW COIL  
Circuit Equivalent Length (ft)  
Distributor Tube Length (in.)  
Face Split  
52  
26  
62  
32  
34  
18  
40  
20  
45  
23  
11  
11  
11  
11  
11  
11  
11  
15  
11  
16  
4
18  
18  
4
11  
16  
5
18  
18  
5
11  
16  
5
18  
18  
5
Row Split  
Distributor Nozzle Size**  
11/2  
11/2  
21/2  
21/2  
6-ROW COIL  
Circuit Equivalent Length (ft)  
Distributor Tube Length (in.)  
Face Split  
58  
39  
47  
24  
51  
26  
59  
30  
67  
34  
111/2 111/2  
111/2 111/2  
111/2  
16  
4
13  
181/2  
4
111/2  
16  
5
13  
181/2  
5
111/2  
16  
5
13  
181/2  
5
Row Split  
Distributor Nozzle Size**  
111/2  
11/2  
13  
15  
16  
3
11/2  
21/2  
8-ROW COIL††  
Circuit Equivalent Length (ft)  
Distributor Tube Length (in.)  
Face Split  
52  
63  
32  
68  
34  
78  
39  
89  
45  
111/2  
13  
111/2 111/2  
111/2  
16  
4
13  
181/2  
4
111/2  
16  
5
13  
181/2  
5
111/2  
16  
5
13  
181/2  
5
Row Split  
Distributor Nozzle Size**  
15  
16  
3
11/2  
21/2  
SMALL FACE AREA (39LB, 39LC, 39LF)  
18  
UNIT SIZE  
15  
21  
25  
CIRCUITING TYPE  
Half  
Full  
Half  
Full  
Half  
Full  
Half  
Full  
Double  
CFM AT 550 FPM  
FACE AREA (sq ft)  
TUBE FACE  
6666  
12.12  
26  
7689  
13.98  
30  
9405  
17.1  
30  
11,275  
20.5  
36  
TUBE LENGTH (in.)  
53.7  
53.7  
65.5  
65.5  
NUMBER OF CIRCUITS  
NUMBER OF TXVs  
NUMBER OF CIRCUITS/TXV†  
SUCTION CONNECTIONS  
(in. OD)  
DISTRIBUTOR CONNECTIONS  
(in. OD)  
16  
2
26  
4*  
15  
2
30  
4*  
15  
2
30  
4*  
18  
2
36  
4*  
9
13/8  
72  
4*  
6-7  
6-7  
7-8  
7-8  
7-8  
7-8  
9
18  
13/8  
13/8  
13/8  
13/8  
13/8  
13/8  
13/8  
15/8  
7
7
/
/
7/8-11/8  
7/8-11/8  
7/8-11/8  
7/8-11/8  
11/8  
11/8  
13/8  
8
8
4-ROW COIL  
Circuit Equivalent Length (ft)  
Distributor Tube Length (in.)  
Face Split  
45  
23  
45  
23  
54  
26  
54  
26  
13  
21  
6
16  
16  
3
13  
23  
8
16  
16  
4
13/15  
231/2  
8
16  
16  
4
16  
26  
8
15  
15  
4
Row Split  
Distributor Nozzle Size**  
6-ROW COIL  
Circuit Equivalent Length (ft)  
Distributor Tube Length (in.)  
Face Split  
67  
34  
67  
34  
81  
40  
40  
13  
21  
6
16  
16  
3
13  
231/2  
8
16  
16  
4
13/15  
231/2  
8
16  
16  
4
163/4  
163/4  
4
Row Split  
Distributor Nozzle Size**  
8-ROW COIL  
Circuit Equivalent Length (ft)  
Distributor Tube Length (in.)  
Face Split  
89  
45  
89  
45  
54  
54  
26  
13  
21  
6
16  
16  
3
15  
231/2  
8
16  
16  
4
16  
16  
4
163/4  
163/4  
4
16  
16  
8
Row Split  
Distributor Nozzle Size**  
LEGEND  
**Factory-supplied distributors have factory-selected nozzle sizes  
shown. If necessary, replace factory-supplied nozzles with field-  
supplied and installed nozzles. Consult Electronic Catalog AHU  
selection program for correct nozzle selection.  
AHU — Air-Handling Unit Selection Program  
TXV — Thermostatic Expansion Valve (Field-supplied)  
††Not available on 39LB units.  
*May be field manifolded for either face split or row split.  
†Where each TXV has the same number of circuits, that number is  
shown once. When coil has an uneven number of circuits per TXV,  
both values are shown.  
21  
Table 8 — Distributor Part Numbers  
SPORLAN  
NO.  
OF  
TUBES  
PART NO.  
Sporlan Carrier  
CONNECTION  
OD (in.)  
NOZZLE  
Type Size  
1112-2-1/4 EA07NC261  
1112-3-1/4 EA07FC027  
1112-4-1/4 EA07NC262  
1112-5-1/4 EA07NC263  
1112-6-1/4 EA07NC264  
1113-7-1/4 EA07HC207  
1113-8-1/4 EA07HC208  
1115-8-1/4 EA07KC240  
1115-9-1/4 EA07KC241  
1115-10-1/4 EA07KC242  
1116-11-1/4 EA07HC011  
2
3
4
5
6
7
8
8
9
10  
11  
0.88  
1.12  
G
E
3/4 to 12  
3 to 30  
1117-11-1/4 EA07LC510  
1117-12-1/4 EA07HC012  
1117-13-1/4 EA07HC013  
1126-14-1/4 EA07TC290  
1126-15-1/4 EA07HC015  
1126-16-1/4 EA07TC207  
1126-17-1/4 EA07HC017  
11  
12  
13  
14  
15  
16  
17  
1.38  
C
3 to 50  
Fig. 27 — Expansion Valve Piping  
Fig. 28 — Distributor and Hot Gas Bypass  
Auxiliary Side Connector  
Table 9 — Side Connector (Hot Gas Bypass) Data  
CONNECTION SIZES (in.)  
SPORLAN  
TYPE  
CARRIER  
PART NO.  
USED WITH  
NOZZLE  
SIZE  
DISTRIBUTOR TYPE  
Inlet — ODM Solder  
Outlet — ODF Solder  
Auxiliary — ODF Solder  
5
5
1
ASC-5-4  
ASC-7-4  
ASC-9-5  
ASC-11-7 EA19BA905  
ASC-13-9  
/
/
/
/
/
/
/
1620, 1622  
1112, 1113  
1115, 1116  
J
G
E
C
A
8
8
2
7
7
1
EA19BA504  
EA19BA705  
/
8
8
2
5
11/8  
13/8  
15/8  
11/8  
13/8  
15/8  
8
7
1117, 1126  
8
11/8  
1125, 1127, 1143  
DIMENSIONS (in.)  
SPORLAN  
TYPE  
ASC-5-4  
ASC-7-4  
ASC-9-5  
A
B
C
D
E
F
5/8 ODM  
7/8 ODM  
5/8 ODF 1.88 0.95 1.25  
7/8 ODF 2.25 1.06 1.38  
1/2 ODM  
1/2 ODM  
11/8 ODM 11/8 ODF 2.81 1.47 1.62 15/8 ODM  
ASC-11-7 13/8 ODM 13/8 ODF 3.53 1.89 2.19 17/8 ODM  
ASC-13-9 15/8 ODM 15/8 ODF 3.72 1.83 2.75 11/8 ODM  
LEGEND  
ODF  
ODM  
Outside Diameter, Female  
Outside Diameter, Male  
22  
UNLOADING CONSIDERATIONS — Direct expansion coils  
can have two intertwined refrigerant circuits. In addition, quar-  
ter, half, full and double circuiting configurations are offered to  
allow optimum system performance and oil return at full and  
part-load operation.  
Circuiting selection should result in a circuit loading of 0.8  
to 2.0 tons per circuit at design load. Circuit loading must be  
evaluated at minimum load to ensure that it does not drop  
below 0.6 tons per circuit. Solenoid valves may be used, if nec-  
essary, to shut off the refrigerant supply to individual expansion  
valves to maintain adequate coil circuit loading.  
There are three different options to control tons/circuit when  
using an unloading compressor. The first is to use drop sole-  
noid valve control as illustrated above and let the suction cutoff  
unloaders “ride” with the load. The second is to use drop  
solenoid valve control as illustrated above with electric unload-  
ers and let the control algorithm determine the combination of  
solenoid valves and unloaders to limit tons/circuit to acceptable  
limits. The third is to limit the minimum amount of unloading  
so that tons/circuit is within acceptable limits.  
SPECIAL PIPING WITH 4 SPLITS PER COIL  
Manifolding for 2-Face Splits — Refer to Fig. 29 and exter-  
nally manifold as follows:  
1. Connect the 4 expansion valves to the 4 distributors on  
each coil and connect the 4 suction lines to the  
15-diameter-long risers as outlined in previous piping  
instructions.  
Compressor minimum unloading and TXV quantity is nec-  
essary to determine minimum tonnage per circuit.  
Minimum Unloading Equation:  
(Tons/Circuit) x (Minimum Unloading)  
x (Total # of TXVs)  
2. Install common liquid line for upper face split to first  
(upper) and second expansion valves. Also, install a  
common suction line from suction lines attached to first  
(upper) and second suction header connections.  
# of TXVs Active  
Example:  
Condensing Unit:  
38ARS012  
Minimum Unloading:33%  
3. Repeat Step 2 for lower face split using third and fourth  
distributor and suction connections.  
Coil:  
6 row, 11 FPI, Half Circuit  
Coil Tons/Circuit:  
Total TXVs:  
In the first example we will determine the tons/circuit when  
both TXVs are active and the compressor is unloaded to its  
minimum of 33%.  
1.68  
2
Manifolding for 2-Row Splits — Refer to Fig. 30 and exter-  
nally manifold as outlined for the 2-face splits with the  
following exceptions:  
1. Manifold in pairs, the first and third coil connections for  
one split.  
2. Manifold the second and fourth pairs of coil connections  
for the other split.  
NOTE: Split section using first and third pairs of coil connec-  
tions should be first on, last off for coils with right hand (facing  
direction of airflow) connections and the reverse for left hand  
connections.  
Hot Gas Bypass Connection with 4 Splits per Coil — For  
either face or row splits connect a hot gas bypass auxiliary side  
connector to each distributor of coil split that is first on, last off.  
Refer to installation instructions for Hot Gas Bypass.  
(1.68 Tons/Circuit) x (33% Minimum Unloading)  
x (2 TXVs)  
=
2 TXVs Active  
(1.68) x (.33) x (2)  
=
2
= .55 tons/circuit at minimum unloading UNACCEPTABLE  
If we install a liquid line solenoid valve before one of the  
TXVs and close it so that only one TXV is active when the  
compressor is unloaded to its minimum of 33%, we see the  
following:  
(1.68 Tons/Circuit) x (33% Minimum Unloading)  
x (2 TXVs)  
1 TXV Active  
=
(1.68) x (.33) x (2)  
=
1
= 1.10 tons/circuit at minimum unloading ACCEPTABLE  
23  
TXV — Thermostatic Expansion Valve  
Fig. 29 — Face Split Coil Manifolding (Typical)  
TXV — Thermostatic Expansion Valve  
Fig. 30 — Row Split Coil Manifolding (Typical)  
24  
Electric Heaters — Electric heaters may be factory in-  
stalled or drop shipped to the jobsite and field installed. The  
heater can only be installed in the preheat-electric section.  
To install electric heater, refer to Fig. 31 and proceed as  
follows:  
1. Locate preheat-electric section already mounted on unit  
and remove protective shipping cover.  
2. Locate crate containing electric heater and verify heater  
matches the unit. Unit hand and heater hands must agree.  
3. Remove both knockout slugs (power and signal). Install  
conduit connectors in top of coil connection box.  
4. Remove top panel of the preheat-electric section and drill  
or punch 2 holes are specified in Fig. 31.  
5. Insert the electric heater into unit. It must slide between  
2 angles located on the bottom of the section.  
6. Secure heater to the preheat-electric section using  
4 screws.  
7. Locate top panel of section. Run conduit through top pan-  
el and tighten conduit connectors. Lower top panel and  
replace panel on unit.  
8. Complete wiring per wiring diagram and job require-  
ments. Follow all applicable local codes.  
CONNECT POWER AND CONTROL WIRES — Heater wir-  
ing schematic is located on control box panel. (Figure 32 shows  
typical wiring details.) Electrical data for each standard heater  
arrangement is shown in Table 10. Verify that minimum airflow  
requirement (minimum coil face velocity, fpm) will be met,  
especially on applications where variable air volume is supplied.  
Use copper power supply wires rated for 75 C minimum.  
On 250-v or greater applications, use 600-v rated wiring. Size  
wires to carry 125% of current load on each set of terminals  
(Table 11). Use the following formulas as required:  
Single-phase line current  
Fig. 31 — Electric Heater Installation  
1 (kW per set of terminals) (1000)  
=
voltage  
Provide sufficient clearance for convection cooling of heat-  
ers with solid-state controllers. Provide at least 5-in. of free air  
space above and below cooling fins extending from heater ter-  
minal box. Be sure to connect interlock terminals F1 and F2 to  
auxiliary contacts on fan starter.  
Three-phase line current  
(kW per set of terminals) (1000)  
=
(voltage) (1.73)  
Each heater has 2 different types of factory-installed ther-  
mal cutouts for overtemperature protection; an automatic reset  
thermal cutout for primary protection and a manual reset ther-  
mal cutout to protect against failure of the primary system.  
Also provided is an airflow pressure differential switch to pre-  
vent the heater from operating when the fan is not in operation  
or airflow is restricted or insufficient. The primary automatic  
reset cutout is a bi-metal disk-type cutout. It is wired into the  
control circuit which operates the magnetic disconnecting con-  
tactors (the same contactors which also switch on and off the  
various steps of the coil). The secondary manual reset cutout is  
a bi-metal disk-type cut-out. This secondary thermal cutout is  
load carrying and is installed in each heater subcircuit. The pri-  
mary and secondary overtemperature protection systems are  
independent of each other. The secondary system is designed to  
protect against possible failure of the primary system to deen-  
ergize the heater.  
(kW per set of terminals) (1000) = (voltage) (1.73)  
Note that if the heater is rated at 50 kW (or more) and is con-  
trolled by a cycling device such as a multi-stage thermostat, or  
a step controller, conductors may be sized at 100% of load  
amperes (as in Tables 10 and 11) per National Electrical Code  
(NEC) Section 424-22. Heater construction and application  
information (Tables 10 and 11) are based upon Underwriters’  
Laboratories (UL) Space Heating Standard No. 1096 and the  
requirements of the NEC. Installer is responsible for observing  
local code requirements.  
Install a disconnect switch or main circuit breaker in accor-  
dance with NEC and other applicable codes. Locate so that it is  
easily accessible and within sight of heater control box (per  
NEC Article 424-19 and 424-65).  
Weatherproof junction boxes have no knockouts for wire  
entrance. Drill or punch holes for conduit as required and make  
all junctions watertight.  
Where field-supplied thermostats are used, isolate circuits  
to prevent possible interconnection of control circuit wiring.  
Subcircuits in the heaters are designed in compliance with  
paragraph 424-22 of the NEC. The coil is subdivided into cir-  
cuits that draw no more than 48 amps each and is fused for at  
least 125% of the circuit rating.  
Pitot tube is to be positioned so that the airflow switch is ac-  
tuated by a minimum negative pressure of 0.07 in. wg.  
Where field-supplied step controller is used, connect steps  
to terminals as marked on wiring schematic. When connecting  
multi-stage heaters, wire stage no. 1 so that it is first stage on,  
last stage off. Connect thermostats as required.  
25  
NOTE: All wiring must be copper and must conform to the NEC (National Electrical Code).  
Fig. 32 — Typical Electric Heater Wiring Schematic  
26  
Table 10 — Electric Heater Data  
208/3/60 VOLTS  
240/3/60 VOLTS  
480/3/60 VOLTS  
380/3/50 VOLTS  
NOMINAL  
COIL FACE  
VELOCITY  
(fpm)  
UNIT HEATER  
NO. OF  
CONTROL  
STEPS*  
HEATER  
COIL  
kW  
TEMP  
RISE  
(F)  
No.  
MCA† Sub- MOCP  
Ckt  
No.  
MCA† Sub- MOCP  
Ckt  
No.  
MCA† Sub- MOCP  
Ckt  
No.  
MCA† Sub- MOCP  
Ckt  
SIZE  
39L  
AREA  
(sq ft)  
Total  
FLA  
Total  
FLA  
Total  
FLA  
Total  
FLA  
9
15  
17.2  
8
10  
17  
19.9  
27  
29.8  
36  
15  
25  
35  
39.9  
43.2  
51  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
500  
26  
44  
50  
14  
17  
29  
34  
47  
51  
62  
19  
31  
44  
50  
54  
64  
15  
26  
41  
49  
53  
62  
17  
26  
35  
38  
45  
63  
13  
19  
25  
29  
33  
42  
55  
11  
14  
19  
25  
28  
43  
51  
9
25  
42  
48  
22  
28  
47  
55  
75  
83  
31  
52  
60  
28  
35  
59  
69  
94  
1
1
1
1
1
1
2
2
2
3††  
1
2
3
3
3
3
1
2
3
3
3
2
2
3
3
3
2
2
3
3
35  
60  
60  
30  
35  
60  
70  
100  
110  
150  
60  
22  
36  
41  
19  
24  
41  
48  
65  
72  
87  
36  
60  
84  
27  
45  
52  
24  
30  
51  
60  
81  
90  
108  
45  
75  
105  
120  
130  
154  
45  
1
1
1
1
1
1
1
2
2
2
1
2
2
3
3
3
1
2
3
3
3
1
2
3
3
3
1
2
3
3
3
1
2
2
3
3
1
2
2
3
3
2
3
3
4
5
30  
50  
60  
25  
35  
60  
60  
90  
90  
110  
50  
80  
110  
125  
150  
175  
50  
11  
18  
21  
10  
12  
20  
24  
33  
36  
43  
18  
30  
42  
48  
52  
61  
18  
30  
48  
57  
62  
72  
24  
36  
48  
52  
62  
87  
24  
36  
48  
54  
62  
78  
104  
24  
31  
42  
54  
62  
94  
113  
24  
31  
42  
54  
62  
96  
111  
140  
36  
48  
60  
78  
96  
116  
132  
175  
14  
23  
26  
12  
15  
26  
30  
41  
45  
54  
23  
38  
53  
60  
65  
77  
23  
38  
60  
71  
78  
90  
30  
45  
60  
65  
78  
108  
30  
45  
60  
68  
78  
98  
1
1
1
1
1
1
1
1
1**  
1**  
1
1
1
2
2
2
1
1
2
2
2
2
1
1
2
2
2
2
1
1
2
2
2
2
3
1
1
1
2
2
2
3
1
1
1
2
2
3
3
3
1
2
2
2
3
3
3
20  
25  
30  
20  
20  
30  
30  
45  
45  
60  
25  
40  
60  
70  
70  
80  
25  
40  
70  
80  
80  
100  
30  
45  
70  
70  
80  
110  
30  
45  
70  
70  
80  
100  
150  
30  
40  
60  
70  
80  
125  
150  
30  
40  
60  
70  
80  
125  
150  
175  
50  
14  
23  
26  
12  
15  
26  
30  
41  
45  
55  
23  
38  
53  
61  
66  
78  
23  
38  
61  
72  
79  
91  
30  
45  
61  
65  
79  
110  
30  
45  
61  
68  
79  
99  
131  
30  
39  
53  
68  
79  
119  
143  
30  
39  
53  
68  
79  
121  
140  
17  
29  
33  
15  
19  
32  
38  
51  
57  
68  
29  
48  
67  
76  
82  
97  
29  
48  
76  
90  
98  
114  
38  
57  
76  
82  
98  
137  
38  
57  
76  
86  
98  
124  
164  
38  
49  
67  
86  
98  
148  
179  
38  
49  
67  
86  
98  
152  
175  
57  
76  
95  
1
1
1
1
1
1
1
1
1
2**  
1
1
2
2
2
2
1
1
2
2
2
2
1
1
2
2
2
3††  
1
1
2
2
2
3
3
1
1
2
2
2
3
3
1
1
2
2
2
3
3
1
2
20  
30  
35  
20  
20  
35  
40  
60  
60  
70  
30  
50  
70  
80  
90  
100  
30  
50  
80  
90  
100  
125  
40  
60  
80  
90  
100  
150  
40  
60  
80  
03  
06  
2.2  
3.7  
3
6
104  
125  
52  
100  
42  
69  
87  
90  
97  
122  
139  
150  
177  
52  
125  
150  
175  
200  
60  
08  
10  
12  
5.1  
6.2  
7.3  
6
6
6
111  
120  
142  
42  
96  
104  
123  
36  
60  
96  
114  
125  
48  
72  
15  
25  
69  
87  
90  
75  
80  
39.9  
47.3  
51.8  
59.8  
19.9  
29.8  
39.9  
43  
51.8  
72  
19.9  
29.8  
39.9  
45  
51.8  
65  
86  
19.9  
25.8  
35  
111  
131  
144  
55  
83  
111  
119  
144  
55  
83  
111  
125  
144  
55  
72  
97  
125  
144  
139  
164  
180  
150  
175  
200  
120  
142  
156  
60  
90  
120  
129  
156  
60  
90  
120  
135  
156  
60  
125  
150  
175  
60  
90  
125  
150  
175  
60  
90  
125  
150  
175  
60  
69  
70  
104  
139  
149  
180  
110  
150  
150  
200  
96  
104  
125  
48  
72  
69  
70  
104  
139  
156  
180  
69  
90  
122  
156  
180  
69  
110  
150  
175  
200  
70  
90  
125  
175  
200  
70  
96  
15  
18  
10.0  
6
6
108  
125  
48  
62  
84  
108  
125  
48  
62  
84  
108  
125  
90  
3
100  
125  
175  
40  
50  
70  
2
2
3
3
3
2
2
3
3
3
2
3
3
129  
30  
39  
53  
68  
78  
80  
105  
135  
156  
60  
110  
150  
175  
60  
11.74  
45  
51.8  
78  
90  
78  
100  
150  
200  
40  
50  
70  
117  
141  
30  
39  
53  
68  
78  
120  
138  
175  
45  
60  
75  
98  
120  
145  
166  
218  
94  
55  
72  
97  
125  
144  
19.9  
25.8  
35  
12  
16  
20  
23  
36  
41  
52  
11  
14  
18  
23  
29  
35  
39  
52  
90  
90  
78  
80  
122  
156  
180  
104  
139  
174  
226  
277  
335  
125  
175  
200  
110  
150  
175  
250  
300  
350  
105  
135  
156  
110  
150  
175  
100  
125  
175  
200  
250  
300  
350  
45  
90  
21  
14.21  
6
51.8  
79.8  
92  
116  
30  
39.9  
50  
65  
79.8  
96.5  
110  
145  
100  
175  
175  
60  
80  
100  
125  
175  
200  
225  
300  
83  
72  
96  
90  
46  
61  
76  
99  
121  
147  
167  
221  
111  
139  
181  
222  
268  
120  
151  
196  
240  
291  
331  
70  
80  
120  
157  
192  
232  
265  
2
3
3
4
5
6
100  
125  
150  
175  
225  
124  
152  
183  
209  
276  
25  
17.79  
6
5
6
4***  
4***  
5†††  
4***  
LEGEND  
NOTES:  
1. Subcircuits are internal heater circuits of 48 amps or less.  
ARI  
Air Conditioning and Refrigeration Institute  
American Wire Gage  
2. Electric heat performance is not within the scope of ARI standard 430 certification.  
3. To avoid damage due to overheating, minimum face velocity cannot fall below  
350 fpm.  
AWG  
FLA  
Full Load Amps  
Kilowatts  
kW  
MCA  
MOCP  
Minimum Circuit Amps  
Maximum Overcurrent Protection  
*Standard control steps are listed under the Control Step heading. “Free” additional  
steps of control are optionally available when the number of subcircuits exceeds the  
standard number of control steps.  
†MCA = 1.25 x FLA; for proper wire sizing, refer to Table 310-16 of the NEC.  
**2 control steps in this voltage.  
††3 control steps in this voltage.  
***4 control steps in this voltage.  
†††5 control steps in this voltage.  
27  
Table 11 — Field Wiring for Incoming Conductors  
Sized for 125% of Heater Load  
1. Sizes 03-18 without inlet guide vanes (IGVs) — See  
Fig. 33. It is not necessary to remove the bearing support  
channels from the fan housing.  
LOAD AMPS*  
Copper  
LOAD AMPS*  
Copper  
WIRE SIZE  
(AWG or kcmil)  
WIRE SIZE  
(AWG or kcmil)  
Sizes 21 and 25 without IGV and 06-25 with IGVs —  
See Fig. 34. The “A” frame support must be removed. To  
change from upblast to horizontal discharge or from  
horizontal to upblast discharge, the bearings must be  
relocated to keep the wheel centered in the housing. To  
change from upblast front (UBF) to upblast rear (UBR)  
or from top horizontal front (THF) to top horizontal rear  
(THR) or vice versa, turn the entire fan housing 180 de-  
grees about its base.  
12  
10  
8
16  
24  
1/0  
2/0  
120  
140  
160  
184  
204  
228  
248  
268  
304  
40  
3/0  
6
52  
4/0  
4
68  
250  
300  
350  
400  
500  
3
80  
2
92  
1
104  
2. Inlet guide vane actuators and linkages, where provided,  
may be moved to the opposite fan scroll side sheet.  
LEGEND  
AWG — American Wire Gage  
kcmil — Thousand Circular Mils  
NOTE: The swivel joint must be at the 12 o’clock posi-  
tion on the IGV assembly. (See Fig. 12.) The jackshaft  
crankarm, attached to the jackshaft at the “A” frame, will  
sit vertically up on all units. Figure 12 illustrates a jack-  
shaft crankarm in the vertical up position.  
*Values are based on Table 310-16 of the NEC (National Electrical  
Code) for 75 C insulated copper wire. Not more than 3 conductors  
in a raceway.  
NOTES:  
1. Be sure to consider length of wiring run and possible voltage  
drops when sizing wires.  
3. The fan shaft may be driven out and reinstalled to place  
the drive pulley on the opposite end.  
4. The fan scroll is prepunched for horizontal or vertical dis-  
charge to match the support angles at the base of the unit.  
5. The motor and motor base may be rotated to place the  
motor at the front or rear of the unit. Proper location is  
that which results in the longest drive center line distance.  
The motor conduit box location may need to be reversed.  
2. Field power wiring — Heaters are furnished with a terminal  
block sized for incoming copper conductors with 75 C insulation  
rated to carry at least 125% of the heater load. However, con-  
ductors can be sized to carry 100% of the heater load if the  
heater is rated at 50 kW or more, and the heater is controlled by  
a cycling device such as a multi-stage thermostat, step control-  
ler, or SCR (silicon control rectifier) power controller. Terminal  
blocks and knockouts are sized to handle either 100% or 125%  
conductors.  
6. When hand of fan is changed, it may be necessary to turn  
the discharge panel inside-out to fit correctly with the fan  
discharge. In this case, remove the existing insulation and  
install new duct-liner type insulation on the opposite side  
of the discharge panel.  
Discharge Modification — If field modification of  
discharge position is required, 39L fans can be converted (by a  
skilled mechanic) to any standard hand and discharge without  
any additional parts. (NOTE: This does not apply to a model  
change conversion.) All mounting holes are prepunched.  
7. Rebalancing of the unit is recommended.  
To convert a 39L fan, note the following:  
LEGEND  
THF — Top Horizontal Front  
THR — Top Horizontal Rear  
UBF — Upblast Front  
UBR — Upblast Rear  
Fig. 33 — Fan Discharge Positions, Fans without IGVs  
28  
LEGEND  
THF — Top Horizontal Front  
THR — Top Horizontal Rear  
UBF — Upblast Front  
UBR — Upblast Rear  
Fig. 34 — Fan Discharge Positions, Fans with IGVs  
START-UP  
Check List — Make a walkway inside unit components to  
protect insulation. Remove all construction debris from unit  
interior. Remove walkway before starting unit.  
FILTERS — Install unit filters in all filter sections.  
FANS  
1. Check lubrication of fan, motor bearings, and linkages.  
a. Note that bearings are shipped completely full of  
grease for corrosion protection and may run warm  
temporarily on start-up until excess grease has  
discharged.  
b. Hand-operate all linkages, such as damper and  
guide vanes, to check for freedom of movement.  
2. Check tightness of bearing setscrews or locking collars  
(Fig. 35). Also, check tightness of setscrews on fan  
wheels and sheaves.  
3. Check tightness of fan shaft bearing mounting.  
4. Recheck sheave alignment and belt tension. (Refer to  
Fig. 14 and 15.)  
SQUEEZE-TYPE LOCKING COLLAR  
BEARING SETSCREW TORQUE (in.-lb)  
39L UNIT SIZE  
03,06,08,10,12  
15,18,21,25  
TORQUE  
70  
90  
5. Hand turn fan to make certain fan wheel does not rub in  
housing.  
BEARING HOLDDOWN BOLT TORGQUE (ft-lb)  
BOLT SIZE  
3/8-16  
TORQUE  
30  
1/2-13  
63  
5/8-11  
100  
Fig. 35 — Fan Shaft Bearing Details  
29  
6. Check fan speed with a strobe-type tachometer or use the  
following formula: Obtain the motor rpm from the fan  
motor nameplate and read sheave pitch diameters marked  
on the fan and motor pulleys, or estimate the pitch diame-  
ters by using the pulley outside diameters.  
DX Coil — Charge refrigerant. Also refer to condensing unit  
service and installation instructions. Refrigerant operating  
charge for unit coil is shown in Table 1.  
SERVICE  
General  
Then:  
Motor Rpm x Motor Sheave  
1. Place a suitable walkway to protect floor insulation  
Pitch Diameter (in.)  
Fan Rpm =  
whenever entering the fan section.  
Fan Sheave Pitch Diameter (in.)  
2. Review Safety Considerations at beginning of these in-  
structions. Good safety habits are important tools when  
performing service procedures.  
3. To make speed measurements, use a strobe-style tachom-  
eter or calculate per Step 6 of Start-Up, Check List.  
Example:  
Actual  
1760  
Approximate  
1760  
Nameplate Motor  
Rpm  
Mtr Sheave Pitch  
Diameter  
=
=
Fan Motor Replacement  
1. Shut off motor power.  
2. Disconnect and tag power wires at motor terminals.  
3. Loosen motor brace-to-mounting-rail attaching bolts.  
Loosen belt tensioning bolts to adjust the motor position  
so V-belts can be removed without stretching over  
grooves.  
8.9 in.  
9.0 (OD)  
Fan Sheave Pitch  
Diameter  
Fan Rpm  
=
=
=
=
12.4 in.  
1760 x 8.9  
12.4  
12.5 (OD)  
1760 x 9  
12.5  
1263 Rpm  
1267 Rpm  
Refer to Table 1, Physical Data for maximum allowable  
fan speeds for standard wheels. Excessive fan speed may  
result in condensate carryover from cooling coil or fan  
motor overload and wheel failure.  
4. Mark belt as to position. Remove and set aside belts.  
5. Remove motor to motor bracket holddown bolts.  
6. Remove motor pulley and set aside.  
7. Remove motor.  
8. Install new motor. Reassemble by reversing Steps 1-6. Be  
sure to reinstall multiple belts in their original position.  
Use a complete new set if required. Do not stretch belts  
over sheaves. Review the sections on motor and sheave  
installation, sheave alignment and belt tensioning dis-  
cussed previously (Fig. 13-15).  
7. Check direction of rotation (see Fig. 36). Arrow on drive  
side of fan housing indicates correct direction of rotation.  
9. Reconnect motor leads and restore power. Check fan for  
proper rotation as described in Start-Up, Check List.  
Coil Cleaning  
DETERGENT — Spray mild detergent solution on coils with  
garden-type sprayer. Rinse with fresh water. Check to ensure  
condensate line is free. Excess water from cleaning may flood  
unit if condensate line is plugged.  
STEAM — Remove coil to facilitate cleaning and prevent  
damage to unit insulation. See Coil Removal section which  
follows.  
Fig. 36 — Fan Wheel Rotation  
8. Check vibration. If excessive vibration occurs, check for  
the following:  
Winter Shutdown (Chilled Water Coil Only) — It  
is recommended that auxiliary drain piping be added to coil  
piping if yearly winterizing of coils is anticipated. This auxilia-  
ry piping should be located at the highest and lowest point on  
the respective header connection for each coil.  
a. Variable sheave (if air balance of system has been  
accomplished: replace sheave with fixed sheave  
for continuous application).  
ANTIFREEZE METHODS OF COIL PROTECTION  
1. Close coil water supply and return valves.  
2. Drain coil as follows:  
b. Drive misalignment.  
c. Mismatched, worn or loose belts.  
d. Wheel or sheaves loose on shaft.  
e. Loose bearings.  
f. Loose mounting bolts.  
g. Motor out of balance.  
h. Sheaves eccentric or out of balance.  
i. Vibration isolators improperly adjusted.  
j. Out-of-balance or corroded wheel (rebalance or  
replace if necessary).  
k. Accumulation of material on wheel (remove  
excess material).  
Method I — ‘Break’ flange of coupling at each header  
location. Separate flange or coupling connection to facili-  
tate coil draining.  
Method II — Open both valves to auxiliary drain piping.  
3. After coil is drained, Method I, connect line with a service  
valve and union from upper nozzle to an antifreeze reser-  
voir. Connect a self-priming reversible pump between the  
low header connection and the reservoir. Method II, make  
connection to auxiliary drain valves.  
4. Fill reservoir with any inhibited antifreeze acceptable to  
code and underwriter authority.  
COILS  
5. Open service valve and circulate solution for 15 minutes;  
then check its strength.  
Chilled Water Coil — Typical coil vents, drains, and lifting  
points are shown in Fig. 17.  
30  
6. If solution is too weak, add more antifreeze until desired  
strength is reached, then circulate solution through coil  
for 15 minutes or until concentration is satisfactory.  
7. Remove upper line from reservoir to reversible pump.  
Drain coil to reservoir and then close service valve.  
8. Break union and remove reservoir and its lines.  
9. Leave coil flanges or coupling open and auxiliary drain  
valves open until spring.  
install the coil with the downstream bottom of the coil attached  
to the upright mounting flange as shown in Fig. 36. Adjust  
the coil and then attach the top coil baffle to the top flange  
provided.  
Coil Removal  
HORIZONTAL UNIT SLANT COIL REMOVAL (39LA  
Units)  
NOTE: Item numbers are in Fig. 38.  
AIR DRYING METHOD OF COIL PROTECTION (Unit  
and coil must be level for this method.)  
1. Close coil water supply and return main valves.  
1. Refer to Fig. 4 for service area clearance.  
2. Disconnect piping (Item 5).  
3. On top panel (Item 3), remove screws located directly  
above side panels (Items 2 and 6). Top panels may be re-  
moved from unit to provide more workspace, but it is not  
required.  
2. Drain coil as described in procedures for Antifreeze  
Methods of Coil Protection.  
3. Connect air supply or air blower to inlet header connec-  
tion and close its drain connection.  
4. Circulate air and check for air dryness by holding mirror  
in front of open vent in outlet header drain connection.  
Mirror will fog if water is still present.  
5. Allow coil to stand for a few minutes; repeat step 4 until  
coil is dry.  
4. Remove right side panels (Item 6).  
5. If accessory is present, remove accessory side panel  
(Item 1) on left side of unit. Detach filter track support  
bracket if upstream accessory is a filter.  
6. Remove screws from inside baffle (Item 13). Leave baffle  
attached to left side panel (Item 2).  
Field-Installed Coils (39LA,LD Only)  
7. Remove left side panel (Item 2).  
When a 39LA or 39LD unit is ordered without the coil, the fol-  
lowing loose parts are shipped: (see Fig. 37)  
• bottom coil baffle  
8. Remove condensate baffle (Item 8).  
9. Remove coil holddown screws (Items 9 and 11).  
10. Remove baffle screws (Item 4) from downstream side of  
coil.  
11. Tilt coil (Item 10) away from coil support panels (Items 7  
and 12) and slowly slide coil out of unit.  
12. Replace coil by reversing preceding Steps 1-11.  
• side hairpin baffle  
• side header baffle  
• top coil baffle  
These parts should be field-installed onto the coil before  
placing the coil into the unit. Once the baffles are installed,  
SIDE HAIRPIN  
BAFFLE  
TOP COIL  
BAFFLE  
SIDE HEADER  
BAFLE  
SEE TOP  
FLANGE DETAIL  
BOTTOM  
MOUNTING  
FLANGE  
BOTTOM COIL  
BAFFLE  
TOP FLANGE DETAIL  
Fig. 37 — Field-Installed Coils (39LA and LD only)  
31  
LEGEND  
1
2
3
4
5
6
7
Accessory Side Panel  
Left Side Panel  
Top Panels  
8
Condensate Baffle  
9
10  
11  
12  
13  
Holddown Screws  
Coil  
Baffle Screws  
Holddown Screws  
Left Support Panel  
Inside Baffle  
Piping  
Right Side Panels  
Right Support Panel  
Fig. 38 — Horizontal Unit Slant Coil Removal (39LA Units — Sizes 03-21)  
VERTICAL UNIT SLANT COIL REMOVAL (39LD  
6. Remove screws from inside baffle (item 14). Leave baffle  
attached to left side panel (Item 16).  
7. Remove left side panel (Item 16).  
NOTE: Support of fan section may be required after re-  
moval of side panels (Items 7 and 16).  
8. Remove condensate baffle (Item 9).  
9. Remove coil holddown screws (Items 10 and 12).  
10. Remove baffle screws (Item 5) from downstream side of  
coil.  
11. Tilt coil (Item 11) away from coil support panels (Items 8  
and 13).  
12. Replace coil by reversing preceding Steps 1 - 11.  
Units)  
NOTE: Item numbers are in Fig. 39.  
1. Refer to Fig. 4 for service area clearance.  
2. Disconnect piping (Item 6).  
3. Through fan access door (Item 2), remove screws  
(Item 3), while holding angle (Item 4) to top of coil side  
panels (Item 7). On opposite end of unit, gain access to  
similar screws by removing side panels (Item 1).  
4. Remove right side panels (Item 7).  
NOTE: Support of fan section may be required after re-  
moval of side panels (Items 7 and 16).  
5. If accessory is present, remove accessory side panel  
(Item 15) on left side of unit. Detach filter track support  
bracket if upstream accessory is a filter.  
32  
LEGEND  
1
2
3
4
5
6
7
8
9
Fan Side Panel  
Fan Access Door  
Screws  
10  
Holddown Screws  
11  
12  
13  
14  
15  
16  
17  
Coil  
Holddown Screws  
Left Support Panel  
Inside Baffle  
Accessory Side Panel  
Left Side Panels  
Rear Panel  
Angle  
Baffle Screws  
Piping  
Right Side Panels  
Right Support Panel  
Condensate Baffle  
Fig. 39 — Vertical Unit Slant Coil Removal (39LD Units — Sizes 03-21)  
HORIZONTAL OR VERTICAL UNIT — DUAL COIL  
REMOVAL (39LA,39LD units — size 25) — (NOTE: Item  
numbers are in Fig. 40 unless otherwise indicated.)  
1. Refer to Fig. 4 for service area requirements.  
2. Disconnect piping (Item 5).  
3. Horizontal Unit, 39LA — On top panel (Item 3) remove  
screws located directly above side panels (Items 2 and 6).  
Top panels may be removed from unit to provide more  
workspace, but it is not required.  
NOTE: Vertical units may require support of fan section  
after removal of side panels.  
5. If accessory is present, remove accessory side panel (Item  
1) on left side of unit. Detach filter track support bracket  
if upstream accessory is a filter.  
6. Remove screws from horizontal baffle (Item 8). Leave  
baffle attached to upper condensate pan (Item 9).  
7. Remove screws from inside baffles (Item 7). Leave  
baffles attached to left side panel (Item 2).  
Vertical Unit, 39LD — Through fan access door (Item 2,  
Fig. 39), remove screws (Item 3, Fig. 39) holding angle  
(Item 4, Fig. 39) to top of coil panels (Item 7, Fig. 39).  
8. Slide coils and header and baffles from unit.  
9. Replace coils by reversing proceeding Steps 1-8.  
Remove rear panel (Item 17, Fig. 39) and remove baffle  
angle screws (Item 4) holding top baffle to coil.  
4. Remove side panel(s) (Item 6).  
33  
LEGEND  
1
2
3
4
5
Accessory Side Panel  
Left Side Panel  
Top Panels  
Baffle Angle Screws  
Piping  
6
7
Right Side Panels  
Inside Baffle  
Horizontal Baffle  
Upper Condensate Pan  
Baffle Screw  
8
9
10  
Fig. 40 — Horizontal or Vertical Unit — Dual Coil Removal (39LA,LD Units, Sizes 25)  
HORIZONTAL OR VERTICAL UNIT — VERTICAL COIL  
REMOVAL (39LB,LC,LF,LH Units) — Item numbers are in  
Fig. 41 unless otherwise indicated.  
Remove rear panel (Item 17, Fig. 39) and remove baffle  
angle screws (Item 5) holding top baffle to coil.  
4. Remove side panel(s) (Item 7).  
1. Refer to Fig. 4 for service area requirements.  
2. Disconnect piping (Item 6).  
NOTE: Vertical units may require support of fan section  
after removal of side panels.  
3. Horizontal Unit, 39LB and 39LC — On top panel  
(Item 4) remove screws located directly above side panels  
(Items 2 and 7). Top panels may be removed from unit to  
provide more workspace, but it is not required.  
5. If accessory is present, remove accessory side panel  
(Item 1) on left side of unit. Detach filter track support  
bracket if upstream accessory is a filter.  
6. Remove screws (Item 8) from inside baffle (Item 3).  
Leave baffle attached to left side panel (Item 2).  
7. Slide coil and header end baffle from unit.  
8. Replace coil by reversing preceding Steps 1-7.  
Vertical Unit, 39LF and 39LH — Through fan access  
door (Item 2, Fig. 39), remove screws (Item 3, Fig. 39)  
holding angle (Item 4, Fig. 39) to top of coil panels  
(Item 7, Fig. 39).  
34  
LEGEND  
1
2
3
4
Accessory Side Panel  
Left Side Panel  
Inside Baffles  
5
6
7
8
Baffle Angle Screw  
Piping  
Right Side Panel  
Baffle Screw  
Top Panels  
Fig. 41 — Horizontal or Vertical Unit — Vertical Coil Removal (39LB,LC,LF,LH Units)  
Changing Coil Hand  
NOTE: Electric heat coil hand cannot be changed.  
result is often experienced if after-market fin coatings are  
applied.  
If a NuFin hydronic coil is installed with correct airflow, but  
opposite piping hand, and counterflow is maintained, steps  
must be taken to ensure that the coil is continuously vented,  
and that the water velocity is maintained to prevent the coil  
from air-binding.  
Hot or cold areas of the coil face (or otherwise broad tem-  
perature differences and stratification) are usually indications  
that one or more circuits are air-locked internally. This can  
result in coil freeze-up (a condition NOT covered by warranty).  
Refrigerant coils may be rotated for opposite hand applica-  
tions, maintaining the proper airflow direction.  
Do not reposition the distributor(s), they will perform equal-  
ly well in upflow or downflow positions. When soldering  
expansion valves to up-feed distributors, use the minimum  
satisfactory amount of solder to prevent damaging the valve or  
plugging passages.  
DIRECT EXPANSION COILS — Rotate the coil in vertical  
plane and reinstall. Distributor must be on downstream side of  
coil. (Refer to Fig. 42).  
CHILLED WATER AND HOT WATER COILS — These coils  
can be rotated. If coil is rotated in vertical plane and reinstalled  
with counterflow maintained, supply will be at the top of the coil  
and return will be at the bottom. Ensure coil is continuously  
vented and water velocity is maintained to prevent air binding.  
NOTE: The coil cover panel is not part of the coil. Remove  
cover panel from end of unit. New holes must be cut in coil  
cover panel. Original holes must be plugged and insulated.  
New side panels may be necessary when changing coil hand.  
NU-FIN COILS — The NuFin coil is airflow direction sensi-  
tive, especially when used in dehumidifying applications.  
Hydronic versions are counterflow circuited for full gravity  
draining when installed level.  
Correct installation will result in the typical bottom inlet on  
leaving air face and top outlet on entering air face of coil, a  
self-venting design. This will ensure cold air contact with cold  
water, and warm air with hot water.  
Coil repositioning for opposite hand application will com-  
promise one or more of these characteristics. However, there  
will be those situations where this may prove acceptable.  
As a general rule, a change from counterflow circuiting to  
parallel flow for sensible heating and cooling applications will  
result in a 5% drop in net capacity per row of coil. In one and  
two row heating coils, the actual drop may not be measurable,  
thus of insignificant consequence.  
It is important that the airflow direction of the NuFin coil be  
adhered to when latent cooling is possible. Significant moisture  
carryover from the face of the dehumidifying coil will result if  
this rule is violated, even at very low face velocities. The same  
35  
2. Use a vacuum breaker in the return.  
3. Do not use overhead returns from the coil. A floodback  
can occur.  
4. An immersion thermostat to control outdoor-air dampers  
and the fan motor is recommended. This control is acti-  
vated when the steam supply fails or the condensate  
temperature drops below a predetermined temperature,  
usually 120 F.  
Chilled and hot water coils must not be rotated horizon-  
tally. If coils are rotated horizontally, severe water blow-off  
will result.  
STEAM INNER DISTRIBUTING TUBE COILS — Rotate  
in horizontal plane and reinstall. See Fig. 42.  
PIPING — Direct expansion, chilled water, and hot water  
coils should always be piped for counterflow. (Fluid should  
enter the coil at the leaving-air side.) Steam coils must have the  
condensate connection at bottom of coil.  
To determine intervals for cleaning coils in contaminated air  
operations, pressure taps should be installed across the coils  
and checked periodically. Abnormal air pressure drop will indi-  
cate a need for cleaning the coils.  
Annual maintenance should include:  
1. Clean the line strainers.  
2. Blow down the dirt leg.  
5. On low pressure and vacuum systems, the immersion  
thermostat may be replaced by a condensate drain with a  
thermal element. This element opens and drains the coil  
when the condensate temperature drops below 165 F.  
Note the thermal condensate drain is limited to 5 psig  
pressure. At greater coil pressures they will not open.  
In spite of the precautions listed above, a coil may still  
freeze up. An oversize capacity coil, at partial load, with a  
modulating steam control valve will occasionally freeze.  
Freezing occurs in the 20 F to 35 F range of entering-air  
temperatures. A better installation would be an undersize coil,  
with an on/off control valve with thermostatic control in the  
outside air, set at 35 F air temperature, installed downstream of  
the first coil; or setting the minimum steam pressure at 5 psig.  
3. Clean and check operation of steam traps.  
4. Check operation of control valves.  
5. Check the operation of check valves to prevent conden-  
sate flowback.  
6. Check operation of thermostatic air vents, if used. A float  
and thermostatic trap will contain a thermostatic air vent.  
When the bellows is ruptured, it will fail closed.  
7. Check operation of vacuum breakers.  
8. Check operation of the thermal protection devices used  
for freeze-up protection.  
9. Steam or condensate should not be allowed to remain in  
the coil during the off season.This will prevent the forma-  
tion and build up of acids.  
There are additional precautions and control strategies, as  
found in various catalogues and in the ASHRAE Fundamentals  
Handbook and in the Carrier System Design Guide — Piping  
Section, when the entering-air temperature to the coil falls be-  
low 35 F. These conditions occur when IDT coils are used for  
pre-heat and/or face and bypass applications.  
Filters  
FILTER SECTIONS — See Table 12 for filter data. Filters  
are field supplied.  
On the size 03 angle filter, a spacer is required on each side  
of the filters.  
Flat filter section can use 2-in. or 4-in. thick filters. (Size 03  
accepts 2-in. filters only.) The flat filter section as shipped ac-  
cepts 2-in. filters. Remove angle spacer in each filter track to  
provide the 4-in. space required to accommodate 4-in. filters.  
On all filter sections except size 03, filters are pushed into  
the track until they touch the opposite side of the unit. Any re-  
maining space is taken up by the adjustable 2-piece sheet metal  
spacer. See Fig. 43 for filter arrangements.  
Fan Shaft Bearing Removal  
1. Lock open and tag electrical disconnect.  
2. Enter through fan section access door or remove panels as  
required.  
Freeze up protection:  
3. Place plywood or other rigid covering on floor to protect  
insulation from damage.  
1. Use a strainer in the supply line and the dirt leg ahead of  
the trap.  
4. Block wheel so that it will not pinwheel due to natural  
draft through the unit.  
5. Loosen motor base to frame bolts. Adjust motor to re-  
lease belt tension so removal of belts is done without  
stretching. Do not stretch belts over sheaves. Damage to  
belt can result.  
DX AND ALL  
WATER COILS  
6. Remove bolts on bushing of fan shaft sheave, insert bolts  
in jacking hole provided on bushing and slowly jack  
bushing from sheave. Then remove bushing on sheave.  
7. Loosen bearing setscrews and locking collar.  
8. Remove bearing holddown bolts.  
9. Remove bearing while observing the following  
precautions:  
a. Make certain fan shaft surface is not rough or  
scored. If so, clean up surface with fine emery  
cloth.  
STEAM COILS  
ONLY  
b. Add a few drops of oil after cleanup of shaft end.  
It should not be necessary to drive a new bearing onto  
shaft. If light tapping is needed, do not tap against outer  
race.  
Fig. 42 — Coil Rotation  
36  
Table 12 — Filter Data  
39L UNIT SIZE  
03  
06  
08  
10  
12  
15  
18  
21  
25  
Angle Filter Section  
Filter Qty…Size (in.)  
Nominal Face Area (sq ft)  
2…16x20  
2…16x25  
10.00  
4…16x20  
8…16x25  
31.11  
4…16x20  
8…16x25  
31.11  
2…16x25  
5.56  
4…16x20  
8.89  
4…16x25  
11.11  
6…16x20  
13.33  
9…16x20  
20.00  
12…16x20  
26.67  
Filter Mixing Box Section  
Filter Qty…Size (in.)  
Nominal Face Area (sq ft)  
2…16x20  
2…16x25  
10.00  
3…16x20  
6…16x25  
23.33  
4…16x20  
8…16x25  
31.11  
2…16x25  
5.56  
4…16x20  
8.89  
4…16x25  
11.11  
6…16x20  
13.33  
9…16x20  
20.00  
9…16x20  
20.00  
Flat Filter Section  
2…16x20  
2…20x20  
2…20x25  
2…16x25  
22.50  
Filter Qty…Size (in.)*  
2…16x25  
1…20x25  
3…16x20  
3…20x20  
3…20x25  
3…16x25  
2…16x16  
3.56  
2…20x20  
5.56  
2…20x25  
6.94  
3…20x25  
10.42  
6…16x20  
13.33  
Nominal Face Area (sq ft)  
9.03  
15.00  
18.75  
*Only 2-in. filters are available on size 03.  
SIZE 21  
16”  
20”  
25”  
25”  
25”  
SIZE 25  
20”  
25”  
20”  
20”  
16”  
16”  
Fig. 43 — Filter Arrangement, 2-in. and 4-in. Flat  
37  
10. Check fan shaft diameter at bearing mount. If worn by  
more than .001 in. below nominal, shaft should be re-  
placed.  
11. Install new bearing, tighten holddown bolts and then  
tighten bearing locking collar and setscrews.  
12. Make certain fan wheel does not rub sides of fan housing  
after installing new bearings.  
13. Recoat fan shaft with a rust inhibitor or grease.  
14. Replace sheave and belts. Adjust and align as described  
in Installation sections on installing sheaves and V-belts.  
15. Remove insulation protection.  
16. Replace access panels.  
17. Restore electrical power.  
Fan and Shaft Removal (Fig. 44) — The fan wheel  
and shaft may be removed through inlet side of fan housing.  
1. Remove drive belts as described in Fan Shaft Bearing Re-  
moval on page 36.  
2. Block up fan wheel within housing to prevent dropping  
when bearing bolts are removed.  
3. Loosen and remove bearing holddown bolts.  
4. Remove bearing support channels and inlet ring from one  
side.  
5. Remove fan shaft and fan wheel from unit.  
6. Remove fan shaft from fan wheel.  
Fig. 44 — Fan Shaft and Bearing Removal  
(Unit without IGVs shown)  
7. Replace shaft and wheel into fan in the reverse order of  
their removal.  
8. Inspect bearings and if serviceable, replace on shaft.  
9. Align fan wheel and shaft assembly in fan scroll. Check  
cutoff location if wheel failure damaged cutoff plate. See  
Fig. 45.  
10. Tighten bearing holddown bolts, bearing setscrews and  
shaft setscrews.  
11. Field balancing of shaft and wheel is recommended.  
IMPORTANT: Replacement shafts must have a diam-  
+ .0000  
eter tolerance at bearing mount of  
nominal.  
– .001  
Carrier-specified parts are recommended.  
Lubrication  
MOTORS — Lubricate in accordance with nameplate at-  
tached to motor or with manufacturer’s recommendations  
included with motor.  
CUTOFF  
A
CUTOFF CLEARANCE  
39L UNIT SIZE  
B
BEARINGS  
7
03  
06  
08  
10  
12  
15  
18  
21  
25  
65/8  
/
8
Fan Bearings — Lubricate fan bearings every 3 months  
with suitable bearing grease. Typical lubricants are given in  
Table 13.  
Inlet Vane and Outlet Damper Bearings — These bearings  
are oil-impregnated. Annually lubricate with a few drops of  
nondetergent SAE (Society of Automotive Engineers) 20 oil.  
8
1
103/8  
93/4  
93/4  
12  
11/2  
13/8  
13/8  
15/8  
2
153/4  
153/4  
201/2  
2
211  
/
16  
Table 13 — Lubricant Data  
Fig. 45 — Fan Cutoff Plate Data (in.)  
MANUFACTURER  
LUBRICANT  
Sunoco  
Texaco  
Texaco  
Mobil  
Prestige 42  
Multipak 2  
Regal AFB-2*  
Mobilplex EP No. 1  
*Preferred lubricant because it contains rust and oxi-  
dation inhibitors.  
38  
METRIC CONVERSION CHART  
39  
Copyright 2004 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 533-932  
Printed in U.S.A.  
Form 39L-6SI  
Pg 40  
1110  
2-04  
Replaces: 39L-5SI  

Acer AL1516W User Manual
Brother MFC 7360N User Manual
Cisco Systems OL 23857 01 User Manual
Energizer Battery Charger CHVCM3 User Manual
Epson Stylus SX420W User Manual
Friedrich MR18Y3F User Manual
Graco Baby Accessories PD212022B User Manual
Haier Air Conditioner AC60FS1ERA User Manual
Havis Shields Slide Out Radio Tray C 3190 User Manual
HP Hewlett Packard HP PhotoSmart 5514 E all in one CQ183A#B1H User Manual