| installation, start-up and   service instructions   619FNF   619FNQ   Sizes 018-03036   IN-CEILING CASSETTE   FAN COIL UNITS   Cancels: New   II 619F-18-1   4/1/06   CONTENTS   GENERAL   Page   CAUTION: This system uses Puron® refrigerant   (R-410A), which has higher pressures than R-22 and   other refrigerants. No other refrigerant may be used in   this system. All equipment must be designed to handle   R-410A refrigerant. If unsure about equipment, consult   the equipment manufacturer.   SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1   GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1   INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-19   I. Step 1 — Complete Pre-Installation Checks . . . . . . 2   II. Step 2 — Locating and Mounting the Unit. . . . . . . . 6   III. Step 3 — Locating and Mounting the Room   Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8   CAUTION: Do not operate the unit without a filter   or with the grille removed. Damage to the unit or per-   sonal injury may result.   IV. Step 4 — Complete Refrigerant Piping   Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10   V. Step 5 — Make Electrical Connections . . . . . . . . . 11   INSTALLATION OPTIONS . . . . . . . . . . . . . . . . . . . . . . . .19-22   I. Fresh Air Intake . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19   II. Conditioned Air Supply to Adjacent Room . . . . . . 19   III. Room Controller Configuration Setup. . . . . . . . . . 21   IV. Louver Mode Selection . . . . . . . . . . . . . . . . . . . . . . 21   V. Main Board Configuration. . . . . . . . . . . . . . . . . . . . 21   These instructions cover the installation, start-up and service   of in-ceiling cassette fan coil units. See Fig. 1.   The following accessories can be used with 619FNF, FNQ   units. See the price pages for part numbers and additional   information for the following accessories:   • photocatalytic and electrostatic filter with mount   • air supply outlet obstruction kit   • wired room controller   • room controller wiring kit for multiple units   • zone manager kit for multiple units   • zone manager   START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22,23   SERVICE AND MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . 23   TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .23,24   SAFETY CONSIDERATIONS   • infrared remote kit   Installing and servicing air-conditioning equipment can be   hazardous due to system pressure and electrical components.   Only trained and qualified service personnel should install or   service air-conditioning equipment.   Untrained personnel can perform basic maintenance, such as   cleaning and replacing filters. All other operations should be   performed by trained service personnel. When working on air   conditioning equipment, observe safety precautions in litera-   ture, tags, and labels attached to unit.   Follow all safety codes. Wear safety glasses and work gloves.   Use quenching cloth for brazing operations. Have fire extin-   guisher available. Read these instructions thoroughly. Con-   sult local building codes and the National Electrical Code   (NEC) for special installation requirements.   WARNING: Before installing or servicing system,   always turn off main power to system. There may be   more than one disconnect switch. Turn off accessory   heater power if applicable. Electrical shock can cause   serious personal injury.   Fig. 1 — 619FNF, FNQ Unit   1?10-5/8?(?575)   1' -10-5/8"(575)   3/8"(9)   2"(52)   Ø 2-3/14" (70)   0 5 1 ( 1 -5/16"(49)   2-13/64"(56)   " 2 3 / 9 2 - 5 Ø ) 2'-4-11/32"(720)   1'-9-21/32"(550)   Supply air   Supply air   Return air   619FNF018   Ø1"(25)   2 " (50)   1-7/8"(47)   2'-8-1/2"(825)   2'-8-1/2"(825)   1 -31/32"   (50)   ) 0 11-57/64"   (302)   5 1 ( " 2 3 / 9 2 - 5 Ø Supply air   Supply air   Return air   1'-11-7/16"(595)   619FNF024, 03036 / 619FNQ01824, 03036   ) 0 5 1 ( " 2 / 9 2 - 5 Ø3-15/16"   (100)   2 - 5 / 8 " ( 6 6 7 ) / 8 " ( 4 8 ) ) 9 4 ( " 6 1 / 5 1 - 1 NOTE: Dimensions in ( ) are in mm.   Fig. 2 — Unit Dimensions   —3—   Table 4A — 619FNF Physical Data   018   SYSTEM SIZE   NOMINAL CAPACITY (Btuh)   OPERATING WEIGHT (lb)   SEER   024   030   29,000   95   036   36,400   95   17,000   49   23,600   91   13   REFRIGERANT*   Control (Cooling)   R-410A   AccuRator Control   INDOOR FAN   Direct Drive Centrifugal   Rpm/Cfm High   1000/470   890/420   730/340   120   440/690   660/910   550/760   470/670   210   660/910   550/760   470/670   210   Rpm/Cfm Medium   Rpm/Cfm Low   360/560   300/470   110   Motor Watts   Blowers Quantity...Size (in.)   1...11.1   INDOOR COIL   Face Area (sq ft)   No. of Rows   Fins/in.   Copper Tube, Aluminum Fin   3.2   2 22   5 4.8   2 4.6   3 4.6   3 18   10   18   6 18   10   Circuits   FILTERS   Quantity...Size (in.)   Cleanable   1...17 x 16   AIRSWEEP   Horizontal   OPERATING LIMITS   Cooling (Min/Max)   Auto/Preset   55 F/125 F   CONTROLS   Integrated Microprocessor   Remote Controller Options   Diagnostics   Wireless, CRC   Yes   Defrost Method   Timer Mode   Warm Start Feature   Test Mode   Freeze Protection   Dehumidification Mode   Fan Mode   Auto Changeover   Auto Restart   Control Voltage   System Voltage   Demand Defrost   Yes   Yes   Yes   Yes   Yes   High/Medium/Low/Auto   Yes   Yes   24   208/230   REFRIGERANT LINES   Connection Type   Flare   Flare   Flare   Flare   3 3 3 3 Mixed-Phase Line (in.) OD   Vapor Line (in.) OD   / / / / 8 8 8 8 5 5 3 3 / / / / 8 8 4 4 Max Length (ft)   Max Lift (Fan Coil Above) (ft)   Max Lift (Fan Coil Below) (ft)   200   60   200   60   200   60   200   60   60   60   60   60   CONDENSATE DRAIN SIZE (in.)   1 1 1 1 LEGEND   CRC — Carrier Room Controller   SEER — Seasonal Energy Efficiency Ratio   *See Table 3 for factory charge and additional field charge requirements.   —4—   Table 4B — 619FNQ Physical Data   018   SYSTEM SIZE   024   030   036   NOMINAL CAPACITY (Btuh)   Heat Pump   Cooling   17,900   16,800   17,000   22,600   20,800   22,600   29,200   27,400   29,000   33,400   32,400   36,000   Heating   Cooling with Electric Heat   SEER   13   HSPF   7.7   OPERATING WEIGHT (lb)   91   91   95   95   REFRIGERANT*   Control (Cooling)   Control (Heating)   R-410A   AccuRator Control   AccuRator Control   INDOOR FAN   Direct Drive Centrifugal   Rpm/Cfm High   440/690   360/560   300/470   110   440/690   660/910   550/760   470/670   210   660/910   550/760   470/670   210   Rpm/Cfm Medium   Rpm/Cfm Low   360/560   300/470   110   Motor Watts   Blowers Quantity...Size (in.)   1...18   INDOOR COIL   Face Area (sq ft)   No. of Rows   Fins/in.   Copper Tube, Aluminum Fin   4.8   2 18   6 4.8   2 4.6   3 4.6   3 18   10   18   6 18   10   Circuits   FILTERS   Quantity...Size (in.)   Cleanable   1...24 x 235/16   AIRSWEEP   Horizontal   Auto/Preset   OPERATING LIMITS   Heating (Min/Max)   Cooling (Min/Max)   15 F/75 F   55 F/125 F   CONTROLS   Integrated Microprocessor   Remote Controller Options   Diagnostics   Wireless CRC   Yes   Defrost Method   Timer Mode   Warm Start Feature   Test Mode   Freeze Protection   Dehumidification Mode   Fan Mode   Auto Changeover   Auto Restart   Control Voltage   System Voltage   Demand Defrost   Yes   Yes   Yes   Yes   Yes   High/Medium/Low/Auto   Yes   Yes   24   208/230   REFRIGERANT LINES   Connection Type   Flare   Flare   Flare   Flare   3 3 3 3 Mixed-Phase Line (in.) OD   Vapor Line (in.) OD   / / / / 8 8 8 8 5 5 3 3 / / / / 8 8 4 4 Max Length (ft)   Max Lift (Fan Coil Above) (ft)   Max Lift (Fan Coil Below) (ft)   200   60   200   60   200   60   200   60   60   60   60   60   CONDENSATE DRAIN SIZE (in.)   1 1 1 1 LEGEND   CRC — Carrier Room Controller   HSPF — Heating Seasonal Performance Factor   SEER — Seasonal Energy Efficiency Ratio   *See Table 3 for factory charge and additional field charge requirements.   —5—   II. STEP 2 — LOCATING AND MOUNTING THE UNIT   A. Locating the Unit   cable (see Fig. 2 for dimensions). The cardboard template   (supplied with the unit) may be used as a guide. Depending   on the type of ceiling, the hangers can be fixed as shown in   Fig. 5.   Install the unit as centrally as possible in the room. The air-   flow direction can be controlled by the remote control (where   used) or automatically, according to the unit operating mode   (cooling or heating). Controlling the airflow automatically   will ensure optimum distribution of the air in the room.   Once the threaded hangers have been positioned, do not   tighten the nuts. Insert the washers as shown in Fig. 5. First   position the refrigerant lines, which will be connected in the   Complete Refrigerant Piping Connections section. Remove   the “T” bar in the ceiling to facilitate installation. See Fig. 6.   In Cooling mode, the louvers should be positioned so that the   air is directed towards the ceiling. Refer to Fig. 3. In Heating   mode, the louvers should be positioned so that the air is   directed toward the floor to prevent layers of hot air forming   close to the ceiling. Refer to Fig. 3. The louvers will be auto-   matically positioned when the louvers are set to Automatic   mode. Alternatively, the louvers can be placed in intermedi-   ate positions (with infrared remote accessory kit only) or   allowed to move continuously (Swing mode).   Carefully lift the unit (without the frame) using the four sus-   pension brackets (or the four corners), and insert it into the   false ceiling. If the “T” bar cannot be removed from the ceil-   ing the unit may need to be tilted. See Fig. 7.   NOTE: Tilting the unit may only be carried out with false   ceilings with a minimum height of 11 ft-13/16 inches.   Align and level the unit by adjusting the nuts and locknuts   on the threaded hangers, maintaining a distance of 1 in. to   13/16 in. between the sheet metal body and the underside of   the false ceiling. See Fig. 8. Reposition the “T” bar and align   the unit in relation to the bar by tightening the nuts and   locknuts. After connection of the condensate drain line and   the refrigerant lines, carry out a final check to make sure   that the unit is level.   In order to allow easy and rapid installation and mainte-   nance, ensure that the unit is mounted in a location that is   easily accessible.   Restricting Air Outlets   A maximum of two air outlets can be restricted at one time.   See Fig. 3. The air supply outlet obstruction accessory kit   can be used to obstruct air outlets. Contact your local dealer   for more information.   Drilling the Hole for Connection Pipes in the External Wall   After positioning the units and determining the connection   position, drill a 23/4 in. hole in the wall. The same hole can be   used as a condensate drain pipe conduit. The hole should   B. Mounting the Unit   Use a stacker to lift the unit to the installation location.   Refer to Fig. 4. If the mounting location is in a plaster board   ceiling, the maximum dimensions of the unit housing cutout   must not exceed 2 ft, 2 in. square for 619FNF018 units and   2 ft, 11 in. square for 619FNF024, 03036 and 619FNQ01824,   03036 units.   3 3 have a /16 in. to /8 in. slope toward the outside. Refer to   Fig. 9. Insert the plastic conduit. Pass the power connection   cables through the conduit. The power connection cables will   be connected in the Make Electrical Connections section.   Running the Condensate Drain Piping   NOTE: In rooms with high humidity, brackets should be   insulated using self-adhesive insulation.   To ensure correct condensate water flow, the drain pipe   should have a gradient of 2% without obstructions. Addition-   ally, a trap of at least 2 in. depth should be made to prevent   unpleasant odors from reaching the room.   Mark the position of the hangers, refrigerant lines and con-   densate drain pipe, power supply cables and remote control   Max. 2 louvers closed   Heat pump: louver position for correct airflow.   Cooling: louver position for correct airflow.   Fig. 3 — Louver Positioning   —6—   Spirit   Level   False   Ceiling   1“ to 1-3/16”   Fig. 4 — Positioning Unit   Fig. 8 — Align and Level the Unit   Outdoor   3/16"÷3/8"   (5÷10 mm)   Indoor   Nut   Washer   Threaded hangers   Washers   Fig. 9 — Drilling for Connections   Threaded hangers   Wooden frame   Nut   Washer   Nut   The condensate may be discharged at a maximum height of   77/8 in. above the unit, as long as the ascending tube is verti-   cal and aligned with the drainage flange.   Nut   Fig. 5 — Attaching Hangers to Ceiling   If it is necessary to discharge the condensate from a level   above 77/8 in., install an auxiliary water discharge pump and   float valve. A float valve is recommended to stop the com-   pressor if there is a fault at the auxiliary pump.   The condensate pipe must be insulated with condensation   proof material such as polyurethane, propylene or neoprene   of 3/16 in. to 3/8 in. thickness. See Fig. 10.   Threaded hangers   CAUTION: The drain tube extension must be   securely fastened to the condensate drain. Failure to   do so could result in condensate water dripping on to   the floor, which could cause personal injury.   "T" bar   (to be removed)   Fig. 6 — Threaded Hangers and T Bar   NOTE: If more than one unit is installed in the room, the   drain system can be designed as shown in Fig. 10.   Installing the Grille and Frame Assembly   Carefully unpack the assembly and check for damage sus-   tained in transport. Attach the assembly to the unit by using   the two hooks. See Fig. 11. Tighten the four screws, link the   electrical connectors and insert the wires in the cable clamp.   Use the screws supplied to fix the frame in to position. See   Fig. 12.   Threaded Hangers   Threaded Hangers   T-Bar   Ensure that the frame is not distorted by excessive tighten-   ing, that it is aligned with the false ceiling and that there is   a seal between the air inlet and outlet. See Fig. 13. Gasket   “A” prevents return air from mixing with the supply air and   gasket “B” prevents the supply air from leaking into the ceil-   ing void. Once the unit is mounted in the ceiling, the gap   between the unit frame and the false ceiling must not be   more than 3/16 in. wide.   T-Bar   T-Bar   Supension Brackets   Supension Brackets   Fig. 7 — Positioning Unit in Ceiling   —7—   2%   2” (50 mm)   A. Gasket "A"   B. Gasket "B"   max.   7-7/8”(200 mm)   A AIR   B Fig. 10 — Condensate Drain Pipe   Fig. 13 — Gasket Location   Frame support brackets   III. STEP 3 — LOCATING AND MOUNTING THE ROOM   CONTROLLER   WARNING: Electrical shock can cause personal   injury and death. Shut off all power to this equipment   during installation. There may be more than one dis-   connect switch. Tag all disconnect locations to alert   others not to restore power until work is completed.   A. Locating the Room Controller   See Fig. 14 for room controller dimensions. If the air sensor   in the room controller is going to be used, the room controller   should be located by considering the following:   Fig. 11 — Attach Frame Assembly   • Position controller with a minimum clearance of 5 ft from   the floor.   • Locate the unit in the same area as the fan coil unit; pref-   erably on an inside partitioning wall.   • Locate on a section of the wall without pipes or ductwork.   • Do not locate close to a window, on an outside wall, or   next to a door leading to the outside.   • Do not locate where the controller is exposed to direct   light and heat from a lamp, sun, fireplace, or other tem-   perature-radiating object that may cause a false reading.   • Do not locate close to, or in direct airflow of, a heating or   cooling supply.   • Do not locate in areas with poor circulation, such as   behind a door or in an alcove.   Safety cord   Cable clamp   Power connection   cables from unit   Power connection   cables from frame   Frame support   screws   NOTE: Do not exceed 500 ft of network wiring when mount-   Fig. 12 — Fix Frame in Position   ing the room controller.   —8—   3/4"(20mm)   4-1/4" (108mm)   Fig. 14 — Room Controller Dimensions   B. Mounting the Room Controller (Fig. 15-17)   Unscrew the side fixing screw. Open the room controller rear   mounting base to expose the mounting holes. The base can   be removed to simplify mounting (snap apart carefully at   hinge to separate mounting base from the rest of the room   controller). Route the room controller wires through the   large hole in the mounting base. Level the mounting base   against the wall (for aesthetic value only, as the room con-   troller does not need to be level for proper operation) and   P G C mark the wall through the two mounting holes. Drill two   Connection Cable   Fig. 16 — Locating the Connection Cable   3 / 16 in. mounting holes in the wall where marked. Secure the   mounting base correctly (UP) to the wall with the two screws   and two anchors provided, (additional anchoring holes are   available for more secure mounting if necessary) making   sure all wires extend through the hole in the mounting base.   Adjust the length and routing of each wire to reach the   proper terminal in the connector block on the mounting base,   with 1/4 in. of extra wire (strip only 1/4 in. of insulation from   each wire to prevent adjacent wires from shorting together   when connected).   Match and connect equipment wires to proper terminals in   the connector block. Both power and communication wires   must be connected correctly for proper room controller   operation.   Push any excess wire into the wall and against mounting   base. If the air sensor is being used on the room controller,   seal the hole in the wall to prevent air leaks. Leaks can   affect sensor operation.   P G C Push the room controller snap hinge to the base and tighten   the side fixing screw.   Connection Cable   Fig. 17 — Connecting the Room Controller   Mounting screws   P G C Fig. 15 — Mounting the Room Controller   —9—   IV. STEP   CONNECTIONS   4 — COMPLETE REFRIGERANT PIPING   If either refrigerant tubing or indoor coil is exposed to the   atmosphere, the system must be evacuated following good   refrigeration practices.   IMPORTANT: During unit installation make the refrigerant   connections first and then the electrical connections. If the   unit is uninstalled, disconnect the electrical cables first and   then the refrigerant connections. Refer to the outdoor unit   installation instructions for tube sizing and limitations.   Use field-supplied refrigerant grade piping designed for use   with R-410A refrigerant.   A. Flaring the Ends of Pipes   Remove the protective caps from the copper pipe ends. Hold-   ing the tube downward, cut the extreme end off, removing   any copper shavings with a deburring blade. Remove the   flare nuts from the “FLARE” connection body of the indoor   unit and insert them into the pipes. Make the flare to the   pipe end with the proper flaring tool. The flare end must not   have any burrs or imperfections. The length of the flared   walls must be uniform. See Fig. 18 and 19.   Fig. 18 — Removing Burrs   Lubricate the end of pipe and the thread of the flare connec-   tion with anti-freeze oil. Tighten by hand and then use two   wrenches to tighten all connections fully, applying the tight-   ening torque shown in Table 5. Refer to Fig. 20.   L Table 5 — Tightening Torque   L TUBE DIAMETER   (in.)   TORQUE   (ft-lb)   3/8 in.   5/8 in.   3/4 in.   31   48   74   B. Piping Connection to the Unit   Use two wrenches to tighten all connections.   CAUTION: Insufficient tightening torque could   cause a refrigerant leak from the connection. Excessive   tightening torque will damage the pipe flare.   Fig. 19 — Flared Walls are Equal   Once all connections have been completed, check for leaks   using soapy water. If no leaks were found, wrap connections   with anti-condensate insulation and tighten with tape, with-   out exerting excessive pressure on the insulation. Repair and   cover any possible cracks in the insulation.   1 CAUTION: DO NOT BURY MORE THAN 36 IN.   OF REFRIGERANT PIPE IN THE GROUND. If any   section of pipe is buried, there must be a 6-in. vertical   rise to the valve connections on the outdoor unit. If   more than the recommended length is buried, refriger-   ant may migrate to cooler, buried section during   extended periods of system shutdown. This causes   refrigerant slugging and could possibly damage the   compressor at start-up.   3 Adjustable wrench or torque wrench   Outdoor end   2 Indoor end   Fig. 20 — Tightening Connections   —10—   V. STEP 5 — MAKE ELECTRICAL CONNECTIONS   unit, readily accessible, but out of reach of children. Provi-   sion for locking the switch open (off) is advisable to prevent   power from being turned on while unit is being serviced. Dis-   connect switch, fuses, and field wiring must comply with the   NEC and local code requirements. Use copper wire only   between the disconnect switch and unit. Use minimum 60 C   wire for the field power connection.   WARNING: Unit cabinet must have an uninter-   rupted, unbroken electrical ground to minimize the   possibility of personal injury if an electrical fault   should occur. This ground may consist of electrical   wire connected to unit ground lug in control compart-   ment, or conduit approved for electrical ground when   installed in accordance with NEC, and local electrical   codes. Failure to follow this warning could result in the   installer being liable for the personal injury of others.   Remove the external box cover. Route the low voltage wires   from the outdoor unit to the indoor unit:   7 1. Place wiring through /8 in. knockouts on the left or   right hand side of external control box (low voltage   side).   CAUTION: Unit failure as a result of operation on   improper line voltage or excessive phase imbalance   constitutes abuse and may cause damage to electrical   components. Such operation would invalidate any   applicable Bryant warranty.   2. Connect the R and Y wires to the 2 pin terminal block   for cooling only units (619FNF) and heat pump units   (619FNQ) that are matched to 538ENF outdoor units.   3. Connect the R, Y, O, G, DT, A, and B wires to the   (PGB-1) 1 terminal for 619FNQ indoor units matched   with 538QNF outdoor units.   WARNING: Electrical shock can cause personal   injury and death. Shut off all power to this equipment   during installation. There may be more than one dis-   connect switch. Tag all disconnect locations to alert   others not to restore power until work is completed.   Route the line power leads from the indoor disconnect to the   fan coil unit.   7 1. Place wiring through /8 in. or 11/8 in. knockouts on   the left and on the right hand side of external control   box (high voltage side).   2. Connect L1 to the black wire and L2 to the red wire   using wire nuts and fix the ground wire between the   2 washers.   See Tables 6A and 6B for electrical information.   A. Units With Electric Heater   The unit is equipped with two thermostats: one with auto-   matic reset and one with manual (electric) reset that can be   reactivated by switching the power supply off and then   back on.   See Fig. 27 for a view of the internal control panel. The inter-   nal control panel can be accessed by opening the grille and   removing the metal cover attached by four screws.   NOTE: The internal control panel does not need to be   accessed during the installation process unless there is a   need for service.   B. Power Wiring (Fig. 21-26)   The unit is factory wired for voltage shown on nameplate.   Provide adequate, fused disconnect switch within sight from   Table 6A — 619FNF Fan Coil Electrical Data   VOLTAGE   RANGE*   FAN   POWER   MIN WIRE   SIZE   AWG   SYSTEM   SIZE   CONDENSATE   PUMP FLA   LOUVER   MOTOR FLA   V-PH-Hz   Motor Power   (Watts)   Min   Max   FLA   MCA   MOCP   018   024   030   036   208/230-1-60   208/230-1-60   208/230-1-60   208/230-1-60   187   187   187   187   253   253   253   253   0.55   0.50   0.95   0.95   120   110   210   210   0.06   0.06   0.06   0.06   0.01   0.01   0.01   0.01   0.8   0.7   1.3   1.3   15   15   15   15   14   14   14   14   LEGEND   AWG — American Wire Gage   FLA — Full Load Amps   MCA — Minimum Circuit Amps per NEC Section 430-24   MOCP — Maximum Overcurrent Protection   NEC — National Electrical Code   *Permissible limits of the voltage range at which unit will operate   satisfactorily.   NOTE: In compliance with NEC requirements for multimotor and combina-   tion load equipment (refer to NEC Articles 430 and 440), the overcurrent pro-   tective device for the unit shall be fuse or equipped with a breaker.   Table 6B — 619FNQ Fan Coil Electrical Data   VOLTAGE   RANGE*   ELECTRIC   HEATERS   MIN   WIRE   SIZE   AWG   FAN   POWER   SYSTEM   SIZE   CONDENSATE   PUMP FLA   LOUVER   MOTOR FLA   V-PH-Hz   Motor Power   (Watts)   Min   Max   FLA   kW   FLA   MCA MOCP   018   024   030   036   208/230-1-60   208/230-1-60   208/230-1-60   208/230-1-60   187   187   187   187   253   253   253   253   0.50   0.50   0.95   0.95   110.0   110.0   210.0   210.0   0.06   0.06   0.06   0.06   0.01   0.01   0.01   0.01   3 3 3 3 12.5   12.5   12.5   12.5   16.3   16.3   16.9   16.9   20   20   20   20   12   12   12   12   LEGEND   AWG — American Wire Gage   FLA — Full Load Amps   MCA — Minimum Circuit Amps per NEC Section 430-24   MOCP — Maximum Overcurrent Protection   NEC — National Electrical Code   *Permissible limits of the voltage range at which unit will operate   satisfactorily.   NOTE: In compliance with NEC requirements for multimotor and combina-   tion load equipment (refer to NEC Articles 430 and 440), the overcurrent pro-   tective device for the unit shall be fuse or equipped with a breaker.   —11—   Room Controller   Connections   Low   Voltage   Outdoor Unit   Connections   Power   Connections   Ground   Connection   High   Voltage   Fig. 21 — 619FNF Unit Matched to 538ENF Outdoor Unit — Wiring Connection   (Cooling Only System)   —12—   Room Controller   Connections   Low   Voltage   Outdoor Unit   Connections   Power   Connections   Ground   Connection   High   Voltage   Fig. 22 — 619FNQ Unit Matched to 538ENF Outdoor Unit — Wiring Connection   (Cooling with Electric Heat System)   —13—   Room Controller   Connections   Low   Voltage   Outdoor Unit   Connections   Power   Connections   Ground   Connection   High   Voltage   Fig. 23 — 619FNQ Unit Matched to 538QNF Outdoor Unit — Wiring Connection   (Heat Pump System)   —14—   DISPLAY   TM-COIL   TM-AIR   MODULAR "D"   CONTROL 1PCB   BARE COPPER   TO UNIT DISCONNECT   (USE CABLE PROVIDED)   EQUIP. GND   619FNF GLOBAL CASSETTE   538ENF OUTDOOR CONDENSER   NOTE 7   EQUIP GND   208/230V   1PH   (SEE NOTE 9)   TO OUTDOOR   UNIT DISCONNECT   TO CASSETTE   TO CASSETTE   NOTE 8   NOTES:   LEGEND   1. If any of the original wire furnished must be replaced, it must be   replaced with Type 90° C wire or its equivalent.   2. Wire in accordance with National Electrical Code (NEC) and local   codes.   1PCB   — Main Control Printed   OFM   OL   S — — — — — Outdoor Fan Motor   Overload   Emergency   Terminal Block   Sensor   Circuit Board   2PCB   C CAP   CH   — — — — — — — — — Display Board   Contactor   3. Compressor and fan motors are protected by internal thermal   overloads.   TB   TM   Capacitor   Crankcase Heater   Crankcase Heater Switch   Compressor   4. Indoor unit transformer has internal 2A thermal fuse on the primary   side.   5. Infrared (IR) connection to be inserted on “J5” (replace the actual   factory-installed “CRC” connector) for IR option.   6. Terminal strip for Carrier Room Controller (CRC) connection.   7. Compressor crankcase heater installed on 538QNF035 and   538QNF030 only.   8. Outdoor unit transformer is factory wired for 230 v. For 208 v move   the black wire to the 208-v tap.   9. Use minimum 60° C wire for the field power wiring.   TRAN — Transformer   CHS   COMP   CRC   DP   Terminal (Marked)   Carrier Room Controller   Drain Pump   Equipment Ground   Terminal (Unmarked)   Splice   EQUIP.   GND   FC   Terminal Block   — — — — — — — — Fan Capacitor   Float Switch   Ground   High Pressure Switch   Indoor Fan Motor   Infrared   Indoor Test Point   Liquid Low Pressure   Switch   Louver Motor   Louver Micro Switch   FS   Factory Wiring   GND   HPS   IFM   Field Control Wiring   Field Power Wiring   Accessory or Optional Wiring   Plug Connector   THERMISTOR EQUIVALENCE   IR   TEMPERATURE   RESISTANCE   Ω ITP   °F   95   72   32   °C   35   22   0 LLPS   6,500   11,400   32,500   LM   LMS   — — NOTE: All thermistors are identical.   Fig. 24 — 619FNF/538ENF Cooling Only System Wiring Diagram   —15—   DISPLAY   TM-COIL   TM-AIR   MODULAR "D"   CONTROL 1PCB   BARE COPPER   TO UNIT DISCONNECT   (USE CABLE PROVIDED)   EQUIP. GND   619FNQ GLOBAL CASSETTE   538ENF OUTDOOR CONDENSER   EQUIP GND   208/230V   1PH   NOTE 7   (SEE NOTE 9)   TO OUTDOOR   UNIT DISCONNECT   TO CASSETTE   TO CASSETTE   NOTE 8   NOTES:   LEGEND   1. If any of the original wire furnished must be replaced, it must be   replaced with Type 90° C wire or its equivalent.   2. Wire in accordance with National Electrical Code (NEC) and local   codes.   1PCB   — Main Control Printed   Circuit Board   LMS   OFM   OL   S — — — — — — — Louver Micro Switch   Outdoor Fan Motor   Overload   2PCB   3PCB   — — Display Board   Printed Circuit Board for   Electric Heat   Contactor   Capacitor   3. Compressor and fan motors are protected by internal thermal   overloads.   Emergency   ST   Safety Thermostat   Terminal Block   Sensor   C CAP   CH   CHS   COMP   CRC   DP   — — — — — — — — — 4. Indoor unit transformer has internal 2A thermal fuse on the primary   side.   5. Infrared (IR) connection to be inserted on “J5” (replace the actual   factory-installed “CRC” connector) for IR control.   6. Terminal strip for Carrier Room Controller (CRC) connection.   7. Compressor crankcase heater installed on 538QNF035 and   538QNF030 only.   8. Outdoor unit transformer is factory wired for 230 v. For 208 v move   the black wire to the 208-v tap.   9. Use minimum 60° C wire for the field power wiring.   TB   TM   Crankcase Heater   Crankcase Heater Switch   Compressor   TRAN — Transformer   Terminal (Marked)   Carrier Room Controller   Drain Pump   Terminal (Unmarked)   Splice   E-HTR   EQUIP.   GND   FC   Electric Heater   Equipment Ground   Terminal Block   — — — — — — — — Fan Capacitor   Float Switch   Ground   High Pressure Switch   Indoor Fan Motor   Infrared   Factory Wiring   THERMISTOR EQUIVALENCE   FS   GND.   HPS   IFM   TEMPERATURE   RESISTANCE   Ω Field Control Wiring   Field Power Wiring   Accessory or Optional Wiring   Plug Connector   °F   95   72   32   °C   35   22   0 6,500   11,400   32,500   IR   ITP   Indoor Test Point   Liquid Low Pressure   Switch   LLPS   NOTE: All thermistors are identical.   LM   — Louver Motor   Fig. 25 — 619FNQ/538ENF Heat/Cool System Wiring Diagram with Electric Heaters   —16—   DISPLAY   TM-COIL   TM-AIR   OUTDR DEFROST   MODULAR "D"   CONTROL 1PCB   BARE COPPER   TO UNIT DISCONNECT   (USE CABLE PROVIDED)   EQUIP. GND   619FNQ GLOBAL CASSETTE   538QNF OUTDOOR CONDENSER   208/230V   1PH   EQUIP GND   NOTE 7   (SEE NOTE 9)   TO OUTDOOR   UNIT DISCONNECT   TO CASSETTE   TO CASSETTE   TO CASSETTE   TO CASSETTE   TO CASSETTE   TO CASSETTE   TO CASSETTE   TO CASSETTE   NOTE 8   LEGEND   NOTES:   1. If any of the original wire furnished must be replaced, it must be   replaced with Type 90° C wire or its equivalent.   2. Wire in accordance with National Electrical Code (NEC) and local   codes.   1PCB   — Main Control Printed   Circuit Board   OAS   — — — — — — — — — Outdoor Air Sensor   Outdoor Fan Motor   Outdoor Fan Relay   Overload   OFM   OFR   OL   2PCB   3PCB   — — Display Board   Printed Circuit Board for   Electric Heat   3. Compressor and fan motors are protected by internal thermal   overloads.   RVS   S Reversing Valve Solenoid   Emergency   C CAP   CH   — — — — — — — — — Contactor   4. Indoor unit transformer has internal 2A thermal fuse on the primary   side.   5. Infrared (IR) connection to be inserted on “J5” (replace the actual   factory-installed “CRC” connector) for IR option.   6. Terminal strip for Carrier Room Controller (CRC) connection.   7. Compressor crankcase heater installed on 538QNF035 and   538QNF030 only.   8. Outdoor unit transformer is factory wired for 230 v. For 208 v move the   black wire to the 208-v tap.   9. Use minimum 60° C wire for the field power wiring.   Capacitor   ST   Safety Thermostat   Terminal Block   Sensor   Crankcase Heater   TB   CHS   COMP   CRC   DFT   DP   Crankcase Heater Switch   Compressor   TM   TRAN — Transformer   Carrier Room Controller   Defrost Thermostat   Drain Pump   Terminal (Marked)   Terminal (Unmarked)   Splice   E-HTR   Electric Heater   EQUIP. — Equipment Ground   GND   Terminal Block   FC   — — — — — — — — — — Fan Capacitor   THERMISTOR EQUIVALENCE   FS   Float Switch   TEMPERATURE   RESISTANCE   Ω Factory Wiring   GND   HPS   IFM   IR   Ground   °F   95   72   32   °C   35   22   0 High Pressure Switch   Indoor Fan Motor   Infrared   Field Control Wiring   Field Power Wiring   Accessory or Optional Wiring   Plug Connector   6,500   11,400   32,500   ITP   Indoor Test Point   Liquid Low Pressure Switch   Louver Motor   LLPS   LM   NOTE: All thermistors are identical.   LMS   Louver Micro Switch   Fig. 26 — 619FNQ/538QNF Heat Pump System Wiring Diagram with Electric Heaters   —17—   CA   CLR   CG   CP   CV   C G CV   CP   CLR   CA   INTERNAL CONTROL PANEL   619FNF018   INTERNAL CONTROL PANEL   619FNF024, 03036   619FNQ01824, 03036   Capacitor   GMC board   Electric heater board   (only on models with electric heater)   Transformer   Holes for fixing panel in position   Emergency push-button   CV   Fan connector   LED/RECEIVER connector   Float connector   Pump connector   Louver connector   CLR   CG   CP   CA   Fig. 27 — Internal Control Panel   —18—   C. Wiring the Room Controller   INSTALLATION OPTIONS   The room controller is capable of controlling from 1 to 6 fan   coil units. The total run length of the wire connecting the   room controller to the fan coil units should be kept to under   500 feet. Wire the room controller to the unit using daisy   chain wiring. See Fig. 28. The room controller connects to   the receiver board connection on the electronic board inside   the unit.   The 619FNF, FNQ units can be used to cool an adjacent   room or for fresh-air ventilation. Plan the installation care-   fully. Measure carefully and follow acceptable building prac-   tices and the National Electric Code (NEC).   I. FRESH AIR INTAKE   1. Using Fig. 30, locate and remove the factory-installed   insulation from the side of the unit where the   pre-punched knockouts are located.   Wiring the Power Connection to the Room Controller   The thermostat will be powered by unregulated nominal   12.5 volts DC (10V min to 20V max) which is provided by the   electronic board inside the unit. The power consumption will   be 50 mA 12.5 volts DC. For applications where more than   one fan coil unit is to be controlled, the fan coil unit closest to   the room controller will be the only one that supplies power   to the room controller. The control should be protected from   damage in case of accidental wiring of power, ground and   signal wiring occurs.   2. Remove the pre-punched knockouts for fresh air   intake. Refer to Fig. 30. Be careful not to damage   internal parts such as the heat exchanger coil.   3. If installing a 619FNF018 unit, install baffle. Refer to   Fig. 30.   4. Install ductwork using field-supplied, insulated flex   duct, or insulated sheet metal suitable for working   temperatures up to 140 F. Conduits can be of flexible   polyester (with spiral core) or corrugated aluminum,   externally covered with anti-condensate material   (fiberglass from 1/4 in. to 1 in. thickness).   Wiring the Room Controller to the Indoor Unit   Loosen the screws of terminals P (DC Power), G (GROUND)   and C (SIGNAL) on the indoor unit and room controller   terminal blocks. Refer to Fig. 29 and connect the indoor unit   terminal block to the room controller terminal block.   5. Use Fig. 31 to determine the allowable static pres-   sure loss for the ductwork airflow. The ductwork   design must not exceed this value or the job airflow   requirements will not be met.   6. Use a field-supplied fan if airflow does not meet job   requirements. The field-supplied fan motor for out-   side air intake must be controlled by a bipolar ON/   OFF switch with safety fuses.   REMOTE   FCU 1   FCU 2   FCU 3   FCU 6   IMPORTANT: Ventilated air must not exceed 10% of the total   airflow or problems with operation will result. If the venti-   lated air surpasses 10% of the total airflow, a field-supplied   primary air treatment system with separate deflectors is   recommended.   7. Install an air inlet grille with filter inspection port to   prevent dust and dirt from entering and fouling the   indoor unit heat exchanger. Filter installation also   makes the installation of a duct closing damper dur-   ing shutdown periods unnecessary.   8. All non-insulated ducts must be covered with anti-   condensate insulation (such as expanded neoprene,   1/4 in. thickness).   Fig. 28 — Room Controller Daisy Chain Wiring   (Multidrop)   II. CONDITIONED AIR SUPPLY TO ADJACENT ROOM   Diagram 1   Air supply to an adjacent room requires that the outlet corre-   sponding with the duct is closed, using the air supply outlet   obstruction accessory kit.   NOTE: The accessory kit cannot be used in units equipped   with an electric heater.   Red   Black   White   P P G C G C An air inlet grille must be fitted (if possible near the floor)   between the air conditioned room (where the unit is situ-   ated) and the adjacent room or, alternatively, the door must   be undercut, as shown in Fig. 30. The duct lengths can be   calculated in accordance with Fig. 30, also taking into   account the pressure drop through air diffusers and fresh air   filters.   A B Remote connector   (J5) 5 pins   Main electronic card   4 pins terminal block placed on external   control box   A B Indoor unit   Wires supplied by the installer   Terminal block in the Room Controller   Room Controller   IMPORTANT: DO NOT use active carbon or electrostatic   filter kits for ducts towards adjacent rooms.   Fig. 29 — Wiring the Room Controller to   the Indoor Unit   —19—   B Ø A   Ø C   Ø A   Duct connection flange   Clip   1/4" (6 mm) neoprene gasket   Insulated flexible duct   Fresh air intake   Conditioned air supply to an   adjacent room   Polystyrene partition   Baffle (619FNF018 only)   Frame   619FNF024, 03036   Unit   Ø A   B 619FNF018   5-29/32"(150 mm)   4-3/4"(120 mm)   2-3/4"(70 mm)   619FNQ01824, 03036   5-29/32"(150 mm)   4-3/4"(120 mm)   Ø C   3-15/16"(100 mm)   NOTE: Dimensions in ( ) are in mm.   Air intake grille   Wall   Undercut door   Wall-fitted grille   Door-fitted grille   Fig. 30 — Installation Options   Supply air duct to adjacent room   0.18   0.16   0.14   0.12   619FNF, FNQ03036   0.1   0.08   0.06   619FNF018, 024   619FNQ01824   0.04   0.02   0 150   200   250   0 50   100   Airflow (cfm)   NOTE: When two louvers are closed, the fresh airflow towards the adjacent room is 50% higher than when   one louver is closed (with equal static external pressure).   Fig. 31 — Pressure Drop for Conditioned Air Supply to an Adjacent Room: One Louver Closed   —20—   III. ROOM CONTROLLER CONFIGURATION SETUP   C — The Room Controller will allow and display the   following modes:   To configure the room controller, press the Mode button for   5 seconds. After 5 seconds, “10” will appear. This indicates   that the user is setting the first software configuration item.   To display the value of configuration item 10, press the Mode   button again. The value of the Heat/Cool vs Cooling only   remote configuration will be displayed along with the “Set   Temp” icon to indicate that the number displayed is the con-   figuration data. Refer to Table 7 for configuration values. To   change the Heat/Cool vs Cooling only remote Configuration,   press the Up and Down buttons. To move to the next setting,   press the Mode button again and the “10” will be displayed.   Press the up button and the display will change to “11.”   Refer to Fig. 32. The Mode button will toggle the display   between the items and the configuration value. The Up and   Down buttons will change either the index or the value,   whichever is displayed at the time. Press the Fan button to   exit the Configuration Setup Mode. This mode will exit auto-   matically after 10 seconds of inactivity. Once a configuration   value is changed, the last value displayed will be the new   configuration value for the room controller.   •Off   •Fan   •Cool   •Dry   2. Configuration Item 11: Room Thermistor Override   On — Room Thermistor Override is active. Units will   be controlled to the air temperature displayed via the   Room Controller.   Of (Off) — Room Thermistor Override is not active.   All units will be controlled to the room air ther-   mistors located on the units.   3. Configuration Item 12: Celsius vs Fahrenheit   C — Temperatures will be displayed in degrees   Celsius.   F — Temperatures will be displayed in degrees   Fahrenheit.   IV. LOUVER MODE SELECTION   NOTE: The only way to abort a configuration change is to   change the value back to its original value.   To enter louver mode selection, ensure the room controller is   on and then press the Fan button for 5 seconds. After 5 sec-   onds, the selected louver setting will be displayed. Press the   up and down arrows to modify the louver setting between   swing and auto. Refer to Fig. 33. The two settings will be dis-   played as follows:   Table 7 — Room Controller Configuration Values   ITEM   10   VALUE   DESCRIPTION   Heat/Cool Remote   Cooling Only Remote   H*   C S with Swing Louver Icon   A with Auto Louver Icon   Represents the swing louver   Represents the auto louver   Room Thermistor Override   Active.   On   Control and display room air   temperature at the room con-   troller. Room Thermistor Over-   ride Inactive. Do not display   room air temperature at the   room controller and control to   unit room air thermistor(s).   The fan icon will also be displayed in the louver mode. Press   Fan button to exit the Louver Mode selection. This mode will   exit automatically after 10 seconds of inactivity. The only   way to abort a louver change is to change the value back to   its original value.   11   Of*   Temperatures displayed in   degrees Celsius.   Temperatures displayed in   degrees Fahrenheit.   NOTE: If units are grouped to one room controller, all units   will have the same louver value. Louver Mode selection is   not available during OFF mode.   C*   F 12   V. MAIN BOARD CONFIGURATION   * Factory default.   To configure the main electronic board, push the Up and   Down arrows for 5 seconds while the room controller is off.   1. Configuration Item 10: Heat Pump vs Cooling Mode   H — The Room Controller will allow and display the   following modes:   After 5 seconds, a “20” will appear. This indicates that the   user is setting the first software configuration item. To check   the value of configuration item “20,” press the Mode button.   The value for the Heat Pump/AC Only configuration will be   displayed. To change the value, use the Up and Down   buttons. Once the desired value is selected, press the Fan   button to send that configuration data to the unit. Refer to   Table 8.   •Off   •Fan   •Auto   •Cool   •Dry   •Heat   up   Keep it pressed for   at least 5 seconds   Check the   value   Change the   value   Next   item   down   A To check/change   the values of items   11 and 12 go back   to point A   up   down   Fig. 32 — Room Controller Configuration Steps   —21—   up   Room Controller   ON   Keep it pressed   for 5 seconds   To change   the value   Automatic   (AUTO)   down   Or   Continuous   movement   (swing)   Fig. 33 — Selecting the Louver Mode   Down button to send a message of Off mode to the unit. Ser-   vice Test mode automatically times out after 30 minutes and   the remote will operate normally.   Table 8 — Modular Platform D Unit Configuration Values   ITEM   20   VALUE   1: Heat Pump   0: AC only (indoor unit with   or without electric heaters)   COMMENT   When test mode is selected, the unit will operate as   described below:   Unit Configuration   defaults to heat pump   • The Unit Status (Green) and Timer (Yellow) LEDs blink   every 2 seconds.   • The indoor fan will operate according to user-selected   speed. If user-selected speed is Auto, the fan will run in   High speed.   • If the unit is configured as an A/C Only unit, it will oper-   ate in cool mode with demand.   • If the unit is configured as a Heat Pump unit, the louver   will operate according to user-selected position. If user   selected louver is Auto, louver operates according to auto   heat or cool louver based on operating mode.   • The unit will run in cool mode for 3 minutes, then it will   run in heat mode for 2 minutes, or until the indoor coil is   greater than 104 F. The unit will run in cool mode until   test mode is exited.   CCN Address of the unit.   Defaults to 1.   21   1-199 in increments of 1   0-199 in increments of 1   To display the hundreds,   push   . Zone number -   Communications zone   the system is located in   Defaults to 0   22   24   To display the hundreds,   push   . 0: Start in Off mode   1: Start in last active mode   Auto Restart   Defaults to “On”   Only the current value being displayed is transmitted. Once   the Fan button is pressed, the room controller will switch to   displaying the configuration item number. To move to the   next setting, press the Mode button again and the “20” will   be displayed. Press the Up button and the display will   change to “21.” The Mode button will toggle the display   between the software configuration item number (i.e., “20,”   “21,” etc.) and the configuration value. The Up and Down   buttons will change either the item number or the value,   whichever is displayed at the time.   Any of the following will cancel the Service Test mode:   • When the unit is turned off by the controller.   • If the power is cycled during the Test Mode, the unit will   return to its normal operating mode.   • After 30 minutes of receiving the last valid test request   message.   • Fail Mode.   This mode will exit automatically after 30 seconds of   inactivity.   START-UP   The following checks should be made before system start-up.   Refer to outdoor unit Installation, Start-Up, and Service   manual for system start-up instructions and refrigerant   charging methods. Be sure to use the refrigerant charge   shown in Table 3.   NOTE: If units are grouped to one room controller, all units   will have the same configuration value.   VI. SERVICE TEST MODE   Prior to start-up, conduct the Service Test mode to ensure   the unit is ready for start-up.   1. Check condensate drainage system.   a. Remove grille and frame from the unit.   b. On the opposite side of the drain connection,   insert a water bottle up into the fan coil unit and   fill drain pan. Refer to Fig. 34. Water must flow   regularly with condensate pump energized. If   water does not, check the pipe slope or see if   there are any pipe restrictions.   There is a hidden Service Test mode that is initiated through   a combination of button presses when the remote is off. The   following buttons need to be pressed, in sequence, within   6 seconds:   1. Down arrow   2. Fan button   3. Up arrow   NOTE: The unit is equipped with a safety float   switch to deenergize the compressor if the drain   water level gets too high.   4. Fan button   5. Mode button   2. Make sure that all wiring connections are correct and   that they are tight.   Once in Service Test mode, the Service Test mode message   will be sent, and Sr will be displayed in the temperature   icons until the Down button is pressed. During Service Test   mode all the icons are off, and the only button that is active   is the Down button. To cancel Service Test mode, press the   3. Make sure that all barriers, covers, and panels are in   place.   —22—   2. Remove the air intake and distribution assembly.   Remove the condensate water in the drain pan by   pulling out the rubber drain plug and letting water   drain into a 3-gallon bucket.   CAUTION: Do not use a screw driver to pry drain   pan out of assembly. It could damage the pan.   3. Remove screws holding the drain pan. Carefully hold   the drain pan to remove it from the assembly.   4. Reinstall the drain pan using the appropriate num-   ber of screws. Center and align the metal fan inlet   orifice with the fan. Ensure the fan spins freely.   Fig. 34 — Inserting Water into Drain Pan   TROUBLESHOOTING   See Table 9 and Fig. 35 for troubleshooting information.   4. Ensure that the filters and return air grilles have   been installed and that the discharge louvers are   correctly positioned.   I. FAULT CODE   Once a failure occurs with the indoor unit in operation, the   green LED on the indoor unit flashes at intervals of 0.5 sec-   onds. The fault code is deduced from the number of times the   green LED flashes, blocking unit operation. Between one   flash cycle and the next one, a pause of 5 seconds elapses.   See Fig. 35.   CAUTION: Never operate unit without a filter or   with grille removed. Damage to the unit or personal   injury may result.   SERVICE AND MAINTENANCE   Table 9 — Fault Codes   Remove unit grille, filter, and condensate pan for cleaning,   lubricating, or replacing parts.   CODE   2 DESCRIPTION   Condensate discharge pump   Room air sensor fault   Indoor unit coil sensor fault   Filter dirty   CAUTION: To avoid personal injury or damage to   unit, do not service until all power sources are shut   down, locked out, and tagged out. Failure to do so could   result in personal injury or unit damage.   3 4 6*   7 Outdoor unit failure   I. MINIMUM MAINTENANCE   10   11   12   13   14   EEPROM corrupt   Card serial number damaged   Address or zone incomplete   Gas flow distributor corrupt   Outdoor air thermistor fault   1. Check, clean, or replace air filter each month or as   required.   2. Check cooling coil, drain pan, condensate trap, and   condensate drain pan each cooling season for cleanli-   ness. Clean as necessary.   *When code is enabled.   3. Check fan motor and wheel for cleanliness each heat-   ing and cooling season.   A. Using the Emergency Button   The Emergency button is for use by a qualified service tech-   nician only. The Emergency button is for use when the room   controller is inoperative. Use a screwdriver to press the   emergency button through the metal protection grille. See   Fig. 35.   4. Check electrical connections for tightness and con-   trols for proper operation each heating and cooling   season. Service as necessary.   II. SERVICE   A. To Clean or Replace Air Filters   Emergency Operation   1. Place a plastic sheet on the floor to catch any water   that may spill from drain pan.   When the unit is in the OFF mode and the Emergency but-   ton is pressed for 5 seconds, the unit will operate as follows:   2. Slide filter out.   • Automatic mode   • temperature preset to 72 F   • automatic fan speed   • louvers set automatically according to the operating mode   • Timer function is cancelled   • buzzer beeps   3. Vacuum clean or wash filter with soapy water. Rinse   and let air dry. If filter needs replacing, filters are   available from the local dealer.   CAUTION: If air filter is not replaced in the unit,   dust and dirt gather in air conditioner and operation   becomes impaired.   When the unit is ON and the Emergency button is pressed   for 5 seconds, the unit will operate as follows:   • the unit is turned off   • buzzer beeps   B. To Clean or Replace Drain Pan   1. Place a plastic sheet on the floor to catch any water   that may spill from drain pan.   When a signal is received by the remote control, the unit   operates accordingly.   —23—   Remote control   signal receiver   Red   LED   Emergency   Button   Green   LED   Yellow   LED   Fig. 35 — Warning Lamps and Emergency Button   Copyright 2006 Bryant Heating & Cooling Systems   Printed in U.S.A.   CATALOG NO. 02-619F0001-II   |