Models 566D, 566E, 569D,
569F, 576C
COMMERCIAL AIR-COOLED
CONDENSING UNITS WITH
524A AIR-HANDLING UNITS
with 524A
6 to 20 Tons
569D072-120
576C120
569F120
524A072-300
566D150-240
566E150-240
pressures. A low-pressure switch protects the system from
low-pressure conditions, including loss of charge.
FEATURES/BENEFITS
These dependable split systems match Bryant’s indoor-air han-
dlers and direct-expansion coils with outdoor condensing units
for a wide selection of commercial cooling solutions.
The 569F120 and 566E150-240 units feature 2 scroll compres-
sors and 2 refrigerant circuits that provide continuous air
conditioning and design flexibility. These units also include
Cycle-LOC™ anti-short-cycling protection which helps to
protect the units against compressor failure.
CONSTRUCTED FOR LONG LIFE — The 569D (single cir-
cuit, scroll compressor), 576C (single circuit semi-hermetic
compressor), 569F/566E (dual circuit, scroll compressor) and
566D (semi-hermetic compressor) models are designed and
built to last. The copper tube-aluminum fin outdoor coil
construction provides years of trouble-free operation. Where
conditions require them, E-coated coils and pre-coated fin coils
are also available. Cabinets are constructed of prepainted
galvanized steel, delivering unparalleled protection from the
environment. Inside and outside surfaces are protected to
ensure long life, good looks, and reliable operation. Safety con-
trols are used for enhanced system protection and reliability.
All units include a crankcase heater to eliminate liquid slugging
at start-up. Units with semi-hermetic compressors are also
equipped with an oil-level sight glass.
Latest safety standards are assured through UL and UL
Canada approvals.
INNOVATIVE BRYANT PACKAGED AIR HANDLERS ARE
CUSTOM MATCHED TO THE CONDENSING UNITS — The
524A Series has excellent fan performance, efficient direct-
expansion (DX) coils, a unique combination of indoor-air qual-
ity features, and easy installation. Its versatility and state-of-
the-art features help to ensure that your split system provides
economical performance now and in the future.
EFFICIENT OPERATION — Building owners will appreciate
the high unit EERs (Energy Efficiency Ratios) offered by these
condensing units. These units provide greater efficiency than
similar units in the marketplace, which translates into year-
round operating savings.
Indoor-Air Quality (IAQ) Features — The unique combination
of IAQ features in the 524A Series air handlers help to ensure
that only clean, fresh, conditioned air is delivered to the occu-
pied space.
CONTROLS FOR PERFORMANCE DEPENDABILITY — The
condensing units offer the building owner operating controls
and components designed for performance dependability. The
highly efficient hermetic and semi-hermetic compressors are
engineered for long life and durability. The compressors
include overload protection and vibration isolation for enhance-
ment of quiet operation. The high-pressure switch protects the
entire refrigeration system from abnormally high operating
Direct-expansion (DX) cooling coils prevent the build-up of
humidity in the room, even during part-load conditions. Unit
sizes of 10 tons and above feature dual-circuit coils for
improved temperature control.
Standard 2-in. disposable filters remove dust and airborne par-
ticles from the occupied space for cleaner air.
Form No. PDS 569D.72.2
ARI* CAPACITY RATINGS
SYSTEM†
Net Cap.
CONDENSING UNIT ONLY**
AIR
HANDLER/
INDOOR COIL
CONDENSING
UNIT
Gross Cap.
EER
IPLV
EER
IPLV
(Btuh)
(Btuh)
524A-B072††
524A-C072††
524A-B090
69,000
72,000
71,000
74,000
11.0
11.2
10.8
11.0
N/A
N/A
N/A
N/A
569D072
569D090
569D120
576C120
569F120
566D150
72,000
12.4
N/A
524A-C090††
524A-B072
87,000
91,000
90,000
94,000
10.6
11.3
10.6
11.2
N/A
N/A
N/A
N/A
524A-C072††
524A-B090
100,000
133,000
124,000
123,000
150,000
12.7
12.4
12.0
12.3
12.1
N/A
N/A
524A-C090††
524A-B120
524A-C120
524A-B150
524A-C150
118,000
125,000
123,000
130,000
10.3
10.4
10.4
10.4
N/A
N/A
N/A
N/A
524A-B120
524A-C120
524A-B150
524A-C150
114,000
119,000
118,000
125,000
10.3
10.3
10.4
10.3
13.1
13.6
14.1
14.5
16.5
16.0
15.8
524A-B120
524A-C120
524A-B150
524A-C150
113,000
118,000
118,000
124,000
10.3
10.5
10.5
10.9
11.7
12.4
12.8
13.2
524A-B150
524A-C150
524A-B180
524A-C180
138,000
144,000
144,000
146,000
10.4
10.6
10.6
10.8
12.7
13.0
11.6
13.1
524A-B120
524A-C120
524A-B150
524A-C150
524A-B180
524A-C180
135,000
143,000
145,000
153,000
152,000
161,000
9.7
10.2
10.5
11.1
10.8
11.3
9.9
10.3
10.9
11.5
11.0
11.5
566E150
566D180
566E180
158,000
198,000
204,000
12.5
11
15.1
14.9
13.9
524A-B180
524A-C180
524A-B240
524A-C240
176,000
182,000
184,000
196,000
9.8
9.7
12.3
12.1
12.2
12.5
9.8
10.0
524A-B150
524A-C150
524A-B180
524A-C180
524A-B240
524A-C240
176,000
185,000
187,000
198,000
194,000
204,000
10.0
10.3
10.2
10.6
10.1
10.4
10.4
10.8
10.5
10.9
10.2
10.4
11.9
566D240
566E240
524A-C300
244,000
9.5
11.8
248,000
259,000
10.5
11.2
13.9
13.1
524A-C240
524A-B300
524A-C300
243,000
242,000
252,000
9.6
9.6
9.7
9.8
9.9
9.9
LEGEND
EER — Energy Efficiency Ratio
IPLV — Integrated Part Load Value
N/A
—
Not Applicable
SST — Saturated Suction Temperature
*Air Conditioning and Refrigeration Institute.
†Ratings in accordance with latest ARI Standard revisions.
**Condensing unit only ratings are at 45 F SST and 95 F entering-air temperature.
††ENERGY STAR® compliant combination of condensing unit and air handler/
indoor coil.
SOUND LEVELS, dB — 569D/576C/566D,E
OCTAVE BANDS
250 500 1000 2000 4000 8000
SOUND RATING
(60 Hz) dB (A)
UNIT
63
125
072
569D 090
120
80.0
84.0
85.0
43.8 61.4 66.2 70.8 73.8
58.5 67.3 71.3 75.4 77.2
63.7 67.6 72.5 77.0 80.4
75.2
75.8
77.5
73.0
76.5
74.7
62.7
71.3
65.9
576C 120
150
83.0
52.5 66.1 75.1 75.4 78.3
73.5
71.0
64.2
86.2
86.2
90.0
—
—
93.0 86.0 83.0 80.0
93.0 86.0 83.0 80.0
78.0
78.0
82.5
73.0
73.0
76.5
71.0
71.0
61.5
566D
180
240
83.5 81.5 88.5 86.5 85.5
150
566E 180
240
86.9
87.5
88.0
—
—
—
90.9 86.1 83.1 84.0
90.9 86.1 83.4 84.5
90.9 86.1 83.8 84.5
73.5
76.6
79.2
71.7
73.2
74.3
66.7
63.5
65.5
ESTIMATED SOUND POWER LEVELS (Lw) — 524A072-300
OCTAVE BAND CENTER FREQUENCY
UNIT
CFM
dB(A)
63
125
89.2
91.3
94.6
93.3
94.9
98.6
98.5
250
85.2
87.3
90.6
89.3
90.9
94.6
94.5
500
84.2
86.3
89.6
90.3
91.9
95.6
95.5
1000
80.2
82.3
85.6
84.3
85.9
89.6
89.5
2000
78.2
80.3
83.6
82.3
83.9
87.6
87.5
4000
74.2
76.3
79.6
78.3
79.9
83.6
83.5
524A072
524A090
524A120
524A150
524A180
524A240
524A300
2,400
3,000
4,000
5,000
6,000
8,000
10,000
86.3
88.3
91.6
91.1
92.7
96.4
96.2
93.2
95.3
98.6
97.3
98.9
102.6
102.5
NOTE: Since this data is calculated, these sound power levels may be different than the actual
sound power levels. The accoustic center of the unit is located at geometric center of the unit.
3
OPTIONS AND ACCESSORIES
566D, 566E, 569D, 569F, 576C FACTORY-INSTALLED
Non-Fused Disconnect Switch (566E, 569D, 569F, 576C
Only) to remove power locally at the condensing unit. This
switch also includes a power lockout capability to protect the
service person. This lockout switch saves the service person
time and effort because there is no need to access a distant dis-
connect switch while servicing the unit.
OPTIONS
Dura-Shield Condenser Coils offer several options to match
coil protection to site conditions for optimum durability. See
table below. Consult your Bryant representative for further
information.
FIELD-INSTALLED ACCESSORIES
E-Coated Aluminum-Fin Coils have a flexible and durable
epoxy coating uniformly applied to all coil surfaces. Unlike brittle
phenolic dip and bake coatings, E-coating provides superior
protection with unmatched flexibility, edge coverage, metal
adhesion, thermal performance, and most importantly, corro-
sion resistance.
Electric Unloader Package (576C120 Only) includes hard-
ware and solenoid valve to convert a pressure-operated
unloader to electric unloading.
–20 F Low-Ambient Temperature Accessory Kit (Motormas-
ter) controls outdoor-fan motor operation to maintain the correct
head pressure at low outdoor ambient temperatures.
E-coated coils provide this protection since all coil surfaces are
completely encapsulated from environmental contamination.
This coating is especially suitable in industrial environments.
Condenser Coil Grille Package protects condensing unit coil
from impact by large objects and vandalism.
Pre-Coated Fin Coils provide protection in mild coastal
environments.
Bryant’s Line of Thermostats provide both programmable and
non-programmable capability with the new Debonair® line of
commercial programmable thermostats. The Commercial
Electronic thermostats provide 7-day programmable capability
for economical applications.
–20 F Low-Ambient Temperature Kit Option (Motormaster®)
(566E, 569D, 569F, 576C Only) controls outdoor-fan motor
operation to maintain the correct head pressure at low outdoor
ambient temperatures.
Hail Guard Package protects against damage from flying
debris and hail.
115-v Convenience Outlet (566E, 569D, 569F, 576C Only) to
power up electric drills, lights, and refrigerant recovery
machines. This means you are no longer required to run a sep-
arate 115-v power supply.
Gage Panel Package provides a suction and discharge pres-
sure gage for the refrigerant circuit.
CONDENSER COIL OPTIONS
ENVIRONMENT
COPPER-TUBE COILS
WITH DURA-SHIELD
OPTION
Mild
Coastal
Industrial/
Coastal
Standard
Al Fins (Standard Coils)
Al Fins, E-Coated
X
X
Al Fins, Pre-Coated
X
LEGEND
Al — Aluminum
LOW AMBIENT CONTROL
(FACTORY-INSTALLED OR
FIELD-INSTALLED)
FACTORY-INSTALLED
DURA-SHIELD
COIL PROTECTION
FACTORY-INSTALLED
CONVENIENCE OUTLET
FACTORY-INSTALLED
DISCONNECT SWITCH
Options and Accessories
4
OPTIONS AND ACCESSORIES (cont)
Return-Air Grille provides a protective barrier over the return-
524A-B, C FACTORY-INSTALLED OPTIONS
air opening and gives a finished appearance to units installed in
the occupied space. Accessory is available unpainted or
painted.
Alternate Fan Motors and Drives are available to provide the
widest possible range of performance.
High-Capacity 4-Row Coils are available to provide increased
latent and sensible capacities (524A-C).
Subbase provides a stable, raised platform and room for con-
densate drain trap connection for vertical floor-mounted units.
Accessory is available unpainted or painted.
Prepainted Steel Units are available from the factory for appli-
cations that require painted units. Units are painted with Ameri-
can Sterling Gray color.
Overhead Suspension Package includes necessary brackets
to support units in horizontal ceiling installations.
FIELD-INSTALLED ACCESSORIES
Two-Row Hot Water Coils have copper tubes mechanically
bonded to aluminum plate fins and non-ferrous headers.
Bryant’s Line of Thermostats provide both programmable and
non-programmable capability. The Commercial Electronic
thermostats provide 7-day programmable capability for eco-
nomical applications.
One-Row Steam Coil has copper tubes and aluminum fins.
The Inner Distributing Tube (IDT) design provides uniform
temperatures across the coil face. The steam coil has a broad
operating pressure range; up to 20 psig (138 kPag) at 260 F
(127 C). The IDT steam coils are especially suited to applica-
tions where sub-freezing air enters the unit.
Condensate Drain Trap includes an overflow shutoff switch
that can be wired to turn off the unit if the trap becomes
plugged. Kit also includes a wire harness that can be connected
to an alarm if desired. The transparent trap is designed for easy
service and maintenance.
Electric Resistance Heat Coils have an open-wire design and
are mounted in a rigid frame. Safety cutouts for high tempera-
ture conditions are standard. Terminal block for single-point
power connection is included.
UV-C Germicidal Lamps kill mold and fungus, which may grow
on evaporator coil and condensate pan surfaces. The use of
UV-C germicidal lamps eliminates the foul odors that result from
this growth of mold and fungus. It also provides a self-cleaning
function for the evaporator coil and drain pan.
Economizer (Enthalpy Controlled) provides ventilation air
and “free” cooling if outside ambient temperature and humidity
are suitable.
Discharge Plenum directs the air discharge directly into the
occupied space integral horizontal and vertical louvers enable
redirection of airflow. Accessory is available unpainted or
painted. Field assembly required.
Commercial Programmable
and Non-Programmable Thermostat
5
OPTIONS AND ACCESSORIES (cont)
HOT WATER OR
STEAM COIL
DISCHARGE
PLENUM
RETURN-AIR
GRILLE
SUBBASE
FAN
COIL
UNIT
FAN COIL
UNIT
524A with Discharge Plenum,
Return Grille, and Subbase
524A with Hot Water or Steam Coil
ECONOMIZER
FAN COIL UNIT
524A with Economizer
524A with Condensate Trap
6
SELECTION PROCEDURE
To determine combination ratings for 569D/F, 576C and 566D/E
units matched with 524A Series air handlers, follow these steps:
III DETERMINE SIZES OF LIQUID AND SUCTION LINES.
Enter Refrigerant Piping Sizes table. The sizes shown are
based on an equivalent length of pipe. This equivalent
length is equal to the linear length of pipe indicated at the
top of each sizing column, plus a 50% allowance for fitting
losses. (For a more accurate determination of actual
equivalent length in place of using the estimated 50%
value, refer to a standard refrigeration piping practice.) For
this example, note in the linear length column that the
I DETERMINE COOLING LOAD, EVAPORATOR-AIR
TEMPERATURE, AND QUANTITY.
Given:
Total Cooling Capacity
Required (TC). . . . . . . . . . . . . . . . . . . . . . 127,000 Btuh
Sensible Heat Capacity
Required (SHC) . . . . . . . . . . . . . . . . . . . . . 95,000 Btuh
Compressor Type . . . . . . . . . . . . . . . . . . . . . . . . . . .Scroll
Temperature Air Entering Condenser (Edb). . . . . . . . 95 F
Temperature Air Entering
Evaporator (db/wb). . . . . . . . . . . . . . . .80 F db, 67 F wb
Evaporator Air Quantity . . . . . . . . . . . . . . . . . . . 4,000 cfm
External Static Pressure . . . . . . . . . . . . . . . . . . 0.4 in. wg
Length of Interconnecting
Refrigerant Piping . . . . . . . . . . . . . . . . . . . 25 ft (Linear)
Power Supply (V-Ph-Hz) . . . . . . . . . . . . . . . 208/230-3-60
1
proper pipe size is /2 in. for the liquid line and 13/8 in. for
the suction line.
IV DETERMINE FAN RPM AND BHP (BRAKE
HORSEPOWER).
At the Air Handler Fan Performance table enter at 524A-
C120 with high capacity coil at 4000 cfm and move to the
External Static Pressure (ESP) column. Note that the con-
ditions require 803 rpm at 1.77 bhp.
V DETERMINE MOTOR AND DRIVE.
II SELECT
CONDENSING
UNIT
AIR-HANDLER
Enter the Fan Motor Data tables and find the standard
motor for 524A-C120 unit rated at 2.4 Hp. Since the bhp
required is 1.77, a standard motor satisfies the require-
ment and should be used.
COMBINATION.
For this example, select a 569D120 matched with a
524A-C120 with high-capacity 4-row coil This 569D120/
524A-C120 condensing unit air-handler combination
provides 130,000 Btuh of total cooling capacity and
98,200 Btuh of sensible capacity at the given conditions. If
other temperatures or airflow values are required, interpo-
late the values from the combination ratings.
Next, find the type of drive that satisfies the 803 rpm
requirement in the Drive Data tables. For the 524A-C120
unit, the Standard Drive table on shows an rpm range of
666-863. Since the rpm required is 803, the standard drive
satisfies the requirement and should be used. Select the
standard motor and standard drive combination (option
code GC or ED).
7
CONTROLS
the cooling continues to decrease, stage one of the thermostat
OPERATING SEQUENCES
opens causing compressor no. 1 and outdoor-fan motor no. 1 to
shut down. The LLS valve for each compressor will close when
the associated compressor stops, minimizing the potential for
refrigerant migration during the off cycle.
569D072-120, 576C120 — At start-up, the thermostat calls for
cooling. With all safety devices satisfied, the compressor
contactor and fan contactor energize, causing the compressor
and outdoor-fan motor to operate. Thermostat contacts
energize, allowing the field-supplied and field-installed indoor-
fan contactor to function. A field-supplied and field-installed liq-
uid line valve also opens, allowing the system to function in
Cooling mode. As cooling demand is satisfied, the thermostat
contacts break, deenergizing the contactor and causing the
system to shut off. The liquid line solenoid valve closes, mini-
mizing the potential for refrigerant migration. The compressor
does not restart until the thermostat again calls for cooling. The
system is protected with a safety circuit so that the system will
not start if a fault exists (i.e., high or low pressure fault). To reset
the safety circuit, set the thermostat to eliminate the cooling
demand, then return to original set point. This should be done
only once, and if system shuts down due to the same fault,
determine the problem before attempting to restart the system.
The indoor-fan motor will stop if the thermostat is set to AUTO
and will continue to operate if the thermostat is set to CONT.
Each compressor is protected with a Cycle-LOCTM device so
that the compressor will not operate if there is a high-pressure
fault, low pressure fault, or a compressor is off due to internal
line break overcurrent/overtemperature protection. To reset the
Cycle-LOC device, set the thermostat higher to remove the
cooling demand, then return to the original set point. This
should be done only once. If the system shuts down with the
same fault, the cause for the fault should be determined and
corrected before the a Cycle-LOC device is reset again.
566E150-240 — At start-up, when the thermostat calls for first
stage cooling and all safety devices are satisfied, the compres-
sor contactor (C1) energizes causing compressor no. 1 and fan
motor no. 1 to start. Fan motor no. 2 will start when the fan
cycling pressure switch (FCPS) closes as discharge pressure
builds (refer to physical data table for FCPS specifications).
With the indoor-fan contactor wired to TB2-4 and TB2-9
contacts on the terminal block, the indoor fan will also start with
the compressor. The liquid line solenoid (LLS) valve will open
when compressor no. 1 starts, allowing refrigerant to flow in the
system.
566D150-240 — When the first stage of cooling thermostat
closes, the timer starts. After approximately 3 seconds, the
timer activates the compressor and fan motor no. 1 contactors.
When the liquid pressure builds to approximately 257 psig, fan
motor no. 2 is energized.
When there is demand for additional cooling capacity, the
second stage of the cooling thermostat closes, energizing a
field-supplied liquid line solenoid (LLS) valve, which opens. This
increases the suction pressure, causing the compressor to
operate at higher capacity (compressor loads).
When the thermostat calls for stage two cooling, compressor
contactor no. 2 (C2) energizes causing compressor no. 2 to
start. As the cooling demand decreases, stage two on the
thermostat opens, causing compressor no. 2 to shut down. As
the cooling continues to decrease, stage one of the thermostat
opens causing compressor no. 1 and outdoor-fan motor to shut
down. The LLS valve for each compressor will close when the
associated compressor stops, minimizing the potential for
refrigerant migration during the off cycle.
When the fan switch is set at AUTO, the indoor-air fan cycles
with the compressor. When the switch is set at CONT, the
indoor-air fan runs continuously.
At shutdown, the Time Guard II timer prevents the compressor
from restarting for approximately 5 minutes.
In addition, an LLS valve wired in parallel with the compressor
contactor coil shuts off the liquid line to prevent refrigerant
migration back to the compressor during the off cycle.
The indoor-fan motor will stop if the thermostat is set to AUTO
and will continue to operate if the thermostat is set on CONT.
Each compressor is controlled by the thermostat so they will not
start until there is a demand from the thermostat. Each
compressor is protected with a Cycle-LOC device so that the
compressor will not operate if there is a high-pressure fault,
low-pressure fault, or compressor is off due to internal line
break overcurrent/overtemperature protection. To reset the a
Cycle-LOC device, set the thermostat higher to remove the
cooling demand, then return to the original set point. This
should be done only once. If the system shuts down with the
same fault, the cause for the fault should be determined and
corrected before the a Cycle-LOC device is reset again.
569F120 — When the thermostat calls for stage one cooling at
start-up, and all safety devices are satisfied, the compressor
contactor no. 1 (C1) energizes causing compressor no. 1 and
outdoor-fan motor no. 1 to start (the indoor-fan contactor should
be wired to start at the same time as the compressor). The
liquid line solenoid (LLS) valve will open when compressor no. 1
starts, allowing refrigerant to flow in the system.
When the thermostat calls for stage two cooling, compressor
contactor no. 2 (C2) energizes causing compressor no. 2 and
outdoor-fan motor no. 2 to start. As the cooling demand
decreases, stage two on the thermostat opens, causing
compressor no. 2 and outdoor-fan motor no. 2 to shut down. As
8
TYPICAL WIRING SCHEMATICS
NOTES:
1. If any of the original wire furnished must be
replaced, it must be replaced with type 90° C
wire or its equivalent.
2. Thermostat: HH07AT170, 172, 174
2783
&
P272-
Subbase: HH93AZ176, 178 & P272-1882, 1883
or HH93AZ177 & 179.
3. Sealed VA for IFC and LLSV is not to exceed
22.
4. Use copper conductors only.
5. TRAN is wired for 230 v unit. If unit is to be run
with 200 v power supply, disconnect BLK wire
from 230 v tap and connect to 200 v tap.
6. If TRAN is wired for 460-3-60 v and unit is to be
run with 400-3-50 v power supply, disconnect
BLK wire from 460 v tap and connect to 400 v
tap.
7. Three-phase motors are protected under pri-
mary single phasing conditions.
CB
MUST
TRIP
AMPS
VOLTAGE
RATING
Mfg. Part No.
Potter & Brumfield
W28X-1024-3.2
24 V
3.2
LEGEND
AHA
C
—
—
—
—
—
—
—
—
—
—
—
—
—
Adjustable Heat Anticipator
Contactor, Compressor
Capacitor
LLSV
LPS
NEC
OFM
QT
—
—
—
—
—
—
—
—
—
Liquid Line Solenoid Valve
Low-Pressure Switch
National Electrical Code
Outdoor-Fan Motor
Quadruple Terminal
Terminal Block
Thermostat-Cooling
Thermostat-Heating
Transformer
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
CAP
CB
Circuit Breaker
CC
CH
Cooling Compensator
Crankcase Heater
Compressor Lockout
Compressor Motor
Discharge Gas Thermostat
Equipment
Ground
High-Pressure Switch
Indoor-Fan Contactor
Splice
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
TB
CLO
COMP
DGT
EQUIP
GND
HPS
IFC
TC
TH
— —
TRAN
Field Splice
Marked Wire
To Indicate Common Potential
Only, Not Represent Wiring
569D090, 208/230-3-360 and 460-3-60 Units
9
TYPICAL WIRING SCHEMATICS (cont)
LEGEND
AHA
C
—
—
Adjustable Heat
Anticipator
Contactor,
Compressor
Capacitor
CAP
CB
—
—
—
—
—
—
Circuit Breaker
Cooling Compensator
Crankcase Heater
Compressor Motor
Compressor Over
Temperature Protection
Equipment
CC
CH
COMP
COTP
EQUIP
GND
HPS
IFC
LLSV
—
—
—
—
—
Ground
High-Pressure Switch
Indoor-Fan Contactor
Liquid Line Solenoid
Valve
LPS
NEC
OFM
OL
—
—
—
—
—
—
—
—
—
Low-Pressure Switch
National Electrical Code
Outdoor-Fan Motor
Overload Relay
Relay
Terminal Block
Thermostat-Cooling
Thermostat-Heating
Transformer
R
TB
TC
TH
TRAN
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Factory Wiring
Field Control Wiring
Field Power Wiring
— —
Accessory or
Optional Wiring
To Indicates Common
Potential Only, Not
Represent Wiring
576C120, 208/230-3-60 and 460-3-60 Units
10
MODEL NUMBER NOMENCLATURE
569D 072 000 – –
P
X
569D — Commercial Air-Cooled Condensing
Unit With Scroll Compressor
Factory-Installed Options*
569F — Dual Circuit Commercial Air-Cooled
Condensing Unit With Scroll Compressor
Voltage Designation
E — 460-3-60
P — 208/230-3-60
T
— 575-3-60
Heating
X — None
Nominal Tons Cooling
072 — 6 (569D Only)
090 — 7-1/2 (569D Only)
120 — 10 (569D, 569F)
Heating Capacity
000 — No Heat
576C
P
X
120 000 – –
576C — Commercial Air-Cooled Condensing
Factory-Installed Options*
Unit With Semi-Hermetic Compressor
Heating Capacity
000 — No Heat
Voltage Designation
E — 460-3-60
P — 208/230-3-60
T — 575-3-60
Nominal Tons Cooling
120 — 10
Heating
X — None
*Contact your local representative for more details.
Quality Assurance
Certified to ISO 9001:2000
11
PHYSICAL DATA
569D072-120, 576C120, 569F120 UNITS
UNIT
569D072
569D090
71/2
569D120
576C120
569F120
NOMINAL CAPACITY (tons)
6
10
10
10
OPERATING WEIGHT (lb)
Aluminum Coils (Standard)
Copper Coils (Optional)
300
352
383
484
430
531
575
676
488
589
R-22
22
2.0
RREFRIGERANT TYPE*
Operating Charge, Typical (lb)†
Shipping Charge (lb)
12
2.0
20
2.0
24
2.0
11/Circuit
2.0
COMPRESSOR
Type
Qty...Model
Oil Charge (oz)
No. Cylinders
Speed (rpm)
Scroll
1...SR_94
90
Reciprocating
Scroll
2...SR_60
72 (ea)
N/A
1...SR_68
88
1...ZR125
110
1...06DH824
128
6
1750
N/A
3500
3500
CONDENSER FAN
Qty...Rpm
2...850
2...1100
2...1100
2...1100
2...1100
1
/
1
/
1
/
1
/
1
/
Motor HP (rpm)
Diameter
8
22
5400
340
4
4
4
22
6500
570
4
22
6500
570
22
6500
570
Nominal Airflow (Cfm Total)
Watts (Total)
CONDENSER COIL (Qty)
Face Area (sq ft total)
Rows...Fins/in.
2
2
29.2
2...17
17.1 (ea)
29.2
2...17
34.2
29.2
2...17
34.2
1...17
17.3
2...17
34.2
Storage Capacity (lb)**
CONTROLS
Pressurestat Settings (psig)
High Cutout
Cut-in
Low Cutout
Cut-in
428 10
320 20
428 10
320 20
428 10
320 20
27
44
3
5
27
44
3
5
27
44
3
5
DISCHARGE GAS THERMOSTAT (°F)
Cutout
Cut-in
2
2
—
—
—
—
270
9
—
—
—
—
190 13
PRESSURE RELIEF
Location
Temperature (F)
Suction Line
200
PIPING CONNECTIONS (in. ODM)
Qty...Suction
Qty...Liquid
1...11/8
1...3/8
1...11/8
1...3/8
1...13/8
1...1/2
1...13/8
1...1/2
2...11/8
2...3/8
*Unit is factory-supplied with holding charge only.
NOTE: Unit 576C120 has one step of unloading. Full load is at 100% of
capacity, and one step of unloading is 67% capacity. Unit 576C120 has
the following unloader settings: load is 70 1 psig and unload is 60
2 psig.
†Typical operating charge with 25 ft of interconnecting piping.
**Storage capacity of condenser coil with coil 80% full of liquid R-22 at
95 F.
12
DIMENSIONS
ALUMINUM COIL
Standard Unit Weight Corner W Corner X Corner Y Corner Z
ELECTRICAL
UNIT
CHARACTERISTICS
UNIT
Center of Gravity
lb kg X mm [in.] Y mm [in.]
569D072
569D090
569D120
576C120
208/230-3-60, 460-3-60, 575-3-60
208/230-3-60, 460-3-60, 575-3-60
208/230-3-60, 460-3-60, 575-3-60
208/230-3-60, 460-3-60, 575-3-60
lb
kg
lb
kg
lb kg lb kg
569D072
569D090
569D120
576C120
300
383
430
575
136
174
195
261
62 28 103 47 62 28
86 39 123 56 85 39
72 33 831.9 [32.75] 641.4 [25.25]
89 40 822.3 [32.38] 635.0 [25.00]
84 38 166 75 66 30 114 52 812.8 [32.00] 676.3 [26.63]
55 25 265 120 88 40 167 76 927.1 [36.50] 647.7 [25.50]
SERVICE VALVE CONNECTIONS
Suction
Liquid
Unit
mm [in.]
mm [in.]
9.5 [3/8]
569D072
569D090
569D120
576C120
28.6 [11/8]
28.6 [11/8]
34.9 [13/8]
34.9 [13/8]
9.5 [3/8]
12.7 [1/2]
12.7 [1/2]
569D072-120, 576C120
13
DIMENSIONS (cont)
OUTDOOR COIL
CORNER “A”
CORNER “B”
1162.7
[45.78]
Y
OUTDOOR COIL
CORNER “C”
X
CORNER “D”
ACCESS PANEL
ELECTRICAL DISCONNECT
LOCATION
TOP VIEW
O 34.5 [1.36]
LIQUID
POWER ENTRY
CONNECTION
(SEE CHART
FOR SIZE)
WITH 50.0/58.0/65.0 K.O.
CONTROL BOX
ACCESS PANEL
CONVENIENCE
OUTLET LOCATION
OUTDOOR
COIL
SUCTION
CONNECTION
(SEE CHART
FOR SIZE)
OUTDOOR
COIL
OUTDOOR
COIL
ACCESS
PANEL
872.8
[34.36]
582.5
[22.93]
BOTTOM
OF UNIT
341.5
287.8
226.9
[13.45]
167.5
[6.59]
172.9
[6.81]
[11.33]
[8.93]
637.9
LIQUID CONNECTION
(SEE CHART FOR SIZE)
111.7
116.7
[4.59]
[25.11]
644.6
[25.38]
RIGHT SIDE VIEW
FORK TRUCK SLOTS
(3 SIDES ONLY)
[4.40]
O 22.0 [0.87] FIELD
ENTRY SERVICE PORT
1509.3
[59.42]
FRONT VIEW
LEFT SIDE VIEW
OUTDOOR
COIL
COMPRESSOR
ACCESS PANEL
(in.)
(in.)
569F120
REAR VIEW
ALUMINUM COIL
Std. Unit
Wt.
Corner
A
Corner
B
Corner
C
Corner
Center of
Gravity
ELECTRICAL
CHARACTERISTICS
UNIT
D
X
Y
lb
kg
lb kg lb kg lb kg lb kg
mm [in.]
mm [in.]
208/230-3-60,
400/460-3-50/60,
575-3-60
873.8
[34.4]
591.8
[23.3]
569F120
488 221 102 46 143 65 139 63 104 47
569F120
14
PERFORMANCE DATA
CONDENSING UNIT RATINGS
569D072
SST (F)
576C120
Air Temperature Entering Condenser (F)
Air Temperature Entering Condenser (F)
SST (F)
80
85
95
100
105
115
80
85
95
100
105
115
TC
53.6
4.24
101.0
59.1
4.33
102.0
64.9
4.42
104.0
71.0
4.53
106.0
77.4
4.65
107.0
84.2
4.78
109.0
52.3
4.49
106.0
49.4
5.02
115.0
48.0
5.31
120.0
46.5
5.60
125.0
43.6
6.24
135.0
48.3
6.33
136.0
53.4
6.43
138.0
58.7
6.55
139.0
64.3
6.68
141.0
70.2
6.81
142.0
TC
89.0
7.52
103.0
85.1
7.79
108.0
77.4
8.29
118.0
73.6
8.49
123.0
69.7
8.70
128.0
62.2
9.02
138.0
25
30
kW
SDT
25
30
35
40
45
50
kW
SDT
TC
kW
SDT
57.6
4.57
107.0
54.6
5.10
117.0
53.0
5.39
122.0
51.5
5.69
126.0
TC
kW
SDT
101.0
7.76
104.0
96.6
8.07
108.0
88.5
8.64
118.0
84.4
8.89
123.0
80.3
9.14
128.0
72.2
9.55
138.0
TC
kW
SDT
63.3
4.67
109.0
60.1
5.20
118.0
58.4
5.49
123.0
56.7
5.79
128.0
TC
kW
SDT
113.0
8.01
105.0
109.0
8.36
109.0
100.0
8.99
119.0
95.8
9.28
124.0
91.5
9.55
128.0
83.0
10.05
138.0
35
TC
kW
SDT
69.3
4.77
110.0
65.8
5.31
120.0
64.1
5.60
125.0
62.3
5.90
129.0
40
TC
kW
SDT
125.0
8.29
106.0
121.0
8.66
111.0
112.0
9.35
120.0
107.0
9.65
125.0
103.0
9.95
129.0
94.1
10.55
139.0
TC
kW
SDT
75.6
4.89
112.0
71.9
5.43
122.0
70.1
5.72
126.0
68.2
6.02
131.0
45
TC
kW
SDT
138.0
8.57
108.0
133.0
8.97
113.0
124.0
9.75
122.0
119.0
10.05
127.0
115.0
10.50
131.0
106.0
11.05
140.0
TC
kW
SDT
82.3
5.03
114.0
78.4
5.56
123.0
76.4
5.86
128.0
74.3
6.16
133.0
50
TC
kW
SDT
152.0
8.85
111.0
147.0
9.28
115.0
137.0
10.15
124.0
132.0
10.45
129.0
127.0
10.90
133.0
117.0
11.55
142.0
569D090
Air Temperature Entering Condenser (F)
SST (F)
569F120
80
85
95
100
105
115
TC
73.9
5.81
98.6
82.0
5.88
99.6
90.4
5.98
101.0
99.2
6.09
103.0
109.0
6.22
104.0
71.7
6.14
67.0
6.84
64.6
7.21
62.1
7.58
57.0
8.36
Air Temperature Entering Condenser (F)
SST (F)
25
30
kW
SDT
80
85
95
100
105
115
104.0
114.0
118.0
123.0
133.0
TC
90.5
7.75
100.0
87.9
8.17
105.0
82.6
9.05
115.0
79.8
9.52
120.0
76.9
10.00
125.0
71.1
11.00
135.0
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
79.7
6.21
104.0
88.0
6.31
106.0
96.7
6.43
107.0
106.0
6.56
109.0
74.9
6.90
114.0
83.0
7.02
115.0
91.4
7.14
117.0
100.0
7.28
119.0
72.4
7.28
119.0
80.4
7.40
120.0
88.7
7.53
122.0
97.4
7.68
123.0
69.9
7.65
124.0
77.8
7.78
125.0
85.9
7.92
126.0
94.5
8.07
128.0
64.7
8.46
134.0
72.4
8.59
135.0
80.3
8.74
136.0
88.6
8.91
138.0
25
30
35
40
45
50
kW
SDT
TC
kW
SDT
100.0
7.79
101.0
97.8
8.21
106.0
92.2
9.09
116.0
89.3
9.57
120.0
86.3
10.10
125.0
80.2
11.10
135.0
35
TC
kW
SDT
111.0
7.89
102.0
108.0
8.30
107.0
102.0
9.18
116.0
99.0
9.66
121.0
96.0
10.10
126.0
89.7
11.20
136.0
40
TC
kW
SDT
122.0
8.01
104.0
119.0
8.42
108.0
112.0
9.31
118.0
109.0
9.79
123.0
106.0
10.30
127.0
99.4
11.30
137.0
45
TC
kW
SDT
118.0
6.36
106.0
116.0
6.70
111.0
110.0
7.43
120.0
107.0
7.83
125.0
104.0
8.23
130.0
97.2
9.09
139.0
TC
kW
SDT
133.0
8.15
105.0
130.0
8.57
110.0
123.0
9.46
120.0
120.0
9.95
124.0
116.0
10.40
129.0
109.0
11.50
138.0
50
TC
kW
SDT
145.0
8.30
107.0
141.0
8.72
112.0
134.0
9.63
121.0
131.0
10.10
126.0
127.0
10.60
131.0
120.0
11.70
140.0
569D120
Air Temperature Entering Condenser (F)
SST (F)
80
85
95
100
105
115
LEGEND
TC
102.0
8.04
99.3
8.38
93.8
9.13
90.9
9.55
88.1
9.95
81.9
10.85
136.0
kW
—
—
—
—
Compressor Power
25
30
35
40
45
50
kW
SDT
SDT
SST
TC
Saturated Discharge Temperature at Compressor (F)
Saturated Suction Temperature (F)
101.0
106.0
116.0
121.0
126.0
Gross Cooling Capacity (1000 Btuh)
TC
kW
SDT
112.0
8.26
103.0
109.0
8.60
107.0
103.0
9.31
117.0
99.8
9.65
12.02
96.7
10.05
127.0
90.3
10.95
136.0
TC
kW
SDT
122.0
8.52
104.0
119.0
8.85
109.0
113.0
9.55
118.0
109.0
9.95
123.0
106.0
10.35
128.0
99.0
11.15
137.0
TC
kW
SDT
133.0
8.81
106.0
130.0
9.15
110.0
123.0
9.85
120.0
119.0
10.25
125.0
115.0
10.55
129.0
108.0
11.35
139.0
TC
kW
SDT
144.0
9.12
108.0
141.0
9.45
112.0
133.0
10.15
122.0
130.0
10.55
126.0
126.0
10.85
131.0
118.0
11.65
140.0
TC
kW
SDT
156.0
9.45
109.0
152.0
9.85
114.0
145.0
10.55
123.0
141.0
10.85
128.0
137.0
11.25
133.0
128.0
12.05
142.0
15
PERFORMANCE DATA (cont)
COMBINATION RATINGS*
UNIT 569D072
569D072/524A-C072 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air — Cfm
2400
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
1800
3000
57
62
67
72
57
62
67
72
57
62
67
72
TC
66.0
66.0
4.45
65.1
65.1
4.72
68.6
60.9
4.49
67.5
60.3
4.76
74.3
51.0
4.60
73.1
50.5
4.87
80.7
40.8
4.71
79.3
40.3
4.99
72.0
72.0
4.55
71.0
71.0
4.83
72.6
70.5
4.57
71.4
69.8
4.84
77.7
58.6
4.66
76.3
58.1
4.93
84.1
45.5
4.78
82.6
45.0
5.05
76.2
76.2
4.63
75.0
75.0
4.91
76.2
76.2
4.63
75.1
75.1
4.90
79.9
65.7
4.70
78.5
65.2
4.97
86.2
50.0
4.82
84.6
49.5
5.09
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
63.3
63.3
5.26
65.2
59.2
5.30
70.6
49.4
5.41
76.7
39.3
5.53
68.9
68.9
5.37
69.1
68.3
5.38
73.6
57.0
5.47
79.7
44.0
5.60
72.8
72.8
5.45
72.8
72.8
5.45
75.7
64.0
5.51
81.6
48.5
5.64
95
TC
62.3
62.3
5.57
61.3
61.3
5.88
59.3
59.3
6.51
64.0
58.6
5.61
62.8
58.0
5.91
60.5
56.8
6.53
69.2
48.9
5.71
67.9
48.3
6.02
65.2
47.2
6.63
75.2
38.8
5.84
73.8
38.2
6.15
70.9
37.2
6.77
67.7
67.7
5.68
66.6
66.6
5.99
64.4
64.4
6.61
67.9
67.4
5.68
66.7
66.6
5.99
64.3
64.3
6.61
72.2
56.5
5.78
70.7
55.9
6.08
67.8
54.8
6.70
78.2
43.5
5.90
76.6
42.9
6.21
73.5
41.9
6.83
71.5
71.5
5.76
70.3
70.3
6.07
67.9
67.9
6.69
71.5
71.5
5.76
70.3
70.3
6.08
67.9
67.9
6.70
74.2
63.4
5.82
72.7
62.8
6.12
69.7
61.6
6.74
80.0
47.9
5.95
78.4
47.4
6.26
75.2
46.4
6.88
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
569D072/524A-B072 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
2400
Evaporator Air — Ewb (F)
1800
3000
Air Entering
Condenser
(Edb)
57
62
67
72
57
62
67
72
57
62
67
72
TC
63.4
63.4
4.40
62.5
62.5
4.67
66.1
58.4
4.45
65.1
57.9
4.72
71.7
49.0
4.55
70.5
48.5
4.82
77.8
39.2
4.66
76.6
38.8
4.93
69.0
69.0
4.50
68.0
68.0
4.77
69.8
67.2
4.52
68.7
66.6
4.79
74.9
56.0
4.60
73.6
55.5
4.88
81.1
43.6
4.72
79.7
43.1
4.99
72.9
72.9
4.57
71.9
71.9
4.84
72.9
72.9
4.57
71.9
71.9
4.84
76.9
62.5
4.64
75.6
62.0
4.91
83.1
47.6
4.76
81.7
47.2
5.03
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
60.8
60.8
5.22
62.9
56.8
5.26
68.2
47.5
5.36
74.1
37.9
5.48
66.1
66.1
5.32
66.5
65.2
5.33
71.1
54.6
5.42
77.0
42.2
5.54
69.7
69.7
5.39
69.8
69.8
5.39
73.1
60.9
5.46
78.9
46.2
5.58
95
TC
59.9
59.9
5.53
59.0
59.0
5.84
57.1
57.1
6.46
61.8
56.3
5.56
60.7
55.7
5.87
58.4
54.6
6.48
67.0
47.0
5.67
65.7
46.5
5.98
63.3
45.5
6.59
72.8
37.4
5.79
71.4
36.9
6.10
68.7
35.9
6.72
65.1
65.1
5.63
64.0
64.0
5.94
61.9
61.9
6.57
65.4
64.4
5.63
64.2
63.7
5.94
61.9
61.9
6.56
69.8
54.0
5.73
68.5
53.5
6.03
65.8
52.4
6.65
75.6
41.7
5.85
74.1
41.2
6.16
71.3
40.2
6.78
68.6
68.6
5.70
67.5
67.5
6.01
65.2
65.2
6.64
68.6
68.6
5.70
67.5
67.5
6.01
65.2
65.2
6.63
71.7
60.4
5.76
70.3
59.8
6.07
67.4
58.7
6.68
77.4
45.7
5.89
75.9
45.2
6.20
72.9
44.2
6.82
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
*Combinations on this page are ENERGY STAR® compliant.
16
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 569D072 (cont)
569D072/524A-C090 WITH HIGH-CAPACITY 4-ROW COIL*
Evaporator Air — Cfm
3000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
2400
3750
57
62
67
72
57
62
67
72
57
62
67
72
TC
71.9
71.9
4.55
70.9
70.9
4.83
72.9
69.5
4.57
71.7
68.8
4.84
78.3
57.7
4.67
76.9
57.2
4.94
84.8
45.1
4.79
83.3
44.6
5.07
77.7
77.7
4.66
76.5
76.5
4.93
77.7
77.7
4.66
76.5
76.5
4.93
81.3
67.0
4.73
79.8
66.4
5.00
87.6
50.9
4.85
86.1
50.3
5.12
81.6
81.6
4.73
80.3
80.3
5.01
81.6
81.6
4.73
80.3
80.3
5.01
83.4
75.2
4.77
81.9
74.6
5.04
89.4
56.4
4.89
87.8
55.9
5.16
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
68.8
68.8
5.37
69.3
67.5
5.38
74.2
56.1
5.48
80.4
43.5
5.61
74.1
74.1
5.48
74.1
74.1
5.48
76.9
65.2
5.54
82.9
49.3
5.66
77.7
77.7
5.55
77.8
77.8
5.56
79.0
73.3
5.58
84.5
54.8
5.70
95
TC
67.7
67.7
5.68
66.5
66.5
5.99
64.3
64.3
6.61
68.0
66.8
5.69
66.8
66.0
6.00
64.3
64.3
6.61
72.8
55.5
5.79
71.3
54.9
6.09
68.4
53.8
6.71
78.8
43.0
5.92
77.3
42.5
6.23
74.2
41.4
6.85
72.8
72.8
5.79
71.6
71.6
6.10
69.0
69.0
6.73
72.9
72.9
5.79
71.6
71.6
6.10
69.1
69.1
6.73
75.4
64.6
5.85
73.9
64.0
6.15
70.8
62.8
6.77
81.3
48.8
5.97
79.6
48.2
6.28
76.2
47.1
6.90
76.4
76.4
5.87
75.0
75.0
6.18
72.3
72.3
6.81
76.4
76.4
5.87
75.0
75.0
6.18
72.3
72.3
6.8
77.4
72.5
5.89
75.9
71.8
6.20
72.7
70.3
6.81
82.8
54.3
6.01
81.1
53.7
6.32
77.7
52.6
6.94
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
569D072/524A-B090 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
3000
Evaporator Air — Ewb (F)
2400
3750
Air Entering
Condenser
(Edb)
57
62
67
72
57
62
67
72
57
62
67
72
TC
68.4
68.4
4.49
67.4
67.4
4.76
69.5
65.8
4.51
68.4
65.2
4.78
74.8
54.8
4.61
73.6
54.3
4.88
81.0
42.9
4.72
79.7
42.4
5.00
73.6
73.6
4.58
72.6
72.6
4.86
73.6
73.6
4.58
72.6
72.6
4.86
77.6
63.1
4.65
76.3
62.6
4.93
83.8
48.1
4.77
82.4
47.6
5.05
77.3
77.3
4.65
76.1
76.1
4.92
77.3
77.3
4.65
76.1
76.1
4.92
79.5
70.4
4.69
78.2
69.8
4.96
85.5
52.9
4.81
84.0
52.4
5.08
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
65.5
65.5
5.31
66.2
64.0
5.32
71.1
53.3
5.42
77.1
41.5
5.54
70.4
70.4
5.40
70.5
70.5
5.40
73.7
61.5
5.47
79.5
46.6
5.59
73.8
73.8
5.47
73.8
73.8
5.47
75.5
68.7
5.51
81.1
51.4
5.62
95
TC
64.5
64.5
5.62
63.4
63.4
5.93
61.4
61.4
6.55
65.1
63.3
5.63
63.9
62.5
5.94
61.6
61.1
6.55
69.7
52.8
5.72
68.4
52.2
6.03
65.8
51.2
6.64
75.6
41.0
5.85
74.1
40.5
6.16
71.2
39.4
6.78
69.3
69.3
5.71
68.1
68.1
6.03
65.9
65.9
6.65
69.3
69.3
5.72
68.1
68.1
6.03
65.8
65.8
6.65
72.3
60.9
5.78
70.9
60.4
6.08
68.0
59.2
6.70
78.0
46.1
5.90
76.5
45.6
6.21
73.4
44.6
6.83
72.6
72.6
5.78
71.4
71.4
6.10
68.9
68.9
6.72
72.6
72.6
5.78
71.4
71.4
6.10
68.9
68.9
6.73
74.0
68.0
5.82
72.6
67.3
6.12
69.7
66.0
6.74
79.5
50.9
5.93
77.9
50.4
6.24
74.8
49.4
6.86
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
*This combination is ENERGY STAR® compliant.
17
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 569D090
569D090/524A-C072 WITH HIGH-CAPACITY 4-ROW COIL*
Evaporator Air — Cfm
2400
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
1800
3000
57
62
67
72
57
62
67
72
57
62
67
72
TC
78.9
77.9
5.75
77.6
77.0
6.10
85.1
69.0
5.78
83.6
68.3
6.13
92.8
59.0
5.85
91.3
58.3
6.20
101.0
48.7
5.94
99.3
48.0
6.30
87.0
87.0
5.79
85.7
85.7
6.14
90.7
79.9
5.83
89.2
79.1
6.18
98.3
66.9
5.91
96.6
66.3
6.26
106.0
53.6
6.01
105.0
52.9
6.37
93.0
93.0
5.85
91.6
91.6
6.20
94.7
89.3
5.87
93.1
88.4
6.22
102.0
74.2
5.96
100.0
73.5
6.31
110.0
58.0
6.06
108.0
57.4
6.41
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
75.1
75.1
6.80
80.8
66.8
6.82
88.3
56.9
6.90
96.1
46.7
7.00
83.2
83.2
6.85
86.1
77.6
6.87
93.3
64.9
6.96
101.0
51.6
7.08
88.9
88.9
6.91
89.9
86.7
6.92
96.5
72.2
7.01
104.0
56.1
7.12
95
TC
73.9
73.8
7.20
72.6
72.6
7.59
70.1
70.1
8.38
79.2
66.0
7.21
77.6
65.3
7.60
74.5
63.7
8.38
86.6
56.2
7.29
85.0
55.5
7.68
81.7
54.0
8.47
94.4
46.1
7.40
92.6
45.4
7.79
89.1
44.0
8.58
81.8
81.8
7.24
80.4
80.4
7.64
77.7
77.7
8.43
84.4
76.7
7.26
82.7
75.9
7.66
79.4
74.3
8.44
91.4
64.1
7.36
89.6
63.4
7.75
86.0
61.9
8.53
99.2
50.9
7.47
97.3
50.2
7.87
93.5
48.8
8.66
87.4
87.4
7.30
85.9
85.9
7.70
82.9
82.9
8.48
88.2
85.7
7.31
86.5
84.7
7.71
83.1
82.7
8.49
94.5
71.4
7.40
92.6
70.7
7.80
88.8
69.2
8.58
102.0
55.3
7.52
100.0
54.6
7.92
96.2
53.2
8.71
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
569D090/524A-B072 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
1800
2400
3000
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
75.3
74.3
5.77
74.2
73.4
6.12
81.2
65.8
5.82
79.8
65.2
6.18
88.5
56.3
5.91
87.1
55.6
6.27
96.1
46.4
6.00
94.6
45.8
6.37
82.5
82.5
5.84
81.3
81.3
6.20
86.4
75.7
5.88
84.9
75.0
6.24
93.6
63.5
5.97
92.0
62.8
6.33
101.0
50.9
6.07
99.5
50.2
6.44
88.0
88.0
5.90
86.7
86.7
6.26
89.9
84.1
5.93
88.4
83.3
6.28
96.8
70.0
6.01
95.2
69.4
6.38
104.0
54.9
6.12
103.0
54.3
6.48
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
71.8
71.6
6.83
77.2
63.8
6.89
84.2
54.3
6.98
91.6
44.6
7.10
79.0
79.0
6.91
82.0
73.6
6.95
88.8
61.5
7.05
96.2
49.0
7.17
84.1
84.1
6.99
85.4
81.7
7.00
91.9
68.1
7.10
99.2
53.0
7.22
95
TC
70.6
70.5
7.22
69.4
69.4
7.61
67.0
67.0
8.39
75.7
63.1
7.28
74.2
62.4
7.67
71.3
60.9
8.45
82.6
53.6
7.38
81.1
53.0
7.78
78.0
51.6
8.59
89.9
43.9
7.50
88.3
43.3
7.91
85.0
41.9
8.73
77.7
77.7
7.31
76.4
76.4
7.70
73.8
73.8
8.49
80.4
72.8
7.35
78.8
72.0
7.75
75.6
70.5
8.54
87.1
60.8
7.45
85.4
60.1
7.86
82.0
58.7
8.66
94.4
48.3
7.58
92.6
47.7
7.99
89.0
46.4
8.80
82.7
82.7
7.39
81.3
81.3
7.79
78.5
78.5
8.59
83.8
80.7
7.40
82.2
79.8
7.80
78.9
77.9
8.60
90.0
67.4
7.51
88.2
66.7
7.91
84.6
65.3
8.71
97.3
52.3
7.63
95.4
51.7
8.04
91.7
50.3
8.86
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
*This combination is ENERGY STAR® compliant.
18
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 569D090 (cont)
569D090/524A-C090 WITH HIGH-CAPACITY 4-ROW COIL*
Evaporator Air — Cfm
3000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
2205
3750
57
62
67
72
57
62
67
72
57
62
67
72
TC
86.0
86.0
5.78
84.8
84.8
6.14
90.4
78.0
5.83
88.9
77.3
6.18
98.0
65.6
5.91
96.4
64.9
6.26
106.0
52.8
6.01
104.0
52.2
6.37
94.1
94.1
5.86
92.7
92.7
6.22
95.7
90.3
5.88
94.1
89.4
6.23
103.0
75.0
5.97
101.0
74.2
6.32
111.0
58.5
6.07
109.0
57.8
6.42
96.9
96.9
5.90
95.4
95.4
6.25
97.8
94.8
5.91
96.2
93.7
6.26
104.0
79.3
5.98
102.0
78.5
6.34
112.0
61.1
6.09
110.0
60.5
6.44
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
82.3
82.3
6.85
85.8
75.8
6.88
93.1
63.5
6.96
101.0
50.9
7.07
90.0
90.0
6.92
90.9
87.7
6.93
97.3
72.8
7.02
105.0
56.5
7.13
92.6
92.6
6.96
93.1
91.4
6.96
98.7
77.1
7.04
106.0
59.2
7.15
95
TC
81.0
81.0
7.24
79.6
79.6
7.63
77.0
77.0
8.41
84.2
75.0
7.26
82.5
74.1
7.65
79.2
72.5
8.42
91.3
62.8
7.36
89.6
62.1
7.75
86.0
60.6
8.53
99.1
50.2
7.47
97.2
49.5
7.87
93.5
48.1
8.66
88.5
88.5
7.32
87.0
87.0
7.71
83.9
83.9
8.50
89.2
86.7
7.33
87.5
85.7
7.72
84.1
83.7
8.50
95.4
72.1
7.41
93.5
71.4
7.81
89.8
69.9
8.60
103.0
55.8
7.53
101.0
55.2
7.93
97.2
53.8
8.73
91.0
91.0
7.35
89.5
89.5
7.75
86.3
86.3
8.54
91.4
90.1
7.36
89.7
88.8
7.75
86.4
86.2
8.54
96.8
76.4
7.43
94.9
75.6
7.83
91.0
74.1
8.62
104.0
58.5
7.55
102.0
57.8
7.95
98.3
56.4
8.75
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
569D090/524A-B090 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
2205
3000
3750
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
81.7
81.7
5.83
80.6
80.6
6.19
85.9
74.2
5.88
84.5
73.5
6.23
93.2
62.4
5.97
91.6
61.7
6.33
101.0
50.2
6.07
99.2
49.6
6.43
89.0
89.0
5.92
87.7
87.7
6.28
90.8
85.2
5.94
89.3
84.5
6.30
97.5
70.9
6.02
95.8
70.2
6.39
105.0
55.4
6.12
103.0
54.8
6.49
91.6
91.6
5.95
90.2
90.2
6.31
92.6
89.4
5.96
91.1
88.4
6.32
98.8
74.7
6.04
97.1
74.1
6.40
106.0
57.7
6.14
105.0
57.1
6.51
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
78.3
78.3
6.90
81.7
72.1
6.95
88.5
60.4
7.05
95.9
48.4
7.17
85.2
85.2
7.00
86.3
82.9
7.02
92.5
69.0
7.11
99.9
53.6
7.23
87.6
87.6
7.04
88.2
86.4
7.05
93.8
72.8
7.13
101.0
55.9
7.25
95
TC
77.0
77.0
7.30
75.7
75.7
7.69
73.2
73.2
8.48
80.1
71.3
7.34
78.6
70.6
7.74
75.4
69.0
8.53
86.9
59.8
7.45
85.2
59.1
7.86
81.9
57.7
8.67
94.2
47.7
7.57
92.4
47.0
7.98
88.8
45.7
8.79
83.7
83.7
7.40
82.3
82.3
7.80
79.5
79.5
8.61
84.7
81.9
7.42
83.0
80.9
7.82
79.8
79.0
8.61
90.7
68.3
7.52
88.9
67.6
7.92
85.3
66.1
8.73
98.0
52.9
7.64
96.1
52.2
8.05
92.3
50.9
8.87
86.1
86.1
7.44
84.6
84.6
7.84
81.7
81.7
8.65
86.6
85.2
7.45
85.0
83.9
7.85
81.8
81.4
8.65
91.9
72.1
7.54
90.1
71.4
7.94
86.4
70.0
8.75
99.1
55.2
7.66
97.2
54.6
8.07
93.3
53.2
8.89
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
*This combination is ENERGY STAR® compliant.
19
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 569D120
569D120/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air — Cfm
4000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
3000
5000
57
62
67
72
57
62
67
72
57
62
67
72
TC
117.0
117.0
8.34
115.0
115.0
8.72
122.0
106.0
8.48
120.0
104.0
8.85
132.0
88.4
8.74
129.0
87.5
9.11
142.0
70.9
9.02
140.0
70.0
9.40
127.0
127.0
8.61
125.0
125.0
8.99
129.0
122.0
8.66
127.0
121.0
9.04
138.0
101.0
8.89
135.0
100.0
9.27
148.0
78.6
9.18
145.0
77.6
9.56
134.0
134.0
8.81
132.0
132.0
9.19
134.0
134.0
8.80
132.0
132.0
9.19
141.0
113.0
9.00
139.0
112.0
9.38
151.0
85.9
9.28
148.0
84.9
9.67
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
112.0
112.0
9.49
116.0
102.0
9.60
125.0
85.5
9.86
135.0
68.2
10.20
121.0
121.0
9.76
122.0
119.0
9.79
130.0
98.2
10.00
140.0
75.8
10.30
128.0
128.0
9.96
128.0
128.0
9.95
134.0
110.0
10.10
143.0
83.1
10.40
95
TC
110.0
110.0
9.90
108.0
108.0
10.30
104.0
104.0
11.10
113.0
101.0
10.00
111.0
100.0
10.40
106.0
97.7
11.20
122.0
84.4
132.0
67.1
119.0
119.0
10.20
117.0
117.0
10.60
112.0
112.0
11.40
120.0
117.0
10.20
117.0
116.0
10.60
112.0
112.0
11.40
127.0
97.1
137.0
74.8
125.0
125.0
10.40
123.0
123.0
10.80
118.0
118.0
11.60
125.0
125.0
10.40
123.0
123.0
10.80
118.0
118.0
11.60
131.0
109.0
10.50
128.0
108.0
10.90
122.0
105.0
11.70
140.0
82.1
100
105
115
SHC
kW
10.30
10.60
10.40
10.70
10.80
TC
SHC
kW
TC
SHC
kW
120.0
83.3
10.70
114.0
81.2
11.50
129.0
66.1
11.00
124.0
64.0
11.70
125.0
96.0
10.80
119.0
93.8
11.60
134.0
73.7
11.10
128.0
71.7
11.90
137.0
81.0
11.20
131.0
78.9
12.00
569D120/524A-B120 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
3000
4000
5000
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
110.0
110.0
8.19
108.0
108.0
8.57
115.0
99.4
8.32
113.0
98.4
8.70
124.0
83.3
8.55
122.0
82.4
8.93
134.0
66.8
8.82
132.0
66.0
9.20
119.0
119.0
8.41
117.0
117.0
8.80
121.0
114.0
8.48
119.0
113.0
8.85
130.0
94.6
8.70
128.0
93.7
9.08
139.0
73.6
8.96
137.0
72.8
9.35
126.0
126.0
8.59
124.0
124.0
8.97
126.0
125.0
8.60
124.0
123.0
8.98
133.0
105.0
8.80
131.0
104.0
9.17
143.0
79.9
9.06
140.0
79.0
9.44
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
105.0
105.0
9.34
110.0
96.6
9.45
118.0
80.7
9.69
127.0
64.3
9.96
114.0
114.0
9.57
115.0
111.0
9.61
123.0
91.9
9.83
132.0
71.1
10.10
120.0
120.0
9.73
120.0
120.0
9.74
126.0
102.0
9.93
135.0
77.3
10.20
95
TC
104.0
104.0
9.76
102.0
102.0
10.20
98.4
98.4
11.00
107.0
95.5
9.86
105.0
94.4
10.30
101.0
92.2
11.10
116.0
79.7
125.0
63.4
112.0
112.0
9.98
110.0
110.0
10.40
106.0
106.0
11.20
113.0
109.0
10.00
111.0
108.0
10.40
106.0
105.0
11.20
121.0
90.9
130.0
70.2
118.0
118.0
10.10
116.0
116.0
10.60
111.0
111.0
11.40
118.0
118.0
10.10
116.0
116.0
10.60
111.0
111.0
11.40
124.0
101.0
10.30
121.0
100.0
10.70
116.0
97.9
11.50
132.0
76.4
100
105
115
SHC
kW
10.10
10.40
10.20
10.50
10.60
TC
SHC
kW
TC
SHC
kW
114.0
78.7
10.5
109.0
76.7
11.30
122.0
62.4
10.80
117.0
60.5
11.60
118.0
89.9
10.60
113.0
87.8
11.40
127.0
69.2
10.90
122.0
67.3
11.70
130.0
75.5
11.00
124.0
73.6
11.80
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
20
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 569D120 (cont)
569D120/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
3750
6250
57
62
67
72
57
62
67
72
57
62
67
72
TC
126.0
126.0
8.60
124.0
124.0
8.98
129.0
119.0
8.68
127.0
118.0
9.05
138.0
98.7
8.94
136.0
97.7
9.31
149.0
77.4
9.23
146.0
76.5
9.61
136.0
136.0
8.87
134.0
134.0
9.25
136.0
135.0
8.87
134.0
133.0
9.25
143.0
114.0
9.08
141.0
113.0
9.46
153.0
86.5
9.37
151.0
85.6
9.76
142.0
142.0
9.06
140.0
140.0
9.44
142.0
142.0
9.05
140.0
140.0
9.44
147.0
127.0
9.18
144.0
126.0
9.56
156.0
95.0
9.46
154.0
94.1
9.84
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
120.0
120.0
9.74
122.0
116.0
9.80
131.0
95.7
10.10
141.0
74.6
10.40
129.0
129.0
10.00
129.0
129.0
10.00
136.0
111.0
10.20
145.0
83.8
10.50
136.0
136.0
10.20
136.0
136.0
10.20
139.0
124.0
10.30
148.0
92.3
10.60
95
TC
118.0
118.0
10.20
116.0
116.0
10.60
112.0
112.0
11.40
120.0
114.0
10.20
117.0
113.0
10.60
112.0
110.0
11.40
128.0
94.6
138.0
73.6
127.0
127.0
10.40
125.0
125.0
10.80
120.0
120.0
11.60
127.0
127.0
10.40
125.0
125.0
10.80
120.0
120.0
11.70
133.0
109.0
10.60
130.0
108.0
11.00
124.0
106.0
11.80
142.0
82.7
133.0
133.0
10.60
130.0
130.0
11.00
125.0
125.0
11.80
133.0
133.0
10.60
130.0
130.0
11.00
125.0
125.0
11.80
136.0
123.0
10.70
133.0
121.0
11.10
127.0
119.0
11.90
145.0
91.2
100
105
115
SHC
kW
10.50
10.80
10.90
11.00
TC
SHC
kW
TC
SHC
kW
126.0
93.5
10.90
120.0
91.4
11.70
135.0
72.6
11.20
129.0
70.5
12.00
139.0
81.6
11.30
133.0
79.5
12.10
142.0
90.1
11.40
135.0
87.9
12.20
569D120/524A-B150 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
3750
5000
6250
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
119.0
119.0
8.42
118.0
118.0
8.80
123.0
112.0
8.51
121.0
111.0
8.89
132.0
93.2
8.77
130.0
92.3
9.14
142.0
73.4
9.05
140.0
72.5
9.43
128.0
128.0
8.66
126.0
126.0
9.05
129.0
127.0
8.68
127.0
126.0
9.06
137.0
106.0
8.90
135.0
105.0
9.28
147.0
81.4
9.18
144.0
80.5
9.56
135.0
135.0
8.84
133.0
133.0
9.22
135.0
135.0
8.84
133.0
133.0
9.22
140.0
118.0
8.99
138.0
117.0
9.37
150.0
88.6
9.27
147.0
87.8
9.65
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
114.0
114.0
9.57
116.0
109.0
9.64
125.0
90.4
9.89
135.0
70.7
10.20
122.0
122.0
9.81
123.0
122.0
9.81
130.0
103.0
10.00
139.0
78.7
10.30
128.0
128.0
9.99
128.0
128.0
9.99
133.0
115.0
10.10
142.0
86.0
10.40
95
TC
112.0
112.0
9.98
110.0
110.0
10.40
106.0
106.0
11.20
114.0
108.0
10.00
112.0
106.0
10.40
107.0
104.0
11.20
123.0
89.3
132.0
69.7
120.0
120.0
10.20
118.0
118.0
10.60
114.0
114.0
11.40
120.0
120.0
10.20
118.0
118.0
10.60
113.0
113.0
11.40
127.0
102.0
10.40
124.0
101.0
10.80
119.0
99.1
11.60
136.0
77.7
126.0
126.0
10.40
123.0
123.0
10.80
119.0
119.0
11.60
126.0
126.0
10.40
123.0
123.0
10.80
119.0
119.0
11.60
130.0
114.0
10.50
127.0
113.0
10.90
121.0
110.0
11.70
139.0
85.0
100
105
115
SHC
kW
10.30
10.60
10.70
10.80
TC
SHC
kW
TC
SHC
kW
120.0
88.2
10.70
115.0
86.1
11.50
129.0
68.7
11.00
124.0
66.6
11.80
133.0
76.7
11.10
127.0
74.6
11.90
136.0
84.0
11.20
130.0
81.9
12.00
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
21
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 576C120
576C120/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air — Cfm
4000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
3000
5000
57
62
67
72
57
62
67
72
57
62
67
72
TC
113.0
113.0
8.00
111.0
111.0
8.39
118.0
104.0
8.12
115.0
102.0
8.51
129.0
87.4
8.35
126.0
86.1
8.76
141.0
70.5
8.61
137.0
69.3
9.05
124.0
124.0
8.26
122.0
122.0
8.67
126.0
121.0
8.29
123.0
119.0
8.69
135.0
101.0
8.49
132.0
99.5
8.91
147.0
78.8
8.75
144.0
77.6
9.20
132.0
132.0
8.43
129.0
129.0
8.86
132.0
132.0
8.43
129.0
129.0
8.86
139.0
113.0
8.58
136.0
112.0
9.01
151.0
86.6
8.82
148.0
85.4
9.28
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
106.0
106.0
9.17
110.0
99.8
9.28
120.0
83.7
9.58
131.0
66.9
9.93
117.0
117.0
9.49
117.0
116.0
9.51
125.0
96.9
9.76
137.0
75.1
10.10
124.0
124.0
9.72
124.0
124.0
9.72
129.0
109.0
9.88
140.0
82.9
10.20
95
TC
104.0
104.0
9.55
102.0
102.0
9.93
97.2
97.2
10.70
107.0
98.4
9.65
104.0
97.0
10.00
98.6
94.2
10.80
117.0
82.4
9.98
114.0
81.1
10.40
107.0
78.6
11.20
128.0
65.7
114.0
114.0
9.90
112.0
112.0
10.30
106.0
106.0
11.10
114.0
114.0
9.90
112.0
112.0
10.30
106.0
106.0
11.10
122.0
95.6
133.0
73.9
121.0
121.0
10.10
118.0
118.0
10.60
113.0
113.0
11.40
121.0
121.0
10.10
118.0
118.0
10.60
113.0
113.0
11.40
126.0
108.0
10.30
122.0
106.0
10.70
116.0
104.0
11.50
137.0
81.7
100
105
115
SHC
kW
10.40
10.20
10.50
10.60
TC
SHC
kW
TC
SHC
kW
124.0
64.5
10.80
118.0
62.1
11.60
119.0
94.3
10.60
112.0
91.7
11.40
130.0
72.7
11.00
122.0
70.2
11.80
133.0
80.5
11.10
125.0
78.0
12.00
576C120/524A-B120 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
3000
4000
5000
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
107.0
107.0
7.91
105.0
105.0
8.29
112.0
98.8
8.03
110.0
97.5
8.40
123.0
83.3
8.25
120.0
82.2
8.65
134.0
67.2
8.49
131.0
66.1
8.92
118.0
118.0
8.14
115.0
115.0
8.54
119.0
114.0
8.18
117.0
113.0
8.57
129.0
95.5
8.38
126.0
94.3
8.79
140.0
74.8
8.62
137.0
73.7
9.06
125.0
125.0
8.30
122.0
122.0
8.71
125.0
125.0
8.30
122.0
122.0
8.71
133.0
107.0
8.46
129.0
105.0
8.88
144.0
81.8
8.71
141.0
80.6
9.15
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
101.0
101.0
9.04
105.0
95.0
9.15
114.0
79.8
9.44
125.0
63.9
9.78
111.0
111.0
9.34
111.0
109.0
9.36
120.0
92.0
9.61
131.0
71.4
9.94
117.0
117.0
9.54
117.0
117.0
9.54
123.0
103.0
9.72
134.0
78.4
10.00
95
TC
98.9
98.9
9.41
96.8
96.8
9.78
92.5
92.5
10.50
102.0
93.7
9.51
99.4
92.3
9.87
94.1
89.7
10.60
111.0
78.7
9.83
108.0
77.5
10.0
103.0
75.1
11.00
122.0
62.8
108.0
108.0
9.73
106.0
106.0
10.10
101.0
101.0
10.90
109.0
108.0
9.74
106.0
106.0
10.10
101.0
101.0
10.90
117.0
90.8
127.0
70.3
115.0
115.0
9.94
112.0
112.0
10.30
107.0
107.0
11.20
115.0
115.0
9.95
112.0
112.0
10.30
107.0
107.0
11.20
120.0
102.0
10.10
117.0
100.0
10.50
110.0
97.7
11.30
131.0
77.3
100
105
115
SHC
kW
10.20
10.00
10.40
10.50
TC
SHC
kW
TC
SHC
kW
119.0
61.6
10.60
113.0
59.4
11.40
113.0
89.5
10.40
107.0
87.1
11.20
124.0
69.2
10.80
117.0
67.0
11.60
127.0
76.1
10.90
120.0
73.9
11.80
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
22
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 576C120 (cont)
576C120/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
3750
6250
57
62
67
72
57
62
67
72
57
62
67
72
TC
122.0
122.0
8.23
120.0
120.0
8.64
125.0
117.0
8.28
122.0
116.0
8.69
135.0
97.7
8.51
132.0
96.5
8.94
147.0
77.1
8.77
144.0
76.0
9.22
133.0
133.0
8.47
130.0
130.0
8.90
133.0
133.0
8.47
130.0
130.0
8.90
141.0
113.0
8.64
138.0
112.0
9.07
153.0
86.9
8.88
149.0
85.6
9.35
141.0
141.0
8.62
138.0
138.0
9.07
141.0
141.0
8.62
138.0
138.0
9.07
145.0
127.0
8.72
142.0
126.0
9.16
157.0
96.0
8.95
153.0
94.7
9.42
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
115.0
115.0
9.46
116.0
113.0
9.50
126.0
93.9
9.78
137.0
73.6
10.10
125.0
125.0
9.76
125.0
125.0
9.76
131.0
109.0
9.95
142.0
83.2
10.30
132.0
132.0
9.97
132.0
132.0
9.97
135.0
123.0
10.10
145.0
92.3
10.40
95
TC
113.0
113.0
9.86
110.0
110.0
10.30
105.0
105.0
11.10
113.0
111.0
9.89
111.0
109.0
10.30
105.0
105.0
11.10
123.0
92.6
134.0
72.4
122.0
122.0
10.20
119.0
119.0
10.60
114.0
114.0
11.50
122.0
122.0
10.20
119.0
119.0
10.60
114.0
114.0
11.50
128.0
108.0
10.40
124.0
107.0
10.80
117.0
104.0
11.60
139.0
82.0
129.0
129.0
10.40
126.0
126.0
10.80
120.0
120.0
11.70
129.0
129.0
10.40
126.0
126.0
10.80
120.0
120.0
11.70
131.0
121.0
10.50
128.0
120.0
10.90
121.0
117.0
11.80
141.0
91.1
100
105
115
SHC
kW
10.20
10.60
10.70
10.80
TC
SHC
kW
TC
SHC
kW
119.0
91.4
10.60
113.0
88.8
11.40
130.0
71.1
11.00
123.0
68.7
11.90
135.0
80.8
11.20
127.0
78.4
12.10
138.0
89.9
11.30
130.0
87.4
12.20
576C120/524A-B150 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
3750
5000
6250
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
115.0
115.0
8.08
113.0
113.0
8.47
118.0
110.0
8.14
116.0
109.0
8.53
129.0
92.3
8.37
126.0
91.1
8.78
140.0
73.1
8.62
137.0
71.9
9.06
125.0
125.0
8.30
123.0
123.0
8.71
126.0
125.0
8.30
123.0
123.0
8.72
134.0
106.0
8.48
131.0
105.0
8.91
146.0
81.7
8.74
142.0
80.5
9.18
132.0
132.0
8.45
130.0
130.0
8.88
132.0
132.0
8.45
130.0
130.0
8.88
138.0
119.0
8.57
134.0
117.0
8.99
149.0
89.6
8.81
146.0
88.5
9.26
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
109.0
109.0
9.25
110.0
106.0
9.31
120.0
88.7
9.60
131.0
69.6
9.94
118.0
118.0
9.54
118.0
118.0
9.54
124.0
102.0
9.75
136.0
78.2
10.10
124.0
124.0
9.73
124.0
124.0
9.74
128.0
114.0
9.85
139.0
86.1
10.20
95
TC
106.0
106.0
9.64
104.0
104.0
10.00
99.2
99.2
10.80
108.0
104.0
9.68
105.0
103.0
10.10
99.3
99.3
10.80
116.0
87.5
9.99
113.0
86.2
10.40
107.0
83.7
11.20
127.0
68.5
115.0
115.0
9.95
112.0
112.0
10.40
107.0
107.0
11.20
115.0
115.0
9.95
113.0
113.0
10.40
107.0
107.0
11.20
121.0
101.0
10.10
118.0
99.7
10.60
111.0
97.1
11.40
132.0
77.0
121.0
121.0
10.20
118.0
118.0
10.60
113.0
113.0
11.40
121.0
121.0
10.20
118.0
118.0
10.60
113.0
113.0
11.40
124.0
113.0
10.30
121.0
111.0
10.70
114.0
108.0
11.50
135.0
84.9
100
105
115
SHC
kW
10.40
10.50
10.60
TC
SHC
kW
TC
SHC
kW
124.0
67.3
10.80
117.0
64.9
11.60
129.0
75.8
10.90
121.0
73.5
11.80
131.0
83.8
11.00
124.0
81.4
11.90
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
23
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 569F120
569F120/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air — Cfm
4000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
3000
5000
57
62
67
72
57
62
67
72
57
62
67
72
TC
112.0
112.0
7.90
110.0
110.0
8.35
116.0
102.0
7.94
114.0
102.0
8.39
126.0
85.9
8.06
123.0
85.0
8.51
136.0
68.8
8.19
134.0
67.9
8.65
122.0
122.0
8.01
120.0
120.0
8.46
123.0
119.0
8.03
121.0
118.0
8.47
131.0
98.8
8.13
129.0
97.9
8.58
142.0
76.7
8.27
140.0
75.8
8.72
129.0
129.0
8.10
127.0
127.0
8.55
129.0
129.0
8.10
127.0
127.0
8.55
135.0
111.0
8.18
133.0
110.0
8.63
146.0
84.2
8.32
143.0
83.3
8.77
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
107.0
107.0
9.24
110.0
99.6
9.28
119.0
83.2
9.40
130.0
66.3
9.56
116.0
116.0
9.36
117.0
115.0
9.37
124.0
96.1
9.48
135.0
74.1
9.63
123.0
123.0
9.46
123.0
123.0
9.46
128.0
108.0
9.53
138.0
81.6
9.69
95
TC
105.0
105.0
9.74
103.0
103.0
10.20
99.7
99.7
11.20
108.0
98.6
9.78
106.0
97.5
10.30
102.0
95.5
11.30
117.0
82.3
9.91
115.0
81.3
10.40
110.0
79.5
11.40
127.0
65.4
114.0
114.0
9.87
112.0
112.0
10.40
108.0
108.0
11.40
115.0
114.0
9.87
113.0
112.0
10.40
108.0
108.0
11.40
122.0
95.1
9.98
119.0
94.1
10.50
115.0
92.2
11.50
132.0
73.2
121.0
121.0
9.97
119.0
119.0
10.50
115.0
115.0
11.50
121.0
121.0
9.97
119.0
119.0
10.50
114.0
114.0
11.50
125.0
107.0
10.00
123.0
106.0
10.50
118.0
104.0
11.60
135.0
80.7
100
105
115
SHC
kW
10.10
10.10
10.20
TC
SHC
kW
TC
SHC
kW
125.0
64.4
10.60
120.0
62.6
11.60
129.0
72.3
10.70
124.0
70.5
11.70
132.0
79.8
10.70
127.0
78.0
11.70
569F120/524A-B120 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
3000
4000
5000
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
106.0
106.0
7.83
104.0
104.0
8.28
110.0
97.2
7.89
108.0
96.3
8.33
119.0
81.5
7.98
117.0
80.7
8.43
130.0
65.3
8.11
127.0
64.5
8.56
115.0
115.0
7.94
113.0
113.0
8.38
116.0
112.0
7.95
114.0
111.0
8.40
125.0
93.2
8.05
123.0
92.3
8.49
135.0
72.4
8.17
133.0
71.7
8.63
121.0
121.0
8.01
120.0
120.0
8.46
121.0
121.0
8.01
120.0
120.0
8.46
128.0
104.0
8.09
126.0
103.0
8.54
138.0
79.0
8.22
136.0
78.2
8.67
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
101.0
101.0
9.18
105.0
94.5
9.21
114.0
79.1
9.33
123.0
63.0
9.47
110.0
110.0
9.28
111.0
108.0
9.29
118.0
90.7
9.39
128.0
70.2
9.54
116.0
116.0
9.36
116.0
116.0
9.36
122.0
101.0
9.44
131.0
76.7
9.58
95
TC
99.7
99.7
9.67
98.1
98.1
10.20
94.9
94.9
11.20
103.0
93.6
9.71
101.0
92.6
10.20
97.1
90.6
11.20
111.0
78.3
9.83
109.0
77.4
10.30
105.0
75.7
11.30
121.0
62.2
9.97
119.0
61.3
10.50
114.0
59.7
11.50
108.0
108.0
9.78
106.0
106.0
10.30
103.0
103.0
11.30
109.0
107.0
9.79
107.0
106.0
10.30
103.0
103.0
11.30
116.0
89.8
9.90
114.0
89.0
10.40
110.0
87.3
11.40
126.0
69.3
114.0
114.0
9.87
112.0
112.0
10.40
108.0
108.0
11.40
114.0
114.0
9.87
112.0
112.0
10.40
108.0
108.0
11.40
119.0
100.0
9.94
117.0
99.3
10.40
112.0
97.5
11.50
129.0
75.9
10.1
126.0
75.1
10.60
121.0
73.4
11.60
100
105
115
SHC
kW
10.00
TC
SHC
kW
TC
SHC
kW
123.0
68.5
10.60
119.0
66.8
11.60
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
24
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 569F120 (cont)
569F120/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
3750
6250
57
62
67
72
57
62
67
72
57
62
67
72
TC
121.0
121.0
8.00
119.0
119.0
8.45
123.0
116.0
8.03
121.0
115.0
8.48
132.0
96.4
8.14
130.0
95.5
8.59
143.0
75.6
8.29
141.0
74.8
8.74
131.0
131.0
8.12
129.0
129.0
8.58
131.0
131.0
8.12
129.0
129.0
8.58
138.0
112.0
8.21
135.0
111.0
8.67
148.0
85.1
8.36
146.0
84.3
8.82
140.0
140.0
8.24
138.0
138.0
8.70
138.0
138.0
8.22
137.0
137.0
8.68
143.0
127.0
8.28
140.0
126.0
8.73
153.0
94.5
8.42
150.0
93.6
8.88
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
115.0
115.0
9.35
117.0
112.0
9.37
125.0
93.7
9.50
136.0
73.1
9.66
125.0
125.0
9.49
125.0
125.0
9.49
131.0
109.0
9.57
141.0
82.5
9.73
134.0
134.0
9.62
133.0
133.0
9.60
135.0
124.0
9.64
145.0
91.9
9.80
95
TC
113.0
113.0
9.86
112.0
112.0
10.40
108.0
108.0
11.40
115.0
111.0
9.87
113.0
110.0
10.40
108.0
107.0
11.40
123.0
92.8
10.0
121.0
91.8
10.50
116.0
89.9
11.50
133.0
72.1
123.0
123.0
10.00
121.0
121.0
10.50
116.0
116.0
11.50
123.0
123.0
9.99
121.0
121.0
10.50
116.0
116.0
11.50
128.0
108.0
10.10
125.0
107.0
10.60
120.0
105.0
11.60
138.0
81.6
131.0
131.0
10.10
129.0
129.0
10.60
124.0
124.0
11.70
131.0
131.0
10.10
129.0
129.0
10.60
124.0
123.0
11.70
132.0
123.0
10.10
130.0
122.0
10.70
124.0
120.0
11.70
142.0
91.0
100
105
115
SHC
kW
10.20
10.20
10.30
TC
SHC
kW
TC
SHC
kW
131.0
71.2
10.70
126.0
69.4
11.70
135.0
80.7
10.80
130.0
78.9
11.80
139.0
90.0
10.80
133.0
88.2
11.90
569F120/524A-B150 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
3750
5000
6250
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
114.0
114.0
7.93
113.0
113.0
8.37
117.0
109.0
7.96
115.0
108.0
8.40
126.0
91.1
8.07
124.0
90.2
8.51
137.0
71.7
8.20
134.0
70.8
8.65
124.0
124.0
8.03
122.0
122.0
8.49
124.0
124.0
8.04
122.0
122.0
8.49
131.0
105.0
8.13
129.0
104.0
8.58
142.0
80.0
8.27
139.0
79.2
8.72
132.0
132.0
8.14
130.0
130.0
8.59
130.0
130.0
8.12
129.0
129.0
8.57
136.0
118.0
8.19
133.0
117.0
8.64
146.0
88.2
8.33
144.0
87.4
8.78
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
109.0
109.0
9.27
111.0
106.0
9.29
120.0
88.5
9.41
130.0
69.2
9.56
118.0
118.0
9.39
118.0
118.0
9.39
124.0
102.0
9.48
135.0
77.6
9.63
126.0
126.0
9.51
125.0
125.0
9.48
129.0
115.0
9.55
139.0
85.8
9.70
95
TC
107.0
107.0
9.77
106.0
106.0
10.30
102.0
102.0
11.30
109.0
105.0
9.79
107.0
103.0
10.30
103.0
101.0
11.30
117.0
87.6
9.91
115.0
86.7
10.40
110.0
84.8
11.40
127.0
68.3
116.0
116.0
9.90
114.0
114.0
10.40
110.0
110.0
11.40
116.0
116.0
9.89
114.0
114.0
10.40
110.0
110.0
11.40
122.0
101.0
9.99
119.0
100.0
10.50
114.0
98.1
11.50
132.0
76.7
124.0
124.0
10.00
122.0
122.0
10.50
118.0
118.0
11.50
123.0
123.0
9.99
121.0
121.0
10.50
117.0
117.0
11.50
126.0
114.0
10.10
124.0
113.0
10.60
118.0
111.0
11.60
136.0
84.9
100
105
115
SHC
kW
10.10
10.10
10.20
TC
SHC
kW
TC
SHC
kW
125.0
67.4
10.60
120.0
65.7
11.60
129.0
75.8
10.70
124.0
74.1
11.70
133.0
84.0
10.70
128.0
82.3
11.70
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
25
ELECTRICAL DATA
569D072-120, 576C120, 569F120 UNITS
NOMINAL
VOLTAGE
V-Ph-Hz
VOLTAGE
RANGE*
MIN MAX
FAN MOTORS
(Qty 2)
POWER
SUPPLY
FACTORY-
INSTALLED
OPTION
COMPRESSOR
UNIT
SIZE
RLA
LRA
FLA (ea)
LRA (ea)
MCA
MOCP
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
25.8
30.6
12.8
15.0
10.2
12.0
35.0
39.8
17.4
19.6
13.8
15.5
50.3
55.1
22.9
25.1
17.8
19.5
48.0
52.8
23.9
26.1
18.6
20.3
39.0
43.8
19.4
21.6
15.8
17.5
35
35
20
20
15
15
60
60
30
30
20
20
60
70
30
30
25
25
60
70
35
35
30
30
50
50
25
25
20
20
208/230-3-60
187
418
523
187
418
523
187
418
523
187
418
523
187
418
523
254
506
632
254
506
632
254
506
632
254
506
632
254
506
632
19.2
146
0.9
1.6
072
090
460-3-60
575-3-60
9.6
7.7
25.6
12.8
10.2
37.8
17.2
13.4
36
73
58.4
190
95
0.4
0.4
1.5
0.7
0.7
1.5
0.7
0.7
1.5
0.7
0.7
1.5
0.7
0.7
0.9
0.9
3.1
1.9
1.9
3.1
1.9
1.9
3.1
1.9
1.9
3.1
1.9
1.9
208/230-3-60
460-3-60
569D
575-3-60
76
208/230-3-60
460-3-60
239
125
80
120
575-3-60
208/230-3-60
460-3-60
198
99
576C 120
569F 120
18
575-3-60
14
79
208/230-3-60
460-3-60
16
125
66.5
50
8
575-3-60
6.4
LEGEND
FLA — Full Load Amps
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC — National Electrical Code
RLA — Rated Load Amps
*Units are suitable for use on electrical systems where voltage supplied
to the unit terminals is not below or above the listed limits.
NOTES:
1. The MCA and MOCP values are calculated in accordance with the
NEC, Article 440.
2. Motor RLA and LRA values are established in accordance with
Underwriters’ Laboratories (UL), Standard 1995.
3. The 575-v units are UL, Canada-listed only.
4. Convenience outlet is available as either a factory-installed option
or a field-installed accessory and is 115-v, 1 ph, 60 Hz.
26
APPLICATION DATA — 569D072-120, 576C090-120, 569F120
OPERATING LIMITS MINIMUM OUTDOOR-AIR OPERATING
TEMPERATURE
Maximum Cooling Outdoor
115 F
MINIMUM
OUTDOOR TEMP
(F)
See Minimum Outdoor-Air
Operating Temperature
table at right.
COND
TEMP
(F)
Minimum Outdoor Ambient
UNIT
SIZE
COMPR
CAPACITY
With
Minimum Return-Air
Temperature
Std
Motormaster®
Control
55 F
Maximum Return-Air
Temperature
Normal Acceptable Saturation
Suction Temperature Range
Maximum Discharge
Temperature
Minimum Discharge Superheat
072
090
120
100%
100%
100%
100%
67%
90
90
90
90
80
35
35
35
35
35
95 F
569D
25 to 55 F
–20
576C
569F
120*
120
275 F
60 F
100%
90
35
*Unit has one step of unloading.
NOTES:
1. Select air handler at no less than 300 cfm/ton (nominal condens-
ing unit capacity).
REFRIGERANT PIPING SIZES
2. Total combined draw of the field-supplied liquid line solenoid valve
and air handler fan contactor must not exceed 22 va. If the speci-
fied va must be exceeded, use a remote relay to control the load.
LINEAR LENGTH OF PIPING — FT
25-50 50-75
Line Size (in. OD)
0-25
75-100
UNIT
SIZE
1. LIQUID LINE — For applications with liquid lift greater than
L
S
L
S
L
S
L
S
3
5
20 ft, use 1/2-in. liquid line where /8 in. is shown; use /8-in.
3
3
3
3
072
/
/
/
/
11/8
11/8
13/8
13/8
/
/
/
/
11/8
11/8
13/8
13/8
/
8
/
2
/
2
/
2
11/8
11/8
13/8
13/8
/
/
/
/
11/8
11/8
13/8
13/8
8
8
2
2
8
2
2
2
8
2
2
2
1
liquid line where /2 in. is shown. The maximum liquid lift is
3
1
1
1
1
1
1
1
1
1
1
1
569D 090
120
60 ft.
576C 120
MAXIMUM REFRIGERANT CHARGE
569F 120 (2) 3/8 (2) 11/8 (2) 3/8 (2) 11/8 (2) 3/8 (2) 11/8 (2) 3/8 (2) 11/8
UNIT
R-22 (lb)
SIZE
LEGEND
L — Liquid Line
S — Suction Line
072
090
120
120
120
17.3
34.2
34.2
34.2
(2) 17.1
569D
NOTES:
1. Pipe sizes are based on a 2° F loss for liquid and suction lines.
2. Pipe sizes are based on the maximum linear length, shown for
each column, plus a 50% allowance for fittings.
576C
569F
3. Charge units with R-22 in accordance with unit installation
instructions.
2. REFRIGERANT PIPING — It is recommended that the
refrigerant piping for all commercial split systems include a
liquid line solenoid valve, a liquid line filter drier, and a sight
glass.
For refrigerant lines longer than 75 lineal ft, a liquid line
solenoid valve and a suction accumulator are required.
Refer to the Refrigerant Specialties table.
REFRIGERANT SPECIALTIES PART NUMBERS
LIQUID LINE
SIZE (in.)
LIQUID LINE
SOLENOID VALVE (LLSV)
LLSV
COIL
SIGHT
GLASS
FILTER
DRIER
SUCTION LINE
ACCUMULATOR
UNIT
3
569D072
/
200RB5T3M
200RB5T3M
200RB5T4M
200RB6T4M
200RB6T4M
AMG/24V
AMG/24V
AMG/24V
AMG/24V
AMG/24V
AMI-1TT3
AMI-1TT3
AMI-1TT4
AMI-1TT4
AMI-1TT4
P502-8304S*
P502-8304S*
P502-8304S
P502-8307S*
P502-8307S*
S-7063S*
S-7063S*
S-7063S*
S-7063
S-7063
S-7061 Qty 2
8
3
/
1
8
569D090
569D120
576C120
/
2
1
/
1
2
/
2
3
/
200RB5T3M Qty 2
AMG/24V Qty 2
AMI-1TT3 Qty 2
P502-8304S* Qty 2
8
*Bushings required.
27
TYPICAL PIPING AND WIRING
WEATHERPROOF
FUSED DISCONNECT*
PER NEC
CONDENSING
MOISTURE
UNIT
ELECTRIC
HEATER
ACCESSORY
INDICATOR
SIGHT GLASS*
FIELD
SUPPLIED
POWER
POWER WIRES
LLSV*
PITCH
LIQUID
LINE
FILTER
DRIER*
INSULATED
VAPOR
LINE
524A
UNIT
CONTROL
WIRES
CONDENSATE DRAIN
POWER WIRES
INDOOR
THERMOSTAT†
FUSED DISCONNECT
PER NEC
TO OPEN SIGHT
DRAIN
NOTES:
LEGEND
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System
Design Manual for details.
LLSV — Liquid Line Solenoid Valve
NEC — National Electrical Code
TXV — Thermostatic Expansion Valve
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not
intended for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refriger-
ant migration to the compressor.
*Field supplied.
†Accessory item.
5. Internal factory-supplied TXVs not shown.
Rooftop Installation — 569D072-120, 576C120
28
GUIDE SPECIFICATIONS — 569D072-120, 576C120
COMMERCIAL AIR-COOLED CONDENSING UNITS D. Compressor:
1. Compressor shall be of the scroll type (569D) or
HVAC GUIDE SPECIFICATIONS
semi-hermetic reciprocating type (576C).
SIZE RANGE: 6 TO 10 TONS, NOMINAL
2. Compressors shall be mounted on vibration
isolators.
BRYANT MODEL NUMBERS: 569D, SIZES 072-120
576C, SIZE 120
3. Compressors shall include overload protection.
PART 1 — GENERAL
4. Compressors shall be equipped with a crankcase
heater.
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit suitable for
on-the-ground or rooftop installation. Unit shall consist of a
reciprocating air-conditioning compressor assembly
(576C) or scroll compressor (569D), an air-cooled coil,
propeller-type condenser fan, and a control box. Unit shall
discharge supply air upward as shown on contract draw-
ings. Unit shall be used in a refrigeration circuit matched
with a packaged air-handling unit.
5. Compressor shall be equipped with internal high dis-
charge temperature protection (569D072 and 120
only).
6. Compressor shall unload using suction cutoff unload-
ing (576C120 only). Electric solenoid unloading
available as an accessory.
E. Condenser Coil:
1.02 QUALITY ASSURANCE
1. Condenser coil shall be air-cooled and circuited for
integral subcooler.
A. Unit shall be rated in accordance with ARI latest
revisions.
2. Coil shall be constructed of aluminum fins (copper
fins optional) mechanically bonded to internally
grooved seamless copper tubes which are then
cleaned, dehydrated, and sealed.
B. Unit construction shall comply with ANSI/ASHRAE 15
safety code latest revision and comply with NEC.
C. Unit shall be constructed in accordance with UL 1995
standard and shall carry the UL and UL, Canada label.
F. Refrigeration Components:
D. Unit cabinet shall be capable of withstanding 500-hour
salt spray exposure per ASTM B117 (scribed specimen).
Refrigeration circuit components shall include liquid line
service valve, suction line service valve, liquid filter drier,
a full charge of compressor oil, and a holding charge of
refrigerant. Unit 569D120 shall include an accumulator.
Units with semi-hermetic compressors (576C) shall have
oil-level sight glass and all units shall have crankcase
heater.
E. Air-cooled condenser coils for semi-hermetic compressor
units (576C) shall be leak tested at 150 psig and pressure
tested at 480 psig. Air-cooled condenser coils for scroll
compressor units (569D) shall be leak tested at 200 psig,
and pressure tested at 428 psig.
G. Controls and Safeties:
F. Unit shall be manufactured in a facility registered to
ISO 9001:2000 manufacturing quality standard.
1. Minimum control functions shall include:
a. Control wire terminal blocks.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as single package only, and shall be
stored and handled according to unit manufacturer’s
recommendations.
b. Compressor lockout on auto-reset safety until
reset from thermostat.
2. Minimum safety devices which are equipped with
automatic reset (after resetting first at thermostat),
shall include:
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING
ENGINEER.)
PART 2 — PRODUCTS
2.01 EQUIPMENT
A. General:
a. High discharge pressure cutout.
b. Low Pressure cutout.
c. High discharge temperature cutout (569D090
only).
Factory-assembled, single piece, air-cooled condensing
unit. Contained within the unit enclosure shall be all
factory wiring, piping, controls, compressor, holding
charge (R-22), and special features required prior to field
start-up.
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet or
exceed Btuh at a suction temperature of ______ F.
The power consumption at full load shall not exceed
______ kW.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
bonderized and coated with a prepainted baked
enamel finish.
2. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net cool-
ing capacity of ______ Btuh or greater at conditions
of ______ cfm entering-air temperature at the evapo-
rator at ______ F wet bulb and ______ F dry bulb,
and air entering the condensing unit at ______ F.
2. A heavy-gage roll-formed perimeter base rail with
forklift slots and lifting holes shall be provided to facil-
itate rigging.
3. The system shall have an EER of ______ Btuh/Watt
or greater at standard ARI conditions.
C. Fans:
1. Condenser fans shall be direct driven, propeller-type,
discharging air vertically upward.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
______ v, 3-ph, 60 Hz. The unit shall be capable of
satisfactory operation within voltage limits of
______ v to ______ v.
2. Fan blades shall be balanced.
3. Condenser fan discharge openings shall be
equipped with PVC coated steel wire safety guards.
4. Condenser fan and motor shaft shall be corrosion
resistant.
2. Unit electrical power shall be single-point connection.
3. Unit control circuit shall contain a 24-v transformer
for unit control.
29
GUIDE SPECIFICATIONS — 569D072-120, 576C120 (cont)
shall be aluminum-fins mechanically bonded to
J. Special Features:
copper tubes.
1. Low-Ambient Temperature Control Accessory:
3. Thermostat Control Accessory:
Low-ambient control shall be available as a factory-
installed option or a field-installed accessory and
shall regulate speed of condenser-fan motor in
response to the saturated condensing temperature
of the unit. The control shall maintain correct con-
densing pressure at outdoor temperatures down to
–20 F (fan motor change required for 569D and
576C units).
a. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multi-stage capabil-
ity, and large LCD temperature display.
b. Commercial Electronic Non-programmable Ther-
mostat with auto-changeover, multi-stage capacity,
and large LCD display.
4. Hail Guard Accessory:
2. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Hail guard package shall protect coils against dam-
age from hail and other flying debris.
Shall have a durable epoxy-phenolic coating to
provide protection in mildly corrosive coastal envi-
ronments. Coating shall be applied to the alumi-
num fin stock prior to the fin stamping process to
create an inert barrier between the aluminum
fin and copper tube. Epoxy-phenolic barrier shall
minimize galvanic action between dissimilar
metals.
5. Condenser Coil Grille Accessory:
Grille shall add decorative appearance to unit and
protect condenser coil after installation.
6. Electric Solenoid Unloader Accessory:
Electric unloader valve piston, coil, and hardware
shall be supplied to convert the pressure-operated
compressor unloader to electric unloading (576C120
only).
b. E-Coated Aluminum-Fin Coils:
7. Unit-Mounted, Non-Fused Disconnect Switch:
Shall have a flexible epoxy polymer coating uni-
formly applied to all coil surface areas without
material bridging between fins. Coating process
shall ensure complete coil encapsulation. Color
shall be high gloss black with gloss requirements
of 60° of 65-90% per ASTM D523-89. Uniform dry
film thickness from 0.8 to 1.2 mil on all surface
areas including fin edges. Superior hardness char-
acteristics of 2H per ASTM D3363-92A and cross
hatch adhesion of 4B-5B per ASTM D3359-93.
Impact resistance shall be up to 160 in./lb (ASTM
D2794-93). Humidity and water immersion resis-
tance shall be up to a minimum of 1000 and
250 hours respectively (ASTM-D2247-92 and
ASTM D870-92). Corrosion durability shall be con-
firmed through testing to no less than 1000 hours
salt spray per ASTM B117-90. Coil construction
Shall be factory-installed, internally mounted. NEC
and UL approved non-fused switch shall provide unit
power shutoff. Shall be accessible from outside the
unit and shall provide power off lockout capability.
Not to be used when rooftop electrical rating
exceeds 80 amperes.
8. Convenience Outlet:
Shall be factory-installed and internally mounted
with easily accessible 115-v female receptacle. Shall
include 15 amp GFI receptacle with independent
fuse protection. Voltage required to operate conve-
nience outlet shall be provided by a factory-installed
step-down transformer. Shall be accessible from out-
side the unit.
30
GUIDE SPECIFICATIONS — 569F120
4. Compressors shall be equipped with a crankcase
COMMERCIAL AIR-COOLED CONDENSING UNITS
heater.
HVAC GUIDE SPECIFICATIONS
SIZE RANGE: 10 TONS, NOMINAL
BRYANT MODEL NUMBER: 569F, SIZE 120
PART 1 — GENERAL
5. Compressors shall be equipped with high discharge
temperature protection.
E. Condenser Coil:
1. Condenser coil shall be air-cooled and circuited for
integral subcooler.
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit suitable for
on-the-ground or rooftop installation. Unit shall have
2 independent refrigeration circuits. Unit shall consist of
dual scroll compressors, air-cooled coils, propeller-type
condenser fans, and a control box. Unit shall discharge
supply air upward as shown on contract drawings. Unit
shall be used in a refrigeration circuit matched with a pack-
aged air-handling unit.
2. Coil shall be constructed of aluminum fins (copper
fins optional) mechanically bonded to internally
grooved seamless copper tubes which are then
cleaned, dehydrated, and sealed.
F. Refrigeration Components:
Refrigeration circuit components shall include liquid
line service valve, suction line service valve, a full
charge of compressor oil, and a holding charge of
refrigerant.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standard 210/
240, latest revision.
G. Controls and Safeties:
B. Unit construction shall comply with ANSI/ASHRAE 15
safety code latest revision and comply with NEC.
1. Minimum control functions shall include:
a. Control wire terminal blocks.
C. Unit shall be constructed in accordance with UL 1995
standard and shall carry the UL and UL, Canada label.
b. Compressor lockout on auto-reset safety until
reset from thermostat.
D. Unit cabinet shall be capable of withstanding 500-hour
salt spray exposure per ASTM B117 (scribed specimen).
2. Minimum safety devices which are equipped with
automatic reset (after resetting first at thermostat),
shall include:
E. Air-cooled condenser coils shall be leak tested at
200 psig, and pressure tested at 428 psig.
a. High discharge pressure cutout.
b. Low pressure cutout.
F. Unit shall be manufactured in a facility registered to ISO
9001:2000 manufacturing quality standard.
H. Operating Characteristics:
1.03 DELIVERY, STORAGE, AND HANDLING
1. The capacity of the condensing unit shall meet or
exceed _____ Btuh at a suction temperature of
_____ F. The power consumption at full load shall not
exceed _____ kW.
Unit shall be shipped as single package only, and shall be
stored and handled according to unit manufacturer’s
recommendations.
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING
ENGINEER.)
2. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net cool-
ing capacity of _____ Btuh or greater at conditions of
_____ cfm entering-air temperature at the evaporator
at _____ F wet bulb and _____ F dry bulb, and air
entering the condensing unit at _____ F.
PART 2 — PRODUCTS
2.01 EQUIPMENT
A. General:
Factory-assembled, single piece, air-cooled condensing
unit. Contained within the unit enclosure shall be all
factory wiring, piping, controls, compressor, holding
charge (R-22), and special features required prior to field
start-up.
3. The system shall have an EER of _____ Btuh/ Watt
or greater at standard ARI conditions.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be _____
v, 3-ph, 60 Hz. The unit shall be capable of satisfac-
tory operation within voltage limits of _____ v to
_____ v.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
bonderized and coated with a prepainted baked
enamel finish.
2. Unit electrical power shall be single-point connection.
3. Unit control circuit shall contain a 24-v transformer
for unit control.
2. A heavy-gage roll-formed perimeter base rail with
forklift slots and lifting holes shall be provided to facil-
itate rigging.
J. Special Features:
C. Fans:
1. Low-Ambient Temperature Control:
1. Condenser fans shall be direct driven, propeller-type,
discharging air vertically upward.
A low-ambient temperature control shall be available
as a factory-installed option or as a field-installed
accessory. This low-ambient control shall regulate
speed of the condenser-fan motors in response to
the saturated condensing temperature of the unit.
The control shall maintain correct condensing pres-
sure at outdoor temperatures down to –20 F.
2. Fan blades shall be balanced.
3. Condenser fan discharge openings shall be
equipped with PVC coated steel wire safety guards.
4. Condenser fan and motor shaft shall be corrosion
resistant.
2. Gage Panel Package:
D. Compressor:
Gage panel package shall include a suction and dis-
charge pressure gage.
1. Compressors shall be of the hermetic scroll type.
2. Compressors shall be mounted on vibration isolators.
3. Compressors shall include overload protection.
31
GUIDE SPECIFICATIONS — 569F120 (cont)
3. Optional Condenser Coil Materials:
4. Thermostat Controls:
a. Pre-Coated Aluminum-Fin Coils:
a. Programmable multi-stage thermostat with 7-day
clock, holiday scheduling, large backlit display,
remote sensor capability, and Title 24 compliance.
Shall have a durable epoxy-phenolic coating to
provide protection in mildly corrosive coastal
environments. Coating shall be applied to the
aluminum fin stock prior to the fin stamping
process to create an inert barrier between the
aluminum fin and copper tube. Epoxy-phenolic
barrier shall minimize galvanic action between
dissimilar metals.
b. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multi-stage capabil-
ity, and large LCD temperature display.
5. Hail Guard Package:
Hail guard package shall protect coils against dam-
age from hail and other flying debris.
b. E-Coated Aluminum-Fin Coils:
6. Condenser Coil Grille:
Shall have a flexible epoxy polymer coating
uniformly applied to all coil surface areas without
material bridging between fins. Coating process
shall ensure complete coil encapsulation. Color
shall be high gloss black with gloss requirements
of 60° of 65 to 90% per ASTM D523-89. Uniform
dry film thickness from 0.8 to 1.2 mil on all surface
areas including fin edges. Superior hardness
characteristics of 2H per ASTM D3363-92A
and cross hatch adhesion of 4B-5B per ASTM
D3359-93. Impact resistance shall be up to
160 in./lb (ASTM D2794-93). Humidity and water
immersion resistance shall be up to a minimum
of 1000 and 250 hours respectively (ASTM
D2247-92 and ASTM D870-92). Corrosion dura-
bility shall be confirmed through testing to no less
than 1000 hours salt spray per ASTM B117-90.
Coil construction shall be aluminum fins mechani-
cally bonded to copper tubes.
Grille shall add decorative appearance to unit and
protect condenser coil after installation.
7. Unit-Mounted, Non-Fused Disconnect Switch:
Shall be factory-installed, internally mounted. NEC
and UL approved non-fused switch shall provide unit
power shutoff. Shall be accessible from outside the
unit and shall provide power off lockout capability.
8. Convenience Outlet:
Shall be factory-installed and internally mounted with
easily accessible 115-v female receptacle. Shall
include 15 amp GFI receptacle with independent
fuse protection. Voltage required to operate conve-
nience outlet shall be provided by a factory-installed
step-down transformer. Shall be accessible from out-
side the unit.
32
MODEL NUMBER NOMENCLATURE
566D 150 000 – –
E
X
566D — Commercial Air-Cooled Condensing
Unit With Semi-Hermetic Compressor
Factory-Installed Options*
566E — Dual Circuit Commercial Air-Cooled
Condensing Unit With Scroll Compressors
Heating Capacity
000 — No Heat
Voltage Designation
E — 460-3-60
P — 208/230-3-60
T — 575-3-60
Nominal Tons Cooling
150 — 12-1/2
180 — 15
Heating
X — None
240 — 20
*Contact your local representative for more details.
Quality Assurance
Certified to ISO 9001:2000
33
PHYSICAL DATA
566D150-240 UNITS
UNIT
566D150
121/2
566D180
566D240
NOMINAL CAPACITY (tons)
15
20
OPERATING WEIGHTS (lb)
Aluminum-Fin Coil (Standard)
Copper-Fin Coil (Optional)
779
919
789
929
929
1040
REFRIGERANT TYPE*
Operating Charge, Typical (lb)†
Shipping Charge (lb)
R-22
23
3.1
23
3.1
28
3.1
COMPRESSOR
Qty...Model
Reciprocating, Semi-Hermetic
1...06DD328
1...06DD537
1...06E4250
No. Cylinders
Speed (rpm)
Oil Charge (pt)
Capacity Steps
Accessory
6
6
4
1750
10
1750
10
1750
15.5
33**, 66, 100
66, 100
33**, 66, 100
66, 100
—
50, 100
Standard
Unloader Setting (psig)
Load
70
60
125
1
2
Unload
Crankcase Heater Watts
CONDENSER FANS
Qty...Rpm
Axial Flow, Direct Drive
2...1075
Diameter (in.)
26
1
/
Nominal Hp
Nominal Airflow (cfm, total)
Watts (total)
2
11,000
1460
CONDENSER COIL
Rows...Fins/in.
Copper Tubes, Aluminum Fins
3...15
29.2
48
3...15
29.2
48
3...15
29.2
38
Face Area (sq ft)
Storage Capacity (lb)††
CONTROLS
Pressurestat (psig)
High Pressure
Cutout
395 10
295 20
Cut-in
Low Pressure
Cutout
Cut-in
27
67
4
7
FAN CYCLING CONTROLS
Operating Pressure (psig)
No. 2 Fan, Close
255 10
160 10
Open
PRESSURE RELIEF
Location
Temperature (F)
Liquid Line
200
PIPING CONNECTIONS (in. ODM)
Suction
13/8
13/8
15/8
5
/
Liquid
8
3
/
Hot Gas Stub
8
*Unit is factory-supplied with holding charge only.
†Typical operating charge with 25 ft of interconnecting piping. Operating charge is approximate for maximum system
capacity.
**Indicates capacity step (%) with electric unloader accessory.
††Storage capacity is measured at liquid saturated temperatures of 120 F.
34
PHYSICAL DATA (cont)
566E150-240 UNITS
UNIT
566E150
121/2
566E180
566E240
NOMINAL CAPACITY (tons)
OPERATING WEIGHTS (lb)
15
20
Aluminum-Fin Coil (Standard)
Copper-Fin Coil (Optional)
676
822
740
886
764
904
REFRIGERANT TYPE*
R-22
Operating Charge, Typical (lb)†
Shipping Charge (lb)
23
3.1
23
3.1
28
3.1
COMPRESSOR
Scroll
Qty...Model
2...ZR72
3500
60 (ea)
2...ZR94
3500
85 (ea)
70
2...ZR125
3500
110 (ea)
Speed (rpm)
Oil Charge (oz)
Crankcase Heater Watts
CONDENSER FANS
Qty...Rpm
2...1075
26
Diameter (in.)
1
/
Nominal Hp
Nominal Airflow (cfm, total)
Watts (total)
2
11,000
1460
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
Storage Capacity (lb)**
3...15
29.2
48
CONTROLS
Pressurestat (psig)
High Pressure
Cutout
426
7
Cut-in
320 20
Low Pressure
Cutout
Cut-in
27
67
4
7
FAN CYCLING CONTROLS
Operating Pressure (psig)
No. 2 Fan, Close
Open
255 10
160 10
PRESSURE RELIEF
Location
Temperature (F)
Liquid Line
200
PIPING CONNECTIONS (in. ODM)
Suction
(2) 13/8
(2) 1/2
Liquid
3
/
Hot Gas Stub
8
*Unit is factory-supplied with holding charge only.
†Typical operating charge with 25 ft of interconnecting piping. Operating charge is approximate for
maximum system capacity.
**Storage capacity is measured at liquid saturated temperatures of 120 F.
35
DIMENSIONS
NOTES:
1. Service clearances are as follows:
Side (compressor) — 31/2 ft
Side (opposite compressor) — 3 ft
Ends — 2 ft
Top — 5 ft
2. See page 38 for corner weights and
unit center of gravity.
566D150-240
36
DIMENSIONS (cont)
NOTES:
1. Service clearances are as follows:
Side (compressor) — 31/2 ft (1067 mm)
Side (opposite compressor) — 3 ft (914 mm)
Ends — 2 ft (610 mm)
Top — 5 ft (1524 mm)
2. See page 38 for corner weights and unit
center of gravity.
566E150-240
37
DIMENSIONS (cont)
566D150-240
ALUMINUM COIL
UNIT
566D
Standard
Weight
(lb)
Operational Weight Points (lb)
A
B
C
D
E
F
150
180
240
779
789
900
70
70
84
177
180
234
68
69
82
100
101
108
261
265
310
103
104
111
CENTER OF GRAVITY (in.)
Aluminum Coil
UNIT
566D
X
Y
150
180
240
38
38
37
16
16
17
566E150-240
ALUMINUM COIL
Operational Weight Points (lb)
UNIT
566E
Standard
Weight
(lb)
A
B
C
D
E
F
150
180
240
676
740
764
84
86
87
168
186
192
72
71
72
78
82
85
183
216
226
91
99
102
CENTER OF GRAVITY (in.)
Aluminum Coil
UNIT
566E
X
Y
150
180
240
35
35
35
19
18
18
NOTES:
1. Corner weights are approximate.
2. Actual support weights depend on level of unit and evenness of support posts.
3. Total weights represent approximate unit weights without shipping package.
4. Bottom or top skid is NOT included in the weights.
566D150-240, 566E150-240
38
PERFORMANCE DATA
CONDENSING UNIT RATINGS
566E150
566D150
SST (F)
Air Temperature Entering Condenser (F)
Air Temperature Entering Condenser (F)
SST (F)
80
85
95
100
105
115
80
85
95
100
105
115
TC
101.0
8.56
94.6
97.6
8.90
99.4
90.0
9.55
86.0
9.85
82.2
10.20
119.0
74.7
10.70
129.0
TC
102.0
9.04
99.1
9.58
93.2
10.80
118.0
90.3
11.40
123.0
87.3
12.10
128.0
81.1
13.50
138.0
25
30
kW
SDT
20
kW
109.0
114.0
SDT
103.0
108.0
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
118.0
8.80
96.6
113.0
9.17
101.0
105.0
9.90
111.0
101.0
10.20
116.0
96.7
10.60
121.0
88.5
11.20
131.0
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
114.0
9.09
103.0
111.0
9.64
108.0
105.0
10.90
118.0
102.0
11.50
123.0
98.8
12.20
128.0
92.2
13.60
138.0
25
30
35
40
45
134.0
9.03
98.6
129.0
9.44
103.0
120.0
10.20
113.0
116.0
10.60
117.0
111.0
11.00
122.0
102.0
11.70
132.0
127.0
9.14
103.0
124.0
9.70
108.0
117.0
10.90
118.0
114.0
11.50
123.0
110.0
12.20
128.0
103.0
13.70
138.0
35
150.0
9.26
101.0
145.0
9.71
105.0
135.0
10.60
115.0
130.0
11.00
119.0
126.0
11.40
124.0
116.0
12.20
134.0
140.0
9.19
103.0
137.0
9.75
108.0
130.0
11.00
118.0
126.0
11.60
123.0
123.0
12.30
128.0
115.0
13.70
138.0
40
166.0
9.50
103.0
161.0
9.98
107.0
150.0
10.90
116.0
145.0
11.40
121.0
140.0
11.80
126.0
130.0
12.70
135.0
155.0
9.26
103.0
151.0
9.81
108.0
144.0
11.00
118.0
140.0
11.70
123.0
136.0
12.30
128.0
128.0
13.80
138.0
45
TC
kW
SDT
182.0
9.73
105.0
177.0
10.30
109.0
166.0
11.30
118.0
160.0
11.70
123.0
155.0
12.20
127.0
144.0
13.10
136.0
TC
kW
SDT
170.0
9.37
103.0
166.0
9.90
108.0
158.0
11.10
118.0
154.0
11.70
123.0
150.0
12.40
128.0
141.0
13.90
138.0
50
TC
186.0
9.55
182.0
10.10
109.0
173.0
11.30
119.0
169.0
11.90
124.0
164.0
12.60
129.0
155.0
14.00
139.0
566D180
50
kW
SDT
104.0
Air Temperature Entering Condenser (F)
SST (F)
80
85
95
100
105
115
566E180
TC
139.0
12.30
99.5
134.0
12.70
104.0
126.0
13.60
114.0
121.0
14.00
118.0
117.0
14.40
123.0
108.0
15.10
133.0
Air Temperature Entering Condenser (F)
25
30
35
40
45
kW
SDT
SST (F)
80
85
95
100
105
115
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
159.0
12.90
102.0
154.0
13.40
107.0
144.0
14.30
116.0
139.0
14.70
121.0
134.0
15.20
125.0
125.0
16.00
135.0
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
141.0
12.01
101.0
137.0
12.60
105.0
129.0
13.70
115.0
124.0
14.30
120.0
120.0
14.90
125.0
110.0
16.10
135.0
20
25
30
35
40
45
179.0
13.50
105.0
173.0
14.00
109.0
163.0
15.00
119.0
157.0
15.50
123.0
152.0
16.00
128.0
142.0
16.90
137.0
156.0
12.40
102.0
152.0
12.90
107.0
143.0
14.00
116.0
138.0
14.60
121.0
133.0
15.20
126.0
123.0
16.40
136.0
198.0
14.00
108.0
192.0
14.60
112.0
181.0
15.70
121.0
175.0
16.30
125.0
170.0
16.80
130.0
158.0
17.80
139.0
171.0
12.70
104.0
166.0
13.20
108.0
157.0
14.30
118.0
152.0
14.90
123.0
147.0
15.50
127.0
136.0
16.70
137.0
218.0
14.60
110.0
212.0
15.20
115.0
199.0
16.50
124.0
193.0
17.00
128.0
187.0
17.60
132.0
175.0
18.70
141.0
187.0
13.10
105.0
182.0
13.60
110.0
172.0
14.70
119.0
166.0
15.30
12.04
161.0
15.90
129.0
150.0
17.10
138.0
TC
kW
SDT
237.0
15.20
113.0
231.0
15.90
117.0
218.0
17.20
126.0
211.0
17.80
130.0
205.0
18.40
135.0
192.0
19.60
144.0
203.0
13.50
107.0
198.0
14.00
112.0
187.0
15.10
121.0
181.0
15.70
126.0
176.0
16.30
130.0
164.0
17.50
140.0
50
221.0
13.90
109.0
215.0
14.50
114.0
204.0
15.60
123.0
198.0
16.10
127.0
192.0
16.70
132.0
179.0
17.90
141.0
566D240
Air Temperature Entering Condenser (F)
SST (F)
239.0
14.40
111.0
233.0
14.90
116.0
221.0
16.10
125.0
215.0
16.70
129.0
208.0
17.20
134.0
195.0
18.40
143.0
80
85
95
100
105
115
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
175.0
16.30
104.0
169.0
16.80
108.0
157.0
17.70
117.0
151.0
18.20
122.0
145.0
18.60
126.0
134.0
19.40
135.0
25
30
35
40
45
50
566E240
200.0
17.20
107.0
193.0
17.80
111.0
180.0
18.80
120.0
173.0
19.30
125.0
166.0
19.80
129.0
154.0
20.70
138.0
Air Temperature Entering Condenser (F)
SST (F)
80
85
95
100
105
115
224.0
18.20
110.0
217.0
18.80
115.0
202.0
19.90
123.0
195.0
20.50
128.0
188.0
21.00
132.0
175.0
22.00
141.0
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
184.0
16.20
105.0
179.0
17.00
110.0
170.0
18.50
119.0
165.0
19.40
124.0
160.0
20.20
129.0
148.0
21.70
139.0
20
25
30
35
40
45
50
249.0
19.10
114.0
241.0
19.80
118.0
225.0
21.00
126.0
218.0
21.60
131.0
210.0
22.20
135.0
195.0
23.30
144.0
202.0
16.80
107.0
197.0
17.50
112.0
186.0
19.00
121.0
181.0
19.80
126.0
176.0
20.60
131.0
163.0
22.20
140.0
273.0
20.10
117.0
265.0
20.80
121.0
248.0
22.10
129.0
240.0
22.70
134.0
232.0
23.40
138.0
216.0
24.60
146.0
220.0
17.30
109.0
214.0
18.00
113.0
203.0
19.50
123.0
197.0
20.30
127.0
191.0
21.10
132.0
179.0
22.70
141.0
297.0
21.00
120.0
289.0
21.80
124.0
271.0
23.20
132.0
262.0
23.90
137.0
253.0
24.60
141.0
236.0
25.90
149.0
239.0
18.00
111.0
233.0
18.60
116.0
220.0
20.10
125.0
214.0
20.80
129.0
208.0
21.60
134.0
194.0
23.20
143.0
259.0
18.70
113.0
253.0
19.30
118.0
239.0
20.70
127.0
232.0
21.50
131.0
225.0
22.20
136.0
211.0
23.80
145.0
LEGEND
Compressor Power
kW
—
SDT — Saturated Discharge Temperature at Compressor (F)
SST — Saturated Suction Temperature (F)
280.0
19.40
116.0
273.0
20.10
120.0
259.0
21.50
129.0
252.0
22.20
134.0
244.0
22.90
138.0
229.0
24.50
147.0
TC
—
Gross Cooling Capacity (1000 Btuh)
302.0
20.20
118.0
295.0
20.90
123.0
280.0
22.30
132.0
272.0
23.00
136.0
264.0
23.70
140.0
247.0
25.20
149.0
39
PERFORMANCE DATA (cont)
COMBINATION RATINGS
UNIT 566D150
566D150/524A-C150 WITH HIGH CAPACITY 4-ROW COIL
Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
3750
6250
57
62
67
72
57
62
67
72
57
62
67
72
TC
133.0
133.0
9.00
131.0
131.0
9.44
139.0
123.0
9.07
136.0
122.0
9.54
151.0
103.0
9.27
148.0
102.0
9.75
165.0
83.1
9.48
161.0
81.9
9.99
146.0
146.0
9.18
143.0
143.0
9.66
147.0
142.0
9.20
144.0
140.0
9.69
158.0
119.0
9.38
155.0
117.0
9.88
172.0
92.7
9.59
169.0
91.3
10.10
154.0
154.0
9.32
152.0
152.0
9.82
154.0
154.0
9.32
151.0
151.0
9.81
163.0
133.0
9.45
160.0
131.0
9.96
177.0
101.0
9.66
173.0
100.0
10.20
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
126.0
126.0
10.40
130.0
119.0
10.50
142.0
99.5
10.70
155.0
79.3
11.00
138.0
138.0
10.60
138.0
137.0
10.60
148.0
115.0
10.90
161.0
88.8
11.20
146.0
146.0
10.80
146.0
146.0
10.80
153.0
128.0
11.00
165.0
97.5
11.30
95
TC
123.0
123.0
10.80
121.0
121.0
11.30
116.0
116.0
12.20
127.0
117.0
10.90
124.0
116.0
11.40
118.0
113.0
12.30
138.0
98.2
151.0
78.0
135.0
135.0
11.10
132.0
132.0
11.60
127.0
127.0
12.50
135.0
134.0
11.10
132.0
132.0
11.60
127.0
127.0
12.50
145.0
113.0
11.30
141.0
112.0
11.80
134.0
109.0
12.80
157.0
87.5
143.0
143.0
11.30
140.0
140.0
11.80
134.0
134.0
12.80
143.0
143.0
11.30
140.0
140.0
11.80
134.0
134.0
12.80
149.0
127.0
11.50
145.0
125.0
12.00
138.0
122.0
12.90
161.0
96.2
100
105
115
SHC
kW
11.20
11.50
11.70
11.80
TC
SHC
kW
TC
SHC
kW
135.0
96.8
11.70
129.0
94.1
12.60
148.0
76.8
12.00
141.0
74.2
13.00
154.0
86.1
12.20
146.0
83.5
13.20
157.0
94.8
12.30
149.0
92.2
13.30
566D150/524A-B150 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
3750
5000
6250
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
127.0
127.0
8.93
125.0
125.0
9.37
134.0
118.0
9.01
131.0
117.0
9.45
146.0
99.4
9.19
143.0
98.2
9.67
160.0
80.2
9.40
156.0
78.9
9.90
140.0
140.0
9.09
137.0
137.0
9.55
142.0
136.0
9.12
139.0
134.0
9.58
153.0
114.0
9.31
150.0
112.0
9.79
167.0
89.0
9.51
163.0
87.6
10.00
148.0
148.0
9.22
145.0
145.0
9.70
148.0
148.0
9.22
145.0
145.0
9.71
158.0
126.0
9.37
154.0
125.0
9.87
172.0
96.9
9.58
168.0
95.6
10.10
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
121.0
121.0
10.30
125.0
114.0
10.30
137.0
95.6
10.60
150.0
76.4
10.90
132.0
132.0
10.50
133.0
130.0
10.50
143.0
110.0
10.70
156.0
85.1
11.00
140.0
140.0
10.70
140.0
140.0
10.70
147.0
122.0
10.80
160.0
93.0
11.10
95
TC
118.0
118.0
10.70
116.0
116.0
11.20
111.0
111.0
12.00
122.0
112.0
10.80
119.0
111.0
11.20
113.0
108.0
12.10
134.0
94.3
146.0
75.2
129.0
129.0
11.00
127.0
127.0
11.40
121.0
121.0
12.40
130.0
128.0
11.00
127.0
126.0
11.40
121.0
121.0
12.40
140.0
108.0
11.20
136.0
107.0
11.70
129.0
104.0
12.60
152.0
83.8
137.0
137.0
11.20
134.0
134.0
11.60
128.0
128.0
12.60
137.0
137.0
11.20
134.0
134.0
11.60
128.0
128.0
12.60
144.0
121.0
11.30
140.0
119.0
11.80
133.0
116.0
12.80
156.0
91.7
100
105
115
SHC
kW
11.10
11.40
11.60
11.70
TC
SHC
kW
TC
SHC
kW
131.0
92.9
11.50
124.0
90.3
12.50
143.0
73.9
11.90
136.0
71.4
12.90
149.0
82.5
12.10
141.0
79.9
13.10
153.0
90.4
12.20
145.0
87.8
13.20
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
40
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566D150 (cont)
566D150/524A-C180 WITH HIGH CAPACITY 4-ROW COIL
Evaporator Air — Cfm
6000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
4500
7500
57
62
67
72
57
62
67
72
57
62
67
72
TC
142.0
142.0
9.13
140.0
140.0
9.60
145.0
136.0
9.17
142.0
134.0
9.65
157.0
114.0
9.37
154.0
112.0
9.86
171.0
89.6
9.57
168.0
88.3
10.10
154.0
154.0
9.31
151.0
151.0
9.81
154.0
154.0
9.32
151.0
151.0
9.81
164.0
131.0
9.47
160.0
129.0
9.97
178.0
100.0
9.66
174.0
99.1
10.20
163.0
163.0
9.44
160.0
160.0
9.96
163.0
163.0
9.45
160.0
160.0
9.96
168.0
146.0
9.53
165.0
145.0
10.00
182.0
110.0
9.72
178.0
109.0
10.30
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
134.0
134.0
10.50
136.0
131.0
10.60
147.0
109.0
10.80
160.0
85.7
11.20
146.0
146.0
10.80
146.0
146.0
10.80
153.0
127.0
11.00
166.0
96.4
11.30
153.0
153.0
11.00
153.0
153.0
11.00
157.0
142.0
11.10
170.0
106.0
11.40
95
TC
132.0
132.0
11.00
129.0
129.0
11.50
124.0
124.0
12.40
133.0
129.0
11.10
130.0
127.0
11.50
124.0
123.0
12.50
144.0
108.0
11.30
140.0
107.0
11.80
133.0
104.0
12.80
157.0
84.4
143.0
143.0
11.30
140.0
140.0
11.80
134.0
134.0
12.80
143.0
143.0
11.30
140.0
140.0
11.80
134.0
134.0
12.80
150.0
125.0
11.50
146.0
124.0
12.00
139.0
121.0
13.00
162.0
95.1
150.0
150.0
11.50
147.0
147.0
12.00
140.0
140.0
13.00
150.0
150.0
11.50
147.0
147.0
12.00
140.0
140.0
13.00
154.0
140.0
11.60
150.0
138.0
12.10
142.0
135.0
13.10
166.0
105.0
11.90
162.0
104.0
12.40
153.0
101.0
13.50
100
105
115
SHC
kW
11.70
11.80
TC
SHC
kW
TC
SHC
kW
153.0
83.1
12.20
146.0
80.5
13.20
158.0
93.8
12.30
150.0
91.0
13.40
566D150/524A-B180 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
4500
6000
7500
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
140.0
140.0
9.09
137.0
137.0
9.56
144.0
134.0
9.14
140.0
132.0
9.61
156.0
112.0
9.34
152.0
110.0
9.84
170.0
88.3
9.55
166.0
87.0
10.10
152.0
152.0
9.28
149.0
149.0
9.78
152.0
152.0
9.28
149.0
149.0
9.77
162.0
128.0
9.44
159.0
127.0
9.94
176.0
98.7
9.65
172.0
97.3
10.20
160.0
160.0
9.41
157.0
157.0
9.92
160.0
160.0
9.41
157.0
157.0
9.92
167.0
143.0
9.51
163.0
142.0
10.00
181.0
108.0
9.71
176.0
107.0
10.20
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
132.0
132.0
10.50
134.0
129.0
10.50
146.0
107.0
10.80
159.0
84.4
11.10
143.0
143.0
10.70
143.0
143.0
10.70
151.0
124.0
10.90
165.0
94.6
11.20
151.0
151.0
10.90
151.0
151.0
10.90
155.0
138.0
11.00
168.0
104.0
11.30
95
TC
130.0
130.0
11.00
127.0
127.0
11.40
121.0
121.0
12.40
131.0
127.0
11.00
128.0
125.0
11.50
122.0
121.0
12.40
142.0
106.0
11.30
139.0
105.0
11.80
131.0
102.0
12.70
155.0
83.1
140.0
140.0
11.30
137.0
137.0
11.70
131.0
131.0
12.70
140.0
140.0
11.20
137.0
137.0
11.70
131.0
131.0
12.70
148.0
123.0
11.40
144.0
12.01
11.90
136.0
118.0
12.90
161.0
93.3
148.0
148.0
11.40
145.0
145.0
11.90
138.0
138.0
12.90
148.0
148.0
11.40
145.0
145.0
11.90
138.0
138.0
12.90
152.0
137.0
11.50
148.0
135.0
12.00
140.0
132.0
13.00
164.0
103.0
11.80
160.0
101.0
12.40
152.0
98.7
13.40
100
105
115
SHC
kW
11.60
11.80
TC
SHC
kW
TC
SHC
kW
151.0
81.7
12.10
144.0
79.0
13.10
157.0
91.9
12.30
148.0
89.2
13.30
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
41
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566D180
566D180/524A-C180 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air — Cfm
6000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
4500
7500
57
62
67
72
57
62
67
72
57
62
67
72
TC
167.0
167.0
13.10
165.0
165.0
13.70
177.0
152.0
13.40
174.0
150.0
14.00
192.0
128.0
13.90
189.0
127.0
14.50
209.0
104.0
14.40
205.0
102.0
15.00
183.0
183.0
13.60
180.0
180.0
14.20
187.0
175.0
13.70
184.0
174.0
14.30
202.0
146.0
14.10
198.0
145.0
14.80
219.0
115.0
14.70
214.0
113.0
15.30
194.0
194.0
13.90
191.0
191.0
14.60
195.0
193.0
13.90
192.0
191.0
14.60
208.0
163.0
14.30
204.0
161.0
15.00
225.0
125.0
14.80
220.0
124.0
15.50
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
160.0
160.0
14.90
167.0
147.0
15.20
182.0
123.0
15.70
197.0
99.3
16.40
174.0
174.0
15.50
177.0
170.0
15.60
190.0
141.0
16.10
206.0
110.0
16.70
185.0
185.0
15.90
185.0
185.0
15.90
196.0
158.0
16.30
211.0
120.0
16.90
95
TC
157.0
157.0
15.50
154.0
154.0
16.00
148.0
148.0
17.30
164.0
145.0
15.80
160.0
144.0
16.30
153.0
140.0
17.50
178.0
122.0
16.40
174.0
120.0
17.00
166.0
117.0
18.20
193.0
97.8
171.0
171.0
16.10
168.0
168.0
16.70
162.0
162.0
18.00
173.0
168.0
16.20
169.0
165.0
16.80
162.0
161.0
18.00
186.0
140.0
16.70
182.0
138.0
17.40
174.0
135.0
18.60
202.0
109.0
17.40
197.0
107.0
18.10
188.0
104.0
19.40
181.0
181.0
16.50
178.0
178.0
17.20
171.0
171.0
18.50
181.0
181.0
16.50
178.0
178.0
17.20
171.0
171.0
18.50
191.0
156.0
17.00
187.0
154.0
17.60
178.0
151.0
18.90
207.0
119.0
17.60
202.0
117.0
18.30
193.0
114.0
19.70
100
105
115
SHC
kW
17.00
TC
SHC
kW
TC
SHC
kW
189.0
96.3
17.70
181.0
93.2
19.00
566D180/524A-B180 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
4500
6000
7500
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
165.0
165.0
13.00
162.0
162.0
13.60
175.0
149.0
13.30
171.0
148.0
13.90
190.0
126.0
13.80
187.0
125.0
14.40
207.0
102.0
14.30
203.0
101.0
15.00
180.0
180.0
13.50
177.0
177.0
14.10
185.0
172.0
13.60
181.0
170.0
14.20
200.0
143.0
14.10
196.0
142.0
14.70
217.0
113.0
14.60
213.0
112.0
15.30
191.0
191.0
13.80
188.0
188.0
14.50
193.0
190.0
13.90
189.0
187.0
14.50
206.0
159.0
14.30
202.0
158.0
14.90
223.0
123.0
14.80
218.0
121.0
15.50
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
157.0
157.0
14.80
165.0
144.0
15.10
179.0
121.0
15.70
195.0
97.9
16.30
171.0
171.0
15.30
174.0
166.0
15.50
188.0
139.0
16.00
204.0
108.0
16.60
182.0
182.0
15.80
182.0
181.0
15.80
193.0
154.0
16.20
209.0
118.0
16.90
95
TC
154.0
154.0
15.30
151.0
151.0
15.90
146.0
146.0
17.10
161.0
143.0
15.70
158.0
141.0
16.20
151.0
137.0
17.40
176.0
120.0
16.30
172.0
118.0
16.90
164.0
115.0
18.10
191.0
96.3
168.0
168.0
16.00
165.0
165.0
16.60
159.0
159.0
17.80
170.0
164.0
16.10
167.0
162.0
16.70
160.0
157.0
17.90
184.0
137.0
16.70
180.0
135.0
17.30
171.0
132.0
18.50
199.0
107.0
17.30
195.0
105.0
18.00
186.0
102.0
19.30
178.0
178.0
16.40
175.0
175.0
17.00
168.0
168.0
18.30
178.0
178.0
16.40
175.0
175.0
17.00
168.0
168.0
18.30
189.0
153.0
16.90
185.0
151.0
17.50
176.0
147.0
18.80
205.0
117.0
17.50
200.0
115.0
18.20
191.0
112.0
19.50
100
105
115
SHC
kW
17.00
TC
SHC
kW
TC
SHC
kW
187.0
94.8
17.60
179.0
91.7
18.90
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
42
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566D180 (cont)
566D180/524A-C240 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air — Cfm
8,000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
6,000
10,000
57
62
67
72
57
62
67
72
57
62
67
72
TC
196.0
196.0
13.90
193.0
193.0
14.60
200.0
188.0
14.00
196.0
186.0
14.70
215.0
156.0
14.50
211.0
154.0
15.20
234.0
123.0
15.00
229.0
121.0
15.70
212.0
212.0
14.40
209.0
209.0
15.10
212.0
212.0
14.40
209.0
209.0
15.10
224.0
181.0
14.70
220.0
179.0
15.40
242.0
138.0
15.20
237.0
136.0
16.00
223.0
223.0
14.70
219.0
219.0
15.40
224.0
224.0
14.70
220.0
220.0
15.40
230.0
203.0
14.90
225.0
201.0
15.60
247.0
152.0
15.30
242.0
151.0
16.10
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
186.0
186.0
15.90
188.0
182.0
16.00
203.0
151.0
16.50
219.0
118.0
17.10
201.0
201.0
16.50
201.0
201.0
16.50
210.0
175.0
16.80
227.0
133.0
17.40
211.0
211.0
16.80
211.0
211.0
16.80
216.0
197.0
17.00
231.0
147.0
17.60
95
TC
183.0
183.0
16.50
179.0
179.0
17.20
172.0
172.0
18.50
184.0
179.0
16.60
180.0
177.0
17.20
172.0
172.0
18.50
198.0
149.0
17.20
193.0
147.0
17.80
184.0
144.0
19.10
215.0
116.0
17.90
210.0
114.0
18.60
200.0
111.0
20.00
197.0
197.0
17.20
193.0
193.0
17.80
185.0
185.0
19.20
197.0
197.0
17.10
193.0
193.0
17.80
185.0
185.0
19.20
205.0
173.0
17.50
201.0
171.0
18.20
191.0
168.0
19.50
222.0
131.0
18.10
216.0
129.0
18.90
206.0
126.0
20.30
207.0
207.0
17.60
203.0
203.0
18.30
194.0
194.0
19.70
207.0
207.0
17.50
203.0
203.0
18.30
194.0
194.0
19.70
211.0
195.0
17.70
206.0
192.0
18.40
196.0
188.0
19.80
226.0
146.0
18.30
221.0
144.0
19.00
210.0
140.0
20.50
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
566D180/524A-B240 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
6,000
8,000
10,000
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
186.0
186.0
13.70
183.0
183.0
14.30
190.0
178.0
13.80
186.0
176.0
14.40
205.0
148.0
14.20
200.0
147.0
14.90
222.0
117.0
14.70
217.0
115.0
15.40
201.0
201.0
14.10
197.0
197.0
14.80
201.0
201.0
14.10
197.0
197.0
14.80
212.0
171.0
14.50
208.0
169.0
15.10
230.0
130.0
15.00
225.0
129.0
15.70
211.0
211.0
14.40
207.0
207.0
15.10
211.0
211.0
14.40
207.0
207.0
15.10
218.0
190.0
14.60
213.0
188.0
15.30
235.0
143.0
15.10
230.0
142.0
15.80
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
176.0
176.0
15.50
179.0
172.0
15.60
192.0
143.0
16.20
208.0
112.0
16.80
190.0
190.0
16.10
190.0
190.0
16.10
199.0
165.0
16.50
215.0
125.0
17.10
199.0
199.0
16.50
199.0
199.0
16.50
204.0
184.0
16.70
220.0
138.0
17.30
95
TC
173.0
173.0
16.20
170.0
170.0
16.80
163.0
163.0
18.10
175.0
170.0
16.20
171.0
167.0
16.90
164.0
163.0
18.10
188.0
142.0
16.80
184.0
140.0
17.50
175.0
136.0
18.70
204.0
110.0
17.50
199.0
108.0
18.20
190.0
105.0
19.50
186.0
186.0
16.80
183.0
183.0
17.40
175.0
175.0
18.70
186.0
186.0
16.70
183.0
183.0
17.40
175.0
175.0
18.70
195.0
163.0
17.10
190.0
162.0
17.80
181.0
158.0
19.10
211.0
124.0
17.80
206.0
122.0
18.50
196.0
119.0
19.80
195.0
195.0
17.10
191.0
191.0
17.80
183.0
183.0
19.20
195.0
195.0
17.10
191.0
191.0
17.80
183.0
183.0
19.10
200.0
182.0
17.30
195.0
180.0
18.00
186.0
175.0
19.30
215.0
137.0
18.00
210.0
135.0
18.70
199.0
132.0
20.00
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
43
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566D240
566D240/524A-C300 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air — Cfm
10,000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
7,500
12,500
57
62
67
72
57
62
67
72
57
62
67
72
TC
244.0
244.0
18.90
239.0
239.0
19.70
249.0
233.0
19.20
244.0
231.0
19.90
268.0
194.0
19.90
263.0
192.0
20.70
291.0
152.0
20.80
284.0
150.0
21.60
264.0
264.0
19.70
259.0
259.0
20.50
264.0
264.0
19.70
259.0
259.0
20.50
279.0
224.0
20.30
273.0
222.0
21.10
301.0
171.0
21.20
294.0
169.0
22.00
278.0
278.0
20.30
272.0
272.0
21.10
278.0
278.0
20.30
272.0
272.0
21.10
286.0
252.0
20.60
280.0
249.0
21.40
307.0
189.0
21.40
300.0
187.0
22.30
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
230.0
230.0
21.30
233.0
225.0
21.40
251.0
187.0
22.20
272.0
146.0
23.20
249.0
249.0
22.10
249.0
249.0
22.10
260.0
217.0
22.70
281.0
164.0
23.70
261.0
261.0
22.70
261.0
261.0
22.70
267.0
243.0
23.00
286.0
182.0
23.90
95
TC
226.0
226.0
22.00
221.0
221.0
22.80
212.0
212.0
24.30
228.0
222.0
22.10
222.0
219.0
22.80
212.0
211.0
24.30
245.0
184.0
23.00
239.0
182.0
23.70
226.0
177.0
25.20
265.0
143.0
24.00
259.0
141.0
24.80
245.0
136.0
26.40
244.0
244.0
22.90
238.0
238.0
23.70
227.0
227.0
25.30
244.0
244.0
22.90
238.0
238.0
23.70
227.0
227.0
25.30
254.0
214.0
23.50
247.0
212.0
24.20
235.0
206.0
25.80
274.0
162.0
24.50
267.0
160.0
25.30
253.0
155.0
26.90
256.0
256.0
23.60
250.0
250.0
24.40
238.0
238.0
26.00
256.0
256.0
23.60
250.0
250.0
24.40
238.0
238.0
26.00
260.0
240.0
23.80
254.0
237.0
24.60
240.0
231.0
26.10
279.0
180.0
24.80
272.0
177.0
25.60
257.0
172.0
27.20
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
566D240/524A-B300 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
10,000
Evaporator Air — Ewb (F)
7,500
12,500
Air Entering
Condenser
(Edb)
57
62
67
72
57
62
67
72
57
62
67
72
TC
230.0
230.0
18.40
226.0
226.0
19.20
236.0
219.0
18.60
231.0
217.0
19.40
255.0
183.0
19.40
250.0
181.0
20.20
277.0
144.0
20.20
271.0
142.0
21.00
249.0
249.0
19.10
244.0
244.0
19.90
249.0
248.0
19.20
244.0
244.0
19.90
266.0
209.0
19.80
259.0
207.0
20.60
287.0
161.0
20.60
281.0
159.0
21.50
262.0
262.0
19.60
256.0
256.0
20.40
262.0
262.0
19.60
256.0
256.0
20.40
272.0
233.0
20.10
266.0
231.0
20.80
293.0
176.0
20.90
287.0
174.0
21.70
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
218.0
218.0
20.60
221.0
211.0
20.80
239.0
176.0
21.70
259.0
138.0
22.60
235.0
235.0
21.50
235.0
235.0
21.50
248.0
203.0
22.10
268.0
154.0
23.10
246.0
246.0
22.00
246.0
246.0
22.00
254.0
226.0
22.40
273.0
169.0
23.30
95
TC
214.0
214.0
21.40
209.0
209.0
22.10
201.0
201.0
23.60
217.0
208.0
21.50
212.0
206.0
22.20
202.0
199.0
23.70
233.0
174.0
22.40
228.0
172.0
23.10
216.0
167.0
24.60
253.0
136.0
23.40
247.0
133.0
24.20
235.0
129.0
25.80
230.0
230.0
22.20
225.0
225.0
23.00
215.0
215.0
24.60
230.0
230.0
22.20
225.0
225.0
23.00
215.0
215.0
24.50
242.0
200.0
22.90
236.0
198.0
23.60
224.0
193.0
25.10
261.0
152.0
23.80
255.0
150.0
24.60
242.0
145.0
26.20
241.0
241.0
22.80
236.0
236.0
23.60
226.0
226.0
25.20
241.0
241.0
22.80
236.0
236.0
23.60
226.0
226.0
25.20
248.0
223.0
23.20
242.0
220.0
23.90
229.0
214.0
25.40
266.0
167.0
24.10
260.0
165.0
24.90
246.0
160.0
26.50
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
44
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E150
566E150/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air — Cfm
4000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
3000
5000
57
62
67
72
57
62
67
72
57
62
67
72
TC
126.0
126.0
9.13
125.0
125.0
9.68
135.0
112.0
9.18
133.0
111.0
9.72
148.0
95.4
9.22
146.0
94.5
9.79
161.0
78.5
9.31
159.0
77.5
9.87
140.0
140.0
9.19
138.0
138.0
9.74
144.0
130.0
9.20
142.0
129.0
9.77
156.0
109.0
9.26
154.0
108.0
9.82
170.0
87.0
9.37
168.0
86.0
9.92
149.0
149.0
9.22
147.0
147.0
9.78
151.0
146.0
9.23
148.0
144.0
9.80
162.0
122.0
9.30
159.0
121.0
9.85
176.0
94.8
9.43
173.0
93.8
9.98
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
121.0
121.0
10.90
129.0
109.0
11.00
141.0
92.4
11.00
154.0
75.6
11.10
134.0
134.0
11.00
137.0
127.0
11.00
149.0
106.0
11.00
162.0
84.0
11.10
143.0
143.0
11.00
144.0
141.0
11.00
154.0
118.0
11.10
167.0
91.8
11.20
95
TC
119.0
119.0
11.60
118.0
118.0
12.30
114.0
114.0
13.70
127.0
108.0
11.60
124.0
107.0
12.30
120.0
104.0
13.80
138.0
91.4
151.0
74.6
132.0
132.0
11.60
130.0
130.0
12.30
126.0
126.0
13.80
135.0
126.0
11.60
132.0
124.0
12.30
127.0
122.0
13.80
146.0
105.0
11.70
143.0
104.0
12.40
137.0
101.0
13.80
159.0
82.9
141.0
141.0
11.60
138.0
138.0
12.30
134.0
134.0
13.80
141.0
140.0
11.70
139.0
138.0
12.40
134.0
134.0
13.80
151.0
117.0
11.70
148.0
116.0
12.40
142.0
114.0
13.90
164.0
90.7
100
105
115
SHC
kW
11.70
11.70
11.80
11.80
TC
SHC
kW
TC
SHC
kW
136.0
90.3
12.40
131.0
88.0
13.80
149.0
73.5
12.40
143.0
71.4
13.90
156.0
81.9
12.50
150.0
79.6
13.90
161.0
89.6
12.50
154.0
87.4
14.00
566E150/524A-B120 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
3000
4000
5000
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
119.0
119.0
9.09
118.0
118.0
9.66
128.0
106.0
9.15
126.0
105.0
9.72
140.0
90.4
9.18
138.0
89.5
9.75
153.0
74.3
9.23
151.0
73.4
9.81
131.0
131.0
9.15
130.0
130.0
9.72
136.0
122.0
9.16
134.0
121.0
9.72
148.0
103.0
9.21
146.0
102.0
9.77
161.0
82.0
9.30
159.0
81.2
9.87
140.0
140.0
9.19
138.0
138.0
9.75
142.0
136.0
9.19
140.0
135.0
9.75
153.0
114.0
9.25
151.0
113.0
9.80
166.0
89.0
9.33
164.0
88.1
9.89
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
115.0
115.0
10.90
122.0
103.0
10.90
134.0
87.7
11.00
146.0
71.7
11.00
126.0
126.0
10.90
130.0
119.0
10.90
141.0
99.9
11.00
154.0
79.3
11.10
134.0
134.0
11.00
136.0
132.0
11.00
146.0
111.0
11.00
158.0
86.3
11.10
95
TC
113.0
113.0
11.60
111.0
111.0
12.20
108.0
108.0
13.70
120.0
102.0
11.60
118.0
101.0
12.30
114.0
99.0
13.70
131.0
86.7
144.0
70.8
124.0
124.0
11.60
122.0
122.0
12.30
118.0
118.0
13.70
128.0
118.0
11.60
125.0
117.0
12.30
121.0
114.0
13.80
139.0
98.9
151.0
78.4
132.0
132.0
11.60
130.0
130.0
12.30
126.0
126.0
13.80
133.0
131.0
11.60
131.0
129.0
12.30
126.0
126.0
13.80
143.0
110.0
11.70
140.0
109.0
12.40
135.0
107.0
13.80
156.0
85.3
100
105
115
SHC
kW
11.60
11.70
11.60
11.70
11.80
TC
SHC
kW
TC
SHC
kW
129.0
85.7
12.30
124.0
83.7
13.80
141.0
69.8
12.40
136.0
67.8
13.90
136.0
97.9
12.30
131.0
95.8
13.80
148.0
77.5
12.40
143.0
75.4
13.90
153.0
84.3
12.40
147.0
82.3
13.90
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
45
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E150 (cont)
566E150/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
3750
6250
57
62
67
72
57
62
67
72
57
62
67
72
TC
139.0
139.0
9.18
137.0
137.0
9.74
145.0
127.0
9.21
143.0
126.0
9.76
158.0
107.0
9.27
155.0
106.0
9.84
172.0
86.2
9.38
169.0
85.3
9.95
152.0
152.0
9.25
150.0
150.0
9.80
154.0
148.0
9.24
151.0
146.0
9.82
165.0
123.0
9.33
163.0
122.0
9.90
180.0
96.1
9.48
177.0
95.1
10.00
161.0
161.0
9.29
159.0
159.0
9.86
161.0
161.0
9.31
159.0
159.0
9.87
170.0
138.0
9.37
168.0
137.0
9.93
185.0
105.0
9.54
182.0
104.0
10.10
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
133.0
133.0
11.00
138.0
124.0
11.00
150.0
104.0
11.10
164.0
83.3
11.20
146.0
146.0
11.00
147.0
144.0
11.00
157.0
120.0
11.10
171.0
93.1
11.20
154.0
154.0
11.10
154.0
154.0
11.10
162.0
134.0
11.10
175.0
102.0
11.30
95
TC
131.0
131.0
11.60
129.0
129.0
12.30
125.0
125.0
13.80
136.0
123.0
11.60
133.0
121.0
12.30
128.0
119.0
13.80
148.0
103.0
11.70
145.0
102.0
12.40
139.0
99.4
13.90
161.0
82.2
143.0
143.0
11.70
141.0
141.0
12.40
136.0
136.0
13.80
144.0
142.0
11.70
142.0
140.0
12.40
136.0
136.0
13.90
154.0
119.0
11.80
152.0
118.0
12.50
145.0
115.0
13.90
168.0
92.1
152.0
152.0
11.70
149.0
149.0
12.40
144.0
144.0
13.90
152.0
152.0
11.70
149.0
149.0
12.40
144.0
144.0
13.90
159.0
133.0
11.80
156.0
132.0
12.50
150.0
129.0
13.90
172.0
101.0
11.90
169.0
100.0
12.60
162.0
97.9
14.10
100
105
115
SHC
kW
11.80
11.90
TC
SHC
kW
TC
SHC
kW
158.0
81.1
12.50
152.0
78.9
14.00
165.0
90.9
12.60
158.0
88.7
14.00
566E150/524A-B150 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
3750
5000
6250
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
130.0
130.0
9.14
129.0
129.0
9.70
137.0
120.0
9.18
135.0
119.0
9.73
150.0
101.0
9.22
147.0
100.0
9.78
163.0
81.6
9.32
161.0
80.7
9.88
143.0
143.0
9.20
141.0
141.0
9.76
145.0
138.0
9.20
143.0
137.0
9.76
157.0
115.0
9.27
154.0
114.0
9.82
171.0
90.5
9.38
168.0
89.5
9.93
151.0
151.0
9.24
149.0
149.0
9.79
151.0
151.0
9.23
149.0
149.0
9.79
162.0
128.0
9.30
159.0
127.0
9.85
176.0
98.5
9.43
173.0
97.5
9.98
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
125.0
125.0
10.90
131.0
117.0
11.00
143.0
98.0
11.00
156.0
78.7
11.10
137.0
137.0
11.00
138.0
134.0
11.00
149.0
112.0
11.00
162.0
87.5
11.10
145.0
145.0
11.00
145.0
145.0
11.00
154.0
125.0
11.10
167.0
95.6
11.20
95
TC
123.0
123.0
11.60
122.0
122.0
12.30
118.0
118.0
13.80
128.0
115.0
11.60
126.0
114.0
12.30
121.0
112.0
13.80
140.0
97.0
153.0
77.7
135.0
135.0
11.60
132.0
132.0
12.30
128.0
128.0
13.80
136.0
132.0
11.70
133.0
131.0
12.30
128.0
128.0
13.80
146.0
111.0
11.70
144.0
110.0
12.40
138.0
108.0
13.90
160.0
86.5
143.0
143.0
11.70
140.0
140.0
12.30
135.0
135.0
13.80
143.0
143.0
11.70
140.0
140.0
12.40
135.0
135.0
13.80
151.0
124.0
11.70
148.0
123.0
12.40
142.0
120.0
13.90
164.0
94.5
100
105
115
SHC
kW
11.70
11.70
11.80
11.80
TC
SHC
kW
TC
SHC
kW
137.0
95.9
12.30
132.0
93.6
13.80
150.0
76.7
12.40
144.0
74.5
13.90
157.0
85.4
12.50
150.0
83.3
14.00
161.0
93.5
12.50
154.0
91.3
14.00
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
46
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E150 (cont)
566E150/524A-C180 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air — Cfm
6000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
4500
7500
57
62
67
72
57
62
67
72
57
62
67
72
TC
152.0
152.0
9.24
150.0
150.0
9.80
156.0
145.0
9.26
154.0
144.0
9.82
169.0
121.0
9.35
166.0
120.0
9.92
183.0
95.4
9.53
181.0
94.4
10.10
166.0
166.0
9.33
164.0
164.0
9.89
166.0
166.0
9.33
164.0
164.0
9.89
176.0
140.0
9.43
173.0
139.0
9.99
190.0
107.0
9.63
187.0
106.0
10.20
175.0
175.0
9.42
173.0
173.0
9.98
175.0
175.0
9.43
173.0
173.0
9.99
181.0
157.0
9.49
178.0
156.0
10.00
195.0
119.0
9.69
191.0
118.0
10.20
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
146.0
146.0
11.00
148.0
141.0
11.10
161.0
117.0
11.10
175.0
92.2
11.30
159.0
159.0
11.10
159.0
159.0
11.10
167.0
136.0
11.20
181.0
104.0
11.40
167.0
167.0
11.20
167.0
167.0
11.20
172.0
154.0
11.20
185.0
115.0
11.40
95
TC
144.0
144.0
11.70
141.0
141.0
12.40
137.0
137.0
13.90
146.0
140.0
11.70
143.0
138.0
12.40
138.0
135.0
13.90
158.0
116.0
11.80
155.0
115.0
12.50
148.0
112.0
13.90
171.0
91.1
156.0
156.0
11.80
154.0
154.0
12.50
148.0
148.0
13.90
156.0
156.0
11.80
154.0
154.0
12.50
148.0
148.0
14.00
164.0
135.0
11.90
161.0
134.0
12.50
154.0
131.0
14.00
178.0
103.0
12.00
174.0
102.0
12.70
167.0
99.5
14.20
165.0
165.0
11.80
162.0
162.0
12.50
156.0
156.0
14.00
165.0
165.0
11.90
162.0
162.0
12.50
156.0
156.0
14.00
169.0
152.0
11.90
165.0
151.0
12.60
159.0
148.0
14.00
181.0
114.0
12.10
178.0
113.0
12.80
170.0
111.0
14.20
100
105
115
SHC
kW
11.90
TC
SHC
kW
TC
SHC
kW
168.0
90.0
12.60
162.0
87.6
14.10
566E150/524A-B180 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
4500
6000
7500
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
143.0
143.0
9.19
141.0
141.0
9.75
147.0
136.0
9.22
145.0
134.0
9.77
160.0
113.0
9.28
157.0
112.0
9.85
174.0
89.9
9.42
171.0
89.0
9.98
155.0
155.0
9.27
153.0
153.0
9.82
156.0
155.0
9.26
153.0
153.0
9.82
166.0
130.0
9.34
164.0
129.0
9.90
180.0
100.0
9.49
178.0
99.5
10.00
164.0
164.0
9.31
162.0
162.0
9.87
164.0
164.0
9.33
162.0
162.0
9.89
171.0
146.0
9.37
168.0
144.0
9.93
185.0
110.0
9.54
182.0
109.0
10.10
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
137.0
137.0
11.00
140.0
132.0
11.00
152.0
110.0
11.10
165.0
86.9
11.20
149.0
149.0
11.00
149.0
149.0
11.00
158.0
127.0
11.10
172.0
97.4
11.20
157.0
157.0
11.10
157.0
157.0
11.10
162.0
142.0
11.10
175.0
107.0
11.30
95
TC
135.0
135.0
11.60
133.0
133.0
12.30
129.0
129.0
13.80
138.0
131.0
11.60
135.0
129.0
12.30
130.0
126.0
13.80
149.0
109.0
11.70
146.0
108.0
12.40
140.0
106.0
13.90
162.0
85.8
146.0
146.0
11.70
144.0
144.0
12.40
139.0
139.0
13.90
146.0
146.0
11.70
144.0
144.0
12.40
139.0
139.0
13.90
155.0
126.0
11.80
152.0
125.0
12.50
146.0
122.0
13.90
168.0
96.3
154.0
154.0
11.70
152.0
152.0
12.40
146.0
146.0
13.90
154.0
154.0
11.80
152.0
152.0
12.50
146.0
146.0
13.90
159.0
141.0
11.80
156.0
139.0
12.50
150.0
137.0
13.90
172.0
106.0
11.90
169.0
105.0
12.60
162.0
103.0
14.10
100
105
115
SHC
kW
11.80
11.90
TC
SHC
kW
TC
SHC
kW
159.0
84.7
12.50
153.0
82.5
14.00
165.0
95.2
12.60
158.0
92.9
14.10
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
47
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E180
566E180/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
3750
6250
57
62
67
72
57
62
67
72
57
62
67
72
TC
163.0
161.0
12.60
160.0
159.0
13.10
175.0
142.0
12.80
172.0
141.0
13.40
190.0
121.0
13.20
187.0
120.0
13.80
206.0
99.8
179.0
179.0
12.90
176.0
176.0
13.50
186.0
164.0
13.10
183.0
163.0
13.70
201.0
138.0
13.40
198.0
136.0
14.00
217.0
110.0
13.80
214.0
109.0
14.40
191.0
191.0
13.20
188.0
188.0
13.80
194.0
184.0
13.30
190.0
182.0
13.80
208.0
153.0
13.60
204.0
151.0
14.20
224.0
119.0
14.00
220.0
118.0
14.60
80
85
SHC
kW
13.60
TC
SHC
kW
203.0
98.5
14.20
TC
SHC
kW
155.0
155.0
14.30
166.0
138.0
14.60
180.0
117.0
15.00
196.0
95.6
15.40
170.0
170.0
14.70
176.0
159.0
14.80
190.0
133.0
15.20
206.0
106.0
15.70
181.0
181.0
15.00
183.0
178.0
15.00
196.0
148.0
15.40
212.0
115.0
15.80
95
TC
152.0
152.0
14.90
150.0
150.0
15.60
144.0
144.0
16.90
163.0
136.0
15.20
159.0
134.0
15.80
152.0
131.0
17.10
177.0
115.0
15.60
173.0
114.0
16.20
165.0
110.0
17.50
192.0
94.0
167.0
167.0
15.30
164.0
164.0
16.00
158.0
158.0
17.30
172.0
158.0
15.50
168.0
156.0
16.10
161.0
152.0
17.40
186.0
131.0
15.80
182.0
130.0
16.50
173.0
126.0
17.80
201.0
104.0
16.30
197.0
102.0
16.90
188.0
99.0
18.20
178.0
178.0
15.60
175.0
175.0
16.30
168.0
168.0
17.60
180.0
176.0
15.60
176.0
173.0
16.30
168.0
167.0
17.60
192.0
146.0
16.00
188.0
145.0
16.60
178.0
141.0
17.90
208.0
113.0
16.50
203.0
112.0
17.10
193.0
108.0
18.40
100
105
115
SHC
kW
16.00
TC
SHC
kW
TC
SHC
kW
188.0
92.4
16.60
179.0
89.1
18.00
566E180/524A-B150 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
3750
5000
6250
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
154.0
152.0
12.40
152.0
150.0
12.90
166.0
134.0
12.60
163.0
133.0
13.20
181.0
115.0
13.00
178.0
113.0
13.50
196.0
94.7
168.0
168.0
12.70
166.0
166.0
13.20
176.0
154.0
12.90
173.0
153.0
13.40
191.0
129.0
13.20
188.0
128.0
13.80
206.0
104.0
13.60
203.0
102.0
14.20
179.0
179.0
12.90
176.0
176.0
13.50
183.0
171.0
13.00
180.0
169.0
13.60
197.0
143.0
13.40
194.0
141.0
13.90
213.0
112.0
13.70
210.0
111.0
14.30
80
85
SHC
kW
13.30
TC
SHC
kW
193.0
93.4
13.90
TC
SHC
kW
147.0
146.0
14.10
157.0
130.0
14.40
171.0
111.0
14.70
186.0
90.6
15.10
160.0
160.0
14.40
167.0
149.0
14.60
180.0
125.0
15.00
196.0
99.7
15.40
171.0
171.0
14.70
173.0
166.0
14.80
187.0
138.0
15.10
202.0
108.0
15.50
95
TC
144.0
144.0
14.80
141.0
141.0
15.40
136.0
136.0
16.80
154.0
128.0
15.00
151.0
127.0
15.60
144.0
124.0
16.90
168.0
109.0
15.30
164.0
107.0
16.00
157.0
104.0
17.30
182.0
89.1
158.0
158.0
15.10
155.0
155.0
15.70
149.0
149.0
17.10
163.0
148.0
15.20
160.0
146.0
15.80
152.0
142.0
17.20
177.0
123.0
15.60
173.0
122.0
16.20
165.0
118.0
17.50
191.0
98.1
167.0
167.0
15.30
164.0
164.0
16.00
158.0
158.0
17.30
170.0
163.0
15.40
166.0
161.0
16.00
159.0
156.0
17.30
182.0
137.0
15.70
178.0
135.0
16.40
170.0
132.0
17.70
197.0
106.0
16.20
193.0
105.0
16.80
183.0
101.0
18.10
100
105
115
SHC
kW
15.70
16.00
TC
SHC
kW
TC
SHC
kW
179.0
87.6
16.40
170.0
84.4
17.70
187.0
96.5
16.60
178.0
93.3
17.90
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
48
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E180 (cont)
566E180/524A-C180 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air — Cfm
6000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
4500
7500
57
62
67
72
57
62
67
72
57
62
67
72
TC
180.0
180.0
12.90
177.0
177.0
13.50
190.0
162.0
13.20
187.0
160.0
13.80
206.0
136.0
13.60
203.0
135.0
14.20
223.0
110.0
14.00
220.0
109.0
14.60
197.0
197.0
13.30
194.0
194.0
13.90
201.0
188.0
13.40
198.0
186.0
14.00
216.0
156.0
13.80
212.0
154.0
14.40
233.0
122.0
14.20
229.0
121.0
14.80
209.0
209.0
13.60
206.0
206.0
14.20
210.0
208.0
13.70
206.0
206.0
14.20
222.0
174.0
14.00
219.0
173.0
14.60
239.0
134.0
14.40
235.0
132.0
15.00
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
172.0
172.0
14.70
180.0
157.0
14.90
195.0
132.0
15.40
212.0
106.0
15.80
188.0
188.0
15.20
190.0
182.0
15.20
204.0
151.0
15.60
221.0
118.0
16.10
199.0
199.0
15.50
199.0
199.0
15.50
210.0
169.0
15.80
226.0
129.0
16.20
95
TC
169.0
169.0
15.40
166.0
166.0
16.00
159.0
159.0
17.30
176.0
155.0
15.60
172.0
153.0
16.20
164.0
149.0
17.50
191.0
130.0
16.00
187.0
128.0
16.60
178.0
124.0
17.90
207.0
104.0
16.40
203.0
102.0
17.10
193.0
98.8
18.40
184.0
184.0
15.80
181.0
181.0
16.40
173.0
173.0
17.80
186.0
180.0
15.80
182.0
178.0
16.50
174.0
172.0
17.80
200.0
149.0
16.20
195.0
147.0
16.90
185.0
144.0
18.10
216.0
116.0
16.70
211.0
115.0
17.40
201.0
111.0
18.60
195.0
195.0
16.10
191.0
191.0
16.70
183.0
183.0
18.10
195.0
195.0
16.10
191.0
191.0
16.80
183.0
183.0
18.10
205.0
168.0
16.40
201.0
166.0
17.00
191.0
162.0
18.30
221.0
128.0
16.90
216.0
126.0
17.50
205.0
122.0
18.80
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
566E180/524A-B180 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
4500
6000
7500
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
169.0
169.0
12.70
167.0
167.0
13.30
180.0
152.0
12.90
177.0
151.0
13.50
195.0
128.0
13.30
192.0
127.0
13.90
211.0
104.0
13.70
208.0
103.0
14.30
185.0
185.0
13.10
182.0
182.0
13.60
190.0
175.0
13.20
186.0
173.0
13.70
204.0
146.0
13.50
201.0
144.0
14.10
221.0
115.0
13.90
217.0
113.0
14.50
196.0
196.0
13.30
193.0
193.0
13.90
197.0
193.0
13.30
194.0
191.0
13.90
211.0
162.0
13.70
207.0
160.0
14.30
227.0
125.0
14.10
223.0
123.0
14.70
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
161.0
161.0
14.50
170.0
147.0
14.70
184.0
124.0
15.10
200.0
99.8
15.50
176.0
176.0
14.80
179.0
169.0
14.90
193.0
141.0
15.30
209.0
111.0
15.70
186.0
186.0
15.10
187.0
186.0
15.10
199.0
157.0
15.50
215.0
120.0
15.90
95
TC
159.0
159.0
15.10
156.0
156.0
15.70
150.0
150.0
17.10
166.0
145.0
15.30
163.0
144.0
15.90
155.0
140.0
17.20
181.0
122.0
15.70
177.0
120.0
16.30
168.0
117.0
17.60
196.0
98.2
173.0
173.0
15.50
169.0
169.0
16.10
163.0
163.0
17.50
176.0
167.0
15.50
172.0
165.0
16.20
164.0
160.0
17.50
189.0
139.0
15.90
185.0
138.0
16.50
175.0
134.0
17.80
204.0
109.0
16.40
200.0
107.0
17.00
190.0
104.0
18.30
183.0
183.0
15.70
179.0
179.0
16.40
172.0
172.0
17.70
183.0
183.0
15.70
179.0
179.0
16.40
172.0
172.0
17.70
194.0
155.0
16.10
190.0
153.0
16.70
180.0
150.0
18.00
210.0
119.0
16.50
205.0
117.0
17.20
195.0
114.0
18.50
100
105
115
SHC
kW
16.10
TC
SHC
kW
TC
SHC
kW
192.0
96.6
16.80
183.0
93.2
18.10
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
49
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E180 (cont)
566E180/524A-C240 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air — Cfm
8,000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
6,000
10,000
57
62
67
72
57
62
67
72
57
62
67
72
TC
201.0
201.0
13.40
198.0
198.0
14.00
205.0
191.0
13.50
202.0
190.0
14.10
220.0
159.0
13.90
216.0
157.0
14.50
238.0
125.0
14.40
234.0
123.0
15.00
217.0
217.0
13.80
214.0
214.0
14.40
217.0
217.0
13.80
214.0
214.0
14.40
229.0
184.0
14.10
225.0
182.0
14.70
246.0
140.0
14.60
242.0
139.0
15.20
228.0
228.0
14.10
225.0
225.0
14.70
228.0
228.0
14.10
225.0
225.0
14.70
234.0
207.0
14.30
230.0
205.0
14.90
251.0
155.0
14.70
247.0
154.0
15.30
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
191.0
191.0
15.30
194.0
186.0
15.30
208.0
154.0
15.70
225.0
120.0
16.20
207.0
207.0
15.70
207.0
207.0
15.70
216.0
179.0
15.90
232.0
136.0
16.40
217.0
217.0
16.00
217.0
217.0
16.00
221.0
201.0
16.10
237.0
150.0
16.60
95
TC
188.0
188.0
15.90
184.0
184.0
16.50
176.0
176.0
17.90
190.0
183.0
15.90
185.0
181.0
16.60
177.0
176.0
17.90
204.0
152.0
16.30
199.0
150.0
17.00
189.0
146.0
18.30
220.0
118.0
16.80
215.0
117.0
17.50
205.0
113.0
18.80
202.0
202.0
16.30
198.0
198.0
17.00
190.0
190.0
18.30
203.0
203.0
16.30
198.0
198.0
17.00
190.0
190.0
18.30
211.0
177.0
16.60
206.0
175.0
17.20
196.0
171.0
18.50
227.0
134.0
17.10
222.0
132.0
17.70
211.0
128.0
19.00
213.0
213.0
16.60
208.0
208.0
17.30
199.0
199.0
18.60
213.0
213.0
16.60
208.0
208.0
17.30
199.0
199.0
18.60
216.0
199.0
16.70
211.0
197.0
17.40
201.0
192.0
18.70
232.0
149.0
17.20
226.0
147.0
17.80
214.0
143.0
19.10
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
566E180/524A-B240 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
6,000
8,000
10,000
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
190.0
190.0
13.20
187.0
187.0
13.80
194.0
181.0
13.30
191.0
179.0
13.90
209.0
150.0
13.60
205.0
149.0
14.20
226.0
118.0
14.00
222.0
117.0
14.60
205.0
205.0
13.50
202.0
202.0
14.10
205.0
204.0
13.50
202.0
201.0
14.10
217.0
173.0
13.80
213.0
171.0
14.40
233.0
132.0
14.20
229.0
131.0
14.80
215.0
215.0
13.80
211.0
211.0
14.40
215.0
215.0
13.80
211.0
211.0
14.40
222.0
193.0
14.00
218.0
191.0
14.50
238.0
145.0
14.40
234.0
144.0
15.00
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
181.0
181.0
15.00
184.0
175.0
15.00
197.0
146.0
15.40
213.0
114.0
15.90
195.0
195.0
15.30
195.0
195.0
15.30
204.0
168.0
15.60
220.0
128.0
16.10
204.0
204.0
15.60
204.0
204.0
15.60
209.0
187.0
15.80
225.0
141.0
16.20
95
TC
178.0
178.0
15.60
174.0
174.0
16.20
167.0
167.0
17.60
180.0
173.0
15.70
176.0
171.0
16.30
168.0
166.0
17.60
193.0
144.0
16.00
188.0
142.0
16.60
179.0
138.0
18.00
209.0
112.0
16.50
204.0
110.0
17.10
194.0
107.0
18.40
191.0
191.0
16.00
187.0
187.0
16.60
179.0
179.0
17.90
191.0
191.0
16.00
187.0
187.0
16.60
179.0
179.0
17.90
200.0
166.0
16.20
195.0
164.0
16.90
185.0
160.0
18.10
216.0
126.0
16.70
210.0
124.0
17.30
200.0
121.0
18.60
200.0
200.0
16.20
196.0
196.0
16.90
187.0
187.0
18.20
200.0
200.0
16.20
196.0
196.0
16.90
187.0
187.0
18.20
205.0
185.0
16.40
200.0
183.0
17.00
190.0
178.0
18.30
220.0
139.0
16.80
215.0
137.0
17.50
203.0
133.0
18.70
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
50
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E240
566E240/524A-C240 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air — Cfm
8,000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
6,000
10,000
57
62
67
72
57
62
67
72
57
62
67
72
TC
228.0
228.0
17.60
225.0
225.0
18.40
239.0
207.0
18.00
235.0
205.0
18.70
258.0
174.0
18.70
254.0
172.0
19.40
279.0
139.0
19.40
274.0
137.0
20.10
248.0
248.0
18.30
245.0
245.0
19.10
252.0
240.0
18.40
248.0
237.0
19.20
269.0
199.0
19.10
265.0
197.0
19.80
290.0
155.0
19.80
285.0
153.0
20.60
262.0
262.0
18.80
258.0
258.0
19.60
262.0
262.0
18.80
258.0
258.0
19.60
277.0
222.0
19.30
272.0
220.0
20.10
297.0
169.0
20.10
291.0
167.0
20.80
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
218.0
218.0
20.00
227.0
201.0
20.30
244.0
168.0
21.00
263.0
134.0
21.70
236.0
236.0
20.70
238.0
232.0
20.70
254.0
193.0
21.30
274.0
149.0
22.10
249.0
249.0
21.10
249.0
249.0
21.10
261.0
216.0
21.60
280.0
163.0
22.40
95
TC
214.0
214.0
20.90
211.0
211.0
21.70
203.0
203.0
23.50
222.0
199.0
21.10
217.0
196.0
22.00
207.0
192.0
23.70
239.0
166.0
21.70
234.0
163.0
22.60
223.0
159.0
24.30
258.0
132.0
22.50
252.0
130.0
23.30
241.0
125.0
25.00
232.0
232.0
21.50
228.0
228.0
22.40
219.0
219.0
24.10
234.0
229.0
21.50
229.0
226.0
22.40
219.0
219.0
24.10
249.0
190.0
22.10
243.0
188.0
22.90
231.0
184.0
24.60
268.0
147.0
22.90
262.0
145.0
23.70
249.0
140.0
25.40
245.0
245.0
22.00
240.0
240.0
22.80
230.0
230.0
24.60
245.0
245.0
22.00
240.0
240.0
22.80
230.0
230.0
24.60
255.0
213.0
22.40
249.0
211.0
23.20
237.0
206.0
24.90
274.0
161.0
23.10
267.0
159.0
23.90
254.0
155.0
25.60
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
566E240/524A-B240 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
6,000
8,000
10,000
Air Entering
Condenser
(Edb)
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
TC
219.0
219.0
17.30
216.0
216.0
18.10
229.0
199.0
17.70
226.0
197.0
18.40
248.0
167.0
18.30
243.0
165.0
19.00
267.0
134.0
19.00
263.0
132.0
19.70
237.0
237.0
17.90
234.0
234.0
18.70
241.0
228.0
18.10
237.0
226.0
18.80
259.0
190.0
18.70
254.0
188.0
19.40
278.0
148.0
19.40
273.0
146.0
20.10
250.0
250.0
18.40
246.0
246.0
19.10
251.0
250.0
18.40
247.0
246.0
19.10
265.0
211.0
18.90
261.0
209.0
19.70
285.0
161.0
19.60
280.0
159.0
20.40
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
209.0
209.0
19.70
217.0
192.0
20.00
234.0
161.0
20.60
253.0
128.0
21.30
226.0
226.0
20.30
228.0
221.0
20.40
244.0
184.0
20.90
263.0
142.0
21.70
238.0
238.0
20.70
238.0
238.0
20.70
250.0
205.0
21.20
269.0
155.0
21.90
95
TC
206.0
206.0
20.60
202.0
202.0
21.40
195.0
195.0
23.30
213.0
190.0
20.80
209.0
188.0
21.70
200.0
184.0
23.40
230.0
159.0
21.40
225.0
157.0
22.20
215.0
153.0
24.00
248.0
126.0
22.10
242.0
124.0
22.90
232.0
120.0
24.60
222.0
222.0
21.10
218.0
218.0
22.00
210.0
210.0
23.80
224.0
218.0
21.20
219.0
215.0
22.00
210.0
209.0
23.80
239.0
182.0
21.70
233.0
180.0
22.60
223.0
175.0
24.30
257.0
140.0
22.50
251.0
138.0
23.30
239.0
134.0
25.00
234.0
234.0
21.50
229.0
229.0
22.40
220.0
220.0
24.20
234.0
234.0
21.50
229.0
229.0
22.40
220.0
220.0
24.20
245.0
202.0
22.00
239.0
200.0
22.80
228.0
196.0
24.50
263.0
153.0
22.70
257.0
151.0
23.50
244.0
147.0
25.20
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
51
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E240 (cont)
566E240/524A-C300 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air — Cfm
10,000
Evaporator Air — Ewb (F)
Temp (F)
Air Entering
Condenser
(Edb)
7,500
12,500
57
62
67
72
57
62
67
72
57
62
67
72
TC
249.0
249.0
18.30
245.0
245.0
19.10
254.0
236.0
18.50
249.0
234.0
19.20
272.0
196.0
19.20
267.0
194.0
19.90
293.0
154.0
19.90
288.0
152.0
20.70
268.0
268.0
19.00
263.0
263.0
19.80
268.0
268.0
19.00
263.0
263.0
19.80
282.0
226.0
19.50
277.0
224.0
20.30
303.0
172.0
20.30
297.0
170.0
21.00
281.0
281.0
19.50
276.0
276.0
20.20
281.0
281.0
19.50
276.0
276.0
20.20
289.0
253.0
19.80
283.0
251.0
20.50
309.0
190.0
20.50
303.0
188.0
21.30
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
237.0
237.0
20.70
240.0
229.0
20.80
257.0
190.0
21.40
277.0
148.0
22.20
254.0
254.0
21.30
254.0
254.0
21.30
266.0
220.0
21.80
285.0
166.0
22.60
266.0
266.0
21.80
266.0
266.0
21.80
272.0
246.0
22.00
290.0
184.0
22.80
95
TC
232.0
232.0
21.50
228.0
228.0
22.30
219.0
219.0
24.10
235.0
226.0
21.60
230.0
223.0
22.40
219.0
217.0
24.10
251.0
187.0
22.20
246.0
185.0
23.00
234.0
180.0
24.70
271.0
145.0
23.00
265.0
143.0
23.80
252.0
139.0
25.50
249.0
249.0
22.20
244.0
244.0
23.00
234.0
234.0
24.70
250.0
250.0
22.10
245.0
245.0
23.00
234.0
234.0
24.70
260.0
217.0
22.60
254.0
215.0
23.40
241.0
210.0
25.00
279.0
164.0
23.40
272.0
162.0
24.20
259.0
157.0
25.80
261.0
261.0
22.60
256.0
256.0
23.50
244.0
244.0
25.20
261.0
261.0
22.60
256.0
256.0
23.40
244.0
244.0
25.20
266.0
244.0
22.80
260.0
241.0
23.60
247.0
235.0
25.30
284.0
182.0
23.60
277.0
180.0
24.40
263.0
175.0
26.00
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
566E240/524A-B300 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air — Cfm
10,000
Evaporator Air — Ewb (F)
7,500
12,500
Air Entering
Condenser
(Edb)
57
62
67
72
57
62
67
72
57
62
67
72
TC
236.0
236.0
17.90
233.0
233.0
18.70
242.0
223.0
18.10
238.0
221.0
18.80
260.0
185.0
18.70
256.0
184.0
19.50
280.0
146.0
19.50
275.0
144.0
20.20
254.0
254.0
18.50
250.0
250.0
19.30
254.0
252.0
18.50
250.0
249.0
19.30
269.0
212.0
19.10
265.0
210.0
19.80
290.0
162.0
19.80
285.0
161.0
20.60
266.0
266.0
18.90
262.0
262.0
19.70
266.0
266.0
18.90
262.0
262.0
19.70
276.0
236.0
19.30
271.0
234.0
20.00
296.0
178.0
20.00
290.0
176.0
20.80
80
85
SHC
kW
TC
SHC
kW
TC
SHC
kW
225.0
225.0
20.30
229.0
216.0
20.40
246.0
179.0
21.00
265.0
140.0
21.80
242.0
242.0
20.90
242.0
242.0
20.90
255.0
206.0
21.40
273.0
157.0
22.10
253.0
253.0
21.30
253.0
253.0
21.30
260.0
230.0
21.60
279.0
172.0
22.30
95
TC
221.0
221.0
21.10
217.0
217.0
22.00
209.0
209.0
23.80
225.0
214.0
21.20
220.0
211.0
22.10
211.0
206.0
23.80
241.0
178.0
21.80
236.0
175.0
22.60
225.0
171.0
24.40
260.0
138.0
22.50
254.0
136.0
23.40
242.0
132.0
25.10
237.0
237.0
21.70
233.0
233.0
22.50
223.0
223.0
24.30
237.0
237.0
21.70
233.0
233.0
22.50
223.0
223.0
24.30
249.0
204.0
22.10
243.0
202.0
23.00
232.0
197.0
24.60
268.0
155.0
22.90
262.0
153.0
23.70
249.0
148.0
25.40
248.0
248.0
22.10
243.0
243.0
22.90
233.0
233.0
24.70
248.0
248.0
22.10
243.0
243.0
22.90
233.0
233.0
24.70
255.0
227.0
22.40
249.0
225.0
23.20
237.0
219.0
24.90
273.0
170.0
23.10
266.0
168.0
23.90
253.0
164.0
25.60
100
105
115
SHC
kW
TC
SHC
kW
TC
SHC
kW
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC — Total Capacity (1000 Btuh) Gross
52
ELECTRICAL DATA
566D150-240
COMPRESSOR
FAN MOTORS (Qty 2)
FLA (ea)
POWER SUPPLY
MOCP†
VOLTAGE
RANGE*
NOMINAL
VOLTAGE
(3-Ph, 60 Hz)
UNIT
SIZE
Fan No.
RLA
LRA
kW
MCA
ICF
Min
Max
1
2
208/230
460
187
414
518
253
528
660
49.3
22.1
17.9
191
80
4.3
2.3
1.8
3.7
1.9
1.8
69.6
31.7
25.6
100
50
199
84
150
180
240
1.41
1.41
1.41
575
69
40
73
208/230
460
575
187
414
518
253
528
660
63.6
29.3
23.8
266
120
96
4.3
2.3
1.8
3.7
1.9
1.8
87.5
40.7
33.0
125
60
50
274
124
100
566D
208/230
460
575
187
414
518
254
508
632
67.9
34.7
28.8
345
173
120
4.3
2.3
1.8
3.7
1.9
1.8
93.4
48.1
40.1
150
80
60
353
177
124
LEGEND
Full Load Amps
*Units are suitable for use on electrical systems where voltage supplied to the
unit terminals is not below or above the listed limits.
†Fuse or HACR circuit breaker.
FLA
—
—
HACR
Heating, Air Conditioning and
Refrigeration
NOTES:
1. The MCA and MOCP values are calculated in accordance with the National
Electrical Code (NEC), Article 440.
ICF
—
Maximum Instantaneous Current Flow
During Start-Up (LRA of compressor
plus total FLA of fan motors)
Total Fan Motor Input (kilowatts)
Locked Rotor Amps
Minimum Circuit Amps per NEC,
Section 430-24
Maximum Overcurrent Protection (amps)
Rated Load Amps (compressor)
2. Motor RLA and LRA values are established in accordance with Underwrit-
ers’ Laboratories (UL), Standard 1995.
kW
LRA
MCA
—
—
—
3. The 575-v units are UL, Canada-listed only.
MOCP
RLA
—
—
566E150-240
FAN MOTORS
Qty 2)
VOLTAGE
RANGE*
POWER
SUPPLY
FACTORY-
INSTALLED
OPTION
NOMINAL
COMPRESSOR 1
COMPRESSOR 2
UNIT
SIZE
VOLTAGE
FLA (ea)
(3 Ph, 60 Hz)
Fan No.
kW
Min Max
RLA
LRA
RLA
LRA
1
2
MCA MOCP† ICF
55.6
63.5
27.7
31.3
23.1
25.9
81.2
89.2
42.1
45.7
31.6
34.5
94.1
102.0
48.4
52.0
35.7
38.5
70
80
186
194
90
NONE OR DISCONNECT
CONVENIENCE OUTLET
208/230
460
187 253
20.7
156
20.7
156
4.3 3.7 1.41
2.3 1.9 1.41
1.8 1.8 1.41
4.3 3.7 1.41
2.3 1.9 1.41
1.8 1.8 1.41
4.3 3.7 1.41
2.3 1.9 1.41
1.8 1.8 1.41
35
NONE OR DISCONNECT
CONVENIENCE OUTLET
150
414 528
518 660
187 253
414 528
518 660
187 253
414 528
518 660
10.0
8.2
75
54
10.0
8.2
75
54
40
94
30
67
NONE OR DISCONNECT
CONVENIENCE OUTLET
575
30
70
100
100
50
236
244
117
120
97
NONE OR DISCONNECT
CONVENIENCE OUTLET
208/230
460
32.1
16.4
12.0
37.8
19.2
13.8
195
95
32.1
16.4
12.0
37.8
19.2
13.8
195
95
NONE OR DISCONNECT
CONVENIENCE OUTLET
566E 180
60
40
NONE OR DISCONNECT
CONVENIENCE OUTLET
575
80
80
40
99
125
150
60
286
294
149
153
98
NONE OR DISCONNECT
CONVENIENCE OUTLET
208/230
460
239
125
80
239
125
80
NONE OR DISCONNECT
CONVENIENCE OUTLET
240
70
45
NONE OR DISCONNECT
CONVENIENCE OUTLET
575
50
101
LEGEND
Full Load Amps
Heating, Air Conditioning and
Refrigeration
Maximum Instantaneous Current Flow
During Start-Up (LRA of compressor
plus total FLA of fan motors)
Total Fan Motor Input (kilowatts)
Locked Rotor Amps
Minimum Circuit Amps per NEC,
Section 430-24
Maximum Overcurrent Protection (amps)
Rated Load Amps (compressor)
*Units are suitable for use on electrical systems where voltage supplied to the
unit terminals is not below or above the listed limits.
†Fuse or HACR circuit breaker.
FLA
HACR
—
—
NOTES:
1. The MCA and MOCP values are calculated in accordance with the National
Electrical Code (NEC), Article 440.
ICF
—
2. Motor RLA and LRA values are established in accordance with Underwrit-
ers’ Laboratories (UL), Standard 1995.
kW
LRA
MCA
—
—
—
3. The 575-v units are UL, Canada-listed only.
4. Convenience outlet is available as either a factory-installed option or a field-
installed accessory and is 115-v, 1ph, 60 Hz.
MOCP
RLA
—
—
53
APPLICATION DATA — 566D150-240, 566E150-240
1. INSTALLATION — Select equipment to match or to be
slightly less than peak load. This provides better humidity
control, less unit cycling, and less part-load operation.
MINIMUM OUTDOOR-AIR OPERATING
TEMPERATURE — 566E150-240 UNITS
MINIMUM
When selecting vapor line sizes, oil return must be evalu-
ated, particularly at part-load conditions.
OUTDOOR-AIR
FULL LOAD
CAPACITY
(%)
TEMPERATURE (F)
UNIT
566E
SATURATED COND
TEMPERATURE (F)
With
The indoor fan must always be operating when outdoor unit
is operating.
Base
Low-Ambient
Unit
Control
Ductwork should be sized according to unit size, not build-
ing load.
150
180
240
100/50
90
50
–20
To minimize the possibility of air recirculation, avoid the use
of concentric supply/return grilles.
LIQUID LINE DATA — 566D150-240 UNITS
Indoor equipment should be selected at no less than
300 cfm/ton.
LIQUID LINE
MAX
ALLOW.
LIFT
Max Allow.
Pressure
Drop
Max Allow.
Temp
UNIT
566D
OPERATING LIMITS
Loss
(°F)
(ft)
Maximum Outdoor
115 F
(psi)
See Minimum Outdoor-Air
Operating Temperature
table below.
150
180
240
67
82
87
7
2
Minimum Outdoor Ambient
Minimum Return-Air
Temperature
Maximum Return-Air
Temperature
55 F
NOTE: Data above is for units operating at 45 F saturated suction and
95 F entering air.
95 F
LIQUID LINE DATA — 566E150-240 UNITS
Normal Acceptable Saturation
Suction Temperature Range
Maximum Discharge
Temperature
25 to 55 F
LIQUID LINE
MAX
Max Allow.
Pressure
Drop
Max Allow.
Temp
UNIT
566E
ALLOW.
LIFT
295 F
60 F
Loss
(°F)
(ft)
Minimum Discharge Superheat
(psi)
150
180
240
60
7
2
MINIMUM OUTDOOR-AIR OPERATING
TEMPERATURE — 566D150-240 UNITS
MINIMUM
2. REFRIGERANT PIPING — It is recommended that the
refrigerant piping for all commercial split systems include a
liquid line solenoid valve, a liquid line filter drier, and a sight
glass.
OUTDOOR-AIR
OPERATING
FULL LOAD
CAPACITY
(%)
UNIT
566D
NO. OF
CYLINDERS
TEMPERATURE (F)
With
Low-Ambient
Control
Base
Unit
For refrigerant lines longer than 75 lineal ft, a liquid line
solenoid valve and a suction accumulator are required.
Refer to the Refrigerant Specialties table.
6
4
100
67
20
31
40
20
33
47
15
20
150
2*
6
4
33*
100
67
–20
180
240
2*
4
2
33*
100
50
*Requires field-installed unloader.
REFRIGERANT SPECIALTIES PART NUMBERS
LIQUID LINE
UNIT
LIQUID LINE
SOLENOID VALVE (LLSV)
LLSV
COIL
SIGHT
GLASS
FILTER
DRIER
SUCTION LINE
ACCUMULATOR
SIZE (in.)
1
/
200RB7T4M
200RA8T5M
AMG/24V
AMG/24V
AMI-1TT4
AMI-1TT5
P502-8757S*
P502-8757S*
S-7063
S-7063
2
566D150
5
/
8
1
/
2
200RB7T4M
AMG/24V
AMI-1TT4
P502-8757S*
S-7721
5
566D180
/
8
/
8
/
8
/
8
/
2
/
2
/
8
/
2
/
8
200RA8T5M
200RA8T7M
200RA9T5M
200RA9T7M
AMG/24V
AMG/24V
AMG/24V
AMG/24V
AMI-1TT5
AMI-1TT7
AMI-1TT5
AMI-1TT7
P502-8757S*
P502-8757S
P502-8757S*
P502-8757S
P502-8304S Qty 2
P502-8304S Qty 2
P502-8304S Qty 2
P502-8307S*
S-7721
S-7721
S-7721
S-7721
7
5
7
1
1
5
1
5
566D240
566E150
566E180
200RB5T4M Qty 2
200RB5T4M Qty 2
200RB5T5M Qty 2
200RB6T4M Qty 2
200RB6T5M Qty 2
AMG/24V Qty 2
AMG/24V Qty 2
AMG/24V Qty 2
AMG/24V Qty 2
AMG/24V Qty 2
AMI-1TT4 Qty 2
AMI-1TT4 Qty 2
AMI-1TT5 Qty 2
AMI-1TT5 Qty 2
AMI-1TT5 Qty 2
S-7063S* Qty 2
S-7063S Qty 2
S-7063S Qty 2
S-7063S Qty 2
S-7063S Qty 2
566E240
P502-8307S*
*Bushings required.
54
APPLICATION DATA — 566D150-240, 566E150-240 (cont)
REFRIGERANT PIPING SIZES
LINEAR LENGTH OF INTERCONNECTING PIPING (FT)
0-15
16-25
26-50
Line Size (in. OD)
51-75
76-100
UNIT
566D
L
S
L
S
L
S
L
S
L
S
1
1
5
5
7
150
180
240
/
2
/
2
/
8
11/8
13/8
15/8
/
2
/
8
/
8
13/8
13/8
15/8
/
8
/
8
/
8
13/8
15/8
15/8
/
8
/
8
/
8
15/8*
15/8
21/8
/
8
/
8
/
8
15/8*
21/8*
21/8
1
5
5
5
5
7
7
7
7
7
LINEAR LENGTH OF INTERCONNECTING PIPING (FT)
0-25 25-50 50-75 75-100
Line Size (in. OD)
UNIT
566E
TXV — Thermostatic
L
S
L
S
L
S
L
S
Expansion Valve
1
1
1
1
150
180
240
/
2
/
2
/
2
11/8
13/8
13/8
/
2
/
2
/
2
11/8
13/8
13/8
/
/
/
11/8
13/8
13/8
/
/
/
11/8
13/8
13/8
2
2
8
2
8
8
1
1
1
1
1
5
5
5
Location of One Liquid Line Solenoid
Valve Serving 2 Coil Circuits
(Solenoid Drop Control)
LEGEND
—
—
L
S
Liquid
Suction
Close-coupled.
*Requires a double suction riser if 2 unloaders are used and the evaporator is
below the condensing unit. See Refrigerant Piping Sizes — Double Suction Ris-
ers table and Suction Line Piping figure below for more information.
NOTES:
1. Pipe sizes are based on a 2° F loss for liquid lines and a 1.5° F loss for suc-
tion lines.
2. Pipe sizes are based on an equivalent length equal to the maximum length
of interconnecting piping plus 50% for fittings. A more accurate estimate
may result in smaller sizes.
REFRIGERANT PIPING SIZES —
DOUBLE SUCTION RISERS
LINEAR LENGTH OF INTERCONNECTING PIPING (FT)
51-75
76-100
UNIT
566D
Line Size (in. OD)
A
B
C
A
B
C
150
180
11/8
—
13/8
—
15/8
—
11/8
13/8
15/8
15/8
13/8
21/8
NOTES:
1. See Suction Line Piping figure below for “A,” “B,” and “C” dimensions.
2. No double suction risers are needed for unit size 240.
TXV — Thermostatic
Expansion Valve
Face-Split Coil Suction and
Liquid Line Piping
LEGEND
Suction Riser Without Trap
Suction Riser With Trap
A
B
C
D
Suction Line to Condensing Unit
Short Vertical Riser Into Condensing Unit:
566D150,180 — 13/8 in. OD
Suction Line Piping
55
APPLICATION DATA — 566D150-240, 566E150-240 (cont)
MULTIPLE CONDENSING UNIT ARRANGEMENTS*
566D, 566E150-240
566D, 566E150-240
566D, 566E150-240
Space for Service and Airflow
*For clearances between controls and grounded surfaces,
check local codes.
566D,566E
150-240
DIMENSIONS (ft)
A
B
4
4
56
TYPICAL PIPING AND WIRING
NOTES:
LEGEND
1. All piping must follow standard refrigerant piping techniques.
NEC
TXV
—
—
National Electrical Code
Thermostatic Expansion Valve
Piping
2. All wiring must comply with the applicable local and national
codes.
3. Wiring and piping shown are general points-of-connection
guides only and are not intended for, or to include all details for, a
specific installation.
*Field supplied.
4. Liquid line solenoid valve (solenoid drop control) is recom-
mended to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.
Rooftop Installation — 566D150-240
57
TYPICAL PIPING AND WIRING (cont)
NOTES:
LEGEND
1. All piping must follow standard refrigerant piping techniques.
NEC
—
—
National Electrical Code
Thermostatic Expansion Valve
Piping
2. All wiring must comply with the applicable local and national
codes.
3. Wiring and piping shown are general points-of-connection
guides only and are not intended for, or to include all details for, a
specific installation.
TXV
*Field supplied.
4. Liquid line solenoid valve (solenoid drop control) is recom-
mended to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.
Ground Level Installation — 566D150-240
58
GUIDE SPECIFICATIONS — 566D150-240, 566E150-240
COMMERCIAL AIR-COOLED CONDENSING UNITS
HVAC GUIDE SPECIFICATIONS
SIZE RANGE: 121/2 TO 20 TONS, NOMINAL
b. Compressor shall be equipped with an automati-
cally reversible oil pump, operating oil charge,
suction and discharge shutoff valves, and an
insert-type, factory-sized crankcase heater to
control oil dilution.
BRYANT MODEL NUMBER: 566D, SIZES 150-240
566E, SIZES 150-240
c. Compressor shall be mounted on spring vibration
isolators with an isolation efficiency of no less
than 95%.
PART 1 — GENERAL
1.01 SYSTEM DESCRIPTION
d. Compressor speed shall not exceed 1750 rpm.
Outdoor-mounted, air-cooled condensing unit suitable for
on-the-ground or rooftop installation. Unit shall consist of a
semi-hermetic reciprocating compressor (566D) or scroll
compressor (566E), an air-cooled coil, propeller-type con-
denser fans, and a control box. Unit shall discharge supply
air upward as shown on contract drawings. Unit shall be
used in a refrigeration circuit to match a packaged fan coil
unit.
e. Compressor shall unload using suction cutoff
unloading (electrical solenoid unloading shall be
available as an accessory).
f. Compressor shall include overload protection.
g. Compressor shall be equipped with internal high
discharge temperature protection (566E180 and
240 only).
1.02 QUALITY ASSURANCE
2. 566E150-240 Units:
A. Unit shall be rated in accordance with ARI latest revisions
and shall be certified and listed in the latest ARI directory.
a. Compressors shall be of the hermetic scroll type.
b. Compressors shall be mounted on vibration
isolators.
c. Compressors shall include overload protection.
d. Compressors shall be equipped with a crankcase
heater.
B. Unit shall be manufactured in a facility registered to ISO
9001:2000 manufacturing quality standard.
C. Unit construction shall comply with latest edition of ANSI/
ASHRAE and with NEC.
D. Unit shall be constructed in accordance with UL
standards and shall carry the UL and UL, Canada label.
E. Condenser Coil:
1. Condenser coil shall be air cooled, circuited for inte-
gral subcooler.
E. Unit cabinet shall be capable of withstanding 500-hour
salt spray exposure per ASTM B117 (scribed specimen).
2. Coil shall be constructed of aluminum fins mechani-
cally bonded to copper tubes which are then
cleaned, dehydrated, and sealed. Copper fins shall
be available as an option.
F. Air-cooled condenser coils shall be leak tested at
150 psig and pressure tested at 480 psig.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as a single package only, and
shall be stored and handled per manufacturer’s
recommendations.
F. Refrigeration Components:
1. Refrigeration circuit components for 566D units shall
include hot gas muffler, high-side pressure relief
device, liquid line shutoff valve, suction and dis-
charge shutoff valves, holding charge of refrigerant
R-22, and compressor oil.
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING
ENGINEER.)
PART 2 — PRODUCTS
2.01 EQUIPMENT
A. General:
2. Refrigeration circuit components for 566E units shall
include liquid line service valve, suction line service
valve, a full charge of compressor oil, and a holding
charge of refrigerant.
Factory assembled, single piece, air-cooled condensing
unit. Contained within the unit enclosure shall be all
factory wiring, piping, controls, compressor, holding
charge (R-22), and special features required prior to field
start-up.
G. Controls and Safeties:
1. Minimum control functions shall include:
a. Power and control terminal blocks.
B. Unit Cabinet:
b. Compressor cycle delay protection prevents the
compressor from restarting for a minimum of
5 minutes after shutdown.
c. Capacity control on the compressor shall be by
suction cutoff unloader in response to compres-
sor suction pressure. Electric solenoid unloading
shall be available as an accessory (566D unit).
d. Head pressure control by fan cycling. One con-
denser fan shall be cycled by discharge pressure
to maintain proper head pressure.
Unit cabinet shall be constructed of G-90 galvanized
steel, bonderized and coated with a prepainted, baked
enamel finish.
C. Fans:
1. Condenser fans shall be direct-drive propeller type,
discharging air vertically upward.
2. Condenser-fan motor no. 1 shall be ball bearing type
compatible with accessory low-ambient control.
3. Shafts shall have inherent corrosion resistance.
2. Minimum safety devices shall include:
Automatic reset (after resetting first at thermostat)
a. High discharge-pressure cutout.
4. Fan blades shall be statically and dynamically
balanced.
5. Condenser fan openings shall be equipped with
PVC-coated steel wire safety guards.
b. Low suction pressure cutout.
c. Condenser-fan motors to be protected against
overload condition by internal overloads.
D. Compressors:
1. 566D150-240 Units:
a. Compressor shall be serviceable, reciprocating,
semi-hermetic type.
59
GUIDE SPECIFICATIONS — 566D150-240, 566E150-240 (cont)
Manual reset at the unit
b. E-Coated Aluminum-Fin Coils:
Electrical overload protection through the use of def-
inite-purpose contactors and calibrated, ambient
compensated, magnetic trip circuit breakers. Circuit
breakers shall open all 3 phases in the event of an
overload in any one of the phases or a single-phase
condition.
Shall have a flexible epoxy polymer coating uni-
formly applied to all coil surface areas without
material bridging between fins. Coating process
shall ensure complete coil encapsulation. Color
shall be high gloss black with gloss requirements
of 60° of 65-90% per ASTM D523-89. Uniform dry
film thickness from 0.8 to 1.2 mil on all surface
areas including fin edges. Superior hardness
characteristics of 2H per ASTM D3363-92A and
cross hatch adhesion of 4B-5B per ASTM D3359-
93. Impact resistance shall be up to 160 in./lb
(ASTM D2794-93). Humidity and water immersion
resistance shall be up to a minimum of 1000 and
250 hours respectively (ASTM-D2247-92 and
ASTM D870-92). Corrosion durability shall be
confirmed through testing to no less than 1000
hours salt spray per ASTM B117-90. Coil con-
struction shall be aluminum-fins mechanically
bonded to copper tubes.
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet or
exceed_____Btuh at a suction temperature of_____ F.
The power consumption at full load shall not
exceed_____ kW.
2. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net cool-
ing capacity of _____ Btuh or greater at conditions of
_____ cfm entering-air temperature at the evaporator
at _____ F wet bulb and _____ F dry bulb, and air
entering the condensing unit at _____ F.
3. The system shall have an EER of _____ Btuh/Watt or
greater at standard ARI conditions.
6. Thermostat Control Accessory:
I. Electrical Requirements:
a. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multi-stage capabil-
ity, and large LCD temperature display.
1. Nominal unit electrical characteristics shall be _____ v,
3-ph, 60 Hz. The unit shall be capable of satisfactory
operation within voltage limits of _____ v to _____ v.
b. Commercial Electronic Non-programmable Ther-
mostat with auto-changeover, multi-stage capabil-
ity, and large LCD temperature display.
2. Unit electrical power shall be single point connection.
3. Unit control circuit shall contain a 24-v transformer
for unit control, with capacity to operate an indoor fan
interlock.
7. Unit-Mounted, Non-Fused Disconnect Switch:
Shall be factory-installed, internally mounted. NEC
and UL approved non-fused switch shall provide unit
power shutoff. Shall be accessible from outside the
unit and shall provide power off lockout capability.
Not to be used when rooftop electrical rating
exceeds 80 amperes.
J. Special Features:
1. Low-Ambient Temperature Control (Factory-Installed
Option or Field-Installed Accessory):
Control shall regulate fan motor speed in response
to the saturated condensing temperature of the unit.
The control shall allow the unit to operate down to an
ambient temperature of –20 F.
8. Convenience Outlet:
Shall be factory-installed and internally mounted
with easily accessible 115-v female receptacle. Shall
include 15 amp GFI receptacle with independent
fuse protection. Voltage required to operate conve-
nience outlet shall be provided by a factory-installed
step-down transformer. Shall be accessible from out-
side the unit.
2. Electric Solenoid Unloader Accessory:
Unloader valve piston, coil, and hardware shall be
supplied to convert the pressure-operated compres-
sor unloader to electric unloading.
3. Hail Guard Package:
Hail guard package shall protect coil against hail and
other flying debris.
4. Condenser Coil Grille Package:
Grilles shall protect the condenser coils after unit
installation.
5. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Shall have a durable epoxy-phenolic coating to
provide protection in mildly corrosive coastal envi-
ronments. Coating shall be applied to the alumi-
num fin stock prior to the fin stamping process to
create an inert barrier between the aluminum fin
and copper tube. Epoxy-phenolic barrier shall
minimize galvanic action between dissimilar
metals.
60
MODEL NUMBER NOMENCLATURE
524A 120 000 GC
P
B
Factory-Installed Options
GC — Unpainted, Standard Motor
and Standard Drive
HC — Unpainted, Standard Motor
and Medium-Static Drive
(not available for 300 sizes)
TC — Unpainted, Alternate Motor
and Medium-Static Drive
(300 size only)
YC — Unpainted, Alternate Motor
and High-Static Drive*
ED — Painted, Standard Motor
and Standard Drive
524A — Fan Coil
Voltage
E — 460-3-60†
J — 208/230-1-60 (Sizes 072, 090 Only)
P — 208/230-3-60
T — 575-3-60
Coil Option
B — DX Cooling Coil With TXVs
C — DX High Capacity Cooling Coil With TXVs
FD — Painted, Standard Motor
and Medium-Static Drive
(not available for 300 size)
RD — Painted, Alternate Motor
and Medium-Static Drive
(300 size only)
Nominal Cooling (Tons)
072 — 6
090 — 7-1/2
120 — 10
150 — 12-1/2
180 — 15
WD — Painted, Alternate Motor
and High-Static Drive*
240 — 20
300 — 25
Nominal Heating (Btuh)
000 – Not applicable (524A-B and 524A-C Cooling-Only Units)
Quality Assurance
Certified to ISO 9001:2000
LEGEND
DX — Direct Expansion
TXV — Thermostatic Expansion Valve
*The YC and WD option codes for all 090 size units with 208/230-1-60 voltage designate standard motor and high-static drive.
†All 524A072-150 units with an “E” voltage designation are triple voltage (i.e., 208/230/460-3-60). Size 524A180 is also triple voltage in the “E” con-
figuration unless the alternate motor (YC or WD) option is used.
61
PHYSICAL DATA
524A-B,C UNITS
UNIT 524A
072
090
120
150
180
240
300
NOMINAL CAPACITY (Tons)
6
71/2
10
121/2
15
20
25
OPERATING WEIGHT (lb)
Base Unit with TXV (3 Row/4 Row)
Plenum
381/399
175
385/404
175
405/425
175
670/695
225
685/713
225
690/730
225
1020/1050
325
Economizer
185
185
185
340
340
340
340
Hot Water Coil
Steam Coil
195
215
195
215
195
215
285
340
285
340
285
340
345
405
FANS
Qty...Diam. (in.)
1...15
2400
1...15
3000
1...15
4000
2...15
5000
2...15
6000
2...15
8000
2...18
10,000
Nominal Airflow (cfm)
Airflow Range (cfm)
Nominal Motor Hp (Standard Motor)*
208/230-1-60
1800-3000
2250-3750
3000-5000
3750-6250
4500-7500
6000-10,000
7500-12,500
1.3
2.4
1.0
2.4
2.4
2.0
—
2.4
2.0
—
2.9
3.0
—
3.7
3.0
—
5.0
5.0
—
7.5
7.5
208/230-3-60 and 460-3-60
575-3-60
Motor Speed (rpm)
208/230-1-60
208/230-3-60 and 460-3-60
575-3-60
1725
1725
1725
1725
1725
1725
—
1725
1725
—
1725
1725
—
1725
1725
—
1745
1745
—
1745
1755
REFRIGERANT
R-22
Operating charge (lb)
(approx per circuit)†
3.0
3.0
1.5/1.5
2.0/2.0
2.5/2.5
3.5/3.5
4.5/4.5
DIRECT-EXPANSION COIL
Max Working Pressure (psig)
Face Area (sq ft)
Enhanced Copper Tubes, Aluminum Sine-Wave Fins
435
6.67
1
8.33
1
10.01
2
13.25
2
17.67
19.88
2
24.86
2
No. of Splits
2
Split Type...Percentage
No. of Circuits per Split (3 Row/4 Row)
Fins/in.
—
—
Face...50/50
12/16
15
12/12
15
15/15
15
9/9
17
9/12
15
13/18
17
15/20
15
STEAM COIL
Max Working Pressure (psig at 400 F)
Total Face Area (sq ft)
Rows...Fins/in.
175
13.33
1...10
6.67
1...9
6.67
1...9
6.67
1...9
13.33
1...10
13.33
1...10
15.0
1...10
HOT WATER COIL
Max Working Pressure (psig)
Total Face Area (sq ft)
Rows...Fins/in.
Water Volume
(gal)
150
6.67
2...8.5
6.67
6.67
2...8.5
13.33
13.33
13.33
2...8.5
15.0
2...8.5
2...8.5
2...8.5
2...12.5
8.3
1.1
13.9
1.85
14.3
1.90
(ft3)
PIPING CONNECTIONS
Quantity...Size (in.)
DX Coil — Suction (ODF)
DX Coil — Liquid Refrigerant (ODF)
Steam Coil, In (MPT)
1...11/8
1...11/8
2...11/8
2...11/8
2...11/8
2...5/8
2...1 1
/
8
2...13/8
1...5/8
1...21/2
1...11/2
1...11/2
1...11/2
1...21/2
1...11/2
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
1...11/2
1...11/2
1...2
1...2
1...11/4 ODM/1 IDF
FILTERS
Throwaway — Factory Supplied
4...16 x 20 x 2
4...20 x 24 x 2
4...20 x 25 x 2
Quantity...Size (in.)
Access Location
4...16 x 24 x 2
4...16 x 24 x 2
Right or Left Side
LEGEND
DX
TXV
—
—
Direct Expansion
Thermostatic Expansion Valve
*Refer to Alternate Fan Motor Data table, page 80, for alternate motor data.
†Units are shipped without refrigerant charge.
62
DIMENSIONS
UNIT WEIGHT
(lb)
UNIT
524A-B072
524A-B090
524A-B120
524A-C072
524A-C090
524A-C120
381
385
405
399
404
425
LEGEND
TXV
—
Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3″ (76.2 mm) (2′-6″ [762 mm]
with electric heat accessory)
• Front: 2′-6″ (762 mm)
• Right Side: 2′-6″ (762 mm)
• Left Side: 2′-6″ (762 mm)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Bryant.
5. Duct flange is factory supplied and field
installed.
524A-B,C072-120
63
DIMENSIONS (cont)
.
UNIT
WEIGHT
(lb)
UNIT
524A
B150
B180
B240
C150
C180
C240
670
685
690
695
713
730
LEGEND
Thermostatic Expansion Valve
TXV
—
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3″ (76.2 mm) (2′-6″ [762 mm]
with electric heat accessory)
• Front: 2′-6″ (762 mm)
• Right Side: 2′-6″ (762 mm)
• Left Side: 2′-6″ (762 mm)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Bryant.
5. Duct flange is factory supplied and field
installed.
524A-B,C150-240
64
DIMENSIONS (cont)
UNIT
WEIGHT
(lb)
UNIT
524A
CONTROL BOX
B300
C300
1020
1050
ALTERNATE
ACCESS
FOR FILTERS
ALTERNATE
ACCESS FOR
MOTOR/BELT
RETURN AIR
OPENING
CONTROL BOX
LEGEND
Thermostatic Expansion Valve
TXV
—
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3″ (76.2 mm) (2′-6″ [762 mm]
with electric heat accessory)
• Front: 2′-6″ (762 mm)
• Right Side: 2′-6″ (762 mm)
• Left Side: 2′-6″ (762 mm)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Bryant.
5. Duct flange is factory supplied and field
installed.
524A-B,C300
65
PERFORMANCE DATA
524A-B FAN PERFORMANCE DATA — 0.0-1.2 in. wg ESP
EXTERNAL STATIC PRESSURE (in. wg)
UNIT
AIRFLOW
0.0
0.2
0.4
0.6
0.8
1.0
1.2
524A-B
(Cfm)
Rpm
399
446
498
544
594
Bhp
0.19
0.28
0.40
0.55
0.73
Rpm
454
497
541
588
635
Bhp
0.24
0.34
0.47
0.63
0.82
Rpm
548
583
622
663
707
Bhp
0.35
0.46
0.60
0.78
0.99
Rpm
634
660
693
730
770
Bhp
0.47
0.59
0.74
0.93
1.15
Rpm
713
733
760
792
828
Bhp
0.60
0.73
0.89
1.09
1.32
Rpm
785
802
824
851
883
Bhp
0.74
0.88
1.05
1.26
1.50
Rpm
850
867
885
909
937
Bhp
0.89
1.05
1.22
1.44
1.69
1,800
2,100
2,400
2,700
3,000
072
090
120
150
180
240
300
2,250
2,600
3,000
3,400
3,750
273
322
552
615
671
0.08
0.15
0.65
0.91
1.20
493
540
595
653
706
0.37
0.52
0.73
1.01
1.31
580
622
673
726
773
0.49
0.66
0.91
1.21
1.53
656
693
740
789
834
0.62
0.81
1.07
1.40
1.74
727
757
800
846
889
0.76
0.96
1.24
1.59
1.95
794
819
856
899
940
0.92
1.12
1.41
1.78
2.16
858
878
910
950
988
1.08
1.29
1.60
1.97
2.37
3,000
3,500
4,000
4,500
5,000
399
604
680
756
834
0.29
0.92
1.33
1.86
2.51
573
641
713
787
861
0.69
1.02
1.45
1.99
2.67
654
714
778
845
914
0.86
1.22
1.68
2.26
2.96
722
780
839
901
966
1.03
1.42
1.91
2.52
3.25
784
838
896
955
1180
1.19
1.61
2.14
2.78
3.54
841
892
947
1005
1064
1.37
1.81
2.36
3.03
3.82
896
942
995
1051
1109
1.55
2.01
2.58
3.28
4.11
3,750
4,300
5,000
5,700
6,250
394
436
492
550
596
0.40
0.57
0.86
1.23
1.59
453
487
535
587
630
0.52
0.70
0.99
1.37
1.74
558
586
623
664
700
0.80
1.00
1.31
1.71
2.09
643
670
704
740
770
1.10
1.34
1.69
2.11
2.51
717
742
775
809
837
1.39
1.67
2.08
2.55
2.97
785
806
838
872
899
1.71
2.01
2.47
2.99
3.45
848
867
896
929
955
2.04
2.36
2.86
3.43
3.94
4,500
5,300
6,000
6,800
7,500
428
488
542
604
660
0.59
0.92
1.29
1.83
2.42
475
528
578
637
690
0.70
1.04
1.43
1.99
2.59
570
609
649
700
747
0.99
1.34
1.74
2.32
2.95
656
689
721
763
804
1.33
1.71
2.11
2.70
3.34
730
762
791
826
861
1.68
2.11
2.55
3.15
3.79
796
827
855
888
919
2.02
2.51
3.00
3.64
4.29
856
886
914
946
975
2.38
2.92
3.46
4.15
4.83
6,000
7,000
8,000
9,000
10,000
532
608
686
764
843
1.25
1.93
2.83
3.97
5.38
569
641
716
791
868
1.39
2.09
3.01
4.18
5.62
639
702
770
841
914
1.69
2.42
3.38
4.59
6.09
711
763
823
888
957
2.06
2.80
3.77
5.02
6.55
781
824
876
935
1000
2.48
3.23
4.21
5.47
7.02
846
885
930
982
1042
2.93
3.71
4.70
5.96
7.53
905
943
983
1030
1084
3.39
4.23
5.24
6.51
8.08
7,500
8,750
10,000
11,250
12,500
456
521
587
653
720
1.29
1.98
2.88
4.03
5.46
490
551
614
678
743
1.47
2.18
3.11
4.29
5.75
556
608
664
724
785
1.85
2.61
3.59
4.82
6.33
621
664
714
768
825
2.25
3.07
4.09
5.37
6.93
678
720
763
812
865
2.64
3.53
4.62
5.95
7.55
729
770
812
856
904
3.06
3.99
5.15
6.54
8.20
778
816
857
899
944
3.60
4.45
5.68
7.14
8.86
See Legend and Notes on page 67.
66
PERFORMANCE DATA (cont)
524A-B FAN PERFORMANCE DATA — 1.4-2.4 in. wg ESP
EXTERNAL STATIC PRESSURE (in. wg)
UNIT
AIRFLOW
1.4
1.6
1.8
2.0
2.2
2.4
524A-B
(Cfm)
Rpm
910
927
944
964
989
Bhp
1.04
1.21
1.41
1.63
1.89
Rpm
965
983
999
1018
1039
Bhp
1.20
1.38
1.59
1.82
2.10
Rpm
1180
1035
1052
1069
1089
Bhp
1.36
1.56
1.78
2.03
2.31
Rpm
1065
1084
1101
1118
1136
Bhp
1.52
1.74
1.98
2.24
2.53
Rpm
1111
1131
1149
1165
1183
Bhp
1.69
1.92
2.18
2.45
2.76
Rpm
1155
1175
1193
—
Bhp
1.86
2.11
2.38
—
1,800
2,100
2,400
2,700
3,000
072
090
120
150
180
240
300
—
—
2,250
2,600
3,000
3,400
3,750
918
936
963
998
1360
1.26
1.48
1.79
2.18
2.58
975
991
1150
1045
1078
1.43
1.67
1.99
2.39
2.80
1029
1044
1064
1092
1122
1.62
1.87
2.20
2.61
3.03
1079
1094
1113
1137
1164
1.80
2.07
2.42
2.83
3.27
1126
1142
1159
1182
—
1.99
2.28
2.64
3.07
—
1172
1188
—
—
—
2.18
2.49
—
—
—
3,000
3,500
4,000
4,500
5,000
949
990
1040
1094
1151
1.74
2.21
2.80
3.53
4.39
1000
1037
1084
1136
1191
1.93
2.42
3.03
3.78
4.66
1050
1083
1126
1176
—
2.14
2.64
3.26
4.03
—
1099
1128
1167
—
2.36
2.86
3.50
—
1147
1172
—
2.58
3.10
—
1192
—
—
2.81
—
—
—
—
—
—
—
—
—
—
—
—
3,750
4,300
5,000
5,700
6,250
909
925
950
981
1072
2.37
2.73
3.26
3.88
4.42
968
980
1002
1031
1057
2.74
3.11
3.67
4.33
4.91
1026
1360
1052
1079
1103
3.12
3.52
4.09
4.79
5.40
1080
1084
1101
1125
1148
3.51
3.92
4.53
5.25
5.90
1131
1135
1148
1169
1191
3.92
4.35
4.98
5.73
6.40
1181
1184
1190
—
4.32
4.78
5.44
—
—
—
4,500
5,300
6,000
6,800
7,500
912
940
968
1000
1300
2.75
3.33
3.92
4.67
5.39
967
992
1018
1050
1078
3.13
3.75
4.38
5.19
5.97
1019
1041
1066
1097
1125
3.52
4.18
4.85
5.71
6.54
1070
1088
1112
1142
1170
3.92
4.61
5.32
6.23
7.11
1120
1134
1156
1185
—
4.35
5.06
5.80
6.76
—
1168
1179
1198
—
4.79
5.52
6.29
—
—
—
6,000
7,000
8,000
9,000
10,000
954
990
1300
1073
1126
3.83
4.74
5.79
7.11
8.75
1005
1040
1078
1120
1166
4.27
5.24
6.38
7.72
9.37
1052
1090
1130
1169
—
4.72
5.80
7.00
8.37
—
1098
1135
1173
—
5.22
6.30
7.60
—
1142
1176
—
—
—
5.67
6.84
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
7,500
8,750
10,000
11,250
12,500
831
859
900
941
984
4.41
4.97
6.20
7.73
9.53
870
901
939
980
1022
5.10
5.59
6.74
8.32
10.19
913
944
976
1017
1058
5.90
6.42
7.33
8.90
10.84
950
980
1013
1052
1093
6.88
7.20
8.00
9.51
11.49
985
1020
1050
1086
—
7.70
8.10
8.82
10.16
—
—
—
—
—
—
—
—
—
—
—
LEGEND
NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit size 300;
1200 rpm for all other sizes.
Bhp — Brake Horsepower Input to Fan
ESP — External Static Pressure
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See table on page 70 for factory-supplied
filter pressure drop.
3. The medium-static drive and standard motor combination is not
available for 300 size. Use alternate motor if medium-static drive is
required for these sizes.
Bold indicates field-supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than
the standard motor and standard drive combination is required. Refer to
fan motor and drive tables, pages 79-81, to complete selection.
67
PERFORMANCE DATA (cont)
FAN PERFORMANCE DATA — 524A-C WITH HIGH CAPACITY COIL —
0.0-1.2 in. wg ESP
UNIT
EXTERNAL STATIC PRESSURE (in. wg)
524A-C
AIRFLOW
(Cfm)
0.0
0.2
0.4
0.6
0.8
1.0
1.2
(High-Capacity
4-Row Coil)
Rpm Bhp Rpm Bhp Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1,800
2,100
2,400
2,700
3,000
419
471
524
578
633
0.21
0.31
0.44
0.61
0.81
471
519
568
619
671
0.26
0.37
0.51
0.69
0.90
564
602
645
690
738
0.37
0.49
0.64
0.84
1.07
649
679
715
755
799
0.49
0.62
0.79
0.99
1.24
727
751
781
816
856
0.63
0.77
0.94
1.15
1.41
797
819
844
875
910
0.77
0.92
1.11
1.33
1.60
862
882
905
932
963
0.92
1.09
1.28
1.51
1.79
072
090
120
150
180
240
300
2,250
2,600
3,000
3,400
3,750
290
349
579
646
705
0.10
0.19
0.70
0.99
1.31
510
561
621
683
739
0.39
0.55
0.79
1.09
1.42
594
640
695
752
804
0.51
0.70
0.96
1.29
1.63
669
709
759
813
862
0.65
0.84
1.12
1.48
1.85
739
773
818
869
915
0.79
1.00
1.30
1.67
2.05
806
834
874
920
964
0.95
1.16
1.47
1.86
870
893
928
970
1.12
1.34
1.66
2.06
2.48
2.26 1011
3,000
3,500
4,000
4,500
5,000
421
626
706
786
867
0.35
0.98
1.42
1.99
2.70
592
664
738
815
893
0.73
1.08
1.54
2.12
2.84
670
735
803
873
946
0.90
1.28
1.77
2.39
3.14
737
798
862
929
997
1.06
1.48
2.00
2.65
797
855
917
980
1.23
1.67
2.23
2.90 1300
3.72 1092
854
908
967
1.41
1.87
2.45 1150
3.16 1073
4.00 1135
908
958
1.59
2.07
2.67
3.41
4.28
3.43 1046
3,750
4,300
5,000
5,700
6,250
410
455
514
575
624
0.43
0.62
0.92
1.32
1.71
467
504
556
612
657
0.55
0.74
1.06
1.47
1.87
567
599
641
686
725
0.83
1.05
1.39
1.82
2.24
649
679
718
759
793
1.12
1.38
1.76
2.23
2.66
721
748
786
825
856
1.41
1.70
2.14
2.66
3.12
788
811
847
884
915
1.72
2.04
2.52
3.09
3.59
851
871
903
939
969
2.05
2.39
2.91
3.52
4.06
4,500
5,300
6,000
6,800
7,500
437
499
555
620
677
0.61
0.95
1.34
1.91
2.52
483
538
590
651
706
0.72
1.07
1.48
2.06
2.69
576
617
659
712
761
1.01
1.37
1.79
2.39
3.04
660
696
730
774
817
1.35
1.74
2.17
2.78
3.44
732
767
798
836
873
1.69
2.13
2.59
3.22
3.89
797
830
860
896
929
2.03
2.53
3.04
3.71
4.39
856
888
918
952
984
2.38
2.94
3.49
4.21
4.93
6,000
7,000
8,000
9,000
10,000
542
620
700
781
862
1.29
1.99
2.92
4.10
5.56
577
652
728
806
885
1.42
2.15
3.10
4.30
5.79
646
711
781
854
929
1.72
2.48
3.46
4.71
6.24
716
771
833
900
971
2.09
2.85
3.85
5.13
785
831
885
946
2.51
3.28
4.29
5.58
849
890
938
993
2.95
3.76
4.78
6.08 1039
7.69 1096
907
947
990
3.40
4.27
5.32
6.62
8.24
6.70 1120
7.18 1054
7,500
8,750
10,000
11,250
12,500
476
545
615
685
756
1.39
2.14
3.12
4.37
5.92
510
574
641
709
778
1.58
2.35
3.36
4.64
6.22
579
633
692
754
819
1.99
2.81
3.87
5.20
6.83
644
691
743
800
860
2.40
3.29
4.41
5.79
7.47
701
747
794
845
901
2.81
3.77
4.96
6.40
8.14
752
797
843
891
942
3.29
4.25
5.51
7.02
8.83
804
842
888
935
983
3.96
4.76
6.05
7.64
9.52
See Legend and Notes on page 69.
68
PERFORMANCE DATA (cont)
FAN PERFORMANCE DATA — 524A-C
WITH HIGH CAPACITY COIL — 1.4-2.4 in. wg ESP
UNIT
EXTERNAL STATIC PRESSURE (in. wg)
1.8 2.0
524A-C
AIRFLOW
(Cfm)
1.4
1.6
2.2
2.4
(High-Capacity
4-Row Coil)
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1,800
2,100
2,400
2,700
3,000
921
942
963
987
1015
1.07
1.26
1.47
1.71
1.99
975
997
1017
1039
1065
1.23
1.43
1.66
1.91
2.20
1026
1048
1069
1090
1113
1.39
1.61
1.85
2.12
2.42
1074
1097
1118
1138
1161
1.55
1.79
2.05
2.33
2.65
1120
1143
1164
1185
—
1.72
1.97
2.25
2.55
—
1164
1186
—
—
—
1.90
2.16
—
—
—
072
090
120
150
180
240
300
2,250
2,600
3,000
3,400
3,750
930
950
980
1018
1057
1.29
1.53
1.86
2.26
2.69
986
1005
1031
1065
1101
1.47
1.72
2.06
2.48
2.92
1039
1057
1081
1111
1144
1.65
1.92
2.27
2.70
3.15
1089
1107
1129
1156
1186
1.84
2.13
2.49
2.93
3.39
1136
1154
1175
—
2.03
2.33
2.72
—
1181
—
—
—
—
2.22
—
—
—
—
—
—
3,000
3,500
4,000
4,500
5,000
961
1005
1058
1116
1176
1.78
2.27
2.90
3.66
4.56
1120
1052
1101
1157
—
1.98
2.49
3.13
3.91
—
1062
1098
1143
1196
—
2.19
2.71
3.36
4.16
—
1111
1142
1184
—
2.41
2.94
3.60
—
1158
1186
—
—
—
2.64
3.18
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
3,750
4,300
5,000
5,700
6,250
912
928
956
990
1019
2.39
2.75
3.30
3.96
4.54
971
982
1072
1039
1067
2.76
3.13
3.71
4.40
5.02
1300
1036
1056
1086
1112
3.14
3.53
4.13
4.85
5.50
1083
1087
1104
1130
1156
3.54
3.94
4.56
5.31
5.99
1135
1138
1151
1174
1198
3.95
4.37
5.00
5.78
6.49
1185
1187
1196
—
4.36
4.81
5.46
—
—
—
4,500
5,300
6,000
6,800
7,500
912
942
971
1005
1036
2.75
3.34
3.95
4.72
5.48
967
992
1020
1054
1084
3.12
3.76
4.40
5.23
6.04
1019
1041
1067
1101
1131
3.52
4.18
4.86
5.75
6.61
1070
1088
1112
1145
1174
3.92
4.61
5.33
6.27
7.17
1120
1134
1156
1187
—
4.35
5.06
5.81
6.79
—
1168
1179
1198
—
4.79
5.52
6.29
—
—
—
6,000
7,000
8,000
9,000
10,000
961
1000
1041
1086
1138
3.86
4.79
5.88
7.21
8.83
1011
1050
1090
1133
1240
4.31
5.32
6.47
7.82
9.46
1058
1097
1137
1178
—
4.77
5.85
7.07
8.47
—
1104
1142
1181
—
5.24
6.38
7.67
—
1147
1184
—
—
—
5.71
6.91
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
7,500
8,750
10,000
11,250
12,500
874
886
930
976
1023
5.33
5.36
6.60
8.25
10.20
897
930
969
1150
1061
5.91
6.13
7.20
8.86
10.88
940
982
1072
1051
1097
6.80
7.32
7.89
9.49
11.56
990
1020
1045
1086
—
7.50
8.10
8.71
10.17
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit size 300;
1200 rpm for all other sizes.
Bhp — Brake Horsepower Input to Fan
ESP — External Static Pressure
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See table on page 70 for factory-supplied
filter pressure drop.
3. The medium-static drive and standard motor combination is not
available for 300 size. Use alternate motor if medium-static drive is
required for these sizes.
Bold indicates field-supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than
the standard motor and standard drive combination is required. Refer to
fan motor and drive tables, pages 79-81, to complete selection.
69
PERFORMANCE DATA (cont)
FACTORY-SUPPLIED FILTER PRESSURE DROP ACCESSORY PLENUM AIR THROW DATA
UNIT
VANE DEFLECTION
UNIT
524A
AIRFLOW
AIRFLOW
PRESSURE DROP
(in. wg)
524A-B
524A-C
(Cfm)
(Cfm)
Straight
21½°
33
45°
24
28
30
33
28
31
37
47
072
090
102
120
150
180
240
300
2,400
3,000
3,400
4,000
5,000
6,000
8,000
10,000
39
45
49
55
45
50
60
76
1,800
2,400
3,000
2,250
3,000
3,750
3,000
4,000
5,000
3,750
5,000
6,250
4,500
6,000
7,500
6,000
8,000
10,000
0.05
0.08
0.11
0.07
0.11
0.15
0.11
0.17
0.23
0.06
0.10
0.13
0.08
0.12
0.17
0.12
0.19
0.26
0.15
0.22
0.30
072
090
120
150
180
240
300
38
41
46
38
43
51
65
Throw distances shown are for 75 fpm terminal velocity. Use the follow-
ing multipliers to determine throw values for other terminal velocities.
TERMINAL VELOCITY
THROW FACTOR
(Fpm)
50
100
150
X 1.50
X 0.75
X 0.50
7,500
10,000
12,500
ACCESSORY PRESSURE DROP (in. wg)
HEATING COILS
Steam
UNIT
524A
AIRFLOW
(Cfm)
DISCHARGE
PLENUM
RETURN AIR
GRILLE
ECONOMIZER
Hot Water
Electric
1,800
2,400
3,000
2,250
3,000
3,750
2,550
3,400
4,250
3,000
4,000
5,000
3,750
5,000
6,250
4,500
6,000
7,500
6,000
8,000
10,000
0.06
0.10
0.14
0.09
0.14
0.21
0.11
0.17
0.24
0.14
0.22
0.32
0.07
0.12
0.17
0.10
0.16
0.23
0.16
0.26
0.37
0.15
0.24
0.34
0.01
0.01
0.02
0.01
0.02
0.03
0.02
0.03
0.04
0.02
0.04
0.06
0.01
0.02
0.02
0.01
0.02
0.03
0.02
0.04
0.06
0.02
0.03
0.05
0.10
0.16
0.23
0.15
0.23
0.35
0.18
0.28
0.41
0.23
0.37
0.53
0.11
0.17
0.25
0.15
0.23
0.33
0.23
0.37
0.53
0.28
0.44
0.63
0.10
0.16
0.23
0.15
0.23
0.35
0.18
0.28
0.41
0.23
0.37
0.53
0.11
0.17
0.25
0.15
0.23
0.33
0.23
0.37
0.53
0.28
0.44
0.63
0.04
0.06
0.10
0.06
0.10
0.15
0.07
0.12
0.19
0.10
0.17
0.26
0.04
0.07
0.11
0.06
0.10
0.15
0.10
0.17
0.26
0.09
0.16
0.24
0.05
0.07
0.09
0.06
0.09
0.15
0.07
0.13
0.19
0.09
0.17
0.28
0.05
0.07
0.11
0.06
0.09
0.15
0.09
0.17
0.28
0.06
0.09
0.14
072
090
102
120
150
180
240
300
7,500
10,000
12,500
70
PERFORMANCE DATA (cont)
HYDRONIC HEATING CAPACITIES
1-ROW
STEAM*
2-ROW
HOT WATER COIL†
UNIT
524A-B
524A-C
AIRFLOW
(Cfm)
Water
Cap.
Ldb
Cap.
Ldb
Flow
PD
(Gpm)
1,800
2,400
3,000
2,250
3,000
3,750
3,000
4,000
5,000
3,750
5,000
6,250
146
173
209
168
209
240
209
243
279
370
425
465
402
458
479
458
487
499
511
575
626
134
126
123
129
123
117
123
115
111
150
137
128
141
129
118
129
115
105
122
112
106
156.0
183.0
206.0
174.0
206.0
238.0
299.0
275.0
316.0
362.0
409.0
456.0
412.0
471.0
529.0
506.0
584.0
652.0
649.0
752.0
842.0
140
131
124
133
124
118
152
124
119
149
136
128
145
133
125
138
128
120
140
130
122
15.6
18.3
20.6
17.4
20.6
23.8
29.9
27.5
31.6
36.2
40.9
45.6
41.2
47.1
52.9
50.6
58.4
65.2
64.9
75.2
84.2
3.4
4.3
5.2
4.0
5.2
6.5
5.0
6.6
8.2
4.2
5.1
6.0
4.5
5.5
6.6
5.1
6.3
7.5
5.7
7.1
8.5
072
090
120
150
180
240
300
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
LEGEND
NOTES:
1. Maximum operating limits for heating coils: 20 psig at 260 F.
Cap. — Capacity (Btuh in thousands)
Capacity (Btuh)
Lab
PD
—
—
Leaving-Air Dry-Bulb Temp (F)
Pressure Drop (ft water)
2. Leaving db = ent db (F) +
1.1 x cfm
3. See Heating Correction Factors table.
*Based on 5 psig steam, 60 F entering-air temperature. All steam coils
are non-freeze type.
†Based on 200 F entering water, 20 F water temperature drop, 60 F
entering-air temperature.
HEATING CORRECTION FACTORS
HOT WATER COIL
Water Temp
Drop
Ent Water
Temp
(F)
Entering-Air Temp (F)
60
40
50
70
80
(F)
140
160
240
200
220
140
160
240
200
220
140
160
240
200
220
0.72
0.89
1.06
1.22
1.39
0.64
0.81
0.98
1.15
1.32
0.56
0.74
0.91
1.08
1.25
0.64
0.81
0.98
1.15
1.32
0.57
0.74
0.91
1.08
1.25
0.49
0.66
0.83
1.00
1.18
0.57
0.74
0.90
1.07
1.24
0.49
0.66
0.83
1.00
1.17
0.41
0.58
0.76
0.93
1.10
0.49
0.66
0.83
1.00
1.17
0.41
0.58
0.75
0.93
1.10
0.33
0.51
0.68
0.85
1.03
0.41
0.58
0.75
0.92
1.09
0.33
0.51
0.68
0.85
1.02
0.24
0.43
0.60
0.78
0.95
10
20
30
STEAM COIL
50
Entering-Air Temp (F)
60
Steam Pressure
(psig)
40
70
80
0
2
5
1.06
1.09
1.13
0.98
1.02
1.06
0.91
0.95
1.00
0.85
0.89
0.93
0.78
0.82
0.87
NOTE: Multiply capacity given in the Hydronic Heating Capacities table by the correction factor for conditions at which unit is actually
operating. Correct leaving-air temperature using formula in Note 2 of Hydronic Heating Capacities table.
71
ELECTRICAL DATA
524A-B,C STANDARD MOTORS
FAN MOTOR
POWER SUPPLY
Minimum Circuit
UNIT
524A-B
524A-C
VOLTAGE
V*-PH-Hz
LIMITS
Hp (kW)
FLA
MOCP
Amps
208/230-1-60
208/230-3-60
460-3-60
187-253
187-253
414-506
518-632
187-253
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
1.3 (0.97)
2.4 (1.79)
2.4 (1.79)
1.0 (0.75)
2.4 (1.79)
2.4 (1.79)
2.4 (1.79)
2.0 (1.49)
2.4 (1.79)
2.4 (1.79)
2.0 (1.49)
2.9 (2.16)
2.9 (2.16)
3.0 (2.24)
3.7 (2.76)
3.7 (2.76)
3.0 (2.24)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
7.6
5.2
2.6
1.4
11.0
5.2
2.6
2.3
5.2
2.6
9.5
6.5
3.3
1.8
13.8
6.5
3.3
2.9
6.5
3.3
2.9
9.4
4.3
4.8
12.8
6.0
4.8
18.3/16.0
8.0
15
15
15
15
20
15
15
15
15
15
15
15
15
15
20
15
15
072
090
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
120
150
180
240
300
2.3
7.5
3.4
3.8
10.2
4.8
3.8
14.6/12.8
6.4
5.1
21.5/19.4
9.7
30/25
15
15
45/40
20
15
6.4
26.9/24.3
12.1
9.8
575-3-60
7.8
See Legend and Notes on page 73.
72
ELECTRICAL DATA (cont)
524A-B,C ALTERNATE MOTORS
FAN MOTOR
POWER SUPPLY
Minimum Circuit
UNIT
VOLTAGE
524A-B
524A-C
V*-PH-Hz
LIMITS
Hp (kW)
FLA
MOCP
Amps
13.8
9.4
4.3
2.9
13.8
9.4
4.3
4.8
12.8
6.0
4.8
12.7
6.0
6.4
18.3/16.0
8.0
208/230-1-60
208/230-3-60
460-3-60
187-253
187-253
414-506
518-632
187-253
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
2.4 (1.79)
2.9 (2.16)
2.9 (2.16)
2.0 (1.49)
2.4 (1.79)
2.9 (2.16)
2.9 (2.16)
3.0 (2.24)
3.7 (2.76)
3.7 (2.76)
3.0 (2.24)
3.7 (2.76)
3.7 (2.76)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)
11.0
7.5
3.4
2.3
11.0
7.5
3.4
3.8
10.2
4.8
3.8
10.2
4.8
5.1
14.6/12.8
6.4
5.1
21.5/19.4
9.7
20
15
15
15
15
15
15
15
20
15
15
20
15
15
30/25
15
15
45/40
20
072
090
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
120
150
180
240
300
6.4
26.9/24.3
12.1
9.8
35.3/33.5
16.8
12.9
7.8
15
60/60
30
28.2/26.8
13.4
10.3
575-3-60
20
LEGEND
Full Load Amps
Determine maximum deviation from average voltage.
(AB) 397 – 393 = 4 v
FLA
—
(BC) 403 – 397 = 6 v
MOCP — Maximum Overcurrent Protection
(AC) 397 – 396 = 1 v
*Motors are designed for satisfactory operation within 10% of nominal
voltages shown. Voltages should not exceed the limits shown in the
Voltage Limits column.
Maximum deviation is 6 v.
Determine percent of voltage imbalance.
6
% Voltage Imbalance = 100 x
NOTES:
397
1. Minimum circuit amps (MCA) and MOCP values are calculated in
accordance with NEC (National Electrical Code) Article 440.
2. Motor FLA values are established in accordance with UL (Under-
writers’ Laboratories) Standard 1995.
= 1.5%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage
is greater than 2%. Use the following formula to determine the per-
centage of voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 460-3-60.
AB = 393 v
BC = 403 v
AC = 396 v
393 + 403 + 396
Average Voltage =
3
1192
3
=
= 397
73
ELECTRICAL DATA (cont)
ELECTRIC HEATER DATA
ELECTRIC HEATER(S)
FAN MOTOR
Nominal
HEATER PART NO.
CAELHEAT001A00
UNIT
V-PH-Hz
Actual Capacity (kW)
Stage 1 Stage 2 Total
MCA* MOCP*
FLA
Capacity (kW)
Hp
kW FLA
7.6
1.3† 0.97
2.4† 1.79 11.0
2.4
2.9
3.7
5
5
5
5
5
3.8
3.8
3.8
3.8
3.8
—
—
—
—
—
3.8 10.4 22.5
3.8 10.4 26.8
3.8 10.4 19.5
3.8 10.4 22.4
3.8 10.4 25.8
25
35
20
25
30
208-3-60
1.79
2.16
5.2
7.5
2.76 10.2
1.3† 0.97
7.6
5
5
5
5
5
5.0
5.0
5.0
5.0
5.0
—
—
—
—
—
5.0 12.0 24.5
5.0 12.0 28.8
5.0 12.0 21.5
5.0 12.0 24.4
5.0 12.0 27.8
25
35
25
25
30
2.4† 1.79 11.0
240-3-60
2.4
2.9
3.7
1.79
2.16
2.76 10.2
5.2
7.5
2.4
2.9
3.7
1.0
2.0
3.0
1.79
2.16
2.76
0.75
1.49
2.24
2.6
3.4
4.8
1.4
2.3
3.8
5
5
5
5
5
5
5.0
5.0
5.0
5.0
5.0
5.0
—
—
—
—
—
—
5.0 6.00 10.8
5.0 6.00 11.8
5.0 6.00 13.5
15
15
15
15
15
15
CAELHEAT002A00
CAELHEAT003A00
480-3-60
575-3-60
5.0 5.00
5.0 5.00
8.0
9.2
5.0 5.00 11.0
1.3† 0.97
7.6
10
10
10
10
10
7.5
7.5
7.5
7.5
7.5
—
—
—
—
—
7.5 20.8 35.6
7.5 20.8 39.8
7.5 20.8 32.6
7.5 20.8 35.4
7.5 20.8 38.8
40
40
35
40
40
2.4† 1.79 11.0
208-3-60
240-3-60
2.4
2.9
3.7
1.79
2.16
2.76 10.2
5.2
7.5
CAELHEAT004A00
1.3† 0.97
7.6
10
10
10
10
10
10.0
10.0
10.0
10.0
10.0
—
—
—
—
—
10.0 24.1 39.6
10.0 24.1 43.8
10.0 24.1 36.6
10.0 24.1 39.4
10.0 24.1 42.8
40
50
40
40
50
2.4† 1.79 11.0
524A-B072-120
524A-C072-120
2.4
2.9
3.7
1.79
2.16
2.76 10.2
5.2
7.5
2.4
2.9
3.7
1.0
2.0
3.0
1.79
2.16
2.76
0.75
1.49
2.24
2.6
3.4
4.8
1.4
2.3
3.8
10
10
10
10
10
10
10.0
10.0
10.0
10.0
10.0
10.0
—
—
—
—
—
—
10.0 12.0 18.3
10.0 12.0 19.3
10.0 12.0 21.0
10.0 10.0 14.3
10.0 10.0 15.4
10.0 10.0 17.3
20
20
25
15
20
20
CAELHEAT005A00
CAELHEAT006A00
480-3-60
575-3-60
1.3† 0.97
7.6
15
15
15
15
15
11.3
11.3
11.3
11.3
11.3
—
—
—
—
—
11.3 31.3 48.6
11.3 31.3 52.9
11.3 31.3 45.6
11.3 31.3 48.5
11.3 31.3 51.9
50
60
50
50
60
2.4† 1.79 11.0
208-3-60
240-3-60
2.4
2.9
3.7
1.79
2.16
2.76 10.2
5.2
7.5
CAELHEAT007A00
1.3† 0.97
7.6
15
15
15
15
15
15.0
15.0
15.0
15.0
15.0
—
—
—
—
—
15.0 36.1 54.6
15.0 36.1 58.9
15.0 36.1 51.6
15.0 36.1 54.5
15.0 36.1 57.9
60
60
60
60
60
2.4† 1.79 11.0
2.4
2.9
3.7
1.79
2.16
2.76 10.2
5.2
7.5
2.4
2.9
3.7
1.0
2.0
3.0
1.79
2.16
2.76
0.75
1.49
2.24
2.6
3.4
4.8
1.4
2.3
3.8
15
15
15
15
15
15
15.0
15.0
15.0
15.0
15.0
15.0
—
—
—
—
—
—
15.0 18.0 25.8
15.0 18.0 26.8
15.0 18.0 28.6
15.0 15.1 20.6
15.0 15.1 21.7
15.0 15.1 23.6
30
30
30
25
25
25
CAELHEAT008A00
CAELHEAT009A00
480-3-60
575-3-60
See Legend and Notes on page 75.
74
ELECTRICAL DATA (cont)
ELECTRIC HEATER DATA (cont)
ELECTRIC HEATER(S)
FAN MOTOR
Hp kW FLA
HEATER PART NO.
CAELHEAT010A00
UNIT
V-PH-Hz
Actual Capacity (kW)
MCA* MOCP*
Nominal
FLA
Capacity (kW)
Stage 1 Stage 2 Total
1.3† 0.97
7.6
25
25
25
25
25
25
25
25
25
25
11.3
11.3
11.3
11.3
11.3
15.0
15.0
15.0
15.0
15.0
7.5
7.5
7.5
7.5
7.5
10.0
10.0
10.0
10.0
10.0
18.8 52.1
18.8 52.1
18.8 52.1
18.8 52.1
18.8 52.1
25.0 60.1
25.0 60.1
25.0 60.1
25.0 60.1
25.0 60.1
74.7
78.9
71.7
74.5
77.9
80
80
80
80
80
2.4† 1.79 11.0
208-3-60
2.4
2.9
3.7
1.79
2.16
2.76 10.2
5.2
7.5
1.3† 0.97
2.4† 1.79 11.0
7.6
84.7
88.9
81.7
84.6
87.9
90
90
90
90
90
240-3-60
2.4
2.9
3.7
1.79
2.16
2.76 10.2
5.2
7.5
2.4
2.9
3.7
1.0
2.0
3.0
1.79
2.16
2.76
0.75
1.49
2.24
2.6
3.4
4.8
1.4
2.3
3.8
25
25
25
25
25
25
15.0
15.0
15.0
15.0
15.0
15.0
10.0
10.0
10.0
10.0
10.0
10.0
25.0 30.1
25.0 30.1
25.0 30.1
25.0 25.1
25.0 25.1
25.0 25.1
40.8
41.8
43.6
33.1
34.3
36.1
50
50
50
35
35
40
CAELHEAT011A00
CAELHEAT012A00
480-3-60
575-3-60
524A-B072-120
524A-C072-120
2.4† 1.79 11.0
35
35
35
35
15.0
15.0
15.0
15.0
11.3
11.3
11.3
11.3
26.3 73.0 105.0
110
100
110
110
2.4
2.9
3.7
1.79
2.16
5.2
7.5
26.3 73.0
97.7
208-3-60
240-3-60
26.3 73.0 100.6
26.3 73.0 104.0
2.76 10.2
CAELHEAT013A00
2.4† 1.79 11.0
35
35
35
35
20.0
20.0
20.0
20.0
15.0
15.0
15.0
15.0
35.0 84.2 119.0
35.0 84.2 111.7
35.0 84.2 114.6
35.0 84.2 118.0
125
125
125
125
2.4
2.9
3.7
1.79
2.16
5.2
7.5
2.76 10.2
2.4
2.9
3.7
2.0
3.0
1.79
2.16
2.76
1.49
2.24
2.6
3.4
4.8
2.3
3.8
35
35
35
35
35
20.0
20.0
20.0
20.0
20.0
15.0
15.0
15.0
15.0
15.0
35.0 42.1
35.0 42.1
35.0 42.1
35.0 35.1
35.0 35.1
55.9
56.9
58.6
46.8
48.7
60
60
60
50
50
CAELHEAT014A00
CAELHEAT015A00
480-3-60
575-3-60
LEGEND
FLA — Full Load Amps
Hp — Horsepower
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection (Amps)
2. The following equation converts kW of heat energy to Btuh:
kW x 3,412 = Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total
external static pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate fac-
tory-supplied motors.
6. Approximate shipping weight for CAELHEAT001A00-015A00 is
55 lb each, CAELHEAT016A00-027A00 is 60 lb each, and
CAELHEAT028A00-039A00 is 75 lb each.
*Values shown are for single-point connection of electric heat acces-
sory and air handler.
†Single-phase motors. All other motors are 3-phase.
NOTES:
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To
determine heater capacity (kW) at unit nameplate multiply the
240-v, 480-v, or 575-v capacity (kW) by the factor shown in the
table below for the unit voltage.
HEATER
RATING
VOLTAGE
ACTUAL HEATER VOLTAGE
200 208 230 240 400 440 460 480 550 575 600
240
480
575
0.694 0.751 0.918
1
—
—
—
—
—
—
1
—
—
—
—
1
—
—
—
—
—
—
—
—
0.694 0.84 0.918
—
—
—
—
0.915
1.089
75
ELECTRICAL DATA (cont)
ELECTRIC HEATER DATA (cont)
ELECTRIC HEATER(S)
FAN MOTOR
HEATER PART NO.
CAELHEAT016A00
UNIT
V-PH-Hz
Actual Capacity (kW)
MCA*
MOCP*
Nominal
FLA
Capacity (kW)
Hp kW
2.9 2.16
FLA
7.5
Stage 1 Stage 2 Total
10
10
10
10
7.5
7.5
7.5
7.5
—
—
—
—
7.5 20.8
7.5 20.8
7.5 20.8
7.5 20.8
35.4
38.8
41.3
52.9
39.4
42.8
46.1
54.4
40
40
50
60
40
50
50
60
3.7 2.76 10.2
5.0 3.73 14.6
7.5 5.59 21.5
208-3-60
2.9 2.16
7.5
10
10
10
10
10.0
10.0
10.0
10.0
—
—
—
—
10.0 24.1
10.0 24.1
10.0 24.1
10.0 24.1
3.7 2.76 10.2
5.0 3.73 12.8
7.5 5.59 19.4
240-3-60
2.9 2.16
3.7 2.76
5.0 3.73
7.5 5.59
3.0 2.24
5.0 3.73
7.5 5.59
3.4
4.8
6.4
9.7
3.8
5.1
7.8
10
10
10
10
10
10
10
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
30
30
30
30
30
30
30
30
10.0
10.0
10.0
10.0
10.0
10.0
10.0
14.9
14.9
14.9
14.9
19.9
19.9
19.9
19.9
20.0
20.0
20.0
20.0
20.0
20.0
20.0
15.0
15.0
15.0
15.0
20.0
20.0
20.0
20.0
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
7.5
7.5
7.5
7.5
10.0
10.0
10.0
10.0
10.0 12.0
10.0 12.0
10.0 12.0
10.0 12.0
10.0 10.0
10.0 10.0
10.0 10.0
14.9 41.5
14.9 41.5
14.9 41.5
14.9 41.5
19.9 47.9
19.9 47.9
19.9 47.9
19.9 47.9
20.0 24.1
20.0 24.1
20.0 24.1
20.0 24.1
20.0 20.1
20.0 20.1
20.0 20.1
22.5 62.5
22.5 62.5
22.5 62.5
22.5 62.5
30.0 72.2
30.0 72.2
30.0 72.2
30.0 72.2
19.3
21.0
23.0
27.2
17.3
19.6
22.1
51.2
64.6
70.1
78.7
69.2
72.6
75.8
84.1
34.3
36.1
39.1
43.2
29.9
31.5
34.9
20
25
25
30
20
20
25
70
70
80
80
70
80
80
80
35
40
40
50
30
35
35
90
100
100
110
100
110
110
125
CAELHEAT017A00
CAELHEAT018A00
480-3-60
575-3-60
208-3-60
2.9 2.16
7.5
3.7 2.76 10.2
5.0 3.73 14.6
7.5 5.59 21.5
CAELHEAT019A00
2.9 2.16
7.5
3.7 2.76 10.2
5.0 3.73 12.8
7.5 5.59 19.4
240-3-60
524A-B150-240
524A-C150-240
2.9 2.16
3.7 2.76
5.0 3.73
7.5 5.59
3.0 2.24
5.0 3.73
7.5 5.59
3.4
4.8
6.4
9.7
3.8
5.1
7.8
CAELHEAT020A00
CAELHEAT021A00
480-3-60
575-3-60
208-3-60
2.9 2.16
7.5
87.5
90.9
3.7 2.76 10.2
5.0 3.73 14.6
7.5 5.59 21.5
96.4
105.0
CAELHEAT022A00
2.9 2.16
7.5
99.6
103.0
106.2
114.5
3.7 2.76 10.2
5.0 3.73 12.8
7.5 5.59 19.4
240-3-60
2.9 2.16
3.7 2.76
5.0 3.73
7.5 5.59
3.0 2.24
5.0 3.73
7.5 5.59
3.4
4.8
6.4
9.7
3.8
5.1
7.8
30
30
30
30
30
30
30
20.0
20.0
20.0
20.0
20.0
20.0
20.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
30.0 36.1
30.0 36.1
30.0 36.1
30.0 36.1
30.0 30.1
30.0 30.1
30.0 30.1
49.4
51.1
53.1
57.2
42.4
44.0
47.4
50
60
60
60
50
50
50
CAELHEAT023A00
CAELHEAT024A00
480-3-60
575-3-60
See Legend and Notes on page 77.
76
ELECTRICAL DATA (cont)
ELECTRIC HEATER DATA (cont)
ELECTRIC HEATER(S)
FAN MOTOR
HEATER PART NO.
CAELHEAT025A00
UNIT
V-PH-Hz
Actual Capacity (kW)
FLA MCA* MOCP*
Nominal
Capacity (kW)
Hp
kW FLA
Stage 1 Stage 2 Total
3.7 2.76 10.2
5.0 3.73 14.6
7.5 5.59 21.5
3.7 2.76 10.2
5.0 3.73 12.8
7.5 5.59 19.4
50
50
50
50
50
50
50
50
50
50
50
50
22.6
22.6
22.6
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
15.0
15.0
15.0
20.0
20.0
20.0
20.0
20.0
20.0
20.0
20.0
20.0
37.6 104.3 143.1
37.6 104.3 148.6
37.6 104.3 157.2
150
150
175
208-3-60
240-3-60
480-3-60
575-3-60
50.0 120.3 163.1
50.0 120.3 166.4
50.0 120.3 174.6
175
175
200
524A-B180,240
524A-C180,240
3.7 2.76
5.0 3.73
7.5 5.59
4.8
6.4
9.7
50.0
50.0
50.0
50.0
50.0
50.0
60.1
60.1
60.1
81.2
83.2
87.3
90
90
90
CAELHEAT026A00
CAELHEAT027A00
3.0 2.24
5.0 3.73
7.5 5.59
3.8
5.1
7.8
50.2
50.2
50.2
67.5
69.1
72.5
70
70
80
7.5 5.59 19.8
10.0 7.46 28.2
7.5 5.59 19.4
10.0 7.46 26.8
20
20
20
20
20
20
20
20
40
40
40
40
40
40
40
40
14.9
14.9
19.9
19.9
20.0
20.0
20.0
20.0
15.0
15.0
20.0
20.0
20.0
20.0
20.0
20.0
—
—
—
—
—
—
—
—
15.0
15.0
20.0
20.0
20.0
20.0
20.0
20.0
14.9
14.9
19.9
19.9
20.0
20.0
20.0
20.0
30.0
30.0
40.0
40.0
40.0
40.0
40.0
40.0
41.5
41.5
47.9
47.9
24.1
24.1
20.1
20.1
83.4
83.4
96.2
96.2
47.9
47.9
40.2
40.2
78.7
87.1
81.4
93.3
42.2
46.8
34.9
38.0
131.1
139.5
144.5
153.8
71.9
76.6
60.0
63.1
80
208-3-60
240-3-60
480-3-60
575-3-60
208-3-60
240-3-60
480-3-60
575-3-60
100
CAELHEAT028A00
90
110
50
50
35
40
150
150
150
175
80
80
60
70
7.5 5.59
9.7
CAELHEAT029A00
CAELHEAT030A00
10.0 7.46 13.4
7.5 5.59
7.8
524A-B300
524A-C300
10.0 7.46 10.3
7.5 5.59 19.8
10.0 7.46 28.0
7.5 5.59 19.4
10.0 7.46 26.8
CAELHEAT031A00
7.5 5.59
9.7
CAELHEAT032A00
CAELHEAT033A00
10.0 7.46 13.4
7.5 5.59 7.8
10.0 7.46 10.3
LEGEND
FLA — Full Load Amps
Hp — Horsepower
MCA — Minimum Circuit Amps
MOCP— Maximum Overcurrent Protection (Amps)
2. The following equation converts kW of heat energy to Btuh:
kW x 3,412 = Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total
external static pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate fac-
tory-supplied motors.
6. Approximate shipping weight for CAELHEAT001A00-015A00 is
55 lb each, CAELHEAT016A00-027A00 is 60 lb each, and
CAELHEAT028A00-039A00 is 75 lb each.
*Values shown are for single-point connection of electric heat acces-
sory and air handler.
NOTES:
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To
determine heater capacity (kW) at unit nameplate multiply the
240-v, 480-v, or 575-v capacity (kW) by the factor shown in the
table below for the unit voltage.
HEATER
RATING
VOLTAGE
ACTUAL HEATER VOLTAGE
200 208 230 240 400 440 460 480 550 575 600
240
480
575
0.694 0.751 0.918
1
—
—
—
—
1
—
—
—
0.915
—
—
1
—
—
1.089
—
—
—
—
—
—
—
—
0.694 0.84 0.918
—
—
—
77
ELECTRICAL DATA (cont)
ELECTRIC HEATER DATA (cont)
ELECTRIC HEATER(S)
FAN MOTOR
HEATER PART NO.
CAELHEAT034A00
UNIT
V-PH-Hz
Actual Capacity (kW)
MCA* MOCP*
Nominal Capacity (kW)
FLA
Hp kW FLA
Stage 1 Stage 2 Total
7.5 5.59 19.8
10.0 7.46 28.0
7.5 5.59 19.4
10.0 7.46 26.8
7.5 5.59 9.7
10.0 7.46 13.4
7.5 5.59 7.8
10.0 7.46 10.3
7.5 5.59 19.8
10.0 7.46 28.0
7.5 5.59 19.4
10.0 7.46 26.8
7.5 5.59 9.7
10.0 7.46 13.4
7.5 5.59 7.8
10.0 7.46 10.3
50
50
50
50
50
50
50
50
70
70
70
70
70
70
70
70
22.6
22.6
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
40.0
40.0
40.0
40.0
40.0
40.0
15.0
15.0
20.0
20.0
20.0
20.0
20.0
20.0
22.6
22.6
30.0
30.0
30.0
30.0
30.0
30.0
37.6 104.3 157.2
37.6 104.3 165.6
175
175
208-3-60
240-3-60
480-3-60
575-3-60
208-3-60
240-3-60
480-3-60
575-3-60
50.0 120.3 174.6
50.0 120.3 183.9
200
200
50.0
50.0
50.0
50.0
60.1
60.1
50.2
50.2
87.3
91.9
90
100
CAELHEAT035A00
CAELHEAT036A00
72.5
75.6
80
80
524A-B300
524A-C300
52.6 145.9 172.8
52.6 145.9 181.2
175
200
CAELHEAT037A00
70.0 168.4 192.6
70.0 168.4 201.9
200
225
70.0
70.0
70.0
70.0
84.2
96.3
84.2 100.9
100
110
CAELHEAT038A00
CAELHEAT039A00
70.3
70.3
80.0
83.2
90
90
LEGEND
FLA — Full Load Amps
Hp — Horsepower
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection (Amps)
2. The following equation converts kW of heat energy to Btuh:
kW x 3,412 = Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total
external static pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate fac-
tory-supplied motors.
6. Approximate shipping weight for CAELHEAT001A00-015A00 is
55 lb each, CAELHEAT016A00-027A00 is 60 lb each, and
CAELHEAT028A00-039A00 is 75 lb each.
*Values shown are for single-point connection of electric heat acces-
sory and air handler.
NOTES:
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To
determine heater capacity (kW) at unit nameplate multiply the
240-v, 480-v, or 575-v capacity (kW) by the factor shown in the
table below for the unit voltage.
HEATER
RATING
VOLTAGE
ACTUAL HEATER VOLTAGE
200 208 230 240 400 440 460 480 550 575 600
240
480
575
0.694 0.751 0.918
1
—
—
—
—
1
—
—
—
0.915
—
—
1
—
—
1.089
—
—
—
—
—
—
—
—
0.694 0.84 0.918
—
—
—
78
APPLICATION DATA — 524A
The air handler fan must always be operating when the con-
1. OPERATING LIMITS
densing unit is operating.
Maximum fan speed — 524A-B,C072-240 . . . . . . . .1200rpm
Maximum fan speed — 524A-B,C300 . . . 1100 rpm (18.3 r/s)
Ductwork should be sized according to unit size, not build-
ing load. For larger units with two fans, a split duct transition
is recommended at the fan outlets, but a plenum can
be used with slight reduction in external static pressure
capability.
2. GENERAL — Select equipment to match or to be slightly
less than peak load. This provides better humidity control,
less unit cycling, and less part-load operation. Equipment
should be selected to perform at no less than 300 cfm/ton.
FACTORY-INSTALLED NOZZLE AND DISTRIBUTOR DATA
FEEDER TUBES
PER DISTRIBUTOR
Qty...Size (in.)
COIL
TYPE
TXV
Qty...Part No.*
DISTRIBUTOR
Qty...Part No.†
NOZZLE
Qty...Part No.
UNIT
524A-B,C 072
524A-B,C 090
524A-B,C 120
524A-B 150
524A-C 150
524A-B 180
524A-C 180
524A-B 240
524A-C 240
524A-B 300
524A-C 300
3, 4 Row
3, 4 Row
3, 4 Row
3 Row
4 Row
3 Row
4 Row
3 Row
4 Row
3 Row
1...TDEBX8
1...TDEBX8
2...TDEX6
1...1116
1...1126
2...1115
2...1115
2...1115
2...1116
2...1126
2...1116
2...1126
2...1126
2...1126
12...1/4
15...1/4
9...1/4
1...E5
1...C6
2...E4
2...E5
2...E5
2...E6
2...C6
2...E8
2...C8
2...C10
2...C15
2...TDEBX8
2...TDEBX8
2...TDEBX8
2...TDEBX8
2...TDEBX11
2...TDEBX11
2...TDEBX11
2...TDEBX11
9...1/4
12...3/16
12...1/4
16...1/4
13...1/4
18...3/16
15...1/4
20...3/16
4 Row
*Danfoss part numbers shown.
†Sporlan Valve Co. part numbers shown.
NOTE: Hot gas bypass applications require field-supplied auxiliary side
connector.
FAN MOTOR DATA
STANDARD MOTOR
UNIT SIZE 524A
208/230-1-60
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)
208/230-3-60 and 460-3-60
Speed (rpm)
Hp
072
090
120
150
180
240
300
1725
1.3
56Y
1725
2.4
56Y
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
5
5
/
/
8
8
1725
2.4
1725
2.4
1725
2.4
1725
2.9
1725
3.7
1745
5.0
1745
7.5
Frame (NEMA)
Shaft Dia (in.)
575-3-60
56Y
56Y
56Y
56Y
56Y
S184T
11/8
S213T
13/8
5
5
5
7
7
/
/
8
/
8
/
/
8
8
8
Speed (rpm)
Hp
1725
1.0
1725
2.0
1725
2.0
1725
3.0
1725
3.0
1745
5.0
1755
7.5
Frame (NEMA)
Shaft Dia (in.)
56
56HZ
56HZ
56HZ
56HZ
184T
11/8
S213T
13/8
5
7
7
7
7
/
/
8
/
8
/
/
8
8
8
LEGEND
NEMA — National Electrical Manufacturers Association
79
APPLICATION DATA — 524A (cont)
FAN MOTOR DATA (cont)
ALTERNATE MOTOR
UNIT SIZE 524A
208/230-1-60
072
090
120
150
180
240
300
Speed (rpm)
Hp
1725
2.4
56Y
1725
2.4
56Y
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Frame (NEMA)
Shaft Dia (in.)
230-3-60 and 460-3-60
Speed (rpm)
Hp
5
5
/
/
8
8
1725
2.9
1725
2.9
1725
3.7
1725
3.7
1725
5.0
1745
7.5
1745
10.0
Frame (NEMA)
Shaft Dia (in.)
575-3-60
56Y
56Y
Y56Y
Y56Y
S184T
11/8
S213T
13/8
S215T
13/8
7
7
7
7
/
/
/
8
/
8
8
8
Speed (rpm)
Hp
1725
2.0
1725
3.0
1725
3.0
1745
5.0
1745
5.0
1755
7.5
1750
10.0
Frame (NEMA)
Shaft Dia (in.)
56HZ
56HZ
56HZ
184T
11/8
184T
11/8
S213T
13/8
D215T
13/8
7
7
7
/
/
/
8
8
8
LEGEND
NEMA — National Electrical Manufacturers Association
STANDARD DRIVE DATA
UNIT SIZE 524A
072
090
120
150
180
240
300
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
Pulley Factory Setting
Full Turns Open
2.4-3.4
2.5
2.8-3.8
2.5
3.4-4.4
2.5
2.8-3.8
2.5
2.8-3.8
2.5
3.7-4.7
3.0
4.3-5.3
3.0
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
8.8
1
1—A
8.8
1
1—A
8.8
1
1—A
9.0
17/16
1—A
9.0
17/16
1—A
9.4
17/16
1—B
11.0
115
/
16
2—B*
(2) 42.8
(2) 43.8
Belt Pitch (in.)
40.3
41.3
42.3
42.3
632
537-728
1200
42.3
41.8
FAN SPEEDS (rpm)
Factory Settings
Range
568
470-666
1200
647
549-745
1200
764
666-863
1200
632
537-728
1200
771
679-863
1200
752
682-841
1100
Max Allowable Speed (rpm)
Change per 1/2 turn of
Moveable Motor Pulley
Flange
19.6
19.6
19.7
19.1
19.1
15.3
13.1
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
5
6
6
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
9.12-
10.99
6.67-
9.43
SHAFTS CENTER DISTANCE (in.)
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
80
APPLICATION DATA — 524A (cont)
MEDIUM-STATIC DRIVE DATA
UNIT SIZE 524A
072
090
120
150
180
240
300
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
Pulley Factory Setting
Full Turns Open
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.7-4.7
3.0
4.3-5.3
3.0
4.3-5.3
3.0
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
8.8
1
1—A
8.0
1
1—A
8.0
1
1—A
8.2
17/16
1—A
8.6
17/16
1—B
9.4
17/16
2—B
9.4
115
/
16
2—B*
(2) 38.8
(2) 39.8
Belt Pitch (in.)
42.3
40.3
40.3
41.3
41.8
41.8
FAN SPEEDS (rpm)
Factory Setting
Range
764
666-863
1200
841
733-949
1200
841
733-949
1200
820
715-926
1200
842
742-943
1200
881
798-984
1200
881
798-984
1100
Max Allowable Speed (rpm)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
19.7
21.6
21.6
21.1
16.7
15.3
15.3
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
6
6
6
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
9.16-
10.99
6.67-
9.43
SHAFTS CENTER DISTANCE (in.)
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
HIGH-STATIC DRIVE DATA
UNIT SIZE 524A
MOTOR DRIVE
072
090
120
150
180
240
300
Motor Pulley Pitch Diameter (in.)
Pulley Factory Setting
Full Turns Open
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.7-4.7
3.0
4.3-5.3
3.0
4.3-5.3
3.0
4.3-5.3
3.0
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
7.0
1
1—A
41.3
6.0*
1
1—A
37.3
6.0
1
1—A
37.3
7.4
7.9
7.4
8.6
17/16
1—B
39.8
17/16
1—B
39.8
17/16
2—B
36.8
115
/
16
2—B
37.8
FAN SPEEDS (rpm)
Factory Setting
961
1121
1121
979
1060
1118
1024
838-
1084
978-
1200*†
978-
1200†
873-
1096
950-
1171
1014-
1200†
873-
1075
Range
Max Allowable Speed (rpm)
1200
24.6
1200
28.7
1200
28.7
1200
19.4
1200
18.4
1200
1100
16.7
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
19.4
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
6
6
6
6
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32**
9.16-
10.99
8.16-
10.02
6.67-
9.43
SHAFTS CENTER DISTANCE (in.)
*Values for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 7 in.
and resulting fan speed is 837-1096 rpm.
†It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT
exceed 1200 rpm.
**575-v unit has a center distance of 9.16-10.99.
81
GUIDE SPECIFICATIONS — 524A
COMMERCIAL PACKAGED AIR-HANDLING UNIT
HVAC GUIDE SPECIFICATIONS
4. Unit shall have factory-supplied 2-in. throwaway-type
filters installed upstream from the cooling coil. Filter
access shall be from either the right or left side of the
unit.
SIZE RANGE: 1,800 to 12,500 CFM, NOMINAL AIRFLOW 6 TO
25 TONS, NOMINAL COOLING
B. Coils:
BRYANT MODEL NUMBERS: 524A-B (DIRECT-EXPANSION
COIL), 524A-C (HIGH-CAPACITY 4-ROW DIRECT-EXPANSION
COIL)
Coils shall consist of 3 rows (524A-B) or 4 rows (524A-C)
of copper tubes with sine-wave aluminum fins bonded to
the tubes by mechanical expansion. Suction and liquid
line connections or supply and discharge connections
shall be made on the same side of the coil.
PART 1 — GENERAL
1.01 SYSTEM DESCRIPTION
A. Indoor, packaged air-handling unit for use in commercial
split systems. Unit shall have a multiposition design and
shall be capable of horizontal or vertical installation on a
floor or in a ceiling, with or without ductwork. (Only verti-
cal units are to be applied without ductwork.)
1. Direct-expansion coils shall feature factory-installed
thermostatic expansion valves (TXVs) for refrigerant
control. The TXVs shall be capable of external
adjustment. Coil tubing shall be internally rifled to
maximize heat transfer.
B. Unit with direct-expansion coil shall be used in a refriger-
ant circuit with a matching air-cooled condensing unit.
2. High-Capacity Coil:
The high-capacity 4-row coil consists of 4 rows of
3/8-in. copper tubes with sine-wave aluminum fins
bonded to the tubes by mechanical expansion. Coil
tubing shall be internally rifled to maximize heat
transfer. Suction and liquid line connections shall be
made on the same side of the coil. Direct-expansion
coils shall feature factory-installed thermostatic
expansion valves (TXVs) for refrigerant control. The
TXVs shall be capable of external adjustment.
1.02 QUALITY ASSURANCE
A. Coils shall be designed and tested in accordance with
ASHRAE 15 Safety Code for Mechanical Refrigeration,
latest edition.
B. Unit shall be constructed in accordance with ETL and
ETL, Canada, standards and shall carry the ETL and
ETL, Canada, labels.
C. Unit insulation and adhesive shall comply with NFPA-90A
requirements for flame spread and smoke generation.
Insulation shall contain an EPA-registered immobilized
antimicrobial agent to effectively resist the growth of
bacteria and fungi as proven by tests in accordance with
ASTM standards G21 and 22.
C. Operating Characteristics:
Unit shall be capable of providing
external static pressure of
cfm airflow at an
in. wg.
D. Motor:
Fan motor of the size and electrical characteristics speci-
fied on the equipment schedule shall be factory supplied
and installed.
D. Unit shall be manufactured in a facility registered to the
ISO 9001:2000 manufacturing quality standard.
E. Direct-expansion coils shall be burst and leak tested at
435 psi.
Motors rated at 1.3 through 3.7 hp shall have internal
thermal overload protection. Motors rated at 5, 71/2, and
10 hp shall be protected by a circuit breaker.
1.03 DELIVERY AND STORAGE
Units shall be stored and handled per manufacturer’s
recommendations.
E. Special Features:
1. Alternate Motor and Drive:
PART 2 — PRODUCTS
2.01 EQUIPMENT
An alternate motor and/or medium-static or high-
static drive shall be available to meet the airflow and
external static pressure requirements specified on
the equipment schedule.
Indoor mounted, draw-thru, packaged air-handling unit
that can be used in a suspended horizontal configuration
or a vertical configuration. Unit shall consist of forward-
curved belt-driven centrifugal fan(s), motor and drive
assembly, prewired fan motor contactor, factory-installed
refrigerant metering devices (direct-expansion coil units),
cooling coil, 2-in. disposable air filters, and condensate
drain pans for vertical or horizontal configurations.
2. External Paint:
Where conditions require, units shall be painted with
an American Sterling Gray finish.
3. Hot Water Coil:
Coil shall be 2-row, U-bend coil with copper tubes
and aluminum plate fins bonded to the tubes by
mechanical expansion. Coil shall be mounted in a
galvanized steel housing that shall be fastened to the
unit’s fan deck for blow-thru heating operation. Coil
shall have maximum working pressure of 150 psig.
A. Base Unit:
1. Cabinet shall be constructed of mill-galvanized steel.
2. Cabinet panels shall be fully insulated with 1/2-in.
fire-retardant material. Insulation shall contain an
EPA-registered immobilized antimicrobial agent to
effectively resist the growth of bacteria and fungi as
proven by tests in accordance with ASTM standards
G21 and 22.
4. Steam Distributing Coil:
Coil shall consist of one row of copper tubes with
aluminum plate fins, and shall have inner steam dis-
tributing tubes. Coil shall be mounted in a galvanized
steel housing and shall be fastened to the unit’s fan
deck for blow-thru heating operation. Coil shall have
maximum working pressure of 20 psig at 260 F.
3. Unit shall contain non-corroding condensate drain
pans for both vertical and horizontal applications.
Drain pans shall have connections on right and left
sides of unit to facilitate field connection. Drain pans
shall have the ability to be sloped toward the right or
left side of the unit to prevent standing water from
accumulating in pans.
82
GUIDE SPECIFICATIONS — 524A (cont)
5. Electric Heaters:
11. Overhead Suspension Package:
Heaters for nominal 240, 480, or 575-volt, 3-phase,
60 Hz power supply shall be factory-supplied for field
installation as shown on the equipment drawings.
Electric heat assembly shall be ETL and ETL, Can-
ada, agency approved, and shall have single-point
power wiring. Heater assembly shall include contac-
tors with 24-v coils, power wiring, 24-v control wiring
terminal blocks, and a hinged access panel. Electric
heaters shall not be used with air discharge plenum.
Package shall include necessary brackets to support
units in a horizontal ceiling installation.
12. Condensate Drain Trap:
Trap shall have transparent, serviceable design for
easy cleaning. Kit shall include overflow shutoff
switch and wiring harness for connection to an alarm
if desired.
13. UV-C Germicidal Lamps:
UV-C emitters and fixtures shall be specifically
designed for use inside an HVAC system. An ASME
nozzled test apparatus using a 45 F airstream mov-
ing at not less than 400 fpm shall measure individual
lamp output. Lamp output at 253.7 nm shall not be
less than 10µW/cm2 per inch of arc length measured
at a distance of one meter.
6. Air Discharge Plenum:
Plenum shall be factory supplied to provide free-blow
air distribution for vertical floor-mounted units. A
grille with moveable vanes for horizontal or vertical
airflow adjustment shall be included. Plenum shall
be field-assembled and field-installed on the unit’s
fan deck for blow-thru air distribution. Plenum shall
not be used with electric heaters.
a. UV-C power supplies shall be high efficiency,
electric type which are matched to the emitters
and are capable of producing the specified output
intensity with an input power no more than
80 watts.
7. Return-Air Grille:
Grille shall be factory supplied for field installation on
the unit’s return air opening.
8. Unit Subbase:
b. Emitters and fixtures shall be installed in sufficient
quantity and arranged so as to provide an equal
distribution of UV-C energy on the coil and drain
fan.
Subbase assembly shall be factory supplied for field
installation. Subbase shall elevate floor-mounted
vertical units to provide access for correct conden-
sate drain connection.
c. The minimum UV-C energy striking the leading
edge of the coil fins shall be not less than
820 µW/cm2 at the closest point and through
placement, not less than 60% of that value at the
farthest point. Equal amounts are to strike the
drain pan, either directly or indirectly through
reflection.
9. Economizer:
Economizer for ventilation or “free” cooling shall be
factory provided for field installation on either return
air opening of air handler. For free cooling applica-
tions, economizer shall be compatible with separate
thermostat; economizer dampers shall open when
outdoor air enthalpy is suitable for free cooling.
Economizer shall include enthalpy control and
damper actuator. Economizer shall be compatible
with accessory CO2 sensor. Economizer damper
shall open when indoor CO2 level rises above prede-
termined set point.
d. Emitters and fixtures shall be installed at right
angles to the conforming lines of the coil fins,
such that through incident angle reflection, UV-C
energy strikes all target surfaces of the coil, drain
pan, and the available line of sight airstream.
14. CO2 Sensor:
A 2 to 10 vdc actuator adapter must be field-supplied
and installed on economizer for demand control ven-
tilation using the CO2 sensor accessory.
The field-installed CO2 ventilation sensor measures
the amount of ventilation needed by the space and a
proportional integral derivative loop (PID) calculation
makes adjustments to the economizer minimum
position during occupied operation. The indoor CO2
will be compared to an outdoor CO2 reference before
making adjustments to the economizer minimum
position.
10. Thermostat Controls:
a. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multi-stage capabil-
ity, and large LCD temperature display.
b. Commercial Electronic Non-programmable Ther-
mostat with auto-changeover, multi-stage capac-
ity, and large LCD display.
83
INDEX
Motormaster® options
569D/F072-120, 576C120 11-32
566D/E150-240 33-60
4
Operating sequence
8
524A072-300 61-83
Options and accessories 4-6
Alternate motors and drives 5, 73, 80, 81
Application data
569D/F, 576C, 566D/E
524A 5, 6
4
569D/F072-120, 576C120 27
566D/E150-240 54-56
Performance data
569D/F072-120, 576C120 15-25
566D/F150-240 39-52
524A072-300 66-71
524A072-300 79-81
ARI capacity ratings
CO2 sensor 83
3
Physical data
Combination ratings
569D/F072-120, 576C120 12
566D/E150-240 34, 35
524A072-300 62
566D150-240/524A 40-44
566E150-240/524A 45-52
569D072-120/524A 16-21
569F120/524A 24, 25
576C/524A 22, 23
Piping and wiring
569D072-120, 576C120 28
566D150-240 57, 58
Refrigerant charge 27
Refrigerant piping 27, 54, 55
Return-air grille 5, 6
Condenser coil grille
Condensing unit ratings 15, 39
Controls
4
8
Convenience outlet
Dimensions
4
Selection procedure
Sound data
7
3
Base unit
569D/F072-120, 576C120 13, 14
Static pressure drop
Filter 70
566D/E150-240 36-38
Economizer
70
524A072-300 63-65
Discharge plenum 5, 6
Heating coil 70
Plenum 70
Dura-Shield options
E-coated coils
Economizer 5, 6
4
Steam coil 5, 6, 71
Subbase 5, 6
Thermostat 4, 5
4
Electrical data
Thermostatic expansion
569D/F072-120, 576C120 26
566D/E150-240 53
valve (TXV) 79
Unloader package
4
524A072-300 72-78
Electric heat 5, 74-78
Fan performance tables
524A072-300 66-69
Features/Benefits 1, 2
Unit-mounted non-fused disconnect
4
UV-C germicidal lamps
5
Wiring 9, 10
Gage panel
4
Guide specifications
569D072-120, 576C120 29, 30
569F120
31, 32
566D/E150-240 59, 60
524A072-300 82, 83
Hail guard
4
Hot water coil 5, 6, 71
Hydronic heat 71
Indoor-air quality (IAQ)
Liquid line piping 27, 55
1
Low ambient controls
4
Maximum temperature 27, 54
Minimum ambient operating
temperature 27, 54
Minimum temperature 27, 54
Model number nomenclature
569D/E072-120, 576C120 11
566D/E150-240 33
524A072-300 61
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
UNIT MUST BE INSTALLED IN ACCORDANCE
WITH INSTALLATION INSTRUCTIONS
Copyright 2004 Bryant Heating & Cooling Systems
Printed in U.S.A.
7/04
Catalog No. 5256-904
|
Briggs Stratton 8FBPC User Manual
Briggs Stratton 10T600 User Manual
Briggs Stratton 126300 User Manual
Briggs Stratton 217700 User Manual
Brother IntelliFAX 1575MC User Manual
Friedrich CP08 User Manual
GE 2 9824 User Manual
Haier AB124FAAHA User Manual
Heat Controller Inc Air Conditioner SMH 18 User Manual
HP Hewlett Packard LaserJet M1319f MFP User Manual