Hubbell Switch LXi 1200 User Manual

Hubbell Industrial Controls, Inc.  
Electric Fire Pump Controllers  
Specifications for LXi 1200 Across-the-Line Fire Pump Controllers * July 2002  
The fire pump controller shall be factory assembled, wired, tested as a unit assembly, shall conform to the requirements of the latest  
editions of NFPA-20 and NFPA-70, and shall be Listed by and bear the label of Underwriters’ Laboratories and Factory Mutual. The  
controller shall be Hubbell-Lexington Lxi1200 equipped with LXi logic.  
The controller shall be of the combined manual/automatic type and be furnished in a floor mounted drip-proof steel Type 2 enclosure  
with lifting eyes. The enclosure shall be red with a non-glare surface. The controller shall be designed, tested, and marked for the  
rated horsepower, 3-phase voltage and frequency in a 40 degree C. ambient.  
All electrical components shall be accessible from the front for maintenance and service. No components or component wiring shall  
be permitted on the door of the enclosure. The controller shall have a common operating handle for both the line isolating switch and  
the controller circuit breaker mounted in the enclosure flange. The minimum withstand rating for the fire pump controller shall be  
150,000 amps RMS symmetrical at 200-600volts. The unit shall be Listed/Approved with UL/FM as “Suitable For Use as Service  
Equipment”.  
The controller shall have separate and independent pressure settings with a minimum run timer capable of being set for 10 minutes.  
Start and stop pressure settings shall be established at the time of the field acceptance test. Provisions shall be included to allow for  
manual or automatic shutdown in the field.  
The controller shall have two sets of Form “C” contacts for Pump Running, Phase Reversal, Power/Phase Failure, and one set of Form  
“C” contacts for Trouble. The Trouble contacts shall be activated by the following conditions: Invalid Configuration Memory,  
Emergency Manual Start, Pump Running, Phase Failure, Phase Reversal, Overload, Locked Rotor, Fail-to-Start, and Lockout.  
The controller shall be equipped with LXi intelligent fire pump control system logic. All firmware shall be non-volatile flash based  
CPLD ( complex-programmable logic device). The boot-up time for the logic shall be 3 seconds or less. Controllers that do not boot-  
up and allow the pump to be started in 3 seconds or less are not acceptable. An RS232 serial port shall be supplied for downloading  
event history to a PC for analysis and printing.  
The digital pressure readings and settings shall be displayed on the LXi LCD mounted on the enclosure flange. The LCD screen shall  
be 4 x 20 (4 lines of 20 characters) per screen, with screens that may be scrolled to give a total of 320 characters. The display shall  
provide simultaneous 3-phase digital amps and volts for the pump power and a digital reading for the system pressure. Controllers that  
do not simultaneously display digital 3-phase amps, line-to-line voltage readings, and system pressure are not acceptable.  
The event alarm caches shall be compartmentalized and no compartment shall over-ride any other compartment. The compartments  
shall allow for analysis of four types of informational events without having to look through all events including those not related to a  
problem. Events shall be shown with Date and Time for each event occurrence as follows:  
1.  
2.  
3.  
4.  
Events that have occurred during a pump idle period  
Events that occurred during the last start period  
Events that occurred during the last run period  
Events that occurred during the last stop period.  
The LED displays shall be mounted on the enclosure flange and have an LED for the following:  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
Power Available  
Low Suction  
Pump Start Delay On  
Locked Rotor  
Pressure Switch Start  
Emergency Manual Start  
Fail to Start  
8.  
9.  
Phase Reversal  
Overload  
Local Manual Start  
Local Manual Stop  
Lockout On  
15.  
Remote Start  
10.  
11.  
12.  
13.  
14.  
Run Timer On  
Pump Running  
LED’s shall be multi-color; red for critical alarms, yellow for infomational and green for status.  
Programming of the LXi logic shall be from the touch pad mounted on the enclosure flange. Programming shall be password protected  
so that unauthorized personnel cannot change the logic functions. The fire pump controller shall be Model LXi1200 equipped with  
LXi Logic as manufactured by Hubbell Industrial Controls, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Car Seat ISPB004HB User Manual
Grizzly Lathe G4002 User Manual
Harbor Freight Tools Microscope Magnifier 54949 User Manual
Harbor Freight Tools Portable Generator 92863 User Manual
Harbor Freight Tools Work Light 91033 User Manual
Hasbro Motorized Toy Car 33392 User Manual
Heatiator Indoor Fireplace Rave4013i c User Manual
HP Hewlett Packard Waterskis E1312A User Manual
HP Hewlett Packard Welder 519819 001 User Manual
Image Hot Tub 83121007 User Manual