Hoshizaki America, Inc.
Hoshizaki
Stackable Crescent Cuber
Models
KM-1601SAH/3
KM-1601SWH/3
KM-1601SRH/3
SERVICE MANUAL
“A Superior Degree
of Reliability”
™
Number: 73145
Issued: 10-31-2006
Revised: 6-24-2011
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT
This manual should be read carefully before the icemaker is serviced or
maintenance operations are performed. Only qualified service technicians
should install, service, and maintain the icemaker. Read the warnings contained
in this booklet carefully as they give important information regarding safety.
Please retain this booklet for any further reference that may be necessary.
CONTENTS
Important Safety Information ................................................................................................. 5
I. Specifications...................................................................................................................... 6
A. Icemaker ....................................................................................................................... 6
B. Condenser Unit ........................................................................................................... 16
II. General Information......................................................................................................... 18
A. Construction................................................................................................................ 18
B. Sequence of Operation ............................................................................................... 21
1. Sequence Cycles and Shutdown .......................................................................... 21
a) KM-1601SAH/3 "G" Control Board................................................................... 21
b) KM-1601SWH/3 and KM-1601SRH/3 "E" Control Board.................................. 23
2. Sequence Flow Chart ........................................................................................... 25
a) KM-1601SAH/3 "G" Control Board................................................................... 25
b) KM-1601SWH/3 and KM-1601SRH/3 "E" Control Board.................................. 26
C. Control Board.............................................................................................................. 27
1. Control Board Layout ............................................................................................. 28
a) KM-1601SAH/3 "G" Control Board................................................................... 28
b) KM-1601SWH/3 and KM-1601SRH/3 "E" Control Board.................................. 29
2. LED Lights and Audible Alarm Safeties ................................................................. 30
a) KM-1601SAH/3 "G" Control Board................................................................... 30
b) KM-1601SWH/3 and KM-1601SRH/3 "E" Control Board.................................. 31
3. Controls and Adjustments...................................................................................... 32
a) Default Dip Switch Settings.............................................................................. 32
b) Harvest Timer (S4 dip switch 1 & 2)................................................................. 33
c) Pump-Out Timer (S4 dip switch 3 & 4)............................................................. 33
d) Pump-Out Frequency Control (S4 dip switch 5 & 6)......................................... 34
e) Harvest Pump Timer/Bin Control Selector (S4 dip switch 7)............................ 34
f) Factory Use (S4 dip switch 8)........................................................................... 35
g) Freeze Timer (S4 dip switch 9 & 10) ................................................................ 35
h) Float Switch Selector (S5 dip switch 1), KM-1601SAH/3 "G" Control Board.... 35
i) Refill Counter (S5 dip switch 2 through 5), KM-1601SAH/3 "G" Control Board. 35
D. Control Switch ............................................................................................................. 36
III. Technical Information...................................................................................................... 37
A. Water Circuit and Refrigeration Circuit........................................................................ 37
1. KM-1601SAH/3 (air-cooled).................................................................................... 37
2. KM-1601SWH/3 (water-cooled) ............................................................................. 38
3. KM-1601SRH/3 (remote air-cooled)....................................................................... 39
3
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Wiring Diagrams.......................................................................................................... 40
1. KM-1601SAH (air-cooled)....................................................................................... 40
2. KM-1601SAH3 (air-cooled).................................................................................... 41
3. KM-1601SWH (water-cooled), KM-1601SRH (remote air-cooled) ......................... 42
4. KM-1601SWH3 (water-cooled), KM-1601SRH3 (remote air-cooled) ..................... 43
C. Performance Data ....................................................................................................... 44
IV. Service Diagnosis........................................................................................................... 54
A. Diagnostic Procedure ................................................................................................. 54
B. Control Board Check................................................................................................... 58
C. Bin Control Check ....................................................................................................... 59
D. Float Switch Check and Cleaning ............................................................................... 60
1. Float Switch Check ................................................................................................ 60
2. Float Switch Cleaning............................................................................................ 61
E. Thermistor Check........................................................................................................ 62
F. Adjustment of Water Regulating Valve (water-cooled model) ...................................... 62
G. Diagnostic Charts ....................................................................................................... 63
1. No Ice Production................................................................................................... 63
2. Freeze Up.............................................................................................................. 65
3. Low Ice Production ................................................................................................ 66
V. Replacement of Components .......................................................................................... 68
A. Service for Refrigerant Lines....................................................................................... 68
1. Refrigerant Recovery ............................................................................................. 68
2. Brazing .................................................................................................................. 69
3. Evacuation and Recharge (R-404A)...................................................................... 69
B. Important Notes for Component Replacement............................................................ 71
VI. Cleaning and Maintenance............................................................................................. 72
A. Cleaning and Sanitizing Instructions........................................................................... 72
1. Cleaning Procedure................................................................................................ 73
2. Sanitizing Procedure - Following Cleaning Procedure............................................74
B. Maintenance................................................................................................................ 75
C. Preparing the Icemaker for Long Storage ................................................................... 75
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Important Safety Information
Throughout this manual, notices appear to bring your attention to situations which could
result in death, serious injury, or damage to the unit.
WARNING
Indicates a hazardous situation which could result in death or
serious injury.
CAUTION
IMPORTANT
Indicates a situation which could result in damage to the unit.
Indicates important information about the use and care of the
unit.
WARNING
This icemaker should be destined only to the use for which it has been
expressly conceived. Any other use should be considered improper and
therefore dangerous. The manufacturer cannot be held responsible for injury or
damage resulting from improper, incorrect, and unreasonable use.
To reduce the risk of death, electric shock, serious injury, or fire, follow
basic precautions including the following:
• Only qualified service technicians should install, service, and maintain the
icemaker.
• Electrical connection must be hard wired and must meet national, state, and
local electrical code requirements. Failure to meet these code requirements
could result in death, electric shock, serious injury, fire, or severe damage to
equipment.
• This unit requires an independent power supply. See the nameplate for
proper voltage and breaker/fuse size. Failure to use a proper breaker or fuse
can result in a tripped breaker, blown fuse, or damage to existing wiring. This
could lead to heat generation or fire.
• THE ICEMAKER MUST BE GROUNDED. Failure to properly ground the
icemaker could result in death or serious injury.
• Move the control switch to the "OFF" position and turn off the power supply
before servicing. Lockout/Tagout to prevent the power supply from being
turned back on inadvertently.
• Do not make any alterations to the unit. Alterations could result in electric
shock, injury, fire, or damage to the unit.
Additional Warning for Remote Air-Cooled Model
• THE REMOTE CONDENSER UNIT MUST BE GROUNDED. The power
supply and ground wire to the remote condenser unit are supplied from the
icemaker. Failure to properly ground the remote condenser unit could result
in death or serious injury.
• Move the icemaker control switch to the "OFF" position and turn off the power
supply to the icemaker before servicing the remote condenser unit.
Lockout/Tagout to prevent the power supply from being turned back on
inadvertently.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
I. Specifications
A. Icemaker
1. KM-1601SAH (air-cooled)
AC SUPPLY VOLTAGE
AMPERAGE
208-230/60/1 (3 wire with neutral for 115V)
15.0 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY
MAXIMUM FUSE SIZE
APPROXIMATE ICE PRODUCTION
PER 24 HR.
20 A
20 A
Ambient
WATER TEMP. (°F)
70
Temp.(°F)
50
90
lbs./day ( kg/day )
Reference without *marks
70
80
90
100
*1462 (663)
1435 (651)
1427 (647)
1379 (625)
1427 (647)
1381 (627)
*1343 (609)
1309 (594)
1307 (593)
1221 (554)
1198 (543)
1064 (483)
SHAPE OF ICE
Crescent Cube
ICE PRODUCTION PER CYCLE
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W (kWH/100 lbs.)
WATER gal./24HR (gal./100 lbs.)
CEC/CEE TIER LEVEL
31.4 lbs. (14.3 kg) 1440pcs.
N/A
90/70°F
2630(4.70)
228(17.0)
2
70/50°F
2450(4.03)
709(48.5)
ENERGY STAR
YES
EXTERIOR DIMENSIONS (WxDxH)
EXTERIOR FINISH
WEIGHT
CONNECTIONS - ELECTRIC
- WATER SUPPLY
48" x 27-3/8" x 27-3/8" (1219 x 695 x 695 mm)
Stainless Steel, Galvanized Steel (Rear)
Net 275 lbs. (125 kg), Shipping 315 lbs. (143 kg)
Permanent - Connection
Inlet
1/2" FPT
- DRAIN
Outlet
3/4" FPT
- CONDENSATE DRAIN
CUBE CONTROL SYSTEM
HARVESTING CONTROL SYSTEM
ICE MAKING WATER CONTROL
COOLING WATER CONTROL
BIN CONTROL SYSTEM
COMPRESSOR
3/8" OD Tube
Float Switch
Hot Gas and Water, Thermistor and Timer
Timer Controlled. Overflow Pipe
N/A
Thermostat
Hermetic, Model CS18K6E-PFV-237
Air-Cooled , Fin and tube type
Vertical type, Stainless Steel and Copper
Thermostatic Expansion Valve
R404A, 3 lb. 12.5 oz. (1715g)
High 467PSIG, Low 230PSIG
High Voltage Cut-out ( Internal )
Auto-reset Overload Protector ( Internal )
Auto-reset High Pressure Control Switch
Float Switch
CONDENSER
EVAPORATOR
REFRIGERANT CONTROL
REFRIGERANT CHARGE
DESIGN PRESSURE
P.C. BOARD CIRCUIT PROTECTION
COMPRESSOR PROTECTION
REFRIGERANT CIRCUIT PROTECTION
LOW WATER PROTECTION
ACCESSORIES -SUPPLIED
-REQUIRED
N/A
Ice Storage Bin
OPERATING CONDITIONS
VOLTAGE RANGE
AMBIENT TEMP.
187 - 253 V
45 -100° F
WATER SUPPLY TEMP.
WATER SUPPLY PRESSURE
45 - 90° F
10 - 113 PSIG
Note: We reserve the right to make changes in specifications and design without prior
notice.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
2. KM-1601SAH3 (air-cooled)
AC SUPPLY VOLTAGE
AMPERAGE
208-230/60/3
12.0 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY
MAXIMUM FUSE SIZE
APPROXIMATE ICE PRODUCTION
PER 24 HR.
20 A
20 A
Ambient
WATER TEMP. (°F)
70
Temp.(°F)
50
90
lbs./day ( kg/day )
Reference without *marks
70
80
90
100
*1456 (660)
1431 (649)
1423 (646)
1379 (626)
1423 (646)
1381 (626)
*1345 (610)
1314 (596)
1313 (596)
1234 (560)
1211 (549)
1088 (494)
SHAPE OF ICE
Crescent Cube
ICE PRODUCTION PER CYCLE
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W (kWH/100 lbs.)
WATER gal./24HR (gal./100 lbs.)
CEC/CEE TIER LEVEL
32.5 lbs. (14.8 kg) 1440pcs.
N/A
90/70°F
2610(4.65)
249(18.5)
3
70/50°F
2370(3.91)
708(48.6)
ENERGY STAR
YES
EXTERIOR DIMENSIONS (WxDxH)
EXTERIOR FINISH
WEIGHT
CONNECTIONS - ELECTRIC
- WATER SUPPLY
48" x 27-3/8" x 27-3/8" (1219 x 695 x 695 mm)
Stainless Steel, Galvanized Steel (Rear)
Net 275 lbs. (125 kg), Shipping 315 lbs. (143 kg)
Permanent - Connection
Inlet
1/2" FPT
- DRAIN
Outlet
3/4" FPT
- CONDENSATE DRAIN
CUBE CONTROL SYSTEM
HARVESTING CONTROL SYSTEM
ICE MAKING WATER CONTROL
COOLING WATER CONTROL
BIN CONTROL SYSTEM
COMPRESSOR
3/8" OD Tube
Float Switch
Hot Gas and Water, Thermistor and Timer
Timer Controlled. Overflow Pipe
N/A
Thermostat
Hermetic, Model CS18K6E-TF5-237
Air-Cooled, Fin and tube type
Vertical type, Stainless Steel and Copper
Thermostatic Expansion Valve
R404A, 3 lb. 12.5 oz. (1715g)
High 467PSIG, Low 230PSIG
High Voltage Cut-out ( Internal )
Auto-reset Overload Protector ( Internal )
Auto-reset High Pressure Control Switch
Float Switch
CONDENSER
EVAPORATOR
REFRIGERANT CONTROL
REFRIGERANT CHARGE
DESIGN PRESSURE
P.C. BOARD CIRCUIT PROTECTION
COMPRESSOR PROTECTION
REFRIGERANT CIRCUIT PROTECTION
LOW WATER PROTECTION
ACCESSORIES -SUPPLIED
-REQUIRED
N/A
Ice Storage Bin
OPERATING CONDITIONS
VOLTAGE RANGE
AMBIENT TEMP.
187 - 253 V
45 -100° F
WATER SUPPLY TEMP.
WATER SUPPLY PRESSURE
45 - 90° F
10 - 113 PSIG
Note: We reserve the right to make changes in specifications and design without prior
notice.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
3. KM-1601SWH (water-cooled)
AC SUPPLY VOLTAGE
AMPERAGE
208-230/60/1 (3 wire with neutral for 115V)
13.4 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY
MAXIMUM FUSE SIZE
APPROXIMATE ICE PRODUCTION
PER 24 HR.
20 A
20 A
Ambient
WATER TEMP. (°F)
70
Temp.(°F)
50
90
lbs./day ( kg/day )
Reference without *marks
70
80
90
100
*1492 (677)
1499 (680)
1501 (681)
1453 (659)
1501 (681)
1513 (686)
*1523 (691)
1496 (679)
1419 (643)
1378 (625)
1408 (639)
1303 (591)
SHAPE OF ICE
Crescent Cube
ICE PRODUCTION PER CYCLE
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W (kWH/100 lbs.)
WATER gal./24HR (gal./100 lbs.)
WATER COOLED CONDENSER
gal./24HR (gal./100 lbs.)
EXTERIOR DIMENSIONS (WxDxH)
EXTERIOR FINISH
30.2 lbs. (13.7 kg) 1440 pcs.
N/A
90/70°F
2410(3.8)
373(24.5)
1493(98)
70/50°F
2300(3.7)
698(46.8)
930(62)
48" x 27-3/8" x 27-3/8" (1219 x 695 x 695 mm)
Stainless Steel, Galvanized Steel (Rear)
WEIGHT
Net 310 lbs. ( 141 kg ), Shipping 360 lbs. ( 163 kg )
Permanent - Connection
CONNECTIONS - ELECTRIC
- WATER SUPPLY
Inlet
1/2" FPT
Condenser Inlet 1/2" FPT
Condenser Outlet 3/8" FPT
- DRAIN
Outlet
3/4" FPT
3/8" OD Tube
CUBE CONTROL SYSTEM
HARVESTING CONTROL SYSTEM
ICE MAKING WATER CONTROL
COOLING WATER CONTROL
BIN CONTROL SYSTEM
COMPRESSOR
Float Switch
Hot Gas and Water, Thermistor and Timer
Timer Controlled. Overflow Pipe
Water Regulating Valve
Thermostat
Hermetic, Model CS18K6E-PFV-237
Water-cooled, Tube in tube type
Vertical type, Stainless Steel and Copper
Thermostatic Expansion Valve
R-404A, 3 lbs. 1 oz. ( 1400g )
High 427PSIG, Low 230PSIG
High Voltage Cut-out ( Internal )
Auto-reset Overload Protector ( Internal )
Auto-reset High Pressure Control Switch
Float Switch
CONDENSER
EVAPORATOR
REFRIGERANT CONTROL
REFRIGERANT CHARGE
DESIGN PRESSURE
P.C. BOARD CIRCUIT PROTECTION
COMPRESSOR PROTECTION
REFRIGERANT CIRCUIT PROTECTION
LOW WATER PROTECTION
ACCESSORIES -SUPPLIED
-REQUIRED
N/A
Ice Storage Bin
OPERATING CONDITIONS
VOLTAGE RANGE
AMBIENT TEMP.
187 - 253 V
45 -100° F
WATER SUPPLY TEMP.
WATER SUPPLY PRESSURE
45 - 90° F
10 - 113 PSIG
Note: We reserve the right to make changes in specifications and design without prior
notice.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
4. KM-1601SWH3 (water-cooled)
AC SUPPLY VOLTAGE
AMPERAGE
208-230/60/3
9.0 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY
MAXIMUM FUSE SIZE
APPROXIMATE ICE PRODUCTION
PER 24 HR.
20 A
20 A
Ambient
WATER TEMP. (°F)
Temp.(°F)
50
70
90
lbs./day ( kg/day )
Reference without *marks
70
80
90
100
*1555 (705)
1557 (706)
1558 (707)
1507 (684)
1558 (707)
1562 (708)
*1565 (710)
1536 (697)
1466 (665)
1417 (643)
1440 (653)
1326 (601)
SHAPE OF ICE
Crescent Cube
ICE PRODUCTION PER CYCLE
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W (kWH/100 lbs.)
WATER gal./24HR (gal./100 lbs.)
WATER COOLED CONDENSER
gal./24HR (gal./100 lbs.)
CEC/CEE TIER LEVEL
30.2 lbs. (13.7 kg) 1440 pcs.
N/A
90/70°F
2390(3.66)
372(23.8)
1565(100)
70/50°F
2270(3.5)
804(51.7)
910(59)
2
ENERGY STAR
N/A
EXTERIOR DIMENSIONS (WxDxH)
EXTERIOR FINISH
48" x 27-3/8" x 27-3/8" (1219 x 695 x 695 mm)
Stainless Steel, Galvanized Steel (Rear)
WEIGHT
Net 310 lbs. ( 141 kg ), Shipping 360 lbs. ( 163 kg )
Permanent - Connection
CONNECTIONS - ELECTRIC
- WATER SUPPLY
Inlet
1/2" FPT
Condenser Inlet 1/2" FPT
Condenser Outlet 3/8" FPT
- DRAIN
Outlet
3/4" FPT
3/8" OD Tube
CUBE CONTROL SYSTEM
HARVESTING CONTROL SYSTEM
ICE MAKING WATER CONTROL
COOLING WATER CONTROL
BIN CONTROL SYSTEM
COMPRESSOR
Float Switch
Hot Gas and Water, Thermistor and Timer
Timer Controlled. Overflow Pipe
Water Regulating Valve
Thermostat
Hermetic, Model CS18K6E-TF5-237
Water-cooled, Tube in tube type
Vertical type, Stainless Steel and Copper
Thermostatic Expansion Valve
R-404A, 3 lbs. 1 oz. ( 1400g )
High 427PSIG, Low 230PSIG
High Voltage Cut-out ( Internal )
Auto-reset Overload Protector ( Internal )
Auto-reset High Pressure Control Switch
Float Switch
CONDENSER
EVAPORATOR
REFRIGERANT CONTROL
REFRIGERANT CHARGE
DESIGN PRESSURE
P.C. BOARD CIRCUIT PROTECTION
COMPRESSOR PROTECTION
REFRIGERANT CIRCUIT PROTECTION
LOW WATER PROTECTION
ACCESSORIES -SUPPLIED
-REQUIRED
N/A
Ice Storage Bin
OPERATING CONDITIONS
VOLTAGE RANGE
AMBIENT TEMP.
187 - 253 V
45 -100° F
WATER SUPPLY TEMP.
WATER SUPPLY PRESSURE
45 - 90° F
10 - 113 PSIG
Note: We reserve the right to make changes in specifications and design without prior
notice.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
5. KM-1601SRH with URC-21F (remote air-cooled) (auxiliary codes: R-0; R-1; some S-1)
This data applies to units with an 8 l/min water valve. The 8 l/min water valve is part
number 3U0111-02 and has J248-032 stamped on the side of the valve facing the rear of
the unit.
AC SUPPLY VOLTAGE
AMPERAGE
208-230/60/1 (3 wire with neutral for 115V)
12.8 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY
MAXIMUM FUSE SIZE
APPROXIMATE ICE PRODUCTION
PER 24 HR.
20 A
20 A
Ambient
WATER TEMP. (°F)
70
Temp.(°F)
50
90
lbs./day ( kg/day )
Reference without *marks
70
80
90
100
*1583 (718)
1558 (707)
1550 (703)
1503 (682)
1550 (703)
1507 (684)
*1472 (668)
1439 (653)
1435 (651)
1353 (614)
1332 (604)
1203 (546)
SHAPE OF ICE
Crescent Cube
ICE PRODUCTION PER CYCLE
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W (kWH/100 lbs.)
WATER gal./24HR (gal./100 lbs.)
EXTERIOR DIMENSIONS (WxDxH)
EXTERIOR FINISH
29.4 lbs. (13.3 kg) 1440 pcs.
N/A
90/70°F
2640(4.3)
255(17.3)
70/50°F
2440(3.7)
503(31.8)
48" x 27 3/8" x 27 3/8" (1219 x 695 x 695 mm)
Stainless Steel, Galvanized Steel (Rear)
Net 275 lbs. (125 kg), Shipping 350 lbs. (159 kg)
Permanent - Connection
WEIGHT
CONNECTIONS - ELECTRIC
- WATER SUPPLY
Inlet
1/2" FPT
- DRAIN
Outlet
3/4" FPT
- CONDENSATE DRAIN
CUBE CONTROL SYSTEM
HARVESTING CONTROL SYSTEM
ICE MAKING WATER CONTROL
COOLING WATER CONTROL
BIN CONTROL SYSTEM
COMPRESSOR
CONDENSER
EVAPORATOR
REFRIGERANT CONTROL
3/8" OD Tube
Float Switch
Hot Gas and Water, Thermistor and Timer
Timer Controlled. Overflow Pipe
N/A
Thermostat
Hermetic, Model CS18K6E-PFV
Air-Cooled Remote, Condenser Unit URC-21F
Vertical type, Stainless Steel and Copper
Thermostatic Expansion Valve
Condensing Pressure Regulator on URC-21F
R404A, 24 lb. 14.6 oz. (11300g)
(Icemaker 15 lb. 3.4 oz. Cond. Unit 9 lb. 11.2 oz.)
High 467PSIG, Low 230PSIG
High Voltage Cut-out ( Internal )
Auto-reset Overload Protector ( Internal )
Auto-reset High Pressure Control Switch
Float Switch
REFRIGERANT CHARGE
DESIGN PRESSURE
P.C. BOARD CIRCUIT PROTECTION
COMPRESSOR PROTECTION
REFRIGERANT CIRCUIT PROTECTION
LOW WATER PROTECTION
ACCESSORIES -SUPPLIED
-REQUIRED
N/A
Ice Dispenser or Ice Storage Bin, Remote Condenser Unit
OPERATING CONDITIONS
VOLTAGE RANGE
187 - 253 V
AMBIENT TEMP.
WATER SUPPLY TEMP.
WATER SUPPLY PRESSURE
45 -100° F
45 - 90° F
10 - 113 PSIG
Note: We reserve the right to make changes in specifications and design without prior
notice.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
6. KM-1601SRH with URC-21F (remote air-cooled) (auxiliary codes: some S-1; S-2 and
later)
This data applies to units with a 15 l/min or 11 l/min water valve. The 15 l/min water valve
is part number 3U0111-01 and has J248-030 stamped on the side of the valve facing the
rear of the unit. The 11 l/min water valve is either part number 4A1176-04 or 4A5251-04
and has the part number stamped on the side of the valve facing the front of the unit.
AC SUPPLY VOLTAGE
AMPERAGE
208-230/60/1 (3 wire with neutral for 115V)
12.8 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY
MAXIMUM FUSE SIZE
APPROXIMATE ICE PRODUCTION
PER 24 HR.
20 A
20 A
Ambient
WATER TEMP. (°F)
70
Temp.(°F)
50
90
lbs./day ( kg/day )
Reference without *marks
70
80
90
100
*1564 (709)
1551 (703)
1547 (702)
1512 (686)
1547 (702)
1524 (691)
*1505 (683)
1482 (672)
1468 (666)
1415 (642)
1407 (638)
1317 (597)
SHAPE OF ICE
Crescent Cube
ICE PRODUCTION PER CYCLE
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W (kWH/100 lbs.)
WATER gal./24HR (gal./100 lbs.)
CEC/CEE TIER LEVEL
ENERGY STAR
31.2 lbs. (14.2 kg) 1440 pcs.
N/A
90/70°F
2700(4.30)
375(24.9)
2
70/50°F
2610(4.00)
785(50.2)
YES
EXTERIOR DIMENSIONS (WxDxH)
EXTERIOR FINISH
WEIGHT
CONNECTIONS - ELECTRIC
- WATER SUPPLY
48" x 27 3/8" x 27 3/8" (1219 x 695 x 695 mm)
Stainless Steel, Galvanized Steel (Rear)
Net 275 lbs. (125 kg), Shipping 350 lbs. (159 kg)
Permanent - Connection
Inlet
1/2" FPT
- DRAIN
Outlet
3/4" FPT
- CONDENSATE DRAIN
CUBE CONTROL SYSTEM
HARVESTING CONTROL SYSTEM
ICE MAKING WATER CONTROL
COOLING WATER CONTROL
BIN CONTROL SYSTEM
COMPRESSOR
CONDENSER
EVAPORATOR
REFRIGERANT CONTROL
3/8" OD Tube
Float Switch
Hot Gas and Water, Thermistor and Timer
Timer Controlled. Overflow Pipe
N/A
Thermostat
Hermetic, Model CS18K6E-PFV
Air-Cooled Remote, Condenser Unit URC-21F
Vertical type, Stainless Steel and Copper
Thermostatic Expansion Valve
Condensing Pressure Regulator on URC-21F
R404A, 24 lb. 14.6 oz. (11300g)
(Icemaker 15 lb. 3.4 oz. Cond. Unit 9 lb. 11.2 oz.)
High 467PSIG, Low 230PSIG
High Voltage Cut-out ( Internal )
Auto-reset Overload Protector ( Internal )
Auto-reset High Pressure Control Switch
Float Switch
REFRIGERANT CHARGE
DESIGN PRESSURE
P.C. BOARD CIRCUIT PROTECTION
COMPRESSOR PROTECTION
REFRIGERANT CIRCUIT PROTECTION
LOW WATER PROTECTION
ACCESSORIES -SUPPLIED
-REQUIRED
N/A
Ice Dispenser or Ice Storage Bin, Remote Condenser Unit
OPERATING CONDITIONS
VOLTAGE RANGE
187 - 253 V
AMBIENT TEMP.
WATER SUPPLY TEMP.
WATER SUPPLY PRESSURE
45 -100° F
45 - 90° F
10 - 113 PSIG
Note: We reserve the right to make changes in specifications and design without prior
notice.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
7. KM-1601SRH with URC-22F (remote air-cooled) (auxiliary codes: S-2 and later)
This data applies to units with an 11 l/min water valve. The 11 l/min water valve is either
part number 4A1176-04 or 4A5251-04 and has the part number stamped on the side of
the valve facing the front of the unit.
AC SUPPLY VOLTAGE
AMPERAGE
208-230/60/1 (3 wire with neutral for 115V)
12.8 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY
MAXIMUM FUSE SIZE
APPROXIMATE ICE PRODUCTION
PER 24 HR.
20 A
20 A
Ambient
WATER TEMP. (°F)
70
Temp.(°F)
50
90
lbs./day ( kg/day )
Reference without *marks
70
80
90
100
*1531 (694)
1522 (690)
1519 (689)
1475 (669)
1519 (689)
1503 (682)
*1490 (676)
1462 (663)
1426 (647)
1368 (620)
1371 (622)
1261 (572)
SHAPE OF ICE
Crescent Cube
ICE PRODUCTION PER CYCLE
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W (kWH/100 lbs.)
WATER gal./24HR (gal./100 lbs.)
CEC/CEE TIER LEVEL
ENERGY STAR
31.6 lbs. (14.3 kg) 1440 pcs.
N/A
90/70°F
2710(4.36)
352(23.6)
2
70/50°F
2560(4.01)
755(49.3)
YES
EXTERIOR DIMENSIONS (WxDxH)
EXTERIOR FINISH
WEIGHT
CONNECTIONS - ELECTRIC
- WATER SUPPLY
48" x 27 3/8" x 27 3/8" (1219 x 695 x 695 mm)
Stainless Steel, Galvanized Steel (Rear)
Net 275 lbs. (125 kg), Shipping 350 lbs. (159 kg)
Permanent - Connection
Inlet
1/2" FPT
- DRAIN
Outlet
3/4" FPT
- CONDENSATE DRAIN
CUBE CONTROL SYSTEM
HARVESTING CONTROL SYSTEM
ICE MAKING WATER CONTROL
COOLING WATER CONTROL
BIN CONTROL SYSTEM
COMPRESSOR
CONDENSER
EVAPORATOR
REFRIGERANT CONTROL
3/8" OD Tube
Float Switch
Hot Gas and Water, Thermistor and Timer
Timer Controlled. Overflow Pipe
N/A
Thermostat
Hermetic, Model CS18K6E-PFV
Air-Cooled Remote, Condenser Unit URC-22F
Vertical type, Stainless Steel and Copper
Thermostatic Expansion Valve
Condensing Pressure Regulator on URC-22F
R404A, 22 lb. 14.8 oz. (10400g)
(Icemaker 15 lb. 3.4 oz. Cond. Unit 7 lb. 11.5 oz.)
High 467PSIG, Low 230PSIG
High Voltage Cut-out ( Internal )
Auto-reset Overload Protector ( Internal )
Auto-reset High Pressure Control Switch
Float Switch
REFRIGERANT CHARGE
DESIGN PRESSURE
P.C. BOARD CIRCUIT PROTECTION
COMPRESSOR PROTECTION
REFRIGERANT CIRCUIT PROTECTION
LOW WATER PROTECTION
ACCESSORIES -SUPPLIED
-REQUIRED
N/A
Ice Dispenser or Ice Storage Bin, Remote Condenser Unit
OPERATING CONDITIONS
VOLTAGE RANGE
187 - 253 V
AMBIENT TEMP.
WATER SUPPLY TEMP.
WATER SUPPLY PRESSURE
45 -100° F
45 - 90° F
10 - 113 PSIG
Note: We reserve the right to make changes in specifications and design without prior
notice.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
8. KM-1601SRH3 with URC-21F (remote air-cooled) (auxiliary codes:R-0;R-1;some S-1)
This data applies to units with an 8 l/min water valve. The 8 l/min water valve is part
number 3U0111-02 and has J248-032 stamped on the side of the valve facing the rear of
the unit.
AC SUPPLY VOLTAGE
AMPERAGE
208-230/60/3
7.9 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY
MAXIMUM FUSE SIZE
APPROXIMATE ICE PRODUCTION
PER 24 HR.
20 A
20 A
Ambient
WATER TEMP. (°F)
Temp.(°F)
50
70
90
lbs./day ( kg/day )
Reference without *marks
70
80
90
100
*1596 (724)
1565 (710)
1556 (706)
1510 (685)
1556 (706)
1503 (682)
*1459 (662)
1426 (647)
1436 (651)
1347 (611)
1316 (597)
1184 (537)
SHAPE OF ICE
Crescent Cube
ICE PRODUCTION PER CYCLE
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W (kWH/100 lbs.)
WATER gal./24HR (gal./100 lbs.)
EXTERIOR DIMENSIONS (WxDxH)
EXTERIOR FINISH
29.4 lbs. (13.3 kg) 1440 pcs.
N/A
90/70°F
2580(4.3)
261(17.9)
70/50°F
2450(3.7)
504(31.6)
48" x 27 3/8" x 27 3/8" (1219 x 695 x 695 mm)
Stainless Steel, Galvanized Steel (Rear)
Net 275 lbs. (125 kg), Shipping 350 lbs. (159 kg)
Permanent - Connection
WEIGHT
CONNECTIONS - ELECTRIC
- WATER SUPPLY
Inlet
1/2" FPT
- DRAIN
Outlet
3/4" FPT
- CONDENSATE DRAIN
CUBE CONTROL SYSTEM
HARVESTING CONTROL SYSTEM
ICE MAKING WATER CONTROL
COOLING WATER CONTROL
BIN CONTROL SYSTEM
COMPRESSOR
CONDENSER
EVAPORATOR
REFRIGERANT CONTROL
3/8" OD Tube
Float Switch
Hot Gas and Water, Thermistor and Timer
Timer Controlled. Overflow Pipe
N/A
Thermostat
Hermetic, Model CS18K6E-TF5
Air-Cooled Remote, Condenser Unit URC-21F
Vertical type, Stainless Steel and Copper
Thermostatic Expansion Valve
Condensing Pressure Regulator on URC-21F
R404A, 24 lb. 14.6 oz. (11300g)
(Icemaker 15 lb. 3.4 oz. Cond. Unit 9 lb. 11.2 oz.)
High 467PSIG, Low 230PSIG
High Voltage Cut-out ( Internal )
Auto-reset Overload Protector ( Internal )
Auto-reset High Pressure Control Switch
Float Switch
REFRIGERANT CHARGE
DESIGN PRESSURE
P.C. BOARD CIRCUIT PROTECTION
COMPRESSOR PROTECTION
REFRIGERANT CIRCUIT PROTECTION
LOW WATER PROTECTION
ACCESSORIES -SUPPLIED
-REQUIRED
N/A
Ice Dispenser or Ice Storage Bin, Remote Condenser Unit
OPERATING CONDITIONS
VOLTAGE RANGE
187 - 253 V
AMBIENT TEMP.
WATER SUPPLY TEMP.
WATER SUPPLY PRESSURE
45 -100° F
45 - 90° F
10 - 113 PSIG
Note: We reserve the right to make changes in specifications and design without prior
notice.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
9. KM-1601SRH3 with URC-21F (remote air-cooled) (auxiliary codes: some S-1; S-2 and
later)
This data applies to units with a 15 l/min or 11 l/min water valve. The 15 l/min water valve
is part number 3U0111-01 and has J248-030 stamped on the side of the valve facing the
rear of the unit. The 11 l/min water valve is either part number 4A1176-04 or 4A5251-04
and has the part number stamped on the side of the valve facing the front of the unit.
AC SUPPLY VOLTAGE
AMPERAGE
208-230/60/3
7.9 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY
MAXIMUM FUSE SIZE
APPROXIMATE ICE PRODUCTION
PER 24 HR.
20 A
20 A
Ambient
WATER TEMP. (°F)
Temp.(°F)
50
70
90
lbs./day ( kg/day )
Reference without *marks
70
80
90
100
*1585 (719)
1568 (711)
1563 (709)
1520 (689)
1563 (709)
1535 (696)
*1511 (685)
1482 (672)
1464 (664)
1396 (633)
1387 (629)
1273 (577)
SHAPE OF ICE
Crescent Cube
ICE PRODUCTION PER CYCLE
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W (kWH/100 lbs.)
WATER gal./24HR (gal./100 lbs.)
CEC/CEE TIER LEVEL
ENERGY STAR
31.2 lbs. (14.2 kg) 1440 pcs.
N/A
90/70°F
2960(4.70)
363(24.0)
1
70/50°F
2580(3.90)
781(49.3)
NO
EXTERIOR DIMENSIONS (WxDxH)
EXTERIOR FINISH
WEIGHT
CONNECTIONS - ELECTRIC
- WATER SUPPLY
48" x 27 3/8" x 27 3/8" (1219 x 695 x 695 mm)
Stainless Steel, Galvanized Steel (Rear)
Net 275 lbs. (125 kg), Shipping 350 lbs. (159 kg)
Permanent - Connection
Inlet
1/2" FPT
- DRAIN
Outlet
3/4" FPT
- CONDENSATE DRAIN
CUBE CONTROL SYSTEM
HARVESTING CONTROL SYSTEM
ICE MAKING WATER CONTROL
COOLING WATER CONTROL
BIN CONTROL SYSTEM
COMPRESSOR
CONDENSER
EVAPORATOR
REFRIGERANT CONTROL
3/8" OD Tube
Float Switch
Hot Gas and Water, Thermistor and Timer
Timer Controlled. Overflow Pipe
N/A
Thermostat
Hermetic, Model CS18K6E-TF5
Air-Cooled Remote, Condenser Unit URC-21F
Vertical type, Stainless Steel and Copper
Thermostatic Expansion Valve
Condensing Pressure Regulator on URC-21F
R404A, 24 lb. 14.6 oz. (11300g)
(Icemaker 15 lb. 3.4 oz. Cond. Unit 9 lb. 11.2 oz.)
High 467PSIG, Low 230PSIG
High Voltage Cut-out ( Internal )
Auto-reset Overload Protector ( Internal )
Auto-reset High Pressure Control Switch
Float Switch
REFRIGERANT CHARGE
DESIGN PRESSURE
P.C. BOARD CIRCUIT PROTECTION
COMPRESSOR PROTECTION
REFRIGERANT CIRCUIT PROTECTION
LOW WATER PROTECTION
ACCESSORIES -SUPPLIED
-REQUIRED
N/A
Ice Dispenser or Ice Storage Bin, Remote Condenser Unit
OPERATING CONDITIONS
VOLTAGE RANGE
187 - 253 V
AMBIENT TEMP.
WATER SUPPLY TEMP.
WATER SUPPLY PRESSURE
45 -100° F
45 - 90° F
10 - 113 PSIG
Note: We reserve the right to make changes in specifications and design without prior
14
notice.
Download from Www.Somanuals.com. All Manuals Search And Download.
10. KM-1601SRH3 with URC-22F (remote air-cooled) (auxiliary codes: S-2 and later)
This data applies to units with an 11 l/min water valve. The 11 l/min water valve is either
part number 4A1176-04 or 4A5251-04 and has the part number stamped on the side of
the valve facing the front of the unit.
AC SUPPLY VOLTAGE
AMPERAGE
208-230/60/3
7.9 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY
MAXIMUM FUSE SIZE
APPROXIMATE ICE PRODUCTION
PER 24 HR.
20 A
20 A
Ambient
WATER TEMP. (°F)
Temp.(°F)
50
70
90
lbs./day ( kg/day )
Reference without *marks
70
80
90
100
*1530 (694)
1523 (691)
1521 (690)
1468 (666)
1521 (690)
1508 (684)
*1498 (679)
1465 (665)
1414 (641)
1349 (612)
1359 (616)
1231 (558)
SHAPE OF ICE
Crescent Cube
ICE PRODUCTION PER CYCLE
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W (kWH/100 lbs.)
WATER gal./24HR (gal./100 lbs.)
CEC/CEE TIER LEVEL
ENERGY STAR
32.1 lbs. (14.6 kg) 1440 pcs.
N/A
90/70°F
2780(4.46)
348(23.2)
2
70/50°F
2490(3.90)
704(46.0)
YES
EXTERIOR DIMENSIONS (WxDxH)
EXTERIOR FINISH
WEIGHT
CONNECTIONS - ELECTRIC
- WATER SUPPLY
48" x 27 3/8" x 27 3/8" (1219 x 695 x 695 mm)
Stainless Steel, Galvanized Steel (Rear)
Net 275 lbs. (125 kg), Shipping 350 lbs. (159 kg)
Permanent - Connection
Inlet
1/2" FPT
- DRAIN
Outlet
3/4" FPT
- CONDENSATE DRAIN
CUBE CONTROL SYSTEM
HARVESTING CONTROL SYSTEM
ICE MAKING WATER CONTROL
COOLING WATER CONTROL
BIN CONTROL SYSTEM
COMPRESSOR
CONDENSER
EVAPORATOR
REFRIGERANT CONTROL
3/8" OD Tube
Float Switch
Hot Gas and Water, Thermistor and Timer
Timer Controlled. Overflow Pipe
N/A
Thermostat
Hermetic, Model CS18K6E-TF5
Air-Cooled Remote, Condenser Unit URC-22F
Vertical type, Stainless Steel and Copper
Thermostatic Expansion Valve
Condensing Pressure Regulator on URC-22F
R404A, 22 lb. 14.8 oz. (10400g)
(Icemaker 15 lb. 3.4 oz. Cond. Unit 7 lb. 11.5 oz.)
High 467PSIG, Low 230PSIG
High Voltage Cut-out ( Internal )
Auto-reset Overload Protector ( Internal )
Auto-reset High Pressure Control Switch
Float Switch
REFRIGERANT CHARGE
DESIGN PRESSURE
P.C. BOARD CIRCUIT PROTECTION
COMPRESSOR PROTECTION
REFRIGERANT CIRCUIT PROTECTION
LOW WATER PROTECTION
ACCESSORIES -SUPPLIED
-REQUIRED
N/A
Ice Dispenser or Ice Storage Bin, Remote Condenser Unit
OPERATING CONDITIONS
VOLTAGE RANGE
187 - 253 V
AMBIENT TEMP.
WATER SUPPLY TEMP.
WATER SUPPLY PRESSURE
45 -100° F
45 - 90° F
10 - 113 PSIG
Note: We reserve the right to make changes in specifications and design without prior
notice.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Condenser Unit
1. URC-21F
AC SUPPLY VOLTAGE
FAN MOTOR
115/60/1 (Connection to Icemaker)
115 V Total 2.6FLA 130W
EXTERIOR DIMENSIONS (WxDxH)
DIMENSIONS INCLUDING LEGS (WxDxH)
EXTERIOR FINISH
46-3/8" x 15-11/16" x 25-15/16" (1178 x 398 x 659 mm)
48-7/16" x 18-1/8" x 40-7/8" (1230 x 460 x 1039 mm)
Galvanized Steel
WEIGHT
Net 158 lbs. ( 72 kg )
Shipping 169 lbs. ( 77 kg )
CONNECTIONS - ELECTRIC
- REFRIGERANT
Permanent - Connection
Discharge Line 1-1/16"-12 UNF Fitting (#10 PARKER)
Liquid Line 5/8"-18 UNF Fitting (#6 PARKER)
CONDENSER
Air-cooled, Fin and tube type
Thermal Protection
FAN MOTOR PROTECTION
REFRIGERANT CONTROL
REFRIGERANT CHARGE
DESIGN PRESSURE
Condensing Pressure Regulator
R-404A
9 lb. 11oz.
(4400g)
High 467 PSIG
VOLTAGE RANGE
AMBIENT TEMP.
Leg
32.2 Bar
OPERATING CONDITIONS
104 ~ 127 V
-20 ~ 122 °F
ACCESSORIES -SUPPLIED
2 pcs
8 pcs
8 pcs
Hex. Head Bolt w/Washer 8 x 16
Hex. Nut
8
Note: We reserve the right to make changes in specifications and design without prior
notice.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
2. URC-22F
AC SUPPLY VOLTAGE
FAN MOTOR
115/60/1 (Connection to Icemaker)
115 V Total 2.6FLA 130W
EXTERIOR DIMENSIONS (WxDxH)
DIMENSIONS INCLUDING LEGS (WxDxH)
EXTERIOR FINISH
46-3/8" x 15-11/16" x 25-15/16" (1178 x 398 x 659 mm)
48-7/16" x 18-1/8" x 40-7/8" (1230 x 460 x 1039 mm)
Galvanized Steel
WEIGHT
Net 134 lbs. (61 kg )
Shipping 145 lbs. ( 66 kg )
CONNECTIONS - ELECTRIC
- REFRIGERANT
Permanent - Connection
Discharge Line 1-1/16"-12 UNF Fitting (#10 PARKER)
Liquid Line 5/8"-18 UNF Fitting (#6 PARKER)
CONDENSER
Air-cooled, Fin and tube type
Thermal Protection
FAN MOTOR PROTECTION
REFRIGERANT CONTROL
REFRIGERANT CHARGE
DESIGN PRESSURE
Condensing Pressure Regulator
R-404A
7 lb. 11.5 oz. (3500g)
High 467 PSIG
VOLTAGE RANGE
AMBIENT TEMP.
Leg
32.2 Bar
OPERATING CONDITIONS
104 ~ 127 V
-20 ~ 122 °F
ACCESSORIES -SUPPLIED
2 pcs
8 pcs
8 pcs
Hex. Head Bolt w/Washer 8 x 16
Hex. Nut
8
Note: We reserve the right to make changes in specifications and design without prior
notice.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
II. General Information
A. Construction
1. KM-1601SAH/3 (air-cooled)
Separators
Low-Side Service Valve
High-Side Service Valve
Spray Tubes
Inlet Water Valve
(WV)
Evaporator Assembly
Thermostatic Expansion Valves
(TXV)
Water Supply Inlet
Junction Box
Hot Gas Valve
(HGV)
Check Valves
Cube Guides
Air-Cooled
Condenser
Control Box
Fan Blade
Pump-Out
Check Valve
Water Pump
(PM)
Fan Motor
(FM)
Float Switch
(F/S)
Cleaning Valve
Drier
Compressor
(Comp)
Liquid Line Valve
(LLV)
Control Switch
Extension
Bracket
Transformer Box
KM-1601SAH3
Bin Control Thermostat
(TBC)
18
Download from Www.Somanuals.com. All Manuals Search And Download.
2. KM-1601SWH/3 (water-cooled)
Spray Tubes
Inlet Water Valve
(WV)
Low-Side Service Valve
High-Side Service Valve
Separators
Evaporator Assembly
Thermostatic Expansion Valves
(TXV)
Water Supply Inlet
Junction Box
Hot Gas Valve
(HGV)
Cube Guides
Check Valves
Water Regulating Valve
(WRV)
Pump-Out
Check Valve
Water Pump
(PM)
Float Switch
(F/S)
Water-Cooled
Condenser
Cleaning Valve
Compressor
(Comp)
Control Box
Drier
Extension
Bracket
Control Switch
Capacitor Box
Liquid Line Valve
(LLV)
Bin Control Thermostat
(TBC)
(KM-1601SWH)
Transformer Box
(KM-1601SWH3)
19
Download from Www.Somanuals.com. All Manuals Search And Download.
3. KM-1601SRH/3 (remote air-cooled)
Spray Tubes
Low-Side Service Valve
Inlet Water Valve
(WV)
Separators
High-Side Liquid Service Valve
High-Side Vapor Service Valve
Evaporator Assembly
Water Supply Inlet
Hot Gas Valve
(HGV)
Junction Boxes
Thermostatic Expansion Valves
(TXV)
Cleaning Valve
Check Valves
Pump-Out
Check Valve
Water Pump
(PM)
Receiver
Float Switch
(F/S)
Compressor
(Comp)
Control Box
Drier
Extension
Bracket
Control Switch
Bin Control Thermostat
(TBC)
Liquid Line Valve
(LLV)
Capacitor Box
(KM-1601SRH)
Transformer Box
(KM-1601SRH3)
20
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Sequence of Operation
1. Sequence Cycles and Shutdown
a) KM-1601SAH/3 "G" Control Board
IMPORTANT
KM-1601SAH/3 utilize a "G" control board and TBC. For KM-1601SAH/3
operation, the K4 jumper (4A4883G01) must be in place on the control board
RED K4 connector or the unit will not operate.
The steps in the sequence are as outlined below. When power is supplied, CB red
"POWER OK" LED and green "BC CLOSED" LED turn on. If red "POWER OK" LED is
off, clear ice away from TBC bulb in the storage bin area. If yellow "BC OPEN" LED is
on, the unit will not start. In this case check that CB has the K4 jumper in place on CB
RED K4 connector. There is a 5-second delay before startup. Note that the order of the
component LEDs from the outer edge of CB is 1, 4, 3, 2.
(1) 1-Minute Fill Cycle
LED 4 is on. WV and X11 relay energize and the 1-minute fill cycle begins. After
1 minute, CB checks for a closed F/S. If F/S is closed, the harvest cycle begins. If open,
WV remains energized through additional 1-minute fill cycles until water fills the water
tank and closes F/S. This serves as a low water safety to protect PM.
(2) Initial Harvest Cycle
LEDs 1, 4, and 2 are on. WV and X11 relay remain energized, Comp, FM, HGV, and
X10 relay energize. CB monitors the warming of the evaporator via the thermistor located
on the suction line. When the thermistor reaches 48°F (9°C), CB reads a 3.9 kΩ signal
from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch
1 & 2). The harvest timer has settings of 60, 90, 120, and 180 seconds. For details, see
"II.C.3.b) Harvest Timer (S4 dip switch 1 & 2)." WV is energized during harvest for a
maximum of 6 minutes or the length of harvest minus 0 or 50 seconds (harvest pump
timer (S4 dip switch 7)), whichever is shorter. CAUTION! Do not adjust S4 dip switch
7 out of the factory default position on this model. Adjustment outside of the
factory default position may result in damage to the icemaker. LED 4 turns off when
WV and X11 relay de-energize. LED 3 turns on and PM energizes and runs for the last
0 or 50 seconds of harvest depending on S4 dip switch 7 setting. This circulates water
over the evaporator for the last 0 or 50 seconds of harvest. PM is energized through
CB K1 ten-pin connector pin #5 (DBU wire) and the X10 relay. When the harvest timer
terminates, the harvest cycle is complete. CB checks the position of F/S and proceeds
to the freeze cycle if it is closed or calls for a 1-minute fill cycle if it is open. The minimum
total time allowed by CB for a complete harvest cycle is 2 minutes.
(3) Freeze Cycle
LED 1 is on. Comp and FM remain energized, PM energizes or remains energized
depending on harvest pump timer (S4 dip switch 7) setting. LLV energizes. HGV and
X10 relay de-energize. The unit is held in freeze by a 5-minute short cycle protection
timer (CB will not accept a signal from F/S during the first 5 minutes of freeze). After the
5-minute short cycle protection timer terminates, CB turns freeze termination over to F/S.
As ice builds on the evaporator, the water level in the water tank lowers. The freeze cycle
21
Download from Www.Somanuals.com. All Manuals Search And Download.
continues until F/S opens and terminates the cycle. There is a 15 second delay before CB
acknowledges an open F/S.
(4) Pump-Out Cycle
LEDs 1, 3, and 2 are on. LED 4 is on when S4 dip switch 3 & 4 are set to 3 off and 4 on.
For details, see "II.C.3.c) Pump-Out Timer (S4 dip switch 3 & 4)." CAUTION! Do not
adjust S4 dip switch 3 & 4 to 3 off and 4 on. Adjustment to this position on this
model prevents the pump motor from rotating in the pump-out direction. Comp and
FM remain energized, HGV energizes, WV energizes if S4 dip switch 3 off and 4 on. LLV
de-energizes. PM stops for 2 seconds then reverses, taking water from the bottom of the
water tank and forcing pressure against the pump-out check valve seat allowing water to
go through the pump-out check valve and down the drain. At the same time, water flows
through the small tube to power flush F/S. When the pump-out timer terminates, pump-
out is complete.
The first pump-out occurs after the 11th freeze cycle, then every 10th cycle thereafter.
The pump-out frequency control is factory set, and generally no adjustment is required.
However, where water quality is bad and the icemaker needs a pump-out more often, the
pump-out frequency can be adjusted. The pump-out frequency control (S4 dip switch 5 &
6) can be set to have a pump-out occur every cycle, or every 2, 5, or 10 cycles. Timing of
the first pump-out is dependent on S4 dip switch 5 & 6 settings. See the table below.
S4 Dip Switch Setting
Pump-Out
Frequency
1st Pump-Out
No. 5
OFF
ON
No. 6
OFF
OFF
ON
Every cycle
Every 2 cycles
Every 5 cycles
Every 10 cycles
After 2nd freeze cycle
After 3rd freeze cycle
After 6th freeze cycle
After 11th freeze cycle
OFF
ON
ON
(5) Harvest Cycle
Same as the initial harvest cycle. See "II.B.1.a)(2) Initial Harvest Cycle."
Note: Unit continues to cycle until TBC is satisfied or power is turned off. The unit always
restarts at the 1-minute fill cycle.
(6) Shutdown
When ice contacts TBC bulb (TBC open), TBC shuts down the unit within 10 seconds.
TBC is factory set, and generally no adjustment is required. However, adjustment may be
needed in some conditions, particularly at higher altitude locations.
Legend: CB–control board; Comp–compressor; FM–fan motor; F/S–float switch; HGV–hot
gas valve; LLV–liquid line valve; PM–pump motor; TBC–thermostatic bin control;
WV–inlet water valve
22
Download from Www.Somanuals.com. All Manuals Search And Download.
b) KM-1601SWH/3 and KM-1601SRH/3 "E" Control Board
IMPORTANT
KM-1601SWH/3 and KM-1601SRH/3 utilize an "E" control board and TBC.
The steps in the sequence are as outlined below. When power is supplied, CB red
"POWER OK" LED turns on. There is a 5-second delay before startup. Note that the
order of the component LEDs from the outer edge of CB is 1, 4, 3, 2.
(1) 1-Minute Fill Cycle
LED 4 is on. WV energizes and the 1-minute fill cycle begins. After 1 minute, CB
checks for a closed F/S. If F/S is closed, the harvest cycle begins. If open, WV remains
energized through additional 1-minute fill cycles until water fills the water tank and closes
F/S. This serves as a low water safety to protect PM.
(2) Initial Harvest Cycle
LEDs 1, 4, and 2 are on. WV remains energized, Comp, FMR, HGV energize. CB
monitors the warming of the evaporator via the thermistor located on the suction line.
When the thermistor reaches 48°F (9°C), CB reads a 3.9 kΩ signal from the thermistor
and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2). The harvest
timer has settings of 60, 90, 120, and 180 seconds. For details, see "II.C.3.b) Harvest
Timer (S4 dip switch 1 & 2)." WV is energized during harvest for a maximum of 6 minutes
or the length of harvest, whichever is shorter. LED 4 turns off when WV de-energizes.
When the harvest timer terminates, the harvest cycle is complete. CB checks the position
of F/S and proceeds to the next cycle if it is closed or calls for a 1-minute fill cycle if it is
open. The minimum total time allowed by CB for a complete harvest cycle is 2 minutes.
(3) Freeze Cycle
LED 1 is on. Comp and FMR remain energized, PM and LLV energize, HGV and WV
de-energize. The unit is held in freeze by a 5-minute short cycle protection timer (CB will
not accept a signal from F/S during the first 5 minutes of freeze). After the 5-minute short
cycle protection timer terminates, CB turns freeze termination over to F/S. As ice builds
on the evaporator, the water level in the water tank lowers. The freeze cycle continues
until F/S opens and terminates the cycle.
(4) Pump-Out Cycle
LEDs 1, 3, and 2 are on. LED 4 is on when S4 dip switch 3 & 4 are set to 3 off and
4 on. For details, see "II.C.3.c) Pump-Out Timer (S4 dip switch 3 & 4)." Comp and FMR
remain energized. HGV energizes. WV energizes if S4 dip switch 3 off and 4 on. LLV
de-energizes. PM stops for 2 seconds then reverses, taking water from the bottom of the
water tank and forcing pressure against the pump-out check valve seat allowing water to
go through the pump-out check valve and down the drain. At the same time, water flows
through the small tube to power flush F/S. When the pump-out timer terminates, the
pump-out is complete.
The first pump-out occurs after the 1st freeze cycle, then every 10th cycle thereafter. The
pump-out frequency is factory set, and generally no adjustment is required. However,
where water quality is bad and the icemaker needs a pump-out more often, the pump-out
frequency can be adjusted. The pump-out frequency control (S4 dip switch 5 & 6) can
be set to have a pump-out occur every cycle, or every 2, 5, or 10 cycles. For details, see
"II.C.3.d) Pump-Out Frequency Control (S4 dip switch 5 & 6)."
23
Download from Www.Somanuals.com. All Manuals Search And Download.
(5) Harvest Cycle
Same as the initial harvest cycle. See "II.B.1.b)(2) Initial Harvest Cycle."
Note: Unit continues to cycle until TBC is satisfied or power is turned off. The unit always
restarts at the 1-minute fill cycle.
(6) Shutdown
When ice contacts TBC bulb (TBC switch open), TBC shuts down the unit within
10 seconds. TBC is factory set, and generally no adjustment is required. However,
adjustment may be needed in some conditions, particularly at higher altitude locations.
CAUTION! Do not adjust S4 dip switch 7 out of the factory default position on this
model.This dip switch must be left in the factory default position or this unit will
not operate correctly.
Legend: CB–control board; Comp–compressor; FMR–fan motor-remote; F/S–float switch;
HGV–hot gas valve; LLV–liquid line valve; PM–pump motor; TBC–thermostatic bin
control; WV–inlet water valve
24
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Sequence Flow Chart
a) KM-1601SAH/3 "G" Control Board
25
Download from Www.Somanuals.com. All Manuals Search And Download.
b) KM-1601SWH/3 and KM-1601SRH/3 "E" Control Board
26
Download from Www.Somanuals.com. All Manuals Search And Download.
C. Control Board
• A Hoshizaki exclusive control board is employed in Hoshizaki Stackable Crescent
Cubers.
• All models are pretested and factory set.
• For a control board check procedure, see "IV.B. Control Board Check."
CAUTION
1. The control board is fragile; handle very carefully.
2. The control board contains integrated circuits, which are susceptible to failure
due to static discharge. It is especially important to touch the metal part of
the unit before handling or replacing the control board.
3. Do not touch the electronic devices on the control board or the back of the
control board.
4. Do not change wiring and connections. Do not misconnect K3, K4, and K5,
because the same connector is used for all three.
K3 = Thermistor
K4 = Jumper (4A4883G01) on KM-1601SAH/3 "G" control board
K4 = Open on KM-1601SWH/3 and KM-1601SRH/3 "E" control board
K5 = Float Switch
5. Always replace the whole control board assembly if it goes bad.
6. Do not short out power supply to test for voltage.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Control Board Layout
a) KM-1601SAH/3 "G" Control Board
"G" Control Board
• "OUTPUT TEST" Button
(used to test relays on control board)
• Bin Control Switch
Closed LED (green)
(on continuously
in thermostatic bin
control application)
• "ALARM RESET" Button
• S4 Dip Switch
• WHITE K3 Connector
Harvest Control
(thermistor)
• Bin Control Switch
Open LED (yellow)
(mechanical bin control
application only)
• RED K4 Connector
K4 Jumper (4A4883G01)
for Thermostatic Bin
Control Application
• Part Number
• Alarm Buzzer
• S5 Dip Switch
• Power LED (red)
(lights when 10.5VAC
is supplied to K2
connector)
• BLACK K5 Connector
Float Switch
• Label
• Relay LEDs (green)
(indicate which
relays and K1
connector pins are
energized)
(control board revision
level indicated on label
on side of relay)
• K1 Ten-Pin Connector
Pins #1 through #10
#1, 9-LED 1 on:
Compressor Relay/
Magnetic Contactor and
Fan Motor (FM)
#2-LED 2 on: Hot Gas
Valve (HGV); X10 Relay in
Harvest
• LED 2 (X2 Relay)
LED 2 ON:
K1 Connector Pin #2
LED 2 OFF:
K1 Connector Pin #3
• LED 3 (X3 Relay)
LED 3 on:
#3-LED 2 off: Liquid Line
Valve (LLV)
#4-LED 3 off: Pump Motor
(PM) in Freeze
K1 Connector Pin #5
(energized during
harvest pump timer)
LED 3 off:
#5-LED 3 on: Pump
Motor (PM) in
K1 Connector Pin #4
(energized in freeze)
Harvest Pump Timer
and Pump-Out
#6-LED 4: Inlet Water Valve
(WV) and X11 Relay
# 7, 10 Supply Voltage
#8 Open
• LED 4 (X4 Relay)
K1 Connector Pin #6
• LED 1 (X1 Relay)
K1 Connector Pin #1, #9
• K2 Connector
Control Transformer (10.5VAC)
"G" Control Board
Part Number 2A3792-01
28
Download from Www.Somanuals.com. All Manuals Search And Download.
b) KM-1601SWH/3 and KM-1601SRH/3 "E" Control Board
"E" Control Board
• "OUTPUT TEST" Button
(used to test relays on control board)
• "ALARM RESET" Button
• S4 Dip Switch
• Harvest Timer LED
(orange)
• WHITE K3 Connector
Harvest Control
(thermistor)
• Freeze Timer LED
(yellow)
• RED K4 Connector
Mechanical Bin Control
(open on units with
thermostatic bin control)
• Part Number
• Alarm Buzzer
• Power LED (red)
(lights when 10.5VAC
is supplied to K2
connector)
• BLACK K5 Connector
Float Switch
• Label
• Relay LEDs (green)
(indicate which
relays and K1
connector pins are
energized)
(control board revision
level indicated on label
on side of relay)
• K1 Ten-Pin Connector
Pins #1 through #10
#1, 9-LED 1 on:
Compressor Relay/
Magnetic Contactor and
Fan Motor-Remote (FMR)
#2-LED 2 on: Hot Gas
Valve (HGV)
#3-LED 2 off: Liquid Line
Valve (LLV)
#4-LED 3 off: Pump Motor
(PM) in Freeze
#5-LED 3 on: Pump Motor
(PM) in Pump-Out
#6-LED 4: Inlet Water Valve
(WV)
# 7, 10 Supply Voltage
#8 Open
• LED 2 (X2 Relay)
LED 2 ON:
K1 Connector Pin #2
LED 2 OFF:
K1 Connector Pin #3
• LED 3 (X3 Relay)
LED 3 on:
K1 Connector Pin #5
(energized during
harvest pump timer)
LED 3 off:
K1 Connector Pin #4
(energized in freeze)
• LED 4 (X4 Relay)
K1 Connector Pin #6
• LED 1 (X1 Relay)
K1 Connector Pin #1, #9
• "C" "ALP" Switch
• K2 Connector
Control Transformer (10.5VAC)
Switch for "C" control board
and "ALPINE" control board
(service control board only)
"E" Control Board
Part Number 2A1410-01 (factory); 2A1410-02 (service)
29
Download from Www.Somanuals.com. All Manuals Search And Download.
2. LED Lights and Audible Alarm Safeties
a) KM-1601SAH/3 "G" Control Board
At startup, a 5-second delay occurs while the control board conducts an internal timer
check. A beep occurs when the control switch is moved to the "ICE" position.
The red LED indicates proper control voltage and remains on unless a control voltage
problem occurs. The green LEDs 1 through 4 energize and sequence from initial startup
as listed in the table below. Note that the order of the LEDs from the outer edge of the
control board is 1, 4, 3, 2. For details, see "II.B. Sequence of Operation."
Time LEDs are On
Max.
Energized
Components
Sequence Step
LED
Min.
Avg.
1-Minute Fill Cycle
Harvest Cycle
4
WV
1 minute
20 minutes 3 to 5 minutes
1, 4, 2
Comp, FM, WV,
HGV
Comp, FM, PM,
HGV
2 minutes
0 seconds
Harvest Pump Timer 1, 3, 2
50 seconds harvest pump timer
setting
Freeze Cycle
1
Comp, FM, PM, LLV 5 minutes
freeze timer 30 to 35 minutes
setting
Pump-Out Cycle
1, 4*, 3, 2 Comp, FM, WV*,
PM, HGV
10 seconds 20 seconds *pump-out timer
setting
The built-in safeties shut down the unit and have alarms as listed below.
No. of Beeps
(every 3 sec.)
Type of Alarm
Notes
1
High Evaporator Temp.
(temperature > 127°F (53°C))
Check for harvest problem (stuck HGV or relay), hot
water entering unit, or shorted thermistor.
2
3
Harvest Backup Timer
(harvest > 20 min. for two cycles LLV leaking by, low charge, or inefficient Comp.
in a row)
Check for open thermistor, HGV not opening, TXV or
Freeze Timer
Check for F/S stuck closed (up), WV leaking by, HGV
(freeze > freeze timer setting for leaking by, PM not pumping, TXV not feeding properly,
two cycles in a row)
LLV not opening, low charge, or inefficient Comp.
Timer is factory set using S4 dip
switch 9 & 10
To reset the above safeties, press the "ALARM RESET" button with the power supply on.
6
Low Voltage
(92Vac 5% or less)
High Voltage
Red LED turns off if voltage protection operates.
The control voltage safeties automatically reset when
voltage is corrected.
7
(147Vac 5% or more)
Legend: Comp–compressor; FM–fan motor; F/S–float switch; HGV–hot gas valve;
LLV–liquid line valve; PM–pump motor; TXV–thermostatic expansion valve;
WV–inlet water valve
30
Download from Www.Somanuals.com. All Manuals Search And Download.
b) KM-1601SWH/3 and KM-1601SRH/3 "E" Control Board
At startup, a 5-second delay occurs while the control board conducts an internal timer
check. A beep occurs when power is turned off. The red LED indicates proper control
voltage and remains on unless a control voltage problem occurs. The green LEDs
1 through 4 energize and sequence from initial startup as listed in the table below. Note
that the order of the LEDs from the outer edge of the control board is 1, 4, 3, 2.
For details, see "II.B. Sequence of Operation."
Time LEDs are On
Max.
Energized
Components
Sequence Step
LED
Min.
Avg.
1-Minute Fill Cycle
Harvest Cycle
4
WV
1 minute
20 minutes 3 to 5 minutes
1, 4, 2
Comp, FMR, WV,
HGV
Comp, FMR, PM,
LLV
2 minutes
5 minutes
Freeze Cycle
1
freeze timer 30 to 35 minutes
setting
Pump-Out Cycle
1, 4*, 3, 2 Comp, FMR, WV*, 10 seconds 20 seconds *pump-out timer
PM, HGV setting
The built-in safeties shut down the unit and have alarms as listed below.
No. of Beeps
(every 3 sec.)
Type of Alarm
Notes
1
High Evaporator Temp.
(temperature > 127°F (53°C))
Check for harvest problem (stuck HGV or relay), hot
water entering unit, stuck HM, or shorted thermistor.
2
Harvest Backup Timer
Orange "H TIMER" LED on.
(harvest > 20 min. for two cycles Check for open thermistor, HGV not opening, TXV or
in a row)
LLV leaking by, low charge, inefficient Comp, or WRV
leaking by.
3
Freeze Timer
Yellow "F TIMER" LED on.
(freeze > freeze timer setting for Check for F/S stuck closed (up), WV leaking by, HGV
two cycles in a row) leaking by, PM not pumping, TXV not feeding properly,
Timer is factory set using S4 dip LLV not opening, low charge, HM not bypassing, or
switch 9 & 10 inefficient Comp.
To reset the above safeties, press the "ALARM RESET" button with the power supply on.
6
Low Voltage
(92Vac 5% or less)
High Voltage
Red LED turns off if voltage protection operates.
The control voltage safeties automatically reset when
voltage is corrected.
7
(147Vac 5% or more)
Legend: Comp–compressor; FMR–fan motor-remote; F/S–float switch; HGV–hot gas valve;
HM–headmaster (C.P.R.); LLV–liquid line valve; PM–pump motor;
TXV–thermostatic expansion valve; WRV–water regulating valve; WV–inlet water
valve
31
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Controls and Adjustments
CAUTION
Dip switches are factory set. Failure to maintain factory settings may adversely
affect performance and warranty coverage. For more information, contact
Hoshizaki Technical Support at 1-800-233-1940.
a) Default Dip Switch Settings
Note that the settings vary for KM-1601SRH/3 depending on the water valve installed.
The dip switches are factory set to the following positions:
S4 Dip Switch
Water
Valve Part Water
Number Valve
Code on
S4 Dip Switch No.
Auxiliary
Code
1
2
3
4
5
6
7
8
9
10
Model
KM-1601SAH/3 Dip switch settings for air-cooled units
"G" Control Board are as listed, regardless of auxiliary
code.
OFF OFF ON ON ON ON ON OFF OFF OFF
KM-1601SWH/3 Dip switch settings for water-cooled
"E" Control Board units are as listed, regardless of
auxiliary code.
OFF OFF OFF OFF ON ON OFF OFF OFF ON
ON OFF ON OFF OFF OFF OFF OFF OFF OFF
KM-1601SRH/3 R-0, R-1,
"E" Control Board some S-1
3U0111-02 J248-032
(8 l/min)
Some S-1
3U0111-01 J248-030
(15 l/min)
ON OFF OFF OFF ON ON OFF OFF OFF OFF
S-2 & later
4A1176-04 (11 l/min)
V-1 (M) & later 4A5251-04 (11 l/min)
S5 Dip Switch (Do Not Adjust)
S5 Dip Switch No.
1
2
3
4
5
Model
KM-1601SAH/3
KM-1601SWH/3
KM-1601SRH/3
OFF OFF OFF OFF OFF
Not Applicable
S4 Dip Switch
S5 Dip Switch
All Models
KM-1601SAH/3 "G" Control Board
Freeze Timer (9 & 10)
Factory Use (8)
Harvest Pump Timer (7) KM-1601SAH/3 "G" Control Board
Bin Control Selector (7) KM-1601SWH/3 & KM-1601SRH/3
"E" Control Board
Refill Counter (2 through 5)
Float Switch Selector (1)
Pump-Out Frequency Control (5 & 6)
Pump-Out Timer (3 & 4)
Harvest Timer (1 & 2)
32
Download from Www.Somanuals.com. All Manuals Search And Download.
b) Harvest Timer (S4 dip switch 1 & 2)
The harvest timer starts when the thermistor reads 48°F (9°C) at the evaporator outlet
and the control board reads the thermistor's 3.9 kΩ signal. The harvest timer is factory
set, and generally no adjustment is required. However, a setting longer than the factory
setting may be advised in cases where the flush provided at harvest needs to be
prolonged for extra cleaning. Before changing this setting, contact Hoshizaki Technical
Support at 1-800-233-1940 for recommendations. Keep in mind that setting the harvest
timer to a longer setting decreases 24-hour production.
Note that the pump-out timer (S4 dip switch 3 & 4) acts in place of the harvest timer
during cycles with a pump-out. For details, see "II.C.3.c) Pump-Out Timer (S4 dip switch
3 & 4)."
S4 Dip Switch Setting
Time
(seconds)
No. 1
OFF
ON
No. 2
OFF
OFF
ON
60
90
OFF
ON
120
180
ON
c) Pump-Out Timer (S4 dip switch 3 & 4)
CAUTION
Do not adjust S4 dip switch 3 off and S4 dip switch 4 on for KM-1601SAH/3.
Otherwise, pump motor does not rotate in the pump-out direction.
When a pump-out is called for, the pump motor stops after the preceding freeze cycle.
The pump motor restarts 2 seconds later in the reverse direction, taking water from the
bottom of the water tank and forcing pressure against the pump-out check valve seat
allowing water to go through the pump-out check valve and down the drain. At the same
time, water flows through the small tube to power flush the float switch. The pump motor
drains the water tank for the time determined by the pump-out timer. The pump-out timer
also acts in place of the harvest timer during cycles with a pump-out. The pump-out timer
is factory set, and generally no adjustment is required. The pump-out timer control can
be set to pump-out for 10 or 20 seconds.
Inlet
Water
S4 Dip Switch Setting Time (seconds)
T1
10
10
10
20
Valve
closed
closed
open
No. 3
OFF
ON
No. 4
OFF
OFF
ON
T2
150
180
120
180
OFF
ON
ON
closed
T1: Time to drain the water tank
T2: Harvest timer at pump-out
33
Download from Www.Somanuals.com. All Manuals Search And Download.
d) Pump-Out Frequency Control (S4 dip switch 5 & 6)
The pump-out frequency control is factory set to drain the water tank every 10 cycles
(except for KM-1601SRH/3 utilizing 3U0111-02 water valve), and generally no adjustment
is required. However, where water quality is bad and the icemaker needs a pump-out
more often, the pump-out frequency can be adjusted. The pump-out frequency control
can be set to have a pump-out occur every cycle, or every 2, 5, or 10 cycles.
Timing of the first pump-out is dependent on the control board. For KM-1601SAH/3 ("G"
control board), first pump-out is dependent on S4 dip switch 5 & 6. See the table below.
For KM-1601SWH/3 and KM-1601SRH/3 ("E" control board), first pump-out is after the
first freeze cycle.
KM-1601 SAH/3 "G" & KM-1601SWH/3 & KM-1610SRH/3 "E" Control Board
1st Pump-Out
S4 Dip Switch Setting
KM-1601SWH/3
KM-1601SRH/3
"E" Control Board
Pump-Out
Frequency
KM-1601SAH/3
"G" Control Board
No. 5
OFF
ON
No. 6
OFF
OFF
ON
Every cycle
Every 2 cycles
Every 5 cycles
Every 10 cycles
After 2nd freeze cycle
After 3rd freeze cycle
After 6th freeze cycle
After 11th freeze cycle
After 1st freeze cycle
OFF
ON
ON
e) Harvest Pump Timer/Bin Control Selector (S4 dip switch 7)
Depending on the control board, S4 dip switch 7 is either a harvest pump timer or bin
control selector.
(1) Harvest Pump Timer, KM-1601SAH/3 "G" Control Board
CAUTION
Factory set for proper operation. Do not adjust. Adjustment outside of the
factory default setting may result in damage to the icemaker.
Depending on the harvest pump timer setting, the pump motor energizes and runs
the last 0 or 50 seconds of harvest. When the pump is on, water circulates over the
evaporator. The water valve is open during harvest for a maximum of 6 minutes or the
length of harvest minus 0 or 50 seconds (determined by the harvest pump timer setting),
whichever is shorter.
When S4 dip switch 7 is on, the pump motor is energized through the #5 pin (DBU wire)
on the control board K1 ten-pin connector and the X10 relay. The #5 pin (DBU wire)
is used in most applications to reverse the pump motor or energize the drain valve in
pump-out cycles. In this application, it is used for the pump-out cycle (reverse rotation) as
well as the harvest pump timer (freeze rotation). Therefore, the harvest pump timer relays
are needed to control the pump motor direction during the pump-out and harvest cycles.
See "III.B. Wiring Diagrams."
KM-1601SAH/3
"G" Control Board
S4 Dip Switch Setting
Pump Motor
Time (seconds)
No. 7
ON
50
0
OFF
34
Download from Www.Somanuals.com. All Manuals Search And Download.
(2) Bin Control Selector, KM-1601SWH/3 & KM-1601SRH/3 "E" Control Board
Factory set for proper operation. Do not adjust. When set to the on position on a unit
with a thermostatic bin control, a 5-beep alarm sounds (open circuit) and the unit does
not operate.
KM-1601SWH/3 & KM-1601SRH/3
"E" Control Board
S4 Dip Switch Setting
Bin Control
No. 7
ON
Mechanical
OFF
Thermostatic
f) Factory Use (S4 dip switch 8)
Factory set. Do not adjust. This must be left in the factory default position.
g) Freeze Timer (S4 dip switch 9 & 10)
CAUTION
Adjust to proper specification, or the unit may not operate correctly.
The freeze timer setting determines the maximum allowed freeze time to prevent possible
freeze-up issues. Upon termination of the freeze timer, the control board initiates the
harvest cycle. After 2 consecutive freeze timer terminations, the control board shuts down
the icemaker. In this case, see "IV.G.3. Low Ice Production" for possible solutions. The
freeze timer is factory set, and generally no adjustment is required. Before changing this
setting, contact Hoshizaki Technical Support at 1-800-233-1940 for recommendations.
Time
S4 Dip Switch Setting
(minutes)
No. 9
OFF
OFF
ON
No. 10
OFF
ON
60
50
70
60
OFF
ON
ON
h) Float Switch Selector (S5 dip switch 1), KM-1601SAH/3 "G" Control Board
CAUTION
Factory set. Do not adjust. This must be left in the factory default position or the
unit will not operate correctly.
S5 dip switch 1 allows for single or double float switch applications. The KM-1601SAH/3
use a single float switch.
i) Refill Counter (S5 dip switch 2 through 5), KM-1601SAH/3 "G" Control Board
CAUTION
Factory set. Do not adjust. These must be left in the factory default position or
the unit will not operate correctly.
S5 dip switch 2 through 5 allows for refills during the freeze cycle.
The KM-1601SAH/3 do not refill.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
D. Control Switch
The control switch has three positions: "OFF" for power off, "ICE" for icemaking, and
"WASH" to activate the water pump when cleaning and sanitizing.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
III.Technical Information
A. Water Circuit and Refrigeration Circuit
1. KM-1601SAH/3 (air-cooled)
37
Download from Www.Somanuals.com. All Manuals Search And Download.
2. KM-1601SWH/3 (water-cooled)
38
Download from Www.Somanuals.com. All Manuals Search And Download.
3. KM-1601SRH/3 (remote air-cooled)
39
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Wiring Diagrams
1. KM-1601SAH (air-cooled)
40
Download from Www.Somanuals.com. All Manuals Search And Download.
2. KM-1601SAH3 (air-cooled)
41
Download from Www.Somanuals.com. All Manuals Search And Download.
3. KM-1601SWH (water-cooled), KM-1601SRH (remote air-cooled)
*
42
Download from Www.Somanuals.com. All Manuals Search And Download.
4. KM-1601SWH3 (water-cooled), KM-1601SRH3 (remote air-cooled)
43
Download from Www.Somanuals.com. All Manuals Search And Download.
C. Performance Data
1. KM-1601SAH (air-cooled)
APPROXIMATE ICE
PRODUCTION PER 24 HR.
WATER TEMP. (ºF/ºC)
70/21
AMBIENT TEMP.
(ºF/ºC)
70/21
80/27
90/32
100/38
70/21
80/27
90/32
50/10
90/32
1462
1435
1427
1379
663
651
647
625
1427
1381
1343
1309
647
627
609
594
1307
1221
1198
1064
593
554
543
483
lbs./day kg./day
APPROXIMATE ELECTRIC
CONSUMPTION
2450
2490
2503
2511
2503
2572
2630
2643
2563
2625
2687
2740
watts
100/38
70/21
80/27
90/32
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
709
602
568
411
2.68
2.28
2.15
1.56
568
383
228
223
2.15
1.45
0.86
0.84
505
392
206
185
1.91
1.49
0.78
0.70
gal./day m3/day
100/38
70/21
80/27
90/32
100/38
70/21
FREEZING CYCLE TIME
29
30
30
31
4.6
30
31
33
33
3.9
33
35
36
39
3.6
min.
HARVEST CYCLE TIME
80/27
90/32
100/38
4.0
3.9
3.1
2.9
2.1
2.1
3.1
2.1
2.1
min.
HEAD PRESSURE
70/21
80/27
90/32
273
283
287
19.2
19.9
20.2
287
305
320
20.2
21.4
22.5
312
333
348
21.9
23.4
24.4
PSIG kg/cm2G
100/38
294
20.7
326
23.0
373
26.2
SUCTION PRESSURE
70/21
80/27
90/32
41
41
41
2.9
2.9
2.9
41
42
42
2.9
2.9
3.0
46
49
48
3.2
3.4
3.4
PSIG kg/cm2G
100/38
44
3.1
43
3.1
54
3.8
TOTAL HEAT OF REJECTION FROM CONDENSER
20,700 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
Note:
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold
should be used for reference only.
2. We reserve the right to make changes in specifications and design without prior
notice.
44
Download from Www.Somanuals.com. All Manuals Search And Download.
2. KM-1601SAH3 (air-cooled)
APPROXIMATE ICE
PRODUCTION PER 24 HR.
WATER TEMP. (ºF/ºC)
70/21
AMBIENT TEMP.
(ºF/ºC)
70/21
80/27
90/32
100/38
70/21
80/27
90/32
50/10
90/32
1456
1431
1423
1379
660
649
646
626
1423
1381
1345
1314
646
626
610
596
1313
1234
1211
1088
596
560
549
494
lbs./day kg./day
APPROXIMATE ELECTRIC
CONSUMPTION
2370
2424
2440
2420
2440
2533
2610
2610
2463
2515
2610
2610
watts
100/38
70/21
80/27
90/32
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
708
605
573
422
2.68
2.29
2.17
1.60
573
396
249
243
2.17
1.50
0.94
0.92
510
400
222
198
1.93
1.51
0.84
0.75
gal./day m3/day
100/38
70/21
80/27
90/32
100/38
70/21
FREEZING CYCLE TIME
28
30
30
31
4.8
30
32
33
34
4.1
33
35
37
39
3.8
min.
HARVEST CYCLE TIME
80/27
90/32
100/38
4.2
4.1
3.3
3.1
2.4
2.4
3.2
2.3
2.2
min.
HEAD PRESSURE
70/21
80/27
90/32
267
286
291
18.8
20.1
20.5
291
323
350
20.5
22.7
24.6
316
343
372
22.2
24.1
26.1
PSIG kg/cm2G
100/38
293
20.6
355
25.0
392
27.6
SUCTION PRESSURE
70/21
80/27
90/32
41
44
45
2.9
3.1
3.1
45
49
53
3.1
3.5
3.7
48
52
57
3.4
3.7
4.0
PSIG kg/cm2G
100/38
45
3.2
54
3.8
60
4.2
TOTAL HEAT OF REJECTION FROM CONDENSER
24,400 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
Note:
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold
should be used for reference only.
2. We reserve the right to make changes in specifications and design without prior
notice.
45
Download from Www.Somanuals.com. All Manuals Search And Download.
3. KM-1601SWH (water-cooled)
APPROXIMATE ICE
PRODUCTION PER 24 HR.
WATER TEMP. (ºF/ºC)
70/21
AMBIENT TEMP.
(ºF/ºC)
50/10
90/32
70/21
80/27
1492
1499
677
680
1501
1513
681
686
1419
1378
643
625
90/32
100/38
1501
1453
681
659
1523
1496
691
679
1408
1303
639
591
lbs./day kg./day
APPROXIMATE ELECTRIC
CONSUMPTION
70/21
80/27
90/32
2300
2325
2332
2319
2332
2375
2410
2408
2335
2354
2400
2390
watts
100/38
70/21
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
1628
1681
1697
6.16
6.36
6.43
1697
1789
1866
6.43
6.77
7.06
2042
2272
2297
7.73
8.60
8.70
80/27
90/32
gal./day m3/day
100/38
1908
7.22
1967
7.44
2693
10.20
FREEZING CYCLE TIME
70/21
80/27
25
25
25
26
27
28
90/32
100/38
70/21
25
26
27
27
29
30
min.
HARVEST CYCLE TIME
5.0
4.2
3.8
80/27
90/32
4.4
4.2
3.3
2.5
3.2
2.2
min.
100/38
70/21
80/27
90/32
3.4
2.4
2.0
HEAD PRESSURE
241
244
246
16.9
17.2
17.3
246
252
257
17.3
17.7
18.0
257
265
269
18.0
18.6
18.9
PSIG kg/cm2G
100/38
70/21
80/27
90/32
100/38
249
43
43
44
44
17.5
3.0
3.1
3.1
3.1
260
44
44
44
45
18.3
3.1
3.1
3.1
3.2
281
45
47
47
49
19.8
3.2
3.3
3.3
3.4
SUCTION PRESSURE
PSIG kg/cm2G
TOTAL HEAT OF REJECTION FROM CONDENSER
23,100 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
3,300 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
101 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]
TOTAL HEAT OF REJECTION FROM COMPRESSOR
WATER FLOW FOR CONDENSER
PRESSURE DROP OF COOLING WATER LINE
less than 10 PSIG
Note:
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold
should be used for reference only.
2. We reserve the right to make changes in specifications and design without prior
notice.
46
Download from Www.Somanuals.com. All Manuals Search And Download.
4. KM-1601SWH3 (water-cooled)
APPROXIMATE ICE
PRODUCTION PER 24 HR.
WATER TEMP. (ºF/ºC)
70/21
AMBIENT TEMP.
(ºF/ºC)
50/10
90/32
70/21
80/27
1555
1557
705
706
1558
1562
707
708
1466
1417
665
643
90/32
100/38
1558
1507
707
684
1565
1536
710
697
1440
1326
653
601
lbs./day kg./day
APPROXIMATE ELECTRIC
CONSUMPTION
70/21
80/27
90/32
2270
2297
2305
2303
2305
2351
2390
2395
2332
2367
2411
2430
watts
100/38
70/21
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
1714
1764
1779
6.49
6.68
6.73
1779
1866
1937
6.73
7.06
7.33
2186
2449
2455
8.28
9.27
9.29
80/27
90/32
gal./day m3/day
100/38
2013
7.62
2059
7.79
2930
11.09
FREEZING CYCLE TIME
70/21
80/27
24
24
24
25
26
27
90/32
100/38
70/21
24
25
26
26
28
30
min.
HARVEST CYCLE TIME
6.0
4.9
4.4
80/27
90/32
5.2
4.9
3.6
2.4
3.6
2.2
min.
100/38
70/21
80/27
90/32
3.8
2.4
2.0
HEAD PRESSURE
239
240
241
16.8
16.9
16.9
241
244
246
16.9
17.1
17.3
257
268
267
18.1
18.8
18.8
PSIG kg/cm2G
100/38
70/21
80/27
90/32
100/38
249
41
17.5
2.9
2.9
3.0
3.0
251
42
44
45
17.6
3.0
3.1
3.2
3.2
287
45
47
48
51
20.2
3.2
3.3
3.4
3.6
SUCTION PRESSURE
42
42
43
PSIG kg/cm2G
46
TOTAL HEAT OF REJECTION FROM CONDENSER
23,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
3,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
111 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]
TOTAL HEAT OF REJECTION FROM COMPRESSOR
WATER FLOW FOR CONDENSER
PRESSURE DROP OF COOLING WATER LINE
less than 10 PSIG
Note:
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold
should be used for reference only.
2. We reserve the right to make changes in specifications and design without prior
notice.
47
Download from Www.Somanuals.com. All Manuals Search And Download.
5. KM-1601SRH with URC-21F (remote air-cooled) (auxiliary codes: R-0; R-1; some S-1)
This data applies to units with an 8 l/min water valve. The 8 l/min water valve is part
number 3U0111-02 and has J248-032 stamped on the side of the valve facing the rear of
the unit.
APPROXIMATE ICE
PRODUCTION PER 24 HR.
WATER TEMP. (ºF/ºC)
70/21
AMBIENT TEMP.
(ºF/ºC)
50/10
90/32
70/21
80/27
1583
1558
718
707
1550
1507
703
684
1435
1353
651
614
90/32
100/38
1550
1503
703
682
1472
1439
668
653
1332
1203
604
546
lbs./day kg./day
APPROXIMATE ELECTRIC
CONSUMPTION
70/21
80/27
90/32
2440
2485
2499
2507
2499
2576
2640
2655
2564
2633
2703
2760
watts
100/38
70/21
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
503
448
430
1.90
1.69
1.63
430
335
255
1.63
1.27
0.96
396
336
240
1.50
1.27
0.91
80/27
90/32
gal./day m3/day
100/38
348
1.32
251
0.95
226
0.86
FREEZING CYCLE TIME
70/21
80/27
22
23
23
25
26
28
90/32
100/38
70/21
23
24
26
27
29
31
min.
HARVEST CYCLE TIME
6.7
5.7
5.4
80/27
90/32
5.9
5.7
4.3
3.2
4.6
3.2
min.
100/38
70/21
80/27
90/32
4.6
3.2
3.2
HEAD PRESSURE
201
211
215
14.1
14.9
15.1
215
233
248
15.1
16.4
17.4
235
254
269
16.5
17.8
18.9
PSIG kg/cm2G
100/38
70/21
80/27
90/32
100/38
219
36
38
38
39
15.4
2.5
2.6
2.7
2.7
253
38
41
43
44
17.8
2.7
2.9
3.0
3.1
288
41
44
47
50
20.2
2.9
3.1
3.3
3.5
SUCTION PRESSURE
PSIG kg/cm2G
TOTAL HEAT OF REJECTION FROM CONDENSER
24,600 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
3,300 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
441 CU. IN (URC-21F)
TOTAL HEAT OF REJECTION FROM COMPRESSOR
CONDENSER VOLUME
Note:
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold
should be used for reference only.
2. We reserve the right to make changes in specifications and design without prior
notice.
48
Download from Www.Somanuals.com. All Manuals Search And Download.
6. KM-1601SRH with URC-21F (remote air-cooled) (auxiliary codes: some S-1; S-2 and
later)
This data applies to units with a 15 l/min or 11 l/min water valve. The 15 l/min water valve
is part number 3U0111-01 and has J248-030 stamped on the side of the valve facing the
rear of the unit. The 11 l/min water valve is either part number 4A1176-04 or 4A5251-04
and has the part number stamped on the side of the valve facing the front of the unit.
APPROXIMATE ICE
PRODUCTION PER 24 HR.
WATER TEMP. (ºF/ºC)
70/21
AMBIENT TEMP.
(ºF/ºC)
50/10
90/32
70/21
80/27
1564
1551
709
703
1547
1524
702
691
1468
1415
666
642
90/32
100/38
1547
1512
702
686
1505
1482
683
672
1407
1317
638
597
lbs./day kg./day
APPROXIMATE ELECTRIC
CONSUMPTION
70/21
80/27
90/32
2610
2630
2636
2650
2636
2671
2700
2712
2684
2725
2752
2800
watts
100/38
70/21
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
785
694
665
2.97
2.63
2.52
665
507
375
2.52
1.92
1.42
583
471
318
2.21
1.78
1.20
80/27
90/32
gal./day m3/day
100/38
519
1.97
361
1.37
266
1.01
FREEZING CYCLE TIME
70/21
80/27
24
25
25
27
27
29
90/32
100/38
70/21
25
26
28
29
30
32
min.
HARVEST CYCLE TIME
5.6
4.6
4.2
80/27
90/32
4.8
4.6
3.4
2.4
3.4
2.2
min.
100/38
70/21
80/27
90/32
3.6
2.3
2.0
HEAD PRESSURE
213
223
226
15.0
15.7
15.9
226
243
257
15.9
17.1
18.1
245
263
277
17.2
18.5
19.5
PSIG kg/cm2G
100/38
70/21
80/27
90/32
100/38
230
40
16.2
2.8
2.9
2.9
3.0
262
41
43
45
18.4
2.9
3.1
3.2
3.2
296
44
47
48
51
20.8
3.1
3.3
3.4
3.6
SUCTION PRESSURE
41
41
42
PSIG kg/cm2G
46
TOTAL HEAT OF REJECTION FROM CONDENSER
22,800 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
3,300 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
441 CU. IN (URC-21F)
TOTAL HEAT OF REJECTION FROM COMPRESSOR
CONDENSER VOLUME
Note:
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold
should be used for reference only.
2. We reserve the right to make changes in specifications and design without prior
notice.
49
Download from Www.Somanuals.com. All Manuals Search And Download.
7. KM-1601SRH with URC-22F (remote air-cooled) (auxiliary codes: S-2 and later)
This data applies to units with an 11 l/min water valve. The 11 l/min water valve is either
part number 4A1176-04 or 4A5251-04 and has the part number stamped on the side of
the valve facing the front of the unit.
APPROXIMATE ICE
PRODUCTION PER 24 HR.
WATER TEMP. (ºF/ºC)
70/21
AMBIENT TEMP.
(ºF/ºC)
50/10
90/32
70/21
80/27
1531
1522
694
690
1519
1503
689
682
1426
1368
647
620
90/32
100/38
1519
1475
689
669
1490
1462
676
663
1371
1261
622
572
lbs./day kg./day
APPROXIMATE ELECTRIC
CONSUMPTION
70/21
80/27
90/32
2560
2593
2604
2606
2604
2662
2710
2719
2645
2693
2746
2780
watts
100/38
70/21
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
755
665
637
2.86
2.52
2.41
637
481
352
2.41
1.82
1.33
555
444
294
2.10
1.68
1.11
80/27
90/32
gal./day m3/day
100/38
493
1.87
338
1.28
241
0.91
FREEZING CYCLE TIME
70/21
80/27
25
26
26
28
28
30
90/32
100/38
70/21
26
27
29
29
31
34
min.
HARVEST CYCLE TIME
5.5
4.6
4.1
80/27
90/32
4.8
4.6
3.5
2.6
3.4
2.3
min.
100/38
70/21
80/27
90/32
3.6
2.5
2.0
HEAD PRESSURE
207
217
220
14.5
15.2
15.5
220
237
252
15.5
16.7
17.7
240
258
273
16.9
18.1
19.2
PSIG kg/cm2G
100/38
70/21
80/27
90/32
100/38
224
40
41
42
42
15.8
2.8
2.9
2.9
3.0
257
42
44
46
46
18.1
2.9
3.1
3.2
3.3
292
44
47
49
51
20.5
3.1
3.3
3.4
3.6
SUCTION PRESSURE
PSIG kg/cm2G
TOTAL HEAT OF REJECTION FROM CONDENSER
21,000 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
2,800 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
214 CU. IN (URC-22F)
TOTAL HEAT OF REJECTION FROM COMPRESSOR
CONDENSER VOLUME
Note:
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold
should be used for reference only.
2. We reserve the right to make changes in specifications and design without prior
notice.
50
Download from Www.Somanuals.com. All Manuals Search And Download.
8. KM-1601SRH3 with URC-21F (remote air-cooled) (auxiliary codes:R-0;R-1;some S-1)
This data applies to units with an 8 l/min water valve. The 8 l/min water valve is part
number 3U0111-02 and has J248-032 stamped on the side of the valve facing the rear of
the unit.
APPROXIMATE ICE
PRODUCTION PER 24 HR.
WATER TEMP. (ºF/ºC)
70/21
AMBIENT TEMP.
(ºF/ºC)
50/10
90/32
70/21
80/27
1583
1558
718
707
1550
1507
703
684
1435
1353
651
614
90/32
100/38
1550
1503
703
682
1472
1439
668
653
1332
1203
604
546
lbs./day kg./day
APPROXIMATE ELECTRIC
CONSUMPTION
70/21
80/27
90/32
2440
2485
2499
2507
2499
2576
2640
2655
2564
2633
2703
2760
watts
100/38
70/21
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
503
448
430
1.90
1.69
1.63
430
335
255
1.63
1.27
0.96
396
336
240
1.50
1.27
0.91
80/27
90/32
gal./day m3/day
100/38
348
1.32
251
0.95
226
0.86
FREEZING CYCLE TIME
70/21
80/27
22
23
23
25
26
28
90/32
100/38
70/21
23
24
26
27
29
31
min.
HARVEST CYCLE TIME
6.7
5.7
5.4
80/27
90/32
5.9
5.7
4.3
3.2
4.6
3.2
min.
100/38
70/21
80/27
90/32
4.6
3.2
3.2
HEAD PRESSURE
201
211
215
14.1
14.9
15.1
215
233
248
15.1
16.4
17.4
235
254
269
16.5
17.8
18.9
PSIG kg/cm2G
100/38
70/21
80/27
90/32
100/38
219
36
38
38
39
15.4
2.5
2.6
2.7
2.7
253
38
41
43
44
17.8
2.7
2.9
3.0
3.1
288
41
44
47
50
20.2
2.9
3.1
3.3
3.5
SUCTION PRESSURE
PSIG kg/cm2G
TOTAL HEAT OF REJECTION FROM CONDENSER
24,600 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
3,300 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
441 CU. IN (URC-21F)
TOTAL HEAT OF REJECTION FROM COMPRESSOR
CONDENSER VOLUME
Note:
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold
should be used for reference only.
2. We reserve the right to make changes in specifications and design without prior
notice.
51
Download from Www.Somanuals.com. All Manuals Search And Download.
9. KM-1601SRH3 with URC-21F (remote air-cooled) (auxiliary codes: some S-1; S-2 and
later)
This data applies to units with a 15 l/min or 11 l/min water valve. The 15 l/min water valve
is part number 3U0111-01 and has J248-030 stamped on the side of the valve facing the
rear of the unit. The 11 l/min water valve is either part number 4A1176-04 or 4A5251-04
and has the part number stamped on the side of the valve facing the front of the unit.
APPROXIMATE ICE
PRODUCTION PER 24 HR.
WATER TEMP. (ºF/ºC)
70/21
AMBIENT TEMP.
(ºF/ºC)
50/10
90/32
70/21
80/27
1585
1568
719
711
1563
1535
709
696
1464
1396
664
633
90/32
100/38
1563
1520
709
689
1511
1482
685
672
1387
1273
629
577
lbs./day kg./day
APPROXIMATE ELECTRIC
CONSUMPTION
70/21
80/27
90/32
2580
2665
2691
2651
2691
2838
2960
2955
2712
2785
2939
2920
watts
100/38
70/21
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
781
688
659
2.96
2.60
2.49
659
497
363
2.49
1.88
1.37
585
476
318
2.21
1.80
1.20
80/27
90/32
gal./day m3/day
100/38
514
1.95
352
1.33
276
1.05
FREEZING CYCLE TIME
70/21
80/27
24
25
25
27
27
29
90/32
100/38
70/21
25
26
28
29
30
32
min.
HARVEST CYCLE TIME
5.5
4.6
4.1
80/27
90/32
4.8
4.6
3.4
2.4
3.4
2.2
min.
100/38
70/21
80/27
90/32
3.6
2.4
2.0
HEAD PRESSURE
202
212
215
14.2
14.9
15.1
215
233
247
15.1
16.3
17.4
237
257
271
16.7
18.1
19.1
PSIG kg/cm2G
100/38
70/21
80/27
90/32
100/38
221
37
15.5
2.6
2.7
2.7
2.8
253
39
41
43
17.8
2.7
2.9
3.0
3.1
293
42
45
47
51
20.6
3.0
3.2
3.3
3.6
SUCTION PRESSURE
38
39
40
PSIG kg/cm2G
44
TOTAL HEAT OF REJECTION FROM CONDENSER
22,000 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
3,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
441 CU. IN (URC-21F)
TOTAL HEAT OF REJECTION FROM COMPRESSOR
CONDENSER VOLUME
Note:
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold
should be used for reference only.
2. We reserve the right to make changes in specifications and design without prior
notice.
52
Download from Www.Somanuals.com. All Manuals Search And Download.
10. KM-1601SRH3 with URC-22F (remote air-cooled) (auxiliary codes: S-2 and later)
This data applies to units with an 11 l/min water valve. The 11 l/min water valve is either
part number 4A1176-04 or 4A5251-04 and has the part number stamped on the side of
the valve facing the front of the unit.
APPROXIMATE ICE
PRODUCTION PER 24 HR.
WATER TEMP. (ºF/ºC)
70/21
AMBIENT TEMP.
(ºF/ºC)
50/10
90/32
70/21
80/27
1530
1523
694
691
1521
1508
690
684
1414
1349
641
612
90/32
100/38
1521
1468
690
666
1498
1465
679
665
1359
1231
616
558
lbs./day kg./day
APPROXIMATE ELECTRIC
CONSUMPTION
70/21
80/27
90/32
2490
2555
2575
2548
2575
2687
2780
2779
2599
2659
2775
2770
watts
100/38
70/21
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
704
624
599
2.66
2.36
2.27
599
462
348
2.27
1.75
1.32
531
435
301
2.01
1.65
1.14
80/27
90/32
gal./day m3/day
100/38
474
1.79
337
1.27
259
0.98
FREEZING CYCLE TIME
70/21
80/27
26
26
27
28
29
31
90/32
100/38
70/21
27
27
29
30
32
34
min.
HARVEST CYCLE TIME
5.3
4.5
4.1
80/27
90/32
4.7
4.5
3.5
2.7
3.4
2.4
min.
100/38
70/21
80/27
90/32
3.6
2.6
2.2
HEAD PRESSURE
220
233
237
15.4
16.4
16.7
237
260
279
16.7
18.3
19.6
244
258
281
17.2
18.2
19.8
PSIG kg/cm2G
100/38
70/21
80/27
90/32
100/38
233
40
42
42
43
16.4
2.8
2.9
3.0
3.0
279
42
19.6
3.0
3.2
3.3
3.4
283
45
48
50
53
19.9
3.2
3.4
3.5
3.7
SUCTION PRESSURE
45
47.6
48
PSIG kg/cm2G
TOTAL HEAT OF REJECTION FROM CONDENSER
26,400 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
3,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
214 CU. IN (URC-22F)
TOTAL HEAT OF REJECTION FROM COMPRESSOR
CONDENSER VOLUME
Note:
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold
should be used for reference only.
2. We reserve the right to make changes in specifications and design without prior
notice.
53
Download from Www.Somanuals.com. All Manuals Search And Download.
IV. Service Diagnosis
WARNING
1. This unit should be diagnosed and repaired only by qualified service
personnel to reduce the risk of death, electric shock, serious injury, or fire.
2. Risk of electric shock. Use extreme caution and exercise safe electrical
practices.
3. Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.
4. CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews
are securely in place after the unit is serviced. Make sure that none have
fallen into the storage bin.
5. Make sure all food zones in the icemaker and storage bin are clean after
the unit is serviced. For cleaning procedures, see "VI. Cleaning and
Maintenance."
A. Diagnostic Procedure
The diagnostic procedure is basically a sequence check which can be used at unit
startup or for system diagnosis. Before conducting the diagnostic procedure, check
for correct installation, proper voltage per unit nameplate, and adequate water supply.
Check CB using the steps in "IV.B. Control Board Check." Check the dip switch settings
to assure that S4 dip switch 3, 4, 7, 8, 9, 10 and S5 (KM-1601SAH/3 "G" CB) dip switch
1 through 5 are in the factory default position. S4 dip switch 1, 2, 5, 6 are cleaning
adjustments and the settings are flexible. For factory default settings, see "II.C.3.a)
Default Dip Switch Settings." As you go through the procedure, check to assure the
components energize and de-energize correctly. If not, those components and controls
are suspect.
1) Turn off the power supply, then access the control box. Clear any ice from TBC.
2) Turn on the power supply, then move the control switch to the "ICE" position. A
5-second delay occurs. CB red "POWER OK" LED and green "BC CLOSED" LED
(KM-1601SAH/3 "G" CB) turn on. If red "POWER OK" LED is off, clear ice away from
TBC bulb in the storage bin area. If no ice is near TBC bulb or the LED does not turn on
even after clearing away ice, check TBC. See "IV.C. Bin Control Check." If yellow "BC
OPEN" LED (KM-1601SAH/3 "G" CB) is on (indicating a full bin), confirm that CB K4
jumper is in place.
3) 1-Minute Fill Cycle – LED 4 is on. WV and X11 relay (KM-1601SAH/3) energize and
the 1-minute fill cycle begins. After 1 minute, CB checks for a closed F/S. If F/S is
closed, the harvest cycle begins. If closed, continue to step 4. If open, WV remains
energized through additional 1-minute fill cycles until water fills the water tank and
closes F/S (low water safety). Diagnosis: Confirm that water is filling the water tank. If
not, check that the water supply shut-off valve is open and WV screen and any external
filters are clear. If WV does not energize (LED 4 on), check CB K1 ten-pin connector
pin #6 (O wire) for 115VAC. If no voltage is present, CB is bad and must be replaced.
If voltage is present, check WV connections and solenoid continuity. If unit fails to start
harvest, check for open F/S or bad 1-minute timer in CB. See "IV.D. Float Switch Check
and Cleaning."
54
Download from Www.Somanuals.com. All Manuals Search And Download.
4) Initial Harvest Cycle – LEDs 1, 4, and 2 are on. WV and X11 relay (KM-1601SAH/3)
remain energized, Comp, FM/FMR, HGV, and X10 relay (KM-1601SAH/3) energize.
CB monitors the warming of the evaporator via the thermistor located on the suction
line. When the thermistor reaches 48°F (9°C), CB reads a 3.9 kΩ signal from the
thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2).
The harvest timer has settings of 60, 90, 120, and 180 seconds.
KM-1601SAH/3 "G" CB: WV is energized during harvest for a maximum of
6 minutes or the length of harvest minus 50 seconds, whichever is shorter.
50 seconds before the harvest timer terminates, LED 4 turns off, WV and X-11 relay
de-energize, LED 3 turns on and PM energizes for the last 50 seconds of harvest.
CAUTION! S4 dip switch 7 must remain in the factory default position of
7 on. Otherwise, PM will not energize during the last 50 seconds of harvest.
Adjustment outside of the factory default position may result in damage to
the icemaker. PM is energized through CB K1 ten-pin connector pin #5 (DBU wire)
and the X10 relay.
KM-1601SWH/3, KM-1601SRH/3 "E" CB: WV is energized during harvest for a
maximum of 6 minutes or the length of harvest, whichever is shorter.
When the harvest timer terminates, the harvest cycle is complete. CB checks the
position of F/S and proceeds to the next cycle if it is closed, or calls for a 1-minute fill
cycle if it is open. The minimum total time allowed by CB for a complete harvest cycle is
2 minutes.
Diagnosis: Check that Comp, FM/FMR, HGV, and WV are energized. Average initial
harvest cycle at factory setting is 2 to 3 minutes. 1.5 minutes after initial harvest begins,
touch Comp discharge line. Is it hot? If not, check that Comp is energized, refrigerant
pressures are in range, HGV is energized and open, LLV is de-energized and closed. If
discharge line is hot, touch the inlet line to the evaporator. If discharge line is hot, place
a thermometer on the suction line next to the thermistor. Has it warmed to 48°F (9°C) or
warmer? Confirm thermistor status. See "IV.E. Thermistor Check."
KM-1601SAH/3 "G" CB: If temperature has been reached, check that WV and X-11
relay de-energize (LED 4 off) and PM energizes (LED 3 on) to circulate water over
evaporator for the last 50 seconds of harvest. If not, make sure S4 dip switch 7 is
in the factory default position. Check CB K1 ten-pin connector pin #5 (DBU wire)
for 115VAC. Also check X10 relay. X10 relay and X10 relay terminal #4 must be
energized for PM to rotate in the proper direction.
All: If 1-minute fill cycle starts after the harvest timer terminates, see "IV.D. Float
Switch Check and Cleaning." If the thermistor reading is in proper range and CB
fails to terminate the harvest cycle and initiate the freeze cycle, CB is bad and must
be replaced.
55
Download from Www.Somanuals.com. All Manuals Search And Download.
5) Freeze Cycle – LED 1 is on. Comp and FM/FMR remain energized, PM energizes
or, for KM-1601SAH/3, remains energized. LLV energizes. HGV and X10 relay
(KM-1601SAH/3) de-energize. The unit is held in freeze by a 5-minute short cycle
protection timer (CB will not accept a signal from F/S during the first 5 minutes of
freeze). After the 5-minute short cycle protection timer terminates, CB turns freeze
termination over to F/S. Diagnosis: Check that Comp, FM/FMR, PM, and LLV are
energized. Confirm that the evaporator temperature drops. If not, confirm that LLV has
energized and is open. Make sure WV and HGV are de-energized and closed. Next,
confirm proper unit pressures and TXV operation, check for an inefficient Comp or an
inoperative HM. After 5 minutes in freeze, disconnect black F/S connector from CB
BLACK K5 connector. After a 15 second delay, the unit should switch out of freeze. If
the unit switches out of freeze with F/S connector removed, but would previously not
switch out of freeze with F/S connected (long freeze - 3 beep alarm), F/S may be
sticking. To check and clean F/S, see "IV.D. Float Switch Check and Cleaning." If the
unit remains in freeze longer than 15 seconds after disconnecting black F/S connector,
replace CB. For short freeze cycle, check that reservoir is full at beginning of freeze,
pump-out check valve is not leaking by, and drain plug is in and not leaking.
Note: Normal freeze cycle will last 20 to 40 minutes depending on model and
conditions. Cycle times and pressures should follow performance data provided in
this manual. See "III.C. Performance Data."
6) Pump-Out Cycle – (10/20 second pump-out) – LEDs 1, 3, and 2 are on. LED 4 is
on when S4 dip switch 3 & 4 are set to 3 off and 4 on. CAUTION! for KM-1601SAH/3:
Do not adjust S4 dip switch 3 & 4 to 3 off and 4 on. Adjustment to this position
on this model prevents the pump motor from rotating in the pump-out direction.
Comp and FM/FMR remain energized, HGV energizes. WV energizes if S4 dip switch
3 off and 4 on. LLV de-energizes. PM de-energizes for 2 seconds, then reverses for
10/20 seconds depending on pump-out timer S4 dip switch 3 & 4 setting. When the
pump-out timer terminates, the pump-out is complete. The pump-out frequency control
is factory set for every 10th cycle (except for KM-1601SRH/3 utilizing 3U0111-02 water
valve), and generally no adjustment is required. However, where water quality is bad
and the icemaker needs a pump-out more often, the pump-out frequency can be
adjusted.
The pump-out frequency control (S4 dip switch 5 & 6) can be set to have a pump-out
occur every cycle, or every 2, 5, or 10 cycles. Timing of the first pump-out is dependent
on the control board. For KM-1601SAH/3 "G" CB, first pump-out is dependent on S4 dip
switch 5 & 6. See the table below. For KM-1601SWH/3 and KM-1601SRH/3 "E" CB, first
pump-out occurs after the first freeze cycle.
KM-1601 SAH/3 "G" & KM-1601SWH/3 & KM-1610SRH/3 "E" Control Board Settings
1st Pump-Out
S4 Dip Switch Setting
KM-1601SWH/3
KM-1601SRH/3
"E" Control Board
Pump-Out
Frequency
KM-1601SAH/3
"G" Control Board
No. 5
OFF
ON
No. 6
OFF
OFF
ON
Every cycle
Every 2 cycles
Every 5 cycles
Every 10 cycles
After 2nd freeze cycle
After 3rd freeze cycle
After 6th freeze cycle
After 11th freeze cycle
After 1st freeze cycle
OFF
ON
ON
56
Download from Www.Somanuals.com. All Manuals Search And Download.
Diagnosis:
KM-1601SAH/3 "G" CB: If PM does not reverse, check to see if S4 and S5 dip
switch settings are in the factory default position. If S4 dip switch 3 and 4 are
adjusted to 3 off and 4 on, WV and harvest pump timer relays energize. Once these
relays energize, PM rotates in the freeze cycle rotation. See "III.B. Wiring Diagrams."
Check PM circuit and capacitor, check CB K1 ten-pin connector pin #5 (DBU wire)
for voltage. Also check X10 relay. X10 relay must be de-energized and X10 relay
terminal #2 must be energized for PM to rotate in the proper direction. If water does
not pump out, check and clean the pump-out check valve assembly and tubing.
KM-1601SWH/3, KM-1601SRH/3 "E" CB: If PM does not energize, check PM
circuit and capacitor, check CB K1 ten-pin connector pin #5 (DBU wire) for voltage.
If water does not pump out, check and clean the pump-out check valve assembly
and tubing.
7) Normal Harvest Cycle – same as the initial harvest cycle – Return to "IV.A.4) Initial
Harvest Cycle."
8) Shutdown – When the unit is running hold ice in contact with TBC bulb, TBC switch
opens within 10 seconds, shutting down the unit (CB red "POWER OK" LED turns off).
TBC is factory set, and generally no adjustment is required. However, adjustment may
be needed in some conditions, particularly at higher altitude locations. Diagnosis: See
"IV.C. Bin Control Check."
Legend: CB–control board; Comp–compressor; FM–fan motor; FMR–fan motor-remote;
F/S–float switch; HGV–hot gas valve; HM–headmaster (C.P.R.); LLV–liquid
line valve; PM–pump motor; TBC–thermostatic bin control; TXV–thermostatic
expansion valve; WV–inlet water valve
57
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Control Board Check
Before replacing CB that does not show a visible defect and that you suspect is bad,
always conduct the following check procedure. This procedure will help you verify your
diagnosis. Always choose a white neutral wire to establish a good neutral connection
when checking voltages.
Alarm Reset: If CB is in alarm (beeping), press the "ALARM RESET" button on CB while
it is beeping. WARNING! Risk of electric shock. Care should be taken
not to touch live terminals. Once reset, the unit starts at the 1-minute fill
cycle. For audible alarm information, see "II.C.2. LED Lights and Audible
Alarm Safeties."
1) Check the dip switch settings to assure that S4 dip switch 3, 4, 7, 8, 9, 10 and
S5 (KM-1601SAH/3 "G" CB) dip switch 1 through 5 are in the factory default position.
S4 dip switch 1, 2, 5, 6 are cleaning adjustments and the settings are flexible. For
factory default settings, see "II.C.3.a) Default Dip Switch Settings."
2) Move the control switch to the "ICE" position. If CB red "POWER OK" LED is on, the
control voltage is good. If CB red "POWER OK" LED is off, clear ice away from TBC
bulb in the storage bin area. If no ice is near TBC bulb or CB red "POWER OK" LED
does not turn on even after clearing away ice, check TBC. See "IV.C. Bin Control
Check." If TBC is okay (closed) and CB red "POWER OK" LED is off, check the fuse,
control switch contacts, HPS, and CT secondary circuit. CT output is 10.5V at 115V
primary input. If the secondary circuit has proper voltage and CB red "POWER OK"
LED is off, CB is bad and should be replaced.
If CT secondary circuit does not have proper voltage, check the CT primary circuit.
Check for 115V at CB K1 ten-pin connector. Check the #10 pin (BR wire) to a white
neutral wire for 115V. For additional checks, see "IV.G.1. No Ice Production."
3) The "OUTPUT TEST" button provides a relay sequence test. Make sure the control
switch is in the "ICE" position, then press the "OUTPUT TEST" button. For the correct
lighting sequence, see the table below. Note that the order of the LEDs from the outer
edge of CB is 1, 4, 3, 2. Components (e.g., compressor) will cycle during the test.
Control Correct LED
Model
Board Lighting Sequence
KM-1601SAH/3
"G"
1, 4, 3, 2
2, 3, 4, 1
KM-1601SWH/3, KM-1601SRH/3 "E"
Following the test, the icemaker resumes operation. If the LEDs do not turn on as
described above, CB is bad and should be replaced.
4) To verify voltage output from CB to the components, slide CB K1 ten-pin connector
out far enough to allow multimeter lead contact. With the unit in the cycle to be tested,
check output voltage from the corresponding pin on CB K1 ten-pin connector to ground.
If output voltage is not present and the appropriate LED is on, CB is bad and must be
replaced.
Legend: CB–control board; CT–control transformer; HPS–high-pressure switch;
TBC–thermostatic bin control
58
Download from Www.Somanuals.com. All Manuals Search And Download.
C. Bin Control Check
To check TBC, follow the steps below.
CAUTION
When the ambient temperature is below 45°F (7°C), TBC switch opens and
shuts down the icemaker even if the ice storage bin is empty. When TBC is
set in the prohibited range, the icemaker operates continuously even if the ice
storage bin is filled with ice. Setting in the prohibited range may result in severe
damage to the icemaker.
TBC is factory set, and generally no adjustment is required. However, adjustment may be
needed in some conditions, particularly at higher altitude locations. Note that when TBC
switch is open, CB red "POWER OK" LED is off.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Clear any ice away from TBC bulb.
4) Remove the control box cover, then disconnect TBC wires from TBC switch.
5) Hold your hand around TBC bulb to warm it up.
6) Check for continuity across TBC switch. If closed, continue to step 6. If open, adjust or
replace TBC.
7) With the multimeter test leads still in place, hold ice on TBC bulb to lower the
temperature. Within 10 seconds, TBC switch should open (no continuity). If it remains
closed, adjust or replace TBC.
Legend: CB–control board; TBC–thermostatic bin control
59
Download from Www.Somanuals.com. All Manuals Search And Download.
D. Float Switch Check and Cleaning
F/S is used to determine that there is sufficient water in the water tank after the 1-minute
fill cycle and after each harvest cycle. F/S is also used to determine that the appropriate
volume of water has been converted into ice before switching out of the freeze cycle. No
adjustment is required.
1. Float Switch Check
To check F/S, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel, then move the
control switch to the "OFF" position.
3) Remove the insulation panel, then remove
the drain plug located on the lower front
part of the ice chute. See Fig. 1. Allow the
water tank to drain.
4) Replace the drain plug in its correct
position. Be careful not to cross thread it.
Ice Chute
Drain Plug
Float Switch Assembly
5) Remove the control box cover.
Fig. 1
6) Disconnect the black F/S connector from
CB BLACK K5 connector.
7) Check for continuity across F/S leads. With the water tank empty, F/S should be open.
If open, continue to step 8. If closed, follow the steps in "IV.D.2. Float Switch Cleaning."
After cleaning F/S, check it again. Replace if necessary.
8) Reconnect the black F/S connector to CB BLACK K5 connector, then replace the
control box cover in its correct position.
9) Move the control switch to the "ICE" position. Replace the insulation panel and the
front panel in their correct positions, then turn on the power supply. After 1 minute, the
1-minute fill cycle should end and the initial harvest cycle should begin. If the initial
harvest cycle begins, F/S is good and the check is complete. If the initial harvest cycle
does not begin, continue to step 10.
10) Turn off the power supply.
11) Remove the front panel, then move the control switch to the "OFF" position.
12) Remove the control box cover.
13) Disconnect the black F/S connector from CB BLACK K5 connector.
14) Check for continuity across F/S leads. With the water tank full, F/S should be closed. If
F/S is closed and the icemaker will not switch from the 1-minute fill cycle to the initial
harvest cycle, replace CB.
If open, confirm that the water tank is full. If the water tank is not full, check the water
supply, water filters, and WV. If the water tank is full, follow the steps in "IV.D.2. Float
Switch Cleaning." After cleaning F/S, check it again. Replace if necessary.
60
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Float Switch Cleaning
Depending on local water conditions, scale may build up on F/S. Scale on the switch can
cause the float to stick. In this case, F/S should be cleaned.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Remove the insulation panel, then remove the drain plug located on the lower front part
of the ice chute. See Fig. 1. Allow the water tank to drain.
4) Replace the drain plug in its correct position. Be careful not to cross thread it.
5) Disconnect the vent tube and the flush tube from the top of F/S, then remove F/S
assembly from the mounting bracket and remove the rubber boot from the bottom of
F/S assembly. See Fig. 2.
6) Remove the retainer rod from the bottom of F/S assembly, then remove the float. Be
careful not to bend the retainer rod excessively when removing it.
7) Wipe down F/S assembly's housing, shaft, float, and retainer rod with a mixture of 1 part
Hoshizaki "Scale Away" and 25 parts warm water. Clean the inside of the rubber boot
and hose with cleaning solution. Rinse the parts thoroughly with clean water.
8) Reassemble F/S assembly and replace it and the rubber boot in their correct positions.
Reconnect the vent tube and the flush tube.
9) Move the control switch to the "ICE" position.
10) Replace the insulation panel and front panel in their correct positions.
11) Turn on the power supply to start the automatic icemaking process.
Legend: CB–control board; F/S–float switch; WV–inlet water valve
Vent
Flush
Shaft
Fig. 2
Float Switch
Housing
Float
Retainer Rod
Rubber Boot
and Hose
61
Download from Www.Somanuals.com. All Manuals Search And Download.
E.Thermistor Check
To check thermistor resistance, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Remove the control box cover.
4) Remove the thermistor.
5) Immerse the thermistor sensor portion in a glass containing ice and water for 2 or
3 minutes.
6) Disconnect the white thermistor connector from CB WHITE K3 connector and check
the resistance between thermistor leads. Normal range is 4.7 to 6.2 kΩ. If outside
the normal range, replace the thermistor. See "V.B. Important Notes for Component
Replacement." If within the normal range, continue to the next step.
7) Replace the thermistor in its correct position. See "V.B. Important Notes for Component
Replacement."
8) Reconnect the white thermistor connector to CB WHITE K3 connector.
9) Replace the control box cover in its correct position, then turn on the power supply.
10) Move the control switch to the "ICE" position.
11) Once the harvest cycle starts, begin timing the harvest cycle.
12) The harvest timer should terminate and end the harvest cycle within 2 to 3 minutes. If
the harvest timer does not terminate and end the harvest cycle, the harvest timer is bad
and CB must be replaced.
Legend: CB–control board
F. Adjustment of Water Regulating Valve (water-cooled model)
WRV is factory set, and generally no adjustment is required. However, when necessary,
adjust WRV using the procedure below.
1) Prepare a thermometer to check the condenser drain temperature. Attach a pressure
gauge to the high-side line of the system.
Adjustment Screw
2) Five minutes after a freeze cycle starts, confirm that the
thermometer reads 104°F to 115°F (40°C to 46°C). If it does
not, use a flat blade screwdriver to rotate the adjustment
screw on WRV until the temperature is in the proper
range (rotate counterclockwise to raise the temperature or
clockwise to lower the temperature). See Fig. 3. Next, check
that the reference pressure is in the range indicated in the
Head Pressure table in the Performance Data section. If it is
not in the proper range, verify the refrigerant charge.
Top View
CCW – Higher
CW – Lower
Fig. 3
3) Check that the condenser drain temperature is stable.
Legend: WRV–water-regulating valve
62
Download from Www.Somanuals.com. All Manuals Search And Download.
G. Diagnostic Charts
Before consulting the diagnostic charts, check for correct installation, proper voltage per
unit nameplate, and adequate water supply. Check the control board using the steps in
"IV.B. Control Board Check." Check the dip switch settings to assure that S4 dip switch 3, 4,
7, 8, 9, 10 and S5 (KM-1601SAH/3 "G" CB) dip switch 1 through 5 are in the factory default
position. S4 dip switch 1, 2, 5, 6 are cleaning adjustments and the settings are flexible. For
factory default settings, see "II.C.3.a) Default Dip Switch Settings."
1. No Ice Production
No Ice Production - Possible Cause
1. Power Supply
a) Off, blown fuse, or tripped breaker.
b) Not within specifications.
2. Main Transformer (230V/115V)
(3 Phase Only)
a) Coil winding open or shorted.
3. Water Supply
a) Water supply off or improper water pressure.
b) External water filters clogged.
a) Open position.
4. Interlock Switch (Cleaning
Valve)
b) Bad contacts.
5. Thermostatic Bin Control
a) Tripped with bin filled with ice.
b) Ambient temperature too cool.
c) Set too warm.
See "IV.C. Bin Control Check."
d) Bulb out of position.
e) Bad contacts.
6. Fuse (Control Box)
7. Control Switch
a) Blown.
a) Bad contacts.
8. High-Pressure Switch
a) Bad contacts.
b) Dirty air filter (air-cooled models).
c) Clogged condenser.
d) Ambient temperature too warm.
e) Refrigerant overcharged.
f) Fan not operating (air-cooled and remote air-cooled models).
g) Refrigerant lines or components plugged.
h) Headmaster (C.P.R.) open (remote air-cooled models).
i) Condenser water temperature too warm (water-cooled models).
j) Insufficient water supply to condenser (water-cooled models).
k) Water regulating valve out of adjustment or defective (water-cooled
models).
l) Condenser water temperature too warm.
a) Coil winding open or shorted.
9. Control Transformer
(115V/10.5V)
10. Control Board
a) In alarm.
See "IV.B. Control Board Check."
b) Defective.
11. Thermistor
a) Leads shorted or open.
See "IV.E. Thermistor Check."
12. Hot Gas Valve
a) Open in freeze cycle.
b) Closed in harvest cycle.
63
Download from Www.Somanuals.com. All Manuals Search And Download.
No Ice Production - Possible Cause
13. Inlet Water Valve
a) Mesh filter or orifice clogged.
b) Coil winding open.
c) Open in freeze cycle.
a) Float does not move freely.
b) Defective.
14. Float Switch
See "IV.D. Float Switch Check
and Cleaning."
15. Compressor
a) Compressor relay/magnetic contactor contacts bad or coil winding
open.
b) Start capacitor or run capacitor defective.
c) Internal overload protector open.
d) Starter contacts bad or coil winding open.
e) Protector tripped.
f) Compressor defective.
16. Pump Motor
a) Motor winding open.
b) Bearing worn out or locked rotor.
c) Defective capacitor.
d) Mechanical seal worn out.
a) Leaking by.
17. Pump-Out Check Valve
18. Water System
a) Water leaks causing short freeze time.
a) Motor winding open.
19. Fan Motor
b) Bearing worn out or locked rotor.
c) Defective capacitor.
20. Liquid Line Valve (if applicable) a) Closed in freeze cycle.
b) Open in harvest cycle.
21. Thermostatic Expansion Valve
(TXV)
a) Bulb loose.
b) Operating erratically.
22. Headmaster (C.P.R.) (remote
condenser unit)
a) Open out of temperature/pressure range.
23. Water Regulating Valve
(water-cooled model)
a) Insufficient water supply.
b) Out of adjustment or defective.
c) Clogged.
See "IV.F. Adjustment of Water
Regulating Valve."
64
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Freeze Up
Defrost and clean the unit prior to diagnosing freeze up. See "VI.A. Cleaning and Sanitizing
Instructions."
Freeze Up - Possible Cause
Harvest Cycle
1. Evaporator
a) Scaled up.
b) Damaged.
2. Separators
a) Out of position.
b) Damaged.
3. Cube Guide
4. Inlet Water Valve
a) Out of position.
b) Damaged.
a) Water valve screen clogged.
b) Defective.
5. Spray Tubes and/or Spray
Guides
a) Dirty.
b) Out of position.
a) Low.
6. Refrigerant Charge
7. Ambient Temperature
8. Water Supply
a) Too cool.
a) Low water pressure.
b) External water filters clogged.
c) Insufficient water line size.
Minimum 3/8" nominal ID copper water tubing or equivalent.
9. Thermostatic Bin Control
a) Extension bracket not installed.
b) Bulb out of position.
See "IV.C. Bin Control Check."
c) Bad contacts.
10. Control Board
a) Harvest timer set too short.
b) Defective.
See "IV.B. Control Board Check."
11. Thermistor
a) Loose, disconnected, or defective.
See "IV.E. Thermistor Check."
12. Hot Gas Valve
a) Closed.
13. Liquid Line Valve (if applicable) a) Open.
14. Thermostatic Expansion Valve
(TXV)
a) Defective.
15. Water Regulating Valve
(water-cooled model)
a) Leaking by.
b) Defective.
Freeze Cycle
1. Evaporator
2. Separators
a) Scaled up.
b) Damaged.
a) Out of position.
b) Damaged.
3. Spray Tubes and/or Spray
Guides
a) Dirty.
b) Out of position.
a) Low.
4. Refrigerant charge.
5. Check Valve
a) Defective.
6. Control Board
a) Freeze timer set incorrectly.
b) Defective.
See "IV.B. Control Board Check."
65
Download from Www.Somanuals.com. All Manuals Search And Download.
Freeze Up - Possible Cause
7. Inlet Water Valve
a) Leaking by.
8. Float Switch
a) Float does not move freely.
b) Defective.
See "IV.D. Float Switch Check
and Cleaning."
9. Pump Motor
a) RPM too slow.
b) Impeller damaged.
a) Defective.
10. Thermostatic Expansion Valve
(TXV)
11. Headmaster (C.P.R.) (remote
condenser unit)
a) Defective.
12. Water Regulating Valve
(water-cooled model)
a) Out of adjustment.
See "IV.F. Adjustment of Water
Regulating Valve."
3. Low Ice Production
Low Ice Production - Possible Cause
Long Harvest Cycle
a) Scaled up.
1. Evaporator
2. Spray Tubes and/or Spray
Guides
a) Dirty.
b) Out of position.
a) Low.
3. Refrigerant Charge
4. Water Supply
a) Low water pressure.
b) External water filters clogged.
c) Insufficient water line size.
Minimum 3/8" nominal ID copper water tubing or equivalent.
d) Too cold.
5. Control Board
a) Thermistor connection loose (K3).
b) Defective.
See "IV.B. Control Board Check."
6. Thermistor
a) Loose, disconnected, or defective.
See "IV.E. Thermistor Check."
7. Hot Gas Valve
8. Inlet Water Valve
9. Compressor
a) Erratic or closed.
a) Water valve screen clogged.
a) Inefficient or off.
10. Liquid Line Valve (if applicable) a) Erratic or open.
11. Thermostatic Expansion Valve
(TXV)
a) Defective.
12. Water Regulating Valve
(water-cooled model)
a) Leaking by.
Long Freeze Cycle
1. Evaporator
a) Scaled up.
a) Low.
2. Refrigerant Charge
3. Air Filter (air-cooled model)
4. Condenser
a) Clogged.
a) Clogged.
5. Condenser (water-cooled model) a) Water temperature out of specification.
66
Download from Www.Somanuals.com. All Manuals Search And Download.
Low Ice Production - Possible Cause
6. Control Board
a) Float switch connection loose (K5).
b) Defective.
See "IV.B. Control Board Check."
7. Hot Gas Valve
a) Erratic or open.
8. Inlet Water Valve
a) Leaking by.
9. Float Switch
a) Float does not move freely or defective switch.
See "IV.D. Float Switch Check
and Cleaning."
10. Compressor
11. Pump Motor
a) Inefficient or off.
a) RPM too slow.
12. Liquid Line Valve (if applicable) a) Erratic or closed.
13. Expansion Valve (TXV)
a) Bulb loose.
b) Defective.
14. Headmaster (C.P.R.) (remote
condenser unit)
a) Not bypassing.
15. Water Regulating Valve
(water-cooled model)
a) Insufficient water supply.
b) Out of adjustment or defective.
c) Clogged.
See "IV.F. Adjustment of Water
Regulating Valve."
67
Download from Www.Somanuals.com. All Manuals Search And Download.
V. Replacement of Components
WARNING
1. This unit should be diagnosed and repaired only by qualified service
personnel to reduce the risk of death, electric shock, serious injury, or fire.
2. Move the control switch to the "OFF" position and turn off the power supply
before servicing. Lockout/Tagout to prevent the power from being turned back
on inadvertently.
3. CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews
are securely in place after the unit is serviced. Make sure that none have
fallen into the storage bin.
4. Make sure all food zones in the icemaker and storage bin are clean after
the unit is serviced. For cleaning procedures, see "VI. Cleaning and
Maintenance."
A. Service for Refrigerant Lines
WARNING
1. Repairs requiring the refrigeration circuit to be opened must be performed by
properly trained and EPA-certified service personnel.
2. Always recover the refrigerant and store it in an approved container. Do not
discharge the refrigerant into the atmosphere.
3. Use an electronic leak detector or soap bubbles to check for leaks. Add a
trace of refrigerant to the system (if using an electronic leak detector), and
then raise the pressure using nitrogen gas (140 PSIG). DO NOT use R-404A
as a mixture with pressurized air for leak testing.
CAUTION
1. Do not leave the system open for longer than 15 minutes when replacing or
servicing parts. The Polyol Ester (POE) oils used in R-404A units can absorb
moisture quickly. Therefore it is important to prevent moisture from entering
the system when replacing or servicing parts.
2. Always install a new drier every time the sealed refrigeration system is
opened.
3. Do not replace the drier until after all other repair or replacement has been
made. Install the new drier with the arrow on the drier in the direction of the
refrigerant flow.
4. When brazing, protect the drier by using a wet cloth to prevent the drier from
overheating. Do not allow the drier to exceed 250°F (121°C).
1. Refrigerant Recovery
The icemaker is provided with refrigerant service valves. Using proper refrigerant practices,
recover the refrigerant from the service valves and store it in an approved container. Do not
discharge the refrigerant into the atmosphere.
68
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Brazing
WARNING
1. R-404A itself is not flammable at atmospheric pressure and temperatures up
to 176°F (80°C).
2. R-404A itself is not explosive or poisonous. However, when exposed to
high temperatures (open flames), R-404A can be decomposed to form
hydrofluoric acid and carbonyl fluoride both of which are hazardous.
3. Do not use silver alloy or copper alloy containing arsenic.
4. Use an electronic leak detector or soap bubbles to check for leaks. Add a
trace of refrigerant to the system (if using an electronic leak detector), and
then raise the pressure using nitrogen gas (140 PSIG). DO NOT use R-404A
as a mixture with pressurized air for leak testing.
1) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.
Note: Because the pipes in the evaporator case are specially coated to resist corrosion,
it is important to make connections outside the evaporator case when possible. If
it is necessary to braze inside the evaporator case, use sandpaper to remove the
coating from the brazing connections before unbrazing the components.
CAUTION
1. Always install a new drier every time the sealed refrigeration system is
opened.
2. Do not replace the drier until after all other repair or replacement has been
made. Install the new drier with the arrow on the drier in the direction of the
refrigerant flow.
3. When brazing, protect the drier by using a wet cloth to prevent the drier from
overheating. Do not allow the drier to exceed 250°F (121°C).
2) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with
pressurized air for leak testing.
3. Evacuation and Recharge (R-404A)
1) Attach a vacuum pump to the system. Be sure to connect the charging hoses to both
high and low-side service valves.
IMPORTANT
The vacuum level and vacuum pump may be the same as those for current
refrigerants. However, the rubber hose and gauge manifold to be used for
evacuation and refrigerant charge should be exclusively for POE oils.
2) Turn on the vacuum pump. Open the gauge manifold valves, then open the high and
low-side service valves. Never allow the oil in the vacuum pump to flow backwards.
3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends
on pump capacity.
69
Download from Www.Somanuals.com. All Manuals Search And Download.
4) Close the high and low-side valves on the gauge manifold.
5) Disconnect the gauge manifold hose from the vacuum pump and attach it to a
refrigerant service cylinder. Remember to loosen the connection and purge the air
from the hose. For air-cooled and water-cooled models, see the nameplate for the
required refrigerant charge. For remote air-cooled model, see the rating label inside the
icemaker. Hoshizaki recommends only virgin refrigerant or reclaimed refrigerant which
meets ARI Standard 700 (latest edition) be used.
6) A liquid charge is required when charging an R-404A system (to prevent fractionation).
Place the service cylinder on the scales; if the service cylinder is not equipped with
a dip tube, invert the service cylinder, then place it on the scales. Open the high-side
valve on the gauge manifold.
7) Allow the system to charge with liquid until the proper charge weight is met.
8) If necessary, add any remaining charge to the system through the low-side.
CAUTION! To prevent compressor damage, use a throttling valve or liquid
dispensing device to add the remaining liquid charge through the low-side
service valve with the unit running.
9) Close the high and low-side service valves. Close the high and low-side gauge manifold
valves, then disconnect the gauge manifold hoses.
10) Cap the service valves to prevent a possible leak.
70
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Important Notes for Component Replacement
CAUTION
When replacing a component listed below, see the notes to help ensure proper
operation.
Component
Notes
Compressor
Install a new start capacitor, run capacitor, and start relay.
Thermostatic
• Attach the thermostatic expansion valve bulb to the suction line in the same location as
Expansion Valve
the previous bulb.
• The bulb should be between the 10 and 2 o'clock position on the tube.
• Secure the bulb with the clamp and holder, then insulate it.
• Replace the strainer when replacing the hot gas valve.
Hot Gas Valve
Liquid Line Valve
• Use copper tube of the same diameter and length when replacing valve lines.
Install a new capacitor.
Fan Motor
Pump Motor
Thermistor
Install a new capacitor.
• Attach the new thermistor to the suction line in the same location as the previous
thermistor.
• The thermistor should be at the 12 o'clock position on the tube.
• Smoothly fill the recessed area of the thermistor holder with high thermal conductive
type sealant. Hoshizaki America part number 4A0683-01 (Silicone Heat Sink Compound
10-8108 manufactured by GC Electronics), KE-4560 RTV (manufactured by ShinEtsu
Silicones), or equivalent are recommended.
• Secure the thermistor with the holder, then insulate it.
• Be very careful to prevent damage to the leads.
Thermistor Holder
Thermistor Lead
Foam Insulation
Cable Tie
71
Download from Www.Somanuals.com. All Manuals Search And Download.
VI. Cleaning and Maintenance
This icemaker must be cleaned and maintained in accordance with the instruction
manual and labels provided with the icemaker. Consult with your local distributor
about cleaning and maintenance service. To obtain the name and phone number of
1-800-233-1940 in the USA.
WARNING
1. Only qualified service technicians should service this icemaker.
2. CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews
are securely in place after any cleaning or maintenance is done to the unit.
Make sure that none have fallen into the storage bin.
3. The storage bin is for ice use only. Do not store anything else in the storage
bin.
A. Cleaning and Sanitizing Instructions
Hoshizaki recommends cleaning and sanitizing this unit at least once a year. More
frequent cleaning and sanitizing, however, may be required in some existing water
conditions.
WARNING
1. To prevent injury to individuals and damage to the icemaker, do not use
ammonia type cleaners.
2. Carefully follow any instructions provided with the bottles of cleaning and
sanitizing solution.
3. Always wear liquid-proof gloves and goggles to prevent the cleaning and
sanitizing solutions from coming into contact with skin or eyes.
4. To prevent damage to the water pump seal, do not operate the icemaker with
the control switch in the "WASH" position when the water tank is empty.
IMPORTANT
1. The cleaning valve is opened during cleaning and sanitizing to allow solution
flow to the inside of the evaporator. It should be closed for all icemaking
operation. The compressor will not operate unless this valve is completely
closed.
2. To close the cleaning valve, the valve handle should be at a right angle to the
valve body. To open the cleaning valve, the valve handle should be parallel to
the valve body.
OPEN
CLOSED
Cleaning and Sanitizing Operation
Normal Icemaking Operation
(allows solution flow to the inside of the evaporator)
72
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Cleaning Procedure
1) Dilute 27 fl. oz. (800 ml) of Hoshizaki "Scale Away" with 5 gal. (19 l) of warm water.
2) Remove all ice from the evaporator and the storage bin.
Note: To remove cubes on the evaporator, turn off the power supply and turn it back on
after 3 minutes. The harvest cycle starts and the cubes will be removed from the
evaporator.
3) Turn off the power supply.
4) Remove the front panel, then remove the insulation panel by first removing the
thumbscrew, lifting up the panel slightly and pulling it towards you.
5) Remove the drain plug located on the lower front part of the ice chute. Allow the water
tank to drain.
6) Replace the drain plug in its correct position. Be careful not to cross thread it.
7) In bad or severe water conditions, clean the float switch assembly as described below.
Otherwise, continue to step 8.
a. Disconnect the vent tube and the flush tube from the top of the float switch, then
remove the float switch assembly. Remove the rubber boot from the bottom of the
assembly.
b. Remove the retainer rod from the bottom of the float switch housing, then remove
the float. Be careful not to bend the retainer rod excessively when removing it.
c. Wipe down the float switch assembly's housing, shaft, float, and retainer rod with
cleaning solution. Clean the inside of the rubber boot and hose with cleaning
solution. Rinse the parts thoroughly with clean water.
d. Reassemble the float switch assembly and replace it and the rubber boot in their
correct positions. Reconnect the vent tube and the flush tube.
8) Pour the cleaning solution into the water tank.
9) Fully open the cleaning valve on the left side wall of the machine compartment.
10) Move the control switch on the control box to the "WASH" position.
11) Replace the insulation panel and the front panel in their correct positions.
12) Turn on the power supply to start the washing process.
13) Turn off the power supply after 30 minutes.
14) Remove the front panel and the insulation panel.
15) Remove the drain plug. Allow the water tank to drain. Replace the drain plug and the
insulation panel in their correct positions.
16) Move the control switch to the "ICE" position.
17) Close the cleaning valve.
Note: The icemaker will not operate unless the cleaning valve is completely closed.
18) Replace the front panel in its correct position.
19) Turn on the power supply to fill the water tank with water.
20) Turn off the power supply after 3 minutes.
73
Download from Www.Somanuals.com. All Manuals Search And Download.
21) Remove the front panel and fully open the cleaning valve.
22) Move the control switch to the "WASH" position.
23) Replace the front panel in its correct position.
24) Turn on the power supply to rinse off the cleaning solution.
25) Turn off the power supply after 5 minutes.
26) Remove the front panel and the insulation panel.
27) Remove the drain plug. Allow the water tank to drain. Replace the drain plug and the
insulation panel in their correct positions.
Note: Do not replace the insulation panel when you proceed to "2. Sanitizing
Procedure."
28) Repeat steps 16 through 27 three more times to rinse thoroughly.
Note: If you do not sanitize the icemaker, go to step 9 in "2. Sanitizing Procedure."
2. Sanitizing Procedure - Following Cleaning Procedure
1) Dilute 2.5 fl. oz. (74 ml or 5 tbs) of a 5.25% sodium hypochlorite solution (chlorine
bleach) with 5 gal. (19 l) of warm water.
2) Pour the sanitizing solution into the water tank.
3) Replace the insulation panel and the front panel in their correct positions.
Note: Make sure the control switch is in the "WASH" position and the cleaning valve is
open.
4) Turn on the power supply to start the sanitizing process.
5) Turn off the power supply after 15 minutes.
6) Remove the front panel and the insulation panel.
7) Remove the drain plug. Allow the water tank to drain. Replace the drain plug and the
insulation panel in their correct positions.
8) Repeat steps 16 through 27 in "1. Cleaning Procedure" two times to rinse thoroughly.
9) Close the cleaning valve.
10) Move the control switch to the "ICE" position.
11) Replace the front panel in its correct position.
12) Clean the storage bin liner using a neutral cleaner. Rinse thoroughly after cleaning.
13) Turn on the power supply to start the automatic icemaking process.
74
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Maintenance
This icemaker must be maintained individually, referring to the instruction manual and
labels provided with the icemaker.
WARNING
1. Only qualified service technicians should service this icemaker.
2. Move the control switch to the "OFF" position and turn off the power supply
before servicing. Lockout/Tagout to prevent the power supply from being
turned back on inadvertently.
1. Stainless Steel Exterior
To prevent corrosion, wipe the exterior occasionally with a clean, soft cloth. Use a damp
cloth containing a neutral cleaner to wipe off oil or dirt buildup.
2. Storage Bin and Scoop
• Wash your hands before removing ice. Use the plastic scoop provided (bin accessory).
• The storage bin is for ice use only. Do not store anything else in the storage bin.
• Clean the scoop and the storage bin liner using a neutral cleaner. Rinse thoroughly
after cleaning.
3. Air Filters (air-cooled model)
Plastic mesh air filters remove dirt and dust from the air, and keep the condenser from
getting clogged. As the filters get clogged, the icemaker’s performance will be reduced.
Check the filters at least twice a month. When clogged, use warm water and a neutral
cleaner to wash the filters.
4. Condenser (air-cooled and remote air-cooled models)
Check the condenser once a year, and clean the coil if required by using a brush or
vacuum cleaner. More frequent cleaning may be required depending on location.
C. Preparing the Icemaker for Long Storage
CAUTION
1. When storing the icemaker for an extended time or in sub-freezing
temperatures, follow the instructions below to prevent damage.
2. To prevent damage to the water pump seal, do not operate the icemaker with
the control switch in the "WASH" position when the water tank is empty.
When the icemaker is not used for two or three days under normal conditions, it is
sufficient to move the control switch to the "OFF" position. When storing the icemaker for
an extended time or in sub-freezing temperatures, follow the instructions below.
1. Remove the water from the icemaker water supply line:
1) Turn off the power supply, then remove the front panel.
2) Move the control switch on the control box to the "OFF" position.
3) Close the icemaker water supply line shut-off valve, then open the icemaker water
supply line drain valve.
75
Download from Www.Somanuals.com. All Manuals Search And Download.
4) Allow the line to drain by gravity.
5) Attach a compressed air or carbon dioxide supply to the icemaker water supply line
drain valve.
6) Move the control switch to the "ICE" position.
7) Replace the front panel in its correct position, then turn on the power supply.
8) Blow the icemaker water supply line out using the compressed air or carbon dioxide
supply.
9) Close the icemaker water supply line drain valve.
2. Drain the water tank:
1) Turn off the power supply, then remove the front panel. Move the control switch to the
"OFF" position.
2) Remove the insulation panel. Remove the drain plug located on the lower front part of
the ice chute. See Fig. 1. Allow the water tank to drain.
3) Replace the drain plug and the insulation panel in their correct positions. Be careful not
to cross thread the drain plug.
4) Remove all ice from the storage bin. Clean the storage bin using a neutral cleaner.
Rinse thoroughly after cleaning.
5) Replace the front panel in its correct position.
3. On water-cooled model only, first remove the water from the water-cooled
condenser:
1) Make sure the power supply is off, then remove the front panel and right side panel.
2) Close the condenser water supply line shut-off valve. If connected to a closed loop
system, also close the condenser return line shut-off valve.
3) Open the condenser water supply line drain valve. If connected to a closed loop system,
also open the condenser return line drain valve.
4) Attach a compressed air or carbon dioxide supply to the condenser water supply line
drain valve.
5) Open the water regulating valve by using a screwdriver to pry up on the spring retainer
underneath the spring. While holding the valve open, blow out the condenser using the
compressed air or carbon dioxide supply until water stops coming out.
6) Close the drain valve(s).
7) Replace the right side panel and front panel in their correct positions.
76