Hoshizaki Ice Maker KM 1601MRH 3 User Manual

Hoshizaki America, Inc.  
Hoshizaki  
Modular Crescent Cuber  
Models  
KM-1601MRH/3  
SERVICE MANUAL  
“A Superior Degree  
of Reliability”  
Number: 73129  
Issued: 6-16-2006  
Revised: 3-28-2011  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT  
This manual should be read carefully before the icemaker is serviced or  
maintenance operations are performed. Only qualified service technicians  
should install, service, and maintain the icemaker. Read the warnings contained  
in this booklet carefully as they give important information regarding safety.  
Please retain this booklet for any further reference that may be necessary.  
CONTENTS  
Important Safety Information ................................................................................................. 5  
I. Specifications...................................................................................................................... 6  
A. Icemaker ....................................................................................................................... 6  
1. KM-1601MRH with URC-21F................................................................................... 6  
2. KM-1601MRH with URC-22F .................................................................................. 7  
3. KM-1601MRH3 with URC-21F ................................................................................ 8  
4. KM-1601MRH3 with URC-22F ................................................................................ 9  
B. Condenser Unit ........................................................................................................... 10  
II. General Information..........................................................................................................11  
A. Construction.................................................................................................................11  
1. KM-1601MRH, KM-1601MRH3 ...............................................................................11  
2. URC-21F, URC-22F............................................................................................... 12  
B. Sequence of Operation ............................................................................................... 13  
1. Sequence Cycles and Shutdown ........................................................................... 13  
a) One Minute Fill Cycle....................................................................................... 13  
b) Initial Harvest Cycle ........................................................................................ 13  
c) Freeze Cycle ................................................................................................... 13  
d) Pump-Out Cycle .............................................................................................. 13  
e) Normal Harvest Cycle ..................................................................................... 14  
2. Sequence Flow Chart............................................................................................ 15  
C. Control Board.............................................................................................................. 16  
1. Control Board Layout ............................................................................................. 17  
2. LED Lights and Audible Alarm Safeties ................................................................. 18  
3. Controls and Adjustments...................................................................................... 19  
a) Default Dip Switch Settings.............................................................................. 19  
b) Harvest Timer (dip switch 1 & 2)...................................................................... 19  
c) Pump-Out Timer (dip switch 3 & 4) .................................................................. 20  
d) Pump-Out Frequency Control (dip switch 5 & 6).............................................. 20  
e) Factory Use (S4 dip switch 7 & 8).................................................................... 20  
f) Freeze Timer (dip switch 9 & 10)....................................................................... 21  
D. Control Switch ............................................................................................................. 21  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
III. Technical Information...................................................................................................... 22  
A. Water Circuit and Refrigeration Circuit........................................................................ 22  
B. Wiring Diagrams.......................................................................................................... 23  
1. KM-1601MRH......................................................................................................... 23  
2. KM-1601MRH3...................................................................................................... 24  
C. Performance Data ....................................................................................................... 25  
1. KM-1601MRH with URC-21F................................................................................. 25  
2. KM-1601MRH with URC-22F................................................................................. 26  
3. KM-1601MRH3 with URC-21F............................................................................... 27  
4. KM-1601MRH3 with URC-22F............................................................................... 28  
IV. Service Diagnosis........................................................................................................... 29  
A. Diagnostic Procedure ................................................................................................. 29  
B. Control Board Check................................................................................................... 31  
C. Bin Control Check ....................................................................................................... 32  
D. Float Switch Check and Cleaning ............................................................................... 33  
1. Float Switch Check ................................................................................................ 33  
2. Float Switch Cleaning............................................................................................ 34  
E. Thermistor Check........................................................................................................ 35  
F. Diagnostic Charts ........................................................................................................ 36  
1. No Ice Production................................................................................................... 36  
2. Evaporator is Frozen Up........................................................................................ 39  
3. Low Ice Production ................................................................................................ 40  
4. Abnormal Ice ......................................................................................................... 41  
5. Other...................................................................................................................... 41  
V. Replacement of Components .......................................................................................... 42  
A. Service for Refrigerant Lines....................................................................................... 42  
1. Refrigerant Recovery ............................................................................................. 42  
2. Brazing .................................................................................................................. 43  
3. Evacuation and Recharge (R-404A)...................................................................... 43  
B. Important Notes for Component Replacement............................................................ 45  
VI. Cleaning and Maintenance Instructions ......................................................................... 46  
A. Cleaning and Sanitizing Procedures ........................................................................... 46  
1. Cleaning Procedure................................................................................................ 47  
2. Sanitizing Procedure - Following Cleaning Procedure........................................... 48  
B. Maintenance................................................................................................................ 49  
C. Preparing the Icemaker for Long Storage ................................................................... 49  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Important Safety Information  
Throughout this manual, notices appear to bring your attention to situations which could  
result in death, serious injury, or damage to the unit.  
WARNING  
Indicates a hazardous situation which could result in death or  
serious injury.  
CAUTION  
IMPORTANT  
Indicates a situation which could result in damage to the unit.  
Indicates important information about the use and care of the  
unit.  
WARNING  
This icemaker should be destined only to the use for which it has been  
expressly conceived. Any other use should be considered improper and  
therefore dangerous. The manufacturer cannot be held responsible for injury or  
damage resulting from improper, incorrect, and unreasonable use.  
To reduce the risk of death, electric shock, serious injury, or fire, follow  
basic precautions including the following:  
• Only qualified service technicians should install, service, and maintain the  
icemaker.  
• Electrical connection must be hard-wired and must meet national, state, and  
local electrical code requirements. Failure to meet these code requirements  
could result in death, electric shock, serious injury, re, or severe damage to  
equipment.  
• This unit requires an independent power supply. See the nameplate for  
proper voltage and breaker/fuse size. Failure to use a proper breaker or fuse  
can result in a tripped breaker, blown fuse, or damage to existing wiring. This  
could lead to heat generation or fire.  
THE ICEMAKER MUST BE GROUNDED. Failure to properly ground the  
icemaker could result in death or serious injury.  
• Move the control switch to the "OFF" position and turn off the power supply  
before servicing. Lockout/Tagout to prevent the power supply from being  
turned back on inadvertently.  
• Do not make any alterations to the unit. Alterations could result in electric  
shock, injury, re, or damage to the unit.  
Additional Warning for Remote Air-Cooled Model  
THE REMOTE CONDENSER UNIT MUST BE GROUNDED. The power  
supply and ground wire to the remote condenser unit are supplied from the  
icemaker. Failure to properly ground the remote condenser unit could result  
in death or serious injury.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
I. Specifications  
A. Icemaker  
1. KM-1601MRH with URC-21F  
AC SUPPLY VOLTAGE  
AMPERAGE  
208-230/60/1 (3 wire with neutral for 115V)  
11.6 A ( 5 Min. Freeze AT 104°F / WT 80°F)  
MINIMUM CIRCUIT AMPACITY  
MAXIMUM FUSE SIZE  
APPROXIMATE ICE PRODUCTION  
PER 24 HR.  
20 A  
20 A  
Ambient  
WATER TEMP. (°F)  
70  
Temp.(°F)  
50  
90  
lbs./day ( kg/day )  
Reference without *marks  
70  
80  
90  
100  
*1508 (684)  
1489 (675)  
1483 (673)  
1449 (657)  
1483 (673)  
1450 (658)  
*1422 (645)  
1398 (634)  
1399 (634)  
1338 (607)  
1320 (599)  
1227 (557)  
SHAPE OF ICE  
Crescent Cube  
ICE PRODUCTION PER CYCLE  
APPROXIMATE STORAGE CAPACITY  
ELECTRIC & WATER CONSUMPTION  
ELECTRIC W (kWH/100 lbs.)  
WATER gal./24HR (gal./100 lbs.)  
EXTERIOR DIMENSIONS (WxDxH)  
EXTERIOR FINISH  
29.8 lbs. (13.5 kg) 1440 pcs.  
N/A  
90/70°F  
2670(4.5)  
263(18.5)  
70/50°F  
2450(3.9)  
483(32.0)  
30" x 27.4" x 41.7" (762 x 695 x 1059 mm)  
Stainless Steel, Galvanized Steel (Rear)  
Net 259 lbs. (117 kg), Shipping 316 lbs. (143 kg)  
Permanent - Connection  
WEIGHT  
CONNECTIONS - ELECTRIC  
- WATER SUPPLY  
Inlet  
1/2" FPT  
- DRAIN  
Outlet  
3/4" FPT  
3/8" OD Tube  
CUBE CONTROL SYSTEM  
HARVESTING CONTROL SYSTEM  
ICE MAKING WATER CONTROL  
COOLING WATER CONTROL  
BIN CONTROL SYSTEM  
COMPRESSOR  
CONDENSER  
EVAPORATOR  
REFRIGERANT CONTROL  
Float Switch  
Hot Gas and Water, Thermistor and Timer  
Timer Controlled. Overflow Pipe  
N/A  
Thermostat  
Hermetic, Model CS18K6E-PFV  
Air-Cooled Remote, Condenser Unit URC-21F  
Vertical type, Stainless Steel and Copper  
Thermostatic Expansion Valve  
Condensing Pressure Regulator on URC-21F  
R-404A, 24 lb. 4.0 oz. (11,000g)  
(Icemaker 14 lbs. 8.8 oz. Cond. Unit 9 lb. 11.2 oz.)  
High 467PSIG, Low 230PSIG  
High Voltage Cut-out ( Internal )  
Auto-reset Overload Protector ( Internal )  
Auto-reset High Pressure Control Switch  
Float Switch  
REFRIGERANT CHARGE  
DESIGN PRESSURE  
P.C. BOARD CIRCUIT PROTECTION  
COMPRESSOR PROTECTION  
REFRIGERANT CIRCUIT PROTECTION  
LOW WATER PROTECTION  
ACCESSORIES -SUPPLIED  
-REQUIRED  
N/A  
Ice Dispenser or Ice Storage Bin, Remote Condenser Unit  
OPERATING CONDITIONS  
VOLTAGE RANGE  
187 - 253 V  
AMBIENT TEMP.  
45 -100° F  
WATER SUPPLY TEMP.  
WATER SUPPLY PRESSURE  
45 - 90° F  
10 - 113 PSIG  
Note: We reserve the right to make changes in specifications and design without prior  
notice.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. KM-1601MRH with URC-22F  
AC SUPPLY VOLTAGE  
AMPERAGE  
208-230/60/1 (3 wire with neutral for 115V)  
11.6 A ( 5 Min. Freeze AT 104°F / WT 80°F)  
MINIMUM CIRCUIT AMPACITY  
MAXIMUM FUSE SIZE  
APPROXIMATE ICE PRODUCTION  
PER 24 HR.  
20 A  
20 A  
Ambient  
WATER TEMP. (°F)  
70  
Temp.(°F)  
50  
90  
lbs./day ( kg/day )  
Reference without *marks  
70  
80  
90  
100  
*1493 (677)  
1476 (670)  
1471 (667)  
1449 (657)  
1471 (667)  
1441 (654)  
*1417 (643)  
1400 (635)  
1410 (640)  
1364 (619)  
1346 (610)  
1280 (581)  
SHAPE OF ICE  
Crescent Cube  
ICE PRODUCTION PER CYCLE  
APPROXIMATE STORAGE CAPACITY  
ELECTRIC & WATER CONSUMPTION  
ELECTRIC W (kWH/100 lbs.)  
WATER gal./24HR (gal./100 lbs.)  
CEC/CEE TIER LEVEL  
ENERGY STAR  
27.9 lbs. (12.7 kg) 1440 pcs.  
N/A  
90/70°F  
2740(4.64)  
264(18.6)  
2
70/50°F  
2590(4.17)  
521(34.9)  
YES  
EXTERIOR DIMENSIONS (WxDxH)  
EXTERIOR FINISH  
WEIGHT  
CONNECTIONS - ELECTRIC  
- WATER SUPPLY  
30" x 27.4" x 41.7" (762 x 695 x 1059 mm)  
Stainless Steel, Galvanized Steel (Rear)  
Net 259 lbs. (117 kg), Shipping 316 lbs. (143 kg)  
Permanent - Connection  
Inlet  
1/2" FPT  
- DRAIN  
Outlet  
3/4" FPT  
3/8" OD Tube  
CUBE CONTROL SYSTEM  
HARVESTING CONTROL SYSTEM  
ICE MAKING WATER CONTROL  
COOLING WATER CONTROL  
BIN CONTROL SYSTEM  
COMPRESSOR  
CONDENSER  
EVAPORATOR  
REFRIGERANT CONTROL  
Float Switch  
Hot Gas and Water, Thermistor and Timer  
Timer Controlled. Overflow Pipe  
N/A  
Thermostat  
Hermetic, Model CS18K6E-PFV  
Air-Cooled Remote, Condenser Unit URC-22F  
Vertical type, Stainless Steel and Copper  
Thermostatic Expansion Valve  
Condensing Pressure Regulator on URC-22F  
R-404A, 22 lb. 4.3 oz. (10,100g)  
(Icemaker 14 lbs. 8.8 oz. Cond. Unit 9 lb. 11.2 oz.)  
High 467PSIG, Low 230PSIG  
High Voltage Cut-out ( Internal )  
Auto-reset Overload Protector ( Internal )  
Auto-reset High Pressure Control Switch  
Float Switch  
REFRIGERANT CHARGE (w/URC-22F)  
DESIGN PRESSURE  
P.C. BOARD CIRCUIT PROTECTION  
COMPRESSOR PROTECTION  
REFRIGERANT CIRCUIT PROTECTION  
LOW WATER PROTECTION  
ACCESSORIES -SUPPLIED  
-REQUIRED  
N/A  
Ice Dispenser or Ice Storage Bin, Remote Condenser Unit  
OPERATING CONDITIONS  
VOLTAGE RANGE  
187 - 253 V  
AMBIENT TEMP.  
WATER SUPPLY TEMP.  
WATER SUPPLY PRESSURE  
45 -100° F  
45 - 90° F  
10 - 113 PSIG  
Note: We reserve the right to make changes in specifications and design without prior  
notice.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. KM-1601MRH3 with URC-21F  
AC SUPPLY VOLTAGE  
AMPERAGE  
208-230/60/3  
8.4 A ( 5 Min. Freeze AT 104°F / WT 80°F)  
MINIMUM CIRCUIT AMPACITY  
MAXIMUM FUSE SIZE  
APPROXIMATE ICE PRODUCTION  
PER 24 HR.  
20 A  
20 A  
Ambient  
WATER TEMP. (°F)  
Temp.(°F)  
50  
70  
90  
lbs./day ( kg/day )  
Reference without *marks  
70  
80  
90  
100  
*1471 (667)  
1453 (659)  
1448 (657)  
1408 (639)  
1448 (657)  
1417 (643)  
*1392 (631)  
1365 (619)  
1354 (614)  
1290 (585)  
1277 (579)  
1171 (531)  
SHAPE OF ICE  
Crescent Cube  
ICE PRODUCTION PER CYCLE  
APPROXIMATE STORAGE CAPACITY  
ELECTRIC & WATER CONSUMPTION  
ELECTRIC W (kWH/100 lbs.)  
WATER gal./24HR (gal./100 lbs.)  
EXTERIOR DIMENSIONS (WxDxH)  
EXTERIOR FINISH  
28.0 lbs. (12.7 kg) 1440 pcs.  
N/A  
90/70°F  
2640(4.6)  
267(19.2)  
70/50°F  
2410(3.9)  
491(33.4)  
30" x 27.4" x 41.7" (762 x 695 x 1059 mm)  
Stainless Steel, Galvanized Steel (Rear)  
Net 259 lbs. (117 kg), Shipping 316 lbs. (143 kg)  
Permanent - Connection  
WEIGHT  
CONNECTIONS - ELECTRIC  
- WATER SUPPLY  
Inlet  
1/2" FPT  
- DRAIN  
Outlet  
3/4" FPT  
3/8" OD Tube  
CUBE CONTROL SYSTEM  
HARVESTING CONTROL SYSTEM  
ICE MAKING WATER CONTROL  
COOLING WATER CONTROL  
BIN CONTROL SYSTEM  
COMPRESSOR  
CONDENSER  
EVAPORATOR  
REFRIGERANT CONTROL  
Float Switch  
Hot Gas and Water, Thermistor and Timer  
Timer Controlled. Overflow Pipe  
N/A  
Thermostat  
Hermetic, Model CS18K6E-TF5  
Air-Cooled Remote, Condenser Unit URC-21F  
Vertical type, Stainless Steel and Copper  
Thermostatic Expansion Valve  
Condensing Pressure Regulator on URC-21F  
R-404A, 24 lb. 4.0 oz. (11,000g)  
(Icemaker 14 lbs. 8.8 oz. Cond. Unit 9 lb. 11.2 oz.)  
High 467PSIG, Low 230PSIG  
High Voltage Cut-out ( Internal )  
Auto-reset Overload Protector ( Internal )  
Auto-reset High Pressure Control Switch  
Float Switch  
REFRIGERANT CHARGE  
DESIGN PRESSURE  
P.C. BOARD CIRCUIT PROTECTION  
COMPRESSOR PROTECTION  
REFRIGERANT CIRCUIT PROTECTION  
LOW WATER PROTECTION  
ACCESSORIES -SUPPLIED  
-REQUIRED  
N/A  
Ice Dispenser or Ice Storage Bin, Remote Condenser Unit  
OPERATING CONDITIONS  
VOLTAGE RANGE  
187 - 253 V  
AMBIENT TEMP.  
WATER SUPPLY TEMP.  
WATER SUPPLY PRESSURE  
45 -100° F  
45 - 90° F  
10 - 113 PSIG  
Note: We reserve the right to make changes in specifications and design without prior  
notice.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. KM-1601MRH3 with URC-22F  
AC SUPPLY VOLTAGE  
AMPERAGE  
208-230/60/3  
8.4 A ( 5 Min. Freeze AT 104°F / WT 80°F)  
MINIMUM CIRCUIT AMPACITY  
MAXIMUM FUSE SIZE  
APPROXIMATE ICE PRODUCTION  
PER 24 HR.  
20 A  
20 A  
Ambient  
WATER TEMP. (°F)  
Temp.(°F)  
50  
70  
90  
lbs./day ( kg/day )  
Reference without *marks  
70  
80  
90  
100  
*1486 (674)  
1465 (664)  
1458 (661)  
1422 (645)  
1458 (661)  
1422 (645)  
*1391 (631)  
1365 (619)  
1366 (620)  
1300 (590)  
1280 (581)  
1178 (534)  
SHAPE OF ICE  
Crescent Cube  
ICE PRODUCTION PER CYCLE  
APPROXIMATE STORAGE CAPACITY  
ELECTRIC & WATER CONSUMPTION  
ELECTRIC W (kWH/100 lbs.)  
WATER gal./24HR (gal./100 lbs.)  
CEC/CEE TIER LEVEL  
ENERGY STAR  
28.3 lbs. (12.8 kg) 1440 pcs.  
N/A  
90/70°F  
2640(4.55)  
267(19.2)  
2
70/50°F  
2460(3.97)  
498(33.5)  
YES  
EXTERIOR DIMENSIONS (WxDxH)  
EXTERIOR FINISH  
WEIGHT  
CONNECTIONS - ELECTRIC  
- WATER SUPPLY  
30" x 27.4" x 41.7" (762 x 695 x 1059 mm)  
Stainless Steel, Galvanized Steel (Rear)  
Net 259 lbs. (117 kg), Shipping 316 lbs. (143 kg)  
Permanent - Connection  
Inlet  
1/2" FPT  
- DRAIN  
Outlet  
3/4" FPT  
3/8" OD Tube  
CUBE CONTROL SYSTEM  
HARVESTING CONTROL SYSTEM  
ICE MAKING WATER CONTROL  
COOLING WATER CONTROL  
BIN CONTROL SYSTEM  
COMPRESSOR  
CONDENSER  
EVAPORATOR  
REFRIGERANT CONTROL  
Float Switch  
Hot Gas and Water, Thermistor and Timer  
Timer Controlled. Overflow Pipe  
N/A  
Thermostat  
Hermetic, Model CS18K6E-TF5  
Air-Cooled Remote, Condenser Unit URC-22F  
Vertical type, Stainless Steel and Copper  
Thermostatic Expansion Valve  
Condensing Pressure Regulator on URC-22F  
R-404A, 22 lb. 4.3 oz. (10,100g)  
(Icemaker 14 lbs. 8.8 oz. Cond. Unit 7 lb. 11.5 oz.)  
High 467PSIG, Low 230PSIG  
High Voltage Cut-out ( Internal )  
Auto-reset Overload Protector ( Internal )  
Auto-reset High Pressure Control Switch  
Float Switch  
REFRIGERANT CHARGE  
DESIGN PRESSURE  
P.C. BOARD CIRCUIT PROTECTION  
COMPRESSOR PROTECTION  
REFRIGERANT CIRCUIT PROTECTION  
LOW WATER PROTECTION  
ACCESSORIES -SUPPLIED  
-REQUIRED  
N/A  
Ice Dispenser or Ice Storage Bin, Remote Condenser Unit  
OPERATING CONDITIONS  
VOLTAGE RANGE  
187 - 253 V  
AMBIENT TEMP.  
45 -100° F  
WATER SUPPLY TEMP.  
WATER SUPPLY PRESSURE  
45 - 90° F  
10 - 113 PSIG  
Note: We reserve the right to make changes in specifications and design without prior  
notice.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Condenser Unit  
1. URC-21F, URC-22F  
AC SUPPLY VOLTAGE  
FAN MOTOR  
115/60/1 (Connection to Icemaker)  
115 V Total 2.6FLA 130W  
(WxDxH) 46-3/8" x 15-11/16" x 25-15/16" (1178 x 398 x 659 mm)  
EXTERIOR DIMENSIONS  
DIMENSIONS INCLUDING LEGS (WxDxH) 48-7/16" x 18-1/8" x 40-7/8" (1230 x 460 x 1039 mm)  
EXTERIOR FINISH  
WEIGHT  
Galvanized Steel  
URC-21F Net 158 lbs. (72 kg )  
URC-22F Net 134 lbs. (61 kg )  
Permanent - Connection  
Shipping 169 lbs. ( 77 kg )  
Shipping 145 lbs. ( 66 kg )  
CONNECTIONS - ELECTRIC  
- REFRIGERANT  
Discharge Line 1-1/16"-12 UNF Fitting (#10 PARKER)  
Liquid Line 5/8"-18 UNF Fitting (#6 PARKER)  
CONDENSER  
Air-cooled, Fin and tube type  
Thermal Protection  
FAN MOTOR PROTECTION  
REFRIGERANT CONTROL  
REFRIGERANT CHARGE  
Condensing Pressure Regulator  
URC-21F R-404A  
URC-22F R-404A  
High 467 PSIG  
VOLTAGE RANGE  
9 lb. 11 oz. (4400g)  
7 lb. 11.5 oz. (3500g)  
DESIGN PRESSURE  
32.2 Bar  
OPERATING CONDITIONS  
104 ~ 127 VAC  
-20 ~ 122 °F  
AMBIENT TEMP.  
Leg  
ACCESSORIES -SUPPLIED  
2 pcs  
8 pcs  
8 pcs  
Hex. Head Bolt w/Washer 8 x 16  
Hex. Nut  
8
Note: We reserve the right to make changes in specifications and design without prior  
notice.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
II. General Information  
A. Construction  
1. KM-1601MRH, KM-1601MRH3  
Inlet Water Valve  
Spray Tube  
Water Supply Inlet  
Hot Gas Valve  
Junction Box  
Check Valve  
Evaporator  
Expansion Valve  
Cleaning Valve  
Control Box  
Line Valve  
Receiver  
Control Switch  
Bin Control  
Thermostat  
Capacitor Box  
Float Switch  
Water Pump  
(KM-1601MRH)  
Transformer Box  
(KM-1601MRH3)  
Drier  
Compressor  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. URC-21F, URC-22F  
Fan Blade  
Condenser Fan Motors  
Fan Blade  
Condenser  
Headmaster  
(C.P.R.)  
Junction Box  
Discharge Line  
Connection  
Liquid Line  
Connection  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Sequence of Operation  
1. Sequence Cycles and Shutdown  
The steps in the sequence are as outlined below. When power is supplied, a 5-second  
delay occurs at startup. Note that the order of the LEDs from the outer edge of the control  
board is 1, 4, 3, 2.  
a) One Minute Fill Cycle  
LED 4 is on. WV opens and the fill period begins. After 1 minute, the control board  
checks for a closed F/S. If F/S is closed, the harvest cycle begins. If not, WV will remain  
energized through additional 1 minute cycles until water enters the sump and F/S closes.  
This serves as a low water safety to protect the water pump.  
b) Initial Harvest Cycle  
LEDs 1, 4, and 2 are on. WV remains open, Comp and FMR energize, HGV opens,  
and harvest begins. As the evaporator warms, the thermistor located on the suction  
line checks for a 48°F (9°C) temperature. When 48°F (9°C) is reached, a 3.9 kΩ signal  
turns the harvest over to the adjustable harvest timer which is factory set for normal  
conditions. The timer has settings of 60, 90, 120, and 180 seconds (dip switch 1 & 2). The  
water valve is open during harvest for a maximum of 6 minutes or the length of harvest,  
whichever is shorter. When the harvest timer completes its count down, the harvest cycle  
is complete and the freeze cycle starts. The minimum total time allowed by the control  
board for a complete harvest cycle is 2 minutes.  
c) Freeze Cycle  
LED 1 is on. Comp and FMR continue to run, PM and FMS energize, LLV opens, HGV  
and WV close and the freeze cycle starts. For the first 5 minutes the control board will not  
accept a signal from F/S. This 5 minute minimum freeze acts as a short cycle protection.  
At the end of 5 minutes, F/S assumes control. As ice builds on the evaporator the water  
level in the sump lowers. The freeze continues until F/S opens and terminates ice  
production.  
d) Pump-Out Cycle  
LEDs 1, 3, and 2 are on. Comp and FMR continue to run, HGV opens, LLV closes, and  
FMS deenergizes. PM stops for 2 seconds and reverses, taking water from the bottom of  
the sump and forcing pressure against the check valve seat allowing water to go through  
the check valve and down the drain. At the same time water flows through the small  
tube to power flush the F/S. When the pump-out timer stops counting, the pump out is  
complete.  
Pump out always occurs on the 2nd harvest after startup. Then, depending on the control  
board setting, pump out occurs every cycle, or every 2nd, 5th or 10th cycle (dip switch  
5 & 6).  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
e) Normal Harvest Cycle  
LEDs 1, 4, and 2 are on. Comp and FMR continue to run, HGV remains open and WV  
opens. As the evaporator warms, the thermistor reaches 48°F (9°C). The control board  
then receives the thermistor's 3.9 kΩ signal and starts the harvest timer. The water valve  
is open during harvest for a maximum of 6 minutes or the length of harvest, whichever is  
shorter. When the harvest timer completes its count down, the harvest cycle is complete  
and the next freeze cycle starts. The unit continues to cycle through 3, 4 and 5 sequence  
until the bin control senses ice and shuts the unit down.  
Legend: Comp–compressor; FMR–remote fan motor; FMS–self-contained fan motor;  
F/S–float switch; HGV–hot gas valve; LLV–Liquid Line Valve; PM–pump motor;  
WV–inlet water valve  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Sequence Flow Chart  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Control Board  
A Hoshizaki exclusive solid-state control is employed in KM-1601MRH and  
KM-1601MRH3 Modular Crescent Cubers.  
All models are pretested and factory-adjusted.  
CAUTION  
1. The control board is fragile; handle very carefully.  
2. The control board contains integrated circuits, which are susceptible to failure  
due to static discharge. It is especially important to touch the metal part of  
the unit when handling or replacing the control board.  
3. Do not touch the electronic devices on the control board or the back of the  
control board.  
4. Do not change wiring and connections. Do not misconnect K3, K4 and K5,  
because the same connector is used for the thermistor and float switch. K4 is  
not connected.  
5. Always replace the whole control board assembly if it goes bad.  
6. Do not short out power supply to test for voltage.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Control Board Layout  
"E" Control Board  
Output Test Switch  
(used to test relays on control  
board)  
Dip Switch  
Alarm Reset Switch  
Backup Freeze  
Timer LED  
Connector K3  
Harvest Control  
(thermistor)  
Backup Harvest  
Timer LED  
Connector K4  
Open  
(not connected)  
Alarm Buzzer  
Power LED  
Microprocessor  
(control board  
revision level  
indicated by last 2  
digits on label)  
(lights when  
power is supplied  
to the control  
board)  
Relay LEDs (4)  
(indicate which  
Connector K5  
Float Switch  
relays are energized  
as listed below)  
Part Number  
Connector K1  
LED 2  
Hot Gas Valve (HGV)  
Self-Contained Fan  
Motor (FMS) (FMS  
off when LED on)  
Pins #1 through #10  
#1, 9 Magnetic Contactor  
#2 Hot Gas Valve  
#3 Line Valve  
Self-Contained Fan Motor (FMS)  
#4 Pump Motor (icemaking)  
#5 Pump Motor (drain)  
#6 Water Valve  
#7, 10 Power (line, bin control)  
#8 Open  
LED 3  
Pump Motor (PM)  
(on at pump out only)  
LED 4  
Water Valve (WV)  
LED 1  
Switch for "C" and  
"ALPINE" control board  
(service control boards only)  
Compressor (Comp)  
Remote Fan Motor  
(FMR)  
Transformer  
Connector  
Control Board  
Part Number  
2A1410-01 (factory); 2A1410-02 (service)  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. LED Lights and Audible Alarm Safeties  
The red LED indicates proper control voltage and will remain on unless a control voltage  
problem occurs. At startup a 5 second delay occurs while the control board conducts an  
internal timer check. A short beep occurs when the power switch is turned OFF.  
The green LEDs 1 through 4 energize and sequence from initial startup as listed in the  
table below. Note that the order of the LEDs from the outer edge of the control board is 1,  
4, 3, 2. For more information, see "II.B. Sequence of Operation."  
Time LEDs are On  
Energized  
Components  
Sequence Step  
LED  
Min.  
Max.  
Avg.  
1 Minute Fill Cycle 4  
WV  
60 seconds  
2 minutes 20 minutes 3 to 5 minutes  
Harvest Cycle  
1, 4, and 2 WV, HGV,  
Comp, FMR  
Freeze Cycle  
1
Comp, PM, 5 minutes freeze timer 30 to 35 minutes  
FMR/FMS,  
LLV  
setting  
Reverse Pump Out 1, 3, and 2 Comp, HGV, 10 seconds 20 seconds factory setting  
PM, FMR  
The built in safeties shut down the unit and have alarms as follows:  
No. of Beeps  
Type of Alarm  
Notes  
(every 3 sec.)  
1
High Evaporator Temp.  
(temperature > 127°F)  
(53°C)  
Check for harvest problem (stuck HGV or  
relay), hot water entering unit, stuck HM,  
or shorted thermistor.  
2
3
Harvest Backup Timer  
(harvest > 20 min. for two Check for open thermistor, HGV not  
cycles in a row)  
Orange LED marked H TIMER lights up.  
opening, TXV leaking by, low charge, or  
inefficient compressor.  
Freeze Timer  
Yellow LED marked F TIMER lights up.  
(freeze > specified setting Check for F/S stuck closed (up), WV  
for two cycles in a row) leaking by, HGV leaking by, TXV not  
Timer is factory set using feeding properly, low charge, HM not  
dip switches 9 & 10 bypassing, or inefficient compressor.  
To manually reset the above safeties, press the alarm reset button with the power  
supply on.  
6
Low Voltage  
(92Vac 5% or less)  
Red LED will turn off if voltage protection  
operates.  
The control voltage safeties automatically  
reset when voltage is corrected.  
7
High Voltage  
(147Vac 5% or more)  
Legend: Comp–compressor; FMR–remote fan motor; FMS–self-contained fan motor;  
F/S–float switch; HGV–hot gas valve; HM–headmaster (C.P.R.); LLV–Liquid  
Line Valve; PM–pump motor; TXV–thermostatic expansion valve; WV–inlet  
water valve  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Controls and Adjustments  
CAUTION  
Dip switches are factory set. Failure to maintain factory settings may adversely  
affect performance and warranty coverage. For more information, contact  
Hoshizaki Technical Support at 1-800-233-1940.  
a) Default Dip Switch Settings  
The dip switch is factory-adjusted to the following positions:  
Dip Switch No.  
1
2
3
4
5
6
7
8
9
10  
KM-1601MRH/3 OFF OFF ON OFF ON ON OFF OFF OFF ON  
Freeze Timer (9 & 10)  
Normally in the OFF position.  
Pump-Out Frequency Control (5 & 6)  
Pump-Out Timer (3 & 4)  
Harvest Timer (1 & 2)  
b) Harvest Timer (dip switch 1 & 2)  
The harvest timer starts counting when the thermistor reads 48°F (9°C) at the evaporator  
outlet and sends a 3.9 kΩ signal to the control board.  
No adjustment is required under normal use, as the harvest timer is adjusted to the  
suitable position. However, a setting longer than the factory setting may be advised in  
cases where the flush provided at harvest needs to be prolonged for extra cleaning.  
Before changing this setting, call the Hoshizaki Technical Support Department at  
1-800-233-1940 for recommendations. Keep in mind that setting the harvest timer to a  
longer setting will decrease 24 hour production.  
Dip Switch Setting  
Time  
(seconds)  
No. 1  
OFF  
ON  
OFF  
ON  
No. 2  
OFF  
OFF  
ON  
60  
90  
120  
180  
ON  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
c) Pump-Out Timer (dip switch 3 & 4)  
When a freeze cycle is completed, the pump motor stops, and the icemaker resumes  
operation in 2 seconds. Then, during cycles when a pump out is called for, the pump  
motor drains the water tank for the time determined by the pump-out timer. The pump-out  
timer also acts in place of the harvest timer during cycles with a pump out.  
The pump-out timer is factory-adjusted, and no adjustment is required.  
Time (seconds)  
Dip Switch Setting  
T1  
10  
10  
10  
20  
No. 3  
OFF  
ON  
OFF  
ON  
No. 4  
OFF  
OFF  
ON  
T2  
150  
180  
120  
180  
ON  
T1: Time to drain the water tank  
T2: Harvest timer at pump out  
Pump out always occurs on the 2nd harvest after startup. Then, depending on the  
pump-out frequency control setting (dip switch 5 & 6), pump out occurs every cycle, or  
every 2nd, 5th or 10th cycle.  
d) Pump-Out Frequency Control (dip switch 5 & 6)  
The pump motor drains the water tank at the frequency set by the pump-out frequency  
control.  
The pump-out frequency control is factory-adjusted to drain the water tank every 10  
cycles, and no adjustment is required. However, where water quality is bad and the  
icemaker needs a pump drain more often, the pump-out frequency can be adjusted as  
shown in the table below:  
Dip Switch Setting  
Frequency  
No. 5  
OFF  
ON  
OFF  
ON  
No. 6  
OFF  
OFF  
ON  
every cycle  
every 2 cycles  
every 5 cycles  
every 10 cycles  
ON  
e) Factory Use (S4 dip switch 7 & 8)  
Factory set for proper operation. Do not adjust. This must be left in the factory default  
position.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
f) Freeze Timer (dip switch 9 & 10)  
CAUTION  
Adjust to proper specification, or the unit may not operate correctly.  
The freeze timer setting determines the maximum allowed freeze time to prevent possible  
freeze-up issues. Upon termination of freeze timer, machine initiates the harvest cycle.  
After 2 consecutive timer terminations, machine will shut down, possibly indicating a  
problem.  
The freeze timer is factory adjusted and no adjustment is required.  
Dip Switch Setting  
Time  
(minutes)  
No. 9  
OFF  
OFF  
ON  
No. 10  
OFF  
ON  
OFF  
ON  
60  
50  
70  
60  
ON  
D. Control Switch  
The control switch has three positions: "OFF" for power off, "ICE" for icemaking, and  
"WASH" to activate the water pump when cleaning and sanitizing.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
III.Technical Information  
A. Water Circuit and Refrigeration Circuit  
1. KM-1601MRH, KM-1601MRH3  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Wiring Diagrams  
1. KM-1601MRH  
*
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. KM-1601MRH3  
*
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Performance Data  
1. KM-1601MRH with URC-21F  
APPROXIMATE ICE  
PRODUCTION PER 24 HR.  
WATER TEMP. (ºF/ºC)  
70/21  
AMBIENT TEMP.  
(ºF/ºC)  
50/10  
90/32  
70/21  
80/27  
1508  
1489  
684  
675  
1483  
1450  
673  
658  
1399  
1338  
634  
607  
90/32  
100/38  
1483  
1449  
673  
657  
1422  
1398  
645  
634  
1320  
1227  
599  
557  
lbs./day kg./day  
APPROXIMATE ELECTRIC  
CONSUMPTION  
70/21  
80/27  
90/32  
2450  
2499  
2514  
2494  
2514  
2599  
2670  
2669  
2532  
2577  
2665  
2660  
watts  
100/38  
70/21  
APPROXIMATE WATER  
CONSUMPTION PER 24 HR.  
483  
434  
418  
1.83  
1.64  
1.58  
418  
334  
263  
1.58  
1.26  
1.00  
363  
296  
217  
1.37  
1.12  
0.82  
80/27  
90/32  
gal./day m3/day  
100/38  
335  
1.27  
252  
0.95  
174  
0.66  
FREEZING CYCLE TIME  
70/21  
80/27  
23  
24  
24  
25  
26  
27  
90/32  
100/38  
70/21  
24  
24  
27  
27  
28  
30  
min.  
HARVEST CYCLE TIME  
5.3  
4.6  
4.1  
80/27  
90/32  
4.8  
4.6  
3.6  
2.8  
3.4  
2.5  
min.  
100/38  
70/21  
80/27  
90/32  
3.7  
2.8  
2.2  
HEAD PRESSURE  
200  
211  
215  
14.1  
14.9  
15.1  
215  
234  
251  
15.1  
16.5  
17.6  
231  
249  
266  
16.3  
17.5  
18.7  
PSIG kg/cm2G  
100/38  
70/21  
80/27  
90/32  
100/38  
217  
35  
36  
37  
37  
15.3  
2.5  
2.6  
2.6  
2.6  
254  
37  
39  
41  
41  
17.9  
2.6  
2.7  
2.9  
2.9  
281  
39  
41  
43  
45  
19.8  
2.7  
2.9  
3.0  
3.2  
SUCTION PRESSURE  
PSIG kg/cm2G  
TOTAL HEAT OF REJECTION FROM CONDENSER  
23,400 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
3,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
441 CU. IN (URC-21F)  
TOTAL HEAT OF REJECTION FROM COMPRESSOR  
CONDENSER VOLUME  
Note:  
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold  
should be used for reference only.  
2. We reserve the right to make changes in specifications and design without prior  
notice.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. KM-1601MRH with URC-22F  
APPROXIMATE ICE  
PRODUCTION PER 24 HR.  
WATER TEMP. (ºF/ºC)  
70/21  
AMBIENT TEMP.  
(ºF/ºC)  
50/10  
90/32  
70/21  
80/27  
1493  
1476  
677  
670  
1471  
1441  
667  
654  
1410  
1364  
640  
619  
90/32  
100/38  
1471  
1449  
667  
657  
1417  
1400  
643  
635  
1346  
1280  
610  
581  
lbs./day kg./day  
APPROXIMATE ELECTRIC  
CONSUMPTION  
70/21  
80/27  
90/32  
2590  
2623  
2634  
2642  
2634  
2692  
2740  
2752  
2687  
2741  
2792  
2840  
watts  
100/38  
70/21  
APPROXIMATE WATER  
CONSUMPTION PER 24 HR.  
521  
464  
446  
1.97  
1.75  
1.69  
446  
346  
264  
1.69  
1.31  
1.00  
396  
327  
230  
1.50  
1.24  
0.87  
80/27  
90/32  
gal./day m3/day  
100/38  
355  
1.34  
256  
0.97  
200  
0.76  
FREEZING CYCLE TIME  
70/21  
80/27  
22  
23  
24  
25  
25  
27  
90/32  
100/38  
70/21  
24  
24  
26  
27  
28  
30  
min.  
HARVEST CYCLE TIME  
5.4  
4.7  
4.2  
80/27  
90/32  
4.8  
4.7  
3.8  
3.0  
3.5  
2.6  
min.  
100/38  
70/21  
80/27  
90/32  
3.8  
2.9  
2.2  
HEAD PRESSURE  
205  
215  
218  
14.4  
15.1  
15.3  
218  
236  
250  
15.3  
16.6  
17.6  
233  
249  
265  
16.4  
17.5  
18.6  
PSIG kg/cm2G  
100/38  
70/21  
80/27  
90/32  
100/38  
220  
38  
39  
40  
40  
15.5  
2.7  
2.8  
2.8  
2.8  
254  
40  
42  
43  
44  
17.8  
2.8  
2.9  
3.1  
3.1  
279  
42  
44  
46  
48  
19.6  
3.0  
3.1  
3.2  
3.4  
SUCTION PRESSURE  
PSIG kg/cm2G  
TOTAL HEAT OF REJECTION FROM CONDENSER  
27,400 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
3,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
214 CU. IN.  
TOTAL HEAT OF REJECTION FROM COMPRESSOR  
CONDENSER VOLUME  
Note:  
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold  
should be used for reference only.  
2. We reserve the right to make changes in specifications and design without prior  
notice.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. KM-1601MRH3 with URC-21F  
APPROXIMATE ICE  
PRODUCTION PER 24 HR.  
WATER TEMP. (ºF/ºC)  
70/21  
AMBIENT TEMP.  
(ºF/ºC)  
50/10  
90/32  
70/21  
80/27  
1471  
1453  
667  
659  
1448  
1417  
657  
643  
1354  
1290  
614  
585  
90/32  
100/38  
1448  
1408  
657  
639  
1392  
1365  
631  
619  
1277  
1171  
579  
531  
lbs./day kg./day  
APPROXIMATE ELECTRIC  
CONSUMPTION  
70/21  
80/27  
90/32  
2410  
2461  
2477  
2460  
2477  
2566  
2640  
2641  
2503  
2555  
2645  
2650  
watts  
100/38  
70/21  
APPROXIMATE WATER  
CONSUMPTION PER 24 HR.  
491  
441  
426  
1.86  
1.67  
1.61  
426  
339  
267  
1.61  
1.28  
1.01  
368  
299  
218  
1.39  
1.13  
0.83  
80/27  
90/32  
gal./day m3/day  
100/38  
340  
1.29  
256  
0.97  
173  
0.66  
FREEZING CYCLE TIME  
70/21  
80/27  
23  
23  
24  
25  
26  
27  
90/32  
100/38  
70/21  
24  
24  
27  
27  
29  
31  
min.  
HARVEST CYCLE TIME  
5.7  
4.9  
4.4  
80/27  
90/32  
5.1  
4.9  
3.9  
3.1  
3.6  
2.7  
min.  
100/38  
70/21  
80/27  
90/32  
4.0  
3.0  
2.3  
HEAD PRESSURE  
203  
214  
218  
14.3  
15.1  
15.3  
218  
237  
253  
15.3  
16.7  
17.8  
242  
263  
279  
17.0  
18.5  
19.6  
PSIG kg/cm2G  
100/38  
70/21  
80/27  
90/32  
100/38  
224  
38  
40  
40  
40  
15.7  
2.7  
2.8  
2.8  
2.8  
259  
40  
43  
45  
45  
18.2  
2.8  
3.0  
3.2  
3.2  
303  
42  
44  
47  
48  
21.3  
2.9  
3.1  
3.3  
3.4  
SUCTION PRESSURE  
PSIG kg/cm2G  
TOTAL HEAT OF REJECTION FROM CONDENSER  
24,900 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
3,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
441 CU. IN (URC-21F)  
TOTAL HEAT OF REJECTION FROM COMPRESSOR  
CONDENSER VOLUME  
Note:  
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold  
should be used for reference only.  
2. We reserve the right to make changes in specifications and design without prior  
notice.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. KM-1601MRH3 with URC-22F  
APPROXIMATE ICE  
PRODUCTION PER 24 HR.  
WATER TEMP. (ºF/ºC)  
70/21  
AMBIENT TEMP.  
(ºF/ºC)  
50/10  
90/32  
70/21  
80/27  
1486  
1465  
674  
664  
1458  
1422  
661  
645  
1366  
1300  
620  
590  
90/32  
100/38  
1458  
1422  
661  
645  
1391  
1365  
631  
619  
1280  
1178  
581  
534  
lbs./day kg./day  
APPROXIMATE ELECTRIC  
CONSUMPTION  
70/21  
80/27  
90/32  
2460  
2500  
2513  
2510  
2513  
2582  
2640  
2647  
2553  
2605  
2671  
2700  
watts  
100/38  
70/21  
APPROXIMATE WATER  
CONSUMPTION PER 24 HR.  
498  
446  
430  
1.88  
1.69  
1.63  
430  
341  
267  
1.63  
1.29  
1.01  
375  
307  
223  
1.42  
1.16  
0.84  
80/27  
90/32  
gal./day m3/day  
100/38  
344  
1.30  
257  
0.97  
183  
0.69  
FREEZING CYCLE TIME  
70/21  
80/27  
23  
24  
25  
26  
26  
28  
90/32  
100/38  
70/21  
25  
25  
27  
28  
29  
31  
min.  
HARVEST CYCLE TIME  
4.7  
4.2  
3.7  
80/27  
90/32  
4.3  
4.2  
3.5  
2.9  
3.2  
2.5  
min.  
100/38  
70/21  
80/27  
90/32  
3.5  
2.8  
2.2  
HEAD PRESSURE  
210  
228  
233  
14.8  
16.0  
16.4  
233  
264  
290  
16.4  
18.6  
20.4  
249  
270  
300  
17.5  
19.0  
21.1  
PSIG kg/cm2G  
100/38  
70/21  
80/27  
90/32  
100/38  
231  
37  
39  
39  
39  
16.2  
2.6  
2.7  
2.7  
2.8  
292  
39  
41  
43  
44  
20.6  
2.7  
2.9  
3.1  
3.1  
310  
41  
44  
46  
48  
21.8  
2.9  
3.1  
3.2  
3.4  
SUCTION PRESSURE  
PSIG kg/cm2G  
TOTAL HEAT OF REJECTION FROM CONDENSER  
24,300 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
3,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
214 CU. IN.  
TOTAL HEAT OF REJECTION FROM COMPRESSOR  
CONDENSER VOLUME  
Note:  
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold  
should be used for reference only.  
2. We reserve the right to make changes in specifications and design without prior  
notice.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IV. Service Diagnosis  
WARNING  
1. This unit should be diagnosed and repaired only by qualified service  
personnel to reduce the risk of death, electric shock, serious injury, or fire.  
2. Risk of electric shock. Use extreme caution and exercise safe electrical  
practices.  
3. Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.  
4. CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews  
are securely in place after the unit is serviced. Make sure that none have  
fallen into the storage bin.  
5. Make sure all food zones in the icemaker and storage bin are clean after the  
unit is serviced. For cleaning procedures, see "VI. Cleaning and Maintenance  
Instructions."  
A. Diagnostic Procedure  
The diagnostic procedure is basically a sequence check which can be used at unit start-  
up or for system diagnosis. Using this check out procedure will allow you to diagnose  
electrical system and component failures in approximately 10 minutes under normal  
operating conditions of 70°F or warmer air and 50°F or warmer water temperatures.  
Before conducting a 10 minute checkout, check for correct installation, proper voltage per  
unit nameplate and adequate water supply. As you go through the procedure, check to  
assure the components energize and de-energize correctly. If not, those components and  
controls are suspect. Check for voltage at the 10-pin connector.  
1) Turn off the power supply, then access the control box. Clear any ice from bin control  
bulb.  
2) Turn on the power supply, then move the control switch to the "ICE" position. A 5 second  
delay occurs.  
3) One Minute Fill Cycle – The inlet water valve is energized. After 1 minute, the control  
board checks the float switch. If the float switch is closed, the unit cycles to harvest. If  
closed, continue to step 4. If the float switch is open, the unit repeats the 1 minute fill  
cycle until water enters and the float switch closes (low water safety protection during  
initial start up and at the end of each harvest). Diagnosis: If the water valve does not  
open, check for no supply voltage at water valve terminals, bad coil, or plugged screen  
or external filter (no water flow). If unit fails to start harvest, check for open float switch  
or bad 1 minute timer in control board.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4) Initial Harvest Cycle – Inlet water valve remains energized, contactor coil energizes to  
start the compressor (and fan motor on a remote condenser unit), and the hot gas valve  
energizes. The evaporator warms and the thermistor senses 48°F (9°C). The control  
board then receives the thermistor's 3.9 kΩ signal and turns operation of harvest over  
to the harvest timer. The timer completes counting (1 to 3 minutes). The unit then cycles  
to freeze. Diagnosis: Check if compressor is running, hot gas valve is open, water  
valve still open. Average harvest cycle at factory setting is 2 to 3 minutes. How long  
does initial harvest last? 1.5 minutes after initial harvest begins, touch the compressor  
discharge line. Is it hot? If not check refrigerant pressures and compressor operation.  
If it is hot, touch the inlet line to the evaporator. Is it hot? If it is hot and the freeze cycle  
is not starting, check the harvest timer adjustment, the thermistor for open circuit, the  
discharge line temperature, compressor efficiency, and if the hot gas valve is fully open.  
5) Freeze Cycle – compressor remains energized, pump motor, (line valve on remote  
condenser unit), and fan motor energize. The inlet water valve and hot gas valve  
de-energize. The unit is held in freeze by a 5 minute short cycle protection timer.  
After 5 minutes, the freeze cycle operation is transferred to the float switch for freeze  
termination. During the first 5 minutes of freeze, confirm that the evaporator temperature  
drops. After 7 minutes in freeze, remove the black float switch lead from the K5  
connector. The unit should immediately switch to the pump-out cycle. Diagnosis: If the  
evaporator is not cold, check to see if the hot gas valve is still open or if the expansion  
valve is not opening properly, if the water valve is continuing to fill the reservoir, if there  
are improper unit pressures, an inoperative compressor, or an inoperative headmaster  
(C.P.R.) (remote condenser unit only). If the unit remains in freeze with the float switch  
removed, replace the control board.  
Note: Normal freeze cycle will last 20 to 40 minutes depending on model and  
conditions. Cycle times and pressures should follow performance data provided in  
this manual.  
6) Pump-Out Cycle (10/20 second pump out) – the compressor remains energized,  
the hot gas valve energizes, the fan motor de-energizes, the pump motor stops for  
2 seconds and starts in reverse rotation for 10/20 seconds. (This removes contaminants  
from the water reservoir through the check valve (drain valve) and down the drain and  
allows for a power flush of the float switch.) Check for clear tubing at the check valve  
housing and check the unit drain for water flow. Diagnosis: If the pump motor does not  
reverse, check the circuit and capacitor. If water does not pump out, remove the check  
valve (drain valve) housing and check/clean the valve assembly.  
7) Normal Harvest Cycle – same as the initial harvest cycle – Return to step 4.  
Note: Unit continues to cycle until bin control is satisfied or power is switched OFF. (The  
pump out cycle can be adjusted to occur every cycle, or every 2, 5, or 10 cycles.  
The factory default is every 10 cycles.) The unit always restarts at the 1 minute fill  
cycle.  
8) Shutdown – When the unit is running hold ice in contact with the thermostatic bulb, the  
thermostatic bin control switch opens within 10 seconds, shutting down the unit. The bin  
control is factory set, and generally no adjustment is required. However, adjustment may  
be needed in some conditions, particularly at higher altitude locations. Diagnosis: See  
"IV.C. Bin Control Check."  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Control Board Check  
Before replacing a control board that does not show a visible defect and that you suspect  
is bad, always conduct the following check procedure. This procedure will help you verify  
your diagnosis.  
Alarm Reset: If the control board is in alarm (beeping), press the "ALARM RESET" button  
on the control board while the control board is beeping. WARNING! Risk  
of electric shock. Care should be taken not to touch live terminals.  
Once reset, the unit starts at the 1-minute fill cycle. For audible alarm  
information, see "II.C.2. LED Lights and Audible Alarm Safeties."  
1) Check the dip switch settings to assure that S4 dip switch #3, 4, 7, 8, 9, & 10 and S5 dip  
switch 1 through 5 are in the factory default position. S4 dip switch 1, 2, 5, & 6 are  
cleaning adjustments and the settings are flexible. For factory default settings, see  
"II.C.3. Default Dip Switch Settings."  
2) Move the control switch to the "ICE" position. If the red "POWER OK" LED is on, the  
control voltage is good. If the red "POWER OK" LED is off, clear ice away from the  
thermostatic bin control bulb in the storage bin area. If no ice is near the thermostatic  
bin control bulb or the red "POWER OK" LED does not come on even after clearing  
away ice, check the thermostatic bin control. See "IV.C. Bin Control Check." If the  
thermostatic bin control is okay (closed) and the red "POWER OK" LED is off, check the  
fuse, control switch contacts, high-pressure switch, and control transformer secondary  
circuit. Transformer output is 10.5V at 115V primary input. If the secondary circuit has  
proper voltage and the red LED is off, the control board is bad and should be replaced.  
If the secondary circuit does not have proper voltage, check the control transformer  
primary circuit. Check for 115V at the control board K1 ten-pin connector. Check the  
#10 pin (BR wire) to a white neutral wire for 115V. (Always choose a white neutral wire  
to establish a good neutral connection when checking voltages.) For additional checks,  
see "IV.F.1. No Ice Production."  
3) The "OUTPUT TEST" button provides a relay sequence test. Make sure the control  
switch is in the "ICE" position, then press the "OUTPUT TEST" button. The correct  
lighting sequence is 2, 3, 4, 1. Note that the order of the LEDs from the outer edge  
of the control board is 1, 4, 3, 2. Components (e.g., compressor) will cycle during the  
test. Following the test, the icemaker resumes operation. If the LEDs do not light as  
described above, the control board is bad and should be replaced.  
4) To verify voltage output from the control board to the components, slide the control  
board K1 ten-pin connector out far enough to allow multimeter lead contact. With the  
unit in the cycle to be tested, check output voltage from the corresponding pin on the  
control board K1 ten-pin connector to ground. If output voltage is not found and the  
appropriate LED is on, the control board is bad and should be replaced.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Bin Control Check  
To check the thermostatic bin control, follow the steps below.  
CAUTION  
When the ambient temperature is below 45°F (7°C), the thermostatic bin  
control switch opens and shuts down the icemaker even if the ice storage bin  
is empty. When the thermostat is set in the prohibited range, the icemaker  
operates continuously even if the ice storage bin is filled with ice. Setting in the  
prohibited range may result in severe damage to the icemaker.  
The thermostatic bin control is factory set, and generally no adjustment is required.  
However, adjustment may be needed in some conditions, particularly at higher altitude  
locations. Note that when the thermostatic bin control switch is open, the control board  
red "POWER OK" LED is off.  
1) Turn off the power supply.  
2) Remove the front panel, then move the control switch to the "OFF" position.  
3) Clear any ice away from the thermostatic bin control bulb.  
4) Remove the control box cover, then disconnect the thermostatic bin control wires from  
the thermostatic bin control switch.  
5) Hold your hand around the thermostatic bulb to warm it up.  
6) Check for continuity across the thermostatic bin control switch. If closed, continue to  
step 6. If open, adjust or replace the thermostatic bin control.  
7) With the multimeter test leads still in place, hold ice on the thermostatic bin control bulb  
to lower the temperature. Within 10 seconds, the thermostatic bin control switch should  
open (no continuity). If it remains closed, adjust or replace the thermostatic bin control.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
D. Float Switch Check and Cleaning  
The float switch is used to determine that there is sufficient water in the tank after the  
1-minute fill cycle and after each harvest cycle. The float switch is also used to determine  
that the appropriate volume of water has been converted into ice before switching out of  
the freeze cycle. No adjustment is required.  
1. Float Switch Check  
To check the float switch, follow the steps below.  
1) Turn off the power supply.  
2) Remove the front panel, then move the  
control switch to the "OFF" position.  
3) Remove the insulation panel, then remove  
the drain plug located on the lower front  
part of the ice chute. See Fig. 1. Allow the  
water tank to drain.  
4) Replace the drain plug in its correct  
position. Be careful not to cross thread it.  
5) Remove the control box cover.  
Ice Chute  
Drain Plug  
Float Switch Assembly  
6) Disconnect the black float switch  
connector from the control board BLACK  
K5 connector.  
Fig. 1  
7) Check for continuity across the float switch leads. With the water tank empty, the float  
switch should be open. If open, continue to step 8. If closed, follow the steps in "IV.D.2.  
Float Switch Cleaning." After cleaning the float switch, check it again. Replace if  
necessary.  
8) Reconnect the black float switch connector to the control board BLACK K5 connector,  
then replace the control box cover in its correct position.  
9) Move the control switch to the "ICE" position. Replace the insulation panel and the  
front panel in their correct positions, then turn on the power supply. After 1 minute, the  
1-minute fill cycle should end and the initial harvest cycle should begin. If the initial  
harvest cycle begins, the float switch is good and the check is complete. If the initial  
harvest cycle does not begin, continue to step 10.  
10) Turn off the power supply.  
11) Remove the front panel, then move the control switch to the "OFF" position.  
12) Remove the control box cover.  
13) Disconnect the black float switch connector from the control board BLACK K5 connector.  
14) Check for continuity across the float switch leads. With the water tank full, the float  
switch should be closed. If the float switch is closed and the icemaker will not switch  
from the 1-minute fill cycle to the initial harvest cycle, replace the control board.  
If open, confirm that the water tank is full. If the tank is not full, check the water supply,  
water filters, and inlet water valve. If the tank is full, follow the steps in "IV.D.2. Float  
Switch Cleaning." After cleaning the float switch, check it again. Replace if necessary.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Float Switch Cleaning  
Depending on local water conditions, scale may build up on the float switch. Scale on the  
switch can cause the float to stick. In this case, the float switch should be cleaned.  
1) Turn off the power supply.  
2) Remove the front panel, then move the control switch to the "OFF" position.  
3) Remove the insulation panel, then remove the drain plug located on the lower front part  
of the ice chute. See Fig. 1. Allow the water tank to drain.  
4) Replace the drain plug in its correct position. Be careful not to cross thread it.  
5) Disconnect the vent tube and the flush tube from the top of the float switch, then remove  
the float switch assembly from the mounting bracket and remove the rubber boot from  
the bottom of the float switch assembly. See Fig. 2.  
6) Remove the retainer rod from the bottom of the float switch assembly, then remove the  
float. Be careful not to bend the retainer rod excessively when removing it.  
7) Wipe down the float switch assembly's housing, shaft, float, and retainer rod with a  
mixture of 1 part Hoshizaki "Scale Away" and 25 parts warm water. Clean the inside of  
the rubber boot and hose with cleaning solution. Rinse the parts thoroughly with clean  
water.  
8) Reassemble the float switch assembly and replace it and the rubber boot in their correct  
positions. Reconnect the vent tube and the flush tube.  
9) Move the control switch to the "ICE" position.  
10) Replace the insulation panel and front panel in their correct positions.  
11) Turn on the power supply to start the automatic icemaking process.  
Vent  
Flush  
Shaft  
Float Switch  
Housing  
Float  
Retainer Rod  
Rubber Boot  
and Hose  
Fig. 2  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E.Thermistor Check  
To check thermistor resistance, follow the steps below.  
1) Turn off the power supply.  
2) Remove the front panel, then move the control switch to the "OFF" position.  
3) Remove the control box cover.  
4) Remove the thermistor.  
5) Immerse the thermistor sensor portion in a glass containing ice and water for 2 or  
3 minutes.  
6) Disconnect the white thermistor connector from the control board WHITE K3 connector  
and check the resistance between thermistor leads. Normal reading is within 4.7 to  
6.2 kΩ. If outside the normal reading, replace the thermistor. See "V.B. Important Notes  
for Component Replacement." If inside the normal reading, continue to the next step.  
7) Replace the thermistor in its correct position. See "V.B. Important Notes for Component  
Replacement."  
8) Reconnect the white thermistor connector to the control board WHITE K3 connector.  
9) Replace the control box cover in its correct position, then turn on the power supply.  
10) Move the control switch to the "ICE" position.  
11) Once the harvest cycle starts, begin timing the harvest cycle.  
12) The harvest timer should expire and terminate the harvest cycle within 2 to 3 minutes. If  
the harvest timer does not expire and terminate the harvest cycle, the harvest timer is  
bad and the control board should be replaced.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F. Diagnostic Charts  
Before consulting the diagnostic charts, check for correct installation, proper voltage per  
unit nameplate, and adequate water supply. Check CB using the steps in "IV.B. Control  
Board Check." Check the dip switch settings to assure that S4 dip switch 3, 4, 7, 8, 9,  
10, are in the factory default position. S4 dip switch 1, 2, 5, 6 are cleaning adjustments  
and the settings are flexible. For factory default settings, see "II.C.3.a) Default Dip Switch  
Settings."  
1. No Ice Production  
Problem  
Possible Cause  
Remedy  
[1] The icemaker will not a)Power Supply  
start.  
1. OFF position.  
1. Move to ON position.  
2. Tighten.  
2. Loose connection.  
3. Bad contacts.  
3. Check for continuity and  
replace.  
4. Voltage too high or too 4. Check and get  
low.  
recommended voltage.  
b)Fuse (Inside fused  
disconnect, if any)  
1. Blown.  
1. Check for short circuit and  
replace.  
c)Control Switch  
1. OFF position.  
2. Bad contacts.  
1. Move to ICE position.  
2. Check for continuity and  
replace.  
d)Bin Control Thermostat 1. Tripped with bin filled 1. Remove ice.  
with ice.  
2. Ambient temperature 2. Increase ambient  
too cool.  
temperature.  
3. Set too warm.  
3. See "IV.C. Bin Control  
Check."  
4. Bulb out of position.  
5. Bad contacts.  
4. Place in position.  
5. Check for continuity and  
replace.  
e)High Pressure Control 1. Bad contacts.  
1. Check for continuity and  
replace.  
2. Dirty air filter or  
condenser.  
2. Clean.  
3. Ambient or condenser 3. Reduce temperature.  
water temperature too  
warm.  
4. Refrigerant  
overcharged.  
4. Recharge.  
5. Fan not operating.  
5. See chart 1.[6]  
6. Refrigerant line or  
components plugged.  
6. Clean and replace drier.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Problem  
Possible Cause  
Remedy  
[1]  
The icemaker will not f) Transformer  
start. (continued).  
1. Coil winding opened 1. Replace.  
or shorted.  
g)Wiring to Control Board 1. Loose connections or 1. Check for continuity and  
open.  
replace.  
h)Thermistor  
1. Leads shorted or  
opened and high  
1. See "II.C.3. Controls and  
Adjustments, b) Harvest  
temperature or harvest Timer."  
backup timer safety  
operates. (1 beep or 2  
beep alarm)  
i) Hot Gas Valve  
1. Continues to open  
in freeze cycle and  
freeze timer safety  
operates. (3 beep  
alarm)  
1. Check for hot gas valve  
stuck open and replace.  
j) Water Supply Line  
1. Water supply off and 1. Check and get  
water supply cycle  
does not finish.  
recommended pressure.  
2. Condenser water  
pressure too low  
2. Check and get  
recommended pressure.  
or off and pressure  
control opens and  
closes frequently to  
finally operate high  
temperature safety.  
(1 beep alarm)  
k)Inlet Water Valve  
1. Mesh filter or orifice  
gets clogged and  
water supply cycle  
does not finish.  
1. Clean.  
2. Coil winding opened. 2. Replace.  
3. Wiring to water valve. 3. Check for loose  
connection or open, and  
replace.  
l) Control Board  
1. Defective.  
1. See "IV.B. Control Board  
Check."  
m)Interlock Switch  
(Cleaning Valve)  
1. OFF Position  
2. Bad contacts.  
1. Move to ON position.  
2. Check for continuity and  
replace.  
n)Wash Switch  
a)Float Switch  
1. WASH position.  
2. Bad contacts.  
1. Move to ICE position.  
2. Check and replace.  
1. Place in position.  
[2] Water continues to  
be supplied, and the  
icemaker will not  
start.  
1. Connector  
disconnected.  
2. Leads opened or  
defective switch.  
2. Check and replace.  
3. Float does not move 3. Clean or replace.  
freely.  
b)Control Board  
1. Defective.  
1. Replace.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Problem  
Possible Cause  
Remedy  
[3] Compressor will  
not start or stops  
operating.  
a)Magnetic Contactor  
1. Bad contacts.  
1. Check for continuity and  
replace.  
2. Coil winding opened. 2. Replace.  
b)Start Capacitor or Run 1. Defective.  
Capacitor  
1. Replace.  
c)Internal Overload  
1. Loose terminal.  
1. Tighten or replace.  
Protector Open (check  
1 through 3 to the right  
and d through f below)  
2. Voltage.  
2. Check and correct.  
3. Clean.  
3. Dirty condenser.  
d)Starter  
1. Bad contacts.  
1. Check and replace.  
2. Coil winding opened. 2. Replace.  
e)Compressor  
1. Wiring to compressor. 1. Check for loose  
connection or open, and  
replace.  
2. Defective.  
2. Replace.  
3. Protector tripped.  
3. Reduce temperature.  
f) Control Board  
a)Inlet Water Valve  
b)Control Board  
1. No power to contactor. 1. See "IV.B. Control Board  
Check."  
[4] Water continues to  
be supplied in freeze  
cycle.  
1. Diaphragm does not 1. Check for water leaks with  
close.  
icemaker off.  
1. Defective.  
1. See "IV.B. Control Board  
Check."  
[5] No water comes from a)Water Supply Line  
spray tubes. Water  
1. Water pressure too  
low and water level in  
water tank too low.  
1. Check and get  
recommended pressure.  
pump will not start, or  
freeze cycle time is  
too short.  
b)Inlet Water Valve  
1. Dirty mesh filter or  
orifice and water level  
in water tank too low.  
1. Clean.  
c)Water System  
1. Water leaks.  
1. Check connections for  
water leaks, and replace.  
2. Clogged.  
2. Clean.  
3. Pump out check valve 3. Check assembly and  
leaking by. clean.  
1. Motor winding opened. 1. Replace.  
d)Pump Motor  
2. Bearing worn out.  
3. Wiring to pump motor. 3. Check for loose  
connection or open, and  
2. Replace.  
replace.  
4. Defective capacitor.  
4. Replace.  
5. Defective or bound  
impeller.  
5. Replace and clean.  
6. Mechanical seal worn 6. Check and replace.  
out.  
e)Control Board  
1. Defective.  
1. See "IV.B. Control Board  
Check."  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Problem  
Possible Cause  
Remedy  
[6] Fan motor will  
not start, or is not  
operating.  
a)Fan Motor  
1. Motor winding opened. 1. Replace.  
2. Bearing worn out.  
3. Wiring to fan motor.  
2. Replace.  
3. Check for loose  
connection or open, and  
replace.  
4. Defective capacitor.  
5. Fan blade bound.  
1. Defective.  
4. Replace.  
5. Check and replace.  
b)Control Board  
a)Refrigerant  
1. See "IV.B. Control Board  
Check."  
[7] All components  
run, but no ice is  
produced.  
1. Undercharged.  
1. Check for leaks and  
recharge.  
2. Air or moisture  
trapped.  
2. Replace drier and  
recharge.  
b)Compressor  
1. Defective valve.  
1. Replace.  
c)Hot Gas Valve  
1. Continues to open in 1. Check and replace.  
freeze cycle.  
d)Line Valve  
1. Continues to close in 1. Check and replace.  
freeze cycle.  
e)Inlet Water Valve  
1. Water valve is wide  
open during freeze.  
1. Check for water leaks with  
icemaker off.  
f) Headmaster (C.P.R.)  
(Remote Unit)  
1. Not operating properly 1. Replace headmaster.  
and liquid line  
temperature too warm.  
2. Evaporator is Frozen Up  
Problem  
Possible Cause  
Remedy  
[1]Freeze cycle time is a)Float Switch  
too long.  
1. Leads short-circuit or 1. Check and replace.  
defective switch.  
2. Float does not move 2. Clean or replace.  
freely.  
b)Inlet Water Valve  
c) Control Board  
1. Diaphragm does not 1. Check for water leaks with  
close.  
icemaker off.  
1. Defective.  
1. See "IV.B. Control Board  
Check."  
[2]All ice formed on  
evaporator does not  
fall into bin in harvest  
cycle.  
a)Evaporator  
1. Scaled up.  
1. Clean.  
b)Water Supply Line  
1. Water pressure too  
low.  
1. Check and get  
recommended pressure.  
c) Water Filter System  
d)Inlet Water Valve  
1. Dirty/Restricted  
1. Replace filter.  
1. Clean.  
1. Dirty mesh filter or  
orifice.  
2. Diaphragm does not 2. Check for water leaks with  
close.  
icemaker off.  
e)Ambient and/or water 1. Too cool.  
temperature.  
1. Increase temperature.  
f) Line Valve  
1. Continues to open in 1. Check operation in harvest  
harvest cycle. cycle and replace.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Problem  
Possible Cause  
Remedy  
[2]All ice formed on  
ecaorator does not  
fall into bin in harvest.  
(continued).  
g)Thermistor  
1. Out of position or  
loose attachment.  
1. See "V.B. Important  
Notes for Component  
Replacement."  
h)Control Board  
a)Spray Tubes  
1. Harvest timer is set  
too short.  
1. Adjust longer, referring  
to "II.C.3. Controls and  
Adjustments, c) Harvest  
Timer.  
2. Defective.  
2. See "IV.B. Control Board  
Check."  
[3]Other  
1. Clogged.  
1. Clean  
2. Out of position.  
1. Dirty.  
2. Place in position.  
1. Clean.  
b)Water System  
c) Refrigerant  
1. Undercharged.  
1. Check for leaks and  
recharge.  
d)Expansion Valve  
e)Hot Gas Valve  
1. Bulb out of position or 1. Place in position.  
loose attachment.  
2. Defective.  
2. Replace.  
1. Coil winding opened. 1. Replace.  
2. Plunger does not  
move.  
2. Replace.  
3. Wiring to hot gas  
valve.  
3. Check for loose  
connection or open, and  
replace.  
f) Ice Cube Guide  
1. Out of position and ice 1. Place in position.  
trapped.  
g)Water Supply Line  
1. Too small; requires  
1/2" OD line dedicated  
per machine.  
1. Increase water line size.  
h)Water Filter  
1. Flow rate too small.  
1. Replace with filter that has  
larger flow rate.  
3. Low Ice Production  
Problem  
Possible Cause  
Remedy  
[1]Freeze cycle time is a)See chart 1.[3] and check dirty air filter or condenser, ambient or water  
long.  
temperature, water pressure, condenser water regulating valve (water-cooled  
model), and refrigerant charge.  
b)See chart 2.[1] and check float switch, inlet water valve and control board.  
c) Check pump, hot gas valve, headmaster (C.P.R.) (remote air-cooled model),  
expansion valve, refrigeration check valve, and compressor.  
[2]Harvest cycle time is a)See chart 2.[2] and check control board, thermistor, evaporator, ambient and/or  
long.  
water temperature, water supply line, inlet water valve, line valve, and gas valve.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Abnormal Ice  
Problem  
Possible Cause  
Remedy  
[1] Small cubes.  
a)Ice Cube Guide  
1. Out of position.  
Circulated water falls  
into bin.  
1. Place in position.  
b)See chart 1.[5] and check water supply line, inlet water valve, water system,  
pump motor, and control board.  
c) Pump Out Check Valve 1. Dirty.  
1. Clean.  
[2] Cloudy or irregular  
cubes.  
a)See chart 2.[1] and 2.[3], and check float switch, inlet water valve, control board,  
spray tubes, water system, refrigerant charge, and expansion valve.  
b)Spray Guide  
c) Water Quality  
1. Dirty.  
1. Clean.  
1. High hardness or  
contains impurities.  
1. Install a water softener or  
filter.  
5. Other  
Problem  
Possible Cause  
Remedy  
[1]Icemaker will not stop a)Bin Control Thermostat 1. Set too cold.  
when bin is filled with  
1. Adjust warmer.  
2. Defective.  
2. Replace  
ice.  
[2] Abnormal noise.  
a)Pump Motor  
b)Fan Motor  
1. Bearings worn out.  
1. Bearings worn out.  
1. Replace  
1. Replace  
2. Fan blade deformed. 2. Replace fan blade.  
3. Fan blade does not  
move freely.  
3. Replace.  
c) Compressor  
1. Bearings worn out or 1. Replace.  
cylinder valve broken.  
2. Mounting pad out of  
position.  
2. Reinstall.  
d)Refrigerant Lines  
1. Rub or touch other  
lines or surfaces.  
1. Replace.  
[3]Ice in storage bin  
often melts.  
a)Drain Line(s)  
1. Plugged.  
1. Clean.  
b)Icemaker and Bin  
1. Drains not run  
separately.  
1. Separate the drain lines.  
c) Ice Cube Guide  
1. Out of position.  
Circulated water falls  
into bin.  
1. Place in position.  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
V. Replacement of Components  
WARNING  
1. This unit should be diagnosed and repaired only by qualified service  
personnel to reduce the risk of death, electric shock, serious injury, or fire.  
2. Move the control switch to the "OFF" position and turn off the power supply  
before servicing. Lockout/Tagout to prevent the power from being turned back  
on inadvertently.  
3. CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews  
are securely in place after the unit is serviced. Make sure that none have  
fallen into the storage bin.  
4. Make sure all food zones in the icemaker and storage bin are clean after the  
unit is serviced. For cleaning procedures, see "VI. Cleaning and Maintenance  
Instructions."  
A. Service for Refrigerant Lines  
WARNING  
1. Repairs requiring the refrigeration circuit to be opened must be performed by  
properly trained and EPA-certified service personnel.  
2. Always recover the refrigerant and store it in an approved container. Do not  
discharge the refrigerant into the atmosphere.  
3. Use an electronic leak detector or soap bubbles to check for leaks. Add a  
trace of refrigerant to the system (if using an electronic leak detector), and  
then raise the pressure using nitrogen gas (140 PSIG). DO NOT use R-404A  
as a mixture with pressurized air for leak testing.  
CAUTION  
1. Do not leave the system open for longer than 15 minutes when replacing or  
servicing parts. The Polyol Ester (POE) oils used in R-404A units can absorb  
moisture quickly. Therefore it is important to prevent moisture from entering  
the system when replacing or servicing parts.  
2. Always install a new drier every time the sealed refrigeration system is  
opened.  
3. Do not replace the drier until after all other repair or replacement has been  
made. Install the new drier with the arrow on the drier in the direction of the  
refrigerant flow.  
4. When brazing, protect the drier by using a wet cloth to prevent the drier from  
overheating. Do not allow the drier to exceed 250°F (121°C).  
1. Refrigerant Recovery  
The icemaker is provided with refrigerant access valves. Using proper refrigerant practices,  
recover the refrigerant from the service valves and store it in an approved container. Do not  
discharge the refrigerant into the atmosphere.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Brazing  
WARNING  
1. R-404A itself is not flammable at atmospheric pressure and temperatures up  
to 176°F (80°C).  
2. R-404A itself is not explosive or poisonous. However, when exposed to high  
temperatures (open flames), R-404A can be decomposed to form hydrofluoric  
acid and carbonyl fluoride both of which are hazardous.  
3. Do not use silver alloy or copper alloy containing arsenic.  
4. Use an electronic leak detector or soap bubbles to check for leaks. Add a  
trace of refrigerant to the system (if using an electronic leak detector), and  
then raise the pressure using nitrogen gas (140 PSIG). DO NOT use R-404A  
as a mixture with pressurized air for leak testing.  
1) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.  
Note: Because the pipes in the evaporator case are specially coated to resist corrosion,  
it is important to make connections outside the evaporator case when possible. If  
it is necessary to braze inside the evaporator case, use sandpaper to remove the  
coating from the brazing connections before unbrazing the components.  
CAUTION  
1. Always install a new drier every time the sealed refrigeration system is  
opened.  
2. Do not replace the drier until after all other repair or replacement has been  
made. Install the new drier with the arrow on the drier in the direction of the  
refrigerant flow.  
3. When brazing, protect the drier by using a wet cloth to prevent the drier from  
overheating. Do not allow the drier to exceed 250°F (121°C).  
2) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of  
refrigerant to the system (if using an electronic leak detector), and then raise the  
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with  
pressurized air for leak testing.  
3. Evacuation and Recharge (R-404A)  
1) Attach a vacuum pump to the system. Be sure to connect the charging hoses to both  
high and low-side access valves.  
IMPORTANT  
The vacuum level and vacuum pump may be the same as those for current  
refrigerants. However, the rubber hose and gauge manifold to be used for  
evacuation and refrigerant charge should be exclusively for POE oils.  
2) Turn on the vacuum pump. Open the gauge manifold valves, then open the high and  
low-side access valves. Never allow the oil in the vacuum pump to flow backwards.  
3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends  
on pump capacity.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4) Close the low-side valve and high-side valve on the gauge manifold.  
5) Disconnect the gauge manifold hose from the vacuum pump and attach it to a  
refrigerant service cylinder. Remember to loosen the connection and purge the air from  
the hose. For refrigerant charge, see the rating label inside the icemaker. Hoshizaki  
recommends only virgin refrigerant or reclaimed refrigerant which meets ARI Standard  
700 (latest edition) be used.  
6) A liquid charge is required when charging an R-404A system (to prevent fractionation).  
Place the service cylinder on the scales; if the service cylinder is not equipped with  
a dip tube, invert the service cylinder, then place it on the scales. Open the high-side  
valve on the gauge manifold.  
7) Allow the system to charge with liquid until the proper charge weight is met.  
8) If necessary, add any remaining charge to the system through the low-side.  
CAUTION! To prevent compressor damage, use a throttling valve or liquid  
dispensing device to add the remaining liquid charge through the low-side  
access valve with the unit running.  
9) Close the high and low-side gauge manifold valves, then disconnect the gauge manifold  
hoses.  
10) Cap the access valves to prevent a possible leak.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Important Notes for Component Replacement  
CAUTION  
When replacing a component listed below, see the notes to help ensure proper  
operation.  
Component  
Notes  
Compressor  
Install a new start capacitor, run capacitor, and start relay.  
Expansion Valve • Attach the expansion valve bulb to the suction line in the same location as the previous  
bulb.  
• The bulb should be between the 10 and 2 o'clock positions on the tube.  
• Secure the bulb with the clamp and holder, then insulate it.  
Hot Gas Valve  
• Replace the strainer when replacing the hot gas valve.  
Liquid Line Valve  
• Use copper tube of the same diameter and length when replacing valve lines.  
Install a new capacitor.  
Fan Motor  
Pump Motor  
Thermistor  
Install a new capacitor.  
• Attach the new thermistor to the suction line in the same location as the previous  
thermistor.  
• The thermistor should be at the 12 o'clock position on the tube.  
• Smoothly fill the recessed area of the thermistor holder with high thermal conductive  
type sealant. Hoshizaki America part number 4A0683-01 (Silicone Heat Sink Compound  
10-8108 manufactured by GC Electronics), KE-4560 RTV (manufactured by ShinEtsu  
Silicones), or equivalent are recommended.  
• Secure the thermistor with the holder, then insulate it.  
• Be very careful to prevent damage to the leads.  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VI. Cleaning and Maintenance Instructions  
A. Cleaning and Sanitizing Procedures  
WARNING  
Ensure all components, fasteners and thumbscrews are securely in place after  
any maintenance or cleaning is done to the equipment.  
WARNING  
1. Hoshizaki recommends cleaning this unit at least once a year. More frequent  
cleaning, however, may be required in some existing water conditions.  
2. To prevent injury to individuals and damage to the icemaker, do not use  
ammonia type cleaners.  
3. Always wear liquid-proof gloves to prevent the cleaning and sanitizing  
solutions from coming into contact with skin.  
CAUTION  
1. The cleaning valve is used to allow solution flow to the inside of the  
evaporator during the cleaning and sanitizing operation. It should be closed  
for all icemaking operation. The compressor will not operate unless this valve  
is completely closed.  
2. To open the cleaning valve, the valve handle should be parallel to the valve  
body. To close the valve, the valve handle should be at a right angle to the  
valve body.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Cleaning Procedure  
1) Dilute 27 fl. oz. (800 ml) of Hoshizaki "Scale Away" with 5 gal. (19 l) of warm water.  
2) Remove all ice from the evaporator and the storage bin.  
Note: To remove cubes on the evaporator, turn off the power supply and turn it on  
after 3 minutes. The harvest cycle starts and the cubes will be removed from the  
evaporator.  
3) Turn off the power supply.  
4) Remove the front panel and then remove  
Rubber Cap  
the insulation panel by first removing the  
thumbscrew, lifting the panel slightly and  
Overflow Pipe  
pulling it toward you.  
5) Drain the water tank by removing the  
rubber cap covering the overflow pipe in  
the water tank. Remove the overflow pipe  
by turning it counterclockwise. See Fig. 3.  
Fig. 3  
6) Replace the removed parts in their correct positions.  
7) In bad or severe water conditions, clean the float switch assembly as described below.  
Otherwise, continue to step 8.  
a. Remove the float switch assembly from the mounting bracket and remove the  
rubber boot from the bottom of the assembly.  
b. Remove the retainer rod from the bottom of the float switch assembly, then remove  
the float. Be careful not to bend the retainer rod excessively when removing it.  
c. Wipe down the float switch assembly's housing, shaft, float, and retainer rod with  
cleaning solution. Wipe the inside of the rubber boot with cleaning solution.  
d. Reassemble the float switch assembly and replace it and the rubber boot in their  
correct positions.  
8) Pour the cleaning solution into the water tank.  
9) Fully open the cleaning valve on the left side wall of the machine compartment.  
10) Move the control switch (on the control box) to the "WASH" position.  
11) Replace the insulation panel and the front panel in their correct positions.  
Note: When replacing the insulation panel, do not catch the hose between the panel  
and the body.  
12) Turn on the power supply and start the washing process.  
13) Turn off the power supply after 30 minutes.  
14) Remove the front panel and the insulation panel.  
15) Drain the water tank. (See step 5 above). Replace the removed parts and the insulation  
panel in their correct positions.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
16) Move the control switch to the "ICE" position.  
17) Close the cleaning valve.  
Note: The icemaker will not operate unless the cleaning valve is completely closed.  
18) Replace the front panel in its correct position.  
19) Turn on the power supply to fill the water tank with water.  
20) Turn off the power supply after 3 minutes.  
21) Remove the front panel and fully open the cleaning valve.  
22) Move the control switch to the "WASH" position.  
23) Replace the front panel in its correct position.  
24) Turn on the power supply to rinse off the cleaning solution.  
25) Turn off the power supply after 5 minutes.  
26) Remove the front panel and insulation panel.  
27) Drain the water tank. (See step 5 above.) Replace the removed parts and the insulation  
panel in their correct positions.  
Note: Do not replace the insulation panel when you proceed to "2. Sanitizing  
Procedure."  
28) Repeat steps 16 through 27 three more times to rinse thoroughly.  
Note: If you do not sanitize the icemaker, go to step 9 in "2. Sanitizing Procedure."  
2. Sanitizing Procedure - Following Cleaning Procedure  
1) Dilute a 5.25% sodium hypochlorite solution (chlorine bleach) with water. (Add 2.5 fl. oz.  
(74 ml) of sanitizer to 5 gal. (19 l) of water).  
2) Pour the sanitizing solution into the water tank.  
3) Replace the insulation panel and the front panel in their correct positions.  
Note: Make sure that the control switch is in the "WASH" position and the cleaning valve  
is open.  
4) Turn on the power supply, and start the sanitizing process.  
5) Turn off the power supply after 15 minutes.  
6) Remove the front panel and the insulation panel.  
7) Drain the water tank. See step 5 in "1. Cleaning Procedure." Replace the removed parts  
and the insulation panel in their correct positions.  
8) Repeat steps 16 through 27 in "1. Cleaning Procedure" two times to rinse thoroughly.  
9) Close the cleaning valve.  
10) Move the control switch to the "ICE" position.  
11) Replace the front panel in its correct position.  
12) Clean the storage bin with water.  
13) Turn on the power supply and start the automatic icemaking process.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Maintenance  
IMPORTANT  
This icemaker must be maintained individually, referring to the instruction  
manual and labels provided with the icemaker.  
1. Stainless Steel Exterior  
To prevent corrosion, wipe the exterior occasionally with a clean and soft cloth. Use a  
damp cloth containing a neutral cleaner to wipe off oil or dirt build up.  
2. Storage Bin and Scoop  
• Wash your hands before removing ice. Use the plastic scoop provided.  
• The storage bin is for ice use only. Do not store anything else in the bin.  
• Keep the scoop clean. Clean it by using a neutral cleaner and rinse thoroughly.  
• Clean the bin liner by using a neutral cleaner. Rinse thoroughly after cleaning.  
3. Condenser  
Check the condenser once a year, and clean if required by using a brush or vacuum  
cleaner. More frequent cleaning may be required depending on the location of the  
condenser unit.  
C. Preparing the Icemaker for Long Storage  
WARNING  
When shutting off the icemaker for an extended time, drain out all water from  
the water tank and remove the ice from the storage bin. The storage bin should  
be cleaned and dried. Drain the icemaker to prevent damage to the water  
supply line at subfreezing temperatures, using air or carbon dioxide. Shut off  
the icemaker until the proper ambient temperature is resumed.  
Note: When the icemaker is not used for two or three days, it is sufficient to only  
move the control switch to the "OFF" position, unless the icemaker will be at  
subfreezing temperatures.  
1. Remove the water from the potable water supply line:  
1) Remove the front panel.  
2) Move the control switch (on the control box) to the "OFF" position.  
3) Wait 3 minutes.  
4) Close the potable water supply line shut-off valve and open the potable water supply  
line drain valve.  
5) Allow the line to drain by gravity.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6) Attach compressed air or carbon dioxide supply to the potable water line drain valve.  
7) Move the control switch to the "ICE" position.  
8) Blow the potable water line out using compressed air or carbon dioxide.  
2. Drain the potable water tank:  
1) Turn off the power supply.  
2) Move the control switch to the "OFF" position.  
3) Drain the water tank by removing the  
Rubber Cap  
insulation panel and the rubber cap  
covering the overflow pipe in the water  
Overflow Pipe  
tank. Remove the overflow pipe by turning  
it counterclockwise. See Fig. 4.  
4) Replace the removed parts in their correct  
positions.  
Fig. 4  
5) Remove all ice from the storage bin, and  
clean the storage bin.  
6) Replace the front panel in its correct position.  
7) Close the drain valve.  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Automobile Parts 234397 User Manual
Graco Baby Accessories ISPA338AA User Manual
Greenway Home Products Indoor Fireplace MEF2511OK User Manual
Harbor Freight Tools Grinder 95504 User Manual
Honeywell Cooktop Central Heating Cooker Natural Gas User Manual
Hotpoint Washer Dryer HE9L493 User Manual
Hotpoint Washer WmAQL 721 User Manual
HP Hewlett Packard Scanner L2683B201 User Manual
Hunter Fan Humidifier 35216 User Manual
Husqvarna Chainsaw 315 320 User Manual