| 	
		 Y8196A (T8196AThermostat/   
					Q682A Subbase) Heating/Cooling New   
					Construction Thermostat/Subbase   
					Package—Installation Instructions   
					Assure power is off to the heating, cooling, or heating/   
					cooling system at the main fuse panel. Most buildings have   
					Preparation   
					a separate switch box or circuit breaker for disconnecting   
					Check thermostat and subbase suitability for the heat-   
					power to the heating and cooling (if applicable) equipment.   
					ing, cooling, or heating/cooling system. Refer to Table 1.   
					This thermostat is compatible with virtually all heating,   
					Assemble tools required: flat bladed screwdriver, hand   
					cooling or heating/cooling systems. Refer to Table 1 for   
					or power drill with 3/16-in. drill bit, wire cutter/stripper or   
					additional thermostat compatibility information.   
					sharp knife, bubble level or plumb bob and line.   
					TABLE 1—THERMOSTAT AND SYSTEM COMPATIBILITY.   
					Type of Heating System   
					to be Controlled   
					Conditions/Compatibility   
					Electric (Line Voltage)—typical baseboard and   
					radiant   
					• 
					• 
					• 
					The R8239D1015 Isolating Relay or R841 Silent Switching   
					Center must be installed in the thermostat control circuit.a   
					Gas—Direct Spark Ignition (DSI), Intermittent   
					Pilot (IP), and Standing Pilot (SP)   
					Compatible.   
					Heat Pump   
					Compatible. Assure correct subbase identity is selected for fan   
					control and changeover control (O terminal for cool and B   
					terminal for heat). Jumper Y to W for heat pump compressor   
					control.   
					Hot Water Zone   
					• 
					• 
					Honeywell 2-wire valves are compatible.   
					Some non-Honeywell 2-wire valves require an R8239D1015   
					Isolating Relay in the thermostat control circuit.a   
					Some 3-wire valves require an R8239A1052 Isolating Relay   
					in the thermostat control circuit.a, b   
					• 
					Oil   
					• 
					Compatible.   
					Vent Damper   
					• 
					• 
					Honeywell damper motors are compatible.   
					Some non-Honeywell damper motors require an R8239D1015   
					Isolating Relay in the thermostat control circuit.a Check   
					control amperage requirement.   
					Warm Air Zone   
					• 
					Most are compatible.   
					a If thermostat is not compatible with the system being controlled, the system will not operate. No hazard exists. The thermostat   
					will not be damaged unless it is used to directly control a line voltage system. A Honeywell R841 or R8239D1015 Isolating   
					Relay must be added to the thermostat control circuit for proper system operation.   
					b Consult manufacturer for installation requirements.   
					Recycling Notice   
					This control contains mercury in a sealed tube. Do not   
					place control in the trash at the end of its useful life.   
					If this control is replacing a control that contains mer-   
					cury in a sealed tube, do not place your old control in the   
					trash.   
					Contact your local waste management authority for   
					instructions regarding recycling and the proper disposal of   
					this control, or of an old control containing mercury in a   
					sealed tube.   
					• Form Number 69-0637—2   
					D. F. • Rev. 12-94 • ©Honeywell Inc. 1994 •   
					M3375   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Outlet Box Mounting (Fig. 4)   
					Fig. 3—Leveling methods for subbase.   
					Use a horizontally mounted outlet box if possible. If a   
					vertical outlet box is used, the subbase must be mounted on   
					a 202689A Cover Plate Assembly (ordered separately).   
					Follow the instructions provided with the cover plate as-   
					sembly.   
					SPIRIT LEVEL   
					Align the subbase mounting holes on the outlet box and   
					loosely fasten with the two screws.   
					Carefully level the subbase (Fig. 3) and firmly tighten   
					the screws.   
					PLUMB   
					LINE   
					O 
					B 
					R 
					G 
					W 
					Y 
					PLUMB   
					BOB OR   
					WEIGHT   
					FAN   
					COOL   
					ON   
					AUTO   
					HEAT   
					OFF   
					M1555   
					Fig. 4—Mounting subbase on outlet box.   
					VERTICAL   
					OUTLET   
					1 
					BOX   
					EXISTING   
					HORIZONTAL   
					OUTLET BOX   
					2 
					COVER   
					PLATE   
					ADAPTER   
					RING   
					2 
					O 
					B 
					R 
					W 
					HEATING/   
					COOLING   
					SUBBASE   
					W 
					R 
					G 
					G 
					Y 
					FAN   
					COOL   
					ON   
					AUTO   
					HEAT   
					OFF   
					SUBBASE OR   
					WALLPLATE   
					MOUNTING   
					SCREWS (2)   
					M1553A   
					1 
					2 
					NOT INCLUDED WITH UNIT.   
					M1554A   
					ACCESSORY PARTS AVAILABLE.   
					WIRE SUBBASE   
					Connect the wires to corresponding terminals on the   
					subbase.   
					If labels do not agree with your new subbase, refer to   
					Table 2 or Fig. 11.   
					Follow the instructions provided by the heating, cool-   
					ing, or heating/cooling equipment manufacturer. If not   
					available, refer to the Typical Wiring Diagrams section at   
					the end of this publication.   
					Disconnect the power supply before making wiring con-   
					nections to prevent electrical shock or equipment damage.   
					TABLE 2—TERMINAL DESIGNATIONS.   
					Subbase   
					NOTE: All wiring must comply with local electrical codes   
					and ordinances.   
					Terminal   
					Control Function   
					Control transformer power.   
					Heating control circuit.   
					R 
					W 
					Y 
					Refer to Fig. 5 and strip thermostat wire insulation as   
					necessary.   
					Cooling control circuit (jumper to W for   
					heat pump compressor control).   
					Fig. 5—Methods of connecting terminals.   
					G 
					O 
					Fan control circuit.   
					FOR STRAIGHT   
					CONNECTION—   
					STRIP 5/16 in. [8 mm]   
					Cooling damper or changeover/reversing   
					valve, makes continuously in cool.   
					B 
					Heating damper or changeover/reversing   
					valve, makes continuously in heat.   
					FOR WRAPAROUND   
					BARRIER   
					CONNECTION—   
					STRIP 7/16 in. [11 mm]   
					Push excess wire back into the wall.   
					Plug the hole in the wall with nonhardening caulk, putty,   
					or nonflammable insulation to prevent drafts from affect-   
					ing thermostat operation.   
					M1556B   
					3 
					69-0637—2   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				MOUNT THE THERMOSTAT   
					SET TIMER   
					Note the tabs on the top inside edge of the thermostat   
					base. These tabs fit the slots molded into the top of the   
					subbase.   
					Adjust the timer by moving the knob clockwise   
					Do NOT reverse the knob.   
					. 
					When time is correctly set, the time indicator arrow   
					(Fig. 8) must point to the corresponding daytime (light) or   
					nighttime (dark) portion of the program dial.   
					Hang thermostat base on subbase.   
					Insert the two captive mounting screws located in the   
					bottom corners of the base (Fig. 6).   
					Firmly tighten the screws.   
					Fig. 8—Set timer.   
					Fig. 6—Thermostat mounting.   
					PROGRAM   
					PINS (4)   
					SEE OWNER'S   
					MANUAL FOR   
					DETAILS   
					TAB (2)   
					TIMER   
					SETTING   
					KNOB   
					MOUNTING SLOT (2)   
					TIME   
					INDICATOR   
					ARROW   
					1 
					M5161   
					35   
					30   
					25   
					20   
					10   
					ATTACH THERMOSTAT COVER   
					Make sure the packing inserts in the thermostat base are   
					removed.   
					Place the two tabs on the upper edge of the cover into the   
					mounting slots in the thermostat base (Fig. 9).   
					Swing the cover downward until it catches at the bottom   
					of the base.   
					CAPTIVE   
					MOUNTING SCREWS   
					WALLPLATE   
					OR SUBBASE   
					THERMOSTAT   
					BASE   
					M8674   
					INSERT TIMER BATTERIES   
					Power is supplied to the timer by two AAA alkaline   
					batteries (not included).   
					Fig. 9—Attach cover.   
					Install the batteries in the thermostat (Fig. 7).   
					Once a year or when batteries are dead, replace with two   
					new AAA alkaline batteries. We recommend Energizer®   
					batteries.   
					50   
					60   
					70   
					80   
					Fig. 7—Insert timer batteries.   
					BATTERY LOCATION FOR   
					(2) AAA BATTERIES;   
					INSTALL WITH POSITIVE   
					ENDS UP   
					M8604   
					SET TEMPERATURE CONTROL LEVERS   
					The two levers on top of thermostat control the low and   
					high temperatures for energy savings and comfort control   
					(Fig. 10). The lever on the left (blue mark) controls the   
					lower temperature. The lever on the right (red mark) con-   
					trols the higher temperature.   
					We recommend pushing the levers together at an appro-   
					priate temperature for either heat or cool until the occupant   
					programs the thermostat and makes the final temperature   
					selections.   
					M8585   
					69-0637—2   
					4 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				HEATING/COOLING SYSTEM   
					Fig. 10—Temperature control levers.   
					Turn on power to the furnace and cooling system.   
					Place the system switch lever to HEAT and fan switch   
					lever to AUTO.   
					LOW TEMPERATURE   
					(BLUE MARK)   
					SET LEVER   
					HIGH TEMPERATURE   
					(RED MARK)   
					SET LEVER   
					Push both temperature setting levers together at least   
					5°F (3°C) above room temperature. The main burner should   
					come on. The fan will start when the furnace heats up. (If   
					central electric heat or heat pump system, fan starts imme-   
					diately.)   
					70   
					60   
					80   
					50   
					Move both levers 5°F (3°C) below room temperature.   
					The burner should shut off.   
					Place the system switch lever at COOL and the fan   
					switch lever at AUTO. The cooling equipment should   
					operate, and the fan will start. Allow for any time delay that   
					may be built into the compressor control circuit.   
					M859   
					SET SUBBASE SWITCHES   
					The subbase system switch controls system operation as   
					follows:   
					HEAT: Heating system is controlled by the thermostat.   
					Cooling system is off.   
					NOTE: To avoid compressor damage, do not operate the   
					system if outdoor temperature is below 50°F (10°C).   
					Refer to manufacturer recommendations.   
					COOL: Cooling system is controlled by the thermostat.   
					Heating system is off.   
					OFF: Both the heating and cooling systems are off. If the   
					fan switch is in the AUTO position, the fan is also off.   
					Move both temperature setting levers together at least   
					5°F (3°C) above room temperature. The cooling equipment   
					should shut off.   
					Place the fan switch to ON. The fan should run continu-   
					ously with the system switch in any position.   
					Place the system switch to OFF. Move both temperature   
					setting levers to various positions. The heating and cooling   
					systems should not operate.   
					Operate the entire system for at least one complete cycle   
					with the system switch at COOL and one complete cycle   
					with the switch at HEAT.   
					If thermostat fails any test, refer to the Troubleshooting   
					Guide in the Owner’s Manual.   
					The subbase fan switch controls fan operation as follows:   
					ON: Fan operates continuously.   
					AUTO: Fan operates with the cooling equipment as   
					controlled by the thermostat or with the heating equip-   
					ment as controlled by the plenum switch. In electric   
					heat, heat pump and fan coil systems, the fan is   
					controlled by the thermostat in heating and cooling.   
					To switch positions, use thumb or index finger to slide   
					lever to the desired position. Switch lever must stop in   
					detent over the desired function indicator mark for proper   
					circuit operation.   
					Reset both temperature setting levers to the desired   
					temperatures.   
					Leave Owner’s Manual and Assistance Information in a   
					convenient place for the building occupant or provide with   
					other appliance manuals.   
					CHECK OUT THERMOSTAT OPERATION   
					CAUTION   
					TYPICAL WIRING DIAGRAMS   
					For wiring, follow the hookup diagram supplied with   
					your heating, cooling or heating/cooling equipment. If not   
					available, use Fig. 11 as a guide.   
					Do NOT check operation by shorting across   
					terminals of relay or valve coil; this will burn   
					out the thermostat heat anticipator.   
					REMEMBER: Your wiring must follow local electrical   
					codes and ordinances.   
					5 
					69-0637—2   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Fig. 11—Typical hookup for Y8196A Package (T8196A Thermostat/Q682A Subbase) in heating/cooling   
					system.   
					TIMER   
					C 
					C 
					H 
					H 
					FILTER   
					LIGHT   
					THERMOSTAT   
					FALL   
					FALL   
					HEAT   
					ANTICIPATOR   
					HEAT   
					ANTICIPATOR   
					2 
					BATTERIES   
					COOL   
					ANTICIPATOR   
					SYSTEM   
					SWITCH   
					SUBBASE   
					FAN   
					SWITCH   
					SWITCH   
					R 
					O 
					G 
					W 
					B 
					Y 
					3 
					REVERSING   
					VALVE/   
					HEATING   
					DAMPER   
					REVERSING   
					VALVE/   
					COOLING   
					DAMPER   
					FAN   
					RELAY   
					HEAT   
					RELAY   
					COMPRESSOR   
					CONTACTOR   
					1 
					L1   
					(HOT)   
					L2   
					1 
					2 
					3 
					POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.   
					REMOTE INDICATION FOR FILTER OPTIONAL.   
					JUMPER W TO Y FOR HEAT PUMP COMPRESSOR CONTROL.   
					M2386A   
					Automation and Control Solutions   
					Honeywell International Inc.   
					1985 Douglas Drive North   
					Golden Valley, MN 55422   
					Honeywell Limited—Honeywell Limitée   
					35 Dynamic Drive   
					Scarborough, Ontario M1V 4Z9   
					69-0637—2   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |