		 MM-2 MASTERTROL®   
					MINI-ZONE™-2   
					SCHEMATIC   
					OIL FURNACES - When using the MM-2 with an Oil   
					The Mastertrol® Mini-Zone™ -2 Zone Control Panel,   
					Model MM-2, controls 2 zones on any single stage   
					heating and cooling system. Each zone is controlled   
					by a thermostat which operates a motorized damper   
					in the zone duct to control the flow of conditioned air   
					to the zone. (Up to 2 dampers may be wired to a   
					single zone. When 3 or more dampers are required   
					a Slave Damper Control Relay, Model SDCR, is re-   
					quired.)   
					ZONE THERMOSTAT WIRING - The MM-2 can be   
					used with several different single stage thermostats.   
					The wiring shown is for the following recommended   
					thermostats:   
					Fired Furnace to provide heating, the T and T termi-   
					nals on the Oil Burner Primary Control must wire to   
					the RH and W terminals, on the left side of the MM-   
					2. NOTE: Once operational the Oil Furnace contin-   
					ues to run when all zones are satisfied, reverse the   
					RH and W wires on the MM-2.   
					Zone 1 Thermostat   
					TRT(-W) and MCRS(-W)   
					T8090T1003*   
					T8602C   
					Zone 2 Thermostat   
					TRT(-W)/T87F   
					T8090T1011*   
					T8602D   
					DAMPER MOTOR WIRING - This diagram shows   
					Trol-A-Temp’s typical power open-power closed op-   
					posed blade damper motors. Note the jumper wire   
					required on the motor terminals 2 and 5. Round   
					Spring Return Dampers can also be wired to the   
					MM-2.When using the ARD-PC, wire to the M1 and   
					M6 terminals. When using the ARD-PO, wire to the   
					M1 and M4 terminals.   
					T8601C*   
					T8603D*   
					*These thermostats may require additional wires.   
					Refer to the wiring information included with the ther-   
					mostat for complete information.   
					The Zone 1 Thermostat requires a manual   
					changeover subbase with “O” and “B” terminals.The   
					“O” terminal must make with R when the subbase is   
					switched to the COOL Mode. The “B” terminal must   
					make with R when the subbase is switched to the   
					HEAT Mode.When the Zone 1 Subbase in either the   
					Heat or Cool Mode, either zone thermostat can call   
					for the respective mode.The zone thermostat will en-   
					ergize it’s zone relay which activates the heating or   
					cooling controls, opens it’s zone damper and closes   
					the damper to the zone that is satisfied. When both   
					zone thermostats are satisfied the heating (or cool-   
					ing) will shut off and all zone dampers will return to   
					their normal position.The normal position of the zone   
					dampers is set by the OPEN/CLOSED (O/C) slide   
					switch next to the motor terminals.   
					ZONE 1 THERMOSTAT   
					AND SUBBASE   
					ZONE 2 THERMOSTAT   
					5/R   
					O 
					B 
					Y 
					G 
					R 
					4/W   
					6/Y   
					W 
					MODEL DPBT   
					(T678A)   
					SYSTEM CONNECTIONS: The MM-2   
					System Terminals, on the far left side of   
					the panel, wire to the HVAC Unit. These   
					terminals are isolated “dry”switching con-   
					tacts similar to any typical thermostat.   
					These terminals are wired to the HVAC   
					Unit the same as any thermostat would,   
					when not using this zone control panel.   
					The MM-2 connections used are typically   
					the RC-G-Y-W terminals wired the the   
					HVAC Unit Control Center.   
					MASTERTROL MINI - ZONE   
					MODEL MM-2   
					SYSTEM   
					Y 
					Y 
					T6/Y   
					O1   
					T6/Y   
					T5/R   
					T4/W   
					G 
					O 
					G 
					HYDRO-AIR Systems - When using the   
					MM-2 with a Hydro-Air System, one   
					which uses a hot water coil in the air han-   
					dler to provide heating in place of a fur-   
					nace, the wiring is almost similar to that   
					shown. In this application the Heat Re-   
					lay shown may be a zone valve or circu-   
					lator relay. The Fan must be controlled   
					by an Aquastat. In order to bring the fan   
					on when the water in the coil is heated.   
					This is wired independently of the MM-2   
					panel.   
					T5/R   
					G1   
					B1   
					B 
					FAN RELAY   
					T4/W   
					R 
					C 
					RC   
					C 
					C 
					O 
					M6   
					M6   
					24 VOLT   
					TRANSFORMER   
					O 
					RH   
					W 
					2 
					1 
					M4   
					M4   
					M1   
					W 
					ZONE 1   
					ZONE 2   
					M11   
					HEAT RELAY   
					HVAC UNIT CONNECTIONS   
					6 
					3 
					6 
					3 
					4 
					1 
					5 
					2 
					Z 
					4 
					1 
					5 
					2 
					Z 
					X 
					R 
					C 
					X 
					24 VOLT 40 VA   
					TRANSFOMER   
					MODEL PMT-40   
					ZONE 1 DAMPER MOTOR   
					ZONE 2 DAMPER MOTOR   
					M13557   