Honeywell Smoke Alarm MS 10UD User Manual

MS-5UD & MS-10UD Series Fire Alarm Control Panel  
OperatingInstructions  
NORMAL - Only AC POWER is illuminated green.  
PANEL KEY - The key to open the panel can be found at the  
All other indicators are off. LCD display will read SYSTEM  
ALL NORMAL.  
following location:  
WHEN AUDIBLE DEVICES ARE SOUNDING -  
FORANALARM  
1. Evacuate the protected area  
2. Notify the monitoring service and/or the Fire Department immediately. Tell them briefly what happened and what  
your current status is.  
Phones:____________________________ _________________________________  
Fire Department  
Monitoring Service  
3. If the Fire Department is responding, be prepared to provide directions to arriving firefighters.  
FORTROUBLEONLY  
1. Notify the monitoring service and/or Fire department if this panel is connected to either one, and tell them  
what is happening.  
2. Silence audible devices by unlocking and opening the panel and pressing the ACKNOWLEDGE/STEP button. The  
TROUBLE indicator will remain illuminated yellow. Contact authorized service personnel immediately! (See Below).  
WARNING!  
DO NOT ALLOW TROUBLE CONDITIONS TO REMAIN LOGGED IN THE SYSTEM.  
THE PROTECTION THE SYSTEM OFFERS HAS BEEN COMPROMISED, OR ELIMINATED WHEN A  
TROUBLE CONDITION EXISTS.  
To return to normal after an alarm  
1. Do not enter the protected area until safe to do so.  
2. Clear all initiating devices. Smoke detectors will not reset  
if there is still smoke in the area.  
Manual activation (Fire Drill or otherwise)  
Notification Appliance Circuits (NACs) can be activated by  
pressing and holding the DRILL button for at least two  
seconds.  
3. Reset the control panel (PRESS the RESET button)  
NOTE: You may want to disconnect municipal box by sliding  
DISCONNECT switch, located on 4XTMF module, to its  
disconnect position (to the right). If a DACT is con-  
nected, notify the monitoring service before conducting  
any fire drills or tests.  
Power failure or brownout  
If AC power drops too low or fails, AC POWER indicator will  
extinguish, the system TROUBLE indicator will turn on yellow, and  
the panel buzzer and any other audible trouble devices will sound.  
Contact authorized service personnel immediately. See below.  
AlarmSilencing  
Notification Appliance Circuits may be silenced by pressing the  
ALARM SILENCE button. ALARM SILENCED will turn on yellow.  
Subsequent alarms will reactivate circuits. Press the RESET  
button to clear the "silenced" condition.  
NOTE: Notification Appliance Circuits may be programmed as  
nonsilenceable. Also, Signal Silence Inhibit, if enabled, will  
prevent silencing of NACs for one minute after an alarm (see  
manual).  
To test the indicators, LCD display and piezo  
Press and release the RESET button and check all indicators/  
LEDs. Every indicator/LED should be on, LCD shows all pixels  
on, piezo sounder beeps.  
In the event of trouble, contact the  
local Fire-Lite Service Representative  
Name:_____________________________________  
Company:_________________________________  
Address:___________________________________  
Telephone Number: ________________________  
For more information, refer to the MS-5UD & MS-10UD Series  
Manual, Document #52626. It is kept in the following location:  
THISSHEETSHALLBEFRAMEDADJACENTTO  
THECONTROLPANEL  
Document #52805 Rev. A 10/05/06 ECN 05-765  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Grundig Stereo System Weather AM FM Radio User Manual
Harbor Freight Tools Air Compressor 9592 User Manual
Harman Kardon Microphone WMS 470 User Manual
Hasbro Games 12791 12790 User Manual
HP Hewlett Packard Switch 2012i User Manual
HP Hewlett Packard Switch 2600 Series User Manual
Husky Work Light HSK141HD User Manual
Husqvarna Tiller 650RTT User Manual
Hyundai IT Computer Monitor U70D User Manual
I Data Power Supply 5250 ALLY User Manual