Honeywell Home Security System Ademco Security Systems User Manual

ADEMCO VISTA-10P  
ADEMCO VISTA-10PSIA  
Security Systems  
Installation and Setup Guide  
K0735V3 10/04 Rev. B  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table Of Contents  
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •  
Features and Installation Highlights...............................................................................................1-1  
Capabilities.............................................................................................................................................1-1  
Functions..............................................................................................................................................1-1  
Compatible Devices..............................................................................................................................1-1  
Important Installation Highlights (Installer Please Read)...............................................................1-2  
Mounting and Wiring the Control.....................................................................................................2-1  
Cabinet and Lock.................................................................................................................................2-1  
Mounting the PC Board Alone (no RF Receiver)................................................................................2-1  
Mounting Board with RF Receiver .....................................................................................................2-2  
Wiring to Keypads ...............................................................................................................................2-3  
Sounder (Bell) Connections.................................................................................................................2-4  
Wiring the AC Transformer ................................................................................................................2-4  
Backup Battery....................................................................................................................................2-4  
Earth Ground.......................................................................................................................................2-5  
Hardwire Zones....................................................................................................................................2-6  
Smoke Detectors ..................................................................................................................................2-6  
Installing the RF Receiver ..................................................................................................................2-7  
Installing a 5800TM Module...............................................................................................................2-7  
Installing the Transmitters.................................................................................................................2-8  
Installing a Keyswitch.........................................................................................................................2-8  
Connecting Relay Modules..................................................................................................................2-9  
On-Board Triggers.............................................................................................................................2-10  
Phone Line/Phone Module Connections ...........................................................................................2-10  
Long Range Radio Connections ........................................................................................................2-11  
AAV Connections ...............................................................................................................................2-12  
Programming Overview ......................................................................................................................3-1  
About Programming ............................................................................................................................3-1  
Keypads................................................................................................................................................3-1  
Wireless Receiver, Transmitters, and Wireless Keys (keyfobs)........................................................3-2  
Pager Programming.............................................................................................................................3-2  
Function Keys ......................................................................................................................................3-2  
Output Devices.....................................................................................................................................3-2  
Zone Type Definitions..........................................................................................................................3-3  
Mechanics of Programming.................................................................................................................3-5  
Data Field Programming.....................................................................................................................4-1  
About Data Field Programming..........................................................................................................4-1  
Programming Data Fields...................................................................................................................4-1  
System Setup Fields ............................................................................................................................4-1  
Zone Sounds & Timing ........................................................................................................................4-2  
Dialer Programming............................................................................................................................4-3  
System Status Report Codes...............................................................................................................4-4  
Miscellaneous System Fields ..............................................................................................................4-6  
Pager Programming Fields .................................................................................................................4-8  
Miscellaneous System Fields ..............................................................................................................4-8  
Configurable Zone Type Programming Fields ...................................................................................4-9  
Keypad Programming Fields ............................................................................................................4-11  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table Of Contents  
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •  
Menu Mode Programming...................................................................................................................5-1  
Zone Programming Overview (56 and 58 Menu Modes)................................................................5-1  
56 Zone Programming Procedure......................................................................................................5-1  
58 Expert Programming Mode Procedures ......................................................................................5-3  
Wireless Key Programming Templates..............................................................................................5-4  
Output Device Programming Overview (*79/*80 Menu Mode).........................................................5-6  
*79 Menu Mode: Output Device Mapping..........................................................................................5-6  
*80 Menu Mode: Defining Output Functions.....................................................................................5-7  
Zone List Overview (81 Menu Mode)................................................................................................5-9  
Zone List Programming.......................................................................................................................5-9  
Function Key Programming Overview (57 Menu Mode)...............................................................5-10  
Programming Function Keys............................................................................................................5-10  
About Descriptor Programming Overview (82 Menu Mode).........................................................5-11  
Programming Zone Descriptors (Menu mode 82) ..........................................................................5-11  
Adding Custom Words.......................................................................................................................5-12  
Programming Installer and User Schedules....................................................................................5-14  
System Communication and Operation...........................................................................................6-1  
System Communication Overview......................................................................................................6-1  
Report Code Formats...........................................................................................................................6-1  
®
Ademco Contact ID ...........................................................................................................................6-3  
User Security Codes.............................................................................................................................6-4  
Keypad Functions................................................................................................................................6-5  
Various System Trouble Displays.......................................................................................................6-6  
Testing the System................................................................................................................................7-1  
About Test Procedures.........................................................................................................................7-1  
System Test..........................................................................................................................................7-1  
Checking Transmitter Enrollment (Sniffer Mode) ............................................................................7-1  
Go/No Go Test Mode ............................................................................................................................7-2  
Dialer Communication Test ................................................................................................................7-2  
Automatic Standby Battery Tests.......................................................................................................7-2  
Specifications & Accessories ..............................................................................................................8-1  
Security Control...................................................................................................................................8-1  
Compatible Devices..............................................................................................................................8-1  
5800 Series Transmitter Input Loop Identification...........................................................................8-2  
Regulatory Agency Statements..........................................................................................................9-1  
Limitations and Warranty.................................................................................................................10-1  
iv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S E C T I O N  
1
Features and Installation Highlights  
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •  
SIA Installations: The VISTA-10PSIA is a certified SIA-compliant control that meets SIA  
specifications for False Alarm Reduction. The VISTA-10P is not certified as SIA compliant, but can be  
programmed for False Alarm Reduction. To program for False Alarm Reduction, follow the SIA  
Guidelines noted in the applicable programming fields.  
Capabilities  
Up to 22 zones plus eight keyfob zones (zones 49-56) for total of 30 zones:  
-- Six basic hardwired zones (zone 1-6)  
-- Supports up to 16 wireless transmitter zones (5800 series; zones 9-24)  
-- Supports one configurable zone type  
Up to 16 security codes, each with separate authority levels  
Supports Downloading: Via an IBM compatible computer, Compass downloading software, and a  
compatible HAYES or CIA modem specified by Ademco.  
Functions  
Single-button arming feature: Can use dedicated keys to arm the system AWAY or STAY  
Up to two schedules (1 installer, 1 end-user), to control devices and/or auto-arm/disarm the system  
One keypad macro, which can simplify a long command string (e.g., bypassing zones before arming)  
Paging feature allows certain system conditions to be reported to one pager phone number; can use a  
dedicated key on keypads to send a signal to the pager  
Event Logging records up to 32 selected events in a history log; control and readout from the log is  
done via Ademco Compass Downloader software or installer/master code at Keypad  
Zone descriptors for all zones (useful only when using Alpha keypads and/or the 4285/4286 Phone Module).  
Optional bell supervision detects external sounder wiring short or open; causes a trouble condition,  
keypad display, and sends a report to the central monitoring station, if enabled.  
Optional RF jam detection for wireless systems detects a condition that may impede proper RF  
reception (i.e., jamming or other RF interference); causes keypad display, and sends a report to the  
central monitoring station (if trouble reporting is enabled).  
Compatible Devices  
Up to eight Addressable Keypads: 6150 Fixed-Word Keypad, 6160 Alpha Keypad, 6150V Fixed-  
Word Display Voice Keypad, 6160V Alpha Display Voice Keypad, 6150RF Keypad/Transceiver  
Supports 5881 series receiver and 5800 series transmitters  
Up to four output relays (4204) plus two on-board triggers (does not support Powerline Carrier  
Devices) -- Up to 12 output functions.  
Ademco 4285/4286 Phone Module; provides access to the system via on premises or off-premises  
phones for arming, disarming, etc., plus control of relay outputs.  
Audio Alarm Verification (using AAV module, such as ADEMCO UVS); can be used in conjunction  
with an output trigger to permit voice dialog between an operator at the central station and a  
person at the premises.  
Alarm output provides a 12VDC, 2 AMP output that can drive the compatible sounders; steady  
output for burglary/panic, or temporal pulse (3 pulses – pause – 3 pulses – pause – 3 pulses. . .) for  
fire. Uses current limiting circuitry for protection.  
Auxiliary Power Output: 12VDC, 600 mA maximum (uses fuse for protection).  
Backup Battery: Rechargeable (sealed lead-acid type) 12VDC, 4AH minimum.  
Long Range Radio: Primary telephone number messages can be reported via ECP connection to  
various Long Range Radios (check compatibility and availability of specific models)  
AC Power Supply: Plug-in 120VAC transformer, ADEMCO 1321 (1321CN in Canada)  
1-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and Setup Guide  
NOTE: All devices and accessories used in a Canadian installation must be Listed for use in Canada.  
Important Installation Highlights (Installer Please Read)  
This system uses addressable keypads and Relay Modules (see table of addresses in Programming  
Overview section).  
Keypads must be set for addresses 16-23 (first keypad is address 16, which is different from  
previous controls) and programmed in data fields *190-*196.  
4204 Relay Modules must be set for specific address 12 (see Connecting Relay Modules section).  
Relays have two programming menu modes: Use *79 Menu mode to map module addresses and  
device (output) numbers. Use *80 Menu mode to define the output functions (see Output Device  
Programming section).  
This system supports programmable function keys. Use *57 Menu mode to define the function keys  
(see Function Key Programming section).  
This system provides various paging features. Refer to the Programming Overview section for a  
summary on pager programming.  
1-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S E C T I O N  
2
Mounting and Wiring the Control  
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •  
Cabinet and Lock  
1. Mount the control cabinet to a sturdy wall in a clean, dry area, which is not readily accessible to  
the general public, using fasteners or anchors (not supplied) with the four cabinet mounting  
holes.  
2. Remove cabinet door, then remove the lock knockout from the door. Insert the key into the lock.  
3. Position the lock in the hole, making certain that the latch will make contact with the latch  
bracket when the door is closed. When correctly positioned, push the lock until it is held securely  
by its snap tabs.  
NOTES  
The cabinet can be closed and secured without a lock by using 2 screws in the cover's edge.  
PUSH  
ON LOCK  
UNTIL IT  
IS SEATED  
SECURELY  
CHECK  
SNAP  
POSITION  
TAB  
LOCKED  
PUSH  
SNAP  
TAB  
UNLOCKED  
CABINET DOOR  
BOTTOM  
STEP 1  
STEP 2  
Figure 1. Installing the Cabinet Lock  
Mounting the PC Board Alone (no RF Receiver)  
1. Hang two short mounting clips (provided) on the raised cabinet tabs (see Detail B in Fig. 2).  
2. a. Insert the top of the circuit board into the slots at the top of the cabinet. Make sure that the  
board rests on the correct row (see Detail A).  
b. Swing the base of the board into the mounting clips and secure the board to the cabinet with  
the accompanying screws (see Detail B).  
NOTES  
Before installing the cabinet's contents, remove the metal cabinet knockouts required for wiring  
entry. Do not remove the knockouts after the circuit board has been installed.  
CIRCUIT  
CABINET  
BOARD  
CIRCUIT  
BOARD  
+
+
CABINET  
DETAIL B  
SIDE VIEW  
OF MOUNTING  
CLIPS  
DETAIL A  
SIDE VIEW  
OF BOARD  
SUPPORTING  
SLOTS  
MOUNTING-001-V0  
Figure 2. Mounting the PC Board  
2-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
Mounting Board with RF Receiver  
1. a.Remove the receiver board from its case, then insert the top of the board into the slots at the top  
of the cabinet, as shown in Detail A in Figure 3. Make sure that the board rests on the correct  
row of tabs.  
b.Swing the base of the board into the mounting clips and secure it to the cabinet with the  
accompanying screws.  
c. Insert the top of the control's board into the slot in the clips and position two clips at the lower  
edge of the board.  
d.Swing this board into place and secure it with two additional screws.  
2. Insert grounding lugs (supplied with the receiver) through the top of the cabinet into the left-  
hand terminals of the antenna blocks (at the upper edge of the receiver board) and secure them to  
the cabinet top with the screws provided, as shown in Detail B.  
3. Insert the receiver's antennas through the top of the cabinet, into the blocks' right-hand  
terminals, and tighten the screws.  
NOTES  
Do not mount the cabinet on or near metal objects. This will decrease RF range and/or block RF  
transmissions from wireless transmitters.  
Do not locate the cabinet in an area of high RF interference (revealed by frequent or prolonged  
lighting of the LED in the receiver after it is operational (random flicker is OK)  
CABINET  
A
B
CABINET  
BOARD  
SUPPORTING  
SLOTS  
RECEIVER CIRCUIT BOARD  
+
+
CIRCUIT  
BOARD  
MOUNTING  
CLIP  
CONTROL  
CIRCUIT  
BOARD  
DETAIL A  
SIDE VIEW  
OF BOARD -  
SUPPORTING SLOTS  
MOUNTING  
CLIP  
INSTALLATION WITH RECEIVER CIRCUIT BOARD  
ANTENNA  
(2)  
SCREW  
(2)  
GROUNDING  
LUG  
(2)  
WHITE  
MOUNTING  
CLIP  
BLACK  
MOUNTING  
CLIP  
RED  
MOUNTING  
CLIP  
NOTE  
A COMBINATION OF THESE MOUNTING CLIPS HAS BEEN  
INCLUDED IN YOUR INSTALLATION KIT.  
ANTENNA  
MOUNT  
(2 PLACES)  
USE THE APPROPRIATE CLIPS FOR MOUNTING.  
DETAIL B  
ANTENNA AND GROUNDING  
LUG INSTALLATION  
IF NO RF RECEIVER IS USED, MOUNT THE PC BOARD USING  
EITHER THE WHITE OR BLACK CLIPS, WHICHEVER ARE  
INCLUDED IN THE CONTROL PANEL'S HARDWARE KIT.  
pc_mount-001-V1  
Figure 3. Mounting the PC Board and RF Receiver  
2-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting and Wiring the Control  
Wiring to Keypads  
1. Connect keypads to the keypad terminals as shown on the Summary of Connections diagram.  
Determine wire size using the Wire Run Chart below.  
2. Set keypad addresses. Refer to the address setting instructions included with the keypads and set  
each keypad device address according to the chart at right.  
3. Program the keypad addresses and sound options in data fields *190-*196.  
IMPORTANT: Each keypad must be assigned a unique address, starting at address 16.  
Keypads programmed with the same address will give unpredictable results.  
Supplementary Power (optional)  
1. Connect as shown. Be sure to connect the negative (–) terminal on the power supply unit to terminal 4  
(AUX –) on the control.  
NOTES  
SUPPLEMENTARY  
POWER SUPPLY  
CONTROL TERMINAL STRIP  
+
Typical Fixed-Word Display: 6150  
Typical Alpha Display: 6160  
AUX. AUX. DATA DATA  
IN OUT  
4
+
5
6
7
Voice Keypads: 6150V, 6160V  
The system supports up to 8 keypads  
(see program fields *190-*196).  
For single 4-wire runs, determine the current  
drawn by all units, then refer to the Wiring  
Run chart to determine the maximum length  
that can be safely used for each wire size.  
Use supplementary power if the control’s aux.  
power load for all devices exceeds 600mA.  
Suggested power supply: AD12612  
IMPORTANT:  
MAKE THESE  
CONNECTIONS  
DIRECTLY TO  
SCREW  
TERMINALS AS  
SHOWN.  
Keypad Addresses  
Figure 4. Using a Supplementary Power Supply  
Keypad  
no. 1  
no. 2  
Address  
16**  
17  
Keypad  
no. 5  
no. 6  
no. 7  
no. 8  
Address  
20  
21  
22  
23  
no. 3  
18  
no. 4  
19  
** The first keypad is address 16, which is always  
enabled and set with all sounds on.  
U
L Use a UL Listed, battery-backed supply for UL installations. The battery supplies power to these keypads in  
case of AC power loss.  
The battery-backed power supply should have enough power to supply the keypads with the UL required  
minimum standby power time.  
Keypads powered from supplies that do not have a backup battery will not function if AC power is lost.  
Make sure to power at least one keypad from the control’s auxiliary power output.  
Wire Run Chart For Devices* Drawing Aux Power From The Control (12V+ & 12V–)  
TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN  
Wire  
Size  
#22  
#20  
#18  
#16  
50 mA or less  
900 ft (274m)  
1400 ft (427m)  
1500 ft (457m)  
1500 ft (457m)  
100 mA  
300 mA  
500 mA  
600 mA  
450 ft (137m)  
700 ft (213m)  
1100 ft (335m)  
1500 ft (457m)  
150 ft (46m)  
240 ft (73m)  
350 ft (107m)  
550 ft (168m)  
90 ft (27m)  
140 ft (43m)  
220 ft (67m)  
350 ft (107m)  
75 ft (23m)  
120 ft (37m)  
170 ft (52m)  
270 ft (82m)  
* Includes Keypads, RF Receivers, Zone Expander/Relay Units, 4285/4286 Phone Module, and LRR.  
Maximum wire lengths for any device that is homerun to the control can also be determined from the Wiring Run Chart, based on  
the current draw of that device alone.  
The length of all wire runs combined must not exceed 1500 feet (457m) when unshielded quad conductor cable is used (750 feet  
if shielded cable is used). This restriction is due to the capacitive effect on the data lines when quad cable is used.  
2-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
Sounder (Bell) Connections  
1. Make sounder connections to alarm output  
terminals 3 (+) and 4 (–).  
EXTERNAL ALARM  
SOUNDER  
TERMINALS ON  
CONTROL BOARD  
For supervised output, continue with steps 2  
and 3.  
2. Cut the red Bell Supervision Jumper located  
above terminals 2 and 3 on the control board.  
3. Connect a 2k ohm resistor across the  
terminals of the last sounder.  
4
2000  
OHM  
EOL  
RESISTOR  
ALARM  
OUTPUT  
TERMINALS  
OBSERVE  
POLARITY  
+
+
3
2
IF BELL SUPERVISION IS ENABLED  
This control complies with NFPA requirements for  
temporal pulse sounding of fire notification  
appliances. Temporal pulse sounding for a fire alarm  
consists of:  
(RED JUMPER ON CONTROL BOARD IS CUT)  
CONNECT A 2000 OHM RESISTOR ACROSS  
THE EXTERNAL SOUNDER AS SHOWN BY  
THE DOTTED LINE.  
CUT RED JUMPER ON CONTROL  
BOARD TO ENABLE BELL  
(SOUNDER) SUPERVISION.  
DO NOT CONNECT THE RESISTOR AT THE  
ALARM OUTPUT TERMINALS THEMSELVES!  
3 pulses – pause – 3 pulses – pause – 3 pulses–etc..  
Figure 5. Sounder Wiring (Supervised)  
NOTES  
The 12VDC sounder output activates when an alarm occurs.  
Total current drawn from this output cannot exceed 2 amps (going beyond 2 amps will overload the  
power supply, or may cause the electronic circuit protecting the sounder output to trip).  
You must install a battery, since the battery supplies this current.  
U
L
Use only UL Listed sounding devices for UL installations.  
Bell supervision is required for fire alarm installations.  
The total current drawn from the alarm output and the auxiliary power output, combined, cannot exceed 600  
mA. In addition, the sounding device must be a UL Listed audible signal appliance rated to operate in a 10.2-  
13.8 VDC voltage range, and must be mounted indoors.  
Wiring the AC Transformer  
Wire Run Chart  
Distance from control  
Up to 50 feet  
Connect the 1321 Transformer to terminals 1 and  
2 on the control board. See Wire Run Chart for  
wire size to use. (Use 1321CN in Canada.)  
Wire Size  
# 20  
# 18  
50–100 feet  
NOTES  
100-250 feet  
# 16  
Use caution when wiring the transformer to the control to guard against blowing the transformer  
fuse (the fuse is non-replaceable).  
Wiring to the AC transformer must not exceed 250 feet using 16 gauge wire. The voltage reading  
between terminals 1 and 2 of the control must not fall below 16.5VAC or an “AC LOSS” message  
will be displayed.  
Do not plug the transformer into the AC outlet while making any wiring connections to the control.  
As a safety precaution, always power down the control when making such connections.  
Backup Battery  
1. Place the 12-volt backup battery in the cabinet.  
2. After all connections to the control are completed and AC power has been applied, connect the red  
and black flying leads on the control board to the battery. Do not attach these leads to the battery  
terminals until all connections are completed.  
IMPORTANT: The panel will not power up initially on battery power only. You must plug the  
transformer in first, and then connect the battery.  
U
L For UL installations and Residential fire installations, refer to the chart below for the correct battery size  
required to meet the mandatory standby time.  
2-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting and Wiring the Control  
CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE  
24-HOUR BATTERY BACKUP REQUIREMENTS  
The California State Fire Marshal and UL have regulations which require that all residential fire alarm control  
panels must be provided with a backup battery which has sufficient capacity to operate the panel and its attached  
peripheral devices for 24 hours in the intended standby condition, followed by at least 4 minutes in the intended  
fire alarm signaling condition. This control panel can meet these requirements without using a supplementary  
power supply, provided that the panel’s auxiliary power and bell output currents are limited as indicated below.  
OUTPUT LIMITATIONS TO MEET CSFM 24 HOUR BATTERY BACKUP REQUIREMENTS  
AND UL RESIDENTIAL FIRE INSTALLATIONS  
OUTPUT CURRENT LIMITATIONS  
Output Current Total Maximum Auxiliary Current  
BATTERY INFORMATION  
Battery Capacity  
To Use (Amp/Hrs)  
Recommended Battery  
(Yuasa Model No.)  
NP4-12 (or ADEMCO 467)  
NP7-12  
600mA maximum total of  
auxiliary power plus bell  
output currents  
45mA  
160mA  
200mA  
425mA  
500mA  
4AH  
7AH  
8AH  
NP4-12 (two) ‡  
NP7-12 (two) ‡  
NPG18-12  
14AH  
17.2AH  
NOTE: Use two batteries, connected in parallel. Obtain an Ademco Battery Harness Kit SA5140-1. (Both batteries  
will fit inside the panel’s cabinet.)  
Earth Ground  
Metal Cold Water Pipe:  
Use a non-corrosive metal strap (copper is recommended) firmly secured to the pipe to which the  
ground lead is electrically connected and secured.  
AC Power Outlet Ground:  
Available from 3-prong, 120VAC power outlets only. To test the integrity of the ground terminal, use  
a 3-wire circuit tester with neon lamp indicators, such as the UL Listed Ideal Model 61-035, or  
equivalent, available at most electrical supply stores.  
This product has been designed and laboratory-tested to ensure its resistance to damage from  
generally expected levels of lightning and electrical discharge, and does not normally require an  
earth ground.  
If an earth ground is desired for additional protection in areas of severe electrical activity, terminal  
25 on the control board, or the cabinet, may be used as the ground connection point. The examples  
of good earth grounds listed at the left are available at most installations.  
AUXILIARY DEVICE CURRENT DRAW WORKSHEET  
* If using hardwire  
devices such as PIRs,  
refer to the  
specifications for that  
particular unit's current  
draw.  
DEVICE  
6150 Fixed-Word Keypad  
6160 Alpha Keypad  
6150V Fixed-Word Display Voice Keypad  
6160V Alpha Display Voice Keypad  
5881/5882 RF Receiver  
5883 Transceiver  
CURRENT  
30mA  
100mA  
60mA  
60mA  
35mA  
UNITS  
TOTAL CURRENT  
80mA  
‡ Figures are for relays  
OFF/relays ON.  
4204 Relay Unit  
15/180mA  
160mA  
4285 Phone Module  
4286 Phone Module  
300mA  
*
*
*
(Current available from Aux. terminals = 600 mA max.)  
TOTAL =  
In UL installations, maximum current draw from the Auxiliary Output and the Alarm Output combined must not exceed  
600 mA (500 mA max from Auxiliary Output).  
2-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
Hardwire Zones  
Normally Open Zones/ Normally Open EOLR Zones  
1. Connect open circuit devices in parallel across the loop; for EOLR zones, connect the EOLR across  
the loop wires at the last device.  
2. Enable normally open/EOLR zones using Zone Programming mode, “Hardwire Type” prompt.  
Normally Closed Zones/Normally Closed EOLR Zones  
1. Connect closed circuit devices in series in the high (+) side of the loop; for EOLR zones, connect the  
EOLR in series following the last device.  
2. Enable normally closed/EOLR zones using Zone Programming mode, “Hardwire Type” prompt.  
NOTES  
EOLR: If the EOLR is not at the end of the loop, the zone is not properly supervised and the system  
may not respond to an “open” on the zone.  
U
L For UL commercial burglar alarm installations, use EOLR zones.  
Smoke Detectors  
4-Wire Smoke Detectors  
Connect 4-wire smoke detectors (up to 16, depending on detector current draw) to any zone as shown  
below. This control does not automatically reset power to 4-wire smoke detector zones, so you must  
use a relay (e.g., 4204), or on-board trigger to reset power (also required for fire verification). Do  
this by programming the designated relay/trigger as zone type 54 (fire zone reset); see On-Board  
Trigger section for other information.  
Figure 7. 4-Wire Smoke Detector Connections  
+
5
RELAY  
PROGRAM  
BLK  
+
RED  
AUX PWR  
OUTPUT  
TERMINALS  
RELAY  
AS ZONE  
TYPE 54  
EOL  
POWER  
(
+
)
5
AUX PWR  
(FIRE ZONE  
RESET)  
N.O.  
BLK  
+
RED  
SUPERVISION  
RELAY MODULE  
A77-716B.  
TO OUTPUT 17  
PROGRAM OUTPUT 17  
FOR "OUT NORM  
LOW" = YES IN 79 MENU  
MODE AND AS ZONE  
TYPE 54 IN  
(
)
4
EOL  
POWER  
SUPERVISION  
RELAY MODULE  
A77-716B.  
N.C.  
USE N.O.  
CONTACT OPENS  
MOMENTARILY UPON  
FIRE ALARM RESET  
CONTACT,  
WHICH CLOSES  
WHEN POWER  
IS APPLIED.  
N.O.  
+
+
VIOLET  
VIOLET  
4-WIRE SMOKE  
OR COMBUSTION  
DETECTOR  
4-WIRE SMOKE  
OR COMBUSTION  
DETECTOR  
USE N.O.  
80 MENU MODE  
2000  
CONTACT,  
WHICH CLOSES  
WHEN POWER  
IS APPLIED.  
2000  
OHMS  
EOLR  
OHMS  
EOLR  
TO ZONE TERM. (  
+
)
TO ZONE TERM. (  
+
)
HEAT  
DETECTOR  
HEAT  
DETECTOR  
TO ZONE TERM. (  
)
TO ZONE TERM. (  
)
4-Wire Smoke Detector Using Relay for Power Reset  
4-Wire Smoke Detector Using Output 17 for Power Reset  
NOTES  
Fire Verification (zone type 16): The control panel will “verify” a fire alarm by resetting the  
smoke detectors after the first alarm trigger, and then waiting 90 seconds for a second alarm  
trigger. If the smoke detector or thermostat does not trigger again, the control will disregard the  
first trigger, and no alarm signal will occur. This feature eliminates false alarms due to electrical or  
physical transients.  
SIA Installations: If using fire verification on zones other than zone 1, UL Fire Alarm Listed relay  
accessories must be used to reset power as described above.  
Power Reset: Maximum current on trigger 17 is 100mA.  
2-6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting and Wiring the Control  
Installing the RF Receiver  
You can any ADEMCO 5800 Series Wireless Receivers, including:  
RF Receiver No. of Zones  
5881L/5882L up to 8  
5881M/5882M up to 16 (transmitter zone numbers = 9-24; button zone numbers = 49-56)  
5883, 6150RF up to 16 (transmitter zone numbers = 9-24; button zone numbers = 49-56)  
1. Set Device Address to “00” as described in its instructions (set all switches to the right, “off” position).  
2. Mount the receiver, noting that the RF receiver can detect signals from transmitters within a  
nominal range of 200 feet.  
3. Connect the receiver's wire harness to the control's keypad terminals. Plug the connector at the  
other end of the harness into the receiver. Refer to the installation instructions provided with the  
receiver for further installation procedures regarding antenna mounting, etc.  
NOTES  
The receiver is supervised and a trouble report is sent (“CHECK 100” displayed) if communication  
between the panel and receiver is interrupted, or if no valid RF signals from at least one supervised  
transmitter are received within 12 hours.  
If the receiver is mounted remotely:  
Place the RF receiver in a high, centrally located area for best reception.  
Do not locate the receiver or transmitters on or near metal objects. This will decrease range and/or  
block transmissions.  
Do not locate the RF receiver in an area of high RF interference (indicated by frequent or prolonged  
lighting of the LED in the receiver; random flicker is OK).  
Do not locate RF receiver closer than 10 feet from any keypads to avoid interference from the  
microprocessors in those units.  
NOTE  
ANTENNAS  
(INSERT IN  
RIGHT-HAND  
TERMINALS)  
CIRCUIT BOARD IS MOUNTED IN  
CONTROL'S CABINET. GROUNDING  
LUGS (2) PROVIDED MUST BE INSERTED  
IN LEFT-HAND TERMINALS OF ANTENNA  
BLOCKS AND SECURED TO CABINET.  
(SEE RECEIVER'S AND CONTROL'S  
INSTRUCTIONS)  
INSERT IN  
RIGHT- HAND  
TERMINALS  
YELLOW  
RED  
BLACK  
GREEN  
TO CONTROL'S  
REMOTE KEYPAD  
CONNECTION  
POINTS.  
MODEL NO. IS INDICATED ON CIRCUIT BOARD  
5882  
LOCATION  
DIP  
SWITCH  
MOUNTING  
HOLES  
WIRING OPENING  
INTERFERENCE  
INDICATOR  
LED  
KNOCKOUT AREA  
FOR SURFACE WIRING  
CIRCUIT BOARD  
PLUG  
SOCKET  
TO RELEASE CIRCUIT BOARD,  
REMOVE SCREWS AND  
BEND BACK TABS  
5881-003-V0  
Figure 9. 5881/5882 RF Receiver (cover removed)  
Installing a 5800TM Module  
1. Mount the 5800TM next to the RF receiver (between one and two feet from the receiver’s  
antennas) using its accompanying mounting bracket. Do not install within the control cabinet.  
2. Connect the 5800TM to the control panel’s keypad connection terminals as shown on the  
Summary of Connections diagram and set to address 28.  
NOTES  
Use this module only if you are using one or more wireless bi-directional keypads or keyfobs with a  
wireless Receiver; 5800TM is not necessary if using a Transceiver (e.g., 5883).  
The 5800TM must be set to address 28 (cut red-W1 jumper).  
For additional information regarding the 5800TM, refer to the 5800TM’s instructions.  
2-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
Installing the Transmitters  
1. To be sure reception of the transmitter's signal at the proposed mounting location is adequate,  
perform a Go/No Go Test, described in the Testing the System section.  
2. Install transmitters in accordance with the instructions provided with each.  
3. Set 5827, 5827BD, 5804BD wireless keypads to the programmed House ID (field *24), using its  
DIP switches (5827) or follow the instructions provided with the device.  
ULC NOTE: In accordance with ULC standards, the RF supervision period for the VISTA-10P is three hours for  
Fire zones (Zone Type 9 and 16) and 12 hours for all other zone types.  
NOTES  
Refer to the table of compatible devices at the back of this manual.  
Supervised transmitters send check-in signals to the receiver at 70-90 minute intervals. If at least  
one check-in message is not received from each transmitter within a 12-hour period, the “missing”  
transmitter number(s) and “CHECK” is displayed.  
† Hand-held transmitters (e.g., 5802, 5802CP, 5804, 5804BD, 5827, 5827BD) do not send check-in  
signals.  
U
L The following transmitters are not intended for use in UL installations: 5802MN, 5802MN2, 5804, 5804BD,  
5814, 5816TEMP, 5819, 5819WHS & BRS, and 5850.  
The 5827BD and 5800TM can be used in UL Listed Residential Burglar installations.  
Transmitter Battery Life  
• See Wireless Transmitter paragraph in the Limitations of This Alarm System statement located at the end  
of this manual for information on transmitter battery life.  
• Some transmitters (e.g., 5802 and 5802CP) contain long-life but non-replaceable batteries, and no battery  
installation is required. At the end of their life, the complete unit must be replaced (and a new serial number  
enrolled by the control).  
• Button-type transmitters (such as 5801, 5802, and 5802CP) should be periodically tested for battery life.  
• The 5802MN and 5804 Button Transmitters have replaceable batteries.  
Do not install batteries in wireless transmitters until you are ready to enroll during system programming.  
After enrolling, batteries need not be removed.  
Installing a Keyswitch  
1. Connect the 4146 keyswitch's normally open momentary switch to a zone’s terminals. Remove the  
2000 ohm EOL resistor if connected across the selected zone.  
2. Using a standard keypad cable as shown:  
Connect the yellow and white keyswitch wires to trigger connector pin 3 (+12V).  
Connect the Red and Green LED wires to the appropriate output 17/output 18 trigger connector  
pins.  
3. Connect a 2000 ohm EOL resistor across the momentary switch.  
4. You can wire an optional closed-circuit tamper switch (model 112) in series with the zone. If the  
switchplate is then removed from the wall, the tamper will open, disabling keyswitch operation  
until the system is next disarmed from the keypad.  
If the tamper is opened when the system is armed, an alarm will occur.  
NOTES  
Use 4146 keyswitch or any N.O. keyswitch.  
When using a keyswitch, the zone it is connected to is no longer available for use as a protective  
zone.  
Use *56 Menu mode to program the keyswitch zone and assign it zone type 77.  
Use *80 Menu mode to program the LED functions: program outputs 17 and 18 for system  
operation zone type 78 (red LED) and 79 (green LED) as appropriate (see Output Device  
Programming section).  
2-8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting and Wiring the Control  
5-PIN TRIGGER CONNECTOR  
1
3
4
5
U
L A UL Listed keyswitch is required for fire  
installations and UL commercial and residential burglar  
alarm installations.  
If a keyswitch is used on:  
an installation that transmits opening and closing  
signals, the keyswitch zone must be programmed to  
send opening and closing signals.  
4-WIRE  
4146 KEYSWITCH  
CABLE  
(ARMED)  
RED  
YELLOW  
a UL commercial burglar alarm installation, the  
keyswitch’s tamper switch must be connected in to  
the alarm system. This tamper switch zone must  
also be programmed for Zone Type 05 – Trouble by  
Day / Alarm by Night.  
(READY)  
GREEN  
WHITE  
820  
ohms  
820  
ohms  
BLACK  
RED  
TAMPER  
SWITCH (N. C.)  
a fire alarm installation, the keyswitch must be  
BROWN  
BLUE  
BROWN  
located next to an alphanumeric display keypad.  
11  
The Ademco 4146 keyswitch is UL Listed.  
TYPICAL ZONE  
ON CONTROL  
BOARD  
LOCK  
SWITCH (N. O.)  
BLUE  
10  
EOLR  
(use appropriate value)  
Figure 10. Keyswitch Wiring Connections  
Connecting Relay Modules  
1. Mount either remotely or in the control panel.  
2. Connect to control’s keypad terminals using the connector harness supplied with the module. Use  
standard 4-conductor twisted cable for long wiring runs.  
3. Set the module’s device address to address 12.  
4. Connect the desired field wiring to the unit's relay contact terminals.  
NOTES  
Use 4204 module.  
Supervision: 4204 module is supervised against removal. The module’s device address is displayed  
as follows if a module is disconnected from the control’s terminals, or if the module cover is removed  
and the tamper jumper is installed:  
Alpha:  
CHECK xx Wire Expansion  
FAULT xx Wire Expansion  
ALARM xx Wire Expansion  
Fixed-Glass: lxx (or 91 if field *199 set for 2-digit display); where “xx is the module’s address.  
If communication/tamper failure occurs on a device with zones wired to it, all zones on the device  
will be displayed.  
RELAY  
C
4204  
U
4
NC  
NO  
C
L For UL installation requirements, refer to the  
DIP SWITCH  
FOR SETTING DEVICE ADDRESS  
AND ENABLING/DISABLING TAMPER  
TYPICAL  
(SHOWN "OFF")  
Installation Instructions for the 4204.  
RE3LAY  
NC  
COVER TAMPER (REED) SWITCH  
NO  
C
RELAY  
4-PIN TOUCHPAD PLUG  
NC  
NO  
C
2
EITHER OR BOTH  
CAN BE USED  
RELAY  
TB1  
NC  
NO  
1
13 14 15 16  
DATA IN  
FROM CONTROL  
YEL  
BLK  
GRN  
RED  
TB2  
() GROUND  
DATA OUT  
TO CONTROL  
(+) 12V  
4204_conn-1-V0  
Figure 11. 4204 Connections to Control  
2-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
On-Board Triggers  
5-PIN TRIGGER CONNECTOR  
Connect field wiring to the desired trigger pin on  
the 8-pin trigger connector centrally located  
above the terminal strip.  
1
3
4
5
You can use a 4-wire cable as shown.  
U
L If on-board triggers are used, the wiring between  
the control unit and the UL Listed device must be run  
in conduit, be no more than 3 feet apart and have no  
intervening barriers or walls.  
4-WIRE CABLE  
00-trigcon-005-V3  
Figure 12.  
On-Board Trigger Connector with 4-Wire Cable  
NOTES  
There are two on-board triggers that can be used to activate output devices.  
These outputs are normally high, and go low upon programmed condition.  
Outputs can be programmed for inverted operation (normally low, go high) using *79 Menu mode.  
Program these triggers using *80/*81 Menu modes as you would for any other relay output.  
When using these outputs, note:  
pin 1 = output number 17 (trigger 1):  
15 ohms to ground when closed (output low), open when off (output high, normal default); can  
be used to reset smoke detector power (must set “output normal low = yes” in *79 Menu mode,  
and set for zone type 54, fire zone reset, in *80 Menu mode); or can support 12V relay module  
that draws less than 100mA  
pin 5 = output number 18 (trigger 2):  
100 ohms to ground when closed (output low); open when off (output high, normal default); or  
can support 12V relay module that draws less than 20mA  
† e.g., Altronix AX-RBS  
Phone Line/Phone Module Connections  
1. Connect incoming phone line and handset wiring to the main terminal block (via an RJ31X jack)  
as shown in the Summary of Connections diagram at the back of this manual. Wire colors  
represent the colors of the cable to the RJ31X jack.  
If using a phone module, continue with the following steps.  
2. Make 12V (+) and (–) and data in and data out connections from the phone module to the control,  
using the connector cable supplied with the phone module, then insert the keyed connector at the  
other end of the connector cable into the header on the phone module.  
3. Connect Phone Module terminals as shown below. Use an RJ31X jack with a direct-connect cord  
and make all connections exactly as shown.  
4. Caller ID Units: If a Caller ID unit is being used, connect the unit directly to the “Handset”  
terminals (21 & 22) on the control, as shown.  
NOTES  
Use 4285 or 4286 Phone Modules.  
Compatibility: 4286 Phone Modules must have software version WA4286-15.1 or higher (refer to the  
label on the square 4286 microprocessor chip).  
Only one phone module can be used.  
The phone lines must be in service for the phone module to function, even when accessing the system  
from an on-premises phone.  
If you are also using an Audio Alarm Verification (AAV) unit, refer to Audio Alarm Verification  
(AAV) section for special wiring connections.  
CAUTION: To reduce the risk of fire, use only No. 26 AWG or larger telecommunication line cord for  
phone line connections.  
2-10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting and Wiring the Control  
U
L The 4285 and 4286 modules are UL Listed only for use on residential fire and UL residential burglar alarm  
installations.  
Phone Module Problems  
If no touch tones are produced following access to the security system from on-premises (this problem  
may arise in rare cases), it may be necessary to reverse the wires connected to terminals 3 and 4 on  
the phone module and the wires connected to terminals (21) & (22) on the control. The wiring  
diagram shows the wiring connections that will provide proper operation in most cases.  
Connection to the incoming telco line via a RJ31X jack and direct-connect cord, as shown, is essential,  
even if the system is not connected to a central station. Otherwise the 4285/4286 will not function and  
an error signal (fast busy signal) will occur when accessing the system via the phone.  
The house phone lines (gray and brown wires) must be wired to the phone module terminals; not to  
the control terminals. Otherwise, an error signal (fast busy signal) will occur when trying to access  
the system from an on-premises phone.  
INCOMING  
HANDSET TELCO LINE  
GROUND  
TERMINALS  
ON CONTROL  
TO EARTH GROUND (COLD WATER PIPE, ETC.)  
INCOMING TELCO LINE  
21  
22  
23  
24  
25  
CALLER ID  
UNIT  
DIRECT  
CONNECT  
CORD  
TIP  
IMPORTANT NOTE FOR  
RJ31X  
RING  
JACK  
EXISTING INSTALLATIONS:  
EXISTING WIRES  
CONNECTED TO THE  
CA38A  
IN  
CANADA  
"HANDSET" TERMINALS ON  
CONTROL MUST BE MOVED  
FROM THERE TO TERMINALS  
3 AND 4 ON THE 4285/4286.  
PREMISES ANSWERING  
MACHINE AND PHONES  
PLUG  
ANSWERING  
MACHINE  
4285/4286  
*
*
VIP MODULE  
LOUDER  
VOLUME  
(4286  
ONLY)  
KEYED  
HEADER  
* NOTE: IF THE TELEPHONE HAS BUILT-IN CALLER ID,  
THE CALLER ID FUNCTION MAY NOT WORK.  
UNUSED  
4285/4286  
TERMINAL ASSIGNMENTS  
TO CONTROL  
PANEL  
TERMINALS  
USED FOR  
KEYPAD  
YELLOW: TO DATA OUT (term. 7)  
NO CONNECTION  
1 - TIP  
2 - RING  
3 - TIP  
4 - RING  
PHONE INPUT  
}
RED:  
TO AUX (+) (term. 5)  
CONNECTOR  
WITH FLYING  
LEADS  
BLACK: TO AUX. GROUND () (term.4)  
GREEN: TO DATA IN (term. 6)  
PHONE OUTPUT  
}
5 - NO CONNECTION  
CONNECTIONS  
6 -  
7 -  
AUDIO OUT  
4286 ONLY  
}
Figure 13. 4285/4286 Phone Module Wiring Connections  
Long Range Radio Connections  
Connect the data in/data out terminals and voltage input terminals of the Long Range Radio to  
the control's keypad connection points.  
Set the radio’s address to “03” following the instructions provided with the radio.  
Use compatible Long Range Radios (e.g., 7720PLUS, 7820, 7835C, or 7845C).  
2-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
Audio Alarm Verification Connections (AAV, “listen-In”)  
Refer to the connection diagrams below. One diagram shows connections when a 4285/4286 Phone  
Module is used, the other shows connections when the 4285/4286 is not used.  
Connections use one of the on-board triggers.  
U
system)  
UL installations using the AAV feature must use the ADEMCO UVCM module (part of the ADEMCO UVS  
L
Suggested AAV Module: ADEMCO UVS (shown) or Eagle 1250  
NOTES  
Set field *91 for AAV and program the appropriate output (output 17 or 18) using *80 Menu mode:  
select zone type 60 and output action 1 (close for 2 seconds) or action 2 (stay closed).  
For voice session monitoring, connect a zone to UVCM module terminals 6 & 7, and program the  
zone as zone type 81 (*56 Menu mode).  
E.g., Using output 18 for the trigger, program an output function in *80 Menu mode as:  
ZT = 60, P = 0, Action = 1, Device = 18  
TRIGGER  
CONNECTOR  
5
EARTH  
GROUND  
ZONE  
TERMINALS  
CONTROL  
AUXILIARY  
AUDIO LEVEL  
ADJUSTMENT  
TRIM POT  
21 22 23  
4
5
24 25  
EOL  
RING  
TIP  
UVCM  
MODULE  
RED (R)  
GREEN (T)  
GREY (R)  
RJ31X  
BROWN (T)  
NOTE:  
REFER TO UVCM MODULE  
INSTRUCTIONS FOR  
CONNECTIONS TO AUDIO  
SPEAKERS AND MICROPHONE.  
OPTIONAL  
MONITORING ZONE  
CONNECTION  
(USE ZONE TYPE 81)  
TO  
PREMISES  
HANDSET  
SWITCH  
BANK 1  
SWITCH  
BANK 2  
1 = OFF  
2 = OFF  
3 = OFF  
4 = OFF  
5 = OFF  
6 = OFF  
7 = OFF  
8 = ON  
1 = ON  
2 = ON  
3 = OFF  
4 = ON  
5 = ON  
6 = ON  
7 = ON  
8 = ON  
INCOMING  
PHONE LINE  
FALLING VOICE TRIG  
GND  
+12VDC IN  
Figure 14. Connection of AAV Unit When Not Using a 4285/4286 Phone Module  
TRIGGER  
CONNECTOR  
5
EARTH  
GROUND  
ZONE  
TERMINALS  
CONTROL  
AUXILIARY  
AUDIO LEVEL  
ADJUSTMENT  
TRIM POT  
4
5
21 22 23 24 25  
EOL  
RING  
TIP  
UVCM  
MODULE  
RING  
TIP  
RED (R)  
GREEN (T)  
GREY (R)  
RJ31X  
OPTIONAL  
MONITORING  
ZONE  
CONNECTION  
(USE ZONE  
TYPE 81)  
BROWN (T)  
NOTE:  
REFER TO UVCM MODULE  
INSTRUCTIONS FOR  
CONNECTIONS TO AUDIO  
SPEAKERS AND MICROPHONE.  
TO  
PREMISES  
HANDSET  
SWITCH  
BANK 1  
SWITCH  
BANK 2  
1 = OFF  
2 = OFF  
3 = OFF  
4 = OFF  
5 = OFF  
6 = OFF  
7 = OFF  
8 = ON  
1 = ON  
2 = ON  
3 = OFF  
4 = ON  
5 = ON  
6 = ON  
7 = ON  
8 = ON  
INCOMING  
PHONE LINE  
FALLING VOICE TRIG  
4285/4286  
4
3
2
GND  
+12VDC IN  
1
Figure 15. Connection of AAV Unit When Using a 4285 or 4286 Phone Module  
2-12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S E C T I O N  
3
Programming Overview  
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •  
About Programming  
You can program the system at any time, even at the installer's premises prior to the actual  
installation. Programming can also be performed remotely from the installer’s office/home, using an  
IBM personal computer, a modem, and Compass downloading software.  
The following is a list of the various Programming modes used to program this system:  
Programming Mode…  
Used to …  
Data Field Programming  
Program basic data fields used for setting the various system options.  
Most of the data fields in this system have been programmed for specific  
default values. However, some fields must be programmed for each particular  
installation to establish its specific alarm and reporting features.  
Assign zone characteristics, report codes, alpha descriptors, and serial  
numbers for 5800 RF transmitters.  
56 Zone Programming  
Program each of the four alphabet function keys to perform one of several  
system operations.  
57 Function Key Programming  
58 Zone Programming  
(Expert Mode)  
Assign zone attributes similar to 56 mode, but provides a faster  
programming procedure and is intended for those more experienced in  
programming controls of this type.  
Assign device address of the 4204 Relay module and map the specific relays  
Define up to 12 output definitions which can control the output relays mapped  
using *79 Output Device Mapping mode.  
79 Output Device Mapping  
80 Output Definitions  
Create Zone Lists for relay zones, chime, night-stay, cross zones, and pager  
zones.  
81 Zone List Programming  
Create alpha descriptors for easy zone identification.  
Create schedules to automate various system functions.  
82 Alpha Programming  
Scheduling Mode (code + [#] +64)  
Keypads  
Keypads are identified by predefined addresses (starting at address 16) as follows:  
Address Keypad  
Program Field  
16  
17  
18  
19  
20  
21  
22  
23  
keypad 1  
keypad 2  
keypad 3  
keypad 4  
keypad 5  
keypad 6  
keypad 7  
keypad 8  
always enabled, all sounds enabled.  
data field *190  
data field *191  
data field *192  
data field *193  
data field *194  
data field *195  
data field *196  
NOTE: First keypad is address 16.  
To enable keypads:  
1. Set desired address at keypad (refer to keypad’s instructions for setting the address).  
2. Use data field program mode to enable keypad addresses and enable sound options in fields *190-  
*196 as shown in the table above.  
3. Set the following keypad-related data fields as required by the installation:  
*21 Quick Arm Enable; *23 Forced Bypass; *84 Auto STAY Arm  
3-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
Wireless Receiver, Transmitters, and Wireless Keys (keyfobs)  
Receiver: Set the receiver’s address to “00” using its DIP switches, then set the following options:  
*22 RF Jam Option  
*24 RF House ID Code (if using wireless keypads)  
*67 Transmitter Low Battery Report Code  
*75 Transmitter Low battery restore report code  
*173 RF Reporting Options  
These fields must be enabled for Residential  
Fire, UL Residential Burglar Alarm, and UL  
Commercial Burglar Alarm installations.  
Transmitters: Use *56 or *58 Zone Programming Menu modes to program zone information and  
enroll transmitters.  
Wireless Keys: Use Wireless Key Programming Templates section of the *58 Zone Programming  
Menu mode to program zone information and enroll each button of the wireless keys  
used. Once a wireless key is enrolled, it must be assigned to a user before it becomes  
active. See Adding/Deleting Security Codes section for procedure.  
Pager Programming  
The system can send various reports to a pager.  
To program pager reporting, do the following:  
1. Enter the appropriate information in the following data fields:  
*160, Pager Phone Number  
*161, Pager Prefix Characters  
*162, Pager Reporting Options  
2. Enable Pager Delay, if desired, in field *172  
3. Make sure appropriate user open/close pager reports are enabled using the user attribute  
command (see Security Codes, Assigning Attributes in Section 6. System Communication and  
Operation).  
4. If using latchkey pager report, define the latchkey report schedule using Scheduling mode (master  
code + [#] [6] [4] then select event type “03”). System must be armed for the Latchkey report to be  
sent.  
5. If using a function key to manually send a message to a pager, see Function Keys paragraph on  
the next page.  
6. If reporting zone alarms and troubles to a pager, use *81 Zone List menu mode to assign the zones  
associated with each pager (zone lists 9).  
Function Keys  
To assign functions to the function keys, use *57 Function Key menu mode.  
To assign emergency key functions (function key option “00”), first program the respective emergency  
zone number (95 for “A” key, 96 for “C” key, 99 for “B” key) with the desired zone type using *56 Zone  
Programming mode, then use *57 Function Key menu mode to assign the desired key.  
If using a function key to activate a relay action (*57 Menu mode key function 07), use *79 Menu  
mode to map the output, and use *80 Menu mode to define the output’s action; select system  
operation type “66.”  
If using a function key for a user macro, use *57 menu mode to activate the desired key, then define  
the actual macro functions using the user code + [#] + [6] [6] command.  
Output Devices  
To program a device for manual activation (user code + [#] [7] / [#] [8] + 2-digit device number) or for  
scheduled automatic activation, simply map the device using *79 Menu mode.  
To program a device to automatically activate upon a system event (or function key), use *79 Menu  
mode to map the device, then use *80 Menu mode to define the automated device action.  
If the device action is based on more than one zone, use *81 Zone List menu mode to assign the zones.  
3-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Zone Type Definitions  
You must assign a zone type to each zone, which defines the way in which the system responds to  
faults in that zone. Zone types are defined below.  
Zone Type  
Type 00  
Description  
Program a zone with this zone type if the zone is not used.  
Zone Not Used  
Type 01  
Entry/Exit Burglary #1  
Assign to zones that are used for primary entry and exit.  
Provides entry delay when zone is faulted if control is armed in the Away, Stay,  
or Night-Stay modes.  
No entry delay provided when the panel is armed in the Instant/Maximum mode.  
Entry delay 1 is programmable.  
Exit delay begins whenever the control is armed, regardless of the arming mode  
selected, and is programmable.  
Type 02  
Entry/Exit Burglary #2  
Assign to zones that are used for entry and exit and require more time than the  
primary entry/exit point.  
Provides a secondary entry delay, in same manner as entry delay #1.  
Entry delay 2 is programmable.  
Exit delay is same as described for Type 01.  
Type 03  
Perimeter Burglary  
Assign to all sensors or contacts on exterior doors and windows.  
Provides an instant alarm if the zone is faulted when the panel is armed in the  
Away, Stay, Night-Stay, Instant or Maximum modes.  
Type 04  
Interior Follower  
Assign to a zone covering an area such as a foyer, lobby, or hallway through  
which one must pass upon entry (to and from the keypad).  
Provides a delayed alarm (using the programmed entry 1 time) if the entry/exit  
zone is faulted first. Otherwise this zone type gives an instant alarm.  
Active when the panel is armed in the Away mode.  
Bypassed automatically when the panel is armed in the Stay or Instant modes;  
if armed in Night-Stay mode, zones assigned to zone list 05 (night-stay zone list)  
are not bypassed when system armed in Night-Stay mode.  
Assign to a zone that contains a foil-protected door or window (such as in a store),  
or to a zone covering a sensitive area such as a stock room, drug supply room, etc.  
Can also be used on a sensor or contact in an area where immediate notification  
of an entry is desired.  
Type 05  
Trouble by Day/  
Alarm by Night  
Provides an instant alarm if faulted when armed in the Away, Stay, Night-Stay,  
Instant or Maximum (night) modes.  
During the disarmed state (day), the system will provide a latched trouble  
sounding from the keypad (and a central station report, if desired).  
Usually assigned to a zone containing an emergency button.  
Sends a report to the central station but provides no keypad display or sounding.  
Type 06  
24-hour Silent Alarm  
Type 07  
24-hour Audible Alarm  
Assign to a zone that has an emergency button.  
Sends a report to the central station, and provides an alarm sound at the keypad,  
and an audible external alarm.  
Type 08  
24-hour  
Auxiliary Alarm  
Assign to a zone containing an emergency button, or to a zone containing  
monitoring devices such as water or temperature sensors.  
Sends a report to the central station and provides an alarm sound at the keypad.  
(No bell output is provided.)  
Type 09  
Supervised Fire  
Provides a fire alarm on short circuit and a trouble condition on open circuit. A  
fire alarm produces a pulsing bell output.  
This zone type is always active and cannot be bypassed.  
Type 10  
Interior w/Delay  
Provides entry delay (using the programmed entry time), if tripped when the  
panel is armed in the Away mode.  
Entry Delay 1 begins whenever sensors in this zone are violated, regardless of  
whether or not an entry/exit delay zone was tripped first.  
Bypassed when the panel is armed in the Stay or Instant modes; if armed in  
Night-Stay mode, zones assigned to zone list 05 (night-stay zone list) are not  
bypassed when system armed in Night-Stay mode.  
3-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
Type 12  
Monitor Zone  
Works as a dynamic monitor of a zone fault/trouble (not alarm). In the case of a  
short/open, the message, "*ALARM*-24 Hr. Non-Burg. -#XXX " (where XXX is the  
zone number) will be sent to the Central Station. The system keypad will display  
a “check” message indicating the appropriate zone (but keypad beeping does not  
occur). Upon restoral of the zone, the message, "*RESTORE*-24 Hr. Non-Burg. -  
#XXX " will be sent to the Central Station.  
The “check” message will automatically disappear from the keypad dynamically,  
when the zone restores; a user code + off sequence is not needed to reset the zone.  
Faults of this zone type are independent of the system, and can exist at the time  
of arming without interference.  
Since this is a “trouble” zone type, do not use this zone type with relays set to  
activate upon “alarm.”  
Type 14  
24 Hour Carbon  
Monoxide Monitor  
Assigned to any zone with a carbon monoxide detector.  
The bell output will pulse when this zone type is alarmed.  
Always active and cannot be bypassed.  
Type 16  
Fire w/Verification  
Provides a fire alarm when zone is shorted, but only after alarm verified.  
System verifies alarm by resetting zones for 12 seconds after short is detected. A  
subsequent short circuit within 90 seconds triggers fire alarm.  
Provides a trouble response when zone is open.  
Type 20  
Arm-Stay (BR only)  
Arms the system in Stay mode when the zone is activated.  
Pushbutton units send the user number to the central station when arming or  
disarming.  
User number for button must be assigned.  
Type 21  
Arm-Away (BR only)  
Arms the system in Away mode when the zone is activated.  
Pushbutton units send the user number to the central station when arming or  
disarming.  
User number for button must be assigned.  
Disarms the system when the zone is activated.  
User number for button must be assigned.  
Type 22  
Disarm (BR only)  
Type 23 *  
No Alarm Response  
Can be used on a zone when an output relay action is desired, but with no  
accompanying alarm (e.g., lobby door access).  
Type 24  
Silent Burglary  
Usually assigned to all sensors or contacts on exterior doors and windows where  
bells and/or sirens are NOT desired.  
Provides an instant alarm, with NO audible indication at any keypad or external  
sounder, if the zone is faulted when the system is armed in the Away, Stay,  
Instant, or Maximum modes.  
A report is sent to the central station.  
Type 77  
Keyswitch  
Assign to zone wired to a keyswitch.  
Do not use devices assigned as input type “BR” with this zone type.  
Type 81  
AAV Monitor Zone  
Assign to zone connected to AAV module.  
Monitors 2-way voice sessions as follows:  
- When the zone is faulted, all alarm sounding and dialer reporting stops, except  
for fire alarms, which immediately terminate the voice session and cause  
a fire report to be sent.  
- When the zone is restored (session ended), sounding resumes (if bell timeout  
has not expired) and reports that were stopped are sent.  
Allows for a custom zone response. Options include response to entry/exit delays,  
response opens/shorts, types of alarm/trouble sounding, dial delay, and unique  
Contact ID report code.  
Types 90  
Configurable  
UL installations: Zone Type 90 may not be used as fire or burglar alarm zones on  
fire or UL burglar alarm installations.  
* The system can still be armed when these zone types are in a faulted condition.  
NOTE: All of the zone types described are available for the wireless portion of the system, if used.  
3-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanics of Programming  
Data Field Programming Procedures (You must use a 2-line Alpha display keypad)  
Task  
Procedure  
Entering Program Mode  
A) Press both [ ] and [#] at the same time within 50 seconds after power is applied  
to the control, OR  
B) After power-up, enter [Installer code (4-1-1-2)] + 8 0 0.  
(method “B” is disabled if you exit the program mode using 98)  
Go to a Data Field  
Entering Data  
Press [ ] + [Field Number] (for example, 21).  
A display of “EE” or “Entry Error” means you have entered a nonexistent field.  
Simply re-enter [ ] plus a valid field number.  
When the desired field number appears, simply enter the digits required. The  
keypad beeps three times after the last digit is entered and automatically displays  
the next data field in sequence.  
If entering less than the maximum digits available (e.g., phone number field),  
enter the desired digits, then press [ ] to end the entry.  
Review a Data Field  
Deleting an Entry  
Press [#] + [Field Number]. Field data is displayed, but no changes can be made.  
Press [ ] + [Field No.] + [ ] (applies only to phone number, account number, and  
pager character fields).  
Menu Mode Programming (56, *57, 58, 79, 80, 81, 82)  
Entering Menu Mode  
Press [ ] + [Menu Mode No.] (for example, 56) while in Program Mode. The  
Alpha display keypad displays the first of a series of prompts.  
After making the appropriate entry, press the [] key to accept the entry and  
continue to the next prompt.  
Loading Factory Defaults/Initializing for Download  
To Load Default Entries  
Press 97 while in Program Mode. This resets all data fields to the default  
values shown on the Program Form. Use 97 only if you wish to return to the  
original factory-programmed defaults. Do not press 97 to load defaults if any  
programming has been done previously—data already programmed into the  
system will be changed!  
To Initialize Download ID  
Press 96 while in Program Mode. This initializes the system for  
downloading and resets all the subscriber account numbers and CSID.  
Exiting the Programming Mode  
Prevent installer code reentry  
Press 98. Exits Programming Mode and prevents re-entry by:  
Installer Code + [8] + [0] + [0]. To enter the programming mode if 98 was  
used to exit, you must first power the system down. Then power up again,  
and press [] and [#] at the same time, within 50 seconds of powering up.  
See field *88 for other Program mode lockout options.  
Allow installer code reentry  
Press 99. Exits Program Mode and allows re-entry by method A or B above.  
3-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
Table of Device Addresses  
Reports as††  
This Device  
Uses Address  
Enabled By…  
RF Receiver  
Long Range Radio  
4286 Voice Module  
4204 Relay Module  
Keypads:  
keypad 1  
keypad 2  
keypad 3  
keypad 4  
keypad 5  
keypad 6  
keypad 7  
keypad 8  
00  
03  
04  
12  
100  
103  
104  
112  
*56 zone programming: input device type entry  
automatic if output to long range radio field *29 enabled  
automatic if phone module access code field *28 enabled  
*79 output device programming: entered at device address prompt:  
data field programming as listed below:  
always enabled, all sounds enabled.  
data field *190  
data field *191  
data field *192  
data field *193  
data field *194  
data field *195  
data field *196  
16  
17  
18  
19  
20  
21  
22  
23  
28  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
5800TM Module  
automatic  
†† Addressable devices are identified by “1” plus the device address when reporting. Enter a report code for zone 91 to enable  
addressable device reporting (default = reports enabled). See field *199 for addressable device (ECP) 3-digit/2-digit  
identification keypad display options.  
3-6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S E C T I O N  
4
Data Field Programming  
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •  
About Data Field Programming  
The following pages provide explanations of this control’s data fields and is intended to be used in  
conjunction with the Programming Guide. Refer to the Programming Guide for the specific  
option choices for each data field.  
Use the blank programming form to record the data for this installation.  
Programming Data Fields  
Data field programming involves making the appropriate entries for each of the data fields.  
Start Data Field programming by entering the installer code + 8 + 0 + 0.  
SIA Guidelines: Notes in certain data fields give instructions for programming the VISTA-10P for False Alarm  
Reduction.  
Fields unique to the VISTA-10PSIA are indicated by heavy borders and reverse type for easy  
identification.  
System Setup Fields  
FIELD  
TITLE and EXPLANATION  
Installer Code  
*20  
Enter a 4-digit Installer Code. This code can perform all system functions except it cannot disarm the  
system unless it is used to arm the system.  
Quick Arm Enable  
*21  
Select whether or not users can press the [#] key in place of entering a security code when arming the  
system (e.g., to arm AWAY, press [#] + AWAY). If not selected, users must enter a security code to arm  
the system. In either case, the user code is always needed to disarm the system.  
RF Jam Option  
*22  
*23  
Select whether or not the system sends an RF jam report if an RF jamming signal is detected.  
UL installations must be 1 if wireless devices are used.  
Quick (Forced) Bypass  
Select whether or not the Quick Bypass command (code +[6] + [#]) is active. Zones bypassed by this  
function will be displayed after the bypass is initiated.  
UL installations must be 0 (no forced bypass)  
RF House ID Code  
*24  
*26  
*28  
Enter the RF House ID, which identifies receivers and wireless keypads. If a 5827 or 5827BD Wireless  
Keypad or 5804BD Transmitter is being used, a House ID code must be entered, and the keypad set to  
the same House ID.  
Chime By Zone List 3  
Select if you want a list of specific zones to chime when faulted while the system is in Chime mode (use  
zone list 3 to assign these zones; see 81 Zone List Programming section for details). If not selected,  
all entry/exit and perimeter zones will chime when faulted and system is in Chime mode.  
Access Code for Phone Module  
Enter a 2-digit access code for the 4285/4286 Phone Module, if used. Example: If desired access code is  
7, 7 is the first entry, and [#] + 11 (for ) is the second entry.  
NOTE: A “0” in either digit disables the phone module.  
Must be “00” for UL Commercial Burglar Alarm installations.  
Long Range Radio Output  
*29  
Select whether or not all messages programmed to go to the primary telephone line receiver will also be  
sent to the connected 7720PLUS, 7820, 7835, or 7845 Radio (sent in Contact ID format). The data line is  
supervised as well as certain functions in the radio. If communication is lost or a trouble develops, an  
attempt will be made to send a message via both radio and telephone to the central station.  
Program the radio for device address 3.  
4-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
Zone Sounds & Timing  
FIELD  
TITLE and EXPLANATION  
Single Alarm Sounding Per Zone  
Select whether or not the system limits alarm sounding to once per arming period for a given zone.  
*31  
VISTA-10PSIA: If “0” selected, “alarm sounding per zone” will be the same as the “number of reports  
in armed period” set in field *93 (1 if one report, 2 if 2 reports, unlimited for zones in zone list 7).  
Fire Alarm Sounder Timeout  
Select whether or not alarm sounding continues until manually turned off (ignores sounder timeout). If  
not selected, sounding stops at timeout programmed in 33.  
*32  
This control complies with NFPA requirements for temporal pulse sounding of fire notification  
appliances. Temporal pulse sounding for a fire alarm consists of the following:  
3 pulses – pause – 3 pulses – pause – 3 pulses. UL fire alarm installations: must be 1.  
Alarm Sounder Timeout  
*33  
*34  
Enter the desired alarm sounding time. Entering “0” lets sounding continue until manually turned off.  
UL installations: For residential fire alarm installation, must be set for a minimum of 4 min (option 1);  
for UL Commercial Burglary installations, must be minimum of 16 min (option 4).  
Exit Delay  
Enter the desired time the system waits before arming entry/exit zones. If the entry/exit door is left  
open after this time expires, an alarm will occur.  
UL installations: For UL Commercial Burglar Alarm (Grade AA) and UL Residential Burglar Alarm  
installations with line security, total exit time must not exceed 60 seconds. For UL Burglar Alarm  
installations without line security (Grade A), total exit time must not exceed 120 seconds.  
SIA Guidelines: minimum exit delay is 45 seconds  
VISTA-10PSIA: 45 - 96 = 45 - 96 secs; 97 = 120 secs  
NOTE: Entries less than 45 will result in a 45-sec delay.  
Entry Delay 1  
*35  
Enter the desired time within which the system must be disarmed after opening an entry door. If this  
time expires without disarming, an alarm occurs.  
UL installations: For UL Residential Burglary Alarm installations, must be set for a maximum of 30  
seconds; entry delay plus dial delay should not exceed 1 min. For UL Commercial Burglar Alarm, total  
entry delay may not exceed 45 seconds. SIA Guidelines: minimum entry delay is 30 seconds  
VISTA-10PSIA: 30-96 = 30 - 96 secs; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs  
NOTE: Entries less than 30 will result in a 30-sec delay.  
Entry Delay 2  
*36  
*37  
Use this entry for a secondary entry door. See *35 above for explanation.  
Audible Exit Warning  
Select whether or not you want exit warning sounds, which consist of slow continuous beeps until the  
last 10 seconds, then it changes to fast beeps. Sound ends when exit time expires.  
SIA Guidelines: must be enabled (enter 1)  
VISTA-10PSIA: Feature always enabled; field does not exist.  
Confirmation Of Arming Ding  
*38  
*39  
Select whether and when you want a confirmation of arming “ding” (1/2 second external sounder “ding”).  
If “1” selected, ding occurs when closing report is sent, or at the end of Exit Delay.  
If “2” selected, ding occurs upon reception of the wireless arming command.  
UL installations: must be “1” for UL Commercial Burglar Alarm installations.  
Power-Up In Previous State  
Select whether or not the system powers up in its previous state (if the system powers up armed and a  
zone is faulted, an alarm will occur 1 minute after power up). Note that if the previous state was armed  
Away or Stay, the system will not respond to sensor changes for 1 minute, which allows time for  
sensors such as PIRs to stabilize.  
UL installations: must be 1 (power-up in previous state); SIA Guidelines: must be 1 (power-up in  
previous state)  
VISTA-10PSIA: Feature must be enabled.  
4-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dialer Programming  
FIELD  
TITLE and EXPLANATION  
PABX Access Code  
*40  
Enter the PABX code, if used. To clear entries from field, press 40. If fewer than 6 digits need to be  
entered, exit by pressing [], which advances to the next field.  
Call Waiting: If the subscriber’s phone service has “call waiting” (and is not using PABX), enter “*70”  
(“# + 11”) plus “# + 13” (pause) as the PABX entry to disable “call waiting” during control panel calls. If  
the subscriber does not have “call waiting” and is not using PABX, make no entry in this field.  
Important: 1. The call waiting disable feature cannot be used on a PABX line. 2. Using Call Waiting  
Disable on a non-call waiting line will prevent successful communication to the central station.  
VISTA-10PSIA: If call waiting is used, enter call waiting disable digits as described above, and also set  
Call Waiting Disable option in field *91.  
Primary Phone No.  
*41  
*42  
Enter the primary phone number. If you enter fewer than 20 digits, exit by pressing []. To clear  
entries from field, press 41.  
NOTE: Backup reporting (8 calls are made to the secondary phone number if no kissoff is received  
after 8 attempts to the primary number) is automatic only if there is a secondary number (field 42).  
Secondary Phone No.  
Enter the secondary phone number. If you enter fewer than 20 digits, exit by pressing []. To clear  
entries from field, press 42. See backup reporting note for field 41. Don’t fill unused spaces.  
Primary Subs. Acct. No.  
Enter the primary subscriber account number. To clear entries from field, press 43.  
*43  
*44  
*47  
*48  
*49  
Secondary Subs. Acct. No.  
Enter the secondary subscriber account number. To clear entries from field, press 44.  
Phone System Select  
Select whether the system will be using pulse or tone dialing, and whether it is on a WATS line.  
Report Format (Primary/Secondary)  
Select the report format for primary/secondary phone lines from the list on the Programming Guide.  
Split/Dual Reporting  
Select the desired type of reports to be sent to the primary/secondary numbers. Make selection from the  
table in the Programming Guide. If “0” selected, all reports go only to the primary number unless  
unsuccessful, then control will attempt to dial secondary number.  
Burglary Dialer Delay  
*50  
Enter the desired delay time (none, 15, 30, or 45 seconds) before a “BURGLARY ALARM” report is sent  
to the central station. This delay allows time for the subscriber to avoid sending a false alarm if the  
alarm was inadvertently caused. This delay does not apply to zone type 24 alarms (silent burglary) or  
to 24-hour zone types 6, 7, and 8 (silent panic, audible alarm, auxiliary alarm), which are always sent  
as soon as they occur. UL: must be “0”; SIA Guidelines: delay must be minimum of 30 seconds  
VISTA-10PSIA: Delay Time: 1 = 15 secs; 2 = 30 secs; 3 = 45 secs  
Delay Disable: 0 = use delay set in entry 1  
1 = dial delay disabled for zones listed in zone list 6 (use zone list 6 to enter those zones that  
require dial delay to be disabled; these zones ignore the setting in entry 1)  
UL: Dial delay plus entry delay must not exceed one minute; use zone list 6 to disable dial delay  
from appropriate zones, if necessary.  
SESCOA/Radionics Select  
*53  
*54  
Select whether SESCOA format is used.  
Dynamic Signaling Delay (Intended for use with Long Range Radio reporting)  
Enter the desired time (0-255 seconds in 15-second increments) the panel should wait, per message, for  
acknowledgment from the first reporting destination (see 55) before it attempts to send a message to  
the second destination. Entering ”0” sends redundant reports to both Primary Dialer and LRR.  
UL Installations: For Fire Alarm and UL Burglar Alarm installations without Line Security (Grade A),  
the maximum Dynamic Signaling Delay must be no more than 15 seconds.  
For UL Burglar Alarm installations with Line Security (Grade AA), Dynamic Signaling Delay must be  
“0”. The reports will be sent to both the dialer and the LRR.  
4-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
Dynamic Signaling Priority  
*55  
UL Installations: For UL Commercial Burglary installations that use a DACT and LRR, the DACT must be programmed  
for priority (option 0).  
Intended for use with Long Range Radio reporting (field 29 OUTPUT TO LONG RANGE RADIO must  
be enabled).  
Select the initial reporting destination for messages as follows:  
Primary Dialer First selected (0):  
If acknowledged before delay expires (see 54), then message will not be sent to LRR.  
If not acknowledged before delay expires, message is sent to both the Primary Phone No. and LRR.  
Long Range Radio First selected (1):  
If acknowledged before delay expires, then message will not be sent to the primary dialer.  
If not acknowledged before delay expires, then message is sent to both Primary Phone No. and LRR.  
Zone Programming Menu Mode  
*56  
*57  
*58  
Use this menu mode to program zone information. See Zone Programming section for procedures.  
Function Key Menu Mode  
Use this menu mode to program keypad function keys. See Function Key section for procedures.  
Expert Zone Programming Menu Mode  
This menu mode can be used to quickly program zone information, but is recommended only for those  
already familiar with *56 menu mode. See Zone Programming section for procedures.  
System Status Report Codes  
Zone report codes are programmed using interactive 56 or 58 Zone Programming modes, while system status  
(non-alarm) codes and restore codes are entered in data fields *59 - *68, *70 - *76, *89. The actual report code digits  
that you enter depend on the installation, and should agree with the Central Station office receiving the signals.  
3+1 or 4+1 Standard Format: Enter a code in the first box: 1–9, A, B, C, D, E, or F. Enter #+10 for A (this  
reports a 0 on some receivers), #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F.  
An entry of 0 in the first box disables a report. Entering 0 in the second box advance to the next field.  
Expanded or 4+2 Format: Enter codes in both boxes (first and second digits) for 1–9 or A–F, as described above.  
“0” in the first box disables a report. “0” in the second box eliminates the expanded message for that report.  
ADEMCO Contact ID® Reporting: Enter a digit in the first box to enable the zone to report. Use a different  
digit for each zone until you have used up available digits. If the number of zones exceeds the number of  
available digits, begin with digit 1 again. This is an “enabling” code only and is not the actual code sent to the  
Central Station office. Entries in the second boxes are ignored. An entry of 0 in the first box disables the report.  
UL installations: Program fields *59 - *76 as required by applicable UL Standards shown in each field.  
FIELD  
TITLE and EXPLANATION  
Exit Error Report Code  
*59  
After arming the system, entry/exit and interior zones remaining open after exit delay expires cause an  
alarm sound at the keypad and external sounder (keypad also displays “EXIT ALARM”), and entry  
delay begins. Disarming before the end of the entry delay stops alarm sounding and no message is sent  
to the central station. The keypad displays “CA” (fixed-word) or “ALARM CANCELED” (alpha display).  
If the system is not disarmed before entry delay expires, an “EXIT ALARM” message (VISTA-10PSIA:  
also zone alarm message) will be sent to the central station if Exit Error Report Code is enabled. The  
keypad will display “EA” (fixed-word ) or “EXIT ALARM” (alpha display), and alarm sounding  
continues until the system is disarmed (or timeout occurs).  
An Exit Alarm condition will also result if a fault occurs in an exit or interior zone within 2 minutes  
following the end of the exit delay, and an “EXIT ALARM” message will be sent to the central station  
(except for VISTA-10PSIA, see field *69 Recent Closing report).  
VISTA-10PSIA: [1] Always enabled. Also see field *69.  
Trouble Report Code  
*60  
*61  
Enter the appropriate report code, which is sent if a zone has a trouble condition.  
UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations.  
Bypass Report Code  
Enter the appropriate report code, which is sent when a zone is manually bypassed.  
UL: Required for UL commercial burglar alarm installations.  
4-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIELD  
TITLE and EXPLANATION  
AC Loss Report Code  
*62  
Enter the appropriate report code. Timing of this report is random with up to a 4-hour delay. If AC  
restores before the report goes out, there is no “AC RESTORE” report.  
UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations.  
Low Bat Report Code  
*63  
*64  
Enter the appropriate report code; sent when a low-battery condition exists in the system’s battery.  
UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations.  
Test Report Code  
Enter the appropriate report code, which is sent periodically to test that the communicator and phone  
lines are operational. Frequency of report is set in Scheduling mode (event 11) or by the following key  
commands: installer code + [#] + 0 + 0 = test report sent every 24 hours  
installer code + [#] + 0 + 1 = test report sent once per week  
installer code + [#] + 0 + 2 = test report sent every 28 days  
Each mode sets schedule 2 to the selected repeat option; first test report sent 12 hours after command.  
NOTE: Make sure the Real-Time Clock is set to the proper time before entering the test report schedule  
command to ensure that test reports are sent when expected. (see Setting the Real-Time Clock section).  
UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations.  
Open Report Code  
Enter the appropriate report code, which is sent upon disarming of the system.  
UL: Required for UL commercial burglar alarm installations.  
*65  
Arm Away/Stay Report Code  
*66  
*67  
Enter appropriate report code. NOTE: “OPEN” reports not sent if associated closing report is not enabled.  
RF Trans. Low Batt. Report Code  
Enter the appropriate report code; sent when a wireless transmitter low-battery condition exists.  
UL installations: must be enabled if wireless devices are used.  
Cancel Report Code  
*68  
*69  
Enter the appropriate report code; sent upon disarming of the system after an alarm was reported.  
VISTA-10PSIA: Default = code enabled  
Recent Closing Report VISTA-10PSIA only Always enabled. Field does not apply to other controls.  
Similar to the Exit Error condition described in field *59, but occurs if any burglary zone is faulted within two  
minutes after the initial exit delay expires. Disarming the system within the two minutes stops the alarm  
sound and displays " ALARM CANCELED " or "CA" and the faulted zone number. No message is sent to the  
Central Monitoring Station.  
If the system is not disarmed within two minutes, the alarm sound continues and a “recent closing” and a “zone  
alarm” message are sent to the Central Monitoring Station (after dial delay expires).  
Alarm Restore Report Code  
Enter the appropriate report code; sent when an alarm zone is restored to its non-faulted condition.  
UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations.  
*70  
*71  
*72  
*73  
*74  
*75  
Trouble Restore Report Code  
Enter the appropriate report code, which is sent when a trouble in a zone is restored  
UL: Required for UL commercial burglar alarm installations.  
Bypass Restore Report Code  
Enter the appropriate report code, which is sent when a zone that has been bypassed is unbypassed.  
UL: Required for UL commercial burglar alarm installations.  
AC Restore Report Code  
Enter the appropriate report code; sent when AC power has been restored after an AC power outage.  
UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations.  
Low Bat Restore Report Code  
Enter the appropriate report code; sent when a system low-battery condition is restored to normal.  
UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations.  
RF Xmtr Low Batt. Restore Code  
Enter the appropriate report code; sent when a trans. low battery is restored (new battery installed).  
UL installations: must be enabled if wireless devices are used. Required for UL commercial burglar  
alarm installations and required for residential fire alarm installations.  
4-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
FIELD  
TITLE and EXPLANATION  
Test Restore Report Code  
Enter the appropriate report code, which is sent when the Test mode is exited.  
UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations.  
*76  
Miscellaneous System Fields  
FIELD  
TITLE and EXPLANATION  
Daylight Saving Time Start/End Month  
Enter the start and end month for daylight savings time, if applicable to the region.  
*77  
Daylight Saving Time Start/End Weekend  
*78  
*79  
Enter the start and end weekend for daylight savings time, if applicable to the region.  
Output Device Mapping Menu Mode  
Use this menu mode to enter output devices/powerline carrier devices into the system. See Output Device  
Programming section for procedures.  
Output Programming Menu Mode  
Use this menu mode to define output functions for use with output devices/powerline carrier devices. See  
Output Programming section for procedures.  
*80  
Zone List Programming Menu Mode  
*81  
*82  
*84  
Use the menu mode to define zone lists. See Zone List Programming section.  
Alpha Descriptor Programming Menu Mode  
Use this menu mode to assign alpha descriptors to zones.  
Auto-Stay Arm  
If enabled, the system will automatically change AWAY mode to STAY mode if the entry/exit door is not  
opened and closed within the exit delay time after a user arms in AWAY mode from a wired keypad (non-  
RF device). An Opening report followed by an Armed Stay report is sent to the Central Station.  
If the door is opened and closed within the exit delay period, the system remains in AWAY mode.  
Any RF device that arms the system AWAY overrides this feature and the system remains armed AWAY.  
Cross Zone Timer  
*85  
*86  
Select the maximum amount of time in which two cross zones must be tripped in an armed system to  
send an alarm message to the Central Station. If only one cross zone is tripped during this time, a  
trouble message (CID code 380) for that zone is sent to the Central Station.  
Assign cross zone pairs in zone list 4. This option not for use in UL installations.  
Cancel Verify Keypad Display  
Select whether “ ALARM CANCELEDis displayed on the LCD keypad under the following conditions:  
After the kissoff of the cancel message to the Central Station, indicating a successful transmission.  
When an alarm is successfully canceled before the Central Station received the Alarm message. E.g., if  
an alarm is incorrectly triggered and the user presses code + OFF before the dial delay time has  
expired, the message will never go out to the CS.  
When the Cancel report is not enabled and the system is disarmed:  
a. before dialer delay expires (alarm report not sent) message “Alarm Canceled” is displayed.  
b. after dialer delay expires message “Alarm Canceled” is not displayed  
.
Misc. Fault Delay Time  
*87  
*88  
Enter the desired fault delay time. Used with zones assigned to a configurable zone type with fault delay  
on (configurable zone type digit “6”), and sets a zone response time of 15 seconds to 15 min. It can be  
assigned to zones with sensors that provide a trouble indication when an oil tank is low, or similar  
applications for critical condition monitoring where a non-alarm response is desired.  
UL: May only be used on non-burglar alarm and non-fire alarm zones when used on a fire and/or UL  
burglar alarm installation.  
Program Mode Lockout Options  
0 = standard *98 installer code lockout (reentry only by [] + [#] within 50 secs after power up or  
downloader)  
1 = lockout [] + [#] reentry after *98 exit (reentry only by installer code or downloader)  
2 = not used  
3 = lockout all local programming after *98 exit (reentry by downloader only)  
4-6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIELD  
TITLE and EXPLANATION  
Event Log Full Report Code  
Enter the appropriate report code, which is sent when the event log is 80% full (if an event log enable is  
made in field 90). If the log becomes full, new messages overwrite the oldest messages in the log.  
*89  
Event Log Enables  
*90  
Select the types of events (up to 32 events) the system should log. The downloader operator can then  
upload the log and view or print out all or selected categories of the log. The downloader operator can  
also clear the log. The Event log can also be viewed at an alpha keypad. The display/printout at the  
central station will show the date, time, event, and description of occurrences.  
Example: For Alarm/Alarm Restore” and “Open/Close”, enter 9 (1+ 8); to select all events, enter #15.  
Option Selection  
*91  
Select the desired options by adding the values of each desired option. Multiple choice example: for both  
AAV and Exit delay restart, enter # + 12 (4 + 8).  
VISTA-10PSIA: Options: Same as VISTA-10P.  
Call Waiting Disable: 0 = call waiting not used  
1 = call waiting disable digits (*70) entered in field *40; (when selected, the system dials the entry  
in field *40 only on alternate dial attempts; this allows proper dialing in the event call waiting  
service is later canceled by the user).  
“Exit Delay Restart/reset” option allows use of the [] key to restart the exit delay at any time when the  
system is armed STAY or INSTANT. This feature also enables automatic exit delay reset, which resets  
exit delay if the entry/exit door is re-opened and closed before exit delay time expires after arming  
AWAY. Automatic Exit Delay Reset occurs only once during an armed period.  
IMPORTANT: AAV should not be used when Paging or Alarm Reports are sent to a secondary  
number unless the monitoring zone option is used (which pauses calls). Otherwise, the call to the  
secondary number by the communicator after the alarm report will prevent the AAV from taking  
control of the telephone line, and the AAV “Listen in” session cannot take place.  
U
L
UL installations using the AAV feature must use the ADEMCO UVCM module (part of  
the ADEMCO UVS system). Exit Delay Restart/Reset must be disabled.  
SIA Guidelines: Exit delay should be enabled.  
No. of Reports In Armed Period per Zone (Swinger Suppression)  
Select the number (0, 1, or 2) of alarm/alarm restore message pairs per zone allowed to be sent to the  
central station in an armed period. SIA Guidelines: Must be set for option 1 or 2.  
*93  
VISTA-10PSIA: Report Pairs: 1 = 1 report pair; 2 = 2 report pairs  
Unlimited Reports Enable:  
0 = restrict reports to the setting in entry 1  
1 = unlimited reports for zones listed in zone list 7; (use zone list 7 to list zones that require unlimited  
reporting; these zones ignore the setting in entry 1)  
Download Phone Number  
*94  
*95  
Enter the downloading computer phone number.  
Do not fill unused spaces. End field by entering . To clear entries from field, press 94.  
Ring Count For Downloading  
Refer to the chart below and program this field accordingly.  
phone  
answer  
down-  
module machine  
loading Set field 95 to…  
yes  
yes  
no  
yes  
no  
no  
1-14 (not 0)  
higher than number of rings set on answer machine (e.g., if ans. machine is 4  
rings, set this field to 5). This allows access to the phone module if the answer  
machine is turned off.  
1-14 (not 0)  
yes  
no  
yes  
no  
yes  
no  
yes  
yes  
yes  
no  
no  
yes  
yes  
yes  
no  
no  
no  
no  
15 (bypasses answer machine)  
0
0
1-14  
15  
NOTE: If “15” is entered to bypass an answering machine, and a 4285 or 4286 Phone Module is included in the system, note the  
following: When calling in from an off-premises phone, the user should make the initial call, allow 1 or 2 rings only, then hang up,  
then call again. The phone module will now seize the line, and 2 long tones sound, followed by the usual voice prompt for the access  
code. If this procedure is not followed, phone module operation will not be possible.  
4-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
FIELD  
TITLE and EXPLANATION  
Command to Initialize CSID and Subscriber Account Number  
This is a command function, not a data field. Use this command, if necessary, to reset all subscriber account  
numbers and the internal CSID to the factory default values.  
*96  
Command to Reset System to Factory Default Values  
This is a command function, not a data field. Pressing 97 resets all data fields to the factory default values  
(shown on the Program Form).  
*97  
IMPORTANT: Do not press 97 to load defaults if any programming has been done previously—data  
already programmed into the system will be changed!  
Command to Exit Program Mode (with installer code lockout)  
Exits Programming Mode and prevents re-entry by:  
*98  
Installer Code + [8] + [0] + [0]. To enter the programming mode if 98 was used to exit, you must first  
power the system down. Then power up again, and press [] and [#] at the same time, within 50 seconds  
of powering up.  
See field *88 for other Program mode lockout options.  
Command to Exit Program Mode  
Exits Programming Mode and allows re-entry by:  
*99  
Installer Code + [ 8] + [0] + [0] or by: Pressing [] and [#] at the same time, within 50 seconds of power-up.  
Pager Programming Fields  
FIELD  
TITLE and EXPLANATION  
Pager 1 Phone No.  
*160  
Enter the pager phone number. If you enter fewer than 20 digits, exit by pressing [] and next field  
number. To clear entries from this field, press 160.  
Pager 1 Characters  
*161  
Enter up to 16 optional characters, which may be sent as a prefix to the 7-digit system status code sent  
to Pager 1 (if used). Phone number in field *160 must be entered. If fewer than 16 characters, exit by  
pressing [] and next field number. To clear entries from this field, press 161.  
For example, these optional 16 characters may be composed of the following:  
paging company PIN number, subscriber account number, (enter # + 11 to send ), # (enter # + 12  
to send #), pause (enter # + 13 to allow a 2-second pause; some paging systems require pause)  
Any special character(s) the end user may decide to transmit  
The format for the 7-digit system status code is defined as follows:  
Pager Format: XXX-YYYY where:  
XXX  
= 3-digit event code: 911 = Alarm  
811 = Trouble  
101 = Opening (disarm)  
102 = Closing (arm AWAY)  
YYYY = 4-digit user or zone number (depending on type of event).  
The first digit is “1,” followed by the 3-digit user or zone number, or “0,” followed by a 3-digit  
device address number.  
Example 1. Pager displays: 9 1 1 1 0 0 4 : an alarm (911) caused by a fault in zone 4 (1004).  
Example 2. Pager displays: 1 0 2 1 0 0 5 : a closing–system arming (102) by User 5 (1005).  
Pager 1 Report Options  
Enter the types of reports to be sent to the pager.  
*162  
Open/close reports go to pager only when arming (close)/disarming (open) from a keypad using a  
security code; auto-arming/disarming, arming with assigned button, and keyswitch arming do not send  
pager messages.  
Miscellaneous System Fields  
Pager Delay Option for Alarms  
Enter the desired pager delay (none, 1, 2, or 3 minutes) for alarms. This delay applies to all pagers in  
*172  
the system.  
Device Duration 1, 2  
*177  
*181  
Enter the desired duration for output action options 5 (duration 1) and 6 (duration 2) programmed in  
80 Output Function Programming.  
50/60 Hz AC Operation  
Select the type of AC power applied to the control (option is used for Real-Time Clock synchronization).  
4-8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configurable Zone Type Programming Fields  
The system allows you to define a custom zone type, based on the options described below. This  
configurable zone types can be programmed via the downloader or from a keypad using data fields  
*182-*183 described below.  
UL installations: Do not configure zones as fire alarm or UL burglar alarm zones.  
FIELD  
TITLE and EXPLANATION  
Configurable Zone Type 90  
Enter the appropriate value for each entry, 1-10, based on the charts on the next page.  
*182  
To calculate the  
value for each entry, add the values of the selected options in each of the entry’s columns shown in the  
respective chart (one option per column). For example, to program entry 2 for “alarm response to  
short,” “auto restore on,” but not a “vent zone,” enter 5 (“1” for alarm short + “4” for auto restore-yes +  
“0” for vent zone-no).  
Zone Type 90 Report Codes  
Enter the desired 3-digit Contact ID® report codes for alarms and troubles occurring on zones assigned  
*183  
to this zone type.  
Press [] to accept and continue.  
Important Notice on Report Codes: To avoid confusion at the central station, it is recommended  
that existing Contact ID® codes be used with configurable zone types whenever possible. See list in  
System Communication section and/or check with the central station for a complete list of Contact  
ID® report codes. If none of the codes are suitable, choose a code in the reserved range of 750-789  
(reserved for configurable zone type report codes) and make sure to define the code with your central  
station.  
Configurable Zone Type Options  
Auto Restore (entry 2)  
Faults on zones set for this option are cleared; restore messages sent upon  
restoral of faults.  
Vent Zone (entry 2)  
Zones set for this option are ignored if faulted when arming the system, but are  
protected if the zone is later restored (e.g., an open window can be ignored when  
arming, but if the window is later closed, it will be protected; opening the  
window again causes an alarm.)  
Bypass Disarmed (entry 4) Zones set for this option can be bypassed only while the system is disarmed.  
Bypass Armed (entry 4)  
Zones set for this option can be bypassed when the system is armed or  
disarmed.  
Dial Delay (entry 6)  
Alarms on zones set for this option participate in dial delay central station  
reporting, if system dial delay enabled in field *50.  
Fault Delay (entry 6)  
Faults Display (entry 7)  
Faults on zones set for this option are delayed by the time set in field *87. Do  
not use this option if using entry/exit delay for this zone type.  
Selects how faults on zones set for this zone type are displayed.  
Power Reset/Verification Selects whether the system resets power (when user enters code + OFF), and  
(entry 7)  
whether the system performs alarm verification (see description for zone type  
16 in Programming Overview section) when a fault occurs on these zones.  
Use Entry Delay (entry 8) Selects whether to use the system’s entry delay times.  
Use Exit Delay (entry 8)  
Interior Type (entry 8)  
Selects whether to use the system’s exit delay time.  
Zones set for this option are treated same as standard zone type 4 (bypasses  
when armed STAY, faults displayed).  
Alarm Sounds (entry 9)  
Bell Timeout (entry 9)  
Selects the type of alarms sound for zones set for this zone type.  
Alarm sounding on zones set for this option remain for the duration set in fields  
*32/*33.  
Fire Zone (entry 9)  
Zones set for this option respond in the same manner as if programmed for zone  
type 9. Do not set fire zones to respond as a “fault” in entries 1-6.  
Trouble Sounds (entry 10) Selects the type of trouble sounds for zones set for this zone type (periodic beeps  
= once every 30 seconds; trouble beeps = rapid beeping).  
Chime Enable (entry 10)  
Zones set for this option cause a chime when Chime mode is on.  
4-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
Configurable Zone Type Charts  
ENTRY 1  
ENTRY 2  
Response when system disarmed and zone is:  
Auto  
Restore  
Vent Zone  
Intact EOL  
Open  
RF zone N/A  
Shorted  
RF zn off-normal  
RF zone normal  
INTACT  
EOL  
OPEN  
SHORTED  
0 = normal  
1 = alarm  
2 = trouble  
3 = fault  
0 = normal  
4 = alarm  
8 = trouble  
12 = fault  
see note 4  
0 = normal  
1 = alarm  
2 = trouble  
3 = fault  
0 = no  
4 = yes  
0 = no  
8 = yes  
ZONE-003-V0  
Zone Conditions Represented  
in Entries 1-6  
Entry 1 = EOL + Open  
Entry 2 = Short + auto restore + vent zone  
Configurable Zone Type Notes  
1. Do not use the “fault delay” option  
with a configurable zone type if it  
is set for an entry or exit delay,  
otherwise unpredictable results  
may occur.  
ENTRY 3  
Response when armed STAY and zone is:  
Intact EOL  
RF zone normal  
0 = normal  
1 = alarm  
2 = trouble  
3 = fault  
ENTRY 4  
Byp. when  
disarmed  
Byp. when  
armed  
Open  
Shorted  
RF zn off-normal  
0 = normal  
1 = alarm  
2 = trouble  
3 = fault  
RF zone N/A  
0 = normal  
4 = alarm  
8 = trouble  
12 = fault  
see note 4  
0 = no  
4 = yes  
0 = no  
8 = yes  
2. To create an interior type zone,  
select “respond as interior zone  
type” (entry 8, interior type = yes),  
and set zone response to “fault” in  
entries 3-4 to ensure fault  
Entry 3 = EOL + Open  
Entry 4 = Short + byp. disarmed + byp. armed  
displays; do not set as “normal,”  
“alarm,” or “trouble.”  
ENTRY 5  
ENTRY 6  
Response when armed AWAY and zone is:  
Dial Delay  
(see field *50) (see field *87)  
Fault Delay  
3. Do not set fire zones to respond as  
a “fault” (entries 1-6), otherwise  
faults will not display unless the  
[] key is pressed.  
Intact EOL  
RF zone normal  
Open  
RF zone N/A  
Shorted  
RF zn off-normal  
0 = normal  
1 = alarm  
2 = trouble  
3 = fault  
0 = normal  
4 = alarm  
8 = trouble  
12 = fault  
see note 4  
0 = normal  
1 = alarm  
2 = trouble  
3 = fault  
0 = no  
4 = use delay  
0 = no  
8 = use delay  
4. RF Zones: The “open” options in  
entries 1, 3, and 5 are not  
applicable for RF zones. Use the  
“intact EOL” option for normal RF  
zone conditions and “shorted” for  
off-normal RF zone conditions.  
see note 1  
Entry 5 = EOL + Open  
Entry 6 = Short + dial delay + fault delay  
ENTRY 7  
ENTRY 8  
Display Faults  
Power Reset/  
Verification  
Use Entry  
Delay 1/2  
Use Exit  
Delay  
Respond as  
Interior Type  
0 = show alarms 0 = no  
0 = no  
1 = delay 1  
2 = delay 2  
0 = no  
4 = use exit  
delay  
0 = no  
8 = yes  
when armed 4 = power reset  
& disarmed  
1 = dont show  
alarms when  
after fault  
(with code + OFF)  
12 = verification  
(see zone  
see note 2  
armed (show  
alarms, trbles,  
faults when  
type 16)  
disarmed)  
3 = never show  
any alarms,  
trbles, faults  
Entry 7 = fault display + power  
reset/verification  
Entry 8 = entry delay 1/entry delay 2 + exit delay +  
interior zone type  
ENTRY 9  
ENTRY 10  
Alarm Sounds  
Use Bell  
Timeout  
Respond as  
Fire Zone  
Trouble  
Sounds  
Chime when Chime  
Mode On  
0 = none  
1 = steady  
keypad  
2 = steady bell see fields *32,  
and keypad *33  
3 = pulsing bell  
0 = no  
4 = yes  
0 = no  
8 = yes  
0 = none  
1 = periodic  
beep  
2 = trouble  
beeps  
0 = no  
4 = yes  
see zone type  
09; see note 4  
and keypad  
Entry 9 = alarm sounds + bell timeout + fire zone  
Entry 10 = trouble sounds + chime  
4-10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Keypad Programming Fields  
NOTE: Each keypad must be assigned a unique address. Keypads programmed with the same  
address will give unpredictable results.  
Address 16 is reserved for keypad 1, which is automatically set with all sounds enabled.  
FIELD  
TITLE and EXPLANATION  
Keypad 2 Device Address 17  
Select whether or not this keypad is used, and enter the desired sound option for this keypad.  
*190  
Keypad 3 Device Address 18  
*191  
*192  
*193  
*194  
*195  
*196  
*197  
Select whether or not this keypad is used, and enter the desired sound option for this keypad.  
Keypad 4 Device Address 19  
Select whether or not this keypad is used, and enter the desired sound option for this keypad.  
Keypad 5 Device Address 20  
Select whether or not this keypad is used, and enter the desired sound option for this keypad.  
Keypad 6 Device Address 21  
Select whether or not this keypad is used, and enter the desired sound option for this keypad.  
Keypad 7 Device Address 22  
Select whether or not this keypad is used, and enter the desired sound option for this keypad.  
Keypad 8 Device Address 23  
Select whether or not this keypad is used, and enter the desired sound option for this keypad.  
Exit Time Display Interval  
Select whether or not keypads display the exit time remaining after arming the system, with display  
updates at the interval selected (i.e. if the exit delay is 30 seconds and “2” is selected in this field, the  
keypad display refreshes every 2 seconds, displaying 30, 28, 26, 24, etc.).  
An interval greater than “1” may be necessary for some older keypads to allow users time to enter key  
presses between display updates.  
FIXED-WORD KEYPAD NOTE: If using 2-digit display keypads (e.g. 6150RF), do not use exit times  
greater than the 96-second delay option. Using a longer delay time may cause end-user confusion  
because 2-digit display keypads cannot display times greater than “99.” If longer exit time is required  
by the installation, it is recommended that the Exit Time Display option be disabled (“0”).  
ECP Fail Display  
*199  
Select the 2-digit or 3-digit ECP Fail display, based on the type of keypads being used. The 3-digit  
display option displays ECP faults as “1” plus the device address (00-30) of the device causing the fault  
(e.g., faults on device 07 display as “107”), and is intended for Alpha keypads and/or 3-digit Fixed-Word  
Display keypads.  
The 2-digit Fixed-Word Display displays ECP faults for all devices as “91” on 2-digit displays, and  
“191” on 3-digit or Alpha keypads. It is intended for 2-digit display keypads (e.g., certain 6128 series  
keypads  
4-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
4-12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S E C T I O N  
5
Menu Mode Programming  
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •  
Zone Programming Overview (56 and 58 Menu Modes)  
Use 56 Zone Programming to program zones, zone types, report codes, enroll 5800 RF Wireless  
Transmitter serial numbers, and identify the type of loop input device(s). This mode can also be used  
to enter alpha descriptors for programmed zones; however, we recommend entering descriptors in  
menu mode 82 (Alpha Descriptor Programming) after all zone programming has been completed.  
58 Expert Programming Mode offers a faster method of zone programming for those who have had  
previous experience in programming control panels of this type.  
56 Zone Programming Procedure  
Zone Programming involves:  
1. Entering the zone number to be programmed;  
2. Making appropriate entries at the prompts;  
3. Confirming the serial number of wireless transmitter zones.  
Start Zone Programming mode by pressing 56 while in Data Programming mode. The following  
prompts are displayed:  
PROMPT  
VALID ENTRIES and EXPLANATION  
If 1 (Yes) is entered, you will be prompted to confirm each transmitter after entering the  
serial and loop numbers (at the “XMIT TO CONFIRM” prompt later in this procedure). We  
recommend that you confirm the programming of every transmitter.  
SET TO CONFIRM?  
0 = NO 1 = YES  
Enter the zone number that you wish to program (e.g. zone 10 as shown in the display).  
wired zones 01-06; wireless zones 09-24; button zones 49-56  
Enter a report code for zone 91 to enable addressable device reporting.  
Enter a report code for zone 92 to enable duress reporting.  
95, 96, 99 are emergency (panic) key zones.  
Enter Zn Num.  
(00 = Quit)  
10  
00 to quit; [] to continue  
A summary display appears.  
Zn ZT RC In:  
10 00 10 RF:  
L
1
“IN: L” appears for wireless zones and indicates input type and loop.  
“HW: RT” appears for hardwire zones and indicates configuration (EOL, NO, NC,) and  
response time selection.  
[] to continue  
Each zone must be assigned to a zone type (list below), which defines the way in which the  
system responds to faults in that zone.  
Note: If 00 is entered, Delete Zone ? will be displayed.  
10 Zone Type  
Perimeter  
03  
00 = Not used  
07 = 24-Hr Audible  
08 = 24-Hr Aux  
09 = Fire  
10 = Interior w/Delay  
12 = Monitor Zone  
20 = Arm–STAY*  
21 = Arm–AWAY*  
22 = Disarm*  
23 = No Alarm Resp  
24 = Silent Burglary  
01 = Entry/exit #1  
02 = Entry/exit #2  
03 = Perimeter  
04 = Interior Follower  
05 = Trouble Day/Alarm Night 14 = Carbon Monoxide 77 = Keyswitch  
06 = 24-Hr Silent  
*5800 button-type transmitters only  
16 = Fire w/Verify  
81 = AAV Monitor Zone  
90 = Configurable  
5-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
Enter the report code for this zone, which consists of 2 hexadecimal digits, each in turn  
consisting of 2 numerical digits. For example, for a report code of “10,” enter 01 and 00.  
10 Report Code  
1st 01 2nd 00 10  
®
For Contact ID , entering any non-zero entry as the first digit enables the report code for  
this zone. Refer to the System Communication section for information about report codes  
and formats.  
Report code digits: 1-9, #+10 for 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F  
00 to disable; [] to continue  
This prompt appears only for zone numbers 01-06.  
Enter the desired hardwire type:  
0 = EOL; 1 = NC; 2 = NO  
02 HARDWIRE TYPE  
EOL  
0
[] to continue  
This prompt appears only for hard-wired zones 01-06 (zone 02 is used as an example in  
display).  
Enter the desired response time for this zone:  
0 = 10mSec; 1 = 350mSec; 2 = 700mSec; 3 = 1.2 seconds  
[] to continue  
02 Response Time  
1
For wired zones 1-6, the Input Type automatically displays as HW and cannot be edited.  
All of the RF transmitters have one or more unique factory-assigned input loops (ID codes).  
Each of the input loops requires its own programming zone (e.g., a 5804's four button inputs  
require four programming zones). Select the desired input type for the transmitter zone  
being programmed.  
10 INPUT TYPE  
RF TRANS  
3
3 = RF (supervised RF transmitter; sends fault, restore, and low-battery signals, and sends  
periodic check-in signals; transmitter must stay within receiver's range)  
4 = UR (unsupervised RF transmitter; sends fault, restore, and low-battery signals, but  
does not send periodic check-in signals; transmitter may be carried off-premises)  
5 = BR (unsupervised button type RF transmitter; sends fault and low battery signals when  
activated, does not send restore or check-in signals; transmitter may be carried off-  
premises)  
[] to continue  
For wireless transmitters, enroll the serial number and loop number.  
1. a. Transmit two open/close sequences. If using a button-type transmitter, press and  
release the button twice, but wait about 4 seconds before pressing the button the  
second time.  
10 INPUT S/N:  
A022-4064  
L
1
OR  
b. Manually enter the 7-digit serial number printed on the label of the transmitter.  
Press the [] key to move to the “L” position, then enter the loop number (see Loop  
Identification chart on back cover).  
If desired, you can press the [C] key to copy the previously enrolled serial number  
(used when programming a transmitter with several input loops). The cursor moves to  
the loop number position.  
c. To delete an existing serial number, enter 0 in the loop number field. The serial  
number will change to 0's. If 0 was entered in error, simply re-enter the loop number or  
press [#], and the serial number will return to the display.  
2. Press [] to continue. The system now checks for a duplicate serial/loop number  
combination.  
If the serial/loop number combination is not a duplicate in the system, a display showing the  
serial number and loop number entry appears.  
[] to continue  
10 INPUT S/N  
A022-4064  
L
1
This prompt will only appear if you answered “Yes” at the “SET TO CONFIRM” prompt.  
The system now enters a confirmation mode so that the operation of the actual programmed  
input can be confirmed.  
XMIT TO CONFIRM  
PRESS TO SKIP  
Activate the loop input or button that corresponds to this zone.  
[] to continue  
5-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If the serial number transmitted does not match the serial number entered, a display  
similar to the one shown appears. If the loop number does not match, it will also be  
displayed.  
Entd A022-4063 1  
Rcvd A022-4064  
1
If so, activate the loop input or button on the transmitter once again. If a match is not  
obtained (i.e., summary display does not appear), press the [#] key twice and then enter (or  
transmit) the correct serial number.  
[] to continue  
If the serial number transmitted matches the serial number entered, the keypad will  
beep 3 times and a summary display will appear, showing that zone's programming.  
An “s” indicates that a transmitter’s serial number has been enrolled.  
[] to accept the zone information and continue  
Zn ZT RC In: L  
10 03 10 RF: 1s  
If you want to program descriptors for the zone now, enter 1 (yes) and refer to the *82  
Descriptor Programming section for procedures.  
To program descriptors later, enter 0 (no).  
PROGRAM ALPHA?  
0 = NO 1 = YES  
0
[] to continue  
If 0 (No) was entered at the Program Alpha prompt, the system will return you to the ZONE  
NUMBER prompt. Repeat these steps for each zone in the system.  
When all zones have been programmed, enter 00 as the zone number to quit.  
[] to continue  
ENTER ZN NUM.  
(00 = QUIT) 11  
Completing Zone Programming  
When you have finished programming all zones, test each zone using the system’s TEST mode. Do  
not use the Transmitter ID Sniffer Mode for checking wireless transmitting devices, as it  
will only check for transmission of one zone on a particular transmitter, NOT the zones assigned to  
each additional loop.  
NOTE: Following the successful enrollment of each wireless device, note the device serial number in  
the appropriate column on the ENROLLED TRANSMITTERS worksheet in the Programming Form;  
then enter the other information (zone number, zone type, loop number, etc.) relevant to that device.  
58 Expert Programming Mode Procedures  
This method is designed for use by installers with previous experience in programming ADEMCO  
control panels. This mode is also used to program wireless keys using pre-defined templates.  
Start Expert Programming mode by pressing 58 while in Data Programming mode. The following  
prompts are displayed:  
PROMPT  
VALID ENTRIES  
EXPLANATION  
We recommend that you select “yes” to confirm the programming of every transmitter.  
If selected, a prompt appears after entering the serial and loop numbers to confirm each  
transmitter)  
SET TO CONFIRM?  
0 = NO 1 = YES  
A summary screen will appear, showing zone 1’s currently programmed values.  
Enter the zone number being programmed, then press []. In this example, zone 10 is being  
entered  
Zn ZT RC HW: RT  
01 09 10 EL  
1
(see Zone Number prompt in *56 Menu Mode for zone numbers).  
[D] = for assigning wireless key programming templates (see Wireless Key Programming  
Templates section in i/i); lets you choose from a series of preset templates for easy  
programming of wireless key zones  
Zn ZT RC IN: L  
10 :  
00 = quit (when all zones have been programmed, press “00” to quit this menu mode)  
[] to continue  
5-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
A summary screen with the selected zone’s current programming appears.  
Begin programming zone information as follows:  
Enter Zone Type (ZT; see Zone Types listed in *56 Menu Mode “Zone Type” prompt), Report  
Code (RC), and Input Device Type (IN)* sequentially (Loop Number (L) is entered at the next  
prompt).  
Zn ZT RC IN: L  
10 00 10 RF 1  
Use the [A] (Advance) and [B] (Back) keys on the keypad to move the cursor within the  
screen.  
Use the [C] key to copy the previous zone’s attributes.  
* If HW (hardwired) or AW (Auxiliary) is entered for Input Device Type, the display will be  
similar to the prompt shown, except that HW or AW will be under “IN”.  
Press [] to save the programming and continue. If needed, press the [#] key to back up  
without saving.  
For wireless devices (input types RF, UR, BR), continue to the serial number/loop number  
prompt.  
For wired devices, return to the initial summary screen prompt to begin programming the  
next zone.  
Manually enter the serial number (found on the transmitter label), by typing digits in the  
“X” locations, using the [A] (advance) or [B] (back) keys as required.  
OR  
10 INPUT S/N:  
AXXX-XXX  
L
Transmit two open/close sequences. If using a button-type transmitter, press and release the  
button twice, but wait about 4 seconds before pressing the button the second time.  
If you want to copy the previous zone’s serial number, press the [C] key.  
Press [] to advance to the loop number, then enter loop number.  
Press [] to accept the existing serial and loop number and continue to the “Confirm” prompt  
described in *56 Menu mode above.  
Zn ZT P RC In  
L
10 03 1 10 RF:1s  
If necessary, press [#] to back up and re-enter or edit the serial number.  
If the serial number transmitted matches the serial number entered, the keypad will beep 3  
times and a summary display will appear, showing the programmed information for that  
zone.  
Press [] to begin programming the next zone. See first “Summary Screen” prompt  
paragraph.  
Wireless Key Programming Templates  
This procedure programs the wireless keys, but a key is not active for arming/disarming until  
it is assigned to a user number (see System Operation section, assigning attributes command).  
Enter this mode by pressing the D key while at the *58 Menu mode Summary Screen. The following  
prompts appear.  
Enter desired template number 1–6 (see chart).  
Press [#] if you want to return to *58 Menu mode Summary Screen.  
If necessary, press [#] to back up and re-enter template number.  
TEMPLATE ?  
16  
1
Press [] to continue to template display.  
The selected template is displayed.  
Top line of display represents loop numbers, bottom line represents zone type assigned for  
L
T
01 02 03 04  
23 22 21 23  
each loop.  
Press [] to accept template and continue.  
The system will search for the highest available consecutive 4-zone group (the four zones in  
the case of the 5804 and 5804BD), and display the lowest zone number of the group.  
If you want to start at a different zone, enter the zone desired, and press []. If that zone  
number is displayed, the system has the required number of consecutive zones available,  
beginning with the zone you entered. If not, the system will again display a suggested zone  
that can be used.  
ENTER START ZONE  
00 = QUIT 36  
If the required number of consecutive zones is not available at all, the system will display  
“00”.  
To quit this mode and return to *58 Menu mode, enter 00 at this prompt.  
Press [] to accept and continue.  
5-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Manually enter the serial number printed on the label for the wireless key or press and  
release the button to transmit its serial number.  
Press [] to accept the serial number. The system will check for duplicate.  
If necessary, press the [#] key to back up without saving, and re-enter the serial number.  
Use the [A] key to move forward within the screen, and the [B] key to move backward.  
INPUT S/N  
L
AXXX-XXXX  
If “Yes” was entered at the SET TO CONFIRM? prompt (first prompt following entry into  
the 58 Expert Programming Mode), this display appears.  
Confirm serial and loop numbers by activating the wireless key. Refer to the “Confirm”  
prompt described in *56 Menu mode above for more information on confirming the serial  
number.  
XMIT TO CONFIRM  
PRESS TO SKIP  
If the serial number transmitted matches the serial number entered, the keypad will beep 3  
times and will return you to the ENTER START ZONE NUMBER prompt to enter the  
starting zone for the next wireless key.  
Or you can return to *58 Menu mode by pressing 00 at the Zone Number prompt.  
IMPORTANT: When confirmed, the key is not active for arming/disarming until it is  
assigned to a user number (using the assigning attributes command, attribute “4”). See  
System Operation section.  
[] to skip confirm.  
Wireless Key Predefined Default Templates  
LOOP 3  
GREEN/YELLOW  
LED  
LOOP 2  
YOU MUST  
PROGRAM  
THIS BUTTON  
LOOP 4  
OFF  
LOOP 2  
LOOP 1  
ON  
Note:  
RED/YELLOW  
LED  
LOOP 4  
(YOU MUST  
PROGRAM  
These transmitters  
are not intended for  
use in UL  
THIS BUTTON)  
LOOP 3  
installations.  
LOOP 1  
• •  
• •  
ENROLL AS "BR"  
ENROLL AS "BR"  
5804BD-007-V0  
5804-001-V1  
5804BD 2-Way Wireless Key Transmitter  
For 5804BD  
5804 Wireless Key Transmitter  
For 5804  
TEMPLATE 1 Loop Function  
No Response  
Disarm  
Zone Type  
23  
22  
TEMPLATE 4 Loop  
Function  
Zone Type  
1
2
1
2
3
4
No Response  
No Response  
Arm Away  
Disarm  
23  
23  
21  
22  
3
4
Arm Away  
21  
No Response  
23  
TEMPLATE 2 Loop Function  
Zone Type  
23  
22  
21  
TEMPLATE 5 Loop  
Function  
No Response  
Arm Stay  
Arm Away  
Disarm  
Zone Type  
23  
20  
21  
1
2
3
4
No Response  
Disarm  
Arm Away  
Arm Stay  
1
2
3
4
20  
22  
TEMPLATE 3 Loop Function  
Zone Type  
7
22  
21  
20  
TEMPLATE 6 Loop  
Function  
24-hour audible  
Arm Stay  
Arm Away  
Disarm  
Zone Type  
7
20  
21  
22  
1
2
3
4
24-hour audible  
Disarm  
Arm Away  
Arm Stay  
1
2
3
4
5-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
Output Device Programming Overview (*79/*80 Menu Mode)  
Output Devices:  
The system supports up to 4 relays plus 2 built-in trigger outputs. These  
“output devices” are assigned to system-wide output numbers (01-04, 17, 18).  
Relays are identified by the relay module’s device address and the relay position on  
the module (i.e. the physical relay number, 1-4, on the module). Built-in triggers are  
identified by the output number, 17 for Trigger 1 and/or 18 for Trigger 2.Use *79  
Menu Mode to assign output numbers and map them to device addresses.  
Output Functions: The system also provides up to 12 installer-defined output functions, which can  
be assigned to any of the physical outputs. Therefore, the action of any one of the  
outputs can be based on as many of these functions as desired. This lets a single  
relay perform many functions. Use *80 Menu Mode to define output functions.  
Relays are not recommended for life safety applications.  
MENU NAVIGATION NOTE: For *79 and *80 menus, press the [ ] key to accept an entry and  
advance to the next prompt. Use the [#] key to go back to the last question if needed (to check or  
change an entry). Press [ ] to go forward again.  
Output Device programming involves:  
1. Use *79 Menu Mode to assign module and output numbers and map them to device addresses.  
NOTE: You must map output devices using *79 Menu Mode before you can use *80 menu Mode.  
2. Use *80 Menu Mode to create output definitions, which control the output devices.  
*79 Menu Mode: Output Device Mapping  
Use this menu to assign the Relay Module device address and specific relay numbers. The system is  
based on predefined module addresses. The address for the 4204 is 12. Refer to the “Module Address”  
prompt on the next page and set the module’s address (via module DIP switches) accordingly.  
Start Output Device Mapping by pressing *79 while in Data Programming Mode. The following  
prompts are displayed:  
79 Menu Mode  
PROMPT  
VALID ENTRIES and EXPLANATION  
Enter the logical (or reference) relay number as used in the system.  
01-04 = relays; 17-18 = on-board triggers (can be programmed for inverted output; see next  
ENTER OUTPUT NO.  
00 = QUIT  
xx  
prompt).  
Use the worksheet on the Programming Form (printed separately) to organize device  
numbers.  
[] to continue  
This prompt appears only for Triggers 17 and 18.  
17 OUT NORM LOW  
0 = NO 1 = YES  
0 = no (standard default); sets the trigger output level normally high  
1 = yes; sets the trigger output normally low (can be used for resetting 4-wire smoke  
detectors by connecting trigger wire to the negative power terminal of the smoke detector,  
selecting 1 at this prompt, and setting as zone type 54, fire zone reset, in *80 Menu  
mode)  
0
[] to return to Output Number prompt (use *80 Menu mode to program the function of the  
trigger)  
Enable or delete this output.  
0 = delete this output number; 1 = enable output  
[] to continue  
XX OUTPUT TYPE  
DELETE?  
0
Enter the module’s predefined address “12” (set the module’s DIP switches to “12”).  
[] to continue  
XX MODULE ADDR  
07-15  
yy  
zz  
Enter the actual (or physical) relay number, 1-4, with respect to the Relay Module upon  
which it is located.  
XX REL POSITION  
1-4  
[] to return to the Output Number prompt for programming the next device  
5-6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
*80 Menu Mode: Defining Output Functions  
Use this mode to program output function definitions (up to 12 functions) that provide automated  
control of any of the output devices, based on events occurring on individual zones or zones with  
Each output definition is identified by an output function number, and includes  
certain zone types.  
the following components:  
Output Definition Components  
Component  
Description  
Output Function No. A reference number that defines an output’s characteristics.  
Activated By  
Event  
Determines whether the initiating event occurs on a zone, a zone list, or a zone type.  
Event that triggers the output action. Can be an event occurring on a specific zone  
number or a zone list, or a specific zone type.  
Output Action  
Output No.  
Defines the action of the relay when the defined event occurs. Can close for 2 seconds,  
stay closed until reset, continuously pulse (1-second close-open-close-open, etc.), toggle  
the device state, or activate for a defined duration (set in data field *177).  
Assigns this function to a specific output number (defined in *79 Menu Mode). This is  
the output number that will perform this function upon the triggering event. Note that  
each defined function is associated with only one output number. This means that if  
more than one output device needs to perform this particular function, you need to  
define another output function number with the same attributes, but assign the  
appropriate output number. (i.e. output devices can be assigned more than one function  
number, but each function number can only be assigned a single output number.  
For example, if you want to pulse a strobe light upon fire alarms on zone 4 using a relay mapped to  
output number 2 (as programmed in *79 Menu Mode), program the following in *80 Menu Mode:  
Prompt  
Entry  
Output Funct. # = 01 (assuming this is the first output function)  
Activated By:  
Enter Zn No.  
Output Action  
= 3 (zone number)  
= 04 (requires 2-digit zone numbers)  
= 3 (continuous pulse)  
Output Number = 02 (device mapped in *79 Menu Mode)  
Start Output Definition mode by pressing ✱  
80 while in Data Programming mode.  
80 Menu Mode  
PROMPT  
VALID ENTRIES and EXPLANATION  
Enter the output function number to be defined  
01-12 = output function number  
Output Funct. #  
(00 = Quit)  
01  
Trig  
[] to continue; 00 = exit  
This screen displays a summary of the current output programming  
A = Output Action; E = Triggering event; Trig = Trigger type  
Question mark indicates the device shown has not been mapped. Use *79 Menu mode to  
map the device.  
01 A E  
?00 0 0 ZL=00  
[] to continue  
Select where the initiating event for this output definition is to occur.  
0 = delete (deletes the output function and any previous programming)  
01 Activated By:  
Zone List  
Delete?  
To delete this output definition, press 1.  
0 = NO, 1 = YES  
If you do not want to delete this output,. press 0.  
1 = zone list (go to “A” prompt); 2 = zone type (go to “B” prompt); 3 = zone number (go to “C”  
prompt)  
[] to continue  
5-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
A”  
If zone list was selected, this screen appears. Otherwise skip to the next prompt.  
Enter the desired zone list number associated with this output number:  
01-08 = zone list (Do not use pager zone list 09 in output definitions)  
Enter the zone list event that will activate this output:  
01 Zn List  
1
Enter Event  
Alarm  
0 = restore; 1 = alarm;  
2 = fault; 3= trouble  
1
NOTE: For alarm, fault, and trouble, an event on ANY zone in the list activates the output,  
but ALL zones in the list must be restored before the output is restored.  
Press [] to continue and skip to the “Output Action” prompt.  
B”  
If zone type was selected, this screen appears. Otherwise skip to the next prompt.  
Enter the desired zone type for this output number.  
CHOICES FOR ZONE TYPES:  
01 Enter Zn type  
Perimeter  
03  
00 = Not Used  
01 = Ent/Exit #1  
02 = Ent/Exit #2  
03 = Perimeter  
04 = Interior Follower 09 = Fire  
10 = Interior w/Delay  
05 = Trouble Day/Alarm Night 12 = Monitor Zone  
06 = 24 Hr Silent  
07 = 24 Hr Audible  
08 = 24 Hr Aux  
14 = Carbon Monoxide  
16 = Fire w/verification  
23 = No Alarm Response  
24 = Silent Burglary  
77 = Keyswitch Zone  
81 = AAV Monitor Zone  
90 = Configurable  
CHOICES FOR SYSTEM OPERATION:  
20 = ArmingStay  
21 = ArmingAway  
22 = Disarming  
36 = At Bell Timeout***  
38 = Chime  
52 = Kissoff  
54 = Fire Zone Reset  
58 = Duress  
39 = Any Fire Alarm  
40 = Bypassing  
31 = End of Exit Time  
60 = AAV  
32 = Start of Entry Time 41 = AC Power Failure  
33 = Any Burglary Alarm 42 = System Battery Low  
43 = Comm. Failure  
66 = Function Key†  
67 = Bell Fail  
68 = Telco line cut  
78 = Keyswitch Red LED  
79 = Keyswitch Green LED  
*** Or at Disarming, whichever occurs earlier.  
Use *57 Menu Mode to assign the function key (function “07”).  
Note: In normal operation mode:  
Code + # + 7 + NN Key Entry starts Device NN.  
Code + # + 8 + NN Key Entry stops Device NN.  
Press [] to continue and skip to the Output Actionprompt.  
C”  
If zone number was selected, this screen appears.  
Enter the desired zone number associated with this output number.  
Press [] to continue.  
01 Enter Zn No.  
12  
Enter the zone event that will activate this output.  
01 Enter Event  
Restore  
0 = restore; 1 = alarm/fault/trouble  
0
Press [] to continue to the “Output Action” prompt  
Enter the desired device action as listed below.  
01 Output Action  
Close for 2 sec  
0 = off  
4 = Change Device State  
5 = Duration 1 (see data field *177)  
6 = Duration 2 (see data field *177)  
1
1 = Close for 2 seconds  
2 = Stay Closed  
3 = Pulse 1 sec ON, 1 sec OFF  
Press [] to continue.  
Enter the device output number (programmed in *79 Menu Mode) you want associated with  
this output.  
01-04 = output no.  
17-18 = on-board triggers  
Press [] to continue.  
Enter Output No.  
R02  
02  
A summary screen appears showing the programmed settings.  
02 A E P TRIG  
R02 1 1 3 ZL=00  
Press [] to return to output function number prompt.  
5-8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Zone List Overview (81 Menu Mode)  
Zone lists let you group individual zones for use with certain system actions. The following table  
shows the available zone lists and their purposes:  
List No. Used for…  
1, 2  
3
4
general purpose  
chime-by-zone  
cross zones  
5
night stay zones  
6
general purpose  
VISTA-10PSIA: dial delay disable  
general purpose  
7
VISTA-10PSIA: unlimited reports  
8
9
general purpose  
zones that activate Pager 1  
Zone List Programming  
Zone List programming involves:  
1. Selecting an appropriate zone list number;  
2. Adding the desired zone numbers to be included in that list.  
Start Zone List Program Mode by pressing while in Data Programming mode. The following  
81  
prompts are displayed  
:
*81 Menu Mode  
PROMPT  
VALID ENTRIES  
EXPLANATION  
Enter the Zone List Number to program (or 00 to end these entries).  
01-09 = zone list number  
[] to continue  
Zone List No.  
(00 = Quit)  
01  
Enter each zone number followed by [] to add each zone to the zone list.  
01-06 = wired zones; 09-24 = wireless zones; 49-56 = button zones  
91 = addr. device report enable (Enter a report code for zone 91 to enable addressable device  
reporting.  
01 Enter Zn Num.  
(00 = Quit)  
00  
92 = duress report enable (Enter a report code for zone 92 to enable duress reporting)  
95, 96, 99 =emergency zones  
00 to continue  
IMPORTANT: Do not include fire zones in zone lists that are used to STOP device actions.  
To delete the zone list, enter 1. All zones in the zone list will be deleted automatically and  
the system returns to the Zone List No. prompt.  
To save the zone list, enter 0.  
01 Del Zn List?  
0 = No 1 = Yes  
0
[] to continue  
To save the entire zone list, enter 0 and the system returns to the Zone List No. prompt.  
To delete a zone or zones in a zone list enter 1 to continue.  
[] to continue  
01 Delete Zone?  
0 = No 1 = Yes  
0
Enter each zone to be deleted from the list followed by [] to accept each zone.  
01-64 = zones to be deleted from list  
00 when done to return to the Zone List No. prompt  
01 Zn to Delete?  
(00 = Quit)  
00  
NOTES:  
Any list may include any or all of the system's zone numbers.  
A zone list can be assigned to more than one output relay.  
When creating zone list 4 for cross zoning, include only zones assigned to zone types 3, 4, or 5. Do  
not include zones that have delays (entry/exit zones, interior w/delay) or 24-hour zones, as these  
zone types may produce unpredictable operation and may not function as intended. See field *85 for  
Cross Zone Timer option.  
Zone List 6: VISTA-10PSIA: See field *50 for Dial Delay Disable option.  
Zone List 7: VISTA-10PSIA: See field *93 for Unlimited Reports option.  
5-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
Function Key Programming Overview (57 Menu Mode)  
The system provides the ability to program each of the four keypad function keys to perform one of 12  
system operations. The end user can then activate the function by simply pressing and holding the  
programmed key for 2 seconds. Typical functions (listed below) include single-button arming, turning  
lights on/off, or single-button paging.  
Programming Function Keys  
Function key programming involves:  
1. Assigning the function key number;  
2. Selecting the desired function for that key.  
Start Function Key Programming mode by pressing 57 while in Data Programming mode. The  
following prompts are displayed:  
PROMPT  
VALID ENTRIES  
EXPLANATION  
Press the desired function key, A-D.  
NOTE: A key programmed as a function key  
is no longer available to be used as an end-  
user macro key or panic key.  
OFF  
AWAY  
TEST  
CODE  
STAY  
A
B
C
D
1
4
7
2
5
8
0
3
6
9
#
Press Key to Pgm  
0 = Quit  
0
BYPASS  
CHECK  
MAX  
INSTANT  
[] to continue  
READY  
*
Enter the desired function for this key:  
Key "A" Func  
00 = For the Function key selected, the function will be as follows (system default):  
If A selected = Zone 95 (emergency key, same as [1] [] pair)  
If B selected = Zone 99 (emergency key, same as [] [#] pair)  
If C selected = Zone 96 (emergency key, same as [3] [#] pair)  
If D selected = Single-button paging  
Zone 95  
00  
01 = Single-button paging (sends a 999-9999 message to pager)  
02 = Display time  
03 = Arm AWAY (reports as User 00 if closing reports are enabled)  
04 = Arm STAY (reports as User 00 if closing reports are enabled)  
05 = Arm NIGHT-STAY (reports as User 00 if closing reports enabled)  
06 = Step Arming (arms STAY, then NIGHT-STAY, then AWAY)  
07 = Output Device Command (for device programmed as system operation type 66 in *80  
Menu Mode)  
08 = Communication Test (sends Contact ID code 601)  
09= Macro Key (defined by [#] [6] [6] command)  
[] to continue; returns to key number prompt with the next function key letter displayed.  
† If Night-Stay zones are listed in zone list 5  
5-10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
About Descriptor Programming Overview (82 Menu Mode)  
The system lets you assign zone descriptors for protection zones, keypad panics, and RF receiver  
supervision faults. Each description can be composed of a combination of words (up to 3) selected  
from a vocabulary of 196 words stored in memory (see a following page). In addition, up to 10  
installer-defined words can be added to those already in memory. Thus, when an alarm or trouble  
occurs in a zone, an appropriate description for that zone's location can be displayed at the keypad.  
Zone descriptors are recommended for systems using Alpha display keypads, and are necessary if a  
Phone Module is used.  
NOTE: You can enter zone descriptors when the zone is being defined in 56 Menu mode, but we  
recommend you do it using 82 Menu mode.  
If using a 4285 or 4286VIP Phone Module, select from those words in the Alpha Vocabulary List  
shown in boldface type. The phone module will not provide annunciation of the other words.  
If a 4285/4286 Phone Module is added to an existing system, the Alpha descriptors presently in  
the system should be reprogrammed, selecting from those words shown in boldface type in the  
Alpha Vocabulary List. The phone module will not provide annunciation of any other words.  
Programming Zone Descriptors (Menu mode 82)  
Descriptor programming involves:  
1. Entering index numbers for up to three words from the vocabulary list for each descriptor;  
2. Entering up to ten 10-digit custom words, if desired, which can then be used in descriptors.  
When defining descriptors:  
Pressing the [6] key accepts the entered index number and moves the cursor to the next position.  
Pressing the [8] key saves the entered descriptor and moves to the next descriptor.  
Start Zone Descriptor Programming mode by pressing *82 while in Data Programming mode.  
PROMPT  
VALID ENTRIES and EXPLANATION  
Press 1 to program descriptors.  
0 = exit this mode  
Program Alpha ?  
0=No, 1=Yes  
0
To program standard alpha descriptors from the fixed vocabulary, press 0. The system will  
then automatically display the descriptor for zone 1.  
To define custom words (described below in “Adding Custom Words” section), press 1.  
Custom Words ?  
0=No, 1=Yes 00  
Summary screen of zone 1 descriptor (if programmed) is displayed.  
Press [] to start blinking cursor at zone number, then enter the zone number for which the  
descriptor is being programmed.  
ZN 01  
If a descriptor is programmed for that zone, it is displayed.  
To delete or change a previously programmed descriptor, press [] plus the same zone  
number. This will clear that descriptor and move the cursor to the first word position.  
If you do not wish to change the existing descriptor, enter [] plus the next zone number  
for which you wish to enter (or check) a descriptor. A summary display for that zone will  
appear. You must then press [] plus the same zone number again to program a descriptor  
for that zone.  
If no descriptor has been programmed for that zone, the cursor moves to first word  
position.  
Select first word of descriptor:  
Press [#] plus the 3-digit index number for the first word from the Alpha Vocabulary List. See  
index for entries.  
ZN 01  
Example: The descriptor that we wish to enter for zone 1 is BACK DOOR. From the list,  
BACK = 013. Therefore, you would enter #013.  
If you enter the wrong word, simply press [#] plus the 3-digit number for the desired word.  
Save first word of descriptor:  
ZN 01 BACK  
6 = save word and go to next word in this descriptor  
8 = save word and end descriptor if this is the only word used for the descriptor - go to  
summary screen  
5-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
Enter the 3-digit number for the next word. In the example, the word is DOOR, whose  
number is “057.”  
See index for entries.  
ZN 01 BACK  
D OOR  
[] to continue  
Save second word of descriptor:  
6 = save word and go to next word in this descriptor  
8 = save word and end descriptor if this is the only word of the descriptor - go to summary  
screen  
ZN 01 BACK  
DOOR  
The two words in the example have now been entered. Note, however, that up to three words  
may be entered (provided the number of characters will fit on the screen).  
Summary Screen  
ZN 01 BACK  
The blinking cursor will disappear, indicating that the word(s) are saved in memory.  
To enter a descriptor for the next zone, press [] plus the desired zone number (e.g., 02).  
The summary display for that zone will appear.  
DOOR  
Repeat the previous steps to enter the descriptor for the next zone.  
To exit the Alpha descriptor mode, enter zone “00” at the summary display, which returns  
you to the Program Alpha prompt. Enter “0” at that prompt to exit.  
Adding Custom Words (will not be annunciated by 4285/4286 Phone Module)  
You can add up to 10 installer-defined words to the built-in vocabulary, which can then be used  
when programming zone descriptors. Each of the 10 words can actually consist of a word string of  
one or more words, but no more than ten characters can be used for each word or word string.  
PROMPT  
VALID ENTRIES and EXPLANATION  
The “Program Alpha ?” prompt will appear.  
1 = program zone descriptors, custom message, or reminder words; 0 = exit  
[] to continue  
Program Alpha ?  
0=No, 1=Yes 00  
Custom words let you assign custom zone descriptors, a custom message (replaces  
“DISARMED READY TO ARM”), and “reminder” words (for Scheduling mode, event “10”).  
NOTE: Do not assign reminder words if using fixed-word keypads.  
1 = yes, program custom words or reminder words  
Custom Words ?  
0=No, 1=Yes  
0
0 = no, go to zone descriptors (see above)  
If “1” selected, enter the 2-digit custom word number (01-10) to be programmed,  
corresponding to index numbers 245 - 254 respectively (for example, if you are creating the  
first custom word or word-string, enter 01, for the second, enter 02, etc.). A cursor will now  
appear at the beginning of the second line.  
Custom?  
00  
08-10 = “reminder” words used with scheduling mode  
11 = custom message (replaces “DISARMED READY TO ARM” message)  
A cursor appears at the beginning of the second line.  
Special Keys:[6] = accept character and move cursor to next position to right  
[4] = move cursor to left  
Custom?  
01  
[8] = save custom word  
1. Refer to the Character Chart.  
Press [#], followed by the two-digit entry for the first letter you want to display (e.g., # 6  
5 for “A”).  
Press [6] to accept the character and move the cursor to the right, in position for the  
next character. To delete a character, enter the SPACE character (#32).  
2. Repeat Step 1 to enter the next characters until the desired custom word is entered. You  
can use the [4] key to move the cursor to the left, if necessary.  
Each custom word can be a maximum of 10 characters.  
3. When done, press the [8] key to save the custom word and return to the “Custom ?”  
prompt.  
4. Repeat steps 1-3 to enter other custom words. To change a custom word, simply  
overwrite it.  
To exit, enter “00,” which returns you to the Program Alpha prompt. Enter “0” at that  
prompt to exit.  
Once Custom words are programmed they can be used in a descriptor in the same way the  
built-in vocabulary words are used.  
5-12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ALPHA VOCABULARY LIST  
(For Entering Zone Descriptors)  
108 LEVEL  
000 (Word Space)  
• 059 DOWN  
• 219 WING  
220 WIRELESS  
– X –  
222 XMITTER  
– Y –  
223 YARD  
– Z –  
• 162 ROOM ∗  
163 ROOF  
• 060 DOWNSTAIRS  
061 DRAWER  
• 062 DRIVEWAY  
• 064 DUCT  
– E –  
• 065 EAST  
066 ELECTRIC  
067 EMERGENCY  
068 ENTRY  
• 069 EQUIPMENT  
• 071 EXIT ∗  
072 EXTERIOR  
– F –  
• 073 FACTORY  
075 FAMILY  
• 076 FATHERS  
• 077 FENCE  
• 079 FIRE ∗  
• 080 FLOOR ∗  
081 FLOW  
• 109 LIBRARY ∗  
• 110 LIGHT  
111 LINE  
• 113 LIVING ∗  
• 114 LOADING  
115 LOCK  
116 LOOP  
117 LOW  
• 118 LOWER  
– A –  
• 001 AIR  
• 002 ALARM ∗  
004 ALLEY  
005 AMBUSH  
• 006 AREA  
• 007 APARTMENT  
• 009 ATTIC ∗  
010 AUDIO  
– S –  
164 SAFE  
165 SCREEN  
166 SENSOR  
• 167 SERVICE  
• 168 SHED ∗  
169 SHOCK  
• 170 SHOP ∗  
171 SHORT  
• 173 SIDE ∗  
174 SKYLIGHT  
175 SLIDING ∗  
• 176 SMOKE ∗  
• 178 SONS  
• 179 SOUTH  
180 SPRINKLER  
• 182 STATION  
184 STORE  
• 185 STORAGE ∗  
186 STORY  
190 SUPERVISED  
224 ZONE (No.)  
• 225 ZONE ∗  
• 226  
• 227  
0
1
– M –  
• 119 MACHINE  
121 MAIDS  
– B –  
• 228 1ST ∗  
• 229  
• 230 2ND ∗  
• 231  
• 232 3RD ∗  
• 233  
• 234 4TH  
• 235  
• 236 5TH  
• 237  
• 238 6TH  
• 239  
• 240 7TH  
• 241  
• 242 8TH  
• 243  
• 012 BABY ∗  
• 013 BACK ∗  
• 014 BAR  
• 016 BASEMENT ∗  
• 017 BATHROOM ∗  
• 018 BED  
• 019 BEDROOM ∗  
020 BELL  
• 021 BLOWER  
• 022 BOILER  
023 BOTTOM  
025 BREAK  
2
122 MAIN ∗  
• 123 MASTER ∗  
• 125 MEDICAL ∗  
126 MEDICINE  
128 MONEY  
129 MONITOR  
• 130 MOTHERS  
• 131 MOTION ∗  
132 MOTOR  
– N –  
• 134 NORTH  
135 NURSERY  
– O –  
• 136 OFFICE ∗  
• 138 OPEN ∗  
139 OPENING  
• 140 OUTSIDE  
142 OVERHEAD  
– P –  
3
4
5
6
082 FOIL  
7
• 083 FOYER  
084 FREEZER  
• 085 FRONT ∗  
– G –  
• 089 GARAGE ∗  
• 090 GAS  
091 GATE  
• 026 BUILDING  
191 SUPERVISION  
192 SWIMMING  
193 SWITCH  
– T –  
194 TAMPER  
196 TELCO  
8
– C –  
028 CABINET  
• 029 CALL  
030 CAMERA  
031 CAR  
033 CASH  
034 CCTV  
9
• 244 9TH  
245 Custom Word #1  
246 Custom Word #2  
247 Custom Word #3  
248 Custom Word #4  
249 Custom Word #5  
250 Custom Word #6  
251 Custom Word #7  
252 Custom Word #8  
253 Custom Word #9  
254 Custom Word #10  
197 TELEPHONE  
• 199  
• 092 GLASS  
093 GUEST  
094 GUN  
035 CEILING  
036 CELLAR  
• 037 CENTRAL  
038 CIRCUIT  
• 040 CLOSED ∗  
• 046 COMPUTER  
047 CONTACT  
– D –  
• 048 DAUGHTERS  
049 DELAYED  
• 050 DEN ∗  
051 DESK  
• 052 DETECTOR ∗  
• 053 DINING ∗  
054  
DISCRIMINATOR  
055 DISPLAY  
• 057 DOOR ∗  
TEMPERATURE  
200 THERMOSTAT  
• 201 TOOL  
202 TRANSMITTER  
– U –  
143 PAINTING  
• 144 PANIC ∗  
145 PASSIVE  
• 146 PATIO ∗  
147 PERIMETER  
• 148 PHONE  
150 POINT  
151 POLICE ∗  
152 POOL ∗  
• 153 POWER  
– R –  
H –  
• 095 HALL ∗  
• 096 HEAT  
098 HOLDUP  
099 HOUSE  
100 INFRARED  
• 101 INSIDE ∗  
102 INTERIOR  
103 INTRUSION  
– J –  
• 205 UP  
• 206 UPPER  
• 207 UPSTAIRS ∗  
• 208 UTILITY ∗  
– V –  
209 VALVE  
210 VAULT  
212 VOLTAGE  
– W –  
213 WALL  
214 WAREHOUSE  
• 216 WEST  
• 217 WINDOW ∗  
NOTE: Custom words  
8, 9, 10 are reminder  
wordsthat can be  
programmed to display  
using Scheduling  
Mode.  
104 JEWELRY  
– K –  
• 105 KITCHEN ∗  
155 RADIO  
• 156 REAR  
157 RECREATION  
159  
REFRIGERATION  
160 RF  
L –  
• 106 LAUNDRY ∗  
• 161 RIGHT  
• 107 LEFT  
Note: Bulleted () words in boldface type are those that are also available for use by the 4285/4286 Phone Module. If using  
a phone module, and words other than these are selected for Alpha descriptors, the phone module will not provide  
annunciation of those words.  
Italicized words followed by an asterisk indicate those words supported by the 6160V/6150V Voice Keypads  
–––––––––––––––––––––––––––– CHARACTER (ASCII) CHART ––––––––––––––––––––––––––––  
(For Adding Custom Words)  
32 (space)  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
*
+
,
.
/
0
1
2
3
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
4
5
6
7
8
9
:
;
<
=
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
>
?
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
H
I
J
K
L
M
N
O
P
Q
82  
83  
84  
85  
86  
87  
88  
89  
90  
R
S
T
U
V
W
X
Y
Z
33  
34  
35  
36  
37  
38  
39  
40  
41  
!
#
$
%
&
'
@
A
B
C
D
E
F
(
)
G
5-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
Programming Installer and User Schedules  
The system provides 2 schedules (one for the installer, one for the end user), which can be used to  
control 11 types of system events at pre-defined times.  
Start Scheduling mode by entering installer code + [#] + [6] [4] while in normal operating mode.  
NOTE: The master code can only access schedules 01 and events 00-07.  
PROMPT  
VALID ENTRIES and EXPLANATION  
Enter the desired schedule number.  
01 = end-user schedule; 02 = installer-only schedule; 00 = exit scheduling mode  
ENTER SCHED NO.  
00=QUIT  
00  
[] to continue  
Enter the desired event number for event you want to occur at a specified time.  
Events 10-11 are reserved for the installer only.  
00 = clear event  
ENTER EVENT  
CLEAR EVENT 00  
01 = Relay On/Off  
02 = User Access  
NOTE: Events 07 and 10  
cause the keypad to  
beep every 30 seconds  
when messages are  
displayed. Stop the  
beeps by pressing any  
key.  
03 = Latch Key Report to Pager (sent to all pagers and is active only when the system is  
armed; message sent is 777-7777; user must be enabled for paging; see User Attributes  
in System Operation section)  
04 = Forced Stay Arming (forced bypass is automatically enabled regardless of setting in  
field *23)  
05 = Forced Away Arming (forced bypass is automatically enabled regardless of setting in  
field *23)  
06 = Auto Disarm  
07 = Display “Reminder”  
10 = Display custom words (system displays custom words 8, 9, and 10 at defined time; can  
be used as installer’s reminder message to the end user)  
11 = Periodic Test Report (see key commands in Testing the System section to quickly set  
periodic test reporting intervals)  
[] to continue  
This prompt appears if event “1” (relay on/off) was selected, otherwise it is skipped.  
Enter the physical device number as programmed in 79 Menu Mode.  
01-04 = device number; 17, 18 = built-in triggers 1 and 2 respectively  
[] to continue to the “Start” prompt  
DEVICE NUMBER  
XX  
5-14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
This prompt appears if event “2” (user access) was selected. Otherwise it is skipped.  
1-8 = group number  
[] to continue to the “Start” prompt  
GROUP NUMBER  
X
Enter the event’s start time and days of the week to occur.  
01-12 = hour; 00-59 = minute; 0 = AM; 1 = PM  
Days = position the cursor under the desired days using the [] key to move forward, then  
press “1” to select the desired day(s)  
START  
SMTWTFS  
HH MMAM 0 0 1 0 0 0 0  
[] to continue  
Enter the event’s stop time and days of the week to occur.  
This entry applies only to the following events: 1 (relay on/off); 2 (user access); 3 (latch key  
report)  
STOP  
SMTWTFS  
HH MMAM 0 0 1 0 0 0 0  
01-12 = hour; 00-59 = minute; 0 = AM; 1 = PM  
Days = position the cursor under the desired days using the [] key to move forward, then  
press “1” to select the desired day(s)  
[] to continue  
Enter the desired repeat option for this schedule.  
e.g., To make a schedule that happens everyday you would select all days with a repeat  
count of 1. To make a schedule that runs for one week then stops, select everyday with a  
REPEAT OPTION  
0-4  
X
repeat count of 0.  
0 = do not repeat; 1 = repeat schedule weekly; 2 = repeat schedule biweekly (every other  
week)  
3 = repeat every 3rd week; 4 = repeat every 4th week  
[] to continue  
Select whether you want this schedule to start and stop at random times.  
This option applies only to events 01 (relay on/off) and 11 (periodic test report).  
If selected, the scheduled start and stop times will vary within 60 minutes of the “hour”  
time. For example, if a schedule is set to start at 6:15pm, it will do so the first time 6:15pm  
arrives, but on subsequent days it will start anytime between 6:00 and 6:59 p.m.  
[] to continue  
RANDOMIZE  
0=NO 1=YES  
X
NOTE: Do not use the random option if the start and stop times are within the same “hour”  
setting, otherwise unpredictable results may occur (e.g., the randomized stop time may occur  
before the start time).  
5-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
5-16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S E C T I O N  
6
System Communication and Operation  
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •  
System Communication Overview  
This system accommodates several formats for reporting alarms and other system conditions to the  
Central Station. The process of a successful transmission consists of both the method of communication  
between the control panel and the Central Station receiver; and the actual way the information is sent  
and displayed at the Central Station.  
When the panel calls the Central Station receiver, it waits to hear a “handshake” frequency from the  
receiver to confirm that the receiver is on-line and ready to receive its message. Once the panel hears  
the handshake it is programmed to listen for, it sends its message. The panel then waits for a “kissoff”  
frequency from the receiver acknowledging that the message was received and understood.  
If the handshake frequency is not given or is not understood by the panel, the panel will not send its  
message. Once the handshake frequency is received and understood by the panel, the panel sends its  
message. If there is an error in the transmission (the receiver does not receive a “valid” message), the  
kissoff frequency is not given by the Central Station receiver.  
The panel makes a total of eight attempts to the primary telephone number and eight attempts to the  
secondary telephone number (if programmed) to get a valid message through. If the panel is not  
successful after its numerous attempts, the keypad displays COMM. FAILURE (on alpha keypads) or  
FC (on fixed-word keypads).  
Report Code Formats  
The following chart indicates the types of (handshake/kissoff) frequencies that the panel supports and  
the different formats that can be sent with each.  
FORMAT  
Low Speed  
HANDSHAKE  
1400 Hz  
TRANSMITS DATA  
1900Hz (10PPS)  
KISSOFF  
1400 Hz  
TRANSMIT TIME  
Under 15 secs  
3+1, 4+1, 4+2  
(Standard report)  
Sescoa/Rad  
3+1, 4+1, 4+2  
Express  
4+2  
2300 Hz  
1800Hz (20PPS)  
DTMF (10 cps)  
2300 Hz  
1400 Hz  
Under 10 secs  
(Standard report)  
Under 3 secs  
14002300 Hz  
Contact ID  
14002300 Hz  
DTMF (10 cps)  
1400 Hz  
Under 3 secs  
The following table describes each format in greater detail.  
FORMAT TYPE  
3+1 and 4+1  
Standard Formats  
3+1 and 4+1  
DESCRIPTION  
Comprises a 3- (or 4-) digit subscriber number and a single-digit report  
code (e.g., Alarm, Trouble, Restore, Open, Close, etc).  
Comprises a 3- (or 4-) digit subscriber number and a two-digit report code.  
The first digit is displayed on the first line. On the second line, it is  
repeated 3 (or 4) times and is followed by the second digit. This is the  
expandeddigit.  
Expanded Formats  
4+2 Format  
ADEMCO Contact ID  
Reporting Format  
Comprises a 4-digit subscriber number and 2-digit report code.  
Comprises a 4 or 10-digit subscriber number (depending on format  
selected), 1-digit event qualifier (newor restore), 3-digit event code,  
and 3-digit zone number, user number, or system status number (see the  
following page).  
6-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
The following table lists codes for reports sent in different formats:  
Code for  
3+1/4+1  
Standard  
Code for  
3+1/4+1  
Expanded  
Type of  
Report  
Code for  
4+2  
Alarm  
SSS(S) A  
SSS(S) T  
SSS(S) B  
SSS(S) E  
SSS(S) A  
AAA(A) Z  
SSSS AZ  
SSSS Tt  
SSSS Bb  
SSSS EA  
Trouble  
Bypass  
AC Loss  
SSS(S) T  
TTT(T) t  
SSS(S) B  
BBB(B) b  
SSS(S) E  
C
EEE(E) A  
C
Low Batt  
SSS(S) L  
SSS(S) L  
SSSS LL  
B
LLL(L) L  
B
Open  
Close  
Test  
SSS(S) O  
SSS(S) C  
SSS(S) G  
SSS(S) R  
SSS(S) O  
OOO(O) U  
SSSS OU  
SSSS CU  
SSSS Gg  
SSSS RZ  
SSS(S) C  
CCC(C) U  
SSS(S) G  
GGG(G)g  
Restore  
Alarm  
SSS(S) R  
RRR(R) Z  
AC Restore  
LoBat Res.  
Trouble Res.  
Bypass Res.  
SSS(S) R  
A
SSS(S) R  
SSSSR  
A
c
A
A
R R R (R )A  
A A A  
A
c
SSS(S) R  
L
SSS(S) R  
SSSS R L  
L B  
L
R R R (R )L  
L L L  
L
B
SSS(S) R  
T
SSS(S) R  
SSSS R t  
T
T
R R R (R )t  
T T T  
T
SSS(S) R  
B
SSS(S) R  
SSSS R b  
B
B
R R R (R )b  
B B B  
B
Where:  
SSS or SSSS = Subscriber ID  
A = Alarm Code–1st digit  
C = Close Code–1st Digit  
U = User Number (in hex)  
Gg = Test Code (1st & 2nd digits)  
R = Restore Code (Alarm)  
Z = Typically Zone Number*–2nd digit  
Tt = Trouble Code (1st & 2nd digits)  
Bb = Bypass Code (1st & 2nd digits)  
R t = Restore Code (Trbl) 1st & 2nd  
T
digits  
digits  
EA  
AC Loss Code (1st & 2nd digits)  
R b = Restore Code (Byps) 1st & 2nd  
B
C =  
LL  
Low Battery Code (1st & 2nd digits)  
R A  
A C  
=
Restore Code (AC) 1st & 2nd digits  
Restore Code (Bat) 1st & 2nd digits  
B =  
O = Open Code–1st Digit  
R L  
L B =  
*Zone numbers for: & #, or B = 99  
1 + , or A = 95  
Duress = 92  
3 + #, or C = 96  
6-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
®
Ademco Contact ID  
®
The Ademco Contact ID Reporting Format comprises the following:  
4-digit or 10-digit subscriber number (depending on format selected.  
1-digit event qualifier (“new” or “restore”).  
3-digit event code.  
3-digit zone number, user number, or system status number (see the following page).  
®
Ademco Contact ID Reporting takes the following format: CCCC(CCCCCC) Q EEE GG ZZZ  
where:  
CCCC(CCCCCC) = Customer (subscriber) ID  
Q = Event qualifier, where:  
E = new event , and R = restore  
EEE = Event code (3 hexadecimal digits)  
Note: For a complete list of event codes, refer to the central office  
receiver manual.  
GG = Partition number (always sent as “01” for this control; system  
messages show “00.”  
ZZZ = Zone/contact ID number reporting the alarm, or user number for  
open/close reports. System status messages (AC Loss, Walk Test,  
etc.) contain zeroes in the ZZZ location.  
TABLE OF CONTACT ID EVENT CODES  
Code Definition  
Code Definition  
110  
121  
122  
123  
131  
132  
134  
135  
143  
145  
146  
150  
162  
301  
302  
305  
309  
321  
333  
341  
344  
351  
353  
373  
374  
380  
Fire Alarm  
Duress  
Alarm, 24-hour Silent  
Alarm, 24-hour Audible  
Alarm, Perimeter  
Alarm, Interior  
Alarm, Entry/Exit  
Alarm, Day/Night  
Alarm, Expansion Module  
ECP Module cover tamper  
Silent Burglary  
Alarm, 24-Hour Auxiliary/Monitor zone  
Carbon Monoxide  
381  
382  
383  
384  
393  
401  
RF Sensor Supervision  
Supervision Auxiliary Wire Zone  
RF Sensor Tamper  
RF Sensor Low-battery  
Clean Me  
Disarmed, Armed AWAY, Armed  
MAXIMUM  
Schedule Arm/Disarm AWAY  
Cancel by User  
Remote Arm/Disarm (Downloading)  
Quick Arm AWAY  
Keyswitch Arm/Disarm AWAY  
Disarmed/Armed STAY/INSTANT,  
Quick-Arm STAY/INSTANT  
Keyswitch Arm/Disarm STAY  
Recent Close (restore only)  
Bypass  
Manually Triggered Dialer Test  
Periodic Test  
AAV to Follow  
Walk Test Entered/Exited  
Event Log 80% Full  
Real-Time Clock was Changed (log only)  
Program Mode Entry (log only)  
Program Mode Exit (log only)  
Latch Key (log only)  
403  
406  
407  
408  
409  
441  
AC Power  
442  
459  
570  
601  
602  
606  
607  
623  
625  
627  
628  
642  
Low System Battery/Battery Test Fail  
System Reset (Log only)  
Battery Test Failure  
Bell/Siren Trouble  
Trouble, Expansion Mod. Supervision  
Trouble, ECP Cover Tamper  
RF Receiver Jam  
Telco Line Fault  
Long Range Radio Trouble  
Fire Loop Trouble  
Exit Error Alarm  
Global Trouble, Trouble Day/Night  
750 - Reserved for Configurable Zone Type  
789  
report codes (check with central station  
when using these codes)  
6-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
User Security Codes  
The system supports up to 16 security codes, which can each be assigned one of 4 authority levels.  
The authority level determines the functions each code can perform as follows:  
Authority Levels (authority levels can be assigned to users 3-16 only; users 1 and 2 cannot be changed)  
Level  
User No.  
Functions  
Installer  
01  
(default=4112) perform all security functions except can disarm only if used to  
arm; can enter program mode; can change System Master code; cannot assign any  
other user codes  
System  
Master  
02  
(default 1234) only one system master code per system; can perform all  
security functions, add/delete users, change system master code, view event log, set  
system clock, program keypad macro, program scheduled events, activate output  
devices (triggers/relays)  
0-User  
03-16  
perform security functions (arm, disarm, etc.) only; cannot add/delete  
users, view event log, set system clock or program scheduled events  
1-Arm Only  
2-Guest  
see “user”  
see “user”  
see “user”  
arm system only  
can disarm the system only if it was used to arm the system  
3-Duress  
performs security functions, but also silently sends a duress message to the central  
station; reports as duress code user number.  
Refer to the user guide for procedures on adding/deleting security codes and changing attributes.  
The following is a brief description of how to add user codes.  
Changing the System Master code...  
Using Installer code: Installer code + [8] + 02 + new code  
Using current System Master code: System Master code + [8] + 02 + new code + new code again  
Adding a User Code: Master code + [8] + 2-digit user no. + user’s code  
Deleting a User Code: Master code + [8] + 2-digit user no. + [#] [0]  
Assigning Attributes: Master code + [8] + 2-digit user no. + [#] [attribute no.] + value  
Attributes:  
Values  
1 = Authority Level 0-3 (see Authority Level table above)  
2 = Access Group 0-8 (0 = not assigned to a group)  
3 =  
Not Used  
4 = RF Zone No.;assigns user number to button type zone (keyfob) for arm/disarm.  
(keyfob must be enrolled in system first; see Wireless Key Templates section)  
5 = Open/Close Paging; 1 for yes, 0 for no  
Setting the Real-Time Clock  
Alpha Display:  
1.  
+[#] + [6] [3]  
(Security Code)  
DISARMED  
READY TO ARM  
2. Press [] when the time/date is displayed.  
A cursor appears under the first digit of the hour.  
To move cursor ahead, press []. To go back, press [#].  
Enter the 2-digit hour and 2-digit minute setting.  
Press [1] for PM or [2] for AM.  
TIME/DATE  
04:04PM 10/17/00  
SAT  
Current time display  
Enter the last two digits of the current year.  
Enter the 2-digit month and 2-digit day setting.  
3. To exit, press [] when cursor is at the last digit, or  
wait 10 seconds.  
TIME/DATE  
04:04P2000/10/17  
Time/date editing display  
SAT  
6-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Keypad Functions  
The following is a brief list of system commands. For detailed information, see the User's Manual.  
Voice Keypads  
The 6150V/6160V Voice Keypads provide the following features:  
Message Center, which lets the user record and playback one message.  
Voice Status, which can announce system status by using the STATUS key.  
Voice Chime, which can alert users to the opening of doors/windows while the system is disarmed.  
Refer to the User Guide for specific procedures for activating and using these features.  
Keypad Commands  
Function  
Description  
Silence alarms  
Pressing any key will silence the keypad sounder for 10 seconds. Disarming the  
system will silence both keypad and external sounders.  
Quick Arm  
If enabled (field 21), you can press [#] in place of the system's security code, plus  
the desired arming key (Away, Stay, Instant, Maximum)  
Single-Button arming  
If programmed (*57 Function Key menu mode), lettered keys A-D can be used for  
arming, using options 3-AWAY, 4-STAY, 5-NIGHT-STAY, or 6-Step-Arming  
If used, no security code is required to arm the system.  
Alarm Memory  
Arming Away  
When the system is disarmed, any zones that were in an alarm condition during the  
armed period will be displayed. To clear this display, simply repeat the disarm  
sequence (enter the security code and press the OFF key) again.  
Enter code + AWAY [2] or simply press appropriate lettered key on the keypads (see  
“Single-Button Arming” above). If the “Auto-Stay Arm” feature is enabled (field *84)  
and the entry/exit door is not opened and closed within the programmed exit delay  
time, the system will automatically arm in STAY mode if armed from a wired  
keypad (non-RF device). If the door is opened and closed within the exit delay  
period, the system arms in AWAY mode.  
Arming Stay  
Enter code + STAY [3] or simply press appropriate key on the keypads (see “Single-  
Button Arming” above). See “Arming Away” above for Auto-Stay arming feature.  
Enter code + STAY [3] + STAY [3] or simply press appropriate key on the keypads  
(see “Single-Button Arming” above).  
Arming Night-Stay  
Arming Instant  
Enter code + INSTANT [7].  
Arming Maximum  
Enter code + MAXIMUM [4] or simply press appropriate lettered key on the  
keypads (see “Single-Button Arming” above).  
Disarming  
Enter code + OFF [1]. If entry delay or an alarm is active, you do not need to  
press OFF.  
Bypassing Zones  
Enter code + BYPASS [6] + zone number(s).  
Forced (Quick) Bypass  
To automatically bypass all faulted zones, use the “Quick Bypass” method. Enter  
code + BYPASS + [#], then wait for all open zones to be displayed. Arm when  
display indicates “ZONE BYPASSED” and “READY TO ARM”.  
Enter code + CHIME [9]. To turn chime off, enter code + CHIME again.  
If relay outputs are used, two keypad entries available to the user are included. If  
programmed, these entries can be used to manually activate or deactivate the  
device(s) for starting or stopping some action, such as turning lights on or off, etc.  
These keypad entries are:  
Chime Mode  
Activate Output Devices  
[Security Code] + # + 7 + [2-digit Device #] activates (starts) that device.  
[Security Code] + # + 8 + [2-digit Device #] deactivates (stops) that device.  
SUMMARY OF ARMING MODES  
Arming Mode  
Features for Each Arming Mode  
Exit Delay  
Yes  
Entry Delay  
Yes  
Perimeter Armed  
Interior Armed  
AWAY  
STAY  
NIGHT-STAY  
Yes  
Yes  
Yes  
Yes  
No  
Yes  
Yes  
Yes  
Yes  
only those zones  
listed in Night-  
Stay zone list  
No  
INSTANT  
MAXIMUM  
Yes  
Yes  
No  
No  
Yes  
Yes  
Yes  
6-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
Panic Keys  
There are three Panic keys (A, B, and C) that, if programmed, can be used to manually initiate  
alarms and send a report to the central station by pressing and holding the appropriate key for at  
least 2 seconds. Each key can be programmed for 24-hour Silent, 24-hour Audible, Fire, or Personal  
Emergency responses. The Panic keys are identified by the system as follows:  
Keys  
Displayed as Zone  
IMPORTANT: For a Silent panic function (if programmed) to be of  
practical value, you must program a report code for the zone and the  
system must be connected to a central station.  
95  
99  
96  
[A] (/1)  
[B] (/#)  
[C] (3/#)  
Various System Trouble Displays  
Alpha Display  
Fixed Disp.Meaning  
ALARM CANCELED  
CA  
will appear if an exit or interior zone contained a fault during closing at the time  
the Exit Delay ended (e.g., exit door left open), but the system was disarmed during  
the Entry Delay time. The alarm sounder and keypad sound continuously, but stop  
when the system is disarmed. No message will be transmitted to the central station.  
EXIT ALARM  
EA  
will appear when the Exit Delay ends if an exit or interior zone contained a fault  
during closing. The alarm sounder and keypad sound continuously until the system  
is disarmed (or timeout occurs). An “Exit Alarm” message is sent to the central  
station.  
Also results if an alarm from an exit or interior zone occurs within 2 minutes after  
the end of an Exit Delay.  
CHECK  
CHECK  
indicates that a problem exists with the displayed zone(s) and requires attention.  
ALARM 1xx  
FAULT 1xx  
CHECK 1xx  
1xx  
1xx  
1xx  
91  
indicates that communication between control and a zone expander or wireless  
receiver is interrupted, where “xx” is the device address. Check the wiring and  
DIP switch settings on the units.  
If field *199 is set to “1,” all ECP module problems are displayed as “91.”  
If there are wireless sensors in the system, the Check condition may also be caused  
by some change in the environment that prevents the receiver from receiving  
signals from a particular sensor.  
SYSTEM LO BAT  
LO BAT  
BAT  
BAT  
with no zone number indicates that the system's main standby battery is weak.  
with a zone number and a once-per-minute beeping at the keypad indicates that a  
low-battery condition exists in the wireless sensor displayed (zone “00” indicates a  
wireless keypad). If the battery is not replaced within 30 days, a “CHECK” display  
may occur.  
NOTE: Some wireless sensors use a non-replaceable long-life battery which requires  
replacement of the entire unit at the end of battery life (e.g., 5802, 5802CP).  
Busy-Standby  
Modem Comm  
dl  
CC  
If this remains displayed for more than 1 minute, the system is disabled.  
The system is in communication with the central station for change of function or  
status verification.  
no display  
no display  
Power Failure  
If there is no keypad display at all and the LEDs are unlit, operating power (AC and  
battery) for the system has stopped and the system is inoperative.  
If the message “AC LOSS” (Alpha display keypads) or “NO AC” (Fixed-Word display  
keypads) is displayed, the keypad is operating on battery power only.  
If the battery standby capacity is used up during a prolonged AC power outage, the  
control's power will shut down to minimize deep discharge of the battery.  
Comm. Failure  
Open Circuit  
Long Rng Trbl  
FC  
OC  
bF  
A communication failure has occurred.  
The keypad is not receiving signals from the control and sees an open circuit.  
Backup LRR communication failure.  
Bell supervision failure.  
Bell Failure  
70  
RCVR Jam  
90  
RF jam detected.  
KEYPAD LOW BAT  
Phone Okay  
Dialer Off  
Test in Progress  
Upload Completed  
Upload Failed  
00 BAT  
Cd  
dO  
dd  
dC  
dF  
Wireless keypad low battery  
The dialer test has been successful (CID code 601).  
The dialer is disabled.  
Walk test mode is active(CID code 607).  
The upload or download session was completed.  
The upload or download session failed before completion.  
6-6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S E C T I O N  
7
Testing the System  
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •  
About Test Procedures  
After the installation is complete, you should perform the following tests:  
System Test:  
Checks that all zones have been installed properly and the system properly  
responds to faults.  
Dialer Test:  
Go/No Go Test:  
Checks that the phone connection to the central station is working properly.  
Checks that transmissions can be received from transmitters. Should be  
performed before permanently mounting transmitters.  
RF Sniffer Mode: Checks that RF transmitter serial numbers have been properly entered into the  
system.  
Battery Tests:  
Automatic battery tests are performed by the system. See Automatic Battery Test  
paragraph for details.  
System Test  
With the system in the disarmed state, check that all zones are intact (not faulted). Doors and  
windows with contacts should be closed, PIRs should be covered (use a cloth to mask them  
temporarily if necessary). If a “NOT READY” message is displayed, press [] to display the faulted  
zone(s). Restore faulted zone(s) if necessary, so that the “READY” message is displayed.  
1. Enter Installer Code + 5 [TEST] , then press “0” at the prompt to start Walk Test mode.  
1=DIAL, 0=WALK  
(no special display on Fixed-Word Display Keypads)  
The following will be displayed:  
TEST IN PROGRESS  
(dddisplayed on Fixed-Word Display Keypads)  
A Contact ID report will also be sent (code 607)  
2. Upon entering the system test mode, the outside sounder should sound for 1 second.  
If the backup battery is discharged or missing, the sounder may not turn on and a “LOW  
BATTERY” report will be transmitted with a “TEST” report.  
The keypad will beep about every 40 seconds as a reminder that the system is in the Test mode.  
NOTE: Wireless motion detectors (Passive Infrared units) will send signals out only if they have  
been inactive for 3 minutes (conserves battery life).  
3. Test all sensors using the procedure described in the User’s Guide “Testing the System” section  
and/or the each device’s instructions.  
4. After checking sensors, turn off the test mode by entering installer code + OFF.  
NOTE: Test mode automatically ends after 4 hours. During the final 5 minutes (after 3 hours 55  
minutes of Test mode), the keypad emits a double-beep every 30 seconds to alert that the end of  
Test mode is nearing.  
Checking Transmitter Enrollment (Sniffer Mode)  
Use this mode to verify that all transmitters have been properly programmed.  
1. Press [Installer code] + [#] + 3.  
The keypads will display all zone numbers of wireless units programmed into the system. Fault  
each transmitter in turn, causing each one to send a signal. As the system receives a signal from  
each transmitter, the zone number of that transmitter disappears from the display.  
NOTE: If the communicator is in the process of sending a report to the central station, the  
system will not go into the Sniffer mode. If so, wait a few minutes, and try again.  
2. After all transmitters have been checked, exit the sniffer mode by: [Installer code] + OFF.  
IMPORTANT: Sniffer mode does not automatically expire. You must manually exit Sniffer mode  
(by entering [Installer code] + OFF) to return to normal operation.  
7-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
NOTES: • All BR type units must physically be activated to clear the display.  
• When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to  
other buttons on that transmitter are cleared. This also applies to 5816 and 5817  
transmitters, which have multiple loops (zones).  
• Any transmitter that is not “enrolled” will not turn off its zone number.  
Go/No Go Test Mode  
The Go/No Go Test verifies adequate RF signal strength from the proposed transmitter location, and  
allow you to reorient or relocate transmitters if necessary, before mounting the transmitters  
permanently. This mode is similar to the Transmitter Test mode, except that the wireless receiver  
gain is reduced. This will enable you to make sure that the RF signal from each transmitter is  
received with sufficient signal amplitude when the system is in the normal operating mode.  
1. Enter [Installer code] + [#] + 4.  
2. After you have placed transmitters in their desired locations and the approximate length of wire to  
be run to sensors is connected to the transmitter's screw terminals (if used), fault each  
transmitter. Do not conduct this test with your hand wrapped around the transmitter.  
a. The keypad beeps three times to indicate signal reception and displays the unit’s zone number.  
b. If the keypad does not beep, you should reorient or move the transmitter to another location.  
Usually a few inches in either direction is all that is required.  
4. If each transmitter produces the proper keypad response when it is faulted, you can then  
permanently mount each of the transmitters according to the instructions provided with them.  
5. Exit the Go/No Go Test mode by entering: any user code + OFF.  
Dialer Communication Test and Periodic Test Reports  
The following steps can be followed to manually test communication to the central station.  
1. Enter Installer Code + 5 [TEST], then press “1” at the prompt to start the Dialer Test.  
1=DIAL, 0=WALK  
(no special display on Fixed-Word Display Keypads)  
The following will be displayed (accompanied by 2 beeps) if test is successful:  
PHONE OKAY  
(Cddisplayed on Fixed-Word Display Keypads)  
A Contact ID report will also be sent (code 601)  
If the dialer test is unsuccessful, the following is displayed:  
COMM FAILURE  
(FCdisplayed on Fixed-Word Display Keypads)  
2. Enter Installer code + OFF to clear the display and exit.  
Automatic Periodic Test Report  
The system can be set to automatically send test reports (enabled in field *64; Contact ID code 602) at  
specified intervals.  
Frequency of the reports is set in Scheduling mode (event 11) or by the following key commands:  
installer code + [#] + 0 + 0 = test report sent every 24 hours  
installer code + [#] + 0 + 1 = test report sent once per week  
installer code + [#] + 0 + 2 = test report sent every 28 days  
Each mode sets schedule 2 to the selected repeat option; first test report sent 12 hours after command.  
To ensure that test reports are sent at the times expected, set the Real-Time Clock to the proper time  
before entering the test report schedule command.  
Automatic Standby Battery Tests  
1. An automatic test is conducted every 3 minutes to ensure that a standby battery is present and  
properly connected. If a battery is not present or is not properly connected, a “LOW BATTERY”  
message is displayed and, if so programmed, will be reported to the central station.  
2. A battery capacity test is automatically conducted for 2 minutes every 4 hours, beginning 4 hours  
after exiting the Programming mode or after powering up the system. In addition, entry into the  
Test mode will also cause a battery capacity test to be initiated. If the battery cannot sustain a load,  
a “Low Battery” message is displayed and, if so programmed, will be reported to the central station.  
7-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S E C T I O N  
8
Specifications & Accessories  
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •  
SECURITY CONTROL  
Physical: 12-1/2” W x 14-1/2” H x 3” D (318mm x 368mm x 76mm)  
Electrical:  
VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, Ademco No. 1321 (in U.S.A.)  
RECHARGEABLE BACKUP BATTERY: 12VDC, 4AH (sealed lead acid type).  
Charging Voltage: 13.8VDC.  
ALARM SOUNDER: 12V, 2.0 Amp output can drive 12V BELLS or can drive one or two 702  
(series connected) self-contained 20-watt sirens.  
Do not connect two 702s in parallel.  
AUXILIARY POWER OUTPUT: 12VDC, 600mA max.  
NOTE: For UL installations, Alarm Sounder plus Auxiliary  
Power currents should not exceed 600mA total.  
FUSE: Battery (3A) No. 90–12  
Maximum Zone Resistance: Zones 1–8 = 300 ohms excluding EOLR standard zones  
Communication:  
FORMAT SUPPORTED:  
ADEMCO Express:  
10 characters/sec, DTMF (TouchTone) Data Tones,  
1400/2300Hz ACK, 1400Hz KISSOFF.  
ADEMCO Low Speed: 10 pulses/sec, 1900Hz Data Tone, 1400Hz ACK/KISSOFF.  
Radionics/SESCOA:  
20 pulses/sec, 1800Hz Data Tone, 2300Hz ACK/KISSOFF.  
Can report 0-9, B-F  
Ademco Contact ID  
10 characters/sec., DTMF (TouchTone) Data Tones,  
1400/2300Hz ACK, 1400Hz KISSOFF.  
LINE SEIZE: Double Pole  
RINGER EQUIVALENCE: 0.1B  
FCC REGISTRATION No.: 5GBUSA-44003-AL-E  
COMPATIBLE DEVICES  
Keypads:  
6150, 6160, 6150V, 6160V  
Wireless Receivers: 5881L/5882L: accepts up to 8 transmitters  
5881M/5882M: accepts up to 16 transmitters  
5800TM Transmitter Module (used with 5827BD Wireless 2-Way Keypad)  
5883 Transceiver: accepts up to system maximum transmitters  
6150RF Keypad/Transceiver: accepts up to system maximum transmitters  
Relay Module:  
Phone Modules:  
4204 RELAY MODULE  
4285 PHONE MODULE  
4286VIP PHONE MODULE  
Long Range Radio 7835C/7845C  
Sounders: Ademco AB-12M 10Motorized Bell & Box  
Ademco 1011BE12M 10Motorized Bell & Box  
Ademco 702 Outdoor Siren  
Ademco 719 2-Channel Siren  
Ademco 747 Indoor Siren  
Ademco 747UL Indoor Siren  
Ademco 744 Siren Driver  
Ademco 745X3 Voice Siren Driver  
Ademco 705-820, 5-inch Round Speaker  
Ademco 713 Speaker  
System Sensor PA400B (beige)/; PA400R (red) Indoor Piezo Sounder  
8-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
5800 Series Transmitter Input Loop Identification  
All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. Each of  
the input loops requires its own programming zone (e.g., a 5804's four inputs require four programming zones).  
LOOP 3  
LOOP 2  
LOOP 3  
LOOP 4  
YOU MUST  
ENROLL  
THIS  
LOOP 4  
YOU MUST  
ENROLL  
THIS  
O
N
LOOP 4  
O
F
F
LOOP 2  
LOOP 1  
NOTE: For information on any transmitter not  
shown, refer to the instructions accompanying  
that transmitter for details regarding loop  
numbers, etc.  
LOOP 2  
LOOP 1  
YOU MUST  
ENROLL  
LOOP  
1
BUTTON  
THIS BUTTON  
BUTTON  
LOOP 3  
LOOP 1  
SET  
HOUSE  
CODE  
5801  
ENROLL AS  
"UR" OR "RF"  
5802MN  
ENROLL AS  
"UR" OR "RF"  
5804BD  
5804  
ENROLL AS "BR"  
ENROLL AS "BR"  
UL NOTE: The following transmitters are  
not intended for use in UL  
installations:  
LOOP 1  
LOOP 1  
LOOP 1  
(PRIMARY)  
LOOP 2  
(AUX.  
CENTER)  
LOOP 2  
(REED)  
LOOP 2  
5808  
(REED)  
ENROLL AS "RF"  
LOOP 1  
(TERMINALS)  
LOOP 1  
(TERMINALS)  
5802MN, 5802MN2, 5804,  
5804BD, 5814, 5816TEMP,  
5819, 5819WHS & BRS, and  
5850.  
LOOP 3  
(AUX.  
RIGHT)  
ALTERNATE  
POSITION  
FOR LOOP 2  
5816  
5817  
5809  
5816MN  
ENROLL AS "RF"  
ENROLL AS "RF"  
ENROLL AS "RF"  
ENROLL AS "RF"  
LOOP 2  
(REED)  
LOOP 2  
(REED)  
LOOP 3  
LOOP  
1
MOTION  
(TERMINALS)  
LOOP 1  
(INTERNAL  
SHOCK  
LOOP 1  
(TERMINALS)  
(Green)  
(Red)  
SENSOR  
LOOP 3  
(TERMINALS)  
(Yellow)  
5890  
ENROLL AS  
"RF" OR "RM"  
5819  
ENROLL AS "RF"  
5819S (WHS & BRS)  
ENROLL AS "RF"  
5850 (GBD)  
ENROLL AS "RF"  
V20P-006-V0  
Compatible 5800 Series Transmitters Table  
Model  
Product  
Input Type  
Description  
Four pushbuttons, each with a unique input (loop) code.  
Programmable responses (e.g., Panic, Arm, Disarm, etc.)  
5801  
Wireless Panic  
Transmitter  
UR or RF  
Has single pushbutton.  
5802  
Pendant (Personal  
BR Only  
Emergency Transmitter)  
Usually programmed for response type of 24-Hr audible or 24-Hr  
Silent (other zone responses are possible).  
Same as 5802.  
5802CP  
5802MN  
5804  
Belt Clip (Personal  
Emergency)  
BR Only  
UR or RF  
BR Only  
BR  
Same as 5802.  
Miniature (Personal  
Emergency Trans.)  
Has four pushbuttons, each with a unique input (loop) code.  
Programmable responses (e.g., Arm, Disarm, etc.)  
House ID must be set.  
Requires 5800TM Transmitter Module.  
Wireless Key  
Transmitter  
5804BD  
Bi-Directional  
Wireless Key  
Can indicate system status via its 2 LEDs and built-in sounder.  
Has four pushbuttons, each with a unique input (loop) code.  
Operates the system similarly to wired keypads.  
One-piece smoke detectors with a built-in transmitter.  
5806  
5807  
5808  
Wireless  
Photoelectric Smoke  
Detectors  
RF  
One-piece rate-of-rise heat detector with a built-in transmitter.  
5809  
Heat Detector  
RF  
RF  
Has two unique input (loop) codes: one for a wired closed circuit  
contact loop; the other for its built-in reed switch (used with a  
magnet).  
5816  
Door/Window  
Transmitters  
5816MN  
Transmits a fault condition when temperature drops below 45°F.  
5816TEMP  
Low-Temp. Sensor  
RF  
8-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Compatible 5800 Series Transmitters Table (continued)  
Model  
5817  
Product  
Multi-Point Universal  
Transmitter  
Input Type  
Description  
Has three unique input (loop) codes: one for a Primarycontact  
loop with programmable options; the others for two auxiliary”  
closed circuit contact loops.  
RF  
Reed switch magnetic contact sensor; easily hidden in the frame  
5818  
5819  
Recessed  
Transmitter  
RF  
RF  
and edge of a door or window.  
Has a single unique input (loop) code.  
Connects to externally mounted inertia-type shock detector (not  
supplied).  
Shock Processor  
Transmitter  
Has built-in tampered cover switch.  
Has 3 unique input (loop) codes:  
Loop 1: Terminals for a wired, N.C. sensor loop.  
Loop 2: For a closed circuit contact loop using the built-in reed  
switch in conjunction with a magnet.  
Loop 3: Terminals for a wired, closed circuit contact loop.  
5819WHS  
5819BRS  
Shock Processor  
Transmitter  
RF  
Has built-in shock sensor.  
Has built-in tampered cover switch.  
Has 3 unique input (loop) codes:  
Loop 1: Built-in shock sensor loop wired to TB1 (normally closed).  
Loop 2: For a closed circuit contact loop using the built-in reed  
switch in conjunction with a magnet.  
Loop 3: Externally wired, closed circuit loop connected to TB2.  
5827  
Wireless Keypad  
Uses House  
ID only  
Can be used to turn the burglary protection on and off.  
Features the same built-in panic functions as wired keypads.  
The keypad is identified as zone 00on wired keypads when it  
transmits with a low battery.  
5827BD  
Wireless Two-Way  
Keypad  
Uses House  
ID only  
Requires 5800TM Transmitter Module.  
Operates the system similarly to wired keypads, including panics.  
Can indicate system status via its 3 LEDs and sounder.  
Includes 3 panic keys.  
5849  
5890  
Glassbreak Detector  
PR Detector  
RF  
RF  
House ID must also be set.  
Requires both sound and shock of breaking glass to cause  
alarm to be transmitted.  
Dual-element passive infrared detector/transmitter with built-in  
selectable pulse count.  
Note: There is a 3-minute lockout between fault transmissions to  
conserve battery life.  
5899  
Magnets  
Package of 4 magnets for use with 5816 and 5817 transmitters.  
8-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
8-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S E C T I O N  
9
Regulatory Agency Statements  
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •  
• • •  
RADIO FREQUENCY EMISSIONS  
Federal Communications Commission (FCC) Part 15  
This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful  
interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.  
Industry Canada  
This Class B digital apparatus complies with Canadian ICES-003.  
Cet Appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.  
TELEPHONE/MODEM INTERFACE  
FCC Part 68  
This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains the FCC registration  
number and Ringer Equivalence Number (REN). You must provide this information to the telephone company when requested.  
This equipment uses the following USOC jack: RJ31X  
This equipment may not be used on telephone-company-provided coin service. Connection to party lines is subject to state tariffs. This  
equipment is hearing-aid compatible.  
Industry Canada  
NOTICE: The Industry Canada Label identifies certified equipment. This certification means that the equipment meets telecommunications  
network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements  
document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction.  
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications  
company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with  
the above conditions may not prevent degradation of service in some situations.  
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made by the user  
to this equipment, or equipment malfunctions, may give the telecommunications company to request the user to disconnect the equipment.  
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic  
water pipe system, if present, are connected together, This precaution may be particularly important in rural areas.  
Caution: Users should not attempt to make such connections themselves but should contact appropriate electric inspection authority, or  
electrician, as appropriate.  
Ringer Equivalence Number Notice:  
The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed  
to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to the  
requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5.  
Industrie Canada  
AVIS: l’étiquette d’Industrie Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme aux normes de  
protection, d’exploitation et de sécurité des réseaux de télécommunications, comme le prescrivent les documents concernant les exigences  
techniques relatives au matériel terminal. Le Ministère n’assure toutefois pas que le matériel fonctionnera à la satisfaction de l’utilisateur.  
Avant d’installer ce matériel, l’utilisateur doit s’assurer qu’il est permis de le raccorder aux installations de l’enterprise locale de  
télécommunication. Le matériel doit également être installé en suivant une méthode acceptée da raccordement. L’abonné ne doit pas oublier qu’il  
est possible que la conformité aux conditions énoncées ci-dessus n’empêche pas la dégradation du service dans certaines situations.  
Les réparations de matériel nomologué doivent être coordonnées par un représentant désigné par le fournisseur. L’entreprise de  
télécommunications peut demander à l’utilisateur da débrancher un appareil à la suite de réparations ou de modifications effectuées par  
l’utilisateur ou à cause de mauvais fonctionnement.  
Pour sa propre protection, l’utilisateur doit s’assurer que tous les fils de mise à la terre de la source d’energie électrique, de lignes téléphoniques  
et des canalisations d’eau métalliques, s’il y en a, sont raccordés ensemble. Cette précaution est particulièrement importante dans les régions  
rurales.  
Avertissement : L’utilisateur ne doit pas tenter de faire ces raccordements lui-même; il doit avoir racours à un service d’inspection des  
installations électriques, ou à un électricien, selon le cas.  
AVIS : L’indice d’équivalence de la sonnerie (IES) assigné à chaque dispositif terminal indique le nombre maximal de terminaux qui  
peuvent être raccordés à une interface. La terminaison d’une interface téléphonique peut consister en une combinaison de quelques dispositifs, à  
la seule condition que la somme d’indices d’équivalence de la sonnerie de tous les dispositifs n’excède pas 5.  
9-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
UL NOTICES  
1. Entry Delay No. 1 and No. 2 (fields 35, 36) cannot be greater than 30 seconds for UL Residential  
Burglar Alarm installations, and entry delay plus dial delay should not exceed 1 minute. For UL  
Commercial Burglar Alarm installations, total entry delay may not exceed 45 seconds.  
2. For UL Commercial Burglar Alarm (Grade AA) and UL Residential Burglar Alarm installations  
with line security, total exit delay time must not exceed 60 seconds. For UL Burglar Alarm  
installations without line security (Grade A), total exit delay time must not exceed 120 seconds.  
3. The maximum number of reports per armed period (field 93) must be set to “0” (unlimited) for UL  
installations.  
4. Periodic testing (see scheduling mode) must be at least every 24 hours.  
5. Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL installations  
(Aux power 500mA max.).  
6. If used, the audible alarm device(s) must be placed where it/they can be heard by all users.  
7. For UL commercial burglar alarm installations the control unit must be protected from  
unauthorized access. The tamper switch installed to protect the control unit enclosure door is  
suitable for this purpose.  
8. Remote downloading without an alarm company technician on-site (unattended downloading) is not  
permissible for UL installations.  
9. Auto-disarming is not a UL Listed feature.  
10. As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial and  
residential applications, the following UL requirements per UL681 are provided:  
The maximum time that a control unit shall be programmed to delay the transmission of a signal to  
a remote monitoring location, or to delay the energizing of a local alarm sounding device to permit  
the alarm system user to enter and disarm the system, or to arm the system and exit shall not  
exceed:  
a) 60 seconds for a system with standard line security or encrypted line security,  
b) 120 seconds for a system without standard line security or encrypted line security, or  
c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.  
SIA Quick Reference Guide  
1. *31 Single Alarm Sounding per Zone: If “0” selected, “alarm sounding per zone” will be the same as  
the “number of reports in armed period” set in field *93 (1 if one report, 2 if 2 reports, unlimited for  
zones in zone list 7).  
2. *34 Exit Delay: Minimum exit delay is 45 seconds.  
3. *35/*36 Entry Delay 1 and 2: Minimum entry delay is 30 seconds.  
4. *37 Audible Exit Warning: Feature always enabled; field does not exist.  
5. *39 Power Up in Previous State: Must be “1,” power up in previous state.  
6. *40 PABX Access Code or Call Waiting Disable: If call waiting is used, call waiting disable option in  
field *91 must be set.  
7. *50 Burglary Dial Delay: Delay must be minimum of 30 seconds.  
8. *59 Exit Error Alarm Report Code: Always enabled.  
9
*68 Cancel Report Code: Default is “code enabled.”  
10. *69 Recent Closing Report Code: Always enabled.  
11. *91 Option Selection: Exit Delay option should be enabled. If call waiting is used, Call Waiting  
Disable must be set to “1” (enabled).  
12. *93 No. reports in Armed Period: Must be set for 1 or 2 report pairs.  
9-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S E C T I O N 1 0  
Limitations and Warranty  
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •  
WARNING  
THE LIMITATIONS OF THIS ALARM SYSTEM  
While this System is an advanced design security system, it does not offer guaranteed protection  
against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is  
subject to compromise or failure to warn for a variety of reasons. For example:  
• Intruders may gain access through unprotected openings or have the technical sophistication to  
bypass an alarm sensor or disconnect an alarm warning device.  
• Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other sensing  
devices will not work without power. Battery-operated devices will not work without batteries, with  
dead batteries, or if the batteries are not put in properly. Devices powered solely by AC will not work  
if their AC power supply is cut off for any reason, however briefly.  
• Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the  
alarm receiver. Even if the signal path has been recently checked during a weekly test, blockage can  
occur if a metal object is moved into the path.  
• A user may not be able to reach a panic or emergency button quickly enough.  
• While smoke detectors have played a key role in reducing residential fire deaths in the United  
States, they may not activate or provide early warning for a variety of reasons in as many as 35% of  
all fires, according to data published by the Federal Emergency Management Agency. Some of the  
reasons smoke detectors used in conjunction with this System may not work are as follows. Smoke  
detectors may have been improperly installed and positioned. Smoke detectors may not sense fires  
that start where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the  
other side of closed doors. Smoke detectors also may not sense a fire on another level of a residence  
or building. A second floor detector, for example, may not sense a first floor or basement fire.  
Finally, smoke detectors have sensing limitations. No smoke detector can sense every kind of fire  
every time. In general, detectors may not always warn about fires caused by carelessness and safety  
hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable  
materials, overloaded electrical circuits, children playing with matches, or arson. Depending on the  
nature of the fire and/or location of the smoke detectors, the detector, even if it operates as  
anticipated, may not provide sufficient warning to allow all occupants to escape in time to prevent  
injury or death.  
• Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as  
diagrammed in their installation manual. Passive Infrared Detectors do not provide volumetric area  
protection. They do create multiple beams of protection, and intrusion can only be detected in  
unobstructed areas covered by those beams. They cannot detect motion or intrusion that takes place  
behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or windows. Mechanical  
tampering, masking, painting or spraying of any material on the mirrors, windows or any part of the  
optical system can reduce their detection ability. Passive Infrared Detectors sense changes in  
temperature; however, as the ambient temperature of the protected area approaches the  
temperature range of 90° to 105°F (32° to 40°C), the detection performance can decrease.  
• Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if  
they are located on the other side of closed or partly open doors. If warning devices are located on a  
different level of the residence from the bedrooms, then they are less likely to waken or alert people  
inside the bedrooms. Even persons who are awake may not hear the warning if the alarm is muffled  
by noise from a stereo, radio, air conditioner or other appliance, or by passing traffic. Finally, alarm  
warning devices, however loud, may not warn hearing-impaired people.  
• Telephone lines needed to transmit alarm signals from a premises to a central monitoring station  
may be out of service or temporarily out of service. Telephone lines are also subject to compromise by  
sophisticated intruders.  
• Even if the system responds to the emergency as intended, however, occupants may have  
insufficient time to protect themselves from the emergency situation. In the case of a monitored  
alarm system, authorities may not respond appropriately.  
• This equipment, like other electrical devices, is subject to component failure. Even though this  
equipment is designed to last as long as 10 years, the electronic components could fail at any time.  
(Continued)  
10-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
WARNING  
THE LIMITATIONS OF THIS ALARM SYSTEM  
(Continued)  
The most common cause of an alarm system not functioning when an intrusion or fire occurs is  
inadequate maintenance. This alarm system should be tested weekly to make sure all sensors and  
transmitters are working properly. The security keypad (and remote keypad) should be tested as well.  
Wireless transmitters (used in some systems) are designed to provide long battery life under normal  
operating conditions. Longevity of batteries may be as much as 4 to 7 years, depending on the  
environment, usage, and the specific wireless device being used. External factors such as humidity,  
high or low temperatures, as well as large swings in temperature, may all reduce the actual battery life  
in a given installation. This wireless system, however, can identify a true low-battery situation, thus  
allowing time to arrange a change of battery to maintain protection for that given point within the  
system.  
Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm  
system is not a substitute for insurance. Homeowners, property owners and renters should continue to  
act prudently in protecting themselves and continue to insure their lives and property.  
We continue to develop new and improved protection devices. Users of alarm systems owe it to  
themselves and their loved ones to learn about these developments.  
10-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
– INDEX –  
1321................................... 1-1, 2-4  
24-Hour Audible Alarm .............. 3-3  
24-Hour Silent Alarm................. 3-3  
3+1 and 4+1 Standard Formats. 6-1  
4204 1-2, 2-5, 2-6, 2-9, 3-1, 5-6, 8-1  
4229................................... 2-6, 3-1  
4285 Phone Module 1-1, 2-12, 5-11  
4286 Phone Module 1-1, 2-12, 5-11  
4-Wire Smoke Detectors ........... 2-6  
5800 Series Transmitters 2-8, 8-2, 8-3  
5800TM......... 2-7, 2-8, 8-1, 8-2, 8-3  
5801................................... 2-8, 8-2  
5802............................ 2-8, 6-6, 8-2  
5802CP....................... 2-8, 6-6, 8-2  
5804 wireless key...................... 5-4  
5804BD wireless key................. 5-4  
5827............................ 2-8, 4-1, 8-3  
5827BD..2-7, 2-8, 4-1, 8-1, 8-2, 8-3  
5881............................ 1-1, 2-5, 2-7  
6128.......................................... 2-3  
6139................................... 2-3, 3-5  
7720PLUS or 7820.................... 1-1  
9-pin connector ......................... 2-8  
D
N
Data Field Programming Procedures  
..............................................3-5  
Defining Output Functions .........5-7  
Descriptor Programming..........5-11  
device address . 2-3, 2-9, 3-1, 3-6, 4-  
1, 4-11, 5-6, 6-6  
No Alarm Response............3-4, 5-8  
Normally Closed Zones..............2-6  
Normally Open Zones ................2-6  
O
On-Board Triggers ..........2-10, 2-12  
Output Device Mapping.......3-1, 5-6  
Output Devices ............3-2, 5-6, 6-5  
Output Functions .......................5-6  
Output relays .............................1-1  
Output To Long Range Radio ....4-1  
Device number . 5-1, 5-2, 5-3, 5-4, 5-  
7, 5-9  
DIP Switches.............................2-8  
Disarming ...........................5-8, 6-5  
E
Enrolling .............................2-8, 5-1  
entering serial number...............5-4  
Entry Delay...........3-3, 4-9, 6-5, 6-6  
Entry Delay 02...........................4-2  
Entry/Exit Burglary.....................3-3  
P
Pager Format.............................4-8  
Pager Programming............3-2, 4-8  
Paging .......................................4-7  
Panic Keys.................................6-5  
Perimeter Burglary.....................3-3  
Phone Line...............................2-10  
Phone Module. 1-1, 2-3, 2-5, 2-10, 2-  
11, 2-12, 4-1, 4-7, 5-11, 5-12, 8-1  
Power Failure......................5-8, 6-6  
power supply.......2-3, 2-4, 2-5, 10-2  
Primary Phone No......................4-4  
Event Logging.....................1-1,  
4-7  
Exit Delay ......4-2, 4-7, 4-9, 6-5, 6-6  
Exit Error Alarm .........................6-6  
Exit Error Report Code...............4-4  
Expert Programming Mode.5-3, 5-5  
A
F
AAV Connections.................... 2-12  
AC Power Supply ...................... 1-1  
AC Transformer......................... 2-4  
AD12612................................... 2-3  
Alarm Output............... 1-1, 2-4, 2-5  
Alarm Sounder Timeout ............ 4-2  
Alpha Descriptor........ 5-1, 5-3, 5-12  
Alpha Keypads.......................... 3-5  
Alpha Programming................... 3-1  
Alpha Vocabulary List.............. 5-11  
Arming Away............................. 6-5  
Arming Instant........................... 6-5  
Arming Modes........................... 6-5  
Arming Stay .............................. 6-5  
Audio Alarm Verification (AAV) 2-10  
Authority Levels......................... 6-4  
Auto-STAY Arming.................... 4-6  
Auxiliary Output......................... 2-5  
Factory Defaults ........................3-5  
Fast Busy Signal......................2-11  
Fault Delay Time .......................4-6  
Function Key Programming 1-2, 3-1,  
5-10  
Function Keys...................3-2, 5-10  
Fuse ..........................................8-1  
Q
Quick Arm Enable......................3-1  
R
Receiver and Transmitters.........3-2  
Relay Modules ....................1-2, 2-9  
Relay Programming ...................3-1  
Remote Keypads .......................1-1  
G
Report Code . 4-4, 4-5, 4-6,  
, 4-9,  
Go/No Go Test Mode.................7-2  
4-7  
5-2, 5-4, 6-1  
H
Report Code Formats ................6-1  
Reports In Armed Period............4-7  
response time  
RF Interference..........................2-7  
RF jam detection........................1-1  
RF Receiver2-1, 2-2, 2-3, 2-5, 2-7, 3  
RJ31X Jack.....................2-10, 2-11  
Handshake ................................6-1  
hardwired zones .................1-1, 6-6  
HAYES Modem .........................1-1  
House ID ..............2-8, 4-1, 8-2, 8-3  
..................... , 5-1  
4-6  
I
IBM Personal Computer ............3-1  
Ideal Model 61035 ...................2-5  
Input Device Type........5-4, 8-2, 8-3  
Installer Code .......3-5, 4-8, 7-1, 7-2  
Interior Follower...........3-3, 5-1, 5-8  
Interior w/Delay............3-3, 5-1, 5-8  
B
S
Backup Battery.......................... 1-1  
Battery Life................................ 2-8  
Battery Tests...................... 7-1, 7-2  
Bell Supervision ........................ 2-4  
Bell Supervision Jumper............ 2-4  
Bypassing Zones....................... 6-5  
Schedules................................5-14  
Security Codes ...................1-1, 6-4  
Silent Burglary .........3-4, 5-1, 5-8, 3  
Silent Panic................................6-5  
Smoke Detectors .......................8-2  
Sniffer Mode .......................5-3, 7-1  
sounder connections..................2-4  
Supervised Fire..........................3-3  
Supplementary Power................2-3  
Swinger Suppression .................4-7  
System Communication4-9, 5-2, 6-1  
System Operation5-4, 5-5, 5-8, 5-14  
System Status Report Codes.....4-4  
System Test...............................7-1  
K
keypad addresses ..............2-3, 3-1  
Keypad Programming Fields....4-11  
Keyswitch .............2-8, 2-9, 3-4, 5-1  
Kissoff ................................5-8, 6-1  
C
Cabinet...................................... 2-1  
California State Fire Marshall .... 2-5  
Caller ID Unit........................... 2-10  
Cancel Report Code.................. 4-5  
Character List.......................... 5-12  
Charging Voltage....................... 8-1  
Chime Mode..................... 4-10, 6-5  
Communication .. 5-10, 6-1, 7-2, 8-1  
Configurable Zone Type Options4-9  
Configurable Zone Type  
L
Lock...........................................2-1  
Long Range Radio. 1-1, 2-11, 4-3, 4-  
4, 3, 8-1  
Low Battery Message ................7-2  
M
Programming Fields.............. 4-9  
Contact ID Reporting................. 8-1  
Custom Words ......... 5-11, 5-12, 13  
macros ......................................1-1  
model 112..................................2-8  
Modem ...............................3-1, 6-6  
momentary switch......................2-8  
10-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Instructions  
T
V
Z
Tamper Switch ............ 2-8, 2-9, 9-2  
Telco Line ........................... 2-11, 3  
Test Mode.......................... 7-1, 7-2  
Test Restore Report Code......... 4-6  
Transmitter Battery Life............. 2-8  
Transmitter Input Types ............ 5-2  
Trouble by Day/......................... 3-3  
Trouble Displays................. 6-4, 6-6  
Vocabulary List........................5-11  
Zone Lists...........................3-1, 5-9  
Zone Programming Procedure...5-1  
Zone Types.......... 3-3, 5-1, 5-4, 5-8  
W
Wireless Key Templates............5-4  
Wiring Length/Gauge Chart .......2-3  
Wiring Run Chart.......................2-3  
Word String .............................5-12  
Worksheet.................................2-5  
10-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
}
H I  
Z O N E 6  
Z O N E 5  
L O  
L O  
H I  
H I  
Z O N E 4  
Z O N E 3  
L O  
L O  
H I  
H I  
Z O N E 2  
Z O N E 1  
L O  
L O  
H I  
Y S )  
4 O R T E L A  
( A N D / O R U P  
1 O 6 T A D D I T I O F N O A R L U R P F Z O N E S  
O P T I O N A L  
T U N S O E D  
O A U T A T  
) +  
A D D K E W Y : P Y E L L O  
A D  
O M K E I Y N A P T F A R D  
G R E E N :  
A D P W K R E ( Y P R E D :  
B L K  
2 )  
( T R I G .  
O U T P U T 1 8  
G N D  
X U + 1 2 A  
}
1 ) ( T R I G .  
O U T P U T 1 7  
O U N D A ( - D ) R G E R T K U E R Y C N P K : B L A  
Figure 17. Summary of Connections  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIMITED WARRANTY  
Honeywell International Inc., acting through its Security & Custom Electronics business ("Seller") 165 Eileen  
Way, Syosset, New York 11791, warrants its product(s) to be in conformance with its own plans and  
specifications and to be free from defects in materials and workmanship under normal use and service for 24  
months from the date stamp control on the product(s) or, for product(s) not having a manufacturer’s date stamp,  
for 12 months from date of original purchase unless the installation instructions or catalog sets forth a shorter  
period, in which case the shorter period shall apply. Seller's obligation shall be limited to repairing or replacing,  
at its option, free of charge for materials or labor, any product(s) which is proved not in compliance with Seller's  
specifications or proves defective in materials or workmanship under normal use and service. Seller shall have  
no obligation under this Limited Warranty or otherwise if the product(s) is altered or improperly repaired or  
serviced by anyone other than Honeywell factory service. Connection of any device(s) to a communicating bus of  
a Honeywell security system (e.g., keypad bus, polling loop) other than those manufactured or approved by  
Honeywell shall void this warranty. For warranty service, return product(s) transportation prepaid, to  
Honeywell Factory Service, 165 Eileen Way, Syosset, New York 11791.  
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, OF MERCHANTABILITY, OR FITNESS FOR A  
PARTICULAR PURPOSE OR OTHERWISE, WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF.  
IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES  
FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, OR UPON ANY OTHER BASIS OF  
LIABILITY WHATSOEVER, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER'S OWN NEGLIGENCE  
OR FAULT.  
Seller does not represent that the product(s) it sells may not be compromised or circumvented; that the  
product(s) will prevent any personal injury or property loss by burglary, robbery, fire or otherwise; or that the  
product(s) will in all cases provide adequate warning or protection. Customer understands that a properly  
installed and maintained alarm system may only reduce the risk of a burglary, robbery, fire, or other events  
occurring without providing an alarm, but it is not insurance or a guarantee that such will not occur or that  
there will be no personal injury or property loss as a result. CONSEQUENTLY, SELLER SHALL HAVE NO  
LIABILITY FOR ANY PERSONAL INJURY, PROPERTY DAMAGE OR OTHER LOSS BASED ON A CLAIM  
THAT THE PRODUCT(S) FAILED TO GIVE WARNING. HOWEVER, IF SELLER IS HELD LIABLE,  
WHETHER DIRECTLY OR INDIRECTLY, FOR ANY LOSS OR DAMAGE ARISING UNDER THIS LIMITED  
WARRANTY OR OTHERWISE, REGARDLESS OF CAUSE OR ORIGIN, SELLER'S MAXIMUM LIABILITY  
SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT(S), WHICH SHALL BE  
THE COMPLETE AND EXCLUSIVE REMEDY AGAINST SELLER.  
This warranty replaces any previous warranties and is the only warranty made by Seller on this product(s). No  
increase or alteration, written or verbal, of the obligations of this Limited Warranty is authorized.  
165 Eileen Way, Syosset, NY 11791  
Copyright © 2004 Honeywell International Inc.  
ÊK0735V3^Š  
K0735V3 10/04 Rev. B  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Baby Playpen ISPP007AE User Manual
Grizzly CD Player H5524 User Manual
Grizzly Drill H0626 User Manual
Grizzly Lathe G0709 User Manual
Grizzly Utility Trailer H6241 User Manual
Hotpoint Dishwasher FDYB 10011 User Manual
HP Hewlett Packard Computer Monitor 2011S User Manual
Humminbird Fish Finder 345c User Manual
IFoundry Systems Switch IFSYS 5651 MSP430 User Manual
i Tech Dynamic Headphones iSlider User Manual