Honeywell Automobile Battery Charger CHG 120 User Manual

Fire Control Instruments  
14-16 Southwest Park  
Westwood, MA 02090, USA  
Phone: (781) 471-3000  
FAX: (781) 471-3099  
CHG-120 Battery Charger  
Instruction Manual  
FCI P/N 9000-0572  
Document 52459  
11/22/04  
PN 52459:A  
Revision:  
A
ECN 04-691  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Adherence to the following will aid in problem-free  
installation with long-term reliability:  
Installation Precautions  
WARNING - Several different sources of power can be con-  
nected to the fire alarm control panel. Disconnect all sources  
of power before servicing. Control unit and associated equip-  
ment may be damaged by removing and/or inserting cards,  
Like all solid state electronic devices, this system may  
operate erratically or can be damaged when subjected to light-  
ning-induced transients. Although no system is completely  
immune from lightning transients and interferences, proper  
modules, or interconnecting cables while the unit is energized. grounding will reduce susceptibility. Overhead or outside  
Do not attempt to install, service, or operate this unit until this  
manual is read and understood.  
aerial wiring is not recommended, due to an increased sus-  
ceptibility to nearby lightning strikes. Consult with the Techni-  
cal Services Department if any problems are anticipated or  
encountered.  
CAUTION - System Reacceptance Test after Software  
Changes. To ensure proper system operation, this product  
must be tested in accordance with NFPA 72 Chapter 7 after  
any programming operation or change in site-specific soft-  
ware. Reacceptance testing is required after any change, ad-  
dition or deletion of system components, or after any modifica-  
tion, repair or adjustment to system hardware or wiring.  
Disconnect AC power and batteries prior to removing or in-  
serting circuit boards. Failure to do so can damage circuits.  
Remove all electronic assemblies prior to any drilling, filing,  
reaming, or punching of the enclosure. When possible, make  
all cable entries from the sides or rear. Before making modifi-  
cations, verify that they will not interfere with battery, trans-  
former, and printed circuit board location.  
All components, circuits, system operations, or software func-  
tions known to be affected by a change must be 100% tested.  
In addition, to ensure that other operations are not inadvert-  
ently affected, at least 10% of initiating devices that are not  
directly affected by the change, up to a maximum of 50 de-  
vices, must also be tested and proper system operation veri-  
fied.  
Do not tighten screw terminals more than 9 in-lbs.  
Over-tightening may damage threads, resulting in reduced  
terminal contact pressure and difficulty with screw terminal  
removal.  
Though designed to last many years, system components  
can fail at any time. This system contains static-sensitive  
components. Always ground yourself with a proper wrist strap  
before handling any circuits so that static charges are re-  
moved from the body. Use static-suppressive packaging  
to protect electronic assemblies removed from the unit.  
This system meets NFPA requirements for operation at  
0-49° C/32-120° F and at a relative humidity of 85% RH (non-  
condensing) at 30° C/86° F. However, the useful life of the  
system's standby batteries and the electronic components  
may be adversely affected by extreme temperature ranges  
and humidity. Therefore, it is recommended that this system  
and all peripherals be installed in an environment with a nomi-  
nal room temperature of 15-27° C/60-80° F.  
Follow the instructions in the installation, operating, and  
programming manuals. These instructions must be followed  
to avoid damage to the control panel and associated  
equipment. FACP operation and reliability depend upon  
proper installation by authorized personnel.  
Verify that wire sizes are adequate for all initiating and  
indicating device loops. Most devices cannot tolerate more  
than a 10% I.R. drop from the specified device voltage.  
FCC Warning  
Canadian Requirements  
WARNING: This equipment generates, uses, and can  
radiate radio frequency energy and if not installed and  
used in accordance with the instruction manual, may  
cause interference to radio communications. It has  
been tested and found to comply with the limits for class  
A computing device pursuant to Subpart B of Part 15 of  
FCC Rules, which is designed to provide reasonable  
protection against such interference when operated in a  
commercial environment. Operation of this equipment in  
a residential area is likely to cause interference, in which  
case the user will be required to correct the interference  
at his own expense.  
This digital apparatus does not exceed the Class A  
limits for radiation noise emissions from digital  
apparatus set out in the Radio Interference Regulations  
of the Canadian Department of Communications.  
Le present appareil numerique n'emet pas de bruits  
radioelectriques depassant les limites applicables aux  
appareils numeriques de la classe A prescrites dans le  
Reglement sur le brouillage radioelectrique edicte par le  
ministere des Communications du Canada.  
LimWarLg.p65 01/10/2000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Introduction to the Charger....................................................................................... 1  
Overview................................................................................................................... 1  
Specifications............................................................................................................ 2  
Compliance with NFPA Codes and UL Standards................................................... 2  
Charger Maintenance................................................................................................ 2  
Installing the Charger................................................................................................. 3  
Overview................................................................................................................... 3  
Installation Precautions and Standards ..................................................................... 3  
Battery Precautions............................................................................................... 3  
Installation Standards............................................................................................ 4  
Charger Connections, Jumpers, and Switches .......................................................... 4  
Connecting AC Power to the Charger ...................................................................... 5  
Connecting Batteries to the Charger......................................................................... 6  
Mounting the Charger............................................................................................... 8  
Mounting the Charger into a CAB-X3 Series Cabinet ......................................... 8  
Mounting the Charger into a BB-55 Battery Box................................................. 9  
Connecting the Charger to a Load .......................................................................... 10  
Connecting the Charger to a Multiple Load ....................................................... 10  
Adding the Charger for Additional Current.........................................................11  
Configuring the Charger ......................................................................................... 12  
Delay loss of AC Reporting................................................................................ 12  
Disable Ground Fault Detection......................................................................... 12  
Trouble and Form-C Relay Connections (Optional) .............................................. 13  
Installing Optional Meters ...................................................................................... 14  
Installing an AM-1.............................................................................................. 14  
Installing a VM-1................................................................................................ 14  
Operating the Charger.............................................................................................. 15  
Overview................................................................................................................. 15  
Starting the Charger ................................................................................................ 15  
Understanding the LED Status Indicators............................................................... 15  
Normal Operation ................................................................................................... 16  
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
v
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
vi  
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Introduction to the Charger  
Overview  
The CHG-120 battery charger is designed to charge lead-acid batteries that provide  
emergency standby power for a Fire Alarm Control Panel (FACP). Two 12-volt batteries  
are always used in series to supply 24 VDC nominal. The following list gives answers to  
some common questions about the charger:  
Note: Throughout this manual,  
the term “charger” refers to a  
CHG-120.  
What types of FACPs can be used with the charger? Any 24 VDC FACP that uses  
lead-acid 25 AH to 120 AH batteries and that has the feature to disable the FACP  
battery charger.  
Where does the charger mount? You can mount the charger into a CAB-X3 Series  
Cabinet or into a BB-55 Battery Box.  
How many outputs does the charger provide? The charger provides two output  
circuits for connection to multiple loads (such as a power supply, amplifier, auxiliary  
amplifier, and so forth).  
What options are available with the charger? You can configure the charger to  
disable the charger’s ground fault detection, to delay AC loss reporting (8 or 16 hours),  
and to operate with 120 VAC or 240 VAC.  
How long does it take the charger to charge batteries? Typically, it takes 9 hours to  
charge 25 AH batteries, 20 hours to charge 60 AH batteries, and up to 48 hours to  
charge 120 AH batteries. Refer to “Specifications” on page 2 for details.  
Figure 1 identifies features of the charger:  
Note: For detailed descriptions of charger connections, jumpers, and  
switches, see “Charger Connections, Jumpers, and Switches” on page 4.  
Nine LED status  
indicators  
Heavy duty primary  
AC power  
connections  
Open collector trouble daisy chain  
connections  
Voltage Selection Switch  
for 120 VAC or 240 VAC  
operation  
External trouble  
input  
Form-C trouble relay to  
other devices  
Two output circuits to  
load (power supply,  
auxiliary power supply,  
amplifiers, etc.)  
15 A replaceable fuses provide  
short circuit and overload  
protection  
25 AH – 120 AH battery  
connections  
Optional Ammeter  
connection  
Figure 1 Charger Features  
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction to the Charger  
Specifications  
The charger also provides the following features:  
AM-1 ammeter (0-10A) ordered separately  
VM-1 voltmeter (0-50 V) ordered separately  
Disable local ground fault detection  
Selectable loss of AC delay (8 or 16 hours)  
Specifications  
Table 1 contains electrical specifications for the charger:  
Primary AC power in (TB1)  
120 VAC, 60 Hz, 2 A  
240 VAC, 50 Hz, 1 A  
5 A at 30 VDC  
27.6 VDC  
Form-C relay (TB3)  
Float charge voltage  
Maximum charging current  
Fuses F1-F3 (PN 12057)  
Battery sizes  
4.5 A  
15 A  
25 AH to 120 AH  
Charging Time (to charge two fully discharged  
batteries  
25 AH – 9 hours  
55 AH/60 AH – 20 hours  
120 AH – 38 hours  
Table 1 Charger Specifications  
Compliance with NFPA Codes and UL Standards  
The charger complies with the following standards:  
NFPA 72-1993 National Fire Alarm Code  
UL 864 Standard for Control Units for Fire Alarm Systems and UL 1481 Power  
Supplies for Fire Alarm Systems  
CAN/ULC-S527-M87  
Charger Maintenance  
The charger does not require regular maintenance. While installing the charger, however,  
make sure to maintain proper polarity when connecting power leads and battery  
connections. To ensure optimal operation of the charger, observe the following:  
Overload and reverse-polarity protection Fuses F1, F2 and F3 (15 A, PN 12057) provide  
overload and reverse-polarity protection. Replace a blown fuse with a fuse with the same  
rating and type.  
Periodic Inspection Periodically inspect the batteries for corrosion and make sure that  
corrosive effects to the batteries do not affect the charger or cabinet.  
Troubleshooting Most problems with a charger are due to faulty batteries or loose  
connections. If you encounter problems, inspect the charger, the battery, and all  
connections for loose wiring or short circuits.  
Replacing Batteries Only replace batteries with the same charge rate and capacity as  
other batteries in the set. For example, if replacing one of four 60 AH batteries, make sure  
the replacement battery has the same charge rate and capacity as the other three batteries.  
2
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installing the Charger  
Overview  
This section contains instructions and illustrations for installing the charger, divided into  
the following topics:  
Section  
Topic(s) Covered  
Page  
InstallationPrecautions and Precautions to take when installing the charger  
3
Standards  
and recommended installation standards.  
Charger Connections,  
Jumpers, and Switches  
Location and references to connections,  
jumpers, and switches used to configure,  
maintain, and operate the charger.  
4
Connecting AC Power to  
the Charger  
How to connect AC power to the charger.  
5
6
Connecting Batteries to the  
Charger  
How to connect batteries to the charger in two  
configurations: using two batteries and using  
four batteries.  
Mounting the Charger  
How to mount the charger to a CAB-X3.  
How to mount the charger to a BB-55.  
8
Connecting the Charger to  
a Load  
Instructions and illustrations for wiring a charger  
to a multiple load and for wiring a charger for a  
large system installation.  
10  
Configuring the Charger  
Configuring the charger for the following  
options:  
Delaying loss of AC reporting (DACT); and  
Disabling ground fault detection  
12  
13  
Trouble and Form-C Relay  
Connections (Optional)  
Instructions and illustrations for connecting the  
following:  
Open Collector Trouble In (JP5)  
Trouble Out (JP4)  
Master Trouble In (JP6)  
Form-C Trouble Relay (TB3)  
Installing Optional Meters  
How to install an optional ammeter, voltmeter,  
or both.  
14  
Table 2 Installation Topics  
Installation Precautions and Standards  
Battery Precautions When installing the charger, observe the following precautions:  
!
Observe polarity when making connections.  
Do not connect the Battery Interconnect Cable until instructed.  
Batteries, although sealed, contain hazardous acid chemicals.  
Charging batteries can cause flammable hydrogen gas.  
Take care when handling batteries: batteries are heavy—take care in lifting and  
handling them.  
Mounting batteries requires proper mounting hardware. Follow the battery  
manufacture’s installation instructions  
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the Charger  
Charger Connections, Jumpers, and Switches  
Installation Standards An installer should be familiar with the following standards:  
NEC Article 300 Wiring Methods.  
NEC Article 760 Fire Protective Signaling Systems.  
Applicable Local and State Building Codes.  
Requirements of the Authority Having Jurisdiction.  
Charger Connections, Jumpers, and Switches  
Figure 2 show all connections, jumpers, and switches needed to maintain, configure, and  
operate the charger:  
JP4 – Open Collector Trouble Out  
and JP5 – Open Collector Trouble In  
(see “Trouble and Form-C Relay  
LED Status Indicators – Nine LEDs to  
indicate status of the charger (see  
“Understanding the LED Status  
Indicators” on page 15)  
Connections (Optional)” on page 13)  
JP6 – Master Trouble In  
(see “Trouble and Form-C  
Relay Connections  
(Optional)” on page 13)  
TB1 – AC Power (120 VAC  
or 240 VAC (see  
“Connecting AC Power to  
the Charger” on page 5)  
TB3 – Form-C Trouble Relay  
(see “Trouble and Form-C  
Relay Connections (Optional)”  
on page 13)  
TB2 – Output Circuits  
1 and 2 (see  
“Connecting the  
Charger to a Load” on  
page 10)  
SW1 Voltage Selection  
Switch for selecting 120  
VAC or 240 VAC operation  
(See Figure 3 on page 5)  
TB2 – Battery  
Connections (see  
“Connecting Batteries to  
the Charger” on page 6)  
Resistor R104 – Cut to  
disable ground fault  
detection (refer to “Disable  
Ground Fault Detection” on  
page 12)  
Resistor R100 – Used  
with JP8 to delay loss of  
AC reporting (refer to  
“Delay loss of AC  
Fuses F1, F2, and F3 – Replaceable  
plugged fuses (see “Charger  
Maintenance” on page 2)  
Reporting” on page 12)  
JP3 (AM-1 connector) and JP9 for  
enabling an optional AM-1  
ammeter. (see “Installing an AM-1”  
on page 14)  
Figure 2 Charger Connections, Switches, and Jumpers  
4
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connecting AC Power to the Charger  
Installing the Charger  
Connecting AC Power to the Charger  
Caution: Before connecting AC power to the charger—make sure to set the Voltage Select  
Switch (SW1) on the charger (Figure 2) to match your AC power source (120 VAC or 240  
VAC). Figure 3 shows the voltage selection positions for SW1:  
Note: The charger is rated  
for 120 VAC or 240 VAC  
operation. Therefore, 115V  
on SW1 indicates 120 VAC  
operation; and 230V,  
indicates 240 VAC  
operation.  
SW1 set to 120 VAC  
operation  
SW1 set to 240 VAC  
operation  
Figure 3 Using SW1 to Select AC Voltage  
Figure 4 shows the steps for connecting the charger to the main AC power source.  
Plastic  
Earth ground (EARTH)  
insulating cover  
(PN 02114)  
TB1  
TB1  
Step 2: Connect the Earth ground line to  
TB1.  
Step 1: Remove the plastic insulating cover  
from TB1.  
Primary Hot line in (HOT)  
Earth ground (EARTH)  
Earth ground (EARTH)  
Neutral line in (NUTRL)  
Neutral line in (NUTRL)  
TB1  
TB1  
Step 4: Connect the Primary Hot line to TB1.  
Check all connections, then replace the  
plastic insulating cover.  
Step 3: Connect the Primary Neutral line to  
TB1.  
Figure 4 Connecting AC Power to the Charger  
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the Charger  
Connecting Batteries to the Charger  
Connecting Batteries to the Charger  
Overview you can connect 25 AH –120 AH batteries to the charger. This section provides  
illustrations and instructions for connecting two batteries or for connecting four batteries.  
Connecting Two Batteries Figure 5 shows how to connect two 25 AH batteries to the  
charger:  
TB1  
TB2  
CHG-120  
Warning: Do not  
connect the Battery  
!
Power Supply  
Interconnect Cable  
at this time.  
Refer to “Starting the  
Charger” on page 15.  
Figure 5 Connecting 25 AH Batteries  
Table 3 contains instructions for connecting batteries to the charger:  
Step  
Action  
1
2
Remove all power sources to the charger.  
Connect the battery negative cable to the TB2 terminal (on the charger  
labeled “Battery –” as shown in Figure 5.  
3
4
Connect the battery positive cable to the TB2 terminal (on the charger)  
labeled “Battery +” as shown in Figure 5.  
Proceed to the section “Connecting the Charger.” Do not connect the Battery  
Interconnect Cable at this time—refer to “Starting the Charger” on page 15.  
Table 3 Connecting 25 AH Batteries  
6
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connecting Batteries to the Charger  
Installing the Charger  
Connecting Four Batteries Figure 6 shows how to connect four 55 AH batteries to the  
charger:  
TB1  
TB2  
Warning: Do not  
Charger  
!
connect the Battery  
Interconnect Cable  
at this time.  
Power Supply  
Refer to “Starting the  
Charger” on page 15.  
Figure 6 Connecting Four Batteries to a Charger  
Table 4 contains instructions for connecting four batteries to the charger:  
Step  
Action  
1
2
Remove all power sources to the charger.  
Tie the batteries in pairs by connecting the battery negative terminals and the  
battery positive terminals as shown in Figure 6.  
3
4
5
Connect the battery negative cable to the TB2 terminal (on the charger labeled  
“Battery –”) as shown in Figure 6.  
Connect the battery positive cable to the TB2 terminal (on the charger) labeled  
“Battery +”) as shown in Figure 6.  
Proceed to the section “Connecting the Charger.” Do not connect the Battery  
Interconnect Cable at this time—refer to “Starting the Charger” on page 15.  
Table 4 Connecting 55 AH Batteries  
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the Charger  
Mounting the Charger  
Mounting the Charger  
Mounting the Charger into a CAB-X3 Series Cabinet You can mount a charger into the  
bottom row of a CAB-X3 Series Cabinet, as long as the charger is within 20 feet of the  
load. Typically, a charger mounts into the lower right corner of the CAB-X3—beside the  
power supply (Figure 7, position 2). If using an additional CAB-X3, you can mount the  
charger in the lower left corner (Figure 7, position 2). Figure 7 shows the two mounting  
positions of a charger into a CAB-X3.  
Mounting  
hooks  
Position 1: Lower right corner.  
Position 2: Lower left corner.  
Figure 7 Mounting a Charger into a CAB-X3 (CAB-C3 shown)  
To mount a charger into a CAB-X3 Series Cabinet, follow these instructions:  
Step  
Action  
1
Place the charger chassis mounting slots in line with the mounting holes in the cabinet. If  
mounting in position 2, place the charger chassis onto the mounting hooks in the cabinet.  
2
Insert the self-tapping screws through the charger chassis mounting slots and into the  
mounting holes in the cabinet.  
Chassis mounting  
slot  
Self-tapping screw  
3
Tighten the self-tapping screws.  
8
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting the Charger  
Installing the Charger  
Mounting the Charger into a BB-55 Battery Box You can also mount a charger into a  
BB-55 battery box, as long as the BB-55 is within 20 feet of the load. Note that a charger  
takes up half the space of the BB-55. This means you only have room left for two 25 AH  
batteries in the BB-55. Figure 8 shows the mounting position of a charger in a BB-55.  
Optional bracket for  
mounting an optional  
AM-1 or VM-1  
Self-tapping screws  
Figure 8 Mounting a Charger into a BB-55  
To mount a charger into a BB-55 battery box, follow these instructions:  
Step  
Action  
1
2
Place the charger chassis mounting slots in line with the mounting holes in the BB-55.  
Insert the self-tapping screws through the charger chassis mounting slots and into the  
mounting holes in the BB-55.  
Chassis mounting  
slot  
Self-tapping screw  
3
Tighten the self-tapping screws.  
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the Charger  
Connecting the Charger to a Load  
Connecting the Charger to a Load  
This section provides two applications for connecting a charger to a load. While connecting  
a charger to a load, observe the following precautions:  
Make sure all power sources are off to the charger and the load.  
Follow polarity when making connections.  
Connecting the Charger to a Multiple Load You can connect a charger to multiple  
loads, such as a main power supply, auxiliary power supply, amplifiers, and so forth, as  
shown in Figure 9.  
Power Supply  
Note: Figure 10 shows a  
wiring diagram for tying the  
load to battery terminals to  
obtain additional current. For  
example, the first AA-120  
draws 7 A, the daisy-chained  
Generic Audio Amplifiers  
draw 7 A, and the second  
AA-120 draws 7 A of  
additional current from the  
batteries.  
CHG-120  
Generic Audio  
Amplifier  
Figure 9 Typical Wiring for a Charger to a Multiple Load  
To connect a charger as shown in Figure 9, follow these steps:  
Step  
Action  
1
Connect the battery+ and battery– terminals of the power supply to the charger  
output circuit (TB2: Out 1+ and Out 1–) as shown in Figure 9.  
2
3
Connect the battery+ and battery– terminals of the amplifier to the charger  
output circuit (TB2: Out 2+ and Out 2–) as shown in Figure 9.  
Connect the batteries to the charger (for battery connections see Figure 5 or  
Figure 6).  
10  
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connecting the Charger to a Load  
Installing the Charger  
Adding the Charger for Additional Current Due to internal fuses, the maximum alarm  
current that can be drawn from the batteries and passed through the charger’s two output  
circuits is limited to 10 amps maximum (each circuit). The PS-12600 batteries, however,  
are capable of supplying up to 45 amps of current in alarm. The remaining 25 amps of  
alarm current can be drawn directly from the battery terminals to supply Notification  
Appliance Circuits, control modules and other alarm devices as illustrated in Figure 10:  
First  
AA-120  
Charger  
Power Supply  
First  
Generic  
Audio Amp  
Second  
Generic  
Audio Amp  
55 AH/60 AH  
12 VDC  
55 AH/60 AH  
12 VDC  
Second  
AA-120  
55 AH/60 AH  
12 VDC  
55 AH/60 AH  
12 VDC  
Figure 10 Typical Connections for Drawing Additional Current  
To connect a charger as shown in Figure 10, follow these steps:  
Step  
Action  
1
Connect the Battery+ and Battery– terminals of the power supply to the charger  
Battery output (TB2: Batt 1+ and Batt 1–) as shown in Figure 10.  
2
3
4
5
6
Connect the Battery+ and Battery– terminals of the first AA-120 to the charger  
output circuit (TB2: Out 2+ and Out 2–) as shown Figure 10.  
Connect the Battery+ and Battery– terminals of the first Generic Audio Amp to  
the charger output circuit (TB2: Out 1+ and Out 1–) as shown in Figure 10.  
Connect the Battery+ and Battery– terminals of the second Generic Audio Amp to  
the Battery+ and Battery– terminals of the first Audio Amp as shown in Figure 10.  
Connect the Battery+ and Battery– terminals of the second AA-120 to the  
batteries as shown in Figure 10.  
Connect the batteries to the charger.  
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the Charger  
Configuring the Charger  
Configuring the Charger  
You can configure the charger to do the following:  
Set the charger input power (see Figure 3 on page 5).  
Delay AC loss reporting (for Central Station applications); and  
Disable charger ground fault detection.  
Figure 11 shows how to configure the charger for delaying the loss of AC reporting and for  
disabling ground fault detection:  
Disable ground fault detection  
cut and remove R104  
Delay loss of AC (16 hrs) cut and  
remove R100, in addition to  
cutting JP8  
Delay loss of AC (8 hrs) cut JP8  
Figure 11 Configuring the Charger  
Delay loss of AC Reporting If using a Digital Alarm Communicator (DACT), you must  
delay the reporting of an AC loss condition to a central station. This delays activation of the  
trouble bus and Form-C trouble contacts when AC fails. You can configure the charger for  
an 8-hour or a 16-hour delay as follows:  
8-hour delay – Cut and remove jumper JP8 on the charger (Figure 11).  
16-hour delay – Cut jumper JP8; then, cut and remove resistor R100 (Figure 11).  
Disable Ground Fault Detection To disable local (charger) earth fault detection, cut and  
remove resistor R104 (Figure 11). Figure 12 contains a simplified block diagram that  
shows ground fault detection disabled on a charger connected to multiple power supplies:  
On the charger,  
disable ground fault  
detection (cut R104).  
Charger  
On Power Supply #1,  
enable ground fault  
detection.  
On Power Supply #2 and  
#3, disable ground fault  
detection.  
Power  
Power  
Power  
Supply  
Supply  
Supply  
# 2  
# 3  
# 1  
Figure 12 Disabling Ground Fault Detection  
12  
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Trouble and Form-C Relay Connections (Optional)  
Installing the Charger  
Trouble and Form-C Relay Connections (Optional)  
Table 5 contains descriptions of optional connectors on the charger:  
Function  
Connector  
Use open collector input and output to daisy  
chain a trouble signal through the charger  
without affecting charger operation.  
JP5 Open Collector Trouble In  
JP4 Open Collector Trouble Out  
Receive trouble signals from another device,  
such as a Control Module.  
JP6 Master Trouble In  
Transmit a charger trouble signal to another  
device.  
TB3 Form-C Trouble Relay  
Table 5 Charger Trouble and Form-C Relay Connections  
Figure 13 shows charger trouble and Form-C relay connections:  
Figure 13 Connections for Optional Devices  
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the Charger  
Installing Optional Meters  
Installing Optional Meters  
You can also order and install a ammeter (AM-1) or voltmeter (VM-1) for use with the  
charger. If mounting an AM-1 or a VM-1, mount the meter to a BB-55 as shown in Figure  
14. Table 6 contains descriptions and part numbers for these optional meters:  
Item  
Part Number  
Description  
Ammeter  
AM-1  
0-10 A ammeter with a 3-ft. cable for connection to the  
charger (JP3). Mounts into a BB-55 battery box only.  
Voltmeter  
VM-1  
0-50 V voltmeter with 3-ft. positive and negative leads  
for connection to the charger output circuit. Mounts  
into a BB-55 battery box only.  
Table 6 Optional Meters  
Installing an AM-1 To install an AM-1, follow these steps:  
1. Cut jumper JP9 on the charger (Figure 13).  
2. Connect the AM-1 harness to JP3 on the charger (Figure 11)—making sure to observe  
proper polarity.  
3. Mount the AM-1 into a mounting slot on the front of the BB-55 (Figure 14):  
AM-1 or VM-1  
(BB-55 only)  
BB-55 Mounting Slot  
Figure 14 Mounting an AM-1 or VM-1 to a BB-55 Battery Box  
Installing a VM-1 You can connect a VM-1 across a charger output circuit. For example,  
to install a VM-1 to measure voltage from charger output circuit 1, follow these steps:  
1. Connect the positive lead to TB2 Out 1 (+). See Figure 13.  
2. Connect the negative lead to TB2 Out 1 (–). SeeFigure 13.  
3. Mount the VM-1 into a mounting slot on the front of the BB-55 battery box.  
14  
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Operating the Charger  
Overview  
This section contains information on starting the charger, interpreting the LED Status  
Indicators on the charger, and normal operation of the charger.  
Starting the Charger  
Warning: Before starting the charger, do the following:  
!
Follow the installation instructions in Section 2, “Installing the Charger.”  
Verify proper polarity on all connections between the charger and the batteries, load,  
and optional meters.  
Make sure there are no short circuits between leads and between battery terminals.  
Make sure the Battery Interconnect Cable(s) is not connected.  
To start the charger, follow these steps:  
4. Connect AC power to the charger. The AC On LED and Trouble LED go on.  
5. Connect the batteries to the charger  
6. Connect the Battery Interconnect Cable. The Trouble LED goes off.  
7. Connect the charger to the load (such as a power supply, an amplifier, and so on).  
Understanding the LED Status Indicators  
The charger provides nine LED Status Indicators, which are identified in Figure 15. Also  
refer to Table 7 for conditions, such as troubles, that cause LEDs to light.  
AC On Primary AC on  
Trouble Charger in trouble condition (see Table 7)  
Ground Fault Earth fault condition detected  
HI Charge Charging current greater than 400 mA  
LO Charge Charging current less than 400 mA (loss of AC)  
27V Battery voltage greater than 27 VDC  
25V Battery voltage between 25-27 VDC  
23V Battery voltage between 23-25 VDC  
Low Battery Battery voltage less than 23 VDC  
Green LED  
Yellow LED  
Figure 15 LED Status Indicators  
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operating the Charger  
Normal Operation  
Table 7 shows the conditions that cause the charger LEDs to come on:  
LED  
AC On  
H
H
H
H
H
H
I
H
H
H
H
H
Trouble  
H
H
H
H
Ground Fault  
HI Charge  
I
I
I
I
I
I
I
LO Charge  
(Loss of AC)  
H
H
H
I
27 V  
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
25 V  
23 V  
Low Battery  
H
H
Legend:  
H LED on.  
I LED on or off, depending on battery voltage. Refer to “Normal Operation.”  
Table 7 LED Status Indicators  
Normal Operation  
The CHG-120 charges batteries at 4.5 A. When batteries are fully charged, the charger  
maintains a float charge of 27.6 VDC at a trickle charge rate of less than 400 mA. While  
charging the batteries, the HI and LO Charge LEDs switch on and off approximately every  
20 seconds. Also, one of the 23 V, 25 V, 27 V, or Low Battery LEDs also comes on,  
depending on the battery voltage.  
16  
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
A
LED status indicators 4, 15  
AC loss reporting 1, 4, 12  
AC Power 4  
M
meters  
AC power connections 5  
AM-1  
installation 14  
AM-1 ammeter 2  
AM-1 connector 4  
B
installation 14  
mounting 1  
BB-55 9  
CAB-X3 8  
N
NFPA Codes 2  
normal operation 16  
O
batteries 1  
battery  
25 AH connection 6  
connecting four 7  
battery charger 1  
battery connections 4, 6  
battery replacement 2  
battery sizes 2  
C
operation 15  
normal 16  
options 1  
outputs 1, 4  
Overview 1  
P
Precautions 3  
primary power 1, 2  
protection  
overload & reverse-polarity 2  
R
relay 2, 4  
connections 13  
S
charger 1  
additional current 11  
connecting to FACP 11  
connecting to load 10  
connecting to multiple load 10  
operation 15  
starting 15  
Charger Maintenance 2  
charger voltage 2  
charging current 2  
Charging Time 2  
compatibility 1  
configuring charger 12  
connections 4  
F
Specifications 2  
starting charger 15  
switches 4  
T
trouble  
connections 13  
Trouble In 4  
Trouble Out 4  
troubleshooting 2  
U
FACP compatibility 1  
Features 1  
Fuses 2  
fuses 4  
UL Standards 2  
V
G
VM-1  
ground fault detection 1, 4, 12  
I
inspection 2  
installation 3  
precautions 3  
standards 4  
installation 14  
VM-1 voltmeter 2  
Voltage Select Switch 5  
voltage selection 4  
J
jumpers 4  
L
LED  
status 16  
CHG-120 Instruction 11/22/04 PN: 52459:A FCI P/N:9000-0572  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Limited Warranty  
The manufacturer warrants its products to be free from defects in materials and workmanship  
for eighteen (18) months from the date of manufacture, under normal use and service. Products  
are date-stamped at time of manufacture. The sole and exclusive obligation of the manufacturer  
is to repair or replace, at its option, free of charge for parts and labor, any part which is  
defective in materials or workmanship under normal use and service. For products not under  
the manufacturer's date-stamp control, the warranty is eighteen (18) months from date of  
original purchase by the manufacturer's distributor unless the installation instructions or catalog  
sets forth a shorter period, in which case the shorter period shall apply. This warranty is void  
if the product is altered, repaired, or serviced by anyone other than the manufacturer or its  
authorized distributors, or if there is a failure to maintain the products and systems in which  
they operate in a proper and workable manner. In case of defect, secure a Return Material  
Authorization form from our customer service department. Return product, transportation  
prepaid, to the manufacturer.  
This writing constitutes the only warranty made by this manufacturer with respect to its  
products. The manufacturer does not represent that its products will prevent any loss by fire  
or otherwise, or that its products will in all cases provide the protection for which they are  
installed or intended. Buyer acknowledges that the manufacturer is not an insurer and assumes  
no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse,  
abuse, accident, or similar incident.  
THE MANUFACTURER GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF  
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE  
WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER  
NO CIRCUMSTANCES SHALL THE MANUFACTURER BE LIABLE FOR ANY LOSS  
OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL, OR CONSEQUENTIAL,  
ARISING OUT OF THE USE OF, OR INABILITY TO USE THE MANUFACTURER'S  
PRODUCTS. FURTHERMORE, THE MANUFACTURER SHALL NOT BE LIABLE FOR  
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR  
AS A RESULT OF, PERSONAL, COMMERCIAL, OR INDUSTRIAL USE OF ITS  
PRODUCTS.  
This warranty replaces all previous warranties and is the only warranty made by the  
manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty  
is authorized.  
LimWarLg.p65 01/10/2000  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Greenheck Fan Ventilation Hood CFSD XXX Series User Manual
Grundig Stereo System UMS 5800 DEC User Manual
Haier Refrigerator 16 User Manual
Harbor Freight Tools Stove 44894 User Manual
Hoshizaki Ice Maker KM2100SRH350 User Manual
HP Hewlett Packard Electric Heater 11744195 User Manual
Hunter Fan Fan 21322 User Manual
Igloo MP3 Player MPK1066UKAB User Manual
IKEA Indoor Furnishings AA 68273 2 User Manual
IKEA Indoor Furnishings AA 250875 1 User Manual