Heat Glo LifeStyle Indoor Fireplace BW36 User Manual

No one builds a better fire  
Heat-N-Glo, a Division of Hearth Technologies Inc.  
20802 Kensington Blvd.  
Lakeville, MN 55044  
BW36  
BW36C  
WOODBURNING FIREPLACE  
INSTALLATION & OPERATING  
INSTRUCTIONS  
FOR RESIDENTIAL USE  
Model BW36 shown.  
558-900-D-4/00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
No one builds a better fire  
A. LISTINGS AND CODE APPROVALS  
The BW36 Series fireplace system has been tested  
and listed in accordance with the UL127 Standards,  
and has been listed by Underwriters Laboratories Inc.  
for installation and operation in the United States as  
described in these Installation & Operating  
Instructions.  
Check with your local Building Code agency prior to  
installing this fireplace to ensure compliance with local  
Codes, including the need for permits and follow-up  
inspections. If any assistance is required during  
installation, please contact your local dealer or the  
Heat-N-Glo Technical Services Department, 20802  
Kensington Blvd., Lakeville, MN 55044.  
The BW36 Series fireplaces have been tested and  
listed for use with the optional components given on  
page 4. These optional components may be pur-  
chased separately and installed at a later date.  
However, installation of an outside air kit will require  
significant reconstruction, and should be installed at  
the time of the initial fireplace installation.  
Heat-N-Glo is a Division of Hearth Technologies Inc.  
WARNING!  
THIS HEAT-N-GLO FIREPLACE AND ITS COMPONENTS ARE DESIGNED TO BE  
INSTALLED AND OPERATED AS A SYSTEM. ANY ALTERATION TO OR  
SUBSTITUTION FOR ITEMS IN THIS SYSTEM, UNLESS ALLOWED BY THESE  
INSTALLATION INSTRUCTIONS, WILL VOID THE UNDERWRITERS LABORATORIES  
LISTING AND MAY VOID THE PRODUCT WARRANTY. IT MAY ALSO CREATE A  
HAZARDOUS INSTALLATION.  
READ THROUGH THESE INSTRUCTIONS THOROUGHLY BEFORE STARTING YOUR  
INSTALLATION AND FOLLOW THEM CAREFULLY THROUGHOUT YOUR PROJECT!  
B. DESCRIPTION OF THE FIREPLACE SYSTEM  
The HEAT-N-GLO fireplace system consists of the following:  
1. Fireplace/Integral Grate  
2. Hearth Extension  
3. Chimney System  
4. Chimney Termination Cap  
Optional components include:  
1. Glass Doors  
3. Heat Circulating Fans  
2. Outside Combustion Air System  
Tools and Building Supplies Normally  
Required:  
NOTE: Illustrations throughout these  
instructions reflect “typical installations”  
and are for design purposes only. Actual  
installation may vary slightly due to indi-  
vidual design preferences. However, min-  
imum and maximum clearances must be  
maintained at all times.  
Tools  
Building Supplies  
Saw  
Pliers  
Hammer  
Hearth Extension Material  
Wall-finishing Materials  
Framing Material  
Phillips Screwdriver Fireplace Surround  
Tape Measure  
Plumb Line  
Caulking Material  
The illustrations and diagrams used  
throughout these installation instructions  
are not drawn to scale.  
Level  
Electric Drill and Bits  
Framing Square  
4-00  
3
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
No one builds a better fire  
C. FIREPLACE SYSTEM COMPONENTS  
The table below, together with the following pictures, show only those components which may be safely used  
with this fireplace.  
HTI Catalog #  
Description  
BW36*  
BW36C*  
Radiant Fireplace, includes integral grate and hearth protection strips  
Heat Circulating Fireplace, includes integral grate and hearth  
protection strips  
HX3  
Hearth Extension  
DM1036  
DM1036A  
DM1036B  
GR16  
AK22  
Glass Doors - Original Series, Black  
Glass Doors - Original Series,Brushed Brass Finish  
Glass Doors - Original Series, Polished Brass Finish  
Integral Grate (included with Fireplace)  
Outside Air Kit  
FK22  
BC10  
Fan Kit with electrical junction box (BW36C ONLY)  
Fan motor rheostat control  
JK9  
ID4  
Electrical Junction Box (BW36C ONLY)  
Insulated Duct/Outside Air  
UD4  
Uninsulated Duct/Outside Air  
Chimney Section - 6” long  
Chimney Section - 12” long  
Chimney Section - 18” long  
Chimney Section - 24” long  
Chimney Section - 36” long  
Chimney Section - 48” long  
Chimney Stabilizer  
SL306  
SL312  
SL318  
SL324  
SL336  
SL348  
SL3  
SL315  
SL330  
FS338  
FS339  
FS340  
AS8  
JB877  
CB876  
RF370  
RF371  
TR342  
TR344  
ST375  
TS345  
TS345P  
CT35  
Chimney Offset/Return - 15°  
Chimney Offset/Return - 30°  
Firestop - Straight  
Firestop - 15°  
Firestop - 30°  
SL300 Straight Attic Insulation Shield, 24"  
Chimney Joint Band  
Chimney Bracket  
Roof Flashing - Flat to 6/12 Pitch  
Roof Flashing - 6/12 to 12/12 Pitch  
Telescoping Chimney Terminal Cap - Round  
Chimney Terminal Cap - Round (Storm collar included)  
Chimney Terminal Cap - Square  
Chimney Terminal Cap - Square  
Chimney Terminal Cap - Square (Painted)  
Chase Top  
LDS33  
LDS46  
Decorative Shroud - 3’ x 3’  
Decorative Shroud - 4’ x 6’  
*Heat-N-Glo Part Number  
4-00  
4
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
No one builds a better fire  
217/8  
"
183/4  
"
335/8  
327/8  
"
21"  
8"  
"
111/2  
"
71/4  
"
5
/
8"  
33/4  
71/4  
107/8  
"
36"  
6"  
1"  
385/8  
"
"
BW36C  
"
335/8  
"
327/8  
"
21"  
6"  
36"  
385/8  
"
BW36  
HEARTH EXTENSIONS  
GLASS DOORS  
STRAIGHT ATTIC  
INSULATION SHIELD  
16"  
52"  
193/4  
"
24"  
HX3  
BI-FOLD DOORS  
351/2  
"
AS8  
DM1036  
INSULATED DUCT  
INTEGRAL GRATES  
93/8  
"
4"  
4"  
42"  
ID4  
175/8  
"
UNINSULATED DUCT  
OUTSIDE AIR KIT  
GR16  
42"  
UD4  
4"  
AK22  
4-00  
5
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
No one builds a better fire  
CHIMNEY SECTIONS  
CHIMNEY STABILIZER  
OFFSETS/RETURNS  
A
8"  
A
8"  
101/2  
"
203/4  
"
21"  
HTI CAT.#  
A
B
101/2  
"
SL306  
SL312  
SL318  
SL324  
SL336  
SL348  
6"  
43/4"  
103/4"  
163/4"  
223/4"  
343/4"  
463/4"  
6"  
101/2  
"
8"  
12"  
18"  
24"  
36"  
48"  
HTI CAT.#  
A
SL3  
SL315  
SL330  
15°  
30°  
A= Actual length  
B= Effective length (length of chimney part  
after it has been snapped to another)  
FIRESTOP SPACERS  
ROOF FLASHING  
12"  
A
245/8  
"
141/2  
"
B
271/4  
"
Flat to 6/12 Pitch  
RF370  
12"  
HTI CAT.#  
A
B
245/8  
"
FS338  
FS339  
FS340  
0°  
141/2"  
183/8"  
23"  
15°  
30°  
271/4  
"
6/12 to 12/12 Pitch  
RF371  
CHIMNEY BRACKET  
JOINT BAND  
101/2  
"
2"  
101/2  
"
CB876  
JB877  
4-00  
6
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
No one builds a better fire  
CHIMNEY TERMINAL CAPS & VENT SECTIONS  
167/8  
"
167/8  
"
153/4  
"
291/4  
"
TR344  
ROUND TERMINAL CAP  
WITH STORM COLLAR  
TR342  
ROUND TERMINAL CAP  
131/4  
"
143/4  
"
231/2  
221/4  
"
161/2  
"
"
23"  
(101/2" Outer)  
(8" Flue)  
173/4  
"
ST375  
SQUARE TERMINAL CAP  
TS345/TS345P  
SQUARE TERMINAL CAP  
72"  
36"  
107/8  
"
2"  
CT35  
CHASE TOP  
4-00  
7
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
No one builds a better fire  
D. PRE-INSTALLATION PREPARATION  
1. FIREPLACE LOCATIONS AND SPACE REQUIREMENTS.  
Several options are available to you when choosing a location for your fireplace. This fireplace may be used as  
a room divider, installed along a wall, across a corner or use an exterior chase. See Figure 1.  
In an exterior chase or  
As a room divider.  
projecting into a garage.  
Along a wall.  
Across a corner.  
Figure 1  
Fireplace Locations  
Figures 2 and 3 show two typical installations assuming an outside air kit is being used. Therefore, an  
allowance must be made for 90° bends. Less space is required when ducting goes directly outside without form-  
ing elbows.  
WITHOUT OUTSIDE AIR  
WITH OUTSIDE AIR  
193/4  
"
CAT. #  
BW36  
A
5
39 / "  
CAT. #  
BW36  
A
395/  
395/  
8
8
"
"
5
A
8
BW36C  
8
BW36C  
39 / "  
Figure 2  
Installation along a wall or an  
exterior chase.  
D
WITH OR WITHOUT OUTSIDE AIR  
E
D
CAT. #  
A
B
C
D
7
E
C
5
1
8
4
8
BW36  
39 / 62 / ”  
31”  
31”  
13 / ”  
44”  
44”  
5
1
7
8
4
8
BW36C  
39 / 62 / ”  
13 / ”  
A
B
* A minimum of 1" air clearance must be  
maintained between the firebox and wall.  
Figure 3  
Corner Installation  
WARNING!  
DO NOT DRAW OUTSIDE AIR FROM GARAGE SPACES. EXHAUST PRODUCTS OF  
GASOLINE ENGINES ARE HAZARDOUS.  
DO NOT INSTALL OUTSIDE AIR DUCTS SUCH THAT THE AIR MAY BE DRAWN  
FROM ATTIC SPACES, BASEMENTS OR ABOVE THE ROOF WHERE OTHER  
HEATING APPLIANCES OR FANS AND CHIMNEYS EXHAUST OR UTILIZE AIR.  
THESE PRECAUTIONS WILL REDUCE THE POSSIBILITY FOR SMOKING OR FLOW  
REVERSAL.  
4-00  
8
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
No one builds a better fire  
WARNING!  
TO PREVENT CONTACT WITH SAGGING OR LOOSE INSULATION, THE FIREPLACE  
MUST NOT BE INSTALLED AGAINST VAPOR BARRIERS OR EXPOSED INSULA-  
TION. LOCALIZED OVERHEATING COULD OCCUR AND A FIRE COULD RESULT.  
2. FRAMING THE FIREPLACE.  
Figure 4 shows a typical framing (using 2 x 4 lumber)  
of the fireplace, assuming combustible materials are  
used. All required clearances to combustibles around  
the fireplace must be adhered to. Any framing across  
the top of the fireplace must be above the level of the  
hemmed edge along the top of the firebox assembly.  
Vertical framing at the side of the firebox assembly to  
which the side nailing flanges are attached must be  
perpendicular to the face of the fireplace and may  
have point contact with the side of the fireplace at the  
nailing flange. A 1" air clearance must be maintained  
at the back and sides of the firebox assembly.  
Chimney Sections at any level require a two inch  
minimum air space clearance between the framing  
and chimney section.  
2" MIN. AIR SPACE  
CLEARANCE TO  
ENCLOSURE  
POSITION MANTEL  
12" ABOVE TOP OF  
FIREBOX OPENING.  
CAT. #  
BW36  
A
5
39 / "  
8
5
A
8
BW36C  
39 / "  
193/4  
"
335/8  
"
Figure 4  
Framing the Fireplace  
Combustible Material. Material made of or surfaced  
with wood, compressed paper, plant fibers, plastics,  
or any material capable of igniting and burning,  
whether flame proofed or not, plastered or unplas-  
tered.  
will not ignite and burn; General Electric  
RTV103Black, or equivalent. Rutland, Inc. Fireplace  
Mortar #63, or equivalent.  
After completing the framing and applying the facing  
material (dry wall) over the framing, a non-com-  
bustible sealant, one-half inch wide maximum, must  
be used to close off any gaps at the top and sides  
between the fireplace and facing to prevent cold air  
leaks.  
Non-combustible Material. Material which will not  
ignite and burn. Such materials are those consisting  
entirely of steel, iron, brick, tile, concrete, slate, glass  
or plasters, or combination thereof.  
Non-combustible Sealant Material. Sealants that  
Only non-combustible materials may be used to  
cover the black metal fireplace front.  
WARNING!  
DO NOT APPLY FINISHING MATERIALS OVER THE BOTTOM AIR INLET SLOTS  
NEAR THE GLASS DOOR OPENING ON THE FACE OF THESE FIREPLACES. THIS  
WILL BLOCK THE FLOW OF COOLING AIR AND MAY CAUSE DANGEROUSLY HIGH  
TEMPERATURES ON COMBUSTIBLE SURFACES OR ON THE FIREPLACE ITSELF.  
4-00  
9
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
No one builds a better fire  
3. HEARTH EXTENSIONS.  
A hearth extension must be installed with all fire-  
places. It is to protect the combustible floor in front of  
the fireplace from both radiant heat and sparks.  
A hearth extension of this construction may be cov-  
ered with any non-combustible decorative material  
and may have a maximum thickness of 6" for the  
BW36 and 3for the BW36C. Seal gaps between the  
hearth extension and the front of the fireplace with a  
non-combustible sealant.  
The construction of and materials used for a factory-  
built hearth extension are shown in Figure 5.  
GAP (SEAL WITH NON-COMBUSTIBLE SEALANT)  
BLACK FIREPLACE BOTTOM  
NON-COMBUSTIBLE  
DECORATIVE MATERIAL  
1
/
2"  
HX3 FACTORY-BUILT  
HEARTH EXTENSION  
BW36-6"  
HEARTH SEALING STRIP  
BW36C-3"  
Figure 5  
Factory-Built Hearth Extension  
Field constructed Hearth Extensions should be constructed in accordance with  
the minimum dimensions provided in Figure 6.  
EXAMPLES OF INSULATION  
NON-COMBUSTIBLE DECORATIVE  
COVERING OR .018 MIN. SHEET METAL  
REQUIRED  
THICKNESS K VALUE  
USG MICORE CV230  
1/2"  
0.43  
INSULATION MIN. R VALUE 1.16  
(THERMAL CONDUCTIVITY) "K" = BTU in./hr. ft2 °F  
TO SUBSTITUTE ALTERNATE INSULATION MATERIAL, YOU NEED TO KNOW THE "K"  
FACTOR FOR THAT MATERIAL. TO CALCULATE THE REQUIRED THICKNESS FOR THE  
ALTERNATE MATERIAL USE THE FOLLOWING FORMULA:  
52"  
16"  
EXAMPLE:KOF BRICK = 5  
K ALT.  
.43  
5
.43  
x .5 = 5.81 IN. OF BRICK.  
x .5 = THICKNESS OF ALTERNATE MAT. (INCHES)  
Figure 6  
Hearth Extension  
WARNING!  
HEARTH EXTENSIONS ARE TO BE INSTALLED ONLY AS ILLUSTRATED  
TO PREVENT HIGH TEMPERATURES FROM OCCURRING ON CON-  
CEALED COMBUSTIBLE MATERIALS. HEARTH SEALING STRIPS PRE-  
VENT BURNING OR HOT PARTICLES FROM INADVERTENTLY FALLING  
DIRECTLY ON COMBUSTIBLE SURFACES IN THE EVENT THE BUILDING  
SHOULD SETTLE AND DISTURB THE ORIGINAL CONSTRUCTION.  
4-00  
10  
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
4. SIDEWALLS/SURROUNDS.  
No one builds a better fire  
Adjacent combustible side walls must be located a minimum of 12" from the fireplace opening. See Figure 7. If  
you are using a decorative surround constructed of combustible material, it may be located within the shaded  
area defined in Figure 7. Short stub walls are also acceptable if they are contained within the shaded area.  
BRICK  
FRONT  
4"  
FLUSH FRONT  
12"  
143/8  
50°  
"
A
93/4  
"
B
39°  
12"  
MIN.  
12"  
12"  
CAT. #  
A
B
5
TOP OF  
FIREPLACE  
OPENING  
335/8  
"
8
BW36  
36"  
36"  
38 / "  
5
8
BW36C  
38 / "  
Figure 7  
Sidewalls/Surrounds  
5. MANTEL.  
A combustible mantel may be positioned no lower  
than 12above the top of the firebox opening. The  
combustible mantel may have a maximum depth of  
12. Combustible trim materials, projecting no more  
than 1 1/2from the face of the fireplace, can be  
placed no closer than 6from the top and side of the  
firebox opening. (See the shaded areas on each  
side of the firebox, as defined in Figure 7).  
Combustible trim must not cover the black metal sur-  
faces of the fireplace. This mantel clearance is in  
accordance with Section 7-3.3.3 of ANSI/NFPA 211.  
E. CHIMNEY REQUIREMENTS  
When planning your fireplace location, the chimney construction and necessary clearances must be considered.  
The fireplace system and chimney components have been tested to provide the following flexibility in construc-  
tion. The following figures are the minimum distances from the base of the unit.  
Minimum overall straight height  
Minimum height with Offset/Return  
Maximum height  
Maximum chimney length between an Offset/Return  
Maximum distance between Chimney Stabilizers  
Double Offset/Return minimum height  
Maximum unsupported chimney length between Offset/Return  
Maximum straight unsupported chimney height above firebox  
14.5 ft.  
14.5 ft.  
90 ft.  
12 ft.  
35 ft.  
20 ft.  
6 ft.  
25 ft.  
1. USING OFFSETS AND RETURNS.  
elbows must never exceed 12 feet in total  
length.  
To bypass any overhead obstructions, the chimney  
may be offset using a 15° offset/return (SL315) or a  
30° offset/return (SL330). Perform the following steps  
to determine the correct chimney component combi-  
nation for your particular installation.  
a. Measure how far the chimney needs to be  
shifted to enable it to avoid the overhead  
obstacle. See Figure 8, dimension A.  
b. After determining the offset dimension, refer  
to Table 1 (page 13) and find the Adimen-  
sion closest to but not less than the dis-  
tance of shift needed for your installation.  
An offset and return may be attached together or a  
chimney section(s) may be used between an offset  
and return. However, the distance between two  
4-00  
11  
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
No one builds a better fire  
c. The Bdimensions that coincide with the Adim-  
e. Whenever the chimney penetrates a floor/ceiling,  
ensions represent the required vertical clearance  
that is needed to complete the offset and return.  
a firestop spacer must be installed.  
f. The effective height of the firebox assembly  
is 3358".  
d. Read across the chart and find the number of  
chimney sections required and the model num-  
ber of those particular chimney parts.  
Example: Your Adimension from Figure 8 is 1412".  
Using Table 1, the dimension closest to but not less  
than 1412" is 1458" using a 30° offset/return. It is then  
determined from the table that you would need 33"  
(Dimension B) between the offset and return. The  
chimney components that best fit your application are  
two [2] SL312s.  
A
WARNING!  
B
DO NOT COMBINE OFFSETS TO  
CREATE AN OFFSET GREATER  
THAN 30° FROM VERTICAL. THIS  
MAY CREATE A FIRE HAZARD  
SINCE THE NATURAL DRAFT MAY  
BE RESTRICTED.  
11/4" OVERLAP  
Figure 8  
Chimney Offset/Return  
Offset Chart*  
TABLE 1  
15°  
30°  
A
B
A
B
SL306  
SL312  
SL318  
SL324 SL336 SL348  
15/8”  
27/8”  
133/8”  
173/4”  
37/8”  
61/4”  
85/8”  
141/2”  
185/8”  
223/4”  
233/4”  
277/8”  
29”  
1”  
2”  
1”  
2”  
1”  
41/2”  
235/8”  
91/4”  
1”  
1”  
115/8”  
121/4”  
145/8”  
151/4”  
175/8”  
205/8”  
211/4”  
235/8”  
265/8”  
271/4”  
295/8”  
325/8”  
355/8”  
385/8”  
41”  
1”  
6”  
71/4”  
293/8”  
34”  
33”  
2”  
341/8”  
381/4”  
431/2”  
445/8”  
483/4”  
537/8”  
553/4”  
59”  
641/4”  
691/2”  
745/8”  
783/4”  
85”  
1”  
1”  
1”  
105/8”  
117/8”  
133/4”  
15”  
161/2”  
18”  
463/4”  
513/8”  
1”  
1”  
1”  
2”  
583/8”  
1”  
1”  
1”  
1”  
1”  
1”  
1”  
1”  
2”  
63”  
1”  
683/4”  
745/8”  
1”  
1”  
1”  
1”  
223/4”  
24”  
257/8”  
917/8”  
961/2”  
1031/2”  
445/8”  
1”  
1”  
47”  
505/8”  
891/8”  
951/2”  
1”  
*Proper assembly of air cooled chimney parts result in an overlap at chimney joints of 11/4. Effective length is built into this  
chart.  
4-00  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
No one builds a better fire  
IF 10  
FEET OR  
LESS  
12"  
12"  
MIN.  
THEN  
TOP OF  
FIREPLACE  
OPENING  
335/8  
"
Figure 8a - Fireplace (Side View)  
MUST BE AT  
LEAST 2 FEET  
2. CHIMNEY HEIGHT REQUIREMENTS.  
(Above the roof line)  
BUT  
Major building codes specify a minimum chimney height  
above the roof top. These specifications are summarized  
in what is known as the Ten Foot Rule. This rule states:  
If the horizontal distance from the side of the chimney to  
the peak of the roof is 10 feet or less, the top of the chim-  
ney must be at least 2 feet above the peak of the roof, but  
never less than 3 feet in overall height above the highest  
point where it passes through the roof. See Figure 9.  
NEVER LESS  
THAN 3 FEET  
If the horizontal distance from the side of the chimney to  
the peak of the roof is more than 10 feet, a chimney  
height reference point is established on the surface of the  
roof a distance of 10 feet from the side of the chimney in a  
horizontal plane. The top of the chimney must be at least  
2 feet above this reference point, but never less than 3  
feet in height above the highest point where it passes  
through the roof.  
Figure 9  
Chimney Height  
Height of Chimney Components  
Chimney Stabilizer  
These chimney heights are necessary in the interest of  
safety and do not ensure smoke-free operation. Trees,  
buildings, adjoining roof lines, adverse wind conditions,  
etc., may create a need for a taller chimney should smok-  
ing occur.  
SL3  
434  
Firestop Spacers  
FS338  
0
0
0
FS339  
DETERMINING THE NUMBER OF CHIMNEY  
SECTIONS REQUIRED.  
FS340  
Offset/Returns  
SL315  
133⁄  
8
To determine the chimney components needed to com-  
plete your particular installation, follow the below steps:  
SL330  
1412  
Roof Flashing  
RF370  
1. Determine the total vertical height of the fireplace  
installation. This dimension is measured from the  
base of the firebox assembly to the point where the  
smoke exits the terminal cap.  
0
0
RF371  
Chimney Sections*  
SL306  
434  
2. Subtract the height of the firebox assembly (3358")  
SL312  
103⁄  
163⁄  
223⁄  
343⁄  
463⁄  
4
from the overall height of the fireplace installation.  
SL318  
4
3. Reference the below chart to determine what compo-  
nents must be selected to complete the fireplace  
installation.  
SL324  
4
SL336  
4
SL348  
4
4. Determine the number of firestop spacers, stabilizers,  
roof flashing, etc. required to complete the fireplace  
installation.  
*Dimensions reflect effective height.  
4-00  
13  
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
No one builds a better fire  
F. STEP-BY-STEP INSTALLATION OF THE FIREPLACE SYSTEM  
WARNING!  
BEFORE STARTING, DO THE FOLLOWING:  
1. WEAR GLOVES AND SAFETY GLASSES FOR PROTECTION.  
2. KEEP HAND TOOLS IN GOOD CONDITION. SHARPEN CUTTING EDGES AND  
MAKE SURE TOOL HANDLES ARE SECURE.  
3. ALWAYS MAINTAIN THE MINIMUM AIR SPACE REQUIRED TO THE ENCLOSURE  
TO PREVENT FIRE.  
STEP 1 - Positioning the Fireplace.  
This fireplace may be placed on either a combustible  
or non-combustible continuous surface. Follow the  
instructions for framing on page 9. Be sure to pro-  
vide the minimum 1" air clearance at the sides and  
back of the firebox assembly. Framing that is per-  
pendicular to the fireplace front may contact the side  
of the firebox assembly at the nailing flanges.  
STEP 2 - Placing the Protective Metal Hearth  
Strips.  
Included with your fireplace are two metal hearth  
1" OVERLAP  
strips measuring approximately 26" x 4". These  
strips are used to provide added protection where the  
fireplace and hearth extension meet.  
UNDER EDGE OF FIREPLACE  
METAL STRIPS TWO INCHES  
Slide the metal strips two inches under the front edge  
of the fireplace with the 2 pieces overlapping other in  
the middle of the fireplace to provide continuous cov-  
erage of the floor. See Figure 10.  
AND HEARTH EXTENSION  
Figure 10  
Positioning the Metal Strips  
STEP 3 - Leveling the Fireplace.  
Level the fireplace side-to-side and front-to-back.  
Shim with non-combustible material, such as sheet  
metal, as necessary.  
WARNING!  
CAREFULLY FOLLOW THE  
INSTRUCTIONS FOR ASSEMBLY  
OF THE PIPE AND OTHER PARTS  
NEEDED TO INSTALL THIS FIRE-  
PLACE SYSTEM. FAILURE TO DO  
SO MAY RESULT IN A FIRE, ESPE-  
CIALLY IF COMBUSTIBLES ARE  
TOO CLOSE TO THE FIREPLACE  
OR CHIMNEY AND AIR SPACES  
ARE BLOCKED PREVENTING THE  
FREE MOVEMENT OF COOLING  
AIR.  
Important: To ensure proper fit of the glass doors,  
check the firebox opening for squareness. Measure  
diagonal distances of the opening to make sure they  
are equal. If they do not equal, continue to shim the  
firebox until those diagonals correspond.  
Secure the fireplace by utilizing the nailing tabs locat-  
ed on either side of the fireplace to the vertical fram-  
ing. Hold-down tabs are provided at the base of the  
firebox assembly for attachment to the subfloor if  
desired.  
NOTE: Top Header may be positioned on the  
hemmed seam across the top of the firebox  
assembly.  
4-00  
14  
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
STEP 4 - Assembling Chimney Sections.  
No one builds a better fire  
Attach either a straight chimney section or an offset to  
the top of the fireplace depending on your installation  
requirement. When using offsets and returns, we highly  
recommend securing in place on the top of the fireplace  
with screws to permanently attach them to the top of the  
fireplace. See Figure 11.  
CAUTION:  
INNER FLUE AND OUTER LINER  
SECTIONS CANNOT BE DISASSEM-  
BLED ONCE LOCKED TOGETHER.  
PLAN AHEAD TO INSURE THE  
PROPER INSTALLATION HEIGHT IS  
ACHIEVED WITH THE SELECTED  
CHIMNEY COMPONENTS.  
When using elbows right off of the top of the unit, you  
will need to flatten the lances before you slip it on the  
collar. Once it is on, line it up and secure it with screws  
to the unit collar through the slots in the elbow.  
These firestop spacers are designed to provide the  
minimum two inch air space required around the  
chimney. In all situations, the firestop spacers are to  
be nailed to the ceiling joists from the bottom or fire-  
place side, EXCEPT when the space above is an  
insulated ceiling or attic space. In this situation, the  
firestop spacer must be nailed from the top side to  
prevent loose insulation from falling into the required  
two inch air space around the chimney.  
Figure 11  
Offset Secured to Fireplace  
Firestop spacers must be used whenever the chim-  
ney penetrates a ceiling/floor area.  
ROOM ABOVE  
NOTE: The inner  
flue is placed to  
the inside of the  
flue section  
below it. The  
outer casing is  
placed outside  
the outer casing  
of the chimney  
section below it.  
See Figure 12.  
ATTIC ABOVE  
Figure 12  
Connecting Chimney  
Sections  
Figure 13  
Installing the Firestop Spacer  
STEP 5 - Preparing the Ceiling for Firestop  
Spacers.  
STEP 7 - Installing an AS8 insulation shield  
Mark and cut out an opening in the ceiling for the par-  
ticular firestop spacer being utilized (1412" x 1412" for  
an FS338, 1412" x 1834" for an FS339, or 1412" x 23"  
for an FS340). Frame the opening with the same  
dimension lumber used in the ceiling joists.  
An AS8 insulation shield should be installed when  
there is a possibility of insulation coming into contact  
with the factory-built chimney system. The AS8 is  
installed by positioning it over the vertical chimney  
section where it penetrates an FS338 firestop spacer.  
The FS338 will support the AS8. See Figure 14 on  
page 16. When the factory-built chimney penetrates  
an insulated ceiling at either 15 or 30 degrees from  
vertical, an insulation dam should be constructed from  
plywood or sheet metal. A minimum 2" air space  
must be provided between the insulation dam and the  
factory-built chimney system.  
STEP 6 - Installing the Firestop Spacers.  
Install the firestop spacer FS338 (Straight), FS339 (if  
a 15° offset located is in the ceiling joist area) or  
FS340 (if a 30° offset is located in the ceiling joist  
area). Nail the four [4] sides of the firestop spacer to  
the joists using a minimum of three [3] nails per side.  
4-00  
15  
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
No one builds a better fire  
141/2  
"
AS8 ATTIC  
INSULATION  
SHIELD  
WARNING!  
INSULATION  
WHEN CHIMNEY SECTIONS EXCEED-  
ING SIX FEET IN LENGTH ARE  
INSTALLED BETWEEN AN OFFSET/  
RETURN, STRUCTURAL SUPPORT  
MUST BE PROVIDED TO REDUCE  
OFF-CENTER LOADING AND PRE-  
VENT CHIMNEY SECTIONS FROM  
SEPARATING AT THE CHIMNEY  
JOINTS.  
FS338  
FIRESTOP  
SPACER  
24"  
CHIMNEY  
101/2  
"
Figure 14  
Installing an AS8  
STEP 10 - Marking the Exit Point of the Roof.  
STEP 8 - Double-checking the Chimney Assembly.  
Locate the point where the chimney will exit the roof  
by plumbing down to the center of the chimney.  
Drive a nail up through the roof to mark the center.  
See Figure 16.  
Continue assembling the chimney sections up through  
the firestop spacers as needed. While doing so, be  
aware of the height and unsupported chimney length  
limitations that are given on page 11 under Chimney  
Requirements.  
Check each section by pulling up slightly from the top  
to ensure proper engagement before installing the  
succeeding sections. If they have been connected  
correctly, they will not disengage when tested.  
STEP 9 - Securing the Chimney System.  
When offsets and returns are joined to straight pipe  
sections, they must be locked into position with the  
screws provided, using the predrilled holes. To prevent  
gravity from pulling the chimney sections apart, the  
returns and the chimney stabilizers have straps for  
securing these parts to joists or rafters.  
See Figure 15.  
NOTE: Be sure to provide support for the  
pipe during construction and check to be  
sure inadvertent loading has not dislodged  
the chimney section from the fireplace or at  
any chimney joint.  
Figure 16  
Ceiling and Attic Construction  
FIRESTOP  
STRAPS  
STEP 11 - Cutting Out the Hole in the Roof.  
Measure to either side of the nail and mark the 1412" x  
1412" opening required. This is measured on the hori-  
zontal; actual length may be larger depending on the  
pitch of the roof. Cut out and frame the opening.  
See Chapter 25 of the Uniform Building Code for  
Roof Framing details. Be sure to maintain a 2" mini-  
mum air space between the chimney section and the  
roof.  
JOINT  
BAND  
OPTIONAL  
ADDITIONAL  
SUPPORT  
(OPTIONAL)  
Figure 15 - Offset/Return with Stabilizer  
4-00  
16  
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
STEP 12 - Assembling the Chimney Sections.  
No one builds a better fire  
STEP 15 - Completion of the Fireplace Enclosure.  
Continue to add chimney sections through the roof  
opening, maintaining at least a 2" air space.  
Complete the fireplace enclosure, allowing space for out-  
side air ducts and gas piping if desired. Electrical wiring  
should not come in contact with the unit. A minimum  
clearance of 1" must be maintained between the fireplace  
sides and the enclosure as well as the fireplace back and  
the enclosure. See Figure 4 for framing details.  
STEP 13 - Installing Roof Flashing (optional).  
If a roof flashing is to be used, install the roof flashing  
appropriate to the roof pitch and install a TR344 ter-  
minal cap (round) following the instructions shipped  
with these accessories.  
STEP 16 - Provisions for an Optional Gas Log Set.  
Knockouts are provided on both sides of the fireplace to  
allow for connection of a certified gas log lighter or a dec-  
orative gas appliance with a maximum input of 100,000  
BTU/hr. incorporating an automatic gas shutoff device  
and complying with the Standard for Decorative Gas  
Appliances for Installation in Vented Fireplaces, ANSI  
Z21.60. The decorative gas appliance should be  
installed in accordance with the National Fuel Gas Code,  
ANSI Z223.1-1980. The side refractories are designed to  
allow 1/2black pipe to pass through. Use a non-com-  
bustible sealant to seal any opening between the gas  
pipe and refractory on the inside. Repack the insulation  
removed, to seal around the gas pipe where it exits the  
side of the fireplace. A minimum 1-1/2air clearance  
must be provided to the 1/2black pipe. See Figure 18.  
STEP 14 - Installing an Outside Combustion  
Air Kit.  
The outside air damper assembly is factory installed  
on the left hand side of the firebox assembly. While  
its use is optional, it is highly recommended to mini-  
mize the effects of negative pressure within the  
structure. Figure 17 illustrates two of many possible  
methods that can be used to supply outside air to the  
fireplace system. To complete the outside air system  
install the AK22 Outside Air Kit according to the  
installation instructions supplied with the compo-  
nents.  
NOTE: The outside air kit can terminate at  
any level with the exception that it  
must terminate at least three feet  
below the chimney terminal cap as  
shown in Figure 17.  
This fireplace has been set up for installation of the gas  
pipe on the right hand side. If it is necessary to plumb  
the unit from the left hand side, remove the gas cover  
plate and gas tube from the right hand side of the unit  
and install on the left hand side. Cover the hole in the  
right hand side outer shell of the fireplace with the cover  
plate that covered the gas tube.  
3' MIN.  
WARNING!  
UPPERMOST  
CHIMNEY  
SECTION  
THIS FIREPLACE WAS NOT TESTED BY THE  
FIREPLACE MANUFACTURER FOR USE WITH AN  
UNVENTED GAS LOG HEATER. DO NOT  
INSTALL AN UNVENTED GAS LOG HEATER IN  
THIS FIREPLACE UNLESS IT HAS BEEN SPECIFI-  
CALLY TESTED AND LISTED BY UNDER-  
WRITERS LABORATORIES INC FOR USE IN THIS  
SPECIFIC MODEL FIREPLACE. UNLESS THE  
UNVENTED GAS LOG HEATER IS TESTED AND  
LISTED FOR USE IN THIS FACTORY-BUILT FIRE-  
PLACE, A FIRE HAZARD MAY BE CREATED  
THAT CAN RESULT IN A STRUCTURE FIRE.  
CAUTION:  
WHEN USING A GAS LOG SET, THE  
FIREPLACE DAMPER MUST BE SET  
IN THE FULLY OPEN POSITION.  
THIS ENSURES A PROPER VENTING  
OF COMBUSTION PRODUCTS.  
Figure 17  
Outside Air Location  
4-00  
17  
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
No one builds a better fire  
1-1/2" clearance to  
combustibles  
Figure 18  
Gas Knockout Location  
STEP 18 - Installing the Firescreen.  
Figure 19  
Positioning the Hearth Extension  
Attach the firescreen to the fireplace side, utilizing  
the [2] hairpin clips in the columns. Use pliers to  
insert the clip through the last strand of screen wire  
and into the hole at the midpoint of the fireplace side.  
G. CONSTRUCTING A CHASE  
A chase is a vertical box-like enclosure built around  
the chimney and firebox. A chase may be constructed  
for the fireplace and chimney or for the chimney only.  
It is most commonly constructed on an outside wall.  
STEP 19 - Installing the Glass Doors.  
If desired, or required by local building codes, install  
the glass doors using the instructions supplied with  
the particular set of doors you have chosen.  
In cold climates, it is recommended that the chase  
floor be insulated using batt type insulation between  
the floor joists.  
STEP 20 - Positioning the Hearth Extension.  
Position and secure the hearth extension over the  
protective metal strips that have been placed partially  
under the firebox front. See Figure 19. These strips  
should be protruding approximately two inches from  
under the fireplace front. Seal the crack between the  
hearth extension and fireplace with a non-com-  
bustible sealant.  
Three examples of chase applications are shown in  
Figure 20.  
STEP 21 - Applying Finishing Materials on the  
Hearth Extension.  
Apply the non-combustible finishing material of your  
choice to the hearth extension. Do not install com-  
bustible materials over the black face of the fire-  
place This poses a safety hazard and may start a  
structure fire. You may only use non-combustible  
material over the black face of the fireplace. Refer to  
Figure 7 for combustible material information.  
1
2
3
Do not cover or restrict any of the louvered openings  
on the front face of the BW36C Fireplace. Restricting  
or covering the louvered opening will create a safety  
hazard and may start a structure fire.  
Figure 20  
Chase Constructions  
1. Fireplace and chimney enclosed in an exterior  
chase.  
2. Chimney offset through exterior wall and  
enclosed in chase.  
3. Chase constructed on roof.  
4-00  
18  
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
1. Materials for the Chase.  
No one builds a better fire  
WARNING!  
The chase is constructed using framing mate-  
rials much the same as the walls in your  
home. A variety of materials may be used  
including brick, stone, veneer brick, or stan-  
dard siding materials.  
DETAIL INSTRUCTIONS FOR INSTALLA-  
TION OF THE CHASE TOP, STORM COL-  
LAR AND TERMINAL CAP ARE PACKAGED  
WITH THESE PARTS. TO AVOID DANGER  
OF FIRE, ALL INSTRUCTIONS MUST BE  
STRICTLY FOLLOWED, INCLUDING THE  
PROVISION OF AIR SPACE CLEARANCE  
BETWEEN CHIMNEY SYSTEM AND ENCLO-  
SURE. TO PROTECT AGAINST AGAINST  
THE EFFECTS OF CORROSION ON THOSE  
PARTS EXPOSED TO THE WEATHER, WE  
RECOMMEND THAT THE CHASE TOP AND  
TERMINAL CAP BE PAINTED WITH A RUST  
RESISTANT PAINT.  
In constructing the chase, several factors  
must be considered.  
a. Maintain a 1" minimum air space around  
the firebox.  
b. Maintain a 2" air space around the chim-  
ney.  
c. The chase top must be constructed of a  
non-combustible material.  
2. Installing a Terminal Cap on a Chase Enclosed  
Chimney.  
d. In cold climates a firestop spacer should  
be installed in an insulated false ceiling  
at the 8 foot level above the firebox  
assembly. This prevents heat loss  
through the fireplace.  
Construct a chase of desired materials maintaining a mini-  
mum 2" air space around the chimney.  
WARNING!  
e. In cold climates, the walls of the chase  
should be insulated to the level of the  
false ceiling as shown in Figure 21. This  
will help prevent heat loss from the home  
around and through the fireplace.  
NEVER INSTALL A SINGLE WALL SLIP SECTION OR  
SMOKE-PIPE IN A CHASE STRUCTURE. THE HIGH-  
ER TEMPERATURE OF THIS SINGLE WALL PIPE  
MAY RADIATE SUFFICIENT HEAT TO COM-  
BUSTIBLE CHASE MATERIALS TO CAUSE A FIRE.  
Install the chimney sections up through the chase  
enclosure. When using a round terminal cap  
(TR344), the last section of pipe must extend above  
the top of the chase cone to allow installation of the  
storm collar and terminal cap.  
ROUND TERMINAL CAP  
(TR342, TR344)  
METAL CHASE TOP  
A telescoping round terminal cap (TR342) is provided  
to simplify the installation of the terminal cap on a  
chase installation. The uppermost chimney section  
must terminate below the level of the chase top, but  
be no more than 15below the level of the chase top.  
A 2tall flashing collar must be provided on the chase  
top.  
FIRESTOP  
SPACER  
The ST375 Square Terminal Cap is intended for a  
chase installation. The uppermost chimney section  
must terminate no more than 4-3/4 below the level of  
the chase top. A 2tall flashing collar must be pro-  
vided on the chase top.  
FALSE  
CEILING  
When installing a TS345 or TS345P Square  
Termination, the uppermost chimney section must not  
be more than 3below the chase top.  
Attach the chase top (CT35) to the top of the chase.  
Figure 21  
Chase Assembly  
Install the terminal cap, using the instructions provid-  
ed with it.  
4-00  
19  
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
No one builds a better fire  
It is extremely important that the fire be super-  
vised whenever the fireplace is in use. It is also  
recommended that an annual inspection be per-  
formed on the fireplace system to determine if  
the flue system needs to be cleaned, or as in  
the case of any appliance, if minor repairs are  
required to maintain the system in top operating  
condition.  
TR342  
TERMINAL CAP  
CHASE TOP  
18"  
MAX.  
DISTANCE  
INTENDED USAGE. This factory-built fire-  
place is intended for use with either solid fuel  
(firewood) or a decorative gas appliance that  
has been tested and listed to the Standard for  
Decorative Gas Appliances for Installation in  
Vented Fireplaces, ANSI Z21.60. When oper-  
ating your fireplace, the flue damper must  
be in the open position.  
UPPERMOST  
CHIMNEY  
SECTION  
Figure 22  
Installing a Terminal Cap  
This fireplace was not tested and listed for use  
with an unvented gas log heater. Do not install  
an unvented gas log heater in this fireplace and  
operate it with the flue damper in the full closed  
position unless the unvented gas log has been  
specifically tested and listed for use in this fire-  
place by Underwriters Laboratories Inc. Use of  
an unvented gas log heater in this factory-build  
fireplace may create a fire hazard that can  
result in a structure fire.  
H. OPERATING  
INSTRUCTIONS  
NOTICE:  
SAVE AND PASS THESE OPERATING  
INSTRUCTIONS AND THE INSTALLATION  
INSTRUCTIONS TO SUBSEQUENT  
OWNERS. THE INFORMATION  
PROVIDED IS INTENDED TO NOTIFY  
AND WARN THEM ABOUT MAKING  
UNSAFE FUTURE MODIFICATIONS SUCH  
AS THE ADDITION OF SHELVES OR THE  
USE OF UNAUTHORIZED PARTS AND  
REPAIRS.  
WARNING!  
DO NOT OPERATE THIS FIREPLACE WITH  
THE FLUE DAMPER IN THE CLOSED POSI-  
TION. COMBUSTION PRODUCTS MUST  
VENT UP THE CHIMNEY SYSTEM TO PRE-  
VENT CARBON MONOXIDE POISONING,  
AND TO PREVENT HOT COMBUSTION  
GASES FROM CONTACTING AND OVER-  
HEATING COMBUSTIBLE SURFACES.  
FAILURE TO OPERATE THIS FIREPLACE  
WITH THE DAMPER IN THE OPEN POSI-  
TION MAY RESULT IN ASPHYXIATION OR  
A STRUCTURE FIRE.  
CAUTION:  
EDGES ARE SHARP! HAND PRO-  
TECTION IS RECOMMENDED.  
This fireplace is intended to operate as a supplemen-  
tal heat source for a single room. It is not designed  
to function as a primary heat source.  
CAUTION:  
FIREPLACE OPERATION DOES RE-  
QUIRE AIR. DO NOT TAKE AIR  
FROM OTHER FUEL BURNING  
APPLIANCES WHICH CAN RESULT  
IN IMPROPER VENTING (SMOKING)  
OR AIR DILUTION. ALWAYS PRO-  
VIDE ADEQUATE MAKE-UP AIR.  
Fireplaces, as well as other woodburning appliances,  
have been used safely for many years. It has been  
our experience that most problems are caused by  
improper installation and operation of the unit. Make  
certain that installation and operation of the fireplace  
system is in accordance with these instructions.  
4-00  
20  
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
No one builds a better fire  
STARTING THE FIRE. Check the flue damper to be  
certain it is in the full open position. Place crumpled  
or twisted paper under the fireplace grate. Loosely  
arrange kindling or small pieces of wood to form a  
layer above the paper. Light the paper and add small  
pieces of wood until a hot bed of embers has been  
established. At this point add progressively larger  
pieces of wood until you are able to position 4diame-  
ter split logs as shown in Figure 23.  
Use only a solid wood fuel or a listed Heat-N-Glo gas  
log set. Do not use a fireplace insert or products not  
specifically tested and listed for use in this fireplace.  
Use common sense when burning this fireplace. The  
fire must be built on the fireplace grate, without dan-  
ger of the burning fuel falling out of the firebox.  
CAUTION:  
When first lighting your fireplace, it may be necessary  
to pre-warm the flue to establish a draft. This is done  
by holding a rolled up piece of burning newspaper  
under the flue damper for a few moments. This will  
prevent smoke spillage during start-up.  
NEVER USE GASOLINE, GASO-  
LINE-TYPE LANTERN FUEL,  
KEROSENE, CHARCOAL LIGHTER  
FLUID, OR SIMILAR LIQUIDS TO  
START OR FRESHEN UPA FIRE  
IN THIS FIREPLACE. KEEP ALL  
SUCH LIQUIDS WELL AWAY FROM  
THE FIREPLACE WHILE IT IS IN  
USE TO AVOID THE RISK OF A  
HOSTILE FIRE.  
93/8  
"
REFRACTORY  
BACK  
INTEGRAL GRATE  
(CAT. NO.  
GR16 ONLY)  
DISPOSAL OF ASHES. Ashes should be placed in a  
metal container with a tight-fitting lid. The closed con-  
tainer of ashes should be placed on a non-combustible  
floor or on the ground, well away from all combustible  
materials, pending final disposal. If the ashes are dis-  
posed of by burial in soil or otherwise locally dis-  
persed, they should be retained in the closed contain-  
er until all embers have thoroughly cooled.  
REFRACTORY  
HEARTH  
Figure 23  
Sectional View of Fireplace  
Firewood should be seasoned for at least 6 months  
before it can be burned as a fireplace fuel.  
Improperly seasoned (green or wet) wood will cause  
the fireplace to smoke, will allow creosote deposits  
to rapidly build-up in the chimney system and may  
cause roof stains to develop.  
Fuel products with abnormal burning characteristics,  
including synthetic logs that contain wax binders,  
scrap lumber, wax or plastic coated cardboard and  
other highly volatile fuels that burn at excessive tem-  
peratures, may cause the fireplace to operate in an  
unsafe manner. Flammable liquid fuel are explosive  
and must never be used to start or freshen a fire.  
Heat-N-Glo does not warrant the structural or func-  
tional performance of the fireplace system when  
such synthetic fuels or flammable liquids have been  
used.  
GLASS DOORS. Most efficient fireplace operation  
using glass doors is with the doors open. When the  
doors are open, the screen must be closed. Only  
Hearth Technologies Inc. (HTI) glass doors, model  
numbers DM1036, DM1036A and DM1036B may  
be used on the BW36 Series fireplaces.  
FULLY OPEN  
CORRECT  
PARTLY OPEN  
WRONG  
FULLY CLOSED  
CORRECT  
PARTLY OPEN  
WRONG  
NOTE: When heated for the first several  
times, the fireplace should be heated gradu-  
ally to prevent moisture in the refractory  
from causing cracks and to allow binders in  
the insulation to dissipate. You will notice  
an industrial odor during the first few fires  
that are burned. This is considered to be  
normal.  
Figure 24  
Recommended Operating Positions of Doors  
4-00  
21  
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
No one builds a better fire  
Before starting a fire in your BW36 Series fireplace,  
use the following check list:  
WARNING!  
FIREPLACES EQUIPPED WITH  
DOORS SHOULD BE OPERATED  
ONLY WITH DOORS FULLY OPEN  
OR FULLY CLOSED. IF DOORS  
ARE LEFT PARTIALLY OPEN, GAS  
AND FLAME MAY BE DRAWN OUT  
OF THE FIREPLACE OPENING,  
CREATING THE RISK OF BOTH  
FIRE AND SMOKE.  
FLUE DAMPER. The flue damper is operated by  
moving a handle located in the fire chamber, which  
should place the damper in a fully open position.  
Pull the handle down to open, push the handle up to  
close. Verify this by looking up from the inside of  
the firebox. Always operate this fireplace with the  
damper fully open. Please note: down drafts,  
obstructions, damage or poor (wet) fuels can cause  
smoke spillage.  
CHIMNEY INSPECTION. Visually inspect the chim-  
ney internally for obstructions and construction dam-  
age. Flue pipe joints and seams must be continu-  
ous and mechanically tight. In a used chimney,  
additional inspection is needed for creosote build-up  
which is the formation of a flammable sediment.  
When wood is burned slowly, it produces tar and  
other organic vapors, which combine with expelled  
moisture to form creosote. The creosote vapors  
condense in the relatively cool chimney flue of a  
slow-burning fire. As a result, creosote residue  
accumulates on the flue lining. When ignited, this  
creosote makes an extremely hot fire.  
WARNING!  
CONTINUED OVER-FIRING CAN  
PERMANENTLY DAMAGE YOUR  
FIREPLACE SYSTEM. EXAMPLES  
OF OVER-FIRING ARE:  
The chimney should be inspected at least twice a  
year during the heating season to determine if cre-  
osote build-up has occurred.  
If creosote has accumulated, it should be removed  
to reduce the risk of a chimney fire.  
1. THE NORMAL LOG FIRE”  
SHOULD BE CONTAINED IN THE  
GRATE, WITH THE LENGTH OF  
LOGS NO GREATER THAN THE  
BACK WALL OF THE FIREPLACE.  
CHIMNEY CLEANING. If you do detect a build-up  
of creosote, contact a qualified chimney sweep or  
clean it yourself. To do this, perform the following  
steps:  
2. THE FOLLOWING MATERIALS  
MUST NOT BE USED IN THIS FIRE-  
PLACE: QUANTITIES OF SCRAP  
LUMBER, PINE BRANCHES,  
PROCESSED FIRE LOGS AND FIRE  
STARTERS, OR CARDBOARD  
BOXES WHICH EXCEED THE VOL-  
UME OF THE NORMAL LOG  
FIRE. THESE MATERIALS PRO-  
DUCE MANY SPARKS AND MUST  
NOT BE USED.  
1. Open the damper.  
2. Hang a damp sheet across the fireplace  
opening to stop dirt and soot from entering  
the room.  
3. Remove the Terminal Cap or Housing  
Top. See Figure 25.  
4. Clean with a stiff nylon brush attached to a  
pole OR tie a rope to a burlap bag filled  
with straw and several small stones or  
sand. Work up and down the flue until  
clean.  
5. Replace the terminal cap or housing top.  
4-00  
22  
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BW36 SERIES WOODBURNING FIREPLACE  
No one builds a better fire  
REMOVE (4) SCREWS  
AND LIFT TOP  
PAN OFF.  
LIFT UP TO  
REMOVE.  
1. REMOVE THE  
4 SCREWS.  
SCREW  
SCREW  
2. REMOVE SCREEN.  
3. REMOVE BAFFLE.  
CAP  
SLIP  
CAP  
CHASE  
SECTION  
TS345  
SQUARE  
TERMINAL CAP  
TR342, TR344  
ROUND TERMINAL CAPS  
ST375  
SQUARE  
TERMINAL CAP  
Figure 25  
Terminal Caps  
WARNING!  
CAUTION:  
A CHIMNEY FIRE CAN PERMA-  
NENTLY DAMAGE YOUR CHIMNEY  
WHEN LEFT CLOSED WHILE  
BURNING YOUR FIREPLACE, FIRE-  
SCREENS AND GLASS DOORS  
WILL BE HOT. HANDLE WITH  
CARE.  
SYSTEM. THIS DAMAGE CAN ONLY  
BE REPAIRED BY REPLACING THE  
DAMAGED COMPONENT PARTS.  
CHIMNEY FIRES ARE NOT COV-  
ERED BY THE LIMITED WARRANTY  
AND BUYER PROTECTION PLAN.  
CLEAR SPACE NEAR FIREPLACE. The hearth  
extension must extend at least 16 inches to the front  
and 8to the sides of the firebox opening for the  
BW36 Series fireplace. Combustible materials must  
not be stored in this area. Combustible walls perpen-  
dicular to the front of the fireplace must be at least 12  
inches from the fireplace opening. Room furnishings  
such as drapes, curtains, chairs, or other com-  
bustibles must be at least 4 feet from the open front of  
the fireplace.  
NEGATIVE AIR PRESSURE WITHIN THE STRUC-  
TURE. This fireplace will operate correctly only if  
adequate ventilation is provided to allow proper draft  
to the fireplace system. Heat-N-Glo assumes no  
responsibility for the improper performance of the  
fireplace system caused by inadequate draft due to  
environmental conditions, downdrafts, tight sealing  
construction of the structure, or mechanical exhaust-  
ing devices which create a negative air pressure with-  
in the structure where the fireplace is located.  
GRATE. The factory installed integral grate must be  
used to hold the logs from falling out of an open fire-  
place and to allow air to pass between the burning  
logs. It is important to keep the fire off the hearth  
and to allow the ashes to collect beneath the fire,  
thereby forming a layer of additional heat protection.  
See Figure 23, page 21. Use only model number  
GR16 integral grate for replacement.  
OUTSIDE AIR. A damper control handle allows the  
individual control of the outside air inlets if your fire-  
place is equipped with this option. Use of outside air  
for combustion is highly recommended to conserve  
heated air within the structure and to provide make  
up air to keep the fireplace venting properly.  
4-00  
23  
30491D  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARRANTY  
FOR HEAT-N-GLO FIREPLACES  
The limited warranty will not become effective until you have mailed the completed warranty card to HEAT-N-GLO,  
A DIVISION OF HEARTH TECHNOLOGIES INC., 20802 Kensington Blvd., Lakeville, MN 55044.  
This card must be mailed within 60 days of the fireplace installation.  
Subject to the conditions set forth herein, Heat-N-Glo extends the following limited warranty with respect to your Heat-N-Glo fireplace, excluding  
accessories, Chimney components and Glass Doors.  
If Heat-N-Glo is satisfied that any part or portion of the fireplace covered by this warranty is defective in material or workmanship under normal  
use and service as described in the operating instructions, Heat-N-Glo will take the following actions:  
1.  
2.  
3.  
4.  
Within the first five (5) years from the date of installation, Heat-N-Glo shall, at its option, replace or repair any  
such defect in material or workmanship, at Heat-N-Glos expense. HEAT-N-GLO SHALL NOT BE RESPONSIBLE FOR  
ANY OTHER LABOR COSTS, OR EXPENSES, INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.  
During the sixth (6th) through the (10th) years after the date of installation, Heat-N-Glo shall supply replacement parts  
or parts at no charge, but SHALL NOT BE RESPONSIBLE FOR ANY LABOR, TRANSPORTATION, OR OTHER INDI-  
RECT DAMAGES.  
During the eleventh (11th) through the fifteenth (15th) years after date of installation, Heat-N-Glo will send to you, FOB  
its factory, replacement parts (if available) at the current minimum wholesale price, but Heat-N-Glo SHALL NOT BE  
RESPONSIBLE FOR ANY LABOR, TRANSPORTATION OR OTHER INDIRECT DAMAGES.  
During the first six (6) months after installation, HEAT-N-GLO shall, at its option, replace or repair the Glass Doors and  
any electrical components, if operation is faulty. (This does not include Glass panels broken during shipment, misuse or  
careless handling.) After the first six (6) months, HEAT-N-GLO will sell to you, FOB its factory, replacement parts at the  
current list price, but HEAT-N-GLO SHALL NOT BE RESPONSIBLE FOR ANY LABOR, TRANSPORTATION OR  
OTHER INDIRECT DAMAGES. IF GLASS DOORS OTHER THAN FACTORY DOORS ARE USED ALL WARRANTY  
AND LIABILITY ON THE FIREPLACE IS VOIDED.  
Heat-N-Glo may discharge its entire warranty liability by refunding the price of the product.  
Products made by other manufacturers, sold with the fireplace or thereafter are not covered by this limited warranty.  
This limited warranty will be void if the fireplace is not installed according to the installation instructions. The limited warranty also is void if the  
fireplace is not operated, at all times, according to the operating instructions furnished. The limited warranty will also be void if the fireplace is  
removed from the place originally installed.  
EXCEPT TO THE EXTENT PROVIDED BY LAW, NO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR  
PURPOSE, AND NO IMPLIED WARRANTIES SHALL APPLY TO THE FIREPLACE AFTER THE ABOVE LIMITED WARRANTY HAS  
EXPIRED.  
In states that do not allow limitations on how long implied warranty lasts, or do not allow exclusion of indirect damages, those limitations or  
exclusions may not apply to you. You may also have additional rights not covered in this limited warranty.  
HEAT-N-GLO reserves the right to make changes at anytime, without notice, in design, material, specifications and prices and the right to dis-  
continue styles and products.  
UNDERWRITERS LABORATORIES FILE NO. MH5850  
No one builds a better fire  
4-00  
24  
30491 REV D  
Download from Www.Somanuals.com. All Manuals Search And Download.  

GPX Portable Radio R300B User Manual
Graco Baby Playpen 1762135 User Manual
Hasbro Electronic Keyboard 87 001 User Manual
Hasbro Robotics 69239 User Manual
Hauppauge TV Receiver WINTV HVR 1250 User Manual
Honeywell Thermostat CT62A User Manual
HP Hewlett Packard Time Clock 6212B User Manual
Humminbird Fish Finder LCR 40ID User Manual
Husqvarna Chainsaw CS 2156 User Manual
Iluv Headphones i913 User Manual