Owner’s Manual
Installation and Operation
Models:
BAY-40, PIER-40
Multi-sided
Woodburning Fireplace
CAUTION
DO NOT DISCARD THIS MANUAL
•
Read, understand
and follow these
instructions for safe
installation and
operation.
•
Leave this manual with
party responsible for
use and operation.
•
Important operating
and maintenance
instructions included.
¨
WARNING
WARNING
HOT SURFACES!
If the information in these instruc-
tions is not followed exactly, a
fire may result causing property
damage, personal injury, or death.
Glass and other surfaces are
hot during operation AND
cool down.
• Do not store or use gasoline or other flam-
mable vapors and liquids in the vicinity of
this or any other appliance.
Hot glass will cause burns.
•
•
•
•
Do not touch glass until it is cooled
NEVER allow children to touch glass
Keep children away
CAREFULLY SUPERVISE children in same room
as fireplace.
• Do not overfire. Overfiring will void your
warranty.
• Comply with all minimum clearances to
combustibles as specified. Failure to
comply may cause house fire.
•
Alert children and adults to hazards of high
temperatures.
High temperatures may ignite clothing or other
flammable materials.
•
Keep clothing, furniture, draperies and other
flammable materials away.
Installation and service of this fireplace should
be performed by qualified personnel. Hearth &
Home Technologies suggests NFI certified or
factory-trained professionals, or technicians
supervised by an NFI certified
WARNING
Fire Risk
•
For use with solid wood fuel or decorative
gas appliance only.
Do not install unvented gas logs.
•
professional.
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
1
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
1
2
Listing and Code Approvals
A. Appliance Certification. . . . . . . . . . . . . . . . . . . . . . . . . 4
4
8
Finishing
27
A. Hearth Extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
B. Finishing Material. . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
C. Mantel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
D. Sidewalls/Surrounds . . . . . . . . . . . . . . . . . . . . . . . . . 29
E. Glass Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Getting Started
5
A. Design and Installation Considerations . . . . . . . . . . . . 5
B. Negative Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
C. Typical Fireplace System. . . . . . . . . . . . . . . . . . . . . . . 7
D. Tools and Supplies Needed. . . . . . . . . . . . . . . . . . . . . 8
E. Inspect Fireplace and Components. . . . . . . . . . . . . . . 8
9
Operating Instructions
30
A. General Information. . . . . . . . . . . . . . . . . . . . . . . . . . 30
B. Outside Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
C. Clear Space Near the Fireplace. . . . . . . . . . . . . . . . . 31
D. Flue Damper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
E. Firescreen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
F. Glass Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
G. Grate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
H. Wood Fuel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
I. Starting a Fire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3
Framing and Clearances
9
A. Selecting Fireplace Location . . . . . . . . . . . . . . . . . . . . 9
B. Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
C. Sidewalls/Surrounds . . . . . . . . . . . . . . . . . . . . . . . . . 11
E. Construct the Chase . . . . . . . . . . . . . . . . . . . . . . . . . 12
F. Chimney Requirements . . . . . . . . . . . . . . . . . . . . . . . 12
4
5
Installation of Fireplace
A. Install the Outside Air Kit . . . . . . . . . . . . . . . . . . . . . . 13
13
10 Troubleshooting
34
Chimney Assembly
16
A. Understanding Vent Problems. . . . . . . . . . . . . . . . . . 34
A. Chimney Requirements . . . . . . . . . . . . . . . . . . . . . . . 17
B. Using Offsets/Returns . . . . . . . . . . . . . . . . . . . . . . . . 18
C. Assemble the Chimney Sections. . . . . . . . . . . . . . . . 19
D. Install the Ceiling Firestops . . . . . . . . . . . . . . . . . . . . 19
E. Install the Attic Insulation Shield . . . . . . . . . . . . . . . . 20
F. Double-check the Chimney Assembly . . . . . . . . . . . . 21
G. Secure the Chimney . . . . . . . . . . . . . . . . . . . . . . . . . 21
B. Diagnostics and Problem Solving . . . . . . . . . . . . . . . 35
11 Maintenance and Servicing the Fireplace 37
A. Disposal of Ashes . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
B. Chimney Inspection/Cleaning . . . . . . . . . . . . . . . . . . 37
C. Firebox Refractory . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
D. Maintenance Task List . . . . . . . . . . . . . . . . . . . . . . . . 38
E. Chimney Fire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
6
7
Complete the Enclosure
22
12 Reference Materials
39
A. Chimney Termination . . . . . . . . . . . . . . . . . . . . . . . . . 22
B. Chase Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
C. Install the Termination Cap . . . . . . . . . . . . . . . . . . . . 24
A. Fireplace Dimensions . . . . . . . . . . . . . . . . . . . . . . . . 39
B. Fireplace Components. . . . . . . . . . . . . . . . . . . . . . . . 40
C. Chimney Components . . . . . . . . . . . . . . . . . . . . . . . . 41
D. Service Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
E. Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
F. Contact Information . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Accessories
26
A. Gas Log/Lighter Provisions . . . . . . . . . . . . . . . . . . . . 26
Note: An arrow (¨) found in the text signifies change in content.
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Listing and Code Approvals
1
A. Appliance Certification
WARNING
This fireplace system has been tested and listed in accor-
dance with UL 127 standards by Underwriters Laboratories
Inc. for installation and operation in the United States.
Improper installation, adjustment, alteration, service
or maintenance can cause injury or property damage.
Refer to the owner’s information manual provided with
this fireplace. For assistance or additional information
consult a qualified installer, service agency or your
dealer.
This fireplace has been tested and listed for use with the
optional components specified in this manual. Glass doors
are required. Optional components may be purchased sep-
arately and installed at a later date. Installation of an outside
air kit will require significant reconstruction and is best if in-
stalled at the time of fireplace installation.
Heat & Glo is a registered trademark of Hearth & Home
Technologies Inc.
Not intended for use as a primary heat source.
This fireplace is tested and approved as a decorative fire-
place. It should not be factored as a primary heat source
in residential heating calculations.
WARNING
Fire Risk
•
•
•
Do not install or operate damaged fireplace.
Do not modify fireplace.
Installation other than as instructed by Hearth & Home
Technologies Inc. is strictly prohibited.
Do not operate the fireplace without fully assembling
all components.
•
•
•
Do not overfire.
Do not install an unvented gas log set. This fireplace
has not been tested for use with unvented gas log
sets.
•
Installation and/or use of any component part not
approved by Hearth & Home Technologies.
Hearth & Home Technologies disclaims any responsibility
for, and the warranty and agency listing will be voided by
the above actions.
4
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
Getting Started
2
A. Design and Installation Considerations
CAUTION
WARNING
Check building codes prior to installation.
Asphyxiation Risk
•
Installation MUST comply with local, regional,
state and national codes and regulations.
Negative pressure can cause spillage of
combustion fumes and soot. Fire needs to draft
properly for safe operation.
•
Consult insurance carrier, local building inspector,
fire officials or authorities having jurisdiction about
restrictions, installation inspection and permits.
B. Negative Pressure
Negative pressure results from the imbalance of air avail-
able for the fireplace to operate properly. Causes for this
imbalance include:
When planning a fireplace installation, it is necessary to de-
termine the following information before installing:
•
Where the fireplace is to be installed. See Sections
3 and 4.
•
•
•
Exhaust fans (kitchen, bath, etc.).
Range hoods.
Combustion air requirements for furnaces, water heaters
and other combustion appliances.
Clothes dryers.
•
The vent system configuration to be used. See Sections
5 and 6.
•
•
•
•
Gas supply piping. See Section 7.
Electrical wiring. See Section 7.
Framing and finishing details. See Sections 3, 6 and 8.
Whether optional accessories—devices such as a fan, wall
switch or remote control—are desired. See Section 12.
•
•
Location of return-air vents to furnace or air
conditioning.
•
•
Imbalances of the HVAC air handling system.
Upper level air leaks: recessed lighting, attic hatch
opening, duct leaks.
Draft is the pressure difference needed to vent fireplaces
successfully. Considerations for successful draft include:
To minimize the effects of negative air pressure, the follow-
ing must be considered:
•
•
Preventing negative pressure
Location of fireplace and chimney
•
Install the outside air kit. Install the intake on the side of
the house towards prevailing winds during the heating
season.
•
•
•
•
Ensure adequate outdoor air is supplied for combustion
appliances and exhaust equipment.
Ensure furnace and air conditioning return vents are not
located in the immediate vicinity of the fireplace.
Avoid installing the fireplace near doors, walkways or small
isolated spaces.
Recessed lighting should be a “sealed can” design; attic
hatches weather stripped or sealed; attic mounted duct
work and air handler joints and seams taped or sealed.
Basement installations should be avoided due to stack
effect. Stack effect creates negative pressure in lower
levels. Hearth & Home Technologies recommends the
use of direct vent fireplaces in basements.
•
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Location of the fireplace and chimney will affect performance.
As shown in Figure 2.1 the chimney should:
•
Be installed through the warm airspace enclosed by the
building envelope. This helps to produce more draft,
especially during lighting and die-down of the fire.
Penetrate the highest part of the roof. This minimizes the
effects of wind turbulence.
•
•
Be located away from trees, adjacent structures, uneven
roof lines and other obstructions.
Offsets can restrict draft so their use should be minimized.
Consider the fireplace location relative to floor and ceiling
and attic joists.
Recommended
Recommended
Location
Location
Marginal
Location
Location
Not
Recommended
Location
Not
Recommended
Windward
Outside Air Intake
Leeward
Multi-level Roofs
Figure 2.1 Recommended Chimney Locations
6
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
C. Typical Fireplace System
The Heat & Glo fireplace system consists of the following:
•
•
•
•
•
•
Fireplace/integral grate/refractory/outside air system
Refractory
Chimney termination cap
Chimney system
Hearth extension
Glass Doors
Optional components include:
Chimney air kit
•
Additional lateral
Termination cap
Storm Collar
support for chimney
above roof (or enclosed
in chase) if needed
Non-combustible
roof flashing maintains
minimum clearance
around chimney
Chimney penetrates roof
preferably without affecting
roof rafters
Support straps
on rafter supports
chimney (not shown)
Offset/Return (with hanger straps)
Attic insulation shield (not shown) must
be used here to keep insulation away
from chimney if attic is insulated
Ceiling firestop
on floor of attic
Chimney system
Framing headed off
in ceiling joists
Combustible
framing/header
on top of
Enclosed space above
and around fireplace
V-shaped
standoffs
(spacers)
Mantel and surround
Decorative facing
and trim
Hearth extension
Outside
combustion air
Factory-built fireplace
Protective metal
hearth strip(s)
Figure 2.2 Typical Fireplace System
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
7
Download from Www.Somanuals.com. All Manuals Search And Download.
D. Tools and Supplies Needed
E. Inspect Fireplace and Components
Before beginning the installation be sure the following tools
and building supplies are available:
WARNING
Fire Risk
Reciprocating saw
Pliers
Framing material
High temp caulking material
Gloves
Explosion Risk
Inspect fireplace and components for
damage. Damaged parts may impair safe
operation.
Hammer
Phillips screwdriver
Framing square
•
•
•
Do NOT install damaged components.
Do NOT install incomplete components.
Do NOT install substitute components
Flat blade screwdriver Electric drill and bits
Plumb line
Level
Safety glasses
Tape measure
Report damaged parts to dealer.
1/2-3/4 in. length, #6 or #8 self-drilling screws
Misc. screws and nails
•
•
Carefully remove the fireplace and components from the
packaging.
The vent system components and doors are shipped in
separate packages.
•
•
Report to your dealer any parts damaged in shipment.
Read all the instructions before starting the installation.
Follow these instructions carefully during the
installation to ensure maximum safety and benefit.
CAUTION
•
•
Keep fireplace dry.
Mold or rust may cause odors.
8
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
Framing and Clearances
WARNING
3
Note:
•
Illustrations and photos reflect typical installations
Fire Risk
and are FOR DESIGN PURPOSES ONLY.
Illustrations/diagrams are not drawn to scale.
Actual installation/appearance may vary due to
individual design preference.
Hearth & Home Technologies reserves the right to
alter its products.
Provide adequate clearances.
•
•
•
•
•
Around air openings
To combustibles
For service access.
•
Locate fireplace away from traffic areas.
Locating the fireplace in a basement, near frequently opened
doors, central heat outlets or returns, or other locations of
considerable air movement can affect the performance and
cause intermittent smoke spillage from the front of the fire-
place. Consideration should be given to these factors before
deciding on a location. See Sections 2 and 10.
A. Selecting Fireplace Location
Several options are available to you when choosing a loca-
tion for your fireplace. This fireplace may be used as a room
divider, installed along a wall, across a corner or used in an
exterior chase. See Figure 3.1.
12 in. (305 mm)
from opening of
fireplace
62 in.
(1575 mm)
72 in.
(1829 mm)
16 in.
(406 mm)
Note:
1/2 in. min. distance from
fireplace to combustible
materials.
16 in.
(406 mm)
56 in.
40-1/2 in.
In addition to these
framing dimensions,
also reference the
following sections:
• Clearances (Section
3.B.)
Note:
(1422 mm)
(1029 mm)
26 in.
6 in.
(152 mm)
(660 mm)
to front of
fireplace
opening
HEARTH
EXTENSION
(shaded)
HEARTH
EXTENSION
(shaded)
• Mantel Projections
(Section 8.C)
• Fireplace Dimensions
(Section 12.A.)
64 in.
(1626 mm)
64 in.
(1626 mm)
BAY-40
PIER-40
Figure 3.1 Fireplace Locations
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
9
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Clearances
WARNING
Fire Risk
•
•
Comply with all minimum clearances to combustibles as specified.
Framing or finishing material used on the front of, or in front of, the
appliance closer than the minimums listed, must be constructed entirely
of noncombustible materials (i.e., steel studs, concrete board, etc.).
Failure to comply may cause fire.
Storm Collar
(roof)
Roof Flashing
2 in. (51 mm) min.
2 in. min.
(51 mm)
Attic
Insulation
Shield
(attic)
Ceiling Firestop
(ceiling)
2 in. (51 mm) min.
Ceiling Firestop
2 in. (51 mm) min.
Offset/Return with
hanger straps
(ceiling)
2 in. (51 mm) min.
2 in. (51 mm) min.
Must have 2 in. (51 mm)
minimum clearance
to header
0 in. to level
of standoffs
1/2
in. [13 mm] to back
of appliance
0 in.
to floor
1/2 in. (13 mm) to
side of appliance
Figure 3.2 Clearances to Combustible Materials
10
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
C. Sidewalls/Surrounds
Adjacent combustible side walls must be located a minimum distance from the fireplace opening as per Figure 3.3.
12 in. (305 mm)
62 in.
(1575 mm)
from opening of
fireplace
72 in.
(1829 mm)
16 in.
(406 mm)
Note:
Note:
1/2 in. min. distance from
fireplace to combustible
materials.
16 in.
(406 mm)
56 in.
40-1/2 in.
(1029 mm)
In addition to these
framing dimensions,
also reference the
following sections:
• Clearances (Section
3.B.)
(1422 mm)
26 in.
6 in.
(152 mm)
(660 mm)
to front of
fireplace
opening
HEARTH
HEARTH
EXTENSION
(shaded)
EXTENSION
(shaded)
• Mantel Projections
(Section 8.C)
• Fireplace Dimensions
(Section 12.A.)
64 in.
(1626 mm)
64 in.
(1626 mm)
BAY-40
PIER-40
Figure 3.3 Sidewalls and Surrounds
D. Frame the Fireplace
Figure 3.4 shows a typical framing (using 2 x 4 lumber) of the fireplace, assuming combustible materials are used. All re-
quired clearances to combustibles around the fireplace must be adhered to. See Figure 3.2. Any framing across the top of
the fireplace must be above the level of the top standoffs.
2 in. (51 mm) minimum air space
2 in. (51 mm) minimum air space
clearance to enclosure
clearance to enclosure
Mantel
Mantel
12 in. max.
(305 mm)
12 in. max.
(305 mm)
47-1/8 in. (1197 mm)
Header Height
47-1/8 in. (1197 mm)
Header Height
PIER-40
BAY-40
Figure 3.4 Framing the Fireplace
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Gas line holes and other openings should be caulked with
high temperature caulk or stuffed with unfaced fiberglass in-
sulation. If the fireplace is being installed on a cement slab,
we recommend that in cold climates, a sheet of plywood or
other raised platform be placed underneath to prevent con-
ducting cold up into the room.
E. Construct the Chase
Achase is a vertical boxlike structure built to enclose the fire-
place and/or its vent system. Vertical chimneys that run on
the outside of a building must be installed inside a chase.
Construction of the chase may vary with the type of build-
ing. These instructions are not substitutes for the require-
ments of local building codes. Local building codes MUST
be checked.
Three examples of chase applications are shown in Fig-
ure 3.6.
Chases should be constructed in the manner of all outside
walls of the home to prevent cold air drafting problems. The
chase should not break the outside building envelope in any
manner. All outer walls need to be insulated.
1. Fireplace and chimney enclosed in an exterior chase.
2. Chimney offset through exterior wall and enclosed in
chase.
3. Chase constructed on roof.
Building codes require false ceiling and ceiling firestops at
each floor of the chase or every 10 ft (3.05 m) of clear space
to control spread of fire.
Walls, ceiling, base plate and cantilever floor at the first level
of the chase should be insulated. See Figure 3.5. Vapor and
air infiltration barriers should be installed in the chase as per
regional codes for the rest of the home. Additionally, Hearth
& Home Technologies recommends that the inside surfac-
es be sheet rocked and taped (or the use of an equivalent
method) for maximum air tightness.
Round Termination Cap
Metal Chase Top
2
1
Figure 3.6 Chase Constructions
Ceiling
Firestop
F. Chimney Requirements
When planning your fireplace location, the chimney con-
struction and necessary clearances must be considered.
The fireplace system and chimney components have been
tested to provide flexibility in construction. Vertical distances
are measured from the base of the fireplace as shown in
Figure 5.2.
False Ceiling
• Minimum overall straight height
• Minimum height with offset/return
• Maximum height
14
(4.27 m)
(5.03 m)
16.5 ft
90 ft (27.43 m)
20 ft (6.1 m)
• Maximum chimney length between an offset
and return
Figure 3.5 Chase Assembly
• Maximum distance between chimney
stabilizers
35 ft (10.67 m)
• Double offset/return minimum height
20 ft
6 ft
(6.1 m)
• Maximum unsupported chimney length
between the offset and return
(1.83 m)
• Maximum unsupported chimney height above
the fireplace
35 ft (10.67 m)
6 ft (1.83 m)
• Maximum unsupported chimney above roof
Note: A maximum of two pairs of offsets and returns may
be used.
12
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation of Fireplace
4
WARNING
CAUTION
Fire Risk
Asphyxiation Risk
Do not draw outside combustion air from:
harp Edges
•
Wear protective gloves and safety glasses
during installation.
•
•
Wall, floor or ceiling cavity.
Enclosed space such as an attic or
garage.
•
Close proximity to exhaust vents or
chimneys.
Fumes or odor may result.
A. Install the Outside Air Kit
This fireplace will operate correctly only if adequate ventila-
tion is provided to allow proper draft to the fireplace system.
See Section 2.
CAUTION
Risk of Smoke Spillage
The outside air kit is supplied with this fireplace. Using an
outside air kit is highly recommended to minimize the effects
of negative pressure within the structure. We recommend
you utilize the shortest duct run to optimize the performance
of the outside air kit. Cold air flow can be minimized by put-
ting a small dip in the duct creating a cold air trap. This trap
can also help prevent heat build-up and exhausting out the
intake due to the stack effect. The outside air kit inlet should
be positioned in a manner that will not allow snow, leaves,
etc. to block the inlet. In some installations the air duct
may need to be run vertically. In such an installation, a 3 ft
(.914 m) height difference must be maintained from the top
of the uppermost chimney section to the outside combustion
air inlet. See Figure 4.2.
Outside air inlet must be located to prevent blockage
from:
• Leaves
• Snow/ice
• Other debris
Blockage may cause combustion air starvation.
The outside air kit is installed on the right side (PIER-40)
or open end (BAY-40) of the fireplace. See Figure 4.4 for
handle location/operation.
Remove the cover plate from the side (PIER-40) or bottom
(BAY-40) of the fireplace assembly where the air kit is to be
installed.
See Figure 4.3 for proper placement of outside air inlet.
Flexible Duct
(not supplied)
Outside Air
Plate
Assembly
Outside Air
Shield
2 Wire Ties
Figure 4.1 Outside Air Installation
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
13
Download from Www.Somanuals.com. All Manuals Search And Download.
LIFT TO
OPEN
Attic insulation shield
must be used to keep
insulation away from
chimney.
3 ft min. from top of
uppermost chimney
section to air inlet.
BAY-40
Ceiling firestop
on floor of attic.
PULL TO
OPEN
PIER-40
Figure 4.4 Locating the Outside Air Control
Figure 4.2 Outside Air Inlet Locations
NO
NO
Garage or
combustible
liquids storage
NO
Outlet blocked by
snow, leaves, etc.
Attic space
NO
Outlet placed
higher than 3 ft
below the
termination cap
YES
Clear area
Factory-built
fireplace
outside
house or in
ventilated
crawl space
Use only duct materials specified
by manufacturer (preferably with
short run or mainly straight duct,
except small dip for cold air trap
which will help prevent flow of cold air).
Figure 4.3 Outside Combustion Air Placement
14
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Secure the Fireplace
• Position the Fireplace
This fireplace may be placed on either a combustible or
noncombustible continuous flat surface. Follow the in-
structions for framing in Section 3.D. Slide the fireplace
into position. Be sure to provide the minimum air clear-
ance at the sides and back of the fireplace assembly.
See Section 3.B.
WARNING
Fire Risk!
•
Prevent contact with sagging, loose
insulation.
•
Do NOT install against vapor barriers or
exposed insulation.
1 in. (25 mm)
overlap
• Place the Protective Metal Hearth Strips
Metal strips 2 in. (51 mm) under the edges
of the fireplace and must extend beyond the
front and side openings by 2 in. (51 mm)
WARNING
Figure 4.5 Position the Protective Metal Hearth Strips
Fire Risk!
•
Metal hearth strips MUST be installed.
Top piece must overlap
bottom piece
Sparks or embers may ignite flooring.
Included with your fireplace you will find two metal
hearth strips measuring approximately 26 in. x 4 in.
(660 mm x 102 mm). These strips are used to provide
added protection where the fireplace and the hearth ex-
tension meet.
Raised Platform
2 in.
(51 mm)
1 in. (25 mm) min.
overlap
Floor
Slide each metal strip 2 in. (51 mm) under the front
edge of the fireplace. The individual pieces must over-
lap each other by 1 in. (25 mm) minimum in the middle
of the fireplace to provide continuous coverage of the
floor. See Figure 4.5. These metal strips should extend
from the front and sides of the fireplace opening by 2 in.
(51 mm).
2 in.
(51 mm)
Figure 4.6 Protect the Front of an Elevated Platform
Note: When elevating the fireplace above the hearth exten-
sion the front of the elevated platform must be protected with
a protective metal hearth strip as shown in Figure 4.6.
• Level the Fireplace
Level the fireplace side-to-side and front-to-back. Shim
with noncombustible material, such as sheet metal, as
necessary. Secure the fireplace (using the nailing flang-
es located on either side of the fireplace) to the vertical
framing.
Important: To ensure proper fit of the glass doors, check
the fireplace opening for square. Measure diagonal dis-
tances of the opening to make sure they are equal. If they
are not, continue to shim the fireplace until those diagonals
are equal.
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Chimney Assembly
5
Termination Cap
Chimney must extend
beyond combustible
roof structure
Additional
support for
tall chimneys
Maintain minimum
height of chimney
above roof
Storm Collar
Install roof flashing
according to minimum
requirements
Maintain minimum
clearances to
combustibles as
specified
Offsets/returns
may not exceed
30° from vertical
Support straps for offsets/
returns must be secured
to adequate framing
Lock chimney
sections together
firmly to resist
movement
Ceiling firestops
are required where
chimney passes
through ceiling or
floor
Figure 5.1 Typical Chimney System - Guidelines for Chimney System Installation
NOTE:
•
•
Chimney performance may vary.
Trees, buildings, roof lines and wind conditions affect
performance.
•
Chimney height may need adjustment if smoking or
overdraft occurs.
16
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
A. Chimney Requirements
Vertical distances are measured from the base of the fire-
place as shown in Figure 5.2.
To determine the chimney components needed to complete
your particular installation, follow the steps below:
•
Determine the total vertical height of the fireplace
installation. This dimension is measured from the base of
the fireplace assembly to the point where the smoke exits
the termination cap.
• Minimum overall straight height
• Minimum height with offset/return
• Maximum height
14
(4.27 m)
(5.03 m)
16.5 ft
90 ft (27.43 m)
20 ft (6.1 m)
•
Subtract the effective height of the fireplace assembly from
the overall height of the fireplace installation (measured
from the base of the fireplace to the bottom of the
termination cap).
• Maximum chimney length between an offset
and return
• Maximum distance between chimney
stabilizers
35 ft (10.67 m)
•
•
Refer to Table 5.1 to determine what components must
be selected to complete the fireplace installation.
Determine the number of ceiling firestops, stabilizers,
roof flashing, etc. required to complete the fireplace
installation.
• Double offset/return minimum height
20 ft
6 ft
(6.1 m)
• Maximum unsupported chimney length
between the offset and return
(1.83 m)
• Maximum unsupported chimney height above
the fireplace
35 ft (10.67 m)
6 ft (1.83 m)
• Maximum unsupported chimney above roof
6 ft (1.83 m) max.
unsupported chimney
above roof
Note: A maximum of two pairs of offsets and returns may
be used.
WARNING
6 ft (1.8 m) max.
unsupported
run
Fire Risk
20 ft (6.10 m) max.
pipe between an
offset & return
•
Must maintain 2 in. (51 mm) air clearance
to insulation and other combustible
materials.
35 ft (10.7 m)
max. straight
Ceiling Firestop
unsupported
chimney height
Table 5.1
HEIGHT OF CHIMNEY COMPONENTS
Chimney Stabilizer
in.
mm
13.25 ft (4.04 m) min. height/single offset-return
20 ft. (6.10 m) min. height/double offset-return
44 in.
(1118 mm)
Effective
Height
90 ft (27.4 m) max. height
SL11
4-3/4
121
Ceiling Firestops
FS538
0
0
0
0
FS540
Offsets/Returns
Figure 5.2 Chimney Requirements
SL1130
18
457
Roof Flashing
RF570
0
0
0
0
RF571
Chimney Sections*
SL1106
4-3/4
10-3/4
16-3/4
34-3/4
46-3/4
121
273
425
883
1187
CAUTION
SL1112
SL1118
•
•
Do NOT connect this fireplace to a chimney flue
servicing another appliance.
Do NOT connect to any air distribution duct or
system.
SL1136
SL1148
* Dimensions reflect effective height.
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
17
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Using Offsets/Returns
To bypass any overhead obstructions, the chimney may be
offset using an offset/return.
•
Measure how far the chimney needs to be shifted to enable
it to avoid the overhead obstacle. See Figure 5.3. Use
dimension “A” to determine chimney section required to
achieve the needed shift.
An offset and return may be attached together or a chimney
section(s) may be used between an offset and return.
•
•
•
After determining the offset dimension, refer to Table 5.2
and find the “A” dimension closest to but not less than the
distance of shift needed for your installation.
The “B” dimension that coincides with the “A” dimension
represents the required vertical clearance that is needed
to complete the offset and return.
Read across the chart and find the number of chimney
sections required and the model number of those particular
chimney parts.
Whenever the chimney penetrates a floor/ceiling, a ceiling
firestop must be installed.
The effective height of the fireplace assembly is measured
from the base of the fireplace to the top of the starter collar.
See Dimensions in Section 12.
Perform the following steps to determine the correct chim-
ney component combination for your particular installation:
WARNING
Fire Risk
•
•
•
Draft will be restricted if offset/returns
greater than 30° are used.
Table 5.2
A
B
A
in.
mm
in.
mm
454
SL1106 SL1112 SL1118 SL1136 SL1148
4 7/8
124
184
248
260
324
337
400
460
476
552
565
629
705
718
781
857
933
1010
1045
1162
1222
1314
17 7/8
22
-
1
2
-
-
-
-
-
-
-
-
-
7 1/4
559
9 3/4
26 1/8
27 1/4
31 3/8
32 3/8
36 5/8
40 3/4
41 3/4
47
664
-
-
-
-
B
10 1/4
12 3/4
13 1/4
15 3/4
18 1/8
18 3/4
21 3/4
22 1/4
24 3/4
27 3/4
28 1/4
30 3/4
33 3/4
36 3/4
39 3/4
41 1/8
45 3/4
48 1/8
51 3/4
692
1
1
-
-
-
-
797
1
-
-
-
-
822
1
-
-
-
930
-
2
2
1
-
-
-
1-1/4 in. (32 mm)
OVERLAP
1035
1060
1194
1219
1324
1457
1483
1588
1721
1854
1984
2092
2248
2356
2511
1
-
-
-
-
1
2
-
-
-
Figure 5.3 Chimney Offset/Return
-
-
-
Example: Your “A” dimension from Figure
5.3 is 14 1/2 in. (368 mm). Using Table
5.2 the dimension closest to, but not less
than 14 1/2 in. (368 mm) is 15 3/4 in.
(400 mm) using a 30° offset/return. It is
then determined from the table that you
would need 36 5/8 in. (930 mm) (Dimen-
sion “B”) between the offset and return.
The chimney components that best fit your
application are two SL1112s.
4 8
-
-
1
1
1
-
-
52 1/8
57 3/8
58 3/8
62 1/2
67 3/4
73
1
-
-
-
-
1
-
-
-
-
-
1
1
1
1
-
1
-
-
-
-
1
-
-
-
-
1
-
-
78 1/8
82 3/8
88 1/2
92 3/4
98 7/8
-
-
2
2
1
1
-
1
-
-
-
-
-
-
1
1
2
1
-
-
-
-
-
Proper assembly of air cooled chimney parts results in an overlap of chimney joints
of 1-1/4 in. (32 mm). Effective length is built into this table.
18
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
C. Assemble the Chimney Sections
Note: The ceiling firestop MUST be nailed to the bottom
of the ceiling joists EXCEPT when the space above is
uninsulated and the attic insulation shield is not being used
(see Figure 5.5). When the attic insulation shield is used
the ceiling firestop may be above or below the joist of an
insulated ceiling.
Attach either a straight chimney section or an offset to the
top of the fireplace (depending on your installation require-
ment). Chimney sections are locked together by pushing
downward until the top section meets the stop bead on the
lower section.
The inner flue is placed to the inside of the flue section below
it. The outer casing is placed outside the outer casing of the
chimney section below it. See Figure 5.4.
ROOM ABOVE (non-insulated ceiling)
B
A
Ceilng firestop from
bottom
ATTIC ABOVE (insulated ceiling)
Ceiling firestop from
top
When attic insulation
shield not used
Figure 5.4 Assembling Chimney Sections
Note: Inner flue and outer liner sections cannot be disas-
sembled once locked together. Plan ahead to ensure the
proper installation height is achieved with the selected
chimney components.
Note: Use same dimensional lumber for framing
ceiling firestop and joists.
A
B
WARNING
Fire Risk
Catalog #
FS538
in.
17
17
mm
432
432
in.
17
26
mm
432
660
FS540
Do NOT install substitute or damaged
chimney components.
•
MUST use chimney system described in
this manual.
Figure 5.5 Installing the Ceiling Firestop
•
NO OTHER chimney components may
be used.
Substitute or damaged chimney components
may impair safe operation.
Note: You must provide support for the pipe during con-
struction and check to be sure inadvertent loading has not
dislodged the chimney section from the fireplace or at any
chimney joint.
D. Install the Ceiling Firestops
•
•
•
Mark and cut an opening in the ceiling for the ceiling
firestop being used. See Figure 5.5.
Frame the opening with the same size lumber used in the
ceiling joists.
CAUTION
•
•
Ceiling firestops must be used at ceiling/floor.
Chase construction requires ceiling firestops at each
floor or every 10 ft (3.05 m) of clear space.
Use same dimensional lumber as joists.
Install the ceiling firestop.
•
Ceiling firestop slows spread of fire and reduces cold air
infiltration.
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
19
Download from Www.Somanuals.com. All Manuals Search And Download.
E. Install the Attic Insulation Shield
¨
Tabs bent in to
rest against pipe
Pipe
WARNING
Attic Insulation Shield
Fire Risk
•
DO NOT pack insulation or other
17 in. (432 mm)
diameter
combustibles: between ceiling firestops;
between chimney and attic insulation
shield.
6 Tabs bent
in 90°
Ceiling Firestop
•
•
ALWAYS maintain specified clearances
around chimney and ceiling firestop
systems.
Pipe
Insulation
Insulation
Install ceiling firestops as specified.
13 in.
(330 mm)
Failure to keep insulation or other material
away from chimney pipe may cause fire.
Figure 5.7 Install Attic Insulation Shield Above the Ceiling
An insulation shield must be installed when there is a pos-
sibility of insulation coming into contact with the factory built
chimney system. Installation of a ceiling firestop is required
(see Figures 5.7 and 5.8).
¨
Tabs bent in to
rest against pipe
•
Roll the shield (around the chimney if already installed)
until you have a 3 in. (76 mm) overlap and the three holes
on each side match up (large holes on top).
Insert three screws into the matching holes to form a
tube.
Bend three tabs on the bottom of the tube inward to 90°
to maintain chimney clearance. See Figure 5.6.
Rest the insulation shield on the ceiling firestop below.
Bend the three short tabs at the top of the shield inward
to 90° to maintain the 2 in. (51 mm) clearance from the
chimney.
Pipe
Attic Insulation Shield
17 in. (432 mm)
diameter
•
•
6 Tabs bent
in 90°
Insulation
Insulation
•
•
13 in.
(330 mm)
Ceiling Firestop
Pipe
•
Bend the remaining top tabs to just meet the pipe.
Figure 5.8 Install Attic Insulation Shield Below the Ceiling
¨
Bend remaining tabs
to rest against pipe to
prevent insulation
If you wish to make a custom shield or barrier, follow these
guidelines:
Bend inward
from falling in.
90°
•
Metal is preferred, although any material stiff enough to
hold up against the insulation can be used.
The shield or barrier must be tall enough to extend above
the insulation and prevent blown-in insulation from spilling
into the cavity.
Insert three
screws
•
•
•
Maintain specified cleaances around chimney.
Check instructions and local codes for further details.
3 in. (76 mm)
overlap
Figure 5.6 Prepare Attic Insulation Shield
20
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
F. Double-check the Chimney Assembly
Continue assembling the chimney sections up through the
ceiling firestops as needed. While doing so, be aware of the
height and unsupported chimney length limitations given un-
der Section 5.A. Chimney Requirements.
Check each section by pulling up slightly from the top to en-
sure proper engagement before installing the succeeding
sections. If they have been connected correctly, they will not
disengage when tested.
Ceiling
Firestop
Straps
Joint
Band
(Optional)
G. Secure the Chimney
Optional
When offsets and returns are joined to straight pipe sections,
they must be locked into position with the screws provided*
(outer only), using the predrilled holes. To prevent gravity
from pulling the chimney sections apart, the returns and the
chimney stabilizers have hanger straps for securing these
parts to joists or rafters. See Figure 5.9.
Additional
Support
Figure 5.9 Secure the Chimney
*
or equivalent #6 or #8 sheet metal screw no longer than
3/4 in. (19 mm).
WARNING
Fire Risk
•
Secure offsets with screws (not to exceed
3/4 in./19 mm in length).
•
•
Secure returns with strapping.
Straight chimney sections may be secured with screws
(not to exceed 3/4 in./19 mm in length) at the joints.
Keep chimney sections from separating or twisting.
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Complete the Enclosure
6
A. Chimney Termination
Chimney Termination Requirements (See Figures 6.1 and 6.2)
•
•
•
Must have a cap approved and listed for this fireplace system
Must not be located where it will become plugged by snow or other material
Must terminate at least 3 ft (914 mm) above the roof and at least 2 ft (610 mm) above any portion of the roof within 10 ft
(3.05 m)
•
Must be located away from trees or other structures
Slanted Roofs
Chimney must extend 2 ft (.6 m)
above any portion of the roof
within 10 ft (3 m) of the chimney
above the roof
Chimney must
extend 3 ft (.9 m)
Flat Roofs
Chimney must extend 2 ft (.6 m)
above any portion of the roof
within 10 ft (3 m) of the chimney
Chimney must
extend 3 ft (.9 m)
above the roof
Figure 6.1 Termination Requirements
Gas, Wood or Fuel
Termination Caps Same Height
Oil Termination
8 ft
(2.44 m)
Gas, Wood or Fuel
Oil Termination
A
(min. for B-Vent)
20 in.
18 in.
8 ft
(2.44 m)
(457 mm)
(508 mm)
(min. for direct vent)
to
(min. for B-Vent)
20 in.
B
20 in. min. *
(508 mm)
Wood
Perpendicular
Wall
(508 mm)
(min. for direct vent)
to
Gas
Termination
Perpendicular
Wall
Termination Caps Staggered Height
* If using decorative cap cover(s), this distance may
need to be increased. Refer to the installation instruc-
tions supplied with the decorative cap cover.
A
B
Gas Termination Wood or Fuel Oil Termination
6 in. (152 mm) min.
20 in. (508 mm) min.
Figure 6.2 Multiple Chimneys
22
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
Mark the Exit Point of the Roof
Locate the point where the chimney will exit the roof by
plumbing down to the center of the chimney. Drive a nail
up through the roof to mark the center. See Figure 6.3.
¨Cut Out the Hole in the Roof
Measure to either side of the nail and mark the 17 in.
x 17 in. (432 mm x 432 mm) opening required. This is
measured on the horizontal; actual length may be larger
depending on the pitch of the roof. Cut out and frame the
opening. See Chapter 25 of the Uniform Building Code
for roof framing details.
WARNING
Fire Risk
•
Must maintain 2 in. (51 mm) air clearance
to insulation and other combustible
materials.
Assemble the Chimney Sections Through the
Roof
Continue to add chimney sections through the roof open-
ing, maintaining at least a 2 in. (51 mm) air space to com-
bustible materials.
Install the Roof Flashing
If a roof flashing is to be used, install the roof flashing
appropriate to the roof pitch and install a round termination
cap and storm collar following the instructions shipped with
the cap.
Figure 6.3 Ceiling/Attic Construction
Install the Chimney Air Kit (required in Canada):
When installing the chimney air kit, follow the instructions
provided with this accessory.
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
23
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Chase Top
C. Install the Termination Cap
A metal chase top is required to seal the top of the chase
around the chimney pipe. The top should include a turn-
down and drip edge to prevent water from seeping into the
chase. Provide a 1/8 in. (3 mm) gap around the flue pipe
and slope the top downward away from the penetration. See
Figure 6.4.
Note: To protect against the effect of corrosion on those
parts exposed to the weather, the termination cap can be
painted with a rust-resistant paint.
WARNING
•
•
All seams must be caulked to prevent leaks.
A chase installation must use a chase top. Chase tops
are available from your Heat & Glo dealer or may be field
constructed.
Fire Risk
•
The minimum overlap of cap to pipe
MUST be met or chimney may separate
from cap.
•
Attach the chase top to the top of the chase.
Separation allows sparks, heat and embers
to escape.
Termination Cap
•
Install the chimney sections up through the chase
enclosure. When using a TR11 Round Termination Cap,
the uppermost top section of pipe must extend 6 in.
(152 mm) above the top of the flashing collar to allow
installation of the storm collar and termination cap. See
Figure 6.5.
2 in. (51 mm) Collar
on Chase Top
Caulk
Storm Collar
Slope Downward
Turn-down
Drip Edge
Minimum 1-1/2 in. (38 mm) overlap of cap over pipe
Storm Collar
2 in. (51 mm) min.
Chase
(Chimney)
6 in. (152mm) min.
Flashing Collar
2 in. (51 mm) min. collar
.018 (26 ga) min.
Galvanized
Chase Top
Figure 6.4 Chase Top Construction
Figure 6.5 Installing a TR11 Round Termination Cap
•
For installations utilizing a TR11T Round Telescoping
Termination Cap, the uppermost chimney section must be
below the top of the chase top, but not more than 14-1/2 in.
(368 mm) below the top of the chase top. Minimum overlap
of chimney and termination cap must be 1-1/2 in. (38 mm).
See Figure 6.6.
Storm Collar
Flashing Collar
2 in. (51 mm) min.
14-1/2 in. (368mm) max.
Top of Pipe
1-1/2 in. (38 mm) min.
overlap
Figure 6.6 Installing a TR11T Round Telescoping Termination Cap
24
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
•
For installations utilizing an ST1175 Square Termination
Cap the last chimney section must not be more than
4-1/2 in. (114 mm) below the chase top. See Figure 6.7.
•
For chase installations you can use a TR11 Round
Termination Cap, a TR11T Round Telescoping Termination
Cap, an ST1175 Square Termination Cap, or a TCT1175
Terra Cotta Termination Cap.
•
•
For installations utilizing a European Copper Series
Termination Cap, See Figure 6.9.
Flashing Collar
Install termination caps following instructions provided
with them.
Cap Standoff
2 in. (51 mm) min.
4-1/2 in.
(114 mm)
max.
1-1/2 in.
(38 mm) min.
overlap
Top of Pipe
Cap Base
Figure 6.7 Installing an ST1175 Square Termination Cap
(cap inner flue)
•
For installations utilizing an TCT1175 Terra Cotta Cap the
last chimney section must be between 7 in. (178 mm) below
the chase top and 2 in. (51 mm) above. See Figure 6.8.
bracket (8)
screw (8)*
The last section of pipe
must stop between the
distances given below.
chimney top
2 - 6 in.
(51-152 mm)
chase
top
1-1/2 in. (38 mm)
min. overlap
2 in. (51 mm)
(metal or masonry)
SL pipe
inner flue
typical
2 in. (51 mm) above top
of the chase.
{
7 in. (178 mm) below top
Figure 6.9 Installing a European Copper Series Termination Cap
(CT3-King shown)
of the chase.
Top of Pipe
Figure 6.8 Installing a TCT1175 Terra Cotta Cap
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessories
7
A. Gas Log/Lighter Provisions
A certified gas log lighter or decorative gas log set can be
installed in this fireplace.
WARNING
Asphyxiation Risk
•
•
Maximum input is 100,000 BTU/hr.
•
Damper must be locked open when gas logs
installed.
Decorative gas appliance must be certified to ANSI Z21.60
“Standard for Decorative Gas Appliances for Installation
in Vented Fireplaces”.
Gas fire generates fumes.
•
Must be installed in accordance with the National Fuel
Gas Code, ANSI Z223.1.
WARNING
•
•
A log set must incorporate a gas shutoff.
Log set requires the damper to be locked fully open.
Fire Risk
•
For use with solid wood fuel or decorative
gas appliance only.
DO NOT install unvented gas logs.
Knockouts are provided on both sides of the fireplace and in
refractories for 1/2 in. (13 mm) iron pipe.
•
•
We recommend you seal refractory around pipe with
fireplace mortar or high temperature, noncombustible
sealant.
WARNING
Fire Risk
•
•
Repack insulation from the knockout around the pipe.
Maintain 1-1/2 in. (38 mm) air space around the pipe for
4 in. (102 mm) beyond the fireplace.
Explosion Risk
Inspect appliance and components for
damage. Damaged parts may impair safe
operation.
•
See Figure 7.1.
Outer Shell
of Fireplace
•
•
•
Do NOT install damaged components.
Do NOT install incomplete components.
Do NOT install substitute components
Firebox
Maintain air clearance
to combustibles.
Report damaged parts to dealer.
Refractory
Combustible
Materials
Seal with
fireplace mortar
or high temp
noncombustible
sealant
1-1/2 in.
(38 mm)
air space
Gas Line
Gas Line
Combustible materials
may be located at zero
clearance to gas line
beyond 4 in. (102 mm)
from fireplace side.
Repack
Insulation
Knockout
4 in.
(102 mm)
Figure 7.1 Gas Line Installation
26
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
Finishing
8
A. Hearth Extension
High temperature
(300°F min.) continuous,
non-combustible sealant
A hearth extension must be installed with all fireplaces to
protect the combustible floor in front of the fireplace from
both radiant heat and sparks. See Figures 8.1-8.3.
HX3 or HX4
Hearth Ext
or equivalent
insulation
Tile, stone or other
non-combustible material
Protective
Metal Hearth
Strip
(see Table below)
WARNING
2 in. (51 mm)
required
Fire Risk
Floor constructed of wood or
other combustible material
•
Metal hearth strips MUST be installed.
Figure 8.1 Hearth Extension Construction
Sparks or embers may ignite flooring.
This fireplace has been tested and approved for use with a
hearth extension insulated to a minimum R value of 1.03.
To substitute materials for the factory-available hearth ex-
tensions, see Figure 8.3 and calculate insulation alterna-
tives as per Table 8.1 and the following formulas:
•
•
•
Thermal conductivity per inch thickness = k
k = (BTU)(inch) / (foot2)(hour)(°F)
Required thickness = Rk
•
•
•
Thermal resistance per inch thickness = r
r = (foot2)(hour)(°F) / (BTU)(inch)
Required thickness = R / rB.
¨
Table 8.1
Hearth Extension Insulation Alternatives-Total minimum R Value must equal 1.03
Minimum
k per inch
thick
r per inch
thick
thickness
required
Material
Hearth & Home HX3, HX4 (Micore 300™)
USG Micore 160™
0.49
0.39
1.92
5.0
2.06
2.54
0.52
0.20
0.20
0.08
2.18
1/2 in.
1/2 in.
USG Durock™ Cement Board
Cement Mortor
2 in.
5-1/8 in.
5-1/8 in.
12-1/4 in.
1/2 in.
Common Brick
5.0
Ceramic Tile
12.50
0.46
Armstrong™ Privacy Guard Plus
Marble
14.3-20.0
0.07-0.05 14-5/8 in. - 20-3/8 in.
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
27
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Finishing Material
•
Combustible Material
Material which is made of or surfaced with wood,
compressed paper, plant fibers, plastics, or any material
capable of igniting and burning, whether flame proofed or
not, plastered or not plastered.
•
Non-Combustible Material
Material which will not ignite and burn. Such materials are
those consisting entirely of steel, iron, brick, tile, concrete,
slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in a
Vertical Tube Furnace at 750° C, shall be considered
non-combustible materials.
1 in. (25 mm)
overlap
•
Non-Combustible Sealant Material
Metal strips 2 in. (51 mm) under the edges
of the fireplace and must extend beyond the
front and side openings by 2 in. (51 mm)
Sealants which will not ignite and burn: Rutland, Inc.
Fireplace Mortar #63, Rutland 72R, Nuflex 302, GE
RTV106, GE RTV116.
After completing the framing and applying the facing material
(drywall) over the framing, a bead of non-combustible seal-
ant must be used to close off any gaps at the top and sides
between the fireplace and facing to prevent cold air leaks.
Large gaps can be bridged with fiberglass rope gasket.
Figure 8.2 Positioning the Protective Metal Hearth Strips
WARNING
Only non-combustible materials may be used to cover the
metal fireplace front.
Fire Risk
•
Hearth extensions must be installed
exactly as specified.
High temperatures or hot embers may ignite
concealed combustibles.
WARNING
Fire Risk
•
•
Maintain clearances.
Use only non-combustible material below
standoffs, material such as cement board is
acceptable.
•
Framing or finishing material used on the front of, or
in front of, the appliance closer than the minimums
listed, must be constructed entirely of noncombustible
materials (i.e., steel studs, concrete board, etc.).
B
A
C
CAT. #
A
52
B
16
C
8
HX3
in
mm
1321
406
203
Figure 8.3 Hearth Extension Dimensions
28
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
C. Mantel
12 in. (305 mm)
max.
A combustible mantel may be positioned no lower than
12 in. (305 mm) above the top of the fireplace opening. The
combustible mantel may have a maximum depth of 12 in.
(305 mm). Combustible trim pieces that project no more
than 1-1/2 in.(38 mm) from the face of the fireplace can
be placed no closer than 6 in. (152 mm) from the top of the
fireplace opening. See Figure 8.4. Combustible trim must
not cover the metal surfaces of the fireplace. This mantel
clearance is in accordance with Section 7-3.3.3 of ANSI/
NFPA211.
1-1/2 in. (38 mm) max.
Header
Mantel
Standoff
12 in. (305 mm)
min.
Top of
Fireplace
Opening
6 in. (152 mm) min.
Figure 8.4 Mantel Specifications
WARNING
Fire Risk
12 in.
62 in.
Do NOT obstruct air inlets.
Finishing materials must not interfere with:
(305 mm)
(1575 mm)
from opening
of fireplace
72 in.
(1829 mm)
16 in.
(406 mm)
•
•
•
Air flow through inlets
Operation of doors
Access for service
16 in.
(406 mm)
56 in.
(1422 mm)
40-1/2 in.
(1029 mm)
26 in.
6 in.
(152 mm)
(660 mm)
to front of
fireplace
opening
HEARTH
EXTENSION
(shaded)
HEARTH
EXTENSION
(shaded)
D. Sidewalls/Surrounds
Adjacent combustible side walls must be located a minimum
of 12 in. (305 mm) from the fireplace opening. If you are us-
ing a decorative surround constructed of combustible ma-
terial, it must be located within the shaded area defined in
Figure 8.5. Short stub walls are also acceptable if they are
contained within the shaded area.
64 in.
(1626 mm)
64 in.
(1626 mm)
BAY-40
PIER-40
Figure 8.5 Sidewalls/Surrounds
WARNING
E. Glass Doors
This fireplace has been tested and listed with doors (re-
quired). See Section 12B Fireplace Components for avail-
able doors. Please refer to the manual packed with each set
of doors for installation instructions.
Fire Risk
Finish all edges and fronts to clearances and
specifications.
•
Metal fireplace front may be covered with
non-combustible material only.
•
•
•
Do NOT overlap combustible materials onto fireplace
front.
Install combustible materials up to specified clearances
on top front and side edges.
Seal joints between the finished wall and fireplace top
and sides using only a 300° F minimum sealant.
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
9
¨
WARNING
WARNING
HOT SURFACES!
Fire Risk
Glass and other surfaces are
hot during operation AND
cool down.
•
Do not operate fireplace before
reading and understanding operating
instructions.
Failure to operate fireplace properly may
cause fire.
Hot glass will cause burns.
•
•
•
•
Do not touch glass until it is cooled
NEVER allow children to touch glass
Keep children away
CAREFULLY SUPERVISE children in same room
as fireplace.
Alert children and adults to hazards of high
temperatures.
A. General Information
Fireplaces, as well as other woodburning appliances, have
been used safely for many years. It has been our experience
that most problems are caused by improper installation and
operation of the fireplace. Make certain that installation and
operation of the fireplace system is in accordance with these
instructions.
•
High temperatures may ignite clothing or other
flammable materials.
Keep clothing, furniture, draperies and other
•
It is extremely important that the fire be supervised when-
ever the fireplace is in use. It is also recommended that an
annual inspection be performed on the fireplace system to
determine if the flue system needs to be cleaned, or as in
the case of any appliance, if minor repairs are required to
maintain the system in top operating condition.
flammable materials away.
WARNING
Fire Risk
•
For use with solid wood fuel or decorative gas
appliance only.
•
Do not install unvented gas logs.
Damper Control
Up - Open
LIFT TO
OPEN
Down - Closed
Outside Air Control
Handle Out - Open
Handle In - Closed
BAY-40
PULL TO
OPEN
PIER-40
Figure 9.1 General Operating Parts
30
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Outside Air
E. Firescreen
A source of air (oxygen) is required in order for combustion A firescreen is always provided to control sparks. It must
to take place. Whatever air is consumed by the fire must be be closed whenever the fireplace is in use. Glass doors or
replaced through cracks around windows, under doors, etc. firescreens must not be used to hold burning material in-
Most newly constructed houses or existing homes fitted with side the fireplace. Only those glass doors specifically tested
tightly sealed doors and windows are relatively air tight. In and listed for use with the specific fireplace model should be
this case, an outside air source must be made available to used. Screens should be closed when the glass doors are
feed combustion air from outside the home.
closed.
An outside air control handle allows you control of the out-
side air inlet if your fireplace is equipped with this option.
Use of outside air for combustion is highly recommended to
conserve heated air within the structure and to provide make
up air to keep the fireplace venting properly.
WARNING
Fire Risk
•
•
Close firescreen when burning fireplace.
Do not use firescreen or glass doors to
hold burning material in fireplace.
This fireplace will operate correctly only if adequate ventila-
tion is provided to allow proper draft to the fireplace sys-
tem.
Firescreen controls sparks.
Glass may break or burning material may
roll out.
See Figure 9.1 for location and operation.
CAUTION
Outside air control handle is HOT. Adjust before lighting
F. Glass Doors
Most efficient fireplace operation using glass doors is with
the doors open. When the doors are open the screen must
be closed. Only Hearth & Home Technologies glass doors
may be used. See Figure 9.2 for proper glass door opera-
tion.
fire.
C. Clear Space Near the Fireplace
Combustible materials must not be stored on the hearth ex-
tension. Room furnishings such as drapes, curtains, chairs
or other combustibles must be at least 4 ft (1.22 m) from the
open front of the fireplace.
FULLY OPEN
CORRECT
PARTLY OPEN
INCORRECT
D. Flue Damper
The flue damper must be in full open position, and is oper-
ated by moving the handle up toward the top of the fireplace.
Before lighting the fire, verify this by looking up from the in-
side of the fireplace. Always operate this fireplace with the
damper fully open. Please note: Down drafts, obstructions,
damaged or poor (wet) fuels can cause smoke spillage.
FULLY CLOSED
CORRECT
PARTLY CLOSED
INCORRECT
See Figure 9.1 for location and operation.
WARNING
Asphyxiation Risk
Fire Risk
Figure 9.2 Proper Operating Positions of Bi-fold Doors
•
Open damper to operate fireplace.
Closed damper will over-fire fireplace and
prevent venting of combustion gases.
WARNING
Fire Risk
Smoke Risk
•
Doors must be fully opened or fully closed
when operating fireplace.
Partially opened doors may draw flame, smoke
or heat from fireplace.
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Seasoning
G. Grate
Seasoned firewood is nothing more than wood that is
The factory installed integral grate must be used to hold the
logs from falling out of an open fireplace and to allow air to
pass between the burning logs. It is important to keep the fire
off the hearth and to allow the ashes to collect beneath the
fire, thereby forming a layer of additional heat protection.
cut to size, split and air dried to a moisture content of
around 20%. The time it takes to season wood varies
from around nine months for soft woods to as long as
eighteen months for hardwoods. The key to seasoning
wood is to be sure it has been split, exposing the wet
interior and increasing the surface area of each piece. A
tree that was cut down a year ago and not split is likely
to have almost as high a moisture content now as it did
when it was cut.
WARNING
Fire Risk
•
Use only factory installed integral grate.
The following guideline will ensure properly seasoned
wood:
May cause overfire.
•
•
•
Stack the wood to allow air to circulate freely around
and through the woodpile.
Elevate the woodpile off the ground to allow air
circulation underneath.
The smaller the pieces, the faster the drying process.
Any piece over 6 in. (152 mm) in diameter should be
split.
Cover the top of the woodpile for protection from
rain and snow. Avoid covering the sides and ends
completely. Doing so may trap moisture from the
ground and impede air circulation.
H. Wood Fuel
Firewood
Your fireplace performance depends on the quality of the
firewood you use. All seasoned wood, regardless of spe-
cies, contains about 8,000 BTU’s per pound, and hard-
woods have a greater density than soft woods. A piece
of hardwood will contain about 60% more BTU’s than
an equal size piece of soft wood. Firewood is commonly
sold by the cord (128 cu. ft.). A cord of seasoned oak
(hardwood) would contain about 60% more potential en-
ergy than a cord of seasoned pine (soft wood).
•
The problems with burning wet, unseasoned wood are
twofold: First, you will receive less heat output from wet
wood because it requires energy in the form of heat to
evaporate the water trapped inside. This is wasted ener-
gy that should be used for heating your home. Secondly,
this moisture evaporates in the form of steam which has
a cooling effect in your fireplace and chimney system.
When combined with tar and other organic vapors from
burning wood it will form creosote which condenses in
the relatively cool fireplace and chimney.
Examples of soft wood trees are Douglas fir, pine, spruce,
and cedar, poplar, aspen and alder. Soft woods require
less time to dry, burn faster and are easier to ignite than
hardwoods.
Examples of hardwood trees are oak, maple, apple, and
birch. Hardwoods require more time to season, burn
slower and are usually harder to ignite than soft woods.
The best wood fuel is a combination of soft wood and
hardwood. Start the fire with soft wood; the fire will give
off quick heat to bring the fireplace up to operating tem-
perature, and then the hardwood can be added for slow,
even heat and longer burn time.
WARNING
Fire Risk
•
•
•
Do NOT burn wet or green wood.
Store wood in dry location.
Stack wood so both ends are exposed to
air.
Moisture
Regardless of which species of wood you burn, the single
most important factor that effects the way your fireplace
operates is the amount of moisture in the wood. The ma-
jority of the problems fireplace owners experience are
caused by trying to burn wet, unseasoned wood.
Wet, unseasoned wood can cause
accumulation of creosote.
Freshly cut wood can be as much water as it is wood,
having a moisture content of around 50%. Imagine a
wooden bucket that weighs about eight pounds. Fill it
with a gallon of water, put it in the fireplace and try to burn
it. This sounds ridiculous but that is exactly what you are
doing if you burn unseasoned wood.
WARNING
Fire Risk
Do NOT store wood:
•
Closer than required clearances to
combustibles to fireplace.
•
Within space required for loading or ash
removal.
32
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
I. Starting a Fire
CAUTION
Odors and vapors released during initial
operation.
Check the flue damper to be certain it is in the full open po-
sition. Place crumpled or twisted paper under the fireplace
grate. Loosely arrange kindling or small pieces of wood to
form a layer above the paper.
•
Curing of high temperature paint.
•
Open windows for air circulation.
The fires must be built on the fireplace grate, without danger
of the burning fuel falling out of the fireplace opening.
Odors may be irritating to sensitive individuals.
Light the paper and add small pieces of wood until a hot bed
of embers has been established.
After establishing the fire bed, and the small firewood is burn-
ing briskly, add a minimum of three average sized pieces of
split firewood, place the wood in such a manner to allow
combustion air and flames between them.
WARNING
Fire Risk
Keep combustible materials, gasoline and
other flammable vapors and liquids clear of
fireplace.
Note: When first lighting your fireplace, it may be neces-
sary to pre-warm the flue to establish a draft. This is done
by holding a rolled up piece of burning newspaper under
the flue damper for a few moments. This will help reduce
smoke spillage during start-up.
•
Do NOT store flammable materials close
to the fireplace.
Do NOT use gasoline, lantern fuel,
kerosene, charcoal lighter fluid or similar
liquids to start or “freshen up” a fire in this
fireplace.
•
Note: The first three or four fires should be of moderate
size to allow the oils and binders to be burned from the
fireplace and the refractory and paint to cure. You may
notice an industrial odor the first few fires. This is consid-
ered normal.
•
Keep all such liquids well away from the
fireplace while it is in use.
Combustible materials may ignite.
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
10
This fireplace will operate correctly only if adequate ventila- flue, or some condition is in effect to draw smoke from the
tion is provided to allow proper draft to the fireplace system. fireplace into the house. Understanding and differentiating
Hearth & Home Technologies assumes no responsibility for the conditions which can cause each of these kinds of spill-
the improper performance of the fireplace system caused age problems is essential to their solution.
by inadequate draft due to environmental conditions, down
drafts, tight sealing construction of the structure, or mechan-
ical exhausting devices which will create a negative air pres-
sure within the structure where the fireplace is located.
•
Flue Leakage
Check for improperly connected flue joints or a damaged
flue joint in the chimney system. Such leakage would
reduce draft (air would be drawn in through the leaks rather
than through the fireplace). The result might be difficult
start-up and smoky fires that might spill if other adverse
draft conditions accompany this problem.
Flue Blockage
A. Understanding Vent Problems
If smoke spillage occurs from a fireplace opening when the
door is open and the proper chimney height, flue size, and
configuration requirements for the installation have been
met, there is either a leakage in the flue, a blockage in the
•
The damper should be open.
Overhanging
tree?
Bird's nest
or leaves in
termination
cap?
Structural
changes in
chimney area?
Another appliance in
home also exhausting
air (furnace, fan,
dryer, etc.)?
can lights?
Unsealed
Overhead fan
operating?
Creosote buildup
in flue?
Air register from
furnace near
fireplace?
Damper closed?
Doors opening
and closing?
Window closed
for start-up?
Outside air
closed?
Figure 10.1 Factory-built Fireplaces: Troubleshooting
34
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Diagnostics and Problem Solving
I can’t get a good fire going. What am I doing wrong?
Diagnostic Questions
Possible Causes of Condition
Solutions
Is the damper open?
• No draft
Open damper.
Is there enough paper/starter? • Insufficient heat to ignite kindling
Use more paper/starter.
Use more dry kindling.
Is there enough kindling?
Is the kindling dry?
• Insufficient heat to ignite fuel
Is there enough or too much
wood? Is it too large? Is it dry
enough?
• Insufficient heat to establish draft
• Insufficient air passage
Use small split wood that is well seasoned (split, covered on top at
least 6 months, preferably a year).
• Insufficient surface area
• Ignition temperature high due to moisture
Are there adequate air spaces • Insufficient combustion air and exposed
Arrange kindling and wood for air movement.
between fuel pieces?
surface area
Is the chimney pre-warmed?
• Exposed, cold chimney down drafting
Use lighted rolled newspaper at throat or flue opening to start
upward movement.
Is there smoke in the house?
• Damper closed
Check damper; have chimney checked if it worked previously;
pre-warm chimney, shut off exhaust devices, open window slightly.
• Obstruction in chimney
• Down draft from chimney temperature or
from negative house pressure
Does the kindling, wood not
ignite?
• Condition, amount, arrangement of kindling Use more, drier, well-spaced kindling and fuel.
and fuel
Does the kindling ignite, but the • Amount of kindling
Use more kindling; use smaller, dry wood.
fuel doesn’t?
• Condition of fuel
Does the fuel ignite, but not
burn well?
• Condition of fuel
• Draft problem
Use well-seasoned wood and sufficient amount; turn exhaust fans
off; open window slightly. Perform Simplified House Pressure Test.
I don’t get enough/any heat from the fireplace. What can I do about it?
Diagnostic Questions
Possible Causes of Condition
Solutions
How much wood is used for
• Insufficient fuel
Make larger fires.
fire?
How well seasoned is the
wood?
• Condition of fuel
Burn seasoned wood: covered on top, split and stacked for 9
months to 2 years.
Do you have a blower (where
possible)?
• Yes: Turning blower on too early or setting
too high, cooling firebox
Yes: Wait until fire established and leave on lower speed.
No: Add blower if available.
No: Need for all heat boosts possible
How much heat output do you • Unrealistic expectations
expect?
Explanation of decorative nature of fireplace; suggestion of
approved fireplace insert.
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
35
Download from Www.Somanuals.com. All Manuals Search And Download.
The fireplace burns the wood too fast. What can I do?
Diagnostic Questions
Possible Causes of Condition
Solutions
Do you have glass doors?
• Need to slow air intake
Add glass doors.
What is the condition of the
wood?
• Extremely dry wood
Mix in less seasoned wood after fire established.
I smell smoke in the house during operation. What’s causing that?
Diagnostic Questions
Possible Causes of Condition
Solutions
Does the fire start and burn
No:
well?
• Damper not fully open
• Chimney obstruction
Open damper; check and clean chimney if needed; use adequate
kindling and fuel; open glass doors or open window, check for
need for balanced air make-up.
• Not enough kindling and/or fuel to establish
draft
• Inadequate combustion air
Yes:
• Fire too close to front
• Competition with exhaust devices
Build fire farther back. Do not use exhaust fans during startup
and/or check for need for balanced air make-up system.
I smell smoke in the house after we’ve had a fire in the fireplace. What is the cause/what can we do?
Diagnostic Questions
Possible Causes of Condition
Solutions
Is the damper closed?
• No: Down draft or negative pressure
Close the damper at end of burn.
• Yes: Negative pressure from exhaust fans
and/or house stack effect.
Check for need for glass doors. Check for need for balanced air
make-up system or raising chimney.
Is the chimney clean?
• No: Creosote odor
Have chimney cleaned.
• Yes: Damper closed too early
Wait until fire completely out before closing damper.
36
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance and Servicing the Fireplace
11
A. Disposal of Ashes
B. Chimney Inspection/Cleaning
Ashes should be placed in a metal container with a tight-fit- Inspect the chimney internally for obstructions and construc-
ting lid. The closed container of ashes should be placed on tion damage. Flue pipe joints and seams must be continu-
a noncombustible floor or on the ground, well away from all ous and mechanically tight.
combustible materials, pending final disposal. If the ashes
The chimney should be inspected once every two months
are disposed of by burial in soil or otherwise locally dis-
during the heating season.
persed, they should be retained in the closed container until
If creosote has accumulated, it should be removed to reduce
the risk of a chimney fire.
all embers have thoroughly cooled.
Refer to Figure 11.1 to remove/reinstall termination caps.
WARNING
C. Firebox Refractory
Fire Risk
Check firebox refractory for excessive cracks or gaps. If
cracks exceed 1/4 in. (6 mm) in width the refractory should
be replaced. See Section 12 for replacement information.
Disposal of ashes
•
•
•
Ashes should be placed in metal container with tight
fitting lid.
Do not place metal container on combustible
surface.
Ashes should be retained in closed container until all
embers have thoroughly cooled.
WARNING
Fire Risk
•
Inspect fireplace refractory annually.
Crumbling, deteriorated refractory can allow
overheating of surrounding materials.
WARNING
Fire Risk
Note: As you use the fireplace, expansion and contraction
will cause minor cracking of the refractory. This is normal,
unavoidable, and will not affect the performance of the
fireplace. If the cracks become large enough that the metal
behind the refractory is exposed or large pieces fall out, the
panels should be replaced.
Prevent creosote buildup
•
Inspect chimney once every two months during heating
season.
Remove creosote to reduce risk of chimney fire.
Ignited creosote is extremely HOT.
•
•
Remove 8 screws
(9 for King), lift top
cover.
Remove screws,
lift top cover.
1. Remove the 4 screws.
2. Remove the screen.
3. Remove the baffle.
Remove 4 screws
and lift top pan off.
Remove 2 screws from
the front and back and
lift the top off.
Cap Top
(Be sure
holes in
cap top
Top Cover
and cap
base are
aligned.)
Cap
Cap
Cap
Chimney
Cap Base
Slip
Section
Chase
TCT375
Terra Cotta
Termination Cap
ST375
Square
Termination Cap
TS345/TS345P
Square
Termination Caps
TR344/TR342
Round
Termination Cap
European Copper Series
Termination Cap
(CT-King shown)
Figure 11.1 Chimney & Termination Cap Cleaning
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
37
Download from Www.Somanuals.com. All Manuals Search And Download.
CAUTION
WARNING
Handle glass assembly with care.
Asphyxiation Risk
When cleaning glass door:
Fire Risk
•
Avoid striking, scratching or slamming
glass.
Annual inspection by qualified technician
recommended.
•
•
Do NOT use abrasive cleaners.
Use a hard water deposit glass cleaner on
white film.
Check:
•
•
•
Condition of doors, surrounds and fronts
Condition of glass and glass assembly
Obstructions of combustion and ventilation
air
•
Do NOT clean glass when it is hot.
•
•
•
Gas connections and fittings (if present)
Obstructions of termination cap
Refractory panels
WARNING
Fire Risk
Clean:
•
•
•
Do not use chimney cleaners or flame
colorants in your fireplace.
Glass
Air passageways, grilles
Will corrode chimney.
D. Maintenance Task List
Inspect
Maintenance Tasks
Screens
1. Assess condition of screen and replace as necessary. Screens are required.
2. Verify maintenance of proper clearance to combustible household objects.
1. Inspect glass panels for cracks. Replace if this condition is present.
2. Confirm there is no damage to glass or glass frame. Replace as necessary.
3. Clean glass using a non-abrasive cleaner such as Brasso©.
Glass Doors
Circulation Compartment 1. Remove any foreign objects.
2. Verify unobstructed air circulation.
Firebox
1. Inspect condition of refractory. Replace if crumbly, deteriorated, or if cracks exceed 1/4 in. (6 mm).
Chimney
1. Inspect for blockage or obstruction such as bird nests, leaves, etc.
2. Confirm that termination cap remains clear and unobstructed by plants, etc.
3. Verify that termination cap clearance to subsequent construction (building additions) has been maintained.
4. Inspect for corrosion or separation.
5. Verify weather stripping, sealing and flashing remain intact.
6. Inspect for creosote and remove as needed. (See Sections 10 and 11)
Grate
1. If grate burns out, it should be replaced only with the grate specified on the rating plate and in the replacement
parts list for this fireplace.
E. Chimney Fire
In the event of a chimney fire:
•
•
Replace components of the chimney and fireplace as
specified by the professionals.
Ensure all joints are properly engaged and the chimney
is properly secured.
•
Have the chimney and adjacent structure inspected by
qualified professionals. Hearth & Home Technologies
recommends that NFI or CSIA certified professionals, or
technicians under the direction of certified professionals,
conduct a minimum of an NFPA 211 Level 2 inspection
of the chimney.
A chimney fire can permanently damage your chimney sys-
tem. Failure to replace damaged components and make
proper repairs creates risk of fire.
38
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
Reference Materials
12
A. Fireplace Dimensions
20"
471/8"
42"
42"
½"
22½"
5¾"
24"
22½"
5¾"
11"
12"
36"
40"
36"
40"
TOP VIEW - BOTH MODELS
175/8"
FRONT VIEW - BAY-40
FRONT VIEW - PIER-40
5¼"
12"
GAS
KNOCKOUT
44"
471/8"
8¾"
3"
40"
8¼"
12"
GAS
KNOCKOUT
9½"
53/8"
24"
ELECTRICAL
KNOCKOUT
FOR ST36C
7"
END VIEW - BAY-40
BOTTOM VIEW
BAY-40
END VIEW - PIER-40
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
39
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Fireplace Components
Catalog #
Description
PIER-40
BAY-40
Peninsula Fireplace
Island Fireplace
DM1036
DM1036B
DM1036S
DM1000
DM1000B
DM1000S
HX3
Glass Doors - bi-fold, Clear-View - Black
Glass Doors - bi-fold, Clear-View - Polished Brass
Glass Doors - bi-fold, Clear-View - Stainless Steel
Fixed End Glass Panel, Clear-View - Black
Fixed End Glass Panel, Clear-View - Polished Brass
Fixed End Glass Panel, Clear-View - Stainless Steel
Hearth Extension
GR3
Integral Grate (included with Fireplace)
Trim Kit, Polished Brass Fireplace Perimeter (2 required)
TK53B1
Bi-fold Glass Doors
(SIDE OF FIREPLACE)
GR3
Integral Grate
AK17/AK18
Outside Air Kit
52 in.
(1321 mm)
16 in.
(406 mm)
HX3 Hearth Extension
1/2 in.
TK53B
(13 mm)
Trim Kit
40
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
C. Chimney Components
The following pictures show only those chimney components which may be safely used with this fireplace.
ID4 Insulated Duct
Catalog # Description
CAK5A
ID4
Chimney Air Kit
4 in. (102 mm) i
Insulated Duct/Outside Air
42 in.
(1067 mm)
UD4
Uninsulated Duct/Outside Air
SL1106
SL1112
SL1118
SL1136
SL1148
SL11
Chimney Section - 6 in. (152 mm) long
Chimney Section - 12 in. (305 mm) long
Chimney Section - 18 in. (457 mm) long
Chimney Section - 36 in. (914 mm) long
Chimney Section - 48 in. (1219 mm) long
Chimney Stabilizer
UD4 Uninsulated Duct
4 in. (102 mm) i
42 in.
SL1130
FS538
FS540
AS10
Chimney Offset/Return - 30 deg
Ceiling Firestop - Straight
Ceiling Firestop - 30 deg
A
SL1100 Straight Attic Insulation Shield, 24 in. (610 mm)
Chimney Joint Band
JB577
CB576
RF570
RF571
TR11
13 in.
(330 mm)
11 in.
(279 mm)
Chimney Bracket
Roof Flashing - Flat to 6/12 Pitch
Roof Flashing - 6/12 to 12/12 Pitch
Round Termination Cap
B
Chimney Sections
TR11T
TCT1175
ST1175
CT56
Round Telescoping Termination Cap
Terra Cotta Termination Cap
A
B
Square Termination Cap
Catalog #
in
6
mm
152
305
457
914
1219
in
mm
121
273
425
883
1187
Chase Top
SL1106
SL1112
SL1118
SL1136
SL1148
4-3/4
LDS33
LDS46
LDS-BV
Decorative Shroud - 3 ft x 3 ft (.91 m x .91 m)
Decorative Shroud - 4 ft x 6 ft (1.22 m x 1.83 m)
Decorative Shroud - 26 in. x 26 in. (660 mm x 660 mm)
12
18
36
48
10-3/4
16-3/4
34-3/4
46-3/4
Field Constructed Shrouds (See “Woodburning
Termination Cap”)
CT11-King
European Copper Termination Cap - King Style
A = Actual Length
B = Effective Length (length of
chimney part after it has
CT11-Queen European Copper Termination Cap - Queen Style
CT11-Bishop European Copper Termination Cap - Bishop Style
CT11-Knight European Copper Termination Cap - Knight Style
been snapped to another)
CT11-Pawn
European Copper Termination Cap - Pawn Style
14 in.
(356 mm)
14 in.
(356 mm)
Inside
Diameter
11 in.
(279 mm)
20-3/4 in.
(527 mm)
5-1/4 in.
(133 mm)
4 in. (102 mm)
13 in.
(330 mm)
Outside Diameter
13 in.
(330 mm)
CAK5A Chimney Air Kit
SL11 Chimney Stabilizer
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
41
Download from Www.Somanuals.com. All Manuals Search And Download.
A
Inside
Diameter
11 in.
(279 mm)
B
14-1/2 in.
(368 mm)
21 in.
(533 mm)
Outside
Diameter
13 in.
Ceiling Firestop
(330 mm)
Catalog #
FS538
A
B
SL1130 Offset/Return
0-deg.
30-deg.
17 in.
26 in.
432 mm
660 mm
FS540
15-1/4 in.
(387 mm)
Assembled
Diameter: 17 in./432 mm
Height: 24 in./610 mm
25-1/4 in.
(641 mm)
29 in.
(737 mm)
AS10 Straight Attic Insulation Shield
RF570 Roof Flashing
15-1/4in.
(387 mm)
10-1/2 in.
(267 mm)
2 in. (51 mm)
28 in.
(711 mm)
39-7/8 in.
(1013 mm)
JB577 Chimney Joint Band
RF571 Roof Flashing
10-1/2 in.
(267 mm)
CB576 Chimney Joint Band
42
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
72 in.
36 in.
(1829 mm)
(914 mm)
13-3/8 in.
(340 mm)
15-3/4 in.
(400 mm)
2 in.
(51 mm)
TR11 Round Termination Cap
CT56 Chase Top
32-3/8 in.
(822 mm)
C
D
34-3/8 in.
(873 mm)
B
A
Decorative Shroud
LDS33/LDS46
TR11T Round Telescoping Termination Cap
A
B
C
D
Catalog # in.
mm
914
in.
36
72
mm
in.
mm
in.
11
11
mm
279
279
LDS33
LDS46
36
48
914 8-1/2 216
1829 8-1/2 216
14-3/4 in.
(375 mm)
1219
23 in.
23 in.
E
D
(584 mm)
(584 mm)
ST1175 Square Termination Cap
C
B
A
20 in.
(508 mm)
LDS-BV Decorative Shroud
Catalog #
A
26
B
C
D
22
E
17 in.
(432 mm)
in.
mm
12-1/2 15-1/2
318 394
23
9-3/8 in.
(238 mm)
LDS-BV
660
533
584
9-1/4 in.
(235 mm)
TCT1175 Terra Cotta Cap
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
43
Download from Www.Somanuals.com. All Manuals Search And Download.
European Copper Caps
21 in.
(533 mm)
18-1/4 in.
(464 mm)
20-3/4 in.
(527 mm)
47-3/4 in.
(1213 mm)
41-1/8 in.
(1045 mm)
38-5/8 in.
(981 mm)
20 in.
(508 mm)
20 in.
(508 mm)
24 in.
(610 mm)
CT3-King
CT3-Queen
CT3-Bishop
16 in.
(406 mm)
21 in.
(533 mm)
38-3/8 in.
(975 mm)
25-3/4 in.
(654 mm)
16 in.
(406 mm)
20-5/8 in.
(524 mm)
CT3-Knight
CT3-Pawn
44
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
Woodburning Termination Cap
TR342 / 344 TV
TR342 / 344
TR442 / 444
TS345 / 445
(Top Vent)
TR11 / 11T TV
Shroud
TR11 / 11T
TR442 / 444 TV
(with TR-TVK installed)
(with TR-TVK installed)
OPEN TOP with solid sides and 3 in. opening at the bottom.
32 X 32 with
Radiation
Shield
Minimum Base Dimensions
(Inches)
28 X 28 with
Radiation Shield
23 X 23
20 x 20
26 X 26
23 X 23
26 x 26
23 x 23
Minimum Top Dimensions
(Inches)
25 X 25
29 X 29
MAILBOX STYLE with open ends and 3 inch opening at the bottom of the sides.
34 X 34 with
Radiation
Shield
28 X 30 with
Radiation Shield or
34 X 34
Minimum Base Dimensions
(Inches)
26.5 X 28 with
Radiation Shield
N/A
N/A
28 X 30
27 1/2
Minimum Height (Inches)
28 1/4
28 1/4
27 1/2
ROOFED STYLE with 12 X 22 (264 sq. in.) opening on each side and 3 in. space between the
radiation shield and chase top.
34 X 34 with
Radiation
Shield
Minimum Base Dimensions
(Inches)
27 X 27 with
Radiation Shield Radiation Shield
27 X 27 with
34 X 34 with
Radiation Shield
N/A
N/A
Minimum Height (Inches)
23
23
23
23
Minimum Height is measured from the bottom of the termination cap:
Minimum height is established with the bottom of the termination cap 7 in. above the chase top. Minimum height must increase
accordingly for any height above 7 in.
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
45
Download from Www.Somanuals.com. All Manuals Search And Download.
D. Service Parts
Service Parts
BAY-40
Beginning Manufacturing Date: 2/4/04
Ending Manufacturing Date: Active
Service Parts Diagram
Multi-Sided Woodburning Fireplace
1
2
3
10
7
8
14
5
13
4
6
11
12
9
46
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Parts
BAY-40
Beginning Manufacturing Date: N/A
Ending Manufacturing Date: 08/01/01
Service Parts List
Multi-Sided Woodburning Fireplace
Qty.
Part Number
req.
#
Description of Part
1
2
3
4
5
6
7
8
9
Top Standoff
11864i
22072B
34515
4
1
Starter Section Assembly
Damper Assembly
Front Door Support
Side Door Support
Grate
1
4012-035
23954
1
2
GR3
1
End Retainer Assembly
13929A
13294B
27856
2
Grate Retainer (for End Retainer Assembly)
Back Refractory
4
1
10 Side Refractory
11 Hearth Refractory
27857
2
13213A
13214A
13827A
13828A
12692
1
12 Front Ashlip
1
13 Left Side Ashlip
14 Right Side Ashlip
Nailing Flange
1
1
4
Firescreen Rod
11866B
12267
2
Firescreen Assembly
Screen Handle
2
4021-149
13229
1ea.
1
Damper Control
Damper Weight
19785A
4012-002
15425
1
Door Track (for bottom)
Door Track (for top)
Grate Retainer
1
1
13834B
13831C
13896B
13268A
AK17
2
Side Refractory Bracket
Refractory Bracket
Outside Air Door Assembly
Air Kit
2
2
1
1
Fastener Pack
12010B
19081A
19954A
31168
1
Plate Assembly
1
Long Cable Tie
2
Air Kit Installation Instructions
Outside Air Shield
Strip Protector
1
33271
1
18320
4
BAY-40 Installation Instructions and Owner’s Manual
34977
1
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Parts
PIER-40
Beginning Manufacturing Date: N/A
Ending Manufacturing Date: Active
Service Parts Diagram
Multi-Sided Woodburning Fireplace
3
2
1
9
10
11
13
7
6
12
8
5
4
14
48
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Parts
PIER-40
Beginning Manufacturing Date: N/A
Ending Manufacturing Date: Active
Service Parts List
Multi-Sided Woodburning Fireplace
#
1
2
Description of Part
Ashlip
PIER-40
13214A
13319
Qty.
2
1
2
1
1
1
4
1
1
1
1
1
1
1
1
4
4
4
4
1
4
1
1
2
2
4
1
1
1
1
2
2
4
2
2
Back Refractory
Corner Refractory
Damper Blade Assembly
Damper Control
Damper Rod
13320A
13227
13229
13230A
12757
3
4
5
6
6
7
7
8
8
9
9
Door Track Support
End Ashlip
13215A
23954A
13234B
23950A
13254F
23911A
13233C
23949A
11855A
12267
End Door Support
End Lower Front Face (overlay only) - pre 14/95
End Lower Front Face (overlay only) - post 15/95
End Top Front Face (overlay only) - pre 14/95
End Top Front Face (overlay only) - post 15/95
End Upper Front Face (overlay only) - pre 14/95
End Upper Front Face (overlay only) - post 15/95
Firescreen Assembly - pre 22/97
Firescreen Assembly - post 23/97
Heat & Glo Logo Screen Handle
4021-149
11866B
GR3
Firescreen Rod
10 Grate
Hairpin Clips
101025
13321B
17920
Hearth Refractory
Installation Instructions
11
11
Lower Front Face (overlay only) - pre 14/95
Lower Front Face (overlay only) - post 15/95
Nailing Flange
12847B
23942
12692
12 Outside Air Kit
Refractory Retainer
13330
11847C
13238C
22072B
13263G
23953
13 Side Smoke Shield
14 Starter Section
15 Top Front Face (overlay only) - pre 14/95
15 Top Front Face (overlay only) - post 15/95
16 Top Standoff
11864i
17 Upper Front Face (overlay only) - pre 14/95
17 Upper Front Face (overlay only) - post 15/95
13232C
22937B
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
49
Download from Www.Somanuals.com. All Manuals Search And Download.
This page intentionally left blank.
50
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
Download from Www.Somanuals.com. All Manuals Search And Download.
E. Limited Warranty
WARRANTY
FOR HEAT & GLO FIREPLACES
The limited warranty will not become effective until you have mailed the completed warranty card to:
Hearth & Home Technologies Inc.
20802 Kensington Blvd., Lakeville, MN 55044.
This card must be mailed within 60 days of the fireplace installation.
Subject to the conditions set forth herein, HEARTH & HOME TECHNOLOGIES INC. (HHT) extends the following
limited warranty with respect to your Heat & Glo fireplace, excluding accessories, chimney components and glass
doors.
If HHT is satisfied that any part or portion of the fireplace covered by this warranty is defective in material or work-
manship under normal use and service as described in the operating instructions, HHT will take the following
actions:
1. Within the first five (5) years from the date of installation, HHT shall, at its option, replace or repair any such
defect in material or workmanship, at HHT’s expense. HHT SHALL NOT BE RESPONSIBLE FOR ANY
OTHER LABOR COSTS, OR EXPENSES, INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL
DAMAGES.
2. During the sixth (6th) through the (10th) years after the date of installation, HHT shall supply replacement
parts or parts at no charge, but SHALL NOT BE RESPONSIBLE FOR ANY LABOR, TRANSPORTATION,
OR OTHER INDIRECT DAMAGES.
3. During the eleventh (11th) through the fifteenth (15th) years after date of installation, HHT will send to you,
FOB its factory, replacement parts (if available) at the current minimum wholesale price, but HHT SHALL
NOT BE RESPONSIBLE FOR ANY LABOR, TRANSPORTATION OR OTHER INDIRECT DAMAGES.
4. During the first six (6) months after installation, HHT shall, at its option, replace or repair the glass doors
and any electrical components, if operation is faulty. (This does not include glass panels broken during
shipment, misuse or careless handling.) After the first six (6) months, HHT will sell to you, FOB its factory,
replacement parts at the current list price, but HHT SHALL NOT BE RESPONSIBLE FOR ANY LABOR,
TRANSPORTATION OR OTHER INDIRECT DAMAGES. IF GLASS DOORS OTHER THAN FACTORY
DOORS ARE USED ALL WARRANTY AND LIABILITY ON THE FIREPLACE IS VOIDED.
HHT may discharge its entire warranty liability by refunding the price of the product.
Products made by other manufacturers, sold with the fireplace or thereafter are not covered by this limited warranty.
This limited warranty will be void if the fireplace is not installed according to the installation instructions. The limited
warranty also is void if the fireplace is not operated, at all times, according to the operating instructions furnished.
The limited warranty will also be void if the fireplace is removed from the place originally installed.
EXCEPT TO THE EXTENT PROVIDED BY LAW, NO IMPLIED WARRANTIES OF MERCHANTABILITY OR
FITNESS FOR A PARTICULAR PURPOSE, AND NO IMPLIED WARRANTIES SHALL APPLY TO THE FIRE-
PLACE AFTER THE ABOVE LIMITED WARRANTY HAS EXPIRED.
In states that do not allow limitations on how long implied warranty lasts, or do not allow exclusion of indirect dam-
ages, those limitations or exclusions may not apply to you. You may also have additional rights not covered in this
limited warranty.
HHT reserves the right to make changes at anytime, without notice, in design, material, specifications and prices
and the right to discontinue styles and products.
Feb 2006
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
51
Download from Www.Somanuals.com. All Manuals Search And Download.
¨
F. Contact Information
Please contact your Heat & Glo dealer with any questions or concerns.
– NOTES –
CAUTION
DO NOT DISCARD THIS MANUAL
•
Read, understand
and follow these
instructions for safe
installation and
operation.
•
Leave this manual with
party responsible for
use and operation.
•
Important operating
and maintenance
instructions included.
This product may be covered by one or more of the following patents: (United States) 4593510, 4686807, 4766876,
4793322, 4811534, 5000162, 5016609, 5076254, 5113843, 5191877, 5218953, 5263471, 5328356, 5341794, 5347983,
5429495, 5452708, 5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485, 5931661, 5941237,
5947112, 5996575, 6006743, 6019099, 6048195, 6053165, 6145502, 6170481, 6237588, 6296474, 6374822, 6413079,
6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2, 6729551, 6736133, 6748940,
6748942, 6769426, 6774802, 6796302, 6840261, 6848441, 6863064, 6866205, 6869278, 6875012, 6880275, 6908039,
6919884, D320652, D445174, D462436; (Canada) 1297749, 2195264, 2225408, 2313972; (Australia) 780250, 780403,
1418504 or other U.S. and foreign patents pending.
52
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07