ENGINEERING
DESIGN GUIDE
HTV/HTD/HTH Series
Two-Stage
Geothermal Heat Pumps
2 to 6 Tons
Download from Www.Somanuals.com. All Manuals Search And Download.
Heat Controller, Inc.
HTV/HTD/HTH SERIES
Engineering Design Guide
Two Stage Geothermal Heat Pump Systems
Features of the Two Stage HT Series
The HT Series Geothermal Heat Pumps are some of the most efficient and innovative geothermal units on the market today.
Packed with features, they offer the best value to the homeowner who is interested in quiet comfort and low operating costs
as a result of extraordinary efficiencies.
Technically, the HT Series are state-of-the-art with digital electronic controls, multi-stage scroll compressors, computer
controlled fan motors, zero ozone depleting refrigerant, and much more.
Design Features
Service Advantages
• Five capacities to meet all application requirements—two,
three, four and six ton models.
• Three removable access panels for the compressor compartment
and one or two (depends on model) for the air handler compart-
ment offer quick access to all internal components even with
ductwork in place, making the unit service-friendly.
• Efficient operation from 20°F to 120°F entering water tempera-
tures. Flow rates may be as low as 1.6 gpm/ton.
• Built with bi-directional thermal expansion valve.
• Top supply air discharge accommodates upflow applications.
• Brass, swivel water connections make it easy to connect loop
and hot water piping.
• Select left or right hand return air positions for all models;
cabinets include a deluxe filter rack/duct collar.
• Insulated divider and separate air handling/compressor access
panels allow service testing without air bypass.
• Variable speed ECM blower motor adjusts to multiple duct
system applications and provides soft start for added comfort
and quiet operation.
• Design allows in-place service in tight installation spaces.
• Narrow cabinet design can be easily moved through doorways.
• CXM control features LED status light with memory feature for
easy diagnostics.
• Internally trapped condensate piping (on all vertical units)
allows easy, compact installation.
• Control box and fan motors have quick-attach wiring connections
for fast removal/reconnection.
• Internal electric heat unit (optional) is designed for easy field
installation.
• Biflow liquid line filter drier is factory-installed.
• Electric box is positioned for easy field wiring from two sides.
• Loop pump power block is built with circuit breaker.
• 75 VA control transformer comes with circuit breaker.
• Internal drop-out blower assemblymakes servicing simple.
• Refrigerant circuit includes high and low pressure service ports.
• Coaxial low temperature protection can be selected in the field
for well or closed loop installations.
• E-coated refrigerant-to-air coil helps protect the coil from
corrosion and extends life expectancy.
• Air coil low temp. protection utilizes high accuracy thermistors.
• Coaxial heat exchanger, refrigerant suction lines, hot water
generator coil, and all water pipes are fully insulated to reduce
condensation in low temperature conditions.
Factory Quality
• All units are built using our state-of-the-art manufacturing system
that is designed to assure quality of the highest standards. This
system:
• Isolation mounted compressors and low RPM blowers are used
to reduce noise; compressor compartment and interior cabinet
are insulated with 1/2" coated glass fiber insulation.
-Verifies that the correct components are being assembled;
-Automatically performs special leak tests on all joints;
-Conducts pressure tests;
• Double isolated compressor delivers extra quiet operation.
• Safety features include: high pressure and loss of charge pro-
tection for the compressor; condensate overflow protection; low
temperature protection sensors to safeguard the coaxial heat
exchanger and air coil; hot water high-limit hot water genera-
tor pump shutdown; fault lockout that enables emergency heat
and prevents compressor operation until thermostat or circuit
breaker has been reset.
-Performs a highly detailed run test;
-Automatically prevents a "failed" unit from being packaged for
shipment;
-Creates a computer database of run tests for future service
analysis and diagnostics;
-Includes painting heavy gauge steel cabinets with durable epoxy
for a long-lasting finish;
Operating Efficiencies
• AHRI/ASHRAE/ISO 13256-1 ratings for heating COPs and
cooling EERs are industry leaders.
-Performs all refrigerant brazing in a nitrogen-rich environment;
• Hot water generator (HWG) with internal pump generates hot
water at dramatic savings while improving system performance.
-Evacuates units to a deep vacuum of less than 50 microns
prior to refrigerant charging
• Efficient scroll compressors provide quiet, reliable operation.
-Halogen leak tests all joints to ensure a leak rate of less
than 1/4 ounce per year.
• Oversized coaxial tube water-to-refrigerant heat exchanger
delivers high efficiency and extra heating capacity; convoluted
water tube functions efficiently at low flow rates and provides
resistance to freeze damage.
Options & Accessories
• Optional internal auxiliary electric heat.
• Electronic auto-changeover thermostats with indicator LEDs.
• Closed loop flow controller and hose kits.
See Geo Accessories brochure for complete list of accessories.
• Oversized rifled copper tube/lanced aluminum fin air-to-refriger-
ant heat exchanger offers high efficiencies at low air velocity.
• Large, low RPM blower is both quiet and efficient, and provides
high static capability.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
Engineering Design Guide
HTV/HTD/HTH SERIES
Heat Controller, Inc.
Two Stage Geothermal Heat Pump Systems
What’s New
,{£äꢀÊ,ivÀ}iÀ>Ì
J;CF;H7JKH;ꢁB;L;BIꢁ7D:ꢁBEM;HꢁH;B7J?L;ꢁ>KC?:?JOꢊꢁ.>?Iꢁ;B?C?D7J;Iꢁ
KD;L;DꢁF;7AIꢁ7D:ꢁL7BB;OIꢁ7D:ꢁ7BBEMIꢁ<EHꢁIJ;7:Oꢁ9EEB?D=ꢁ9EC<EHJꢊꢁ
#EC;EMD;HIꢁDEMꢁ>7L;ꢁ7ꢁ8;JJ;HꢁCEH;ꢁ;<Xꢁ9?;DJꢁM7OꢁJEꢁFEM;Hꢁ
J>;?Hꢁ>;7J?D=ꢁ7D:ꢁ9EEB?D=ꢁIOIJ;CꢁH7?I?D=ꢁJ>;?HꢁB;L;BꢁE<ꢁ9EC<EHJꢁ
M>?B;ꢁBEM;H?D=ꢁ;D;H=Oꢁ8?BBIꢊꢁ-EꢁM>;DꢁOEKHꢁ9KIJEC;HIꢁD;;:ꢁ7ꢁD;Mꢁ
>;7J?D=ꢁ7D:ꢁ9EEB?D=ꢁIOIJ;CꢁC7A;ꢁIKH;ꢁ?Jꢁ>7IꢁJ>;ꢁ8;IJꢁJ;9>DEBE=Oꢁ
?DI?:;ꢁSꢁJ>;ꢁꢀEF;B7D:ꢁ-9HEBBꢁ/BJH7.;9>Wꢁ9ECFH;IIEHꢊ
R-410A is a non-chlorine-based refrigerant with
zero ozone depletion and low global warming
potential
,{£äÊVꢁ>À>VÌiÀÃÌVÃÊ>Ài\
UÊÊ i>ÀÊ>âiÌÀ«VÊÝÌÕÀiÊvÊxä¯Ê,ÎÓÊ>`Ê
Ê
xä¯Ê,£Óx°
UÊ6ÀÌÕ>ÞÊÊ}`i°
UÊxäÈä¯Êꢁ}ꢁiÀÊ«iÀ>Ì}Ê«ÀiÃÃÕÀiÃÊÌꢁ>Ê,ÓÓ°
UÊÊꢀÌꢁÕ}ꢁÊ>ÊL>ÀÞÊLi`ÊÌꢁiÊÌÜÊV«iÌÃÊꢁ>ÛiÊÊÊ
Ê
Ê
Ê
-7L;ꢁM?J>ꢁIKF;H?EHꢁ;<Xꢁ9?;D9Oꢊꢁ)L;HꢁꢋꢆꢌꢁE<ꢁIKCC;HꢁKJ?B?JOꢁ8?BBIꢁ97Dꢁ
9EC;ꢁ<HECꢁJ>;ꢁ7?Hꢁ9ED:?J?ED;Hꢁ9ECFH;IIEHꢁEF;H7J?EDꢊꢁꢃꢁIOIJ;Cꢁ
M?J>ꢁJ>;ꢁꢀEF;B7D:ꢁ-9HEBBꢁ/BJH7.;9>Wꢁ9ECFH;IIEHꢁ:;B?L;HIꢁ>?=>;Hꢁ
;<Xꢁ9?;D9OꢁJ>7Dꢁ7DOꢁEJ>;HꢁI?D=B;ꢁ9ECFH;IIEHꢁIOIJ;Cꢊꢁ$Dꢁ<79JꢁIOIJ;CIꢁ
M?J>ꢁ/BJH7.;9>WꢁFHEL?:;ꢁKFꢁJEꢁꢇꢆꢌꢁ=H;7J;Hꢁ;D;H=Oꢁ;<Xꢁ9?;D9Oꢁ7Iꢁ
Ê
Ê
ÌꢁiÊÃ>iÊi>ÊÀ>Ìi°ÊꢀÃÊ>ÊÀiÃÕÌÊÀivÀ}iÀ>ÌÊV>ÊÊ
Ê
LiÊ>``i`]ÊvÊiViÃÃ>ÀÞ]ÊÜÌꢁÕÌÊÀiVÛiÀ}ÊÌꢁiÊ
Vꢁ>À}i°
9ECF7H;:ꢁJEꢁ- ,ꢁIOIJ;CIꢁSꢁM>?9>ꢁ97DꢁI7L;ꢁ>EC;EMD;HIꢁ
£Î
>KD:H;:IꢁE<ꢁ:EBB7HIꢁ7ꢁO;7Hꢁ?Dꢁ;D;H=Oꢁ9EIJIꢊ
.7A;ꢁ?Jꢁ;7IOꢁM?J>ꢁGK?;J;Hꢁ9EDJHEBꢊꢁꢀEF;B7D:ꢁ-9HEBBꢁ/BJH7.;9>Wꢁ?Iꢁ
H;C7HA78BOꢁGK?;Jꢁ7Jꢁ8EJ>ꢁ<KBBꢈꢁ7D:ꢁF7HJꢈBE7:ꢁ97F79?JOꢊꢁ$Jꢁ?IꢁKFꢁ
I
JEꢁ<EKHꢁJ?C;IꢁGK?;J;HꢁJ>7Dꢁ7ꢁH;9?FHE97J?D=ꢁ9ECFH;IIEHꢊꢁ#EC;EMD;HIꢁ
97Dꢁ;D@EOꢁ?JIꢁIKF;H?EHꢁ;<Xꢁ9?;D9Oꢁ7D:ꢁ9EC<EHJꢁM?J>EKJꢁ>7L?D=ꢁJEꢁ>;7Hꢁ
J>;ꢁEF;H7J?EDꢊ
&;7HDꢁJ>;ꢁ8;7KJOꢁ
E<ꢁJ>;ꢁ:;I?=Dꢊꢁ1?J>ꢁ
ꢀEF;B7D:ꢁ-9HEBBꢁ
/BJH7.;9>WꢁJMEꢁ
?DJ;HD7Bꢁ8OF7IIꢁFEHJIꢁ
;D78B;ꢁJ>;ꢁIOIJ;CꢁJEꢁ
HKDꢁ7JꢁꢇꢉꢌꢁF7HJꢈBE7:ꢁ
97F79?JOꢁ<EHꢁ8;JJ;Hꢁ
;<Xꢁ9?;D9Oꢁ7D:ꢁ>KC?:?JOꢁ
9EDJHEBꢊꢁꢎ7I;:ꢁEDꢁ:;C7D:ꢁJ>;ꢁCE:KB7J?EDꢁH?D=ꢁ?Iꢁ79J?L7J;:ꢁI;7B?D=ꢁ
J>;ꢁ8OF7IIꢁFEHJIꢁ7D:ꢁ?DIJ7DJBOꢁI>?<J?D=ꢁ97F79?JOꢁJEꢁꢍꢆꢆꢌꢊꢁ.7A;ꢁ
7:L7DJ7=;ꢁE<ꢁTI>?<JꢁEDꢁJ>;ꢁYꢁOUꢁIJ7=;ꢁ9>7D=?D=ꢁꢏDEꢁIJEFF?D=ꢁ7D:ꢁ
IJ7HJ?D=ꢁH;GK?H;:ꢁB?A;ꢁEJ>;HꢁJMEꢈIJ7=;ꢁ9ECFH;IIEHIꢐꢊ
Electro deposition-Coated Air Coil
ꢀÊꢂ/ÊÃiÀiÃÊ`iÃÊvi>ÌÕÀiÊ>ÊiV>Ìi`
>ÀV°Ê/ꢁÃÊꢆiVÌÀ`i«ÃÌÊ«ÀViÃÃÊ
ÜÊ«ÀÛ`iÊÞi>ÀÃÊvÊ«ÀÌiVÌÊ>}>ÃÌÊ
VÀÀÃÊvÀÊ>ÀLÀiÊVꢁiV>ÃÊ
ÀiÃÕÌ}ÊvÀÊ`iÀÊLÕ`}Ê>ÌiÀ>Ê
ÕÌÊ}>ÃÃ}Ê>`ÊÃÌÊiÛÀiÌ>Ê
9>;C?97BIꢁ<EKD:ꢁ?DꢁJ>;ꢁ7?Hꢊꢁ'E:;HDꢁ8K?B:?D=ꢁ
C7J;H?7BIꢁIK9>ꢁ7Iꢁ9EKDJ;HꢈJEFIꢁYꢁEEHꢁ
9EL;H?D=IꢁF7?DJIꢁ7D:ꢁEJ>;HꢁC7J;H?7BIꢁ97Dꢁ
TEKJ=7IUꢁ9>;C?97BIꢁ?DJEꢁJ>;ꢁ>EC;VIꢁ7?Hꢊꢁ-EC;ꢁ
E<ꢁJ>;I;ꢁ9>;C?97BIꢁ7H;ꢁIKIF;9J;:ꢁE<ꢁ9EDJH?8KJ?D=ꢁJEꢁ9EHHEI?EDꢁ?Dꢁ
J>;ꢁ7?Hꢁ9E?BIꢁ<EKD:ꢁ?Dꢁ8EJ>ꢁJH7:?J?ED7Bꢁ7D:ꢁ=;EJ>;HC7Bꢁ>;7J?D=ꢁ7D:ꢁ
9EEB?D=ꢁ;GK?FC;DJꢊꢁꢀEHHEI?EDꢁE<J;DꢁH;IKBJIꢁ?DꢁH;<H?=;H7DJꢁB;7AIꢁ
7D:ꢁ;L;DJK7Bꢁ<7?BKH;ꢁE<ꢁJ>;ꢁ7?Hꢁ9E?Bꢁ9EIJ?D=ꢁ>KD:H;:IꢁE<ꢁ:EBB7HIꢁ
JEꢁH;FB79;ꢊꢁ
HBBB
7ꢁiÊꢄ«i>`Ê-VÀÊ1ÌÀ>Ê/iVꢁÒÊLÕ`ÃÊÊiÃÌ>LÃꢁi`ÊÃVÀÊ
ÌiVꢁ}Þ]ÊÌÊÃÊÃÌÊ>ÊÃVÀÊ>ÌÊꢁi>ÀÌ]ÊÜꢁVꢁÊi>ÃÊÌÊ«iÀ>ÌiÃÊ
ÜÌꢁÊviÜiÀÊÛ}Ê«>ÀÌÃÊ>`ÊÀiÃÕÌÊÊÕÃÕÀ«>ÃÃi`ÊÀi>LÌÞÊ>`Ê
ÛÀÌÕ>ÞÊÃiÌÊ«iÀ>Ì°
ꢐ&'ꢁ#ꢅ%ꢎꢂꢒꢓ(&##ꢂꢐ&$'(ꢁ))&(ꢂ
ꢃ9>?;L;ꢁ7ꢁ=H;7J;HꢁB;L;BꢁE<ꢁ9EC<EHJꢊꢁ.>;ꢁ
ꢀEF;B7D:ꢁ-9HEBBꢁ/BJH7.;9>WꢁFHEL?:;IꢁIKF;H?EHꢁ
9EC<EHJꢁJ>7
Ì
fixed-capacity compressors by
?D9EHFEH7J?D=ꢁ7ꢁH;LEBKJ?ED7HOꢁJMEꢈIJ;Fꢁ:;I?=Dꢊꢁ
1?J>ꢁ7ꢁKD?GK;ꢁꢇꢉꢌꢁF7HJꢈBE7:ꢁ97F79?JOꢁIJ;Fꢁ
IOIJ;CIꢁM?J>ꢁ/BJH7.;9>WꢁC7?DJ7?DꢁFH;9?I;ꢁ
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Heat Controller, Inc.
HTV/HTD/HTH SERIES
Engineering Design Guide
Two Stage Geothermal Heat Pump Systems
Copeland UltraTech Two-Stage Scroll Compressor
1
2
3
4
5
6
ꢀ>FÌi?ÃÌÊD/iBVꢁJꢈ}ÞꢂiVꢈÌÀꢁV> ÞÊVÕÌ>Ìi`]Ê
*À}À>>Li]Ê6>À>LiÊ-«ii`Ê ÜiÀÊꢃÌÀ
x
Ó
ꢂiVÌÀÊ`i«ÃÌÊV>Ìi`Ê>ÀÊV
!KBBOꢁ$DIKB7J;:ꢁꢊBEM;Hꢁ-;9J?EDꢁM?J>ꢁ!KBBOꢁ
$DIKB7J;:ꢁꢄECFH;IIEHꢁ-;9J?ED
$DJ;=H7J;:ꢁ!?BJ;Hꢁ,79AꢁM?J>ꢁ,;JKHDꢁꢉ?H
ꢇK9JꢁꢄEDD;9J?ED
-«i`Ê-Ì>iÃÃÊ-ÌiiÊꢄÀ>Ê*>ÊÜÌꢁÊ
ꢅ`iÃ>ÌiÊ"ÛiÀyÜÊ-iÃÀ
Î
{
1ÌÊ*iÀvÀ>ViÊ-iÌi\ÊꢆÕÌ>ÌVÊ
ꢆiÀÌÊ-ÞÃÌiÊꢀiÌÃÊꢇiÜiÀÊꢈÜÊꢉvÊ
7
È
£
/ꢁiÊ-ÞÃÌiÊꢉÃÊ ÌÊ,Õ}ÊꢆÌÊ*i>Ê
*iÀvÀ>ViI
ꢄÕLiÊ-«À}ÊorÊꢊÀiÌÊꢅ«ÀiÃÃÀÊ
8
9
ꢉÃ>ÌÊꢋÀÊ1ÌÀ>Ê+ÕiÌÊ"«iÀ>Ì
ꢋÛiÊꢂ>ÃÞÊ,iÛ>LiÊ-iÀÛViÊꢆVViÃÃÊ
*>iÃ
Ç
I7ꢁiÊÃÌ>i`ÊÜÌꢁÊ>ÊÌꢁiÀÃÌ>ÌÊÌꢁ>ÌÊꢁ>ÃÊ>Êv>ÕÌÊꢀꢂꢄ
8
Ó
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Engineering Design Guide
HTV/HTD/HTH SERIES
Heat Controller, Inc.
Two Stage Geothermal Heat Pump Systems
HT Series Ratings
ARI/ASHRAE/ISO 13256-1
at EWT (Entering Water Temperature)
HTV/HTD/HTH024
HTV/HTD/HTH036
HTV/HTD/HTH048
HTV/HTD/HTH060
HTV/HTD/HTH070
Heating capacities based upon 68°F DB, 59°F WB entering air temperature.
HT Electrical Data
Compressor
Voltage
Code
Min/Max
Voltage
Fan Motor Total Unit
Model
024
Voltage
QTY
1
RLA
LRA
FLA
FLA
MCA
21.2
Max/Fuse
30
1
1
1
1
1
208/230-60/1
197/254
197/254
197/254
197/254
197/254
10.3
52.0
3.9
18.6
036
048
060
070
208/230-60/1
208/230-60/1
208/230-60/1
208/230-60/1
1
1
1
1
16.7
21.2
25.6
27.2
82.0
96.0
3.9
6.9
6.9
6.9
25.0
32.5
36.9
38.5
29.2
37.8
43.3
45.3
45
50
60
70
118.0
150.0
Min/Max Voltage of 197/254
HACR circuit breaker in USA only
All fuses Class RK-5
Wire size based on 60°C copper conductor and Minimum Circuit Ampacity.
Wire length based on one way measurement with 2% voltage drop
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Heat Controller, Inc.
HTV/HTD/HTH SERIES
Engineering Design Guide
Two Stage Geothermal Heat Pump Systems
HT Physical Data
HT 024
HT 036
HT 048
HT 060
HT 070
Two-Stage Scroll
ECM Variable Speed
Vertical-HTV & Downflow-HTD
36x25
1-24x28
1-218x30
12-300x032
1-306x306
1-30x36
Standard Filter - 2” Pleated
HERV11, Quantity - in x in
Horizontal-HTH
Air Coil Dimensions (H x W), in
18 x 31
20 x 35
20 x 40
20 x 45
20 x 45
Standard Filter - 2” Pleated
MERV11, Quantity - in x in
1 - 12 x 20
1 - 20 x 25
1 - 18 x 20
1 - 20 x 24
2 - 18 x 18
2 - 20 x 24
2 - 20 x 24
Weight - Operating, lbs
Weight - Packaged, lbs
266
276
327
337
416
426
443
453
443
453
All units have spring compressor mountings, TXV expansion devices, and 1/2” [12.7mm] & 3/4” [19.1mm] electrical knockouts.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Engineering Design Guide
HTV/HTD/HTH SERIES
Heat Controller, Inc.
Two Stage Geothermal Heat Pump Systems
Dimensions – Vertical Upflow
Overall Cabinet
Vertical
Upflow
Model
A
B
Depth
C
Width
Height
in
cm
22.4
56.8
25.6
65.1
48.5
123.2
024
in
cm
25.4
64.5
30.6
77.8
50.5
128.3
036
in
cm
25.4
64.5
30.6
77.8
54.5
138.4
048
in
cm
25.4
64.5
30.6
77.8
58.5
148.6
060
in
cm
25.4
64.5
30.6
77.8
58.5
148.6
070
Water Connections
4
Vertical
Upflow
Model
1
2
3
5
F
HWG
IN
G
Loop
Water
IPT
D
In
E
Out
H
HWG
IPT
HWG
Out
Condensate
in
cm
2.1
5.2
10.0
25.4
13.9
35.2
16.9
42.9
7.8
19.8
1”
Swivel
1”
Swivel
024
in
cm
3.4
8.6
10.8
27.5
15.6
39.7
18.9
47.9
7.8
19.8
1”
Swivel
1”
Swivel
036
in
cm
3.4
8.6
10.8
27.5
15.6
39.7
18.9
47.9
7.8
19.8
1”
Swivel
1”
Swivel
048
in
cm
3.4
8.6
10.8
27.5
15.6
39.7
18.9
47.9
7.8
19.8
1”
Swivel
1”
Swivel
060
in
cm
3.4
8.6
10.8
27.5
15.6
39.7
18.9
47.9
7.8
19.7
1”
Swivel
1”
Swivel
070
Electrical Knockouts
K
Vertical
J
L
Upflow
1/2”
1/2”
3/4”
Model
Low
External
Power
Voltage
Pump
Supply
in
cm
3.6
9.2
6.1
15.6
8.6
21.9
024
in
cm
3.6
9.2
6.1
15.6
8.6
21.9
036
in
cm
3.6
9.2
6.1
15.6
8.6
21.9
048
in
cm
3.6
9.2
6.1
15.6
8.6
21.9
060
in
cm
3.6
9.2
6.1
15.6
8.6
21.9
070
Condensate is 3/4” PVC female glue socket and is switchable from front to side.
Unit shipped with deluxe duct collar/filter rack extending from unit 32”” [(5..1cm])aand is suuitableforrduuctconnnection. n
Discharge flange is field installed.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Heat Controller, Inc.
HTV/HTD/HTH SERIES
Engineering Design Guide
T
w
o
S
t
ag
e
G
eothe
rm
a
l
H
e
at
P
u
m
p
S
ys
t
s
em
Dimensions – Vertical Upflow
Return Connection
Standard Deluxe Filter Rack
(+/- 0.10 in, +/- 2.5mm)
Discharge Connection
Duct Flange Installed (+/- 0.10 in, +/- 2.5mm)
Vertical
Upflow
Model
M
Left
Return
O
P
Q
Right
Retuen
S
T
N
Supply
Width
Supply
Depth
R
Return
Depth
Return
Height
U
in
cm
7.8
18.3
5.8
14.8
14.0
35.6
14.0
35.6
4.9
12.4
1.7
4.2
22.2
56.4
26.2
66.4
1.5
3.9
024
in
cm
6.4
16.1
6.3
16.0
18.0
45.7
18.0
45.7
5.3
13.5
2.1
5.4
27.1
68.9
26.1
66.4
1.5
3.9
036
in
cm
6.4
16.1
6.3
16.0
18.0
45.7
18.0
45.7
5.3
13.5
2.1
5.4
27.1
68.9
30.1
76.5
1.5
3.9
048
in
cm
6.4
16.1
6.3
16.0
18.0
45.7
18.0
45.7
5.3
13.5
2.1
5.4
27.1
68.9
34.1
86.7
1.5
3.9
060
in
cm
6.4
16.1
6.3
16.0
18.0
45.7
18.0
45.7
5.3
13.5
2.1
5.4
27.1
68.9
34.1
86.7
1.5
3.9
070
Field Installed
Discharge Flange
Access Panels
Deluxe Filter Bracket
Legend
CAP=Control Access Panel
CSP=Compressor Service Panel
BSP=Blower Service Panel
ASP=Alternate Service Panel
Air Coil
B
ASP
P
N
P
N
BSP
O
M
2' (61cm)
Optional
Service
Access
O
A
Left Rtn
ASP
CSP
(right
Opposite)
CAP
Q
Air Coil Side
Air Coil Side
Top View-Right Return
Top View-Left Return
R
S
S
R
2' (61cm)
Service
Isometric
View
1.00 [25.4 mm]
U
U
Air Coil
Air Coil
Residential
Filter Rack
Shown
Residential
Filter Rack
Shown
T
T
1.68 [42.7 mm]
C
C
Condensate
Power Supply
3 / 4" [19.1mm]
HV Knockout
3 / 4" Glue
(PVC Socket)
4
3
CAP
1.63
[41.4 mm]
1 / 2" [12.7mm]
Knockout
1.18 [30.0 mm]
CSP
Low Voltage
1 / 2" [12.7mm]
LV Knockout
ASP
2
5
1
G
F
CSP
L
E
Front
Front
Back
Back
K
J
H
D
Right Return Right View
- Filter Rack Knife Edge
Left Return Left View
- Filter Rack Knife Edge
Front-View
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Engineering Design Guide
HTV/HTD/HTH SERIES
Heat Controller, Inc.
Two Stage Geothermal Heat Pump Systems
Dimensions – Vertical Downflow
Overall Cabinet
Vertical
Downflow
Model
A
B
Depth
C
Width
Height
in
cm
56.8
52.4
25.6
22.4
024
133.1
65.1
25.4
in
cm
30.6
77.8
54.4
036
64.5
138.2
in
cm
148.2
25.4
30.6
58.4
048
64.5
77.8
in
cm
25.4
30.6
62.4
060
64.5
77.8
158.5
in
cm
25.4
30.6
62.4
070
64.5
77.8
158.5
Water Connections
4
Vertical
1
2
3
5
Downflow
Model
F
HWG
IN
G
HWG
Out
Loop
Water
IPT
D
In
E
Out
H
HWG
IPT
Condensate
in
cm
13.7
6.1
8.9
1”
Swivel
1”
Swivel
17.0
14.0
5.4
3.6
2.4
024
42.9
35.3
in
cm
13.7
6.1
8.9
1”
Swivel
1”
Swivel
16.0
19.0
5.4
3.6
2.4
036
40.4
48.0
in
cm
6.1
1”
Swivel
1”
Swivel
19.0
16.0
5.4
3.6
2.4
048
48.0
40.4
13.7
8.9
19.0
in
cm
13.7
6.1
8.9
1”
Swivel
1”
Swivel
16.0
5.4
3.6
2.4
060
48.0
40.4
in
cm
6.1
1”
Swivel
1”
Swivel
16.0
19.0
5.4
3.6
2.4
070
40.4
48.0
13.7
8.9
Electrical Knockouts
K
Vertical
J
L
Downflow
1/2”
1/2”
3/4”
Model
Low
External
Power
Voltage
Pump
Supply
in
cm
13.7
9.7
24.1
7.2
024
33.0
17.8
in
cm
33.0
17.8
9.7
13.7
7.2
036
24.1
in
cm
33.0
24.1
17.8
7.2
13.7
9.7
048
in
cm
24.1
17.8
13.7
9.7
7.2
060
33.0
9.7
in
cm
13.7
7.2
070
24.1
33.0
17.8
Condensate is 3/4” PVC female glue socket and is switchable from front to side.
2” (5.1 cm) and is suitable for duct connection.
Unit shipped with deluxe duct collar/filter rack extending from unit 3
Downflow unit does not have discharge flange, and is rated for zero clearance installation.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Heat Controller, Inc.
HTV/HTD/HTH SERIES
Engineering Design Guide
T
w
o
S
t
ag
e
G
eothe
rm
a
l
H
e
at
P
u
m
p
S
y
st
s
em
Dimensions – Vertical Downflow
Return Connection
Standard Deluxe Filter Rack
(+/- 0.10 in, +/- 2.5mm)
Discharge Connection
Duct Flange Installed (+/- 0.10 in, +/- 2.5mm)
Vertical
Downflow
Model
M
Left
Return
O
P
Q
Right
Return
S
T
N
Supply
Width
Supply
Depth
R
Return
Depth
Return
Height
U
in
cm
20.8
26.4
23.5
4.6
56.6
53.6
26.2
6.1
10.9
8.2
9.4
1.8
22.3
21.1
10.4
024
66.5
15.4
27.9
in
cm
22.1
34.4
27.5
3.8
70.6
66.5
13.3
7.4
23.1
8.6
27.8
26.2
13.6
10.5
1.5
036
33.7
18.3
58.4
in
cm
27.5
3.8
70.6
58.4
13.6
13.3
7.4
8.6
30.2
10.5
1.5
27.8
23.1
048
34.4
33.7
18.3
22.1
76.7
in
cm
27.5
3.8
66.5
58.4
27.8
7.4
8.6
13.6
13.3
23.1
10.5
1.5
26.2
060
70.6
18.3
22.1
34.4
33.7
in
cm
18.3
22.1
27.5
3.8
70.6
86.9
58.4
13.3
13.6
7.4
8.6
10.5
1.5
23.1
27.8
34.2
070
33.7
34.4
Deluxe Filter Bracket
Legend
CAP=Control Access Panel
CSP=Compressor Service Panel
BSP=Blower Service Panel
ASP=Alternate Service Panel
CSP
ASP
CAP
P
N
N
ASP
P
Blower
Opening
2’ [61cm] Optional Service
O
Q
BSP
Blower
O
Access Right Rtn
(left opposite)
Opening
A
A
Front
Front
Condensate 3/4”
Glue
M
Air Coil Side
B
Air Coil Side
B
2’ [61cm] Service
Access
Left Return Discharge
Floor Foot Print
Right Return Discharge
Floor Foot Print
Isometric View
Right Return
Left Return
A
B
Filter Rack Dimensions
1.6
4
G
F
Power Supply
External Pump
3/4“HV
Knockout
L
3
K
“
E
3/4HV
Knockout
U
J
Low Voltage
D
“
2
1
1/2LV
“
1/2LV
Knockout
Knockout
Aux Htr Knock-Out
C
Access Panels
Access Panels
T
“
Condensate 3/4Ó
glue socket
H
5
R
S
Note:Filter Rack extends
out from cabinet 22”
O
M
N
O
P
P
N
Q
Discharge Dimensions
Discharge Dimensions
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Engineering Design Guide
HTV/HTD/HTH SERIES
Heat Controller, Inc.
Two Stage Geothermal Heat Pump Systems
Dimensions – V
Horizontal
Overall Cabinet
Horizontal
Model
A
Width
B
C
Depth
Height
in
cm
22.4
56.8
62.2
158.0
19.3
48.9
024
036
048
060
070
in
cm
25.4
64.5
71.2
180.8
21.3
54.0
in
cm
25.4
64.5
76.2
193.5
21.3
54.0
in
cm
25.4
64.5
81.2
206.2
21.3
54.0
in
cm
25.4
64.5
81.2
206.2
21.3
54.0
Water Connections
4
1
2
3
5
Horizontal
F
HWG
IN
G
HWG
Out
Loop
Water
IPT
Model
D
In
E
Out
H
HWG
IPT
Condensate
in
cm
2.1
5.2
10.0
25.4
13.9
35.2
16.9
42.9
0.6
1.5
1”
Swivel
1”
Swivel
024
036
048
060
070
in
cm
3.4
8.6
10.8
27.5
15.6
39.7
18.9
47.9
0.6
1.5
1”
Swivel
1”
Swivel
in
cm
3.4
8.6
10.8
27.5
15.6
39.7
18.9
47.9
0.6
1.5
1”
Swivel
1”
Swivel
in
cm
3.4
8.6
10.8
27.5
15.6
39.7
18.9
47.9
0.6
1.5
1”
Swivel
1”
Swivel
in
cm
3.4
8.6
10.8
27.5
15.6
39.7
18.9
47.9
0.6
1.5
1”
Swivel
1”
Swivel
Electrical Knockouts
K
J
L
Horizontal
Model
1/2”
1/2”
3/4”
Low
Voltage
External
Pump
Power
Supply
in
cm
3.6
9.2
6.1
15.6
8.6
21.9
024
036
048
060
070
in
cm
3.4
9.2
6.1
15.6
8.6
21.9
in
cm
3.6
9.2
6.1
15.6
8.6
21.9
in
cm
3.6
9.2
6.1
15.6
8.6
21.9
in
cm
3.6
9.2
6.1
15.6
8.6
21.9
Condensate is 3/4” IPT.
Unit shipped with deluxe duct collar/filter rack extending from unit 3” [7.6cm] and is suitable for duct connection.
Discharge flange and hanger brackets are factory installed.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Heat Controller, Inc.
HTV/HTD/HTH SERIES
Engineering Design Guide
Two Stage Geothermal Heat Pump Systems
Dimensions – V
Horizontal
Return Connection
Standard Deluxe Filter Rack
(+/- 0.10 in, +/- 2.5mm)
Discharge Connection
Duct Flange Installed (+/- 0.10 in, +/- 2.5mm)
Horizontal
Model
O
P
S
T
M
N
Supply
Width
Supply
Depth
Q
R
Return
Depth
Return
Height
U
V
in
cm
3.6
9.3
2.0
5.1
12.5
31.8
15.5
39.4
3.6
9.2
2.0
5.2
33.8
85.8
16.2
41.0
2.3
5.8
1.5
3.9
024
036
048
060
070
in
cm
3.1
7.4
1.2
3.1
19.0
48.3
17.5
44.5
3.1
7.4
1.0
2.6
34.8
88.3
18.2
46.1
3.1
7.8
1.5
3.9
in
cm
3.1
7.4
1.2
3.1
19.0
48.3
17.5
44.5
3.1
7.4
1.0
2.6
39.8
101.0
18.2
46.1
3.1
7.8
1.5
3.9
in
cm
3.1
7.4
1.2
3.1
19.0
48.3
17.5
44.5
3.1
7.4
1.0
2.6
44.8
113.7
18.2
46.1
3.1
7.8
1.5
3.9
in
cm
3.1
7.4
1.2
3.1
19.0
48.3
17.5
44.5
3.1
7.4
1.0
2.6
44.8
113.7
18.2
46.1
3.1
7.8
1.5
3.9
Legend
CAP=Control Access Panel
LEFT RETURN
RIGHT RETURN
CSP=Compressor Service Panel
BSP=Blower Service Panel
ASP=Alternate Service Panel
2" [61cm] Service
Access
Front
2" [61cm] Service
Access
CSP
2" [61cm] optional
service access
Front
2" [61cm] optional
service access
Power Supply
3 / 4" Knockout
Left Return
Right Return
1.6 [40.6mm]
1.6 [40.6mm]
1 / 2"
Knockout
CSP
ASP
3.25
[82.6mm]
Low Voltage
1 / 2" Knockout
3.25
[82.6mm]
4
3
L
G
2
1
K
F
E
J
CAP
A
H
H
Straight
Discharge
5
Straight
Discharge
5
D
Condensate
3 / 4" IP T
Back
Discharge
Back
Discharge
Front-View
Condensate
3 / 4" IP T
Unit Hanger Detail
R
P
X
Y
Z
Model
Q
in.
cm.
157.7
180.6
193.3
206
in.
cm.
62.2
69.9
69.9
69.9
69.9
in.
cm.
P
BSP
Blower
Outlet
024
036
048
060
070
62.1
71.1
76.1
81.1
81.1
24.5
27.5
27.5
27.5
27.5
20.25
23.25
23.25
23.25
23.25
51.5
59.1
59.1
59.1
59.1
BSP
O
Q
Y
Z
C
C
Blower
Outlet
O
R
206
A
A
X
Right Return Back Discharge
Left Return Back Discharge
P
M
O
N
P
Blower
Outlet
BSP
ASP
BSP
CSP
Blower
Outlet
O
N
Front
Front
M
Right Return Straight Discharge
Left Return Straight Discharge
1.1 [27.9mm]
Air Coil
V
C
V
U
S
S
Air Coil
U
CSP
ASP
T
T
C
Front
Front
B
Left Return Left View
- Filter Rack Knife Edge
B
Right Return Right View
- Filter Rack Knife Edge
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Engineering Design Guide
HTV/HTD/HTH SERIES
Heat Controller, Inc.
Two Stage Geothermal Heat Pump Systems
PERFORMANCE DATA
HTV024, HTD024 & HTH024 Part Load
Performance capacities shown in thousands of Btuh.
560 CFM Rated Airflow
COOLING - EAT 80°F DB / 67°F WB
HEATING - EAT 70°F
WPD
Sens/Tot
Ratio
EWT °F GPM
PSI
FT
TC
SC
KW
HR
EER
HWG
HC
KW
HE
LAT
COP
HWG
Operation Not Recommended
1.4
20
30
7.0
3.5
5.8
7.0
3.5
5.8
7.0
3.5
5.8
7.0
3.5
5.8
7.0
3.5
5.8
7.0
3.5
5.8
7.0
3.5
5.8
7.0
3.5
5.8
7.0
3.5
5.8
7.0
3.5
5.8
7.0
4.5
1.2
2.8
4.1
1.1
2.6
3.6
1.0
2.4
3.4
1.0
2.2
3.2
0.9
2.1
3.0
0.8
2.0
2.8
0.8
1.9
2.7
0.8
1.8
2.6
0.7
1.7
2.5
0.7
1.7
2.4
10.3
2.8
6.5
9.4
2.5
5.9
8.4
2.3
5.5
7.9
2.2
5.1
7.4
2.1
4.8
7.0
1.9
4.5
6.5
1.8
4.3
6.2
1.8
4.1
6.0
1.7
4.0
5.7
1.6
3.9
5.5
11.4
13.3
13.9
14.1
15.7
16.4
16.6
17.9
18.7
18.9
20.0
20.8
21.0
22.0
22.8
23.1
23.9
24.8
25.1
25.8
26.8
27.1
1.06
1.10
1.11
1.11
1.17
1.17
1.17
1.19
1.19
1.20
1.23
1.23
1.24
1.24
1.25
1.25
1.26
1.27
1.27
1.28
1.30
1.30
7.8
88.8
92.1
3.14
3.54
3.69
3.74
3.95
4.11
4.16
4.41
4.58
4.63
4.77
4.94
4.99
5.18
5.35
5.39
5.55
5.71
5.76
5.88
6.05
6.10
1.9
1.5
2.0
0.5
21.6
21.9
21.9
22.4
22.6
22.6
22.2
22.4
22.5
21.4
21.9
22.0
20.2
20.9
21.1
18.9
19.6
19.8
17.6
18.1
18.4
16.2
16.7
16.9
15.1
15.4
15.6
14.2
14.5
14.6
13.5
13.5
13.5
14.5
14.6
14.6
14.9
14.9
14.9
14.8
15.0
15.0
14.3
14.6
14.7
13.7
14.0
14.1
13.2
13.4
13.5
12.5
12.7
12.8
12.3
12.2
12.3
12.2
12.1
12.1
0.62
0.62
0.62
0.65
0.65
0.64
0.67
0.67
0.67
0.69
0.68
0.68
0.71
0.70
0.70
0.73
0.72
0.71
0.75
0.74
0.73
0.78
0.76
0.76
0.81
0.79
0.79
0.86
0.84
0.83
0.57
0.56
0.56
0.64
0.60
0.60
0.73
0.68
0.67
0.84
0.78
0.76
0.96
0.89
0.87
1.09
1.02
1.00
1.24
1.17
1.14
1.40
1.33
1.31
1.57
1.51
1.49
1.82
1.71
1.69
23.6
23.8
23.8
24.6
24.6
24.7
24.7
24.7
24.7
24.2
24.5
24.6
23.5
23.9
24.0
22.6
23.1
23.2
21.8
22.1
22.3
20.9
21.2
21.3
20.5
20.6
20.6
20.4
20.3
20.3
37.8
38.7
39.3
34.8
37.4
37.8
30.3
33.0
33.7
25.6
28.2
29.0
21.1
23.5
24.2
17.3
19.2
19.8
14.3
15.6
16.1
11.6
12.6
12.9
9.6
-
9.6
1.6
2.0
0.4
-
10.2
10.3
11.8
12.4
12.6
13.9
14.6
14.8
15.8
16.6
16.8
17.7
18.5
18.8
19.6
20.5
20.7
21.4
22.3
22.6
93.0
0.4
1.6
1.9
93.3
1.6
-
96.0
0.7
1.7
2.0
40
50
-
0.7
97.1
0.6
-
1.8
97.4
1.1
1.7
2.1
99.7
1.8
1.0
100.9
101.2
103.1
104.4
104.8
106.3
107.7
108.1
109.5
111.0
111.4
112.6
114.3
114.8
0.9
0.6
1.9
2.0
1.1
2.1
2.2
1.9
1.9
2.0
60
1.7
1.9
2.1
2.1
2.2
1.7
70
1.5
2.2
2.3
2.4
2.2
2.3
2.3
80
2.1
2.4
2.4
3..3
3.0
1.9
90
2.5
2.8
2.5
3.8
3.7
100
110
120
3.6
4.9
4.7
Operation Not Recommended
10.2
10.5
7.8
4.5
6.2
5.9
8.4
5.7
8.6
†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB
EAT in cooling and 68°F DB / 59°F WB EAT in heating.
Interpoaltion is permissable, extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating
All performance data is based upon the lower voltage of dual voltage rated units
See performance correction tables for operating conditions other than those listed above.
Operation below 60°F EWT requires optional insulated water circuit.
Operation below 40°F EWT is based upon 15% antifreeze solution.
,EGEND
Ìi\
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
25<ꢀ /ꢀ JR[fꢀX` ꢀL^KRLꢀONN]#VRW^]N
ꢀÀÊ«iÀ>ÌÊÊÌꢁiÊÃꢁ>`i`Ê>Ài>ÊÜꢁiÊÜ>ÌiÀÊÃÊÕÃi`ÊÊiÕÊvÊ>Ê
>ÌvÀiiâiÊÃÕÌ]ÊÌꢁiÊꢂ7/Ê-ꢂi>Û}Ê7>ÌiÀÊ/i«iÀ>ÌÕÀi®ÊÕÃÌÊ
LiÊV>VÕ>Ìi`°ÊꢀÜÊÕÃÌÊLiÊ>Ì>i`ÊÌÊ>ÊiÛiÊÃÕVꢁÊÌꢁ>ÌÊ
ÌꢁiÊꢂ7/ÊÃÊ>Ì>i`Ê>LÛiÊ{äÂꢀÊÜꢁiÊÌꢁiÊꢃ7ÎÊÕ«iÀÊÃÊÌÊ
V««i`°Ê/ꢁÃÊÃÊ`ÕiÊÌÊÌꢁiÊ«ÌiÌ>ÊvÊÌꢁiÊÀivÀ}iÀ>ÌÊÌi«iÀ>
ÌÕÀiÊLi}Ê>ÃÊÜÊ>ÃÊÎÓÂꢀÊÜÌꢁÊ{äÂꢀÊꢂ7/]ÊÜꢁVꢁÊ>ÞÊi>`ÊÌÊ>Ê
ÕÃ>ViÊVÕÌÕÌÊ`ÕiÊÌÊÌꢁiÊ>VÌÛ>ÌÊvÊÌꢁiÊꢂÜÊ/i«iÀ>ÌÕÀiÊ
*ÀÌiVÌ°Êꢃ7ÎÊÃꢁÕ`ÊiÛiÀÊLiÊV««i`ÊvÀÊÃÞÃÌiÃÊÜÌꢁÕÌÊ
>ÌvÀiiâi°
4FCꢀ /ꢀ NW]N[RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀꢁ5
6?<ꢀ /ꢀ `J]N[ꢀfꢀX`ꢀRWꢀDBꢀPJUUXW\#VRW^]N
40Cꢀ /ꢀ NW]N[RWPꢀJR[ꢀ]NVYN[J]^[N ꢀ5JQ[NWQNR]ꢀꢂM[bꢀK^UK#`N]ꢀK^UKꢃ
72ꢀ /ꢀ JR[ꢀQNJ]RWPꢀLJYJLR]b ꢀ<K]^Q
C2ꢀ /ꢀ ]X]JUꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B2ꢀ /ꢀ \NW\RKUNꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
:Fꢀ /ꢀ ]X]JUꢀYX`N[ꢀ^WR]ꢀRWY^] ꢀ:RUXFJ]]\
7Aꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀ[NSNL]RXW ꢀ<K]^Q
ꢀ
74ꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀNa][JL]RXW ꢀ<K]^Q
ꢀ 7F2ꢀ /ꢀ 7X]ꢀFJ]N[ꢀ6NWN[J]X[ꢀꢂMN\^YN[QNJ]N[ꢃꢀLJYJLR]b ꢀ<K]^Q
ꢀꢀꢀF?3ꢀ /ꢀ FJ]N[ꢀLXRUꢀY[N\\^[NꢀM[XYꢀꢂY\RꢀꢄꢀO]ꢀQMꢃ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
44Aꢀ /ꢀ 4WN[Pbꢀ4OeꢀLRNWLbꢀAJ]RXꢀ/ꢀ1CDꢀX^]Y^]#FJ]]ꢀRWY^]
2>?ꢀ /ꢀ 2XNOeꢀLRNW]ꢀXOꢀ?N[OX[VJWLNꢀ/ꢀ1CDꢀX^]Y^]#1CDꢀRWY^]
;FCꢀ /ꢀ UNJ_RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀg5
ꢄ>VÕ>ÌiÊꢂ7/>ÃÊvÜÃ\
ꢆꢅ
Ê
Ê
Ê
ꢂ7/ÊrÊꢅ7/ÊÊ
;0Cꢀ /ꢀ UNJ_RWPꢀJR[ꢀ]NVYN[J]^[N ꢀg5
ꢇ*ꢈÊÝÊxää
;2ꢀ /ꢀ UJ]NW]ꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B#Cꢀ /ꢀ \NW\RKUNꢀ]Xꢀ]X]JUꢀLXXURWPꢀ[J]RX
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Heat Controller, Inc.
HTV/HTD/HTH SERIES
Engineering Design Guide
Two Stage Geothermal Heat Pump Systems
PERFORMANCE DATA
H
HTV024, HTD024 & HTH024 Full Load
Performance capacities shown in thousands of Btuh.
800 CFM Rated Airflow
WPD
COOLING - EAT 80°F DB / 67°F WB
HEATING - EAT 70°F
Sens/Tot
Ratio
EWT °F GPM
PSI
FT
TC
SC
KW
HR
EER
HWG
HC
KW
HE
LAT
COP
HWG
Operation Not Recommended
1.6
20
30
8.0
4.0
6.0
8.0
4.0
6.0
8.0
4.0
6.0
8.0
4.0
6.0
8.0
4.0
6.0
8.0
4.0
6.0
8.0
4.0
6.0
8.0
4.0
6.0
8.0
4.0
6.0
8.0
4.0
6.0
8.0
5.6
1.5
3.1
5.1
1.3
2.8
4.5
1.3
2.6
4.3
1.2
2.5
4.0
1.1
2.3
3.8
1.0
2.2
3.5
10.3
2.8
6.5
9.4
2.5
5.9
8.4
2.3
5.5
7.9
2.2
5.1
7.4
2.1
4.8
7.0
1.9
4.5
6.5
1.8
4.3
6.2
1.8
4.1
6.0
1.7
4.0
5.7
1.6
3.9
5.5
15.0
17.8
18.6
19.1
21.2
22.2
22.7
24.4
25.4
25.9
27.2
28.3
28.8
29.9
31.0
31.5
32.3
33.5
34.0
34.7
35.9
36.5
1.47
1.53
1.54
1.55
1.61
1.63
1.64
1.69
1.71
1.73
1.76
1.80
1.81
1.84
1.88
1.89
1.92
1.96
1.98
2.00
2.04
2.06
10.0
12.6
13.3
13.8
15.8
16.6
17.1
18.6
19.5
20.0
21.2
22.2
22.7
23.6
24.6
25.0
25.8
26.8
27.3
27.9
28.9
29.4
87.4
90.6
3.00
3.41
3.53
3.60
3.88
3.99
4.05
4.24
4.35
4.40
4.53
4.62
4.66
4.75
4.83
4.87
4.93
5.01
5.04
5.09
5.16
5.19
2.4
1.9
2.4
0.6
30.6
30.8
31.0
30.4
30.7
30.8
29.6
30.1
30.3
28.4
29.1
29.4
27.0
27.8
28.2
25.4
26.2
26.7
23.7
24.5
25.0
22.0
22.8
23.3
20.5
21.2
21.6
19.1
19.7
20.0
19.6
19.6
19.7
20.0
20.1
20.1
20.1
20.2
20.2
19.7
19.9
20.0
19.0
19.4
19.6
18.3
18.7
18.9
17.5
17.9
18.1
16.7
17.1
17.3
16.0
16.3
16.5
15.5
15.7
15.8
0.64
0.64
0.63
0.66
0.65
0.65
0.68
0.67
0.67
0.69
0.68
0.68
0.71
0.70
0.69
0.72
0.71
0.71
0.74
0.73
0.72
0.76
0.75
0.74
0.78
0.77
0.76
0.81
0.80
0.79
1.02
0.97
0.95
1.11
1.06
1.03
1.23
1.16
1.13
1.35
1.28
1.24
1.50
1.42
1.38
1.66
1.57
1.53
1.84
1.75
1.70
2.05
1.95
1.89
2.29
2.17
2.11
2.55
2.43
2.36
34.1
34.1
34.2
34.2
34.3
34.3
33.8
34.1
34.2
33.0
33.5
33.7
32.1
32.6
32.9
31.0
31.6
31.9
30.0
30.5
30.8
29.0
29.5
29.7
28.3
28.6
28.8
27.8
28.0
28.1
30.1
31.8
32.8
27.3
29.0
29.9
24.2
25.9
26.8
21.0
22.8
23.6
18.0
19.6
20.5
15.3
16.7
17.5
12.9
14.1
14.7
10.7
11.7
12.3
8.9
-
2.0
2.4
0.6
-
91.5
0.5
-
2.1
2.4
92.1
2.2
1.-0
94.6
2.3
2.5
0.9
-
40
50
95.7
0.9
-
2.4
96.3
1.6
1.1
2.5
2.6
98.2
2.6
2.6
1.5
99.4
1.3
2.7
2.6
100.0
101.5
102.7
103.4
104.6
105.8
106.5
107.4
108.7
109.4
110.2
111.5
112.2
.
2.2
.8
2.8
2.0
2.9
60
1.8
3.0
3.0
3.1
3.3
2.7
70
2.4
3.4
3.0
3.6
3.4
3.6
3.3
80
3.0
3.7
3.7
4.5
1.0
2.1
3.4
1.0
2.0
3.2
0.9
1.9
3.1
0.9
1.8
3.0
4.2
2.8
3.9
90
3.9
4.0
5.0
4.8
100
110
120
4.6
6.0
5.8
Operation Not Recommended
9.8
5.5
10.2
7.5
7.1
6.8
8.1
6.5
8.5
†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB
EAT in cooling and 68°F DB / 59°F WB EAT in heating.
Interpoaltion is permissable, extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating
All performance data is based upon the lower voltage of dual voltage rated units
See performance correction tables for operating conditions other than those listed above.
Operation below 60°F EWT requires optional insulated water circuit.
Operation below 40°F EWT is based upon 15% antifreeze solution.
,EGEND
Ìi\
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
25<ꢀ /ꢀ JR[fꢀX` ꢀL^KRLꢀONN]#VRW^]N
ꢀÀÊ«iÀ>ÌÊÊÌꢁiÊÃꢁ>`i`Ê>Ài>ÊÜꢁiÊÜ>ÌiÀÊÃÊÕÃi`ÊÊiÕÊvÊ>Ê
>ÌvÀiiâiÊÃÕÌ]ÊÌꢁiÊꢂ7/Ê-ꢂi>Û}Ê7>ÌiÀÊ/i«iÀ>ÌÕÀi®ÊÕÃÌÊ
LiÊV>VÕ>Ìi`°ÊꢀÜÊÕÃÌÊLiÊ>Ì>i`ÊÌÊ>ÊiÛiÊÃÕVꢁÊÌꢁ>ÌÊ
ÌꢁiÊꢂ7/ÊÃÊ>Ì>i`Ê>LÛiÊ{äÂꢀÊÜꢁiÊÌꢁiÊꢃ7ÎÊÕ«iÀÊÃÊÌÊ
V««i`°Ê/ꢁÃÊÃÊ`ÕiÊÌÊÌꢁiÊ«ÌiÌ>ÊvÊÌꢁiÊÀivÀ}iÀ>ÌÊÌi«iÀ>
ÌÕÀiÊLi}Ê>ÃÊÜÊ>ÃÊÎÓÂꢀÊÜÌꢁÊ{äÂꢀÊꢂ7/]ÊÜꢁVꢁÊ>ÞÊi>`ÊÌÊ>Ê
ÕÃ>ViÊVÕÌÕÌÊ`ÕiÊÌÊÌꢁiÊ>VÌÛ>ÌÊvÊÌꢁiÊꢂÜÊ/i«iÀ>ÌÕÀiÊ
*ÀÌiVÌ°Êꢃ7ÎÊÃꢁÕ`ÊiÛiÀÊLiÊV««i`ÊvÀÊÃÞÃÌiÃÊÜÌꢁÕÌÊ
>ÌvÀiiâi°
4FCꢀ /ꢀ NW]N[RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀꢁ5
6?<ꢀ /ꢀ `J]N[ꢀfꢀX`ꢀRWꢀDBꢀPJUUXW\#VRW^]N
40Cꢀ /ꢀ NW]N[RWPꢀJR[ꢀ]NVYN[J]^[N ꢀ5JQ[NWQNR]ꢀꢂM[bꢀK^UK#`N]ꢀK^UKꢃ
72ꢀ /ꢀ JR[ꢀQNJ]RWPꢀLJYJLR]b ꢀ<K]^Q
C2ꢀ /ꢀ ]X]JUꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B2ꢀ /ꢀ \NW\RKUNꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
:Fꢀ /ꢀ ]X]JUꢀYX`N[ꢀ^WR]ꢀRWY^] ꢀ:RUXFJ]]\
7Aꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀ[NSNL]RXW ꢀ<K]^Q
ꢀ
74ꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀNa][JL]RXW ꢀ<K]^Q
ꢀ 7F2ꢀ /ꢀ 7X]ꢀFJ]N[ꢀ6NWN[J]X[ꢀꢂMN\^YN[QNJ]N[ꢃꢀLJYJLR]b ꢀ<K]^Q
ꢀꢀꢀF?3ꢀ /ꢀ FJ]N[ꢀLXRUꢀY[N\\^[NꢀM[XYꢀꢂY\RꢀꢄꢀO]ꢀQMꢃ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
44Aꢀ /ꢀ 4WN[Pbꢀ4OeꢀLRNWLbꢀAJ]RXꢀ/ꢀ1CDꢀX^]Y^]#FJ]]ꢀRWY^]
2>?ꢀ /ꢀ 2XNOeꢀLRNW]ꢀXOꢀ?N[OX[VJWLNꢀ/ꢀ1CDꢀX^]Y^]#1CDꢀRWY^]
;FCꢀ /ꢀ UNJ_RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀg5
ꢄ>VÕ>ÌiÊꢂ7/>ÃÊvÜÃ\
ꢆꢅ
Ê
Ê
Ê
ꢂ7/ÊrÊꢅ7/ÊÊ
;0Cꢀ /ꢀ UNJ_RWPꢀJR[ꢀ]NVYN[J]^[N ꢀg5
ꢇ*ꢈÊÝÊxää
;2ꢀ /ꢀ UJ]NW]ꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B#Cꢀ /ꢀ \NW\RKUNꢀ]Xꢀ]X]JUꢀLXXURWPꢀ[J]RX
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Engineering Design Guide
HTV/HTD/HTH SERIES
Heat Controller, Inc.
Two Stage Geothermal Heat Pump Systems
PERFORMANCE DATA
H
ꢀ
HTV036, HTD036 & HTH036 Part Load
Performance capacities shown in thousands of Btuh.
800 CFM Rated Airflow
COOLING - EAT 80°F DB / 67°F WB
HEATING - EAT 70°F
WPD
Sens/Tot
Ratio
EWT °F GPM
PSI
FT
TC
SC
KW
HR
EER
HWG
HC
KW
HE
LAT
COP
HWG
Operation Not Recommended
1.9
20
30
8.0
4.0
6.0
8.0
4.0
6.0
8.0
4.0
6.0
8.0
4.0
6.0
8.0
4.0
6.0
8.0
4.0
6.0
8.0
4.0
6.0
8.0
4.0
6.0
8.0
4.0
6.0
8.0
4.0
6.0
8.0
4.7
1.2
2.6
4.5
1.1
2.6
4.4
1.0
2.5
4.2
0.9
2.4
4.1
0.8
2.3
4.0
0.7
2.3
3.9
10.9
2.8
6.1
10.4
2.5
5.9
10.2
2.2
5.7
9.7
2.0
5.5
9.5
1.8
5.3
9.2
1.7
5.2
9.0
17.3
19.1
19.8
20.1
21.8
22.6
23.1
24.6
25.6
26.2
27.5
28.7
29.4
30.5
32.0
32.7
33.7
35.3
36.2
36.9
38.8
39.9
1.46
1.51
1.51
1.51
1.56
1.57
1.58
1.64
1.64
1.65
1.66
1.66
1.67
1.68
1.68
1.69
1.70
1.71
1.71
1.72
1.73
1.74
12.3
14.0
14.6
15.0
16.5
17.3
17.7
19.0
20.0
20.5
21.9
23.0
23.7
24.8
26.2
27.0
27.9
29.5
30.4
31.0
32.9
33.9
90.0
92.1
3.48
3.71
3.84
3.91
4.08
4.22
4.29
4.40
4.57
4.64
4.87
5.06
5.16
5.34
5.56
5.68
5.82
6.06
6.20
6.30
6.57
6.73
2.4
2.1
0.5
29.8
30.1
30.3
30.6
30.8
31.0
30.3
30.7
30.9
29.2
29.9
30.2
27.7
28.6
29.0
26.0
26.9
27.4
24.2
25.1
25.6
22.7
23.4
23.8
21.5
22.0
22.3
20.7
21.1
21.3
18.9
18.9
19.0
20.4
20.4
20.5
21.1
21.2
21.2
21.2
21.3
21.4
20.6
20.9
21.1
19.8
20.2
20.4
19.0
19.4
19.6
18.5
18.7
18.9
18.3
18.3
18.4
18.0
18.3
18.4
0.63
0.63
0.63
0.67
0.66
0.66
0.70
0.69
0.69
0.72
0.71
0.71
0.74
0.73
0.73
0.76
0.75
0.75
0.79
0.77
0.77
0.81
0.80
0.79
0.85
0.83
0.82
0.87
0.87
0.86
0.79
0.75
0.73
0.90
0.84
0.81
1.03
0.95
0.92
1.19
1.09
1.05
1.36
1.26
1.21
1.56
1.45
1.39
1.78
1.66
1.60
2.02
1.89
1.83
2.30
2.16
2.09
2.57
2.44
2.40
32.5
32.7
32.8
33.6
33.7
33.7
33.8
33.9
34.0
33.3
33.7
33.8
32.3
32.9
33.1
31.3
31.9
32.2
30.3
30.8
31.1
29.6
29.9
30.1
29.3
29.4
29.5
29.4
29.5
29.5
37.7
40.3
41.6
34.0
36.9
38.3
29.4
32.2
33.7
24.6
27.3
28.7
20.4
22.7
24.0
16.7
18.6
19.7
13.6
15.1
16.0
11.2
12.4
13.0
9.4
-
2.1
2.4
0.5
-
92.9
0.4
-
2.2
2.4
93.3
2.2
2.5
0.-8
95.2
2.3
2.5
0.7
-
40
50
96.2
0.7
-
2.4
96.7
1.2
0.8
2.4
98.5
2.5
2.6
1.1
99.6
1.0
2.6
100.3
101.9
103.2
104.0
105.3
107.0
107.9
109.0
110.9
111.9
112.7
114.9
116.1
2.5
2.6
2.2
1.2
2.7
60
2.0
21..28
2.8
2.9
3.0
2.0
1.7
70
1.8
1.5
3.1
2.8
33..10
3.2
2.6
80
2.4
3.3
3.3
3.2
3.8
0.6
2.1
3.7
0.6
2.1
3.6
0.6
2.0
3.4
0.5
1.9
3.3
1.5
4.9
8.5
1.4
4.8
8.3
1.3
4.6
7.9
1.2
4.5
7.7
3.6
3.4
90
3.3
3.6
4.5
4.3
100
110
120
4.2
5.8
5.6
Operation Not Recommended
10.2
10.7
8.1
5.4
7.3
7.0
8.6
6.8
8.9
†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB
EAT in cooling and 68°F DB / 59°F WB EAT in heating.
Interpoaltion is permissable, extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating
All performance data is based upon the lower voltage of dual voltage rated units
See performance correction tables for operating conditions other than those listed above.
Operation below 60°F EWT requires optional insulated water circuit.
Operation below 40°F EWT is based upon 15% antifreeze solution.
,EGEND
Ìi\
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
25<ꢀ /ꢀ JR[fꢀX` ꢀL^KRLꢀONN]#VRW^]N
ꢀÀÊ«iÀ>ÌÊÊÌꢁiÊÃꢁ>`i`Ê>Ài>ÊÜꢁiÊÜ>ÌiÀÊÃÊÕÃi`ÊÊiÕÊvÊ>
>ÌvÀiiâiÊÃÕÌ]ÊÌꢁiÊꢂ7/Ê-ꢂi>Û}Ê7>ÌiÀÊ/i«iÀ>ÌÕÀi®ÊÕÃÌ
LiÊV>VÕ>Ìi`°ÊꢀÜÊÕÃÌÊLiÊ>Ì>i`ÊÌÊ>ÊiÛiÊÃÕVꢁÊÌꢁ>ÌÊ
ÌꢁiÊꢂ7/ÊÃÊ>Ì>i`Ê>LÛiÊ{äÂꢀÊÜꢁiÊÌꢁiÊꢃ7ÎÊÕ«iÀÊÃÊÌÊ
V««i`°Ê/ꢁÃÊÃÊ`ÕiÊÌÊÌꢁiÊ«ÌiÌ>ÊvÊÌꢁiÊÀivÀ}iÀ>ÌÊÌi«iÀ>
ÌÕÀiÊLi}Ê>ÃÊÜÊ>ÃÊÎÓÂꢀÊÜÌꢁÊ{äÂꢀÊꢂ7/]ÊÜꢁVꢁÊ>ÞÊi>`ÊÌÊ>Ê
ÕÃ>ViÊVÕÌÕÌÊ`ÕiÊÌÊÌꢁiÊ>VÌÛ>ÌÊvÊÌꢁiÊꢂÜÊ/i«iÀ>ÌÕÀiÊ
*ÀÌiVÌ°Êꢃ7ÎÊÃꢁÕ`ÊiÛiÀÊLiÊV««i`ÊvÀÊÃÞÃÌiÃÊÜÌꢁÕÌÊ
>ÌvÀiiâi°
4FCꢀ /ꢀ NW]N[RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀꢁ5
6?<ꢀ /ꢀ `J]N[ꢀfꢀX`ꢀRWꢀDBꢀPJUUXW\#VRW^]N
40Cꢀ /ꢀ NW]N[RWPꢀJR[ꢀ]NVYN[J]^[N ꢀ5JQ[NWQNR]ꢀꢂM[bꢀK^UK#`N]ꢀK^UKꢃ
72ꢀ /ꢀ JR[ꢀQNJ]RWPꢀLJYJLR]b ꢀ<K]^Q
C2ꢀ /ꢀ ]X]JUꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B2ꢀ /ꢀ \NW\RKUNꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
:Fꢀ /ꢀ ]X]JUꢀYX`N[ꢀ^WR]ꢀRWY^] ꢀ:RUXFJ]]\
7Aꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀ[NSNL]RXW ꢀ<K]^Q
ꢀ
74ꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀNa][JL]RXW ꢀ<K]^Q
ꢀ 7F2ꢀ /ꢀ 7X]ꢀFJ]N[ꢀ6NWN[J]X[ꢀꢂMN\^YN[QNJ]N[ꢃꢀLJYJLR]b ꢀ<K]^Q
ꢀꢀꢀF?3ꢀ /ꢀ FJ]N[ꢀLXRUꢀY[N\\^[NꢀM[XYꢀꢂY\RꢀꢄꢀO]ꢀQMꢃ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
44Aꢀ /ꢀ 4WN[Pbꢀ4OeꢀLRNWLbꢀAJ]RXꢀ/ꢀ1CDꢀX^]Y^]#FJ]]ꢀRWY^]
2>?ꢀ /ꢀ 2XNOeꢀLRNW]ꢀXOꢀ?N[OX[VJWLNꢀ/ꢀ1CDꢀX^]Y^]#1CDꢀRWY^]
;FCꢀ /ꢀ UNJ_RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀg5
ꢄ>VÕ>ÌiÊꢂ7/>ÃÊvÜÃ\
ꢆꢅ
Ê
Ê
Ê
ꢂ7/ÊrÊꢅ7/ÊÊ
;0Cꢀ /ꢀ UNJ_RWPꢀJR[ꢀ]NVYN[J]^[N ꢀg5
ꢇ*ꢈÊÝÊxää
;2ꢀ /ꢀ UJ]NW]ꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B#Cꢀ /ꢀ \NW\RKUNꢀ]Xꢀ]X]JUꢀLXXURWPꢀ[J]RX
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Heat Controller, Inc.
HTV/HTD/HTH SERIES
Engineering Design Guide
Two Stage Geothermal Heat Pump Systems
PERFORMANCE DATA
HTV036 & HTD036 Full Load
ꢀ/6äÎÈÊꢁÕÊꢂ>`
HTV036, HTD036 & HTH036 Full Load
Performance capacities shown in thousands of Btuh.
1200 CFM Rated Airflow
COOLING - EAT 80°F DB / 67°F WB
HEATING - EAT 70°F
WPD
Sens/Tot
Ratio
EWT °F GPM
PSI
FT
TC
SC
KW
HR
EER
HWG
HC
KW
HE
LAT
COP
HWG
Operation Not Recommended
9.0
4.5
6.8
9.0
4.5
6.8
9.0
4.5
6.8
9.0
4.5
6.8
9.0
4.5
6.8
9.0
4.5
6.8
9.0
4.5
6.8
9.0
4.5
6.8
9.0
4.5
6.8
9.0
4.5
6.8
9.0
5.9
1.7
3.3
5.7
1.5
3.2
5.4
1.3
3.1
5.2
1.2
2.9
5.0
1.1
2.9
4.8
1.0
2.8
4.5
13.7
3.9
26.1
28.3
29.6
30.3
32.3
33.8
34.7
36.3
38.1
39.2
40.4
42.6
43.8
44.7
47.2
48.5
49.0
51.9
53.5
53.6
56.8
58.6
2.30
2.34
2.37
2.38
2.43
2.46
2.48
2.52
2.56
2.59
2.62
2.68
2.71
2.74
2.81
2.86
2.87
2.96
3.01
3.02
3.13
3.19
18.2
20.3
21.5
22.2
24.0
25.4
26.2
27.7
29.4
30.3
31.5
33.4
34.5
35.3
37.6
38.8
39.2
41.8
43.2
43.3
46.1
47.7
90.1
91.9
3.32
3.54
3.66
3.73
3.90
4.03
4.10
4.22
4.36
4.43
4.52
4.65
4.73
4.78
4.91
4.98
5.01
5.13
5.20
5.20
5.32
5.38
2.3
2.9
20
30
2.7
3.0
0.6
43.9
44.1
44.3
43.2
43.8
44.0
41.9
42.9
43.3
40.4
41.5
42.0
38.5
39.8
40.4
36.5
37.9
38.6
34.5
35.8
36.5
32.4
33.7
34.4
30.4
31.6
32.3
28.6
29.7
30.2
30.7
30.7
30.7
30.7
30.8
30.9
30.3
30.6
30.7
29.6
30.1
30.3
28.7
29.3
29.6
27.7
28.4
28.7
26.7
27.4
27.7
25.7
26.3
26.7
24.7
25.3
25.6
23.8
24.3
24.6
0.70
0.70
0.69
0.71
0.70
0.70
0.72
0.71
0.71
0.73
0.72
0.72
0.75
0.74
0.73
0.76
0.75
0.75
0.78
0.76
0.76
0.79
0.78
0.78
0.81
0.80
0.79
0.83
0.82
0.81
1.61
1.51
1.45
1.77
1.66
1.60
1.93
1.81
1.75
2.11
1.98
1.92
2.32
2.17
2.10
2.55
2.39
2.31
2.81
2.63
2.55
3.12
2.92
2.82
3.49
3.25
3.14
3.91
3.64
3.51
49.4
49.3
49.2
49.2
49.4
49.4
48.5
49.0
49.2
47.6
48.3
48.6
46.4
47.2
47.6
45.2
46.0
46.5
44.1
44.8
45.2
43.0
43.7
44.0
42.3
42.7
43.0
41.9
42.1
42.2
27.2
29.3
30.4
24.4
26.4
27.5
21.7
23.7
24.7
19.1
20.9
21.9
16.6
18.3
19.2
14.3
15.9
16.7
12.2
13.6
14.3
10.4
11.5
12.2
8.7
-
2.8
3.0
7.6
0-.6
92.9
0.6
-
13.1
3.5
93.4
22..99
33..11
33..30
3.4
33..63
-
94.9
1.1
40
50
7.3
-
96.1
1.1
12.5
3.1
1-.0
1.8
11..72
96.8
98.0
3.7
7.1
99.4
1.5
1.0
3.9
3.1
12.0
2.8
100.2
101.2
102.8
103.8
104.5
106.4
107.4
107.8
110.0
111.3
111.3
113.8
115.2
1.9
2.6
3.6
4.1
60
6.8
2.3
4.2
11.6
2.5
1.4
2.0
3.5
4.4
3.4
4.6
4.7
43..98
70
6.6
3.1
2.7
11.0
2.3
.4
4.1
4.3
5.0
5.2
80
6.5
3..89
3.5
2.3
5.4
10.4
4.2
5.3
5.4
0.9
2.6
4.4
0.8
2.6
4.2
0.8
2.5
4.0
0.7
2.5
3.8
2.1
6.1
10.2
1.9
6.0
9.7
1.8
5.8
9.2
1.6
5.8
8.8
90
43..96
4.5
5.6
5.9
4.6
5.8
5.6
100
110
120
5.4
7.0
Operation Not Recommended
9.7
6.7
6.5
10.3
7.3
8.2
73
7.9
8.2
7.6
8.6
†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB
EAT in cooling and 68°F DB / 59°F WB EAT in heating.
Interpoaltion is permissable, extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating
All performance data is based upon the lower voltage of dual voltage rated units
See performance correction tables for operating conditions other than those listed above.
Operation below 60°F EWT requires optional insulated water circuit.
Operation below 40°F EWT is based upon 15% antifreeze solution.
,EGEND
Ìi\
ꢀ
25<ꢀ /ꢀ JR[fꢀX` ꢀL^KRLꢀONN]#VRW^]N
ꢀÀÊ«iÀ>ÌÊÊÌꢁiÊÃꢁ>`i`Ê>Ài>ÊÜꢁiÊÜ>ÌiÀÊÃÊÕÃi`ÊÊiÕÊvÊ>Ê
>ÌvÀiiâiÊÃÕÌ]ÊÌꢁiÊꢂ7/Ê-ꢂi>Û}Ê7>ÌiÀÊ/i«iÀ>ÌÕÀi®ÊÕÃÌÊ
LiÊV>VÕ>Ìi`°ÊꢀÜÊÕÃÌÊLiÊ>Ì>i`ÊÌÊ>ÊiÛiÊÃÕVꢁÊÌꢁ>ÌÊ
ÌꢁiÊꢂ7/ÊÃÊ>Ì>i`Ê>LÛiÊ{äÂꢀÊÜꢁiÊÌꢁiÊꢃ7ÎÊÕ«iÀÊÃÊÌÊ
V««i`°Ê/ꢁÃÊÃÊ`ÕiÊÌÊÌꢁiÊ«ÌiÌ>ÊvÊÌꢁiÊÀivÀ}iÀ>ÌÊÌi«iÀ>
ÌÕÀiÊLi}Ê>ÃÊÜÊ>ÃÊÎÓÂꢀÊÜÌꢁÊ{äÂꢀÊꢂ7/]ÊÜꢁVꢁÊ>ÞÊi>`ÊÌÊ>Ê
ÕÃ>ViÊVÕÌÕÌÊ`ÕiÊÌÊÌꢁiÊ>VÌÛ>ÌÊvÊÌꢁiÊꢂÜÊ/i«iÀ>ÌÕÀiÊ
*ÀÌiVÌ°Êꢃ7ÎÊÃꢁÕ`ÊiÛiÀÊLiÊV««i`ÊvÀÊÃÞÃÌiÃÊÜÌꢁÕÌÊ
>ÌvÀiiâi°
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
4FCꢀ /ꢀ NW]N[RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀꢁ5
6?<ꢀ /ꢀ `J]N[ꢀfꢀX`ꢀRWꢀDBꢀPJUUXW\#VRW^]N
40Cꢀ /ꢀ NW]N[RWPꢀJR[ꢀ]NVYN[J]^[N ꢀ5JQ[NWQNR]ꢀꢂM[bꢀK^UK#`N]ꢀK^UKꢃ
72ꢀ /ꢀ JR[ꢀQNJ]RWPꢀLJYJLR]b ꢀ<K]^Q
C2ꢀ /ꢀ ]X]JUꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B2ꢀ /ꢀ \NW\RKUNꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
:Fꢀ /ꢀ ]X]JUꢀYX`N[ꢀ^WR]ꢀRWY^] ꢀ:RUXFJ]]\
7Aꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀ[NSNL]RXW ꢀ<K]^Q
ꢀ
74ꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀNa][JL]RXW ꢀ<K]^Q
ꢀ 7F2ꢀ /ꢀ 7X]ꢀFJ]N[ꢀ6NWN[J]X[ꢀꢂMN\^YN[QNJ]N[ꢃꢀLJYJLR]b ꢀ<K]^Q
ꢀꢀꢀF?3ꢀ /ꢀ FJ]N[ꢀLXRUꢀY[N\\^[NꢀM[XYꢀꢂY\RꢀꢄꢀO]ꢀQMꢃ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
44Aꢀ /ꢀ 4WN[Pbꢀ4OeꢀLRNWLbꢀAJ]RXꢀ/ꢀ1CDꢀX^]Y^]#FJ]]ꢀRWY^]
2>?ꢀ /ꢀ 2XNOeꢀLRNW]ꢀXOꢀ?N[OX[VJWLNꢀ/ꢀ1CDꢀX^]Y^]#1CDꢀRWY^]
;FCꢀ /ꢀ UNJ_RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀg5
ꢄ>VÕ>ÌiÊꢂ7/>ÃÊvÜÃ\
ꢆꢅ
Ê
Ê
Ê
ꢂ7/ÊrÊꢅ7/ÊÊ
;0Cꢀ /ꢀ UNJ_RWPꢀJR[ꢀ]NVYN[J]^[N ꢀg5
ꢇ*ꢈÊÝÊxää
;2ꢀ /ꢀ UJ]NW]ꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B#Cꢀ /ꢀ \NW\RKUNꢀ]Xꢀ]X]JUꢀLXXURWPꢀ[J]RX
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Engineering Design Guide
HTV/HTD/HTH SERIES
Heat Controller, Inc.
Two Stage Geothermal Heat Pump Systems
PERFORMANCE DATA
HTV048 & HTD048 Part Load
ꢀ/6ä{nÊ*>ÀÌÊꢁ>`
HTV048 HTD048 & HTH048 Part Load
Performance capacities shown in thousands of Btuh.
1050 CFM Rated Airflow
COOLING - EAT 80°F DB / 67°F WB
HEATING - EAT 70°F
WPD
Sens/Tot
Ratio
EWT °F GPM
PSI
FT
TC
SC
KW
HR
EER
HWG
HC
KW
HE
LAT
COP
HWG
Operation Not Recommended
20
30
11.0
5.5
4.0
1.1
2.2
3.9
1.0
2.1
3.7
0.9
2.1
3.6
0.9
2.0
3.5
0.8
2.0
3.2
0.7
1.9
3.2
9.3
2.5
5.2
8.9
2.3
5.0
8.6
2.1
4.9
8.3
2.0
4.7
8.1
1.8
4.6
7.5
1.7
4.5
7.3
22.7
25.1
26.0
26.5
29.0
30.3
31.0
33.4
34.9
35.8
37.9
39.8
40.8
42.5
44.7
45.8
47.1
49.4
50.6
51.4
53.7
54.9
2.14
2.17
2.18
2.19
2.21
2.23
2.23
2.25
2.27
2.27
2.29
2.31
2.31
2.33
2.35
2.36
2.37
2.40
2.42
2.43
2.47
2.49
15.4
17.7
18.6
19.1
21.5
22.7
23.3
25.7
27.2
28.0
30.1
31.9
32.9
34.6
36.6
37.8
39.0
41.2
42.3
43.1
45.3
46.4
90.0
92.2
3.12
3.39
3.49
3.55
3.84
3.99
4.06
4.34
4.52
4.62
4.85
5.06
5.17
5.35
5.57
5.69
5.81
6.02
6.13
6.20
6.38
6.47
23..23
2.5
3.4
37.9
38.1
38.4
40.1
40.5
40.6
40.1
40.5
40.6
39.3
40.0
40.3
37.6
38.6
39.1
35.3
36.6
37.2
32.8
34.1
34.8
30.3
31.6
32.2
28.0
29.1
29.7
26.2
27.0
27.4
23.6
23.7
23.6
25.8
25.8
25.8
26.4
26.4
26.4
26.7
26.8
26.8
26.1
26.5
26.6
25.3
25.7
26.0
24.3
24.8
25.0
23.3
23.8
24.0
22.6
22.9
23.1
22.3
22.4
22.4
0.62
0.62
0.62
0.64
0.64
0.64
0.66
0.65
0.65
0.68
0.67
0.67
0.70
0.69
0.68
0.71
0.70
0.70
0.74
0.73
0.72
0.77
0.75
0.75
0.81
0.79
0.78
0.85
0.83
0.82
1.19
1.12
1.09
1.35
1.27
1.24
1.48
1.40
1.39
1.71
1.60
1.55
1.92
1.80
1.74
2.15
2.02
1.96
2.41
2.27
2.20
2.70
2.55
2.48
3.03
2.87
2.79
3.41
3.22
3.14
42.0
42.0
42.1
44.8
44.8
44.8
45.2
45.2
45.3
45.2
45.5
45.5
44.1
44.8
45.0
42.7
43.5
43.9
41.1
41.9
42.3
39.6
40.3
40.7
38.4
38.9
39.2
37.8
38.0
38.1
31.9
34.0
35.2
29.7
31.9
32.7
27.2
28.9
29.2
23.0
25.0
26.0
19.6
21.5
22.4
16.4
18.1
19.0
13.6
15.0
15.8
11.2
12.4
13.0
9.3
0.-6
0.-5
2.6
3.3
8.3
93.0
0.5
-
11.0
5.5
93.4
23..63
2.7
-
95.6
1.0
2.8
40
50
8.3
-
96.7
0.9
11.0
5.5
0.-9
1.6
97.3
2..94
99.4
2.8
8.3
0.8
1.5
100.8
101.6
103.4
105.1
106.0
107.5
109.4
110.4
111.5
113.5
114.6
115.3
117.4
118.4
2.9
11.0
5.5
1.3
3.0
3.1
1.6
3.5
60
8.3
3.2
3.3
3.4
11.0
5.5
1.3
2.8
2.2
3.1
3.8
3.5
70
8.3
2.0
2.8
33..68
11.0
5.5
2.5
3.7
2.8
4.0
4.1
3.7
3.8
80
8.3
32..75
3.4
4.0
11.0
5.5
5.5
4.0
4.1
4.3
0.7
1.8
3.1
0.6
1.8
2.9
0.6
1.7
2.9
0.6
1.6
2.7
1.6
4.2
7.2
1.5
4.1
6.8
1.5
4.0
6.6
1.4
3.8
6.3
90
8.3
5.1
11.0
5.5
2.7
4.7
6..5
6.2
100
110
120
8.3
6.0
11.0
5.5
8.3
83..09
Operation Not Recommended
8.3
10.2
10.7
7.7
11.0
5.5
7.7
10.6
10.2
8.3
8.4
9.8
.
11.0
8.8
†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB
EAT in cooling and 68°F DB / 59°F WB EAT in heating.
Interpoaltion is permissable, extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating
All performance data is based upon the lower voltage of dual voltage rated units
See performance correction tables for operating conditions other than those listed above.
Operation below 60°F EWT requires optional insulated water circuit.
Operation below 40°F EWT is based upon 15% antifreeze solution.
,EGEND
Ìi\
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
25<ꢀ /ꢀ JR[fꢀX` ꢀL^KRLꢀONN]#VRW^]N
ꢀÀÊ«iÀ>ÌÊÊÌꢁiÊÃꢁ>`i`Ê>Ài>ÊÜꢁiÊÜ>ÌiÀÊÃÊÕÃi`ÊÊiÕÊvÊ>
>ÌvÀiiâiÊÃÕÌ]ÊÌꢁiÊꢂ7/Ê-ꢂi>Û}Ê7>ÌiÀÊ/i«iÀ>ÌÕÀi®ÊÕÃ
LiÊV>VÕ>Ìi`°ÊꢀÜÊÕÃÌÊLiÊ>Ì>i`ÊÌÊ>ÊiÛiÊÃÕVꢁÊÌꢁ>ÌÊ
ÌꢁiÊꢂ7/ÊÃÊ>Ì>i`Ê>LÛiÊ{äÂꢀÊÜꢁiÊÌꢁiÊꢃ7ÎÊÕ«iÀÊÃÊÌÊ
V««i`°Ê/ꢁÃÊÃÊ`ÕiÊÌÊÌꢁiÊ«ÌiÌ>ÊvÊÌꢁiÊÀivÀ}iÀ>ÌÊÌi«iÀ>
ÌÕÀiÊLi}Ê>ÃÊÜÊ>ÃÊÎÓÂꢀÊÜÌꢁÊ{äÂꢀÊꢂ7/]ÊÜꢁVꢁÊ>ÞÊi>`ÊÌÊ>Ê
ÕÃ>ViÊVÕÌÕÌÊ`ÕiÊÌÊÌꢁiÊ>VÌÛ>ÌÊvÊÌꢁiÊꢂÜÊ/i«iÀ>ÌÕÀiÊ
*ÀÌiVÌ°Êꢃ7ÎÊÃꢁÕ`ÊiÛiÀÊLiÊV««i`ÊvÀÊÃÞÃÌiÃÊÜÌꢁÕÌÊ
>ÌvÀiiâi°
4FCꢀ /ꢀ NW]N[RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀꢁ5
6?<ꢀ /ꢀ `J]N[ꢀfꢀX`ꢀRWꢀDBꢀPJUUXW\#VRW^]N
40Cꢀ /ꢀ NW]N[RWPꢀJR[ꢀ]NVYN[J]^[N ꢀ5JQ[NWQNR]ꢀꢂM[bꢀK^UK#`N]ꢀK^UKꢃ
72ꢀ /ꢀ JR[ꢀQNJ]RWPꢀLJYJLR]b ꢀ<K]^Q
C2ꢀ /ꢀ ]X]JUꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B2ꢀ /ꢀ \NW\RKUNꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
:Fꢀ /ꢀ ]X]JUꢀYX`N[ꢀ^WR]ꢀRWY^] ꢀ:RUXFJ]]\
7Aꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀ[NSNL]RXW ꢀ<K]^Q
ꢀ
74ꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀNa][JL]RXW ꢀ<K]^Q
ꢀ 7F2ꢀ /ꢀ 7X]ꢀFJ]N[ꢀ6NWN[J]X[ꢀꢂMN\^YN[QNJ]N[ꢃꢀLJYJLR]b ꢀ<K]^Q
ꢀꢀꢀF?3ꢀ /ꢀ FJ]N[ꢀLXRUꢀY[N\\^[NꢀM[XYꢀꢂY\RꢀꢄꢀO]ꢀQMꢃ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
44Aꢀ /ꢀ 4WN[Pbꢀ4OeꢀLRNWLbꢀAJ]RXꢀ/ꢀ1CDꢀX^]Y^]#FJ]]ꢀRWY^]
2>?ꢀ /ꢀ 2XNOeꢀLRNW]ꢀXOꢀ?N[OX[VJWLNꢀ/ꢀ1CDꢀX^]Y^]#1CDꢀRWY^]
;FCꢀ /ꢀ UNJ_RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀg5
ꢄ>VÕ>ÌiÊꢂ7/>ÃÊvÜÃ\
ꢆꢅ
Ê
Ê
Ê
ꢂ7/ÊrÊꢅ7/ÊÊ
;0Cꢀ /ꢀ UNJ_RWPꢀJR[ꢀ]NVYN[J]^[N ꢀg5
ꢇ*ꢈÊÝÊxää
;2ꢀ /ꢀ UJ]NW]ꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B#Cꢀ /ꢀ \NW\RKUNꢀ]Xꢀ]X]JUꢀLXXURWPꢀ[J]RX
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Heat Controller, Inc.
HTV/HTD/HTH SERIES
Engineering Design Guide
Two Stage Geothermal Heat Pump Systems
PERFORMANCE DATA
HTV048, HTD048 & HTH048 Full Load
Performance capacities shown in thousands of Btuh.
1600 CFM Rated Airflow
WPD
COOLING - EAT 80°F DB / 67°F WB
HEATING - EAT 70°F
Sens/Tot
Ratio
EWT °F GPM
PSI
FT
TC
SC
KW
HR
EER
HWG
HC
KW
HE
LAT
COP
HWG
Operation Not Recommended
20
30
12.0
6.0
4.8
1.3
2.6
4.5
1.2
2.6
4.4
1.1
2.5
4.2
1.0
2.4
4.0
1.0
2.3
3.8
0.9
2.3
3.6
11.0
2.9
6.1
10.5
2.7
5.9
10.1
2.5
5.7
9.6
2.3
5.5
9.2
2.2
5.4
8.8
2.1
5.2
8.3
2.0
5.0
8.1
1.9
4.8
7.7
1.8
4.7
7.3
1.7
4.5
7.0
32.1
35.3
36.9
37.7
40.6
42.6
43.8
46.3
48.7
50.1
52.1
55.1
56.7
58.1
61.5
63.4
64.3
68.1
70.2
3.09
3.12
3.16
3.19
3.17
3.21
3.23
3.16
3.22
3.26
3.31
3.38
3.42
3.46
3.55
3.61
3.63
3.74
3.81
21.6
24.6
26.1
26.9
29.8
31.7
32.7
35.5
37.7
39.0
40.8
43.5
45.0
46.3
49.4
51.1
51.9
55.3
57.2
88.6
90.4
3.04
3.31
3.41
3.47
3.76
3.89
3.97
4.29
4.43
4.51
4.62
4.77
4.85
4.92
5.08
5.16
5.19
5.33
5.41
23..79
3.3
4.1
57.6
58.1
58.4
57.3
57.9
58.2
56.0
57.1
57.5
53.9
55.5
56.1
51.3
53.2
54.0
48.4
50.4
51.4
45.2
47.3
48.3
42.0
44.0
45.0
38.8
40.7
41.7
35.9
37.6
38.5
37.1
37.2
37.2
38.1
38.2
38.2
38.5
38.6
38.7
37.8
38.3
38.5
36.7
37.5
37.8
35.4
36.3
36.7
34.1
35.0
35.4
32.9
33.7
34.1
31.9
32.5
32.8
31.2
31.6
31.8
0.64
0.64
0.64
0.67
0.66
0.66
0.69
0.68
0.67
0.70
0.69
0.69
0.72
0.70
0.70
0.73
0.72
0.72
0.76
0.74
0.73
0.78
0.77
0.76
0.82
0.80
0.79
0.87
0.84
0.83
2.24
2.12
2.05
2.44
2.31
2.24
2.64
2.50
2.43
2.85
2.70
2.63
3.09
2.92
2.84
3.35
3.17
3.08
3.66
3.45
3.36
4.01
3.78
3.67
4.42
4.16
4.04
4.90
4.61
4.47
65.3
65.3
65.4
65.7
65.8
65.8
65.0
65.7
65.8
63.6
64.7
65.1
61.8
63.1
63.7
59.8
61.2
61.9
57.7
59.0
59.7
55.6
56.9
57.6
53.9
54.9
55.5
52.6
53.3
53.7
25.7
27.5
28.5
23.5
25.1
26.0
21.2
22.9
23.7
18.9
20.5
21.4
16.6
18.2
19.0
14.4
15.9
16.7
12.4
13.7
14.4
10.5
11.6
12.3
8.8
0.-8
0.-7
3.4
4.0
9.0
91.3
0.7
-
12.0
6.0
91.8
34..50
3.8
-
93.5
1.6
3.9
40
50
9.0
-
94.7
1.4
12.0
6.0
1.-3
95.3
4.1
4.1
2.6
96.8
4.4
9.0
1.7
2.3
98.2
4.5
4.7
12.0
6.0
2.1
99.0
4.9
2.9
3.7
100.2
101.9
102.8
103.6
105.6
106.7
107.2
109.4
110.6
60
9.0
32.35
2.9
54..1
5.3
12.0
6.0
4.0
5.0
5.1
5.5
4.5
70
9.0
55..81
12.0
6.0
3.9
6.0
5.0
6.0
5.7
6.1
6.3
80
9.0
54..53
5.1
6.5
12.0
6.0
7.7
0.9
2.2
3.5
0.8
2.1
3.3
0.8
2.0
3.2
0.7
1.9
3.0
90
9.0
7.1
12.0
6.0
4.4
6.6
87.58
8.2
67
100
110
120
9.0
7.9
12.0
6.0
Operation Not Recommended
10.2
98.90
9.0
9.8
12.0
6.0
10.3
7.3
9.5
12.1
11.7
9.0
8.1
12.0
8.6
171..82
†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB
EAT in cooling and 68°F DB / 59°F WB EAT in heating.
Rev: 01/07/07JH
Interpoaltion is permissable, extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating
All performance data is based upon the lower voltage of dual voltage rated units
See performance correction tables for operating conditions other than those listed above.
Operation below 60°F EWT requires optional insulated water circuit.
Operation below 40°F EWT is based upon 15% antifreeze solution.
,EGEND
Ìi\
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
25<ꢀ /ꢀ JR[fꢀX` ꢀL^KRLꢀONN]#VRW^]N
ꢀÀÊ«iÀ>ÌÊÊÌꢁiÊÃꢁ>`i`Ê>Ài>ÊÜꢁiÊÜ>ÌiÀÊÃÊÕÃi`ÊÊiÕÊvÊ>
>ÌvÀiiâiÊÃÕÌ]ÊÌꢁiÊꢂ7/Ê-ꢂi>Û}Ê7>ÌiÀÊ/i«iÀ>ÌÕÀi®ÊÕÃÌÊ
LiÊV>VÕ>Ìi`°ÊꢀÜÊÕÃÌÊLiÊ>Ì>i`ÊÌÊ>ÊiÛiÊÃÕVꢁÊÌꢁ>ÌÊ
ÌꢁiÊꢂ7/ÊÃÊ>Ì>i`Ê>LÛiÊ{äÂꢀÊÜꢁiÊÌꢁiÊꢃ7ÎÊÕ«iÀÊÃÊÌÊ
V««i`°Ê/ꢁÃÊÃÊ`ÕiÊÌÊÌꢁiÊ«ÌiÌ>ÊvÊÌꢁiÊÀivÀ}iÀ>ÌÊÌi«iÀ>
ÌÕÀiÊLi}Ê>ÃÊÜÊ>ÃÊÎÓÂꢀÊÜÌꢁÊ{äÂꢀÊꢂ7/]ÊÜꢁVꢁÊ>ÞÊi>`ÊÌÊ>Ê
ÕÃ>ViÊVÕÌÕÌÊ`ÕiÊÌÊÌꢁiÊ>VÌÛ>ÌÊvÊÌꢁiÊꢂÜÊ/i«iÀ>ÌÕÀiÊ
*ÀÌiVÌ°Êꢃ7ÎÊÃꢁÕ`ÊiÛiÀÊLiÊV««i`ÊvÀÊÃÞÃÌiÃÊÜÌꢁÕÌÊ
>ÌvÀiiâi°
4FCꢀ /ꢀ NW]N[RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀꢁ5
6?<ꢀ /ꢀ `J]N[ꢀfꢀX`ꢀRWꢀDBꢀPJUUXW\#VRW^]N
40Cꢀ /ꢀ NW]N[RWPꢀJR[ꢀ]NVYN[J]^[N ꢀ5JQ[NWQNR]ꢀꢂM[bꢀK^UK#`N]ꢀK^UKꢃ
72ꢀ /ꢀ JR[ꢀQNJ]RWPꢀLJYJLR]b ꢀ<K]^Q
C2ꢀ /ꢀ ]X]JUꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B2ꢀ /ꢀ \NW\RKUNꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
:Fꢀ /ꢀ ]X]JUꢀYX`N[ꢀ^WR]ꢀRWY^] ꢀ:RUXFJ]]\
7Aꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀ[NSNL]RXW ꢀ<K]^Q
ꢀ
74ꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀNa][JL]RXW ꢀ<K]^Q
ꢀ 7F2ꢀ /ꢀ 7X]ꢀFJ]N[ꢀ6NWN[J]X[ꢀꢂMN\^YN[QNJ]N[ꢃꢀLJYJLR]b ꢀ<K]^Q
ꢀꢀꢀF?3ꢀ /ꢀ FJ]N[ꢀLXRUꢀY[N\\^[NꢀM[XYꢀꢂY\RꢀꢄꢀO]ꢀQMꢃ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
44Aꢀ /ꢀ 4WN[Pbꢀ4OeꢀLRNWLbꢀAJ]RXꢀ/ꢀ1CDꢀX^]Y^]#FJ]]ꢀRWY^]
2>?ꢀ /ꢀ 2XNOeꢀLRNW]ꢀXOꢀ?N[OX[VJWLNꢀ/ꢀ1CDꢀX^]Y^]#1CDꢀRWY^]
;FCꢀ /ꢀ UNJ_RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀg5
ꢄ>VÕ>ÌiÊꢂ7/>ÃÊvÜÃ\
ꢆꢅ
Ê
Ê
Ê
ꢂ7/ÊrÊꢅ7/ÊÊ
;0Cꢀ /ꢀ UNJ_RWPꢀJR[ꢀ]NVYN[J]^[N ꢀg5
ꢇ*ꢈÊÝÊxää
;2ꢀ /ꢀ UJ]NW]ꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B#Cꢀ /ꢀ \NW\RKUNꢀ]Xꢀ]X]JUꢀLXXURWPꢀ[J]RX
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Engineering Design Guide
HTV/HTD/HTH SERIES
Heat Controller, Inc.
Two Stage Geothermal Heat Pump Systems
PERFORMANCE DATA
H
ꢀ/6äÈäÊ*>ÀÌÊꢁ>`
HTV060, HTD060 & HTH060 Part Load
Performance capacities shown in thousands of Btuh.
1350 CFM Rated Airflow
COOLING - EAT 80°F DB / 67°F WB
HEATING - EAT 70°F
WPD
Sens/Tot
Ratio
EWT °F GPM
PSI
FT
TC
SC
KW
HR
EER
HWG
HC
KW
HE
LAT
COP
HWG
Operation Not Recommended
2.4
20
30
14.0
7.0
4.1
0.5
1.9
3.9
0.4
1.9
3.7
0.3
1.8
3.5
0.3
1.7
3.4
0.2
1.7
3.2
0.2
1.6
3.1
0.1
1.6
2.9
0.1
1.5
2.8
0.1
1.4
2.7
0.0
1.4
2.6
9.4
1.1
4.4
9.0
0.9
4.3
8.6
0.7
4.1
8.2
0.6
4.0
7.8
0.5
3.9
7.5
0.4
3.8
7.2
0.3
3.6
6.8
0.2
3.5
6.5
0.2
3.3
6.2
0.1
3.2
6.0
28.4
31.3
32.3
32.8
35.7
37.0
37.7
40.4
41.9
42.8
45.2
47.0
47.9
50.0
52.1
53.1
54.8
57.0
58.1
59.5
61.7
62.9
2.44
2.54
2.55
2.55
2.66
2.68
2.69
2.82
2.83
2.84
2.86
2.87
2.88
2.90
2.92
2.93
2.95
2.98
3.00
3.02
3.06
3.09
20.0
22.7
23.6
24.1
26.7
27.9
28.5
30.8
32.3
33.1
35.5
37.2
38.1
40.2
42.1
43.1
44.8
46.8
47.9
49.2
51.3
52.4
89.5
91.5
3.40
3.61
3.71
3.77
3.94
4.05
4.10
4.19
4.34
4.42
4.64
4.80
4.88
5.06
5.23
5.32
5.45
5.61
5.68
5.77
5.91
5.97
3.4
2.6
3.5
0.6
49.1
50.1
51.6
51.9
52.3
52.7
52.0
52.6
52.8
50.2
51.3
51.8
47.5
49.1
49.8
44.5
46.1
46.9
41.2
42.9
43.7
38.1
39.6
40.4
35.5
36.7
37.3
33.7
34.4
34.9
34.5
34.9
35.7
37.1
37.2
37.2
37.9
37.9
37.9
37.1
37.6
37.8
35.8
36.6
36.9
34.3
35.1
35.5
32.8
33.5
33.9
31.5
32.0
32.4
30.7
31.0
31.2
30.3
30.4
30.6
0.70
0.70
0.69
0.71
0.71
0.71
0.73
0.72
0.72
0.74
0.73
0.73
0.75
0.75
0.74
0.77
0.76
0.76
0.79
0.78
0.78
0.82
0.81
0.80
0.86
0.84
0.83
0.90
0.88
0.88
1.56
1.52
1.51
1.71
1.63
1.59
1.91
1.79
1.74
2.15
2.01
1.94
2.44
2.28
2.20
2.78
2.59
2.51
3.16
2.96
2.86
3.59
3.38
3.27
4.08
3.84
3.73
4.63
4.36
4.24
54.4
55.2
56.7
57.8
57.9
58.1
58.5
58.7
58.7
57.5
58.2
58.4
55.9
56.8
57.3
53.9
55.0
55.5
52.0
53.0
53.5
50.4
51.1
51.6
49.4
49.8
50.0
49.5
49.3
49.3
31.4
32.9
34.3
30.4
32.2
33.1
27.3
29.4
30.4
23.3
25.6
26.7
19.5
21.5
22.6
16.0
17.8
18.7
13.0
14.5
15.3
10.6
11.7
12.4
8.7
-
2.7
3.5
0.6
10.5
14.0
7.0
92.2
0.5
-
2.8
3.4
92.5
2.9
3.0
1.-1
94.5
1.0
40
50
10.5
14.0
7.0
95.4
0.9
-
3.1
95.8
1.7
3.0
97.7
3.2
1.6
0.9
10.5
14.0
7.0
98.8
1.4
0.8
3.3
99.3
3.4
.
1.
3.8
101.0
102.2
102.9
104.3
105.7
106.4
107.6
109.1
109.9
110.8
112.3
113.1
3.4
3.5
60
10.5
14.0
7.0
3.6
3.0
3.7
3.4
3.9
3.0
70
10.5
14.0
7.0
2.7
4.0
4.3
4.0
4.1
4.0
80
10.5
14.0
7.0
3.7
2.4
4.3
4.3
5.9
3.5
5.5
3.2
4.4
90
10.5
14.0
7.0
4.6
4.0
5.0
2.9
7.0
6.7
100
110
120
10.5
14.0
7.0
6.5
9.0
8.7
Operation Not Recommended
10.5
14.0
7.0
9.5
8.3
10.0
7.3
11.4
11.0
10.5
14.0
7.9
10.5
8.2
†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB
EAT in cooling and 68°F DB / 59°F WB EAT in heating.
Rev: 01/07/07JH
Interpoaltion is permissable, extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating
All performance data is based upon the lower voltage of dual voltage rated units
See performance correction tables for operating conditions other than those listed above.
Operation below 60°F EWT requires optional insulated water circuit.
Operation below 40°F EWT is based upon 15% antifreeze solution.
,EGEND
Ìi\
ꢀ
25<ꢀ /ꢀ JR[fꢀX` ꢀL^KRLꢀONN]#VRW^]N
ꢀÀÊ«iÀ>ÌÊÊÌꢁiÊÃꢁ>`i`Ê>Ài>ÊÜꢁiÊÜ>ÌiÀÊÃÊÕÃi`ÊÊiÕÊvÊ>Ê
>ÌvÀiiâiÊÃÕÌ]ÊÌꢁiÊꢂ7/Ê-ꢂi>Û}Ê7>ÌiÀÊ/i«iÀ>ÌÕÀi®ÊÕÃÌÊ
LiÊV>VÕ>Ìi`°ÊꢀÜÊÕÃÌÊLiÊ>Ì>i`ÊÌÊ>ÊiÛiÊÃÕVꢁÊÌꢁ>ÌÊ
ÌꢁiÊꢂ7/ÊÃÊ>Ì>i`Ê>LÛiÊ{äÂꢀÊÜꢁiÊÌꢁiÊꢃ7ÎÊÕ«iÀÊÃÊÌÊ
V««i`°Ê/ꢁÃÊÃÊ`ÕiÊÌÊÌꢁiÊ«ÌiÌ>ÊvÊÌꢁiÊÀivÀ}iÀ>ÌÊÌi«iÀ>
ÌÕÀiÊLi}Ê>ÃÊÜÊ>ÃÊÎÓÂꢀÊÜÌꢁÊ{äÂꢀÊꢂ7/]ÊÜꢁVꢁÊ>ÞÊi>`ÊÌÊ>Ê
ÕÃ>ViÊVÕÌÕÌÊ`ÕiÊÌÊÌꢁiÊ>VÌÛ>ÌÊvÊÌꢁiÊꢂÜÊ/i«iÀ>ÌÕÀiÊ
*ÀÌiVÌ°Êꢃ7ÎÊÃꢁÕ`ÊiÛiÀÊLiÊV««i`ÊvÀÊÃÞÃÌiÃÊÜÌꢁÕÌÊ
>ÌvÀiiâi°
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
4FCꢀ /ꢀ NW]N[RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀꢁ5
6?<ꢀ /ꢀ `J]N[ꢀfꢀX`ꢀRWꢀDBꢀPJUUXW\#VRW^]N
40Cꢀ /ꢀ NW]N[RWPꢀJR[ꢀ]NVYN[J]^[N ꢀ5JQ[NWQNR]ꢀꢂM[bꢀK^UK#`N]ꢀK^UKꢃ
72ꢀ /ꢀ JR[ꢀQNJ]RWPꢀLJYJLR]b ꢀ<K]^Q
C2ꢀ /ꢀ ]X]JUꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B2ꢀ /ꢀ \NW\RKUNꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
:Fꢀ /ꢀ ]X]JUꢀYX`N[ꢀ^WR]ꢀRWY^] ꢀ:RUXFJ]]\
7Aꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀ[NSNL]RXW ꢀ<K]^Q
ꢀ
74ꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀNa][JL]RXW ꢀ<K]^Q
ꢀ 7F2ꢀ /ꢀ 7X]ꢀFJ]N[ꢀ6NWN[J]X[ꢀꢂMN\^YN[QNJ]N[ꢃꢀLJYJLR]b ꢀ<K]^Q
ꢀꢀꢀF?3ꢀ /ꢀ FJ]N[ꢀLXRUꢀY[N\\^[NꢀM[XYꢀꢂY\RꢀꢄꢀO]ꢀQMꢃ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
44Aꢀ /ꢀ 4WN[Pbꢀ4OeꢀLRNWLbꢀAJ]RXꢀ/ꢀ1CDꢀX^]Y^]#FJ]]ꢀRWY^]
2>?ꢀ /ꢀ 2XNOeꢀLRNW]ꢀXOꢀ?N[OX[VJWLNꢀ/ꢀ1CDꢀX^]Y^]#1CDꢀRWY^]
;FCꢀ /ꢀ UNJ_RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀg5
ꢄ>VÕ>ÌiÊꢂ7/>ÃÊvÜÃ\
ꢆꢅ
Ê
Ê
Ê
ꢂ7/ÊrÊꢅ7/ÊÊ
;0Cꢀ /ꢀ UNJ_RWPꢀJR[ꢀ]NVYN[J]^[N ꢀg5
ꢇ*ꢈÊÝÊxää
;2ꢀ /ꢀ UJ]NW]ꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B#Cꢀ /ꢀ \NW\RKUNꢀ]Xꢀ]X]JUꢀLXXURWPꢀ[J]RX
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Heat Controller, Inc.
HTV/HTD/HTH SERIES
Engineering Design Guide
Two Stage Geothermal Heat Pump Systems
PERFORMANCE DATA
HTV060, HTD060 & HTH060 Full Load
Performance capacities shown in thousands of Btuh.
2000 CFM Rated Airflow
WPD
COOLING - EAT 80°F DB / 67°F WB
HEATING - EAT 70°F
Sens/Tot
Ratio
EWT °F GPM
PSI
FT
TC
SC
KW
HR
EER
HWG
HC
KW
HE
LAT
COP
HWG
Operation Not Recommended
2.9
20
30
15.0
7.5
5.0
0.6
2.3
4.8
0.5
2.2
4.5
0.4
2.1
4.3
0.3
2.1
4.1
0.3
2.0
3.9
0.2
1.9
3.6
0.2
1.8
3.5
0.1
1.8
3.3
0.1
1.7
3.1
0.0
1.7
2.9
11.6
1.5
5.3
11.0
1.2
5.0
10.4
1.0
4.8
9.9
0.8
4.7
9.4
0.7
4.5
8.9
0.5
4.4
8.4
0.4
4.2
8.0
0.3
4.1
7.6
0.2
4.0
7.2
0.1
3.9
6.8
41.6
45.3
47.1
48.1
51.4
53.6
54.8
57.6
60.2
61.6
64.0
67.0
68.7
70.5
74.1
76.1
77.3
81.5
83.8
84.4
89.2
91.9
3.73
3.83
3.88
3.90
3.99
4.05
4.08
4.15
4.22
4.26
4.33
4.41
4.46
4.51
4.61
4.67
4.71
4.83
4.90
4.92
5.06
5.14
28.9
32.2
33.9
34.8
37.8
39.8
40.9
43.4
45.8
47.1
49.2
52.0
53.5
55.1
58.4
60.1
61.3
65.0
67.1
67.7
72.0
74.4
89.3
91.0
3.27
3.47
3.56
3.61
3.78
3.88
3.94
4.06
4.18
4.24
4.33
4.45
4.52
4.58
4.71
4.78
4.82
4.95
5.02
5.04
5.17
5.24
4.0
3.6
4.1
0.8
68.0
69.0
70.4
69.8
70.7
71.0
70.0
70.7
71.1
68.0
69.5
70.1
65.2
67.2
68.1
61.8
64.2
65.3
58.1
60.6
61.9
54.1
56.7
58.0
50.2
52.7
54.0
46.4
48.7
49.9
49.7
50.3
51.3
51.5
51.8
51.9
52.3
52.4
52.4
51.8
52.2
52.4
50.8
51.5
51.8
49.4
50.4
50.8
47.8
48.9
49.4
46.1
47.2
47.8
44.3
45.4
46.0
42.7
43.7
44.2
0.73
0.73
0.73
0.74
0.73
0.73
0.75
0.74
0.74
0.76
0.75
0.75
0.78
0.77
0.76
0.80
0.78
0.78
0.82
0.81
0.80
0.85
0.83
0.82
0.88
0.86
0.85
0.92
0.90
0.89
2.99
2.86
2.80
3.23
3.07
2.99
3.51
3.31
3.22
3.83
3.60
3.49
4.21
3.94
3.81
4.64
4.34
4.19
5.14
4.80
4.63
5.72
5.34
5.15
6.40
5.96
5.75
7.18
6.68
6.45
78.2
78.7
79.9
80.8
81.2
81.2
82.0
82.0
82.1
81.1
81.8
82.0
79.5
80.7
81.1
77.7
79.0
79.6
75.6
77.0
77.7
73.7
74.9
75.6
72.0
73.0
73.6
70.9
71.5
71.9
22.7
24.2
25.2
21.6
23.0
23.7
19.9
21.3
22.1
17.7
19.3
20.0
15.5
17.1
17.9
13.3
14.8
15.6
11.3
12.6
13.4
9.5
-
3.7
4.1
11.3
15.0
7.5
0.-8
91.8
3.8
0.7
92.3
4.1
4.3
-
93.8
1.7
4.3
4.2
40
50
11.3
15.0
7.5
-
94.8
1.5
1.-4
2.8
95.4
4.4
44..75
96.7
11.3
15.0
7.5
1.9
2.5
97.9
4.9
2.2
1.5
5.1
4.3
98.5
3.9
99.6
4.8
5.4
60
11.3
15.0
7.5
3.5
101.0
101.8
102.7
104.3
105.2
105.8
107.7
108.8
109.1
111.3
112.5
5.6
54..87
6.0
6.3
2.2
3.1
5.4
70
11.3
15.0
7.5
4.8
4.2
6..4
5..9
5.1
6.5
.8
6.6
6.9
.7
80
11.3
15.0
7.5
5.5
7.1
6.7
8.3
7.2
76..54
7..83
90
11.3
15.0
7.5
75..77
4.8
7.0
9.1
8.8
100
110
120
11.3
15.0
7.5
10.6
11.3
7.8
8.5
11.0
Operation Not Recommended
11.3
15.0
7.5
8.8
10.6
10.2
9.4
6.5
113..1
12.6
11.3
15.0
7.3
12.1
7.7
†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB
EAT in cooling and 68°F DB / 59°F WB EAT in heating.
Interpoaltion is permissable, extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating
All performance data is based upon the lower voltage of dual voltage rated units
See performance correction tables for operating conditions other than those listed above.
Operation below 60°F EWT requires optional insulated water circuit.
Operation below 40°F EWT is based upon 15% antifreeze solution.
,EGEND
Ìi\
ꢀ
25<ꢀ /ꢀ JR[fꢀX` ꢀL^KRLꢀONN]#VRW^]N
ꢀÀÊ«iÀ>ÌÊÊÌꢁiÊÃꢁ>`i`Ê>Ài>ÊÜꢁiÊÜ>ÌiÀÊÃÊÕÃi`ÊÊiÕÊvÊ>Ê
>ÌvÀiiâiÊÃÕÌ]ÊÌꢁiÊꢂ7/Ê-ꢂi>Û}Ê7>ÌiÀÊ/i«iÀ>ÌÕÀi®ÊÕÃÌÊ
LiÊV>VÕ>Ìi`°ÊꢀÜÊÕÃÌÊLiÊ>Ì>i`ÊÌÊ>ÊiÛiÊÃÕVꢁÊÌꢁ>ÌÊ
ÌꢁiÊꢂ7/ÊÃÊ>Ì>i`Ê>LÛiÊ{äÂꢀÊÜꢁiÊÌꢁiÊꢃ7ÎÊÕ«iÀÊÃÊÌÊ
V««i`°Ê/ꢁÃÊÃÊ`ÕiÊÌÊÌꢁiÊ«ÌiÌ>ÊvÊÌꢁiÊÀivÀ}iÀ>ÌÊÌi«iÀ>
ÌÕÀiÊLi}Ê>ÃÊÜÊ>ÃÊÎÓÂꢀÊÜÌꢁÊ{äÂꢀÊꢂ7/]ÊÜꢁVꢁÊ>ÞÊi>`ÊÌÊ>Ê
ÕÃ>ViÊVÕÌÕÌÊ`ÕiÊÌÊÌꢁiÊ>VÌÛ>ÌÊvÊÌꢁiÊꢂÜÊ/i«iÀ>ÌÕÀiÊ
*ÀÌiVÌ°Êꢃ7ÎÊÃꢁÕ`ÊiÛiÀÊLiÊV««i`ÊvÀÊÃÞÃÌiÃÊÜÌꢁÕÌÊ
>ÌvÀiiâi°
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
4FCꢀ /ꢀ NW]N[RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀꢁ5
6?<ꢀ /ꢀ `J]N[ꢀfꢀX`ꢀRWꢀDBꢀPJUUXW\#VRW^]N
40Cꢀ /ꢀ NW]N[RWPꢀJR[ꢀ]NVYN[J]^[N ꢀ5JQ[NWQNR]ꢀꢂM[bꢀK^UK#`N]ꢀK^UKꢃ
72ꢀ /ꢀ JR[ꢀQNJ]RWPꢀLJYJLR]b ꢀ<K]^Q
C2ꢀ /ꢀ ]X]JUꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B2ꢀ /ꢀ \NW\RKUNꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
:Fꢀ /ꢀ ]X]JUꢀYX`N[ꢀ^WR]ꢀRWY^] ꢀ:RUXFJ]]\
7Aꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀ[NSNL]RXW ꢀ<K]^Q
ꢀ
74ꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀNa][JL]RXW ꢀ<K]^Q
ꢀ 7F2ꢀ /ꢀ 7X]ꢀFJ]N[ꢀ6NWN[J]X[ꢀꢂMN\^YN[QNJ]N[ꢃꢀLJYJLR]b ꢀ<K]^Q
ꢀꢀꢀF?3ꢀ /ꢀ FJ]N[ꢀLXRUꢀY[N\\^[NꢀM[XYꢀꢂY\RꢀꢄꢀO]ꢀQMꢃ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
44Aꢀ /ꢀ 4WN[Pbꢀ4OeꢀLRNWLbꢀAJ]RXꢀ/ꢀ1CDꢀX^]Y^]#FJ]]ꢀRWY^]
2>?ꢀ /ꢀ 2XNOeꢀLRNW]ꢀXOꢀ?N[OX[VJWLNꢀ/ꢀ1CDꢀX^]Y^]#1CDꢀRWY^]
;FCꢀ /ꢀ UNJ_RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀg5
ꢄ>VÕ>ÌiÊꢂ7/>ÃÊvÜÃ\
ꢆꢅ
Ê
Ê
Ê
ꢂ7/ÊrÊꢅ7/ÊÊ
;0Cꢀ /ꢀ UNJ_RWPꢀJR[ꢀ]NVYN[J]^[N ꢀg5
ꢇ*ꢈÊÝÊxää
;2ꢀ /ꢀ UJ]NW]ꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B#Cꢀ /ꢀ \NW\RKUNꢀ]Xꢀ]X]JUꢀLXXURWPꢀ[J]RX
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Engineering Design Guide
HTV/HTD/HTH SERIES
Heat Controller, Inc.
Two Stage Geothermal Heat Pump Systems
PERfoRmaNcE Data
HTV070, HTD070 & HTH070 Part Load
Performance capacities shown in thousands of Btuh.
1600 CFM Rated Airflow
WPD
COOLING - EAT 80°F DB / 67°F WB
HEATING - EAT 70°F
Sens/Tot
Ratio
EWT °F
GPM
PSI
FT
TC
SC
KW
HR
EER
HWG
HC
KW
HE
LAT
COP
HWG
Operation Not Recommended
20
15.0
7.5
10.1
1.7
3.9
6.9
1.6
3.6
6.5
1.5
3.4
6.0
1.4
3.1
5.4
1.3
3.0
5.4
1.3
2.8
5.0
1.3
2.8
5.0
1.2
2.7
4.8
1.1
2.5
4.5
1.1
2.4
4.3
23.3
3.9
33.0
36.9
38.3
39.0
43.1
45.0
46.1
49.9
52.3
53.7
56.9
59.9
61.6
64.1
67.5
69.3
71.1
74.7
76.6
77.7
81.3
83.1
3.68
3.74
3.77
3.78
3.84
3.87
3.88
3.94
3.97
3.99
4.04
4.09
4.11
4.15
4.21
4.24
4.27
4.34
4.38
4.40
4.48
4.52
20.4
24.1
25.4
26.1
30.0
31.8
32.8
36.4
38.8
40.1
43.2
46.0
47.5
49.9
53.1
54.9
56.5
59.9
61.7
62.7
66.0
67.7
89.1
91.3
2.62
2.89
2.98
3.03
3.29
3.41
3.48
3.71
3.86
3.94
4.13
4.30
4.39
4.52
4.70
4.79
4.88
5.05
5.13
5.18
5.32
5.39
4.1
4.8
4.8
4.8
5.5
5.5
5.5
6.2
6.1
6.1
6.8
8.3
6.8
7.4
7.4
7.4
8.0
8.0
8.0
8.6
8.6
8.5
59.1
60.0
61.0
61.1
61.8
62.5
61.9
62.6
62.9
59.7
61.2
61.8
56.8
58.6
59.5
53.3
55.4
56.4
49.7
51.8
52.8
46.1
48.1
49.1
42.9
44.5
45.5
40.2
41.5
42.3
42.1
42.5
43.1
43.0
43.5
43.8
43.5
43.9
44.0
42.3
43.1
43.4
40.9
41.8
42.2
39.4
40.3
40.7
37.9
38.7
39.1
36.6
37.2
37.6
35.7
36.1
36.3
35.5
35.5
35.6
0.71
0.71
0.71
0.70
0.70
0.70
0.70
0.70
0.70
0.71
0.70
0.70
0.72
0.71
0.71
0.74
0.73
0.72
0.76
0.75
0.74
0.79
0.77
0.77
0.83
0.81
0.80
0.88
0.85
0.84
2.25
2.15
2.10
2.46
2.33
2.27
2.72
2.55
2.48
3.02
2.83
2.74
3.36
3.15
3.05
3.76
3.52
3.41
4.21
3.95
3.82
4.73
4.44
4.29
5.31
4.99
4.83
5.97
5.61
5.44
66.8
67.3
68.1
69.5
69.8
70.2
71.2
71.3
71.4
70.0
70.8
71.1
68.3
69.4
69.9
66.2
67.4
68.0
64.1
65.3
65.9
62.2
63.2
63.7
61.0
61.6
61.9
60.6
60.7
60.8
26.3
27.9
29.0
24.8
26.6
27.5
22.8
24.5
25.4
19.8
21.6
22.6
16.9
18.6
19.5
14.2
15.7
16.6
11.8
13.1
13.8
9.8
-
30
40
11.25
15.0
7.5
9.0
-
92.1
15.9
3.7
-
92.6
-
94.9
11.25
15.0
7.5
8.3
-
96.0
15.0
3.5
-
96.7
2.3
2.1
1.9
2.8
2.5
2.3
3.4
3.1
2.9
4.2
3.8
3.5
5.1
4.7
4.3
6.1
5.7
5.2
7.4
6.8
6.2
8.7
8.1
7.4
98.9
50
11.25
15.0
7.5
7.9
100.3
101.1
103.0
104.7
105.6
107.1
109.1
110.1
111.1
113.2
114.4
115.0
117.1
118.1
13.9
3.2
60
11.25
15.0
7.5
7.2
12.5
3.0
70
11.25
15.0
7.5
6.9
12.5
3.0
80
11.25
15.0
7.5
6.5
11.6
3.0
90
11.25
15.0
7.5
6.5
11.6
2.8
100
110
120
11.25
15.0
7.5
6.2
10.8
11.4
8.1
11.1
2.5
Operation Not Recommended
11.25
15.0
7.5
5.8
8.9
10.4
2.5
9.4
6.7
11.25
15.0
5.5
7.4
9.9
7.8
†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB
EAT in cooling and 68°F DB / 59°F WB EAT in heating.
Interpoaltion is permissable, extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating
All performance data is based upon the lower voltage of dual voltage rated units
See performance correction tables for operating conditions other than those listed above.
Operation below 60°F EWT requires optional insulated water circuit.
Operation below 40°F EWT is based upon 15% antifreeze solution.
,EGEND
Ìi\
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
25<ꢀ /ꢀ JR[fꢀX` ꢀL^KRLꢀONN]#VRW^]N
ꢀÀÊ«iÀ>ÌÊÊÌꢁiÊÃꢁ>`i`Ê>Ài>ÊÜꢁiÊÜ>ÌiÀÊÃÊÕÃi`ÊÊiÕÊvÊ>Ê
>ÌvÀiiâiÊÃÕÌ]ÊÌꢁiÊꢂ7/Ê-ꢂi>Û}Ê7>ÌiÀÊ/i«iÀ>ÌÕÀi®ÊÕÃÌÊ
LiÊV>VÕ>Ìi`°ÊꢀÜÊÕÃÌÊLiÊ>Ì>i`ÊÌÊ>ÊiÛiÊÃÕVꢁÊÌꢁ>ÌÊ
ÌꢁiÊꢂ7/ÊÃÊ>Ì>i`Ê>LÛiÊ{äÂꢀÊÜꢁiÊÌꢁiÊꢃ7ÎÊÕ«iÀÊÃÊÌÊ
V««i`°Ê/ꢁÃÊÃÊ`ÕiÊÌÊÌꢁiÊ«ÌiÌ>ÊvÊÌꢁiÊÀivÀ}iÀ>ÌÊÌi«iÀ>
ÌÕÀiÊLi}Ê>ÃÊÜÊ>ÃÊÎÓÂꢀÊÜÌꢁÊ{äÂꢀÊꢂ7/]ÊÜꢁVꢁÊ>ÞÊi>`ÊÌÊ>Ê
ÕÃ>ViÊVÕÌÕÌÊ`ÕiÊÌÊÌꢁiÊ>VÌÛ>ÌÊvÊÌꢁiÊꢂÜÊ/i«iÀ>ÌÕÀiÊ
*ÀÌiVÌ°Êꢃ7ÎÊÃꢁÕ`ÊiÛiÀÊLiÊV««i`ÊvÀÊÃÞÃÌiÃÊÜÌꢁÕÌÊ
>ÌvÀiiâi°
4FCꢀ /ꢀ NW]N[RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀꢁ5
6?<ꢀ /ꢀ `J]N[ꢀfꢀX`ꢀRWꢀDBꢀPJUUXW\#VRW^]N
40Cꢀ /ꢀ NW]N[RWPꢀJR[ꢀ]NVYN[J]^[N ꢀ5JQ[NWQNR]ꢀꢂM[bꢀK^UK#`N]ꢀK^UKꢃ
72ꢀ /ꢀ JR[ꢀQNJ]RWPꢀLJYJLR]b ꢀ<K]^Q
C2ꢀ /ꢀ ]X]JUꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B2ꢀ /ꢀ \NW\RKUNꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
:Fꢀ /ꢀ ]X]JUꢀYX`N[ꢀ^WR]ꢀRWY^] ꢀ:RUXFJ]]\
7Aꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀ[NSNL]RXW ꢀ<K]^Q
ꢀ
ꢀ
74ꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀNa][JL]RXW ꢀ<K]^Q
7F2ꢀ /ꢀ 7X]ꢀFJ]N[ꢀ6NWN[J]X[ꢀꢂMN\^YN[QNJ]N[ꢃꢀLJYJLR]b ꢀ<K]^Q
ꢀꢀꢀF?3ꢀ /ꢀ FJ]N[ꢀLXRUꢀY[N\\^[NꢀM[XYꢀꢂY\RꢀꢄꢀO]ꢀQMꢃ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
44Aꢀ /ꢀ 4WN[Pbꢀ4OeꢀLRNWLbꢀAJ]RXꢀ/ꢀ1CDꢀX^]Y^]#FJ]]ꢀRWY^]
2>?ꢀ /ꢀ 2XNOeꢀLRNW]ꢀXOꢀ?N[OX[VJWLNꢀ/ꢀ1CDꢀX^]Y^]#1CDꢀRWY^]
;FCꢀ /ꢀ UNJ_RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀg5
ꢄ>VÕ>ÌiÊꢂ7/>ÃÊvÜÃ\
ꢆꢅ
Ê
Ê
Ê
ꢂ7/ÊrÊꢅ7/ÊÊ
;0Cꢀ /ꢀ UNJ_RWPꢀJR[ꢀ]NVYN[J]^[N ꢀg5
ꢇ*ꢈÊÝÊxää
;2ꢀ /ꢀ UJ]NW]ꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B#Cꢀ /ꢀ \NW\RKUNꢀ]Xꢀ]X]JUꢀLXXURWPꢀ[J]RX
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Heat Controller, Inc.
HTV/HTD/HTH SERIES
Engineering Design Guide
Two Stage Geothermal Heat Pump Systems
PERfoRmaNcE Data
HTV070, HTD070 & HTH070 Full Load
Performance capacities shown in thousands of Btuh.
2100 CFM Rated Airflow
WPD
COOLING - EAT 80°F DB / 67°F WB
HEATING - EAT 70°F
Sens/Tot
Ratio
EWT °F
GPM
PSI
FT
TC
SC
KW
HR
EER
HWG
HC
KW
HE
LAT
COP
HWG
Operation Not Recommended
20
17.0
8.5
10.1
2.2
5.0
8.9
2.1
4.7
8.3
1.9
4.3
7.7
1.7
3.9
7.0
1.7
3.9
6.9
1.6
3.6
6.5
1.6
3.6
6.5
1.5
3.4
6.1
1.4
3.3
5.8
1.4
3.1
5.6
23.3
5.1
45.1
49.5
51.6
52.8
57.4
60.3
62.0
66.2
70.0
72.1
75.4
80.1
82.6
84.9
90.1
92.9
94.1
99.6
102.4
102.7
108.0
110.6
4.67
4.74
4.78
4.81
4.90
4.97
5.01
5.11
5.21
5.26
5.35
5.49
5.56
5.63
5.80
5.90
5.94
6.15
6.26
6.27
6.52
6.65
29.2
33.3
35.3
36.4
40.6
43.4
44.9
48.7
52.2
54.2
57.2
61.3
63.6
65.6
70.3
72.8
73.8
78.6
81.0
81.3
85.8
87.9
89.9
91.8
2.8
3.1
3.2
3.2
3.4
3.6
3.6
3.8
3.9
4.0
4.1
4.3
4.4
4.4
4.6
4.6
4.6
4.7
4.8
4.8
4.9
4.9
5.0
5.9
5.9
5.8
6.7
6.7
6.7
7.5
7.5
7.5
8.3
8.3
8.3
9.1
9.0
9.0
9.8
9.8
9.7
10.5
10.4
10.4
74.9
75.4
76.0
79.2
79.7
80.2
80.1
80.8
81.3
78.0
78.9
79.7
72.5
75.0
76.1
68.1
71.2
72.6
63.4
66.5
68.1
58.8
61.7
63.2
55.1
57.3
58.6
52.9
54.0
54.9
49.2
49.6
50.0
51.4
51.8
52.2
51.7
52.5
53.0
50.8
51.4
51.8
50.3
50.7
50.8
49.8
50.2
50.4
48.8
49.5
49.8
47.3
48.3
48.8
45.4
46.6
47.2
43.3
44.6
45.2
0.66
0.66
0.66
0.65
0.65
0.65
0.64
0.65
0.65
0.65
0.65
0.65
0.69
0.68
0.67
0.73
0.71
0.69
0.77
0.74
0.73
0.80
0.78
0.77
0.82
0.81
0.81
0.82
0.83
0.82
3.36
3.23
3.10
3.57
3.45
3.33
4.08
3.93
3.80
4.65
4.45
4.37
5.02
4.75
4.63
5.47
5.15
5.01
6.01
5.65
5.47
6.61
6.21
6.03
7.28
6.86
6.65
8.01
7.55
7.33
86.4
86.4
86.6
91.4
91.5
91.6
94.1
94.2
94.3
93.9
94.1
94.6
89.6
91.2
91.9
86.8
88.7
89.7
83.9
85.8
86.8
81.4
82.9
83.8
79.9
80.7
81.3
80.2
79.8
79.9
22.3
23.4
24.5
22.2
23.1
24.1
19.6
20.6
21.4
16.8
17.7
18.2
14.4
15.8
16.4
12.4
13.8
14.5
10.5
11.8
12.5
8.9
-
30
40
12.8
17.0
8.5
11.6
20.6
4.9
-
92.8
-
93.3
-
95.3
12.8
17.0
8.5
10.9
19.2
4.4
-
96.6
-
97.3
3.7
3.4
3.2
4.5
4.2
3.8
5.5
5.1
4.7
6.8
6.3
5.8
8.3
7.7
7.0
10.1
9.3
8.5
12.0
11.1
10.2
14.3
13.2
12.1
99.2
50
12.8
17.0
8.5
9.9
100.9
101.8
103.3
105.3
106.4
107.4
109.7
111.0
111.5
113.9
115.2
115.3
117.6
118.8
17.8
3.9
60
12.8
17.0
8.5
9.0
16.2
3.9
70
12.8
17.0
8.5
9.0
15.9
3.7
80
12.8
17.0
8.5
8.3
15.0
3.7
90
12.8
17.0
8.5
8.3
15.0
3.5
100
110
120
12.8
17.0
8.5
7.9
9.9
14.1
3.2
10.5
7.6
Operation Not Recommended
12.8
17.0
8.5
7.6
8.4
13.4
3.2
8.8
6.6
12.8
17.0
7.2
7.2
12.9
7.5
†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB
EAT in cooling and 68°F DB / 59°F WB EAT in heating.
Interpoaltion is permissable, extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating
All performance data is based upon the lower voltage of dual voltage rated units
See performance correction tables for operating conditions other than those listed above.
Operation below 60°F EWT requires optional insulated water circuit.
Operation below 40°F EWT is based upon 15% antifreeze solution.
,EGEND
Ìi\
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
25<ꢀ /ꢀ JR[fꢀX` ꢀL^KRLꢀONN]#VRW^]N
ꢀÀÊ«iÀ>ÌÊÊÌꢁiÊÃꢁ>`i`Ê>Ài>ÊÜꢁiÊÜ>ÌiÀÊÃÊÕÃi`ÊÊiÕÊvÊ>Ê
>ÌvÀiiâiÊÃÕÌ]ÊÌꢁiÊꢂ7/Ê-ꢂi>Û}Ê7>ÌiÀÊ/i«iÀ>ÌÕÀi®ÊÕÃÌÊ
LiÊV>VÕ>Ìi`°ÊꢀÜÊÕÃÌÊLiÊ>Ì>i`ÊÌÊ>ÊiÛiÊÃÕVꢁÊÌꢁ>ÌÊ
ÌꢁiÊꢂ7/ÊÃÊ>Ì>i`Ê>LÛiÊ{äÂꢀÊÜꢁiÊÌꢁiÊꢃ7ÎÊÕ«iÀÊÃÊÌÊ
V««i`°Ê/ꢁÃÊÃÊ`ÕiÊÌÊÌꢁiÊ«ÌiÌ>ÊvÊÌꢁiÊÀivÀ}iÀ>ÌÊÌi«iÀ>
ÌÕÀiÊLi}Ê>ÃÊÜÊ>ÃÊÎÓÂꢀÊÜÌꢁÊ{äÂꢀÊꢂ7/]ÊÜꢁVꢁÊ>ÞÊi>`ÊÌÊ>Ê
ÕÃ>ViÊVÕÌÕÌÊ`ÕiÊÌÊÌꢁiÊ>VÌÛ>ÌÊvÊÌꢁiÊꢂÜÊ/i«iÀ>ÌÕÀiÊ
*ÀÌiVÌ°Êꢃ7ÎÊÃꢁÕ`ÊiÛiÀÊLiÊV««i`ÊvÀÊÃÞÃÌiÃÊÜÌꢁÕÌÊ
>ÌvÀiiâi°
4FCꢀ /ꢀ NW]N[RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀꢁ5
6?<ꢀ /ꢀ `J]N[ꢀfꢀX`ꢀRWꢀDBꢀPJUUXW\#VRW^]N
40Cꢀ /ꢀ NW]N[RWPꢀJR[ꢀ]NVYN[J]^[N ꢀ5JQ[NWQNR]ꢀꢂM[bꢀK^UK#`N]ꢀK^UKꢃ
72ꢀ /ꢀ JR[ꢀQNJ]RWPꢀLJYJLR]b ꢀ<K]^Q
C2ꢀ /ꢀ ]X]JUꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B2ꢀ /ꢀ \NW\RKUNꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
:Fꢀ /ꢀ ]X]JUꢀYX`N[ꢀ^WR]ꢀRWY^] ꢀ:RUXFJ]]\
7Aꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀ[NSNL]RXW ꢀ<K]^Q
ꢀ
ꢀ
74ꢀ /ꢀ ]X]JUꢀQNJ]ꢀXOꢀNa][JL]RXW ꢀ<K]^Q
7F2ꢀ /ꢀ 7X]ꢀFJ]N[ꢀ6NWN[J]X[ꢀꢂMN\^YN[QNJ]N[ꢃꢀLJYJLR]b ꢀ<K]^Q
ꢀꢀꢀF?3ꢀ /ꢀ FJ]N[ꢀLXRUꢀY[N\\^[NꢀM[XYꢀꢂY\RꢀꢄꢀO]ꢀQMꢃ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
44Aꢀ /ꢀ 4WN[Pbꢀ4OeꢀLRNWLbꢀAJ]RXꢀ/ꢀ1CDꢀX^]Y^]#FJ]]ꢀRWY^]
2>?ꢀ /ꢀ 2XNOeꢀLRNW]ꢀXOꢀ?N[OX[VJWLNꢀ/ꢀ1CDꢀX^]Y^]#1CDꢀRWY^]
;FCꢀ /ꢀ UNJ_RWPꢀ`J]N[ꢀ]NVYN[J]^[N ꢀg5
ꢄ>VÕ>ÌiÊꢂ7/>ÃÊvÜÃ\
ꢆꢅ
Ê
Ê
Ê
ꢂ7/ÊrÊꢅ7/ÊÊ
;0Cꢀ /ꢀ UNJ_RWPꢀJR[ꢀ]NVYN[J]^[N ꢀg5
ꢇ*ꢈÊÝÊxää
;2ꢀ /ꢀ UJ]NW]ꢀLXXURWPꢀLJYJLR]b ꢀ<K]^Q
B#Cꢀ /ꢀ \NW\RKUNꢀ]Xꢀ]X]JUꢀLXXURWPꢀ[J]RX
Page 15
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Engineering Design Guide
HTV/HTD/HTH SERIES
Heat Controller, Inc.
Two Stage Geothermal Heat Pump Systems
*>ÀÌÊꢀ>`Ê"«iÀ>Ì
ꢉ
Part Load Cooling Corrections 400 CFM per Ton
$,5:ꢀꢁ3.ꢀꢁ(7ꢀꢂ<3;0730,9:ꢃꢀꢄ5;,905.ꢀꢅꢆꢀꢇ
ꢄ5;ꢀꢈ09ꢀ %6;(3ꢀꢁ3.ꢀ
ꢏ,(;ꢀ6-ꢀ
#,1
"6>,9
ꢊꢑꢎꢐꢉ
'ꢆꢀꢇ
ꢁ(7
ꢉꢊ
ꢔ
ꢉꢋ
ꢔ
ꢌꢊ
ꢔ
ꢌꢋ
ꢔ
ꢍꢊ
ꢔ
ꢀꢁꢂꢃ
ꢍꢋ
ꢔ
ꢎꢊ
ꢔ
ꢎꢋ
ꢔ
ꢊꢊ
ꢔ
ꢐꢋ
ꢋꢊ
ꢊꢑꢍꢒꢓ
ꢔ
ꢔ
ꢔ
ꢔ
ꢊꢑꢍꢋꢒ
ä°nx
ä°nÇÈ
ä°n£
£°£Çn £°ÓÓ
ꢔ
ꢔ
ꢔ
ꢔ
ꢔ
ꢔ
ꢔ
ä°ä£
ä°nnÎ
ä°nx
ä°nÓ £°äÓ{
£°£ÓÎ
ꢋꢋ
ꢔ
ꢔ
ꢔ
ꢔ
ꢔ
ꢔ
ꢔ
ꢔ
ꢔ
ꢔ
ꢔ
ä°äÎ
ä°n
ä°£n
ä°ÇÓx
ä°nx
ꢉꢊ
£°änn
ä°Îx
ä°Î
ä°{x
ä°ÈÓÈ
ä°nxÇ
ꢉꢋ
ꢉꢉꢑꢓ
ꢃꢄ
ꢌꢊ
ꢌꢋ
ꢑꢊꢎꢒ
ꢑ ꢓꢊ
ꢔ
ꢔ
ꢔ
ꢔ
ä°Ç
ä°n
ä°nÓ
£°äx
£°äx
ä°{ä
ä°ÇÓn
ꢔ
ꢔ
ꢔ
£°ÓnÎ
ä°£
ä°
ä°Î
£°äÎ
£°äÎ
ä°{În
ꢔ
ꢔ
ꢔ
ä°ÈÇÎ
£°Ó{x
£°äää
£°äää
£°äää
£°äää
£°äää
ꢑꢒꢊꢓ
ꢔ
ꢔ
ꢔ
ä°xxÓ
£°äÇ
£°äÎx
£°ääÎ
£°äÎä
£°ÎÎx
ä°n{Ç
ä°n{Ç
ä°nÎÎ
ꢑꢓꢎꢉ
£°ÎÓ{
£°£äx
£°ään
£°änn
£°änx
ä°xÈÇ
ä°xÈÇ
ꢔꢀꢀ$,5:0)3,ꢀ*(7(*0;@ꢀ,8<(3:ꢀ;6;(3ꢀ*(7(*0;@ꢑ
ꢉ911ꢊꢋ4'*ꢊꢆ+'8/3-ꢊꢇ466+)8/437
Part Load Heating Corrections
ꢍ/6,14:ꢊꢉ911ꢊꢋ4'*
Airflow Part Load
ꢆ+'8/3-
ꢇ441/3-
ꢁꢇꢂꢀ",9ꢀ
%65ꢀ6-ꢀ
6405(3
ꢁ3.
ꢄ5;ꢀꢈ09ꢀ
ꢏ,(;ꢀ6-ꢀ
ꢄ?;
ꢕꢀ6-ꢀ
ꢏ,(;ꢀ6-ꢀ
ꢄ?;
%6;(3
ꢁ(7
$,5:
ꢁ(7
ꢏ,(;ꢀ6-ꢀ
#,1
ꢏ;.ꢀꢁ(7 "6>,9
ꢏ;.ꢀꢁ(7 "6>,9
$ꢖ%
"6>,9
ꢅꢆꢀꢇ
£°££ä
ꢑ
£°£äÇ
£°£äÓ
£°ä{
ä°ÈÇ{
£°ÓäÈ
ꢑ
£°ÓäÓ
£°£Ó
£°£Ç
ꢓꢐꢊ
ꢓꢌꢋ
ꢒꢊꢊ
ꢒꢓꢋ
ꢒꢋꢊ
ꢒꢌꢋ
ꢈꢁꢁ
ꢐꢓꢋ
ꢐꢋꢊ
ꢐꢌꢋ
ꢋꢊꢊ
ꢋꢓꢊ
ꢉꢊꢑꢊ
ꢉꢍꢑꢍ
ꢌꢋꢑꢊ
ꢍ ꢑꢒ
ꢍꢌꢑꢋ
ꢎꢒꢑꢍ
ꢅꢁꢁꢂꢁ
ꢊꢉꢑꢒ
ꢓꢑꢋ
ꢊꢑꢎꢐꢉ
ꢑ ꢋꢒ
£°£ÈÎ
ꢊꢑꢍꢎꢉ
ꢊꢑꢎꢓꢋ
ꢊꢑꢌꢍꢍ
ꢊꢑꢍꢋꢓ
ꢊꢑꢎ ꢒ
ꢊꢑꢎꢓꢓ
ä°ÓÇ
ꢓꢊ
ꢓꢋ
ꢒꢊ
ꢒꢋ
ꢐꢊ
ꢐꢋ
ꢋꢊ
ꢋꢋ
ꢉꢊ
ꢉꢋ
ꢉꢍ
ꢌꢊ
ꢌꢋ
ꢍꢊ
£°Ó{£
ꢑ ꢊꢌ
ä°nn£
ä°Óä
ä°Çn£
ä°n{
ä°x
ä°ÈÇÈ
ä°ÈnÇ
ä°ÇäÈ
ä°Èä
ꢊꢑꢎꢋꢎ
ꢊꢑꢎꢓꢐ
ꢊꢑꢎꢐꢉ
ꢊꢑꢍꢓꢎ
ꢊꢑꢍꢌꢉ
ꢊꢑꢎꢓꢉ
ꢊꢑꢎꢐꢓ
ä°£x
ä°{Ó
ä°nÎÓ
ä°nnÎ
ä°È{
ä°{È
ꢊꢑꢎꢉꢎ
£°ꢑ£ꢊ£ꢌxꢍ
ꢊäꢑ°ꢎÎꢐÇꢓ
äꢊ°ꢎxꢉÈꢊ
äꢊ°ꢑnꢍÈꢉÇ
äꢊ°ꢑꢍäꢎÈꢌ
äꢊ°ꢎÈꢒꢌ
äꢊ°ꢑꢎxꢋꢋ
ä°Çn
ꢊꢑꢎꢌꢌ
ꢑꢊꢋꢒ
ꢊꢑꢎꢋꢎ
ꢊꢑꢎꢌꢓ
ꢊꢑꢍꢎꢋ
ꢊꢑꢎꢓ
ꢊꢑꢎꢋꢊ
ꢊꢑꢎꢉꢍ
£°äÇÈ
ä°xÈ
ä°È
ä°ä£
ä°Ó
ä°Çx
ä°Çä
£°än{
ä°ÇÎÓ
£°£È£
äꢊ°ꢑꢎnꢍÈꢋ
ꢊꢑꢎꢎꢒ
ꢅꢂꢁꢁꢁ
ꢑꢊꢊꢉ
ꢑꢊꢒꢓ
ꢊꢑꢎꢌꢐ
ꢊꢑꢎꢍꢒ
ꢊꢑꢎꢒꢊ
ꢊꢑꢎꢐꢉ
ꢊꢑꢎꢉꢋ
ꢊꢑꢎꢌꢎ
£°ä{Î
ä°ÇÎ
ä°n£
ä°Î{
ä°xÓ
ä°nÓ
ä°n£
£°äÇÎ
ä°ÇÈ{
£°£{ä
ꢑꢊ ꢐ
ꢊꢑꢎꢍꢍ
ꢊꢑꢎꢎꢓ
ꢊꢑꢎꢉꢋ
ꢊꢑꢎꢌꢒ
ꢊꢑꢎꢍꢓ
ꢊꢑꢎꢎꢊ
£°ä£n
ä°nn
ä°£
ä°ÈÇ
ä°ÇÈ
ä°ä
ä°£
£°äÈä
ä°näÓ
£°££Ç
ꢅꢂꢁꢁꢁ
ꢅꢂꢁꢁꢁ
ꢅꢂꢁꢁꢁ
ꢅꢂꢁꢁꢁ
ꢅꢂꢁꢁꢁ
ꢅꢂꢁꢁꢁ
ꢅꢂꢁꢁꢁ
ꢊꢑꢎꢍꢎ
ꢑꢊ
ꢑꢊꢊꢌ
ꢑꢊꢒꢒ
ꢑꢊꢓꢌ
ꢑꢊꢓꢊ
ꢑꢊꢊꢎ
£°ä{È
ä°n{È
£°ää
ä°ä
£°ä£ä
£°ääÇ
£°äÎÎ
£°äÓx
£°ä££
£°ään
ꢑꢊ ꢓ
ꢊꢑꢎꢍꢓ
ꢑꢊ ꢎ
ꢑꢊ ꢓ
ꢑꢊꢉꢐ
ꢑꢊꢋꢓ
ꢑꢊꢐꢓ
ꢑꢊ ꢍ
£°äΣ
ä°nÎ
£°äÈ£
ä°nÈ
£°ä£Ç
£°ä£Î
£°äÈx
£°äx£
£°äÓÎ
£°ä£x
ꢍꢑꢍ
ꢓꢋꢑꢊ
ꢒꢊꢑꢊ
ꢑꢊ ꢍ
ꢊꢑꢎꢌꢎ
ꢑꢊꢓꢌ
ꢑꢊ ꢉ
ꢑꢊꢎꢓ
ꢑꢊꢌꢋ
ꢑꢊꢉꢉ
ꢑꢊꢓꢋ
ä°nÎ
£°äÓ{
£°ä£n
£°än
£°äÇ
£°äÎÈ
£°äÓ£
£°ä£È
ä°{x
£°äΣ
£°ä£Ç
£°ꢑäꢊÓꢓ£ꢓ
ꢊꢑꢎꢌꢌ
ꢑꢊꢒꢒ
ꢑꢊ ꢍ
ꢑ
ꢉ
ꢑꢊꢎꢉ
ꢑꢊꢎ
ꢑꢊꢒꢓ
£°ääÈ
ä°Çn
£°ä£Î
ä°n£
£°äÎä
£°äÓ£
£°£Î£
£°£än
£°äx£
£°äÓÈ
ꢑꢊꢓꢉ
ꢊꢑꢎꢌꢋ
ꢊꢒꢍ
ꢊ ꢎ
ꢑ ꢒꢓ
ꢊ
ꢓ
ꢑꢊꢒꢌ
£°äÓ{
£°äää
£°äää
£°äää
ä°Ç
£°äÎ{
£°äÓÎ
£°£x
£°£ÎÎ
£°äÈÎ
£°äÎä
ä°n{
ä°Èn
£°äxn
£°££Ç
ä°Èn
ä°ÎÈ
ꢁÕÊꢀ>`Ê"«iÀ>Ì
'68ꢉꢊ4'*ꢉꢇ441/3-ꢉꢇ466+)8/437ꢉꢈꢁꢁꢉꢇꢋꢌꢉ5+6ꢉ$43
Full Load Cooling Corrections 400 CFM per Ton
$,5:ꢀꢁ3.ꢀꢁ(7ꢀꢂ<3;0730,9:ꢃꢀꢄ5;,905.ꢀꢅꢆꢀꢇ
ꢄ5;ꢀꢈ09ꢀ %6;(3ꢀꢁ3.ꢀ
ꢐ,(;ꢀ6-ꢀ
#,1
"6>,9
'ꢆꢀꢇ
ꢁ(7
ꢉꢊ
ꢒ
ꢉꢋ
ꢒ
ꢌꢊ
ꢌꢋ
ꢒ
ꢀꢁ
ꢒ
ꢍꢊꢎꢉ
ꢍꢋ
ꢒ
ꢏꢊ
ꢒ
ꢏꢋ
ꢒ
ꢊꢊ
ꢒ
ä°nÎÓ
ꢑꢋ
ꢋꢊ
ꢒ
ꢒ
ꢒ
ꢒ
ꢒ
ꢒ
äꢊ°{ꢍÈ
ä°ꢎnxꢏÎ
£°äÈÈ £°Ó{È
ä°nxä
ꢒ
ꢒ
ꢒ
ꢒ
ꢒ
ꢒ
ä°xÎ
ä°nÇä
£°££
ä°ÇÎÇ ä°xn
ꢋꢋ
ꢒ
ꢒ
ꢒ
ꢒ
ꢒ
ꢒ
ꢒ
ꢒ
ꢒ
ꢒ
ꢒ
ꢒ
ä°nnä
ä°È{
ä°nÈ
ä°nÓ
£°£äÓ
ä°ÈnÈ
ꢉꢊ
ä°ÓÓ
ä°ÇÇ
ä°ÎÓ
ä°È{£
£°äÎ
£°£Óä
ä°nÈn
ä°Çx
ꢉꢋ
ꢒ
ꢒ
ꢒ
ä°Î
ä°Ç
£°ÓÈ£
ä°x{Ç
£°äÎn
£°äÈx
ä°ÇÈÎ
ꢉꢉꢎꢔ
ꢂꢃ
ä°ä
ꢒ
ꢒ
ꢒ
ä°Ç
ä°£
£°ÓÓÎ
ä°xäx
ä°Ç£Ç
£°äää
£°äÓÇ
ꢒ
ꢒ
ꢒ
£°äää
£°äää
£°äää
£°änä
£°ÎäÓ
ꢌꢊ
£°ä{ä
ä°ÈäÎ
ä°nxÇ
ä°nn{
ä°ÈÎÇ
ꢒ
ꢒ
ꢒ
£°ä££
£°äÎx
ä°nÎ{
£°££Ç
£°äÈÓ
ꢌꢋ
ä°È£ä
£°ÓÈ
£°äÎÎ
£°£ä£
ꢒꢀꢀ$,5:0)3,ꢀ*(7(*0;@ꢀ,8<(3:ꢀ;6;(3ꢀ*(7(*0;@ꢎ
'68ꢉꢊ4'*ꢉꢆ+'8/3-ꢉꢇ466+)8/437
Full Load Heating Corrections
ꢍ/6,14:ꢉꢋ911ꢉꢊ4'*
ꢆ+'8/3-
ꢇ441/3-
ꢁꢇꢂꢀ",9ꢀ
%65ꢀ6-ꢀ
6405(3
ꢁ3.
ꢄ5;ꢀꢈ09ꢀ
ꢅꢆꢀꢇ
ꢐ,(;ꢀ6-ꢀ
ꢄ?;
ꢕꢀ6-ꢀ
ꢐ,(;ꢀ6-ꢀ
ꢄ?;
%6;(3
ꢁ(7
$,5:
ꢁ(7
ꢐ,(;ꢀ6-ꢀ
#,1
ꢐ;.ꢀꢁ(7 "6>,9
ꢐ;.ꢀꢁ(7 "6>,9
$ꢖ%
"6>,9
ꢔꢊ
ꢔꢋ
ꢓꢊ
ꢓꢋ
ꢑꢊ
ꢑꢋ
ꢋꢊ
ꢋꢋ
ꢉꢊ
ꢉꢋ
ꢉꢍ
ꢌꢊ
ꢌꢋ
ꢍꢊ
ꢎ
ꢊ
ꢎ
ä°Çä£
ꢔ
£°£Ç
ꢔꢑꢊ
ꢔꢌꢋ
ꢓꢊꢊ
ꢓꢔꢋ
ꢓꢋꢊ
ꢓꢌꢋ
ꢉꢊꢎꢊ
ꢉꢍꢎꢍ
ꢌꢋꢎꢊ
ꢍ ꢎꢓ
ꢍꢌꢎꢋ
ꢏꢓꢎꢍ
ꢊꢎꢏꢑꢉ
ꢎꢔꢑ
ꢊꢎꢍꢍ
ꢊꢎꢏꢔꢊ
ꢊꢎꢌꢍ
ꢊäꢎ°nꢍxꢑÓꢏ
ꢊäꢎ°nꢍÇꢍÈꢓ
ꢊꢎꢏꢋꢏ
ä°ÓÈ
äꢊ°ꢎꢏÓꢔÓꢌ
äꢊ°ꢎꢏ{ꢑÓꢉ
ä°xx
äꢊ°ꢎꢏÈꢌnꢊ
£°än
ä°nÈ
ä°Óx
ä°Çnn
ä°£Î
ꢊꢎꢏꢉꢑ
£°£xÎ
ä°x
ꢊꢎꢏꢉꢊ
ä°Ç£{
£°£ÇÇ
ꢊäꢎ°ꢏꢑ{ꢔÈ
ꢊä°nꢍÓꢓꢔ
£°än{
£°ꢎ£äꢉÇꢓ
£°äÇn
£°ꢎäꢊxꢌÎꢉ
äꢊ°ꢎꢏÓ{ꢋ
ꢊꢎꢏꢉꢏ
ꢊꢎꢏꢓꢌ
ꢊꢎꢏꢋꢉ
ꢊꢎꢍꢉꢌ
ä°nÈ£
ꢊꢎꢏꢊꢉ
ä°nÇ
ä°ÎÇ
ꢊäꢎ°ꢏxꢌäꢋ
ꢊÈꢎxꢏnꢍÓꢔ
£°äÇÓ
ä°ÇΣ
£°£xÇ
ä°Èä
ä°{Ó
ä°ÇÇ
ꢊꢎꢏꢌꢍ
ꢊꢎꢏꢋꢉ
ꢊꢎꢏꢉꢏ
ꢊꢎꢏꢊ
ꢊꢎꢏꢔꢏ
ä°Ó£
£°äÈ£
ä°ÇxÎ
£°£În
ä°ÇÓ
ä°nx
ä°x
ä°nx
ꢊꢎꢏꢍꢉ
ꢎꢊꢑꢓ
ꢊꢎꢏꢍ
ꢊꢎꢏꢓꢑ
ꢊꢎꢏꢋꢔ
ꢊꢎꢏꢍ
ä°nÎ
ä°{È
ä°Ç
£°äxÓ
ä°ÇÇ
£°£Óä
£°äÎÓ
ä°Ç{
ä°Îä
ꢊꢎꢏꢏꢓ
ꢄꢅꢁꢁꢁ
ꢎꢊꢊꢉ
£°ꢎäꢊ£{ꢍ
ꢊꢎꢏꢍꢍ
ꢊꢎꢏꢏ
ꢊꢎꢏꢉꢌ
ꢊꢎꢏꢌꢉ
ꢊꢎꢏꢏꢊ
ꢊꢎꢏꢏ
ä°nn
ä°Èx
ä°nÓ
£°ä{Î
ä°nän
£°£äÓ
ä°Ó
ä°ÇÎ
ä°ä
ꢈꢁꢁ ꢄꢁꢁꢅꢁ
ꢄꢅꢁꢁꢁ
ꢄꢅꢁꢁꢁ
ꢄꢅꢁꢁꢁ
ꢄꢅꢁꢁꢁ
ꢄꢅꢁꢁꢁ
ꢄꢅꢁꢁꢁ
ꢄꢅꢁꢁꢁ
£°äÎx
ä°n{£
£°än{
ꢑꢔꢋ
ꢑꢋꢊ
ꢑꢌꢋ
ꢋꢊꢊ
ꢋꢔꢊ
ꢊꢉꢎꢓ
ꢔꢎꢋ
ꢍꢎꢍ
ꢔꢋꢎꢊ
ꢓꢊꢎꢊ
ꢊꢎꢏꢏꢊ
£°ꢎäꢊ££ꢊ
£ꢎ°ꢊäꢊäꢌÇ
ꢎꢊꢓꢓ
ꢎꢊꢔꢋ
ꢎꢊ
ꢎꢊꢊꢍ
£°ää
ä°n
£°äÎÎ
£°äÓÇ
£°äÓä
£°äÓÇ
ä°nÇÇ
£°äÈx
ꢎꢊ ꢔ
äꢊ°ꢎꢏnꢍÓꢉ
ꢎꢊ ꢌ
ꢎꢊ ꢓ
£°ꢎäꢊÈꢉ{ꢋ
ꢎꢊꢋ
£°äxÓ
ꢎꢊꢔꢓ
ꢎꢊ ꢋ
£°ä£Ó
ꢎꢊ ꢍ
£°ä{Ó
£°ä£n
£°ä£
ä°£x
£°ä{x
£°ä£
£°ä£n
ꢎꢊ ꢌ
ꢊꢎꢏꢍꢓ
£°ꢎäꢊÓꢔÇꢑ
ꢎꢊꢏꢍ
ꢎꢊꢌꢏ
£°äÇx
£°ꢎäꢊÈꢓÈꢉ
£°ꢎäꢊÓꢔx
ä°Ç
£°ä£È
£°äÓ
£°ä£ä
ä°xÇ
£°äÓÎ
£°äÓÓ
ꢎꢊꢔ
ꢊꢎꢏꢍ
£°ꢎäꢊÎꢓÎꢊ
ꢎꢊꢔ
ꢓ
ꢊꢍ
ꢎꢊꢋ
£°ꢎäꢊÎꢔÓꢉ
ä°ÇÇ
£°ä£n
ꢎꢊꢔꢓ
£°££È
£°äÈ
£°ä£
£°ää{
ä°nÓ
£°ä£ä
£°äÓÈ
ꢎꢊꢔꢑ
ꢊꢎꢏꢌꢏ
ꢎꢊꢓꢑ
ꢎ ꢋꢏ
ꢎ ꢓꢓ
ꢎꢊꢉꢓ
ꢎꢊꢓꢊ
£°ä£
ä°Çx
£°äÎn
£°£ÎÓ
£°££ä
£°££Ó
£°äÎÇ
£°äää
£°äää
£°äää
ä°n
£°ä{x
ä°Ç{
ä°{È
ä°ÇÈ
£°äÎ
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Heat Controller, Inc.
HTV/HTD/HTH SERIES
Engineering Design Guide
Two Stage Geothermal Heat Pump Systems
Blower Performance Data
Residential
Airflow in CFM with wet coil and clean air filter
Units Only
Max
ESP
(in. wg)
Fan
Motor
(hp)
Cooling Mode
Stg 1 Stg 2 Fan
Dehumid Mode
Stg 1 Stg 2 Fan
Heating Mode
Stg 1 Stg 2 Fan
Aux/
Emerg
Mode
Tap
Setting
AUX
CFM
Model
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
810
725
950
850
475
425
370
300
700
630
540
450
870
780
670
560
1020
920
790
660
1050
980
910
850
630
560
490
740
660
570
475
425
370
920
825
1060
950
475
425
370
300
700
630
540
450
870
780
670
560
1020
920
790
660
1050
980
910
850
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
1060
950
024
620
730
710
820
820
520
610
600
690
690
1120
1000
860
1400
1250
1080
900
870
780
670
1090
980
700
630
540
1120
1000
860
1400
1250
1080
900
1400
1350
1350
1350
1850
1660
1430
1350
2280
2040
1750
1470
2230
2100
1870
1670
036
840
730
730
1460
1300
1120
940
1730
1550
1330
1120
2050
1825
1580
1320
2190
1950
1830
1700
1140
1020
870
1350
1210
1040
870
780
670
1560
1400
1200
1010
1860
1650
1430
1200
1690
1600
1400
1240
1850
1650
1430
1200
2280
2050
1750
1470
2230
2100
1850
1620
1
048
1
1
1
1670
1500
1280
1080
1620
1500
1400
1320
1300
1160
1000
1600
1430
1230
1020
920
1
060
1
790
1
1
1270
1170
1100
1650
1520
1420
1050
980
1
070
1
910
1
Factory shipped on Tap Setting 2
During Auxiliary operation (residential units only) the CFM will run at the higher if the heating (delay jumper) or AUX settings
Airflow is controlled within +/- 5% up to Max ESP shown with wet coil and standard 1” fiberglass filter
Do not select Dehumidification mode if HP CFM is on setting 1
All units ARI/ISO/ASHRAE 13256-1 rated HP (Cooling) Delay (Heating) CFM Setting 3
ECM Control Features
ꢀ$ꢃꢌ9,;/ꢃN,:ꢃ(0==482<
ꢀ996482ꢀ\N]]RWP\.ꢀꢀ ꢀ]
"0,=482ꢀ\N]]RWP\.ꢀꢀꢀ
ꢁ>Aꢂ 70;2ꢃ"0,= ꢀ\N]]RWP\.ꢀ
ꢈKMꢃ(@4=.3
ꢈKMꢃ(@4=.3
ꢈKMꢃ(@4=.3
N,:
N,:
N,:
(+G
(+ꢄ
>=
(+ꢅ
(+ꢆ
>=
(+H
(+ꢇ
>=
(0==482
(0==482
(0==482
>=
>=
>=
>=
>=
>=
%
&
'
(
%
%
&
'
(
>55
>=
>55
>=
>55
>=
&
>55
>55
>55
>55
>55
>55
'
>55
>55
>55
(
W
ꢃ.9
ꢀ!$ꢃꢁ/P><=ꢀ\N]]RWP\.ꢀꢀCC ꢀCB ꢀ6Bꢀ^WR]\
ꢈ03>7ꢃ$9/0ꢀ\N]]RWP\.ꢀꢀCC ꢀCB ꢀ6Bꢀ^WR]\
ꢂꢀꢁÊꢃÌiÀv>ViÊꢄ>ÞÕÌ
ꢈKMꢃ(@4=.3
ꢈKMꢃ(@4=.3
(+ꢋ
£É{»Ê-«>`i
GꢆE(:,/0
ꢀiVÌÃ
N,:
N,:
ÌÊꢀ8ꢁÊ >À`
N30;79<=,=
K8:>=ꢃ# ꢈ<
(+I
(+ꢉ
>=
(0==482
(0==482
6
6
6
6
A
>=
>=
=>A<
>=
C4BC
>55
>=
3NQ^VRM
>55
ꢊ
F
>55
>55
>55
ꢀ!$ꢃꢀ9>8=0;
=>A<
N30;79<=,=
Gꢃ16,<3ꢃ:0;ꢃGꢍꢍꢃꢀ!$
ꢀ9880.=498<
j
ꢀ$ꢃ$9=9;
#9@ꢃ*96=,20
ꢀ9880.=9;
6
ꢈ03>74/414.,=498
# ꢈ
!,8ꢃ(:00/ꢃ(060.=498ꢃꢈKMꢃ(@4=.3
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Engineering Design Guide
HTV/HTD/HTH SERIES
Heat Controller, Inc.
Two Stage Geothermal Heat Pump Systems
ꢁ ꢀ'ꢁꢀEDJHEBꢁ!;7JKH;I
CQNꢀ42<ꢀOJWꢀR\ꢀLXW][XUUNMꢀKbꢀJWꢀRW]N[OJLNꢀKXJ[Mꢀ]QJ]ꢀ
LXW_N[]\ꢀ]QN[VX\]J]ꢀRWY^]\ꢀJWMꢀeꢀNUMꢀ\NUNL]JKUNꢀ25<ꢀ
\N]]RWP\ꢀ]Xꢀ\RPWJU\ꢀ^\NMꢀKbꢀ]QNꢀ42<ꢀVX]X[ꢀLXW][XUUN["ꢀ
ꢁ!$ꢀꢂ/P><=ꢀ\N]]RWP\.ꢀCQNꢀ25<ꢀJMS^\]ꢀ\N]]RWPꢀJUUX`\ꢀ
OX^[ꢀ\NUNL]RXW\"ꢀCQNꢀ=>A<ꢀ\N]]RWPꢀR\ꢀ]QNꢀOJL]X[bꢀMNOJ^U]ꢀ
YX\R]RXW"ꢀCQNꢀꢃꢀX[ꢀmꢀ\N]]RWP\ꢀJMS^\]ꢀ]QNꢀJR[fꢀX`ꢀKbꢀꢃ#!ꢀ%)h"ꢀ
CQNꢀꢃ#!ꢀ\N]]RWP\ꢀJ[Nꢀ^\NMꢀ]XꢀleꢀWNꢀ]^WNdꢀJR[fꢀX`ꢀJMS^\]VNW]\"ꢀ
CQNꢀC4BCꢀ\N]]RWPꢀ[^W\ꢀ]QNꢀ42<ꢀVX]X[ꢀJ]ꢀ+$hꢀ]X[Z^N ꢀ
`QRLQꢀLJ^\N\ꢀ]QNꢀVX]X[ꢀ]XꢀXYN[J]NꢀURTNꢀJꢀ\]JWMJ[Mꢀ?B2ꢀ
VX]X[ ꢀJWMꢀMR\JKUN\ꢀ]QNꢀ25<ꢀLX^W]N["
5JWꢀ\YNNM\ꢀJ[Nꢀ\NUNL]NMꢀ
`R]QꢀS^VYN[\ꢀ_RJꢀJꢀWRWNꢀYX\R]RXWꢀ38?ꢀ\`R]LQꢀ
CXꢀ]JTNꢀO^UUꢀJM_JW]JPNꢀXOꢀ]QNꢀ42<ꢀVX]X[ꢀ
ONJ]^[N\ ꢀJꢀV^U]R!\]JPNꢀ]QN[VX\]J]ꢀ\QX^UMꢀKNꢀ^\NMꢀꢁ&!\]JPNꢀ
vi>ÌÕÀiÃ]Ê>ÊÕÌÃÌ>}iÊÌꢀiÀÃÌ>ÌÊÃÕVꢀÊ>ÃÊÇnääÓä£ÊÃꢀÕ`Ê
LiÊÕÃi`Ê-ÓÃÌ>}iÊꢀi>ÌÉÓÃÌ>}iÊVÊÀÊÎÃÌ>}iÊꢀi>ÌÉÓÃÌ>}iÊ
ꢄ03>74/4Qꢀ.,=498ꢀ$9/0ꢀ\N]]RWP\.ꢀCQNꢀMNQ^VRMReꢀLJ]RXWꢀ
VXMNꢀ\N]]RWPꢀY[X_RMN\ꢀeꢀNUMꢀ\NUNL]RXWꢀXOꢀQ^VRMR]bꢀLXW][XU"ꢀ
FQNWꢀXYN[J]RWPꢀRWꢀ]QNꢀWX[VJUꢀVXMN ꢀ]QNꢀLXXURWPꢀJR[fꢀX`ꢀ
\N]]RWP\ꢀJ[NꢀMN]N[VRWNMꢀKbꢀ]QNꢀLXXURWPꢀ]JYꢀ\N]]RWPꢀJKX_N"ꢀ
FQNWꢀMNQ^VRMReꢀLJ]RXWꢀR\ꢀNWJKUNMꢀ]QN[NꢀR\ꢀJꢀ[NM^L]RXWꢀRWꢀ
JR[fꢀX`ꢀRWꢀLXXURWPꢀ]XꢀRWL[NJ\Nꢀ]QNꢀVXR\]^[Nꢀ[NVX_JUꢀXOꢀ]QNꢀ
V®°
%9=0Jꢀ?X`N[ꢀV^\]ꢀKNꢀXOOꢀ]Xꢀ]QNꢀ^WR]ꢀOX[ꢀJ]ꢀUNJ\]ꢀ]Q[NNꢀ
\NLXWM\ꢀKNOX[Nꢀ]QNꢀ42<ꢀVX]X[ꢀ`RUUꢀ[NLXPWRcNꢀJꢀ\YNNMꢀ
LQJWPN"ꢀCQNꢀVX]X[ꢀ`RUUꢀ[NLXPWRcNꢀJꢀLQJWPNꢀRWꢀ]QNꢀ25<ꢀ
0MS^\]ꢀX[ꢀMNQ^VRMReꢀLJ]RXWꢀVXMNꢀ\N]]RWP\ꢀ`QRUNꢀ]QNꢀ^WR]ꢀ
R\ꢀYX`N[NM"
ꢀi>ÌÊ«Õ«°ÊꢁÃÕÌÊ>ÀyÜÊëiVwV>ÌÃÊvÀÊÌꢀiÊëiVwVÊÕÌÊ
QNJ]ꢀY^VY"ꢀ2XW\^U]ꢀ\^KVR]]JUꢀMJ]JꢀX[ꢀ\YNLReꢀLJ]RXW\ꢀLJ]JUXPꢀ
`iÊÌÊVÀÀi>ÌiÊëii`ÊÌ>«ÊÃiÌÌ}ÊÌÊ>ÀyÜÊÊꢁꢂꢃ°Ê/ꢀiÊ
CQN[NꢀJ[NꢀOX^[ꢀMROON[NW]ꢀJR[fꢀX`ꢀ\N]]RWP\ꢀO[XVꢀUX`N\]ꢀJR[fꢀX`ꢀ `iꢀÕ`wV>ÌÊ`iÊV>ÊLiÊi>Li`ÊÊÌÜÊÜ>Þð
[J]Nꢀꢁ\YNNMꢀ]JYꢀ%ꢂꢀ]Xꢀ]QNꢀQRPQN\]ꢀJR[fꢀX`ꢀ[J]Nꢀꢁ\YNNMꢀ]JYꢀ(ꢂ"ꢀ
CQNꢀLQJ[]\ꢀKNUX`ꢀRWMRLJ]Nꢀ\N]]RWP\ꢀOX[ꢀKX]Qꢀ_N[\RXW\ꢀXOꢀ]QNꢀ
42<ꢀRW]N[OJLNꢀKXJ[M ꢀOXUUX`NMꢀKbꢀMN]JRUNMꢀRWOX[VJ]RXWꢀOX[ꢀ
NJLQꢀ\N]]RWP"
%"ꢀꢀ 2XW\]JW]ꢀ3NQ^VRMReꢀLJ]RXWꢀ<XMN.ꢀFQNWꢀ]QNꢀ
MNQ^VRMReꢀLJ]RXWꢀVXMNꢀR\ꢀ\NUNL]NMꢀꢁ_RJꢀ38?ꢀ\`R]LQꢀX[ꢀ
S^VYN[ꢀ\N]]RWPꢂ ꢀ]QNꢀ42<ꢀVX]X[ꢀ`RUUꢀXYN[J]Nꢀ`R]QꢀJꢀ
V^U]RYURN[ꢀJYYURNMꢀ]Xꢀ]QNꢀLXXURWPꢀ25<ꢀ\N]]RWP\ꢀꢁJYY[Xa"ꢀ
&$!&)hꢀUX`N[ꢀJR[fꢀX`ꢂ"ꢀ0Wbꢀ]RVNꢀ]QNꢀ^WR]ꢀR\ꢀ[^WWRWPꢀRWꢀ
]QNꢀLXXURWPꢀVXMN ꢀR]ꢀ`RUUꢀXYN[J]NꢀJ]ꢀ]QNꢀUX`N[ꢀJR[fꢀX`ꢀ
]XꢀRVY[X_NꢀUJ]NW]ꢀLJYJLR]b"ꢀCQNꢀl347D<dꢀ;43ꢀ`RUUꢀKNꢀ
RUU^VRWJ]NMꢀJ]ꢀJUUꢀ]RVN\"ꢀ7NJ]RWPꢀJR[fꢀX`ꢀR\ꢀWX]ꢀJOONL]NM"ꢀ
=>C4.ꢀ3XꢀWX]ꢀ\NUNL]ꢀMNQ^VRMReꢀLJ]RXWꢀVXMNꢀROꢀLXXURWPꢀ
\N]]RWPꢀR\ꢀ]JYꢀ%"
ꢁ996482ꢀ\N]]RWP\.ꢀCQNꢀLXXURWPꢀ\N]]RWPꢀMN]N[VRWN\ꢀ]QNꢀ
LXXURWPꢀꢁWX[VJUꢂꢀ25<ꢀOX[ꢀJUUꢀ^WR]\ꢀ`R]Qꢀ42<ꢀVX]X["ꢀ
2XXURWPꢀꢁWX[VJUꢂꢀ\N]]RWPꢀR\ꢀ^\NMꢀ`QNWꢀ]QNꢀ^WR]ꢀR\ꢀWX]ꢀRWꢀ
MNQ^VRMReꢀLJ]RXWꢀVXMN"ꢀ
CJYꢀ%ꢀR\ꢀ]QNꢀUX`N\]ꢀ25<ꢀ\N]]RWP ꢀ`QRUNꢀ]JYꢀ(ꢀR\ꢀ]QNꢀQRPQN\]ꢀ
ꢁꢂꢃÊÃiÌÌ}°Ê/Ê>Û`Ê>ÀÊVÊvÀiiâiÕ«]ÊÌ>«Ê£Ê>ÞÊÌÊLiÊ
25<ꢀ\N]]RWP"ꢀCXꢀ
&"ꢀꢀ 0^]XVJ]RLꢀꢁ7^VRMR\]J]!LXW][XUUNMꢂꢀ3NQ^VRMReꢀLJ]RXWꢀ
<XMN.ꢀFQNWꢀ]QNꢀMNQ^VRMReꢀLJ]RXWꢀVXMNꢀR\ꢀ\NUNL]NMꢀ
ꢁ_RJꢀ38?ꢀ\`R]LQꢀX[ꢀS^VYN[ꢀ\N]]RWPꢂꢀ0=3ꢀJꢀQ^VRMR\]J]ꢀR\ꢀ
LXWWNL]NMꢀ]Xꢀ]N[VRWJUꢀ37ꢃ
ÕÃi`ÊvÊÌꢀiÊ`iꢀÕ`wV>ÌÊ`iÊÃÊÃiiVÌi`°ÊꢁÃÕÌÊ>ÀyÜÊ
ëiVwV>ÌÃÊvÀÊÌꢀiÊëiVwVÊÕÌÊ`iÊÌÊVÀÀi>ÌiÊëii`Ê
Ì>«ÊÃiÌÌ}ÊÌÊ>ÀyÜÊÊꢁꢂꢃ°
]QNꢀLXXURWPꢀJR[fꢀX`ꢀ`RUUꢀXWUbꢀKNꢀ[NM^LNMꢀ`QNWꢀ]QNꢀ
Q^VRMR\]J]ꢀ\NW\N\ꢀ]QJ]ꢀJMMR]RXWJUꢀMNQ^VRMReꢀLJ]RXWꢀR\ꢀ
[NZ^R[NM"ꢀCQNꢀ37ꢀ]N[VRWJUꢀR\ꢀ[N_N[\NꢀUXPRL"ꢀ
"0,=482ꢀ\N]]RWP\.ꢀCQNꢀQNJ]RWPꢀ\N]]RWPꢀMN]N[VRWN\ꢀ]QNꢀ
QNJ]RWPꢀ25<ꢀOX[ꢀꢀ
CQN[NOX[N ꢀJꢀQ^VRMR\]J]ꢀꢁWX]ꢀMNQ^VRMR\]J]ꢂꢀR\ꢀ[NZ^R[NM"ꢀ
CQNꢀl347D<dꢀ;43ꢀ`RUUꢀKNꢀRUU^VRWJ]NMꢀXWUbꢀ`QNWꢀ
]QNꢀQ^VRMR\]J]ꢀR\ꢀLJUURWPꢀOX[ꢀMNQ^VRMReꢀLJ]RXWꢀVXMN"ꢀ
7NJ]RWPꢀJR[fꢀX`ꢀR\ꢀWX]ꢀJOONL]NM"ꢀ=>C4.ꢀ3XꢀWX]ꢀ\NUNL]ꢀ
MNQ^VRMReꢀLJ]RXWꢀVXMNꢀROꢀLXXURWPꢀ\N]]RWPꢀR\ꢀ]JYꢀ%"
.
ꢀ
/>«Ê£ÊÃÊÌꢀiÊÜiÃÌÊꢁꢂꢃÊÃiÌÌ}]ÊÜꢀiÊÌ>«Ê{ÊÃÊÌꢀiÊꢀ}ꢀiÃÌÊ
CJYꢀ%ꢀR\ꢀ]QNꢀUX`N\]ꢀ25<ꢀ\N]]RWP ꢀ`QRUNꢀ]JYꢀ(ꢀR\ꢀ]QNꢀQRPQN\]ꢀ
ꢁꢂꢃÊÃiÌÌ}°ÊꢁÃÕÌÊ>ÀyÜÊëiVwV>ÌÃÊvÀÊÌꢀiÊëiVwVÊÕÌÊ
`iÊÌÊVÀÀi>ÌiÊëii`ÊÌ>«ÊÃiÌÌ}ÊÌÊ>ÀyÜÊÊꢁꢂꢃ°
ꢂ>A464,;Bꢃ 70;208.Bꢀ"0,=ꢀ\N]]RWP\.ꢀCQNꢀJ^aRURJ[b#
NVN[PNWLbꢀQNJ]ꢀ\N]]RWPꢀMN]N[VRWN\ꢀ]QNꢀ25<ꢀ`QNWꢀ]QNꢀ^WR]ꢀ
R\ꢀRWꢀJ^aRURJ[bꢀQNJ]ꢀX[ꢀNVN[PNWLbꢀQNJ]ꢀVXMN"ꢀCQR\ꢀ\N]]RWPꢀ
R\ꢀ^\NMꢀOX[ꢀ[N\RMNW]RJUꢀ^WR]\ꢀ`R]QꢀRW]N[WJUꢀNUNL][RLꢀQNJ]"ꢀ
FQNWꢀJ^aRURJ[bꢀNUNL][RLꢀQNJ]ꢀR\ꢀNWN[PRcNMꢀꢁR"N"ꢀLXVY[N\\X[ꢀ
JWMꢀNUNL][RLꢀQNJ]ꢂ ꢀ]QNꢀP[NJ]N[ꢀXOꢀ]QNꢀJ^aRURJ[b#NVN[PNWLbꢀ
X[ꢀQNJ]RWPꢀ\N]]RWPꢀ`RUUꢀKNꢀ^\NM"ꢀ0ꢀl6dꢀꢁOJWꢂꢀ\RPWJUꢀV^\]ꢀKNꢀ
Y[N\NW]ꢀO[XVꢀ]QNꢀ]QN[VX\]J]ꢀOX[ꢀNUNL][RLꢀQNJ]ꢀ]XꢀXYN[J]N"ꢀ
ꢁ2XWÃ\Õ^UÌ]Êꢀ>]QÀyNꢀ\Ü^ÊKëViRV]]JwVUꢀ>MÌJ]JꢀÃXÊv[ꢀ\ÀÊYÌꢀNiLÊRÃeꢀ«LiJV]RXwWVÊ\ÕꢀLJÌÊ]JUX`PiꢀOXÊÌ[ꢀÊ
VÀÀi>ÌiÊëii`ÊÌ>«ÊÃiÌÌ}ÊÌÊ>ÀyÜÊÊꢁꢂꢃ°
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Heat Controller, Inc.
HTV/HTD/HTH SERIES
Engineering Design Guide
Two Stage Geothermal Heat Pump Systems
Auxiliary Electric Heat
Auxiliary Heat Ratings
HT
kW Rating
Btuh Rating
Minimum
CFM
Required
Auxiliary Electric
Heat Model
024
036
048 060
070
230V
208V
230V
208V
HGM5A
4.8
7.6
3.6
5.7
16300
25900
32700
38900
32700
49100
65500
12300
19400
24600
29200
24600
36900
49200
500
650
HGM8A
HGM10A
9.6
7.2
650
HGM12A
11.4
9.6
8.6
750
HGL10A
7.2
1300
1350
1350
HGL15A
14.4
19.2
10.8
14.4
HGL20A
Grey area denotes compatibility
Note: Vertical units rated for zero clearance for both unit and duct.
Auxiliary Heat Electrical Data
Minimum
Circuit Amps
Heater Amps
Maximum Fuse
Supply Wire
Min
Auxiliary Electric
Heat Model
Supply
Circuit
230V
208V
230V
25.0
208V
230V
25
208V
Max Ft
AWG
HGM5A
Single
Single
Single
Single
20.0
31.7
40.0
47.5
17.3
27.5
34.7
41.2
21.6
34.4
43.4
51.5
25
35
45
60
10
70
70
90
70
HGM8A
39.6
50.0
59.4
40
50
60
8
6
6
HGM10A
HGM12A
Dual - L1/L2
Dual - L3/L4
31.7
15.8
27.5
13.7
39.6
19.8
34.4
17.1
40
20
35
20
8
12
70
50
HGL10A
Single
Single
40.0
60.0
34.7
52.0
50.0
75.0
50.0
43.4
65.0
50
80
45
70
6
6
80
50
HGL15A
Dual - L1/L2
Dual - L3/L4
40.0
20.0
34.7
17.3
43.4
21.6
50
25
45
25
6
10
80
70
25.0
Single
80.0
69.3
100.0
86.6
100
50
90
2
100
HGL20A
Dual - L1/L2
Dual - L3/L4
40.0
40.0
34.7
34.7
50.0
50.0
43.4
43.4
45
45
6
6
80
80
50
All heaters rated single phase 208-230V 60Hz
Wire size based on 60°C (90*C)copper conductor
Wire length based on one way measurement with 2% voltage drop
All models 12kW or larger feature internal circuit breakers All Fuses UL Class K general purpose
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Engineering Design Guide
HTV/HTD/HTH SERIES
Heat Controller, Inc.
Typical Wiring Diagram
HTV/HTD/HTH Units with CXM Board and ECM Fan Motor (single phase)
27
Download from Www.Somanuals.com. All Manuals Search And Download.
08/2011
Download from Www.Somanuals.com. All Manuals Search And Download.
|