Greenheck Fan Ventilation Hood FSDR 511 User Manual

FSDR-511  
Combination Fire Smoke Damper  
Application  
Round Steel Blade  
Model FSDR-511 is a combination fire smoke damper with round style  
blades. The FSDR-511 has been qualified to 3000 fpm (15.2 m/s) and  
4 in. wg (1 kPa) for operation and dynamic closure in emergency fire  
smoke situations. Model FSDR-511 may be installed vertically (with  
blades running horizontal) or horizontally and is rated for airflow and  
leakage in either direction.  
UL 555S Leakage Class I  
UL555 1 1/2 Hour Fire Resistance Rating  
Model FSDR-511 meets the requirements for fire  
dampers, smoke dampers and combination fire  
smoke dampers established by:  
Ratings  
UL 555 Fire Resistance Rating  
Fire Rating: 1 1/2 Hour  
National Fire Protection Association  
NFPA Standards 80, 90A, 92A, 92B, 101, & 105  
IBC International Building Codes  
New York City (MEA listing #260-91-M)  
California State Fire Marshall  
Dynamic Closure Rating: Actual ratings are size dependant  
Maximum Velocity: 3000 fpm (15.2 m/s)  
Maximum Pressure: 4 in. wg (1 kPa)  
UL 555S Leakage Rating  
Leakage Class:  
I
Listing #: 3225-0981:112 (fire)  
Operational Rating: Actual ratings are actuator dependant  
Maximum Velocity: 3000 fpm (15.2 m/s)  
Listing #: 3230-0981:113 (smoke)  
Maximum Pressure: 4 in. wg (1 kPa)  
Maximum Temperature: 350º F (177°C) —Depending on actuator  
“UL CLASSIFIED (see complete marking on  
product)”  
Standard Construction  
“UL CLASSIFIED to Canadian safety standards  
(see complete marking on product)”  
Standard 555 (Listing #R13317)  
Frame/Sleeve: 20 ga. (1mm) galvanized steel round  
Blade: Double skin galvanized steel (14 ga.  
[2mm] equivalent) round style blades  
Standard 555S (Listing #R13447)  
Seal: Extruded silicone rubber blade seals  
Axle: 1/2 in. (13mm) dia. plated steel  
Bearings: Stainless steel sleeve type  
Fusible Link: UL listed 165ºF (74ºC) -not 304SS  
Size Limitations  
Minimum Size: 6 in. (152mm) diameter  
Maximum Size: 24 in. (610mm) diameter  
Optional Features  
• OCI (Open closed indication switches)  
• 165º F (74°C), 212º F (100°C), and 350º F (177°C) RRL available  
• TOR (remote override of 165º F (74°C) closure allows damper to  
perform smoke management functions during a fire emergency)  
• Electric or pneumatic actuators to accomplish smoke management  
and system functions.  
• One retainer plate required, additional retainer plate available.  
• 14 ga. (2mm) or 16 ga. (1.5mm) frame/sleeve  
* Dimensions furnished approximately 1/8 in. (3mm) undersize.  
Opening + 2 in. Min.  
Nut  
Clamping  
Minimum Wall/Floor Opening  
Screw  
Retaining  
Plate Assembly  
= Nominal Dia. + 7/8 in.  
1.00 in. Min. Typ.  
Fasteners  
Clamping Screw  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Grandstream Networks Telephone HANDYTONE 286 User Manual
Grundig Automobile Accessories VCH 3610 User Manual
Grundig DVR 5550 HDD User Manual
Harbor Freight Tools Saw 41146 User Manual
Heath Zenith Home Safety Product SH 5408 User Manual
Hotpoint Microwave Oven AHP67X User Manual
Hotpoint Refrigerator 6936 User Manual
HP Hewlett Packard Welder 53A User Manual
Humax Flat Panel Television LGB 19DRT User Manual
Hunter Fan Outdoor Ceiling Fan 21337 User Manual